ADT Security Services Home Security System 50075 User Manual

®
Security  
Systems  
UNI•COM  
Universal Digital Alarm Communicator/Transmitter  
for the Unimode Series Fire Alarm Systems  
Product Information, Installation,  
Programming and Operation Manual  
Document # 50075 B  
3/13/95  
Rev:  
ECN 95-107  
P/N 50075:B  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NFPA Standards, UL Documents  
5
1.0  
1.1  
Product Description  
Product Features  
6
6
Figure 1-1: UNI•COM Assembly  
Controls and Indicators  
Figure 1-2: Controls and Indicators  
Compatible Panels  
Digital Communicator  
Circuits  
7
8
8
8
8
9
9
10  
10  
10  
10  
10  
11  
12  
12  
12  
12  
12  
12  
12  
12  
12  
12  
12  
1.2  
1.3  
1.4  
1.5  
1.6  
1.7  
1.8  
Optional Device  
Specifications  
Telephone Requirements and Warnings  
1.8.1 Telephone Circuitry  
1.8.2 Digital Communicator  
1.8.3 Telephone Company Rights and Warnings  
1.8.4 For Canadian Applications  
Modes and Special Functions  
1.9.1 Normal Mode  
1.9.2 Serviceman Code  
1.9.3 Program Mode  
1.9.4 Walktest Mode  
1.9.5 Troubleshoot Mode  
1.9.6 Type Mode  
1.9.7 Clear Function  
1.9.8 Manual Test Function  
1.9.9 Lamp Test Mode  
1.9.10 User Code  
1.9  
2.0  
2.1  
2.3  
Installation & Wiring  
General  
Output Circuits  
Figure 2-1: Wiring Phone Jacks  
Figure 2-2: Relay Driver Connections  
Figure 2-3: Monitoring for UNI•COM Trouble  
UL Power-limited Wiring Requirements  
Figure 2-4: Typical Wiring for UL Power-limiting  
13  
13  
13  
13  
14  
15  
16  
16  
2.4  
3.0  
3.1  
3.2  
Programming Instructions  
Entering Program Mode  
Switch Functions  
17  
17  
18  
18  
Figure 3-1: UNI•COM Keypad  
3
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.3  
Programming Options  
18  
20  
23  
24  
Table 3-1: Start and End Monitoring Address  
Table 3-2: Event Codes, Primary Number  
Table 3-3: Event Codes, Primary Number  
4.0  
4.1  
Operating Instructions  
Normal Mode  
4.1.1 Keys  
25  
25  
25  
26  
27  
27  
29  
31  
32  
33  
33  
34  
4.1.2 Displays  
Figure 4-1: UNI•COM Phone Connectors & LEDs  
4.1.3 Normal Mode Operation  
4.1.4 Key Report Descriptions  
Walktest Mode  
Type Mode  
Troubleshoot Mode  
4.2  
4.3  
4.4  
Figure 4-2: Handset/Speaker Connection  
Lamp Test Mode  
4.5  
5.0  
6.0  
Compatible Receivers  
35  
36  
42  
Programming Reference Sheets  
Appendix A: Point Assignments - Unimode 200  
Appendix B: Zone Assignments - Unimode 4-16 43  
Appendix C: Zone Assignments - Unimode II  
Appendix D: Unimode 200  
44  
45  
47  
49  
Appendix E: Unimode 4-16  
Appendix F: Unimode II  
4
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This digital communicator has been designed to comply with standards set forth by the following  
regulatory agencies:  
Underwriters Laboratories Standard UL 864  
NFPA Standards 72-1993 Local, Remote Station and Central Station Fire Alarm Systems  
• CAN/ULC - S527-M87 Standard for Control Units for Fire Alarm Systems  
Before proceeding, the installer should be familiar with the following documents.  
NFPA Standards, NFPA 72-1993 National Fire Alarm Code:  
• Central Station Fire Alarm Systems (Automatic, Manual and Waterflow) Protected Premises Unit.  
• Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems.  
• Proprietary Fire Alarm Systems (Protected Premises Unit).  
• Automatic Fire Detectors  
• Installation, Maintenance, and Use of Notification Appliances for Fire Alarm Systems  
• Inspection, Testing and Maintenance for Fire Alarm Systems  
Underwriters Laboratories Documents:  
UL 38 Manually Actuated Signaling Boxes  
UL 217 Smoke Detectors, Single and Multiple Station  
UL 228 Door Closers—Holders for Fire Protective Signaling Systems  
UL 268 Smoke Detectors for Fire Protective Signaling Systems  
UL 268A Smoke Detectors for Duct Applications  
UL 346 Waterflow Indicators for Fire Protective Signaling Systems  
UL 464 Audible Signaling Appliances  
UL 521 Heat Detectors for Fire Protective Signaling Systems  
UL 864 Standard for Control Units for Fire Protective Signaling Systems  
UL 1481 Power Supplies for Fire Protective Signaling Systems  
UL 1638 Visual Signaling Appliances  
CAN/ULC - S524-M91 Standard for Installation of Fire Alarm Systems  
Other:  
NEC Article 300 Wiring Methods  
NEC Article 760 Fire Protective Signaling Systems  
Applicable Local and State Building Codes  
Requirements of the Local Authority Having Jurisdiction  
5
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.0 Product Description  
The UNI•COM Universal Digital Alarm Communicator/Transmitter may be used with compatible (refer to  
Appendices) ADT fire alarm control panels (FACPs). The UNI•COM transmits system status to the UCS (Universal  
Communication System) via the public switched telephone network. The UNI•COM is compact in size and may be  
mounted inside selected host control panels or mounted externally in a separate ADT-ABS8RF or ADT-UBS1F  
enclosure. EIA-485 annunciator communications bus and 24 volt (nominal) connections are required.  
1.1 Product Features  
Dual telephone lines  
Dual telephone line voltage detect  
Surface mount technology  
Compact in size: 6.75" x 4.25"  
Built-in programmer  
Built-in four character red 7-segment LED display  
Manual test report function  
Manual master transmission clear function  
Optional Zone/Point disable  
Mounts either inside selected control panels or in  
separate ADT-ABS8RF or ADT-UBS1F enclosure  
Optional Dead Front Cover (ADT-DPUBS1F)  
Communicates vital system status including:  
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
Independent zone/point alarm  
Independent zone/point trouble  
Independent zone/point supervisory  
Serviceman on premises  
Optional Walktest data transmission (Unimode 200 only)  
AC (mains) power loss (programmable)  
Low battery  
System off normal  
12 or 24 hour test signal  
Abnormal test signal per new UL requirements  
Annunciation of UNI•COM troubles including: loss of phone  
lines, communication failure with either central station, total  
communication failure  
ADT-UBS1F  
• Troubleshoot mode converts keypad to DTMF touchpad  
• Individual LEDs for:  
ü
ü
ü
ü
ü
ü
ü
ü
Power  
EIA-485 loss  
Manual Test  
Kissoff  
Comm Fail  
Primary Line Seize  
Secondary Line Seize  
Modem  
• Open collector relay driver for Total Communication Failure or  
UNI•COM trouble.  
• Real Time Clock  
Optional ADT-DPUBS1F  
• Extensive transient protection  
• Simple EIA-485 interface to host panel  
6
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Primary  
Secondary  
Phone Line  
Phone Line  
Modular Cables  
P/N MCBL-7  
(Order Separately)  
Make No Connection  
Comm Fail Output  
(power-limited)  
24 VDC Power in  
(use power-limited  
source)  
24 VDC  
(power-limited)  
EIA-485 Connector  
(use power-limited  
source)  
Connector  
on back of  
board  
Figure 1-1: UNI•COM Assembly  
7
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Front Panel Switches  
CLEAR  
TEST  
MODE  
Up Arrow  
Down Arrow  
1st EVENT  
ENTER/STORE  
1.2  
Controls and  
Indicators  
Digits 0-9  
A
B
C
D
E
F
Displays  
• EIA-485 - yellow LED  
• COMM. FAIL - yellow LED  
• KISS OFF - green LED  
• POWER - green LED  
• Four, Seven Segment Displays -  
red  
• Primary Phone Line Active - red  
LED  
• Secondary Phone Line Active - red  
LED  
• TEST - green LED  
• MODEM - green LED  
Figure 1-2: Controls and Indicators  
The UNI•COM has been designed to be compatible with a variety of ADT fire alarm  
control panels (refer to Appendices).  
1.3  
1.4  
Compatible  
Panels  
Two modular phone jacks allow easy connection to telephone lines. Modular jacks  
are labeled PH1 and PH2 for the Primary and Secondary phone lines. Telephone line  
'Primary and Secondary Active' red LEDs are provided as well as a green 'Kissoff'  
LED. The integral digital communicator provides the following functions:  
Digital  
Communicator  
• Line Seizure - takes control of the phone lines disconnecting any premises  
phones.  
• Off/On Hook - perform on and off-hook status to the phone lines.  
• Listen for dial tone - 440 hertz tone typical in most networks.  
• Dialing the central station(s) number - default is Touch-Tone®, programmable  
to rotary.  
• Discern proper synchronization with UCS receiver.  
• Transmit data to UCS receiver.  
• Verify data has been accepted by the UCS receiver.  
• Hang up and release phone lines.  
• Communicate in the ADT FSK II format (refer to Section 5.0 for compatible  
receivers):  
8
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The UNI•COM circuit board contains a CPU, other primary components and wiring  
interface connectors.  
1.5  
Circuits  
1.5.1 Power Requirements  
Operating voltage for the UNI•COM must be power-limited, filtered, nonresettable  
21.2 to 28.2 volts. The 24 VDC nominal operating power must be supplied by the  
Control Panel and is connected to TB1 of the UNI•COM.  
Note: If the UNI•COM is installed in a Unimode 200 Control Panel, power is  
provided directly through UNI•COM connector J10 which plugs into the Unimode  
200 main circuit board.  
1.5.2 Communications  
Communications between the UNI•COM and the host control panel is accomplished  
over a two wire EIA-485 serial interface which is power-limited and supervised by  
the control panel and the UNI•COM. The wiring connections are made to the RS+,  
RS- and Shield terminals of TB1 on the UNI•COM.  
