Kollmorgen M SS 005 03 User Manual

KOLLMORGEN  
www.DanaherMotion.com  
SERVOSTAR® MC  
M-SS-005-03  
Revision E  
Firmware Version 5.0.0  
Danaher Motion  
06/2005  
Table of Contents  
Table of Contents  
M-SS-005-03  
Rev E  
i
Table of Contents  
06/2005  
Danaher Motion  
ii  
Rev E  
M-SS-005-03  
Danaher Motion  
06/2005  
Table of Contents  
M-SS-005-03  
Rev E  
iii  
Table of Contents  
06/2005  
Danaher Motion  
iv  
Rev E  
M-SS-005-03  
Danaher Motion  
06/2005  
Table of Contents  
M-SS-005-03  
Rev E  
v
Table of Contents  
06/2005  
Danaher Motion  
vi  
Rev E  
M-SS-005-03  
Danaher Motion  
06/2005  
Table of Contents  
M-SS-005-03  
Rev E  
vii  
Danaher Motion  
06/2005  
Overview  
1.  
OVERVIEW  
This manual describes how to use the SERVOSTAR® MC (Multi-axis  
Controller) product. To execute the examples described in this manual, you  
must at least have a SERVOSTAR MC and BASIC Moves Development  
Studio® installed on your host computer. Some examples further require that  
you have a drive installed and connected to the MC using the SERCOS  
InterfaceTM cables. The SERVOSTAR® MC Installation Manual describes the  
procedures for all the necessary installations.  
Version 5.0.0 of the firmware incorporates many new commands, functions,  
and properties, and, in some instances, the behavior of functions,  
commands, and properties found in previous versions of the firmware have  
been changed. This edition of the SERVOSTAR® MC User's Manual applies  
to version 5.0.0 firmware, and is not necessarily backward compatible with  
previous versions of the firmware. If you have used previous versions of the  
MC, you may find that some functions, commands, or properties which you  
are familiar with, now have different behavior, or may no longer exist. Refer  
to the SERVOSTAR® MC Reference Manual for additional information, as it  
covers all versions of the firmware.  
When you complete this manual you should feel comfortable using all the  
features available in the SERVOSTAR MC. Related manuals:  
SERVOSTAR® MC Installation Manual  
SERVOSTAR® MC BASIC Moves Development Studio Manual  
SERVOSTAR® SC/MC API Reference Manual  
SERVOSTAR® MC InstallationManual  
The SERVOSTAR MC is Danaher Motion’s multi-axis controller. The MC has  
the features and performance required of today’s multi-axis controllers, and  
is designed for easy integration into motion control systems and for simplicity  
of use. The key benefits of the product are:  
Motion Components Guaranteed to Work Together  
Danaher Motion can provide a complete motion control system,including  
controller, drives, and motors. All the components are supplied by  
DanaherMotion, and are tested and guaranteed to work together.  
Complete Digital System at an Affordable Price  
The MC is fully digital, including communication with the drives. The analog  
interface is eliminated, but the price is competitive with analog systems.  
Local Field Bus for Simple Set up, Less Wiring, More Flexibility  
The MC communicates via fiber-optic cables using an industrial field bus  
called SERCOS. SERCOS greatly simplifies system set-up and wiring, while  
improving system flexibility and reliability compared to its analog  
counterparts.  
Windows®-Based Software Supports Microsoft Visual Basic™, Visual  
C++™, and other Popular Languages  
The MC product family includes Danaher Motion's Kollmorgen API, which  
allows Windows NT® application integration with the MC controller.  
Communication uses dual-port RAM, so the process is fast and reliable.  
M-SS-005-03  
Rev E  
1
 
Overview  
06/2005  
Danaher Motion  
1. 1  
SYSTEM HARDWARE  
The MC hardware is available in two types of implementation: a plug-in  
circuit board for a host computer, and a stand-alone model.  
The PCI plug-in board hardware installs in a host computer (typically a PC),  
running the Windows NT 4.0, Windows 2000/XP operating systems. The MC  
contains a fully-independent computer system., so it does not compete with  
the host processor system for resources. The MC uses Pentium 233 MHz or  
faster microprocessor to provide the power your system needs today, and  
the x86 upgrade path allows for future enhancement. The MC includes large  
on-board memory with ample capacity for your programs and enough space  
for expansion. There is also an onboard Flashdisk for storage of your  
programs.  
The stand-alone model of the MC is designed for installation as a component  
part in industrial equipment. It consists of the PCI version plug-in board and a  
power supply in an enclosure. The stand-alone model does not have a host  
CPU to provide a Windows operating system and environment, so it can not  
directly provide an operator interface. For interactive operation of the stand-  
alone MC, you will need a host computer running BASIC Moves  
Development Studio software and communicating with the MC via Ethernet  
or serial communications with Windows NT, Windows 2000/XP operating  
system. For additional information concerning communications configuration  
refer to the SERVOSTAR® MC Installation Manual.  
All implementation models of the SERVOSTAR MC are functionally  
equivalent for servo motion control  
1. 2  
1. 3  
OPERATING SYSTEM  
The SERVOSTAR MC is based on the VxWorks® RealTime Operating  
System (RTOS), providing a stable platform for the SERVOSTAR's software.  
VxWorks is produced by Wind River Systems, Incorporated. VxWorks is  
continuously evolving, providing a clear path for future upgrades to the MC.  
MC-BASIC LANGUAGE COMPILER  
The MC uses a language interpreter that semi-compiles commands so they  
typically execute in less than 5 microseconds. MC-BASIC® is true BASIC. It  
has familiar commands such as FOR…NEXT, IF…THEN, PRINTUSING,  
PEEK and POKE as well as common string functions such as CHR$,  
INSTR, MID$, and STRING$. It allows arrays (up to 10 dimensions) with full  
support for double precision floating-point math. MC-BASIC is extended to  
provide support for functions required for motion systems control, (e.g., point  
to point moves, circular and linear interpolation, camming, and gearing). In  
addition, there is support for multi-tasking and event-driven programs.  
Gearing and camming have the versatility required for motion control. You  
can slave any axis to any master. You can enable and disable gearing at any  
time. The gear ratio is expressed as a double-precision value. The MC also  
supports simulated axes, which can be master or slave in gearing and  
camming applications and incremental moves run by any axis, master or  
slave, at any time.  
2
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Overview  
Camming links master and slave axes by a cam table. Camming has all the  
features of gearing, plus the cam table can have any number of points. The  
cam points are in x-y format so spacing can be provided independently.  
Multiple tables can be linked together, allowing you to build complex cam  
profiles from simpler tables. There is a cycle counter that lets you specify  
how many cycles to run a cam before ending.  
The MC supports multi-tasking with up to 256 tasks, running at up to 16  
different priority levels. Each task can generate OnEvent(s), for code that you  
want executed when events occur such as switches tripping, a motor  
crossing a position, or just about any combination of factors.  
1. 4  
I/O  
The MC provides 23 optically-isolated inputs and 20 optically-isolated  
outputs as standard features, in addition to limit switches and other drive I/O  
points that are connected directly to the drives and transferred to the MC via  
SERCOS. Additionally, each SERVOSTAR drive provides hardware for six  
I/O points: three digital inputs, one digital output, a 14-bit analog input, and a  
12-bit analog output. An auxiliary encoder can also be connected to any  
SERVOSTAR drive.  
If you need more I/O, the MC includes a PC104 bus. Each MC can  
accommodate as many as two PC104 cards. You can also add I/O to your  
PC bus or other field buses such as DeviceNet and ProfiBus, and your  
application controls it all. The figure below shows the various possible I/O  
options.  
SERVOSTAR MC  
PC I/O Cards  
PCI Bus  
Standard I/O  
SERVOSTAR  
Auxillary I/O  
Host CPU  
SERCOS  
Field  
Bus  
PC-104  
Mezzanine Bus  
PC Field  
Bus Cards  
PC-104  
I/O Cards  
Field I/O  
1. 5  
SERCOS  
The SERCOS interface™ (developed in the mid-1980’s) provides an  
alternative to the analog interface for communicating between motion  
controllers and drives. In 1995, SERCOS became an internationally  
accepted standard as IEC 1491 and later was continued to standard IEC  
61491. The popularity of SERCOS has been steadily growing. All signals are  
transmitted between controller and drives on two fiber optic cables. This  
eliminates grounding noise and other types of Electro-Mechanical  
Conductance (EMC) and Electro-Mechanical Interference (EMI).  
M-SS-005-03  
Rev E  
3
 
Overview  
06/2005  
Danaher Motion  
Because SERCOS is digital, it can transmit signals such as velocity and  
position commands with high resolution. The SERVOSTAR® MC and  
accompanying drives ( SERVOSTAR CD series), support 32-bit velocity  
commands. This provides a much higher resolution than can be achieved  
with the analog interface. The most common SERCOS functions are  
provided in such a way that you do not have to be an expert to gain the  
benefits.  
1. 6  
1. 7  
API  
DanaherMotion's Kollmorgen API® is a software package that allows you to  
communicate with the SERVOSTAR MC from popular programming  
languages, such as Visual Basic. The API provides complete access to all  
the elements of your system across dual-port ram. See the SERVOSTAR®  
SC/MC API Reference Manual for more information.  
MULTI-TASKING  
The SERVOSTAR MC is a fully multi-tasking system (see figure below) in  
which you can create multiple tasks and multiple elements (e.g., axes) that  
operate independently of one another. Also, because the API supports  
multiple applications communicating concurrently, you can write one or more  
applications that have access to all of the tasks and elements.  
Axis 3  
Task 3  
3rd Party Soft PLC  
Axis 2  
Axis 1  
Task 2  
Task 1  
Visual C  
Visual BASIC  
Dual Port RAM  
Kollmorgen API  
Host CPU  
SERVOSTAR MC  
1. 8  
USER COMMUNICATION  
The ETHERNET and Serial ports of the MC are used for ASCII data transfer.  
Non-printable characters are sent using CHR$. Data access is stream-  
oriented. There is no data framing. MC Basic applications gain access to  
either raw serial port or TCP socket. The TCP socket guaranties error free  
data transfer, while the serial port does not offer error recovery. The  
transmitted data does not have any meaning in terms of directly controlling  
the MC.  
User communication provides the basic features of serial and TCP/IP data  
communication, which is not limited to a specific communication protocol,  
enabling the usage of any protocol over serial or TCP/IP through an MC  
application.  
4
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Overview  
1.8.1. Serial Communication  
The MC has two RS-232 ports, which can be used for user communication.  
When COM1 is used for communication with BASIC Moves over API, tasks  
cannot access it to eliminate interference with BMDS communications. Use  
DIPswitch bit #8 to configure this port:  
DIP Switch bit #8 state  
ON (default)  
OFF  
COM1 is reserved for communication with the host and cannot  
be used by any other application  
COM1 is available for user communication  
When DIPswitch bit # 8 is ON, the MC's firmware prints boot status  
messages from COM1 using the following serial communication parameters:  
Baudrate  
Parity  
9600 bps  
none  
Stopbits  
Databits  
1
8
State ON of DIPswitch read as 0.  
For example:  
Switches 6 & 8 are OFF. All others are ON.  
-->?sys.dipswitch bin  
0b10100000  
-->  
NOTE  
1.8.1.1. WITH HOST  
When DIPswitch #8 is ON, the MC can communicate with the host via serial  
port. This mode of communication requires Virtual Miniport driver, which is  
installed during setup of BMDS. The driver simulates Ethernet connection  
over serial interface using following fixed parameters:  
Baudrate  
115200 bps  
Parity None  
Stopbits  
Databits  
1
8
IP address  
Subnet mask  
192.1.1.101  
255.255.255.0  
All the parameters are fixed and cannot be modified.  
If the driver is installed correctly and BMDS is running, it appears in the list of  
Ethernet adapters as shown below:  
C:\>ipconfig /all  
Ethernet adapter Local Area Connection 5:  
Connection-specific DNS Suffix . . . . :  
Description . . . . . . . . . . . . . . : Giant Steps Virtual miniport  
Physical Address. . . . . . . . . . . . : 00-02-1B-D1-A5-FC  
DHCP Enabled. . . . . . . . . . . . . . : No  
IP Address. . . . . . . . . . . . . . . : 192.1.1.1  
Subnet Mask . . . . . . . . . . . . . . : 255.255.255.0  
Default Gateway . . . . . . . . . . . . :  
DNS Servers . . . . . . . . . . . . . . :  
M-SS-005-03  
Rev E  
5
 
Overview  
06/2005  
Danaher Motion  
1.8.1.2. OPEN SERIAL PORT  
Configurate the serial port with OPEN. Set the following port properties:  
BaudRate - baud rate of the device set to a specified value.  
Parity – enable/disable parity detection. When enabled, parity is odd or even.  
DataBits - number of data bits.  
StopBit - number of stop bits.  
Xonoff – sets raw mode or ^S/^Q flow control protocol mode (optional parameter  
disabled by default).  
For example:  
OPEN COM2 BUADRATE=9600 PARITY=0 DATABITS=8 STOPBIT=1 AS #1  
Opens COM2 at 9600 bps baud-rate, No parity, 8-bit data, 1 stop bit.  
OPEN assigns a device handle to the communication port. Any further  
references to the communication port uses the device handle number. The  
device handle range is 1…255. To change the communication parameters,  
close the serial port and reopen it using the new parameters. For more  
information, see PRINT # and INPUT$.  
1.8.2. TCP/IP Communication  
Use TCP/IP communication with other computers and intelligent I/O devices  
over the Ethernet network. MC-BASIC uses TCP/IP API (sockets).  
TCP/IP provides multi-thread communications. The same physical link  
(Ethernet) is shared between several applications. This way, the MC can  
connect to BASIC Moves and one or more intelligent I/O devices.  
The MC supports both client and server roles for TCP/IP communications.  
The TCP/IP client connects to a remote system, which waits for a connection  
while the TCP/IP server accepts a connection from a remote system.  
Usually, the MC serves as client while interfacing to an intelligent I/O  
connected to the LAN, and as a server when working toward remote host like  
a software PLC. The MC uses Realtek RTL8019AS Ethernet NIC at a bit rate  
of 10 M bps.  
1.8.2.1. SETUP  
TCP communication starts by opening a socket either to connect to a remote  
computer (remote host) or accept a connection from a remote host. Use  
CONNECT or ACCEPT, depending on the MC functionality (client or server).  
OPENSOCKET creates a TCP socket and assigns the socket descriptor to  
the specified device handle. The socket is created with OPTIONS  
NO_DELAY (send data immediately= 1). Otherwise, the data is buffered in  
the protocol stack until the buffer is full or a time-out is reached. This  
improves responsiveness when small amounts of data are sent. This option  
is recommended for interactive applications with relatively small data  
transfer. Otherwise, OPTIONS = 0.  
OPENSOCKET OPTIONS=1 AS #1  
OPENSOCKET assigns a device handle to the communication port (as  
OPEN). Any further reference to the communication port uses the device  
handle number. The device handle range is 1…255.  
6
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Overview  
There are several ways to set the IP address of the controller. By default, the  
MC boots without a valid IP address. The following options are available to  
set the IP address of the controller:  
Static IP address setting  
Use SYS.IPADDRESSMASK in the Config.prg file to assign the IP  
address and Subnet mask:  
SYS.IPADDRESSMASK=”212.25.84.109:255.255.255.128”  
Dynamic address setting by Windows API  
API assigns an IP address to the MC when it establishes TCP  
communication with the controller. The IP address and Subnet mask  
are taken out of a pre-defined address pool. BASIC Moves uses this  
address assigning method. Refer to the BASIC Moves Development  
Studio® User Manual and SERVOSTAR® MC Reference Manual for  
detailed information.  
DHCP  
IP address is assigned by the DHCP server. If your network does not  
support DHCP, the controller tries to get the address from the DHCP  
server and times out after few minutes. During that time, communication  
with the controller is not possible.  
SYS.IPADDRESSMASK=”dhcp”  
If DHCP is used, select Automatic connection method as shown below:  
Get the controller’s IP address  
Use SYS.IPADDRESSMASK to query the IP address and Subnet mask  
of the MC.  
-->?SYS.IPADDRESSMASK  
172.30.3.11:255.255.0.0  
The MC has several IP interfaces: Ethernet, IP over serial and IP  
over DPRAM. However SYS.IPADDRESSMASK is only valid for  
Ethernet interfaces. Others have fixed IP addresses, which  
cannot be changed.  
NOTE  
PING tests that a remote host is reachable. The remote host must  
support ICMP echo request.  
?PING(”212.25.84.109”)  
1.8.2.2. MC AS TCP CLIENT  
When acting as a client, the MC tries to connect to a remote server until a  
time out value expires or the connection is rejected. Use CONNECT when  
the MC acts as a client.  
M-SS-005-03  
Rev E  
7
Overview  
06/2005  
Danaher Motion  
The MC requests a connection from a remote host, according to a specific IP  
address and port. CONNECT blocks task execution until the connection is  
established or until the command fails. To unblock a task waiting in  
CONNECT, close the corresponding socket using CLOSE. In addition, killing  
a task (KILLTASK) blocked by CONNECT closes the socket to release the  
task. CONNECT may fail due to the following reasons:  
1. Invalid socket descriptor  
2. Remote host has no application attached to specified port.  
3. Destination address is not reachable  
The following example illustrates a typical procedure of establishing a  
connection to a remote host, and sending and receiving data:  
OPENSOCKET OPTIONS=0 AS #1  
CONNECT (#1,”212.25.84.100”,6002)  
PRINT #1,”HELLO”  
?INPUT$(LOC(1),#1)  
CLOSE #1  
1.8.2.3. MC AS TCP SERVER  
When acting as a server. the MC endlessly waits for a connection from the  
remote host. Use ACCEPT when the MC acts as server. ACCEPT binds a  
socket to a specified port and waits for a connection. Simultaneous  
ACCEPTs on the same port are not allowed. ACCEPT blocks the execution  
of the calling task until a connection is established. To unblock the task  
waiting in ACCEPT, close the corresponding socket with CLOSE. In addition,  
killing a task (KILLTASK) blocked in ACCEPT closes the socket and  
releases the task. The following example illustrates a typical procedure of  
waiting for a connection from a remote host, and sending and receiving data:  
OPENSOCKET OPTIONS=0 AS #1  
ACCEPT (#1,20000)  
PRINT #1,”HELLO”  
?INPUT$(LOC(1),#1)  
CLOSE #1  
1.8.3. Send /Receive Data  
Serial and TCP communication use the same commands to send and  
receive data. After establishing communication over TCP or after configuring  
the serial port communication parameters, send and receive data regardless  
the communication type. Data flow differences are communication speed  
and the size of the input and output buffers. TCP/IP communication uses  
larger communication buffers.  
1.8.3.1. RECEIVE DATA  
The input-buffer of the serial ports is a fixed512 bytes size. User  
communication allows receiving strings using INPUT$. To check if data is  
ready at the input buffer, use LOC. The following example checks the  
number of bytes available at the input buffers and reads all the available  
data:  
-->?LOC(1)  
11  
-->STRING_VAR = INPUT$(11, #1)  
-->?STRING_VAR  
Hello World  
8
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Overview  
If INPUT$ requests reading a data length larger than available data, the  
command returns only the available data:  
-->?LOC(1)  
11  
-->STRING_VAR = INPUT$(20, #1)  
-->?STRING_VAR  
Hello World  
LOC can be used within the INPUT$:  
STRING_VAR = INPUT$(LOC(1), #1)  
A partial read of the input buffer is allowed. This way, several calls to  
INPUT$ empty the input-buffer:  
-->?LOC(1)  
11  
-->STRING_VAR = INPUT$(3, #1)  
-->?STRING_VAR  
Hel  
-->?LOC(1)  
8
-->STRING_VAR = INPUT$(8, #1)  
-->?STRING_VAR  
lo World  
When calling INPUT$, the system does not wait for data. If the input-buffer is  
empty, the command returns without any return value:  
-->?LOC(1)  
0
-->STRING_VAR = INPUT$(10, #1)  
-->?len(STRING_VAR)  
0
1.8.3.2. SEND DATA  
PRINT # and PRINTUSING # send data over the serial port. Both  
commands use the same formatting as PRINT and PRINTUSING.  
PRINT # and PRINTUSING # appends a carriage-return (ASCII  
value 13) and line-feed (ASCII value 10) characters at the end of  
each message. To print a message without the terminating  
carriage-return and line-feed characters use a semicolon at the  
NOTE  
end of the command.  
For example, the following uses PRINT # to send data:  
-->STRING_MESSAGE = "ERROR"  
-->PRINT #1, STRING_MESSAGE,"A1.PCMD=";A1.PCMD;  
The output is:  
ERROR  
A1.PCMD=0.000000000000000e+00  
The values of the following variables are sent one after the other. The output  
is (hexadecimal) 0x37 0x28:  
I1=55  
I2=40  
PRINT #1, I1;I2  
The output is:  
5540  
M-SS-005-03  
Rev E  
9
Overview  
06/2005  
Danaher Motion  
1.8.3.3. SEND DATA BLOCK  
PRINTTOBUFF # and PRINTUSINGTOBUFF # allows buffering of data  
before actually being sent. This eliminates inter-character delays.  
printtobuff #handle,chr$(0); chr$(message_length);  
chr$(0);send=false  
printtobuff #handle,chr$(request[ii]);send=false  
printtobuff #handle,chr$(request[ii]);send=true  
1.8.3.4. SEND/RECEIVE NULL CHARACTER  
When using a specific protocol over Serial or TCP/IP ModBus RTU or  
ModBus TCP), the NULL character is part of the message. The message  
block cannot be saved in a STRING type variable since the NULL character  
terminates the string.  
To send a NULL character in a message, send the data as single bytes  
instead of a string type message:  
COMMON SHARED X[10] AS LONG  
X[1]=0x10  
X[2]=0  
X[3]=0x10  
PRINT #1, CHR$(X[1]);CHR$(X[2]);CHR$(X[3]);  
The output is the following stream of bytes:  
0x10, 0x0, 0x10  
When the received data contains a NULL character, read the data from the  
input buffer as single bytes instead of reading it into a string type variable.  
Convert the incoming data to a numeric value to get its ASCII value:  
DIM SHARED TEMP[10] AS DOUBLE  
FOR IDX = 1 TO LOC(1)  
TEMP[IDX] = ASC(INPUT$(1,#1))  
NEXT IDX  
The figure below gives a general description of the TCP/IP communication  
for both the client and host.  
Client  
Server  
Open TCP connection  
(open socket)  
Open Socket  
Listen to specific  
port and accept  
connection  
Connect to specific  
port and specific IP  
address  
Accept  
Connect  
Read  
Read  
Write  
Write  
Read  
Write  
Read  
Write  
Close  
Close TCP connection  
(close socket)  
1.8.3.5. CLOSE CONNECTION  
CLOSE closes the connection and releases the device handle:  
-->CLOSE #1  
10  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
BASIC Moves Development Studio  
2.  
BASIC MOVES DEVELOPMENT STUDIO  
BASIC Moves Development Studio (BMDS) provides Windows-based  
project control for each application. BASIC Moves Development Studio  
supports development for multi-tasking and also provides numerous tools  
and wizards to simplify programming the MC.  
BASIC Moves also provides modern debugging features such as allowing  
task control by visually setting breakpoints, watch variables, and single  
stepping. BASIC Moves automatically displays the data recorded on the MC  
during operation. BASIC Moves provides all the tools you need for  
developing and debugging your application. When you start Basic Moves,  
your first action is to select a method for communicating with your MC.  
If you are using either a PCI or ISA model MC, choose ISA/PCI Bus. If you  
are using a Stand-alone model MC, select either Serial Port or Ethernet  
(communication method configured for your system). For more information  
concerning communication with the stand-alone MC, refer to the Software  
Installation section of the SERVOSTAR® MC Installation Manual.  
2. 1  
COMMUNICATION  
Communicating with a stand-alone MC is not as automatic as is  
comunicating with a PCI or ISA plug-in MC. Assuming you have properly  
configured the communication method during installation of the BASIC  
Moves Development Studio on your host computer, there are still some  
operating procedures you may need to perform.  
If you configured Ethernet communications, subsequent communication  
with the MC is automatically enabled and no further intervention is needed  
unless you change the Ethernet network environment. If your network  
environment changes, you may need to edit the IP address file. Refer to  
the SERVOSTAR® MC Installation Manual for additional information.  
Ethernet  
The installation package includes the Virtual NIC device driver, which is  
started automatically by Basic Moves Development Studio. No special  
configuration is required. Refer to the SERVOSTAR® MC Installation  
Manual for additional information.  
Serial  
2. 2  
MC-BASIC  
The MC is programmed in MC-BASIC® (Motion Control BASIC), a version of  
the BASIC programming language enhanced for multi-tasking motion control.  
If you are familiar with BASIC, you already know much of MC-BASIC. For  
detailed information on any of the commands (including examples) used in  
MC-BASIC, refer to the SERVOSTAR® MC Reference Manual.  
M-SS-005-03  
Rev E  
11  
 
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
To develop your application on the MC, you must install BASIC Moves  
Development Studio. Refer to the software installation section of the  
SERVOSTAR® MC Installation Manual for detailed instructions.  
2.2.1. Instructions  
Instructions are the building blocks of BASIC. Instructions set variables, call  
functions, control program flow, and start processes such as events and  
motion. In this manual we will use the terms instruction and command  
interchangeably. For detailed information on any of the instructions (including  
examples), refer to the SERVOSTAR® MC Reference Manual.  
Syntax is the set of rules that must be observed to construct a legal  
command (that is, a command the MC can recognize).  
MC-BASIC is line-oriented. The end of the line indicates the end of the  
instruction. Whitespace (i. e., spaces and tabs within the statement line and  
blank lines), is ignored by the Basic interpreter. You can freely use  
indentation to delineate block structures in your program code for easier  
readability. The maximum allowed length of a line is 80 characters.  
MC-BASIC is case insensitive. Commands, variable names, filenames, and  
task names may be written using either upper case or lower case letters. The  
only exception is that when printing strings with the “Print” and “PrintUsing”  
commands, upper and lower case characters can be specified.  
Syntax uses the following notation:  
[ ]  
indicates the contents are required  
{ }  
indicates the contents are optional for the command  
Example lines of text are shown in Courier type font and with a border:  
X = 1  
2.2.2. Type  
There are many types of instructions: comments, assignments, memory  
allocation, flow control, task control, and motion. For detailed information on  
any of the commands (including examples), refer to the SERVOSTAR® MC  
Reference Manual.  
Comments allow you to document your program. Indicate a comment with  
either the Rem command or a single apostrophe ('). You can add comments  
to the end of an instruction with either Rem or an apostrophe.  
Rem This is a comment  
' This is a comment too.  
X = 1 'This comment is added to the line X = 1  
X = 1 REM This is a comment too  
Use comments generously throughout your program. They are an asset  
when you need support from others and they avoid confusing code.  
Declarations allocate MC memory for variables and system elements  
(groups, cam tables, etc.). This might be a simple type as an integer, or a  
complex structure as a cam table.  
Assignments Assignment instructions assign a new value to a variable.  
The syntax of an assignment is  
[Lvalue] [=] [expression]  
For example:  
X = Y + 1  
12  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
BASIC Moves Development Studio  
The term, Lvalue, is a shorthand notation, which indicates the value to the  
left of the equals sign. Valid Lvalues are variables or writable properties,  
which can be assigned. Expressions can be variables, constants, properties  
and function calls, as well as various combinations of them in arithmetic and  
logical statements . An exception to this rule is generic elements’  
assignment, at which the right side of the equal sign is not an expression, but  
an axis or a group (either real or generic), and Lvalue is a generic elements.  
If you assign a Double (floating point) value (expression, variable or  
constant) to a Long variable, the fractional portion of the double value is  
truncated, and the integer portion is assigned to the long variable. To query a  
variable or expression from the BASIC Moves terminal window, use the  
PRINT or ? command:  
PRINT 1/100  
? X1  
MC-BASIC also provides the standard PRINTUSING (PrintU) command for  
formatted printing.  
Commands for flow control change the way your program is executed.  
Without flow control, program execution is limited to processing the line  
immediately following the current command. Examples of flow control include  
GOTO, FOR…NEXT, and IF…THEN.  
MC-BASIC is a multi-tasking language in which many tasks can run  
concurrently. Generally, tasks run independently of each other. However,  
tasks can control each other using inter-task control instructions. One task  
can start, idle, or terminate another task.  
Most commands are started and finished immediately. For example:  
x = 1  
y = 2  
' this line is executed completely…  
' …before this line is started  
For general programming, one command is usually finished before the next  
command starts. Effects of these commands do not persist beyond the time  
required to execute them. However, the effects of many other commands  
persist long after the execution of the command. In general programming, for  
example, the effects of opening a file or allocating memory persist  
indefinitely. In real-time systems, persistence is more complicated because  
the duration of persistence is less predictable.  
Consider a command that specifies a 1,000,000 counts move on an axis  
named, A2:  
Move A2 1000000.0  
Y = 2  
The MC does not wait for the 1,000,000 move to be complete before  
executing Y=2. Instead, the first command starts the motion and then the MC  
continues with the next line (Y = 2). The move continues well after the move  
command has been executed.  
Persistence can affect programs. For example, you may not want to start one  
move until the previous move is complete. In general, you need access to  
persistent processes if you are to control your program according to their  
state of execution. As you will see later, MC-BASIC provides this access.  
M-SS-005-03  
Rev E  
13  
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
2.2.3. Constants and Variables  
All constant, variable and system element names must start with an  
alphabetical character (a-z, A-Z) and may be followed with up to 31  
alphabetical characters, numbers (0-9) and underscores (“_”). Keywords  
may not be used as names. For detailed information on any of the constants  
and variables (including examples), refer to the SERVOSTAR® MC  
Reference Manual.  
2.2.3.1. CONSTANTS  
Constants are numbers, which are written as ordinary text characters; for  
example, 161. Constants can be written in decimal or in hexadecimal (HEX).  
To write a constant in hex, precede it by a 0x; for example, 0xF is the hex  
representation of 15 decimal.  
The MC provides numerous literal constants (reserved words with a fixed  
value). You can use these constants anywhere in your program to make your  
code more intuitive and easier to read. For example:  
A1.Motion = ON  
turns on the A1 property Motion. This is more intuitive to read than:  
A1.Motion = 1  
although the effect is identical.  
2.2.3.1.1 Literal Constants Table  
ABORT = 4  
NEGATIVE = -1  
NEXTMOTION or NMOT = 2  
NOFLIP = 1  
ABOVE = 2  
BELOW = 1  
CAM = 2  
CAPTURING = 16  
CLEARMOTION or CMOT = 3  
CLOSE = 0  
NOOVERLAP = 0  
NOTELEVEL = 3  
OFF = 0  
ON = 1  
CONTINUE or CONT = 1  
ENDMOTION or EMOT = 3  
ERRORLEVEL = 2  
ONPATH = 2  
OPEN = 1  
OVERLAP = 1  
EXTERNAL = 1  
FALL = 2  
PI = 3.14159265359  
POSITIVE = 1  
FALSE = 0  
RESTART = 1  
FAULTLEVEL = 1  
RIGHTY = 2  
FLIP = 2  
RISE = 1  
GEAR = 1  
SILENTLEVEL = 0  
SUPERIMMEDIATE or SIMM = 5  
SYNC = 4  
GENERATORCOMPLETED or GCOM = 3  
HALT = 0  
HOMING = 10  
TASK_ERROR = 4  
TASK_IGNORE = -1  
TASK_INCORRECT = 9  
TASK_INTERRUPTED = 0x200  
TASK_KILLED = 10  
TASK_LOCKED = 0x100  
TASK_READY = 7  
TASK_RUNNING = 1  
TASK_STOPPED = 2  
TRACK = 3  
IDN_CAPTURE1ENABLE = 405  
IDN_CAPTURE1POSITIVELATCHED = 409  
IDN_CAPTURE1NEGATIVELATCHED = 410  
IMMEDIATE or IMMED = 1  
INPOSITION or INPOS = 2  
LEFTY = 1  
MAXDOUBLE = 1.797693134862311e+308  
MAXLONG = 2147483647  
MINDOUBLE = -1.797693134862311e+308  
MINLONG = -2147483648  
MULTIPLE = 1  
TRUE = 1  
2.2.3.2. VARIABLES  
You must declare a variable in MC-BASIC before you can it. In the  
declaration, you define variable name, scope and variable type. MC-BASIC  
supports Long for integer values, Double for floating point values, and String  
for ASCII character strings.  
14  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
BASIC Moves Development Studio  
Besides these basic types, MC-BASIC also supports Structure-like variables  
and some MC-BASIC specific types, such as points (Joints and Locations),  
generic motion elements (Axes and Groups) and UEAs (user error  
assertions-Errors and Notes).  
DeleteVar deletes a global variable. Since variable name can include  
wildcards, a single DELETEVAR can be used to delete more than one  
variable.  
DeleteVar int1  
DeleteVar int*  
' Deletes all variables starting with int  
Current values of global variables (both scalar and arrays) can be stored in a  
Prg file, in assignment format, within an automatically executable Program  
Continue…Terminate Program block. Obligatory parameters of SAVE are  
the name of storage file, and type of stored variables (could be all types).  
Optional parameters are robot type (for point variables), variable name  
(which may include wildcards) and mode of writing to storage file (overwriting  
or appending). Variable types available for storage through SAVE are longs,  
doubles, strings, joints and locations, but not structures, user-defined  
exceptions nor generic motion elements.  
Save File = “IntFile.Prg” Type = All VariableName = “int*”  
Save all variables starting with int in IntFile.Prg (overwrite file)  
Save File = “Points.Prg” Type = Joint RobotType = XYZR Mode = Append  
Append all joint-type points with XYZR robot-type to Points.Prg file  
Scope defines how widely a variable can be accessed. The broadest scope  
is global. A global variable can be read from any part of the system software.  
Other scopes are more restrictive, limiting access of variables to certain  
sections of code. MC-BASIC supports three scopes: global, task, and local.  
Task variables can be read from or written to anywhere within the task where  
it is defined, but not from outside the task. Local variables can only be used  
within their declaration block, i.e. program, subroutine or function blocks. The  
scope of a variable is implicitly defined when a variable is declared using the  
keywords: Common, Shared, and Dim.  
Global variables can be defined within the system configuration task,  
Config.Prg, within a task files (Prg files), before the program block, within  
library files (Lib files), before the first subroutine or function block, or from the  
terminal window of BASIC Moves. To declare a variable of global scope use  
the Common Shared instruction.  
Task variables are defined within a task or a library. To declare a variable of  
task scope use the Dim Shared instruction.  
All Dim Shared commands must appear above the Program  
statement in task files. In library files, all Dim Shared commands  
must appear above the first block of subroutine or function. The  
values of variables declared with Dim Shared persist as long as the  
task is loaded, which is usually the entire time the unit is  
operational. This is commonly referred to as being static.  
NOTE  
Local variables are defined and used within a program, a subroutine, or a  
function. To declare a local variable, use the Dim instruction. The Dim  
command for local variables must be entered immediately below the  
Program, Sub, or Function statement. Local variables cannot be declared  
within event blocks, and events cannot use local variables declared within  
the program.  
M-SS-005-03  
Rev E  
15  
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
2.2.4. Data Types  
MC-BASIC has two numeric data types: Long and Double. Long is the only  
integer form supported by MC-BASIC. Long and Double are MC-BASIC's  
primitive data types.  
Type  
Description  
Range  
Long  
32 bit signed integer  
-2,147,483,648 (MinInteger)to  
2,147,483,647 (MaxInteger)  
±1.79769313486223157 E+308  
Double  
Double precision floating point  
(about 16 places of accuracy)  
MC-BASIC provides the string data type which consists of a string of ASCII-  
coded characters. MC-Basic strings are dynamic. Reallocation of memory for  
new strings is preformed through a simple assignment of the string variable,  
and there is no need to specify the length of the new string. A full  
complement of string functions is provided to create and modify strings.  
Type  
Description  
Range  
String  
ASCII character string (no string length limit)  
0 to 255 (ASCII code)  
MC-BASIC has two point data types: JOINT and LOCATION. A point  
variable is related to a robot type. Robot type examples: XY – two axes XY  
table, XYZ – three axes XYZ system, XYZR – three cartesian axes + roll, etc.  
Type  
Description  
Range  
Joint  
A set of 2-10 double precision  
floating point joint (motor)  
coordinates  
±1.79769313486223157 E+308  
for each coordinate  
Location  
A set of 2-10 double precision  
floating point cartesian coordinates  
±1.79769313486223157 E+308  
for each coordinate  
MC-Basic enables definition of structure-like data types, composed of a  
limited number of long, double, string and point (joint and/or location) scalar  
and array elements. Array elements can have only a single dimension. Name  
of structure type and composition of elements are defined by the user within  
configuration file (Config.Prg).  
Type  
Description  
Range  
0-100 longs  
32 bit signed integer  
-2,147,483,648 (MinInteger) to  
2,147,483,647 (MaxInteger)  
±1.79769313486223157 E+308  
0-100 doubles  
0-100 strings  
Double precision floating point  
(about 16 places of accuracy)  
ASCII character string (no  
practical limit to string length)  
A set of 2-10 double precision  
floating point coordinates  
0 to 255 (ASCII code)  
0-100 points  
(joints and/or  
locations)  
0-10 long  
arrays  
0-10 double  
arrays  
0-4 string  
arrays  
±1.79769313486223157 E+308  
for each coordinate  
1-32,767 32 bit signed integers  
-2,147,483,648 (MinInteger) to  
2,147,483,647 (MaxInteger)  
±1.79769313486223157 E+308  
1-32,767 double precision  
floating point elements  
1-32,767 ASCII character  
strings  
0 to 255 (ASCII code)  
1-2 point  
(joints and/or  
locations)  
arrays  
1-32,767 sets of 2-10 Double  
precision floating point  
coordinates  
±1.79769313486223157 E+308  
for each coordinate  
16  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
BASIC Moves Development Studio  
MC-Basic has two UEA (user error assertion) data types (severities): Error  
and Note. Each UEA is defined with a string-type error message given by the  
user and a unique exception number, which might be determined either by  
the user or by the system. The SERVOSTAR® MC handles UEAs similar to  
internal exceptions.  
Type  
Description  
Range  
Error  
An ASCII message string and a  
unique integer exception  
number  
20001-20499 for user determined  
exception number  
20500-20999 for system determined  
exception number  
Note  
An ASCII message string and a  
unique integer exception  
number  
20001-20499 for user determined  
exception number  
20500-20999 for system determined  
exception number  
MC-Basic provides generic element data types designed to serve as a  
reference to real axes and groups. Through a simple assignment statement,  
the generic element gets the element identifier (see below) of a real motion  
element, thus acquiring all its properties. Afterwards, all activities preformed  
on the generic element identically affect the real element. The referenced  
element can be changed, through recurring assignments, as many times as  
the user wishes.  
Type  
Generic Axis  
Description  
An integer element  
identifier  
Range  
0 (before first assignment)  
1 to number of axes in system (up  
to 32)  
Generic Group  
An integer element  
identifier  
0 (before first assignment)  
33 to number of groups in system  
(up to 64)  
Each real motion element gets a unique element identifier from the system  
during its declaration. Axes get successive element identifiers ranging from 1  
to 32 according to axis number. Groups get successive identifiers ranging  
from 33 to 64 according to declaration order. Value of element identifier can  
be queried directly through ELEMENTID.  
SYS.NUMBERAXES = 2  
Common Shared G2 As Group AxNm = A1 AxNm = A2  
Common Shared G1 As Group AxNm = A1 AxNm = A2  
? A1.ELEMENTID  
1
? A2.ELEMENTID  
2
? G2.ELEMENTID  
33  
? G1.ELEMENTID  
34  
MC-BASIC uses integers to support Boolean (logical) operations. Logical  
variables have one of two values: true or false. MC-BASIC uses type Long to  
support logical expressions. The value 0 is equivalent to false. Usually, 1 is  
equivalent to true, although any non-zero value is taken to be true. Boolean  
expressions are used in conditional statements such as If…Then, and with  
Boolean operators like And, Or, and Not.  
Arrays can be any data type. Arrays may have from 1 to 10 dimensions. The  
maximum number of elements in any dimension is 32,767. Array dimensions  
always start at 1.  
M-SS-005-03  
Rev E  
17  
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
2.2.4.1. STRUCTURES  
A structure is a new data type used for storing a list of variables of different  
type in one variable.  
2.2.4.1.1 Definition  
Since a structure is a user-defined data type; it must first be defined.  
Structure type definition can be done only in the Config.prg file (before the  
PROGRAM block, at the declaration level), using the following syntax:  
TYPE <structure_type_name>  
<element_name>{[]} AS <element_type> {OF <robot_type>}  
END TYPE  
This block defines the name of the structure type and the names, types and  
array sizes of the various structure elements (fields). Data types supported  
as structure elements are: long, double, string, and points (JOINT and  
LOCATION). Array elements can only have a single dimension. The  
maximum structure block can include: 100 longs, 100 doubles, 100 strings,  
100 points JOINTs and/or LOCATIONs), 10 long-type arrays, 10 double-type  
arrays, 4 string-type arrays and 2 point-type arrays JOINTs and/or  
LOCATIONs). The total size of the MC-Basic structure is limited. The  
maximum number of each type of element is fixed. Trying to define more  
structure elements than allowed results in a translation error. An array of  
structures may have up to 10 dimensions.  
2.2.4.1.2 Declare  
You must declare a structure before you can use it. If you want to declare a  
structure variable, you must first declare a structure data type and then use  
this data type structure to declare the variable. The structure data type  
definition can be done in the Config.prg file only with the following syntax  
(before the PROGRAM token, at the declaration level):  
TYPE <variable_name>  
<variable_name> as <type>  
<variable_name> as <type> {<of> <robot_type>}  
END TYPE  
This block defines the new element names of the structure type. The  
different types supported for the structure are: long, double, string, and  
points. The maximum structure block is defined as:  
100 longs  
100 doubles  
100 strings  
100 points  
2.2.4.1.3 Syntax  
(COMMON SHARED|DIM {SHARED}) <variable_name> AS <variable_name>  
or  
(COMMON SHARED|DIM {SHARED}) <variable_name>[<index>] AS  
<variable_name>(arrays of structure)  
where the second variable name = the structure type  
18  
Rev E  
M-SS-005-03l  
Danaher Motion  
For example:  
In config file ->  
06/2005  
BASIC Moves Development Studio  
Type X  
Type as Long  
Length as Long  
End Type  
In application file ->  
Dim shared s1 as X  
Program  
?s1->Type  
End program  
Do not define the size of the structure data type. The size of the structure is  
constant. If you declare more structure elements than allowed, a translation  
error is generated.  
2.2.4.1.4 Assignment  
The assignment of a structure uses the following syntax:  
<variable_name> = <expression> where <expression> is of  
structure type  
Whole structure assignment is allowed only if both structures are of the same  
structure type. For example:  
Dim STa1 As Type_1  
Dim STb1 As Type_1  
Dim STa2 As Type_2  
STa1 = STb1  
STa2 = STa1  
-> Structure types match  
-> Error - structure type mismatch  
2.2.4.1.5 Elements  
A structure element is addressed through the structure’s name and the arrow  
sign. For example:  
<structure_name>{[]…}-><element_name>{[]}  
Structure elements are handled almost like regular variables. Structure  
elements are printed, assigned, participate in mathematical operations, and  
string-type elements are concatenated to other strings. They can also serve  
as arguments of system functions (SIN, UCASE$, etc.), used in logic  
statements and as conditions of flow control statements and event  
definitions. For example:  
Common Shared ST As STRUCT  
PRINT ST->LongElm1  
ST->LongElm2 = 21.2 * ST->LongArrElm[1]  
? UCASE$(“String Element Is: “ + ST->StringElm)  
IF ST->LongElm1 > 0 THEN  
SELECT CASE ST->LongElm2  
2.2.5. System Elements  
There are several system elements: axes, groups, cam tables, PLSs,  
conveyers and compensation tables. These are not regular data types, but  
are more like user interfaces of the system's internal memory or internal  
function calls. You cannot handle them as a whole in expressions. Each  
system element has a set of properties, which is accessed through syntax  
resembling data elements of a structure, using the point character.  
M-SS-005-03  
Rev E  
19  
 
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
Despite the syntax, properties are not data elements, since a system  
element and its properties are not located on a continuous block of memory.  
All properties return a value, so they can be printed, combined in  
expressions and passed by value to functions and subroutines. Many  
properties are also writable and can be assigned like variables.  
Unlike variables, properties do not have a fixed address in memory and  
cannot be passed by reference. Data types of properties are Long, Double,  
String, Joint and Location. For axis A1 and cam table Cam1, and a long type  
variable named Var1:  
? A1.Enable  
A1.Enable = 1  
? A1.PositionCommand  
A1.PositionCommand = 0  
Query  
Set (read-write property)  
Query  
Syntax Error (read-only property)  
Var1 = Cam1.Cycle  
Cam1.Cycle = -1  
Var1 = Cam1.Inuse  
Cam1.Inuse = 1  
Query  
Set (read-write property)  
Query  
Syntax Error (read-only property)  
2.2.6. Units  
Many variables have associated units. This include variables, which contain  
quantities of position, velocity, acceleration, and time. Some units are fixed.  
For example, time is always in milliseconds. MC-BASIC allows you to define  
units of position, velocity and acceleration independently. In the next chapter,  
we will discuss how to set up units.  
2.2.7. Expressions  
Expressions are combinations of operators and value-returning entities, such  
as variables, constants, function calls, which are all calculated into a value.  
In MC-Basic, expressions can also contain unique entities like element  
properties (see above) and system properties (see below). Operators (like +  
and -) specify how to combine the variables and constants. Expressions are  
used in almost all commands.  
An expression has one of two syntax forms  
[operand] [binary operator] [operand]  
[unary operator] [operand]  
An operand can be a constant (123.4), variable name (X), or another  
expression. Most operators are binary (they take two operands), but some  
are unary (taking only one operand). So, -5.5 is a valid expression. It has the  
unary minus (also called negation) and a single operand.  
There are two types of expressions: algebraic and logical (or Boolean).  
Algebraic expressions are combinations of data and algebraic operators.  
The results of all algebraic operations are converted to double precision  
floating-point after executing the expression.  
2.2.8. Automatic Conversion of Data Types  
If the assignment of an expression is an integer, the expression is still  
evaluated in double precision. For example:  
Common Shared I as Long  
I = 6.33 * 2.79  
20  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
BASIC Moves Development Studio  
The value of the expression (6.33 * 2.79) is converted from double to long  
when the value (17) is copied into I. In the conversion to long, the number is  
truncated to the integer portion of the floating-point value.  
Logical expressions are combinations of data and logical operators. For  
example, X1 And X2is a logical expression. The data and results of logical  
elements are type Long. Double variables are not allowed in logical  
expressions. The terms, logical and Boolean are considered  
interchangeable.  
Logical expressions are evaluated from left to right. They are evaluated only  
far enough to determine the result. So, in A And B And C, if A is 0 (false),  
the result is false without evaluating B or C.  
Precedence dictates which operator is executed first. If two operators  
appear in an expression, the operator with higher precedence is executed  
first. For example, multiplication has a higher precedence than addition. The  
expression 1+2*3is evaluated as 7 ((2 * 3) + 1), not 9 ((2 + 1) * 3).  
The minus sign in the math operators’ table (below) is sometimes confusing  
since it shows up twice in the table: once with a high precedence (unary  
negation) and once with low precedence subtraction (binary minus). This  
difference in precedence is intuitive: 5 * -6only makes sense if the  
negation is executed first.  
The tables that follow list different types of operators. The entries in the  
tables are listed in order of precedence: the higher in the table, the higher the  
operator precedence. Also, the tables themselves are arranged in order of  
precedence with respect to one another. Math operators have the highest  
precedence. So, all math operations are executed before any other type of  
operator is executed. Finally, any time you need to change the standard  
precedence, use parentheses. Parentheses have the highest precedence of  
all.  
Algebraic Operator  
Parentheses  
Exponentiation  
Negation  
Symbol  
( )  
^
-
+
*
/
Mod  
+
-
Unary/Binary  
NA  
Operand Type  
double, long, string, joint, location  
double, long  
double, long, joint, location  
double, long, joint, location  
double, long, joint, location  
double, long, joint, location  
double, long  
Binary  
Unary  
Unary  
Binary  
Binary  
Binary  
Binary  
Binary  
Binary  
Unary Plus  
Multiplication  
Division  
Modulo  
Addition  
double, long, string, joint, location  
double, long, joint, location  
location  
Subtraction  
Compound  
:
Relational Operator  
Parentheses  
Symbol  
( )  
=
<>  
<
>
Binary/Unary  
Not applicable  
Operand Type  
double, long, string  
double, long, string  
double, long, string  
double, long, string  
double, long, string  
double, long, string  
double, long, string  
Equality  
Inequality  
Less than  
Greater than  
Binary  
Binary  
Binary  
Binary  
Binary  
Binary  
Less than or equal to  
Greater than or equal to  
<=  
>=  
Word-wise Logical Operator  
Symbol  
And  
Or  
Xor  
Not  
Unary/Binary  
Operand Type  
And  
Or  
Exclusive or  
Not  
Binary  
Binary  
Binary  
Unary  
long  
long  
long  
long  
M-SS-005-03  
Rev E  
21  
BASIC Moves Development Studio  
06/2005  
Symbol  
Danaher Motion  
Bit-Wise Logical Operator  
Bitwise Negation  
Bitwise And  
Unary/Binary  
Unary  
Operand Type  
long  
BNot  
BAnd  
BOr  
Binary  
Binary  
long  
long  
Bitwise Or  
Bitwise Xor  
Shift Left  
Shift Right  
BXor  
SHL  
SHR  
Binary  
Binary  
Binary  
long  
long  
long  
Negation is simply placing a minus sign in front of a constant or variable to  
invert its arithmetic sign. Modulo division produces the remainder of an  
addition. For example, 82 Mod 5is equal to 2(the remainder of 82/5). If the  
first operand is negative, the resultant value is negative (-2). The sign of the  
result is determined by the sign of the first operand, and the sign of the  
second operand has no effect.  
The relative precedence of exponentiation and negation may seem  
somewhat counter-intuitive. The following examples illustrate the actual  
behavior.  
Common shared D as double  
D = -1  
? D^2  
1
? -1^2  
-1  
In the second section of the above example, exponentiation is performed first  
then negation is performed.  
Common shared D as double  
D = -1  
? D = -1  
1
In the example above, the “=” sign is taken as a relational operator (i.e., Is D  
= -1?) The relation is True, or 1.  
? D^2 = -1^2  
0
In the example above, the “=” sign is taken as a relational operator, (i.e.,  
Is D^2 = -1^2?). Again, the exponentiation is performed first, and then the  
relation is evaluated as False, or 0.  
The "+" operator, when used with strings, performs concatenation of strings.  
In points, “+” (addition) and “-“ (subtraction) operators can be used between  
points of the same type and size, or between a point and a long or double  
type scalar. On the other hand, “*” (multiplication) and “/” (division) operators  
can only be operated between a point and double or long scalar, but not  
between two points.  
In Logical operations, every value that is not 0 is assumed true and set to 1.  
And-ing combines two values so the result is true (1) if both values are true  
(that is, non-zero). Or-ing combines them so the result is true (1) if either  
value is true. Exclusive-Or produces true if one or the other value is true. It  
produces false (0) if both or neither are true. Before logical operations begin,  
all operands are converted to 1 (true) or 0 (false). The rule is that everything  
that is not 0 becomes 1.  
22  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
BASIC Moves Development Studio  
Bit-wise expressions differ from logical expressions in that there may be  
many results from a single operation. Bitwise operations are frequently used  
to mask I/O bits. For example, the standard SERVOSTAR MC inputs can be  
operated on with BAnd (Bitwise And) to mask off some of the inputs. The  
following example masks off all bits of the digital outputs, except the  
rightmost four:  
Dim Shared MaskedBits As Long  
MaskedBits = System.Dout Band 0xF  
‘Mask all but rightmost four bits  
All bitwise operations produce 32-bit result from two 32-bit numbers. Bitwise  
operations are really 32 independent, bit-by-bit operations. For example:  
15 (Binary 1111) BAnd 5 (Binary 101) is 5 (Binary 101)  
BNot 15 is 0xFFFFFFF0.  
2.2.9. Math Functions  
MC-BASIC provides a large assortment of mathematical functions. All take  
either numeric type as input (Double and Long) and all but Int and Sgn  
produce Double results. Int and Sgn produce Long results. For detailed  
information on any of the math functions (including examples), refer to the  
SERVOSTAR® MC Reference Manual.  
Abs(x)  
Returns the absolute value of X.  
Acos(x)  
Asin(x)  
Atan2(Y, X)  
Returns the arc cosine of X. X is assumed to be in radians.  
Returns the arc sine of X. X is assumed to be in radians.  
Returns the inverse tangent of Y/X in radians. The range of the result is  
between ±PI radians (±180°). Atan2 is an improvement over ATN(Y/X)  
in that it works correctly if X is zero, and if X<0.  
Returns the inverse tangent of X in radians. The range of the result is  
between ± PI/2 radians (± 90°).  
Atn(X)  
Cos(X)  
Exp(X)  
Int(X)  
Returns the cosine of X. X is assumed to be in radians.  
Returns ex.  
Returns the largest long value less than or equal to a numeric  
expression (for example, ?Int(12.5) returns 12  
?Int(-12.5) returns -13)  
Log(X)  
Sgn(X)  
Returns the natural logarithm of X. X must be > 0. If you want the base-  
10 log, use Y = LOG(X)/LOG(10).  
Returns the arithmetic sign of X. If X > 0, return 1. If X < 0, return -1. If X  
= 0, return 0.  
Sin(X)  
Sqrt(X)  
Tan(X)  
Returns the sine of X. X is assumed to be in radians.  
Returns the positive square root of X. X must be >= 0.  
Returns the tangent of X. X is assumed to be in radians.  
Returns the integer nearest to X. If X falls exactly between two integers  
(for example, 1.5), return the even integer. So 1.5 and 2.5 round to 2.  
Round(X)  
M-SS-005-03  
Rev E  
23  
 
