Bosch Appliances Water Heater GWH 345 450 ESR L User Manual

GWH 345/450 ESR  
Temperature Modulated with Electronic Ignition  
Suitable for heating and recirculating potable water  
GWH-345/450-ESR-N - Natural Gas  
GWH-345/450-ESR-L - Liquefied Petroleum (LP) Gas  
Warning: If the information in this manual is not  
followed exactly, a fire or explosion may result  
causing property damage, personal injury or death.  
Do not store or use gasoline or other flammable  
vapor and liquids in the vicinity of this or any other  
appliance.  
What to do if you smell gas  
• Close gas valve. Open windows and doors, and  
evacuate the building.  
• Do not try to operate any appliance.  
• Do not touch any electrical switch; do not use any  
phone in your building  
Improper installation, adjustment, alteration,  
service or maintenance can cause injury or  
property damage. Refer to this manual. For  
assistance or additional information consult a  
qualified installer, service agency or the gas  
supplier.  
In the Commonwealth of Massachusetts this  
product must be installed by a licensed plumber or  
gas fitter.  
• Immediately call your gas supplier from a neighbor’s  
phone. Follow the gas supplier’s instructions.  
• If you cannot reach your gas supplier, call the fire  
department.  
• Installation and service must be performed by a  
qualified installer, service agency or the gas supplier.  
Upon completion of the installation, these  
instructions should be handed to the user of the  
appliance for future reference.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warning  
Warning: The recirculating water  
heater must be disconnected from the  
gas supply piping system during any  
pressure testing of that system at test  
pressures equal to or more than 0.5  
psig (14” W.C.).  
FCC:  
This device complies with Part 15 of the FCC rules.  
Operation is subject to the following two conditions: (1)  
This device may not cause harmful interference, and (2)  
this device must accept any interference received,  
including interference that may cause undesired  
operation.  
Caution:  
Any  
changes  
or  
modifications not expressly approved  
by the party responsible for compliance  
could void the user’s authority to  
operate the equipment.  
Fig. 1  
3
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appliance details  
2
Appliance details  
Temperature Control  
2.1 Features  
Selection range: 115°F (45°C) - 190°F (90°C)  
Parts  
Gas Requirement  
• Sealed combustion burner.  
Gas connection (inches) - ¾”  
Safety  
Inlet gas pressure under operation (with a high hot  
water flow rate)*  
• Ionization flame sensor  
• Over temperature protection.  
• Propane: 11” - 14” water column  
• Natural Gas: 5.5” - 8” water column.  
High quality materials for long working life  
• Copper heat exchanger  
* To measure gas pressure, see Measuring Gas  
Pressure, chapter 3.8.  
• Compact space saver: mounts on a wall with  
supplied bracket.  
Venting  
Features  
3" AL 29-4C single wall sealed stainless steel vent  
pipe.  
See chapter 3.6 for Venting.  
• LCD screen to display temperatures, burner  
operation and error codes  
• On/Off button and separate temperature controls for  
domestic water heating and recirculating water  
Water  
• Hot water connection - ¾” NPT  
• Cold water connection - ¾” NPT.  
• Reset button  
• Failure codes for diagnostics and repair  
• Freeze prevention cycle.  
Combustion  
• NOx 100 ppm  
• CO 250 ppm  
BOSCH is constantly improving its  
products, therefore specifications are  
subject to change without prior notice.  
i
• CO level (see table 8 for correct restrictor  
2
dimension).  
Dimensions  
2.2 GWH-345/450-ESR Specifications  
(Technical data)  
• Depth (in): 11 ¾” (300 mm)  
• Width (in): 15 ¾” (400 mm)  
• Height (in): 27 ½” (700 mm)  
• Weight: 47 pounds (21 kg).  
Approved in US/Canada  
Capacity  
GWH345 Maximum flow rate: 3.5 GPM (13 l/min) at a  
45°F (25°C) rise.  
GWH450 Maximum flow rate: 4.5 GPM (17 l/min) at a  
45°F (25°C) rise.  
Gas types  
Natural Gas.  
Liquid Propane.  
The appliance is not field convertible.  
Maximum output  
GWH345 - 77,900 Btu/h (22.8 kW)  
GWH450 - 98,400 Btu/h (28.8 kW)  
Voltage  
120 V AC (50/60 Hz)  
Maximum input  
Amperage  
GWH345 - 95,000 Btu/h (27.8 kW)  
GWH450 - 120,000 Btu/h (35.1 kW)  
Idle - 40 mA  
Operation - 1.5 A  
Efficiency in %  
Noise  
GWH345 Combustion efficiency: 82%  
GWH450 Combustion efficiency: 81%  
50 db (A)  
Safety devices  
Min. Output  
• Flame failure device (Ionization flame control)  
• Overheat prevention (temperature limiter)  
GWH345 - 23,900 Btu/h (7 kW)  
GWH450 - 35,500 Btu/h (10.4 kW)  
• Pressure switch (blocked vent protection).  
4
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appliance details  
Water resistant  
To remove front cover  
The front cover is secured with two  
IP X4 (protection against water drops)  
screws to prevent unauthorized access.  
Always secure the control panel and front  
cover with these screws.  
i
2.3 Unpacking the GWH-345/450-ESR  
heater  
This heater is packed securely.  
B Loosen the two Philips head screws located as  
shown in fig. 2.  
The box includes:  
• Wall-mounted gas fired recirculating water heater  
• Bracket and screws for wall hanging the heater  
• Exhaust vent adaptor (with 4 screws and gasket  
provided)  
• Combustion air inlet adaptor (with 4 screws and  
gasket provided)  
• Installation manual  
• Product registration card  
Fig. 2 Screws  
• Energy Guide label  
• Pressure relief valve  
B Pull control panel outwards and then pull it  
downwards (Fig. 3).  
Inlet air restrictors  
– GWH 345 ESR N: Ø38/40/42  
– GWH 345 ESR LP: Ø38/40/42  
– GWH 450 ESR N: Ø44/47/50/55  
– GWH 450 ESR LP: Ø47/50/55/60  
Front cover  
Do not lose this manual. Please complete and return  
the enclosed product registration card.  
Before installing the unit, be certain you have the  
correct heater for your type of Gas - Propane or  
Natural Gas. Identification labels are found on the  
shipping box, and on the rating plate which is located on  
the right side panel of the cover.  
Low voltage  
access cover  
Control panel  
Fig. 3 Service position to access water and electric  
connections  
B Lift front cover upward and remove.  
The GWH-345/450-ESR is not approved or  
designed for:  
• Manufactured (mobile) homes, RV's or boats  
• Outdoor installation  
• Combination venting with other appliances  
• Closed loop heating applications.  
5
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appliance details  
11.The heater must not be installed in an unheated area  
where temperatures will reach 36°F or lower. If the  
heater is left in an area susceptible to such  
temperatures, drain the unit and disconnect from  
electrical supply. See Chapter 4.7 for additional  
freeze prevention information.  
2.4 General rules to follow for safe  
operation  
1. You must follow these instructions when you install  
your heater. In the United States: The installation  
must conform with local codes or, in the absence of  
local codes, the National Fuel Gas Code ANSI  
Z223.1/NFPA 54.  
12.In areas where water supply has a high mineral  
content, a water softener is strongly recommended.  
A water softener is required if the water hardness  
exceeds 6 grains/gal (103 mg/l) calcium carbonate.  
Damage to the water heater resulting from hard  
water/scale deposits will not be covered under  
warranty.  
In Canada: The Installation must conform with CGA  
B149.(1,2) INSTALLATION CODES and /or local  
installation codes.  
2. Carefully plan where you install the heater. Correct  
combustion air supply and vent pipe installation are  
very important. If not installed correctly, fatal  
accidents can be caused by lack of air, carbon  
monoxide poisoning or fire.  
3. When the unit is installed indoors with ROOM  
SEALED (twin pipe) combustion air and venting, it is  
permitted to be located in bathrooms, bedrooms and  
occupied rooms that are normally kept closed. See  
chapter 3.6. If the unit will be installed indoors and  
use indoor combustion air, the place where you  
install the heater must have enough ventilation. The  
National Fire Codes do not allow UNSEALED gas  
fired water heater installations in bathrooms,  
bedrooms or any occupied rooms normally kept  
closed. See chapter 3.2 and 3.5.  
4. You must vent your heater. See chapter 3.6 Venting.  
5. The appliance and its gas connection must be leak  
tested before placing the appliance in operation. The  
appliance must be isolated from the gas supply  
piping system by closing its individual manual gas  
shutoff valve (not supplied with heater) during any  
pressure testing at pressures in excess of ½ Psig  
(3.5 kPa).  
6. Keep water heater area clear and free from  
combustibles and flammable liquids. Do not locate  
the heater over any material which might burn.  
7. Correct gas pressure is critical for the optimum  
operation of this heater. Gas piping must be sized to  
provide the required pressure at the maximum output  
of the heater, while all the other gas appliances are in  
operation. Check with your local gas supplier, and  
see the section on connecting the gas supply.  
8. Should overheating occur or the gas supply fails to  
shut off, turn off the gas supply at the manual gas  
shut off valve, on the gas line. Note: manual gas  
shutoff valve is not supplied with the heater.  
9. Do not use this appliance if any part has been  
underwater. Immediately call a qualified service  
technician to inspect the appliance and to replace  
any part of the control system and any gas control  
which has been underwater.  
10.Failure to install heater correctly may lead to unsafe  
operation and void the warranty.  