The EIA-485 circuit cannot be T-Tapped and must be wired in a continuous fashion  
from the control panel to the UNI•COM and, if installed, an annunciator. The wire  
must be 12AWG to 18AWG twisted shielded pair cable with a Characteristic  
Impedance of 120 Ohms, +/-20%. Limit the total wire resistance to 100 Ohms on the  
EIA-485 circuit. Do not run cable adjacent to, or in the same conduit as 120 volts  
AC service, noisy electrical circuits that are powering mechanical bells or horns,  
audio circuits above 25 voltsRMS, motor control circuits, or SCR power circuits.  
Note: If the UNI•COM is installed in a Unimode 200 Control Panel, the EIA-485  
data line is connected directly through UNI•COM connector J10 which plugs into  
the Unimode 200 main circuit board.  
1.5.3 Primary and Secondary Phone Lines - Modular jacks are used to interface  
the primary and secondary phone lines to the public telephone network.  
1.5.4 Communicator Fail Relay Driver - Relay driver output for central station  
communication failure is available.  
1.5.5 Earth Ground - Connect a separate earth ground wire to TB3 terminal 1 for  
transient protection. When mounted in the Unimode 200, the UNI•COM receives an  
earth ground connection via a metal standoff located on the upper right corner  
mounting position.  
Future use.  
1.6 Optional Device  
9
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DC Power - TB1, Terminals 1 & 2  
1.7  
Specifications  
24 VDC (nominal) filtered, non-resettable and power-limited. Voltage range is 21.2  
to 28.2 volts. DC Power TB1 Terminals 1 (+), 2 (-) 40 mA in standby, 75 mA max.  
while communicating (for installation in the Unimode 200 enclosure use connector  
J10) and 100 mA with the open collector output engaged and communicating.  
Data Communications - TB1, Terminals 3 - 7  
EIA-485 serial interface, TB1 Terminal 3 = RS+, 4 = RS-, 5= Shield, 6 = Future use,  
7 = Future use. Power-limited source must be used. (For installation in the Unimode  
200 use connector J10).  
Auxiliary Output - TB3, Terminals 2 & 3  
TB3-2 = Communicator Failure. Power-limited circuit. An Open Collector type  
output, normally high, active low which sinks up to 40 mA. TB3-3 = 21.2 to 28.2  
volts, power-limited. Use UL listed relay P/N: MR-101/C or MR-201/C with this  
output.  
Earth Ground - TB3, Terminal 1  
TB3-1 = Earth Ground connection. Connect this terminal to building earth ground  
using solid 12 AWG wire to provide lightning protection. This connection is not  
required when the UNI•COM is mounted in a Unimode 200 since the metal standoff  
used in mounting provides an earth ground connection.  
1.8.1  
Telephone Circuitry - PH1 & PH2  
Ringer Equivalence Number (REN) = 0.6B  
AC Impedance 10.0 Mega Ohm  
1.8  
Telephone  
Requirements  
and Warnings  
Complies with FCC Part 68  
Mates with RJ31X Male Connector  
Supervision Threshold: less than 4.0 volts for 2 minutes  
The REN is used to determine the quantity of devices which may be connected to the  
telephone line. Excessive REN's on the telephone line may result in the devices not  
ringing in response to an incoming call. In most, but not all areas, the sum of the  
REN's should not exceed five (5.0). To be certain of the number of devices that may  
be connected to the line, as determined by the total REN's, contact the telephone  
company to determine the maximum REN for the calling area.  
1.8.2  
Digital Communicator:  
Before connecting the UNI•COM to the public switched telephone network, the  
installation of two RJ31X jacks is necessary. The following information is provided  
if required by the local telephone company :  
Manufacturer : Fire·Lite Alarms Inc.  
12 Clintonville Rd.  
Northford, CT 06472  
Product Model Number: UNI•COM  
FCC Registration Number: 1W6USA-20723-AL-E  
Ringer Equivalence 0.6B  
1.8.3  
Telephone Company Rights and Warnings:  
The telephone company under certain circumstances may temporarily discontinue  
services and/or make changes in its facilities, services, equipment or procedures  
which may affect the operation of this control panel. However, the telephone  
company is required to give advance notice of such changes or interruptions.  
10  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the control panel causes harm to the telephone network, the telephone company  
reserves the right to temporarily discontinue service. Advance notification will be  
provided except in cases when advance notice is not practical. In such cases,  
notification will be provided as soon as possible. The opportunity will be given to  
correct any problems and to file a complaint.  
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START,  
OR PARTY LINE SERVICES.  
When the control panel activates, premise phones will be disconnected.  
Two separate phone lines are required. Do not connect both telephone interfaces to  
the same telephone line.  
The control panel must be connected to the public switched telephone network  
upstream of any private telephone system at the protected premises.  
An FCC compliant telephone cord must be used with this equipment. This equipment  
is designed to be connected to the telephone network or premises wiring using a  
compatible RJ31X male modular plug which is Part 68 compliant.  
1.8.4  
For Canadian Applications  
The following is excerpted from CP-01 Issue 5:  
"NOTICE: The Canadian Department of Communications label identifies certified  
equipment. This certification means that the equipment meets certain  
telecommunications network protective, operational and safety requirements. The  
Department does not guarantee the equipment will operate to the user's satisfaction.  
Before installing this equipment, users should ensure that it is permissible to be  
connected to the facilities of the local telecommunications company. The  
equipment must also be installed using an acceptable method of connection. In  
some cases, the company's inside wiring associated with a single line individual  
service may be extended by means of a certified connector assembly (telephone  
extension cord). The customer should be aware that compliance with the above  
conditions may not prevent degradation of service in some situations.  
Repairs to certified equipment should be made by an authorized Canadian  
maintenance facility designated by the supplier. Any repairs or alterations made by  
the user to this equipment, or equipment malfunctions, may give the  
telecommunications company cause to request the user to disconnect the equipment.  
Users should ensure for their own protection that the electrical ground connections  
of the power utility, telephone lines and internal metallic water pipe system, if  
present, are connected together. This precaution may be particularly important in  
rural areas.  
Caution: Users should not attempt to make such connections themselves, but should  
contact the appropriate electric inspection authority, or electrician, as appropriate."  
"The Load Number (LN) assigned to each terminal device denotes the percentage of  
the total load to be connected to a telephone loop which is used by the device, to  
prevent overloading. The termination on a loop may consist of any combination of  
devices subject only to the requirement that the total of the Load Numbers of all the  
devices does not exceed 100."  
11  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Industry Canada (IC) Compliance - "This digital apparatus does not exceed the Class  
A limits for radio noise emissions from digital apparatus set out in the Radio  
Interference Regulations of the Canadian Department of Communications."  
IC Registration Number: 2132 6030 A  
Load Number: 3  
1.9  
Modes and  
Special  
Functions  
1.9.1 Normal Mode:  
Normal mode is the standard mode of operation in which the UNI•COM monitors  
host FACP status as well as telephone line voltage. The UNI•COM reports system  
status information to UL listed Central Station Receivers. Information transmitted  
includes zone/point: fire alarm, fire alarm trouble and supervisory alarm. Specific  
system trouble conditions and specific UNI•COM troubles are also transmitted.  
1.9.2 Serviceman Code:  
The serviceman code, once entered, allows access to program, walktest, troubleshoot  
and type modes. The serviceman code also enables the clear function. Refer to  
following sections.  
1.9.3 Program Mode:  
Program mode is used to program the UNI•COM. While the UNI•COM is in the  
program mode, it cannot receive host FACP status information. See Section 3.0 for  
complete programming instructions.  
1.9.4 Walktest Mode:  
While in the walktest mode, transmission of FACP system events may be optionally  
transmitted to the UCS receiver (Central Station).  
1.9.5 Troubleshoot Mode:  
Troubleshoot mode may be used for testing the telephone line wiring. Connection  
from the UNI•COM's modular jacks, through RJ31X jacks and into the telephone  
network may be easily checked. In this mode, the keypad acts similar to a telephone  
touchpad.  
1.9.6 Type Mode:  
Type mode is used to program into the UNI•COM the system zones/points which are  
non-fire alarm, i.e. supervisory type. This mode is also used to disable the alarm  
report for any zone/point in the system. The feature which disables the zone/point  
alarm report must be used for zones/points programmed into the host FACP as  
remote silence, reset, drill or acknowledge switches.  
1.9.7 Clear Function:  
When the clear function is activated, it causes the UNI•COM to immediately stop  
transmissions, disconnect from the telephone network, clear out any messages that  
were waiting for transmission and reset.  
1.9.8 Manual Test Function:  
The manual test function allows a test report message to be sent to both central  
stations upon activation. A Serviceman Code is not required.  
1.9.9 Lamp Test Mode:  
The UNI•COM 4-character display segments plus all LEDs illuminate in this mode.  
1.9.10 User Code:  
The user code, once entered, allows for user level testing and maintenance functions.  
The user may be allowed to transmit walktest data to the UCS for the Unimode 200  
system.  
12  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.0 Installation and Wiring  
For information on installing the UNI•COM in a specific ADT fire alarm control  
panel, refer to the appropriate Appendix.  
2.1  
General  
Telephone Circuits  
2.2 Output Circuits  
Provision to connect to two independent telephone lines is available via two  
telephone jacks labeled PH1 (Primary) and PH2 (Secondary). Telephone line control/  
command is possible via double line seizure as well as usage of an RJ31X style  
interconnection. (RJ31X jacks must be ordered separately).  
Note: It is critical that the UNI•COM be located as the first device on the incoming  
telephone circuit to properly function.  
(Secondary Lines)  
Incoming Telco  
Phone Lines  
(Primary Lines)  
Incoming Telco  
Phone Lines  
Green Wire  
Red Wire  
Tip  
Ring  
Green Wire  
Ring  
Tip  
Ring  
To premise phones  
Tip  
To premise phones  
Tip  
Red Wire  
Ring  
Note: Shorting bars  
inside RJ31X Jack  
removed during male  
plug insertion  
7 foot  
Cable  
(MCBL-7)  
Secondary  
Phone Line  
PH-2  
Primary  
Phone Line  
PH-1  
Order Separately  
Male Plug  
Connectors  
Modular Female  
Connectors  
Make No  
Connection  
Figure 2-1: Wiring Phone Jacks  
13  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Relay Driver  
The UNI•COM's open collector output on TB3, terminal 2 is provided for Communi-  
cator Failure and UNI•COM trouble. It can be used to drive UL listed relay MR-101/  
C or MR-201/C. The output is rated for 40 mA and is power-limited. The normal  
condition for the output is Off (deenergized).  
Communicator Failure occurs when the maximum number of attempts to reach both  
central stations has taken place or when both phone lines are disconnected.  
