A Sierra Monitor Company
Driver Manual
(Supplement to the FieldServer Instruction Manual)
FS-8700-84 Lutron eLumen
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after May 1, 2001
FS-8700-84_Lutron_eLumen Manual
Table of Contents
4.1.26. System Control Commands containing no Parameters: Toggle system
variable value....................................................................................................................... 20
4.1.27. System Control Commands containing no Parameters: Output temp scene
21
4.1.28. System Control Commands containing no Parameters: Select scene in
area
22
4.1.29. System Control Commands containing no Parameters: Timeclock new
schedule 23
4.1.30. System Control Commands containing no Parameters: Set timeclock...... 23
4.1.31. System Control Commands containing no Parameters: Enable
wallstation(s)......................................................................................................................... 24
4.1.32. System Control Commands containing no Parameters: Disable
wallstation(s)......................................................................................................................... 24
4.1.33. System Control Commands containing no Parameters: Simulate
wallstation(s) switch press ................................................................................................. 25
4.1.34. System Control Commands containing no Parameters: Simulate
wallstation(s) switch release.............................................................................................. 26
4.1.35. System Control Commands containing no Parameters: Stop scene ramp
down
26
4.1.36. System Control Commands Containing Parameters: Toggle zone............ 27
4.1.37. System Control Commands Containing Parameters: Fade zone(s) to level
27
4.1.38. System Control Commands Containing Parameters: Ramp zone(s) up ... 28
4.1.39. System Control Commands Containing Parameters: Ramp zone(s) down
28
4.1.40. System Control Commands Containing Parameters: Pommel or pulse
zone(s Toggle zone) ........................................................................................................... 29
4.1.41. System Control Commands Containing Parameters: Flash zones aka
“Multi level ( Flash or Warn or Chase )“........................................................................... 30
4.1.42. System Control Commands Containing Parameters: Ramp scene zones
up
4.1.43. System Control Commands Containing Parameters: Ramp scene zones
down 31
30
4.1.44. System Control Commands Containing Parameters: Select system
scene(s) using override times............................................................................................ 31
4.1.45. System Control Commands Containing Parameters: Set system variable
value
32
4.1.46. Listening to switch presses and releases: Enabling switch presses and
releases reporting................................................................................................................ 32
4.1.47. Listening to switch presses and releases: Disabling switch presses and
releases reporting................................................................................................................ 32
4.1.48. Listening to switch presses and releases: Listening to switch presses and
releases 33
4.1.49. Active read on startup: Retrieving names....................................................... 34
Appendix A. Data Tables..................................................................................................... 35
Appendix B. Revision History............................................................................................ 36
FS-8700-84_Lutron_eLumen Driver Manual
Page 1 of 36
1.
Lutron eLumen Description
The Serial Lutron eLumen driver allows the FieldServer to transfer data to and from
devices over RS-232 or RS-485 using eLumen protocol. The FieldServer can only be
used operationally as a Lutron Client driver. Any existing Lutron Server drivers are for
FieldServer testing purposes only and cannot be used to emulate a Lutron eLumen
system.
The driver supports the following 3 panels: GRAFIK5000, GRAFIK6000 and
GRAFIK7000. The hardware for all 3 panels is identical. The only differences are limits
in the database. GRAFIK5000 has only 1 CSD link and can have a max of 128 zones.
GRAFIK6000 has 3 CSD links with 512 zones. GRAFIK7000 has 6 links with 512
zones and can communicate with other processors.
The FieldServer eLumen driver implements the following functionality:
Status monitoring of eLumen system data and parameters.
System Control of eLumen.
Status monitoring is achieved by sending status requests to the eLumen system.
Retrieved status data are collected and stored in FieldServer Data Arrays that allow
access by other protocols.
System Control Commands can be configured in the FieldServer to address any groups
of Areas, Zones or Scenes. A mechanism is provided by which the parameters are set
before the command is triggered using the upstream protocol.
Commands are provided to read the names of Areas, Zones and Scenes from the
eLumen to facilitate access by SCADA systems.
FS-8700-84_Lutron_eLumen Driver Manual
Page 2 of 36
2.
Driver Scope of Supply
1.01
Supplied by FieldServer Technologies for this driver
FieldServer Technologies
PART #
Description
FS-8915-10
FS-8917-02
FS-8700-84
UTP cable (7 foot) for RS-232 use
RJ45 to DB9F connector adapter
Driver Manual.
1.02
Provided by the Supplier of 3rd Party Equipment
2.1.1.
Required 3rd Party Hardware
Part #
Description
Lutron Panel
FS-8700-84_Lutron_eLumen Driver Manual
Page 3 of 36
3.
Hardware Connections
The FieldServer is connected to the Lutron eLumen as shown in connection drawing.
Configure the eLumen according to manufacturer’s instructions
FS-8917-02
LUTRON SERIAL
RS-232 INTERFACE
PART # 470-784
8917-02 WIRE LIST
CAT 5 CABLE
FS-8915-10
FUNCTION
RX
FROM
TO
COLOUR
WHITE
BROWN
YELLOW
GREEN
RED
BLACK
ORANGE
BLUE
RJ45-01
RJ45-02
RJ45-03
RJ45-04
RJ45-05
RJ45-06
RJ45-07
RJ45-08
DB9M-02
DB9M-08
DB9M-06
DB9M-05
CTS
DSR
GND
GND
DTR
RTS
TX
DB9M-04
DB9M-07
DB9M-03
Serial
Power OK
(408)-262-2299
Tx
EIA232
Rx Tx
Rx
-
+
Ethernet
USB
EIA485
LUTRON ELUMEN RS-232
CONNECTION DIAGRAM
FS-B2010
BASE NAME:
FILE NAME: FS-T28700-84 .VSD
DATE: 11/12/04
BY: MC
FS-8700-84_Lutron_eLumen Driver Manual
Page 4 of 36
120V 15A
Dedicated Control
Feed
Wallstation link
To control stations
To dimmer panels
eLumen
Processor
Aux Link (RS-485)
User Interface link
Dimmer panel link
Inter-processor link
Serial
Power OK
Tx
EIA232
Rx Tx
Rx
-
+
Ethernet
USB
EIA485
FS-B2010
(408)-262-2299
LUTRON ELUMEN RS-485
CONNECTION DIAGRAM
BASE NAME:
FILE NAME: FS-T28700-84 .VSD
DATE: 11/12/04
BY: MC
FS-8700-84_Lutron_eLumen Driver Manual
Page 5 of 36
4.
