WARNING:
Improper installation, setup, modification, operation or
maintenance of the heating system can cause personal
injury and property damage.
Follow each appliances' instructions precisely.
For assistance or further information, contact a trained
and certified installer, service provider, or the gas
supply company.
In Massachusetts, the boiler must be installed by a
licensed plumber or gas fitter.
Application drawings in this manual are conceptual only
and do not purport to address all design, installation,
code, or safety considerations.
The diagrams in this manual are for reference use by
code officials, designers and licensed installers. It is
expected that installers have adequate knowledge of
national and local codes, as well as accepted industry
practices, and are trained on equipment, procedures,
and applications involved. Drawings are not to scale.
Refer to the boiler, control and module installer manuals
for additional detailed information!
Gas Condensing Boiler
Bosch
100, 151 Combi Boiler
57, 100, 131, 151 Heating Boiler
Applications Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 3
Table of Contents
1 Information about the appliance
1.1 Boiler types and sizes
4
4
5
6
7
8
1.2 FW200 Boiler Energy Management
1.3 FB100 Remote Control & Room Sensor
1.4 IPM2 Space Heating Module
1.5 ISM2 Solar Module
2 Applications
9
9
Legend
List of most common applications
Boiler pump capacity in single zone systems
10
11
Single Zone Baseboard Systems:
2.1 System 1: Greenstar Heating Boiler in a
single zone system
13
17
21
2.2 System 2: Greenstar Combi Boiler in a
single zone system
2.3 System 3: Greenstar Heating Boiler in a single
zone system with DHW tank loading
2.4 System 4: Greenstar Heating Boiler in a single
zone system with solar thermal DHW and
boiler backup
25
Single Zone Systems with Primary/Secondary Piping:
2.5 System 5: Greenstar Heating Boiler in a
single zone system
29
33
37
2.6 System 6: Greenstar Combi Boiler in a
single zone system
2.7 System 7: Greenstar Heating Boiler in a single
zone system with DHW tank loading
2.8 System 8: Greenstar Heating Boiler in a single
zone system with room thermostat and DHW
tank loading
41
45
2.9 System 9: Greenstar Heating Boiler in a single
zone system with solar thermal DHW and
boiler backup
Multi-zone Systems with Primary/Secondary Piping:
2.10 System 10: Greenstar Heating Boiler with
zone pumps and room thermostats
49
2.11 System 11: Greenstar Heating Boiler with
zone pumps, room thermostats and DHW
tank loading
53
57
2.12 System 12: Greenstar Heating Boiler with
zone valves and room thermostats
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
4
Bosch Greenstar
Applications Manual
1 Information about the appliance
1.1 Boiler types and sizes
Greenstar Heating boilers
Greenstar 57: ZBR 16-3, 54,600btu (16kW) output
Greenstar 100: ZBR 28-3, 95,500btu (28kW) output
Greenstar 131: ZBR 35-3, 119,400btu (35kW) output
Greenstar 151: ZBR 42-3, 143,000btu (42kW) output
Greenstar Combi-boilers
Greenstar Combi 100: ZWB 28-3, 95,500btu (28kW)
output
Greenstar Combi 151: ZWB 42-3, 143,000btu (42kW)
output
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 5
Scope of delivery
1.2 FW200 Boiler Energy Management
System
The Boiler Energy Management System includes the
FW200 user programming interface with integrated
outdoor reset control.
2
3
In connection with the IPM2 module the FW200 offers
an outdoor reset control for two heating zones and
DHW generation with time programs:
8
1
—
Central heating
: Six weekly heating
programs with six programmable switch points
per day (one program is active).
5
4
—
—
DHW
points per day.
: weekly DHW program with six switch
DHW Recirculation pump program.
Options:
2x
2x
—
—
Remote control and room sensor FB100
provides status information and a programming
interface in each zone.
Fig. 1 FW200 Energy Management System
1 Controls top section
2 Base for wall-mounting
Module ISM2 for solar DHW heating and solar
space heating support.
3 Top cover
4 Installation and operating instructions
Programs and settings are stored in a permanent
memory and remain even during power outages.
5 Outdoor temperature sensor with mounting kit
Installation options:
—
—
In the boiler
Wall-mounted as a remote room sensor
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
6
Bosch Greenstar
Applications Manual
Scope of delivery
1.3 FB100 Remote Control & Room Sensor
The FB100 can only be connected
to systems with FW200 and a boiler
with BUS-enabled Heatronic 3.
3
2
The FB100 is a remote room sensor and user interface
that is used to display device and system information
and to change the settings of that particular zone.
8
The FB100 is designed for wall mounting.
In connection with the IPM2 module, the FB100
controls the assigned heating circuit using a timer
program. Three weekly heating programs with six
switch points per day are available for a heating circuit
(one program is active).
1
4
Maximum of four FB100 in a heating system with
FW200.
Fig. 2 FB100 Remote Control & Room Sensor
1 Upper part of remote control
2 Base for wall-mounting
In case of power failure, the display will be off. All
settings are saved.
3 Top cover
4 Installation and operating instructions
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 7
1.4 IPM2 Space Heating Module
The IPM2 module operates pumps and mixing valves of
2 heating zones. Each zone is run independently based
on the programming and feedback from the FB100 room
sensor (if installed). Instead of a second zone a DHW
recirculation pump can also be controlled by the IMP-2.
Combination overview
Outdoor reset controls
FW200
and primary room sensor
Remote control for
FB100
additional zones
2 mixed heating zones
1 mixed heating zone
+ 1 unmixed heating zone
+ 1 DHW recirculation pump
2 unmixed heating zones
Available
systems
+ 1 DHW recirculation pump
1 mixed heating zone
+ 1 storage tank
+ 1 DHW tank loading pump
1 unmixed heating zone
+ 1 storage tank
+ 1 DHW tank loading pump
Max. number of Modules
per system
max. 5 IPM2
Tab. 1
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
8
Bosch Greenstar
Applications Manual
1.5 ISM2 Solar Module
The ISM2 module controls the components of a solar
thermal system. Integration of solar thermal with a boiler
and central heating system for backup brings additional
benefits as it allows minimizing boiler run time and
reduces burner starts significantly compared to a non-
integrated system.
Combination overview
With the ISM2 module, it is possible to realize a variety of
solar thermal systems.
Basic solar thermal systems
System 1 : Solar thermal DHW heating
System 2 : Solar thermal DHW heating and space
heating support
System expansions
Option A : Two collector arrays (east/west orientation)
Option B : Reloading system with two single coil DHW
tanks
Option C : First/second priority system with 2 tanks,
realized with
—
—
p-p : a separate pump for each tank
p-v : common pump and diverter valve
Option D : External heat exchanger on the solar circuit
Option E : Thermal disinfection of the solar tank
Combine a basic system with one or several options to
realize the desired solar system.
This manual shows basic solar thermal DHW systems only.
For information on all options, please consult the Installa-
tion and Service Manual.
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 9
2 Applications
Legend
Flow check valve
pipe
pipe
Greenstar
Greenstar boiler
Greenstar
Greenstar combi-boiler
Fig. 3 Legend
NOTICE: All drawings in this manual are conceptual in nature and only depict components relevant for the systems
shown. It is the installer's responsibility to know national and local code and install safety devices as required. Install
and size peripheral devices such as air purge, expansion vessel, feeder valve, mud separator, shutoff valves, etc. per best
installation practices. Contact Bosch with installation related questions.
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
10
Bosch Greenstar
Applications Manual
List of most common applications
Single Zone Baseboard Systems:
System 1: Greenstar Heating Boiler in a single zone
system (page 13-16).