UNI•COM trouble conditions include loss of telephone line voltage to the primary or  
secondary phone lines, communication failure to the primary or secondary central  
stations or entry into Programming, Troubleshoot or Type Mode..  
Wiring from the UNI•COM terminal TB3 to the relay must be in the same room no  
more than 20 feet in length and enclosed in conduit. Wiring from the relay output  
contacts must also remain in the same room as the UNI•COM.  
When the UNI•COM is programmed as 'Receive Only' (typically this occurs when  
annunciators are also used and are set for 'Receive/Transmit'), the relay output is  
used to provide a UNI•COM trouble input to the host control panel. For Unimode  
200 applications, use a monitor module to supervise the relay closure. Refer to  
Figure 2-3. Program the adjective and noun fields for 'DACT Trouble'. For  
Unimode II or Unimode 4-16 applications, wire the relay output to the annunciator  
trouble input circuit or use the relay to trigger zone trouble.  
When the UNI•COM is programmed as 'Receive/Transmit', EIA-485 supervision and  
UNI•COM trouble status are automatically handled by the host control panel.  
Relay Energized LED  
TB3  
Earth Gnd  
Comm Fail  
+24 VDC  
DPDT Contacts  
10 Amps  
@ 115 VAC  
All wiring to relay must  
Connections must be  
in same room as  
UNI•COM  
MR-201/C *  
be in same room within  
20 feet of UNI•COM and  
in conduit.  
Relay Energized LED  
TB3  
SPDT Contacts  
10 Amps  
Earth Gnd  
Comm Fail  
+24 VDC  
@ 115 VAC  
MR-101/C *  
* Note: The MR-101/C and MR-201/C include an enclosure.  
Figure 2-2: Relay Driver Connections  
Document # 50075 Rev B 3/13/95  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SLC Loop to Fire Alarm  
Control Panel  
M-300 Series Monitor Module  
Wiring in  
same room  
as UNI•COM  
All wiring to relay must  
3.9K EOL  
be in same room within  
20 feet of UNI•COM and  
in conduit.  
Resistor  
(supplied)  
TB3  
Earth Grnd  
Comm Fail  
+24 VDC  
MR-101/C  
(MR-201/C may also be used)  
DACT  
Note: 1) M-300 Series Monitor Module is used to supervise Normally Closed output of M-101/C. On  
DACT trouble and Comm Fail, MR-101/C relay contact will open causing M-300 to transmit  
trouble condition to FACP.  
Figure 2-3: Monitoring for UNI•COM Trouble  
15  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power-limited and nonpower-limited circuit wiring must remain separated in the  
cabinet. All power-limited circuit wiring must remain at least 0.25" away from any  
nonpower-limited circuit wiring. Furthermore, all power-limited circuit wiring and  
nonpower-limited circuit wiring must enter and exit the cabinet through different  
knockouts and/or conduits. A typical wiring diagram for the UNI•COM is shown  
below.  
2.3  
UL Power-  
limited Wiring  
Requirements  
Power-limited circuits  
Use power-limited source  
Figure 2-4: Typical Wiring Diagram for UL Power-limited Requirements  
16  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.0 Programming Instructions  
Programming of the UNI•COM is possible at any time including while the UNI•COM  
is communicating with a central station.  
Programming Mode  
The UNI•COM has a built-in programmer. All programming selections are stored in  
nonvolatile Electrically-Erasable Programmable Read-Only Memory (EEPROM).  
This ensures that the UNI•COM will retain all entries made in programming mode  
even if power is removed.  
The user must program the primary and secondary phone numbers, account numbers  
and 24 hour test report times for each central station account and the current time.  
The UNI•COM comes with factory chosen options/features already programmed.  
Other options/features may be programmed if desired. If all factory default settings  
are acceptable, programming is complete.  
Note: Access to the Programming Mode is not available to the end user. It may only  
be accessed by the serviceman.  
3.1  
Entering  
Program Mode  
To enter the Program Mode, first press the MODE key followed by the 4-digit  
serviceman code (factory default is 6, 3, 2, 1) then press the ENTER key. Next, to  
enter the Program Mode, press the MODE key once (the display will go blank) then  
start entering the code (7764). You have ten seconds to start entering the code.  
7764 spells PROG on a Touch-Tone® phone  
If an incorrect key is entered, reenter the proper 4-digit code before pressing the  
[ENTER/STORE] key  
___7  
__77  
_776  
7764  
Note that as you enter information into the  
UNI•COM, the digits will scroll across the  
display from right to left  
You are allowed a pause of up to 10 seconds in between each number while entering  
the code. After pressing the [ENTER/STORE] key, the UNI•COM will be in  
Program Mode and display 00_F. You are allowed up to ten minutes of idle time at  
this point before starting your programming, otherwise the UNI•COM will go back  
to Normal Mode. You also have a maximum of 10 minutes between any key stroke.  
All entries made prior to the 10 minute time-out are valid and stored.  
Once in Programming Mode, the UNI•COM will:  
Ignore the Test and Clear keys.  
Continue to communicate any events not previously acknowledged at the  
central station prior to entering Programming Mode.  
Location 54 is factory set to = 0, UNI•COM communications disabled. This keeps the  
communicator off until location 54 is changed to 1, 2, 3 or 4. Refer to program  
selection for address 54 in this section. Once location 54 is changed from 0 to 1, 2,  
3 or 4 and a valid phone number is entered, transmission of the Serviceman on  
Premises report will occur.  
17  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Throughout programming mode, the first three locations on the left of the display  
represent the memory address which can range from 00 to 164 (Alpha characters are  
not used). The last location (farthest right) represents the contents of the memory  
address. The first address displayed is shown below:  
00_F  
(address)(data)  
3.2  
Switch  
The Function of each switch in program mode is shown below:  
Functions  
No function in this mode  
- Select operating mode  
- Increment memory address  
Address entry  
keys are 0 to 9  
- Decrement memory address  
- Once = First memory address  
Twice = type any address  
Data entry keys  
are 0 to 9 and A  
to F  
{
- Save data, go to next address  
Figure 3-1: UNI•COM Keypad  
3.3  
Programming Primary phone number. (00-15)  
Options  
The first sixteen addresses, 00-15, are factory set to 'F' (from 00_F to 15_F).  
Programming is typically done as follows: If your phone # is 484-7161, type 4,  
the display will read 00_4, press [ENTER/STORE] to save the entry to memory and  
increment to the next address 01_F.  
Enter the remaining numbers in their respective addresses as shown below:  
4 8 4 7 1 6 1 F F F F F F F F F  
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 .  
18  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Valid entries for both the primary and secondary phone numbers are 0 - F with the  
numeric digits as dialed numbers and hexadecimal digits (A-F) representing the  
following functions:  
A= * on a Touchtone phone keypad  
B= # on a Touchtone phone keypad  
C= look for secondary dial tone for up to 2 seconds (then, dial anyway)  
D= 3-second pause  
E= 5-second pause  
F= end of phone number (Note: F must be entered)  
Primary Number Communication Format (16)  
One location is needed to select the Communication Format to the primary phone  
number. Address 16 is used for this purpose. The default (factory setting) for this  
address is '0' and cannot be changed. The format is ADT FSK II.  
Primary Number Account Code (17-19) Three locations at addresses 17-19 default  
to all '0's. Valid entries are 0-9.  
Primary Number 24 Hour Test Time (20-23).  
Use military time when entering the 24 hour 'test' time. The 24 hour test report to  
phone number 1 takes up four locations, from addresses 20-23. The default is 00:00  
(12:00 midnight). The limits for each location are as follows: 20: enter 0, 1 or 2;  
21: enter 0-9; 22 : enter 0-5; 23: enter 0-9. Note: Do not use A-F.  
Primary Number 24/12 Hour Test Time Interval (24). The test report sent to the  
Primary phone number may be sent every 12 or 24 hours. If the message is to be sent  
every 24 hours, leave the factory default entry of zero. If 12 hour test report time is  
needed, enter 1=12 hours.  
Secondary Phone Number (25-40). Programming is similar to programming the  
primary phone number located at addresses 00 - 15. The defaults are also all 'F's.  
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40  
Secondary Number Communication Format (41). Programming is the same as the  
primary number's Comm Format at address 16. Default entry is '0', ADT FSK II.  
Secondary Number Account Code (42-44) is programmed in addresses 42 - 44 in  
the same manner as the primary phone number Account Code. Default entries are all  
'0s'.  
Secondary Number 24-Hour Test Time (45-48) is programmed in addresses 45-  
48 in the same manner as the primary number 24-Hour Test Time. Default is 00:00  
(12:00 midnight).  
Note: The UNI•COM automatically programs all of the event codes. See  
Tables 3-2 and 3-3.  
19  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Secondary Number 24/12 Hour Test Time (49) The test message sent to the  
Secondary phone number may be sent every 12 or 24 hours. If the message is to be  
sent every 24 hours, leave the factory default entry of zero. If a 12 hour test report  
time is needed, enter 1=12 hours.  
Start Monitoring Address (50-51) is programmed to indicate the first group of  
zones or points to be monitored and reported to the central station. Default is '01'.  
Valid entries are '01, 02, 03 and 04'. See Table 3-1.  
End Monitoring Address (52-53) is programmed to indicate the last group of zones  
or points to be monitored and reported to the central station. Default is '01'. Valid  
entries are '01, 02, 03 and 04'. See Table 3-1.  
Use the Start and End Monitoring Address programming locations to set the  
reporting range of the UNI•COM.  
Zone Reporting (Factory Default)  
Point Reporting  
START  
START  
END  
END  
Addr. 50-51 Addr. 52-53  
Adtr. 50-51 Addr. 52-53  
1
1
1
Unimode 200  
Unimode 4-16  
01  
01  
01  
01  
01  
02  
Unimode 200  
01  
04  
1
2
Unimode II  
1 = Reports status of 56 zones.  
2 = Reports status of 120 zones.  
1 = Report status of 198 points  
Note: For additional information on the starting and ending addresses,  
refer to the host FACP Technical Manual.  
Table 3-1: Start and End Monitoring Address  
UNI•COM Communication Selection (54)  
Leaving address 54 at '0' disables communications to the central station(s). Enter '1'  
for zone reporting, receive only. Enter '2' for zone reporting, receive/transmit. Enter  
'3' for point reporting, receive only. Enter '4' for point reporting, receive/transmit.  