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
2.2.10. String Functions  
Beginning with version 3.0, MC-BASIC supports all the common string  
functions supported in standard BASIC. For detailed information on any of  
the string functions (including examples), refer to the SERVOSTAR® MC  
Reference Manual.  
ASC(S,I)  
Returns an ASCII character value from within a string, S, at  
position, I.  
BIN$(X)  
Returns the string representation of a number (X) in binary  
format (without the Ob prefix).  
CHR$(X)  
Returns a one-character string corresponding to a given ASCII  
value, X.  
HEX$(X)  
Returns the string representation of a number (X) in  
hexadecimal format (without the 0x prefix).  
Returns the position, I, of the starting character of a substring,  
SS, in a string, S.  
Returns a copy of the string, S, passed to it with all the  
uppercase letters converted to lowercase.  
Returns the specified number, X, of characters from the left-  
hand side of the string, S.  
INSTR(I,SS,S)  
LCASE$(S)  
LEFT$(S,X)  
LEN(S)  
Returns the length of the string, S.  
LTRIM$(S)  
Returns the right-hand part of a string, S, after removing any  
blank spaces at the beginning.  
MID$(S,I,X)  
RIGHT$(S,X)  
RTRIM$(S)  
SPACE$(X)  
Returns the specified number of characters, X, from the string,  
S, starting at the character at position, I.  
Returns the specified number of characters, X, from the right-  
hand side of the string, S.  
Returns the left-hand part of a string, S, after removing any  
blank spaces at the end.  
Generates a string consisting of the specified number, X, of  
blank spaces.  
STR$(X)  
STRING$(X,{S},{Y})  
Returns the string representation of a number, X.  
Creates a new string with the specified number, X, of characters,  
each character of which is the first character of the specified  
string argument, S, or the specified ASCII code, Y.  
Returns a copy of the string, S, passed to it with all the  
lowercase letters converted to uppercase.  
Returns the real value represented by the characters in the input  
string, S.  
UCASE$(S)  
VAL(S)  
24  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
BASIC Moves Development Studio  
2.2.11. System Commands  
The following commands provide information about the system. You can  
issue these commands at any time either from task, terminal or the  
CONFIG.PRG file (with some exceptions). For detailed information on any of  
the system commands (including examples), refer to the SERVOSTAR® MC  
Reference Manual.  
AxisList  
Returns a comma-separated-list of the axes' names  
defined in the system. If wildcards are used, the query  
returns the proper axes.  
BreakPointList  
CamList  
Lists all the breakpoints in the task, loaded to memory.  
This query returns a list of the cam table names defined in  
the system. If wildcards are used, the query returns the  
proper existing cam names.  
Dir  
Lists all files that exist on the RAM disk and on the Flash  
disk. The File Specification may contain the * and ?  
wildcard characters, in order to refine the list. When  
invoked without a parameter, all the files are listed.  
Displays the log file containing the last 64 errors that  
occurred in the system.  
ErrorHistory  
ErrorHistoryClear  
EventList  
Clears the error log file.  
Lists the names of the existing events and their states. If a  
task name precedes EventList, only events belonging to  
the specified task are listed.  
GroupList  
PlsList  
Lists the names of the groups defined in the system. Each  
group name is followed by a list of the axes' names that  
are part of that group.  
Returns a list of the PLS names defined in the system. If  
wildcards are used, the query returns the correct existing  
PLS data.  
ProgramPassword  
Reset All | Tasks  
Sets the file password and toggles the password  
protection state.  
Reset All removes all tasks, variables, and system  
variables from program memory. All external outputs are  
turned off and all drives are disabled. Reset All runs  
Config.prg, not Autoexec.prg. Reset All is only issued  
from the terminal.  
Reset Tasks removes all tasks from memory, but leaves  
system variables loaded. It deallocates all defined  
variables and user programs. Reset Tasks does not  
disable motors, or reset outputs. Reset Tasks is only  
issued from the terminal.  
System.AccelerationRate  
System.AutostartTask  
Queries or sets the system acceleration exchange rate.  
Queries or sets the name of the auto-start task. The  
default auto-start task is Autoexec.Prg. Assignment of an  
empty string prevents auto-start task run.  
System.AverageLoad  
System.Clock  
Returns the average realtime load on the CPU. This is the  
average realtime load measured during a 0.5 second  
interval.  
Returns the number of system clock ticks. This is the clock  
run by the VxWorks Operating System. One clock tick  
corresponds to 1 millisecond.  
System.CpuType  
System.Date  
Returns the type and model of the CPU that was found  
during the system’s power-up. Supports only Intel, AMD  
and Cyrix processors.  
Queries or sets the date. The date is entered as a  
character string and must be enclosed between double  
quotes ("). The parameters Day, Month, and Year, must  
be separated with the / (slash) character.  
M-SS-005-03  
Rev E  
25  
 
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
System.DecelerationRate  
System.DIn  
Queries or sets the system deceleration exchange rate.  
Returns the value of one or more of the 23 digital inputs.  
System.DIn returns the values of the individual bits in  
the system input word. In order to read the value of a  
single input bit, bit number should be specified as  
System.DIn.<bit number>.  
System.DipSwitch  
Returns the value of one or more of the eight DIPswitch  
inputs. System.DipSwitch returns the values of the  
eight individual bits in the DIPswitch byte. In order to  
read the value of a single input bit, bit number should be  
specified as System.DipSwitch.<bit number>.  
Returns the amount of free space on the flash disk.  
Queries and sets the printing format of Doubles. Zero  
value stands for d.ddddddddddddddde+/-dd style, with  
precision of 15 digits after the decimal point. 1 relates to  
the ddd.ddd style if the exponent is between -4 and 5,  
and to d.de+/-dd style otherwise. Setting can be done  
only in Config.Prg file, and therefore requires system  
reset (through RESET All or hardware reset).  
Queries and sets the value of one or more of the 20  
digital outputs. System.DOut sets or returns the values  
of the individual bits in the system output word. In order  
to read or write into a single output bit, bit number should  
be specified as System.DOut.<bit number>.  
Enables and disables the system.  
System.DiskFreeSpace  
System.DoubleFormat  
System.DOut  
System.Enable  
System.Error  
Queries the last system error message.  
System.ErrorHandlerMode  
Determines the scope of the effect of an error occurring  
in task context. When the value of  
System.ErrorHandlerMode is one (the default value),  
the error will affect the entire system by stopping all  
motion, idling all tasks that have attached elements and  
turning off System.Motion flag. Setting this property to  
zero results in limiting the Motion stop and task idling to  
the erroneous task itself.  
System.ErrorNumber  
System.ErrorPrintLevel  
Queries the number of the last system error and returns  
only the error number.  
Controls which errors are printed, according to the  
severity of the error. Only asynchronous errors are  
printed. Synchronous errors are not affected.  
Returns the size of the Flash disk.  
System.FlashDiskSize  
System.HostDouble  
Reads the value of one of eight double-type DPRAM  
variables written by the host.  
System.HostInteger  
System.Information  
Reads the value of one of eight long-type DPRAM  
variables written by the host.  
Returns information found during system power-up.  
Performs a test on the SERCON chip cycle time. The  
result is the average cycle time found in a 500 ms test.  
Queries or sets the IP address and subnet mask for the  
Ethernet interface.  
System.IPAddressMask  
System.JerkRate  
System.Led  
Queries or sets the system jerk exchange rate.  
Queries and sets one or more of the three general  
purpose LEDs. In order to read or write into a single  
LED, LED number should be specified as  
System.LED.<LED number>.  
System.MaxMemBlock  
System.MCDouble  
System.MCInteger  
System.Motion  
Returns the size (in bytes), of the largest block of free  
memory.  
Reads or writes to one of eight double-type DPRAM  
variables available for use by the MC.  
Reads or writes to one of the long-type DPRAM  
variables available for use by the MC.  
Enables and disables Motion commands.  
26  
Rev E  
M-SS-005-03l  
Danaher Motion  
System.MotionAssistance  
06/2005  
BASIC Moves Development Studio  
Enables and disables display of additional notes  
returned from the motion task.  
System.Name  
System.NoMotion  
Queries and sets the name of the controller.  
Enables and disables the System.Motion  
monitoring apparatus.  
System.NumberAxes  
System.PeakLoad  
System.PipeMode  
System.PrintMode  
Returns the number of axes currently loaded in the  
system. This is a read-only variable. It can be used  
in the terminal window or in any task.  
Returns the peak realtime load on the CPU. This is  
the maximum value of the realtime load measured  
during a 0.5 second interval.  
Queries and sets the type of motion pipe mode.  
Available types are: active, position only, or  
position and velocity.  
Queries and sets the printing format of Longs.  
Optional formats are DECIMAL (decimal format),  
HEX (hexadecimal format) and BIN (binary  
format). Default format is decimal.  
System.RamDriveFreeSpace  
System.RamSize  
Returns the amount of free space on the RAM  
drive.  
Returns the size of the RAM found during the  
system power-up.  
System.RtsTimeout  
Queries and sets the timeout of the real-time  
scheduler.  
System.SerconVersion  
System.SerialNumber  
System.ServicePrintLevel  
Returns the version number of the SERCON chip.  
Returns the serial number of the MC.  
Controls (query or set) printing of service  
messages (ON or OFF).  
System.Time  
Queries or sets the current time of day. Hours,  
minutes, and seconds are each specified using  
two digits. The MC uses 24-hour clock notation.  
Time is entered as a character string and must be  
enclosed between double quotes ("). The  
parameters, Hours, Minutes, and Seconds, must  
be separated with : (colon) characters.  
Returns the user authorization code.  
Queries or sets the system velocity override.  
Queries or sets the system velocity exchange rate.  
Returns the value of one or more of the 32 virtual  
inputs. System.VIn returns the values of the  
individual bits in the system input word. In order to  
read the value of a single input bit, bit number  
should be specified as System.VIn.<bit number>.  
Queries and sets the value of one or more of the  
32 virtual outputs. System.VOut sets or returns  
the values of the individual bits in the system  
output word. In order to read or write into a single  
output bit, bit number should be specified as  
System.VOut.<bit number>.  
System.UserAuthorizationCode  
System.VelocityOverride  
System.VelocityRate  
System.VIn  
System.VOut  
System.WatchDogTest  
Checks the correct operation and timeout of the  
WatchDog. After the test has finished, the MC  
must be rebooted. The test returns either the WD  
timeout (in ms) when executed successfully, or an  
error in case of a test failure.  
TaskList  
VarList  
Lists the names and states of loaded tasks.  
Returns a list of the variable names defined in the  
system.  
Version  
Returns information pertaining to the version of  
BASIC Moves Development Studio loaded into  
your MC.  
M-SS-005-03  
Rev E  
27  
BASIC Moves Development Studio  
With…End With  
06/2005  
Danaher Motion  
Simplifies blocks of code, which set a number of parameters on  
the same motion element (axis or group). After a With is  
encountered, all parameters where the element is not specified  
are assumed to belong to the element specified in the With.  
With is valid in Configuration, Task, or Terminal contexts. The  
scope of a configuration With is global, whereas the scopes of  
both terminal and task With’s are limited to terminal and task,  
respectively.  
To put off the With’s effect, use End With. A task With must be  
followed by the End With, thus creating a closed With block. A  
With block must be closed within the same block it was opened  
(i.e., Program, Sub and Function blocks). For example:  
A1.VMax = 5000  
A1.Vord = 5000  
A1.VCruise = 3000  
A1.PEMax = 10  
A1.PESettle = 0.01  
Move A1 100  
Can be simplified using With:  
With A1  
VMax = 5000  
Vord = 5000  
VCruise = 3000  
PEMax = 10  
PESettle = 0.01  
Move 100  
End With  
2.2.12. Printing  
MC-BASIC provides unformatted and formatted printing using the PRINT  
and PRINTUSING commands. For detailed information on any of the print  
commands (including examples), refer to the SERVOSTAR® MC Reference  
Manual.  
The Print command (short form, ?) is used to print expressions from the  
terminal window or from your program. If you issue print commands from the  
terminal window, they print to the terminal window. If you issue them from  
your program, they print to the BASIC Moves Message Log. You can view  
the message log by selecting Window, Message Log.  
Within programs, PRINT allows you to suppress the carriage return at the  
end of a line by terminating the command with a comma or a semicolon.  
Semicolon and comma have no effect when added to the end of print  
commands from the terminal window.  
Print “Hello, “;  
Print “ world.”  
'Prints:  
Hello, world.  
When commas are added to print command as separators between  
expressions, a tabular space is placed between the expressions in the  
printed outcome.  
Print “Hello, “,  
Print “ world.”  
Hello, world.  
'Prints:  
28  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
BASIC Moves Development Studio  
On the other hand, expressions separated by a semicolon or a space in the  
print command are printed adjacently.  
Print 1,2  
1
2
Print 1;2  
12  
Print 1 2  
12  
PrintUsing introduces formatting for printing. You can control the format and  
the number of digits that print. For example, by using the “#” sign and the  
decimal point, you can specify a minimum number of characters to be  
printed.  
PrintU "The number is #, # ";j1,j2  
-->The number is 1, 2  
Be aware that using a single format to print more than one expression will  
result in repetition of any text written within string format according to the  
number of printed expressions.  
PrintU "The number is #, ";j1,j2  
-->The number is 1, The number is 2,  
By specifying the number of digits to print, data can be printed in tabular form  
since the number of places printed will not vary with the value of the number.  
PrintU “Keep numbers to a fixed length with PrintUsing:  
######” ; 100  
Be aware that if the number requires more digits than you have allocated, it  
overruns the space.  
PrintU “Overrun: ##” ; 1000000  
Takes 7 spaces for 1,000,000 even though PrintU allocates only 2.  
For printing of double type expressions, formatted printing also enables to  
control precision, i.e. number of digits printed after the decimal point.  
PrintU “Print PI with 3 digits after decimal point: #.###” ; 3.14159  
Prints only 3 digits after the decimal point, while rounding the PI’s value to  
3.142.  
You can also precede the “#” signs with a “+” to force PrintU to output a sign  
character (+ or -). Normally, the sign is printed for negative numbers, not  
positive numbers.  
Finally, you can terminate the format string with “^^^^” to force the number to  
print in exponential format.  
PrintU “Exponential format: ####.##^^^^” ; 100  
Prints 1e+02. You must include exactly four “^” characters for this format to  
work.  
Be aware that while PRINT and PRINTUSING allow you to print out many  
expressions on a single line, these expressions are not synchronized to  
each other. The values can and usually do come from different servo cycles.  
If you are monitoring motion and need the command to be synchronized, you  
must use Record.  
Normally, printing of longs is done in decimal format. To change printing to  
Hexadecimal format, type:  
System.PrintMode = HEX  
M-SS-005-03  
Rev E  
29  
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
To change printing to Binary format, type:  
System.PrintMode = BIN  
To restore printing to Decimal format, enter:  
System.PrintMode = DECIMAL  
Printing double floating point numbers is not affected by System.PrintMode.  
As an alternative to PrintMode, you can place the keywords Decimal, Hex or  
Binat the end of Print or PrintUsing to print expressions in these formats.  
Subsequent print instructions (?, PRINT, PRINTU, and PRINTUSING) are  
not affected.  
INPB, INPW, PEEKB, and PEEKW return long values. If you query any of  
these functions while in PrintMode decimal, the result is misleading. Change  
to Hex or Bin for the correct result.  
System.DoubleFormat , defined from the configuration file , sets the double number  
printing format for print of double-type numbers.  
System.DoubleFormat = 1 – print in Floating point format ( 132.555 )  
System.DoubleFormat = 0 - print in Exponential format ( 1.325550000000000e+02 )  
Program  
Sys.DoubleFormat = 1  
End Program  
-->?Sys.DoubleFormat  
-->1  
2.2.13. Flow Control  
Flow control is the group of instructions that control the sequence of  
execution of all other instructions. For detailed information on any of the flow  
control commands (including examples), refer to the SERVOSTAR® MC  
Reference Manual.  
If…Then is the most basic flow control statement. The syntax of If…Then is:  
If condition Then  
<first statement to execute if condition is true>  
{multiple statements to execute if condition is true}  
{Else  
<first statement to execute if condition is false>  
{multiple statements to execute if condition is false}}  
End If  
where:  
If…Then must be followed by at least one statement.  
Else is optional, but if present must be followed by at least  
one statement.  
There is no Else if. If you use an If after an Else, you must  
place the If on a new line.  
Select…Case is an extension of If…Then. Anything that can be done with  
Select…Case can also be done with If…Then. Many times, Select…Case  
simplifies programming logic.  
On the first line of a Case block of commands, you specify the variable or  
expression you want tested. For example:  
Select Case I  
Tests the variable I for a range of conditions.  
You can also select expressions:  
Select Case I - M/N  
30  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
BASIC Moves Development Studio  
After you have specified the variable or expression, list one or more values  
or value ranges that the variable can take. There are four ways you can  
specify cases:  
Exact Value  
Logical Condition  
Range  
Else  
The syntax of Select…Case is:  
Select Case SelectExpression  
{Case Expression1  
{statements to be executed if SelectExpression = Expression1}}  
{Case Expression2  
{statements to be executed if SelectExpression = Expression2}}  
{Case Is RelationalOperator Expression3  
{statements to be executed if the condition is true}}  
{Case Expression4 To Expression5  
{statements to be executed if SelectExpression is between values}}  
{Case Else  
{statements to be executed if none of the above conditions are met}}  
End Select  
where  
SelectExpression is a Long, Double or String expression  
in Case…To…, if Expression4 > Expression5, the case is  
never true; no error is flagged.  
Select…Case block. The following example puts all four types of cases  
together:  
Program  
Dim N as Long  
Select Case N  
Case 0  
Print "N = 0"  
Case 1  
Print "N = 1"  
Case is >=10  
Print "N >= 10"  
Case is < 0  
Case 5 TO 9  
‘No requirement for statements after Case  
Print "N is between 5 and 9"  
Case Else  
Print "N is 2, 3, or 4"  
End Select  
End Program  
For…Next statements allow you to define loops in your program. The syntax  
is:  
For counter = Start To End {Step Size}]  
{Loop Statements}  
Next {counter}  
where  
If Size is not defined, it defaults to 1.  
The loop is complete when the counter value exceeds End.  
For positive Size, this occurs when counter>End. For  
negative Size, when counter<End.  
Counter, Start, End, and Size may be Long or Double.  
M-SS-005-03  
Rev E  
31  
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
For example:  
For I = 2 TO 5  
Print "I = " I  
Next I  
'Prints 2, 3, 4, 5  
For I = 4 TO 2 STEP –0.5  
Print "I = " I  
Next  
'Prints 4.0, 3.5, 3.0, 2.5, 2.0  
While…End While allows looping dependent on a dynamic condition. For  
example, you may want to remain in a loop until the velocity exceeds a  
certain value.  
The syntax of While is:  
While Condition  
{statements to execute as long as condition is true}  
End While  
where  
The condition is evaluated before any statements are  
executed. If the condition is initially false, no statements are  
executed.  
Statements are optional. If none are included, While…End  
While acts as a delay.  
You can have any number of statements (including zero) to  
be executed.  
For example:  
Program  
While A2.VelocityFeedback < 1000  
Print "Axis 2 Velocity Feedback still under 1000"  
End While  
End Program  
Using the While or Do…Loop, the CPU repeatedly executes the While  
block (even if the block is empty). This is sometimes a problem. These  
commands do not relinquish system resources to other tasks. If you want to  
free up CPU resources during a While block or Do…Loop, include the  
Sleep command within the block as follows:  
Program  
While A1.VCmd < 1000  
Sleep 1  
End While  
End Program  
The Do...Loop is similar to While except that the statement block is  
executed before the first evaluation of the condition. With the Do...Loop, the  
statement block are always executed at least once. Do...Loop also allows an  
option on the condition. Use While to execute while the condition is true, or  
Until to execute while the condition is false. The syntax of the Do...Loop is:  
Do  
{statements}  
LOOP While|Until Condition  
where:  
The statements are executed at least once.  
Statements are optional. If none are included, Do...Loop acts  
as a delay.  
32  
Rev E  
M-SS-005-03l  
Danaher Motion  
For example:  
Dim Shared i as Long  
06/2005  
BASIC Moves Development Studio  
Program  
i = 0  
Do  
i = i + 1  
Print i  
Loop Until i = 10  
End Program  
or, equivalently, you can use Loop While:  
Dim Shared i as Long  
Program  
i = 0  
Do  
i = i + 1  
Print i  
Loop While i < 10  
End Program  
GoTo unconditionally redirects program execution. The syntax is:  
GoTo Label1  
Label1:  
where:  
Label1 is a valid label within the same task as the GoTo.  
The label must be on a separate line.  
You can only branch within a Program, Event, Function, or  
Subroutine.  
You can GoTo a label placed within a program block  
(If…Then, For…Next, Select…Case, While…End While,  
and Do...Loop) only if the GoTo and label are within the  
same block.  
If the program is within a program block, you cannot GoTo a  
label outside that block.  
Avoid GoTo wherever possible. History has shown that excessive use of  
GoTo makes programs harder to understand and debug. Use the other  
program control statements whenever possible.  
2.2.13.1. ERROR TRAPPING  
There are four ways to specify catch statements: Exact Value, Logical  
Condition, Range, and Else. The syntax used is:  
Catch Error_Number  
{statements to execute if error Error_Number had occurred}  
Catch Is <RelationalOperator> Error_Number  
{statements to execute if the condition is true}  
Catch Error_Number1 To Error_Number2  
{statements to execute if error number is between values}  
Catch Else  
{statements to execute if all other errors had occurred}  
where:  
The number of Catch statements is not explicitly limited.  
Error_Numbers can only be long-type numeric values.  
In Catch…To…, if Error_Number1 > Error_Number2, the  
catch statement is never true and no error is flagged.  
M-SS-005-03  
Rev E  
33  
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
Catch statements are used within three types of error trapping blocks.  
The Try block is designed to trap synchronous errors within task context (For  
more details, see the Error Handling section). There is no explicit limitation  
on the number of Try blocks instances in a program. The syntax for a Try  
block is:  
Try  
{code being examined for synchronous errors}  
{Catch Error_Number  
{statements to be executed}}  
{Catch Is <RelationalOperator> Error_Number  
{statements to be executed}}  
{Catch Error_Number1 To Error_Number2  
{statements to be executed}}  
{Catch Else  
{statements to be executed}}  
{Finally  
{statements to be executed if an error was trapped}}  
End Try  
An example of a Try block, designed to catch errors in the loading process of  
Task1.Prg:  
Try  
Load Task1.Prg  
Catch 4033  
Print “Task not found”  
Catch 6007  
KillTask Task1.Prg  
‘ File does not exist  
‘ Task must be killed first  
Unload Task1.Prg  
Load Task1.Prg  
Catch Else  
Print “Error while loading Task1.Prg”  
Finally  
Print “Caught error: “ Task1.prg.Error  
End Try  
The OnError block is designed to trap and process both synchronous  
and asynchronous errors in a task. OnError traps errors not trapped by  
the Try/Finally mechanism within the task. (For more details, see “Error  
Handling” section). Only one instance of OnError may exist in a  
program. The syntax for OnError block is:  
OnError  
{Catch Error_Number  
{statements to be executed}}  
{Catch Is <RelationalOperator> Error_Number  
{statements to be executed}}  
{Catch Error_Number1 To Error_Number2  
{statements to be executed}}  
{Catch Else  
{statements to be executed}}  
End OnError  
34  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
BASIC Moves Development Studio  
An example of an OnError block, designed to stop motion in case of a  
motion error:  
OnError  
Catch 3001 To 3999  
System.Motion = 0  
A1.Enable = 0  
‘ Motion errors  
? VESExecute("System.Motion = 1")  
A1. Enable = 1  
Print "Caught a Motion error: " ThisTask.Prg.Error  
Catch Else  
Print "Caught a non-Motion error: " ThisTask.Prg.Error  
End Onerror  
The OnSystemError block is designed to trap and process both  
synchronous and asynchronous errors in all tasks, as well as errors that  
occur within the context of the system (For more details, see the Error  
Handling section). Only one instance of OnSystemError may exist in  
the system. The syntax for OnSystemError block is:  
OnSystemError  
{Catch Error_Number  
{statements to be executed}}  
{Catch Is <RelationalOperator> Error_Number  
{statements to be executed}}  
{Catch Error_Number1 To Error_Number2  
{statements to be executed}}  
{Catch Else  
{statements to be executed}}  
End OnSystemError  
An example of an OnSystemError block, designed to monitor errors in  
task Errors.Prg:  
OnSystemError  
Catch Is < 12000  
Print “Caught a MC error: ” System.Error  
‘ MC errors  
KillTask Errors.Prg  
Catch Is > 20000  
Print “Caught a user error: ” System.Error  
‘ User defined errors  
KillTask Errors.Prg  
End OnSystemError  
2.2.13.2. NESTING  
Program control commands can be nested. Nesting is when one program  
control command (or block of commands) is within another. There is no  
specified limit on the number of levels of nesting.  
For example, the following program nests a WHILE…END WHILE sequence  
within a FOR…NEXT sequence:  
For I = 1 to 10  
N=5  
While N>0  
N=N-1  
'This command will be executed 50 times  
End While  
Next I  
There is no specified limit on the number of levels of nesting. The Sample  
Nesting Program in Appendix A shows numerous combinations of nesting.  
M-SS-005-03  
Rev E  
35  
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
2. 3  
PROGRAM DECLARATIONS  
You must declare the start of programs and subroutines. For programs, use  
Program…End Program. Use Sub…End Sub keywords for subroutines.  
2.3.1. Program  
The Program…End Program keywords mark the boundary between the  
variable declaration section and the main program. Each task must have only  
one Program keyword, which ends with the End Program keyword. Another  
option is the Program Continue…Terminate Program block. In this case, the  
program is automatically executed after loading, and automatically unloaded  
from memory when it ends.  
{Import of libraries}  
{Declaration of global and static variables}  
PROGRAM  
END PROGRAM  
{Local functions and subroutines}  
2.3.2. Subroutine  
Parameters (either scalar or array) passed to the subroutine are used within  
the code of the subroutine. The declaration line for the subroutine  
(SUB<name>) is used to declare names and types of the parameters to pass.  
Parameters are passed either by reference or by value (ByVal). The default  
method is to pass parameters by reference. Whole arrays are passed only  
by reference. Trying to pass a whole array by value results in a translation  
error. However, array elements can be passed both by reference and by  
value. The syntax for a subroutine is:  
SUB <name> ({<par_1>([*])+ as <type_1>}…{, <par_n>([*])+ as<type_n>})  
END SUB  
<par_l>: name of array variable  
<par_n>: name of array variable  
[*]: dimension of an array without specifying the bounds  
+: means one or more [*]  
SUB CalculateMean(x[*][*] as DOUBLE, TheMean[*] as LONG)  
DIM sum as DOUBLE  
DIM I as LONG  
FOR i = 1 to 100  
sum = sum + x[i][1]  
NEXT i  
TheMean[1] = sum/100  
END SUB  
SUB PrintMean(ByVal Mean as LONG)  
PRINT “Mean Value Is “, Mean  
END SUB  
CALL CalculateMean(XArray, TheMeanArray) ‘ Pass entire array by reference  
CALL PrintMean(TheMeanArray[1])  
‘ Pass a single array element by value  
36  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
BASIC Moves Development Studio  
When a variable is passed by reference (whether the variable is local to the  
task or global), the address of the variable is passed to the subroutine, which  
changes the value of the original variable (if the code of the subroutine is  
written to do this).  
When a variable is passed by value (ByVal) a local copy of the value of the  
variable is passed to the subroutine, and the subroutine cannot change the  
value of the original variable.  
There is no explicit limit on the number of subroutines allowed in a task. All  
subroutines must be located following the main program and must be  
contained wholly outside the main program. Subroutines can only be called  
from within the task where they reside. Subroutines may be recursive (can  
call itself). Use CALL to execute a subroutine with the following syntax:  
CALL <subroutine_name>{(<par_1>{, …<par_n>})}  
Parentheses are not used in subroutine CALL if no parameters are passed.  
MC-BASIC automatically checks the type of compliance between the  
subroutine declaration and the subroutine call. Any mismatch (in number of  
parameters or parameters types) causes an error during program loading.  
Automatic type casting applies only for “by value” long and double  
parameters.  
SUB MySub(RefPar as long, byval ValPar as double)  
END SUB  
CALL MySub(LongVar, “String”) -> type mismatch in second parameter  
CALL MySub(LongVar) -> wrong number of parameters  
CALL MySub(LongVar, 2) -> a valid type casting for a by-value parameter  
CALL MySub(DoubleVar, 2.2) -> invalid type casting for a by-ref parameter  
2.3.3. User-Defined Functions  
MC BASIC allows the definition of user functions to be used in programs in  
the same manner as using BASIC's pre-defined functions. User-defined  
functions are composed with multiple lines and may be recursive (can call  
itself). Unlike BASIC's system functions, the scope of user-defined functions  
is limited to the task in which it is defined.  
Functions are different from subroutines in one respect. Functions always  
return a value to the task that called the function. Otherwise, functions and  
subroutines use the same syntax and follow the same rules of application  
and behavior.  
Because functions return a value, function calls should be treated as  
expressions. Therefore, function called can be combined within print  
commands, assignment statements, mathematical operations and conditions  
of flow control statements. They can also be passed as by-value parameters  
of system or user-defined functions and subroutines.  
PRINT <function_name>{(<par_1>{, …<par_n>})}  
<variable_name> = <function_name>{(<par_1>{, …<par_n>})}  
IF <function_name>{(<par_1>{, …<par_n>})} > 10 THEN  
? LOG( <function_name>{(<par_1>{, …<par_n>})} )  
M-SS-005-03  
Rev E  
37  
 
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
Parentheses are not used in function CALL if no parameters are passed.  
Parameters (either scalar or array) passed to the function are used within the  
code of the function. Declare variable names and types of parameters in the  
declaration line of the function. Parameters can be passed by reference or by  
value. The default is by reference.  
Arrays can only be passed by reference. Trying to pass a whole array by  
value results in a translation error. On the other hand, array elements can be  
passed by reference and by value.  
To set up the return value, assign the return value to a virtual local variable  
with the same name as the function somewhere within the code of the  
function. This local variable is declared automatically during function  
declaration and the function uses it to obtain the return value.  
There is no explicit limit on the number of functions allowed in a task. All  
functions must be located following the main program and must be contained  
wholly outside of the main program.  
MC-BASIC automatically checks the type of compliance between the  
function declaration and the function call. Any mismatch (in number of  
parameters, in parameters and returned value types) causes an error during  
program loading. Automatic type casting applies only for long and double  
returned values and “by value” parameters. For example:  
Function LongReturnFunc(…) As Long  
LongReturnFunc = “String”  
End Function  
-> type mismatch in returned value  
Function LongReturnFunc(…) As Long  
LongReturnFunc = 43.7  
End Function  
-> valid type casting in returned value  
A function can be recursive (can call itself). The following example defines a  
recursive function to calculate the value of N:  
FUNCTION Factorial (ByVal N As Long) As Double  
'By declaring N to be long, this truncates floating point numbers  
'to integers  
'The function returns a Double value  
If N < 3 then  
Factorial = N  
Else  
'This statement stops the recursion  
'0!=0; 1!=1' 2!=2  
Factorial=N * Factorial(N-1)  
End If  
'Recursive statement  
END FUNCTION  
When writing a recursive function, you must have an IF statement to force  
the function to return without the recursive call being executed. Otherwise,  
the function never returns once it is called.  
2. 4  
LIBRARIES  
Some applications repeatedly use the same subroutines and functions. Such  
subroutines and functions can be gathered into a library file. The library file  
can be imported to another task with IMPORT on the .lib file at the beginning  
of the task. Then, each public subroutine and function defined in the  
imported library file can be called within the importing task.  
38  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
BASIC Moves Development Studio  
An MC-BASIC library is an ASCII file containing only the subroutines’ and  
functions’ code. The file does not have a main program part. The name of a  
library file must have the extension, .LIB. The format of a library file is:  
Declarations of static variables  
{PUBLIC} SUB <sub_name>  
{declaration of variables local to the sub-program}  
{sub code}  
END SUB  
{PUBLIC} FUNCTION <function_name> AS <return_type>  
{declaration of variables local to the function-program}  
{function code}  
END FUNCTION  
The Public keyword allows a subroutine or a function to be called from  
within the importing task. These subroutines and functions are visible from  
outside the scope of the library. Subroutines and functions declared without  
the Public keyword can only be used inside the scope of the library. They  
are PRIVATE library functions. For example:  
PUBLIC SUB public_sub(…)  
END SUB  
SUB private_sub(…)  
END SUB  
The subroutine, private_sub, can be used only inside the library (i.e., by  
other subroutines and functions of the library). public_sub can be used in  
any user task (program file, another library file) importing the library.  
However, the same library can be imported by multiple tasks  
simultaneously.  
A library file is handled like any other program file. A library file can be sent  
to the Flash disk, or retrieved and deleted from Flash disk. To use a library  
file in a program, the library must first be loaded into memory from either the  
terminal or another task.  
LOAD MyLib.lib  
To unload the library, enter:  
UNLOAD MyLib.lib  
If a program or library task references a subroutine or a function of a library,  
the program or library task must be unloaded from memory before the  
library can be unloaded.  
After a library is loaded in memory, it must then be imported into a program.  
IMPORT must be placed at the beginning of the program code before any  
other command or declaration.  
IMPORT MyLib.lib  
The syntax for calling a library subroutine or function from the importing task  
is the same as the syntax for calling a local subroutine or function. There is  
no need to specify which library file contains the called subroutine or  
function (because a task cannot import two libraries defining subroutines or  
functions with identical names).  
M-SS-005-03  
Rev E  
39  
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
2.4.1. Global Libraries  
Global libraries are library files (.LIB), which, instead of being loaded from  
either the terminal or another task, are loaded from the configuration file  
(Config.Prg). Another option is loading from terminal, using LOADGLOBAL.  
PUBLIC subroutines and functions defined in such libraries can be called  
from everywhere (i.e., terminal and other tasks), without first being imported  
by the calling task. IMPORT cannot be applied to global libraries.  
LOAD GlobLib.lib  
LOADGLOBAL GlobLib.lib  
‘ In Config.Prg  
‘ In terminal  
IMPORT GlobLib.lib Æ Error  
‘ In task or library  
The syntax for calling a global library’s subroutine or function from either the  
terminal or task is the same as the syntax for calling a subroutine or  
function of a regular (imported) library. Because of the wide recognition  
scope of global, public functions and subroutines, the names of such  
subroutines and functions cannot be used for another function or  
subroutine, variable, motion element, etc. As in regular libraries,  
subroutines and functions declared without the PUBLIC keyword can only  
be used inside the scope of the library.  
A global library cannot be unloaded if there are task files (.PRG) loaded in  
memory. To unload a global library, all .Prg files must first be unloaded. If a  
global library file is unloaded and then reloaded from either the terminal or a  
task, it becomes a regular library, which must be imported before use.  
2. 5  
C-FUNCTIONS  
The MC offers users an outstanding option to incorporate applications written  
in C or C++ into an MC-Basic task.You can write your algorithm in C/C++,  
compile it with a GNU compiler, download it into a target program and call  
the code from a program written in MC-Basic or directly from the command  
line.  
The parameters can be passed by value as well as by reference. This  
function returns a value that can be processed by an MC-Basic application.  
MC-BASIC provides a facility to load a user object-file into the RAM of the  
MC. This file is relocatable and must include information about global  
symbols for the MC to find the C-function. The object module may consist of  
any number of functions. The only restriction is RAM limit.  
2.5.1. Object Files  
Object files (extension “.o”), contain compiled C-programs and are stored in  
the Flash disk. You can SEND object files to the controller, load files into  
RAM with OLOAD and unload them with OUNLOAD. If OLOAD/OUNLOAD  
fails for any reason, details are found in the OLOAD.ERR file.  
40  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
BASIC Moves Development Studio  
2.5.2. Prototype File  
For the MC-Basic language translator to match function parameters, provide  
a C-function prototype file (PROTO.PRO). It is important to understand that  
matching between the provided MC prototype and actual C implementation  
cannot be tested by the translator. It is your responsibility to keep  
consistency between the function prototype and C implementation.  
To speedup translation of the prototype file, PROTO.PRO is  
copied into RAM at startup and at every OLOAD. When  
PROTO.PRO is modified and sent to the controller, issue an  
OLOAD or reboot the MC to refresh the prototypes in the RAM.  
NOTE  
The translator is case-insensitive, while object module loader is case-  
sensitive, so write the name of a C function in capital letters within the C  
code. MC prototypes of C functions and C function calls through the MC are  
not case sensitive.  
Parameters can be passed “by value” and “by reference”  
Few object files may be incrementally linked together.  
The general syntax for the MC prototype of a C-function is:  
IMPORT_C <Function_Name> ({AS <type>}, {BYVAL AS {<type>}) {AS <type>}  
A parameter passed by value has the BYVAL prefix.  
A parameter passed by reference has no prefix.  
Prototypes do not include parameter names.  
A C function prototype with no parameters is written with empty parentheses:  
IMPORT_C <Function_Name> ( ) {AS <type>}  
A C function prototype with no returned value (a void function) is written as:  
IMPORT_C <Function_Name> ({AS <type>}, {BYVAL AS {<type>})  
A C-function accepts any combination of double-, long- and string-type  
parameters. The parameters may be passed “by value” or “by reference”.  
The returned value may be long, double, string or none (for C functions with  
void returned value).  
Examples of prototypes and implementation:  
MC-Basic Prototype  
import_c cFunc_LV As Long  
C Implementation  
int CFUNC_LV(void);  
import_c cFunc_DV As double  
double CFUNC_LV(void);  
char* CFUNC_LV(void);  
import_c cFunc_SV As string  
import_c cFunc_VV()  
void CFUNC_VV(void);  
import_c cFunc_LL(ByVal As Long) As Long  
import_c cFunc_DRD(As Double) As Double  
import_c cFunc_SRS(As String) As String  
Import_C cFunc_LARD([*] as Long) as Double  
import_c cFunc_SS(ByVal As String) As String  
int CFUNC_LL(int L);  
double CFUNC_DRD(double* D);  
char* CFUNC_SRS(char** S);  
double CFUNC_LARD(long *l);  
char* CFUNC_SS(char* S);  
Parameters can be of type long, double or string; in any order, up to 32  
parameters.  
Only one-dimensional arrays are allowed as C-functions arguments.  
M-SS-005-03  
Rev E  
41  
 
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
Example of calling a C-function from MC-Basic:  
Dim shared Str2global as string  
Dim shared Str1global as string  
Dim shared LongArray[100] as long  
Dim shared d1 as double  
program  
'
'
Use OLOAD to load the object file before loading the program  
that uses the C-Functions  
'
'
/* No Parameters */  
int CFUNC_LV(void)  
?CFUNC_LV()  
'
'
double CFUNC_DV(double)  
?CFUNC_DRD(1.2345)  
/* returns string */  
char* CFUNC_SV(void)  
?CFUNC_SV()  
'
'
/* No Parameters, not return value */  
void CFUNC_VV(void)  
CFUNC_VV()  
/* Strings */  
char* CFUNC_SS(char* S)  
Str2global=CFUNC_SS(Str1global)  
'
'
'
'
/* Arrays */  
double CFUNC_LARD(long *l);  
d1=cFunc_LARD(LongArray)  
end program  
Example of PROTO.PRO:  
'No Parametrs  
import_c CFUNC_LV() As Long  
import_c CFUNC_DV() As Double  
import_c CFUNC_SV() As String  
import_c CFUNC_VV()  
'A Single "By Value" Parameter  
import_c CFUNC_LL(ByVal As Long) As Long  
import_c CFUNC_DD(ByVal As Double) As Double  
import_c CFUNC_SS(ByVal As String) As String  
'A Single "By Reference" Parameter  
import_c CFUNC_LRL(As Long) As Long  
import_c CFUNC_DRD(As Double) As Double  
import_c CFUNC_SRS(As String) As String  
'Multiple "By Value" Parametrs  
import_c CFUNC_LVALP(ByVal As double, ByVal As Long, ByVal As  
String) As Long  
import_c CFUNC_VVALP(ByVal As String, ByVal As double, ByVal AS  
Long)  
'Multiple "By Reference" Parameters  
import_c CFUNC_DREFP(As String, As Long, As Double) As Double  
import_c CFUNC_VREFP(As Long, As Double, As String)  
' Mixed Parameters  
import_c CFUNC_VMIXP(ByVal As Long,As Double,ByVal As String,As  
String,As Long,ByVal As double) AS Long  
42  
Rev E  
M-SS-005-03l  
Danaher Motion  
Example of test.c:  
06/2005  
BASIC Moves Development Studio  
/* No Parameters */  
int CFUNC_LV(void)  
{
return 1;  
}
double CFUNC_DV(void)  
{
return 2.2;  
}
char* CFUNC_SV(void)  
{
return "SV";  
}
void CFUNC_VV(void)  
{
int fd = open("/tyCo/1",2,0);  
fdprintf(fd,"VV\r\n");  
close(fd);  
}
/* A Single "By Value" Parameter */  
int CFUNC_LL(int L)  
{
L = L + 1;  
return L;  
}
double CFUNC_DD(double D)  
{
D = D + 2.2;  
return D;  
}
char* CFUNC_SS(char* S)  
{
strcpy(S,"SS");  
return S;  
}
/* A Single "By Reference" Parameter */  
int CFUNC_LRL(int* L)  
{
*L = *L + 3;  
return *L;  
}
double CFUNC_DRD(double* D)  
{
*D = *D + 4.4;  
return *D;  
}
char* CFUNC_SRS(char** S)  
{
strcpy(*S,"SRS");  
return *S;  
}
/* Multiple Parameters */  
/* By Value Parameters */  
int CFUNC_LVALP(double D, int L, char* S)  
Continued on next page……….  
M-SS-005-03  
Rev E  
43  
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
{
return (D + L + atoi(S));  
}
void CFUNC_VVALP(char* S, double D, int L)  
{
int fd = open("/tyCo/1",2,0);  
fdprintf(fd,"Original Values:%d, %f, %s\r\n", L, D, S);  
L = 10;  
D = 22.2;  
strcpy(S,"VValP");  
fdprintf(fd,"New Value:%d, %f, %s\r\n", L, D, S);  
close(fd);  
}
/* By Reference Parameters */  
double CFUNC_DREFP(char** S, int* L, double* D)  
{
return (*D + *L + atof(*S));  
}
2.5.3. Special Considerations  
Motion and System properties can only be passed by value.  
KILLTASK will not unblock a task locked inside the C-function. An endless  
block on a semaphore, message queue, etc. inside a C-function prevent sa  
task from correct being killed. If C-function has some blocking operation  
system call (taskDelay(), semTake(), msgQGet(), msqQSend(), IO operation,  
etc.), this may interfere with killing the user task.  
When an object module is loaded several times without unloading, all its  
instances are kept in the RAM, while the system symbol table has references  
only to the resent instance. MC-Basic applications may refer to the obsolete  
version of some modified object file.  
OUNLOAD does not check to see if the object file is in use. It is your  
responsibility to ensure that the object is not unloaded as long as there tasks  
and libraries that refer to the object.  
Consider following example, both the program TASK1.PRG and  
TASK2.PRG use the same function from object module.  
Æoload my_obj.o  
Æload TASK1.PRG  
Æsend my_obj.o  
Æoload my_obj.o  
Æload TASK2.PRG  
‘ send updated version of object file  
In this example, TASK1.PRG references the oldest instance of my_obj.o  
while TASK2.PRG references the recent version.  
44  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
BASIC Moves Development Studio  
2. 6  
SEMAPHORES  
Semaphores are the basis for synchronization and mutual exclusion. The  
difference is that the mutual exclusion semaphore is created as “full” or “1”,  
while the synchronization semaphore is empty “0”. If the semaphore is used  
for protecting mutual resources, it is taken before accessing the resource  
and releases at the end. A synchronization semaphore is given by the  
producer and taken (consumed) by the consumer.  
A semaphore is created as “full.”  
NOTE  
Global semaphore are defined with COMMON SHARED in CONFIG.PRG or  
from the command line. Since a semaphore's purpose is to protect data  
among tasks, there is no meaning to local semaphores.  
A semaphore is given/released by SEMAPHOREGIVE and taken/consumed  
by SEMAPHORETAKE. It is possible to specify a time out of up to 5000 ms.  
SEMAPHORETAKE acquires a semaphore and returns before timeout or  
does not acquire a semaphore and returns after timeout.  
Mutual exclusion semaphores are taken and given by the same task.  
Synchronization semaphores are given by one task and taken by  
another task.  
NOTE  
2.6.1. Mutual Exclusion Semaphores  
Mutual exclusion semaphores lock resources by taking a semaphore.  
Another task(s) competing for the same resource is blocked until the  
semaphore is released.  
Example of a mutually exclusive semaphore:  
‘ common shared comMutex as semaphore  
‘ defined in config.prg  
Program  
Open COM2 BaudRate=9600 Parity=0 DataBits=8 StopBit=1 As #1  
While 1  
‘ take semaphore lock serial port  
If SemTake(comMutex,5000) = 1 Then  
Print #1,”Hello ”;  
Print #1,”world”  
SemGive(comMutex)  
End if  
‘unlock serial port  
End While  
End program  
M-SS-005-03  
Rev E  
45  
 
