OWNER’S
MANUAL
COMMEERCIAL
THERMMOSTAT
P/N33CS400-01
DIGITAL
IGITAL
THERMOSTAT
NON-PROGRAMMABLE
HEAT
COOL
I2:00
Pm
Su
74
HEAT
PUMP
COOL
AUTO
&
HEAT
72
3ConffiguraableOuutputs
Contrroluppto3Heat&
2CoolSStages
BacklitDisplay&Button
Legends
AuxHeatIndicator
DryContactEquipped
SetPointLimiting
AcceptsEZProgrammer
AcceptsOptionalHumidityModule:
ControlsHumidification,
RemoteSensorReady
OutdoorSensorReady
DehumidificationandReheat
AcceptsOptionalIRRemoteControl
Accepts the OPTIONAL
HUMIDITY MODULE
Use with most Air Conditioning & Heating Systems including: 1 or 2 Stage
Electric Cooling & 3 Stage Gas Heating, Heat Pump, Electric or Hydronic Heat.
Carrier Corporation 04/06
Download from Www.Somanuals.com. All Manuals Search And Download.
How to Use TThis MMaanual
The Table of Contents divides the thermostat features into sections
making it easier to quickly find information.
The first page of each section contains a more detailed list of the
contents within that section, such as the example page shown below.
SECTION 14
Timers andd Deaddbbands
Header shows section #
and title of section
Section 14 Contents:
Adjusting the Heat/Cool
Differential..............................14.2
Adjusting the Cycles
Per Hour..................................14.3
Section contents
Adjusting the Deadband..........14.4
Adjusting the Minutes of
Run-Time Before the
14
Next Stage...............................14.6
Selecting 2nd Stage Turn
Visible section tab
on the side of the
page
Off Temperature.....................14.7
Section and page #
Page 14.1
In addition, this manual also has an Index to help you find any information
regarding this thermostat quickly.
Page ii
Download from Www.Somanuals.com. All Manuals Search And Download.
Glossaryy of Terms
Auto-Changeover: A mode in which the thermostat will turn on
the heating or cooling based on room temperature demand.
Configurable Output Jumper: Using jumpers on the thermostat
you can configure the MISC1, MISC2, and MISC3 terminals to
control humidification, dehumidification, and 2nd stage cooling.
Cool Setpoint: The warmest temperature that the space should
rise to before cooling is turned on (without regards to
deadband).
Deadband: The number of degrees the thermostat will wait, once
setpoint has been reached, before energizing heating or cooling.
Dehumidify: To reduce the amount of moisture in the air.
Differential: The forced temperature difference between the
heat setpoint and the cool setpoint.
Heat Setpoint: The coolest temperature that the space should
drop to before heating is turned on (without regards to
deadband).
Humidify: To increase the amount of moisture in the air.
Icon: The word or symbol that appears on the thermostat
display.
Mode: The current operating condition of the thermostat (i.e. Off,
Heat, Cool, Auto).
Non-Programmable Thermostat: A thermostat that does not
have the capability of running the Time Period Programming.
Temperature Swing: Same as Deadband.
Page iii
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of CContents
Quick Start
1
2
Getting to Know Your
Thermostat
Basic Operation
3
Viewing Temperature
and Humidity Sensors
4
Override Operation
5
Programming the
Fan Operation
Thermostat Display
Options
6
7
Humidification
8
Dehumidification
9
Viewing Equipment
Run-Times
Electric Heat and
Heat Pump Operation
10
11
12
13
14
15
16
Timers and Deadbands
Programming Remote
Sensor Operation
Programming the Dry
Contact
Programming the Run-
Time Alerts
Configuring the MISC
Outputs
Factory Defaults,
Calibration, and Sensors 17
Accessories
18
19
Advanced Setup Table
Page iv
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 1
Quickk Start
1
Section 1 Contents:
Selecting the Heat or Cool
Mode............................................1.2
Selecting Your Desired
Temperature................................1.3
Using the Fan Button...................1.3
Note: Following the instructions in this section will allow you to
operate your thermostat using the factory default settings. These
settings are depicted in the illustrations throughout this manual.
Page 1.1
Download from Www.Somanuals.com. All Manuals Search And Download.
Selectting the HHeat or CCoool Mode
1
Select Mode by Pressing the MODE Button
Heating Only
The HEAT setting indicates the
temperature the room has to
reach before the furnace will
turn on to heat the room.
HEAT
Press
70
70
70
70
68
76
MODE
Cooling Only
The COOL setting indicates the
temperature the room has to
reach before the air conditioner
will turn on to cool the room.
COOL
Press
MODE
76
Heating or Cooling
AUTO will automatically select
heat or cool based on room
temperature demand.
COOL
AUTO
HEAT
68
Press
MODE
Off
OFF indicates both heating
and air conditioning
systems are turned off.
OFF
Page 1.2
Download from Www.Somanuals.com. All Manuals Search And Download.
Selectinng Your Deessired Tempperature
(adjussting tthhe setpooints)
1
AUTO MODE
Pressing the UP or DOWN buttons in Auto mode
will adjust both the heat and cool set temperatures
simultaneously.
Adjust the desired
set temperature with the
76
COOL
AUTO
HEAT
70
68
buttons.
HEAT OR COOL MODE
Pressing the UP or DOWN buttons in Heat or Cool mode will
adjust only the heat or cool set temperature.
Adjust the desired
set temperature with the
76
COOL
70
buttons.
Press
Usingg the FFan Button
FAN
Fan On indicates constant fan operation.
If Fan On is selected the fan will run
continuously at all times, except in Off,
and will nly run if there is a heating or
cooling demand in Unoccupied periods.
Pressing the FAN button toggles this
feature on or off.
76
COOL
AUTO
HEAT
70
68
FanOn
Page 1.3
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 2
Gettingg to Knoww YYour Therrmostat
2
Section 2 Contents:
Front Panel Buttons.....................2.2
Display Features...........................2.3
Page 2.1
Download from Www.Somanuals.com. All Manuals Search And Download.
Frontt Panel
2
Warmer Button sometimes referred
glows red) to as the UP button
Backlit LCD Display
[ ]
Carrier
I2:00
Pm
Su
74
COOL
AUTO
HEAT
72
Cooler Button sometimes refer-
(glows blue)
red to as the
[ ]
DOWN button
Override
Button
Heat or Cool Demand Indicator
Red = Heat, Green = Cool
Commercial
Thermostat
74
COOL
AUTO
HEAT
72
MODE HUMIDITY
FAN
OUTSIDE RESET
FILTER
OVER
RIDE
QUICK RELEASE FOR
ACCESSORY PORT
(pg. 18.1)
MODE HUMIDITY
FAN
OUTSIDE
RESET
FILTER
Page 2.2
Download from Www.Somanuals.com. All Manuals Search And Download.
Display FFeatures
2
2
Setup
DeHumidify
88
Service Filter
COOL
Outside
Remote
AUXHEAT
Pan UV Light
AUTO
OFFON
Override
FanOn
I88 88
Mode Indicators - Section 3
Selects the operational mode of the equipment.
HEAT - Indicates the heating mode.
COOL - Indicates the air conditioning mode.
AUTO - Indicates the system will automatically changeover
between heat and cool modes as the temperature varies.
OFF - Indicates heating and cooling is turned off.
Room Temperature Display - Section 4
Indicates the current room temperature and displays the outside
temperature when selected.
Desired Set Temperature - Section 3/4
Indicates desired room temperature(s). Also displays the daily
maximum and minimum outside temperatures.
Outside icon - Section 4
Indicates the temperature displayed is from the optional outside
sensor.
Override icon - Section 5
Indicates the Unoccupied mode of the thermostat is being overriden
for up to 4 hours.
Page 2.3
Download from Www.Somanuals.com. All Manuals Search And Download.
Display FFeatures
2
2
Setup
DeHumidify
88
Service Filter
COOL
Outside
Remote
AUXHEAT
Pan UV Light
AUTO
OFFON
Override
FanOn
I88 88
Setup icon - Sections 6-15
Indicates the thermostat is in the setup mode.
Fan On icon - Section 6
Indicates constant, continuous fan operation. When Fan On is not
lit - indicates the fan will only operate when necessary to heat or to
cool.
Service Filter icon - Section 15
Appears when the filter should be serviced under normal conditions.
Adjustable from 0 - 1950 hours of blower operation.
icon - Section 7
Indicates keypad has been locked.
UV Light icon - Section 10/15
Appears when the UV bulb should be serviced under normal
conditions. Adjustable from 0 - 1950 days of operation.
Remote icon - Pages 4.2, 13.3 & 17.3
Indicates the remote sensor reading of the thermostat is being
viewed.
Page 2.4
Download from Www.Somanuals.com. All Manuals Search And Download.
Display FFeatures
2
Setup
DeHumidify
88
Service Filter
COOL
Outside
Remote
AUXHEAT
Pan UV Light
AUTO
OFFON
Override
FanOn
I88 88
AuxHeat icon - Page 12.4
Indicates 2nd stage electric strip heat is being used when the
thermostat is programmed for Heat Pump operation.