Note: Use receive only selections when using remote annunciators. Be certain to set  
one of the annunciators for receive/transmit for EIA-485 communications bus  
supervision. Use the receive/transmit entries when annunciators are not installed or  
when the UNI•COM receive/transmit function is used to supervise the EIA-485  
communication bus. For additional information on the receive/transmit function,  
refer to annunciator technical manuals.  
Backup Reporting (55) address 55 entry of '0' allows reports to be sent to  
Secondary phone number as backup only. Leaving address 55 with the default  
setting of '1' permits transmission to either the central station's Primary or Secondary  
phone number. The report will be sent to the first available receiver. An entry of '2'  
disables reports from being sent to the Secondary phone number.  
Touchtone/Rotary Select (56) A '0' programmed in this address by the factory  
triggers Touchtone dialing over both phone lines. Select '1' for rotary dialing.  
Make Break Ratio (57) Use this address only if you have chosen '1' for address 56.  
The make/break ratio is factory set to '0' which is 67/33, but may be changed to '1'  
which is a 62/38 ratio.  
Address (58) Leave default of 0.  
Address (59) Leave default of 0.  
20  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AC Loss Reporting Delay (60) '1' is factory default which causes a 6 hour time  
delay for AC loss reporting. Valid entries are 0 to 9 and A to F corresponding to the  
following reporting delay times: '1' = 6 hour, '2' = 7 hours, '3' = 8 hours, '4' = 9  
hours, '5' = 10 hours, '6' = 11 hours, '7' = 15 hours, '8' = 16 hours, '9' = 17 hours, 'A'  
= 18 hours, 'B' = 19 hours, 'C' = 20 hours, 'D' = 21 hours, 'E' = 22 hours and 'F' = 23  
hours. '0' entry causes immediate reporting of AC loss.  
Host Panel ID (61)  
Enter one of the following digits corresponding to the Control Panel in which the  
UNI•COM is installed. A correct entry is essential for proper operation.  
0 = Unimode 200  
1 = Unimode 416  
2 = Unimode II  
3 = Do not use  
4 = Do not use  
5 = Do not use  
6 = Do not use  
7 = Do not use  
8 = Do not use  
9 = Do not use  
Serviceman Code (62-65)  
The factory default is 62=6, 63=3, 64=2 and 65=1. The code must be properly  
entered to enable the following modes: program, walktest, troubleshoot and type. It  
also enables the clear function. The code may be changed. If, however, the code is  
changed and then forgotten, the factory default code of 6321 may be restored by  
pressing the MODE key followed by A, A, 1, 2, 3 and then pressing [ENTER/  
STORE].  
Safety Delay Time (66-68)  
Factory default is addresses 66=0, 67=0 and 68=0. Do not use.  
User Codes (69-98)  
Six 4-digit user codes may be programmed. The user is identified at the UCS  
receiver by this 4-digit code. In addition, each user code may designate whether or  
not the walktest events are transmitted to the UCS when the UNI•COM is used with  
a Unimode 200 FACP.  
69 - 72 = User 1 Walk Test Code  
73  
= User 1 Walk Test Transmit Enable  
74 - 77 = User 2 Walk Test Code  
78  
= User 2 Walk Test Transmit Enable  
79 - 82 = User 3 Walk Test Code  
83  
= User 3 Walk Test Transmit Enable  
84 - 87 = User 4 Walk Test Code  
88  
= User 4 Walk Test Transmit Enable  
89 - 92 = User 5 Walk Test Code  
93  
= User 5 Walk Test Transmit Enable  
94 - 97 = User 6 Walk Test Code  
98  
= User 6 Walk Test Transmit Enable  
For all User Walk Test Codes, the factory default of FFFF means no user is  
identified. Altering the default entries causes the user to be identified. Valid entries  
are 0 - 9 and A - F. For the Walk Test Transmit Enable addresses, a factory default  
entry of '0' disables the transmission of walktest events, while an entry of '1' enables  
the transmission of walktest events.  
21  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Programming Event Codes (99-168)  
A description of the type of reports with reported 'event code' that are sent to the  
central station appear in Tables 3-2 and 3-3. Entering a transmit selection of '0' will  
cause the communicator to inhibit transmission of the report. Transmission of  
reports to either or both central station phone numbers may be disabled.  
Note the special 'System Abnormal Test Report' event code. This report was added  
per new UL DACT requirements. This report is generated in place of the normal test  
report when an alarm and/or trouble condition exists at the time the test report is  
due to be sent.  
Programming the Real-Time Clock  
Entering an address greater than 172 will cause a display of the current time. On  
initial power up, the clock will start running from the factory setting of 00:01  
(military time). The far left digit will be flashing, indicating that this is the first digit  
to be programmed.  
Hours/Minutes  
Select a digit then press [ENTER/STORE]. The digit 2nd from the left will start  
flashing. Select a digit then press [ENTER/STORE]. Hours setting is complete.  
With the digit 2nd from the right flashing, select a digit then press [ENTER/  
STORE]. The digit on the far right will start flashing. Select a digit then press  
[ENTER/STORE]. Minutes setting is complete.  
End Programming  
Exit Programming Mode by pressing MODE, followed by the 4-digit code  
corresponding to an alternate mode of operation, then press [ENTER/STORE].  
During Program Mode, if no key is pressed within 10 minutes, the UNI•COM will  
revert to normal mode.  
22  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Address  
Description  
Primary # General Alarm Code  
Setting  
Event Codes  
FA  
99  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
124  
125  
126  
127  
128  
129  
130  
131  
132  
133  
134  
135  
Primary # Zone/Point Alarm Code  
FA###*1ST  
SS  
Primary # General Supervisory Code  
Primary # Zone/Point Supervisory Code  
Primary # General System Fault Code  
Primary # AC Fault Code  
SS###*1ST  
FT  
AA  
Primary # Zone/Point Fault Code  
FT###*2ST  
ST###*2ST  
YT  
Primary # Supervisory Zone/Point Fault Code  
Primary # Low Battery/Earth Fault Code  
Primary # Telco Primary Line Fault Code  
Primary # Telco Secondary Line Fault Code  
Primary # NAC Fault Code  
LT1  
LT2  
UT*2ST  
LT1*8ST  
LT2*8ST  
YC  
Primary # Comm. Trouble Primary # Code  
Primary #Comm. Trouble Secondary # Code  
Primary # 485 Communication Trouble Code  
Primary # Serviceman on Premises  
Walk Test Start  
id##SI  
id#FM1  
FH  
General Alarm Restore Code  
Primary # Zone/Point Alarm Restore Code  
General Supervisory Restore Code  
FR###  
SR  
Primary # Zone/Point Supervisory Restore Code  
Primary # General Fault Restore Code  
Primary # AC Fault Restore Code  
SR###  
FJ  
AH  
Primary # Alarm Zone/Point Fault Restore Code  
Primary # Supervisory Zone/Point Fault Restore Code  
Primary # Low Battery Fault Restore Code  
Primary #Telco Primary Line Fault Restore Code  
Primary #Telco Secondary Line Fault Restore Code  
Primary # NAC Fault Restore Code  
FR###  
SR###  
YR  
LR1  
LR2  
UR  
Primary # Comm. Trouble Primary # Restore Code  
Primary # Comm. Trouble Secondary # Restore Code  
Primary # 485 Communication Trouble Restore Code  
Primary # System Serviceman off Premises  
Primary # Walk Test End  
LR1  
LR2  
YO  
id##SO  
id#FK1  
RP1  
Primary # Normal System 24 Hour Test  
Primary # Abnormal System 24 Hour Test  
Manual Test  
RP5  
RP1  
Note: 1) Setting of 0 = do not transmit report to UCS  
2) Setting of 1 = transmit report to UCS  
3) Reports transmitted to the UCS for zone or point transmission use the following  
convention: *1ST = Alarm Only, *2ST = Trouble Only, *3ST = Alarm & Trouble Simultaneously  
Table 3-2: Event Codes, Primary Number  
23  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Address  
Description  
Setting  
Event Codes  
FA  
136  
137  
138  
139  
140  
141  
142  
143  
144  
145  
146  
147  
148  
149  
150  
151  
152  
153  
154  
155  
156  
157  
158  
159  
160  
161  
162  
163  
164  
165  
166  
167  
168  
169  
170  
171  
172  
Secondary # General Alarm Code  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Secondary # Zone/Point Alarm Code  
FA###*1ST  
SS  
Secondary # General Supervisory Code  
Secondary # Zone/Point Supervisory Code  
Secondary # General System Fault Code  
Secondary # AC Fault Code  
SS###*1ST  
FT  
AA  
Secondary # Zone/Point Fault Code  
FT###*2ST  
ST###*2ST  
YT  
Secondary # Supervisory Zone/Point Fault Code  
Secondary # Low Battery/Earth Fault Code  
Secondary # Telco Primary Line Fault Code  
Secondary # Telco Secondary Line Fault Code  
Secondary # NAC Fault Code  
LT1  
LT2  
UT*2ST  
LT1*8ST  
LT2*8ST  
YC  
Secondary # Comm. Trouble Primary # Code  
Secondary #Comm. Trouble Secondary # Code  
Secondary # 485 Communication Trouble Code  
Secondary # Serviceman on Premises  
Walk Test Start  
id##SI  
id#FM1  
FH  
General Alarm Restore Code  
Secondary # Zone/Point Alarm Restore Code  
General Supervisory Restore Code  
FR###  
SR  
Secondary # Zone/Point Supervisory Restore Code  
Secondary # General Fault Restore Code  
Secondary # AC Fault Restore Code  
SR###  
FJ  
AH  
Secondary # Alarm Zone/Point Fault Restore Code  
Secondary # Supervisory Zone/Point Fault Restore Code  
Secondary # Low Battery Fault Restore Code  
Secondary #Telco Primary Line Fault Restore Code  
Secondary #Telco Secondary Line Fault Restore Code  
Secondary # NAC Fault Restore Code  
Secondary # Comm. Trouble Primary # Restore Code  
Secondary # Comm. Trouble Secondary # Restore Code  
Secondary # 485 Communication Trouble Restore Code  
Secondary # System Serviceman off Premises  
Secondary # Walk Test End  
FR###  
SR###  
YR  
LR1  
LR2  
UR  
LR1  
LR2  
YO  
id##SO  
id#FK1  
RP1  
Secondary # Normal System 24 Hour Test  
Secondary # Abnormal System 24 Hour Test  
Manual Test  
RP5  
RP1  
Note: 1) Setting of 0 = do not transmit report to UCS  
2) Setting of 1 = transmit report to UCS  
3) Reports transmitted to the UCS for zone or point transmission use the following  
convention: *1ST = Alarm Only, *2ST = Trouble Only, *3ST = Alarm & Trouble simultaneously  
Table 3-3: Event Codes, Secondary Number  
24  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.0 Operating Instructions  
The UNI•COM has six Modes of operation; Normal, Program, Walktest,  
Troubleshoot, Type and Lamp Test. Upon initial power up, the system will be in  
Normal Mode. This section discusses operation of the UNI•COM in the Normal  
Mode.  
