Carrier Heat Pump 30RA User Manual

AQUASNAP  
30RA / 30RH  
U
A
Q
L
R
I
T
E
Y
T
S
A
I
G
S
S
E
U
R
R
S
'
A
D
N
Y
E C  
O
L
L
I
S
1
O
0
9
0
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30RA  
Physical data and electrical data - Model RA  
Table I: Physical data - Model RA  
30RA  
017  
021  
026  
033  
Net cooling capacity*  
kW  
17.70  
21.60  
25.80  
31.70  
Operating weight  
without hydronic module  
with hydronic module  
kg  
kg  
200  
220  
220  
240  
250  
280  
285  
315  
Refrigerant charge R-407C  
Compressor  
kg  
4.80  
5.13  
6.41  
7.70  
One scroll compressor  
Evaporator  
One plate heat exchanger  
Net water volume  
l
1.50  
1
1.88  
2.16  
2.82  
Water connections (MPT gas)  
Maximum water pressure  
(unit without hydronic module)  
inches  
kPa  
1
1-1/4  
1000  
1-1/4  
1000  
1000  
1000  
Hydronic module  
Pump, mesh filter, expansion tank, flow switch, pressure gauges, automatic air purge valve and drain plug,  
flow control valve and safety valve.  
Pump  
One single-speed pump  
Available pressure**  
Water inlet connection (MPT gas)  
Water outlet connection (MPT gas)  
Closed expansion tank water volume  
Water fill system (option)  
Inlet/outlet diameter (MPT gas)  
Condenser  
kPa  
138  
1-1/4  
1
126  
1-1/4  
1
150  
1-1/4  
1-1/4  
8
138  
1-1/4  
1-1/4  
8
inches  
inches  
l
8
8
inches  
inches  
1/2  
1/2  
1/2  
1/2  
One, copper tubes and aluminium fins  
Tube diameter  
3/8  
2
3/8  
3
3/8  
2
3/8  
3
No. of rows  
Tubes/row  
52  
52  
60  
60  
Fin spacing  
mm  
mm  
1.81  
1.81  
1.81  
1.81  
Fan  
Two,axial type with two speeds  
Diameter  
500  
5
500  
5
610  
5
610  
5
No. of blades  
Air flow (high speed)  
Fan speed (high speed)  
l/s  
2450  
12.83  
2222  
12.91  
3278  
11.05  
3000  
10.96  
r/s  
*
The ratings indicated refer to an evaporator entering/leaving temperature of 12/7 °C,and air entering the condenser at 35 °C.  
** At nominal water flow rate.  
Table II: Electrical data - Model RA  
30RA  
017  
021  
026  
033  
Power supply  
Voltage range  
V-ph-Hz  
400-3-50 / 400-3-50+N  
360-440  
V
Nominal power input*  
Effective power input**  
Nominal current drawn*  
Effective current drawn**  
Maximum power drawn***  
Maximum current drawn**  
Starting current  
kW  
kW  
A
6.43  
6.54  
10.75  
10.95  
7.87  
13.50  
87  
8.57  
8.72  
15.50  
15.75  
10.8  
20.00  
132  
9.56  
12.39  
12.60  
24.55  
24.95  
14.95  
28.00  
139  
9.75  
18.80  
19.10  
12.23  
22.50  
134  
A
kW  
A
A
Pump power input  
kW  
0.65  
0.68  
0.89  
0.93  
*
Based on an outdoor entering air temperature of 35 °C db,an evaporator entering water temperature of 12 °C and an evaporator leaving water temperature of 7 °C,unit without hydronic  
module  
** The power and current values indicated refer to Eurovent Standard conditions.  
*** The power and current values indicated refer to an evaporator leaving water temperature of 10 °C and condenser entering air temperature of 46 °C.  
GB - 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30RH  
Physical data and electrical data - Model RH  
E N G L I S H  
Table I: Physical data - Model RH  
30RH  
017  
021  
026  
033  
Net cooling capacity*  
kW  
kW  
16.70  
18.80  
21.60  
24.80  
24.60  
27.80  
29.00  
34.00  
Net heating capacity**  
Operating weight  
without hydronic module  
with hydronic module  
kg  
kg  
235  
255  
265  
285  
285  
315  
315  
345  
Refrigerant charge R-407C  
Compressor  
kg  
7.15  
7.84  
9.30  
11.00  
One scroll compressor  
Pro Dialog-Plus  
Control system  
Refrigerant-water heat exchanger  
Net water volume  
One plate heat exchanger  
l
1.50  
1
1.88  
2.16  
2.82  
Water connections (MPT gas)  
Maximum water pressure  
inches  
kPa  
1
1-1/4  
1000  
1-1/4  
1000  
1000  
1000  
(unit without hydronic module)  
Hydronic module  
Pump, mesh filter, expansion tank, flow switch, pressure gauges, automatic air purge valve and drain plug,  
flow control valve and safety valve.  
