U3
U3A
OPERATING & SERVICE MANUAL
BUNN-O-MATIC CORPORATION
POST OFFICE BOX 3227
SPRINGFIELD, ILLINOIS 62708-3227
PHONE: (217) 529-6601 FAX: (217) 529-6644
To ensure you have the latest revision of the Operating Manual, or to view the Illustrated Parts
Catalog, Programming Manual, or Service Manual, please visit the Bunn-O-Matic website, at
manual updates. For Technical Service, contact Bunn-O-Matic Corporation at 1-800-286-6070.
10060.0000K 10/08 ©1984 Bunn-O-Matic Corporation
INTRODUCTION
This brewer will brew a three gallon batch of coffee into each reservoir (one at a time). Each reservoir has
its own dispensing faucet(s).The brewer also has a hot water faucet(s) for allied beverage use. It is only for
indoor use on a sturdy counter where ambient temperature is in the range of 10-30°C (50-85°F). Brewer to be
installed at a location where it can be overseen by trained personnel.
USER NOTICES
Carefully read and follow all notices on the brewer and in this manual. They were written for your protection.
All notices on the brewer are to be kept in good condition. Replace any unreadable or damaged labels.
This equipment must be installed to comply
WARNING
with the International Plumbing Code of the
Fill water tank before turning - on -
thermostat or connecting appliance
to power source.
International Code Council and the Food
Code Manual of the Food and Drug Adminis-
tration (FDA). For models installed outside
the U.S.A., comply with the applicable
Plumbing /Sanitation Code.
Use only on a properly protected
circuit capable of the rated load.
Electrically ground the chassis.
Follow national/local electrical codes.
Do not use near combustibles.
#00656.0000
FAILURE TO COMPLY RISKS EQUIPMENT
DAMAGE, FIRE, OR SHOCK HAZARD
READ THE ENTIRE OPERATING MANUAL
BEFORE BUYING OR USING THIS PRODUCT
THIS APPLIANCE IS HEATED WHENEVER
CONNECTED TO A POWER SOURCE
00831.0000F 3/98 ©1998 BUNN-O-MATIC CORPORATION
#00831.0000
#37881.0000
WARNING
WARNING
Very Hot Water
REMOVE FUNNEL
#03408.0000
Use With Care!
#12593.0000
WARNING
H O T
CAUTION
#03409.0000
HOT
ATTENTION: TURN OFF WHEN UNATTENDED
SURFACES
#00878.0000
#12555.0000
#00824.0001
10060 011708
Page 3
ELECTRICAL REQUIREMENTS
CAUTION - The brewer must be disconnected from the power source until specified in Initial Set-Up.
RED
L2 RED
WHITE
L2
L3
L1
208V OR 240V
380V OR 440V
120V A.C.
120V A.C.
BLUE
208V OR 240V
380V OR 440V
208 OR
240V A.C.
208V OR 240V
380V OR 440V
NEUTRAL
L1 BLACK
BLACK
GREEN
GREEN
P1841
P1843
U3 & U38 requires 3-wire, grounded service rated
120/208or120/240voltsac,U3-30amp,U38-40amp,
single phase, 60 Hz. Proceed as follows:
U333 & U3833 requires 3-wire, grounded service
rated 240 volt ac, 35 amp or 440 volts ac, 30 amp for
U333,three phase, 60 Hz or 380 volts ac, 30 amp for
U3833, three phase, 50 Hz. Proceed as follows:
L1, L2, L3, are the 3 phases
WHITE
(NEUTRAL)
N
V1 = Phase to phase voltage,
RED
between any 2 phases.
L2
L3
L1
BLACK
L1
BLUE
V2 = Phase to neutral voltage,
any phase to neutral.
BLACK
230V A.C.
RED
L2
GREEN
GREEN
SYSTEM
VOLTAGE
208
V1
V2
GREEN
GREEN
208
240
380
120
139
220
P1844
240
380
P1842
440
440
254
U3833 requires 4-wire, grounded service rated
380 volts ac or 440 volts ac, 30 amp, three phase, 50
Hz. Proceed as follows:
U3Amodelsrequire2-wire,groundedservicerated
230 volts ac, 30 amp, single phase, 50 Hz. Proceed
as follows:
ELECTRICAL INSTALLATION INSTRUCTIONS
NOTE: Electrical source should have a circuit breaker between the brewer and the main supply which breaks all
poles with a contact separation of at least 3 mm.
CAUTION – Improper electrical installation will damage electronic components.
1. An electrician must provide electrical service as specified.
2. Using a voltmeter, check the voltage and color coding of each conductor at the electrical source.
3. Before electrically connecting the brewer, remove the front cupola cover (some models have the thermostat
knob on the outside of the cover) and rotate the thermostat knob fully counterclockwise to the "OFF" position.
Keep this knob in the "OFF" position until performing the Initial Setup.
4. Electrical service is connected at the upper rear of the single service and scrambler brewers using a junc-
tion box. On double service brewers the rear decorative channel must be removed for access to the terminal
block.
5. Connect the brewer to the power source and verify the voltage at the terminal block before proceeding. Re-
place all panels.
6. If plumbing is to be hooked up later be sure the brewer is disconnected from the power source. If plumbing
has been hooked up, the brewer is ready for Initial Setup.
NOTE: Schematic wiring diagrams are included in this manual.
10060 011708
Page 4
CE REQUIREMENTS
• This appliance must be installed in locations where it can be overseen by trained personnel.
• For proper operation, this appliance must be installed where the temperature is between 5°C to 35°C.
• Appliance shall not be tilted more than 10° for safe operation.
• An electrician must provide electrical service as specified in conformance with all local and national codes.
• This appliance must not be cleaned by water jet.
• This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given instructions concerning use of
this appliance by a person responsible for its safety.
• Children should be supervised to ensure they do not play with the appliance.
• If the power cord is ever damaged, it must be replaced by the manufacturer or authorized service personnel with
a special cord available from the manufacturer or its authorized service personnel in order to avoid a hazard.
PLUMBING REQUIREMENTS
These brewers must be connected to a cold water system with operating pressure between 20 (138) and 90 psi (620 kPa)
from a 1/2" or larger supply line. A shut-off valve should be installed in the line before the brewer. Install a regulator in the
line when pressure is greater than 90 psi (620 kPa) to reduce it to 50 psi (345 kPa). The water inlet fitting is 3/8" flare.
NOTE - Bunn-O-Matic recommends 3/8" copper tubing for installations from the 1/2" water supply line. A tight coil of
copper tubing in the water line will facilitate moving the brewer to clean the countertop. Bunn-O-Matic does not recom-
mend the use of a saddle valve to install the brewer. The size and shape of the hole made in the supply line by this type
of device may restrict water flow.
ThisequipmentmustbeinstalledtocomplywiththeInternationalPlumbingCodeoftheInternational
Code Council and the Food Code Manual of the Food and Drug Administration (FDA). For models
installed outside the U.S.A., you must comply with the applicable Plumbing/Sanitation Code for
your area.
INITIAL SETUP
CAUTION - The brewer must be disconnected from the power source throughout the initial setup, except when specified
in the instructions.
IMPORTANT: Brewer must be level and installed on a sturdy structure.
Electrician's and Plumber's Instructions are provided. These instructions should be carefully followed
before proceeding with initial setup.
Be sure all electrical and plumbing connections are tight.
1. Open manual fill valve located on the bottom of the brewer. Water should start filling the tank. When water is visible
in the hot water gauge glass (center spigot), close valve. Approximate time for filling manually is 3 minutes.
CAUTION: Never leave brewer unattended while manually filling tank.
2. Connect the brewer to the power source. Turn "ON/OFF" switch to the "ON" position. Water should finish filling tank
automatically.
NOTE: It is recommended that the "ON/OFF" switch be left in the "OFF" position at the end of the operating day or when
unattended for a long period of time.
3. Disconnect the brewer from the power source. Remove front cupola cover for access to thermostat knob and timer.
On some brewers the thermostat knob is located on the front of the cupola cover.
4. Turn the thermostat knob clockwise to an approximate 5 o'clock position. Allow 1-1/2 hours for water to heat. Time
will vary with incoming water temperature.
5. On initial warm-up, some water may flow thru the overflow spigot due to expansion of the cold water in the tank.
This will not recur during the use of the brewer and may be avoided on the initial warm-up by drawing off 1/2 gallon
decanters of water each 15 minutes till brewing temperature is reached.
10060 102808
Page 5
INITIAL SETUP (cont.)
6. Brewing cycles may be started whenever water temperature is correct. This condition is indicated by the dial
thermometer on front of the brewer. Whenever the pointer is in the green, brewer is ready for brewing. The
recommended brewing temperature is approximately 200° F (93°C). Water temperature may be increased by
turning thermostat knob clockwise, decreased by turning knob counterclockwise.