4.1  
Normal Mode  
4.1.1 Keys: Below is a description of the function keys in Normal Mode:  
MODE  
Pressing the Mode Key followed by a valid 4-digit numerical code and [ENTER/  
STORE] selects one of the six modes of operation.  
To enter normal mode from any other mode press MODE then  
6676 [ENTER/STORE]. 6676 spells NORM on a  
Touch-Tone® phone.  
If the Test Key is pressed three times in rapid succession the UNI•COM will transmit  
a manual test message to both central stations.  
TEST  
The Clear function will cause the UNI•COM to:  
CLEAR  
• cease transmissions  
• clear any active or pending transmissions  
• reset and return to normal system processing  
To perform the Clear function, first press the MODE key, enter a valid serviceman  
code and then press the [ENTER/STORE] key. Next press the CLEAR key  
followed by 2, 5, 3, 2, then press the [ENTER/STORE] key.  
25  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1st EVENT  
This key along with the UP Arrow and DOWN Arrow keys, are used to display  
UNI•COM fault conditions. Press the 1st EVENT key at any time to display the first  
event that occurred.  
DOWN ARROW  
UP ARROW  
Use the DOWN Arrow key to view other UNI•COM fault events (older) that have  
occurred and are active - not cleared yet.  
Use the UP Arrow key to view other UNI•COM fault events (newer), that have  
occurred and are active - not cleared yet.  
[ENTER/STORE]  
See individual mode descriptions in other sections.  
4.1.2 Displays: Four 7-segment red LED characters provide visual annunciation of  
UNI•COM trouble conditions. A list of messages that may appear on the display in  
normal mode is shown below:  
Primary Number Communication Fault  
PH_1  
Secondary Number Communication Fault  
PH_2  
Primary Phone Line Fault  
no_1  
Secondary Phone Line Fault  
no_2  
Individual LEDs are provided for:  
EIA-485—A yellow LED that turns on steady when a fault on the EIA-485 circuit is  
detected.  
Comm. Fail—This yellow LED turns on to indicate the loss of both telephone lines  
or that the maximum number of attempts to communicate with both Central Stations  
has been unsuccessful. Note: During a comm fail, the display will show either a PH1  
and PH2 or no1 and no2.  
Power On—A green LED that remains on while DC power is supplied to the  
UNI•COM. If this indicator fails to light under normal conditions, service the system  
immediately.  
Kiss-Off —A green LED that blinks when the central station has acknowledged  
receipt of each transmitted message.  
Test—A green LED that turns on to indicate that a manual test message is being  
transmitted.  
Primary Line Active—A red LED that indicates the primary phone line is active.  
Secondary Line Active—A red LED that indicates the secondary phone line is  
active.  
Modem —A green LED that stays on steady while communication to the UCS is  
taking place.  
26  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Primary  
Line  
Secondary  
Line  
Modem  
LED  
Primary Active  
Secondary  
Active  
LED  
Kiss-Off  
LED  
Figure 4-1: UNI•COM Phone Connectors and LEDs  
4.1.3 Normal Mode Operation: Normal mode is the standard mode of operation. In  
this mode, the UNI•COM monitors host FACP status, power input, EIA-485  
communications and telephone line voltage.  
The four character 7-segment display is normally off and does not annunciate events  
that are being transmitted. The display will only annunciate UNI•COM trouble  
conditions in the normal mode.  
The UNI•COM transmits zone/point and system status reports to a central station via  
the public switched telephone network. Two supervised telephone line connections  
are made to interface the UNI•COM to the telephone lines.  
The UNI•COM supervises both telephone lines for proper voltage. A delay of two  
minutes will occur before a fault in either phone line connection is reported as a  
trouble. When a fault is detected, the 4 character display will show either 'no 1' or 'no  
2' (depending upon which telephone line has the fault. 'no 1' = Primary Line, 'no 2' =  
Secondary Line) and the trouble condition will be reported to the central station over  
the remaining good phone line.  
The UNI•COM comes with line seizure capability provided for both the primary and  
secondary telephone line interfaces. Any time that the UNI•COM needs to make a  
call to the central station, line seizure will disconnect any local premises phones  
sharing the same telephone line.  
All transmission to the central station will be sent over the Primary phone line. In the  
event of noisy phone lines, transmissions will be sent over the backup Secondary  
phone line.  
Options exist to: (1) send reports to the secondary phone number as backup only, (2)  
send reports to either the primary or secondary phone numbers or (3) send reports to  
the primary phone number only. For additional information, refer to programming  
address 55. If 10 total attempts to communicate are unsuccessful, the Communicator  
Failure output will be turned on (TB3, terminal 2).  
27  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The UNI•COM meets NFPA 72 for Remote Station Protective Signaling Service and  
central station Signaling Service reporting requirements for: (a) the type of signal (b)  
condition and (c) location of the reporting premises.  
Since higher priority events take precedence over lower priority events, the  
UNI•COM will transmit higher priority events before sending the lower priority  
events. Priorities are as follows:  
Event Activations  
1. General Alarm  
2. Zone/Point Alarm #N  
3. General Supervisory  
4. Zone/Point Supervisory #N  
5. General System Trouble  
6. AC Power Loss  
7. Zone/Point Trouble #N  
8. Low Battery  
9. Telco Primary Line Fault  
10. Telco Secondary Line Fault  
11. NAC Fault Code  
12. Communication Trouble, Primary Number  
13. Communication Trouble, Secondary Number  
14. EIA-485 Communication Bus Trouble  
15. Serviceman on Premises  
16. Walktest Start  
17. System Automatic Test Report  
18. System Abnormal Automatic Test Report  
19. Manual Activated Test Report  
Event Restorals  
20. General Restoral  
21. Zone/Point Alarm #N Restoral  
22. General Supervisory Restoral  
23. Zone/Point Supervisory #N Restoral  
24. General System Trouble Restoral  
25. AC Power Loss Restoral  
26. Zone/Point Trouble #N Restoral  
27. Low Battery Restoral  
28. Telco Primary Line Fault Restoral  
29. Telco Secondary Line Fault Restoral  
30. NAC Fault Code Restoral  
31. Communication Trouble, Primary Number Restoral  
32. Communication Trouble, Secondary Number Restoral  
33. EIA-485 Communication Bus Trouble Restoral  
34. Serviceman off Premises  
35. Walktest End  
Where #N represents the zone or device ID number.  
Note: The Unimode 200 has a maximum capacity of 99 addressable smoke detectors  
and 99 addressable modules. When the UNI•COM is programmed for point transmis-  
sion, the reported range of addresses is 001 to 099 for detectors at addresses 01 to 99  
and 101 to 199 for modules at addresses 01 to 99.  
When using AIM modules with the Unimode II, the UNI•COM will report AIM devices  
in up to 8 zones maximum.  
28  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The 'general' reports for general fire, general supervisory and general fault are  
always transmitted (unless disabled). Zone or point information will follow the  
general reports if enabled.  
4.1.4 Key Report Descriptions  
Serviceman on Premises  
This report is generated any time that the serviceman enters a 4-digit code into the  
UNI•COM that matches the entry programmed into addresses 62-65. The report  
generated to the UCS receiver tells the central station that a serviceman is on the  
premises and is about to perform some type of maintenance on the system.  
The Serviceman Code must first be entered in order for the serviceman to gain  
access to program, walktest, troubleshoot and type modes. The Serviceman Code  
also enables the clear function.  
To enter the Serviceman Code, press the MODE key followed by the correct 4-digit  
code, then press the [ENTER/STORE] key. Once the [ENTER/STORE] key is  
pressed, the UNI•COM transmits the serviceman on premises report to the UCS. At  
this time, the UNI•COM continues to be fully capable of reporting system status to  
the central station.  
Once the Serviceman Code is correctly entered, the UNI•COM may be placed into  
any mode by pressing the MODE key, entering the appropriate 4-digit code and then  
pressing the [ENTER/STORE] key. While in any of the selected modes, the  
UNI•COM is not capable of reporting system status to the central station. The  
4-digit codes are as follows:  
Program Mode  
Walktest Mode  
Troubleshoot Mode  
Type Mode  
7764  
9255  
8768  
8973  
2532  
Clear Function  
For additional information on the functionality of each mode, see the appropriate  
sections.  
Note: If the Serviceman Code is forgotten, the factory default code of 6321 may be  
restored by pressing the MODE key followed by A, A, 1, 2, 3 and then pressing the  
[ENTER/STORE] key.  
The UNI•COM will also transmit the Serviceman on Premises Report when the  
correct level one password is entered into the Unimode 200.  
Serviceman off Premises Report  
The serviceman off premises report is generated to indicate that the serviceman has  
completed maintenance on the fire alarm system and is exiting the premises. This  
report is transmitted by the UNI•COM by pressing the MODE key, entering the  
digits 99 and then pressing the [ENTER/STORE] key.  
System Test Report  
The UNI•COM will transmit a test message to both central stations at programmed  
intervals (typically every 24 hours). Should there exist an abnormal condition in the  
fire alarm system (such as an alarm, trouble or supervisory condition) at the time  
when the test report is due to be transmitted, the UNI•COM will report the 'system  
abnormal test report.' If the system is normal, the report transmitted will be the  
normal 'system test report.'  
29  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EIA-485 Communications Trouble Report  
The UNI•COM supervises the integrity of the information received from the FACP  
via the EIA-485 communications bus. Should the communications bus malfunction,  
the UNI•COM transmits the report '485 comm trouble.' When the communications  
bus returns to proper operation, the UNI•COM will report '485 comm trouble  
restoral.' The EIA-485 communications bus is supervised when the UNI•COM is  
configured for receive only or receive/transmit operation.  
Manual Test Report  
By pressing the TEST key three times in rapid succession, the UNI•COM will  
transmit a manual test report to the UCS. The TEST key may be pressed at any  
time. The Serviceman Code is not required.  
