T
S
A
L
H
B
O
T
Model 1300/1400
OWNERS MANUAL
SOLID FUEL
WARM AIR FURNACE
*FOR PARALLEL INSTALLATION WITH
EXISTING FORCED AIR-GAS OR OIL
FIRED FURNACE (U.S. ONLY)
*FOR INSTALLATION AS A CENTRAL FURNACE
*CERTIFIED UNDER ANSI/UL 391 & CAN/CSA-B366.1-M91
IMPROPER INSTALLATION MAY VOID
YOUR WARRANTY
CAUTION:
READALLINSTRUCTIONSCARE-
FULLY BEFORE STARTING THE
INSTALLATION OR OPERATING
THE FURNACE
DO NOT USE THIS FURNACE
IN A MOBILE HOME OR TRAILER
UNITED STATES STOVE COMPANY
A
E
S
T
S
S
D
T
E
O
227 Industrial Park Road
P.O.Box 151
South Pittsburg, TN 37380
(423) 837-2100
T
VE
I
N
U
S
C
U
S
C
O
Y
N
M
P
A
851486 02/01
Caution Labels
Your Furnace has the following labels. Read and Obey all labels.
DANGER: RISK OF FIRE OR EXPLOSION.
DO NOT burn garbage, gasoline, drain oil, or other flammable liquids.
WARNING: FIRE HAZARD.
DO NOT operate with fire draft exceeding .06 inches w.c.
DO NOT operate with fuel loading or ash removal doors open.
DO NOT store fuels, paints, thinners, flammable liquids, or other highly
volatile substances in the furnace room.
CAUTION: HOT SURFACES
Keep children away.
Do not touch during operation.
_______________________CAUTION!________________________
INSPECT FLUE PIPES, FLUE PIPE JOINTS AND FLUE PIPE SEALS
REGULARLY TO ENSURE THAT SMOKE AND FLUE GASES ARE
NOT DRAWN INTO, AND CIRCULATED BY, THE AIR CIRCULATION
SYSTEM.
CAUTION!
CLEANOUT OF THE HEAT EXCHANGER, FLUE PIPE, CHIMNEY,
AND DRAFT INDUCER (IF USED), IS ESPECIALLY IMPORTANT AT
THE END OF THE HEATING SEASON TO MINIMIZE CORROSION
DURING THE SUMMER MONTHS, CAUSED BY ACCUMULATED
ASH.
SAFETY NOTICE: If this heater is not properly installed, a house
fire may result. For your safety, follow the installa-
tion directions. Contact local building or fire offi-
cials about restrictions and installation inspection
requirements in your area.
If not already installed, we recommend that smoke
detectors be installed.
3
Rules for safe installation and operation
Read these rules and the instructions carefully. Failure to follow them will cause a hazard that
could result in death, serious bodily injury, and/or property damage.
1. Check your local codes. The installation must comply with their rulings.
2. Do not install this furnace in a mobile home or trailer.
3. Always connect this furnace to a chimney and vent to the outside. Never vent to another room
or inside a building.
4. Do not connect this furnace to an aluminum Type B gas vent. This is not safe and is prohibited
by the National Fire Protection Association Code. This furnace requires a masonry or a UL/ULC
Listed Factory Built Chimney for residential type or Building Heating Appliance Chimney. Use a 6"
diameter chimney or larger, that is high enough to give a good draft. (See page 7)
5. Be sure that if a masonry chimney is used, it is safely constructed and in good repair. Have the
chimney inspected by the Fire Department or an inspector.
6. Inspect chimney connector and chimney before and frequently during the heating season for any
deposit of creosote or soot which must be removed (See Chimney Maintenance, page 18).
7. Provide air for combustion into the room where the furnace is located. If the intake is not in the
same room, air must have free access to the room.
8. CAST IRON PARTS MUST BE "SEASONED" TO AVOID CRACKING, BUILD ONLY SMALL
FIRES ON FIRST USE.
9. To prevent injury, do not allow anyone to use this furnace who is unfamiliar with the correct
operation of the furnace.
10. Forfurtherinformationonusingyourfurnacesafely, obtainacopyofthe NationalFireProtection
Association (NFPA) publication "Chimney's, Fireplaces and Solid Fuel Burning Appliances" NFPA
211. The address of the NFPA is Batterymarch Park, Quincy, MA 02269. For more information on
Canadian installation, obtain a copy of CAN/CSA-B365-M91 Installation Code for Solid-Fuel-
Burning Appliances and Equipment.
11. Keep the ashpit section free of excess ashes. Do not allow ashes to stack higher than the sides
of the ash pan.
12. DISPOSAL OF ASHES- Place ashes in a metal container with a tight fitting lid. Keep the closed
containeronanoncombustiblefloororontheground,wellawayfromallcombustiblematerials. Keep
the ashes in the closed container until all cinders have thoroughly cooled. The ashes may be buried
in the ground or picked up by a refuse collector.
13. CAUTION- The special paints used on your furnace may give off some smoke while they are
curing during first few fires., Build small fires at first. The metal used in construction of the furnace
and duct work has a light coating of oil. This could give off smoke and/or odor from registers when
furnace is used for the first time. This should disappear after a short period of time. Once this burn-
off has occurred, it should not reoccur.
14. CARING FOR PAINTED PARTS- This furnace has a painted outside jacket, which is durable,
but it will not stand rough handling or abuse. When installing your furnace, use care in handling.
Clean with soap and warm water when furnace in not hot. DO NOT use any acids or scouring soap,
as these wear and dull the finish. DISCOLORATION WILL OCCUR IF THE FURNACE IS
OVERHEATED. FOLLOW OPERATING INSTRUCTIONS CAREFULLY.
15. Keep the feed and ash doors closed at all times except while tending the furnace.
Your Furnace is designed to be installed in a parallel air flow arrangement with a gas or oil-fired
forced air upflow-type central furnace, or it may be installed as a central furnace.
