3M Air Conditioner 5797A MT User Manual

Cold Shrink QS-III  
Three-Conductor Splice Kit for use on  
Armor and Non-Armor Cables  
Instructions  
IEEE Std. 404  
35 kV Class  
250 kV BIL  
Cable Range Requirements  
Kit Number  
5797A-MT  
Cable Insulation  
O.D. Range  
Conductor  
Size Range  
1.07" to 1.70"  
(27,2 mm to 43,2 mm)  
1/0 AWG - 350 kcmil*  
(60 - 185 mm2)  
* Splices (including size transitions) can be made to smaller or larger conductors, provided  
both cables are within the Insulation O.D. Range and the connector meets the dimensional  
requirements shown below.  
Connector Dimensional Requirements  
Minimum  
inches (mm)  
Maximum  
inches (mm)  
Outside Diameter  
0.51" (13,0 mm)  
1.70" (43,2 mm)  
6.00" (152 mm)  
6.50" (165 mm)  
Length  
Aluminum (Al/Cu)  
------  
------  
Length  
Copper (Cu)  
3MCold Shrink  
QS-III Splicing Kit  
5797A-MT  
78-8126-0432-6-A  
ƽCAUTION  
Working around energized high-voltage systems may cause serious  
injury or death. Installation should be performed by personnel familiar  
with good safety practice in handling high-voltage electrical equipment.  
De-energize and ground all electrical systems before installing product.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.0 Kit Contents:  
1.1 Kit Contents are as follows:  
3 ..............Cold Shrink 5467A QS-III Silicone Splice Bodies  
6 ..............Tubes, P55/R Red Compound  
3 ..............Metallic Shield Sleeves  
6 ..............Constant Force Spring Shield Connectors (1.31" I.D.)  
2 ..............Constant Force Spring Shield Connectors (1.54" I.D.)  
1 ..............Armor to Armor Continuity Braid  
2 ..............Cold Shrink Jacket Tubes  
1 ..............3MCC-2 Cable Preparation Kit  
1 ..............Roll, Scotch33+ Vinyl Electrical Tape (3/4" x 66')  
5 ..............Rolls, ScotchSuper 88 Vinyl Electrical Tape (1 1/2" x 44')  
4 ..............Rolls, Scotch-Seal2229 Mastic Tape (3 3/4" x 10')  
1 ..............Roll, Scotch24 Electrical Shielding Tape (1" x 15')  
1 ..............Roll, Scotch2228 Rubber Mastic Tape (2" x 10')  
6 ..............Rolls, ArmorcastStructural Material (4" x 15')  
6 ..............Cold Shrink Adapter Tubes (3 white core and 3 red core)  
1 ..............Instruction Sheet  
6 ..............Copper Foil Tape (1/2" x 10")  
12 ............Gloves  
2.0 Prepare Cable  
2.1 Prepare the cable according to your company's  
standard procedures. Allow cable ends to overlap as  
much as 10" (254 mm).  
Cable X  
33" (838 mm)  
Remove 33" (838 mm) of cable jacket, plus half of  
the overlap from Cable X.  
Remove 25" (635 mm) of cable jacket, plus half of  
the overlap from Cable Y.  
Keep a 22" (559 mm) piece of cable jacket removed  
from Cable X and a 14" (356 mm) piece of jacket  
from Cable Y for use later in these instructions.  
Cable Y  
25" (635 mm)  
2.2 If cable is armored, remove cable armor leaving  
1 1/2" (37 mm) armor exposed beyond jacket end.  
1 1/2"  
(37 mm)  
Remove cable binder , if present, at the end of the  
jacket or armor and discard.  
Fold cable fillers and ground wire(s) back over  
cable jacket end. Do not cut off.  
Temporarily hold the fillers and ground wire(s) back  
by banding them to the cable jacket using Scotch  
33+ vinyl tape.  
remove  
binder  
fold fillers back  
DO NOT CUT OFF  
78-8126-0432-6-A  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.3 Cut the phase cores to the appropriate length.  
