30HK040-060
30HL050,060
30HW018-040
Reciprocating Liquid Chillers
50/60 Hz
Installation, Start-Up and
Service Instructions
• COMPRESSOR INTERNAL THERMAL PROTECTION
CONTENTS
• CRANKCASE HEATER
Page
• OIL PRESSURE SAFETY SWITCH (OPS)
Check Unit Safeties . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
• CONTROL MODULE
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-25
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Step 1 — Inspect Shipment . . . . . . . . . . . . . . . . . . . . . 3
Step 2 — Rig the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 3
• 30HK,HL UNITS
• HIGH-PRESSURE SWITCH
• LOW-PRESSURE SWITCH
• CHILLED FLUID TEMPERATURE CONTROLLER
• FREEZE-UP PROTECTION
• LOSS-OF-COOLER-FLOW PROTECTION
• COMPRESSOR GROUND FAULT SENSOR
• 30HW UNITS
Step 3 — Place the Unit . . . . . . . . . . . . . . . . . . . . . . . . 3
• 30HK,HL UNITS
UNIT OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-32
Capacity Control and Operating Sequence . . . . . . . 30
• 30HK,HL UNITS
• 30HW UNITS
Step 4 — Check Compressor Mounting and
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Step 5 — Make Piping Connections . . . . . . . . . . . . . 13
• 30HK,HWC,HWS CONDENSER DESCRIPTION
• 30HL,HWA SYSTEM CONDENSER
• 30HWB CONDENSER DESCRIPTION
• 30HK,HWC,HWS CONDENSER(S)
• 30HWB CONDENSER
• 30HW UNITS
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-35
Compressor Replacement . . . . . . . . . . . . . . . . . . . . . . 32
Circuit Breaker(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Brazed-Plate Cooler and Condenser
Heat Exchanger Replacement . . . . . . . . . . . . . . . . . 32
Brazed-Plate Cooler and Condenser
Heat Exchanger Cleaning . . . . . . . . . . . . . . . . . . . . . 32
Shell-and-Tube Condenser Cleaning . . . . . . . . . . . . . 32
Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
• THERMISTOR REPLACEMENT, 30HK,HL UNITS
• THERMISTOR REPLACEMENT, 30HW UNITS
• 30HK,HWB,HWC,HWS UNITS
• COOLER DESCRIPTION
• COOLER PIPING
Step 6 — Make Electrical Connections . . . . . . . . . . . 19
• 30HK,HL UNITS
SERVICING COOLER (30HK,HL ONLY) . . . . . . . . . 36,37
Tube Plugging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
• RETUBING
Tightening Cooler Head Bolts . . . . . . . . . . . . . . . . . . 36
• GASKET PREPARATION
• BOLT TORQUES
• 30HW UNITS
• ALL UNITS
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-27
Initial Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Check Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . 26
• LIQUID CHARGING METHOD
Check Oil Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
• TO ADD OIL
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 37-39
Complete Unit Stoppage and Restart . . . . . . . . . . . . 37
• GENERAL POWER FAILURE
• UNIT ON-OFF SWITCH IS OPEN
• CONTACTS OF ANY AUXILIARY INTERLOCKS ARE
OPEN
• CHILLED FLUID PROOF-OF-FLOW SWITCH(ES) OPEN
• OPEN LOW-PRESSURE SWITCH
• TEMPERATURE CONTROLLER SHUTS UNIT DOWN ON
OUT-OF-RANGE
• OPEN HIGH-PRESSURE SWITCH(ES)
• OPEN COMPRESSOR INTERNAL THERMAL
PROTECTION
• OPEN OIL PRESSURE SWITCH
• OPEN CONTACTS ON COMPRESSOR GROUND-
CURRENT SENSOR(S) (Accessory)
• OPEN 24-V CONTROL CIRCUIT BREAKER(S)
• COOLING LOAD SATISFIED
• THERMISTOR FAILURE
• TO REMOVE OIL
START-UP AND OPERATION . . . . . . . . . . . . . . . . . . 27-30
Operation Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Operating Limitations . . . . . . . . . . . . . . . . . . . . . . . . . 27
• HIGH COOLER LEAVING CHILLED WATER (FLUID)
TEMPERATURES (LCWT)
• LOW COOLER LCWT
• MAIN POWER SUPPLY
Check Refrigerant Feed Components . . . . . . . . . . . . 27
• THERMOSTATIC EXPANSION VALVE (TXV)
• FILTER DRIER
• MOISTURE-LIQUID INDICATOR
• LIQUID LINE SERVICE VALVE
• DISCHARGE LINE CHECK VALVE
• HOT GAS BYPASS VALVE
• LIQUID LINE SOLENOID VALVE (30HL ONLY)
• PRESSURE RELIEF DEVICES
Compressor and Unit Protective Devices . . . . . . . . . 28
• CIRCUIT BREAKER
START-UP CHECKLIST FOR
CHILLER SYSTEMS . . . . . . . . . . . . . . . . . . . CL-1 to CL-4
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
PC 903
Catalog No. 533-070
Printed in U.S.A.
Form 30H-10SI
Pg 1
11-98
Replaces: 30H-8SI
Tab 5c
Download from Www.Somanuals.com. All Manuals Search And Download.
If unit is to be dragged into final position, or moved on
rollers, it is recommended that it be left on the skid. When
dragging or rolling, apply force only to the skid, not to the
unit. Lift from above, using the lifting angles provided, to
remove unit from the skid.
INSTALLATION
Location — Do not store units in an area exposed to weather
because of sensitive control mechanisms and electronic
devices. Locate unit indoors. See Fig. 4-8 for unit dimen-
sional details.
Allow 36 in. (914 mm) in front of the unit for control box
access door. Compressor can be removed from either side or
the front of the unit. Prior to installation determine which
direction compressor will be removed, and leave 3 to 4 ft
(914 to 1219 mm) clearance for removal.
On 30HK,HL units leave 71⁄2 ft (2.3 m) (for 040 units) or
9 ft (2.7 m) (for 050,060 units) clearance on one side for
cooler tube removal. Leave 2 ft (610 mm) clearance on the
other side for making fluid connections to cooler and water
connections to condenser. See Fig. 4 and 5.
On 30HWA,B units, leave 2 ft (610 mm) on one side for
making fluid connections to cooler and water connections to
condenser, accessing the thermostatic expansion valve (TXV),
and replacing heat exchanger(s) if necessary. See Fig. 6
and 7.
On 30HWC,S units, leave 75 in. (1905 mm) on one side
for condenser tube removal and 2 ft (610 mm) on the other
side for making fluid connections to cooler and water con-
nections to condenser, accessing the TXV, and replacing heat
exchanger(s) if necessary. See Fig. 8.
The floor must be strong enough to support the unit op-
erating weight (see Tables 1A-2B and Fig. 9 and 10). If nec-
essary, add a supporting structure (steel beams or reinforced
concrete slabs) to the floor to transfer weight to nearest beams.
30HW UNITS
NOTE: If accessory mobility package (Carrier part no.
30HW900008) is to be used, install this accessory after bring-
ing unit into building and before moving the unit to its final
location per installation instructions provided with the
accessory.
Units Equipped With Factory-Installed Unit Wheels — This
factory-installed option consists of 4 swivel-type wheels
mounted to the legs of the unit. See Fig. 11. For units equipped
with this option, leave the skid on until the unit is in the
building. Once in the building, remove the skid, and wheel
the unit to its final location.
NOTE: The wheels are equipped with a thumb-screw brake.
Units Not Equipped With Factory-Installed Unit Wheels —
Do not remove the skid until the unit has been moved to its
final location. The unit may be moved by means of rollers
under the skid, a forklift truck, or rig and slings.
Step 3 — Place the Unit
30HK,HL UNITS — When unit is in final position, remove
skid, level the unit (using a level), and bolt the unit to floor
or pad.
NOTE: These units are not suitable for unprotected outdoor
use.
Carrier recommends that these units be located in the base-
ment or on the ground floor. However, if it is necessary to
locate the unit on an upper floor, be sure the structure has
been designed to support the unit weight. If necessary, add
structural support to floor. Also, be sure the surface for in-
stallation is level. Refer to Fig. 4 and 5 for space require-
ments and Fig. 9 for weight distribution.
Additional weights of factory-installed options (30HW only)
are:
Sound enclosure — 75 lb (34 kg)
Hot gas bypass — 15 lb (7 kg)
80-amp non-fused disconnect — 15 lb (6.8 kg)
100-amp non-fused disconnect — 25 lb (11.3 kg)
200-amp non-fused disconnect — 70 lb (31.8 kg)
Only electrical power connections, water connections for
condenser, and fluid connections for cooler are required for
30HK installation. Installation of 30HL units varies only in
field piping required for the remote condenser.
Be sure interconnecting piping and electrical conduits
are suspended freely, and are not in contact with any
adjacent walls. Be sure unit capillaries are not rubbing
against anything.
30HW UNITS — When the unit is in its final position, re-
move the skid (from units not equipped with factory-
mounted wheels), or remove the wheels (if equipped). Re-
3
move ⁄8-in. wheel nuts to remove wheels from unit legs.
Step 1 — Inspect Shipment — Inspect unit for dam-
age or missing parts. If damaged, or if shipment is incom-
plete, file a claim immediately with the shipping company.
Level the unit (using a level), and bolt the unit to the floor
or pad.
If unit is to be mounted on unit external vibration isola-
tors, follow the mounting instructions included with the ac-
cessory vibration isolator (Carrier part numbers 30HW900-
001 and -002).
Step 2 — Rig and Place Unit
30HK,HL UNITS — On each end of cooler, a steel loop is
provided for the preferred method of lifting unit. Use spreader
bars to keep cables away from compressor enclosure and
control box. If unit is to be moved by forklift truck, use one
of the following two methods:
1. From front or rear, lift under the cooler rails. Unit can be
either on or off skid.
Step 4 — Check Compressor Mounting and
Connections — As shipped, the compressor is held down
by special self-locking nuts (Fig. 12). After unit is installed,
loosen the self-locking nuts one at a time until compressor
floats freely. Do not remove nuts, as they are self-locking
and will hold their locked position.
2. When moving from the ends, leave unit on the skid. Lift
from under the skid.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
TOP VIEW
FRONT VIEW
RIGHT SIDE VIEW
DIMENSIONS — in. (mm)
UNIT
30HK
A
B
C
D
715⁄16
(202)
51⁄4
(133)
90
(2286)
149⁄16
(370)
040
103⁄4
(273)
108
(2743)
201⁄16
(510)
139⁄16
(344)
050,060
LEGEND
COMP
—
—
—
—
Compressor
Knockout
Mounting
K.O.
MTG
SAE
Society of Automotive Engineers (U.S.A.)
NOTES:
1. Standard unit shown with the sound enclosure
accessory.
2. Dimensions are in inches unless otherwise
indicated.
Dimensions in ( ) are in millimeters.
3. Service clearance for the control box is 36-in.
LEFT SIDE VIEW
Fig. 4 — 30HK040-060 (Fluid Cooled)
4
Download from Www.Somanuals.com. All Manuals Search And Download.
TOP VIEW
FRONT VIEW
RIGHT SIDE VIEW
LEGEND
CLY
—
—
—
—
Cylinder
COMP
CONN
K.O.
Compressor
Connection
Knockout
NOTES:
1. Standard unit shown with the sound en-
closure accessory.
2. Dimensions are in inches unless oth-
erwise indicated. Dimensions in ( ) are
in millimeters.
LEFT SIDE VIEW
Fig. 5 — 30HL050,060 (Condenserless)
5
Download from Www.Somanuals.com. All Manuals Search And Download.
REAR VIEW
LEFT SIDE VIEW
DIMENSIONS — in. (mm)
UNIT
30HWA
A
B
C
D
E
F
G
12.58
(320)
19.20
(488)
20.48
(520)
33.85
(860)
11.72
(298)
5.75
17.95
(456)
018
025
028
035
040
(146)
12.82
(326)
18.98
(482)
20.57
(522)
33.85
(860)
11.72
(298)
5.75
(146)
17.95
(456)
12.64
(321)
18.31
(465)
20.73
(527)
33.85
(860)
11.72
(298)
5.75
(146)
17.95
(456)
12.87
(327)
18.62
(473)
20.81
(529)
33.85
(860)
11.72
(298)
5.75
(146)
17.95
(456)
12.66
(322)
18.64
(473)
21.30
(541)
34.15
(867)
11.34
(288)
8.22
(209)
17.36
(441)
RIGHT SIDE VIEW
LOCATION — in. (mm)
MODEL 30HWA (See Table Below)
DISCONNECT
(Amps)
J
K
L
M
018---
025---
028---
035---
040---
3.33
(85)
2.98
(76)
14.44
(367)
46.50
100,200,
100,200,
600,900
100,200,
600,900
80
100
200
100,600,900
—
(1181)
600,800,900
4.33
(110)
4.98
(126)
14.82
(376)
47.50
(1207)
100,200,
600,900
500
—
500,800
—
800
500
200,800
500
7.46
(189)
11.19
(284)
15.82
(402)
54.50
(1384)
500,800
NOTES:
LEGEND
MODEL
VOLT-Hz
DISC.
K.O.
—
—
Disconnect
Knockout
1.
2.
Denotes center of gravity.
Denotes accessory or factory-installed option.
100
200
500
600
800
900
575-60
380-60
3. Dimensions are in inches. Dimensions in ( ) are in millimeters.
208/230-60
460-60
230-50
400-50
Fig. 6 — 30HWA018-040 (Condenserless)
6
Download from Www.Somanuals.com. All Manuals Search And Download.
REAR VIEW
LEFT SIDE VIEW
DIMENSIONS — in. (mm)
UNIT
30HWB
A
B
C
D
E
F
G
H
J
13.14 18.72 22.02 33.85 11.72 5.75 12.29 17.95 9.28
(334) (475) (559) (860) (298) (146) (312) (456) (236)
018
025
028
035
040
13.22 18.25 22.10 33.85 11.72 5.75 12.29 17.95 9.28
(336) (464) (561) (860) (298) (146) (312) (456) (236)
13.18 17.71 22.39 33.85 11.72 5.75 12.29 17.95 9.28
(335) (450) (569) (860) (298) (146) (312) (456) (236)
13.45 17.98 22.68 33.85 11.72 5.75 12.29 17.95 9.28
(342) (457) (576) (860) (298) (146) (312) (456) (236)
13.27 17.75 23.44 34.15 11.34 8.22 12.38 17.36 8.22
(337) (451) (595) (867) (288) (209) (314) (441) (209)
RIGHT SIDE VIEW
LOCATION — in. (mm)
MODEL 30HWB (See Table Below)
DISCONNECT
(Amps)
K
L
M
N
018---
025---
028---
035---
040---
3.33
(85)
2.98
(76)
14.44
(367)
46.50
(1181)
100,200,300,
600,800,900
100,200,
600,900
100,200,
600,900
100,200,
600,900
80
100
4.33
4.98
14.82
(376)
47.50
200,
100
200
500
—
500,800
—
500,800
—
800
500
(110)
(126)
(1207)
600,900
7.46
(189)
11.19
(284)
15.82
(402)
54.50
(1384)
500,800
LEGEND
NOTES:
MODEL
VOLT-Hz
COND
DISC.
K.O.
—
—
—
Condenser
Disconnect
Knockout
1.
2.
Denotes center of gravity.
Denotes accessory or factory-installed option.
100
200
500
600
800
900
575-60
380-60
3. Dimensions are in inches. Dimensions in ( ) are in millimeters.
208/230-60
460-60
230-50
400-50
Fig. 7 — 30HWB018-040 (Fluid Cooled)
7
Download from Www.Somanuals.com. All Manuals Search And Download.
LEFT SIDE VIEW
FRONT VIEW
DIMENSIONS — in. (mm)
UNIT
30HWC,S
A
B
C
D
E
F
G
47.50
9.90
14.00
(356)
18.15
(461)
17.95
(456)
6.69
34.20
(869)
018
025
028
035
040
(1206)
(251)
(170)
48.30
(1227)
9.90
(251)
15.50
(394)
18.15
(461)
17.95
(456)
6.69
(170)
34.20
(869)
48.00
(1219)
10.00
(254)
15.80
(401)
18.15
(461)
17.95
(456)
6.69
(170)
34.20
(869)
48.20
(1224)
10.00
(254)
15.90
(404)
18.15
(461)
17.95
(456)
6.69
(170)
34.20
(869)
47.80
(1214)
10.00
(254)
15.90
(404)
18.45
(469)
17.36
(441)
6.40
(163)
32.94
(837)
RIGHT SIDE VIEW
LOCATION — in. (mm)
K
MODEL 30HWC,S (See Table Below)
DISCONNECT
(Amps)
J
L
018---
025---
028---
035---
040---
77.61
4.38
3.33
100,200,
100,200,
600,900
100,200,
600,900
100,200,
600,900
80
100
200
100
(1971)
(111)
(85)
600,800,900
79.61
(2022)
5.00
(127)
4.33
(110)
200,
600,900
500
—
500,800
—
500,800
—
800
500
83.74
(2127)
10.00
(254)
7.46
(189)
500,800
LEGEND
NOTES:
MODEL
100
VOLT-Hz
D.
