GE Monogram ZGU365 User Manual

GE Monogram®  
Installation  
Instructions  
36" Downdraft  
Gas Cooktops  
Models  
ZGU365  
Design Information  
G as Downdraft Cooktop  
ZGU365  
36" gas downdraft cooktops  
Models  
Available  
These models are shipped for natural gas  
operation. They can be converted to liquid  
propane. (Order JXLP56 conversion kit.)  
These gas downdraft cooktops are equipped  
with an vent system which can be retracted  
when not in use.  
JXBA56WW, white or JXBA56BB, black  
motor and blower assembly is required for  
both models. Be sure to order the color that  
matches the cooktop.  
JXRB57 optional accessory for indoor  
remote location of the blower/motor  
assembly. Use this kit when the blower and  
motor assembly will be located outside of or  
below the cabinet floor.  
JXBC57 optional outdoor cover accessory  
may be ordered for installation of blower  
and motor assembly on the outside wall.  
Accessories  
Dimensions  
and Clearances  
2"  
13"  
Max.  
19-3/4"  
36"  
2"  
8-3/4"  
15"  
30"  
Min.  
18"  
Min.  
3-7/8" Min.  
8" Min. to  
Wall When  
Installed Both Sides  
2"  
From Cooktop  
to Rear Vertical  
Combustible  
When Installed  
8-1/2" Lift  
1-1/2" Min.  
When Installed  
7-1/2"  
2-1/4"  
3-1/4"  
3-1/4"  
6-3/8"  
7"  
12-3/8"  
36"  
33-3/4"  
5-3/8"  
14-3/4"  
27"  
26"  
3
Design Information  
G as Downdraft Cooktop  
The combined installation of a downdraft vent Base Cabinet Requirements:  
Advance  
Planning  
and cooktop require careful consideration.  
This installation requires a 24" min. deep  
cabinet base. The cabinet must be at least 36"  
wide.  
Countertop Requirements:  
The countertop must have a deep flat surface  
to accommodate the cooktop and the vent.  
Countertops with a rolled front edge and  
backsplash may not provide the flat surface  
area required.  
Clearances  
least 1/4" thick or gypsum board at least  
3/16" thick covered with 28 gauge sheet  
steel or .02" thick copper.  
Clearance between cooktop and protected  
cabinetry must not be less than 24".  
The downdraft system with blower, motor  
and ductwork will occupy the cabinet below  
the cooktop. Drawers cannot be installed  
below this cooktop.  
Refer to “Dimensions & Clearances” for  
information on appropriate placement and  
necessary clearances when planning installa-  
tion.  
Avoid placing cabinetry directly above the  
cooktop when possible.  
If cabinetry is used above cooking surface:  
Use cabinets no more than 13" deep.  
Maintain 30" minimum clearance between  
cooktop and unprotected cabinets directly  
above cooktop.  
EXCEPTION: Installation of a listed micro-  
wave oven or cooking appliance over the  
cooktop shall conform to the installation  
instructions packed with that appliance.  
Working areas adjacent to the cooktop  
should have 18" minimum clearance be-  
tween countertop and cabinet bottom.  
Installation must conform with local codes.  
In the absence of local codes, the gas cooktop  
must comply with the National Fuel Gas Code,  
If clearance is less than 30", protect cabinet ANSI Z223.1, latest edition.  
bottoms with flame-retardant millboard at  
Ductwork Advance Planning  
Prepare ductwork to vent to outdoors:  
Use the shortest and straightest duct run  
possible:  
Duct run should not exceed equivalent  
length of 150 feet.  
The downdraft blower system is designed to  
use 3-1/4"x10" ductwork. It can be  
transitioned to 6" round.  
Ductwork MUST be vented to the outside–  
never into a crawl space, attic or other  
enclosed space.  
Refer to “Duct Fittings” chart to calculate  
equivalent length for various duct  
configurations.  
Determine the need for a wall cap or roof  
cap. Order the cap in advance.  
Gas and Electrical Locations  
Refer to “Power Supply Locations” page 8 for  
details.  
Plan the placement of the electrical outlet and  
gas carefully. Gas and electrical outlets cannot  
be placed on the back wall of the cabinet  
because it may interfere with the downdraft  
plenum.  