6
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appliance details  
2.5 Dimensions and minimum installation clearances  
Fig. 4 Dimensions  
1
2
3
4
5
6
7
8
9
Combustion air inlet adapter (right side only)  
Exhaust adapter with CO2 measuring point  
Front cover  
On/Off button  
Reset button  
Recirculating water temperature selector  
LED - (ON) warning light (blinks when in error lock out)  
Domestic hot water temperature selector  
Mounting plate  
Fig. 5 Minimum clearances  
Model GWH-345/450-ESR  
12”  
TOP  
FRONT (B)  
BACK  
4”  
0”  
SIDES  
½”  
12”  
BOTTOM  
Table 1 Minimum clearances  
7
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appliance details  
2.6 Applications  
Caution: the water heater which will be  
used to supply potable water shall not  
be connected to any heating system or  
component(s) previously used with a  
nonpotable water heating appliance.  
Introduction  
The application designs provided in this manual are general guides to be used when installing this recirculating water  
heater.  
Pump Sizing  
Required PS pumps are Taco 007 Bronze or Grundfos 15-42B. PZ pumps should be sized by a professional plumb-  
ing contractor based on the specific application.  
Caution: Do not overpump the heater.  
Maximum 5 gpm water flow permitted  
through the heater.  
Instantaneous water heater (direct tank load design)  
Note: maximum amp draw:  
1,5A. Do not connect  
additional pump to the  
appliance but use a relay panel  
if powering multiple pumps.  
Fig. 6  
Front cover  
Low voltage  
access cover  
Control panel  
Fig. 7 Service position to access water and electric  
connections  
8
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appliance details  
Pressure drop curves  
Note: Flow above 6 GPM is not permitted.  
50 feet of head  
GWH 345 ESR  
40 feet of head  
30 feet of head  
20 feet of head  
10 feet of head  
0 feet of head  
0 GPM  
1 GPM  
2 GPM  
3 GPM  
4 GPM  
5 GPM  
6 GPM  
water flow rate  
Fig. 8 GWH 345 ESR  
50 feet of head  
GWH 450 ESR  
40 feet of head  
30 feet of head  
20 feet of head  
10 feet of head  
0 feet of head  
0 GPM  
1 GPM  
2 GPM  
3 GPM  
4 GPM  
5 GPM  
6 GPM  
water flow rate  
Fig. 9 GWH 450 ESR  
2.7 Water quality  
Water quality can have an impact on appliance performance and appliance longevity, and may not be covered by the  
manufacturer's warranty.  
For water analysis data call your local water department. If on a well system, have well water analyzed periodically. If  
water quality is exceeding one or more of the values specified below, Bosch recommends installing a water condi-  
tioner or softener.  
Descri-  
ption  
pH  
TDS  
(Total  
Total  
hardness  
Aluminum Chlorides  
Copper  
Iron  
Manganese Zinc  
Dissolved  
Solids)  
Max.  
Levels  
pH  
range  
mg/l or  
ppm  
mg/l or  
ppm  
mg/l or  
ppm  
mg/l or  
ppm  
mg/l or  
ppm  
mg/l or  
ppm  
mg/l or ppm mg/l or  
ppm  
6.5-8.5  
500  
100 (6  
grains)  
0.2  
250  
1.0  
0.3  
0.05  
5.0  
Table 2 Venting Specifications  
9
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
3
Installation instructions  
3.1 Introduction  
3.3 Heater placement and clearances  
Please follow these instructions. Failure to follow  
instructions may result in:  
The GWH-345/450-ESR is design certified for  
installation on a combustible wall (see 3.4 Mounting  
installation) provided the floor covering below the  
heater is noncombustible. For installations in an alcove  
or closet, maintain the minimum clearances to  
combustible and non-combustible materials listed  
below. See also fig. 5.  
• Property damage or personal injury  
• Improper operation  
• Heater damage  
• Loss of warranty.  
Please contact Bosch Water Heating with any  
questions.  
A. Top 12 inches (305 mm)  
B. Front 4 inches (100 mm)  
C. Back 0 inches  
D. Sides ½ inches (12 mm)  
E. Bottom 12 inches (305 mm)  
3.2 Proper location for installing your  
heater  
Carefully select the location of the water heater. For  
your safety and for proper heater operation, you must  
provide combustion air to the heater and a proper  
exhaust vent system.  
Clearances from any exhaust vent pipe are dependent  
upon the clearance requirements of the stainless steel  
vent pipe manufacturer. Single wall sealed stainless  
steel (AL29-4C) vent pipe (rated for Category III  
appliances) must be used when exhaust venting this  
appliance. See 3.6 Venting.  
Follow the guidelines below:  
B 1. Locate the heater where venting, gas and  
plumbing connections are feasible and convenient.  
3.4 Mounting installation  
B 2. The hot water lines should be kept short to save  
energy. Centrally locating the water heater is best. It  
is always best to have hot water lines insulated.  
Warning: before starting installation:  
B check that there are no loose parts  
inside the appliance  
Warning:  
The  
water  
in  
this  
recirculating water heater is cold and  
always remains cold except for the  
times the burners are on. In the event of  
power outage in conjunction with  
B check that the gas type of the heater  
matches the gas supply you will be  
connecting to the heater.  
B ensure that gas pipe, gas valve, fan and  
burner have no damage and are proper-  
ly fitted.  
freezing  
temperatures,  
it  
is  
recommended that the heater be  
drained to prevent heater from freezing.  
See chapter 9 for draining instructions.  
Front cover should be removed (see  
instructions on page 5) in order to inspect  
components visually.  
i
Warning:  
Flammable  
materials,  
gasoline, pressurized containers, or any  
other items or articles that are potential  
fire hazards must NOT be placed on or  
adjacent to the heater. The appliance  
area must be kept free of all  
combustible materials, gasoline and  
other flammable vapors and liquids.  
B Secure the wall mounting bracket provided with the  
heater to a wall surface.  
Warning: Do not install this appliance  
on a carpeted wall. The heater must be  
mounted on a wall using appropriate  
anchoring materials.  
If wall is a stud wall sheathed with plasterboard, it is rec-  
ommended that support board(s), either 1x4’s or  
1/2" (minimum) plywood first be attached across a pair  
of studs. Then attach the heater’s bracket to the upper  
support board. The heater should be kept level on the  
wall surface. See Fig. 10.  
10  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
Single pipe  
Although it is permissible to draw combustion air from  
inside the structure, it is not the manufacturer’s recom-  
mended installation method. Always install a 3 inch  
elbow on the combustion air inlet to prevent foreign  
objects from falling into the unit (see Fig. 11).  
Fig. 11  
If a single pipe installation is performed. Use the follow-  
ing guidelines when providing adequate combustion air  
for the recirculating water heater as well as any other  
appliances that may consume air in the space. Always  
follow local codes if more stringent.  
Fig. 10 Mounting the heater  
3.5 Combustion air requirements  
Warning: In areas where freezing  
temperatures are common the twin pipe  
system is recommended. In a single  
pipe installation, a negative air condition  
may result in cold air being drawn  
across the heat exchanger coil causing  
it to freeze and burst. This failure is  
not covered under the  
Appliances located in unconfined spaces:  
a) An unconfined space is one whose volume is  
greater than 50 cubic feet (1.42 cubic meter) per  
1000 Btu per hour (292.81 watts) of the  
combined rating of all appliances installed in the  
space. That would be 6200 cubic feet (175.6  
cubic meter) of air required for the GWH-345/  
450-ESR alone.  
manufacturer’s warranty.  
b) In unconfined spaces in buildings of  
conventional  
construction, infiltration air is normally adequate to  
provide air for combustion.  
frame,  
masonry,  
or  
metal  
Warning: When installed in an  
environment where corrosive chemicals  
or dirty air are present the twin pipe  
system is required.  
c) Installations in structures that have been tightly  
constructed (air infiltration rate of 0.40 ACH or  
less) must provide combustion air per the National  
Fuel Gas Code. Consult an HVAC specialist if  
your air infiltration rate is questionable. For these  
types of installations, the twin pipe system must be  
used.  
Twin pipe  
The GWH-345/450-ESR is designed as a sealed  
combustion appliance. It is recommended that the  
combustion air be provided by a dedicated 3” pipe to  
the outside. If terminating combustion air piping  
horizontally, pitch vent down 1/4" per foot towards  
termination to prevent rain from entering the appliance.  
The combustion air pipe may be constructed of  
aluminum flex, PVC or any other rigid or semi rigid  
sealed pipe. The combustion air inlet must be located in  
such a manner as to provide a minimum 3 foot  
clearance from the exhaust vent terminator.  
The maximum length of the combustion air inlet is 39  
feet with one elbow. Subtract 6 feet for each additional  
elbow. Maximum number of elbows permitted is 4.  
11  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
Appliances located in confined spaces:  
The confined space must be provided with two per-  
manent openings, one commencing within 12 inches  
(304.8mm) of the top and one commencing within  
12 inches (304.8mm) of the bottom of the enclosure.  
Each opening must have a minimum free area of one  
square inch per:  
– 1000 Btu/hr (292.81 watts) if all air is taken from  
inside the building  
– 2000 Btu/hr (585.62 watts) if all air is taken from  
the outside by horizontal ducts  
– 4000 Btu/hr (1171.24 watts)if all air is taken from  
the outside by direct openings.  
Or the confined space must be provided with one  
permanent opening or duct that is within 12 inches  
(304.8mm) of the ceiling of the enclosure. This opening  
must have a minimum free area of one square inch per:  
– 3000 Btu/hr (878.43 watts) if all air is taken from  
the outside by a direct opening.  
Louvers, grills and screens have a blocking effect, when  
used, increase the sizes of your openings by 400% for  
wood louvers (as wood type will reduce the free air by  
75%) and 135% for metal louvers (as metal will reduce  
the free air by 30%). Refer to the National Fuel Gas  
Code for complete information.  