—
—
—
—
Diameter
1.
2.
Denotes center of gravity.
Denotes accessory or factory-installed option.
575-60
380-60
Disc.
K.O.
SCH.40
Disconnect
Knockout
200
Schedule 40 Pipe
3. Dimensions are in inches. Dimensions in ( ) are in millimeters.
500
208/230-60
460-60
600
800
230-50
900
400-50
Fig. 8 — 30HWC,S018-040 (Fluid Cooled)
8
Download from Www.Somanuals.com. All Manuals Search And Download.
WEIGHT DISTRIBUTION AT EACH MOUNTING HOLE, 60 HZ UNITS
MOUNTING HOLES
30HK
Kg
30HL
UNIT
SIZE
A
B
C
D
A
B
C
D
Lb
Kg
322
357
380
Lb
Lb
Kg
320
355
377
Lb
Kg
319
354
376
Lb
—
Kg
—
Lb
—
Kg
—
Lb
—
Kg
—
Lb
—
Kg
—
040
050
060
710
787
838
712
789
840
323
358
381
705
782
832
703
780
830
519
534
235
242
521
536
236
243
516
531
234
241
514
529
233
240
NOTE: See Fig. 4 and 5 for specific mounting hole location dimensions.
WEIGHT DISTRIBUTION AT EACH MOUNTING HOLE, 50 HZ UNITS
MOUNTING HOLES
30HK
Kg
30HL
UNIT
SIZE
A
B
C
D
A
B
C
D
Lb
Kg
327
380
387
Lb
Lb
Kg
325
377
384
Lb
Kg
325
376
383
Lb
—
Kg
—
Lb
—
Kg
—
Lb
—
Kg
—
Lb
—
Kg
—
040
050
060
721
838
853
723
840
855
328
381
388
716
832
847
715
830
845
534
550
242
249
526
551
238
250
531
545
241
247
529
544
240
247
NOTE: See Fig. 4 and 5 for specific mounting hole location dimensions.
LOCATION OF MOUNTING HOLES
Fig. 9 — Weight Distribution and Mounting Hole Location; 30HK,HL Units
30HWA,B
30HWC,S
WEIGHT DISTRIBUTION AT EACH MOUNTING HOLE — Lb (kg)
MOUNTING HOLE NO.
UNIT
30HW
1
2
3
4
5
6
7
8
A018
A025
185 (83.9)
220 (99.8)
240 (108.9)
244 (110.7)
270 (122.5)
199 (90.3)
238 (108.0)
266 (120.7)
271 (122.9)
328 (148.8)
171 (77.6)
196 (88.9)
211 (95.7)
216 (98.0)
240 (108.9)
—
—
A028
—
A035
—
—
A040
B018
—
B025
—
B028
—
B035
—
B040
—
C,S018
C,S025
C,S028
C,S035
C,S040
136 (61.7)
144 (65.3)
160 (72.6)
161 (73.0)
185 (83.9)
Fig. 10 — Mounting Hole Weight Distribution; 30HW Units
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1A — Physical Data; 30HK, HWB, HWC, and HWS Fluid-Cooled Units — English
UNIT 30
HW-018*
HW-025*
HW-028*
HW-035*
HW-040*
HK040
HK050
HK060
OPERATING WT (Approximate) − lb
HWB
795
950
1065
1484
1085
1508
1310
1702
—
—
—
—
3340/
3400†
HWC,S
1231
1358
—
—
2830/
2875†
3138/
3340†
HK
—
—
—
—
—
REFRIGERANT — lb
HWB
R-22
12.5
35.0
—
15.0
37.0
—
17.5
42.0
—
18.5
42.0
—
23.2
47.0
—
—
—
—
HWC,S
—
—
—
HK — Ckt 1
HK − Ckt 2
35/40†
35/35†
45/45†
35/45†
45/45†
45/45†
—
—
—
—
—
COMPRESSOR
Model No.
06E6175,
06E2150
20,30
06DG537
06E2150**
06E7265
06E7175**
06E7299
06E2150
06E6175
Nominal Hp
Quantity
Cylinders Per Compressor
Capacity Control — Standard
No. of Steps
Minimum Step Capacity (%)
Capacity Control — With Optional
Hot Gas Bypass
No. of Steps
Minimum Step Capacity (%)
Relief Valve Flow Rate — lb air/min
15
1
6
20
1
4
25
1
6
30
1
6
35
1
6
20 (ea)
2
4 (ea)
30 (ea)
2
6 (ea)
1 (ea)
6,4
3
33
2
50
3
33
3
33
3
33
4
25
4
20††
4
33
4
10
—
3
4
4
4
5
5
5
10
10
10
10
10
10
10
15.1
15.1
15.1
15.1
15.1
15.1
15.1
COOLER
Part No.
LL01SB006 LL01SB007 LL01SB009 LL01SB009 LL01SC005 10HA400654 10HA400664 10HA400664
Dry Weight — lb
Fluid Side — psig
Refrigerant Side — psig
Net Fluid Volume — Gal.
(includes nozzles)
Fluid Connections — in.
Inlet
69
300
430
1.4
81
300
430
1.6
105
300
430
2.1
105
300
430
2.1
145
300
430
3.3
657
150
235
13.1
726
150
235
15.2
726
150
235
15.2
Grooved End
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
21⁄2
21⁄2
3
3
3
3
3
3
Outlet
CONDENSER
30HWB (Water Cooled)
Part No. LL01S-
Dry Weight — lb
Water Side — psig
Refrigerant Side — psig
Net Water Volume — Gal.
(includes nozzles)
Water Connections — in.
Inlet
D001
48
300
430
0.9
D002
62
300
430
1.2
D003
79
300
430
1.6
D004
87
300
430
1.8
E004
153
300
430
3.3
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Grooved End
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
21⁄2
21⁄2
—
—
—
—
—
—
Outlet
30HWC (Water Cooled)
Part No. 09RW-
400007
532
400007
532
400011
560
400011
560
400009
624
—
—
—
—
—
−
—
—
—
—
—
—
—
—
—
—
—
—
Dry Weight — lb
Water Side — psig
Refrigerant Side — psig
Net Water Volume — Gal.
Relief Valve Flow Rate — lb air/min
Water Connections — in.
Inlet
300
300
300
300
300
365
365
365
365
365
7.3
2.6
2.6
4.0
4.0
24.6
24.6
24.6
24.6
24.6
Weld
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
—
—
—
—
—
—
Outlet
30HWS (Water Cooled)
Part No. 09RW-
400017
532
400017
532
400019
560
400019
560
400018
624
—
—
—
—
—
−
—
—
—
—
—
—
—
—
—
—
—
—
Dry Weight — lb
Water Side — psig
Refrigerant Side — psig
Net Water Volume — Gal.
Relief Valve Flow Rate — lb air/min
Water Connections — in.
Inlet
300
300
300
300
300
335
335
335
335
335
7.3
2.6
2.6
4.0
4.0
22.6
22.6
22.6
22.6
22.6
Weld
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
—
—
—
—
—
—
Outlet
30HK (Water Cooled)
Part No. 09RP-
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
022/022†
1000
022/027†
1095
027/027†
1190
Dry Weight — lb
Water Side — psig
Refrigerant Side — psig
Net Water Volume — Gal.
(includes nozzles)
Relief Valve Flow Rate — lb air/min
Water Connections — in.
Inlet
250
250
250
385
4.4/4.4†
385
4.4/5.2†
385
5.2/5.2†
—
—
—
—
—
25.9
25.9
25.9
Weld
—
—
—
—
—
—
—
—
—
—
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
Outlet
LEGEND
NOTES:
1. Operating weight includes refrigerant operating charge and weight of fluid
in the heat exchangers.
ODS
—
Outside Diameter, Sweat
*Unless otherwise noted, data is for HWB, HWC, and HWS units.
†60 Hz/50 Hz units.
2. 30HK,HWB,HWC, and HWS units are shipped with full operating charge.
**For 025 50 Hz units, compressor number is 06E2250, for 035 50 Hz units
compressor number is 06E7275.
††With transfer switch set to compressor no. 2 position; 40% with transfer switch
set to compressor no. 1 position.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1B — Physical Data; 30HK, HWB, HWC, and HWS Fluid-Cooled Units — SI
UNIT 30
HW-018*
HW-025*
HW-028*
HW-035*
HW-040*
HK040
HK050
HK060
OPERATING WT (Approximate) − kg
HWB
360
554
431
611
483
668
492
679
594
766
—
—
—
HWC,S
—
—
—
1284/
1305†
1424/
1514†
1514/
1542†
HK
—
—
—
—
—
REFRIGERANT — kg
HWB
R-22
8.4
5.7
15.9
—
6.8
16.8
—
7.9
19.1
—
10.5
21.3
—
—
—
—
HWC,S
19.1
—
—
—
—
HK — Ckt 1
HK — Ckt 2
15.9/18.1†
15.9/15.9†
20.4/20.4†
15.9/20.4†
20.4/20.4†
20.4/20.4†
—
—
—
—
—
COMPRESSOR
Model No.
06E6175,
06E2150
14.9,22.4
1 (ea)
06DG537
06E2150**
06E7265
06E7175**
06E7299
06E2150
06E6175
Nominal kW
Quantity
Cylinders Per Compressor
Capacity Control — Standard
No. of Steps
Minimum Step Capacity (%)
Capacity Control — With Hot Gas Bypass
No. of Steps
Minimum Step Capacity (%)
Relief Valve Flow Rate — kg air/min
11.1
1
6
14.9
1
4
18.7
1
6
22.4
1
6
26.1
1
6
14.9 (ea)
2
4 (ea)
22.4 (ea)
2
6 (ea)
6,4
3
33
2
50
3
33
3
33
3
33
4
25
4
20††
4
33
4
10
—
3
10
6.8
4
10
6.8
4
10
6.8
4
10
6.8
5
10
6.8
5
10
6.8
5
10
6.8
COOLER
Part No.
LL01SB006 LL01SB007 LL01SB009 LL01SB009 LL01SC005 10HA400654 10HA400664 10HA400664
Dry Weight — kg
Fluid Side — kPa
Refrigerant Side — kPa
Net Fluid Volume — L
(includes nozzles)
Fluid Connections — in.
Inlet
31.3
2069
2965
5.3
36.7
2069
2965
6.1
47.6
2069
2965
8.0
47.6
2069
2965
8.0
65.7
2069
2965
12.5
297
1034
1620
49.9
330
1034
1620
57.5
330
1034
1620
57.5
Grooved End
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
21⁄2
21⁄2
3
3
3
3
3
3
Outlet
CONDENSER
30HWB (Water Cooled)
Part No. LL01S-
Dry Weight — kg
Water Side — kPa
Refrigerant Side — kPa
Net Water Volume — L
(includes nozzles)
Water Connections — in.
Inlet
D001
21.8
2069
2965
3.4
D002
28.1
2069
2965
4.5
D003
35.8
2069
2965
6.1
D004
39.5
2069
2965
6.8
E004
69.4
2069
2965
12.5
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Grooved End
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
21⁄2
21⁄2
—
—
—
—
—
—
Outlet
30HWC (Water Cooled)
Part No. 09RW-
400007
241
400007
241
400011
254
400011
254
400009
283
2069
2517
27.6
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Dry Weight — kg
Water Side — kPa
Refrigerant Side — kPa
Net Water Volume — L
Relief Valve Flow Rate — kg air/min
Water Connections — in.
Inlet
2069
2517
9.8
2069
2517
9.8
2069
2517
15.4
2069
2517
15.4
11.2
11.2
11.2
11.2
11.2
Weld
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
—
—
—
—
—
—
Outlet
30HWS (Water Cooled)
Part No. 09RW-
400017
241
400017
241
400019
254
400019
254
400018
283
2069
2310
27.6
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Dry Weight — kg
Water Side — kPa
Refrigerant Side — kPa
Net Water Volume — L
Relief Valve Flow Rate — kg air/min
Water Connections — in.
Inlet
2069
2310
9.8
2069
2310
9.8
2069
2310
15.4
2069
2310
15.4
10.3
10.3
10.3
10.3
10.3
Weld
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
—
—
—
—
—
—
Outlet
30HK (Water Cooled)
Part No. 09RP-
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
022/022†
454
022/027†
497
027/027†
540
Dry Weight — kg
Water Side — kPa
Refrigerant Side — kPa
Net Water Volume — L
(includes nozzles)
Relief Valve Flow Rate — kg air/min
Water Connections — in.
Inlet
1724
1724
1724
2655
17/17†
2655
17/20†
2655
20/20†
—
—
—
—
—
11.7
11.7
11.7
Weld
—
—
—
—
—
—
—
—
—
—
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
Outlet
LEGEND
NOTES:
1. Operating weight includes refrigerant operating charge and weight of fluid
in the heat exchangers.
ODS
—
Outside Diameter, Sweat
*Unless otherwise noted, data is for HWB, HWC, and HWS units.
†60 Hz/50 Hz units.
2. 30HK,HWB,HWC, and HWS units are shipped with full operating charge.
**For 025 50 Hz units, compressor number is 06E2250, for 035 50 Hz units
compressor number is 06E7275.
††With transfer switch set to compressor no. 2 position; 40% with transfer switch
set to compressor no. 1 position.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2A — Physical Data; 30HL, HWA Condenserless Units — English
UNIT 30
HWA018
HWA025
HWA028
HWA035
HWA040
HL050
HL060
2070/
2120*
2130/
2190*
OPERATING WT (Approximate) − lb
REFRIGERANT† — lb
740
880
960
975
1080
R-22
2.4
1.6
2.0
2.4
3.0
6.3/4.2**
5.3/5.3**
COMPRESSOR
Model No.
06E6275,
06E2250
25,20
06DG537
06E2250
06E7265
06E7275
06E7299
06E6275
Nominal Hp
Quantity
Cylinders Per Compressor
Capacity Control — Standard
No. of Steps
Minimum Step Capacity (%)
Capacity Control — With Optional
Hot Gas Bypass
No. of Steps
Minimum Step Capacity (%)
Relief Valve Flow Rate — lb air/min
15
1
6
20
1
4
25
1
6
30
1
6
35
1
6
30 (ea)
2
6
1 (ea)
6,4
3
33
2
50
3
33
3
33
3
33
4
20††
4
33
4
10
—
3
4
4
4
5
5
10
10
10
10
10
10
15.1
15.1
15.1
15.1
15.1
15.1
COOLER
Part No.
LL01SB006
LL01SB007
LL01SB009
105
LL01SB009
105
LL01SC005
145
10HA400654
726
10HA400664
726
Dry Weight — lb
Fluid Side — psig
Refrigerant Side — psig
Net Fluid Volume — Gal.
(includes nozzles)
Fluid Connections — in.
Inlet
69
81
300
430
1.4
300
430
1.6
300
300
300
150
150
430
2.1
430
2.1
430
3.3
235
13.1
235
15.2
Grooved End
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
21⁄2
21⁄2
3
3
3
3
Outlet
CONDENSER CONNECTIONS
Refrigerant Connections — in.
Liquid Line ODS
7
7
7
7
7
7
7
⁄
8
⁄
8
⁄
8
⁄
8
⁄
8
⁄
8
⁄
8
Discharge Line ODS
11⁄8
11⁄8
13⁄8
13⁄8
15⁄8
13⁄8
13⁄8
LEGEND
NOTE: Operating weight includes refrigerant operating charge and weight of
fluid in the heat exchangers.
ODS
—
Outside Diameter, Sweat
*60 Hz/50 Hz units.
†30HWA and HL units (condenserless) are shipped with a refrigerant holding
charge. Approximate cooler operating charge is shown.
**Ckt 1/Ckt 2.
††With transfer switch set to compressor no. 2 position; 40% with transfer switch
set to compressor no. 1 position.
Table 2B — Physical Data; 30HL, HWA Condenserless Units — SI
UNIT 30
HWA018
HWA025
HWA028
HWA035
HWA040
HL050
HL060
938/
966/
OPERATING WT (Approximate) − kg
REFRIGERANT† — kg
335
399
435
442
490
961†
993†
R-22
1.1
0.7
0.9
1.1
1.4
2.9/1.9**
2.4/2.4**
COMPRESSOR
Model No.
06E6275,
06E2250
18.7,14.9
1 (ea)
06DG537
06E2250
06E7265
06E7275
06E7299
06E6175
Nominal kW
Quantity
Cylinders Per Compressor
Capacity Control — Standard
No. of Steps
Minimum Step Capacity (%)
Capacity Control — With Optional Hot Gas Bypass
No. of Steps
Minimum Step Capacity (%)
Relief Valve Flow Rate — kg air/min
11.2
1
6
14.9
1
4
18.7
1
6
22.4
1
6
26.1
1
6
22.4 (ea)
2
6
6,4
3
33
2
50
3
33
3
33
3
33
4
20††
4
33
4
10
—
3
10
6.8
4
10
6.8
4
10
6.8
4
10
6.8
5
10
6.8
5
10
6.8
COOLER
Part No.