Cable X 33" (838 mm)  
Cable Y 25" (635 mm)  
Cores of Cable X should be 33" (838 mm) when  
measured from the cable jacket end or 31 1/2"  
(800 mm) when measured from end of the armor.  
Cores of Cable Y should be 25" (635 mm) when  
measured from the cable jacket end or 23 1/2"  
(597 mm) when measured from end of the armor.  
2.4 Bind the metallic shields of both Cable X and  
Cable Y cores with a copper tape strip at a point  
11 1/2" (292 mm) from the end of each conductor.  
Remove the metallic shields to the copper tape  
binding.  
copper  
tape strips  
If the phase cores are individually jacketed, remove  
the individual jackets a distance of 15" (381 mm)  
from the end of each conductor.  
2.5 Remove cable semi-conductive insulation screen  
from cores of both Cable X and Cable Y for  
a distance of 8 1/2" (216 mm) from the end of each  
conductor.  
11 1/2" (292 mm)  
Note: Cables must be within Insulation O.D. range of  
the splice kit.  
2.6 Remove cable insulation from conductors ends of  
both Cable X and Cable Y.  
Remove cable insulation for 1/2 connector length plus  
an allowance * for increases in connector length due  
to crimping. Insulation removal length shall not  
exceed 3 1/4" (83 mm) from conductor end.  
8 1/2" (216 mm)  
Do not install connectors now.  
*Note: This assumes that the installer has determined  
the increased length of an aluminum connector  
crimped with a specific tool and die.  
field determine  
Aluminum  
Connector Size  
Typical Growth  
allowance per end  
1/0 AWG  
2/0 AWG  
3/0 AWG  
4/0 AWG  
250 kcmil  
350 kcmil  
1/8" (3 mm)  
1/8" (3 mm)  
1/8" (3 mm)  
1/4" (6 mm)  
1/4" (6 mm)  
1/4" (6 mm)  
Notes: 1. Copper connectors do not require a length  
change allowance.  
2. Maximum aluminum connector crimped length  
allowed is 6.50" (165 mm).  
78-8126-0432-6-A  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.0 Place Components on Cable  
loose core  
ribbon end  
3.1 Slide one large cold shrink jacket tube onto  
Cable X and one onto Cable Y with the loose  
core ribbon ends going on the cable last, extending  
toward the cable ends.  
large jacket tube  
loose core ribbon end  
splice body  
3.2 Slide a 3Mcold shrink splice body onto each  
core of Cable X with the loose core ribbon  
end going on the cable first, away from cable end.  
shield  
sleeve  
3.3 Expand metallic shield sleeves and slide one onto  
each core of Cable Y. Compress the ends of each  
shield sleeve together next to the cable armor or  
jacket, away from the prepared conductor ends.  
3.4 For 1/0 through 3/0 AWG connectors, or  
connectors with an O.D. between 0.51–0.76"  
(13,0–19,3 mm): Slide the cold shrink adapter tube  
with the WHITE CORE onto the insulation with the  
loose core ribbon end going on first, away from the  
cable end.  
loose core ribbon end  
For 4/0 AWG through 350 kcmil connectors or  
connectors with an O.D. between 0.68–1.07"  
(17,3–27,2 mm): Slide the cold shrink adapter tube  
with the RED CORE onto the insulation with the  
loose core ribbon end going on first, away from the  
cable end.  
adapter tube  
78-8126-0432-6-A  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.0 Install Splice  
4.1 Install connectors. See Table on front cover of  
this instruction for proper connector dimensions.  
Crimp connectors per recommendations from  
connector manufacturer. For standard 3M™  
connectors, refer to the table at the end of this  
instruction for crimping information.  
4.2 Apply a tape marker to core semi-con insulation  
screens of Cable Y (cable side which does not  
contain splice body) at a distance of 10"  
(254 mm) measured from the CENTER of  
connectors.  
10" (254 mm)  
4.3 Position cold shrink copper connector adapter over  
CENTER of connector. Shrink the adapter near  
center of connector by pulling and unwinding the  
loose core ribbon end in a counter-clockwise  
direction.  
