48PG03-16
Gas Heating/Electric Cooling Units
with PURON® (R-410A) Refrigerant
User’s Information Manual
NOTE TO INSTALLER:
CONTENTS
Page
This manual should be left with the equipment owner.
DETERMINE TYPE OF UNIT CONTROL . . . . . . . . . . . . . . 1
TO LIGHT UNIT (Units with Electro-Mechanical
Control) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
TO LIGHT UNIT (Units with ComfortLink™
WARNING: If the information in this manual
is not followed exactly, a fire or explosion
may result causing property damage, per-
sonal injury or loss of life.
Control) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
TO SHUT UNIT OFF (Units with
Electro-Mechanical Control). . . . . . . . . . . . . . . . . . . . . . . 5
TO SHUT UNIT OFF (Units with ComfortLink
— Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
Control) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
MAINTAINING YOUR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
ROUTINE MAINTENANCE AND CARE FOR
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions.
THE EQUIPMENT OWNER. . . . . . . . . . . . . . . . . . . . . . . 8,9
Air Filter(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Alarm Status (Units with ComfortLink Control) . . . . . . 8
Integrated Gas Controller (IGC) . . . . . . . . . . . . . . . . . . . . . 9
Combustion Area and Vent System . . . . . . . . . . . . . . . . . 9
Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Evaporator, Condenser, and
Combustion Fan Motors. . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Indoor Fan, Belt, and Pulleys . . . . . . . . . . . . . . . . . . . . . . . . 9
Indoor Fan Shaft Bearings (Sizes 03-14). . . . . . . . . . . . . 9
Indoor Fan Shaft Bearings (Size 16) . . . . . . . . . . . . . . . . . 9
Refrigerant Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Evaporator and Condenser Coils. . . . . . . . . . . . . . . . . . . . 9
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Compressors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Condenser Fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Controls and Wiring. . . . . . . . . . . . . . . . . . . . . . . 9
Unit Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
REGULAR DEALER MAINTENANCE. . . . . . . . . . . . . . . . 10
BEFORE YOU CALL FOR SERVICE CHECK FOR
SEVERAL EASILY SOLVED PROBLEMS. . . . . . . . . . 10
IN CASE OF TROUBLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
• If you cannot reach your gas supplier,
call the fire department.
— Installation and service must be per-
formed by a qualified installer, service
agency or the gas supplier.
Improper installation, adjustment, alteration, ser-
vice or maintenance can cause injury or property
damage. Refer to this manual. For assistance or
additional information consult a qualified installer,
service agency, or the gas supplier.
DETERMINE TYPE OF UNIT CONTROL
The procedures used to light or shut off the unit depend on
the type of unit control. This section will help determine the
control type of the unit.
Before performing recommended maintenance, be sure
main power switch to unit is turned off and lockout tag is
installed. Electrical shock could cause personal injury.
Electro-Mechanical Control — These units may be
controlled directly by a thermostat, or indirectly by a third-
party control that connects to the thermostat inputs. For direct
thermostat control, use the Electro-Mechanical Control
procedures in this book. For units with third-party controls
connected to the thermostat inputs, refer to the third-party con-
trol instructions for procedures to ensure complete unit shut off.
Your combination heating/cooling unit is equipped with di-
rect spark ignition and induced draft power combustion blower.
ComfortLink Control — These units have a factory-
installed Carrier ComfortLink control. A Scrolling Marquee
display is located on the front of the unit control box behind the
control box and compressor access door. These units may be
controlled directly by a thermostat, directly by a space temper-
ature sensor, or indirectly through other Carrier Comfort
Network® (CCN) communication devices. To ensure complete
unit shut off, use the ComfortLink Control procedures in this
book.
Burners will light automatically. Do not attempt to light by
hand; personal injury may result.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 04-53480006-01 Printed in U.S.A. Form 48PG-5SO Pg 1 8-05 Replaces: 48PG-4SO
Book 1
4
Tab 1a 6a
Download from Www.Somanuals.com. All Manuals Search And Download.
MAIN
ON
OFF
LOCK-OUT
G
TA
STEP 1
STEP 2
STEP 3
STEP 4
STEP 5
STEP 6
STEP 7
STEP 9
STEP 8
STEP 10
Fig. 2 — To Light Unit (Units with Electro-Mechanical Control)
3
Download from Www.Somanuals.com. All Manuals Search And Download.
