B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 1
MAINS POWERED
CARBON MONOXIDE ALARMS
WITH RECHARGEABLE LITHIUM CELL BACK-UP
Model Ei261ENRC
Model Ei261DENRC
WITH DIGITAL DISPLAY
Read and retain carefully for as long as the product is being used. Contains vital information on the
operation and installation. This leaflet should be regarded as part of the product.
If you are just installing the unit, this leaflet must be given to the householder. This leaflet is to be
given to any subsequent user.
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 3
CONTENTS
Page
4
1 IMPORTANT INFORMATION
6
2 CARBON MONOXIDE - THE SILENT KILLER
3 ALARM POSITIONING
10
15
20
22
22
24
25
27
27
28
30
32
4 INSTALLATION
5 TESTING
6 HOW TO DISTINGUISH BETWEEN CO ALARM & SMOKE ALARM WARNINGS
7 MAINTENANCE
8 LIMITATIONS OF CO ALARMS
9 HOW TO PROTECT YOUR FAMILY
10 GETTING YOUR CO ALARM SERVICED
11 FIVE YEAR GUARANTEE
12 TECHNICAL SPECIFICATIONS
13 TROUBLESHOOTING
14 ACCESSORIES
3
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 4
1. IMPORTANT INFORMATION
WARNING: The Alarm should be permanently wired to the mains by a qualified electrician in accordance
with IEE wiring regulations (BS7671).
Install a Carbon Monoxide (CO) Alarm in every room that contains a fuel burning appliance,
particularly rooms where people spend a lot of time e.g. bedrooms, kitchens and sitting rooms.
In rooms with an appliance, install (preferably) on the ceiling (300mm from walls and between 1m
to 3m horizontally from appliance). In rooms remote from the appliance install at breathing level,
where the light indicators can be seen.
Regularly check that the green power light is on, so that rechargeable back-up cells will remain fully
charged. Important: The CO Alarm will not work if the mains supply is off and the rechargeable
cells are depleted.
Test the unit weekly by pressing and holding the Test/Hush button. The horn will sound.
Replace sensor module after 5 years operation (see page 23).
4
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 5
WHAT TO DO WHEN THE ALARM SOUNDS:
?
(1) Open the doors and windows to ventilate the area.
(2) Turn off all fuel appliances where possible. (The alarm can be silenced immediately by
pushing the Test/Hush button).
(3) Evacuate the property leaving the doors and windows open.
(4) Get medical help immediately for anyone suffering the effects of Carbon Monoxide
poisoning (headache, nausea), and advise that Carbon Monoxide poisoning is suspected.
(5) Ring your gas or other fuel supplier on their emergency number. Keep the number in a
prominent place.
(6) Do not re-enter the property until the alarm has stopped. (If the alarm has been silenced
by pressing the Test/Hush button, wait at least 5 minutes. The alarm will then check that the
CO has cleared).
(7) Do not use the fuel appliances again until they have been checked by an expert. In the
case of gas appliances this must be a Registered Gas Installer.
When the CO Alarm detects abnormal levels of CO (above 50ppm CO) the red light starts to flash
and the horn will sound within 90 minutes. At higher levels of CO the alarm will turn on sooner (see
?
Table B - page 8).
The CO Alarm will automatically reset once the CO has cleared. Pressing the Test/Hush button will
silence the CO Alarm immediately (below 300ppm CO). If CO is still present the red light and horn
?
will turn on again after about 4 minutes.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 6
The CO Alarm is no substitute for keeping chimneys and flues clear and in good condition, and all of your
appliances serviced regularly according to the manufacturer’s instructions.
?
Do not fit alarm until all building work is completed to avoid contamination.
2. CARBON MONOXIDE - THE SILENT KILLER
2.1 WHAT IS CARBON MONOXIDE ?
Congratulations on becoming the owner of an Ei Carbon Monoxide Alarm. This will help protect you and
your household from the dangerous effects of Carbon Monoxide - The Silent Killer. Many are killed each
year, and many more suffer ill health from Carbon Monoxide (CO) poisoning (CO is the chemical symbol,
indicating the molecule has one carbon atom and one oxygen atom). CO is an invisible, odourless, tasteless
and extremely toxic gas. It is produced by appliances and vehicles burning fuels, such as coal, oil,
natural/bottled gas, paraffin, wood, petrol, diesel, charcoal etc. CO is absorbed by red blood cells in the
lungs in preference to oxygen - this results in rapid damage to the heart and brain from oxygen starvation.
High levels of CO in a house can be caused by:
• Incorrectly or poorly installed fuel-burning appliances.
• Blocked or cracked chimneys/flues.
• Blocked vents or draught-proofing which makes areas with fuel burning appliances or fireplaces airtight.
• Engines of cars, lawnmowers etc. left running in confined spaces.
• Portable paraffin or gas heaters in badly ventilated rooms.