12  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
length is 39 feet with one 90 degree elbow. Sub-  
tract 3 feet for each additional 90 degree elbow  
used (a maximum of four elbows are permitted in  
3.6 Venting  
Danger: Do not combination vent this  
appliance with any other appliance.  
2)  
the inlet air supply) .  
Horizontal section of vent must pitch upward from  
heater 1/4" for every foot of horizontal length, to prevent  
the pooling of condensate, and be supported at 4 foot  
intervals with overhead hangers. See Table 3. The last  
horizontal run including the termination must be sloped  
to the outside 1/4" per foot to prevent rain from entering  
the venting system.  
Warning: Do not reduce the vent  
(exhaust and combustion) pipe sizes.  
Warning: Failure to vent the exhaust  
gases to the outside with sealed  
stainless steel vent pipe (AL29-4C)  
may result in dangerous flue gases  
filling the structure in which it is  
installed.  
Diam.  
Max.  
Material  
equivalent  
length  
Exhaust  
Vent  
3 inches 39 feet with  
1 elbow  
Sealed stainless  
steel (AL29-4C)  
Warning: Do not mix vent pipe or  
joining methods from different  
manufacturers.  
Intake  
Vent  
3 inches 39 feet with  
1 elbow  
Aluminum flex,  
PVC or any other  
rigid or semi rigid  
sealed 3” pipe  
Caution: The vent system must be  
installed by a qualified individual or  
agency in accordance with these  
instructions. If improperly installed, a  
hazardous condition such as fire or  
carbon monoxide poisoning could  
result. Bosch Thermotechnology Corp.  
will not be responsible for improperly  
installed appliances.  
Table 3 Venting Specifications  
The minimum exhaust vent length is  
3 feet.  
The use of a 90 degree elbow is  
equivalent to 6 ft in vent length.  
The use of 45 degree elbow is  
equivalent to 3 ft in vent length.  
3.6.1 Vent material and specifications  
Establish vent clearances that comply with the vent  
manufacturer's specifications. In all cases follow local  
codes.  
Fig. 12 Minimum exhaust vent length  
Note: Listed thimbles or collars are necessary to pass  
through wall and ceiling partitions. If the vent system  
passes through combustible areas where the vent  
clearance requirements cannot be maintained, it is  
permissible to chase straight sections of sealed 3 inch  
single wall vent through 4 inch (or greater) Type-B vent.  
The distance to combustibles using this chase  
technique is 1 inch.  
Warning: Type-B vent should never be  
used as the actual exhaust vent system  
for the appliance, as it is not gas tight.  
Vent lengths  
The appliance should be located as close to the point  
of termination as possible.  
The maximum equivalent exhaust length is 39  
feet with one 90 degree elbow. Subtract 6 feet for  
each additional 90 degree elbow used (a maxi-  
mum of four elbows are permitted in the exhaust  
1)  
vent) .  
1) or subtract 3 feet for each 45° elbow used  
2) or subtract 1.5 feet for each 45° elbow used  
The maximum equivalent inlet air supply pipe  
13  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
Z flex  
Protech  
Heat Fab  
3” Horizontal  
terminator  
TEE only  
TEE only  
9390 TEE  
Vent pipe  
3” Vertical  
terminator  
2SVSRCF03  
2SVEVWCF03  
2SVEDWCF03  
2SVSEVDP03  
2SVEDTK  
FSRC3  
5300CI  
93PLSTEE  
9321  
Reduce maximum  
length 6 ft for each  
90 elbow after the  
first one and 3 ft for  
each 45 elbow.  
90°  
Condensate  
drain Tee  
FST3 &  
FSDF3  
Horizontal  
Condensate  
drain  
FSHD03  
N/A  
Combustion  
air intake  
Vertical  
Condensate  
drain  
N/A  
Fig. 13 Maximum vent and combustion air lengths  
Condensate  
Drain Tube  
N/A  
7000TUBE  
Vent material  
The GWH-345/450-ESR requires 3 inch sealed single  
wall stainless steel vent pipe (AL29-4C). Use of any  
other vent material will void the manufactures warranty  
and may result in a hazardous condition. For specific  
questions concerning vent material, specifications,  
usage or installation, contact the vent manufacturer  
directly.  
Table 5 Approved vent termination and condensate  
drain part numbers (subject to change)  
Contact your Bosch supplier for stocked vent material.  
Vent Safety System  
The GWH-345/450-ESR will shut down if inadequate  
exhaust venting is detected or a lack of combustion air  
is provided to the unit; see troubleshooting section on  
page 32. Correct the problem and then reset the heater  
before operating.  
Company  
Z-flex  
Contact information  
800-654-5600  
3.6.2 Vent connections and air inlet restrictors  
Exhaust vent connection  
ProTech  
Industries  
800-766-3473  
B Attach the flue gas exhaust accessory (8 705 504  
142) to the top of the unit (position 1) using the 4  
screws and gasket provided  
B Insert 3" single wall stainless steel vent pipe into  
exhaust vent adapter 1.5" and tighten the clamp  
(position 2).  
Heat-Fab  
800-772-0739  
Note: Failure to fully insert and tighten vent pipe may  
cause flue gas leakage or condensate damage that is  
not covered under the manufacturer's warranty.  
Table 4 Vent manufacturer contact information  
14  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
Fig. 14 Exhaust vent connection  
15  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
Selecting inlet air restrictor  
Example  
Note: Before installing the combustion air inlet  
accessory, the appropriate inlet air restrictor must  
be determined using Tables 6, 7 and 8.  
Exhaust  
• 10 - 3' straight sections  
• 1 - 1' straight section  
Refer to Fig. 15 for mounting sequence.  
Total length 31'  
B Determine the total length of the straight sections of  
• 1 - 90° elbow  
3" stainless steel exhaust and enter that length in line  
1.  
• 1 - GWH 450 ESR termination.  
B Count the number of 90° elbows used and enter that  
Intake  
value in line 2.  
• 5 - 4' straight sections  
• 2 - 1' straight sections  
B Count the number of 45° elbows used and enter that  
value in line 3.  
Total length 22'  
B For model GWH 345 ESR, enter a 1 in line 4 for  
model GWH 450 ESR enter a 1 in line 5.  
• 2 - 90° elbows  
B Repeat steps 1 through 4 for the 3" intake pipe and  
• 1 - GWH 450 ESR termination.  
enter those values in the intake section.  
Example  
B Add the totals from the Exhaust table and the Intake  
table to determine the equivalent vent length. Use  
this value in Table 6 to determine which restrictor  
size to use.  
Exhaust  
Straight section length  
90° elbows (qty)  
21 x 1 =  
1 x 6 =  
0 x 3 =  
0 x 15 =  
1 x 12 =  
Total:  
21  
6
Exhaust  
1
Straight section length  
90° elbows (qty)  
__ x 1 = ____  
__ x 6 = ____  
__ x 3 = ____  
45° elbows (qty)  
0
2
GWH 345 ESR termination  
GWH 450 ESR termination  
0
3
45° elbows (qty)  
12  
39  
4
GWH 345 ESR termination __ x 15 = ____  
GWH 450 ESR termination __ x 12 = ____  
5
Intake  
6
Total:  
____  
Intake  
Straight section length  
90° elbows (qty)  
22 x .5 =  
2 x 3 =  
0 x 1.5 =  
0 x 6 =  
1 x 3 =  
Total:  
11  
6
1
2
3
4
5
6
7
Straight section length  
90° elbows (qty)  
__ x .5 = ____  
__ x 3 = ____  
__ x 1.5 ____  
__ x 6 = ____  
__ x 3 = ____  
Total: ____  
45° elbows (qty)  
0
45° elbows (qty)  
GWH 345 ESR termination  
GWH 450 ESR termination  
0
GWH 345 ESR termination  
GWH 450 ESR termination  
3
20  
59  
Total equivalent vent length =  
Total equivalent vent length = ____  
Table 7 Determining equivalent length example  
Table 6 Determining equivalent vent length (see  
example in Table 7)  
Using table 8, the following restrictors would be  
required:  
• GWH 450 ESR NG - restrictor 55  
• GWH 450 ESR LP - restrictor 55.  
16  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
Use table below to define which restrictor to be used.  
Combustion air inlet connection  
The combustion air inlet accessory can only be  
connected to the top right of the appliance. The left side  
must remain sealed.  
Total equivalent length (ft)  
Restrictor Ø  
Note: Before installing the combustion air inlet  
accessory, the appropriate inlet air restrictor must  
be determined using Tables 6, 7 and 8.  
Refer to Fig. 15 for mounting sequence.  
20 - 38  
38 - 78  
38  
40  
B Place gasket, deflector, gasket and inlet air restrictor  
on the air inlet opening lining up screw holes as seen  
in Fig. 15.  
18 - 28  
28 - 40  
40 - 65  
65 - 78  
44  
47  
50  
55  
Total equivalent length (ft)  
Restrictor Ø  
20 - 38  
38 - 78  
38  
40  
Fig. 15 Mounting sequence  
18 - 28  
28 - 50  
50 - 78  
47  
50  
55  
a
b
c
Gasket  
Deflector  
Restrictor  
Adaptor  
d
B Attach the combustion air inlet accessory (8 705  
504 141) to the top of the unit (position 3) using the  
4 screws provided.  
Table 8 Restrictors table  
After installation is complete, check CO levels per  
2
B Install 3" combustion air pipe over the air inlet  
accessory. If using flexible piping, secure with a  
clamp (position 4, not included).  
chapter 3.9.  
Fig. 16 Exhaust air inlet accessory  
17  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
3.6.3 Condensate drain requirements  
3.6.4 Room sealed installation (Twin pipe)  
An external condensate drain must always be installed  
except when using one 90° elbow and less than 3 feet  
of horizontal pipe.  
