Bunn System III User Manual

®
BUNN  
®
SYSTEM III  
OPERATING & SERVICE MANUAL  
BUNN-O-MATIC CORPORATION  
POST OFFICE BOX 3227  
SPRINGFIELD, ILLINOIS 62708-3227  
PHONE: (217) 529-6601 FAX: (217) 529-6644  
27362.0000B 9/00 ©1996 Bunn-O-Matic Corporation  
USER NOTICES  
Carefully read and follow all notices in this manual and on the equipment. The notices on this brewer should  
be kept in good condition. Replace any unreadable or damaged labels.  
12364.0000  
10044.0000  
! WARNING HOT WATER  
20201.5600  
00831.0000  
03408.0000  
00656.0000  
03409.0000  
27362 092900  
Page 3  
ELECTRICAL REQUIREMENTS  
CAUTION - The brewer must be disconnected from the power source until specified in Initial Set-Up.  
L2RED  
L2 RED  
120V.A.C.  
WHITE  
208 or 240V.A.C.  
200 OR 240V.A.C.  
P2185  
L1 BLACK  
NEUTRAL  
BLACK  
120V.A.C.  
P1841  
"A" & "B" models require 2-wire,  
grounded service rated 200 volts ac  
or240voltsac,20amp,singlephase,  
50 Hz.  
Requires 3-wire, grounded ser-  
vice rated 120/208 volts or 120/240  
volts ac, 20 amp, single phase, 60  
Hz.  
Electrical Hook-Up  
CAUTION – Improper electrical installation will damage electronic components.  
1. An electrician must provide electrical service as specified.  
2. Using a voltmeter, check the voltage and color coding of each conductor at the electrical source.  
3. Remove the front panel beneath the sprayhead.  
Models with digital brewer control assembly:  
Place the tank heater toggle switch at the bottom left of the control assembly in the "OFF" position.  
Models with electro/mechanical thermostats:  
Rotate the control thermostat knob fully counterclockwise to the "OFF" position.  
4. Feed the cord through the strain relief and connect it to the terminal block.  
5. Connectthebrewertothepowersourceandverifythevoltageattheterminalblockbeforeproceeding. Replace  
the front panel.  
6. If plumbing is to be hooked up later be sure the brewer is disconnected from the power source. If plumbing  
has been hooked up, the brewer is ready for Initial Set-Up.  
PLUMBING REQUIREMENTS  
This brewer must be connected to a cold water system with operating pressure between 20 (138) and 90 psi  
(620 kPa) from a 12" or larger supply line. A shut-off valve should be installed in the line before the brewer. Install  
a regulator in the line when pressure is greater than 90 psi (620 kPa) to reduce it to 50 psi (345 kPa). The water  
inlet fitting is 38" flare.  
3
NOTE – Bunn-O-Matic recommends 8" copper tubing for installations of less than 25 feet and 1/2" for more than  
25 feet from the 12" water supply line. A tight coil of copper tubing in the water line will facilitate moving the brewer  
to clean the countertop. Bunn-O-Matic does not recommend the use of a saddle valve to install the brewer. The  
size and shape of the hole made in the supply line by this type of device may restrict water flow.  
This equipment must be installed to comply with the Basic Plumbing Code of the  
Building Officials and Code Administrators International, Inc. (BOCA)  
and the Food Service Sanitation Manual of the Food and Drug Administration (FDA).  
Plumbing Hook-Up  
3
1. Remove the 8" flare cap from the bulkhead fitting on the bottom of the brewer.  
2. Flush the water line and securely attach it to the bulkhead fitting on the bottom of the brewer.  
3. Turn on the water supply.  
27362 092900  
Page 4  
INITIAL SET-UP  
CAUTION – The brewer must be disconnected from the power source throughout the initial set-up, except when  
specified in the instructions.  
1. Remove the front panel beneath the sprayhead.  
Models with digital brewer control assembly:  
Place the tank heater toggle switch at the bottom left of the control assembly in the "OFF" position.  
Models with electro/mechanical thermostats:  
Rotate the control thermostat knob fully counterclockwise to the "OFF" position.  
2. Connect the brewer to the power source. Water will begin flowing into the tank.  
3. When water stops flowing into the tank, remove the front panel and proceed as directed.  
Models with digital brewer control assembly:  
Place the tank heater toggle switch at the bottom left of the control assembly in the "ON" position and replace  
the front panel.  
Models with electro/mechanical thermostats:  
Rotate the control thermostat knob fully clockwise to the "ON" position and replace the front panel.  
4. On208Vor240VModels, waitapproximatelytwenty-fiveminutes forthewaterinthetanktoheattotheproper  
temperature.  
5. Place an empty server beneath the brew station. Place the Selector switch in the desired position, the ON/OFF  
switch in the "ON" (upper) position and initiate a brew cycle. Each volume must be set individually.  
6. PlacetheON/OFFswitchinthe"OFF"(lower)positionafterwaterhasstoppedflowingfromthefunnel,andcheck  
the water volume in the server. It should be 128 oz (1 gallon), 192 oz (1-1/2 gallon) or 256 oz (2 gallon).  
7. (A) If not, adjust the brew timer as required. SeeAdjusting Brew Volumes for electro/mechanical brewers. See  
Service - Digital Brewer Control Board for DBC Brewers. Allow the water to reheat, start, and measure another  
brew cycle.  
(B) If necessary adjust the needle valve to achieve water volume to be bypassed around the coffee filter in the  
funnel.  
NOTE: To increase the water bypass turn the needle valve counterclockwise, to decrease the water bypass turn  
the needle valve clockwise. An adjustment to the needle valve will require a timer adjustment for desired  
volume.  
8. Repeat step 7 until the proper water volume is achieved.  
9. The brewer is now ready for use in accordance with the coffee brewing instructions.  
ADJUSTING BREW VOLUMES  
electro/mechanical brewers  
CAUTION - Disconnect the power source from the brewer prior to the removal of any panel for the replacement  
or adjustment of any component.  
NOTE: Prior to setting or modifying batch sizes, check that the brewer is connected to water supply, the tank is  
properly filled, and a funnel and server are in place.  
1. Modifying batch sizes. To modify a batch volume, first check that the SET/LOCK switch is in the SET”  
position on the circuit board. Select the batch volume to be set. (1, 1-1/2, or 2 gallons)  
NOTE: Each batch setting must be adjusted separately.  
To increase a batch size. Press and hold the START or BREW switch until three clicks are heard. Release the  
switch (Failure to release the switch within two seconds after the third click causes the volume setting to be  
aborted and previous volume setting will remain in memory) and press it again one or more times. Each time  
the switch is pressed, two seconds are added to the brew time period. Allow the brew cycle to finish in order  
to verify that the desired volume has been achieved.  
27362 092900  
Page 5  
ADJUSTING BREW VOLUMES (cont.)  
To decrease a batch size. Press and release the START or BREW switch once for every two-second interval  
to be removed from the total brew time period; then immediately press and hold down the START or BREW  
switch until three clicks are heard. Release the switch. (Failure to release the switch within two seconds after  
the third click causes the volume setting to be aborted and previous volume setting will remain in memory).  
Allow the brew cycle to finish in order to verify that the desired volume has been achieved.  
2. Setting batch sizes. To set a batch volume, first check that the SET/LOCK switch is in the "SET" position on  
the circuit board. Press and hold the START or BREW switch until three distinct clicks are heard, and then  
release the switch. (Failure to release the switch within two seconds after the third click causes the volume  
setting to be aborted and previous volume setting will remain in memory). View the level of the liquid being  
dispensed. When the desired level is reached, turn the ON/OFF switch to "OFF" (lower). The brewer remem-  
bers this volume and will continue to brew batches of this size until the volume setting procedure is repeated.  
NOTE: When brewing coffee, batch volumes will decrease due to absorption by the coffee grounds.  
3. Setting programming disable feature. If it becomes necessary to prevent anyone from changing brew times  
once programmed, you can set the SET/LOCK switch to the "LOCK" position. This will prevent any program-  
ming to be done until switch is once again placed in the "SET" position.  
OPERATING CONTROLS  
BREW SELECTOR SWITCH  
Placing the switch in the 1Gal, 1-1/2Gal or 2Gal position selects the amount of coffee to be brewed in  
subsequent brew cycles. Repositioning this switch after a brew cycle has been initiated does not change the brew  
batch in progress.  
ON/0FF (Warmer) SWITCH  
Placing the switch in the unlighted lower position cuts power to the brew station warmer and stops brewing.  
Stopping a brew cycle after it has been started will not stop the flow of water from the funnel. Placing the switch  
in the lighted upper position supplies power to the brew station warmer and enables the brew circuit.  
START SWITCH  
Momentarily pressing and releasing this switch starts a brew cycle when the ON/OFF switch is in the lighted  
upper position.  
NOTE – The ON/OFF switch must be in the lighted upper position to initiate and complete a brew cycle.  
COFFEE BREWING  
1. Select the desired batch size.  
2. Insert a BUNN® filter into the funnel.  
3. Pour the proper amount of fresh coffee into the filter and level the bed of grounds by gently shaking.  
4. Slide the funnel into the funnel rails.  
5. Place an empty server under the funnel.  
6 Place the ON/OFF switch in the lighted upper position. Momentarily press and release the Start switch.  
7. When brewing is complete, simply discard the grounds and filter.  
CLEANING  
1. The use of a damp cloth rinsed in any mild, nonabrasive, liquid detergent is recommended for cleaning all  
surfaces on Bunn-O-Matic equipment.  
2. Check and clean the sprayhead. The sprayhead holes must always remain open.  
NOTE – In hard water areas, this may need to be done daily. It will help prevent liming problems in the brewer and  
takes less than a minute.  
27362 092900  
Page 6  
TROUBLESHOOTING  
A troubleshooting guide is provided to suggest probable causes and remedies for the most likely problems  
encountered. If the problem remains after exhausting the troubleshooting steps, contact the Bunn-O-Matic  
Technical Service Department.  
Inspection,testing,andrepairofelectricalequipmentshouldbeperformedonlybyqualifiedservice  
personnel.  
All electronic components have 120 - 240 volt ac and low voltage dc potential on their terminals.  
Shorting of terminals or the application of external voltages may result in board failure.  