4
HOW THE FURNACE FUNCTIONS
PARALLEL INSTALLATION: (U.S. ONLY)
Your HOTBLAST Furnace is designed
tobeasupplementalorcentralheatingsource
for your home. This Solid Fuel Furnace may
be installed in conjunction with a properly
operating central furnace that is listed or cer-
tified in accordance with nationally recog-
nized safety standards and equipped with the
required controls and other safety features
and which has been installed in accordance
with appropriate standards of the National
Fire Protection Association with installation
clearances specified in the furnace name-
plate marking. The installation must be ac-
complished by a qualified agency (one who is
engaged in, and is responsible for, or is thor-
oughly familiar with the installation and op-
eration of the gas, oil, and solid fuel burning
heating appliances, who is experienced in
suchwork,familiarwithalltherequirementsof
the authority having jurisdiction.) The instal-
lation shall be in strict accordance with the
manufacturer's installation instructions fur-
nished with the solid fuel furnace.
(See Optional Wiring Diagram, Page 16, Fig.
15) The design is such that when the blower
comes on, the blower on the central system
also comes on. The blower will only come on
when the temperature in the plenum has
reached the setting on the blower control.
Thisistoinsurethatthereissufficientwarmair
in the system to make it efficient for the unit to
operate. When the central system thermostat
calls for heat, the central system will operate
by the burner igniting and the blower coming
on. Itispossiblethatbothsystemswilloperate
simultaneously. Itisrecommendedthatforthe
most efficient use of your HOTBLAST Fur-
nace, that it be fired as much as possible in
order to reduce the demand on your existing
central heating system. This unit has an op-
tional forced draft kit that operates from a wall
thermostat. Whenthetemperaturefallsbelow
the setting on the wall thermostat, the forced
draftwillcomeon(U.S.StoveOption11/DKU)
The warm air supply outlet of the
HOTBLAST Furnace shall not be connected
to the cold air return of the central furnace,
because the possibility exists of components
of the central furnace overheating and caus-
ing the central furnace to operate other than is
intended.
The chimney connector of the furnace is
to be installed to provide clearances to com-
bustible material not less than specified in the
individual classifications and marked on the
furnace. The chimney connector must be
connected to a chimney suitable for use with
residentialtypeorbuildingheatingappliances
which burn solid fuel.
SERIES INSTALLATION: (U.S. & CANADA)
This type of installation uses only the blowers
of the existing central furnace. The solid fuel
fan/limitcontrolmustalsocontrolthefunctions
of the existing furnace. All electrical power
must come from a single branch circuit (See
Fig. 15).
The Furnace is designed to operate in
either parallel or series air flow arrangement
with the central furnace or as a central fur-
nace.
CENTRAL FURNACE INSTALLATION: As
a central furnace, the unit functions indepen-
dently of any other system. The blower will
come on when the plenum temperature
reaches the setting on the blower control.
5
DIMENSIONS OF FURNACE
41"
Figure 1A
1300
24-7/8"
21-1/32"
1-3/4"
33-7/8"
40-11/16"
9"
49-1/8"
Figure 1B
1400
32-1/8"
24-1/16"
1-3/4"
33-7/8"
40-11/16"
9"
6
Locating the Furnace
18"
6" CHIMNEY
1.The furnace should be located in the
same room as the central system
and as close as possible, but not
closer than 9". There should be no
wall between the furnace and the
warmairoutletductthatisconnected
directly to the warm air outlet plenum
of the central furnace. (See Fig. 2)
CENTRAL
FURNACE
12"
9"
48"
2.
The unit will require installation with
the following clearances:
Figure 2
Unit to sidewall............12"(305mm)
Unit to backwall...........30"(760mm)
Chimney connector pipe to sidewall
.....................................18"(460mm)
Chimney connector pipe to backwall
.....................................18"(460mm)
Hot air ducts to combustibles
.......................................6"(150mm)
(Refer to Fig. 2 & 3)
18"
6" SOLID DAMPER
6" BAROMETRIC
DRAFT REGULATOR
(OPTIONAL)
18"
Place the furnace on a noncombus-
tible floor.
3.
4.
Check figures 2 and 3. Be sure you
have the clearances shown from the
furnace and the connector pipe to
combustible surfaces. If you have a
solid brick or stone wall behind your
furnace, you can place the furnace
ascloseasyouwishtothewall. Ifthe
wall is only faced with brick or stone,
treat it as a combustible wall.
NON-COMBUSTIBLE FLOOR
Figure 3
7
THIMBLE
6" ELBOW
6" SOLID DAMPER
6" BAROMETRIC
DRAFT REGULATOR
(OPTIONAL)
6" CHIMNEY
CONNECTOR
NON-COMBUSTIBLE
WALL
6" ELBOW
Chimney Connection
Fig. 4
MASONRY CHIMNEY
Before using an existing masonry chimney, clean the chimney and inspect the flue liner to be sure
it is safe to use. Make repairs before attaching the furnace. See page 4, item 5. Look at Fig. 4.
The connector pipe and fittings you will need to connect directly to a masonry chimney are shown.
The chimney connection should be as short as possible.
If the connector pipe must go through a combustible wall before entering the masonry chimney,
consult a qualified mason or chimney dealer. The installation must conform to local fire codes, and
N.F.P.A. 211.
DO NOT CONNECT THIS FURNACE TO A CHIMNEY FLUE SERVING ANOTHER APPLI-
ANCE.
The chimney used for a furnace must not be used to ventilate the cellar or basement. If there is
a cleanout opening at the base of the chimney, close it tightly.
REFER TO CHIMNEY
2' MIN.
MANUFACTURER'S
INSTRUCTIONS AND
PARTS.
10'
3' MIN.
Fig. 5
6" SOLID DAMPER
6" BAROMETRIC
DRAFT REGULATOR
(OPTIONAL)
6" CHIMNEY CONNECTOR
6" ELBOW
LISTED FACTORY BUILT CHIMNEY
Carefully follow chimney manufacturer's instructions. Use only a Listed Residential Type or
Building Heating Appliance Chimney. If your chimney starts at the ceiling (Fig. 5), you will need
enough 6" pipe to reach the ceiling.
The top of the chimney must be at least 3 feet above the roof and be at least 2 feet higher than any
point of the roof within 10 feet (Fig. 5).
8
Rules for Connector
Pipe Installation
NOTE:
1. The crimped end of the chimney connector fits
inside the furnace flue collar. Install additional chim-
ney connectors and elbow with the CRIMPED END
TOWARD THE FURNACE. This will allow any
condensation in the flue to run back into the furnace.
Use 6" dia. steel pipe and elbows for connection to
chimney. Never use less than 26 gauge and al-
though blued steel is satisfactory, high temp painted
black is much more desirable.
