ABB POWERVALUE 11 T G2 6 KVA B User Manual

USER MANUAL  
PowerValue 11 T G2  
6 kVA B / 6 kVA B2 / 6 kVA S  
10 kVA B / 10 kVA B2 / 10 kVA S  
CONTENTS  
3
Contents  
1
Important safety instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
1.1  
1.2  
1.3  
1.4  
1.5  
Operator precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
Environmental considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
Declaration of safety conformity and CE marking . . . . . . . . . . . . . . . . . . . . . . . . . .6  
Inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6  
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6  
2
3
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7  
2.1  
UPS disposal and recycling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8  
2.1.1 For professional users in the European Union . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
2.1.2 For disposal in countries outside of the European Union . . . . . . . . . . . . . . . . . . . . 8  
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
3.1  
3.2  
3.3  
3.4  
Delivery, transportation, positioning and storage . . . . . . . . . . . . . . . . . . . . . . . . . .9  
3.1.1 Receipt of the UPS and visual inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
3.1.2 Unpacking list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
3.1.3 Storage of UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Site planning and positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
3.2.1 Planning before the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
3.2.2 Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
3.2.3 Standalone / tower installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
General characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
3.3.1 UPS 6-10 kVA S. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
3.3.2 UPS 6-10 kVA B/B2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
3.3.3 External battery module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14  
Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
3.4.1 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15  
3.4.2 Recommended cable sections and fuse ratings . . . . . . . . . . . . . . . . . . . . . . . . .15  
3.4.3 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
3.4.4 Parallel installation operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
4
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
4.1  
Control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
4.1.1 Selection keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
4.1.2 LED’s status indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
4.1.3 LCD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
4.2 Operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
4.3 UPS start-up and shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
4.3.1 UPS start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23  
4.3.2 UPS shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23  
4.4 Display functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
4.5 User settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
4.6 LCD operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
4.6.1 Main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26  
4.6.2 UPS status menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26  
4.6.3 Measurement menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27  
4.6.4 Event log menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27  
4.6.5 Control menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28  
4.6.6 Identification menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28  
4.6.7 Setting menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29  
4
ABB UPS PRODUCTS AND SOLUTIONS  
5
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
5.1  
5.2  
5.3  
RS-232 port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
USB port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Emergency power off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
5.3.1 Dry IN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
5.3.2 Dry OUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
5.4 Network management card (optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32  
5.4.1 Installing a serial network management card (optional). . . . . . . . . . . . . . . . . . . .32  
5.4.2 Monitoring software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32  
6
7
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
6.1  
6.2  
Fault identification and rectification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
Accessing alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
UPS status menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33  
Event log menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33  
Silencing the alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
6.3  
Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
Appendix A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
Appendix B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40  
1
IMPORTANT SAFET Y INSTRUC TIONS  
5
1 Important safety instructions  
READ THIS IMPORTANT SAFETY INSTRUCTION CHAPTER BEFORE READING THE OPERATING MANUAL  
1.1 Operator precautions  
Always follow the precautions and instructions  
DO NOT REMOVE ANY SCREWS FROM THE  
UPS SYSTEM OR FROM THE BATTERY  
CABINET: DANGER OF ELECTRICAL SHOCK.  
described in this manual. Any deviations from the  
instructions may result in electric shock or cause  
accidental load loss.  
DANGER  
DANGER  
HIGH FAULT CURRENTS (LEAKAGE  
CURRENTS). BEFORE CONNECTING THE  
MAINS ENSURE THAT THE UPS IS EARTHED!  
ABB DOES NOT TAKE ANY RESPONSIBILITY FOR  
DAMAGES CAUSED THROUGH INCORRECT USE  
OF THE UPS SYSTEM.  
DISPLAY A WARNING LABEL ON ALL  
PRIMARY POWER ISOLATORS INSTALLED  
AWAY FROM THE UPS AREA TO WARN  
ELECTRICAL MAINTENANCE PERSONNEL  
THAT THE CIRCUIT FEEDS A UPS.  
MAKE SURE THAT WARNING LABEL  
CONTAINS THE FOLLOWING TEXT OR  
EQUIVALENT: “ISOLATE THE UPS  
(UNINTERRUPTIBLE POWER SUPPLY)  
BEFORE WORKING ON THIS CIRCUIT.”  
DANGER  
1.2 Environmental considerations  
To operate the UPS with optimal efficiency,  
your installation site should meet the  
environmental parameters outlined in this user  
manual. Excessive amounts of dust or moisture  
in the operating environment may cause  
damage or lead to malfunction. The UPS should  
always be protected from the weather and  
sunshine. The operating environment must  
meet the weight, airflow, size and clearance  
requirements specified in the technical  
datasheet.  
Under no circumstances should the UPS be  
installed in an airtight room, in the presence  
of flammable gases, or in an environment  
exceeding the environmental requirements  
specified below. An ambient temperature of  
+20°C to +25°C is recommended to achieve a  
long life of the UPS and batteries. The cooling  
air entering the UPS must not exceed +40 °C  
and the humidity should be below 95 percent  
(non-condensing).  
6
ABB UPS PRODUCTS AND SOLUTIONS  
1.3 Declaration of safety conformity and CE marking  
The PowerValue 11 T G2 is designed, manufactured  
and commercialized in accordance with the  
EN ISO 9001 standard relating to quality  
management systems.  
These products also meet the following product  
standards:  
Table 1: Standards  
Product Standards  
These products conform with the following  
directives:  
• 2014/35/EU Low voltage directive  
• 2014/30/EU Electromagnetic Compatibility  
directive (EMC)  
Safety  
IEC/EN 62040-1: 2008+A1: 2013  
IEC/EN 62040-2: 2006  
IEC/EN 62040-3  
EMC  
Performance  
ESD  
IEC 61000-4-2: Level 3  
IEC 61000-4-3: Level 3  
IEC 61000-4-4: Level 4  
IEC 61000-4-5: Level 4  
IEC 61000-4-6: Level 3  
IEC 61000-4-8: Level 4  
IEC/EN50581:2012  
Radiated field  
EFT  
• 2011/65/EU Restriction of the use of certain  
hazardous substances (RoHS) directive  
Fast transients  
Electromagnetic field  
Conducted magnetic field  
RoHS  
1.4 Inquiries  
Inquiries regarding the UPS should be addressed  
ABB or authorized agent. The serial number is  
shown on the nameplate of the product.  
For further information on troubleshooting,  
see Chapter 6.  
to the local ABB office or agent authorized  
by ABB. Note the type code and the serial  
number of the equipment before contacting  
1.5 Operation  
DO NOT DISCONNECT THE MAINS CABLE  
FROM THE UPS OR THE BUILDING WIRING  
SOCKET DURING OPERATION AS THIS  
REMOVES THE GROUND FROM THE UPS  
AND ALL CONNECTED LOADS.  
INDISCRIMINATE OPERATION OF  
SWITCHES MAY CAUSE OUTPUT  
LOSS OR DAMAGE TO EQUIPMENT.  
WARNING  
WARNING  
NOTE  
PRESS THE OFF BUTTON TO FULLY  
DISCONNECT THE UPS. ENSURE THE UPS  
IS ON BYPASS OR ON STANDBY MODE  
BEFORE DISCONNECTING IT FROM  
THE MAINS.  
NEVER DISPOSE OF BATTERIES IN A FIRE  
AS THEY MAY EXPLODE.  
WARNING  
DO NOT OPEN OR DAMAGE THE  
BATTERIES.  
TO REDUCE THE RISK OF FIRE, CONNECT THE  
UPS TO A CIRCUIT PROVIDED WITH BRANCH  
CIRCUIT OVERCURRENT PROTECTION WITH  
AN AMPERE RATING IN ACCORDANCE WITH  
THE IEC/EN 60934 STANDARD OR YOUR  
LOCAL ELECTRICAL CODE.  
WARNING  
RELEASED ELECTROLYTE IS HARMFUL TO  
THE SKIN AND EYES.  
SEE TECHNICAL SPECIFICATIONS  
FOR RECOMMENDATIONS.  
WARNING  
NOTE  
1
IMPORTANT SAFET Y INSTRUC TIONS  
7
2 Maintenance  
PowerValue 11 T G2 UPS requires only minimal  
maintenance.  
COMPONENTS INSIDE THE UPS ARE  
CONNECTED TO THE BATTERY EVEN  
WHEN THE UPS IS DISCONNECTED FROM  
THE MAINS POWER SUPPLY.  
DANGER  
DANGER  
Charge the UPS regularly to maximize the  
expected life of the battery. When connected to  
mains power, the UPS charges the batteries and  
prevents the batteries from overcharging and  
over-discharging.  