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
2.6.2. Synchronization Semaphores  
Synchronization semaphores are essential in producer-consumer  
applications where task A prepares some data, while task B consumes it. In  
this case, the semaphore may eliminate constant polling for ready data and  
save considerable CPU resources.  
Example of Producer:  
‘ common shared syncSemaphore as semaphore  
‘ defined in config.prg  
‘ common shared globalA as long  
config.prg  
‘ defined in  
Program  
Dim dummy as long  
‘ Semaphore is created as “full” - flush it before first use  
dummy=semTake(syncSemaphore)  
While 1  
‘ no waiting  
globalA=globalA+1  
semGive(syncSemaphore)  
sleep (100)  
‘ produce some data  
End While  
End program  
Example of Consumer:  
' common shared syncSemaphore as semaphore  
' defined in config.prg  
' common shared globalA as long  
' defined in config.prg  
Program  
While 1  
If SemTake(syncSemaphore,5000) = 1 Then  
Print "A is "; globalA  
End if  
End While  
End program  
2. 7  
VIRTUAL ENTRY STATION  
Virtual Entry Station (VES) allows a CLI-like approach to the system from  
any task or library. VES permits access to virtually any system property. The  
application developer must take into account that, in the contrast to regular  
programs and libraries, the string is passed to VES and are interpreted and  
translated at run-time. Execution takes much more time than the equivalent  
line in the program.  
The response of VES is ASCII an string, which could be immediately printed  
or assigned to any string variable. Since VES involves translation and then  
interpretation, the result could also be an error message. To distinguish  
between a normal response and an error, VES gives either a “D:” or “E:”  
prefix to the output.  
46  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
VES Example:  
06/2005  
BASIC Moves Development Studio  
Program  
Dim s2 as string  
Dim s1 as string  
S2="?sys.time"  
S1=VesExecute(s2)  
Print s1  
S1=VesExecute(“sys.time”) ‘ incorrect, returns syntax error  
Print s1  
End program  
Output:  
D:18:27:19  
E:Error: 7039, "Syntax Error", Module: Translator  
2. 8  
OUTPUT REDIRECTION  
Typically, tasks inherit their standard output from the loading context, such  
as the entry station or standard output of a loader task. Sometimes, you must  
redirect task output (print) to a different place, such as another entry station  
or even a virtual entry station. RedirectStdOut/RedirectStdOut$ provides this  
capability.  
-->RedirectStdOut task32.prg NewStdOut=1  
-->  
NewStdOut may be:  
1 – Ethernet  
2 – DPRAM  
3 – Virtual Entry Station  
4 – Etherent2  
Systems with FPGA version 8.51, firmware 4.0.0 and higher  
support IP over DPRAM. NewStdOut type is 1,3 or 4.  
CAUTION  
2. 9  
FILE OPERATIONS  
Input and output, whether to or from files, are supported on Flash and RAM  
devices. The files are accessed either in serial or random order. Currently,  
only ASCII text files are supported – both printable and non-printable  
characters.  
2.9.1. OPEN  
Opens an existing file or creates a new one with the name specified in the  
string expression. The file name should not exceed 8 characters plus  
extensions. Acceptable file extensions are:  
PRG , DAT , TSK , CMP for permanent files on the Flash disk  
REC for temporary files on the RAM disk  
You can open a text file to read, write or append to the existing file according  
to mode flag.  
“r” - open text file for reading  
“w” - truncate to zero length or create text file for writing  
“a” - append; open or create text file for writing at end-of-file  
Use APPEND to add new lines at the end of the original contents of the  
file.Use WRITE to overwrite the previous file or to create a new file.  
M-SS-005-03  
Rev E  
47  
 
BASIC Moves Development Studio  
06/2005  
Danaher Motion  
2.9.2. OPEN #, INPUT #, CLOSE, LOC  
See Serial port.  
2.9.3. TELL  
Returns current file pointer, offset from the beginning of the file. Value has  
meaning only for SEEK to move the file pointer within a file.  
2.9.4. SEEK  
Moves file pointer to specified location. Use with TELL.  
File operations example:  
program  
dim pos as long  
dim d1 as double  
dim s1 as string  
'create file for writing  
Open "test.prg" mode ="w" as #1  
print #1, "1.2345"  
close #1  
'append to existing file  
Open "test.prg" mode ="a" as #1  
print #1, PI  
close #1  
'read from file  
Open "test.prg" mode ="r" as #1  
'how many characters in the file?  
print "File contains ";loc(1);" characters"  
s1 = input$(#1)  
'convert from string to double  
d1=val(s1)  
?d1  
'save current file pointer  
pos = tell(#1)  
?input$(#1)  
'rewind file  
seek (#1,pos)  
?input$(#1)  
close #1  
end program  
Output:  
File contains 31 characters  
1.234500000000000e+00  
3.141592653590000e+00  
3.141592653590000e+0  
48  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Project  
3.  
PROJECT  
A project is all the software written for an application. The projects in MC-  
BASIC are multi-tasking. They consist of many tasks running concurrently  
with, and independently of, each other. The project is stored in multiple files,  
one file for each task. Tasks are routines that run simultaneously with many  
other tasks. Projects also include other files such as cam tables and record  
files. Projects are controlled from the BASIC Moves (BMDS) software. BMDS  
automatically sets up a separate directory for each project. For detailed  
information on any commands listed within this section, refer to the  
SERVOSTAR® MC Reference Manual.  
For clarity, a project is managed by BMDS and conveniently handles a group  
of logically coupled files (programs, CAM tables, etc.), while the MC deals  
with separate files (PRG, CAM, etc.). The Motion controller does not keep  
project files in the Flash and it is not aware of logical coupling of files and  
programs.  
3. 1  
PROJECT STRUCTURE  
Project files include tasks and cam tables. Each project can contain three  
types of tasks:  
General-purpose task  
An optional configuration task (Config.Prg) to declare groups,  
programmable limit switches (PLS), cams, global variables and load of  
global libraries.  
An optional autoexec task (Autoexec.Prg) to automatically start the  
application on power-up.  
3. 2  
TASKS  
The three types of tasks are general-purpose tasks, configuration tasks, and  
autoexec tasks. Each type of task is outlined below.  
3.2.1. General Purpose Tasks  
General-purpose tasks are the work horse of the MC language. They  
implement the basic logic of your application. The great majority of your  
programming is implemented with general-purpose tasks. Each general-  
purpose task is divided into three sections: a task-variable section, a main  
program, and subroutines. The main program is further divided into three  
sections: a Start-up section, an OnError section, and an OnEvent section.  
M-SS-005-03  
Rev E  
49  
 
Project  
06/2005  
Danaher Motion  
A task-variable definition section  
The task-variable definition section, where all task variables are declared  
with the Dim…Shared command.  
The main program  
Most programming is done in the main programming section. The main  
programming section falls between the Program…End Program keywords.  
The main program itself has three sub-sections:  
The Start-up section  
The start-up section immediately follows the Program keyword. This is  
where task execution begins when you start a task.  
OnError section  
The OnError section responds to errors generated by the task, allowing  
your program to automatically respond to error conditions and (where  
possible), gracefully recover and restart the machine. There is (at most)  
one OnError section for each task and it is normally written just before  
the OnEvent section.  
OnEvent section  
This section contains optional blocks of code that respond to realtime  
changes, such as a motor position changing or an input switch turning  
on. The main program can contain code to automatically respond to  
events. This reduces the effort required to make tasks respond quickly  
and easily to realtime events.  
Event handlers begin with the OnEvent and end with End OnEvent  
keywords. One OnEvent…End OnEven keyword combination is  
required for each realtime event. Event handlers must be contained  
wholly within the main program.  
50  
Rev E  
M-SS-005-03l  
Danaher Motion  
Optional subroutines  
06/2005  
Project  
Each task can have any number of subroutines. Subroutines are component  
parts of the task, and consequently, they can only be called from within the  
task. If you want to call the same subroutine from two tasks, place one copy  
in each task.  
3.2.2. Configuration Task  
The name of the configuration task is Config.Prg. The configuration task is  
used for declaration of number of axes, global variables and other  
constructs, such as cam tables, programmable limit switches (PLS), and  
group. The key to understanding the configuration task is that all data and  
constructs shared across tasks must be declared in the configuration task.  
Refer to the following figure.  
The configuration task can contain a program. Axes can be renamed here.  
3.2.3. AutoExec Task  
The AutoExec task (AutoExec.Prg) is executed once on power up, just after  
the Configuration Task. Use AutoExec to start power-up logic. For example,  
you might want to use AutoExec to start a task that sets the outputs to the  
desired starting values. That way, the outputs are set immediately after the  
MC boots, usually sooner than the PC.  
For safety considerations we do not recommend starting of motion from the  
AutoExec task. Motion should be started by explicit operator’s request either  
by I/O or communication link from host PC.  
Set the AutoExec task to run on power up. To do this, add the keyword  
Continue to the Program command. Do not include OnError or OnEvent  
sections in the AutoExec. Limit the AutoExec task to starting other tasks in  
the system. Refer to the next figure.  
M-SS-005-03  
Rev E  
51  
 
Project  
06/2005  
Danaher Motion  
3. 3  
PROGRAM DECLARATIONS  
You must declare the start of programs and subroutines. For programs, use  
the Program…End Program keywords. Use Sub…End Sub keywords for  
subroutines.  
The Program…End Program keywords mark the boundary between the  
variable declaration section and the main program. Each task must have only  
one Program keyword and end with the End Program keyword.  
Program  
<code for program>  
End Program  
‘Standard form of program command  
The AutoExec task, which must be loaded and run automatically at power-up  
must have CONTINUE following Program.  
You pass parameters (either scalar or array) to the subroutine, which can  
then be used in the code of the subroutine. In the declaration line for the  
subroutine (SUB<name>), you declare the variable names and types of the  
parameters to pass. Parameters are passed either by reference or by value  
(ByVal). The default method is to pass parameters by reference. Arrays are  
passed only by reference. When you pass a variable (whether the variable is  
local to the task or is global) by reference, you pass the address of the  
variable to the subroutine, which changes the value of the variable (if the  
code of the subroutine is written to do this). When you pass a variable by  
value (ByVal) a copy of the value of the local variable is passed to the  
subroutine. The subroutine cannot change the value of the local variable.  
The syntax for defining a subroutine is:  
SUB <name> ({{ByVal} <p_1> as <type_1> }…{, {ByVal} <p_n> as type_n>})  
{ local variable declaration }  
{ subroutine code }  
END SUB  
There is no explicit limit on the number of subroutines allowed in a task. All  
subroutines must be located following the main program, and must be contained  
wholly outside the main program. Subroutines can only be called from within the  
task where they reside. Subroutines may be recursive (call itself).  
52  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Project  
Use CALL to execute a subroutine:  
CALL <subroutine>({<p_1>...<p_n>})  
where:  
<subroutine> is the name of the subroutine  
<p_1>...<p_n> are the subroutine parameters  
Parentheses are not used in a subroutine if no parameters are passed.  
MC-BASIC automatically checks the type of compliance between the  
subroutine declaration and the subroutine call. Any type mismatch causes an  
error during program loading. Automatic casting applies to numericc  
variables types. For example, suppose MySub is a subroutine that takes a  
Long parameter. In this case, the following scenario applies:  
CALL MySub(3.3432)  
'OK: The double value 3.3432 is demoted to the Long value, 3  
CALL MySub(a)  
'Error: a is a string, there is a type mismatch  
Call MySub(3,4)  
'Error: The number of parameters is not correct  
See the Subroutine Example in Appendix A for further details.  
3.3.1. Arrays  
Arrays can only be passed by reference. If a user tries to pass a whole array  
by value, the translator gives an error. Array syntax is:  
SUB <name> ({<p_1>([*])+ as <type_1>}…{, <p_n>([*])+ as <type_n>})  
{ local variable declaration }  
{ subroutine code }  
END SUB  
where  
<p_l> : name of array variable  
<p_n> : name of array variable  
[*]  
+
: dimension of array without specifying the bounds  
: means one or more  
Syntax example:  
SUB mean(x[*][*] as DOUBLE, TheMean[*] as LONG)  
DIM sum as DOUBLE  
DIM I as LONG  
FOR i = 1 to 100  
sum = sum + x[i][1]  
NEXT i  
TheMean[1] = sum/100  
END SUB  
Subroutine Libraries. As you develop programs for a variety of applications,  
you will find that there are some subroutines that you use repeatedly. You  
can collect such subroutines (and user-defined functions) into a library file.  
Then, when you program a task, import the .lib file at the beginning of the  
program and you call any of its defined subroutines (functions).  
An MC-BASIC library is an ASCII file containing only the sub-program's  
code. The file does not have a main program part. The names of the library  
files must have the extension, .LIB.  
M-SS-005-03  
Rev E  
53  
 
Project  
06/2005  
The format of a library file is:  
Danaher Motion  
Declaration of static variables  
...Etc.  
{PUBLIC}SUB <sub_name_1> etc…  
{Declaration of variables local to the sub-program}  
{sub-program code}  
END SUB  
…etc …  
{PUBLIC} SUB <sub_name_n> etc…  
{Declaration of variables local to the sub-program}  
{sub-program code}  
END SUB  
The {PUBLIC} keyword allows a subroutine to be called from within any MC  
task. These subroutines are visible from outside the scope of the library.  
Sub-routines declared without the {PUBLIC} keyword can only be used  
inside the scope of the library. They are PRIVATE library functions. For  
example:  
PUBLIC SUB public_sub(…etc…)  
…etc…  
END SUB  
SUB private_sub(…etc…)  
…etc…  
END SUB  
The subroutine “private_sub” can be used only inside the library. The  
"public_sub” can be used in any program file by importing the library into it.  
The scope of the library is the task that imports it. However, you can import  
the library into each of multiple tasks.  
A library file is used like any other program file. You can send a library file to  
the Flash disk and you can retrieve it or delete it. In order to use a library file  
in a program, the library must first be loaded into memory.  
LOAD MyLibrary.lib  
To unload the library, enter:  
UNLOAD MyLibrary.lib  
If a program or library task references a subroutine in a library, the program  
or library task must be unloaded from memory before the library can be  
unloaded.  
After a library is loaded in memory, it must then be imported into a program.  
IMPORT must be placed at the beginning of the program code before any  
other command or declaration.  
IMPORT MyLibrary.lib  
The syntax for calling a library subroutine or function from a task is the same  
as the syntax for calling a local subroutine from the task. You do not need to  
specify which library file contains the subroutine you want to call (because you  
can not import two library files that contain the same library function name).  
User-defined Functions. MC BASIC allows you to define your own  
functions to be used in programs in the same manner as using BASIC's pre-  
defined functions. User-defined functions are composed with multiple lines  
and are recursive (can call itself). Unlike BASIC's system functions, the  
scope of user-defined functions is limited to the task in which it is defined.  
54  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Project  
Functions are different from subroutines in one respect. Functions always  
return a value to the task that called the function. Otherwise, functions and  
subroutines use the same syntax and follow the same rules of application  
and behavior.  
Because funtions return a value, you can use functions expressions (i.e.,  
tangent=sin(x)/cos(x) or If (Sgn(x) Or Sgn(y)) Then…). The syntax for  
defining a function is:  
Function <name> ({{ByVal} <p_1> as <type_1> }…{, {ByVal} <p_n> as type_n>}) As  
<function type>  
{ local variable declaration }  
{ function code }  
END function  
You can pass parameters (either scalar or array) to the function. These  
parameters are then used in the code of the function. Declare the variable  
names and types of parameters you want to pass in the declaration line for  
the function. Parameters can be passed by reference or by value (ByVal).  
The default is by reference. When you pass a variable by reference, you  
actually pass the address of the variable to the function, which changes the  
value of the variable (if the function code is written to do this). When you  
pass a variable by value, a copy of the value of the variable is passed to the  
function. The function cannot change the value of the variable. Arrays are  
only passed by reference.  
To set up the return value, assign the value you want to return to a virtual  
variable with the same name as the function somewhere in the code of the  
function. You do not declare the variable, but the function uses it to obtain  
the return value. If the function's code includes conditional statements,  
assignments to the function variable can be made in multiple locations in the  
function code.  
There is no explicit limit on the number of functions allowed in a task. All  
functions must be located following the main program and must be contained  
wholly outside of the main program.  
A function can be recursive (can call itself). The following example defines a  
recursive function to calculate the value of N:  
FUNCTION Factorial (ByVal N As Long) As Double  
'Declaring N as long truncates floating point numbers to integers  
'The function returns a Double value  
If N < 3 then  
Factorial = N  
Else  
'This statement stops the recursion  
'0!=0; 1!=1' 2!=2  
Factorial=N * Factorial(N-1) 'Recursive statement  
End If  
END FUNCTION  
When writing a recursive function, you must have an IF statement to force  
the function to return without the recursive call being executed. Otherwise,  
the function never returns once it is called.  
3. 4  
MULTI-TASKING  
The MC supports multi-tasking. You can have multiple tasks running  
independently, sharing a single computer. A task is a section of code that  
runs in its own context. Microsoft Windows® is a multi-tasking system. If you  
open Explorer and Word at the same time, they run nearly independently of  
each another.  
M-SS-005-03  
Rev E  
55  
 
Project  
06/2005  
Danaher Motion  
In this case, both Explorer and Word have their own contexts. They share  
one computer, but run as if the other were not present. There is inter-task  
communication. If you double-click on a document in the file manager, it  
launches Word to edit the file you clicked.  
With MC-BASIC, you can use different tasks to control different operational  
modes: one for power up, one for set-up, one for normal operation, and  
another for when problems occur. Like Windows, each task can run  
independently of the others, and you can prescribe interactions between  
tasks.  
Multi-tasking is used when you want multiple processes to run largely  
independent of each other. For example, if you are using the MC to interface  
to the operator, you will usually use a separate task to execute the interface  
code. Another example is when two parts of a machine are largely  
independent of each other. There is usually some control required between  
tasks as one task may start or stop another.  
If a machine is simple to control, you should try to keep the entire program in  
one task (in addition to Config.Prg). If you do need to use multi-tasking, you  
should keep a highly structured architecture. Kollmorgen recommends that  
you limit use of the main task for axis and group set up, machine  
initialization, and controlling the other tasks. Normal machine operation  
should be programmed in other tasks. For example, Main.Prg might be  
limited to setting up axes, and then starting Pump.Prg, Conveyor.Prg, and  
Operator.Prg.  
Do not split control of an axis or group across tasks. You can put control for  
multiple axes in one task. Ideally, you should use multiple tasks for machines  
where different sections operate more or less independently. You can also  
use tasks to implement different operational modes.  
Multi-tasking is a powerful tool, but it carries a cost. It is easy to make errors  
that are difficult to find. When multiple tasks are running concurrently,  
complex interaction is difficult to understand and recreate. Limit the use of  
tasks to situations where they are needed.  
Do not create a task as a substitute for an event handler. Events and tasks  
are not the same. MC-BASIC supports event handlers to respond to realtime  
events. Events are similar to interrupts in microprocessor systems. They  
normally run at higher priorities than the programs that contain them. They  
are ideal for quick responses to realtime events. Add the event handler to an  
existing task to respond to an event.  
Do not use tasks in place of subroutines. Remember that when you start a  
task, the original task continues to run. When you call a subroutine, you  
expect the calling program to suspend execution until the subroutine is  
complete. The behavior of tasks where the two routines continue to execute  
can cause complex problems.  
Knowing when to use multi-tasking and when to avoid it requires some  
experience. If you are new to multi-tasking, you may want to start slow until  
you are familiar with how it affects program structure. When you start a new  
project, BASIC Moves creates the main task as part of opening a new  
project. After that process is complete, you can add a new task to your  
project by selecting File, New. You can also press the new task button on the  
BASIC Moves tool bar.  
56  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Project  
3.4.1. Loading the Program  
BASIC Moves automatically loads all tasks in your project when you select  
Run Project. You can select Run Project by selecting it from the Debug  
menu, by pressing the F5 key, or by pressing the “Load Task”and “Run  
Task” buttons on the tool bar. By default, tasks are loaded from the host PC  
to the MC at a low priority (Priority = 16).  
When you select Run Task, the project’s main task is started at the lowest  
priority (Priority = 16). You can change the priority of the main task by  
selecting View-> Project Manager->Options and then changing the priority in  
the bottom of the window. If you structure your software so that the main  
program loads all other tasks, the Run Project button starts your machine.  
3.4.2. Preemptive Multi-tasking & Priority Levels  
Because many tasks share one processor, you must carefully design your  
system so tasks get processing resources when they need them. You do not  
want the operator interface taking all the resources when you need fast  
response to a realtime event. The operating system provides system  
resources based on two criteria: task priority level and time slice.  
When you create a program, you must select the task priority level. MC-  
BASIC allows you to specify 16 levels of priority. The task with the highest  
priority takes all the system resources it can use. In fact, no task of a lower  
priority receives any resources until all tasks of higher priority relinquish  
them. Most systems have one main task that runs at a medium priority and  
perhaps a background task that runs at a low priority, with a few high priority  
tasks. At every time slice, the MC re-evaluates which task has the highest  
priority and assigns resources to it.  
The BASIC Moves terminal window relies on the MC command line task,  
which runs at priority 2. If you start a task with priority 1, the terminal will not  
be available until the task is complete or idle. Consequently, you will not be  
able to communicate with the MC and you may have to power-down the  
system to recover the terminal window. You can optionally set the priority of  
a task when you start it. For example:  
StartTask Aux.Prg Priority=6  
The default priority of events is 1 (highest) and the default priority of  
programs is 16.  
Time Slice is a method by which the operating system divides up resources  
when multiple tasks share the same priority level. The MC provides the first  
task with one time slice, the next time slice goes to the second, the next to  
the third, and so on. The time slice is currently one millisecond duration. This  
method is sometimes called round robin scheduling.  
3.4.3. Inter-Task Communications and Control  
Tasks can control one-another. In fact, any task can start, continue, idle, or  
kill any other task, regardless of which task has the higher priority. For  
detailed information on these commands, refer to the SERVOSTAR® MC  
Reference Manual.  
M-SS-005-03  
Rev E  
57  
 
Project  
06/2005  
Danaher Motion  
StartTask starts tasks from the main task. For testing, you can use  
STARTTASK from the terminal window. DanaherMotion recommends you  
do not use STARTTASK in AutoExec.Prg. The syntax of STARTTASK is:  
StartTask <TaskName> {Priority = <Level>}{NumberOfLoops = <Loop Count>}  
NOL is a short form for NumberOfLoops.  
NOTE  
where:  
<Level> is a long with value between 1 and 16. If <Level> is not  
entered, it defaults to 16, the lowest priority. Priority = 1  
is the highest priority.  
<Loop Count> is either -1 (indicating unlimited number of loops) or  
between 1 and 32768 indicating the number of  
times the task is executed. If <Loop Count> is not  
entered, it defaults to 1.  
For example:  
StartTask Task1.Prg Priority=8 NumberOfLoops = -1  
StartTask Main.Prg NOL=1  
'Run Task1 forever  
'Run Main once  
IdleTask stops the task at the end of the line currently being executed and  
idles all its events. An idled task can be continued (using CONTINUETASK)  
or terminated (using KILLTASK). IDLETASK does not stop motion currently  
being executed. This is significant because all the events are idled and  
cannot respond to an axis' motion. Tasks can be idled explicitly by other  
tasks, but cannot idel itself. This command is issued from a task or the  
terminal window. The syntax of IdleTask is:  
IdleTask <TaskName>  
For example:  
IdleTask TASK1.PRG  
Tasks that have been idled with IDLETASK are restarted only with  
CONTINUETASK. The command continues an idled task from the point at  
which it was stopped, or continues task execution after a break point has  
been reached. It is frequently used to restart tasks from the ONERROR error  
handler. If a run time error has occured, CONTINUETASK retries the line  
which caused the error. The error must be corrected before the task  
continues. This command is issued from any task or the terminal window.  
The syntax of ContinueTask is:  
ContinueTask <TaskName>  
For example:  
ContinueTask TASK1.PRG  
KillTask aborts the execution of a task. The program pointer is left on the  
line at which the task was stopped. The first action of KILLTASK is to kill and  
delete all events associated with the task. This is done to ensure that no  
event initiates an action after KILLTASK was executed. KILLTASK is issued  
from the terminal window. The syntax of the KillTask is:  
KillTask <TaskName>  
For example:  
KillTask TASK1.PRG  
58  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Project  
3.4.4. Monitoring Tasks From the Terminal  
For detailed information on these commands, refer to the SERVOSTAR® MC  
Reference Manual.  
TASK.STATUS provides the current state of any task. You can query  
TASK.STATE from the terminal window. You cannot use TASK.STATUS  
from within a program. The syntax for TASK.STATUS is:  
? <TaskName>.Status  
For example:  
? TASK1.PRG.Status  
TASKLIST returns the state and priority of all tasks loaded in the system.  
You can query TASKLIST only from the terminal window.  
For example, if you type:  
? TaskList  
A typical result is:  
TaskName = TASK1.PRG, Status = sstep, Priority=16  
TaskName = DO.PRG, Status = suspend, Priority=4  
3.4.5. Relinquishing Resources  
When tasks of different priorities compete for processor time, the highest  
priority task always takes all the resources it needs. However, tasks of high  
priority can relinquish computer resources under some conditions. In these  
cases, tasks of lower priority run until the high priority tasks again demand  
the resources. There are three conditions under which a task relinquishes  
resources: when the task is terminated, when the task is suspended, or when  
the task is idled. For detailed information on these commands, refer to the  
SERVOSTAR® MC Reference Manual.  
A task terminates when it is finished executing. If a task starts with  
NUMBEROFLOOPS greater than zero, the task executes the specified  
number of times and terminates. The task relinquishes all resources.  
Terminated tasks remain loaded in the system and can be restarted.  
One task can terminate another task by issuing KILLTASK. A task  
relinquishes all resources after the kill command. Killed tasks remain in the  
system and can be restarted.  
Tasks relinquish processing resources temporarily when they are  
suspended. A task is suspended when it is waiting for a resource or is  
delayed. Suspended tasks still monitor events as long as the event priority is  
higher than the task priority. Never run a task at a higher priority level than  
any of its events.  
Use SLEEP to delay a task for a specific period of time. This command can  
only be issued from within the task. One task cannot issue a SLEEP for  
another task. SLEEP causes the task to relinquish resources until the sleep  
time has expired.  
Idled tasks relinquish resources. In this case, resources are relinquished  
until another task revokes the idle by issuing a CONTINUETASK.  
Delete Task/Library deletes a file from the Flash Disk. Only filesnot loaded  
into RAM can be deleted.Files that are protected by a password may not be  
deleted. For example:  
Delete FILE1.PRG  
M-SS-005-03  
Rev E  
59  
 
Project  
06/2005  
Danaher Motion  
3. 5  
EVENT HANDLER  
The main program can contain sections which automatically handle events.  
This reduces the programming effort required to make tasks respond quickly  
and easily to realtime events. Event handlers begin with OnEvent and end  
with End OnEvent and occur just after the Program keyword.  
After OnEvent is loaded, turn the event On with EventOn just after the End  
OnEvent keyword (enable immediately). However, you can enable and  
disable OnEvent at any time using EventOn and EventOff. Multiple  
OnEvents can be written sequentially. The MC system can support up to 64  
events. The number of OnEvent(s) in a single task is not restricted, so a task  
may have from 0 to 64 OnEvent(s).  
It is important to understand that OnEvents are different from ordinary tasks.  
OnEvents are preemptive within the task. That is, an OnEvent runs until  
complete and the program execution returns to the main program. While an  
OnEvent is executing, it does not release CPU time to the parent task or any  
other task. In this sense, OnEvents are similar to interrupt calls. They run to  
completion before execution returns to the main program. An OnEvent must  
have a higher priority than its parent task to ensure that when an event  
occurs, it interrupts its parent task and runs to completion. The rules are valid  
for a single process, (that is, the parent task and its events), while events of  
the respective tasks in the system share the CPU among themselves.  
3.5.1. OnEvent  
The syntax of OnEvent is:  
OnEvent [EventName] [Condition] {Priority=EventPriority}{ScanTime=time}  
where  
EventName is any legal name that is otherwise not used in the  
task.  
Condition is any logical expression such as System.Dout.1 = 1.  
The event fires on transitions of the condition from false  
to true.  
Priority is an integer from 1 (highest) to 16 (lowest). If not entered,  
priority defaults to 1. The priority should always be  
higher than the priority of the task or the event never  
runs.  
Time is an integer indicating the number of cycles between each  
scan. Time defaults to 1.  
In this example, an event is set up to move axis "X-axis" to 10000 counts  
each time an input goes high:  
OnEvent MOVE_ON_TRIGGER System.Din.1=ON  
Move X-axis 10000  
End OnEvent  
Normally, event handlers run at a high priority so that once the event occurs,  
they run to completion. In most cases, this code should be very short as it  
usually takes all resources until it is complete.  
ScanTime is in cycles of the SERCOS update rate. This is normally 2 or 4  
milliseconds. Setting ScanTime to 5 configures the system to check the  
event condition every 10 or 20 milliseconds, depending on your update rate.  
For example:  
OnEvent System.Din.2 = ON ScanTime = 5  
60  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Project  
Events can either be controlled from within the task in which they reside, or  
from the terminal. The main program or any subroutine can issue EventOn  
(to enable the OnEvent command) or EventOff (to disable it). OnEvents  
cannot be controlled from other tasks.  
3.5.2. EventOn  
EventOn enables OnEvent. The syntax of EventOn is:  
EventOn [Event Name]  
EventOn must come after the definition of the OnEvent.  
3.5.3. EventOff  
EventOff disables OnEvent. The syntax of EventOff is:  
EventOff [Event Name]  
Refer to the SERVOSTAR® MC Reference Manual for information additional  
information about OnEvent, EventOn, and EventOff.  
3.5.4. EventList  
EventList provides a complete list of all events in all tasks with their name,  
the task name, the priority, whether the event is armed, and current status.  
EventList is valid only from the terminal window. For example:  
? EventList  
the result is something like the following line for each task:  
Name = IOEvent Owner=Task1 Edge=1 Status=1 Scan=1 Priority=5  
Action = Stop  
where:  
edge=1 indicates the event is armed (that is, the condition is false  
so that the condition becoming true will fire the OnEvent)  
status=1 means the event is enabled  
3.5.5. EventDelete  
Deletes the specified event. The event does not respond to the specified  
condition until the task is executed again and the event is enabled.  
EventDelete EVENT1  
3.5.6. Events at Start-up  
Events are normally triggered by the OnEvent condition changing from false  
to true. So a single transition in the condition is required to run OnEvent.  
One exception to this is start-up. At start-up, if the condition is true, OnEvent  
executes once, even if there has not been a transition.  
3.5.7. Program Flow and OnEvent  
You can use GoTo commands within an OnEvent block of code. However,  
because OnEvent interrupts the main program, you cannot use GoTo to  
branch out of the event handler or into the event handler. You cannot place  
OnEvent…End OnEvent in the middle of program flow commands (e.g.,  
For…Next, If…Then, etc.). You cannot declare or use local variables inside  
an OnEvent block.  
M-SS-005-03  
Rev E  
61  
 
Project  
06/2005  
Danaher Motion  
3. 6  
SETTING UP AXES  
In this section, we set up the axes in the system. We will discuss units for  
position, velocity, and acceleration. We discuss how the SERVOSTAR MC’s  
acceleration profile works. We talk about how to set up limits for axes. We  
conclude with a discussion of a few advanced topics: an overview of  
SERCOS, simulated axes, and dual-loop position control.  
3.6.1. Axis Definition  
The MC is oriented around axes. An axis is a combination of a drive, a  
motor, and some portions of the MC. The diagram below shows an MC axis:  
Each axis has a set of properties that are defined by the MC. These  
properties are used in the calculation of position and velocity commands,  
monitoring limits, and stores configuration data for the axis. The MC sends  
commands to the drive and the drive controls the motor. All these  
components together form an axis of motion.  
3.6.2. Axis Name  
The MC automatically sets up all your axes according to their addresses: A1,  
A2, A3, and so on until A32 ( the maximal number of axes is limited by User  
Autorization Code by manufacturer ). You access axis properties by  
preceding the property name with the axis name and a period. For example,  
each axis has a property, VELOCITYFEEDBACK, which provides the  
current velocity of that axis. You can query the VELOCITYFEEDBACK  
value with the ? command in the BASIC Moves terminal:  
? A1.VelocityFeedback  
62  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Project  
You can rename the axis. It is usually worthwhile to name the axes according  
to their function. It makes your program easier to understand and to debug.  
For example, you could enter:  
A1.AxisName = ConveyorAxis  
Later, you can query the velocity with:  
? ConveyorAxis.VelocityFeedback  
The axis name may only be changed into the configuration program  
Config.Prg. You cannot print the axis name at any time.  
3.6.3. Drive Address  
You must specify the drive address property of the axis. Simulated axes do  
not have drive addresses and do not require this property to be assigned.  
This assigns the physical address (dip switch setting on the SERVOSTAR  
drive) to the axis defined in the SERVOSTAR MC. If we wanted to assign the  
drive with address 5 to axis 1, we type the following command into the  
terminal window of the BASIC Moves Developer Studio or in our program:  
A1.Dadd = 5  
‘ Assign drive address 5 to axis 1  
The short form, DADD, of axis property DRIVEADDRESS is used in the  
example. Axis.DriveAddress property should meet to the drive hardware  
address configuration . Most axis properties and constants have short forms  
that can speed typing and ease the programming effort. Refer to the  
SERVOSTAR® MC Reference Manual for more information.  
3.6.4. Starting Position  
Before we get started here, you must:  
Install and tune drives  
Follow the process for installing and tuning all drives according to the  
SERVOSTAR® MC Installation Manual. Run MOTIONLINK® to select  
your motor type and tune the axis to your satisfaction.  
Install and check out your MC  
Install and check out your SERVOSTAR MC according to the  
SERVOSTAR® MC Installation Manual. Wire all I/O, connect the fiber-  
optic ring, and follow the procedures in the SERVOSTAR® MC  
Installation Manual to check out the wiring.  
Install BASIC Moves Development Studio  
Install BASIC Moves Development Studio after reviewing the BASIC  
Moves User’s Manual. We use the terminal screen here extensively.  
Remember, any commands typed in the terminal window are lost when  
you power down. Enter these commands in your MC program to be  
recalled at power up.  
3.6.5. BASIC Moves Auto Setup Program  
BMDS automatically generates a setup program each time you open a new  
project. BMDS first requests information regarding units and preferences for  
each axis in the system. Then, it generates a program with most of the setup  
for your application.  
The auto setup program has four sections: a short task-variable declaration,  
an example program which generates simple motion, a SERCOS setup  
subroutine, and an axis setup subroutine. The variable declaration section  
provides one or two examples of variable declarations for a task.  
M-SS-005-03  
Rev E  
63  
 
Project  
06/2005  
Danaher Motion  
The motion program cycles axis A1 10 times. Most of this main program is  
commented out because this code enables the drive and generates motion  
commands. Remove the single-quote comment markers for the program to  
run. These lines are commented out because to ensure that it is safe to  
operate your machine before executing this program. This includes tuning  
your axes properly to assure stable motion control. Refer to the  
SERVOSTAR® MC Installation Manual for more information.  
The third section of the auto setup program is a SERCOS setup subroutine.  
This subroutine brings up the SERCOS ring in preparation for the drives  
being enabled. The final section of the auto setup program is the axis setup  
subroutine. This subroutine loads axis properties for units and limits. Refer to  
Appendix A for a Sample Nesting Program.  
3.6.6. User Units  
The MC supports user units with one floating-point conversion factor for each  
of six types of properties: position, velocity, acceleration, jerk, external  
position, and external velocity.  
<axis>.DIRECTION is applied as a multiplier to the units conversion factors.  
The movement factors (i.e., POSITIONFACTOR, VELOCITYFACTOR,  
ACCELERATIONFACTOR) are only assigned positive values and  
DIRECTION determines their sign. DIRECTION can take one of two values:  
-1 for forward direction or +1 for reverse direction.  
MC units allow you to work in units that are convenient. All unit types are  
independent, so position units are inches, velocity units are feet/min and  
acceleration is rpm/second. Units are changed only when the axis is  
disabled.  
3.6.7. Position Units  
Position units are controlled by POSITIONFACTOR or PFAC. The MC  
internal units are encoder counts for encoder-based systems or 65536  
counts per revolution for resolver-based systems. Encoder counts are four  
times encoder lines. To set up position units, determine how many counts  
are in one of your selected units. For example, suppose you had this system:  
Desired units: inches  
Rotary motor (as opposed to linear motor)  
2000 line Encoder  
3:1 gearbox  
5 turn per inch ball screw  
Determine POSITIONFACTOR (number of counts per inch):  
1 inch = 5 turns on the screw  
= 15 turns into the gearbox  
= 15 * 2000 lines  
= 15 * 2000 * 4 counts  
= 120,000 counts  
POSITIONFACTOR is set to the number of counts per inch: 120000.  
A1.PositionFactor = 120000  
For a second example, let’s change the first example from encoder to  
resolver, change the ball screw and use meters for the units:  
Desired units: meters  
Rotary motor  
Resolver (65536 counts per revolution)  
3:1 gearbox  
2 turn/cm ball screw  
64  
Rev E  
M-SS-005-03l  
   
Danaher Motion  
06/2005  
Project  
Determine POSITIONFACTOR (number of counts per meter):  
1 meter = 200 turns on the screw  
= 600 turns into the gearbox  
= 600 * 65536 counts  
= 39,321,600 counts  
POSITIONFACTOR is set to the number of counts per meter: 39321600. If  
you use the BASIC Moves auto setup program, provide the motor resolution  
and number of motor rotations per unit movement and BASIC Moves  
calculates the math.  
3.6.8. Velocity Units  
Velocity units convert MC internal velocity units (counts/mSec) to your units.  
They are controlled using VELOCITYFACTOR or VFAC. Normally, velocity  
units are either the position units per second or per minute, or they are rpm.  
If you want velocity units to be your position units per second, set  
VELOCITYFACTOR to POSITIONFACTOR divided by 1000 (to convert  
milliseconds to seconds):  
A1.VelocityFactor = A1.PositionFactor/1000 ‘ for position units/sec  
If you want position units per minute, divide by 60000:  
A1.VelocityFactor = A1.PositionFactor/60000 ‘ for position units/min  
If you want rpm, you must calculate the number of counts per revolution and  
then divide that by 60000 (to convert milliseconds to minutes):  
Desired units: rpm  
2000 line Encoder  
You first need to determine the number of counts per inch for each  
revolution:  
1 rev = 2000 lines  
= 2000 * 4 counts  
= 8000 counts  
VelocityFactor is set to the number of counts per revolution divided by  
60000:  
A1.VelocityFactor = 8000/60000  
3.6.9. Acceleration Units  
Acceleration units convert MC internal acceleration units (counts/msec2) to  
your units. They are controlled using <axis>.ACCELERATIONFACTOR or  
<axis>.AFAC. Normally, acceleration units are either the velocity units per  
second or per minute. If you want acceleration units to be your velocity units  
per second, set ACCELERATIONFACTOR to VELOCITYFACTOR divided  
by 1000 (to convert milliseconds to seconds). Divide by 60000 to set  
acceleration units to velocity units per minute:  
A1.AccelerationFactor = A1.VelocityFactor/1000 ‘Accel units = vel/sec  
or  
A1.AccelerationFactor = A1.VelocityFactor/60000 ‘Accel units = vel/min  
M-SS-005-03  
Rev E  
65  
   
Project  
06/2005  
Danaher Motion  
3.6.10. Jerk Units  
It is also necessary to define the jerk factor, even if you always use the  
smooth factor. The smooth factor automatically defines the jerk value from  
the velocity and acceleration values, but it is a value before factors, therefore  
totally invalid values of jerk (internally) can be computed. At least set  
Jfac=Afac/1000 and it should work. <axis>.JERKFACTOR specifies the  
conversion factor between your jerk units and the internal units [counts per  
msec3]. <axis>.JERKFACTOR must contain the conversion factor for both  
the position dimension and the time dimension.  
3. 7  
ACCELERATION PROFILE  
The MC provides smooth, controlled acceleration profiles to reduce vibration  
and wear on the machine, and to allow high acceleration rates. The  
SERVOSTAR MC allows you to independently control acceleration and  
deceleration to further reduce vibration. For detailed information any listed  
commands, refer to the SERVOSTAR® MC Reference Manual.  
ACCELERATION and DECELERATION control the acceleration rates. The  
following lines of code entered at the terminal window (or in your program)  
change the acceleration rates for Axis A1:  
A1.Acceleration = 1000  
A1.Deceleration = 1000  
Do not enter these commands yet. Acceleration units should be set before  
these values are entered. You can impose limits which constrain the time  
during which acceleration and deceleration occurs. The motion includes  
three major parts: acceleration phase, constant velocity cruise phase, and  
deceleration phase.  
Time-based Acceleration/Deceleration is the motion interface in which the  
duration of the acceleration/deceleration phases during the movement is  
defined. These duration times will be used internally to calculate proper  
motion parameters to meet the time requirements as accurate as possible.  
<axis/group>.TIMEACCELERATION and  
<axis/group>.TIMEDECELERATION can be used for time-based definition.  
Jerk is the first derivative of acceleration. Fast moves usually generate large  
amounts of jerk. Having a large amount of jerk in a motion profile can excite  
machine resonance frequencies and thereby, cause unnecessary wear and  
noise. Some motion controllers simplify motion profiles by instantaneously  
changing the acceleration command which implies a very high level of jerk.  
The MC allows you to limit the amount of jerk in all profiles by using the axis  
properties SMOOTHFACTOR or JERKFACTOR.  
Specify trapezoidal profiles by setting SMOOTHFACTOR (SMOOTH) to  
zero. If you want a smoother acceleration, increase the SMOOTHFACTOR  
from 1to a maximum of 100. If SMOOTHFACTOR is large (greater than 50),  
it can increase the acceleration time by one or more orders of magnitude.  
Using <axis>.ACCELERATION and <axis>.JERK to limit velocity changes  
produces acceleration profiles that remove the high frequency components  
of torque that are present in straight-line acceleration. This minimizes the  
excitation of machine resonance frequencies which in turn reduces audible  
noise, vibration, and mechanical wear. For example, the figure below shows  
a typical MC acceleration profile showing how controlled jerk produces  
smooth acceleration.  
66  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Project  
3. 8  
POSITION AND VELOCITY  
Position and velocity are the key command and feedback signals for each  
axis. These properties are updated by the MC every SERCOS cycle and  
may be read at any time. Their properties are double-precision floating point  
numbers. Velocity Units are discussed above. The four properties which hold  
these values are:  
<axis>.POSITIONCOMMAND or <axis>.PCMD  
<axis>.POSITIONFEEDBACK or <axis>.PFB  
<axis>.VELOCITYCOMMAND or <axis>.VCMD  
<axis>.VELOCITYFEEDBACK or <axis>.VFB  
You can read these properties anytime the SERCOS ring is up.  
Position error is defined as the difference between position commanded and  
position feedback. When an axis is at rest, (i.e., ISSETTLED), this simple  
definition of position error is valid. However, when the axis is in motion, the  
true position error does not equal the instaneous commanded position minus  
the instantaneous feedback position because there is a time delay of two  
SERCOS cycle times (2 ms) from when MOVE is issued until the feedback  
position is received.  
When the MC calculates position error, it automatically accounts for the  
communication delay. In most circumstances, the two-cycle time delay is  
correct. However, if microinterpolation is enabled in the drive, the feedback  
position is delayed an additional one or more cycle times.  
To manage position error problems, the MC provides a number of axis and  
group properties relating to position error. <axis>.POSITIONERRORDELAY  
(new in firmware version 3.0), allows you to specify the number of SERCOS  
cycle times to apply when calculating position error. The default is two.  
The MC allows you to set up any axis in your system as a rotary axis. Rotary  
axes are often used for mechanical mechanisms that repeat after a fixed  
amount of rotation.  
M-SS-005-03  
Rev E  
67  
 
Project  
06/2005  
Danaher Motion  
For example, a motor driving a rotating table is often configured as a rotary  
axis. In this case, the table units are set up as degrees and the units of the  
axis are set to repeat after 360°. In that way, the position repeats after every  
rotation of the table, rather than continuing to increase indefinitely. The key  
to the rotary mode is setting rollover position (POSITIONROLLOVER or  
PROLLOVER) correctly and accurately.  
Consider this example where the axis drives a rotary table through a 5:3  
gearbox:  
Desired units: Degrees  
Desired repeat: 360  
Gearbox:  
Feedback  
5:3  
2000 line encoder  
For this example, first set position units to degrees:  
1 degree = 1/360 revolution of table  
= (5/3) * (1/360) revolution of the motor  
= 2000 * (5/3) * (1/360) lines  
= 4 * 2000 * (5/3) * (1/360) counts  
= 40000/1080  
After setting these units, you must enable the rotary mode and set the  
rollover to 360 as follows:  
A1.PositionFactor = 40000/1080  
A1.PositionRollover = 360  
A1.PositionRolloverEn = On‘Enable Rotary Motion  
In this case, the feedback position is always between 0 and 360. You can still  
command long moves, say 10,000 degrees. However, when the motor  
comes to rest, the feedback is read as less than 360.  
When using rotary mode in applications where the motor turns continuously  
in one direction, it is important to take advantage of all available accuracy in  
the MC. This is because inaccuracy is accumulated over many revolutions of  
the motor. For example, we could have rounded A1.POSITIONFACTOR in  
the above example to 37.037, which is accurate to 1 part in 1,000,000.  
However, after 10,000 revolutions (2000 rpm for just 5 minutes), that 1 part in  
a 1,000,000 would have accumulated to a few degrees. This means that if  
the table position is 100 degrees, it might read as 97°. In other words, the  
table appears to drift.  
In the example above, the math is exact until the MC performs the division.  
Because the MC calculates with double precision (about 14 places of  
accuracy), you should use MC math when calculating ratios that cannot be  
represented precisely in decimal notation. In the example, using the full  
accuracy of the MC (about one part in 1014) the motor would have to travel  
about 3x1011 revolutions to accumulate one degree of error. That is  
equivalent to 88 years of continuous rotation at 6000 rpm.  
All SERVOSTAR drives provide interface hardware to accept an external or  
auxiliary encoder. This encoder is in addition to the primary position  
feedback device. You will need to set up the SERCOS telegram to support  
this. External position is frequently used in master-slave operations (gearing  
and camming) where the system is slaved to an external signal such as a  
line-operated motor.  
68  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Project  
The MC provides the external position through the axis property,  
POSITIONEXTERNAL or PEXT. This variable contains the accumulated  
encoder movement of the drive’s external encoder input. It is updated every  
SERCOS cycle.  
You can access PEXT two ways: realtime or on a as-needed basis. To  
access PEXT on an as-needed based, issue IDNVALUE. For example:  
Dim Shared StorePExt as Double  
StorePExt = IDNValue(1, 53, 7)  
This gets PEXT in counts, not user units. You can access PEXT in realtime  
by properly configuring the telegram for the axis with the external encoder.  
The SERVOSTAR MC allows you to control the units of the  
POSITIONEXTERNAL (PEXT). This is controlled with  
<axis>.POSITIONEXTERNALFACTOR or <axis>.PEXTFAC. The process  
is identical to setting position units for an encoder. The external position and  
velocity factors are only effective for cases when the SERCOS telegram is  
configured to transmit the external encoder.  
Do not access PEXT using IDNVALUE because the encoder values coming  
into the drive are subject to rollover. The MC continuously monitors these  
values and adjusts the value when a rollover is detected. The values  
accessed via the SERCOS service channel cannot be monitored for rollover.  
Also, external position units are not in effect.  
The MC provides the external velocity through the  
<axis>.VELOCITYEXTERNAL or <axis>.VEXT. This variable contains the  
accumulated encoder movement per millisecond and is also updated every  
SERCOS cycle when the SERCOS telegram is configured to transmit the  
external encoder.  
The MC allows you to control the units of VELOCITYEXTERNAL with  
<axis>.VELOCITYEXTERNALFACTOR or <axis>.VEXTFAC. The process  
is identical to setting position units except that <axis>.VEXTFAC can only be  
input as an encoder signal.  
3. 9  
LIMITS  
This section outlines the many types of limits you can impose on the MC  
system. These limits help protect the machine from excessive excursions of  
travel, speed, and torque. There are three types of limits in the SERVOSTAR  
system:  
MC Generator Limits  
MC Realtime Limits  
Drive Limits  
Limits can be imposed in several ways. First, some limits are imposed by the  
MC and others by the SERVOSTAR drive. Limits can be checked in realtime  
or they can be checked only for subsequent actions.  
MC Generator limits affect subsequent commands to the motion generator.  
For example, if you change an acceleration limit, this has no effect on the  
current motion command, but it applies to subsequent motion commands. If  
the axis is not in a jog or acting as a slave, then POSITIONMIN and  
POSITIONMAX (position limits) are checked only at the beginning of the  
move.  
M-SS-005-03  
Rev E  
69  
 
