9/14CBi, 14/19CBi, 19/24CBi
WALL MOUNTED BOILERS FOR CENTRAL HEATING
AND INDIRECT SUPPLY OF DOMESTIC HOT WATER
INSTALLATION AND
SERVICING INSTRUCTIONS
Worcester supports the
Benchmark code of practice
This appliance is for use with Natural Gas or LPG (Cat II 2H3P).
9/14CBi GC NUMBER 41 311 50 (N.G.)
14/19CBi GC NUMBER 41 311 52 (N.G.)
19/24CBi GC NUMBER 41 311 54 (N.G.)
9/14CBi GC NUMBER 41 311 51 (LPG)
14/19CBi GC NUMBER 41 311 53 (LPG)
19/24CBi GC NUMBER 41 311 55 (LPG)
APPLIANCE OUTPUTS
9/14CBi N.G.
14/19CBi N.G.
19/24CBi N.G.
Minimum 9.0 kW
Maximum 14.0 kW
Minimum 14.0 kW
Maximum 19.1 kW
Minimum 19.1 kW
Maximum 23.5 kW
9/14CBi LPG
14/19CBi LPG
19/24CBi LPG
Minimum 10.0 kW
Maximum 14.0 kW
Minimum 14.0 kW
Maximum 19.1 kW
Minimum 19.1 kW
Maximum 23.5 kW
IMPORTANT: THESE INSTRUCTIONS APPLY IN THE UK ONLY
AND MUST BE LEFT WITH THE USER OR AT THE GAS METER
Read the instructions before starting work - they have been written to make
the installation easier and prevent hold-ups.
Download from Www.Somanuals.com. All Manuals Search And Download.
working at a gauge pressure of at least 0.35bar above the relief
valve setting if on a sealed system.
Fig. 1. Water flow diagram.
Where a storage system will not have a vent to atmosphere the
installation must comply with Building Regulations and Water
Company bye-laws. If connecting to an existing system the local
authority should be informed.
Pipes
Return Flow
2.7 Flue
There are 3 fluing options available.
(i)
Rear Only Flue Kit.
Flue can be fitted within
the height of the casing from
220mm to 375mm without
cutting.
The minimum length is
100mm with cutting.
No flue bends or extensions
can be fitted to this system.
Side view
(ii)
Multi-Directional Horizontal Flue Kit.
Standard Flue Kit
can be adjusted from
425mm to 725mm without
cutting.
The minimum length is 250
mm with cutting.
Extended flue lengths upto
Alternative position
a
maximum of 2.5m
of Flow and Return pipes
(19/24CBi) and 3.0m (9/14
and 14/19CBi) are available.
NOTE: Flow pipe is at the rear
in the alternative position.
Flow Return
Optional 45° and 90° flue
bend kits are available
NOTE: When using flue
bends the maximum flue
length is reduced (see
Section 11.2.8).
2.10 Operation
Central Heating
A demand for heat will ignite the burner. The temperature is
controlled by the integral sensor. At the end of the demand the
burner will go out and the pump will continue to run for up to 4
minutes and the fan for 1 minute to dissipate the residual heat.
Side view
If access to the flue is a
problem then this option
combined with an internal
flue fixing kit should be
used.
Domestic Hot Water:
The supply of domestic hot water depends upon the type of hot
water equipment installed and the control system.
The use of unvented cylinders must be in accordance with the
manufacturers instructions and relevant to British Standards.
(iii) Vertical Flue Kit
A vertical flue option is also available with flue lengths from
1.1m (without cutting) to a maximum of 3.35m (19/24CBi) or
4.1m (9/14 and 14/19CBi). Optional 45° and 90° bends are
available with this option. NOTE: When using flue bends the flue
length is reduced (see Section11.2.8).
The boiler is despatched from the factory with the flow and
return pipework prepared for top outlet connection.
The pipework can be orientated to allow connection from the
bottom by simply unplugging the bayonet style pushfit connec-
tions.
2.8 Controls
A control knob adjusts the boiler temperature, switches the
boiler ON or to STANDBY and acts as a lock-out reset.
NOTE: When changing from a top connection to one at the bot-
tom the pipe functions are reversed.
Top flow pipe becomes the bottom return pipe.
Top return pipe becomes the bottom flow pipe.
2.9 Safety
The appliance must not be operated with the inner casing cover removed.
The gas and electricity supplies must be turned off before
servicing or working on the appliance.
The drain off point on the return pipe becomes an air vent if the
pipes are reversed. In this case a drain point should be fitted
close to the appliance.
The casing is earthed through a push-on connector at the base.
When the casing is refitted this connection MUST be remade.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Technical Data
The data plate is fixed to the inner casing cover.
Table 1.
Factory set at maximum input
NOMINAL BOILER RATINGS (10 Minutes After Lighting)
APPLIANCE
BURNER
PRESSURE
m bar.
OUTPUT
INPUT (Net)
GAS RATE
3
kW
kW
m /h
14.00
11.50
9.00
15.28
12.70
10.11
20.57
17.96
15.38
25.74
23.35
21.16
15.28
13.18
11.17
20.57
17.96
15.38
25.74
23.35
21.16
11.0
7.3
1.62
1.41
1.07
2.18
1.90
1.63
2.72
2.47
2.24
0.63
0.54
0.45
0.84
0.73
0.63
1.05
9/14CBi NG
4.5
14/19CBi NG
19.05
16.52
14.00
23.45
21.25
19.05
14.00
12.00
10.00
19.05
16.52
14.00
23.45
21.25
19.05
11.5
8.5
6.0
12.0
9.8
7.8
27.2
20.4
15.4
25.4
19.0
13.9
29.9
24.6
20.2
19/24CBi NG
9/14CBi LPG
14/19CBi LPG
19/24CBi LPG
Table 2.
0.96
0.87
Natural Gas: Net Input = Gross Input x 0.901
Propane: Net Input = Gross Input x 0.921
FLUE DETAILS
HORIZONTAL FLUE
mm
110
150
425
WALL HOLE DIAMETER
EXTERNAL FIX
INTERNAL FIX
MINIMUM LENGTH
MAXIMUM LENGTH
MAXIMUM LENGTH
MINIMUM LENGTH
MAXIMUM LENGTH
STANDARD TELESCOPIC FLUE KIT
EXTENDED FLUE
725
2.5m (19/24CBi) or 3.0m (9/14 and 14/19CBi)
INTERNAL FLUE - REAR ONLY WITHIN CABINET
220
375
100
FLUE ASSEMBLY DIAMETER
VERTICAL FLUE
MINIMUM LENGTH
1100
3.35m (19/24CBi) or 4.1m (9/14 and 14/19CBi)
MAXIMUM LENGTH INCLUDING TERMINAL
NOTE: FOR VERTICAL FLUE REFER TO A SEPARATE LEAFLET FOR INFORMATION
Table 3 9/14CBi
Table 3 14/19CBi
HYDRAULIC RESISTANCE
HYDRAULIC RESISTANCE
FLOW/RETURN
DIFFERENTIAL
°C
FLOW/RETURN
DIFFERENTIAL
°C
BOILER OUTPUT RESISTANCE MIN. FLOW RATE
BOILER OUTPUT RESISTANCE MIN. FLOW RATE
kW
Metres
L/min.
kW
Metres
L/min.
0.06
0.13
0.28
6.5
20
11
11
0.09
0.26
0.52
10
20
11
11
9.0
14.0
11.7
18.2
18.2
24.8
14.0
19 .05
Table 3 19/24CBi
NOTE: Pump is fitted externally
HYDRAULIC RESISTANCE
FLOW/RETURN
DIFFERENTIAL
°C
BOILER OUTPUT RESISTANCE MIN. FLOW RATE
kW
Metres
L/min.
0.15
0.52
0.73
13.7
24.8
30.5
20
11
11
19.05
23.44
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4
FLOW - COPPER TAILS
MECHANICAL SPECIFICATIONS
22mm
RETURN - COPPER TAILS
GAS INLET
22mm
15mm COMPRESSION
600mm
CASING HEIGHT
CASING WIDTH
CASING DEPTH
WEIGHT - LIFT
390mm
260mm
9/14CBi 28kg
9/14CBi 41kg
14/19 & 19/24CBi 33.5kg
14/19 & 19/24CBi 47kg
WEIGHT - PACKAGED
Table 5
PERFORMANCE SPECIFICATIONS
9/14CBi 1.6 litres 14/19 & 19/24CBi 2.1 litres
MINIMUM 1.2M MAXIMUM 30M
82°C (nom)
PRIMARY WATER CAPACITY
STATIC HEAD
MAXIMUM FLOW TEMPERATURE
MAXIMUM CENTRAL HEATING SYSTEM OPERATING PRESSURE (Sealed System)
2.5 bar
MINIMUM CENTRAL HEATING SYSTEM SET PRESSURE
OUTPUT TO CENTRAL HEATING
(Sealed System)
0.12 bar
9/14CBi 9.0 - 14.0kw 14/19CBi 14.0 - 19.05kw 19/24CBi 19.05 - 23.45kw
NOx CLASSIFICATION FOR CBi APPLIANCES
SEDBUK NUMBER AND BAND*
Class 1
9/14CBi NG 78.5 D
9/14CBi LPG 81.0 D
14/19CBi NG 79.4 D
14/19CBi LPG 81.7 D
19/24CBi NG 78.4 D
19/24CBi LPG 80.8 D
* The value is used in the UK Government Standard Assesment Procedure (SAP) for the energy rating of dwellings. The test data from which it has been calculated
have been certified by the GASTEC noified body.
Table 6
GAS SUPPLY SYSTEM - BASED ON NG (G20)
TOTAL LENGTH OF GAS SUPPLY PIPE (COPPER) metres
3
6
9
12
3
MAXIMUMGAS DISCHARGERATE-PRESSUREDROP 1mbar. m /h PIPE DIAMETER mm
8.7
18.0
5.8
12.0
4.6
9.4
3.9
8.0
22
28
GAS SUPPLY SYSTEM - BASED ON PROPANE (G31)
TOTAL LENGTH OF GAS SUPPLY PIPE (COPPER) metres
3
1.5
8.0
15.9
6
9
12
—
3.6
7.2
PIPE DIAMETER mm
—
—
15
22
28
5.2
8.8
4.2
8.5
Table 7
CLEARANCES
(mm)
INSTALLATION
SERVICE
30
ABOVE APPLIANCE - INTERNAL REAR FLUE
30
180
600
200
5
ABOVE APPLIANCE - EXTERNAL FLUE TURRET
IN FRONT OF APPLIANCE
BENEATH APPLIANCE
180
600
200
5
RIGHT HAND SIDE
LEFT HAND SIDE
5
5 *
**
The appliance can be installed on the above clearance dimensions however, for improved access the following is suggested:
* Improved access - 50mm is recommended
** For improved access minimum clearance when fitted to an adjacent LHS wall is 100mm
NOTE: It is possible to fit the appliance in an unventilated compartment. Refer to Section 6 for details.
Table 8
SEALED SYSTEM CAPACITY - 10 litre vessel
TOTAL SYSTEM VOLUME litres
INITIAL
PRESSURE bar
1.0
INITIAL CHARGE PRESSURE bar
0.5
72
39
1.0
92
53
1.5
N/A
64
1.5
5
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Siting The Appliance
Fig. 3. Appliance pipework connections
The appliance may be installed in any room subject to the
requirements of the current IEE regulations and, in Scotland, the
relevant electrical provisions of the Building Regulations with
respect to the installation of appliances in rooms containing
baths or showers.