Intermittent operation of electronic circuit boards is unlikely. Board failure will normally be  
permanent. If an intermittent condition is encountered, the cause will likely be a switch contact or  
a loose connection at a terminal or crimp.  
Solenoid removal requires interrupting the water supply to the valve. Damage may result if  
solenoids are energized for more than ten minutes without a supply of water.  
The use of two wrenches is recommended whenever plumbing fittings are tightened or loosened.  
This will help avoid twists and kinks in the tubing.  
Makecertainthatallplumbingconnectionsaresealedandelectricalconnectionstightandisolated.  
This brewer is heated at all times. Keep away from combustibles.  
WARNING  
Exercise extreme caution when servicing electrical equipment.  
Disconnect power source when servicing, except when electrical tests are specified.  
Follow recommended service procedures.  
Replace all protective shields or safety notices.  
Probable Cause  
Remedy  
Problem  
1. No power or incorrect voltage  
Equipment will not operate.  
(A1) Check the terminal block for  
120 volts across the red and white  
terminals and the black and white  
terminals on 120/208 or 120/240  
volt brewers.  
(A2) Check the terminal block for  
200 volts on "B Series" brewers or  
240 volts on "A Series" brewers  
across the red and black terminals.  
(B) Check circuit breakers or fuses.  
Check plumbing and shut-off valves  
1. No water  
Brew cycle will not start.  
2. Water strainer/flow control (.500  
GPM)  
(A) Direction of flow arrow must be  
pointing towards the right.  
(B) Remove the strainer/flow  
control and check for obstructions.  
Clear or replace.  
27362 092996  
Page 7  
TROUBLESHOOTING (cont.)  
Remedy  
Problem  
Probable Cause  
Brew cycle will not start (cont.)  
Refer to Service - ON/OFF switch for  
testing procedures. See page 28  
3. ON/OFF switch  
Refer to Service - Start switch for  
testing procedures. See page 32  
4. Start switch  
Refer to Service - Timer for testing  
procedures. See page 34 or 35  
5. Timer  
Refer to Service - Dispense valve for  
testing procedures. See page 21  
6. Dispense Valve  
7. Digital Brewer Control  
Refer to Service - Digital brewer  
controls for testing procedures. See  
page 22 step 4  
Automatic refill will not operate  
Checkplumbingandshut-offvalves.  
1. No water  
(A) Direction of flow arrow must be  
pointing towards the right.  
2. Water strainer/flow control (.500  
GPM)  
(B) Remove the strainer/flow con-  
trolandcheckforobstructions.Clear  
or replace.  
Refer to Service - Limit thermostat  
for testing procedures. See page 27  
3. Limit thermostat (Electro/me-  
chanicalandDigitalBrewerControl)  
Refer to Service - Overflow protec-  
tion switch for testing procedures.  
See page 29  
4. Overflow protection switch  
RefertoService-Levelcontrolboard  
for testing procedures. See page 25  
5. (A) Level control board & level  
probe. (Electro/mechanical)  
Refer to Service - Digital brewer  
control for testing procedures. See  
page 22 step 2  
(B) Digital Brewer Control Assem-  
bly (DBC)  
27362 092900  
Page 8  
TROUBLESHOOTING (cont.)  
Problem  
Probable Cause  
Remedy  
Refer to Service - Solenoid valve for  
testing procedures. See page 30  
Automatic refill will not operate 6. Solenoid Valve  
(cont.)  
RefertoService-Selectorswitchfor  
testing procedures. See page 16  
Beveragelevelwillnotadjust(Selec- 1. Selector switch  
tor switch in any position)  
RefertoService-Levelcontrolboard  
for testing procedures. See page 25  
Water flows into tank continuously 1. (A) Level control board and level  
(ON/OFF Switch "OFF")  
probe (Electro/mechanical)  
Refer to Service - Digital brewer  
control for testing procedures. See  
page 23 step 10  
(B) Digital Brewer Control  
Refer to Service - Overflow protec-  
tion switch for testing procedures.  
See page 29  
2. Overflow protection switch  
3. Solenoid valve  
Refer to Service - Solenoid valve for  
testing procedures. See page 30  
Refer to Service -Limit thermostat  
for testing procedures. See page 27  
Water from tank is not hot  
1. Limit thermostat  
CAUTION - Do not eliminate or by-  
pass limit thermostat. Use only  
B.O.M. part #23717.0001  
Refer to Service - Control thermo-  
statfortestingprocedures.Seepage  
20  
2. (A) Control Thermostat (Electro/  
mechanical)  
Refer to Service - Digital brewer  
control for testing procedure. See  
page 22 step 3  
(B) Digital Brewer Control  
Refer to Service - Contactor for test  
procedures. See page 18  
3. Contactor (Electro/mechanical)  
4. Tank heater  
Refer to Service - Tank heater for  
testing procedures. See page 33  
27362 092900  
Page 9  
TROUBLESHOOTING (cont.)  
Problem  
Remedy  
Probable Cause  
Water from tank is not hot (cont.)  
5. Triac assembly (DBC)  
RefertoService-Digitalbrewercon-  
trolfortestingprocedures. Seepage  
22  
Server warmer is not hot.  
1. ON/OFF switch  
Refer to Service - ON/OFF switch for  
testing procedures. See page 28  
2. Warmer element  
Refer to Service - Warmer element  
for testing procedures. See page 37  
Spitting or unusual steaming from  
sprayhead or airvent.  
1. (A) Control thermostat (Electro/ Refer to Service - Control thermo-  
mechanical)  
statfortestingprocedures.Seepage  
20  
(B) Digital Brewer Control  
RefertoService-Digitalbrewercon-  
trolfortestingprocedures. Seepage  
23 step 10  
2. Triac assembly (DBC)  
Refer to Service - Digital Brew Con-  
trolfortestingprocedures. Seepage  
22  
3. Lime build-up  
Inspectthetankassemblyforexces-  
sive lime deposits. Delime as re-  
CAUTION - Tank and tank compo- quired.  
nents should be delimed regularly  
dependingonlocalwaterconditions.  
Excessivemineralbuild-uponstain-  
less steel surfaces can initiate cor-  
rosive reactions resulting in serious  
leaks.  
Inconsistentbeveragelevelinserver.  
1. Strainer/flow control (.500 GPM) (A) Direction of flow arrow must be  
pointing towards the brewer.  
2. Improper water pressure  
(B) Remove the strainer/flow con-  
trolandcheckforobstructions. Clear  
or replace.  
Check the operating water pressure  
to the brewer. It must be between 20  
(138) and 90 psi (620 kPa).  
27362 092900  
Page 10  
TROUBLESHOOTING (cont.)  
Problem  
Probable Cause  
Remedy  
Inconsistentbeveragelevelinserver. 3. Dispense valve  
(cont.)  
Refer toService - Dispense valve for  
testing procedures. See page 21  
Consistently high or low beverage 1. (A) Time adjustment (Electro/  
Refer to Service - Brew Timer for  
testing and adjustment procedures.  
See pages 34 or 35  
level in server.  
mechanical)  
(B) DBC volume adjustment  
Refer to Service - Digital brewer  
control for testing procedures. See  
page 23 step 8  
Dripping from sprayhead.  
Water overflows filter.  
1. Dispense valve  
Refer to Service - Dispense valve  
for testing procedures. See page 21  
1. Bypass valve (Electro/mechani-  
cal)  
RefertoAdjustmentsonpage5step  
#7. Fortestproceduresseepage15.  
BUNN® paper filters should be used  
for proper extraction.  
2. Type of paper filters  
3. No sprayhead  
Check sprayhead  
Beverage overflows server.  
1. Beverage left in server  
The brew cycle should be started  
only with an empty server under the  
funnel.  
2. Timer adjustment  
3. Dispense valve  
1. Type of paper filters  
2. Coffee  
Refer to Service - Timer for testing  
procedures. See page 34 or 35  
Refer toService- Dispense valve for  
testing procedures. See page 21  
BUNN® paper filters should be used  
for proper extraction.  
Weak beverage.  
A sufficient quantity of fresh drip or  
regular grind should be used for  
proper extraction.  
27362 092900  
Page 11  
TROUBLESHOOTING (cont.)  
Problem  
Probable Cause  
Remedy  
B.O.M. sprayhead #01082.0002  
should be used to properly wet the  
bed of ground coffee in the funnel.  
3. Sprayhead  
Weak beverage (cont.)  
The BUNN® paper filter should be  
centered in the funnel and the bed of  
groundcoffeeleveledbygentleshak-  
ing.  
4. Funnel loading  
Empty the server, remove its cover,  
and place the server on the warmer.  
Place empty funnel over the server  
entrance, with ON/OFF switch in the  
"ON" (upper) position press the start  
switch and release it. Check the wa-  
ter temperature immediately below  
the sprayhead with a thermometer.  
The reading should not be less than  
195˚F (91˚C).  
5. Water temperature  
Thenutonbackofthesolenoidmust  
be tight or it will vibrate during op-  
eration  
1. Solenoid (Inlet)  
Brewer is making unusual noises.  
Plumbing lines should not be rest-  
ing on the counter top.  
2. Plumbing lines  
3. Water supply  
(A) The brewer must be connected  
to a cold water line.  
(B) Water pressure to the brewer  
must not be higher than 90 psi (620  
kPa). Install a regulator if necessary  
to lower the working pressure to  
approximately 50 psi (345 kPa).  
Remove and clean lime off the tank  
heater.  
4. Tank heater  
Check for low voltage.  
5. Contactor  
Refer to Service - Digital brewer  
control for testing procedures. See  
page 22 step 6  
1. Digital brewer control  
Temperature on the DBC display  
varies.  
27362 092900  
Page 12  
TROUBLESHOOTING (cont.)  
Probable Cause  
Remedy  
Problem  
RefertoService-Digitalbrewercon-  
trolfortestingprocedures. Seepage  
22 step 7  
Cannot access the DBC  
1. Digital brewer control  
RefertoService-Digitalbrewercon-  
trolfortestingprocedures. Seepage  
23 step 9  
DBC display is blank  
1. Digital brewer control  
27362 092900  
Page 13  
SERVICE  
This section provides procedures for testing and  
replacing various major components used in this  
brewer should service become necessary. Refer to  
Troubleshooting for assistance in determining the  
cause of any problem.  