7. When desired temperature is reached, insert funnel support, funnel and funnel cover in position. Be sure
the water swing spout is over the center of the funnel cover, turn "ON/OFF" switch to the "ON" position, push
and release "START" and run a brew cycle of hot water only. At the end of this cycle, brewer will be ready for
checking timer adjustment.
8. The timer has been preset for a 4 minute cycle. This setting will deliver approximately 3 gallons of water per
brewing cycle. To increase or decrease amount of water, adjust the timer as required. See Adjusting Brew
Volumes.
9. Having determined final settings of the thermostat and the timer, replace front cupola cover. Brewer is now
ready for brewing coffee.
ADJUSTING BREW VOLUMES
CAUTION - Disconnect the power source from the brewer prior to the removal of any panel for the replacement
or adjustment of any component.
NOTE: Prior to setting or modifying batch sizes, check that the brewer is connected to water supply, the tank is
properly filled, and a funnel support, funnel and funnel cover are in place.
1. Modifying batch sizes. To modify a batch volume, first check that the SET/LOCK switch is in the “SET” posi-
tion on the circuit board.
To increase a batch size. Press and hold the START or BREW switch until you see three breaks in the water
stream from the swing arm. Release the switch (Failure to release the switch within two seconds after the
third break in the water stream causes the volume setting to be aborted and previous volume setting will
remain in memory) and press it again one or more times. Each time the switch is pressed, two seconds are
added to the brew time period. Allow the brew cycle to finish in order to verify that the desired volume has
been achieved.
To decrease a batch size. Press and release the START or BREW switch once for every two-second interval
to be removed from the total brew time period; then immediately press and hold down the START or BREW
switch until you see three breaks in the water stream from the swing arm. Release the switch. (Failure to
release the switch within two seconds after the third break in the water stream causes the volume setting to
be aborted and previous volume setting will remain in memory). Allow the brew cycle to finish in order to
verify that the desired volume has been achieved.
2. Setting batch sizes. To set a batch volume, first check that the SET/LOCK switch is in the “SET” position on
the circuit board. Press and hold the START or BREW switch until you see three breaks in the water stream
from the swing arm, and then release the switch. (Failure to release the switch within two seconds after the
third break in the water stream causes the volume setting to be aborted and previous volume setting will
remain in memory). View the level of the liquid being dispensed. When the desired level is reached, turn the
ON/OFF switch to “OFF” (lower). The brewer remembers this volume and will continue to brew batches of
this size until the volume setting procedure is repeated.
NOTE: When brewing coffee, batch volumes will decrease due to absorption by the coffee grounds.
NOTE: HALF-BATCH AND FULL BATCH SETTINGS MUST EACH BE SET SEPARATELY.
3. Setting programming disable feature. If it becomes necessary to prevent anyone from changing brew times
once programmed, you can set the SET/LOCK switch to the “LOCK” position. This will prevent any program-
ming to be done until switch is once again placed in the “SET” position.
10060 080900
Page 6
COFFEE BREWING
1. Brewing cycles may be started whenever water temperature is correct. This condition is indicated by the dial
thermometer on front of the brewer. Whenever the pointer is in the green, brewer is ready for brewing.
2. Insert Bunn® filter in funnel and add desired amount of coffee.
3. Level the bed of coffee and place funnel into the funnel support. Place funnel cover over the funnel and be
sure the water swing spout is over the center of the funnel cover.
4. Turn "ON/OFF" switch to the "ON" position.
5. Push and release "START" switch to start the brew cycle.
6. Water swing spout should not be moved as long as water is flowing into the funnel cover. When water stops
flowing, it may then be moved for access to brewing funnel.
7. Remove funnel cover. Funnel should not be removed from brewer until drip out of coffee has been com-
pleted.
8. To empty funnel, invert it over a waste container to dispose of filter and grounds. An additional flange is
provided on the funnel to help make this step easier.
NOTE: Hot water may be drawn from the hot water faucet during a brew cycle. However, if a large amount of
hot water is drawn off (over 1 gallon) operator should wait to do so between brewing cycles.
CLEANING
NOTE: Tanks and tank components should be delimed regularly based on local water conditions. Excessive
mineral build-up on stainless steel surfaces can initiate corrosion reactions resulting in serious leaks.
1. Remove both funnels, funnel lids and supports, under hot water, rinse away all coffee oils. Wipe with a clean
damp cloth.
2. Drain both coffee reservoirs by opening coffee faucets. When empty, close faucets.
3. Cycle two or three inches of water into each coffee reservoir and scrub entire reservoir area.
NOTE: The brewer must NOT be rinsed or cleaned by a water jet device.
4. Drain both coffee reservoirs and rinse. Use clean damp cloth to wipe both reservoirs.
5. Install both coffee funnel supports, funnels and funnel lids.
6. Remove the sight gauge cap, insert sight gauge cleaning brush into the sight gauge glass tube and clean.
7. To clean coffee faucets, remove the faucet handle from the faucet and faucet clean out cap. Clean faucet with
a faucet cleaning brush and wipe all parts with a damp cloth. Replace faucet seat cups periodically if badly
stained or to stop faucet dripping. DO NOT CLEAN THE HOT WATER FAUCET.
8 Reassemble the coffee faucets.
9. Wipe the entire outside surface of the machine with a clean damp cloth. Wipe dry.
FILTER HOLDER
1. A filter holder is supplied with each U3 coffee brewer. Its purpose is to keep the filters in their originally
formed shape to properly fit the brewer funnel.
2. It is suggested that only one cluster of filters be placed in the holder at one time for best results.
3. Not using the filter holder may permit the filters to gradually widen out towards a flat shape, especially so if
humidity is present. Once a filter has lost its upright side walls, it may tend to collapse inward when placed
in the brewing funnel. If this happens the hot water spray may cause one side to fall inwards, letting coffee
grounds flow over the edge of filter and into the brewed coffee. Proper use of the holder should prevent this
problem.
10060 081106
Page 7
TROUBLESHOOTING
A troubleshooting guide is provided to suggest probable causes and remedies for the most likely problems
encountered. If the problem remains after exhausting the troubleshooting steps, contact the Bunn-O-Matic
Technical Service Department.
•
•
•
Inspection, testing, and repair of electrical equipment should be performed only by qualified service person-
nel.
All electronic components have 120 volt ac and low voltage dc potential on their terminals. Shorting of
terminals or the application of external voltages may result in board failure.
Intermittent operation of electronic circuit boards is unlikely. Board failure will normally be permanent. If
an intermittent condition is encountered, the cause will likely be a switch contact or a loose connection at a
terminal or crimp.
•
•
Solenoid removal requires interrupting the water supply to the valve. Damage may result if solenoids are
energized for more than ten minutes without a supply of water.
The use of two wrenches is recommended whenever plumbing fittings are tightened or loosened. This will
help to avoid twists and kinks in the tubing.
•
•
Make certain that all plumbing connections are sealed and electrical connections tight and isolated.
This brewer is heated at all times. Keep away from combustibles.
WARNING – • Exercise extreme caution when servicing electrical equipment.
• Unplug the brewer when servicing, except when electrical tests are specified.
• Follow recommended service procedures
• Replace all protective shields or safety notices
PROBLEM
PROBABLE CAUSE
REMEDY
Brew cycle will not start
1. No water
Water lines and valves to the brewer
must be open.
(A1) Check the terminal block for
120voltsacacrosstheredandwhite
terminals and the black and white
terminal on three wire 102/208 volt
or 120/240 volt models.
2. No power or incorrect voltage to
the brewer
(A2)Checktheterminalblockfor208
volts ac, 230 volts ac or 240 volts
ac on "A Series" brewers across the
red and black terminals on two wire
single phase 208 volt, 230 volt and
240 volt models.
(A3)Checktheterminalblockfor208
volts ac, 240 volts ac, 380 volts ac
across the black and blue terminals,
the blue and red and the black and
red terminals on three wire three
phase 208 volt, 240 volt and 380
volt models.
10060 031500
Page 8
TROUBLESHOOTING (cont.)
PROBLEM
REMEDY
PROBABLE CAUSE
Brew cycle will not start (cont)
(A4) Check the terminal block for
440 volts ac across the black and
blue terminals, black and red termi-
nals and the red and blue terminals
on four wire three phase 440 volt
models.
2. No power or incorrect voltage to
the brewer (cont)
(B) Check circuit breakers or
fuses.
Be sure water shut-off valve is open
and that the in-line filters or strain-
ers are not blocking water flow. (Do
not confuse water shut-off valve
with the manual fill and drain valve
underneath the brewer).
3. Water level below pump housing.
(Water level in the hot water gauge
glass should be approximately half
full).