A flue pipe shall not pass through an attic,
roofspace,closetorsimilarconcealedspace,
a floor or ceiling of combustible construc-
tion. Where passage through a wall or parti-
tion is desired, installation must conform
with UL standards.
2. Slope any horizontal pipe upward toward the
chimney at least 1/4 inch for each foot of horizontal
run.
3. You must have at least 18 inches of clearance
between any horizontal piping and the ceiling.
(See Fig. 3)
4. The chimney connector must not extend into the
chimney flue. (See Fig. 6)
5. Seal each chimney connector pipe joint with fur-
nace cement. Also seal the pipe at the chimney.
6. Use 3 sheet metal screws at each chimney pipe
joint to make the piping rigid.
RIGHT
WRONG
WRONG
Fig. 6
7. The chimney connector may include a section for
abarometricdraftregulatorbetweenthefurnaceand
the chimney (Fig. 4,5, &7). The barometric draft
regulator must be installed in the same room (same
pressure zone) as the furnace.
8. Install the barometric draft regulator strictly in
accordance with the instructions that are provided
with the barometric draft regulator.
9. A solid damper must be used in the chimney
connecting pipes between the flue collar and the
chimney. When used in conjunction with a baromet-
ric draft regulator, the solid damper must be placed
between the barometric and the chimney. (See Fig.
4,5,7)
NON-COMBUSTIBLE
INSTALLATION PER
NFPA 211
6" SOLID DAMPER
6" BAROMETRIC
DRAFT REGULATOR
(OPTIONAL)
MEASURE FLUE
DRAFT HERE
Adjusting the Barometric Draft Regula-
tor
1. Drill a hole in the chimney connector within 18" of
the flue collar below the barometric draft regulator
just large enough for the tube of the manometer.
2. Build a fire after all chimney connections have
been made.
Fig. 7
3. Use a manometer to measure the draft in the flue.
4. Adjust the Barometric Draft Regulator to obtain a
draftof0.05-0.06"W.C. understablefireconditions.
9
CONNECTION OF CHIMNEY CONNECTOR TO A MASONRY CHIMNEY THROUGH A COMBUSTIBLE WALL
Figure 8 shows how to connect the chimney connector of a heater to a masonry chimney through a combustible wall.
There are five allowable ways that a chimney connector can be connected to a masonry chimney by passing through
a combustible wall. NFPA Standard 211 allows the following wall pass-through systems.
FIGURE 8 -
CONNECTION OF CHIMNEY CONNECTORTO A MA-
SONRY CHIMNEYTHROUGH A COMBUSTIBLEWALL
CEILING
SEE PARTS A, B,
C, D, AND E OF
THIS FIGURE FOR
OPTIONS.
CHIMNEY CONNECTOR
MASONRY CHIMNEY
CONSTRUCTED TO
NFPA 211
TO
HEATER
COMBUSTIBLE WALL
FLOOR
PROTECTOR
AIRTIGHT
CLEANOUT
DOOR
(FIGURE 8 CONTINUED ON NEXT PAGE)
10
PART A, FIGURE 8
(FIGURE 8 CONTINUED ON NEXT PAGE)
MINIMUM CHIMNEY CLEARANCE TO
BRICK AND COMBUSTIBLES IS 2 IN.
MINIMUM CLEARANCES 12 IN.
OF BRICK ALL AROUND
CHIMNEY CONNECTOR
TO HEATER
FIRE CLAY LINER
MINIMUM 12 IN.
(5/8" MIN.WALL THICKNESS)
TO COMBUSTIBLES
MASONRY CHIMNEY
CONSTRUCTED TO
NFPA 211
MIN. 3-1/2" THICK BRICK
MASONRY WALL
1. Use a minimum 3-1/2" thick brick masonry wall framed into the combustible wall. A fireclay liner (ASTM C315 or
equivalent) having a 5/8" minimum wall thickness must be used and it must be at least 12" away from any material
that could catch fire. The inside diameter of the fireclay liner shall be sized for the proper snug fit of a 6" diameter
chimney connector pipe. The fireclay liner shall run from the outer surface of the brick wall to, but not beyond, the
inner surface of the chimney flue and shall be firmly cemented in place. See Part A of Figure 8.
2. Use a solid insulated listed factory-built chimney length having an inside diameter of 6" and having 1" or more of
solid insulation. There must be at least a 9" air space between the outer wall of the chimney length and any
combustible materials. The inner end of the chimney length shall be flush with the inside of the masonry chimney
flue shall be sealed to the flue and to the brick masonry penetration with nonwater-soluble refractory cement. Sheet
steel supports which are at least 24 gauge(0.024") in thickness shall be securely fastened to wall
surfaces on all sides. Fasteners between supports and the chimney length shall not penetrate the chimney liner.
See Part B of Figure 8.
3. Use a 10" diameter ventilated thimble made of at least 24 gauge(0.024") steel having two 1" air channels. The venti-
lated thimble must be separated from combustible materials by a minimum of 6" glass fiber insulation. The opening
in the combustible wall shall be covered and the thimble supported with sheet steel supports which are at least 24
gauge (0.024") in thickness. The sheet steel supports shall be securely fastened to wall surfaces on all sides and
shall be sized to fit and hold the chimney section. Fasteners used to secure chimney sections shall not penetrate
chimney flue liner. See Part C of Figure 8.
4. Use an 8" inside diameter solid insulated listed factory-built chimney length which has 1" or more of solid insulation.
The minimum length of this chimney section shall be 12" and will serve as a pass-through for the 6" diameter
chimney connector. There must be at least a 12" air space between the outer wall of the chimney section and any
combustible materials. The chimney section shall be concentric with and spaced 1" away from the chimney connec
tor by means of sheet steel support plates on both ends of the chimney section. The opening in the combustible wall
shall be covered and the chimney section supported on both sides with sheet steel supports which are at least 24
gauge (0.024") in thickness. The sheet steel supports shall be securely fastened to wall surfaces on all sides and
shall be sized to fit and hold the chimney section. Fasteners used to secure chimney sections shall not penetrate
chimney flue liner. See Part C of Figure 8.
5. A listed factory-built wall pass-through system may be purchased and installed according to the instructions pack
aged with it to provide a safe method of passing the chimney connector through a combustible wall for connection
to a masonry chimney.