Although it is permitted to draw combustion air from  
inside, the recommended method is to provide  
combustion air through a 3" pipe from the outside. See  
Chapter 3.5 for more direction on combustion air.  
To reduce pressure differentials between the exhaust  
and combustion air intake, it is required that both  
terminators exit on the same wall or roof. See Fig. 18 for  
an example horizontal twin pipe termination and Fig. 19  
for the vertical twin pipe termination example. Use only  
approved rain caps. For vertical air inlets use 2 90°  
elbows with opening facing down and covered with a  
screen.  
Note: condensate must be disposed of according to  
local codes.  
1. Install condensate drain as close to heater as  
possible.  
2. Use 3/8" ID high temperature silicone tube to  
connect to condensate drain port. Do not use copper  
piping for any portion of the condensate drain.  
3. Form a condensate trap by means of a 3" loop  
partially filled with water to form a gas trap. Add small  
amount of mineral oil if the trap is drying out.  
4. To increase the tube length, connect to end of the  
high temperature silicone tubing with vinyl tubing,  
PVC or CPVC pipe. Do not reduce the internal  
diameter at any point.  
6 ft  
2 ft  
Fig. 18 Horizontal twin pipe termination  
Fig. 17 Required condensate drain installation  
Fig. 19 Vertical twin pipe termination  
18  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
3.6.5 Vertical terminations  
Caution: Failure  
Over 12/12 to 14/12  
Over 14/12 to 16/12  
Over 16/12 to 18/12  
Over 18/12 to 20/12  
Over 20/12 to 21/12  
5.0  
6.0  
7.0  
7.5  
8.0  
1.52  
1.83  
2.13  
2.27  
2.44  
to  
install  
a
condensate drain may result in damage  
not covered by the manufacturer's  
warranty. See chapter 3.6.3. An  
approved vent terminator must be used.  
See Table 5 for known approved  
vertical vent terminations.  
Table 9 Termination heights at various roof pitches  
Horizontal runs  
Interior masonry chimneys  
Any gas vent section that is greater than 45 degrees  
from the vertical is considered horizontal. Horizontal  
sections must slope upwards from heater at least ¼  
inch for every foot of its horizontal length and be  
properly supported. Under no circumstances should  
the exhaust vent pipe pitch downward away from  
heater. Pitch the termination to the outside 1/4" per foot  
to prevent rain water from entering the pipe.  
The single wall stainless steel exhaust vent pipe must  
be permanently mounted inside the masonry chimney.  
The masonry chimney may have to be tile or metal lined  
before the insertion of the gas vent pipe; check local  
codes for clarification.  
You may not vent any other fuel burning appliances into  
any free space remaining in the chimney. The vent  
terminator must extend at least 3 feet (0.9 m) above  
where the chimney meets the roofline and at least 2 feet  
(0.6 m) higher than any vertical wall or similar  
obstruction within 10 feet (3.1 m). The top of the  
chimney must be sealed to prevent rain water or other  
elements from entering the chimney.  
Vent terminations  
The exhaust vent must terminate above the roof surface  
with an approved vent cap not less than 2 feet (0.6 m)  
above the highest point where it passes through the  
roof and at least 2 feet (0.6 m) higher than any vertical  
wall or similar obstruction within 10 feet (3.1m). See  
Fig. 20 and Table 9.  
Exterior Masonry Chimney  
Refer to the National Fuel Gas Code and consult a local  
venting HVAC contractor. Not recommended in cold  
climates.  
3.6.6 Horizontal terminations  
Warning: Pitch the last horizontal pipe  
and the termination to the outside 1/4"  
per foot to prevent rain water from  
entering the pipe.  
An approved vent terminator must be used. See Table 5  
for known approved horizontal vent terminations.  
Install a condensate drain if the total straight vent length  
is greater than 5 feet or if the exhaust vent pipe passes  
through an unconditioned space.  
Fig. 20 Vertical vent termination clearances  
The exhaust termination tee must project out a minimum  
of 10" and maximum of 16” on center from the wall  
thimble.  
GAS VENT TERMINATIONS FOR LISTED VENT  
CAPS  
Fig. 21 and table 10 show the required clearances for  
the vent termination. Follow local codes if more  
stringent.  
Roof pitch  
H (min.)  
feet  
meters  
Flat to 6/12  
1.0  
1.25  
1.5  
0.30  
0.38  
0.46  
0.61  
0.76  
0.99  
1.22  
6/12 to 7/12  
Over 7/12 to 8/12  
Over 8/12 to 9/12  
Over 9/12 to 10/12  
Over 10/12 to 11/12  
Over 11/12 to 12/12  
2.0  
2.5  
3.25  
4.0  
Table 9 Termination heights at various roof pitches  
19  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
3.6.6.1Requirements for installation in  
Massachusetts  
4. INSPECTION. The state or local gas inspector of the  
side wall horizontally vented gas fueled equipment shall  
not approve the installation unless, upon inspection, the  
inspector observes carbon monoxide detectors and  
signage installed in accordance with the provisions of  
248 CMR 5.08(2)(a)1 through 4.  
(b)EXEMPTIONS: The following equipment is exempt  
from 248 CMR 5.08(2)(a)1 through 4:  
1. The equipment listed in Chapter 10 entitled  
"Equipment Not Required To Be Vented" in the most  
current edition of NFPA 54 as adopted by the Board;  
and  
Attention residents of the Commonwealth of  
Massachusetts:  
In the Commonwealth of Massachusetts the following  
regulation went into effect on 12/30/2005:  
(a)For all side wall horizontally vented gas fueled  
equipment installed in every dwelling, building or  
structure used in whole or in part for residential  
purposes, including those owned or operated by the  
Commonwealth and where the side wall exhaust vent  
termination is less than seven (7) feet above finished  
grade in the area of the venting, including but not limited  
to decks and porches, the following requirements shall  
be satisfied:  
2. Product approved side wall horizontally vented gas  
fueled equipment installed in a room or structure  
separate from the dwelling, building or structure used in  
whole or in part for residential purposes.  
(c)MANUFACTURERS REQUIREMENTS - GAS  
EQUIPMENT VENTING SYSTEM REQUIRED. When  
the manufacturer of Product Approved side wall  
horizontally mounted gas equipment provides a venting  
system design or venting system components with the  
equipment, the instructions provided by the  
manufacturer for the installation of the equipment and  
the venting shall include:  
1. Detailed instructions for the installation of the venting  
system or the venting system components: and  
2. A complete parts list for the venting system design or  
venting system.  
(d)MANUFACTURER REQUIREMENTS - GAS  
EQUIPMENT VENTING SYSTEM NOT PROVIDED.  
When the manufacturer of a product approved side wall  
horizontally vented gas fueled equipment does not  
provide the parts for the venting of flue gases, but  
identifies "special venting systems," the following  
requirements shall be satisfied by the manufacturer:  
1. The referenced "special venting system" instructions  
shall be included with the appliance or equipment  
installation instructions; and  
2. The "special venting systems" shall be product  
approved by the Board, and the instructions for that  
system shall include a parts list and detailed installation  
instructions.  
(e) A copy of all installation instructions for all products  
approved side wall horizontally vented gas fueled  
equipment, all venting instructions, all parts lists for  
venting instructions, and/or all venting design  
instructions shall remain with the appliance or  
equipment at the completion of the installation.  
1. INSTALLATION OF CARBON MONOXIDE  
DETECTORS. At the time of installation of the side wall  
horizontal vented gas fueled equipment, the installing  
plumber or gasfitter shall observe that a hard wired  
carbon monoxide detector with an alarm and battery  
back-up is installed on the floor level where the gas  
equipment is to be installed. In addition, the installing  
plumber or gasfitter shall observe that a battery  
operated or hard wired carbon monoxide detector with  
an alarm is installed on each additional level of the  
dwelling, building or structure served by the side wall  
horizontal vented gas fueled equipment. It shall be the  
responsibility of the property owner to secure the  
services of qualified licensed professionals for the  
installation of hard wired carbon monoxide detectors.  
a. In the event that the side wall horizontally vented gas  
fueled equipment is installed in a crawl space or an  
attic, the hard wired carbon monoxide detector with  
alarm and battery back-up may be installed on the next  
adjacent floor level.  
b. In the event that the requirements of this subdivision  
can not be met at the time of completion of installation,  
the owner shall have a period of thirty (30) days to  
comply with the above requirements; provided,  
however, that during said thirty (30) day period, a  
battery operated carbon monoxide detector with an  
alarm shall be installed.  
2. APPROVED CARBON MONOXIDE DETECTORS.  
Each carbon monoxide detector as required in  
accordance with the above provisions shall comply with  
NFPA 720 and be ANSI/UL 2034 listed and IAS  
certified.  
3. SIGNAGE. A metal or plastic identification plate shall  
be permanently mounted to the exterior of the building  
at a minimum height of eight (8) feet above grade  
directly in line with the exhaust vent terminal for the  
horizontally vented gas fueled heating appliance or  
equipment. The sign shall read, in print size no less than  
one half (1/2) inch in size, "GAS VENT DIRECTLY  
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".  
20  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
Recommended exhaust vent terminator position  
Fig. 21  
Ref.  