4
Cabinetry/Ductwork  
G as Downdraft Cooktop  
Self-adhesive gasket  
(supplied)  
Two clamping  
brackets and  
screws (supplied)  
Gas pressure  
regulator (supplied)  
Large flat-blade  
screwdriver  
Carpenter’s square  
Pipe wrench  
Manual gas line  
shut-off valve  
3/4" NPT x 3/4"  
I.D. or 1/2" NPT x  
1/2" I.D. flare  
union adaptor for  
connection to  
•Duct work to suit the 5 foot AGA-certified  
Tools and  
Materials  
Required  
installation  
flexible metal  
1/2" NPT x 3/4"  
I.D. or 1/2" I.D.  
flare union adaptor  
for connection to  
regulator  
appliance connec-  
tor, 3/4" or 1/2"  
I.D. to match gas  
supply line:  
If required by local  
codes, use solid  
pipe with fittings.  
Gas-resistant pipe  
joint sealant  
Saw  
supply line  
Note: Purchase new  
flexible line, DO  
NOT USE OLD,  
PREVIOUSLY USED  
FLEXIBLE LINE.  
Top View–Countertop Surface  
Cut the  
Opening  
4-5/8" Cooktop  
Cutout to  
Rear Vertical  
Combustible  
Surface  
36"  
1/4"  
1/4"  
1/4" Overlap  
1/8" Gap  
34" Vent Cutout  
2-9/16"  
20-11/16"  
Cutout  
Depth  
21-3/4"  
Total Flat  
Surface  
18-1/8"  
Cooktop  
Cutout  
Depth  
Required  
34-1/2"  
Cooktop Area Cutout  
3/4" Cooktop Overlap  
2-1/4" Min. Clearance to Cutout  
Front Edge of Countertop  
8-13/16" Min. Cutout  
to Wall Both Sides  
Measure carefully when cutting countertop.  
Make sure sides of opening are parallel and  
rear and front cuts are exactly perpendicular  
to sides.  
The Monogram gas downdraft cooktop is  
designed to fit in a 36" or larger base  
cabinet.  
Allow at least 4-5/8" clearance between back  
of cutout and combustible wall.  
Allow at least 8-13/16" clearance from right  
and left sides of cutout to adjacent wall.  
Allow at least 2-1/4" clearance between front  
of cutout and front edge of countertop.  
Caution: Wall coverings,  
The countertop cutout for the cooktop  
must be:  
countertops and cabinets  
should withstand 200°F heat  
34-1/2" at the front of the counter and,  
34" at the back  
generated by the cooktop.  
18-1/8" front to back notch  
20-11/16" front to back of cutout  
The notches at the back of the cutout are:  
2-9/16" forward and 1/4" to the inside.  
Follow the illustration shown.  
5
Ductwork  
G as Downdraft Cooktop  
Loosen Screws to  
Adjust Blower  
Left to Right  
• The downdraft vent is shipped with the  
discharge outlet pointing straight down and  
can be changed to the left or right side.  
• The blower outlet is sized for 3-1/2" x 10"  
and can be transitioned to 6" round.  
Venting  
Options  
Side to side adjustments:  
The entire blower mounting plate can be  
adjusted 3-1/2" to the left or right. This will  
help to align vent discharge to house  
ductwork.  
30° Rotation  
Nut Location  
Inside the Blower  
Discharge  
For even more flexibility, the entire blower  
can be rotated up to 30° towards the left or  
30° towards to right.  
Discharge direction  
The blower assembly may be removed and  
turned 90° for a left or right side discharge.  
Loosen Screws to Rotate  
30° to Left or 30° to Right  
30" Rotation Left or Right  
• A left or right 90° direction adjustment  
should be performed before dropping into  
the countertop opening.  
• Flatten the shipping box to use as a pad.  
• Lay the vent on its back onto the pad.  
To change to a left or right discharge:  
• Remove 4 nuts holding the blower to the  
mounting plate. See illustration. One nut is  
just inside the blower discharge.  
• Remove and turn the blower to the right or  
left.  
Discharge Down  
(as Supplied)  
• Reinstall the 4 nuts.  
To locate the ductwork holes in the cabinet  
floor or side walls:  
• Temporarily, place vent into the countertop  
opening.  
• Push the vent all the way to the back of the  
opening.  
• If you are transitioning to 6" round, place  
transition piece over the discharge outlet.  
