48PG20-28
Single Package Rooftop Units
Electric Cooling/Gas Heating with
Electromechanical Controls and PURON® (R-410A) Refrigerant
Installation, Start-Up and Service Instructions
Page
CONTENTS
Control Circuit, 24-V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Replacement Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57-61
Unit Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
EconoMi$er IV Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . 60
Phase Loss Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-17
Step 1 — Provide Unit Support . . . . . . . . . . . . . . . . . . . . . . . . .2
•
•
•
ROOF CURB
ALTERNATE UNIT SUPPORT
SLAB MOUNT
UNIT START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . CL-1
Step 2 — Remove Shipping Rails . . . . . . . . . . . . . . . . . . . . . . .2
Step 3 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
SAFETY CONSIDERATIONS
•
•
•
POSITIONING
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance
functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the unit,
and other safety precautions that may apply.
ROOF MOUNT
INSTALLATION ONTO CURB
Step 4 — Field Fabricate Ductwork . . . . . . . . . . . . . . . . . . . . .9
Step 5 — Make Unit Duct Connections. . . . . . . . . . . . . . . . . .9
•
•
VERTICAL CONFIGURATION
HORIZONTAL APPLICATIONS
Step 6 — Install Flue Hood and Inlet Hood . . . . . . . . . . . . 10
Step 7 — Trap Condensate Drain . . . . . . . . . . . . . . . . . . . . . 10
Step 8 — Install Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Step 9 — Make Electrical Connections. . . . . . . . . . . . . . . . .11
•
•
FIELD POWER SUPPLY
FIELD CONTROL WIRING
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
Step 10 — Install Outdoor-Air Hood. . . . . . . . . . . . . . . . . . . 12
•
MANUAL DAMPER ASSEMBLY
Step 11 — Position Optional Power
Exhaust or Barometric Relief Damper Hood . . . . . . . . . 16
Step 12 — Non-Fused Disconnect . . . . . . . . . . . . . . . . . . . . 16
Step 13 — Install All Accessories. . . . . . . . . . . . . . . . . . . . . 16
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-45
Unit Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Compressor Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Refrigerant Service Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Crankcase Heater(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Compressor Rotation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Internal Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Subcooler Heat Exchanger (SHX). . . . . . . . . . . . . . . . . . . . . 18
Evaporator Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Condenser Fans and Motors. . . . . . . . . . . . . . . . . . . . . . . . . . 19
Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Outdoor-Air Inlet Screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Gas Heat. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Optional EconoMi$er IV. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Operating Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Puron (R-410A) refrigerant systems operate at higher pres-
sures than standard R-22 systems. Do not use R-22 service
equipment or components on Puron refrigerant equipment.
If service equipment is not rated for Puron refrigerant,
equipment damage or personal injury may result.
SERVICE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46-57
Cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Manual Outdoor Air Damper . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Economizer Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Evaporator Fan Service and Replacement . . . . . . . . . . . . 48
Evaporator Fan Performance Adjustment. . . . . . . . . . . . . 48
Evaporator Fan Belt Tension Adjustment . . . . . . . . . . . . . 48
Condenser Fan Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Verify Sensor Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Economizer Operation During Power Failure. . . . . . . . . . 49
Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Gas Valve Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
High Altitude. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Main Burners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Filter Drier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Relief Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
1. Improper installation, adjustment, alteration, service,
or maintenance can cause property damage, personal
injury, or loss of life. Refer to the User’s Information
Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any
phone in your building.
3. IMMEDIATELY call your gas supplier from a neigh-
bor’s phone. Follow the gas supplier’s instructions.
4. If you cannot reach your gas supplier, call the fire
department.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 534-80211 Printed in U.S.A. Form 48PG-10SI Pg 1 9-05 Replaces: New
Book 1
4
Tab 1a 6a
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
SHIPPING RAILS
Fig. 2 — Shipping Rail Removal
MAX
WEIGHT
(LB) *
CENTER OF GRAVITY ( IN.)
UNIT SIZE
Z
Y
X
3825
4075
4300
PG20
PG24
PG28
66.5
36.7
31.4
66.5
70.5
37.0
37.0
31.8
35.2
DOES NOT INCLUDE ERV ( ENERGY RECOVERY VENTILATOR) OPTION.
NOTES:
1. Add 150 lb (68 kg) for domestic crating.
2. See label for unit location on roof curb.
Fig. 3 — Rigging Details
4
Download from Www.Somanuals.com. All Manuals Search And Download.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1 — Physical Data
UNIT 48PG
20
24
28
VOLTAGE
NOMINAL CAPACITY (Tons)
208/230 and 460
18
575
18
208/230 and 460
20
575
20
208/230 and 460
25
575
25
OPERATING WEIGHT (lb)
48 Series (Low Heat) Al/Al*
2480
2480
2588
2588
2773
2773
COMPRESSOR
Fully Hermetic Scroll
Quantity
2
2
2
2
2
2
2
3
2
3
2
Number of Refrigerant Circuits
Oil (ounces) Comp A1, A2, B1
2
85, NA, 85
85, NA, 85
85, NA, 85
85, NA, 85
85, 85, 85
85, 85, 85
REFRIGERANT TYPE
Expansion Device
Change Type
Puron® Refrigerant (R-410A)
TXV
TXV
TXV
TXV
TXV
TXV
Operating Charge (lb)
Circuit A
25.3
25.3
25.3
25.3
35.7
33.5
35.7
33.5
49.3
24.3
49.3
24.3
Circuit B
REFRIGERANT SUBCOOLER
Heat Exchanger Size
Expansion Device
B15Hx26x26
TXV
B15Hx26x26
TXV
B15Hx26x26
TXV
B15Hx26x26
TXV
B15Hx26x36
TXV
B15Hx26x36
TXV
CONDENSER COIL
Rows...Fins/inch
Quantity
Enhanced Copper Tubes, Aluminum Lanced Fins
2...17
2
2...17
2
3...17
3
3...17
3
3...17
3
3...17
3
Length of Tube Sheets (in.)
Width (in.)
80.3
60
80.3
60
80.3
60
80.3
60
33.46
80.3
60
80.3
60
Total Face area (sq. ft)
33.46
33.46
33.46
33.46
33.46
CONDENSER FAN
Propeller
Nominal Cfm (Total, all fans)
Quantity...Diameter (in.)
Motor Hp...Rpm
14,000
4...22
14,000
4...22
21,000
6...22
21,000
6...22
21,000
6...22
21,000
6...22
1/4...1100
1400
1/4...1100
1400
1/4...1100
2100
1/4...1100
2100
1/4...1100
2100
1/4...1100
2100
Watts input (Total)
EVAPORATOR COIL
Rows...Fins/inch
Enhanced Copper Tubes, Face Split, Aluminum Double-Wavy Fins
4...15
69.4
48
4...15
69.4
48
4...15
69.4
48
4...15
69.4
48
4...15
69.4
60
4...15
69.4
60
Length of Tube Sheets (in.)
Width (in.)
Total Face area (sq ft)
23.13
23.13
23.13
23.13
28.92
28.92
EVAPORATOR FAN
Quantity...Size (in.)
Type Drive
Centrifugal, Belt Type
2...15 x 11
Belt
2...15 x 11
Belt
2...15 x 11
Belt
2...15 x 11
Belt
2...15 x 11
Belt
2...15 x 11
Belt
Nominal Cfm
7000
7000
8000
8000
Ball
10,000
Ball
10,000
Ball
Motor Bearing Type
Maximum Allowable Fan Rpm
Ball
1400
Ball
1400
Ball
1400
1400
1400
1400
FURNACE SECTION
Rollout Switch Cutout Temp (F)
Burner Orifice Diameter (in. ...drill size)
Gas
Vertical
225
225
225
225
225
225
0.136...29
Natural
0.136...29
Natural
0.136...29
Natural
0.136...29
Natural
0.136...29
Natural
0.136...29
Natural
Thermostat Heat Anticipator Setting
Stage 1 (amps)
0.98
0.44
317,000
400,000
82
25-55
281,000
365,000
81
0.98
0.44
317,000
400,000
82
25-55
281,000
365,000
81
0.98
0.44
317,000
400,000
82
25-55
281,000
365,000
81
0.98
0.44
317,000
400,000
82
25-55
281,000
365,000
81
0.98
0.44
317,000
400,000
82
25-55
281,000
365,000
81
0.98
0.44
317,000
400,000
82
25-55
281,000
365,000
81
Stage 2 (amps)
Gas Input (Btuh) HIGH HEAT
Stage 1
Stage 2
Vertical
Efficiency (Steady State) %
Temperature Rise Range
Gas Input (Btuh) MEDIUM HEAT
Stage 1
Stage 2
Vertical
Efficiency (Steady State) %
Temperature Rise Range
Gas Input (Btuh) LOW HEAT
25-55
199,000
250,000
82
25-55
199,000
250,000
82
25-55
199,000
250,000
82
25-55
199,000
250,000
82
25-55
199,000
250,000
82
25-55
199,000
250,000
82
Stage 1
Stage 2
Vertical
Efficiency (Steady State) %
Temperature Rise Range
Manifold Pressure
15-45
15-45
15-45
15-45
15-45
15-45
Natural Gas (in. wg)
Vertical
Horizontal
3.00
2.95
3.00
2.95
3.00
2.95
3.00
2.95
3.00
2.95
3.00
2.95
Natural Gas (in. wg)
Gas Valve Quantity
1
1
1
1
1
1
Gas Valve Pressure Range
Min-Max Allowable
(in. wg)
(psig)
5.5-13.0
5.5-13.0
5.5-13.0
5.5-13.0
5.5-13.0
5.5-13.0
.235-.469
.235-.469
.235-.469
.235-.469
.235-.469
.235-.469
3
3
3
3
3
3
Field Gas Connection Size (in...FPT)
/
/
/
/
/
/
4
4
4
4
4
4
HIGH-PRESSURE SWITCHES (psig)
Cutout
630 10
505 20
630 10
505 20
630 10
505 20
630 10
505 20
630 10
505 20
630 10
505 20
Reset (Auto)
OUTDOOR AIR INLET SCREENS
Quantity...Size (in.)
3...20 x 25
3...20 x 25
3...20 x 25
3...20 x 25
3...20 x 25
3...20 x 25
RETURN-AIR FILTERS
Quantity...Size (in.)
9...16 x 25 x 2
9...16 x 25 x 2
9...16 x 25 x 2
9...16 x 25 x 2
9...20 x 25 x 2
9...20 x 25 x 2
LEGEND
TXV — Thermostatic Expansion Valve
*Aluminum evaporator coil/aluminum condenser coil.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2 — Fan Motor and Drive Data — Vertical Supply/Return
20
208/230 and 460
24
208/230 and 460
28
208/230 and 460
48PG
575
575
575
LOW RANGE
Motor Hp
3.7
5
1750
5.75
3.7
5
1750
5.75
5
1750
5.75
5
1750
5.75
Motor Nominal Rpm
1750
4.26
1750
4.26
Maximum Continuous Bhp
Maximum Continuous Watts
Motor Frame Size
3174
56HZ
4290
S184T
11/8
3174
56HZ
4290
S184T
11/8
4290
S184T
11/8
4290
S184T
11/8
7
7
Motor Shaft Diameter (in.)
/
/
Fan Rpm Range
685-8939
751-954
3.7
685-8939
751-954
3.7
687-873
3.7
687-873
3.7
Motor Pulley Min. Pitch Diameter (in.)
Motor Pulley Max. Pitch Diameter (in.)
Blower Pulley Pitch Diameter (in.)
Blower Pulley Shaft Diameter (in.)
Blower Pulley Type
2.7
3.7
2.7
3.7
4.7
4.7
4.7
4.7
6.8
8.6
6.8
8.6
9.4
9.4
13/16
13/16
13/16
13/16
13/16
13/16
Fixed
Fixed
9.81-13.055
Fixed
Fixed
9.81-13.055
Fixed
9.81-13.055
Fixed
9.81-13.055
Pulley Center Line Distance (in.)
Belt, Quantity...Type...Length (in.)
Speed Change Per Turn — Moveable Pulley (rpm)
Moveable Pulley Maximum Full Turns
Factory Speed Setting (rpm)
11.293-13.544
11.293-13.544
1...BX38...39.8 1...BX40...41.8 1...BX38...39.8 1...BX40...41.8 1...BX41...42.8 1...BX41...42.8
42
6
812
34
6
853
42
6
812
34
6
853
31
6
780
31
6
780
MID-LOW RANGE
Motor Hp
5
1750
5
1750
5
1750
5
1750
5
1750
5
1750
Motor Nominal Rpm
Maximum Continuous Bhp
Maximum Continuous Watts
Motor Frame Size
5.75
5.75
5.75
5.75
5.75
5.75
4290
4290
4290
4290
4290
4290
S184T
S184T
S184T
S184T
S184T
S184T
Motor Shaft Diameter (in.)
Fan Rpm Range
11/8
11/8
11/8
11/8
11/8
11/8
949-1206
3.7
949-1206
3.7
949-1206
3.7
949-1206
3.7
805-1007
4.8
805-1007
4.8
Motor Pulley Min. Pitch Diameter (in.)
Motor Pulley Max. Pitch Diameter (in.)
Blower Pulley Pitch Diameter (in.)
Blower Pulley Shaft Diameter (in.)
Blower Pulley Type
4.7
4.7
4.7
4.7
6
6
6.8
6.8
6.8
6.8
10.4
10.4
13/16
13/16
13/16
13/16
13/16
13/16
Fixed
9.81-13.055
Fixed
9.81-13.055
Fixed
9.81-13.055
Fixed
9.81-13.055
Fixed
9.81-13.055
Fixed
9.81-13.055
Pulley Center Line Distance (in.)
Belt, Quantity...Type...Length (in.)
Speed Change Per Turn — Moveable Pulley (rpm)
Moveable Pulley Maximum Full Turns
Factory Speed Setting (rpm)
1...BX38...39.8 1...BX38...39.8 1...BX38...39.8 1...BX38...39.8 1...BX45...46.8 1...BX45...46.8
43
6
1078
43
6
1078
43
6
1178
43
6
1078
34
6
906
34
6
906
MID-HIGH RANGE
Motor Hp
7.5
1750
7.5
1750
7.5
1750
7.5
1750
7.5
1750
7.5
1750
Motor Nominal Rpm
Maximum Continuous Bhp
Maximum Continuous Watts
Motor Frame Size
8.63
8.63
8.63
8.63
8.63
8.63
6434
6434
6434
6434
6434
6434
S213T
S213T
S213T
S213T
S213T
S213T
Motor Shaft Diameter (in.)
Fan Rpm Range
13/8
13/8
13/8
13/8
13/8
13/8
941-1176
4.8
941-1176
4.8
941-1176
4.8
941-1176
4.8
941-1176
4.8
941-1176
4.8
Motor Pulley Min. Pitch Diameter (in.)
Motor Pulley Max. Pitch Diameter (in.)
Blower Pulley Pitch Diameter (in.)
Blower Pulley Shaft Diameter (in.)
Blower Pulley Type
6.0
6.0
6.0
6.0
6.0
6.0
8.9
8.9
8.9
8.9
8.9
8.9
13/16
13/16
13/16
13/16
13/16
13/16
Fixed
9.025-12.179
Fixed
9.025-12.179
Fixed
9.025-12.179
Fixed
9.025-12.179
Fixed
9.025-12.179
Fixed
9.025-12.179
Pulley Center Line Distance (in.)
Belt, Quantity...Type...Length (in.)
Speed Change Per Turn —
Moveable Pulley (rpm)
Moveable Pulley Maximum Full Turns
Factory Speed Setting (rpm)
1...BX42...43.8 1...BX42...43.8 1...BX42...43.8 1...BX42...43.8 1...BX42...43.8 1...BX42...43.8
39
39
39
39
39
39
6
6
6
6
6
6
1059
1059
1059
1059
1059
1059
HIGH RANGE
Motor Hp
10
1750
10
1750
10
1750
10
1750
10
1750
10
1750
Motor Nominal Rpm
Maximum Continuous Bhp
Maximum Continuous Watts
Motor Frame Size
11.50
8579
11.50
8579
11.50
8579
11.50
8579
11.50
8579
11.50
8579
S215T
S215T
S215T
S215T
S215T
S215T
Motor Shaft Diameter (in.)
Fan Rpm Range
13/8
13/8
13/8
13/8
13/8
13/8
1014-1297
4.3
1014-1297
4.3
1014-1297
4.3
1014-1297
4.3
1014-1297
4.3
1014-1297
4.3
Motor Pulley Min. Pitch Diameter (in.)
Motor Pulley Max. Pitch Diameter (in.)
Blower Pulley Pitch Diameter (in.)
Blower Pulley Shaft Diameter (in.)
Blower Pulley Type
5.5
5.5
5.5
5.5
5.5
5.5
7.4
7.4
7.4
7.4
7.4
7.4
13/16
13/16
13/16
13/16
13/16
13/16
Fixed
9.025-12.179
Fixed
9.025-12.179
Fixed
9.025-12.179
Fixed
9.025-12.179
Fixed
9.025-12.179
2...BX38..39.8
47
Fixed
9.025-12.179
2...BX38...39.8
47
Pulley Center Line Distance (in.)
Belt, Quantity...Type...Length (in.)
Speed Change Per Turn — Moveable Pulley (rpm)
Moveable Pulley Maximum Full Turns
Factory Speed Setting (rpm)
2...BX38...39.8 2...BX38...39.8 2...BX38...39.8 2...BX38...39.8
47
6
1156
47
6
1156
47
6
1156
47
6
1156
6
6
1156
1156
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 3 — Fan Motor and Drive Data — Horizontal Supply/Return
20
208/230 and 460
24
208/230 and 460
28
208/230 and 460
48PG
575
575
575
LOW RANGE
Motor Hp
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
5
1750
5
1750
Motor Nominal Rpm
Maximum Continuous Bhp
Maximum Continuous Watts
Motor Frame Size
Motor Shaft Diameter (in.)
Fan Rpm Range
Motor Pulley Min. Pitch Diameter (in.)
Motor Pulley Max. Pitch Diameter (in.)
Blower Pulley Pitch Diameter (in.)
Blower Pulley Shaft Diameter (in.)
Blower Pulley Type
Pulley Center Line Distance (in.)
Belt, Quantity...Type...Length (in.)
Speed Change Per Turn —
Moveable Pulley (rpm)
Moveable Pulley Maximum Full Turns
Factory Speed Setting (rpm)
5.75
5.75
4290
4290
S184T
S184T
11/8
11/8
687-873
3.7
687-873
3.7
4.7
4.7
9.4
9.4
13/16
13/16
Fixed
Fixed
9.81-13.055
1...BX41...42.8
9.81-13.055
1...BX41...42.8
—
—
—
—
31
31
—
—
—
—
—
—
—
—
6
780
6
780
MID-LOW RANGE
Motor Hp
3.7
5
1750
3.7
5
1750
5
1750
5
1750
Motor Nominal Rpm
1750
4.26
3174
1750
4.26
3174
Maximum Continuous Bhp
Maximum Continuous Watts
Motor Frame Size
5.75
5.75
5.75
5.75
4290
4290
4290
4290
56HZ
S184T
56HZ
S184T
S184T
S184T
7
7
Motor Shaft Diameter (in.)
Fan Rpm Range
/
8
11/8
/
8
11/8
11/8
11/8
896-1227
2.7
873-1108
3.7
896-1227
873-1108
3.7
805-1007
4.8
805-1007
4.8
Motor Pulley Min. Pitch Diameter (in.)
Motor Pulley Max. Pitch Diameter (in.)
Blower Pulley Pitch Diameter (in.)
Blower Pulley Shaft Diameter (in.)
Blower Pulley Type
2.7
3.7
3.7
4.7
4.7
6.0
6.0
5.2
7.4
5.2
7.4
10.4
10.4
13/16
13/16
13/16
13/16
13/16
13/16
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Pulley Center Line Distance (in.)
Belt, Quantity...Type...Length (in.)
Speed Change Per Turn —
Moveable Pulley (rpm)
Moveable Pulley Maximum Full Turns
Factory Speed Setting (rpm)
11.293-13.544
1...BX35...36.8
9.81-13.055
1...BX38...39.8
11.293-13.544
1...BX35...36.8
9.81-13.055
1...BX38...39.8
9.81-13.055
1...BX45...46.8
9.81-13.055
1...BX45...46.8
55
39
55
39
34
34
6
6
991
6
6
991
6
906
6
906
1062
1062
MID-HIGH RANGE
Motor Hp
5
1750
5
1750
5
1750
5
1750
7.5
1750
7.5
1750
Motor Nominal Rpm
Maximum Continuous Bhp
Maximum Continuous Watts
Motor Frame Size
5.75
5.75
5.75
5.75
8.63
8.63
4290
4290
4290
4290
6434
6434
S184T
S184T
S184T
S184T
S213T
S213T
Motor Shaft Diameter (in.)
Fan Rpm Range
11/8
11/8
11/8
11/8
13/8
13/8
1113-1414
3.7
1113-1414
3.7
1113-1414
3.7
1113-1414
3.7
941-1176
4.8
941-1176
4.8
Motor Pulley Min. Pitch Diameter (in.)
Motor Pulley Max. Pitch Diameter (in.)
Blower Pulley Pitch Diameter (in.)
Blower Pulley Shaft Diameter (in.)
Blower Pulley Type
4.7
4.7
4.7
4.7
6.0
6.0
5.8
5.8
5.8
5.8
8.9
8.9
13/16
13/16
13/16
13/16
13/16
13/16
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Pulley Center Line Distance (in.)
Belt, Quantity...Type...Length (in.)
Speed Change Per Turn —
Moveable Pulley (rpm)
Moveable Pulley Maximum Full Turns
Factory Speed Setting (rpm)
9.81-13.055
1...BX35...36.8
9.81-13.055
1...BX35...36.8
9.81-13.055
1...BX35...36.8
9.81-13.055
1...BX35...36.8
9.025-12.179
1...BX42...43.8
9.025-12.179
1...BX42...43.8
50
50
50
50
39
39
6
6
6
6
6
6
1264
1264
1264
1264
1059
1059
HIGH RANGE
Motor Hp
7.5
1750
7.5
1750
7.5
1750
7.5
1750
10
1750
10
1750
Motor Nominal Rpm
Maximum Continuous Bhp
Maximum Continuous Watts
Motor Frame Size
8.63
8.63
8.63
8.63
11.50
11.50
6434
6434
6434
6434
8579
8579
S213T
S213T
S213T
S213T
S215T
S215T
Motor Shaft Diameter (in.)
Fan Rpm Range
13/8
13/8
13/8
13/8
13/8
13/8
1096-1339
5.4
1096-1339
5.4
1096-1339
5.4
1096-1339
5.4
1014-1297
4.3
1014-1297
4.3
Motor Pulley Min. Pitch Diameter (in.)
Motor Pulley Max. Pitch Diameter (in.)
Blower Pulley Pitch Diameter (in.)
Blower Pulley Shaft Diameter (in.)
