Lincoln Impinger Conveyor Oven Series 1200 User Manual

SERVICE MANUAL  
(INTERNATIONAL)  
IMPINGER CONVEYOR OVENS  
MODEL SERIES 1000 & 1200  
Lincoln Foodservice Products, LLC  
1111 North Hadley Road  
Fort Wayne, Indiana 46804  
United States of America  
Phone: (800) 374-3004  
U.S. Fax: (888) 790-8193 • Int’l Fax: (260) 436-0735  
Technical Service Hot Line  
(800) 678-9511  
www.lincolnfp.com  
1000serviceexp  
REV: 1/5/07  
SEQUENCE OF OPERATIONS 1002/1003  
MODEL 1002 - 240VAC - 50HZ - NATURAL GAS  
MODEL 1003 - 240VAC - 50HZ - L.P. GAS  
POWER SUPPLY  
Electrical Power to be supplied to the Oven by a three conductor service.  
Black conductor is Hot  
Red conductor is Neutral  
Green conductor is Ground  
CONTROL BOX  
AUTO COOL DOWN  
When the temperature in the Control Box reaches 120°F +  
3°, the Cooling Fan Thermostat will switch power to the Control Box Cooling Fan.  
The Thermostat will interrupt power to the Cooling Fan when the Control Box  
temperature falls to 100°F + 3°.  
MAIN FAN CIRCUIT  
Electrical power is permanently supplied to the normally open contacts of the Double  
Pole Main Fan Relay, the Cooling Fan Thermostat, the normally open Double Pole  
Main Fan Switch, and the normally open Cool Down Thermostat (thermostat closes  
at 160°F and opens at140°F). Closing the Main Fan Switch supplies 240 VAC  
through a 3A Fuse to the primary of the control circuit Step down Transformer. The  
Transformer steps the voltage down to 120 VAC for the control circuit. 120 VAC is  
supplied to the coil of the Double Pole Main Fan Relay. The coil of the relay is  
energized. The normally open contacts now close, energizing the Main Fan Motor  
through one 10A Fuse. Closing the Fan Switch also supplies power to the Cooling  
Fan, Hour Meter (hour meter discontinued after S/N 3484), the 12.6 VAC  
Transformer, the Burner and Conveyor Switches.  
BURNER CIRCUIT  
Closing the Fan Switch and the normally open Burner Switch supplies 120 VAC  
through the Air Pressure Switch, to the normally open contacts of the Burner Motor  
Relay, and the primary of the 24 VAC Step Down Transformer. The Transformer  
secondary supplies 24 VAC to the Relay Coil (the normally open contacts close  
within 30 seconds), and the normally open Centrifugal Switch. When the Relay  
contacts close, the Burner Blower Motor is energized. As this motor reaches  
approximately 1600 R.P.M., its internal centrifugal switch closes, supplying 24 VAC  
to the Gas Control Valve. When the Gas Control Valve is supplied with 24 VAC, the  
pilot valve is energized, and the igniter circuit is energized. Ignition should now  
occur. After pilot flame is proven, the main gas valve is energized. The Burner  
Indicator Light is also energized.  
CONVEYOR DRIVE  
(S/N 100 to 4389)  
Closing the Fan Switch and the normally open Conveyor Switch supplies 120 VAC  
through a 3A Fuse, to the Motor Control Board. AC volts are converted to D.C. volts  
and are supplied to the Conveyor Motor at board terminals A1 and A2 through a  
D.P.D.T. Reversing Switch. Adjustment of the Speed Control Potentiometer (500  
ohm, 10 turn) will change resistance at terminals S1, S2, and S3 varying the D.C.  
voltage to the motor. The speed of the Conveyor Motor will increase or decrease as  
the D.C. voltage from the Motor Control Board increases or decreases respectively  
Closing the fan switch and the conveyor switch supplies 120 VAC to the Motor  
Control Board. AC volts are converted to DC volts and are supplied to the Conveyor  
Motor at terminals A+ and A-. Adjustment of the Speed Control Potentiometer (5,000  
ohm 10 turn) will change resistance at terminals P1, P2, and P3 varying the DC  
voltage to the motor. The speed of the conveyor motor will increase or decrease as  
the DC voltage from the board increases or decreases respectively. As the motor  
turns, it drives both the reducer gear box and the tach. generator which supplies a  
voltage to the DC motor control board and is used as a reference for maintaining a  
constant conveyor speed  
(S/N 4390 and UP)  
Impinger I -–1000 Series Service Manual - International  
3
TIME TEMP DISPLAY  
The Time/Temp Display is energized when the Fan Switch is closed, supplying 120  
VAC to the primary of the 12.6 volt Transformer. The secondary output of the  
transformer, normally 13 to 14 VAC (depending on input), with a center tap, is  
supplied to terminals 1,2, and 3 of the Time/Temp Display. The center tap is terminal  
2. The display works on a balanced input and center tap voltage to each leg must be  
1/2 the total reading.  
The speed side of the Time/Temp. Display uses a slotted disc (cemented to tach.  
coupling) to break the infra-red light beam of the optical switch (mounted on gear  
motor) producing electrical pulses that are transmitted to the display. The display  
converts these pulses into a read-out of minutes and seconds.  
The temperature portion of the display uses a Thermistor Probe to sense oven  
temperature. The thermistor outputs a resistance proportional to the oven  
temperature. This resistance is then converted by the display into a temperature  
reading.  
SEQUENCE OF OPERATIONS 1106  
MODEL 1006 - 240 VAC - 50HZ - 1 PHASE - NATURAL GAS  
POWER SUPPLY  
Electrical Power to be supplied to the Oven by a three conductor service.  
Red conductor is Hot  
Black conductor is Neutral  
Green conductor is Ground  
CONTROL BOX AUTO  
COOL DOWN  
When the temperature in the Control Box reaches 120°F + 3°, the Cooling Fan  
Thermostat will switch power to the Control Box Cooling Fan. The Thermostat will  
interrupt power to the Cooling Fan when the Control Box temperature falls to 100°F +  
3°.  
MAIN FAN CIRCUIT  
Electrical power is permanently supplied to the normally open contacts of the Double  
Pole Main Fan Relay, the Cooling Fan Thermostat, and through a 3A Fuse to the  
normally open Double Pole Main Fan Switch, and the normally open Cool Down  
Thermostat (thermostat closes at 160°F and opens at 140°F). Closing the Main Fan  
Switch supplies 240 VAC to the primary of the control circuit Step Down  
Transformer. (The transformer steps the voltage down to 120VAC for the control  
circuit) 120 VAC is supplied to the coil of the Main Fan Relay. The coil of the Relay is  
energized, the normally open contacts now close, energizing the Main Fan Motor  
through one 10A fuse. Closing the Fan Switch also supplies power to the Cooling  
Fan, the 12.6 VAC Transformer, the Burner and Conveyor Switches  
Upon closure of the Fan Switch, 120 VAC is supplied to the primary of the 12.6 VAC  
Transformer. The Transformer steps the voltage down to 12.6 VAC (normally 13 to  
14 VAC) with a center tap, and supplies power to the Time/Temp Display. The  
voltage from each leg of the Transformer's secondary to the center tap should be  
one half of the secondary voltage.  
TRANSFORMER (12.6  
VAC)  
BURNER CIRCUIT  
Closing the Fan Switch and the normally open Burner Switch supplies 120 VAC  
through the Air Pressure Switch, to the normally open contacts of the Burner Motor  
Relay, and the primary of the 24 VAC Step Down Trans-former. The Transformer  
secondary supplies 24 VAC to the coil of the Burner Motor Relay (the normally open  
contacts close within 30 seconds), and through the Burner Air Pressure Switch to the  
normally open Centrifugal Switch. When the Relay contacts close, the Burner Blower  
Motor is energized. As this motor reaches approximately 1600 R.P.M., the Burner Air  
Pressure Switch closes, and the motor's internal centrifugal switch closes supplying  
24 VAC to the Gas Control Valve. When the Gas Control Valve is supplied with 24  
VAC, the pilot valve is energized, and the igniter circuit is energized. Ignition should  
now occur. After pilot flame is proven, the main gas valve is energized. The Burner  
Indicator Light is also energized.  
CONVEYOR DRIVE  
(S/N 4390 AND UP)  
Closing the fan switch and the normally open conveyor switch supplies 120 VAC to  
the Motor Control Board .AC volts are converted to DC volts and are supplied to the  
Conveyor Motor at terminals A+ and A-. Adjustment of the Speed Control  
Potentiometer (5000 ohm 10 turn ) will change resistance at terminals P1, P2, and  
P3 varying the DC voltage to the motor. The speed of the conveyor motor will  
4
Impinger I -–1000 Series Service Manual - International  
increase or decrease as the DC voltage from the board increases or decreases  
respectively. As the motor turns, it drives both the reducer gearbox and the Tach.  
Generator. The Tach. Generator is a DC voltage generator, which supplies a voltage  
to the DC motor control board and is used as a reference for maintaining a constant  
conveyor speed.  
The Time/Temp. Display is energized when the Fan Switch is closed, supplying 120  
VAC to the primary of the 12.6 volt Transformer. The secondary output of the  
transformer, normally 13 to 14 VAC (depending on input), with a center tap is  
supplied to terminals 1,2, and 3 of the Time/Temp Display. The center tap is terminal  
2. The display works on a balanced input and center tap voltage to each leg must be  
1,2 the total reading.  
TlME/TEMP DISPLAY  
The speed side of the Time/Temp. Display uses a slotted disc (cemented to tach.  
coupling) to break the infra-red light beam of the optical switch (mounted on gear  
motor) producing electrical pulses that are transmitted to the display. The display  
converts these pulses into a read-out of minutes and seconds.  
The temperature portion of the display uses a Thermistor Probe to sense oven  
temperature. The thermistor outputs a resistance proportional to the oven  
temperature. This resistance is then converted by the display into a temperature  
reading.  
SEQUENCE OF OPERATIONS 1028 / 1029 / 1228 / 1229  
MODEL 1028 - 380Y/220 VAC - 50 HZ - 3 PHASE  
MODEL 1029 - 415Y/240 VAC - 50 HZ - 3 PHASE  
MODEL 1228 - 380Y/220 VAC - 50 HZ - 3 PHASE - DUAL BELT  
MODEL 1229 - 415Y/240 VAC - 50 HZ - 3 PHASE - DUAL BELT  
POWER SUPPLY  
Electrical Power to be supplied to the Oven by a five conductor service.  
Black conductor is Hot  
Red conductor is Hot  
Orange conductor is Hot  
White conductor is Dedicated Neutral  
Green conductor is Ground  
MAIN FAN CIRCUIT  
Electrical power is permanently supplied through 3, 50A fuses to the normally open  
contacts of the Mercury Contactor. Power is also supplied through 1, 10A fuse to the  
normally open contact of the Main Fan Relay, through a 1A Fuse to the normally  
open Double Pole Main Fan Switch, and to the normally open Cool-Down  
Thermostat (thermostat closes at 160°F and opens at 140°F.) Closing the Main Fan  
Switch supplies 220 or 240 VAC to the primary of the control circuit Step Down  
Transformer. (The transformer steps the voltage down to 120 VAC for the control  
circuit.) 120 VAC is supplied to the coil of the Main Fan Relay. The coil of the relay is  
energized, the normally open contacts close, energizing the Main Fan Motor. Closing  
the Main Fan Switch also supplies power to the 12.6 VAC Transformer, the Control  
Box Cooling Fan, and the Heat and Conveyor Switches.  
TRANSFORMER (12.6  
VAC)  
Upon closure of the Fan Switch, 120 VAC is supplied to the primary of the 12.6 VAC  
Transformer. The Transformer steps the voltage down to 12.6 VAC (normally 13 to  
14 VAC) with a center tap, and supplies power to the Time/Temp. Display. The  
voltage from each leg of the Transformer's secondary to the center tap should be  
one half of the secondary voltage.  
HEAT CIRCUIT  
Closing the Fan Switch and the normally open Heat Switch supplies 120 VAC  
through the normally open Air Pressure Switch, and the normally closed Hi-Limit  
Thermostat (manually re-settable, opens at 190°F) and, the 3A Fuse, to the L1  
terminal of the Temperature Control Board, the coil of the Mercury Contactor, and to  
the Heat Indicator Light.  
TEMPERATURE  
CONTROL  
When the Heat Switch is closed, 120 VAC is supplied to the Temperature Control.  
The Temperature Control Potentiometer (2.5K ohm) is adjusted to desired  
temperature. The Thermocouple will provide varying millivolts to the Temperature  
Controller. The Temperature Controller switches the L 2 line of the Contactor coils at  
intermittent intervals to maintain desired temperatures.  
Impinger I -–1000 Series Service Manual - International  
5
CONVEYOR DRIVE  
(S/N 100 to 4389)  
Closing the Fan Switch and the normally open Conveyor Switch supplies 120 VAC  
through a 3A Fuse, to the Motor Control Board. AC volts are converted to D.C. volts  
and are supplied to the Conveyor Motor at board terminals A1 and A2 through a  
D.P.D.T. Reversing Switch. Adjustment of the Speed Control Potentiometer (500  
ohm, 10 turn) will change resistance at terminals S1, S2, and S3 varying the D.C.  
voltage to the Conveyor Motor. The speed of the Conveyor Motor will increase or  
decrease as the D.C. voltage from the Motor Control Board increases or decreases  
respectively.  
(S/N 4390 and UP  
1000 Series)  
(S/N 4390 to 14790  
1200 Series)  
Closing the fan switch and the normally open Conveyor switch supplies 120 VAC to  
the Motor Control Board. AC volts are converted to DC volts and are supplied to the  
Conveyor Motor at terminals A+ and A-. Adjustment of the Speed Control  
Potentiometer (5,000 ohm 10 turn ) will change resistance at terminals P1, P2, and  
P3 varying the DC voltage to the motor. The speed of the conveyor motor will  
increase or decrease as the DC voltage from the board increases or decreases  
respectively. As the motor turns, it drives both the reducer gearbox and the tach.  
generator. The tach. generator is a DC voltage generator which supplies a voltage to  
the DC motor control board and is used as a reference for maintaining a constant  
conveyor speed.  
(S/N 14791 & Above  
1200 Series  
See Page 9  
NOTE  
TIME TEMP  
DISPLAY(S/N 4390 &  
Above1000 Series) S/N  
The 1200 Series Ovens utilize 2 complete conveyor drive systems.  
The Time/Temp. Display is energized when the Fan Switch is closed, supplying 120  
VAC to the primary of the 12.6 volt Transformer. The secondary output of the  
transformer, normally 13 to 14 VAC (depending on input), with a center tap, is  
4390-147901200 Series) supplied to terminals 1,2, and 3 of the Time/Temp. Display. The center tap is  
terminal 2. The display works on a balanced input and center tap voltage to each leg  
must be 1/2 the total reading.  
(T/T Display S/N  
Q14791& Above1200  
Series See Page 9  
The speed side of the Time/Temp. Display uses a slotted.disc (cemented to tach.  
coupling) to break the infra-red light beam of the optical switch (mounted on gear  
motor) producing electrical pulses that are transmitted to the display. The display  
converts these pulses into a read-out of minutes and seconds.  
The temperature portion of the display uses a Thermistor Probe to sense oven  
temperature. The thermistor outputs a resistance proportional to the oven  
temperature. This resistance is then converted by the display into a temperature  
reading.  
The 1200 Series Ovens use a Double Pole Double Throw Switch to connect the two  
Optical Encoder Assemblies to the Time/Temp. Display. By activating the switch,  
either the front or rear belt speed can be shown by the Time/Temp. Display.  
NOTE  
SEQUENCE OF OPERATIONS 1030  
MODEL 1030 - 220 VAC - 50HZ - 1 PHASE  
POWER SUPPLY  
Electrical Power to be supplied to the Oven by a three conductor service.  
Black conductor is Hot  
Red conductor is Neutra  
Green conductor is Ground  
CONTROL BOX  
AUTO COOL DOWN  
When the temperature in the Control Box reaches 120°F + 3°, the Cooling Fan  
Thermostat will switch power to the Control Box Cooling Fan. The Thermostat will  
interrupt power to the Cooling Fan when the Control Box temperature falls to 100°F +  
3°.  
MAIN FAN CIRCUIT  
Electrical power is permanently supplied to the normally open contacts of the Double  
Pole Main Fan Relay, the Cooling Fan Thermostat, the normally open Main Fan  
Switch, and the normally open Cool Down Thermostat (thermostat closes at 160°F  
and opens at 140°F). Closing the Main Fan Switch supplies 220 VAC through a 3A  
Fuse to the (normally open) Burner Switch, and to the control circuit Step Down  
Transformer (the transformer steps the voltage down to 120 VAC for the control  
circuit) 120 VAC is supplied to the coil of the Main Fan Relay The coil is energized,  
the normally open contacts close, supplying 220 VAC through one 10A Fuse to the  
Main Fan Motor. 120 VAC is also supplied to the 12.6 VAC Transformer, the  
Temperature Controller and the Conveyor Switch.  
TRANSFORMER (12.6  
VAC)  
Upon closure of the Fan Switch, 120 VAC is supplied to the primary of the 12.6 VAC  
Transformer. The Transformer steps the voltage down to 12.6 VAC (normally 13 to  
6
Impinger I -–1000 Series Service Manual - International  
14 VAC) with a center tap, and supplies power to the Time/Temp Display. The  
voltage from each leg of the Transformer's secondary to the center tap should be  
one half of the secondary voltage  
Closing the normally open Burner Switch supplies 220 VAC, through the gas  
pressure-proving switch, and through the Main Fan Air Pressure Switch, to the  
Ignition Control. The combustion motor relay is energized, its normally open contacts  
now close, supplying120 VAC to the combustion motor. The normally open  
combustion air switch closes upon sensing air. After pre-purge period of between 30  
and 60 seconds, the Ignition Transformer is energized and the Main Gas Valve is  
energized. Ignition should now occur.  
BURNER CIRCUIT  
TEMPERATURE  
CONTROL  
Closing the Fan Switch supplies (through the Step down Transformer) 120 VAC to  
the Temperature Control Board. The 2.5K ohm Temperature Potentiometer is  
adjusted to desired temperature. The Thermocouple will provide varying millivolts to  
the Temperature Controller. The Temperature Controller supplies 120 VAC to the  
Solenoid Valve at intermittent intervals to maintain desired temperature.  
Closing the fan switch and the normally open conveyor switch supplies 120 VAC to  
the Motor Control Board. AC volts are converted to DC volts and are supplied to the  
Conveyor Motor at terminals A+ and A-. Adjustment of the Speed Control  
Potentiometer (5,000 ohm 10 turn) will change resistance at terminals P1, P2, and  
P3 varying the DC voltage to the Conveyor Motor. The speed of the conveyor motor  
will increase or decrease as the DC voltage from the board increases or decreases  
respectively. As the motor turns, it drives both the reducer gearbox and the tach.  
generator. The tach. generator is a DC voltage generator which supplies a voltage to  
the DC motor control board and is used as a reference for maintaining a constant  
conveyor speed.  
CONVEYOR DRIVE  
(S/N4390-Q17170)  
(Conveyor Drive  
Q171701 & Above See  
Page 9)  
(Time/Temp Display  
Q17171 & Above See  
Page 9)  
The Time/Temp. Display is energized when the Fan Switch is closed, supplying 120  
VAC to the primary of the 12.6 volt Transformer. The secondary output of the  
transformer, normally 13 to 14 VAC (depending on input), with a center tap, is  
supplied to terminals 1,2, and 3 of the Time/Temp. Display. The center tap is  
terminal 2. The display works on a balanced input and center tap voltage to each leg  
must be 1/2 the total reading.  
TIME/TEMP  
DISPLAY(Q17171 &  
Above See Page 9  
The speed side of the Time Temp. Display uses a slotted disc (cemented to tach.  
coupling) to break the infra-red light beam of the optical switch (mounted on gear  
motor) producing electrical pulses that are transmitted to the display. The display  
converts these pulses into a read-out of minutes and seconds.  
The temperature portion of the display uses a Thermistor Probe to sense oven  
temperature. The thermistor outputs a resistance proportional to the oven  
temperature. This resistance is then converted by the display into a temperature  
reading.  
SEQUENCE OF OPERTIONS 1032  
MODEL 1032 - 380Y/220 VAC - 50 HZ - 3 PHASE  
POWER SUPPLY  
Electrical Power to be supplied to the Oven by a five conductor service  
Black conductor is Hot  
Red conductor is Hot  
Orange conductor is Hot  
White conductor is Dedicated Neutral  
Green conductor is Ground  
MAIN FAN CIRCUIT  
Electrical power is permanently supplied through 3, 50A fuses to the normally open  
contacts of the Mercury Contactor. Power is also supplied through one 10A fuse to  
the normally open contact of the Main Fan Relay, through a 1A Fuse to the normally  
open Double Pole Main Fan Switch, and to the normally open Cool-Down  
Thermostat (thermostat closes at 160°F and opens at 140°F.) Closing the Main Fan  
Switch supplies 220VAC to the primary of the control circuit Step Down Transformer.  
(The transformer steps the voltage down to 120 VAC for the control circuit.) 120 VAC  
is supplied to the coil of the Main Fan Relay. The coil of the relay is energized, the  
normally open contacts close, energizing the Main Fan Motor. Closing the Main Fan  
Switch also supplies power to the 12.6 VAC Transformer, the Control Box Cooling  
Impinger I -–1000 Series Service Manual - International  
7
Fan, and the Heat and Conveyor Switches.  
TRANSFORMER (12.6  
VAC)  
Upon closure of the Fan Switch, 120 VAC is supplied to the primary of the 12.6 VAC  
Transformer. The Transformer steps the voltage down to 12.6 VAC (normally 13 to  
14 VAC) with a center tap, and supplies power to the Time/Temp Display. The  
voltage from each leg of the Transformer's secondary to the center tap should be  
one half of the secondary voltage.  
HEAT CIRCUIT  
Closing the Fan Switch and the normally open Heat Switch supplies 120 VAC  
through the normally open Air Pressure Switch, and the normally closed Hi-Limit  
Thermostat (manually re-settable, opens at 368°C) through the 3A Fuse, to the  
Temperature Control Board, the coil of the Mercury Contactor, and to the Heat  
Indicator Light.  
TEMPERATURE  
CONTROL  
When the Heat Switch is closed, 120 VAC is supplied to the Temperature Control.  
The Temperature Control Potentiometer (2.5K ohm) is adjusted to desired  
temperature. The Thermocouple will provide varying millivolts to the Temperature  
Controller. The Temperature Controller switches the L2 line of the Contactor coil at  
intermittent intervals to maintain desired temperature.  
CONVEYOR DRIVE  
(S/N 4390 AND UP)  
Closing the fan switch and the normally open conveyor switch supplies 120 VAC to  
the Motor Control Board AC volts are converted to DC volts and are supplied to the  
Conveyor Motor at terminals A+ and A-. Adjustment of the Speed Control  
Potentiometer (5,000 ohm 10 turn ) will change resistance at terminals P1, P2, and  
P3 varying the DC voltage to the Conveyor Motor. The speed of the conveyor motor  
will increase or decrease as the DC voltage from the board increases or decreases  
respectively. As the motor turns, it drives both the reducer gear box and the tach.  
generator. The tach. generator is a DC voltage generator which supplies a voltage to  
the DC motor control board and is used as a reference for maintaining a constant  
conveyor speed.  
TIME TEMP DISPLAY  
The Time/Temp. Display is energized when the Fan Switch is closed, supplying 120  
VAC to the primary of the12.6 volt Transformer. The secondary output of the  
transformer, normally 13 to 14 VAC (depending on input), with a center tap, is  
supplied to terminals 1,2, and 3 of the Time/Temp. Display. The center tap is  
terminal 2.The display works on a balanced input and center tap voltage to each leg  
must be 1/2 the total reading.  
The speed side of the Time/Temp. Display uses a slotted disc (cemented to tach.  
coupling) to break the infra-red light beam of the optical switch (mounted on gear  
motor) producing electrical pulses that are transmitted to the display. The display  
converts these pulses into a read-out of minutes and seconds.  
The temperature portion of the display uses a Thermistor Probe to sense oven  
temperature. The thermistor outputs a resistance proportional to the oven  
temperature. This resistance is then converted by the display into a temperature  
reading.  
SEQUENCE OF OPERATIONS / 1033, 1034, 1046, 1047  
MODEL 1033 / 220 VAC - 50HZ / NATURAL GAS  
MODEL 1034 / 220 VAC - 50HZ / L.P. GAS  
MODEL 1046 / 240 VAC - 50HZ / NATURAL GAS  
MODEL 1047 / 240 VAC - 50HZ / L.P. GAS  
POWER SUPPLY  
Electrical Power to be supplies to the oven by a three-conductor service.  
Brown conductor is Hot  
Blue conductor is Neutral  
Green conductor is Ground  
CONTROL BOX AUTO  
COOL DOWN  
When the temperature in the Control Box reaches 120°F 3°, the Cooling Fan  
Thermostat will switch power to the Control Box Cooling Fan. The Thermostat will  
interrupt power to the Cooling Fan when the Control Box temperature falls to  
100°F 3°.  