4.4 Remove any excess oxidation inhibitor from  
connector ends if aluminum connectors are used.  
Clean cable using standard practice:  
a. Do not use solvent or abrasive on cable  
semi-conductive insulation shield.  
b. If abrasive is used on cable insulation, do not  
reduce diameter below the 1.07" (27,2 mm)  
minimum specified for the splice.  
78-8126-0432-6-A  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5 Apply red compund on cable insulation, making  
certain to fill in edges of cable semi-cons.  
Red P55/R  
compound  
Note: DO NOT use silicone grease.  
4.6 Position each splice body over the connector and  
align the leading end of the rubber part with the  
center of the marker tape.  
align end of splice body to  
marker tape  
Slowly begin to remove the inner support core by  
pulling, while unwinding, the loose ribbon end in a  
counterclockwise direction. Allow only 1/4"  
(6 mm) of the splice to shrink onto the marker tape.  
Carefully slide the splice body off the marker tape  
until its leading edge is aligned with the marker tape  
edge. Continue removing the core to complete splice  
body installation.  
Note: The splice body ends must overlap onto the  
semi-conducting layer of each cable by at least  
1/2" (12,7 mm).  
Note: DO NOT push the splice body towards the tape  
marker, as this may cause the end to roll under. If  
the end does roll under, DO NOT use sharp edged  
tools to pull it out as this could cut and damage  
the splice.  
vinyl tape bands  
4.7 Apply copper shield sleeves:  
a) Center one shield sleeve over each splice body.  
b) Starting at center, form sleeves to splice bodies  
using vinyl tape bands.  
4.8 Connect sleeve ends to the cable metallic shield  
with constant force springs.  
Install each spring by unwrapping and rewrapping  
the spring around itself over the shield sleeve end and  
cable metallic shield.  
Trim off excess shield sleeve braid material.  
Cover springs and trimmed shield sleeve ends with  
one half-lapped layer of vinyl tape.  
trim off excess sleeve  
78-8126-0432-6-A  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.9 Connect the ground wire(s) from Cable X to the  
ground wire(s) from Cable Y. Make the connection  
away from the splice bodies.  
connect ground wire(s)  
33+ vinyl tape  
4.10 Unfold the cable fillers and reestablish their lay  
between the cable phase cores. Hold the fillers in  
place with a band of 33+ vinyl tape.  
5.0 Install Armor Continuity (If Cable is Armored)  
5.1 Apply multiple wraps of Scotch24 shielding tape  
around the exposed armor on both Cable X and  
Cable Y to fill a valley in the corrugated armor. Half  
hitch to tie off.  
5.2 Wrap an end of the ground continuity braid around  
exposed armor and applied 24 tape on one cable end.  
constant  
force  
spring  
°
Wrap one wrap only and fold the braid at 90 with  
the long braid end extending toward splice opening.  
Install a large constant force spring around the  
braid wrapped on the armor. Spiral wrap the braid  
around the splice opening to the other cable armor.  
°
Fold the braid 90 and wrap braid end around armor.  
Wrap braid end for one wrap only. Cut off and  
discard excess braid.  
Connect braid by installing other constant force  
spring. Overwrap each spring with 33+ tape.  
78-8126-0432-6-A  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.0 Install Splice Jacket  
6.1 Over wrap the exposed conductors on each side of  
splice bodies with jacket pieces saved from step 2.1.  
overwrap jacket piece  
with vinyl tape  
Bind the cable jacket pieces in place with one  
half-lapped layer of Scotch88, 1 1/2" wide tape.  
6.2 At both ends of splice, apply four wraps of 2228  
rubber mastic, around the cable jacket 1/2" from  
jacket ends.  
2228 rubber  
mastic  
Stretch the rubber mastic to three-fourth original  
width when applying.  
6.3 Install a Cold Shrink jacket tube on each cable with  
the leading end just covering the 2228 mastic and the  
tube extending toward the splice bodies.  