Additional requirements pertaining to Figure 8 and the above wall pass-through systems:
1. Insulation material used as part of wall pass-through system shall be of noncombustible material and shall have a
thermal conductivity of 1.0 Btu • in./ft.² • °F (4.88 kg • cal/hr • m² • °C) or less
2. All clearances and thicknesses are minimums: larger clearances and thickness are acceptable.
3. A chimney thimble, as shown for 3" and 4" above (Parts C and D respectively of Figure 8) shall be for types "3" and
4" connections to facilitate removal of the chimney connector for cleaning. The chimney thimble shall be of ASTM
C315 fireclay with 5/8" minimum wall thickness , or material or equivalent durability. The inside diameter of the
thimble shall be sized for the proper snug fit of a 6" diameter chimney connector pipe. The thimble shall be installed
without damage to the chimney flue. The thimble shall extend through the chimney wall to, but not beyond, the
inner surface of the chimney flue and shall be permanently cemented in place with high temperature cement.
4. A chimney connector to a masonry chimney, except for 2" above (Part B of Figure 8), shall extend through the wall
pass-through system to the inner face of the chimney flue, but not beyond. It does not have to be fastened in place
so long as it cannot accidently be pulled out of the chimney or shoved into the chimney flue. If fasteners are used
to secure the chimney connector to a masonry chimney, the fasteners shall not penetrate the chimney flue liner.
5. Any material used to close up any opening for the connector shall be noncombustible.
11
PART B
FIGURE 8 -
MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO
SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN.
(FIGURE 8 CONTINUED)
FACTORY-BUILT
CHIMNEY LENGTH
MINIMUM CLEARANCE
9 IN. ALL AROUND
NONSOLUBLE
REFACTORY
CEMENT
CHIMNEY CONNECTOR
TO HEATER
CHIMNEY LENGTH
FLUSH WITH INSIDE
OF FLUE
USE CHIMNEY MFRS. PARTS TO
ATTACH CONNECTOR SECURELY
AIR SPACE
9 IN. MINIMUM
SOLID INSULATED, LISTED
FACTORY-BUILT CHIMNEY LENGTH
MASONRY CHIMNEY CONSTRUCTED
TO NFPA 211
SHEET STEEL SUPPORTS
(24 GAUGE MIN. THICKNESS)
PART C
FIGURE 8
MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO
SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN.
24 GAUGE
VENTILATED THIMBLE WITH
TWO 1 INCH AIR CHANNELS
CHIMNEY THIMBLE
CHIMNEY CONNECTOR
TO HEATER
TWOVENTILATED AIR
CHANNELS EACH 1 INCH.
CONSTRUCTED OF
SHEET STEEL.
MINIMUM 6 IN. GLASS
FIBER INSULATION ALL AROUND
SHEET STEEL SUPPORTS
(24 GAUGE MIN. THICKNESS)
MASONRY CHIMNEY CONSTRUCTED
TO NFPA 211
MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO
SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN.
PART D
FIGURE 8
SHEET STEEL SUPPORTS
CHIMNEY SECTION
MINIMUM CLEARANCE
2 IN. ALL AROUND
1 IN. AIR SPACE TO
CHIMNEY LENGTH
CHIMNEY THIMBLE
CHIMNEY
CONNECTOR
CHIMNEY CONNECTOR
TO HEATER
SOLID INSULATED, LISTED
FACTORY-BUILT CHIMNEY
LENGTH (12 IN. LONG MIN.)
AIR SPACE
2 IN.
SHEET STEEL SUPPORTS
(24 GAUGE MIN. THICKNESS)
MASONRY CHIMNEY CONSTRUCTED
TO NFPA 211
PART E - (Figure 8)
In addition to the methods shown by A, B, C, and D of Figure 8, a listed factory-built wall pass-through system
may be purchased and installed according to the instructions packaged with it to provide a safe method of
passing chimney connector through a combustible wall for a connection to a masonry chimney.
CONNECTION OF CHIMNEY CONNECTORTO A MASONRY CHIMNEYWHEN CHIMNEY CONNECTOR
DOES NOT PASSTHROUGH A COMBUSTIBLEWALL
If the chimney connector does not have to pass through a combustible wall to get to a masonry chimney, simply connect
the chimney connector directly to the masonry chimney's chimney thimble as described and shown by parts C and D of
Figure 8. Remember, the chimney connector should extend into the chimney thimble to the innerface of the chimney flue
but not beyond; if the chimney connector is extended through the chimney thimble into the chimney flue, resistance to the
flow of smoke and gases up the chimney will occur; that flow resistance will have an adverse affect on the operation and
performance of the heater and venting system.
12
Assembly of Furnace
Your furnace requires the following items
to be assembled or installed by the service
person:
Feed Door Pull Handle
Feed Door Locking Handle
Blower(s) and Blower Controls
Electrical Connections
Remove all parts from inside the furnace
and inspect for damage, including the
firebrick as some breakage could occur
during shipment.
Assemble the feed door pull handle as
shown in Figure 9. Install thermostat
assembly and cover (complete with
handle) as illustrated in Figure 9.
Align thermostat control knob with flat on
thermostat control shaft and press onto
shaft. (See Fig. 9)
Attach feed door locking handle as in
Figure 10 with screws and nuts provided.
Note: Slotted holes are for adjustment of
handle. Adjust handle until some pres-
sure is required to lock feed door during
firing sequence.
1.
2.
Fig. 9
3.
4.
Fig. 10
Honeywell
FAN/LIMIT
CONTROL
Install Honeywell Fan/Limit Control on
rear of furnace cabinet as shown in Fig-
ure 11.
Remove blower(s) from carton(s). Re-
movejunctionboxcover. Attachclipnuts
as in Figure 10. Install blower(s) and
gasket(s) with 1/4"-20x3/4" bolts as
shown.
Wire right side blower first (See wiring
diagram, Fig. 12 & 13) and replace cover
on junction box on blower.
Wire left blower same as above and
replace cover.
5.
6.
4" ELECTRICAL
JUNCTION BOX
BLOWER
ASSEMBLY
7.
8.
Check operation of shaker grates with
grate handle before operating furnace.