MAIN FAN CIRCUIT  
Electrical power is permanently supplied to the normally open contacts of the oven  
fan motor relay, the Cooling Fan Thermostat, and the normally open Oven Fan  
Switch. Closing the oven fan switch supplies 220 VAC, through a 3 AMP Fuse, to the  
primary of the Power Transformer (the transformer steps the voltage down to 120  
VAC for the control circuit). 120 VAC is supplied to the Cooling Fan, the normally  
open Conveyor Switch, the Electronic Temperature Control, and to the coil of the  
8
Impinger I -–1000 Series Service Manual - International  
oven start and cool down relay. Its normally open contacts close, supplying 220 VAC  
to the Burner Switch and enabling the 20-minute Time Delay module. The 20-minute  
Time Delay module supplies 120 VAC to the oven fan motor relay, these normally  
open contacts now close, supplying 220 VAC to the Oven Fan Motor.  
Upon closure of the Fan Switch, 120 VAC is supplied to the primary of the 12.6 VAC  
Transformer. The Transformer steps the voltage down to 12.6 VAC (normally 13 to 14  
VAC) with a center tap, and supplies power to the Time/Temp Display. The voltage  
from each leg of the Transformer's secondary to the center tap should be one half of  
the secondary voltage.  
TRANSFORMER(12.6V  
AC)  
BURNER CIRCUIT  
Closing the normally open burner switch supplies 220 VAC through the oven air  
pressure switch, the gas inlet pressure switch, the normally closed high limit  
thermostat (opens at 368°C) to the ignition control. The combustion motor is now  
energized. The normally open burner blower air pressure switch closes upon sensing  
air pressure. After a pre-purge period of 30-60 seconds, the main gas valve and the  
spark generator are energized. Ignition should now occur. After proving the pilot  
flame, and a 30 second delay, the gas control relay and the burner indicator lamp are  
energized.  
TEMPERATURE  
CONTROL  
Closing the Fan Switch supplies (through the Step Down Transformer) 120 VAC to  
the Temperature Control Board. The Temperature Potentiometer is adjusted to  
desired temperature. The Thermocouple will provide varying millivolts to the  
Temperature Controller. The Temperature Controller supplies 120 VAC to the  
Solenoid Valve at intermittent intervals to maintain desired temperature. (An  
electronic flame monitor proves main flame operation in the 1033-1034 models)  
Closing the Oven Fan Switch supplies 120 VAC, through the Power Transformer, to  
the normally open Conveyor Switch. Closing the Conveyor Switch supplies 120 VAC,  
through a 3 AMP Fuse, to the primary of the Conveyor Control Transformer. The  
secondary of this Transformer supplies 10 VAC and 29 VAC to the Conveyor Control.  
The conveyor control supplies voltage pulses to the Conveyor Control. The Conveyor  
Control Potentiometer varies the frequency of these pulses. The motor speed will  
increase or decrease, as the frequency of the pulses increase or decrease  
respectively.  
Closing the Oven Fan Switch supplies 120 VAC, through the Power Transformer, to  
the primary of the Time/Temp. Transformer. The secondary output of the  
Transformers, 12.5 to 15 VAC with a center tap, is supplies to terminals 1, 2, and of  
the Time/Temp. Display. The display works on a balanced input, and the center tap  
voltage to each leg must be 1/2 the total reading.The speed side of the Time/Temp.  
Display is supplied, by the Conveyor Control, with the frequency of the pulses to the  
Conveyor Motor. This frequency is converted by the Time/Temp. Display into a read  
out of minutes and seconds. NOTE: The Conveyor Control uses a sensor and  
magnet, mounted on the Conveyor Motor that senses when the motor is not turning. If  
the motor is not turning, the Time/Temp Display will show --:-- in the window. The  
temperature portion of the display uses a Thermistor Probe to sense oven  
temperature. The Thermistor outputs a resistance proportional to oven temperature.  
This resistance is then converted by the Display into a temperature reading.  
CONVEYOR DRIVE  
TIME TEMP DISPLAY  
OR:  
The temperature portion of the display uses a "J" type thermocouple to measure oven  
temperature. The thermocouple generates D.C. millivolts proportional to oven  
temperature. This millivolt reading is then converted by the display into a temperature  
reading.  
Impinger I -–1000 Series Service Manual - International  
9
SEQUENCE OF OPERATIONS 1042 / 1043 / 1242 / 1243  
MODEL 1042 - 240V - 50HZ - NATURAL GAS  
MODEL 1043 - 240V - 50HZ - L.P. GAS  
MODEL 1242 - 240V - 50HZ - NATURAL GAS/DUAL BELT  
MODEL 1243 - 240V - 50HZ - L.P.GAS/DUAL BELT  
POWER SUPPLY  
Electrical Power to be supplied to the Oven by a three conductor service.  
Black conductor is Hot  
Red conductor is Neutral  
Green conductor is Ground  
CONTROL BOX AUTO  
COOL DOWN  
When the temperature in the Control Box reaches 120°F + 3°, the Cooling Fan  
Thermostat will switch power to the Control Box Cooling Fan. The Thermostat will  
interrupt power to the Cooling Fan when the Control Box temperature falls to 100°F +  
3°.  
MAIN FAN CIRCUIT  
Electrical power is permanently supplied to the normally open contacts of the Double  
Pole Main Fan Relay, the Cooling Fan Thermostat, the normally open Double Pole  
Main Fan Switch, and the normally open Cool Down Thermostat (thermostat closes  
at 160°F and opens at 140°F). Closing the Main Fan Switch supplies 240 VAC  
through a 3A Fuse to the primary of the control circuit Step Down Transformer. The  
Transformer steps the voltage down to 120 VAC for the control circuit. 120 VAC is  
supplied to the coil of the Double Pole Main Fan Relay. The coil of the relay is  
energized. The normally open contacts now close, energizing the Main Fan Motor  
through one 10A Fuse. Closing the Fan Switch also supplies power to the Cooling  
Fan, the 12.6 VAC Transformer the Burner and Conveyor Switches.  
TRANSFORMER (12.6  
VAC)  
Upon closure of the Fan Switch, 120 VAC is supplied to the primary of the 12.6 VAC  
Transformer. The Transformer steps the voltage down to 12.6 VAC (normally 13 to  
14 VAC) with a center tap, and supplies power to the Time/Temp Display. The  
voltage from each leg of the Transformer's secondary to the center tap should be  
one half of the secondary voltage.  
BURNER CIRCUIT  
Closing the Fan Switch and the normally open Burner Switch supplies 120 VAC  
through the Air Pressure Switch, to the Temperature Control Board, the normally  
open contacts of the Burner Motor Relay (Burner Motor Relay discontinued after S/N  
14791) and the primary of the 24 VAC Transformer. The transformer's secondary  
supplies 24 VAC to the burner motor relay coil (the normally open contacts close  
within 30 seconds), and the normally open Centrifugal Switch. When the relay  
contacts close, the Burner Blower Motor is energized. As this motor reaches approx.  
1,600 R.P.M its internal centrifugal switch closes, supplying 24 VAC to the Gas  
Control Valve. When the Gas Control Valve is supplied with 24 VAC, the pilot valve  
is energized, and the igniter circuit is energized. Ignition should now occur. After pilot  
flame is proven, the Main Gas Valve is energized. The Burner Indicator Light is also  
energized.  
TEMPERATURE  
CONTROL  
Closing the Fan Switch and Burner Switch supplies 120 VAC to the Temperature  
Control Board. The 1K or 1000 ohm Temperature Potentiometer is adjusted to  
desired temperature. The Thermocouple will provide varying millivolts to the  
Temperature Controller. The Temperature Controller supplies 120 VAC to the  
Solenoid Valve at intermittent intervals to maintain desired temperature.  
Closing the fan switch and the normally open conveyor switch supplies 120 VAC to  
the Motor Control Board. AC volts are converted to DC volts and are supplied to the  
Conveyor Motor at terminals A+ and A-. Adjustment of the Speed Control  
Potentiometer (5,000 ohm 10 turn ) will change resistance at terminals P1, P2, and  
P3 varying the DC voltage to the motor. The speed of the conveyor motor will  
increase or decrease as the DC voltage from the board increases or decreases  
respectively. As the motor turns, it drives both the reducer gearbox and the tach.  
generator. The tach. generator is a DC voltage generator which supplies a voltage to  
the DC motor control board and is used as a reference for maintaining a constant  
conveyor speed.  
CONVEYOR DRIVE  
(S/N Q14790 & Below,  
1200 series  
S/N Q14973 & Below,  
1000 series)  
(S/N Q14791 & Above,  
1200 series  
S/N Q14974 & Above,  
1000 series refer to  
Pg. 9)  
10  
Impinger I -–1000 Series Service Manual - International  
TIME/TEMP  
The Time/Temp. Display is energized when the Fan Switch is closed, supplying 120  
DISPLAY(S/N Q14790 & VAC to the primary of the12.6 volt Transformer. The secondary output of the  
Below, 1200 series S/N  
Q14973 & Below, 1000  
series)  
transformer, normally 13 to 14 VAC (depending on input), with a center tap, is  
supplied to terminals 1,2, and 3 of the Time/Temp. Display. The center tap is  
terminal 2. The display works on a balanced input and center tap voltage to each leg  
must be 1/2 the total reading.  
(S/N Q14791 & Above,  
The speed side of the Time/Temp. Display uses a slotted disc (cemented to tach.  
1200 series S/N Q14974 coupling) to break the infra-red light beam of the optical switch (mounted on gear  
& Above,  
1000 series refer to Pg.  
9)  
motor) producing electrical pulses that are transmitted to the display. The display  
converts these pulses into a read-out of minutes and seconds. The temperature  
portion of the display uses a Thermistor Probe to sense oven temperature. The  
thermistor outputs a resistance proportional to the oven temperature. This resistance  
is then converted by the display into a temperature reading.  
Impinger I -–1000 Series Service Manual - International  
11  
SCHEMATIC / 1002, 1003  
12  
Impinger I -–1000 Series Service Manual - International  
SCHEMATIC / 1006 TO SERIAL NUMBERS Q14279  
Impinger I -–1000 Series Service Manual - International  
13  
SCHEMATIC / 1028, 1029, S/N Q19071 & BELOW  
14  
Impinger I -–1000 Series Service Manual - International  
SCHEMATIC / 1028, 1029, S/N Q19078 & ABOVE  
Impinger I -–1000 Series Service Manual - International  
15  
SCHEMATIC / 1030, TO S/N Q17170  
16  
Impinger I -–1000 Series Service Manual - International  
SCHEMATIC / 1030, S/N Q17171 & ABOVE  
Impinger I -–1000 Series Service Manual - International  
17  
SCHEMATIC / 1032. S/N Q19077 & BELOW  
18  
Impinger I -–1000 Series Service Manual - International  
SCHEMATIC / 1032, S/N Q19078 & ABOVE  
Impinger I -–1000 Series Service Manual - International  
19  
SCHEMATIC / 1033, 1034, 1046, 1047  
20  
Impinger I -–1000 Series Service Manual - International  
SCHEMATIC / 1042, 1043, S/N Q14279 & BELOW  
Impinger I -–1000 Series Service Manual - International  
21  
SCHEMATIC / 1042, 1043, S/N Q14280 & ABOVE  
22  
Impinger I -–1000 Series Service Manual - International  
SCHEMATIC / 1228. 1229, S/N Q14790 & BELOW  
Impinger I -–1000 Series Service Manual - International  
23  
SCHEMATIC / 1228, 1229, S/N Q14791 & ABOVE  
24  
Impinger I -–1000 Series Service Manual - International  
SCHEMATIC / 1242, 1243  
Impinger I -–1000 Series Service Manual - International  
25  
TROUBLESHOOTING GUIDE 1000 & 1200 / GAS OVENS  
SYMPTOM  
Oven fan will not run  
POSSIBLE CAUSE  
Incoming Power Supply  
EVALUATION  
Check breakers/ Reset if required / Call Power Co.  
if needed.  
For some export ovens, there is a control circuit  
step-down transformer. This transformer steps  
down supply voltage to 120 VAC. If main fan will  
not run, the secondary of this transformer must be  
checked for 120 VAC output. Check specific oven  
model schematic for circuit location.  
Check and/or Replace  
NOTE:  
(Export Ovens)  
Oven Fan Fuse(s)  
Fuse Holder  
Fan Switch  
Check and/or Replace  
Check continuity between switch terminals.  
Check continuity to 120 VAC coil. Check for power  
to relay coil (120 VAC). Check for 208/240 VAC to  
relay terminals. Visually check for contact pull-in.  
Check for opens, shorts, or grounds. WITH  
POWER OFF: Turn Fan Blade to check for locked  
rotor.  
Main Relay  
Fan Motor  
Capacitor  
Cool Down Thermostat  
Check for opens, shorts, or grounds.  
Check cool down thermostat (thermostat closes at  
160°F and opens at 140°F). Check for power (120  
VAC) at cool down thermostat. With the cool down  
thermostat pre-heated, check for continuity. If  
switch is open, replace.  
No Main Fan Cool  
Down  
No Control Box  
Main Fan Relay  
Check for power to Main Fan Relay. Visually check  
Cooling(For ovens  
equipped with Control  
Box Cooling Fan)  
for contact pull in.  
(Export Ovens)  
Axial Cooling Fan  
(For ovens equipped with a control circuit step-  
down transformer, the supply voltage for the  
cooling fan is 240 VAC.)  
WITH POWER OFF: check for locked rotor. Check  
for power (120 VAC) to cooling fan. If 120 VAC is  
present at the fan motor and the fan does not run,  
replace fan assembly.  
NOTE:  
No automatic control  
box cooling (For ovens  
equipped with control  
box cooling fan)  
Incoming Power Supply  
Cooling Fan Thermostat  
Check breakers/Reset if needed. Check for  
incoming power (120 VAC)at cooling fan  
thermostat.  
Check cooling fan thermostat (thermostat closes at  
120°F and opens at 100°F). With cooling fan  
thermostat pre-heated, check for continuity. If  
switch is open, replace.  
Axial Cooling Fan  
Check for 120 VAC to cooling fan, if present and  
fan does not run, replace fan.  
Control box cooling fan Cooling Fan Thermostat  
continues to run  
See "Cooling Fan Thermostat"  
Transformer, 24 VAC  
Check for 120 VAC to primary Check for adequate gas supply to oven.  
of transformer. Check for 24  
VAC from secondary of  
transformer. If there is  
primary voltage, but no  
secondary voltage, replace  
transformer.  
Manual Gas Shut-off Valve  
Fan Switch  
Main Oven Fan  
Check to see that manual shut-off valve is open.  
Check to see that fan switch is "on".  
Check if main oven fan is operating. If not, refer to  
"Oven fan will not run". Page 26.  
26  
Impinger I -–1000 Series Service Manual - International  
Burner Switch  
Check for 120 VAC to neutral on both sides of  
switch. If switch is closed and 120 VAC is present  
on one side only, replace the switch.  
Air Pressure Switch  
Check for 120 VAC on both sides of switch. If  
voltage present on one side only, check for air tube  
blockage. Adjust air switch. If above fails, replace  
air pressure switch.  
NOTE:  
(Model 1004 & 1005)  
For oven models 1004 and 1005, there is a 1 Amp  
fuse located between the 24 VAC output from the  
transformer and the coil of the burner motor relay. If  
there is 24 VAC output from the transformer, but no  
burner motor relay action, check fuse and fuse  
holder. Replace as necessary.  
Burner Motor Relay  
Burner Blower Motor  
Delete burner motor relay refer to page 55.  
Check for 120 VAC supply to burner blower motor.  
If 120 VAC is present and motor does not run,  
replace motor. WITH POWER OFF: turn blower  
wheel to check for locked rotor.  
Centrifugal Switch of Burner  
Blower Motor  
Check for 24 VAC output from secondary of  
transformer. If voltage is present, check for 24 VAC  
at pin 6 and the ground bar on ignition control and  
valve assembly. If the burner blower motor is  
running and there is no voltage at pin 6 and the  
ground bar on the ignition control valve, replace the  
burner blower motor.  
For ovens with  
Johnson Controls  
Ignition Control  
Ignition Control and Valve  
Assembly  
Check for 24 VAC supply to the ignition control and  
valve assembly at pin 6 and the ground bar. If  
voltage is present, check for 24 VAC across pin #1  
and the ground bar (pilot valve). If voltage is not  
present, replace electronic control package. If the  
pilot valve is energized, check to see that the high  
voltage ignitor circuit is also energized. To check,  
disconnect the ignitor lead from the bottom of  
ignition control. Place female terminal of ignitor  
lead approximately 1/8" from terminal post on  
ignition control. Spark should jump the 1/8" gap. If  
no spark is present, replace ignition control.  
If the ignition control is supplied with 24 VAC, and  
the pilot valve (internal to valve assembly) and  
ignitor circuits are energized, visually check for pilot  
flame. This may be done by opening the small  
inspection door on the end of the burner, or by  
opening the main oven door and looking under the  
lower finger housings on the right side of the oven.  
If no pilot flame is visible, check the following.  
Check to see that pilot shut-off valve is open (shut-  
off valve is located between ignition control and  
valve assembly and burner.)  
Check for gas pressure at pilot tube. Disconnect  
pilot tube at burner and connect manometer to pilot  
tube. If no gas pressure is present, check for  
blockage in pilot tube or pilot shut-off valve. If these  
are clear, and there is gas supplied to the oven,  
replace the ignition control and valve assembly.  
If there is gas pressure at the pilot tube, check the  
pilot orifice for obstructions. Replace as need  
Check the burner ignitor head for any obstructions,  
also check for frayed or broken wire, any type of  
damage to spark gap (.100 in. 2.5 m.m.) If there is  
visible damage, replace ignitor assembly.  
(For ovens with  
Honeywell Ignition  
control, See Pg. 28)  
No Pilot  
Pilot Shut-off Valve  
Pilot Tube  
Pilot Orifice  
Burner Ignitor  
Impinger I -–1000 Series Service Manual - International  
27  
Pilot flame but no main Flame Sensor  
flame  
(There should be a visible pilot flame at this time.)  
To check for proper flame sensor operation,  
connect a digital multimeter (capable of measuring  
D. C. microamperes) in series between the flame  
sensor wire (normally connected to terminal #4)  
and terminal #4. NOTE: This is a current  
measurement and the meter must be connected in  
series. This procedure is for checking the pilot  
flame only. Remove main valve wire (Red) from  
terminal #3 on ignition control. With a visible pilot  
flame, the current readings should be as follows:  
Johnson G-65 control, 0.2 micro amp. D.C.  
minimum/Johnson G-60 control, 0.7 micro amp.  
D.C. minimum. If these values are not achieved,  
replace flame sensor. Also check for any type of  
damage to flame sensor wire and connections.  
If there is a pilot flame, and there is sufficient micro  
amp. current at terminal #4, check for 24 VAC  
that the main valve (internal to valve assembly) has  
opened. Connect a manometer to the manifold gas  
pressure tap located on the back side of the ignition  
control and valve assembly. If no gas is present,  
replace ignition control and valve assembly.  
Check for 24 VAC output from secondary of  
transformer. If voltage is present, check for 24 VAC  
at terminals marked "24V" and "24V gnd" on  
Ignition Control. If the Burner Blower Motor is  
running and there is no voltage at terminals 24V  
and 24V gnd on the ignition control, replace the  
Burner Blower Motor.  
Ignition Control and Valve  
Assembly  
For ovens with  
Honeywell ignition  
control  
Centrifugal Switch of Burner  
Blower Motor  
NOTE:  
These Ignition Controls have a 30 second pre-  
purge(Delay) and a 15 second lock-out time – The  
Ignition Control will try for ignition for 15 seconds  
and then shut-off. To Re-try for ignition, turn off  
burner switch, wait 30 seconds and re-try ignition.  
Check for 24 VAC supply to ignition control at  
terminals "24V" and "24V gnd". If voltage is  
present, check for 24V at terminal "P.V. (Pilot  
Valve) and "gnd". If voltage is not present, replace  
Ignition Control. If the pilot valve is energized,  
check to see that the high voltage ignitor circuit is  
also energized. To check, disconnect the ignitor  
lead from the ignition control. Place the terminal of  
ignitor lead approximately 1/8" from terminal post  
on Ignition Control. Spark should jump the 1/8"  
gap. If no spark is present, replace ignition control.  
If the ignition control is supplied with 24 VAC and  
the pilot valve (in gas valve) and ignitor circuits are  
energized, visually check for pilot flame. This may  
be done by opening the small inspection door on  
the end of the burner, or by opening the main oven  
door and looking under the lower finger housing in  
the right side of the oven.  
Ignition Control  
No Pilot  
Pilot Shut-off Valve  
Pilot Tube  
If no pilot flame is visible, check to see that the pilot  
shut-off valve is open (shut-off valve is located  
between gas valve and burner).  
Check for gas pressure at pilot tube. Disconnect  
pilot tube at burner and connect manometer to pilot  
tube. If no gas pressure is present, check for  
blockage in pilot tube or pilot shut-off valve.  
If there is gas pressure at the pilot tube, check the  
pilot orifice for obstructions. Replace as needed.  
Pilot Orifice  
28  
Impinger I -–1000 Series Service Manual - International  
Burner Ignitor  
Check the burner ignitor head for any obstructions,  
also check for frayed or broken wire, any type of  
damage to spark gap (.100 in. 2.5 mm) If there is  
visible damage, replace ignitor assembly.  
(There should be a visible pilot flame at this time).  
NOTE: The Honeywell Ignition Control uses the  
spark ignitor as the flame sensor. If spark  
continues, check for proper ground connections at  
Ignition Control. Check pilot orifice for any partial  
blockage. If the above checks OK, replace ignition  
control. If spark stops when pilot is lit, check for 24  
VAC across M.V. - M.V/ P.V. terminals, if voltage is  
not present, replace ignition control. If voltage is  
present at terminals M.V. - M.V./P.V., the indicator  
light on the control panel should be on, verify that  
the main valve has opened, connect manometer to  
manifold gas pressure tap (located on the back  
side of the gas valve). If no gas is present, replace  
gas valve.  
Pilot flame but no main Spark Ignitor (Flame Sensor)  
flame  
Red Indicator Light is  
on, but no main  
flame(For ovens with  
mechanical  
Temperature Control Valve  
(Robert Shaw)  
Main Orifice  
Check for gas supply at temperaturecontrol. Check  
for temperature control set above 300°F.  
Check for blockage of main orifice. If there is no  
blockage to the main orifice, replace the  
temperature control.  
thermostat)  
(For ovens with  
Temperature Control  
Potentiometer  
Check for 120 VAC across L1 and L2on  
Electronic  
temperature control board. Potentiometer (1000  
ohm,1 turn) WITH POWER OFF: check ohms  
across red and black leads, the ohm reading  
should be 0 to1000 ohms as the dial is turned.  
From green to red, the reading should be 1000  
ohms steady throughout the full turn of the dial.  
Temperature Control)  
NOTE: Ovens S/N Q18037 and above, the potentiometer is internal to temperature control. Proceed to next  
component.  
Thermocouple Probe  
Remove thermocouple leads from the temperature  
control board, and measure the millivolt output of  
these leads. Refer to chart on page 59 in the  
adjustment section for proper readings.  
Temperature Control  
Solenoid Valve  
Turn temperature control dial to full "on" position.  
Measure for 120 VAC across terminals "N.O." and  
"L2", if voltage is not present; replace control.  
If voltage is present at terminals "N.O." and "L2",  
check for voltage at solenoid valve. If voltage is  
present, listen for valve to open and close. Also,  
check for opens and shorts in coil. If solenoid valve  
is defective, replace  
Intermittent Heating  
Both the main fan motor and burner blower motor  
are equipped with thermo-protection and will cease  
to operate when not cooled properly. This can  
cause the units to cycle on and off intermittently.  
Also, most of the problems listed under "oven will  
not heat" can cause intermittent failures.  
For continuing intermittent problems, a series of test lights may be made and installed in  
the ovens. The lights will allow the customer to advise the service technician a trouble code when  
the oven fails.  
The lights should be connected in the following manner:  
Light#l attached in 120VAC line after Air Pressure Switch.  
Light#2 attached after 120VAC contacts of Burner Motor Relay (or, refer to Bulletin #028  
for Relay Removal).  
Light#3 in 24VAC Burner Transformer Secondary.  
Impinger I -–1000 Series Service Manual - International  
29  
Light#4 in 24VAC at terminal #6 of Johnson control valve or "24V" on Honeywell Control.  
Light#5 in 24VAC at terminal #1 of Johnson control valve or "PV" on Honeywell Control.  
Light#6 in 24VAC at terminal #3 of Johnson control valve or "MV" on Honeywell Control.  
CODE:  
All lights off - lights of main power, main fan off, air pressure switch out.  
1 on 2 off 3 on 4 off 5 off 6 off  
1 on 2 on 3 on 4 off 5 off 6 off  
1 on 2 on 3 on 4 on 5 off 6 off  
- Burner Motor Relay bad.  
- Burner Motor Centrifugal Switch bad.  
- Ignition Control bad.  
1 on 2 on 3 on 4 on 5 on 6 off - Pilot Shield missing or warped, Flame Sensor bad, Pilot  
- Orifice plugged, or Gas Valve bad.  
1 on 2 on 3 on 4 on 5 on 6 on  
- Unit still not working Main Orifice plugged, Gas Valve bad,  
- Temperature Control bad.  
- However, Main Orifice would not be intermittent problem.  
30  
Impinger I -–1000 Series Service Manual - International  
Model 1030 - 1031  
SYMPTION  
POSSIBLE CAUSE  
EVUALATION  
Gas Supply Manual Gas  
Check for adequate gas supply to oven. Check to  
see that manual shut-off valve is open.  