RefertoService-ON/OFFSwitchfor
testing. See page 22
4. ON/OFF Switch
5. Start Switch
6. Relay
Refer to Service - Start Switches for
testing procedures. See page 29
Refer to Service - Relay for testing
procedures. See page 24
Refer to Service - Timer for testing
procedures. See page 31 or 33
7. Timer
Refer to Service - Pump for testing
procedures. See page 23
8. Pump
Refer to Service - Solenoid Valve for
testing procedures. See page 27
9. Solenoid Valve
10. Strainer
(A) Direction of flow arrow must be
pointing towards brewer.
(B) Remove the strainer and check
for obstructions. Clear or replace.
Brew cycle starts with brew lockout
relay engaged.
Refer to Service - Relay for testing
procedures. See page 24
1. Relay
10060 080900
Page 9
TROUBLESHOOTING (cont.)
PROBLEM
PROBABLE CAUSE
REMEDY
1.ON/OFF Switch (This switch
must be in the "ON" position for
the refill circuit to operate.
Tank not filling
Refer to Service - ON/OFF Switch
for testing procedures. See page
22
2. No water
Be sure water shut-off is open and
that in-line filters or strainers are
not blocking water flow. (Do not
confuse water shut-off valve with
the manual fill and drain valve
underneath brewer).
3. Solenoid Valve
Refer to Service - Solenoid Valve
for testing procedures. See page
27
4. Probe
RefertoService-Probefortesting
procedures. See page 20
5. Liquid Level Board
Refer to Service - Liquid Level
Board for testing procedures. See
page 20
1.Brewer not level
2. Solenoid Valve
Water running out of the over-
flow
Brewer must be level and installed
on a sturdy structure.
Refer to Service - Solenoid Valve
for testing procedures. See page
27
3. Liquid Level Board
4. Probe
Refer to Service -Liquid Level
Board for testing procedures. See
page 20
RefertoService-Probe fortesting
procedures. See page 20
5. Manual fill and drain valve un-
derneath brewer open.
Be sure valve is closed.
10060 080900
Page 10
TROUBLESHOOTING (cont.)
PROBLEM
PROBABLE CAUSE
REMEDY
Water not hot
1. Limit Thermostat
Refer to Service - Limit Thermo-
stat for testing procedures. See
page19
CAUTION - Do not eliminate or
bypass limit thermostat. Use only
Bunn-O-Matic replacement part
#29329.1000
2. Control Thermostat
Refer to Service - Control Ther-
mostat for testing procedures.
See page 17
3. Tank Heater(s)
4. Contactor
Refer to Service - Tank Heater for
testing procedures. See page 30
Refer to Service - Contactor for
testing procedures. See page 15
Circuit breaker keeps tripping
1. Circuit Breaker
Refer to Service - Circuit Breaker
for testing procedures. See page
14
2. Tank Heater(s)
1. Timer
Refer to Service - Tank Heater for
testing procedures. See page 30
Water keeps running from swing
spout
RefertoService-Timerfortesting
procedures. See page 31 or 33
2. Start Switch
1. Timer
Refer to Service - Start Switch for
testing procedures. See page 29
Inconsistent coffee yield
RefertoService-Timerfortesting
procedures. See page 31 or 33
2. Solenoid Valve
Refer to Service - Solenoid Valve
for testing procedures. See page
27
3. Lime build-up in swing spout
and pump tubing.
Remove swing spout and insert
deliming rod down into pump
tubing as far as possible.
Use Bunn® filters made for the
U3 brewer.
Funnels overflow
1. Filters
2. Hole in bottom of funnel ob-
structed.
Remove obstruction.
10060 080900
Page 11
TROUBLESHOOTING (cont.)
PROBLEM
PROBABLE CAUSE
REMEDY
Checkpumpflowratewithawatch.
Pumpflowrateshouldbeapproxi-
mately 24 ounces in 15 seconds.
Be sure pump assembly is free of
any obstructions.
3. Pump - Flow Rate
Funnels overflow (cont.)
4. Soft Water
When using a water softener, a
coarse grind of coffee may be
preferred. If required, a bypass
system is available as an optional
feature.
Coffee reservoir overflows
Be sure coffee reservoir is empty
before brew cycle is started.
1. Coffee reservoir not completely
empty befor a brew cycle was
started.
RefertoService-Timer for testing
procedures. See page 31 or 33
2. Timer
Checkpumpflowratewithawatch.
Pumpflowrateshouldbeapproxi-
mately 24 ounces in 15 seconds.
Be sure pump assembly is free of
any obstructions.
3. Pump - Flow Rate
Brewer is making unusal noises
The nut on the solenoid must
be tight or it will vibrate during
operation.
1. Solenoid Valve
Plumbinglinesshouldnotberest-
ing on the counter top.
2. Plumbing lines
3. Water supply
(A)Thebrewermustbeconnected
to a cold water line.
(B) Water pressure to the brewer
must not exceed 90 psi (620 kPa).
Install a regulator if necessary to
lower the pressure to approxi-
mately 50 psi (345 kPa).
Removeandcleanlimeoffthetank
heater. See page 30
4. Tank Heater(s)
10060 080900
Page 12
SERVICE
Contents
Circuit Breaker .....................................................14
Contactor ..............................................................15
Control Thermostat...............................................17
Fuse and Fuse Holder ...........................................18
Limit Thermostat...................................................19
Liquid Level Board and Level Probe .................... 20
ON/OFF Switch......................................................22
Pump ....................................................................23
Relay ................................................................... 24
Selector Switch (Half Batch) .................................26
Solenoid ...............................................................27
Start Switch (Brew)...............................................29
Tank Heater(s).......................................................30
Thermal Cut-off ................................................... 31
Timer (Early Models).............................................31
Digital Timer (Late Models)...................................33
Transformer ..........................................................35
Master ON/OFF Switch (Late Models)...................36
Wiring Diagrams...................................... 37 thru 42
This section provides procedures for testing and
replacing various major components used in this
brewer should service become necessary. Refer to
Troubleshooting for assistance in determining the
cause of any problem.
WARNING - Inspection, testing, and repair of electri-
cal equipment should be performed only by qualified
service personnel. The brewer should be unplugged
when servicing, except when electrical tests are re-
quired and the test procedure specifically states to
plug in the brewer.
COMPONENT ACCESS
WARNING - Disconnect the brewer from the power
source before the removal of any panel or the replace-
ment of any component.
All components are accessible by the removal of
the swing spout, front cupola cover, rear cupola cover
and the cupola.
Disconnect the swing spout nut from the swing
spout base fitting. Remove swing spout.
Remove the four #8-32 screws, two on the front and
rear, securing front and rear cupola covers to the
cupola.
Slip cupola off of the component bracket.
P1317.30
FIG. 1 COMPONENT ACCESS
10060 011708
Page 13
SERVICE (cont.)
CIRCUIT BREAKER (120/208V and 120/240V Three
Wire Models and 440V Four Wire Models)
4. With the black wire removed, remove the other
black wire from the circuit breaker.
5. Check for continuity across the terminals on the
circuit breaker.
If continuity is present as described the circuit breaker
is operating properly.
Ifcontinuityisnotpresentasdescribed,pressthereset
button and repeat step 5, if continuity is not present
as described, replace the circuit breaker.
Removal and Replacement:
1. Remove wires from the circuit breaker.
2. Remove the nut securing the circuit breaker to the
component bracket.
3. Remove circuit breaker and discard.
4. Install new circuit breaker on component bracket
and secure with nut.
P2209.60
FIG. 2 CIRCUIT BREAKER
5. Refer to Fig. 3 and reconnect the wires.
Location:
The circuit breaker is located on the right rear of
the component bracket.
BLK from Main
Harness
Test Procedures:
1. Disconnect the brewer from the power source.
2. Disconnect the black wire from the main harness
from the circuit breaker and the white wire on the
pumpassembly.Withavoltmeter,checkthevoltage
across the black wire and the white wire. Connect
the brewer to the power source. The indication
must be:
BLK from ON/
OFF Switch
P1723
FIG. 3 CIRCUIT BREAKER TERMINALS
a) 120 volts ac for three wire 120/208 volt and
120/240 volt models.
b) 208 or 240 volts ac for four wire 440 volt mod-
els.
3. Disconnect the brewer from the power source.
If voltage is present as described, reconnect the white
wire to the pump assembly and proceed to #4. If volt-
age is not present as described, refer to the Wiring
Diagrams and check the brewer wiring harness.
10060 080900
Page 14
SERVICE (cont.)
CONTACTOR
a) 120 volts ac for three wire 120/208, 120/240
volt and 380 volt models.
b) 230 volts ac for two wire 230 volt models.
c) 208 or 240 volts ac for two wire 208 or 240 volt
models.
d) 220 or 254 volts ac for four wire 280 or 440
volt models.
5. Disconnect the brewer from the power source.
If voltage is present as described, proceed to #6.
IfvoltageisnotpresentasdescribedrefertotheWiring
Diagrams and check the brewer wiring harness.
6. Check for continuity between the black leads on
the contactor coil or the left and right terminals
on the contactor coil on 230V models.