Humidify/DeHumidify icon - Sections 8-9
Indicates the system is currently humidifying/dehumidifying the air.
Service Pan icon - Section 14
Indicates that a sensor (accessory) has detected the condensate
drain pan is full and the compressor (Y1) has been locked out.
Page 2.5
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 3
Basic Opperation
3
Section 3 Contents:
Programming for Auto or
Manual Operation......................3.2
Selecting the Proper
Operating Mode.........................3.3
Selecting Your Desired
Temperature...............................3.5
Note: During setup & programming pressing the UP or DOWN
buttons will modify the flashing selection.
Page 3.1
Download from Www.Somanuals.com. All Manuals Search And Download.
Manuall or Auttoo-Changgeover
Thermmostat
3
When the very simplest operation is desired, this thermostat may
be configured to be a manual heat and cool thermostat. Follow the
step below.
The thermostat may be programmed to function as a Heat Only or
Cool Only thermostat by selecting ‘NO’ in the setup screen below.
This will lockout the Auto-Changeover screen and only allow the Off,
Heat, and Cool screens to be accessed.
Press the MODE button. While holding
MODE
Note: Press the MODE
the MODE, press the HUMIDITY button
button momentarily
HUMIDITY
to move through the
to enter Setup screens.
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
Press the M DE button repeatedly
until this setup screen appears.
MODE
Setup
YES
Select Yes if you would
like the thermostat to
be Auto-Changeover or
No for a Heat Only and
I
AUTO
Cool Only Thermostat.
Press
NO
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 3.2
Download from Www.Somanuals.com. All Manuals Search And Download.
Operatiing Mode whhen the Thheermostat
is Connfiguured to be:
3
MANUAL-CHANGEOVER - If the thermostat is configured to be Manual-
Changeover, the following screens will be available by pressing the
MODE button.
Select the Mode by Pressing the MODE Button
Heating Only
The HEAT setting indicates the
temperature the room has to
reach before the furnace will
turn on to heat the room.
HEAT
70
70
70
68
Press
MODE
Cooling Only
76
COOL
The COOL setting indicates the
temperature the room has to
reach before the air conditioner
will turn on to cool the room.
Press
MODE
Off
OFF indicates both heating
and air conditioning
systems are turned off.
OFF
Page 3.3
Download from Www.Somanuals.com. All Manuals Search And Download.
Operatiing Mode whhen the Thheermostat
is Connfiguured to be:
AUTO-CHANGEOVER - If the thermostat is configured to be Auto-
Changeover, the following screens will be available by pressing
the MODE button.
3
Select the Mode by Pressing the MODE Button
Heating Only
The HEAT setting indicates the
temperature the room has to
reach before the furnace will
turn on to heat the room.
HEAT
70
70
70
70
68
Press
MODE
Cooling Only
76
The COOL setting indicates the
temperature the room has to
reach before the air conditioner
will turn on to cool the room.
COOL
Press
MODE
76
Heating or Cooling
COOL
AUTO will automatically select
heat or cool based on room
temperature demand.
AUTO
HEAT
68
Press
MODE
Off
OFF indicates both heating
and air conditioning
systems are turned off.
OFF
Page 3.4
Download from Www.Somanuals.com. All Manuals Search And Download.
Selectting Yourr Desireed Tempeerrature (aadjustiing setppoints)
AUTO MODE
Pressing the UP or DOWN buttons in Auto mode
3
will adjust both the heat and cool set temperatures
simultaneously. For more information on this see page 12.2.
Adjust the desired
set temperature with the
76
COOL
AUTO
HEAT
70
68
buttons.
HEAT OR COOL MODE
Pressing the UP or DOWN buttons in Heat or Cool modes will
adjust only the heat or cool set temperature.
Adjust the desired
set temperature with the
76
COOL
70
buttons.
Page 3.5
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 4
Viewiing thee Temppeeratuurre and HHumiddiity Sennsors
4
Section 4 Contents:
Viewing the Outside
Temperature..............................4.2
Viewing the Indoor
Humidity....................................4.3
Page 4.1
Download from Www.Somanuals.com. All Manuals Search And Download.
Viewingg the Outsside Tempperature
Requires an outside sensor (optional accessory) to be installed
(see page 13.2 for wiring instructions). To read the temperature
from the outside sensor, press the OUTSIDE button. The display
4
will then show the current outside temperature.
AN
OUTSIDE RESE
FILTE
Press the OUTSIDE
button to view
the Outside
temperature.
The current outside
temperature will be
displayed.
Current outside
temperature.
Outside
This reading is from the
sensor connected to RS2.
83
Press
MODE
This reading is from
the sensor connected
to RS1.
78
HUMIDITY
MAODNE
OUTSIDE RESE
FILTE
Press the OUTSIDE
button to leave the
Outside temperature
screen.
Note: If no sensors are connected 2 dashes [- -] will appear on the display.
Page 4.2
Download from Www.Somanuals.com. All Manuals Search And Download.
Viewinng the Inndoor Huumidity
Requires the Humidity Module (optional accessory) to be installed.
To display the current humidity at the thermostat, press the
HUMIDITY button. The display will then show the current indoor
4
humidity along with the humidification setpoint (Section 8).
Note: The humidity reading will not appear unless the Humidity
Module has been installed. If the Humidity Module has not been
installed dashes will appear in place of the humidity reading.
To view the indoor humidity
HUMIDITY
reading, press the
HUMIDITY button
Setup
Current Room Humidity
40
Humidify
I
0
Press
HUMIDITY
Press the HUMIDITY button
again to return the display
to normal operation.
NOTE: Due to variations in environmental conditions, it is not always possible
to achieve the desired humidification or dehumidification setpoint.
Page 4.3
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 5
Overrride OOperation
Overridding the NNormal Opperation
The OVERRIDE button may only be used when the Dry Contact has
forced the thermostat into the Unoccupied mode.
Unoccupied Operation - During a Dry Contact forced
unoccupied period pressing the OVERRIDE button will
temporarily force the thermostat into the mode it was in before
the Dry Contact forced it into the Unoccupied mode.
For example: If the thermostat was in the Auto mode and the
Dry Contact forced the thermostat into the Unoccupied mode,
then pressing the OVERRIDE button will force the thermostat
back into the Auto mode.
The remaining override time will be displayed in the upper left
hand corner of the display. The override timer can be set up to a
maximum of four (4:00) hours, in increments of 30 minutes. If the
timer has been set for the maximum time, the next press of the
OVERRIDE button will reset the timer, returning the thermostat to
the Unoccupied mode.
To adjust the setpoints for the Unoccupied mode, see page 15.4.
85
COOL
HEAT
Unoccupied
65
65
55
Press
OVERRIDE
:30
AUTO
74
COOL
HEAT
Override
72
Page 5.1
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 6
Prograamming thhe Fan Oppeeration
Section 6 Contents:
6
Using the Fan Button.................6.2
Smart Fan Operation..................6.2
Setting the Fan-Off Time
Delay..........................................6.3
Page 6.1
Download from Www.Somanuals.com. All Manuals Search And Download.
Usingg the FFan Button
When the fan is set for automatic operation it will energize any time
there is a call for heating or cooling, otherwise the fan will remain off.
Pressing the FAN button will energize the fan and display the FanOn
icon on the thermostat display. To operate the fan in the automatic
mode, press the FAN button again and the FanOn icon will disappear.
Press
6
FAN
Fan On indicates constant fan operation.
If Fan On is selected the fan will run
76
continuously at all times, except in Off,
and will only run if there is a heating or
cooling demand in Unoccupied periods.
Pressing the FAN button toggles this
feature on or off.
COOL
AUTO
HEAT
70
68
FanOn
Smartt Fan OOperation
This feature allows the fan to run continuously in Heat, Cool or
Auto mode, and automatically de-energize during dry contact initiated
Unoccupied periods (see page 14.3), except when necessary to
heat or cool. To use this feature, place the thermostat in the Heat,
Cool or Auto mode. Next, press the FAN button to display the
FanOn icon (see below).
Press
FAN
76
COOL
AUTO
HEAT
70
68
FanOn
Page 6.2
Download from Www.Somanuals.com. All Manuals Search And Download.
Settinng the Fann-Off Tiimme Delay
To increase cooling efficiency of your unit, the thermostat may be
programmed to continue running the fan after a call for cooling has
been satisfied. This delay may be set for 30, 60, or 90 seconds. If
the Fan Off Delay is set for zero seconds, the fan will not energize
af er a call for cooling has been satisfied.
6
Press the MODE button. While holding
the MODE, press the HUMIDITY button
to enter Setup screens.
MODE
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
HUMIDITY
MODE
Press the MODE button repeatedly
until this setup screen appears.
Setup
:00
2
Set the Fan Off Delay
to 0, 30, 60, or 90
seconds.
Press
FanOn
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 6.3
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 7
Thermoostat Diisplay OOptions
Section 7 Contents:
Turning On/Off the
7
Backlight...................................7.2
Programming the Thermostat
to Display Temperature in
Fahrenheit or Celsius..............7.2
Locking/Unlocking the
Keypad......................................7.3
Programming a Security
Level..........................................7.4
Page 7.1
Download from Www.Somanuals.com. All Manuals Search And Download.