2.2 SYMPTOMS OF CARBON MONOXIDE POISONING
Most people know that high levels of CO are harmful, however the period of exposure is also important.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 7
A low level for a long period (e.g. 150 ppm for 90 minutes) can cause the same symptoms (a slight
headache) as a high level of CO for a short period (e.g. 350 ppm CO for 30 minutes). Table A shows how
exposure to different concentrations of CO generally affects people.
Many cases of reported Carbon Monoxide poisoning indicate that while victims are aware they are not
well, they become so disorientated they are unable to save themselves by either leaving the building or
calling for assistance. Young children and household pets may be the first affected.
Table A: Effects of Carbon Monoxide Poisoning
Concentration
of CO in Air
Inhalation Time (approx) and Symptoms Developed
ppm
35
The maximum allowable concentration for continuous exposure in any 8 hour period according to OSHA *.
Slight headache after 1.5 hours.
150
200
400
Slight headache, fatigue, dizziness, nausea after 2-3 hours.
Frontal headaches within 1-2 hours, life threatening after 3 hours, also maximum parts per million in flue gas
(on an air free basis) according to US Environmental Protection Agency.
800
Dizziness, nausea and convulsions within 45 minutes. Unconsciousness within 2 hours. Death within 2-3 hours.
Headache, dizziness and nausea within 20 minutes. Death within 1 hour.
Headache, dizziness and nausea within 5-10 minutes. Death within 25-30 minutes.
Headache, dizziness and nausea within 1-2 minutes. Death within 10-15 minutes.
Death within 1-3 minutes.
1,600
3,200
6,400
12,800
ppm = parts per million
*OSHA = Occupational Safety & Health Association
7
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 8
2.3 WHAT HAPPENS WHEN YOUR CO ALARM DETECTS CARBON MONOXIDE ?
When the Alarm detects potentally dangerous levels of CO, it flashes the red alarm light and then sounds
a loud alarm if the CO persists. The digital display (Model Ei261DENRC only) indicates the CO level in
parts per million (ppm) CO.
Table B below shows how the CO Alarm reacts to different levels of CO gas and exposure time. At higher
levels of CO the alarm turns on sooner. The rate of flashing of the red light indicates the level of CO.
Table B: CO Alarm Response
Red
Alarm Light
Horn sounds
within
CO Level
(ppm)
0
Off *
Off
50
1 Flash / 2 Seconds
2 Flashes / Second
4 Flashes / Second
60 to 90 minutes
10 to 40 minutes
3 minutes
100
300
* unless it has been in alarm (see 2.4 CO Alarm Memory overleaf)
If your CO Alarm sounds follow the instructions on page 5.
When ventilation is provided by leaving windows and doors open, the CO build up may have
dissipated by the time help arrives and the alarm may have stopped sounding. Although your problem
may appear temporarily solved, it is crucial that the source of the CO is determined and appropriate
repairs made.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 9
NEVER IGNORE THE ALARM
Pre-Alarm: When the alarm detects over 50ppm CO the red light flashes every 2 seconds. This helps
locate CO leaks as the unit gives an indication straight away (without this feature the CO level would need
to be at 50ppm CO for 90 minutes for the horn to sound). Note the Pre-Alarm signal may be triggered by
CO coming for example, from cooking with gas, from car engines or from nearby barbecues. This is
usually not a concern unless the Pre-Alarm signal persists until the alarm sounds and the CO source is
unknown.
Note: The CO Alarm may sound if cigarette smoke is blown into it, or aerosols are released nearby.
2.4 CO ALARM MEMORY
When the Test button is pressed the horn will sound, and the red light will only flash if the unit has
previously detected CO and been in alarm. The flash rate indicates the level of CO detected as below:-
- Red light is Off – No CO detected since reset or power up.
- Red light flashes 2 times (in 2 seconds) every 40 seconds - 50 ppm CO detected for approximately
90 minutes since reset or power-up.
- Red light flashes 4 times (in 2 seconds) every 40 seconds - 100 ppm CO detected for approximately
40 minutes since reset or power-up.
- Red light flashes 8 times (in 2 seconds) every 40 seconds - 300 ppm CO detected for approximately
3 minutes.
When the Test button is held, the digital display on the Ei261DENRC model shows the previous peak
reading. This tells you if the unit has detected CO in your absence and helps to detect and locate leaks,
monitor premises etc.
Reset Memory by holding down the Test button for over 20 seconds until the red light stops flashing.
Cover the horn with a cloth to muffle the alarm during this time.