WARNING - Inspection, testing, and repair of electri-  
cal equipment should be performed only by qualified  
service personnel. The brewer should be unplugged  
when servicing, except when electrical tests are re-  
quired and the test procedure specifically states to  
plug in the brewer.  
COMPONENT ACCESS  
WARNING - Disconnect the brewer from the power  
sourcebeforetheremovalofanypanelorthereplace-  
ment of any component.  
All components are accessible by the removal of  
thetopcover, frontinspectionpanelandwarmerbase  
plate.  
Thetopcoverisattachedwithfour#6-32 screws.  
The front inspection panel is attached with five  
#6-32 screws.  
The warmer base is attached with four #6-32  
screws.  
Contents  
Brewer Selector Switch....................................... 16  
Bypass Valve ...................................................... 15  
Contactor Assembly............................................ 18  
Control Thermostat............................................. 20  
Digital Brewer Control (DBC) .............................. 22  
Dispense Valve ................................................... 21  
Level Control Board and Level Probe.................. 25  
Limit Thermostat ................................................ 27  
ON/OFF Switch (Warmer) ................................... 28  
Overflow Protection Switch ................................ 29  
Solenoid (Refill).................................................. 30  
Start Switch (Brew) ............................................ 32  
Tank Heater ........................................................ 33  
Timer (Early Models) .......................................... 34  
Digital Timer (Late Models) ................................ 35  
Triac/Heat Sink ................................................... 24  
Warmer Element ................................................. 37  
Wiring Diagrams................................................. 38  
P1095.40  
FIG. 1 COMPONENT ACCESS  
27362 092900  
Page 14  
SERVICE (cont.)  
BYPASS VALVE  
4. Disconnect the white/green wire and white/violet  
wire. Check for continuity across the bypass valve  
coil terminals.  
If continuity is present as described, reconnect the  
white/green and white/violet wires to the bypass valve  
and proceed to #5.  
If continuity is not present as described, replace the  
bypass valve.  
CK  
LO  
CK  
LO  
T
SE  
S E T  
2
J
1
5. Check the bypass valve for coil action. Connect  
brewer to the power source. With the "ON/OFF  
(Warmer)"switchinthe"ON"(upper)positionpress  
the start switch. Listen carefully in the vicinity of  
the bypass valve for a "clicking" sound as the coil  
attracts and repels the plunger.  
1
L
T
2
L
T
3
L
T
4
L
T
5
L
T
O
g
u  
g
e
0
50  
0  
p
.0  
l
00  
r
3
)
pe  
22  
00  
0)  
o
#
.05  
a
ro  
6
52  
ig  
ps  
nt  
o
20  
C
#
0
0
low  
er  
00  
h
F
r/  
s
2
1.  
a
7
23  
ne  
W
ai  
w
#
r  
lo  
F
e
n
l.  
re  
ep  
Sc  
(R  
pl.  
e
(R  
If the sound is heard as described, there may be a  
blockage in the water line before the bypass valve or  
the bypass valve may require inspection for wear and  
removal of waterborne particles.  
R
E
WAT  
T
O
H
N
O
TI  
AU  
C
!
If the sound is not heard as described, replace the  
bypass valve.  
P2231.35  
FIG. 2 BYPASS VALVE  
Removal and Replacement:  
Location:  
1. Remove the wires from the bypass valve.  
2. Drain enough water from the tank so bypass valve  
is above the water line.  
The bypass valve is located inside the hood on the  
left side just in front of the tank.  
3. Remove water lines from valve.  
4. Removetwonutsretainingbypassvalveinsidethe  
hood and remove bypass valve.  
5. Install new bypass valve.  
6. Reconnect the water tubes and the wires to the  
bypass valve.  
Test Procedures:  
1. Disconnect the brewer from the power source.  
2. With a voltmeter, check the voltage across the  
white/green wire and the white/violet wire on the  
bypass valve. Connect the brewer to the power  
source. With the "ON/OFF (Warmer)" switch in the  
"ON" (upper) position, and the selector switch in  
the 1-1/2 or 2 gallon position press the start  
switch. The indication must be:  
7. Refer to FIG. 3 when reconnecting the wires.  
WHI/VIO to Brew Selector Switch  
WHI/GRN to Dispense Valve  
a.) 120 volts ac for three wire 120/208 volt models  
and three wire 120/240 volt models.  
b.) 200 to 240 volts ac for two wire 200 or 240 volt  
models.  
3. Disconnect the brewer from the power source.  
If voltage is present as described, proceed to #4.  
If voltage is not present as described refer to the  
Wiring Diagrams and check the brewer wiring har-  
ness.  
P1096  
FIG. 3 BYPASS VALVE TERMINALS  
27362 092900  
Page 15  
5. Reattach the connector to the brew timer circuit  
board or DBC connector.  
SERVICE (cont.)  
BREW SELECTOR SWITCH  
Grinder Interface:  
6. Disconnectpink,grayandtanwiresontheselector  
switch from the pink, gray and tan wires on the  
interface socket.  
7. Check for continuity across the pink wire and the  
tan wire on the selector switch when the switch is  
in the 1 gallon position. Continuity must not be  
present in any other position.  
8. Check for continuity across the pink wire and gray  
wire on the selector switch when the switch is in  
the 1-1/2 gallon position. Continuity must not be  
present in any other position.  
9. Reconnect the pink, gray and tan wires on the  
selector switch to the pink, gray and tan wires on  
the interface socket.  
Bypass Valve:  
10. Disconnect the white/violet wire on the selector  
switch from the bypass valve coil and disconnect  
the white/red wire from the dispense valve coil.  
11. Check for continuity across the white/violet wire  
and white/red wire when the selector is in the 1-1/  
2 gallon and 2 gallon position. Continuity must not  
be present in any other position.  
12. Reconnect the white/violet wire to the bypass  
valve coil and the white/red wire to the dispense  
valve coil.  
P1097.40  
FIG. 4 BREW SELECTOR SWITCH  
Location:  
The brew selector switch is located in the front of  
the hood on the lower right side on DBC models and to  
the right of center on electro/mechanical models.  
If continuity is as described the switch is operating  
properly.  
Ifcontinuityisnotpresentasdescribedreplaceswitch  
assembly.  
Test Procedure:  
Timer or DBC  
Removal and Replacement:  
1. Disconnect the brewer from the power supply.  
2. Separate the connector on the selector switch  
harness from the brew timer circuit board or DBC  
connector.  
3. Check for continuity across the pink and tan wires  
on the connector when the switch is in the 1 gallon  
position. Continuity must not be present in any  
other position.  
1. Disconnect the connector on the selector switch  
harness from the brewer timer circuit board.  
2. Disconnect wires from the selector switch, inter-  
face socket, dispense valve and bypass valve.  
3. Loosen the set screw on the switch knob.  
4. Remove the 9/16" nut and washer holding the  
switch to the hood.  
5. Remove the switch.  
4. Check for continuity across the pink wire and the  
gray wire when the switch is in the 1-1/2 gallon  
position. Continuity must not be present in any  
other switch position.  
6. Installthenewswitch. Thepositioningtabmustbe  
in the hole in the hood for proper switch and knob  
alignment.  
27362 092996  
Page 16  
SERVICE (cont.)  
BREW SELECTOR SWITCH (cont.)  
8. Reattach the connector to the brew timer circuit  
board or DBC  
9. Refer to Fig. 5 when reconnecting the wires.  
7. Install the knob so that the arrow lines up in the 2  
gallonpositionwhentheswitchisturnedtothefull  
right position.  
WHI/VIO to By-Pass Valve  
WHI/RED to Dispense Valve  
To Timer (Electro/mechanical Models)  
TAN  
GRY to GRY Lead on Interface  
Socket  
PNK to PNK Lead on Interface  
Socket  
GRY  
PNK  
TAN to TAN Lead on Interface  
Socket  
ELECTRO/MECHANICAL  
P1105.75  
WHI/VIO to By-Pass Valve  
WHI/RED to Dispense Valve  
To DBC Board (Digital Brewer Controlled Models)  
PNK  
TAN  
GRY to GRY Lead on Interface  
Socket  
GRY  
PNK to PNK Lead on Interface  
Socket  
TAN to TAN Lead on Interface  
Socket  
DIGITAL CONTROL (DBC)  
FIG. 5 BREW SELECTOR SWITCH TERMINALS  
Page 17  
P1112.75  
27362 092996  
SERVICE (cont.)  
b.) 200 to 240 volts ac for two wire 200 or 240 volt  
models.  
CONTACTOR ASSEMBLY (ELECTRO/MECHANICAL  
ONLY)  
5. Disconnect the brewer from the power source.  
If voltage is present as described, proceed to #6.  
If voltage is not present as described, refer to the  
Wiring Diagrams and check the brewer wiring har-  
ness.  
6. Check for continuity between the two black wires  
of the contactor coil.  
K  
LO  
CK  
LO  
T
SE  
T
S E  
J2  
1
J
If continuity is present as described, reconnect one  
black wire to the white wire or red wire from the  
terminal block and the other black wire to the black  
wire from the control thermostat. Reinstall capillary  
tube into tank to line 7" above the bulb and proceed to  
#7.  
1
L
2
L
T
3
L
T
4
L
T
5
L
T
ressure  
F
.
5
0
0
g
p
m
operating  
ax  
N
ntrol  
#
22300.0500  
20526.0500)  
90 psig  
m
er  
#
.0000)  
sh  
If continuity is not present as described, replace the  
contactor.  
Wa  
Strainer/Flow Co  
(Repl. Flow  
(Repl. Screen #23721  
7. Withavoltmeter,carefullycheckthevoltageacross  
the red and black wires on L1 and L2. The indica-  
tion must be:  
R
WATE  
T
O
H
N
O
AUTI  
C
!
a.) 208voltsacforthreewire120/208voltmodels  
and 240 volts ac for three wire 120/240 volt  
models.  
b.) 200 to 240 volts ac for two wire 200 or 240 volt  
models.  
P2231.35  
FIG. 6 CONTACTOR ASSEMBLY  
Location:  
The contactor assembly is located inside the hood  
to the right of the overflow cup.  