P2209.60
FIG. 4 CONTACTOR
Location:
The contactor is located on the left front of the
component bracket
If continuity is present as described, reconnect the
wires and proceed to #7.
If continuity is not present as described, replace the
contactor.
Test Procedures:
1. Disconnect the brewer from the power source.
2A. 120/208V,120/240V,380VTHREEWIREMODELS,
380V and 440V FOUR WIRE MODELS
Disconnect the black wire from the contactor coil
to the limit thermostat and black wire from the
white wire on the main harness.
7. On all brewers, with a voltmeter, check the voltage
across the upper left terminal and the upper right
terminal on the contactor. Connect the brewer to
the power source. The indication must be:
a) 120 volts ac for three wire 120/208, 120/240
volt and 380 volt models.
2B. 208V or 240V TWO WIRE MODELS (Prior to
# U300004095), 208V and 240V THREE WIRE
MODELS
b) 230 volts ac for two wire 230 volt models.
c) 208 or 240 volts ac for two wire 208 or 240 volt
models.
d) 220 or 254 volts ac for four wire 280 or 440
volt models.
Disconnect the black wire from the contactor coil
to the limit thermostat and black wire from the red
wire on the main harness.
8. Disconnect the brewer from the power source.
2C. 230V MODELS (S/N U300004095 - UP)
Disconnect the red wire from contactor coil to the
limit thermostat and the black wire from the main
harness.
3. Connect the brewer to the power source.
4. Check the voltage across the coil wire and the wire
from the the main harness.The indication must
be:
If voltage is present as described, proceed to #9.
Ifvoltageisnotpresentasdescribed,refertotheWiring
Diagrams and check the brewer wiring harness.
10060 080900
Page 15
SERVICE (cont.)
CONTACTOR (cont.)
Removal and Replacement:
9. Check for continuity across the terminals on the
left side of the contactor by manually closing the
contacts. Continuity must not present when the
contact is released.
1. Disconnect all the wires from the contactor.
2. Remove the two #8-32 screws securing the con-
tactor to the contactor mounting bracket, remove
contactor and protective shield. Discard contac-
tor.
3. Installnewcontactorwithshieldbetweenmounting
bracket and contactor and secure with two #8-32
screws
10. Check for continuity across the terminals on the
right side of the contactor by manually closing the
contacts.Continuity must not be present when the
contact is released.
4. Refer to Fig. 5 and reconnect the wires.
If continuity is present as described, the contactor is
operating properly.
If continuity is not present as described, replace the
contactor.
BLK to Right Tank
Heater (T1)
BLK to Terminal
Block (L1)
RED to Left Tank
BLK Thermal Fuse
to Right Tank Heater
BLK to Terminal
Block (L1)
RED Thermal Fuse
to Left Tank Heater
Heater (T2)
RED to Terminal
Block(L2)
BLK to Terminal
Block (L2)
BLK to left
Tank Heater
(L1)
RED to Terminal
Block (L2)
BLK Thermal
Fuse to Left
Tank Heater
RED to Right
Tank Heater
(L2)
WHI from Main Harness
RED to Limit
Thermostat
(120/208V,120/240V,380V
Three Wire Models, 380V and
440V Four Wire Models)
RED from Main Harness
(208V, 240V Two Wire Models
and 208, 240V Three Wire
Models)
BLK to Limit
Thermostat
RED Thermal Fuse
to Right Tank
Heater
230V - CE Models
120/208V, 120/240V, 208V,
240V, 380V 440V MODELS
P1725
FIG.5 CONTACTOR TERMINALS
10060 080900
Page 16
SERVICE (cont.)
CONTROL THERMOSTAT
not be present when the thermostat is in the "OFF"
position (fully counterclockwise).
If continuity is present as described, the control ther-
mostat is operating properly.
If continuity is not present as described, replace the
control thermostat.
Removal and Replacement:
1. Disconnect the wires from the control thermo-
stat.
2. Remove the thermostat capillary bulb by firmly
pulling up on the capillary at the component
bracket. This will disengage the grommet from
the component bracket.
P2209.60
FIG. 6 CONTROL THERMOSTAT
3. Remove the #8-32 screw securing the control
thermostatandmountingbrackettothecomponent
bracket. Remove control thermostat and bracket
as an assembly.
Location:
The control thermostat is mounted on the right
front of the component bracket.
4. Remove knob from control thermostat.
5. Removethetwo#6-32screwssecuringthecontrol
thermostat to the thermostat mounting bracket.
Remove and discard thermostat.
Test Procedures:
1. Disconnect the brewer from the power source.
2. Locate the thermostat and the voltage check
points.
6. Install new control thermostat on thermostat
mounting bracket and secure with two #6-32
screw.
3. Connect the brewer to the power source.
Model
120/208V & 120
240V - 3 wire w/
ground single phase
Check Voltage Across
Voltage
Black wire on thermostat 120V
frommainharnesstowhite
wire in terminal block.
7. Install knob on thermostat.
8. Install thermostat and mounting bracket on the
component bracket and secure with one #8-32
screw.
Red wire on thermostat 230V
frommainharnesstoblack
wire in terminal block.
230V - 2 wire w/
ground single
phase
9. Carefully bend the capillary tube so that the tube
and bulb inside the brewer are in the vertical posi-
tion.
NOTE:Thecapillarytubemustbeclearofanyelectrical
termination and not kinked.
Black wire on thermostat 208V or
from main harness to red 240V
wire in the terminal block.
208V or 240V - 2
wire w/ground
single phase
10. Refer to Fig. 7 and reconnect the wires.
11. Adjust the control thermostat as required.
Black wire on thermostat 220V or
frommainharnesstowhite 254V
wire in terminal block.
280V or 440V - 4
wire w/ground 3
phase
BLK from Main Har-
ness (All Models Ex-
cept 230V CE Models
RED from Main
Harness (230V CE
Models)
Black wire on thermostat 120V
frommainharnesstowhite
wire on step down trans-
former.
380V - 3 wire w/
ground 3 phase
w/ stepdown
transformer
4. Disconnect the brewer from the power source.
If voltage is present as described, proceed to #5.
Ifvoltageisnotpresentasdescribed,refertotheWiring
Diagrams and check the brewer wiring harness.
BLK to Limit Thermostat
(All Models Except 230V CE
Models
RED to Limit Thermostat
(230V CE Models)
P1730.80
5. Disconnect the black wires from the control ther-
mostat.
6. Check for continuity across the terminals on the
control thermostat with the control thermostat in
the"ON"position(fullyclockwise),continuitymust
FIG. 7 CONTROL THERMOSTAT TERMINALS
10060 080900
Page 17
SERVICE (cont.)
Removal and Replacement:
Fuse:
1. Remove the cap from the fuse holder.
2. Removefusefromthefuseholder,inspect,ifblown
discard.
FUSE AND FUSE HOLDER (208V, 240V, 230V Two
Wire Models and 380V Three Wire Models)
3. Install new 5 amp fuse in the fuse holder.
4. Reinstall fuse holder cap.
Fuse Holder:
1. Disconnect the wires from the rear of the fuse
holder.
2. Remove the nut securing the fuse holder to the
component bracket.
3. Pushfuseholderthroughtheholeinthecomponent
bracket.
4. Install new fuse holder and fuse through the hole
in the component bracket and secure with nut.
5. Refer to Fig. 9 and reconnect the wires.
P1731.55
BLK from ON/OFF Switch
(208V, 240V Two Wire
Models and 380V Three
Wire Models)
FIG.8 FUSE AND FUSE HILDER
Location:
The fuse and fuse holder are located on the right
rear of the component bracket.
RED from ON/OFF Switch
(230V Two Wire Models)
Test Procedures:
1. Disconnect the brewer from the power source.
2. Remove the cap and fuse from the fuse holder.
3. Remove fuse from the cap.
BLK from Main Harness
(208V and 240V Two Wire
Models)
BLK from Transformer
(380V Three Wire Models)
RED from Main Harness
(230V Two Wire Models)
4. Check for continuity through the fuse.
Ifcontinuityispresentasdescribed, reinstallthefuse,
the fuse is operating properly.
If continuity is not present as described replace the
fuse.
P1331
FIG. 9 FUSE HOLDER TERMINALS
10060 031599
Page 18
SERVICE (cont.)
LIMIT THERMOSTAT
Removal and Replacement:
1. Remove the wires from the limit thermostat ter-
minals.
2. Carefully slide the limit thermostat out from under
the retaining clip and remove the limit thermo-
stat.
3. Carefully slide the new limit thermostat into the
retaining clip.
4. Refer to Fig. 11 and reconnect the wires.
P2209.60
FIG. 10 LIMIT THERMOSTAT
Location:
The limit thermostat is located on the center front
of the component bracket behind the timer mounting
bracket.