One single-speed pump  
Pump  
Available pressure***  
Water inlet connection (MPT gas)  
Water outlet connection (MPT gas)  
Drain tap coupling (MPT gas)  
Closed expansion tank water volume  
Water fill system (option)  
Inlet/outlet diameter (MPT gas)  
Refrigerant-air heat exchanger  
Tube diameter  
kPa  
142  
1-1/4  
1
125  
1-1/4  
1
155  
1-1/4  
1-1/4  
1/2  
149  
1-1/4  
1-1/4  
1/2  
inches  
inches  
inches  
l
1/2  
8
1/2  
8
8
8
inches  
inches  
1/2  
1/2  
1/2  
1/2  
One, copper tubes and aluminium fins  
3/8  
3
3/8  
2
3/8  
3
3/8  
4
No. of rows  
Tubes/row  
52  
60  
60  
60  
Fin spacing  
mm  
mm  
1.81  
1.81  
1.81  
1.81  
Fan  
Two, axial type with two speeds  
Diameter  
500  
5
610  
5
610  
5
610  
5
No. of blades  
Air flow (high speed)  
Fan speed (high speed)  
l/s  
2222  
12.83  
3611  
10.83  
3111  
11.67  
3333  
11.83  
r/s  
*
*The ratings indicated refer to an evaporator entering/leaving temperature of 12/7 °C,and air entering the condenser at 35 °C.  
** The ratings indicated refer to a condenser entering/leaving temperature of 40/45 °C,and air entering the condenser at 7 °C d.b.and 6 °C w.b.  
*** At nominal water flow rate during cooling.  
Table II: Electrical data - Model RH  
30RH  
017  
021  
026  
033  
Power supply  
Voltage range  
V-ph-Hz  
V
400-3-50 / 400-3-50+N  
360-440  
Nominal power input*  
Effective power input**  
Nominal current drawn*  
Effective current drawn**  
Maximum power drawn***  
Maximum current drawn***  
Starting current  
kW  
kW  
A
6.21  
6.30  
10.75  
10.90  
7.87  
13.50  
87  
7.95  
8.10  
14.80  
15.05  
10.8  
20.00  
132  
9.13  
11.83  
12.00  
23.65  
24.00  
14.95  
28.00  
139  
9.30  
18.70  
19.05  
12.23  
22.50  
134  
A
kW  
A
A
Pump power input  
kW  
0.65  
0.68  
0.89  
0.93  
*
Based on an outdoor entering air temperature of 35 °C db, an evaporator entering water temperature of 12 °C and an evaporator leaving water temperature of 7 °C, unit without hydronic  
module  
** The power and current values indicated refer to Eurovent Standard conditions.  
*** The power and current values indicated refer to an evaporator leaving water temperature of 10 °C and a condenser entering air temperature of 46 ° C.  
GB - 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30RA/30RH  
Dimensions and location of hydraulic connections (mm)  
Mod. 30RA 026 - 033  
Mod. 30RH 021 - 026 - 033  
Mod. 30RA 017 - 021  
Mod. 30RH 017  
1503  
1328  
3
1
3
1
2
180 125  
2
175 105  
130  
1243  
130  
130  
1068  
130  
12x20  
12x20  
1. Water inlet  
2. Water outlet  
3. 3/4” gas safety valve outlet  
200  
400  
Main switch  
Grommet: 1 Pg 29 and 2 Pg 16 for power  
supply and control cables entry  
GB - 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30RA/30RH  
General information and hydronic module  
E N G L I S H  
This is necessary to prevent ice from accumulating on the frame  
and to permit correct operation also in the event of heavy  
snowfalls.  
The unit must be levelled on both axes (the tolerance is less than  
2 mm per metre).  
In some cases it may be necessary to fit deflectors against  
strong winds and to stop snow from hitting the coil directly.  
These deflectors must be installed so that the normal air  
circulation is not obstructed.  
Unit installation  
Read this instruction manual thoroughly before starting the  
installation.  
This unit complies with low-voltage (EEC/73/23) and electro-  
magnetic compatibility (EEC/89/336) directives.  
The installation must be carried out by a qualified installer.  
Follow all current national safety code requirements.  
In particular ensure that a properly sized and connected ground  
wire is in place.  
Check that voltage and frequency of the mains power supply are  
those required; the available power must be adequate to operate  
any other possible appliances connected to the same line.  
Also ensure that national safety code requirements have been  
followed for the mains supply circuit.  
Siting the unit  
Check that:  
- The location is able to support unit operating weight (Table I).  
- There is sufficient space for servicing and air flow around the  
unit (see Clearancesfigure).  
After installation thoroughly test the system operation and  
explain all system functions to the owner.  
Leave this manual with the owner for consultation during future  
- The selected site is without dust or foreign material which could  
obstruct the coil.  
periodic maintenance.  
- When installing the unit on the ground, the selected site is not  
subject to flooding.  
Be sure the unit and its components are checked periodically to  
look for loosen, damaged or broken components.  
In case of persisting defects, the unit may cause personal injury  
or property damage.  
- The installation is in accordance with local rules and standards  
governing the installation of air conditioning equipment.  
- Vibration absorbers have been provided throughout the  
installation to prevent noise from being transmitted.  
IMPORTANT:  
During the unit installation make first the hydronic  
connections and then electrical connections. If unit is  
uninstalled first disconnect electrical cables, then the  
hydronic connections.  
Transport  
1. Use spreader bars to lift the unit to avoid damage to the  
panels. Avoid violent movements.  
2. Never roll or swing the unit more than 15°.  
WARNING:  
Disconnect the mains power supply switch before servicing  
the system or handling any internal parts of the unit.  
All mains supply circuits must be disconnected.  
IMPORTANT:  
Ensure that all unit panels are fixed in place before moving  
the unit. Raise and set down the unit carefully.  