Check to see that the fan switch is on  
Check if main oven fan is operating. If not, refer to  
"Oven fan will not run."  
Oven will not heat  
Shut-Off Valve  
Fan Switch  
Main Oven Fan  
Burner Switch  
Check for 220 VAC to neutral on both sides of  
switch. If switch is closed, and 220 VAC is present  
on one side only, replace switch .  
Gas Pressure Switch (internal Check for 220 VAC to neutral on both sides of  
to gas valve)  
switch. If voltage is present on one side of switch  
only, check the following. Check for proper gas  
pressure supply to gas valve. (Marked on oven  
spec plate) Check for proper adjustment of gas  
pressure switch. Should be set at 8.8 Nat., 23 L.P.  
2.0 Town Gas. Check gas filter in gas valve for  
blockage or damage. (See Adjustment Section for  
location) If the above checks okay, but switch still  
not closed, replace gas valve.  
Air Pressure Switch  
Hi-Limit Thermostat  
Check for 220 VAC on both side of switch. If  
voltage present on one side only, check for air tube  
blockage or misalignment adjust air switch. If above  
fails, replace air pressure switch.  
Terminals are normally closed. If open, reset and  
test oven for proper operation. If thermostat will not  
hold for maximum oven temperature, and oven is  
not exceeding temperature dial setting, check for  
proper location of capillary bulb in its spring holder.  
If above checks okay, replace hi-limit thermostat.  
Check for 220 VAC supply to ignition control at pin  
#1 and neutral. If voltage is not present, retrace  
wiring back to hi-limit thermostat. Check for 220  
VAC at pin #6 to neutral. (Power to burner motor  
relay). If voltage present, proceed. If no voltage is  
present, wait 30 seconds and check reset button. If  
above fails, replace ignition control.  
Ignition Control  
Burner Motor Relay  
Burner Blower Motor  
Check for continuity to 220 VAC coil. Check for  
power to relay coil (220 VAC). Check for 120 VAC  
to relay contact terminals. Visually check for  
contact pull-in.  
Check for 120 VAC supply to burner blower motor.  
WITH POWER OFF: turn blower wheel to check for  
locked rotor. If 120 VAC is present and motor does  
not run, replace motor.  
Burner Blower Motor Air  
Pressure Switch  
Check for 220 VAC switching to pin "N.O." as the  
air pressure switch closes. Connect a temporary  
jumper wire (for testing purposes only) from pin "C"  
to pin "N.O." on ignition control (to bypass air  
switch). NOTE: For Honeywell control only. Check  
for air tube blockage or misalignment, adjust air  
pressure switch. If the above fails, replace air  
pressure switch.  
Spark Generator  
After a pre-purge time of 30 to 60 seconds after  
blower motor starts, check for 220 VAC to spark  
generator. If voltage is not present, check reset  
button on ignition control. If voltage is still not  
present, replace ignition control. f voltage is  
present, visually check for spark at ignitor head.  
Impinger I -–1000 Series Service Manual - International  
31  
Ignitor/Sensor Assembly  
Check for visible damage to ignitor/ sensor  
assembly. If there is no visible damage to the  
components, and no spark, replace the spark  
generator. If there is visible damage to the Ignitor  
sensor assembly, replace it. Also check for frayed  
or damaged wires in burner tube.  
Gas Valve  
Check for 220 VAC supply to gas valve. If no  
voltage present, check reset button on ignition  
control, check all connections for tightness. If there  
still is no voltage at gas valve, replace  
No Pilot  
Solenoid Valve  
Flame Sensor  
If all above are operating properly, but there is no  
pilot flame, check for any obstructions in bypass  
orifice (drilled port through wall inside solenoid  
valve).  
Pilot flame, but burner  
will not stay ignited  
(There should be a visible pilot flame at this time.)  
To check for flame sensor operation, connect a  
digital multimeter (capable of measuring D. C.  
micro amperes) between the flame sensor wire and  
terminal "F" on the ignition control or in flame  
sensor lead for Landis & Gyr. NOTE: this is a  
current measurement and the meter must be  
connected in series. Proper current readings  
should be between 2 and 4 micro Amp. D.C. for  
Honeywell, 3 micro amp for Landis & Gyr minimum.  
If these readings are not achieved, replace  
ignitor/sensor assembly. Also check for any type of  
damage to flame sensor wire and connections.  
Ignition Control If there is sufficient flame sensor  
current, but the burner will not remain ignited,  
check reset button on ignition control, if all above  
are okay, replace ignition control.  
Red indicator light is  
on but no main flame  
Temperature Control  
Thermocouple Probe  
Check for 120 VAC across L1 and L2 on  
temperature control board. If no voltage present,  
retrace wiring back to power supply. Turn the  
temperature adjustment knob to the maximum  
temperature position and check for 120 VAC at the  
load terminal to neutral. If 120 VAC is not present,  
proceed as follows: If 120 VAC is present and unit  
is not heating, see "Solenoid Valve."  
Remove thermocouple leads from the temperature  
control board and measure the millivolt output of  
these leads. Refer to chart on page 59 for proper  
readings.  
Temperature Control  
Potentiometer  
WITH POWER OFF: remove the leads from the  
temperature control board and measure ohms from  
black and white leads. The ohm reading should be  
0 to 2.5K ohms as the dial is turned through its full  
rotation. From black to red leads the reading should  
be 2.5K ohms and remain steady throughout the  
full rotation of the dial. If the thermocouple probe  
and the control potentiometer check good, then the  
problem is usually with the temperature control  
board.  
Solenoid Valve  
If output voltage is present at temperature control  
board, check for voltage at solenoid valve. If  
voltage is present, listen for valve to open and  
close. Also check for opens and shorts in coil.  
Replace as needed.  
32  
Impinger I -–1000 Series Service Manual - International  
Intermittent heating  
As Follows  
Both the main fan motor and burner blower motor  
are equipped with thermal protection and will cease  
to operate if overheating occurs. This can cause  
the units to cycle on and off intermittently. This may  
be caused by improper ventilation. Also most of the  
problems listed under "oven will not heat" can  
cause intermittent failure.  
Conveyor will not run  
(S/N 100-4389)  
Voltage Supply  
3 Amp Fuse  
Check incoming voltage supply at line 1 to neutral.  
There should be a voltage reading of 120 VAC. If  
not present, check breakers.  
This conveyor fuse is located on the front panel.  
Replace if defective.  
Fuse Holder Conveyor Switch Check and/or Replace. Same procedure as for fan  
switch.  
D. C. Motor Control Board  
Check for 120 VAC input to D. C. control board  
across L1 and L2. Check the 3 amp fuse on the D.  
C control board. Check for D.C. voltage at terminal  
F1 and F2. Voltage should be 100 VDC 10  
steady. If this voltage is not present, replace D. C.  
control board. Check for D. C. voltage output to the  
motor across terminals A1 and A2 (this voltage  
should be approx. 125 VDC at maximum conveyor  
motor speed).  
Speed Control Potentiometer  
This is a 0 to 400 ohm or 0 to 500 ohm, 10-turn  
potentiometer. WITH POWER OFF: remove the  
red, white, and black leads from terminals S1, S2,  
S3. With a digital multimeter, check the ohm  
reading across the red to black leads. This ohm  
reading should be a steady 400-ohm, or 500-ohm,  
through the entire 10-turn rotation of the  
potentiometer. Red to white, should be 0-400 or 0-  
500 ohms as the pot. is rotated. Check for shorts or  
opens or unsteady, ohm reading, if potentiometer is  
defective, replace. If the potentiometer checks OK,  
and  
there is no output at terminals A1 and A2, replace  
the D.C. control board.  
Reversing Switch  
If there is D. C. voltage output from the motor  
control board, but the conveyor drive motor is not  
running, check the D.P.D.T. reversing switch.  
Check the conveyor drive sprocket for tightness.  
Disconnect the motor, check the red and black  
motor leads for opens, shorts or grounds. Check  
Conveyor Drive Motor  
the brushes for excessive or  
abnormal wear.  
Replace as needed. Reconnect motor. Test for  
operation. If motor does not run, replace.  
Check incoming voltage supply at line 1 to neutral.  
There should be a voltage reading of 120 VAC. If  
not present, check breakers.  
This conveyor fuse is located on the front panel.  
Replace if defective.  
Conveyor will not run  
(S/N 4390 to Q14974  
1000 Series  
S/N 4390-Q14790  
1200 Series)  
Voltage Supply  
3 Amp Fuse  
Fuseholder  
Fan Switch  
Conveyor Switch  
(Dual Belt Ovens)  
Check and/or Replace  
See procedure for checking on page 26.  
Same procedure as for fan switch.  
Dual belt ovens utilize 2 complete independent  
conveyor drive systems. The trouble shooting  
procedures are the same as single belt ovens,  
except that the dual belt ovens use one each of the  
following: one "A" DC. control board and one "B" D.  
C. control board.  
NOTE:  
Impinger I -–1000 Series Service Manual - International  
33  
Speed Adjustment  
Potentiometer  
This is a 0 to 5 K ohm, 10 turn potentiometer. With  
power off, remove the red, black and white pot  
leads from the motor control board at terminals  
P1,P2, and P3. With a digital multimeter, check the  
ohm reading across the red lead (P3) to the black  
lead (P1). This reading should be 5 K ohms 5%  
as the pot is rotated from low to high. Place the  
meter leads on the red lead (P3) and on the white  
lead (P2). Rotating the pot. slowly, from low to high,  
the meter reading should show an even transition  
from 0 to 5 K ohms 5%. There should be no dead  
or open spots through out the 10 turns of the pot.  
Check all three leads to ground. There should be  
no continuity to ground. If any of the above checks  
fail, replace the pot.  
DC Motor Control Board  
Check for 120 VAC input to the control board at  
terminals L1 and L2. If not present, check the  
conveyor switch and wiring back to 3 amp fuse and  
then back to power source if necessary. If 120 VAC  
is present at L1 and L2, check the VDC output at  
terminals A+ and A-. If a DC voltage is not present,  
check the 4 amp and the 1 amp fuses on the  
control board. If 120 VAC is present at terminals L1  
and L2, but DC voltage is not present at A+ and A-,  
providing the 1 amp and 4 amp fuses are good,  
replace the board. If DC voltage is present at A+  
and A-, but motor does not run, check gear motor  
as follows.  
Conveyor Gear Motor  
If DC voltage is present at A+ and A- and the motor  
does not run, first check the mini breaker and then  
the conveyor. Refer to the next possible cause.  
Check the leads to the motor for evidence of any  
shorts or opens, and each lead to ground. If the  
motor fails the above tests, replace motor. Remove  
dust cover from the top of the motor and rotate  
motor shaft to determine if there is a locked rotor or  
a locked gear box (use care so encoder disc is not  
damaged).  
Conveyor  
Check for any mechanical miss-alignment or  
improper adjustment. Also check for worn bearings.  
The Installation and Operations Manual shows  
proper conveyor belt adjustment. A conveyor belt  
that is over tightened will cause excessive bearing  
wear and sometimes, irregular speed.  
Conveyor speed  
varying or intermittent  
Power Supply  
Check power supply at the DC control board for the  
120 VAC at board terminals L1 and L2. If voltage is  
not present, check main circuit breakers.  
34  
Impinger I -–1000 Series Service Manual - International  
Tach generator and DC Motor With the power to the DC motor control board  
Control Board  
turned off, remove the leads from terminals T1 and  
T2. Place the test leads of a digital meter on the  
tach leads, turn power on, and the meter reading  
should be approximately 30 to 35 VDC. This  
reading should be steady within 0.2 to 0.3 VDC. If  
this reading is not within 0.5 VDC, place the test  
meter probes on terminals A+ and A-. The meter  
reading should be approximately 150 to 160 VDC  
and steady within approximately 2 VDC. If the tach.  
voltage is unsteady, and the board output is steady,  
check the coupling for loose set screws or any type  
of damage. If the coupling checks good, the tach. is  
usually bad. If the board voltage output is unsteady  
beyond limits, then the board is probably bad.  
Always check the speed pot. be sure it is okay  
before changing a board or tach. This test is not  
always 100% accurate as this test is not performed  
at operating speeds. However, this test is the best  
method currently available. Readjustment should  
always be attempted at least once before  
replacement. See procedure for board adjustment  
on page 65.  
If the DC control board is steadythen the problem  
may be the motor or gearbox. Check the brushes in  
the motor for excessive arching and/or unusual  
wear. Check the motor and gearbox from  
instruction located on page 34 under "possible  
cause" listing "Conveyor gear motor".  
Check incoming voltage supply at Line 1 to neutral.  
There should be a voltage reading of 120 VAC.  
DC Gear motor  
Voltage Supply  
Conveyor will not run  
S/N Q14974 & up1000  
Series S/N Q14791 &  
up 1200 Series  
Fan Switch  
Conveyor Switch  
See procedure for checking on page 26.  
Check for 120 VAC to conveyor Switch. If no  
voltage is present, trace wiring back to the fan  
switch. WITH POWER OFF: Check continuity  
between switch terminals.  
Conveyor Fuse (3A)  
Fuseholder  
Conveyor Control (Stepper)  
Transformer  
Check, replace if necessary.  
Check, replace if necessary.  
Check for 120 VAC supply to primary of  
transformer, if voltage is not present, trace wiring  
back to the fuse holder. If voltage is present, check  
for out-put voltage from the transformer secondary.  
NOTE: this control transformer outputs (2)  
secondary voltages Red Leads 29 VAC Brown  
Leads 10 VAC. If BOTH secondary voltages are  
not present, replace the transformer.  
Impinger I -–1000 Series Service Manual - International  
35  
Speed Adjustment  
Potentiometer  
This is a 0 to 50k ohm, 10 turn potentiometer.  
WITH POWER OFF: remove the 3-pin  
potentiometer cable plug from the motor control  
board. With a digital multimeter, check the ohm  
reading across the red lead to the black lead. This  
reading should be 50k ohms 5% as the  
potentiometer is rotated through its 10-turn rotation.  
Place the meter leads on the red lead and white  
lead. Rotating the potentiometer slowly, from low to  
high, the meter should show an even transition  
from 0 to 50k ohms 5% through the 10-turn  
rotation of the potentiometer. There should be no  
dead or open spots through the 10 turns of the  
potentiometer. Check all three leads to ground.  
There should be no continuity to ground. If any of  
the above checks fail, replace the potentiometer.  
NOTE: if the conveyor drive motor becomes  
jammed or begins to run at an uncontrolled speed,  
the conveyor motor will stop running. To reset, turn  
off the conveyor switch, wait 10 seconds, turn the  
conveyor switch on. If the motor does not run after  
attempting re-set, check for 2 to 29 VAC across the  
motor terminal 1 to 2 and 3 to 5 on the conveyor  
motor control. If voltage is not present at both sets  
of terminals, replace control.  
Conveyor Motor  
(Stepper)Control  
Conveyor Drive  
(Stepper)Motor  
Check the drive sprocket on motor output shaft to  
insure that is tight. Check motor windings;  
measurements should be approximately 2 ohms.  
Terminal 1-5, 2-6, 3-7, 4-8. WITH POWER OFF:  
Turn the motor shaft to check for jammed gear box.  
If motor shaft will not turn, replace conveyor  
drive(stepper) motor.  
Time/Temp Display  
inoperative  
12.6 VAC Power Supply  
Measure the transformer primary for a nominal 120  
VAC input. Measure the secondary voltage output  
which will be 12.5 to 15 VAC normally. Recheck  
secondary output at rear of Time/Temp Display.  
Terminals 1 to 3 should read 12.5 to 15 VAC.  
Terminals 1 to 2 and 2 to 3 should be 1/2 of the  
reading across 1 to 3. If you do not get the above  
secondary readings, replace the transformer. If 120  
VAC primary voltage is not available, refer to the  
schematic and trace circuit for incoming power  
failure. There is a 4-amp fuse in each red  
secondary lead. These may be jumpered (for test  
only) to determine if they are defective or  
intermittent.  
NOTE  
(Dual Belt Ovens)  
Dual belt ovens utilize a double pole double throw  
switch, which allows either of the optical encoders  
to be read from a single Time/Temp. Display.  
Check the switch and replace as needed.  
Temp Display out or  
inaccurate  
NOTE: Time/Temp displays  
use two types of temperature  
sensor, Thermistor Probe - 2  
yellow wires, Thermocouple  
Probe - 1 red wire and 1  
white wire  
Place your pyrometer thermocouple into the center  
between fingers T2 and T3 in the oven. Disconnect  
the yellow tipped thermistor leads from the  
time/temp. terminals 9 and 10. Measure the  
resistance of the thermistor probe.  
Thermistor Probe  
See chart on page 72 for proper resistance  
readings. Inspect the thermistor bulb for its proper  
location in its spring holder. Check for shorts in  
leads where they enter the sensor bulb. Also check  
each thermistor lead for short to ground.  
36  
Impinger I -–1000 Series Service Manual - International  
Thermocouple Probe  
Place your pyrometer thermocouple into the center  
between fingers T2 and T3 in the oven. For ovens  
with Mechanical Measure D.C. millivolts at  
Thermostat terminals 9 and 10 on the time/temp  
display. See thermocouple chart on page 59 for  
proper readings. Replace thermocouple if proper  
readings not achieved. If readings are correct on  
the thermocouple, replace time/temp display.  
Connect temperature meter to thermocouple at  
terminals 9 & 10 on back of the time/temp display.  
(Be sure to maintain proper polarity on  
For ovens with  
Electronic Thermostat  
thermocouple connections.) Compare actual oven  
temperature with the readings at the time/temp  
display. If the temperature readings match,  
recalibrate or replace time/temp display. If the  
readings do not match, replace thermocouple  
probe.  
Erratic time/temp  
display  
If strange or unusual behavior is experienced such  
as a rolling of numbers, lock up at a given number,  
first check for a display circuit lock up. This can be  
caused by a voltage spike or surge. To eliminate  
this condition remove power from the time/temp.  
display by shutting off the main fan switch, or if  
display stays on, (older models) circuit breaker  
interruption may be required. This should eliminate  
the problem. If the problem continues, jumper the  
two fuses in the red wires leading from the 12.6  
VAC transformer to the display. If this does not  
solve the problem, it may be coming in through the  
commercial power lines. Suggest that customer  
contact his power company for evaluation.  
Perform the power supply check, the thermistor  
probe check, and then perform the time/temp  
simulator test. Refer to page 72 for instructions.  
Remember, when using the time/temp simulator,  
remove all the leads from the back of the display  
except the 3 power leads. After completion of this  
test and if reinstalling back into the oven, the dip  
switches must be reset for oven operation.  
Perform all checks as in the above evaluation. If  
the time check is okay, refer to the next section  
optical encoder.  
Temp Display  
inaccurate erratic, or  
inoperative  
Time display  
inaccurate erratic, or  
inoperative(S/N  
Q4615-Q14970) 1000  
Series(S/N Q4615-  
Q14790) 1200 Series  
Optical Encoder  
The above time/temp test should have already  
been performed. Remove dust cover from the  
gearmotor and inspect the coupling and encoder  
disc. The coupling set screws should be tight and  
not slipping on the motor shaft or the tach.  
generator shaft. The encoder disc should be firmly  
attached to the coupling and not warped. Check the  
positioning of the optical encoder disc. The disc  
should not be touching the optical encoder  
assembly and the encoder assembly should be  
mounted so it is squarely facing the coupling shaft.  
This is to allow the infrared beams to be broken by  
the encoder disc. If all this is okay, then replace the  
optical encoder assembly.  
Impinger I -–1000 Series Service Manual - International  
37  
Time Display  
inaccurate, erratic, or  
inoperative(S/N  
Q14975 & Above1000  
Series) (S/N Q14791 &  
Above1200 Series)  
Conveyor Drive  
Perform all check as in the above evaluation. If the  
time check is ok, refer to the next section. Check to  
see if the conveyor drive (stepper) motor is running.  
If motor is not running, refer to "Conveyor will not  
run" on Page 35.  
Check to insure that the magnet (cemented to shaft  
of conveyor drive (stepper) motor) has not been  
damaged, or come loose from motorshaft. Replace  
as needed. Hall Effect Sensor Check for any  
physical damage to Hall Effect sensor(mounted on  
conveyor drive(stepper)motor). Check all wiring  
and connections for damage.  
(Stepper) Motor  
Magnet  
Conveyor Drive  
(Stepper)Control  
Check all connections for tightness or proper  
location and check all wiring for visible damage.  
Replace as needed. If there is still no time display,  
wire in (temporarily) a new conveyor drive control.  
If there is still no time display, reconnect original  
conveyor drive control. Replace Hall Effect Sensor.  
38  
Impinger I -–1000 Series Service Manual - International  
TROUBLESHOOTING GUIDE 1000 & 1200 SERIES / ELECTRIC OVENS  
SYMPTOM  
Oven fan will not run  
POSSIBLE CAUSE  
Incoming Power Supply  
EVALUATION  
Check breakers/Reset if required/ Call Power Co. if  
needed.  
For some export ovens, there is a control circuit  
step-down transformer. This transformer steps  
down supply voltage to 120 VAC. If main fan will  
not run, the secondary of this transformer must be  
checked for 120 VAC output. Check specific oven  
model schematic for circuit location.  
NOTE:  
(Export Ovens)  
Oven Fan Fuse(s)  
Fuse Holder  
Fan Switch  
Check and/or Replace  
Check and/or Replace  
Check continuity between switch terminals.  
Check continuity to 120 VAC coil. Check for power  
to the relay coil (120 VAC). Check for 208/220/240  
VAC to relay terminals. Visually check for contact  
pull-in  
Main Relay  
Fan Motor  
Check for opens, shorts, or grounds.WITH POWER  
OFF: Turn Fan Blade to check for locked rotor.  
Check for opens, shorts, or grounds.  
Capacitor  
No Main Fan Cool  
Down  
Cool Down Thermostat  
Check cool down thermostat (thermostat closes at  
160°F and opens at 140°F). Check for power (120  
VAC) at cool down thermostat. With cool down  
thermostat pre-heated, check for continuity. If  
switch is open, replace.  
No control box cooling Main Fan Relay  
Axial Cooling Fan  
Check for power to main fan relay. Visually check  
for contact pull in.  
WITH POWER OFF: turn the fan blade to check for  
locked rotor. Check for power (120 VAC) to cooling  
fan. If 120 VAC is present at the fan motor and the  
fan does not run, replace fan assembly.  
Check if main oven fan is operating. If not, refer to  
"Oven fan will not run."  
Oven will not heat  
Main Oven Fan  
Heat Switch  
Check for continuity between switch terminals with  
switch on. Replace if defective.  
Air Pressure Switch  
Check for 120 VAC on both sides of switch. If  
voltage present on one side only, check for air tube  
blockage, adjust air switch. If above fails, replace  
air pressure switch.  
Hi Limit Thermostat  
Terminals are normally closed. If open, reset and  
test oven for proper operation. If thermostat will not  
hold for maximum oven temperature, and oven is  
not exceeding temperature dial setting, replace  
thermostat (rated at 190°F).  
NOTE:  
Hi Limit Thermostat  
(Model 1032)  
Terminals are normally closed. If open, reset and  
test oven for proper operation. If thermostat will not  
hold for maximum oven temperature, and oven is  
not exceeding temperature dial setting. Replace the  
thermostat. Check for proper location of sensing  
bulb in its spring holder. If hi-limit is still tripping,  
replace (rated for 368°C).  
3 Amp Temperature Control  
Fuse  
Check and/or Replace  
Fuseholder  
Check and/or replace.  
Impinger I -–1000 Series Service Manual - International  
39  
Temperature Control Board  
Check for 120 VAC input to temperature control  
board. If not present, check wiring from fuse holder  
to temperature control board. Turn the temperature  
adjustment dial to the maximum temperature  
position Check for 120 VAC at coil of mercury  
contactor(s). Next, short the leads of thermocouple  
on the temperature control board, check for 120  
VAC at coil of mercury contactor(s). If voltage is not  
present, replace temperature control board. If  
voltage is present proceed.  
Temperature Control  
Potentiometer  
Potentiometer is 0 to 2.5K ohm. WITH POWER  
OFF: remove the leads from the temperature  
control board terminals 1, 2, and 3 and measure  
ohms from black to white leads. The ohm reading  
should be 0 to approximately 2.5K ohms as the dial  
Remove thermocouple leads from the temperature  
control board, and measure the millivolt output of  
the leads. Refer to chart in adjustment section for  
proper millivolt readings.  
Check for 120 VAC to the contactor coil. If voltage  
is present and contactor will not activate, replace  
the contactor(s). Also check each contactor for  
proper high voltage input and output.  
Thermocouple Probe  
Mercury Contactor(s)  
50 Amp Fuses  
If there is no high voltage input to the mercury  
contactor(s), check the 50 amp fuses and replace if  
necessary.  
Heater Elements  
Check the Amp. draw on each hot leg for proper  
load. Check the specifications plate for rating  
information. If the Amp. draw is low or high, check  
the individual elements for opens, shorts, and  
proper resistance . To check resistance of the  
elements, turn off the power! Remove all leads  
from the elements and use an accurate digital  
VOM. The element resistance should be as follows:  
208V - 9.8 ohms approx. 220V - 10.5 ohms approx.  
240V - 13 ohms approx. If all readings are not  
correct, replace elements as needed.  