CLIP NUTS
(DO NOT USE CLIP NUT
ON UPPER CENTER HOLE)
GASKET
(MODEL 1300 - 1 BLOWER,
MODEL 1400 - 2 BLOWERS)
Fig. 11
13
LOAD
FAN
LINE
LOAD
LIMIT
LINE
FAN "OFF"
INDICATOR
LIMIT
INDICATOR
BREAK OFF
JUMPER FOR
LOW VOLTAGE
FAN "ON"
INDICATOR
Honeywell
LIMIT SWITCH
R2
R1
WIRE NUTS
WIRE COLOR CODE
G - GREEN - GROUND
B - BLACK - POWER SUPPLY
IT
OWERPLY
- W
IT ANOL
R2 - BLACK - FAN CONTROL
W
-
W
H
E
-
P
S
U
P
R
1
H E
-
F
CONTR
GROUND
G
B
G
B
M1 - BLACK - BLOWER MOTOR
M2 - BLACK - BLOWER MOTOR
110
VAC,
60
W
W
HZ.
ELECTRICAL JUNCTION BOX
M2
M1
Fig. 12
BLOWER
MOTOR
IMPORTANT: POWER SUPPLY WIRING MUST NOT BE LESS THAN 90 CENTIGRADE.
LOAD
FAN
LINE
LOAD
LIMIT
LINE
FAN "OFF"
INDICATOR
LIMIT
INDICATOR
BREAK OFF
JUMPER FOR
LOW VOLTAGE
FAN "ON"
INDICATOR
Honeywell
LIMIT SWITCH
WIRE COLOR CODE
G - GREEN - GROUND
B - BLACK - POWER SUPPLY
R2
R1
W - WHITE - POWER SUPPLY
R1 - WHITE - FAN CONTROL
R2 - BLACK - FAN CONTROL
M1 - BLACK - BLOWER MOTOR
M2 - BLACK - BLOWER MOTOR
GROUND
G
B
G
B
110
VAC,
60
W
HZ.
W
ELECTRICAL JUNCTION BOX
M2
M1
M1
M2
BLOWER
MOTOR
BLOWER
MOTOR
WIRE NUT
(7 PLACES)
Fig. 13
IMPORTANT: POWER SUPPLY WIRING MUST NOT BE LESS THAN 90 CENTIGRADE.
14
Installation
Please see all methods of Installation in
Appendix at the rear of this booklet.
Pipe to combustible:
Sides: 18"(460mm)
Back: 18"(460mm)
This is a furnace, not a free standing stove. The installation must be made only on a noncom-
Youmustdirectheatedairfrom8"outletsawayfrom bustible floor.
the furnace, or it will not function properly.
d) Install the smoke pipe connector to the chim-
ney with 26-gauge pipe and elbows (to be pur-
1. This installation must be done by a qualified chased separately), maintaining the proper clear-
heating equipment installer.
ances for the specific model. Seal the smoke pipe
2. The installation is to be done in compliance with in the chimney with furnace cement. (The chimney
NationalFireProtectionAssociationinstallationstan- connector shall be securely supported, and joints
dards: No. 89M, 90B, 211, 70 (National Electrical fastened with sheet metal screws or rivets.)
Code)andUniformMechanicalCode913,6-4,inthe
e) Install 8" diameter heat pipe to plenum of the
states where applicable. (Their code offers con- central hot air furnace. Use 26-gauge pipe and
necting smoke pipe connectors into chimney with connectors (to be purchased separately). (See Fig.
other fuel burning appliances.)
14) If central air conditioning is installed in the
3. Rooms large in comparison with size of the plenum, install heat pipe above the air conditioning
appliance:
unit. Secure heat pipe connection with supports
a)Wood or Coal Burning Furnace needs air for and sheet metal screws.
combustion and circulation to house.
f) Connect electrical supply in the electrical junc-
b) Provision must be made to make up this air tion box that is mounted on the back of the Furnace.
and not starve gas or oil furnace of combustion air. See Wiring Diagram (Fig. 12 or Fig. 13). Remove
c) Have "Authority Having Jurisdiction" deter- the cover from electrical junction box and connect
mine that air is of adequate makeup. (Reference power supply wires to wires designated, using wire
N.F.P.A. Nos. 30&54, Code for Installation of Gas & nuts. The power cord supplied may be used for
Oil Equipment).
installation, if permitted by local codes and
4. Have"AuthorityHavingJurisdiction"istoinspect regulations. If the power cord supplied cannot be
all chimneys and installations for adequate venting used, the power supply wiring must be 90 degrees
and for compliance with standard and local codes centigradeinametalcableandshouldbecompleted
and regulations regarding installation of wood burn- byaqualifiedinstallercomplyingwithNFPAStandard
ing appliances.
No. 70 and local codes.
5. Installation for Supplemental Heat Application to
g) Optional Plenum Fan Control Switch (Part No.
Existing Central System. (See Fig. 2 for typical 11PCS) is available for installation on the plenum of
installation.)
central hot air heating furnace. The purpose of this
a) Place Wood or Coal Burning Furnace so that switch is to activate the circulating fan of the central
the chimney connector will be as short as practical hot air heating furnace when the temperature in the
and avoiding unnecessary sharp turns in the smoke plenum exceeds 120 degrees F., and shut off the
pipe connector and the installation of devices that fan when the temperature in the plenum is reduced
would create excessive resistance to the flow of flue to 100 degrees F. This avoids overheating the
gases.
b) Locate the Wood or Coal Burning Furnace as
plenum.
The electrical supply for operation of this fan
close as practical to the existing central hot air control switch is to be obtained from the same
heating system, maintaining clearances as stated electrical supply as the central hot air heating sys-
on the label on the fuel door.
tem. Follow the instructions of the wiring diagram
c) Clearance from combustible materials must (Fig. 12 or 13) Do not make connections across
comply with those stated on the label on the fire Limit Control in the furnace.
door:
Unit to combustible:
Front: 48"(900mm)
Make electrical wire connections in accordance
with NFPA Standard No. 70 and local codes in the
power supply junction box (See Fig. 15). The wiring
to complete the connections should be 18 AWG
minimum copper and 90 degrees centigrade in a
cable.
Back: 30"(760mm)
Sides: 12"(305mm)
Plenum to Ceiling: 6"(150m)
15
PLENUM
6" MIN.
TO
Figure 14
CEILING
2" MIN. AIR SPACE
REQUIRED BY CODE
CENTRAL
FURNACE
TO GAS/OIL/ELECTRIC
TRANSFORMER AND
COMBUSTION FAN OF
SOLID FUEL UNIT
Figure 15
COMBINATION CONTROL
LIMIT
H
POWER
SUPPLY
JUMPER IN
N
FAN
GAS/OIL/ELECTRIC
POWER SUPPLY
JUNCTION BOX
CAUTION!