The manufacturer declines any liability for damage resulting from  
modifications or errors in the electrical or hydronic connections.  
IMPORTANT:  
Always ensure that the unit is levelled correctly.  
Failure to observe the installation instructions or use of the unit  
under conditions other than those indicated in Tables Operating  
limits, will immediately void the unit warranty.  
Failure to observe electric safety codes may cause a fire hazard  
in case of short circuits.  
Hydronic module  
The hydronic module is factory-installed.  
Inspect equipment for damage due to improper transportation or  
handling: file an immediate claim with the shipping company.  
Do not install or use damaged units.  
This eliminates the need to install the necessary components  
on-site, making the unit more compact and easy to install.  
During unit operation, some of the refrigerant circuit elements  
could reach a temperature in excess of 70oC so only trained and  
qualified personnel should access areas protected by access  
panels.  
In case of any malfunctioning turn the unit off, disconnect the  
mains power supply and contact a qualified service engineer.  
Automatic purge  
Pressure gauge for  
hydraulic circuit  
static pressure  
Flow switch  
Safety valve  
• All of the manufacturing and packaging materials used for  
your new appliance are compatible with the environment  
and can be recycled.  
Dispose of the packaging material in accordance with local  
requirements.  
This equipment contains refrigerant R407-C that must be  
disposed of in a proper manner. When disposing of the unit after  
its operational life, remove it carefully. The unit must then be  
delivered to an appropriate disposal center or to the original  
equipment dealer.  
Arrangement for  
possible installation  
of automatic fill kit  
option  
Expansion vessel  
Mesh filter*  
Flow control valve*  
Hydronic module  
drain valve  
Pump drain plug  
Pump  
Carefully recover refrigerant within this unit before final disposal  
or when servicing. Never vent refrigerant to atmosphere.  
*
Factory-supplied,  
fit during  
installation  
Choosing the installation site  
This unit should not be installed in an explosive atmosphere.  
The unit can operate in normal radioelectric atmospheres in  
residential, commercial and light industrial installations.  
For other applications, please consult Carrier.  
In the case of heat pump operation with an outdoor temperature  
of less than 0 °C the unit must be installed at least 300 mm  
above ground level.  
GB - 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30RA/30RH  
Water connections  
Typical water circuit diagram for units without hydronic module  
Mesh filter  
Legend for units without  
hydronic module:  
Pressure couplings  
Thermometers  
Flow switch  
Automatic purge valve  
Hydraulic circuit drain  
valve  
Charge valve  
Flexible coupling  
Safety valve  
30RA - RH unit  
without hydronic  
module  
Fan coil units  
Water circulating  
pump  
Expansion vessel  
Pressure gauges  
Manual shut-off  
valves  
Plate-type heat  
exchanger drain valve  
Typical water circuit diagram for units with hydronic module  
Charge valve  
Legend for units with  
hydronic module:  
Flexible coupling  
Shut-off valve with  
incorporated stop  
Pressure reducer  
Hydraulic circuit drain  
valve  
30RA - RH unit with  
hydronic module  
Fan coil units  
Pressure gauges  
Manual shut-off  
valves  
Mesh filter *  
Flow control valve *  
Pressure couplings  
Thermometers  
Plate-type heat  
exchanger drain valve  
*
Factory-supplied, fit  
during installation  
NOTE:  
If the automatic  
Power supply  
fill kit option is used on the unit,  
fitting an extra charging  
valve is unnecessary.  
Automatic fill kit option  
GB - 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30RA/30RH  
Water connections  
E N G L I S H  
Ethylene glycol curve  
ATTENTION:  
The pump leakproof  
components are not suitable  
for use with propylene  
glycol.  
CAUTION:  
Weight concentration of ethylene glycol in water %  
Using water with glycol may  
make it necessary to change the  
configuration of the control  
system.  
Make the plate heat exchanger hydraulic connections with the  
necessary components, using material which will guarantee that  
the screwed joints are leakproof.  
The typical hydraulic circuit diagram shows a typical water circuit  
installation in an air conditioning system.  
It is therefore necessary to protect the heat exchanger inlet with  
an extractable mesh filter.  
The filter mesh gauge must be at least 10 mesh/cm2.  
The standard supply of the unit with hydronic module includes a  
mesh filter to be fitted during installation.  
3. After assembling the system, or repairing the circuit, the whole  
system must be thoroughly cleaned with special attention paid  
to the state of the filters.  
4. Pump flow rate control is made through a flow control valve  
supplied with the unit with hydronic module, which must be  
installed on the delivery pipe during installation.  
5. In case of water refrigeration at temperatures lower than 5°C, or  
if the unit is installed in areas where temperatures drop below  
0°C, water must be mixed with a proper quantity of ethylene  
glycol (see the curve above).  
For an application with a water circuit, the following  
recommendations must be taken into account:  
1. The pump must be fitted immediately before of the heat  
exchanger and after the connection to the system return (unit  
without hydronic module).  
2. It is advisable to install shut-off valves to allow isolation of the  
most important circuit components, as well as the heat  
exchanger itself.  
These valves (ball, globe or butterfly valves) should produce a  
minimum loss of charge when they are open.  
3. Provide unit and system drains and vents at the lowest system  
point.  
Use the curve to determine the correct ethylene glycol  
concentration for the temperature.  