Configuring the FieldServer as a Lutron eLumen Client
For a detailed discussion on FieldServer configuration, please refer to the FieldServer
Configuration Manual. The information that follows describes how to expand upon the
factory defaults provided in the configuration files included with the FieldServer (See
“.csv” sample files provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the
FieldServer to communicate with a Lutron eLumen Server
1.03
Data Arrays/Descriptors
The configuration file tells the FieldServer about its interfaces, and the routing of
data required. In order to enable the FieldServer for Lutron eLumen
communications, the driver independent FieldServer buffers need to be declared in
the “Data Arrays” section, the destination device addresses need to be declared in
the “Client Side Nodes” section, and the data required from the Servers needs to be
mapped in the “Client Side Map Descriptors” section. Details on how to do this can
be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value
being the default.
Section Title
Data_Arrays
Column Title
Function
Legal Values
Up to 15 alphanumeric
characters
Data_Array_Name
Provide name for Data Array
Float, Bit, UInt16,
SInt16, Packed_Bit,
Byte, Packed_Byte,
Swapped_Byte
Provide data format. Each Data
Array can only take on one
format.
Data_Array_Format
Data_Array_Length
Number of Data Objects. Must
be larger than the data storage
area required by the Map
Descriptors for the data being
placed in this array.
1-10,000
Example
// Data Arrays
Data_Arrays
Data_Array_Name,
Area_status,
Zone_list,
Data_Format,
UInt16,
UInt16,
Data_Array_Length
64
64
10
Zone_pars,
UInt16,
FS-8700-84_Lutron_eLumen Driver Manual
Page 6 of 36
1.04
Client Side Connection Descriptions
Section Title
Connections
Column Title
Function
Specify which port the
device is connected to the
FieldServer
Legal Values
P1-P8, R1-R21
Port
Protocol
Baud*
Parity*
Specify protocol used
Specify baud rate
Specify parity
eLumen
9600 – Vendor limitation
None
Data_Bits*
Stop_Bits*
Specify data bits
Specify stop bits
Specify hardware
handshaking
8
1
Handshaking*
Poll _Delay*
None
Time between internal polls 0-32000 seconds, 1 second
Example
// Client Side Connections
Connections
Port, Protocol,
Baud, Parity, Data Bits, Stop Bits, Poll_Delay
9600, None, None, 1, 0.100s
P1,
eLumen,
1.05
Client Side Node Descriptors
Section Title
Nodes
Column Title
Function
Legal Values
Up to 32 alphanumeric
characters
Node_Name
Node_ID
Provide name for node
The eLumen processor
address - only decimal values
allowed e.g. 11 hex has to be
entered as 17.
0-255
Protocol
Port
Specify protocol used
eLumen
P1-P8, R1-R21
Specify which port the device is
connected to the FieldServer
Specifies the eLumen
Node_type
Hex, decimal
command and data format
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for
details of the ports available on specific hardware.
FS-8700-84_Lutron_eLumen Driver Manual
Page 7 of 36
Example
// Client Side Nodes
Nodes
Node_Name,
LUT_GRF6_0,
Node_ID, Protocol,
17, eLumen,
Connection, Node_type
P1,
hex
1.06
Client Side Map Descriptors
The driver uses Map Descriptors with Lutron commands to build poll messages that
will be sent to the eLumen system. Example Map Descriptors are shown in the next
section. Note the following in the use of Map Descriptors for the Lutron driver:
Lutron command
Every Map Descriptor must have a Lutron command specified so the driver will know
which command to send to the eLumen.
Function
Map Descriptor functions must be correctly specified to implement the functionality
embodied by the specific Lutron command, e.g. a command to retrieve area status
requires a read Map Descriptor whereas a command to toggle zones requires a
write Map Descriptor.
DA_Area_Names, DA_Scene_Names, DA_Zone_Names, xxx_Offset
These are user Map Descriptor fields needed to retrieve area, scene and zone
names from the eLumen. Please refer to the Map Descriptor examples.
Link, Area, Link_station, Switch, Zone, Sys_var, Panel
These are user Map Descriptor fields that must be used as needed with a specific
Lutron command. Please refer to the Map Descriptor examples.
DA_Lut_List, DA_Lut_List_Offset
Lutron commands that allow multiple areas, zones, etc to be specified in one
command e.g. Toggle zones use the areas or zones in the Data Array specified by
DA_Lut_List at an offset specified by DA_Lut_List_Offset to build the poll message.
The list must be filled in before the command is triggered by writing into the Data
Array specified by Data_Array_Name.
DA_Lut_Parms, DA_Lut_Parms_Offset
Lutron commands that use parameters such as delay and fade cycles use the
parameters at the offset as specified by these Map Descriptor fields. Parameters
must be filled in together with the list data if applicable before triggering the
command by writing into the Data Array specified by Data_Array_Name. Please
refer to the Map Descriptor examples.