– Mark the location and remove the  
assembly.  
Discharge Left  
Discharge Right  
– Cut holes and install ductwork  
connections.  
Order JXRB57 for installation of the blower and motor  
below the floor.  
Order JXBC57 for installation of the blower and motor  
outdoors.  
6
Ductwork  
G as Downdraft Cooktop  
Use this form to  
compute maximum  
permissible lengths  
for duct runs to  
outdoors.  
Total  
Equivalent  
Length  
Duct  
Fittings  
Equivalent Quantity  
Duct Piece  
Dimensions  
Length*  
Used  
1 ft.  
(per foot  
length)  
6" round,  
straight  
Note: Do not exceed  
maximum permissible  
equivalent lengths!  
1 ft.  
(per foot  
length)  
3-1⁄4" x 10"  
straight  
Flexible ducting:  
6"  
If flexible metal  
90° elbow  
15 ft.  
9 ft.  
ducting is used, all the  
equivalent feet values  
in the table should be  
doubled. The flexible  
metal duct should be  
straight and smooth  
and extended as much  
as possible.  
6"  
45° elbow  
3-1⁄4" x 10"  
90° elbow  
16 ft.  
5 ft.  
3-1⁄4" x 10"  
45° elbow  
Do NOT use flexible  
plastic ducting.  
3-1⁄4" x 10"  
90° flat elbow  
18 ft.  
7 ft.  
Gas Downdraft  
Cooktop  
Model ZGU365  
150' maximum  
equivalent length  
6" round  
to 3-1⁄4" x 10"  
transition  
3-1⁄4" x 10"  
round to 6"  
transition  
5 ft.  
6" round to  
314" x 10"  
transition  
90° elbow  
Note: Any home  
ventilation system,  
such as a cooktop with  
a downdraft exhaust  
mechanism, may  
interrupt the proper  
flow of combustion air  
and exhaust required  
by fireplaces, gas  
furnaces, gas water  
heaters and other  
naturally vented  
systems. To minimize  
the chance of inter-  
ruption of such  
20 ft.  
12 ft.  
21 ft.  
27 ft.  
20 ft.  
3-1⁄4" x 10" to 6"  
round transition  
90° elbow  
6" round  
wall cap  
with damper  
3-1⁄4" x 10"  
wall cap  
with damper  
6" round  
roof cap  
naturally vented  
systems, follow the  
heating equipment  
manufacturer’s  
6" round  
roof vent  
24 ft.  
guidelines and safety  
standards such as those  
published by NFPA  
and ASHRAE.  
Total Duct Run  
* Actual length of straight duct plus duct fitting  
equivalent. Equivalent length of duct pieces are based  
on actual tests conducted by GE Evaluation Engineer-  
ing and reflect requirements for good venting  
performance with any downdraft cooktop.  
7
Gas and Electrical Supply  
G as Downdraft Cooktop  
Gas supply:  
Power Supply  
Locations  
Do Not Locate Gas or Electrical  
Connections Within Shaded Area  
These cooktops are designed to operate on  
natural gas at 4" of water column pressure or  
on LP gas at 10" of water column pressure.  
These cooktops are shipped from the  
factory set for natural gas. If you decide  
to use this cooktop with LP gas, conversion  
adjustments must be made by a service  
technician or other qualified person.  
JXLP56 conversion kit is required for  
LP operation.  
34"  
29-1/2"  
Electrical  
Outlet  
12" Above  
Cabinet Floor  
4"  
14"  
The pressure regulator must be connected in  
series with the manifold of the cooktop and  
must remain in series with the supply line  
regardless of type of gas being used.  
Gas Location  
For proper operation, the maximum inlet  
pressure to the regulator must be no more  
than 10" water column pressure for natural  
gas and 14" water column pressure for LP gas.  
When checking the regulator, the inlet  
pressure must be at least 1" greater than the  
regulator output setting.  
If the regulator is set for 4" of water column  
pressure, the inlet pressure must be at  
least 5".  
Electrical supply:  
•A properly-grounded 3-prong receptacle  
should be located within reach of cooktop’s  
four foot power cord.  
– Locate the receptacle inside the cabinet on  
the right side wall. See illustration.  
IMPORTANT: (Please read carefully).  
FOR PERSONAL SAFETY, THIS APPLIANCE  
MUST BE PROPERLY GROUNDED.  