165mm
FLOW
RETURN
If the appliance is installed in a room containing a bath or
shower, any switch or appliance control using mains electricity
must NOT be able to be touched by a person using the bath or
shower.
The appliance shall not be installed in a room or internal space
below ground level when it is intended for use with LPG propane
(G31). This does not preclude the installation into a room or
space which are basements with respect to one side of the
building but are open to the ground on the opposite side.
The appliance is NOT suitable for external installation.
The wall must be able to support the weight of the appliance.
Refer to Table 4.
The specified clearances must be available for installation and
servicing. Refer to Table 7 and Fig.2.
88mm 36mm
25mm
GAS
The appliance can be installed in a cupboard/compartment to
be used for airing clothes providing that the requirements of
BS6798 and BS5440/2 are followed.
The clearance between the front of the appliance and the
cupboard/compartment door should be not less than 25mm for
air circulation.
Fig. 2. Appliance casing dimensions and
required clearances.
30mm*
External
flue turret
150mm
100mm
30mm
(Rear only flue)
142mm
Rear only flue
36mm
Rear only flue
Side view
Front view
260mm
600mm*
390mm
200mm*
5mm*
5mm*
Fixing clip
* Space required for installation and servicing. Refer to Table 7
6
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Flue terminal positions
6. Air Supply
The flue system must be installed following the requirements of
BS5440:1.
The standard flue kit length is 425 - 725mm. Extension kits for
flues up to 3.0m are available.
A separate vent for combustion air is not required.
The appliance can be fitted in a cupboard or compartment with
no vents for cooling, but the minimum clearances must be
increased to those given below. Refer to BS6798.
A rear flue suitable for walls from 220 - 375mm thick is available
which can be contained within the boiler casing.
The terminal must not cause an obstruction nor the combustion
products a nuisance.
Note: the clearance at the front is to a removable panel, e.g. door.
The user must be informed not to restrict the clearances by the
addition of extra shelves etc and that flammable materials must
not be stored in this compartment.
If the terminal is less than 2m above a surface to which people
have access then a guard must be fitted. The guard must be
evenly spaced about the terminal and fixed with plated screws.
A guard Type K2 can be obtained from Tower Flue Components,
Vale Rise, Tonbridge, TN9 1TB.
It is essential that products of combustion cannot re-enter the
building. Refer to Fig 4.
Above Appliance (when using Rear only Flue)
30mm
Above Appliance (when using
horizontal flue) 180mm
In front
Below
Right-hand side
Left-hand side
340mm
200mm
105mm
105mm
If the appliance is fitted in a cupboard or compartment with less
clearance than those stated in the table above (minimum
clearances are given in Section 4 Siting the Appliance) then
permanent air vents for cooling are required, one at high level
and one at low level. Both high and low level vents must
communicate with the same room or must be on the same wall
to outside air. The minimum requirements are:
Model Position of vent
Air from room Air from outside
2
2
19/24CBi
14/19CBi
9/14CBi
High
Low
High
Low
High
Low
255cm
128cm
2
2
255cm
207cm
128cm
104cm
2
2
2
2
207cm
152cm
104cm
2
2
76cm
2
2
152cm
76cm
Fig. 4. Siting of the flue terminal.
If the boiler is fitted between kitchen units and a decorative
door panel is fitted then the top and bottom of the space must
be left open.
*NOTE: A minimum of 75mm must be achieved
where the terminal is near fusible or combustible
material such as plastic drain pipes, guttering or a
carport roof UNLESS suitable heat shields are
provided.
A
L
G
B,C
K
L
D
K
F
F
HI
A
G
M
F
J
E
TERMINAL POSITION
MIN. DISTANCE
TERMINAL POSITION
MIN. DISTANCE
A– directly below an openable window or
I– From a terminal facing a terminal
1200mm
other opening e.g. air brick.
300mm
75mm
25mm
25mm
25mm
25mm
300mm
600mm
J– From an opening in a car port (e.g. door
B– Below gutters, soil pipes or drain pipes.*
C– Below eaves.*
D– Below balconies or car port roof.*
E– From vertical drain pipes and soil pipes.*
F– From internal or external corners.
G– Above ground, roof or balcony level.
H– From a surface facing a terminal.
window) into dwelling.
K– Vertically from a terminal on the same
wall.
L– Horizontally from a terminal on the same
wall.
1200mm
1500mm
300mm
300mm
M– From door, window or air vent.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
7. System
8. Domestic Hot Water
The system must comply with requirements of BS6798 and
BS5449.
The appliance is NOT suitable for direct water supply.
Do not connect to a direct cylinder.
General:
The CBi can be connected to any indirect cylinder, i.e unvented or
thermal store, and all the benefits of a "dry loft" and mains
pressure hot water can be realised. Contact The Worcester
Technical Helpline. 08705 266241.
The appliance is only suitable for connection to indirect fully
pumped sealed and open vent systems. The minimum static
head is 1.2m and the maximum is 30m.
The pump MUST be wired to the boiler control to ensure that the
pump-overrun function operates to prevent the risk of
overheating and hence nuisance shutdown.
The controls must be wired to ensure that the boiler does not
cycle when electronically controlled zone valves are closed.
A by-pass is required if the controls i.e. 2-port valves, can result
in the closure of the CH and DHW circuits when the boiler is hot.
If mechanically operated thermostatically controlled valves are
fitted on all radiators then a by-pass located at least 2m from the
boiler is required.
Cylinder
Indirect coil type or a direct cylinder with an immersion calorifier
that is suitable for a pressure of 0.35bar above the setting of the
pressure relief valve. Single feed indirect cylinders are NOT
suitable for sealed systems. Any connection to the mains water
supply must conform to the relevant Building and Water
Regulations and be approved by the local Water company.
A bypass is generally unecessary on a system using a 3 way diverter
valve as one port will be open to flow at all times. This will be
satisfactory for the pump overrun requirement. However if TRV's are
used throughout then a bypass or open radiator may be necessary.
Sealed System:
A sealed system must include an expansion vessel, pressure
relief valve and pressure gauge - these are available as
proprietary kits, the sealed system expansion vessel and fittings
must be connected at the neutral point of the system on the
entry to the pump. A pump and diverter valves are also required
as appropriate to the system. Refer to Fig 5,6,7.
The sealed system must be filled through a WRc approved filling
kit. Refer to Fig.8. The approved method for temporary
connection for filling a closed circuit in a house can be found on
Page 8.25. Fig R24-2a of the Water Regulation Guide and Water
Bylaws 2000 Scotland.
The appliance must not be operated without the system being
full of water and correctly pressurised.
All connections in the system must withstand a pressure of up to
3 bar.
The system and the appliance must be properly vented.
Repeated venting loses water from the system and usually
indicates that there is a leak.
For system wiring please refer to
Fig. 10. and the controls
manufacturers details.
Fig. 5. System layout if using Honeywell 'Y' plan
Feed and
Vent Cistern
S.H. – Minimum static head 1.2m
measured from the highest point in the
heating system (top surface of the appliance
S.H.
or highest point in the heating system) to the
Primary
S.H.
water level in the feed and expansion tank
cold feed
Domestic hot
water cylinder
(15mm min.)
Heating vent
(22mm min.)
Diverting
valve
N.B. A drain cock should be
installed at the lowest point of
the heating circuit
Pump
Radiator
Boiler
Bypass or
150mm max
uncontrolled
radiator
(if required)
8
Download from Www.Somanuals.com. All Manuals Search And Download.
For system wiring please refer to
Fig. 10. and the controls
manufacturers details.
Fig. 6. System layout if using Honeywell 'S' plan
Feed and
Vent Cistern
S.H. – Minimum static head 1.2m
measured from the highest point in the
heating system (top surface of the appliance
S.H.
or highest point in the heating system) to the
Primary
S.H.
water level in the feed and expansion tank
cold feed
Domestic hot
water cylinder
(15mm min.)
Heating vent
(22mm min.)
Diverting
valves
N.B. A drain cock should be
installed at the lowest point of
the heating circuit
Pump
Radiator
Boiler
Bypass or
uncontrolled
radiator
150mm max
For system
wiring
Fig. 7. Fully pumped sealed system.
please refer to
Fig. 10. and the
controls
manufacturers
Note:
A drain cock
INDIRECT
CYLINDER
details.
LV
LV
should be fitted
RV
RV
at the lowest
point of the
heating circuit
and beneath
the appliance
APPLIANCE
LV
LV
RV
Pressure
Gauge
RV
Bypass
balancing valve or
bathroom
Expansion
Vessel
radiatior with two
lockshield valves
Relief
Valve
Radiator Valve - Flow RV
Lockshield Valve - Return LV
Mains Cold Water
BS
Stop Valve Fixed Cylinder Type or sealed systems - Approved connection
Fig. 8. Sealed system filling and make-up.
Make up
vessel
Auto
Heating return
air vent
Non return
valve
Stop
cock
1200mm (48 in)
above the highest
point of the system.
Fill point
9
Download from Www.Somanuals.com. All Manuals Search And Download.
10. Electrical
9. Gas Supply
The gas supplier must be contacted to check the suitability of
the appliance for the local gas supply conditions before
connecting the appliance.
Mains Supply: 230V, 50 Hz, 125 watts.
External Fuse: 5A (must be to BS1362).
Internal Fuse: F1 4A (Spare supplied with appliance).
IP Rating: IP 20.
3
The 19/24CBi appliance requires a maximum of 2.72 m /h of
3
natural gas (G20), 1.05 m /h propane (G31).
The appliance must be earthed and it must be possible to
completely isolate the appliance.
3
The 14/19CBi appliance requires a maximum of 2.18 m /h of
3
The mains cable must be 0.75mm2 (24 x 0.2mm) to
BS6500 - Table 15 or 16
natural gas (G20), 0.84 m /h propane (G31).
3
The 9/14CBi appliance requires a maximum of 1.62 m /h of
3
natural gas (G20), 0.63 m /h propane (G31). Refer to Table 1.
Mains supply to the boiler and system wiring centre must be
through a common fused double pole isolator situated adjacent
to the appliance. The isolator must have a contact separation of
3mm minimum in all poles. A single switched live cable should
be wired into the boiler from the system wiring centre.
The mains and pump cables must be fed through the mains lead
bracket, secured through the cable clamp and connected to the
connector plug. Refer to Fig. 9, 10 and 11.
Frost protection of the boiler is provided on the control board.
A frost thermostat should be considered where parts of the
system are remote from the appliance. For any frost thermostat
function, the boiler temperature control knob must not be set to
the 'OFF' position. The frost thermostat must be fitted to the
system junction box in accordance with the manufacturers
instructions. Refer to Fig. 11.
A natural gas appliance must be connected to a governed meter.
The installation of the gas supply to the appliance must be in
accordance with BS6891.
The meter and the pipework to the appliance must be checked,
preferably by the gas supplier, to ensure that a dynamic pressure
of 20mbar for natural gas is available at the appliance
[equivalent to about 19.0 mbar at the gas valve inlet pressure
connection] and that the gas flow is adequate for all the installed
gas appliances or a dynamic pressure of 37 mbar equivalent to
36 mbar at gas valve inlet pressure connection on propane (G31).
Safety Check: If there is an electrical fault after installation check
for fuse failure, short circuits, incorrect polarity of connections,
earth continuity or resistance to earth.
Fig.9 . Mains electricity and controls
10
connections.
11
12
13
14
9
1
2
8
7
Earth post detail.
