1.  
Allen Bradley DF1 Description  
The DF1 driver allows the FieldServer to transfer data to and from devices over RS-232 using  
DF1 protocol. The FieldServer can emulate either a Server or Client.  
The information that follows describes how to expand upon the factory defaults provided in the  
configuration files included with the FieldServer.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-03 DF1 Driver Manual  
Page 4 of 16  
2.  
Driver Scope of Supply  
2.1. Supplied by FieldServer Technologies for this driver  
FieldServer Technologies  
PART #  
Description  
FS-8915-10  
FS-8917-06  
FS-8700-03  
UTP cable (7 foot) for RS-232 use  
RJ45 to DB9M connection adapter  
Driver Manual.  
2.2.  
Provided by the Supplier of 3rd Party Equipment  
PART #  
DESCRIPTION  
AB DF1 compatible PLC, e.g. SLC5/03, PLC 5/40, etc. 1  
DF1 Client, e.g. Wonderware, Intellution FIX, GE Cimplicity, etc. 2  
1 If FieldServer used as Allen Bradley DF1 Client  
2 If FieldServer used as Allen Bradley DF1 Server  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-03 DF1 Driver Manual  
Page 5 of 16  
3.  
Hardware Connections  
It is possible to connect an Allen Bradley PLC to any of the RS-232 ports. These ports simply  
need to be configured for an Allen Bradley PLC in the configuration file.  
ALLEN BRADLEY PLC  
COMM 2  
FS8917-06  
RJ45 CAT 5 Cable  
FS8915-10  
8917-06 WIRE LIST  
FUNCTION  
FROM  
RJ45-01  
RJ45-04  
RJ45-08  
TO  
COLOUR  
WHITE  
GREEN  
BLUE  
Rx  
GND  
Tx  
DB9F-03  
DB9F-05  
DB9F-02  
(408)-262-2299  
FIELDSERVER  
DF1  
CONNECTION DIAGRAM  
BASE NAME:  
FILE NAME:  
DATE: 4/20/04  
BY: MC  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-03 DF1 Driver Manual  
Page 6 of 16  
4.  
Configuring the FieldServer as a DF1 Client  
For a detailed discussion on FieldServer configuration, please refer to the FieldServer  
Configuration Manual. The information that follows describes how to expand upon the factory  
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files  
provided with the FS).  
This section documents and describes the parameters necessary for configuring the FieldServer  
to communicate with a DF1 Server  
4.1.  
Data Arrays/Descriptors  
The configuration file tells the FieldServer about its interfaces, and the routing of data  
required. In order to enable the FieldServer for DF1 communications, the driver  
independent FieldServer buffers need to be declared in the “Data Arrays” section, the  
destination device addresses need to be declared in the “Client Side Nodes” section, and  
the data required from the Servers needs to be mapped in the “Client Side Map Descriptors”  
section. Details on how to do this can be found below.  
Note that in the tables, * indicates an optional parameter, with the bold legal value being the  
default.  
Section Title  
Data_Arrays  
Column Title  
Function  
Legal Values  
Up to 15 alphanumeric  
characters  
Data_Array_Name  
Provide name for Data Array  
Data_Format  
Data_Array_Length  
Provides data format  
Number of Data Objects  
INT16, INT32, BIT, FLOAT  
1-10,000  
Example  
// Data Arrays  
Data_Array_Name,  
DA_AI_01,  
DA_AO_01,  
DA_DI_01,  
Data_Format,  
Float,  
Float,  
Bit,  
Bit,  
Data_Array_Length  
200  
200  
200  
200  
DA_DO_01,  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-03 DF1 Driver Manual  
Page 7 of 16  
4.2.  
Client Side Connections  
Section Title  
Connections  
Column Title  
Function  
Legal Values  
Specify which port the device is  
connected to the FieldServer  
Specify baud rate  
Specify parity  
Specify data bits  
Port  
P1-P83  
Baud*  
Parity*  
300 to 115200; 9600  
Even, Odd, None  
8
Data_Bits*  
Handshaking*4  
Specify hardware handshaking  
RTS, RTS/CTS, None  
DF1_FD, DF1_HD_MASTER,  
DF1_HD_SLAVE  
Protocol *  
Specify protocol used  
Example  
// Client Side Connections  
Ports,  
Port,  
P8,  
Protocol  
DF1_FD  
4.3.  