BLK to Contactor
(All Models Except
230V CE Models)
Red to Contactor
BLK to Control
Thermostat(All
Models Except
230V CE Models)
RED to Control
Thermostat
(230V Models)
Test Procedures:
(230V CE Models)
1. Disconnect the brewer from the power source.
2. Disconnect the black wires or the red wires from
the limit thermostat.
3. With an ohmmeter, check for continuity across
the limit thermostat terminals.
P1800
FIG. 11 LIMIT THERMOSTAT TERMINALS
Ifcontinuityispresentasdescribed,thelimitthermostat
is operating properly.
If continuity is not present as described, replace the
limit thermostat.
10060 080900
Page 19
SERVICE (cont.)
LIQUID LEVEL BOARD AND LEVEL PROBE
7. Touchingthefreeendofthejumpertothebrewer's
frame simulates a "FULL" condition, preventing
jumperfromtouchingthebrewer'sframesimulates
"NEED WATER" condition. Connect the brewer to
the power source, simulate the conditions in the
chart below while measuring the voltage between
T1 and T3 0n the liquid level board. Repeat these
several times. There is an approximate five second
delay for output to stabilize.
Voltage -
Jumper
Touching
Frame
Voltage -
Jumper
Not Touching
Frame
Model
P2209.60
FIG.12 LIQUID LEVEL BOARD AND
LEVEL PROBE
0
120V
230V
120/208V &
120/240V - 3
wire w/ground
single phase
Location:
The liquid level board is located on the left rear of
the component bracket. The level probe is located on
the right rear of the component bracket.
0
230V - 2 wire
w/ground
single phase
Test Procedures:
1. Disconnect the brewer from the power source.
2. Disconnect the blue wire (T1) and the pink wire
(T4).
3. Check the voltage across terminals (T2) and (T3)
with the ON/OFF switch in the "ON" position. The
indication must be:
0
0
208V or
240V
208V or 240V -
2 wire wground
single phase
0
0
220V or
254V
280V or 440V -
4 wire w/ground
3 phase
a) 120 volts ac for 120/208 volt, 120/240 volt and
380 volt models.
b) 208 volts ac or 240 volts ac for two wire 208
volt or 240 volt models.
d) 230 volts ac for two wire 230 volt models.
e) 220 volts ac or 440 volts ac for four wire 280
volt or 440 volt machines.
0
120V
380V - 3 wire
w/ground 3
phase w/
stepdown trans-
former
4. Disconnect the brewer from the power source.
If voltage is present as described, proceed to #5.
If voltage is not present as described, refer to Wiring
Diagrams and check the brewer wiring harness.
8. Disconnect the brewer from the power source and
remove the jumper wire from terminal 4.
If voltage is present as described, liquid level board
is operating properly, proceed to #9.
If voltage is not present as described, replace the
liquid level board.
5. Reconnect the blue wire to T1 on the liquid level
board.
6. Carefully connect a piece of insulated jumper wire
to terminal 4. Keep the other end of this wire away
from any metal surface of the brewer.
10060 080900
Page 20
SERVICE (cont.)
14. Disconnect the brewer from the power source.
LIQUID LEVEL BOARD AND LEVEL PROBE (cont.)
9. Reconnect the pink wire to terminal 4.
10. Remove the two #8-32 screws securing the level
probe to the component bracket.
11. Gentlypulltheprobeoutofthecomponentbracket
and inspect for corrosion. Replace if necessary.
12 Place the probe so that neither end is in contact
with any metal surface of the brewer.
If voltage is present as described, reinstall the level
probe, the liquid level board and level probe are op-
erating properly.
If voltage is not present as described, check the
pink wire on the level probe from liquid level board
terminal 4.
13. Connect the brewer to the power source. Check
the voltage across terminals 1 and 3, refer to
chart below. There is an approximate delay of five
seconds for output to stabilize.
Removal and Replacement:
1. Remove all wires from the liquid level board.
2. Removethe#10-32screwandflatwashersecuring
the protective shield to the component bracket.
3. Remove the #10-32 screw and internal tooth
lockwasher securing the liquid level board to the
component bracket.
4. Remove liquid level board and discard.
5. Installnewliquidlevelboardoncomponentbracket
and secure with a #10-32 screw and internal tooth
lockwasher.
Voltage -
Jumper
Touching
Frame
Voltage -
Jumper
Not Touching
Frame
Model
0
120V
230V
120/208V &
120/240V - 3
wire w/ground
single phase
6. Install protective shield and secure with #10-32
screw and flat washer.
7. Refer to Fig. 13 and reconnect the wires.
0
230V - 2 wire
w/ground
T1 BLU to Solenoid Valve
single phase
T2 BLK to ON/OFF Switch (All models
except 230V-CE models)
0
0
208V or
240V
208V or 240V -
2 wire wground
single phase
T3 WHI to Main Harness
(120/208V, 120/240V,
four wire 380V and 440V
models)
T3 WHI to Transformer
(380V three wire models)
T3 RED to Main Harness
(208V, 240V single phase
and three phase models)
T3 BLK to Main Harness
(230V two wire models)
0
0
220V or
254V
280V or 440V -
4 wire w/ground
3 phase
0
120V
380V - 3 wire
w/ground 3
phase w/
stepdown trans-
former
T4 PIN to Level Probe
P1733
FIG.13 LIQUID LEVEL BOARD TERMINALS
10060 080900
Page 21
SERVICE (cont.)
ON/OFF SWITCH
5. Disconnect the wires on the ON/OFF switch.
6. a) 120/208V, 120/240V, 208V, 240V, 380V and
440V Models - Check for continuity across the
terminals on the rear of the switch with the switch
in the "ON" (upper) position. Continuity must not
be present when the switch is in the "OFF" (lower)
position.
b) 230V - CE Models - Check for continuity across
the center terminal (2) and the lower terminal (1)
when the switch is in the "ON" (upper) position.
Continuity must not present when the switch is in
"OFF" (lower) position.
P2209.60
FIG.14 ON/OFF SWITCH
Location:
The ON/OFF switch is located on the left side of the
switchmountingbracket.Theswitchmountingbracket
is mounted on the front of the component bracket.
If continuity is present as described, the switch is
operating properly.
If continuity is not present as described, replace the
switch.
Test Procedures:
1. Disconnect the brewer from the power source.
2. a)120/208V, 120/240V, 208V and 240V Models
Remove the black wire on the ON/OFF switch from
the fuse holder or circuit breaker and the red wire
on the power indicator light.
Removal and Replacement:
1. Remove the wires from the switch terminals.
2. Compress the clips on the back side of the switch
mounting bracket and gently push the through the
opening.
b) 380V and 440V Models - Remove the black wire
on the ON/OFF switch from the fuse holder or
circuit breaker and the white wire from the power
indicator light.
3. Push the new switch into the opening and spread
the clips to hold switch in the mounting bracket.
NOTE: ON 230V - CE models terminal (3) must be
on the top.
c) 230V - CE Models - Remove the red wire on the
ON/OFF switch from the fuse holder and the black
wire on the power indicator light.
4. Refer to Fig. 15 and reconnect the wires.
BLK from Main Harness
3. Connect the brewer to the power source. With a
voltmeter, check the voltage across the removed
wires. The indication must be:
a) 120 volts ac for 120/208 volt, 120/240 volt and
380 volt models.
b) 208 volts ac for two or three wire 208 volt
models.
BLK to Start Switch, Brew
Timer & Liuqid Level Board
L2
c)240voltsacfortwowire240voltmodelspriorto
#U300004095 and three wire 240 volt models.
d) 230 volts ac for two wire 230 volt models
#U300004095 and up).
e) 208 or 240 volts ac for four wire 440 volt mod-
els.
120/208V, 120/240V, 208V, 240V, 380V AND 440V
MODELS
BLK from Main Harness
RED to Main Harness
4. Disconnect the brewer from the power source.
RED to Start Switch, Brew
Timer & Liquid Level Board
If voltage is present as described, reconnect the wires
and proceed to #5
Ifvoltageisnotpresentasdescribed,refertotheWiring
Diagrams and check the brewer wiring harness.
230V - CE Models
P1735
FIG. 15 ON/OFF SWITCH TERMINALS
10060 080900
Page 22
SERVICE (cont.)
PUMP ASSEMBLY
Removal and Replacement (Refer to Fig. 17):
1. Disconnect the wires from the pump assembly.
2. Loosen the #8-32 screw (2) securing the clamp
(3) on the fill tube (1) and slide the clamp (3) up
the fill tube (1).
3. Disengagethefilltube(1)fromthepumpassembly
(4).
4. Remove the four #8-32 screws (6) securing the
pump assembly (4) to the component bracket
(7).
5. Remove pump assembly (4).
6. Remove pump gasket (5) and inspect, replace if
necessary.
P2209.60
FIG.16 PUMP ASSEMBLY
7. Position gasket (5) on component bracket (7).
8. Install new pump assembly (4) on component
bracket (7) and secure with four #8-32 screws
(6).
Location:
The pump is located on the center rear of the
component bracket.