LL01SB006 LL01SB007 LL01SB009 LL01SB009 LL01SC005 10HA400654 10HA400664
Dry Weight — kg
Fluid Side — kPa
Refrigerant Side — kPa
Net Fluid Volume — L
(includes nozzles)
Fluid Connections — in.
Inlet
31.3
2069
2965
5.3
36.7
2069
2965
6.1
47.6
2069
2965
8.0
47.6
2069
2965
8.0
65.7
2069
2965
12.5
330
1034
1620
49.9
330
1034
1620
57.5
Grooved End
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
11⁄2
21⁄2
21⁄2
3
3
3
3
Outlet
CONDENSER CONNECTIONS
Refrigerant Connections — in.
Liquid Line ODS
7
7
7
7
7
⁄
8
⁄
8
⁄
8
⁄
8
⁄
8
Discharge Line ODS
11⁄8
13⁄8
15⁄8
13⁄8
13⁄8
LEGEND
NOTE: Operating weight includes refrigerant operating charge and weight of
fluid in the heat exchangers.
ODS
—
Outside Diameter, Sweat
*60 Hz/50 Hz units.
†30HWA and HL units (condenserless) are shipped with a refrigerant holding
charge. Approximate cooler operating charge is shown.
**Ckt 1/Ckt 2.
††With transfer switch set to compressor no. 2 position; 40% with transfer switch
set to compressor no. 1 position.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
The number of tubes in the condenser(s) varies depending
on the unit size. The condensers have internal subcoolers which
provide approximately 8 F (4.4 C) for 30HK, HL units or 13 F
(7.2 C) for 30HW units subcooling at ARI (Air Condition-
ing and Refrigeration Institute, U.S.A.) rating conditions.
30HL, HWA SYSTEM CONDENSER — For detailed con-
denser piping installation instructions for 30HL and HWA
systems, refer to separate instructions packaged with the re-
mote condenser unit(s).
Condenser refrigerant piping for 30HL and HWAunits should
be sized to minimize the amount of refrigerant required.
The 30HL and HWA units that use an air-cooled evapo-
rative condenser(s) must have adequate means for head pres-
sure control when operating below 60 F (15.6 C).
Carrier recommends that a field-supplied pressure relief
device be installed after the muffler in each discharge line.
Most local codes require the relief valve to be vented di-
rectly to the outdoors. The vent must not be smaller than the
relief valve outlet.
30HWB CONDENSER DESCRIPTION —All 30HWB units
use a brazed-plate heat-exchanger-type condenser. These heat
exchangers are made of embossed plates of acid-resistant stain-
less steel. Every other plate is reversed so that the ridges of
the herringbone pattern intersect one another on adjacent plates,
forming a lattice of contact points. These plates are vacuum-
brazed together to form a compact and pressure-resistant heat
exchanger.
THUMB-SCREW
BRAKE
Fig. 11 — Factory-Installed Unit Wheels (4)
After brazing, the impressions in the plates form 2 sepa-
rate systems of channels where the refrigerant and water flows
are counter-current. The number of plates varies depending
on unit tonnage. The condensers provide approximately 14°
to 18° F (8° to 10° C) liquid subcooling at the standard
Air Conditioning and Refrigeration Institute (ARI) rating
condition.
30HK, HWC, HWS CONDENSER(S) — When facing the
front of the unit, the condenser(s) is in the uninsulated shell(s)
located across the bottom of the unit. The water connections
are such that the water inlet is located on the left-hand side
(30HK) or right-hand side (30HW) of the unit. The water
inlet must ALWAYS be on the bottom of the condenser(s) to
provide the proper subcooling. The water outlet is located
on the right-hand side (30HK) or left-hand side (30HW) of
the unit. The water connections can be reversed by rotating
the heads and gaskets 180 degrees ON BOTH ENDS OF
THE CONDENSER(S).
Fig. 12 — Compressor Mounting
IMPORTANT: THE WATER INLET MUST AL-
WAYS BE ON THE CONDENSER HEAD(S) THAT
HAS THE NOZZLE CONNECTION AT THE BOT-
TOM OF THE HEAD. Incorrect inlet connection will
result in poor system performance due to incorrect
subcooling.
Step 5 — Make Piping Connections — See
Fig. 13 and 14 for typical piping applications.
30HK, HWC, HWS CONDENSER DESCRIPTION — All
30HWC and HWS units use a shell-and-tube condenser with
removable heads for easy tube servicing. Refrigerant is con-
tained within the shell, and water flows through the tubes.
The 30HK and HWC units use a steel shell condenser(s) with
steel tube sheets and copper tubes. The 30HWS units are
designed for sea coast applications and use a steel shell con-
denser with cupronickel tube sheets and tubes. In addition,
the 30HWS water heads utilize ‘‘sacrificial’’ zinc anodes for
condenser corrosion protection.
The LIQUID-IN and LIQUID-OUT labels indicate water
connections AS SUPPLIED FROM THE FACTORY.
It is recommended that strainer with a minimum of 20 mesh
be installed ahead of the condenser water inlet(s) to prevent
debris from clogging or damaging the heat exchanger(s).
There is a pressure-relief device on the condenser(s) of all
30HK, HWC, and HWS units. Most local codes require that
this relief be vented directly to the outdoors.
NOTE: The relief line must not be smaller than the relief
valve outlet. Be sure to provide a way of draining and ser-
vicing the unit.
IMPORTANT: Inspect the zinc anodes every 3 months
for deterioration and replace as needed. Galvanic pro-
tection of the condenser is lost if the anodes are not
replaced prior to complete deterioration.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
vley
14
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES:
1. Chiller must be installed levelly to maintain proper compres-
sor oil return.
2. Wiring and piping shown are general points-of-connection guides
only and are not intended for a specific installation. Wiring
and piping shown are for a quick overview of system and are
not in accordance with recognized standards.
3. All wiring must comply with applicable local and national codes.
4. All piping must follow standard piping techniques. Refer to
Carrier System Design Manual part 3, Carrier E20-IIா soft-
ware Refrigerant Piping program, or appropriate ASHRAE
(American Society of Heating, Refrigeration, and Air Condi-
tioning Engineers) handbook for details on proper piping sizes
and design.
5. See Table 3 on page 17 for minimum system fluid volume.
This system may require the addition of a holding tank to en-
sure adequate volume.
6. Hot gas lines should rise above refrigerant level in condenser
circuit. Double riser may be required; check compressor mini-
mum capacity.
7. Trap should be installed on hot gas lines to prevent con-
denser oil and refrigerant vapor migration from accumulating
on compressor heads during off cycle.
8. Pitch all horizontal lines downward in the direction of refrig-
erant flow.
9. For piping lengths greater than 50 ft, provide support to liquid
and gas lines near the connections to the condenser coil.
10. For pressure relief requirements, see latest revision of
ASHRAE Standard 15, Safety Code for Mechanical
Refrigeration.
Fig. 14 — Typical Piping with Air-Cooled 30HWA with Remote 09DK Unit Shown
15
Download from Www.Somanuals.com. All Manuals Search And Download.
30HWB CONDENSER — When facing the back of the unit,
the condenser is the uninsulated heat exchanger located on
the right-hand side. The water connections are on the right-
hand side of the heat exchanger with the LIQUID-IN con-
nection at the bottom, and the LIQUID-OUT connection at
the top.
A strainer with a minimum of 20 mesh must be installed
ahead of the condenser water inlet to prevent debris from
clogging or damaging the heat exchanger.
Provide a means for draining the system in the winter (if
not used) and for maintenance.
Accessory steel manifold packages for inlet and outlet con-
denser water are available for 30HK units. Each manifold is
furnished in 2 sections, to be field welded as shown in
Fig. 4. Manifolds should not be used where regulating valves
are required because separate valves must be used on each
condenser circuit.
To install the grooved end coupling (see Fig. 15):
1. Lubricate the gasket lips and stretch the gasket over
the end of the pipe. Avoid twisting the gasket when
installing.
Retighten all condenser head bolts before filling system
with water. Torque bolts to a maximum of 40 to
45 ft-lb.
2. Bring the pipe and heat exchanger coupling ends to-
gether into alignment. Slide the gasket so that it is cen-
tered over the ends. Apply a light film of lubricant to the
gasket, or to the gasket recess of the coupling housing.
Avoid twisting the gasket during installation.
Water leaving the condenser is under pressure and should
not be connected directly into sewer lines. Check local codes.
A 3/8-in. drain plug is located in the head at each condenser
end.
3. Seat the coupling halves over the gasket and install the
nuts and bolts. Tighten the nuts equally on both sides.
4. Alternately tighten the nuts with a wrench to draw
the coupling halves together uniformly. The joint is now
complete.
Refer to Pressure Relief Devices and Discharge Line Check
Valve sections on page 28, concerning piping connections
for these components.
COOLER DESCRIPTION
30HK, HL Units — The cooler is a direct-expansion type
with removable heads and is partitioned for multi-pass re-
frigerant flow. Fluid flow across the tube bundle is directed
by baffles designed for minimum fluid-pressure drop. The
tubes have integral internal fins for maximum heat transfer
efficiency.
Viewed from unit front, the return chilled fluid enters at
the left end of the cooler and leaves at the right end. The
sensing bulb for the factory-supplied fluid temperature con-
troller is in the leaving-fluid nozzle; the leaving-fluid tem-
perature being the control point.
The cooler is insulated with a flexible, closed-cell plastic
foam insulation of suitable thickness. Fluid vapor cannot pen-
etrate the cellular structure to condense either within cells or
on the cooler shell. Thus, the insulation itself is a vapor bar-
rier. Because of the toughness of insulation, a protective sheet
metal covering is not necessary.
Special modification may be necessary for brine chillers.
Contact your Carrier representative for details. For calcium
or sodium chloride brines, it is important that the proper in-
hibitors be carefully selected for protection of the copper tubes.
Refer to the publications of the Calcium Institute or the
Mutual Chemical Division of Allied Chemical Corporation
for information on corrosion control for calcium or sodium
chloride systems.
30HK, HWB, HWC, HWS UNITS — In order to minimize
the water pressure drop in the system, use as few bends as
possible in the field water piping, and run the lines as short
as possible. Size the water lines according to the available
pump pressure (not necessarily the connection size), espe-
cially on cooling tower applications. See Carrier System De-
sign Manual, Part 3, Piping Design. See Fig. 16 for condenser
pressure drops.
Set water regulating valve to maintain design head pres-
sure. Do not adjust to compensate for high head pressures
caused by fouled condenser tubes, excess refrigerant, or
the presence of noncondensables. Due to changes in water
temperature, it may be necessary to adjust the valve season-
ally. After adjusting for design head pressure, shut unit down.
The water regulating valve should shut off the flow of water
in a few minutes. If it does not, raise head pressure setting.
Make sure that the capillary tube from each water regulating
valve is connected to the proper condenser purge valve.
30HW Units — All 30HW units use a brazed-plate heat-
exchanger type cooler. The heat exchanger is constructed es-
sentially the same as the brazed-plate condenser used on
30HWB units. See 30HWB Condenser Description section
on page 13 for more details. Similar to the condenser, the
cooler can only be chemically cleaned.
COOLER PIPING — Plan cooler fluid piping for minimum
number of changes in elevation, and for the fewest number
of bends as possible. Install manual or automatic vent valve
at high points in the line. Maintain system pressure by using
a pressure tank or a combination or relief and reducing valves.
A strainer with a minimum of 20 mesh must be installed
ahead of the cooler fluid inlet to prevent debris from clog-
ging or damaging the heat exchanger.
See Carrier System Design Manual, Part 3, Piping
Design, for chilled fluid piping details.
Fig. 15 — Installed Coupling Fastening Grooved
Pipe Ends
16
Download from Www.Somanuals.com. All Manuals Search And Download.
The cooler fluid inlet and outlet connections are grooved-
end. On 30HW units, the fluid enters at the top connection
and leaves at the bottom connection. Procedures for making
the grooved-end connections are the same as for the 30HWB
condensers. See 30HWB Condenser section on page 16 for
more details.
Table 3 — Minimum Cooler and Condenser Flow
Rates Minimum Loop Volume
MINIMUM COOLER
LOOP VOLUME†
COOLER CONDENSER*
UNIT SIZE
Gal./Min L/s Gal./Min L/s
Gal.
120
148
174
44
L
30HK040
30HK,HL050
30HK,HL060
30HW018
30HW025
30HW028
30HW035
30HW040
56.0
68.0
68.0
22.5
30.0
37.5
45.0
57.0
3.5
4.3
4.3
1.4
1.9
2.4
2.8
3.6
67
4.23
4.79
5.24
1.4
454.2
560.2
658.6
167
Run the pump for 10 minutes, then clean the strainer be-
fore starting the unit.
76
83
A cooler flow switch must be field-installed on all units.
This should be a differential pressure switch that is installed
between the cooler fluid inlet and outlet. The switch should
be set to open when the cooler fluid flow drops below the
values shown in Table 3. Use the cooler water pressure drop
curves (Fig. 16) to determine correct setting for each unit
size. Use Carrier accessory flow switch, part number
30HW900003. See Table 3 for Minimum Flow rates and loop
volumes.
22.5
30.0
37.5
45.0
57.0
1.9
59
223
2.4
76
288
2.8
85
322
3.6
113
428
LEGEND
ARI
N
V
—
—
—
Air Conditioning and Refrigeration Institute
Liters per kW
Gallons per ton
See Step 6 — Make Electrical Connections section on
page 19 for flow switch wiring details.
*30HK, HWB, HWC and HWS only.
†Minimum system fluid volumes.
NOTES:
30HK, HL Units — The thermistor used for sensing fluid
temperature is factory-installed in the cooler leaving fluid
line.
30HW Units — The thermistor used for sensing the fluid
temperature is inside the cooler leaving-water cavity.
Gallons = V x ARI capacity in tons.
Liters = N x ARI capacity in kW.
APPLICATION
V
N
Normal Air Conditioning
Process Type Cooling
Low Ambient Operation
3
3.25
6.5 to 10.8
6.5 to 10.8
6 to 10
6 to 10
COOLER PRESSURE DROP — 30HW UNITS
COOLER PRESSURE DROP — 30HK, HL UNITS
NOTE: Ft of water = 2.31 x change in psig.
Fig. 16 — Cooler and Condenser Water Pressure Drop
17
Download from Www.Somanuals.com. All Manuals Search And Download.
CONDENSER PRESSURE DROP —
30HK UNITS
CONDENSER PRESSURE DROP —
30HWB UNITS
CONDENSER PRESSURE DROP —
30HWC AND 30HWS UNITS
NOTE: Ft of water = 2.31 x change
in psig.
Fig. 16 — Cooler and Condenser Water Pressure Drop (cont)
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Control Box, Controls Section — The control box controls
section contains the following components:
Step 6 — Make Electrical Connections — All field
wiring must comply with local code requirements. Electrical
data for the complete unit and for the compressors is shown
in Tables 4A and 4B. See Fig. 17 and 18 for field wiring
connections. A field-supplied branch circuit disconnect switch
that can be locked in either OPEN or OFF position must be
installed.
• temperature controller
• control relay(s)
• control module(s)
• low-voltage control transformer(s)
• terminal block for ground current sensing accessory
30HK, HL UNITS — On all 60 Hz units, a fused (15 amp
maximum), 115 v control circuit must be supplied by either
a separate power source or by using a minimum 300 va trans-
former. On 208/230 and 460 v units, control circuit power
can be supplied by accessory transformer part no. 07EA900051.
Check to be sure that installation of the 115 v control power
source meets all local codes.
On all 50 Hz units, a fused (15 amp maximum), 230 v
control circuit must be field supplied. On 200-3-50 units, power
for the control circuit can be supplied by connecting a field-
supplied fuse (15 amp maximum) between TB1 and TB2 for
L1 overcurrent protection. On 400-3-50 units, power for the
control circuit can be supplied by connecting a field-
supplied fuse (15 amp maximum) between TB1 and a neu-
tral leg from TB2 for L1 overcurrent protection. On all units,
check to be sure that installation of the 230 v control power
source meets all local codes.
Control Box, Field Control Wiring Section — Inside this
section is a 10-terminal (30HK, HL) or 14-terminal (30HW),
low-voltage, field-wiring terminal strip. All low-voltage field-
wiring connections are made to this terminal block. Seven
3
⁄4-in. (19 mm) knockouts are provided for field wiring in
this section. Connections for chilled fluid flow switch, chilled
fluid pump interlock, condenser pump interlock, remote alarm
output, and ground current sensor accessory are made at this
location. The remote condenser relay connections are made
to a separate 4-terminal (30HK, HL) or 3-terminal (30HW)
field wiring strip. See Fig. 17-20 for specific location of
connections.
Unbalanced 3-Phase Supply Voltage — Never operate a com-
pressor where a phase imbalance in the supply voltage is
greater than 2%. Use the following formula to determine
the percent voltage imbalance:
% Voltage Imbalance =
30HW UNITS — Control circuit power is 24 v and 115 v
on all units, and is supplied by factory-installed control
transformers.
max voltage deviation from average voltage
100 x
average voltage
ALL UNITS — Inside the control box are terminals for field
power and ground (earth) wiring, as well as a terminal for a
neutral wire when needed (380-3-60 and 400-3-50 units only).