Project  
06/2005  
Danaher Motion  
The MC checks realtime limits each SERCOS update cycle. Changes in  
these limits affect current operations. VELOCITYFEEDBACK is checked  
against VELOCITYOVERSPEED in every SERCOS cycle.  
Drive limits are imposed by the SERVOSTAR CD drive. Changes in these  
limits affect current operations. For example, ILIM limits the peak current that  
is output by the drive. These limits are imposed independently of the position  
and velocity commands issued by the controller.  
3.9.1. Position Limits  
There are several limits in the MC related to position:  
POSITIONMIN or PMIN  
POSITIONMAX or PMAX  
POSITIONMIN (PMIN) and POSITIONMAX (PMAX) place minimum and  
maximum limits on the position feedback for an axis. Set the limits with:  
A1.PositionMin = -10  
A1.PositionMax = 200.5  
or you can use the short form:  
A1.PMin = -10  
A1.PMax = 200.5  
Position limits must be enabled before they can operate. Limits are enabled  
with POSITIONMINENABLE and POSITIONMAXENABLE. Position Units  
are discussed above.  
Position limits are checked two ways. First, they are checked in the motion  
generator. If you command a position move beyond the position limits, an  
error is generated and the move does not start. Second, they are checked  
each SERCOS update cycle (generally, 2 or 4 ms). If the axis is moving and  
crosses the position limit, this generates an error.  
If the axis has already stopped because the position limits were crossed, the  
MC does allow you to back out. In other words, you can enter commands  
that move the axis back within the limits. The axis will move without  
generating errors.  
Position limits are continuously checked only when the drive is in master-  
slave mode. Some conditions may occasionally result in the motor moving  
outside PMIN or PMAX limits which are not detected by the MC. SERCOS  
loop instability may also cause position errors.  
You can control whether the MC watches either one or both of the limits in  
position limit. To do this, set POSITIONMINENABLE and  
POSITIONMAXENABLE to either ON or OFF.  
A1.PositionMinEnable = ON  
A1.PositionMaxEnable = ON  
or, you can use the short forms:  
A1.PMinEn = ON  
A1.PMaxEn = ON  
The default state of PMINEN and PMAXEN is off. You must enable them to  
use these limits.  
You should limit the maximum position error your system tolerates. You do  
this by setting <axis>.POSITIONERRORMAX (<axis>.PEMAX).  
70  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Project  
Care should be taken to set PEMAX to a value that matches the needs of  
the application. When the actual position following error (PE) exceeds  
PEMAX, motion stops. If the motion is stopped when this condition is  
detected, the axis is disabled.  
During normal operation, occasional occurrences of position error overflow  
usually indicates a malfunction of the machine, such as a worn or broken  
part, or a need for lubrication. You should set the maximum position error  
well outside the boundaries of normal machine operation or nuisance errors  
occur when the machine is running.  
During installation, position error overflow frequently occurs because the  
system is unstable. In this case, the motor runs away even though zero  
velocity is commanded. Set POSITIONERRORMAX to a reasonably small  
value before powering the system up. For example, you might set it to a few  
revolutions of the motor (or a few inches or centimeters for linear systems).  
This way, if the tuning is unstable, the system is less likely to cause a  
problem. Setting PEMAX to a very large number prevents the Position Error  
Overflow error from detecting an unstable system, and consequently, the  
motor is able to run away.  
The proportional position loop is the simplest position loop. The next figure  
shows a block diagram of a proportional position loop:  
As you can see, the velocity command is proportional to the following error.  
Large velocity commands need large following error limits. At first, the units  
of inches/min/mil may seem confusing. The following error for an  
acceleration with a typical proportional loop is shown in the next figure.  
The good news about 100% feed-forward is that it eliminates steady-state  
following error. The bad news is that the system overshoots when subjected  
to acceleration or deceleration. In some cases, this is not an issue because  
the system may always transition smoothly, or some overshoot is  
acceptable.  
M-SS-005-03  
Rev E  
71  
Project  
06/2005  
Danaher Motion  
In many cases, 100% feed-forward is not acceptable. In these cases, you  
can reduce the feed-forward to reduce overshoot. The larger the feed-  
forward gain, the greater reduction is seen steady-state following error. Most  
systems can tolerate the overshoot generated by feed-forward gains of 50%.  
Acceleration feed-forward allows the use of 100% velocity feed-forward  
with no overshoot. Acceleration feed-forward works by adding current  
equivalent to the torque required to accelerate a fixed load. Acceleration  
feed-forward effectively cancels the torque generated by the inertia changing  
speed. This is why this technique is sometimes called inertial feed-forward.  
Acceleration feed-forward works only when the inertia load is proportional to  
the axis acceleration. It does not work with axes that are coupled, such as  
non-rectangular robots. It also does not work well when the axis inertia  
varies. However, for most applications, acceleration feed-forward reduces  
overshoot and following-error significantly.  
To use acceleration feed-forward, use MOTIONLINK, or set the acceleration  
feed-forward scaling constant from the MC. Acceleration feedforward is IDN  
348. For an axis A1, the correct line of code is:  
WriteIDNValue Drive = A1.DriveAddress IDN=348 Value = 1000  
The valid range for this value is 0 to 2000. The purpose of the acceleration  
feed forward is to zero the following error during constant acceleration. The  
automatic design (user gain = 1000) gives good results. Fine-tune this value  
by applying trapezoidal trajectory and find the user gain that yields the  
minimum following error during the acceleration and deceleration.  
<axis>.POSITIONERRORSETTLE, defines what level of position error is  
considered close enough to zero to be settled. For example, you can use:  
A1.PositionErrorSettle = 0.01  
or you can use the short form:  
A1.PESettle = 0.01  
to specify that the position error must be below 0.01 units to be considered  
settled.  
POSITIONERRORSETTLE is used when the motion controller must  
determine when an axis is close enough to the final end point of a move to  
be considered settled. This is commonly used between moves to ensure that  
the response to the first move is complete before moving to the second. The  
MC does this automatically through STARTTYPE when executing MOVE  
commands as is discussed in the Single Axis Motion section of this manual.  
You must set TSETTLE>0 or POSITIONERRORSETTLE is ignored.  
TIMESETTLE (or TSETTLE) defines the amount of time the position error  
must be lower than the value of PESETTLE before the move is considered  
settled. After the move profile is complete and the position error is less than  
POSTIONERRORSETTLE, the MC waits TIMESETTLE milliseconds for  
settling. If the position error goes above POSITIONERRORSETTLE during  
that time, the timer resets.  
ISSETTLED is a logical (TRUE or FALSE) property that indicates if the axis  
is settled. To be settled, the motion profile must be complete and the position  
error must be below POSITIONERRORSETTLE for a period of  
TIMESETTLE milliseconds.  
72  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Project  
ISMOVING is a property that indicates the state of the motion profiler. The  
valid range of values is from –1 to 3, with the following meaning:  
-1 = element is a slave (gear or cam) unless an incremental move is  
issued, in which instance the following values are valid:  
0 = element is not moving  
1 = element is accelerating  
2 = element is at constant velocity phase (cruise)  
3 = element is decelerating  
Example:  
While a1.ismoving > 0  
End While  
‘wait for profiler to finish  
3.9.2. Axis Velocity Limits  
There are several limits in the MC related to velocity:  
VelocityOverspeed  
VelocityMax  
Acceleration  
Deceleration  
VELOCITYOVERSPEED defines an absolute motor velocity limit. When this  
limit is exceeded, an error is generated and the axis is brought to an  
immediate stop. VELOCITYOVERSPEED is in MC velocity units and is set  
any time. It is checked every SERCOS update cycle. For example:  
A1.VelocityOverspeed = 4000  
VELOCITYMAX (VMAX) sets the maximum speed that the motion  
generator can command. VELOCITYMAX is in MC velocity units and is only  
set from the terminal window or in the configuration file, Config.Prg. It is  
checked at the beginning of each move. For example:  
A1.VelocityMax = 5000  
Two limits control acceleration and deceleration which themselves limit the  
velocity transients on acceleration profiles. These properties may be set from  
the terminal or in a user task (or any other context). These are  
ACCELERATIONMAX and DECELERATIONMAX.  
ACCELERATIONMAX is the upper limit for acceleration in motion  
commands. It is in MC acceleration units. ACCELERATIONMAX is set up in  
the BASIC Moves auto-setup program when you start a new project.  
DECELERATIONMAX is the upper limit for deceleration in motion  
commands. It is in MC acceleration units. DECELERATIONMAX is set up in  
the BASIC Moves auto-setup program when you start a new project.  
3. 10  
VELOCITY, ACCELERATION AND JERK  
RATE PARAMETERS  
Axis.VelocityRate defines the axis velocity maximum scaling factor from 0.1  
to 100 persents independently of acceleration, deceleration or jerk.  
<axis>.VelocityRate may be modal or nodal.  
Axis.AccelerationRate defines the axis acceleration maximum scaling  
factor from 0.1 to 100 persent independently of velocity, deceleration or jerk.  
<axis>.AccelerationRate may be modal or nodal.  
M-SS-005-03  
Rev E  
73  
 
Project  
06/2005  
Danaher Motion  
Axis.DecelerationRate defines the axis deceleration maximum scaling  
factor from 0.1 to 100 persent independently of velocity, acceleration or jerk.  
<axis>.DecelerationRate may be modal or nodal.  
Axis.JerkRate defines the axis Jerk maximum scaling factor from 0.1 to 100  
persents independently of velocity, acceleration or deceleration.  
<axis>.JerkRate may be modal or nodal.  
For example:  
A1.VRate = 50  
A1.ARate = 70  
A1.DRate = 80  
A1.JRate = 60  
‘ VelocityRate 50%  
‘ AccelerationRate 70%  
‘ AccelerationRate 80%  
‘ JerkRate 60%  
3. 11  
VERIFY SETTINGS  
Now, you can check the system using the MC MOVE command. This  
command is discussed in detail later. For right now, use it to verify some of  
the settings above. First, enable your drive.  
3.11.1. Enabling  
Enable the drive with the following commands:  
System.Enable = ON  
A1.Enable = ON  
After the SERCOS phase is set to 4, the drive can be enabled. This condition  
is indicated with an “S” on the front of each SERVOSTAR amplifier. You do  
this with MC command:  
Sercos.Phase = 4.  
The code to do this is normally generated in the BASIC Moves auto-setup  
program which runs each time you start a new project. A decimal point at the  
bottom-left of the S on the SERVOSTAR drive display should come on when  
the drive is enabled. The decimal point may flash under certain conditions.  
You must turn on SYSTEM.ENABLE (SYS.EN) before turning on any of the  
drive-enable properties. This is because when SYSTEM.ENABLE is off, it  
forces all the axis-enable properties off.  
3.11.2. Motion Flags  
The next step in preparing a system for motion is turning on the motion flags.  
There are two motion flags that must be on: the system motion flag and the  
axis motion flag:  
System.Motion = ON  
A1.Motion = ON  
3.11.3. Move  
Now you can perform a move command. For example, enter:  
Move A1 1000 VelocityCruise = 10  
to move to position 1000 with a velocity of 10. You should see the motor  
move. Use a hand tachometer or other speed sensing device to verify that  
the speed settings are correct. Move to various positions using the  
incremental move (by setting Absolute to OFF) and verify your position units:  
Move 1000 VelocityCruise = 10 Absolute = Off  
74  
Rev E  
M-SS-005-03l  
   
Danaher Motion  
06/2005  
Project  
3. 12  
SERCOS  
The MC uses the SERCOS fiber-optic ring network to communicate with the  
drives. The SERCOS interface (SErial Realtime COmmunication System) is  
an internationally recognized specification (IEC 1491), supported by many  
companies around the world. SERCOS replaces analog connections with  
digital, high-speed fiber-optic communication. Danaher Motion supports  
2/4/8/16 Mbit/s baud rate speeds. Danaher Motion selected the SERCOS  
interface because of numerous technical advantages:  
Determinism  
SERCOS provides deterministic communication to all drives. The  
communication method provides complete synchronization between  
controller and axes, and among all axes.  
International Standard  
SERCOS is the only digital communication method for motion control  
supported by an international body. It is the only standard with motion control  
products provided by a wide base of companies.  
Reduced Wiring Between Drive And Controller  
SERCOS greatly reduces wiring between controller and drives. While analog  
and PWM amplifiers require 10 to 15 connections-per-drive, SERCOS  
requires only two fiber-optic cables between the controller and the drive.  
Noise  
Because SERCOS is based on fiber optics, electromagnetic noise is greatly  
reduced. The controller is electrically isolated from drives and feedback  
devices, as well as from limit switches and other I/O wired through the drives.  
Most grounding and shielding problems, notorious for the difficulties they  
cause during installation of analog motion control systems, are eliminated.  
Simplifying Replacement  
SERCOS allows you to download configuration parameters for all drives  
simultaneously via the SERCOS network. You can configure your system to  
automatically configure the drives after each power up. If a drive needs to be  
replaced, all re-configuration is automatically done.  
Reliable Connections  
SERCOS uses fiber optic connections to eliminate the tens or even  
hundreds of hard-wired connections between the drives and the controller.  
This eliminates many possibilities for intermittent or reversed connections.  
Access to Drive  
SERCOS provides complete access to drive data. For the SERVOSTAR  
drive, you can even record variables realtime in the drive and send the data  
via SERCOS to your PC using MOTIONLINK.  
Axis Modularity  
SERCOS relies on the drive to connect to most external signals related to an  
individual drive: feedback device, limit switches, and registration sensors.  
When an axis is added to a system, most of the wiring associated with the  
axis connects directly to the drive. This minimizes the changes to system  
wiring required to support adding or removing drives.  
M-SS-005-03  
Rev E  
75  
 
Project  
06/2005  
Danaher Motion  
3.12.1. Communication Phases  
In SERCOS, one master controller and many drives are connected with the  
fiber optic cable to form a communication ring.  
The master attempts to establish communication in a step-by-step process.  
This process is referred to as bringing up the ring. Each step is defined in  
SERCOS as a phase. In order to bring up the ring, the system must proceed  
successfully through five phases (0 through 4). The MC simplifies this  
process by allowing you to specify at which phase you want the ring. In most  
cases, you simply need to set the SERCOS property phase to 4. The main  
exception to this is when configuring telegram Type 7 to include external  
encoder data, which requires that you first set the phase to 2 and then to 4.  
In phase 0, the master establishes synchronization by passing the Master  
Synchronization Telegram (MST) to the first drive. That drive passes it to the  
next and so on until it is returned to the master, indicating that the ring is  
complete. After the master determines that 10 MST telegrams have been  
passed through the ring, phase 0 is complete.  
In phase 1, the master sends the Master Data Telegram (MDT). Each  
drive is addressed individually and each drive responds with an  
Amplifier Telegram (AT). When all drives have responded, phase 1 is  
complete.  
In phase 2, all drives are configured through a series of IDNs. First, the  
communication parameters are sent. Then, the drives are configured for  
operation.  
Up to this point, all data have been sent via the service channel. In  
phase 3, the cyclic data channel is established. Configuration is  
completed and verified.  
Phase 4 is normal SERCOS operation.  
SERCOS.PHASE automatically moves the SERCOS ring through each  
phase. You can observe this operation by watching the 7-Segment LED  
display on the SERVOSTAR drive. The number displayed indicates the  
current communication phase. When the process is complete, an S (or 5) is  
displayed, indicating that the ring is up and drives can be operated.  
3.12.2. Telegrams  
All SERCOS data are organized into data packets called telegrams.  
Telegrams transport data and also provide protocol support and error  
checking. SERCOS provides three telegrams, which are issued in order:  
Master Synchronization Telegram (MST)  
Amplifier Telegram (AT)  
Master Data Telegram (MDT)  
76  
Rev E  
M-SS-005-03l  
   
Danaher Motion  
06/2005  
Project  
The first telegram in a communication cycle is the Master Synchronization  
Telegram (MST). The MST, issued by the controller. It provides a single  
mark in time for all the drives. All feedback and command data are  
synchronized for all axes via the MST.  
Immediately after the MST is issued, each drive returns feedback and status  
data in the Amplifier Telegram (AT). This includes position and velocity  
feedback as well as responses to non-cyclic commands.  
The final telegram in the communication cycle is the Master Data Telegram  
(MDT). The controller issues the MDT. It contains information transmitted  
from the MC, such as signals and position and velocity commands. The  
service channel sends signals as well as non-cyclic commands.  
3.12.3. Telegram Types  
SERCOS provides for a variety of telegram types. Different telegram types  
define different sets of data to be exchanged in the AT and MDT. There are  
seven standard telegrams in SERCOS. The simplest telegram is Type 0,  
which defines only the service channel. No data are transferred in the cyclic  
data. The most complex type is Telegram Type 7, which allows the user to  
configure which data are in the cyclic data (all telegrams equally support the  
service channel.) The other telegrams (Types 1 through 6) define different  
combinations of position, velocity and current in the AT and MDT. The uses  
only Telegram Types 5 and 7 for data communication.  
Normally, the relies on the SERCOS telegram type 5. In Telegram  
Type 5, position and velocity feedback are transmitted by the drive in  
the AT cyclic data, and position and velocity command are transmitted  
by the MC in the MDT cyclic data. These four components are the only  
motion data transmitted in the cyclic data. Telegram type 5 works well  
unless you need to have the external encoder position brought in with  
the cyclic data. This is necessary when you want to slave an axis to the  
external encoder In this case, you need to configure a Type 7 telegram.  
When you need to bring an external encoder position from a drive to the  
MC in realtime (cyclic data) you must configure a telegram type 7 for  
the drive. This telegram must contain all the motion data found in  
telegram type 5 (position and velocity in both the AT and MDT), with the  
external encoder position added.  
To set up an axis for telegram type 7, you must modify the  
SERCOSSETUP subroutine, which is generated as part of the BASIC  
Moves auto setup program. You need to take the following steps:  
Set SERCOS.PHASE to 0 and set the baud rate  
Set the axis PEXTFAC of the axis with external encoder  
Set the drive addresses (DRIVEADDRESS)  
Set the axis MASTERSOURCE, GEARRATIO, and slave  
properties of the slave axis  
Set Sercos.Phase to 2  
Configure the axis for Telegram Type 7 using IDN 15  
Configure the AT for VFB, PFB, and PEXT (IDNs 40, 51, 53)  
Configure the MDT for VCMD, PCMD (IDNs 36, 47)  
Set SERCOS.PHASE to 4  
See SERCOS Setup Subroutine in Appendix A for a sample subroutine.  
M-SS-005-03  
Rev E  
77  
 
Project  
06/2005  
Danaher Motion  
3.12.4. Cyclic vs. Non-Cyclic Communication  
SERCOS communicates across the fiber-optic ring with two types of data:  
cyclic and non-cyclic. Cyclic data are sometimes referred to as real-time, and  
are updated at a regular rate (SERCOS update rate). The SERVOSTAR  
system supports update rates from 1 millisecond. The MC requires that the  
cyclic data include position and velocity command (transmitted from the  
controller) and position and velocity feedback (transmitted from the drives.)  
These data must be updated once each SERCOS update.  
Non-cyclic data are updated irregularly and on a demand basis via the  
service channel. The service channel is roughly equivalent to a 9600-baud  
serial link between the drives and the controller, except that it is transferred  
on the fiber optic cable along side the cyclic data. Using the service channel,  
you can request data from the drive or set a parameter that resides in the  
drive. Each SERVOSTAR drive has I/O points. You can use the service  
channel to access this I/O or you can use a Telegram type 7 to configure the  
I/O as cyclic data. The service channel is non-deterministic. Consequently,  
non-cyclic data transmits considerably slower than cyclic data.  
3.12.5. IDNs  
SERCOS commands are organized according to an Identification Number or  
IDN. SERCOS defines hundreds of standard IDNs, which support  
configuration and operation. Manufacturers, such as Danaher Motion,  
provide IDNs specific to their products. IDNs are numbered. Standard IDNs  
are from 1 to 32767 (although only several hundred are used to date) and  
manufacturer IDNs are numbered from 32768 to 65535.  
If you are using a SERVOSTAR drive, you normally use only a few IDNs for  
special functions (e.g., for querying drive I/O or changing the peak current of  
a drive).  
SERCOS requires that you define every IDN used on each drive. The  
SERVOSTAR system eliminates most of this step because the MC  
automatically defines all necessary IDNs for SERVOSTAR drives. This  
process would otherwise be tedious as there are quite a few IDNs that must  
be defined.  
Most requests from the service channel are responded to immediately. For  
example, when you set the digital-to-analog converter (DAC) on the drive,  
the value is placed in the DAC by the drive immediately upon receipt. The  
drive acknowledges the command almost as soon as it is received, thereby  
freeing the service channel for subsequent commands. However, some  
functions of the drive that are accessed from the service channel require a  
much longer time for execution. For example, incremental encoder-based  
systems must be oriented on power up. The wait for verification that the  
process has completed successfully can take many SERCOS cycles, far too  
long to tie up the service channel. To support these functions, SERCOS  
developed procedures.  
With procedures, the master starts a procedure and optionally halts and  
restarts it. Procedures allow processing in the service channel without  
blocking other communication. For example, waiting for a registration mark is  
a procedure. In this case, the motor is turning and the drive is searching for a  
registration mark. By using a procedure, the service channel remains  
available for other communication during the search.  
78  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Project  
3.12.6. Position and Velocity Commands  
The MC sends position and velocity commands in the cyclic data, and  
SERVOSTAR drives return position and velocity feedback in the cyclic data.  
This allows you to configure your system as a position or a velocity loop. It  
also allows you to switch between position and velocity loop on-the-fly. The  
format of each data type is shown below:  
Signal  
Size  
32 Bit  
32 Bit  
32 Bit  
32 Bit  
Scale  
Position Command  
Position Feedback  
Velocity Command  
Velocity Feedback  
One count  
One count  
1/256 count per SERCOS update  
1/256 count per SERCOS update  
3.12.7. SERCOS Support  
The MC provides numerous commands within the language to support  
SERCOS.  
Sercos.Baudrate for SERCON 410B:  
The SERCOS baud rate is set to 2 (2MBits/sec) or 4 (4MBits/sec). The  
baud rates of all drives must be the same. To control the baud rate on  
the drive, find the 10-position DIP switch on top of the drive and set the  
switches according to the following:  
Baud rate  
2 MBits/sec  
4 MBits/sec  
Sercos.Baudrate Drive, Switch 6  
2
4
Off  
On  
Sercos.Baudrate for SERCON 816:  
The SERCOS baud rate is set to 2 (2 M bits/sec) / 4 (4 M bits/sec) /  
8 (8 M bits/sec) or 16 (16 M bits/sec). The baud rates of all drives must  
be the same. To control the baud rate on the drive, find the 10-position  
DIP switch on top of the drive and set the switches according to the  
following:  
Baud rate  
Sercos.Baudrate Drive, Switch 6 Drive, Switch 10  
2 M bits/sec  
4 M bits/sec  
8 M bits/sec  
16 M bits/sec  
2
4
8
Off  
On  
Off  
On  
Off  
Off  
On  
On  
16  
Remember that DIP Switch-6 and DIP Switch-10 are read by the drive only  
on power up. If you change DIP switch-6 or DIP Switch-10, you must cycle  
power on the drive. Some versions of drives exists SERCON816, but in  
compatible mode – in this case it equals to SERCON 410B. For checking  
drive sercon version and mode see drive product number.  
For the current SERCON version, query from the terminal with:?  
System.SERCONversion. It returns:  
Æ2  
Æ16  
For SERCON 410B Version or  
For SERCON 816 Version  
M-SS-005-03  
Rev E  
79  
 
Project  
06/2005  
Danaher Motion  
Sercos.CycleTime is used to either set or query the SERCOS  
communications cycle time - rate of updating cyclic data (rate with which to  
the desired phase of communication (see Cyclic vs. Non-Cyclic  
Communication). This property is only set in SERCOS communication  
phases 0, 1, and 2, transferred from the MC to drives during phase 2 and  
becomes active in phase 3.  
sercos.cycletime = 2000  
? sercos.cycletime  
Sercos.NumberAxes is used for querying the actual number of SERCOS  
drives detected on the ring. This value is generated during communication  
phase 1, when the SERCOS driver scans the ring for drives (or when the the  
drive addresses are explicitly set)  
? sercos.numberaxes  
Sercos.Power is used to set or query the SERCOS transmission power. The  
transmission power is governed by the SERCON interface chip and is set to  
one of six levels. Setting the power level too high drives the fiber-optic  
receiver into saturation and causes communication errors. This value should  
not have to change unless a very long cable is being used (>10 meters).  
Level 6 is the highest power.  
Sercos.power = 3  
? sercos.power  
Sercos.Scan indicates to the SERCOS driver whether to scan the ring for  
drives. If the property is set to a value greater than 0, the ring is scanned  
during communication phase 1. The scan value indicates the highest drive  
address for which to scan. For example, if the value is set to 5, the ring is  
scanned for drives at addresses up to 5.  
Sercos.scan = 0  
Sercos.scan = 5  
‘Do not scan the ring  
‘Scan for drives up to address 5  
Set SERCOS.PHASE to the desired phase of communication (see Enabling  
and Communication Phases). Normally, the command stream outlined in the  
procedure below is sufficient to bring up the ring. Because it takes time to  
bring up the SERCOS ring, you may want to speed the process by changing  
the phase only when it is at some phase other than 4.  
Most IDNs have numeric values. After these IDNs are defined, you can read  
their values with IDNVALUE. To do this, you must specify the drive address,  
IDN, and the IDN element. For example, you can enter:  
? IDNValue{5, 104, 7}  
This lists the value of IDN 104, element 7, for the drive at address 5.  
IDNVALUE is only executed in SERCOS communication phases 3 and 4 as  
cyclic data, or in phases 2, 3, or 4 via the service channel (some restrictions  
apply for writing to an IDN). For a complete listing of IDNs supported by the  
SERVOSTAR drive, refer to the SERVOSTAR® MC Installation Manual.  
IDNs have numeric values and you can write to most of them with the  
WRITEIDNVALUE command. To do this, specify the drive address, IDN  
and the value. For example, you can enter:  
WriteIDNValue Drive = 5 IDN = 104 value=1  
which sets the position loop gain (IDN 104) of drive 5 to 1.  
WRITEIDNVALUE is executed only in SERCOS communication phases 2,  
3 and 4.  
80  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Project  
Some IDNs have alpha-numeric string values. After these IDNs are defined,  
you can read the string values with READIDNSTRING. Specify the drive  
address, IDN, and IDN element. For example, you can enter:  
? IDNString(5, 104, 7)  
IDNSTRING is used only in SERCOS communication phases 2, 3 and 4.  
Some IDNs have alpha-numeric string values. After these IDNs are defined,  
you can write new string values to most of them with WRITEIDNSTRING.  
Specify the drive address, IDN and the value. For example, you can enter:  
WriteIDNString Drive = 5 IDN = 104 Element = 7  
String = IDN String  
WRITEIDNSTRING is executed only in SERCOS communication phases 2,  
3 and 4.  
IDNState returns the state of a specified procedure command from a  
specified drive. It is used when executing a procedure command to  
determine progress of that procedure’s execution. Common procedures are  
99 (clear faults) and 148 (drive-controlled homing).For example, you can  
enter:  
‘Check how procedure terminated  
If IdnState(a1.dadd, 99) <> 3 Then  
Print “Reset Faults procedure failed”  
End If  
For more information about states of this property, refer to the  
SERVOSTAR® MC Reference Manual.  
Use MOTIONLINK to configure and operate the SERVOSTAR drive. The  
parameters are stored in the drive, but not in the controller. So, if you need to  
replace a drive in the field, you must reconfigure that drive with  
MOTIONLINK.  
One benefit of SERCOS is that it allows you to download all drive  
parameters via the SERCOS link each time you power up. If you need to  
replace a SERVOSTAR drive, you do not need to configure it with  
MOTIONLINK. This is a significant advantage when maintenance people  
unfamiliar with the design of the system do drive replacement. For this  
reason, Danaher Motion recommends that you configure your systems to  
download all parameters on power up. BASIC Moves provides a utility that  
reads all pertinent IDNs after the unit is configured and the ring is up and  
stores them in a task you automatically download each power up.  
3. 13  
LOOPS  
The SERVOSTAR system supports three main loop types:  
Standard position loop  
Dual-feedback position loop  
Velocity loop  
The MC sends position and velocity commands each SERCOS update cycle.  
The operation of the MC is hardly affected by the loop selection because the  
loop selection is made in the drive.  
M-SS-005-03  
Rev E  
81  
 
Project  
06/2005  
Danaher Motion  
3.13.1. Standard Position Loop  
Position loop is the standard operating mode of the SERVOSTAR system.  
For position operation, set the position loop gain to a value greater than zero.  
Typically, you set up the position loop using MOTIONLINK. See the  
SERVOSTAR® MC Installation Manual for more information.  
3.13.2. Dual-feedback Position Loop  
Dual-feedback position loop compensates for non-linearity in mechanical  
systems (inaccuracy from gears, belt drives, or lead screws, or backlash  
from gears and lead screws). Dual-feedback position loop adds a second  
feedback sensor (usually a linear encoder) to the system so the load position  
is directly determined. Unfortunately, the load sensor cannot be the sole  
feedback sensor in most systems. Relying wholly on the load sensor usually  
causes machine resonance that severely affects system response. Dual-  
feedback position loop forms a compromise: uses the load sensor for  
position feedback (accuracy is critical) and uses the motor sensor for velocity  
feedback (low compliance required). This is the dual-feedback position loop  
shown below.  
The additional hardware for dual-feedback position loop is a second encoder  
connected to the drive which is running dual-feedback position loop. You  
configure the drive for dual-feedback position loop operation using  
MOTIONLINK. See the SERVOSTAR® MC Installation Manual for more  
information. The SERVOSTAR MC does not close the servo loops and is not  
directly involved in dual-feedback position loop operation. In a sense, the MC  
is not aware that the drive is operating in dual-feedback position loop.  
However, when setting up the feedback system, you must configure your  
units for the external encoder, not the motor feedback device. In addition,  
you must also tell the MC to monitor the external encoder for position error.  
This is done with <axis>.FEEDBACK. For example:  
A1.Feedback = External  
'Set the axis feedback to the load  
82  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Project  
3.13.3. Velocity Loop  
For some applications, the motor must be under velocity loop control.  
Maintaining a position is not important. The advantage is that the motor is  
more responsive (typically 3 to 5 times faster in settling time). When you  
configure an axis for velocity loop, you more or less fool the drive by setting  
gains to disable the position loop. You need to set the position loop gain to  
zero and the feed-forward gain to 100%. This produces the following servo  
loop:  
Since a lot of position error can accumulate in velocity loop, it is best to  
configure the system to have such a large maximum position error that it  
never realistically generates an error.  
3. 14  
SIMULATED AXES  
A simulated axis is an axis that exists only inside the MC. Simulated axes  
have most of the functions of physical axes including profile generators,  
units, position and velocity commands and feedback signals, and limits.  
However, simulated axes do not include a drive, motor or feedback device.  
An axis can only be configured as a simulated axis during Sercos.Phase 0 or  
before SERCOS configuration takes place in CONFIG.PRG or  
AUTOEXEC.PRG. To set up a simulated axis, set the axis property  
SIMULATED to ON:  
A1.Simulated = ON  
This step is inserted in the BASIC Moves auto setup program, in the  
subroutine, SercosSetup, just after the phase is set to zero. See SERCOS  
Setup Subroutine in Appendix A for additional details.  
Simulated axes require about the same amount of resources from the MC,  
as physical axes. As a result, simulated axes are part of the total axis count  
of the controller. For example, a system with three physical axes and one  
simulated axis requires a four-axis MC. Simulated axes are used in the MC  
in the same way as physical axes. They are profiled with JOG and MOVE,  
can be geared and cammed, and can act as masters for geared and  
cammed axes. Variables from simulated axes such as position feedback can  
be used to generate events. During operation, the feedback position and  
velocity are set to their respective command values.  
Although most commands and variables for axes work for simulated axes,  
there are some exceptions. Simulated axes cannot receive SERCOS  
commands. You cannot set drive variables such as position loop gains in  
simulated axes.  
M-SS-005-03  
Rev E  
83  
 
Project  
06/2005  
Danaher Motion  
The units on a simulated axis are flexible. The simplest way to set the units is  
to set PFAC=1, which can be thought of as 1 simulated unit (eg, 1 meter, 1  
inch). Set VFAC to PFAC/1000 for units-per-second or set to PFAC/60000  
for units-per-minute such as rpm. Set AFAC to VFAC/1000, such as meters-  
per-second2. Most axis properties do work with simulated axes, including:  
Position properties: command, feedback, final  
Velocity properties: command, feedback, cruise, maximum  
Acceleration and deceleration  
Acceleration maximum and deceleration maximum  
In addition, you can move, jog, gear, and cam simulated axes. The following  
axis properties do not work with simulated axes:  
Position error and velocity error (assume to be zero)  
Velocity Overspeed  
Tuning parameters  
External position and velocity  
84  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Single-Axis Motion  
4.  
SINGLE-AXIS MOTION  
The SERVOSTAR MC supports three main types of motion:  
Single-axis motion  
Master-Slave motion  
Multiple-axes motion  
A motion generator controls all motion in the MC. This software device  
receives commands from MC tasks and produces position and velocity  
commands for the drives every servo cycle. The two main single-axis motion  
commands are JOG and MOVE. The MC also provides ways to synchronize  
the execution of motion commands as well as changing motion profiles on-  
the-fly. In addition, the MC provides multiple modes for starting and stopping  
motion.  
All motion commands are subject to inherent system delays due to SERCOS  
communications. One cycle time is required to transmit a command. A  
second cycle time is required to receive the position feedback. Thus, the  
minimum system delay is 2 SERCOS cycles. If microinterpolation is enabled  
in the drive, there is an additional delay of 1 cycle time. Additional,  
indeterminate, delays may result from the servo system dependent on drive  
tuning and kinetics of the mechanical system.  
4. 1  
MOTION GENERATOR  
The basis of all motion in the MC is the motion generator. When you issue a  
motion command such as JOG or MOVE to an axis, a motion generator is  
created in software. That motion generator controls the position and velocity  
commands of the axis specified in the move command. At regular intervals  
(normally 2 or 4 ms), the motion generator updates these commands. At the  
end of motion, the motion generator is terminated. The figure below shows  
the normal operation of a motion generator.  
4.1.1. Motion Conditions  
Several conditions must be met before the MC generates motion:  
The controlling task must attach to the controlled axis.  
The controlled axis must be enabled.  
The system and axis motion flags must be enabled.  
Before a task can send motion commands to an axis, the axis must be  
attached to the task. Attaching is also required for gearing. This prevents  
other tasks from attempting to control the axis. To attach an axis, issue  
ATTACH from the controlling task:  
Program  
Attach A1  
M-SS-005-03  
Rev E  
85  
 
Single-Axis Motion  
06/2005  
Danaher Motion  
If no other task is attached to the axis, the axis is immediately attached. If  
another task has already attached the axis, an error is generated. A TRY  
CATCH can be used to wait for an axis to be unattached.  
As long as the task has the axis attached, no other task can control the axis.  
When a task is finished with an axis, it should detach the axis:  
Detach A1  
If you issue DETACH while profile motion for that axis is in progress,  
DETACH delays execution until that motion is complete. If a task ends with  
some axes still attached, all axes are automatically detached.  
One exception for the requirement that an axis be attached is if the motion  
command is issued from the terminal window. In this case, assuming the axis  
is not attached by any other task, the axis is automatically attached to the  
terminal window for the duration of the motion command.  
Enable the drive by typing the following commands in the terminal window:  
System.Enable = ON  
A1.Enable = ON  
Enable is also necessary for asimulated axis although there is no drive  
connected.  
There are two other signals that are required to enable the drive: DRIVEON  
and HALTRESTART. These signals are normally ON. These signals are  
provided to comply with SERCOS. They are seldom used in MC programs. If  
you do turn either of these off, you will need to turn them back on before  
motion is allowed.  
The last step in preparing a system for motion is turning on the motion  
flags. There are two motion flags which must be on: the system motion flag  
and the axis motion flag. For example:  
System.Motion = ON  
A1.Motion = ON  
These lines of code are included in the BASIC Moves auto setup program.  
In many applications, a hardware switch is tied to the motion flag. The  
SERVOSTAR MC does not have a hardware motion input. However, you  
can use MC events to create this function. The following example shows a  
task that uses input external data input 1 to control the system motion flag:  
Program  
OnEvent MOTION_ON System.DIn.1 = ON  
System.Motion = ON  
End OnEvent  
OnEvent MOTION_OFF System.DIn.1 = OFF  
System.Motion = OFF  
End OnEvent  
End Program  
The purpose of the motion generators is to convert motion commands (JOG  
or MOVE) into a regularly updated series of position and velocity commands.  
That series is called a motion profile. The position and velocity commands  
are sent via SERCOS to the controlled SERVOSTAR drive. All the servo  
loops (position, velocity, and current) are closed in the drives. The next figure  
shows the profile for the velocity portion of a JOG command.  
86  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Single-Axis Motion  
The profile must be updated at regular intervals. The MC usually updates the  
profile every cycle time (1 ms update rate, if possible when the drive  
supports this update rate). The SERCOS telegram also gets longer with  
more axes. When using the MC with Pentium™ CPU board, the  
recommended update time to controls 8 or fewer axes is 2 ms and 4 ms  
when the MC controls 9-16 axes. When the MC is used with Pentium™III  
CPU, it controls up to 32 axes at 2 ms update rate.  
4.1.2. Motion Buffering  
The motion generator for each axis can process only one motion command  
at a time because the axis can process only one position or velocity  
command. However, you can send a second motion command to the  
generator where it is held until the current motion command is complete  
(motion buffering).  
Motion buffering is controlled with STARTTYPE. If STARTTYPE is set to  
GENERATORCOMPLETED, the buffered profile starts immediately after the  
current profile is complete. If STARTTYPE is set to INPOSITION, the  
buffered profile starts after the current profile is complete and the position  
feedback has settled out to the position command. In both cases, the second  
command is held in the motion generator to begin immediately after the  
appropriate conditions are met.  
You can also specify that the motion generator not buffer, but process the  
new motion command immediately. This is useful when you want to make  
realtime changes to the profile (changing the end position of the current  
command). For this, set STARTTYPE to IMMEDIATE (IMMED) or  
SUPERIMMEDIATE (SIMM).  
4.1.3. Override versus Permanent  
Axes have numerous properties such as acceleration and deceleration.  
These properties are normally set directly:  
ConveyorAxis.Acc = 100  
This setting is permanent. It persists until the next time the property is  
assigned a value. For convenience, the MC also supports override values  
where the property is set as part of a command. In this case, the setting is  
used only for the current command.  
M-SS-005-03  
Rev E  
87  
 
Single-Axis Motion  
For example:  
06/2005  
Danaher Motion  
ConveyorAxis.Acc = 100  
Jog ConveyorAxis 1000 ACC = 10  
Even though the acceleration rate of the conveyor axis is specified at 100 in  
the first line, JOG accelerates at 10 (the override value). Motion commands  
that do not specify an override acceleration rate accelerate at the permanent  
value.  
Override values are used extensively in motion commands. The values that  
can be overridden are specified below as well as in the SERVOSTAR® MC  
Reference Manual.  
4.1.4. Acceleration Profile  
The single-axis motion commands, MOVE and JOG, produce acceleration  
curves that are limited by:  
ACCELERATION (ACC)  
DECELERATION (DEC)  
SMOOTHFACTOR (SMOOTH)  
Limit ACCELERATION and DECELERATION to less than the acceleration  
capabilities of the motor and load. SMOOTH helps limit or reduce  
mechanical wear on the machine by smoothing motion.  
There are two types of acceleration profiles – sinus-curve profile and  
trapezoidal profile. In the sinus profile the acceleration is smoothly increased  
while in the trapezoidal profile, the acceleration is increases in one sample.  
Setting the acceleration increasing smoothness is done using  
SMOOTHFACTOR.  
4.1.5. Jog  
When you want to command the motor to move at a constant velocity  
independent of the current position, use JOG. Velocity can be negative to  
produce motion in the reverse direction. For example:  
Jog ConveyorAxis 2000  
produces this profile:  
Velocity  
Command  
2000  
rpm  
0
Accel  
Cruise  
Time  
You can optionally limit the amount of time JOG runs using TIMEJOG.  
TIMEJOG must be placed on the same line with JOG. TIMEJOG is  
specified in milliseconds and includes acceleration time. Deceleration starts  
when the time expires. When TIMEJOG is -1, JOG continues indefinitely.  
TIMEJOG defaults to -1. For example:  
Jog ConveyorAxis 2000 TimeJog = 1000  
produces the profile below.  
88  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Single-Axis Motion  
The following axis properties can be overridden as part of JOG:  
TIMEJOG  
ACCELERATION  
DECELERATION  
SMOOTHFACTOR  
JERK  
VELOCITYRATE  
ACCELERATIONRATE  
DECELERATIONRATE  
JERKRATE  
4.1.6. Stop  
STOP stops motion in the motion buffer. In the command, you must specify  
the axis. For example:  
Stop ConveyorAxis  
Normally, STOP is set to stop motion immediately at the rate of  
DECELERATIONMAX. However, you can modify the effects of STOP with  
STOPTYPE. STOPTYPE can take three values:  
StopType = Immediate or IMMED  
Stop axis immediately at DECELERATIONMAX rate  
StopType = EndMotion  
Stop axis at end of current motion command and clear buffered motion  
StopType = Abort  
Stop the current motion immediately without ability to restore the  
stopped movements. Only the current motion command is stopped, the  
commands coming after are generated.  
STOPTYPE defaults to IMMED. If STOPTYPE = ENDMOTION, the current  
move is completed before STOP is executed. For JOG with TIMEJOG = -1  
(continue indefinitely), STOPTYPE = ENDMOTION has no meaning because  
JOG never ends. During STOP, the current and pending movements in the  
buffer are stored to allow recovery of these movement using PROCEED.  
STOP uses the modal maximum deceleration and maximum jerk.  
STOPTYPE is overridden as part of a STOP.  
4.1.7. Proceed  
When a task stops motion in axes it has attached, restarting the motion is  
simple. The logic is contained inside the task. However, when motion is  
stopped from another task, the situation is more complex. For example, the  
system should prevent any task from restarting the motion except the task  
that stopped it. To control the restarting of motion after a STOP, the MC  
supports PROCEED.  
M-SS-005-03  
Rev E  
89  
 