9. Install fill tube (1) on pump assembly (4).
10. Slide clamp (3) down into position on the fill tube
(1) and tighten screw (2).
Test Procedures:
1. Disconnect the brewer from the power source.
2. Disconnect the black wire from the black lead on
the pump and the white wire from the black lead
on the pump.
11. Refer to Fig. 17 and reconnect the wires.
3. With a voltmeter, check the voltage across the
black wire and the white wire. Connect the brewer
to the power source. The indication must be:
a)120voltsacforthreewire120/208volt,120/240
volt and 380 volt models).
WHI from Brew Timer
BLK from Brew Timer
1
2
b) 208 volts ac for two or three wire 208 volt
models.
c) 240 volts ac for two or three wire 240 volt
models.
3
6
d) 230 volts ac for two wire 230 volt models.
e) 208 or 240 volts ac for four wire 440 volt mod-
els
4
5
4. Disconnect the brewer from the power source.
7
If voltage is present as described, reconnect the wires
to the pump. Install swing spout and position over the
reservoir.PlacetheON/OFFinthe"ON"(upper)position
and push the start switch and release. If pump does
not run, replace the pump.
Ifvoltageisnotpresentasdescribed,refertotheWiring
Diagrams and check the brewer wiring harness.
P1737
FIG.17 PUMP INSTALLATION
10060 080900
Page 23
SERVICE (cont.)
RELAY (BREWERS W/BREW LOCKOUT)
If continuity is present as described, reconnect the
wires, the relay is operating properly.
If continuity is not present as described, replace the
relay.
230V - CE Models
1. Disconnect the brewer from the power source.
2. Disconnect the black wire from relay terminal "A"
and the red wire from relay terminal "B". Check
the voltage across the black and red wire with a
voltmeter.Connectthebrewertothepowersource.
The indication must be 230 volts ac.
If voltage is present as described, proceed to #3.
If voltage is not present as described, refer to the Wir-
ing Diagrams and check the brewer wiring harness.
3. Disconnect the brewer from the power source.
4. Check for continuity across relay terminals "A" &
"B"
P1731.55
FIG.18 RELAY
Location:
The relay is located on the front part of the com-
ponent bracket, mounted on the top of the timer
bracket.
If continuity is present as described, reconnect the
wires to terminals "A" & "B" and proceed to #5.
If continuity is not present as described, replace the
relay.
Test Procedures:
All Models Except 230V - CE Models
1. Disconnect the brewer from the power source.
2. Disconnect the wires from relay terminals "A" &
"B". Check for continuity between terminals "A" &
"B".
5. With the thermostat in the "ON" position and the
relay engaged disconnect the brewer from the
power source.
6. Disconnect the blue wires from relay terminals 1
and 7. Check for continuity across terminals 1 and
7.
If continuity is present as described, reconnect the
wires to terminals "A" & "B" and proceed to #3.
If continuity is not present as described replace the
relay.
If continuity is present as described, proceed to #7
If continuity is not present as described, replace the
relay.
3. Disconnect the wires from relay terminals 2 & 7.
4. Check for continuity across terminals 2 & 7.
7. Turn the thermostat to the "OFF" position, con-
nect the brewer to the power source and turn the
thermostat back to the "ON" position. Continuity
should not be present across terminals 1 & 7.
If continuity is present as described, reconnect the
wires to terminals 2 & 7 and proceed to # 5.
If continuity is not present as described, replace the
relay.
If continuity is not present as described, the relay is
operating properly.
If continuity is present as described, replace the
relay.
5. Disconnect the wires from relay terminals 5 & 7.
6. Check for continuity across terminals 5 & 7 by
manually closing relay contact. Continuity must
not be present when contact is released.
10060 080900
Page 24
SERVICE (cont.)
RELAY (BREWERS W/BREW LOCKOUT)
BLU from
Start Switch
BLU from
Brew Timer
Removal and Replacement:
3
1. Disconnect the wires from the relay.
2. For 120/208V, 120/240V, 208V, 380V, 440V and
240V models prior to #U300004095 remove the
#6-32screwsecuringtherelaytotherelaymount-
ing bracket. For 230V models #U300004095 and
up, remove the two screws securing the relay to
the relay mounting bracket.
2
1
4
B
7
BLK to Control
Thermostat
A
RED from
Main Harness
120/208V, 120/240V, 208V, 380V, 440V AND 240V
MODELS PRIOR TO #U300004095
3. Remove relay and discard.
4. For 120/208V,120/240V, 208V, 380V, 440V and
240V models prior to #U300004095, install new
relay on relay mounting bracket and secure with
a #6-32 screw. For 230V models #U300004095
andup,installnewrelayonrelaymountingbracket
and secure with two #6-32 screws.
BLU to Start
Switch
BLU from
Brew Timer
3
2
6
1
5
5. Refer to Fig. 19 and reconnect the wires.
4
8
RED to Control
7
Thermostat
A
BLK from
Main Harness
230V MODELS #U300004095 AND UP
P1739
FIG.19 RELAY TERMINALS
10060 080900
Page 25
SERVICE (cont.)
SELECTOR SWITCH (HALF BATCH OPTION)
Removal and Replacement:
1. Remove the wires from the switch terminals.
2. Compress the clips on the back side of the switch
mounting bracket and gently push the through the
opening.
3. Push the new switch into the opening and spread
the clips to hold switch in the mounting bracket.
4. Refer to Fig. 21 and reconnect the wires.
P1317.30
FIG. 20 SELECTOR SWITCH (HALF BATCH)
Location:
GRY to Brew Timer
PNK to Brew Timer
The selector switch is located in the upper center
of the switch mounting panel.
Test Procedures:
1. Disconnect the brewer from the power source.
2. Disconnect the wires from the switch terminals.
3. Check for continuity across the switch terminals
with the switch in the "CLOSED" (left - half) posi-
tion. Continuity must not present when the switch
is in the "OPEN" (right - full) position.
P1740
FIG. 21 SELECTOR SWITCH TERMINALS
If continuity is present as described, the switch is
operating properly.
If continuity is not present as described, replace the
switch.
10060 080900
Page 26
SERVICE (cont.)
SOLENOID
C) For 230V - CE two wire single phase models,
disconnect the red wire from the liquid level board
#2 and the black wire from the solenoid. With a
voltmeter,checkthevoltageacrosstheredwireand
the black wire. Connect the brewer to the power
source. The indication must be 230 volts ac.
3. Disconnect the dispenser from the power
source.
If voltage is present as described, proceed to #4.
Ifvoltageisnotpresentasdescribed,refertothebrewer
Wiring Diagrams and check the wiring harness.
P2209.60
FIG. 22 SOLENOID
4. Disconnect the blue wire and the white wire, the
blue wire and the red wire or blue wire and black
wire from the solenoid terminals.
5. Check for continuity across the solenoid valve coil
terminals.
Location:
The solenoid is mounted on the upper left rear of
the component bracket.
Test Procedures:
1. Disconnect the dispenser from the power
source.
If continuity is present as described, reconnect the
wires to the solenoid.
2. A) For 120/208 volt and 120/240 volt three wire,
single phase models, 380 volt three wire, three
phase models and 380 volt, 440 volt four wire,
three phase models, disconnect the black wire
from the liquid level board #2 and the white wire
onthesolenoid.Withavoltmeter,checkthevoltage
across the black and the white wire. Connect the
brewer to the power source. The indication must
be:
If continuity is not present as described, replace the
solenoid valve.
6. Check the solenoid valve for coil action. Connect
thedispensertothepowersource. Listencarefully
in the vicinity of the solenoid valve for a "clicking"
sound as the coil magnet attracts.
If the sound is heard as described and water will not
pass through the solenoid valve, there may be a block-
age in the water line before the solenoid valve or, the
solenoid valve may require inspection for wear, and
removal of waterborne particles.
If the sound is not heard as described, replace the
solenoid valve.
a) 120 volts ac for 380 volt three wire, three phase
models and 208 0r 240 volts ac for four wire three
phase 440 volt models.
b) 208 volts ac for three wire 120/208 volt mod-
els.
c) 240 volts ac for three wire 120/240 volt mod-
els.
B) For 208 volt, 240 volt two wire single phase and
208 volt, 240 volt three wire three phase models,
disconnect the black wire from the liquid level
board #2 and the red wire from the solenoid. With
avoltmeter, checkthe voltageacrosstheblackand
redwires.Connectthebrewertothepowersource.
The indication must be:
a) 208 volts ac for 208 volt two wire single phase
and 208 volt three wire three phase models.
b) 240 volts ac for 240 volt two wire single phase
and 240 volt three wire three phase models.
Removal and Replacement:
1. Remove the wires from the solenoid valve.
2. Turn off the water supply to the dispenser.
3. Disconnect the water inlet line from the connector
on the solenoid valve.