Turningg On/Offf the Baccklight
Press the MODE button. While holding
the MODE, press the HUMIDITY button
to enter Setup screens.
MODE
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
HUMIDITY
Press the MODE button repeatedly
until this setup screen appears.
MODE
7
Setup
3
Select backlight operation:
ON - Light continuously.
OFF - Light for 8 seconds
after a button press.
ON
Press
MODE
Progrrammiing the Theermostat tto Dissplay
Temperatture in Fahhrenheit oor Celsius
Setup
4
Select thermostat
operation in degrees
Fahrenheit or Celsius.
F
Press
f
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 7.2
Download from Www.Somanuals.com. All Manuals Search And Download.
Lockinng/Unloccking thhee Keypad
To prevent unauthorized use of the thermostat, the front panel
buttons may be disabled. To disable, or ‘lock’ the keypad, press
and hold the MODE button. While holding the MODE button,
press the UP and DOWN buttons together. The
appear on the display, then release the buttons.
icon will
7
Press all three
buttons in the order
outlined above for
keypad lockout
85
COOL
AUTO
HEAT
MODE
65
icon will disappear from the display, then
55
To unlock the keypad, press and hold the MODE button. While
holding the MODE button, press the UP and DOWN buttons
together. The
release the buttons.
Page 7.3
Download from Www.Somanuals.com. All Manuals Search And Download.
Programmming a SSecuritty Level
When a security level has been programmed, the thermostat will allow
limited adjustment to the setpoints (steps # 6 and 7). In security
levels 2 and 3, the thermostat is forced into the Program On mode.
To disable the security feature, set the value in step #5 to 0; this will
cause steps # 6 and 7 not to appear.
Press the MODE button. While holding
the MODE, press the HUMIDITY button
to enter Setup screens.
MODE
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
7
HUMIDITY
Press the MODE button repeatedly
until this setup screen appears.
MODE
Setup
Select the security level:
0=No security in effect
1=Setpoint range limited
2=1+ locked in current
mode.
5
Press
3=2 + prohibits setpoint
changes
0
MODE
Step #6 appears only
if step #5 is not 0.
Setup
HI
6
Adjust the maximum
allowable heat setpoint
when security is in effect.
HEAT
(35 - 99 )
Press
80
65
MODE
Step #7 appears only
if step #5 is not 0.
Setup
Adjust the minimum
allowable cool setpoint
when security is in effect.
7
COOL
(35 - 99 )
LO
Press
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons are
presse , the display will leave the setup screens after 30 seconds.
Page 7.4
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 8
Humidiffication
Section 8 Contents:
Installing the Humidity
Module.......................................8.2
8
Setting a Thermostat Jumper
for Humidity Operation............8.3
Adjusting the Humidification
Setpoint.....................................8.4
NOTE: The humidification functions described in this section will
only be available if a Humidity Module has been properly installed.
Disclaimer:
The manufacturer of this thermostat cannot be liable for
misinstallation, improper connection or improper programming
the humidity functions of this thermostat that may result in water
damage or mold growth.
f
Additionally, the manufacturer of this thermostat is not responsible
for the fitness of the humidifier and/or installation of said humidifier
connected to this thermostat. Furth rmore, the maintenance of the
humidifier components, including but not limited to, the filters and
pads are not the responsibility of the thermostat manufacture .
The Humidifier Service icon is only a suggestive reminder and
should not take the place of the humidifier manufacturer’s
required maintenance requirements and schedule.
Page 8.1
Download from Www.Somanuals.com. All Manuals Search And Download.
Installling thee HHumidityy Module
To install the Humidity Module the thermostat must be detached
from the back plate. Plug the Humidity Module into the Humidity
Module connector as shown in Figure 2 below. Follow the detailed
instructions included with the Humidity Module accessory. Once the
Humidity Module has been installed, you must adjust the Humidity
jumper setting to HUM as shown in Figure 1 below. This will allow
you to access the humidification and dehumidification setup steps.
For proper humidity operation, this
jumper must be set for HUM.
Figure 1
8
Back of 33CS400-01
HUM
OR
ELEC
GAS
HP
HUM
DEHUM
ECON
GAS
NO HUM
Y2
(MISC1
ONLY)
B
MISC3 MISC2 MISC1
O
W1
W2
Y1
G
MISC1
RS2
MISC2
CK1
CKGND
R
MISC3
RS+5
Rs1
I
MOD
EL
RSGND
C
Install the Humidity Module
(see Humidity Module Instruction
Sheet for more detailed information).
Figure 2
Humidity Module
Plug located on
the Thermostat
Circuit Board.
Humidity Module
Thermostat Circuit
Board.
Page 8.2
Download from Www.Somanuals.com. All Manuals Search And Download.
Settingg a Thermmoostat Jummper for
Humiddity OOperation
To control a MISC output for humidification, place the MISC1, MISC2,
or MISC3 jumper on the terminal labeled HUM (see diagram below).
This will supply 24VAC to the selected MISC terminal based on the
humidification programming in the following pages. Only one of the
three outputs (MISC1, MISC2, or MISC3) is required to have this
jumper. For more information regarding the MISC1, MISC2, and
MISC3 outputs, please see Section 16.
8
In the diagram below, the MISC3 jumper
has been set for HUM (humidify) operation.
ELEC
GAS
HP
HUM
GAS
DEHUM
B
MISC3 M
O
HUM
W1
W2
Y1
G
MISC1
Rs2
DEHUM
MISC2
CK1
CKGND
R
MISC3
RS+5
Rs1
IN
MOD
EL
RSGND
MISC3
C
IMPORTANT CAUTION
NEVER PUT MORE THAN ONE JUMPER
ON THE SAME MISC JUMPER BLOCK!
THIS MAY DAMAGE THE THERMOSTAT
AND VOID YOUR WARRANTY
MISC1
MISC1
OK
Page 8.3
Download from Www.Somanuals.com. All Manuals Search And Download.
Adjustinng thee Humiddificcationn Setpoint
If your HVAC unit is equipped with a humidification system and the
Humidity Module has been installed, the thermostat will provide power
to the appropriate terminal on the backplate of the thermostat when
the humidity in the home falls below the setpoint you have chosen.
The value for this setpoint ranges from 0% to 60%.
NOTE: Due to variations in environmental conditions, it is not always possible
to achieve the desired humidification or dehumidification setpoint.
8
NOTE: Each step # is located at
the top right corner of the
display for easy reference.
Press the HUMIDITY
button to enter the
Humidity Setup screen.
HUMIDITY
Current Room Humidity
Setup
40
Humidify
I
Adjust the desired
humidification setpoint
(0%-60%)
Press
HUMIDITY
0
Press the HUMIDITY button to leave the
Humidity Control screens (if no buttons are
pressed, the display will leave the Humidity
Control screens after 30 seconds).
Humidification Notes: Press the
button to set the humidity
setpoint to 0% for no humidification operation.
You cannot set the dehumidify setpoint any lower than the humidify setpoint; a
5% differential is forced between the humidify and dehumidify setpoints.
Page 8.4
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 9
Dehumidiificaation
Section 9 Contents:
Configuring a Thermostat Output
Jumper for Dehumidification
Operation...................................9.2
9
Adjusting the Dehumidification
Setpoint......................................9.3
Using Your Air Conditioner
to Dehumidify............................9.4
Using the DEHUM
Terminal.....................................9.5
NOTE: The dehumidification functions described in this section will
only be available if a Humidity Module has been properly installed.
For instructions on installing the Humidity Module please see age 8.2.
Page 9.1
Download from Www.Somanuals.com. All Manuals Search And Download.
Settingg a Thermmoostat Jummper for
Dehumiddificattion Opeeration
To control a MISC output for dehumidification, install the Humidity
Module and place the Humidity Jumper on HUM (see page 8.2).
Then place the MISC1, MISC2, or MISC3 jumper on the terminal
labeled DEHUM (see diagram below). This will supply 24VAC to the
selected MISC terminal based on the programming in the following
pages. Only one of the three outputs (MISC1, MISC2, or MISC3) is
required to have a jumper. For more information regarding the
MISC1, MISC2, and MISC3 outputs, please see section 16.
9
In the diagram below, the MISC2 jumper has
been set for DEHUM (dehumidification) operation.
ELEC
GAS
HP
HUM
GAS
DEHUM
B
MISC2
O
HUM
W1
W2
Y1
G
MISC1
Rs2
DEHUM
MISC2
CK1
CKGND
R
MISC3
RS+5
Rs1
IN
MOD
EL
RSGND
MISC2
C
IMPORTANT CAUTION
NEVER PUT MORE THAN ONE JUMPER
ON THE SAME MISC JUMPER BLOCK!
THIS MAY DAMAGE THE THERMOSTAT
AND VOID YOUR WARRANTY
MISC1
MISC1
OK
Page 9.2
Download from Www.Somanuals.com. All Manuals Search And Download.