Note: Pump earth (top connection)
Mains earth (bottom connection)
3
4
5
6
Pump Earth
Mains Earth
9. Gas valve connection
10. Mains lead bracket
1. Base plate
2. Control board
3. Control knob
4. Fuse 4A
11. Spark electrode connection
12. Air pressure switch, temperature sensor,
overheat thermostat connection
13. Fan connection
5. External control connector block
6. Earth post
7. Cable clamp
8. Internal earth connection
14. Flame sense connection
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig.10. Boiler wiring diagram
Polarity of these connections is not
important.
Fan
*
Air pressure
switch
*
white
NC
grey
NO
brown
COM
Overheat
Thermostat
orange
black
*
Spark
Electrode
Flame
Sense
Electrode
Temperature
sensor
*
Gas Valve
X4
1
1
X6
X5
X3
X7
1
Control Board
blue
X2
brown
earth
Pump Live
Pump Neutral
Installer
Connections
X1
Permanent Neutral
Permanent Live
User control
potentiometer/switch
Switched Live (Boiler Demand)
3 pin header
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig.11 . System wiring diagram
System components wired into terminal strip
in accordance with component manufacturers instructions
System
wiring centre
Boiler/pump
demand from
system wiring
centre
L switched
Terminal strip
Pump not to be
connected to
system wiring
centre
230V 50Hz
(5A Fuse)
E
N
L
Common isolator
for wiring centre
and boiler
Pump
(supplied from
boiler only)
Should be located
adjacent to the
boiler
OUTSIDE OF BOILER
INSIDE OF BOILER
Cable clamp
Control Board
Pump L
Pump N
Permanent N
Permanent L
Switched L
(Boiler Demand)
X1
Earth post
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 12a. Boiler Assembly 9/14CBi
Shown set for Rear Only flue kit
26
18
17
20
19
21
16
22
1
15
2
14
3
13
25
4
12
11
5
24
23
6
9
10
7
8
1. Inner case
14. Overheat thermostat
15. Air pressure switch
16. Flow pipe
2. J bolts and wing nuts (2)
3. Combustion chamber cover
4. Burner
17. Return pipe
5. Burner fixing screw
6. Control knob
18. Combustion test point
19. Sensing tubes
7. Indicator lights
20. Fan
8. Base/controls fixing screw
9. Cabinet fixing screw
10. Gas valve
21. Flue hood
22. Inner case cover fixing points (4)
23. Outer case earth tag
24. Side cover plate
25. Wire clip
11. Spark electrode
12. Burner injector
13. Temperature sensor
26. Pressure tube junction
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 12b. Boiler Assembly 14/19 and 19/24CBi
Shown set for
horizontal flue or vertical flue
17
18
20
21
19
16
22
23
15
1
2
14
13
3
27
26
4
12
11
5
25
24
6
10
8
7
9
1. Inner case
15. Air pressure switch
16. Flow pipe
2. J bolts and wing nuts (2)
3. Combustion chamber cover
4. Burner
5. Burner fixing screw
6. Control knob
7. Indicator lights
8. Base/controls fixing screw
9. Cabinet fixing screw
10. Gas valve
11. Spark electrode
12. Burner injector
17. Return pipe
18. Combustion test point
19. Sensing tubes
20. Fan
21. Fan clamp (2 screws)
22. Inner case cover fixing points (4)
23. Flue hood
24. Outer case earth tag
25. Side cover plate
26. Wire clip
13. Temperature sensor
14. Overheat thermostat
27. Front baffle
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 13b . Flue and wall plate
11. Installing The Appliance
NOTE: READ THIS SECTION FULLY BEFORE COMMENCING THE
INSTALLATION
To install a boiler with a rear only flue refer to Section 11.1.
To install a boiler with a
to Section 11.2.
telescopic horizontal flue kit refer
To install a boiler with a vertical flue refer to Section 11.2. and the
literature with the flue kit.
11. Installation of the Boiler with a
Rear Only Flue Kit
Flue fixing position
11.1 Unpacking the Boiler
Check the contents against the packing list.
Remove the wall mounting template, the mounting plate
assembly and the external flue turret connector and restrictors.
11.1.4 Flue Preparation
11.1.2 Site Preparation
(i)
Drill the hole for the flue at 110mm diameter.
Check that the correct position for the appliance has been chosen
and that the wall is sound, flat and will support the weight of the
appliance. Refer to Sections 4 & 5 and Tables 4 to 8.
(ii)
Fix the wall-mounting plate - do not fully tighten the
screws.
11.1.3 Fixing Holes and Flue Opening
(iii) Measure the wall thickness L - Min 220mm, Max 375mm.
If L is less than 220mm thick then it is necessary to cut
the flue. To do this subtract L from 220 and cut all flue
parts by this amount.
Hold the template to the wall. Check that the template is level.
Mark the position of the fixing holes and the flue opening. Refer to Fig 13.
Mark the position of the bottom fixing point for a screw or
optional security bolt.
Ensure that the ducts are square and free from burrs.
Always check dimensions before cutting.
The minimum length L is 100mm with cutting.
Fig. 13 . Fixing the wall mounting plate.
(iv) Adjust the telescopic flue assembly to a length L+5mm
and secure with the screw supplied. Refer to Fig. 14.
(v)
Apply the plastic tape onto the duct in contact with the
wall (position shown in Fig. 14.).
Centre line
of boiler
(vi) Remove the inner flue duct (with the fixing bar).
(vii) Push the outer duct assembly through the wall mounting
plate and wall. Tighten the wall mounting plate fixing
screws after checking that the plate is level.
Centre line
of flue
Fig. 14 . Flue assembly - Rear Only Flue Kit
6
Fig. 13a . Wall plate
4
36mm
L + 5
Top of
boiler to
centre of
flue
3
=142mm
1
Tape
2
5
Centre line of boiler
Centre line of flue
1. Telescopic flue assembly
2. Terminal
3. Flange
4. Flue tube with fixing bar
5. Indents
6. Gasket - fitted to inner case
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 14a . Rear only flue assembly
3
L + 5
6
Tape
2
4
1
5
1. Telescopic flue assembly
2. Terminal assembly
3. Flange / flue assembly
4. Indents
5. Wall mounting plate
6. Flue tube with fixing bar
11.1.6 Install the Boiler
Fig. 14b . Rear of casing
IMPORTANT: Thoroughly flush the system before connecting the
boiler. Any system cleanser must be flushed from the system
before adding any inhibitor.
(i)
Lift the boiler onto the wall mounting plate. See Fig. 15.
(ii)
Level the boiler using the two levelling feet at the base of the
back panel.
(iii) Fit the bottom fixing screw (or optional security screw).
(iv) Connect the gas supply using the nut and olive supplied in the
literature pack - details of the position are shown in Fig. 3.
(v)
Connect the flow and return pipes to the system. It is important
that the flow and return pipes are not fixed near to the boiler
using clips that put a strain on the connections.
A drain point should be fitted close to the appliance if bottom
connections are made.
Always consider the possible need to disconnect and remove
the boiler.
Gasket
11.1.7 Installation of Flue onto Boiler
(i)
Pull the flue into position so that the holes in the flange
line up with those in the case
NOTE: The correct rectangular flue restrictor must now be fitted
11.1.5 Boiler Preparation
when the boiler is on the wall.
9/14CBi and 14/19CBi
66 X 62 (Rectangular)
19/24CBi
77 X 62 (Rectangular)
(i)
Remove the appliance casing by releasing the screw at
the centre base. Disconnect the earth connection at the base
and lift off.
(ii)
From the inside, place the correct restrictor in position
over the flue opening and using the screws provided, fix
through the inner casing into the flue system.
(ii)
Release the four screws and remove the inner casing cover.
(iii) Release the two wing-nuts and remove the combustion
chamber front panel. The cover is located into notches at
the base of the side plates. Leave the stainless steel baffles
in place.
(iii) Slide the inner flue duct with fixing bar into the flue.
(iv) Slide the fluehood and fan assembly back into position
engaging the fan outlet into the inner duct assembly
and reconnect the fan electrical terminals (polarity is not
important). Reconnect the pressure sensing tubes onto the
junction pieces. See Fig. 16.
(iv) Disconnect the fan electrical terminals and the sensing
tube from the junction pieces. Slide the flue hood/fan
assembly out of the boiler.
(v)
Ensure that the combustion chamber is slotted underneath
the flue hood and re-assemble with the combustion
chamber front and 'J' bolts.
(v)
From the literature pack take the self adhesive gasket
and stick around the rear flue opening on the outside of
the casing ensuring that the fixing holes are not blocked
(see Fig. 14b).
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 15 . Fixing the appliance to the wall mounting plate.
2
6
5
8
1
7
1. Telescopic flue assembly
2. Wall mounting plate
3
3. Fixing or security screw
4. Levelling feet (2)
5. Restrictor plate with rectangular hole
6. Gasket
7. Flue fixing screws
8. Flue tube with fixing bar
4
Fig. 16 . Fan/Flue hood Assembly with Rear Only Flue Kit
5
NOTE: The polarity of wires is
not important
6
11
9
—ve
1
10
1. Flue hood
2. Fan
+ve
3. Sensing connection (+)
4. Sensing connection (—)
5. Top outlet sealing plate
6. Fan lead clip
+
7. Fan fixing screws (2)
8. Pressure tube junction
9. — ve pressure tube
8
7
4 ( — )
2
10. + ve pressure tube
12
(clear tube)
11. — ve pressure tube extension
12. + ve pressure tube extension
3 (+)
(red tube)
17
Download from Www.Somanuals.com. All Manuals Search And Download.
11.1.8 Completion of the Installation
Check that all the gas and water connections have been
tightened.
Fig.17 . Mains electricity and controls
connections.
10
11
12 13
Lower the base plate/control panel. Refer to Fig. 17.
The permanent mains and switched live supply to the boiler
must come from the system junction box. Refer to Fig.11. A 4
core cable is recommended.
9
14
1
Feed the 4 core cable and the pump cables through the bracket
and secure in the cable clamp. Refer to Fig. 17.
2
Fit all the supply and pump wires to the 5 way plug before fitting
the plug to the socket on the board. This will avoid stress to the
board when using a screwdriver. Refer to Fig.11. for the
connections.
8
7
Check that the cables cannot touch the inner casing.
Test for gas soundness as described in BS6891.
4
6
5
3
1. Base plate
2. Control board
3. Control knob
4. Fuse 4A
5. External control connector block
6. Earth post
7. Cable clamp
9. Gas valve connection
10. Mains lead bracket
11. Spark electrode connection
12. Air pressure switch,
temperature sensor,
overheat thermostat
connection
13. Fan connection
14. Flame sense conection
If the appliance is not commissioned immediately, refit the
combustion cover, inner casing cover, base/controls assembly
and the casing. Re-connect the earth connection at the base of
the casing. Check that the gas and electricity services have been
turned off.
REFER NOW TO SECTION 12 - COMMISSIONING THE
APPLIANCE
8. Internal earth connection
9. Gas valve connection
11.2.4 Boiler Preparation
11.2 Installation of the Boiler with a
Telescopic Horizontal Flue Kit
(i)
Remove the appliance casing by releasing the screw at
the centre base. Disconnect the earth connection at the base
and lift off.
11.2.1 Unpacking the Boiler
Check the contents against the packing list.
Remove the wall mounting template, the mounting plate
assembly and the flue spigot and restrictors.
The flue spigot is positioned within the boiler carton and not in
the accessory pack.
(ii)
Release the four screws and remove the inner casing cover.
(iii) Release the two wing-nuts and remove the combustion
chamber front panel. The cover is located into notches at
the base of the side plates. Leave the stainless steel baffles
in place.