Blower Pulley Type
6.6
6.6
6.6
6.6
5.5
5.5
8.6
8.6
8.6
8.6
7.4
7.4
13/16
13/16
13/16
13/16
13/16
13/16
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Pulley Center Line Distance (in.)
Belt, Quantity...Type...Length (in.)
Speed Change Per Turn —
Moveable Pulley (rpm)
Moveable Pulley Maximum Full Turns
Factory Speed Setting (rpm)
9.025-12.179
1...BX42...43.8
9.025-12.179
1...BX42...43.8
9.025-12.179
1...BX42...43.8
9.025-12.179
1...BX42...43.8
9.025-12.179
1...BX38...39.8
9.025-12.179
1...BX38...39.8
41
41
41
41
47
47
6
6
6
6
6
6
1218
1218
1218
1218
1156
1156
8
Download from Www.Somanuals.com. All Manuals Search And Download.
ALIGNMENT
HOLE
(IN BASE RAIL)
For vertical supply and return units, tools or parts could
drop into ductwork and cause an injury. Install a 90 degree
turn in the return ductwork between the unit and the condi-
tioned space. If a 90 degree elbow cannot be installed, then
a grille of sufficient strength and density should be installed
to prevent objects from falling into the conditioned space.
ALIGNMENT
HOLE SHOULD
LINE UP WITH
ROOF CURB
EDGE FLANGE
EDGE FLANGE
HORIZONTAL APPLICATIONS — Horizontal units are
shipped with outer panels that allow for side by side horizontal
duct connections. If specified during ordering, the unit will be
shipped with the vertical duct openings blocked off from the
factory, ready for side supply installation. If the horizontal
supply/return option was not specified at time of ordering the
unit, a field-installed accessory kit is required to convert the
vertical unit into a horizontal supply configuration.
Fig. 5 — Alignment Hole Details
Installation of the duct block-off covers should be complet-
ed prior to placing the unit unless sufficient side clearance is
available. A minimum of 66 in. is required between the unit
and any obstruction to install the duct block-off covers. Side
supply duct dimensions and locations are shown on Fig. 4.
Install ductwork to horizontal duct flange connections on side
of unit.
SUPPLY
RETURN
OPENING
OPENING
CURB
RETURN
OPENING
CURB
SUPPLY
OPENING
ALIGNMENT
HOLES FOR
CURB-BOTH
SIDES
ECONOMIZER
ROOF CURB
Fig. 6 — Alignment Hole Location
Step 4 — Field Fabricate Ductwork — On vertical
units, secure all ducts to roof curb and building structure. Do
not connect ductwork to unit. For horizontal applications, field-
supplied flanges should be attached to horizontal discharge
openings and all ductwork secured to the flanges. Insulate and
weatherproof all external ductwork, joints, and roof openings
with counter flashing and mastic in accordance with applicable
codes.
HEAT
EXCHANGER
SEE
NOTE
SEE
NOTE
Ducts passing through an unconditioned space must be
insulated and covered with a vapor barrier.
AIR
IN
AIR
OUT
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with applica-
ble fire codes.
A minimum clearance is not required around ductwork.
Cabinet return-air static shall not exceed –0.35 in. wg with
economizer or 0.45 in. wg without economizer.
These units are designed for a minimum continuous return-
air temperature in heating of 50 F (dry bulb), or an intermittent
operation down to 45 F (dry bulb), such as when used with a
night set-back thermostat.
NOTE: Do not drill in this area; damage to basepan may result in
water leak.
Fig. 7 — Air Distribution — Vertical Supply/Return
ECONOMIZER
To operate at lower return-air temperatures, a field-supplied
outdoor-air temperature control must be used to initiate both
stages of heat when the temperature is below 45 F. Indoor com-
fort may be compromised when these lower air temperatures
are used with insufficient heating temperature rise.
HEAT
Step 5 — Make Unit Duct Connections
SEE
SEE
NOTE
EXCHANGER
NOTE
VERTICAL CONFIGURATION — Unit is shipped for ver-
tical supply and return duct connections. Ductwork openings
are shown in Fig. 1 and 4. Duct connections for vertical
configuration are shown in Fig. 7. Field-fabricated concentric
ductwork may be connected as shown in Fig. 8 and 9. The unit
is designed to attach the ductwork to the roof curb. Do not
attach duct directly to the unit.
AIR OUT
AIR OUT
AIR IN
NOTE: Do not drill in this area; damage to basepan may result in
water leak.
Fig. 8 — Air Distribution — Concentric Duct
9
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTE: Dimensions A, A′, B, and B′ are obtained from field-supplied
ceiling diffuser.
Shaded areas indicate block-off pans.
Fig. 9 — Concentric Duct Details
Step 6 — Install Flue Hood and Inlet Hood —
Flue hood (smaller hood), inlet hood (larger hood), and screens
are shipped inside the unit in the fan section. To install, remove
the heat panel. The flue hood is attached to the heat section
panel from the outside using the screws provided. See Fig. 10.
The inlet hood is installed by inserting the hood through the
back of the heat panel. Attach the hood by inserting the screws
provided through the clearance holes in the heat panel and into
the intake hood.
Install the screens into both hoods using the screws and re-
taining nuts provided with the unit.
FLUE HOOD
Attach the cover of the observation hole on the intake hood
and then replace the heat panel onto the unit to complete the in-
stallation.
INLET HOOD
NOTE: When properly installed, the flue hood will line up
with the combustion fan housing. See Fig. 11.
Fig. 10 — Flue and Inlet Hood Locations
Step 7 — Trap Condensate Drain — See Fig. 12
for drain location. One 3/4-in. half coupling is provided outside
unit evaporator section for condensate drain connection. A trap
at least 4-in. deep must be used. See Fig. 13.
All units must have an external trap for condensate drain-
age. Install a trap at least 4 in. deep and protect against freeze-
up. If drain line is installed downstream from the external trap,
pitch the line away from the unit at 1 in. per 10 ft of run. Do not
use a pipe size smaller than the unit connection.
Step 8 — Install Gas Piping — Unit is equipped for
use with natural gas. Refer to local building codes, or in the
absence of local codes, to ANSI Z223.1-latest year and
addendum Z223.1A-latest year entitled NFGC. In Canada,
installation must be in accordance with the CAN1.B149.1 and
CAN1.B149.2 installation codes for gas burning appliances.
COMBUSTION
FAN HOUSING
HEAT
EXCHANGER
SECTION
3
Support gas piping. For example, a /4-in. gas pipe must
have one field-fabricated support beam every 8 ft. Therefore,
an 18-ft long gas pipe would have a minimum of 3 support
beams.
INDUCED-DRAFT
MOTOR
MAIN BURNER
SECTION
Install field-supplied manual gas shutoff valve with a 1/8-in.
NPT pressure tap for test gage connection at unit. The pressure
tap is located on the gas manifold, adjacent to the gas valve.
Field gas piping must include sediment trap and union. See
Fig. 14.
Fig. 11 — Combustion Fan Housing Location
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 9 — Make Electrical Connections
FIELD POWER SUPPLY — Unit is factory wired for volt-
age shown on unit nameplate. Be sure to check for correct
voltage.
Do not pressure test gas supply while connected to unit.
Always disconnect union before servicing.
When installing units, provide disconnect per NEC (Nation-
al Electrical Code) of adequate size (MOCP [Maximum Over-
current protection] of unit is on the informative plate). See
Tables 4A and 4B. All field wiring must comply with NEC and
local codes. Size wire based on MCA (Minimum Circuit
Amps) on the unit informative plate. See Fig. 15 for power
wiring connection to the unit power terminal block and equip-
ment ground.
IMPORTANT: Natural gas pressure at unit gas connection
must not be less than 5.5 in. wg or greater than 13.0 in. wg.
Size gas-supply piping for 0.5-in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas connection.
Route power and ground lines through control box end pan-
el or unit basepan (see Fig. 4) to connections as shown on unit
wiring diagram and Fig. 15.
The correct power phasing is critical to the operation of the
scroll compressors. An incorrect phasing will result in
compressor shutdown on thermal overload and possible
damage to compressor. Should this occur, power phase cor-
rection must be made to the incoming power.
Unit cabinet must have an uninterrupted, unbroken electri-
cal ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist of
electrical wire connected to unit ground lug in control com-
partment, or conduit approved for electrical ground when
installed in accordance with NEC, ANSI/NFPA (American
National Standards Institute/National Fire Protection Asso-
ciation), latest edition, and local electrical codes. Do not
use gas piping as an electrical ground. Failure to follow
this warning could result in the installer being liable for
personal injury of others.
Fig. 12 — Condensate Drain Details
Field wiring must conform to temperature limitations for
type “T” wire. All field wiring must comply with NEC and
local requirements.
Operating voltage to compressor must be within voltage
range indicated on unit nameplate. On 3-phase units, voltages
between phases must be balanced within 2%.
Unit failure as a result of operation on improper line voltage
or excessive phase imbalance constitutes abuse and may cause
damage to electrical components.
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4-in. trap is recommended.
FIELD CONTROL WIRING — Unit can be controlled with
either a Carrier-approved accessory thermostat. Install thermo-
stat according to the installation instructions included with
accessory. Locate thermostat assembly on a solid interior wall
in the conditioned space to sense average temperature.
Fig. 13 — Condensate Drain Piping Details
Route thermostat cable or equivalent single leads of colored
wire from subbase terminals through conduit into unit to low-
voltage connections as shown on unit label wiring diagram and
in Fig. 16.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft,
use no. 16 AWG insulated wire (35 C minimum). For over
75 ft, use no. 14 AWG insulated wire (35 C Minimum). All
wire larger than no. 18 AWG cannot be directly connected at
the thermostat and will require a junction box and splice at the
thermostat.
Fig. 14 — Field Gas Piping
11
Download from Www.Somanuals.com. All Manuals Search And Download.
facing outward from the unit. Install the filter track with 4
screws provided.
5. Apply seal strip (provided) to back flange of both hood
sides where hood side connects to the unit back panel.
See Fig. 18.
6. Apply seal strip (provided) to top flange of both hood
sides where hood sides connect to the hood top panels.
See Fig. 18.
7. Install hood sides to the back panels using the screws
from Step 2. The sloped flanges point outward. The drip
edges of the side panels should face outward as well. The
filter guides to the hood sides. The flanges of the filter
guides should face inward to hold the filters in place.
See Fig. 18.
LEGEND
EQUIP — Equipment
GND — Ground
8. Apply seal strip along the entire length of the bottom
flange of the hood top. See Fig. 18.
9. Install the bottom part of the hood top using 4 screws pro-
vided. See Fig. 18.
10. Remove the packaging from filters (3) and install into the
filter tracks. Slide the filters to the sides then place the last
filter into the center of the filter track.
NEC
TB
— National Electrical Code
— Terminal Board
NOTE: The maximum wire size for TB1 is 2/0.
Fig. 15 — Field Power Wiring Connections
NOTE: For units with manual dampers, replace the end filters
with the manual dampers. Install the filter in the center
between the manual dampers.
THERMOSTAT ASSEMBLY
REMOVABLE JUMPER
L
11. Install the filter retainer track along the bottom edge of
the outdoor air hood using 4 screws provided. See
Fig. 18.
RH
RC
Y1
Y2
W1
W2
G
C
X
12. Install top section of the outdoor air hood using 9 screws
provided. See Fig. 18. See Fig. 19 for a picture of the as-
sembled outdoor air hood.
TB2-
J11
R
1
Y1
2
Y2
3
W1
4
W2
5
G
6
C
7
X
8
Fig. 16 — Field Control Thermostat Wiring
NOTE: For filter removal, remove the four screws holding the
filter retainer. The filters can then be removed, cleaned, or
replaced. Install the filters by reversing the procedure.
MANUAL DAMPER ASSEMBLY — For units equipped
with manual dampers, the assembly process is similar to the
outdoor air hood for units with economizers. There are two
slide dampers shipped with the unit to allow for manual setting
of the outside air volume. When assembling the hood, place
one of the manual slide dampers in each of the end positions
and the remaining filter in the center position. The manual
dampers can then be moved to the appropriate position and
then locked into place using the screws mounted in the adjust-
ment slots. See Fig. 20.
Set heat anticipator settings as follows:
STAGE 1
(W1) ON
0.98
STAGE 1 AND 2
(W1 AND W2) ON
VOLTAGE
All
0.44
Settings may be changed slightly to provide a greater degree
of comfort for a particular installation.
Step 10 — Install Outdoor Air Hood — Per-
form the following procedure to install the outdoor-air hood on
units equipped with an economizer, two-position damper, or
manual outdoor air damper:
1. Remove blank panel from return end of unit (hood sec-
tion). Save the screws. See Fig. 17 for shipping location
of components.
HOOD
SIDE
HOOD TOP
(BOTTOM HALF)
HOOD TOP
(TOP HALF)
HOOD
SIDE
2. Hood sides are fastened to sides of outdoor air opening.
Remove the hood sides and save the screws (3 each side).
3. Remove the bracket holding the bottom half of the hood
in the shipping position. Remove the hood bottom half
and filters (or manual dampers on units so equipped)
from outdoor section.
RETURN AIR
SECTION
NOTE: On units without economizers, the components
are attached to the unit basepan. To access the compo-
nents, remove the panel below the outdoor air intake
section.
Fig. 17 — Outdoor-Air Hood Component
Shipping Location
4. Remove inner filter track from shipping position in out-
door section. Position inner filter track so the track is
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4A — Electrical Data (Units Without Optional Powered Convenience Outlet)
COMPRESSOR
No. 2
POWER SUPPLY
VOLTAGE
RANGE
POWER
COMBUSTION
FAN MOTOR
POWER
UNITS WITH
OPTIONAL HACR
BREAKER
DISCONNECT
SIZE
OFM
IFM
UNIT NOMINAL
EXHAUST
SUPPLY*
No. 1
No. 3
SIZE
VOLTAGE
48HG (3 Ph, 60 Hz)
FLA
(ea)
FLA
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
Hp
FLA
Qty Hp
FLA
MCA
MOCP
MCA
MOCP
FLA
(ea)
—
—
2
—
1
80/ 79 100/100 80/ 80 100/100
92/ 91 100/100 92/ 92 100/100
86/ 85 100/100 86/ 86 100/100
98/ 96 100/100 98/ 98 100/100
94/ 91 100/100 94/ 94 100/100
105/103 125/125 105/105 125/125
101/ 97 125/100 101/101 125/125
113/109 125/125 113/113 125/125
84/ 83
98/ 96
91/ 89
105/103
100/ 97
113/111
107/104
121/118
44
3.7 10.6/ 9.6
5.9
—
—
2
—
1
5
16.7/15.2
5.9
—
208/230
187 253 28.2 208 28.2 208
—
—
4
0.25 1.5
0.5
—
2
—
1
7.5 24.2/22
10 30.8/28
5.9
—
—
2
—
1
5.9
—
—
2
—
1
42
48
45
51
48
55
51
58
38
43
41
45
43
47
50
60
60
60
60
60
60
60
50
50
50
50
50
60
42
48
45
51
48
55
51
58
38
43
41
45
43
47
50
60
60
60
60
60
60
60
50
50
50
50
50
60
3.7
5
4.8
7.6
11
14
6.1
9
3.1
—
51
—
2
—
1
47
20
3.1
—
55
460
414 506 15.4 104 15.4 104
518 633 12.8 83 12.8 83
187 253 32.1 240 32.1 240
—
—
—
—
—
—
4
4
6
0.25 0.7
0.3
0.24
0.5
—
2
—
1
51
7.5
10
5
3.1
—
58
—
2
—
1
55
3.1
—
62
—
2
—
1
40
2.4
—
45
—
2
—
1
43
575
0.25 0.7 7.5
10
2.4
—
49
—
2
—
1
45
11
2.4
—
51
—
2
—
1
92/ 91 100/100 92/ 92 100/100
104/103 125/125 104/104 125/125
98/ 96 100/100 98/ 98 100/100
110/108 125/125 110/110 125/125
105/103 125/125 105/105 125/125
117/115 125/125 117/117 125/125
112/109 125/125 112/112 125/125
124/121 150/150 124/124 150/150
96/ 95
110/109
103/102
117/115
112/109
126/123
120/116
133/130
46
3.7 10.6/ 9.6
5.9
—
—
2
—
1
5
16.7/15.2
5.9
—
208/230
0.25 1.5
—
2
—
1
7.5 24.2/22
10 30.8/28
5.9
—
—
2
—
1
5.9
—
—
2
—
1
44
50
46
53
50
56
53
59
39
44
42
47
44
49
50
60
60
60
60
60
60
60
50
50
50
50
50
60
44
50
46
53
50
56
53
59
39
44
42
47
44
49
50
60
60
60
60
60
60
60
50
50
50
50
50
60
3.7
5
4.8
7.6
3.1
—
53
—
2
—
1
49
24
3.1
—
56
460
414 506 15.4 110 15.4 110
—
—
6
0.25 0.7
0.3
—
2
—
1
53
7.5
10
5
11
3.1
—
60
—
2
—
1
56
14
3.1
—
63
—
2
—
1
41
6.1
2.4
—
47
—
2
—
1
45
575
518 633 12.8 88 12.8 88
—
—
6
6
6
6
0.25 0.7 7.5
9
0.24
2.4
—
50
—
2
—
1
47
10
5
11
2.4
—
52
—
2
—
1
117/116 125/125 117/117 125/125
129/128 150/150 129/129 150/150
125/123 150/150 125/125 150/150
137/134 150/150 137/137 150/150
132/129 150/150 132/132 150/150
144/140 150/150 144/144 150/150
127/125
140/139
135/133
149/147
143/140
157/153
67
16.7/15.2
5.9
—
—
2
—
1
208/230
187 253 28.2 208 28.2 208 28.2 208
414 506 15.4 104 15.4 104 15.4 104
518 633 12.8 83 12.8 83 12.8 83
0.25 1.5 7.5 24.2/22
10 30.8/28
0.5
5.9
—
—
2
—
1
5.9
—
—
2
—
1
62
68
65
71
68
74
52
57
55
60
57
62
70
80
80
80
80
80
60
60
60
60
60
70
62
68
65
71
68
74
52
57
55
60
57
62
70
80
80
80
80
80
60
60
60
60
60
70
5
7.6
11
14
6.1
9
3.1
—
74
—
2
—
1
71
28
460
575
0.25 0.7 7.5
0.3
3.1
—
78
—
2
—
1
74
10
3.1
—
81
—
2
—
1
56
5
0.25 0.7 7.5
10
2.4
—
62
—
2
—
1
59
0.24
2.4
—
65
—
2
—
1
62
11
2.4
67
See Legend and Notes on page 15.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4B — Electrical Data (Units With Optional Powered Convenience Outlet)
COMPRESSOR
No. 2
POWER SUPPLY
VOLTAGE
RANGE
POWER
COMBUSTION
FAN MOTOR
POWER
UNITS WITH
OPTIONAL HACR
BREAKER
DISCONNECT
SIZE
OFM
IFM
UNIT NOMINAL
EXHAUST
SUPPLY*
No. 1
No. 3
SIZE
VOLTAGE
48HG (3 Ph, 60 Hz)
FLA
(ea)
FLA
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
Hp
3.7 10.6/ 9.6
16.7/15.2
FLA
Qty Hp
FLA
MCA
MOCP
MCA
MOCP
FLA
(ea)
—
—
2
—
1
85/ 84 100/100 85/ 85 100/100
97/ 96 100/100 97/ 97 100/100
91/ 90 100/100 91/ 91 100/100
103/101 125/125 103/103 125/125
99/ 96 100/100 99/ 99 100/100
110/108 125/125 110/110 125/125
106/102 125/125 106/106 125/125
118/114 125/125 118/118 125/125
90/ 89
103/102
97/ 95
110/109
105/103
119/116
113/110
127/123
48
5.9
—
—
2
—
1
5
5.9
—
208/230
187 253 28.2 208 28.2 208
—
—
4
0.25 1.5
0.5
—
2
—
1
7.5 24.2/22
10 30.8/28
5.9
—
—
2
—
1
5.9
—
—
2
—
1
45
51
48
54
51
58
54
61
41
46
44
48
46
50
60
60
60
60
60
60
60
70
50
50
50
60
50
60
45
51
48
54
51
58
54
61
41
46
44
48
46
50
60
60
60
60
60
60
60
70
50
50
50
60
50
60
3.7
5
4.8
7.6
11
14
6.1
9
3.1
—
55
—
2
—
1
51
20
3.1
—
58
460
414 506 15.4 104 15.4 104
518 633 12.8 83 12.8 83
187 253 32.1 240 32.1 240
—
—
—
—
—
—
4
4
6
0.25 0.7
0.3
0.24
0.5
—
2
—
1
55
7.5
10
5
3.1
—
62
—
2
—
1
58
3.1
—
65
—
2
—
1
43
2.4
—
49
—
2
—
1
46
575
0.25 0.7 7.5
10
2.4
—
52
—
2
—
1
49
11
2.4
—
54
—
2
—
1
97/ 96 100/100 97/ 97 100/100
109/108 125/125 109/109 125/125
103/101 125/125 103/103 125/125
115/113 125/125 115/115 125/125
110/108 125/125 110/110 125/125
122/120 150/150 122/122 150/150
117/114 125/125 117/117 125/125
129/126 150/150 129/129 150/150
102/101
116/115
109/107
123/121
118/115
131/129
125/122
139/136
49
3.7 10.6/ 9.6
16.7/15.2
5.9
—
—
2
—
1
5
5.9
—
208/230
0.25 1.5
—
2
—
1
7.5 24.2/22
10 30.8/28
5.9
—
—
2
—
1
5.9
—
—
2
—
1
47
53
49
56
53
59
56
62
42
47
45
50
47
52
60
60
60
60
60
60
60
70
50
50
50
60
50
60
47
53
49
56
53
59
56
62
42
47
45
50
47
52
60
60
60
60
60
60
60
70
50
50
50
60
50
60
3.7
5
4.8
3.1
—
56
—
2
—
1
52
24
7.6
3.1
—
60
460
414 506 15.4 110 15.4 110
—
—
6
0.25 0.7
0.3
—
2
—
1
56
7.5
10
5
11
3.1
—
63
—
2
—
1
60
14
3.1
—
67
—
2
—
1
45
6.1
2.4
—
50
—
2
—
1
48
575
518 633 12.8 88 12.8 88
—
—
6
6
6
6
0.25 0.7 7.5
9
11
0.24
2.4
—
54
—
2
—
1
50
10
5
2.4
—
56
—
2
—
1
122/121 150/125 122/122 150/150
134/133 150/150 134/134 150/150
130/128 150/150 130/130 150/150
142/139 150/150 142/142 150/150
137/134 150/150 137/137 150/150
149/145 175/150 149/149 175/175
133/131
146/144
141/139
155/152
149/146
162/159
70
16.7/15.2
5.9
—
—
2
—
1
208/230
187 253 28.2 208 28.2 208 28.2 208
414 506 15.4 104 15.4 104 15.4 104
518 633 12.8 83 12.8 83 12.8 83
0.25 1.5 7.5 24.2/22
10 30.8/28
0.5
5.9
—
—
2
—
1
5.9
—
—
2
—
1
65
71
68
74
71
77
55
60
58
63
60
65
80
80
80
80
80
90
60
60
60
70
60
70
65
71
68
74
71
77
55
60
58
63
60
65
80
80
80
80
80
90
60
60
60
70
60
70
5
7.6
11
14
6.1
9
3.1
—
77
—
2
—
1
74
28
460
575
0.25 0.7 7.5
0.3
3.1
—
81
—
2
—
1
78
10
3.1
—
85
—
2
—
1
59
5
0.25 0.7 7.5
10
2.4
—
65
—
2
—
1
63
0.24
2.4
—
68
—
2
—
1
65
11
2.4
71
14
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND AND NOTES FOR TABLES 4A AND 4B
LEGEND
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
BC = 464 v
AC = 455 v
IFM
LRA
— Indoor (Evaporator) Fan Motor
— Locked Rotor Amps
452 + 464 + 455
MCA — Minimum Circuit Amps
Average Voltage=
3
MOCP — Maximum Overcurrent Protection
1371
NEC
— National Electrical Code
=
OFM — Outdoor (Condenser) Fan Motor
RLA — Rated Load Amps
3
= 457
Determine maximum deviation from average voltage.