A
Description  
Minimum distance  
Directly below an opening; operable windows, doors and any non-  
mechanical fresh air openings  
36 in (twin pipe installation)  
48 in (single pipe installation)  
Below a gutter, sanitary pipework or eaves  
24 in  
12 in  
B
Below a gutter, sanitary pipework or eaves, protected by metal  
shielding  
C
From any internal corner  
12 in  
12 in  
7 ft  
Above ground or snow pack  
D*  
Above a paved sidewalk  
From an opposing wall or structure facing the termination  
From the relief valve of a Ip gas regulator  
From a terminator facing a terminator  
24 in  
36 in  
48 in  
E
F
G
Vertically between two exhaust vent terminators on the same wall  
60 in  
12 in  
H
Horizontally between two exhaust vent terminators on the same wall  
Horizontally and vertically from the combustion air inlet terminator  
36 in  
I**  
From the gravity combustion air inlet any other equipment  
From any external corner  
48 in  
12 in  
J
Horizontally from an opening; operable windows, doors and any non-  
mechanical fresh air openings  
K
12 in  
10 in  
L
From wall on exhaust applications  
Table 10  
* Subject to local codes and anticipated snow level  
** Other equipment that operates with a mechanical air inlet may require greater distances, reference manufacturer's instructions  
NOTICE: Exhaust and air intake must always be located  
on the same wall to cancel wind pressure effects.  
21  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
3.6.7 Exhaust vent configuration examples  
Fig. 22 Horizontal side wall venting installation  
Fig. 24 Vertical venting installation  
NOTE: If appliance uses room air, do not place any  
other combustion appliance in the same space, to avoid  
depressurizing of the building and winter freeze-up. Use  
room sealed operation instead.  
Fig. 23 Vertical venting installation  
Chimney  
-
Masonry  
22  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
Measure the length of gas supply line and use the tables  
in Fig. 26 or the gas line manufacturer’s sizing tables to  
determine the pipe diameter necessary to  
accommodate the BTU demand of the unit. If there are  
more gas drawing appliances on the line, size the gas  
line according to the total maximum amount of BTU  
draw for all appliances.  
3.7 Gas piping & connections  
Before connecting the gas supply, check the rating  
plate on the right side of the heater to be sure that the  
heater is rated for the same gas to which it will be  
connected.  
In the United States: The installation must conform with  
local codes or, in the absence of local codes, the  
National Fuel Gas Code ANSI Z223.1/NFPA 54.  
In Canada: The installation must conform to CGA B149  
INSTALLATION CODES and/or local installation  
codes.  
Note: Under sizing the gas line may result in diminished  
output and improper operation. See chapter 3.8 for the  
procedure to confirm gas pressure.  
Warning: DO NOT connect to an  
unregulated or high pressure propane  
line or to a high pressure commercial  
natural gas line.  
Warning: The heater must be isolated  
from the gas supply piping system  
during any pressure testing of that  
system at test pressures equal to or  
more than 0.5 psig. If overpressure has  
occurred, such as through improper  
testing of the gas lines or malfunction of  
the supply system, the gas valve must  
be checked for safe operation.  
Inlet gas particle screen  
Gas piping  
Fig. 25  
GAS CONNECTIONS  
B Install a manual gas shut off valve (installer supplied)  
on the gas supply line.  
B Install a union when connecting gas supply.  
B The minimum diameter required for any appliance  
connector used is ¾”.  
B National Fuel Gas Code requires that a sediment  
trap (drip leg) be installed on gas appliances not so  
equipped. The drip leg must be accessible and not  
subject to freezing conditions. Install in accordance  
with the recommendations of the serving gas  
supplier.  
When connections are made, check for gas leaks at all  
joints. Apply some gas leak detection solution to all gas  
fittings. Bubbles are a sign of a leak. A combustible gas  
detector may also be used to detect for leaks.  
Danger: If you have a leak, shut off the  
gas. Tighten appropriate fittings to stop  
leak. Turn the gas on and check again  
with a gas leak detection solution.  
Never test for gas leaks using a match  
or flame.  
GAS LINE SIZING  
The gas supply piping should be sized according to the  
applicable code for a maximum draw of 120,000 BTUH  
(GWH450ESR) or 96,000BTUH (GWH345ESR).  
23  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
FOR NATURAL GAS  
Maximum Capacity of pipe in Cubic Feet of Gas per Hour for Gas Pressure of 0.5 Psig or less and a Pressure drop  
of 0.3 in Water Column (0.75mbar).(Based on a 0.60 Specific Gravity Gas) Btu numbers given in thousands.  
Follow boxed numbers for piping just one GWH-450-ESR (example: ¾” B.I. Natural Gas pipe for 20 ft  
(6.1m). will handle 190,000 btu’s (55.7 kWh). For multiple appliances combine the total btu input load and  
then refer to applicable chart below. Follow the shaded numbers for just one GWH-345-ESR.  
Nominal  
Iron  
Length of Black Iron Pipe, Feet  
Pipe  
Size,  
Internal  
Diameter  
(inches) (inches)  
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
125  
150  
175 200  
1/4  
3/8  
1/2  
0.364  
0.493  
0.622  
32  
72  
22  
49  
92  
18  
40  
73  
15  
34  
63  
14  
30  
56  
12  
27  
50  
11  
25  
46  
11  
23  
43  
10  
22  
40  
9
8
8
7
6
21  
38  
18  
34  
17  
31  
15  
28  
14  
26  
132  
3/4  
1
0.824  
1.049  
278  
520  
190  
350  
152  
285  
130  
245  
115 105  
96  
90  
84  
79  
72  
64  
59  
55  
215 195 180  
170  
160  
150  
130  
120  
110 100  
1 1/4  
1 1/2  
2
1.380  
1.610  
2.067  
2.469  
3.068  
4.026  
1050  
1600  
3050  
4800  
8500  
730  
590  
890  
500  
760  
440 400 370  
670 610 560  
350  
530  
320  
490  
930  
305  
460  
870  
275  
410  
780  
250  
380  
710  
225 210  
350 320  
650 610  
1100  
2100 1650 1450  
3300 2700 2300  
5900 4700 4100  
1270 1150 1050 990  
2 1/2  
3
2000 1850 1700 1600 1500 1400 1250  
3600 3250 3000 2800 2600 2500 2200  
1130 1050 980  
2000 1850 1700  
4
17,500 12,000 9,700 8,300 7,400 6,80 6,200 5,800 5,400 5,100 4,500 4,100 3,800 3500  
Length of Flexible Corrugated Stainless Steel Tubing (CSST), Feet  
Tube  
size,  
inches  
EHD*  
10  
20  
58  
30  
47  
96  
40  
41  
50  
37  
60  
34  
1/2  
3/4  
1
18 EHD 82  
23 EHD 161 116  
83  
75  
68  
30 EHD 330 231 188  
162  
325  
144  
292  
131  
267  
* EHD = Equivalent Hydraulic Diameter. The greater the  
value of EHD, the greater the gas capacity of the tubing.  
1 1/4 37 EHD 639 456 374  
FOR LP GAS  
Maximum Capacity of Pipe in Thousands of BTU per Hour of Undiluted Petroleum Gases (at 11 inches Water Column Inlet  
Pressure) (Based on a Pressure Drop of 0.5 Inch Water Column).  
* EHD = Equivalent Hydraulic Diameter. The greater the  
value of EHD, the greater the gas capacity of the tubing.  
Length of Flexible Corrugated Stainless Steel Tubing (CSST), Feet  
Nominal  
Tube  
size  
iron  
Black Iron Pipe  
pipe  
Length of Pipe, Feet  
inches  
EHD*  
10  
20  
91  
30  
74  
40  
64  
50  
58  
60  
53  
Inches  
10  
20 30 40 50 60 80 100 125 150 200  
1/2  
3/4  
1
18 EHD 129  
1/2  
3/4  
1
291 200 160 137 122 110 94  
84  
74  
67  
58  
608 418 336 287 255 231 197 175 155 140 120  
1145 787 632 541 480 434 372 330 292 265 227  
23 EHD 254 183 151  
30 EHD 521 365 297  
131  
256  
449  
118  
227  
397  
107  
207  
359  
1 1/4 37 EHD 971 661 528  
Maximum Capacity of Semi-Rigid (flexible, non  
corrugated) Tubing in Thousands of BTU per Hour of  
Undiluted Liquefied Petroleum Gases (at 11 inches  
Water Column Inlet Pressure).  
Copper  
Length of Tubing, Feet  
Outside  
diameter  
Inch  
10 20  
39 26  
92 62  
30 40  
21 19  
50 41  
50  
_
60 70 80 90 100  
3/8  
1/2  
_
_
_
_
_
(Based on a Pressure Drop of 0.5 Inch Water Column)  
37  
79  
35 31 29 27 26  
72 67 62 59 55  
* Source National Fuel Gas Code NFPA 54, ANSI  
Z223.1 - No Additional Allowance is necessary for an  
ordinary number of fittings  
5/8 199 131 107 90  
3/4 329 216 181 145 131 121 112 104 95 90  
Fig. 26  
24  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
3.8 Measuring gas pressure  
Static Gas Pressure Reading (see Chapter 3.8)  
Connecting manometer  
enter here: ___________________  
B Turn power off.  
B Shut off gas supply.  
Operating Gas Pressure Reading (see Chapter 3.8)  
B Remove front cover and locate the inlet gas  
enter here: ___________________  
measuring point (see Fig. 27).  
Table 11  
B Loosen screw inside test point fitting (do not remove)  
and connect manometer tube on test point.  
3.9 Checking restrictor plate size by  
measuring CO level value.  
2
B Remove brass flat head screw on the exhaust collar.  
Fig. 27 Gas pressure measuring (lower tapping)  
Static pressure test  
Fig. 28 Measuring port  
B Turn gas supply on.  
B Insert CO analyzer probe into the measuring point.  
2
B Operate all other gas appliances on same gas piping  
The tip of the probe should be in the center of the flue  
pipe. Avoid air gaps between probe and measuring  
port to avoid inaccurate readings.  
system at maximum output.  
B Keep unit off and record static pressure reading in  
Table 11.  
B Press On/Off button to turn heater On.  
For this test the unit has to be put in Service Level.  
Operating pressure test  
B Open a hot water tap.  