8. Disconnect the brewer from the power source.  
Test Procedures:  
Mechanical Thermostat  
If voltage is present as described, proceed to #9.  
If voltage is not present as described, refer to the  
Wiring Diagrams and check the brewer wiring har-  
ness.  
1. Disconnect the brewer from the power source.  
2. Disconnect the white wire or the red wire and the  
black wire of the contactor coil and disconnect the  
black wire of the control thermostat from the  
remaining black wire of the contactor coil.  
3. Gently remove the capillary bulb and grommet  
from the tank.  
9. Check for continuity across the terminals on the  
left side of the contactor by manually closing the  
contacts. Continuitymustnotbepresentwhenthe  
contact is released.  
4. With a voltmeter, check the voltage across the  
white wire from the terminal block on 120/208,  
120/240 volt units or the red wire from 200, 240  
volt units and the black wire from the control  
thermostat when the thermostat is turned clock-  
wisetothe"FULLON"position.Connectthebrewer  
to the power source. The indication must be:  
a.)120voltsacfor threewire120/208voltmodels  
and three wire 120/240 volt models.  
10. Check for continuity across the terminals on the  
right side of the contactor by manually closing the  
contacts. Continuitymustnotbepresentwhenthe  
contact is released.  
If continuity is present as described, the contactor is  
operating properly.  
If continuity is not present as described, replace the  
contactor.  
27362 092900  
Page 18  
SERVICE (cont.)  
CONTACTOR ASSEMBLY (ELECTRO/MECHANICAL  
ONLY) (cont.)  
Removal and Replacement:  
1. Remove all wires from the contactor.  
2. Removethetwo#10-32 screws securingcontactor  
to the inside of the hood.  
3. Securely install the new contactor inside the hood.  
4. Refer to Fig. 7 when reconnecting the wires.  
RED L1 to Terminal  
Block (Red Insert)  
BLK T2 to Tank Heater  
BLK L2 to Limit Ther-  
mostat  
RED T1 to Tank Heater  
BLK to WHI Lead from the  
Three Pole 120/208V or 120/  
240V Terminal Block  
BLK to RED Lead from the  
Two Pole 200V or 240V Ter-  
minal Block  
BLK to BLK Lead from Thermostat  
MECHANICAL THERMOSTAT ONLY  
P1113  
FIG.7CONTACTORASSEMBLYTERMINALS  
27362 092900  
Page 19  
SERVICE (cont.)  
CONTROL THERMOSTAT (ELECTRO/MECHANICAL  
ONLY)  
b.) 200 to 240 volts ac for two wire 200 or 240 volt  
models.  
Voltage must not be indicated across these termi-  
nals when the thermostat is turned "OFF" (fully  
counterclockwise).  
6. Disconnect the brewer from the power source.  
K  
L
CK  
LO  
T
SE  
E T  
S
1
L
T
2
L
T
3
L
T
4
L
T
Ifvoltageispresentasdescribed,reinstallthecapillary  
tube into the tank to the line 7" above the bulb, the  
control thermostat is operating properly.  
If voltage is not present as described, replace the  
thermostat.  
5
L
T
re  
.0  
.0  
g
e
0
50  
pr  
n  
l
00  
3
0)  
pe  
22  
50  
x
o
#
a
ro  
6
52  
m
nt  
ps  
C
#
20  
0
0)  
00  
o
w
er  
Flo  
h
1.  
/
as  
2
er  
W
37  
in  
ra  
low  
pl.  
#
2
F
e
n
re  
l.  
ep  
Sc  
(R  
e
(R  
Removal and Replacement:  
1. Remove wires from the control thermostat.  
2. Remove the thermostat capillary bulb by firmly  
pulling up on the capillary tube on top of the tank  
lid. This will disengage the grommet from tank lid.  
3. Remove the #8-32 screw holding the control ther-  
mostat to the component bracket.  
P2231.30  
FIG. 8 CONTROL THERMOSTAT  
Location:  
The control thermostat is located inside the front  
of the brewer in the center of the component bracket.  
4. Slide the grommet to the line 7" above the bulb on  
the new capillary tube.  
5. Insert the capillary bulb through the hole in the  
tank lid and press the grommet firmly and evenly  
so that the groove in the grommet fits into the tank  
lid.  
6. Carefully bend the capillary tube so that the tube  
andbulbinsidethetankareintheverticalposition.  
NOTE - The capillary tube must be clear of any electri-  
cal termination and not kinked.  
7. Using a #8-32 screw, fasten the control thermo-  
stat to the component bracket.  
Test Procedures:  
1. Disconnect the brewer from the power source.  
2. Withavoltmeter,checkthevoltageacrosstheblue  
wires on the control thermostat and the white  
insert on the three pole 120/208V, 120/240V ter-  
minal block or the red insert on two pole 240V  
terminal block. Connect the brewer to the power  
source. The indication must be:  
a.) 120 volts ac for three wire 120/208 volt models  
and three wire 120/240 volt models.  
b.) 200 to 240 volts ac for two wire 200 or 240 volt  
models.  
8. Refer to Fig. 9 when reconnecting the wires.  
9. Adjust the control thermostat as required.  
3. Disconnect the brewer from the power source.  
If voltage is present as described, proceed to #4.  
If voltage is not present as described, refer to the  
Wiring Diagrams and check the brewer wiring har-  
ness.  
4. Gently remove the capillary bulb and grommet  
from the tank.  
BLU to Ready Light  
BLU to RED Lead from Overflow  
Protection Switch  
BLK to BLK Lead on Contactor Coil  
BLK to Ready Light  
5. With a voltmeter, check the voltage across the  
blackwiresofthecontrolthermostatandthewhite  
insert on the three pole 120/208V or 120/240V  
terminal blocks and the red insert on two pole  
200V/240V terminal blocks when the control ther-  
mostat is turned "ON" (fully clockwise). Connect  
the brewer to the power source. The indication  
must be:  
P1098  
a.) 120 volts ac for three wire 120/208 volt models  
and three wire 120/240 volt models.  
FIG. 9 CONTROL THERMOSTAT TERMINALS  
27362 092900  
Page 20  
SERVICE (cont.)  
DISPENSE VALVE  
5. Check the dispense valve for coil action. Connect  
the brewer to power source. Place the "ON/OFF  
(Warmer)" switch in the "ON" (upper) position,  
press and release the start switch. Listen carefully  
in the vicinity of the dispense valve for a "clicking"  
sound as the coil magnet attracts and repels the  
plunger.  
6. Disconnect the brewer from the power source.  
CK  
LO  
CK  
O
L
SET  
S E T  
If the sound is heard as described, there may be a  
blockage in the dispense valve or the water line to the  
dispense valve. Remove the dispense valve and in-  
spect for wear, and remove waterborne particles.  
If the sound is not heard as described, replace the  
dispense valve.  
2  
1
1
L
T
2
L
T
3
L
T
4
L
T
5
L
T
re  
.0  
)
00  
05  
g
su  
s  
0
50  
00  
r  
tin  
00  
3
pe  
22  
N
x
o
#
P2231.35  
Removal and Replacement:  
FIG. 10 DISPENSE VALVE  
1. Disconnect wires from dispense valve.  
2. Drain enough water from the tank so the dispense  
valve is above the water line.  
3. Remove water lines and hose barb fitting from  
dispense valve.  
4. Removedispensevalvefromthesprayheadpanel.  
5. Install new dispense valve .  
6. Reconnect the water lines, hose barb fitting and  
the wires to the dispense valve.  
Location:  
Dispense valve is located inside the hood directly  
above the sprayhead.  
Test Procedures:  
1. Disconnect the brewer from the power source.  
2. Disconnect the wires from the dispense valve and  
check for continuity across the dispense valve coil  
terminals.  
If continuity is present as described, reconnect the  
wires to the dispense valve and proceed to #3.  
If continuity is not present as described, replace the  
dispense valve.  
7. Refer to Fig. 11 when reconnecting wires.  
WHI/VIO to Timer TL1  
WHI/VIO to ON/OFF Switch  
WHI/RED to Brew Selector Switch  
3. With a voltmeter, check the voltage across dis-  
pense valve using the white/violet wire and white/  
greenwireonelectro/mechanicalmodels,orwhite/  
red wire and white/green wire on DBC models.  
Connect brewer to the power source. Place the  
"ON/OFF (Warmer)" switch in the "ON" (upper)  
position. Press and release the start switch. The  
indication must be:  
WHI/GRN to Timer TL4  
WHI/GRN to By-Pass Valve  
ELECTROMECHANICAL  
WHI/RED to DBC Board J1-2  
WHI/RED to Brew Selector Switch  
a.) 120 volts ac for three wire 120/208 volt models  
and three wire 120/240 volt models.  
b.) 200 to 240 volts ac for two wire 200 or 240 volt  
models.  
WHI/GRN to Bypass Valve  
WHI to DBC J1-3 (120/208 or 120/240 Volt  
Models  
RED to DBC J1-3 (200 or 240 Volt Models)  
4. Disconnect brewer from the power source.  
If voltage is present as described in step 3, proceed to  
#5.  
DIGITAL CONTROL (DBC)  
P1106  
If voltage is not present as described, refer to the  
Wiring Diagrams and check the brewer wiring har-  
ness.  
FIG.11DISPENSEVALVETERMINALS  
27362 092900  
Page 21  
SERVICE (cont.)  
DIGITAL BREWER CONTROL BOARD AND DISPLAY  
(DBC)  
the following functions are set properly.  
A) set refill probe delay (larger values add more  
delay time)  
B) refill sensing probe ("no" means that there will  
be no automatic refill)  
C) refill solenoid separate from brew solenoid  
(usually on gravity brewers) ("no" means that refill  
will occur automatically only when not brewing.  
D) set refill resistance threshold (only necessary  
to change in pure water areas)(changing the set-  
tingtoavaluehigherthan128meansthewaterwill  
be more likely to create a full condition).  
E) check wiring to refill solenoid  
F) replace Digital Brewer Control Board  
3. If the brewer will not heat then check the follow-  
ing.  
A) test the main tank heater  
B) check the main brew tank temperature setting  
C) check dry plug-in prevention probe setting  
("yes" means that there must be a dry plug-in  
prevention probe)  
D) limit thermostat on top of the brewer tank  
E) temporarily substitute a known working heater  
triac assembly  
P1094.35  
FIG. 12 DIGITAL CONTROL BOARD  
Location  
The digital control board is located inside the  
upper front of the trunk on the component bracket.  