*Fuse or HACR circuit breaker.
(AB) 457 - 452 = 5 v
(BC) 464 - 457 = 7 v
(AC) 457 - 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance.
7
% Voltage Imbalance = 100 x
457
NOTES:
= 1.53%
1. In compliance with NEC requirements for multimotor and com-
bination load equipment (refer to NEC Articles 430 and 440),
the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more
than 2%, contact the local electric utility company immediately.
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percent voltage imbalance.
3. The convenience outlet full load amps (FLA) are 5, 3, and 3 for
208/230, 460, 575-V units, respectively.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
TOP HOOD
SECTION
ADD
SEAL
STRIP
SEAL
HOOD
SIDE
ADD
SEAL
STRIP
STRIP
LOCATION
INNER
FILTER
TRACK
BOTTOM
HOOD
SECTION
ADD
SEAL
STRIP
ADD
SEAL
STRIP
FILTER
GUIDE
FILTER
RETAINER
FILTER
GUIDE
FILTER
HOOD
SIDE
MANUAL
DAMPER
(IF EQUIPPED)
UNIT
BACK
PANEL
NOTE: Units with manual damper only use one filter.
Fig. 18 — Outdoor-Air Hood Details
15
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Pivot the damper assembly outward until top edge of the
damper assembly rests against the inside wall of unit.
3. Secure each damper assembly to unit with 6 screws
across top (3 screws provided) and bottom (3 screws
from Step 1) of damper.
4. With screws saved from Step 1, install brackets on each
side of damper assembly. See Fig. 22.
5. Remove tape from damper blades.
Step 12 — Non-Fused Disconnect — The handle
for the factory-installed non-fused disconnect is shipped inside
the unit to prevent the handle from damage during shipping.
Follow these steps to complete installation of the handle.
BE SURE POWER IS SHUT OFF TO THE UNIT FROM
THE BUILDING POWER SUPPLY. Electrical shock
could cause personal injury.
1. Open the control box access door.
2. Remove the small cover plate located on the unit corner
post near the control section.
Fig. 19 — Outdoor-Air Hood Assembled
3. Remove the inner control box cover. The handle and shaft
are located in a plastic bag at the bottom of the control
box.
4. Insert the square shaft into the disconnect with the pins
vertical. On the 100-amp disconnect, the shaft is keyed
into the disconnect and can only be installed one way
(with the pins vertical).
5. Insert the handle through the corner post and onto the
shaft with the handle positioned so that “OFF” is on top.
6. Rotate the handle to the “ON” position to lock the pins
into the handle.
7. From the inside of the corner post, attach the handle
mounting screws to the handle. Slide the shaft fully into
the handle and tighten the set screw(s) on the disconnect
to lock the shaft. Tighten the screws that attach the handle
to the corner post.
LOCKING SCREW
MOVEABLE DAMPER
AIR FILTER POSITION
MOVEABLE DAMPER
Fig. 20 — Manual Damper Details
8. Rotate the handle back to the “OFF” position.
9. Replace all panels and doors. Power can now be turned
back on to the unit.
Step 11 — Position Optional Power Exhaust or
Barometric Relief Damper Hood — The optional
power exhaust or barometric relief dampers are shipped
assembled and tilted back into the unit for shipping. Brackets
and extra screws are shipped in shrink wrap around the
dampers.
1. Remove 9 screws holding each damper assembly in
place. See Fig. 21. Each damper assembly is secured with
3 screws on each side and 3 screws along the bottom.
Save screws.
Step 13 — Install All Accessories — After all of
the factory-installed options have been adjusted, install all
field-installed accessories. Refer to the accessory installation
instructions included with each accessory. Consult the Carrier
Price Pages for accessory package numbers for particular
applications.
Be careful when tilting blower assembly. Hoods and blow-
ers are heavy and can cause injury if dropped.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 21 — Power Exhaust or Barometric Relief Damper Mounting Details
Fig. 22 — Bracket and Hood Positioning
17
Download from Www.Somanuals.com. All Manuals Search And Download.
PRE-START-UP
START-UP
Use the following information and Start-Up Checklist on
page CL-1 to check out unit PRIOR to start-up.
Failure to observe the following warnings could result in
serious personal injury.
1. Follow recognized safety practices and wear protective
goggles when checking or the servicing refrigerant
system.
2. Do not operate the compressor or provide any electric
power to the unit unless the compressor terminal cover
is in place and secured.
3. Do not remove the compressor terminal cover until all
electrical sources are disconnected.
4. Relieve all pressure from the system before touching or
disturbing anything inside the compressor terminal box
if refrigerant leak is suspected around the compressor
terminals.
5. Never attempt to repair a soldered connection while the
refrigerant system is under pressure.
Unit Preparation — Check that unit has been installed in
accordance with these installation instructions and all applica-
ble codes.
Compressor Mounting — Compressors are internally
spring mounted. Do not loosen or remove compressor hold-
down bolts.
Refrigerant Service Ports — Each independent re-
frigerant system has a total of 3 Schrader-type service gage
ports per circuit. One port is located on the suction line, one on
the compressor discharge line, and one on the liquid line. Be
sure that caps on the ports are tight.
Crankcase Heater(s) — Crankcase heaters are ener-
gized as long as there is power to the unit and the compressor is
not operating.
6. Do not use torch to remove any component. The sys-
tem contains oil and refrigerant under pressure. To
remove a component, wear protective goggles and pro-
ceed as follows:
IMPORTANT: Unit power must be on for 24 hours prior
to start-up. Otherwise, damage to compressor may
result.
a. Shut off gas and then electrical power to the unit.
Install lockout tag.
Compressor Rotation — On 3-phase units, it is impor-
tant to be certain the scroll compressor is rotating in the proper
direction. To determine whether or not compressor is rotating
in the proper direction:
1. Connect service gages to suction and discharge pressure
fittings.
b. Relieve all pressure from the system using both
high-pressure and low-pressure ports.
c. Cut the component connection tubing with a tubing
cutter, and remove the component from the unit.
d. Carefully unsweat the remaining tubing stubs when
necessary. Oil can ignite when exposed to torch
flame.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pres-
sure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels:
Proceed as follows to inspect and prepare the unit for initial
start-up:
1. Remove all access panels.
1. Note that the evaporator fan is probably also rotating in
the wrong direction.
2. Turn off power to the unit and install lockout tag.
3. Reverse any two of the unit power leads.
4. Turn on power to the unit.
The suction and discharge pressure levels should now move
to their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direc-
tion, the unit makes an elevated level of noise and does not
provide heating or cooling.
2. Read and follow instructions on all WARNING, CAU-
TION, and INFORMATION labels attached to, or
shipped with, the unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such as
broken lines, loose parts, or disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections
and on unit base. Detecting oil generally indicates a
refrigerant leak. Leak-test all refrigerant tubing con-
nections using an electronic leak detector, halide
torch, or liquid-soap solution.
c. Inspect all field-wiring and factory-wiring connec-
tions. Be sure that connections are completed and
tight.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten the fins with a fin
comb.
Compressor damage will occur if rotation is not immedi-
ately corrected.
Internal Wiring — Check all electrical connections in
unit control boxes; tighten as required.
4. Verify the following conditions:
Subcooler Heat Exchanger (SHX) — The subcool-
er heat exchanger adds approximately 10 to 15° F of sub-
cooling to the system. Check all valves and TXV (thermostatic
expansion valve).
a. Make sure that condenser fan blade is correctly
positioned in the fan orifice. See Condenser-Fan
Adjustment section on page 49 for more details.
b. Make sure that air filter(s) is in place.
Evaporator Fan — Fan belt and variable pulleys are
factory-installed. See Tables 5-23 for fan performance data. Be
sure that fans rotate in the proper direction. See Table 24 for air
quantity limits. See Table 25 for evaporator fan motor specifi-
cations. See Table 26 for accessory/FIOP static pressure. See
Table 27 for fan rpm at various motor pulley settings. To alter
fan performance, see Evaporator Fan Performance Adjustment
section on page 48.
c. Make sure that condensate drain trap is filled with
water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose parts
have been removed.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Connect pressure gage to manifold pressure tap.
Condenser Fans and Motors — Condenser fans and
motors are factory set. Refer to Condenser-Fan Adjustment
section (page 49) as required.
4. Turn on field-supplied manual gas stop. Temporarily
install the jumper wire between “R” and “W1” on TB2.
Set thermostat to HEAT and raise set point until heat
comes on.
5. After the unit has run for several minutes, verify the sup-
ply gas pressure is between 5.5 in. wg to 13.0 in. wg, and
the manifold pressure is 2.95 in. wg on horizontal dis-
charge applications and 3.00 on vertical discharge appli-
cations. If manifold pressure must be adjusted, refer to
Gas Valve Adjustment section.
NOTE: Supply gas pressure must not exceed 13.0 in. wg.
6. Set thermostat to OFF.
7. Remove jumper wire if the unit will be operating under
thermostat mode.
Return-Air Filters — Check that correct filters are in-
stalled in filter tracks (see Table 1). Do not operate unit without
return-air filters.
NOTE: For units with 4-in. filter option, units are shipped with
standard 2-in. filters. To install 4-in. filters, the filter spacers
must be removed.
Outdoor-Air Inlet Screens — Outdoor-air inlet screens
must be in place before operating unit.
Gas Heat — Verify gas pressures before turning on heat as
follows:
1. Turn off field-supplied manual gas stop, located external
to unit.
8. Return thermostat to desired set point.
2. Connect pressure gage to supply gas tap, located on field-
supplied manual shutoff valve (see Fig. 14).
Table 5 — Fan Performance — 48PGD20 Vertical Supply/Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.6
AIRFLOW
(Cfm)
0.2
0.4
0.8
1.0
Rpm
590
633
677
722
767
813
859
906
952
Bhp
1.47
1.82
2.21
2.67
3.17
3.74
4.36
5.05
5.81
Rpm
663
703
744
786
828
871
915
959
1004
Bhp
1.74
2.11
2.53
3.01
3.53
4.12
4.77
5.47
6.25
Rpm
727
764
803
842
883
924
966
1008
1051
Bhp
2.01
2.40
2.84
3.33
3.88
4.48
5.15
5.87
6.67
Rpm
786
Bhp
2.26
2.67
3.13
3.64
4.21
4.83
5.52
6.26
7.07
Rpm
840
Bhp
2.52
2.94
3.42
3.95
4.53
5.18
5.88
6.64
7.47
5000
5500
6000
6500
7000
7500
8000
8500
9000
820
872
A
A
857
907
A
A
894
942
979
933
A
C
B
C
972
1017
1056
1096
1136
B
C
B
C
1012
1053
1095
B
C
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
891
Bhp
2.77
3.21
3.70
4.25
4.85
5.51
6.23
7.01
7.86
Rpm
940
968
Bhp
3.02
3.48
3.99
4.55
5.17
5.84
6.58
7.38
8.24
Rpm
987
Bhp
3.27
3.74
4.27
4.85
5.48
6.17
6.92
7.74
8.61
Rpm
1032
1057
1084
1114
1145
1178
1213
1248
1285
Bhp
3.52
4.01
4.55
5.14
5.79
6.50
7.26
8.09
8.99
Rpm
1076
1099
1125
1153
1183
1215
1249
1283
1319
Bhp
3.77
4.27
4.83
5.44
6.10
6.82
7.60
8.45
9.36
5000
5500
6000
6500
7000
7500
8000
8500
9000
A
B
921
1014
1042
1073
1106
1140
1176
1212
1250
B
B
D
954
999
B
B
988
1032
1066
1101
1138
1175
1214
C
D
1024
1060
1098
1137
1176
C
D
C
D
C
LEGEND
Brake Horsepower Input to Fan
Bhp
—
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(A) Low Range: 685-939 rpm, 4.26 bhp (208/230 and 460-v), 751-954 rpm, 5.75 bhp (575-v)
(B) Mid-Low Range: 949-1206 rpm, 5.75 bhp
(C) Mid-High Range: 941-1176 rpm, 8.63 bhp
(D) High Range: 1014-1297 rpm, 11.50 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 6 — Fan Performance — 48PGE20 — Vertical Supply/Return Units
AVAILABLE EXTERNAL STATIC PRESSUSRE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
607
652
699
746
794
842
891
940
990
Bhp
1.53
1.90
2.32
2.79
3.33
3.93
4.59
5.32
6.12
Rpm
677
719
763
807
851
897
943
990
1037
Bhp
1.80
2.19
2.63
3.12
3.68
4.30
4.98
5.72
6.54
Rpm
740
779
819
861
904
947
991
1036
1082
Bhp
2.06
2.47
2.93
3.44
4.02
4.65
5.35
6.11
6.95
Rpm
797
Bhp
2.31
2.74
3.22
3.75
4.34
5.00
5.71
6.49
7.35
Rpm
850
Bhp
2.57
3.01
3.50
4.05
4.66
5.33
6.07
6.87
7.73
5000
5500
6000
6500
7000
7500
8000
8500
9000
833
884
A
B
A
872
921
A
A
911
958
A
C
952
998
B
C
994
1038
1079
1121
1163
1036
1080
1124
B
C
B
C
C
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
900
Bhp
2.82
3.27
3.79
4.35
4.98
5.67
6.42
7.23
8.12
Rpm
949
Bhp
3.06
3.54
4.07
4.65
5.29
5.99
6.76
7.59
8.49
Rpm
995
Bhp
3.31
3.80
4.35
4.94
5.60
6.32
7.10
7.95
8.87
Rpm
1040
1066
1095
1127
1160
1195
1231
1269
1308
Bhp
3.56
4.06
4.62
5.24
5.91
6.64
7.44
8.30
9.23
Rpm
1083
1108
1135
1165
1197
1231
1267
1303
1341
Bhp
3.81
4.33
4.90
5.53
6.22
6.96
7.78
8.65
9.60
5000
5500
6000
6500
7000
7500
8000
8500
9000
A
B
933
979
1023
1054
1087
1122
1158
1195
1234
1273
B
B
D
967
1011
1046
1082
1119
1158
1198
1238
B
B
1003
1041
1079
1119
1160
1202
C
D
C
D
C
D
C
D
LEGEND
Brake Horsepower Input to Fan
Bhp
—
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(A) Low Range: 685-939 rpm, 4.26 bhp (208/230 and 460-v), 751-954 rpm, 5.75 bhp (575-v)
(B) Mid-Low Range: 949-1206 rpm, 5.75 bhp
(C) Mid-High Range: 941-1176 rpm, 8.63 bhp
(D) High Range: 1014-1297 rpm, 11.50 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 7 — Fan Performance — 48PGF20 — Vertical Supply/Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
607
652
699
746
794
842
891
940
990
Bhp
1.53
1.90
2.32
2.79
3.33
3.93
4.59
5.32
6.12
Rpm
677
719
763
807
851
897
943
990
1037
Bhp
1.80
2.19
2.63
3.12
3.68
4.30
4.98
5.72
6.54
Rpm
740
779
819
861
904
947
991
1036
1082
Bhp
2.06
2.47
2.93
3.44
4.02
4.65
5.35
6.11
6.95
Rpm
797
Bhp
2.31
2.74
3.22
3.75
4.34
5.00
5.71
6.49
7.35
Rpm
850
Bhp
2.57
3.01
3.50
4.05
4.66
5.33
6.07
6.87
7.73
5000
5500
6000
6500
7000
7500
8000
8500
9000
833
884
A
A
872
921
A
A
911
958
A
C
952
998
B
C
994
1038
1079
1121
1163
B
C
1036
1080
1124
B
C
B
C
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
900
Bhp
2.82
3.27
3.79
4.35
4.98
5.67
6.42
7.23
8.12
Rpm
949
Bhp
3.06
3.54
4.07
4.65
5.29
5.99
6.76
7.59
8.49
Rpm
995
Bhp
3.31
3.80
4.35
4.94
5.60
6.32
7.10
7.95
8.87
Rpm
1040
1066
1095
1127
1160
1195
1231
1269
1308
Bhp
3.56
4.06
4.62
5.24
5.91
6.64
7.44
8.30
9.23
Rpm
1083
1108
1135
1165
1197
1231
1267
1303
1341
Bhp
3.81
4.33
4.90
5.53
6.22
6.96
7.78
8.65
9.60
5000
5500
6000
6500
7000
7500
8000
8500
9000
A
B
933
979
1023
1054
1087
1122
1158
1195
1234
1273
B
B
D
967
1011
1046
1082
1119
1158
1198
1238
B
B
1003
1041
1079
1119
1160
1202
C
D
C
C
D
C
D
D
LEGEND
Bhp — Brake Horsepower Input to Fan
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(A) Low Range: 685-939 rpm, 4.26 bhp (208/230 and 460-v), 751-954 rpm, 5.75 bhp (575-v)
(B) Mid-Low Range: 949-1206 rpm, 5.75 bhp
(C) Mid-High Range: 941-1176 rpm, 8.63 bhp
(D) High Range: 1014-1297 rpm, 11.50 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 8 — Fan Performance — 48PGD24 — Vertical Supply/Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
633
677
722
767
813
859
906
952
999
1047
Bhp
1.82
2.21
2.67
3.17
3.74
4.36
5.05
5.81
6.63
7.53
Rpm
703
Bhp
2.11
2.53
3.01
3.53
4.12
4.77
5.47
6.25
7.09
8.00
Rpm
764
Bhp
2.40
2.84
3.33
3.88
4.48
5.15
5.87
6.67
7.53
8.46
Rpm
820
Bhp
2.67
3.13
3.64
4.21
4.83
5.52
6.26
7.07
7.95
8.90
Rpm
872
Bhp
2.94
3.42
3.95
4.53
5.18
5.88
6.64
7.47
8.36
9.33
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
A
B
744
803
857
907
A
A
B
A
786
842
894
942
979
A
C
828
883
933
871
924
972
1017
1056
1096
1136
1177
1219
B
C
915
959
966
1012
1053
1095
1137
1180
B
C
1008
1051
1094
1138
C
D
1004
1049
1094
C
D
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
921
Bhp
3.21
3.70
4.25
4.85
5.51
6.23
7.01
7.86
8.77
9.75
Rpm
968
Bhp
3.48
3.99
4.55
5.17
5.84
6.58
7.38
8.24
9.17
10.16
Rpm
1014
1042
1073
1106
1140
1176
1212
1250
1288
1327
Bhp
3.74
4.27
4.85
5.48
6.17
6.92
7.74
8.61
9.56
10.57
Rpm
1057
1084
1114
1145
1178
1213
1248
1285
1322
1360
Bhp
4.01
4.55
5.14
5.79
6.50
7.26
8.09
8.99
9.95
10.98
Rpm
1099
1125
1153
1183
1215
1249
1283
1319
1355
1393
Bhp
4.27
4.83
5.44
6.10
6.82
7.60
8.45
9.36
10.33
11.38
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
A
954
999
B
C
B
D
B
B
988
1032
1066
1101
1138
1175
1214
1253
1292
B
1024
1060
1098
1137
1176
1216
1256
C
D
C
D
D
C
D
LEGEND
Brake Horsepower Input to Fan
Bhp
—
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(A) Low Range: 685-939 rpm, 4.26 bhp (208/230 and 460-v), 751-954 rpm, 5.75 bhp (575-v)
(B) Mid-Low Range: 949-1206 rpm, 5.75 bhp
(C) Mid-High Range: 941-1176 rpm, 8.63 bhp
(D) High Range: 1014-1297 rpm, 11.50 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 9 — Fan Performance — 48PGE24 — Vertical Supply/Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
652
699
746
794
842
891
940
990
1039
1089
Bhp
1.90
2.32
2.79
3.33
3.93
4.59
5.32
6.12
7.00
7.95
Rpm
719
Bhp
2.19
2.63
3.12
3.68
4.30
4.98
5.72
6.54
7.43
8.40
Rpm
779
Bhp
2.47
2.93
3.44
4.02
4.65
5.35
6.11
6.95
7.85
8.83
Rpm
833
Bhp
2.74
3.22
3.75
4.34
5.00
5.71
6.49
7.35
8.27
9.26
Rpm
884
Bhp
3.01
3.50
4.05
4.66
5.33
6.07
6.87
7.73
8.67
9.69
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
A
B
763
819
872
921
A
B
A
A
807
861
911
958
A
C
851
904
952
998
897
947
994
1038
1079
1121
1163
1207
1251
B
C
D
943
990
991
1036
1080
1124
1168
1213
B
C
1036
1082
1128
1174
C
D
1037
1085
1133
C
D
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
933
Bhp
3.27
3.79
4.35
4.98
5.67
6.42
7.23
8.12
9.07
10.10
Rpm
979
Bhp
3.54
4.07
4.65
5.29
5.99
6.76
7.59
8.49
9.46
10.51
Rpm
1023
1054
1087
1122
1158
1195
1234
1273
1314
1355
Bhp
3.80
4.35
4.94
5.60
6.32
7.10
7.95
8.87
9.85
10.91
Rpm
1066
1095
1127
1160
1195
1231
1269
1308
1347
1387
Bhp
4.06
4.62
5.24
5.91
6.64
7.44
8.30
9.23
10.24
11.31
Rpm
1108
1135
1165
1197
1231
1267
1303
1341
1379
—
Bhp
4.33
4.90
5.53
6.22
6.96
7.78
8.65
9.60
10.62
—
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
A
B
967
1011
1046
1082
1119
1158
1198
1238
1279
1321
B
C
D
B
D
B
B
1003
1041
1079
1119
1160
1202
1244
1287
C
D
C
D
C
D
LEGEND
Brake Horsepower Input to Fan
Bhp
—
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(A) Low Range: 685-939 rpm, 4.26 bhp (208/230 and 460-v), 751-954 rpm, 5.75 bhp (575-v)
(B) Mid-Low Range: 949-1206 rpm, 5.75 bhp
