Carrier Refrigerator 30GN040 420 User Manual

30GN040-420  
Flotronic™ II Reciprocating Liquid Chillers  
50/60 Hz  
Controls, Operation, and  
Troubleshooting  
with Microprocessor Controls and Electronic Expansion Valves  
CONTENTS  
Page  
Page  
Unit Shutoff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48  
Complete Unit Stoppage . . . . . . . . . . . . . . . . . . . . 48  
Single Circuit Stoppage . . . . . . . . . . . . . . . . . . . . . 48  
Lag Compressor Stoppage . . . . . . . . . . . . . . . . . . 48  
Restart Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . 48  
• POWER FAILURE EXTERNAL TO THE UNIT  
Alarms and Alerts . . . . . . . . . . . . . . . . . . . . . . . . . . 48  
Compressor Alarm/Alert Circuit . . . . . . . . . . . . . 50  
Electronic Expansion Valve (EXV) . . . . . . . . . . . 55  
• EXV OPERATION  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . 2  
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
MAJOR SYSTEM COMPONENTS . . . . . . . . . . . . 2-5  
Processor Module . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Low-Voltage Relay Module . . . . . . . . . . . . . . . . . . . 4  
Electronic Expansion Valve Module . . . . . . . . . . . 4  
Options Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
Keypad and Display Module  
(Also Called HSIO or LID) . . . . . . . . . . . . . . . . . . 4  
Control Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
Electronic Expansion Valve (EXV) . . . . . . . . . . . . 4  
Thermostatic Expansion Valves (TXV) . . . . . . . . 4  
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Compressor Protection Control  
• CHECKOUT PROCEDURE  
Thermostatic Expansion Valve (TXV) . . . . . . . . . 57  
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57  
• LOCATION  
• THERMISTOR REPLACEMENT (T1, T2, T7, T8)  
Pressure Transducers . . . . . . . . . . . . . . . . . . . . . . 60  
• TROUBLESHOOTING  
Module (CPCS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
OPERATION DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 5-46  
Capacity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . 24  
• EXV UNITS  
• TXV UNITS  
Pumpout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
• EXV UNITS  
• TRANSDUCER REPLACEMENT  
Control Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63  
• PROCESSOR MODULE (PSIO), 4IN/4OUT  
MODULE (SIO), LOW-VOLTAGE RELAY  
MODULE (DSIO-LV), AND EXV DRIVER  
MODULE (DSIO-EXV)  
• RED LED  
• GREEN LED  
• PROCESSOR MODULE (PSIO)  
• LOW-VOLTAGE RELAY MODULE (DSIO)  
• 4IN/4OUT MODULE (SIO)  
• TXV UNITS  
Keypad and Display Module  
(Also Called HSIO or LID) . . . . . . . . . . . . . . . . . 24  
• ACCESSING FUNCTIONS AND SUBFUNCTIONS  
• AUTOMATIC DEFAULT DISPLAY  
• AUTOMATIC DISPLAY OPERATION/DEFAULT  
DISPLAY  
• KEYPAD OPERATING INSTRUCTIONS  
• STATUS FUNCTION  
• TEST FUNCTION  
• HISTORY FUNCTION  
• SET POINT FUNCTION  
• SERVICE FUNCTION  
• SCHEDULE FUNCTION  
ACCESSORY UNLOADER INSTALLATION . . . 64-68  
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65  
• 040-110, 130 (60 Hz) UNITS  
(And Associated Modular Units)  
• 130 (50 Hz), 150-210 UNITS  
(And Associated Modular Units)  
FIELD WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69,70  
REPLACING DEFECTIVE PROCESSOR  
MODULE (PSIO) . . . . . . . . . . . . . . . . . . . . . . . . . . 70  
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 47-64  
Checking Display Codes . . . . . . . . . . . . . . . . . . . . 47  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 2  
PC 903  
Catalog No. 563-079  
Printed in U.S.A.  
Form 30GN-3T  
Pg 1  
7-95  
Replaces: 30G-1T  
Tab 5c  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMM 3  
PWR  
POINT NUMBER  
OF  
FIRST CHANNEL  
X
X
EXV  
LV  
STATUS  
STATUS  
COMM  
COMM  
J5  
COMM 1  
COMM 3  
PWR  
S1  
S2  
J4  
J4  
X
X
EQUIP GND  
99NA505322  
D
FUSE  
1
SW1  
LOCAL/  
ENABLE  
STOP  
CCN  
FUSE  
3
STAT  
HIST  
SRVC  
TEST  
EXPN  
CLR  
7
4
1
8
5
2
0
9
6
3
FUSE  
CO  
2
GFI  
-
SCHD  
SET  
(
5
AMP MAX  
)
CB5  
CB6  
ENTR  
30GT510568  
LEGEND  
CCN  
TB  
Carrier Comfort Network  
Terminal Block  
Fig. 1 — 30GN Control Panel (040-110 Unit Shown)  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
also controls the EXV driver module (as appropriate), com-  
manding it to open or close each EXV in order to maintain  
the proper superheat entering the cylinders of each lead com-  
pressor. Information is transmitted between the processor mod-  
ule and relay module, the EXV driver module, and the key-  
pad and display module through a 3-wire communications  
bus. The options module is also connected to the commu-  
nications bus.  
For the Flotronic™ II chillers, the processor monitors sys-  
tem pressure by means of 6 transducers, 3 in each lead com-  
pressor. Compressor suction pressure, discharge pressure, and  
oil pressure are sensed. If the processor senses high dis-  
charge pressure or low suction pressure, it immediately shuts  
down all compressors in the affected circuit. During opera-  
tion, if low oil pressure is sensed for longer than one minute,  
all compressors in the affected circuit are shut down. At start-  
up, the oil pressure signal is ignored for 2 minutes. If shut-  
down occurs due to any of these pressure faults, the circuit  
is locked out and the appropriate fault code is displayed.  
Table 2 — LOCAL/ENABLE-STOP-CCN  
Switch Positions and Operation  
CONFIGURATION AND  
SWITCH  
POSITION  
UNIT  
OPERATION  
SET POINT CONTROL  
Keypad Control  
CCN Control  
STOP  
Unit Cannot Run Read/Write  
Read Only  
LOCAL/ENABLE Unit Can Run  
Read/Limited Write Read Only  
CCN Stop —  
Unit Cannot Run Read Only  
Read/Write  
Read/Limited  
Write  
Run —  
Unit Can Run Read Only  
In the CCN position, the chiller is under remote control  
and responds only to CCN network commands. The occupied/  
unoccupied conditions are defined by the network. All key-  
pad and display functions can be read at the chiller regard-  
less of position of the switch.  
CCN run or stop condition is established by a command  
from the CCN network. It is not possible to force outputs  
from the CCN network, except that an emergency stop com-  
mand shuts down the chiller immediately and causes ‘‘ALARM  
52’’ to be displayed.  
Low-Voltage Relay Module — This module closes  
contacts to energize compressor unloaders and/or compres-  
sors. It also senses the status of the safeties for all compres-  
sors and transmits this information to the processor.  
Electronic Expansion Valve (EXV) — The micro-  
processor controls the EXV (if so equipped) through the EXV  
driver module. Inside the expansion valve is a linear actua-  
tor stepper motor.  
Electronic Expansion Valve Module (If So  
Equipped) — This module receives signals from the pro-  
cessor and operates the electronic expansion valves.  
The lead compressor in each circuit has a thermistor and  
a pressure transducer located in the suction manifold after  
the compressor motor. The thermistor measures the tem-  
perature of the superheated gas entering the compressor cyl-  
inders. The pressure transducer measures the refrigerant pressure  
in the suction manifold. The microprocessor converts the pres-  
sure reading to a saturated temperature. The difference be-  
tween the temperature of the superheated gas and the satu-  
ration temperature is the superheat. The microprocessor controls  
the position of the electronic expansion valve stepper motor  
to maintain 30 F (17 C) superheat.  
Options Module — This module allows the use of Flo-  
tronic II features such as dual set point, remote reset, de-  
mand limit, hot gas bypass, and accessory unloaders. The  
options module also allows for reset and demand limit to be  
activated from a remote 4-20 mA signal. The options mod-  
ule is installed at the factory.  
Keypad and Display Module (Also Called HSIO  
At initial unit start-up, the EXV position is at zero. After  
that, the microprocessor keeps accurate track of the valve  
position in order to use this information as input for the other  
control functions. The control monitors the superheat and  
the rate of change of superheat to control the position of the  
valve. The valve stroke is very large, which results in very  
accurate control of the superheat.  
or LID) — This device consists of a keypad with 6 func-  
tion keys, 5 operative keys, 12 numeric keys, and an alpha-  
numeric 8-character LCD (liquid crystal display). Key us-  
age is explained in Accessing Functions and Subfunctions  
section on page 24.  
Control Switch — Control of the chiller is defined by  
the position of the LOCAL/ENABLE-STOP-CCN switch.  
This is a 3-position manual switch that allows the chiller to  
be put under the control of its own Flotronic II controls, manu-  
ally stopped, or put under the control of a Carrier Comfort  
Network (CCN). Switch allows unit operation as shown in  
Table 2.  
In the LOCAL/ENABLE position, the chiller is under lo-  
cal control and responds to the scheduling configuration and  
set point data input at its own local interface device (keypad  
and display module).  
Thermostatic Expansion Valves (TXV) — Model  
30GN040 and 045 units with factory-installed brine option  
are equipped with conventional thermostatic expansion valves  
with liquid line solenoids. The liquid line solenoid valves  
are not intended to be a mechanical shut-off. When service  
is required, use the liquid line service valve to pump down  
the system.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
The TXV is set at the factory to maintain approximately  
8 to 12° F (4.4 to 6.7° C) suction superheat leaving the cooler  
by monitoring the proper amount of refrigerant into the cooler.  
All TXVs are adjustable, but should not be adjusted unless  
absolutely necessary. When TXV is used, thermistors T7 and  
T8 are not required.  
The TXV is designed to limit the cooler saturated suction  
temperature to 55 F (12.8 C). This makes it possible for unit  
to start at high cooler fluid temperatures without overload-  
ing the compressor.  
Sensors — The Flotronic™ II chiller control system gath-  
ers information from sensors to control the operation of the  
chiller. The units use 6 standard pressure transducers and  
4 standard thermistors to monitor system pressures and tem-  
peratures at various points within the chiller. Sensors are listed  
in Table 3.  
Fig. 2 — Compressor Protection Control Module  
Table 3 — Thermistor and Transducer Locations  
THERMISTORS  
Sensor  
Location  
T1  
T2  
T7  
T8  
T10  
Cooler Leaving Fluid Temp  
Cooler Entering Fluid Temp  
Compressor Suction Gas Temp Circuit A  
Compressor Suction Gas Temp Circuit B  
Remote Temperature Sensor (Accessory)  
PRESSURE TRANSDUCERS  
Location  
Sensor  
DPT-A  
SPT-A  
OPT-A  
DPT-B  
SPT-B  
OPT-B  
Compressor A1 Discharge Pressure  
Compressor A1 Suction Pressure  
Compressor A1 Oil Pressure  
Compressor B1 Discharge Pressure  
Compressor B1 Suction Pressure  
Compressor B1 Oil Pressure  
Fig. 3 — Compressor Ground Fault Module  
Compressor Protection Control Module (CPCS)  
ground of any compressor winding exceeds 2.5 amps. If this  
condition occurs, the CPCS module shuts down the  
compressor.  
Each compressor on models 30GN070 (50 Hz), 080-  
110, and 230B-315B, has its own CPCS as standard equip-  
ment. See Fig. 2. All 30GN040-060 and 070 (60 Hz) units  
feature the CPCS as an accessory, and CR (control relay) as  
standard equipment. The 30GN130-210 and associated modu-  
lar units have a CR as standard equipment. The CPCS or CR  
is used to control and protect the compressors and crankcase  
heaters. The CPCS provides the following functions:  
• compressor contactor control  
A high-pressure switch with a trip pressure of 426  
± 7 psig (2936 ± 48 kPa), is wired in series with the CPCS.  
If this switch opens during operation, the compressor stops  
and the failure is detected by the processor when the signal  
contacts open. The compressor is locked off. If the lead com-  
pressor in either circuit is shut down by the high-pressure  
switch or ground current protector, all compressors in the  
circuit are locked off.  
• crankcase heater control  
• compressor ground current protection  
• status communication to processor board  
OPERATION DATA  
• high-pressure protection  
The CR provides all of the same functions as the CPCS  
with the exception of compressor ground current protection.  
Ground current protection is accomplished by using a CGF  
(compressor ground fault module) in conjunction with the  
CR. The CGF (See Fig. 3) provides the same ground fault  
function as the CPCS for units where the CPCS is not  
utilized.  
One large relay is located on the CPCS board. This relay  
(or CR) controls the crankcase heater and compressor  
contactor. The CPCS also provides a set of signal contacts  
that the microprocessor monitors to determine the operating  
status of the compressor. If the processor board determines  
that the compressor is not operating properly through the sig-  
nal contacts, it will lock the compressor off by deenergizing  
the proper 24-v control relay on the relay board. The  
CPCS board contains logic that can detect if the current-to-  
Capacity Control — The control system cycles  
compressor to give capacity control steps as shown in  
Tables 4A-4C. The unit controls leaving chilled fluid tem-  
perature. Entering fluid temperature is used by the micro-  
processor in determining the optimum time to add or sub-  
tract steps of capacity, but is not a control set point.  
The chilled fluid temperature set point can be automati-  
cally reset by the return temperature reset or space and  
outdoor-air temperature reset features. It can also be reset  
from an external 4 to 20 mA signal, or from a network  
signal.  
The operating sequences shown are some of many pos-  
sible loading sequences for the control of the leaving fluid  
temperature. If a circuit has more unloaders than another,  
that circuit will always be the lead circuit.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4A — Capacity Control Steps, 040-070  
LOADING SEQUENCE A  
%
LOADING SEQUENCE B  
UNIT  
30GN  
CONTROL  
STEPS  
%
Displacement  
(Approx)  
Compressors  
Displacement  
(Approx)  
Compressors  
1
2
3
4
25  
50  
A1*  
A1  
A1*, B1  
A1,B1  
040 (60 Hz)  
A1†,B1  
75  
100  
1
2
3
4
25  
50  
A1*  
A1  
A1*,B1  
A1,B1  
25  
50  
B1*  
B1  
A1,B1*  
A1,B1  
040 (60 Hz)  
A1†,B1**  
75  
75  
100  
100  
1
2
3
4
24  
47  
A1*  
A1  
A1*,B1  
A1,B1  
040 (50 Hz)  
045 (60 Hz)  
A1†,B1  
76  
100  
1
2
3
4
5
24  
47  
A1*  
A1  
A1*,B1*  
A1*,B1  
A1,B1  
37  
53  
B1*  
B1  
A1*,B1*  
A1,B1*  
A1,B1  
040 (50 Hz)  
045 (60 Hz)  
A1†,B1**  
61  
61  
76  
100  
84  
100  
1
2
3
4
5
6
21  
37  
B1††  
B1*  
040 (50 Hz)  
045 (60 Hz)  
A1†,B1**  
53  
B1  
68  
A1,B1††  
A1,B1*  
A1,B1  
84  
100  
1
2
3
4
31  
44  
A1*  
A1  
A1*,B1  
A1,B1  
045 (50 Hz)  
050 (60 Hz)  
A1†,B1  
87  
100  
1
2
3
4
5
31  
44  
A1*  
A1  
A1*,B1*  
A1*,B1  
A1,B1  
38  
56  
B1*  
B1  
A1*,B1*  
A1,B1*  
A1,B1  
045 (50 Hz)  
050 (60 Hz)  
A1†,B1**  
69  
69  
87  
100  
82  
100  
1
2
3
4
5
18  
31  
A1††  
A1*  
A1††,B1  
A1*,B1  
A1,B1  
045 (50 Hz)  
050 (60 Hz)  
A1†**,B1  
73  
87  
100  
1
2
3
4
5
6
7
18  
31  
A1††  
A1*  
045 (50 Hz)  
050 (60 Hz)  
A1†**,B1**  
44  
A1  
56  
A1††,B1*  
A1††,B1  
A1*,B1  
A1,B1  
73  
87  
100  
1
2
3
4
5
6
7
20  
38  
B1††  
B1*  
045 (50 Hz)  
050 (60 Hz)  
A1†,B1**  
56  
B1  
51  
A1*,B1††  
A1,B1††  
A1,B1*  
A1,B1  
64  
82  
100  
*Unloaded compressor.  
†Compressor unloader, standard.  
**Compressor unloader(s), accessory.  
††Two unloaders, both unloaded.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4A — Capacity Control Steps, 040-070 (cont)  
LOADING SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
30GN  
CONTROL  
STEPS  
%
%
Displacement  
(Approx)  
Compressors  
Displacement  
(Approx)  
Compressors  
1
2
3
4
5
6
7
18  
31  
A1††  
A1*  
20  
38  
B1††  
B1*  
045 (50 Hz)  
050 (60 Hz)  
A1†**,B1**  
44  
A1  
56  
B1  
56  
A1††,B1*  
A1††,B1  
A1*,B1  
A1,B1  
64  
82  
100  
A1,B1††  
A1,B1*  
A1,B1  
73  
87  
100  
1
2
3
4
28  
42  
A1*  
A1  
A1*,B1  
A1,B1  
050 (50 Hz)  
060 (60 Hz)  
A1†,B1  
87  
100  
1
2
3
4
5
28  
42  
A1*  
A1  
A1*,B1*  
A1*,B1  
A1,B1  
38  
58  
B1*  
B1  
A1*,B1*  
A1,B1*  
A1,B1  
050 (50 Hz)  
060 (60 Hz)  
A1†,B1**  
67  
67  
87  
100  
80  
100  
1
2
3
4
5
15  
28  
A1††  
A1*  
A1††,B1  
A1*,B1  
A1,B1  
050 (50 Hz)  
060 (60 Hz)  
A1†**,B1  
73  
87  
100  
1
2
3
4
5
6
7
15  
28  
A1††  
A1*  
050 (50 Hz)  
060 (60 Hz)  
A1†**,B1**  
42  
A1  
53  
A1,B1*  
A1††,B1  
A1*,B1  
A1,B1  
73  
87  
100  
1
2
3
4
5
6
18  
38  
B1††  
B1*  
050 (50 Hz)  
060 (60 Hz)  
A1†,B1**  
58  
B1  
60  
A1,B1††  
A1,B1*  
A1,B1  
80  
100  
1
2
3
4
5
6
7
15  
28  
A1††  
A1*  
18  
38  
B1††  
B1*  
050 (50 Hz)  
060 (60 Hz)  
A1†**,B1**  
42  
A1  
58  
B1  
53  
A1††,B1*  
A1††,B1  
A1*,B1  
A1,B1  
60  
80  
100  
A1,B1††  
A1,B1*  
A1,B1  
73  
87  
100  
1
2
3
4
33  
50  
A1*  
A1  
A1*,B1  
A1,B1  
060 (50 Hz)  
070 (60 Hz)  
A1†,B1  
83  
100  
1
2
3
4
5
33  
50  
A1*  
A1  
A1*,B1*  
A1*,B1  
A1,B1  
33  
50  
B1*  
B1  
A1*,B1*  
A1,B1*  
A1,B1  
060 (50 Hz)  
070 (60 Hz)  
A1†,B1**  
67  
66  
83  
100  
83  
100  
1
2
3
4
5
16  
33  
A1††  
A1*  
060 (50 Hz)  
070 (60 Hz)  
A1†**,B1  
66  
A1††,B1  
A1*  
83  
100  
A1,B1  
1
2
3
4
5
6
16  
33  
A1††  
A1*  
060 (50 Hz)  
070 (60 Hz)  
A1†**,B1**  
50  
A1  
66  
A1††,B1  
A1*,B1  
A1,B1  
83  
100  
1
2
3
4
5
6
16  
33  
B1††  
B1*  
060 (50 Hz)  
070 (60 Hz)  
A1†,B1**  
50  
B1  
66  
A1,B1††  
A1,B1*  
A1,B1  
83  
100  
*Unloaded compressor.  
†Compressor unloader, standard.  
**Compressor unloader(s), accessory.  
††Two unloaders, both unloaded.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4A — Capacity Control Steps, 040-070 (cont)  
LOADING SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
30GN  
CONTROL  
STEPS  
%
%
Displacement  
(Approx)  
Compressors  
Displacement  
(Approx)  
Compressors  
1
2
3
4
5
6
16  
33  
A1††  
A1*  
16  
33  
B1††  
B1*  
060 (50 Hz)  
070 (60 Hz)  
A1†**,B1  
50  
A1  
50  
B1  
66  
A1††,B1  
A1*,B1  
A1,B1  
66  
A1,B1††  
A1,B1*  
A1,B1  
83  
83  
100  
100  
1
2
3
4
5
6
19  
27  
A1*  
A1  
070 (50 Hz)  
A1†,B1  
65  
A1*,B1  
A1,B1  
73  
92  
A1*,A2,B1  
A1,A2,B1  
100  
1
2
3
4
5
6
7
8
19  
27  
A1*  
A1  
31  
47  
B1*  
B1  
49  
A1*,B1*  
A1*,B1  
49  
A1*,B1*  
A1,B1*  
070 (50 Hz)  
A1†,B1**  
65  
57  
73  
A1,B1  
73  
A1,B1  
76  
A1*,A2,B1*  
A1*,A2,B1  
A1,A2,B1  
76  
A1*,A2,B1*  
A1,A2,B1*  
A1,A2,B1  
92  
84  
100  
100  
1
2
3
4
5
6
7
8
11  
19  
A1††  
A1*  
57  
A1††,B1  
A1*,B1  
070 (50 Hz)  
A1†**,B1  
65  
73  
A1,B1  
84  
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
92  
100  
1
2
11  
19  
27  
41  
57  
65  
73  
84  
92  
100  
A1††  
A1*  
3
A1  
4
A1††,B1*  
A1††,B1  
A1*,B1  
070 (50 Hz)  
A1†**,B1**  
5
6
7
A1,B1  
8
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
9
10  
1
2
3
4
5
6
7
15  
31  
B1††  
B1*  
47  
B1  
070 (50 Hz)  
A1†,B1ሻ  
57  
A1*,B1*  
A1,B1  
A1,A2,B1*  
A1,A2,B1  
73  
84  
100  
1
2
11  
19  
27  
41  
57  
65  
73  
84  
92  
100  
A1††  
A1*  
15  
31  
47  
54  
73  
84  
100  
B1††  
B1*  
3
A1  
B1  
4
A1††,B1*  
A1††,B1  
A1*,B1  
A1*,B1*  
A1,B1  
A1,A2,B1*  
A1,A2,B1  
070 (50 Hz)  
A1†**,B1ሻ  
5
6
7
A1,B1  
8
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
9
10  
*Unloaded compressor.  
†Compressor unloader, standard.  
**One compressor unloader, accessory.  
††Two unloaders, both unloaded.  
Two compressor unloaders, accessory.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units  
LOADING SEQUENCE A  
%
LOADING SEQUENCE B  
UNIT  
30GN  
CONTROL  
STEPS  
%
Displacement  
Compressors  
Displacement  
(Approx)  
Compressors  
(Approx)  
1
2
3
4
5
6
7
22  
34  
A1*  
A1  
A1*,B1*  
A1*,B1  
A1,B1  
A1*,A2,B1  
A1,A2,B1  
30  
44  
B1*  
B1  
A1*,B1*  
A1,B1*  
A1,B1  
A1,A2,B1*  
A1,A2,B1  
52  
52  
080, 230B (60 Hz)  
A1†,B1†  
67  
63  
78  
78  
89  
85  
100  
100  
1
2
3
4
5
6
7
8
9
11  
22  
A1††  
A1*  
34  
A1  
41  
A1††,B1*  
A1††,B1  
A1*,B1  
A1,B1  
A1*,A2,B1  
A1,A2,B1  
080, 230B (60 Hz)  
A1†**, B1†  
55  
67  
78  
89  
100  
1
2
3
4
5
6
7
8
15  
30  
B1††  
B1*  
44  
B1  
080, 230B (60 Hz)  
A1†,B1†**  
48  
A1,B1††  
A1,B1*  
A1,B1  
A1,A2,B1*  
A1,A2,B1  
63  
78  
85  
100  
1
2
3
4
5
6
7
8
9
11  
22  
A1††  
A1*  
15  
30  
44  
48  
63  
78  
85  
100  
B1††  
B1*  
34  
A1  
B1  
41  
A1††,B1*  
A1††,B1  
A1*,B1  
A1,B1  
A1*,A2,B1  
A1,A2,B1  
A1,B1††  
A1,B1*  
A1,B1  
A1,A2,B1*  
A1,A2,B1  
080, 230B (60 Hz)  
A1†**,B1†**  
55  
67  
78  
89  
100  
1
2
3
4
5
6
7
8
17  
25  
A1*  
A1  
25  
38  
B1*  
B1  
A1*,B1*  
A1, B1*  
A1,B1  
A1*,A2,B1*  
A1,A2,B1*  
A1,A2,B1  
42  
A1*,B1*  
A1*,B1  
42  
080, 230B (50 Hz)  
A1†,B1†  
54  
50  
62  
A1,B1  
62  
79  
A1*,A2,B1*  
A1*,A2,B1  
A1,A2,B1  
79  
92  
88  
100  
100  
1
2
8
17  
25  
33  
46  
54  
62  
71  
84  
92  
100  
A1††  
A1*  
3
A1  
4
A1††,B1*  
A1††,B1  
A1*,B1  
5
080, 230B (50 Hz)  
A1†**,B1†  
6
7
A1,B1  
8
A1††,A2,B1*  
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
9
10  
11  
1
2
3
4
5
6
7
8
9
13  
25  
B1††  
B1*  
38  
B1  
50  
A1,B1*  
A1,B1  
A1*,A2,B1††  
A1,A2,B1††  
A1,A2,B1*  
A1,A2,B1  
080, 230B (50 Hz)  
A1†,B1†**  
62  
67  
75  
88  
100  
1
2
8
17  
25  
33  
46  
54  
62  
71  
84  
92  
100  
A1††  
A1*  
13  
25  
38  
50  
62  
67  
75  
88  
100  
B1††  
B1*  
3
A1  
B1  
4
A1††,B1*  
A1††,B1  
A1*,B1  
A1,B1*  
A1,B1  
5
080, 230B (50 Hz)  
A1†**,B1†**  
6
A1*,A2,B1††  
A1,A2,B1††  
A1,A2,B1*  
A1,A2,B1  
7
A1,B1  
8
A1††,A2,B1*  
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
9
10  
11  
*Unloaded compressor.  
NOTE: These capacity control steps may vary due to lag compressor  
sequencing.  
†Compressor unloader, standard.  
**Compressor unloader, accessory.  
††Two unloaders, both unloaded.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units (cont)  
LOADING SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
30GN  
CONTROL  
STEPS  
%
%
Displacement  
(Approx)  
Compressors  
Displacement  
(Approx)  
Compressors  
1
2
18  
27  
35  
44  
53  
56  
65  
74  
82  
91  
100  
A1*  
A1  
18  
27  
35  
44  
53  
62  
71  
80  
82  
91  
100  
B1*  
B1  
3
A1*,B1*  
A1*,B1*  
4
A1*,B1  
A1,B1  
A1,B1*  
A1,B1  
5
090, 245B (60 Hz)  
A1†,B1†  
6
A1*,A2,B1*  
A1*,A2,B1  
A1,A2,B1  
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,B1*,B2  
A1,B1*,B2  
A1,B1,B2  
A1*,A2,B1*,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
7
8
9
10  
11  
1
2
9
18  
27  
35  
44  
53  
56  
65  
74  
82  
91  
100  
A1††  
A1*  
3
A1  
4
A1††,B1  
A1*,B1  
A1,B1  
5
090, 245B (60 Hz)  
A1†**,B1†  
6
7
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
8
9
10  
11  
12  
1
2
9
18  
27  
35  
44  
53  
62  
71  
80  
82  
91  
100  
B1††  
B1*  
3
B1  
4
A1,B1††  
A1,B1*  
A1,B1  
5
090, 245B (60 Hz)  
A1†,B1†**  
6
7
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
8
9
10  
11  
12  
1
2
9
18  
27  
35  
44  
53  
56  
65  
74  
82  
91  
100  
A1††  
A1*  
9
18  
27  
35  
44  
53  
62  
71  
80  
82  
91  
100  
B1††  
B1*  
3
A1  
B1  
4
A1††,B1  
A1*,B1  
A1,B1  
A1,B1††  
A1,B1*  
A1,B1  
5
090, 245B (60 Hz)  
A1†**,B1†**  
6
7
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
8
9
10  
11  
12  
1
2
14  
21  
29  
36  
43  
61  
68  
75  
86  
93  
100  
A1*  
A1  
14  
21  
29  
36  
43  
53  
60  
67  
86  
93  
100  
B1*  
B1  
3
A1*,B1*  
A1*,B1*  
4
A1*,B1  
A1,B1  
A1,B1*  
A1,B1  
5
090, 245B (50 Hz)  
A1†,B1†  
6
A1*,A2,B1*  
A1*,A2,B1  
A1,A2,B1  
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,B1*,B2  
A1,B1*,B2  
A1,B1,B2  
A1*,A2,B1*,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
7
8
9
10  
11  
1
2
7
14  
21  
29  
36  
43  
54  
61  
68  
75  
79  
86  
93  
100  
A1††  
A1*  
3
A1  
4
A1††,B1  
5
A1*,B1  
6
A1,B1  
090, 245B (50 Hz)  
A1†**,B1†  
7
A1††,A2,B1*  
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
8
9
10  
11  
12  
13  
14  
*Unloaded compressor.  
NOTE: These capacity control steps may vary due to lag compressor  
sequencing.  