11.2.2 Site Preparation
(iv) Disconnect the fan electrical terminals and the sensing
tube from the junction pieces. Slide the flue hood/fan
assembly out of the boiler.
Check that the correct position for the appliance has been chosen
and that the wall is sound, flat and will support the weight of the
appliance. Refer to Sections 4 & 5 and Tables 4 and 8.
(v)
Remove the blanking plate from the top of the inner
casing and refit onto the rear flue opening ensuring a good
seal.
11.2.3 Fixing Holes and Flue Opening
Hold the template to the wall. Check that the template is level.
Mark the position of the fixing holes and the flue opening. Refer to Fig 13.
Mark the position of the bottom fixing point for a screw or
optional security bolt.
(vi) From the literature pack take the self adhesive gasket
and stick around the top flue opening on the outside of
the casing ensuring that the fixing holes are not blocked
(see Fig. 19).
Drill the 5 fixing holes 60mm deep for the No.12 size plugs.
(vii) Fix the spigot and the appropriate restrictor (if the flue is
less than 1m in length) to the top of the inner casing. Refer
to Fig. 19.
Fig. 18. Fixing the wall mounting plate.
The fixing screw hole on the spigot must be pointing to
the front.
Centre of boiler
IMPORTANT:
9/14CBi and 14/19CBi
Ø72mm
Top Exit Restrictors
19/24CBi
Ø79mm
(viii) The boiler is supplied for flow and return connections at
the top. If a bottom connection is required then pull out
the clips, remove and invert the pipes. Refer to Fig. 1.
NOTE: When changing the connections the pipe functions are
reversed -
Top flow becomes the bottom return
Top return becomes bottom flow
18
Download from Www.Somanuals.com. All Manuals Search And Download.
(iii) The method of installation of the flue system may be
varied to suit the actual site conditions. The instructions
for connecting and fixing the ducts must, however, be
strictly followed.
Fig.19. Flue turret fixing and combustion
sensing point
1
1
2
8
Remove all packing material from the flue components.
7
The standard telescopic flue assembly is suitable for lengths
from 425mm up to 725mm measured from the centre-line of the
boiler flue outlet to the outer face of the wall. Refer to Fig. 17.
1. Flue spigot fixing screws
2. Flue spigot
3. Restrictor ring (if required)
4. Gasket
5. Flue spigot fixing holes
6. Combustion sensing
point
3
If the length needed is greater than 725mm then extension duct
kit/s will be required - each kit extends the flue by 750mm up to
a maximum of 2.5m (19/24CBi) or 3.0m (9/14 and 14/19CBi).
See table below.
4
5
7. Clamping ring
8. Fixing screw hole
EXTENSION
MAXIMUM FLUE LENGTH mm
1475
6
1
2
3
3
2225
2500 (19/24CBi)
2975 (9/14 and 14/19CBi)
(iv) Measure length L. Refer to Fig 20, 21, 22.
(v)
For installation of standard flue up to 750mm refer to
Section 11.2.6.
For installation of flue greater than 750mm refer to
Section 11.2.7.
11.2.5 Flue Preparation
For installation of bend kits refer to Sections above and
Section 11.2.8.
(i)
Drill the hole for the flue at Ø110mm unless the optional
internal fitting kit (WHS part No. 7 716 191 019) is used in
which case a Ø150mm hole is required.
For installation of vertical adaptor refer to Section 11.2.9.
For installation of internal fitting kit refer to Sections
above and Section 11.2.10.
(ii)
Fix the wall mounting plate onto the wall. Ensure it is level
before tightening the screws.
Fig.20 . Extension Duct.
Tape
L
Turret
assembly
Terminal
Fixing screws
Fixing screw
assembly
Ducts of equal length
Appliance casing
Shorten first extension fitted
to the turret assembly if more
than one extension is fitted
Fig.21. Flue duct length (side flue).
Fig.22 . Flue duct length (rear flue).
L
Tape
L
Fixing
screws
Fixing
screws
Terminal
assembly
Flue
Turret
assembly
Tape
External
wall face
Rear face of appliance
and face of mounting
wall
19
Download from Www.Somanuals.com. All Manuals Search And Download.
11.2.6
Telescopic Horizontal Flue Kit up to
750mm in Length
11.2.8 Flue Bends
90° and 45° directional bends are available. A maximum of two
45° or 90° bends may be used in addition to the first bend on
the flue turret.
A 90° bend is equivalent to 750mm of straight duct.
A 45° bend is equivalent to 375mm of straight duct.
(i)
The standard flue can be telescopically adjusted to any
length between 425mm and 725mm.
It will only be necessary to cut the standard assembly if
L<425mm. Cut the flue turret assembly and the terminal
assembly by the same amount i.e L=350 - remove 75mm
from each assembly.
Measure the lengths X and Y. Refer to Fig.23.
The maximum value of X using the turret assembly only is
506mm. Reduce the ducts to the appropriate length e.g. X =
406mm, cut 100mm from the air duct and 120mm (to cover the
entry into the 45° or 90° elbow) from the flue duct. Refer to
Fig.24.
The minimum length L is 250mm with cutting.
General: Cut the ducts as necessary, ensuring that the ducts are
square and free from burrs. Always check the dimensions before
cutting.
The final section, dimension Y, of the flue system must include a
section of plain duct assembly i.e . an extension assembly with
the sockets removed. Reduce the final section, including the
terminal assembly, by the appropriate amount i.e. Air duct Y -
81mm and the flue duct Y - 51mm. Refer to Fig.23.
(i)
Fix the flue assembly together using the self-tapping
screws provided. Refer to Fig. 21, 22.
(ii)
Apply the plastic tape onto the duct in contact with the
wall (see Fig. 21, 22).
If an internal fitting kit is to be used refer now to Section 11.2.10
otherwise refer to Section 11.2.11.
If Y is smaller than425mm it will be necessary to cut the air and
flue ducts of the extension to a plain length of 100mm and
reduce the length of the terminal assembly e.g. Y=350mm -
remove 75mm from the terminal assembly.
11.2.7
Telescopic Horizontal flue Kit
Greater Than 750mm in Length
If Y is between 425 and 725mm it is not necessary to cut the
terminal assembly or use a second extension duct as the length
can be set telescopically.
If bends are to be used refer also to Section 11.2.8.
(i)
By adding extension duct kits to the standard flue kit it is
not necessary to cut the extension ducts if
If Y is greater than 725mm then two extension duct assemblies
will be required, the first assembly being cut to length as plain
tubes.
L is between
1175 - 1475mm (1 extension)
1925 - 2225mm (2 extension)
If more than two extension ducts are needed in any section to
achieve the required length then the final section of the
assembly must not be less than 325mm without cutting the
terminal assembly.
NOTE: The flue duct of the final extension must be 30mm longer
than the air duct.
(ii)
However extension ducts need to be cut if
L is between
725 - 1175mm (1 extension)
1475 - 1925mm (2 extension)
2225 - 2500mm (3 extension) 19/24 CBi
2225 - 2975mm (3 extension) 14/19 and 19/24CBi
Each section must be connected to the previous section of the
flue bend by fixing the flue ducts together and then similarly
fixing the air ducts which engage the elbows.
(iii) To shorten the duct the first extension only should be cut.
To work out the length to be cut off:
Fix the flue assembly together using the self tapping screws
provided.
(No. of extensions x 750) + 425 — L = length to be cut.
NOTE: Extension duct measurements do not include the
socketed end. Unless specifically instructed the socketed
end must not be removed.
Apply the plastic tape onto the duct in contact with the wall (see
Fig. 23).
If an internal fitting kit is to be used refer now to Section 11.2.10
otherwise refer to Section 11.2.11.
(iv) Fix the flue assembly together using the self tapping
screws provided (see Fig. 20).
(v)
Apply the plastic tape onto the duct in contact with the
wall (see Fig. 20).
Tape
If an internal fitting kit is to be used refer now to Section 11.2.10
otherwise refer to Section 11.2.11.
Fig. 23. Flue bends.
Swaged ends
Plain ends
Y
Note: Connections to and from
bend should be plain ended and
the same length.
X
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig.26 . Terminal assembly for internal
Fig. 24 - Elbow to Flue Turret
Assembly.
fitting of the flue.
120mm
100mm
Tape
5
1
Flue Turret
4
3
2
Bend
1. Flue centring ring
2. Air duct
3. Flue duct
4. Rubber sealing gasket
5. Flue Terminal
11.2.9 Vertical Adaptor for Horizontal Flues
An adapter is available for an initial short section of vertical flue.
Refer to Fig. 25.
Rubber sealing
gasket
Measure and cut the flue as described in Section 11.2.7.
The first, vertical, section (equivalent to dimension X) is
measured from the top of the boiler casing. Cut the vertical
section of the extension duct to 167mm less than the measured
distance. Do not remove the socketed ends.
Flue terminal
Clamping ring
The minimum measured distance is 167mm.
Seal the air duct to the turret using silicone sealant.
11.2.11 Install the Boiler
Fig.25 Vertical Adaptor
IMPORTANT: Thoroughly flush the system before connecting the
boiler. Any system cleanser must be fully flushed from the system
before adding any inhibitor.
Flue Duct
(i)
Lift the boiler onto the wall mounting plate. See Fig. 27.
(ii)
Level the boiler using the two levelling feet at the base of the
back panel.
Air Duct
(iii) Fit the bottom fixing screw (or optional security screw).
(iv) Connect the gas supply using the nut and olive supplied in the
literature pack - details of the position are shown in Fig. 3.
(v)
Connect the flow and return pipes to the system. It is
important that the flow and return pipes are not fixed
near to the boiler using clips that put a strain on the
connections.
Clamping
Adaptor
ring
A drain point should be fitted close to the appliance if bottom
connections are made.
Always consider the possible need to disconnect and remove
the boiler.
Fixing screw hole
Flue Spigot
Fig. 27 . Fixing the appliance to the wall
mounting plate.
11.2.10 Fitting of the Flue Assembly without access
to the Terminal
4
An internal flue fixing kit (WHS part No. 7 716 191 019) is
available from Worcester, Bosch Group.
NOTE: A larger diameter opening (Ø150mm) in the wall is
required. Refer to Table 2.
3
Prepare the flue assembly as described in Section 11.2.6 - 11.2.8.
Fit the rubber sealing gasket centrally onto the terminal
assembly and tighten the clamp. Refer to Fig. 26.
Apply the plastic tape to the air duct in contact with the external
brickwork.
Appliance
2
From inside push the assembly through the wall so that the
gasket flange is against the outer face. Refer to Fig. 26.
It may be necessary to adjust the legs of the flue centring ring.
1. Levelling feet (2)
2. Fixing or security
screw
3. Boiler support
4. Wall plate
1
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig.29 . Flue Turret Fixing .
11.2.12 Installation of Flue onto Boiler
(i)
Fit the clamping ring around the flue spigot but leave loose.
From the inside push the assembly through the wall. Align
the flue turret and push fully onto the spigot on the appliance.
1
(ii)
Slide the clamping ring into position so that the hole in
the spigot lines up with the hole in the ring. Tighten the
ring in this position. Through the fixing hole screw the self
drilling screw into the flue (see Fig. 29).
2
3
(iii) Remove the fan from the fan/fluehood assembly by
removing the two fan flange fixing screws and also
releasing the fan clamping bracket.
4
1. Flue turret assembly
2. Clamp
3. Appliance
4. Fixing screw hole
(iv) Disconnect the two end lengths of the pressure sensing
hoses up to and the connection joints (approx 150mm of
hose). Both of these hoses should be discarded. Refer to
Fig. 16.