Adjusstingg the Dehumiidifiicatiioon Setpoint
Dehum Terminal: If a MISC terminal selected for DEHUM operation
(see page 9.2) then the thermostat will provide power to this terminal
the when the humidity in the home is above the setpoint you have
chosen. See page 9.6 for detailed programming instructions. To utilize
this feature your HVAC unit must be equipped with a DEHUM terminal.
Cool to Dehumidify: If the thermostat is programmed for Cool to
Dehumidify operation, then the thermostat will energize the cooling
system any time the humidity in the home is above the setpoint you
have chosen. See page 9.4 for detailed programming instructions.
In each case, when the indoor humidity falls below the setpoint you
have selected, Cool to Dehumidify and the MISC terminal will be
de-energized. The value for this setpoint ranges from 25% to 99%.
9
NOTE: Due to variations in environmental conditions, it is not always
possible to achieve the desired humidification or dehumidification setpoint.
Press the HUMIDITY button
HUMIDITY
NOTE: Each step # is located at
to enter the Humidification
the top right corner of the
Setup screens.
display for easy reference.
MODE
Press the MODE button once
Setup
Current Room Humidity
ON / +
40
DeHumidify
2
Adjust the desired
dehumidification setpoint
Press
(25%-99%)
HUMIDITY
OFF / -
99
Press the HUMIDITY button to leave the Humidity
Control screens (if no buttons are pressed, the display
will leave the Humidity Control screens after 30 seconds).
Dehumidification Notes: Press the
button to set the
dehumidification setpoint to 99% for no dehumidification operation.
This will lockout Advanced Setup steps 8 and 9 (see page 9.4).
You cannot set the dehumidify setpoint any lower than the humidify setpoint; a
5% differential is forced between the humidify and dehumidify setpoints.
Page 9.3
Download from Www.Somanuals.com. All Manuals Search And Download.
Using Yourr Air CCondiittionerr to Deehumidify
If Cool to Dehumidify is on and the Humidity Module is installed,
the thermostat has the ability to initiate a cooling cycle for advanced
dehumidification operation. When the thermostat detects the humidity
percentage is above the setpoint for dehumidification, and heating or
cooling is not on, the thermostat will force the compressor to run with
the fan, thus reducing moisture in the air. The green LED will blink
once every eight seconds to indicate this is taking place. This feature
will also allow you to adjust the cooling overshoot of the setpoint, from
0° to 5° (adjustable in step #9). For Example: If the cooling overshoot is
set for 3°F and the cooling setpoint is set for 74°F, then as long as the room
temperature reads between 71°F and 74°F this feature will energize the
compressor and fan to dehumidify the air.
Note: Press the MODE
Press the MODE button. While holding
the MODE, press the HUMIDITY button
to enter Setup screens.
9
MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
HUMIDITY
Press the MODE button repeatedly
until this setup screen appears.
MODE
Steps 8 and 9 only appear if the Dehumidification
setpoint is not 99% (see page 9.3).
Setup
On
DeHumidify
8
Select Cool to
Dehumidify feature.
OFF
Press
Off
MODE
Step 9 appears only if step 8 is set to “ON”
Setup
DeHumidify
9
Adjust the maximum
overshoot of the set
temperature in Cool to
Dehumidify mode.
COOL
Press
HUMIDITY
(0 - 5 )
3
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Dehumidification Notes: The thermostat must be in the Cool or Auto
mode for the Cool to Dehumidify feature to be available.
Page 9.4
Download from Www.Somanuals.com. All Manuals Search And Download.
Using tthe Dehhum Terrminal
If you configure a MISC output jumper for DEHUM, it may be
programmed to operate in one of two ways:
1) Normally Closed (NC): The thermostat will de-energize the
DEHUM terminal to allow the fan to run in low speed when there
is a call for 1st stage cooling and the room humidity is greater than
the dehumidification setpoint.
2) Normally Open (NO): The thermostat will energize the DEHUM
terminal to allow the fan to run in low speed when there is a call
for 1st stage cooling only and the room humidity is greater
than the dehumidification setpoint.
9
Note: Press the MODE
button momentarily
Press the MODE button. While holding
MODE
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
the MODE, press the HUMIDITY button
to enter Setup screens.
HUMIDITY
MODE
Press the MODE button repeatedly
until this setup screen appears.
Setup
NC
NO
Normally Closed (NC) =
DEHUM de-energized for
low speed fan.
DeHumidify
I0
Normally Open (NO) =
DEHUM energized for
low speed fan.
Press
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Dehumidification Notes: The DEHUM terminal will “release” and allow
the fan to operate normally if there is call for 2nd stage cooling or if the call
for Cooling and/or Cool to Dehumidify has been satisfied.
Page 9.5
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 10
Viewingg Equipmment Runn-Times
Section 10 Contents:
Viewing the Override
Run-Time.................................10.2
Viewing the Humidifier
Run-Time................................ 10.3
10
Viewing the UV Light
Run-Time.................................10.4
Page 10.1
Download from Www.Somanuals.com. All Manuals Search And Download.
Viewing thhe Oveerriddee Operaationn Run-Time
This display will track the number of hours that your thermostat has
been operating in the Override mode (see page 5.1). Press the FAN
button to reset the counter.
Press the MODE button. While holding
the MODE, press the HUMIDITY button
to enter Setup screens.
MODE
Note: Press the MODE
button momentarily
HUMIDITY
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
Press the MODE button repeatedly
until this setup screen appears.
MODE
Setup
0
Counts the number of
hours Override has
Press
10
I i
been active. Press FAN
to reset the Override Run-
Time counter.
FAN
Override
Press
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 10.2
Download from Www.Somanuals.com. All Manuals Search And Download.
Viewing tthe Humidiificationn Run-Time
After your humidification system has been operating for the number of
days set in step #12 below, the Service Humidify icon will appear. This
counter keeps track of the number of days since the Service Humidify
icon was reset.
Press the MODE button. While holding
the MODE, press the HUMIDITY button
to enter Setup screens.
MODE
Note: Press the MODE
button momentarily
HUMIDITY
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
Press the MODE button repeatedly
until this setup screen appears.
MODE
10
Setup
Counts the number of
0
days the humidifier has
been running. Press
FAN to reset the
Service Humidify
counter and remove the
icon from the display.
Humidify
Press
I2
Service
FAN
Press
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 10.3
Download from Www.Somanuals.com. All Manuals Search And Download.
Viewingg the UV LLight Ruun-Time
After the UV light has been operating for the number of days set in
step #13 below, the Service UV Light icon will appear. This counter
keeps track of the number of days since the UV light icon was last
reset.
Press the MODE button. While holding
MODE
Note: Press the MODE
the MODE, press the HUMIDITY button
button momentarily
HUMIDITY
to enter Setup screens.
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
Press the MODE button repeatedly
until this setup screen appears.
MODE
10
Setup
0
UV Light
Counts the number of days
Press
I3
Service
since the UV Light was last
reset. Press FAN to reset
the Service UV Light counter
and remove the icon from the
display.
FAN
Press
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 10.4
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 11
Electricc Heat and HHeat Pump OOperation
Section 11 Contents:
Viewing the Heat Pump and
Reversing Valve Jumper
Setting.....................................11.2
Viewing the Electric Heat
11
Jumper Setting.......................11.3
Using Emergency Heat............11.4
Page 11.1
Download from Www.Somanuals.com. All Manuals Search And Download.
Viewinng the HHeat Puump and
Reversiing Valvee Jumper SSettings
Steps 14 and 15 are ‘Read Only’ and may only be set with the
jumpers on the circuit board of the thermostat.
Press the MODE button. While holding
the MODE, press the HUMIDITY button
to enter Setup screens.
MODE
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
HUMIDITY
MODE
Press the MODE button repeatedly
until this setup screen appears.
Setup
11
I4
I5
ON = Heat Pump
operation
OFF = Gas Electric
operation
OFF
Press
Setup
MODE
Indicates that the
thermostat jumper
is set for an O
reversing valve
(energize in cooling)
or a b reversing valve
(energize in heating).
Press
O
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 11.2
Download from Www.Somanuals.com. All Manuals Search And Download.
Viewing thhe Eleectriicc Heat JJumpeer Setting
Placing the jumper on ELEC will cause the thermostat to turn on the
fan immediately any time there is a heat demand. Since most gas
furnaces control the fan, this feature should be off unless it is
necessary for the thermostat to energize the fan with first stage heat.
Step 16 is ‘Read Only’ and may only be set with the jumpers on the
circuit board of the thermostat.
Note: Press the MODE
button momentarily
to move through the
Press the MODE button. While holding
the MODE, press the HUMIDITY button
to enter Setup screens.
MODE
setup screens. Press
HUMIDITY
and hold the MODE
button to move back-
wards through the
setup screens.
Press the MODE button repeatedly
until this setup screen appears.
MODE
11
Setup
ON indicates that the
I6
thermostat jumper is
set for Electric Heat
operation, or OFF for
Gas/Electric or Heat
Pump operation.
OFF
Press
EH
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 11.3
Download from Www.Somanuals.com. All Manuals Search And Download.