(C) Mid-High Range: 941-1176 rpm, 8.63 bhp
(D) High Range: 1014-1297 rpm, 11.50 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 10 — Fan Performance — 48PGF24 Vertical Supply/Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
652
699
746
794
842
891
940
990
1039
1089
Bhp
1.90
2.32
2.79
3.33
3.93
4.59
5.32
6.12
7.00
7.95
Rpm
719
Bhp
2.19
2.63
3.12
3.68
4.30
4.98
5.72
6.54
7.43
8.40
Rpm
779
Bhp
2.47
2.93
3.44
4.02
4.65
5.35
6.11
6.95
7.85
8.83
Rpm
833
Bhp
2.74
3.22
3.75
4.34
5.00
5.71
6.49
7.35
8.27
9.26
Rpm
884
Bhp
3.01
3.50
4.05
4.66
5.33
6.07
6.87
7.73
8.67
9.69
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
A
B
763
819
A
B
872
921
A
A
807
861
911
958
A
C
851
904
952
998
897
947
994
1038
1079
1121
1163
1207
1251
B
C
D
943
990
991
1036
1080
1124
1168
1213
B
C
1036
1082
1128
1174
C
D
C
D
1037
1085
1133
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
933
Bhp
3.27
3.79
4.35
4.98
5.67
6.42
7.23
8.12
9.07
10.10
Rpm
979
Bhp
3.54
4.07
4.65
5.29
5.99
6.76
7.59
8.49
9.46
10.51
Rpm
1023
1054
1087
1122
1158
1195
1234
1273
1314
1355
Bhp
3.80
4.35
4.94
5.60
6.32
7.10
7.95
8.87
9.85
10.91
Rpm
1066
1095
1127
1160
1195
1231
1269
1308
1347
1387
Bhp
4.06
4.62
5.24
5.91
6.64
7.44
8.30
9.23
10.24
11.31
Rpm
1108
1135
1165
1197
1231
1267
1303
1341
1379
—
Bhp
4.33
4.90
5.53
6.22
6.96
7.78
8.65
9.60
10.62
—
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
A
B
967
1011
1046
1082
1119
1158
1198
1238
1279
1321
B
D
B
C
D
B
B
1003
1041
1079
1119
1160
1202
1244
1287
C
D
C
D
C
D
LEGEND
Brake Horsepower Input to Fan
Bhp
—
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(A) Low Range: 685-939 rpm, 4.26 bhp (208/230 and 460-v), 751-954 rpm, 5.75 bhp (575-v)
(B) Mid-Low Range: 949-1206 rpm, 5.75 bhp
(C) Mid-High Range: 941-1176 rpm, 8.63 bhp
(D) High Range: 1014-1297 rpm, 11.50 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 11 — Fan Performance — 48PGD28 — Vertical Supply/Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
750
Bhp
2.28
2.78
3.34
3.97
4.68
5.46
6.32
7.26
8.28
9.40
10.61
11.91
13.32
Rpm
806
Bhp
2.62
3.17
3.78
4.48
5.25
6.10
7.04
8.07
9.20
10.42
11.74
13.17
—
Rpm
854
Bhp
2.93
3.50
4.15
4.88
5.69
6.59
7.59
8.67
9.86
11.15
12.54
—
Rpm
898
Bhp
3.25
3.84
4.51
5.26
6.10
7.04
8.07
9.19
10.43
11.76
13.21
—
Rpm
943
Bhp
3.59
4.18
4.87
5.64
6.50
7.46
8.52
9.68
10.95
12.33
—
6,500
7,000
A
B
B
C
A
B
797
853
899
941
982
A
B
B
7,500
8,000
8,500
845
900
945
985
1024
1067
1112
1157
1203
1249
1296
1342
—
892
948
991
1030
1076
1122
1169
1216
1263
1310
1357
—
939
995
1038
1085
1132
1180
1227
1274
1322
—
C
D
9,000
9,500
986
1042
1090
1137
1184
1232
1279
1326
—
C
D
1033
1079
1126
1172
1219
1265
1311
C
D
10,000
10,500
11,000
11,500
12,000
12,500
D
C
D
—
—
—
—
—
—
—
—
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
988
Bhp
3.97
4.56
5.25
6.03
6.91
7.89
8.97
10.16
11.45
12.86
—
Rpm
1035
1066
1101
1140
1180
1222
1266
1310
1355
—
Bhp
4.40
4.98
5.66
6.44
7.33
8.32
9.42
10.63
11.95
—
Rpm
1082
1109
1141
1176
1214
1255
1296
1340
1384
—
Bhp
4.87
5.43
6.10
6.88
7.77
8.77
9.88
11.10
12.44
—
Rpm
1130
1153
1181
1213
1249
1287
1327
1369
—
Bhp
5.39
5.94
6.59
7.36
8.24
9.24
10.36
11.59
—
Rpm
1177
1197
1222
1251
1283
1319
1357
1398
—
Bhp
5.95
6.48
7.12
7.87
8.74
9.74
10.86
12.09
—
6,500
7,000
7,500
B
C
C
D
1024
1063
1104
1146
1190
1235
1280
1326
1372
—
C
D
C
D
D
8,000
8,500
9,000
9,500
D
10,000
10,500
11,000
11,500
12,000
12,500
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Brake Horsepower Input to Fan
Bhp
—
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(A) Low Range: 687-873 rpm, 5.75 bhp
(B) Mid-Low Range: 805-1007 rpm, 5.75 bhp
(C) Mid-High Range: 941-1176 rpm, 8.63 bhp
(D) High Range: 1014-1297 rpm, 11.50 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 12 — Fan Performance — 48PGE28 — Vertical Supply/Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
775
Bhp
2.43
2.98
3.60
4.31
5.11
6.00
6.98
8.08
9.28
10.60
12.04
13.60
—
Rpm
825
Bhp
2.75
3.22
3.89
4.73
5.56
6.49
7.53
8.66
9.91
11.28
12.76
—
Rpm
871
Bhp
3.05
3.58
4.28
5.11
5.97
6.94
8.00
9.18
10.46
11.86
13.39
—
Rpm
915
Bhp
3.37
3.98
4.69
5.48
6.37
7.36
8.45
9.65
10.97
12.41
—
Rpm
959
Bhp
3.72
4.34
5.05
5.86
6.76
7.77
8.89
10.12
11.47
12.93
—
A
B
6,500
7,000
A
B
B
C
A
B
826
875
918
959
1000
1043
1088
1134
1181
1229
1278
1327
1376
—
B
C
D
7,500
8,000
8,500
878
925
966
1005
1052
1100
1148
1198
1247
1297
1347
—
929
975
1015
1064
1114
1164
1214
1265
1316
1367
—
981
1026
1076
1128
1179
1230
1282
1333
—
C
D
9,000
9,500
1033
1085
1137
1190
1242
1294
1347
—
C
D
D
C
D
10,000
10,500
11,000
11,500
12,000
12,500
—
—
—
—
—
—
—
—
—
—
—
—
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
1004
1041
1081
1124
1168
1214
1260
1308
1356
—
Bhp
4.11
4.73
5.44
6.26
7.17
8.20
9.33
10.58
11.95
—
Rpm
1050
1083
1120
1160
1202
1245
1290
1337
1384
—
Bhp
4.55
5.15
5.86
6.68
7.60
8.64
9.79
11.05
12.44
—
Rpm
1098
1126
1159
1196
1235
1277
1320
1365
—
Bhp
5.04
5.62
6.32
7.13
8.06
9.10
10.25
11.53
—
Rpm
1145
1170
1199
1233
1269
1309
1351
1394
—
Bhp
5.57
6.14
6.82
7.62
8.54
9.58
10.74
12.03
—
Rpm
1192
1214
1240
1270
1304
1341
1381
—
Bhp
6.14
6.70
7.36
8.15
9.05
10.09
11.25
—
6,500
7,000
7,500
B
C
C
D
C
D
D
C
D
8,000
8,500
9,000
9,500
D
10,000
10,500
11,000
11,500
12,000
12,500
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Brake Horsepower Input to Fan
Bhp
—
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(A) Low Range: 687-873 rpm, 5.75 bhp
(B) Mid-Low Range: 805-1007 rpm, 5.75 bhp
(C) Mid-High Range: 941-1176 rpm, 8.63 bhp
(D) High Range: 1014-1297 rpm, 11.50 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 13 — Fan Performance — 48PGF28 — Vertical Supply/Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
775
Bhp
2.43
2.98
3.60
4.31
5.11
6.00
6.98
8.08
9.28
10.60
12.04
13.60
—
Rpm
825
Bhp
2.75
3.22
3.89
4.73
5.56
6.49
7.53
8.66
9.91
11.28
12.76
—
Rpm
871
Bhp
3.05
3.58
4.28
5.11
5.97
6.94
8.00
9.18
10.46
11.86
13.39
—
Rpm
915
Bhp
3.37
3.98
4.69
5.48
6.37
7.36
8.45
9.65
10.97
12.41
—
Rpm
959
Bhp
3.72
4.34
5.05
5.86
6.76
7.77
8.89
10.12
11.47
12.93
—
A
B
6,500
7,000
A
B
B
C
A
B
826
875
918
B
C
D
959
1000
1043
1088
1134
1181
1229
1278
1327
1376
—
7,500
8,000
8,500
878
925
966
1005
1052
1100
1148
1198
1247
1297
1347
—
929
975
1015
1064
1114
1164
1214
1265
1316
1367
—
981
1026
1076
1128
1179
1230
1282
1333
—
C
D
9,000
9,500
1033
1085
1137
1190
1242
1294
1347
—
C
D
C
D
D
10,000
10,500
11,000
11,500
12,000
12,500
—
—
—
—
—
—
—
—
—
—
—
—
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
1004
1041
1081
1124
1168
1214
1260
1308
1356
—
Bhp
4.11
4.73
5.44
6.26
7.17
8.20
9.33
10.58
11.95
—
Rpm
1050
1083
1120
1160
1202
1245
1290
1337
1384
—
Bhp
4.55
5.15
5.86
6.68
7.60
8.64
9.79
11.05
12.44
—
Rpm
1098
1126
1159
1196
1235
1277
1320
1365
—
Bhp
5.04
5.62
6.32
7.13
8.06
9.10
10.25
11.53
—
Rpm
1145
1170
1199
1233
1269
1309
1351
1394
—
Bhp
5.57
6.14
6.82
7.62
8.54
9.58
10.74
12.03
—
Rpm
1192
1214
1240
1270
1304
1341
1381
—
Bhp
6.14
6.70
7.36
8.15
9.05
10.09
11.25
—
B
C
6,500
7,000
7,500
C
D
C
D
D
C
D
8,000
8,500
9,000
9,500
D
10,000
10,500
11,000
11,500
12,000
12,500
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Brake Horsepower Input to Fan
Bhp
—
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(A) Low Range: 687-873 rpm, 5.75 bhp
(B) Mid-Low Range: 805-1007 rpm, 5.75 bhp
(C) Mid-High Range: 941-1176 rpm, 8.63 bhp
(D) High Range: 1014-1297 rpm, 11.50 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 14 — Fan Performance — 48PGD20 — Horizontal Supply and Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
862
937
Bhp
2.65
3.26
3.58
4.48
5.52
6.71
8.07
9.60
—
Rpm
917
Bhp
2.93
3.56
3.96
4.89
5.96
7.18
8.57
—
Rpm
969
Bhp
3.21
3.53
4.35
5.31
6.41
7.66
9.08
—
Rpm
1019
1083
1149
1216
1285
1355
—
Bhp
3.17
3.90
4.75
5.73
6.86
8.14
—
Rpm
1066
1127
1191
1256
1323
1391
—
Bhp
3.52
4.28
5.16
6.17
7.32
8.63
—
5000
5500
6000
6500
7000
7500
8000
8500
9000
F
F
F
988
1036
1105
1175
1247
1319
1392
—
F
F
G
1013
1089
1166
1243
1320
1398
—
1060
1133
1207
1282
1356
—
G
H
G
H
G
H
H
G
H
—
—
—
—
—
—
—
—
—
—
—
—
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
1112
1171
1232
1295
1360
—
Bhp
3.88
4.67
5.57
6.61
7.80
—
Rpm
1156
1212
1271
1333
1396
—
Bhp
4.25
5.06
6.00
7.06
8.27
—
Rpm
1199
1253
1310
1369
—
Bhp
4.63
5.47
6.43
7.52
—
Rpm
1240
1292
1348
—
Bhp
5.02
5.88
6.87
—
Rpm
1280
1331
1384
—
Bhp
5.42
6.30
7.31
—
G
H
G
H
5000
5500
6000
6500
7000
7500
8000
8500
9000
F
G
F
G
H
G
H
H
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Bhp — Brake Horsepower Input to Fan
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(E) Low Range: Not Used
(F) Mid-Low Range: 896-1227 rpm, 4.26 bhp (208/230 and 460-v), 873-1108 rpm, 5.75 bhp (575-v)
(G) Mid-High Range: 1113-1414 rpm, 5.75 bhp
(H) High Range: 1096-1339 rpm, 8.63 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 15 — Fan Performance — 48PGE20 — Horizontal Supply and Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
875
952
Bhp
2.74
3.38
3.74
4.67
5.75
7.00
8.41
—
Rpm
931
Bhp
3.04
3.32
4.15
5.11
6.23
7.50
8.95
—
Rpm
984
1053
1123
1194
1266
1340
—
Bhp
3.34
3.70
4.56
5.56
6.71
8.01
—
Rpm
1035
1100
1167
1236
1306
1377
—
Bhp
3.33
4.09
4.98
6.01
7.19
8.53
—
Rpm
1083
1145
1210
1276
1344
—
Bhp
3.69
4.49
5.41
6.47
7.68
—
5000
5500
6000
6500
7000
7500
8000
8500
9000
F
F
F
G
H
F
1003
1077
1151
1226
1302
1378
—
F
G
H
1029
1106
1184
1262
1341
—-
G
H
G
H
G
H
—
—
—
—
—
—
—
—
—-
—
—
—
—
—
—
—
—
—
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
1130
1189
1251
1315
1381
—
Bhp
4.07
4.90
5.85
6.94
8.18
—
Rpm
1174
1232
1292
1354
—
Bhp
4.45
5.31
6.29
7.41
—
Rpm
1218
1273
1331
1391
—
Bhp
4.84
5.72
6.74
7.89
—
Rpm
1259
1313
1369
—
Bhp
5.23
6.15
7.19
—
Rpm
1300
1352
—
Bhp
5.63
6.58
—
5000
5500
6000
6500
7000
7500
8000
8500
9000
F
G
H
G
G
H
G
H
G
H
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Brake Horsepower Input to Fan
Bhp
—
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(E) Low Range: Not Used
(F) Mid-Low Range: 896-1227 rpm, 4.26 bhp (208/230 and 460-v), 873-1108 rpm, 5.75 bhp (575-v)
(G) Mid-High Range: 1113-1414 rpm, 5.75 bhp
(H) High Range: 1096-1339 rpm, 8.63 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 16 — Fan Performance — 48PGF20 — Horizontal Supply and Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
875
952
Bhp
2.74
3.38
3.74
4.67
5.75
7.00
8.41
—
Rpm
931
Bhp
3.04
3.32
4.15
5.11
6.23
7.50
8.95
—
Rpm
984
1053
1123
1194
1266
1340
—
Bhp
3.34
3.70
4.56
5.56
6.71
8.01
—
Rpm
1035
1100
1167
1236
1306
1377
—
Bhp
3.33
4.09
4.98
6.01
7.19
8.53
—
Rpm
1083
1145
1210
1276
1344
—
Bhp
3.69
4.49
5.41
6.47
7.68
—
5000
5500
6000
6500
7000
7500
8000
8500
9000
F
F
F
G
H
F
1003
1077
1151
1226
1302
1378
—
F
G
H
1029
1106
1184
1262
1341
—
G
H
G
H
G
H
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
1130
1189
1251
1315
1381
—
Bhp
4.07
4.90
5.85
6.94
8.18
—
Rpm
1174
1232
1292
1354
—
Bhp
4.45
5.31
6.29
7.41
—
Rpm
1218
1273
1331
1391
—
Bhp
4.84
5.72
6.74
7.89
—
Rpm
1259
1313
1369
—
Bhp
5.23
6.15
7.19
—
Rpm
1300
1352
—
Bhp
5.63
6.58
—
F
5000
5500
6000
6500
7000
7500
8000
8500
9000
G
G
H
G
H
G
H
G
H
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Brake Horsepower Input to Fan
Bhp
—
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(E) Low Range: Not Used
(F) Mid-Low Range: 896-1227 rpm, 4.26 bhp (208/230 and 460-v), 873-1108 rpm, 5.75 bhp (575-v)
(G) Mid-High Range: 1113-1414 rpm, 5.75 bhp
(H) High Range: 1096-1339 rpm, 8.63 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 17 — Fan Performance — 48PGD24 — Horizontal Supply and Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
937
Bhp
3.26
3.58
4.48
5.52
6.71
8.07
9.60
—
Rpm
988
1060
1133
1207
1282
1356
—
Bhp
3.56
3.96
4.89
5.96
7.18
8.57
—
Rpm
1036
1105
1175
1247
1319
1392
—
Bhp
3.53
4.35
5.31
6.41
7.66
9.08
—
Rpm
1083
1149
1216
1285
1355
—
Bhp
3.90
4.75
5.73
6.86
8.14
—
Rpm
1127
1191
1256
1323
1391
—
Bhp
4.28
5.16
6.17
7.32
8.63
—
F
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
F
F
G
H
G
H
F
1013
1089
1166
1243
1320
1398
—
G
H
G
H
G
H
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
1171
1232
1295
1360
—
Bhp
4.67
5.57
6.61
7.80
—
Rpm
1212
1271
1333
1396
—
Bhp
5.06
6.00
7.06
8.27
—
Rpm
1253
1310
1369
—
Bhp
5.47
6.43
7.52
—
Rpm
1292
1348
—
Bhp
5.88
6.87
—
Rpm
1331
1384
—
Bhp
6.30
7.31
—
G
H
G
H
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
H
G
H
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Brake Horsepower Input to Fan
Bhp
—
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(E) Low Range: Not Used
(F) Mid-Low Range: 896-1227 rpm, 4.26 bhp (208/230 and 460-v), 873-1108 rpm, 5.75 bhp (575-v)
(G) Mid-High Range: 1113-1414 rpm, 5.75 bhp
(H) High Range: 1096-1339 rpm, 8.63 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 18 — Fan Performance — 48PGE24 — Horizontal Supply and Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
952
1029
1106
1184
1262
1341
—
Bhp
3.38
3.74
4.67
5.75
7.00
8.41
—
Rpm
1003
1077
1151
1226
1302
1378
—
Bhp
3.32
4.15
5.11
6.23
7.50
8.95
—
Rpm
1053
1123
1194
1266
1340
—
Bhp
3.70
4.56
5.56
6.71
8.01
—
Rpm
1100
1167
1236
1306
1377
—
Bhp
4.09
4.98
6.01
7.19
8.53
—
Rpm
1145
1210
1276
1344
—
Bhp
4.49
5.41
6.47
7.68
—
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
F
G
H
F
F
F
G
H
G
H
G
H
G
H
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
1189
1251
1315
1381
—
Bhp
4.90
5.85
6.94
8.18
—
Rpm
1232
1292
1354
—
Bhp
5.31
6.29
7.41
—
Rpm
1273
1331
1391
—
Bhp
5.72
6.74
7.89
—
Rpm
1313
1369
—
Bhp
6.15
7.19
—
Rpm
1352
—
Bhp
6.58
—
G
H
G
H
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
G
H
H
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Brake Horsepower Input to Fan
Bhp
—
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(E) Low Range: Not Used
(F) Mid-Low Range: 896-1227 rpm, 4.26 bhp (208/230 and 460-v), 873-1108 rpm, 5.75 bhp (575-v)
(G) Mid-High Range: 1113-1414 rpm, 5.75 bhp
(H) High Range: 1096-1339 rpm, 8.63 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 19 — Fan Performance — 48PGF24 — Horizontal Supply and Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
952
1029
1106
1184
1262
1341
—
Bhp
3.38
3.74
4.67
5.75
7.00
8.41
—
Rpm
1003
1077
1151
1226
1302
1378
—
Bhp
3.32
4.15
5.11
6.23
7.50
8.95
—
Rpm
1053
1123
1194
1266
1340
—
Bhp
3.70
4.56
5.56
6.71
8.01
—
Rpm
1100
1167
1236
1306
1377
—
Bhp
4.09
4.98
6.01
7.19
8.53
—
Rpm
1145
1210
1276
1344
—
Bhp
4.49
5.41
6.47
7.68
—
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
F
G
H
F
F
F
G
H
G
H
G
H
G
H
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
1189
1251
1315
1381
—
Bhp
4.90
5.85
6.94
8.18
—
Rpm
1232
1292
1354
—
Bhp
5.31
6.29
7.41
—
Rpm
1273
1331
1391
—
Bhp
5.72
6.74
7.89
—
Rpm
1313
1369
—
Bhp
6.15
7.19
—
Rpm
1352
—
Bhp
6.58
—
G
H
G
H
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
G
H
H
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Brake Horsepower Input to Fan
Bhp
—
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(E) Low Range: Not Used
(F) Mid-Low Range: 896-1227 rpm, 4.26 bhp (208/230 and 460-v), 873-1108 rpm, 5.75 bhp (575-v)
(G) Mid-High Range: 1113-1414 rpm, 5.75 bhp
(H) High Range: 1096-1339 rpm, 8.63 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 20 — Fan Performance — 48PGD28 — Horizontal Supply and Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
786
Bhp
2.50
3.09
3.77
4.55
5.42
6.41
7.51
8.74
10.09
11.58
13.20
—
Rpm
819
Bhp
2.70
3.30
3.99
4.77
5.65
6.65
7.76
8.99
10.35
11.85
13.48
—
Rpm
857
Bhp
2.96
3.55
4.24
5.03
5.92
6.92
8.04
9.28
10.64
12.15
13.79
—
Rpm
899
Bhp
3.25
3.85
4.54
5.33
6.22
7.23
8.35
9.59
10.96
12.47
—
Rpm
943
Bhp
3.59
4.19
4.88
5.67
6.56
7.57
8.69
9.93
11.31
12.82
—
E
6,500
7,000
E
E
F
F
F
842
871
905
943
983
F
7,500
8,000
8,500
898
925
955
989
1026
1070
1117
1165
1215
1266
1318
1370
—
F
955
979
1007
1059
1113
1167
1221
1276
1332
1388
—
1037
1087
1138
1190
1243
1296
1350
—
G
H
1012
1069
1127
1184
1242
1299
1357
—
1034
1090
1146
1202
1258
1315
1372
—
G
H
G
H
G
H
9,000
9,500
G
H
10,000
10,500
11,000
11,500
12,000
12,500
—
—
—
—
—
—
—
—
—
—
—
—
—
—
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
988
Bhp
3.97
4.57
5.25
6.04
6.94
7.94
9.07
10.31
11.69
13.20
—
Rpm
1035
1066
1102
1140
1181
1225
1270
1316
1364
—
Bhp
4.39
4.98
5.66
6.45
7.34
8.35
9.47
10.72
12.10
—
Rpm
1082
1109
1141
1176
1215
1256
1298
1343
1389
—
Bhp
4.87
5.43
6.11
6.89
7.78
8.79
9.91
11.16
12.54
—
Rpm
1129
1153
1181
1213
1249
1287
1328
1370
—
Bhp
5.39
5.93
6.59
7.36
8.25
9.25
10.37
11.62
—
Rpm
1177
1197
1221
1250
1283
1319
1358
1399
—
Bhp
5.95
6.48
7.11
7.87
8.74
9.74
10.87
12.11
—
F
6,500
7,000
7,500
G
H
1024
1063
1105
1149
1194
1242
1290
1340
1391
—
G
H
G
H
H
G
8,000
8,500
9,000
9,500
H
10,000
10,500
11,000
11,500
12,000
12,500
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Brake Horsepower Input to Fan
Bhp
—
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(E) Low Range: 687-873 rpm, 5.75 bhp
(F) Mid-Low Range: 805-1007 rpm, 5.75 bhp
(G) Mid-High Range: 941-1176 rpm, 8.63 bhp
(H) High Range: 1014-1297 rpm, 11.50 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 21 — Fan Performance — 48PGE28 — Horizontal Supply and Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
799
Bhp
2.58
3.19
3.89
4.69
5.60
6.62
7.75
9.01
10.40
11.93
13.61
—
Rpm
833
887
941
996
1052
1108
1165
1222
1279
1337
—
Bhp
2.79
3.41
4.12
4.93
5.85
6.87
8.02
9.29
10.69
12.23
—
Rpm
872
Bhp
3.05
3.67
4.39
5.20
6.12
7.16
8.31
9.59
11.00
12.55
—
Rpm
914
Bhp
3.36
3.98
4.69
5.51
6.44
7.47
8.63
9.92
11.34
12.89
—
Rpm
958
Bhp
3.71
4.33
5.04
5.86
6.78
7.82
8.99
10.28
11.70
13.26
—
6,500
7,000
E
F
E
E
F
F
856
921
958
999
F
7,500
8,000
8,500
913
972
1006
1055
1106
1158
1211
1265
1319
1374
—
1042
F
971
1024
1078
1132
1187
1243
1299
1355
—
G 1088
1136
1029
1087
1145
1203
1261
1320
1378
—
G
H
G
H
G
H
G
H
9,000
9,500
1185
1236
1288
1341
1394
—
H
10,000
10,500
11,000
11,500
12,000
12,500
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
1005
1041
1080
1122
1167
1214
1262
1312
1363
—
Bhp
4.12
4.72
5.43
6.24
7.16
8.21
9.37
10.66
12.09
—
Rpm
1052
1084
1119
1158
1200
1244
1290
1338
1387
—
Bhp
4.57
5.16
5.86
6.66
7.58
8.62
9.78
11.08
12.51
—
Rpm
1100
1128
1160
1195
1234
1275
1319
1365
—
Bhp
5.06
5.64
6.33
7.13
8.04
9.07
10.23
11.52
—
Rpm
1148
1172
1201
1233
1269
1308
1349
1392
—
Bhp
5.60
6.17
6.84
7.63
8.53
9.56
10.71
12.00
—
Rpm
1195
1217
1242
1272
1304
1340
1379
—
Bhp
6.17
6.74
7.40
8.17
9.06
10.08
11.23
—
F
6,500
7,000
7,500
G
H
G
H
H
G
H
G
8,000
8,500
9,000
9,500
H
10,000
10,500
11,000
11,500
12,000
12,500
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Brake Horsepower Input to Fan
Bhp
—
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(E) Low Range: 687-873 rpm, 5.75 bhp
(F) Mid-Low Range: 805-1007 rpm, 5.75 bhp
(G) Mid-High Range: 941-1176 rpm, 8.63 bhp
(H) High Range: 1014-1297 rpm, 11.50 bhp
All other rpms require field-supplied motor or drive.