FS-8700-84_Lutron_eLumen Driver Manual
Page 8 of 36
4.1.1.
FieldServer Related Map Descriptor Parameters
Column Title
Function
Name of this Map
Descriptor
Name of Data Array
where data is to be
stored in the
Legal Values
Up to 32 alphanumeric
characters
Map_Descriptor_Name
Data_Array_Name
One of the Data Array
names from “Data Array”
section above
FieldServer
0 to maximum specified in
“Data Array” section
above
ARS, RDBC, WRBC,
WRBX, AWT
Starting location in
Data Array
Data_Array_Location
Function
Function of Client
Map Descriptor
4.1.2.
Driver Related Map Descriptor Parameters
Column Title
Function
Legal Values
One of the node names
specified in “Client Node
Descriptor” above
Name of Node to fetch
data from
Node_Name
Specifies the command
to be sent to the
eLumen.
A list of commands is
provided in Appendix A.
GRAFIK_command
0–11 for
GRAFIK_command:
ena_wallstation,
dis_wallstation,
sim_ws_sw_press,
sim_ws_sw_rls,
Link
Wallstation link number
0-31 for
GRAFIK_command:
wallstation_status,
switch_status,
GRAFIK system area
number
Wallstation on link’s
number
Wallstation switch
number
GRAFIK system zone
number
Area
0–511
0–31
Link_station
Switch
Zone
0–31
0–511
GRAFIK system variable
number
GRAFIK panel number
Sys_var
Panel
0–65535
0–511
FS-8700-84_Lutron_eLumen Driver Manual
Page 9 of 36
Column Title
Function
Legal Values
Any Data Array name. If
not listed under Data
Arrays the driver will
auto-create the Data
Array.
Name of Data Array that
contains a list of zones
or areas, etc, needed to
build the poll message.
DA_Lut_List
The offset into the
DA_Lut_List Data Array
where the driver will
retrieve the list data
when building the poll
message.
0 to the maximum offset
into the DA_Lut_List
Data Array.
DA_Lut_List_Offset
DA_Lut_Parms
Any Data Array name. If
not listed under Data
Arrays the driver will
auto-create the Data
Array.
Name of Data Array
containing parameters
needed to build the poll
message.
The offset into the
DA_Lut_Parms Data
Array where the driver
will retrieve the
parameters when
building the poll
message.
0 to the maximum offset
into the DA_Lut_Parms
Data Array.
DA_Lut_Parms_Offset
DA_Area_Names
Any Data Array name. If
not listed under Data
Arrays the driver will
auto-create the Data
Array.
Name of Data Array
where retrieved area
names will be stored.
The offset into the
DA_Area_Names Data
DA_Area_Names_Offset Array where retrieved
0 to the maximum offset
into the
DA_Area_Names Data
Array.
area names will be
stored.
Any Data Array name. If
not listed under Data
Arrays the driver will
auto-create the Data
Array.
Name of Data Array
where retrieved scene
names will be stored.
DA_Scene_Names
The offset into the
DA_Scene_Names Data
Array where retrieved
scene names will be
stored.
0 to the maximum offset
into the
DA_Scene_Names Data
Array.
DA_Scene_Names_Offs
et
FS-8700-84_Lutron_eLumen Driver Manual
Page 10 of 36
Column Title
Function
Legal Values
Any Data Array name. If
not listed under Data
Arrays the driver will
auto-create the Data
Array.
Name of Data Array
where retrieved zone
names will be stored.
DA_Zone_Names
The offset into the
DA_Zone_Names Data
Array where retrieved
zone names will be
stored.
0 to the maximum offset
into the
DA_Zone_Names Data
Array.
DA_Zone_Names_Offse
t
Start and end numbers
of area name to be
retrieved with
Area_Names_Start
Area_Names_End
0–511
get_names cmd
Start and end numbers
of scene name to be
retrieved with
Scene_Names_Start
0–32,768
0–511
Scene_Names_End
Zone_Names_Start
get_names cmd
Start and end numbers
of zone name to be
retrieved with
Zone_Names_End
get_names cmd
Length of Map
Descriptor. The length is
an indication of the
number of data elements
this Map Descriptor is
responsible for updating.
It is used in the overall
points calculation of the
FieldServer.
See example Map
Descriptors for individual
lengths per Map
Descriptor.
Length
4.1.3.
Column Title
Scan_Interval
Timing Parameters
Function
Legal Values
0s to 32000s
Rate at which data is polled
FS-8700-84_Lutron_eLumen Driver Manual
Page 11 of 36
4.1.4.
System Monitor Command – Time Now
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,
GRAFIK_command, Length
Time_now, 5s, Time_now, 0, rdbc, LUT_GRF6_0, time_now,
1
Data storage in Data Array
Position from offset Description:
0
Minutes from midnight
4.1.5.
System Monitor Command – Astro Times
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,
Astro_times, 5s, Astro_times, 0, rdbc,
GRAFIK_command, Length
LUT_GRF6_0, astro_times,
2
Data storage in Data Array
Position from offset
Description:
0
1
Sunrise minutes from midnight
Sunset minutes from midnight
FS-8700-84_Lutron_eLumen Driver Manual
Page 12 of 36
4.1.6.
System Monitor Command – Date
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,
GRAFIK_command, Length
Date, 5s, Date, 0, rdbc, LUT_GRF6_0, date,
4
Data storage in Data Array
Position from offset
Description:
0
1
2
3
Month ( 1-12 )
Day of month ( 1-31 )
Year ( 0-99 )
Day of week ( 1-7, 1=Sunday )
4.1.7.