Using Emerrgenccyy Heat
ENTER EMERGENCY HEAT: Only available if you have a Heat Pump
installed. To initiate the Emergency Heat feature, press the FAN
button. While holding the FAN button press the UP button. The
Cool setpoint display will read ‘EH’ (emergency heat).
Press for
Emergency Heat
HEAT
73
74
FAN
11
OPERATION: During Emergency Heat operation the
thermostat will turn on the fan and the 2nd stage of heat
when there is a demand for heat. Also during Emergency
Heat the 1st stage of heating or cooling will be unavailable.
EXIT EMERGENCY HEAT: Follow the same steps as entering
Emergency Heat by pressing the FAN and UP buttons. During
Emergency Heat, only OFF and HEAT modes are available by
pressing the MODE button.
Page 11.4
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 12
Timers andd Deaddbbands
Section 12 Contents:
Adjusting the Heat/Cool
Differential..............................12.2
Adjusting the Cycles
Per Hour..................................12.3
Adjusting the Deadband..........12.4
12
Selecting 2nd Stage Turn
Off Temperature.....................12.6
Page 12.1
Download from Www.Somanuals.com. All Manuals Search And Download.
Adjusstingg the Heat//Cool Diffferenntial
The Heat and Cool setpoints will not be allowed to come any closer to
each other than the value in this step. This minimum difference is
enforced during Auto-Changeover operation.
Press the MODE button. While holding
the MODE, press the HUMIDITY button
to enter Setup screens.
MODE
Note: Press the MODE
button momentarily
HUMIDITY
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
Press the MODE button repeatedly
until this setup screen appears.
MODE
Setup
Adjust the minimum
difference between
cooling & heating
setpoints.
I7
COOL
HEAT
(0 - 6 )
Press
12
2
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons
are pressed, the display will leave the setup screens after 30 seconds.
Note: To increase the spread between the heating and cooling
setpoints, press the MODE button until only the heat setpoint is
displayed. Adjust the desired setpoint. Wait two seconds after
adjusting the set point so the thermostat can accept the change.
Press the MODE button until only the cool setpoint is displayed.
Adjust the desired setpoint. Wait two seconds after adjusting the
set point so the thermostat can accept the change. Press the
MODE button again to enter the Auto-Changeover mode where
both the heat and cool setpoints are displayed.
Page 12.2
Download from Www.Somanuals.com. All Manuals Search And Download.
Adjustiing the CCycles PPer Hour
The Cycles Per Hour setting may limit the number of times per hour
your HVAC unit may energize. For example, at a setting of 6 cycles
per hour the HVAC unit will only be allowed to energize once every 10
minutes. The Cycles Per Hour limit may be overridden and reset by
pressing the UP or DOWN buttons on the thermostat.
Press the MODE button. While holding
MODE
Note: Press the MODE
the MODE, press the HUMIDITY button
button momentarily
HUMIDITY
to enter Setup screens.
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
Press the MODE button repeatedly
until this setup screen appears.
MODE
Setup
Select the cycles per
hour limit.
d=cycles per hour
limit defeated.
I8
12
d1=d + defeat 5 min.
compressor lockout.
Press
6Cy
(d1, d, 2 - 6)
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 12.3
Download from Www.Somanuals.com. All Manuals Search And Download.
Adjussting tthe Deaadband
MULTI-STAGE OPERATION - Controls up to two Heat and two Cool
stages.
The 2nd Stage of heat or cool is turned on when:
(A) The 1st Stage has been on for the two minutes.
And
(B) The temperature spread from the setpoint is equal to or greater
than: the setpoint plus the 1st stage deadband (step #19, next
page), plus two degrees.
Heating
Deadband
Cooling
Deadband
Deadband
Deadband
db 2
(adj. 0-10 )
db 1
(adj. 1-6 )
db 1
(adj. 1-6 )
db 2
(adj. 0-10 )
2nd Stage
turn on
1st Stage
turn on
Heat
Cool
1st Stage
turn on
2nd Stage
turn on
12
Setpoint Setpoint
DECREASE
INCREASE
TEMPERATURE
Page 12.4
Download from Www.Somanuals.com. All Manuals Search And Download.
Adjussting tthe Deaadband
For more detailed information, please see the explanation on the
previous page.
Press the MODE button. While holding
the MODE, press the HUMIDITY button
to enter Setup screens.
MODE
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
HUMIDITY
MODE
Press the MODE button repeatedly
until this setup screen appears.
Setup
Adjust the deadband
for the 1st stage.
I9
12
(1 - 6 )
Press
2
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 12.5
Download from Www.Somanuals.com. All Manuals Search And Download.
Selectting 2nnd Stagge Turn
Off Tempperature
If ON is selected, the second stage of cooling or heating will remain
energized until the thermostat reaches the setpoint on the thermostat
display.
If OFF is selected, the second stage of cooling or heating will turn off
after reaching the 1st stage deadband (see page 12.4 for more
information).
Press the MODE button. While holding
MODE
Note: Press the MODE
the MODE, press the HUMIDITY button
button momentarily
HUMIDITY
to enter Setup screens.
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
Press the MODE button repeatedly
until this setup screen appears.
MODE
12
Setup
On
Off
Select On or Off:
On - 2nd stage will
remain on until
setpoint is reached.
Off - 2nd stage will
turn off after reaching
1st stage deadband.
20
OFF
Press
2
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 12.6
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 13
Programmming Remotte Sensor OOperation
Section 13 Contents:
Installing the Remote
Sensors...................................13.2
Controlling or Reading the
Remote Temperature (RS1)...13.3
13
Page 13.1
Download from Www.Somanuals.com. All Manuals Search And Download.
Installling thee Remotee SSensors
One wired or up to eight wireless remote sensors may be installed on
the thermostat (RS1) to control the temperature in another room. If
more than one wireless sensor is used on RS1, the thermostat will ave-
rage the sensors to determine the displayed temperature reading. One
wired or wireless remote sensor may be installed to read the outside
temperature (RS2). If a sensor is connected to RS1 and is program-
med to control the thermostat, the degree icon on the thermostat will
blink once per second to indicate that a remote sensor reading is being
displayed. The wired sensor can be connected to the thermostat with
up to 150’ of 18 ga., 300’ of 20 ga., or 450’ of 22 ga. unshielded,
thermostat wire. The wired sensor can be connected to the therm-
ostat using a two or three wire installation. If a two wire installation is
required, then RS+5 must be connected to RSGND (see below).
This wire MUST be completely separated from the thermostat or
any other control wiring and must NOT be in the same conduit
as high voltage wiring.
13
W2
MISC1
Rs2
W1/O/B
Y1
G
MISC3
RS+5
RS1
MISC2
CK1
CKGND
R
RSGND
C
RS-GND
RS-GND
RS
RS
RS
RS
RS1
RS2
See the Remote Sensor accessory for further details.
Page 13.2
Download from Www.Somanuals.com. All Manuals Search And Download.
Controollingg oor Readiing the
Remotte Tempeeraturree (RS1)
The thermostat may be programmed to only READ the remote sensor,
or to CONTROL to the remote sensor. Refer to Advanced Setup step
#21, below.
Read Only Sensor (RS1): If step #21 is set to only READ to the
remote sensor, this temperature may be viewed by pressing the
OUTSIDE button on the thermostat and then pressing the MODE
button (see page 4.2).
Control Sensor (RS1): If step #21 is set to CONTROL to the remote
sensor, the thermostat will ignore the reading of its internal
temperature sensor and only display the temperature reading from
the remote sensor. The degree icon on the thermostat will blink
once per second to indicate that a remote sensor reading is being
displayed.
13
Press the MODE button. While holding
the MODE, press the HUMIDITY button
MODE
Note: Press the MODE
HUMIDITY
button momentarily
to enter Setup screens.
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
Press the MODE button repeatedly
until this setup screen appears.
MODE
Setup
YES
Optional Remote Sensor:
YES = Control to Remote
Sensor RS1.
NO = Read Only Remote
Sensor RS1.
2 i
Remote
Press
NO
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 13.3
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 14
Prograamming tthe Dry CContact
Section 14 Contents:
Dry Contact Operation............ 14.2
Dry Contact Polarity.................14.2
Dry Contact Programming.......14.3
Override Operation...................14.4
Random Start............................14.5
14
Page 14.1
Download from Www.Somanuals.com. All Manuals Search And Download.
Dry Coontacctt Operaation
If the dry contact is going to be used, select YES in step #22 below; if
the dry contact is not going to be used, select NO. in step #22 below.
DRY CONTACT POLARITY - The terminals may be set to be
Normally Open (NO) or Normally Closed (NC) in step #23.
If NO is selected the dry contact will operate when it is forced
closed. If NC is selected, the dry contact will operate until it is
forced open.
Press the MODE button. While holding
the MODE, press the HUMIDITY button
to enter Setup screens.
MODE
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
HUMIDITY
MODE
Press the MODE button repeatedly
until this setup screen appears.
Setup
YES
22
23
Set to YES if the dry
contact will be used.
Set to NO if the dry
contact will not be used.
14
Press
NO
MODE
Step 23 appears only if step 22 is “YES”.
