CFM Fan AFK 0906 User Manual

PANEL & FLANGE FANS  
better AIRFLOW  
by DESIGNTM  
AFK  
DIRECT DRIVE  
FLANGE FANS  
Airfoil adjustable pitch cast aluminum impeller  
Superior performance and sound characteristics  
Advanced computer selection program  
Unit can be built for supply or exhaust configurations  
Heavy gauge steel with baked polyester coating  
GRP [polypropylene] blades available  
Ideal for OEM use or as replacement fans  
Capacities to 34,000 cfm from stock components  
Custom Fan SolutionsTM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AFK FLANGE FAN  
PRODUCT SPECIFICATION GUIDE  
1.0 GENERAL  
A. Fans shall be model AFK Flange Fans, as manufactured by Continental Fan Manufacturing Inc., of Buffalo,  
NY, and of the size, capacity and flow direction as indicated on the drawings and fan schedule.  
B. Fans shall be rated and tested in accordance with ANSI/AMCA Standard 210-99.  
C. All motors and electrical components shall conform to NEMA standards.  
2.0 FAN HOUSING  
A. Fan housing shall be constructed of rolled and continuously welded heavy gauge steel.  
B. Inlet and outlet flanges shall be integrally formed to ensure concentricity and alignment of the flanges.  
C. Adjustable motor base shall be constructed from heavy gauge steel and bolted to the flange.  
D. Fan housing and motor base shall be coated with baked polyester powder coat finish.  
3.0 FAN IMPELLER  
A. Axial impeller shall be constructed of spark resistant die cast aluminum airfoil shaped blades secured  
to a die cast aluminum hub assembly.  
B. Axial impeller blades shall be of adjustable pitch construction with multiple hub-to-blade arrangements  
to maximize air performance. Blade pitch angles shall be factory set.  
C. Axial impeller hub shall be designed to incorporate a split taper bushing, and be keyed directly to drive shaft.  
4.0 FAN MOTOR AND DRIVE  
A. Motor shall be TEFC industrial duty and conform to NEMA standards.  
B. Motor shall be of voltage, horsepower, RPM and enclosure as indicated on the fan schedule.  
5.0 OPTIONAL FAN ACCESSORIES  
A. Where indicated, fan shall be provided with the following optional accessories:  
Mounting panel  
AMCA spark resistant construction  
Motor side guard  
Reverse flow construction  
Propeller side guard  
Special materials  
Special coatings  
Housing yoke with mounting bracket  
Motors  
- Explosion proof  
- Special duty  
6.0 FAN TESTING  
A. Axial impeller shall be balanced and mounted in fan assembly.  
B. Fan assembly shall be run and tested prior to shipment.  
C. A test report shall be maintained on file for each individual fan.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
AFK DIRECT DRIVE FLANGE FANS  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Bissell Vacuum Cleaner 12U9 User Manual
Blackberry Cell Phone ICQ User Manual
Bosch Appliances Dishwasher SHP65TL5UC User Manual
Broan Ventilation Hood 61000EX User Manual
Cabletron Systems Network Router 9T101 04 User Manual
Campbell Hausfeld Nail Gun CHN70600 User Manual
Canon Digital Camera WM V1 User Manual
Carson Stereo Amplifier SA 500 27 User Manual
Chamberlain Garage Door Opener 1270LMC User Manual
Chauvet Universal Remote FC 5 User Manual