DISCONNECT THE BATTERIES BEFORE  
CARRYING OUT ANY KIND OF SERVICE  
AND/OR MAINTENANCE. VERIFY THAT NO  
CURRENT IS PRESENT, AND NO  
HAZARDOUS VOLTAGE EXISTS IN THE  
CAPACITOR OR BUS CAPACITOR  
TERMINALS.  
• Replace the batteries when the battery service  
life has been exceeded (around three to five  
years at 25°C ambient temperature). Contact  
your local ABB or an agent authorized by ABB for  
replacements.  
THE BATTERY CIRCUIT IS NOT ISOLATED  
FROM THE INPUT VOLTAGE. HAZARDOUS  
VOLTAGES MAY OCCUR BETWEEN THE  
BATTERY TERMINALS AND THE GROUND.  
VERIFY THAT NO VOLTAGE IS PRESENT  
BEFORE SERVICING.  
DANGER  
• Charge the UPS once every four to six months  
if it is not used regularly.  
• In high-temperature regions, charge and  
discharge the battery every two months.  
The standard charging time should be at least  
12 hours.  
A BATTERY CAN PRESENT A RISK OF  
ELECTRICAL SHOCK AND HIGH SHORT  
CIRCUIT CURRENT. THE FOLLOWING  
PRECAUTIONS SHOULD BE OBSERVED  
WHEN WORKING ON BATTERIES:  
REMOVE WATCHES, RINGS OR OTHER  
METAL OBJECTS  
MAKE USE OF PROPER PPE (PERSONAL  
PROTECTION EQUIPMENT) AS PER  
LOCAL POLICIES AND RULES  
• Replace the battery when the discharge time  
is less than 50 percent of specified after fully  
charging. Check the battery connection or  
contact your local dealer to order a new battery.  
-
WEAR FLAME/ARC RESISTANT  
WHOLE BODY CLOTHING  
-
WEAR SUITABLE VOLTAGE RATED  
GLOVES  
DANGER  
-
-
-
USE SAFETY DIELECTRIC FOOTWEAR  
WEAR ARC FLASH FACE SHIELD  
USE VOLTAGE RATED TOOLS  
DO NOT LAY TOOLS OR METAL PARTS  
ON TOP OF BATTERIES  
DISCONNECT THE CHARGING SOURCE  
PRIOR TO CONNECTING OR  
DISCONNECTING BATTERY TERMINALS.  
REPLACE BATTERIES WITH THE SAME  
NUMBER AND SAME TYPE OF BATTERIES.  
WARNING  
WARNING  
REPLACE FUSES ONLY WITH FUSES OF  
THE SAME TYPE AND OF THE SAME  
AMPERAGE TO AVOID FIRE HAZARDS.  
8
ABB UPS PRODUCTS AND SOLUTIONS  
2.1 UPS disposal and recycling  
2.1.1 For professional users in the European Union  
2.1.2 For disposal in countries outside of the  
European Union  
THE CROSSED –OUT WHEELED BIN  
SYMBOL ON THE PRODUCT(S) AND / OR  
ACCOMPANYING DOCUMENTS MEANS  
THAT USED ELECTRICAL AND  
ELECTRONIC EQUIPMENT (WEEE)  
SHOULD NOT BE MIXED WITH GENERAL  
HOUSEHOLD WASTE.  
THE CROSSED –OUT WHEELED BIN  
SYMBOL IS ONLY VALID IN THE EUROPEAN  
UNION (EU) AND MEANS THAT USED  
ELECTRICAL AND ELECTRONIC EQUIPMENT  
(WEEE) SHOULD NOT BE MIXED WITH  
GENERAL HOUSEHOLD WASTE.  
IF YOU WISH TO DISCARD ELECTRICAL  
AND ELECTRONIC EQUIPMENT (EEE),  
PLEASE CONTACT YOUR DEALER OR  
SUPPLIER FOR FURTHER INFORMATION.  
IF YOU WISH TO DISCARD THIS PRODUCT  
PLEASE CONTACT YOUR LOCAL  
AUTHORITIES OR DEALER AND ASK FOR  
THE CORRECT METHOD OF DISPOSAL.  
DISPOSING OF THIS PRODUCT  
CORRECTLY WILL HELP SAVE VALUABLE  
RESOURCES AND PREVENT ANY  
POTENTIAL NEGATIVE EFFECTS ON  
HUMAN HEALTH AND THE ENVIRONMENT,  
WHICH COULD OTHERWISE ARISE FROM  
INAPPROPRIATE WASTE HANDLING.  
DISPOSING OF THIS PRODUCT  
CORRECTLY WILL HELP SAVE VALUABLE  
RESOURCES AND PREVENT ANY  
POTENTIAL NEGATIVE EFFECTS ON  
HUMAN HEALTH AND THE ENVIRONMENT,  
WHICH COULD OTHERWISE ARISE FROM  
INAPPROPRIATE WASTE HANDLING.  
3
INSTALL ATION  
9
3 Installation  
3.1 Delivery, transportation, positioning and storage  
3.1.1 Receipt of the UPS and visual inspection  
When receiving the UPS, carefully examine the  
packing container and the UPS for any signs of  
physical damage. In case of damage, notify the  
carrier immediately.  
Examine the UPS for any signs of damage and  
ensure that the received UPS corresponds to the  
material indicated in the delivery note. Notify  
your carrier or supplier immediately in case of  
any damage.  
The packing container of the UPS protects it from  
mechanical and environmental damage. To increase  
protection, the UPS is wrapped in a plastic sheet.  
Keep the packaging for later re-use.  
3.1.3 Storage of UPS  
If you plan to store the UPS prior to use, keep it  
in a dry, clean and cool storage room with an  
ambient temperature between -15 °C to +60°C  
and humidity of less than 95 percent (non-  
condensing). If the packing container has been  
removed, protect the UPS from dust. Always keep  
the UPS in an upright position and do not drop.  
3.1.2 Unpacking list  
After examining the package, open the box and  
check the following items are included:  
• 1 x PowerValue 11 T G2 UPS  
• 1 x user manual  
• 2 x UPS stands (support)  
(only for 6 kVA B/B2 & 10 kVA B/B2)  
• 4 x M4 round screw (UPS stands)  
• EPO contactor  
• Dry contactor  
• 1 x IEC C13-C14 cable  
• 1 x monitoring software CD  
• 1 x 15-pin communication cable  
(for parallel systems)  
• RS232 cable  
• 1 x USB cable  
10  
ABB UPS PRODUCTS AND SOLUTIONS  
3.2 Site planning and positioning  
3.2.1 Planning before the installation  
To ensure a long service life, install the unit  
in a position where any danger to the UPS is  
minimized:  
01 Stabilizer brackets  
preparation  
02 Stabilizer brackets  
installation  
• Install the UPS indoors.  
• Leave 50 cm of space on each side of the  
cabinet to allow cooling airflow and ensure  
that the circulation of air to the ventilation  
slits is not obstructed.  
• Avoid excessively high temperatures and  
excessive moisture.  
• Make sure that the surface is solid and flat.  
3.2.2 Positioning  
PowerValue 11 T G2 can only be installed in a  
standalone configuration.  
01  
WATER CONDENSATION MAY OCCUR IF  
THE UPS IS UNPACKED IN A VERY LOW  
TEMPERATURE. TO AVOID HAZARDS AND  
RISK OF ELECTRIC SHOCK, WAIT UNTIL  
THE UPS IS FULLY DRY BOTH INSIDE AND  
WARNING  
OUTSIDE BEFORE INSTALLING/USING  
THE UPS.  
3.2.3  
Standalone / tower installation  
3.2.3.1 UPS  
1. Place the unit on a flat, stable surface in its  
final location.  
2. Install ‘Stabilizer bracket’(optional): remove  
side’s screw from the unit, then install  
‘Stabilizer bracket’ to the unit.(figure 1).  
3. Install the unit to a surface(optional): place  
4pcs bolts(M8 is recommended) to the final  
location previously, bolt’s position please  
refer to below, then fix the unit to the bolts.  
02  
3
INSTALL ATION  
11  
3.2.3.2 External battery modules  
1. Install the EBM model (Refer to UPS model  
installation as privous described).  
03 EBM Connection  
04 EBM Connection  
2. Connect EBM to UPS with ‘Battery power cable’.  
FOR EACH UPS MAKE USE OF THE  
STANDARD MATCHING BATTERY  
CABINET; PLEASE REFER TO YOUR  
LOCAL SALES MANAGER / DEALER  
NOTE  
NOTE  
FOR DETAILS  
UP TO FOUR EXTERNAL BATTERY  
ENCLOSURES CAN BE CONNECTED TO  
THE UPS IN THE SAME WAY AS  
SHOWN ABOVE.  