DO NOT CONNECT
PLENUM FAN CONTROL
SWITCH ACROSS FURNACE
LIMIT CONTROL.
FURNACE
BLOWER
MOTOR
Power Failure Instructions:
Operation after loss of power--
1. Remove filter if provided
2. Do not expect to keep home at normal temperatures.
3. Do not load fuel above bottom of feed door.
16
CAUTION
Operating Instructions
GASES THAT ARE DRIVEN FROM FRESH
COAL MUST BE BURNED OR THEY WILL
ACCUMULATE AND EXPLODE. NEVER
SMOTHER A FIRE WHEN ADDING FRESH
COAL.
FUEL, Model 1300
Egg size (1-3/16" or larger) bituminous coal
for residential furnaces, or any of the specially
packed fireplace coals can be used. Coal with a
low ash content (2% to 6%) is recommended.
FUEL, Model 1400
Hardwood, 18" to 26" should be split and air dried
(seasoned) for 6 months.
LIGHTING
CAUTION
DO NOT OPERATE WITH THE FEED AND/OR
ASH DOOR OPEN. THIS FURNACE IS DE-
SIGNED FOR THERMOSTATIC OPERATION.
OPERATION WITH ANY OF THESE DOORS
OPEN WILL OVERHEAT AND DAMAGE THE
FURNACE.
1.
Set the thermostat on "HIGH" for maximum
draft.
2.
Open the feed door and place paper and
kindling on the grate for starting the fire.
Light the fire and close the feed door.
Add wood or about 15 lbs. of coal (depending
on which model) after fire is burning briskly.
Set thermostat for desired temperature.
"MEDIUM" setting is normally satisfactory.
Set higher or lower for your comfort.
3.
4.
CAUTION
NEVER USE GASOLINE, GASOLINE-TYPE
LANTERN FUEL, KEROSENE, CHARCOAL
LIGHTER FLUID, OR FLAMMABLE LIQUIDS
TO START OR "FRESHEN UP" A FIRE IN THE
FURNACE.
5.
ADDING FUEL
WARNING
When starting a fire, add small amounts of fuel
instead of adding large quantities of fuel. This will
give more complete combustion and less buildup
of tars or soot in the chimney.
NEVER STORE FLAMMABLE LIQUIDS, ES-
PECIALLY GASOLINE, IN THE VICINITY OF
THE FURNACE.
ADJUSTING BLOWER LIMIT CONTROL SET-
TINGS.
1. Set thermostat to HIGH before opening feed
door.
The temperature in the plenum of the warm air
furnace at which the blower turns on or turns off,
is controlled by the setting of the pointers in the
blower limit control. These pointers may be ad-
justed through their entire range of settings to
achieve the desired warm air output from furnace.
(See Fig. 16 below)
2. Wood fire - Model 1400.
Add wood to a convenient level.
3. Coal Fire - Model 1300.
a. Never smother the fire when adding coal (See
Caution). Gasaccumulationandamildsmoky
explosion will occur. Add fresh kindling if the
bed of coals has cooled.
b. Addupto20lbs.ofcoalperloading. Neveradd
coal above the bottom of feed door opening.
Stir the coal and watch the fire. Be sure the
c. new coal is burning briskly before you close
the doors and turn the thermostat down.
Shakegratesvigorously1/2"lefttorighttospill
d. ashes into the ash pan. Do this at least once
every 12 hours of operation. Empty ash pan
regularly. Do not allow ashes to buildup to
grate as grate will warp and burnout, and you
might spill the ashes when removing the pan.
Dispose of hot ashes properly (See note 12 on
page 4).
Move both pointers towards the right (counter
clockwise) - this increases the temperature
setting at which the blower will turn on and off.
Move both pointers towards the left (clock-
wise) - this decreases the temperature setting
at which the blower will turn on and off.
Move pointers away or apart from each other-
this increases the time that the blower will run
on each warm air cycle.
Fig. 16
BLOWER FAN
"OFF" POINTER
Rotation of the handle (5 o'clock to 7 o'clock)
e. position will agitate coals and spill ashes into
ash pan.
BLOWER FAN
"ON" POINTER
It is advisable for you to get familiar with the
shaker grate operation before firing.
f.
BLOWER LIMIT
POINTER & STOP
17
Service Hints
If the chimney is operating too cool, water
will condense in the chimney and run back
into the furnace. Creosote formation will be
rapid and may block the chimney. Operate
the furnace at a high enough fire to keep the
chimney warm, preventing this condensa-
tion.
Do not expect a furnace to draw. It is the
chimney that creates the draft. Smoke spillage
into the house or excessive buildup of water or
creosote in the chimney are warnings that the
chimneyisnotfunctioningproperly. Correctthe
problembeforeusingfurnace. Possiblecauses
are:
4.
5.
If the fire burns well, but sometimes smokes
or burns slowly, it may be caused by the
chimney top being lower than another part
of the house or a nearby tree. The wind
blowing over a house or a tree, falls on top
of the chimney like water over a dam, beat-
ingdownthesmoke. Thetopofthechimney
should be at least 3 feet above the roof and
be at least 2 feet higher than any point of the
roof within 10 feet (Fig. 5).
1. The connector pipe may be pushed into the
chimney too far, stopping the draft (Fig. 6)
2. Do not connect two furnaces or a stove and
furnace into the same chimney flue.
3. The chimney used for a furnace must not be
used to ventilate the cellar or basement. If
there is a cleanout opening at the base of
the chimney, it must be closed tightly.
6.
See page 29 for list of trouble shooting tips.
A draft reading of .05 to .06 w.c. is suggested for proper burning of this unit when using
wood or bituminous coal as fuel. When using anthracite coal, this draft reading is a
minimum reading.
Chimney Maintenance
Creosote and Soot - Formation and Need for Removal
When wood is burned slowly, it produces tar
and other organic vapors, which combine with
expelled moisture to form creosote. The creo-
sote vapors condense in the relatively cool
chimney flue of a slow-burning fire. As a result,
creosote residue accumulates on the flue lin-
ing. When ignited, this creosote makes an
extremely hot fire.
If creosote or soot has accumulated, it should
be removed to reduce the risk of a chimney fire.