Program settings for zone or point reporting must match in both the host FACP and  
the UNI•COM. Refer to the Unimode 200 Technical Manual section on Level One  
programming for instructions on setting the FACP for zone or point annunciation.  
Refer to Section 3.3 of this manual for instructions on setting addresses 50 through  
54 and 61. Also refer to Section 4.3 for a discussion of Type Mode.  
Zone/Point Fire Alarm Report  
The UNI•COM reports activated status of specific zones or points defined as fire  
alarm. Fire alarm devices include smoke detectors, pull stations, waterflow devices,  
heat sensors, etc. The report transmitted includes the fire alarm message and the  
identity of the activated zone or point.  
Note: Use the Type Mode to identify all supervisory devices installed in the system  
to the UNI•COM. Refer to the Type Mode instructions in Section 4.3.  
Zone/Point Supervisory Activation Report  
The UNI•COM reports activated status of specific zones or points defined as  
supervisory. The report transmitted includes the supervisory alarm message and the  
identity of the activated zone or point.  
General Fault Report  
The general fault report is transmitted for most types of system trouble conditions  
including the following:  
• Zone/point trouble  
Maintenance alert  
Wrong device  
Improper device  
Improper address  
Auto-detector test failure  
No response  
Shorted or open initiating device circuit  
• Main SLC loop fault  
• Earth fault  
• Reverse polarity/city box trouble  
• Memory corruption  
• Disabled point  
• Off-line programming  
• Annunciator trouble.  
Note: When a zone or point is in trouble, transmitted messages include the specific  
zone or point trouble report and the general fault report (unless disabled).  
A general fault report is not sent for AC loss and EIA-485 failure. These trouble  
conditions are transmitted as individual trouble reports.  
30  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Zone or Point Restoral Report  
Zone or point restoral reports are not transmitted to the UCS unless the zone or  
point is fully cleared of both alarm and trouble conditions.  
Walktest Begin and End Reports  
• Serviceman Walktest:  
Once a correct Serviceman Code is entered, Walktest Mode may be entered. In  
Walktest Mode, the serviceman has the option of transmitting all system walktest  
activity to the UCS or not reporting the activity to the UCS. The begin and end  
walktest messages identify the person walktesting the system as a serviceman  
(User id7).  
• User Walktest:  
Once a correct User Code is entered, Walktest Mode may be entered at the host  
FACP. In Walktest Mode, the user option of transmitting all system walktest  
activity to the UCS or not reporting the activity to the UCS is determined by  
program entries 69-98. The begin and end walktest messages identify the user  
walktesting the system as user 1 through 6. Refer to Section 3.3 for programming  
addresses 69-98.  
When used with a Unimode 200 FACP, Walktest Mode allows the option of  
transmitting all system activity during walktesting to a central station. It also  
prevents unwanted signals from being transmitted to the central station that may  
be interpreted as real fire alarm reports.  
4.2  
Walktest Mode  
For Unimode II and Unimode 4-16 applications, placing the FACP into Walktest  
Mode causes transmission of an EIA-485 bus failure message. Exiting Walktest  
Mode at the FACP causes the UNI•COM to transmit a restoral of EIA-485 bus  
message.  
To perform a Walktest, first, enter the Serviceman Code into the UNI•COM by  
pressing the MODE key, entering 9255 and then pressing the [ENTER/STORE]  
key. Next, place the host FACP into Walktest Mode (refer to appropriate section  
in the host FACP Technical Manual). Note that the Unimode 200 must be placed  
into point reporting operation in order to transmit walktest reports.  
The display will show the letter C as the left most character and a flashing zero as  
the right character. If the [ENTER/STORE] key is pressed, system walktesting  
will occur without transmitting the system activity to the central station. With the  
zero flashing, if the digit 1 is pressed changing the right most character to 1, and  
then the [ENTER/STORE] key is pressed, walktesting will occur with system  
activity transmitted to the central station.  
The UNI•COM will display 9256 if walktest data is not being transmitted to the  
central station. If the UNI•COM is transmitting the walktest data, 9259 will be  
displayed.  
The clear function may be used while in the walktest mode to stop the UNI•COM  
from completing transmissions of walktest data. Exiting walktest mode is not  
possible as long as there is walktest data waiting to be transmitted.  
If users are allowed to walktest a system, they must follow the same steps de-  
scribed above except they must first enter their User Code.  
31  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The UNI•COM will not transmit any system walktest data unless the UCS receiver  
(central station) first acknowledges receipt of the Begin Walk Test report. This is  
an added precaution to insure that the walktest data is not misinterpreted at the  
central station as a live report.  
Exit walktest mode by entering the Serviceman off Premises code or return to an  
alternate mode by entering the appropriate 4-digit code for that mode. Users  
should enter the Normal Mode by entering code 6676. Should no activity occur in  
the system for one hour, the UNI•COM will automatically exit walktest mode and  
report 'id0BE1'.  
Type mode may be used for the following purposes:  
4.3  
Type Mode  
• Disable alarm reports by zone or point  
• Identify which zones or points in the system are supervisory points  
• Identify which zones or points are fire alarm points  
• Change NAC fault report to unique report versus zone/point fault  
• Bypass reports for alarm or trouble on a zone/point  
To access Type Mode, enter a valid serviceman code and press the MODE key.  
Next enter the 4-digit code 8973 and then press the [ENTER/STORE] key. The  
UNI•COM will display three digits. For example the display may be as follows:  
01  
0
The characters to the left identify the zone or point number. In this example, 01  
identifies zone 01 or point address 01. The character to the right (0 in this  
example) identifies the type of zone or point as follows:  
0 = Zone or point defined as fire alarm  
1 = Disable zone or point report for alarm only, transmit zone or point  
fault  
2 = Zone or point defined as supervisory  
3 = NAC fault to be reported as 'UT###'  
4 = Bypass zone or point reports entirely. No transmission of zone/point  
alarm or fault  
Factory default is all zones or points set to '0' for fire alarm. To change the type  
definition of the zone or point from the factory setting of '0', press the 1, 2, 3 or 4  
keys. The digit entered will appear on the far right display. Next press the  
[ENTER/STORE] key. This stores the entry into E2 memory and increments to  
the next higher address.  
Use the UP, DOWN and 1st EVENT keys to move through the list of 120 zones  
or 198 points (refer to Appendices A, B and C), similar to the method described in  
the programming section of this manual.  
For Unimode 200 applications, when the UNI•COM is programmed for point  
reporting, detectors are reported as points 001 to 099 and modules are reported as  
points 101 to 199.  
To define all zones or points as fire alarm (return to original factory default  
settings) enter zone or point 999 and then press the [ENTER/STORE] key. The  
display will change to 01 0, indicating a return to the factory default settings.  
32  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3.1 Disabling of Zones or Points  
This feature is primarily used when system points have been defined as remote  
reset, acknowledge, silence or drill switches. Refer to the FACP Technical  
Manual for additional information. Activation of remote switches appear as  
alarms on the EIA-485 bus while in point type of annunciation. The UNI•COM  
will report these points as fire alarm points unless disabled in the Type Mode.  
Disabling of zones or points also prohibits the activation (shorted or alarm  
activated condition) from being reported by the UNI•COM. Disabling of the zone  
or point does not affect the reporting of the zone or point trouble condition.  
4.3.2 Zone or Point Supervisory  
Defining a zone or point as supervisory is required in order for the UNI•COM to  
identify the correct report to transmit to the UCS. Follow the programming  
instructions in the Unimode 200 manual to program a zone or point as superviso-  
ry. Next program the zone or point as a code 2 for supervisory.  
Use the charts in Appendices C and D to enter point and zone definitions.  
Note that while in Type Mode, the fire protection and reporting capabilities of the  
UNI•COM remain inactive.  
To access the Troubleshoot Mode, enter the correct Serviceman Code, then press  
MODE 8768 and [ENTER/STORE].  
4.4  
Troubleshoot  
Mode  
8768 spells TROU on a Touch-Tone® phone.  
Once in this mode, the UNI•COM will continue to communicate any events not  
yet acknowledged at the central station prior to entering Troubleshoot Mode.  
The UP Arrow, DOWN Arrow and 1st EVENT keys do not function in this  
mode.  
Telephone Line Testing  
Pressing C for touchtone dialing or D for rotary dialing, followed by [ENTER/  
STORE] causes seizure of the Primary phone line which in turn lights the red LED  
signifying Primary phone line active. After a delay of three seconds, the UNI•COM  
goes off hook to acquire a dial tone.  
The UNI•COM keypad may be used as a telephone touchpad for number dialing.  
Once the first digit is pressed, the display will move the C or D character one  
position to the left, while placing the digit to be dialed on the farthest right display  
position. Continue to press the phone numbers to be dialed. Successive depressions  
of the [ENTER/STORE] key hangs up and picks up the phone (places the phone on  
or off the hook).  
The secondary phone line may be tested by pressing the E key for touchtone dialing  
or the F key for rotary dialing and then following the same procedure used for the  
primary phone line.  
33  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A handset may be temporarily connected across transformer T1 as indicated in  
Figure 4-2. The handset, when connected across T1, may be used only as an  
amplifier/speaker or telephone with the UNI•COM used for number dialing.  
Both Primary and  
Secondary Lines  
Figure 4-2: Handset/Speaker Connection  
To perform a Lamp Test, press MODE then 5267 followed by [ENTER/STORE].  
This will test all system LEDs. The LEDs will stay on for five seconds, then the  
UNI•COM will return to normal mode.  
4.5  
Lamp Test  
Mode  
5267 spells LAMP on a Touch-Tone® phone.  
34  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.0 Compatible Receivers  
The table below shows UL listed receivers compatible with the UNI•COM:  
Addresses  
16 and 41  
Format Type  
ADT FSK II  
ADT UCS Receiver  
Model #  
E
Revision #  
E913  
Factory Default 0  
Software Revision #  
31893  
35  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.0 Programming Reference Sheets  
--- To enter Programming, press Mode: 7 7 6 4, Enter  
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑  
00  
01  
02  
03  
04  
05  
06  
07  
08  
09  
10  
11  
12  
13  
14  
15  
Addresses 00 to 15 store the Primary Phone Number. Enter 'F' to represent the end of the number.  
Primary Comm Format: 0 = ADT FSK II.  
16  
❑ ❑ ❑  
Primary Account Code: Valid keys are 0-9.  
Primary 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM).  