Cold Shrink jacket  
tube  
Pull while unwinding the loose core ribbon end in  
a counterclockwise direction to install jacket tubes.  
6.4 Apply one half lapped layer of 88 tape over the  
unjacketed area in splice center. Do not overlap the  
Cold Shrink jacket tubes.  
88 vinyl  
tape  
78-8126-0432-6-A  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.5 Apply two half-lapped layers of 4" wide 2229 tape  
over applied vinyl tape in splice center. Overlap ends  
of Cold Shrink jacket tubes 2" (51 mm).  
2229 mastic  
tape  
6.6 Cover the applied 2229 mastic with two half lapped  
layers of 88 tape.  
88 vinyl  
tape  
6.7 Overwrap the entire splice with a minimum of two  
half lapped layers of Armorcastwrap.  
Tear open the top end of the foil Armorcast material  
container and fill foil container half full with water.  
Squeeze the container four or five times allowing the  
water to penetrate the roll. Pour out water, remove  
roll from foil container and immediately apply to  
splice area.  
Armorcast  
wrap  
Bind the final wrap in place with vinyl tape.  
Note: Wear rubber gloves provided when handling  
Armorcast Wrap. The resin contains a  
black die that will stain human skin.  
Armorcast Wrap can be applied first and then  
sprayed with water to activate the curing system  
It will also cure from moisture in the air in  
humid conditions.  
6.8 Splice is complete.  
78-8126-0432-6-A  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Crimping Tool - Die Sets (number of crimps/end)  
Square D Co.  
Anderson Div.  
Burndy  
Thomas & Betts Corp  
Kearney  
Type O  
Conductor  
Size  
3M  
Connector  
Number  
(AWG or  
kcmil)  
Y35, Y39  
VC6-3**  
VC6-FT**  
MD6  
W163 (2) 1/0 (1)  
W241 (2) 1/0 (1) A25AR (1)  
MY29  
Y34A  
Y1000**  
TBM 5  
TBM 8  
TBM 12 TBM 15  
Y45*, Y46*  
10005 (Cu)  
1/0  
1/0  
1/0  
2/0  
2/0  
2/0  
2/0  
3/0  
3/0  
3/0  
3/0  
4/0  
4/0  
4/0  
4/0  
250  
250  
250  
250  
300  
300  
300  
300  
350  
350  
350  
350  
A25R (1)  
U25RT (1)  
U25ART (1)  
U25ART (1)  
U26RT (2)  
U26ART (2)  
U26RT (2)  
U28ART (2)  
U27RT (2)  
U27ART (2)  
U27RT (3)  
U28ART (2)  
U28RT (2)  
U28ART (2)  
U28RT (3)  
U28ART (2)  
U29RT (2)  
U29ART (2)  
U29RT (3)  
U31ART (2)  
U30RT (2)  
U30ART (2)  
U30RT (3)  
U31ART (2)  
U31RT (2)  
U31ART (2)  
U31RT (3)  
U31ART (2)  
(1)  
(1)  
(1)  
(1)  
(1)  
(1)  
(1)  
Pink (2)  
Tan (2)  
Pink (2)  
Tan (2)  
42 (2)  
50 (1)  
50 (1)  
45 (1)  
54H (2)  
45 (2)  
76 (2)  
50 (1)  
60 (2)  
50 (2)  
76 (2)  
54H (2)  
66 (4)  
54H (3)  
76 (2)  
62 (2)  
71H (2)  
62 (3)  
87H (2)  
66 (2)  
76 (1)  
66 (3)  
87H (2)  
71H (3)  
87H (3)  
71H (4)  
87H (2)  
(1)  
(1)  
(1)  
(1)  
(2)  
(2)  
(2)  
(1)  
(2)  
(2)  
(2)  
(2)  
(2)  
(3)  
(2)  
(2)  
(3)  
(3)  
(2)  
(2)  
(2)  
(3)  
(2)  
(2)  
(2)  
(3)  
(3)  
5/8-1 (3)  
5/8-1 (3)  
20005 (Al/Cu)  
CI-1/0 (Al/Cu)  
10006 (Cu)  
BG (3)  
W241 (2) 2/0 (1)  
BG (4)  