Please note that the memory will also be reset when the unit is removed from the mounting plate.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 10
3. ALARM POSITIONING
3.1 IDEALLY A CARBON MONOXIDE (CO) ALARM SHOULD BE INSTALLED IN:
- Every room containing a fuel burning appliance
- Remote rooms where occupants spend a considerable amount of time
- Every bedroom
However if the number of CO Alarms is limited, the following points should be considered when deciding
where best to fit the alarm(s)
- If there is an appliance in a room where people sleep, place a CO Alarm in this room
- Locate a CO Alarm in a room containing a flueless or open-flued appliance
- Locate a CO Alarm in a room where the occupant(s) spend most of their time (e.g. living room)
- In a bedsit, the CO Alarm should be placed as far away from the cooking appliance as possible, but
near to where the occupant sleeps
- If the appliance is in a room not normally used (such as a boiler room) the CO Alarm should be placed
just outside the room so that the alarm will be heard more easily
3.2 UNSUITABLE LOCATIONS
Do not place the CO Alarm in any of the following areas
- In the immediate vicinity of a cooking appliance
- Outside the building
10
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 11
- In an enclosed space (e.g. in or below a cupboard)
- In a damp or humid area
- Directly above a sink or cooker
- Next to a door, window, air vent or anywhere that it would be affected by draughts
- Next to an extractor fan
- Where it would be obstructed, e.g. by curtains or furniture
- In an area where the temperature could drop below –10°C or rise above 40°C
- Where dirt or dust could block the sensor
- Where it could be easily knocked or damaged, or where it could be accidentally turned off or removed
- In a bathroom or other areas where the CO Alarm may be exposed to water splashes, dripping or
condensation (e.g. above an electric kettle)
- Near paint, thinners, solvent fumes or air fresheners
3.3 IF LOCATING THE CO ALARM IN A ROOM WITH A FUEL BURNING APPLIANCE (see Figure 1)
- If it is mounted on a wall, it should be located at a height greater than the height of any door or window
but still be at least 150mm from the ceiling
- If it is mounted on the ceiling it should be at least 300mm from any wall or light fitting
- The CO alarm should be a horizontal distance of between 1m and 3m from the potential CO source
11
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 12
- If there is a partition in the room, the CO Alarm should be located on the same side of the partition as
the potential source
- In rooms with sloped ceilings, the CO Alarm should be located at the high side of the room (see Figure 3)
3.4 IF LOCATING THE CO ALARM IN A BEDROOM OR IN ROOMS REMOTE FROM A FUEL
BURNING APPLIANCE (see Figure 3)
- Mount the CO alarm relatively close to the breathing zone of the occupants
Whatever position is chosen make sure it is possible to view the three light indicators, when in the
vicinity of the alarm.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 13
300mm
CO Alarm
150mm
1 to 3 m
DEAD AIR
DON'T LOCATE
HERE
1 to 3 m
Figure 1. Location in room with a fuel burning appliance
- 1 to 3m from appliance
- Ceiling 300mm (min) from walls - Wall 150mm vertically down from ceiling
13
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 14
CO Alarm
CO Alarm
approx
1 to 2m
Figure 3. Location in bedroom & rooms
Figure 2. Location in rooms with
remote from the appliance
sloped ceilings
- 300mm from apex of ceiling
- High side of the room
- Wall mounted
- Breathing level (approx. 1 to 2m
above floor)
14
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 15
4. INSTALLATION
The Alarm is designed to be permanently
mounted, using its own built-in terminal
block to connect it to the mains wiring. The
mounting plate can be screwed directly to
the ceiling/wall. Alternatively it can be
screwed to a standard junction box (BS
4662 single gang accessory box). The alarm
requires a current of 60mA. The Alarm must
not be exposed to dripping or splashing.
There are important markings on the
underside of the alarm.
Figure 4 - Alarm Installation
LOCATION FOR
TAMPERPROOF SCREW
(see page 16)
GAS ENTRY HOLES
SIDE VIEW
IMPORTANT PRECAUTION: Do not install
the actual alarm itself in new or
renovated buildings until all work is
completed (including floor coverings)
and the building has been fully cleaned.
The wiring can be installed when
appropriate. (Excessive dust and debris
from building work can contaminate the
sensor and cause problems, it will also
invalidate the guarantee). If it must be
installed, cover it completely, particularly
MOUNTING PLATE
TAMPERPROOF CATCH
PUSH SMALL SCREWDRIVER
STRAIGHT IN TO RELEASE.
PUSH COVER AWAY FROM
SCREWDRIVER
WARNING: DISCONNECT MAINS BEFORE REMOVING ALARM FROM
around the
covering, until all cleaning is finished.
edges, with a suitable
CEILING OR WALL
15
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 16
The Alarm must not be connected when the house wiring insulation is being checked with high Voltages
i.e. do not use an insulation tester on the alarm.
Do not use the CO Alarm on an intermittent basis, or as a portable detector for the spillage of
combustion products from fuel burning appliances or chimneys.
Mains operated Alarms should be installed and interconnected by a qualified electrician in accordance
with the Requirements for Electrical Installations published by the Institution of Electrical Engineers (as
BS7671). Failure to install this Alarm correctly may expose the user to shock or fire hazards.
The Alarm must be continuously powered 24 hours a day so it is important that it is not on a circuit
that can be turned off by a switch.