11.2.13 Completion of the Installation
Check that all the gas and water connections have been
tightened.
(v)
Slide the flue hood only back into the boiler facing the
opposite way to before. Ensure that the flue hood hits the
stops at the rear and the rear combustion chamber slots
in underneath (see Fig. 28).
Lower the base plate/control panel. Refer to Fig. 30.
(vi) With the fluehood on the boiler refit the fan:
The permanent mains and switched live supply to the boiler
must come from the system junction box. Refer to Fig.11. A 4
core cable is recommended.
(a)
(b)
Remove the fan lead from the top clip.
With the fan in close proximity to the fluehood re-
attach the fan electrical terminals to the fan. The
polarity of the connection to the fan motor is not
important.
Feed the 4 core cable and the pump cables through the bracket
and secure in the cable clamp. Refer to Fig. 30.
Fit all the supply and pump wires to the 5 way plug before fitting
the plug to the socket on the board. This will avoid stress to the
board when using a screwdriver. Refer to Fig.11. for the
connections.
(c)
Refit the the fan onto the fluehood. The rear flange
should slide into the clips at the rear of the flue hood.
(d)
The fan should then slide upwards into the flue
outlet to enable the fan clamp to be fitted and
tightened into position.
Check that all the cables cannot touch the inner casing.
Test for gas soundness as described in BS6891.
(vii) Re-assemble the front combustion chamber with the 'j'
bolts and replace inner case door.
If the appliance is not commissioned immediately, refit the
combustion cover, inner casing cover, base/controls assembly
and the casing. Re-connect the earth connection at the base of
the casing. Check that the gas and electricity services have been
turned off.
Fig. 28 . Fan/Flue hood Assembly with
Flue Turret Kit
REFER NOW TO SECTION 12 - COMMISSIONING THE
APPLIANCE
Fig. 30 . Mains electricity and controls
connections.
5
10
11
12 13
9
14
1
4 ( )
(Clear tube)
6
+
2
7
8
3 (+)
(Red tube)
7
6
4
5
3
1. Base plate
2. Control board
3. Control knob
4. Fuse 4A
5. External control connector block
6. Earth post
7. Cable clamp
10. Mains lead bracket
11. Spark electrode connection
12. Air pressure switch,
temperature sensor,
1
2
overheat thermostat
connection
13. Fan connection
14. Flame sense connection
1. Flue hood
2. Fan
5. Flue turret
6. Fan clamp
3. Sensing connection (+)
7. Fan clamp fixing screw
8. Internal earth connection
9. Gas valve connection
4. Sensing connection (
)
22
Download from Www.Somanuals.com. All Manuals Search And Download.
12. Commissioning The Appliance
Fig. 31. Gas Valve.
2
1
Cleansing and Inhibiting a Central Heating
Installation in compliance with Benchmark
It is accepted good practice in compliance with BS 7593, Pas 33 and
Benchmark, to cleanse both an existing central heating system when
fitting a replacement boiler, and when fitting a new central heating
system. Then treat with a 'Corrosion Protector.'
Worcester recommend only products from water treatment manu-
facturers participating in Benchmark. These include:
GAS
INLET
Fernox
Sentinel
Alpha-Fry Technologies
Tandem House
Marlowe Way
Beddington Farm Road
Croydon
Betz Dearborn Ltd
Foundry Lane
Widnes
4
6
Cheshire
WA8 8UD
1. Gas valve
2. Solenoids
3. Connector
3
CRO 4XS
Tel: 01799 521133
5
4. Inlet pressure test point
5. Burner pressure test point
6. Burner pressure adjustment screw
Tel: 0151 424 5351
Please call either of the above for a specific cleansing method
statement if so required. Below is a general guide for flushing,
which we would advise you to follow along with the chemical
manufacturers recommendations.
The
charge pressure of an expansion vessel is usually 0.5bar, which
is equivalent to a static head of 5m [17ft].
Fill up and commission the system in the normal way, i.e: flush
at least once without firing the boiler to remove loose debris.
The charge pressure must not be less than the static head at the
point of connection. The expansion vessel must be charged to
0.3bar less than the initial system design pressure.
Note: 1bar = 10.2m = 33.5ft of water.
Then add the cleansing agent, with regard to COSHH, this must
be in the system for a minimum of 1 hour with the system at
normal operating temperature. A longer period of time, up to 48
hours, would be more beneficial to the cleansing process, espe-
cially if heavy sludge deposits are suspected to be present (see
water analysis kit).
12.3 Set the System Pressure
Fill the system initially until the pressure gauge is at 2.5bar and check for leaks.
Release water through the drain cock until the required system
pressure is obtained, up to a maximum of 1.5bar.
Set the pointer on the pressure gauge to record the set system pressure.
If the pressure indicated on the gauge is greater than 2.65bar
when operating at the maximum central heating temperature,
the expansion vessel is too small and a larger vessel must be fitted.
The boiler with a 10 litre expansion vessel can accommodate a
sealed system volume of about 90 litres. Refer to BS7074 Part 1,
BS5449 and Table 9.
Drain the system thoroughly at least twice to remove the cleans-
ing agent and any debris/flux present. This is a crucial part of
the cleansing process and must be done correctly. A TDS meter
is recommended to ensure adequate flushing.
Once you are sure that the system has been cleansed thoroughly,
then add a mixed metal corrosion protector. This will protect
against the formation of scale, corrosion and microbiological
growths. A minimum of one treatment should be added per system.
12.4 Clock/Programmer
Any controls fitted to the system should be set up at this stage.
The label that is supplied by the manufacturer with the corrosion
protector treatment, shall be correctly filled in and attached to
the boiler. Also, the instructions in the Benchmark logbook will
be adhered to.
12.5 Check that the gas and electricity supplies are turned off.
Connect a pressure gauge to the burner pressure test point on
the gas valve. Refer to Fig. 31.
12.6 Light the Boiler
Please note that the corrosion protector level should be checked
on an annual basis. This is normally done at the time of the
mandatory boiler service. Water analysis test kits and postal
analysis services are available from water treatment suppliers for
this purpose.
Switch on the gas and electricity supply.
Set the temperature control knob to maximum and any clocks or
programmer to operate continuously.
The gas supply pipe will be purged by the boiler.
The control will work as follows:
Failure to comply with these recommendations, may invalidate
the boiler warranty. If any of the above is unclear, then please
contact The Worcester Technical Services for further advice.
(i)
Pre-purge (air) for approximately 20 seconds.
(ii) Spark and gas for approximately 5 seconds
(iii) Purge (air) for approximately 10 seconds
The boiler will attempt to light a maximum of 5 times before
going to lockout. To reset the product turn the control knob
fully anti-clockwise and back.
12.1 Remove the outer casing by first loosening the base screw.
Disconnect the earth and lift off the casing.
Check that the electricity and gas supplies to the appliance are
turned off and that all the water connections throughout the
system are tight.
NOTE: The burner pressure is factory set and may be reset to
match the system requirements. If, after checking that the
supply pressure is sufficient i.e. 19 mbar approx [NG] or 36 mbar
approx [PROPANE] at the gas valve inlet pressure test point, the
required pressure cannot be obtained then contact The
Worcester Service Department Tel: 08705 266241.
Reset the pressure as necessary by adjusting the screw on the
gas valve. Refer to Table 1 and Fig.31.
Open any system valves.
Open all the radiator valves. Remove any air vent caps.
If a sealed system has been installed then fill through a WRc
approved filling kit to an initial pressure of 2.5bar.
Check for water soundness throughout the system.
Vent each radiator in turn.
12.7 Domestic Hot Water
Remove the cap from the pump and turn the shaft about half a
turn. Replace the cap.
Check that the relief valve (sealed system) operates by turning
the knob anti-clockwise until it releases.
Check that the cylinder thermostat, if fitted, is set to between 55°C
and 60°C.
Check that all external controls are calling for heat and that the
flow pipe to the cylinder is hot after a short period.
12.2 Set the Expansion Vessel Pressure - Sealed System
23
Download from Www.Somanuals.com. All Manuals Search And Download.
12.8 Central Heating
pressure falls.
Check that the external controls are calling for heat to the heating
circuit.
13.5 Explain that regular servicing, of a maximum of 12 months
between services, will maintain the safe and efficient operation
and extend the life of the appliance. Worcester can offer a
comprehensive maintenance contract.
Check that all the radiators heat up evenly. If necessary carefully vent.
12.9 Balance the system to give the correct temperature
differential. Refer to Table 3. Refer to Section 7. for bypass
requirements.
13.6 Tell the user that any work on the appliance must only be
carried out by a competent person.
12.10 Set the room thermostat to minimum and check that the
burner goes out. Reset the room thermostat and the burner will re-light.
Turn off the gas service cock at the boiler. The burner will go out
but, after a short pause, the appliance will make 5 attempts to
restart sparking for 5 seconds and then 'lock-out'. After 60
seconds carefully open the gas service cock at the boiler, operate
the reset control and observe the burner re-light and follow the
normal sequence of operation. Refer to Fig. 32.
14. Inspection And Service
14.1 The extent of the service will be determined by the
operating condition of the appliance. It is the law that any
service work is carried out by a competent person.
14.2 Inspection
Turn off the gas service cock at the boiler and the electricity
supply to the appliance.
Check that the terminal and the terminal guard, if fitted, are clear
and undamaged.
Drain the system while the appliance is hot.
If the appliance is in a compartment or cupboard check that the
specified clearances are clear. Refer to Table 7 and Section 6 Air
Supply.
Refill, vent and re-pressurise the system (Sealed System) adding a
suitable proprietary inhibitor. Further information is available
from Worcester Technical Information Dept, Telephone 08705
266241.
Check all the joints and connections in the system and remake
any that show signs of leakage. Refill and re-pressurise (Sealed
System) as described in Section 12 Commissioning.
Operate the appliance and take note of any irregularities. Refer to
Section 18-Fault Finding.
12.11 Completion of Commissioning
Disconnect the pressure gauge from the gas valve and tighten
the test point screw.
Restart the appliance and check for gas soundness around the
test point screw.
Check the combustion performance
Lift off the cap from the sample point on the top of the boiler and
connect the meter. Refer to Fig 30/30a.
Fix the red arrow on the data plate to show the boiler setting. If
the setting has been altered the adjustment screw should be re-
sealed by a dab of paint to stop un-authorized adjustment.
Refit the casing, reconnect the earth and tighten the clip.
If the appliance is to be passed over to the user immediately
then set any controls to the users requirements.
With the appliance at maximum rate and stable expect readings
of about:
SHORT FLUE WITH
RESTRICTOR PLATE
FITTED
LONG FLUE WITHOUT
RESTRICTOR PLATE
FITTED
APPLIANCE
2
2
CO
CO
CO
CO
If the appliance is to be left inoperative in frosty conditions then
set a programmer, if fitted, to continuous and the appliance to
operate at a low temperature under the control of a frost
thermostat, if fitted, to protect remote parts of the system.
The boiler has its own integral frost protection which will also
protect a compact system.
If there is any possibility of the appliance being left totally
unused in freezing conditions then switch off the gas and
electricity and drain the appliance and the system.
0.003 - 0.007
0.003 - 0.007
0.002 - 0.005
0.002 - 0.005
0.008 - 0.012
0.005 - 0.010
7.2 - 8.1
8.1 - 8.7
6.6 - 7.5
7.8 - 8.5
7.1 - 7.7
8.0 - 8.9
0.002 - 0.005
0.002 - 0.005
0.002 - 0.005
0.002 - 0.005
0.008 - 0.012
0.008 - 0.015
6.0 - 6.8
6.9 - 7.7
5.6 - 6.5
6.3 - 7.0
7.0 - 7.8
7.8 - 8.5
9/14CBi NG
LPG
14/19CBi NG
LPG
19/24CBi NG
LPG
Refit the sample point cap after the test.