Client Side Node Descriptors  
Section Title  
Nodes  
Column Title  
Node_Name  
Function  
Legal Values  
Up to 32 alphanumeric characters  
Provide name for node  
Node ID of physical Server node  
(PLC)  
Node_ID  
Protocol  
Port  
1-255  
DF1_FD, DF1_HD_MASTER,  
DF1_HD_SLAVE  
P1-P83  
Specify protocol used  
Specify which port the device is  
connected to the FieldServer  
Specify PLC  
PLC_Type  
PLC3, PLC5, SLC5  
Communications type.  
Example  
// Client Side Nodes  
Nodes  
Node_Name,  
PLC_01,  
Node_ID,  
1,  
Protocol,  
DF1_FD,  
PLC _Type,  
SLC5,  
Port  
P8  
3 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction  
manual for details of the ports available on specific hardware.  
4 Handshaking is not supported, only the enabling of the RTS/CTS lines  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-03 DF1 Driver Manual  
Page 8 of 16  
4.4.  
4.4.1.  
Client Side Map Descriptors  
FieldServer Related Map Descriptor Parameters  
Column Title  
Function  
Legal Values  
Up to 32 alphanumeric  
characters  
Map_Descriptor_Name  
Name of this Map Descriptor  
Name of Data Array where  
data is to be stored in the  
FieldServer  
One of the Data Array  
names from “Data Array”  
section above  
Data_Array_Name  
0 to maximum specified in  
“Data Array” section above  
Data_Array_Offset  
Function  
Starting location in Data Array  
Function of Client Map  
Descriptor  
RDBC, WRBC, WRBX  
4.4.2.  
Driver Related Map Descriptor Parameters  
Column Title  
Function  
Legal Values  
One of the node names  
specified in “Client Node  
Descriptor” above  
N, F, B, I, O5  
Name of Node to fetch data  
from  
Node_Name  
File_Type  
File type in PLC  
File_Number  
Address  
Data_Array_Low_Scale*  
Data_Array_High_Scale*  
File Number in PLC  
Starting address of read block  
Scaling zero in Data Array  
Scaling max in Data Array  
Scaling zero in Connected  
Node  
0-255  
0 – 255  
-32767 to 32767, 0  
-32767 to 32767, 100  
Node_Low_Scale*  
Node_High_Scale*  
-32767 to 32767, 0  
Scaling max in Connected  
Node  
-32767 to 32767, 100  
5 Not all PLC’s can support all File_Types. Refer to DFS for further information.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-03 DF1 Driver Manual  
Page 10 of 16  
5.  
Configuring the FieldServer as a DF1 Server  
For a detailed discussion on FieldServer configuration, please refer to the FieldServer  
Configuration Manual. The information that follows describes how to expand upon the factory  
defaults provided in the configuration files included with the FieldServer (See “.csv” files on the  
driver diskette).  
This section documents and describes the parameters necessary for configuring the FieldServer  
to communicate with a DF1 Client.  
The configuration file tells the FieldServer about its interfaces, and the routing of data required.  
In order to enable the FieldServer for DF1 communications, the driver independent FieldServer  
buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs  
to be declared in the “Server Side Nodes” section, and the data to be provided to the Clients  
needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this  
can be found below.  
Note that in the tables, * indicates an optional parameter, with the bold legal value being the  
default.  
5.1.  
Server Side Connection Descriptions  
Section Title  
Connections  
Column Title  
Function  
Legal Values  
Specify which port the device is connected  
to the FieldServer  
Port  
P1-P86  
Baud*  
Parity*  
Specify baud rate  
Specify parity  
Specify data bits  
300 to 115200; 9600  
Even, Odd, None  
8
Data_Bits*  
Handshaking*7 Specify hardware handshaking  
RTS, RTS/CTS, None  
DF1_FD, DF1_HD_MASTER,  
DF1_HD_SLAVE  
Protocol  
Specify protocol used  
Example  
// Server Side Connections  
Ports,  
Port,  
P1,  
Protocol  
DF1_FD  
6 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction  
manual for details of the ports available on specific hardware.  
7 Handshaking is not supported, only the enabling of the RTS/CTS lines  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-03 DF1 Driver Manual  
Page 11 of 16  
5.2.  
Server Side Node Descriptions  
Section Title  
Nodes  
Column Title  
Function  
Legal Values  
Up to 32 alphanumeric  
characters  
Node_Name  
Node_ID  
Provide name for node  
Node ID of physical Server  
node  
1-255  
DF1_FD, DF1_HD_MASTER,  
DF1_HD_SLAVE  
Protocol  
Specify protocol used  
Specify PLC Communications  
type.  
PLC_Type  
PLC3, PLC5, SLC5  
Example  
// Server Side Nodes  
Nodes  
Node_Name,  
DF1_Srv_11,  
Node_ID,  
11,  
Protocol,  
DF1_FD,  
PLC _Type  
SLC5  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-03 DF1 Driver Manual  
Page 12 of 16  
5.3.  