INSTALLATION PROCEDURE
1. Select a location complying with the advice in the previous section (see pages 8-12).
2. Disconnect the AC mains supply from the circuit that is going to be used to power the Alarm.
3. The house wiring must be connected to the terminal block on the mounting plate as follows:
L: Live - connect to the house wires coloured brown or marked L.
N: Neutral - connect to the house wires coloured blue or marked N.
IC: Interconnect - If you are only installing one alarm do not connect any cable to the IC terminal.
See page 19 for information on interconnecting.
Warning: Mixing the Live and Neutral connections when interconnecting alarms will damage all the
alarms - ensure that the same colours are used throughout the premises for Live, Neutral and
Interconnect wires.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 17
We strongly recommend that you check for the following before connecting the alarm:
• check for Live and Neutral using a two probe tester.
• check for Live using a neon tester.
• check that the Interconnect wire is NOT connected to Live, Neutral or Earth. Do not use an Earth wire
for the Interconnect line.
Note:The Alarm does not need to be earthed. However the terminal marked is provided for the convenience
of the installer so that any copper Earth wire or cable coloured green & yellow, can be safely terminated.
4. Lift off the wiring cover as shown in Figure 5 overleaf.
5. If the mains wires are being brought along the surface, conduit can be inserted into the top and/or
bottom of the mounting plate.
(a) position the mounting plate, so that the cable conduit is as shown in Figure 5 overleaf.
(b) Carefully cut around the knockout on the outside wall so the conduit fits. (Note: to comply with
the BS EN 60529, IPX2D protection rating, seal around conduit with silicone rubber or similar to
prevent water entering).
6. If the mains wiring is recessed, bring the wiring through the rear hole in the mounting plate as shown
in Figure 6.
7. Carefully align the mounting plate and screw into place. Connect the wires to the terminal block. With
recessed wiring, ensure the rear gasket seals around the edge of the hole in the ceiling or wall. This is
to prevent air draughts affecting the CO gas entering the alarm. If the hole is not closed off by the gasket
it should be sealed with silicone rubber or equivalent.
8. Replace the wiring cover.
9. Carefully line up the unit on the base and slide on.
10. Press the Test/Hush button for 10 seconds. The horn will sound. Check that any interconnected
alarms also sound within this period.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 18
TERMINAL SCREWS
INSERT SCREWDRIVER TO LIFT
AND REMOVE WIRE COVER
WIRING
CONDUIT
L - LIVE
KNOCK OUT
FOR SURFACE WIRING
CONDUIT
N - NEUTRAL
IC - INTERCONNECT
L N IC
L N IC
WIRING
CONDUIT
SEALING GASKET
(MUST BE IN PLACE)
KNOCK OUT FOR
SURFACE WIRING
CONDUIT
MAINS WIRING
EARTH (IF PRESENT)
RECESSED WIRING AREA
Figure 5 - Surface Wiring
Figure 6 - Recessed Wiring
11. Connect the mains power to the alarm circuit. Check the green light is on.
The CO Alarm is now fully operational and will provide protection against a build up of Carbon
Monoxide gas 70 seconds after it is connected to the mains supply.
12. The unit may be tamperproofed further by removing the knockout in the sidewall of the mounting plate
(as shown in Figure 4) and inserting the self tapping screw (3mm diameter, 12mm long) after the unit
is on the mounting plate.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 19
4.1 INTERCONNECTING
With interconnected alarms, when one unit detects CO all units alarm. All horns will sound but only units
detecting CO will flash their red lights.
A maximum of twelve Ei261ENRC/261DENRC CO Alarms may be interconnected along with an
Ei128RBU & Ei128COV relay module (see “ACCESSORIES” on page 32).
Alternatively, up to twelve Ei261ENRC /Ei261DENRC CO Alarms and Ei161RC/Ei164RC/Ei166RC
Smoke/Heat Alarms may be interconnected provided an Ei1529RC Remote Control is used in the
system (see “ACCESSORIES” on page 32).
Do not connect these Alarms to any other model produced by another manufacturer, or to any
other model of Ei Alarm, apart from those listed above. Doing this may damage the Alarms and could
result in a shock or fire hazard.
The interconnect wire (minimum 0.75mm2 cable) must be treated as if it was Live. It should be insulated
and sheathed.
IC - INTERCONNECT
TO OTHER ALARMS
AS REQUIRED
(see list above)
N - NEUTRAL
L - LIVE
MAINS
POWER
L
N
IC
L
N
IC
Figure 7 - Interconnect Wiring Diagram
19
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 20
A maximum of 250 metres (820 ft) of wire can be used (maximum resistance between detectors 50
Ohms). Connect as shown in Figure 7.
Alarms should be interconnected only within the confines of a single family living unit. If they are
connected between different units there may be excessive nuisance alarms. Everybody may not be
aware that they are being tested etc.