System 2: Greenstar Combi-Boiler in a single zone
system (page 17-20).
System 3: Greenstar Heating Boiler in a single zone
system with DHW tank loading ( page 21-24).
System 4: Greenstar Heating Boiler in a single zone
system with solar thermal DHW and boiler backup
(page 25-28).
Single Zone Systems with Primary/Secondary Piping:
System 5: Greenstar Heating Boiler in a single zone
system (page 29-32)
System 6: Greenstar Combi-Boiler in a single zone
system (page 33-36).
System 7: Greenstar Heating Boiler in a single zone
system with DHW tank loading (page 37-40)
System 8: Greenstar Heating Boiler in a single zone
system with room thermostat and DHW tank loading
(page 41-44).
System 9: Greenstar Heating Boiler in a single zone
system with solar thermal DHW and boiler backup
(page 45-48).
Multi-zone Systems with Primary/Secondary Piping:
System 10: Greenstar Heating Boiler with zone pumps
and room thermostats (page 49-52).
System 11: Greenstar Heating Boiler with zone pumps,
room thermostats, and DHW tank loading (page 53-
56).
System 12: Greenstar Heating Boiler with zone valves
and room thermostats ( page 57-60).
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 11
Boiler pump capacity in single zone systems
When installing the boiler in a single zone application
without primary/secondary piping, it is critical not to
overload the pump. Use the Greenstar Heating or Combi
Boiler in this setup only in low pressure baseboard
applications. Radiant floor, panel radiator, or multi-zone
applications require primary/secondary piping. Do not
install zone valves with this system.
Recommended maximum: 70' (21 m) of 3/4" baseboard
at a 20°F delta T and a flow rate of 4.0 gpm. This allows
sufficient reserves for the necessary supply and return
piping plus elbows.
Alternatively determine the system pressure drop on a case
by case basis to verify that the boiler pump is capable of
delivering the required flow rate. Table 2 provides as an
example the pressure drop of 100’ of 3/4” baseboard and
its relevant heat output.
Water Flow
Pressure Drop per 100'
MBH output per 100’ at shown Medium Water Temperature
and 65°F Room Temperature
GPM
feet of head
110°F
120°F
130°F
140°F
150°F
160°F
170°F
180°F
4
4.375
16
12
26
32
38
46
54
61
Tab. 2 Pressure drop and heat output for ¾” baseboard
Add to that the pressure drop of supply and return piping
plus elbows and other devices like check valves.
Use the pump curves on the following page to verify that
the pump is capable of delivering the needed flow rate for
the given pressure drop of the system.
In order to save as much energy as possible and
keep water circulation noises to a minimum, select
the lowest possible pump speed.
If the working pressure cannot be met, use primary/
secondary piping.
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
12
Bosch Greenstar
Applications Manual
Pump curve of heating boiler
Pump curve of combi boiler (heating side)
25
20
15
10
5
25
20
15
10
5
4
4
3
6
2
4
1
3
2
5
1
0
0
0
1
2
3
4
6
7
8
0
1
2
3
5
7
8
.
.
V / gpm
V / gpm
7
6
7
6
5
4
3
2
1
0
5
4
4
4
3
3
2
1
0
2
1
3
2
1
0
400
800
1200
1600
0
200 400 600 800 1000 1200 1400 1600
.
.
V / l/h
V / l/h
6 720 641 933-59.1O
6 720 641 933-61.1O
Fig. 4
Greenstar boiler pump curves
Key to Fig. 4
4
H
V
Head pressure of the boiler pump by itself (at speed 3)
Head pressure in feet of head (m)
Circulating water volume in gallons per minute (l/h)
1
2
3
Residual head pressure at speed 1
Residual head pressure at speed 2
Residual head pressure at speed 3 (default setting)
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 13
2.1 System 1: Greenstar Heating Boiler in a
single zone system
Summary:
Single boiler supplying one baseboard heating zone
equipped with FW200 outdoor reset controller with built-in
room sensor in the living space. This system is using the
boiler pump for zone water circulation.
This design can only be used with a single loop baseboard
system that has a low pressure drop. Radiant floors, panel
radiator, or multi zone systems require primary-secondary
piping. Do not install zone valves with this system.
The pump will run in constant circulation except when in
warm weather shutdown.
Max. 70' (21 m) of 3/4" baseboard at a 20°F delta T and a
flow rate of 4.0 gpm plus the necessary supply and return
piping.
In detail:
The FW200 is an outdoor temperature based controller
with room temperature influence. The controller adjusts
the heating curve (boiler supply temperature) according to
outdoor temperature. When the FW200 is wall mounted,
it also uses room temperature to adjust the heating curve
and modify boiler supply temperature.
FW200 provides warm weather shutdown.
Required components:
Greenstar heating boiler.
FW200 controller in the room.
Additional instructions:
See manufacturer’s installation and operating instructions.
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
14
Bosch Greenstar
Applications Manual
System 1 - Piping Diagram
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 15
System 1 - Wiring Diagram
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
16
Bosch Greenstar
Applications Manual
System 1: Setup and Programming
When done, ensure the mode selector is set to AUTO.
The room temperature will be displayed.
In this single zone system the FW200 is installed in the
living space in a location that represents the conditions
of the entire zone. Avoid locations exposed to direct or
indirect sunlight, heat sources, draft, etc. that can lead to
over compensation.
Additional information:
With outdoor reset the boiler will provide the water tem-
perature according to the heating curve adjusted by the
level of room influence (if enabled).
Initial setup:
The boiler will always attempt to run at its highest
efficiency in low fire for as long as necessary.
See the installation instructions for description of buttons
and displays, and for details on setup and programming.
The boiler will shut down when the target temperature
is reached followed by a 3 minute post purge by the
pump.
Power up the boiler.
When commissioning for the first time set the display
language, date and time.
—
The boiler and the pump will start again when
the supply water temperature drops 18°F (10°C)
below the set point.
Upon first commissioning the automatic system
configuration starts. Wait 60 seconds and follow the
instructions displayed. You have the option of using
the factory settings or entering custom parameters to
better match the individual requirements.
Set up the weekly heating program for the three
available temperature levels:
—
—
Comfort
Economy
—
Frost (Frost protection)
Take advantage of using one of the preset programs
from the list or enter a custom program.
—
—
—
—
—
—
—
—
—
Program A
Program F
AM weekday worker
PM weekday worker
All day
All day, lunch
Family
All day, early shift
All day, late shift
—
Seniors
Set the room temperatures for the three specified
temperature levels.
Enter the installer menu to configure the heating zone.
—
—
Set heating circuit type to Baseboard.
Set the minimum outdoor temperature, building
storage capacity, design day temperature, and
maximum supply temperature.
—
Set the room influence followed by the
remaining parameters as they apply to the
system.
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 17
2.2 System 2: Greenstar Combi Boiler in a
single zone system
Summary:
Additional instructions:
See manufacturer’s installation and operating instructions.
Single combi-boiler supplying one baseboard heating
zone equipped with FW200 outdoor reset controller with
built-in room sensor in the living space. DHW generation
directly off the boiler through the tankless heat exchanger.
This system is using the boiler pump for zone water circu-
lation.
Install an adequately sized Pressure Relief Valve (PRV) on
the DHW outlet of the combi boiler.
To reduce the risk of scalding it is recommended to install
a DHW tempering valve.
The “combi” or combination boiler is a high efficiency
central heating boiler and water heater combined within
one compact unit. Water is heated on demand directly
from the water main eliminating the need for a hot water
storage tank.