Single-Axis Motion  
06/2005  
Danaher Motion  
PROCEED has two purposes: to enhance safety and to allow motion to  
continue along the original path. The safety enhancement is provided by not  
allowing motion on an axis to restart without the task that stopped the motion  
issuing a PROCEED. The path control is provided by  
<axis>.PROCEEDTYPE. PROCEEDTYPE can be set in one of three modes:  
CONTINUE, NEXT MOTION, and CLEARMOTION. The key rules of  
operation are:  
1. When a task stops the motion of axes to which it is attached, a  
PROCEED is allowed, but not required.  
2. When STOP is issued from the terminal window and the axis being  
stopped is attached to a task, motion is stopped and the task is  
suspended upon execution of the next motion or DETACH. The task  
and the motion it commands can restart only after a PROCEED is  
issued from the terminal window. Motion is commanded from the  
terminal window before PROCEED is issued.  
3. When STOP is issued from one task and the axis being stopped is  
attached to another task, motion is stopped and the task is suspended  
upon execution of the next motion or DETACH. The task and the  
motion it commands restart only after PROCEED is issued from the task  
that stopped motion. Motion cannot be commanded from the task that  
stopped motion.  
4. When STOP is issued from the terminal window for a command given  
from the terminal window, the motion is stopped and cannot proceed. In  
this case, the only available proceed type is CLEARMOTION from the  
terminal.  
There are three ways for PROCEED to restart motion. Use PROCEEDTYPE  
to specify how the motion generator should proceed:  
ProceedType = Continue  
This causes the motion generator to continue the motion command that  
was stopped followed by the pending motion in the stopped buffer.  
ProceedType = NextMotion  
This causes the motion generator to abort the current move and go  
directly to the move in the stopped motion buffer.  
ProceedType = ClearMotion  
This clears the motion buffer. All motion commands in the stopped  
motionbuffer are aborted. This is the default.  
4.1.8. Move  
MOVE is the most common of point-to-point moves. The basic move is a  
three-segment motion:  
Accelerate  
Cruise  
Go from zero speed to VelocityCruise  
Continue at VelocityCruise.  
Decelerate  
Go from VelocityCruise to VelocityFinal  
The critical part of a three-segment move is starting the deceleration at the  
right time so that the motor speed becomes zero (if VELOCITYFINAL = 0)  
just as the position command reaches the final position. For example, the  
following command:  
Move ConveyorAxis 100 VCruise = 2000  
produces the next profile.  
90  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Single-Axis Motion  
4.1.8.1. POSITION FINAL AND INCREMENTAL VERSUS  
ABSOLUTE MOVES  
POSITIONFINAL (the end of a move), is always specified in MOVE. The  
meaning of PFINAL depends on ABSOLUTE (ABS). This allows point-to-  
point moves to be specified two ways:  
Absolute Moves (Absolute = TRUE)  
Final position is specified as actual motor position at the end of the  
move. The final position is equal to PFINAL.  
Incremental (Absolute = FALSE)  
Final position is referenced to the start position. The final position is  
equal to the sum of PFINAL and PCMD from the start of the move. So:  
CutAxis.Absolute = TRUE  
Move CutAxis 100  
moves CutAxis to position 100. On the other hand:  
CutAxis.Absolute = FALSE  
Move CutAxis 100  
moves CutAxis a distance of 100 units from the current position.  
ABSOLUTE defaults to FALSE. You can change ABSOLUTE at any time,  
although the effect does not take place until you issue the next MOVE.  
4.1.8.2. SETTLING TIME  
The MC actively watches to see if axes are settled into position. In almost all  
applications, the motor position feedback is slightly delayed from the position  
command. After a move is complete, some time is required for the actual  
position to settle out to the commanded position; this time is called settling  
time.  
Consider the point-to-point move shown below. The VELOCITYCOMMAND  
(VCMD) is shown in solid line and VELOCITYFEEDBACK (VFB) is shown  
in thin line. The area between the two curves is the following error. As you  
can see, it takes a small amount of time at the end of the move for VFB to  
settle out to zero. The actual amount of time required for this varies from one  
system to another. Higher bandwidth systems have shorter settling times, but  
all systems need some time to settle. Typical times range from a few  
milliseconds to tens of milliseconds.  
M-SS-005-03  
Rev E  
91  
Single-Axis Motion  
06/2005  
Danaher Motion  
Ideally, settling time allows the motor to move to approach zero position  
error. However, you must allow for the condition where the position error  
never quite reaches zero. On the MC, you specify how low you consider to  
be low enough with <axis>.POSITIONERRORSETTLE (<axis>.PESETTLE):  
CutAxis.PESettle = 0.01  
After the motion generator has completed a move which ends with zero  
speed, it actively monitors the position error on the axis to see when it is  
between ±PESETTLE.  
In some applications, you must ensure that the position error remains below  
PESETTLE for a specified period of time before the axis is considered  
settled. The MC allows you to specify this time period with  
<axis>.TIMESETTLE (given in milliseconds). TIMESETTLEMAX sets the  
maximum time allowed for the axis to settle. If the position error exceeds  
PESETTLE during this time, the timer is reset. If position error is within the  
PESETTLE range for the time specified by TSETTLE, the  
<axis>.ISSETTLED flag is TRUE (1). Otherwise, it is FALSE(0).  
4.1.8.3. POINT-TO-POINT MOVES  
When the motion buffer is empty, point-to-point moves begin immediately. If  
you need to delay the start of the next motion command, you have two  
options: use DELAY to insert a fixed delay time, or use STARTTYPE to  
delay depending on a condition.  
Use DELAY to force the motion generator to wait a fixed period of time  
between moves. For example:  
Move MainAxis 100  
Delay 1000  
Move MainAxis 200  
A 1 second delay is forced between the two moves. DELAY has units of  
milliseconds and must be greater than zero. DELAY does not delay the  
execution of your program. If you want to delay your program, use SLEEP.  
If you want to delay the start of a new move until a condition has been met  
by the previous move, use STARTTYPE. There are four choices:  
StartType = GeneratorCompleted (GCom)  
When STARTTYPE = GCOM, the new move starts as soon as the  
motion generator has completed the motion for the current move.  
GENERATORCOMPLETED is constant equal to 3. This command  
incurs a system delay of 2 SERCOS cycle times.  
92  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Single-Axis Motion  
StartType = InPosition (InPos)  
When STARTTYPE = INPOS, the motion generator delays executing  
the new motion command until the current move has completed and the  
position error is settled to near zero. INPOSITION is constant equal to  
2. This command is not subject to additional system delays, but any  
delay associated with the command is due to user-specified parameters  
for settling time.  
StartType = Immediate (Immed)  
When STARTTYPE = IMMED, the new move overwrites the current  
move. Use this when making realtime changes to the profile such as  
changing the end-point of the current move without bringing the system  
to rest. For example, registration applications frequently use this  
function. IMMEDIATE is constant equal to 1. This command incurs a  
system delay of 5 SERCOS cycle times each execution. This time is  
required to blend the previous move with the new move.  
StartType = SuperImmediate (Simm)  
SUPERIMMEDIATE is a variation of IMMEDIATE. The main difference  
is that SUPERIMMEDIATE eliminates the 5 SERCOS cycles delay by  
doing pre-calculation online, rather than offline in the motion manager.  
SUPERIMMEDIATE is constant equal to 5. The numbers of  
SUPERIMMEDIATE changes at a time in the system is limited by the  
load of the system and the type of move. SUPERIMMEDIATE is best  
used for short, high-speed movements.  
When chaining multiple moves which all end at zero speed, you normally  
want STARTTYPE = INPOS. This forces the motion generator to wait for the  
position to settle out before starting the next move. If the position profile  
starts too soon on the second move, the motor may never come to rest. For  
example, the next figure shows this problem when STARTTYPE is  
incorrectly set to GCOM rather than INPOS.  
As you can see, the motor speed never gets to zero because the second  
move takes the velocity command positive before the velocity feedback  
settles to zero.  
Normally, the desired performance is for the velocity to reach zero before the  
second move starts. To do this, the controller needs to wait for the axis  
position error to be settled before starting the second move. This is done by  
setting STARTTYPE to INPOS. This is shown in the following figure.  
M-SS-005-03  
Rev E  
93  
Single-Axis Motion  
06/2005  
Danaher Motion  
As you can see, the motor comes to rest because the MC waits for the  
following error to be small enough before proceeding to the next command.  
MainAxis.PESettle = 0.01  
MainAxis.Tsettle = 10  
Move MainAxis 100  
Move MainAxis 200 StartType=InPos  
Normally, the ending speed of MOVE defaults to zero. However, you can  
specify an end speed other than zero (Non-Zero End Moves). To do this,  
use <axis>.VELOCITYFINAL. VELOCITYFINAL must be specified on the  
same line as MOVE. For example,  
A1.VelocityCruise = 2000  
Move A1 100 VelocityFinal = 1000  
or  
Move A1 100 VelocityCruise = 2000 VelocityFinal = 1000  
both produce the next profile.  
You seldom want to use a single move with a non-zero final velocity because  
motion continues until the specified ending position and abruptly begins  
decelerating to zero. The final position is not specified. Normally, moves with  
non-zero final velocities are used to build multi-step profiles.  
94  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Single-Axis Motion  
Combining non-zero end-point moves in the motion buffer produces multi-  
step moves. For example:  
Program  
Attach A1  
Call AxisSetup  
Call SercosSetup  
Sys.En = On  
A1.En = On  
Sys.Motion = On  
A1.Motion = On  
A1.Abs = Off  
A1.StartType = Gcom  
‘Do Two-step Move  
Move A1 100 VCruise = 20 VFinal = 10  
Move A1 100 VCruise = 10 VFinal = 0  
‘Wait for move to complete and axis to settle out  
While A1.IsSettled = 0  
Sleep 10  
‘Sleep in loop to keep from overloading CPU resources  
End While  
‘Disable, detach and exit  
A1.En = Off  
Detach A1  
End Program  
produces the following profile.  
In the above example, A1.STARTTYPE = GCOM. The second move begins  
when the first move is generated. You must use STARTTYPE = GCOM  
when chaining a non-zero end-point move to another move. You cannot use  
STARTTYPE = IMMED or SIMM because the new move immediately  
overwrites the old move. You cannot use STARTTYPE = INPOS because  
you want the second part of the profile to begin immediately after the first.  
The delay from waiting for INPOS adds error if the second move is  
incremental. For any move type, the move may be delayed indefinitely  
because moving motors never come in position unless the system is  
specifically tuned to do that.  
You can combine non-zero end point moves to produce profiles with as  
many steps as you need. However, there are a few restrictions:  
1. STARTTYPE for all non-zero end-point moves (VELOCITYFINAL<>0)  
must be GCOM.  
2. VELOCITYCRUISE and VELOCITYFINAL are always positive. The  
direction is set by target position.  
M-SS-005-03  
Rev E  
95  
Single-Axis Motion  
06/2005  
Danaher Motion  
3. PFINAL of the succeeding move must be far enough in front of  
PFINAL of the current move that the profile is possible with the  
acceleration limits. The generated profile always reaches the target  
position. If the acceleration and smooth limitations prevent attaining the  
required final velocity, the motion is terminated with the final velocity as  
close as possible to the required value.  
You can change the end position or velocity of a move that is in progress.  
You do this by setting STARTTYPE = IMMED and issuing the second move.  
For example, if you want to issue a move, wait a few seconds, change the  
end position without changing the velocity. For this, you would write:  
CutAxis.StartType = Immed  
CutAxis.Absolute = On  
Move CutAxis 150  
Sleep 3000  
Move CutAxis 100  
This generates the profile shown below.  
As a second example, if you wanted to change the cruise velocity without  
changing the end-position, you would write:  
CutAxis.StartType = IMMED  
Move CutAxis 150  
Sleep 3000  
Move CutAxis 150 VCruise = 1500  
You can change the final position, cruise velocity, and final velocity of any  
move that is executing. However, you must observe a few rules:  
1. STARTTYPE must be IMMED or SIMM  
2. Direction is set according to the target position. For Jog, according to  
the sign of the velocity.  
3. New and old VELOCITYCRUISE and VELOCITYFINAL must be  
positive in case of move command.  
4. If the succeeding move changes PFINAL or VFINAL, it must remain  
possible to create the profile with the axis acceleration limits  
4.1.8.4. SYNCHRONIZING MULTIPLE AXES  
The MC is abile to synchronize many single-axis MOVEs so they all start  
simultaneously. This is useful when you have multiple axes with moves that  
are largely independent, but must start at the same time. It is also useful for  
coordinating more than three axes. Group motion, which is covered later,  
provides tighter coordination, but with one movement profile.  
96  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Single-Axis Motion  
Synchronization is controlled with STARTTYPE = SYNCSTART (SYNC).  
The feature works by allowing you to load the motion generator with a motion  
command, but delaying the generation of motion until a SYNCSTART  
command is issued. For example, the following sequence:  
Move MainAxis 300 VCruise = 1200 StartType = Sync  
Sleep 1000  
‘Program delayed between Move Commands  
Move AuxAxis 100 VCruise = 1000 StartType = Sync  
SyncStart MainAxis AuxAxis  
generates the following profiles.  
You can synchronize as many axes as you want, including simulated axes.  
Since each SYNCSTART specifies the axes it synchronizes, you can  
synchronize multiple sets of axes independently.  
This command incurs a minimum system delay of 2 SERCOS cycle times,  
but the delay may be greater, depending on the number of moves  
synchronized together and the total load of the system.  
If you have loaded a synchronized move into the motion generator and need  
to delete it, use SYNCCLEAR. For example, if you entered the following  
command before issuing SYNCSTART:  
SyncClear MainAxis  
the MainAxis move is deleted. This only affects subsequent moves. You can  
only use SYNCCLEAR to clear pending moves. SYNCCLEAR has no effect  
once the move is executing. Stopping the axis in this case is performed as  
for a non-synchronized move.  
You can override the following axis properties as part of a MOVE:  
ABSOLUTE  
ACCELERATION  
DECELERATION  
SMOOTHFACTOR  
VELOCITYCRUISE  
VELOCITYMAX  
STARTTYPE  
VELOCITYRATE  
ACCELERATIONRATE  
DECELERATIONRATE  
JERKRATE  
M-SS-005-03  
Rev E  
97  
Single-Axis Motion  
06/2005  
Danaher Motion  
4.1.9. Velocity Override  
The MC can speed up or slow down all motion commands. This can be  
applied to the entire machine at once, or to individual axes, independently.  
This capability is used extensively in machine development as it enables you  
to adjust the entire machine speed in a single command. Since the  
command can be issued from the terminal, you can observe the operation of  
the machine at a variety of speeds without modifying your program.  
All axes on an MC are controlled with SYSTEM.VELOCITYOVERRIDE  
(SYSTEM.VORD). For example:  
System.VelocityOverride = 25  
immediately reduces the velocity commands of all currently executing  
MOVEs and JOGs and any subsequent commands to 25% of the current  
values. Since the velocities are controlled by VORD, the acceleration rates of  
all axes are proportionally adjusted. The final positions of MOVEs are not  
affected.  
If you want to override the velocity of a single axis rather than the entire  
machine, you can use <axis>.VORD.VELOCITYOVERRIDE  
(<axis>.VORD). It is used in the same way as SYSTEM.VORD except it  
applies only to one axis. <axis>.VORD can be applied to as many or as few  
axes as desired and the amount of override specified for one axis is  
independent of the others. If you use SYSTEM.VORD and <axis>.VORD  
simultaneously, the axis speed is reduced by the product of both override  
properties as shown below:  
System.VOrd = 66  
‘Reduce entire system to 2/3 speed  
MainAxis.VOrd = 50 ‘Reduce MainAxis to 1/3 speed  
In this example, the entire system is reduced to 66% and the MainAxis is  
reduced to 50% of the system speed which is 33%. There is a delay of 5  
samples until the velocity start to change that to insure a smoothness  
velocity exchange.  
4. 2  
MOTION EXAMPLES  
This section provides a few examples that apply the motion control  
techniques discussed in this chapter to common machine functions.  
4.2.1. Position Capture  
Many drives (including all current SERVOSTAR drives) implement the  
position capture functionality, commonly used in homing and registration  
procedures. Starting with version 3.0, the MC uses the SERCOS procedure  
mechanism to accomplish positioning.  
While position capture is a drive-based function, the MC provides various  
commands to control the capture procedure. SERVOSTAR drives provide  
three digital inputs (IN_1, IN_2, and IN_3), any one of which can be  
designated for the capture trigger signal. The command properties provided  
in the MC are:  
<axis>.Capture Position capture is executed once the SERCOS relevant  
procedure (IDN 170) has been started. <axis>.Capture encapsulates this  
process and starts and stops the capture procedure. It takes the value 1 to  
start or 0 to stop the procedure, respectively.  
98  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
<axis>.In1  
06/2005  
Single-Axis Motion  
Returns the state of the drive digital input 1 (ON or OFF).  
Specifies the functionality of the drive digital input 1. The value 16  
(keyword capturing) selects the capture input.  
<axis>.In1Mode  
<axis>.In2  
Returns the state of the drive digital input 2 (ON or OFF).  
<axis>.In2Mode  
specifies the functionality of the drive digital input 2. The value 16  
(keyword capturing) selects the capture input.  
<axis>.In3  
Returns the state of the drive digital input 3 (ON or OFF).  
<axis>.In3Mode  
Specifies the functionality of the drive digital input 3. The value 16  
(keyword capturing) selects the capture input.  
4.2.2. Homing  
Most machine-axes need to establish a soft home reference position. This  
user-specified homing program is generally run with the power-up cycle of  
the machine or with a manual-mode. The soft home reference position  
(0000….) is established by a homing program for the hard-home plus any  
marker-pulse (for the integrity between the controller and axis-mechanics)  
with HOMEOFFSET (the distance from the hard home).  
The hard-home position on a direct drive axis is usually assigned by the  
once-per-revolution marker pulse of the encoder (incremental, sine encoder  
or ENDAT encoder) or the zero-crossing position of a resolver (see  
HOMETYPES). However, for the machine-axis with a gear-ratio (geared,  
belted, or ball screw, etc.), a more complicated procedure is required for the  
relationship (integrity) between the controller and axis-mechanics of the  
homing program. In these cases, it is common to place a micro-switch or  
proximity-switch on the axis for the indication of the hard-home-reference  
position.  
This home-position switch is placed on one end of the axis  
(inside the mechanical end of the travel-limits of the axis) with  
the switch tripping mechanism designed such that switch-  
circuit is closed on one side of the hard home-position and  
NOTE  
open on the other side of the hard home-position.  
The switch-circuit (high/low) provides the controller-input information for the  
direction of the home position.) Other machine axes may use absolute-  
position-device designs, so the integrity between the controller and axis  
mechanics is established automatically on the power-up of the machine  
(HOMETYPES). The machine position-integrity is established similarly to an  
axis that only rotates 360°.  
The drive executes the HOME procedure. When you start the homing  
procedure on an axis , the drive immediately starts executing the homing  
procedure. The axis properties used to control the homing procedure are:  
<axis>.HomeAcceleration  
Specifies the acceleration and deceleration to be used  
during the homing procedure (with the inclusion of  
HOMEOFFSET or HOMEDISTANCE).  
<axis>.HomeDirection  
Specifies the direction of the home search movement.  
Application-dependant instruction for the model:  
HOME to a hard-stop requires a movement in one  
direction. However, home to a switch-transition at one  
end of the axis-travel requires the direction for a  
closed-switch to be opposite that of an open-switch.  
<axis>.HomeDistance  
Sets the distance from the soft-home (position: 0000….  
within the MC, see HOMEOFFSET) and the start  
position for any given program as you define.  
A1.HomeDistance=5000commands the axis to go  
to position 5000 from the soft home (position: 0000….)  
and stay there.  
M-SS-005-03  
Rev E  
99  
 
Single-Axis Motion  
<axis>.HomeDistanceMax  
06/2005  
Danaher Motion  
Specifies the maximum distance from the point at  
which the homing process began (in either direction)  
that an axis is allowed to travel in order to find the hard-  
home position-switch-transition.  
<axis>.HomeType  
Specifies the homing latch type: 0=Switch +  
marker1=switch2=marker  
<axis>.HomeOffset  
Sets the soft home position to position 0000…. within  
the MC after HOMEOFFSET-specified distance has  
been traveled from the hard-home position (micro or  
prox-switch, etc.). When maintenance on an axis  
effects the integrity between the controller programs  
and the mechanical axes (e.g., replacement of the  
homing-switch), it is the value of HOMEOFFSET that is  
adjusted for the re-establishment of the integrity. Actual  
programs are not effected once the HOMEOFFSET  
has been adjusted. See HOMEDISTANCE when there  
is more than one program that needs to repeatedly  
start from different positions.  
<axis>.HomePolarity  
Specifies the homing switch edge1=rising  
edge2=falling edge  
<axis>.HomeReturn  
Specifies whether the axis assigns and adjusts to the  
proper position feedback for the home-position as the  
axis travels through the home switch-transition or go  
home (back to the switch after the first switch-transition  
for the minimization of any position-lag error + any  
HOMEOFFSET or HOMEDISTANCE for the  
assignment of the home-position)0 = do not go back1 =  
go back to the switch  
<axis>.HomeStatus  
Provides the status of the home (read only property)0 =  
axis not home1 = axis is home2 = home in progress3 =  
error during homing procedure  
<axis>.HomeVelocity  
Specifies the velocity to be used during the homing  
procedure (with the inclusion of HOMEOFFSET or  
HOMEDISTANCE).  
The various homing properties are provided to allow you to set the values of  
the parameters that determine the behavior of the procedure. For instance,  
properties such as <axis>.HOMEVELOCITLY,  
<axis>.HOMEACCELERATION, <axis>.HOMEDISTANCE, and  
<axis>.HOMEOFFSET allow you to control the rate at which the axis  
approaches home.  
The following example illustrates this procedure: A typical home application  
may look like:  
a1.HomeVelocity = 100  
a1.HomeAcceleration = 1000  
a1.HomeOffset = 100  
a1.HomeDistance = 100  
a1.HomeDirection = 1  
a1.HomeType = 1  
a1.HomePolarity = 2  
a1.In1Mode = homing  
a1.HomeDistanceMax = -1  
a1.HomeReturn = 1  
Home a1  
For more information about these properties, refer to the SERVOSTAR® MC  
Reference Manual.  
100  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Single-Axis Motion  
4.2.3. Registration  
Registration applications are those that start motion and then modify the  
profile, based on a subsequent event. These applications generally involve  
discrete product processing, such as are common in the packaging, printing  
and converting industries. The event is usually generated by sensing a  
position on the product being processed (usually a mark is printed on the  
product and detected by an optical sensor). The mark is normally referred to  
as a registration mark.  
A common registration application is cutting a product package, such as a  
bag or label from a web (reel). The web is printed with many copies of the  
product package. The controller begins to unwind the product package from  
the web. During this motion, the controller waits for a registration mark to be  
detected. After the mark is detected, the profile is modified, based on the  
position at which the mark was detected. Commonly, the profile comes to  
rest a fixed distance after the mark position where the package can be cut.  
There are numerous variations of this type of application. The key element is  
that the end position of the move cannot be calculated until after the move  
starts. This requires that the profile be started and then modified on-the-fly.  
The MC combines the ability to change the position end points on-the-fly and  
the ability to command the SERVOSTAR drive to capture a position.  
Registration is similar to homing except that in homing you go back to the  
mark, but in registration you go forward to a fixed distance after the mark.  
The following example shows a typical registration example:  
Program  
'Prepare SERVOSTAR drive to capture  
VCruise = 3000  
Cycle:  
Move FeedAxis 50  
'wait for capture  
Move FeedAxis [capture position] + 10 StartType=IMMED  
End Program  
This example generates the next profile.  
The move starts and the registration mark is detected about 40% of the way  
to the end. After a small amount of processing time, the second move is  
loaded over the current move. The axis comes to rest at a fixed offset after  
the registration mark.  
M-SS-005-03  
Rev E  
101  
 
Single-Axis Motion  
06/2005  
Danaher Motion  
The more accurately the position is determined, the more accurate the cut is  
with respect to the registration mark. If the process is feeding material at 10  
ft/s, and the capture accuracy is ±3 microseconds, the mark is:  
10 (ft/sec) * 3 µs = 3.225e-5 ft or about 0.0004 in.  
The original line was set to go much farther than the actual resultant move.  
This technique is commonly used because you can monitor the end position  
and, if the move is completed before the registration mark is detected, it  
indicates the mark was missed.  
4.2.4. Gating  
Many applications require motion to be gated to an external switch. In these  
cases, you need to start a move after the gating input transitions with as little  
delay as possible. One way you can accomplish this on the MC is by starting  
the move with events containing synchronized motion. For example:  
Program  
Attach MainAxis  
Move MainAxis 100 Absolute=FALSE StartType=SYNC  
While System.Din.1=False; ‘Wait for input to change  
Sleep 1  
End While  
SyncStart MainAxis  
End Program  
‘Start the axis up by disable  
This program moves MainAxis 100 units when DIN.1 transitions high. Motion  
on MainAxis starts as soon after the transition of DIN.1 as possible. OnEvent  
can also be used.  
4.2.5. Clamping  
Clamping applications typically process discrete parts but the end point of a  
move is unknown. Clamping is often applied when the length of the part is  
not accurately known or when the thickness of material is unknown. In  
clamping, the controller moves an axis at low torque until the end of the  
material is detected. Then the torque level is increased, either to measure  
the part more accurately or to hold the part for another axis to process.  
The MC allows you to change torque limits on the drive and uses events to  
monitor position error to sense the end of the piece (below).  
Program  
Dim Shared PartFoundFlag As Long  
OnEvent PartFound Abs(ClampingAxis.pe ) > 0.25  
Stop ClampingAxis  
[Set torque for heavy torque]  
Sleep 30  
‘allow 30 ms for settling  
PartFoundFlag=TRUE  
Return  
End OnEvent  
eventon PartFound  
[set torque for light torque]  
PartFoundFlag=FALSE  
Move ClampingAxis Vcruise=10  
While (PartFoundFlag=FALSE)  
Sleep 10  
End While  
REM Process part here  
Return  
End Program  
102  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Single-Axis Motion  
This program works by starting a slow move with low torque. The move  
continues until position error is greater than 0.25 units. When the axis runs  
into a stop, position error accumulates because the profile continues. You  
must be careful to set the threshold of the event greater than the position  
error of normal operation. The threshold of the event must also be smaller  
than the drive's maximum following error to avoid drive error before the event  
is triggered. Disable OnEvent during the acceleration of the move to avoid  
nuisance PartFound events.  
4.2.6. PIPEMODE  
The MC controller can be used as a pure SERCOS interface card between  
your application and SERCOS drives (PIPEMODE feature). The host  
computer controlls all of what normally occurs in the motion module of the  
MC. It must send a realtime stream of data through the MC to the drives. In  
this case, the MC functions as a data pipe. The feature is enhanced by the  
option of flexibly switching between pipe mode and regular mode. In typical  
applications, the MC starts in regular mode where homing, jogging and initial  
position adjustments are made. After that, the MC can be switched to pipe  
mode and the host computer takes control. There can be both MC-controlled  
and pipe-controlled axes at same time in the system. Following error and  
velocity over-speed errors are not checked with piped axes, but by the host.  
An external profiler path can be designed and fed to the MC point-by-point.  
The controller functions only as a pipe and is not responsible for the  
correctness of the applied profiler. No system limits are checked except for  
position error and feedback velocity limitation. While running under this  
mode, no other movements are allowed.  
Command points are written through the standard Fast-Data DPRAM  
interface and transmitted into the controller. The DPRAM is scanned every  
SERCOS cycle and the command is executed.  
There can be up to eight (8) axes in the system operating in pipe-mode. The  
Fast-Data interface can be configured in one of two communication protocols  
using SYS.PIPEMODE: 1 – sending position command only, 2 – sending  
both position and velocity commands. When the system's pipe mode uses  
only position commands, the controller computes the current velocity.  
Depending on the pipe mode configuration, the controller limits the number  
of axes that can be operated in this mode. When system uses only position  
command, eight (8) axes can operate. When using both position and velocity  
values, only four (4) axes can operate.  
4.2.6.1. DATA STRUCTURE  
The host CPU passes position and velocity commands via a data structure  
through the Fast-Data DPRAM. The API maps the data to  
SYS.HOSTDOUBLE. The SERCOS operation mode of every drive  
connected to an axis working in Pipe Mode must be configured  
(Position/Velocity/Torque). The drive operation mode is selected through a  
status word written in SYS.VIN.  
Only drive modes previously configured in the SERCOS setup  
can be selected.  
NOTE  
M-SS-005-03  
Rev E  
103  
 
Single-Axis Motion  
06/2005  
Danaher Motion  
The data structure mapping depends on the PIPEMODE state:  
SYSTEM.PIPEMODE  
MC variables  
Byte offset  
Position (1)  
A1.PCMD  
A2.PCMD  
A3.PCMD  
A4.PCMD  
A5.PCMD  
A6.PCMD  
A7.PCMD  
A8.PCMD  
A1…A8  
Position and Velocity (2)  
A1.PCMD  
Sys.HostDouble[1]  
Sys.HostDouble[2]  
Sys.HostDouble[3]  
Sys.HostDouble[4]  
Sys.HostDouble[5]  
Sys.HostDouble[6]  
Sys.HostDouble[7]  
Sys.HostDouble[8]  
0…7  
8…15  
A1.VCMD  
A2.PCMD  
A2.VCMD  
A3.PCMD  
A3.VCMD  
A4.PCMD  
A4.VCMD  
16…23  
24…31  
32…39  
40…47  
48…55  
56…63  
A1…A4 operation mode  
information  
Sys.Vin  
96…99  
operation  
mode info  
4.2.6.2. DRIVE OPERATION MODES  
The drive’s operation mode of every axis is set in a 2-bit field, where there  
are two active modes: 0 - position and 1- velocity (set in a 24-bit field  
SYS.VIN variable). Mapping of the SYS.VIN operation mode status variable  
is described below:  
SYSTEM.PIPEMODE  
Bits offset  
Position (1)  
Position and Velocity (2)  
0, 1  
2, 3  
Operation mode of drive1  
Operation mode of drive1  
Operation mode of drive2  
Operation mode of drive3  
Operation mode of drive4  
Operation mode of drive5  
Operation mode of drive6  
Operation mode of drive7  
Operation mode of drive8  
Operation mode of drive2  
4, 5  
Operation mode of drive3  
6, 7  
Operation mode of drive4  
8, 9  
NA  
NA  
NA  
NA  
10, 11  
12, 13  
14, 15  
Every sample, the controller sends the operation mode to the drive. Without  
any dependency at the drive’s operation mode, the controller sends the  
position and velocity commands to the drive.  
Program  
Sys.EN = Off  
Sys.PIPEMODE = 2  
' Definition As Position & Velocity mode  
Sys.EN = On  
Sys.Vin.1 = 1  
' Velocity Operation Mode  
attach A1  
A1.PIPEMODE =1  
' Pipe mode Activation  
A1.en=1  
While Sys.Din.1 = 1  
' External condition for Pipe Mode  
sleep 1000  
end while  
A1.PIPEMODE = 0  
' Exit from the Pipe mode  
Sys.Vin.1 = 0  
' Return to the Position Operation Mode  
detach A1  
End Program  
104  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Master-Slave  
5.  
MASTER-SLAVE  
Master-Slave motion links the position of one axis (slave) to the position of  
another (master). The master axis is any axis controlled by the MC or an  
external axis. External axes are connected to the MC via the external  
encoder input on any of the drives controlled by the MC.  
There are two types of master-slave motion: gearing and camming. Gearing  
is used when the position of the slave must be proportional to the position of  
the master. Camming is used when the relationship is more complex.  
Camming allows you to specify a one-to-one mapping of the positions of the  
master and slave.  
5. 1  
MASTER SOURCES  
The master signal for master-slave motion is one of three sources:  
1. A physical axis controlled by the MC.  
2. A simulated axis inside the MC.  
3. An encoder signal connected to the external encoder input of a drive  
attached to the MC.  
The internal MC clock produces an incremental pulse every SERCOS cycle.  
To set the master source of an axis, use MASTERSOURCE. For example, to  
set the master input for axis A2 to the position feedback of axis A1 enter:  
A2.MasterSource = A1.PositionFeedback  
This works whether A1 is a physical or simulated axis.  
You can also use POSITIONCOMMAND (PCMD) as a source for gearing or  
camming. This eliminates the lag caused by the position error in the master  
axis. The negative side is the slave is following the command, rather than the  
actual position.  
Many times, the master source needs to be an external encoder signal. This  
may be an encoder from a line-driven motor or from a servo motor controlled  
by an external device, such as a PLC or even another MC. Sometimes the  
master source is not a motor. For example, you can use a pulse train as a  
master signal. In all these cases, the signal is connected to the external  
encoder input of one of the drives controlled by the MC. The SERVOSTAR  
drives accept standard quadrature encoder signals as well as pulse trains.  
Refer to the installation manual for your SERVOSTAR drive for more  
information about the external encoder input.  
After the external signal is connected, it can be assigned as the master  
source of any axis using the variable, POSITIONEXTERNAL (PEXT). For  
example, to set axis A2 to follow the external encoder input of axis A1, type:  
A2.MasterSource = A1.Pext  
For this function to work, the axis must be configured in SERCOS to run on  
telegram 7, and PEXT must be selected as one of the data elements  
communicated back from the drive.  
If the axis has to be controlled, instead of adding a simulated master, it can  
follow an internal clock. This makes the master a type of TIMEPULSE. Set  
the GEARRATIO to a low value (less then zero) and increase its value step  
by step to avoid exceeding velocity limit.  
M-SS-005-03  
Rev E  
105  
 
Master-Slave  
06/2005  
Danaher Motion  
For optimal performance, the master axis should have an axis number less  
than the slave axis. If the slave axis is A1 and the master axis is A2, an  
additional time cycle is inserted in the motion.  
If the master velocity override is changed, the slave velocity is changed  
accordingly. In a relative move, the slave moves according to its new velocity  
override. VELOCITYOVERRIDE has no effect on the master signal for a  
slaved axis. It also has no effect on the gear ratio or cam table.  
VELOCITYOVERRIDE modifies the velocity of incremental moves added  
onto geared or cammed motion.  
5. 2  
GEARING  
When two axes are geared, the position command of the slave is  
proportional to the master signal as shown below.  
Gearing works in both directions of master travel. The term, proportional, is  
applied loosely. The offset between the master and slave axes is saved at  
the time gearing is enabled and is maintained throughout gearing.  
5.2.1. Enable Gearing  
To enable gearing, set MASTERSLAVE to GEAR:  
A1.Slave = GEAR 'Enable gearing  
Enabling gearing during an absolute or relative move generates an error. An  
error is also generated if an attempt is made to enable gearing during  
camming. Incremental moves are allowed when gearing is enabled and  
during gearing.  
5.2.2. Disable Gearing  
To disable gearing, set SLAVE to OFF:  
A1.Slave = OFF  
'Disable gearing  
When gearing is disabled, the velocity of the slave axis is decelerated to zero  
at the rate of <axis>.DECELERATIONMAX (DMAX). Disabling an axis  
does not automatically disable gearing. You do not need to enable gearing  
again when the axis is re-enabled. However, issuingJOG or STOP for the  
axis disables gearing.  
STOP turns gearing off immediately. The velocity of the axis is decelerated to  
zero at the rate set by <axis>.DMAX. For JOG, gearing is disabled  
immediately and the movement is controlled by the JOG profile.  
If the master axis' RTK (RealTime Kernel or software code) is executed  
before the slaves’ RTK, (i.e., if ?axislist displays the master before displaying  
the slave) and the master source is PCMD, there is no delay in execution. If  
the master source is a feedback, PFB or PEXT, there is a system delay of 1  
SERCOS cycle time. If the slave RTK is executed before the master RTK, an  
additional delay of 1 cycle time is incurred.  
106  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Master-Slave  
Set the proportional constant between the master and slave with  
<axis>.GEARRATIO:  
A1.GearRatio = 0.5  
'Slave goes half the speed of master  
GEARRATIO is a double-precision floating-point number that is set to less  
than zero to reverse the direction of the slave.  
5.2.3. Incremental Moves  
The MC supports incremental moves with gearing. The profile of the slave  
axis is the sum of two profiles: the gearing profile and the profile of the  
incremental move:  
You can use incremental moves with and without gearing. Issuing an  
absolute move with gearing enabled generates an error. If you issue STOP to  
a geared axis executing incremental moves, gearing is turned off  
immediately and the velocity commanded from gearing ramps to zero at  
<axis>.DECELERATIONMAX. However, the termination of the incremental  
move profile and subsequent launch of JOG is subject to <axis>.STOPTYPE.  
Issuing JOG when gearing with an incremental move is similar to issuing  
JOG with just gearing. The main difference is that the launch of the JOG  
profile is subject to <axis>.STARTTYPE. If STARTTYPE is IMMEDIATE  
(IMMED) or SUPERIMMEDIATE (SIMM), the jog begins immediately. The  
speed from the incremental move ramps up or down to the specified jog  
speed according to either <axis>.DEC or <axis>.ACC. If STARTTYPE is  
GCOM, SYNC or INPOS, the jog profile is delayed.  
The following example issues JOG with an immediate start  
(STARTTYPE=IMMEDIATE).  
Jog A1 100 TimeJog=5000  
Sleep 2000  
A1.StartType=IMMED  
Jog A1 200  
The resulting profile is:  
M-SS-005-03  
Rev E  
107  
 
Master-Slave  
06/2005  
Danaher Motion  
This next example shows the previous example, but with the starting after  
the incremental move is complete (STARTTYPE = GCOM):  
Jog A1 100 TimeJog=5000  
Sleep 2000  
A1.StartType=GCOM  
Jog A1 200  
The resulting profile for this is:  
5. 3  
CAMMING  
Camming is an extension of gearing. It can be thought of as gearing where  
the gear ratio varies according to the master position. The master position,  
optionally runs through a gear ratio and drives the input to a cam table. The  
cam table is a list of point pairs which map the master position to the slave  
position. The output of the cam table provides the slave axis position.  
The operation of camming looks like:  
5.3.1. Key Features  
The MC's camming features are:  
Camming supports motion in both directions. The master runs  
indefinitely in either positive or negative direction without accumulation  
of error.  
Cam tables are driven by an axis position command, an axis position  
feedback, or an encoder brought in through the SERVOSTAR's  
external encoder input. It is driven by either physical or simulated axes.  
Cam tables are two-dimensional. The points may be irregularly  
spaced. Linear interpolation is used between points.  
108  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Master-Slave  
Cam profiles do not need to return to the original position at the end  
of the profile.  
Cam tables are calculated either off-line and stored, or on the fly.  
Cams cycle either indefinitely or are specified to cycle a specific  
number of times.  
Multiple cams are defined and linked together automatically.  
The master position is processed through the master-slave gear ratio  
(GEARRATIO).  
Issued incremental moves are summed with the cam profile to form  
the slave position command.  
5.3.2. GEARRATIO  
In camming, you set the proportional constant between the master and slave  
with <axis>.GEARRATIO. If GEARRATIO = 1, the table is matched one-to-  
one to the master axis. If it is less than one, the table is driven at a speed  
slower than the master is moving. For example, to run the table at half the  
speed of the master:  
A1.GearRatio = 0.5  
'Drive cam table at half speed  
The master turns two units to drive the table one unit.  
GEARRATIO is a double-precision floating-point number. To reverse the  
direction of the slave, enter the ratio as a negative number. Its value is  
changeable during camming, but it has to be done carefully to avoid a  
position jump in the slave value due to large differences between the old and  
new value.  
5.3.3. Incremental Moves  
With incremental moves to the slave, the profile from the incremental move is  
summed with the profile for gearing to form the slave position.  
5.3.4. Cam Tables  
A cam table is a list of master/slave point-pairs that define a one-to-one  
mapping of the master to the slave axis. You specify the number of point  
pairs. It may be as large or as small as the application requires. The  
following is a typical cam table:  
CAM1.1 = (10, 20)  
CAM1.2 = (20, 40)  
CAM1.3 = (30, 60)  
CAM1.4 = (40, 80)  
CAM1.5 = (50, 100)  
In cam tables, the position of both the master and slave are in the position  
units of the respective axes. The individual points in the table are given at  
irregular intervals. This is useful if the cam profile has long smooth sections  
and sharp turns. Irregular intervals allow you to use a few points for the  
smooth section and many for the sharp turns. Although the interval of master  
position is irregular, it must always be greater than zero. The master position  
must be monotonically increasing or decreasing in the cam table. The slave  
position is not limited by this requirement.  
M-SS-005-03  
Rev E  
109  
 
Master-Slave  
06/2005  
Danaher Motion  
In the unusual case that the master position is located exactly on one of the  
master position points, the slave position is the corresponding point of the  
master/slave point-pair. When the master is located between two points, the  
MC uses linear interpolation to calculate the position.  
Cam tables are incremental in one aspect and absolute in another. Within  
the cam table, the positions are absolute. Suppose you want a cam table  
with 5 points with each point of the master separated by 10 units, and slave  
positions separated by 20 units. The table (with the assumed name CAM1)  
is:  
CAM1.1 = (10, 20)  
CAM1.2 = (20, 40)  
CAM1.3 = (30, 60)  
CAM1.4 = (40, 80)  
CAM1.5 = (50, 100)  
The master and slave positions are absolute within the table. This method is  
not a valid way of entering cam table items, but it is an illustration of the table  
entries. Creating cam tables is covered later.  
Cam tables are incremental with reference to the start point. The start  
position in a cam table is always offset to the master and slave positions  
when the cam table is enabled. The operation of the table above is identical  
to the table below where the point pairs are adjusted to allow the first point to  
change from (10, 20) to (0, 0):  
CAM1.1 = (0, 0)  
CAM1.2 = (10, 20)  
CAM1.3 = (20, 40)  
CAM1.4 = (30, 60)  
CAM1.5 = (40, 80)  
Cam tables can be specified to command net motion. The start and end  
points of the cam table are different. The reason cam tables are incremental  
or decremental with regard to starting points is to allow a cam table to  
generate net motion while allowing it to be called many times in succession.  
Consider the following graph that shows just such a cam table with net  
motion executed for four cycles:  
Each successive cycle ratchets the slave position up. The starting position in  
the table cannot be equal to the actual slave position or the cam slave  
position (which is fixed in the cam table) and the actual slave position (which  
is ratcheting up each cycle) does not match for more than one cycle.  
The distance to be moved is specified indirectly through the cam table data.  
The total displacement of one cycle of the master is the master position of  
the last point pair less the master position of the first, divided by  
GEARRATIO.  
110  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Master-Slave  
In many applications, you must ensure that this quantity is precise or the  
master appears to creep over time. The MC uses double-precision math (16  
digits of accuracy) for cam calculations. Use the MC to calculate  
mathematical expressions to obtain the greatest possible precision. For  
example, if GEARRATIO=1:3, use the MC to calculate the value rather than  
rounding a previously calculated value:  
MasterGearRatio = 1/3  
'Good: 1/3 accurate to 16 places  
MasterGearRatio = 0.33333  
'Poor: 1/3 accurate to 5 places  
The net motion commanded to the slave is the slave position of the last  
point-pair less that of the first. If you do not want net motion in the slave, you  
must assign the slave positions of the first and last point-pairs to be identical.  
At the point when camming is enabled, the MC takes a snap-shot of the  
master position feedback, position or position external (depending on master  
definition), and slave position and offsets all entries in the cam table for the  
master and slave. Cam tables are incremental with respect to the actual  
position of the axes at the time camming is started. For example, suppose a  
cam table starts at (0, 0) but when the camming is enabled, the master  
position is 1000 and the slave's position (PCMD) is -2000. Each point-pair in  
the table is implicitly adjusted by (1000, -2000) throughout the cam cycle.  
After each cam cycle, the offset to the master and slave is adjusted by the  
MC. The cam master position is adjusted for the difference between the  
master position at the starting and ending points. If the cam table has net  
motion, each subsequent cycle adds the net motion to the slave-commanded  
position.  
Both the master and slave can be in rotary mode without affecting the  
camming operation.  
5.3.5. Cam Cycles  
One cam cycle is the operation of moving the master position feedback  
through an entire cam table. Instead of using master position feedback, you  
can use position or posistion external. At the end of a cam cycle, the cam  
ends or transitions to the next cycle. The next cycle simply repeats the  
current cam or is another cam. The number of times a cam is repeated is  
controlled by <cam>.CYCLES. Other cams are linked in automatically with  
NEXT and PREVIOUS.  
When the master is moving forward, the cam position feedback counts up.  
The cycle ends when the master position is greater than the last entry in the  
cam table. Then, the cam moves to the next cycle. Similarly, when the  
master is counting down, the cycle ends when master PFB is less than the  
first entry in the table. The cam moves to the previous cycle. It all depends  
on whether the table is increasing or decreasing. If there is no NEXT (or  
PREVIOUS) cam cycle, camming is disabled and the slave axis stops.  
Whether or not the cam cycle repeats, and the number of times it should  
repeat, is specified in <cam>.CYCLES. You can enter 1 to indicate that the  
cam runs once and does not repeat, -1 to indicate the cam runs indefinitely,  
or use a positive numberto indicate the number of times the cycle runs.  
M-SS-005-03  
Rev E  
111  
 
Master-Slave  
06/2005  
Danaher Motion  
For example, suppose you want a cam to run four cycles as shown below:  
You would use the following line:  
CAM1.CYCLE = 4  
' Run cam1 four cycles  
If you want a cam to run the same table an indefinite number of times, use:  
CAM1.CYCLE = -1 'Run the cam indefinitely  
When two cam tables are interconnected in a double-linked chain, only one  
cam table is active at a time. This enables changes in the other chained cam  
table by controlling the cycle time parameter of the active cam table. Setting  
its value to –1 results an infinity periodic of the active cam. After updating all  
the relevant values in the chained table, set the active table cycle to 1. At the  
end of the current period, the two tables are exchanged and the chained cam  
table is generated.  
You can monitor the number of cycles run with <axis>.CAMCYCLE. When  
the master is moving forward, CAMCYCLE counts up. When CAMCYCLE  
reaches CYCLE, the axis transitions to the next cam, if there is one.  
Similarly, when the master is running backward and CAMCYCLE reaches 0,  
the cycle transitions to the previous cam, if there is one.  
The MC allows you to specify multiple cam tables at the same time. The  
maximum number of cam tables is 256. The MC allows you to link cam  
tables together using two properties of the current cam table: NEXT and  
PREVIOUS. These properties allow automatic transition from one cam table  
to another without the accumulation of error in the master or slave positions.  
To link one table to another, assign NEXT and PREVIOUS to the desired  
cam table. For example:  
StartCam.Next = ForwardCam  
StartCam.Previous = ReverseCam  
The linking of the three cams (Cam0, Cam1, Cam2) is shown in the next  
figure.  
Set NEXT and PREVIOUS independently. The NEXT and PREVIOUS  
pointers cannot be changed dynamically. The change takes place at the next  
transition of the cam table. If you do not want to link to another cam at the  
end of the current cam's cycle, set NEXT and PREVIOUS to NULL (0).  
112  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Master-Slave  
If you have linked cams, the cam cycle runs the number of times specified in  
CYCLES. For example, assume Cam1 is being driven by a forward rotating  
master. If CAM1.NEXT=CAM2 and CAM1.CYCLES=4, Cam1 cycles four  
times before transitioning to Cam2. Similarly, if the master is rotating  
backward and CAM1.PREVIOUS=Cam0, Cam1 cycles four times before  
transitioning to Cam0.  
If the cam has run enough to exhaust the number of cycles and no cams are  
linked to the current cam, the axis automatically disables camming and  
decelerates at maximum deceleration to zero velocity.  
5.3.6. Create Cam Tables  
Cam tables contain the point-pairs that map the master position feedback to  
the slave position. Cam tables are only a part of cams. Other properties of  
cams include CYCLE, NEXT and PREVIOUS. Only the table portion of  
cams are stored permanently in the MC's Flash disk. The other properties  
are set during program operation.  
There are two types of cam tables: static and dynamic. Static tables are built  
and stored in flash disk to be used later while dynamic tables are built at run  
time. You should choose a type based on your application.  
5.3.6.1. STATIC TABLES  
Static cam tables are built offline and stored permanently in the MC's Flash  
disk. They allow you to use advanced tools to graphically build and inspect  
the cam table, and do not take away from system processing resources at  
run time. Static cam tables are usually the best choice when the cam table  
does not change during normal operation.  
You can build static tables two ways. First, you can use Windows tools to  
build the table, then use MC tools to convert and store the table. Second,  
you can build static cam tables inside the MC. Both methods are shown in  
the next figure.  
From Windows  
From MC-BASIC  
Create cam with  
CREATECAMDATA.  
Create point-pairs  
with a spreadsheet.  
Save as .CSV file.  
Calculate and store  
cam data point-pairs.  
Use the LOAD button in  
BASIC Moves to convert the  
*.CSV file to a *.CAM file in  
the SERVOSTAR MC.  
Store in Flash with  
STORECAMDATA.  
SERVOSTAR MC Flash Disk  
M-SS-005-03  
Rev E  
113  
 
Master-Slave  
06/2005  
Danaher Motion  
If you are using a static table, use the Windows-based tools. This method is  
simpler and you have more tools available with which to graph and analyze  
the cam table.  
You can create point-pairs using windows applications such as a text editor,  
spread sheets (Excel), or mathematical programs (MatLab). For  
spreadsheets, create a new sheet with two columns and one row for each  
point-pair. Do not include a row for headings and do not include any other  
information within the sheet. The first element of each row is the master  
position. The second is the corresponding slave position. The master  
position must increase or decrease with each point-pair as long as it is  
monotonic. Its value cannot change directions (i.e., increase and then  
decrease) or stay the same.  
When the table is complete, save to a Comma Separated Variable or .CSV  
file. This is a text file format with one line for each point-pair and commas  
between the master and slave values. For a five-point cam table, the .CSV  
file looks like:  
10, 20  
20, 40  
30, 60  
40, 80  
50, 100  
When you add the .CSV file to your project, BASIC Moves converts it to a  
cam table and stores it in the MC.  
When building a cam table using MC-BASIC, first globally allocate cam  
storage. Use Common Shared <var> as Cam:  
Common Shared CAM1 as Cam  
Here, CAM1 is used as the name. Replace CAM1 with any legal MC name.  
The easiest way is to include this line in Config.Prg and reboot the MC. The  
alternative is to enter this at the terminal window. Remember that the effect  
of this line persists only until the MC resets.  
Using MC-BASIC, create storage for the table of point-pairs. First, select a  
task to calculate the point pairs and enter the following line in that task:  
Program CamMaker  
CreateCamData 5 CAM1  
This allocates five data points for CAM1. Essentially two arrays (of size 5)  
are created that are named CAM1.MASTERDATA and CAM1.SLAVEDATA.  
Calculate the point-pairs to use in MC-BASIC. Build loops and iterate through  
the array. The array is 1-based and you receive an error if you go outside the  
bounds of this array. For this example, the points are simply loaded:  
CAM1.MasterData[1]=10  
CAM1.SlaveData[1]=20  
CAM1.MasterData[2]=20  
CAM1.SlaveData[2]=40  
CAM1.MasterData[3]=30  
CAM1.SlaveData[3]=60  
CAM1.MasterData[4]=40  
CAM1.SlaveData[4]=80  
CAM1.MasterData[5]=50  
CAM1.SlaveData[5]=100  
Finally, store the table on the flash disk. If you use:  
StoreCamData MyCam.Cam Cam1  
114  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Master-Slave  
This stores the cam as MyCam.Cam in flash memory. The name of the file  
follows the 8.3 format. The filename cannot have more than 8 characters in  
the main part and 3 characters in the extension. The cam data file must have  
the .cam extension This file can be loaded at any time using  
LOADCAMDATA.  
If you created the cam storage (Common Shared <var> as Cam), delete it  
with:  
DeleteCam Cam1  
A cam table cannot be deleted if it is in use or if the task that it is attached to  
is loaded.  
5.3.6.2. DYNAMIC TABLES  
Cam tables can be calculated dynamically. This allows you to build a cam  
profile based on events that occur during operation, such as the current  
position or speed of an axis. This process is identical to the process of  
creating a static cam table from MC-BASIC except you do not place the data  
in Flash. Instead, you use the cam table directly.  
5.3.7. Operating Cams  
Now that you know the concepts of camming, you need to know the step-by-  
step process to use one. Throughout this section, CAM1 is our example. The  
entire process is shown in the figure below:  
M-SS-005-03  
Rev E  
115  
 
