AMX Network Card RDM HDC User Manual

Installation Sheet  
RDM-HDC Heavy Duty DC Module  
2400 W, 0-12 VDC  
The RDM-HDC Heavy Duty DC Module is a heavy-duty 2400 W module for  
dimming of fluorescent ballast loads. It uses a 0 to 12 VDC current sinking  
or sourcing for use with all four-wire ballasts. It is designed for use with the  
RDA series of enclosures, in an AMX Lighting™ modular digital dimming  
system. The module’s 120, 240, and 277 VAC ratings are CE, UL, and  
C-UL approved.  
Caution: Pre-Installation Notes  
All Class 1 wiring must be connected to proper terminals.  
All control wiring must be connected to proper terminals.  
Disconnect power while installing or connecting the unit.  
Keep top and bottom air vents clear at all times.  
Use low-voltage wires with a 300 volt rating or greater.  
Use field installed copper conductors.  
All electrical ratings are for continuous duty.  
For indoor use only.  
Test loads for shorts before connecting.  
Mounting  
points  
This module may require extra power from the AXlink connection or an  
external power supply connected to the control card.  
Connecting the RDM-HDC to the AMX Lighting Master  
Pin 4 (GND)  
Neutral  
High  
Pin 3 (RLY)  
Pin 2 (DIM)  
voltage  
Line in  
Pin 1 (+12 V)  
- out (LV)  
+ out (LV)  
Load  
Low-voltage  
RDM-HDC 4-pin module connector  
GND  
3 (-)  
2 (DIM)  
1 (+)  
4-pin plug from RDM series module  
Note: The 4-pin plugs from the module connector to the 4-pin  
connector on the master (black plug cover facing up).  
Relay  
FIG. 2 Connecting the RDM-HDC and AMX Lighting Master  
Lighting Application Drawings  
Florescent Ballast  
-
Neutral  
Line in (HOT)  
Ballast  
+
Low-voltage control  
wiring: 4-pin  
connector to AMX  
Lighting master  
controller  
Load  
Neutral  
RDM-HDC  
LOAD LINE NEUT  
CON  
Low-voltage wire rated  
to 300 V  
FIG. 1 RDM-HDC  
Circuit breaker  
panel  
RDM-HDC UL and C-UL Ratings  
120 VAC, 50/60 Hz, 2400 W  
240/277 VAC, 50/60 Hz, 2400 W  
Control Out: 50 mA, 12 VDC  
sourcing/sinking  
FIG. 3 RDM-HDC application wiring  
Warning: Failure to ground the ballast may cause ballast  
failure  
Suggested Dimmed Loads  
Four-wire dimmable ballasts  
All low-voltage DC controlled ballasts  
Specifications  
Dimensions (HW): 10" x 2.75" (25.4 cm x 6.99 cm)  
Non-phase dependant  
Use wires rated at 75°C (167°F)  
Torque terminals to 20 in-lbs. (2.3 N/M)  
Max. wire size: 10 AWG (4 mm²)  
Wire stripping length: 0.28" (7 mm)  
Weight: 1.3 lbs. (0.590 kg)  
BTU/hr: 150  
Control current: 150 mA @ 12 VDC  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Acer Computer Monitor M190E5 L0A User Manual
AEG Refrigerator 2842 6 I User Manual
AG Neovo Universal Remote TSC 40 IC User Manual
AKG Acoustics Headphones K 105 UHF User Manual
Alamo Lawn Mower 02986950P User Manual
Audiovox Remote Starter APD 510 User Manual
Axis Communications Digital Camera AXIS 212 PTZ User Manual
Axis Communications Security Camera AXIS Q6000 E User Manual
Barco Camera Lens R9840000 User Manual
Beckett Water Gardening Outdoor Fountain LT20 User Manual