The Greenstar combi boiler is equipped with an inter-
nal 3.17 gal (12 liter) expansion vessel. The installation
manual provides information on how to determine if it is
of sufficient capacity for the application or if an additional
expansion vessel is needed.
This design can only be used with a single loop baseboard
system that has a low pressure drop. Radiant floors, panel
radiator, or multi zone systems require primary-secondary
piping. Do not install zone valves with this system.
The pump will run in constant circulation while in space
heating mode except during a call for DHW or when in
warm weather shutdown.
Max. 70' (21 m) of 3/4" baseboard at a 20°F delta T and a
flow rate of 4.0 gpm plus the necessary supply and return
piping..
In detail:
The FW200 is an outdoor temperature based controller
with room temperature influence. The controller adjusts
the heating curve (boiler supply temperature) according to
outdoor temperature. When the FW200 is wall mounted,
it also uses room temperature to adjust the heating curve
and modify boiler supply temperature.
FW200 provides warm weather shutdown.
Required components:
Greenstar combi-boiler.
FW200 controller in the room.
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
18
Bosch Greenstar
Applications Manual
System 2 - Piping diagram
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 19
System 2 - Wiring diagram
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
20
Bosch Greenstar
Applications Manual
System 2: Setup and Programming
Enter the installer menu to configure the heating zone.
In this single zone system the FW200 is installed in the
living space in a location that represents the conditions
of the entire zone. Avoid locations exposed to direct or
indirect sunlight, heat sources, draft, etc. that can lead to
over compensation.
—
—
Set heating circuit type to Baseboard.
Set the minimum outdoor temperature, building
storage capacity, design day temperature, and
maximum supply temperature.
—
Set the room influence followed by the
remaining parameters as applicable.
DHW is generated directly by the combi-boiler without the
need for a storage tank.
Set up the weekly program for DHW generation.
For additional features of the combi boiler see the
installation manual.
Initial setup:
See the installation instructions for description of buttons
and displays, and for details on setup and programming.
When done, ensure the mode selector is set to AUTO.
The room temperature will be displayed.
Power up the boiler.
When commissioning for the first time set the display
language, date and time.
Additional information
With outdoor reset the boiler will provide the water tem-
perature according to the heating curve adjusted by the
level of room influence (if enabled).
Upon first commissioning the automatic system
configuration starts. Wait 60 seconds and follow the
instructions displayed. You have the option of using
the factory settings or entering custom parameters to
better match the individual requirements.
The boiler will always attempt to run at its highest
efficiency in low fire for as long as necessary.
Set up the weekly heating program for the three avail-
able temperature levels:
The boiler will shut down when the target temperature
is reached followed by a 3 minute post purge by the
pump.
—
—
Comfort
Economy
The boiler and the pump will start again when the
supply water temperature drops 18°F (10°C) below
the set point.
—
Frost (Frost protection)
Take advantage of using one of the preset programs
from the list or enter a custom program.
When the demand for hot water is sensed by the flow
sensor, the boiler will change to DHW mode. When the
DHW demand ends, the boiler will return to heating
mode.
—
—
—
—
—
—
—
—
—
Program A
Program F
AM weekday worker
PM weekday worker
All day
All day, lunch
Family
All day, early shift
All day, late shift
—
Seniors
Set the room temperatures for the three specified
temperature levels.
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 21
2.3 System 3: Greenstar Heating Boiler in a
single zone system with DHW tank loading
Summary:
Single boiler supplying one baseboard heating zone
equipped with FW200 outdoor reset controller with built-
in room sensor in the living space. This system is using the
boiler pump for zone water circulation and DHW tank load-
ing. A diverter valve is used to switch between space heat-
ing and tank loading. This system is identical to System 1
with an added indirect fired DHW tank.
This design can only be used with a single loop baseboard
system that has a low pressure drop. Radiant floors, panel
radiator, or multi zone systems require primary-secondary
piping.
Max. 70' (21 m) of 3/4" baseboard at a 20°F delta T and a
flow rate of 4.0 gpm plus the necessary supply and return
piping.
Ensure to select a DHW tank with a coil pressure drop that
does not exceed the capacity of the boiler pump.
In detail:
The FW200 is an outdoor temperature based controller
with room temperature influence. The controller adjusts
the heating curve (boiler supply temperature) according to
outdoor temperature. When the FW200 is wall mounted,
it also uses room temperature to adjust the heating curve
and modify boiler supply temperature.
FW200 provides warm weather shutdown.
Required components:
Greenstar combi-boiler.
FW200 controller in the room.
Indirect Fired DHW Tank.
Diverter valve 120VAC, 3-way, spring return.
Additional instructions:
See manufacturer’s installation and operating instructions.
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
22
Bosch Greenstar
Applications Manual
System 3 - Piping diagram
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 23
System 3 - Wiring diagram
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
24
Bosch Greenstar
Applications Manual
System 3: Setup and Programming
Set up the weekly program for DHW tank loading and
the DHW recirculation pump (if installed). Separate
individual programs can be set up or the hours of op-
eration can be linked to the heating program.
In this single zone system the FW200 is installed in the
living space in a location that represents the conditions
of the entire zone. Avoid locations exposed to direct or
indirect sunlight, heat sources, draft, etc. that can lead to
over compensation.
Enter the installer menu to configure the heating zone.
—
—
Set heating circuit type to Baseboard.
Set the minimum outdoor temperature, building
storage capacity, design day temperature, and
maximum supply temperature.
Initial setup:
See the installation instructions for description of buttons
and displays, and for details on setup and programming.
—
Set the room influence followed by the
remaining parameters as applicable.
Power up the boiler.
When done, ensure the mode selector is set to AUTO.
The room temperature will be displayed.
When commissioning for the first time, set the display
language, date and time.
Upon first commissioning the automatic system
configuration starts. Wait 60 seconds and follow the
instructions displayed. You have the option of using
the factory settings or entering custom parameters to
better match the individual requirements.
Additional information
With outdoor reset the boiler will provide the water
temperature according to the heating curve adjusted by
level of room influence (if enabled).
Set up the weekly heating program for the three
available temperature levels:
The boiler will always attempt to run at its highest
efficiency in low fire for as long as necessary.
—
—
Comfort
Economy
The boiler will shut down when the target temperature
is reached followed by a 3 minute post purge by the
pump.
—
Frost (Frost protection)
Take advantage of using one of the preset programs
from the list or enter a custom program.
The boiler and the pump will start again when the
supply water temperature drops 18°F (10°C) below
the set point.
—
—
—
—
—
—
—
—
—
Program A
Program F
When the demand for hot water is sensed by the flow
sensor, the boiler will change to DHW mode. When the
DHW demand ends, the boiler will return to heating
mode.
AM weekday worker
PM weekday worker
All day
All day, lunch
Family
All day, early shift
All day, late shift
—
Seniors
Set the room temperatures for the three specified
temperature levels.
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 25
2.4 System 4: Greenstar Heating Boiler in a
single zone system with solar thermal
DHW and boiler backup
Summary:
Required components:
Single boiler supplying one baseboard heating zone
equipped with FW200 outdoor reset controller with built-
in room sensor in the living space . This system is using
the boiler pump for zone water circulation and DHW tank
loading. A diverter valve is used to switch between space
heating and tank loading. This system is identical to Sys-
tem 3 with an added solar thermal DHW heating system.
Greenstar combi-boiler.
FW200 controller in the room.
ISM2.
DHW solar tank with 2 coils.
Bosch solar thermal system complete.