B Press On/Off button to turn heater On.  
For this test the unit has to be put in Service Level  
B After 10 seconds, press and hold the reset button  
.
B After 10 seconds, press and hold the reset button  
B Rotate the recirculating water temperature selector  
.
(left knob) to the minimum and then to maximum.  
B Rotate the recirculating water temperature selector  
B Release the reset button and the display should  
(left knob) to the minimum and then to maximum.  
show * (blinking).  
B Release the reset button and the display should  
B Rotate the hot water temperature selector  
to the  
show * (blinking).  
maximum.  
The unit has now entered Service Mode.  
B The restrictor size is correct if the CO level is within  
2
B Place a demand for heat by turning external tank ther-  
mostat control to maximum for unit to fire at maximum  
input.  
the values as per table 13.  
CO2 value (%)  
B Record operating pressure reading in Table 11.  
B Press On/Off button to turn heater Off and exit  
enter here: ___________________  
Table 12  
Service Mode.  
Note: after verification tighten the screw  
inside the test point.  
Appliance  
CO (%)  
2
i
GWH-345-ESR-N  
GWH-345-ESR-L  
GWH-450-ESR-N  
GWH-450-ESR-L  
6.8 - 7.2  
7.5 - 8.0  
6.5 - 7.0  
7.0 - 7.5  
Operating gas pressures lower than 5.5" W.C. for nat-  
ural gas or 11" W.C. for LP will result in improper oper-  
ation and must be corrected. See Chapter 3.7 for gas  
line sizing requirements.  
Table 13 CO levels at max. input  
2
25  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation instructions  
B If the CO content is too high, use the next smallest  
piping. Blow out or flush the lines before connecting  
to the water heater.  
2
restrictor.  
B After replacing the restrictor, measure CO level  
B Full port shut off valves should be installed on both  
the cold water supply and hot water outlet lines to  
facilitate servicing the heater (see Fig. 30).  
2
again. Repeat procedure until correct level is  
obtained.  
B Once correct reading is obtained, replace screw with  
Connecting the pressure relief valve (PRV)  
gasket in exhaust collar.  
The listed pressure relief valve supplied with the heater  
must be installed at the time of installation. No valve is  
to be placed between the PRV and the heater. No  
reducing coupling or other restriction may be installed  
in the discharge line. The discharge line must be a  
minimum of 4” above a drain and installed such that it  
allows complete drainage of both the PRV and the line.  
The location of the PRV must be readily accessible for  
servicing or replacement, and be mounted as close to  
the water heater as possible. See Fig. 30. To install the  
PRV, a suitable fitting connected to an extension on a  
“T” fitting can be sweated to the hot water line.  
Support all piping.  
B Press On/Off button to turn heater Off and exit  
Service Mode.  
3.10 Water connections  
B When facing the heater, the ¾” NPT inlet is on the  
bottom right and the ¾” NPT outlet is on the bottom  
left (Fig. 29). Install the heater centrally in the build-  
ing if possible and make piping runs as short as pos-  
sible.  
Fig. 30 Plumbing Connections and Pressure Relief  
Valve  
OUTLET  
Fig. 29  
INLET  
3.11 Electrical connections  
Warning:  
For  
safety  
reasons,  
B The use of unions when connecting both water pipes  
to the inlet and outlet connections is recommended.  
This will facilitate any necessary servicing.  
disconnect the power supply to the  
heater before any service or testing is  
performed.  
B Although water piping throughout the building may  
be other than copper, we recommend that copper or  
suitably rated stainless steel flex line piping be used  
for the water connections for 3’ on either side of the  
recirculating water heater (follow local codes if more  
stringent).  
Warning: This heater must be  
electrically grounded in accordance  
with the most recent edition of the  
National Electrical Code. NFPA 70. In  
Canada, all electrical wiring to the  
heater must be in accordance with local  
codes and the Canadian Electrical  
Code, CSA C22.1 Part 1. Do not rely  
on the gas or water piping to ground the  
metal parts of the heater.  
B Never sweat any rigid piping directly to or beneath  
the water connections, damage can occur to the  
internal heater components during the sweating  
process.  
B Plastics or other PEX type plumbing line materials  
are not suitable for connecting directly to the water  
heater.  
The GWH-345/450-ESR requires an electrical power  
supply from a 120VAC 60Hz circuit and must be  
properly grounded.  
B Keep water inlet and outlet pipes to no less than ¾"  
(19.05mm) diameter to allow the full flow capacity.  
A means for switching off the 120VAC power supply  
must be provided.  
The heater is wired as shown in the wiring diagram  
(chapter 4.8, Fig. 35).  
B If the cold and hot connections to the heater are  
reversed, the heater will not function correctly. Be  
certain there are no loose particles or dirt in the  
26  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operating instructions  
4
Operating instructions  
B Use only your hand to press the on/off control switch.  
Never use tools. Follow these instructions exactly. If  
control switch is jammed, close the gas supply and  
call a qualified service technician. Attempted forceful  
repair may result in a fire or explosion.  
4.1 Initial filling instructions  
Before proceeding with the operation of the heater  
make sure that the system is filled with water:  
B Turn off power supply to heater.  
B Open the cold water inlet supply to the heater fully.  
B Do not use this appliance if any part has been under  
water. Immediately call a qualified service technician  
to inspect the appliance and to replace any part of  
the control system and any gas control which has  
been under water.  
B Open a hot water faucet to permit the water to fill the  
heater and the piping and to eliminate the air trapped  
in the system.  
B Close the hot water faucet after the water flows freely  
and all the air has escaped from the system. Turn on  
power supply to heater. The water heater is now  
ready to operate.  
4.3 Startup instructions  
B 1. STOP! Read the previous safety information.  
B 2. The gas valve must be shut off by putting the ON/  
OFF switch to position OFF. Wait five (5) minutes to  
clear out any gas. If you smell gas, STOP! Follow the  
safety information in Chapter 4.2 above. If you do not  
smell gas, go to the next step.  
B 3. This appliance is equipped with electronic ignition  
for lighting the main burners. When turning the  
heater on, follow these instructions exactly.  
B 4. Press the ON/OFF switch to the ON position. In  
this position, the water heater is ready to use.  
B 5. Connect tank Aquastat to the TT (thermostat)  
connection on the heater's printed circuit board.  
(Fig. 6, page 8). Close circuit on Aquastat to activate  
heater.  
Fig. 31  
4
On/Off button  
5
Reset button  
6
7
8
27  
Recirculation water temperature selector  
LED - (ON) warning light (blinks during lock-out error)  
Domestic hot water temperature selector  
Digital display  
B 6. The burners will remain on until the heat demand  
is met.  
NOTE: upon installation or after  
4.2 For your safety read before  
operating your water heater  
gas line work has been done, air  
i
in the gas line may cause a  
lockout error. Reset the unit  
(Fig. 31, pos. 5). The heater will  
reattempt ignition.  
Warning: If you do not follow these  
instructions exactly, a fire or explosion  
may result causing property damage,  
personal injury or loss of life.  
When the heater is in operation you may hear its  
induced draft vent fan and burner operating. After a call  
for heat is satisfied, the fan will continue to operate for  
up to 5 seconds to exhaust all flue gases.  
WHAT TO DO IF YOU SMELL GAS  
B Do not try to operate any appliance.  
B Do not touch any electric switch; do not use any  
TO TURN OFF GAS TO APPLIANCE  
phone in your building.  
B Turn off the manual gas shut off on the supply line to  
the heater and set the ON/OFF switch to the OFF  
position. Note: a manual gas shut off valve is not  
supplied with the heater.  
B Immediately call your gas supplier from a neighbors  
phone. Follow the gas supplier’s instructions.  
B If you cannot reach your gas supplier, call the fire  
department.  
27  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operating instructions  
4.4 Power  
4.6 Temperature and hot water flow  
Choose one the following:  
On  
• If using a tank mounted Aquastat, set temperature on  
Aquastat control (left knob should be in maximum  
position).  
To start the appliance:  
B press the ON/OFF  
button.  
LED (fig. 31) goes orange.  
When the burner is working, the LCD display shows  
• To activate and use the appliance domestic  
temperature dial, a 12 kOhm thermistor is required  
(part number 8 714 500 034) (See 2.6, Page 8 for  
wiring diagram).  
the symbol  
.
B Connect the 12kOhm thermistor blue wire to the  
DHW NTC terminal block.  
Install the sensor in the tank well.  
Hot water temperature can be set from 50°F to 158°F  
using hot water temperature selector  
(Fig. 34).  
Fig. 32  
Off  
To shut down the appliance:  
B press the ON/OFF  
switch to OFF position.  
4.5 Recirculating water temperature  
Water temperature can be regulated in a range of  
113°F to 190°F. The heater modulates the burner flame  
according to current demand selected on left knob.  
To select water temperature:  
B Rotate recirculating water temperature selector  
in order to change heating recirculating temperature  
(ranging from 113°F to 190°F).  
Fig. 34 Hot water temperature adjustment  
The display will show this symbol  
selected temperature.  
and blink the  
Thermostat  
knob position  
DHW  
temp.  
If the burner is on, symbol  
goes ON.  
Min.  
Max.  
approx. 50°F (10°C)  
approx. 158°F (70°C)  
Table 14 Domestic hot water temperature  
adjustment  
4.7 Freeze protection  
B Do not disconnect the electric supply from heater.  
B Do not install in unheated areas which can  
experience freezing temperatures.  
B Do not use non-potable additives like glycol.  
Fig. 33 Recirculating water temperature adjustment  
Freeze protection  
Freeze protection is always assured by the operation of  
the appliance.  
If the primary NTC (temperature) sensor detects  
temperatures 9°F below the selected temperature, the  
appliance starts on minimum power until the sensor  
reads selected temperature.  