4. Install purges in the higher sections of the installation.  
5. Pressure ports and pressure gauges should be installed  
upstream and downstream of the water pump (unit without  
hydronic module).  
6. Thermometers should be installed in the unit water inlet and  
outlet.  
Frost protection  
The plate heat exchanger and the water connections of the  
hydronic module pump may be damaged in spite of the anti-freeze  
protection system these units are fitted with.  
Frost protection of the plate heat exchanger and of the circuit  
inside the hydronic module is always guaranteed down to -10°C  
by the electric heaters that are automatically activated if needed.  
The power supply to the electric heaters of the plate heat  
exchanger and to the internal circuit of the hydronic module must  
never be interrupted.  
7. All piping must be adequately insulated and supported.  
Installation of the following components is obligatory:  
1. A flow switch should be installed in a straight horizontal stretch  
with a length of at least five times the line diameter on either  
side.  
The flow switch must be positioned in the exchanger inlet pipe.  
It must be electrically connected in accordance with the wiring  
diagram (only unit without hydronic module).  
If this is not possible, the installation should incorporate a  
protection device which is activated when there is no water  
circulating in the heat exchanger.  
IMPORTANT:  
Both the appliance main switch (Q1) and the auxiliary  
protection switch for the electric heaters (QF101) must  
always be in the closed position (the positions of Q1 and  
QF101 are indicated in the wiring diagram).  
2. The presence of particles in the water can lead to obstructions  
in the heat exchanger.  
GB - 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30RA/30RH  
Water connections  
Water pressure drop of the unit without hydronic module  
A. 30RA-RH 017  
B. 30RA-RH 021  
C. 30RA-RH 026  
D. 30RA-RH 033  
Water flow rate, l/s  
Outlet available static pressure of the unit with hydronic module  
A. 30RA-RH 017  
B. 30RA-RH 021  
C. 30RA-RH 026  
D. 30RA-RH 033  
Water flow rate, l/s  
GB - 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30RA/30RH  
Electrical connections and refrigerant charge  
E N G L I S H  
Electrical connections  
Liquid refrigerant charge  
Checking the charge  
WARNING:  
To prevent electrical shock or equipment damage, make sure  
disconnects are open before electrical connections are made.  
If this action is not taken, personal injury may occur.  
WARNING:  
When adjusting the refrigerant charge always ensure that  
water is circulating in the heat exchanger to prevent any  
possibility of freezing up. Damage caused by freezing is not  
covered by the product warranty.  
Power supply cable size and external connection must be made by  
the installer according to the unit installation characteristics and the  
applicable standards. The power supply and earthing multicore  
cable of the unit must be connected to the main disconnecting  
switch by passing it through the grommet on the front pedestal  
after removing the lateral access panel. The maximum section  
allowable for flexible copper cable is 25 mm2.  
30RA-RH units are shipped with a full operating charge of  
refrigerant. Refer to Table I.  
If it is nevertheless necessary to add more refrigerant, run the unit  
for some time in cooling mode and then slowly add liquid refrigerant  
into the suction side until there are no bubbles in the sight glass.  
Before connection, check that phase sequence L1 L2 L3 is  
correct.  
WARNING:  
Take special care when making the earth connection.  
To ensure proper operation of 30RA-RH units there must be at  
least 5 K of subcooling as the liquid refrigerant enters the  
expansion valve.  
The maximum permitted voltage and current imbalance is 10% of  
the values indicated in Table II.  
Contact your local power company for correction of an incorrect line  
voltage.  
30RA-RH units use a HFC-407C refrigerant charge. For your  
information, we are reproducing here some extracts from the official  
publication dealing with the design, installation, operation and  
maintenance of air conditioning and refrigeration systems and the  
training of people involved in these activities, agreed by the air  
conditioning and refrigeration industry.  
Before selecting the power supply line fuses - which must be of the  
type "gG" - check the voltage and the size indicated on the unit  
name plate is.  
WARNING:  
Operation of the unit on improper line voltage constitutes  
abuse and is not covered by the Carrier warranty.  
Refrigerant guidelines  
IMPORTANT:  
To ensure the correct unit power supply (cable entry,  
conductor cross section, protection devices etc.), consult the  
electrical data table, the wiring diagram supplied with the unit  
and the applicable standards concerning the installation of air  
conditioning equipment.  
Refrigeration installations must be inspected and maintained  
regularly and rigorously by specialists. Their activities must be  
overseen and checked by properly trained people.  
To minimise discharge to the atmosphere, refrigerants and  
lubricating oil must be transferred using methods which reduce  
leaks and losses to a minimum.  
Never operate a unit if the voltage imbalance exceeds 2%.  
The following formula must be used to determine the percentage of  
voltage imbalance.  
Leaks must be repaired immediately.  
Service valves fitted to the flow and return lines permit charge  
transfer to a suitably arranged external container.  
Voltage imbalance (%) =  
It is indispensable to use a dedicated transfer station.  
Compressor lubricating oil contains refrigerant. Any oil drained  
from a system during maintenance must therefore be handled and  
stored accordingly.  
Largest deviation from average voltage x 100  
———————————————————————————-  
Average voltage  
Refrigerant under pressure must never be discharged to the  
atmosphere.  
Example:  
Nominal supply: 400-3-50  
Recharging liquid refrigerant  
AB =  
BC =  
AC =  
404 V  
399 V  
394 V  
CAUTION:  
Motor  
30RA-RH units are charged with liquid HFC-407C refrigerant.  