This design can only be used with a single loop baseboard
system that has a low pressure drop. Radiant floors, panel
radiator, or multi zone systems require primary-secondary
piping. Do not install zone valves with this system.
Diverter valve 120VAC, 3-way, spring return.
Additional instructions:
See manufacturer’s installation and operating instructions.
Max. 70' (21 m) of 3/4" baseboard at a 20°F delta T and a
flow rate of 4.0 gpm plus the necessary supply and return
piping.
The Bosch Greenstar boiler and ISM2 offer many different
solar thermal applications including space heating sup-
port and pool heating. Please consult the installation and
operating instructions for details.
Ensure to select a solar tank with a boiler coil pressure
drop that does not exceed the capacity of the boiler pump
(see pages 11 & 12 for details).
Solar thermal provides renewable energy to heat DHW year
round, and if sized properly reduce energy consumption
significantly. Bosch offers plug and play components
that are designed to work together with a boiler backup
system. Bosch solar thermal systems are qualified for
government and utility incentives reducing the upfront
investment cost significantly. Bosch solar thermal
collectors work even in the winter and under cloudy skies
preheating water, and reducing boiler run time and burner
starts.
In detail:
The FW200 is an outdoor temperature based controller
with room temperature influence. The controller adjusts
the heating curve (boiler supply temperature) according to
outdoor temperature. When the FW200 is wall mounted,
it also uses room temperature to adjust the heating curve
and modify boiler supply temperature.
FW200 provides warm weather shutdown.
The control of the solar thermal system is integrated with
the FW200 boiler control, and reduces boiler run time and
burner starts significantly compared to independent sys-
tems. The solar pump will run whenever the collectors are
16°F (9°C) warmer than the bottom of the solar tank.
It is recommended to double the volume of the solar
thermal DHW tank compared to an equivalent conventional
indirect fired DHW tank. This allows sufficient backup
volume ("comfort zone") maintained by the boiler without
sacrificing capacity for solar harvesting.
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
26
Bosch Greenstar
Applications Manual
System 4 - Piping diagram
R1
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 27
System 4 - Wiring diagram
R1
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
28
Bosch Greenstar
Applications Manual
System 4: Setup and Programming
Set up the weekly program for DHW tank loading and
the DHW recirculation pump (if installed). Separate
individual programs can be set up or the hours of op-
eration can be linked to the heating program.
In this single zone system the FW200 is installed in the
living space in a location that represents the conditions
of the entire zone. Avoid locations exposed to direct or
indirect sunlight, heat sources, draft, etc. that can lead to
over compensation.
Enter the installer menu to configure the heating zone.
—
—
Set heating circuit type to Baseboard.
Set the minimum outdoor temperature, building
storage capacity, design day temperature, and
maximum supply temperature.
Initial setup:
See the installation instructions for description of buttons
and displays, and for details on setup and programming.
—
Set the room influence followed by the
remaining parameters as applicable.
Power up the boiler.
Proceed in the installer menu to configure the solar
thermal system. The solar system requires manual
configuration.
Use the FW200 for programming the heating system.
When commissioning for the first time, set the display
language, date and time.
—
—
Run solar system: Yes
Solar system parameters: Standard system.
Upon first commissioning the automatic system
configuration starts. Wait 60 seconds and follow the
instructions displayed. You have the option of using
the factory settings or entering custom parameters to
better match the individual requirements.
—
—
Set options A2 to E as required.
It is recommended to keep the factory default
solar system parameters.
Exit the installer menu.
Set up the weekly heating program for the three
available temperature levels:
When done, ensure the mode selector is set to AUTO.
The room temperature will be displayed.
—
—
Comfort
Economy
—
Frost (Frost protection)
Additional information
Take advantage of using one of the preset programs
from the list or enter a custom program.
The solar thermal system will start harvesting energy once
the collector temperature is at least 16°F (9°C) warmer
than the bottom of the solar tank. The upper half of the
solar tank ("comfort zone") is maintained at temperature
as set in the DHW programming. The lower half is available
for solar harvesting.
—
—
—
—
—
—
—
—
—
Program A
Program F
AM weekday worker
PM weekday worker
All day
With outdoor reset the boiler will provide the water
temperature according to the heating curve adjusted by
the level of room influence (if enabled).
All day, lunch
Family
The boiler will always attempt to run at its highest
efficiency in low fire for as long as necessary.
All day, early shift
All day, late shift
The boiler will shut down when the target temperature
is reached followed by a 3 minute post purge by the
pump.
—
Seniors
The boiler and the pump will start again when the
supply water temperature drops 18°F (10°C) below
the set point.
Set the room temperatures for the three specified
temperature levels.
When the demand for hot water is sensed by the flow
sensor, the boiler will change to DHW mode. When the
DHW demand ends, the boiler will return to heating
mode.
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 29
2.5 System 5: Greenstar Heating Boiler in a
single zone system
Summary:
Single boiler with primary/secondary piping configuration
supplying one heating zone. Outdoor reset with FW200
controller with built-in room sensor mounted in the living
space for room feedback.
Use this design where System 1 cannot be used due to too
great a system pressure drop. Primary/secondary piping is
also required for radiant floor and panel radiator applica-
tions.
Primary/secondary piping isolates the system flow from
the boiler flow and prevents the system from influencing
boiler performance.
In detail:
The FW200 is an outdoor temperature based controller
with room temperature influence. The controller adjusts
the heating curve (boiler supply temperature) according
to outdoor temperature. When the FW200 is wall mounted
as a room sensor, it uses room temperature to adjust the
heating curve and modify boiler supply temperature ac-
cordingly.
FW200 provides warm weather shutdown.
For temperature sensitive radiant floor applications, install
a thermostatic tempering valve for overheat protection.
Required components:
Greenstar heating boiler.
FW200 controller in the room.
Primary/secondary piping and system pump.
Thermostatic mixing valve (optional - overheat
protection for temperature sensitive floors).
Additional instructions:
See manufacturer’s installation and operating instructions.
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
30
Bosch Greenstar
Applications Manual
System 5 - Piping diagram
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 31
System 5 - Wiring diagram
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
32
Bosch Greenstar
Applications Manual
System 5: Setup and Programming
Enter the installer menu to configure the heating zone.
In this single zone system the FW200 is installed in the
living space in a location that represents the conditions
of the entire zone. Avoid locations exposed to direct or
indirect sunlight, heat sources, draft, etc. that can lead to
over compensation.
—
Set heating circuit to the type of heat
distribution system used.
—
Set the minimum outdoor temperature, building
storage capacity, design day temperature, and
maximum supply temperature.
—
Set the room influence followed by the
remaining parameters as applicable.
Initial setup:
See the installation instructions for description of buttons
and displays, and for details on setup and programming.
Set up the weekly program for DHW generation.
When done, ensure the mode selector is set to AUTO.
The room temperature will be displayed.
Power up the boiler.
When commissioning for the first time set the display
language, date and time.
Additional information
Upon first commissioning the automatic system
configuration starts. Wait 60 seconds and follow the
instructions displayed. You have the option of using
the factory settings or entering custom parameters to
better match the individual requirements.
With outdoor reset the boiler will provide the water
temperature according to the heating curve adjusted by
level of room influence (if enabled).
The boiler will always attempt to run at its highest
efficiency in low fire for as long as necessary.
Set up the weekly heating program for the three
available temperature levels:
The boiler will shut down when the target temperature
is reached followed by a 3 minute post purge by the
pump.
—
—
Comfort
Economy
—
Frost (Frost protection)
The boiler and the pump will start again when the
supply water temperature drops 18°F (10°C) below
the set point.
Take advantage of using one of the preset programs
from the list or enter a custom program.