The digital display is located in the upper center of  
the front of hood.  
F) replace Digital Brewer Control Board  
NOTE: Check the function list (supplied) for FUNC-  
TION, ENTRY AND DESCRIPTION.  
4. If the brewer will not brew then use the function  
list and test the brew solenoid and make sure that  
the following functions are set properly.  
A) set main brew tank temperature ( a setting that  
is lower than the ready lamp value can prevent  
brewing)  
1. If display indicates a "FAULT" use the list below to  
troubleshoot the indicated fault.  
FAULT 1 - main brew tank temperature probe is  
shorted  
FAULT 2 - main brew tank temperature probe is  
open circuit  
FAULT 3 - secondary water tank temperature  
probe is shorted (used only in two-tank system)  
FAULT 4 - secondary water tank temperature  
probe is open circuit (used only in two-tank sys-  
tem)  
FAULT 5 - main DBC board is defective  
FAULT 6 - water overflow protection switch is  
open circuit  
B)setmainbrewtank-readylampofftemperature  
(a setting that is higher than the brew value can  
prevent brewing)  
C) select brew lockout ("yes" requires the brewer  
ready lamp to be "ON" in order to brew)  
D) replace Digital Brewer Control Board  
5. If the temperature reading on the display is higher  
than 211˚F (99˚C), disconnect the two pin connec-  
tor (blue wire and tan wire) from the heater triac.  
If the heater remains on, the heater triac is defec-  
tive and must be replaced.  
FAULT 7 - dry plug-in condition (brewer is look-  
ing for connection between the water tank and the  
dry plug-in probe.  
B)  
6. Ifthetemperatureondisplayvariesbymorethan  
one degree while the brewer is at idle, select main  
2. If the brewer will not refill then use the function  
list and test the refill solenoid and make sure that  
27362 092996  
Page 22  
SERVICE (cont.)  
DIGITAL BREWER CONTROL BOARD AND DISPLAY  
(DBC) (cont.)  
brewer from the power source, wait 15 seconds  
and reconnect the brewer to the power source.  
D) If these do not remedy the problem, replace  
Digital Brewer Control Board  
heater relay or triac. ("0" means the temperature  
will be allowed to vary by the value in "set relay  
temperature difference")  
10. If water is running outfrom the base of the brewer  
check the following:  
7. If you cannot access the DBC with the password  
youhaveentered,thepasswordhasbeenchanged.  
If you know what the brew settings are you can  
"reset" the memory back to the way it left the  
factory, which is "0". This is accomplished by  
disconnecting the brewer from the power source,  
pressing the plus (+) and minus (-) buttons simul-  
taneously and holding them in this position then  
connecting the brewer to the power source. Con-  
tinue pressing the buttons until the display shows  
numbers counting upward rapidly. If this does not  
occur press the plus (+) and minus(-) firmly and  
repeat the procedure. The brew values can now be  
set to your desired value.  
A) If the display shows temperature or FAULT 6 ,  
disconnect the brewer from the power source. If  
water continues to flow out of the base of the  
brewer there may be an obstruction in the refill  
solenoid valve. Refer to Refill Solenoid Valve ser-  
vice procedures.  
B) With the brewer disconnected from the power  
source, remove panels as necessary, dry inside of  
brewer as needed, and reinstall panels on brewer.  
C) Reconnectbrewertothepowersupply. Ifwater  
continues to flow out of the base, the Digital  
Brewer Control Board is defective and must be  
replaced.  
8. If the brew volume does not match the pro-  
grammed value then use the following list to  
correct the error.  
Removal and Replacement:  
DBC Control Board  
1. Disconnect the brewer from the power source.  
2. Disconnect all wires from the control board.  
3. Remove the two #8-32 keps nuts securing control  
board to component bracket inside the trunk.  
4. Remove control board and discard,  
5. Installnewcontrolboardonthecomponent bracket  
using two #8-32 keps nuts.  
A) The coffee grounds naturally absorb some of  
the brew water; typically between one and two  
ouncesofwaterperounceofcoffee(dependingon  
the grind).  
B)TheDBCcalculatestheamountoftimethebrew  
solenoidmuststayontodispensetheprogrammed  
brew volume. It uses the sprayhead constant to  
determinetherateofdispense.Thesprayheadrate  
can be measured by capturing the water coming  
out of the sprayhead for 60 seconds. This value (in  
gallons per minute) can be entered into memory.  
C) The last reason can be the brew by-pass. If you  
are using brew by-pass then the amount that  
comesoutoftheby-passmustbesubtractedfrom  
the total desired volume to get the programmed  
brew volume.  
6. Reconnectthemulti-pinplugstothecontrolboard.  
DBC Display Assembly:  
1. Disconnect the display assembly cord from the  
display assembly.  
2. Remove the two #6-32 locking screws securing  
the display assembly to the display assembly  
mounting bracket behind the front of the hood.  
3. Remove display assembly from the front of the  
hood and discard.  
4. Install new display assembly on the front of the  
hood using two #6-32 locking screws to secure it  
to the display assembly mounting bracket.  
5. Reconnect the display assembly cord to the dis-  
play assembly.  
9. IfyourDBCdisplayisblank, youshouldcheckthe  
following.  
A) Make sure brewer is connected to the power  
source.  
B)Makesureconnectorsthatgobetweenthemain  
DBC and the DBC display are plugged into their  
appropriate locations.  
NOTE: If necessary recalibrate the values of the  
DBC using the FUNCTION LIST (supplied).  
C) Restart the DBC program by disconnecting  
27362 092900  
Page 23  
SERVICE (cont.)  
6. Apply heat sink compound and secure new triac  
assembly on rear of the heat sink with one #6-32  
screw.  
TRIAC/HEAT SINK ASSEMBLY (DBC ONLY)  
7. Route the triac wires through the tank support  
channel.  
8. Secure triac/heat sink assembly to the lower rear  
of the brewer with two #6-32 screws.  
9. Reconnect the wires of the new triac assembly.  
Refer to Fig. 14 when reconnecting wires.  
WHI/VIO to Terminal Block (Red Insert)  
BLU to Tank Heater  
BLU to DBC Board J1-17  
TAN to DBC Board J1-16  
P1099  
FIG. 14 TRIAC/HEAT SINK TERMINALS  
P1094.35  
FIG. 13 TRIAC/HEAT SINK  
Location  
The triac/heat sink is located on the lower rear of  
the brewer.  
Removal and Replacement  
NOTE - each triac installation requires the use of an  
approved silicone heat sink compound. Bunn-O-  
Matic recommends the use of Dow Corning 340 com-  
pound or equivalent. It can be purchased direct from  
Bunn-O-Matic (part number M2522.1000).  
1. Place the tank heater switch on the DBC board  
assembly in the OFFposition.  
2. Disconnect triac wires, white/violet from terminal  
block, bluefrom tankheater, blueandtanfromthe  
DBC board assembly.  
3. Remove the two #6-32 screws securing the triac/  
heat sink assembly to the lower rear of the brewer.  
4. Remove heat sink, triac and triac leads as an  
assembly.  
5. Remove the one #6-32 screw securing triac to the  
heat sink and discard triac with leads.  
27362 092996  
Page 24  
SERVICE (cont.)  
6. Carefully connect a piece of insulated jumper wire  
to terminal 4. Keep the other end of this wire away  
from any metal surface of the brewer.  
LEVELCONTROLBOARDANDLEVELPROBE(Electro/  
mechanical only)  
7. With a voltmeter, check the voltage across termi-  
nals 1 & 3. Connect the brewer to the power  
source. The indication must be:  
a.)120voltsacfor threewire120/208voltmodels  
and three wire 120/240 volt models after a delay of  
approximately 1 second.  
b.) 200 to 240 volts ac for two wire 200 or 240 volt  
models after a delay of approximately 1 second.  
8. Touch the free end of jumper wire to the brewer  
housing. The indication must be 0.  
CK  
LO  
OK  
SET  
L
T
E
S
2
J
1
L
T
2
L
T
3
L
T
L4  
T
5
L
T
9. Move the jumper wire away from the brewer  
housing. The indication must again be:  
e
F
u
s  
e  
a.)120 volts ac for three wire 120/208 volt models  
and three wire 120/240 volt models after a delay of  
approximately 1 second.  
00  
0
0
.05  
p
atin  
0
23  
)
er  
2
50  
x
l
#
.0  
a
o
6
N
m
ntr  
52  
g  
C
#
20  
o
p
w
r
0
0
0)  
0  
lo  
er/F  
he  
a
s
2
1.0  
37  
in  
W
tra  
low  
#
2
S
F
e
n
re  
Sc  
l.  
ep  
(R  
e
pl.  
(R  
b.) 200 to 240 volts ac for two wire 200 or 240 volt  
models after a delay of approximately 1 second.  
10. Disconnect the brewer from the power source and  
remove the jumper wire from terminal 4.  
R
E
T
A
W
T
O
H
N
IO  
T
U
A
C
!
P2231.30  
FIG. 15 LIQUID LEVEL CONTROL  
BOARD AND PROBE  
If voltage is present as described, the level control  
board is operating properly, proceed to #11.  
If voltage is not present as described, replace the level  
control board.  
Location:  
The level control board is located inside the front  
of the brewer on the lower left side of the component  
bracket. The level probe is located inside the hood on  
the left center rear of the tank lid next to the limit  
thermostat.  
11. Reconnect the pink wire to terminal 4.  
12. Gently pull the probe out of the tank lid and inspect  
for corrosion. Replace it if necessary.  
13. Place the probe so that neither end is in contact  
with any metal surface of the brewer.  
14. With a voltmeter, check the voltage across termi-  
nals 1 & 3. Connect the brewer to the power  
source. The indication must be:  
Test Procedure:  
1. Disconnect the brewer from the power source.  
2. Removethevioletwirefromterminal1&pinkwire  
from terminal 4 of the circuit board.  