5.3.1.  
Server Side Map Descriptors  
FieldServer Specific Map Descriptor Parameters  
Section Title  
Map_Descriptors  
Column Title  
Function  
Legal Values  
Up to 32 alphanumeric  
characters  
Map_Descriptor_Name  
Name of this Map Descriptor  
Name of Data Array where  
data is to be stored in the  
FieldServer  
One of the Data Array  
names from “Data Array”  
section above  
Data_Array_Name  
Starting location in Data  
Array  
Function of Client Map  
Descriptor  
0 to maximum specified in  
“Data Array” section above  
Data_Array_Offset  
Function  
Server  
5.3.2.  
Driver Specific Map Descriptor Parameters  
Section Title  
Map_Descriptors  
Column Title  
Function  
Legal Values  
One of the node names  
specified in “Client Node  
Descriptor” above  
N, F, B, I, O8  
Name of Node to fetch data  
from  
Node_Name  
File_Type  
File type in PLC  
File_Number  
File number in PLC  
Starting address of read  
block  
0-255  
Address  
0 - 255  
Data_Array_Low_Scale*  
Data_Array_High_Scale*  
Scaling zero in Data Array  
Scaling max in Data Array  
Scaling zero in Connected  
Node  
Scaling max in Connected  
Node  
-32767 to 32767, 0  
-32767 to 32767, 100  
Node_Low_Scale*  
Node_High_Scale*  
-32767 to 32767, 0  
-32767 to 32767, 100  
8 Not all PLC’s can support all File_Types. Refer to DFS for further information.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-03 DF1 Driver Manual  
Page 14 of 16  
Appendix A. Driver Notes  
Appendix A.1. Continuous Map Descriptors  
RS View has been known to crash if it tries to read a Server mapping that is discontinuous.  
e.g.  
Server map 1: N21: 0-31  
Server map 2: N21: 32-100  
This will panic the FieldServer and crash RS view as the DF1 will attempt to map N21: 0-100  
If set up as:  
Server Map 1: N21: 0-100 No problems are experienced  
Appendix A.2. Checksum  
You can now specify a checksum parameter for the serial connection.  
The heading keyword is "Checksum" and the possible values are  
1) BCC or 2) CRC-16  
If nothing is specified it defaults to BCC.  
Example:  
Connections  
Port,  
P1,  
Baud,  
9600,  
Protocol,  
DF1_FD,  
Checksum  
CRC-16  
The Checksum is valid for both DF1_FD and DF1_HD.  
Appendix A.3. Command Support  
The following commands are supported by the FieldServer for the various PLC types:  
Typical  
Command  
PLC_Type File_Type FNC  
Read  
FNC Write  
N
F
B
N
F
B
1
1
1
1
1
1
Range Read  
Range Read  
Range Read  
Range Read  
Range Read  
Range Read  
Protected Typed  
Logical Read  
Protected Typed  
Logical Read  
Protected Typed  
Logical Read  
Protected Typed  
Logical Read  
Protected Typed  
Logical Read  
0
0
2
0
67  
26  
Range Write  
Range Write  
Bit Write  
Range Write  
N7: 3, L5  
PLC3  
PLC5  
F12: 3, L5  
B3/4: 5, l5  
N7: 3 , L5  
F12: 3, L5  
B3/4: 5, L5  
Typed Write  
Read Modify Write  
Protected Typed  
Logical Write  
Protected Typed  
Logical Write  
Protected Typed  
Logical Write  
N
F
B
I
A2/A1  
A2/A1  
A2/A1  
A2/A1  
A2/A1  
AA  
AA  
AB  
-
N7: 3, L5  
B3/4: 5, L7  
B3/4: 5, L8  
I: 13, L5  
SLC5  
-
-
O
-
O: 13, L5  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-03 DF1 Driver Manual  
Page 15 of 16  
Appendix B. Error Messages  
DF1 Rem STS err F0-> Extended error code [See table below]  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-03 DF1 Driver Manual  
Page 16 of 16  
THIS PAGE INTENTIONALLY LEFT BLANK  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: [email protected]  

Nokia 5180 User Manual
Nokia 203 User Manual
Mr Coffee MPX33 User Manual
JVC KD SX949 User Manual
JVC 340SC User Manual
Echo Bear Cat CH9540H 72854 User Manual
Denon DVM 1845 User Manual
Black & Decker AM8C User Manual
AT&T BLACKBERRY 8820 User Manual
Asus CRW 5232AS User Manual