Setup
NC
Dry Contact Polarity:
Normally Closed (NC)
Normally Open (NO)
Press
HUMIDITY
NO
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 14.2
Download from Www.Somanuals.com. All Manuals Search And Download.
Dry Conntact PPrograamming
OVERRIDE OR SERVICE THE CONDENSATE DRAIN PAN - If
Override is selected in step #24 (below), when the dry contact is
energized the thermostat will be forced into or out of Unoccupied
setpoints (next page) depending on the polarity of the Dry Contact.
If Service Pan is selected, when the dry contact is energized the
thermostat will lockout Y1 (compressor) and write Service Pan on
the display.
Press the MODE button. While holding
the MODE, press the HUMIDITY button
to enter Setup screens.
MODE
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
HUMIDITY
MODE
Press the MODE button repeatedly
until this setup screen appears.
Step 24 appears only if step 22 is “YES”.
Service Pan
Select Service Pan to
lockout Y1 when the dry
contact is energized.
Select Override to enable
Override setpoints when
the dry contact is energized.
Setup
24
Press
HUMIDITY
Override
Override
14
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
NOTE: If Service Pan is selected and the dry contact was closed at least once, the
Service Pan icon will remain on the display to alert the user that a problem has
occurred. This icon will be cleared once a button is pressed.
Override
Service Pan
W2
MISC1
RS2
MISC3
RS+5
RS1
W1/O/B
Y1
G
MISC2
CK1
CKGND
R
OR
W2
MISC1
Rs2
MISC3
RS+5
RS1
W1/O/B
Y1
G
MISC2
CK1
CKGND
R
RSGND
RSGND
C
C
Connect wires to a device that
will complete the circuit betw-
een CK1 and CKGND when the
Condensate Drain Pan is full.
Connect wires to a time
clock or other device to
force the thermostat into
or out of Unoccupied.
Page 14.3
Download from Www.Somanuals.com. All Manuals Search And Download.
Dry Conntact PPrograamming
UNOCCUPIED SETPOINTS - If Override is selected in step #24 (see
previous page), when the dry contact is energized the thermostat
will be forced into or out of Unoccupied setpoints. To adjust the
Unoccupied setpoints follow the setup steps below.
Press the MODE button. While holding
the MODE, press the HUMIDITY button
to enter Setup screens.
MODE
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
HUMIDITY
MODE
Press the MODE button repeatedly
until this setup screen appears.
Setup
25
Adjust the cooling
setpoint for unoccupied
periods.
COOL
Unoccupied
(35 - 99, OF )
Press
85
MODE
14
Setup
26
Adjust the heating set-
point for Unoccupied
periods.
HEAT
Unoccupied
(OF, 35 - 99 )
55
Press
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 14.4
Download from Www.Somanuals.com. All Manuals Search And Download.
Randoom Starrt Operration
This feature causes a 2 to 30 second delay before energizing
the thermostat outputs after any of these events:
Loss of Power to the thermostat: When power to the thermostat
is interrupted and then restored, Random Start will lockout the
outputs of the thermostat for a random amount of time. This
delay helps to keep multiple thermostats from energizing their
outputs at the same time after a power outage.
Closure of the Dry Contact to force Heat, Cool or Auto Modes:
If step #24 (page 14.3) is programmed for Override, then
Random Start will lockout all outputs of the thermostat for a
random amount of time when a Dry Contact closure occurs
(depending on step #23, page 14.2). This delay helps to keep
multiple thermostats from energizing their outputs each time the
Dry Contact is used.
14
Page 14.5
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 15
Programmming Ruun-Timee Alerts
Section 15 Contents:
Setting and Resetting the
Service Filter (Fan Run-Time)
Alert........................................15.2
Setting and Resetting the UV
Light Run-Time Alert.............15.3
Setting and Resetting the
Humidify Run-Time Alert......15.4
15
Page 15.1
Download from Www.Somanuals.com. All Manuals Search And Download.
How to Sett and Resett the Serviice Filter
(Fan Run-TTime)) AAlert
This counter keeps track of the number of hours of fan run-time
whether the fan is energized in the Heating or Cooling modes, or in
stand alone fan operation. The Service Filter icon will appear after the
preset number of hours of fan run-time in step #28 (below) has been
achieved. Setting this counter to zero in step #28 will prevent the
Service Filter icon from ever appearing.
Note: Press the MODE
button momentarily
to move through the
setup screens. Press
Press the RESET FILTER button
to enter this setup screen.
RESET
FILTER
and hold the MODE
button to move back-
wards through the
setup screens.
Hours the fan has
run since last reset
Setup
0
Press
27
Service Filter
Reset the counter to 0 to
remove the Service Filter
icon from the display.
FAN
Press
MODE
Setup
0
Adjust the number of
15
28
hours, in increments of
50, the fan will run
before the Service
Filter icon appears on
the display. 0 = off.
Service Filter
Press
HUMIDITY
(0 - 1950 hours)
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 15.2
Download from Www.Somanuals.com. All Manuals Search And Download.
How to SSet and Reeset thee UUV Light
Run-Timme Alert
This counter keeps track of the number of days since the UV Light
counter has been reset. The UV Light icon will appear after the
number of days has been achieved, as shown in step #29 (below).
Setting the counter to zero in Step #29 will prevent the Service UV
Light icon from ever appearing.
Press the MODE button. While holding
MODE
Note: Press the MODE
the MODE, press the HUMIDITY button
to enter Setup screens.
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
HUMIDITY
MODE
Press the MODE button repeatedly
until this setup screen appears.
Days since the UV Light
icon has been reset
Setup
0
Press
I3
Service
UV Light
Reset the counter to 0 to
remove the Service UV
Light icon from the display.
FAN
15
Press the MODE button repeatedly
until this setup screen appears.
MODE
Setup
0
UV Light
29
Adjust the number of days
in increments of 10 before
the UV Light icon appears
on the display. 0 = off.
Service
Press
(0 - 1990 days)
HUMIDITY
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
Page 15.3
Download from Www.Somanuals.com. All Manuals Search And Download.
How to Sett and Reseet the Hummidifier
Run-Timme Alert
This counter keeps track of the number of days since the Service
Humidify icon was last reset; this icon will appear after the number of
days set in step #30 (below) has elapsed. Setting this counter to zero
in step #30 will prevent the Service Humidify icon from ever appearing.
Press the MODE button. While holding
MODE
Note: Press the MODE
the MODE, press the HUMIDITY button
to enter Setup screens.
button momentarily
to move through the
setup screens. Press
and hold the MODE
button to move back-
wards through the
setup screens.
HUMIDITY
MODE
Press the MODE button repeatedly
until this setup screen appears.
Days since the last reset
of the Service Humidify
counter.
Setup
0
Humidify
I2
Service
Reset the counter to 0 to
remove the Service Humidify
icon from the display.
Press
FAN
Press the MODE button repeatedly
until this setup screen appears.
MODE
15
Setup
0
Adjust the number of days
Humidify
30
Service
in increments of 10 before
the Service Humidify icon
appears.
Press
0 = Off
HUMIDITY
(0 - 1990 days)
Press the HUMIDITY button to leave the Setup screens. If no buttons are
pressed, the display will leave the setup screens after 30 seconds.
The humidifier run-time alert does not take the place of
any humidifier manufacturer’s recommended maintenance
plan; it only serves as a helpful reminder.
Page 15.4
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 16
Configuuring thhe MISC OOutputs
Section 16 Contents:
Configuring the Jumpers........16.2
Explanation of Jumper
Settings..................................16.3
16
Page 16.1
Download from Www.Somanuals.com. All Manuals Search And Download.
Configguringg the Juumpers
For additional flexibility, your thermostat has three configurable
outputs. These outputs are designed to have different functions
depending on how the jumpers are set (below).
Each output, labeled MISC1, MISC2, and MISC3 may be set for one
of the four choices available.
In the diagram below, the MISC3 jumper has been set for HUM*
(humidification) operation, the MISC2 jumper has been set for
DEHUM* (dehumidification) operation, and the MISC1 jumper has
been set for Y2 (second stage cooling) operation.
ELEC
GAS
HP
HUM
DEHUM
ECON
GAS
Y2
(MISC1
ONLY)
B
MISC3 MISC2 MISC1
O
HUM
DEHUM
ECON
W1
W2
Y1
G
MISC1
RS2
MISC2
CK1
CKGND
R
MISC3
RS+5
Rs1
Y2
(MISC1
ONLY)
IN
MOD
EL
RSGND
MISC3 MISC2 MISC1
C
*The Humidity Module (sold separately)
must be installed to operate a humid-
ification and/or dehumidification system.
16
CAUTION
NEVER PUT MORE THAN
ONE JUMPER ON THE SAME
MISC JUMPER BLOCK!
DOING SO MAY DAMAGE
YOUR THERMOSTAT.
MISC3
MISC3
Page 16.2
Download from Www.Somanuals.com. All Manuals Search And Download.
Explanaation off JJumper Seettings
HUM JUMPER SETTING
If the jumper for MISC1, MISC2, or MISC3 is set to HUM, the corresponding MISC screw
terminal on the backplate will control a humidification system.