Oven heats with switch Mercury Contactor(s)  
off  
The mercury contactor has probably malfunctioned  
in the closed position. If there is no voltage to the  
operating coil, but there is high voltage at the  
contactor output, replace the mercury contactor.  
Check incoming voltage supply at line 1 to neutral.  
There should be a voltage reading of 120 VAC. If  
not present, check breakers.  
Conveyor will not run  
(S/N 100-4389)  
Voltage Supply  
3 Amp Fuse  
This conveyor fuse is located on the front panel.  
Replace if defective.  
Fuse Holder  
Conveyor Switch  
D. C. Motor Control Board  
Check and/or Replace.  
Same procedure as for fan switch.  
Check for 120 VAC input to D. C. control board  
across L1 and L2. Check the 3 amp fuse on the D.  
C. control board. Check for D. C. voltage at  
terminal F1 and F2. Voltage should be 10 VDC +  
10 steady. If this voltage is not present, replace D.  
C. control board. Check for D. C. voltage output to  
the motor across terminals A1 and A2 (this voltage  
should be approx. 125 VDC at maximum conveyor  
motor speed).  
40  
Impinger I -–1000 Series Service Manual - International  
Speed Control Potentiometer  
This is a 0 to 400 ohm or 0 to 500 ohm, 10-turn  
potentiometer. WITH POWER OFF: remove the  
red, white, and black leads from terminals S1, S2,  
S3. With a digital multimeter, check the ohm  
reading across the red to black leads. This ohm  
reading should be a steady 400-ohm, or 500-ohm,  
through the entire 10-turn rotation of the  
potentiometer. Check for shorts or opens or  
unsteady, ohms reading, if potentiometer is  
defective, replace. If the potentiometer checks OK,  
and there is no output at terminals A1 and A2,  
replace the D. C. control board.  
Reversing Switch  
If there is D. C. voltage output from the motor  
control board, but the conveyor drive motor is not  
running, check the D.P.D.T. reversing switch.  
Check the conveyor drive sprocket for tightness.  
Disconnect the motor, check the red and black  
motor leads for opens, shorts or grounds. Check  
the brushes for excessive or abnormal wear.  
Replace as needed. Reconnect motor. Test for  
operation. If motor does not run, replace.  
Check incoming voltage supply at line 1 to neutral.  
There should be a voltage reading of 120 VAC. If  
no present, check breakers. 3 Amp Fuse. This  
conveyor fuse is located on the front panel.  
Replace if defective.  
Conveyor Drive Motor  
Conveyor will not  
run(S/N 4390 to  
Q190771000 Series)  
(S/N 4390-  
Voltage Supply  
Q147901200 Series)  
Fuseholder  
Check and/or Replace.  
Fan Switch  
Conveyor Switch  
(Dual Belt Ovens)  
See procedure for checking on Page 26.  
Same procedure as for fan switch.  
NOTE:  
Dual belt ovens utilize 2 complete independent  
conveyor drive systems. The trouble shooting  
procedures are the same as single belt ovens,  
except that the dual belt ovens use one each of the  
following: one "A" D. C. control board and one "B"  
D. C. control board.  
Speed Adjustment  
Potentiometer  
This is a 0 to 5 K ohm, 10 turn potentiometer With  
power off, remove the red, black and white pot  
leads from the motor control board at terminals P1,  
P2 and P3. With a digital multimeter, check the  
ohm reading across the red lead (P3) to the black  
lead (P1). This reading should be 5 K ohms 5%  
as the pot is rotated from low to high. Place the  
meter leads on the red lead (P3) and on the white  
lead (P2) Rotating the pot. slowly, from low to high,  
the meter reading should show an even transition  
from O to 5 K ohms 5%. There should be  
no dead or open spots through out the 10 turns of  
the pot. Check all three leads to ground. There  
should be no continuity to ground. If any of the  
above checks fail, replace the pot.  
Impinger I -–1000 Series Service Manual - International  
41  
DC Motor Control Board  
Check for 120 VAC input to the control board at  
terminals L1 and L2. If not present, check the  
conveyor switch and wiring back to 3-amp fuse and  
then back to power source if necessary. If 120 VAC  
is present at L1 and L2, check the VDC output at  
terminals A+ and A-. If a DC voltage is not present,  
check the 4 amp and the 1 amp fuses on the  
control board. Also reset and check the mini  
breaker in the armature line to the gearmotor. If  
120 VAC is present at terminals L1 and L2, but DC  
voltage is not present at A+ and A-, providing the 1  
amp and 4 amp fuses are good, replace the board.  
If DC voltage is present at A+ and A-, but motor  
does not run, check gear motor as follows.  
Conveyor Gear Motor  
If DC voltage is present at A+ and A- and the motor  
does not run, first check the mini breaker and then  
the conveyor. Refer to the next possible cause.  
Check the leads to the motor for evidence of any  
shorts or opens, and each lead to ground. If the  
motor fails the above tests, replace motor. Remove  
dust cover from the top of the motor and rotate  
motor shaft to determine if there is a locked rotor or  
a locked gearbox (use care so encoder disc is not  
damaged).  
Conveyor  
Check for any mechanical misalignment or  
improper adjustment. Also check for worn bearings.  
The Installation and Operations Manual shows  
proper conveyor belt adjustment. A conveyor belt  
that is over tightened will cause excessive bearing  
wear and sometimes, irregular speed.  
Conveyor speed  
varying or intermittent  
Power Supply  
Check power supply at the DC control board for the  
120 VAC at board terminals L1 and L2. If voltage is  
not present, check main circuit breakers.  
Tach generator and DC Motor With the power to the DC motor control board  
Control Board  
turned off, remove the leads from terminals T1 and  
T2.Place the test leads of a digital meter on the  
tach leads, turn power on, and the meter reading  
should be approximately 30 to 35 VDC. This  
reading should be steady within 0.2 to 0.3 VDC. If  
this reading is not within + 0.5 VDC, place the test  
meter probes on terminals A+ and A-. The meter  
reading should be approximately 150 to 160 VDC  
and steady within approximately 2 VDC. If the tach.  
voltage is unsteady, and the board output is steady,  
check the coupling for loose set screws or any type  
of damage. If the coupling checks good, the tach. is  
usually bad. If the board voltage output is unsteady  
beyond limits, then the board is probably bad.  
Always check the speed pot. Be sure it is okay  
before changing a board or tach. This test is not  
always 100% accurate as this test is not performed  
at operating speeds. However, this test is the best  
method currently available. Readjustment should  
always be attempted at least once before  
replacement. See procedure for board adjustment  
on page 65.  
DC Gearmotor  
If the DC control board is steady then the problem  
may be the motor or gearbox. Check the brushes in  
the motor for excessive arching and/or unusual  
wear. Check the motor and gearbox from  
instruction located on page 34 under "possible  
cause" listing "Conveyor gear motor".  
42  
Impinger I -–1000 Series Service Manual - International  
Conveyor will not  
run(S/N Q19078 &  
Up1000 Series) (S/N  
Q14791 & Up1200  
Series)  
Voltage Supply  
Check incoming voltage supply at Line 1 to neutral.  
There should be a voltage reading of 120 VAC.  
See procedure for checking on page 26.  
Check for 120 VAC to conveyor switch. If no  
voltage is present, trace wiring back to the fan  
switch. WITH POWER OFF: Check continuity  
between switch terminals.  
Fan Switch  
Conveyor Switch  
Conveyor Fuse (3A)  
Fuseholder  
Conveyor Control(Stepper)  
Transformer  
Check, replace if necessary.  
Check, replace if necessary.  
Check for 120 VAC supply to primary of  
transformer, if voltage is not present, trace wiring  
back to the fuse-holder. If voltage is present, check  
for output voltage from the transformer secondary.  
NOTE: this control transformer outputs (2)  
secondary voltages. Red Leads 29 VAC Brown  
Leads 10 VAC If BOTH secondary voltages are not  
present, replace the transformer.  
Speed Adjustment  
Potentiometer  
This is a 0 to 50k ohm,10 turn potentiometer. WITH  
POWER OFF: remove the 3 pin potentiometer  
cable plug from the motor control board. With a  
digital multimeter, check the ohm reading across  
the red lead to the black lead, this reading should  
be 50k ohms 5% as the potentiometer is rotated  
through its 10 turn rotation. Place the meter leads  
on the red lead and white lead. Rotating the  
potentiometer slowly, from low to high, the meter  
should show an even transition from 0 to 50K ohms  
5% through the 10 turn rotation of the  
potentiometer. There should be no dead or open  
spots through the 10 turns of the potentiometer.  
Check all three leads to ground. There should be  
no continuity to ground. If any of the above checks  
fail, replace the potentiometer.  
NOTE: if the conveyor drive motor becomes  
jammed or begins to run at an uncontrolled speed,  
the conveyor motor will stop running. To reset, turn  
off the conveyor switch, wait 10 seconds, turn the  
conveyor switch on. If the motor does not run after  
attempting re-set, check for 2-29 VAC across the  
motor terminals 1 to 2 and 3 to 5 on the conveyor  
motor control. If voltage is not present at both sets  
of terminals, replace control  
Conveyor Motor(Stepper)  
Control  
Conveyor Drive (Stepper)  
Motor  
Check the drive sprocket on motor out-put shaft to  
insure that it is tight.. Check motor windings –  
measurements should be approximately 2 ohms.  
Terminal 1-5, 2-6, 3-7, 4-8 WITH POWER OFF:  
Turn the motor shaft to check for jammed gear box.  
If motor shaft will not turn, replace conveyor  
drive(stepper) motor.  
Impinger I -–1000 Series Service Manual - International  
43  
Time/Temp Display  
12.6 VAC Power Supply  
Measure the transformer primary inoperative for a  
nominal 120 VAC input. Measure the secondary  
voltage output which will be 12.5 to 15 VAC  
normally. Recheck secondary output at rear of  
Time/Temp Display. Terminals 1 to 3 should read  
12.5 to 15 VAC. Terminals 1 to 2 and 2 to 3 should  
be exactly 1/2 of the reading across 1 to 3. If you  
do not get the above secondary readings, replace  
the transformer. If 120 VAC primary voltage is not  
available, refer to the schematic and trace circuit  
for incoming power failure. There is a 4 amp fuse in  
each red secondary lead. These may be jumpered  
(for test only) to determine if they are defective or  
intermittent.  
NOTE:  
(Dual Belt Ovens)  
Dual belt ovens utilize a double pole double throw  
switch, which allows either of the optical encoders  
to be read from a single Time/Temp. Display.  
Check switch and replace as needed.  
Temp Display out or  
inaccurate  
NOTE: Time/Temp displays  
use two types of temperature  
Place your pyrometer thermocouple into the center  
between fingers T2 and T3 in the oven. Disconnect  
sensor, Thermistor Probe – 2 the yellow tipped thermistor leads from the  
yellow wires Thermocouple  
Probe 1 red wire and 1 white  
wire  
time/temp. terminals 9 and 10. Measure the  
resistance of the thermistor probe. See chart on  
page 72 for proper resistance readings.  
Inspect the thermistor bulb for its proper location in  
its spring holder. Check for short in leads where  
they enter the sensor bulb. Also check each  
thermistor lead for short to ground.  
Thermistor Probe  
Thermocouple Probe  
Place your pyrometer thermocouple into the center  
between fingers T2 and T3 in the oven. Connect  
temperature meter to thermocouple at terminals 9  
& 10 on back of the time/temp display (Be sure to  
maintain proper polarity on thermocouple  
connections.) Compare actual oven temperature  
with the reading at the time/temp display. If the  
temperature readings match, recalibrate or replace  
time/temp display. If the readings do not match,  
replace thermocouple probe.  
Erratic time/temp display  
If strange or unusual behavior is experienced such  
as a rolling of numbers, lock up at a given number,  
first check for a display circuit lock up. This can be  
caused by a voltage spike or surge. To eliminate  
this condition remove power from the time/temp.  
display by shutting off the main fan switch, or if  
display stays on, (older models) circuit breaker  
interruption may be required. This should eliminate  
the problem. If the problem continues, jumper the  
two fuses in the red wires leading from the 12.6  
VAC transformer to the display. If this does not  
solve the problem, it may be coming in through the  
commercial power lines. Suggest that customer  
contact his power company for evaluation.  
Temp Display inaccurate  
erratic, or inoperative  
Perform the power supply check, the thermistor  
probe check, and then perform the time/temp  
simulator test. Refer to page 72 for instructions.  
Remember, when using the time/temp simulator,  
remove all the leads from the back of the display  
except the 3 power leads. After completion of this  
test and if reinstalling back into the oven, the dip  
switches must be reset for oven operation.  
44  
Impinger I -–1000 Series Service Manual - International  
Time display inaccurate  
erratic, or inoperative  
Perform all checks as in the above evaluation. If  
the time check is okay, refer to the next section  
optical encoder.  
Optical Encoder  
The above time/temp test should have already  
been performed. Remove dust cover from the  
gearmotor and inspect the coupling and encoder  
disc. The coupling set screws should be tight and  
not slipping on the motor shaft or the tach.  
generator shaft. The encoder disc should be firmly  
attached to the coupling and not warped. Check the  
positioning of the optical encoder disc. The disc  
should not be touching the optical encoder  
assembly and the encoder assembly should be  
mounted so it is squarely facing the coupling shaft.  
This is to allow the infrared beams to be broken by  
the encoder disc. If all this is okay, then replace the  
optical encoder assembly.  
Time Display  
inaccurate, erratic, or  
inoperative(S/N  
Q19078 & Above1000  
Series) (S/N Q14791 &  
Above1200 Series)  
Perform all checks as in the above evaluation. If  
the time check is okay, refer to the next section.  
Check to see if the conveyor drive (stepper) motor  
is running. If motor is not running, refer to  
"Conveyor will not run" on page 43.  
Check to insure that the magnet (cemented to shaft  
of conveyor drive (stepper) motor) has not been  
damaged, or come loose from motor shaft. Replace  
as needed.  
Conveyor Drive (Stepper)  
Control  
Magnet  
Hall Effect Sensor  
Check for any physical damage to Hall Effect  
sensor (mounted on conveyor drive(stepper)  
motor). Check all wiring and connections for  
damage.  
Conveyor Drive (Stepper)  
Control  
Check all connections for tightness or proper  
location and check all wiring for visible damage.  
Replace as needed. If there is still no time display,  
wire in (temporarily) a new conveyor drive control.  
If there is still no time display, reconnect original  
conveyor drive control. Replace Hall Effect Sensor.  
Impinger I -–1000 Series Service Manual - International  
45  
TROUBLESHOOTING / GAS OVENS 1033, 1034, 1046, 1047  
SYMPTOM  
Oven fan will not run  
POSSIBLE CAUSE  
Incoming Power Supply  
EVALUATION  
Check breaker/reset if required. Call Power  
Company if needed. In these ovens, there is a  
control circuit step-down transformer. This  
transformer steps down supply voltage to 120 VAC.  
If main fan will not run, the secondary of this  
transformer must be checked for 120 VAC output.  
Check specific oven model schematic for circuit  
location.  
Transformer Fuse  
Fuseholder  
Fan Switch  
Check and/or replace.  
Check and/or replace.  
Check continuity between switch terminals.  
Check for 120 VAC to the relay coil. If voltage is not  
present, trace wiring back to the fan switch. If  
voltage is present, check to insure contacts are  
closing.  
Oven Start Relay  
20 Minute Time Delay  
Oven Fan Relay  
Check for 120 VAC at terminal #1 to neutral on the  
20-minute timer. If no voltage is present, trace  
wiring back to the power supply. If voltage is  
present at terminal #1, check for 120 VAC at  
terminal #2 to neutral. If no voltage is present, and  
the oven start relay is closed, replace the 20-  
minute timer.  
Check for 120 VAC to coil of the oven fan relay. If  
no voltage is present, trace wiring back to terminal  
#2 of the 20-minute timer. Check for 120 VAC at  
terminals #2 and 6 of the relay, if no voltage is  
present, trace wiring back to the power supply. If  
voltage is present at the relay coil, check to insure  
the contacts are closing.  
Fan Fuse  
Fuseholder  
Capacitor  
Motor  
Check, replace if necessary.  
Check, replace if necessary.  
Check for opens, shorts, or grounds.  
Check for opens, shorts, or grounds. WITH  
POWER OFF: turn the fan blade to check for  
locked rotor.  
No main fan cool down 20 Minute Time Delay  
Check for 120 VAC at terminal #2 to neutral while  
oven is "on". Turn off the main fan switch, 120 VAC  
should continue to be present for 20 minutes. If  
voltage is not present for approx. 20 minutes,  
replace the timer.  
Oven Fan Relay  
Check if relay is operating and that the contacts  
remain closed during the 20 minute cool down.  
Contacts should open when main fan switch is  
turned off.  
Main fan runs after 20  
minute cool down  
Oven Start Relay  
20 Minute Time Delay  
120 VAC at terminal #2 should discontinue  
approximately 20 minutes after main fan is  
switched off. If the oven start relay contacts are  
open, and the voltage continues at terminal #2 of  
the 20 minute timer, replace the timer.  
Check to insure that the contacts are opening after  
the coil is de-energized.  
Oven Fan Relay  
No control box cooling Fan Switch Oven Start  
Relay20 Minute Time Delay  
Oven Fan Relay Cooling  
Fans  
(SEE MAIN FAN WILL NOT RUN) 120 VAC should  
now be at this motor. If voltage is present, check  
motor for shorts, opens, or grounds. WITH POWER  
OFF: check for locked rotor.  
46  
Impinger I -–1000 Series Service Manual - International  
No automatic control  
box cooling  
Incoming Power Supply  
Check circuit breakers, reset if required. Call the  
Power Co. if needed.  
Check, replace if necessary.  
Fuse Transformer  
Fuseholder  
Check, replace if necessary.  
Cooling Fan Thermostat  
Check the cooling fan thermostat (Thermostat  
closes at 120°F and opens at 100°F). With the  
cooling fan thermostat pre-heated, check for  
continuity. If switch is open, replace.  
Cooling Fan  
120 VAC should now be at this motor. If voltage is  
present, check motor for shorts, opens, or grounds.  
WITH POWER OFF: check for locked rotor.  
Thermostat is normally open and may have closed  
if control box temperature is 120°F or above.  
Cooling fan continues  
to run after 20 minute  
cool down  
Cooling Fan Thermostat  
Oven will not heat  
Gas Supply  
Manual Gas Shut-off Valve  
Fan Switch Main Oven Fan  
Check for adequate gas supply to oven.  
Check to see that manual shut-off valve is open.  
Check to see that the fan switch is on. Check if  
main oven fan is operating. If not, refer to "Oven  
fan will not run."  
Oven Start Relay  
Burner Switch  
Check for contacts to close.  
Check for 220 VAC to neutral on both sides of  
switch.  
Air Pressure Switch  
Check for 220 VAC on both sides of switch. If  
voltage present on one side only, check for air tube  
blockage. Adjust air switch. If above fails, replace  
air pressure switch.  
Gas Pressure Switch  
Check for 220 VAC to neutral on both sides of  
switch. If voltage is present on one side of switch  
only, check the following. Check for proper gas  
pressure supply to gas valve.(Marked on oven spec  
plate). Check for proper adjustment of gas pressure  
switch. Should be set at 8.8 for Nat., 23 for L.P.  
Check gas filter in gas valve for blockage or  
damage. (See Adjustment Section for location). If  
the above checks okay, but switch still not closed,  
replace gas valve.  
Hi-Limit Thermostat  
Ignition Control  
Terminals are normally closed. If open, reset and  
test oven for proper operation. If thermostat will not  
hold for maximum oven temperature, and oven is  
not exceeding temperature dial setting, check for  
proper location of capillary bulb in its spring holder.  
If above checks okay, replace hi-limit thermostat.  
Check for 220 VAC supply to ignition control at pin  
#1 and neutral. If voltage is not present, retrace  
wiring back to hi-limit thermostat. Check for 220  
VAC at pin #6 to neutral.(Power to burner motor). If  
voltage is present, proceed. If no voltage is  
present, wait 30 seconds and check reset button. If  
above fails, replace ignition control.  
Burner Blower Motor  
Check for 220 VAC supply to burner blower motor.  
WITH POWER OFF: turn blower wheel to check for  
locked rotor. If 220 VAC is present and motor does  
not run, replace motor.  
Burner Blower Motor Air  
Pressure Switch  
Check for 220 VAC switching to pin "N.O." as the  
air pressure switch closes. For Honeywell ignition  
control only, connect a temporary jumper wire (for  
testing purposes only) from pin "C" to pin "N.O." on  
ignition control (to bypass air switch). Check for air  
tube blockage or misalignment, adjust air pressure  
switch. If the above fails, replace air pressure  
switch.  
Impinger I -–1000 Series Service Manual - International  
47  
Spark Generator  
After a pre-purge time of 30 to 60 seconds after  
blower motor starts, check for 220 VAC to spark  
generator. If voltage is not present, check reset  
button on ignition control. If voltage is present,  
visually check for spark at ignitor head.  
Ignitor/Sensor Assembly  
Check for visible damage to ignitor/sensor  
assembly. If there is no visible damage to the  
components, and no spark, replace the spark  
generator. If there is visible damage to the ignitor  
sensor assembly, replace. Also check for frayed or  
damaged wire in burner tube.  
Gas Valve  
Check for 220 VAC supply to gas valve. If no  
voltage present, check reset button on ignition  
control, check all connections for tightness. If there  
is no voltage at gas valve, replace ignition control.  
If there is voltage present, check for gas pressure  
at gas pressure tap located in gas piping. If there is  
no gas pressure, replace gas valve.  
No Pilot  
If the ignition control is energized, and the gas  
valve and ignitor circuits are energized, visually  
check for pilot flame. This may be done by opening  
the small inspection door on the end of the burner,  
or by opening the main oven door and looking  
under the lower finger housings on the right side of  
the oven. If no pilot flame is visible, check the  
following.  
Pilot Tube  
Check for gas pressure at pilot tube. Disconnect  
pilot tube at burner and connect manometer to pilot  
tube. If no gas pressure is present, check for  
blockage in pilot tube. If these are clear, and there  
is gas supplied to the oven, replace the gas valve.  
If there is gas pressure at the pilot tube, check the  
pilot orifice for obstructions. Replace as needed.  
Check the burner ignitor head for any obstructions,  
also check for frayed or broken wire, any type of  
damage to spark gap (.100 in 2.5 mm).If there is  
visible damage, replace ignitor assembly.  
(There should be a visible pilot flame at this time).  
To check for flame sensor operation, connect a  
digital multimeter. (Capable of measuring D.C.  
microamperes) between the flame sensor wire and  
the ignition control. NOTE: This is current  
measurement and the meter must be connected in  
series. Proper current readings should be  
Honeywell 2-4 micro amp D.C., Landis & Gyr. 3  
micro amp D.C. If these readings are not achieved,  
replace ignitor/sensor assembly. Also check for any  
type of damage to flame sensor wire and  
connections.  
Pilot Orifice  
Burner Ignitor  
Pilot flame, but burner  
will not stay ignited  
Flame Sensor  
Ignition Control  
If there is sufficient flame sensor current, but the  
burner will not remain ignited, check reset buttonon  
ignition control.  
Indicator light is on but Gas Control Relay  
no main flame, (Model  
1046-1047)  
Check for 220 VAC to relay coil. If no voltage is  
present, trace wiring back to ignition control. If  
voltage is present, check to insure contacts are  
closing.  
48  
Impinger I -–1000 Series Service Manual - International  
Temperature Control  
Thermocouple Probe  
Check for 120 VAC across L1 and L2 on  
temperature control board. If no voltage is present,  
retrace wiring back to power supply. Turn the  
temperature adjustment knob to the maximum  
temperature position and check for 120 VAC at the  
load terminal to neutral. If 120 VAC is not present,  
proceed as follows: If 120 VAC is present and unit  
is not heating, see "Solenoid Valve."  
Remove thermocouple leads from the temperature  
control board and measure the millivolt output of  
these leads. Refer to chart on page 59 for proper  
readings. If the thermocouple probe checks good,  
then the problem is usually with the temperature  
control board.  
Solenoid Valve  
If output voltage is present at temperature control  
board, check for voltage at solenoid valve. If  
voltage is present, listen for valve to open and  
close. Also check for opens, shorts in coil. Replace  
as needed.  
Indicator light is on,  
but no main flame  
(1033-1034)  
Temperature Control  
Check for 120 VAC across L1 and L2 on  
temperature control board. If no voltage is present,  
retrace wiring back to power supply. Turn the  
temperature adjustment knob to the maximum  
temperature position and check for 220 VAC at the  
load terminal to neutral. If 220 VAC is not present,  
proceed as follows: If 220 VAC is present, and unit  
is not heating, see "Flame Monitor". Check for 220  
VAC at terminal "COM" on temperature control  
board. If no voltage is present, trace wiring back to  
ignition control.  
Thermocouple Probe  
Flame Monitor  
Remove thermocouple leads from the temperature  
control board and measure the millivolt output of  
these leads. Refer to chart on page 59 for proper  
readings. If the thermocouple probe checks good,  
replace temperature control.  
Check for 220 VAC at terminal #1. If no voltage is  
present, trace wiring back to temperature control.  
Check for 220 VAC output at terminal #8. NOTE:  
There is a delay of up to 2 seconds for 220 VAC  
output at terminal #8. If there is no voltage output  
at terminal #8, check the reset button. Replace  
control as needed.  