Always test for gas soundness after the service has been
completed.
Complete the Benchmark Log-book.
Disconnect the electrical supply at the mains and turn off the
gas supply at the gas service cock on the appliance before
starting any service procedures.
13. Instructions To The User
Fig. 32. User controls.
14.3 Component Access
Ensure that the gas and electricity supplies are isolated before
accessing the following parts.
Remove some or all of the following parts to gain access to the
components.
Outer Case. Loosen the screw and clip at the base, disconnect
the earth tag, lift the case up and pull forwards.
Base/Control Assembly. Remove the single screw and lower.
Refer to Fig. 33a/b.
Inner Case Door. Remove the four corner screws and lift the
door off.
1
2
3
4
Combustion Chamber Front Cover. Loosen the two wing-nuts
and slide the 'J' bolts out of the slots. Pull the front cover
forwards and upwards to remove from the boiler.
NOTE: On the 9/14CBi the RHS bolt and clamping bracket must
be removed.
1. Boiler demand
4. Temperature control knob/ ON-STANDBY/ Lock-out reset
2. Burner ON
3. Lock-out
13.1 Hand over the User Booklet and the Benchmark
Log-book and explain how to operate the appliance safely and
efficiently.
Fan - Rear Only Flue. Remove the combustion chamber front
cover. Carefully pull off the electrical connections and the
pressure tubes from the air flow detector. Slide out the fan and
flue hood assembly. Ensure that the combustion chamber rear
fits under the lip on the fluehood. To remove the fan, remove the
two fixing screws and release the clamping bracket.
13.3 Tell the user what to do if the appliance is not to be used in
very cold conditions.
13.4 Tell the user what to do if the system (Sealed System)
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Fan -
Horizontal Flue. Remove the combustion
14.4 Component Cleaning
chamber cover. Carefully pull off the electrical connections and
the tubes from the air flow detector. Loosen the two clamps to
remove the fan . Refer to Fig 34.
Do not use a brush with metal bristles to clean components.
Clean the fan taking care not to block air flow detector.
Clean the burner to ensure that the blades are clear. Do not use a
metal probe to clean the injector.
Flue Hood -
Horizontal Flue. Remove the fan, see
Clean the electrodes and check the alignment. Replace if there is
any sign of deterioration.
above. Remove the combustion chamber cover and withdraw
the hood. When refitting ensure that the combustion front fits
under the lip of the flue hood.
Clean the heat exchanger from top and bottom after covering the
burner injector. To clean the heat exchanger flueways remove the
stainless steel baffles from the appliance - the rear combustion
chamber cover can be tilted for better access. The front and rear
flueways can be cleaned with a brush being careful to protect the
rear combution chamber insulation. The inner flueway can be
cleaned with a scraper.
Burner Blade Assembly. Remove the combustion chamber
cover. Undo the screw at the right hand end of the burner.
Carefully pull-off the connections to the spark electrode. Slide the
burner blade assembly off the injector and remove. Carefully pull
off the flame sense electrode lead. Refer to Fig 33/33a.
Check the combustion chamber insulation and replace if there is
any sign of damage or deterioration. Refer to Section 15.4.11.
Carefully refit any components removed and check that all
screws are tight and the connections properly re-made with the
appropriate gaskets/O-rings/seals.
Re-commission, as necessary, for correct operation to the users
requirements. Refer to Section 12 Commissioning.
Control Board Cover. To gain access to the control board remove
cover from the front clip, with a screwdriver (if necessary) and
unclip from the rear of the controls tray.
Fig. 33a. Inner Casing and control
18
9/14CBi
17
19
16
22
20
1
15
21
27
26
14
13
2
3
25
4
12
11
5
6
24
23
10
7
8
9
1. Inner case
8. Base/controls fixing screw
9. Cabinet fixing screw
10. Gas valve
15. Air pressure switch
16. Flow pipe
22. Inner case cover fixing points (4)
23. Outer case earth tag
24. Side cover plate
2. J bolts and wing nuts (2)
3. Combustion chamber cover
4. Burner
17. Return pipe
18. Combustion test point
19. Sensing tubes
20. Fan
11. Spark electrode
25. Wire clip
5. Burner fixing screw
6. Control knob
7. Indicator lights
12. Burner injector
13. Temperature sensor
14. Overheat thermostat
26. 9/14CBi clamping bracket
27. Pressure tube junction
21. Flue hood
25
Download from Www.Somanuals.com. All Manuals Search And Download.
15.3 Draining the Appliance
Isolate the appliance.
15. Replacement Of Parts
Important: Turn off the gas and electricity supplies and drain,
where necessary, before replacing any components.
Remove the casing. Refer to Section 14.3.
Fit a tube to the drain connection from the system (top connection
only) and open the tap. Refer to Fig 34. Close the tap when the flow
has stopped.
IMPORTANT: A small quantity of water will remain in some
components. Protect any electrical components when removing
items that might retain water.
15.1 Always check for gas soundness where relevant and carry
out functional checks as described in Section 12 Commissioning.
Any O-ring, gasket or seal that appears damaged must be
replaced.
15.4 Component Replacement
15.2 Component Access
Refer to Section 14.3 Inspection and Servicing for access to
components.
Replace any components removed from the appliance in the
reverse order using new gaskets/O-rings/sealant/heat transfer
paste where necessary. Always check that any electrical
connections are correctly made and that all screws are tight.
Fig. 33b. Inner Casing and control
14/19 and 19/24CBi
17
18
20
21
19
16
22
23
1
15
2
14
13
3
27
26
4
12
11
5
6
25
24
10
8
9
7
1. Inner case
8. Base/controls fixing screw
9. Cabinet fixing screw
10. Gas valve
15. Air pressure switch
16. Flow pipe
22. Inner case cover fixing points (4)
23. Flue hood
2. J bolts and wing nuts (2)
3. Combustion chamber cover
4. Burner
17. Return pipe
24. Outer case earth tag
25. Side cover plate
26. Wire clip
11. Spark electrode
18. Combustion test point
19. Sensing tubes
20. Fan
5. Burner fixing screw
6. Control knob
7. Indicator lights
12. Burner injector
13. Temperature sensor
14. Overheat thermostat
27. Front baffle
21. Fan clamp (2 screws)
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig. 34 . Inner Casing - Gas and Electric
Controls. 9/14CBi shown.
17
18
16
19
20
15
21
22
23
1
11
14
2
3
1. Inner casing
13
12
2. J bolts and wing nuts (2)
3. Combustion chamber cover
4. Burner assembly
5. Inner case cover fixing
points (4)
6. Base/control fixing point
7. Gas valve
8. Burner manifold fixing
screws (4 + 4)
11
9. Burner manifold
10. Drain point (top flow return)
11. Flow and return pipe fixing clip
12. Access panel
13. Temperature sensor
14. Overheat thermostat
15. Casing support
14
10
4
8
5
16. Return pipe
17. Flow pipe
18. Air pressure switch
19. Combustion test point
20. Air pressure switch fixing clip (4)
21. Flue hood
7
9
8
22. Fan
6
23. Sensing tubes
24. Outer case earth tag
25. Side cover plate
7
25
24
Fig. 35 . Base/Control Board Assembly
2
3
1. Base/control assembly
2. Base/control assembly fixing
point
10
3. Gas valve
4. Inner connections earth tag
5. External controls earth post
points (4)
6. Cable clamp
7. External controls connection
8. Control knob
9. Fuse
10. Outer case earth tag
NOTE: Control board cover not shown.
6
1
4
7
9
8
5
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Alter the red arrow if a new setting is made.
The adjustment screw must be sealed by a dab of paint to stop
unauthorized adjustment.
15.4.1 Gas Valve
NOTE: If the left hand clearance is >50mm then the gas valve
can be replaced with the burner and combustion chamber cover
in place by unscrewing the four extended screws at the manifold
on the outside of the inner casing. The manifold gasket should be
replaced if it is damaged or has deteriorated.
Switch off the appliance, disconnect the pressure gauge and
tighten the test point screw. Refer to Fig. 31.
Check for gas soundness.
Check that the gas supply is isolated.
15.4.2 Spark Electrode
Remove the inner casing cover, the combustion chamber cover
and the burner blade assembly. Refer to Section 14.3.
Unscrew and lower the base plate/control assembly.
Unplug the electrical connection at the gas valve.
Unscrew and remove the side plate adjacent to the manifold.
Undo the four screws securing the gas cock to the valve. Take
care not to damage the control panel.
Remove the inner casing cover and the combustion chamber
cover.
Carefully pull off the leads at the electrodes. Remove the burner
blade assembly. Refer to Section 14.3.
Unscrew and remove the electrode assembly. Refer to Fig. 36 and 36a.
15.4.3 Flame Sense Electrode
Undo the four pozi-head screws to remove the gas valve and
burner manifold assembly.
Remove the inner casing cover and the combustion chamber
cover.
Undo the four pozi-head screws inside the casing to separate the gas
valve from the manifold.
Pull off the connections to the spark electrode. Carefully remove
the burner blade assembly. Refer to Section 14.3.
Carefully pull off the lead from the electrode.
Unscrew and remove the electrode assembly. Refer to Fig. 36 and 36a.
Ensure that the new electrode is at the correct height and
position on the burner blade.
Use new O-rings when replacing the valve.
Set the Gas Valve:
Connect a pressure gauge to the burner pressure test point on
the valve. Refer to Fig. 31.
Switch on the gas and electricity supplies. Check for gas
soundness at the gas valve inlet.
15.4.4 Burner Blade Assembly
Refer to Section 12 Commissioning for the method of checking
the pressures.
Remove the inner casing cover and the combustion chamber cover.
Remove the burner blade assembly. Refer to Section 14.3.
Check for gas soundness at the gas valve outlet.
Adjust the gas valve to obtain the required pressure. Refer to the
data plate on the cabinet where required pressure will be indicated.
Spark Electrode Gaps
3
Fig. 36. Burner Blade Assembly 14/19 and
19/24CBi
4.1 0.2
2.5
Flame Sense Electrode Gap
3.1 0.2
1. Burner blade assembly
2. Burner fixing screw
3. Flame sense electrode
4. Spark electrode
5
4
5. Burner baffle (not removable from
1
2
the burner
Spark Electrode Position
Fig. 36a . Burner Blade Assembly 9/14CBi
Both Burners
3
Flame Sense Electrode Position
Both Burners
4
5
1
2
28
Download from Www.Somanuals.com. All Manuals Search And Download.
15.4.5 Control Board
15.4.6 Fan
Lower the base plate/control assembly and carefully disconnect
the plug-in connector and all the electrical connections. Refer to
Fig. 35.
Remove the inner casing and combustion chamber cover .
Remove the fan as described in Section 14.3 Inspection and
Servicing. The flue hood gasket should be replaced if it is
damaged or has deteriorated.
Release the five clips and lift out the control board. Refer to Fig. 35.
Pull out and replace, if necessary, a failed fuse.
Ensure that all the connections are correctly made to the new
fan. Refer to Fig. 37 and 37a.
Do not use any sealant on the fan/flue duct connection.
The polarity of wires onto the fan is not important.