03  
AFTER CONNECTING THE BATTERY  
ENCLOSURES, CONFIGURE THE  
NUMBER OF BATTERY MODULES IN  
THE CONTROL PANEL (FOR MORE  
INFORMATION SEE CHAPTER 4.6.7).  
SEE APPENDIX C FOR FURTHER  
DETAILS.  
NOTE  
04  
12  
ABB UPS PRODUCTS AND SOLUTIONS  
3.3 General characteristics  
3.3.1  
UPS 6-10 kVA S  
05 UPS front panel  
06 UPS 6 kVA S  
rear panel  
The figures below shows the front and the rear  
panel of the UPS 6-10 kVA S model.  
07 UPS 10 kVA S  
rear panel  
1
2
3
1
2
3
4
7
5
6
4
7
5
6
8
8
9
9
10  
10  
11  
12  
11  
12  
05  
06  
07  
Table 2: UPS 6-10kVA S model front and  
rear panel connectors and ports  
1
2
RS232  
RJ11 (PDU connection)  
[reserved for future development]  
3
EBM connector  
USB  
4
5
SNMP/Modbus/ AS400 slot  
Dry IN/OUT  
6
7
Parallel card  
8
EPO  
9
Fans  
10  
11  
12  
Maintenance bypass switch  
Input switch  
Input/Output terminals  
3
INSTALL ATION  
13  
3.3.2  
UPS 6-10 kVA B/B2  
08 UPS front panel  
09 UPS 6 kVA B/B2  
rear panel  
The figures below shows the front and the rear  
panel of the UPS 6-10 kVA B/B2 model.  
10 UPS 10 kVA B/B2  
rear panel  
1
2
3
1
2
3
4
7
5
6
4
7
5
6
8
8
9
9
10  
10  
11  
11  
12  
12  
08  
09  
10  
Table 3: UPS 6-10kVA B/B2 model front and  
rear panel connectors and ports  
1
2
RS232  
RJ11 (PDU connection)  
[reserved for future development]  
3
EBM connector  
USB  
4
5
SNMP/Modbus/ AS400 slot  
Dry IN/OUT  
6
7
Parallel card  
8
EPO  
9
Fans  
10  
11  
12  
Maintenance bypass switch  
Input switch  
Input/Output terminals  
14  
ABB UPS PRODUCTS AND SOLUTIONS  
3.3.3  
External battery module  
11 EBM front panel  
12 EBM rear panel  
The figures below shows the front and the rear  
panel of the external battery module.  
1
2
2
11  
12  
Table 4: External battery module (EBM) front  
and rear panel connectors and ports  
1
2
Fuse board cover (to replace EBM fuse)  
EBM connector  
3
INSTALL ATION  
15  
3.4 Electrical installation  
3.4.1  
Commissioning  
13 Circuit breaker  
14 External back-  
feed isolation  
RISK OF BACKFEED VOLTAGE. ISOLATE  
THE UPS BY INSTALLING AN EXTERNAL  
ISOLATING DEVICE BETWEEN THE MAINS  
INPUT AND THE UPS.  
The commissioning of the UPS includes the  
connection of the UPS and batteries, the verification  
of the electrical installation and operating  
environment of the UPS, the controlled start-up  
and testing of the UPS, and customer training.  
DANGER  
BEFORE WORKING ON THIS CIRCUIT,  
CHECK FOR HAZARDOUS VOLTAGE.  
ABB recommends that an external isolating  
device is installed between the mains input and  
UPS as shown in Figure 12 to protect against  
backfeed currents.  
DO NOT OPERATE IN CASE OF PRESENCE  
OF WATER OR MOISTURE.  
WARNING  
WHEN OPENING OR REMOVING THE UPS  
COVERS YOU ARE EXPOSED TO  
DANGEROUS VOLTAGES.  
AC contactor  
Input main breaker  
Line  
input  
Mains  
input  
Neutral  
DANGER  
3.4.2  
ratings  
Recommended cable sections and fuse  
Coil remote  
switch  
When selecting the cable cross-sections and the  
protective devices, follow the recommendations  
in the technical specifications document or follow  
local standards.  
AC Contactor:  
208-240 V, 63 A  
(PowerValue 11 T G2 6 kVA B/B2/S)  
208-240 V, 80 A  
14  
(PowerValue 11 T G2 10 kVA B/B2/S)  
TO REDUCE THE RISK OF FIRE, THE UNIT  
SHOULD ONLY CONNECT TO A CIRCUIT  
PROVIDED WITH BRANCH CIRCUIT  
OVERCURRENT PROTECTION FOR:  
D CURVE 63 A RATING (UPSTREAM  
CIRCUIT), FOR 6KVA MODELS,  
D CURVE 80 A RATING (UPSTREAM  
CIRCUIT), FOR 10KVA MODELS  
DANGER  
13  
Table 5: Recommended cable cross sections  
Model  
6 kVA (B/B2/S)  
10 kVA (B/B2/S)  
Protective  
earthing conductor (8 AWG)  
10 mm^2  
16 mm^2  
(6 AWG)  
(min. cross section)  
Input L, N, G  
(min conductor  
cross section)  
10 mm^2  
(8 AWG)  
16 mm^2  
(6 AWG)  
Input fuse  
63 A  
80 A  
Output L, N,  
(min. conductor  
cross section)  
10 mm^2  
(8 AWG)  
16 mm^2  
(6 AWG)  
16  
ABB UPS PRODUCTS AND SOLUTIONS  
3.4.3  
Connections  
L
OUT  
N
L
IN  
N
15 Terminal connections  
HIGH LEAKAGE CURRENT:  
MAKE SURE THAT THE EARTH WIRE IS  
CONNECTED.  
COMMON INPUT/OUTPUT SOURCES  
CONNECTION  
DANGER  
BEFORE CARRING OUT ANY CONNECTION,  
CHECK THAT THE UPSTREAM  
PROTECTION DEVICES (NORMAL AC  
SOURCE AND BYPASS AC SOURCES)  
ARE OPEN “0” (OFF).  
WARNING  
15  
To access the terminal blocks, remove the  
terminal block cover by unscrewing the two  
screws. Refer to the chapter 3.3 for the poistion  
of the terminal block cover.  
INDUCTIVE LOADS (FOR EXAMPLE  
MONITORS AND LASER PRINTERS) HAVE  
A VERY HIGH POWER CONSUMPTION AT  
START-UP. IF CONNECTED TO THE UPS,  
THE START-UP POWER OF SUCH LOADS  
MUST BE TAKEN INTO CONSIDERATION  
WHEN CALCULATING THE CAPACITY OF  
THE UPS TO PREVENT THE UPS FROM  
BEING OVERLOADED AND TURNED OFF.  
Connect the AC cable to the terminal blocks; refer  
to the indication on the rear panel. Tie up the AC  
cable to the rear panel and re-install the cover of  
the terminal block.  
WARNING  
3
INSTALL ATION  
17  
3.4.4  
Parallel installation operation  
16 Parallel system  
installation diagram  
Up to three UPSs can be connected in parallel to  
configure a sharing and redundant output power.  
From Utility  
Mains Breaker  
I/P Breaker  
I/P Breaker  
I/P Breaker  
UPS 1#  
UPS 2#  
UPS 3#  
O/P Breaker  
O/P Breaker  
O/P Breaker  
Main O/P Breaker  
Mains Mechanical or static switch  
16  
To Load  
18  
ABB UPS PRODUCTS AND SOLUTIONS  
How to install a new parallel UPS system:  
1. Before installing a new parallel UPS system,  
prepare the input/output wires, breakers and  
a main maintenance mechanical switch or  
static switch.  
2. Independent battery packs for each UPS.  
3. Remove the cover plate from the parallel  
connection port on the UPS, connect each  
UPS one by one with a parallel connection cable  
and make sure the cable is screwed in tightly.  
5. Connect the input and output wires and make  
sure all the breakers are turned off.  
17 Parallel cable  
connection  
18 Parallel connection  
cable locker  
19 Parallel system  
wiring diagram  
17  
4. Install the cable locker to protect the parallel  
cable for each UPS.  
19  
18  
3
INSTALL ATION  
19  
6. Turn on the input breakers for the parallel UPS.  
7. Hold button for more than 1 s on one UPS in  
the system; the system will then switch to line  
mode.  
How to remove a single UPS from a parallel system:  
1. Firstly, a main maintenance mechanical switch  
or static switch should be installed on the  
parallel system.  
8. Check the output voltage of each UPS  
separately and check if the difference in output  
voltage is less than 0.5 V among the units in  
the parallel system. If the difference is more  
than 0.5 V, the UPS need to be regulated.  
9. If the difference in output voltage is less than  
0.5 V, turn off the input breakers to let the UPS  
shut down. Then switch on the output breakers  
for all UPSs.  