†Compressor unloader, standard.  
**Compressor unloader, accessory.  
††Two unloaders, both unloaded.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units (cont)  
LOADING SEQUENCE A  
%
LOADING SEQUENCE B  
UNIT  
30GN  
CONTROL  
STEPS  
%
Displacement  
Compressors  
Displacement  
(Approx)  
Compressors  
(Approx)  
1
2
7
14  
21  
29  
36  
43  
46  
53  
60  
67  
79  
86  
93  
100  
B1††  
B1*  
3
B1  
4
A1,B1††  
5
A1,B1*  
6
A1,B1  
090, 245B (50 Hz)  
A1†,B1†**  
7
A1*,B1††,B2  
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
A1*,A2,B1††,B1  
A1,A2,B1††,B1  
A1,A2,B1*,B2  
A1,2,B1,B2  
8
9
10  
11  
12  
13  
14  
1
2
7
14  
21  
29  
36  
43  
49  
54  
61  
68  
75  
79  
86  
93  
100  
A1††  
A1*  
7
14  
21  
29  
36  
43  
46  
53  
60  
67  
72  
79  
86  
93  
100  
B1††  
B1*  
3
A1  
B1  
4
A1††,B1  
A1,B1††  
5
A1*,B1  
A1,B1*  
6
A1,B1  
A1,B1  
7
A1††,A2,B1††  
A1††,A2,B1*  
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,B1††,B2  
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
090, 245B (50 Hz)  
A1†**,B1†**  
8
9
10  
11  
12  
13  
14  
15  
A1††,A2,B1††,B2  
A1*,A2,B1††,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
1
2
16  
23  
31  
39  
46  
58  
66  
73  
85  
92  
100  
A1*  
A1  
16  
23  
31  
39  
46  
58  
66  
73  
85  
92  
100  
A1*  
A1  
3
A1*,B1*  
A1*,B1*  
4
A1*,B1  
A1,B1  
A1*,B1  
A1,B1  
100, 255B,  
270B (60 Hz)  
A1†,B1†  
5
6
A1*,A2,B1*  
A1*,A2,B1  
A1,A2,B1  
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,A2,B1*  
A1*,A2,B1  
A1,A2,B1  
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
7
8
9
10  
11  
1
2
8
16  
23  
31  
39  
46  
50  
58  
66  
73  
77  
85  
92  
100  
A1††  
A1*  
3
A1  
4
A1††,B1  
5
A1*,B1  
6
A1,B1  
100, 255B,  
270B (60 Hz)  
A1†**,B1†  
7
A1††,A2,B1*  
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
8
9
10  
11  
12  
13  
14  
1
2
8
16  
23  
31  
39  
46  
50  
58  
66  
73  
77  
85  
92  
100  
B1††  
B1*  
3
B1  
4
A1,B1††  
5
A1,B1*  
6
A1,B1  
100, 255B,  
270B (60 Hz)  
A1†,B1†**  
7
A1*,B1††,B2  
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
A1*,A2,B1††,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
8
9
10  
11  
12  
13  
14  
*Unloaded compressor.  
NOTE: These capacity control steps may vary due to lag compressor  
sequencing.  
†Compressor unloader, standard.  
**Compressor unloader, accessory.  
††Two unloaders, both unloaded.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units (cont)  
LOADING SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
30GN  
CONTROL  
STEPS  
%
%
Displacement  
(Approx)  
Compressors  
Displacement  
(Approx)  
Compressors  
1
2
8
16  
23  
31  
39  
46  
50  
58  
66  
73  
77  
85  
92  
100  
A1††  
A1*  
8
16  
23  
31  
39  
46  
50  
58  
66  
73  
77  
85  
92  
100  
B1††  
B1*  
3
A1  
B1  
4
A1††,B1  
A1,B1††  
5
A1*,B1  
A1,B1*  
6
A1,B1  
A1,B1  
100, 255B,  
270B (60 Hz)  
A1†**,B1†**  
7
A1††,A2,B1*  
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,B1††,B2  
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
A1*,A2,B1††,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
8
9
10  
11  
12  
13  
14  
1
2
13  
20  
26  
33  
40  
57  
63  
70  
87  
93  
100  
A1*  
A1  
13  
20  
26  
33  
40  
57  
63  
70  
87  
93  
100  
B1*  
B1  
3
A1*,B1*  
A1*,B1*  
4
A1,B1  
A1,B1  
A1,B1*  
A1,B1  
100, 255B,  
270B (50 Hz)  
A1†,B1†  
5
6
A1*,A2,B1*  
A1*,A2,B1  
A1,A2,B1  
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,B1*,B2  
A1,B1*,B2  
A1,B1,B2  
A1*,A2,B1*,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
7
8
9
10  
11  
1
2
7
13  
20  
26  
33  
40  
50  
57  
63  
70  
80  
87  
93  
100  
A1††  
A1*  
3
A1  
4
A1††,B1  
5
A1*,B1  
6
A1,B1  
100, 255B,  
270B (50 Hz)  
A1†**,B1†  
7
A1††,A2,B1*  
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
8
9
10  
11  
12  
13  
14  
1
2
7
13  
20  
26  
33  
40  
50  
57  
63  
70  
80  
87  
93  
100  
B1††  
B1*  
3
B1  
4
A1,B1††  
5
A1,B1*  
6
A1,B1  
100, 255B,  
270B (50 Hz)  
A1†,B1†**  
7
A1*,B1††,B2  
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
A1*,A2,B1††,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
8
9
10  
11  
12  
13  
14  
1
2
7
13  
20  
26  
33  
40  
43  
50  
57  
63  
70  
74  
80  
89  
93  
100  
A1††  
A1*  
7
13  
20  
26  
33  
40  
43  
50  
57  
63  
70  
74  
80  
87  
93  
100  
B1††  
B1*  
3
A1  
B1  
4
A1††,B1  
A1,B1††  
5
A1*,B1  
A1,B1*  
6
A1,B1  
A1,B1  
7
A1††,A2,B1††  
A1††,A2,B1*  
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
A1††,B1††,B2  
A1*,B1††,B2  
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
100, 255B,  
270B (50 Hz)  
A1†**,B1†**  
8
9
10  
11  
12  
13  
14  
15  
16  
A1††,A2,B1††,B2  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1††,A2,B1††,B2  
A1*,A2,B1††,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
*Unloaded compressor.  
NOTE: These capacity control steps may vary due to lag compressor  
sequencing.  
†Compressor unloader, standard.  
**Compressor unloader, accessory.  
††Two unloaders, both unloaded.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units (cont)  
LOADING SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
30GN  
CONTROL  
STEPS  
%
%
Displacement  
(Approx)  
Compressors  
Displacement  
(Approx)  
Compressors  
1
2
14  
21  
29  
36  
43  
61  
68  
75  
86  
93  
100  
A1*  
A1  
14  
21  
29  
36  
43  
53  
60  
67  
86  
93  
100  
B1*  
B1  
3
A1*,B1*  
A1*,B1*  
4
A1*,B1  
A1,B1  
A1,B1*  
A1,B1  
110, 290B,  
315B (60 Hz)  
A1†,B1†  
5
6
A1*,A2,B1*  
A1*,A2,B1  
A1,A2,B1  
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,B1*,B2  
A1,B1*,B2  
A1,B1,B2  
A1*,A2,B1*,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
7
8
9
10  
11  
1
2
7
14  
21  
29  
36  
43  
54  
61  
68  
75  
79  
86  
93  
100  
A1††  
A1*  
3
A1  
4
A1††,B1  
5
A1*,B1  
6
A1,B1  
110, 290B,  
315B (60 Hz)  
A1†**,B1†  
7
A1††,A2,B1*  
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
8
9
10  
11  
12  
13  
14  
1
2
7
14  
21  
29  
36  
43  
46  
53  
60  
67  
79  
86  
93  
100  
B1††  
B1*  
3
B1  
4
A1,B1††  
5
A1,B1*  
6
A1,B1  
110, 290B,  
315B (60 Hz)  
A1†,B1†**  
7
A1*,B1††,B2  
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
A1*,A2,B1††,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
8
9
10  
11  
12  
13  
14  
1
2
7
14  
21  
29  
36  
43  
47  
54  
61  
68  
75  
79  
86  
93  
100  
A1††  
A1*  
7
14  
21  
29  
36  
43  
46  
53  
60  
67  
72  
79  
86  
93  
100  
B1††  
B1*  
3
A1  
B1  
4
A1††,B1  
A1,B1††  
5
A1*,B1  
A1,B1*  
6
A1,B1  
A1,B1  
110, 290B,  
315B (60 Hz)  
A1†**,B1†**  
7
A1††,A2,B1††  
A1††,A2,B1*  
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,B1††,B2  
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
8
9
10  
11  
12  
13  
14  
15  
A1††,A2,B1††,B2  
A1*,A2,B1††,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
1
2
17  
25  
33  
42  
50  
58  
67  
75  
83  
92  
100  
A1*  
A1  
17  
25  
33  
42  
50  
58  
67  
75  
83  
92  
100  
B1*  
B1  
3
A1*,B1*  
A1*,B1*  
4
A1*,B1  
A1,B1  
A1,B1*  
A1,B1  
110, 290B,  
315B (50 Hz)  
A1†,B1†  
5
6
A1*,A2,B1*  
A1*,A2,B1  
A1,A2,B1  
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,B1*,B2  
A1,B1*,B2  
A1,B1,B2  
A1*,A2,B1*,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
7
8
9
10  
11  
*Unloaded compressor.  
NOTE: These capacity control steps may vary due to lag compressor  
sequencing.  
†Compressor unloader, standard.  
**Compressor unloader, accessory.  
††Two unloaders, both unloaded.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4B — Capacity Control Steps, 080-110 and Associated Modular Units (cont)  
LOADING SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
30GN  
CONTROL  
STEPS  
%
%
Displacement  
(Approx)  
Compressors  
Displacement  
(Approx)  
Compressors  
1
2
8
17  
25  
33  
42  
50  
58  
67  
75  
83  
92  
100  
A1††  
A1*  
3
A1  
4
A1††,B1  
A1*,B1  
A1,B1  
5
110, 290B,  
315B (50 Hz)  
A1†**,B1†  
6
7
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
8
9
10  
11  
12  
1
2
8
17  
25  
33  
42  
50  
58  
67  
75  
83  
92  
100  
B1††  
B1*  
3
B1  
4
A1,B1††  
A1,B1*  
A1,B1  
5
110, 290B,  
315B (50 Hz)  
A1†,B1†**  
6
7
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
8
9
10  
11  
12  
1
2
8
17  
25  
33  
42  
50  
58  
67  
75  
83  
92  
100  
A1††  
A1*  
8
17  
25  
33  
42  
50  
58  
67  
75  
83  
92  
100  
B1††  
B1*  
3
A1  
B1  
4
A1††,B1  
A1*,B1  
A1,B1  
A1,B1††  
A1,B1*  
A1,B1  
5
110, 290B,  
315B (50 Hz)  
A1†**,B1†**  
6
7
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
8
9
10  
11  
12  
*Unloaded compressor.  
NOTE: These capacity control steps may vary due to lag compressor  
sequencing.  
†Compressor unloader, standard.  
**Compressor unloader, accessory.  
††Two unloaders, both unloaded.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units  
LOADING SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
30GN  
CONTROL  
STEPS  
%
%
Displacement  
(Approx)  
Compressors  
Displacement  
(Approx)  
Compressors  
1
2
14  
21  
28  
35  
42  
58  
64  
71  
87  
93  
100  
A1*  
A1  
14  
21  
28  
35  
42  
58  
64  
71  
87  
93  
100  
B1*  
B1  
3
A1*,B1*  
A1*,B1*  
4
A1*,B1  
A1,B1  
A1,B1*  
A1,B1  
5
130 (60 Hz)  
A1†,B1†  
6
A1*,A2,B1*  
A1*,A2,B1  
A1,A2,B1  
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,B1*,B2  
A1,B1*,B2  
A1,B1,B2  
A1*,A2,B1*,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
7
8
9
10  
11  
1
2
8
14  
21  
22  
28  
35  
42  
51  
58  
64  
71  
80  
87  
93  
100  
A1††  
A1*  
3
A1  
4
A1††,B1*  
A1††,B1  
A1*,B1  
A1,B1  
5
6
7
130 (60 Hz)  
A1†**,B1†  
8
A1††,A2,B1*  
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
9
10  
11  
12  
13  
14  
15  
1
2
8
14  
21  
22  
28  
35  
42  
51  
58  
64  
71  
80  
87  
93  
100  
B1††  
B1*  
3
B1  
4
A1*,B1††  
A1,B1††  
A1,B1*  
A1,B1  
5
6
7
130 (60 Hz)  
A1†,B1†**  
8
A1*,B1††,B2  
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
A1*,A2,B1††,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
9
10  
11  
12  
13  
14  
15  
1
2
8
14  
21  
22  
28  
35  
42  
44  
51  
58  
64  
71  
73  
80  
87  
93  
100  
A1††  
A1*  
8
14  
21  
22  
28  
35  
42  
44  
51  
58  
64  
71  
73  
80  
87  
93  
100  
B1††  
B1*  
3
A1  
B1  
4
A1††,B1*  
A1*,B1††  
5
A1††,B1  
A1,B1††  
6
A1*,B1  
A1,B1*  
7
A1,B1  
A1,B1  
8
A1††,A2,B1††  
A1††,A2,B1*  
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
A1††,B1††,B2  
A1*,B1††,B2  
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
130 (60 Hz)  
A1†**,B1†**  
9
10  
11  
12  
13  
14  
15  
16  
17  
A1††,A2,B1††,B2  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1††,A2,B1††,B2  
A1*,A2,B1††,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
1
2
10  
14  
26  
35  
39  
44  
53  
57  
69  
78  
82  
87  
96  
100  
A1*  
A1  
16  
25  
26  
31  
39  
51  
56  
64  
69  
74  
82  
87  
91  
100  
B1*  
B1  
3
A1*,B1*  
A1*,B1*  
4
A1*,B1  
A1,B1  
A1*,A2,B1*  
A1*,A2,B1  
A1,A2,B1  
A1,B1*  
A1,B1  
A1*,B1*,B2  
A1,B1*,B2  
A1,B1,B2  
5
6
130 (50 Hz)  
A1†,B1†  
7
8
9
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,A2,A3,B1*,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1*,A2,B1*,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1*,A2,A3,B1*,B2  
A1,A2,A3,B1*,B2  
A1,A2,A3,B1,B2  
10  
11  
12  
13  
14  
*Unloaded compressor.  
NOTE: These capacity control steps may vary due to lag compressor  
sequencing.  
†Compressor unloader, standard.  
**Compressor unloader, accessory.  
††Two unloaders, both unloaded.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)  
LOADING SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
30GN  
CONTROL  
STEPS  
%
%
Displacement  
(Approx)  
Compressors  
Displacement  
(Approx)  
Compressors  
1
2
6
10  
14  
22  
31  
35  
39  
40  
49  
53  
57  
65  
74  
78  
82  
83  
91  
96  
100  
A1††  
A1*  
3
A1  
4
A1††,B1*  
5
A1††,B1  
6
A1*,B1  
7
A1,B1  
8
A1††,A2,B1*  
A1††,A2,B1  
A1*,A2,B1  
9
130 (50 Hz)  
A1†**,B1†  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
A1,A2,B1  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1††,A2,A3,B1*,B2  
A1††,A2,A3,B1,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
1
2
8
16  
25  
31  
39  
43  
47  
56  
64  
65  
74  
82  
83  
91  
100  
B1††  
B1*  
3
B1  
4
A1,B1*  
A1,B1  
5
6
A1*,B1††,B2  
A1,B1††,B2  
A1,B1*,B2  
7
130 (50 Hz)  
A1†,B1†**  
8
9
A1,B1,B2  
10  
11  
12  
13  
14  
15  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1,A2,A3,B1††,B2,B3  
A1,A2,A3,B1*,B2,B3  
A1,A2,A3,B1,B2,B3  
1
2
6
10  
14  
22  
31  
35  
39  
40  
49  
53  
57  
65  
74  
78  
82  
83  
91  
96  
100  
A1††  
A1*  
8
16  
25  
31  
39  
43  
47  
56  
64  
65  
74  
82  
83  
91  
100  
B1††  
B1*  
3
A1  
B1  
4
A1††,B1*  
A1,B1*  
A1,B1  
5
A1††,B1  
6
A1*,B1  
A1*,B1††,B2  
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1,A2,A3,B1††,B2  
A1,A2,A3,B1*,B2  
A1,A2,A3,B1,B2  
7
A1,B1  
8
A1††,A2,B1*  
A1††,A2,B1  
A1*,A2,B1  
9
130 (50 Hz)  
A1†**,B1†**  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
A1,A2,B1  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1††,A2,A3,B1*,B2  
A1††,A2,A3,B1,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
1
2
11  
15  
29  
38  
42  
44  
53  
58  
71  
80  
85  
86  
95  
100  
A1*  
A1  
18  
27  
29  
33  
42  
55  
60  
69  
71  
75  
85  
86  
91  
100  
B1*  
B1  
3
A1*,B1*  
A1*,B1*  
4
A1*,B1  
A1,B1  
A1*,A2,B1*  
A1*,A2,B1  
A1,A2,B1  
A1,B1*  
A1,B1  
A1*,B1*,B2  
A1,B1*,B2  
A1,B1,B2  
5
6
150, 230A, 245A,  
255A (60 Hz)  
A1†,B1†  
7
8
9
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,A2,A3,B1*,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1*,A2,B1*,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1*,A2,A3,B1*,B2  
A1,A2,A3,B1*,B2  
A1,A2,A3,B1,B2  
10  
11  
12  
13  
14  
*Unloaded compressor.  
NOTE: These capacity control steps may vary due to lag compressor  
sequencing.  
†Compressor unloader, standard.  
**Compressor unloader, accessory.  
††Two unloaders, both unloaded.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)  
LOADING SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
30GN  
CONTROL  
STEPS  
%
%
Displacement  
(Approx)  
Compressors  
Displacement  
(Approx)  
Compressors  
1
2
6
11  
A1††  
A1*  
3
15  
24  
33  
38  
42  
49  
53  
58  
66  
75  
80  
85  
91  
95  
100  
A1  
4
A1††,B1*  
5
A1††,B1  
6
A1*,B1  
7
A1,B1  
150, 230A, 245A,  
255A (60 Hz)  
A1†**,B1†  
8
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
9
10  
11  
12  
13  
14  
15  
16  
17  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1††,A2,A3,B1,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
1
2
9
18  
27  
33  
42  
46  
51  
60  
69  
75  
85  
91  
100  
B1††  
B1*  
3
B1  
4
A1,B1*  
A1,B1  
5
150, 230A, 245A,  
255A (60 Hz)  
A1†,B1†**  
6
A1*,B1††,B2  
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1,A2,A3,B1*,B2  
A1,A2,A3,B1,B2  
7
8
9
10  
11  
12  
13  
1
2
6
11  
A1††  
A1*  
9
18  
27  
33  
42  
46  
51  
60  
69  
75  
86  
91  
100  
B1††  
B1*  
3
15  
24  
33  
38  
42  
49  
53  
58  
66  
75  
80  
85  
91  
95  
100  
A1  
B1  
4
A1††,B1*  
A1,B1*  
A1,kB1  
5
A1††,B1  
6
A1*,B1  
A1*,B1††,B2  
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1,A2,A3,B1*,B2  
A1,A2,A3,B1,B2  
7
A1,B1  
150, 230A, 245A,  
255A (60 Hz)  
A1†**,B1†**  
8
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
9
10  
11  
12  
13  
14  
15  
16  
17  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1††,A2,A3,B1,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
1
2
13  
20  
26  
33  
40  
46  
53  
60  
66  
73  
80  
86  
93  
100  
A1*  
A1  
13  
20  
26  
33  
40  
46  
53  
60  
66  
73  
80  
86  
93  
100  
B1*  
B1  
3
A1*,B1*  
A1*,B1*  
4
A1*,B1  
A1,B1  
A1*,A2,B1*  
A1*,A2,B1  
A1,A2,B1  
A1,B1*  
A1,B1  
A1*,B1*,B2  
A1,B1*,B2  
A1,B1,B2  
5
6
150, 230A, 245A,  
255A (50 Hz)  
A1†,B1†  
7
8
9
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,A2,A3,B1*,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1*,A2,B1*,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1*,A2,A3,B1*,B2  
A1,A2,A3,B1*,B2  
A1,A2,A3,B1,B2  
10  
11  
12  
13  
14  
1
2
6
13  
20  
26  
33  
40  
46  
53  
60  
66  
73  
80  
86  
93  
100  
A1††  
A1*  
3
A1  
4
A1††,B1  
5
A1*,B1  
6
A1,B1  
150, 230A, 245A,  
255A (50 Hz)  
A1†**,B1†  
7
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
8
9
10  
11  
12  
13  
14  
15  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1††,A2,A3,B1,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
*Unloaded compressor.  
NOTE: These capacity control steps may vary due to lag compressor  
sequencing.  
†Compressor unloader, standard.  
**Compressor unloader, accessory.  
††Two unloaders, both unloaded.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)  
LOADING SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
SIZE  
CONTROL  
STEPS  
%
%
Displacement  
(Approx)  
Compressors  
Displacement  
(Approx)  
Compressors  
1
2
6
13  
20  
26  
33  
40  
46  
53  
60  
66  
73  
80  
86  
93  
100  
B1††  
B1*  
3
B1  
4
A1,B1††  
5
A1,B1*  
6
A1,B1  
150, 230A, 245A,  
255A (50 Hz)  
A1†,B1†**  
7
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
8
9
10  
11  
12  
13  
14  
15  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1,A2,A3,B1††,B2  
A1,A2,A3,B1*,B2  
A1,A2,A3,B1,B2  
1
2
6
13  
20  
26  
33  
40  
46  
53  
60  
66  
73  
80  
86  
93  
100  
A1††  
A1*  
6
13  
20  
26  
33  
40  
46  
53  
60  
66  
73  
80  
86  
93  
100  
B1††  
B1*  
3
A1  
B1  
4
A1††,B1  
A1,B1††  
5
A1*,B1  
A1,B1*  
6
A1,B1  
A1,B1  
150, 230A, 245A,  
255A (50 Hz)  
A1†**,B1†**  
7
A1††,A2,B1  
A1*,A2,B1  
A1,A2,B1  
A1,B1††,B2  
A1,B1*,B2  
A1,B1,B2  
8
9
10  
11  
12  
13  
14  
15  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1††,A2,A3,B1,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1,A2,A3,B1††,B2  
A1,A2,A3,B1*,B2  
A1,A2,A3,B1,B2  
1
2
11  
17  
23  
28  
33  
39  
45  
50  
56  
61  
67  
73  
78  
83  
89  
95  
100  
A1*  
A1  
11  
17  
23  
28  
33  
39  
45  
50  
56  
61  
67  
73  
78  
83  
89  
95  
100  
B1*  
B1  
3
A1*,B1*  
A1*,B1*  
4
A1*,B1  
A1,B1*  
5
A1,B1  
A1,B1  
6
A1*,A2,B1*  
A1*,B1*,B2  
7
A1*,A2,B1  
A1,B1*,B2  
170, 270A,  
330A/B (60 Hz)  
A1†,B1†  
8
A1,A2,B1  
A1,B1,B2  
9
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,A2,A3,B1*,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1*,A2,A3,B1*,B2,B3  
A1*,A2,A3,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
A1*,A2,B1*,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1*,A2,B1*,B2,B3  
A1,A2,B1*,B2,B3  
A1,A2,B1,B2,B3  
A1*,A2,A3,B1*,B2,B3  
A1,A2,A3,B1*,B2,B3  
A1,A2,A3,B1,B2,B3  
10  
11  
12  
13  
14  
15  
16  
17  
1
2
6
11  
A1††  
A1*  
3
17  
17  
23  
28  
33  
34  
39  
45  
50  
51  
56  
61  
67  
67  
73  
78  
83  
84  
89  
95  
100  
A1  
4
A1††,B1*  
5
A1††,B1  
6
A1*,B1  
7
A1,B1  
8
A1††,A2,B1*  
A1††,A2,B1  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
A1*,A2,B1  
A1,A2,B1  
170, 270A,  
330A/B (60 Hz)  
A1†**,B1†  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1††,A2,A3,B1*,B2  
A1††,A2,A3,B1,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1††,A2,A3,B1*,B2,B3  
A1††,A2,A3,B1,B2,B3  
A1*,A2,A3,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
*Unloaded compressor.  
NOTE: These capacity control steps may vary due to lag compressor  
sequencing.  
†Compressor unloader, standard.  
**Compressor unloader, accessory.  
††Two unloaders, both unloaded.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)  
LOADING SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
SIZE  
CONTROL  
STEPS  
%
%
Displacement  
(Approx)  
Compressors  
Displacement  
(Approx)  
Compressors  
1
2
6
11  
B1††  
B1*  
3
17  
17  
23  
28  
33  
34  
39  
45  
50  
51  
56  
61  
67  
67  
73  
78  
83  
84  
89  
95  
100  
B1  
4
A1*,B1††  
5
A1,B1††  
6
A1,B1*  
7
A1,B1  
8
A1*,B1††,B2  
A1,B1††,B2  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
A1,B1*,B2  
A1,B1,B2  
170, 270A,  
330A/B (60 Hz)  
A1†,B1†**  
A1*,A2,B1††,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1*,A2,B1††,B2,B3  
A1,A2,B1††,B2,B3  
A1,A2,B1*,B2,B3  
A1,A2,B1,B2,B3  
A1*,A2,A3,B1††,B2,B3  
A1,A2,A3,B1††,B2,B3  
A1,A2,A3,B1*,B2,B3  
A1,A2,A3,B1,B2,B3  
1
2
6
11  
A1††  
A1*  
6
11  
B1††  
B1*  
3
17  
17  
23  
28  
33  
34  
39  
45  
50  
51  
56  
61  
67  
67  
73  
78  
83  
84  
89  
95  
100  
A1  
17  
17  
23  
28  
33  
34  
39  
45  
50  
51  
56  
61  
67  
67  
73  
78  
83  
84  
89  
95  
100  
B1  
4
A1††,B1*  
A1*,B1††  
5
A1††,B1  
A1,B1††  
6
A1*,B1  
A1,B1*  
7
A1,B1  
A1,B1  
8
A1††,A2,B1*  
A1††,A2,B1  
A1*,B1††,B2  
A1,B1††,B2  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
A1*,A2,B1  
A1,A2,B1  
A1,B1*,B2  
A1,B1,B2  
170, 270A,  
330A/B (60 Hz)  
A1†**,B1†**  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1††,A2,A3,B1*,B2  
A1††,A2,A3,B1,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1††,A2,A3,B1*,B2,B3  
A1††,A2,A3,B1,B2,B3  
A1*,A2,A3,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
A1*,A2,B1††,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1*,A2,B1††,B2,B3  
A1,A2,B1††,B2,B3  
A1,A2,B1*,B2,B3  
A1,A2,B1,B2,B3  
A1*,A2,A3,B1††,B2,B3  
A1,A2,A3,B1††,B2,B3  
A1,A2,A3,B1*,B2,B3  
A1,A2,A3,B1,B2,B3  
1
2
9
14  
19  
23  
28  
33  
37  
42  
52  
57  
61  
72  
76  
81  
91  
96  
100  
A1*  
A1  
9
14  
19  
23  
28  
38  
43  
47  
52  
57  
61  
72  
76  
81  
91  
96  
100  
B1*  
B1  
3
A1*,B1*  
A1*,B1*  
4
A1*,B1  
A1,B1*  
5
A1,B1  
A1,B1  
6
A1*,A2,B1*  
A1*,B1*,B2  
7
A1*,A2,B1  
A1,B1*,B2  
170, 270A,  
330A/B,360B (50 Hz)  
A1†,B1†  
8
A1,A2,B1  
A1,B1,B2  
9
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,A2,A3,B1*,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1*,A2,A3,B1*,B2,B3  
A1*,A2,A3,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
A1*,A2,B1*,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1*,A2,B1*,B2,B3  
A1,A2,B1*,B2,B3  
A1,A2,B1,B2,B3  
A1*,A2,A3,B1*,B2,B3  
A1,A2,A3,B1*,B2,B3  
A1,A2,A3,B1,B2,B3  
10  
11  
12  
13  
14  
15  
16  
17  
*Unloaded compressor.  
NOTE: These capacity control steps may vary due to lag compressor  
sequencing.  
†Compressor unloader, standard.  