4. Remove the #10-32 screw and the flat washer
securing the liquid level board, shield and the
solenoid to the component bracket.
5. Remove solenoid, connectors, air chamber and
tank inlet tube as an assembly.
10060 080900
Page 27
SERVICE (cont.)
SOLENOID
WHI from Main Harness
(120/208V,120/240V,380V
and 440V Models)
BLU from Liquid Level
Board #1
6. Remove the tank inlet tube grommet and dis-
card.
RED from Main Harness
(208V and 240V Models)
7. Install new tank inlet tube grommet.
8. Install new solenoid assembly.
9. Installliquidlevelboard,shieldandsecuresolenoid
assembly and shield to the component bracket
with a #10-32 screw and flat washer..
10. Install water inlet tube to connector on the sole-
noid.
EARLY MODELS
11. Turn on the water supply to the brewer.
12. Refer to Fig. 23 and reconnect the wires.
BLU from Liquid
Level Board #1
BLK from Main Har-
ness
EARLY 230V - CE MODELS
LATE MODELS
WHI from Main Harness
(120/208V,120/240V,380V
and 440V Models)
BLU from Liquid Level
Board #1
RED from Main Harness
(208V and 240V Models)
P1741
FIG. 23 SOLENOID TERMINALS
10060 081106
Page 28
SERVICE (cont.)
START SWITCH (BREW)
Removal and Replacement:
1. Remove the wires from the switch terminals.
2. Compress the clips on the back side of the switch
mounting bracket and gently push the through the
opening.
3. Push the new switch into the opening and spread
the clips to hold switch in the mounting bracket.
4. Refer to Fig. 25 and reconnect the wires.
BLU to Brew Timer or
Brew Lockout Relay
P1317.30
FIG. 24 START SWITCH (BREW)
Location:
The brew start switch is located on the upper right
side of the brewer component housing.
BLK from ON/OFF Switch
Test Procedures:
ALL MODELS EXCEPT 230V - CE MODELS
1. Disconnect the brewer from the power source.
2. Remove the wires from the start switch termi-
nals.
3. Check for continuity across the switch terminals
when the switch is held in the lower position.
Continuity must not be present when the switch
is in the upper position.
BLU to Brew Timer or
Brew Lockout Relay
RED from ON/OFF
Switch
230V - CE MODELS
P1743
If continuity is present as described, reconnect the
wires the switch is operating properly.
FIG.25 BREW START SWITCH TERMINALS
If continuity is not present as described, replace the
switch.
10060 031599
Page 29
SERVICE (cont.)
TANK HEATERS
Test Procedures:
1. Disconnect the brewer from the power source.
2. Disconnect the wires from the tank heater.
3. Check for continuity across the tank heater termi-
nals.
If continuity is present as described, proceed to #4.
If continuity is not present as described, replace the
tank heater.
Removal and Replacement:
1. Remove the wires or thermal fuses from the tank
heater.
2. Remove the four #8-32 screws securing the tank
heater to the component bracket.
3. Remove tank heater and gasket.
4. Positionnewtankheaterandgasketonthecompo-
nent bracket and secure with four #8-32 screws.
5. Refer to Fig. 27 and reconnect the wires.
P2209.60
FIG. 26 TANK HEATER
Location:
The tank heaters are located on the right center
and the left center of the component bracket.
RED to Contactor T2 (All
Models Except 230V-CE
Models)
BLK to Contactor T1 (All
Models Except 230V-CE
Models)
RED (Thermal Fuse) to Con-
tactor Top Right Terminal)
(230V-CE Models)
BLK (Thermal Fuse) to
ContactorTopLeftTermi-
nal) (230V-CE Models)
BLK to Contactor L1
(120/208V,120/240Three
Wire Single Phase, 208V
and 240V Two Wire,
Single Phase)
RED to Contactor L2
(120/208V, 120/240 Three
Wire Single Phase, 208V
and240VTwoWire,Single
Phase)
BLU to Main Harness
(208V, 240V, 380V Three
Wire ,Three Phase and
380V,440V Four Wire,
Three Phase
BLU to Main Harness
(208V, 240V, 380V Three
Wire ,Three Phase and
380V,440V Four Wire,
Three Phase
BLK (Thermal Fuse to
Contactor Lower Left
Terminal)(230V-CEMod-
els)
RED (Thermal Fuse) to
Contactor Lower Right
Terminal)
RIGHT
LEFT
P1746
FIG. 27 TANK HEATER TERMINALS
10060 031599
Page 30
SERVICE (cont.)
TIMER (Early Models)
THERMAL FUSES (230V-CE MODELS ONLY)
2
J
1
J
1
2
T
TL
4
TL
TL
L5
T
OLD STYLE
FIG. 29 TIMER
P1722.55
P1750.65
FIG. 28 THERMAL FUSES
Location:
Location:
The timer is located on the front center of the
component bracket.
The thermal fuses are mounted on the tank heater
terminals and the contactor terminals.
Test Procedures:
Test Procedures:
1. Disconnect the brewer from the power source.
2. Disconnectthepolarized,threepinconnectorfrom
the brewer main harness and rotate the brew timer
dial fully counterclockwise.
3. With a voltmeter, check the voltage across sockets
P2 and P3 (white and black wire or red wire) of
the female connector on the main wiring harness
when the "ON/OFF" switch is in the "ON" (upper)
position. Connect the brewer to the power source.
The indication must be:
1. Disconnect the brewer from the power source.
2. Disconnect the thermal fuse from the tank heater
terminal and the contactor terminal.
3. Check for continuity across the terminals on the
ends of the thermal fuse.
If continuity is present as described, the thermal is
operating properly.
If continuity is not present as described, replace the
thermal fuse.
a)120voltsacforthreewire120/208volt,120/240
volt, 380 volt models and 208 or 240 volts ac for
four wire 440 volt models.
b) 208 volts ac for two and three wire 208 volt
models.
c) 240 volts ac for two and three wire 240 volt
models.
Removal and Replacement:
1. Disconnect the thermal fuse from the tank heater
terminal and the contactor and discard.
2. Connect the new thermal fuse to the tank heater
terminal and the contactor terminal.
d) 230 volts ac for two wire 230 volt CE models.
4. Disconnect the brewer from the power source.
If voltage is present as described, proceed to #5.
Ifvoltageisnotpresentasdescribed,refertotheWiring
Diagrams and check the brewer wiring harness.
10060 080900
Page 31
SERVICE (cont.)
Removal and Replacement:
1. Separateallconnectorsbetweenthebrewerwiring
harness and the timer.
2. Disconnect the timer leads from the pump
leads.
3. Remove the two #8-32 screws securing the brew
timer to the component bracket and remove
timer.
4. InstallnewtimercircuitboardasdescribedinLate
Model Timer section on the following pages.
5. Refer to Fig. 33 to reconnect the wires.
6. Install the Timer Setting Decal, provided with the
timer replacement kit, on the back of the front
access panel.
TIMER (Early Models)(cont.)
5. With a voltmeter, check the voltage across the
sockets P1 and P2 (blue and white wires) of the
female connector on the main harness when the
"ON/OFF" switch is in the "ON" (upper) position
and the start switch pressed. Connect the brewer
to the power source. The indication must be:
a)120voltsacforthreewire120/208volt,120/240
volt, 380 volt models and 208 or 240 volt ac for
four wire 440 volt models.
b) 208 volts ac for two and three wire 208 volt
models.
c) 240 volts ac for two and three wire 240 volt
models.
7. Adjust the timer as required. Refer to Late Model
Timer section on the following pages.
d) 230 volts ac for two wire 230 volt CE models.
6. Disconnect the brewer from the power source.
7. Reconnect the three pin connector from the main
wiring harness to the connector on the timer.
If voltage is present as described, proceed to #8.
Ifvoltageisnotpresentasdescribed,refertotheWiring
Diagrams and check the brewer wiring harness.
Three Pin Connector from
Half/Full Batch Switch
8. Disconnect the black and white wires to the
pump.
9. With a voltmeter, check the voltage across the
black and white wires when the "ON/OFF" switch
is in the "ON" (upper) position and the start switch
pressedtothestartpositionandreleased.Connect
the brewer to the power source. The indication
must be:
To Three Pin Female
Connector on Main
Harness
a)120voltsacforthreewire120/208volt,120/240
volt, 380 volt and 208 or 240 volt ac for four wire
440 volt models.
b) 208 volts ac for two and three wire 208 volt
models.
BLK to Pump
Lead
c) 240 volts ac for two and three wire 240 volt
models.
d) 230 volts ac for two wire 230 volt CE models.
WHI to Pump Lead
OLD STYLE
P1751
FIG. 31 TIMER TERMINALS
If voltage is present as described, the brew timer is
operating properly. Reset the timer dial as required,
to obtain the desired brew volume.
If voltage is not present as described, replace the
timer.
10060 080900
Page 32
SERVICE (cont.)