2. See page 36 for general fan performance notes.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 22 — Fan Performance — 48PGF28 — Horizontal Supply and Return Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
Rpm
799
Bhp
2.58
3.19
3.89
4.69
5.60
6.62
7.75
9.01
10.40
11.93
13.61
—
Rpm
833
887
941
996
1052
1108
1165
1222
1279
1337
—
Bhp
2.79
3.41
4.12
4.93
5.85
6.87
8.02
9.29
10.69
12.23
—
Rpm
872
Bhp
3.05
3.67
4.39
5.20
6.12
7.16
8.31
9.59
11.00
12.55
—
Rpm
914
Bhp
3.36
3.98
4.69
5.51
6.44
7.47
8.63
9.92
11.34
12.89
—
Rpm
958
Bhp
3.71
4.33
5.04
5.86
6.78
7.82
8.99
10.28
11.70
13.26
—
6,500
7,000
7,500
E
F
E
F
E
F
F
856
921
F
958
999
913
972
1006
1055
1106
1158
1211
1265
1319
1374
—
1042
1088
1136
1185
1236
1288
1341
1394
—
8,000
971
1024
1078
1132
1187
1243
1299
1355
—
G
8,500
9,000
9,500
1029
1087
1145
1203
1261
1320
1378
—
G
H
G
H
G
H
G
H
H
10,000
10,500
11,000
11,500
12,000
12,500
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
(Cfm)
1.2
1.4
1.8
2.0
Rpm
1005
1041
1080
1122
1167
1214
1262
1312
1363
—
Bhp
4.12
4.72
5.43
6.24
7.16
8.21
9.37
10.66
12.09
—
Rpm
1052
1084
1119
1158
1200
1244
1290
1338
1387
—
Bhp
4.57
5.16
5.86
6.66
7.58
8.62
9.78
11.08
12.51
—
Rpm
1100
1128
1160
1195
1234
1275
1319
1365
—
Bhp
5.06
5.64
6.33
7.13
8.04
9.07
10.23
11.52
—
Rpm
1148
1172
1201
1233
1269
1308
1349
1392
—
Bhp
5.60
6.17
6.84
7.63
8.53
9.56
10.71
12.00
—
Rpm
1195
1217
1242
1272
1304
1340
1379
—
Bhp
6.17
6.74
7.40
8.17
9.06
10.08
11.23
—
6,500
7,000
7,500
F
G
H
G
H
G
H
G
8,000
8,500
9,000
H
H
9,500
10,000
10,500
11,000
11,500
12,000
12,500
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Brake Horsepower Input to Fan
Bhp
—
Boldface indicates field-supplied motor/drive required.
NOTES:
1. Motor drive ranges:
(E) Low Range: 687-873 rpm, 5.75 bhp
(F) Mid-Low Range: 805-1007 rpm, 5.75 bhp
(G) Mid-High Range: 941-1176 rpm, 8.63 bhp
(H) High Range: 1014-1297 rpm, 11.50 bhp
All other rpms require field-supplied motor or drive.
2. See below for general fan performance notes.
GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES
1. Static pressure losses (i.e., economizer, electric heat, etc.) must be added
to external static pressure before entering Fan Performance table.
2. Interpolation is permissible. Do not extrapolate.
5. Use of a field-supplied motor may affect wire size. Recalculate the unit
power supply MCA and MOCP if required. Contact the local Carrier repre-
sentative for details.
3. Fan performance is based on wet coils, clean filters, and casing losses.
See Accessory/FIOP Static Pressure information on page 39.
6. Use the following formula to calculate Input Watts:
Input Watts = Bhp x (746/motor eff.)
4. Extensive motor and drive testing on these units ensures that the full
horsepower range of the motor can be utilized with confidence. Using the
fan motors up to the bhp rating shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 23 — Power Exhaust Fan Performance — 48PG20-28
LOW SPEED
230,460,575V
Bhp Watts ESP
MEDIUM SPEED
230,460,575V
Bhp Watts ESP Bhp Watts ESP
HIGH SPEED
230,460,575V
Bhp Watts ESP Bhp Watts
AIRFLOW
(Cfm)
208 V
Bhp Watts ESP
208 V
208 V
ESP
3250
3350
3450
3550
3650
3750
3850
3950
4050
4250
4450
4650
4850
5050
5250
5450
5650
5850
0.32
0.23
0.17
0.13
0.09
—
1.41
1.44
1.46
1.47
1.49
—
1580
1610
1635
1645
1665
—
0.70
0.63
0.59
0.56
0.53
0.51
0.48
0.45
0.40
—
1.49
1.52
1.55
1.56
1.58
1.60
1.62
1.64
1.67
—
1670
1700
1730
1745
1765
1790
1810
1835
1865
—
—
0.60
0.55
0.49
0.43
0.39
0.33
0.27
0.22
0.17
0.00
—
—
1.51
1.54
1.56
1.59
1.62
1.64
1.66
1.68
1.74
1.79
—
—
1690
1720
1750
1780
1815
1835
1860
1885
1945
2005
—
—
—
—
—
—
—
—
—
—
—
—
—
0.82
0.78
0.73
0.68
0.64
0.59
0.54
0.49
0.40
0.30
0.22
0.16
0.12
—
1.62
1.64
1.67
1.70
1.72
1.74
1.76
1.79
1.84
1.89
1.94
1.98
2.02
—
1810
1840
1870
1900
1930
1950
1975
2000
2060
2115
2170
2215
2260
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.60
0.56
0.51
0.41
0.31
0.20
0.11
0.04
—
1.85
1.87
1.89
1.92
1.97
2.04
2.09
2.13
—
2070
2095
2120
2145
2205
2280
2335
2385
—
0.73
0.69
0.65
0.56
0.47
0.37
0.30
0.23
0.17
0.12
0.07
0.04
1.99
2.01
2.04
2.06
2.12
2.19
2.24
2.28
2.33
2.38
2.40
2.42
2230
2255
2280
2310
2370
2450
2505
2555
2610
2665
2690
2710
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
ESP — External Static Pressure
Table 24 — Operation Air Quantity Limits
HEATING
(NAT. GAS,
VERTICAL)
Minimum Cfm
5522
HEATING
(NAT. GAS,
HEATING
(PROPANE,
VERTICAL)
Minimum Cfm
5522
HEATING
(PROPANE,
HORIZONTAL)
Minimum Cfm
4920
COOLING
48PG
GAS HEAT
HORIZONTAL)
Minimum Cfm
5522
Minimum Cfm
Maximum Cfm
High Heat (8 Cell)
Medium Heat (8 Cell)
Low Heat (5 Cell)
High Heat (8 Cell)
Medium Heat (8 Cell)
Low Heat (5 Cell)
High Heat (8 Cell)
Medium Heat (8 Cell)
Low Heat (5 Cell)
20
24
28
5000
9,000
4977
4218
5522
4977
4218
5522
4977
4218
4977
4218
5522
4977
4218
5470*
4977*
4218
4480
4218
5522
4480
4218
5522
4480
4218
4480
3796
4920
4480
5500
6500
10,000
12,000
3796
4920*
4480*
3796
*7000 cfm minimum recommended above 1.0 in. wg external static pressure.
Table 25 — Evaporator Fan Motor Specifications
48PG
DRIVE
ORIENTATION
MOTOR P/N NOMINAL HP
VOLTAGE
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
MAX WATTS
3698
3698
3698
4900
4900
4900
4900
4900
7267
7267
7267
7267
9582
9582
9582
9582
N/A
EFFICIENCY % MAX BHP MAX BkW
MAX AMPS
10.6
9.6
HD60FK651
HD60FK651
HD60FK651
HD60FK575
HD60FK653
HD60FK653
HD60FK653
HD60FK575
HD62FK652
HD62FK652
HD62FK652
HD62FK576
HD64FK651
HD64FK651
HD64FK651
HD64FK575
N/A
3.7
3.7
3.7
5
5
5
85.8
85.8
85.8
87.5
87.5
87.5
87.5
87.5
88.5
88.5
88.5
88.5
89.5
89.5
89.5
89.5
N/A
4.25
4.25
4.25
5.75
5.75
5.75
5.75
5.75
8.63
8.63
8.63
8.63
11.5
11.5
11.5
11.5
N/A
3.17
3.17
3.17
4.29
4.29
4.29
4.29
4.29
6.43
6.43
6.43
6.43
8.58
8.58
8.58
8.58
N/A
Low
Vertical
4.8
6.1
16.7
15.2
7.6
6.1
24.2
22
11
9
Mid-Low
Mid-High
High
Vertical
Vertical
5
5
7.5
7.5
7.5
7.5
10
10
10
10
N/A
N/A
N/A
N/A
3.7
3.7
3.7
5
30.8
28
14
Vertical
11
20
N/A
N/A
N/A
N/A
10.6
9.6
4.8
6.1
16.7
15.2
7.6
6.1
24.2
22
11
9
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Low
Horizontal
Horizontal
Horizontal
Horizontal
N/A
N/A
N/A
N/A
N/A
N/A
HD60FK651
HD60FK651
HD60FK651
HD60FK575
HD60FK653
HD60FK653
HD60FK653
HD60FK575
HD62FK652
HD62FK652
HD62FK652
HD62FK576
3698
3698
3698
4900
4900
4900
4900
4900
7267
7267
7267
7267
85.8
85.8
85.8
87.5
87.5
87.5
87.5
87.5
88.5
88.5
88.5
88.5
4.25
4.25
4.25
5.75
5.75
5.75
5.75
5.75
8.63
8.63
8.63
8.63
3.17
3.17
3.17
4.29
4.29
4.29
4.29
4.29
6.43
6.43
6.43
6.43
Mid-Low
Mid-High
High
5
5
5
5
7.5
7.5
7.5
7.5
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 25 — Evaporator Fan Motor Specifications (cont)
48PG
DRIVE
ORIENTATION
MOTOR P/N NOMINAL HP
VOLTAGE
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
208
230
460
575
MAX WATTS
3698
3698
3698
4900
4900
4900
4900
4900
7267
7267
7267
7267
9582
9582
9582
9582
N/A
EFFICIENCY % MAX BHP MAX BkW
MAX AMPS
10.6
9.6
HD60FK651
HD60FK651
HD60FK651
HD60FK575
HD60FK653
HD60FK653
HD60FK653
HD60FK575
HD62FK652
HD62FK652
HD62FK652
HD62FK576
HD64FK651
HD64FK651
HD64FK651
HD64FK575
N/A
3.7
3.7
3.7
5
5
5
85.8
85.8
85.8
87.5
87.5
87.5
87.5
87.5
88.5
88.5
88.5
88.5
89.5
89.5
89.5
89.5
N/A
4.25
4.25
4.25
5.75
5.75
5.75
5.75
5.75
8.63
8.63
8.63
8.63
11.5
11.5
11.5
11.5
N/A
3.17
3.17
3.17
4.29
4.29
4.29
4.29
4.29
6.43
6.43
6.43
6.43
8.58
8.58
8.58
8.58
N/A
Low
Vertical
4.8
6.1
16.7
15.2
7.6
6.1
24.2
22
11
9
Mid-Low
Mid-High
High
Vertical
Vertical
5
5
7.5
7.5
7.5
7.5
10
10
10
10
N/A
N/A
N/A
N/A
3.7
3.7
3.7
5
30.8
28
14
Vertical
11
24
N/A
N/A
N/A
N/A
10.6
9.6
4.8
6.1
16.7
15.2
7.6
6.1
24.2
22
11
9
16.7
15.2
7.6
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Low
Horizontal
Horizontal
Horizontal
Horizontal
Vertical
N/A
N/A
N/A
N/A
N/A
N/A
HD60FK651
HD60FK651
HD60FK651
HD60FK575
HD60FK653
HD60FK653
HD60FK653
HD60FK575
HD62FK652
HD62FK652
HD62FK652
HD62FK576
HD60FK653
HD60FK653
HD60FK653
HD60FK575
HD60FK653
HD60FK653
HD60FK653
HD60FK575
HD62FK652
HD62FK652
HD62FK652
HD62FK576
HD64FK651
HD64FK651
HD64FK651
HD64FK575
HD60FK653
HD60FK653
HD60FK653
HD60FK575
HD60FK653
HD60FK653
HD60FK653
HD60FK575
HD62FK652
HD62FK652
HD62FK652
HD62FK576
HD64FK651
HD64FK651
HD64FK651
HD64FK575
3698
3698
3698
4900
4900
4900
4900
4900
7267
7267
7267
7267
4900
4900
4900
4900
4900
4900
4900
4900
7267
7267
7267
7267
9582
9582
9582
9582
4900
4900
4900
4900
4900
4900
4900
4900
7267
7267
7267
7267
9582
9582
9582
9582
85.8
85.8
85.8
87.5
87.5
87.5
87.5
87.5
88.5
88.5
88.5
88.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
88.5
88.5
88.5
88.5
89.5
89.5
89.5
89.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
87.5
88.5
88.5
88.5
88.5
89.5
89.5
89.5
89.5
4.25
4.25
4.25
5.75
5.75
5.75
5.75
5.75
8.63
8.63
8.63
8.63
5.75
5.75
5.75
5.75
5.75
5.75
5.75
5.75
8.63
8.63
8.63
8.63
11.5
11.5
11.5
11.5
5.75
5.75
5.75
5.75
5.75
5.75
5.75
5.75
8.63
8.63
8.63
8.63
11.5
11.5
11.5
11.5
3.17
3.17
3.17
4.29
4.29
4.29
4.29
4.29
6.43
6.43
6.43
6.43
4.29
4.29
4.29
4.29
4.29
4.29
4.29
4.29
6.43
6.43
6.43
6.43
8.58
8.58
8.58
8.58
4.29
4.29
4.29
4.29
4.29
4.29
4.29
4.29
6.43
6.43
6.43
6.43
8.58
8.58
8.58
8.58
Mid-Low
Mid-High
High
5
5
5
5
7.5
7.5
7.5
7.5
5
5
5
5
5
5
5
5
Low
6.1
16.7
15.2
7.6
6.1
24.2
22
11
9
30.8
28
14
Mid-Low
Mid-High
High
Vertical
7.5
7.5
7.5
7.5
10
10
10
10
5
5
5
5
5
Vertical
Vertical
11
28
16.7
15.2
7.6
Low
Horizontal
Horizontal
Horizontal
Horizontal
6.1
16.7
15.2
7.6
6.1
24.2
22
11
9
30.8
28
14
5
5
5
Mid-Low
Mid-High
High
7.5
7.5
7.5
7.5
10
10
10
10
11
NOTES:
1. Extensive motor and electrical testing ensures that the motors can be uti-
lized with confidence up to the maximum applied bhp, watts, and amps.
Using the fan motor up to the maximum ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be affected.
2. All indoor-fan motors 5 hp and larger meet the minimum efficiency require-
ments as established by the Energy Policy Act of 1992 (EPACT) effective
October 24, 1997.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 26 — Accessory/FIOP Static Pressure (in. wg)* — 48PG20-28
CFM
COMPONENT
4,000 4,500 5,000 5,500 6,000 6,500 7,000 7,500 8,000
Economizer
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
CFM
8,500 9,000 9,500 10,000 10,500 11,000 11,500 12,000
0.11 0.12 0.13 0.15 0.16 0.17 0.19 0.20
COMPONENT
Economizer
LEGEND
Factory-Installed Option
FIOP
—
*The static pressure must be added to the external static pressure. The sum and the evaporator
entering-air cfm should then be used in conjunction with the Fan Performance tables to deter-
mine blower rpm and watts.
Table 27 — Fan Rpm at Motor Pulley Settings*
MOTOR PULLEY TURNS OPEN
UNIT
DRIVE
1
48PG
0
/
2
1
11/2
749
1013
1000
1085
n/a
2
21/2
3
31/2
4
854
41/2
876
1142
1117
1226
n/a
5
897
1163
1137
1250
n/a
51/2
918
1185
1156
1273
n/a
6
939
1206
1176
1297
n/a
Low
Mid-Low
Mid-High
High
685
949
941
1014
n/a
706
970
961
1038
n/a
727
992
980
1061
n/a
770
791
812
833
1035
1019
1108
n/a
1056
1039
1132
n/a
1078
1059
1156
n/a
1099
1078
1179
n/a
1120
1098
1203
n/a
20 and 24
(230 and 460 volt)
Low
Mid-Low
Mid-High
High
896
1113
1096
751
949
941
1014
n/a
924
951
1163
1137
785
992
980
1061
n/a
979
1006
1213
1177
819
1035
1019
1108
n/a
1034
1238
1197
836
1056
1039
1132
n/a
1062
1264
1218
853
1078
1059
1156
n/a
1089
1289
1238
869
1099
1078
1179
n/a
1117
1314
1258
886
1120
1098
1203
n/a
1144
1339
1278
903
1142
1117
1226
n/a
1172
1364
1299
920
1163
1137
1250
n/a
1199
1389
1319
937
1185
1156
1273
n/a
1227
1414
1339
954
1206
1176
1297
n/a
1138
1116
768
970
961
1188
1157
802
1013
1000
1085
n/a
Low
Mid-Low
Mid-High
High
1038
n/a
20 and 24
(575 volt)
Low
Mid-Low
Mid-High
High
873
1113
1096
687
805
941
1014
687
805
941
1014
893
912
1163
1137
718
839
980
1061
718
839
980
1061
932
951
971
991
1010
1289
1238
796
1030
1314
1258
811
1049
1339
1278
827
1069
1364
1299
842
1088
1389
1319
858
1108
1414
1339
873
1007
1176
1297
873
1138
1116
703
822
961
1038
703
822
961
1038
1188
1157
734
1213
1177
749
1238
1197
765
1264
1218
780
Low
Mid-Low
Mid-High
High
856
872
889
906
923
940
957
973
990
1000
1085
734
856
1000
1085
1019
1108
749
872
1019
1108
1039
1132
765
889
1039
1132
1059
1156
780
906
1059
1156
1078
1179
796
923
1078
1179
1098
1203
811
940
1098
1203
1117
1226
827
957
1117
1226
1137
1250
842
973
1137
1250
1156
1273
858
990
1156
1273
28
(all voltages)
Low
Mid-Low
Mid-High
High
1007
1176
1297
LEGEND
*Approximate fan rpm shown.
NOTE: Factory pulley speed setting is at 3 turns open.
n/a — not available
ECONOMI$ER IV CONTROLLER WIRING AND OPER-
ATIONAL MODES — Determine the EconoMi$er IV control
mode before set up of the control. Some modes of operation may
require different sensors. Refer to Table 28. The EconoMi$er IV
is supplied from the factory with a mixed-air temperature
sensor and an outdoor air temperature sensor. This allows for
operation of the EconoMi$er IV with outdoor air dry bulb
changeover control. Additional accessories can be added to
allow for different types of changeover control and operation
of the EconoMi$er IV and unit.