Average voltage = 404 + 399 + 394 = 399 400 V  
This non-azeotropic refrigerant blend consists of 23% R-32, 25% of  
R-125 and 52% R-134a, and is characterised by the fact that at the  
time of the change in state the temperature of the liquid/vapour  
mixture is not constant, as with azeotropic refrigerants.  
All checks must be pressure tests, and the appropriate pressure/  
temperature ratio table must be used for the interpretation of the  
values.  
3
Determine maximum deviation from average voltage  
AB =  
BC =  
AC =  
404 - 400 = 4  
400 - 399 = 1  
400 - 394 = 6  
Leak detection is especially important for units charged with  
refrigerant R-407C.  
Depending on whether the leak occurs in the liquid or in the vapour  
phase, the proportion of the different components in the remaining  
fluid is not the same.  
Largest deviation is 6 volts. Percentage voltage imbalance is  
therefore:  
6
x 100 = 1,5 %  
400  
NOTE:  
CAUTION:  
Regularly carry out leak checks and immediately repair any  
leak found.  
The installer must install protection devices, as required by  
the applicable legislation.  
GB - 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30RA/30RH  
Refrigerant charge and electronic control  
Undercharge  
Electronic control  
If there is not enough refrigerant in the system, this is indicated by  
gas bubbles in the moisture sight glass.  
Operation and control of all units is carried out via the electronic  
control.  
There are two possibilities:  
The instructions supplied with the control include comprehensive  
descriptions.  
Small undercharge (bubbles in the sight glass, no significant  
change in suction pressure).  
- After detection and repair the unit can be recharged.  
PRO-Dialog Plus electronic control  
- The replenishment of the charge must always be done in the  
cooling mode, slowly introducing liquid refrigerant at the suction  
side, until there are no bubbles in the sight glass.  
PRO-DIALOG Plus is an advanced numeric control system that  
combines complex intelligence with great operating simplicity.  
PRO-DIALOG Plus constantly monitors all machine parameters  
and safety devices, and precisely manages the operation of  
compressor and fans for optimum energy efficiency.  
Significant undercharge (large bubbles in the sight glass,  
significant drop in suction pressure).  
It also controls the operation of the water pump.  
- Completely drain the refrigerant charge, using a refrigerant  
recovery unit. After detection and repair check the charge with  
the unit off, drain the system and recharge the full amount of  
liquid refrigerant (see Table I) on the suction and discharge side.  
A powerful control system  
The PID control algorithm with permanent compensation for the  
difference between entering and leaving water temperature and  
anticipation of load variations regulates compressor operation for  
intelligent leaving water temperature control.  
- The refrigerant container used must contain a minimum of 10%  
of its initial charge.  
To optimise power absorption, the PRO-DIALOG PLUS  
automatically re-calibrates the set point of the entering water  
temperature based on the outside air temperature to one of the two  
pre-set values (occupied building and of an unoccupied building for  
example).  
WARNING:  
If brazing is to be done, the refrigerant circuit must be filled with  
nitrogen.  
Combustion of refrigerant produces toxic phosgene gas.  
PRO-DIALOG Plus control is auto-adaptive for full compressor  
protection. The system permanently optimises compressor run  
times according to the application characteristics (water loop  
inertia), preventing excessive cycling. In most comfort air  
conditioning applications this feature makes a buffer tank  
unnecessary.  
IMPORTANT:  
- Never use the compressor as a vacuum pump.  
- Always add refrigerant via the suction line.  
- Refrigerant must be added very slowly.  
- The complete refrigerant charge must never be filled into the  
suction line.  
- Do not overcharge the system with refrigerant.  
Clear and easy-to-use control system  
The operator interface is clear and user-friendly: LEDs and two  
numeric displays ensure immediate verification of all unit operating  
data.  
10 menus offer direct access to all machine controls, including a  
history of possible faults, for rapid and complete chiller fault  
diagnosis.  
Extended communications capabilities  
PRO-DIALOG Plus allows remote control and monitoring of the  
unit through a wired connection: start/stop, cooling/heating mode  
selection (only 30RH unit), power demand limit or dual set-point  
and customer safety lock.  
The system permits remote signalling of any general anomaly for  
each refrigerant circuit.  
Three independent time schedules permit definition of: chiller  
start/stop, operation at the second set-point (e.g. unoccupied  
mode), and operation at low fan speed (e.g. during the night).  
This option also permits cascade operation of two units and  
remote control via communication bus (RS 485 serial port).  
GB - 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30RA/30RH  
Start-up, compressor and pump replacement, unit protection devices  
E N G L I S H  
Start-up  
Unit start-up is done by the electronic control described above, and  
must always be carried out under the supervision of a qualified air  
conditioning engineer.  
Necessary checks/precautions before start-up  
- Ensure that all electrical connections are properly tightened.  
- Ensure that the unit is level and well-supported.  
- Check that the hydraulic circuit has sufficient water flow and that  
the pipe connections correspond to the installation diagram.  
- Ensure that there are no water losses. Check the correct  
operation of the valves installed.  
- All panels should be fitted and firmly secured with the  
corresponding screws.  
- Make sure that there is sufficient space for servicing and  
maintenance purposes.  
- Ensure that there are no refrigerant leaks.  