When the demand for hot water is sensed by the flow
sensor, the boiler will change to DHW mode. When the
DHW demand ends, the boiler will return to heating
mode.
—
—
—
—
—
—
—
—
—
Program A
Program F
AM weekday worker
PM weekday worker
All day
All day, lunch
Family
All day, early shift
All day, late shift
—
Seniors
Set the room temperatures for the three specified
temperature levels.
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 33
2.6 System 6: Greenstar Combi Boiler in a
single zone system
Summary:
Additional instructions:
See manufacturer’s installation and operating instructions.
Single combi-boiler supplying one heating zone. Outdoor
reset with FW200 controller with built-in room sensor
mounted in the living space for room feedback. DHW
generation directly off the boiler through the tankless heat
exchanger. This system is using the boiler pump for zone
water circulation.
Install an adequately sized Pressure Relief Valve (PRV) on
the DHW outlet of the combi boiler.
To reduce the risk of scalding it is recommended to install
a DHW tempering valve.
The “combi” or combination boiler is a high efficiency
central heating boiler and water heater combined within
one compact unit. Water is heated on demand directly
from the water main eliminating the need for a hot water
storage tank.
The Greenstar combi boiler is equipped with an internal
3.17 gal (12 liter) expansion vessel. The installation
manual provides information on how to determine if it is
of sufficient capacity for the application or if an additional
expansion vessel is needed.
Single boiler with primary/secondary piping configuration
supplying one heating zone. Outdoor reset with FW200
controller and room sensor mounted in the living space for
room feedback.
Use this design where System 2 cannot be used due to too
great a system pressure drop. Primary/secondary piping is
also required for radiant floor and panel radiator applica-
tions.
Primary/secondary piping isolates the system flow from
the boiler flow and prevents the system from influencing
boiler performance.
In detail:
The FW200 is an outdoor temperature based controller
with room temperature influence. The controller adjusts
the heating curve (boiler supply temperature) according
to outdoor temperature. When the FW200 is wall mounted
as a room sensor, it uses room temperature to adjust the
heating curve and modify boiler supply temperature ac-
cordingly.
FW200 provides warm weather shutdown.
For temperature sensitive radiant floor applications, install
a thermostatic tempering valve for overheat protection.
Required components:
Greenstar combi-boiler.
FW200 controller in the room.
Primary/secondary piping and system pump.
Thermostatic mixing valve (optional - overheat
protection for temperature sensitive floors).
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
34
Bosch Greenstar
Applications Manual
System 6 - Piping diagram
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 35
System 6 - Wiring diagram
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
36
Bosch Greenstar
Applications Manual
System 6: Setup and Programming
Enter the installer menu to configure the heating zone.
In this single zone system the FW200 is installed in the
living space in a location that represents the conditions
of the entire zone. Avoid locations exposed to direct or
indirect sunlight, heat sources, draft, etc. that can lead to
over compensation.
—
Set heating circuit to the type of heat
distribution system used.
—
Set the minimum outdoor temperature, building
storage capacity, design day temperature, and
maximum supply temperature.
DHW is generated directly by the combi-boiler without the
need for a storage tank.
—
Set the room influence followed by the
remaining parameters as applicable.
Set up the weekly program for DHW generation.
Initial setup:
For additional features of the combi boiler see the
installation manual.
See the installation instructions for description of buttons
and displays, and for details on setup and programming.
When done, ensure the mode selector is set to AUTO.
The room temperature will be displayed.
Power up the boiler.
When commissioning for the first time set the display
language, date and time.
Additional information
With outdoor reset the boiler will provide the water
temperature according to the heating curve adjusted by
the level of room influence (if enabled).
Upon first commissioning the automatic system
configuration starts. Wait 60 seconds and follow the
instructions displayed. You have the option of using
the factory settings or entering custom parameters to
better match the individual requirements.
The boiler will always attempt to run at its highest
efficiency in low fire for as long as necessary.
Set up the weekly heating program for the three
available temperature levels:
The boiler will shut down when the target temperature
is reached followed by a 3 minute post purge by the
pump.
—
—
Comfort
Economy
The boiler and the pump will start again when the
supply water temperature drops 18°F (10°C) below
the set point.
—
Frost (Frost protection)
Take advantage of using one of the preset programs
from the list or enter a custom program.
When the demand for hot water is sensed by the flow
sensor, the boiler will change to DHW mode. When the
DHW demand ends, the boiler will return to heating
mode.
—
—
—
—
—
—
—
—
—
Program A
Program F
AM weekday worker
PM weekday worker
All day
All day, lunch
Family
All day, early shift
All day, late shift
—
Seniors
Set the room temperatures for the three specified
temperature levels.
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 37
2.7 System 7: Greenstar Heating Boiler in a
single zone system with DHW tank loading
Summary:
Single boiler with primary/secondary piping configuration
supplying one heating zone. Outdoor reset with FW200
controller with built-in room sensor mounted in the living
space for room feedback.
Use this design where System 3 cannot be used due to
too great a system pressure drop. Primary/secondary
piping is also required for radiant floor and panel radiator
applications.
Primary/secondary piping isolates the system flow from
the boiler flow and prevents the system from influencing
boiler performance.
This system is identical to System 5 with an added indirect
fired DHW tank.
Use this system over System 6 where the combi-boiler
does not have the required DHW volume flow capacity;
keep in mind however that the tank capacity is not endless
compared to that of the combi-boiler.
In detail:
The FW200 is an outdoor temperature based controller
with room temperature influence. The controller adjusts
the heating curve (boiler supply temperature) according
to outdoor temperature. When the FW200 is wall mounted
as a room sensor, it uses room temperature to adjust the
heating curve and modify boiler supply temperature ac-
cordingly.
FW200 provides warm weather shutdown.
For temperature sensitive radiant floor applications, install
a thermostatic tempering valve for overheat protection.
Required components:
Greenstar heating boiler.
FW200 controller in the room.
Primary/secondary piping and system pump.
Thermostatic mixing valve (optional - overheat
protection for temperature sensitive floors).
Indirect Fired DHW Tank.
Tank loading pump of sufficient capacity.
Additional instructions:
See manufacturer’s installation and operating instructions.
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
38
Bosch Greenstar
Applications Manual
System 7 - Piping diagram
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 39
System 7 - Wiring diagram
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
40
Bosch Greenstar
Applications Manual
System 7: Setup and Programming
Enter the installer menu to configure the heating zone.
In this single zone system the FW200 is installed in the
living space in a location that represents the conditions
of the entire zone. Avoid locations exposed to direct or
indirect sunlight, heat sources, draft, etc. that can lead to
over compensation.
—
Set heating circuit to the type of heat
distribution system used.
—
Set the minimum outdoor temperature, building
storage capacity, design day temperature, and
maximum supply temperature.
DHW is generated directly by the combi-boiler without the
need for a storage tank.
—
Set the room influence followed by the
remaining parameters as applicable.
Set up the weekly program for DHW generation.
When done, ensure the mode selector is set to AUTO.
The room temperature will be displayed.
Initial setup:
See the installation instructions for description of buttons
and displays, and for details on setup and programming.
Power up the boiler.
Additional information
When commissioning for the first time, set the display
language, date and time.
With outdoor reset the boiler will provide the water
temperature according to the heating curve adjusted by
the level of room influence (if enabled).
Upon first commissioning the automatic system
configuration starts. Wait 60 seconds and follow the
instructions displayed. You have the option of using
the factory settings or entering custom parameters to
better match the individual requirements.
The boiler will always attempt to run at its highest
efficiency in low fire for as long as necessary.