Master-Slave  
06/2005  
Danaher Motion  
Step 1: Allocate Space Allocate space for the cam with Common Shared  
<var> as Cam. All cams are global, so this line must  
be located in Config.Prg. For example:  
Common Shared CAM1 as Cam  
Step 2: Load Cam Data This can be accomplished in two ways. For a static  
cam data array which has been calculated and  
stored in the MC, use LOADCAMDATA:  
LoadCamData MyCam.Cam CAM1  
or dynamically calculate the cam. This is a two step  
process. First, create space for the data array and  
then fill that space. For example, for a five element  
array, you enter:  
CreateCamData 5 CAM1  
CAM1.MasterData[1]=10  
CAM1.SlaveData[1]=20  
CAM1.MasterData[2]=20  
CAM1.SlaveData[2]=40  
CAM1.MasterData[3]=30  
CAM1.SlaveData[3]=60  
CAM1.MasterData[4]=40  
CAM1.SlaveData[4]=80  
CAM1.MasterData[5]=50  
CAM1.SlaveData[5]=100  
This is similar to building a static cam table. The  
difference is that this cam table is never stored to  
or loaded from flash.  
Step 3: Initialize Other Elements Initialize other elements of the cam:  
CAM1.Next = CAM2  
CAM1.Previous = CAM0  
CAM1.Cycles = 3  
Step 4: Initialize the Axis Initialize the elements of the axis related to  
camming. Set FIRSTCAM to the first cam the axis  
follows:  
A1.FirstCam = CAM1  
Set the master position within the cam at the point  
where you wish to start. For example, you may  
have a cam table where the master position goes  
from 0 to 100.00, but the correct starting position  
for the cam might be 33.333, so you enter:  
A1.FirstCamOffset = 33.333  
FIRSTCAMOFFSET must be within the range of  
the master position. Remember that  
FIRSTCAMOFFSET defaults to 0. If the master  
range does not include zero, an error is generated  
if you do not set FIRSTCAMOFFSET.  
Set GEARRATIO and name the source of the  
master signal:  
A1.GearRatio = 1.00  
A1.MasterSource = A2.PFB  
Finally, set SLAVE to CAM:  
A1.Slave = CAM  
116  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Master-Slave  
Step 5: Enable the Axis At this point, camming is enabled. However, you  
must enable the drive to see motion:  
A1.Enable = ON  
Camming cannot be enabled if the axis is in a  
relative or absolute move, or during STOP.  
Enabling camming when gearing is enabled or  
when an absolute move is being executed  
generates an error. Disabling or enabling the drive  
does not affect whether gearing is enabled.  
To disable camming, set SLAVE to OFF:  
A1.Slave = OFF  
'Disable camming  
When camming is disabled, the velocity of the  
slave axis is decelerated to zero at the rate of  
<axis>.DECELERATIONMAX (<axis>.DMAX).  
Issuing JOG or STOP for the axis disables  
camming. Issuing STOP turns camming off  
immediately. The velocity of the axis is decelerated  
to zero at the rate set by  
<axis>.DECELERATIONMAX.  
If JOG command is issued, camming on that axis  
is disabled immediately and the cam profile ramps  
to zero at the rate, <axis>.DEC. The JOG profile  
ramps up at the rate specified by <axis>.ACC. For  
a short time, the axis profile is the sum of these two  
profiles as shown below.  
After the camming profile goes to zero, the profile  
is controlled wholly by the JOG profile. Disabling  
the master or slave does not disable camming.  
Camming remains active and the slave position is  
commanded accordingly, when re-enabled. A fault  
is generated when the drive is re-enabled if the  
distance between the slave position and the  
command from the cam table is greater than  
POSITIONERRORMAX. Be cautious when re-  
enabling a cammed slave axis if a large position  
error exists. The motor rapidly upon enable to  
immediately correct this error.  
M-SS-005-03  
Rev E  
117  
Master-Slave  
06/2005  
Danaher Motion  
Step 6: Read Dynamic Information There are numerous read-only  
properties regarding the operation of the cam.  
Axis Properties  
<axis>.ACTIVECAM provides the name of the  
cam being executed by that axis.  
Cam Properties  
<cam>.CAMCYCLE provides the number of cycles  
the cam has executed. If the cam  
master is moving forward, the  
current cam ends at the completion  
of the cycle where  
CAMCYCLE=CYCLE.  
When the cam master is moving  
backward, the current cam ends at  
the completion of the cycle where  
CAMCYCLE=0.  
<cam>.CAMINDEX provides the current index  
within the current cam table. For  
example, if there are 100 points in  
the table and the cam is half  
complete, CAMINDEX=50.  
<cam>.MASTERDATA is used with CAMINDEX  
to provide the value of the master  
position of the current index within  
the cam. For example, if the current  
cam table master position range is -  
10 to 10 and the position is in the  
middle of the range,  
CAM1.MASTERDATA  
[CAMINDEX]=0.00.  
CAM1.MASTERDATA[CAMINDEX]  
is not equivalent to the position of  
the master signal (<axis>.PFB)  
because cams are incremental with  
respect to starting position.  
<cam>.SLAVEDATA used with CAMINDEX to  
give the value of the slave position  
for the current index of the cam. As  
with CAMVALUE,  
CAM1.SLAVEDATA[CAMINDEX] is  
not equivalent to <axis>.PCMD  
because the two may be offset from  
each other.  
118  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Master-Slave  
5. 4  
SIMULATED AND MASTER-SLAVE AXES  
Simulated axes are used to enhance machine control. They typically are with  
gearing and camming. Three common uses are:  
1. To act as fixed speed masters for slaved axes.  
2. To monitor physical axes.  
3. To synchronize slaved axes.  
5.4.1. Fixed-Speed Masters  
The most common use for a simulated axis is as a fixed-speed master axis  
for geared or cammed axes. This is used for testing or as part of normal  
operation. The simulated axis is normally set to a fixed speed using JOG.  
Slave axes are driven without a physical motor. For example, if you want to  
view a cam table, you can use a simulated axis running at a fixed speed. In a  
sense, the simulated axis provides the ideal condition where the master  
speed is precisely fixed. This can allow you to fine-tune cams and carefully  
inspect the synchronization of geared axes.  
Fixed-speed simulated axes and cams are combined to allow you to produce  
virtually any profile you need for a machine. You need only load the profile,  
cam table and drive the axis with a fixed-speed simulated axis.  
5.4.2. Monitor Physical Axes  
Simulated axes are used to monitor physical axes for machine control by  
slaving a simulated axis to a physical axis and monitoring the position and/or  
velocity of the simulated axis. For example, if you slave a non-rotary  
simulated axis to a rotary physical axis, you can monitor the total distance  
the physical axis has traveled because any variable from a simulated axis  
can be used to fire events. You can generate events based on the simulated  
axis. The position feedback of a simulated axis can drive a Programmable  
Limit Switch (PLS) to add more monitoring flexibility.  
5.4.3. Synchronize Slave Axes  
Many machines have multiple slaved axes that are controlled as a group.  
Normally, synchronization is maintained when these axes share a single  
physical axis as a master. However, on some machines, there are special  
modes of operation where a physical axis cannot provide all the necessary  
functions. Consider a machine where a minimum speed must be maintained  
on the slave axes even if the master axis stops. In this case, you can insert a  
simulated axis between the physical master and slave drives. To do this,  
slave a simulated axis to the physical master and then slave the other axes  
to the simulated axis. Use events to tell when the physical axis is above or  
below the minimum and use JOG to keep the simulated axis above the  
desired minimum to keep the slave axes moving even if the physical master  
stops.  
M-SS-005-03  
Rev E  
119  
 
Master-Slave  
06/2005  
Danaher Motion  
For example:  
Program  
OnEvent Vel_Below_Min PseudoAxis.Vcmd < 100  
Jog PseudoAxis 100  
‘This indirectly turns gearing off  
End OnEvent  
OnEvent Vel_Above_Min PseudoAxis.Vcmd >= 100  
PseudoAxis.Slave=Gear  
End OnEvent  
Attach PseudoAxis  
EventOn Vel_Below_Min  
EventOn Vel_Above_Min  
While 1  
Sleep 100  
End While  
End Program  
The following figure shows this process.  
120  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Groups  
6.  
GROUPS  
Groups allow you to control multiple axes as a single mechanism. With  
groups, the position command and feedback signals are no longer single  
values, but instead, are vectors with two or three elements. Velocity and  
acceleration no longer apply to a motor, but instead, apply to the combination  
of two or three motors moving in concert.  
6. 1  
SET UP  
Groups are combinations of axes. These axes must be orthogonal if their  
scalar properties (velocity) are to be correct. For example, a group can be  
used to drive an x-y table. Groups are supported for two- and three-axis  
machines. In fact, any number of axes can be added to a group.  
To set up a group, first set up each of the axes that will be in the group.  
Then, use Common Shared to form the group:  
Common Shared MyGroup as Group AxisName = xAxis AxisName = yAxis  
There is no limitation to the number of axes in a group. All axes in the system  
(including simulated axes) may be part of one group.  
It is necessary to set VELOCITYFACTOR, ACCELERATIONFACTOR,  
and JERKFACTOR for the group. As a first approximation, set  
<group>.VFAC = 1/1000, set AFAC=VFAC/1000, and set  
JFAC=AFAC/1000.  
6. 2  
6. 3  
DELETEGROUP  
DELETEGROUP deletes the specified group. The participating axes  
thereafter function only as independant axes. They must not be moving. No  
tasks may be loaded.  
DeleteGroup MyGroup  
ACCELERATION PROFILES  
As with single axes, the MC provides controlled acceleration profiles for  
groups. This reduces vibration and wear on the machine, and allows the  
highest acceleration rates. You can independently control the acceleration  
and deceleration rates.  
6.3.1. Acceleration and Deceleration  
<group>.ACCELERATION and <group>.DECELERATION control the  
acceleration rates of the group mechanism. For example, the following lines  
change the acceleration rates for MyGroup:  
MyGroup.Acceleration = 1000  
MyGroup.Deceleration = 1000  
<group>.ACCELERATION and <group>.DECELERATION apply to the  
combined motion of the individual axes. For example, if MyGroup is a three-  
axis group formed with Axis1, Axis2, and Axis3, then:  
MyGroup.Acc = (Axis1.Accel2 + Axis2.Accel2 + Axis3.Accel2) ½  
M-SS-005-03  
Rev E  
121  
 
Groups  
06/2005  
Danaher Motion  
Group acceleration is the orthogonal combination of the axes' acceleration.  
Group acceleration and deceleration are limited according to the axes‘  
values.You can impose limits to constrain the time during which group  
acceleration and deceleration occurs. <group>.TIMEACCELERATION and  
<group>.TIMEDECELERATION define the duration of the acceleration  
phase.  
6. 4  
POSITION  
Group position differs from axis position in that a single property must  
represent the position of multiple axes. In some cases, the individual axis  
properties are maintained so that the property becomes a vector with two or  
three entries. This is the case for POSITIONFEEDBACK or  
POSITIONCOMMAND. In other cases, the position from multiple axes are  
combined using the square root of the sum of the squares, as for  
POSITIONERRORMAX.  
6.4.1. Vector  
With groups, three position properties are vectors: the position command,  
position feedback, and position final. In each case, the quantities in the  
vector are equivalent to the individual axis properties. For example, you can  
set POSITIONFINAL as part of a MOVE:  
Move MyGroup {5.5, 6.5}  
This sets PFINAL of the first axis to 5.5 and the second to 6.5. Querying the  
position feedback from a two-axis group from the terminal also returns a  
vector. For example:  
? MyGroup.PFb  
returns:  
(5.600443e+003, 6.422422e+003)  
The positions in these vectors are ordered according to the way the group  
was created with Common…As Group. The first axis declared occupies the  
first position in the vector, the second occupies the second, etc.  
6.4.2. Scalar  
Other group position properties are scalar. These properties are the  
orthogonal combination of the axis properties. These properties include:  
POSITIONERROR  
POSITIONERRORMAX  
POSITIONERRORSETTLE  
POSITIONTOGO  
If MyGroup is formed with Axis1 and Axis2, and AXIS1.POSITIONTOGO = 1  
and AXIS2.POSITIONTOGO=1, MYGROUP.POSITIONTOGO = 1.414, the  
orthogonal combination of the two axes' POSITIONTOGO. Similarly, when  
you set POSITIONERRORMAX or POSITIONERRORSETTLE, the position  
error they are compared to is the orthogonal combination of the axes'  
POSITIONERROR.  
122  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Groups  
6. 5  
VELOCITY  
A group’s scalar velocity properties are always the orthogonal combination of  
the respective axes' velocity properties. Group velocity properties include:  
VELOCITYCOMMAND  
VELOCITYFEEDBACK  
VELOCITYCRUISE  
VELOCITYFINAL  
VELOCITYMAX  
VELOCITYOVERRIDE  
vector property  
vector property  
scalar property  
scalar property  
scalar property  
scalar property  
Each of these properties operates as its axis equivalent and are clearly  
defined in the SERVOSTAR® MC Reference Manual.  
6. 6  
LIMITS  
Group limits are similar to limits placed on axes. Limits can be imposed in  
two ways: they can be checked realtime, or they can be checked only for  
subsequent actions.  
6.6.1. Generator  
Generator limits affect subsequent commands to the motion generator. For  
example, if you change an acceleration limit, this affects subsequent motion  
commands but has no effect on the current motion.  
6.6.2. Realtime  
The MC checks realtime limits each SERCOS update cycle. For example,  
exiting position error of every axis is monitored each SERCOS cycle.  
6.6.3. Position  
Position limits are imposed solely by the axes and are checked at the  
beginning of every movement. If one of the target’s points exceeds its limit,  
the whole movement is rejected. There are no group position limits. There  
are also several limits in the MC related to position:  
Set POSITIONERRORMAX (PEMAX) to the total position error the system  
can tolerate during operation (maximum square root of the sum of squares):  
MyGroup.PEMax = 1.0  
Set POSITIONERRORSETTLE to the total position error the system can  
tolerate to be considered in position.  
MyGroup.PositionErrorSettle = 1.0  
TIMESETTLE (TSETTLE) is the amount of time required before an axis is  
considered settled (POSITIONERROR<POSITIONERRORSETTLE). After a  
MOVE/CIRCLE profile is complete, the MC waits for POSITIONERROR <  
POSITIONERRORSETTLE for TIMESETTLE milliseconds before setting  
ISSETTLED.  
TIMESETTLEMAX (TSETTLEMAX) defines the amount of time allowed for  
settling after a move has been commanded. After the MOVE/CIRCLE profile  
is complete, the MC waits TIMESETTLEMAX milliseconds for settling. If the  
position error remains above PESETTLE, an error is generated.  
M-SS-005-03  
Rev E  
123  
 
Groups  
06/2005  
Danaher Motion  
ISSETTLED is a binary (ON or OFF) property that indicates if the group is  
settled. To be settled, the motion profile must be complete and the  
orthogonal combination of axis position errors must be below  
POSITIONERRORSETTLE. The time condition must also be satisfied.  
6.6.4. Velocity  
There is one group limit in the MC related to velocity: VELOCITYMAX  
(VMAX) sets the maximum speed the motion generator can command the  
group. This property is checked at the beginning of each move. For example:  
Group.VelocityMax = 5000  
The actual executing velocity is also limited according to the group’s axes  
velocity limitations. The maximum allowed axes velocity is initialize group  
velocity. In this case a note is returned and can be seen only if  
SYS.MOTIONASSISTANCE is on.  
6. 7  
ACCELERATION  
Three limits control acceleration, deceleration, and jerk, which limit the  
velocity transients on acceleration profiles.  
ACCELERATIONMAX is the upper limit for acceleration in MC  
acceleration units.  
DECELERATIONMAX is the upper limit for deceleration in MC  
acceleration units.  
The actual executing acceleration and deceleration are limited also  
according to the group’s axes limitations. The maximum allowed axes of  
those parameters initialize the group’s values. In this case, a note is returned  
and can be seen only if SYS.MOTION ASSISTANCE is on.  
The jerk properties, JERK, JERKFACTOR, JERKMAX, and  
SMOOTHFACTOR are applicable in group motion to obtain smooth motion  
control.  
6. 8  
VELOCITY, ACCELERATION,  
DECELERATION AND JERK RATES  
GROUP.VELOCITYRATE defines the group velocity maximum scaling  
factor from 0.1 to 100 independent of acceleration,  
deceleration or jerk. GROUP.VELOCITYRATE may  
be modal or nodal.  
GROUP.ACCELERATIONRATE defines the group acceleration maximum  
scaling factor from 0.1 to 100 independent of velocity,  
deceleration or jerk. GROUP.ACCELERATIONRATE  
may be modal or nodal.  
GROUP.DECELERATIONRATE defines the group deceleration maximum  
scaling factor from 0.1 to 100 independent of velocity,  
acceleration or jerk. GROUP.DECELERATIONRATE  
may be modal or nodal.  
GROUP.JERKRATE defines the group maximum Jerk scaling factor from  
0.1 to 100 independent of velocity, acceleration or  
deceleration. GROUP.JERKRATE may be modal or  
nodal.  
124  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
For example:  
06/2005  
Groups  
Common Shared Gr1 as Group AxisName=A1 AxisName=A2  
Gr1.VRate = 50  
Gr1.ARate = 70  
Gr1.DRate = 80  
Gr1.JRate = 60  
‘ VelocityRate 50%  
‘ AccelerationRate 70%  
‘ AccelerationRate 80%  
‘ JerkRate 60%  
6. 9  
MOTION  
A group is controlled by the motion generator. This software device receives  
commands from MC tasks and produces position and velocity commands for  
each drive in the group every SERVO cycle. The two group motion  
commands are MOVE and CIRCLE. The MC also provides synchronization  
of the execution of motion commands as well as changing motion profiles on-  
the-fly and blending a followed movement. In addition, the MC provides  
multiple modes for starting and stopping motion. Several conditions must be  
met before the MC generates group motion:  
1. The controlling task must ATTACH to the controlled group.  
2. All axes in the group must be ENABLEd.  
3. The system and axis motion flags must be ENABLEd.  
You can declare a group from every context. However, using Config.prg in  
most applications requires this to only be done once.  
A1.Name = xAxis  
A2.Name = yAxis  
Common Shared xyTable as Group AxisName = xAxis AxisName = yAxis  
6.9.1. Attach Task and Axis  
Before a task can send motion commands to a group, the group must be  
attached to the task. This prevents other tasks from attempting to control the  
group. To attach a group, issue an ATTACH from the controlling task:  
Attach MyGroup  
If no other task is attached to the group and no axis from the group is  
attached, the group is immediately attached. Otherwise, an error is  
generated.  
As long as the task has the group attached, no other task can control the  
group or axes within the group. The axes belonging to the group cannot be  
controlled independently from other tasks. When a task is finished with a  
group, it should detach the group:  
Detach MyGroup  
If a task ends, all attached groups and axes are automatically detached. One  
exception for the requirement that a group be attached is if the motion  
command is issued from the terminal window. In this case, assuming the  
group is not attached by any other task, the group is automatically attached  
to the terminal window for the duration of the motion.  
6.9.2. ENABLE  
Now, enable the drives by typing the following in the terminal window:  
System.Enable = ON  
MyGroup.Enable = ON  
M-SS-005-03  
Rev E  
125  
 
Groups  
06/2005  
Danaher Motion  
6.9.3. Motion Flags  
The last step in preparing a system for motion is to turn the motion flags ON.  
There are two motion flags: the system motion flag and the motion flags of  
each axis within the group. For example:  
System.Motion = ON  
A1.Motion = ON  
A2.Motion = ON  
A3.Motion = ON  
There is a motion flag for the group that can be used to enable motion for all  
axes in the group. In many applications, a hardware switch should be tied to  
the motion flag. The MC does not have a hardware motion input, but you can  
use events to create this function. The following example demonstrates a  
task that uses external input SYSTEM.DIN.1 to control the system motion  
flag:  
Program MotionSwitch  
OnEvent MOTION_ON System.DIN.1 = ON  
System.Motion = ON  
End OnEvent  
OnEvent MOTION_OFF System.DIN.1 = OFF  
System.Motion = OFF  
End OnEvent  
End Program  
6.9.4. STOP  
STOP stops group motion in the motion buffer. In the command, you must  
specify the group:  
Stop GroupA  
Normally, STOP is set to stop motion immediately at the rate of  
DECELERATIONMAX. However, you can modify the effects of STOP with  
STOPTYPE. <group>.STOPTYPE can take four values:  
STOPTYPE = IMMED  
Stop group immediately at DECELERATIONMAX on each axis. The  
current path of the n\movement is not preserved.  
STOPTYPE = ENDMOTION  
Stop group at the end of the current motion.  
STOPTYPE = ONPATH  
Stop group immediately. Keep the stopping trajectory on the current  
motion path.  
STOPTYPE = ABORT  
Stop the current motion immediately without the ability to restore the  
stopped movements.  
STOPTYPE defaults to IMMED. If STOPTYPE = ENDMOTION, the current  
move is completed before STOP is executed. If STOPTYPE = ONPATH,  
STOP is executed so the group stays on the path. Stopping is according to  
the current movement’s deceleration and not at maximum deceleration to  
remain on the path.  
126  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Groups  
6.9.5. PROCEED  
After a STOP, you must PROCEED to clear the motion buffer. You can use  
PROCEEDTYPE to specify which way the motion generator should continue:  
PROCEEDTYPE = CONTINUE  
The motion generator continues the stopped command until complete.  
PROCEEDTYPE = NEXTMOTION  
The motion generator aborts the current move and goes directly to the  
stopped move in the motion buffer.  
PROCEEDTYPE = CLEARMOTION  
Clears the motion buffer. No motion executes. Default value.  
STOPTYPE = ABORT  
Current motion stops immediately but does not need a PROCEED to  
start the next motion. Only the current motion is stopped, the following  
commands are generated.  
6.9.6. MOVE  
MOVE for groups is almost identical to a MOVE for axes. There are two  
differences. First, POSITIONCOMMAND, POSITIONFEEDBACK, and  
PFINAL are group size vectors. Second, the profile, including  
ACCELERATION and DECELERATION, applies to all axes in the group.  
For example:  
MyGroup.VCruise = 2000  
Move MyGroup {100, 100}  
moves to position (100, 100) with a cruise velocity of 2000.  
You can override the following axis properties as part of a MOVE:  
ABSOLUTE  
STARTTYPE  
ACCELERATION  
ACCELERATIONRATE  
DECELERATION  
DECELERATIONRATE  
SMOOTHFACTOR  
VELOCITYCRUISE  
VELOCITYRATE  
JERK  
JERKRATE  
PFINAL (end of a move), is always specified in MOVE. However, the  
meaning of PFINAL depends on <group>.ABSOLUTE. This allows point-to-  
point moves to be specified two ways:  
ABSOLUTE = TRUE  
Final position is specified as actual group position at the end of the  
move. The final position equals PFINAL.INCREMENTAL.  
ABSOLUTE = FALSE  
Final position is referenced to the start position. The final position is the  
sum of PFINAL and PCMD at the start of the move. So:  
xyTableGroup.Absolute = TRUE  
Move xyTableGroup {100, 200}  
moves xyTableGroup to position (100, 200).  
M-SS-005-03  
Rev E  
127  
 
Groups  
06/2005  
Danaher Motion  
On the other hand:  
xyTableGroup.Absolute = FALSE  
Move xyTableGroup {100, 200}  
moves xyTableGroup a distance of (100, 200) units from the start  
position.  
ABSOLUTE defaults to INCREMENTAL. You can change ABSOLUTE any  
time, although the effect does not take place until you issue the next MOVE.  
6.9.7. CIRCLE  
The MC supports 2-axis circular interpolation with CIRCLE. In CIRCLE, you  
specify:  
Group name  
Angle to rotate (in degrees, positive = counter-clockwise) along with  
Center of the circle (CIRCLECENTER or CTR).  
Target point (TARGETPOINT) along with another point on the arc  
(CIRCLEPOINT).  
Circle xyTable Angle=90 CircleCenter = {0,0}  
or  
Circle xyTable CirclePoint = {10,20} TargetPoint = {100,200}  
A 2-axis circle is generated in a specified plane with incremental movement  
in the third axis. That generate a 3 axis circle movement but not helical.  
Circle xyTable CirclePoint = {10,20,10} TargetPoint =  
{100,200,20} circleplane= xy  
In the above example, the circle is implemented in the XY plane along with  
the incremental change of the Z axis. Optionally, you can override the  
following group properties with CIRCLE:  
ABSOLUTE  
ACCELERATION  
ACCELERATIONRATE  
DECELERATION  
DECELERATIONRATE  
JERK  
JERKRATE  
SMOOTHFACTOR  
STARTTYPE  
VELOCITYCRUISE  
VELOCITYMAX  
VELOCITYRATE  
For example, you can enter the following absolute and incremental circular  
moves:  
Circle xyTable Angle=90 CTR = {0,0} Absolute = False  
The value of ANGLE is not limited to 360. Greater values are specified to  
turn the motor more than once. The sign of the angle determines the  
direction of the motion. The value of ANGLE is not permanent. It exists only  
in the context of the command in which it is specified. Consequently, you can  
not query the value of ANGLE.  
The value of CIRCLECENTER is not permanent. It exists only in the context  
of the command in which it is specified. Consequently, you cannot query the  
value of CIRCLECENTER.  
128  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Groups  
CIRCLETARGET is a group size array. It specifies the target point of the  
circle. This array is not queried. CIRCLE, defined using CIRCLETARGET,  
is limited to 360 degrees.  
CIRCLEPOINT is a position array that specifies a point on the arc. The arc  
is calculated using the CIRCLETARGET and these points. This array is not  
queried.  
In case of 3 dimensions circle the active CIRCLEPLANE defines which  
group axes participate in the circle movement. The third axis is moved  
linearly. There are 3 plans that can be chosen: XY, XZ and YZ.  
6.9.8. Chain Commands  
You can chain group MOVEs and CIRCLEs using <group>.STARTTYPE.  
The following program makes a series of moves.  
A1.Name = xAxis  
A2.Name = yAxis  
Common Shared xyTable as Group AxisName = xAxis AxisName = yAxis  
From another task named MoveCircProgram:  
Attach xyTable  
xyTable.Absolute = TRUE  
xyTable.StartType = INPOS  
Move xyTable {-3, -2}  
‘Move to start position  
‘Move to start and wait to settle  
While(xyTable.isSettled = False)  
End While  
‘wait for settling  
‘Begin Pattern  
xyTable.StartType = GCOM  
xyTable.Absolute = FALSE  
Move xyTable {0, 4}  
‘Move smoothly from one move to the next  
‘Incremental moves  
Circle xyTable Angle = -90 CircleCenter = {-2, 2}  
Move xyTable {4, 0}  
Circle xyTable Angle = -90 CircleCenter = { 2, 2}  
Move xyTable {0,-4}  
Circle xyTable Angle = -90 CircleCenter = { 2,-2}  
Move xyTable {-4,0}  
Circle xyTable Angle = -90 CircleCenter = {-2,-2}  
While(xyTable.isSettled = False)  
Detach xyTable  
‘wait for settling  
End Program  
6.9.9. Blending  
Two movements blend tighter to smooth connection points. There are two  
ways to blend the movements: preserving the movement’s path (CP) or  
superposition. Set the blending method's ID with BLENDINGMETHOD.  
The continuous path method (CP) blends where  
continuity and velocity smoothness are required  
(gluing, dispensing, …). It is less useful for high-  
C
B
speed pick and place applications where cycle  
time is the main quality measurement. Using this  
blending method, you ensure that maximum  
space velocities are never exceeded and the  
original path is always followed. The segment's  
A
middle point is always part of the blended path.  
Only two consecutive motions can be blended  
together.  
M-SS-005-03  
Rev E  
129  
 
Groups  
06/2005  
Danaher Motion  
When the second motion is completed before the first one, the system does  
not blend the first and the third motions together. The main parameter in this  
type of blending CP. It specifies the distance from the target point on which  
the blending (second motion) begins. CP is dimensional. It is expressed in  
group position units. The system automatically limits this value to half the  
segments length.  
When the second movement is received too late (during the deceleration  
phase) or when the current motion causes excessive values of acceleration  
and velocity, blending between two movements is ignored.  
For Move-to-Move blending, use:  
Pos = start + I1 direction1 + I2 direction2  
For Move-and-Circle blending, use:  
Pos = start + I1 direction1 + (cos(I2)-1) rot_start2 + sin(I2)  
rot_normal2  
For Circle-and-Circle blending, use:  
Pos = center1 + (cos(I1) rot_start1 + sin(I1) rot_normal1 +  
(cos(I2)-1) rot_start2 + sin(I2) rot_normal2  
6.9.9.1. SUPERPOSITION  
Superposition blends motions at any point of time starting from the initial  
point of the movement up to the target. This blending mode is not limited by  
the combined actions of the two motions. It is your responsibility not to blend  
together motions that, in combination, produce velocities or accelerations  
outside of allowable system limits. However, each individual motion is limited  
by the usual kinematics constrains (VMAX, AMAX, DMAX, JMAX). This  
blending method is also able to swap movements when the second is  
finished before the first. In this case, there is continuous blending of the first  
and the third movements. Although this is a feature, it must be taken into  
consideration when designing blending paths.  
Using BLENDINGFACTOR, you define the beginning blending (second  
motion) point anywhere on the first movement path. It is dimensionless cy  
using a percentage of the path where the blending starts. A zero value of  
BLENDINGFACTOR designatess full blending, while 100 designates no  
blending.  
130  
Rev E  
M-SS-005-03l  
Danaher Motion  
For example.  
06/2005  
Groups  
Dim Shared blen_value As Long  
Program  
Attach xyTable  
BlendingMethod = 2  
BlendingFactor = 0  
StartType = GCom  
For blen_value = 100 To 80 Step -5  
Move xyTable {0,10} Abs=1 Vcruise=100 BlendingFactor=blen_value  
Move xyTable {10,20} Abs=1 Vcruise=100 BlendingFactor=blen_value  
Move xyTable {20,10} Abs=1 Vcruise=100 BlendingFactor=blen_value  
Move xyTable {10,0} Abs=1 Vcruise=100 BlendingFactor=blen_value  
Next  
Detach xyTable  
End Program  
results in the following profile:  
The following are blending limitations:  
Blending type of the first movement defines the actual connection path,  
although the second movement has a different definition. The second  
movement can blend with the current movement, although its blending  
method was not defined. In this case, blending occurs according to the  
second movement.  
Throughout the whole blending process, sine-acceleration or velocity  
trapeze profiles are used. However, mixing profile types is not allowed.  
In the next example, no blending is ignored:  
BlendingMethod = 0 CP = x BlendingFactor = x  
BlendingMethod = 1 CP = 0 BlendingFactor = x  
BlendingMethod = 2 CP = x BlendingFactor = 100  
The Position Command Generator (PCG) has two working modes: single  
and double. When PCG is in single mode, only one profiler call per sample is  
allowed. This is identical to no blending. When PCG is in double mode, there  
are two profiler calls per sample that actually execute the motion  
superposition. If the profiler of the second motion is in Profiler Following  
mode, the profiler of the first movement leads both movements. Use  
DOUBLEMODE to detect double mode interpolation during blending.  
6. 10  
MOVE CONTROL  
This section reviews options the MC provides for controlling group MOVEs  
and CIRCLEs.  
M-SS-005-03  
Rev E  
131  
 
Groups  
06/2005  
Danaher Motion  
6.10.1. Settling Time  
The MC actively watches to determine if the groups are settled into position.  
In most applications, the group position feedback is slightly delayed from the  
position command. After a move is complete, some time is required for the  
actual position to settle out to the commanded position. This time is called  
settling time.  
Ideally, settling time allows the group to move so that position error is zero .  
However, in real systems you must allow for the condition where the position  
error never quite reaches zero. On the MC, you specify how low you  
consider to be low enough with POSITIONERRORSETTLE or PESETTLE:  
xyTableGroup.PESettle = 0.01  
After the motion generator completes a move that ends with zero speed, it  
actively monitors the position error of the group (the orthogonal combination  
of the position error of each axis) to determine when it is between  
±PESETTLE. If it is within this range, <group>.ISSETTLED is true (1).  
Otherwise, it is false.  
In some applications, you must ensure that the position error remains below  
PESETTLE for a specified period of time before the group is considered  
settled. The MC allows you to specify this time period with the  
<group>.TIMESETTLE or <group>.TSETTLE (given in milliseconds). If the  
position error exceeds PESETTLE during this time, the timer is reset. If  
position error is within PESETTLE’s range for the time specified by  
TSETTLE, <group>.ISSETTLED is true (1). Otherwise, it is false. For  
example:  
PESettle = 0.01  
TimeSettle = 0.01 xyTableGroup.StartType = INPOSMove  
xyTableGroup {100 , 200}  
Move xyTableGroup {200 , 400}  
This example requires that after the motion generator completes the first  
move and xyTableGroup has position error at or below 0.01 for at least 10  
ms before the group is settled. Since STARTTYPE is INPOS, the motion  
generator waits for these conditions before starting the second move.  
6.10.2. Start Moves  
When the motion buffer is empty, group moves begin immediately. If you  
need to delay the next motion, you have two options. You can either use  
DELAY to insert a fixed delay time or STARTTYPE to delay, depending on a  
condition.  
Use DELAY to force the motion generator to wait a fixed period of time  
between moves. The motion element xyTableGroup must be specified in  
DELAY. For example:  
Move xyTableGroup {100, -100}  
Delay xyTableGroup 1000  
Move xyTableGroup {200, 500}  
forces a 1 second delay between the two moves. DELAY has units of  
milliseconds and must be greater than zero.  
DELAY differs from SLEEP in that SLEEP delays program execution and  
DELAY delays only the motion generator. DELAY is forced to the  
STARTTYPE mode.  
132  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Groups  
If you want to delay the start of a new move until a condition has been met,  
use <axis>.STARTTYPE. There are four choices:  
StartType = GeneratorCompleted or GCOM  
When STARTTYPE=GCOM, the new move starts as soon as the  
motion generator completes the current move's motion.  
StartType = InPosition or INPOS  
When STARTTYPE=INPOS, the motion generator delays executing the  
new motion until the current move completes and the position error  
settles to near zero.  
StartType = Immediate (IMMED) or SuperImmediate (SIMM)  
When STARTTYPE=IMMED or SIMM, the new move overwrites the  
current move. This is used when making realtime changes to the profile,  
such as changing the end-point of the current move without bringing the  
system to rest. For example, registration applications frequently use this  
function.  
StartType = Sync  
When STARTTYPE = SYNC, the motion is synchronized with  
SYNCSTART.  
6.10.3. Chain Moves  
When chaining multiple moves which all end at zero speed, you normally  
want STARTTYPE=INPOS. This forces the motion generator to wait for the  
position error to become small before starting the next move. If the position  
profile starts on the second move too soon, the motor may never come to  
rest. Normally, the desired performance is for the velocity to go to zero  
before the second move starts. This is the case where STARTTYPE =  
INPOS.  
The ending speed of a MOVE defaults to zero. However, you can specify a  
speed other than zero as the end speed. To do this,  
<axis>.VELOCITYFINAL. For example:  
MyGroup.VelocityCruise = 2000  
Move MyGroup {1.5, -2.33} VelocityFinal = 1000  
Move MyGroup {2.0, 4.2}  
When the final velocity is not specified, the movement terminates with zero  
velocity. If you specify a non-zero final velocity, the smoothness of the  
motion is your responsibility.  
If there are no movement commands to chain, the system stops motion with  
automatic braking and displays a message.  
6.10.4. Multi-Step Moves  
Combining non-zero end-point moves in the motion buffer produces multi-  
step moves. For example:  
REM First Step  
MyGroup.VelocityCruise = 2000  
Move MyGroup {100, 400} VelocityFinal = 1000  
MyGroup.StartType = GCOM  
‘Second Step  
MyGroup.VelocityCruise = 1000  
Move MyGroup {200, 400}  
M-SS-005-03  
Rev E  
133  
 
Groups  
06/2005  
Danaher Motion  
MyGroup.StartType is set to GCOM. The second move begins after the first  
move is complete. You must use STARTTYPE=GCOM when chaining a  
move after non-zero velocity end- move. You cannot use  
STARTTYPE=IMMED or SIMM because the new move overrides the old  
move. When the movement ends with non-zero final velocity, the next  
movement is started at the endpoint of the first movement or immediately, if  
STARTTYPE of the next movement is IMMED or SIMM.  
You can combine non-zero velocity end moves to produce profiles with as  
many steps as needed. However, there are a few restrictions:  
STARTTYPE for all non-zero velocity end moves (that is,  
VELOCITYFINAL<>0) must be GCOM.  
VELOCITYCRUISE and VELOCITYFINAL must be positive.  
PFINAL of the succeeding move must be far enough in front of  
PFINAL of the current move so the profile is possible with the  
acceleration limits. An error is generated if this rule is violated.  
The end position or the end velocity of a move in progress can be changed  
by setting STARTTYPE=IMMED and issuing the second move. This move  
command cancels the current move. For example issuing a move without  
changing the velocity:  
MyGroup.StartType = IMMED  
Move MyGroup {150, -400}  
Sleep 3000  
Move MyGroup {150, -800}  
As a second example, if you wanted to change the cruise velocity without  
changing the end-position, you write:  
MyGroup.StartType = IMMED  
Move MyGroup {150, -400} abs=1  
Sleep 3000  
Move MyGroup {150, -400} abs=1 VCruise = 1500  
You can change the final position, cruise velocity, and final velocity of any  
executing move. Observe a few rules:  
STARTTYPE must be IMMED or SIMM.  
New and old VELOCITYCRUISE and VELOCITYFINAL must be  
positive.  
If the succeeding move changes PFINAL or VFINAL, it must remain  
possible to create the profile with the axis acceleration limits.  
6.10.5. Synchronize Multiple Axes  
The MC provides the ability to synchronize many single axis and group  
MOVEs so they all start simultaneously. This is useful when you have  
multiple axes with moves that are largely independent, but must start at the  
same time. It is also useful for coordinating a single axis with group.  
Synchronization is controlled with <axis>.STARTTYPE, and SYNCSTART.  
The feature allows you to load the motion generator with a motion command,  
but delaying the generation of motion until SYNCSTART is issued.  
134  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
For example:  
06/2005  
Groups  
Group1.StartType = SYNC  
AuxAxis.StartType = SYNC  
Move Group1 {500, 500} VCruise = 2000  
Sleep 1000  
‘Program delayed between Move Commands  
Move AuxAxis 100 VCruise = 1000  
SyncStart Group1 AuxAxis  
causes the two profiles to start at the same time.  
<axis>.STARTTYPE is overridden inside move commands so the above  
example can be done more conveniently:  
Move Group1 {500, 500} VCruise = 2000 StartType = SYNC  
Move AuxAxis 100 VCruise = 1000 StartType = SYNC  
SyncStart Group1 AuxAxis  
You can synchronize as many groups and axes as you want, including  
simulated axes. Since each SYNCSTART specifies the groups and axes it  
synchronizes, you can independently synchronize multiple sets of groups  
and axes.  
6.10.6. Clear A Pending Move  
If you have loaded a synchronized move in the motion generator and need to  
delete it, use SYNCCLEAR. For example, if you entered the following  
command in the above sequence before issuing SYNCSTART:  
SyncClear Group1  
The Group1 move is deleted. Changing GROUP1.STARTTYPE only affects  
subsequent moves. You must use SYNCCLEAR to clear pending  
synchronized moves. SYNCCLEAR has no effect once the move is  
executing. In this case, you stop the move as you would a non-synchronized  
move.  
6. 11  
VELOCITY OVERRIDE  
The MC provides the ability to speed up or slow down all motion commands.  
This can be applied to an entire machine at once, an entire group, or to  
individual axes independently. This capability is used extensively in machine  
development. You can adjust the entire machine speed with a single  
command. Because the command can be issued from the terminal, you can  
observe machine operation at a variety of speeds without modifying your  
program.  
All axes on the MC are controlled with SYSTEM.VELOCITYOVERRIDE  
(SYS.VORD). For example:  
Sys.VOSpd = 25  
immediately (if the velocity is previously greater than 25) reduces the velocity  
of all currently executing MOVEs, CIRCLEs and JOGs, as well as any  
subsequently issued commands. Since, the velocities are controlled by  
VOSPD, the acceleration and jerk rates of all axes are proportionally  
adjusted. The final positions of MOVEs are not affected.  
Use <group>.VELOCITYOVERRIDE (<group>.VORD) to override the  
velocity of a group rather than the entire machine. It is used similarly to  
SYS.VORD, except it applies only to the group. VORD can be applied to as  
many or as few groups as is desired and the amount of override specified for  
one axis is independent of the others.  
M-SS-005-03  
Rev E  
135  
 
Groups  
06/2005  
Danaher Motion  
If you use SYS.VORD and <group>.VORD simultaneously, the axis speed is  
reduced by the product of both override properties. For example:  
Sys.VOrd = 66  
GroupB.VOrd = 50  
‘Reduce entire system to 2/3 speed  
‘Reduce GroupB to 1/3 speed  
You cannot override an axis in a group. Once an axis is part of a group, it  
cannot be controlled independently.  
6.11.1.1. MOTION ASSIGNMENT  
After assignment, a generic element can be used in all motion commands as  
a representative of another, usually “real”, motion element. All activities  
performed on the generic element identically affect the “real” element.  
Common Shared Scara As Group AxNm = A1 AxNm = A2 AxNm = A3 AxNm = A4 Model = 4  
Gen_Group = Scara  
In Task1.Prg:  
‘ Scara is attached to Task1.Prg through its generic representative Gen_Group  
Attach Gen_Group  
? “Scara is attached to “ Scara.AttachedTo  
? “Initial position of Scara is “ Scara.PFb  
‘ Scara is moved through its generic representative Gen_Group  
Move Gen_Group {-300,-500,-40,0} absolute = 1  
Sleep 200  
? “Final position of Robot is “ Scara.PFb  
Detach Gen_Group  
-> Scara is attached to TASK1.PRG  
-> Initial position of Scara is {0 , 0 , 0 , 0}  
-> Final position of Scara is {-300 , -500 , -40 , 0}  
6.11.1.2. MOTION PROPERTIES  
Through assignment, a generic element acquires all properties of the  
element being assigned to it. Properties of “real” elements can be queried  
through their generic representatives.  
Gen_Axes_List[1] = A1  
While Gen_Axes_List[1].IsMoving <> 0  
Sleep 1  
End While  
Sys.Dout.1 = 1  
Changes made in properties of generic elements identically affect the  
properties in the referenced “real” elements.  
Print “Position Factor and Acceleration of A1 Before SetUp: “ A1.Pfac, A1.Acc  
‘ Set A1’s properties through Gen_Axes_List[1]  
Call AxisSetUp(Gen_Axes_List[1])  
Print “Position Factor and Acceleration of A1 After SetUp: “ A1.Pfac, A1.Acc  
-> Position Factor and Acceleration of A1 Before SetUp: 65536  
1000  
-> Position Factor and Acceleration of A1 After SetUp: 32768 1500  
136  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Compensation Tables  
7.  
COMPENSATION TABLES  
Groups allow you to control multiple axes as a single mechanism. With  
groups, the position command and feedback signals are no longer single  
values, but instead, are vectors with two or three elements. Velocity and  
acceleration no longer apply to a motor, but instead, apply to the combination  
of two or three motors moving in concert.  
Some applications require high accuracy in position, so compensate for  
mechanical inaccuracies in the system is required. The MC allows you to  
define a table of corrections for one or more axes. This table defines a  
correction to the positioned command given to the axes, depending on its  
location or other axes’ locations. This correction is achieved every SERCOS  
cycle. The compensation table is usually created by high accuracy tools and  
is then used by the MC to correct small inaccuracies. The correction can also  
take affect when the target axis is part of a group.  
7.1.1. Specification  
The compensation table is constructed from N axes, for which compensation  
is defined. The number of rows in the table will be k1*k2*….*kn, where k1  
through kn are the number of correction points defined for the axes A1  
through An, respectively. The “source” positions (in source axis position  
units) must be equally spaced and monotonously increasing, while the  
“compensations” (in target user position units) are the corrections added to  
the “target” axes.  
A compensation table 3 axes source on 3 axes target is shown below.  
The Header  
3
10  
2
“Source” axis location  
“Target” axis compensation  
1
2
3.1  
3.1  
4.5  
4.5  
0
0.9  
0.5  
0.51  
0.9  
0.2  
------------------------------  
----------------------------------  
6
1
2
3.1  
3.2  
3.2  
4.5  
4.5  
4.5  
2.0  
0
0.65  
0.5  
0.1  
0.01  
0.9  
0.9  
0.9  
------------------------------  
3.2 4.5  
------------------------------  
----------------------------------  
3.0 0.22 0.9  
----------------------------------  
6
6
1
4
3.1  
4.5  
5.0  
2.0  
0
0.2  
0.1  
0.9  
0.87  
------------------------------  
5.0  
----------------------------------  
1.2  
6
4
1
1
The value in the table is locked and calculated according to the source axis'  
PCMD and is linearly transformed. The “source” axes determine the  
correction value, depending on location. The “target” axes are corrected.  
The table has a “header” which consists of the number of axes in the table  
followed by the number of compensation points defined for each axis. The  
table can be created the MC using TARGETDATA, SOURCEDATA, and  
CREATECOMP, or can be loaded from a binary file with a .CMP extension.  
The correction takes affect when ALL the “source” axis position feedbacks  
reach the first (i.e., the minimal) value in the table. The target axes are added  
and the value calculated in the table to its current PCMD and PFB.  
M-SS-005-03  
Rev E  
137  
 
Compensation Tables  
06/2005  
Danaher Motion  
The values in the “source” columns are in absolute units, while the “target”  
values are in relative units (i.e., the value specified in the table is added to  
the current position of the axis, whether it is a geared, cammed or a regular  
axis). A value different from 0 at the beginning of the table causes a jump at  
the target axes whenever the source axes get to the minimum value  
specified in the table.  
The difference between the corrected position (COMPPCMD) and the actual  
position feedback determines the position error of the target axes. PCMD  
returns the position of the generator before correction.  
The source PFB (for example, source1.pcmd=1, source2.pcmd=3.2,  
source3.pcmd=4.5) is searched in the table and linearly transformed from the  
previous points in the table to give the correction for the target positions.  
While the source axis continues its movement along the specified zone, the  
target axes change their positions according to the table. When one of the  
sources goes beyond the max value there are no more correction added for  
any of the axes in the table (correction=0). A jump may occur.  
Correction values are assumed very small and will not cause a large jump in  
the target axis. VOSPD and PEMAX are affected by the corrected position.  
Change these values accordingly to avoid exceeding the maximum values.  
While the compensation table is active, the values of the table cannot be  
changed. After the table is created, only the “target” values can be change.  
7.1.2. Access Data  
The compensation table data is arranged in the form of following target data  
for the points for each individual axis. If there are three axes (A1, A3, A3),  
there are three (N1, N2, N3) compensation points defined. To calculate the  
index to access the table with the indexes i, j, k for A1,A2,A3, use:  
index = i + j*N1 + k*N1*N2 .  
7.1.3. Define  
The compensation table is defined as a global variable.  
Common shared comp1 as comp  
CreateComp Comp1 3 ,4, 8  
‘Creates a table with 3*4*8 number of rows and  
'6 number of columns – 3 for the source & 3 for the target.  
CompSet Comp1 A1 ,A3, A4 on A2, A6, A5  
‘Sources A1 A3 A4 and targets A2 A6 A5 respectively.  
The maximum and minimum positions of the table are set for every axis in  
the compensation table as well as a multiplier:  
Comp1.minposition[2] = 1.32  
Comp1.maxposition[2] = 4.5  
' Set the maximum value for the second axis in the table  
138  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Compensation Tables  
7.1.4. Load/Save From a File  
Another way to create a compensation table is to directly load it from a binary  
file stored on the Flash disk. The structure of the compensation file is:  
Header <number of axes> <number of points axis1> ….<number of points  
axisn> (integer 4 bytes)  
Source data <min axis1> <max axis1>…..<min axisn><max axisn> (double 8  
bytes)  
Target data target values for axis1,…….target values for axisn. (double 8  
bytes)  
The file can be created directly from Basic Moves by loading a list of values  
(arranged as described above) in a .CSV format into the MC's Flash as a  
binary file with the CMP extension (see LOADCOMPDATA and  
STORECOMPDATA in the SERVOSTAR® MC Reference manual).  
7.1.5. Set and Query Values  
While the comensation table is not active, you can change a specific target  
value.  
Comp1.targetdata[1][23] = 3  
‘ Set a new compensation value of index 23 of Axis1  
?Comp1.sourcedata[2][24]  
‘ Read the source value index 23 of Axis1  
7.1.6. Activate  
After defining the correction table turn it ON/OFF with COMPACTIVE.  
Before activating, a check is performed to insure that the table is valid (the  
points are evenly spaced and increasing). After validation and enabling the  
target axis, positions of the target axes are corrected using the value  
calculated from the compensation table. If a target axis is disabled, the  
correction takes effect only after the axis is enabled.  
A jump may occur when the compensation procedure starts  
from a point other than the start point of the table. A jump  
may also occur if the compensation process is disabled  
before reaching the end of the table.  
NOTE  
7.1.7. Query Actual Positions  
The actual positions are return by COMPPCMD and COMPPFB. These  
properties can be operated as the master source for a slave – geared or  
cammed. PCMD and PFB return the command and feedback positions  
without compensation.  
7.1.8. Multi-Dimensional Correction  
In the following example, the correction is performed on several axes. In the  
described system, there are three axes (X, Y, Z). The X, Y, Z position  
corrections are determined according to the location of the X, Y, and Z axes.  
M-SS-005-03  
Rev E  
139  
 
Compensation Tables  
06/2005  
Danaher Motion  
The table is composed from 4, 9, 3 entries for X, Y, Z axes, respectively.  
Common shared comp1 as comp  
‘This declares a table in the system.  
CreateComp comp1 4 ,9, 3  
Comp1.minposition[1] = 0.1  
Comp1.maxposition[1] = 9  
Comp1.minposition[2] = 1.1  
Comp1.maxposition[2] = 2  
‘Setting min for the X  
‘Setting max for the X  
‘Setting min for the Y  
‘Setting max for the Y  
‘Setting min for the Z  
‘Setting max for the Z  
‘Declare before target data definition  
‘Setting the target  
Comp1.minposition[3] = 3  
Comp1.maxposition[3] = 3.12  
CompSet comp1 ax1 ,ax2, ax3 on ax1 ,ax2, ax3  
Comp1.TargetData[1][1] = 0.01  
Comp1.TargetData[3][3*9*4] = 0.02  
Comp1.CompActive=1  
‘Setting the target  
From now on, any movement on any of the axes in the table generates  
compensation.  
140  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
PHASER  
8.  
PHASER  
The purpose of PHASER is to amplify or attenuate the master input value  
before entering the cam table or before multiplying by the gear ratio.  
The master - slave connection is achieved either by a cam table or through  
gearing. A typical problem in camming is an offset in the master position that  
has to be compensated for before translating the value with a cam table.  
PHASER adds a correction to the master position. This avoids unexpected  
jumps at the slave position. By immediately adding the maximum correction  
value, there is a dynamically computation of the correction from zero to the  
maximum value.  
Master  
Position  
CAM Table  
Slave Position  
+
Phaser  
Several slaves can be connected to the same master, but the position  
correction is set per slave. PHASER is a slave command and its effects do  
not harm other slaves connected to the same master. Directly disconnection  
of the slave (SLAVE = OFF) automatically stops PHASER.  
8.1.1. Profiler  
PHASER is a type of MOVE, so all the command’s rules and limitations are  
imported. As an input, PHASER gets the maximum offset added or  
subtracted from the master position. The offset value is equivalent to the  
target position of MOVE. The rate at which the offset changes is determines  
by the profiler. Similar to MOVE, the profiler is calculated according to the  
slave’s motion properties (ACCELERATION, DECELERATION and JERK).  
All changes in these values must be performed in the nodal context so the  
slave‘s property definitions are not effected.  
Comparing PHASER and MOVE:  
Properties  
Element  
Position  
MOVE  
Axis or group  
Target  
PHASER  
Slaved axis only  
Maximum offset  
Ratio factor  
None  
Translation factor between master units  
and slave units  
Kinematics properties  
All  
All  
STARTTYPE  
All types  
All types (special relevance is  
IMMEDIATE)  
M-SS-005-03  
Rev E  
141  
 