If interconnected CO and Smoke/Heat Alarms are all sounding, the LOCATE switch on the Ei1529RC
Remote Control should be pressed. This will just leave the alarm that triggered the system sounding.
This is very important to determine because the actions to take in each situation are very different.
In the case of CO the premises should be fully ventilated by opening doors and windows.The user should
call the gas supplier etc.
In the case of fire, doors and windows should be closed to slow the spread of fire. The user should call
the fire brigade etc.
5. TESTING
1. Regularly check that the green mains power light is on. The unit cannot detect CO if the mains power is
off and the rechargeable battery back-up is depleted. (If it is off check circuit breakers, fuses, wiring etc).
2. Test the unit weekly by pressing the Test/Hush button. Hold the Test button (for up to 10 seconds) until
the horn sounds for over 5 seconds. This will help to familiarise you and your family with the distinctive
on-off sound of the CO Alarm.This test checks that the electronics and horn are working correctly. If units
are interconnected, button test each unit in turn and check all interconnected units alarm. (If the red alarm
light flashes when the button is pressed, see 2.4 “CO ALARM MEMORY” on page 9). Alternatively, if an
Ei1529RC Remote Control is in the system the unit can be tested by pressing the Test switch on the
Ei1529RC. This is equivalent to pressing the Test button on the Alarm. For further information see
“ACCESSORIES” on page 32.
3. If the Alarm gives a short beep and the amber fault light flashes every 40 seconds it means the self-
20
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 21
checking circuit has detected a fault. Press and hold the Test/Hush button. If the amber light flashes
without the horn sounding, the sensor is faulty. On the Ei261DENRC the display will show SF indicating
Sensor Faulty.
4. If the Alarm fails to operate when the Test/Hush button is pressed, switch off the mains supply at the
distribution fuse board and remove unit from mounting plate for 3 minutes. Put unit back on mounting
plate. Reconnect the mains and test again. (This procedure resets the microprocessor in the unit).
5. If the unit beeps every 40 seconds (without a light flash) it means the battery is depleted. (On the
Ei261DENRC with depleted cells, the display will show CP to remind you to Connect mains Power).
Connect mains power (ensure green light is on) to allow cells to charge.
6. Once a year check the rechargeable battery by switching off the mains supply and pressing the Test
/Hush button for 10 seconds. The horn should sound loudly. Reconnect the mains supply.
If the CO Alarm fails any of the above tests it must be replaced immediately (see 9 “GETTING YOUR CO
ALARM SERVICED” on page 27).
TESTING WITH CARBON MONOXIDE
The unit checks for CO every 4 seconds and as soon as it detects CO, it flashes the red light (as per
Table B on page 8) to confirm that is detecting CO gas.
Alternatively:
Pressing the Test/Hush button causes the unit to check for CO - this is the Fast COTest Mode.This eliminates
the long wait normally required (e.g. up to 90 minutes at 55ppm CO and up to 3 minutes at 330ppm CO).
The unit can be tested with CO by using one of the kits that comes with CO either in a glass phial or
aerosol can. Follow the instructions on the kit but be sure to press the Test/Hush button to speed up the
CO sampling directly after you expose the unit to the CO. It is best if possible to inject the CO gas into
the gas entry holes (see Figure 1). When it senses the CO it will give 3 beeps and the red light will flash
as per Table B. It then automatically resets to normal mode. (If unit fails to respond, press the Test/Hush
button again as gas can take some seconds to enter sensor).
21
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 22
The Fast CO Test Mode normally does not activate the memory function unless a high level of CO
remains in the sensor for a few minutes. (This can be checked by pressing the Test/Hush button. If the
red light flashes continuously (indicating CO was detected), hold the Test/Hush button for 20 seconds
until the red light stops flashing as the memory resets).
6. HOW TO DISTINGUISH BETWEEN CO ALARM & SMOKE ALARM WARNINGS
The CO Alarm has a distinctive on-off sound of 3 pulses followed by a pause, as compared with a typical
Smoke/Heat Alarm which has a rapid pulsing sound.
In addition, when your CO Alarm is sounding, the red alarm light on the cover will be flashing.
Testing both your CO Alarms and Smoke/Heat Alarms weekly will help you and your family to clearly
distinguish between them in an emergency.
If CO Alarms and Smoke/Heat Alarms are interconnected (and are all sounding), press the LOCATE
switch on the Ei1529RC Remote Control to leave just the alarm that has triggered the system sounding.
7. MAINTENANCE
Clean the outside case by occasionally wiping with a clean damp cloth (disconnect the mains supply at
the distribution/fuse board first). Do not use any cleaning agents, bleaches, detergents or polishes,
including those in aerosol cans. Avoid spraying air fresheners, hair spray, paint or other aerosols near the
CO Alarm. Do not place air fresheners near the unit.