The boiler will shut down when the target temperature
is reached followed by a 3 minute post purge by the
pump.
Set up the weekly heating program for the three
available temperature levels:
—
—
Comfort
Economy
The boiler and the pump will start again when the
supply water temperature drops 18°F (10°C) below
the set point.
—
Frost (Frost protection)
When a demand for DHW is sensed by the DHW tank
temperature sensor, the boiler will go into DHW mode.
When DHW is satisfied, or after one hour, the boiler
will return to space heating mode.
Take advantage of using one of the preset programs
from the list or enter a custom program.
—
—
—
—
—
—
—
—
—
Program A
Program F
AM weekday worker
PM weekday worker
All day
All day, lunch
Family
All day, early shift
All day, late shift
—
Seniors
Set the room temperatures for the three specified
temperature levels.
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 41
2.8 System 8: Greenstar Heating Boiler in a
single zone system with room thermostat
and DHW tank loading
Required components:
Summary:
Single boiler with primary/secondary piping configuration
supplying one heating zone. Outdoor reset with FW200
controller mounted on the boiler. 3rd party room thermo-
stat used to communicate heat demand.
Greenstar heating boiler.
FW200 controller in the room.
Primary/secondary piping and system pump.
This system is identical to System 7 except that it does not
feature constant circulation. The system circulator runs
only when a heat demand is communicated by the room
thermostat and shut off when the heat demand goes away.
Thermostatic mixing valve (optional - overheat
protection for temperature sensitive floors).
3rd party room thermostat ; self powered with dry
contact closure.
Use this design where Systems 1 through 4 cannot be
used due to too great a system pressure drop. Primary/
secondary piping is also required for radiant floor and
panel radiator applications.
Indirect Fired DHW Tank.
Tank loading pump of sufficient capacity.
Primary/secondary piping isolates the system flow from
the boiler flow and prevents the system from influencing
boiler performance.
Additional instructions:
See manufacturer’s installation and operating instructions.
This system is designed for installations with other
heat sources, e.g. wood stoves or significant solar gain.
Compared to systems with the FW200 installed in the
room that will throttle down the boiler output when the
room reaches its set point, in this setup the thermostat
will shut the boiler off.
This system can also be used with a combi boiler (see
system 6) instead of the indirect fired DHW tank.
In detail:
This system runs on pure outdoor reset without room
feedback on the heating curve. The FW200 installed
in the boiler adjusts the heating curve (boiler supply
temperature) according to outdoor temperature. The 3rd
party room thermostat turns the boiler on and off based
on the conditions in the living space.
FW200 provides warm weather shutdown.
For temperature sensitive radiant floor applications, install
a thermostatic tempering valve for overheat protection.
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
42
Bosch Greenstar
Applications Manual
System 8 - Piping diagram
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 43
System 8 - Wiring diagram
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
44
Bosch Greenstar
Applications Manual
System 8: Setup and Programming
Additional information
In this single zone system the FW200 is installed in the
boiler for pure outdoor reset without room influence.
With outdoor reset the boiler will provide the water
temperature according to the heating curve. There is no
Install a suitable 3rd party thermostat in the living space in room influence on the heating curve in this system. When
a location that represents the entire zone. Avoid locations
exposed to direct or indirect sunlight, heat sources, draft,
etc. that can lead to malfunctioning.
the zone is satisfied the boiler and pump will shut off.
The boiler will always attempt to run at its highest
efficiency in low fire for as long as necessary.
DHW is generated by the boiler loading the indirect fired
DHW tank following the DHW program.
The boiler will shut down when the target temperature
is reached followed by a 3 minute post purge by
the pump unless the 3rd party room thermostat is
satisfied prior.
Initial setup:
When a demand for DHW is sensed by the DHW tank
temperature sensor, the boiler will go into DHW mode.
When DHW is satisfied, or after one hour, the boiler
will return to space heating mode.
Program the 3rd party room thermostat according to the
manufacturer's instructions. it is recommended to set up a
day and night heating program with reduced temperatures
at night and when the home is unoccupied.
Boiler and FW200 programming:
See the installation instructions for description of buttons
and displays, and for details on setup and programming.
Power up the boiler.
When commissioning for the first time, set the display
language, date and time.
Upon first commissioning the automatic system
configuration starts. Wait 60 seconds and follow the
instructions displayed. You have the option of using
the factory settings or entering custom parameters to
better match the individual requirements.
Set the boiler for permanent day mode by switching
the dial on the FW200 to
—
Comfort
Enter the installer menu to configure the heating zone.
—
—
Set heating circuit to the type of heat
distribution system used.
Set the minimum outdoor temperature, building
storage capacity, design day temperature, and
maximum supply temperature.
Set up the weekly program for DHW generation.
When done, ensure the mode selector is set to AUTO.
The room temperature will be displayed.
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 45
2.9 System 9: Greenstar Heating Boiler in a
single zone system with solar thermal
DHW and boiler backup
Required components:
Summary:
Single boiler with primary/secondary piping configuration
supplying one heating zone. Outdoor reset with FW200
controller with built-in room sensor mounted in the living
space for room feedback.
Greenstar heating boiler.
FW200 controller in the room.
Primary/secondary piping and system pump.
Use this design where System 4 cannot be used due to too
great a system pressure drop. Primary/secondary piping is
also required for radiant floor and panel radiator applica-
tions.
Thermostatic mixing vavle (optional - overheat
protection for temperature sensitive floors).
ISM2.
Primary/secondary piping isolates the system flow from
the boiler flow and prevents the system from influencing
boiler performance.
DHW solar tank with 2 coils.
Bosch solar thermal system complete.
Tank loading pump of sufficient capacity.
Solar thermal provides renewable energy to heat DHW year
round, and if sized properly reduce energy consumption
significantly. Bosch offers plug and play components
that are designed to work together with a boiler backup
system. Bosch solar thermal systems are qualified for
government and utility incentives reducing the upfront
investment cost significantly. Bosch solar thermal
collectors work even in the winter and under cloudy skies
preheating water, and reducing boiler run time and burner
starts.
Additional instructions:
See manufacturer’s installation and operating instructions.
The Bosch Greenstar boiler and ISM2 offer many different
solar thermal applications including space heating sup-
port and pool heating. Please consult the installation and
operating instructions for details.
In detail:
The FW200 is an outdoor temperature based controller
with room temperature influence. The controller adjusts
the heating curve (boiler supply temperature) according
to outdoor temperature. When the FW200 is wall mounted
as a room sensor, it uses room temperature to adjust the
heating curve and modify boiler supply temperature ac-
cordingly.
FW200 provides warm weather shutdown.
The control of the solar thermal system is integrated with
the FW200 boiler control, and reduces boiler run time
and burner starts significantly compared to independent
systems. The solar pump will run whenever the collectors
are 16°F (9°C) warmer than the bottom of the solar tank.
For temperature sensitive radiant floor applications install
a thermostatic tempering valve for overheat protection.
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
46
Bosch Greenstar
Applications Manual
System 9 - Piping diagram
R1
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 47
System 9 - Wiring diagram
R1
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
48
Bosch Greenstar
Applications Manual
System 9: Setup and Programming
Set up the weekly program for DHW tank loading and
the DHW recirculation pump (if installed). Separate
individual programs can be set up or the hours of op-
eration can be linked to the heating program.
In this single zone system the FW200 is installed in the
living space in a location that represents the conditions
of the entire zone. Avoid locations exposed to direct or
indirect sunlight, heat sources, draft, etc. that can lead to
over compensation.