17  
18  
19  
❑ ❑ ❑ ❑  
20  
21  
22  
23  
Primary Number Test Time Interval. Enter '0' for 24-hour; '1' - 12-hour.  
24  
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
Addresses 25-40 store the Secondary Phone Number. Enter 'F' to represent the end of the number.  
Secondary Comm Format: 0 = ADT FSK II.  
41  
❑ ❑ ❑  
Secondary Account Code: Valid keys are 0-9.  
Secondary 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM).  
42  
43  
44  
❑ ❑ ❑ ❑  
45  
46  
47  
58  
Secondary Number Test Time Interval. Enter '0' for 24-hour; '1' - 12-hour.  
49  
❑ ❑  
Start Monitoring Address.  
50  
51  
❑ ❑  
End Monitoring Address.  
52  
53  
UNI•COM Communication Selection. Enter '0' to disable UNI•COM communication; '1' for zone report-  
54  
ing receive only communication; '2' for zone reporting receive/transmit communication; '3' for point  
reporting receive only communication; '4' for point reporting receive/transmit communication.  
Backup Reporting. Enter '0' to have secondary phone number act as backup only; '1' to have either  
55  
primary or secondary phone number receive reports; '2' to disable reports to the secondary phone  
number.  
Touchtone/Rotary Select. Enter '0' for touchtone dialing; '1' for rotary dialing.  
56  
Make/Break Ratio. If rotary dialing is selected in Address 58; Enter '0' for a 67/73 make/break ratio; '1'  
for a 62/38 make/break ratio.  
57  
Leave default of 0.  
58  
Leave default of 0.  
59  
AC Loss Reporting Delay. Enter '0' for no time delay after AC loss; '1' for 6 hour delay; '2' for 7 hour  
60  
delay; '3' for 8 hour delay; '4' for 9 hour delay; '5' for 10 hour delay; '6' for 11 hour delay; '7' for 15 hour  
delay; '8' for 16 hour delay; '9' for 17 hour delay; 'A' for 18 hour delay; 'B' for 19 hour delay; 'C' for 20  
hour delay; 'D' for 21 hour delay; 'E' for 22 hour delay; or 'F' for 23 hour delay.  
Host Panel ID. Enter '0' for Unimode 200; '1' for Unimode 416 or '2' for Unimode II; all other entries are  
invalid.  
61  
❑ ❑ ❑ ❑  
Serviceman Code. Valid entries are 0-9.  
62  
63  
64  
65  
❑ ❑ ❑  
Leave default of '000'.  
66  
67  
68  
36  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
❑ ❑ ❑ ❑  
User 1 Walk Test Code. Valid entries are 0-9  
69  
70  
71  
72  
User 1 Walk Test Transmit Enable: Enter '0' for no transmit of walktest events; '1' for transmit.  
73  
❑ ❑ ❑ ❑  
User 2 Walk Test Code. Valid entries are 0-9  
74  
75  
76  
77  
User 2 Walk Test Transmit Enable: Enter '0' for no transmit of walktest events; '1' for transmit.  
78  
❑ ❑ ❑ ❑  
User 3 Walk Test Code. Valid entries are 0-9  
79  
80  
81  
82  
User 3 Walk Test Transmit Enable: Enter '0' for no transmit of walktest events; '1' for transmit.  
83  
❑ ❑ ❑ ❑  
User 4 Walk Test Code. Valid entries are 0-9  
84  
85  
86  
87  
User 4 Walk Test Transmit Enable: Enter '0' for no transmit of walktest events; '1' for transmit.  
88  
❑ ❑ ❑ ❑  
User 5 Walk Test Code. Valid entries are 0-9  
89  
90  
91  
92  
User 5 Walk Test Transmit Enable: Enter '0' for no transmit of walktest events; '1' for transmit.  
93  
❑ ❑ ❑ ❑  
User 6 Walk Test Code. Valid entries are 0-9  
94  
95  
96  
97  
User 6 Walk Test Transmit Enable: Enter '0' for no transmit of walktest events; '1' for transmit.  
98  
37  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Programming Reference Sheet  
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑  
99  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑  
112  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
124  
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑  
125  
126  
127  
128  
129  
130  
131  
132  
133  
134  
135  
136  
137  
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑  
138  
139  
140  
141  
142  
143  
144  
145  
146  
147  
148  
149  
150  
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑  
151  
152  
153  
154  
155  
156  
157  
158  
159  
160  
161  
162  
163  
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑  
164  
165  
166  
167  
168  
169  
170  
171  
172  
38  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Programming Reference Sheet Factory Default Settings  
--- To enter Programming, press Mode: 7 7 6 4, Enter  
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑  
00  
01  
02  
03  
04  
05  
06  
07  
08  
09  
10  
11  
12  
13  
14  
15  
Addresses 00 to 15 store the Primary Phone Number. Enter 'F' to represent the end of the number.  
0
Primary Comm Format:0 = ADT FSK II.  
16  
0
0
0
❑ ❑ ❑  
Primary Account Code.  
17  
18  
19  
0
0
0
0
❑ ❑ ❑ ❑  
Primary 24-Hour Test Time. 0000 = 12:00 midnight.  
20  
21  
22  
23  
0
Primary Number Test Time Interval. '0' for 24-hour.  
24  
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
Addresses 26-41 store the Secondary Phone Number. Enter 'F' to represent the end of the number.  
0
Secondary Comm Format: 0 = ADT FSK II.  
41  
0
0
0
❑ ❑ ❑  
Secondary Account Code.  
42  
43  
44  
0
0
0
0
❑ ❑ ❑ ❑  
Secondary 24-Hour Test Time. 0000 = 12:00 midnight.  
45  
46  
47  
48  
0
Secondary Number Test Time Interval. '0' for 24-hour.  
49  
0
1
❑ ❑  
Start Monitoring Address  
50  
51  
0
1
❑ ❑  
End Monitoring Address  
52  
53  
0
UNI•COM Communication Selection. '0' for UNI•COM Communication disabled.  
Backup Reporting. '1' reports to either Primary or Secondary Central Station.  
56 Touchtone/Rotary Select. '0' for Touchtone.  
54  
1
55  
0
0
Make/Break Ratio. '0' for 67/33 make/break ratio.  
Leave default of zero.  
57  
0
58  
0
Leave default of zero.  
59  
1
AC Loss reporting delay. '1' for 6 hour time delay.  
Host PANEL ID. '0' for Unimode 200.  
60  
0
61  
6
3
2
1
❑ ❑ ❑ ❑  
Serviceman Code. Factory default setting.  
62  
63  
64  
65  
0
0
0
❑ ❑ ❑  
Leave default of '000'.  
66  
67  
68  
39  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F
F
F
F
❑ ❑ ❑ ❑  
User 1 Walktest Code. 'F' for no user identified.  
69  
70  
71  
72  
0
User 1 Walktest Transmit Enable. '0' for no transmit.  
73  
F
F
F
F
❑ ❑ ❑ ❑  
User 2 Walktest Code. 'F' for no user identified.  
74  
75  
76  
77  
0
User 2 Walktest Transmit Enable. '0' for no transmit.  
78  
F
F
F
F
❑ ❑ ❑ ❑  
User 3 Walktest Code. 'F' for no user identified.  
79  
80  
81  
82  
0
User 3 Walktest Transmit Enable. '0' for no transmit.  
83  
F
F
F
F
❑ ❑ ❑ ❑  
User 4 Walktest Code. 'F' for no user identified.  
84  
85  
86  
87  
0
User 4 Walktest Transmit Enable. '0' for no transmit.  
88  
F
F
F
F
❑ ❑ ❑ ❑  
User 5 Walktest Code. 'F' for no user identified.  
89  
90  
91  
92  
0
User 5 Walktest Transmit Enable. '0' for no transmit.  
93  
F
F
F
F
❑ ❑ ❑ ❑  
User 6 Walktest Code. 'F' for no user identified.  
94  
95  
96  
97  
0
User 6 Walktest Transmit Enable. '0' for no transmit.  
98  
40  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Programming Reference Sheet Factory Default  
1
1
1
1
1
1
1
1
1
1
1
1
1
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑  
99  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
1
1
1
1
1
1
1
1
1
1
1
1
1
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑  
112  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
124  
1
1
1
1
1
1
1
1
1
1
1
1
1
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑  
125  
126  
127  
128  
129  
130  
131  
132  
133  
134  
135  
136  
137  
1
1
1
1
1
1
1
1
1
1
1
1
1
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑  
138  
139  
140  
141  
142  
143  
144  
145  
146  
147  
148  
149  
150  
1
1
1
1
1
1
1
1
1
1
1
1
1
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑  
151  
152  
153  
154  
155  
156  
157  
158  
159  
160  
161  
162  
163  
1
1
1
1
1
1
1
1
1
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑  
164  
165  
166  
167  
168  
169  
170  
171  
172  
41  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix A: Point Assignments (Unimode 200)  
Point No.  
Type of Device  
(Detectors)  
Point No.  
Type of Device Point No.  
Type of Device  
(Detectors)  
Point No. Type of Device  
(Detectors)  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
124  
125  
126  
127  
128  
129  
130  
131  
132  
133  
134  
135  
136  
137  
138  
139  
140  
141  
142  
143  
144  
145  
146  
147  
148  
149  
(Detectors)  
151  
152  
153  
154  
155  
156  
157  
158  
159  
160  
161  
162  
163  
164  
165  
166  
167  
168  
169  
170  
171  
172  
173  
174  
175  
176  
177  
178  
179  
180  
181  
182  
183  
184  
185  
186  
187  
188  
189  
190  
191  
192  
193  
194  
195  
196  
197  
198  
199  
01  
02  
03  
04  
05  
06  
07  
08  
09  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
89  
90  
91  
92  
93  
94  
95  
96  
97  
98  
99  
100  
Not Used  
150  
NOTE: The UNI•COM is capable of reporting 198 points when used with the Unimode 200. Use chart to carefully  
identify supervisory points and remote switches in the system. Identify these points using Type Mode (refer to  
Section 4.3 Type Mode).  
42  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix B: Zone Assignments  
(Unimode 200 & Unimode 4-16)  
Zone No.  
Zone Function  
Zone No.  
Zone Function  
1
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
NOTE: The UNI•COM is capable of reporting 56 zones when used with the Unimode 200 or Unimode 4-16. Use  
chart to carefully identify supervisory zones. Identify these zones using Type Mode (refer to Section 4.3 Type  
Mode).  