- Confirm that the electrical power source agrees with the unit  
nameplate rating, wiring diagram and other documentation for the  
unit.  
- Ensure that the power supply corresponds to the applicable  
standards.  
- Make sure that compressors float freely on the mounting springs.  
Compressor replacement  
As the compressors are hermetic, when an internal fault occurs,  
the compressor must be replaced.  
Pipe union  
Screw  
Pipe union  
This must be done as detailed below:  
- Disconnect the unit from the electrical supply.  
- Remove the access panels.  
- Remove the gas from the refrigerant circuit using recovery  
equipment to avoid harming the atmosphere.  
- Electrically disconnect the compressor.  
- Unbraze or unscrew the suction and discharge lines, taking care  
not to damage the rest of the components.  
Description of unit protection devices  
- Remove the compressor fastenings.  
- Replace the compressor, ensuring that it contains sufficient oil.  
The unit includes the following protection devices:  
- Braze or screw in the lines.  
- Internal compressor protection.  
- Fan motor internal thermal protection.  
- Main switch.  
- Connect the compressor according to the wiring diagram.  
- Evacuate the compressor.  
- Introduce the quantity of refrigerant indicated on the nameplate  
through the service couplings located on the high and low  
pressure side.  
- Anti-short-cycle protection.  
- Thermomagnetic main switch.  
- Thermomagnetic control switch.  
- Fans and electric heaters thermomagnetic switch.  
- Defrost thermostat.  
NOTE:  
This operation must be carried out by a qualified person.  
Pump replacement  
- Fault detector for the temperature and pressure sensors.  
If the water pump needs to be replaced, proceed as follows:  
- Disconnect the unit from the power supply.  
- Remove the access panel.  
- Electrically disconnect the pump.  
- Empty all water from the hydronic module.  
- Loosen the pipe unions a and c.  
- Remove the four pump fixing screws b.  
- Replace the pump.  
- Fit the pump fixing screws b.  
- High pressurestat: this protects the unit against excessive  
condensing pressure.  
The high pressurestat has factory-fixed non-adjustable settings.  
The appliance stops due to the intervention of the high pressure  
alarm threshold, before the high pressurestat intervenes.  
This function is performed by the electronic control device via a  
pressure transducer.  
- Low pressurestat: This function is performed by the electronic  
control device via a pressure transducer.  
- Tighten the pipe unions a and c.  
- Electrically connect the pump  
- Connect the unit to the power supply  
- Make sure the pump rotates in the right direction using the hole in  
the back panel.  
Only on appliances with hydronic module  
- Pump motor external thermal protection.  
- Reinstall the lateral access panel.  
GB - 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30RA/30RH  
Unit protection devices, operating limits and operating range  
Table III: Pressure switch settings  
NOTE:  
For industrial process cooling applications, where high  
Cut-out  
Reset  
stability of water temperature levels must be achieved, the  
values above must be increased.  
High pressurestat  
30 bar  
Manual  
WARNING:  
We recommend consulting the factory for these particular  
applications.  
Alteration of factory settings other than the design set-point, without  
manufacturer's authorisation, may void the warranty  
.
In case of use other than the manufacturer configuration, Carrier  
Service must be asked for permission to change the Pro-Dialog Plus  
system configuration.  
Operating range - 30RA units  
50  
46  
42  
38  
34  
30RA - Operating limits  
These units have been designed to operate within the following limits:  
30  
26  
22  
18  
14  
10  
6
Evaporator  
Minimum°C Maximum°C  
Water entering temp. (at start-up)  
Water leaving temp. (in operation)  
Water entering temp. (at shut-down)  
Condenser  
7,8 *  
5**  
-
30  
13  
55  
2
-2  
-6  
Air entering temperature  
-10  
46  
-10  
-14  
-1  
1
0
2
4
5
6
8
12 13 14  
10 11  
3
7
9
30RH - Operating limits  
Cooling cycle  
Leaving water temperature °C  
Plate heat exchanger  
Minimum°C Maximum°C  
Water entering temp. (at start-up)  
Water leaving temp. (in operation)  
Water entering temp. (at shut-down)  
7.8*  
5**  
-
30  
13  
55  
Operating range - 30RH units  
Coil  
Air entering temperature  
-10  
46  
Heating cycle  
50  
46  
42  
38  
34  
Plate heat exchanger  
Minimum°C Maximum°C  
Water entering temp. (at start-up)  
Water leaving temp. (in operation)  
Water entering temp. (at shut-down)  
10  
25  
-
45  
50  
55  
30  
26  
22  
18  
14  
10  
6
Coil  
Minimum°C Maximum°C  
-10 20  
Air entering temperature  
*
Contact Carrier if an entering water temperature lower than 7.8 °C is  
necessary.  
In case of operation with a leaving temperature of less than 5 °C, it is  
necessary to add ethylene glycol to the water in circulation.  