W241 (3) 2/0 (2)  
W249 (3)  
U243 (1)  
A26R (1)  
Olive (2)  
Black (2)  
Olive (2)  
Black (3)  
Blue (4)  
Black (2)  
Olive (2)  
Black (3)  
20006 (Al/Cu)  
11006 (Cu)  
2/0 (1) A26AR (2)  
5/8-1 (3)  
A26R (2)  
CI-2/0 (Al/Cu)  
10007 (Cu)  
840 (4)  
W243 (2) 3/0 (1)  
W166 (4) 3/0 (1)  
W243 (3) 3/0 (2)  
A27R (1)  
Orange (2) Orange (2)  
Ruby (2) Ruby (2)  
Orange (3) Orange (3)  
20007 (Al/Cu)  
11007 (Cu)  
737 (3)  
A27R (2)  
CI-3/0 (Al/Cu)  
10008 (Cu)  
W249 (3)  
BG (3)  
Blue (4)  
Purple (2)  
White (4)  
Purple (3)  
Blue (4)  
Yellow (2)  
840 (4)  
4/0 (1)  
A28R (2)  
Purple (2)  
20008 (Al/Cu)  
11008 (Cu)  
W660 (4) 4/0 (2) A28AR (2)  
840 (4)  
BG (4)  
4/0 (2)  
A28R (3)  
Purple (3)  
CI-4/0 (Al/Cu)  
10009 (Cu)  
W249 (3)  
840 (4)  
W166 (3) 250 (1)  
W249 (3)  
W166 (4) 250 (2)  
A29R (2)  
A29AR (2)  
A29R (3)  
Yellow (2)  
20009 (Al/Cu)  
11009 (Cu)  
71H (2)  
Yellow (3)  
Yellow (3)  
CI-250 (Al/Cu)  
10010 (Cu)  
87H (2)  
A30R (3)  
A30AR (2)  
A30R (3)  
White (2)  
20010 (Al/Cu)  
11010 (Cu)  
76H (3)  
White (3)  
CI-300 (Al/Cu)  
10011 (Cu)  
87H (2)  
A31R (2)  
Red (3)  
20011 (Al/Cu)  
11011 (Cu)  
87H (3)  
A31R (3)  
Red (4)  
CI-350 (Al/Cu)  
87H (2)  
*Y45 and Y46 accept all Y35 dies (“U Series”). For Y45, use PT6515 adapter. For Y46, use PUADP adapter.  
**Anderson VC6-3, VC6-FT and Burndy Y1000 require no die set.  
78-8126-0432-6-A  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Armorcast, Scotch, Scotch-Sealand 3Mare trademarks of 3M Company.  
Note: The core material being removed from the Splice Body, Jacket Tubes  
and adapter are mixed polymers and can be recycled with other waste.  
IMPORTANT NOTICE  
Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability  
associated with such use.  
Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture as of the date of  
purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF  
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above,  
your exclusive remedy shall be, at 3M’s option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except  
where prohibited by law, 3M will not be liable for any loss or damage arising from this 3M product, whether direct, indirect, special,  
incidental or consequential regardless of the legal theory asserted.  
Electrical Products Division  
6801 River Place Blvd.  
Austin, TX 78726-9000  
800/245-3573  
Printed in USA  
© 3M IPC 2002 78-8126-0432-6-A  
Printed on 50% recycled paper  
with 10% post-consumer  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Acer Switch ALH 316ds 324ds User Manual
AEG Washer 52600 User Manual
Amana Range AGR5844VDW User Manual
American Standard Plumbing Product 2555602 User Manual
AMX Network Card RDA CKM User Manual
Audiovox Battery Charger AH780R User Manual
AVERATEC GPS Receiver 320 GPS User Manual
Avet Reels Fishing Equipment HXJ 5 2 User Manual
Baldor Water Heater iMN1800 User Manual
Behringer Music Pedal EM600 User Manual