3. With a voltmeter, check the voltage across termi-  
nals 2 & 3. Connect the brewer to the power  
source. The indication must be:  
a.) 120 volts ac for three wire 120/208 volt mod-  
els and three wire 120/240 volt models after a  
delay of approximately 1 second.  
a.) 120 volts ac for three wire 120/208 volt models  
and three wire 120/240 volt models.  
b.) 200 to 240 volts ac for two wire 200 or 240 volt  
models.  
b.) 200to240voltsacfortwowire200or240volt  
models after a delay of approximately 1 second.  
15. Move the probe's flat end to the brewer housing.  
The indication must be 0.  
4. Disconnect the brewer from the power source.  
16. Move the probe's flat end away from the brewer  
housing. The indication should be:  
If voltage is present as described, proceed to #5.  
If voltage is not present as described, refer to the  
Wiring Diagrams and check the brewer wiring har-  
ness.  
a.)120 volts ac for three wire 120/208 volt models  
and three wire 120/240 volt models after a delay of  
approximately 1 second.  
5. Reconnect the violet wire to terminal 1.  
27362 092996  
Page 25  
SERVICE (cont.)  
LEVELCONTROLBOARDANDLEVELPROBE(Electro/  
mechanical only)(cont.)  
b.) 200 to 240 volts ac for two wire 200 or 240 volt  
models after a delay of approximately 1 second.  
17. Disconnect the brewer from the power source.  
If voltage is present as described, reinstall the probe,  
the level control board and level probe are operating  
properly.  
If voltage is not present as described, check the pink  
probe wire for continuity. If no continuity is present,  
replace or repair pink wire.  
Removal and Replacement:  
1. Remove all wires from the level control board.  
2. Remove two #8-32 screws and lockwashers hold-  
ing level control board to component bracket.  
3. Install the new level control board to the compo-  
nent bracket. Make certain that the lockwashers  
are between the level control board and the com-  
ponent bracket.  
4. Refer to Fig. 16 when reconnecting the wires.  
T4 PNK to Probe  
T3 WHI to Terminal Block (WHI  
Insert on 120/208 or 120/240V  
Brewers)  
T3 RED to Terminal Block (RED  
Insert on 200V or 240V brewers)  
T2 BLU from Overflow Protection  
Switch  
T1 VIO to Solenoid Coil  
P1100  
FIG. 16 LIQUID LEVEL CONTROL BOARD  
TERMINALS  
27362 092900  
Page 26  
SERVICE (cont.)  
LIMIT THERMOSTAT  
Removal and Replacement  
1. Remove all wires from the limit thermostat termi-  
nals.  
2. Carefully remove the two #8-32 nuts securing the  
limit thermostat to tank lid and remove limit ther-  
mostat.  
3. Carefully secure new limit thermostat to tank lid.  
4. Refer to Fig. 18 when reconnecting the wires.  
CK  
LO  
CK  
LO  
T
SE  
T
S E  
1
J
1
L
T
2
L
T
3
L
T
4
L
T
5
L
T
BLK to Tank Heater  
BLK to Terminal Block  
(Black Insert)  
e  
m
es  
0
50  
.0  
t
l
00  
ra  
3
)
pe  
22  
00  
0)  
N
x
o
#
.05  
a
ro  
6
52  
m
nt  
g  
C
#2  
0
o
0
0
low  
er  
00  
h
F
s
2
1.  
r/  
a
7
23  
ne  
W
ai  
w
#
tr  
lo  
F
e
n
l.  
re  
ep  
Sc  
(R  
pl.  
e
(R  
P833  
FIG. 18LIMITTHERMOSTATTERMINALS  
R
E
T
A
W
T
O
H
N
IO  
T
U
A
C
!
P2231.35  
FIG. 17 LIMIT THERMOSTAT  
Location:  
The limit thermostat is located inside the hood on  
the tank lid to the left of the tank heater.  
Test Procedure:  
1. Disconnect the brewer from the power supply.  
2. Disconnect both black wires from the limit ther-  
mostat.  
3. Withanohmmeter,checkforcontinuityacrossthe  
limit thermostat terminals.  
If continuity is present as described, reconnect the  
black wires to the limit thermostat , the limit thermo-  
stat is operating properly.  
If continuity is not present as described, press the  
reset button on the limit thermostat and repeat step  
#3.  
After repeating step #3 and no continuity is shown,  
replace the limit thermostat.  
27362 092900  
Page 27  
SERVICE (cont.)  
ON/OFF (Warmer) SWITCH  
If voltage is not present as described, refer to the  
Wiring Diagrams and check the brewer wiring har-  
ness.  
5. With the black wire removed, remove the white/  
violetwireorwhite/redwireontheswitchfromthe  
lower left terminal.  
6. Check for continuity across the center and lower  
left terminal with switch in the "ON" (upper) posi-  
tion. Continuity must not be present when switch  
is in the "OFF" (lower) position.  
If continuity is present as described, reconnect the  
black wire to the center terminal and the white/violet  
wire or white/red wire on the switch to the lower left  
terminal.  
If continuity is not present as described, replace the  
switch.  
Removal and Installation:  
1. Remove the wires from the switch terminals.  
2. Compress the clips inside the hood and gently  
push the switch through the opening.  
3. Push the new switch into the opening and spread  
the clips to hold switch in the hood.  
4. Refer to Fig. 20 when reconnecting the wires.  
P1101.40  
FIG. 19 ON/OFF SWITCH  
Location:  
The ON/OFF (Warmer) switch is located on the  
front of the hood to the right of the start switch.  
WHI to Terminal Block (WHI  
Insert) or  
WHI to DBC J1-6 (120/208V  
Models)  
RED to Terminal Block (RED  
Insert) or  
Test Procedure:  
BLK to Terminal Block  
(Black Insert)  
1. Disconnect the brewer from the power source.  
2. Viewing the switch from the back remove the red  
or whitewirefromtheupperrightterminal andthe  
black wire from the center terminal.  
3. With a voltmeter, check the voltage across the red  
or white wire and the black wire. Connect the  
brewer to the power source. The indication must  
be:  
RED to DBC J1-6 (200V -  
WHI/VIO to Timer TL1  
240V Models)  
(Electro/mechanical)or  
WHI/RED to DBC Board  
J1-1  
P1102  
FIG. 20 ON/OFF SWITCH TERMINALS  
a.)120voltsacfor threewire120/208voltmodels  
and three wire 120/240 volt models.  
b.) 200 to 240 volts ac for two wire 200 or 240 volt  
models.  
4. Disconnect the brewer from the power source.  
Ifvoltageispresentasdescribed,reconnectthe red or  
white wire, and proceed to #5.  
27362 092900  
Page 28  
Removal and Replacement:  
SERVICE (cont.)  
1. Disconnect the red leads from the overflow pro-  
tection switch from the black wire from the termi-  
nalblockorDBCboardassemblyandtheblue wire  
from the thermostat or red wire from DBC board  
assembly.  
OVERFLOW PROTECTION SWITCH  
2. Remove the nut beneath the copper overflow cup.  
3. Remove the entire switch assembly from the cup.  
4. Place the new switch assembly into the cup, wires  
first. Make sure that a gasket is in place around the  
threaded switch stem.  
L
CK  
LO  
SE  
T
S E  
J2  
1
L
T
2
L
T
3
L
T
4
L
T
5
L
T
NOTE - The magnets must be at the top of float and  
there must be NO adjusting washers installed for  
the overflow protection switch to operate prop-  
erly.  
5. Installthenutbeneaththecopperoverflowcup. Be  
sure not to overtighten.  
L
r
F
g
su  
s  
0
50  
r  
.5  
.0  
tin  
l
00  
ra  
3
)
pe  
22  
00  
)
x
o
#
.05  
a
ro  
6
52  
m
nt  
s
p
C
#
20  
00  
o
1
.
00  
ow  
er  
l
h
F
r/  
a
72  
23  
ne  
W
ai  
w
#
t
lo  
F
e
n
l.  
re  
ep  
Sc  
R  
pl.  
e
(R  
6. Refer to Fig. 22 when reconnecting wires.  
P2231.35  
FIG. 21 OVERFLOW PROTECTION SWITCH  
Location:  
The overflow protection switch is located inside  
the hood on the tank inside the copper overflow cup.  
To test the overflow protection switch, access will  
alsobeneededtothelevelcontrolboardor DBC board  
assembly and terminal block.  
RED to BLK Wire from  
TerminalBlock(Electro/  
Mechanical)  
REDtoBLULeadfromTher-  
mostat (Electro/Mechani-  
cal)  
RED to BLK Wire from  
DBC Board J3-12  
RED to RED Wire from DBC  
Board J3-11  
Test Procedure:  
1. Disconnect the brewer from the power source.  
2. Remove the wire nuts connecting the red wires  
from the overflow protection switch to the black  
wire from the terminal block or DBC board assem-  
bly, and blue wire from the thermostat or the red  
wire from the DBC board assembly.  
P1103  
FIG. 22 OVERFLOW PROTECTION  
SWITCH TERMINALS  
3. Check for continuity across the overflow protec-  
tion switch red wires only until the plastic float is  
raised and check that continuity returns when the  
plastic float is again lowered.  
If continuity is present as described, reconnect the red  
wires to the black wire from the terminal block or DBC  
Board Assembly, and the blue wire from the thermo-  
stat or red wire from DBC board assembly.  
If continuity is not present as described, replace the  
overflow protection switch.  
27362 092996  
Page 29  
SERVICE (cont.)  
c.) Red and violet wires on 200 and 240V volt  
electro/mechanical controlled models.  
d.) Red and white/blue wires on 200 and 240 volt  
DBC models.  
SOLENOID VALVE (Refill)  
Connect the brewer to the power source. The indica-  
tion must be:  
CK  
LO  
T
SE  
S E T  
a.) 120 volts ac for three wire 120/208 volt mod-  
els and three wire 120/240 volt models.  
b.) 200to240voltsacfor twowire200or240volt  
models.  
J
1
L
T
2
L
T
3
L
T
4
L
T
5
L
T
4. Disconnect the brewer from the power source.  
If voltage is present as described, proceed to #5.  
If voltage is not present as described, refer to the  
Wiring Diagrams and check brewer wiring harness.  
re  
u  
es  
0
50  
0
r  
.