**Compressor unloader, accessory.  
††Two unloaders, both unloaded.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)  
LOADING SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
SIZE  
CONTROL  
STEPS  
%
%
Displacement  
(Approx)  
Compressors  
Displacement  
(Approx)  
Compressors  
1
2
5
9
A1††  
A1*  
3
14  
14  
19  
23  
28  
28  
33  
37  
42  
48  
52  
57  
61  
67  
72  
76  
81  
87  
91  
96  
100  
A1  
4
A1††,B1*  
5
A1††,B1  
6
A1*,B1  
7
A1,B1  
8
A1††,A2,B1*  
A1††,A2,B1  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
A1*,A2,B1  
A1,A2,B1  
170, 270A,  
330A/B, 360B (50 Hz)  
A1†**,B1†  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1††,A2,A3,B1*,B2  
A1††,A2,A3,B1,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1††,A2,A3,B1*,B2,B3  
A1††,A2,A3,B1,B2,B3  
A1*,A2,A3,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
1
2
5
9
B1††  
B1*  
3
14  
14  
19  
23  
28  
34  
38  
43  
47  
48  
52  
57  
61  
67  
72  
76  
81  
87  
91  
96  
100  
B1  
4
A1*,B1††  
5
A1,B1††  
6
A1,B1*  
7
A1,B1  
8
A1*,B1††,B2  
A1,B1††,B2  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
A1,B1*,B2  
A1,B1,B2  
170, 270A,  
330A/B, 360B (50 Hz)  
A1†,B1†**  
A1*,A2,B1††,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1*,A2,B1††,B2,B3  
A1,A2,B1††,B2,B3  
A1,A2,B1*,B2,B3  
A1,A2,B1,B2,B3  
A1*,A2,A3,B1††,B2,B3  
A1,A2,A3,B1††,B2,B3  
A1,A2,A3,B1*,B2,B3  
A1,A2,A3,B1,B2,B3  
1
2
5
9
A1††  
A1*  
5
9
B1††  
B1*  
3
14  
14  
19  
23  
28  
28  
33  
37  
42  
43  
48  
52  
57  
61  
63  
67  
72  
76  
81  
82  
87  
91  
96  
100  
A1  
14  
14  
19  
23  
28  
29  
34  
38  
43  
47  
48  
52  
57  
61  
63  
67  
72  
76  
81  
82  
87  
91  
96  
100  
B1  
4
A1††,B1*  
A1*,B1††  
5
A1††,B1  
A1,B1††  
6
A1*,B1  
A1,B1*  
7
A1,B1  
A1,B1  
8
A1††,A2,B1*  
A1††,B1††,B2  
A1*,B1††,B2  
9
A1††,A2,B1  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
A1*,A2,B1  
A1,B1††,B2  
A1,A2,B1  
A1,B1*,B2  
A1††,A2,B1††,B2  
A1††,A2,B1*,B2  
A1††,A2,B1,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1,B1,B2  
170, 270A,  
330A/B, 360B (50 Hz)  
A1†**,B1†**  
A1*,A2,B1††,B2  
A1,A2,B1††,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1††,A2,A3,B1††,B2  
A1††,A2,A3,B1*,B2  
A1††,A2,A3,B1,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1††,A2,A3,B1††,B2,B3  
A1††,A2,A3,B1*,B2,B3  
A1††,A2,A3,B1,B2,B3  
A1*,A2,A3,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
A1††,A2,B1††,B2,B3  
A1*,A2,B1††,B2,B3  
A1,A2,B1††,B2,B3  
A1,A2,B1*,B2,B3  
A1,A2,B1,B2,B3  
A1††,A2,A3,B1††,B2,B3  
A1*,A2,A3,B1††,B2,B3  
A1,A2,A3,B1††,B2,B3  
A1,A2,A3,B1*,B2,B3  
A1,A2,A3,B1,B3,B3  
*Unloaded compressor.  
NOTE: These capacity control steps may vary due to lag compressor  
sequencing.  
†Compressor unloader, standard.  
**Compressor unloader, accessory.  
††Two unloaders, both unloaded.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)  
LOADING SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
SIZE  
CONTROL  
STEPS  
%
%
Displacement  
(Approx)  
Compressors  
Displacement  
(Approx)  
Compressors  
1
2
3
4
5
6
13  
25  
A1  
13  
25  
B1  
A1,B1  
A1,B1  
190, 290A, 360A/B,  
390B (60 Hz)  
A1,B1  
41  
A1,A2,B1  
41  
A1,B1,B2  
56  
A1,A2,B1,B2  
A1,A2,A3,B1,B2  
A1,A2,A3,B1,B2,B3  
56  
A1,A2,B1,B2  
A1,A2,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
78  
78  
100  
100  
1
2
9
13  
21  
25  
37  
41  
53  
56  
74  
78  
96  
100  
A1*  
A1  
3
A1*,B1  
4
A1,B1  
5
A1*,A2,B1  
190, 290A, 360A/B,  
390B (60 Hz)  
A1**,B1  
6
A1,A2,B1  
7
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1*,A2,A3,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
8
9
10  
11  
12  
1
2
9
13  
21  
25  
37  
41  
53  
56  
74  
78  
96  
100  
B1*  
B1  
3
A1,B1*  
4
A1,B1  
5
A1,B1*,B2  
190, 290A, 360A/B,  
390B (60 Hz)  
A1,B1**  
6
A1,B1,B2  
7
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1,A2,B1*,B2,B3  
A1,A2,B1,B2,B3  
A1,A2,A3,B1*,B2,B3  
A1,A2,A3,B1,B2,B3  
8
9
10  
11  
12  
1
2
9
13  
18  
21  
25  
33  
37  
41  
49  
53  
56  
71  
74  
78  
93  
96  
100  
A1*  
A1  
9
13  
18  
21  
25  
33  
37  
41  
49  
53  
56  
71  
74  
78  
93  
96  
100  
B1*  
B1  
3
A1*,B1*  
A1*,B1*  
4
A1*,B1  
A1,B1*  
5
A1,B1  
A1,B1  
6
A1*,A2,B1*  
A1*,B1*,B2  
7
A1*,A2,B1  
A1,B1*,B2  
190, 290A, 360A/B,  
390B (60 Hz)  
A1**,B1**  
8
A1,A2,B1  
A1,B1,B2  
9
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,A2,A3,B1*,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1*,A2,A3,B1*,B2,B3  
A1*,A2,A3,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
A1*,A2,B1*,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1*,A2,B1*,B2,B3  
A1,A2,B1*,B2,B3  
A1,A2,B1,B2,B3  
A1*,A2,A3,B1*,B2,B3  
A1,A2,A3,B1*,B2,B3  
A1,A2,A3,B1,B2,B3  
10  
11  
12  
13  
14  
15  
16  
17  
1
2
3
4
5
6
17  
33  
A1  
17  
33  
B1  
A1,B1  
A1,B1  
190, 290A, 360A,  
390B (50 Hz)  
A1,B1  
50  
A1,A2,B1  
50  
A1,B1,B2  
67  
A1,A2,B1,B2  
A1,A2,A3,B1,B2  
A1,A2,A3,B1,B2,B3  
67  
A1,A2,B1,B2  
A1,A2,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
83  
83  
100  
100  
1
2
11  
17  
28  
33  
44  
50  
61  
67  
78  
83  
94  
100  
A1*  
A1  
3
A1*,B1  
4
A1,B1  
5
A1*,A2,B1  
190, 290A, 360A,  
390B (50 Hz)  
A1**,B1  
6
A1,A2,B1  
7
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1*,A2,A3,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
8
9
10  
11  
12  
*Unloaded compressor.  
NOTE: These capacity control steps may vary due to lag compressor  
sequencing.  
†Compressor unloader, standard.  
**Compressor unloader, accessory.  
††Two unloaders, both unloaded.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)  
LOADING SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
SIZE  
CONTROL  
STEPS  
%
%
Displacement  
(Approx)  
Compressors  
Displacement  
(Approx)  
Compressors  
1
2
11  
17  
28  
33  
44  
50  
61  
67  
78  
83  
94  
100  
B1*  
B1  
3
A1,B1*  
4
A1,B1  
5
A1,B1*,B2  
190, 290A, 360A,  
390B (50 Hz)  
A1,B1**  
6
A1,B1,B2  
7
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1,A2,B1*,B2,B3  
A1,A2,B1,B2,B3  
A1,A2,A3,B1*,B2,B3  
A1,A2,A3,B1,B2,B3  
8
9
10  
11  
12  
1
2
11  
17  
22  
28  
33  
39  
44  
50  
55  
61  
67  
72  
78  
83  
89  
94  
100  
A1*  
A1  
11  
17  
22  
28  
33  
39  
44  
50  
55  
61  
67  
72  
78  
83  
89  
94  
100  
B1*  
B1  
3
A1*,B1*  
A1*,B1*  
4
A1*,B1  
A1,B1*  
5
A1,B1  
A1,B1  
6
A1*,A2,B1*  
A1*,B1*,B2  
7
A1*,A2,B1  
A1,B1*,B2  
190, 290A, 360A,  
390B (50 Hz)  
A1**,B1**  
8
A1,A2,B1  
A1,B1,B2  
9
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,A2,A3,B1*,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1*,A2,A3,B1*,B2,B3  
A1*,A2,A3,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
A1*,A2,B1*,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1*,A2,B1*,B2,B3  
A1,A2,B1*,B2,B3  
A1,A2,B1,B2,B3  
A1*,A2,A3,B1*,B2,B3  
A1,A2,A3,B1*,B2,B3  
A1,A2,A3,B1,B2,B3  
10  
11  
12  
13  
14  
15  
16  
17  
1
2
3
4
5
6
7
11  
25  
A1  
14  
25  
B1  
A1,B1  
A1,B1  
210, 315A, 390A,  
420A/B (60 Hz)  
A1,B1  
36  
A1,A2,B1  
A1,A2,B1,B2  
A1,A2,A3,B1,B2  
A1,A2,A3,B1,B2,B3  
A1,A2,A3,A4,B1,B2,B3  
44  
A1,B1,B2  
A1,A2,B1,B2  
A1,A2,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
A1,A2,A3,A4,B1,B2,B3  
56  
56  
67  
75  
86  
86  
100  
100  
1
2
8
11  
A1*  
A1  
3
22  
25  
33  
36  
52  
56  
63  
67  
83  
86  
97  
100  
A1*,B1  
4
A1,B1  
5
A1*,A2,B1  
6
A1,A2,B1  
210, 315A, 390A,  
420A/B (60 Hz)  
A1**,B1  
7
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1*,A2,A3,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
A1*,A2,A3,A4,B1,B2,B3  
A1,A2,A3,A4,B1,B2,B3  
8
9
10  
11  
12  
13  
14  
1
2
9
14  
21  
25  
40  
44  
51  
56  
71  
75  
82  
86  
96  
100  
B1*  
B1  
3
A1,B1*  
4
A1,B1  
5
A1,B1*,B2  
6
A1,B1,B2  
210, 315A, 390A,  
420A/B (60 Hz)  
A1,B1**  
7
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1,A2,B1*,B2,B3  
A1,A2,B1,B2,B3  
A1,A2,A3,B1*,B2,B3  
A1,A2,A3,B1,B2,B3  
A1,A2,A3,A4,B1*,B2,B3  
A1,A2,A3,A4,B1,B2,B3  
8
9
10  
11  
12  
13  
14  
*Unloaded compressor.  
NOTE: These capacity control steps may vary due to lag compressor  
sequencing.  
†Compressor unloader, standard.  
**Compressor unloader, accessory.  
††Two unloaders, both unloaded.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4C — Capacity Control Steps, 130-210 and Associated Modular Units (cont)  
LOADING SEQUENCE A  
LOADING SEQUENCE B  
UNIT  
SIZE  
CONTROL  
STEPS  
%
%
Displacement  
(Approx)  
Compressors  
Displacement  
(Approx)  
Compressors  
1
2
8
11  
A1*  
A1  
9
14  
17  
21  
25  
37  
40  
44  
48  
51  
56  
67  
71  
75  
78  
82  
86  
92  
96  
100  
B1*  
B1  
3
17  
22  
25  
28  
33  
36  
48  
52  
56  
59  
63  
67  
78  
83  
86  
92  
97  
100  
A1*,B1*  
A1*,B1*  
4
A1*,B1  
A1,B1*  
5
A1,B1  
A1,B1  
6
A1*,A2,B1*  
A1*,B1*,B2  
7
A1*,A2,B1  
A1,B1*,B2  
8
A1,A2,B1  
A1,B1,B2  
9
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,A2,B1*,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
210, 315A, 390A,  
420A/B (60 Hz)  
A1**,B1**  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
A1*,A2,A3,B1*,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1*,A2,A3,B1*,B2,B3  
A1*,A2,A3,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
A1*,A2,A3,A4,B1*,B2,B3  
A1*,A2,A3,A4,B1,B2,B3  
A1,A2,A3,A4,B1,B2,B3  
A1*,A2,B1*,B2,B3  
A1,A2,B1*,B2,B3  
A1,A2,B1,B2,B3  
A1*,A2,A3,B1*,B2,B3  
A1,A2,A3,B1*,B2,B3  
A1,A2,A3,B1,B2,B3  
A1*,A2,A3,A4,B1*,B2,B3  
A1,A2,A3,A4,B1*,B2,B3  
A1,A2,A3,A4,B1,B2,B3  
1
2
3
4
5
6
7
9
26  
A1  
16  
26  
B1  
A1,B1  
A1,B1  
210, 315A, 390A,  
420A/B (50 Hz)  
A1,B1  
35  
A1,A2,B1  
A1,A2,B1,B2  
A1,A2,A3,B1,B2  
A1,A2,A3,B1,B2,B3  
A1,A2,A3,A4,B1,B2,B3  
42  
A1,B1,B2  
A1,A2,B1,B2  
A1,A2,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
A1,A2,A3,A4,B1,B2,B3  
51  
51  
67  
67  
84  
84  
100  
100  
1
2
6
9
A1*  
A1  
3
23  
26  
32  
35  
48  
51  
65  
67  
81  
84  
97  
100  
A1*,B1  
4
A1,B1  
5
A1*,A2,B1  
6
A1,A2,B1  
210, 315A, 390A,  
420A/B (50 Hz)  
A1**,B1  
7
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1*,A2,A3,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
A1*,A2,A3,A4,B1,B2,B3  
A1,A2,A3,A4,B1,B2,B3  
8
9
10  
11  
12  
13  
14  
1
2
11  
16  
20  
26  
36  
42  
46  
51  
62  
67  
78  
84  
94  
100  
B1*  
B1  
3
A1,B1*  
4
A1,B1  
5
A1,B1*,B2  
6
A1,B1,B2  
210, 315A, 390A,  
420A/B (50 Hz)  
A1,B1**  
7
A1,A2,B1*,B2  
A1,A2,B1,B2  
A1,A2,B1*,B2,B3  
A1,A2,B1,B2,B3  
A1,A2,A3,B1*,B2,B3  
A1,A2,A3,B1,B2,B3  
A1,A2,A3,A4,B1*,B2,B3  
A1,A2,A3,A4,B1,B2,B3  
8
9
10  
11  
12  
13  
14  
1
2
7
9
A1*  
A1  
11  
16  
17  
20  
26  
34  
36  
42  
43  
46  
51  
59  
62  
67  
75  
78  
84  
92  
94  
100  
B1*  
B1  
3
17  
23  
26  
27  
32  
35  
43  
48  
51  
59  
65  
67  
75  
81  
84  
92  
97  
100  
A1*,B1*  
A1*,B1*  
4
A1*,B1  
A1,B1*  
5
A1,B1  
A1,B1  
6
A1*,A2,B1*  
A1*,B1*,B2  
7
A1*,A2,B1  
A1,B1*,B2  
8
A1,A2,B1  
A1,B1,B2  
9
A1*,A2,B1*,B2  
A1*,A2,B1,B2  
A1,A2,B1,B2  
A1*,A2,B1*,B2  
A1,A2,B1*,B2  
A1,A2,B1,B2  
210, 315A, 390A,  
420A/B (50 Hz)  
A1**,B1**  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
A1*,A2,A3,B1*,B2  
A1*,A2,A3,B1,B2  
A1,A2,A3,B1,B2  
A1*,A2,A3,B1*,B2,B3  
A1*,A2,A3,B1,B2,B3  
A1,A2,A3,B1,B2,B3  
A1*,A2,A3,A4,B1*,B2,B3  
A1*,A2,A3,A4,B1,B2,B3  
A1,A2,A3,A4,B1,B2,B3  
A1*,A2,B1*,B2,B3  
A1,A2,B1*,B2,B3  
A1,A2,B1,B2,B3  
A1*,A2,A3,B1*,B2,B3  
A1,A2,A3,B1*,B2,B3  
A1,A2,A3,B1,B2,B3  
A1*,A2,A3,A4,B1*,B2,B3  
A1,A2,A3,A4,B1*,B2,B3  
A1,A2,A3,A4,B1,B2,B3  
*Unloaded compressor.  
NOTE: These capacity control steps may vary due to lag compressor  
sequencing.  
†Compressor unloader, standard.  
**Compressor unloader, accessory.  
††Two unloaders, both unloaded.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Head Pressure Control  
Keypad and Display Module (Also Called HSIO  
or LID) — The only function of this module is to allow  
the operator to communicate with the processor. It is used to  
enter configurations and set points and to read data, perform  
tests, and set schedules. This device consists of a keypad  
with 6 function keys, 5 operative keys, 12 numeric keys  
(0 to 9, •, and -), and an alphanumeric, 8-character LCD. See  
Fig. 4. See Table 6 for key usage.  
EXV UNITS (All 30GN units except 040 and 045 with op-  
tional brine) — The microprocessor controls the condenser  
fans in order to maintain the lowest condensing temperature  
possible, thus the highest unit efficiency. Instead of using the  
conventional head pressure control methods, the fans are con-  
trolled by the position of the EXV and suction superheat.  
As the condensing temperature drops, the EXV opens to  
maintain the proper suction superheat. Once the EXV is fully  
open, if the condensing temperature continues to drop, the  
suction superheat begins to rise. Once the suction superheat  
is greater than 40 F (22.2 C), a fan stage is removed after  
2 minutes.  
IMPORTANT: When entering multiple character in-  
puts beginning with a zero, a decimal point must be  
entered in place of the first zero. When entering an in-  
put of zero, only the decimal point need be entered.  
As the condensing temperature rises, the EXV closes to  
maintain the proper suction superheat. Once the EXV has  
closed to 39.5% open (600 steps open), a fan stage is added  
after 2 minutes.  
During start-up, all the condenser fans are started when  
the condensing temperature reaches 95 F (35 C) to prevent  
excessive discharge pressure during pulldown. See Table 5  
for condenser fan sequence of operation.  
For low-ambient operation, the lead fan in each circuit can  
be equipped with the optional or accessory Motormaster  
III head pressure controller. This control has its own sensor  
which is mounted on a return bend in the liquid portion of  
the condenser. It will vary the fan speed to maintain a satu-  
rated condensing temperature of 100 F. The controls auto-  
matically default to condensing temperature control during  
this first stage of condenser-fan operation. When subsequent  
fan stages start, the controls revert to EXV fan control.  
ACCESSING FUNCTIONS AND SUBFUNCTIONS — See  
Tables 6 - 8. Table 7 shows the 6 functions (identified by  
name) and the subfunctions (identified by number).  
AUTOMATIC DEFAULT DISPLAY — When keypad has  
not been used for 10 minutes, display automatically switches  
to the rotating automatic default display. This display has  
7 parts, listed below, which appear in continuous rotating  
sequence.  
DISPLAY  
TUE 15:45  
LOCAL ON  
CLOCK ON  
8 MODE  
EXPANSION  
TODAY IS TUE, TIME IS 15:45 (3:45 PM)  
UNIT IN LOCAL MODE  
UNIT IS ON VIA CLOCK SCHEDULE  
TEMPERATURE RESET IN EFFECT  
NUMBER OF STAGES IS 1  
THERE ARE 2 ALARMS  
COOL 1  
TXV UNITS (30GN040,045 with optional brine only) —  
Head pressure control is based on set point control. The micro-  
processor stages the condenser fans to maintain the set point  
temperature specified by the controller.  
2 ALARMS  
3 MINUTES REMAINING IN THE OFF-TO-ON  
TIME DELAY  
3 MINS  
Pumpout  
EXV UNITS — When the lead compressor in each circuit  
is started or stopped, that circuit goes through a pumpout  
cycle to purge the cooler and refrigerant suction lines of  
refrigerant.  
The pumpout cycle starts immediately upon starting the  
lead compressor and continues until the saturated suction tem-  
perature is 10° F (5.6° C) below the saturated suction tem-  
perature at start-up, is 10° F (5.6° C) below the cooler leav-  
ing fluid temperature, or reaches a saturated suction temperature  
of –15 F (–26 C). No pumpout is necessary if the saturated  
suction temperature is below –15 F (–26 C). At this point,  
the EXV starts to open and continues to open gradually to  
provide a controlled start-up to prevent liquid flood-back to  
the compressor.  
At shutdown, the pumpout cycle continues until the satu-  
rated suction temperature for that circuit is 10° F (5.5° C)  
below the saturated suction temperature when pumpout is  
initiated, or saturated suction temperature reaches –15 F  
(–26 C). At that point, the compressor shuts down and the  
EXV continues to move until fully closed.  
TXV UNITS — Pumpout is based on timed pumpout. On a  
command for start-up, the lead compressor starts. After  
10 seconds, the liquid line solenoid opens. At shutdown, the  
liquid line solenoid closes, and the lead compressor contin-  
ues to run for 10 seconds before stopping.  
Fig. 4 — Keypad and Display Module  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5 — Condenser Fan Sequence  
FAN ARRANGEMENT  
30GN  
FAN CONTACTOR  
FAN NUMBER(S)  
CONTROLLED BY  
(FC)  
040-050  
060,070  
1
2
FC-A1  
FC-B1  
Compressor A1  
Compressor B1  
First Stage  
Microprocessor  
3
4
FC-A2  
FC-B2  
Second Stage  
Microprocessor  
1
2
FC-A1  
FC-B1  
Compressor A1  
Compressor B1  
First Stage  
3, 4  
5, 6  
FC-A2  
FC-B2  
Microprocessor  
Second Stage  
Microprocessor  
080,090 (and associated modular units*)  
1
2
3
4
FC-A1  
FC-B1  
FC-A2  
FC-B2  
Compressor A1  
Compressor B1  
First Stage  
Microprocessor  
FC-A2, FC-B2,  
FC-A3, FC-B3  
Second Stage  
Microprocessor  
3, 4, 5, 6  
100,110 (and associated modular units*)  
1
2
3
4
FC-A1  
FC-B1  
FC-A2  
FC-B2  
Compressor A1  
Compressor B1  
First Stage  
Microprocessor  
Second Stage  
Microprocessor  
5, 7, 6, 8  
FC-A3, FC-B3  
FC-A2, FC-A3,  
FC-B2, FC-B3  
Third Stage  
Microprocessor  
3, 4, 5, 6, 7, 8  
130-170 (and associated modular units*)  
5, 7  
6, 8  
FC-A1  
FC-B1  
Compressor A1  
Compressor B1  
3, 9  
FC-A2  
First Stage  
Microprocessor  
4, 10  
FC-B2  
1, 3, 9  
2, 4, 10  
5, 7  
FC-A2, FC-A3  
FC-B2, FC-B3  
FC-A1  
Second Stage  
Microprocessor  
190,210 (and associated modular units*)  
Compressor A1  
Compressor B1  
6, 8  
FC-B1  
3, 9  
FC-A2  
First Stage  
Microprocessor  
4, 10  
FC-B2  
1, 3, 9, 11  
2, 4, 10, 12  
FC-A2, FC-A3  
FC-B2, FC-B3  
Second Stage  
Microprocessor  
*See Table 1.  
†Control box.  
AUTOMATIC DISPLAY OPERATION/DEFAULT DIS-  
PLAY — This display automatically rotates as follows:  
KEYPAD OPERATING INSTRUCTIONS (Refer to  
Table 9.)  
1. White keys on left side of keypad are shown and oper-  
ated in these instructions according to the following ex-  
ample: keypad entry  
means press the  
, then  
the white key marked  
.
2. The standard display uses abbreviations. Expanded in-  
DOW  
HH  
MM  
Day of Week  
Hour(s)  
Minute(s)  
formation scrolls through the display whenever  
is pressed.  
key  
The default rotating display is displayed every 2 seconds  
if there has been no manual input from the keypad for  
10 minutes.  
To return to automatic display, enter  
at any time.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 6 — Keypad and Display Module Usage  
3. All functions are made up of a group of subfunctions. To  
enter a subfunction, first press subfunction number de-  
sired. Then press the function key in which the subfunc-  
tion resides. To move within that subfunction, press  
FUNCTION  
USE  
KEYS  
STATUS — For displaying diagnostic codes and  
current operating information about the machine.  
the  
or  
arrow. For example, a  
enters  
HISTORY — For displaying run time, cycles and  
previous alarms.  
SERVICE — For entering specific unit configura-  
tion information.  
the Temperature Information subfunction.  
4. At any time, another subfunction may be entered by press-  
ing the subfunction number, then the function key.  
TEST — For checking inputs and outputs for  
proper operation.  
SCHEDULE — For entering occupied/unoccupied  
schedules for unit operation.  
5. Prior to starting unit, check leaving fluid set point for cor-  
rect setting. Refer to Set Point Function section on  
page 38.  
6. Depending on system configuration, all displays may not  
be shown. All displays are shown unless marked with the  
following symbol:  
SET POINT — For entering operating set points  
and day/time information.  
OPERATIVE  
USE  
KEYS  
†Must be configured.  
EXPAND — For displaying a non-abbreviated ex-  
pansion of the display.  
For additional unit start-up procedures, see separate  
Installation, Start-Up, and Service Instructions supplied  
with unit.  
CLEAR — For clearing the screen of all displays.  
UP ARROW — For returning to previous display  
position.  
DOWN ARROW — For advancing to next display  
position.  
ENTER — For entering data.  
Table 7 — Functions and Subfunctions  
FUNCTIONS  
Schedule  
SUBFUNCTION  
NO.  
Status  
Test  
Service  
History  
Set Point  
1
2
3
4
5
Automatic  
Outputs  
Override  
Clock Select  
Period 1  
Period 2  
Period 3  
Log On and  
Log Off  
Run Time  
Starts  
Set Points  
Display  
(Chiller Fluid)  
Alarm  
Display  
Compressors  
and Unloaders  
Version  
(Software)  
Reset  
Set Points  
Mode (Operating)  
Display  
Calibrate  
Transducers  
Factory  
Configuration  
Alarm  
History  
Demand Limit  
Set Points  
Capacity  
Stages  
Field  
Configuration  
Date and  
Time  
Set Points  
(Current Operating)  
Service  
Configuration  
Leaving Chiller  
Fluid Alert Limit  
6
7
Temperatures  
Pressures  
Analog Inputs  
Discrete Inputs  
Outputs  
Period 4  
Period 5  
Period 6  
Period 7  
Period 8  
HOLIDAYS  
8
9
10  
11  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — Accessing Functions and Subfunctions  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
OPERATION  
EXPANSION  
To access a function, press  
subfunction no. and function  
name key. Display shows sub-  
function group.  
RESET  
RESET SETPOINTS  
To move to other elements,  
scroll up or down using arrow  
keys. NOTE: These  
displays do not show if  
control is not configured  
for reset.  
CRT1 x  
COOL RESET AT 20 MA  
CRT2N x  
CRT2F x  
CRT2D x  
COOL RTEMP (NO RESET)  
COOL RTEMP (FULL RESET)  
COOL DEGREES RESET  
When the last element in a  
subfunction has been displayed,  
the first element is repeated.  
RESET  
CRT1 x  
RESET SETPOINTS  
COOL RESET AT 20 MA  
To move to next subfunction  
it is not necessary to use  
subfunction number. Press  
function name key to ad-  
vance display through all  
subfunctions within a  
function and then back  
to the first.  
DEMAND  
TIME  
DEMAND LIMIT SETPOINTS  
CURRENT TIME AND DAY OF  
WEEK  
SETPOINT  
UNIT SETPOINTS  
To move to another function,  
either depress function name  
key for desired function  
(display shows the first  
subfunction),  
X ALARMS  
STAGE  
THERE ARE n ALARMS  
or  
Access a specific sub-  
function by using the sub-  
function number and the  
function name key.  
CAPACITY STAGING  
INFORMATION  
Table 9 — Keypad Directory  
STATUS  
SUBFUNCTION  
KEYPAD ENTRY  
DISPLAY  
COMMENT  
1 AUTOMATIC DISPLAY  
Refer to Automatic Display Operation/Default Display section on page 25.  
2 ALARMS/ALERTS  
X ALARMS  
R S AL  
Number of Tripped Alarms/Alerts  
Reset all Alarms/Alerts  
ALARM* X  
ALARM* X  
ALARM* X  
ALARM* X  
ALARM* X  
Displays Tripped Alarms/Alerts  
}
To toggle between inputs (Yes/No) Press:  
(no) or  
(yes)  
3 MODES  
X MODES  
X MODE  
X MODE  
X MODE  
X MODE  
Number of Modes in Effect  
Displays Mode in Effect  
}
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 — Keypad Directory (cont)  
STATUS (cont)  
SUBFUNCTION  
4 STAGE  
KEYPAD ENTRY  
DISPLAY  
STAGE  
COOL X  
CAPT X  
CAPA X  
CAPB X  
AVAIL X  
AV A X  
COMMENT  
Capacity Staging Information  
Number of Requested Stages  
Percent of Total Capacity  
Percent Circuit A Total Capacity  
Percent Circuit B Total Capacity  
Percent Available Capacity  
Percent Circuit A Available Capacity  
Percent Circuit B Available Capacity  
Demand Limit Set Point (percent)  
Circuit A Compressor Relay Status  
Circuit B Compressor Relay Status  
AV B X  
LMT X†  
CIRA X  
CIRB X  
SMZ X  
Load/Unload Factor for Compressors  
Factor = 1 Unloader Factor = 0.6  
5 SET POINT  
SETPOINT  
SET X  
Fluid Set Point Information  
Set Point (F)  
MSP X  
TW X  
Modified Set Point = Set Point + Reset (F)  
Actual Control Temperature (F)  
6 TEMPERATURE  
TEMPS  
EWT X  
LWT X  
SCTA X  
SSTA X  
CTA X  
Temperature Information (F)  
Cooler Entering Fluid Temperature (F)  
Cooler Leaving Fluid Temperature (F)  
Circuit A Saturated Condenser Temperature (F)  
Circuit A Saturated Suction Temperature (F)  
Compressor A1 Suction Temperature (F)  
Circuit A Suction Superheat (F)  
SHA X  
SCTB X  
SSTB X  
CTB X  
SHB X  
SPC X  
OAT X  
Circuit B Saturated Condenser Temperature (F)  
Circuit B Saturated Suction Temperature (F)  
Compressor B1 Suction Temperature (F)  
Circuit B Suction Superheat (F)  
Space Temperature (F)  
Outdoor-Air Temperature (F)  
LEGEND  
*Will read ALARM or ALERT as appropriate.  