Use the narrow nozzle of a vacuum cleaner to remove dust and other contamination from the gas entry
holes in the cover of the Alarm to ensure CO gas can reach the sensor.
Do not paint the CO Alarm.
Remove the CO Alarm when decorating. Do not allow water or dust to contaminate the alarm.
Do not open or tamper with the CO Alarm.This can damage the unit and may expose the user to shock
or fire hazards. There are no user serviceable parts inside apart from the sensor module - see overleaf.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 23
HOW TO DISCONNECT AND REMOVE THE ALARM:
(1) Disconnect the mains supply to the CO Alarm circuit at the distribution/fuse board.
(2) Remove tamperproofing screw if fitted (see Figure 1).
(3) Release catch (as shown in Figure 1) and slide unit off mounting plate.
SENSOR MODULE REPLACEMENT
Replace the sensor module after 5 years operation (or by the date on the ‘REPLACE SENSOR BY’
label on the side of the unit). After 5 years operation, the amber light will flash once every 40 seconds
(without a beep) to indicate the sensor should be replaced.
It must also be replaced if the amber light flashes and the unit beeps every 40 seconds as this indicates
the sensor is faulty.
(1) Remove the alarm from the mounting plate as described previously.
(2) Pull out the sensor module from the rear.
(3) Replace with a new sensor module (Model No. Ei261MEN - Contact Aico or Ei Electronics, for your
nearest module supplier).
(4) Carefully align the module including the connector pins and push firmly home.
(5) Remove the ‘REPLACE SENSOR BY’ label on the side of the alarm.
(6) Slide the alarm back on to the mounting plate.
(7) Reconnect the mains supply.
(8) Wait 4 minutes for the new sensor to stabilise and then press the Test/Hush button - the horn should
sound.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 24
Note: When the second sensor has completed its 5 years of operation the amber light will flash every 40
seconds.The sensor module can only be replaced once. The entire unit must be replaced after 10 years.
The date for replacing the entire unit is given on the ‘REPLACE UNIT BY’ label on the alarm.
8. LIMITATIONS OF CO ALARMS
- The Ei261EN/261DEN CO Alarm will not work without mains power if the rechargeable cells are
depleted. The green power light indicates that the Alarm is receiving mains power.
- Carbon Monoxide must enter the unit for it to be detected. There may be Carbon Monoxide in other
areas of the house (e.g. downstairs, in a closed room etc) but not in the vicinity of the CO Alarm. Doors,
air draughts and obstructions can prevent the CO from reaching the Alarm. For these reasons we
recommend CO Alarms are fitted both near and in bedrooms, particularly if bedroom doors are closed
at night. Additionally install in rooms where members of the household spend much of their time, and in
rooms with potential sources of CO gas.
- The CO Alarm may not be heard. The sound output is loud but it may not be heard behind a closed door
or if it is too far away. Interconnecting CO Alarms greatly improves the probability that they will be heard.
The Alarm may not wake up somebody who has taken alcohol or drugs.The alarm sound may be masked
by other sounds such as T.V., stereo, traffic noise etc. Fitting CO Alarms on either side of closed doors will
improve their chance of being heard. This CO Alarm is not designed for people with impaired hearing.
- CO Alarms don’t last indefinitely. CO Alarms are sophisticated electronic devices with many parts.
Although the alarm and its component parts have undergone stringent tests and are designed to be very
reliable, it is possible that parts can fail. Therefore, you should test your CO Alarm weekly. The CO Alarm
sensor must be replaced after 5 years operation. The complete unit must be replaced after 10 years.
- CO Alarms are not a substitute for life insurance. House-holders are responsible for their own
insurance. The CO Alarm warns of increasing CO levels, but we do not guarantee that this will protect
everyone from CO poisoning.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 25
- CO Alarms are not suitable as early warning Smoke Alarms. Some fires produce Carbon Monoxide, but
the response characteristics of these CO Alarms are such that they would not give sufficient warning
of fire. Smoke Alarms must be fitted to give early warning of fire.
- This CO Alarm does not detect the presence of natural gas (methane), bottled gas (propane, butane) or
other combustible gases. Fit combustion gas alarms to detect these.
WARNING: THIS CO ALARM IS DESIGNED TO PROTECT INDIVIDUALS FROM THE ACUTE
EFFECTS OF CARBON MONOXIDE EXPOSURE. IT WILL NOT FULLY SAFEGUARD INDIVIDUALS
WITH SPECIFIC MEDICAL CONDITIONS. IF IN DOUBT CONSULT A MEDICAL PRACTITIONER.
9. HOW TO PROTECT YOUR FAMILY
Follow these guidelines to reduce the risk of Carbon Monoxide poisoning.
- Know and look out for tell-tale signs that Carbon Monoxide may be present. These include:-
- The CO Alarm warning of abnormal levels.
- Staining, sooting or discolouration on or around appliances.
- A pilot light frequently going out.
- A naked gas flame which is yellow or orange, instead of the normal blue.