2
-2  
**  
-6  
-10  
-14  
-1  
1
0
2
4
5
6
8
12 13 14  
3
7
9
10 11  
Minimum and maximum water flow rates in  
Leaving water temperature °C  
the plate heat exchangers  
30 RA RH  
Minimum flow  
rate, l/s  
Maximum flow  
rate, l/s*  
Maximum flow  
rate, l/s**  
25  
20  
017  
021  
026  
033  
0,45  
0,57  
0,67  
0,87  
1,4  
1,6  
2,1  
2,3  
1,3  
1,6  
1,9  
2,4  
15  
10  
5
*
Maximum water flow rate with an available static pressure of 50 kPa (units  
with hydronicmodule)  
** Maximum water flow rate at a plate heat exchanger pressure drop of  
100 kPa (units without hydronic module)  
0
-5  
-10  
-15  
Water circuit water content  
20  
25  
35  
Leaving water temperature °C  
55  
30  
40  
45  
50  
Whatever the size of the system, the minimum content of the water  
circuit is given by the following formula:  
Volume = CAP(kW) x N = Litres  
where CAP is the nominal system capacity (kW) at nominal  
operating conditions of the installation.  
Application  
N
Notes:  
1. The temperature rise of the water through the plate heat exchanger = 5K.  
Air conditioning  
3.5  
Industrial process cooling  
See note  
2. Both the plate exchanger and the circuit inside the hydronic module  
are protected against frost down to a temperature of -10°C.  
This volume is necessary for stable operation and accurate  
temperature control.  
It is often necessary to add a buffer water tank to the circuit in order  
Operating range with anti-freeze solution and with special  
configuration of the Pro-Dialog control system.  
to achieve the required volume.  
GB - 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30RA/30RH  
General maintenance, maintenance and final recommendations  
E N G L I S H  
Cleaning should be done at regular intervals and should never be  
left until the unit has become blocked.  
General maintenance  
The time intervals between cleaning depend on the quality of the  
water used, but as a general rule it is advisable to clean it at least  
once a year.  
ATTENTION:  
Before starting any servicing or maintenance operation on the unit,  
make sure that the power supply has been disconnected.  
A current discharge could cause personal injury.  
- Refrigerant circuit:  
Ensure that there is no leakage of refrigerant or oil from the  
compressor.  
Check that the high and low side operating pressures are normal.  
Check the cleanliness of the refrigerant-water heat exchangers by  
checking the pressure drop across them.  
In order to obtain maximum performance from the unit special  
attention should be paid to the following points.  
- Electrical connections:  
- Controls:  
The supply voltage should be within the limits indicated in Table II.  
Ensure that no faulty contacts exist in the terminal blocks,  
contactor boards, etc.  
Check the operation of all the electrical components, the high  
pressurestat and of the high and low pressure transducers and  
the water, air and defrost temperature detector.  
Make sure that all the electrical connections are properly  
tightened, and that all the electrical components (contactors,  
relays, etc) are firmly secured to the corresponding rails.  
Pay special attention to the condition of the connecting cables  
between the control elements and the electrical box, and to that of  
the unit power supply cable.  
Maintenance  
Servicing recommendations  
- Maintenance of the unit must be carried out by skilled personnel  
only.  
They should not be twisted and there should be no slits or notches  
in the insulation.  
Check that the starting and running consumptions are within the  
limits specified in Table II.  
Nevertheless, the easiest operations, such as cleaning of the  
battery and the unit external parts can be carried out by non-  
skilled personnel.  
- For any operation on the unit follow thoroughly the instructions  
shown in the manual and on the unit labels as well as the Safety  
Standards.  
- Water connections:  
Make sure there are no water leaks from the system.  
Should the unit be shutdown for long periods, open the drain valve  
installed on the hydronic module and partially drain the pump and  
the water pipes as well as the drain valve on the plate-type  
exchanger, which must be installed on the hydraulic circuit.  
This operation is essential if temperatures are expected to drop  
below freezing.  
If the unit is not drained, the main switch should remain connected  
so that the defrost thermostat can operate.  
Carefully clean the system water filter.  
Always wear the protective gloves and safety glasses. Pay  
attention to burns when brazing.  
- Use only Carrier Original Spare Parts when repair is required.  
Always make sure the spare parts are installed correctly. Always  
install the spare parts in the original position.  
- Before replacing any of the elements in the cooling circuit, ensure  
that the entire refrigerant charge is removed from both the high  
and low pressure sides of the unit.  
- The control elements of the cooling system are highly sensitive.  
If they need to be replaced, care should be taken not to overheat  
them with blowlamps whilst soldering.  
A damp cloth should be wrapped around the component to be  
soldered, and the flame directed away from the component body.  
- Silver alloy soldering rods should always be used.  
- If the total unit gas charge has to be replaced, the quantity should  
be as given on the nameplate and the unit should be properly  
evacuated beforehand.  
- Plate heat exchanger cleaning:  
In some applications, for example when very hard water is used,  
there is an increased tendency for fouling.  
In these cases the installation of a descaling filter is  
recommended.  
The heat exchanger can always be cleaned by circulating a  
cleaning fluid.  
- During unit operation all panels should be in place, including the  
electrical box access panel.  
A weak acid solution should be used (5% phosphoric acid or, if  
frequently cleaned 5% oxalic acid), and the cleaning fluid should be  
pumped through the exchanger.  
- If it is necessary to cut the lines of the refrigerant circuit, tube  
cutters should always be used and never tools which produce  
burrs. All refrigerant circuit tubing should be of copper, specially  
made for refrigeration purposes.  
The tank installation can be permanent or, alternatively, the  
connections can be prepared and, at any given time, a portable  
cleaning device can be connected.  
Final recommendations  
To achieve optimum cleaning the acid solution should be circulated  
at a minimum of 1.5 times the normal operational flow speed, and  
preferably in reverse direction.  