Fig. 37 . Fan/Flue hood Assembly with
Horizontal Flue
5
4 ( )
(clear tube)
6
+
7
1. Flue hood
3 (+)
(red tube)
2. Fan
3. Sensing connection (+)
4. Sensing connection (
5. Flue turret
6. Fan clamp
7. Fan clamp fixing screw
)
1
2
Fig. 37a . Fan/Flue hood Assembly with Rear Only Flue
NOTE: The polarity of wires is
not important
5
6
1. Flue hood
2. Fan
3. Sensing connection (+)
4. Sensing connection (—)
5. Top outlet sealing plate
6. Fan lead clip
7. Fan fixing screws (2)
8. Pressure tube junction
9. — ve pressure tube
9
—ve
10. + ve pressure tube
1
10
+ve
4 ( — )
(clear tube)
+
3 (+)
(red tube)
8
7
2
29
Download from Www.Somanuals.com. All Manuals Search And Download.
15.4.7 Air Flow Sensor
15.4.10 Air Pressure Switch
Remove the fan as described in 14.3. Unscrew and withdraw,
through the fan outlet, the air flow sensor. Refer to Fig .38 and
38a.
Noting the position of each pressure tube carefully disconnect
the tubes and electrical connections from the switch. Unclip and
remove the switch if there is more than 50mm clearance. Refer
to Fig.40.
The detector is 'handed' - do not force it into place.
If there is minimum clearance then remove the inner casing
cover and release the two screws. Remove the air pressure
switch and mounting bracket complete.
Ensure that the connections are correctly made on the
replacement switch. Red tube to the connection marked (+) and
the clear tube to the connection marked ( —).
Fig. 38 - 9/14CBi
Fig. 38a - 14/19 and
19/24CBi
+
+
Fig. 40. Air Pressure Switch
1
2
7
15.4.8 Temperature Sensor
Remove the access panel to give improved access with minimum
side clearance.
Carefully pull-off the connections.
Remove grommet.
Pull off the clip and remove the sensor. Refer to Fig .39.
When replacing component ensure heat sink compound is
added around contact area.
6
5
15.4.9 Overheat Thermostat
Remove the access panel to give improved access with minimum
side clearance.
Carefully pull-off the connections.
Remove grommet.
Unscrew and remove the sensor (see above).
When replacing component ensure heat sink compound is
added around contact area.
3
4
Fig. 39. Sensor and Overheat Thermostat
6
1. Air pressure switch
2. Fixing clips (4) - mounting bracket
3. Sensing tube connection - clear to ' ' on fan
4. Sensing tube connection - red to '+' on fan
5. Electrical connection COM - brown
6. Electrical connection NO - grey
7. Electrical connection NC - white
3
5
1
4
2
1. Sensor clip with grommet
2. Temperature sensor
3. Overheat thermostat
4. Thermostat pocket
5. Flow manifold
6. Flow pipe
7. Grommet
7
30
Download from Www.Somanuals.com. All Manuals Search And Download.
15.4.11 Combustion Chamber Insulation
The insulation pads are manufactured from a material in
accordance with COSHH.
Fig. 41. Heat Exchanger Baffles in Position
on the Heat Exchanger
Remove the casing, inner casing cover and combustion chamber
cover.
Front Insulation: Unscrew the clamp at the top of the
combustion chamber cover to replace insulation.
3
Side Insulation: Release the clip at the bottom and slide
out the insulation.
2
Rear Insulation: Remove the burner blade assembly and
cover the burner injector.
Remove the fan and flue hood assembly.
Remove the side insulation pads.
1
Unscrew the combustion chamber rear panel and lower.
Cut the rear insulation board to remove it from the boiler.
Cut the replacement board approximately 90mm from the
top so that the joint will be behind the heat exchanger.
Slide in the top section followed by the bottom section.
Refer to Fig.37.
On replacement ensure that the fixing screw returns
through the hole in the rear bracket.
15.4.12 Heat Exchanger
Shut off the gas and electricity supplies.
Drain the appliance.
Protect the electrical components.
NOTE: Some water will remain in the heat exchanger.
Remove the casing, inner casing cover, combustion chamber
cover, heat exchanger baffles, fan and flue hood assembly,
burner blade assembly and the access plate at the left hand side
of the inner casing.
1
Pull off the leads from the sensor and overheat thermostats. Pull
off the clip to remove the sensor and unscrew the overheat
thermostat.
1. Heat exchanger baffle
2. Wire fixing clip
3. Heat exchanger
4. Flow and return manifolds
Pull out the clips securing the flow and return pipes and remove
them from the manifolds. It will be necessary to disconnect the
pipes from the system adjacent to the boiler.
4
Unscrew the slotted hex head screw at the base of the
combustion chamber rear panel.
Slide the panel upwards and unscrew the two screws exposed at
the right and left hand sides at the rear.
Unscrew the four hex head screws, two at each side, securing the
steel side plates to the inner casing.
Lower the combustion chamber rear panel by pulling the lower
fixing point in front of the securing bracket.
Unscrew the two M6 nuts whilst supporting the heat exchanger
(the approximate weight is: 9/14CBi - 18kg, 14/19 and
19/24CBi - 24kg).
Lift out the heat exchanger assembly complete with side plates
and manifolds. Take care as the combustion chamber rear panel
is now unattached.
Transfer the side plates to the new heat exchanger
Fit the new heat exchanger in the reverse order.
Re-commission the appliance. Refer to Section 12.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
(VI) Transfer the spark and flame electrode assemblies to the
new burner blade assembly. Refer to Sections 15.4.2 - 4 for
details of positions.
16. Conversion Instructions
These instructions should only be read if converting appliance
from Natural Gas to LPG or vice versa.
(VII) Fit the new burner blade assembly into the appliance not
forgetting to re-connect the electrode leads.
Only components supplied by Worcester, Bosch Group should be
used.
(VIII) Refit the combustion chamber front and inner case cover.
(IX) Switch on the gas supply and open the gas cock at the
appliance. Check for leaks at the gas valve inlet.
Only competent persons should attempt the conversion.
Conversion from Natural Gas to LPG should not be carried out
on appliances installed in a room or internal space below
ground level.
(X)
Refit the base control assembly.
(XI) Recommission the appliance.
Refer to Section 12. Commissioning for details.
Adjust the burner setting pressure as required. Refer to
Table 1 and Fig. 31.
Turn off the gas and electricity supplies to the boiler.
NOTE: Turning the control knob to off does not isolate the boiler.
(XII) Fix the Red Arrow on the data plate to show the boiler
setting. If the setting has been altered the adjustment
screw should be resealed by a dab of paint to stop un-
authorized adjustment.
16.1 Conversion
(I)
Remove the outer casing by loosening the fixing screw at
the base and lifting off. Refer to Fig. 12a/b.
(II)
Remove the inner casing door and combustion chamber
front. Refer to Section 14.3.
(XIII) If converting to an LPG boiler add LPG sticker to the casing
door. If converting from LPG to NG then remove the LPG
sticker from the casing door.
(III) Lower the base/control assembly. Refer to Section 14.3.
(IV) Remove the burner blade assemby. Refer to Section 14.3.
(XIV) Refit the cabinet casing.
(V)
Unscrew and replace the burner injector and washer with
the new one from the kit. Refer to Tables 9 and10.
(XV) Complete the Benchmark checklist.
Table 9.
Conversion from LPG — NG
9/14CBi
14/19CBi
19/24CBi
7 716 192 271
8 716 157 115 (4.3mm)
8 716 101 994
LPG — NG Kit No.
Burner Injector
Injector Washer
7 716 192 269
8 716 157 116 (3.4mm)
8 716 101 994
7 716 192 279
8 716 103 168 (3.8mm)
8 716 101 994
Bunner Blade Assembly
8 716 142 654
8 716 142 653
8 716 142 653
Table 10. Conversion from NG — LPG
9/14CBi
14/19CBi
7 716 192 277
8 716 103 169 (2.5mm)
8 716 101 994
8 716 102 412
ZK LAB 417
19/24CBi
7 716 192 272
8 716 102 411 (2.7mm)
8 716 101 994
8 716 102 412
ZK LAB 417
NG — LPG Kit No.
Burner Injector
Injector Washer
Bunner Blade Assembly
LPG Label
7 716 192 270
8 716 102 407 (2.1mm)
8 716 101 994
8 716 102 408
ZK LAB 147
32
Download from Www.Somanuals.com. All Manuals Search And Download.
17. Short Parts List
Key
No.
G.C. No.
Part
Manufacturer’s Reference
Qty
WHS
Part No.
1
2
3
E60-473
E60-474
E60-475
Burner Assembly NG 9/14CBi
Burner Assembly LPG 9/14CBi
Burner Assembly NG 14/19, 19/24CBi
Burner Assembly LPG 14/19, 19/24CBi
Injector Burner 3.4mm NG 9/14CBi
Injector Burner 2.1mm LPG 9/14CBi
Injector Burner 3.8mm NG 14/19CBi
Injector Burner 2.5mm LPG 14/19CBi
Injector Burner 4.3mm NG 19/24CBi
Injector Burner 2.7mm LPG 19/24CBi
Gas Valve NG
Air Pressure Switch 9/14, 14/19CBi
Air Pressure Switch 19/24CBi
Spark Electrode Assembly
Sensor Electrode Assembly
Spark Electrode Lead
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
10
1
1
8716121773 0
87161032100
8716121767 0
87161032110
8716157 116 0
8716102407 0
8716103168 0
8716103169 0
8716157 115 0
87161024110
8716156 769 0
8716146 165 0
8716146 163 0
8716142 140 0
8716142 139 0
8716121805 0
8716142 137 0
8716121699 0
8716121700 0
7716101854 0
7716101796 0
8716146 332 0
8716142 399 0
8 716 142 302 0
8 716 104 581 0
8 716 104 582 0
8716156 008 0
8716101797 0
8716101798 0
4
E60-476
5
6
7
8
E60-477
E60-478
E60 479
E60-480
E60-481
E60-482
E60-483
E60-484
E60-485
E60-486
E60-487
E60-492
E60-493
375 696
E60-498
E60-499
E60-500
E60-503
E60-504
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
Sensor Electrode Lead
Heat Exchanger Assembly 9/14CBi
Heat Exchanger Assembly 14/19, 19/24CBi
Insulation Kit 9/14CBi
Insulation Kit 14/19, 19/24CBi
Control Board PCB
Overheat Thermostat
Primary/Domestic Thermister Sensor Kit
FanAssembly 9/14CBi
FanAssembly 14/19, 19/24CBi
Fuse 4A Fast blow 20 X 5mm
O-Ring Kit HT/Exchanger
Gas Section Sealing Kit
33
Download from Www.Somanuals.com. All Manuals Search And Download.
18. Operational Flow Diagram
34
Download from Www.Somanuals.com. All Manuals Search And Download.
19. Fault Finding
NOTE: This fault finding information is for guidance only. Worcester, Bosch Group cannot be held responsible for costs incurred by
persons not deemed to be competent.
The electronic control for this boiler incorporates three lights: Boiler demand, flame on and lockout.
These form the basis for this fault finding guide.
To use this guide, select box below which represents the light situation during your fault, then refer to the appropriate section.
This guide assumes a component failure has occured following a period of normal running. It is not intended to solve installation errors.
PRELIMINARY CHECKS
Preliminary electrical system checks are the first electrical checks to be carried out during a fault-finding procedure. On completion of the
Service/Fault-finding task which has required the breaking and remaking of electrical connections, check (a) EARTH CONTINUITY,
(b) SHORT CIRCUIT CHECK, (c) POLARITY and (d) RESISTANCE TO EARTH.