Relay, Main Burner  
Check for 220 VAC at relay coil, if no voltage is  
present, trace wiring back to flame monitor. Check  
for 120 VAC to relay contacts. If no voltage is  
present, trace wiring back to power supply. Check  
to ensure contacts are closing. Replace relay as  
needed.  
Valve, Temperature  
Regulation  
Check for 120 VAC at valve, if no voltage is  
present, trace wiring back to relay. If voltage is  
present, listen for valve to open and close. Check  
for opens or shorts in coil. Replace as needed.  
Impinger I -–1000 Series Service Manual - International  
49  
Main Flame will not  
stay lit  
Flame Monitor  
(There should be a visible main flame at this time.)  
To check for flame monitor operation, connect a  
digital volt meter (capable of measuring D.C. micro  
amperes) between the flame sensor and terminal  
#15 on the flame monitor. The flame monitor  
requires a minimum of 4 micro amp. D.C. for proof  
of flame. If these readings are not achieved,  
replace sensor assembly. Also check for any type  
of damage to flame sensor wire and connections.  
If the reading is above the minimum required, and  
the flame monitor will not supply 220 VAC to the  
relay coil, replace the flame monitor.  
Intermittent Heating  
Conveyor will not run  
As Follows  
Both the main fan motor and burner blower motor  
are equipped with thermal protection and will cease  
to operate if overheating occurs. This can cause  
the units to cycle on and of intermittently. This may  
be caused by improper ventilation. Also, most of  
the problems listed under "oven will not heat" can  
cause intermittent failure.  
Check for 120 VAC to conveyor switch. If no  
voltage is present, trace wiring back to the power  
supply. WITH POWER OFF: Check continuity  
between switch terminals  
Conveyor Switch  
Conveyor Fuse(3A)  
Fuseholder  
Conveyor Control  
Check, replace if necessary.  
Check, replace if necessary.  
Check for 120 VAC supply to primary (Stepper)  
Transformer of transformer, if voltage is not  
present, trace wiring back to the fuseholder. If  
voltage is present, check for output voltage from  
the transformer secondary. NOTE: this control  
transformer outputs (2) secondary voltages: Red  
Leads 29 VAC Brown Leads 10 VAC. If BOTH  
secondary voltages are not present, replace the  
transformer.  
Speed Adjustment  
Potentiometer  
This is a 0 to 50K ohm, 10 turn potentiometer.  
WITH POWER OFF: remove the 3 pin  
potentiometer cable plug from the motor control  
board. With a digital multimeter, check the ohm  
reading across the red lead to the black lead, this  
reading should be 50K ohms 5% as the  
potentiometer is rotated through its 10 turn rotation.  
Place the meter leads on the red lead and white  
lead. Rotating the potentiometer slowly, from low to  
high, the meter should show an even transition  
from 0 to 50K ohms 5% through the 10 turn  
rotation of the potentiometer. There should be no  
dead or open spots through the 10 turns of the  
potentiometer. Check all three leads to ground.  
There should be no continuity to ground. If any of  
the above checks fail, replace the potentiometer.  
NOTE: if the conveyor drive motor becomes  
jammed or begins to run at an uncontrolled speed,  
the conveyor motor will stop running. To reset, turn  
off the conveyor switch, wait 30 seconds, turn the  
conveyor switch on. If the motor does not run after  
attempting re-set, check for 2 to 29 VAC across the  
motor terminals 1 to 2 and 3 to 5 on, the conveyor  
motor control. If voltage is not present at both sets  
of terminals, replace control.  
Conveyor Motor(Stepper)  
Control  
50  
Impinger I -–1000 Series Service Manual - International  
Conveyor Drive(Stepper)  
Motor  
Check the drive sprocket on motor output shaft to  
insure that it is tight. Check motor windings  
measurement should be approximately 2 ohms.  
Terminals 1-5, 2-6, 3-7, 4-8. WITH POWER OFF:  
Turn the motor shaft to check for jammed gear box.  
If motor shaft will not turn, replace conveyor  
drive(stepper) motor.  
Time/Temp. Display  
inoperative  
12 VAC Power Supply  
(Transformer)  
Measure the transformer primary for a nominal 120  
VAC input, if voltage is not present, trace wiring  
back to the oven fan switch. Measure the  
secondary output, which will normally be 12-15  
VAC. Voltage across terminals 1 and 3 on the  
time/temp. display should read 12-15 VAC.  
Terminals 1-2 and 2-3 should be 1/2 the voltage  
reading 1 to 3. If the above secondary readings are  
not achieved, replace transformer.  
Time/Temp. Display  
If proper voltage is present at terminal 1,2, and 3  
on time/temp. display, but the display is not lighted,  
recheck all connections for tightness. If time/temp.  
display is still not operating, replace the time/temp.  
display.  
Temp. Display out or  
inaccurate  
NOTE: Time/temp displays  
use two types of temperature  
sensor Thermistor Probe - 2  
yellow wires. Thermocouple  
Probe - 1 red & one white  
wire  
Place your pyrometer thermocouple into the center  
between finger T2 and T3 in the oven. Disconnect  
the yellow tipped thermistor leads from the  
time/temp. terminals 9 and 10. Measure the  
resistance of the thermistor probe.  
Thermistor Probe  
See chart on page 72 for proper resistance  
readings. Inspect the thermistor bulb for its proper  
location in its spring holder. Check for short in  
leads where they enter the sensor bulb. Also check  
each thermistor lead for short to ground.  
Thermocouple Probe  
Place your pyrometer thermocouple into the center  
between fingers T2 and T3 in the oven. Connect  
temperature meter to thermocouple at terminals 9  
& 10 on back of the time/temp display. (Be sure to  
maintain proper polarity on thermocouple  
connections.) Compare actual oven temperature  
with the reading at the time/temp display. If the  
temperature readings match, recalibrate or replace  
time/temp display. If the readings do not match,  
replace thermocouple probe.  
If a strange or unusual behavior is experienced,  
such as a rolling of numbers, or lock-up at a given  
number, first check for a display circuit lock-up.  
This may be caused by a voltage spike or surge in  
the incoming power lines. To eliminate this  
Power Supply  
condition, remove power from time/temp. display by  
shutting off the main fan switch for 15 seconds.  
This should eliminate the problem. If this does not  
solve the problem, it may becoming in through the  
Commercial power lines. Suggest that customer  
contact their power company for evaluation.  
Impinger I -–1000 Series Service Manual - International  
51  
Temp. display  
inaccurate, erratic, or  
inoperative  
Time/Temp. Display  
Perform the power supply check, the thermistor  
probe check, and then perform the time/temp.  
simulator test. Refer to page 72 for instructions.  
Remember, when using the time/temp. simulator,  
remove all leads from the back of the time/temp.  
display except the 3 power leads. After completion  
of the test, and if re-installing time/temp. display  
back in the oven, the dip switches must be reset for  
oven operation, and the time/temp. display must be  
recalibrated. If readings are not achieved, replace  
display.  
Time Display  
inaccurate, erratic or  
inoperative  
Perform all checks as in the above evaluation. If  
the time check is okay, refer to the next section.  
Check to see if the conveyor drive (stepper) motor  
is running. If motor is not running refer to  
Conveyor Drive  
(Stepper) Motor  
"Conveyor will not run" on page 50.  
Magnet  
Check to insure that the magnet (cemented to shaft  
of conveyor drive (stepper) motor) has not been  
damaged, or come loose from motor shaft. Replace  
as needed.  
Hall Effect Sensor  
Check for any physical damage to Hall Effect  
Sensor(mounted on conveyor drive(stepper)motor.)  
Check all wiring and connections for damage.  
Check all connections for tightness or proper  
location and check all wiring for visible damage.  
Replace as needed. If there is still no time display,  
wire in (temporarily) a new conveyor drive control.  
If there is still no time display, reconnect original  
conveyor drive control. Replace Hall Effect Sensor.  
Conveyor Drive  
(Stepper) Control  
52  
Impinger I -–1000 Series Service Manual - International  
REMOVAL, INSTALLATION & ADJUSTMENTS  
MODEL SERIES 1000 &1200  
CAUTION !  
BEFORE REMOVING OR INSTALLING ANY COMPONENT IN THE IMPINGER  
OVEN BE SURE TO DISCONNECT ELECTRICAL POWER AND GAS SUPPLY  
MOTOR, MAIN FAN  
1.  
2.  
3.  
4.  
Shut off power at main breaker.  
Remove flue by taking out the two (2) mounting screws.  
Remove louvered motor cover from back of oven.  
Remove wireway by taking out the ten (10) hex head screws.  
NOTE: On Series 1200 ovens there are two (2) wireways to be removed and there is extra  
wire coiled in the control box to allow the wires to hang below the oven back for removal.  
Remove cooling fan if equipped.  
Remove junction box cover below motor and disconnect motor leads. Make note of wire numbers  
and location for reinstallation.  
Remove the twelve (12) hex head bolts from the oven back and slide back straight out  
of the oven .  
Remove two (2) hex head bolts from fan hub and remove fan from motor shaft.  
NOTE: Measure distance from fan blade to rear wall assembly before removal to aid in reassembly.  
Remove the eight (8) hex head bolts from the motor mount and slide the motor assembly out of the  
oven back.  
5.  
6.  
7.  
8.  
9.  
10.  
11.  
Remove heat slinger, if so equipped, by taking out the two (2) hex head cap screws then  
remove motor by taking off motor clamp and removing the four (4) mounting nuts and washers.  
Reassemble in reverse order. When reassembling trim the motor mount bolts off after  
the motor is mounted (if required). Be sure the heat slinger, if so equipped, is set at  
the proper clearance. (3/8" approximately with 1/16" clearance at motor mount  
bolts). When motor mount assembly is set on the oven back, align motor shaft in the  
center of the hole. Set fan assembly on the motor shaft .  
NOTE: Torque specs on bolts (150 in/lb. torque)  
CAPACITOR, MOTOR  
1.  
2.  
3.  
4.  
Shut off power at main breaker.  
Remove motor cover from back of oven.  
Discharge capacitor.  
Remove and replace.  
FAN, MAIN  
1.  
2.  
Shut off power at main breaker.  
Remove back assembly. (See motor, main fan)  
S. N. 100-4612 (GAS)  
S. N. 100-4767 (ELECTRIC)  
Impinger I -–1000 Series Service Manual - International  
53  
FAN BLADE  
9 3/4 IN.  
1/8 IN.  
COOLING FAN  
3.  
Reinstall and locate fan so that the front of fan blades are 9 3/4" from inside of oven back. (See Drawing)  
S. N. 4613 & Above (GAS)  
S. N. 4768 & Above (ELECTRIC)  
FAN SPIDER  
NOTE: MEASUREMENT MUST BE  
MADE FROM CONE TO FAN SPIDER  
FAN HUB  
CONE  
1 1/2 INCH  
3.  
Reinstall and locate fan so that the bottom of the fan spider is 1 1/2" from the top of the oven back cone  
(See Drawing)  
RELAY, D.P.S.T.  
1.  
2.  
3.  
4.  
5.  
6.  
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove cover from relay box.  
Disconnect all wires and mark for replacement.  
Remove relay by removing two (2) mounting screws.  
Reassemble in reverse order.  
COOL DOWN SWITCH  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker  
Remove control panel top and front cover.  
Remove the two (2) wires from the switch, located on the back wall of the control box.  
Remove two (2) screws from the switch bracket.  
Reassemble in reverse order, check condition of teflon insulator and be sure a aluminum  
sensing rod contacts the switch body.  
COOLING FAN, CONTROL BOX  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove four (4) screws from the fan frame.  
Disconnect female cord receptacle and remove fan.  
Reassemble in reverse order.  
THERMOSTAT, COOLING FAN  
1.  
2.  
Shut off power at main breaker.  
Remove control panel top and front cover.  
54  
Impinger I -–1000 Series Service Manual - International  
3.  
4.  
5.  
Remove lead wires and mark for reassembly.  
Remove two (2) screws and remove thermostat.  
Reassemble in reverse order.  
BURNER BLOWER MOTOR  
1.  
2.  
Shut off power at main breaker.  
Remove control panel top and front panel.  
NOTE: Complete burner blower motor assembly, with control box (p/n 369359), is no longer  
available. The burner blower assembly (p/n 369265) has been changed to a burner motor kit  
(p/n 369366). When It is used in the 3 ft Impinger Gas oven, the following modification must be made:  
Remove control box and components mounted on burner blower motor.  
Mount transformer on air switch bracket as shown (use transformer as template).  
Remove three (3) screws that attach blower assembly to burner housing.  
Mount new blower assembly.  
Wire as shown. See page 56.  
Discard control box and relay.  
Transfer air shutter assembly from old blower assembly to new blower assembly.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
MATERIAL NEEDED: #29 drill bit and #8 x 3/8 self tapping screws (3 each)  
AIR SWITCH MOUNTING BRACKET  
MOUNTING HOLES  
(USE #29 DRILL)  
#8 X 3/8  
SELF TAPPING  
SCREW  
SEPARATE GROUND SCREW  
Impinger I -–1000 Series Service Manual - International  
55  
CENTRIFUGAL  
SWITCH  
MOTOR  
WIRING DIAGRAM  
BURNER BLOWER ASSEMBLY  
WITH RELAY REMOVED  
24 VAC TO  
IGNITION CONTROL  
RED  
RED  
TO GROUND TERMINAL  
ON IGNITION CONTROL  
GREEN  
GROUND  
24 VAC  
TRANSFORMER  
P/N 369531  
(WHEN USING OLD  
TRANSFORMER, 120  
VAC LEADS ARE BLACK.  
WIRE TERMINALS ARE  
PROVIDED.)  
120 VAC  
WHITE  
BLACK  
(BUTTSPLICE CONNECTORS PROVIDED FOR 120 VAC POWER SUPPLY)  
BLOWER WHEEL, BURNER  
This is part of the burner blower motor assembly.  
TO REMOVE THE BLOWER WHEEL FOR PERIODIC CLEANING:  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove air shutter held by 3 screws.  
Loosen set screw on blower wheel hub and pull straight out.  
Reassemble in reverse order.  
NOTE: There is no critical placement of the blower wheel on the motor shaft. Just back as  
far as it will go and then spin the blower to be sure it is not rubbing.  
AIR PRESSURE SWITCH  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
Shut off power at main breaker.  
Remove front control compartment cover.  
Remove air switch cover plate.  
Disconnect wiring and mark for reassembly.  
Loosen 2 screws and remove air switch.  
Disconnect 1/4" air tube.  
Reassemble in reverse order.  
Turn on power and calibrate air switch as follows:  
Turn adjusting screw counter clockwise to full out position.  
Turn main fan and heat switch on.  
Turn adjusting screw clockwise until heat shuts off.  
Turn adjusting screw counterclockwise 1/4 turn and unit should heat.  
NOTE: Test as follows:  
Oven must be tested in heated condition.  
Remove main fan fuse. Main fan should shut down, deactivating air switch causing  
heat to shut off in approximately 5 to 25 seconds.  
56  
Impinger I -–1000 Series Service Manual - International  
BURNER ASSEMBLY  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
Shut off power at main breaker.  
Shut off gas supply.  
Remove control panel top and front panel.  
Remove gas control valve (See "GAS CONTROL VALVE")  
Disconnect pilot tube.  
Remove thermostat or solenoid valve.  
Remove four (4) phillips screws that secure the burner backing plate.  
Remove burner assembly from housing, the main and pilot orifice, flame target, pilot  
shield (main and extension), flame sensor, and burner ignitor can now be changed or serviced as  
needed.  
9.  
Reassemble in reverse order.  
GAS CONTROL VALVE  
Shut off power at main breaker.  
Shut off gas supply.  
Remove control panel top and front cover.  
Disconnect the gas piping from the back of the unit.  
Remove the four (4) screws from the incoming nipple mounting bracket.  
Remove incoming nipple.  
Remove pilot tube assembly from control valve.  
Disconnect pipe union just above control valve.  
Disconnect wiring from control valve making note of wire numbers and location.  
Reassemble in reverse order - after assembly is complete be sure to check manifold pressure  
(3.5" W.C. NAT Gas/10" W.C. LP) and adjust if necessary. (See Section  
"MANIFOLD PRESSURE-ADJUSTMENT")  
NOTE: Check all gas line fittings for leaks after installation.  
MANIFOLD ADJUSTMENT  
SCREW LOCATED UNDER  
COVER SCREW  
FRONT VIEW  
MANIFOLD PRESSURE  
ADJUSTMENT CONNECTION  
PILOT  
LINE  
CONNECTION  
MANIFOLD ADJUSTMENT  
SCREW LOCATED UNDER  
COVER SCREW  
TOP VIEW  
MANIFOLD PRESSURE - ADJUSTMENT  
1.  
2.  
Remove control panel top and front cover.  
WITH ELECTRIC POWER AND GAS OFF: remove the outlet pressure tap plug from the gas  
Impinger I -–1000 Series Service Manual - International  
57  
control valve and install the adapter fitting and manometer.  
Turn on electric power and gas and start-up oven.  
With oven at full fire, manifold pressure should be (3.5"W.C. NAT/10" W.C. LP).  
Turn off electric power and gas, replace cover screw, remove manometer and adapter; replace pressure  
tap plug.  
3.  
4.  
5.  
6.  
7.  
Check pressure tap for gas leaks before closing panel.  
Close control panel and check system operation.  
TEMPERATURE CONTROL VALVE (ROBERT SHAW)  
1.  
Shut off power at main breaker  
2.  
3.  
4.  
5.  
6.  
Shut off gas supply.  
Remove control panel top and front cover.  
Remove gas control valve (See Above).  
Remove the two (2) 3/8" x 16 nuts that hold main orifice bracket to the burner assembly.  
Remove temperature control valve sensing bulb from oven cavity.  
NOTE: It may be necessary to remove conveyor and fingers from oven cavity.  
Remove piping from old temperature control valve.  
Reassemble in reverse order, be sure the sensing bulb is properly placed in the oven  
cavity. The sensing bulb is properly placed in the oven cavity when it is placed in  
the spring holder and positioned with the 5 1/2" of the bulb to the left of the spring holder.  
NOTE: The bypass screw should be adjusted all the way in.  
7.  
8.  
SOLENOID VALVE  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
Shut off power at main breaker.  
Shut off gas supply.  
Remove control panel top and front cover.  
Remove gas control valve (See "GAS CONTROL VALVE").  
Disconnect wires from solenoid valve.  
Remove two (2) 3/8" x 16 hex nuts that hold main orifice bracket in place.  
Remove solenoid valve assembly.  
Remove piping from solenoid valve.  
Reassemble in reverse order.  
TEMPERATURE CONTROL BOARD  
Gas Ovens  
1.  
2.  
3.  
4.  
5.  
6.  
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove relay box cover.  
Disconnect wiring from temperature control board.  
Make note of wire number and location for reinstallation.  
Reassemble in reverse order.  
Electric Ovens  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control panel top and front cover.  
Disconnect wiring from temperature control board.  
Make note of wire numbers and location for reinstallation.  
Reassemble in reverse order.  
TEMPERATURE CONTROL POTENTIOMETER – REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
Remove control panel top and front cover.  
Remove one screw from control knob guard and move guard to one side.  
Remove knob and locknut on control pot. shaft and push out.  
Remove three (3) wires from temperature control board. Note wire numbers and location.  
Reassemble in reverse order.  
58  
Impinger I -–1000 Series Service Manual - International  
MERCURY CONTACTOR  
1.  
2.  
3.  
4.  
Shut off power at main breaker.  
Remove control panel top and front cover.  
Disconnect contactor wires and mark for reinstallation.  
Remove screws from mounting bracket and replace contactor.  
NOTE: Be sure contactor is not mounted upside down as this will cause a constant on condition.  
Reassemble in reverse order.  
5.  
THERMOCOUPLE- REPLACEMENT  
1.  
2.  
3.  
Remove control panel top and front cover.  
Remove cover from relay box.  
Slide thermocouple out of oven chamber.  
NOTE: Remove conveyor and bottom fingers to aid in removal and installation of thermocouple.  
Remove two (2) wires from temperature control board. Make note of wire numbers or color and location  
for reinstallation.  
4.  
5.  
Reassemble in reverse order making sure the metal end on the thermocouple is securely in the wire  
form in the oven chamber.  
THERMOCOUPLE MEASUREMENT CHART:  
EXPLANATION: The junction temperature is the ambient air temperature where the thermocouple fastens to the  
electronic temperature control board.  
O
V
E
N
T
E
M
P
200°F 250°F 300°F 325°F 350°F 400°F 425°F 450°F 500°F 550°F 600°F  
90°F  
88°F  
86°F  
84°F  
82°F  
80°F  
78°F  
76°F  
75°F  
74°F  
72°F  
70°F  
68°F  
66°F  
64°F  
62°F  
60°F  
3.26  
3.32  
3.37  
3.43  
3.49  
3.55  
3.60  
3.66  
3.69  
3.72  
3.78  
3.83  
3.89  
3.95  
4.01  
4.06  
4.12  
4.77  
4.83  
4.88  
4.94  
5.00  
5.06  
5.11  
5.17  
5.20  
5.23  
5.29  
5.34  
5.40  
5.46  
5.52  
5.57  
5.63  
6.30  
6.36  
6.41  
6.47  
6.53  
6.59  
6.64  
6.70  
6.73  
6.76  
6.82  
6.87  
6.93  
6.99  
7.05  
7.10  
7.16  
7.06  
7.12  
7.17  
7.23  
7.29  
7.35  
7.40  
7.46  
7.49  
7.52  
7.58  
7.63  
7.69  
7.75  
7.81  
7.86  
7.92  
7.83  
7.89  
7.94  
8.00  
8.06  
8.12  
8.17  
8.23  
5.26  
8.29  
8.35  
8.40  
8.46  
8.52  
8.58  
8.63  
8.69  
9.37 10.14 10.91 12.46 14.00 15.53  
9.43 10.20 10.97 12.51 14.05 15.59  
9.49 10.26 11.03 12.57 14.11 15.65  
9.54 10.31 11.09 12.63 14.19 15.71  
9.60 10.37 11.14 12.69 14.23 15.76  
9.66 10.43 11.20 12.74 14.28 15.82  
9.72 10.49 11.26 12.80 14.34 15.86  
9.77 10.55 11.32 12.86 14.40 15.94  
9.80 10.57 11.35 12.89 14.43 15.97  
9.83 10.60 11.37 12.92 14.46 15.99  
9.89 10.66 11.43 12.97 14.51 16.05  
9.95 10.72 11.49 13.03 14.57 16.11  
10.00 10.78 11.55 13.09 14.63 16.17  
10.06 10.83 11.61 13.15 14.69 16.23  
10.12 10.89 11.66 13.20 14.74 16.28  
10.18 10.95 11.72 13.26 14.80 16.34  
10.24 11.01 11.78 13.32 14.86 16.40  
J
U
N
C
T
I
O
N
T
E
M
P
HEATING ELEMENT  
1.  
2.  
3.  
4.  
Shut off power at main breaker.  
Remove rear motor cover.  
Disconnect heater element wire and mark for reassembly.  
Remove oven back assembly.  
NOTE: For ovens SN 4768 and above, remove fan shroud.  
Remove two (2) mounting screws and remove heating element.  
Reassemble in reverse order.  
5.  
6.  
NOTE: Be sure the lead terminals are double nutted to the heating element and are tight  
If the leads are not attached in this manner, a loose connection may result, causing  
arcing and lead wire burn off.  
Impinger I -–1000 Series Service Manual - International  
59  
IGNITION CONTROL  
NOTE: When replacing Johnson Controls, G-60 or G-65 Ignition Control with the new  
Honeywell Ignition control, the 24 VAC burner transformer (rated at 20VA) must be  
replaced with the larger (rated at 40VA) #369531 Transformer.  
1.  
Read all instructions supplied in kit before starting.  
Tools required: Center punch and 7/32" drill bit.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control panel top and front panel.  
Remove front panel.  
Remove ignition control package from Johnson gas valve and discard.  
The white flame sensor wire, from the burner to terminal #4 on Johnson gas control  
is no longer used. Cut Wire at burner and discard.  
NOTE: On some Impinger ovens, it may be necessary to drill the mounting holes through the  
oven specification plate. Use care to avoid drilling through any important  
information or agency approval markings on the specification plate.  
Use template supplied to locate and drill two (2) 7/32" mounting holes for new Ignition  
Control. When mounting new ignition control, make certain that the green #67 ground  
wire (supplied) is installed properly.  
6.  
7.  
Connect wiring as follows:  
Connect blue wire from gas valve to terminal marked P.V. on ignition control.  
Connect black wire from gas valve to termainal marked M.V./P.V. on ignition control.  
Connect red wire from gas valve to terminal marked M.V. on ignition control.  
Connect white wire from indicator light to ground, by using splice connection on green  
wire supplied.  
Connect orange spark lead from burner to terminal marked "spark" on ignition control.  
NOTE: It may be necessary to replace ignition cable terminal with .250" quick-  
connect terminal (supplied).  
Connect the red wire from burner blower motor centrifugal switch to terminal marked  
24V on ignition control.  
Connect green #68 wire (supplied) from terminal 24 GND to terminal GND (burner)  
to ground.  
Connect the green wire from 24VAC transformer to wire #68 at terminal marked  
24V(GND) on ignition control.  
The Honeywell ignition control module provides 100% safety lockout. Control will try for  
ignition for 15 seconds. If ignition does not occur, control will lockout or shut off. To  
reset control, the burner switch must be turned off for 1 minute.  