System Monitor Command – Code Revision Level
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,
GRAFIK_command, Length
Code_rev,
5s,
Code_rev,
0,
rdbc,
LUT_GRF6_0, code_rev_level,
1
Data storage in Data Array
Position from offset
0
Description
Code revision level
4.1.8.
System Monitor Command – Bootcode Revision Level
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,
GRAFIK_command, Length
Bootcode_rev,
5s,
Bootcode_rev,
0,
rdbc,
LUT_GRF6_0, bootcode_rev_level,
1
Data storage in Data Array
Position from offset
0
Description
Bootcode revision level
FS-8700-84_Lutron_eLumen Driver Manual
Page 13 of 36
4.1.9.
System Monitor Command – Serial Number
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,
GRAFIK_command, Length
Serial_num, 5s, Serial_num, 0, rdbc, LUT_GRF6_0, serial_no,
1
Data storage in Data Array
Position from offset
0
Description
Serial number
4.1.10.
System Monitor Command – Area Status
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,
GRAFIK_command, Area, Length
Area_sts_00,
Area_sts_01,
1s,
1s,
Area_status,
Area_status,
0,
2,
rdbc,
rdbc,
LUT_GRF6_0, Area_status,
LUT_GRF6_0, Area_status,
0,
1,
2
2
Data storage in Data Array
Position from offset
Description
0
1
System scene on status
Sequence running status
Note: This command stores 2 data values. To prevent overlaps, remember to increment Data_Array_Offset by 2 when referencing the same Data
Array with other Map Descriptors.
FS-8700-84_Lutron_eLumen Driver Manual
Page 14 of 36
4.1.11.
System Monitor Command – Timeclock Status
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Tclk_sts_00,
Tclk_sts_01,
Scan_Interval, Data_Array_Name,
Data_Array_Offset, Function, Node_Name,
GRAFIK_command,
Area, Length
1s,
1s,
Tclk_status,
Tclk_status,
0,
4,
rdbc,
rdbc,
LUT_GRF6_0, timeclock_status,
LUT_GRF6_0, timeclock_status,
0,
1,
4
4
Data storage in Data Array
Position from offset
Description
Schedule number
0
1
2
3
Next event type (1 = no more events, 2 = timeclock disabled, 3 = astronomic event, 4 = realtime event )
Next event time ( minutes past midnight )
Next script
Note: This command stores 4 data values. To prevent overlaps, remember to increment Data_Array_Offset by 4 when referencing the same Data
Array with other Map Descriptors.
4.1.12.
System Monitor Command – Zone Intensity
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Zn_int_00,
Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,
GRAFIK_command, Zone, Length
1s,
1s,
Zone_int,
Zone_int,
0,
1,
rdbc,
rdbc,
LUT_GRF6_0, zone_intensity,
LUT_GRF6_0, zone_intensity,
0,
1,
1
1
Zn_int_01,
Data storage in Data Array
Position from offset
0
Description
Zone intensity ( 0-127 )
Note: This command stores 1 data value. To prevent overlaps, remember to increment Data_Array_Offset by 1 when referencing the same Data
Array with other Map Descriptors.
FS-8700-84_Lutron_eLumen Driver Manual
Page 15 of 36
4.1.13.
System Monitor Command – Request Panel Emergency Status
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,
GRAFIK_command, Panel, Length
Pnl_emerg_sts_00,
Pnl_emerg_sts_511,
1s,
1s,
Pnl_emerg_sts,
Pnl_emerg_sts,
0,
511,
rdbc,
rdbc,
LUT_GRF6_0, pnl_emerg_status,
LUT_GRF6_0, pnl_emerg_status,
0,
511,
1
1
Data storage in Data Array
Position from offset
Description
0
Panel emergency status
0 = normal; 1 = override
Note: This command stores 1 data value. To prevent overlaps, remember to increment Data_Array_Offset by 1 when referencing the same Data
Array with other Map Descriptors.
4.1.14.
System Monitor Command – System Variable Value
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,
GRAFIK_command, Sys_var, Length
Sys_var_00,
Sys_var_01,
1s,
1s,
Sys_vars,
Sys_vars,
0,
1,
rdbc,
rdbc,
LUT_GRF6_0, sys_var_val,
LUT_GRF6_0, sys_var_val,
0,
1,
1
1
Data storage in Data Array
Position from offset
0
Description
System variable value
Note: This command stores 1 data value. To prevent overlaps, remember to increment Data_Array_Offset by 1 when referencing the same Data
Array with other Map Descriptors.
FS-8700-84_Lutron_eLumen Driver Manual
Page 16 of 36
4.1.15.
System Monitor Command – Wallstation Status
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Wall_st_sts_0000,
Wall_st_sts_0001,
Scan_Interval,
1s,
1s,
Data_Array_Name,
Wall_st_sts_00,
Wall_st_sts_00,
Data_Array_Offset,
0,
32,
Function,
rdbc,
rdbc,
Node_Name,
LUT_GRF6_0,
LUT_GRF6_0,
GRAFIK_command,
wallstation_status,
wallstation_status,
link,
0,
0,
link_station,
0,
1,
Length
32
32
Data storage in Data Array
Position from offset
0-31
Description
All switches on station and their priority.
Note: This command stores 32 data values. To prevent overlaps, remember to increment Data_Array_Offset by 32 when referencing the same
Data Array with other Map Descriptors.
Implementation note: The wallstation status command retrieves the status of all 32 switches defined on a wallstation. If you only want to retrieve
the status of a few individual switches, rather only use the switch status Map Descriptor as described below.
4.1.16.