HUMIDIFICATION OPERATION - SECTION 8
If your HVAC unit is equipped with a humidification system and the Humidity
Module (sold separately) has been installed, the thermostat will provide power
to the MISC1, MISC2, or MISC3 terminal of the thermostat when the humidity in
the home falls below the humidity setpoint you have chosen. The value for this
setpoint ranges from 0% to 60%. If no humidity is desired or if a humidification
system has not been installed, set the value to 0%.
DEHUM JUMPER SETTING
If the jumper for MISC1, MISC2, or MISC3 is set to DEHUM, the corresponding MISC screw
terminal on the backplate will be connected to the dehumidification terminal of a furnace board.
NOTE: Not all furnaces have a dehumidification terminal.
DEHUMIDIFICATION OPERATION - SECTION 9
If your HVAC unit is equipped with a dehumidification system the thermostat will
operate in one of two ways.
1) Normally Closed (NC): The thermostat will de-energize the MISC1, MISC2,
or MISC3 terminal of the thermostat (this MISC terminal is connected
to the DEHUM terminal on your furnace) to allow the fan to run in low
speed when the humidity in the home is above the dehumidify setpoint you
have chosen and there is a call for 1st stage cooling.
16
2) Normally Open (NO): The thermostat will energize the MISC1, MISC2, or
MISC3 terminal of the thermostat (this MISC terminal is connected to the
DEHUM terminal on your furnace) to allow the fan to run in low speed when
the humidity in the home is above the dehumidify setpoint you have chosen
and there is a call for 1st stage cooling.
Page 16.3
Download from Www.Somanuals.com. All Manuals Search And Download.
Explanatiion off JJumperr Settiings (ccontinued)
Y2 JUMPER SETTING
If the jumper for MISC1 is set to Y2 the MISC1 screw terminal on the backplate will control a
second stage of cooling.
Y2 OPERATION - SECTION 12.4
The 2nd Stage of heat or cool is turned on when:
(A) The 1st Stage has been on for the two minutes.
And
(B) The temperature spread from the setpoint is equal to or greater
than: the setpoint plus the 1st stage deadband (step #19, page
12.5), plus two degrees.
Cooling
Deadband
Deadband
db 1
(adj. 1-6 )
db 2
(adj. 0-10 )
1st Stage
turn on
2nd Stage
turn on
Cool
Setpoint
TEMPERATURE
INCREASE
16
Page 16.4
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 17
Factory Deefaulltts, Callibrattion, aand Sensors
Section 17 Contents:
Resetting the Thermostat to the
Factory Default Settings........17.2
Calibrating the Temperature
and Humidity Sensors...........17.3
17
Page 17.1
Download from Www.Somanuals.com. All Manuals Search And Download.
Resettiing the TThhermostaat to the
Factorry Defaullt Settiings (foorr defaultt valuess see pagge 19.1)
If, for any reason, you desire to return all the stored settings back to
the factory default settings, follow the instructions below.
WARNING: This will reset all Advanced Programming to the
default settings. Any information entered prior to this reset may
be perman ntly lost.
Place the thermostat in the
OFF mode.
MODE
OFF
72
Setup
Press and hold the MODE
button. While holding the
MODE button, press and hold
the FAN button for 5 seconds.
All icons will appear on the
display.
DeHumidify
88
Service Filter
Pan UV Light
AUTO
MODE
FAN
COOL
Outside
Remote
OFFON
AUXHEAT
Override
FanOn
I88
88
After all of the icons appear,
release the MODE and FAN
buttons. Then press and hold
the FAN button for 5 seconds.
17
FAN
After the letters Fd appear on
the display (Factory Default),
release the FAN button. Press
the MODE button once to
return to normal operation.
MODE
OFF
72
Page 17.2
Download from Www.Somanuals.com. All Manuals Search And Download.
Calibbratingg the Teemperaatture andd Humiddity Seensors
Under normal circumstances it will not be necessary to adjust the
calibration of the temperature and humidity sensors. If calibration is
required, please contact a trained HVAC technician to correctly
perform the following procedure.
Pm
I2:00
Su
Place the thermostat in the
OFF mode.
MODE
OFF
72
Setup
Press and hold the MODE
MODE
DeHumidify
button. While holding the
MODE button, press and hold
the FAN button for 5 seconds.
All icons will appear on the
display.
88
Service Filter
Pan UV Light
AUTO
COOL
Outside
Remote
OFFON
AUXHEAT
FAN
Override
FanOn
I88
88
PRESS
THERMOSTAT SENSOR
Press the UP and DOWN buttons
at the same time twice. The
thermostat temperature will be
displayed and may be calibrated
using the UP or DOWN buttons.
CALIBRATE
TWICE
REMOTE SENSOR
Press the MODE button once. The
remote sensor temperature will be
displayed and may be calibrated using the
UP or DOWN buttons. If a remote sensor
is not installed, only dashes will appear.
MODE
CALIBRATE
Remote
17
HUMIDITY SENSOR
Press the MODE button once. The
relative humidity at the thermostat will be
displayed and may be calibrated using the
UP or DOWN buttons.
CALIBRATE
MODE
After calibration is complete, press the MODE button once to return to
normal operation.
Page 17.3
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 18
Accesssories
ACCESSORY PORT - The RJ11 Jack is used to connect the
P374-2700 to the IR Receiver P/N P374-0431 for wireless
communication or the EZ Programmer P/N P374-0432 for
easy downloading or uploading of thermostat information.
The Accessory Port is located on
the bottom of the thermostat.
RJ11 Type Jack
IR RECEIVER / REMOTE CONTROL (optional accessory) - When the
IR Receiver is connected, the thermostat can be controlled using
an IR Remote Control. The thermostat may also interface with
other wireless systems in your home. For more information see the
instruction sheet for the IR Receiver P/N P374-0431.
EZ PROGRAMMER (optional accessory) - When the EZ Programmer
is connected, the thermostat Time Period Programming and
Advanced Setup Programming can be stored into the EZ
Programmer’s memory. This information can then be uploaded to
other P374-2700 thermostats. For more information see the
instruction sheet for the EZ Programmer P/N P374-0432.
18
Page 18.1
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 19
Advanced SSetupp TTable
Step# Description Pg# Range
Df*
Step# Description
Pg# Range Df*
1
2
3
Auto-Changeover
Thermostat
Fan Off Delay
3.2 Yes/No
Yes 17 Minimum Heat/Cool 12.2
2
0 - 6
Differential
Cycles Per Hour
6.3 0, 30, 60,
90
7.2 Auto/On/ Au-
Off
7.2 F/C
7.4 0 - 3
0
18
19 Deadband/Temp.
Swing 1st Stage
12.3
12.5
6
2
d1, d 2-6
1 - 6
Thermoglow
Backlight
F or C
20 2nd Stage turn off at 12.6
setpoint
21 Thermostat control 13.3
to RS1?