The power cord of this appliance is equipped  
with a three-prong (grounding) plug which  
mates with a standard three-prong grounding  
wall receptacle to minimize the possibility of  
electric shock hazard from this appliance. The  
customer should have the wall receptacle and  
circuit checked by a qualified electrician to  
make sure the receptacle is properly  
grounded and has correct polarity.  
Where a standard two-prong wall receptacle is  
encountered, it is the personal responsibility  
and obligation of the customer to have it  
replaced with a properly grounded three-  
prong wall receptacle.  
If the regulator is set for 10" of water  
column pressure, the inlet pressure must  
be at least 11".  
For ease of installation, and if local codes  
permit, the gas supply line into the cooktop  
should be 1/2" or 3/4" ID flexible metal  
appliance connector, three to five feet long.  
Note: Purchase new flexible line. DO NOT  
USE OLD, PREVIOUSLY USED FLEXIBLE  
LINE.  
Make gas connection through rear wall, or  
on cabinet floor at rear, as illustrated.  
Do Not, Under Any Circumstances, Cut Or  
Remove The Third (ground) Prong From The  
Power Cord.  
Do not use an extension cord.  
8
Installation  
G as Downdraft Cooktop  
• Remove the shipping materials and the  
carton, set carton aside. The carton can be  
used as a pad when changing or adjusting  
vent direction.  
Remove  
Packaging  
Plastic Ties  
• Remove the plastic ties on both ends at the  
top of the vent.  
Optional Method  
Secure to Cabinet  
Side With Top  
Step  
Screw on Case  
1
Install  
Downdraft  
Vent  
Or Use Second Screw  
Preferred Method  
Secure the Upper  
Brackets With Screws  
Located on the side of  
Case and Attach to  
Back Wall of Cabinet  
Secure the Lower Brackets  
to Blower Housing  
Place the downdraft vent into the countertop  
cutout, against the back side.  
– Install two brackets on the bottom of the  
vent. Attach brackets to slide screws on the  
vent and to the floor using wood screws  
(not supplied).  
• Secure the downdraft to the countertop  
supplied brackets. See illustration.  
– Fasten brackets to top screws on the front  
side of the vent, secure to cabinet side wall  
just below the countertop. Or,  
• When installing in a tile countertop surface,  
it may be necessary to apply a locally  
approved caulking to cover any gaps.  
– Fasten one bracket to vent side and secure  
to cabinet back wall.  
9
Installation  
G as Downdraft Cooktop  
• The downdraft blower system is designed for  
use with 3-1/4" x 10" ductwork. It can be  
transitioned to 6" round.  
Ductwork MUST be vented to the outside –  
never into a crawl space, attic or other  
enclosed space.  
length when bends or various fittings are  
used. Refer to the table of equivalent lengths  
to calculate your installation.  
• Install ductwork so the piece of duct nearest  
the downdraft unit slots INTO the next  
piece of the duct. Secure the joints with self-  
tapping screws and apply duct tape around  
the joints to ensure an airtight seal.  
Step  
2
Install the  
Ductwork  
6" PVC duct should be used when installing  
under a concrete slab.  
Note: Local building code must be followed  
for installation and in specifying approved  
type and schedule of PVC duct used.  
Duct Tape  
Over Seam and Screw  
• DO NOT USE flexible plastic ducting.  
• Always use appropriate roof or wall cap with  
damper. Laundry type wall caps should  
never be used.  
Air  
Screw  
• Use the straightest duct run possible.  
• For satisfactory performance the duct run  
should not exceed 150 ft. or its equivalent  
Install the supplied pressure regulator and  
nipple in the gas line as close to the cooktop  
inlet as possible. Allowances for ventilation  
ducting may be necessary.  
–Make sure the regulator is installed in the  
right direction.  
Step  
3
Regulator  
Install  
Pressure  
Regulator  
Install a manual shut-off valve in the gas line  
in an easily accessible location.  
Solid Piping  
or Flexible  
Connector  
Note: Instead of using solid piping to connect  
to pressure regulator, an approved flexible  
metal appliance connector may be used  
between the pipe stub and the shut-off valve  
and the pressure regulator, if local codes  
permit.  
– Appropriate flare nuts and adapters are  
required at each end of the flexible  
connector.  