PHASER  
06/2005  
Danaher Motion  
8.1.2. Execute  
PHASER is a slave command, although it acts on the master signal. In the  
command (like MOVE), the slave axis and offset value are essential. With  
PHASER, there is a new factor ratio that translates between slave and  
master units. The additional properties that can be determined are the  
smoothness of change, profiler type, STARTTYPE and kinematics.  
A1.mastersource = a2.pcmd  
A1.slave = CAM  
Phase a1 10 ratio = 1 ‘ slave and master has the same units  
8.1.3. Cancel  
PHASER can be divided into two stages: the convergence and constant  
stages. Stopping the convergence stage is by a special stop command. The  
value reached at the end of stopping is the maximum offset that is added,  
instead of the original offset value. The maximum offset value is queried with  
MAXIMUMOFFSET (see the SERVOSTAR® MC. Reference manual).  
To cancel the second stage, where the offset reaches its final value, insert a  
new PHASER with a complementary correction value.  
StopPhase a1 ratio = 1 ‘ slave and master has the same units  
8.1.4. Serial PHASER  
PHASER is inserted into the movements’ buffer. During the convergence  
stage of PHASER, no other movements are allowed. A new movement or an  
additional PHASER is held until the maximum offset is reached. Executing a  
new motion during the convergence stage can be accomplished only with  
STARTTYPE=IMMEDIATE. You can trace the convergence stage with  
ISMOVING (like tracing other type of movements (see the SERVOSTAR®  
MC. Reference manual).  
142  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
GENERIC ELEMENTS  
9.  
GENERIC ELEMENTS  
Writing complex multi-axis applications requires high level software  
organization. Avoid code repetition by encapsulating blocks of code into  
functions or subroutines. Code blocks of setup or query properties, which  
can be applied for all (or at least several) groups or axes in the system, and  
can be assembled into functions and subroutines. For example, if there are a  
number of identical motors in the system, their setup is the same. Write the  
following lines only once, instead of repeating them for each axis:  
A1.PFac = 0x8000  
A1.VFac = A1.PFac/1000  
A1.AFac = A1.VFac/1000  
A1.JFac = A1.AFac/1000  
A1.VMax = 290  
A1.AMax = 1500  
A1.DMax = A1.AMax  
A1.Acc = A1.Amax  
A1.Dec = A1.DMax  
Another example is writing common procedures as subroutines or functions  
that can later be applied in any system independently of how many axes or  
groups are defined. For example, switching on an output when an axis  
reaches its target:  
While A1.IsMoving <> 0  
Sleep 1  
End While  
Sys.Dout.1 = 1  
9. 1  
ELEMENTID  
Depending on the system configuration, the MC can have several axes or  
groups defined. These motion elements are actually user interfaces of the  
system's internal memory or internal function calls. They are pointers to  
actual groups and axes.  
During system configuration (“Sys.NumberAxes = n” and group definitions),  
each axis and group receives a unique element identifier. Axes get  
successive element identifiers ranging from 1 to 32, according to axis  
number. Groups get successive identifiers ranging from 33 to 64, according  
to declaration order. You cannot change these element identifiers.  
The value of the element identifier is queried directly with ELEMENTID  
(read-only).  
SYS.NUMBERAXES = 4  
Common Shared G2 As Group AxNm = A3 AxNm = A4  
Common Shared G1 As Group AxNm = A1 AxNm = A2  
? A1.ELEMENTID  
1
? A2.ELEMENTID  
2
? G2.ELEMENTID  
33  
? G1.ELEMENTID  
34  
M-SS-005-03  
Rev E  
143  
 
GENERIC ELEMENTS  
06/2005  
Danaher Motion  
9.1.1. Declaration  
Generic elements resemble other MC-Basic variables (longs, doubles,  
strings) in declaration syntax and scope (global, static and local), as well as  
in the ability to define arrays of up to 10 dimensions.  
COMMON SHARED|DIM {SHARED} <axis_name> {[]…} AS GENERIC AXIS  
COMMON SHARED|DIM {SHARED} <group_name> {[]…} AS GENERIC GROUP  
9.1.2. Assignment  
<generic_element_name>{[]…} = <real_element_name>  
<generic_element_name>{[]…} = <generic_element_name>{[]…}  
During declaration, all generic elements receive a zero element identifier,  
which prevents their usage as motion elements prior to assignment. If an  
unassigned generic element is used, an error is returned:  
Common Shared Gen_Axis As Generic Axis  
? Gen_Axis.ElementID  
0
? Gen_Axis.VMax  
Error: 3005, "Nonexistent group or axis", Module: Motion  
Through assignment, a generic element receives the element identifier of  
another motion element, either “real” or generic, thus becoming a pointer to  
this element and acquiring all its properties.  
Gen_Axis = A1  
? Gen_Axis.ElementID  
1
? A1.VMax  
290  
? Gen_Axis.VMax  
290  
By recurring assignments, generic elements have the ability to change their  
pointed axis or group as many times as desired.  
Gen_Axis = A2  
? Gen_Axis.ElementID  
2
? A2.VMax  
360  
? Gen_Axis.VMax  
360  
The left-side (assigned) element of the assignment statement cannot be a  
“real” axis or group. It must always be a generic element.  
A1 = Gen_Axis  
Error: 7039, "Syntax Error", Module: Translator  
144  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
GENERIC ELEMENTS  
The right-side element of the assignment statement can be either generic or  
a “real”. A group cannot be assigned to a generic axis, and an axis cannot  
assign a generic group.  
Common Shared Gen_Group As Generic Group  
Gen_Axis = G1  
Error: 7067, "Wrong input type", Module: Translator  
Gen_Group = A1  
Error: 7067, "Wrong input type", Module: Translator  
Joint axes cannot be used in either sides of assignment statement.  
Gen_Group.j1 = A1  
Error: 7039, "Syntax Error", Module: Translator  
Gen_Axis = G1.j1  
Error: 7039, "Syntax Error", Module: Translator  
9.1.3. Limitations  
Generic elements cannot be printed. Arithmetic, logic and bitwise operators  
cannot be applied on generic elements.  
Generic elements cannot be used as conditions in flow control statements  
and event definitions.  
Generic elements cannot be recorded.  
Generic elements cannot be structure elements.  
Generic element cannot serve as parameters of C functions.  
Deletion of global generic element cannot be performed with DELETEVAR  
or DELETEGROUP. Hardware or software reset (RESET ALL) is required.  
Dim Shared Gen_Axes_List[32] As Generic Axis  
Gen_Axes_List[1] = A1  
Gen_Axes_List[2] = A2  
Gen_Axes_List[3] = A3  
Gen_Axes_List[4] = A4  
? Gen_Axes__List[1]  
Error: 7039, "Syntax Error", Module: Translator  
Gen_Axes__List[4] = Gen_Axes__List[1]+ 3  
Error: 7039, "Syntax Error", Module: Translator  
If Gen_Axes__List[3] > Gen_Axes__List[2] Then  
Æ Syntax Error  
DeleteGroup Gen_Group  
‘ Gen_Group is a global generic group  
Error: 7039, "Syntax Error", Module: Translator  
M-SS-005-03  
Rev E  
145  
 
GENERIC ELEMENTS  
06/2005  
Danaher Motion  
9.1.4. Functions  
Generic elements can be defined “by reference” in MC-Basic functions and  
subroutines. Axes or groups passed as arguments could be either “real” or  
generic. For example, axis setup can be encapsulated in a subroutine. In this  
example, the subroutine arguments are “real” axes:  
Sub AxisSetUp(Ax As Generic Axis)  
Ax.PFac = 0x8000  
Ax.VFac = Ax.PFac/1000  
Ax.AFac = Ax.VFac/1000  
Ax.JFac = Ax.AFac/1000  
Ax.VMax = 290  
Ax.AMax = 1500  
Ax.DMax = Ax.Amax  
Ax.Acc = Ax.Amax  
Ax.Dec = Ax.DMax  
End Sub  
Call AxisSetUp(A1)  
Call AxisSetUp(A2)  
Call AxisSetUp(A3)  
Call AxisSetUp(A4)  
An entire array of generic elements can be passed (by reference) to  
functions and subroutines. Here, the argument is generic:  
Sub AxesListSetUp(AxList[*] As Generic Axis)  
Dim i as long  
For i = 1 To Sys.NumberAxes  
AxList[i].PFac = 0x8000  
AxList[i].VFac = AxList[i].PFac/1000  
AxList[i].AFac = AxList[i].VFac/1000  
AxList[i].JFac = AxList[i].AFac/1000  
Next  
End Sub  
Call AxesListSetUp(Gen_Axes_List)  
The element type (i.e., axis or group) of an argument must match the  
function or subroutine declaration. Otherwise, a translation error occurs.  
Call AxisSetUp(G1)  
‘ G1 is a group  
-> Variable passed by reference has another type as in subroutine/function  
declaration  
Trying to define generic elements “by value” generates an error:  
Sub AxisSetUp(ByVal Ax As Generic Axis)  
End Sub  
-> Cannot pass an axis or a group by value to subroutine/function  
Joint (J) axes cannot serve as function or subroutine arguments.  
Call AxisSetUp(G1.j1)  
-> Syntax Error  
146  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
GENERIC ELEMENTS  
Generic elements can also serve as returned values of MC-Basic functions.  
Both “real” and generic elements can be assigned to returned values. For  
example, to generalize the former code, an axis-indexing function can be  
added, in which a “real” axis is assigned to the return value:  
Function JointAxisByIndex(Byval I As Long) As Generic Axis  
Select Case I  
Case 1  
JointAxisByIndex = G1.J1  
Case 2  
JointAxisByIndex = G1.J2  
End Select  
End Function  
Then, write a general loop:  
Dim A As Generic Axis  
For Index = 1 to Sys.NumberAxes  
A = AxisByIndex(Index)  
Call AxisSetUp(A)  
Next  
The generic element-returning function itself cannot be used as an argument  
since generic elements can only be passed by reference,and a function call  
is passed by value.  
For Index = 1 to Sys.NumberAxes  
Call AxisSetUp( AxisByIndex(Index) )  
Next  
-> Cannot pass a constant or a complex expression by reference to  
subroutine/function  
Joint (J) axes cannot be assigned to return values.  
Function JointAxisByIndex(Byval I As Long) As Generic Axis  
Select Case I  
Case 1  
JointAxisByIndex = G1.J1  
Case 2  
JointAxisByIndex = G1.J2  
Æ
Æ
Syntax Error  
Syntax Error  
End Select  
End Function  
M-SS-005-03  
Rev E  
147  
GENERIC ELEMENTS  
06/2005  
Danaher Motion  
9. 2  
WITH  
WITH can be given in three contexts: configuration file, terminal and task. All  
three contexts of WITH can be applied to generic elements.  
With Gen_Axis  
PFac = 0x8000  
VFac = PFac/1000  
AFac = VFac/1000  
JFac = AFac/1000  
End With  
WITH can be used on assigned and unassigned generic elements. These  
generic elements can be assigned and/or re-assigned later. This changes  
the WITH element without writing a new WITH command.  
With Gen_Axis  
? With  
GEN_AXIS  
? VMax  
Error: 3005, "Nonexistent group or axis", Module: Motion  
Gen_Axis = A1  
? VMax  
290  
Gen_Axis = A2  
? VMax  
360  
148  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Input/Output  
10.  
INPUT/OUTPUT  
The MC provides numerous types of I/O. It includes more than 40 I/O points  
as standard plus the SERVOSTAR drive includes 5 I/O points per drive. In  
addition, you can input an external encoder through any SERVOSTAR drive.  
The I/O can be extended to include PC104 cards from a variety of suppliers.  
10. 1  
STANDARD I/O  
The MC includes 23 inputs and 20 outputs as standard on the MC. These  
are accessed with the system properties DIN.1 through DIN.23 and DOUT.1  
through DOUT.20:  
? System.Din.1  
System.Dout.5 = System.Din1  
?System.Din  
System.Dout=0xfe  
For information concerning the properties of the signals that connect to these  
inputs and outputs, refer to the SERVOSTAR® MC Installatiion Manual.  
10. 2  
SOFTWARE I/O  
The MC provides virtual software I/O in addition to the standard I/O. The  
primary purpose of software I/O is to place a large group of I/O where it can  
be read from and written to as blocks in the MC's dual port RAM. Virtual  
inputs are delivered from the host over DPRAM where virtual outputs are  
stored in the DPRAM and retrieved by the host. This is much faster than  
reading or writing individual I/O points one at a time. This allows efficient  
communication between a machine controller, such as a VB program or a  
software PLC, and the MC program. For more information about virtual  
software I/O, refer to the SERVOSTAR® MC API Manual.  
10.2.1. Bit-oriented Software I/O  
Software I/O is used in the MC program just like standard I/O. Standard  
inputs are accessed with SYSTEM.DIN.1 through DIN.23, and virtual inputs  
are accessed with SYSTEM.VIN.1 through VIN.32. Standard outputs are  
accessed with SYSTEM.DOUT.1 through DOUT.20, and virtual outputs are  
accessed with SYSTEM.VOUT.1 through VOUT.32. You can use software  
I/O to start events just as with standard I/O. Programmable limit switches can  
use software outputs just as with standard outputs. Here is an example:  
OnEvent SoftwareInputEvent System.VIn.1 = ON  
System.VOut.1 = OFF  
If(System.VOut.4 = ON)  
. . .  
M-SS-005-03  
Rev E  
149  
 
Input/Output  
06/2005  
Danaher Motion  
10.2.2. Long-Word-Oriented Software I/O  
The entire word (32 bits) of software input and output is accessed when a bit  
position is not included in the reference to the input or output variable. So the  
following statement is valid:  
System.VOut=System.VIn  
This statement copies the virtual software input to the output. The physical  
input and output variables are used in this manner. Be careful when  
assigning virtual I/O to physical I/O because there are fewer physical bits  
than there are virtual bits. There are only 20 bits of physical output, but the  
virtual output variable can have 32 bits.  
10. 3  
PLS (PROGRAMMABLE LIMIT SWITCH)  
A Programmable Limit Switch (PLS) monitors position feedback on any axis,  
real or simulated. A PLS offers more flexibility than a limit switch, as it allows  
many trip points and can be reconfigured on-the-fly. A PLS toggles the state  
of a specified system output when an axis position reaches any of the  
defined positions of the PLS. Some of the features of a PLS are:  
Multiple position specifications.  
Multiple PLSs per axis  
PLS pattern repetition  
Position hysteresis  
Enabling and disabling of PLSs  
The system output may be digital or soft (fast data)  
PLS positions are defined in an array that allows you to change individual  
values of PLS positions. This array must be increasing monotonic. There is  
no limit of the number of positions or PLSs that can be defined.  
The initial output polarity is specified with PLSPOLARITY. The output state  
is set when the PLS is enabled.  
10.3.1. Enable and Disable  
After being defined, a PLS is disabled (output pattern is not generated). The  
output is set when the PLS is enabled. The output is set to the defined initial  
state.  
PLS properties are changed only when the PLS is disabled. Each enabled  
PLS requires CPU resources. Conserve those resources by disabling the  
unused PLS(s). PLSENABLE controls the status of the PLS:  
MyPLS.PlsEnable = ON | OFF  
PLSENABLE queries the status of a PLS:  
?MyPls.PlsEnable  
if(MyPLS.PlsEnable = OFF)  
. . .  
or drives events:  
EventOn MyEvent MyPLS.PlsOutput = ON  
150  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Input/Output  
10.3.2. Switch Positions  
The basic mechanism of the PLS is the switch position(s) where the PLS  
output changes state. The figure belows shows a PLS output with one switch  
position at 100.  
More switch positions can be added. To have the PLS in the above example  
turn back off at 200, simply add a second position at 200 as shown below:  
You can add any number of positions. For example, to extend the above  
example to turn back on at 400 and off again at 600, add positions 3 and 4  
as 400 and 600 as shown below:  
M-SS-005-03  
Rev E  
151  
 
Input/Output  
06/2005  
Danaher Motion  
There is no explicit limit to the number of positions you can have in a PLS,  
but the PLS positions must be increasing monotonic (Position2 must be  
greater than Position1, Position3 must be greater than Position2, etc.).  
10.3.3. Repetition Interval  
PLSREPEAT allows you to repeat the same PLS after a fixed number of  
counts. For example, the figure below shows a PLS that turns on at 0, off at  
10 and has a PLSREPEAT value of 100:  
10.3.4. Polarity  
PLSPOLARITY allows you to control the polarity of the PLS output. The  
initial polarity may be specified as 1 or 0, indicating that the output is set to 1  
or 0 after the PLS is enabled and when the axis is located between the first  
and second PLS positions. If the axis position (when the PLS is enabled) is  
not located within this segment, the output polarity is set to 0 or 1, according  
to the current position so that when the axis reaches the first segment, the  
output polarity is as indicated. The default value for polarity is 0.  
10.3.5. Hysteresis  
The MC allows you to apply hysteresis around switch points. Hysteresis  
provides a margin in the switching between PLS positions to accommodate  
noise in the PLS axis. Set the hysteresis greater than the noise on the axis,  
(typically, 5 or 10 counts of encoder is sufficient, less is required for resolver  
systems). If you have a hysteresis of 0.01 position units, each transition of  
PLS position is moved forward 0.005 units for positive motion and backward  
0.005 units for negative motion. If the axis driving the PLS is stopped directly  
on a PLS position and the inherent noise on the axis is less than the  
hysteresis, the PLS state does not change due to this noise.  
10.3.6. Enable and Disable  
PLSENABLE enables or disables the PLS(s). After being defined, a PLS is  
disabled. The output is fixed when the PLS is enabled. The PLS output is set  
to the defined initial state when the PLS is enabled.  
152  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Input/Output  
10.3.7. PLS Output State  
Query the digital output associated with the PLS to query the state of the  
PLS output. For example, assume the PLS output is assigned to  
SYSTEM.DOUT.1. To determine the output state of the PLS, query the state  
of SYSTEM.DOUT.1:  
-->?Sys.Dout.1  
0 | 1  
10.3.8. Set Up  
Step 1  
Declare the PLS with Common Shared <var> as PLS in Config.Prg or at the  
terminal. You must name the PLS, specify the axis that drives the PLS, and  
name an output to be controlled by the PLS. For example:  
Common Shared MyPLS as PLS A1 System.Dout.1  
sets up MyPLS as a PLS driven by axis A1 connected to SYSTEM.DOUT.1.  
The output can be a digital output (SYSTEM.DOUT.1 through DOUT.20) or it  
can be one of the virtual outputs (SYSTEM.VOUT.1 through VOUT.32).  
After the Common Shared <var> as PLS executes, the PLS is disabled.  
Properties of the PLS are set as:  
A single PLS position exists at 0.  
The initial output polarity is 1.  
PLSREPEAT is set to 0.  
The hysteresis is set to 0.  
These properties may be set explicitly, as long as the PLS remains disabled.  
You can check which output is associated with a given PLS using  
PLSOUTPUT.  
Step 2  
Create the PLS data structure and define PLS positions. The number of  
defined positions is not explicitly limited. A call to CREATEPLSDATA  
creates an array of n positions that stores the position data. The array is 1-  
based and an error is generated if you attempt to access an index outside of  
the array bounds. For example:  
CreatePLSData 4 MyPLS  
MyPLS.PLSPosition[1] = 1000  
MyPLS.PLSPosition[2] = 1100  
As a short form, you can use PPOS in place of PLSPOSITION:  
MyPLS.Ppos[3] = 2000  
MyPLS.Ppos[4] = 2200  
You cannot change PLS positions when the PLS is enabled. Position values  
must be increasing monotonically.  
Step 3  
Set the polarity. PLSPOLARITY defaults to OFF, indicating the PLS state  
should be OFF after the first position. Change PLSPOLARITY to ON to  
invert the state.  
MyPLS.PLSPolarity = ON  
Change PLSPOLARITY only if the PLS is disabled.  
M-SS-005-03  
Rev E  
153  
 
Input/Output  
06/2005  
Danaher Motion  
Step 4  
Set PLSREPEAT. If you want the PLS to repeat, set the value of  
PLSREPEAT to a non-zero, positive number. For example, to have the PLS  
repeat every 10,000 position units, enter:  
MyPLS.PLSRepeat = 10000  
PLSREPEAT defaults to 0, indicating that there is no repetition. Change  
PLSREPEAT only when the PLS is disabled.  
Step 5  
Step 6  
Set PLSHYSTERESIS, if the application requires it. Hysteresis is only  
necessary if the system does stop on or near a PLS position. Normally, a  
PLSHYSTERESIS of 5 or 10 counts of encoder (converted to position units)  
or 2 or 3 counts of resolver resolution is sufficient.  
MyPLS.PLSHysteresis = 0.01  
Enable the PLS. Enter:  
MyPLS.PLSEnable = ON  
There are a few other PLS functions you may need:  
Change Polarity The default output state of a PLS is 0. Change this  
initial state by modifying PLSPOLARITY.  
MyPLS.PLSPolarity = 1  
The PLS must be disabled when changing this  
setting.  
Query the Name Query the name of the axis driving the PLS:  
? MyPLS.PLSAxisName  
returns the axis associated with the PLS (A1).  
Disable the PLS  
Delete a PLS  
Disable the PLS. For example:  
MyPLS.PLSEnable = OFF  
You must disable a PLS to change PLS properties.  
Disabling a PLS also helps conserve CPU  
resources.  
Delete a PLS to remove it from the system only  
when the PLS is disable and there are no tasks in  
memory. For example:  
DeletePLS MyPLS  
10. 4  
EXTERNAL ENCODERS  
The MC supports external encoders (encoders not connected to an axis  
controlled by the MC). These encoders are connected to the system using  
the external encoder input of any SERVOSTAR drive in the system. You can  
access the encoder periodically with:  
? IDNValue(<Axis>.DriveAddress, 53, 7)  
‘Query external encoder position  
154  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Input/Output  
If you are using the encoder for master/slave operation or in a way that  
requires the value of the signal be updated to the MC every SERCOS cycle,  
you must configure the telegram for that axis as Telegram type 7. You also  
must specify that external position must be included in the telegram. This  
command is only available when in communication phase of 2 or higher.  
10. 5  
PC104  
If you need more I/O than the 23 digital inputs and 20 digital outputs that the  
MC provides, there is an optional PC104 bus. This lets you install PC104-  
compatible cards to provide additional I/O ports. Because the PC104 bus is  
an extension for the MC, this configuration is often called a mezzanine bus.  
The MC supports the full PC104 mechanical specification for as many as two  
PC104 cards. Adding these cards generally increases, by one, the number of  
slots taken by the MC. The MC supports a subset of the electrical  
connections of PC104, but the subset is sufficient to accommodate nearly all  
PC104 I/O cards. Refer to the SERVOSTAR® MC Installation Manual for  
more details concerning which pins are supported.  
10.5.1. Configuring PC104 Cards  
You must configure the PC104 cards for memory and I/O space. See the  
manufacturer’s manual for your particular PC104 carde.  
All PC104 cards used on the MC which are memory mapped, must be  
mapped into the MC’s memory without causing conflict. If you are using two  
PC104 cards, you must be careful not to overlap the memory spaces of  
these cards.  
All PC104 cards used on the MC which are I/O mapped, must be mapped  
between 0x100 to 0xFFFF. Address ranges: 0x300 through 0x3ff and 0x2f8  
through 0x2ff are not available. If you are using two PC104 cards, you must  
be careful not to overlap the I/O spaces of these cards. Do not use ranges  
0x300 through 0x3ff and 0x2f8 through 0x2ff, even though they are not  
protected by the software.  
The MC does not support interrupts from PC104 cards.  
10.5.2. Installation  
To install your PC104 card:  
1. Power down your unit.  
2. Always use proper static handling procedures.  
3. Mount the cards.  
4. Install stand-offs.  
M-SS-005-03  
Rev E  
155  
 
Input/Output  
06/2005  
Danaher Motion  
10.5.3. Commands  
The MC supports PC104 with memory and I/O instructions. For further  
information on these commands, refer to the SERVOSTAR® MC Reference  
Manual.  
If you are using memory-mapped PC104 cards, you will need the memory  
access commands, PEEK and POKE. The valid memory address range for  
PEEK is 0xA0000 through 0xDFFFF. The valid memory address range for  
POKE depends on the hardware version of the MC card.  
For the ISA-Bus card, the valid memory address range for POKE is  
0xA0000 to 0xCFFFF and 0xDA000 to 0xDFFFF.  
For the PCI card, the valid memory address range for POKE is  
0xA0000 to 0xC7FFF and 0xDB000 to 0xDFFFF.  
PEEKB transfers byte-wide (8-bit) data from the PC104 memory  
bus to a variable.  
PEEKW transfers word-wide (16-bit) data from the PC104  
memory bus to a variable.  
POKEB transfers byte-wide (8-bit) data to the PC104 memory bus.  
POKEW transfers word-wide (16-bit) data to the PC104 memory  
bus.  
If you are using I/O-mapped PC104 cards, you need INP and  
OUT.  
INPB transfers byte-wide (8-bit) data from the PC104 I/O bus to a  
variable.  
INPW transfers word-wide (16-bit) data from the PC104 I/O bus to  
a variable.  
OUTB transfers byte-wide (8-bit) data to the PC104 I/O bus.  
OUTW transfers word-wide (16-bit) data to the PC104 I/O bus.  
156  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Error Handling  
11.  
ERROR HANDLING  
Error handling is the method used to react to and process fatal and non-fatal  
errors that occur during the operation of the MC. You can handle non-fatal  
faults, but not fatal faults. Fatal faults cause a WatchDog timer to be  
triggered. All errors have corresponding default actions to be taken when  
they occur.  
There are three contexts in which an error can occur and be handled: task,  
system, and terminal. The following definitions will help you while reading  
through this chapter:  
Term  
Definition  
Internal error action  
Immediate action taken by the system software when  
an error occurs. This action cannot be turned off or  
bypassed.  
Default System error action Action taken by the system according to the context  
and severity of the error if the user does not handle the  
error. All default system error actions can be bypassed  
by defining error handler functions.  
Synchronous error  
Error caused by the user task and detected by the  
interpreter. This type of error is associated with a  
specific line of program code in the user-defined task.  
Examples include division by zero and out of range  
parameters in a MOVE command. The task that  
caused the error is stopped.  
Asynchronous error  
An error caused by the user task not associated with a  
specific line of program code. Examples include  
following error and motion overspeed.  
11. 1  
CONTEXT  
When an error occurs in the MC system, it occurs in one of three contexts:  
task, system or terminal. It is important to recognize the differences among  
these three since the action taken by the system varies, depending on the  
context.  
11.1.1. Task Context  
Errors occurring as a result of an executing task take place in the task  
context. Asynchronous and synchronous errors occur in this context. A  
specific line of code causes synchronous errors. An asynchronous error that  
occurs in a task is not associated with a particular line of program code. A  
good example of an asynchronous error caused by a task is a following error.  
This occurs due to a difference between commanded position and actual  
position. This error may occur when an element being commanded to move  
comes up against a mechanical obstacle. The following figure shows the  
process flow that occurs in the task context.  
M-SS-005-03  
Rev E  
157  
 
Error Handling  
06/2005  
Danaher Motion  
During the internal error action, the synchronous error is logged in the MC  
and the task is idled. The default system error handler stops all motion and  
all attached tasks.  
In the figure above, there are two mechanisms for trapping and dealing with  
errors: OnError and Try/Finally blocks. These two error-handling  
mechanisms allow you to write your program to respond to errors.  
11.1.1.1. ONERROR  
The OnError block is handled like an event handler. An event handler lets  
your program respond to events. The OnError block allows your program to  
catch errors. OnError overrides default system error action if OnError traps  
error. Main program execution is stopped while the OnError block is  
executing and must be resumed if that is desired. An example of this is  
shown later in this section.  
Add an OnError code block to your program between the Program and End  
Program section of your program.  
The number of Catch statements in an OnError block is not explicitly limited.  
Catch Else may optionally be used. If you want a task to resume after an  
error has occurred, use CONTINUETASK.  
You can use GoTo within the error handler. However, because OnError  
interrupts the main program, you cannot use GoTo to branch outside the  
error handler. You cannot place an OnError block in the middle of program  
flow. The scope of OnError is that of the task withing which it is contained. It  
only handlers errors that occur within that task.  
158  
Rev E  
M-SS-005-03l  
Danaher Motion  
06/2005  
Error Handling  
11.1.1.2. TRY/FINALLY  
Unlike an OnError block, the Try/Finally block may appear anywhere in the  
main program section of the task. It can be used to take specific action with  
relation to a particular area of your program code. This type of error handler  
block only traps synchronous errors in the task context. The block is started  
using the Try keyword and is terminated with the End Try keyword.  
Try blocks can be nested. The program lines between the line causing the  
error and the matching catch statement are skipped. The interpreter tries to  
trap an error starting with the innermost catch statement. If there is no  
matching catch statement, the error is handled as a regular synchronous  
error. Errors trapped inside the Try block are not logged. The Finally  
statement is executed only if an error occurred and was caught inside the  
Try block.  
11.1.2. System Context  
System context is the lowest level of the three contexts. It refers to errors not  
directly related to specific tasks. Errors that occur in this context affect all  
running tasks. The default system error handler processes these errors.  
Examples of system context errors include Floating Point Unit errors, CPU  
errors, SERCOS communication errors and errors that occur on motion  
elements not attached to specific tasks.  
11.1.2.1. ONSYSTEMERROR  
OnSystemError traps and processes all errors in the system context. It is the  
upper-level of the hierarchical error processing structure formed by the  
combination of Try, OnError and OnSystemError. OnSystemError may be  
written in the body of any task, but only one instance may exist in the system  
at any time. It traps both synchronous and asynchronous errors in all tasks,  
as well as errors that occur within the context of the system.  
A system error is not associated with a specific task. An example of a system  
error is a position following error that occurs due to some external force  
being applied to an axis not attached to a task. When an error is trapped, the  
specified error processing code runs and the task is stops. The task is in  
state 4. It is possible to continue task execution by explicitly entering  
CONTINUETASK within the error processing code, but the task continues  
only after the error has been corrected.  
OnSystemError traps errors not specifically trapped by Try or by OnError. It  
then executes either an orderly shutdown of the system, or an orderly  
recovery procedure.  
11.1.2.2. ERRORPRINTLEVEL  
SYSTEM.ERRORPRINTLEVEL controls which types of system errors are  
printed to the message log window. There are four levels of system errors:  
fatal faults, errors, and notes.  
0 (SILENTLEVEL) – Notes, errors, and fatal faults are not printed.  
1 (FAULTLEVEL) – Notes and errors are not printed. Fatal faults are printed.  
2 (ERRORLEVEL) – Notes are not printed. Errors and fatal faults are printed.  
3 (NOTELEVEL) – Notes, errors, and fatal faults are printed.  
M-SS-005-03  
Rev E  
159  
 
Error Handling  
06/2005  
Danaher Motion  
SYSTEM.ERRORPRINTLEVEL only affects printing to the message log  
window. Fatal faults and errors continue to be logged, and can be viewed  
using ?ERRORHISTORY. ERRORPRINTLEVEL applies only to  
asynchronous errors. Synchronous errors are not affected.  
11.1.3. Terminal Context  
Terminal context is similar to task context, as commands are processed  
similarly. The error action is different from a task as there is no interpreter to  
be idled when an error occurs.  
11. 2  
WATCHDOG  
The MC provides a WatchDog timer to help determine if the host PC  
connection is operational. To use the WatchDog, configure the MC to expect  
WatchDog messages. During normal operation, the host PC must reset the  
WatchDog timer before the end of the specified interval to avoid a WatchDog  
fault.  
Normally, the WatchDog is cycled indirectly through fast I/O. WDCYCLE  
directly resets the WatchDog, but this is not recommended because it  
requires 15 to 20 ms per WatchDog cycle. Given that WatchDog timers are  
often reset every 100 ms, this implies that the WatchDog function could  
consume 15 to 20% of the MC processor time. Events triggered by the fast  
I/O can avoid this problem. The following commands configure the MC to  
expect WatchDog cycles:  
WDINIT establishes a WatchDog timer. When selecting the reset time, it  
should be long enough that the WatchDog function does not consume undue  
amounts of processing time. The time also should be short enough so that if  
the communication link between MC and host is lost, the MC can shut the  
axes down in a timely manner. Different applications require different times,  
but 100 to 1000 ms (<Cycles> = 5 to 50) are commonly used.  
WDCYCLE cycles the WatchDog timer.  
WDDELETE deletes the WatchDog timer. WDDELETE is seldom used in  
normal operation because once a WatchDog timer is started, it is seldom  
stopped intentionally.  
160  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Error Handling  
11.2.1. WatchDog Setup  
To set up the MC to enable the WatchDog, follow these steps:  
1. Create a new task solely for the WatchDog. Use BASIC Moves with  
File, New.  
2
3
4
5
Define a local variable as a Long. For the example below, we use  
MyVar.  
Initialize the WatchDog timer in the main program. Store the return  
value of the initialization step in the local variable from Step 1.  
Write an event inside the task to reset the WatchDog timer. The event is  
fired with fast I/O (SYSTEM.VIN.1 to 32).  
Set the task to run infrequently so it does not consume more  
computational resources than necessary. The following example  
demonstrates a WatchDog timer task:  
Dim Shared MyVar as Long  
Program  
‘Event which runs once for each WatchDog cycle  
OnEvent WDevent System.Vin.1 = 1 ScanTime = 4 ‘Check every 4th cycle  
WDCycle(MyVar)Cycle the WatchDog  
System.Vin.1 = 0  
End OnEvent  
‘Reset the WatchDog bit  
EventOn WDEvent  
MyVar = WDInit(5)  
WDCycle(MyVar)  
While 1 = 1  
‘Enable the Wdog Event  
‘Set Wdog time for 5 Wdog cycles or 100 ms  
‘You must cycle the Wdog once to begin  
‘Infinitely loop so event will be active  
‘Use sleep to conserve CPU time  
Sleep 1e6  
End While  
End Program  
With this example, the WatchDog must be reset every fifth cycle (every 100  
ms) to avoid a fault.  
11.2.2. Cycle the WatchDog  
The last step in using the MC WatchDog is to issue watch cycle commands  
from the host PC. These are issued more frequently than the specified  
maximum cycle time in WDINIT. For example, if the maximum cycles are  
specified as 5 (equivalent to 100 ms), reset the WatchDog every 50 or 60  
ms. In Visual Basic, this is as simple as setting the fast I/O to 1 based on a  
50 ms timer.  
11.2.3. Reset the WatchDog  
You can reset the WatchDog directly from the host PC using WDCYCLE  
This is simpler than the method presented above because you need not  
generate a task. However, this is not normally recommended because it is  
much slower than the fast-I/O method as it requires 15 to 20 ms to pre-  
compile commands issued directly from the API to the MC. However, should  
you decide to use the direct method, you need only use the following steps  
directly from the API:  
1. Create a global variable.  
2. Initialize the WatchDog timer.  
M-SS-005-03  
Rev E  
161  
 
Error Handling  
06/2005  
Danaher Motion  
3. Reset the WatchDog with an API command based on a timer. Run the  
following Visual BASIC code once upon initialization:  
Include KMAPI.BAS in your project  
KMExecuteCmd(MC, “MyVar=WDInit(5)”)  
KMExecuteCmd(MC, “WDCycle(MyVar)”)  
4. Run the following Visual BASIC code from a timer set for 50 ms:  
KMEXecuteEmd(MC, “WDCycle(MyVar)”)  
11. 3  
UEA (USER ERROR ASSERTION)  
The purpose of User Error Assertion (UEA) is to let the application developer  
extend existing system (internal) errors. You can define application  
(additional) errors (exceptions) so the system handles them like it would its  
own. The application exception may be trapped with TRY/Catch, OnError or  
OnSystemError. Unprocessed application exceptions are treated as any  
known internal error. The system reacts by stopping the task/motion  
according to exception severity. The system provides a range for the  
application errors and prevents an overlap between internal and application  
error codes. The application is able to define an exception name and ASCII  
message to print. User exceptions start from number 20001 and you are able  
to define 1000 exceptions. UEA may have “Note” and “Error” seventies.  
11. 4  
EXCEPTIONS  
11.4.1. Declaration  
The application developer can declare an exception and supply the  
corresponding error message. An exception may be declared on the both  
system and task levels. Declaration of exceptions at the subroutine level is  
not supported. User exceptions are divided into two sub ranges 20001-  
20499 and 20500-20999. Applications developed may use the first sub range  
for explicit definitions of exception number (see below example), while the  
second sub range is used by the system for automatic assignment of  
exception numbers. Double use of the same exception number is forbidden  
as the System gives an error. The exception can be defined with the  
following declaration:  
Dim|common shared <name> as <severity> <ASCII message> [<num>]  
where:  
Parameter  
Severity  
Description  
Note/Error  
Remarks  
Num  
Integer number 20001..20499, which will  
be assigned to exception. This parameter  
is optional, if omitted the system will assign  
some value in range 20500..20999. MC will  
report an error if number given by the  
application developer is already used.  
ASCII text that will appear at error history  
and error message.  
(optional parameter)  
ACII Msg  
For example:  
Dim shared Error1 as Note ”Emergency” 20001  
Dim shared Error2 as Note ”Fault” 20002  
Common shared MyNote as Note ”My Note”  
Common shared MyError as Error ”My Error”  
162  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Error Handling  
If the exception number is not specified, the system associates exceptions  
with some numeric value, which can be queried. However, the system will  
not guarantee that this value is the same from load to load. Do not make any  
assumption about this number. It is a mechanism to maintain the exception  
database.  
11.4.2. Deletion  
All exceptions declared at task level are lost when the task is killed. The  
exception declared at the system level (Common Shared) can be deleted if  
not in use – similar to numeric variables. For example:  
DeleteVar MyNote  
11.4.3. Assertion  
The application asserts (throws) an exception from within an application. The  
system behaves like it is a regular (predefined in firmware) application error.  
You are able to catch application exception with TRY/Catch, OnError or  
OnSystemError.  
Exception assertion is possible with THROW. THROW accepts the name of  
any defined exception. Other expressions are not allowed to be arguments to  
THROW.  
The scope of THROW is not limited. It can be executed inside of Try, Catch,  
Finally, outside the Try block in OnError and OnEvent. For example:  
Dim shared LimitError as Error msg= ”Over travel”  
Program  
Attach a1  
Jog a1 100  
While 1  
‘check the axis position and assert and error,  
‘the system should stop the task and motion  
If a1.pfb > 1e10 Then  
Throw LimitError  
End If  
End while  
End program  
Another example:  
Dim shared Error1 as Error msg= ””  
‘ no message  
Program  
Try  
‘ check Input #1 and do not continue  
‘ if it’s “1”  
If Sys.din.1=1 Then  
Throw Error1  
End if  
Move a1 1e3  
Catch Error1  
Print “I/O error”  
End try  
End program  
M-SS-005-03  
Rev E  
163  
 
Error Handling  
06/2005  
Danaher Motion  
11.4.4. Log  
User exceptions are printed and logged according to existing rules: A note is  
printed but not logged, Unhandled errors are printed and logge, etc. In  
addition, the application developer can log an error without any error  
handling. Application exception is printed and logged but neither task  
generated such an exception nor motion associated with that task stops.  
User exceptions are logged according to the existing rules. Errors and faults  
are printed and logged while notes are only printed.  
You can use LOGGER to lsend exceptions directly to the logger, bypassing  
any error handler. The exception can be logged with the following command:  
Logger <Exception name>  
For example:  
Logger MyError  
11.4.5. Query  
You can query exception numbers and messages, but changing these  
parameters is forbidden. The exception number and text are set during  
exception definition and stay constant until the exception is deleted or the  
defined task is killed. For example:  
Æ?MyError.num  
20007  
Æ?MyError.Msg  
My Error  
11.4.6. Print  
Exceptions are printed and logged with timestamp, task name, and line  
number, severity and other error attributes. In contrast to internal  
(predefined) errors, an exception number is not constant and may vary from  
time to time (from task load to task load). Also, the error log may keep  
exceptions from tasks not in memory and there is no way to associate an  
exception number with its message. The error logger keeps exception  
messages in RAM and files.  
11.4.7. Limitations  
1. VARLIST and SAVE do not show exceptions.  
2. WATCH is not supported.  
3. Arrays of exceptions not supported.  
4. Definition of exceptiosn in subroutines is not supported.  
5. Arithmetical operations are not supported for exceptions. Comparing  
exceptions makes sense only if the application developer explicitly  
gives exception numbers. If the MC assigns exception numbers, the  
result is unpredictable.  
6. The library can assert an exception defined as DIM SHARED or  
COMMON SHARED. Realize that exceptions defined in the library do  
not have constant numbers (if numbers were not assigned explicitly).  
164  
Rev E  
M-SS-005-03l  
 
Danaher Motion  
06/2005  
Appendix A  
APPENDIX A  
SAMPLE NESTING PROGRAM  
Dim Shared I1 As Long  
Dim Shared I2 As Long  
Dim Shared I3 As Long  
Dim Shared I4 As Long  
Dim Shared I5 As Long  
Program  
Do  
If I1=0 Then  
If I2=0 Then  
While I3<5  
Print ""  
'First If...Then  
'Second If...Then  
'First While  
Print "*******I3=";  
?I3  
I3=I3+1  
For I4=1 to I3 Step 2  
Print "I4=";  
?I4  
'First For statement  
For I5=I4 to 10  
Print "I5=";  
?I5  
Sleep 50  
Next I5  
'Second For statement  
'To slow task down  
Next I4  
End While  
End If  
Else  
I3=0  
While I3 <=5  
I3=I3+1  
'Second While  
Select Case I3  
Case 1  
Print "I3=1"  
Case 2  
Print "I3=2"  
Case 3  
Print "I3=3"  
Case Else  
Print "I3 is not 1, 2, or 3"  
End Select  
End While  
End If  
I1=I1+1  
Loop Until I1>1  
End Program  
M-SS-005-03  
Rev E  
165  
   
Appendix A  
06/2005  
Danaher Motion  
SUBROUTINE EXAMPLE  
Dim Shared var_x As Double  
Dim Shared var_y As Long  
Dim Shared array_z[2][2] As Double  
Dim Shared rows As Long  
Dim Shared columns As Long  
Program  
REM initialize variables  
var_x=29.3172  
var_y=5  
rows=2  
colums=2  
array_z[1][1]=125.6  
REM specification of program  
<optional code>  
CALL OrdinarySubroutine(var_x,var_y)  
<more code>  
CALL MatrixMath(array_z[1][1],rows,columns)  
<more code>  
End Program  
SUB OrdinarySubroutine(param1 As Double, ByVal param2 As Long)  
REM pass param1 by Reference, param2 by Value  
REM declare local variables if any  
REM specification of subroutine  
<optional code using param1 and param2>  
End Sub  
SUB MatrixMath(matrix As Double, ByVal rows As Long, ByVal columns As Long)  
REM pass matrix by Reference, rows by Value, columns by Value  
REM declare local variables if any  
REM specification of subroutine  
<optional code using matrix, rows, and columns>  
End Sub  
166  
Rev E  
M-SS-005-03  
 
Danaher Motion  
06/2005  
Appendix A  
SAMPLE AUTOSETUP PROGRAM  
Below is an example auto setup program. This sample covers several pages.  
You do not need to understand the program in detail at this point but you  
should familiarize yourself with the structure.  
REMOVING THE SINGLE QUOTES IN THE FOLLOWING CODE CAUSES THE  
PROGRAM TO ENABLE THE DRIVES AND GENERATE MOTION COMMANDS!  
BE PREPARED FOR THE MACHINE TO MOVE!  
ENABLING THE SYSTEM WITHOUT PROPER TUNING MAY CAUSE  
UNEXPECTED MOTION! BE CERTAIN YOUR SYSTEM IS TUNED PROPERLY!  
SEE THE SERVOSTAR® MC INSTALLATION MANUAL FOR MORE  
INFORMATION.  
rem -------------------------------------------------------------  
rem TASK....: C:\Program Files\KMTG Motion Suite\BASIC  
Moves\Projects\Junk2\Junk2.prg  
rem AUTHOR..: <Name of Author Here>  
rem TIME....: <Time of Creation Here>  
rem PURPOSE.: Main Project File  
rem -------------------------------------------------------------  
rem Declare Variables Here  
Dim Shared sample_int as Long  
Dim Shared sample_real as Double  
rem -------------------------------------------------------------  
rem  
Main Task Begins Here  
rem -------------------------------------------------------------  
Program  
Attach A1  
'Attach to axes  
Call AxisSetup  
Call SercosSetup  
'Set up all axes  
'Bring up SERCOS ring  
rem  
rem  
rem  
'
Auto generated sample program starts here  
Sample program--remove single quote marks at beginning of  
lines to run program  
Sys.En = on  
'Enable the system  
'Enable Axis A1  
'
A1.En = on  
'
A1.StartType = Immediate  
Sleep 1000  
'
'Sleep one second  
Continued on next page……….  
M-SS-005-03  
Rev E  
167  
 
Appendix A  
06/2005  
Danaher Motion  
'
'
'
Sys.Motion = on  
'Allow system motion  
'Allow motion in axis A1  
'Loop 10 times  
A1.Motion = on  
For sample_int = 1 To 10  
rem  
'
Move A1 to 5 position unit(s)  
Move A1 5 Absolute=0  
'
Sleep 2000  
'Sleep two seconds  
'Sleep two seconds  
rem  
'
Move A1 back to start  
Move A1 -5 Absolute=0  
Sleep 2000  
'
'
Next sample_int  
'
Print "Sample program completed."  
'
'
Sys.Motion = off  
Sys.En = off  
'Disable motion in system  
'Disable system  
rem  
Auto generated sample program end here  
Detach A1 'Detach from axes  
End Program  
rem -------------------------------------------------------------  
rem Sercos Set-up Routine Automatically Generated by the Project Wizard  
rem -------------------------------------------------------------  
Sub SercosSetup  
rem  
If ring is not up...  
If Sercos.Phase <> 4 Then  
Sercos.Phase = 0  
'Bring the ring all the way down  
'Set baudrate to 4 Mbaud  
Sercos.Baudrate = 4  
rem  
Set Drive Addresses  
A1.Dadd = 1  
Sercos.Phase = 4  
End If  
'Bring ring all the way up  
End Sub  
Continued on next page……….  
168  
Rev E  
M-SS-005-03  
Danaher Motion  
06/2005  
Appendix A  
rem -------------------------------------------------------------  
rem Axis Set-up Routine Automatically Generated by Project Wizard  
rem -------------------------------------------------------------  
Sub AxisSetup  
If Sercos.Phase = 4 then  
A1.enable = off  
End If  
'make sure axis is disabled  
A1.PFac = 65536  
'Revolutions  
A1.VFac = A1.PFac / 1000  
A1.AFac = A1.PFac / 1000 / 1000  
A1.AMax = 10000  
'Revolutions/second  
'Revolutions/second/second  
A1.DMax = 10000  
A1.Acc = A1.AMax  
A1.Dec = A1.DMax  
A1.JMax=5*A1.DMax  
A1.Jerk=A1.JMax  
A1.VMax = 100  
A1.VOspd = A1.VMax * 1.2  
A1.VCruise = 50  
A1.PEMax = .01  
A1.Displacement = 0  
A1.StartType = GCom  
A1.Absolute = 1  
If Sercos.Phase = 0 then  
'can only modify simulated  
‘property in phase 0  
A1.Simulated = off  
End If  
If Sercos.Phase = 4 then  
A1.enable = on  
End If  
'reenable axis  
End Sub  
SERCOS Setup Subroutine  
The following example modifies the SERCOSSetup subroutine from the BASIC Moves  
auto setup program:  
Sub SercosSetup  
Rem  
Rem  
Setup Axis A1 for Telegram Type 7 with PExt in Cyclic Data  
Setup Axis 2 to Slave to Axis 1 PExt  
Rem If the ring is up, skip this process  
If Sercos.Phase <> 4 Then  
Rem Set Sercos.Phase to 0 and set the baud rate  
Sercos.Phase = 0  
Sercos.Baudrate = 4  
‘for 4 MBaud  
Rem  
Set the drive addresses  
A1.DriveAddress = 1  
A2.DriveAddress = 2  
A1.Simulated = 1  
A2.Simulated = 2  
Rem  
Set Sercos.Phase to 2  
Sercos.Phase = 2  
Continued on next page……….  
M-SS-005-03  
Rev E  
169  
Appendix A  
06/2005  
Danaher Motion  
Rem Configure the axis for Telegram Type 7 using IDN 15  
WriteIDNValue Drive = A1.Dadd IDN = 15 Value = 7  
Rem Configure the AT for VFb, PFb, and PExt (IDNs 40, 51, 53)  
WriteIDNValue Drive = A1.Dadd IDN = 16 Value = 40,51,53  
Rem  
Configure the MDT for VCmd, PCmd (IDNs 36, 47)  
WriteIDNValue Drive = A1.Dadd IDN = 24 Value = 36,47  
Rem  
Sercos.Phase = 4  
End if  
Set Sercos.Phase to 4  
End Sub  
170  
Rev E  
M-SS-005-03  
Danaher Motion  
06/2005  
Appendix B  
APPENDIX B  
NON-HOMOGENOUS GROUPS  
Non-homogenous groups consist of different axes, both rotary and linear. A feature was  
added to support the definition of velocities for non-homogenous groups. In the setup, rotary  
and linear axes are declared. The system determines if it is a linear- or rotary-dominant  
group. For example, in SCARA robot, there are two rotary axes for the first and second joints  
and another rotary axis for the last joint (roll). There is only one linear axis (the Z axis). Such  
a system is rotary-dominant.  
Another example is the OCP system, which is an XY Gantry system with the last two axes  
taken from the SCARA. Here, there are two linear (X & Y) axes and another linear (Z axis)  
with just one rotary axis (roll). In this case, the system is linearly-dominant.  
Axis setup defines the group behavior. Each axis must be declared whether it is linear or  
rotary by setting POSITIONROLLOVERENABLE to either zero(0) for linear or one (1) for  
rotary.  
Kinematics  
In non-homogenous groups, commanded velocity is always given according to the group  
dominancy type. If the group is linearly-dominant, the velocity (VCRUISE, VFINAL) is in  
linear units (mm/sec). The other non-linear axes are checked in the preparation phase of the  
movement. The velocity in these axes cannot exceed the maximum value. If it does, the  
overall (group) velocity is reduced.  
There is only one exception to this rule. This is when a group movement is issued with only  
one axis in motion and all the others are stopped. Then, the given value of the velocity is  
taken directly in the units for that axis. For example, having movement on the third axis of  
the SCARA robot, the velocity value is in mm/sec.  
The same is true for both acceleration and jerk values for group-interpolated motion.  
COORDINATE SYSTEMS  
Having different world and joint coordinates make the robot kinematics unique. The world  
coordinates are normally perceived as working coordinates of an application. Usually, there  
is some form of Cartesian coordinate system originating in the robot base.  
Another set of coordinates is added for the orientation of the end-effector (gripper, etc.). The  
orientation of a body in space is normally described by three angles. Depending on the  
number of degrees of freedom (motors used to actuate the orientation joints), they could be  
unequal. The world space coordinates are given by its position part (X, XY or XYZ tupple), in  
most cases. In general, it could be anything from sphere coordinates to cylindrical system.  
The orientation component can use many forms for describing orientation. The most used  
coordinate system for orientation angles are Euler angels: yaw, pitch and roll. The Euler  
angles can have two or more variations, according to the order of the accepted rotations  
(XYX, XZX etc.).  
The joint space of a robot is a relatively simple concept. A joint coordinate is a number  
uniquely describing the position of a robot segment relative to the previous robot segment. If  
the joint connecting the segment is rotary, the joint coordinates are in degrees of the rotation  
angle. If it is linear, the joint coordinates are the linear displacement (millimeters).  
M-SS-005-03  
Rev E  
171  
 