WARNING: In addition to the controls, the overheat thermostat and fan are connected directly to the permanent live supply. Under
all circumstances remove the permanent live supply before touching these parts.
LIGHT SITUATION DURING FAULT
WITH A SYSTEM BOILER DEMAND AND USER CONTROL SET TO MAXIMUM:
NO LIGHTS AT ALL
FAULT POINT A
DEMAND LIGHT ONLY
FAULT POINT B
FAULT POINT C
BURNER LIGHT ONLY
LOCKOUT LIGHT ON
CONSTANTLY
ON OR OFF
ON OR OFF
OFF
OFF
FAULT POINT D
FAULT POINT E
LOCKOUT LIGHT
FLASHING
OTHER FAULTS NOT COVERED BY ABOVE
FAULT POINT F
35
Download from Www.Somanuals.com. All Manuals Search And Download.
No boiler demand
from the heating
system. Investigate
system.
Gain access to the
control board.
No
Is there 230V at connector
X1 between pins SL & N?
Yes
Replace control board.
NOTE: It is normal to see only a
demand light if the boiler is hot
and the burner has temporarily
shut off.
Ensure boiler is cool and user
control set to maximum.
Replace sensor
or check
cables to it.
No permanent live
supply to control
board. Investigate
electrical supply from
external system.
Gain access to the
control board.
No
Is there 230V at connector
X1 between pins
'PERM LIVE' & 'N'?
No
Remove connector
X5 and test
resistance between
the red and violet
cables. Is the
resistance between
1 kohm and
Yes
Is there 230V
across the fan
terminals?
WARNING:
if NO, both fan
terminals will
be LIVE.
Check fuse F1
on the control
board.
No
No
Does the No
pump
run?
No
Create a new demand.
Does the fan run?
Has it blown?
Yes
30 kohm?
Yes
Yes
Yes
Replace fuse and
investigate cause.
Suggestions:
Air pressure switch
is stuck on.
Yes
Replace air pressure
switch.
connections to (or
faults within) pump,
fan, gas valve,
Replace fan.
system wiring,
possible board fault.
Fan cycles on & off.
Is there any sign of
blockage in the flue or
air pressure tubes?
No
No
Does the fan run
continuously?
Replace control board.
Yes
Yes
Clear blockage.
Air pressure switch not
changing over. Check flue and
air pressure sense tubes. Are
they clear and not damaged?
No
Repair fault.
Yes
Replace air pressure switch.
If this does not solve the
problem check the venturi in
the fan housing.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Demand light has
failed. Replace control
board if it is
Is the boiler in a very cold
environment
No
i.e is the primary water
temperature below 5°C?
considered a problem.
Yes
Boiler is running in
'Autofroststat' mode.
Is the system fully
water pressurised
and is all air vented?
No
Rectify fault/leak.
Yes
The system should have a
bypass fitted as described in
Section 7. SYSTEM and Figs.
5, 6 & 7. Is bypass fitted and
correctly adjusted?
No
No
Add or adjust system
bypass.
Yes
Reset the lockout and create
a boiler demand.
Replace pump or
check cables to it.
With the boiler cool does
the pump run?
Yes
Switch off mains supply.
Remove boiler cover
and inspect the
No
Refit sensor to
manifold or add heat
conductive paste.
temperature sensor.
Is it correctly fitted to the
manifold with heat
conductive paste on its
surface?
Yes
Use a suitable
implement to push
switch to the 'normal'
left position. The
'heatstore' right position
is for commercial
Gain access to control board
and inspect the slide switch
at the front of the board.
In normal domestic
No
No
installation this switch
should be in the left
'normal' position.
applications only.
Yes
Remove connector at X5.
With boiler cool is there a
short circuit between the
orange & black cables?
Replace overheat
thermostat or check
wiring to it.
Yes
Replace control board.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
No
No
Is the gas supply
connected and at the
correct pressure?
Rectify gas supply
problem.
Yes
Remove boiler casing.
Reset and restart
the boiler.
TURN OFF GAS SUPPLY.
Remove inner casing
cover.
Are the electrodes
and gap and
No
No
No
Repair or replace
spark electrode
or HT leads.
Can a flame be seen
through the spyglass?
Note: there is a 20
second delay from fan
on to spark.
connections
Reset and restart boiler.
Does a spark occur
across the electrodes?
in good order?
Yes
Yes
Replace control board.
During spark period
is there 216V D.C.
across the pins at
connector X2?
Yes
Yes
Replace gas valve or
check cable to it.
TURN OFF GAS SUPPLY.
Remove the combustion
chamber cover. Is the
sense (right) electrode
and lead in good
No
Repair or replace
flame sense
or cable to it.
condition and is gap
correct?
See Section 15.4.3
Yes
Replace control board.
Note: It is not possible
to reliably check the
cross light performance
of the burner.
In the unlikely event of
such a fault, investigate
condition of flue,
NOTE: Do not attempt to light the boiler
with the combustion chamber cover
removed.
burner and injector.
Also check polarity of
mains voltage supply.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
Delivered primary water
temperature always too hot.
(Over 85°C)
Check thermister
sensor/heat conductive
paste.
Move control knob to lower
setting.
Replace control board.
Such a fault is likely to be caused
by one or more of the following:
Low gas pressure
Delivered primary water
temperature appears too
low with control knob set to
maximum.
Partially blocked flue
Partially blocked heat exchanger
Blocked/dirty burner
Gas valve sticking
(Less than 75°C)
Control board fault
Faulty themister
39
Download from Www.Somanuals.com. All Manuals Search And Download.
40
Download from Www.Somanuals.com. All Manuals Search And Download.
BENCHMARK No.
GAS BOILER COMMISSIONING CHECKLIST
NOTIFICATION No.
C O L L E C T I V E M A R K
BOILER SERIAL No.
CONTROLS To comply with the Building Regulations, each section must have a tick in one or other of the boxes
TIME & TEMPERATURE CONTROLTO HEATING ROOM T/STAT& PROGRAMMER/TIMER
TIME & TEMPERATURE CONTROLTO HOTWATER CYLINDER T/STAT& PROGRAMMER/TIMER
PROGRAMMABLE ROOMSTAT
COMBI BOILER
HEATING ZONE VALVES
FITTED
FITTED
FITTED
FITTED
NOT REQUIRED
HOTWATER ZONE VALVES
NOT REQUIRED
THERMOSTATIC RADIATOR VALVES
AUTOMATIC BYPASS TO SYSTEM
NOT REQUIRED
FOR ALL BOILERS CONFIRM THE FOLLOWING
THE SYSTEM HAS BEEN FLUSHED IN ACCORDANCE WITH THE BOILER MANUFACTURER S INSTRUCTIONS?
THE SYSTEM CLEANER USED
THE INHIBITOR USED
FOR THE CENTRALHEATING MODE, MEASURE & RECORD
3
m3/hr
N/A
GAS RATE
tf/hr
BURNER OPERATING PRESSURE (IF APPLICABLE)
CENTRALHEATING FLOW TEMPERATURE
CENTRALHEATING RETURN TEMPERATURE
mbar
¡C
¡C
FOR COMBINATION BOILERS ONLY
HAS AWATERSCALEREDUCERBEENFITTED?
YES
NO
WHATTYPE OF SCALE REDUCER HAS BEEN FITTED?
FOR THE DOMESTIC HOT WATER MODE, MEASURE & RECORD
3
m3/hr
N/A
GAS RATE
tf/hr
MAXIMUM BURNER OPERATING PRESSURE (IF APPLICABLE)
COLD WATER INLET TEMPERATURE
HOTWATER OUTLETTEMPERATURE
WATER FLOW RATE
mbar
¡C
¡C
lts/min
FOR CONDENSING BOILERS ONLYCONFIRM THE FOLLOWING
THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH
THE MANUFACTURER S INSTRUCTIONS?
YES
FOR ALL INSTALLATIONS CONFIRM THE FOLLOWING
THE HEATING AND HOTWATER SYSTEM COMPLIES
WITH CURRENTBUILDING REGULATIONS
THE APPLIANCE AND ASSOCIATED EQUIPMENTHAS BEEN INSTALLED AND COMMISSIONED
INACCORDANCE WITH THE MANUFACTURER S INSTRUCTIONS
IF REQUIRED BYTHE MANUFACTURER, HAVEYOU RECORDED ACO/CO2RATIO READING? N/A
YES
CO/CO2RATIO
THE OPERATION OF THE APPLIANCE AND SYSTEM
CONTROLS HAVE BEEN DEMONSTRATED TO THE CUSTOMER
THE MANUFACTURER S LITERATURE HAS BEEN LEFTWITH THE CUSTOMER
COMMISSIONING ENG S NAME PRINT
CORGI ID No.
DATE
SIGN
Download from Www.Somanuals.com. All Manuals Search And Download.
SERVICE INTERVAL RECORD
It is recommended that your heating system is serviced regularly
and that you complete the appropriate Service Interval Record Below.
Service Provider. Before completing the appropriate Service Interval Record below, please ensure you have carried out the service
as described in the boiler manufacturer sinstructions.Always use the manufacturer sspecifiedsparepartwhenreplacingallcontrols
SERVICE 1 DATE
ENGINEER NAME
COMPANYNAME
TEL No.
SERVICE 2 DATE
ENGINEER NAME
COMPANYNAME
TEL No.
CORGI ID CARD SERIALNo.
COMMENTS
CORGI ID CARD SERIALNo.
COMMENTS
SIGNATURE
SIGNATURE
SERVICE 3 DATE
ENGINEER NAME
COMPANYNAME
TEL No.
SERVICE 4 DATE
ENGINEER NAME
COMPANYNAME
TEL No.
CORGI ID CARD SERIALNo.
COMMENTS
CORGI ID CARD SERIALNo.
COMMENTS
SIGNATURE
SIGNATURE
SERVICE 5 DATE
ENGINEER NAME
COMPANYNAME
TEL No.
SERVICE 6 DATE
ENGINEER NAME
COMPANYNAME
TEL No.
CORGI ID CARD SERIALNo.
COMMENTS
CORGI ID CARD SERIALNo.
COMMENTS
SIGNATURE
SIGNATURE
SERVICE 7 DATE
ENGINEER NAME
COMPANYNAME
TEL No.
SERVICE 8 DATE
ENGINEER NAME
COMPANYNAME
TEL No.
CORGI ID CARD SERIALNo.
COMMENTS
CORGI ID CARD SERIALNo.
COMMENTS
SIGNATURE
SIGNATURE
SERVICE 9 DATE
ENGINEER NAME
COMPANYNAME
TEL No.
SERVICE 10 DATE
ENGINEER NAME
COMPANYNAME
TEL No.
CORGI ID CARD SERIALNo.
COMMENTS
CORGI ID CARD SERIALNo.
COMMENTS
SIGNATURE
SIGNATURE
Download from Www.Somanuals.com. All Manuals Search And Download.
43
Download from Www.Somanuals.com. All Manuals Search And Download.
This manual is to be used in conjunction
with the variant part number of the bar
code below:
Bosch Group
Worcester, Bosch Group, Cotswold Way, Warndon, Worcester WR4 9SW.
Telephone: 01905 754624. Fax: 01905 753130.
Technical Helpline 08705 266241.
Worcester, Bosch Group is a trading name of BBT Thermotechnology UK Limited.
This booklet is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests
of continued improvement.
All goods sold are subject to our official Conditions of Sale, a copy of which may be obtained on application.
PUBLICATION 8 716 115 015a (02/08)
Download from Www.Somanuals.com. All Manuals Search And Download.
|