A ground wire must be installed with each field power sup-
ply. Compressor are wired standard from the factory for across-
the-line start. As a factory-installed option, all 025-060 sizes
are available wired for part-wind start (special order option
on 30HK, HL unit).
Example: Supply voltage is 240-3-60
AB = 243 v
BC = 236 v
AC = 238 v
Refer to Tables 4A and 4B for electrical data.
243 + 236 + 238
Average Voltage =
Flow Switch — A cooler flow switch is required for all units,
and must be field-installed. The Carrier flow switch acces-
sory (part number 30HW900003), is available for this pur-
pose. Flow switch wiring terminals are located in the field
wiring compartment of the control box. The flow switch should
be wired between terminals TB3-1 and TB3-7 for 30HK, HL
units or between terminals TB2-7 and TB2-13 for 30HW units.
The factory jumper wire between these 2 terminals must be
removed for proper operation of the flow switch.
Control Box, Power Section — The electrical power supply
is brought in through the top left-hand side (30HK, HL) or
right-hand side (30HW) of the control box (see Fig. 19 and
20). The knockout accepts up to a 3-in. (76 mm) conduit for
30HK, HL units, and a 13⁄4- to 21⁄2-in. (44 to 64 mm) conduit
for 30HW units. Pressure-lug connections on the terminal
blocks are suitable for copper, copper-clad aluminum, or alu-
minum conductors.
3
= 239 v
Determine maximum deviation from average voltage:
(AB) 243 - 239 = 4 v
(BC) 239 - 236 = 3 v
(AC) 239 - 238 = 1 v
Maximum deviation is 4 v.
Determine percent voltage imbalance:
4
% Voltage Imbalance = 100 x
239
= 1.7%
This amount of phase imbalance is satisfactory as it is below
the maximum allowable 2%.
The control box power section contains the following
components:
• power terminal block
• compressor circuit breaker(s)
• compressor contactor(s)
IMPORTANT: If the supply voltage phase imbalance
is more than 2%, contact your local utility company
immediately.
• high-voltage transformer (30HW units only)
• control-circuit circuit breaker for 24-v circuit
• unit ON-OFF switch
• unit service light
• ground lug
• neutral terminal (380-3-60 and 400-3-50 units)
• terminal block for ground current sensing accessory
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4A — Electrical Data — 30HK, HWB, HWC, HWS Fluid-Cooled Units
UNIT
Voltage*
Nameplate (3 ph) Hz Min Max
COMPRESSOR (ea)
LRA
XL
UNIT SIZE
30-
Volts
ICF
PW
MTA
XL
Rec
Fuse
MCA
MFA
RLA
XL
PW
PW
208/230
460
575
60 187
60 414
60 518
253
518
632
129
59
54
†
†
†
340
168
122
175
80
70
150
70
60
57
26
24
†
†
†
283
142
98
†
†
†
89
40
42
HK040
HK050
HK060
220
400
50 198
50 342
253
440
142
71
†
†
390
249
200
100
175 75/48**
90 36/26**
†
†
342/201**
223/142**
†
†
116/74**
56/40**
208/230
460
575
60 187
60 414
60 518
253
518
632
161
75
73
†
†
†
503
249
188
225
110
110
200 83/57**
90 39/26**
90 39/24**
†
†
†
446/283**
223/142**
164/ 88**
†
†
†
89/64**
56/40**
54/37**
220
400
50 198
50 342
253
440
169
81
†
†
417
259
225
110
200
100
75
36
†
†
342
223
†
†
116
56
208/230
460
575
60 187
60 414
60 518
253
518
632
187
88
88
†
†
†
529
262
203
250
125
125
225
100
100
83
39
39
†
†
†
446
223
164
†
†
†
64
56
54
220
400
50 198
50 342
253
440
225
131
†
†
600
403
300
175
250
150
100
58
†
†
545
345
†
†
156
90
208/230
380
60 187
60 342
60 414
60 518
253
418
508
632
62
35
28
24
—
—
—
—
266
145
120
96
110
60
80
45
35
30
49
28
23
19
—
—
—
—
266
145
120
96
—
—
—
—
89
40
33
25
460
50
HWB,C,S018
HWB,C,S025
HWB,C,S028
HWB,C,S035
HWB,C,S040
575
40
230
50 198
50 342
253
440
58
34
—
—
200
115
100
60
70
45
46
27
—
—
200
115
—
—
63
41
380/415
208/230
380
460
575
60 187
60 342
60 414
60 518
253
418
508
632
72 170 283
125
70
60
45
90
60
45
35
57
34
27
22
170
85
85
59
283
142
142
98
88
52
40
33
88
52
42
33
43
34
28
85 142
85 142
59
98
230
380/415
50 198
50 342
253
440
67 150 250
38 104 173
110
60
80
45
53
30
150
104
250
173
80
44
80
44
208/230
380
460
575
60 187
60 342
60 414
60 518
253
418
508
632
89 268 446
54 134 223
44 134 223
150
90
70
60
110
70
60
45
71
43
35
28
268
134
134
98
446
223
223
164
104
66
50
41
104
66
52
42
35
98 164
230
380/415
50 198
50 342
253
440
85 205 342
54 134 223
150
90
110
70
68
43
205
134
342
223
98
60
98
60
208/230
380
460
575
60 187
60 342
60 414
60 518
253
418
508
632
102 268 446
59 134 223
48 134 223
175
100
80
125
80
60
50
81
47
38
31
268
134
134
98
446
223
223
164
120
70
52
42
120
70
57
42
39
98 164
60
230
380/415
50 198
50 342
253
440
94 220 366
54 152 253
150
90
125
70
75
43
220
152
366
253
112
66
112
66
208/230
380
460
575
60 187
60 342
60 414
60 518
253
418
508
632
145 414 690
84 207 345
69 207 345
55 165 276
250
150
110
90
175
110
90
116
67
55
44
414
207
207
165
690
345
345
276
180
98
78
63
180
98
84
66
70
230
380/415
50 198
50 342
253
440
135 327 545
78 207 345
225
125
175
100
108
62
327
207
545
345
166
98
166
98
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4B — Electrical Data — 30HL and HWA Condenserless Units
UNIT
COMPRESSOR (ea)
LRA
UNIT SIZE
30-
Volts
Voltage*
Min Max
ICF
MTA
Rec
Fuse
MCA
MFA
RLA
Nameplate (3 ph)
Hz
PW
XL
PW
XL
PW
XL
208/230
460
575
60
60
60
187
414
518
253
518
632
190
84
75
†
†
†
571
282
203
250
125
110
225
100
90
100/65**
44/29**
38/27**
†
†
†
506/315**
253/173**
176/128**
†
†
†
78/50**
68/45**
58/42**
HL050
HL060
200
400
50
50
198
342
253
440
187
99
†
†
449
297
250
125
225
110
83
44
†
†
366
253
†
†
128
68
208/230
460
575
60
60
60
187
414
518
253
518
632
225
99
86
†
†
†
606
297
214
300
125
110
250
110
100
100
44
38
†
†
†
506
253
176
†
†
†
78
68
58
200
400
50
50
198
342
253
440
261
138
†
†
616
406
350
175
300
175
116
61
†
†
545
345
†
†
180
95
208/230
380
60
60
60
60
187
342
414
518
253
418
508
632
72
40
34
28
—
—
—
—
266
145
120
96
125
70
90
50
45
35
57
32
27
22
—
—
—
—
266
145
120
96
—
—
—
—
89
45
41
33
460
60
HWA018
HWA025
HWA028
HWA035
HWA040
575
45
230
50
50
198
342
253
440
58
34
—
—
200
115
100
60
70
45
46
27
—
—
200
115
—
—
63
41
380/415
208/230
380
460
575
60
60
60
60
187
342
414
518
253
418
508
632
79
47
38
30
207
104
104
72
345
173
173
120
125
80
60
50
100
60
45
40
63
37
30
24
207
104
104
72
345
173
173
120
98
52
42
33
98
52
45
37
230
380/415
50
50
198
342
253
440
67
38
150
104
250
173
110
60
80
45
53
30
150
104
250
173
80
44
80
44
208/230
380
460
575
60
60
60
60
187
342
414
518
253
418
508
632
107
60
54
42
268
134
134
98
446
223
223
164
175
100
90
150
80
70
50
85
48
43
33
268
134
134
98
446
223
223
164
124
70
52
42
124
70
60
52
70
230
380/415
50
50
198
342
253
440
85
54
205
134
342
223
150
90
110
70
68
43
205
134
342
223
98
60
98
60
208/230
380
460
575
60
60
60
60
187
342
414
518
253
418
508
632
119
67
304
152
152
106
506
253
253
176
200
110
90
150
80
70
60
95
53
43
35
304
152
152
106
506
253
253
176
144
80
66
50
144
80
66
52
54
44
70
230
380/415
50
50
198
342
253
440
94
54
220
152
366
253
150
90
125
70
75
43
220
152
366
253
112
66
112
66
208/230
380
460
575
60
60
60
60
187
342
414
518
253
418
508
632
167
95
78
63
414
207
207
165
690
345
345
276
300
150
125
110
200
125
100
80
133
76
62
50
414
207
207
165
690
345
345
276
204
106
95
204
106
98
73
76
230
380/415
50
50
198
342
253
440
135
78
327
207
545
345
225
125
175
100
108
62
327
207
545
345
166
98
166
98
LEGEND FOR TABLES 4A AND 4B
ICF
—
Maximum instantaneous current flow during starting. For these
single-compressor units, ICF is the compressor LRA.
Thousand circular mils
PW
—
—
Part wind
Rec Fuse
Recommended dual element fuse amps (150% of
kcmil
LRA
—
—
compressor RLA). Size up to the next standard fuse size.
Rated load amps
Across the line
Locked rotor amps. First value is for part-wind start. Larger value
is the full LRA.
RLA
XL
—
—
MCA
MFA
—
—
Minimum circuit amps (for wire sizing). Complies with NEC,
Section 430-24.
*Supply Range — Units are suitable for use on electrical systems where volt-
age supplied to the unit terminals is not below or above the listed range limits.
†Contact your local Carrier representative for part-wind details.
**Compressor no. 1/Compressor no. 2.
Maximum fuse amps (225% of compressor RLA). Size down to
the next standard fuse size.
MTA
NEC
—
—
Must-trip amps (compressor circuit breaker).
National Electrical Code (U.S.A.)
NOTES FOR TABLES 4A AND 4B
1. All units have one field power terminal block.
7. For all 30HK,HL units, control circuit MCA is 7.2, and control circuit MFA is
15. For 30HK,HL 60 Hz units, a separately-fused (15 amp maximum) 115 v,
single-phase, 60 Hz, power supply or accessory transformer is required.
For 30HK,HL 50 Hz units, a field-supplied, separately fused (15 amps maxi-
mum), 230 v, single-phase, 50 Hz power supply is required.
2. Maximum incoming wire size:
a. 350 kcmil for unit sizes 040-060; 208/230-3-60, 230-3-50, and 400-3-50
voltages.
b. 2/0 for all other unit sizes; all voltages.
3. Any field modification of factory wiring must be in compliance with all ap-
plicable codes. Field-installed power wires must be rated 75 C minimum.
4. Use copper, copper-clad aluminum, or aluminum conductors for field wiring.
5. For all 30HW units, control circuit power supply is 115-v single phase for 50-
and 60-Hz units. Control power is supplied by the factory-installed control
transformer. Additional control circuit power is not required for 30HW units.
6. Across-the-line start is standard on all units. Part-wind start is available as
a factory-installed option on 025-060 sizes (not available on 018 size; spe-
cial order option on 30HK,HL units).
(30HK, HL, HWA, HWB,
HWC 60 Hz Only)
(30HK, HL, HWA, HWB,
HWC 60 Hz Only)
21
Download from Www.Somanuals.com. All Manuals Search And Download.
FIELD POWER WIRING, 60 Hz UNITS
FIELD CONTROL WIRING, 50 Hz UNITS
LEGEND
COM
CR
—
—
—
—
—
—
—
—
—
Common
Compressor Relay
Chilled Water Pump
Demand Limit Switch
Ground Current Sensing
Normally Closed
Normally Open
CWP
DLS
GCS
NC
NO
TB
Terminal Block
Temperature Control
TC
Field Wiring
Factory Wiring
Accessory
NOTE: Manual lead/lag selector switch must
be disconnected when using automatic lead/
lag accessory.
FIELD ACCESSORY WIRING
Fig. 17 — Field Wiring Diagram; 30HK, HL Units
22
Download from Www.Somanuals.com. All Manuals Search And Download.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
C
—
—
—
—
—
Contactor
GCS
GND
NC
NEUT
NO
—
—
—
—
—
Ground Current Sensor
SW
—
—
—
—
—
Switch
CB
CM
COM
CR
Circuit Breaker
Control Module
Common
Ground
TB
Terminal Block
Time Delay Relay
Termistor
Normally Closed
Neutral
Normally Open
TDR
THERM
TRAN
Control Relay
Transformer
Fig. 20 — 30HW Control Box Components Label
2. Be sure flow switch is properly installed and set. See
instructions packaged with flow switch accessory.
3. Set the temperature controller deadband as specified in
Tables 5 and 6. Set point should be at the desired cooler
leaving fluid temperature. Refer to Chilled Fluid Tem-
perature Controller section on page 29 for additional dead-
band setting information.
PRE-START-UP
IMPORTANT: Before beginning Start-Up, complete
Start-Up Checklist on pages CL-1 to CL-4. This check-
list assures proper start-up of a unit, and provides a
record of unit condition, application requirements, sys-
tem information, and operation at initial start-up.
4. Backseat (open) compressor suction and discharge shut-
off valves. Crack open valves (one turn in) to allow some
pressure to each test gage (if installed).
5. Backseat (open) liquid line shutoff valve(s).
6. Open valve to capillaries from fluid regulating valve (when
used).
ELECTRIC SHOCK HAZARD
Open all disconnects before servicing this
equipment. There may be more than one
disconnect.
Initial Check
7. Fill chilled fluid liquid circuit with clean water or other
noncorrosive fluid to be cooled. Bleed all air out of the
high points of the system. Set flow rate according to job
requirements. See Table 3. If the chilled water is to be
maintained at a temperature below 40 F (4.4 C), a brine
of sufficient concentration must be used to prevent freeze-up
at anticipated suction temperatures.
8. Open supply valve (or fill cooling tower, if used) for
condenser water.
9. Check tightness of all electrical connections.
IMPORTANT: Electrical power source must agree
with unit nameplate rating. Do not start the chiller, even
momentarily, until the following checks have been
completed.
1. Check all auxiliary components, such as cooling tower
(if used), chilled liquid and condenser water pumps, air-
handling equipment, or other equipment to which
the chiller supplies liquid. Consult manufacturer’s
instructions.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 5 — Typical Deadband Requirements
If there is no refrigerant vapor pressure in the system, the
entire system must be leak tested. After repairing leaks, evacu-
ate the system before recharging. Follow approved evacu-
ation procedures when removing refrigeration. Release re-
maining pressure to an approved evacuated cylinder.
The liquid charging method is recommended for com-
plete charging or when additional charge is required.
UNIT
CAPACITY
STEPS
COOLER DESIGN RANGE, F (C)
5.0 (2.8)
10.0 (5.6)
15.0 (8.3)
2
3
4
1.3 (0.7)
0.8 (0.4)
0.6 (0.3)
2.5 (1.4)
1.7 (0.9)
1.3 (0.7)
3.8 (2.1)
2.5 (1.4)
1.9 (1.1)
Table 6 — Deadband Setting
Be careful not to overcharge the system. Overcharging
results in higher discharge pressure with higher cooling
water consumption, possible compressor damage, and
higher power consumption.
MIN. REQUIRED DEADBAND
DEADBAND SETTING (F)
F
0.5 to 1.5
2.0
C
0.28 to 0.83
1.11
1.0
2.0
2.5
2.8
3.0
3.7
4.0
2.5
1.39
LIQUID CHARGING METHOD — Add charge to the unit
through the liquid line service valve. Never charge liquid
into the low-pressure side of the system.
3.0
1.67
3.5
1.94
4.0
2.22
1. Frontseat (close) condenser liquid line shutoff valve.
4.5
2.50
2. Connect a refrigerant cylinder loosely to the charging valve
connection of the liquid line shutoff valve. Purge the charg-
ing hose and tighten the connections.
10. Check compressor oil charge (should be visible in
oil sight glass). Refer to Check Oil Charge section on
page 27.
11. Be sure the compressor crankcase heater is warm (heater
should be on for 24 hours before starting the compres-
sor). The crankcase heater must be firmly locked into
the compressor crankcase.
3. Open the charging valve.
4. If the system has been dehydrated and is under vacuum,
break the vacuum with refrigerant gas. For R-22, build
up system pressure to 58 psig and 32 F (400 kPa and
0° C). Invert the refrigerant cylinder so that the liquid
refrigerant will be charged.
12. Be sure the compressor is floating freely on the com-
pressor springs (see Step 4 — Check Compressor Mount-
ing and Connections section on page 3).
13. For 30HL and HWA units with remote condenser, check
the condenser fans for correct rotation. See instructions
shipped with the condenser.