System Monitor Command – Switch Status
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Sw_sts_000,
Sw_sts_001,
Scan_Interval,
1s,
1s,
Data_Array_Name,
Sw_sts_00,
Sw_sts_00,
Data_Array_Offset,
0,
1,
Function,
rdbc,
rdbc,
Node_Name,
LUT_GRF6_0,
LUT_GRF6_0,
GRAFIK_command,
switch_status,
switch_status,
link,
0,
0,
link_station,
0,
0,
switch,
0,
1,
Length
1
1
Data storage in Data Array
Position from offset
Description
0
Switch status and priority
Note: This command stores 1 data value. To prevent overlaps, remember to increment Data_Array_Offset by 1 when referencing the same Data
Array with other Map Descriptors.
Implementation note: The switch status command only retrieves the status of one switch on a wallstation. To retrieve other switch statuses, use
additional switch status Map Descriptors or else use the wallstation status Map Descriptor to retrieve the status of all 32 switches. When using
both wallstation status and switch status Map Descriptors in the same configuration, it is not permissible to have the target Data Arrays overlap.
FS-8700-84_Lutron_eLumen Driver Manual
Page 17 of 36
4.1.17.
System Control Commands containing no Parameters: – Halt Zone
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Zone_halt,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
0,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
halt_zone,
DA_Lut_List,
Zone_list,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
0-63
Description
Zone(s) to halt
Note: After setting up the zone numbers to halt in the DA_Lut_List Data Array, trigger this command by writing the number of zones to halt into the
Data Array specified by Data_Array_Name at an offset specified by Data_Array_Offset.
4.1.18.
System Control Commands containing no Parameters: – Stop Scene Ramp Up
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Stop_scn_rmp_up,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
1,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
stop_scene_ramp_up,
DA_Lut_List,
Area_list,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
0-31
Description
Area(s) with scenes to stop ramp up
Note: After setting up the area numbers to stop scene ramps in the DA_Lut_List Data Array, trigger this command by writing the number of areas
into the Data Array specified by Data_Array_Name at an offset specified by Data_Array_Offset.
FS-8700-84_Lutron_eLumen Driver Manual
Page 18 of 36
4.1.19.
System Control Commands containing no Parameters: – Select System Scene(s)
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Sel_scene,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
2,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
sel_scene,
DA_Lut_List,
Scene_list,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
0-63
Description
System scenes to select
4.1.20.
System Control Commands containing no Parameters: – Disable Timeclock until Enabled
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Dis_tck_u_e,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
3,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
dis_tclk_u_e,
DA_Lut_List,
Area_list,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
0-31
Description
Area timeclocks to disable
4.1.21.
System Control Commands containing no Parameters: – Disable timeclock until end of day or
enable issued
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Dis_tck_u_eodoe,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
4,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
dis_tclk_u_eodoe,
DA_Lut_List,
Area_list,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
0-31
Description
Area timeclocks to disable
FS-8700-84_Lutron_eLumen Driver Manual
Page 19 of 36
4.1.22.
catchup
System Control Commands containing no Parameters: – Re-enable timeclock with complete
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,
GRAFIK_command, DA_Lut_List,
Area_list,
DA_Lut_List_Offset, Length
0,
Rnbl_tck_cup,
Lut_triggers,
5,
awt,
LUT_GRF6_0, rnbl_tclk_catchup,
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
0-31
Description
Area timeclocks to re-enable
4.1.23.
event
System Control Commands containing no Parameters: – Re-enable timeclock and do previous
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Rnbl_tck_doprev,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
6,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
rnbl_tclk_do_prev_evt,
DA_Lut_List,
Area_list,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
0-31
Description
Area timeclocks to re-enable
4.1.24.
System Control Commands containing no Parameters: Standard re-enable timeclock
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Std_tck_rnbl,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
7,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
std_tclk_rnbl,
DA_Lut_List,
Area_list,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
0-31
Description
Area timeclocks to re-enable
FS-8700-84_Lutron_eLumen Driver Manual
Page 20 of 36
4.1.25.
System Control Commands containing no Parameters: Run script(s)
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Run_script,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
8,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
run_script,
DA_Lut_List,
Script_list,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
0-63
Description
Numbers of scripts to run
4.1.26.
System Control Commands containing no Parameters: Toggle system variable value
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Toggle_sys_var,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
9,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
toggle_sys_var_val,
DA_Lut_List,
Var_list,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
0-31
Description
Numbers of system variables to toggle
FS-8700-84_Lutron_eLumen Driver Manual
Page 21 of 36
4.1.27.
System Control Commands containing no Parameters: Output temp scene
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name,
Data_Array_Offset,
10,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
output_temp_scene,
DA_Lut_List,
Op_Tmp_Scene,
DA_Lut_List_Offset,
0,
Length
1
Output_tmp_scn,
Lut_triggers,
DA_Lut_List data setup
Position from DA_Lut_List_Offset
Description
0
Zone 0
1
2
Intensity 0
Fade 0
3
Delay 0
4
5
6
Zone number 1
Intensity 1
Fade 1
7
Delay 1
..
..
60
61
62
63
Zone 15
Intensity 15
Fade 15
Delay 15
Note: 1 to 16 temp scenes may be selected by this command. To trigger this command, write the number of temp scenes to output into the Data
Array specified by Data_Array_Name at Data_Array_Offset.
FS-8700-84_Lutron_eLumen Driver Manual
Page 22 of 36
4.1.28.
System Control Commands containing no Parameters: Select scene in area
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Sel_scn_in_area,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
11,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
sel_scene_in_area,
DA_Lut_List,
Sel_Scn_Area,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
Description
0
1
2
3
Area 0
Scene 0
Area 1
Scene 1
..
..