In case of minimum setpoint it will start at 41°F.  
28  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operating instructions  
4.8 Electrical diagram  
Fig. 35 Electrical scheme  
10  
11  
12  
13  
14  
15  
16  
17  
Flame sensor  
Ignitor electrode  
Gas valve  
Junction box (wiring of tank pump)  
Fan  
Temperature limiter / ECO  
Differential pressure switch  
TT connection - under low voltage cover plastic  
18  
Domestic hot water temperature sensor (12kOhm only -  
under low voltage cover plastic)  
LED  
Fuse  
19  
20  
NOTICE: Except for the fuse, there are no serviceable  
parts inside the electronics.  
29  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance and service  
5
Maintenance and service  
Adjusting parameters  
Warning: Always turn off the electrical  
power supply, turn off the manual gas  
valve and turn off the manual water shut  
off valves whenever servicing.  
B Rotate hot water temperature selector dial  
to  
change the value of the parameter (only parameter  
03 and 22).  
The unit should be checked once a year by a gas  
technician. If repairs are needed, the repairs should be  
done by a gas technician  
To remove front cover  
B Loosen the two Philips head screws (as shown in  
Fig. 2).  
B Pull control panel upwards and then pull it  
downwards.  
B Lift front cover panel upward and remove.  
Yearly maintenance  
Refer to diagrams on pages 35 and 36.  
• Inspect venting system for leaks, blockage or other  
damage  
• Unclip 4 access clips and remove cover to inspect  
and clean burner assembly  
• Manual operation of the pressure relief valve to insure  
correct operation  
• If flow is reduced or error AA is activated, flush the  
heat exchanger with a descaling solution if mineral  
build up is evident. Scale build up will shorten the life  
of the water heater and is not covered by warranty.  
Descale heat exchanger thoroughly and repeat  
annually depending on mineral content of ground  
water.  
5.1 Service mode  
The service mode provides diagnostic information to  
the technician with a variety of real time parameters.  
See Table 15 for the parameters and their respective  
meaning.  
Accessing the service mode  
B Switch on the equipment.  
B Press and hold the reset button  
B Rotate the hot water temperature sensor dial  
the minimum and to the maximum.  
to  
Now the appliance is in the Service Mode.  
Selecting parameter  
B Rotate the recirculating water temperature selector  
(left dial) to scan the different parameters.  
Rotating clockwise accesses the next parameter  
(increasing).  
Once the desired parameter number has been  
selected, the digital display will change to the value  
stored in that parameter.  
30  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance and service  
Mode  
Parameter  
Values  
01  
02  
03  
Not used  
----------  
----------  
Not used  
Displays the last 8 error codes. Use the hot water temperature selector  
(right dial) to toggle from newest (left) to oldest (right) error codes.  
Error code history  
04  
05  
06  
Actual primary circuit  
temperature  
Displays the actual temperature in the primary circuit as detected by  
the internal heating circuit sensor.  
Selected primary circuit  
temperature  
Displays the recirculating water temperature (primary) as selected  
by the user during normal operation.  
Actual DHW temperature (only  
if 12kOhm thermistor used)  
Displays the actual temperature of the DHW tank as detected by  
the 12kOhm external thermistor  
Selected DHW temperature  
(only if 12kOhm thermistor used)  
Displays the hot water temperature as selected by the user during non-  
diagnostic mode operation (only if 12kOhm external thermistor used).  
07  
08  
09  
Not used  
----------  
00 - Open pressure switch - fan is off or there is no exhaust gas flow  
Pressure switch  
01 - Closed pressure switch - fan is on or there is exhaust gas flow  
10  
Temperature limiter  
01 - temperature is below the limit (180 F)  
E9 - temperature is above the limit (180F)  
----------  
11  
12  
Not used  
Gas valve  
00 - gas valve closed  
01 - gas valve open  
00 - gas valve closed  
01-70 - gas valve position min/max  
00 - thermostat open  
01 - thermostat closed  
00 - fan off  
13  
14  
15  
16  
Modulating gas valve  
Thermostat  
Fan  
01 - fan on  
00 - no flame detected  
01 - flame detected  
----------  
Ionization  
17  
18  
19  
20  
21  
22  
Not Used  
Not Used  
----------  
Not Used  
----------  
Not Used  
----------  
Digital display test  
Temperature unit selection  
All LCD components appear  
Use the hot water temperature selection knob to select temperature  
units °C or °F.  
Table 15  
Parameter storage  
Exiting service mode  
B Keep pressing the reset button  
for at least 2  
B Press ON/OFF button to turn appliance OFF and  
seconds in order to record adjustments. The digital  
then back ON again.  
display blinks with the symbol  
.
If the appliance is not powered off and  
then back on again, it returns to normal  
working conditions after 5 minutes.  
i
31  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
6
Troubleshooting  
Fault Indication  
Possible Cause  
Check  
E9  
Shut down by the temperature limiter  
(over temperature).  
1. Check position of heating NTC  
2. Check temperature limiter, cables  
3. Check system with air, air vent  
4. Bleed air from system.  
EA  
No Flame detected (no ignition).  
1. Check gas inlet pressure, gas  
type, air inside gas pipe  
2. Check flame, ignition  
3. Check burner pressure, injectors  
4. Check ionisation sensor, cable  
1)  
5. Check electronic unit .  
F7  
"false flame" (error during self check of  
electronic).  
1. Check for moisture on the  
Electronics  
2. Check cables, sensor contacts  
(corrosion)  
3. Check flame inside Burner  
chamber  
1)  
4. Check electronic unit .  
E0  
F0  
Shut down because of low voltage.  
Internal error in the electronic unit.  
1. Check power supply  
2. Check electronic unit .  
1)  
1. Check electronic unit connections  
and wiring.  
2. Replace electronic unit.  
C4  
C6  
Fan not working  
1. No power to fan, check for 115  
volts at fan  
2. Check wire connections.  
Shut down by pressure switch.  
1. Blocked vent  
2. Fresh air supply inadequate  
3. Silicone tubes from pressure  
switch not connected - clear or clear  
and black  
4. Check wire and connection.  
E2  
A7  
AA  
Heating - NTC defect (no function)  
1. Check heating - NTC  
2. Check cable (opened, short)  
3. Check electronic unit .  
1)  
Domestic hot water - Tank NTC defect  
(no function)  
1. Check domestic hot water - NTC  
2. Check cable (opened, short)  
3. Check electronic unit .  
1)  
Flow reduced  
1. Check heat exchanger - flush or  
descale if necessary.  
LED or LCD of the appliance doesn't No voltage supply, fuse blown,  
start up, no function. transformer etc. defect  
1. Check voltage supply  
2. Check fuse  
3. Check electronic unit .  
1)  
Noise; boiling noise (over heating), no Low circulation, air inside installation,  
1. Check air in system, air vent  
2. Check heating circulation  
3. Check heat exchanger  
4. Check gas type, injectors, gas  
valve.  
correct function.  
bad heat transfer.  
Table 16  
32  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Fault Indication  
Possible Cause  
Check  
Only tank loading (no heating function). No heat demand by the thermostat,  
1. Check thermostat position  
1)  
thermostat not well adjusted, other  
defect.  
2. Check electronic unit .  
Only heating (no tank load function).  
Low temperature (domestic hot water).  
No heat demand by the NTC, defect.  
1. Check NTC cable  
2. Check water (filter, …)  
3. Check Domestic hot water - NTC  
(Tank)  
1)  
4. Check electronic unit .  
To low burner power, burner ON / OFF.  
1. Check air vent  
2. Check Adjustment of gas, gas  
valve  
3. Check Domestic hot water-NTC  
1)  
4. Check electronic unit .  
Insufficient water flow.  
Low water pressure  
1. Check inlet pressure  
Filter, taps or heat exchanger with  
dirt.  
2. Check filter, taps, heat exchanger  
and clean.  
Table 16  
1)  
Check connections, fuse or if there are visible damages.  
Error lock-out is indicated by the orange LCD blinking. An error lock-out is done for safety reasons. After fixing the  
problem, press the reset button to return the heater to service.  