5. a. For complete charge of 30HK, HWB, HWC, and HWS
units, follow charging by weight procedure. When charge
is nearly full, complete the process by observing the
sight glass for clear liquid flow. The use of sight glass
charging is valid only when unit is operating at full
capacity (no unloaders energized).
14. Be sure the unit is fully charged with refrigerant (see
Check Refrigerant Charge section below).
15. If unit is a brine unit, check to ensure proper brine con-
centration is used to prevent freezing.
b. For complete charge of 30HL and HWA units or where
refrigerant cylinder cannot be weighed, follow charg-
ing by sight glass procedure. The use of sight glass
charging is valid only when unit is operating at full
capacity (no unloaders energized).
Check Refrigerant Charge
6. a. The 30HL and HWA condenserless units are shipped
with a holding charge only. After installation with the
field-supplied system high side, the complete system
should be charged until the sight glass is clear (with
the unit running at full capacity). To achieve maxi-
mum system capacity, add additional charge equal to
the difference between the condenser optimal charge
and the condenser minimum charge, which can be ob-
tained from the charge data provided in the condenser
installation instructions.
When adding or removing refrigerant charge, circulate
water through condenser and cooler at all times to pre-
vent freezing. Freezing damage is considered abuse and
is not covered by Carrier warranty.
The 30HK, HWB, HWC, and HWS units are shipped with
a full refrigerant charge (see Tables 1A-2B). However, if it
is necessary to add refrigerant, operate the unit for some time
at full capacity and then add charge until the sight glass is
clear of bubbles. For maximum liquid subcooling, liquid level
should be up to condenser end (30HK, HWC, HWS units
only). This usually requires additional refrigerant charge be-
yond the amount to clear sight glass.
The 30HL and HWA units (condenserless) are shipped with
a refrigerant holding charge only. After chiller assembly is
completed in the field, system must be fully charged. While
the unit is running at full capacity, add refrigerant until the
sight glass is clear. R-22 is the normal refrigerant.
Do not open the liquid valve or the compressor discharge
valve until there is a charge in remainder of system. A posi-
tive pressure indicates a charge in system. With the unit op-
erating at full load, check liquid line sight glass to be sure
the unit is fully charged (bubbles in the sight glass indicate
the unit is not fully charged).
b. To ensure maximum performance of 30HWB units,
raise the compressor saturated discharge temperature
(SDT) to approximately 105 F (40.6 C) by throttling
the condenser water intake. Add charge until there is
approximately 15 to 17° F (8.3 to 9.4° C) of system
subcooling (SDT minus actual temperature entering the
thermostatic expansion valve).
c. To ensure maximum performance of 30HK, HWC, and
HWS units, raise the compressor saturated discharge
temperature (SDT) to approximately 103 F (39.4 C)
by throttling the condenser water intake. Add charge
until there is approximately 8 to 10° F (4.4 to 5.6° C)
for 30HK units or 12 to 14° F (6.7 to 7.8° C) for 30HWC,
HWS units of system subcooling (SDT minus actual
temperature entering the thermostatic expansion valve).
26
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Recheck compressor oil level (see Check Oil Charge sec-
tion on this page). Add or remove oil to achieve the level
required during steady operation.
Check Oil Charge — The compressor(s) is factory-
charged with oil. If oil is visible in the compressor sight
glass(es), check the unit for operating readiness as described
in Initial Check section (page 25), then start the unit. Ob-
serve oil level and add oil, if required, to bring the oil level
Operating Limitations
1
3
in the compressor crankcase(s) to between ⁄8 and ⁄8 of the
sight glass(es) during steady operation.
Do not operate with cooler leaving chiller water (fluid)
temperature (LCWT) below 40 F (4.5 C) for the stan-
dard units, or below 15 F (−9.4 C) for units factory built
for medium temperature brine.
TO ADD OIL
1. Close the suction shutoff valve and pump the compressor
crankcase down to between zero and 2 psig (zero to
13.8 kPa) (the low-pressure switch must be jumpered).
Wait a few minutes and repeat as needed until the pres-
sure remains between zero and 2 psig (zero to 13.8 kPa).
2. Close the discharge shutoff valve.
3. Remove the oil-fill plug above the compressor sight glass,
add oil through the plug hole, and replace the plug.
HIGH COOLER LEAVING CHILLED WATER (FLUID)
TEMPERATURES (LCWT) — During start-up with cooler
LCWT above approximately 60 F (16 C), the unit expansion
valve will limit suction pressure to approximately 90 psig
(620 kPa) to avoid overloading the compressor.
LOW COOLER LCWT — For standard units, the LCWT
must be no lower than 40 F (4.5 C). If the unit is the factory-
installed optional medium temperature brine unit, the cooler
LCWT can go down to 15 F (−9.4 C).
4. After opening the suction and discharge service valves,
remove low-pressure switch jumper, run the compressor
for about 20 minutes, and check the oil level.
Use only Carrier-approved compressor oil:
MAIN POWER SUPPLY — Minimum and maximum ac-
ceptable supply voltages are listed in Tables 4A and 4B.
Petroleum Specialties, Inc. . . . . . . . . . . . . . . . .Cryol 150*
Texaco, Inc. . . . . . . . . . . . . . . . . . . . . . . . . .Capella WF-32
Witco Chemical Co. . . . . . . . . . . . . . . . . . . . . .Suniso 3GS
*Factory charge.
Do not reuse drained oil, and do not use any oil that has
been exposed to the atmosphere.
Unbalanced 3-Phase Supply Voltage — Never operate a mo-
tor where a phase imbalance between phases is greater than
2%. To determine percent voltage imbalance, see Unbal-
anced 3-Phase Supply Voltage section on page 19.
TO REMOVE OIL
Check Refrigerant Feed Components
THERMOSTATIC EXPANSION VALVE (TXV) — The TXV
controls the flow of liquid refrigerant to the cooler by main-
taining constant superheat of vapor leaving the cooler. There
is one valve per refrigerant circuit. The valve(s) is activated
by a temperature-sensing bulb(s) strapped to the suction line(s).
The crankcase will be under slight pressure. Be careful
not to lose the entire oil charge. Gloves and eye pro-
tection must be worn.
The valve(s) is factory-set to maintain between 8° and
10° F (4.4° and 5.6° C) of superheat leaving the cooler. Check
the superheat during operation after conditions have stabi-
lized. If necessary, adjust the superheat to prevent refriger-
ant floodback to the compressor.
Pump down the compressor to between zero and 2 psig
(zero to 13.8 kPa). Loosen the oil drain valve located in the
compressor base to allow the oil to seep out past plug threads.
Be careful not to remove plug; the entire oil charge may be
lost. Small amounts of oil can be removed through oil pump
discharge connection.
FILTER DRIER — The function of the filter drier is to main-
tain a clean, dry system. The moisture indicator (described
below) indicates any need to change the filter drier. The fil-
ter drier is a sealed-type drier. When the drier needs to be
changed, the entire filter drier must be replaced.
START-UP AND OPERATION
Operation Checks — Start-up should be performed only
under supervision of an experienced refrigeration techni-
cian. Refer to Start-Up Checklist on pages CL-1 to CL-4.
Remove and save the checklist for future reference.
1. Crankcase heater must be energized for at least 24 hours
before the chiller is started.
2. Open all system valves that may have been closed during
or after charging.
3. Check air-handling equipment, chilled water (fluid) and
condenser pumps, and any other equipment connected to
the chiller.
NOTE: The 30HK, HL units have 2 filter driers; one per
circuit.
MOISTURE-LIQUID INDICATOR — The indicator is lo-
cated immediately ahead of the TXV to provide an indica-
tion of the refrigerant moisture content. It also provides a
sight glass for refrigerant liquid. Clear flow of liquid refrig-
erant (at full unit loading) indicates sufficient charge in the
system. Bubbles in the sight glass (at full unit loading) in-
dicate an undercharged system or the presence of noncon-
densables. Moisture in the system, measured in parts per million
(ppm), changes the color of the indicator as follows:
Blue (safe) — Moisture is below 45 ppm
Light Violet (caution) — 45 to 180 ppm
Pink (wet) — above 180 ppm
4. Start the unit by moving the ON-OFF switch to the ON
position.
5. Check all controls for proper operation. Follow Start-Up
Checklist procedures in these instructions.
6. Adjust the water regulating valve (where used) to obtain
the most economical head pressure (based on the relative
cost of water and electricity). Head pressure is normally
200 to 230 psig (1379 to 1586 kPa) for 30HK,HL units,
and 195 to 226 psig (1344 to 1558 kPa) for 30HW units
when using R-22 refrigerant.
7. Check the cooler leaving chilled water temperature to see
that it remains well above 32 F (0° C), or the brine freez-
ing point if the unit is a medium temperature brine unit.
The unit must be in operation at least 12 hours before the
moisture indicator gives an accurate reading, and must be in
contact with liquid refrigerant. At the first sign of moisture
in the system, change the corresponding filter drier.
NOTE: The 30HK, HL units have 2 indicators; one per
circuit.
LIQUID LINE SERVICE VALVE — This valve provides a
refrigerant charging port and, in combination with the com-
pressor discharge service valve(s), allows the refrigerant to
be pumped into the high side of the system.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
DISCHARGE LINE CHECK VALVE — On all 30HL, HWA
units, a factory-supplied check valve is shipped with the unit
(two valves are provided for 30HL units). The check valve(s)
should be installed in the discharge line(s) downstream from,
but close to, the compressor muffler. Install the valve in any
position except bonnet down.
The check valve(s) prevents backwards-migration of re-
frigerant from the condenser(s) to the compressor(s) and cooler
during the compressor off cycle.
COMPRESSOR INTERNAL THERMAL PROTECTION —
On the 30HW018 units, there is a sensor imbedded in
the compressor windings to detect an overtemperature
condition.
The thermostat opens and shuts off the compressor if the
discharge gas temperature exceeds 295 ± 5° F (146 ± 2.8° C).
The thermostat will reset when the temperature drops to ap-
proximately 250 F (121 C). However, the control module
will keep the unit locked off until control power is manually
cycled off, then back on.
HOT GAS BYPASS VALVE — On units equipped with the
factory-installed capacity reduction option (30HW only), a
hot gas bypass valve is located between the discharge line
and the cooler entering-refrigerant line. A solenoid valve is
installed in the equalizer line of the hot gas valve to allow
the temperature control to cycle the hot gas bypass function.
The amount of capacity reduction achieved by the hot gas
bypass valve may be altered by adjusting the spring tension
of the hot gas bypass valve. The total unit capacity should
not be reduced below 10% of the nominal rating.
NOTE: Compressor overtemperature protection for 30HK,
HL units is accomplished by high and low pressure switches
and circuit breakers which are external to the compressors.
CRANKCASE HEATER
Never open or disconnect any switch that energizes the
crankcase heater, unless the unit is being serviced or will
be shut down for an extended period. After service or
shutdown, energize the crankcase heater for 24 hours
before starting the compressor.
LIQUID LINE SOLENOID VALVE (30HL ONLY) — The
solenoid valve closes when its circuit is inoperative, either
from capacity control or from any safety trip.
PRESSURE RELIEF DEVICES — All 30HK, 30HL, and
30HW units are equipped with a compressor pressure relief
valve located on the crankcase of the 06E compressor units
(except for the 30HW018 units which have a compressor
displacement less than 50 cfm). The pressure relief valve opens
at 450 psig (3103 kPa).
IMPORTANT: The crankcase heater is located in the
bottom corner of the compressor and held in place by
a bracket. The heater must be tight to prevent it from
backing out of the heater well. The heater eventually
burns out if exposed to the air for an extended period.
The 30HK,HWC, and HWS units are also equipped with
a high-side refrigerant pressure relief valve on the shell and
tube condenser. The valve is set to open at the working pres-
sure of the condenser, as shown in Table 7.
The 30HWB does not have a condenser pressure relief
valve, because the brazed-plate condenser is not considered
a pressure vessel, as defined in ANSI/ASHRAE 15 (Ameri-
can National Standards Institute/American Society of Heat-
ing, Refrigerating, and Air Conditioning Engineers) safety
code requirements.
The heater in each compressor prevents absorption of liq-
uid refrigerant by the compressor oil when the compressor
is not operating. The heater is wired into the normally closed
contacts of the compressor control relay so that it energizes
only when the compressor is not operating. The heater is
125 w, 115 v on all 60 Hz units; 230 v on 50 Hz 30HK, HL
units; and 115 v on 50 Hz 30HW units.
OIL PRESSURE SAFETY SWITCH (OPS) — One OPS per
compressor is standard on all 30HL and HWA units, and on
all units equipped with the medium temperature brine op-
tion. One is located in each compressor terminal box with
capillaries to the crankcase and oil pump. The switch is also
offered as an accessory (part number 30HW900006) for stand-
ard 30HK, HWB, HWC, and HWS units. When used, the
OPS is monitored by the unit control module. If at any time
after the compressor is started, the OPS is open for more
than 2 minutes, the compressor shuts down and is locked off
until control power is manually cycled to OFF, then back to
the ON position. The OPS cuts out at 5 ± 1 psig (34.5 ±
6.9 kPa), and has a maximum cut-in of 9.5 psig (65.5 kPa).
For 30HL and HWA condenserless units, pressure relief
devices designed to relieve at 450 psig (3103 kPa), must be
field-supplied and installed in the discharge line piping after
the muffler in accordance withANSI/ASHRAE 15 safety code
requirements. Additional pressure relief valves, properly se-
lected, must be field-supplied and installed to protect high
side equipment and may be required by applicable codes.
Most codes require that a relief valve be vented directly
to the outdoors. The vent line must not be smaller than the
relief valve outlet. The condenser relief valves have a 5⁄8-in.
SAE (Society of Automotive Engineers, U.S.A.) flare connec-
3
Check Unit Safeties
tion. The compressor relief valves have a ⁄8-in. SAE Flare
connection. Consult ANSI/ASHRAE 15 for detailed infor-
mation concerning layout and sizing of relief vent lines.
All units have a factory-installed fusible plug in the suc-
tion line which relieves on a temperature rise at 170 F
(77 C) and one in the liquid line which relieves at 210 F (99 C).
CONTROL MODULE — The unit control module is lo-
cated in the control section of the control box. See Fig. 19
and 20. It performs several functions. The control module
has a built-in compressor anti-short-cycle timer which will
not allow a compressor to restart until 5 minutes have elapsed
since the previous shutdown.
Table 7 — Pressure Relief Valve Settings
On 30HL and HWA units (and 30HK, HWB, HWC, and
HWS units equipped with the oil pressure safety switch [OPS]
accessory), the compressor oil pressure and low-pressure
switch(es) (LPS) are monitored through the control module.
The unit is allowed to remain operational as long as the OPS
and/or LPS have not been open for more than 2 minutes af-
ter a compressor has started. After start-up, if the OPS and/or
LPS are open for more than 2 minutes, the control module
shuts down the compressor and places the unit in a lockout
condition. The control module activates the fault indication
circuit, and the unit service lamp is illuminated. The unit
cannot be restarted until control power is manually cycled to
OFF, then to ON.
PRESSURE RELIEF VALVE SETTINGS
UNIT
Psig
385
365
335
kPa
2655
2517
2310
30HK
30HWC
30HWS
Compressor and Unit Protective Devices
CIRCUIT BREAKER — There is a single circuit breaker
per compressor in each unit. The circuit breaker(s) protects
the compressor(s) against overloading, locked rotor condi-
tions, and primary single phasing. If the circuit breaker(s)
trips, determine the cause and correct it before resetting the
breaker(s).
28
Download from Www.Somanuals.com. All Manuals Search And Download.
The control module also monitors the high-pressure
switch(es) and compressor internal thermal protection (30HW).
If at any time one or both of these switches opens, the con-
trol module shuts down the compressor and places the unit
in a lockout condition. The control module activates the fault
indication circuit, and the unit service lamp is illuminated.
The unit cannot be restarted until control power is manually
cycled to OFF, then to ON.
If the unit shuts down on an automatic reset switch, such
as the temperature controller, the compressor will be al-
lowed to restart when the switch closes and the control mod-
ule anti-short-cycle time has elapsed.
To check operation of the low-pressure switch, slowly close
the suction service valve and allow the affected compressor
to pump down. The compressor should cut out when the suc-
tion pressure falls below the low-pressure switch cutout set-
ting. Open the suction service valve. The compressor should
restart after the low-pressure switch closes, and the com-
pressor anti-short-cycle delay expires.
CHILLED FLUID TEMPERATURE CONTROLLER — All
units are equipped with a temperature controller (see
Fig. 21) which is capable of controlling up to 4 steps of ca-
pacity. A thermistor installed inside the cooler supplies the
input to the controller. The temperature controller can op-
erate a system with cooling ranges (entering cooler fluid tem-
perature minus leaving cooler fluid temperature) of 5° to
15° F (2.8° to 8.3° C), and with a range of set points from
40 to 60 F (4.4 to 15.5 C) for standard units, and 15 to
39 F (−9.4 to 3.9 C) for units with the medium temperature
brine option.