2. Ensure the bypass is normal and the auto  
bypass setting is at “enable,” then press the  
button to turn off the UPS system and the UPS  
system will switch to bypass mode.  
3. Transfer the main maintenance switch or static  
switch from “UPS” to “BPS,” then switch off  
the output breakers, input breakers and mains  
breaker in the parallel system. The UPS will  
then shut down.  
10.Switch on the input breakers for the parallel  
UPS. Hold button for more than 1 s on one UPS  
in the system; the system will then switch to  
line mode. After these operations, the system  
will work normally in parallel mode.  
4. Switch off the main output breaker and output  
breaker in the parallel system.  
5. Remove the UPS of interest and disconnect  
cables/wires.  
6. Switch on the mains breaker and input breaker  
of the reserve UPS, make sure the UPS is in  
bypass mode.  
WIRING REQUIREMENT:  
7. Switch on the output breaker and main output  
breaker.  
8. Transfer the main maintenance switch or static  
switch from “BPS” to “UPS” and press the  
button to turn on the UPS, and the UPS will  
turn on in line mode.  
1. IF THE DISTANCE BETWEEN THE UPS  
AND BREAKER PANEL IS LESS THAN 20  
METERS IN A PARALLEL SYSTEM, THE  
LENGTH DIFFERENCE BETWEEN INPUT  
AND OUTPUT CABLE OF THE UPS IS  
REQUIRED TO BE LESS THAN 20%.  
2. IF THE DISTANCE BETWEEN THE UPS  
AND BREAKER PANEL IS MORE THAN 20  
METERS IN A PARALLEL SYSTEM, THE  
LENGTH DIFFERENCE BETWEEN INPUT  
AND OUTPUT CABLE OF THE UPS IS  
REQUIRED TO BE LESS THAN 5%.  
NOTE  
How to remove all the UPSs from a parallel system:  
1. Firstly, a main maintenance mechanical switch  
or static switch should be installed on the  
parallel system.  
2. Ensure the bypass is normal and the auto  
bypass setting is set to “enable”. Press the  
button to turn off the UPS system, and the UPS  
system will switch to bypass mode.  
3. Transfer the main maintenance switch or static  
switch from “UPS” to “BPS”, then switch off the  
output breakers, input breakers and mains  
breaker in the parallel system, and the UPS will  
shut down. The line will power the load via the  
maintenance mechanical switch or static switch.  
How to add a new UPS to a parallel system:  
1. Firstly, a main maintenance mechanical switch  
or static switch should be installed in the  
parallel system.  
2. Regulate the output voltage of the new UPS:  
check if the output voltage difference between  
the new UPS and the parallel system is less  
than 0.5 V.  
3. Ensure the bypass of the parallel system is  
normal and the auto bypass setting is at  
“enable,” then press the button to turn off  
the UPS, the UPS will switch to bypass mode.  
4. Set the main maintenance switch or static  
switch from “UPS” to “BPS,” then switch off  
the main output breaker, input breaker and  
mains breaker. The UPS will then shut down.  
5. Connect the cable and wire for the new UPS.  
6. Switch on the input breakers and mains  
breaker and make sure that every UPS is in  
bypass mode.  
7. Switch on the output breakers and main  
output breaker, transfer the main maintenance  
switch or static switch from “BPS” to “UPS”.  
8. Press the button on one UPS - all the UPSs will  
turn on. The system will work in line mode.  
20  
ABB UPS PRODUCTS AND SOLUTIONS  
4 Operation  
This chapter describes how the UPS is operated  
through the LCD.  
The user can:  
• Operate the LCD  
• Start up and shut down the UPS (excluding the  
commissioning start up)  
• Operate additional SNMP/Modbus adapters  
and their software  
4.1 Control panel  
The user-friendly control panel has two parts:  
• Selection keys  
• Power management LCD (PMD)  
• Status LEDs  
4.1.1  
Selection keys  
20 Control panel  
Table 6: UPS selection keys  
Button  
Function Illustration  
Turn the UPS on  
and off or change  
operating mode.  
Battery mode  
Online mode  
Bypass mode  
Fault  
Power  
ON/OFF  
LED’s  
Battery Load  
Scroll up  
through the menu.  
Scroll UP  
20Min 100%  
LCD  
Output  
230V 50Hz  
Scroll down  
through the menu.  
Scroll DOWN  
Selection  
ESC  
keys  
Select and  
confirm settings.  
Select / Edit  
Exit / Mute  
Escape  
Up  
Down Enter  
On/Off  
20  
Exit menus and  
mute the buzzer.  
4.1.2  
LED’s status indicators  
Table 7: UPS selection keys  
Indicator  
Status  
Description  
The UPS is operating normally  
on online or on high efficiency  
mode.  
NORMAL  
(GREEN)  
ON  
BATTERY  
(ORANGE)  
ON  
The UPS is in battery mode.  
ON  
The UPS is in bypass mode.  
The UPS is in standby mode.  
BYPASS  
(ORANGE)  
Flash  
FAULT  
(RED)  
The UPS has an  
active alarm or fault.  
ON  
4
OPER ATION  
21  
4.1.3  
LCD  
Battery status  
Load/equipment status  
21 The default LCD  
The LCD shows an overview of the status of the UPS:  
- Input  
- Output  
- Battery  
Battery  
Load  
- Load parameters  
- Working mode  
- Settings on voltage  
- Frequency  
20Min 100%  
Output  
- Bypass presence.  
230V 50Hz  
The LCD backlight automatically dims after two  
minutes of inactivity (except in cases of UPS  
fault). Press any button to wake up the screen.  
Operation status  
Input/output information  
21  
A buzzer indicates UPS status. Table 8 lists  
the buzzer status meanings  
For more information on how to use the LCD,  
see Chapter 4.4 and 4.6.  
Table 8: Definition of alarms  
UPS condition  
Buzzer status  
Active fault  
Continuous  
Active warning Beep every second  
Battery  
UPS on battery: Beep every 4 seconds  
Low battery: Buzzer beeps every second  
Bypass  
Beep every two minutes  
Overload  
Beep twice every second  
When powering on, the LCD shows the UPS  
status. The UPS will also return to this default  
screen when no buttons hav been pressed for  
15 minutes.  
The status screen shows the following information:  
• Status summary, including operating mode and  
load information  
• Alarm status, if present (including fault and  
warning information)  
• Battery and charger status (including battery  
voltage, charge level and charger status)  
• Current runtime information  
22  
ABB UPS PRODUCTS AND SOLUTIONS  
4.2 Operating mode  
The following table describes the UPS  
status information:  
Table 9: Symbols in operating mode  
Status  
Symbol  
Description  
Online-mode  
UPS is running through the inverter (online mode)  
UPS is running on battery. The alarm buzzer sounds every 4 seconds.  
Depending on the UPS load and number of external battery modules (EBMs),  
the “Battery Low” warning may occur before the battery reaches 20 percent capacity.  
The alarm buzzer sounds every second  
Battery-mode  
Bypass-mode  
The power used by the load is supplied from the mains power via an internal filter.  
Note that if there is a power failure and the UPS is in bypass mode, it will not transfer  
back to mains or battery mode.  
In bypass mode, the alarm buzzer will sound every two minutes.  
Bypass without  
output  
UPS is running in bypass, but there is no power at the output.  
After the UPS is turned on, the power used by the load is supplied from the mains (if its  
power is within an acceptable range) via an internal filter. This guarantees higher UPS  
efficiency. On mains failure, the UPS transfers to online mode or battery mode and the  
load is supplied continuously.  
ECO-mode  
(HE: high  
efficiency-mode)  
Note: ECO mode can be enabled through the LCD settings or the monitoring software.  
Warning: The transfer time of the UPS output from ECO mode to battery mode is 10 ms  
and is not recommended for sensitive loads.  
In converter mode, the UPS runs with fixed-output frequency (50 Hz or 60 Hz). On mains  
failure, the UPS transfers to battery mode and the load is supplied continuously.  
Converter-mode  
Note:  
-
Converter mode function can be enabled through the LCD settings or the  
monitoring software.  
-
The load is derated to 70 percent in converter mode.  
Warnings indicate abnormal situations that do not stop the UPS from working. The UPS  
continues running, but the user should perform corrective actions, see Chapter 6.  
Warning  
Fault  
In case of failure, the UPS may disconnect the load or transfer to bypass depending on  
the cause of the failure. The UPS alarm sounds a continuous signal and the backlight of  
the UPS will turn red. For more information, see Chapter 6.  
When the UPS is in overload, an alarm sounds twice every second. Disconnect  
unnecessary loads one by one to decrease the load. The load should be lower than 90  
percent of its nominal power capacity in order to stop alarming.  