.0  
tn  
l
00  
ra  
3
)
pe  
22  
00  
0)  
x
#
.05  
a
ro  
6
52  
ig  
s  
m
nt  
o
0
C
#2  
0
0
low  
er  
00  
9  
h
F
s
2
1.  
r/  
a
7
23  
ne  
W
ai  
w
#
tr  
lo  
S
F
e
n
l.  
re  
ep  
Sc  
(R  
pl.  
e
(R  
R
E
T
A
W
T
O
5. Check the solenoid valve for coil action. Connect  
the brewer to the power source and draw water  
from the faucet. Listen carefully in the vicinity of  
the solenoid valve for a "clicking" sound after  
approximately 1 second, as the coil magnet at-  
tracts.  
H
N
IO  
T
U
A
C
!
P2231.35  
FIG. 23 REFILL SOLENOID VALVE  
6. Disconnect the brewer from the power source.  
Location:  
The inlet solenoid valve is located inside the trunk  
on top of the flow control bracket.  
If the sound is heard as described and water will not  
pass through the solenoid valve, there may be a  
blockage in the water line before or after the solenoid  
valve or, the solenoid valve may require inspection for  
wear, and removal of waterborne particles.  
If the sound is not heard as described, replace the  
solenoid valve.  
Test Procedure:  
1. Disconnect the brewer from the power source.  
2. Disconnectbothwiresfromthesolenoidvalvecoil  
terminals and check for continuity across the  
solenoid valve coil terminals.  
Removal and Replacement:  
If continuity is present as described, reconnect the  
white and violet wires on the electro/mechanical con-  
trolled 120/208 and 120/240 volt brewers, white and  
white/blue on DBC 120/208 and 120/240 volt brew-  
ers, red and violet on electro/mechanical controlled  
200 or 240 volt brewers and red and white/blue on  
DBC 200 or 240 volt brewers.  
1. Remove all wires from the solenoid valve coil.  
2. Turn off the water supply to the brewer.  
3. Disconnect the water lines to and from the sole-  
noid valve.  
4. Disconnect water line from the flow control to the  
solenoid and remove.  
5. Remove the four #8-32 screws securing the flow  
control bracket to the support bracket and slide  
bracket and solenoid over flow control.  
6. Remove bracket and solenoid as an assembly.  
7. Remove the two #10-32 screws and lockwashers  
securing the solenoid valve to the flow control  
bracket.  
If continuity is not present as described, replace the  
solenoid valve.  
3. With a voltmeter, check the voltage across the  
solenoid valve terminal wires:  
a.) White and violet wires on 120/208 and 120/  
240 volt electro/mechanical controlled models.  
b.) White and white/blue wires on 120/208 and  
120/240 volt DBC models.  
8. Using two #10-32 screws securely install the new  
solenoid valve to the flow control bracket.  
27362 092900  
Page 30  
SERVICE (cont.)  
SOLENOID VALVE (Refill) (cont.)  
9. Slide flow control bracket and solenoid as an  
assembly over flow control and secure with four  
#8-32 screws to the support bracket.  
10. Securely fasten the water lines to and from the  
solenoid valve and flow control.  
11. Refer to Fig. 24 when reconnecting the wires.  
WHI to Level Control Board T3  
(120/208V, 120/240V Electro/Mechanical)  
or WHI to DBC Board J1-5  
RED to Level Control Board T3 (200 or 240V Electro/  
Mechanical) or RED to DBC Board J1-5 (200V or 240V)  
VIO to Level Control Board T1 (Electro/Mechanical)  
or WHI/BLU to DBC Board J1-23  
FIG. 24 REFILL SOLENOID TERMINALS P1107  
27362 092900  
Page 31  
SERVICE (cont.)  
START SWITCH  
Removal and Replacement:  
1. Remove all wires from the switch terminals.  
2. Compress the clips inside the hood and gently  
push the switch through the opening.  
3. Push the new switch into the opening and spread  
the clips to hold the switch in the hood.  
4. Refer to FIG. 26 when reconnecting the wires.  
WHI/ORN to Timer TL3 -  
(Electro/Mechanical) or  
BLK to DBC J3-6  
WHI/YEL to Timer TL5 -  
(Electro/Mechanical) or  
BLU to DBC J3-21  
P1108  
FIG. 26 START SWITCH TERMINALS  
P1104  
FIG. 25 START SWITCH  
Location:  
The start switch is located in front of hood to the  
left of the ON/OFF switch.  
Test Procedure:  
1. Disconnect the brewer from the power source and  
removethewiresfrombothterminalsoftheswitch.  
2. Check for continuity across the two terminals on  
the switch when it is held in the lower position.  
Continuity must not be present across these ter-  
minals in the upper position.  
If continuity is present as described, reconnect the  
wires, the switch is operating properly.  
If continuity is not present as described, replace the  
switch.  
27362 092900  
Page 32  
SERVICE (cont.)  
TANK HEATER  
If voltage is present as described, proceed to #4.  
If voltage is not present as described, refer to the  
Wiring Diagrams and check the wiring harness.  
4. Disconnect wires from the tank heater.  
5. Check for continuity across the terminals of the  
tank heater.  
If continuity is present as described, reconnect the  
wires, the tank heater is operating properly.  
If continuity is not present as described, replace the  
tank heater.  
K
C  
L
CK  
O
L
SET  
T
S E  
J
1
L
T
2
L
T
3
L
T
4
L
5
L
T
NOTE - If the tank heater remains unable to heat,  
removeandinspecttheheaterforcracksinthesheath.  
DBC Models:  
P2231.35  
FIG. 27 TANK HEATER  
1. Disconnect the brewer from the power source.  
2. Disconnect wires from heater.  
3. Check for continuity across the tank heater ter-  
minals.  
Location:  
The tank heater is located inside the hood on the  
right rear of the tank lid.  
If continuity is present as described, the tank heater is  
operating properly.  
If continuity is not present as described, replace the  
tank heater.  
NOTE - If the tank heater remains unable to heat,  
removeandinspecttheheaterforcracksinthesheath.  
Test Procedure:  
Electro/Mechanical Models.  
1. Disconnect the brewer from the power supply.  
2 With a voltmeter, check the voltage across the  
black and the red wire on the tank heater. With the  
control thermostat turned to the "ON" position  
(fully clockwise), connect the brewer to the power  
supplyandcheckthevoltageacrossthewires. The  
indication should be:  
Removal and Replacement:  
1. Remove wires from tank heater.  
2. Remove the four #8-32 nuts securing tank heater  
to tank lid.  
3. Remove tank heater and gasket.  
4. Install new tank heater and gasket with four #8-32  
nuts on tank lid.  
a.) 208 volts ac for three wire 120/208 volt models  
and 240 volts ac for three wire 120/240 volt  
models.  
b.) 200 to 240 volts ac for two wire 200 or 240 volt  
models.  
5. Refer to Fig. 28 when reconnecting the wires.  
3. Disconnect the brewer from the power supply.  
RED to Contactor T1  
BLU Lead from Triac Assembly  
BLK to Limit Thermostat  
BLK to Limit Thermostat  
ELECTRO/MECHANICAL  
DBC  
P837  
FIG. 28 TANK HEATER TERMINALS  
Page 33  
27362 092996  
tion. Select the 2 gallon batch setting. Connect the  
brewer to the power source and press the start  
switch. The indication must be:  
SERVICE (cont.)  
TIMER (ELECTRO/MECHANICAL ONLY)(EARLY  
MODELS)  
a.)120 volts ac for three wire 120/208 volt models  
and three wire 120/240 volt models for approxi-  
mately 1 minute 20 seconds for 2 gallon batch.  
b.) 200 to 240 volts ac for two wire 200 or 240 volt  
modelsforapproximately1minute20secondsfor  
2 gallon batch.  
7. Select a 1-1/2 gallon batch and repeat #6. The  
voltageindicationshouldremainforapproximately  
1 minute.  
8. Select a 1 gallon batch and repeat #6. The indica-  
tion should remain approximately 40 seconds.  
If voltage is present as described the timer is function-  
ing properly.  
OLD STYLE  
P1093  
FIG. 29 TIMER  
Location:  
The timer is located inside the right front of the  
brewer on the upper part of the component bracket.  
Ifvoltageisnotpresentasdescribed, replacethetimer  
and adjust the dial(s) as required.  
Removal and Replacement:  
1. Remove all wires from the timer.  
Test Procedures:  
2. Remove the two #6-32 keps nuts holding circuit  
board and two #8-32 keps holding dial plate on to  
the component mounting bracket.  
3. Remove circuit board, nylon spacers and dial  
plate.  
4. Install new timer directly to component mounting  
bracket as described in Late Model Timer Section.  
5. Refer to Fig. 32 when reconnecting wires.  
6. Install the Timer Setting Decal, provided with the  
replacement timer, on the inside of the front ac-  
cess panel.  
1. Disconnect the brewer from the power source.  
2. Disconnect the wires from the timer terminals  
TL3, TL4 and TL5 and rotate the dial(s) fully  
counterclockwise.  
3. With a voltmeter, check the voltage across termi-  
nals TL1 and TL2 when the "ON/OFF (Warmer)"  
switch is in the "ON" (upper) position. Connect the  
brewer to the power source. The indication must  
be:  
a.)120 volts ac for three wire 120/208 volt models  
and three wire 120/240 volt models.  
b.) 200 to 240 volts ac for two wire 200 or 240 volt  
models.  
7. Adjust the timer as required. Refer to Late Model  
Timer Section on the following pages.  
4. Disconnect the brewer from the power source.  
If voltage is present as described, proceed to #5.  
If voltage is not present as described, refer to the  
Wiring Diagrams and check the brewer wiring har-  
ness.  
5. Check for continuity across the white/orange wire  
and white/yellow wire when the start switch is  
pressed.  
OLD STYLE  
WHI/VIO TL1 to ON/OFF Switch  
WHI TL2 to Terminal BLock (WHI Insert)  
(120/208V or 120/240V Three Pole Ter-  
minal Block)  
RED TL2 to Terminal Block (RED Insert)  
(200V or 240V Two Pole Terminal Block)  
If continuity is present as described, reconnect the  
wires to terminals TL3, TL4 and TL5 of the timer board  
and proceed to #6.  