30
31
Area 15
Scene 15
Note: 1 to 16 area scenes may be selected by this command. To trigger this command, write the number of area scene pairs into the Data Array
specified by Data_Array_Name at Data_Array_Offset.
FS-8700-84_Lutron_eLumen Driver Manual
Page 23 of 36
4.1.29.
System Control Commands containing no Parameters: Timeclock new schedule
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Tck_new_sched,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
12,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
tclk_new_schedule,
DA_Lut_List,
Clk_sched,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
0
1
2
3
..
Description
Area tclk 0
Schedule 0
Area tclk 1
Schedule 1
..
60
61
62
63
Area tclk 30
Schedule 30
Area tclk 31
Schedule 31
Note: 1 to 32 new schedules may be started by this command. To trigger this command, write the number of area timeclocks into the Data Array
specified by Data_Array_Name at Data_Array_Offset.
4.1.30.
System Control Commands containing no Parameters: Set timeclock
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Set_tck,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
13,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
set_tclk,
DA_Lut_List,
Set_tclk,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
Description
0
1
2
3
4
5
Hour ( 0-23 )
Minutes ( 0-59 )
Month ( 1-12 )
Day of month ( 1-31 )
Year ( 0 – 99 )
Day of week ( 1-7, 1=Sunday )
FS-8700-84_Lutron_eLumen Driver Manual
Page 24 of 36
4.1.31.
System Control Commands containing no Parameters: Enable wallstation(s)
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Enable_ws,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
14,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
ena_wallstation,
DA_Lut_List,
Ctrl_ws_list,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
Description
0
1
..
Link number ( 0-11 ) of Station ID 0
Station on link ( 0-31 ) of Station ID 0
..
62
63
Link number ( 0-11 ) of Station ID 31
Station on link ( 0-31 ) of Station ID 31
Note: 1 to 32 station ids may be used to enable wallstations. To trigger the command, write the number of station IDs into the Data Array specified
by Data_Array_Name at Data_Array_Offset
4.1.32.
System Control Commands containing no Parameters: Disable wallstation(s)
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Disable_ws,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
15,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
dis_wallstation,
DA_Lut_List,
Ctrl_ws_list,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
Description
0
1
..
Link number ( 0-11 ) of Station ID 0
Station on link ( 0-31 ) of Station ID 0
..
62
63
Link number ( 0-11 ) of Station ID 31
Station on link ( 0-31 ) of Station ID 31
Note: 1 to 32 station ids may be used to disable wallstations. To trigger the command, write the number of station IDs into the Data Array specified
by Data_Array_Name at Data_Array_Offset.
FS-8700-84_Lutron_eLumen Driver Manual
Page 25 of 36
4.1.33.
System Control Commands containing no Parameters: Simulate wallstation(s) switch press
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Ws_sw_press,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
16,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
sim_ws_sw_press,
DA_Lut_List,
Sim_sw_list,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
Description
0
1
Link number ( 0-11 )
Station of link ( 0-31 ) of Switch ID 0
2
3
4
..
Switch on station ( 0-31 ) of Switch ID 0
Station of link ( 0-31 ) of Switch ID 1
Switch on station ( 0-31 ) of Switch ID 1
..
63
64
Station of link ( 0-31 ) of Switch ID 31
Switch on station ( 0-31 ) of Switch ID 31
Note: 1 to 32 switch ids may be used in a single command. To trigger the command, write the number of switch IDs into the Data Array specified
by Data_Array_Name at Data_Array_Offset.
FS-8700-84_Lutron_eLumen Driver Manual
Page 26 of 36
4.1.34.
System Control Commands containing no Parameters: Simulate wallstation(s) switch release
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Ws_sw_rls,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
17,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
sim_ws_sw_rls,
DA_Lut_List,
Sim_sw_list,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
Description
0
1
Link number ( 0-11 )
Station of link ( 0-31 ) of Switch ID 0
2
3
4
..
Switch on station ( 0-31 ) of Switch ID 0
Station of link ( 0-31 ) of Switch ID 1
Switch on station ( 0-31 ) of Switch ID 1
..
63
64
Station of link ( 0-31 ) of Switch ID 31
Switch on station ( 0-31 ) of Switch ID 31
Note: 1 to 32 switch ids may be used in a single command. To trigger the command, write the number of switch IDs into the Data Array specified
by Data_Array_Name at Data_Array_Offset.
4.1.35.
System Control Commands containing no Parameters: Stop scene ramp down
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Stop_scn_rmp_dn,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
18,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
stop_scene_ramp_dn,
DA_Lut_List,
Area_list,
DA_Lut_List_Offset,
0,
Length
1
DA_Lut_List data setup
Position from DA_Lut_List_Offset
0-31
Description
Area(s) with scenes to stop ramp down
Note: After setting up the area numbers to stop scene ramps in the DA_Lut_List Data Array, trigger this command by writing the number of areas
into the Data Array specified by Data_Array_Name at an offset specified by Data_Array_Offset.
FS-8700-84_Lutron_eLumen Driver Manual
Page 27 of 36
4.1.36.
System Control Commands Containing Parameters: Toggle zone
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Toggle_zone,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
19,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
toggle_zone,
DA_Lut_List,
Zone_list,
DA_Lut_List_Offset,
0,
DA_Lut_Parms,
Zone_pars,
DA_Lut_Parms_Offset,
0,
Length
1
DA_Lut_List setup
Position from DA_Lut_List_Offset
Description
0-63
Zone(s) to toggle
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset
Description
0
Fade cycles
4.1.37.