On
Yes
No
to
F
On/Off
Yes/No
Yes/No
4
5
6
7
8
9
Security Level
0
Max Heat Setpoint 7.4 35 - 99
80
55
Off
3
22 Dry Contact
Operation
14.2
7.4 35 - 99
Min Cool Setpoint
Cool to Dehumidify 9.4 On/Off
9.4 0 - 5
Maximum Dehum
Overshoot
10 DEHUM Terminal
Polarity
11 Override Run-Time 10.2 read only - -
12 Reset Service
10.3 read only - -
Humidify Icon
23 Dry Contact Polarity 14.2
NO
Ove
rride
NO/NC
Override/
Service
Pan
35 - 99
35 - 99
read only
24 Dry Contact
Programming
14.3
9.5 NO/NC NC
25 Unoccupied Cool
26 Unoccupied Heat
14.4
14.4
85
55
- -
27 Reset Service Filter 15.2
Icon
28 Service Filter Run
Time Set
29 UV Light Run-Time 15.3
Set
30 Service Humidify
Run-Time Set
13 Reset UV Light Icon 10.5 read only - -
14 Heatpump Jumper 11.2 read only - -
Setting
15.2
0
0
0
0 - 1950
0 - 1990
0 - 1990
15 Reversing Valve
Jumper Setting
16 Electric Heat
11.2 read only - -
15.4
11.3 read only - -
*Df = Factory Default Setting
19
Page 19.1
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 20
Index
outside, 2.2, 4.2
indicator, 2.2
mode, 1.2
run-time, see Run-Time
setpoint, 1.2-1.3
to dehumidify, see
Dehumidify
Override, 2.2, 5.1
Reset Filter, 2.2, 15.2
up, 1.2, 2.2, 7.3,
11.4
A
Accessory Port, 18.1
Alerts
Condensate Drain Pan,
2.4, 14.3
Cycles Per Hour, 12.3,
19.1
see Run-Time
Auto
adjust temperature,
1.4, 3.5
changeover, 3.4,
19.1
differential, see
Differential
fan, 6.2
C
C, 7.2, 19.1
Calibration, 17.3
Celsius, 7.2
Compressor Lockout,
12.3
D
icon, 2.3
Cool
Deadband
lockout, 3.2
mode, 1.2
AuxHeat icon, 2.4
1st stage
deadband, see
Deadband
dehum, 9.5
2nd stage
1st stage, 12.4-12.5,
12.6, 16.4, 19.1
2nd stage, 12.4, 12.6
Dehumidify
cool to, 9.3, 19.1
DEHUM jumper,
9.2
icon, 2.4
setpoint, 9.2
Delay
fan-off, see Fan
Differential
heat and cool, 12.2,
19.1
humidify and
dehumidify, 8.3,
9.2
deadband, see
Deadband
dehum, 9.5
turn off
temperature,
12.6, 19.1
Y2 operation,
16.5
deadband, see
Deadband
droop, see Deadband
electric/heat pump,
11.2
B
b reversing valve, 12.2
Buttons
down, 2.2, 7.3,
11.4
fan, 1.3, 2.2, 6.2,
11.4, 17.2
front panel, 2.2
humidity, 2.2, 4.3,
7.3, 8.3
mode, 1.2, 2.2, 7.3,
17.2
Disabled Keypad
see Keypad Lockout
icon, 2.3
Page 20.1
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 20
Index
Drain Pan Overflow
Alarm, see Dry Contact
Dry Contact
override, 14.3, 19.1
operation, 14.2,
19.1
polarity, 14.2, 19.1
random start, 14.5
service pan, 14.3
Buttons
off time delay, 6.3,
19.1
on during heat, see
Electric Heat
on icon, 1.3, 2.4, 6.2
run-time, 15.2
2nd stage heat, see
Emergency Heat
speed, see
Dehumidify
unoccupied, 6.2
Fd, 17.2
deadband, see
Deadband
emergency heat,
11.4
electric strip heat,
2.4
AuxHeat icon, 2.4
deadband, see
Deadband
droop, see Deadband
electric/heat pump,
11.2
icon, 2.3
indicator, 2.2
Mode, 1.2
E
Flashing Selection,1.2
EH, 11.4
run-time, see Run-
Time
Electric Heating
AuxHeat icon, 2.4
jumper setting, 11.3
19.1
Emergency Heat,
11.4
EZ Programmer, 18.1
G
setpoint, 1.2-1.3
Heat Pump
AuxHeat, 2.4
emergency heat,
11.4
jumper setting, 11.2
Humidify
icon, 2.4
Gas Furnace
control the fan, 11.3
jumper, 11.2
Green Indicator, 2.2
F
Factory Defaults
caution, ii
settings, 17.2
resetting, 17.2
Fahrenheit, 7.2
Fan,
service, 10.5, 15.4,
19.1
H
setpoint, 8.3
Humidity Module
connector, 8.2
installation, 8.2
jumper setting, 8.2
required for, 4.3,
8.1, 8.3, 9.1-9.3,
16.4, 17.3
F, 7.2, 19.1
Heat
1st stage
deadband, see
Deadband
emergency heat,
11.4
2nd stage
button function, see
Page 20.2
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 20
Index
see Display
Locked Indication
see Keypad Lockout
12.2
Off Mode, 1.2, 2.3
Outdoor,
see Outside
Outside
I
IR Receiver, 18.1
IR Remote Control,
18.1
button, see Buttons
icon, 2.3
M
sensor, 2.3, 4.2, 12.1-
12.2, 13.2, 17.3
viewing temperature,
2.3, 4.2, 13.2, 17.3
Override
button, see Buttons
icon, 2.3
timer, 5.1
Manual
changeover, 3.3
cool, 3.2
heat, 3.2
J
Jumpers
MISC
DEHUM, 16.3
ECON, 16.3
ELEC, 11.3
electric heat, 11.3
gas electric, 11.2
heat pump, 11.2, 19.1
HUM, 8.2, 16.2-16.3
reversing valve, 11.2,
19.1
jumper, see Jumpers
output, 16.2-16.3
Mode icon, 1.2, 2.3
Multi-stage
Operation, 12.4
viewing run-time,
10.2, 19.1
P
see Dry Contact
Polarity, see Dry Contact
N
Y2, 16.2-16.3
Pan, Service
Non-Programmable
Thermostat, 3.3-3.4
Normally
K
Open/Closed,
dry contact, 14.2
dehum terminal,
9.5
R
Keypad Lockout, 2.4,
7.3
Random Start, 14.5
Red Indicator, 2.2
Remote Sensor
calibrate, 17.3
L O
Page 20.3
control to, 13.3-
LCD
O Reversing Valve,
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 20
Index
13.4, 17.1
outside, see Outside
calibrate, 17.3
Time Delay,
compressor lockout,
12.3
degree icon blink,
13.2-13.3
icon, 2.4
remote, see Remote
thermostat, see
Thermostat
outside temperature,
see Outside
read to, 13.3
wiring, 13.2
RS1, see Remote
Sensor
RS2, see Outside
Sensor
Run-Time
Service
cycles per hour,
12.3, 19.1
filter icon, 15.2
humidify icon, 15.4
pan icon, see Dry
Contact
UV light, 15.3
Setpoint
U
cool, see Cool
dehumidification,
Unoccupied
icon, 2.3
resetting, 15.2-15.4
setting,
humidifier, 15.4,
19.1
service filter, 15.2,
19.1
8.4,
operation, 5.1
override, see
Override
setpoints, 14.4
UV Light
icon, 2.4
9.3, 9.5
heat, see Heat
humidification, 4.3,
8.4, 9.3
security, 7.4
UV light, 15.3, 19.1
viewing,
Override, 10.2
UV light, 10.4
unoccupied, 5.1
Setup Icon, 2.4
Simplest Operation,
3.2
resetting, 15.3
run-time, 15.3
setting, 15.3
Smart Fan, 6.2
Smart Recovery, see
Energy Save
W
W3, see Jumpers
S
Warranty, 26.1
2nd stage turn off
temperature,
12.6, 19.1
T
Security
Terminal, MISC, see
MISC
Thermostat Sensor
Y
level, 7.4, 19.1
setpoints, 7.4, 19.1
Sensor
Y2, see Jumpers
Page 20.4
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 21
Warranty
Five-Year Warranty - This Product is warranted to be free from defects in material and
workmanship. If it appears within five year from the date of original installation, whether or not
actual use begins on that date, that the product does not meet this warranty, a new or
remanufactured part, at the manufacturer’s sole option to replace any defective part, will be
provided without charge for the part itself provided the defective part is returned to the
distributor through a qualified servicing dealer.
THIS WARRANTY DOES NOT INCLUDE LABOR OR OTHER COSTS incurred for diagnosing,
repairing, removing, installing, shipping, servicing or handling of either defective parts or
replacement parts. Such costs may be covered by a separate warranty provided by the installer.
THIS WARRANTY APPLIES ONLY TO PRODUCTS IN THEIR ORIGINAL INSTALLATION
LOCATION AND BECOMES VOID UPON REINSTALLATION.
LIMITATIONS OF WARRANTIES – ALL IMPLIED WARRANTIES (INCLUDING IMPLIED
WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY) ARE
HEREBY LIMITED IN DURATION TO THE PERIOD FOR WHICH THE LIMITED WARRANTY
IS GIVEN. SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED
WARRANTY LASTS, SO THE ABOVE MAY NOT APPLY TO YOU. THE EXPRESSED
WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE ALTERED,
ENLARGED, OR CHANGED BY ANY DISTRIBUTOR, DEALER, OR OTHER PERSON
WHATSOEVER.
ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED DURING
NORMAL WORKING HOURS. ALL REPLACEMENT PARTS, WHETHER NEW OR
REMANUFACTURED, ASSUME AS THEIR WARRANTY PERIOD ONLY THE REMAINING
TIME PERIOD OF THIS WARRANTY.
THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR:
1. Normal maintenance as outlined in the installation and servicing instructions or owner’s
manual, including filter cleaning and/or replacement and lubrication.
2. Damage or repairs required as a consequence of faulty installation, misapplication, abuse,
improper servicing, unauthorized alteration or improper operation.
3. Failure to start due to voltage conditions, blown fuses, open circuit breakers or other
damages due to the inadequacy or interruption of electrical service.
4. Damage as a result of floods, winds, fires, lightning, accidents, corrosive environments or
other conditions beyond the control of the Manufacturer.
5. Parts not supplied or designated by the Manufacturer, or damages resulting from their use.
6. Manufacturer products installed outside the continental U.S.A., Alaska, Hawaii, and
Canada.
7. Electricity or fuel costs or increases in electricity or fuel costs for any reason whatsoever
including additional or unusual use of supplemental electric heat.
8. ANY SPECIAL INDIRECT OR CONSEQUENTIAL PROPERTY OR COMMERCIAL
DAMAGE OF ANY NATURE WHATSOEVER. Some states do not allow the exclusion of
incidental or consequential damages, so the above may not apply to you.
This warranty gives you specific legal rights and you may also have other rights which may vary
from state to state.
P/N 88-502 Rev. 5
Page 21.1
Download from Www.Somanuals.com. All Manuals Search And Download.
|