The set point of the temperature controller should be ad-
justed to the desired leaving cooler fluid temperature, and
verified by using a thermometer placed in the leaving-cooler
piping. The amount of deadband around the set point value
is adjusted through the use of the deadband adjustment knob
on the temperature controller. See Tables 5 and 6 for the cor-
rect setting of the deadband.
The unit should then control the average leaving-fluid tem-
perature to this setting. If the leaving-fluid temperature does
not correspond to the desired set point, slightly readjust the
controller set point knob until the desired leaving-fluid tem-
perature is obtained. The temperature controller has an ad-
justable 30-second (HI position) to 3-minute (LO position)
sample rate knob. The sample rate knob should always be
set at LO position (fully clockwise) for 30HK, HL units, and
at HI position (fully counterclockwise) for 30HW units.
For Servicing Only — To speed up the 5-minute anti-short
cycle, a jumper may be placed between terminals T1 and T6
of the control module.
This jumper must be removed after servicing is complete.
Failure to remove this jumper is considered abusive treat-
ment and will void the Carrier warranty.
HIGH-PRESSURE SWITCH — A high-pressure switch is
provided to protect each compressor and refrigeration sys-
tem from unsafe high pressure conditions. See Table 8 for
high-pressure switch settings.
The high-pressure switch is mounted in the discharge side
of each compressor. A snubber is provided between the com-
pressor discharge manifold and the high-pressure switch to
prevent pressure pulsations from damaging the switch.
If an unsafe, high-pressure condition should exist, the switch
opens and shuts off the affected compressor. The unit control
module prevents the unit from restarting. The unit will not
restart until control power is manually cycled off, then on.
To check operation of the switch, slowly close the com-
pressor discharge shutoff valve until the compressor shuts
down. The switch should open at the pressure corresponding
to the appropriate switch setting as shown in Table 8.
Table 8 — Factory Settings, High-Pressure Switch
(Fixed)
Do not force the knob dials past the stops. This
could cause loss of control point and damage to the
controller.
CUTOUT
Psig kPa
280 ± 10 1931 ± 69 180 ± 20 1241 ± 138
CUT-IN
UNIT
30
Psig
kPa
HK, HWS
HL, HWB, HWC 375 ± 10 2585 ± 69 275 ± 20 1896 ± 138
HWA 395 ± 10 2723 ± 69 298 ± 20 2054 ± 138
Reopen the compressor discharge shutoff valve, and cycle
the unit ON-OFF switch to OFF, then ON. The unit should
restart after the compressor anti-short-cycle delay, built into
the unit control module, expires.
LOW-PRESSURE SWITCH — A low-pressure switch is pro-
vided to protect each compressor and system from a loss of
refrigerant. The low-pressure switch(es) also provides freeze
protection for the cooler. The low-pressure switch(es) is non-
adjustable. See Table 9 for low-pressure switch settings. One
switch is used for standard units, and a different switch is
used for units with the brine option.
Table 9 — Factory Settings, Low-Pressure Switch
(Fixed)
CUTOUT
CUT-IN
kPa
LEGEND
UNIT
TYPE
Psig
kPa
Psig
COM
NC
NO
—
—
—
Common
Normally Closed
Normally Open
STANDARD
BRINE
42 ± 3
27 ± 3
290 ± 21
186 ± 21
57 ± 5
44 ± 5
393 ± 34
303 ± 34
Fig. 21 — Temperature Controller
29
Download from Www.Somanuals.com. All Manuals Search And Download.
If rapid cycling of the capacity steps occurs, the deadband
setting is too low and should be raised to the point that rapid
cycling will cease.
If a cooler design range other than those shown in
Table 5 is desired, determine the setting by using the fol-
lowing formula and Table 6:
phases of the 3-phase power supply to the compressor. If a
short to ground is sensed by the sensor, the compressor au-
tomatically shuts down. This prevents contamination of the
refrigeration system from acid formation. The compressor
shuts down when a 2.5 ± 2 amps ground current is sensed by
a toroid installed around the compressor power leads. The
unit control module locks the compressor off until the circuit
power is cycled to OFF, and then ON. For installation de-
tails, see the instructions included with the accessory
package.
Minimum Required Unit Deadband:
Minimum Deadband
=
(Cooler Design ⌬t
÷
(2 x no. of Capacity Steps)
F (C)
=
NOTE: Two accessory packages are required for 30HK, HL
units.
The lights on the temperature controller will indicate the
status of the control. If the green light labeled ABOVE SET
POINT is illuminated, the controller will add steps of ca-
pacity, if additional steps are available. If the yellow light
labeled BELOW SET POINT is illuminated, the controller
removes steps of capacity.
The temperature controller also has a red light labeled OUT
OF RANGE that indicates the system load was reduced faster
than the controller could remove stages. If this occurs, the
unit shuts down to avoid cooler freeze-up.
UNIT OPERATION
Capacity Control and Operating Sequence —
The 30HW units have a multiple-step temperature control-
ler, factory set to maintain capacity control through leaving
chilled fluid temperature. The controller has 4 capacity steps.
All 30HK, HL units have 4 capacity steps as standard. The
30HW018 and 028-040 units have 3 steps as standard, with
a fourth step available as a factory-installed option. The
30HW025 units have 2 steps of capacity as standard with a
third step available as a factory-installed option. All units
have electric solenoid operated unloaders. See Tables 10 and
11 for capacity control steps of each unit.
Once the temperature rises back into the control band, the
unit restarts automatically. This also occurs if the therm-
istor fails in the open mode. In the case of a thermistor fail-
ure, the unit does not restart until the thermistor is replaced.
At initial start-up, assume that all safety devices are sat-
isfied and there is a call for cooling.
FREEZE-UP PROTECTION
30HK,HL UNITS — Close the compressor circuit breaker
and turn the ON-OFF switch to the ON position.
On medium temperature brine units, the brine must be
properly mixed to prevent freezing at a temperature of
at least 15 F (8.3 C) below the leaving-fluid temperature
set point. Failure to provide the proper brine mixture is
considered abuse and may void the Carrier warranty.
In approximately 5 minutes, the lead compressor starts and
the unloaders are energized (compressor unloads when com-
pressor unloader solenoid is energized). On 30HL units, the
liquid line solenoid valve will remain closed for the first
10 seconds of compressor operation. The low-pressure and
oil pressure switches are bypassed for 2 minutes. At the end
of the 2-minute bypass period, the low-pressure and oil pres-
sure switches are active in the control circuit.
Approximately 30 seconds (high setting) or 3 minutes (low
setting) later, depending on the sample rate setting, the lag
compressor starts and the unloaders are energized (compres-
sor unloads when compressor unloader solenoid is ener-
gized). On 30HL units, the liquid line solenoid valve will
remain closed for the first 10 seconds of compressor opera-
tion. The low-pressure and oil-pressure switches are by-
passed for 2 minutes. At the end of the 2-minute bypass pe-
riod, the low-pressure and oil-pressure switches are active in
the control circuit.
Approximately 30 seconds (high setting) or 3 minutes (low
setting) later, depending on the sample rate setting, the lead
compressor is loaded (unloader solenoids deenergized).
Approximately 30 seconds (high setting) or 3 minutes (low
setting) later, depending on the sample rate setting, the lag
compressor is loaded (unloader solenoids deenergized).
When the load is satisfied and the leaving fluid tempera-
ture falls below the set point, the last stage activated is dropped
immediately. If the leaving fluid temperature still remains
below the set point, then the control drops an additional stage
every 30 (high setting) or 180 (low setting) seconds, de-
pending on the sample rate setting.
All units have the following 2 modes of freeze-up
protection.
1. The temperature controller protects the system from freeze-up
due to rapid loss of load and from low fluid flow by rap-
idly removing all steps of capacity and shutting down the
compressor if an out-of-range condition exists. This nor-
mally occurs if the leaving-fluid temperature drops 6 to
7° F (3.3 to 3.9° C) below the temperature controller set
point. Set point range is 40 to 60 F (4.4 to 15.6 C) for
standard units and 15 to 39 F (−9.4 to 3.9 C) for units
with medium temperature brine option.
2. The low-pressure switch provides a back-up cooler freeze-up
protection system. The low-pressure switch shuts down
the unit when the suction temperature drops to a point
where the cooler will freeze up.
LOSS-OF-COOLER-FLOW PROTECTION — A proof-of-
cooler-flow device (accessory flow switch) must be used with
all 30HK, HL, HW chillers. The device should be a differ-
ential pressure type device and should be set to shut the unit
off if cooler gpm drops below 1.5 times the nominal unit
tonnage. Carrier accessory flow switch, part number
30HW900003 is available for this purpose. See page 19 and
Fig. 17 and 18.
COMPRESSOR GROUND FAULT SENSOR — The ground
fault sensor accessory (Part No. 30HW900004) monitors all
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Once the compressor is shut off, the control system pre-
vents the compressor from restarting within 5 minutes of when
it was last shut down. Once this period has elapsed and the
leaving fluid temperature rises above the set point, the com-
pressor will start within 5 seconds.
If the unit is equipped with field-installed hot gas bypass,
the hot gas bypass valve opens only when stage 1 is active.
If system load drops to the point where the unit is fully
unloaded and the fluid temperature is below the lower dead-
band limit, the compressor shuts off and is not able to restart
until the 5-minute anti-short cycle has expired. If during nor-
mal operation, the fluid temperature rises above the upper
deadband limit, the temperature controller adds a step of ca-
pacity (assuming a step is left to be added).
On condenserless units (30HWA), or on fluid-cooled units
(30HWB,C, and S) equipped with the accessory oil safety
switch, the control module provides a 2-minute bypass of
the oil safety switch.
If the unit is equipped with hot gas bypass option, the hot
gas bypass valve closes before unloaders are deactivated.
If the unit trips out on high pressure, ground current (ac-
cessory), or low oil pressure, the control module locks the
unit off and must be manually reset (by turning the ON-OFF
switch to OFF, then back to ON). If the unit trips out on low
pressure, low fluid temperature, the chilled fluid flow switch,
or the chilled fluid pump switch, it restarts automatically when
the condition is corrected.
If the unit trips out on high pressure, low pressure, ground
current (accessory), or low oil pressure, the control module
locks the unit off and must be manually reset (turn the ON-
OFF switch to OFF and then back to ON). If the unit trips
out on low fluid temperature, chilled fluid flow switch, or
chilled fluid pump switch, it restarts automatically when the
condition is corrected.
30HW UNITS — Close the compressor circuit breaker and
move ON-OFF switch to the ON position. The switch should
light up. In approximately 3 seconds, the compressor starts
unloading. For 2 minutes the low-pressure switch is
bypassed and the unloaders are energized (compressor un-
loads when compressor unloader solenoid is energized). At
end of 2-minute bypass period, the low-pressure switch ac-
tivates the control circuit and the temperature controller regu-
lates the capacity steps based on leaving cooler fluid tem-
perature, set point and deadband settings on the temperature
controller.
Table 10 — Capacity Control Steps — 30HK, HL Standard Units
TRANSFER SWITCH COMPRESSOR
NO. 1 POSITION*
TRANSFER SWITCH COMPRESSOR
NO. 2 POSITION*
CONTROL
STEPS
UNIT
Operating Cylinder
Ckt 1
Operating Cylinder
%
%
Disp.
Disp.
Total
Ckt 2
Total
Ckt 1
Ckt 2
1
2
3
4
25
50
2
4
6
8
2
2
4
4
—
2
25
50
2
4
6
8
—
2
2
2
4
4
30HK040
75
2
75
2
100
4
100
4
1
2
3
4
40
60
4
6
4
4
6
6
—
2
20
60
2
6
—
4
2
2
4
4
30HK,HL050
80
8
2
80
8
4
100
10
4
100
10
6
1
2
3
4
33
66
4
8
10
12
4
4
6
6
—
4
33
66
4
8
10
12
—
4
4
4
6
6
30HK,HL060
88
4
88
4
100
6
100
6
LEGEND
*Manually operated.
NOTE: Circuits are designated from left to right when viewed from
front of unit.
Ckt
Disp.
—
—
Circuit
Displacement
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 11 — Capacity Control Steps —
30HW Standard Units
Brazed-Plate Cooler and Condenser Heat Ex-
changer Replacement — Brazed-plate heat exchang-
ers cannot be repaired if they develop a leak. If a leak (re-
frigerant or water) develops, the heat exchanger must be
replaced. To replace a brazed plate heat exchanger:
1. Disconnect the liquid-in and liquid-out connections at the
heat exchanger.
2. Check that the replacement heat exchanger is the same as
the original heat exchanger. For the condensers, compare
part numbers on the heat exchangers. For the coolers, in-
sulation covers the manufacturer’s part number. Make sure
the depths of the replacement and original cooler heat ex-
changers are the same.
UNIT
CAPACITY CONTROL
STEPS*
CAPACITY
%
OPERATING
CYLINDERS
30HW
1
2
3
33.3
66.7
100.0
2
4
6
018
025
028
1
2
50.0
100.0
2
4
1
2
3
33.3
66.7
100.0
2
4
6
1
2
3
33.3
66.7
100.0
2
4
6
035
040
3. Reclaim the refrigerant from the system, and unsolder the
refrigerant-in and refrigerant-out connections.
1
2
3
33.3
66.7
100.0
2
4
6
1
4. Remove the four ⁄2-in. nuts holding the heat exchanger
to the brackets. Save the nuts.
*Factory-installed hot gas bypass option adds an additional capacity
step to that shown in this table.
5. Install the replacement heat exchanger in the unit and
1
attach to the bracket using the four ⁄2-in. nuts removed
in Step 4.
6. Carefully braze the refrigerant lines to the connections on
the heat exchanger. Lines should be soldered using silver
as the soldering material with a minimum of 45% silver.
Keep the temperature below 1472 F (800 C) under nor-
mal soldering conditions (no vacuum) to prevent the cop-
per solder of the brazed plate heat exchanger from changing
its structure. Failure to do so can result in internal or
external leakage at the connections which cannot be
repaired.
SERVICE
ELECTRIC SHOCK HAZARD
To avoid the possibility of electrical shock,
turn off all power to unit before servicing.
7. Reconnect the water/brine lines.
8. Dehydrate and recharge the unit. Check for leaks.
Do not attempt to bypass, short-out, or modify the con-
trol circuit or electronic boards in any way to correct a
problem. This could result in component failures or a
hazardous operating condition.
Brazed-Plate Cooler and Condenser Heat Ex-
changer Cleaning — Brazed-plate heat exchangers must
be cleaned chemically. A professional cleaning service skilled
in chemical cleaning should be used. Use a weak acid (5%
phosphoric acid, or if the heat exchanger is cleaned fre-
quently, 5% oxalic acid). Pump the cleaning solution through
the exchanger, preferably in a backflush mode. After clean-
ing, rinse with large amounts of fresh water to dispose of all
the acid. Cleaning materials must be disposed of properly.
Compressor Replacement — If a replacement
6-cylinder compressor has a center-bank cylinder head with
discharge valve pad facing the pump end, remove head and
install reverse flange head from original compressor (dis-
charge valve pad toward the motor end). Center-bank cyl-
inder head cannot be rotated 180 degrees.
Be sure all the hardware from the old compressor is
removed and installed on the new compressor, including
the high-pressure switch snubber, the discharge gas thermo-
stat (30HW025-040), the oil pressure safety switch (if equipped),
and the low-pressure switch.
The compressor can be removed from either the front or
the sides of the unit, depending on where clearance space
was allowed during unit installation. The compressor and mount-
ing hardware are mounted on a plate which is screwed down
to the unit basepan. Remove the 4 screws holding the plate
to the basepan and the plate should easily slide out of the
unit. Mount the replacement compressor to the plate, slide
the plate back into the unit and secure with the 4 screws.
The mesh screens in front of the water/brine inlets of the
heat exchangers should be cleaned periodically, depending
on condition of the chiller water/brine.
Shell-and-Tube Condenser Cleaning — The shell-
and-tube condenser tubes can be cleaned either mechani-
cally or chemically. To clean them chemically, follow the
procedure described in Brazed-Plate Cooler and Condenser
Heat Exchanger Cleaning section above.
To clean the condenser tubes manually:
1. Order tubing brushes (Carrier part no. KC21AH105).
2. Close the valves on the condenser and relieve condenser
water pressure. BE SURE TO PROVIDE DRAINAGE
TO PREVENT WATER DAMAGE.
Circuit Breaker(s) — The breaker(s) provides 3-leg over-
load protection. Do not bypass connections or increase the
size of the circuit breaker(s) to correct trouble. Determine
the cause of the trouble and correct it before resetting the
breaker(s). A tripped breaker must be manually reset by mov-
ing the circuit breaker handle to OFF, then ON position. See
Tables 4A and 4B for must-trip amps (MTA).
3. Remove the condenser heads and brush the tubes clean,
removing scale and other deposits.
4. Inspect the head gaskets and replace if necessary.
5. Clean all gasket surfaces prior to reassembly.
6. Replace the water heads and torque the head bolts to
90 ft-lb (122 N-m). Allow the gaskets to set overnight
and re-torque the bolts to ensure proper sealing.
NOTE: One circuit breaker is provided per compressor.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Insert thermistor T1 into coupling body to its full depth.