Shut-Off  
Valve  
Pipe Stub  
IMPORTANT: Disconnect the cooktop and  
the individual shut-off valve from the gas  
supply piping system during any pressure  
testing of that system at test pressures greater  
than 1/2 psig. Isolate the cooktop from the  
gas supply piping system by closing the  
individual manual shut-off valve to the  
cooktop during any pressure testing of the gas  
supply piping system at test pressures equal to  
or less than 1/2 psig.  
Turn on the gas. Check for leaks using a  
liquid leak detector at all joints in the system  
(the pressure test nipple is adjacent to the  
gas inlet pipe on the rear right hand side of  
the cooktop bottom.  
Do not use a flame to check for  
CAUTION  
gas leaks.  
PRUDENCE  
IL NE FAUT PAS UTILISER  
DE FLAMME POUR VÉRIFIER S’IL Y A  
DES FUITES.  
10  
Installation  
G as Downdraft Cooktop  
Step  
Note: If the cooktop is installed into a 36"  
base cabinet, the pressure regulator MUST BE  
installed to the bottom of the cooktop before  
the cooktop is placed into the cabinet.  
4
Install the  
Cooktop  
Remove packaging from the cooktop.  
To insure a good fit, position the cooktop  
over the cutout opening and carefully lower  
into place. Check edges all the way around  
to be sure all cutout edges are concealed  
and there are no gaps.  
Carefully, lift and remove the cooktop.  
Cut a 3/16" gasket strip in half. Peel off the  
backing and apply to the underside of the  
glass cooktop edge.  
1/16"  
on each side at least 3/8" from the back  
and as close to the edge as possible without  
protruding.  
Apply the other gasket strip to the underside  
of the glass at the front of the cooktop.  
Remove remaining adhesive backing.  
Position the cooktop over the opening,  
making sure that the power cord is dropped  
into the cabinet.  
3/8"  
Lower the cooktop into the cutout, pressing  
gently and evenly to seat.  
Gasket  
Note: If the cooktop is installed in a 36" base  
cabinet, the mounting brackets cannot be  
used because of interference with the cabinet  
sides. In this case, the cooktop can be secured  
to the cabinet with angle brackets (not  
supplied).  
Countertop  
Remove one screw at the bottom of the  
cooktop body on both sides and secure the  
bracket with those screws. Then, secure the  
brackets to the cabinet sides.  
Insert hold-down bracket into highest slots  
on the right and left sides of the cooktop:  
– Cooktop has three slots, the highest  
available will depend on the thickness of  
the countertop.  
Secure the brackets to the underside of the  
countertop with screws provided.  
11  
Installation  
G as Downdraft Cooktop  
Connect the 3-pin plastic plug from the  
blower/motor assembly to the 3-pin plastic  
socket on the underside of the vent, next to  
the conduit.  
Slide the metal cover over the connection  
and secure with screws.  
Step  
5
Electrical  
Connections  
Connect the 6-pin plastic plug from the  
downdraft assembly to the 6-pin plastic  
socket on the underside of the cooktop, next  
to the power cord.  
Slide the metal cover over the connection  
and secure with screws.  
Electrical  
6-Pin Socket  
Service  
Plate  
Electrical  
Supply Cord  
Pressure  
Test Point  
6-Pin  
Plug  
Pressure  
Regulator  
Metal Cover  
Plug power cords into properly grounded  
receptacle.  
Step  
6
Connect  
Power  
Medium Head  
And Cap  
Assemble burner as shown. Check to be sure  
that burner heads are securely seated and  
caps are positioned as shown.  
Step  
Medium Head  
And Cap  
Small Head  
And Cap  
7
Burner Grate  
Assemble  
Burners,  
Check  
Medium Head  
And Cap  
Large Head  
And Cap  
Front  
Check for proper ignition:  
Push in one control knob and turn 90° to  
Burner Cap  
Ignition  
HIGH position.  
Burner Head  
Burner Bowl  
The igniter will spark and the burner will  
light; the igniter will cease sparking when  
the burner is lit.  
Make sure slot in burner head  
is positioned over electrode  
First test may require some time, while air is  
flushed out of the gas line.  
Turn knob to OFF.  
Electrode  
Repeat the procedure for each burner.  
12  
Installation  
G as Downdraft Cooktop  
To raise the vent, turn the VENT knob to  
RAISE/LOWER.  