- Family members (including pets) exhibiting the “flu-like” symptoms of CO poisoning (described
in Table B on page 8).
If any of these signs are present get the appliance checked out by an expert before further use. If
family members are ill, get medical help.
- Choose all appliances and vehicles which burn fossil fuels such as coal, oil, natural/bottled gas, paraffin,
wood, petrol, diesel, charcoal etc. with care and have them professionally installed and regularly
maintained.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 26
- These appliances must “breathe in” air to burn the fuel properly. Know where the air comes from and
ensure vents/air bricks etc. remain unobstructed (particularly after building work).
- The appliances must also “breathe out” the waste gases (including the CO) – usually through a flue or
chimney. Ensure chimneys and flues are not blocked or leaking, and get them checked every year.
Check for excessive rust or cracks on appliances and pipe work.
- Never leave your car, motor bike or lawnmower engine running in the garage with the garage door
closed. Never leave the door from the house to the garage open if the car is running.
- Never adjust your own gas pilot lights.
- Never use a gas cooker or a barbecue for home heating.
- Children should be warned of the dangers of CO poisoning and instructed never to touch, or interfere
with the CO Alarm. Do not allow small children to press the Test/Hush button as they could be subjected
to excessive noise when the unit alarms.
- Leaving windows or doors slightly open (even a few inches) will significantly reduce the risk of high
levels of CO occurring. The high levels of draught-proofing in modern houses reduces ventilation and
can allow dangerous gases to build up.
- Install CO Alarms in all the areas recommended in this leaflet.
- Recognise that CO poisoning may be the cause when family members suffer from “flu-like” symptoms
when at home but feel better when they are away for extended periods.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 27
10. GETTING YOUR CO ALARM SERVICED
If your CO Alarm fails to work after you have carefully read all the instructions, checked the unit has been
installed correctly, and is receiving AC power, return it for repair or replacement. (Do not attach to
mounting plate as unit can give beeps or alarm if the Test/Hush button is pressed during shipping). It
should be returned in a padded box to “Customer Assistance and Information” at the nearest address
given on the back page. State the nature of the fault, where the CO Alarm was purchased, and the date
of purchase.
11. FIVE YEAR GUARANTEE
Ei Electronics guarantees this Carbon Monoxide Alarm for five years from the date of purchase against
any defects that are due to faulty materials or workmanship. This guarantee only applies to normal
conditions of use and service, and does not include damage resulting from accident, neglect, misuse,
unauthorised dismantling, or contamination howsoever caused. This guarantee excludes incidental and
consequential damage. If this Carbon Monoxide Alarm should become defective within the guarantee
period, it must be returned to the nearest address given on the back page, carefully packaged, with the
problem clearly stated (see 9 “GETTING YOUR CO ALARM SERVICED”) along with proof of the date of
purchase. We shall at our discretion repair or replace the faulty unit.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 28
12. TECHNICAL SPECIFICATIONS
Operating Voltage
Power
: 230±10% VAC, 50Hz
: 1 Watt (60 mA)
Power on Indicator
: Green Light
Sensor
: Electrochemical Sensor
CO Sensitivity
: Meets BS EN 50291: 2001.
Unit operates as per Table B (on page 8).
Electrical Safety
: Complies with relevant sections of EN 60335-1: 1994
: Complies with BS EN 50270
Electromagnetic
Compatibility
Test/Hush Button
: Checks electronics and horn.
When the unit is alarming, after sensing CO, pressing the Test/Hush button will immediately stop
the horn (the red light will continue to flash). If CO is still present the red light and the horn will turn
on again after about 4 minutes. The unit can only be silenced once during a CO incident. At 300
ppm CO the unit cannot be silenced. (With interconnected units, the Hush only works on the alarm
sensing CO).
Fast CO Test Mode
: Pressing the Test/Hush button also causes the unit to check for CO 4
seconds later to facilitate testing in CO gas. It gives 3 beeps and the red light
flashes to indicate the CO level if CO is sensed and then resets.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 29
Initialisation Time
: 70 seconds. On power up red and amber lights flash momentarily to show
they are operational.
Operating
: -10°C to 40°C
Temperature
Humidity Range
Audible Alarm
Self Diagnostics
Tamperproof
: 15% to 95% R.H. (non-condensing)
: 85dB(A) minimum @ 3m
: Horn beep and amber fault light flashes every 40 seconds if a sensor fault is found.
: Screwdriver needed to release from mounting plate. Additionally a tamper-
proofing screw can be fitted to the mounting plate.
Rechargeable
Lithium Cells:
: Fully charged cells can power unit in standby for over 4 weeks and without
mains power, it can power the unit in alarm for over 2 hours. The unit beeps
every 40 seconds if cells are depleted.