Tighten packing nut finger tight to position ferrules, then
tighten 11⁄4 turns more using a back-up wrench. Ferrules
are not attached to the sensor, which can be withdrawn
from coupling for service.
Thermistor — The resistance at various temperatures for
the thermistor are given in Tables 12A and 12B.
THERMISTOR REPLACEMENT, 30HK, HL UNITS
THERMISTOR REPLACEMENT, 30HW UNITS — To re-
place the thermistor, follow these steps:
1. Disconnect the existing thermistor from the S1 and S2
terminals of the temperature controller (located in the con-
trol section of the control box).
2. Remove the thermistor from the well in the cooler leaving-
fluid cacity.
3. Insert the replacement thermistor into the thermistor well.
Thermistors are installed directly in fluid circuit. Drain
fluid before removing.
Proceed as follows (see Fig. 22):
1. Remove and discard original thermistor and coupling.
IMPORTANT: Do not diassemble new coupling. In-
stall as received.
4. Run thermistor wires into the control box and connect to
the S1 and S2 terminals of the temperature controller.
2. Apply pipe sealant to 1⁄4-in. NPT threads on replacement
coupling and install in place of original. Do not use a pack-
ing nut to tighten coupling. This damages the ferrules (see
Fig. 22).
Fig. 22 — Thermistor
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 12A — Sensor Temperature (F) vs Resistance
TEMPERATURE
(F)
RESISTANCE
(OHMS)
TEMPERATURE
(F)
RESISTANCE
(OHMS)
TEMPERATURE
(F)
RESISTANCE
(OHMS)
- 25
- 24
- 23
- 22
- 21
- 20
- 19
- 18
- 17
- 16
- 15
- 14
- 13
- 12
- 11
- 10
98,010
94,707
91,522
88,449
85,485
82,627
79,871
77,212
74,648
72,175
69,790
67,490
65,272
63,133
61,070
59,081
57,162
55,311
53,526
51,804
50,143
48,541
46,996
45,505
44,066
42,678
41,339
40,047
38,800
37,596
36,435
35,313
34,231
33,185
32,176
31,201
30,260
29,351
28,472
27,624
26,804
26,011
25,245
24,505
23,789
23,096
22,427
21,779
21,153
20,547
19,960
19,392
18,843
18,311
17,796
17,297
16,814
16,346
15,892
15,453
15,027
14,614
14,214
13,826
13,449
13,084
12,730
12,387
12,053
11,730
11,416
11,111
10,816
10,529
10,250
9,979
63
64
7,091
6,911
6,735
6,564
6,399
6,237
6,081
5,929
5,781
5,637
5,497
5,361
5,229
5,101
4,976
4,855
4,737
4,622
4,511
4,403
4,298
4,195
4,096
4,000
3,906
3,814
3,726
3,640
3,556
3,474
3,395
3,318
3,243
3,170
3,099
3,031
2,964
2,898
2,835
2,773
2,713
2,655
2,598
2,542
2,488
2,436
2,385
2,335
2,286
2,238
2,192
2,147
2,103
2,060
2,018
1,977
1,937
1,898
1,860
1,822
1,786
1,750
1,715
1,680
1,647
1,614
1,582
1,550
1,519
1,489
1,459
1,430
1,401
1,373
1,345
1,318
1,291
1,265
1,239
1,214
1,189
1,165
1,141
1,118
1,095
1,072
1,050
1,028
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
1,007
986
965
945
925
906
887
868
850
832
815
798
782
765
749
734
719
705
690
677
663
650
638
626
614
602
591
581
570
560
551
542
533
524
516
508
501
494
487
480
473
467
461
456
450
444
439
434
429
424
419
415
410
405
401
396
391
386
382
377
372
366
361
356
350
344
338
332
325
318
311
304
297
289
282
65
66
67
68
69
70
71
72
73
74
75
76
77
78
-
-
-
-
-
-
-
-
-
9
8
79
80
7
81
6
82
5
83
4
84
3
85
2
86
1
87
0
88
1
89
2
90
3
91
4
92
5
93
6
94
7
95
8
96
9
97
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
9,717
9,461
9,213
8,973
8,739
8,511
8,291
8,076
7,868
7,665
7,468
7,277
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 12B — Sensor Temperature (C) vs Resistance
TEMPERATURE
(C)
RESISTANCE
(OHMS)
TEMPERATURE
(C)
RESISTANCE
(OHMS)
TEMPERATURE
(C)
RESISTANCE
(OHMS)
-32.0
-31.5
-31.0
-30.5
-30.0
-29.5
-29.0
-28.5
-28.0
-27.5
-27.0
-26.5
-26.0
-25.5
-25.0
-24.5
-24.0
-23.5
-23.0
-22.5
-22.0
-21.5
-21.0
-20.5
-20.0
-19.5
-19.0
-18.5
-18.0
-17.5
-17.0
-16.5
-16.0
-15.5
-15.0
-14.5
-14.0
-13.5
-13.0
-12.5
-12.0
-11.5
-11.0
-10.5
-10.0
- 9.5
- 9.0
- 8.5
- 8.0
- 7.5
- 7.0
- 6.5
- 6.0
- 5.5
- 5.0
- 4.5
- 4.0
- 3.5
- 3.0
- 2.5
- 2.0
- 1.5
- 1.0
- 0.5
0.0
100 049
97 006
94 061
91 209
88 449
85 777
83 191
80 687
78 264
75 918
73 648
71 451
69 324
67 265
65 272
63 344
61 477
59 670
57 921
56 228
54 589
53 003
51 467
49 980
48 541
47 148
45 799
44 492
43 228
42 003
40 817
39 668
38 556
37 478
36 435
35 424
34 444
33 495
32 576
31 685
30 821
29 984
29 173
28 386
27 624
26 884
26 168
25 472
24 798
24 144
23 509
22 893
22 296
21 716
21 153
20 606
20 076
19 561
19 061
18 575
18 103
17 645
17 199
16 766
16 346
15 937
15 539
15 153
14 777
14 412
14 057
13 711
13 375
13 048
12 730
12 420
12 119
11 826
11 541
11 263
10 992
10 729
10 472
10 223
9 979
16.0
16.5
17.0
17.5
18.0
18.5
19.0
19.5
20.0
20.5
21.0
21.5
22.0
22.5
23.0
23.5
24.0
24.5
25.0
25.5
26.0
26.5
27.0
27.5
28.0
28.5
29.0
29.5
30.0
30.5
31.0
31.5
32.0
32.5
33.0
33.5
34.0
34.5
35.0
35.5
36.0
36.5
37.0
37.5
38.0
38.5
39.0
39.5
40.0
40.5
41.0
41.5
42.0
42.5
43.0
43.5
44.0
44.5
45.0
45.5
46.0
46.5
47.0
47.5
48.0
48.5
49.0
49.5
50.0
50.5
51.0
51.5
52.0
52.5
53.0
53.5
54.0
54.5
55.0
55.5
56.0
56.5
57.0
57.5
58.0
58.5
59.0
59.5
60.0
60.5
61.0
61.5
62.0
62.5
63.0
63.5
7507
7334
7165
7000
6840
6683
6531
6382
6237
6096
5959
5825
5694
5566
5442
5321
5203
5088
4976
4867
4760
4656
4555
4457
4360
4267
4175
4086
4000
3915
3832
3752
3674
3597
3523
3450
3379
3310
3243
3177
3113
3051
2990
2931
2873
2816
2761
2707
2655
2603
2553
2504
2457
2410
2364
2320
2276
2234
2192
2152
2112
2073
2035
1997
1961
1925
1890
1856
1822
1789
1757
1725
1694
1663
1634
1604
1575
1547
1519
1492
1465
1438
1412
1387
1362
1337
1313
1289
1265
1242
1219
1197
1175
1153
1132
1111
64.0
64.5
65.0
65.5
66.0
66.5
67.0
67.5
68.0
68.5
69.0
69.5
70.0
70.5
71.0
71.5
72.0
72.5
73.0
73.5
74.0
74.5
75.0
75.5
76.0
76.5
77.0
77.5
78.0
78.5
79.0
79.5
80.0
80.5
81.0
81.5
82.0
82.5
83.0
83.5
84.0
84.5
85.0
85.5
86.0
86.5
87.0
87.5
88.0
88.5
89.0
89.5
90.0
90.5
91.0
91.5
92.0
92.5
93.0
93.5
94.0
94.5
95.0
95.5
96.0
96.5
97.0
97.5
98.0
98.5
99.0
99.5
100.0
100.5
101.0
101.5
102.0
102.5
103.0
103.5
104.0
104.5
105.0
105.5
106.0
106.5
107.0
1090
1070
1050
1030
1011
992
973
955
937
919
902
885
868
852
836
820
805
790
775
761
746
733
719
706
693
681
669
657
645
634
623
613
602
592
583
573
564
556
547
539
531
524
516
509
502
496
489
483
477
472
466
461
456
451
446
441
436
432
427
423
419
415
410
406
402
398
393
389
385
380
376
371
367
362
357
352
346
341
335
330
324
318
312
305
299
292
285
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
10.5
11.0
11.5
12.0
12.5
13.0
13.5
14.0
14.5
15.0
15.5
9 742
9 512
9 287
9 068
8 855
8 647
8 444
8 247
8 055
7 868
7 685
35
Download from Www.Somanuals.com. All Manuals Search And Download.
The following Elliott Co. tube rolling tools are required:
SERVICING COOLER (30HK,HL ONLY)
NOTE: The cooler on 30HW units is not serviceable.
When cooler heads and partition plates are removed, tube
sheets are exposed showing tube ends as shown in Fig. 23.
B3400 Expander Assembly
B3401 Cage
B3405 Mandrel
B3408 Rolls
Place one drop of Loctite No. 675 sealant (or equivalent)
on top of the tube prior to rolling.
Tube information:
Four tubes in the bundle are secured inside cooler at baffles
and cannot be removed. These are identified on the tube
sheets by a drill mark horizontally adjacent to each of
the 4 tubes. See Fig. 23. If leakage occurs in any of these
tubes, plug as described in Tube Plugging section
below.
in.
mm
• Tube sheet hole diameter . . . . . . . . . . . . 0.631 16.03
• Tube OD . . . . . . . . . . . . . . . . . . . . . . 0.625 15.87
• Tube ID after rolling . . . . . . . . . . . . . . 0.581 14.76
(includes expansion due
to clearance)
to
to
Tube Plugging — Leaky tube(s) can be plugged until
retubing can be done. The number of plugged tubes deter-
mines how soon the cooler must be retubed. If several tubes
require plugging, check with your local Carrier representa-
tive to find out how number and location will affect unit
capacity.
0.588 14.94
IMPORTANT: Tubes next to gasket webs must be flush
with tube sheet (both ends).
Figure 24 shows an Elliott tube plug and a cross-sectional
view of a plug in place. Table 13 lists the components for
plugging.
Tightening Cooler Head Bolts
GASKET PREPARATION — When reassembling, use
new gaskets. Compressed non-asbestos/neoprene gaskets
(Carrier Material Specification ZA00-32) are to be momen-
tarily dipped in compressor break-in oil prior to assembly.
Do not soak gaskets in oil, as gasket deterioration results.
Use dipped gaskets within 30 minutes to prevent deteriora-
tion.
Use extreme care when installing plugs to prevent dam-
aging the tube sheet sections between holes.
Clean parts with Locquic ‘‘N’’solution (or equivalent) and
apply a few drops of Loctite No. 675 sealant (or equivalent)
to obtain a tight seal without using too much force to set the
pin.
Usually plugs can be removed by heating the projecting
end of pin to approximately 1000 F (538 C) and chilling quickly
with water. Apply heating flame to side of the pin to prevent
overheating tube sheet.
BOLT TORQUES — Apply the following torques during bolt
tightening sequence described below:
5
⁄
8-in. 16-mm) diameter flange
bolts . . . . . . . . . . . . . 150 to 170 ft-lb (203 to 230 N-m)
1
⁄2-in. (13-mm) diameter center-stud
nuts . . . . . . . . . . . . . . . . 70 to 90 ft-lb (95 to 122 N-m)
Bolt Tightening Sequence (Fig. 25) — The recommended
RETUBING (See Table 13) — When retubing is to be done,
obtain the service of qualified personnel experienced in boiler
maintenance and repair. Most standard procedures can be fol-
lowed when retubing the 10HA coolers. A 6% crush is rec-
ommended when rolling replacement tubes into the tube sheet.
A 6% crush can be achieved by setting the torque on the gun
at 48 to 50 in.-lb (780 to 815 N-m).
bolt tightening sequence is:
5
Step 1 — Tighten all
⁄8-in. (16-mm) flange bolts and
1
⁄
2-in. (13-mm) center nuts finger tight.
Step 2 — Following sequence shown in Fig. 25, tighten the
bolts and nuts to approximately 50% of specified torque.
Step 3 — Starting at top (12 o’clock) tighten flange bolts to
specified torque (see Bolt Torques section on this page) con-
secutively in a clockwise direction.
Step 4 — Tighten center nuts to specified torque.
Step 5 — No less than one hour later, retighten center nuts.
Step 6 — After refrigerant is restored to cooler, check center
studs and exposed gasket edges for refrigerant leaks with
soap solution or a Halide device.
*
*
*
Table 13 — Plugs and Tubes
COMPONENTS FOR
PART NUMBER
PLUGGING
For Tubes
Brass Pin
Brass Ring
For Holes without Tubes
Brass Pin
853103-500*
853002-570*
*
853103-1*
853002-631*
No. 675†
‘‘N’’†
Brass Ring
Loctite
Locquic
*Order directly from Elliott Tube Co., Dayton, Ohio.
†Can be obtained locally.
*Four fixed tubes (cannot be removed) identified by adjacent drill points.
Fig. 23 — Typical Tube Sheet
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 24 — Elliott Tube Plug
after completion of the 5-minute timer cycle unless the re-
frigerant charge is either very low or lost. If this is the case,
determine the cause of the loss of charge, correct the prob-
lem, and recharge the unit before restarting.
TEMPERATURE CONTROLLER SHUTS UNIT DOWN
ON OUT-OF-RANGE (See Fig. 21) — Check the ther-
mistor for an open circuit failure. See Tables 12A and 12B
for temperature-resistance values. If thermistor is damaged,
replace it. If thermistor is not damaged, the unit restarts
automatically after completion of the 5-minute timer cycle,
and after the leaving cooler chilled fluid temperature
rises above the upper deadband limit of the temperature
controller.
OPEN HIGH-PRESSURE SWITCH(ES) — The unit ser-
vice light is illuminated. Determine and correct the cause of
the failure. The switch(es) automatically resets but the unit
must be manually reset by cycling the control power (move
ON-OFF switch to OFF, then back to ON). The unit restarts
after completion of 5-minute timer cycle.
HEAD BOLT TIGHTENING SEQUENCE
Fig. 25 — Typical Tube Sheet
OPEN COMPRESSOR INTERNAL THERMAL PROTEC-
TION (30HW UNITS) — This is compressor overtempera-
ture protector on 30HW018 units and the discharge gas ther-
mostat (DGT) on 30HW025-040 units. The unit service light
is illuminated. Determine and correct cause of problem. The
switch resets automatically but unit must be reset by cycling
the control power (move ON-OFF switch to OFF, then back
to ON). The unit restarts after completion of 5-minute timer
cycle.
TROUBLESHOOTING
Complete Unit Stoppage and Restart — Pos-
sible causes for unit stoppage and reset methods are (also
see Table 14):
GENERAL POWER FAILURE — After power is restored,
restart is automatic through the normal timer cycle.
OPEN OIL PRESSURE SWITCH — If oil pressure switch(es)
opens for more than 2 minutes during unit operation, the unit
shuts down and is locked off. The unit service light is illu-
minated. Determine and correct cause of failure. Unit must
be reset by cycling the control power (move ON-OFF switch
to OFF, then back to ON). Unit restarts after completion of
5-minute timer cycle.
UNIT ON-OFF SWITCH IS OPEN — When the switch is
opened, the unit stops immediately. If the switch is closed
immediately after it was opened, the unit restarts automati-
cally after the 5-minute timer cycle is completed. If the switch
is closed after an extended off-period, the unit restarts au-
tomatically in approximately 3 seconds.
CONTACTS OF ANY AUXILIARY INTERLOCKS ARE
OPEN — After the problem has been corrected, restart is
automatic after completion of the 5-minute timer cycle.
OPEN CONTACTS ON COMPRESSOR GROUND-
CURRENT SENSOR(S) (Accessory) — The light-emitting
diode (LED) on the ground current accessory board (located
in field control wiring section of control box) is illuminated.
See Fig. 17-20. Unit service light is also illuminated. Check
the compressor motor windings for a short to ground.
Determine and correct cause of the failure. The unit must be
reset by cycling the control power (move ON-OFF switch to
OFF, then back to ON). Unit restarts after completion of the
5-minute timer cycle.
CHILLED FLUID PROOF-OF-FLOW SWITCH(ES) OPEN
— After the problem causing the loss of flow has been cor-
rected, restart is automatic after completion of the 5-minute
timer cycle.