Overload  
Battery test  
UPS is performing a battery test.  
Battery  
disconnected  
The battery is disconnected or defective. The UPS alarm sounds.  
Parallel  
The system is running in parallel.  
4
OPER ATION  
23  
4.3 UPS start-up and shutdown  
4.3.2  
UPS shutdown  
SWITCH OFF THE CONNECTED LOADS  
BEFORE TURNING ON THE UPS. SWITCH  
ON THE LOADS ONE BY ONE AFTER THE  
UPS IS TURNED ON. SWITCH OFF ALL OF  
THE CONNECTED LOADS BEFORE  
TURNING OFF THE UPS.  
To shut down the UPS with mains supply:  
1. If the UPS is working in bypass mode, go to  
step 3.  
2. If the UPS is in online mode, keep the power  
button pressed for more than 3 seconds.  
The alarm buzzer will sound and the UPS  
will transfer to bypass mode.  
WARNING  
THE FIRST TIME THE UPS IS STARTED UP,  
IT MUST BE CONNECTED TO THE UTILITY.  
NOTE  
THE OUTPUT IS STILL ENERGIZED.  
DANGER  
4.3.1  
UPS start-up  
To start up the UPS with mains supply:  
1. Check that all cables are securely and correctly  
connected.  
3. Disconnect the mains power supply. The  
2. Keep the power button pressed for longer than  
1 second. The fans will activate and the UPS  
will load for a few seconds.  
3. The UPS will perform a self-test and the LCD  
will show the default UPS status screen.  
display will shut down and the output voltage  
will be removed from the UPS output terminal.  
4. If the bypass has been disabled via the  
Settings menu, keep the power button pressed  
for longer than 3 seconds to shut down the  
UPS. The unit will transfer from online to  
standby mode. Disconnect the input power  
cable and the display will shut down.  
BYPASS MODE IS ENABLED BY DEFAULT  
AND CAN BE CONFIGURED THROUGH THE  
USER’S SETTINGS (FOR MORE  
INFORMATION, SEE TABLE 11).  
To shut down the UPS without mains supply:  
1. To power off the UPS, keep the power on/off  
button pressed for more than 3 seconds.  
The alarm buzzer will sound for 3 seconds and  
the output power will be immediately cut off.  
2. The display will shut down and the output  
voltage will be removed from the UPS output  
terminal.  
NOTE  
To start up the UPS without mains supply  
(cold start):  
1. Check that all cables are securely and correctly  
connected.  
2. Keep the power button pressed for longer than  
1 second. The UPS will power on, the fans will  
activate and the LCD will turn on. The UPS will  
perform a self-test and show the default UPS  
status screen.  
3. Keep the power button pressed for longer  
than 1 second. The alarm buzzer will sound  
for 1 second and the UPS will start up.  
4. After a few seconds, the UPS transfers to  
battery mode. When the UPS is supplied with  
power from the mains, the UPS transfers to  
online mode without interrupting the UPS  
power output.  
24  
ABB UPS PRODUCTS AND SOLUTIONS  
4.4 Display functions  
Use the two middle buttons ( and ) to  
When the UPS starts up, the display is in the  
default UPS status summary screen.  
navigate the menu. Press the Enter ( ) button  
to select an option. Press the ESC button to  
cancel or return to the previous menu.  
Table 10: Display functions  
Main menu  
UPS status  
Submenu  
Display information or menu function  
[Status summary screen]  
[Alarm]  
[Battery charging / Volt / level / remaining time]  
[Mode / Para Num. / Running time]  
[Load] W VA  
[Output / Current] A %  
[Output / Voltage] V Hz  
[Input / Voltage] V Hz  
[Battery] V %  
Measurements  
[DC bus] V V  
[Temperature] °C  
[Battery remaining time] Min  
Single UPS  
battery test  
Starts a manual battery test for single UPS  
Starts a manual battery test for parallel UPS  
Parallel UPS  
battery test  
Control  
Single UPS turn off  
Reset fault status  
Clear event log  
Turn off one UPS in parallel UPS system  
Clears active fault  
Clears events  
Restore factory set  
Returns all settings to original values  
Sets parameters  
Settings  
Event log  
Event list  
[Product type/model]  
[Part / Serial number]  
[UPS / NMC firmware]  
Identification  
4
OPER ATION  
25  
4.5 User settings  
The following table displays the options that can  
be changed by the user.  
Table 11: User settings  
Submenu  
Available settings  
Default settings  
USER  
Password  
Key the password  
Language  
[English][Deutsch][Español]  
[disabled] [enabled]  
[enabled] [disabled]  
English  
User password  
Audible alarm  
[disabled]  
[enabled]  
[208V] [220V] [230V] [240V]  
Can be changed in standby  
mode and bypass mode  
Output voltage  
[230V]  
Output frequency  
Power strategy  
Auto bypass  
[autosensing] [50HZ][60HZ]  
[normal] [high efficiency] [converter]  
[enabled] [disabled]  
[autosensing]  
[normal]  
[enabled]  
[enabled] [disabled]  
Authorize the product to  
restart automatically when  
mains recovers after a  
Auto restart  
[enabled]  
complete battery discharge.  
Dry in  
[Disabled] [SON] [SOFF] [Maintain bypass]  
[Disabled]  
[Load powered] [On battery mode]  
[Battery low] [Battery disconnected]  
[Bypass output] [UPS normal]  
Dry out  
[Load powered]  
Start on battery  
[enabled] [disabled]  
[0~20]  
[enabled]  
External battery modules  
External battery AH setting  
Battery remaining time  
According to model  
According to model  
[enabled]  
[0~300]  
[enabled] [disabled]  
[0~4] 0~4A for standard model  
[0~12] 0~12A for long backup model  
Charger current  
[4A] for 6-10 kVA  
Site wiring fault alarm  
LCD contrast  
[disabled] [enabled]  
[disabled]  
[-5 ~ +5]  
[+0]  
26  
ABB UPS PRODUCTS AND SOLUTIONS  
4.6 LCD operation  
In addition to the default UPS status summary  
4.6.2  
UPS status menu  
22 Main menu  
23 UPS status menu  
screen, the user has access to useful information  
about the UPS status, including various detailed  
measurements, previous event records and the  
UPS identification. The settings can be changed  
to optimize the UPS for and by the user.  
By pressing on the UPS status menu, the next  
UPS status menu tree is displayed.  
The content of UPS status menu tree is same as  
the default UPS status summary menu.  
By pressing ESC for more than 3 seconds, the last  
main menu tree is displayed.  
4.6.1  
Main menu  
In the default UPS status summary screen,  
when pressing or for more than 3 seconds,  
detailed information about alarm, battery or  
system status is displayed.  
UPS status  
In the default UPS status summary screen, press  
ESC for more than 3 seconds to return to the main  
menu tree. The main menu tree has six branches:  
UPS status menu, Measurement menu, Event log  
menu, Control menu, Identification menu and  
Settings menu.  
Battery  
Load  
Battery charging  
Battery volt:240.0V  
Battery level:90%  
EBM: 1  
100% 57%  
Output  
230V 50Hz  
Status:  
Line Mode  
Para Num: 1  
Running time:  
0001:21:37:59  
Alarm #A011  
No battery  
Initializing  
23  
Settings  
UPS status  
Event log  
Identiꢀcation  
Control  
Measurements  
22  
4
OPER ATION  
27  
4.6.3  
Measurement menu  
4.6.4  
Event log menu  
24 Measurement menu  
25 Event log menu  
By pressing on the Measurement menu, the  
next measurement menu tree is displayed.  
Detailed, useful information such as the output  
voltage and frequency, the output current, the  
load capacity, the input voltage and frequency,  
etc. can be accessed here.  
By pressing on the Event log menu, the next  
event menu tree is displayed.  
All previous events, alarms and faults are recorded  
here. Data includes the explanation, the event  
code, and the precise time in the UPS when the  
event happened. Pressing or for less than  
3 seconds, scrolls through events one by one.  
The maximum number of recorded events is 100.  
If this limit is exceeded, the latest event will  
replace the oldest.  
Pressing ESC for more than 3 seconds, returns to  
the last main menu tree.  
Measurements  
Pressing ESC for more than 3 seconds displays  
the last main menu tree.  
Event log  
Battery remaining  
Output  
time  
850W 1130VA  
10Min  
0001:03:02:25  
Alarm #A083  
Amb. Temp. alarm  
0001:02:01:00  
Event #F031  
Out. Short circuit  
Output  
4.9A 100%  
Temperature  
22  
1/100  
100/100  
DC Bus  
360.3V 360.9V  
Output  
229.6V 49.9Hz  
0001:03:01:25  
Event #E061  
Online model  
0001:03:01:06  
Event #F042  
Inverter overload  
2/100  
3/100  
25  
Intput  
226.3V 49.9Hz  
Battery  
218.1V 100%  
24  
28  
ABB UPS PRODUCTS AND SOLUTIONS  
4.6.5  
Control menu  
4.6.6  
Identification menu  
26 Control menu  
27 Identification menu  
By pressing on the Control menu, the next  
control menu tree is displayed.  