Outdoor Dry Bulb Changeover — The standard controller is
shipped from the factory configured for outdoor dry bulb
changeover control. The outdoor air and mixed-air temperature
sensors are included as standard. For this control mode, the out-
door temperature is compared to an adjustable set point selected
on the control. If the outdoor-air temperature is above the set
point, the EconoMi$er IV will adjust the outdoor-air dampers to
minimum position. If the outdoor-air temperature is below the
set point, the position of the outdoor-air dampers will be con-
trolled to provided free cooling using outdoor air. When in this
mode, the LED next to the free cooling set point potentiometer
will be on. The changeover temperature set point is controlled
by the free cooling set point potentiometer located on the con-
trol. The scale on the potentiometer is A, B, C, and D. See
Fig. 25 for the corresponding temperature changeover values.
Optional EconoMi$er IV — See Fig. 23 for EconoMi$er
IV component locations. The optional EconoMi$er IV comes
from the factory fully wired and assembled. No field wiring or
assembly is required for standard outdoor dry bulb changeover
operation. Field wiring of accessory sensors is required for
different operational modes.
ECONOMI$ER IV STANDARD SENSORS
Outdoor Air Temperature (OAT) Sensor — The outdoor air
temperature sensor is a 10 to 20 mA device used to measure the
outdoor-air temperature. The outdoor-air temperature is used to
determine when the EconoMi$er IV can be used for free
cooling. The sensor is factory-installed on the EconoMi$er IV
in the outdoor airstream. See Fig. 24. The operating range of
temperature measurement is 40 to 100 F.
Mixed-Air Temperature (MAT) Sensor — The mixed-air
temperature sensor is a 3 K thermistor located at the outlet of
the indoor fan. See Fig. 24. This sensor is factory installed. The
operating range of temperature measurement is 0° to 158 F.
The temperature sensor is a short probe with blue wires
running to it.
Outdoor Air Lockout Sensor — The Economi$er IV is
equipped with an ambient temperature lockout switch located
in the outdoor airstream which is used to lock out the compres-
sors below a 42 F ambient temperature.
39
Download from Www.Somanuals.com. All Manuals Search And Download.
DAMPER
ASSEMBLY
WIRE
HARNESS
DAMPER
ACTUATOR
WIRE TIES
PL7
PL7
OUTSIDE AIR
ENTHALPY
ECONOMIZER
BLOCK OFF
INDOOR AIR
ENTHALPY
Fig. 23 — EconoMi$er IV Component Locations (Exploded View)
19
LED ON
18
D
17
LED ON
LED OFF
16
15
14
C
LED ON
LED OFF
B
13
12
LED ON
LED OFF
MAT LOCATION
A
11
10
9
LED OFF
85 90
95
OAT LOCATION
100
50
55 60
70 75
40 45
65
80
DEGREES FAHRENHEIT
Fig. 24 — Sensor Locations (OAT and MAT)
Fig. 25 — Temperature Changeover Set Points
Table 28 — EconoMi$er IV Sensor Usage
ECONOMI$ER IV WITH OUTDOOR AIR
ECONOMI$ER IV WITH SINGLE
ENTHALPY SENSOR
DRY BULB SENSOR
Accessories Required
APPLICATION
Accessories Required
CRTEMPSN002A00*
Outdoor Air Dry Bulb
Differential Dry Bulb
Single Enthalpy
None. The outdoor air dry bulb sensor is factory installed.
CRTEMPSN002A00*
(2) CRTEMPSN002A00*
HH57AC078
None. The single enthalpy sensor is factory installed.
HH57AC078
and
CRENTDIF004A00*
Differential Enthalpy
CRENTDIF004A00*
CO2 for DCV Control using a
Wall-Mounted CO2 Sensor
33ZCSENCO2
33ZCSENCO2
33ZCSENCO2†
33ZCSENCO2†
CO2 for DCV Control using a
Duct-Mounted CO2 Sensor
and
CRCBDIOX005A00††
and
CRCBDIOX005A00††
33ZCASPCO2**
33ZCASPCO2**
*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As such, these kits may contain parts that will not be
needed for installation.
†33ZCSENCO2 is an accessory CO2 sensor.
**33ZCASPCO2 is an accessory aspirator box required for duct-mounted applications.
††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2 accessories.
40
Download from Www.Somanuals.com. All Manuals Search And Download.
Differential Dry Bulb Control — For differential dry bulb
control the standard outdoor dry bulb sensor is used in conjunc-
tion with an additional accessory dry bulb sensor (part number
CRTEMPSN002A00). The accessory sensor must be mounted
in the return airstream. Wiring is provided in the EconoMi$er
IV wiring harness. See Fig. 26.
In this mode of operation, the outdoor-air temperature is
compared to the return-air temperature and the lower tempera-
ture airstream is used for cooling. When using this mode of
changeover control, turn the enthalpy set point potentiometer
fully clockwise to the D setting.
Outdoor Enthalpy Changeover — For enthalpy control, acces-
sory enthalpy sensor (part number HH57AC078) is required.
Replace the standard outdoor dry bulb temperature sensor with
the accessory enthalpy sensor in the same mounting location.
When the outdoor air enthalpy rises above the outdoor enthalpy
changeover set point, the outdoor-air damper moves to its mini-
mum position. The outdoor enthalpy changeover set point is set
with the outdoor enthalpy set point potentiometer on the
EconoMi$er IV controller. The set points are A, B, C, and D.
See Fig. 27. The factory-installed 620-ohm jumper must be in
place across terminals SR and + on the EconoMi$er IV control-
ler. See Fig. 26.
Differential Enthalpy Control — For differential enthalpy
control, the EconoMi$er IV controller uses two enthalpy
sensors (HH57AC078 and CRENTDIF004A00), one in the
outside air and one in the return air duct. The EconoMi$er IV
controller compares the outdoor air enthalpy to the return air
enthalpy to determine EconoMi$er IV use. The controller
selects the lower enthalpy air (return or outdoor) for cooling.
For example, when the outdoor air has a lower enthalpy than
the return air, the EconoMi$er IV opens to bring in outdoor air
for free cooling.
Replace the standard outside air dry bulb temperature
sensor with the accessory enthalpy sensor in the same mount-
ing location. Mount the return air enthalpy sensor in the return
air duct. Wiring is provided in the EconoMi$er IV wiring
harness. See Fig. 26. The outdoor enthalpy changeover set
point is set with the outdoor enthalpy set point potentiometer
on the EconoMi$er IV controller. When using this mode of
changeover control, turn the enthalpy setpoint potentiometer
fully clockwise to the D setting. See Fig. 28.
Indoor Air Quality (IAQ) Sensor Input — The IAQ input
can be used for demand control ventilation control based on the
level of CO2 measured in the space or return air duct.
Mount the optional IAQ sensor according to manufacturer
specifications. The IAQ sensor should be wired to the AQ and
AQ1 terminals of the controller. Adjust the DCV (demand
controlled ventilation) potentiometers to correspond to the
DCV voltage output of the indoor air quality sensor at the
user-determined set point. See Fig. 29.
If a separate field-supplied transformer is used to power the
IAQ sensor, the sensor must not be grounded or the
EconoMi$er IV control board will be damaged.
Exhaust Set Point Adjustment — The exhaust set point will
determine when the exhaust fan runs based on damper position
(if accessory power exhaust is installed). The set point is modi-
fied with the Exhaust Fan Set Point (EXH SET) potentiometer.
See Fig. 28. The set point represents the damper position above
which the exhaust fans will be turned on. When there is a call
for exhaust, the EconoMi$er IV controller provides a 45 15
second delay before exhaust fan activation to allow the damp-
ers to open. This delay allows the damper to reach the appro-
priate position to avoid unnecessary fan overload.
Fig. 26 — EconoMi$er IV Wiring
41
Download from Www.Somanuals.com. All Manuals Search And Download.
85
90
95 100 105 110
(29) (32) (35) (38) (41) (43)
CONTROL CONTROL POINT
CURVE
APPROX. °F (°C)
AT 50% RH
80
(27)
A
B
C
D
73 (23)
70 (21)
67 (19)
63 (17)
75
(24)
70
(21)
65
(18)
60
(16)
A
55
(13)
B
50
(10)
C
45
(7)
D
40
(4)
35
(2)
A
B
C
D
HIGH LIMIT
CURVE
35
40
45
50
55
60
65
70
75
80
85
90
95 100 105 110
(2)
(4) (7) (10) (13) (16) (18) (21) (24) (27) (29) (32) (35) (38) (41) (43)
APPROXIMATE DRY BULB TEMPERATURE— °F (°C)
Fig. 27 — Enthalpy Changeover Set Points
CO SENSOR MAX RANGE SETTING
2
6000
5000
4000
3000
2000
1000
0
800 ppm
900 ppm
1000 ppm
1100 ppm
2
3
4
5
6
7
8
DAMPER VOLTAGE FOR MAX VENTILATION RATE
Fig. 29 — CO2 Sensor Maximum Range Setting
Fig. 28 — EconoMi$er IV Controller Potentiometer
and LED Locations
42
Download from Www.Somanuals.com. All Manuals Search And Download.
Minimum Position Control — There is a minimum damper
position potentiometer on the EconoMi$er IV controller. See
Fig. 28. The minimum damper position maintains the mini-
mum airflow into the building during the occupied period.
When using demand ventilation, the minimum damper
position represents the minimum ventilation position for VOC
(volatile organic compounds) ventilation requirements. The
maximum demand ventilation position is used for fully occu-
pied ventilation.
When demand ventilation control is not being used, the
minimum position potentimeter should be used to set the occu-
pied ventilation position. The maximum demand ventilation
position should be turned fully clockwise.
Adjust the minimum position potentiometer to allow the
minimum amount of outdoor air, as required by local codes, to
enter the building. Make minimum position adjustments with
at least 10° F temperature difference between the outdoor and
return-air temperatures. To determine the minimum position
setting, perform the following procedure:
Demand Control Ventilation — When using the Econo-
Mi$er IV for demand control ventilation, there are some equip-
ment selection criteria which should be considered. When
selecting the heat capacity and cool capacity of the equipment,
the maximum ventilation rate must be evaluated for design
conditions. The maximum damper position must be calculated
to provide the desired fresh air.
Typically the maximum ventilation rate will be about 5 to
10% more than the typical cfm required per person, using nor-
mal outside air design criteria.
A proportional anticipatory strategy should be taken with
the following conditions: a zone with a large area, varied
occupancy, and equipment that cannot exceed the required
ventilation rate at design conditions. Exceeding the required
ventilation rate means the equipment can condition air at a
maximum ventilation rate that is greater than the required
ventilation rate for maximum occupancy. A proportional-
anticipatory strategy will cause the fresh air supplied to
increase as the room CO2 level increases even though the CO2
set point has not been reached. By the time the CO2 level
reaches the set point, the damper will be at maximum ventila-
tion and should maintain the set point.
In order to have the CO2 sensor control the economizer
damper in this manner, first determine the damper voltage
output for minimum or base ventilation. Base ventilation is the
ventilation required to remove contaminants during unoccu-
pied periods. The following equation may be used to determine
the percent of outside-air entering the building for a given
damper position. For best results there should be at least a
10 degree difference in outside and return-air temperatures.
1. Calculate the appropriate mixed air temperature using the
following formula:
(TO x OA) + (TR x RA) = TM
TO = Outdoor-Air Temperature
OA = Percent of Outdoor Air
TR = Return-Air Temperature
RA = Percent of Return Air
TM = Mixed-Air Temperature
As an example, if local codes require 10% outdoor air
during occupied conditions, outdoor-air temperature is
60 F, and return-air temperature is 75 F.
(TO x OA) + (TR x RA) = TM
TO = Outdoor-Air Temperature
OA = Percent of Outdoor Air
TR = Return-Air Temperature
RA = Percent of Return Air
TM = Mixed-Air Temperature
(60 x .10) + (75 x .90) = 73.5 F
2. Disconnect the mixed air sensor from terminals T and T1.
3. Ensure that the factory-installed jumper is in place across
terminals P and P1. If remote damper positioning is being
used, make sure that the terminals are wired according to
Fig. 26 and that the minimum position potentiometer is
turned fully clockwise.
Once base ventilation has been determined, set the mini-
mum damper position potentiometer to the correct position.
4. Connect 24 vac across terminals TR and TR1.
The same equation can be used to determine the occupied or
maximum ventilation rate to the building. For example, an
output of 3.6 volts to the actuator provides a base ventilation
rate of 5% and an output of 6.7 volts provides the maximum
ventilation rate of 20% (or base plus 15 cfm per person). Use
Fig. 29 to determine the maximum setting of the CO2 sensor.
For example, a 1100 ppm set point relates to a 15 cfm per
person design. Use the 1100 ppm curve on Fig. 29 to find the
point when the CO2 sensor output will be 6.7 volts. Line up the
point on the graph with the left side of the chart to determine
that the range configuration for the CO2 sensor should be 1800
ppm. The EconoMi$er IV controller will output the 6.7 volts
from the CO2 sensor to the actuator when the CO2 concentra-
tion in the space is at 1100 ppm. The DCV set point may be left
at 2 volts since the CO2 sensor voltage will be ignored by the
EconoMi$er IV controller until it rises above the 3.6 volt
setting of the minimum position potentiometer.
5. Carefully adjust the minimum position potentiometer
until the measured mixed air temperature matches the
calculated value.
6. Reconnect the mixed air sensor to terminals T and T1.
Remote control of the EconoMi$er IV damper is desirable
when requiring additional temporary ventilation. If
field-supplied remote potentiometer (Honeywell part number
S963B1128) is wired to the EconoMi$er IV controller, the
minimum position of the damper can be controlled from a re-
mote location.
To control the minimum damper position remotely, remove
the factory-installed jumper on the P and P1 terminals on the
EconoMi$er IV controller. Wire the field-supplied potentiome-
ter to the P and P1 terminals on the EconoMi$er IV controller.
See Fig. 26.
a
Once the fully occupied damper position has been deter-
mined, set the maximum damper demand control ventilation
potentiometer to this position. Do not set to the maximum
position as this can result in over-ventilation to the space and
potential high-humidity levels.
CO2 Sensor Configuration — The CO2 sensor has preset
standard voltage settings that can be selected anytime after the
sensor is powered up. See Table 29.
Use setting 1 or 2 for Carrier equipment. See Table 29.
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
Damper Movement — When the EconoMi$er IV board re-
ceives initial power, it can take the damper up to 21/2 minutes
before it begins to position itself. After the initial positioning,
subsequent changes to damper position will take up to 30 sec-
onds to initiate. Damper movement from full open to full
closed (or vice versa) takes 21/2 minutes.
Thermostats — The EconoMi$er IV control works with con-
ventional thermostats that have a Y1 (cool stage 1), Y2 (cool
stage 2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The
EconoMi$er IV control does not support space temperature
sensors like the T55 or T56. Connections are made at the ther-
mostat terminal connection board located in the main control
box.
2. Press Mode twice. The STDSET Menu will appear.
43
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Use the Up/Down button to select the preset number. See
Table 29.
4. Press Enter to lock in the selection.
outside air. The design should produce an air temperature
somewhat near room conditions to prevent reheat of the air
mixture. The energy recovery device should be interlocked
with the heat to turn off the device when in the heat mode.
5. Press Mode to exit and resume normal operation.
Operating Sequence
The custom settings of the CO2 sensor can be changed any-
time after the sensor is energized. Follow the steps below to
change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD menu
and press Enter.
COOLING, UNITS WITHOUT ECONOMIZER — When
the thermostat calls for one stage of cooling, Y1 and G are en-
ergized. The indoor-fan contactor (IFC) and compressor con-
tactor(s) (C.A1 and C.B1 on three-compressor units or C.A1
only on two-compressor units), and outdoor-fan contactors
(OFC1 and OFC2 when outdoor temperature is above LTS set-
ting) are energized and the indoor-fan motor, compressor(s)
(A1 and B1 on three compressor units or A1 only on two-
compressor units), and outdoor fans controlled by OFC1 are
started. If the outdoor temperature is above the setting of the
low temperature switch, the outdoor fans controlled by OFC2
are also started.
4. Use the Up/Down button to toggle through each of the
nine variables, starting with Altitude, until the desired
setting is reached.
5. Press Mode to move through the variables.
If more cooling is required, the thermostat will call for a
second stage of cooling, energizing Y2. This will allow relay
CR1 to energize, which in turn energizes the compressor
contactor (C.C1 on three-compressor units or C.B1 on
two-compressor units). The second stage compressor (C1 on
three-compressor units or B1 on two-compressor units is then
started.
6. Press Enter to lock in the selection, then press Mode to
continue to the next variable.
Dehumidification of Fresh Air with DCV Control — Infor-
mation from ASHRAE (American Society of Heating,
Refrigeration, and Air Conditioning Engineers) indicates that
the largest humidity load on any zone is the fresh air intro-
duced. For some applications, a device such as a 62AQ energy
recovery unit is added to reduce the moisture content of the
fresh air being brought into the building when the enthalpy is
high. In most cases, the normal heating and cooling processes
are more than adequate to remove the humidity loads for most
commercial applications.
This makes the control of the of the dehumidification device
simple when using the enthalpy or differential enthalpy sensor.
The enthalpy sensor or differential enthalpy sensor is installed
on the equipment to determine economizer operation. The
high enthalpy signal from the enthalpy sensor or differential
enthalpy sensor can be used to turn on the outdoor air moisture
removal device any time fresh air is required for the space.
HEATING, UNITS WITHOUT ECONOMIZER
NOTE: The 48PG20-28 units have 2 stages of heat.
When the thermostat calls for heating, power is sent to W
on the IGC (integrated gas unit controller) board. An LED
(light-emitting diode) on the IGC board will be on during nor-
mal operation. A check is made to ensure that the rollout
switch and limit switch are closed and the induced-draft motor
is running. The induced-draft motor is then energized, and
when speed is proven with the hall effect sensor on the motor,
the ignition activation period begins. The burners will ignite
within 5 seconds.
If the burners do not light, there is a 22-second delay before
another 5-second attempt. If the burners still do not light, this
sequence is repeated for 15 minutes. After the 15 minutes have
elapsed, if the burners still have not lit, heating is locked out.
To reset the control, break 24-v power to the thermostat.
The energy recovery device should be sized for maximum
latent and sensible conditioning at maximum ventilation on a
design day. A calculation for leaving-air temperature on a low
ambient, low ventilation day should also be done to determine
the mixed-air temperature of the return and pre-conditioned
Table 29 — CO2 Sensor Standard Settings
VENTILATION
RATE
(cfm/Person)
CO2
OPTIONAL
RELAY
ANALOG
OUTPUT
SETTING
EQUIPMENT
OUTPUT
CONTROL RANGE RELAY SETPOINT HYSTERESIS
(ppm)
(ppm)
(ppm)
0-10V
1
2
3
4
5
6
7
8
9
Proportional
Proportional
Exponential
Proportional
Proportional
Exponential
Exponential
Proportional
Proportional
Any
Any
Any
15
0-2000
1000
50
4-20 mA
Interface w/Standard
2-10V
7-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-2000
0-2000
0-1100
0- 900
0-1100
0- 900
0-9999
0-2000
1000
1100
1100
900
50
50
Building Control System
50
20
50
Economizer
15
1100
900
50
20
50
Health & Safety
—
5000
700
500
50
Parking/Air Intakes/
Loading Docks
—
LEGEND
PPM — Parts Per Million
44
Download from Www.Somanuals.com. All Manuals Search And Download.
When ignition occurs the IGC board will continue to moni-
tor the condition of the rollout and limit switches, the hall effect
sensor, as well as the flame sensor. If the unit is controlled
through a room thermostat set for fan auto., 45 seconds after
ignition occurs, the indoor-fan motor will be energized (and the
outdoor-air dampers will open to their minimum position). If
for some reason the overtemperature limit opens prior to the
start of the indoor fan blower, on the next attempt, the
45-second delay will be shortened to 5 seconds less than the
time from initiation of heat to when the limit tripped. Gas will
not be interrupted to the burners and heating will continue.
Once modified, the fan on delay will not change back to
45 seconds unless power is reset to the control.
When additional heat is required, W2 closes and initiates
power to the second stage of the main gas valve. When the
thermostat is satisfied, W1 and W2 open and the gas valve
closes, interrupting the flow of gas to the main burners. If the
call for W1 lasted less than 1 minute, the heating cycle will not
terminate until 1 minute after W1 became active. If the unit is
controlled through a room thermostat set for fan auto., the
indoor-fan motor will continue to operate for an additional
45 seconds then stop (and the outdoor-air dampers will close).
If the overtemperature limit opens after the indoor motor is
stopped within 10 minutes of W1 becoming inactive, on the
next cycle the time will be extended by 15 seconds. The
maximum delay is 3 minutes. Once modified, the fan off delay
will not change back to 45 seconds unless power is reset to
the control.
On the initial power to the EconoMi$er IV control, it will
take the damper up to 21/2 minutes before it begins to position
itself. Any change in damper position will take up to 30 sec-
onds to initiate. Damper movement from full closed to full
open (or vice versa) will take between 11/2 and 21/2 minutes.
If free cooling can be used as determined from the appropri-
ate changeover command (switch, dry bulb, enthalpy curve,
differential dry bulb, or differential enthalpy), then the control
will modulate the dampers open to maintain the mixed-air tem-
perature set point at 50 to 55 F.
If there is a further demand for cooling (cooling second
stage — Y2 is energized), then the control will bring on
compressor stage 1 to maintain the mixed-air temperature set
point. The EconoMi$er IV damper will be open at maximum
position. EconoMi$er IV operation is limited to a single
compressor.
HEATING, UNITS WITH ECONOMI$ER IV — When
the room temperature calls for heat, the heating controls are
energized as described in the Heating, Units Without Econo-
mizer section. The IFM is energized and the EconoMi$er IV
damper modulates to the minimum position. When the thermo-
stat is satisfied and W1 and W2 are deenergized, the IFM
continues to run, and the economizer damper modulates to the
minimum position.
SUBCOOLER HEAT EXCHANGER (SHX) — The purpose
of the subcooler heat exchanger (SHX) and the subcooler TXV
is to increase the capacity of the evaporator by sending
subcooled liquid refrigerant into the evaporator. Normally, the
condenser subcools the liquid refrigerant by approximately
10 F. The SHX adds another 10 F to 15 F degrees of subcooling
before the refrigerant reaches the evaporator. This allows the
refrigerant to absorb more heat from the mixed air, thereby
providing more cooling capacity.
A LED indicator is provided on the IGC to monitor opera-
tion. The IGC is located by removing the side panel and view-
ing the IGC through the view port located in the control box
access panel. During normal operation, the LED is continuous-
ly on. For information on troubleshooting refer to page 57.
COOLING, UNITS WITH ECONOMI$ER IV — When free
cooling is not available, the compressors will be controlled by
the zone thermostat. When free cooling is available, the
outdoor-air damper is modulated by the EconoMi$er IV
control to provide a 50 to 55 F mixed-air temperature into the
zone. As the mixed-air temperature fluctuates above 55 or
below 50 F, the dampers will be modulated (open or close) to
bring the mixed air temperature back within control.
If mechanical cooling is utilized with free cooling, the
outdoor-air damper will maintain its current position at the time
the compressor is started. If the increase in cooling capacity
causes the mixed-air temperature to drop below 45 F, then the
outdoor-air damper position will be decreased to the minimum
position. If the mixed-air temperature continues to fall, the
outdoor-air damper will close. Control returns to normal once
the mixed-air temperature rises above 48 F.