6. With a voltmeter, check the voltage across termi-  
nals TL1 and TL4 with a voltmeter when the "ON/  
OFF (Warmer)" switch is in the "ON" (upper) posi-  
WHI/ORN TL3 to Start Swtich  
WHI/GRN TL4 to Dispense Valve  
WHI/YEL TL5 to Start Switch  
P1109  
FIG. 30 TIMER TERMINALS  
27362 092900  
Page 34  
SERVICE (cont.)  
nals TL1 and TL4 when the "ON/OFF" switch is in  
the "ON" (upper) position. Connect the brewer to  
the power source. The indication must be 0 volts.  
DIGITAL TIMER (ELECTRO/MECHANICAL ONLY)  
(LATE MODELS)  
If voltage is as described, proceed to #7.  
If voltage is not as described, disconnect the brewer  
from the power source and replace the timer.  
CK  
LO  
CK  
LO  
T
SE  
S E T  
J
1
1
L
T
2
L
T
3
L
T
4
L
T
5
L
T
7. With a voltmeter, check the voltage across termi-  
nals TL1 and TL4 when the "ON/OFF" switch is in  
the"ON"(upper)position. Selectthe2gallonbatch  
setting. Connect the brewer to the power source  
andpressthe"START"switch. Theindicationmust  
be as follows:  
NEW STYLE  
r
e
pm  
ss  
re  
00  
00  
.05  
i
l
00  
ra  
3
22  
)
e  
x
o
#
.05  
a
ro  
6
ig  
m
nt  
52  
o
20  
C
#
0
0)  
0
low  
low  
er  
00  
9  
h
.
F
s
21  
er/  
Wa  
in  
2
37  
tra  
n
#
S
F
e
l.  
re  
ep  
Sc  
(R  
pl.  
e
(R  
P2231.35  
a) 120 volts ac for three wire 120/208 or 120/240  
volt models for approximately 1 minute 20 sec-  
onds for a 2 gallon batch.  
b) 200 to 240 volts ac on two wire 200 volt or 240  
volt models for approximately 1 minute 20 sec-  
onds for a 2 gallon batch.  
FIG. 31 DIGITAL TIMER  
Location:  
The timer is located inside the front of the trunk on  
the top of the component bracket.  
8. Selectthe1-1/2gallonbatchsettingandrepeat#7.  
The voltage indication should remain for approxi-  
mately 1 minute.  
9. Selectthe1gallonbatchsettingandrepeat#7.The  
voltageindicationshouldremainforapproximately  
40 seconds.  
Test Procedure.  
NOTE:Donotremoveorinstallwireswhiletimerboard  
is installed. Pressure applied to one side may cause  
damage to the board.  
1. Disconnect the brewer from the power source and  
remove the front access panel.  
2. Remove the two #8-32 screws securing circuit  
board to the mounting bracket.  
3. Remove circuit board and spacers (as required).  
4. With a voltmeter, check the voltage across termi-  
nals TL1 and TL2 when the "ON/OFF" switch is in  
the"ON"position. Connectthebrewertothepower  
source. The indication must be:  
If voltage is present as described, the brew timer is  
operating properly. Reset the timer as required, to  
obtain the desired brew volume.  
If voltage is not present as described, disconnect the  
brewer from the power source and replace the timer.  
Removal and Replacement:  
1. Remove the two #8-32 screws securing circuit  
board to the mounting bracket.  
2. Remove circuit board and spacers (as required).  
3. Remove all wires from the timer.  
4. Attach all wires to the replacement timer board  
prior to installation to the component mounting  
bracket. Refer to FIG. 32 when reconnecting the  
wires.  
a) 120voltsacforthreewire120/208or120/240  
volt models.  
b) 200 to 240 volts ac on two wire 200 or 240 volt  
models.  
5. Disconnect the brewer from the power source.  
If voltage is present as described, proceed to #6.  
If voltage is not present as described, refer to the  
Wiring Diagrams and check the brewer wiring har-  
ness.  
5. Install new circuit board with spacers (as re-  
quired) to the component mounting bracket.  
6. Adjust the timer as described below.  
6. With a voltmeter, check the voltage across termi-  
27362 092900  
Page 35  
SERVICE (cont.)  
View the level of the liquid being dispensed. When  
the desired level is reached, turn the ON/OFF switch  
to "OFF".  
NOTE: Several ounces of water will continue to sy-  
phon from the tank after turning the switch "OFF". The  
brewer remembers this volume and will continue to  
brew batches of this size until the volume setting pro-  
cedure is repeated.  
DIGITAL TIMER (ELECTRO/MECHANICAL ONLY)  
(LATE MODELS)(cont.)  
Timer Setting:  
NOTE: Prior to setting or modifying volumes, check  
that the brewer is connected to water supply, the tank  
is properly filled, and a funnel and server are in place.  
NOTE: All volume settings must be done with the  
sprayhead installed.  
NOTE: The timer must be adjusted for each individual  
batch setting.  
NOTE: When brewing coffee, volume will decrease due  
to absorption by the coffee grounds.  
3. Setting programming disable feature. If it be-  
comes necessary to prevent anyone from changing  
brew time once programmed, you can set the SET/  
LOCK switch to the "LOCK" position. This will prevent  
any further programming until switch is once again  
put into the "SET" position.  
1. Modifying brew volumes. To modify a brew vol-  
ume, first check that the SET/LOCK switch is in the  
"SET" position on the circuit board.  
To increase a brew volume, place the ON/OFF  
switch in the "ON" position, press and hold the START  
switch until three clicks are heard. Release the switch  
and press it again one or more times. (Failure to re-  
lease the switch within two seconds after the third  
click causes the volume setting to be aborted and pre-  
vious volume setting will remain in memory.) Each  
time the switch is pressed, two seconds are added to  
the brew time period. Allow the brew cycle to finish in  
order to verify that the desired volume has been  
achieved.  
To decrease a brew volume, place the ON/OFF  
switch in the "ON" position, press and release the  
START switch once for every two-second interval to  
be removed from the total brew time period; then im-  
mediately press and hold down the START switch until  
three clicks are heard. Release the switch. (Failure to  
release the switch within two seconds after the third  
click causes the volume setting to be aborted and pre-  
vious volume setting will remain in memory). Allow  
the brew cycle to finish in order to verify that the de-  
sired volume has been achieved.  
TL1 - WHI/VIO to ON/OFF Switch  
TL2 - WHI to Terminal BLock (WHI Insert)  
(120/208V or 120/240V Three Pole  
Terminal Block)  
RED to Terminal Block (RED Insert)  
(200V or 240V Two Pole Terminal Block)  
TL3 - WHI/ORN to Start Switch  
TL4 - WHI/GRN to Dispense Valve  
2. Setting brew volumes. To set a brew volume,  
first check that the SET/LOCK switch is in the "SET"  
position on the circuit board. Place the ON/OFF switch  
in the "ON" position, press and hold the START switch  
until three distinct clicks are heard and then release  
the switch. (Failure to release the switch within two  
seconds after the third click causes the volume set-  
ting to be aborted and previous volume setting will  
remain in memory.)  
TL5 - WHI/YEL to Start Switch  
P2037  
FIG. 32 DIGITAL TIMER WIRING  
27362 092900  
Page 36  
SERVICE (cont.)  
WARMER ELEMENT  
4. Disconnect wires from the warmer element.  
5. Check the continuity across the two terminals on  
the warmer element.  
If continuity is present as described, reconnect the  
white or red wire and white/red wires, or the white or  
redwireandwhite/violetwiresonthewarmerelement.  
If continuity is not present as described, replace the  
warmer element.  
Removal and Replacement:  
1. Remove the four #6-32 screws securing the base  
(warmer) plate to the brewer housing.  
2. Turn base plate over and disconnect the two wires  
from the warmer element.  
3. Removethe#8-32Kepsnut, warmerretainerplate  
and warmer element. Discard warmer element.  
4. Place new warmer element on the center bottom  
of the base plate with the warmer terminals point-  
ing up and to the rear of the base plate.  
5. Install warmer retainer plate and warmer element  
over the stud in bottom of the base plate, secure  
with #8-32 Keps nut.  
P1111.35  
FIG. 33 WARMER ELEMENT  
6. Reconnectthetwowirestowarmerelementtermi-  
nals.  
7. Turn base plate over and reinstall with four #6-32  
screws to the brewer housing.  
Location:  
The warmer element is located on the bottom the  
base (warmer) plate.  
8. Refer to Fig. 34 when reconnecting wires.  
Test Procedures:  
1. Disconnect the brewer from the power source.  
2. On 120/208V or 120/240V models, with a voltme-  
ter, check the voltage across the white wire and  
the white/violet wire or white/red wire to the ele-  
ment with the "ON/OFF (Warmer)" switch in the  
"ON" (upper) position. On 200V or 240V models,  
with a voltmeter, check the voltage across the red  
wire and the white/violet wire or white/red wire  
with the "ON/OFF (Warmer)" switch in the "ON"  
(upper) position. The indication must be:  
a.)120 volts ac for three wire 120/208 volt models  
and three wire 120/240 volt models.  
WHI/VIO to ON/OFF Switch (Electro/Mechanical)  
WHI/RED to ON/OFF Switch (DBC)  
WHI to Terminal Block (120/208V or 120/  
240V Brewers)  
RED to Terminal Block (200V or 240V  
Brewers  
b.) 200 to 240 volts ac for two wire 200 or 240 volt  
models.  
3. Disconnect the brewer from the power source.  
P1110  
If voltage is present as described, proceed to #4.  
If voltage is not present as described, refer to the  
Wiring Diagrams and check brewer wiring harness.  
FIG. 34 WARMER ELEMENT TERMINALS  
27362 092996  
Page 37  
LOWER  
27362 092900  
Page 38  
27362 092900  
Page 39  
LOWER  
27362 092900  
Page 40  

Motorola Crush User Manual
Microsoft Windows 8 Pro 64 bit FQC 05956 User Manual
Kenwood KDC 217 User Manual
Jura Capresso F50 User Manual
Hitachi Travelstar Z5K500 User Manual
Hitachi Travelstar HTS725032A9A360 User Manual
Dell PowerVault E03J Series User Manual
Apple 2A034 4760 A User Manual
Addonics Technologies AD2CFEXC34 User Manual
ABB TPS 52E01 User Manual