33  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GWH-345/450-ESR Functional scheme  
7
GWH-345/450-ESR Functional scheme  
APS - Air Pressure Switch  
Fig. 36 Functional scheme  
34  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Interior components diagram and parts list  
8
Interior components diagram and parts list  
8.1 Interior components  
Fig. 37 Components  
1
2
3
Combustion air inlet adapter (right side only)  
Exhaust adapter with CO2 measuring point  
Front cover  
4
On/Off button  
5
Reset button  
6
7
8
Recirculation water temperature selector  
LED - (ON) warning light (blinks when in lock out)  
Domestic hot water temperature selector  
Gas valve  
Junction box  
Centrifugal blower  
Main burner  
Heat exchanger  
Holding bracket  
Outlet water pipe  
12  
20  
21  
22  
23  
24  
25  
26  
Inlet water pipe  
35  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Interior components diagram and parts list  
8.2 Components diagram  
Fig. 38 Components Diagram  
36  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Interior components diagram and parts list  
8.3 Parts list  
Item  
Description  
Reference  
Item  
Description  
Reference  
2
Screw  
8 703 404 089  
8 703 401 069  
2 910 952 122  
8 701 003 010  
8 711 304 287  
2 910 619 409  
8 710 103 060  
8 708 107 008  
2 910 642 082  
8 708 107 009  
GROUP 1  
3
Screw  
1
Front cover  
8 705 431 223  
2 910 612 435  
8 701 103 140  
8 704 701 077  
8 708 006 130  
8 710 203 039  
8 700 100 376  
8 703 403 012  
8 708 003 218  
8 705 504 149  
8 716 140 939  
2 910 612 424  
8 711 004 022  
8 709 918 779  
4
Screw M4 x 12 phillips  
Washer  
2
Cover screw no. 10 x 22mm  
Trade mark badge  
Gasket  
9
3
10  
11  
12  
13  
14  
15  
Angle bracket  
Screw  
4
5
Support set  
Washer 1"  
6
Grommet set  
Ignition electrode  
Screw m3.5x6 phillips steel  
Flame sensor  
GROUP 4  
7
Deflector plate  
8
Screw M4,8 x 9,5mm  
Angle bracket  
9
10  
11  
12  
13  
14  
14  
14  
15  
16  
17  
17  
18  
19  
Flue gas accessory  
Washer  
1
2
3
4
5
6
Gas valve  
8 707 021 333  
8 705 202 126  
8 700 103 014  
8 703 305 325  
8 700 205 144  
2 912 601 120  
Connector  
Screw 8x3/8" philips  
Washer  
Washer- fibre 24OD X 16ID X 2MM  
Connection bush  
O-ring  
Throttle disc set (GWH345ESR)  
Throttle disc set (GWH450ESR NG) 8 709 918 780  
Screw  
Throttle disc set (GWH450ESR LP)  
Combustion air accessory  
Clip  
8 709 918 782  
8 705 504 148  
8 701 201 032  
8 701 302 099  
8 701 302 235  
8 701 302 225  
8 708 003 143  
GROUP 5  
1
Front cover  
8 707 207 219  
8 702 000 309  
8 705 400 069  
8 703 403 074  
8 705 400 056  
8 708 300 193  
1 904 522 745  
8 707 204 061  
8 703 305 302  
8 700 703 049  
8 707 406 007  
Holding bracket (GWH345ESR)  
Holding bracket (GWH450ESR)  
Cover  
2
Selector knobs  
Cover  
3
4
Screw  
Mounting bracket with screws  
GROUP 2  
5
Cover  
6
Printed circuit board  
Fuse T3, 15A  
Centrifugal blower  
Differential pressure line  
Set of hose  
7
1
Heat exchanger (GWH345ESR)  
Heat exchanger (GWH450ESR)  
Temperature limiter/ECO 104°C  
Washer 25OD X 21ID X 2MM  
8 705 406 323  
8 705 406 329  
8 707 206 204  
8 700 103 125  
8 713 300 018  
8 710 103 045  
8 700 703 163  
8 700 205 135  
8 700 400 015  
8 703 305 326  
8 714 606 002  
8 701 309 158  
8 743 401 019  
8 703 309 001  
2 910 642 162  
8 716 102 607  
8
1
9
2
10  
11  
3
Pressure differential switch  
(GWH345ESR)  
4
Locknut G 1/2"  
Fiber washer 18.6x13.5x1.5  
5
11  
Pressure differential switch  
(GWH450ESR)  
8 707 406 074  
6
Cold water pipe  
O-ring  
7
12  
Screw tapping no6 x 9.5  
Cable  
2 910 612 410  
8 704 401 311  
8 704 401 312  
8 704 401 309  
8 704 401 308  
8 704 401 310  
8 704 401 267  
8 704 401 295  
8 701 103 142  
8
Temperature sensor  
Connection bush  
Wireform spring  
Mounting bracket  
Screw  
13  
9
14  
Cable  
10  
11  
12  
13  
14  
15  
15  
Set of cables  
Cable  
16  
17  
Set of cables  
Power supply cord  
PCB wire harness  
Junction box  
Cage nut  
18  
Screw M 5.0X20 DIN 7985  
Clip  
19  
20  
GROUP 3  
Table 17  
1
Main burner LP (GWH345ESR)  
Main burner NG (GWH345ESR)  
Main burner LP (GWH450ESR)  
Main burner NG (GWH450ESR)  
8 708 120 625  
8 708 120 624  
8 708 120 623  
8 708 120 622  
1
1
1
Table 17  
37  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Protecting the environment  
9
Protecting the environment  
Packing  
The packing box may be fully recycled as confirmed by  
the recycling symbol  
.
Components  
Many parts in the heater can be fully recycled in the end  
of the product life. Contact your city authorities for  
information about the disposal of recyclable products.  
Saving water resources:  
B Make sure you close all the taps after any use. Avoid  
leaving the taps dripping. Repair any leaking tap.  
B Whenever possible use taps with built-in water flow  
limiters. They will give you the same comfort level  
while saving water.  
B Set the water temperature to the desired  
temperature or slightly higher. Hotter water  
temperatures can result in scalding and wasted  
energy.  
38  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ten Year Limited Warranty  
10 Ten Year Limited Warranty  
General  
costs associated with service, removal or re-installation  
of the original water heater or a replaced water heater.  
BOSCH PRO water heaters are warranted by the  
Manufacturer. Bosch Thermotechnology Corp. will  
furnish a replacement heat exchanger and will furnish a  
replacement of any part which fails in normal use and  
service within the applicable periods specified below, in  
accordance with the terms of this warranty. The  
replacement will be warranted for the unexpired portion  
of the original warranty. This warranty will be valid only  
for water heaters in possession of the original purchaser  
as recorded on the warranty card.  
NOTE: the water heater must be free of  
damaging scale deposits and not subject  
i
to gas pressures greater than those  
shown on the rating plate, which must not  
be altered, defaced or removed.  
How to Make a Claim  
Any claim for warranty parts should be made to your  
local dealer or distributor.  
The Heat Exchanger  
In most cases, the dealer or distributor will be able to  
promptly honor your claim and subsequently notify  
Bosch Thermotechnology Corp.. However, all  
replacements are made subject to validation by Bosch  
Thermotechnology Corp. of in-warranty coverage. The  
damaged or defective item must be made available in  
exchange for the replacement.  
If the heat exchanger fails within five (5) years after the  
original  
installation  
and  
operation,  
Bosch  
Thermotechnology Corp. will furnish a replacement  
heat exchanger at no charge. If the heat exchanger fails  
during years 6-10 after the original installation and  
operation, Bosch Thermotechnology Corp. will cover  
50% of the cost of a replacement heat exchanger.  
However, if the water heater is installed in other than a  
single family dwelling, this heat exchanger replacement  
warranty is limited to two (2) years from date of original  
installation and operation.  
Miscellaneous  
No one is authorized to make any other warranties on  
behalf of Bosch Thermotechnology Corp.. It is expressly  
understood that the replacement warranty of Bosch  
Thermotechnology Corp. shall be in lieu of any and all  
other warranties, express or implied, including  
warranties of merchantability or fitness for a particular  
use or purpose, and further that Bosch  
Thermotechnology Corp. shall not be liable for any loss  
or damage directly or indirectly arising from the use of  
the hot water heater, or for any consequential damages  
arising from such use (including damages from water  
leakage). Bosch Thermotechnology Corp. sole liability  
with respect to any defect shall be for the replacement  
of the defective part(s). Some states do not allow such  
limitations and exclusions, so the above may not apply  
to you.  
Exceptions  
This warranty will not apply:  
1. to defects or malfunctions resulting from failure to  
properly install, operate or maintain the unit in  
accordance with the printed instructions provided;  
2. to damage or abuse, accident, neglect or freezing  
and other acts of nature;  
3. to damage resulting from operation with either the  
flame sensor rod or overheat sensor removed;  
4. to failure of the heat exchanger resulting from the  
operation of the water heater in a corrosive  
atmosphere or at water temperatures exceeding the  
maximum rating, or if the water heater is not supplied  
with potable water;  
This warranty gives specific legal rights. You may also  
have other rights which vary from state to state.  
5. to defects or damage cause by any attachment  
or modification, including any energy-saving device.  
6. to damage resulting from scale deposits and/or  
highly mineralized / unsoftened water supply.  
All Other Parts  
If any other part fails within one (1) year after original  
installation and operation, Bosch Thermotechnology  
Corp. will furnish a replacement part free of charge.  
Service Labor Costs  
This warranty does not cover any labor costs  
associated with service, removal or re-installation of  
part(s). All such costs must be borne by the Purchaser.  
Additionally, this warranty does not cover any labor  
39  
6 720 607 909  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installer Checklist, to be performed by installer upon installation  
Serial Number  
___ ___ ___ ___ ___ ___ ___ ___  
(8 digit serial number is located on rating plate on right side panel)  
Gas Pressure reading*  
Static__________  
__________  
Operating__________  
CO reading  
2
Air restrictor size  
Building Water Pressure  
Installing Company  
Installer name  
Address  
__________  
__________ Range if on Well system __________  
_____________________________________________  
_____________________________________________  
_____________________________________________  
_____________________________________________  
Phone  
* See Chapter 3.8 and gas pressure table (to be filled out by installer)  
Installation manual should be left with the owner after the installation is tested and completed  
BOSCH THERMOTECHNOLOGY  
CORPORATION  
Bosch Termotecnologia SA  
Estrada de Cacia  
50 Wentworth Avenue  
Londonderry, NH 03053  
Tel. 866-330-2730  
3801 - 856 Aveiro - PORTUGAL  
Recycled paper  
© 2008 Bosch Thermotechnology Corp.,  
Londonderry, NH  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Blackberry Cell Phone SWD 1590032 0505111339 001 User Manual
Black Box Multi tool AVU4001A User Manual
Blaupunkt Car Stereo System Car CD Changer User Manual
Blaupunkt Car Stereo System RDM 126 User Manual
Bogen Microphone GDU150 User Manual
Bosch Power Tools Cordless Drill DDS182 02 User Manual
Califone Portable Speaker PA916 User Manual
Carrier Thermostat 53DFS250 FS User Manual
Char Broil Charcoal Grill 463270610 User Manual
Chicago Pneumatic Impact Driver CP8750 User Manual