The subcooler functions by taking a small percentage of the
high pressure, low temperature liquid refrigerant which exits
the condenser and converting it into a low pressure, low tem-
perature gas. This is accomplished by using the subcooler
TXV. The gas is then routed through a reverse-flow heat
exchanger (SHX), which transfers heat from the remaining
liquid refrigerant in the liquid line to the reverse flow gas
refrigerant. The moderate temperature gas is then sent to the
compressor to complete the loop and the cooler liquid refriger-
ant continues its normal path to the main TXV and the
evaporator. See Fig. 30.
COMPRESSOR
COND
If optional power exhaust is installed, as the outdoor-air
damper opens and closes, the power exhaust fans will be ener-
gized and deenergized.
If field-installed accessory CO2 sensors are connected to the
EconoMi$er IV control, a demand controlled ventilation strate-
gy will begin to operate. As the CO2 level in the zone increases
above the CO2 set point, the minimum position of the damper
will be increased proportionally. As the CO2 level decreases
because of the increase in fresh air, the outdoor-air damper will
be proportionally closed.
SUBCOOLER
HX
SUBCOOLER TXV
For EconoMi$er IV operation, there must be a thermostat
call for the fan (G). This will move the damper to its minimum
position.
When the EconoMi$er IV control is in the occupied mode
and a call for cooling exists (Y1 on the thermostat), the control
will first check for indoor fan operation. If the fan is not on,
then cooling will not be activated. If the fan is on, then the
control will open the EconoMi$er IV damper to the minimum
position.
EVAP
MAIN TXV
Fig. 30 — Subcooler Operation
45
Download from Www.Somanuals.com. All Manuals Search And Download.
This will make cleaning efforts more difficult. Surface loaded
fibers must be completely removed prior to using low velocity
clean water rinse.
SERVICE
Periodic Clean Water Rinse — A periodic clean water rinse is
very beneficial for coils that are applied in coastal or industrial
environments. However, it is very important that the water
rinse is made with very low velocity water stream to avoid
damaging the fin edges. Monthly cleaning as described below
is recommended.
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
Routine Cleaning of Coil Surfaces — Monthly cleaning with
Totaline® environmentally sound coil cleaner is essential to
extend the life of coils. This cleaner is available from Carrier
Replacement parts division as part number P902-0301 for a
one gallon container, and part number P902-0305 for a 5 gallon
container. It is recommended that all coils, including standard
aluminum, pre-coated, copper/copper or E-coated coils be
cleaned with the Totaline environmentally sound coil cleaner
as described below. Coil cleaning should be part of the unit’s
regularly scheduled maintenance procedures to ensure long life
of the coil. Failure to clean the coils may result in reduced du-
rability in the environment.
Puron® (R-410A) refrigerant systems operate at higher
pressures than standard R-22 systems. Do not use R-22
service equipment or components on Puron refrigerant
equipment. If service equipment is not rated for Puron
refrigerant, equipment damage or personal injury may
result.
1. Improper installation, adjustment, alteration, service,
or maintenance can cause property damage, personal
injury, or loss of life. Refer to the User’s Information
Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any
phone in your building.
Avoid the use of:
• coil brighteners
• acid cleaning prior to painting
• high pressure washers
• poor quality water for cleaning
Totaline environmentally sound coil cleaner is non-flamma-
ble, hypoallergenic, nonbacterial, and a USDA accepted biode-
gradable agent that will not harm the coil or surrounding com-
ponents such as electrical wiring, painted metal surfaces, or in-
sulation. Use of non-recommended coil cleaners is strongly
discouraged since coil and unit durability could be affected.
Totaline Environmentally Sound Coil Cleaner Application
Equipment
3. IMMEDIATELY call your gas supplier from a neigh-
bor’s phone. Follow the gas supplier’s instructions.
4. If you cannot reach your gas supplier, call the fire
department.
• 21/2 gallon garden sprayer
• water rinse with low velocity spray nozzle
Harsh chemicals, household bleach or acid or basic clean-
ers should not be used to clean outdoor or indoor coils of
any kind. These cleaners can be very difficult to rinse out
of the coil and can accelerate corrosion at the fin/tube inter-
face where dissimilar materials are in contact. If there is
dirt below the surface of the coil, use the Totaline environ-
mentally sound coil cleaner as described above.
Disconnect gas piping from unit when pressure testing at
pressure greater than 0.5 psig. Pressures greater than
0.5 psig will cause gas valve damage resulting in hazardous
condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced before use. When pressure
testing field-supplied gas piping at pressures of 0.5 psig or
less, a unit connected to such piping must be isolated by
closing the manual gas valve(s).
Cleaning — Inspect unit interior at beginning of each heat-
ing and cooling season and as operating conditions require. Re-
move unit top panel and/or side panels for access to unit interior.
High velocity water from a pressure washer, garden hose,
or compressed air should never be used to clean a coil. The
force of the water or air jet will bend the fin edges and
increase airside pressure drop. Reduced unit performance
or nuisance unit shutdown may occur.
COIL MAINTENANCE AND CLEANING RECOMMEN-
DATION — Routine cleaning of coil surfaces is essential to
maintain proper operation of the unit. Elimination of contami-
nation and removal of harmful residues will greatly increase
the life of the coil and extend the life of the unit. The following
maintenance and cleaning procedures are recommended as
part of the routine maintenance activities to extend the life of
the coil.
Remove Surface Loaded Fibers — Surface loaded fibers or
dirt should be removed with a vacuum cleaner. If a vacuum
cleaner is not available, a soft non-metallic bristle brush may
be used. In either case, the tool should be applied in the direc-
tion of the fins. Coil surfaces can be easily damaged (fin edges
can be easily bent over and damage to the coating of a protect-
ed coil) if the tool is applied across the fins.
Totaline Environmentally Sound Coil Cleaner Application
Instructions
1. Proper eye protection such as safety glasses is recom-
mended during mixing and application.
2. Remove all surface loaded fibers and dirt with a vacuum
cleaner as described above.
3. Thoroughly wet finned surfaces with clean water and a
low velocity garden hose, being careful not to bend fins.
4. Mix Totaline environmentally sound coil cleaner in a
21/2 gallon garden sprayer according to the instructions
included with the cleaner. The optimum solution temper-
ature is 100 F.
NOTE: Do NOT USE water in excess of 130 F, as the enzy-
matic activity will be destroyed.
NOTE: Use of a water stream, such as a garden hose, against a
surface loaded coil will drive the fibers and dirt into the coil.
46
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Thoroughly apply Totaline® environmentally sound coil
cleaner solution to all coil surfaces including finned area,
tube sheets and coil headers.
Use caution with ceramic heat exchanger baffles. When in-
stalling retaining clip, be sure the center leg of the clip extends
inward toward baffle. See Fig. 32.
6. Hold garden sprayer nozzle close to finned areas and ap-
ply cleaner with a vertical, up-and-down motion. Avoid
spraying in horizontal pattern to minimize potential for
fin damage.
COMBUSTION-AIR BLOWER — Clean periodically to as-
sure proper airflow and heating efficiency. Inspect blower
wheel every fall and periodically during heating season. For the
first heating season, inspect blower wheel bi-monthly to deter-
mine proper cleaning frequency.
To inspect blower wheel, remove heat section panel. Using
an inspection mirror and flashlight, look into the flue exhaust
duct to inspect the wheel. If cleaning is required, remove motor
and wheel assembly by removing the screws holding the flue
box cover to the flue box. See Fig. 31. Remove the screws hold-
ing the inducer housing to the inlet plate. The wheel can then be
removed from the motor shaft and cleaned with a detergent or
solvent. Replace the wheel onto the motor shaft in the correct
position and reassemble the flue cover onto the flue box.
7. Ensure cleaner thoroughly penetrates deep into finned
areas.
8. Interior and exterior finned areas must be thoroughly
cleaned.
9. Finned surfaces should remain wet with cleaning solution
for 10 minutes.
10. Ensure surfaces are not allowed to dry before rinsing. Re-
applying cleaner as needed to ensure 10-minute satura-
tion is achieved.
11. Thoroughly rinse all surfaces with low velocity clean wa-
ter using downward rinsing motion of water spray nozzle.
Protect fins from damage from the spray nozzle.
CONDENSATE DRAIN — Check and clean each year at the
start of the cooling season. In winter, keep drains and traps dry.
An access panel is located above the condensate connection to
allow easy clean out of the condensate pan. The first time the
panel is removed, the insulation behind the access panel will
need to be cut away. Carefully cut the insulation with a knife or
blade on three sides so the insulation can be folded out of the
way during cleaning. Be careful not to damage components be-
hind the insulation while cutting. Once cleaning is completed,
fold the insulation back into place and secure the access panel
in the original position.
Lubrication
COMPRESSORS — Each compressor is charged with the
correct amount of oil at the factory.
The compressor is in a Puron® refrigerant system and uses
a polyolester (POE) oil. This oil is extremely hygroscopic,
meaning it absorbs water readily. POE oils can absorb
15 times as much water as other oils designed for HCFC
and CFC refrigerants. Avoid exposure of the oil to the
atmosphere. Damage to components could result.
FILTERS — Clean or replace at start of each heating and cool-
ing season, or more often if operating conditions require. Refer
to Table 1 for type and size.
OUTDOOR-AIR INLET SCREENS — Clean screens with
steam or hot water and a mild detergent. Do not use throwaway
filters in place of screens. See Table 2 for quantity and size.
MAIN BURNER — At the beginning of each heating season,
inspect for deterioration or blockage due to corrosion or other
causes. Observe the main burner flames. Refer to Main Burn-
ers section on page 51.
FLUE GAS PASSAGEWAYS — The flue collector box and
heat exchanger cells may be inspected by removing heat
section access panel (Fig. 4), flue box cover, and main burner
assembly (Fig. 31). Refer to Main Burners section on page 51
for burner removal sequence. If cleaning is required, clean
tubes with a wire brush.
Polyolester (POE) compressor lubricants are known to
cause long term damage to some synthetic roofing materials.
Exposure, even if immediately cleaned up, may cause roofing
materials to become brittle (leading to cracking) within a
year. When performing any service which may risk exposure of
compressor oil to the roof, take appropriate precautions to
protect roofing. Procedures which risk oil leakage include com-
pressor replacement, repairing refrigerant leaks, and replacing
refrigerant components. To prepare rooftop:
1. Cover extended roof work area with an impermeable
plastic dropcloth or tarp. Make sure a 10 x 10 area around
the work area is covered.
2. Cover area in front of the unit service panel with a terry
cloth shop towel to absorb lubricant spills and prevent
run-offs. Towel will also protect dropcloth from tears
caused by tools or components.
3. Place terrycloth shop towel inside the unit directly under
components to be serviced to prevent spills through the
bottom of the unit.
4. Perform the required service.
5. Remove and dispose of any oil contaminated material per
local codes.
CERAMIC
BAFFLE
COMBUSTION
FAN HOUSING
CLIP
HEAT
EXCHANGER
INDUCED
DRAFT
SECTION
MOTOR
MAIN GAS
VALVE
IGC BOARD
(HIDDEN)
NOTE: One baffle and clip will be in each upper tube of the heat
exchanger.
MAIN BURNER
SECTION
IGC — Integrated Gas
Controller
Fig. 32 — Removing Heat Exchanger Ceramic
Baffles and Clips
Fig. 31 — Typical Gas Heating Section
47
Download from Www.Somanuals.com. All Manuals Search And Download.
FAN SHAFT BEARINGS — Lubricate bearings at least ev-
ery 6 months with suitable bearing grease. Typical lubricants
are given below:
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from
mounting plate.
MANUFACTURER
LUBRICANT
Texaco
Mobil
Sunoco
Texaco
Regal AFB-2*
Mobilplex EP No. 1
Prestige 42
Evaporator Fan Belt Tension Adjustment — To
adjust belt tension:
Multifak 2
1. Turn off unit power.
*Preferred lubricant because it contains rust and oxidation inhibitors.
2. Slide out fan deck to service position as shown in Evapo-
rator Fan Service and Replacement section above.
3. Loosen fan motor bolts.
4. Move motor mounting plate to adjust to proper belt ten-
sion. See Table 30. Motor adjuster bolts may be used to
tighten belts. See Fig. 33.
5. Check for proper belt alignment. Adjust if necessary.
6. Tighten motor mounting plate bolts to lock motor in
proper position.
7. Return fan deck back into operating position.
8. Restore power to unit.
FAN MOTOR BEARINGS — Fan motor bearings are of the
permanently lubricated type. No field lubrication is required.
No lubrication of the condenser or evaporator motors are
required.
Manual Outdoor Air Damper — If manual outdoor
air damper blade adjustment is required, refer to Step 10 — In-
stall Outdoor Air Hood section on page 12.
Economizer Adjustment — If economizer adjustment
is required, refer to Optional EconoMi$er IV section on
page 39.
Evaporator Fan Service and Replacement — The
48PG units feature a slide-out fan deck for easy servicing of the
indoor-fan motor, pulleys, belt, and bearings. To service com-
ponents in this section, perform the following procedure:
1. Turn off unit power.
MOTOR
2. Open the fan section access panel.
3. Remove three no. 10 screws at front of slide-out fan deck.
Save screws. See Fig. 33.
PULLEY
FAN
PULLEY
(HIDDEN)
4. Disconnect the limit switch wires located on the right
side of the fan deck. Other wires do not need to be
disconnected.
MOTOR
5. Fan deck can now be slid out to access serviceable
components.
MOUNTING
BASE
LIMIT
SWITCH
QUICK
CONNECT
SLIDE-OUT
FAN DECK
DO NOT SLIDE FAN DECK OUT PAST THE STOP
BRACKET. If further access is required, the fan deck must
be supported. Make sure plugs and wiring are not pinched
between fan housing and unit center post. Damage to unit
may result.
Fig. 33 — Evaporator-Fan Motor Adjustment
6. To replace fan deck to operating position, slide fan deck
back into the unit. Secure with the three no. 10 screws
removed in Step 3.
7. Re-attach electrical plugs and wires.
8. Close fan section access door.
9. Restore power to unit.
Evaporator Fan Performance Adjustment
(Fig. 33 and 34) — Fan motor pulleys are factory set
for speed shown in Table 27.
To change fan speeds:
1. Shut off unit power supply.
2. Loosen nuts on the 4 carriage bolts in the mounting base.
Using adjusting bolts and plate, slide motor and remove
belt.
3. Loosen movable-pulley flange setscrew (see Fig. 34).
4. Screw movable flange toward fixed flange to increase
speed and away from fixed flange to decrease speed.
Increasing fan speed increases load on motor. Do not
exceed maximum speed specified in Table 27.
See Table 24 for air quantity limits.
5. Set movable flange at nearest keyway of pulley hub and
tighten setscrew. (See Table 27 for speed change for each
full turn of pulley flange.)
6. Replace and tighten belts (see Evaporator Fan Belt Ten-
sion Adjustment section below).
Fig. 34 — Evaporator-Fan Alignment
and Adjustment
7. Restore power to unit.
48
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 30 — Belt Tension Adjustment
BELT TENSION (lb)
48PG
20
VOLTAGE
Unit Model Number Position 10
A,J
4.8
4.8
5.3
4.8
4.8
5.3
4.5
4.5
4.5
B,K
5.1
5.1
5.1
5.1
5.1
5.1
5.4
5.4
5.4
C,L
5.6
5.6
5.6
5.6
5.6
5.6
5.9
5.9
5.9
D,M
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
E,N
NA
NA
NA
NA
NA
NA
4.5
4.5
4.5
F,P
4.7
4.7
5.2
4.7
4.7
5.2
5.4
5.4
5.4
G,Q
5.0
5.0
5.0
5.0
5.0
5.0
5.9
5.9
5.9
H,R
5.5
5.5
5.5
5.5
5.5
5.5
4.5
4.5
4.5
230
460
575
230
460
575
230
460
575
24
28
Condenser-Fan Adjustment (Fig. 35)
1. Shut off unit power supply.
2. Remove condenser-fan assembly (grille, motor, motor
cover, and fan) and loosen fan hub setscrews.
3. Adjust fan height as shown in Fig. 35.
4. Tighten setscrews and replace condenser-fan assembly.
5. Turn on power to unit.
Evacuation — Proper evacuation of the system will re-
move noncondensables and ensure a tight, dry system before
charging. Evacuate from both high and low side ports. Never
use the system compressor as a vacuum pump. Refrigerant
tubes and indoor coil should be evacuated to 500 microns.
Always break a vacuum with dry nitrogen. The two possible
methods are the deep vacuum method and the triple evacuation
method
DEEP VACUUM METHOD — The deep vacuum method
requires a vacuum pump capable of pulling a minimum vacu-
um of 500 microns and a vacuum gage capable of accurately
measuring this vacuum depth. The deep vacuum method is the
most positive way of assuring a system is free of air and liquid
water. (See Fig. 36.)
TRIPLE EVACUATION METHOD — The triple evacuation
method should only be used when vacuum pump is capable of
pumping down to 28 in. of mercury and system does not con-
tain any liquid water. Proceed as follows:
Fig. 35 — Condenser-Fan Adjustment
1. Pump system down to 28 in. of mercury and allow pump
to continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and
open until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hr.
During this time, dry nitrogen will be able to diffuse
throughout the system, absorbing moisture.
Verify Sensor Performance — Using an ohmmeter
and a thermometer, compare measured temperature to the
resistance shown in Table 31.
Table 31 — Sensor Temperature/Resistance Values
TEMPERATURE (F)
RESISTANCE (ohms)
–58
–40
–22
–4
14
32
50
68
77
86
104
122
140
158
176
185
194
212
230
248
257
266
284
302
200,250
100,680
53,010
29,091
16,590
9,795
5,970
3,747
3,000
2,416
1,597
1,080
746
5. Repeat this procedure. System will then contain minimal
amounts of contaminants and water vapor.
5000
4500
4000
LEAK IN
SYSTEM
3500
3000
2500
2000
525
376
321
274
203
153
116
102
VACUUM TIGHT
TOO WET
1500
1000
TIGHT
DRY SYSTEM
500
2
3
4
5
6
7
0
1
89
70
55
MINUTES
Fig. 36 — Deep Vacuum Graph
Economizer Operation During Power Fail-
ure — Dampers have a spring return. In event of power fail-
ure, dampers will return to fully closed position until power is
restored. Do not manually operate damper motor.
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Refrigerant Charge — Amount of refrigerant charge is
listed on unit nameplate. Refer to Carrier GTAC II; Module 5;
Charging, Recovery, Recycling, and Reclamation section for
charging methods and procedures. Unit panels must be in place
when unit is operating during charging procedure.
Puron® (R-410A) refrigerant cylinders contain a dip tube
which allows liquid refrigerant to flow from the cylinder in an
upright position. Charge units with cylinder in the upright
position and a commercial type metering device in the mani-
fold hose.
This system uses Puron refrigerant which has higher
pressures than R-22 and other refrigerants. No other refrig-
erant may be used in this system. Gage set, hoses, and
recovery system must be designed to handle Puron refrig-
erant. If unsure about equipment, consult the equipment
manufacturer.
Fig. 38 — Charging Chart — 48PG24
NOTE: Do not use recycled refrigerant as it may contain
contaminants.
NO CHARGE — Use standard evacuating techniques. After
evacuating system, weigh in the specified amount of refriger-
ant (refer to unit nameplate).
LOW CHARGE COOLING — Using cooling charging chart
(see Fig. 37-39), add or remove refrigerant until conditions of
the chart are met. An accurate pressure gage and temperature-
sensing device are required. Charging is accomplished by
ensuring the proper amount of liquid subcooling. Measure
liquid line pressure at the liquid line service valve using pressure
gage. Connect temperature sensing device to the liquid line near
the liquid line service valve and insulate it so that outdoor ambi-
ent temperature does not affect reading.
TO USE THE COOLING CHARGING CHART — Use the
above temperature and pressure readings, and find the intersec-
tion point on the cooling charging chart. If intersection point on
chart is above line, add refrigerant. If intersection point on
chart is below line, carefully recover some of the charge. Re-
check suction pressure as charge is adjusted.
Fig. 39 — Charging Chart — 48PG28
NOTE: Indoor-air cfm must be within normal operating range
of unit. All outdoor fans must be operating.
The TXV (thermostatic expansion valve) is set to maintain
between 10 and 15 degrees of superheat at the compressors.
The valves are factory set and cannot be adjusted. Do not use a
TXV designed for use with R-22 refrigerant.
equipment and replacement components are designed to oper-
ate with Puron refrigerant. Do not mix with components that
have been used with other refrigerants. Puron refrigerant, as
with other HFCs, is only compatible with POE oils.
PURON REFRIGERANT — Puron refrigerant operates at 50
to 70 percent higher pressures than R-22. Be sure that servicing
Recovery cylinder service pressure rating must be 400 psig.
Puron systems should be charged with liquid refrigerant. Use a
commercial-type metering device in the manifold hose. Mani-
fold sets should be 750 psig high-side and 200 psig low-side
with 520 psig low-side retard. Use hoses with 750 psig service
pressure rating. Leak detectors should be designed to detect
HFC refrigerant.
Gas Valve Adjustment
NATURAL GAS — The gas valve opens and closes in re-
sponse to the thermostat or limit control.
When power is supplied to valve terminals W2 (High Fire)
and C1, the main valve opens to its preset position.
The regular factory setting is stamped on the valve body.
The setting is 3.00 in. wg for vertical supply/discharge units.
The setting is 2.95 in. wg for horizontal supply/discharge units.
To adjust regulator:
1. Set unit at setting for no call for heat.
2. Turn main gas valve to OFF position.
1
3. Remove /8-in. pipe plug from manifold or gas valve
pressure tap connection. Install a suitable pressure-
measuring device.
Fig. 37 — Charging Chart — 48PG20
50
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Set main gas valve to ON position.
5. Set thermostat at setting to call for heat.
REGULATOR
ADJUSTMENT SCREW
(REMOVE COVER)
2 LEADS, #18 WIRE 1/32 INSULATION,
600V. MAX., 105°C
6. Remove screw cap covering regulator adjustment screw
(see Fig. 40).
7. Turn adjustment screw clockwise to increase pressure or
counterclockwise to decrease pressure.
OUTLET PRESSURE
TAP (PLUGGED)
1/8-27 N.P.T. THDS.
8. Once desired pressure is established, set unit setting
for no call for heat, turn off main gas valve, remove
pressure-measuring device, and replace 1/8-in. pipe
plug and screw cap.
RECEPTACLE AND
TAB COMBINATION
TERMINAL
D-1
W-1
D-2
C1
High Altitude — For high altitude applications greater
than 2000 ft the heat input rate should be reduced. The higher
the altitude is above sea level, the less oxygen is in the air. See
Table 32 for orifice sizing. A high altitude kit is available to
convert unit for altitudes up to 7,000 ft.