†Must be configured.  
CCN  
EXV  
MOP  
Carrier Comfort Network  
Electronic Expansion Valve  
Maximum Operating Pressure  
**If applicable.  
††Not manually resettable.  
NOTE: If metric option is selected under  
, temperature  
expressed as Celsius and pressure will be expressed as kPa.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 — Keypad Directory (cont)  
STATUS (cont)  
SUBFUNCTION  
7 PRESSURE  
KEYPAD ENTRY  
DISPLAY  
PRESSURE  
MM DD YY  
DPA X  
COMMENT  
Refrigerant System Pressure (psig)  
Date of Last Calibration  
Circuit A Discharge Pressure (psig)  
Circuit A Suction Pressure (psig)  
Circuit A Discharge/Suction (psig)  
Circuit A Oil Pressure Differential (psig)  
Circuit B Discharge Pressure (psig)  
Circuit B Suction Pressure (psig)  
Circuit B Discharge/Suction (psig)  
Circuit B Oil Pressure Differential (psig)  
SPA X  
XXXX XXX  
OPA X  
DPB X  
SPB X  
XXXX XXX  
OPB X  
8 ANALOG  
ANALOG  
REF X  
Status of Analog Inputs  
Transducer Supply Voltage (volts)  
Demand 4-20 mA Signal (mA)  
Reset 4-20 mA Signal (mA)  
LMT X†  
RST X†  
9 INPUTS  
SW INPUT  
SPW X†  
DL1 X†  
Status of Switch Inputs  
Dual Set Point Switch (open/closed)  
Demand Limit Switch 1 (open/closed)  
Demand Limit Switch 2 (open/closed)  
DL2 X†  
10 OUTPUTS  
OUTPUTS  
ALMR X  
FRA1 X  
FRA2 X  
FRB1 X  
FRB2 X  
CHWP X†  
ULA1 X  
ULA2 X†  
ULB1 X  
ULB2 X†  
LLSA X  
Status of Outputs  
Alarm Relay K3 (on/off)  
Fan Relay K1 (on/off)  
Fan Relay K2 (on/off)  
Fan Relay K4 (on/off)  
Fan Relay K5 (on/off)  
Cooler Water Pump Relay K6 (on/off)  
Unloader A1 (on/off)**  
Unloader A2 (on/off)**  
Unloader B1 (on/off)**  
Unloader B2 (on/off)**  
Liquid Line Solenoid A  
Liquid Line Solenoid B  
EXVA Percent Open†  
LLSB X  
EXVA X  
LEGEND  
*Will read ALARM or ALERT as appropriate.  
†Must be configured.  
**If applicable.  
CCN  
EXV  
MOP  
Carrier Comfort Network  
Electronic Expansion Valve  
Maximum Operating Pressure  
††Not manually resettable.  
NOTE: If metric option is selected under  
, temperature  
expressed as Celsius and pressure will be expressed as kPa.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 — Keypad Directory (cont)  
STATUS (cont)  
SUBFUNCTION  
KEYPAD ENTRY  
DISPLAY  
COMMENT  
10 OUTPUTS (cont)  
EXVB X  
EXVB Percent Open**  
HGBA X†  
HGBB X†  
MMA X†  
MMB X†  
TEST  
Hot Gas Bypass Relay Circuit A (on/off)**  
Hot Gas Bypass Relay Circuit B (on/off)**  
MotormasterA Output Percent**  
Motormaster B Output Percent**  
To use Test function, LOCAL/ENABLE-STOP-CCN switch must be in STOP position. To operate a test, scroll to desired test.  
Then, press  
SUBFUNCTION  
1 OUTPUTS  
to start test. Press  
to stop test.  
KEYPAD ENTRY  
DISPLAY  
COMMENT  
OUTPUTS  
Test Outputs  
8.8.8.8.8.8.8.8  
ALMR X  
FRA1 X  
FRA2 X  
FRB1 X  
FRB2 X  
CHWP X†  
LSVA X  
Display Check  
Energize Alarm Relay K3 (on/off)  
Energize Fan Relay A1 K1 (on/off)  
Energize Fan Relay A2 K2 (on/off)  
Energize Fan Relay B1 K4 (on/off)  
Energize Fan Relay B2 K5 (on/off)  
Energize Cooler Water Pump K6 (on/off)  
Energize Liquid Line Solenoid A (on/off)**  
Energize Liquid Line Solenoid B (on/off)**  
Enter Desired EXVA Position (percent)**  
Enter Desired EXVB Position (percent)**  
Energize Hot Gas Bypass Relay A (on/off)**  
Energize Hot Gas Bypass Relay B (on/off)**  
Enter Desired Motormaster A Output Signal (percent)**  
Enter Desired Motormaster B Output Signal (percent)**  
LSVB X  
EXVA X  
EXVB X  
HGBA X†  
HGBB X†  
MMA X†  
MMB X†  
(yes)  
To toggle between inputs (Yes/No) Press:  
(no) or  
During compressor test, compressors start and run for  
10 seconds. Compressor service valves and liquid line  
valves must be open. Energize crankcase heaters 24 hours  
prior to performing compressor tests.  
SUBFUNCTION  
KEYPAD ENTRY  
DISPLAY  
COMMENT  
2 COMPRESSORS AND  
UNLOADERS  
COMP  
Compressor and Unloader Test  
CPA1 X  
Test Compressor A1 (on/off)  
Test Compressor A2 (on/off)**  
CPA2 X†  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 — Keypad Directory (cont)  
TEST (cont)  
SUBFUNCTION  
KEYPAD ENTRY  
DISPLAY  
COMMENT  
Test Compressor A3 (on/off)**  
Test Compressor A4 (on/off)**  
Test Compressor B1 (on/off)  
Test Compressor B2 (on/off)**  
Test Compressor B3 (on/off)**  
Test Compressor B4 (on/off)**  
Energize Unloader A1 (on/off)**  
Energize Unloader A2 (on/off)**  
Energize Unloader B1 (on/off)**  
Energize Unloader B2 (on/off)**  
2 COMPRESSORS AND  
UNLOADERS (cont)  
CPA3 X†  
CPA4 X†  
CPB1 X  
CPB2 X†  
CPB3 X†  
CPB4 X†  
UNA1 X  
UNA2 X†  
UNB1 X  
UNB2 X†  
3 CALIBRATE  
TRANSDUCERS  
XDR CAL  
CDPA X  
CSPA X  
COPA X  
CDPB X  
CSPB X  
COPB X  
Transducer Calibration  
Circuit A Discharge Pressure (psig)  
Circuit A Suction Pressure (psig)  
Circuit A Oil Pressure (psig)  
Circuit B Discharge Pressure (psig)  
Circuit B Suction Pressure (psig)  
Circuit B Oil Pressure (psig)  
SCHEDULE  
The Schedule function key  
is used to configure the occupancy schedule. The clock select subfunction can be used for  
unoccupied shutdown or unoccupied setback depending on the cooling set point control configuration. The Schedule function  
described is for clock 1, which is the internal clock. Password required for all subfunctions except override.  
SUBFUNCTION  
1 OVERRIDE  
KEYPAD ENTRY  
DISPLAY  
COMMENT  
OVRD X  
Number of Override Hrs (0 - 4 Hrs)  
For example, to extend current occupied mode for 3 hrs, press:  
OVRD 3  
Extended Occupied Time  
2 CLOCK SELECT  
3 PERIOD 1  
CLOCK XX  
Type of Clock Control  
0 = No Clock, 1 = Clock 1 (Internal)  
PERIOD 1  
OCC HH.MM  
UNO HH.MM  
MON X  
Period 1 Time Schedule  
Occupied Time  
Yes = Schedule Opera-  
tional for that day  
Unoccupied Time  
Monday Flag (yes/no)  
Tuesday Flag (yes/no)  
Wednesday Flag (yes/no)  
Thursday Flag (yes/no)  
TUE X  
WED X  
THU X  
LEGEND  
††Not manually resettable.  
CCN  
EXV  
MOP  
Carrier Comfort Network  
Electronic Expansion Valve  
Maximum Operating Pressure  
NOTE: If metric option is selected under  
, temperature  
expressed as Celsius and pressure will be expressed as kPa.  
*Will read ALARM or ALERT as appropriate.  
†Must be configured.  
**If applicable.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 — Keypad Directory (cont)  
SCHEDULE (cont)  
SUBFUNCTION  
3 PERIOD 1 (cont)  
KEYPAD ENTRY  
DISPLAY  
COMMENT  
Friday Flag (yes/no)  
FRI X  
SAT X  
SUN X  
HOL X  
(yes)  
Saturday Flag (yes/no)  
Sunday Flag (yes/no)  
Holiday Flag (yes/no)  
To toggle between inputs (Yes/No) Press:  
4 PERIOD 2  
(no) or  
PERIOD 2  
Period 2 Time Schedule  
PERIOD 3 ...  
PERIOD 7  
5 PERIOD 3 ... 9 PERIOD 7  
Period 3 ... Period 7 Time Schedule  
Period 8 Time Schedule  
...  
10 PERIOD 8  
11 HOLIDAYS  
PERIOD 8  
HOLIDAYS  
Define Calendar Holidays  
Holiday Date 1  
DAT MM.DD  
New = Unassigned Holiday Date  
DAT MM.DD.NN  
Holiday Date 30  
For example: To enter July 4th holiday press: 07.04.01  
operation, refer to Schedule Function section on page 44.  
. Display shows Jul 04. For further information on the Schedule function and its  
SERVICE  
To view and modify configurations, the password must be entered under the log on subfunction.  
SUBFUNCTION  
KEYPAD ENTRY  
DISPLAY  
COMMENT  
1 LOG ON AND LOG OFF  
PASSWORD  
Enter Password/Disable Password Protection  
LOGGEDON  
Logged On  
At this time, configurations may be modified. When finished viewing and/or modifying configurations, log out as follows:  
LOGGEDON  
LOG OFF  
Disable Password Protection  
EXIT LOG  
Logged Off/Enable Password Protection  
2 VERSION  
VERSION  
Software Information  
XXXXXXXX  
Version No. of Software (CESRXX)  
The next 3 subfunctions provide the ability to modify configurations. Refer to separate Installation, Start-Up, and Service Instructions  
supplied with unit for further information on changing configurations.  
To change a configuration, enter the new configuration and press  
while on the correct configuration.  
3 FACTORY  
FACT CFG  
Factory Configuration Codes  
CONFIGURATION  
XXXXXXXX  
XXXXXXXX  
XXXXXXXX  
XXXXXXXX  
Configuration Code 1  
Configuration Code 2  
Configuration Code 3  
Configuration Code 4  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 — Keypad Directory (cont)  
SERVICE (cont)  
SUBFUNCTION  
KEYPAD ENTRY  
DISPLAY  
COMMENT  
3 FACTORY  
CONFIGURATION (cont)  
XXXXXXXX  
XXXXXXXX  
XXXXXXXX  
Configuration Code 5  
Configuration Code 6  
Configuration Code 7  
4 FIELD  
CONFIGURATION  
FLD CFG  
ENO X  
Adjustable Field Configuration  
CCN Element Address  
BUS X  
CCN Bus Number  
BAUD X  
FLUID X  
UNITS X  
DELAY X  
NULA X  
NULB X  
HGB X  
CCN Baud Rate  
Cooler Fluid Select (water/medium brine)  
Display Unit Select (English/Metric)  
Delay at Power Up (minutes)  
No. Circuit A Unloaders  
No. Circuit B Unloaders  
Hot Gas Bypass Select (used, not used)  
Loading Sequence Select (equal circuit, staged circuit)  
Lead/Lag Sequence Type  
SEQT X  
LEADT X  
OPS X  
Oil Pressure Switch Select (enable/disable)  
Head Pressure Control Type  
HEADT X  
MM X  
(none, air cooled, water cooled)  
MotormasterSelect  
CSPTYP X  
CRTYP X  
ERTYP X  
OATSEL X  
LSTYP X  
RAMP X  
LOCK X  
CPC X  
Cooling Set Point Control Select  
Cooling Reset Control Select  
External Reset Sensor Select  
Outdoor-Air Sensor Select  
Demand Limit Control Select  
Ramp Load Select (enable, disable)  
Cooler Pump Interlock Select  
Cooler Pump Control Select  
REMA X  
ALRST X  
Remote Alarm Option Select (yes/no)  
Allow Local/Stop/CCN Reset of Alarms (yes/no)  
To toggle between inputs (Yes/No) Press:  
(no) or  
(yes)  
5 SERVICE  
CONFIGURATION  
SRV CFG  
XXXXXXXX  
XXXXXXXX  
REFRIG X  
TDTYP X  
OPS X  
Service Configurations  
Configuration Code 8  
Configuration Code 9  
Refrigerant  
Pressure Transducer Select  
Oil Transducer Set Point (psig)  
Low Pressure Set Point (psig)  
Fan Staging Select  
LPS X  
FANTYP X  
SH X  
EXV Superheat Set Point (F)  
EXV MOP Set Point (F)  
Z Multiplier  
MOP X  
ZM X  
LEGEND  
**If applicable.  
††Not manually resettable.  
CCN  
EXV  
MOP  
Carrier Comfort Network  
Electronic Expansion Valve  
Maximum Operating Pressure  
NOTE: If metric option is selected under  
, temperature  
expressed as Celsius and pressure will be expressed as kPa.  
*Will read ALARM or ALERT as appropriate.  
†Must be configured.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 — Keypad Directory (cont)  
HISTORY  
SUBFUNCTION  
1 RUN TIME  
KEYPAD ENTRY  
DISPLAY  
COMMENT  
RUN TIME  
HR X  
Run Time Information  
Total Hrs Unit Has a Comp Operating  
Circuit A Run Time  
HRA X  
HRB X  
HA1 X  
HA2 X  
HA3 X  
HA4 X  
HB1 X  
HB2 X  
HB3 X  
HB4 X  
Circuit B Run Time  
Circuit A, Comp A1 Operating Hours  
Circuit A, Comp A2 Operating Hours**  
Circuit A, Comp A3 Operating Hours**  
Circuit A, Comp A4 Operating Hours**  
Circuit B, Comp B1 Operating Hours  
Circuit B, Comp B2 Operating Hours**  
Circuit B, Comp B3 Operating Hours**  
Circuit B, Comp B4 Operating Hours**  
2 STARTS  
STARTS  
CY X  
Starts Information  
Cycles from Stage 0 to Stage 1  
Circuit A Starts  
CYA X  
CYB X  
CA1 X  
CA2 X  
CA3 X  
CA4 X  
CB1 X  
CB2 X  
CB3 X  
CB4 X  
Circuit B Starts  
Circuit A, Comp A1 Starts  
Circuit A, Comp A2 Starts**  
Circuit A, Comp A3 Starts**  
Circuit A, Comp A4 Starts**  
Circuit B, Comp B1 Starts  
Circuit B, Comp B2 Starts**  
Circuit B, Comp B3 Starts**  
Circuit B, Comp B4 Starts**  
3 ALARM/ALERT  
HISTORY††  
ALRMHIST  
ALARM X  
ALARM X  
ALARM X  
ALARM X  
ALARM X  
ALARM X  
ALARM X  
ALARM X  
ALARM X  
ALARM X  
Last 10 Alarms/Alerts  
Alarm/Alert Description  
}
LEGEND  
*Will read ALARM or ALERT as appropriate.  
†Must be configured.  
CCN  
EXV  
MOP  
Carrier Comfort Network  
**If applicable.  
Electronic Expansion Valve  
††Not manually resettable.  
Maximum Operating Pressure  
NOTE: If metric option is selected under  
, temperature  
expressed as Celsius and pressure will be expressed as kPa.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 — Keypad Directory (cont)  
SET POINT  
To read a set point, go to proper subfunction and read desired set point. To change a set point, enter new set point value, then press  
LOCAL/ENABLE-STOP-CCN switch must be in LOCAL/ENABLE or STOP position.  
.
SUBFUNCTION  
1 SET POINTS  
KEYPAD ENTRY  
DISPLAY  
COMMENT  
SET POINT  
CSP1 X  
Unit Set Point  
Chiller Fluid Set Point 1 (F)  
Chiller Fluid Set Point 2 (F)  
CSP2 X  
HSPA X  
Head Pressure Set Point Circuit A (F)  
Head Pressure Set Point Circuit B (F)  
Cooling Ramp Loading Rate (F)  
HSPB X  
CRAMP X  
2 RESET SET POINTS  
RESET  
Reset Set Points  
CRT1 X  
Cooling reset at 20 mA (F)  
CRT2N X  
CRT2F X  
CRT2D X  
CRT3N X  
CRT3F X  
CRT3D X  
Reference Temperature at No Reset (F)  
Reference Temperature at Full Reset (F)  
Total Degrees of Reset (F)  
Chiller Fluid T at No Reset (F)  
Chiller Fluid T at Full Reset (F)  
Total Degrees of Reset (F)  
3 DEMAND SET POINTS  
DEMAND  
DLS1 X†  
DLS2 X†  
DL20 X  
Demand Set Points  
Demand Switch 1 Set Point (percent)  
Demand Switch 2 Set Point (percent)  
Demand Limit at 20 mA (percent)  
Loadshed Group Number  
DLGN X  
LSDD X  
TIME X  
Loadshed Demand (percent)  
Minimum Loadshed Time (minutes)  
4 DATE AND TIME  
DATE.TIME  
Date, Time and Day of Week  
DOW.HR.MIN  
Day 1 = Mon, 2 = Tues. . .7 = Sun  
Hours are displayed in 24-hr time. Decimal point serves as colon.  
Month.Day.Year. When entering date, enter a decimal  
point between entries. Each entry must be two numbers.  
MM.DD.YR  
LMT X  
5 LEAVING CHILLER  
FLUID ALERT LIMIT  
Leaving Chiller Fluid Alert Limit (F)  
LEGEND  
*Will read ALARM or ALERT as appropriate.  
†Must be configured.  
CCN  
EXV  
MOP  
Carrier Comfort Network  
**If applicable.  
Electronic Expansion Valve  
††Not manually resettable.  
Maximum Operating Pressure  
NOTE: If metric option is selected under  
, temperature  
expressed as Celsius and pressure will be expressed as kPa.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STATUS FUNCTION — This function shows the rotating  
display, current status of alarm and alert (diagnostic) codes,  
capacity stages, operating modes, chilled water set point, all  
measured system temperatures and pressures, superheat val-  
ues, pressure switch positions, analog inputs, and switch in-  
puts. These subfunctions are defined on pages 36 and 37.  
To reset alarms/alerts using keypad and display module:  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
COMMENTS  
Reset all alarms/alerts  
function disabled  
RSAL DSB  
RSAL ENB  
Reset all alarms/alerts  
function enabled  
(Rotating Display)  
(Modes) — The operating mode codes are dis-  
played to indicate the operating status of the unit at a given  
time. See Table 10.  
(Alarms/Alerts) — Alarms and alerts are messages  
that one or more faults have been detected. Each fault is as-  
signed a code number which is reported with the alarm or  
alert. See Table 10 for code definitions. The codes indicate  
failures that cause the unit to shut down, terminate an option  
(such as reset) or result in the use of a default value as set  
point.  
To enter the MODES subfunction, press  
and  
press the key to determine if more than one mode ap-  
plies. See Example 2 to read current mode with expansion.  
Up to 10 codes can be stored at once. To view them  
Example 2 — Reading Current Operating Modes  
in sequence, press  
to enter the alarm/alert dis-  
to move to the individual dis-  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
COMMENTS  
plays and then press  
TUE 15:45  
LOCAL ON  
CLOCK ON  
8 MODE  
Keypad has not been used for at  
least 10 minutes. Rotating summary  
display appears on screen  
plays. Press  
after a code has been displayed. The mean-  
ing of the code scrolls across the screen. See Example 1.  
COOL 1  
Example 1 — Reading Alarm Codes  
0 ALARMS  
3 MINS  
KEYPAD  
ENTRY  
DISPLAY  
COMMENTS  
2 MODES  
LOCAL ON  
8 MODE  
There are 2 modes currently in effect  
Unit is on by chiller on/off switch  
Temperature reset is in effect  
RESPONSE  
TUE 12:45  
LOCAL ON  
CLOCK ON  
13 MODE  
8 MODE  
Keypad has not been used for  
at least 10 minutes. Alternating  
summary display appears on  
screen  
COOL 1  
2 ALARMS  
3 MINS  
(Stage) — This subfunction displays the capac-  
ity stage number. See Tables 4A-4C for compressor loading  
sequence. To enter the STAGE subfunction, press  
2 ALARMS  
RSAL DSB  
2 alarms/alerts detected  
Reset all alarms/alerts  
First alarm/alert code  
and press the  
Continue pressing  
to display the stage number.  
for the following information:  
ALARM 9  
• Number of requested stages.  
COOLER LEAVING  
FLUID THERMISTOR Explanation of alarm/alert code  
FAILURE  
• Percent of total unit capacity being utilized.  
• Percent of each circuit capacity being utilized.  
• Percent of total capacity available.  
Second alarm/alert code.  
ALARM 42  
Cooler freeze protection  
COOLER FREEZE  
• Percent of capacity available in each circuit.  
Explanation of alarm/alert code  
PROTECTION  
• Demand limit set point in effect (can be any value be-  
tween 0% and 100%).  
• Status of each compressor relay. When a compressor is  
on, the number of that compressor is displayed. If a com-  
pressor is off, a 0 is displayed. For example: In a given  
circuit, if compressors 1 and 3 are running, and 2 and 4 are  
not running, 0301 is displayed for that circuit.  
• Load/Unload factor for compressors. This factor is an in-  
dication of when a step of capacity is added or subtracted.  
Its value can range from slightly less than –1.0 to slightly  
more than +1.0. When load/unload factor reaches +1.0, a  
compressor is added. When the load/unload factor reaches  
–1.0, a compressor is subtracted. If compressor unloaders  
are used, at –.6 a compressor is unloaded and at +.6, a  
compressor is loaded up.  
When a diagnostic (alarm or alert) code is stored in the  
display and the machine automatically resets, the code is de-  
leted. Codes for safeties which do not automatically reset  
are not deleted until the problem is corrected and either the  
machine is switched to STOP position, then back to LOCAL/  
ENABLE or CCN position, or by using the keypad and dis-  
play module.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 10 — Operational and Mode Display Codes  
(Set Point) — This subfunction displays leaving  
The operating modes are displayed by name or code num-  
ber, to indicate the operating status of the unit at a given  
time. The modes are:  
fluid temperature and leaving chilled fluid set point. If unit  
is programmed for dual set point, the chilled fluid set point  
currently in effect (either occupied or unoccupied) is  
displayed. If reset is in effect, the unit operates to the modi-  
fied chilled fluid set point. This means the leaving fluid tem-  
perature may not equal the chilled fluid set point. The  
modified chilled fluid set point can also be displayed in the  
Status function. To enter the set point subfunction,  
CODE  
DESCRIPTION  
Unit is off. LOCAL/ENABLE-STOP-CCN switch is in  
OFF position, or LOCAL/ENABLE-STOP-CCN switch  
may be in LOCAL position with external ON/OFF  
switch in OFF position.  
LOCAL OFF  
press  
and press  
to display the set point fol-  
Unit is off due to CCN network command. LOCAL/  
ENABLE-STOP-CCN switch is in CCN position.  
CCN OFF  
lowed by the modified leaving chilled fluid set point and ac-  
tual control temperature.  
Unit is off due to internal clock schedule. LOCAL/  
ENABLE-STOP-CCN switch is in LOCAL position.  
CLOCK OFF  
(Temperature) — The temperature subfunction dis-  
plays the readings at temperature sensing thermistors.  
Unit is on. LOCAL/ENABLE-STOP-CCN switch is in  
LOCAL ON LOCAL position. If external ON/OFF switch is used,  
it will be in ON position.  
To read a temperature, enter  
sired temperature using the  
order of readouts. This subfunction also displays the satu-  
rated refrigerant temperatures corresponding to the suction  
and discharge pressures measured by the compressor  
transducers.  
, then scroll to de-  
Unit is on due to CCN command. LOCAL/ENABLE-  
CCN ON  
STOP-CCN switch is in CCN position.  
key. See Table 9 for the  
Unit is on due to internal clock schedule or occu-  
CLOCK ON pied override function. LOCAL/ENABLE-STOP-  
CCN switch is in LOCAL/ENABLE position.  
Dual set point is in effect. In this mode, unit contin-  
ues to run in unoccupied condition, but leaving fluid  
MODE 7  
set point is automatically increased to a higher level  
(CSP2 set point is in SET function).  
(Pressure) — This subfunction displays suction,  
discharge, and net oil pressure at lead compressor of each  
circuit of unit.  
Temperature reset is in effect. In this mode, unit is  
using temperature reset to adjust leaving fluid set  
point upward, and unit is currently controlling to the  
MODE 8  
modified set point. The set point can be modified based  
(Analog Inputs) — This subfunction displays  
on return fluid, outdoor-air temperature, or space tem-  
perature.  
analog inputs, if any. Press  
, then press  
. The  
Demand limit is in effect. This indicates that ca-  
pacity of unit is being limited by demand limit control  
option. Because of this limitation, unit may not  
be able to produce the desired leaving fluid  
temperature.  
transducer supply voltage, 4-20 mA reset signal can be dis-  
played. This is useful for problem diagnosis prior to using  
the test function.  
MODE 9  
Flotronic™ System Manager (FSM) is controlling the  
chiller.  
(Discrete Inputs) — This subfunction displays sta-  
MODE 10  
MODE 11  
tus (open/closed) of discrete input switch where applicable.  
Status of dual set point switch and demand limit switches 1  
and 2 can be displayed. This is useful for problem diagnosis  
prior to using the test function.  
Not applicable.  
Ramp load (pulldown) limiting is in effect. In this mode,  
the rate at which leaving fluid temperature is dropped  
is limited to a predetermined value to prevent com-  
pressor overloading. See CRAMP set point in the  
SET function in Table 9. The pulldown limit can be  
modified, if desired, to any rate from .2 F to 2 F  
(.1° to 1° C)/minute.  
MODE 12  
MODE 13  
(Outputs) — This function displays on/off sta-  
tus of alarm relay, all fan relays, and chilled water pump  
relay. It also displays on/off status of compressor unloaders  
(if used). The position of each EXV (in percent open) can be  
displayed.  
Timed override is in effect. This is a 1 to 4 hour tem-  
porary override of the programmed schedule, forc-  
ing unit to occupied mode. Override can be imple-  
mented with unit under LOCAL/ENABLE or CCN  
control. Override expires after each use.  
TEST FUNCTION — The test function operates the diag-  
nostic program. To initiate test function, the LOCAL/  
ENABLE-STOP-CCN switch must be in STOP position.  
Low cooler suction protection is in effect. In this mode,  
circuit capacity is not allowed to increase if cooler  
saturated suction temperature is 20° F (11° C) for  
fluid or 30° F (16° C) for brine or more below leaving  
fluid temperature, and saturated suction tempera-  
ture is less than 32 F (0° C). If these conditions per-  
sist beyond 10 minutes, circuit is shut down and fault  
code 44 or 45 is displayed.  
To reach a particular test, press its subfunction number,  
MODE 14  
then scroll to desired test by pressing  
. Press  
to terminate or exit a  
key after a test has started advances  
to  
start a test. Press  
test. Pressing the  
or  
or  
MODE 15  
MODE 16  
MODE 17  
MODE 18  
Water System Manager is controlling the chiller.  
Slow change override is in effect.  
system to next test, whether current test is operating or has  
timed out. Once in the next step, you may start  
X minute off-to-on delay is in effect.  
Low suction superheat protection is in effect.  
test by pressing  
or advance past it by pressing  
.
CCN — Carrier Comfort Network  
While the unit is in test, you may leave test function and  
access another display or function by pressing appropriate  
keys. However, a component that is operating when an-  
other function is accessed remains operating. You must  
re-enter test function and press  
to shut down the com-  
ponent. Components with a timed operating limit time out  
normally even if another function is accessed.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SET POINT FUNCTION — Set points are entered through  
the keypad. Set points can be changed within the upper and  
lower limits, which are fixed. The ranges are listed below.  
Keypad entry  
allows the operator to make the  
:
following checks by using  
• LID display check. Proper display is 8.8.8.8.8.8.8.8.  
• Operation of alarm relay.  
Chilled Fluid Set Point  
Water:  
38 to 86 F (3.3 to 30 C)  
Medium Brine:  
14 to 86 F (–10 to 30 C)  
• Operation of condenser fans.  
• Operation of chilled fluid pump.  
• Operation of liquid line solenoids.  
• Operation of the hot gas bypass relays.  
• Operation of EXVs. To drive EXV fully open, enter  
Pulldown Set Point  
0.2 to 2.0 F (0.11 to 1.1 C)/min.  
(100% open). To drive EXV fully closed, en-  
ter  
(0% open).  
Reset Set Points  
Maximum Reset Range:  
• Operation of each remote alarm.  
• Operation of Motormastersignals.  
–30° to 30° F (–17° to 17° C)  
External Temperature Reset –40 to 240 F  
(–40 to 118 C)  
Chiller Fluid T: 0° to 15° F  
(0° to 8° C)  
External Signal Reset 4 to 20 mA  
Keypad entry  
compressor unloader operational tests.  
accesses the compressor and  
During compressor operational tests, compressor starts  
and runs for 10 seconds. Compressor service valves must  
be open. Energize crankcase heaters 24 hours prior to  
performing compressor tests.  