MAIN
ON
MODE
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Alarm Status
OFF
Outputs
Configuration
Time Clock
Operating Modes
Alarms
ESCAPE ENTER
LOCK-OUT
G
TA
STEP 1
STEP 2
STEP 3
STEP 4
STEP 5
STEP 6
STEP 7
STEP 9
STEP 8
MODE
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Alarm Status
Outputs
Configuration
Time Clock
Operating Modes
Alarms
ESCAPE ENTER
STEP 10
Fig. 3 — To Light Unit (Units with ComfortLink™ Control)
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 8 — Remove lockout tag and turn on the electrical
supply to unit. Normal operation will automatically begin.
Service Test mode will automatically end (exit) after a recycle
of power.
TO SHUT UNIT OFF
(Units with ComfortLink™ Control)
Step 9 — Open the shutoff valve on the gas supply piping.
Do not turn off the electrical power to unit without first
turning off the gas supply.
Failure to follow these procedures can result in serious
fire or personal injury.
Step 10 — To test the operation of the gas section, the
HEAT submenu of Service Test may be used. See the Controls,
Start-Up, Operation, Service, and Troubleshooting Instructions
for more details on use of Service Test.
See Fig. 1 for location of gas valve. Refer to Fig. 5 while
proceeding with the following steps.
Step 11 — For normal operation, make sure that the set
points are at the normal heat set points.
Step 1 — Turn off the unit operation by using the Scrolling
Marquee to put the unit into Service Test mode. The Scrolling
Marquee is located on the front of the unit control box behind
the control box and compressor access door (see Fig. 6).
Thermostat inputs and remote network commands are ignored
when Service Test mode is ON.
a. A password may be required to change Service Test
values depending on previous settings configured in the
unit. Default password is “1111.”
If the main burners fail to light, or the blower fails to come
on, shut down gas heating section and call your dealer for
service. Failure to follow these requirements could result in
serious personal injury.
TO SHUT UNIT OFF
(Units with Electro-Mechanical Control)
ESCAPE
b. Press the
c. Use the arrow keys to scroll the red LED on the display
to the “Service Test” position and press
key until a blank screen is shown.
.
ENTER
d. The control will display the Field Service Test Mode
(TEST) setting. Press once to select the TEST
Do not turn off the electrical power to unit without first
turning off the gas supply.
Failure to follow these procedures can result in serious
fire or personal injury.
ENTER
setting for configuration. Press
“OFF” to begin flashing.
again for
ENTER
e. Use the arrow keys to change the configuration from
See Fig. 1 for location of gas valve. Refer to Fig. 4 while
proceeding with the following steps.
ESCAPE
to
“OFF” to “ON,” then press
save the setting.
and
ENTER
Step 1 — Set room thermostat to lowest temperature setting
and set SYSTEM switch to OFF position.
Step 2 — Close the shutoff valve on the gas supply piping.
Step 2 — Close the shutoff valve on the gas supply piping.
Step 3 — Turn off the electrical power supply to the unit
and install lockout tag.
Step 3 — Turn off the electrical power supply to the unit
and install lockout tag.
Step 4 — Open the heat section access panel.
Step 4 — Open the heat section access panel.
Step 5 — Move ON/OFF switch on the internal gas valve
to the OFF position.
Step 5 — Move ON/OFF switch on the internal gas valve
to the OFF position.
Step 6 — Close the heat section access panel.
Step 6 — Close the heat section access panel.
Step 7 — If unit is being shut down because of a malfunc-
tion, call your dealer as soon as possible.
Step 7 — If unit is being shut down because of a malfunc-
If unit is being shut down because the heating season has
ended, restore electrical power to the unit to ensure operation
of the cooling system during the cooling season.
Should overheating occur, or the gas supply fail to shut off,
shut off the manual gas valve to the unit before shutting off the
electrical supply.
Do not use this unit if any part has been under water. Imme-
diately call a qualified service technician to inspect the unit and
to replace any part of the control system and any gas control
which has been under water.
tion, call your dealer as soon as possible.
If unit is being shut down because the heating season has
ended, restore electrical power to the unit to ensure operation
of the cooling system during the cooling season.