60  
Impinger I -–1000 Series Service Manual - International  
24V (GND)  
24V  
WHITE FROM  
PILOT LIGHT  
BUTT SPLICE AND  
NEW GREEN WIRE  
SUPPLIED IN KIT  
BLUE FROM VALVE  
BLACK FROM VALVE  
#3 RED FROM VALVE  
TO PILOT LIGHT  
WHITE FROM PILOT LIGHT  
BUTT SPLICE AND NEW  
GREEN WIRE SUPPLIED  
IN KIT  
TO PILOT LIGHT  
RING TERMINAL END OF  
WIRE HARNESS SUPPLIED IN KIT  
24V FROM TRANSFORMER  
INSULATED MALE TAB  
CONNECTOR  
FLAME SENSOR  
1.  
2.  
3.  
4.  
5.  
6.  
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove burner assembly (see burner assembly).  
Disconnect one (1) wire from flame sensor.  
Remove flame sensor by removing one (1) mounting nut.  
Reassemble in reverse order.  
NOTE: Be sure flame sensor is not bent or touching any other burner parts.  
Impinger I -–1000 Series Service Manual - International  
61  
BURNER IGNITOR  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove burner assembly.  
Remove flame sensor.  
Remove pilot shield and pilot shield extension.  
Remove burner igniter.  
Reassemble in reverse order.  
NOTE: Be sure to reconnect burner igniter cable to ignition control.  
TRANSFORMER 120/24 VAC  
1.  
2.  
Remove control panel top and front cover.  
Remove control box cover from burner blower motor.  
NOTE: The complete burner blower motor assembly, with control box (PN 369359), is no longer  
available. The blower motor assembly (PN 369265) has been changed to a  
burner motor kit (PN 369366). If the burner blower motor or 24V transformer  
(PN 369531 ) are replaced, the following modifications must be made:  
Shut off power at main breaker.  
Remove control box and components from burner blower motor.  
Mount transformer on air switch bracket (use transformer as template).  
Discard control box and relay.  
3.  
4.  
5.  
6.  
Material needed: #29 drill bit and #8 x 3/8" self tapping screws (3 each)  
See Burner blower motor section for wiring information.  
Replace covers and check system operation.  
7.  
8.  
BURNER LIGHT (24 VAC) - GAS OVENS  
1.  
2.  
3.  
4.  
5.  
6.  
Shut off power at main breaker.  
Remove control panel top and front panel.  
Remove access cover.  
Remove two wires from burner light, note number and location.  
Grasp body of light assembly and slide sideways to remove.  
Reassemble in reverse order and check.  
HEAT LIGHT (125 VAC) - ELECTRIC OVENS  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control panel top and front panel.  
Remove two (2) wires from heat light, note number and location.  
Grasp body of light assembly and slide sideways to remove.  
Reassemble in reverse order and check.  
THERMOSTAT, Hl-LIMIT - ELECTRIC OVENS  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove the two (2) wires from the thermostat located on the back wall of the control box.  
Remove two (2) mounting screws.  
Reassemble in reverse order.  
NOTE: Be sure to press red "reset" button on new thermostat to ensure that it is in the  
"closed" position.  
PILOT ORIFICE - BURNER  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Shut off gas supply.  
Remove burner assembly (see Burner Assembly).  
Remove pilot line from pilot orifice.  
Remove pilot orifice from burner igniter.  
62  
Impinger I -–1000 Series Service Manual - International  
6.  
Reassemble in reverse order.  
MAIN ORIFICE - BURNER  
1.  
2.  
3.  
Shut off power at main breaker.  
Shut off gas supply.  
Unbolt temperature control valve assembly (see Temperature Control Valve) and carefully rotate to  
access main orifice bracket.  
NOTE: Be sure not to damage capillary tube.  
Remove main orifice from orifice bracket.  
Reassemble in reverse order.  
4.  
5.  
6.  
Check all gas fittings for leaks.  
POTENTIOMETER - CONVEYOR SPEED CONTROL  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
Shut off power at main breaker.  
Remove control panel top and front panel.  
Remove conveyor speed control dial.  
Remove mounting nut from pot. shaft.  
Remove pot. from front panel.  
Disconnect pot. wiring from conveyor control board.  
Remove pot. assembly.  
Reassemble in reverse order.  
DIAL, CONVEYOR SPEED CONTROL (NON-DIGITAL DISPLAY OVENS)  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breakers.  
Remove dial by loosening set screws.  
Set new dial indicator to "000" in window and lock.  
Turn speed control pot. shaft to its minimum speed position.  
Slide dial assembly onto pot. shaft and tighten set screw.  
DIAL, CONVEYOR SPEED CONTROL (OVEN WITH DIGITAL DISPLAY)  
1.  
2.  
3.  
4.  
Shut off power at main breaker.  
Remove old dial by loosening set screw.  
Remove shaft locking nut.  
Install new shaft locking nut.  
NOTE: This is a friction type locking nut do not try to trim this nut to fit.  
Install new dial by sliding over pot. shaft and tightening set screw.  
5.  
CONVEYOR MOTOR REPLACEMENT - BODINE (SN 100-4389)  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control panel top and front panel.  
Remove the conveyor drive chain from the motor sprocket.  
Remove chain guard.  
Remove the sprocket from the conveyor motor shaft by loosening the set screws and sliding  
the sprocket off the shaft.  
Unplug the conveyor motor wiring harness.  
Remove the four (4) mounting bolts and nuts.  
Reassemble in reverse order and calibrate the conveyor D. C. control board (See D. C. Motor  
Control Board - Calibration, Bodine System).  
6.  
7.  
8.  
CONVEYOR MOTOR REPLACEMENT - BALDOR  
1000 SERIES SN 4390 - 14974  
1200 SERIES SN 4390 – 14791  
1.  
2.  
3.  
4.  
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove the conveyor drive chain from the motor sprocket.  
Remove chain guard.  
Impinger I -–1000 Series Service Manual - International  
63  
5.  
Remove the sprocket from the conveyor motor shaft by loosening the set screws and sliding  
the sprocket off the shaft.  
6.  
7.  
Unplug the wiring harness for the motor.  
Disconnect the red and black wires from the terminals on the tach. generator which is mounted on the  
top of the D.C. conveyor motor. Note which terminal the red and black wires are attached to.  
(Reversing the polarity will cause motor to run wide open with no control from the speed pot.)  
Remove the four (4) mounting bolts.  
Remove dust cover, remove tach., tach. bracket, coupling, and optical encoder assembly for  
reinstallation on new motor assembly. (See pages 104 & 105)  
8.  
9.  
10.  
Reassemble in reverse order and calibrate in the conveyor D. C. control board (See D. C. Motor Control  
Board - Calibration).  
CONVEYOR MOTOR REPLACEMENT - STEPPER  
1000 SERIES SN14975 AND ABOVE  
1200 SERIES SN14792 AND ABOVE  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove the chain guard.  
Remove the conveyor drive chain from the motor sprocket.  
Remove the sprocket from the conveyor motor shaft by loosening the set screw and sliding the sprocket  
off the shaft.  
6.  
7.  
8.  
9.  
Unplug the wire harness for the motor.  
Unplug the wire harness for the hall effect sensor (mounted on motor) from the conveyor speed control.  
Remove the four (4) mounting bolts and washers.  
Reassemble in reverse order and calibrate the control board. (See Stepper Control-Adjustment)  
NOTE: New drive motors will come as an assembly with Magnet and Hall Effect Sensor. The  
magnet and sensor will also be available as a replaceable spare part. (When replacing the magnet be  
sure  
to clean shaft and locate new magnet up against the shoulder on the shaft.)  
COUPLING AND ENCODER DISC  
1.  
2.  
3.  
4.  
5.  
6.  
Shut off power at main breaker.  
Remove conveyor motor assembly .  
Remove dust cover above motor.  
Loosen both allen set screws (.050 inch allen wrench) located on coupling hub.  
Remove 3 screws from tach. bracket, loosen the 4th.  
Remove encoder assembly, see optical encoder assembly in following procedure.  
Pushing coupling down on motor shaft. Swivel tach. bracket aside and remove coupling.  
To install, push coupling on to motor shaft. The encoder disc must be nearest motor.  
Refasten tach. bracket in proper alignment.  
Tighten the set screw on the tach. side first maintaining the .010 minimum dimension  
between the coupling hub and tach.  
Pull the coupling apart (approximately 1/8",3.2mm) and fasten the motor side set screw.  
If the optical encoder was loosened, refer to optical encoder in this section for adjustment.  
NOTE: The thin, slotted encoder disc must be handled with care so not to bend it.  
Recheck tightness on the set screws to be sure they are tight. If available, LOC TITE (the  
removable kind) should be used to secure set screws.  
7.  
8.  
9.  
10.  
OPTICAL ENCODER ASSEMBLY  
1.  
2.  
Shut off power at main breaker.  
Remove conveyor motor assembly .If replacing with new assembly, cut wires to remove as new wires  
and plug are provided. If only removing for access to coupling follow step 4.  
Remove pins from connectors with pin extractor tool, P/N 369600.  
3.  
4.  
5.  
6.  
Loosen dust cover screws and pull dust cover away from motor.  
Remove 2 screws from optical encoder and remove encoder.  
Reassemble in reverse order.  
To adjust optical encoder: Position the encoder assembly so it does not rub the coupler hub and is square  
with the encoder disc. The infrared light beam will be broken by slots in the encoder disc. The encoder  
disc should not touch the bottom or top of the optical encoder. If it does readjust the coupling. The digital  
speed readout may be observed to check proper adjustment of the optical encoder assembly.  
64  
Impinger I -–1000 Series Service Manual - International  
TACH. GENERATOR  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
Shut off power at main breaker.  
Remove conveyor motor assembly .  
Remove tach. cover plate and tach. Ieads. Mark lead position.  
Remove 2 slotted screws from dust cover base and remove dust cover.  
Loosen coupling set screw (.050 inch allen wrench).  
Remove tach. bracket from motor.  
Remove 4 screws from base of tach. and tach. is now free for removal.  
Reassemble in reverse order. Maintain spacing of .010 minimum between tach. Bracket  
and coupler hub.  
NOTE: If a new tach. generator is installed, the D.C. motor control board MUST BE  
RECALIBRATED There is no repair procedure for the tach. If defective, replace.  
CONVEYOR MOTOR CONTROL BOARD  
1.  
2.  
3.  
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove cover from relay box.  
SN 100-4389 BODINE SYSTEM  
Remove wires from terminal strip on control board making sure to mark wires so they  
will be reinserted on the proper terminal.  
Remove the four (4) hex head screws.  
Reassemble in reverse order and calibrate (See D. C. Motor Control Board - Calibration, Bodine System)  
SN 4390-14974 1000 SERIES GAS OVENS  
SN 4390-14791 1200 SERIES GAS OVENS  
4.  
5.  
Make note of wire number and location before removing them from the control board.  
POLARITY BETWEEN, T1-T2 AND A+ AND A- IS CRITICAL. The bottom mounting screw need  
only be loosened as the mounting bracket for the control board is slotted. Remove top two  
(2)mounting screws and remove control board.  
NOTE: Exchange boards on the mounting bracket before reinstallation.  
Reassemble in reverse order and calibrate (See D. C. Motor Control Board - Calibration)  
SN 14975 AND ABOVE 1000 SERIES GAS OVENS  
SN 14792 AND ABOVE 1200 SERIES GAS OVENS  
Make note of wire numbers and location before removing them from the control board.  
The bottom mounting screw need only be loosened as the mounting bracket for the control  
board is slotted. Remove top two (2) mounting screws and remove control board.  
Reassemble in reverse order and calibrate. (See Stepper Control-Adjustment)  
6.  
7.  
D. C. MOTOR CONTROL BOARD - CALIBRATION  
SN 100 to 4389 - BODINE SYSTEM  
1.  
2.  
3.  
Remove control panel top and front cover.  
Remove cover from relay box.  
Identify D. C. control board and calibrate as per the following instructions:  
NOTE: THE USE OF A DIGITAL VOLTMETER IS NECESSARY FOR PROPER ADJUSTMENT  
Check incoming AC voltage at L1 and L2. Should be 120 VAC 10%.  
Check field voltage at terminals F1 and F2. Should be 100 VDC 10 volts.  
Turn speed control dial clockwise to its maximum speed position.  
PLACE DIGITAL VOLTMETER LEADS ON terminal S1 and S2, adjust the max pot. for a  
reading of 3.4 VDC.  
Place METER LEADS on terminals A1 and A2. Adjust the reg. pot. for a reading of 125 VDC.  
NOTE: In some instances when the input AC voltage runs on the high side of the normal  
input range, you may have difficulty adjusting the max. pot. for a reading of 3.4 VDC. In this  
instance, a reading of 3.45 VDC is acceptable.  
Adjust speed pot to obtain the proper time setting for the conveyor to meet customers desired  
speed .  
Check conveyor travel in a no load situation to insure conveyor belt is traveling at a constant  
speed.  
Impinger I -–1000 Series Service Manual - International  
65  
GND  
S 3  
S 2  
S 1  
A 2  
A 1  
F 2  
F 1  
L 2  
3 A.  
FUSE  
L 1  
D. C. CONTROL BOARD "BODINE" S/N 100-4389  
REG  
MIN  
MAX  
TERMINAL  
STRIP  
3 A. FUSE  
D. C. CONTROL BOARD "BODINE" S/N 100 4389  
( TOP VIEW )  
D. C. MOTOR CONTROL BOARD  
SN 4390 - 14974 1000 SERIES GAS OVENS  
SN 4390 - 14790 1200 SERIES  
Three different styles of control boards have been used and all three are still usable. All three were supplied  
under the same part number.  
STYLE 1 CONTROL BOARD ADJUSTMENT  
NOTE: A digital meter must be used for this adjustment.  
Voltage at L1 and L2 terminals of the control board is to be 120 VAC 10%  
Connect a digital volt meter to terminals A+ and A-, set meter on 200 VDC scale.  
Turn speed control pot. (on oven control panel) to its maximum speed setting.  
Turn "MAX", "MIN", and "IR" pots counter clockwise until they stop (DO NOT turn CL pot.)  
Adjust "TACH" pot. so the volt meter indicates 110 VDC 0.5 volts.  
Adjust "IR" pot. to read between 1.5 and 2 VDC above tach. reading.  
(Example: If tach. reading would be 110.3 then adjust IR to between 111.8 VDC and  
112.3 VDC)  
Turn speed control pot. to its minimum speed setting.  
Adjust "MIN" pot. so the voltmeter indicates between 2 and 6 VDC.  
Turn speed control dial to obtain a reading of 22 VDC on your meter. Observe for approximately  
30 seconds to see if stable within 0.5 VDC. Repeat at 35 VDC.  
Check speed of conveyor and adjust time/temp. display if necessary.  
Seal pots with Glyptol or nail polish.  
66  
Impinger I -–1000 Series Service Manual - International  
L 1  
A+  
L 1  
A +  
.
4 A. FUSE  
1 A. FUSE  
CHOKE  
RESISTOR  
4 A. FUSE  
1 A. FUSE  
L 2  
L 2  
A -  
A -  
P 2  
P 2  
P 3  
P 1  
P 3  
P 1  
MAX  
MIN IR  
CL  
TACH T 1  
T 2  
MAX  
MIN IR  
CL TACH  
T 1  
T 2  
BOARD P/N 369155  
STYLE 1  
" B " BOARD P/N 369272  
STYLE 2 AND STYLE 3 CONTROL BOARD ADJUSTMENT  
NOTE: A digital meter must be used.  
Voltage at L1 and L2 terminals of the control board is to be 120 VAC 10%.  
Connect a digital voltmetet to terminal T1 and T2, set the meter on DC scale.  
Turn speed control pot. (on oven control panel) to its maximum speed setting.  
Adjust the "MAX" pot. so the voltmeter indicates 22.6 to 22.8 VDC.  
Turn the speed control pot. to its minimum speed setting.  
Adjust the "MIN" pot. so the voltmeter indicates 1.4 to 1.5 VDC.  
Reset the speed control pot. to its maximum speed setting and check if voltage is still at 22.6  
to 22.8 VDC. Readjust if necessary.  
Reset the speed control pot. to its maximum speed setting and check if voltage is still at 1.4 to  
1.5 VDC. Readjust if necessary.  
If readjustment of either the "MAX" or "MIN" pot. was necessary, the opposite must always be  
checked until both "MIN" and "MAX" are in proper adjustment.  
Measure the speed of the conveyor and adjust the time/temp. display if necessary.  
Seal pots with Glyptol or nail polish.  
NOTE: Occasionally a new board (Style 2 and 3 only) is so far out of adjustment that you will be  
unable to adjust the correct voltage. To correct, turn both the "MAX" and "MIN" pots 10 turns in  
either direction and then 5 turns in opposite direction. This will center the  
pots and allow them to be calibrated. If after this procedure, the board will not adjust,  
it is probably defective.  
Impinger I -–1000 Series Service Manual - International  
67  
L 1  
A+  
L 1  
A +  
4 A FUSE  
4
1 A FUSE  
RESISTOR  
CHOKE  
4 A FUSE  
1 A. FUSE  
L 2  
L 2  
A -  
A -  
P 2  
P 2  
P1  
P 3  
P 3  
P 1  
MAX  
MIN  
MAX  
MIN  
T 1  
T 2  
T 1  
T 2  
BOARD P/N 369155  
STYLE 2  
" B " BOARD P/N 369272  
L 1  
L 2  
A -  
A +  
RESISTOR  
CAPACITOR  
MIN MAX  
S 3  
S 1  
T 1  
T 2  
S 2  
BOARD P/N 369155  
STYLE 3  
68  
Impinger I -–1000 Series Service Manual - International  
STEPPER CONTROL - ADJUSTMENT  
S/N 14975 AND ABOVE 1000 SERIES GAS OVEN  
S/N 14792 AND ABOVE 1200 SERIES GAS OVEN  
CURRENT SENSE  
DO NOT ADJUST  
Heat Sink  
MOTOR  
J 6  
J 3  
J 1  
J 4  
J 5  
5 4 3 2 1  
Min.  
Conveyor  
Speed Adj.  
ON  
Max.  
Conveyor  
Speed Adj.  
Brown  
Red  
Blue Red  
Gray  
POWER  
LOCKED ROTOR  
POTENTIOMETER  
Black to #4  
White to #7  
To T/T display  
TIME/TEMP  
1.  
2.  
3.  
With power off, the five (5) dip switches located on the conveyor control (see drawing  
above) should be set as below.  
DIP SWITCHES  
CONTROL  
SWITCH POSITION  
1
2
3
4
5
OFF OFF ON OFF OFF  
With power off, the ten (10) dip switches located on rear of Time/Temp Display (see  
drawing on page 73) should be set as below.  
DISPLAY  
1
2
*
3
*
4
5
6
7
8
9
10  
SWITCH POSITION OFF  
ON OFF  
OFF ON  
ON OFF ON  
*SWITCH 2 - OFF FOR 60HZ, ON FOR 50HZ  
*SWITCH 3 - OFF FOR °F, ON FOR °C  
With conveyor running, set conveyor speed control so Time/Temp. Display indicates 5:00 minutes. Place  
a pan on the conveyor, measure (STOPWATCH) the time (SPEED OF PAN) of the leading edge in to  
leading edge out of oven. Turn the speed adjustment pot. on the rear of the Time/Temp. Display so  
display agrees with time measured by the stop watch. (See drawing on page 73).  
Turn conveyor speed control fully counterclockwise and adjust the stepper control maximum speed pot  
(refer to drawing above) so the display indicates 50 seconds.  
Turn conveyor speed control fully clockwise and adjust the stepper control minimum speed  
pot so the display indicates 30 minutes.  
NOTE: Repeat 4 and 5 to be sure settings are accurate.  
4.  
5.  
6.  
Turn power off and set #1 dip switch to its (ON/OFF) other position and verify that the  
conveyor reverses direction when power is applied. Set conveyor travel direction as  
customer requests.  
CAUTION: ALWAYS REMOVE POWER BEFORE CHANGING CONVEYOR DIRECTION.  
Impinger I -–1000 Series Service Manual - International  
69  
REVERSING CONVEYOR DIRECTION  
SN 100-4389 (BODINE)  
1.  
2.  
3.  
4.  
Shut off power at main breaker.  
Remove control panel top.  
Turn reversing switch (located on relay box) to obtain desired belt direction.  
Reassemble in reverse order.  
SN 4390-14974 1000 SERIES GAS OVEN  
SN 4390-14791 1200 SERIES  
All ovens leaving our plant are wired to operate conveyors from left to right. To reverse conveyor direction, use  
the following procedure.  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control panel top.  
Remove cover from relay box.  
Reverse wires fastened to terminals A+ and A-.  
Reverse wires fastened to terminals T1 and T2. Both set of leads must be reversed or oven will run at  
maximum speed with no speed adjustment possible.  
STEPPER DRIVE SYSTEM  
SN 14975 AND ABOVE 1000 SERIES GAS OVEN  
SN 14792 AND ABOVE 1200 SERIES  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control panel top.  
Remove relay box cover.  
Change position of dip switch #1 on stepper control board.  
Reassemble in reverse order.  
MINI CIRCUIT BREAKER  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control panel top and front panel.  
Disconnect two (2) wires from circuit breaker.  
Remove knurled mounting nut and remove.  
Reassemble in reverse order.  
NOTE: Be sure to reset breaker before operating.  
BEARING, CONVEYOR  
SN 100-2163  
1.  
2.  
3.  
Remove conveyor from oven and place of flat surface.  
Remove connecting links from conveyor belting. See Installation and Operating Instructions Manual.  
Remove conveyor belting from conveyor.  
DRIVE END  
1.  
2.  
3.  
4.  
5.  
Remove drive sprocket from drive shaft.  
Remove drive shaft from end of conveyor frame.  
Remove bearing retaining clips from ends of drive shaft.  
Slide bearing off drive shaft.  
Reassemble in reverse order.  
IDLER END  
4.  
5.  
6.  
Remove idler shaft from end of conveyor frame.  
Slide bearing off idler shaft.  
Reassemble in reverse order.  
70  
Impinger I -–1000 Series Service Manual - International  
BEARING, CONVEYOR  
SN 2164 AND ABOVE  
1.  
2.  
3.  
Remove conveyor from oven and place on a flat work surface.  
Remove connecting links from conveyor belting. See Installation and Operating Instructions Manual .  
Remove conveyor belting from conveyor  
DRIVE END  
4.  
5.  
6.  
7.  
Remove drive sprocket from drive shaft.  
Remove two (2) allen head bolts.  
Remove drive shaft and bearing assembly from conveyor frame.  
Reassemble in reverse order.  
IDLER END  
4.  
5.  
6.  
7.  
Remove idler shaft/bearing/mounting plate assembly from conveyor frame.  
Remove bearing/mounting plate assembly from conveyor.  
Remove bearing from mounting plate.  
Reassemble in reverse order.  
TRANSFORMER-STEPPER MOTOR CONTROL  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control panel top and front cover.  
Disconnect transformer wire harness.  
Remove two (2) mounting screws.  
Reassemble in reverse order.  
HALL EFFECT SENSOR – REPLACEMENT  
NOTE: There are two (2) styles of hall effect sensors - (See Drawing).  
OLD STYLE  
Remove two (2) screws from conveyor drive motor and break away hall effect sensor from motor shaft. To install  
new sensor, cut sensor bracket through center hole and install sensor half with one (1) screw. Reinstall plug on  
conveyor control.  
NEW STYLE  
Remove two (2) mounting screws and remove sensor from conveyor motor. Reinstall in reverse order.  
CUT  
HERE  
DISCARD  
NEW STYLE  
OLD STYLE  
Impinger I -–1000 Series Service Manual - International  
71  
TEMPERATURE GAUGE - REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control panel top.  
Disconnect thermocouple from temperature gauge.  
Remove two (2) mounting bolts and remove temperature gauge.  
Reassemble in reverse order.  
THERMISTOR - REPLACEMENT  
1.  
2.  
3.  
Shut off power at main breaker.  
Remove control panel top.  
Slide thermistor probe out of oven chamber.  
NOTE: Remove conveyor and bottom fingers to aid in removal and instaliaticn of thermistor probe.  
Disconnect wires from back of digital display at terminal strip (location #9-10).  
Reassemble in reverse order making sure the probe is placed securely in the wire form in the oven  
chamber.  
4.  
5.  
6.  
Reconnect to digital display and calibrate. (See Time/Temperature Display - Replacement and  
Calibration)  
To test the thermistor probe, refer to the following chart and instructions  
OVEN TEMPERATURE  
300º F  
182  
325º F  
138  
350º F  
102  
400º F  
62  
425º F  
48  
450º F  
38  
500º F  
24  
550º F  
16  
OHMS  
Place test pyrometer thermocouple and preheat oven as specified under temperature calibration.  
Disconnect the thermistor probe from terminals 9 and 10 and measure the resistance across the 2 yellow leads.  
Refer to the above chart to determine if probe is producing the proper resistance.  
EXAMPLE: The probe resistance at 500°F(260°'C) should be 24 ohms.  
TRANSFORMER, TIME/TEMP. DISPLAY  
1.  
2.  
3.  
4.  
Shut off power at main breaker.  
Remove control panel top.  
Remove relay box cover.  
Disconnect two (2) wires at base of transformer and three (3) wires at terminals 1,2, and 3 on Time/Temp  
Display.  