43  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix C: Zone Assignments (Unimode II)  
Zone No.  
Zone Function  
Zone No.  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
Zone Function  
Zone No.  
Zone Function  
1
81  
2
82  
3
83  
4
84  
5
85  
6
86  
7
87  
8
88  
9
89  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
90  
91  
92  
93  
94  
95  
96  
97  
98  
99  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
115  
116  
117  
118  
119  
120  
NOTE:Use chart to carefully identify supervisory points and remote switches in the system. Identify these 120 zones  
using Type Mode (refer to Section 4.3 Type Mode).  
44  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix D: Unimode 200  
The UNI•COM is capable of reporting 198 points or 56 zones when used with the  
Unimode 200.  
The UNI•COM may be mounted in the Unimode 200 control panel or remotely in an  
ADT-ABS8RF or ADT-UBS1F enclosure up to 6000 feet away from the control  
panel. All power must be removed from the control panel before making any  
connections to prevent circuit damage. The EIA-485 serial interface is connected  
between the control panel and UNI•COM using twisted, shielded pair wire. Power  
should be wired from the control panel's 24 VDC (nominal) filtered, non-resettable  
output to TB1 on the UNI•COM if mounted remotely.  
Figure D-1: ADT-UBS1F  
UNI•COM mounting in Unimode 200  
Remove all power from the Unimode 200 by disconnecting AC and batteries. Install the supplied standoffs (three nylon  
and one aluminum standoff) in the appropriate holes located on the right side of the Unimode 200 main circuit board as  
illustrated in Figure D-2. Position J10 located on the back of the UNI•COM over connector J16 which is located center  
right on the main Unimode 200 circuit board, and carefully connect. Secure the UNI•COM to the aluminum standoff  
with the screw provided.  
The EIA-485 circuit and 24 VDC power are provided directly from connector J16 of the Unimode 200. Note: A 120 ohm  
EOL resistor is not required on the UNI•COM EIA-485 terminals when it is installed inside the Unimode 200 cabinet.  
The EOL resistor is required at the last device on the EIA-485 line external to the Unimode 200 panel.  
Unimode 200  
3/4" aluminum standoff  
with nut required for  
transient protection  
UNI•COM  
3/4" Nylon  
Standoffs  
Figure D-2: UNI•COM Mounting to Unimode 200  
45  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Supervised and Power  
Limited EIA-485 and  
power connections  
Solid  
Earth  
Ground  
Connection  
To  
Phone  
Lines  
+24 VDC  
Nonresettable  
Power  
(Supervised)  
Ferrite  
Cores  
P/N 29090  
Install 120 ohm EOL  
resistor (P/N: 71244)  
on TB1 terminals 3  
& 4 if last or only  
device on EIA-485  
line.  
Unimode 200  
Cabinet  
UNI•COM in ADT-ABS8RF  
(shown with cover removed)  
Unimode 200  
Notes:  
1) This arrangement allows use of the UNI•COM simultaneously with the RTM-8F module.  
2) Ferrite cores are recommended for all applications.  
3) Recommended wire is 12 AWG to 18 AWG twisted pair.  
4) Shielded wire is not required (unless mandated by local AHJ).  
If shielded wire is used, connect only one end of shield:  
a) shield may be connected to cabinet (earth ground) at fire alarm panel, or  
b) shield may be connected to TB1 Terminal 5 (Shield) at UNI•COM as shown in  
Figure D-3. NOTE: The shield end that is not connected should be insulated to prevent  
accidental grounding. Do not connect both ends of shield under any circumstance  
since a ground fault may result.  
5) Conduit is recommended for external wire runs. Consult local building codes.  
6) Connect Ground Strap (supplied with ADT-ABS8RF enclosure) from Earth Ground terminal on  
UNI•COM to a solid building earth ground. Conduit alone will not provide a reliable earth ground.  
7) UNI•COM may be located up to 6000 feet away from the host control panel.  
8) Refer to Specifications for power requirements.  
Figure D-3: External UNI•COM Mounting in ADT-ABS8RF  
46  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix E: Unimode 4-16  
The UNI•COM is capable of reporting a maximum of 56 zones when used with the Unimode 4-16.  
The UNI•COM reports alarms and troubles on inputs and reports only troubles on outputs. Beware of  
'gaps' in the reporting of input circuits. The gaps depend upon the mounting location and FACP  
configuration. The Unimode 4-16 has a maximum of 16 inputs.  
The UNI•COM must be mounted remotely in an ADT-ABS8RF or ADT-UBS1F enclosure and may be  
placed up to 6000 feet away from the control panel. All power must be removed from the control panel  
before making any connections to prevent circuit damage. The EIA-485 serial interface is connected  
between the control panel and UNI•COM using twisted, shielded pair wire. Power should be wired  
from the control panel's main power supply (MPS-24BPCA) 24 VDC (nominal) filtered power supply  
output to TB1 on the UNI•COM.  
Figure E-1: ADT-ABS8RF  
Supervised and Power  
Limited EIA-485 and  
power connections  
Solid Earth  
Ground  
Connection  
To Phone  
Lines  
(Supervised)  
P/N 29090  
Install 120 ohm  
EOL resistor (P/N:  
71244) on TB1  
terminals 3 & 4 if  
last or only device  
on EIA-485 line.  
Unimode 4-16  
UNI•COM in ADT-ABS8RF  
(Shown with cover removed)  
Notes:  
2) Ferrite cores are recommended for all applications.  
3) Recommended wire is 12 AWG to 18 AWG twisted pair.  
4) Shielded wire is not required (unless mandated by local AHJ).  
If shielded wire is used, connect only one end of shield:  
a) shield may be connected to cabinet (earth ground) at fire alarm panel, or  
b) shield may be connected to TB1 Terminal 5 (Shield) at UNI•COM as shown in  
Figure E-2. NOTE: The shield end that is not connected should be insulated to prevent  
accidental grounding. Do not connect both ends of shield under any circumstance  
since a ground fault may result.  
5) Conduit is recommended for external wire runs. Consult local building codes.  
6) Connect Ground Strap (supplied with ADT-ABS8RF enclosure) from Earth Ground terminal on  
UNI•COM to a solid building earth ground. Conduit alone will not provide a reliable earth ground.  
7) UNI•COM may be located up to 6000 feet away from the host control panel.  
8) Refer to Specifications for power requirements.  
Figure E-2: External UNI•COM Mounting in ADT-ABS8RF  
47  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Cut jumper JP1  
to make output  
nonresettable for  
use with UNI•COM  
-
+
Filtered, regulated,  
resettable, power-  
limited 24 VDC  
Figure E-3: MPS-24BPCA Connection to UNI•COM  
48  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix F: Unimode II  
The UNI•COM is capable of reporting 120 zones when used with the Unimode II. The UNI•COM  
reports alarms and troubles on inputs but reports only troubles on outputs. Beware of 'gaps' in the  
reporting of input circuits. The gaps depend upon the mounting location and the Unimode II system  
configuration. AIM modules are reported as a maximum of 8 zones.  
The UNI•COM may be mounted in the Unimode II control panel or remotely in an ADT-ABS8RF  
or ADT-UBS1F enclosure up to 6000 feet away from the control panel. All power must be removed  
from the control panel before making any connections to prevent circuit damage. The EIA-485  
serial interface is connected between the control panel and UNI•COM using twisted, shielded pair  
wire. Power should be wired from the control panel's main power supply 24 VDC (nominal) filtered,  
non-resettable output to TB1 on the UNI•COM.  
Figure F-1: ADT-ABS8RF  
UNI•COM mounting in Unimode II  
Remove all power from the Unimode II by disconnecting AC and batteries. Install the three supplied nylon support  
posts for the top and bottom left of the UNI•COM, one aluminum/nylon and one aluminum standoff in the CHS-4 chassis  
slot in which the UNI•COM is to be installed (refer to Figure F-2). Position the UNI•COM on the standoffs and secure  
on aluminum standoff with a #6-32 screw.  
Connect the communication line between the EIA-485 terminal block on the CPU-5000 and TB-1 terminals 3 and 4 on  
the UNI•COM being certain to observe polarity (refer to Figure F-3). Recommended wire is 12 AWG to 18 AWG twisted  
pair. If no other devices are connected to the EIA-485, install a 120 ohm EOL resistor across UNI•COM TB1 terminals  
3 and 4.  
Connect the supplied Ground Strap from the UNI•COM Earth Ground terminal on TB3 to the CHS-4 chassis. Connect  
24 VDC filtered, regulated power to TB1 terminals 1 and 2 on the UNI•COM (refer to Figure F-4).  
UNI•COM  
Nylon Support Posts  
Ground Strap  
Nylon and  
CHS-4  
CPU-5000  
Aluminum Standoff  
Aluminum  
Standoff and  
Screw  
Figure F-2: UNI•COM Mounting in CHS-4  
49  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EIA-485 (Supervised and  
Power Limited)  
-
+
TB1  
Terminal 3 RS+  
Terminal 4 RS-  
Install 120  
ohm EOL  
resistor (P/  
N:71244)  
across  
terminals 3 &  
4 if last or only  
device on EIA-  
485 line. Note  
that Terminals  
6 & 7 are not  
used at this  
time.  
CPU-5000  
UNI•COM  
Figure F-3: EIA-485 Connection  
50  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power (Supervised and  
Power Limited)  
TB1-1 +  
TB1-2 -  
TB3-3 +  
- TB3-4  
UNI•COM  
MPS-24A  
Power (Supervised and  
Power Limited)  
TB1-1 +  
TB1-2 -  
- TB2-2  
TB2-1+  
Cut jumper JP1  
to make output  
nonresettable for  
use with UNI•COM  
UNI•COM  
MPS-24B  
Figure F-4: 24 VDC Power Connection to UNI•COM  
51  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
52  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
53  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
54  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
55  
Document # 50075 Rev B 3/13/95  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Acoustic Research Headphones ARWH2 User Manual
ADC Laser Level P 80 412 User Manual
ADTX Work Light PLUS 90 User Manual
Agilent Technologies Computer Hardware E5250A User Manual
Aiphone Welding System NE NVP W User Manual
Alliance Laundry Systems Clothes Dryer 512685R2 User Manual
American Standard Indoor Furnishings 0240001 User Manual
Atlona Plumbing Product AT HD4 V41 User Manual
Axis Communications All in One Printer 2500 MFP User Manual
Eureka Tents Tent Tetragon 1210 User Manual