Start Battery Test: this is the command that  
allows the UPS to do a battery test.  
Reset Fault status: when a fault occurs, the UPS  
will stay in Fault mode and the alarm will continue  
to ring. Enter this menu to reset error status: then  
the UPS stops the alarm and recovers to bypass  
mode. The cause of the fault should be checked  
and corrected before the UPS is reset manually.  
Restore factory settings: all the settings are reset  
to default factory settings. Can only be done in  
bypass mode.  
By pressing on the Identification menu, the  
next identification menu tree is displayed.  
Identification information includes UPS serial  
number, firmware serial number and model type.  
Press ESC for more than 3 s to return to the last  
main menu tree.  
PowerValue 11 RT/T G2  
6-10kVA  
27  
26  
4
OPER ATION  
29  
4.6.7  
Setting menu  
Example: set rated output voltage value.  
28 Setting menu  
29 Example (set-up)  
PLEASE CONTACT YOUR LOCAL  
DISTRIBUTOR FOR FURTHER  
...  
INFORMATION BEFORE CHANGING  
SETTINGS. SOME SETTINGS CHANGE THE  
SPECIFICATION OF THE UPS AND SOME  
SETTINGS ENABLE OR DISABLE SOME  
IMPORTANT FUNCTIONS. UNSUITABLE  
SETTINGS ENTERED BY A USER MAY  
RESULT IN POTENTIAL FAILURES OR  
PROTECTION FUNCTION LOSS, OR EVEN  
DIRECTLY DAMAGE THE LOAD, BATTERY  
OR UPS.  
NOTE  
29  
MOST SETTINGS CAN ONLY BE CHANGED  
WHILE THE UPS IS IN BYPASS MODE  
NOTE  
28  
30  
ABB UPS PRODUCTS AND SOLUTIONS  
5 Communication  
A USB and an RS-232 port are available to enable  
the communication between the UPS and a  
remote computer/ station. Only one  
communication port can be active at a time  
and the priority is given to the USB port.  
If there is a power failure and a predicted  
shutdown of the UPS due to low battery  
autonomies, the monitoring system can save the  
load data and initiate shutdown of the equipment  
connected to the UPS.  
Once the communication cable is installed,  
the power management software can exchange  
information with the UPS. The software collects  
information from the UPS and indicates the  
status of the device, the power quality of the  
mains and the battery autonomy of the units.  
5.1 RS-232 port  
The UPS has an RS-232 port for UPS monitoring,  
30 RS-232  
Table 12: Communication port pin assignment  
control and firmware updates. To establish  
communication between the UPS and a computer,  
connect one end of the serial communication  
cable to the RS-232 port on the UPS and the other  
end to the RS-232 port of a computer.  
Communication Port  
(DB-9 Connector)  
Direction  
from UPS  
PIN  
1
Signal Name  
DCD  
Function  
Battery low signal  
Out  
Transmit to  
external device  
2
TxD  
Out  
In  
Receive from  
external device  
3
4
RxD  
DTR  
The cable pins for the RS-232 communication  
port are described in “Figure 30” and “Table 11”.  
PnP from  
external device  
In  
5
6
7
8
9
GND  
DSR  
RTS  
CTS  
RI  
Signal common  
To external device  
No connection  
On battery signal  
VDC power  
--  
Out  
In  
Out  
Out  
30  
5
COMMUNIC ATION  
31  
5.2 USB port  
The UPS can communicate with USB-compliant  
computers that run power management  
software. To establish communication between  
the UPS and a computer, connect the USB cable to  
the USB port on the UPS. Connect the other end  
of the cable to the USB port on a computer.  
5.3 Emergency power off  
The EPO connector can be used to block the  
output of the UPS in case of an emergency. The  
EPO connector can be configured as Normally  
Closed (NC) or Normally Opened (NO) through the  
5.3.1  
Dry IN  
31 EPO (Emergency  
power off)  
32 Dry IN & OUT  
connector  
Dry in allows a remote action to switch on/ switch  
off/ maintenance bypass the UPS.  
This is done by switching the contact from closed  
to open.  
USB or RS232 port.  
By default, the EPO connector is Normally Closed  
(NC) by a jumper in the rear panel. If the jumper is  
removed, the UPS output will not supply energy  
to the load until the EPO status is changed.  
To return to normal status, the EPO connector must  
be closed. Enter the LCD menu to clear the EPO  
status (Control-->Reset fault status-->Reset  
fault). The UPS alarm is cleared and bypass mode  
is recovered. Set the UPS to inverter mode manually.  
5.3.2  
Dry OUT  
The dry out port is normally closed. If the dry out  
port is open, it indicates that the UPS is running  
in bypass or inverter mode / on battery mode /  
battery low / battery disconnected /  
bypass output/ UPS normal.  
DRY DRY  
OUT IN  
32  
EPO  
31  
32  
ABB UPS PRODUCTS AND SOLUTIONS  
5.4 Network management card (optional)  
The PowerValue 11 T G2 is equipped with an  
intelligent slot for optional cards for remote  
management of the UPS through the Internet/  
intranet. Either of the following accessories can  
be installed in the intelligent slot:  
To install a network management card:  
1. Remove the two screws that protect the  
communication slot of the UPS.  
2. Insert the SNMP/Modbus card into the  
communication slot.  
SNMP/Modbus Card – SNMP/Modbus, HTTP  
and monitoring capabilities through a Web  
browser interface.  
AS400 Card – AS400 card for AS400  
communication protocol.  
3. Screw the SNMP/Modbus card onto the slot  
using the screws removed in Step 1  
Compatible SNMP/Modbus cards: CS141 Basic,  
CS141 ModBus, CS141 Advanced, Winpower  
SNMP/Modbus, Winpower ModBus.  
5.4.1  
card (optional)  
Installing a serial network management  
For more information on the SNMP/Modbus  
Cards, see the SNMP/Modbus user’s manual.  
For more details about parameters available  
when using an SNMP/Modbus card with  
PowerValue 11 T G2, see Appendices A and B.  
Each UPS has a communication slot for an  
optional serial network management protocol  
(SNMP) card. After installing an SNMP/Modbus  
card, an environmental monitoring probe can be  
connected.  
5.4.2  
Monitoring software  
The UPS can be monitored using software.  
The software provides a remote and safe  
shutdown for multi-client systems in case of  
absence of power at the UPS output. Instructions  
on how to install the software are provided with  
the network management cards.  
THE UPS DOES NOT HAVE TO BE SHUT  
DOWN BEFORE INSTALLING A  
COMMUNICATION CARD.  
NOTE  
For more information, contact your local supplier.  
6
TROUBLESHOOTING  
33  
6 Troubleshooting  
6.1 Fault identification and rectification  
Alarms and events indicate warnings and notify  
of errors or potential failures in the system. The  
output of the UPS is not necessarily affected  
when an alarm arises but taking the correct  
actions may prevent loss of power to the load.  
6.2 Accessing alarms  
The control panel provides troubleshooting  
information from two main menus:  
6. After scrolling through all alarms, press to  
access the battery status screen.  
• UPS status menu: access to all active alarms  
• Event log menu: access to the most recent 50  
events, which may include active and closed alarms.  
Event log menu  
From the Event log menu, you can access the  
latest 50 alarms, events and notices, arranged  
from newest to oldest. Events and alarms are  
logged in the Event log when they occur and, if  
applicable, when they are cleared:  
• Events are silent conditions that are recorded in  
the Event log as status information. Events do  
not require a response.  
• Alarms, including active alarms, are recorded in  
the Event log. Active alarms are announced by  
either an intermittent beep or a continuous  
sound. Examples are “Fan locked” and “Heat  
sink temperature high.” Active alarms require  
a response.  
UPS status menu  
From the UPS status menu, you can access the  
following screens for troubleshooting information:  
Status summary: The status summary screen  
provides information on both operating mode  
and load. During normal operation, the display  
has a blue background with white text. In the  
case of a critical alarm, the backlight color  
changes to orange with dark text.  
Alarm: A separate screen appears for each  
active notice or alarm.  
Battery status: The battery status screen  
indicates the battery charge mode, the  
percentage of the battery that is charged and  
runtime with the present load.  
To access troubleshooting information using the  
Event log menu:  
1. Press for 1 second to go to the main menu  
selection and scroll down to the Event log  
To access troubleshooting information using the  
UPS status menu screen:  
menu using  
.