The installation should then be flushed with large amounts of water  
to totally remove the acid before the system is started up.  
The unit you have purchased has undergone strict quality control  
procedures before leaving the factory.  
All components, including the control systems and electrical  
equipment, etc., are certified by our Quality Control Department,  
and tested under the harshest possible operating conditions in our  
laboratories. However, after leaving the factory, it is possible that  
one or more of these elements may be damaged due to causes  
beyond our control. In such an event, the user should not work  
on any of the internal components, or subject the unit to  
operating conditions which are not specified in this manual,  
since serious damage may result and the guarantee would be  
invalidated. Repair and maintenance work should always be left to  
the installer.  
Tank installation  
Weak acid  
Heat exchanger  
solution tank  
All recommendations concerning unit installation are intended as a  
guideline. The installer should carry out the installation according to  
the design conditions and should comply with all applicable  
regulations for air conditioning and refrigeration installations.  
NOTE:  
The manufacturer does not accept responsibility for any  
malfunctions resulting from misuse of the equipment.  
GB - 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30RA/30RH  
Troubleshooting  
A list of possible faults, as well as the probable cause and  
suggested solutions is shown as follows. In the event of a unit  
malfunction it is recommended to disconnect the power supply and  
ascertain the cause.  
- Badly fitting panels;  
INSTALL CORRECTLY.  
Compressor loses oil:  
- Leaking refrigeration circuit;  
REPAIR LEAK.  
Symptoms  
Cause  
REMEDY  
Water loss:  
Unit does not start:  
- Defective entering or leaving connections;  
CHECK AND TIGHTEN IF NECESSARY.  
- No power supply;  
CONNECT POWER SUPPLY.  
- Main switch open;  
CLOSE SWITCH.  
The unit does not defrost  
(only for 30RH units):  
- Low line voltage;  
CHECK VOLTAGE AND REMEDY THE DEFICIENCY.  
- Four-way reversing valve faulty;  
CHECK AND REPLACE THE VALVE IF NECESSARY.  
- A protection has tripped;  
RESET.  
- Defrost sensor broken;  
CHECK AND REPLACE THE SENSOR IF NECESSARY.  
- Contactor stuck open;  
CHECK AND IF NECESSARY REPLACE CONTACTOR.  
- Seized compressor;  
CHECK AND IF NECESSARY REPLACE COMPRESSOR.  
- Loose electrical connections;  
CHECK CONNECTIONS.  
Unit runs continuously or starts and stops frequently:  
- Defective compressor contactor;  
-
C
H
E
C
K
A
N
D
I
F
N
E
C
E
S
S
A
R
Y
R
E
P
L
A
C
E
C
O
N
T
A
C
T
O
R
.
- Defective compressor;  
CHECK AND IF NECESSARY REPLACE COMPRESSOR.  
- Refrigerant losses;  
CHECK AND ADD THE NECESSARY QUANTITY.  
- Total water flow too low  
CHECK FOR PRESSURE DROP IN THE HYDRAULIC CIRCUIT.  
- Static pressure in the hydraulic circuit too low;  
CHECK IT ON THE PRESSURE GAUGE AND RESTORE IT IF NECESSARY.  
Unit continuously cuts out at low pressure:  
- Refrigerant losses;  
CHECK AND ADD THE NECESSARY QUANTITY.  
- Low water flow in the exchanger;  
CHECK WATER PUMP.  
- Unit start-up delay;  
WAIT UNTIL THE SYSTEM HAS STABILISED.  
Unit continuously cuts out at high pressure:  
- Defective high pressurestat;  
CHECK AND IF NECESSARY REPLACE PRESSURESTAT.  
- Blocked expansion valve;  
CHECK AND REPLACE IF NECESSARY.  
- Blocked filter drier;  
CHECK AND IF NECESSARY REPLACE FILTER.  
- The outdoor fan/s does/do not work;  
CHECK THE CONDITION OF THE FAN MOTOR/S AND ITS/THEIR ELECTRICAL  
CONNECTIONS.  
- Obstructed or dirty battery;  
REMOVE THE OBSTRUCTION OR CLEAN THE BATTERY.  
Abnormal system noise:  
- Piping vibration;  
SUPPORT PIPING.  
- Noisy compressor;  
CHECK AND CHANGE IF NECESSARY.  
- Hissing expansion valve;  
CHECK AND ADD REFRIGERANT IF NECESSARY.  
GB - 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
L010126H27 - 0405  
Via R. Sanzio, 9 - 20058 Villasanta (MI) Italy - Tel. 039/3636.1  
The manufacturer reserves the right to change any product specifications without notice.  
Order No. 13024-74 April 2005. Supersedes Order No. 13024-74, June 2004.  
Printed in Italy  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Bissell Vacuum Cleaner 3101 0 User Manual
Black Decker Toaster T202 User Manual
Bowers Wilkins Speaker DM603 S2 User Manual
BRK electronic Carbon Monoxide Alarm C0250LBT User Manual
Brocade Communications Systems Network Card FCX624S HPOE User Manual
Canon Camera Flash 600EX User Manual
Casio Camcorder EX ZR1500 User Manual
Channel Plus Stereo Receiver 5115BID User Manual
Chevrolet Automobile 2010 Corvette Convertible User Manual
Cisco Systems Computer Hardware 1240AG User Manual