Enter the installer menu to configure the heating zone.
—
Set heating circuit to the type of heat
distribution used.
—
Set the minimum outdoor temperature, building
storage capacity, design day temperature, and
maximum supply temperature.
Initial setup:
See the installation instructions for description of buttons
and displays, and for details on setup and programming.
Proceed in the installer menu to configure the solar
thermal system. (The solar system requires manual
configuration).
Power up the boiler.
Use the FW200 for programming the heating system.
—
—
Run solar system: Yes
Solar system parameters: Standard system.
When commissioning for the first time set the display
language, date and time.
—
—
Set options A2 to E as required.
Upon first commissioning the automatic system
configuration starts. Wait 60 seconds and follow the
instructions displayed. You have the option of using
the factory settings or entering custom parameters to
better match the individual requirements.
It is recommended to keep the factory default
solar sys parameters.
Exit the installer menu.
When done, ensure the mode selector is set to AUTO.
The room temperature will be displayed.
Set up the weekly heating program for the three
available temperature levels:
—
—
Comfort
Economy
Additional information
The solar thermal system will start harvesting energy
once the collector temperature is at least 16°F (9°C)
warmer than the bottom of the solar tank. The upper
half of the solar tank ("comfort zone") is maintained at
temperature by the boiler during DHW day mode as set in
the DHW programming. The lower half is available for solar
harvesting.
—
Frost (Frost protection)
Take advantage of using one of the preset programs
from the list or enter a custom program.
—
—
—
—
—
—
—
—
—
Program A
Program F
AM weekday worker
PM weekday worker
All day
With outdoor reset the boiler will provide the water
temperature according to the heating curve adjusted by
the level of room influence (if enabled).
The boiler will always attempt to run at its highest
efficiency in low fire for as long as necessary.
All day, lunch
Family
The boiler will shut down when the target temperature
is reached followed by a 3 minute post purge by the
pump.
All day, early shift
All day, late shift
The boiler and the pump will start again when the
supply water temperature drops 18°F (10°C) below
the set point.
—
Seniors
Set the room temperatures for the three specified
temperature levels.
When the demand for hot water is sensed by the flow
sensor, the boiler will change to DHW mode. When the
DHW demand ends, the boiler will return to heating
mode.
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 49
2.10 System 10: Greenstar Heating Boiler with
zone pumps and room thermostats
Summary:
Required components:
Single boiler with primary/secondary piping configura-
tion supplying multiple heating zones. Outdoor reset with
FW200 controller mounted on the boiler. 3rd party room
thermostats are used to communicate zone heat demands.
Greenstar heating boiler.
FW200 controller in the boiler.
Primary/secondary piping and system pump.
This system is identical to System 8 expanded to multiple
zones. The zone circulators run only when a heat demand
is communicated by the room thermostat and shut off
when the heat demand goes away.
Thermostatic mixing vavle (optional - overheat
protection for temperature sensitive floors).
3rd party room thermostats with dry contact closure
in each zone.
Primary/secondary piping isolates the system flow from
the boiler flow and prevents the system from influencing
boiler performance.
Indirect Fired DHW Tank.
Tank loading pump of sufficient capacity.
This system works particularly well for installations with
other heat sources, e.g. wood stoves or significant solar
gain. Compared to systems with the FW200 installed in the
room that will throttle down the boiler output when the
room reaches its set point, in this setup the thermostat
will shut the boiler off.
Additional instructions:
See manufacturer’s installation and operating instructions.
This system can also be used with a combi boiler (see
system 6) instead of the indirect fired DHW tank.
In detail:
This system runs on pure outdoor reset without room
feedback on the heating curve. The FW200 installed in the
boiler adjusts the heating curve (boiler supply tempera-
ture) according to outdoor temperature. The 3rd party
room thermostats turn the boiler on and off based on the
conditions in the living space.
FW200 provides warm weather shutdown.
For temperature sensitive radiant floor applications install
a thermostatic tempering valve for overheat protection.
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
50
Bosch Greenstar
Applications Manual
System 10 - Piping diagram
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 51
System 10 - Wiring diagram
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
52
Bosch Greenstar
Applications Manual
System 10: Setup and Programming
Additional information
In this dual zone system the FW200 is installed in the
boiler for pure outdoor reset without room influence on
the heating curve.
With outdoor reset the boiler will provide the water
temperature according to the heating curve. There is no
room influence on the heating curve in this system.
The boiler will always attempt to run at its highest
efficiency in low fire for as long as necessary.
Install suitable 3rd party thermostats in each zone in
a location that best represents its conditions. Avoid
locations exposed to direct or indirect sunlight, heat
sources, draft, etc. that can lead to malfunctioning.
The boiler will shut down when the target temperature
is reached followed by a 3 minute post purge by
the pump unless the 3rd party room thermostat is
satisfied prior.
DHW is generated by the boiler loading the indirect fired
DHW tank following the DHW program.
During DHW day mode the boiler will charge the DHW
tank when a demand is sensed by the DHW tank tem-
perature sensor. When DHW is satisfied, or after one
hour, the boiler will return to space heating mode.
Initial setup:
Program the 3rd party room thermostats according to the
manufacturer's instructions. It is recommended to set up a
day and night heating program with reduced temperatures
at night and when the zone is unoccupied.
Boiler and FW200 programming:
See the installation instructions for description of buttons
and displays, and for details on setup and programming.
Power up the boiler.
When commissioning for the first time, set the display-
language, date and time.
Upon first commissioning the automatic system
configuration starts. Wait 60 seconds and follow the
instructions displayed. You have the option of using
the factory settings or entering custom parameters to
better match the individual requirements.
Set the boiler for permanent day mode by switching
the dial on the FW200 to
—
Comfort
Set the room temperatures for the three specified
temperature levels.
Enter the installer menu to configure the heating zone.
—
Set heating circuit to the type of heat
distribution used.
—
Set the minimum outdoor temperature, building
storage capacity, design day temperature, and
maximum supply temperature.
—
Set the remaining parameters as applicable.
Set up the weekly program for DHW generation.
When done, ensure the mode selector is set to AUTO.
The room temperature will be displayed.
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 53
2.11 System 11: Greenstar Heating Boiler
with zone pumps, relay panel, room
thermostats and DHW tank loading
Summary:
Required components:
Single boiler with primary/secondary piping configuration
supplying three heating zones controlled by individual
zone thermostats and a pump relay panel. Outdoor reset
with FW200 controller mounted on the boiler. 3rd party
room thermostats used to communicate heat demands
from the zones.
Greenstar heating boiler.
FW200 controller in the boiler.
Primary/secondary piping and system pump.
Thermostatic mixing valve (optional - overheat
protection for temperature sensitive floors).
This system does not feature constant circulation and the
zone circulators runs only when a heat demand is com-
municated by the room thermostat and shut off when the
heat demand goes away. It is similar to Systems 8 and 10
except that a pump relay panel is being used.
3rd party room thermostats with dry contact closure
in each zone.
Zone pump relay panel, e.g. TACO SR503 or similar.
Indirect fired DHW tank.
Primary/secondary piping isolates the system flow from
the boiler flow and prevents the system from influencing
boiler performance.
Tank loading pump of sufficient capacity.
This system works particularly well for installations with
other heat sources, e.g. wood stoves or significant solar
gain. Compared to systems with the FW200 installed in the
room that will throttle down the boiler output when the
room reaches its set point, in this setup the thermostat
will shut the boiler off.
Additional instructions:
See manufacturer’s installation and operating instructions.
This system can also be used with a combi boiler (see
system 6) instead of the indirect fired DHW tank.