Demand Limit Set Points  
Switch Input:  
Step 1 — 0 to 100% Capacity Reduction  
Step 2 — 0 to 100% Capacity Reduction  
External Signal:  
Maximum Demand Limit 4 to 20 mA  
Minimum Demand Limit 4 to 20 mA  
Since test function checks only certain outputs, it is good  
practice to also check all inputs and outputs accessible  
through the status function. These are located at  
,
Loadshed Demand Delta: 0 to 60%  
, and (see Table 9). If keypad is not used  
for 10 minutes, unit automatically leaves test function and  
resumes rotating display. See Example 3.  
Maximum Loadshed Time: 0 to 120 min.  
Set points are grouped in subfunctions as follows:  
Subfunction displays chiller fluid set points.  
Example 3 — Using Test Function  
a. The first value shown is the occupied chilled fluid set  
point.  
KEYPAD DISPLAY  
COMMENTS  
ENTRY RESPONSE  
b. The next value displayed depends on how the sched-  
ule function has been programmed. (See pages 44-  
47.) If dual set point has been selected, the next set  
COMP  
Factory/field test of compressors  
subfunction of test function  
CPA 1 OFF Circuit A, Compressor 1A test  
point after  
has been pressed is the second chilled  
CPA 1 ON  
Pressing ENTR starts the test:  
when the compressor should be running  
the display shows CPA1 on  
fluid set point. If single set point or inactive sched-  
ule has been selected in the schedule function,  
CPA 1 OFF If the test is allowed to time out (10 sec-  
onds) the display will show CPA1 off  
then when  
is pressed, the display shows the  
head pressure set points, one for each circuit. These  
are utilized only if the set point controlled method of  
CPA 2 OFF Pressing the down arrow key advances the  
system to Circuit A, compressor 2 test  
head pressure control is selected in  
.
NOTE: Once a compressor has been run using the  
it is not allowed to run again for 30 seconds.  
function,  
c. The final value displayed when the  
is pressed  
is the cooling ramp loading rate. This is the maximum  
rate at which the leaving chilled fluid is allowed to  
drop, and can be field set from 0.2 to 2.0 F (.11° to  
1.1° C)/minute. This value is not displayed unless the  
function is enabled (see Adjustable Field Configura-  
tions on page 44).  
accesses the transducer calibration subfunction.  
All transducers must be calibrated in order for the unit to  
operate. Refer to Pressure Transducers section on page 60  
for calibration procedure.  
HISTORY FUNCTION — Pressing  
plays total unit run time, total run time for each circuit, and  
total run time for each compressor.  
and  
dis-  
Reading and Changing Set Points — Example 4 shows how  
to read and change the chilled fluid set point. Other set points  
can be changed by following the same procedure. Refer to  
Table 9 for the sequence of display of set points in each sub-  
function.  
Pressing  
total starts for each circuit, and total starts for each com-  
pressor. Pressing and displays the last 10 alarms  
along with a description of each alarm.  
and  
displays total unit starts, the  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 4 — Reading and Changing  
Chilled Fluid Set Point  
configuration. Select one of the 4 choices for type of reset:  
Return Fluid Reset, External Temperature Reset, 4-20 mA  
External Signal Reset, or 4-20 mA Internal Signal Reset.  
If dual set point control is enabled (see Field Wiring sec-  
tion on page 69), the amount of reset is applied to whichever  
set point is in effect at the time.  
Examples 5A-5C demonstrate how to activate reset. Ex-  
ample 6 demonstrates how to change the type of reset. As-  
sume that reset is to be based on return fluid temperature,  
the desired reset range is to be 0° to 10° F (0° to 5.5° C) and  
full load is a 10° F (5.5° C) drop across the cooler. See  
Fig. 5.  
Activating reset based on external temperature or  
4-20 mA signal is done the same way, except the reference  
set point range is –40° to 240° F (–40° to 115° C), or 4 to  
20 mA depending on which method was selected at the field  
configuration step.  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
COMMENTS  
SET POINT  
CSP1 44.0  
System set points  
Present occupied chilled fluid  
set point is 44.0 F  
CSP1 42.0  
Press the  
.
Display shows new occupied  
chilled fluid set point is 42.0 F  
Present unoccupied chilled fluid  
set point is 44.0 F  
CSP2 44.0  
CSP2 50.0  
Press the  
. Display  
shows new unoccupied chilled  
fluid set point is 50.0 F  
RESET  
Displays the maximum reset  
set point. The minimum and  
maximum reference reset  
set points can also be displayed.  
These set points are not  
accessible when reset type has  
been configured for NONE in  
the service function.  
Example 5A — External Reset  
In this example, the unit set point is reset from full load  
at 90 F (32 C) to a maximum reset value of 10 F (5.5 C) at  
20 F (–6.7 C) outdoor ambient.  
NOTE: All temperatures given in this example are in F.  
Subfunction displays temperature reset set points.  
KEYPAD  
ENTRY  
DISPLAY  
COMMENTS  
RESPONSE  
Temperature Reset Based on Return Fluid Temperature —  
The control system is capable of providing leaving fluid tem-  
perature reset based on return fluid temperature. Because the  
temperature difference between leaving and return tempera-  
ture is a measure of the building load, return fluid tempera-  
ture reset is essentially an average building load reset method.  
Under normal operation, the chiller maintains a constant  
leaving fluid temperature approximately equal to chilled fluid  
set point. As building load drops from 100% down to 0%,  
entering cooler fluid temperature drops in proportion to load.  
Thus, temperature drop across the cooler drops from a typi-  
cal 10 F (5.5 C) at full load to a theoretical 0° F (0° C) at no  
load. See Fig. 5.  
At partial load, leaving chilled fluid temperature may be  
lower than required. If this is allowed to increase (reset), the  
efficiency of the chiller increases. Amount of reset can be  
defined as a function of cooler temperature drop, as shown  
in Fig. 5. This is a simple linear function that requires  
3 pieces of input data for the set function that will vary de-  
pending on measurement method used as follows (see  
Table 11):  
FLD CFG  
CRTYP 0  
CRTYP 2  
ERTYP 0  
ERTYP 1  
RESET  
Scroll past to reset type  
External reset selected  
Scroll past to space  
thermistor sensor selected  
OAT selected  
Temperature for no  
reset is 0  
CRT2N 0  
CRT2N 90  
CRT2F 0  
CRT2F 20  
CRT2D 0  
CRT2D 10  
Temperature for no  
reset is 90  
Temperature for maximum  
reset is 0  
Temperature for maximum  
reset is 20  
Maximum reset is 0  
Maximum reset is 10  
NOTE: Reset set points are not accessible unless the reset  
function is enabled first. This is done as a field  
Table 11 — Reset Amounts  
MEASUREMENT METHOD  
OAT/Occupied Space  
or Internal/External  
INPUT DATA DESCRIPTION  
4-20 mA  
Return Water  
Variable  
Limits (F)  
Variable  
Limits (F)  
Variable  
Limits (F)  
Maximum Reset Amount — Allowable range for  
maximum amount which LWT is to be reset.  
CRT1  
–30 to 30  
CRT2D  
–30 to 30  
CRT3D  
–30 to 30  
Maximum Reset Reference — Temperature at  
which maximum reset occurs.  
CRT2F  
CRT2N  
–40 to 240  
–40 to 240  
CRT3F  
CRT3N  
0 to 15  
0 to 15  
Minimum Reset Reference — Temperature at  
which no reset occurs.  
LEGEND  
OAT  
LWT  
Outdoor-Air Temperature  
Leaving Fluid Temperature  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example 5B — 4 to 20 mA and Internally or  
Externally Powered Reset  
In this example, the unit set point is reset from full load  
at 4 mA to a maximum reset value of 10 F (5.5 C) at  
20 mA. Internally powered 4 to 20 mA option is used in this  
example.  
Temperature Reset Based on External Temperature — If de-  
sired, temperature reset can be based on an external tem-  
perature, such as space or outdoor-air temperature. This re-  
quires a thermistor (T10, Part No. 30GB660002) located in  
the space or outdoor air and wired to terminals as follows  
(also see Field Wiring section on page 69 and Fig. 6):  
NOTE: To use externally powered reset, when CRTYP  
4 in/4 out Module — J7-15 and J7-16.  
appears, press  
display. The remainder of the information in the fol-  
lowing example applies to either type of reset.  
so CRTYP 4 appears in the  
At the field configuration step, enter set points as de-  
scribed in Examples 5A-5C on pages 39 and 40. Then  
select external temperature reset by entering  
CRTYP 0 appears. See Fig. 7.  
when  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
COMMENTS  
Temperature Reset Based on 4-20 mA Signal— If desired,  
temperature reset can be based on a 4-20 mA signal. For  
proper connections, refer to Field Wiring section on  
page 69 and Fig. 8.  
FLD CFG  
CRTYP 0  
CRTYP 1  
RESET  
Scroll past to reset type  
Internally powered reset  
selected  
At the field configuration step, select 4-20 mA reset by  
entering  
(internally powered) or  
(externally pow-  
ered) when CRTYP 0 appears. Then enter set points as de-  
scribed previously in Examples 5A-C. See Fig. 8.  
CRT1 0  
Reset at 20 mA is 0  
Reset at 20 mA is 10  
CRT1 10  
Subfunction displays demand limit set points.  
Example 5C — Using Return Fluid  
Temperature Reset  
Demand Limit, 2-Stage Switch Control — This control has  
been designed to accept demand limit signals from a build-  
ing load shedding control. The demand limit function pro-  
vides for 2 capacity steps. The keypad is used to set the 2  
demand limit set points, which range from 100 to 0% of ca-  
pacity. Capacity steps are controlled by 2 field-supplied re-  
lay contacts connected to the designated chiller terminals.  
(See Field Wiring section on page 69 and Fig. 7.)  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
COMMENTS  
Field configuration  
subfunction of  
service function  
FLD CFG  
CSPTYP X  
CRTYP 0  
CRTYP 3  
RESET  
Scroll past single/dual  
Display shows no reset  
type has been selected  
Return fluid temperature  
is selected and activated  
Reset set points  
Fig. 5 — Cooling Return Fluid Reset  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 6 — Cooling External Temperature Reset  
LEGEND  
COMM  
PWR  
SW  
Communications Bus  
Power  
Switch  
NOTE: For specific connection points,  
see Fig. 25 - 29.  
Fig. 7 — 4 IN/4 OUT Options Module Wiring for Reset, Demand Limit, and Dual Set Point  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 8 — 4-20 mA Cooling Temperature Reset  
Example 6 — Changing Reset Type  
Table 12 — Service Functions  
To change type of reset, first log on as shown in  
Table 12. Also refer to Set Point Function section, page 38,  
for information on entering reset set points using reset  
feature.  
To view and modify configurations, the password must be  
entered under the log on subfunction.  
SUB-  
KEYPAD  
ENTRY  
DISPLAY  
COMMENT  
FUNCTION  
Enter Password/  
Disable Password  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
1 Log On  
PASSWORD  
COMMENTS  
LOGGEDON Logged On  
Field configuration  
subfunction of  
FLD CFG  
service function  
NOTE: Configurations may be modified at this time. When  
finished viewing and/or modifying configurations, log out as  
follows:  
Scroll past single cooling  
set point  
CSPTYP 0  
CRTYP 0  
CRTYP 1  
No reset has been  
selected  
LOGGEDON  
LOG OFF  
Internally powered 4-20 mA  
signal reset is selected  
Disable Password  
Protection  
Space or outdoor-air  
temperature reset is  
selected  
Logged Off/  
Enable Password  
Protection  
CRTYP 2  
EXIT LOG  
Return fluid temperature  
reset is selected  
CRTYP 3  
CRTYP 4  
CRTYP 0  
2 Version  
Software  
Information  
VERSION  
Externally powered 4-20 mA  
signal reset is selected  
Version No.  
of Software  
XXXXXXXX  
Reset is deactivated  
Demand Limit, 4 to 20 mA Signal — The controls can also  
accept a 4 to 20 mA signal for load shedding. Input for the  
signal are terminals shown below:  
Externally powered  
Positive lead to J7-5 - 4 In/4 Out Module  
Negative lead to J7-6 - 4 In/4 Out Module  
Internally powered  
Positive lead to J7-6 - 4 In/4 Out Module  
Negative lead to J7-7 - 4 In/4 Out Module  
To use Demand Limit, first enable loadshed, then enter  
demand limit set points. See Example 7A. Closing the first  
stage demand limit contact puts unit on the first demand limit  
level, that is, the unit does not exceed the percentage of ca-  
pacity entered as demand limit stage 1. Closing contacts on  
second-stage demand limit relay prevents unit from exceed-  
ing capacity entered as demand limit stage 2. The demand  
limit stage that is set to the lowest demand takes priority if  
both demand limit inputs are closed.  
The demand limit function must be enabled in order to  
function and may be turned off when its operation is not de-  
sired. The demand limit relays can, in off condition, remain  
connected without affecting machine operation.  
See Field Wiring section on page 69 and Fig. 7.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
the loadshed demand delta, which defines the percent of the  
load to be removed when a loadshed command is in effect.  
The third set point is maximum loadshed time, which de-  
fines the maximum length of time that a loadshed condition  
is allowed to exist. The allowable range for this entry is zero  
to 120 minutes.  
At field configuration step, select 4 to 20 mA loadshed  
by entering (internally powered) or (externally pow-  
ered) when the LSTYP 0 display appears. See Example 7B.  
Then enter set points as follows. In this example, set points  
are coordinates of the demand limit curve shown in Fig. 9.  
Example 7A — Using Demand Limit  
(First Log On as Shown in Table 12)  
Subfunction displays date, time, and day of the week.  
Reading and Changing Time Display — Time is entered and  
displayed in 24-hour time. The day of the week is entered as  
a number.  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
COMMENTS  
1 = Mon, 2 = Tue, 7 = Sun, etc.  
Field configuration sub-  
FLD CFG  
LSTYP 0  
LSTYP 1  
function of service function  
Key is used as the colon when entering time. See  
Example 8.  
Loadshed is not enabled  
Loadshed is now enabled  
for 2-stage switch control  
subfunction accesses the leaving chiller fluid alert  
Demand Limit set points  
subfunction of set point  
function  
limit (LMT) option. The value to be entered here is the num-  
ber of degrees above the control set point at which an alert  
should be generated. For example, if the control set point is  
44 F, and an alert is desired (alert 70) if the fluid temperature  
reaches 50 F, then enter 6 for this set point. The allowable  
range for this entry is between 2 and 30 (F).  
DEMAND  
Loadshed 1 currently set  
at 80%  
DLS1 80  
DLS1 60  
DLS2 50  
DLS2 40  
Loadshed reset to 60%  
Loadshed 2 currently set  
at 50%  
SERVICE FUNCTION — This function allows the techni-  
cian to view and input configuration data. Factory configu-  
ration data, field configuration data, and service configura-  
tion data may be viewed or entered through the keypad and  
display module. See Table 9 for a complete listing of con-  
figurable items. Whenever a processor module is replaced in  
the field, the complete list of configuration codes must be  
entered.  
Loadshed 2 reset to 40%  
To Disable Demand Limit:  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
COMMENTS  
Logging On/Logging Off — The service function is pass-  
word protected. Therefore, to gain entry to this function,  
Field configuration sub-  
FLD CFG  
ERTYP 0  
LSTYP 1  
LSTYP 0  
function of service function  
Scroll past other elements  
in the subfunction  
this password must be entered. Pressing  
allows the technician to view, change, or enter configuration  
codes. To log off, perform the following keystrokes:  
Loadshed is enabled for  
2-stage switch control  
Loadshed is now disabled  
. The service function is once again password  
protected.  
NOTES:  
1. Select 2 for internally powered 4 to 20 mA signal load limiting.  
2. Select 3 for Carrier Comfort Network loadshed.  
3. Select 4 for externally powered 4 to 20 mA signal load limiting.  
Software Information —  
displays the version  
number of the software that resides in the processor  
module. The  
rized in Table 12.  
and  
subfunctions are summa-  
Example 7B — Using Demand Limit (4-20 mA)  
(First Log On As Shown in Table 12)  
KEYPAD  
ENTRY  
DISPLAY  
Example 8 — Setting Time of Day and  
Day of Week  
COMMENTS  
RESPONSE  
Field configuration subfunction  
of service function  
FLD CFG  
ERTYP 0  
LSTYP 0  
KEYPAD  
ENTRY  
DISPLAY  
RESPONSE  
COMMENTS  
Scroll past other elements in  
the subfunction  
Time display sub-  
function of set point  
function  
TIME  
Loadshed is not enabled  
Loadshed is now enabled  
for 4-20 mA internally-powered  
signal control  
Current setting is  
Monday, 4:00 p.m.  
MON 16.00  
LSTYP 2  
New setting of  
Tuesday, 1:05 p.m.  
is entered  
DEMAND  
DL20 100  
DL20 90  
Demand Limit set points  
TUE 13.05  
JAN 01 90  
APR 15 90  
and displayed  
Maximum demand limit is 100%  
Maximum demand limit is 90%  
Current date is  
Jan. 1, 1990  
New setting  
April 15, 1990  
is entered  
Scrolling past the 4 to 20 mA demand limit set point brings  
up the loadshed set points. The loadshed feature is activated  
by a redline alert and loadshed commands from the CCN  
loadshed option. The first set point is the group number, es-  
tablished by the CCN system designer. The second option is  
and displayed  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 9 — 4-20 mA Demand Limiting  
Factory Configuration Codes —  
allows entry into  
replaced in the field, the 2 groups of configuration codes must  
be entered through the keypad and display module. The  
2 groups of configuration codes (groups 8 and 9) that apply  
to the unit being serviced can be found on a label diagram  
inside the control box cover. See Table 13 for keystroke in-  
formation to enter configuration codes 8 and 9. The remain-  
ing items in this subfunction are read-only data provided to  
assist in service evaluations.  
the factory configuration subfunction. Under this subfunc-  
tion, there are 7 groups of configuration codes that are down-  
loaded at the factory. Each group is made up of 8 digits. If  
processor module is replaced in the field, these 7 groups of  
configuration codes must be entered through the keypad  
and display module. Factory configuration codes (groups 1  
through 7) that apply to the particular Flotronic™ II chiller  
being serviced are found on a label diagram located inside  
the control box cover. See Table 13 for a summary of factory  
configuration subfunction keystrokes.  
SCHEDULE FUNCTION — This function provides a means  
to automatically switch chiller from an occupied mode to an  
unoccupied mode. When using schedule function, chilled fluid  
pump relay must be used to switch chilled fluid pump on  
and off. Connections for chilled fluid pump relay are: TB3-3  
and TB3-4. The chilled fluid pump relay starts chilled fluid  
pump but compressors do not run until remote chilled fluid  
pump interlock contacts are between TB6-1 and TB6-2 are  
closed and leaving chilled fluid temperature is above set point.  
If a remote chilled fluid pump interlock is not used, the first  
compressor starts (upon a call for cooling) approximately  
one minute after chilled fluid pump is turned on.  
The unit can be programmed for inactive, single set point,  
or dual set point operation.  
When unit is configured for inactive, chilled fluid pump  
relay remains energized continuously but is not used since  
chiller is usually controlled by remote chilled fluid pump in-  
terlock contacts.  
Adjustable Field Configurations — After logging on, press  
to enter subfunction. The subfunction allows opera-  
tion of the chiller to be customized to meet the particular  
needs of the application. The chiller comes from the factory  
preconfigured to meet the needs of most applications. Each  
item should be checked to determine which configuration  
alternative best meets the needs of a particular application.  
See Table 14 for factory loaded configuration codes and al-  
ternative configurations.  
If processor module is replaced, the replacement module  
is preloaded with factory default configuration codes. Each  
configuration code must be checked and, if necessary, re-  
configured to meet needs of the application. See Table 14 for  
pre-loaded service replacement configuration codes.  
When unit is configured for single set point operation, chilled  
fluid pump relay is energized whenever chiller is in occu-  
pied mode regardless of whether chiller is running. When  
chiller is in unoccupied mode, chilled fluid pump relay is  
not energized.  
Service Configuration Codes — Press  
to enter the  
service configuration subfunction. The first 2 items under this  
subfunction are 2 groups (8 digits each) of configuration codes  
that are downloaded at the factory. If processor module is  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 13 — Factory Configuration Keystrokes  
Table 14 — Adjustable Field Configurations  
To change a configuration enter the new configuration  
FACTORY  
CONFIGURATION  
CODE  
SERVICE  
REPLACEMENT  
CODE  
FIELD CONFIGURATION  
ITEM AND CODES  
and press  
while on the correct configuration.  
CCN element address  
(Entered by CCN Technician)  
001  
001  
SUB-  
FUNCTION  
KEYPAD  
ENTRY  
DISPLAY  
COMMENTS  
CCN Bus Number  
(Entered by CCN Technician)  
000  
000  
FACTORY  
CONFIGURATION  
CODES  
CCN Baud Rate  
9600  
9600  
3 FACTORY  
CFG  
(Entered by CCN Technician)  
FACT CFG  
Cooler Fluid Select  
1 = Water (38 to 70 F  
[3.3 to 21 C] Set Point)  
2 = Medium Brine (15 to 70 F  
[–9 to 21 C] Set Point)  
1 = Standard Models  
2 = Brine Models  
1
Configuration  
Code 1  
XXXXXXXX  
XXXXXXXX  
XXXXXXXX  
XXXXXXXX  
XXXXXXXX  
Configuration  
Code 2  
Display Unit Select  
0 = English  
1 = Metric SI  
0
0
0
0
Configuration  
Code 3  
Delay at Power Up  
No. Circuit A Unloaders  
0 = No Unloaders  
1 = One Unloader  
2 = Two Unloaders  
Configuration  
Code 4  
0 = 30GN190-210*  
1 = 30GN040-170*  
0
0
Configuration  
Code 5  
No. Circuit B Unloaders  
0 = No Unloaders  
1 = One Unloader  
2 = Two Unloaders  
0 = 30GN040-070,  
190-210*  
1 = 30GN080-170*  
Configuration  
Code 6  
XXXXXXXX  
XXXXXXXX  
Hot Gas Bypass Select  
0 = No Valve  
0
1
0
1
Configuration  
Code 7  
Loading Sequence Select  
1 = Equal Circuit Loading  
2 = Staged Circuit Loading  
SERVICE  
CONFIGURATION  
CODES  
5 SERVICE  
CFG  
SRV CFG  
Lead/Lag Sequence Select  
1 = Automatic  
2 = Manual, Circuit A Leads  
3 = Manual, Circuit B Leads  
1
1
Configuration  
Code 8  
XXXXXXXX  
XXXXXXXX  
REFRIG X  
TDTYPE X  
OPS X  
Oil Pressure Switch Select  
0 = Not Used  
1 = Air Cooled  
Configuration  
Code 9  
0
1
0
0
Head Pressure Control Type  
0 = Not Used  
1 = Air Cooled  
Refrigerant Type  
Head Pressure Control Method  
1 = EXV Controlled  
2 = Set Point Control for  
Both Circuits  
3 = Set Point Control for  
Circuit A; EXV Control  
for Circuit B  
4 = Set Point Control for  
Circuit B; EXV Control  
for Circuit A  
Pressure Transducer Select  
Oil Pressure Set Point  
Low Pressure Set Point  
Fan Staging Select  
EXV Superheat Set Point  
EXV MOP Superheat  
Z Multiplier  
1
2 = 040,045  
Brine Units  
1
LPS X  
FANTYP X  
SH X  
MotormasterSelect  
0 = None  
2 = Indirect Control  
0
0
0
0
0
0
Cooling Set Point  
Control Select  
0 = Single Set Point Control  
1 = External Switch  
Controlled Set Point  
2 = Clock Controlled  
Set Point  
MOP X  
ZM X  
Cooling Reset Control Select  
0 = No Reset  
LEGEND  
MOP  
EXV  
Maximum Operating Pressure  
Electronic Expansion Valve  
1 = 4-20 mA, Internally Powered  
2 = External Temperature  
Reset  
3 = Return Fluid Reset  
4 = 4-20 mA, Externally Powered  
External Reset Sensor Select  
0 = Thermistor Connected to  
Options Module  
When unit is configured for dual set point, chilled liquid  
pump relay is energized continuously, in both occupied and  
unoccupied modes. Occupied mode places occupied chilled  
water set point into effect; unoccupied mode places unoc-  
cupied chilled water set point into effect.  
0
0
0
0
1 = Obtained Through CCN  
Outdoor-Air Sensor Select  
0 = Not Selected  
1 = Selected  
Demand Limit Control Select  
0 = No Demand Limiting  
1 = Two External Switch Inputs  
2 = Internal 4-20 mA Input  
3 = CCN Loadshed  
Scheduling —  
is used to override any current sched-  
0
1
0
0
ule in effect (for 0-4 hours).  
is used to activate a  
4 = External 4-20 mA Input  
Ramp Load Select  
(Pulldown Control)  
0 = Disabled  
clock for the scheduling function.  
-
are used  
to program schedules for specific occupied and unoccupied  
periods.  
1 = Enabled  
Cooler Pump Interlock Select  
0 = No Interlock  
1 = With Interlock  
1
1
0
0
0
0
The schedule consists of from one to 8 occupied time pe-  
riods, set by the operator. These time periods can be flagged  
to be in effect or not in effect on each day of the week. The  
day begins at 00.00 and ends at 24.00. The machine is in  
unoccupied mode unless a scheduled time period is in effect.  
If an occupied period is to extend past midnight, it must be  
programmed in the following manner: occupied period must  
end at 24:00 hours (midnight); a new occupied period must  
be programmed to begin at 00:00 hours.  
Cooler Pump Control Select  
0 = Not Controlled  
1 = ON/OFF Controlled  
Remote Alarm Option Select  
0 = Not Selected  
1 = Selected  
Local/Enable-Stop-CCN  
Switch Usage†  
0 = Not Allowed  
1 = Allowed  
1
1
LEGEND  
CCN  
EXV  
Carrier Comfort Network  
Electronic Expansion Valve  
*And associated modular units.  
†For reset of alarms.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: This is true only if the occupied period starts at 00:00  
(midnight). If the occupied period starts at a time other than  
midnight, then the occupied period must end at 00:00 hours  
(midnight) and new occupied period must be programmed  
to start at 00:00 in order for the chiller to stay in the occu-  
pied mode past midnight.  
The time schedule can be overridden to keep unit in oc-  
cupied mode for one, 2, 3, or 4 hours on a one-time basis.  
See Example 9.  
Example 9 — Using the Schedule Function (cont)  
KEYPAD  
ENTRY  
DISPLAY  
COMMENT  
PROGRAMMING PERIOD 2:  
PERIOD 2 Define schedule period 2  
OCC 00.00 Start of occupied time  
Occupied time will start  
OCC 7.00  
at 7:00 a.m.  
All subfunctions of schedule function are password  
Start of unoccupied time  
(end of period). For this  
UNO 00.00  
protected except the override subfunction,  
word entry into subfunctions through  
. Pass-  
,
example, period 2 should  
end at 18:00 (6:00 p.m.)  
Period 2 ends at 18:00  
UNO 18.00  
(6:00 p.m.)  
is done through service function. See page 43, logging on/  
logging off.  
Monday is now flagged no  
for period 2. To put period 2  
MON NO  
Figure 10 shows a schedule for an office building with the  
chiller operating on a single set point schedule. The sched-  
ule is based on building occupancy with a 3-hour off-peak  
cool-down period from midnight to 3 a.m. following the week-  
end shutdown. To learn how this sample schedule would be  
programmed, see Example 9.  
NOTE: This schedule was designed to illustrate the pro-  
gramming of the schedule function and is not intended as a  
recommended schedule for chiller operation.  
into effect on Monday,  
Monday must be flagged yes  
Monday is now flagged for  
MON YES  
period 2 to be in effect  
Tuesay is now flagged no  
for period 2. To put period 2  
into effect on Tuesday,  
Tuesday must be flagged  
yes  
TUE NO  
Tuesday is now flagged for  
period 2 to be in effect  
TUE YES  
For this example, period 2  
is to be in effect only on  
Monday and Tuesday.  
All other days must be  
checked to be sure that  
they are flagged no. If  
a day is flagged yes,  
change to no  
Example 9 — Using the Schedule Function  
WED YES  
WED NO  
KEYPAD  
ENTRY  
DISPLAY  
COMMENT  
No scheduled override  
in effect  
OVRD 0  
OVRD 3  
OVRD 0  
CLOCK 0  
CLOCK 1  
Wednesday is now flagged  
no for period 2  
3 hours override in effect  
Override cancelled  
Define schedule  
period 3  
PERIOD 3  
OCC 00.00  
OCC 7.00  
Start of occupied  
time  
Schedule function is inactive  
Occupied time will start  
at 7:00 a.m.  
Schedule function is enabled  
through local unit clock  
Start of unoccupied time  
(end of period 3). For this  
example, period 3 should  
end at 21:30 (9:30 p.m.)  
PROGRAMMING PERIOD 1:  
PERIOD 1  
UNO 00.00  
Define schedule period 1.  
Start of occupied time  
Period 3 ends at 21:30  
(9:30 p.m.)  
UNO 21.30  
MON NO  
For this example, first  
period should start here  
(at midnight) so no entry  
is needed  
OCC 00.00  
Check to be sure that  
Monday and Tuesday are  
flagged no for period 3  
Start of unoccupied time  
(end of period). For this  
example, period 1 should  
end at 3:00 a.m.  
TUE NO  
WED NO  
WED YES  
THUR NO  
FRI NO  
UNO 00.00  
UNO 3.00  
Wednesday is flagged  
no, change to yes  
Period 1 ends at 3:00 a.m.  