1. Press for longer than 1 second to go to the  
UPS status menu screen.  
2. Press to enter the Event log list.  
3. Scroll through the listed events, notices,  
2. Press to access the UPS status main screen.  
3. Press to access the notice and alarm screens.  
4. The UPS status main screen shows load  
information. The status icon indicates the UPS  
operating-mode.  
and alarms using or  
.
THE MOST RECENT EVENTS ARE  
DISPLAYED ON TOP OF THE LIST  
(FOR EXAMPLE 1/50).  
5. Press to scroll through the notice and alarm  
information.  
NOTE  
34  
ABB UPS PRODUCTS AND SOLUTIONS  
Alarm or Event  
Possible cause  
Remedy  
Battery mode  
The UPS is powering the equipment with  
battery power. Prepare your equipment for  
shutdown.  
Battery (Orange) LED is on. A utility failure has occurred and the UPS is in  
1 beep every 4 seconds.  
Code: E062  
battery mode.  
This warning is approximate, and the actual  
time to shutdown may vary significantly.  
Battery low  
Battery(Orange) LED is on.  
1 beep every 1 second.  
Code: A012  
The UPS is in battery mode and the battery is Depending on the UPS load and number of  
running low.  
external battery modules (EBMs), the “Battery  
Low” warning may occur before the batteries  
reach 20 percent capacity.  
No battery  
Verify that all batteries are properly  
connected.  
If the condition persists, contact your service  
representative.  
Fault (Red) LED is Flash  
1beep every 1 second  
Code: A011  
The batteries are disconnected.  
Equipment is powered but not protected by  
the UPS. Check for one of the following  
alarms: over temperature, overload or UPS  
failure.  
Bypass mode  
Bypass (Orange) LED is on.  
Code: E060  
An overload or a fault has occurred, or a  
command has been received and the UPS is in  
bypass mode.  
Remove some of the equipment from the UPS.  
The UPS continues to operate, but may switch  
to bypass mode or shut down if the load  
increases.  
The alarm resets when the condition becomes  
inactive.  
Power overload  
Fault (Red) LED is Flash  
2 beeps every 1 second  
Code: A041  
Power requirements exceed the UPS capacity.  
The UPS internal heat sink temperature is too  
high, or a fan has failed.  
At the warning level, the UPS generates the  
alarm but remains in the current operating  
state.  
Clear vents and remove any heat sources.  
Allow the UPS to cool. Ensure the airflow  
around the UPS is not restricted.  
Restart the UPS.  
If the condition persists, contact your service  
representative.  
UPS over temperature  
Fault (Red) LED is on.  
Beep continuous.  
Code: F081  
If the temperature rises another 2°C, the UPS  
transfers to bypass mode or standby mode.  
ON Maintenance Bypass  
Bypass (Orange) LED is on.  
Code: A072  
UPS was manually commanded to switch to  
bypass and will remain in bypass until  
commanded out of bypass.  
Check the maintenance bypass switch status.  
The equipment transferred to bypass utility  
power as a normal function of high efficiency  
operation. Battery mode is available and your  
equipment is protected.  
In HE Mode  
Line (green) LED is on.  
Code: E063  
The UPS is on bypass while operating on the  
high efficiency setting.  
Site fault detection is supported on all models  
any time there is a grounding neutral  
connection.  
Alarm triggers when the difference between  
ground and neutral voltage is >15 V.  
Site Wiring Fault  
Fault (Red) LED is flash  
1beep every 1 second  
Code: A004  
Site fault detection should be enabled by  
default. It can still be enabled / disabled from  
the LCD settings menu.  
Reconnect all input wires.  
Back feed  
Fault (Red) LED is On.  
Beep continuous.  
Code: F093  
UPS has an unexpected bypass current on  
battery mode.  
Transfer to maintenance bypass and call  
service.  
Inv Overload Fault  
Fault (Red) LED is On  
Beep continuous.  
Code: F042  
The UPS transfers to battery mode if  
supporting the load. Remove some of the  
equipment from the UPS.  
UPS has transferred to bypass or fault mode  
because of overload in inverter mode.  
Byp Overload Fault  
Fault (Red) LED is On.  
Beep continuous.  
Code: F043  
UPS has cut off the output and transferred to  
fault mode because of overload in bypass  
mode or HE mode.  
Remove some of the equipment from the UPS.  
Output Short Circuit  
Fault (Red) LED is On.  
Beep continuous.  
Code: F031  
Remove all the loads. Turn off the UPS. Check  
if UPS output and load has short circuit.  
Ensure short circuit is removed before turning  
on again.  
Indicates that the UPS has detected  
abnormally low impedance placed on its  
output and considers it a short circuit.  
Fan Failure  
Fault (Red) LED is flash  
1 beep every 1 second  
Code: A085  
Indicates that the fan could not work normally. Check UPS fans.  
BUS Over Voltage  
Fault (Red) LED is On.  
Beep continuous.  
Code: F021  
Indicates that the UPS has bus overvoltage  
fault.  
The UPS transfers to bypass mode if  
supporting the load.  
6
TROUBLESHOOTING  
35  
Alarm or Event  
Possible cause  
Remedy  
BUS Under Voltage  
Fault (Red) LED is On.  
Beep continuous.  
Code: F022  
Indicates that the UPS has bus undervoltage The UPS transfers to bypass mode if  
fault.  
supporting the load.  
BUS Unbalance  
Fault (Red) LED is On.  
Beep continuous.  
Code: F023  
Indicates that the positive bus voltage and  
negative bus voltage are too lopsided.  
The UPS transfers to bypass mode if  
supporting the load.  
BUS Short  
Fault (Red) LED is On.  
Beep continuous.  
Code: F024  
Indicates that the bus voltage is decreasing  
very fast.  
Contact your service representative.  
Contact your service representative.  
BUS Softstart Fail  
Fault (Red) LED is On.  
Beep continuous.  
Code: F025  
Indicates that the bus could not soft start  
successfully.  
Inv Over Voltage  
Fault (Red) LED is On.  
Beep continuous.  
Code: F032  
Indicates that the UPS has inverter  
overvoltage fault.  
The UPS transfers to bypass mode if  
supporting the load.  
Inv Under Voltage  
Fault (Red) LED is On.  
Beep continuous.  
Code: F033  
Indicates that the UPS has inverter  
undervoltage fault.  
The UPS transfers to bypass mode if  
supporting the load.  
Inv Softstart Fail  
Fault (Red) LED is On.  
Beep continuous.  
Code: F034  
Indicates that the inverter could not soft start  
successfully.  
Contact your service representative.  
Charger Fail  
The UPS turns off the charger until the next  
power recycle. Contact your service  
representative.  
Fault (Red) LED is flash  
1 beep every 1 second  
Code: A015  
Indicates that the UPS has confirmed the  
charger has failed.  
Battery Over Voltage  
Fault (Red) LED is On.  
Beep continuous.  
Code: F016  
The UPS will turn off the charger until the  
battery voltage is normal.  
Indicates that the battery voltage is too high.  
In a parallel system, power of UPS is negative.  
In parallel system, parallel cable disconnected.  
Negative power Fault  
Fault (Red) LED is On.  
Beep continuous.  
Code: F0E1  
Redundancy mode, the fault UPS turn to fault  
mode without output  
Increase mode, UPS1& UPS2 turn to fault  
mode.  
Parallel cable loss  
Fault (Red) LED is On.  
Beep continuous.  
Code: F0E2  
Disconnect parallel cable one turn to fault  
mode.  
Parallel system battery  
status  
Fault (Red) LED is flash  
1 beep every 1 second  
Code: A0E6  
UPS1 connect battery, UPS2 without battery. Check battery connect status.  
Line input different  
Fault (Red) LED is flash  
1 beep every 1 second  
Code: A0E7  
Parallel system, UPS1 line ok, UPS2 line loss.  
Check the line input.  
Power strategy different  
Fault (Red) LED is flash  
1 beep every 1 second  
Code: A0E9  
Parallel system, UPS mode (normal, converter, Check UPS OP mode, keep OP mode be the  
HE) different.  
same.  
Rate power different  
Fault (Red) LED is flash  
1 beep every 1 second  
Code: A0EA  
Rated power different, not allowed to turn on  
UPS. Keep rated power the same.  
Parallel system rated power different.  
HE in parallel  
Fault (Red) LED is flash  
1 beep every 1 second  
Code: A0EB  
HE not allowed in parallel system, change UPS  
mode.  
Parallel system, UPS mode set as HE  
36  
ABB UPS PRODUCTS AND SOLUTIONS  
Always have the following information available  
when calling the after-sales service department:  
1. Model number and serial number  
2. Date on which the problem occurred  
3. LCD/LED display infrmation and buzzer  
alarm status  
4. Mains power condition, load type and  
capacity, environment temperature and  
ventilation condition  
5. Information on external battery pack  
(battery capacity, quantity).  