Chimney fires burn very hot. If the chimney
catches fire, immediately call the fire depart-
ment, thenreducethefirebyclosingtheinletair
control. Pour a large quantity of coarse salt,
baking soda or cool ashes on top of the fire in
the firebox.
When coal is burned, the products of combus-
tion combine with moisture to form a soot resi-
duewhichaccumulatesonthefluelining. When
ignited, this soot makes an extremely hot fire.
CAUTION
A chimney fire may cause ignition of
wall studs or rafters which you thought
were a safe distance from the chimney.
If you have a chimney fire, have your
chimney inspected by a qualified per-
son before using again.
The chimney should be inspected at least twice
monthly during the heating season to deter-
mineifacreosoteorsootbuilduphasoccurred.
18
19
PARTS LIST
MODEL 1300
(SEE DIAGRAM, PAGE 19)
PART #
22684
22682
22762
88032
40246
22761
83227
83250
22683
22685
22662
23800
83337
83338
68218
68217
68733
68598
89175
86318
68721
89520
23425
83106S
89354
83045A
23445
83274
68238
22686
89308
83339
80230
83339
83340
89319
68231
68232
80154
80145
80231
80232
23397
40257
40256
40260
40264
68225
89066
68234
22140
22824
23787
83250
83445
KEY
1
2
3
4
5
6
N/S
N/S
7
8
9
10
N/S
N/S
11
12
13
DESCRIPTION
QTY.
1
1
1
1
1
1
6
6
1
1
1
1
2
2
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
2
1
5
5
1
1
1
1
1
1
1
1
1
1
1
1
1
10
1
1
1
2
2
2
CABINET LEFT SIDE
CABINET BACK PANEL
FORCED DRAFT RING
FLUE COLLAR GASKET
FLUE COLLAR
FLUE COLLAR RING
BOLT (1/4-20 X 1)
KEP NUT (1/4-20)
CABINET TOP PANEL
CABINET RIGHT SIDE
FEED DOOR HINGE BRACKET
SMOKE CURTAIN
BOLT (5/16-18 X 1)
LOCKNUT (5/16-18)
ASH DOOR ASSEMBLY
FEED DOOR ASSEMBLY
THERMOSTAT COVER ASSEMBLY
THERMOSTAT ASSEMBLY
THERMOSTAT CONTROL KNOB
THERMOSTAT DAMPER CHAIN
THERMOSTAT DAMPER FLAP ASSEMBLY
WOODEN HANDLE
14
14a
14b
14c
15
16
N/S
17
18
19
20
21
HANDLE BRACKET
SCREW (#10-24 X 1/2")
ASH DOOR HANDLE
WASHER (3/32 THK)
DOOR LATCH
NUT (3/8-16)
ASH PAN
CABINET BOTTOM
FEED DOOR LOCKING MECHANISM
BOLT (1/4-20 X 3/4")
BLOWER MOTOR
BOLT (1/4-20 X 3/4")
22
23
N/S
N/S
N/S
N/S
N/S
N/S
N/S
N/S
24
25
N/S
26
27
28
29
30
31
32
33
34
35
36
BLOWER CLIP NUT (1/4-20)
BLOWER GASKET
FAN CONTROL CORD ASSEMBLY
BLOWER CONDUIT ASSEMBLY
CORD STRAIN RELIEF
BLOWER LIMIT CONTROL
JUNCTION BOX
POWER SUPPLY CORD
FLUE BAFFLE
SHAKER GRATE
SHAKER FRAME
SHAKER HANDLE
FRONT AND REAR LINER
FIREBOX ASSEMBLY
FIREBRICK
BLOWER THERMOSTAT BRACKET
RELAY BOX SUPPORT BRACKET
DRAFT KNOB
SMOKE DOOR CLIP
KEP NUT (1/4-20)
BOLT (1/4-20 X 1-1/4")
37
38
20
21
PARTS LIST
MODEL 1400
(SEE DIAGRAM, PAGE 21)
PART #
23461
23459
22762
88032
40246
22761
83227
83250
23457
23461
22662
23800
68218
68217
68733
68598
89175
86318
68721
89520
23425
83106S
89354
83045A
23445
83274
68228
23458
89308
83339
80145
80231
80232
68231
23398
40263
40258
68215
23887
89066
68234
22140
22824
68229
83339
83340
89319
80154
23787
83445
83250
KEY
1
2
3
4
5
6
N/S
N/S
7
DESCRIPTION
CABINETLEFTSIDE
CABINET BACK PANEL
FORCEDDRAFTRING
FLUECOLLARGASKET
FLUE COLLAR
FLUE COLLAR RING
BOLT (1/4-20 X 1)
KEPNUT(1/4-20)
CABINETTOPPANEL
CABINETRIGHTSIDE
FEEDDOORHINGEBRACKET
SMOKECURTAIN
ASHDOORASSEMBLY
FEEDDOORASSEMBLY
THERMOSTATCOVER/PANELASSEMBLY
THERMOSTATASSEMBLY
THERMOSTATCONTROLKNOB
THERMOSTATDAMPERCHAIN
THERMOSTATDAMPERFLAPASSEMBLY
WOODENHANDLE
HANDLE BRACKET
SCREW(#10-24X1/2")]
ASHDOORHANDLE
DOORLATCHWASHER(3/32THK)
DOORLATCH
DOORLATCHNUT(3/8"-16)
ASHPAN
CABINET BOTTOM
FEEDDOORLOCKINGMECHANISM
BOLT (1/4-20 X 3/4")
BLOWER LIMIT CONTROL
JUNCTIONBOX
POWERSUPPLYCORD
FANCONTROLCORDASSEMBLY
FLUEBAFFLE
FURNACEGRATE
FRONTLINER
FIREBOXASSEMBLY
HALF FIREBRICK
FIREBRICK
BLOWERTHERMOSTATBRACKET
RELAYBOXSUPPORTBRACKET
DRAFTCONTROLKNOB
BLOWERMOTORASSEMBLY
MOUNTING BOLT (1/4-20 X 3/4")
CLIPNUT(1/4-20)
QTY.