Should overheating occur, or the gas supply fail to shut off,
shut off the manual gas valve to the unit before shutting off the
electrical supply.
Do not use this unit if any part has been under water. Imme-
diately call a qualified service technician to inspect the unit and
to replace any part of the control system and any gas control
which has been under water.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
MAIN
ON
OFF
LOCK-OUT
G
TA
STEP 1
STEP 2
STEP 3
STEP 5
STEP 4
STEP 7
STEP 6
Fig. 4 — To Shut Unit Off (Units with Electro-Mechanical Control)
6
Download from Www.Somanuals.com. All Manuals Search And Download.
MAIN
ON
MODE
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
OFF
Alarm Status
Outputs
Configuration
Time Clock
Operating Modes
Alarms
ESCAPE ENTER
LOCK-OUT
G
TA
STEP 1
STEP 2
STEP 3
STEP 5
STEP 4
STEP 7
STEP 6
Fig. 5 — To Shut Unit Off (Units with ComfortLink™ Control)
7
Download from Www.Somanuals.com. All Manuals Search And Download.
CONTROL BOX
AND COMPRESSOR
ACCESS DOOR
INDOOR MOTOR
ACCESS DOOR
OUTDOOR AIR
SCREEN
CONDENSER COIL
ACCESS DOOR
GAS SECTION
ACCESS DOOR
FILTER ACCESS
DOOR
Fig. 6 — Panel and Filter Locations (48PG03-07 Shown)
MAINTAINING YOUR UNIT
track. See Fig. 6 for filter access panel location. Note the direc-
tion of flow arrows on the filter frame.
All maintenance should be handled by skilled, experienced
personnel. Your dealer can help you establish a standard
procedure.
For your safety, keep the area around the unit clear and free
of combustible materials, gasoline and other flammable liquids
and vapors.
To assure proper functioning of the unit, flow of combustion
and ventilating air must not be obstructed from reaching the
unit. Clearance of at least 6 ft on all sides is required.
If you have difficulty in locating your air filter in the return-
air duct system, or if you have questions concerning proper
filter maintenance, contact your dealer for instructions. When
replacing your unit filters, always use the correct size and
quantity as shown in Table 1. Filter tracks are field convertible
for 2 or 4-in. thick filters. Verify airflow and duct static values,
and related motor sizing and belt drive adjustment, if filter type
or efficiency rating is changed from the original installation.
Units with outdoor air capability have cleanable screens for
the outdoor air. These screens should be checked annually and
cleaned as necessary.
ROUTINE MAINTENANCE AND CARE
FOR THE EQUIPMENT OWNER
Before proceeding with those things you might want to
maintain yourself, please carefully consider the following:
Never operate your unit without filters in place. Failure to
heed this warning may result in damage to the blower
motor and/or compressor. An accumulation of dust and lint
on internal parts of your unit can cause loss of efficiency
and in some cases, fire.
1. TURN OFF GAS SUPPLY AND ELECTRICAL
POWER TO YOUR UNIT BEFORE SERVICING
OR PERFORMING MAINTENANCE.
Table 1 — Indoor Air Filter Data
2. Do not turn off electrical power to this unit without
first turning off the gas supply.
UNIT 48PG FILTER QUANTITY
FILTER SIZE (in.)
3. When opening access doors or performing mainte-
nance functions inside your unit, be aware of sharp
sheet metal parts and screws. Although special care
has been taken to reduce sharp edges to a minimum,
be extremely careful when handling parts or reaching
into the unit.
03-07
08-14
16
4
6
8
16 x 25 x 2 or 16 x 25 x 4
20 x 25 x 2 or 20 x 25 x 4
20 x 20 x 2 or 20 x 20 x 4
Alarm Status (Units with ComfortLink™ Con-
trol) — The Scrolling Marquee display incorporates an
Alarm Status LED that turns on to indicate an active alarm or
alert. These alarms and alerts are in addition to those that
are indicated by the Integrated Gas Control (IGC). The
ComfortLink control active alarm codes and alarm history can
be viewed with the Scrolling Marquee or other Carrier Comfort
Network® (CCN) devices. Alarms may also be configured to
broadcast automatically on CCN. If the unit will not operate
Air Filter(s) — Air filters should be checked at least
every 3 or 4 weeks and changed or cleaned whenever they
become dirty. Table 1 indicates the correct filter size for your
unit. Open the filter access panel to replace or inspect the
filters. All units have filter tracks into which the filters slide.