Appendix B  
06/2005  
Danaher Motion  
The concept of joint coordinates is an n-tupple number. Each number represents the  
coordinate of the specific joint. The world coordinates are supported by different built-in  
types (XY, XYZ, XYZR) that describe each of the different world space representations.  
Theoretically, there can be different world space descriptions for the same (or same  
dimensional) world coordinates. Each robot has its default world-space type. Different robots  
could have same world space types, as long as they have same number of degrees of  
freedom (NDOF). For example, xy-table world space has XY world space descriptors. A  
SCARA robot having a Z axis for vertical motion and a roll axis for orientation uses world  
frame coordinates consisting of: X, Y, Z and roll or an XYZR descriptor.  
The different coordinate systems are implemented as variables of different data types.  
Generally, a point in a coordinate system is defined as a point data type. Depending on if it is  
a joint space or world space, the sub-type of the point differs. There is a point data type with  
two subtypes: JOINT and LOCATION. Both have a world space descriptor that additionally  
differentiates between the same subtypes. A world space coordinate is stored in a variable  
and is defined as:  
DIM A AS LOCATION OF XYZR  
The joint space is:  
DIM A AS JOINT OF XYZR  
The new point data type with its two subtypes (LOCATION and JOINT) and the world-space  
descriptor (XY, XYZ, XYZR, etc.) covers all the possible robot space variations. These  
variables are independent of the robot and can be used without having a robot defined in the  
system. When they are used in a connection with the robot or a group, the world-subtypes  
must be equal.  
Internally, points are stored as 10-dimensional vectors with a flag describing the subtype and  
a size defining the dimension size of a point. The point can be manipulated as a numeric  
data type using all the arithmetic operations available (+-*/). The operations are defined as  
coordinate-by-coordinate operations. Only points of the same subtype and same world-  
space can be combined.  
Special syntax is used for point constants: a list of values separated by commands inside  
squared brackets ({}) denote points. If it is preceded by pound sign (#), it is a location:  
DIM C AS LOCATION OF XYZR  
C = #{0,0,0,0}  
DIM I AS JOINT OF XYZR  
I = {0,0,0,0}  
USER UNITS  
The MC gives you the freedom to change and choose different units. Robot models have  
less flexibility. Due to a tight relation between joint and world-space, you must define joint  
position units in millimeters or degrees and all time units in seconds so both world space and  
joint space are compatible units. The units of world space are automatically set to  
millimeters-degrees-seconds.  
Each axis has four scaling factors: PFAC,VFAC, AFAC, and JFAC. These translate  
encoder/resolver counts into user position units (inches, millimeters or revolutions). They  
also specify what time units are used in position derivations (VEL, ACC, JERK). As the  
position factor defines the ratio between counts and user position units, the rest of the  
factors define the ratio between milliseconds and user time units. Typically you have:  
<axis>.pfac = <number of counts per user position units>  
<axis>.vfac = pfac/1000 (if in seconds)  
<axis>.afac = vfac/1000 (if in seconds)  
<axis>.jfac = afac/1000 (if in seconds)  
172  
Rev E  
M-SS-005-03  
Danaher Motion  
06/2005  
Appendix B  
Once all axes are set up, groups contain these axes. You must have the same user units  
on all axes. Set the group scaling factors. There is no position factor for the group!  
Instead, PFAC for each axis is used.  
MOVE g1 {1,2,3} vcruise = 10  
Target coordinates are given to each axis and translated into encoder/resolver counts using  
PFAC for each axis. VCRUISE is not related to any axis. Group factors, VFAC, AFAC, and  
JFAC are used. The group velocity is expressed in position user units per seconds.  
To have system units properly working, set the unit factors (PFAC, VFAC, AFAC and JFAC)  
of each axis to millimeters-degrees-seconds and set group units to seconds:  
<group>.vfac = 1/1000  
<group>.afac = vfac/1000  
<group>.jfac = afac/1000  
COUPLING  
In many robotics applications, mechanical construction introduced mechanical coupling  
between the axes. In such cases, two or more motors move only one joint. So activating only  
one motor causes motion in two axes (joints). There are many examples of such mechanical  
setups. Usually when the motors are dislocated for the joints, they are actuating. When the  
motor-actuating second joint is placed before the first joint, the second joint is moved by the  
motions of the first and second motors. Typical examples of such applications are displaced  
motors of a robotic arm (PUMA) moving the robot arm via chains or belts. Differential gearing  
on the last robot segment displaces the last motor (roll) from the end effector and both the  
fifth and sixth motors introduce motions on the sixth and with joint (Staubli RX series).  
Staubli RX – pair axes a5 ,a6:  
j6.pcmd = a6.pcmd – a5.pcmd  
BOSCH – SCARA – pair axes a3,a4:  
j3.pcmd = a3.pcmd + 18.3*a4.pcmd.  
PUMA – a2,a3 and a4:  
j4.pcmd=a2.pcmd+a3.pcmd+a4.pcmd.  
Scaling and Rotation:  
j1 = 707.1*a1.pcmd + 707.1*a2.pcmd  
j2 = 707.1*a1.pcmd + 707.1*a2.pcmd  
Orthogonal Correction:  
j1 =10000*a1.pcmd  
j2 = 2.91*a1.pcmd + 10000*a2.pcmd  
Group joints are standard in the MC's firmware, covering coupling examples given above.  
MOTION ELEMENTS  
The MC is a multi-axis and multi-group system. In many aspects, groups and axes are the  
same. For example, both have properties like: AMAX, VMAX, VCRUISE. Another common  
aspect is the movement in both of them. MOVE moves both axes and groups. Although,  
there are motion commands that are group-only (CIRCLE, MOVES) or axis-only (JOG),  
when moving an axis separately, it is not possible to move the group containing the same  
axis and vice versa. The axis is active in a group. ATTACH and DETACH work the same  
way. You cannot attach an axis when its group is already attached. So, we can denote both  
axes and groups using one term, motion-element.  
M-SS-005-03  
Rev E  
173  
 
Appendix B  
06/2005  
Danaher Motion  
There are some properties that are axis- or group-only properties. For example  
DRIVEADDRESS is an axis-only property.  
MOVE consists two different command behaviors, Move-Group and Move-Axis. Move-  
Group moves the whole group together. All the axes within the group start and end the  
motion at the same time. Move-Group stays within the kinematics limits (VELOCITY,  
ACCELERATION, JERK) of the group and axes. The group limits are taken and imposed  
on the group motion (aggregate, space – XY, XYZ). The axis limits are imposed only  
proportionally to the ratio of the axis motion to the whole group motion. If axis X is moving  
halfway toward axis Y, only half the limit values are used. The total time of the motion is the  
time required for the slowest axis to accomplish the movement. Here, the slowest axis is the  
one with the largest path/velocity ratio and not necessary the axis with smallest maximum  
velocity (because if such an axis has no movement to make, it is not the slowest axis). On  
the other hand, Move-Axis checks only the limits of the specified axis and is independent of  
the limits of any group using this axis.  
Profiler preparations can additionally reduce the motion parameter. This is typical for short  
movements where the given cruise velocity cannot be reached due to existing limitations of  
ACCELERATION and JERK.  
Joints  
Joints are virtual axes. Joints give the illusion of only one axis, both from the language point  
of view and looking at the physical movement of the coupled axis. The joint is analogous to  
an axis. Joints are denoted as J1, J2, etc.  
Each joint actually represents one or several axes of the group, according to the given  
coupling matrix. If the group has no coupling matrix defined, the joint is a direct  
representation of the axis of the same ordinal number in the group as the joint index. To  
introduce another term, the "shadow-axis" of a joint is the axis with the same ordinal number  
in the group as the joint index. For example, if a group consists of axes A2, A3, A4, the  
shadow-axis of the joint J1 is A2.  
Normally, all joint properties are a direct representation (have the same value) of shadow-  
axis properties, independent of whether the coupling matrix is defined or not. The only  
exceptions are properties related to joint position: PCMD, PFB, VCMD, VFB, CCMD, CFB,  
PMAX, and PMIN. These are unique for each joint.  
Current positions and velocities are obtained according to the given coupling matrix. They  
are computed each time a query of these values is issued (PCMD, PFB, etc.). They are  
read-only and do not represent any specific internal variable. Symmetrically the same  
properties, when queried from a group (?g1.PCMD), return lists of joint-property values  
according to the coupling matrix. The movement’s target positions (MOVE or CIRCLE) of  
group movements are treated analogously (coupling matrix).  
On the other hand, the joint’s position limits (PMAX and PMIN) are added to the joints. The  
position limit of the joint and the position limit of the shadow-axis are not related, but  
independent of whether the coupling matrix is defined or not. The joint position limits are  
always used when the coupling matrix is defined (COUPLED = 1). In this case, the shadow-  
axis limits are not used. This is only true for joint and group movements. Single-axis  
movement (e.g., MOVE A1 100) is limited only by the axis limits, independent of coupling.  
Joints represent several axes of a group. Joint movements are actually group movements:  
Move-Group = Move-Joint  
174  
Rev E  
M-SS-005-03  
 
Danaher Motion  
06/2005  
Appendix B  
Joint movement gives the illusion of moving one physical axis (MOVE J1 100), although  
several motors could be moving together. The movement is executed according to the  
specified joint’s movement parameters. For example:  
A1.Acc = 100  
MOVE A1 50  
Is analogous to:  
J1.Acc = 100  
MOVE J1 50  
Move-Joint simulates the behavior of moving a single axis by moving a single joint both by  
the parameters and physical motion. The only difference is that several motors are moving  
instead of just one. When moving joints, all motor limits within each group axis are checked.  
The joint movement is a group movement of one joint-coordinate with the group motion  
parameters copied from the shadow-axis. The following translation rule is true:  
MOVE J1 10  
' MOVE {10,0,0,0} abs = J1.abs vcruise = J1.vcruise acc = J1.acc  
. . .  
The same rules of group-motion apply.  
Robot Models  
A robot is defined as a group with a special model type. Currently, the following kinematics  
models are available:  
1 – regular group: no kinematic model (default value)  
2 – PUMA: 6 axis, XYZYPR (X,Y,Z, Yaw, Pitch, Roll)  
4 – SCARA: 4 axis, XYZR (X,Y,Z, Roll)  
6 – DELTA: 4 axis, XYZR (X,Y,Z, Roll)  
COMMON SHARED scara AS GROUP AxNm = a1 AxNm = a2 AxNm = a3 AxNm = a4 Model = 4  
This automatically defines a robot with a SCARA kinematics model. Contrary to the regular  
groups that need only the axis to be enabled, you must set the robot parameters and  
configure them. The robot parameters needing to be set differs from robot to robot. For the  
SCARA robot, these are:  
Set all axes with all standard kinematics parameters.  
Define the roll-over properties.  
Set all user-units factors for the entire group: VFAC, AFAC, JFAC  
Set segment lengths and joints orientations for each robotic link.  
Set kinematics of regular groups (VELOCITY, ACCELERATION, JERK, etc.)  
Set kinematics of Cartesian motions (VTRAN,VROT, etc.)  
Issue CONFIGGROUP.  
Only after setting all these and successfully executing CONFIGGROUP can the robot be  
moved. Otherwise, an error is returned, stating that the group is not configured. The  
important difference between the regular groups (those with default model value 1) and the  
robot, is the necessity of executing CONFIGGROUP. In robot groups, no motion is allowed  
before the robot is configured.  
Model value automatically defines the default robot world space descriptor. For model 4  
(SCARA), the XYZR (x-y-z-roll) world-space is selected. With no robot model defined  
(model=1), the world-space descriptor is chosen according to the group size:  
2-axes: XY  
3-axes: XYZ  
4-axes: XYZR  
M-SS-005-03  
Rev E  
175  
 
Appendix B  
06/2005  
Danaher Motion  
In these cases, world-space is identical to joint-space. Each coordinate of the joint-space  
vector is directly translated into a coordinate of world-space.  
In groups with the robot model defined (model > 1), the translation between joint- and world-  
space is much more complex. Translating joint coordinates into world coordinates is  
accomplished with TOCART taking both the robot and given joint coordinates (position  
variable) as input arguments. The output of this is world coordinates corresponding to the  
given joint position.  
The other direction is more complex. It is accomplished with TOJOINT receiving three input  
arguments: the robot, the given Cartesian point, and the configuration flag.  
The configuration flag is used to select between the two translation functions. In most robot  
models, there is more than one joint coordinate description for the same world-space  
position. The different robot configurations can produce the same world-space positions with  
different joint-space values. The robot configurations differ from robot to robot. In SCARA,  
there are only two configurations: lefty (second joint coordinate is negative) and righty  
(second joint coordinate is positive).  
Interpolation  
For groups with robot models (model > 1), there is an additional moving type: MOVES. The  
movement makes a straight path from the starting position to the given target position in the  
world space. The straightness is tightly-related to the working space. The same path can be  
straight in the Cartesian working space (XYZ) but curvy in joint space, and vice versa.  
MOVES is used solely for groups from type robot and cannot be used in regular groups.  
Straight line motion refers to motions that are straight lines in world-space. In groups with no  
robot model (model=1), all motions produced with MOVES are straight-line motions in joint-  
space. In regular linearly-dominant groups, most of their axes are linear. As the world-space  
and joint-space are identical, MOVES executes a straight line in both joint- and world-space.  
The target position can be given both in world- and joint-space coordinates. The movement  
differs from joint interpolation (MOVE). Instead of joint-space kinematics parameters used in  
regular groups, the world-space parameters for velocity, acceleration and jerk are used.  
These parameters are available in two forms:, one for the translational part of the motion and  
one for the rotational part (orientation).  
When world-space has both position and orientation components, the straight-line motion  
includes interpolation on both position and orientation. Because these two are intrinsically  
different objects, two different parameters are needed: one for the translation (pure position  
interpolation): VELOCITYTRANS, ACCELERATIONTRANS, JERKTRANS; and one for  
the orientation (rotation interpolation): VELOCITYROT, ACCLERATIONROT, JERKROT.  
These parameter are used only for Cartesian interpolation (MOVES and CIRCLE). These  
parameters have no influence on joint interpolated motion (MOVE) because it is not a world-  
space interpolation.  
The two sets of parameters define the straight line motion. Which parameter is dominant for  
the motion depends on the movement. If most of the movement is in translational position  
change and the orientation change is much smaller, the translational part is taken.  
Conversely, the rotational parameters define the movement.  
176  
Rev E  
M-SS-005-03  
 
Danaher Motion  
06/2005  
Appendix B  
The following graph shows MOVES as seen in joint-space.  
XY  
100  
90  
80  
70  
60  
50  
40  
42  
46  
50  
54  
58  
62  
66  
70  
74  
78  
82  
The following graph shows MOVES as seen in world-space.  
XY  
680  
660  
640  
620  
600  
580  
560  
540  
520  
500  
-300  
-200  
-100  
0
100  
200  
300  
M-SS-005-03  
Rev E  
177  
Appendix B  
06/2005  
Danaher Motion  
The following graph shows MOVE as seen in joint-space.  
XY  
90  
80  
70  
60  
50  
40  
44  
48  
52  
56  
60  
64  
68  
72  
76  
80  
84  
The following graph shows MOVES as seen in world-space.  
XY  
700  
680  
660  
640  
620  
600  
580  
560  
540  
520  
500  
-300  
-200  
-100  
0
100  
200  
300  
There are four commands to make point-to-point movement in robot groups. There are two  
commands to interpolate the motion (MOVE and MOVES) and two commands to define the  
target point (JOINT and LOCATION). The total combination of these gives four options.  
LOCATION target  
JOINT target  
Cartesian-Interpolation  
Joint-Interpolation  
MOVES #{400,400,0,0}  
MOVE #{400,400,0,0}  
MOVES {45,45,0,0}  
MOVE {45,45,0,0}  
CONTOURING  
Contouring connects different motions by defining the final velocity for each movement. This  
way, the motion does not stop at the segment. It is continued with the next motion. This  
method is applicable in one-axis applications, but has several drawbacks that become more  
prominent in multi-axis applications:  
The angle between the movements' direction must be zero. Otherwise, a jump in  
velocity occurs.  
It is not possible to connect arc with linear segments without a jump in acceleration.  
You must calculate the achievable final velocities on each segment to stop after the last  
segment.  
178  
Rev E  
M-SS-005-03  
Danaher Motion  
06/2005  
Appendix B  
Cartesian Profile  
For kinematics parameters of straight-line (MOVES) motion (velocity, acceleration,  
deceleration), different joint parameters are obtained, depending on where in the robot  
working space the starting line is positioned. The further from the origin, the smaller joint  
velocities are obtained. Contrary to that, the closer to the origin the point is, the smaller the  
inertia and higher the acceleration.  
To optimally exploit robot capabilities, execute motions nearer to the origin with smaller  
Cartesian velocities to avoid exceeding the maximum joint velocity. Movements near the  
limits of the working space are farther from the robot origin and have higher robot inertia.  
Lower acceleration must be applied to avoid exceeding the maximum joint values.  
You must know at least two values (threshold of arm radius where reduction begins and end  
point of reduction at straight arm) for all joints. Limits must be considered for the joint. The  
whole Cartesian path and all Cartesian interpolation types (straight, circular, via) must be  
considered.  
Since joint velocity, acceleration, or jerk values cannot be exceeded, take the minimum of  
the commanded Cartesian values (VTRAN, ATRAN, DTRAN, JERKTRAN, VROT, AROT,  
DROT and JERKROT) and account for the values in joint-space (VCRUISE, ACC, DEC,  
JERK).  
Cruise velocity cannot vary. Use a constant cruise value. Leave the principal profile  
acceleration and deceleration phase as it is. Acceleration and deceleration cannot vary  
during the constant ACC/DEC phase. Use the highest acceleration in Cartesian space  
possible that allows constant ACC/DEC phases without exceeding joint values. Acceleration  
and deceleration may differ, and must be considered separately (mostly in long distance  
moves where conditions vary widely for start and destination position). The same restrictions  
apply to JERK.  
Acceleration, deceleration and jerk reduction must be calculated and anticipated, depending  
on payload and arm radius. The parameters for a simple scheme are:  
threshold values for payload and arm radius where reduction begins  
overall 100% reduction value per robot group  
per-joint 100% reduction values  
Since payload is static (varying only with tool change), this is easily accomplished in the  
application. Use the following two mechanisms for Cartesian profiles:  
Cartesian Velocity Adaptation (CVA) is according to the direction and position of the  
movement in the working space. For each path, a point closest to the origin (X=0,Y=0)  
is found and the Cartesian velocity of the whole motion is reduced according to the  
values of joint velocities at that point.  
Cartesian Acceleration/Deceleration/Jerk Adaptation (CADJA), where values of jerk,  
acceleration and deceleration are reduced according to the relative distance from the  
point of origin in reference to the maximum radius of the robot. The reduction  
(INERTIATHRESHOLD) is active only from a certain distance (radius). The maximum  
reduction value is defined at the final point (the fully stretched arm). For all points  
between these two values (INERTIATHRESHOLD = 100%), the reduction value is  
linearly interpolated. Acceleration is reduced according to the initial point of the  
movement. Deceleration is reduced according to the final point of the movement. The  
jerk value is reduced according to the average of the two reduction values (for initial  
and final point).  
M-SS-005-03  
Rev E  
179  
 
Appendix B  
06/2005  
Danaher Motion  
Limitations are:  
Reduction factors are not allowed for individual axes – only for groups.  
The CVA works only for MOVES & PASS-THRUGH .  
The CADJA works only for MOVES & PASS-THRUGH. In PASS-THROUGH, only the  
first and last point are treated.  
Both methods work only for SCARA kinematics.  
Working Envelope  
Robot working space is determined by the position limits of each joint. The working space  
(all reachable positions) is limited by the working envelope of the robot. From the outer side,  
it is limited by the arc made rotating the first joint with a fully stretched arm (j2.pcmd=0).  
This is the maximum radius of reachable points (RMAX). It is an internal value computed  
each time the robot is configured (CONFIGGROUP). Points given outside this radius are  
rejected with the error message, Point Too Far.  
The other limit is the small circle with the radius (RMIN). This circle is obtained by rotating  
the first joint with a maximally-folded second joint (not more then 180 degrees). This radius is  
additionally enlarged by the robot's base size and the attached end-effector mechanism to  
prevent the robot from colliding with itself. The minimal working envelope radius (RMIN) is  
available to the user (contrary to RMAX). Danaher Motion recommends setting this value for  
each application, according to the physical setup of the robot. If a point is given inside  
RMIN, an error message is returned. For example:  
XY  
900  
700  
500  
300  
100  
-100  
-300  
-500  
-700  
-800  
-600  
-400  
-200  
0
200  
400  
600  
800  
180  
Rev E  
M-SS-005-03  
 
Danaher Motion  
06/2005  
Appendix B  
Program  
attach  
move {j1.pmin,j2.pmin,0,0}  
while ismoving  
sleep 1  
End While  
Print "Plotting the workspace"  
move {j1.pmin,0,0,0}  
move {j1.pmax,0,0,0}  
move {j1.pmax,j2.pmax,0,0}  
detach  
End Program  
Robot Configurations  
In robot models, there are several joint points representing the same robot end-effector  
position for each location point. To uniquely select between different joint coordinates, there  
are configuration flags.  
For SCARA kinematics, there is only one configuration flag available: the arm flag. It  
indicates either lefty (1) (j2.pcmd > 0) or righty (2) (j2.pcmd > 0). A value of 1 (lefty)  
means that the joint coordinates having a positive second joint are taken to represent the  
given location. The current configuration of the robot is returned by ARMFBK. The value can  
be 1 or 2, depending on the position feedback value of the second joint. ARMFBK  
determines the movement's target position. It can be automatic (0), lefty(1) or righty(2).  
When a movement with a Cartesian target position is given, the joint coordinates of the  
target position are selected according to ARMFBK. If it is zero (automatic), the current robot  
configuration is used (ARMFBK).  
PUMA models traditionally use three configuration flags (arm,elbow and wrist – ACMD,  
ECMD, WCMD).  
Another use of configuration flags is in the conversion function, TOJOINT. This function  
translates the given location point into joint point. It receives two arguments. The first is the  
location variable and the second is the configuration flag.  
POINTS  
A point is a new data type used for storing a list of doubles in a variable. The main  
advantage of points is that you can directly call the whole vector without having to access  
every element of it. There are two subtypes of the point data type: LOCATION and JOINT.  
Using both point types in the same expression results in a type mismatch translation error.  
Type casting between point types requires the usage of special system functions TOJOINT  
and TOCART.  
M-SS-005-03  
Rev E  
181  
 
Appendix B  
06/2005  
Danaher Motion  
Declaration  
A point must be declared before you can use it. The declaration of points is defined  
according to the type of robot (XYZR, XYZ, etc.). The MC enables the declaration of point  
variables, which can be scalar or arrays. Point arrays may have up to 10 dimensions. Point  
variables are designed to hold a list of 2 to 10 double-type coordinates. A point variable is  
declared in relation to a robot type. Therefore, declaring a point variable must include the  
name of a valid robot type. The dimension of the point is the same as the dimension of the  
type of robot. The syntax is:  
(COMMON SHARED|DIM {SHARED}) <variable_name> AS JOINT OF <robot_type>  
(COMMON SHARED|DIM {SHARED}) <variable_name> AS LOCATION OF <robot_type>  
<robot_type> can be:  
XYZR – Three cartesian axes + roll  
XY – two axes XY table  
XYZ – three axes XYZ system  
For example:  
Common Shared JointXYZ As Joint Of XYZ  
Common Shared JointXYZR As Joint Of XYZR  
Common Shared LocXYZ As Location Of XYZ  
JointXYZ = LocXYZ  
Æ Error – type mismatch  
Variables  
Two new variable types are defined for point variables in the translator: LOCATION and  
JOINT. For the translator, a point variable differs from any other type of variable (Long,  
Double, etc.) only by its type. A point variable is inserted to the expression tree as a variable  
leaf. The variable leaf retains data related to the point variable, including its context (system,  
program or local), its offset (taken from the symbol table), and its type (LOCATION or JOINT,  
also taken from the symbol table).  
DECLARATION  
When declaring a point variable, data corresponding to this variable is entered into the  
correct symbol table (depending on whether it is a system variable, a program variable, or a  
local variable). A point variable is defined in the symbol table by its name, its type  
(LOCATION or JOINT) and an offset of the data segment. Each offset of the data segment  
corresponds to the address of the point variable. The robot type string is sent to a special  
function that gives the robot-type value and the number of coordinates.  
Constant Points  
Constant points are location or joint vectors with an undefined robot type. The constant  
point’s subtype is defined by the shape of its brackets (#{ } for location, { } for joint). In the  
translator, each of these two vector types is considered an expression. Each expression-  
related command and manipulation (such as print commands, mathematical operators, etc.)  
can be applied for the joint and location vectors.  
While executing a vector expression, each vector element is pushed separately into the  
stack as a double type expression (by executing the left side of the JOINT or LOCATION  
node). Long type vector elements are converted to double type expressions (in the  
coordinate node) after the execution of the expression at the right side of each coordinate  
node).  
182  
Rev E  
M-SS-005-03  
 
Danaher Motion  
06/2005  
Appendix B  
Execution of the right side of the JOINT or LOCATION node results in pushing the number of  
the vector elements into the stack (as a long type constant). The point’s subtype (determined  
by the shape of the vector’s brackets) is pushed to the stack (as a long type constant) by  
executing the third side of the JOINT/LOCATION node.  
Vectors  
Vectors are actually constant points, at which a list of 2 to 10 coordinates is written between  
curly brackets {}. In location vectors, the curly brackets are preceded by the # sign. A  
coordinate can be any type of expression (constant, variable, mathematical expression,  
function call, etc.) of long or double type. Long type coordinates are automatically converted  
to doubles. Unlike point variables, vectors are not related to robot types, and characterized  
merely by their size (number of coordinates).  
{<expression_1>, …, <expression_n>}  
#{<expression_1>, …, <expression_n>}  
‘ Joint vector  
‘ Location vector  
Point variables and vectors appearing in the same expression must match in type (joint or  
location) and size.  
Common Shared JointXYZ As Joint Of XYZ  
JointXYZ = #{1.5, 2.8, 3}  
Æ Error – type mismatch  
PRINT {20, 6.7, 23} + #{8.43, 2, 0}  
Æ Error – type mismatch  
JointXYZ = {2, 6}  
Æ Error – size mismatch  
PRINT {20, 6.7, 23} - {5, 4, 22.9, 31}  
Æ Error – size mismatch  
Properties  
Some group properties are points. There are several read-only properties of joint-  
(VELOCITYFEEDBACK, POSITIONCOMMAND, DEST_JOINT), and location-type (DEST,  
HERE, SETPOINT). There are also some location-type read-write properties, like TOOL,  
BASE, etc.  
As in point variables, the robot type also characterizes point properties.Point properties  
appearing in expressions in a mixture with other points must match in type and robot type to  
point properties and variables, or in type and size to vectors.  
Common Shared SCARA As Group Axnm = A1 Axnm = A2 Axnm = A3 Axnm = A4 Model = 4  
Common Shared PointXYZR As Joint Of XYZR  
Dim Shared PointXYZ As Joint Of XYZ  
PointXYZR = SCARA.SetPoint  
Æ Error – type mismatch (Setpoint returns a location)  
PointXYZ = SCARA.VelocityFeedback  
SCARA.Base = #{56.5, -104.7, -90.5}  
Æ Error – robot type mismatch  
Æ Error – size mismatch  
Point Dimension  
You do not define the size of the vector data type at the declaration of it, but you define the  
type of robot related to the point. This gives the point a dimension.  
M-SS-005-03  
Rev E  
183  
 
Appendix B  
06/2005  
Danaher Motion  
Point Assignment  
Point assignment uses the following syntax:  
<variable_name> = (<expr1>,<expr2>,<expr3>,…,<exprn>)  
() = #{} for location  
() = {} for joint  
The expression can be a constant or other vector variable of the same robot type, but the  
size of the right side of the expression must equal the left side. If you try to assign a point  
with a point of other robot type, an error is received.  
Single Coordinate Point Assignment  
The syntax for assigning a single coordinate of a point is:  
<variable_name>{<expression>} = <expression>  
Point Query  
The syntax for querying a point is:  
?<variable_name>  
Single Coordinate Point Query  
The syntax for querying a single coordinate of a point is:  
?<variable_name>{<expression>}  
Example1:  
Common shared P1 as location of XYZR  
'declaration of a vector (global)  
'assign the whole vector  
'return a translation error  
P1 = #{1,2,3,4}  
P1 = #{1,2}  
?P1  
'read the whole vector  
?P1{2}  
'read the second coordinate of the vector  
Example2:  
Common shared P2[5] as location XYZ  
P2[1] = #{1,2,3}  
P2[2] = #{5,2}  
'declare a global array of vectors  
'assign the whole vector  
'return a translation error  
'read the whole vector  
?P2[1]  
?P2[2]{2}  
'read the second value of the vector  
Operators  
Like any other data type, you can use operators for points. The system only defines the  
equal operator (plus, minus, multiplication and division). Operations between points can only  
be performed between points of the same type and robot type (or size). All operations can  
also be performed between points and long or double type expressions.  
ASSIGNMENT  
Point variables and read-write properties can be assigned by point variables, vectors and  
point properties compatible in type and size (or robot type).  
184  
Rev E  
M-SS-005-03  
 
Danaher Motion  
06/2005  
Appendix B  
QUERY  
Point variables, properties and vectors return a value, so they can all be queried through  
printing or assignment into a compatible point variable or read-write property.  
Common Shared SCARA As Group Axnm = A1 Axnm = A2 Axnm = A3 Axnm = A4 Model = 4  
Common Shared PointVar1 As Joint Of XYZR  
Dim Shared PointVar2 As Joint Of XYZ  
Dim PointArr[4] As Joint Of XYZR  
PointVar1 = PointArr[2]  
PointVar2 = {23.4, 60, 42}  
PointArr[1] = SCARA.PositionCommand  
SCARA.Tool = #{10, 20,30, 0}  
PRINT PointVar2, SCARA.Tool, {100.3, 20}  
Æ
{23.4 , 60 , 42}  
#{10 , 20 , 30 , 0}  
{100.3 , 20}  
PLUS  
The point plus operator is used like any other data type. It adds each element of the first  
point with each element of the second point. The result is a point.  
?(1,2)+(2,4)  
Æ (3,6)  
MINUS  
The point minus operator is used like any other data type. It subtracts each element of the  
first point with each element of the second point. The result is a point.  
?(1,2)-(2,4)  
Æ (-1,-2)  
MULTIPLICATION  
The point multiplication operator is used like any other data type. It multiplies each element  
of the first point with a number. You can only multiply a point with a single number (one-  
dimensional number). The result is a point.  
?2*(2,4)  
Æ (4,8)  
DIVISION  
The point division operator is used like any other data type. It divides each element of the  
first point with a number. You can only divide a point with a single number (one-dimensional  
number). The result is a point.  
?(2,4)/2  
?2/(2,4)  
Æ (1,2)  
Æ (1,0,5)  
COMPOUND (:)  
Is an operator specific for points, which should be operated between two locations of the  
same size (or robot type).  
? #{-56.5 , -104.7 , 89.5} : #{ 0.0, -104.7 , -0.5}  
Æ #{-56.5 , -209.4 , 89}  
LIMITATIONS  
MOD (modulus), ^ (power), logic and bitwise operators cannot be used for points.  
Points cannot be used as condition in flow control statements and event definitions.  
Points cannot be recorded.  
M-SS-005-03  
Rev E  
185  
Appendix B  
06/2005  
Danaher Motion  
Points in Functions  
Point variables can be passed to functions and subroutines both by reference and by value.  
An entire array of points can also be passed (by reference) to a function or subroutine. On  
the other hand, point properties and vectors can only be passed by value. Points can also  
serve as return values of functions. However, the point type and size (or robot type) of an  
argument or a return value must match function declaration.  
PASSING BY VALUE AND REFERENCE  
A point can be passed by value and by reference like any other data type. For example:  
Program  
Dim p1 as joint of XYZR  
Call Sub1(P1)  
?p1  
End program  
Sub Sub1(X as joint of XYZR)  
X = {1,2,3,4}  
End Sub  
This program assigns P1 to {1, 2, 3, 4} and prints {1, 2, 3, 4} as output. When a point is  
passed by reference or value, you can only pass a point of the same robot type to X.  
Otherwise, you receive a translation error.  
Example1:  
Program  
Dim p1 as location of XYZR  
Call Sub1(P1  
Æ TRANSLATION ERROR !!!  
?p1  
End program  
Sub Sub1(X as location of XYZ)  
X = #{1,2,3,4}  
End Sub  
Example2:  
Program  
Dim p1 as joint of XYZR  
Call Sub1(P1)  
Æ TRANSLATION ERROR !!!  
?p1  
End program  
Sub Sub1 (ByVal X as joint of XYZ)  
X = {1,2,3,4}  
End Sub  
RETURNING POINT FROM FUNCTION  
A function can return a point variable like any other data type. For example:  
Dim A as location of XYZR  
Program  
Move G1 MyFunc(1) vcruise=299  
Æ this will be OK if G1 is of XYZR robot type.  
End Program  
Function MyFunc(i1 as long) as location of XYZR  
MyFunc = #{1,2,3,4}  
End Function  
186  
Rev E  
M-SS-005-03  
 
Danaher Motion  
06/2005  
Appendix B  
Motion Commands  
Some motion commands use point nodal parameters when applied on groups. For example:  
CIRCLE, MOVE and MOVES.  
Some nodal parameters can be assigned with both point types (LOCATION and JOINT), like  
CIRCLECENTER, CIRCLEPOINT and the target positions of MOVE and MOVES. Other  
nodal parameters can accept only location points, like TOOL, BASE, etc. Assign all nodal  
parameters with points compatible in robot type or size to the group.  
Common Shared SCARA As Group Axnm = A1 Axnm = A2 Axnm = A3 Axnm = A4 Model = 4  
Common Shared JointXYZ As Joint Of XYZ  
MOVE SCARA JointXYZ  
Æ Error – robot type mismatch  
CIRCLE SCARA Angle = 180 CircleCenter = #{350, 500, -80}  
Æ Error – size mismatch  
MOVES SCARA #{-22, 503.8, -8.3, 149} Base = SCARA.Dest_Joint  
Æ Error – type mismatch  
Analog Behavior  
Because a point is a new data type, it has all the functionality of the other data types like  
saving the point to a file, watching points, deleting points.  
Point As An Expression  
With the new point data type, points properties can be stored as a point or can be compared  
as a point. For example:  
Dim A as Joint of XYZR  
A = {1,2,3,4}  
A = G1.Pcmd  
A = G2.Pcmd  
Æ returns a translation error if G2 is not of XYZR type.  
FUNCTIONS  
The following functions are defined:  
<XYZR location> = TOCart (<group>, <XYZR JOINT>)  
<XYZR Joint> = ToJoint (<group>, <XYZR LOCATION>, <arm-flag:integer>)  
<double> distl(<location>,<location>)  
Distance between points (length).  
<double> distr(<location>,<location>)  
Distance between points (angle).  
SAVE/LOAD  
Each global variable can be stored in a file. The variable and its value are stored in same  
syntax as it is defined in the program. You can select a data-type to be stored. If a data-type  
is selected, the SAVE command stores only global variables of that data type. If file with  
same name already exist its extension is renamed to *.bak and new file is created. Loading  
the file overwrites the values of the saved global variables. You can save all the points  
related to some type of robot. For example:  
SAVE file = "Myfile.prg" type = location robottype = xyzr  
SAVE file = "Myfile.prg" type = all  
LOAD Myfile.prg  
M-SS-005-03  
Rev E  
187  
 
Appendix B  
06/2005  
Danaher Motion  
Group Point Properties  
Following modal-only and read-only group properties of the point data-type exist:  
DEST  
START  
HERE  
DEST_JOINT  
START_JOINT  
POSITIONFEEDBACK or PFB  
POSITIONCOMMAND or PCMD  
Target point of the movement.  
Starting point of the movement.  
Actual point of the robot (feedback).  
Actual point of the robot (group).  
SETPOINT  
SINGLE ELEMENT ASSIGNMENT  
Syntax for assigning a single element of a structure:  
<variable_name>-><structure element> =<expression>  
In Functions  
Structures can be passed to functions and subroutines both by reference and by value. Also,  
an entire array of structures can be passed (by reference) to a function or subroutine.  
Structures can also serve as returned values of functions. However, the structure type of an  
argument or a returned value must match function declaration.  
Dim Shared ARG1 As Type_1  
Dim Shared ARR_ARG[4][5] As Type_1  
Dim Shared ARG2 As Type_2  
FUNCTION MyStructFunc(BYVAL Par1 AS Type_1, Par2 AS Type_2) AS Type_1  
MyStructFunc = Par2  
MyStructFunc = Par1  
END FUNCTION  
->  
->  
Error - structure type mismatch  
Structure types match  
SUB MySub(Arr_Par[*][*] AS Type_1)  
END SUB  
ARR_ARG[2][3] = MyStructFunc(ARG1, ARG2)  
ARR_ARG[2][3] = MyStructFunc(ARG1, ARG1)  
mismatch  
->  
->  
Structure types match  
Error - structure type  
CALL MySub(ARR_ARG)  
or  
Common Shared ST As STRUCT  
Common Shared LongVar As Long  
FUNCTION MyFunc(BYVAL Par1 AS LONG, Par2 AS LONG) AS STRUCT  
MyFunc->LongElm2 = 10  
MyFunc->JointElm = {12.3, 5, 43.29}  
END FUNCTION  
FUNCTION NoParamFunc AS STRUCT  
END FUNCTION  
ST = MyFunc(ST->LongElm1, LongVar)  
ST = MyFunc(ST->LongElm1, ST->LongElm2)  
->  
Error – structure element passed by reference  
? MyFunc(ST->LongElm1, LongVar)->LongElm2  
->  
Error – addressed through function call  
LongVar = NoParamFunc->LongElm2  
->  
Error – addressed through function call  
188  
Rev E  
M-SS-005-03  
 
Danaher Motion  
06/2005  
Appendix B  
A function can return a structure variable like any other data type. For example:  
Dim Shared A as X  
Program  
Dim S1 as X  
S1 = MyFunc(1)  
End Program  
Function MyFunc(i1 as long) as X  
MyFunc->Type = 1  
End Function  
Query  
You cannot query a whole structure or you receive a translation error.  
?<variable_name> - gives a translation error  
SINGLE ELEMENT QUERY  
Syntax for querying a single element of a structure:  
?<variable_name>-><structure element>  
For example:  
Common shared s1 as X  
S1->.Type =1  
S1->Length =2  
?S1  
'declaration of a default structure  
'Translation Error  
?S1->Type  
Operators  
You cannot use operators with structures. It is possible to use operators for the single  
elements of the structure.  
Pass Structure  
A structure can be passed by value and reference like any other data type.  
Example1  
Program  
Dim s1 as X  
Call Sub1(S1)  
?S1->Type  
End program  
Sub Sub1(X as X)  
X ->Type= 1  
End Sub  
Example2  
Program  
Dim s1 as X  
Call Sub1(S1)  
?S1->Type  
End program  
Sub Sub1(X as X)  
X ->Type= 1  
End Sub  
M-SS-005-03  
Rev E  
189  
 
Appendix B  
06/2005  
Danaher Motion  
Limitations  
A whole structure cannot be printed.  
Mathematical, logic and bitwise operators cannot be used for whole structures.  
A whole structure cannot be used as a condition in flow control statements and event  
definitions.  
A whole structure cannot be recorded.  
For example:  
Common Shared VAR1 As STRUCT  
Common Shared VAR2 As STRUCT  
PRINT VAR1  
VAR2 = VAR1 * 100  
IF VAR2 > VAR1 THEN  
WHILE VAR2  
->  
->  
->  
->  
Error  
Error  
Error  
Error  
CONVEYER TRACKING  
A moving frame’s variable data-type is defined by the user as a separate unit (object) and  
can be linked to one or more robots. The data type has its own properties and definitions.  
The moving frame represents a coordinate system relative to the robot’s world coordinate  
system. Set a limited area (in further text: window) on which the robot tracks. This area is  
the operation region or the working frame. Before the entrance to this region, there is a  
sensor that marks objects entering the region. The tracking starts when a trigger occurs  
and you enable the procedure. During tracking, you can move the robot both in absolute  
and relative movements. The absolute movements shift by the tracking process in the  
same direction and distance as the moving object. The relative movements are  
commanded in respect to the current robot position. The relative movements are  
superposed to the movements caused by the tracking of the moving frame. The tracking  
lasts until the object exits the working frame,. Then, the robot starts tracking the next item  
on the frame.  
190  
Rev E  
M-SS-005-03  
 
Danaher Motion  
06/2005  
Appendix B  
You can classify objects in the working frame and only track certain types of objects. Each  
moving frame can have several master sources (external sources of moving position). The  
number of sources is the number of degrees of freedom of the moving frame. You can use  
several robots to track the same operating region, but the region must be presented as a  
different moving frame object. Robots must be of the same type as the world frame of the  
object in the tracking process (dimension and robot type). The process is completed in one  
of two ways: disable tracking or send no new triggers.  
There are two different concepts of NDOF’s: one for the robot which means the number of  
motors driving it and one for the moving frame, which means the number of external  
position sources assigned to it. These two numbers can be different. Only the object type  
(dimension and type) of the moving frame must match the robot's world frame.  
Window Declaration  
Limit the region by one or more pairs of points, depending on the number of degrees of  
freedom of the element to be tracked. For every degree of freedom a pair of points defines its  
region limits. The boundaries are the upstream (lower limit) and the downstream (the upper  
limit). The lower and upper limits are referred to the trigger point. The lower limit is closer to  
the trigger point than the upper limit. Moving direction is from upper to lower. While the object  
is inside the working frame, every change of conveyor movement direction is tracked. The  
only limitation is that region limits must be relative to the trigger position so the upstream is  
closest to the trigger. An object might enter from the downstream limit. To correct this error,  
add a direction flag to the trigger to indicate if the region limits are inverse.  
The moving frame is divided into components. For example, an XY table tracks as two axes:  
X and Y. The coordinate translation is done automatically when using the robot coordinate  
system as a base for the position calculation. The moving frame coordinate system is the  
same as the tracking robot. The master source is independent in the moving frame type. The  
group master is used as an input position to follow.  
Tracking  
Tracking starts when the tracking process flag is enabled, which assumes that the object has  
passed the sensor. Tracking actually starts when the relevant object enters the operation  
region and ends when it leaves the frame. During its motion in the frame, the moving frame  
position is re-calculated every sample. The position is based on the frame boundary limits  
and the scaling ratio in moving frame units. To this basic formula, a correction term is added  
to correct a delay of 1-2 samples between the trigger from the sensor to the start of the  
operation. Due to the discretization of the SERCOS samples, this delay causes a gap in the  
position.  
Moving Frame  
The input position is the current moving fame position. The input position (master source) is  
usually taken as an external source (external encoder), simulated axis or even another  
moving frame position.  
If the master source is another moving frame (e.g., TCP-coordinates of any other kinematics  
with more than 2 axes), the offset/transformation between the tracking kinematics and the  
tracked kinematics is considered. In the implementation state of group as a master source  
(phase 3), the offset must be taken into consideration in TRIGGER or other alternative.  
The tracking element and the moving frame must have the same kinematics system. It is  
impossible to track a different kinematics system.  
M-SS-005-03  
Rev E  
191  
 
Appendix B  
06/2005  
Danaher Motion  
The orientation is composed of two components: the master source (if there is one) and the  
orientation change due to movement. On the path, if the new position command is known,  
the new orientation can be calculated.  
Tracking Process  
The tracking process consists of two phases: approach (where the robot position catches  
the moving frame position) and track (when both positions are synchronized (<robot>.HERE  
and <moving frame>.HERE)). The two phases are differentiated by the value of  
ISMOVINGFRAMESYNCHRONIZED. These are pure internal process phases over which  
you have no control. They are shown here to provide a better understanding of the  
implemented algorithms.  
The robot motion is determined by modal values of velocity, acceleration and jerk both for  
rotation and translation (ATRAN, VTRAN, DTRAN, JTRAN, VROT, AROT, DROT, JROT).  
These values are taken during moving frame assignment when <element>.MASTERFRAME  
is assigned. Later, changing these values does not affect the approaching process. For  
groups that do not have a kinematics model, usual kinematics values are used: VCRUISE,  
ACC and JERK. This phase is complete when both differences in velocity and position drop  
below certain thresholds. Higher values of these parameters assure faster approaches. Both  
robot’s position and orientation coordinates are taken into account.  
A system offers two different approach algorithms. One is the absolute tracking algorithm,  
and the other is the relative tracking algorithm. Both are based on internal, closed  
prediction-PD position loop using position and velocity differences as success criteria. Use  
the absolute tracking algorithm in simple, slow-motion tracking with minimal initial distance of  
the robot from the tracking object. Use the relative tracking algorithm in all other cases.  
Besides differences in approaching algorithms there is also difference in the way both  
algorithms are used.  
Absolute Approach  
Absolute tracking algorithm (slave = 3)  
The system automatically moves the robot position (<robot>.SETPOINT) toward  
the tracking object position (<moving frame>.HERE). Once synchronization is  
achieved, both positions are equal.  
In this algorithm, two parameters influence the approaching behavior: <moving  
frame>.FILTERFACTOR and <moving frame>.DAMPINGFACTOR.  
The requirement to enter the tracking phase is that the position error  
between the moving frame and the robot is less than half of the  
product between acceleration and the square of the sampling period  
(1/2 AT2).  
NOTE  
FITERFACTOR significantly influences the synchronization  
(approaching phase) behavior. Use small values in the beginning and  
increase them step-by-step until the desired results are obtained.  
High values of FITERFACTOR lead to robot instability!  
NOTE  
192  
Rev E  
M-SS-005-03  
 
Danaher Motion  
06/2005  
Appendix B  
Relative Approach  
Relative tracking algorithm (slave = 5)  
The system moves the initial (before tracking) robot position (<robot>.SETPOINT)  
in the same direction as the tracking object position. Once synchronization is  
achieved, the robot moves synchronously on the same relative position to the  
moving object at the moment of approach start (slave=0).  
It is your responsibility to add the appropriate movement and bring the robot  
position to the object. In this algorithm, the two parameters are used differently.  
FILTERFACTOR defines the threshold needed to end the approach phase and  
switch to the track phase. As this parameter gets bigger, the approach phase lasts  
less time, but the transition moment becomes jerkier.  
DAMPINGFACTOR tunes the prediction part of the algorithm. Larger values  
correspond to longer approach phases. Smaller values make the approach phase  
shorter.  
Due to non-linear effects (kineamtics, velocity limitations, etc.), the  
algorithm becomes unstable with small DAMPINGFACTOR values.  
Low values of DAMPINGFACTOR lead to robot instability!  
NOTE  
M-SS-005-03  
Rev E  
193  
Appendix B  
06/2005  
Danaher Motion  
CUSTOMER SUPPORT  
Danaher Motion products are available world-wide through an extensive authorized  
distributor network. These distributors offer literature, technical assistance, and a wide range  
of models off the shelf for the fastest possible delivery.  
Danaher Motion sales engineers are conveniently located to provide prompt attention to  
customer needs. Call the nearest office for ordering and application information and  
assistance or for the address of the closest authorized distributor. If you do not know who  
your sales representative is, contact us at:  
Danaher Motion  
203A West Rock Road  
Radford, VA 24141 USA  
Phone: 1-540-633-3400  
Fax: 1-540-639-4162  
Website: www.DanaherMotion.com  
194  
Rev E  
M-SS-005-03  
 