6.3 Silencing the alarm  
Press the ESC (Escape) button on the front  
panel display for 3 seconds to silence the alarm.  
Check the alarm condition and perform the  
relevant action to resolve the condition.  
If the alarm status changes or the ESC button is  
pressed for 3 seconds again, the alarm beeps  
again, overriding the previous alarm silencing.  
7
TECHNIC AL SPECIFIC ATIONS  
37  
7 Technical specifications  
GENERAL DATA  
Output rated power  
Output power factor  
Topology  
11T G2 6kVA B/ B2 / S  
6’000W  
11T G2 10kVA B/ B2 / S  
10’000W  
1.0  
Online double conversion  
Yes, up to 3 UPS  
Yes/Yes/No  
Parallel configuration  
Inbuilt batteries  
INPUT  
Nominal input voltage  
Input voltage tolerance  
Input current THDi  
Frequency range  
Power factor  
208/220/230/240 VAC  
100-276 (load dependent)  
<3% with full resistive load  
45-55Hz / 54-66Hz (extendable to 40~70HZ at load < 60%)  
≥0.995  
OUTPUT  
Rated output voltage  
Voltage tolerance  
Voltage distortion  
208/220/230/240 VAC  
±1% (referred to 230V)  
<1% linear load, <5% non linear load  
10m: 102-125% load  
30s: 126 to 150% load  
500 ms: ≥ 150% load  
Overload capacity (linear  
load) on inverter  
Nominal frequency  
Crest factor  
50 or 60 Hz  
3:1 (load supported)  
EFFICIENCY  
Overall system efficiency  
In eco-mode  
Up to 95%  
Up to 98%  
ENVIRONMENT  
Protection rating  
Storage temperature  
Operating temperature  
Relative humidity  
Altitude (above see level)  
BATTERIES  
IP20  
UPS: -25°C to 60°C; Batteries: 0°C to 35°C  
0°-40°C (up to 50°C at 50% load)  
0% to 95%  
1000m without derating  
Type  
VRLA (valve regulated lead-acid)  
16x9Ah(B)  
Inbuilt batteries  
Charging current  
20x9Ah (B2)  
0-4A adjustable (B,B2)  
0-12 adjustable (S)  
Recharge time  
(inbuilt batteries)  
4h to 90%  
COMMUNICATIONS  
User interface  
LCD display  
Optional communication  
cards  
SNMP/Modbus;ModBus;AS400;Environmental monitoring sensor probe  
STANDARDS  
Safety  
IEC/EN 62040-1  
EMC  
IEC/EN 62040-2  
Performance  
Manufacturing  
WEIGHT, DIMENSIONS  
Weight  
IEC/EN 62040-3  
ISO 9001:2015, ISO 14001:2015, OHSAS 18001  
61/73/13 Kg  
55.2/65.2/15.2 Kg  
B / B2:  
225 x 589x 452 mm  
S: 225x 348 x 452 mm  
B / B2:  
225 x 589x 452 mm  
S: 225x 348 x 452 mm  
Dimensions w x h x d  
38  
ABB UPS PRODUCTS AND SOLUTIONS  
BATTERY  
AUTONOMY  
11T G2 6kVA B  
11T G2 6kVA B2 11T G2 6kVA S  
11T G2 10kVA B 11T G2 10kVA B2 11T G2 10kVA S  
UPS internal  
batteries  
5.5 / 7.5 / 14 / 29  
7.5 / 10 / 19 / 39  
34 / 46 / 87 / 175  
N/A  
2 / 4 / 7 / 17  
3 / 5 / 9 / 23  
N/A  
UPS + 1 EBM 25 / 34 / 64 /129  
18 / 27 / 49 / 133  
12 / 18 / 31 / 83  
16 / 24 / 43 / 114  
33 / 50 / 87 / 237  
8 / 13 / 23 / 64  
UPS + 2 EBM 50 / 68 / 129 / 259 68 / 92 / 175 / 351 49 / 74 / 133 / 358 24 / 36 / 64 / 172  
23 / 35 / 64 / 172  
UPS + 3 EBM 79 / 107 / 204 / 410 107 / 146 / 277 / 556 88 / 133 / 237 / 640 39 / 58 / 101 / 279 53 / 79 / 137 / 384 42 / 64 / 114 / 308  
UPS + 4 EBM 111 / 151 / 287 / 578 151 / 205 / 390 / 784 133 / 200 / 358 / 966 55 / 82 / 143 / 400 75 / 111 / 194 / 550 64 / 96 / 172 / 465  
Battery autonomy in minutes at 100 / 75 / 50 / 25% load.  
Given runtimes are estimates and valid at 20 degrees Celsius.  
Actual runtime of the system will depend, among many variables, on the age of the batteries and  
environmental conditions.  
APPENDIX A  
39  
Appendix A  
CS141 SNMP/Modbus card available parameters  
(valid for CS141 Basic, CS141 ModBus, CS141  
Advanced).  
The parameters available for CS141 SNMP cards  
are shown below.  
Parameter  
Units  
Type  
Available interface  
Modbus register  
Measurement Parameters  
Input Voltage  
V
Input  
Input  
Webserver / Modbus  
Webserver / Modbus  
104  
111  
Input Frequency  
Hz  
Output Voltage  
Output Load Percentage  
Battery Voltage  
Battery Capacity  
Temperature  
V
Output  
Webserver / Modbus  
Webserver / Modbus  
Webserver / Modbus  
Webserver / Modbus  
Webserver / Modbus  
97  
%
V
Output  
100  
110  
103  
107  
Battery  
%
°C  
Battery  
Environmental  
UPS Status Information  
On shutdown  
Webserver / Modbus  
Webserver / Modbus  
Webserver / Modbus  
109  
109  
109  
On inverter  
On battery  
UPS Alarms  
Battery Low  
Webserver / Modbus  
Webserver / Modbus  
Webserver / Modbus  
Webserver / Modbus  
Webserver / Modbus  
Webserver / Modbus  
Webserver / Modbus  
117  
120  
123  
132  
138  
137  
133  
Input Bad  
On Bypass  
General Fault  
Test In Progress  
Shutdown imminent  
Diagnose test failed  
40  
ABB UPS PRODUCTS AND SOLUTIONS  
Appendix B  
Winpower SNMP/Modbus card available  
parameters (webserver interface)  
The parameters available from WinPower  
SNMP/Modbus cards are shown below.  
Parameter  
Type  
View  
UPS Status  
General, status  
UPS Monitoring >> UPS Status  
UPS Monitoring >> UPS Status  
UPS Monitoring >> UPS Status  
UPS Monitoring >> UPS Status  
UPS Monitoring >> UPS Status  
UPS Monitoring >> UPS Status  
UPS Monitoring >> UPS Status  
UPS Monitoring >> UPS Status  
UPS Monitoring >> UPS Status  
UPS Monitoring >> UPS Status  
UPS Monitoring >> UPS Status  
UPS Monitoring >> UPS Parameters  
UPS Monitoring >> UPS Parameters  
UPS Monitoring >> UPS Parameters  
UPS Monitoring >> UPS Identification  
UPS Monitoring >> UPS Identification  
UPS Temperature  
Voltage  
General, measurement  
Input, measurement  
Input, measurement  
Output, measurement  
Output, measurement  
Output, measurement  
Battery, status  
Frequency  
Load (%)  
Voltage  
Frequency  
Battery Status  
Capacity (%)  
Voltage  
Battery, measurement  
Battery, measurement  
Battery, measurement  
Output, Rating  
Time on Battery  
Output Rating Voltage  
Output Frequency Rating  
Output Rating VA  
UPS Model  
Output, Rating  
Output, Rating  
Additional UPS Information  
Additional UPS Information  
UPS Description  
Firmware Version  
MAC Address  
Additional Network card Information  
Additional Network card Information  
UPS Monitoring >> UPS Identification  
UPS Monitoring >> UPS Identification  
APPENDIX B  
41  
© Copyright 2017 ABB. All rights reserved.  
Specifications subject to change without notice.  

Nokia 3120b User Manual
Morphy Richards 47063 User Manual
Maxtor DIAMONDMAX 21 PATA STM380215A User Manual
LG Electronics LG Lifes Good Cell Phone AN430 User Manual
LG Electronics BLISS UX700W User Manual
Kenwood KDC U446 User Manual
Emerson MLT Analyzer Module NGA 2000 User Manual
Braun AROMASTER KF 43 TYPE 4087 User Manual
Black Box Computer Accessories LPJ008A TM User Manual
3Com SP 510UZ User Manual