In detail:
This system runs on pure outdoor reset without room
feedback on the heating curve. The FW200 installed in the
boiler adjusts the heating curve (boiler supply tempera-
ture) according to outdoor temperature. The 3rd party
room thermostats turn the boiler and the zone pumps on
and off based on the conditions in the living space.
FW200 provides warm weather shutdown.
For temperature sensitive radiant floor applications install
a thermostatic tempering valve for overheat protection.
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
54
Bosch Greenstar
Applications Manual
System 11 - Piping diagram
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 55
System 11 - Wiring diagram
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
56
Bosch Greenstar
Applications Manual
System 11: Setup and Programming
Additional information
In this multi zone system the FW200 is installed in the
boiler for pure outdoor reset without room influence on
the heating curve.
With outdoor reset the boiler will provide the water
temperature according to the heating curve. There is no
room influence on the heating curve in this system.
The boiler will always attempt to run at its highest
efficiency in low fire for as long as necessary.
Install suitable 3rd party thermostats in each zone in
a location that best represents its conditions. Avoid
locations exposed to direct or indirect sunlight, heat
sources, draft, etc. that can lead to malfunctioning.
The boiler will shut down when the target temperature
is reached followed by a 3 minute post purge by
the pump unless the 3rd party room thermostat is
satisfied prior.
DHW is generated by the boiler loading the indirect fired
DHW tank following the DHW program. This system can
also be realized with a combi boiler eliminating the DHW
tank if the capacity is sufficient for the DHW load.
During DHW day mode the boiler will charge the DHW
tank when a demand is sensed by the DHW tank tem-
perature sensor. When DHW is satisfied, or after one
hour, the boiler will return to space heating mode.
Initial setup:
Program the 3rd party room thermostats according to the
manufacturer's instructions. It is recommended to set up a
day and night heating program with reduced temperatures
at night and when the zone is unoccupied.
Boiler and FW200 programming:
See the installation instructions for description of buttons
and displays, and for details on setup and programming.
Power up the boiler.
When commissioning for the first time, set the display-
language, date and time.
Upon first commissioning the automatic system
configuration starts. Wait 60 seconds and follow the
instructions displayed. You have the option of using
the factory settings or entering custom parameters to
better match the individual requirements.
Set the boiler for permanent day mode by switching
the dial on the FW200 to
—
Comfort
Set the room temperatures for the
three specified temperature levels.
Enter the installer menu to configure the heating zone.
—
Set heating circuit to the type of heat
distribution used.
—
Set the minimum outdoor temperature, building
storage capacity, design day temperature, and
maximum supply temperature.
—
Set the remaining parameters as applicable.
Set up the weekly program for DHW generation.
When done, ensure the mode selector is set to AUTO.
The room temperature will be displayed.
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 57
2.12 System 12: Greenstar Heating Boiler with
zone valves and room thermostats
Summary:
Required components:
Single boiler with primary/secondary piping configura-
tion supplying three heating zones controlled by 3rd party
room thermostats with zone valves. Outdoor reset with
FW200 controller mounted on the boiler.
Greenstar heating boiler.
FW200 controller in the boiler.
Primary/secondary piping and system pump.
The zone circulator runs only when a heat demand is com-
municated by the room thermostats and shut off when the
heat demand goes away.
Thermostatic mixing valve (optional - overheat
protection for temperature sensitive floors).
3rd party room thermostats with dry contact closure
in each zone.
Primary/secondary piping isolates the system flow from
the boiler flow and prevents the system from influencing
boiler performance.
Zone valve panel (e.g. TACO ZVC403 or similar).
Zone pump (ECM recommended).
Indirect fired DHW tank.
This setup allows the use of a low energy ECM pump (e.g.
Grundfos Alpha) that adjusts the flow rate based on back
pressure depending on the number of zones calling.
This system works particularly well for installations with
other heat sources, e.g. wood stoves or significant solar
gain. Compared to systems with the FW200 installed in the
room that will throttle down the boiler output when the
room reaches its set point, in this setup the thermostat
will shut the boiler off.
Tank loading pump of sufficient capacity.
Additional instructions:
See manufacturer’s installation and operating instructions.
This system can also be used with a combi boiler (see
system 6) instead of the indirect fired DHW tank.
In detail:
This system runs on pure outdoor reset without room
feedback on the heating curve. The FW200 installed in the
boiler adjusts the heating curve (boiler supply tempera-
ture) according to outdoor temperature.
The 3rd party room thermostats turn the boiler and the
zone pump on and off based on the conditions in the living
space.
FW200 provides warm weather shutdown.
For temperature sensitive radiant floor applications install
a thermostatic tempering valve for overheat protection.
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
58
Bosch Greenstar
Applications Manual
System 12 - Piping diagram
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 59
System 12 - Wiring diagram
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
60
Bosch Greenstar
Applications Manual
System 12: Setup and Programming
Set up the weekly program for DHW generation.
When done, ensure the mode selector is set to AUTO.
The room temperature will be displayed.
In this multi zone system the FW200 is installed in the
boiler for pure outdoor reset without room influence
on the heating curve. Zone control is handled by a zone
valve panel with room thermostats in each zone. Use of
an ECM pump (e.g. Grundfos Alpha) for a zone pump
recommended to reduce energy consumption, risk of noisy
pipes, and to establish a constant delta T.
Additional information
With outdoor reset the boiler will provide the water
temperature according to the heating curve. There is no
room influence on the heating curve in this system.
Install suitable 3rd party thermostats in each zone in
a location that best represents its conditions. Avoid
locations exposed to direct or indirect sunlight, heat
sources, draft, etc. that can lead to malfunctioning.
The boiler will always attempt to run at its highest
efficiency in low fire for as long as necessary.
DHW is generated by the boiler loading the indirect fired
DHW tank following the DHW program. This system can
also be realized with a combi boiler eliminating the DHW
tank if the capacity is sufficient for the DHW load.
The boiler will shut down when the target temperature
is reached followed by a 3 minute post purge by
the pump unless the 3rd party room thermostat is
satisfied prior.
Initial setup:
During DHW day mode the boiler will charge the DHW
tank when a demand is sensed by the DHW tank tem-
perature sensor. When DHW is satisfied, or after one
hour, the boiler will return to space heating mode.
Program the 3rd party room thermostats according to the
manufacturer's instructions. It is recommended to set up a
day and night heating program with reduced temperatures
at night and when the zone is unoccupied.
Boiler and FW200 programming:
See the installation instructions for description of buttons
and displays, and for details on setup and programming.
Power up the boiler.
When commissioning for the first time, set the display-
language, date and time.
Upon first commissioning the automatic system
configuration starts. Wait 60 seconds and follow the
instructions displayed. You have the option of using
the factory settings or entering custom parameters to
better match the individual requirements.
Set the boiler for permanent day mode by switching
the dial on the FW200 to
—
Comfort
Set the room temperatures for the three specified
temperature levels.
Enter the installer menu to configure the heating zone.
—
Set heating circuit to the type of heat
distribution used.
—
Set the minimum outdoor temperature, building
storage capacity, design day temperature, and
maximum supply temperature.
—
Set the remaining parameters as applicable.
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 61
Bosch Thermotechnology Corp.
Data subject to change
Download from Www.Somanuals.com. All Manuals Search And Download.
|
62
Bosch Greenstar
Applications Manual
Data subject to change
Bosch Thermotechnology Corp.
Download from Www.Somanuals.com. All Manuals Search And Download.
Applications Manual
Bosch Greenstar | 63
Bosch Thermotechnology Corp.
Data subject to change