Step  
Hold the knob until the vent begins to raise.  
– The vent will automatically stop when it is  
fully extended.  
8
Install  
Filters  
Check  
Operation of  
Downdraft  
Tip filter into the opening and pull straight  
down so that the filter rests on slides.  
Slide the filter to the right side.  
Tip the other filter into the opening and  
pull straight down.  
To turn the fan on, turn the FAN knob to  
HIGH.  
Continue turning the FAN knob to select  
a fan speed between HIGH and LOW.  
Note: It is not necessary to turn the fan OFF  
before lowering the vent. The fan will auto-  
matically turn off when the vent is lowered.  
When the fan is not turned off before lower-  
ing the vent, it will automatically come on at  
the previously selected speed when the vent is  
fully raised.  
To lower the vent, turn the VENT knob to  
RAISE/LOWER. Hold the knob until the vent  
begins to lower.  
13  
JXRB57 Kit  
For Indoor Remote Blower Locations  
Tools and Materials required:  
• Pencil  
• Measuring tape  
• Drill with appropriate bits  
• Nut driver  
• Junction box  
• Wire nuts  
• Safety glasses  
• 3-1/4" x 10" to 6" round transition.  
• 3-1/4 x 10" duct, (or 6" round) sufficient length to reach  
the outdoor wall cap or roof cap.  
• Electrical cable and connectors, sufficient length to  
connect the downdraft vent to the remote blower  
location. 14-guage min. is recommended, must conform  
to local codes.  
This kit provides for the installation of the  
blower and motor outside of the cabinet, such  
as below the floor. Use this kit for indoor  
remote installations only.  
Parts Supplied  
Note: A 3-1/4" x 10 transtion to 6" round is  
required.  
Hanger Brackets  
Package of screws  
Outlet Plate  
Cover Plate  
• Flatten the shipping box to use as a pad.  
• Place the unit on its back onto the protec-  
tive pad.  
• Remove the wire box on the plenum.  
• Cut the blower leads approximately 3" from  
the plug on the end of the vent.  
• Remove the blower conduit by loosening the  
screw on the fitting.  
Step  
3"  
1
Prepare  
the Vent  
Blower Wire Box  
Loosen  
Screw  
• Set aside the 3" wire leads with plug, wire  
box and screws.  
Blower Conduit  
14  
JXRB57 Kit  
For Indoor Remote Blower Locations  
Important: Save any  
unused parts. If the  
appliance is relocated at  
a later time, parts may be  
needed.  
• Remove the 4 nuts holding the blower to the  
mounting plate. One nut is hidden inside  
the outlet. Remove blower.  
• Remove the blower mounting plate.  
• Remove 2 screws along the bottom of the  
blower box which are visible once blower  
plate is removed.  
Step  
1
(continued)  
• Carefully, turn the unit over to access the  
back side.  
• Remove 4 screws along the top of the blower  
box.  
• Turn unit over and remove the 4 screws  
along the top.  
• Remove the blower box.  
Hidden  
Screws  
• Retain all screws.  
Blower Box  
Blower  
Mounting  
Plate  
Blower  
• Determine location of the blower and  
motor.  
– The blower will fit between floor joists, 16”  
on center. Or, provide a surface to attach  
the entire assembly to the underside of the  
floor.  
• Secure mounting brackets to the top of the  
blower with screws and nuts. One bracket in  
each corner, as illustrated.  
14-1/2"  
Step  
2
Determine  
Blower  
Location  
– Set the bracket at the ends of the curved  
slots to reach a 14-1/2” span between floor  
joists, or adjust for your installation  
situation.  
• Mark the installation location and cut hole  
for 6” round duct.  
• Secure the blower to the joists.  
15  
JXRB57 Kit  
For Indoor Remote Blower Locations  
Step  
3
Downdraft  
Connect  
Ductwork  
Duct Adapter  
Outlet Cover  
• The downdraft plenum can discharge from  
either the right or left side. Select the side  
that provides the best alignment to ductwork  
extending to the blower assembly below.  
– For a left side discharge, install the outlet  
plate to the bottom of the plenum on the  
left side. Install the cover plate to the  
bottom of the right side. Reverse plates for  
a right side discharge.  
• Connect the plenum to the ductwork.  
A transition is required to connect the  
3-1/4" x 10" duct to the 6" round inlet on  
the blower.  
