ABB GE GEH3434 User Manual

1
GEH3434 INSTALLATION INSTRUCTIONS  
For Type TED Circuit Breaker  
Three Coil Shunt Trip Device  
NOTE: U/L listing is voided when the circuit  
breakeris modified to add an accessory. The U/L  
labelmust be destroyed  
CAUTION: When installing accessories. the breaker  
must be completely deenergized and disonnected  
from the electrical circuit.This is mandatory  
because breaker must be "ON" during certain  
stages of installation and testing  
VOLTAGE RATING 208-600 VAC  
INSTALLATION  
Removing Breaker Cover  
Open breaker contacts by moving handle to the  
breaker "OFF" position. Removebreakercover by  
removing mounting screws as shown in figure 2.  
Remove and save insulating tubes and plastic  
handle, showninfigure3. Tar mustbe removedto  
gain access toscrewshownbelow.  
FOUR  
Figure 1.  
COVER  
SCREWS  
GENERAL DESCRIPTION AND  
APPLICATION :  
The three-coilshunt tip is designed for the molded  
case circuit breaker in applications with current  
limiting fuses. The accessory prevents single-  
phasing on a three phase system when a single  
fuse blows. Each coil of the shunt trip is wired  
across a fuse so that the voltage across an open  
fuse will trip the breaker. When a coil is energized,  
the solenoid core releases the spring biased latch,  
allowing the slide to rotate the breaker trip bar to  
trip breaker. The fuse must be re-placed, and the  
breaker reset, before it can be reclosed. If the  
breaker is closed on an open fuse, the shunt trip  
will reopen immediately.  
Figure 2  
HANDLE  
INSULATING  
TUBES  
Figure 3  

Maxtor Personal Storage 3000DV User Manual
LG Electronics OPTIMUS MFL6701400112 User Manual
JOBO Digital Storage Device User Manual
IRiver SlimX 450 User Manual
iLive ISPK2806 User Manual
Freestyle FS80934 User Manual
Ego Technology B013281 User Manual
Echo Bear Cat 74800 User Manual
Dell Computer Accessories 3448P User Manual
Aluratek AIRMM01F User Manual