Interconnect
: Up to 12 Ei261ENRC/261DENRC CO Alarms can be interconnected, so
that when one senses CO, all alarm. Alternatively, up to 12 Ei261ENRC/
Ei261DENRC CO Alarms and Ei161RC/Ei164RC/Ei166RC Smoke/Heat
Alarms can be interconnected provided that an Ei1529RC Remote Control
is used.
Relay Module Ei128RBU : This can be connected using the interconnect line.
with Ei128COV (optional)
29
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 30
CO Alarm Memory:
: A unit will indicate if it has been in alarm previously by flashing the red light
for 2 seconds every 40 seconds (2 flashes for 50 ppm CO, 4 flashes for 100
ppm CO and 8 flashes, for 300 ppm CO). When the Test/Hush button is
pressed, the red light flashes (as per Table B on page 8) to indicate the
previous CO alarm level detected. The memory is cleared by holding down
the Test/Hush button until the red light stops flashing.
Digital Display
: Range 50 - 300ppm CO
(Ei261DENRC only)
Resolution 5 ppm CO
With low rechargeable cells - CP
With sensor faulty - SF
With Test/Hush button pressed - previous peak CO level
Dimensions
Weight
: 126 x 150 x 42 mm.
: 330g.
13. TROUBLESHOOTING
1. ALARM DOES NOT WORK WHEN THE TEST BUTTON IS PRESSED:
- Check that the green mains power light is on. If it is off check the wiring, fuse, circuit breakers etc.
- Hold the Test/Hush button down for at least 5 seconds.
2. ALARM BEEPS AND AMBER LIGHT FLASHES EVERY 40 SECONDS:
- If the alarm beeps and the amber fault light flashes every 40 seconds, the CO sensor is probably
defective.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 31
- Press the Test/Hush button for approximately 20 seconds to reset the unit. If the beeping and the amber
light flashing re-occurs replace the sensor module.
3. ALARM BEEPS EVERY 40 SECONDS (without amber light flashing):
- Rechargeable cells depleted. Reconnect mains power if green light is off.
4. ALARM SOUNDS FOR NO APPARENT REASON:
Follow the detailed instructions in Section 1 on page 5 entitled “WHAT TO DO WHEN THE ALARM
SOUNDS”. If there are still problems:
-
-
-
-
Ensure there are no fuel-burning appliances in the vicinity which could be leaking CO gas (e.g. even
from next door).
Ensure there are no fumes in the area (e.g. paint, thinners, alcohol, hair spray, chemical cleaners
aerosol sprays etc).
Ensure there is no outdoor source of CO in the vicinity (e.g. a car with engine running, heavy traffic,
heavy air pollution, barbecue fumes etc).
Press the Test/Hush button to silence the alarm.
If the unit continues to sound it is possibly defective and should be replaced. Follow the instructions in
Section 9 “GETTING YOUR CO ALARM SERVICED”.
4. Test/Hush BUTTON DOES NOT SILENCE ALARMS:
If there are a number of alarms interconnected and they are all sounding, pressing the Test/Hush button
on the unit sensing CO (i.e. the one with the red light flashing) will silence the system. Pressing any other
Test/Hush button will not silence the alarms. The Test/Hush button will only silence the unit once at CO
levels less than 300 ppm CO during a CO incident.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 32
Alternatively, if an optional Ei1529RC Remote Control is fitted, pressing the LOCATE switch when all
alarms are sounding will silence all alarms apart from the alarm that is sensing CO/Smoke/Heat.
This area can then be safely investigated and if determined that it is a false alarm, press the HUSH switch
to silence the alarm.
14. ACCESSORIES
Ei1529RC Remote Control
The Ei1529RC is strongly advised for systems with interconnected CO and
Smoke/Heat Alarms.
It allows the user to perform the following functions from a remote location.
Locate
- When system sounds press Locate to allow the source of
alarm to be identified
Hush
Test
- Press Hush to silence nuisance alarms
- Operate weekly to Test the alarm system
- Test will not work with mains absent
Mains
Check
Ei128RBU Relay Module with Ei128COV Cover
The Ei128RBU module has a relay rated at 230VAC / 5Amps. It is mains
powered with rechargeable battery back-up. It can be used for remote
signalling and activating gas shut-off valves, strobes etc.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 33
The crossed out wheelie bin symbol that is on your
product indicates that this product should not be disposed
of via the normal household waste stream. Proper
disposal will prevent possible harm to the environment or
to human health. When disposing of this product please
separate it from other waste streams to ensure that it can
be recycled in an environmentally sound manner. For
more details on collection and proper disposal, please
contact your local government office or the retailer where
you purchased this product.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 34
Aico Ltd
Mile End Business Park, Maesbury Rd,
Oswestry, Shropshire SY10 8NN, U.K.
Tel: 0870 758 4000
Ei Electronics
Shannon, Co Clare, Ireland.
Tel: +353 (0)61 471277
© Ei Electronics 2007
P/N B16132 Rev 0
Download from Www.Somanuals.com. All Manuals Search And Download.
|