• Tape to seal all joints.  
.
• Use electrical cable and connectors that  
conform to local codes (14 gauge min. is  
recommended). Use a length to reach  
between the vent and the blower/motor  
location.  
• Attach the wire box removed from the  
blower conduit to the end of new wiring.  
• Use wire nuts to secure the wire to the 3"  
remaining wires with plug.  
Step  
Plenum  
Provided  
Mounting  
Screws  
4
Blower  
Wire  
Box  
Connect  
Electrical  
3-Wire  
Connectors  
Wire Nuts  
Wiring to Blower Junction Box  
• Insert the plug into the mating plug on the  
vent.  
• Reinstall wire box with original screws.  
• Install a junction box withing reach of the  
blower conduit.  
• Use a conduit fitting to secure conduit to  
junction box. The red plastic anti-short  
bushing should be secured to the end of the  
conduit.  
• Use wire nuts to connect wires.  
16  
JXBC57 Kit  
For Outdoor Remote Blower Locations  
Materials Required  
(not supplied)  
• Approved liquid tight service connections for use  
between the wire compartment on the base and inside  
the structure.  
• 7 wire nuts or other approved connectors.  
• Six 5/16" dia. fasteners compatible with the type of  
material the base is being fastened to.  
• 3-1/4" x 10" to 6" round transition.  
• 3-1/4 x 10" duct, (or 6" round) sufficient length to reach  
the outdoor installation location.  
• Electrical cable and connectors, sufficient length to  
connect the downdraft vent to the remote blower  
location. 14-guage min. is recommended, must  
conform to local codes.  
Tools required:  
• Pencil or chalk  
• Measuring tape  
• Drill with appropriate bits  
• Phillips head screwdriver  
• 1/4" Nut driver  
• Wire nuts  
• Safely glasses  
The blower and motor assembly can be  
mounted on an outside wall. This kit provides  
a means to mount the blower outside with a  
protective cover.  
• Separate the cover from the base assembly  
by removing 5 screws. Retain screws.  
Step  
• Check to be sure all parts are present.  
1
Check  
Parts  
Supplied  
Package of screws  
4 Hanger Brackets  
Cover  
Cover Plate  
Outlet Plate  
Base  
Assembly  
Junction Box  
Outlet Pan  
Damper  
17  
JXBC57 Kit  
For Outdoor Remote Blower Locations  
16"  
• The base is designed to be mounted to studs  
on 16" centers. Use the dimensions shown to  
determine the location of the ducting and  
wiring through the wall.  
– Or Place the base against the exterior wall  
and mark the 6 mounting locations, the 6"  
duct location and the hole for the wiring.  
Use pencil or chalk.  
6 Holes  
For 5/16  
Fastners  
6-11/16"  
Step  
2
Align  
Mark  
Mounting  
Location  
4-3/4"  
With Duct  
Opening  
On Outside  
Wall  
6"  
• The bottom of the base assembly must be  
10" min. above the ground. There should be  
no obstructions to the discharge from the  
damper.  
12-15/16"  
12"  
• Cut a 6-1/8" dia. hole in the vertical struc-  
ture to accommodate a 6" round duct  
another hole for the wiring.  
• Drill 6 pilot holes through the wall for the  
6/16" fasteners.  
1-13/16"  
10" Min  
Above Ground  
CAUTION: When cutting or drilling into a wall or ceiling,  
do not damage electrical wiring or hidden utilities.  
Check for interference with floor joists and stud walls. If  
necessary, locate the base to provide a secure  
installation.  
• Place a 6" round duct through the hole  
extending approximately 3" from the wall to  
provide a proper seal with the blower.  
Secure the duct to the building structure to  
prevent it from being pushed back when the  
blower is installed.  
• Flatten the shipping box to use as a pad.  
• Place the unit on its back onto the protective  
pad.  
• Remove the wire box on the plenum.  
• Cut the blower leads approximately 3" from  
the plug on the end of the vent.  
• Remove the blower conduit by loosening the  
screw on the fitting.  
3"  
Step  
3
Prepare  
the Vent  
Blower Wire Box  
Loosen  
Screw  
• Set aside the 3" wire leads with plug, wire  
box and screws.  
Blower Conduit  
18  
JXBC57 Kit  
For Outdoor Remote Blower Locations  
• Remove the 4 nuts holding the blower to the  
mounting plate. One nut is hidden inside  
the outlet. Remove blower.  