C2
W-2
PILOT CONNECTION
FOR 1/4” O.D. TUBING
(PLUGGED)
INLET PRESSURE TAP
(PLUGGED)
1/8 - 27 N.P.T. THDS.
RECEPTACLE TERMINAL
Main Burners — For all applications, main burners are
Fig. 40 — Gas Valve
factory set and should require no adjustment.
MAIN BURNER REMOVAL
CLEANING AND ADJUSTMENT
1. Remove burner rack from unit as described in Main
Burner Removal section above.
2. Inspect burners, and if dirty, remove burners from rack.
3. Using a soft brush, clean burners and crossover port as
required.
4. Adjust spark gap. See Fig. 41.
5. Reinstall burners on rack.
6. Reinstall burner rack as described above.
1. Shut off (field-supplied) manual main gas valve.
2. Shut off power to unit.
3. Remove gas section access panel.
4. Disconnect gas piping from gas valve inlet.
5. Remove wires from gas valve.
6. Remove wires from rollout switch.
7. Remove sensor wire and ignitor cable from IGC board.
8. Remove 2 screws securing manifold bracket to basepan.
9. Remove 2 screws that hold the burner assembly to vesti-
bule plate.
10. Lift burner/manifold assembly out of unit.
SEE DETAIL “C”
Fig. 41 — Spark Gap Adjustment
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 32 — Altitude Compensation*
NATURAL GAS
NATURAL GAS ORIFICE SIZE†
ELEVATION
(ft)
Low Heat
Medium Heat
High Heat (6 Cell)
High Heat (8 Cell)
0-1,999
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
29
29
30
30
30
30
31
31
31
32
30
30
31
31
31
31
32
32
32
33
29
29
30
30
30
30
31
31
31
32
29
29
30
30
30
30
31
31
31
32
*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input
rate should be reduced at higher altitudes. Includes a 4% input reduction per each 1000 ft.
†Orifices available through the local Carrier dealer.
PROPANE GAS
PROPANE GAS ORIFICE SIZE†
Medium Heat High Heat (6 Cell)
38 35
ELEVATION
(ft)
Low Heat
High Heat (8 Cell)
0-1,999
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
35
36
36
37
37
38
39
40
41
42
35
36
36
37
37
38
39
40
41
42
39
39
40
40
41
42
43
44
45
36
36
37
37
38
39
40
41
42
*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input
ate should be reduced at higher altitudes. Includes a 4% input reduction per each 1000 ft.
†Orifices available through the local Carrier dealer.
Compressor Lockout (CLO) Device — The CLO prevents
automatic recycling of the compressor as safety controls reset.
If the high-pressure switch, low-pressure switch or freeze pro-
tection switch opens, the CLO device will energize to block
further compressor operation. To reset the CLO (after all safety
switches have reset), either open the thermostat to remove the
cooling demand signal (and then re-close) or cycle the control
power in the unit.
EVAPORATOR FAN MOTOR PROTECTION — A manu-
al reset, calibrated trip, magnetic circuit breaker protects
against overcurrent. Do not bypass connections or increase the
size of the breaker to correct trouble. Determine the cause and
correct it before resetting the breaker.
CONDENSER-FAN MOTOR PROTECTION — Each
condenser-fan motor is internally protected against
overtemperature.
Fuses are also located in the control box and feed power to
the condenser fan motors. Always replace blown fuses with the
correct size fuse as indicated on the unit fuse label.
Filter Drier — Replace whenever refrigerant system is ex-
posed to atmosphere. Only use factory specified liquid-line
filter driers with working pressures no less than 650 psig. Do
not install a suction-line filter drier in liquid line. A liquid-line
filter drier designed for use with Puron® refrigerant is required
for each circuit.
Protective Devices
COMPRESSOR PROTECTION
Overcurrent — Each compressor has internal line break motor
protection.
Overtemperature — Each compressor has an internal protector
to protect it against excessively high discharge gas temperatures.
High-Pressure Switch — If the high-pressure switch opens, the
compressor will shut down and the compressor lockout (CLO)
device will energize to block further compressor operation. The
high-pressure switch will reset automatically as the refrigerant
pressure drops below its reset level. The CLO will remain ener-
gized until manually reset or cooling demand is removed.
Low-Pressure Switch — If the low-pressure switch opens,
the compressor will shut down and the compressor lockout
(CLO) device will energize to block further compressor opera-
tion. The low-pressure switch will reset automatically as the
refrigerant pressure rises above its reset level. The CLO will
remain energized until manually reset or cooling demand is
removed.
Freeze Protection Switch — This switch is installed on each
evaporator coil section to provide protection against continued
unit operation with a frosted evaporator surface. If the freeze
protection switch opens, the compressor on this circuit will
shut down and the compressor lockout (CLO) device will ener-
gize to block further compressor operation. The freeze protec-
tion switch will reset as the evaporator tube temperature rises
above its reset level. The CLO will remain energized until
manually reset or cooling demand is removed.
Relief Devices — All units have relief devices to protect
against damage from excessive pressures (i.e., fire). These
devices protect the high and low side and are located at the suc-
tion line service port. Protect joint during brazing operations
near joint.
Control Circuit, 24-V — Each control circuit is pro-
tected against overcurrent by a 3.2 amp circuit breaker.
Breaker can be reset. If it trips, determine cause of trouble
before resetting. See Fig. 42-45 for schematics.
Replacement Parts — A complete list of replacement
parts may be obtained from any Carrier distributor upon
request.
Diagnostic LEDs — The IGC control board has a LED
for diagnostic purposes. See Unit Troubleshooting section on
page 57 for more information.
52
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 42 — Typical Low Voltage Control Schematic
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 43 — Typical Power Schematic
54
Download from Www.Somanuals.com. All Manuals Search And Download.
55
Download from Www.Somanuals.com. All Manuals Search And Download.
56
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
Unit Troubleshooting — Refer to Tables 33-35 and
Fig. 46.
Table 33 — Cooling Service Analysis
PROBLEM
CAUSE
REMEDY
Compressor and Condenser
Fan Will Not Start.
Power failure.
Fuse blown or circuit breaker tripped.
Call power company.
Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer, or control Replace component.
relay.
Insufficient line voltage.
Incorrect or faulty wiring.
Thermostat setting too high.
Faulty wiring or loose connections in compressor
circuit.
Determine cause and correct.
Check wiring diagram and rewire correctly.
Lower thermostat setting below room temperature.
Check wiring and repair or replace.
Compressor Will Not Start
but Condenser Fan Runs.
Compressor motor burned out, seized, or internal
overload open.
Determine cause. Replace compressor.
Defective overload.
Determine cause and replace.
Compressor locked out
One leg of 3-phase power dead.
Determine cause for safety trip and reset lockout.
Replace fuse or reset circuit breaker.
Determine cause.
Compressor Cycles
(other than normally
satisfying thermostat).
Refrigerant overcharge or undercharge.
Recover refrigerant, evacuate system, and recharge to
nameplate.
Defective compressor.
Insufficient line voltage.
Blocked condenser.
Replace and determine cause.
Determine cause and correct.
Determine cause and correct.
Determine cause and replace.
Replace thermostat.
Replace.
Locate restriction and remove.
Replace filter.
Decrease load or increase unit size.
Reset thermostat.
Locate leak, repair, and recharge.
Recover refrigerant, evacuate system, and recharge.
Clean coil or remove restriction.
Replace filter.
Defective overload.
Defective thermostat.
Faulty condenser-fan motor.
Restriction in refrigerant system.
Dirty air filter.
Unit undersized for load.
Thermostat set too low.
Low refrigerant charge.
Air in system.
Compressor Operates
continuously.
Condenser coil dirty or restricted.
Dirty air filter.
Excessive Head Pressure.
Dirty condenser coil.
Refrigerant overcharged.
Faulty TXV.
Clean coil.
Recover excess refrigerant.
1. Check TXV bulb mounting and secure tightly to suction line.
2. Replace TXV if stuck open or closed.
Air in system.
Recover refrigerant, evacuate system, and recharge.
Determine cause and correct.
Check for leaks, repair, and recharge.
Remove restriction.
Condenser air restricted or air short-cycling.
Low refrigerant charge.
Restriction in liquid tube.
High heat load.
Head Pressure Too Low.
Excessive Suction Pressure.
Check for source and eliminate.
Faulty TXV.
1. Check TXV bulb mounting and secure tightly to suction line.
2. Replace TXV if stuck open or closed.
Refrigerant overcharged.
Dirty air filter.
Recover excess refrigerant.
Replace filter.
Suction Pressure Too Low.
Low refrigerant charge.
Metering device or low side restricted.
Faulty TXV.
Check for leaks, repair, and recharge.
Remove source of restriction.
1. Check TXV bulb mounting and secure tightly to suction line.
2. Replace TXV if stuck open or closed.
Insufficient evaporator airflow.
Increase air quantity. Check filter and replace if necessary.
Temperature too low in conditioned area.
Field-installed filter drier restricted.
Reset thermostat.
Replace.
LEGEND
TXV — Thermostatic Expansion Valve
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 34 — Gas Heating Service Analysis
PROBLEM
CAUSE
REMEDY
Burners Will Not Ignite.
Misaligned spark electrodes.
Check flame ignition and sensor electrode positioning.
Adjust as needed.
No gas at main burners.
Check gas line for air; purge as necessary. After purging gas
line of air, allow gas to dissipate for at least 5 minutes before
attempting to relight unit.
Check gas valve.
Water in gas line.
Drain water and install drip leg to trap water.
Check power supply, fuses, wiring, and circuit breaker.
No power to furnace.
No 24 v power supply to control circuit.
Check transformer. Transformers with internal overcurrent pro-
tection require a cool-down period before resetting. Check 24-v
circuit breaker; reset if necessary.
Miswired or loose connections.
Burned-out heat anticipator in thermostat.
Broken thermostat wires.
Dirty air filter.
Check all wiring and wire nut connections.
Replace thermostat.
Run continuity check. Replace wires if necessary.
Clean or replace filter as necessary.
Inadequate Heating.
Gas input to unit too low.
Check gas pressure at manifold. Clock gas meter for input.
If too low, increase manifold pressure or replace with correct
orifices.
Unit undersized for application.
Restricted airflow.
Replace with proper unit or add additional unit.
Clean filter, replace filter, or remove any restrictions.
Blower speed too low.
Install alternate motor, if applicable, or adjust pulley to increase
fan speed.
Limit switch cycles main burners.
Too much outdoor air.
Check rotation of blower, thermostat heat anticipator settings,
and temperature rise of unit. Adjust as needed.
Adjust minimum position.
Check economizer operation.
Poor Flame Characteristics.
Burners Will Not Turn Off.
Incomplete combustion (lack of combustion air)
results in:
Aldehyde odors, CO, sooting flame, or floating
flame.
Check all screws around flue outlets and burner compartment.
Tighten as necessary.
Cracked heat exchanger. Replace heat exchanger.
Overfired unit — reduce input, change orifices, or adjust gas
line or manifold pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
Unit is locked into Heating mode for a one minute Wait until mandatory one minute time period has elapsed or
minimum. power to unit.
58
Download from Www.Somanuals.com. All Manuals Search And Download.
LEGEND
IDM
IGC
—
—
Induced-Draft Motor
Integrated Gas Unit Controller
NOTE: Thermostat Fan Switch in the
“AUTO” position.
Fig. 46 — IGC Control (Heating and Cooling)
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 35 — IGC Board LED Alarm Codes
LED
FLASH
CODE
ACTION TAKEN BY
RESET METHOD
CONTROL
DESCRIPTION
PROBABLE CAUSE
On
Off
Normal Operation
Hardware Failure
—
—
—
—
No gas heating.
Loss of power to the IGC. Check 5 amp fuse on IGC,
power to unit, 24V circuit breaker, transformer, and
wiring to the IGC.
1 Flash Indoor Fan On/Off Delay
Modified
5 seconds subtracted from Power reset.
On delay.
5 seconds added to Off
delay (3 min max).
High temperature limit switch opens during heat
exchanger warm-up period before fan-on delay
expires.
High temperature limit switch opens within
10 minutes of heat call (W) Off.
See Limit Switch Fault.
2 Flashes Limit Switch Fault
3 Flashes Flame Sense Fault
Gas valve and igniter Off.
Limit switch closed, or
High temperature limit switch is open. Check the oper-
ation of the indoor (evaporator) fan motor. Ensure that
the supply-air temperature rise is within the range on
the unit nameplate. Check wiring and limit switch
operation.
Indoor fan and inducer On. heat call (W) Off.
Indoor fan and inducer On. Flame sense normal.
The IGC sensed a flame when the gas valve should be
Power reset for LED reset. closed. Check wiring, flame sensor, and gas valve
operation.
4 Flashes Four Consecutive Limit
No gas heating.
No gas heating.
Heat call (W) Off.
4 consecutive limit switch faults within a single call for
Switch Fault
Power reset for LED reset. heat. See Limit Switch Fault.
5 Flashes Ignition Fault
Heat call (W) Off.
Unit unsuccessfully attempted ignition for 15 minutes.
Power reset for LED reset. Check igniter and flame sensor electrode spacing,
gaps, etc. Check flame sense and igniter wiring. Check
gas valve operation and gas supply.
6 Flashes Induced Draft Motor Fault
If heat off: no gas heating. Inducer sense normal, or Inducer sense On when heat call Off, or inducer sense
If heat on: gas valve Off and heat call (W) Off.
inducer On.
Off when heat call On. Check wiring, voltage, and
operation of IGC motor. Check speed sensor wiring to
IGC.
7 Flashes Rollout Switch Lockout
8 Flashes Internal Control Lockout
Gas valve and igniter Off.
Indoor fan and inducer On.
Power reset.
Power reset.
Rollout switch has opened. Check gas valve opera-
tion. Check induced-draft blower wheel is properly
secured to motor shaft.
IGC has sensed internal hardware or software error. If
fault is not cleared by resetting 24 v power, replace the
IGC.
No gas heating.
9 Flashes Temporary Software Lockout No gas heating.
1 hour auto reset, or
power reset.
Electrical interference is disrupting the IGC software.
LEGEND
NOTES:
1. There is a 3-second pause between alarm code displays.
2. If more than one alarm code exists, all applicable alarm codes will be
displayed in numerical sequence.
IGC — Integrated Gas Unit Control
LED — Light-Emitting Diode
3. Alarm codes on the IGC will be lost if power to the unit is interrupted.
10. Set DCV maximum position potentiometer fully CW
(clockwise).
11. Set enthalpy potentiometer to D.
EconoMi$er IV Troubleshooting
ECONOMI$ER IV PREPARATION — This procedure is
used to prepare the EconoMi$er IV for troubleshooting. No
troubleshooting or testing is done by performing the following
procedure.
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm
resistor, and a 5.6 kilo-ohm resistor which are not supplied
with the EconoMi$er IV.
12. Apply power (24 vac) to terminals TR and TR1.
DIFFERENTIAL ENTHALPY — To check differential
enthalpy:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
IMPORTANT: Be sure to record the positions of all poten-
tiometers before starting troubleshooting.
2. Place 620-ohm resistor across SO and +.
3. Place 1.2 kilo-ohm resistor across SR and +. The Free
Cool LED should be lit.
4. Remove 620-ohm resistor across SO and +. The Free
Cool LED should turn off.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
1. Disconnect power at TR and TR1. All LEDs should be
off. Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm resistor
across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals SO and +.
Connect 1.2 kilo-ohm 4074EJM checkout resistor across
terminals SO and +.
8. Put 620-ohm resistor across terminals SR and +.
9. Set minimum position, DCV set point, and exhaust
potentiometers fully CCW (counterclockwise).
SINGLE ENTHALPY — To check single enthalpy:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Set the enthalpy potentiometer to A (fully CCW). The
Free Cool LED should be lit.
3. Set the enthalpy potentiometer to D (fully CW). The Free
Cool LED should turn off.
4. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
60
Download from Www.Somanuals.com. All Manuals Search And Download.
DCV (Demand Controlled Ventilation) AND POWER
EXHAUST — To check DCV and Power Exhaust:
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Ensure terminals AQ and AQ1 are open. The LED for
both DCV and Exhaust should be off. The actuator
should be fully closed.
ECONOMI$ER IV TROUBLESHOOTING COMPLE-
TION — This procedure is used to return the EconoMi$er IV
to operation. No troubleshooting or testing is done by perform-
ing the following procedure.
1. Disconnect power at TR and TR1.
3. Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The LED for both DCV and Exhaust
should turn on. The actuator should drive to between 90
and 95% open.
4. Turn the Exhaust potentiometer CW until the Exhaust
LED turns off. The LED should turn off when the
potentiometer is approximately 90%. The actuator should
remain in position.
5. Turn the DCV set point potentiometer CW until the DCV
LED turns off. The DCV LED should turn off when the
potentiometer is approximately 9 v. The actuator should
drive fully closed.
2. Set enthalpy potentiometer to previous setting.
3. Set DCV maximum position potentiometer to previous
setting.
4. Set minimum position, DCV set point, and exhaust
potentiometers to previous settings.
5. Remove 620-ohm resistor from terminals SR and +.
6. Remove 1.2 kilo-ohm checkout resistor from terminals
SO and +. If used, reconnect sensor from terminals SO and
+.
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
6. Turn the DCV and Exhaust potentiometers CCW until
the Exhaust LED turns on. The exhaust contacts will
close 30 to 120 seconds after the Exhaust LED turns on.
7. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
9. Remove 5.6 kilo-ohm resistor from T and T1. Reconnect
wires at T and T1.
10. Remove jumper from P to P1. Reconnect device at P and
P1.
11. Apply power (24 vac) to terminals TR and TR1.
DCV MINIMUM AND MAXIMUM POSITION — To check
the DCV minimum and maximum position:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
Phase Loss Protection — The phase loss protection
option will monitor the three-phase electrical system to provide
phase reversal and phase loss protection.
PHASE REVERSAL PROTECTION — If the control sens-
es an incorrect phase relationship, the relay (K1) will be de-
energized (opening its contact). If the phase relationship is
correct, the relay will be energized. The control has a self-
bypass function after a pre-set time. If the control determines
that the three phases stay in a correct relationship for 10 con-
secutive minutes, the relay will stay energized regardless of the
phase sequence of three inputs as long as 24-vac control
voltage is applied. This self-bypass function will be reset if all
three phases are restored in a phase loss event.
PHASE LOSS PROTECTION — If the reverse rotation
board senses any one of the three phase inputs has no AC
voltage, the relay will be deenergized (opening its contact).
This protection is always active as long as 24-vac control volt-
age is applied, and is not affected by the self bypass function of
the phase sequence monitoring function. However, in the event
of phase loss, the relay will be re-energized only if all three
phases are restored and the three phases are in the correct
sequence.
2. Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The DCV LED should turn on. The
actuator should drive to between 90 and 95% open.
3. Turn the DCV Maximum Position potentiometer to mid-
point. The actuator should drive to between 20 and 80%
open.
4. Turn the DCV Maximum Position potentiometer to fully
CCW. The actuator should drive fully closed.
5. Turn the Minimum Position potentiometer to midpoint.
The actuator should drive to between 20 and 80% open.
6. Turn the Minimum Position Potentiometer fully CW. The
actuator should drive fully open.
7. Remove the jumper from TR and N. The actuator should
drive fully closed.
8. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
MIXED-AIR INPUT — To check mixed-air input:
A red LED is provided to indicate the function of the board.
See the table below.
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Set the Enthalpy potentiometer to A. The Free Cool LED
turns on. The actuator should drive to between 20 and
80% open.
3. Remove the 5.6 kilo-ohm resistor and jumper T to T1.
The actuator should drive fully open.
LED STATUS
On Continuously
FUNCTION
Relay contact closed (normal operation).
Relay contact open (phase loss or phase
reversal has occurred) — No power will be
supplied to the control system.
Blinking
Off
24 vac control power not present (off).
4. Remove the jumper across T and T1. The actuator should
drive fully closed.
61
Download from Www.Somanuals.com. All Manuals Search And Download.
Copyright 2005 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 534-80211 Printed in U.S.A. Form 48PG-10SI Pg 62 9-05 Replaces: New
Book 1
4
Tab 1a 6a
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
UNIT START-UP CHECKLIST
MODEL NO.:___________________________________________
SERIAL NO.:______________________________________________
TECHNICIAN: ____________________________________________
DATE:_________________________________________________
I. PRE-START-UP:
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
VERIFY INSTALLATION OF OUTDOOR AIR HOOD
VERIFY INSTALLATION OF FLUE EXHAUST AND INLET HOOD
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS
VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT
VERIFY GAS PRESSURE TO UNIT GAS VALVE IS WITHIN SPECIFIED RANGE
CHECK GAS PIPING FOR LEAKS
CHECK THAT INDOOR-AIR FILTERS ARE CLEAN AND IN PLACE
CHECK THAT OUTDOOR AIR INLET SCREENS ARE IN PLACE
VERIFY THAT UNIT IS LEVEL
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SETSCREW
IS TIGHT
VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED
VERIFY THAT SCROLL COMPRESSORS ARE ROTATING IN THE CORRECT DIRECTION
VERIFY INSTALLATION OF THERMOSTAT
VERIFY THAT CRANKCASE HEATERS HAVE BEEN ENERGIZED FOR AT LEAST 24 HOURS
II. START-UP
ELECTRICAL
SUPPLY VOLTAGE
L1-L2
L2-L3
L3-L1
COMPRESSOR AMPS — COMPRESSOR A1
— COMPRESSOR A2
L1
L1
L1
L1
L2
L2
L2
L2
L3
L3
L3
L3
— COMPRESSOR B1
SUPPLY FAN AMPS
TEMPERATURES
OUTDOOR-AIR TEMPERATURE
RETURN-AIR TEMPERATURE
COOLING SUPPLY AIR
F DB (Dry Bulb)
F DB
F WB (Wet Bulb)
F
F
GAS HEAT SUPPLY AIR
PRESSURES
GAS INLET PRESSURE
GAS MANIFOLD PRESSURE STAGE NO. 1
REFRIGERANT SUCTION
IN. WG
IN. WG
PSIG
STAGE NO. 2
IN. WG
CIRCUIT A
CIRCUIT B
PSIG
REFRIGERANT DISCHARGE CIRCUIT A
CIRCUIT B
PSIG
PSIG
VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGE 50
GENERAL
ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS
Copyright 2005 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book
1
4
PC 111
Catalog No. 534-80211
Printed in U.S.A.
Form 48PG-10SI
Pg CL-1
9-05
Replaces: New
Tab
1a 6a
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Black Box Headphones Mobile Headset User Manual
Blanco Indoor Furnishings 157 142 User Manual
Braun Thermometer IRT 1020 User Manual
Briggs Stratton Portable Generator 030206 User Manual
Brother Printer MW 145BT User Manual
Brother Sewing Machine Innov is I User Manual
Cambridge Audio Blu ray Player AP26149 1 User Manual
Capresso Coffeemaker CS10 User Manual
Casio Clock Radio MA0806 B User Manual
Cisco Systems Network Card WIC 1DSU 56K4 User Manual