Remove the filters by pulling the filter slide outward from the
8
Download from Www.Somanuals.com. All Manuals Search And Download.
and the Alarm Status LED is on, contact the local dealer and
request service.
exchanger involves removing the gas controls assembly and
the flue collector box cover and, when completed, reinstalling
the gas controls assembly for proper operation. The flue collec-
tor box cover must be reinstalled correctly so that a proper seal
is maintained. Contact your dealer for the required periodic
maintenance.
Integrated Gas Controller (IGC) — The IGC board
incorporates an LED that emits a flashing light to indicate an
alarm code. If the furnace section will not operate and the LED
is flashing a code (1 to 9 flashes in succession), contact your
dealer and request service.
Evaporator, Condenser, and Combustion Fan
Motors — The indoor fan, outdoor fan, and combustion fan
motors have permanently sealed bearings, so no field lubrica-
tion is necessary.
Combustion Area and Vent System — The com-
bustion area and vent system should be visually inspected be-
fore each heating season. The normal accumulation of dirt,
soot, rust, and scale can result in loss of efficiency and improp-
er performance if allowed to build up.
Indoor Fan, Belt, and Pulleys — Periodically check
the condition of the fan wheel(s), pulleys, fan belt and the belt
tension. If there is any loose part or belt wear, contact your
dealer and request service.
Indoor Fan Shaft Bearings (Sizes 03-14) — The
indoor fan has permanently sealed bearings, so no field lubrica-
tion is necessary.
If your unit makes an especially loud noise when the main
burners are ignited, shut down the heating section and call
your dealer.
Indoor Fan Shaft Bearings (Size 16) — Lubri-
cate bearings at least every 6 months with suitable bearing
grease. Typical lubricants are given below:
See Fig. 1 and proceed as follows to inspect the combustion
area and power-venting system of your unit.
1. Turn off electrical power (install disconnect tag) and gas
supply to your unit.
2. Open burner compartment access panel.
3. Using a flashlight, carefully inspect the burner areas for
dirt, soot, or scale.
MANUFACTURER
LUBRICANT
Texaco
Mobil
Sunoco
Texaco
Regal AFB-2*
Mobilplex EP No. 1
Prestige 42
Multifak 2
*Preferred lubricant because it contains rust and oxidation inhibitors.
Refrigerant Circuits — The refrigerant circuits are dif-
ficult to check for leaks without the proper equipment; there-
fore, if inadequate cooling is suspected, contact your dealer for
service.
If dirt, soot, rust or scale accumulations are found, call your
dealer and do not operate your heating section.
Evaporator and Condenser Coils — Cleaning of the
coils should only be done by qualified service personnel. Con-
tact your dealer for the required annual maintenance.
4. When you have completed your inspection, follow the
start-up procedures in this manual to restore your unit to
operation.
5. Observe unit heating operation, and watch the burner
flame with the access panel removed to see if it is bright
blue. If you observe a suspected malfunction, or that the
burner flames are not bright blue, call your dealer. See
Fig. 7. Some yellow flame may be present due to the pan-
el being removed.
Condensate Drain — The drain pan and condensate
drain line should be checked and cleaned at the same time the
cooling coils are checked by your dealer.
Compressors — All compressors are factory shipped
with a normal charge of the correct type refrigerant grade oil.
No field lubrication is necessary except possibly with repair or
replacement of refrigerant circuit components.
6. Close burner compartment access panel.
Condenser Fan
Do not poke sticks, screwdrivers, or any other object into
revolving fan blades. Severe bodily injury may result.
The fan must be kept free of all obstructions to ensure prop-
er cooling. Contact your dealer for any required service.
Fig. 7 — Proper Flame Appearance
ElectricalControls and Wiring — Electrical controls
are difficult to check without proper instrumentation; therefore,
if there are any discrepancies in the operating cycle, contact
your dealer and request service.