Wednesday is now  
flagged yes for period 3  
Monday is now flagged no  
for period 1. To put period 1  
into effect on Monday,  
Monday must be flagged  
yes  
Check to be sure that all  
other days are flagged no  
MON NO  
Monday is now flagged for  
period 1 to be in effect  
MON YES  
SAT NO  
SUN NO  
For this example, period 1  
is to be in effect on Monday  
only. All other days must be  
checked to be sure that they  
are flagged no. If any day is  
flagged yes, change to no  
TUE YES  
TUE NO  
CCN  
Carrier Comfort Network  
Tuesday is now flagged  
no for period 1  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Periods 4 and 5 can be programmed in the same manner,  
flagging Thursday and Friday yes for period 4 and Saturday  
yes for period 5. For this example, periods 6, 7, and 8  
are not used: they should be programmed OCC 00.00,  
UNO 00.00.  
NOTE: When a day is flagged yes for 2 overlapping periods,  
occupied time will take precedence over unoccupied time.  
Occupied times can overlap in the schedule with no  
consequence.  
To extend an occupied mode beyond its normal termina-  
tion for a one-time schedule override, program as shown  
below:  
Override is set for 0. Enter  
OVRD 0  
OVRD 3  
the number of hours of  
override desired  
Unit will now remain in  
occupied mode for  
an additional 3 hours  
Holiday Schedule — Press  
to schedule up to  
30 holiday periods. All holidays are entered with numerical  
values. First, the month (01 to 12), then the day (01 to 31),  
then the duration of the holiday period in days.  
Examples: July 04 is 07.04.01.  
Dec 25 - 26 is 12.25.02  
If any of the 30 holiday periods are not used, the display  
shows NEW.  
See Example 10.  
Fig. 10 — Sample Time Schedule  
TROUBLESHOOTING  
The Flotronic™ II control has many features to aid the  
technicians in troubleshooting a Flotronic II Chiller. By us-  
ing the keypad and display module and the status function,  
actual operating conditions of the chiller are displayed while  
unit is running. Test function allows proper operation of com-  
pressors, compressor unloaders, fans, EXVs and other com-  
ponents to be checked while chiller is stopped. Service func-  
tion displays how configurable items are configured. If an  
operating fault is detected, an alarm is generated and an  
Example 10 — Holiday Schedule Function  
ENTER  
DISPLAY  
HOLIDAY  
JAN01 02 (Includes Jan 1st  
and 2nd)  
APR17 01 (Includes April 17th)  
MAY21 01(Includes May 21st)  
JUL03 01 (Includes July 3rd)  
JUL04 01 (Includes July 4th)  
SEP07 01 (Includes Sep. 7th)  
alarm code(s) is displayed under the subfunction  
,
along with an explanation of the fault. Up to 10 current alarm  
codes are stored under this subfunction. For checking spe-  
cific items, see Table 9.  
Checking Display Codes — To determine how ma-  
chine has been programmed to operate, check diagnostic  
NOV26 02 (Includes Nov. 26th  
and 27th)  
information (  
) and operating mode displays (  
).  
If no display appears, follow procedures in Control Modules  
section on page 63. If display is working, continue as  
follows:  
DEC24 02 (Includes Dec. 24th  
and 25th)  
DEC30 02 (Includes Dec. 30th  
and 31st)  
1. Note all alarm codes displayed,  
2. Note all operating mode codes displayed,  
3. Note leaving chilled water temperature set point in ef-  
fect and current leaving water temperature,  
.
.
NEW  
MAY25 01 (Includes May 25th)  
.
NEW  
If machine is running, compare the ‘‘in effect’’ leaving  
water temperature set point with current water tempera-  
ture. Remember, if reset is in effect, the values may be  
different because machine is operating to the modified chilled  
water set point. If current temperature is equal to set point,  
but set point is not the one desired, remember that if dual  
set point has been selected in the schedule function, there  
are 2 set points to which the machine can be operating.  
Check the programming of schedule function to see if oc-  
cupied or unoccupied set point should be in effect.  
NEW  
NEW  
NEW  
NEW (30TH HOLIDAY)  
NEW indicates a holiday that has not been assigned yet.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Shutoff — To shut unit off, move LOCAL/ENABLE-  
STOP-CCN switch to STOP position. Any refrigeration cir-  
cuit operating at this time continues to complete the pum-  
pout cycle. Lag compressors stop immediately, and lead  
compressors run to complete pumpout.  
If stoppage occurs more than once as a result of any of  
the above safety devices, determine and correct the cause  
before attempting another restart.  
Complete Unit Stoppage — Complete unit stoppage  
Restart Procedure — After cause for stoppage has been  
corrected, restart is either automatic or manual, depending  
on fault. Manual reset requires that LOCAL/ENABLE-  
STOP-CCN switch be moved to STOP position, then back  
to original operating position. Some typical fault conditions  
are described in Table 15. For a complete list of fault con-  
ditions, codes, and reset type, see Table 16.  
can be caused by any of the following conditions:  
1. Cooling load satisfied  
2. Remote on/off contacts open  
3. Programmed schedule  
4. Emergency stop command from CCN  
5. General power failure  
6. Blown fuse in control power feed disconnect  
7. Open control circuit fuse  
8. LOCAL/ENABLE-STOP-CCN switch moved to STOP  
position  
Table 15 — Typical Stoppage Faults and Reset Types  
Chilled Fluid, Low Flow  
Manual reset  
Chilled Fluid, Low Temperature  
Auto reset first time, manual  
if repeated in same day  
9. Freeze protection trip  
10. Low flow protection trip  
11. Open contacts in chilled water flow switch (optional)  
Chilled Fluid Pump Interlock  
Control Circuit Fuse Blown  
High-Pressure Switch Open  
Low Refrigerant Pressure  
Low Oil Pressure  
Manual reset  
Unit restarts automatically when  
power is restored  
Manual reset  
12. Open contacts in any auxiliary interlock. Terminals that  
are jumpered from factory are in series with control switch.  
Opening the circuit between these terminals places unit  
in stop mode, similar to moving the control switch to  
STOP position. Unit cannot start if these contacts are  
open. If they open while unit is running, unit pumps down  
and stops.  
13. Cooler entering or leaving fluid thermistor failure  
14. Low transducer supply voltage  
15. Loss of communications between processor module and  
other control modules  
Auto reset first time, then  
manual if within same day  
Manual reset  
Discharge Gas Thermostat Open Manual reset  
POWER FAILURE EXTERNAL TO THE UNIT — Unit  
restarts automatically when power is restored.  
Alarms and Alerts — These are warnings of abnormal  
or fault conditions, and may cause either one circuit or the  
whole unit to shut down. They are assigned code numbers as  
described below. These code numbers are displayed  
16. Low refrigerant pressure  
17. Off-to-on delay is in effect.  
on the HSIO when the  
subfunction is entered. A  
fault that affects one one circuit of the chiller will generate  
an alert, and a fault that affects the entire unit will generate  
an alarm.  
Following is a detailed description of each alarm and alert  
code error and possible cause. Manual reset is accomplished  
by moving LOCAL/ENABLE-STOP-CCN Switch to STOP  
position, then back to LOCAL or CCN position. See  
Table 16 for listing of each alarm and alert code.  
Single Circuit Stoppage — Single circuit stoppage  
can be caused by the following:  
1. Low oil pressure in lead compressor  
2. Open contacts in lead compressor high-pressure switch  
3. Low refrigerant pressure  
4. Thermistor failure  
5. Transducer failure  
Code 0  
No alarms or alerts exist  
Codes 1 - 8 Compressor failure  
6. Ground fault in lead compressor indicator (indicator is  
field-supplied on 040-060, 070 [60 Hz], and 080-110 and  
associated modular units)  
7. High suction superheat  
8. Low suction superheat  
9. Lead compressor circuit breaker trip. Stoppage of one  
circuit by a safety device action does not affect other  
circuit. When a safety device trips on a lead compres-  
sor, circuit is shut down immediately and EXV closes.  
If DSIO-LV or -EXV relay module control relay feedback  
switch or signal is sensed as open during operation of a com-  
pressor, microprocessor detects this and stops compressor,  
energizes alert light, and displays a code of 1, 2, 3, 4, 5, 6,  
7, or 8 depending on the compressor. Compressor locks off;  
to reset, use manual reset method.  
If lead compressor in a circuit shuts down, the other com-  
pressors in the circuit stop and lock off. Only the alert mode  
for lead compressor is displayed.  
The microprocessor is also programmed to indicate com-  
pressor failure if feedback terminal on DSIO-LV or -EXV J3  
terminal strip receives voltage when compressor is not sup-  
posed to be on.  
10. Ground fault for any circuit compressor (130-210 and  
associated modular units).  
Lag Compressor Stoppage — Lag compressor stop-  
page can be caused by the following:  
1. Open contacts in high-pressure switch  
2. Compressor ground fault (indicator is field-supplied on  
040-060, 070 [60 Hz], and 080-110 and associated modu-  
lar units)  
NOTE: It takes 5 seconds for the control to generate the alarm  
code and lock out the compressor(s) on compressor failure  
code(s) 1 through 8.  
3. Compressor circuit breaker trip  
4. Not required to run to meet cooling load requirement  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 16 — Alarm and Alert Codes  
ALARM  
OR  
ACTION TAKEN  
BY CONTROL  
CIRCUIT  
RESET  
DISPLAY  
DESCRIPTION  
No Alarms or Alerts Exist  
PUMPDOWN METHOD  
PROBABLE CAUSE  
ALERT  
0
1
Compressor A1 failure  
Circuit A shut down  
No  
Manual High-pressure switch trip, or wiring  
error.  
2, 3, 4  
5
Compressor A2, A3, A4 failure  
Compressor B1 failure  
Compressor shut down  
Circuit B shut down  
Compressor shut down  
Unit shut down  
Yes  
No  
Manual CPCS Ground Fault Protection  
Alert  
Manual  
Manual  
Auto.  
6, 7, 8  
9
Compressor B2, B3, B4 failure  
Leaving fluid thermistor failure  
Entering fluid thermistor failure  
Compressor A1 sensor failure  
Compressor B1 sensor failure  
Reset thermistor failure  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
Alarm  
Alert  
10  
Unit shut down  
Auto.  
Thermistor or transducer failure  
or wiring error.  
19  
Circuit A shut down  
Circuit B shut down  
Normal set point used  
Auto.  
20  
Auto.  
Auto.  
Auto.  
Auto.  
21  
22  
Discharge pressure transducer failure, circuit A Circuit A shut down  
Discharge pressure transducer failure, circuit B Circuit B shut down  
Yes  
Yes  
No  
23  
24  
Suction pressure transducer failure, circuit A  
Suction pressure transducer failure, circuit B  
Oil pressure transducer failure, circuit A  
Oil pressure transducer failure, circuit B  
Transducer supply voltage low  
Circuit A shut down  
Circuit B shut down  
Circuit A shut down  
Circuit B shut down  
Unit shut down  
Auto.  
Alert  
Transducer failure or wiring error.  
Auto.  
25  
No  
26  
No  
Auto.  
Auto.  
27  
No  
28  
No  
Auto.  
Unit voltage low or PS1 faulty.  
Alarm  
Alert  
29  
LOCAL/ENABLE-STOP-CCN  
Unit shut down  
No  
Manual Switch failure or wiring error.  
30  
4-20 mA reset input failure  
Normal set point used  
Demand limit ignored  
Unit shut down  
No  
Auto.  
Auto.  
31  
4-20 mA demand limit failure  
No  
32  
Loss of communication with DSIO-LV  
No  
Auto.  
Wiring error or faulty module  
or improper address code.  
Alarm  
33  
34  
35  
36  
Loss of communication with DSIO-EXV  
Unit shut down  
No  
Yes  
Auto.  
Auto.  
Loss of communication with 4 In/4 Out module Unit shut down  
Not used  
Low refrigerant pressure circuit A  
Circuit A shut down  
No  
*
Low refrigerant charge, plugged filter  
drier, faulty expansion valve.  
Alert  
37  
38  
39  
40  
Low refrigerant pressure circuit B  
Failure to pump out circuit A  
Failure to pump out circuit B  
Low oil pressure circuit A  
Circuit B shut down  
Circuit A shut down  
Circuit B shut down  
Circuit A shut down  
No  
No  
No  
No  
*
Low refrigerant charge, plugged filter  
drier, faulty expansion valve.  
Manual Faulty expansion valve, transducer,  
or thermistor.  
Alert  
Alert  
Manual Faulty expansion valve, transducer,  
or thermistor.  
Manual Low oil level, circuit breaker trip,  
faulty expansion valve, crankcase  
heater, or pressure transducer.  
41  
Low oil pressure circuit B  
Circuit B shut down  
No  
Manual Low oil level, circuit breaker trip,  
faulty expansion valve, crankcase  
heater, or pressure transducer.  
42  
43  
Cooler freeze protection  
Low cooler fluid flow  
Unit shut down  
Unit shut down  
No  
No  
*
Low fluid flow or faulty thermistor.  
Alarm  
Alert  
Manual Chilled fluid pump failure  
or faulty thermistor.  
44  
45  
46  
47  
Low suction temperature circuit A  
Low suction temperature circuit B  
High suction superheat circuit A  
High suction superheat circuit B  
Circuit A shut down  
after 10 minutes  
No  
No  
Manual Faulty expansion valve or thermistor.  
Circuit B shut down  
after 10 minutes  
Manual Faulty expansion valve or thermistor.  
Circuit A shut down  
Yes  
Yes  
Manual Low charge, faulty expansion valve or  
thermistor, or plugged filter drier.  
Alert  
Alert  
Circuit B shut down  
Manual Low charge, faulty expansion valve or  
thermistor, or plugged filter drier.  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
Low suction superheat circuit A  
Low suction superheat circuit B  
Illegal configuration  
Circuit A shut down  
Circuit B shut down  
Unit cannot start  
Yes  
Yes  
Manual Faulty EXV or thermistor.  
Manual Faulty EXV or thermistor.  
Manual Configuration error.  
Alarm Initial configuration required  
Emergency stop by CCN command  
Cooler pump interlock failure  
Unit cannot start  
Manual Configuration omitted.  
Unit shut down  
Yes  
No  
No  
CCN  
Network command.  
Unit shut down  
Manual Failure of cooler pump or controls  
Manual Failure of cooler pump or controls  
Manual Failure of cooler pump relay or interlock  
Alarm Cooler pump interlock failure  
Cooler pump interlock failure  
Unit shut down  
Cooler pump shut down  
WSM forces removed  
Circuit cannot start  
Alert  
WSM communication failure  
Auto.  
Auto.  
Wiring fault or module failure  
Transducer not calibrated  
Calibration required for discharge pressure  
transducer, circuit A  
58  
59  
60  
61  
62  
Calibration required for discharge pressure  
transducer, circuit B  
Circuit cannot start  
Circuit cannot start  
Circuit cannot start  
Circuit cannot start  
Circuit cannot start  
Auto.  
Auto.  
Auto.  
Auto.  
Auto.  
Calibration required for suction pressure  
transducer, circuit A  
Alert  
Calibration required for suction pressure  
transducer, circuit B  
Calibration required for oil pressure  
transducer, circuit A  
Calibration required for oil pressure  
transducer, circuit B  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 16 — Alarm and Alert Codes (cont)  
ALARM  
OR  
ACTION TAKEN  
BY CONTROL  
CIRCUIT  
PUMPDOWN  
RESET  
METHOD  
DISPLAY  
63  
DESCRIPTION  
PROBABLE CAUSE  
Check individual alarms  
ALERT  
Alarm  
Alert  
Complete unit shutdown  
Alarm only  
Auto.  
64  
65  
Loss of charge, circuit A  
Loss of charge, circuit B  
Circuit cannot start  
Circuit cannot start  
Auto.  
Auto.  
Refrigerant leak or transducer  
failure  
66  
67  
Alarm  
Alarm  
FSM communication loss  
FSM forces removed  
Unit cannot start  
Auto.  
Auto.  
Wiring faulty or module failure  
Incorrect date code entered  
Transducer calibration date code failure  
Not used  
68,69  
70  
Alert  
High leaving chilled fluid temperature  
Alarm only  
Auto.  
Building load greater than unit capacity,  
low water/brine flow, or compressor  
fault. Check for other alarms or alerts.  
LEGEND  
*Reset automatic first time, manual if repeated same day.  
CPCS  
Compressor Protection Control Module  
Flotronic™ System Manager  
Power Supply  
FSM  
PS  
WSM  
Water System Manager  
Possible causes of failure:  
Compressor Alarm/Alert Circuit — For compres-  
sor A1 circuit, processor closes contacts between J4 termi-  
nals 2 and 3 to start compressor. See Fig. 11A-11C. Safeties  
shown to left of J4 must be closed in order for power to  
reach compressor control relay, and the feedback input ter-  
minals on J3.  
Failure of power to terminal 1 on J3, when contacts be-  
tween 2 and 3 on J4 should be closed, causes a code 1 alert.  
Terminal 2 on J3 is the other leg of the compressor A1  
feedback channel. It is connected to the 24-v common.  
1. High-Pressure Switch Open — High-pressure switch for  
each compressor is wired in series with 24-v power that  
energizes compressor control relay. If high-pressure switch  
opens during operation, compressor stops. This is  
detected by microprocessor through the feedback  
terminals.  
2. DSIO-LV or DSIO-EXV Module Failure — If a DSIO-LV  
relay module relay fails open or closed, microprocessor  
detects this, locks compressor off, and indicates an  
error.  
3. Wiring Errors — If a wiring error exists causing CPCS,  
CR, or feedback switch to not function properly, micro-  
processor indicates an error.  
4. Processor (PSIO) Failure — If hardware that monitors  
feedback switch fails, or processor fails to energize relay  
module relay to on, an error may be indicated.  
NOTE: Similar connections for each compressor can be fol-  
lowed on the unit wiring diagrams located on the unit.  
Code 9  
Leaving fluid thermistor failure (alarm)  
Code 10 Entering fluid thermistor failure (alarm)  
If temperature measured by these thermistors is outside  
range of –40 to 240 F (–40 to 116 C), unit shuts down after  
going through a normal pumpout. Reset is automatic if tem-  
perature returns to the acceptable range, and unit start-up fol-  
lows normal sequence. The cause of the fault is usually a  
bad thermistor, wiring error, or loose connection.  
NOTE: The control does not detect circuit breaker fail-  
ures. If a circuit breaker trips on lead compressor in a  
circuit, a low oil pressure failure is indicated. On the other  
compressors, no failure is indicated.  
Code 19  
Code 20  
Compressor A1 suction sensor failure (alert)  
Compressor B1 suction sensor failure (alert)  
5. Ground Fault Module on 130-210 and associated modu-  
lar units (CGFA or CGFB) Open — Module contacts are  
in lead compressor circuits, but ground fault could be in  
any compressor in affected circuit.  
On units with thermistors, if temperature measured by these  
thermistors is outside the range of –40 to 240 F (–40 to  
116 C), affected circuit shuts down after going through a nor-  
mal pumpout. Other circuit continues to run. Reset is auto-  
matic if temperature returns to the acceptable range, and cir-  
cuit start-up follows normal sequence. The cause of this fault  
is usually a bad thermistor, wiring error, or loose  
connection.  
On units with transducers, if the saturated suction tem-  
perature is greater than the leaving fluid temperature plus  
10° F (5.5 C) for more than 5 minutes, the affected circuit  
shuts down (after going through normal pumpout). The reset  
is automatic if the saturated suction temperature returns to  
the acceptable range and start-up follows the normal se-  
quence. The cause of this fault is usually a bad transducer,  
a wiring error, or a loose connection.  
Ground fault of any 040-110 and associated modular unit  
compressor (field-supplied accessory on 040-060 and 070,  
60 Hz units; standard on 070, 50 Hz and 80-110 and as-  
sociated modular units) will cause a trip.  
6. Checkout Procedure — Shut off main power to unit. Turn  
on control power, then step through subfunc-  
tion  
to proper compressor number (i.e., failure  
code 5 is compressor B1). Next, energize the step. If step  
works correctly, then failure code is caused by:  
• HPS (high-pressure switch) open  
• Misplaced feedback wire from J4 and J5 terminals  
• Ground wire and 24-v feeds reversed on one or more  
points on J3  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND  
C
Contactor  
CB  
Circuit Breaker  
COM, COMM  
CPCS  
Communications Bus  
Compressor Protection  
Control Module  
CR  
Compressor Contactor Relay  
Discharge Gas Thermostat (Optional)  
Relay Module (Low Voltage)  
High-Pressure Switch  
Low Voltage  
DGT  
DSIO  
HPS  
LV  
NC  
Normally Closed  
Normally Open  
NO  
PL  
Plug  
PWR  
SNB  
TB  
Power  
Snubber  
Terminal Block  
TRAN  
U
Transformer  
Unloader  
Fig. 11A — 24-V Safety Circuit Wiring (040-070)  
Code 21 Reset thermistor failure (applies only to installa-  
Code 27 Compressor B1 oil pressure transducer failure (alert)  
tions having external temperature reset) (alert)  
If output voltage of any of these transducers is greater than  
5 v, affected circuit shuts down without going through pum-  
pout process (Alerts 24-27). Other circuit continues to run.  
Reset is automatic if output voltage returns to the acceptable  
range, and circuit start-up follows normal sequence. The cause  
of this fault is usually a bad transducer or a wiring error.  
If temperature measured by this thermistor is outside range  
of –40 to 240 F (–40 to 116 C), reset function is disabled and  
unit controls to normal set point. If temperature returns to  
the acceptable range, reset function is automatically en-  
abled. The cause of this fault is usually a bad thermistor,  
wiring error, or loose connection.  
Code 28  
Low transducer supply voltage (alarm)  
Code 22 Compressor A1 discharge pressure  
If transducer supply voltage is less than 4.5 v or greater  
than 5.5 v, unit shuts down without going through pumpout  
process. Reset is automatic if supply voltage returns to the  
acceptable range, and circuit start-up follows normal se-  
quence. The cause of this fault is usually a faulty trans-  
former or primary voltage is out of range.  
transducer failure (alert)  
Code 23 Compressor B1 discharge pressure  
transducer failure (alert)  
Code 24 Compressor A1 suction pressure transducer  
failure (alert)  
Code 25 Compressor B1 suction pressure transducer  
failure (alert)  
Code 26 CompressorA1 oil pressure transducer failure (alert)  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND  
C
Contactor  
CB  
Circuit Breaker  
COMM  
CPCS  
DGT  
DSIO  
HPS  
LV  
Communications Bus  
Compressor Protection Control Module  
Discharge Gas Thermostat (Optional)  
Relay Module (Low Voltage)  
High-Pressure Switch  
Low Voltage  
*And associated modular units.  
PL  
Plug  
PWR  
TB  
Power  
Terminal Block  
TRAN  
U
Transformer  
Unloader  
Fig. 11B — 24-V Safety Circuit Wiring (080-110 and Associated Modular Units)  
The voltage supplied to the processor is polarized. When  
checking for proper voltage supply, be sure to consider this  
polarity. If voltage appears to be within acceptable toler-  
ance, check to be sure the transformer supplying PS1 is not  
grounded. Grounding the supply transformer can result in  
serious damage to the control system.  
Loss of communication can be attributed to a grounded  
transformer with a secondary voltage of 21 vac supplying  
the PSIO, DSIO-LV, or 4 IN/4 OUT modules; the 12.5-vac  
transformer supplying the DSIO-EXV module; or the  
24-vac transformer supplying PS1 for the transformers.These  
transformers should not be grounded, or serious damage to  
controls can result. Check to be sure the transformers are  
not grounded.  
Code 29 LOCAL/ENABLE-STOP-CCN Switch Failure  
(switch resistances out of range) (alarm)  
NOTE: If a blank PSIO module is downloaded without be-  
ing connected to the modules DSIO, this alarm is  
energized.  
Code 34 Loss of communication with 4 In/4 Out module  
(alarm)  
This fault occurs due to the failure of the switch or due to  
a wiring error.  
Code 30 Reset input failure (4 to 20 mA) (alert)  
Code 31 Demand limit input failure (4 to 20 mA) (alert)  
These codes apply only if unit is configured for these func-  
tions. If 4 to 20 mA signal is less than 4 or more than  
20 mA, reset or demand limit function is disabled and unit  
functions normally. If mA signal returns to the acceptable  
range, function is automatically enabled.  
Code 32 Loss of communication with compressor  
relay module (DISO-LV) (alarm)  
Code 33 Loss of communication with EXV relay  
module (DSIO-EXV) (alarm)  
This applies only if one or more of the following options  
are used:  
• external temperature reset  
• 4 to 20 mA temperature reset  
• external switch controlled dual set point  
• switch controlled demand limit  
• 4 to 20 mA demand limit  
• hot gas bypass  
If communication is lost with 4 IN/4 OUT module, the  
unit shuts off automatically, after finishing pumpout. Reset  
of alarm is automatic when communication is restored. Start-up  
after alarm is remedied follows a normal sequence. Probable  
cause of condition is a faulty or improperly connected plug,  
wiring error, or faulty module.  
If communication is lost with either of these modules, unit  
shuts down without pumpout. This alarm resets automati-  
cally when communication is restored. The unit starts up nor-  
mally after alarm condition is reset. Probable cause of con-  
dition is a faulty or improperly connected plug, wiring error,  
or faulty module.  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND  
CB  
Circuit Breaker  
CGF  
COMM  
CR  
Ground Fault Module  
Communications Bus  
Compressor Contactor Relay  
Relay Module (Low Voltage)  
High-Pressure Switch  
Low Voltage  
DSIO  
HPS  
LV  
*And associated modular units.  
PL  
Plug  
SNB  
TB  
Snubber  
Terminal Block  
TRAN  
U
Transformer  
Unloader  
Fig. 11C — 24-V Safety Circuit Wiring (130-210 and Associated Modular Units)  
Loss of communication can be attributed to a grounded  
transformer with a secondary voltage of 21 vac supplying  
the PSIO, DSIO-LV, or 4 IN/4 OUT; the 12.5-vac trans-  
former supplying the DSIO-EXV module, or the 24-vac trans-  
former supplying PS1 for the transformers.These transformers  
should not be grounded, or serious damage to controls can  
result. Check to be sure the transformers are not grounded.  
Possible causes of fault are low refrigerant charge, faulty  
EXV, plugged filter drier, or faulty transducer.  
Code 38 Failure to pump out, Circuit A (alert)  
Code 39 Failure to pump out, Circuit B (alert)  
The pumpout process is terminated when saturated suc-  
tion temperature is 10° F (5.6° C) below temperature at be-  
ginning of pumpout, or 10° F (5.6° C) below leaving water  
temperature or reaches a saturated suction temperature of  
–15 F (–26 C). If appropriate saturated suction temperature  
is not met within 3 minutes (on 2 consecutive tries), circuit  
shuts down without pumpout. Reset is manual with LOCAL/  
ENABLE-STOP-CCN switch, and start-up follows normal  
sequence.  
Code 36 Low refrigerant pressure, Circuit A (alert)  
Code 37 Low refrigerant pressure, Circuit B (alert)  
If suction pressure transducer senses a pressure below set  
point for more than 5 minutes at start-up or more than  
2 minutes during normal operation, affected circuit shuts down  
without going through the pumpout process. Reset is auto-  
matic when pressure reaches 10 psig above set point if there  
have been no previous occurrences of this fault on the same  
day. If this is a repeat occurrence on same day, then reset is  
manual, with LOCAL/ENABLE-STOP-CCN switch. Fac-  
tory configured set point is 27 psig for standard chillers and  
12 psig for brine chillers.  
Possible causes for this alarm are a bad thermistor or trans-  
ducer or a faulty expansion valve.  
Code 40 Low oil pressure, Circuit A (alert)  
Code 41 Low oil pressure, Circuit B (alert)  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If oil pressure differential is less than set point for more  
than 2 minutes at start-up, or more than one minute during  
normal operation, affected circuit shuts down without going  
through pumpout process. Reset is manual with LOCAL/  
ENABLE-STOP-CCN switch, and start-up follows normal  
sequence. Factory configured differential oil pressure is  
6 psig.  
Possible causes of fault are faulty compressor, expansion  
valve, crankcase heater or transducer, refrigerant over-  
charge, insufficient oil charge, or tripped circuit breaker.  
Code 50 Illegal configuration (alarm)  
This fault indicates a configuration error. Unit is not al-  
lowed to start. Check all configuration data and set points  
and correct any errors.  
Code 51 Initial configuration required (alarm)  
This fault indicates factory configuration has not been done,  
and unit is not allowed to start. Refer to unit wiring  
label diagrams for factory configuration codes. There are  
9 groups of 8-digit numbers that must be entered. The first  
7 groups must be entered under  
subfunction. Groups  
Code 42 Cooler freeze protection (alarm)  
8 and 9 must be entered under  
subfunction.  
If cooler entering or leaving water temperature is below  
34° F (1.1° C) for water or more than 8° F (4.4° C) below  
set point for brine, unit shuts down without pumpout. Chilled  
water pump continues to run if controlled by chiller con-  
trols. Reset is automatic when leaving fluid temperature reaches  
6° F (3° C) above set point, providing there has been no prior  
occurrence of this fault the same day. If fault has occurred  
previously the same day, reset is manual with LOCAL/  
ENABLE-STOP-CCN switch.  
Enter each group, then press the  
key. Press the  
down arrow  
after each group to bring up the next  
empty screen. Unit should start after factory and field con-  
figurations are correctly entered.  
The usual cause of this fault is replacement of the pro-  
cessor module. Refer to instructions accompanying the re-  
placement module.  
Possible causes of fault are low fluid flow or faulty  
thermistor.  
Code 52 Emergency stop by CCN command (alarm).  
Unit shuts down immediately without pumpout when this  
command is received, and goes through normal start-up when  
command is cancelled.  