OPEN LOW-PRESSURE SWITCH — If a low-pressure switch
remains open for more than 2 minutes during unit operation,
the compressor(s) shuts down and is locked off. The unit ser-
vice light is illuminated. Determine and correct the cause of
the failure. The switch automatically resets, but the unit must
be manually reset by cycling the unit control power (move
the ON-OFF switch to OFF, then to ON). The unit restarts
OPEN 24-V CONTROL CIRCUIT BREAKER(S) — De-
termine the cause of the failure and correct. Reset circuit
breaker(s). Restart is automatic after completion of 5-minute
timer cycle.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING LOAD SATISFIED — Unit shuts down if cool-
ing load is satisfied. Unit restarts if required after comple-
tion of 5-minute timer cycle.
NOTE: If the thermistor fails in closed mode, the tempera-
ture controller keeps trying to load up.
THERMISTOR FAILURE — If thermistor fails in open mode,
the temperature controller shuts down the unit in an out-of-
range condition. Replace the thermistor. Unit restarts auto-
matically after completion of a 5-minute timer cycle, and
when the leaving cooler chilled fluid temperature rises above
the upper deadband limit of the temperature controller.
If unit stoppage occurs more than once as a result of
any of the safety devices listed, determine and correct
cause before attempting another restart.
Table 14 — Troubleshooting
SYMPTOMS
CAUSE
REMEDY
Compressor does
not run
Power line open
Reset circuit breaker.
Control fuse or circuit breaker opens
Check control circuit for ground or short. Reset breaker
and replace fuse.
Compressor overtemperature sensor open
Tripped power breaker
Find cause of high temperature and reset controls.
Check the controls. Find the cause of trip and
reset breaker.
Condenser circulating pump not running
Power off — restart.
Pump binding — free pump.
Incorrect wiring — rewire.
Pump motor burned out — replace.
Check connections.
Loose terminal connection
Improperly wired controls
Low line voltage
Check wiring and rewire if necessary.
Check line voltage — determine location of voltage drop
and remedy deficiency.
Compressor motor defective
Check motor winding for open or short. Replace
compressor if necessary.
Seized compressor
Replace compressor.
Compressor cycles
off on loss of
charge
Loss of charge control erratic in action
Repair leak and recharge.
Replace control.
Low refrigerant charge
Add refrigerant.
Low suction temperature
Raise cooler leaving fluid temperature set point.
Replace valve plate.
Compressor suction valve leaking
Plugged compressor suction strainer
Clean or replace strainer.
Compressor suction shutoff valve partially closed Open valve.
Compressor cycles
off on out of range
condition
Thermistor failure
Replace thermistor.
System load was reduced faster than
controller could remove stages
Unit will restart after fluid temperature rises back into the
control band. Avoid rapidly removing system load.
Compressor cycles control Temperature controller deadband setting is
Raise deadband setting.
steps rapidly
too low
Compressor shuts
down on high-
pressure control
High-pressure control acting erratically
Compressor discharge valve partially closed
Air in system
Replace control.
Open valve or replace (if defective).
Purge system.
Condenser scaled/dirty
Clean condenser.
Receiver not properly vented — refrigerant
backs up into evaporator condenser
Repipe as required to provide adequate venting.
Condenser water pump or fans not operating
System overcharged with refrigerant
Low refrigerant charge
Start pump — repair or replace if defective.
Reduce charge.
Unit operates too long
or continuously
Add refrigerant.
Control contacts fused
Replace control.
Air in system
Purge system.
Partially plugged or plugged expansion valve
or filter drier
Clean or replace as needed.
Defective insulation
Service load
Replace or repair as needed.
Keep doors and windows closed.
Check valves, and replace if necessary.
Support piping as required.
Inefficient compressor
Piping vibration
Unusual or loud system
noises
Check for loose pipe connections.
Add refrigerant.
Expansion valve hissing
Compressor noisy
Check for plugged liquid line filter drier.
Check valve plates for valve noise.
Replace compressor (worn bearings).
Check for loose compressor holddown bolts.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 14 — Troubleshooting (cont)
SYMPTOMS
CAUSE
REMEDY
Compressor
loses oil
Leak in system
Repair leak.
Mechanical damage (blown piston or broken
discharge valve)
Repair damage or replace compressor as needed.
Oil trapped in line
Check piping for oil traps.
Crankcase heater not energized
during shutdown
Check wiring and crankcase heater contacts on the
temperature controller, and replace heater if necessary.
Hot liquid line
Shortage of refrigerant due to leak
Shutoff valve partially closed or restricted
Restricted filter drier
Repair leak and recharge.
Open valve or remove restriction.
Replace filter drier.
Frosted liquid line
Frosted suction line
Expansion valve admitting excess refrigerant
Burned-out coil
Adjust expansion valve. Replace valve if defective.
Replace coil.
Compressor will
not unload
Defective capacity control valve
Miswired solenoid
Replace valve.
Rewire correctly.
Weak, broken, or wrong valve body spring
Miswired solenoid
Replace spring.
Compressor will
not load
Rewire correctly.
Defective capacity control valve
Plugged strainer (high side)
Stuck or damaged unloader piston or piston ring(s)
Piping vibration
Replace valve.
Clean or replace strainer.
Clean or replace the necessary parts.
Support piping as required.
Check for loose pipe connectors.
Add refrigerant.
System noises
Expansion valve hissing
Compressor noisy
Check for plugged liquid line strainer.
Check valve plates for valve noise.
Replace compressor (worn bearings).
Check for loose compressor holddown bolts.
Freeze-up
Improper charging
Make sure a full quantity of fluid is flowing through the
cooler while charging, and suction pressure in cooler is
equal to or greater than pressure corresponding to 32 F
(0° C) (58 psig [400 kPa] for Refrigerant 22).
Improperly set safety thermostat
Check safety thermostat for proper setting at beginning of
each season.
Operating with safety thermostat bypassed
Improper circulation of condenser water
If thermostat was bypassed for checking, be sure it is back
in circuit before starting unit.
Use adequately sized cleanable strainer in the condenser
water circuit. Make sure strainer is clean. It may sometimes
be necessary to chemically treat the water to prevent for-
mation of deposits.
System not drained for winter shutdown
Loose Thermistor
Remove drain plugs at end of cooling season. Blow out any
residual water. Instead of draining, a suitable anti-freeze
may be added to the water. Damage to chiller due to freez-
ing is considered abuse and is not covered by warranty.
Tighten thermistor to pipe and reinsulate (30HW).
39
Download from Www.Somanuals.com. All Manuals Search And Download.
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your knowledge of the equip-
ment discussed in this manual, including:
• Unit Familiarization
• Installation Overview
• Maintenance
• Operating Sequence
A large selection of product, theory, and skills programs are available, using popular video-based for-
mats and materials. All include video and/or slides, plus companion book.
Classroom Service Training which includes ‘‘hands-on’’ experience with the products in our labs can
mean increased confidence that really pays dividends in faster troubleshooting and fewer callbacks.
Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-962-9212
[
] Packaged Service Training
[
] Classroom Service Training
Copyright 1998 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
PC 903
Catalog No. 533-070
Printed in U.S.A.
Form 30H-10SI
Pg 40
11-98
Replaces: 30H-8SI
Tab 5c
Download from Www.Somanuals.com. All Manuals Search And Download.
START-UP CHECKLIST FOR CHILLER SYSTEMS
(Remove and use for job file)
A. Preliminary Information
JOB NAME
LOCATION
INSTALLING CONTRACTOR
DISTRIBUTOR
START-UP PERFORMED BY
EQUIPMENT:
Chiller:
MODEL #
SERIAL #
COMPRESSORS:
CIRCUIT #1
CIRCUIT #2 (30HK,HL ONLY)
MODEL #
SERIAL #
MOTOR #
MODEL #
SERIAL #
MOTOR #
CONDENSER (30HK, HWB, HWC, HWS ONLY):
MODEL #
SERIAL #
COOLER:
MODEL #
SERIAL #
MANUFACTURED BY
DATE
AIR-HANDLING EQUIPMENT:
MANUFACTURER
MODEL #
SERIAL #
ADDITIONAL AIR-HANDLING UNITS AND ACCESSORIES
B. Preliminary Equipment Check (YES or NO)
IS THERE ANY SHIPPING DAMAGE?
IF SO, WHERE
WILL THIS DAMAGE PREVENT UNIT START-UP?
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT?
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (refer to Installation Instructions)
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (refer to Installation Instructions)
HAS THE GROUND WIRE BEEN CONNECTED?
ARE ALL TERMINALS TIGHT?
ON 30HW UNITS, IS THE THERMISTOR SECURELY STRAPPED TO THE COOLER LEAVING CHILLED FLUID LINE, AND
IS IT PROPERLY INSULATED?
ON 30HW UNITS, IS YELLOW WIRE GOING TO TRANSFORMER 1 (POWER TRANSFORMER) ON THE CORRECT
TERMINAL (TERMINAL H2 FOR 208 V AND 575 V; TERMINAL H3 FOR 230 V, 380 V, AND 400 V, TERMINAL H4
FOR 460 V)?
IF UNIT IS A MEDIUM TEMPERATURE BRINE UNIT, IS TEMPERATURE CONTROLLER SET FOR BRINE AND NOT
FOR WATER? IF UNIT IS NOT A BRINE UNIT, IS TEMPERATURE CONTROLLER SET FOR WATER AND NOT FOR
BRINE?
HAVE TEMPERATURE CONTROLLER, CONTROL MODULE AND CONTROL RELAY CONNECTIONS BEEN CHECKED
FOR TIGHTNESS?
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
PC 903
Catalog No. 533-070
Printed in U.S.A.
Form 30H-10SI
Pg CL-1
11-98
Replaces: 30H-8SI
Tab 5c
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Preliminary Equipment Check (YES or NO) (cont)
HAVE POWER SIDE ELECTRICAL COMPONENT CONNECTIONS BEEN CHECKED FOR TIGHTNESS?
ON 30HK,HL UNITS, IS THE PROPER CONTROL VOLTAGE SUPPLIED TO TB2-1 AND TB2-3?
ON 30HK,HL 50 HZ UNITS, IS THE BLACK WIRE GOING TO TRAN1 AND TRAN2 CONNECTED TO THE RED LEAD FROM
THE TRANSFORMER?
CHECK AIR SYSTEMS (YES OR NO)
ARE ALL AIR HANDLERS OPERATING? (refer to air-handling equipment Installation and Start-Up Instructions)
ARE ALL CHILLED FLUID VALVES OPEN?
IS THE FLUID PIPING CONNECTED PROPERLY?
HAS ALL AIR BEEN VENTED FROM THE COOLER LOOP?
IS THE CHILLED WATER (FLUID) PUMP (CWP) OPERATING?
IS THE CWP ROTATION CORRECT?
CWP MOTOR AMPERAGE:
Rated
Actual
C. Unit Start-Up (insert check mark as each item is completed)
HAS THE CHILLER BEEN PROPERLY INTERLOCKED WITH THE AUXILIARY CONTACTS OF THE CONDENSER
WATER PUMP STARTER?
ASSURE THAT UNIT IS SUPPLIED WITH CORRECT CONTROL VOLTAGE POWER.
ASSURE CRANKCASE HEATERS HAVE BEEN ENERGIZED FOR A MINIMUM OF 24 HOURS PRIOR TO
START-UP.
ASSURE COMPRESSOR OIL LEVEL IS CORRECT.
ASSURE LIQUID LINE SERVICE VALVE(S) IS BACKSEATED.
ASSURE COMPRESSOR DISCHARGE SERVICE VALVE(S) IS BACKSEATED.
ASSURE COMPRESSOR SUCTION SERVICE VALVE(S) IS BACKSEATED.
LOOSEN COMPRESSOR SHIPPING ISOLATOR LOCKNUTS.
OPEN GAGE PANEL SERVICE VALVES.
BE SURE TEMPERATURE CONTROLLER DEADBAND AND SAMPLE RATE SETTINGS ARE SET.
SET POINT SHOULD BE ADJUSTED TO THE DESIRED COOLER LEAVING FLUID TEMPERATURE. (refer to installation
instructions)
LEAK CHECK THOROUGHLY: COMPRESSOR(S), CONDENSER FITTINGS, TXV(s), SOLENOID VALVE(S), FILTER
DRIER(S), FUSIBLE PLUG(S), AND COOLER HEAD(S), WITH GENERAL ELECTRIC H-10-B ELECTRONIC LEAK
DETECTOR.
LOCATE, REPAIR, AND REPORT ANY R-22 LEAKS.
CHECK VOLTAGE IMBALANCE:
AB
AC
BC
V
AB + AC + BC (divided by 3) = AVERAGE VOLTAGE =
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE
(MAX. DEVIATION)
=
VOLTAGE IMBALANCE =
x 100 =
% VOLTAGE IMBALANCE
AVERAGE VOLTAGE
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START CHILLER!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
ASSURE THAT INCOMING POWER VOLTAGE TO CHILLER IS WITHIN RATED UNIT VOLTAGE RANGE.
SYSTEM FLUID VOLUME IN LOOP:
TYPE SYSTEM:
AIR CONDITIONING — MINIMUM 3 GAL. (3.25 L) PER NOMINAL TON (kW) =
PROCESS COOLING — MINIMUM 6 GAL. (6.5 L) PER NOMINAL TON (kW) =
GAL. (L)
GAL. (L)
CL-2
Download from Www.Somanuals.com. All Manuals Search And Download.
C. Unit Start-Up (cont)
COOLER LOOP PROTECTION IF REQUIRED:
GALLONS (LITERS) OF BRINE ADDED:
PIPING INCLUDES ELECTRIC TAPE HEATERS.
CHECK PRESSURE DROP ACROSS COOLER.
FLUID ENTERING COOLER:
PSIG (kPa)
PSIG (kPa)
FLUID LEAVING COOLER:
(PSIG DIFFERENCE) x 2.31 = FT OF FLUID PRESSURE DROP =
(kPa DIFFERENCE) x .335 = FT OF FLUID PRESSURE DROP =
PLOT COOLER PRESSURE DROP ON PERFORMANCE DATA CHART (LOCATED IN PRODUCT DATA LITERATURE) TO
DETERMINE TOTAL GPM (L/s).
TOTAL GPM (L/s) =
UNIT’S RATED MIN. GPM (L/s)
=
GPM (L/s) PER TON =
UNIT’S RATED MIN. PRESSURE DROP =
(Refer to product data literature.)
JOB’S SPECIFIED GPM (L/s) (if available)
NOTE: IF UNIT HAS LOW FLUID FLOW, FIND SOURCE OF PROBLEM: CHECK FLUID PIPING, IN-LINE FLUID STRAINER,
SHUT-OFF VALVES, CHILLED FLUID PUMP ROTATION, ETC.
COOLER LOOP PROTECTION:
GAL. (L) OF BRINE ADDED (IF REQUIRED).
IN-LINE WATER STRAINER INSTALLED ADJACENT TO COOLER FLUID INLET. (REQUIRED FOR 30HW COOLERS.)
YES
NO
CONDENSER PROTECTION:
IN-LINE MINIMUM 20-MESH STRAINER INSTALLED ADJACENT TO THE CONDENSER WATER INLET.
YES
NO
TO START THE CHILLER: (insert check mark as each item is completed)
PLACE ON-OFF SWITCH IN THE ON POSITION.
ASSUMING THERE IS A CALL FOR CHILLED FLUID, THE COMPRESSOR WILL START UNLOADED AFTER A 6-SECOND
TO 5-MINUTE DELAY (DEPENDING ON THE TIMING LOGIC).
THE LOW-PRESSURE SWITCH (ALL UNITS) AND OIL-PRESSURE SWITCH (30HL, HWA UNITS — ACCESSORY ON 30HK,
HWB, HWC, HWS UNITS) ARE BYPASSED FOR 2 MINUTES.
IF ADDITIONAL CAPACITY IS REQUIRED AFTER THE 2-MINUTE PERIOD, COMPRESSOR WILL LOAD UP.
MEASURE THE FOLLOWING: WHILE MACHINE IS IN STABLE OPERATING CONDITION.
SUCTION PRESSURE
SUCTION LINE TEMP.
SUCTION SUPERHEAT
DISCHARGE PRESSURE
DISCHARGE LINE TEMP.
DISCHARGE SUPERHEAT
CHECK AND ADJUST SUCTION SUPERHEAT (9 to 11 F [5 to 6 C]).
CL-3
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES:
Copyright 1998 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
PC 903
Catalog No. 533-070
Printed in U.S.A.
Form 30H-10SI
Pg CL-4
11-98
Replaces: 30H-8SI
Tab 5c
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Bose Car Amplifier 1800 VI User Manual
Bose Portable Speaker COMPANION 2 User Manual
Broil King Food Warmer RV00 User Manual
Bush Hog Automobile Accessories SRG60 User Manual
Bushnell Digital Camera 119439 User Manual
Cambridge Audio Stereo Amplifier Azur 740A User Manual
Campbell Hausfeld Pressure Washer MX5222 User Manual
Chamberlain Battery Charger SL930 User Manual
Chicago Electric Washer 98332 User Manual
Chimera Work Light 8000 User Manual