• Remove the blower mounting plate.  
• Remove 2 screws along the bottom of the  
blower box which are visible once blower  
plate is removed.  
Step  
3
(continued)  
Hidden  
Screws  
• Carefully, turn the unit over to access the  
back side.  
• Remove 4 screws along the top of the blower  
box.  
• Turn the unit over and remove the 4 screws  
along the top.  
• Remove the blower box.  
• Retain all screws.  
Important: Save any unused parts. If the  
appliance is relocated at a later time, parts  
may be needed.  
Blower Box  
Blower  
Mounting  
Plate  
Blower  
• The downdraft plenum can discharge from  
either the right or left side. Select the side  
that provides the best alignment to ductwork  
extending to the blower assembly.  
– For a left side discharge, install the outlet  
plate to the bottom of the plenum on the  
left side. Install the cover plate to the  
bottom of the right side. Reverse plates for  
a right side discharge.  
Downdraft  
.
• A transition is required to connect the  
3-1/4" x 10" duct to the 6" round inlet on  
the blower.  
Duct Adapter  
• Tape to seal all joints.  
Outlet Cover  
• Check that the red plastic anti-short bushing  
is secured in the end of the conduit. Install  
the blower conduit into the conduit connector  
on the junction box and tighten the screw.  
• Install a liquid tight fitting in the hole of the  
wire compartment on the base, sized to fit wire  
being used.  
Step  
Blower  
Conduit  
4
Connect  
Blower  
Wires  
Red Anti-  
Short Bushing  
Conduit  
Connector  
Base  
Assembly  
Wires  
to Vent  
Wire  
Compartment  
• Run the electrical wiring from the downdraft  
vent to the wire compartment.  
• Attach the green ground leads from the wire  
compartment, connecting one to the green  
ground lead on the blower and the other to  
the ground lead of the wiring from the  
downdraft vent.  
Green Ground  
Leads  
Strain  
Relief  
• Connect the neutral (white) and power lead  
(black) from the blower to the leads from the  
downdraft vent.  
• Use wire nuts to connect wires.  
19  
JXBC57 Kit  
For Outdoor Remote Blower Locations  
Plenum  
• Use electrical cable and connectors that  
conform to local codes (14 gauge min. is  
recommended). Use a length to reach  
between the vent and the blower/motor  
location.  
• Attach the wire box removed from the  
blower conduit to the end of new wiaring.  
• Use wire nuts to secure the wire to the 3"  
remaining wires with plug.  
Provided  
Mounting  
Screws  
Step  
5
Blower  
Wire  
Box  
Connect  
Electrical  
3-Wire  
Connectors  
Wire Nuts  
Wiring to Blower Junction Box  
• Insert the plug into the mating plug on the  
vent.  
• Reinstall wire box with original screws.  
• Mount the blower onto the mounting plate.  
Secure with original nuts.  
Step  
• Install damper to bottom of outlet with 4  
screws.  
6
Mount  
Blower  
• Place the cover over the the assembled kit  
and secure with 16 screws.  
Step  
7
Finalize  
Installation  
20  
Notes  
21  
Notes  
22  
Notes  
23  
NOTE: While performing installations described in this book,  
safety glasses or goggles should be worn.  
To obtain specific information concerning any  
Monogram product or service, call GE Answer Center®  
consumer information service at 800.626.2000—any  
time, day or night.  
For Monogram local service in your area, call  
1-800-444-1845.  
NOTE: Product improvement is a continuing endeavor at General  
Electric. Therefore, materials, appearance and specifications are  
subject to change without notice.  
Pub. No. 49-8999-1  
Part No. 183D5580P082  
2000 GE Appliances  
(N.D. 505) 5/00  
®
Monogram.  
General Electric Company  
Louisville, KY 40225  
Printed in Mexico  

GE 25898 User Manual
GE 17 Feb User Manual
FUNAI MJ419TG, MJ413TG User Manual
Electrolux E30IC75FSS User Manual
Diamond Multimedia Radeon 9600 PRO User Manual
BenQ Computer Monitor GL2240M User Manual
AT T 9050 User Manual
Asus P8C WS User Manual
AMD KM780V User Manual
Accton Technology EN2216 2 User Manual