Code 43 Low fluid flow (alarm)  
If any compressors are operating and entering fluid tem-  
perature is 3° F (1.7° C) or more below leaving fluid tem-  
perature for more than one minute, unit shuts down without  
pumpout. Chilled fluid pump also shuts down. Reset is manual  
with LOCAL/ENABLE-STOP-CCN switch, and start-up fol-  
lows normal sequence.  
This is a suitable method for sensing low fluid flow be-  
cause entering fluid thermistor is in the cooler shell and re-  
sponds more quickly to compressor operation than the leav-  
ing fluid thermistor in the leaving water nozzle. Possible causes  
of fault are faulty chilled fluid pump, control or thermistor.  
Code 53 Cooler pump interlock failure — Contacts fail to  
close at start-up (alarm)  
If the unit is configured for cooler pump control and cooler  
pump interlock, and the interlock fails to close within one  
minute of starting the cooler pump, the unit is shut down  
without pumpout. The cooler pump is also shut down. Reset  
is manual with the LOCAL/ENABLE-STOP-CCN switch,  
and start-up follows the normal sequence.  
Possible causes are:  
Code 44 Low cooler suction temperature, Circuit A (alert)  
Code 45 Low cooler suction temperature, Circuit B (alert)  
1. Interlock switch fails to close within one minute after chilled  
water pump starts  
If saturated suction temperature is less than 32 F (0°C)  
and is 20° F (11° C) for water or 30° F (16° C) for brine or  
more below leaving fluid temperature, mode 14 is dis-  
played. Unit continues to run, but additional compressors are  
not allowed to start. If condition persists for more than  
10 minutes, fault code is displayed, and unit shuts down with-  
out pumpout. Reset is manual with LOCAL/ENABLE-STOP-  
CCN switch, and start-up follows normal sequence.  
Possible causes of fault are low refrigerant charge, plugged  
filter drier, or a faulty expansion valve or thermistor.  
Code 46 High suction superheat, Circuit A (alert)  
Code 47 High suction superheat, Circuit B (alert)  
If expansion valve is fully open, suction superheat is greater  
than 75 F (42 C), and saturated evaporator temperature is  
less than MOP (maximum operating pressure) for more than  
5 minutes, unit shuts down after normal pumpout process.  
Reset is manual with LOCAL/ENABLE-STOP-CCN switch,  
and start-up follows normal sequence.  
Possible causes of fault are low refrigerant charge, plugged  
filter drier, or a faulty expansion valve or thermistor.  
Code 48 Low suction superheat, Circuit A (alert)  
Code 49 Low suction superheat, Circuit B (alert)  
2. Interlock switch opens during unit operation  
3. Interlock voltage is detected, but unit is not configured  
for interlock  
4. Interlock voltage is outside its valid range  
If any of these conditions occur, all compressors are dis-  
abled and, if running, shutdown occurs without pumpout.  
Chilled fluid pump also shuts down. Reset is manual, with  
LOCAL/ENABLE-STOP-CCN switch. Most probable cause  
of this fault is shutdown or failure of chilled fluid pump to  
start. Other possibilities are improper configuration or wir-  
ing errors.  
Code 54 Cooler pump interlock failure — Contacts open  
during normal operation (alarm)  
If the unit is configured for cooler pump control and cooler  
pump interlock, and the interlock opens during normal op-  
eration, the unit is shut down without pumpout. The cooler  
pump is also shut down. Reset is manual with the LOCAL/  
ENABLE-STOP-CCN switch, and startup follows the nor-  
mal sequence.  
Possible causes are:  
1. Interlock switch fails to close within one minute after chilled  
water pump starts  
If EXV is at minimum position, suction superheat is less  
than 10° F (5.5° C) or saturated evaporator temperature is  
greater than MOP (maximum operating pressure) for more  
than 5 minutes, affected circuit shuts down after going through  
pumpout process. Reset is manual with LOCAL/ENABLE-  
STOP-CCN switch, and start-up follows normal sequence.  
2. Interlock switch opens during unit operation  
3. Interlock voltage is detected, but unit is not configured  
for interlock  
4. Interlock voltage is outside its valid range  
If any of these conditions occur, all compressors are dis-  
abled and, if running, shutdown occurs without pumpout.  
Chilled fluid pump also shuts down. Reset is manual, with  
Possible causes of fault are faulty expansion valve or  
thermistor.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LOCAL/ENABLE-STOP-CCN switch. Most probable cause  
of this fault is shutdown or failure of chilled fluid pump to  
start. Other possibilities are improper configuration or wir-  
ing errors.  
15 psig. This alarm does not function in units using different  
part number transducers for suction and discharge pressure,  
since the discharge transducer in that application does not  
function below 20 psig.  
Code 55 Cooler pump interlock failure — Contacts closed  
Code 66 Flotronic™ System Manager loss of communi-  
when pump is off (alarm)  
cations (alarm)  
If the unit is configured for cooler pump control and cooler  
pump interlock, and the interlock is closed when the cooler  
pump relay is off, the cooler pump shall be shut down and  
the unit prevented from starting. Reset is manual with the  
LOCAL/ENABLE-STOP-CCN switch.  
Possible causes are:  
1. Interlock switch fails to close within one minute after chilled  
water pump starts  
If the FSM has established communication with the con-  
trol, and the communication is subsequently lost for more  
than 20 seconds, the control will remove all forces on the  
chiller variables. Control of the unit will revert to stand-  
alone basis, and reset is automatic upon re-establishment of  
communication.  
Code 67 Transducer calibration failure due to incorrect date  
code (alarm)  
This applies to units having pressure transducers with the  
same part number for both suction and discharge pressures.  
If the transducer calibration is attempted and the factory de-  
fault date code (Jan. 1, 1980) is in the date variable, then the  
unit will not start. Reset is automatic when the proper date  
code is entered upon calibration.  
2. Interlock switch opens during unit operation  
3. Interlock voltage is detected, but unit is not configured  
for interlock  
4. Interlock voltage is outside its valid range  
If any of these conditions occur, all compressors are dis-  
abled and, if running, shutdown occurs without pumpout.  
Chilled fluid pump also shuts down. Reset is manual, with  
LOCAL/ENABLE-STOP-CCN switch. Most probable cause  
of this fault is shutdown or failure of chilled fluid pump to  
start. Other possibilities are improper configuration or wir-  
ing errors.  
Code 70 High leaving chilled fluid temperature (alert)  
If the leaving chilled fluid temperature is rising and is  
higher than the limit established in the  
subfunction  
and the unit is at full capacity then alert 70 will be activated.  
The unit will continue to function normally, and reset will  
be automatic upon leaving chilled fluid temperature drop-  
ping to 5° F below the limit or less than control  
set point.  
Code 56 Water System Manager (WSM) communication  
failure (alert)  
If the WSM has previously established communications  
with the control and the WSM is not disabled and has not  
communicated with the control within the last 5 minutes, the  
control will remove all WSM forces from the chillers vari-  
ables. The chiller will continue to operate on a stand-alone  
basis. Reset is automatic when the WSM re-establishes com-  
munication with the unit.  
Code 57 Calibration required for discharge pressure trans-  
ducer, circuit A (alert)  
Code 58 Calibration required for discharge pressure trans-  
ducer, circuit B (alert)  
If the discharge pressure transducer has not been success-  
fully calibrated, the circuit will not start. Reset is automatic  
upon successful calibration of the transducer.  
Code 59 Calibration required for suction pressure trans-  
ducer, circuit A (alert)  
Code 60 Calibration required for suction pressure trans-  
ducer, circuit B (alert  
Electronic Expansion Valve (EXV)  
NOTE: This applies to all units except 30GN040 and 045  
with optional brine. The 040 and 045 units with optional brine  
have TXVs.  
EXV OPERATION — These valves control the flow of liq-  
uid refrigerant into the cooler. They are operated by the pro-  
cessor to maintain a specified superheat at lead compressor  
entering gas thermistor (located between compressor motor  
and cylinders). There is one EXV per circuit. See  
Fig. 12.  
High-pressure liquid refrigerant enters valve through bot-  
tom. A series of calibrated slots are located in side of orifice  
assembly. As refrigerant passes through orifice, pressure drops  
and refrigerant changes to a 2-phase condition (liquid and  
If the suction pressure transducer has not been success-  
fully calibrated, the circuit will not start. Reset is automatic  
upon successful calibration of the transducer.  
Code 61 Calibration required for oil pressure transducer,  
circuit A (alert)  
Code 62 Calibration required for oil pressure transducer,  
circuit B (alert)  
If the oil pressure transducer has not been successfully  
calibrated, the circuit will not start. Reset is automatic upon  
successful calibration of the transducer.  
Code 63 Complete unit shutdown due to failure (alarm)  
This alarm alerts the user that the unit is totally shut down  
due to one or more fault conditions. Reset is automatic when  
all alarms causing complete unit shutdown are reset.  
Code 64 Loss of charge, circuit A (alert)  
Code 65 Loss of charge, circuit B (alert)  
If the unit uses suction and discharge transducers with the  
same part number, and the discharge pressure is below  
10 psig when the unit is shut down, the circuit will not start.  
Reset is automatic when the discharge pressure rises above  
Fig. 12 — Electronic Expansion Valve (EXV)  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
vapor). To control refrigerant flow for different operating con-  
ditions, sleeve moves up and down over orifice, thereby chang-  
ing orifice size. Sleeve is moved by a linear stepper motor.  
Stepper motor moves in increments and is controlled di-  
rectly by the processor module. As stepper motor rotates,  
motion is transferred into linear movement by lead screw.  
Through stepper motor and lead screws, 1500 discrete steps  
of motion are obtained. The large number of steps and long  
stroke result in very accurate control of refrigerant flow.  
The  
subfunction shows EXV valve position as  
a percent of full open. Position should change constantly while  
unit operates. If a valve stops moving for any reason (me-  
chanical or electrical) other than a processor or thermistor  
failure, the processor continues to attempt to open or close  
the valve to correct the superheat. Once the calculated valve  
position reaches 120 (fully closed) or 1500 (fully open), it  
remains there. If EXV position reading remains at 120 or  
1500, and the thermistors and pressure transducers are read-  
ing correctly, the EXV is not moving. Follow EXV checkout  
procedure below to determine cause.  
EXV  
Electronic Expansion Valve  
Fig. 13 — EXV Cable Connections to EXV Driver  
Module, DSIO (EXV)  
The EXV is also used to limit cooler suction temperature  
to 50 F (10 C). This makes it possible for chiller to start at  
higher cooler fluid temperatures without overloading com-  
pressor. This is commonly referred to as MOP (maximum  
operating pressure), and serves as a load limiting device to  
prevent compressor motor overloading. This MOP or load  
limiting feature enables the 30G Flotronic™ II chillers to  
operate with up to 95 F (35 C) entering fluid temperatures  
during start-up and subsequent pull-down.  
Control of valve is by microprocessor. A thermistor and  
a pressure transducer located in lead compressor are used  
to determine superheat. The thermistor measures tem-  
perature of the superheated gas entering the compressor  
cylinders. The pressure transducer measures refrigerant  
pressure in the suction manifold. The microprocessor con-  
verts pressure reading to a saturation temperature. The  
difference between temperature of superheated gas and  
saturation temperature is the superheat.  
Because the EXVs are controlled by the processor mod-  
ule, it is possible to track valve position. During initial  
start-up, EXV is fully closed. After start-up, valve posi-  
tion is tracked by processor by constantly observing amount  
of valve movement.  
The processor keeps track of EXV position by counting  
the number of open and closed steps it has sent to each  
valve. It has no direct physical feedback of valve posi-  
tion. Whenever unit is switched from STOP to RUN po-  
sition, both valves are initialized, allowing the processor  
to send enough closing pulses to the valve to move it from  
fully open to fully closed, then reset the position counter  
to zero.  
CHECKOUT PROCEDURE — Follow steps below to di-  
agnose and correct EXV problems.  
1. Check EXV driver outputs. Check EXV output signals at  
appropriate terminals on EXV driver module (see  
Fig. 13) as follows:  
Connect positive test lead to terminal 1 on EXV driver.  
Set meter for approximately 20 vdc. Enter outputs  
subfunction of test function by pressing  
advance to EXVA test by pressing  
, then  
10 times. Press  
. The driver should drive the circuit A  
EXV fully open. During next several seconds connect nega-  
tive test lead to pins 2, 3, 4, and 5 in succession. Voltage  
should rise and fall at each pin. If it remains constant at  
a voltage or at zero v, remove connector to valve and  
recheck.  
4. The EXV test can be used to drive EXV to any desired  
position. When EXV opens, the metering slots begin to  
provide enough refrigerant for operation at step 120. This  
is fully closed position when circuit is operating. The fully  
open position is 1500 steps.  
Press  
to close circuit A EXV. If a problem still  
exists, replace EXV driver module. If voltage reading is  
correct, expansion valve should be checked. Next, test  
EXVB. Connect positive test lead to pin 7 and the nega-  
tive test lead to pin 8, 9, 10, and 11 in succession during  
EXVB test.  
5. Check thermistors and pressure transducers that control  
EXV. Check thermistors and pressure transducers that con-  
trol processor output voltage pulses to EXVs. See Fig. 14  
for locations.  
Circuit A — Thermistor T7, Suction Pressure Transducer  
2. Check EXV wiring. Check wiring to electronic expan-  
sion valves from terminal strip on EXV driver. See  
Fig. 13.  
SPTA  
Circuit B — Thermistor T8, Suction Pressure Transducer  
SPTB  
a. Check color coding and wire connections. Make sure  
they are connected to correct terminals at driver and  
EXV plug connections.  
b. Check for continuity and tight connection at all pin  
terminals.  
a. Use temperature subfunction of the status function  
(
) to determine if thermistors are reading  
correctly.  
b. Check thermistor calibration at known temperature by  
measuring actual resistance and comparing value mea-  
sured with values listed in Tables 17 and 18.  
c. Check plug connections at driver and at EXVs to be  
sure EXV cables are not crossed.  
c. Make sure thermistor leads are connected to proper  
pin terminals at J7 terminal strip on processor module  
and that thermistor probes are located in proper posi-  
tion in refrigerant circuit. See Fig. 15 and 16.  
3. Check resistance of EXV motor windings. Remove plug  
at J4 terminal strip and check resistance between com-  
mon lead (red wire, terminal D) and remaining leads, A,  
B, C, and E (see Fig. 13). Resistance should be  
25 ohms Ϯ 2 ohms.  
d. Use the pressure subfunction of the Status function  
(
) to determine if pressure transducers are  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
reading correctly. Connect a calibrated gage to lead  
compressor suction or discharge pressure connection  
to check transducer reading.  
Other possible causes of improper refrigerant flow con-  
trol could be restrictions in liquid line. Check for plugged  
filter drier(s) or restricted metering slots in the EXV. For-  
mation of ice or frost on lower body of electronic ex-  
pansion valve is one symptom of restricted metering slots.  
However, frost or ice formation is normally expected when  
leaving fluid temperature from the cooler is below 40 F.  
Clean or replace valve if necessary.  
NOTE: Frosting of valve is normal during compressor  
test steps and at initial start-up. Frost should dissipate af-  
ter 5 to 10 minutes operation in a system that is operating  
properly. If valve is to be replaced, wrap valve with a wet  
cloth to prevent excessive heat from damaging internal  
components.  
e. Make sure transducer leads are properly connected in  
junction box and at processor board. Check trans-  
former 5 output. Check voltage transducer 5 vdc  
Ϯ .2 v.  
When above checks have been completed, check ac-  
tual operation of EXV by using procedures outlined in  
this step.  
6. Check operation of EXV.  
a. Close liquid line service valve of circuit to be checked,  
and run through the test step (  
) for lead com-  
pressor in that circuit to pump down low side of sys-  
tem. Repeat test step 3 times to ensure all refrigerant  
has been pumped from low side.  
NOTE: Be sure to allow compressors to run for the  
full pumpout period.  
Thermostatic Expansion Valve (TXV) — Refer to  
base unit Installation Instructions for TXV information  
(30GN040,045 with optional brine only).  
Thermistors — All thermistors are identical in their tem-  
perature vs. resistance performance. Resistance at various tem-  
peratures are listed in Tables 17 and 18.  
b. Turn off compressor circuit breaker(s). Close com-  
pressor discharge service valves and remove any re-  
maining refrigerant from low side of system.  
c. Remove screws holding top cover of EXV. Carefully  
remove top cover. If EXV plug was disconnected dur-  
ing this process, reconnect it after cover is removed.  
LOCATION — General location of thermistor sensors are  
shown in Fig. 14.  
Cooler Leaving Fluid Thermistor (T1) — T1 is located in  
leaving fluid nozzle. The probe is immersed directly in the  
1
fluid. All thermistor connections are made through a 4-in.  
coupling. See Fig. 16. Actual location is shown in Fig. 14  
and 15.  
When removing top cover, be careful to avoid dam-  
aging motor leads.  
Cooler Entering Fluid Thermistor (T2) — T2 is located in  
cooler shell in first baffle space near tube bundle. Thermistor  
d. Enter appropriate EXV test step for EXVA or  
EXVB in the outputs subfunction of the test function  
1
connection is made through a 4-in. coupling. See Fig. 16.  
Actual location is shown in Fig. 14 and 15.  
Compressor Suction Gas Temperature Thermistors (T7 and  
T8) — T7 and T8 are located in lead compressor in each  
circuit in suction passage between motor and cylinders, above  
oil pump. They are well-type thermistors. See Fig. 14  
and 15.  
(
). Press  
to initiate test. With  
cover lifted off EXV valve body, observe operation of  
valve motor and lead screw. The motor should turn  
counterclockwise, and the lead screw should move up  
out of motor hub until valve is fully open. Lead screw  
movement should be smooth and uniform from  
fully closed to fully open position. Press  
check open to closed operation.  
THERMISTOR REPLACEMENT (T1, T2, T7, T8)  
to  
If valve is properly connected to processor and receiv-  
ing correct signals, yet does not operate as described  
above, valve should be replaced.  
Thermistors are installed directly in fluid Relieve all pres-  
sure using standard practices or drain fluid before re-  
moving.  
Operation of EXV valve can also be checked without  
removing top cover. This method depends on opera-  
tor’s skill in determining whether or not valve is mov-  
ing. To use this method, initiate EXV test and open  
valve. Immediately grasp EXV valve body. As valve  
drives open, a soft, smooth pulse is felt for approxi-  
mately 26 seconds as valve travels from fully closed  
to fully open. When valve reaches end of its opening  
stroke, a hard pulse is felt momentarily. Drive valve  
closed and a soft, smooth pulse is felt for the 52 sec-  
onds necessary for valve to travel from fully open to  
fully closed. When valve reaches end of its stroke, a  
hard pulse is again felt as valve overdrives by 50 steps.  
Valve should be driven through at least 2 complete cycles  
to be sure it is operating properly. If a hard pulse is  
felt for the 26-second duration, valve is not moving  
and should be replaced.  
Proceed as follows (see Fig. 16):  
To replace thermistor sensor T2:  
1. Remove and discard original thermistor and coupling.  
IMPORTANT: Do not disassemble new coupling.  
Install as received.  
2. Apply pipe sealant to 14-in. NPT threads on replacement  
coupling and install in place of original. Do not use pack-  
ing nut to tighten coupling. This damages ferrules (see  
Fig. 16).  
3. Insert new thermistor in coupling body to its full depth.  
If thermistor bottoms out before full depth is reached, pull  
thermistor back out 18 in. before tightening packing nut.  
Hand tighten packing nut to position ferrules, then finish  
tightening 114 turns with a suitable tool. Ferrules are now  
attached to thermistor which can be withdrawn from cou-  
pling for unit servicing.  
The EXV test can be repeated as required by enter-  
ing any percentage from 0 (  
movement.  
) to 100 to initiate  
To replace thermistors T1, T7, and T8:  
If operating problems persist after reassembly, they may  
be due to out-of-calibration thermistor(s) or intermittent  
connections between processor board terminals and EXV  
plug. Recheck all wiring connections and voltage signals.  
Add a small amount of thermal conductive grease to ther-  
mistor well. Thermistors are friction-fit thermistors, which  
must be slipped into well located in the compressor pump  
end.  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 17 — Thermistor Temperature (°F) vs Resistance/Voltage Drop; Flotronic™ II  
TEMPERATURE  
(F)  
VOLTAGE  
DROP (V)  
RESISTANCE  
(OHMS)  
TEMPERATURE  
(F)  
VOLTAGE  
DROP (V)  
RESISTANCE  
(OHMS)  
TEMPERATURE  
(F)  
VOLTAGE  
DROP (V)  
RESISTANCE  
(OHMS)  
−25.0  
−24.0  
−23.0  
−22.0  
−21.0  
−20.0  
−19.0  
−18.0  
−17.0  
−16.0  
−15.0  
−14.0  
−13.0  
−12.0  
−11.0  
−10.0  
−9.0  
−8.0  
−7.0  
−6.0  
−5.0  
−4.0  
−3.0  
−2.0  
−1.0  
0.0  
4.821  
4.818  
4.814  
4.806  
4.800  
4.793  
4.786  
4.779  
4.772  
4.764  
4.757  
4.749  
4.740  
4.734  
4.724  
4.715  
4.705  
4.696  
4.688  
4.676  
4.666  
4.657  
4.648  
4.636  
4.624  
4.613  
4.602  
4.592  
4.579  
4.567  
4.554  
4.540  
4.527  
4.514  
4.501  
4.487  
4.472  
4.457  
4.442  
4.427  
4.413  
4.397  
4.381  
4.366  
4.348  
4.330  
4.313  
4.295  
4.278  
4.258  
4.241  
4.223  
4.202  
4.184  
4.165  
4.145  
4.125  
4.103  
4.082  
4.059  
4.037  
4.017  
3.994  
3.968  
3.948  
3.927  
3.902  
3.878  
3.854  
3.828  
3.805  
3.781  
3.757  
3.729  
3.705  
3.679  
3.653  
3.627  
3.600  
3.575  
3.547  
3.520  
3.493  
3.464  
3.437  
3.409  
3.382  
3.353  
3.323  
3.295  
3.267  
3.238  
3.210  
3.181  
3.152  
3.123  
98010  
94707  
91522  
88449  
85486  
82627  
79871  
77212  
74648  
72175  
69790  
67490  
65272  
63133  
61070  
59081  
57162  
55311  
53526  
51804  
50143  
48541  
46996  
45505  
44066  
42679  
41339  
40047  
38800  
37596  
36435  
35313  
34231  
33185  
32176  
31202  
30260  
29351  
28473  
27624  
26804  
26011  
25245  
24505  
23789  
23096  
22427  
21779  
21153  
20547  
19960  
19393  
18843  
18311  
17796  
17297  
16814  
16346  
15892  
15453  
15027  
14614  
14214  
13826  
13449  
13084  
12730  
12387  
12053  
11730  
11416  
11112  
10816  
10529  
10250  
9979  
71  
72  
3.093  
3.064  
3.034  
3.005  
2.977  
2.947  
2.917  
2.884  
2.857  
2.827  
2.797  
2.766  
2.738  
2.708  
2.679  
2.650  
2.622  
2.593  
2.563  
2.533  
2.505  
2.476  
2.447  
2.417  
2.388  
2.360  
2.332  
2.305  
2.277  
2.251  
2.217  
2.189  
2.162  
2.136  
2.107  
2.080  
2.053  
2.028  
2.001  
1.973  
1.946  
1.919  
1.897  
1.870  
1.846  
1.822  
1.792  
1.771  
1.748  
1.724  
1.702  
1.676  
1.653  
1.630  
1.607  
1.585  
1.562  
1.538  
1.517  
1.496  
1.474  
1.453  
1.431  
1.408  
1.389  
1.369  
1.348  
1.327  
1.308  
1.291  
1.289  
1.269  
1.250  
1.230  
1.211  
1.192  
1.173  
1.155  
1.136  
1.118  
1.100  
1.082  
1.064  
1.047  
1.029  
1.012  
0.995  
0.978  
0.962  
0.945  
0.929  
0.914  
0.898  
0.883  
0.868  
0.853  
5781  
5637  
5497  
5361  
5229  
5101  
4976  
4855  
4737  
4622  
4511  
4403  
4298  
4196  
4096  
4000  
3906  
3814  
3726  
3640  
3556  
3474  
3395  
3318  
3243  
3170  
3099  
3031  
2964  
2898  
2835  
2773  
2713  
2655  
2597  
2542  
2488  
2436  
2385  
2335  
2286  
2239  
2192  
2147  
2103  
2060  
2018  
1977  
1937  
1898  
1860  
1822  
1786  
1750  
1715  
1680  
1647  
1614  
1582  
1550  
1519  
1489  
1459  
1430  
1401  
1373  
1345  
1318  
1291  
1265  
1240  
1214  
1190  
1165  
1141  
1118  
1095  
1072  
1050  
1029  
1007  
986  
167  
168  
169  
170  
171  
172  
173  
174  
175  
176  
177  
178  
179  
180  
181  
182  
183  
184  
185  
186  
187  
188  
189  
190  
191  
192  
193  
194  
195  
196  
197  
198  
199  
200  
201  
202  
203  
204  
205  
206  
207  
208  
209  
210  
211  
212  
213  
214  
215  
216  
217  
218  
219  
220  
221  
222  
223  
224  
225  
0.838  
0.824  
0.810  
0.797  
0.783  
0.770  
0.758  
0.745  
0.734  
0.722  
0.710  
0.700  
0.689  
0.678  
0.668  
0.659  
0.649  
0.640  
0.632  
0.623  
0.615  
0.607  
0.600  
0.592  
0.585  
0.579  
0.572  
0.566  
0.560  
0.554  
0.548  
0.542  
0.537  
0.531  
0.526  
0.520  
0.515  
0.510  
0.505  
0.499  
0.494  
0.488  
0.483  
0.477  
0.471  
0.465  
0.459  
0.453  
0.446  
0.439  
0.432  
0.425  
0.417  
0.409  
0.401  
0.393  
0.384  
0.375  
0.366  
719  
705  
690  
677  
663  
650  
638  
626  
614  
602  
591  
581  
570  
561  
551  
542  
533  
524  
516  
508  
501  
494  
487  
480  
473  
467  
461  
456  
450  
445  
439  
434  
429  
424  
419  
415  
410  
405  
401  
396  
391  
386  
382  
377  
372  
367  
361  
356  
350  
344  
338  
332  
325  
318  
311  
304  
297  
289  
282  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
89  
90  
91  
92  
93  
94  
95  
96  
1.0  
97  
2.0  
98  
3.0  
99  
4.0  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
124  
125  
126  
127  
128  
129  
130  
131  
132  
133  
134  
135  
136  
137  
138  
139  
140  
141  
142  
143  
144  
145  
146  
147  
148  
149  
150  
151  
152  
153  
154  
155  
156  
157  
158  
159  
160  
161  
162  
163  
164  
165  
166  
5.0  
6.0  
7.0  
8.0  
9.0  
10.0  
11.0  
12.0  
13.0  
14.0  
15.0  
16.0  
17.0  
18.0  
19.0  
20.0  
21.0  
22.0  
23.0  
24.0  
25.0  
26.0  
27.0  
28.0  
29.0  
30.0  
31.0  
32.0  
33.0  
34.0  
35.0  
36.0  
37.0  
38.0  
39.0  
40.0  
41.0  
42.0  
43.0  
44.0  
45.0  
46.0  
47.0  
48.0  
49.0  
50.0  
51.0  
52.0  
53.0  
54.0  
55.0  
56.0  
57.0  
58.0  
59.0  
60.0  
61.0  
62.0  
63.0  
64.0  
65.0  
66.0  
67.0  
68.0  
69.0  
70.0  
9717  
9461  
9213  
8973  
8739  
8511  
8291  
965  
8076  
945  
7868  
925  
7665  
906  
7468  
887  
7277  
868  
7091  
850  
6911  
832  
6735  
815  
6564  
798  
6399  
782  
6238  
765  
6081  
750  
5929  
734  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 18 — Thermistor Temperature (°C) vs Resistance/Voltage Drop; Flotronic™ II  
TEMPERATURE  
(C)  
VOLTAGE  
DROP (V)  
RESISTANCE  
(Ohms)  
TEMPERATURE  
(C)  
VOLTAGE  
DROP (V)  
RESISTANCE  
(Ohms)  
−40  
−39  
−38  
−37  
−36  
−35  
−34  
−33  
−32  
−31  
−30  
−29  
−28  
−27  
−26  
−25  
−24  
−23  
−22  
−21  
−20  
−19  
−18  
−17  
−16  
−15  
−14  
−13  
−12  
−11  
−10  
−9  
4.896  
4.889  
4.882  
4.874  
4.866  
4.857  
4.848  
4.838  
4.828  
4.817  
4.806  
4.794  
4.782  
4.769  
4.755  
4.740  
4.725  
4.710  
4.693  
4.676  
4.657  
4.639  
4.619  
4.598  
4.577  
4.554  
4.531  
4.507  
4.482  
4.456  
4.428  
4.400  
4.371  
4.341  
4.310  
4.278  
4.245  
4.211  
4.176  
4.140  
4.103  
4.065  
4.026  
3.986  
3.945  
3.903  
3.860  
3.816  
3.771  
3.726  
3.680  
3.633  
3.585  
3.537  
3.487  
3.438  
3.387  
3.337  
3.285  
3.234  
3.181  
3.129  
3.076  
3.023  
2.970  
2.917  
2.864  
2.810  
2.757  
2.704  
2.651  
2.598  
2.545  
2.493  
2.441  
2.389  
2.337  
2.286  
2.236  
2.186  
2.137  
2.087  
2.039  
1.991  
168 230  
157 440  
147 410  
138 090  
129 410  
121 330  
113 810  
106 880  
100 260  
94 165  
88 480  
83 170  
78 125  
73 580  
69 250  
65 205  
61 420  
57 875  
54 555  
51 450  
48 536  
45 807  
43 247  
40 845  
38 592  
38 476  
34 489  
32 621  
30 866  
29 216  
27 633  
26 202  
24 827  
23 532  
22 313  
21 163  
20 079  
19 058  
18 094  
17 184  
16 325  
15 515  
14 749  
14 026  
13 342  
12 696  
12 085  
11 506  
10 959  
10 441  
9 949  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
89  
90  
91  
92  
93  
94  
95  
96  
97  
98  
99  
100  
101  
102  
103  
104  
105  
106  
107  
1.944  
1.898  
1.852  
1.807  
1.763  
1.719  
1.677  
1.635  
1.594  
1.553  
1.513  
1.474  
1.436  
1.399  
1.363  
1.327  
1.291  
1.258  
1.225  
1.192  
1.160  
1.129  
1.099  
1.069  
1.040  
1.012  
0.984  
0.949  
0.920  
0.892  
0.865  
0.838  
0.813  
0.789  
0.765  
0.743  
0.722  
0.702  
0.683  
0.665  
0.648  
0.632  
0.617  
0.603  
0.590  
0.577  
0.566  
0.555  
0.545  
0.535  
0.525  
0.515  
0.506  
0.496  
0.486  
0.476  
0.466  
0.454  
0.442  
0.429  
0.416  
0.401  
0.386  
0.370  
2 272  
2 184  
2 101  
2 021  
1 944  
1 871  
1 801  
1 734  
1 670  
1 609  
1 550  
1 493  
1 439  
1 387  
1 337  
1 290  
1 244  
1 200  
1 158  
1 118  
1 079  
1 041  
1 006  
971  
938  
906  
876  
836  
805  
775  
747  
719  
−8  
693  
−7  
669  
−6  
645  
−5  
623  
−4  
602  
−3  
583  
−2  
564  
−1  
547  
0
531  
1
516  
2
502  
3
489  
4
477  
5
466  
6
456  
7
446  
8
436  
9
427  
10  
419  
11  
9 485  
410  
12  
9 044  
402  
13  
8 627  
393  
14  
8 231  
385  
15  
7 855  
376  
16  
7 499  
367  
17  
7 161  
357  
18  
6 840  
346  
19  
6 536  
335  
20  
6 246  
324  
21  
5 971  
312  
22  
5 710  
299  
23  
5 461  
285  
24  
5 225  
25  
5 000  
26  
4 786  
27  
4 583  
28  
4 389  
29  
4 204  
30  
4 028  
31  
3 861  
32  
3 701  
33  
3 549  
34  
3 404  
35  
3 266  
36  
3 134  
37  
3 008  
38  
2 888  
39  
2 773  
40  
2 663  
41  
2 559  
42  
2 459  
43  
2 363  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND  
DPT  
EXV  
OPT  
SPT  
T
Discharge Pressure Transducer  
Electronic Expansion Valve  
Oil Pressure Transducer  
Suction Pressure Transducer  
Thermistor Number  
Fig. 14 — Thermistor and Pressure Transducer Locations  
Pressure Transducers — A single style of pressure  
transducer is used for both high- and low-pressure sensing  
on Flotronic™ II chillers. However, this transducer must be  
calibrated before the unit will operate. On new units, this  
will have been done at the factory in order to test run the  
unit. If a transducer or PSIO is replaced in the field, how-  
ever, the transducer will have to be field calibrated as  
follows:  
4. Press  
on the HSIO keypad. This automatically ap-  
plies the proper correction factor to all future inputs from  
the transducer.  