5.  
6.  
Remove two (2) mounting screws.  
Reassemble in reverse order.  
TIME/TEMPERATURE DISPLAY - REPLACEMENT & CALIBRATION  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control panel top.  
Disconnect wires from rear of display. Make note of wire numbers and location for reinstallation.  
Remove four (4) screws from display bezel (2 top/2 bottom) and remove display.  
Install new display in reverse order. Note dip switch position and calibrate display as follows:  
a) Check all wire connections to insure proper tightness.  
b) Check dip switch setting to insure proper positions for the model of oven:  
72  
Impinger I -–1000 Series Service Manual - International  
ALL 1000 & 1200 SERIES OVENS  
SWITCH SETTINGS  
1
2
3
4
5
6
7
8
9
10  
TYPE I  
OFF  
OFF*  
ON  
ON  
ON  
OFF*  
*
TYPE II  
TYPE III  
OFF  
OFF  
OFF*  
OFF*  
OFF** ON  
OFF** ON  
ON  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
ON  
ON  
(Baldor Motor)  
TYPE III  
(Stepper Motor)  
TYPE IV  
(Baldor Motor)  
TYPE IV  
(Stepper Motor)  
OFF  
OFF  
OFF  
OFF*  
OFF  
OFF  
OFF** ON  
OFF  
OFF  
OFF  
OFF  
ON  
**  
**  
ON  
ON  
OFF  
*These switches are for Hertz settings (OFF=60HZ) & (ON=50HZ)  
**These switches are for temperature read-out (OFF=Degrees F) & (ON=Degrees C)  
c)  
d)  
Turn power on.  
Calibrate time:  
Place an object on the conveyor belt and time with a stopwatch, the elapsed time for  
the object to travel through the oven. (Leading edge in to leading edge out.)  
Push in and hold the set button.  
Adjust the time calibration pot on the rear of the module until the display numbers  
match the measured time. Seal adjustment pot. with Glyptol or nail polish.  
Calibrate temperature:  
e)  
Place a temperature sensor in between top two fingers and set temperature control to  
500°F; allow temperature to stabilize.  
"Fine Tune" temperature setting to achieve measured temperature swings from  
497°F to 503°F. So if actual temperature falls between 497°F and 503°F the display  
must show 500°F. Adjust temperature calibration pot to achieve a display reading of  
500°F(260°C).  
DIP SWITCH MODULE  
(TYPE I AND II HAVE ONLY 6 SWITCHES)  
HI  
TEMP  
1
2
3
4
5
6
7
8
9
10  
TIME  
TEMP CAL  
1
2
3
4
5
6
7
8
9
10  
SWITCH POSITION  
ON  
OFF  
FROM  
TRANSFORMER  
TO  
SET  
SWITCH  
TO  
THERMISTOR  
PROBE  
TO CONVEYOR  
MOTOR PICK UP  
To identify the module, measure the width of the case.  
Type I is 51/8 inches wide  
Type II is 5 5/8 inches wide  
Type I & II have a 6 position dip switch module.  
Type III has a 10 position dip switch module.  
Type IV is 5 5/8 inches wide x 3 ¼ inches deep  
Impinger I -–1000 Series Service Manual - International  
73  
Type IV has adjustment pots. In the center board.  
If temperature is still inaccurate after above calibration and troubleshooting, use the following  
to check the High Temp. Pot. normally the High Temp. Pot. does not require  
adjustment. Occasionally the pot is accidentally moved or needs adjustment. Refer to the  
following drawing showing proper adjustment of the High Temp. Pot.  
BOTTOM OF TIME TEMP DISPLAY  
test leads here  
reading should be 26 .5 ohms if not, adjust.  
pot. range 0-34 ohms  
SWITCH, DISPLAY, SET  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control panel top.  
Disconnect wires from time/temp. display terminals 5 and 6.  
Pull off black operating knob and remove hex mounting nut.  
Reassemble in reverse order.  
PROCEDURE FOR USE OF TIME/TEMP. SIMULATOR  
NOTE: DO NOT CHANGE HI TEMP POT.  
TEST PROBES SHOULD  
READ 18 OHMS  
4
7
9
10  
Check incoming power to display at Terminals 1, 2, and 3. Approximately 13 VAC at 1-3, 6.5  
VAC at 1-2, 6.5 VAC at 2-3.  
WithpowerOFF,removeleadsfrom4,5,6,7,8,9,and10.Installtime/temp.simulator  
terminals 4,7,9,10.  
to  
To identify display type: (MEASURE WIDTH OF COVER ON DISPLAY)  
Type I is 51/8 inches wide.  
Type II is 5 5/8 inches wide.  
Type I & II have a 6 position dip switch module.  
Type III has a 10 position dip switch module.  
74  
Impinger I -–1000 Series Service Manual - International  
Dip Switch  
1
2
3
4
5
6
7
8
9
10  
TYPE I  
TYPE II  
TYPE III  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
ON  
NOTE: When on 50 HZ power, dip switch #2 must be "ON"  
With power ON turn time and temperature cal. pot. fully counterclockwise.  
Display should read: (Wait 15-20 seconds)  
TYPE I 9:30 + 10 sec.475 + 10°F  
TYPE II 9:20 + 10 sec. HHH  
TYPE III 9:35 + 10 sec. 635 + 10°F  
Turn time and temp. cal. pot. fully clockwise.  
Display should read: (Wait 15-20 seconds)  
TYPE I 10:20 + 10 sec. 615 + 10°F  
TYPE II 10:10 + 10 sec. 475 + 10°F  
TYPE III 10:20 + 10 sec. 475 + 10°F  
Turn time pot. to 10:00 minutes and temp. pot. to 540°F.  
Time reading 10:00 5 seconds.  
Temperature reading should be steady at 540°F + 10°F.  
If these readings are not achieved, replace display.  
NOTE: After simulator test is completed, the oven Time/Temperature Display must be re-calibrated.  
SWITCH REPLACEMENT (FAN, HEAT, CONVEYOR)  
1.  
2.  
3.  
4.  
5.  
6.  
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove switch access cover.  
Depress the spring clips on the sides of the switch and push out.  
Remove wires from back of switch. Note wire number and location.  
Install new switch in reverse order and check.  
SWITCH REPLACEMENT - (FAN SWITCH UPDATE)  
INSTALLATION OF DOUBLE POLE FAN SWITCH #369260 IN PLACE OF SINGLE POLE  
FAN SWITCH #350705  
NOTE:  
This change is not necessary for proper operation of oven nor is it  
permissible to change under warranty. Should be changed only at  
customer's request and their agreement to pay your bill.  
Allows time/temp. display, in older models, to operate same as current  
production models. Also allows locked time/temp. display (caused by  
voltage surge, interruption or spike) to be reset by fan switch rather than  
circuit breaker.  
ADVANTAGE:  
IDENTIFICATION:  
To determine which fan switch you have, observe if temperature displays  
stays on during cooling down. If it stays on , you have the single pole  
switch. If it goes out as soon as fan switch is turned off you have the double  
pole switch.  
REPLACEMENT: Replace single pole switch # 350705.  
Install double pole switch # 369260.  
Disconnect lead indicated by # in proper diagram and reroute as shown.  
Install jumper lead indicated by * in proper diagram.  
Reapply all other leads as removed.  
Impinger I -–1000 Series Service Manual - International  
75  
THE FOLLOWING ITEMS ARE USED IN THE MODEL 1030, 1046, 1047  
IMPINGER OVEN (EXPORT)  
AIR PRESSURE SWITCHES - REPLACEMENT AND ADJUSTMENT  
1.  
2.  
3.  
4.  
5.  
Remove control panel top.  
Disconnect wires from switch making note of wire number and location for reinstallation.  
Remove air tube from switch assembly.  
Remove switch from wire hanger.  
Install new switch in reverse order, make sure air tube is not blocked miss-aligned. Adjust as needed.  
To adjust the air pressure switch, remove snap on cover on the side of the switch to  
expose adjusting screw. To increase sensitivity, turn screw counter clockwise; to  
decrease sensitivity, turn screw clockwise. Check for proper line voltage switching from  
N.C. to N.O. as the air pressure switch closes.  
GAS VALVE - REPLACEMENT AND ADJUSTMENTS  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
Remove control panel top and front cover.  
Disconnect the gas piping from the back of the unit.  
Remove the four (4) screws from the incoming nipple mounting bracket.  
Remove incoming nipple.  
Disconnect two (2) plugs, (1 ) 3 prong and (1 ) 4 prong - Note location.  
Disconnect pipe union just above gas valve and remove assembly.  
Reassemble in reverse order (check all pipe fittings for leaks). After assembled, check  
for proper adjustment of gas pressure switch, 8.8 on dial for natural gas, 23 for L.P. Gas  
and 4.5 for town gas.  
8.  
9.  
Check and adjust manifold pressure. Remove pressure tap located in gas piping above  
the gas valve prior to the burner orifice and install manometer . Adjustment screw is  
located on the front of the valve, remove plastic cap and adjust as needed: 3.5" W.C. for  
Natural Gas and 10" W.C. for L.P.  
Check gas filter by removing cover plate (located on either side of valve). Remove four  
(4) screws and slide filter out of valve housing and inspect. Reassemble in reverse  
order and check for leaks around cover.  
SIDE VIEW  
TOP VIEW  
OUTPUT  
MANIFOLD  
PRESSURE  
ADJUSTMENT  
PRESSURE  
CONTROLLER  
ADJUSTMENT  
+
gnd  
ELECTRICAL  
CONNECTOR  
1
2
3
-
FILTER  
COVER  
PLATE  
FILTER  
COVER  
PLATE  
3
2
ELECTRICAL  
CONNECTOR  
gnd  
76  
Impinger I -–1000 Series Service Manual - International  
IGNITION CONTROL - REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
6.  
Remove control panel top and front cover.  
Loosen two (2) locking screws on front cover of relay (approx. 1/2 turn).  
Remove front portion of relay by pulling straight out (rocking motion).  
Remove wires from plug-in terminal strip, note wire numbers and locations.  
Remove two (2) screws from mounting bracket and remove.  
Reassemble in reverse order (NOTE: Plug in terminal strip is polarized and will only  
allow relay to plug in one direction, make sure manual reset button lines up with access  
hole in front cover.) Check system operation.  
HIGH - LIMIT THERMOSTAT - REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
6.  
Remove control panel top and front cover.  
Remove conveyor and fingers.  
Remove capillary bulb from wire form in oven chamber and pull through tube into control box.  
Remove two (2) wires from thermostat, note wire numbers and location for reinstallation.  
Remove screws from bracket and remove thermostat.  
Reassemble in reverse order making sure capillary tube is placed securely in the wire form.  
NOTE: Depress reset button to insure thermostat is set for operation.  
SPARK GENERATOR – REPLACEMENT  
1.  
2.  
Remove control panel top and front cover.  
Loosen two (2) locking screws (approx. 1/2 turn) on ignition control and remove front  
portion of relay exposing terminal strip.  
Remove two (2) wires for spark generator.  
Unplug connector on bottom of spark generator.  
Remove two (2) mounting screws and remove generator assembly.  
Reassemble in reverse order and check system operation.  
3.  
4.  
5.  
6.  
SOLENOID VALVE – REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
6.  
Remove control panel top and front cover.  
Disconnect pipe union just above gas valve assembly.  
Disconnect two (2) wires from solenoid, note wire number and location for reinstallation.  
Remove four (4) nuts from main orifice burner bracket and remove assembly.  
Replace valve and reassemble in reverse order.  
After assembly, check all fittings for leaks and check system operation.  
FLOW  
BURNER ALARM - REPLACEMENT  
1.  
2.  
3.  
4.  
Remove control panel top and front cover.  
Remove two (2) wires from alarm, note wire numbers and location.  
Remove retainer cover from alarm and remove assembly from mounting bracket.  
Reassemble in reverse order and check.  
Impinger I -–1000 Series Service Manual - International  
77  
BURNER ALARM LIGHT - REPLACEMENT  
1.  
2.  
3.  
4.  
Remove control panel top and front cover.  
Remove two (2) wires from light assembly, note wire number and location.  
Grasp body of light assembly and slide sideways to remove.  
Reassemble in reverse order and check.  
PILOT LIGHT (220V) - REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
Remove control panel top and front cover.  
Remove switch access cover.  
Remove two (2) wires from light assembly, note wire number and location.  
Grasp body of light assembly and slide sideways to remove.  
Reassemble in reverse order and check.  
IGNITER SENSOR ASSEMBLY - REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
6.  
Remove control panel top and front cover.  
Remove gas valve assembly (See Gas Valve)  
Remove screws from burner tube and pull burner assembly out.  
Remove wire connectors from igniter sensor assembly.  
Remove screws from mounting bracket and remove assembly.  
Reassemble in reverse order and check system operation.  
NOTE: After installation, check all pipe fittings for leaks.  
BURNER BLOWER MOTOR – REPLACEMENT  
1.  
2.  
3.  
4.  
Remove control panel top and front cover.  
Remove screws around blower tube.  
Disconnect motor wiring and remove.  
Reassemble in reverse order and check system operation.  
TEMPERATURE CONTROL BOARD - REPLACEMENT- MODEL 1030  
1.  
2.  
3.  
4.  
5.  
6.  
Remove control panel top and front cover.  
Remove potentiometer leads (3), note color and location.  
Remove thermocouple leads (2), note color and location (white:pos/red:neg.).  
Remove power and solenoid leads (4), note wire number and location.  
Remove screw and board assembly and replace.  
Reassemble in reverse order and check system operation.  
NOTE: When replacing #369174 with (new) #369728, turn temperature control to its  
maximum position and allow oven 30 minute preheat then calibrate board as follows:  
Place temperature probe between top fingers #2 and #3 (making sure probe is  
not touching any metal) and adjust potentiometer P6 to a Maximum temperature  
of 575°F.  
RED  
POTENTIOMETER  
transformer marked with  
2.5 K OHMS  
green gold or silver dot  
1
BLACK  
P 6  
P 5  
2
3
L 1 120 VAC  
L 2  
WHITE  
11  
10  
+
6
7
P 3  
9
-
LOAD  
THERMOCOUPLE  
TYPE J  
78  
Impinger I -–1000 Series Service Manual - International  
TEMPERATURE CONTROL POTENTIOMETER - REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
Remove control panel top and front cover.  
Remove one screw from control knob guard and move guard to one side.  
Remove knob and locknut on control pot shaft and pushout.  
Remove three (3) wires from temperature control board, note wire colors and location.  
Install new control pot. in reverse order and check system operation.  
NOTE: If temperature control knob is type with temperature numbers on it, adjust it to  
agree with the time/temp. display for knobs with reference numbers only, #9 is  
500°F/260°C.  
RELAY ASSEMBLY, BURNER BLOWER MOTOR - REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
Remove control box top and front cover.  
Remove cover from relay box.  
Remove wire from ignition control (#20).  
Remove two (2) wires from transformer (#21 and #23).  
Remove wire from burner blower motor connector plug (requires pin extractor tool (#369600) (#73).  
Remove nut and washer from rear of relay assembly and remove assembly.  
Install new relay in reverse order and check system operation.  
TEMPERATURE CONTROL - REPLACEMENT - 1046-1047  
1.  
2.  
3.  
4.  
5.  
Remove control panel top and front cover.  
Remove one screw from control knob guard and move guard to one side.  
Remove temp. control knob and locknut.  
Remove six (6) wires from temperature control board , note wire colors and location.  
Install new temperature control board in reverse order and check system operation.  
RELAY, GAS CONTROL - REPLACEMENT - MODEL 1046,1047  
1.  
2.  
3.  
4.  
5.  
6.  
Shut off power at main breaker.  
Remove control panel top and front cover.  
Remove cover from relay box.  
Disconnect all wires and mark for replacement.  
Remove relay by removing two (2) mounting screw.  
Reassemble in reverse order.  
TIME DELAY RELAY, 20 MINUTE - REPLACEMENT  
1.  
2.  
3.  
4.  
Remove control box top and front cover.  
Disconnect all wires and mark for replacement.  
Remove center mounting screw.  
Reassemble in reverse order.  
NOTE: Do not over tighten mounting screw as this may damage the internal  
electronic components.  
CONVEYOR BEARING REPLACEMENT AND SHAFT LUBRICATION – 1200 SERIES OVENS  
1.  
2.  
3.  
4.  
Remove conveyor from oven.  
Remove conveyor belt.  
Remove idle & drive shaft assemblies.  
Disassemble and clean/replace parts as needed. Use Molykote G-N Metal Assembly Paste for lubrication.  
Impinger I -–1000 Series Service Manual - International  
79  
PARTS / MODEL SERIES 1000 & 1200 - GENERAL  
LETTER  
PART NO.  
369003  
369207  
369337  
369110  
369209  
369828  
369157  
1534  
DESCRIPTION  
Door Hinge  
Handle Retainer  
Retainer (See Page E-18)  
Access Window (See Page E-18)  
Latch & Strike  
Handle Spacer  
Complete Door  
A
B
C
D
E
F
G
H
I
Finger Support Assy.  
Support Bracket Pins  
Strike Assy.  
369057  
369643  
1009  
J
Oven Top  
K
L
369062  
369046  
369367  
369140  
369903  
369141  
369139  
369058  
369211  
369369  
369203  
369749  
369204  
369373  
369205  
369651  
369379  
369052  
369030  
369328  
369904  
369218  
369053  
Top, Control Panel  
Flue Assy. (Gas)  
Flue Assy. (Electric)  
Compression Spring  
Flat Washer, 5/16”  
Conveyor Hold Down Bracket  
Shoulder Screw  
Baffle, Inlet and Outlet  
Thumb Screw  
Seam Cover, Conveyor Opening  
Stud Wing Head  
Chain Cover Assy. ( S/N Q14974 & Above)  
Split Ring Retainer  
Receptacle, Snap In  
Chain Guard Cover – S/N 2164 to Q14973  
Top, Chain Guard – S/N 2164 to Q14973  
Bottom Chain Guard – S/N 2164 to Q14973  
Adjustable Leg  
Caster – 6”  
Leg, Stand  
Insulation Holder  
Internal Crumb Pan  
Finger Housing  
Columnating Plates (See Installation Manual)  
Finger Cover  
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
AA  
BB  
CC  
DD  
EE  
FF  
GG  
HH  
JJ  
KK  
LL  
MM  
NN  
OO  
369055  
369748  
369690  
370048  
369673  
369244  
369887  
369886  
Bracket, Chain Cover – S/N Q14974 & Above  
Label, Time/Temp Display Cover  
Instrument Cover  
Thermostat Guard  
Instrument Cover Assy.  
Instrument Cover Label  
Window Fº  
Window Cº  
Display Bezel  
369199  
369246  
PP  
80  
Impinger I -–1000 Series Service Manual - International  
BLOW UP / 1000, 1200 – GENERAL  
Impinger I -–1000 Series Service Manual - International  
81  
PARTS / MODEL 1002-1003 , S/N 2584 TO 4389  
LETTER  
P/N  
DESCRIPTION  
Fuseholder  
Fuse, 3 Amp  
Fuse, 10 Amp  
Conveyor Speed Control Dial  
Sprocket, Drive - Prior to S/N 4390  
Switch, On/Off  
Lens, Red  
Pilot Light, 24 VAC  
Blower Air Switch  
Conveyor Motor- S/N 4389 & Below  
Brush  
Brush Cap  
Brush Spring  
Relay  
D. C. Conveyor Controller - S/N 4389 & Below  
Reverse Switch w/Harness - S/N 4389 & Below  
A
B
369012  
369013  
369014  
369064  
369066  
369260  
350225  
369104  
369025  
369022  
369113  
369114  
369115  
369032  
369008  
369080  
369543  
C
D
E
F
G
H
I
J
K
L
M
N
Transformer, 230/460/575 VAC  
See Burner Blower Motor - Page 55  
Transformer, 120/24V - 40VA  
Burner Blower Motor Kit  
Thermocouple  
N. L. A.  
369531  
369366  
369009  
369029  
369108  
369300  
369263  
369393  
369344  
369006  
369072  
369099  
369144  
369202  
369075  
369073  
369100  
369076  
369142  
369007  
369902  
369067  
369063  
O
P
Q
R
S
Temperature Gauge  
Thermostat Knob (Degree F)  
Thermostat Knob (Degree C)  
Gas Valve (Body Only), NAT/LP  
Ignition Control, NAT & LP  
Pilot Shut Off Valve  
Temperature Control Valve  
Main Burner Orifice, Natural Gas  
Main Burner Orifice, LP  
Pilot Shield, Extension  
Pilot Shield, Main  
Flame Sensor  
Pilot Orifice, Natural Gas  
Pilot Orifice, LP  
Burner Ignitor  
Flame Target  
T
U
V
W
X
Y
Z
A A  
B B  
C C  
D D  
Temperature Sensing Switch  
Sensing Rod Kit  
Air Switch Tube  
E E  
F F  
Conveyor Speed Controller - S/N 4389 & Below  
82  
Impinger I -–1000 Series Service Manual - International  
BLOW UP / 1002, 1003 – S/N 2584 TO 4389  
Impinger I -–1000 Series Service Manual - International  
83  
PARTS / MODEL 1002-1003, S/N 4390 & UP  
LETTER  
P/N  
DESCRIPTION  
A
B
369247  
357107  
369012  
369013  
369014  
369064  
369248  
369158  
350705  
369260  
350224  
369104  
369507  
Shaft Lock Ring  
Fuse Holder  
Fuse Holder  
Fuse, 3 Amp  
Fuse, 10 Amp  
C
D
Conveyor Speed Control Dial (Non-Digital Display Ovens)  
Knob  
10 Tooth Sprocket - S/N 4390 & Above  
Switch, ON/OFF  
Double Pole Fan Switch  
Lens, Yellow  
Pilot Light, 24 VAC  
E
F
G
H
I
J
K
Cooling Fan Thermostat  
SEE PAGE 104  
L
M
N
369025  
369032  
369155  
357028  
369201  
369240  
369007  
369173  
369363  
369543  
N. L. A  
369531  
369366  
369331  
369193  
369167  
369172  
369029  
369108  
369300  
369263  
369393  
369344  
369006  
369072  
369099  
369144  
369202  
369075  
369073  
369100  
369076  
369142  
369154  
369124  
369535  
369067  
369152  
Blower Air Switch  
Relay  
Conveyor Motor Control Board  
Fuse, Non Delay, 1A 250V  
Fuse, 4 Amp, 250V  
O
P
Q
R
S
T
U
V
W
X
Y
Z
Hi Hat  
Temperature Sensing Switch  
Control Transformer  
Unit Relay Cover, Top LH  
Transformer, 230/460/575  
See Burner Blower Motor - Page 55  
Transformer, 120/24V - 40VA  
Burner Blower Motor Kit  
Finger Guard, Cooling Fan  
Thermistor Probe  
Set Switch Assy.  
Digital Display  
Temperature Gauge  
Thermostat Knob (Degree F)  
Thermostat Knob (Degree C)  
Gas Valve (Body Only), NAT/LP  
Ignition Control, NAT & LP  
Pilot Shut Off Valve  
Temperature Control Valve  
Main Burner Orifice, Natural Gas  
Main Burner Orifice, LP  
Pilot Shield, Extension  
Pilot Shield, Main  
Flame Sensor  
Pilot Orifice, Natural Gas  
Pilot Orifice, LP  
Burner Ignitor  
Flame Target  
AA  
B B  
C C  
D D  
E E  
F F  
G G  
H H  
I I  
JJ  
K K  
L L  
MM  
0.7 Amp Circuit Breaker  
Cooling Fan, Control Box  
Cord Set, Cooling Fan  
Air Switch Tube  
N N  
O O  
Oven Conveyor Control Pot.  
84  
Impinger I -–1000 Series Service Manual - International  
BLOW UP / 1002, 1003 – S/N 4390 & ABOVE  
Impinger I -–1000 Series Service Manual - International  
85  
PARTS / MODEL 1006  
LETTER  
P/N  
DESCRIPTION  
Shaft Lock Ring  
Fuse Holder  
Fuse, 3 Amp  
Fuse, 10 Amp  
Knob  
10 Tooth Sprocket - S/N 4390 & Above  
Switch, ON/OFF  
Double Pole Fan Switch  
Lens, Yellow  
Pilot Light, 24 VAC  
Blower Air Switch  
Cooling Fan Thermostat  
SEE PAGE 104  
A
B
C
369247  
357107  
369013  
369014  
369248  
369158  
350705  
369260  
350224  
369104  
369025  
369507  
D
E
F
G
H
I
J
K
L
M
N
369032  
369155  
357028  
369201  
369240  
369007  
369902  
369173  
369363  
369543  
N. L. A.  
369531  
369366  
369331  
369193  
369167  
369172  
369108  
369300  
N.L.A.  
Relay  
Conveyor Motor Control Board  
Fuse, Non Delay, 1 A 250V  
Fuse, 4 Amp, 250V  
Hi Hat  
Temperature Sensing Switch  
Sensing Rod Kit  
Control Transformer  
Unit Relay Cover, Top LH  
Transformer, 230/460/575 VAC  
See Burner Blower Motor - Page 55  
Transformer, 120/24V - 40VA  
Burner Blower Motor Kit  
Finger Guard, Cooling Fan  
Thermistor Probe  
O
P
Q
R
S
T
U
V
W
X
Y
Z
Set Switch Assy.  