Heat Exchanger — To ensure dependable and efficient
heating operation, the heat exchanger should be checked by a
qualified maintenance person before each heating season, and
cleaned when necessary. This checkout should not be attempt-
ed by anyone not having the required expertise and equipment
to do the job properly. Checking and/or cleaning the heat
Unit Panels — After performing any maintenance or
service on the unit, be sure all panels are securely fastened in
place to prevent rain from entering unit cabinet and to prevent
disruption of the correct unit airflow pattern.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
REGULAR DEALER MAINTENANCE
BEFORE YOU CALL FOR SERVICE CHECK
FOR SEVERAL EASILY SOLVED PROBLEMS
In addition to the type of routine maintenance you might be
willing to perform, your unit should be inspected regularly by a
properly trained service technician. An inspection (preferably
each year, but at least every other year) should include the
following:
1. Inspection of all flue product passages — including the
burners, combustion baffles, heat exchanger, flue collec-
tor box, and vent pipe.
2. Inspection of all combustion-air and ventilation-air pas-
sages and openings.
3. Close inspection of all gas pipes leading to and inside
your unit.
If insufficient heating or cooling is suspected:
(
) Check for sufficient airflow. Check the air filter for dirt.
Check for blocked return-air or supply-air grilles. Be sure they
are open and unobstructed. If these checks do not reveal the
cause, call your servicing dealer.
If your unit is not operating at all, check the following list
for easy solutions:
(
) If using a thermostat, check to be sure that your thermo-
stat temperature selector is set above the indoor temperature
during the heating season, or below the indoor temperature
during the cooling season. Be sure the SYSTEM switch in the
proper HEAT or COOL position and not in the OFF position.
4. Inspection, and if required, cleaning of the condenser and
evaporator coils.
5. Inspection, and if required, cleaning of the evaporator
drain pan.
(
) If using ComfortLink™ control, check Scrolling Mar-
quee to be sure unit is not in SERVICE TEST mode. Check set
points are properly set.
(
) Is the electrical supply switch on? Are any fuses blown,
or has the circuit breaker tripped?
) During the heating season, check the manual gas shutoff
6. Inspection, cleaning, and lubrication of blower wheel
housing and motor.
7. Inspection of all supply-air and return-air ducts for leaks,
obstructions, and insulation integrity. Any problems
found should be resolved at this time.
8. Inspection of the unit base to ensure that no cracks, gaps,
etc., exist which may cause a hazardous condition.
9. Inspection of the unit casing for signs of deterioration.
10. Inspection of all electrical wiring and components to
assure proper connection.
11. Inspection for leaks in the refrigerant circuit. Pressure-
check to determine appropriate refrigerant charge
12. Operational check of the unit to determine working con-
ditions. Repair or adjustment should be made at this time.
(
valve. Is this lever parallel with the pipe, indicating that the
valve is open? Or is the lever at the right angle, indicating that
the valve is closed? If closed, has the gas been shut off for
safety reasons? Otherwise, you may open the valve and follow
the start-up procedures listed in this manual.
NOTE: Before proceeding with the next check, turn off the
electrical power supply to the unit.
(
) During the heating season, check the control dial on the
gas valve. Is it in the ON position? If it is not, be sure it has not
been turned off for the purpose of safety. If nothing else is
incorrect, follow the start-up procedures in this manual.
(
) If your unit still fails to operate, call your servicing dealer
for troubleshooting and repairs. Specify the model and serial
numbers of your unit. (Record them in this manual in the space
provided.) If the dealer knows exactly which unit you have, he
may be able to offer suggestions over the phone, or save valu-
able time through knowledgeable preparation for the service
call.
13. Your servicing dealer may offer an economical service
contract that covers seasonal inspections. Ask for further
details.
Complete Service Instructions can be found in the unit
Installation, Start-Up and Service Instructions.
IN CASE OF TROUBLE
If, after performing the above, unit performance is unsatis-
factory, shut off the unit and call your dealer.
Dealer’s Name _____________________________________
Telephone No.______________________________________
Unit Model ________________________________________
Unit Serial Number _________________________________
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Copyright 2005 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 04-53480006-01 Printed in U.S.A. Form 48PG-5SO Pg 12 8-05 Replaces: 48PG-4SO
Book 1
4
Tab 1a 6a
Download from Www.Somanuals.com. All Manuals Search And Download.
|