6. Withavoltmeter,checkthevoltageacrossterminals
TL1 and TL4 when the "ON/OFF" switch is in the
"ON" position. Connect the brewer to the power
source. The indication must be 0 volts.
DIGITAL TIMER (Late Models)
If voltage is as described, proceed to #7.
If voltage is not as described, disconnect the brewer
from the power source and replace the timer.
7. With a voltmeter, check the voltage across ter-
minals TL1 and TL4 when the "ON/OFF" switch
is in the "ON" position. Connect the brewer to the
power source and press the "START" switch. The
indication must be as follows:
a)120voltsacforthreewire120/208volt,120/240
volt and 380 volt models.
b) 208 volts ac for two wire 208 volt models.
c) 240 volts ac for two wire 240 volt models.
d) 230 volts ac for two wire 230 volt CE models.
e) 208 or 240 volts ac for four wire 440 volt mod-
els.
P2209.60
FIG. 32 DIGITAL TIMER
Location:
The timer is located on the front center of the
component bracket.
Test Procedure.
If voltage is present as described, the brew timer is
operating properly. Reset the timer as required, to
obtain the desired brew volume.
If voltage is not present as described, disconnect the
brewer from the power source and replace the timer.
NOTE:Donotremoveorinstallwireswhiletimerboard
is installed. Pressure applied to one side may cause
damage to the board.
1. Disconnect the brewer from the power source.
2. Remove the two #8-32 screws securing circuit
board to the mounting bracket.
Removal and Replacement:
3. Remove circuit board and spacers (as required).
4. Withavoltmeter,checkthevoltageacrossterminals
TL1 and TL2 when the "ON/OFF" switch is in the
"ON" position. Connect the brewer to the power
source. The indication must be:
1. Remove the two #8-32 screws securing circuit
board to the mounting bracket.
2. Remove circuit board and spacers (as required).
3. Remove all wires from the timer.
4. Attach all wires to the replacement timer board
prior to installation to the component mounting
bracket. Refer to FIG. 33 when reconnecting the
wires.
5. Installnewcircuitboardwithspacers(asrequired)
to the component mounting bracket.
a)120voltsacforthreewire120/208volt,120/240
volt and 380 volt models.
b) 208 volts ac for two wire 208 volt models.
c) 240 volts ac for two wire 240 volt models.
d) 230 volts ac for two wire 230 volt CE models.
e) 208 or 240 volts ac for four wire 440 volt mod-
els.
6. Adjust the timer as described below.
Timer Setting:
5. Disconnect the brewer from the power source.
NOTE: Prior to setting or modifying volumes, check
that the brewer is connected to water supply, the
tank is properly filled, and a funnel and server are in
place.
If voltage is present as described, proceed to #6.
Ifvoltageisnotpresentasdescribed,refertotheWiring
Diagrams and check the brewer wiring harness.
10060 080900
Page 33
SERVICE (cont.)
DIGITAL TIMER (Late Models)
NOTE: The brewer remembers this volume and will
continue to brew batches of this size until the volume
setting procedure is repeated.
NOTE: All volume settings must be done with the
sprayhead installed.
NOTE: When brewing coffee, volume will decrease
due to absorption by the coffee grounds.
NOTE: Half-Batch and full batch settings must each
be set separately.
1. Modifying brew volumes. To modify a brew vol-
ume, first check that the SET/LOCK switch is in the
“SET” position on the circuit board.
To increase a brew volume, place the ON/OFF
switch in the “ON” position, press and hold the START
switch until you see three breaks in the water stream
from the swing arm. Release the switch and press it
again one or more times. (Failure to release the switch
within two seconds after the third break in the water
stream causes the volume setting to be aborted and
previous volume setting will remain in memory.) Each
time the switch is pressed, two seconds are added to
the brew time period. Allow the brew cycle to finish
in order to verify that the desired volume has been
achieved.
3. Setting programming disable feature. If it be-
comes necessary to prevent anyone from changing
brew time once programmed, you can set the SET/
LOCK switch to the “LOCK” position. This will prevent
any further programming until switch is once again
put into the “SET” position.
To decrease a brew volume, place the ON/OFF
switch in the “ON” position, press and release the
START switch once for every two-second interval
to be removed from the total brew time period; then
immediately press and hold down the START switch
until you see three breaks in the water stream from the
swing arm. Release the switch. (Failure to release the
switch within two seconds after the third break in the
water stream causes the volume setting to be aborted
and previous volume setting will remain in memory).
Allow the brew cycle to finish in order to verify that
the desired volume has been achieved.
2. Setting brew volumes. To set a brew volume,
first check that the SET/LOCK switch is in the “SET”
position on the circuit board. Place the ON/OFF switch
in the “ON” position, press and hold the START switch
until you see three breaks in the water stream from
the swing arm and then release the switch. (Failure to
release the switch within two seconds after the third
break in the water stream causes the volume setting
to be aborted and previous volume setting will remain
in memory.)
BLU/BLK wire from TL5 to P1
WHI/GRN wire from TL4 to (WHI) Pump
WHI/BLU wire from TL3 to (BLK) Pump
WHI wire from TL2 to P2
BLK wire from TL1 to P3
J2 - Three Pin connector from Half/Full Batch
Switch
View the level of the liquid being dispensed. When
the desired level is reached, turn the ON/OFF switch
to “OFF”.
P2037
FIG. 33 DIGITAL TIMER TERMINALS
10060 080900
Page 34
SERVICE (cont.)
TRANSFORMER (380V THREE WIRE MODELS ONLY)
If voltage is present as described, the transformer is
operating properly
If voiltage is not present as described, replace the
transformer.
Removal and Replacement:
1. Disconnect all the wires from the transformer.
2. Remove the two #8-32 screws securing the trans-
form to the transformer mounting bracket.
3. Remove the transformer and discard.
4. Positionnewtransformerontransformermounting
bracket and secure with two #8-32 screws.
5. Refer to Fig. 35 and reconnect the wires.
P1752.55
FIG. 34 TRANSFORMER
RED from
Terminal Block
WHI from Main
Harness
Location:
The transformer is located on the top rear of the
timer mounting bracket.
Test Procedures:
1. Disconnect the brewer from the power source.
2. Disconnect black wire and the red wire from the
terminal block at the transformer.
3. With a voltmeter, check the voltage across the
black wire and the red wire. Connect the brewer
to the power source. The indication must be 380
volts ac.
4. Disconnect the brewer from the power source.
If voltage is present as described, proceed to #5.
If voltage is not present as described, refer to wiring
diagram and check the brewer wiring harness.
BLK from
BLK from
Terminal Block
Main Harness
5. Reconnect the black wire and the red to the trans-
former.
6. Disconnect the black wire and the white wire from
the transformer terminals.
P1753
FIG. 35 TRANSFORMER TERMINALS
7. With a voltmeter, check the voltage across the
transformer terminals. Connect the brewer to the
power source. The indication must be 120 volts
ac.
10060 031599
Page 35
SERVICE (cont.)
MASTER ON/OFF SWITCH (Late Models)
Removal and Replacement:
1. Remove all wires from the switch terminals.
2. Remove the two screws from the outside of the
base and gently push the switch through the
opening.
3. Locate the new switch into the opening and se-
cure with screws removed in step 2.
4. Refer to FIG. 37 when reconnecting the wires.
Incoming Power Supply
L1 - BLK
P1752.55
L2 - RED
FIG. 36 MASTER ON/OFF SWITCH LOC.
Location:
Main Wiring harness
BLK
The Master ON/OFF switch is located in the top hous-
ing at the rear, FIG. 36.
RED
Test Procedure:
1. Disconnect the brewer from the power source
and remove the wires from all terminals of the
Master ON/OFF switch.
P3955
FIG. 37 MASTER ON/OFF SWITCH WIRING
2. Check for continuity across the two terminals on
the switch at L1 BLK and BLK to Main Harness
when it is held in the lower position, Fig. 32.
Check for continuity across the two terminals on
the switch at L2 RED and RED to Main Harness
when it is held in the lower position.
Continuity must not be present across these
terminals in the upper position.
If continuity is present as described, reconnect the
wires, the switch is operating properly.
If continuity is not present as described, replace the
switch.
10060 011708
Page 36
L1
N
L2
MAIN ON/OFF SWITCH
(Late Models only)
BLK
RED
120/208 VOLTS AC
120/240 VOLTS AC
3 WIRE + GND
SINGLE PHASE
10060 011708
Page 37
10060 080900
Page 38
SCHEMATIC WIRING DIAGRAM U3A & U38A
(BREWERS PRIOR TO U300004095)
10060 080900
Page 39
SCHEMATIC WIRING DIAGRAM U3A - CE
(BREWERS S/N U300004095 - UP)
10060 080900
Page 40
SCHEMATIC WIRING DIAGRAM U3833
10060 080900
Page 41
SCHEMATIC WIRING DIGRAM U3833
10060 080900
Page 42
|