Digital Display  
A A  
Thermostat Knob (Degree F)  
Thermostat Knob (Degree C)  
Gas Valve  
Pilot Shut Off Valve  
Temperature Control Valve  
MAKE FROM 369067  
Main Burner Orifice, Natural Gas  
Main Burner Orifice, LP  
Pilot Shield, Extension  
Pilot Shield, Main  
Flame Sensor  
Pilot Orifice, Natural Gas  
Pilot Orifice, LP  
Burner Ignitor  
Flame Target  
BB  
C C  
D D  
E E  
F F  
369344  
369006  
369072  
369099  
369144  
369202  
369075  
369073  
369100  
369076  
369142  
369154  
369378  
369535  
369067  
369152  
G G  
H H  
I I  
JJ  
K K  
L L  
MM  
N N  
0.7 Amp Circuit Breaker  
Fan Motor, 230 VAC  
Cord Set, Cooling Fan  
Air Switch Tube  
O O  
PP  
Oven Conveyor Control Pot.  
86  
Impinger I -–1000 Series Service Manual - International  
BLOW UP / 1006  
Impinger I -–1000 Series Service Manual - International  
87  
PARTS / 1028-1029-1032  
LETTER  
P/N  
DESCRIPTION  
A
B
C
369247  
357107  
369014  
369335  
369195  
369304  
369013  
369248  
369064  
369066  
369158  
369260  
369605  
350224  
369128  
369025  
369022  
369113  
369114  
369115  
369302  
354258  
369127  
369368  
369154  
369118  
369007  
369902  
369119  
369134  
369155  
369008  
369640  
357028  
369201  
369240  
369193  
369167  
370046  
369172  
369029  
Shaft Lock Ring  
Fuseholder  
Fuse, 10 Amp  
Fuse MDL Time Delay, 1 Amp  
Fuse, 1 Amp FNM1  
Fuseholder for FNM1 Fuse  
Fuse, 3 Amp  
Knob  
Conveyor Speed Control Dial (Non-digital Display Ovens)  
Sprocket, Drive - S/N 4389 & Below and Q19078 & Above  
10 Tooth Sprocket - S/N 4390 to Q19077  
Switch, ON/OFF  
Transformer (Stepper)  
Lens, Yellow  
Neon Pilot Light, 125 VAC  
Blower Air Switch  
Motor,Conveyor S/N 4389 & Down See Pg 104 S/N 4390 & Up  
Brush (For 369022)  
Brush Cap (For 369022)  
Brush Spring (For 369022)  
Contactor, 50A, 120V  
Transformer, 230V-115V  
Hi Limit Thermostat  
Hi Limit Thermostat--Bulb & Capillary  
0.7 Amp Circuit Breaker  
Power Terminal Block  
Temperature Sensing Switch  
Sensing Rod Kit  
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
60A Fuseholder  
Fuse, 50A  
Conveyor Motor Control Board S/N 4390-Q19077  
Conveyor DC Control Board - S/N 4389 & Below  
Control Stepper, S/N Q19078 & Above  
Fuse, Non Delay, 1A 250V  
Fuse, 4 Amp, 250V  
Hi Hat  
Thermistor Probe  
Set Switch Assy.  
Button Only  
U
V
W
X
Digital Display  
Not Shown  
Temperature Gauge (Non-digital Display Ovens)  
Uses 369009 Thermocouple  
Knob, Temperature Control  
Potentiometer, Temp. Control & Harness  
Temperature Control Board  
Control Transformer  
Thermocouple Probe Assy.  
Relay  
Cooling Fan, Control Box  
Y
Z
369342  
369340  
369132  
369173  
369131  
369032  
369124  
A A  
B B  
C C  
D D  
E E  
88  
Impinger I -–1000 Series Service Manual - International  
BLOW UP / 1028, 1029, 1032  
Impinger I -–1000 Series Service Manual - International  
89  
PARTS/ MODEL 1030  
LETTER  
P/N  
DESCRIPTION  
A
B
C
D
369247  
369248  
357107  
369013  
369014  
369260  
350224  
369507  
369158  
Shaft Lock Ring  
Knob  
Fuse Holder  
Fuse, 3 Amp  
Fuse, 10 Amp  
Double Pole Fan Switch  
Lens, Yellow  
Cooling Fan Thermostat  
10 Tooth Sprocket  
See Page 104  
E
F
G
H
I
J
K
369154  
369007  
369902  
369032  
369575  
369543  
369155  
369640  
369240  
369381  
369173  
369574  
369579  
369331  
369368  
369573  
369728  
369085  
369736  
369398  
369572  
369167  
369172  
350225  
369522  
369520  
369366  
369589  
369548  
369571  
369570  
369580  
369542  
0.7 Amp Circuit Breaker  
Temperature Sensing Switch  
Sensing Rod Kit  
L
M
N
O
Relay  
Differential Air Pressure Switch  
Transformer, 230/460/575 VAC  
Conveyor motor Control Board, S/N 17170 & Below  
Control, Stepper S/N 17171 & Above  
Hi-Hat  
Fan Relay  
Control Transformer  
Spark Generator  
Alarm (Burner Shutdown)  
Finger Guard, Cooling Fan  
Thermostat, Hi-Limit  
Ignition Control, 220 VAC  
Temperature Control (Thermostat)  
Junction Box  
P
Q
R
S
T
U
V
W
X
Y
Z
Terminal, 3 Pole  
AA  
BB  
CC  
DD  
EE  
FF  
GG  
HH  
4” Cover, Junction Box-Blank  
Burner Shutdown Light  
Set Switch Assy.  
Digital Display  
Lens, Red  
Knob, Thermostat – Thermologic  
Thermologic, Potentiometer  
Burner Blower Motor S/N 17170 & Below  
Burner Blower Motor, 220V S/n 17171 & Above  
Coil, Asco Valve  
II  
JJ  
KK  
LL  
MM  
NN  
OO  
PP  
QQ  
Connector, 4 Pole  
Connector, 3 Pole  
Gas Valve, Multi – Block  
Solenoid, 2 Way Valve  
Main Burner Orifice Nat.  
Ignitor Sensor Probe  
Pilot Light, Harness  
Oven Conveyor Control Pot.  
Speed Pot., Stepper Control S/N 17171 & Above  
Fan Motor, 230 VAC  
Transformer, Stepper  
369590  
369382  
369152  
369391  
369378  
369605  
RR  
Not Shown  
90  
Impinger I -–1000 Series Service Manual - International  
BLOW UP / 1030  
Impinger I -–1000 Series Service Manual - International  
91  
PARTS / 1042, 1043  
LETTER  
P/N  
DESCRIPTION  
A
B
C
D
E
369378  
369247  
369248  
357107  
369013  
369014  
369260  
350224  
369067  
369507  
369158  
369066  
369025  
369032  
369543  
369155  
369640  
369240  
369173  
369007  
369902  
369154  
369393  
369331  
369085  
353082  
369398  
369317  
369167  
369046  
369172  
369316  
369263  
369344  
369086  
369398  
369072  
369099  
369144  
369202  
369075  
369073  
369100  
369076  
369142  
369366  
369531  
369270  
Fan Motor, 230 VAC  
Shaft Lock Ring  
Knob  
Fuse Holder  
Fuse, 3 Amp  
Fuse, 10 Amp  
Double Pole Fan Switch  
Lens, Yellow  
F
G
H
I
Air Switch Tube  
Cooling Fan Thermostat  
10 Tooth Sprocket, S?n 4390 – Q14970  
Sprocket, ½” – S/n Q14971 & Above - See Page 104  
Blower Air Switch  
J
L
M
N
O
Relay  
Transformer, 230/460/575 VAC  
Conveyor Motor Control Board – S/N 4390 – Q14970  
Control, Stepper, S/n Q14971 & Above  
Hi-Hat  
Control Transformer  
Temperature Sensing Switch  
Sensing Rod Kit  
.7 Amp Circuit Breaker  
Ignition Control NAT/LP  
Finger Guard, Cooling Fan  
Junction Box  
P
Q
R
S
T
U
V
W
X
Y
Z
Terminal Lug  
4” Cover, junction Box-Blank  
Pot., Temperature Adjustment w /Faceplate  
Set Switch Assy.  
Button only  
Digital Display  
Knob, Temperature Adjustment  
Gas Valve (Body Only), NAT/LP  
Pilot Shut Off Valve  
Pilot Line Assy., S/N 121 & Above  
Solenoid Valve, NAT & LP  
Main Burner Orifice, Nat. Gas  
Main Burner Orifice, LP gas  
Pilot Shield, Extension  
Pilot Shield, Main  
Flame Sensor  
Pilot Orifice, Nat. Gas  
Pilot Orifice, LP Gas  
Burner Igniter  
Flame Target  
Burner Blower Motor Kit  
Transformer, 120/24V – 40 VA  
Electronic Temperature Control  
AA  
BB  
CC  
DD  
EE  
FF  
GG  
HH  
JJ  
KK  
LL  
MM  
NN  
OO  
PP  
QQ  
92  
Impinger I -–1000 Series Service Manual - International  
BLOW-UP / 1042, 1043  
Impinger I -–1000 Series Service Manual - International  
93  
PARTS / 1033, 1034, 1046, 1047  
LETTER  
P/N  
DESCRIPTION  
A
B
C
D
369247  
369248  
357107  
369013  
369014  
369603  
369066  
369260  
350224  
369572  
369507  
369422  
369253  
369605  
369508  
369640  
369173  
369543  
369368  
369331  
369579  
369574  
369573  
369771  
369580  
369571  
369570  
369398  
369193  
369172  
369801  
369131  
369072  
369099  
369144  
369202  
369075  
369073  
369100  
369076  
369142  
369589  
369736  
369737  
369575  
369124  
369391  
369898  
Shaft Lock Ring  
Knob  
Fuse Holder  
Fuse, 3 Amp  
Fuse, 10 Amp  
E
F
G
H
J
Motor, Gear Box Assy.  
Sprocket, 10 Tooth  
On/Off  
Lens, Yellow  
Burner Light  
Cooling Fan Thermostat  
Relay, 240V  
Relay, 120V  
Transformer, Stepper Control  
Timer, 20 Minute  
Control, Stepper  
Transformer, Control  
Transformer, Power  
Thermostat, Hi-Limit  
Finger Guard  
K
L
M
N
O
P
Q
R
S
T
U
V
W
Alarm  
Spark Generator  
Ignition Control  
Push Button Switch  
Gas Valve (Multi Block)  
Connector, 4- Pole  
Connector, 3- Pole  
Solenoid Valve, Nat & LP Gas  
Thermistor Probe  
Time/Temp Display  
Temperature Control  
Thermocouple  
Main Burner Orifice, Nat. Gas  
Main Burner Orifice, LP Gas  
Pilot Shield, Extension  
Pilot Shield, Main  
Flame Sensor  
Pilot Orifice, Nat. Gas  
Pilot Orifice, LP Gas  
Burner Igniter  
Flame Target  
Burner Blower Motor  
Magnet  
X
Y
Z
AA  
BB  
DD  
EE  
FF  
GG  
HH  
JJ  
KK  
LL  
MM  
NN  
OO  
PP  
QQ  
RR  
SS  
TT  
Sensor, Hall Effect  
Differential Air Pressure Switch  
Cooling Fan  
Potentiometer, Conveyor  
Flame Monitor, 1033/ 1034  
UU  
94  
Impinger I -–1000 Series Service Manual - International  
BLOW-UP / 1033, 1034, 1046, 1047  
Impinger I -–1000 Series Service Manual - International  
95  
PARTS / 1228-1229  
LETTER  
P/N  
DESCRIPTION  
A
B
C
369247  
357107  
369013  
369014  
369335  
369248  
369252  
369260  
350224  
369128  
369025  
369302  
354258  
369127  
369118  
369007  
369902  
369119  
369134  
369193  
369167  
370046  
369172  
369342  
369340  
369132  
369131  
369173  
369032  
369124  
369535  
369067  
369253  
369254  
369652  
Shaft Lock Ring  
Fuse Holder  
Fuse, 3 Amp  
Fuse, 10 Amp  
Fuse MDL Time Delay, 1 Amp  
Knob  
Paddle Switch  
Switch, ON/OFF  
Lens, Yellow  
Neon Pilot Light, 125 VAC  
Blower Air Switch  
Contactor, 50A, 120V  
Transformer, 230V-115V  
Hi Limit Thermostat  
60A Fuseholder  
Temperature Sensing Switch  
Sensing Rod Kit  
60A Fuseholder  
Fuse, 50A  
Thermistor Probe  
Set Switch Assy.  
Button Only  
D
E
F
H
I
J
K
L
M
N
O
Q
R
S
T
U
V
W
X
Y
Z
Digital Display  
Knob, Temperature Control  
Potentiometer, Temp. Control &Harness  
Temperature Control Board  
Thermocouple Probe Assy.  
Control Transformer  
Relay  
Cooling Fan, Control Box  
Cord Set, Cooling Fan  
Air Switch Tube  
AA  
B B  
C C  
D D  
Speed Pot., "A" S/N 14974 & Below  
Speed Pot., "B" S/N 14974 & Below  
Speed Pot. (Stepper) S/N 14974 & Above  
96  
Impinger I -–1000 Series Service Manual - International  
BLOW UP / 1228, 1229  
Impinger I -–1000 Series Service Manual - International  
97  
PARTS / 1242, 1243  
LETTER  
P/N  
DESCRIPTION  
A
B
C
369247  
357107  
369013  
369014  
369248  
369252  
369260  
350224  
369131  
369507  
369025  
369032  
369363  
369543  
369173  
369393  
369331  
369366  
369317  
369193  
369167  
369172  
369316  
369263  
369344  
369086  
369398  
369072  
369099  
369144  
369202  
369075  
369073  
369100  
369076  
369142  
369933  
369007  
369902  
369944  
369067  
369104  
369652  
369378  
369531  
369270  
Shaft Lock Ring  
Fuse Holder  
Fuse, 3 Amp  
Fuse, 10 Amp  
Knob  
Paddle Switch  
Switch, On/Off  
Lens, Yellow  
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
Thermocouple  
Thermostat, Cooling Fan  
Air Pressure Switch  
Relay  
Cover, Relay  
Transformer, Power  
Transformer, 12.6 VAC  
Ignition Control  
Finger Guard  
Burner Blower Motor  
Temperature Control Pot.  
Thermister  
Set Switch  
Time/Temp. Display  
Temperature Dial  
Gas Valve Nat/LP (Body Only)  
Pilot Shut-Off Valve  
Pilot Line  
Solenoid Valve Nat. & LP  
Main Burner Orifice, Nat. Gas  
Main Burner Orifice, LP Gas  
Pilot Shield, Extension  
Pilot Shield, Main  
Flame Sensor  
Pilot Orifice, Nat. Gas  
Pilot Orifice, LP Gas  
Burner Igniter  
Flame Target  
Flange, Burner  
AA  
BB  
CC  
DD  
EE  
FF  
GG  
HH  
II  
JJ  
KK  
LL  
MM  
NN  
OO  
PP  
QQ  
Temperature Sensing Switch  
Rod, Sensing Kit  
Washer  
Air Switch Tube  
Pilot Light, 24 VAC  
Conveyor Pot. Assy.  
Cooling Fan Control Box  
Transformer, 120/24, 40 VA  
Temperature Control  
98  
Impinger I -–1000 Series Service Manual - International  
BLOW - UP / 1242, 1243  
Impinger I -–1000 Series Service Manual - International  
99  
PARTS / OVEN BACK – GAS  
LETTER  
P/N  
DESCRIPTION  
A
B
369048  
369212  
369214  
369192  
369045  
369306  
369646  
369647  
369213  
Motor and Fan Cover  
Motor, S/N begins with a"Q"  
Motor, 50 Hz, 240V  
Capacitor 7.5 MFD, 370 VAC  
Oven Back- S/N 4612 & Below  
Oven Back Assy. - S/N 4613 & Above  
Rod, Stand Off  
Inlet Panel, 16"  
Fan, S/N begins with a "Q"  
See Page 108  
See Conversion Kits Below  
Heat Slinger Bar  
Motor Support Assy - S/N Q4613 & Above  
Motor Mount Support Assy. - S/N 4612 & Below  
Oven Fan Motor- S/N 4612 & Below  
Motor Cooling Fan  
Wire Form, Thermostat Bulb  
Wire Form, Thermostat Bulb -1040 Series  
Cone Conversion Kit 60 HZ  
Replaces N.L.A. Fan Assy. with New Style Oven Back Assy.  
Cone Conversion Kit 50 HZ  
Replaces N.L.A. Fan Assy. with New Style Oven back Assy.  
C
D
E
F
G
H
I
N.L.A.  
369026  
369215  
369028  
369020  
369027  
369545  
369547  
369318  
J
K
L
M
N
Not Shown  
Not Shown  
369321  
100  
Impinger I -–1000 Series Service Manual - International  
BLOW UP / OVEN BACK – GAS  
Impinger I -–1000 Series Service Manual - International  
101  
PARTS / OVEN BACK- ELECTRIC  
LETTER  
P/N  
DESCRIPTION  
A
B
369699  
369212  
369214  
369192  
369307  
369122  
369287  
369315  
369647  
369213  
Rear Cover Assy.  
Motor, S/N begins with a "Q"  
Motor, 50 Hz, 240V  
Capacitor 7.5 MFD, 370 VAC  
Oven Back Assy. - S/N 4768 & Above  
240V Heating Element  
208V Heating Element  
220V Heating Element  
Inlet Panel, 16"  
C
D
E
F
G
H
I
Fan, S/N begins with a "Q"  
See Detail Page 108  
See Conversion Kits Below  
N.L.A  
J
K
L
369646  
369026  
369215  
369028  
369020  
369027  
369547  
369319  
Rod, Stand Off  
Heat Slinger Bar  
Motor Support Assy - S/N Q4768 & Above  
Motor Mount Support Assy. - S/N Q4767 & Below  
Oven Fan Motor- S/N Q4767 & Below  
Motor Cooling Fan  
Wire Form, Thermostat Bulb- Electric Ovens  
Cone Conversion Kit 208V 60 HZ  
Replaces N.L.A. Fan Assy. with New Style Oven Back Assy  
Cone Conversion Kit 240V 60 HZ  
Replaces N.L.A. Fan Assy. with New Style Oven Back Assy.  
Cone Conversion Kit 220V 50 HZ  
Replaces N.L.A. Fan Assy. with New Style Oven Back Assy.  
Cone Conversion Kit 240V 50 HZ  
Replaces N.L.A. Fan Assy. with New Style Oven Back Assy.  
M
N
O
Not Shown  
Not Shown  
Not Shown  
Not Shown  
369320  
369322  
369323  
102  
Impinger I -–1000 Series Service Manual - International  
BLOW UP / OVEN BACK – ELECTRIC  
Impinger I -–1000 Series Service Manual - International  
103  
PARTS / CONVEYOR MOTOR ASSEMBLY S/N 4390 & ABOVE  
LETTER  
P/N  
DESCRIPTION  
A
369291  
369384  
369294  
369296  
369290  
369151  
369146  
369294  
369292  
369297  
369156  
369293  
369150  
369298  
369299  
350247  
369295  
369603  
369737  
369900  
369658  
369736  
Motor, DC - Conveyor  
Motor Brush Assy.  
#4 Lockwasher  
B
C
D
E
F
G
H
I
Screw, 4-40 x 1/4  
Optical Encoder Assy.  
Coupling and Encoder Disc (.050 in. Allen Wrench included)  
Hex Nut, 4-40  
#4 Lockwasher  
Bracket, Tach. Generator  
Screw, 6-32 x 1/4  
#6 Lockwasher  
Screw, 4-40 x 3/8  
Tach. Generator  
Dust Cover  
Bushing  
Screw, 10-32 x 3/8  
#10 Lockwasher  
Stepper Motor Gearbox Assy. - includes R, S, T, U  
Hall Effect Sensor  
#8 Lockwasher  
J
K
L
M
N
O
P
Q
R
S
T
Screw, 8-32 x 1/4  
Magnet  
U
104  
Impinger I -–1000 Series Service Manual - International  
BLOW UP / CONVEYOR MOTOR ASSEMBLY S/N 4390 & ABOVE  
Impinger I -–1000 Series Service Manual - International  
105  
PARTS / SERIES 1000 – CONVEYOR  
LETTER  
P/N  
DESCRIPTION  
A
B
C
D
E
F
G
H
I
369002  
369314  
369835  
369312  
369160  
369641  
369220  
369005  
369237  
369161  
Tension Knob, Conveyor  
Roll, Conveyor-Notched  
Conveyor Frame Assy.  
Conveyor Shaft, Idler  
Conveyor Pan Stop  
Idle Bearing Bracket  
Idle Bearing  
Conveyor Belt Connecting Link  
Conveyor Drive Shaft  
Roller Chain Sprocket, S/N 2164-Q14973 (Gas)  
S/N 2164-Q19077 (Electric)  
Drive Sprocket S/N Q14974 & Above (Gas)  
S/N Q19078 & above (Electric)  
Drive Key  
Rod End, Female  
Screw 1/2-20 x 3/4  
Crumb Pan  
Conveyor Belt  
J
369066  
369413  
369219  
369644  
369206  
369163  
369362  
369143  
369036  
N.L.A.  
K
L
M
N
Conveyor Belt by Foot  
Crumb Pan  
Drive Bearing Assy.  
O
P
Q
Conveyor Frame  
(Replace with 369117 Complete Conveyor Assy.)  
Conveyor Guard Strap  
L.H. Conveyor Guard Assy.  
Snap Ring  
L.H. Conveyor Idler Bearing Assy.  
R.H. Conveyor Idler Bearing Assy.  
Idler Shaft  
Blank Drive Gear  
Notched Drive Gear  
Drive Shaft  
R.H. Conveyor Guard Assy.  
Conveyor Sprocket (Uses 369042 Key  
R
S
T
U
V
W
X
Y
Z
A A  
B B  
369380  
369060  
369037  
369034  
369035  
369042  
369039  
369038  
369043  
369059  
369040  
106  
Impinger I -–1000 Series Service Manual - International  
BLOW UP / SERIES 1000 CONVEYOR  
Impinger I -–1000 Series Service Manual - International  
107  
PARTS / SERIES 1200 - CONVEYOR CONTROL  
LETTER  
P/N  
DESCRIPTION  
A
B
C
D
E
SEE PAGE 104  
Fuseholder  
Fuse, 3 Amp  
Hi Hat  
Conveyor Motor Control, "A" S/N Q4613 to Q14973  
Conveyor Control (Stepper) S/N Q14974 & Above  
Fuse, Non Delay, 1A 250V  
Fuse, 4 Amp, 250V  
Conveyor Motor Control "B" S/N Q4613 to Q14973  
Fuse, Non Delay, 1A 250V  
Fuse, 4 Amp, 250V  
369012  
369013  
369240  
369155  
369640  
357028  
369201  
369272  
357028  
369201  
369154  
N. L.A.  
369665  
369289  
369242  
369696  
369124  
369605  
F
G
H
I
0.7 Amp Circuit Breaker  
Chain Guard  
J
Sprocket, 5/8" - S/N Q14791 & Below  
Sprocket, 1/2" (Stepper) S/N Q14791 & Above  
Clip, Chain Guard  
Cooling Fan, Control Box  
Transformer (Stepper)  
K
L
M
108  
Impinger I -–1000 Series Service Manual - International  
BLOW UP / SERIES 1200 – CONVEYOR CONTROL  
Impinger I -–1000 Series Service Manual - International  
109  
PARTS / SERIES 1200 – CONVEYOR  
LETTER  
P/N  
DESCRIPTION  
A
B
C
D
E
F
369277  
369275  
369276  
369274  
369279  
369278  
369241  
369242  
369005  
369280  
369284  
369039  
369038  
369281  
369160  
350238  
369697  
369282  
369206  
369273  
369249  
369250  
369817  
369818  
Retaining Block, Inner  
Flanged Bearing, .50 ID  
Inner Drive Shaft  
Flanged Bearing, .75 ID  
Retaining Block, Outer  
Outer Drive Shaft  
Sprocket 3/4" Bore  
Sprocket 1/2" Bore  
Conveyor Belt Connecting Links  
Idler Shaft, Inner  
Collar Shaft Spacer  
Blank Drive Gear  
Roll, Conveyor, Notched  
Idler Shaft, Outer  
Conveyor Pan Stop  
Nut, 10-24  
Lockwasher, SS #10  
Compression Spring  
Crumb Pan  
Complete Conveyor Belt  
Drive Chain, Long  
G
H
I
J
K
L
M
N
O
P
Q
R
S
Not Shown  
Not Shown  
Not Shown  
Not Shown  
Drive Chain, Short  
Drive Chain, Long (Stepper Drive)  
Drive Chain, Short(Stepper Drive)  
110  
Impinger I -–1000 Series Service Manual - International  
BLOW UP / SERIES 1200 – CONVEYOR  
Impinger I -–1000 Series Service Manual - International  
111  
112  
Impinger I -–1000 Series Service Manual - International  

IBM T84H User Manual
KitchenAid Cooktop KGCU407V User Manual
Life is good Life is Good Computer Monitor E2351VQ User Manual
Miele Cooktop KM 5950 User Manual
Mitsubishi Electronics DV300 User Manual
Moffat Blue Seal Evolution Series E514B LS User Manual
Philips 28PV5776 User Manual
Philips 29PT5618 User Manual
Philips 239C4Q User Manual
Philips DVP3360K User Manual