System Control Commands Containing Parameters: Fade zone(s) to level
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Fade_to_level,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
20,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
fade_zone,
DA_Lut_List,
Zone_list,
DA_Lut_List_Offset,
0,
DA_Lut_Parms,
Zone_pars,
DA_Lut_Parms_Offset,
0,
Length
1
DA_Lut_List setup
Position from DA_Lut_List_Offset
Description
0-63
Zone(s) to fade to level
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset
Description
0
1
2
Level to fade to ( 0-127 )
Fade cycles
Delay cycles
FS-8700-84_Lutron_eLumen Driver Manual
Page 28 of 36
4.1.38.
System Control Commands Containing Parameters: Ramp zone(s) up
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Rmp_zones_up,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
21,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
ramp_zones_up,
DA_Lut_List,
Zone_list,
DA_Lut_List_Offset,
0,
DA_Lut_Parms,
Zone_pars,
DA_Lut_Parms_Offset,
0,
Length
1
DA_Lut_List setup
Position from DA_Lut_List_Offset
Description
0-63
Zone(s) to ramp up
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset
Description
0
1
Initial rate step size
Repeat rate step size
4.1.39.
System Control Commands Containing Parameters: Ramp zone(s) down
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Rmp_zones_up,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
22,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
ramp_zones_down,
DA_Lut_List,
Zone_list,
DA_Lut_List_Offset,
0,
DA_Lut_Parms,
Zone_pars,
DA_Lut_Parms_Offset,
0,
Length
1
DA_Lut_List setup
Position from DA_Lut_List_Offset
Description
0-63
Zone(s) to ramp down
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset
Description
0
1
Initial rate step size
Repeat rate step size
FS-8700-84_Lutron_eLumen Driver Manual
Page 29 of 36
4.1.40.
System Control Commands Containing Parameters: Pommel or pulse zone(s Toggle zone)
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Pulse_zone,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
23,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
pulse_zone,
DA_Lut_List,
Zone_list,
DA_Lut_List_Offset,
0,
DA_Lut_Parms,
Zone_pars,
DA_Lut_Parms_Offset,
0,
Length
1
DA_Lut_List setup
Position from DA_Lut_List_Offset
Description
0-63
Zone(s) to pommel or pulse
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset
Description
0
1
2
3
4
5
Delay1 cycles
Intensity1 ( 0-127 )
Fade1 cycles
Delay2 cycles
Intensity2 ( 0-127 or 255 )
Fade2 cycles
FS-8700-84_Lutron_eLumen Driver Manual
Page 30 of 36
4.1.41.
System Control Commands Containing Parameters: Flash zones aka “Multi level ( Flash or
Warn or Chase )“
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Flash_zone,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
24,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
flash_zone,
DA_Lut_List,
Zone_list,
DA_Lut_List_Offset,
0,
DA_Lut_Parms,
Zone_pars,
DA_Lut_Parms_Offset,
0,
Length
1
DA_Lut_List setup
Position from DA_Lut_List_Offset
Description
0-63
Zone(s) to flash
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset
Description
0
1
2
3
4
5
6
7
Delay1 cycles
Intensity1 ( 0-127 )
Fade1 cycles
Delay2 cycles
Intensity2 ( 0-127 )
Fade2 cycles
Delay2 cycles
Repeat ( 0-255 )
4.1.42.
System Control Commands Containing Parameters: Ramp scene zones up
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Rmp_scn_zns_up,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
25,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
ramp_scene_zones_up,
DA_Lut_List,
Area_list,
DA_Lut_List_Offset,
0,
DA_Lut_Parms,
Area_pars,
DA_Lut_Parms_Offset,
0,
Length
1
DA_Lut_List setup
Position from DA_Lut_List_Offset
Description
0-31
System area numbers
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset
Description
0
1
2
Unaffected intensity ( 0-128 )
Initial rate step size
Repeat rate step size
FS-8700-84_Lutron_eLumen Driver Manual
Page 31 of 36
4.1.43.
System Control Commands Containing Parameters: Ramp scene zones down
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Rmp_scn_zns_dn,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
26,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
ramp_scene_zones_dn,
DA_Lut_List,
Area_list,
DA_Lut_List_Offset,
0,
DA_Lut_Parms,
Area_pars,
DA_Lut_Parms_Offset,
0,
Length
1
DA_Lut_List setup
Position from DA_Lut_List_Offset
Description
0-31
System area numbers
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset
Description
0
1
2
Unaffected intensity ( 0-128 )
Initial rate step size
Repeat rate step size
4.1.44.
times
System Control Commands Containing Parameters: Select system scene(s) using override
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Sel_scene_oride,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
27,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
sel_scene_override,
DA_Lut_List,
Scene_list,
DA_Lut_List_Offset,
0,
DA_Lut_Parms,
Scene_pars,
DA_Lut_Parms_Offset,
0,
Length
1
DA_Lut_List setup
Position from DA_Lut_List_Offset
Description
0-63
System scene numbers
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset
0
1
Description
Fade cycles
Delay cycles
FS-8700-84_Lutron_eLumen Driver Manual
Page 32 of 36
4.1.45.
System Control Commands Containing Parameters: Set system variable value
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Set_sys_var,
Data_Array_Name,
Lut_triggers,
Data_Array_Offset,
28,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
set_sys_var_val,
DA_Lut_List,
Var_list,
DA_Lut_List_Offset,
0,
DA_Lut_Parms,
Var_pars,
DA_Lut_Parms_Offset,
0
Length
1
DA_Lut_List setup
Position from DA_Lut_List_Offset
Description
0-31
System variable numbers
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset
Description
0
New value
4.1.46.