1
1
1
1
1
1
6
6
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
2
1
1
1
3
2
3
1
1
2
12
1
1
1
2
10
10
2
1
2
8
9
10
11
12
13
14
14a
14b
14c
15
16
N/S
17
18
19
20
21
22
23
N/S
24
25
N/S
N/S
26
27
28
29
30
31
32
33
34
N/S
N/S
N/S
N/S
N/S
35
36
37
BLOWERGASKET
CORDSTRAINRELIEF
SMOKECURTAINCLIP
BOLT(1/4-20X1-1/4")
KEPNUT(1/4-20)
2
2
22
Central Installation
(U.S. ONLY)
COLD AIR DUCT
6" PIPE
90 ELBOW
DAMPER
OPTIONAL
11 RPT
PIPE
CONNECTOR
FURNACE
Fig. 17-1
Add-On Installation
(U.S. ONLY)
COLD AIR DUCT
8" PIPE
6" PIPE
90 ELBOW
DAMPER
PIPE
CONNECTOR
FURNACE
EXISTING GAS/OIL/ELECTRIC FURNACE
Fig. 17
23
APPENDIX
INSTALLATION A
(U.S. ONLY)
TO EXISTING
DUCT WORK
COLD AIR
RETURN
WARM AIR
EXISTING
FURNACE
FILTER BOX
SOLID FUEL
FURNACE
24
INSTALLATION B
(U.S. ONLY)
PLENUM
COLLECTOR BOX
TO EXISTING
DUCT WORK
COLD AIR
RETURN
WARM AIR
EXISTING
FURNACE
FILTER BOX
SOLID FUEL
FURNACE
INSTALLATION C
(U.S. ONLY)
PLENUM ELBOW
TO EXISTING
DUCT WORK
COLD AIR
RETURN
WARM AIR
PLENUM TOP
(OPTIONAL)
EXISTING
FURNACE
FILTER BOX
SOLID FUEL
FURNACE
25
INSTALLATION D
(U.S. ONLY)
DUCT
WORK
2" MINIMUM
CLEARANCE
11 PCS
(OPTIONAL PLENUM
FAN CONTROL LOCATION)
COLD AIR
RETURN
FURNACE PLENUM
EXISTING FURNACE
ANTI-BACKDRAFT
FLAPPER
SOLID FUEL
FURNACE
INSTALLATION E
(U.S. ONLY)
DUCT
WORK
2" MINIMUM
CLEARANCE
BAFFLE
COLD AIR
RETURN
FURNACE PLENUM
EXISTING FURNACE
SOLID FUEL
FURNACE
26
INSTALLATION F
DUCT
WORK
2" MINIMUM
CLEARANCE
COLD AIR
RETURN
FURNACE PLENUM
EXISTING FURNACE
SOLID FUEL
FURNACE
INSTALLATION G
DUCT
WORK
2" MINIMUM
CLEARANCE
CENTRAL
FURNACE
INSTALLATION
COLD AIR
RETURN TO
FILTER BOX
SOLID FUEL
FURNACE
27
INSTALLATION H
EXISTING OIL,
ELECTRIC OR
GAS FURNACE
SOLID FUEL
FURNACE
(TOP VIEW)
2" MINIMUM
CLEARANCE
EXISTING OIL,
ELECTRIC OR
GAS FURNACE
SOLID FUEL
FURNACE
(FRONT VIEW)
26
Trouble Shooting Tips for Warm Air Furnace
LIST OF PROBLEMS
POSSIBLE CAUSE
SOLUTIONS
1. Smoking when feed door
is open.
a) Insufficient Draft.
b) Clogged chimney or chimney
connector.
a) Set Thermostat higher.
b) CleanChimney.
c) Add raincap to chimney.
c) Down draft in chimney.
2. Furnace does not heat.
3. Blower Does not run.
a) Wood not seasoned and dry.
b) Blower control set too low.
c) Insufficient flue draft.
a) Allow wood to season in a
dry area for six months.
b) Set blower control to higher
temperatures. (See P. 17)
c) Set flue draft. (See P. 9)
a) Improperlywired.
b) Badblowercontrol.
c) Bad relay.
a) Wireunitproperly.
b) Replaceblowercontrol.
c) Replacerelay.
d) Badblowermotor
d) Replaceblower.
4. No air from registers-
fanrunning.
a) Registers are closed.
a) Openregisters.
b) Correct duct work install.
c) Wireunitproperly.
b) Duct work improperly installed.
c) Improperwiringbetweencentral
furnace and this unit.
5. Air from Registers is not hot
6. Blower runs too long.
a) Blower control is set too low.
b) Badblowercontrol.
a) Adjust blower control to
higher setting. (See P. 17)
b) Replaceblowercontrol.
Blower control cut off set
too low.
Set blower control cut off to
higher setting. (See P. 17)
7. Blower does not run long
enough.
a) Blower control cut off set
too high.
b) Badblowermotor.
a) Set blower control cut off to
lower setting. (See P. 17)
b) ReplaceBlower.
8. Smoke and/or odor from
registerswhenfurnace
is used for first time.
Oil from furnace and duct
work.
The metal used in constuc-
tion of the furnace and duct
work has a light coating of
oil. This should disappear
after a short period of time.
Once this burnoff has occur-
red, is should not reoccur.
9. Creosotebuild-up.
a) Burninggreenwood(not
seasoned or dry).
a) Burn only seasoned wood.
b) Thermostat setting too low
for type fuel.
b) Set thermostat higher to
attainhigherfluetempera-
tures. This will aid in pre-
venting buildup of creosote.
10. Flame spillage when feed
door is open.
a) Insufficient draft.
b) Smotheringfirewhenadding
fresh fuel.
a) Set thermostat higher.
b) Add fuel so as not to
smother fire.
29
NOTES
30
NOTES
31
HOW TO ORDER REPAIR PARTS
THIS MANUAL WILL HELP YOU OBTAIN EFFICIENT, DEPENDABLE SERVICE FROM
THE HEATER, AND ENABLE YOU TO ORDER REPAIR PARTS CORRECTLY.
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
WHEN WRITING, ALWAYS GIVE THE FULL MODEL NUMBER WHICH IS ON THE
NAMEPLATE ATTACHED TO THE BACK OF THE HEATER.
WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THE
FOLLOWING INFORMATION AS SHOWN IN THIS LIST:
1. The PART NUMBER
2. The PART DESCRIPTION
3. The MODEL NUMBER: 1300 1400
4. The SERIAL NUMBER:
UNITED STATES STOVE COMPANY
227 Industrial Park Road
P.O. Box 151
South Pittsburg, TN 37380
(423) 837-2100
|