Three pressure transducers are mounted on each lead com-  
pressor: 2 low-pressure transducers to monitor compressor  
suction pressure and oil pressure, and a high-pressure trans-  
ducer to monitor compressor discharge pressure (see  
Fig. 17 for exact locations on compressor). Each transducer  
is supplied with 5 vdc power from a rectifier which changes  
24 vac to 5 vdc.  
1. Disconnect transducer from the system.  
2. Hang the transducer in the atmosphere.  
3. Press  
on the HSIO keypad, and Read the pres-  
TROUBLESHOOTING — If transducer is suspected of be-  
ing faulty, first check supply voltage to transducer. Supply  
voltage should be 5 vdc ± .2 v. If supply voltage is correct,  
compare pressure reading displayed on keypad and display  
module against pressure shown on a calibrated pressure gage.  
If the 2 pressure readings are not reasonably close, replace  
pressure transducer.  
sure. Pressures before calibration must be within the  
range of Ϯ 5 psig. If the pressure is outside the range of  
Ϯ 5 psig, the HSIO display will read ---. If this is the  
case, replace the transducer or PSIO or check for a wir-  
ing error. If the value of the atmospheric pressure is greater  
than 5 psig or less than –5 psig, the transducer will be  
considered out of range and will not calibrate.  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 15 — Thermistor Locations  
(Circuits A and B, Lead Compressor Only)  
COMPRESSOR SUCTION GAS TEMPERATURE  
FLUID-SIDE TEMPERATURE THERMISTOR T2  
(ALL UNITS)  
THERMISTORS T7 AND T8  
(ALL UNITS) AND FLUID-SIDE TEMPERATURE  
THERMISTOR T1 (ALL UNITS)  
Fig. 16 — Thermistors  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 17 — Lead Compressor Transducer and Thermistor Locations  
1
TRANSDUCER REPLACEMENT  
3. Unscrew transducer from 4-in. male flare fitting. When  
installing new pressure transducer, do not use thread  
sealer. Thread sealer can plug transducer and render it  
inoperative.  
Transducers are installed directly in the refrigerant cir-  
cuit. Relieve all refrigerant pressure using standard re-  
frigeration practices before removing.  
4. Insert weathertight wiring plug into end of transducer un-  
til locking tab snaps in place.  
5. Check for refrigerant leaks.  
1. Relieve refrigerant pressure using standard refrigeration  
practices.  
2. Disconnect transducer wiring at transducer by pulling up  
on locking tab while pulling weathertight connection plug  
from end of transducer. Do not pull on transducer wires.  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Modules  
Turn controller power off before servicing controls. This  
ensures safety and prevents damage to controller.  
PROCESSOR MODULE (PSIO), 4 IN/4 OUT MODULE  
(SIO), LOW-VOLTAGE RELAY MODULE (DSIO-LV),  
AND EXV DRIVER MODULE (DSIO-EXV) — The PSIO,  
DSIO and SIO modules all perform continuous diagnostic  
evaluations of the condition of the hardware. Proper opera-  
tion of these modules is indicated by LEDs (light-emitting  
diodes) on the front surface of the DSIOs, and on the top  
horizontal surface of the PSIO and SIO.  
RED LED — Blinking continuously at a 3- to 5-second rate  
indicates proper operation. Lighted continuously indicates a  
problem requiring replacement of module. Off continuously  
indicates power should be checked. If there is no input power,  
check fuses. If fuse is bad, check for shorted secondary of  
transformer or for bad module. On the PSIO module, if the  
light is blinking at a rate of twice per second, the module  
should be replaced.  
GREEN LED — On a PSIO and an SIO, this is the green  
LED closest to COMM connectors. The other green LED on  
module indicates external communications, when used. Green  
LED should always be blinking when power is on. It indi-  
cates modules are communicating properly. If green LED is  
not blinking, check red LED. If red LED is normal, check  
module address switches. See Fig. 18. Proper addresses are:  
PSIO (Processor Module) — 01 (different when CCN  
connected)  
DSIO (Relay Module) — 19  
DSIO (EXV Driver Module) — 31  
SIO  
(4 In/4 Out Module) — 59  
If all modules indicate communication failure, check COMM  
plug on PSIO module for proper seating. If a good connec-  
tion is assured and condition persists, replace PSIO module.  
If only DSIO or SIO module indicates communication fail-  
ure, check COMM plug on that mode for proper seating. If  
a good connection is assured and condition persists, replace  
DSIO or SIO module.  
All system operating intelligence rests in PSIO module,  
the module that controls unit. This module monitors condi-  
tions through input and output ports and through DSIO mod-  
ules (low-voltage relay module and EXV driver module).  
The machine operator communicates with microproces-  
sor through keypad and display module. Communication be-  
tween PSIO and other modules is accomplished by a 3-wire  
sensor bus. These 3 wires run in parallel from module to  
module.  
On sensor bus terminal strips, terminal 1 of PSIO module  
is connected to terminal 1 of each of the other modules.  
Terminals 2 and 3 are connected in the same manner. See  
Fig. 19. If a terminal 2 wire is connected to terminal 1, sys-  
tem does not work.  
In Flotronic™ II chillers, processor module, low-voltage  
relay module, and keypad and display module are all pow-  
ered from a common 21-vac power source which connects  
to terminals 1 and 2 of power input strip on each module. A  
separate source of 21-vac power is used to power options  
module through terminals 1 and 2 on power input strip. A  
separate source of 12.5 vac power is used to power EXV  
driver module through terminals 1 and 2 on power input strip.  
Fig. 18 — Module Address  
Selector Switch Locations  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 19 — Sensor Bus Wiring  
(Communications)  
PROCESSOR MODULE (PSIO) (Fig. 20)  
Inputs — Each input channel has 3 terminals; only 2 of the  
terminals are used. Application of machine determines which  
terminals are used. Always refer to individual unit wiring  
for terminal numbers.  
Outputs — Output is 24 vdc. There are 3 terminals, only 2  
of which are used, depending on application. Refer to unit  
wiring diagram.  
NOTE: Address switches (see Fig. 20) must be set at 01 (dif-  
ferent when CCN connected).  
LOW VOLTAGE RELAY MODULE (DSIO-LV) (Fig. 21)  
Inputs — Inputs on strip J3 are discrete inputs (ON/OFF).  
When 24-vac power is applied across the 2 terminals in a  
channel it reads as on signal. Zero v reads as an off signal.  
PWR  
Power  
Outputs — Terminal strips J4 and J5 are internal relays whose  
coils are powered-up and powered-off by a signal from  
microprocessor. The relays switch the circuit to which they  
are connected. No power is supplied to these connections by  
DSIO module.  
Fig. 20 — Processor Module (PSIO)  
4 IN/4 OUT MODULE (SIO) (Fig. 22) — 4 In/4 Out mod-  
ule allows the following features to be utilized:  
1. Temperature Reset by outdoor air or space temperature.  
A remote thermistor (Part No. 30GB660002) is also re-  
quired.  
NOTE: This accessory is not required for return water  
temperature reset.  
2. Temperature Reset by remote 4 to 20 mA signal.  
3. Demand Limit by remote 2-stage switch.  
4. Demand Limit by remote 4 to 20 mA signal  
5. Dual Set Point by remote switch.  
The options module is standard. Remember to reconfig-  
ure the chiller for each feature selected (see Table 14). For  
temperature reset, demand limit, and dual set point, desired  
set points must be entered through keypad and display mod-  
ule (see Set Point Function section on page 38).  
See Table 19 for overall troubleshooting information.  
ACCESSORY UNLOADER INSTALLATION  
Some of the 30G Flotronic™ II units come standard with  
unloader(s), and many permit additional unloader(s) to be  
added if desired. See Table 20.  
IMPORTANT: The following combinations ARE NOT  
permitted (combinations are per circuit):  
LEGEND  
1. Two unloaders and hot gas bypass  
2. Four compressors and 2 unloaders.  
3. Four compressors, 1 unloader, and hot gas  
bypass.  
COMM  
NC  
Communications Bus  
Normally Closed  
NO  
PWR  
Normally Open  
Power  
Fig. 21 — Low-Voltage Relay Module (DSIO)  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Install the additional unloader cylinder head on the lead  
compressor, A1 or B1, according to instructions provided  
by the compressor manufacturer in the accessory  
package.  
4. Continue installation per either 040-110, 130 (60 Hz) units  
or 130 (50 Hz), 150-210 units section as appropriate.  
040-110, 130 (60 Hz) UNITS (AndAssociated Modular Units)  
1. Wire the solenoid before any field wiring begins. Wiring  
between components and control box must be enclosed  
in conduit. All local electrical codes and National Elec-  
trical Code (NEC) must be followed. Factory wires are  
provided in the compressor harness to connect the sole-  
noid. These wires are in the compressor control box.  
2. Wire the control side. Open the left side control box door  
and remove inner panel. Using the holes provided and  
field-supplied screws, install field-supplied transformer above  
the DSIO-LV on the control panel.  
Wire the primary side of the transformer in parallel with  
TRAN4. See Fig. 23. This supplies transformer with proper  
line voltage. Be sure to connect proper tap of the trans-  
former to ensure supply of proper secondary voltage.  
Wire the secondary side of transformer to DSIO-LV - J5-9,  
and a jumper from DSIO-LV - J5-9 to DSIO-LV - J4-9.  
Wire the secondary common to TB7-2. Connect the trans-  
former ground to ground hole supplied near the trans-  
former. These connections provide DSIO with necessary  
power to energize the solenoid coils.  
3. When all connections are made, check for proper wiring  
and tight connections. Replace and secure inner panel.  
Restore power to unit.  
4. Configure the processor. With the addition of extra un-  
loaders, the unit configuration has changed. To change  
the configuration of the processor, enter the service func-  
tion using the keypad and display module. Before any  
changes can be made, the LOCAL/ENABLE-STOP-  
CCN switch must be in the STOP position, and the ser-  
vicer must log on to the processor.  
LEGEND  
COMM  
PWR  
Communications Bus  
Power  
a. Press  
PASSWORD.  
b. Enter  
LOGGEDON.  
. Keypad LCD displays the word  
Keypad LCD displays  
. Keypad LCD  
Fig. 22 — 4 In/4 Out Module (SIO)  
.
If accessory unloaders are desired, an accessory unloader  
package is used. Package includes a suction cutoff unloader  
head package. The 24-v coil in the package can be used  
for 040-110, 130 (60 Hz), and associated modular units  
(Table 1). A 115 v or 230 v coil must be used for 130  
(50 Hz), 150-210, and associated modular units (Table 1).  
Coil voltage depends on control circuit voltage. Consult cur-  
rent Carrier price pages for appropriate part numbers.  
c. To change configuration, press  
displays FLD CFG.  
d. If an additional unloader was added to compressor  
A1, press  
until NULA 1 appears in keypad dis-  
play. Press  
for the number of unloaders on  
circuit A. Keypad display now reads NULA 2.  
e. If an additional unloader was added to compressor  
NOTE: The accessory package will include all necessary com-  
ponents and wiring with the following exceptions: The field  
must provide screws, and on the 130-210, and associated modu-  
lar units, the field must also supply a 20 vdc (part number  
B1, press  
until NULB 1 appears in keypad dis-  
HK35AB001) unloader relay and wire (90°  
equivalent).  
C
or  
play. Press  
for the number of unloaders on  
circuit B. Keypad display now reads NULB 2.  
Installation  
f. When configuration is complete, press  
pad display reads LOGGEDON. Press  
. Key-  
1. Be sure all electrical disconnects are open and tagged be-  
fore any work begins. Inspect the package contents for  
any damage during shipping. File a claim with the ship-  
per if damage has occurred.  
until key-  
pad display reads LOG OFF. Press  
play reads EXIT LOG.  
. Keypad dis-  
2. For ease of installation, factory-supplied wiring for the  
additional unloader is provided in the compressor  
harness.  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 19 — Troubleshooting  
SYMPTOMS  
CAUSE  
REMEDY  
COMPRESSOR DOES  
NOT RUN  
Power line open  
Control fuse open  
Reset circuit breaker.  
Check control circuit for ground or short.  
Replace fuse.  
High-Pressure Switch (HPS)  
tripped  
Move LOCAL/ENABLE-STOP-CCN switch to STOP  
position then back to RUN or CCN position.  
Tripped power breaker  
Check the controls. Find cause of trip  
and reset breaker.  
Loose terminal connection  
Improperly wired controls  
Low line voltage  
Check connections.  
Check wiring and rewire.  
Check line voltage. Determine location  
of voltage drop and remedy deficiency.  
Compressor motor defective  
Check motor winding for open or short.  
Replace compressor if necessary.  
Seized compressor  
Replace compressor.  
Repair leak and recharge.  
Replace transducer.  
COMPRESSOR CYCLES OFF  
ON LOW PRESSURE  
Loss of charge  
Bad transducer  
Low refrigerant charge  
Add refrigerant.  
COMPRESSOR SHUTS DOWN  
ON HIGH PRESSURE  
CONTROL  
High-pressure control erratic in action  
Compressor discharge valve partially closed  
Condenser fan(s) not operating  
Replace control.  
Open valve or replace if defective.  
Check wiring. Repair or replace motor(s)  
if defective.  
Condenser coil plugged or dirty  
Low refrigerant charge  
Clean coil.  
UNIT OPERATES LONG OR  
CONTINUOUSLY  
Add refrigerant.  
Replace control.  
Clean or replace.  
Control contacts fused  
Partially plugged or plugged expansion  
valve or filter driver  
Defective insulation  
Service load  
Replace or repair.  
Keep doors and windows closed.  
Check valves. Replace if necessary.  
Support piping as required.  
Inefficient compressor  
Piping vibration  
SYSTEM NOISES  
Expansion valve hissing  
Add refrigerant.  
Check for plugged liquid line filter drier.  
Check valve plates for valve noise.  
Replace compressor (worn bearings).  
Check for loose compressor holddown bolts.  
Repair leak.  
Compressor noisy  
COMPRESSOR LOSES OIL  
FROSTED SUCTION LINE  
Leak in system  
Mechanical damage (blown piston or  
broken discharge valve)  
Repair damage or replace compressor.  
Crankcase heaters not energized  
during shutdown  
Replace heaters, check wiring and  
crankcase heater relay contacts.  
Expansion valve admitting either too  
much or too little refrigerant  
Check cooler and compressor thermistors.  
Test EXV.  
HOT LIQUID LINE  
Shortage of refrigerant due to leak  
Shutoff valve partially closed or restricted  
Burned out coil  
Repair leak and recharge.  
Open valve or remove restriction.  
Replace coil.  
FROSTED LIQUID LINE  
COMPRESSOR DOES NOT  
UNLOAD  
Defective capacity control valve  
Miswired solenoid  
Replace valve.  
Rewire correctly.  
Weak, broken, or wrong valve body spring  
Miswired solenoid  
Replace spring  
COMPRESSOR DOES NOT  
LOAD  
Rewire correctly.  
Defective capacity control valve  
Plugged strainer (high side)  
Replace valve.  
Clean or replace strainer.  
Clean or replace the necessary parts.  
Stuck or damaged unloader piston or  
piston ring(s)  
EXV  
Electronic Expansion Valve  
Table 20 — Standard and Accessory Unloaders  
NO. OF ACCESSORY  
UNLOADERS  
PERMITTED  
NO. OF STANDARD  
UNLOADER(s)  
UNIT  
Circuit A  
Circuit B  
30GN040-070  
30GN080-170*  
30GN190-210*  
1
2
0
1
1
1
1 or 2  
1
1
*And associated modular units.  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
b. Log into the processor and enter the service func-  
tion using the keypad and display module.  
5. Using test function, check unloaders. Press  
pad display reads OUTPUTS. Press  
. Key-  
until display  
Press  
.
The keypad LCD will display  
reads UNA2 OFF. Press  
and relay deenergizes. Press  
UNB2 OFF. Press . Relay energizes. Press  
and relay deenergizes.  
. Relay energizes. Press  
‘‘PASSWORD.’’ Enter  
keypad LCD will display ‘‘LOGGEDON.’’  
, and the  
until display reads  
c. To change the configuration, press  
, and the  
keypad LCD will display ‘‘FLD CFG.’’ Press  
6. When unloader check has been performed, return LOCAL/  
ENABLE-STOP-CCN to proper position. Close and se-  
cure control box door.  
until either ‘‘NULA 0’’ or ‘‘NULA 1’’ is displayed  
(depending on the number of unloaders provided as  
standard). Then press  
or (for 2 unloaders on compressor A1). The  
display will now read either ‘‘NULA 1’’ or  
‘‘NULA 2,’’ as appropriate. Press to get to the  
(for 1 unloader on A1)  
130 (50 Hz), 150-210 UNITS (AndAssociated Modular Units)  
1. Install control wiring. The minimum wire size for instal-  
lation is 16 AWG (American Wire Gage). Refer to  
Fig. 23 and 24 for proper wiring. Open the control box  
door. Locate unloader relays A and B (UA, UB) in place  
of the hot gas bypass relays as shown on the component  
arrangement diagram on the unit. Mount the relays with  
the field-supplied screws. Be careful not to damage the  
components and wiring in the area when mounting the  
relays.  
2. Wire the control side. Wire the UA coil in series between  
J6-18 and J6-19 of the 4 IN/4 OUT module with the wires  
provided. Wire the UB coil in series between J6-21 and  
J6-22 of the same module with the wires provided.  
NULB display, and change this setting in the same man-  
ner as with circuit A.  
d. Once the configuration is complete, press  
,
and the keypad LCD will display ‘‘LOGGEDON,’’  
Press until the keypad LCD display reads ‘‘LOG  
OFF.’’ Press  
and the keypad LCD will display  
‘‘EXIT LOG.’’  
5. Once the unloader heads are installed, the unit is checked  
for leaks, and the system is prepared for operation per the  
instructions for the compressor unloader head installa-  
tion, check the output of the relays using the test function  
as follows:  
Locate the black wire in the control harness originating  
from TRAN5 labeled HGBPR-A-COM. Connect this wire  
to the UAterminal COM. Connect the wire labeled HGBPR-  
A-NO to UA-NO. Connect the wire from UA-NO to  
TB3-5. For an extra unloader on circuit B, connect the  
wire labeled HGBPR-B-COM to UR-B-COM, and the wire  
labeled HGBPR-B-NO to UB-NO. Connect the wire from  
UB-NO to TB3-6.  
a. Press  
, and the display will read ‘‘COMP.’’  
b. Press the  
to scroll down until the display reads  
‘‘CPA1 OFF.’’  
3. Wire in the solenoid valves.  
c. Press  
d. Press  
, and the compressor should start.  
, and the compressor should stop.  
NOTE: Wires external to the control box must be run in  
conduit.  
Terminal blocks are provided for easy field wiring. Use  
one of the isolated 78-in. (22-mm) holes in the side of the  
compressor electrical box with a strain relief to run the  
wires to the solenoid coil. Connect UA between TB3-5  
and TB3-8. Connect UB between TB3-6 and TB3-8. Check  
all of the electrical connections for proper location and  
tightness, and replace and secure the electrical box of the  
compressor.  
e. Press  
f. Press  
until the display reads ‘‘UNA1 OFF.’’  
, and the solenoid should energize.  
g. Press  
and the solenoid should deenergize.  
h. Use the  
and  
keys to check the remainder of  
the unloader coils.  
6. Once the check has been performed, return the LOCAL/  
ENABLE-STOP-CCN switch to the proper position.  
7. Close and secure the control box door.  
8. Start the unit and confirm that the chiller operates  
properly.  
4. Configure the microprocessor. Once the relays are mounted  
in the control box, the microprocessor must be config-  
ured for the unloader option. To do so:  
a. Be sure the LOCAL/ENABLE-STOP-CCN switch is  
in the STOP position.  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND  
*Or HGBPR-A.  
†Or HGBPR-B.  
C
Contactor  
PWR  
SW  
TRAN  
U
Power  
CB  
Circuit Breaker  
Switch  
COMM  
HGBPR  
Communications Bus  
Hot Gas Bypass Relay  
Transformer  
Unloader  
Fig. 23 — Accessory Unloader Control Wiring, All Units  
LEGEND  
COM  
HGBPR  
NO  
Communications Bus  
Hot Gas Bypass Relay  
Normally Open  
TB  
TRAN  
U
Terminal Block  
Transformer  
Unloader  
SNB  
Snubber  
Fig. 24 — Flotronic™ II 115/230-V (Unloader Wiring, 130 (50 Hz), 150-210 and Associated Modular Units  
(See Table 1)  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIELD WIRING  
Refer to Fig. 25-35 for field wiring.  
NOTE: Contacts must be rated for dry circuit application, capable of  
reliably switching a 5 vdc, 1 mA to 20 mA load.  
Fig. 25 — Demand Limit — Two External  
Switch Inputs  
Fig. 26 − Demand Limit — 4-20 mA Signal  
Fig. 30 — Remote Reset from 4-20 mA Signal  
(Internally Powered)  
(Externally Powered)  
TB  
Terminal Block  
NOTE: Contacts must be rated for dry circuit application, capable of  
reliably switching a 5 vdc, 1 mA to 20 mA load.  
Fig. 27 — Demand Limit — 4-20 mA Signal  
(Internally Powered)  
Fig. 31 — Remote On/Off  
Fig. 28 — Remote Reset from Space or  
Outdoor-Air Temperature  
Fig. 32 — Remote Dual Set Point Control  
Fig. 29 — Remote Reset from 4-20 mA Signal  
(Externally Powered)  
CWP  
TB  
Chilled Water (Fluid) Pump  
Terminal Block  
Fig. 33 — Chilled Fluid Pump  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Remove defective PSIO by removing its mounting screws  
with a Phillips screwdriver, and removing the module  
from the control box. Save the screws for later use.  
5. Use a small screwdriver to set address switches S1 and  
S2 on the new PSIO module to exactly match the set-  
tings on the defective module.  
6. Package the defective module in the carton of the new  
module for return to Carrier.  
TB  
Terminal Block  
7. Mount the new module in the unit control box using a  
Phillips screwdriver and the screws saved in Step 4 above.  
Fig. 34 — Remote Alarm  
8. Reinstall all 6 wire connectors and the green ground wire.  
9. Carefully check all wiring connections before restoring  
power.  
10. Verify the LOCAL/ENABLE-STOP-CCN switch is in  
STOP position.  
11. Restore control power. Verify the red and green lights  
on top of PSIO and front of each DSIO module respond  
as described in Control Modules section on page 63. The  
keypad and display module should also begin its rotat-  
ing display.  
CWP1  
CWFS  
Chilled Water (Fluid) Pump Interlock  
Chilled Water (Fluid) Flow Switch (not required — low flow  
protection is provided by Flotronic™ II controls)  
Terminal Block  
TB  
12. Using the keypad and display module, press  
to verify that the software version number matches the  
ER (engineering requirement) number shown on the PSIO  
label.  
Fig. 35 — Interlocks  
REPLACING DEFECTIVE  
PROCESSOR MODULE  
13. Press  
to verify that the 7 factory configuration  
codes (CODE 1 through CODE 7) exactly match the codes  
listed for this unit model on the component arrangement  
label diagram on the control box door. If they are dif-  
ferent or are all zeros, reenter the 7 codes. If any changes  
are required, the PSIO display becomes blank and  
The replacement part number is printed on a small label  
on the front of the PSIO module. The model and serial num-  
bers are printed on the unit nameplate located on an exterior  
corner post. The proper software and unit configuration data  
is factory installed by Carrier in the replacement module.  
Therefore, when ordering a replacement processor module  
(PSIO), specify complete replacement part number, full unit  
model number, and serial number. If these numbers are not  
provided, the replacement module order is configured in-  
stead as a generic Flotronic II replacement module. This re-  
quires reconfiguration of the module by the installer.  
reconfigures itself after pressing the  
key while dis-  
playing CODE 7. The display returns in approximately  
15 seconds.  
NOTE: Codes with leading zeros in the configuration  
will be displayed starting with the first number greater  
than zero.  
14. Press  
to verify each item is configured as needed  
Electrical shock can cause personal injury. Disconnect  
all electrical power before servicing.  
for this particular installation. Table 14 shows the fac-  
tory configuration code default settings. Table 14 also  
shows the service replacement code default settings which  
are used if no model number was specified when order-  
ing the replacement PSIO module. It is strongly sug-  
gested that the Start-Up Checklist for Flotronic II Chiller  
Systems (completed at time of original start-up) be used  
at this time to verify and/or reprogram the various op-  
tions and configurations required for this job.  
Installation  
1. Verify the existing PSIO module is defective by using  
the procedure described in the Control Modules section  
on page 63.  
2. Refer to Start-Up Checklist for Flotronic II Chiller Sys-  
tems (completed at time of original start-up) found in  
job folder. This information is needed later in this  
15. Press  
to verify that the 2 field configuration  
codes (codes 8 and 9) match exactly the codes listed on  
the label diagram on the control box door. If they are  
different, or are all zeros, reenter the 2 codes.  
procedure. If checklist does not exist, fill out the  
and  
configuration code sections on a new check-  
list. Tailor the various options and configurations as needed  
for this particular installation.  
16. After completing the configuration steps outlined above,  
restore main power and perform a unit test as de-  
3. Check that all power to unit is off. Carefully disconnect  
all wires from defective module by unplugging the 6 con-  
nectors. It is not necessary to remove any of the indi-  
vidual wires from the connectors. Remove the green ground  
wire.  
scribed in  
and  
sections on page 38.  
17. Complete this procedure and restore chiller to normal  
operation by returning the LOCAL/ENABLE-STOP-  
CCN switch to desired position.  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Copyright 1995 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 2  
PC 903  
Catalog No. 563-079  
Printed in U.S.A.  
Form 30GN-3T  
Pg 72  
7-95  
Replaces: 30G-1T  
Tab 5c  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Blomberg Ice Maker DND 1972 ED User Manual
Bosch Appliances Clothes Dryer WTMC5521 User Manual
Bosch Appliances Security Camera LTC9412 00 User Manual
Breville Mixer BFP250 User Manual
Briggs Stratton Portable Generator Liquid Cooled Home Generator System User Manual
Brother Wheelchair BAS 311G User Manual
Bryant Furnace 376C User Manual
Cabletron Systems Switch ELS100 24TXM User Manual
Campbell Hausfeld Air Compressor IN615601AV User Manual
Canon Camera Lens EF 300mm f 4L IS USM User Manual