Listening to switch presses and releases: Enabling switch presses and releases reporting
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Ena_sw_lsn,
Data_Array_Name,
Sw_lsn_trigger,
Data_Array_Offset,
0,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
enable_sw_listen,
length
1
Note: To enable the reporting of switch presses and releases, write any value into the Sw_lsn_trigger Data Array at offset specified by
Data_Array_Offset.
4.1.47.
Listening to switch presses and releases: Disabling switch presses and releases reporting
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Dis_sw_lsn,
Data_Array_Name,
Sw_lsn_trigger,
Data_Array_Offset,
1,
Function,
awt,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
disable_sw_listen,
length
1
Note: To disable the reporting of switch presses and releases, write any value into the Sw_lsn_trigger Data Array at offset specified by
Data_Array_Offset.
FS-8700-84_Lutron_eLumen Driver Manual
Page 33 of 36
4.1.48.
Listening to switch presses and releases: Listening to switch presses and releases
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Raw_sw_sts_00,
Data_Array_Name,
Raw_sw_sts_00,
Data_Array_Offset,
0,
Function,
passive,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
raw_sw_status,
link
0
Switch press and release status storage Data Array format
Position from Data_Array_Offset
Description
0
1
..
Station0, Switch0, status
Station0, Switch1, status
..
31
32
63
..
Station0, Switch31, status
Station1, Switch0, status
Station1, Switch31, status
..
1022
1023
Station31, Switch30, status
Station31, Switch31, status
Note: You have to set up a separate Map Descriptor for every link to be monitored for switch presses and releases.
FS-8700-84_Lutron_eLumen Driver Manual
Page 34 of 36
4.1.49.
Active read on startup: Retrieving names
Warning: Only one (1) active read on startup Map Descriptor may be used.
The retrieval of area, scene and zone names is done with a single active read on startup (ars ) Map Descriptor. Enter the
start and end numbers for the names you want to retrieve from the eLumen. The names will be stored sequentially in the
indicated Data Arrays
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Get_Names,
Function,
ars,
Node_Name,
LUT_GRF6_0,
GRAFIK_command,
get_names,
DA_Area_Names,
Area_Names,
DA_Area_Names_Offset,
0,
Area_Names_Start,
0,
Area_Names_End,
511,
DA_Scene_Names_Offset,
0,
Scene_Names_Start,
0,
Scene_Names_End,
50,
DA_Zone_Names,
Zone_Names,
DA_Zone_Names_Offset,
0,
Zone_Names_Start,
0,
Zone_Names_End,
511,
Length
1
Area names storage format
Position from DA_Area_Names_Offset Description
0
Area (name_start) name
40
80
Area (name_start+1) name
Area (name_start+2) name
..
40 * name_end
Area (name_end) name
Scene names storage format
Position from DA_Scene_Names_Offset Description
0
Scene (name_start) name
40
80
Scene (name_start+1) name
Scene (name_start+2) name
..
40 * name_end
Scene (name_end) name
Zone names storage format
Position from DA_Zone_Names_Offset Description
0
Zone (name_start) name
40
80
Zone (name_start+1) name
Zone (name_start+2) name
..
40 * name_end
Zone (name_end) name
FS-8700-84_Lutron_eLumen Driver Manual
Page 35 of 36
Appendix A. Data Tables
Table of Legal Values for Commands to be sent to the eLumen
pnl_emerg_status
wallstation_status
switch_status
Area_status
timeclock_status
zone_intensity
sys_var_val
time_now
astro_times
date
run_script
toggle_sys_var_val
output_temp_scene
sel_scene_in_area
tclk_new_schedule
set_tclk
ena_wallstation
dis_wallstation
sim_ws_sw_press
sim_ws_sw_rls
toggle_zone
code_rev_level
bootcode_rev_level
serial_no
fade_zone
ramp_zones_up
ramp_zones_down
pulse_zone
halt_zone
stop_scene_ramp_up
stop_scene_ramp_dn
sel_scene
flash_zone
ramp_scene_zones_up
ramp_scene_zones_dn
sel_scene_override
set_sys_var_val
get_names
dis_tclk_u_e
dis_tclk_u_eodoe
rnbl_tclk_catchup
rnbl_tclk_do_prev_evt
std_tclk_rnbl
FS-8700-84_Lutron_eLumen Driver Manual
Page 36 of 36
Appendix B. Revision History
Driver Doc.
Date
Resp Format
Comment
Ver.
1.00
1.00
Rev.
0
1
05/10/02
06/27/02
Initial version
Updated with awt Map Descriptor function
Updated get_names function using one
ars Map Descriptor
06/28/02
1.00
2
Updated switch status and wallstation
status mapdesc descriptions. Added
length column to all mapdesc examples.
Added stop scene ramp down command.
Added request panel emergency status
command.
08/14/02
1.00
3
09/23/02
12/31/02
1.01
1.02
0
0
03/18/02
08/20/03
1.03
1.03
0
1
Updated max area number to 511
Releasing
DUR0262, removed extra rows in Select
Scene in Area data setup table.
Major manual reformat – DUR0479
Changed document name – DUR0468.
Updated Description – 0469
Added RS-485 functionality – DUR0481
Changed protocol and description name
to ELUMEN. Some formatting updates.
DUR0468
Further changes as sanctioned by DR.
Connection diagram updated to show
correct adapter, wire list tidied up. Info
on RS-485 connection requested from
DR.
11/07/03
1.03
2
10/20/04 Meg Meg
11/11/04 Meg Meg
1.03
3
1.04
1.04
0
1
11/12/04 Meg Meg
Connection drawings updated according
to data from customer and comments
from Mac. Formatting and common
documentation errors eliminated.
Releasing
12/17/04 Meg Meg
1.04
1.04
2
3
1/6/05
JD
|