ABB ACS880 307LC User Manual

ABB INDUSTRIAL DRIVES  
ACS880-307LC diode supply units  
Hardware manual  
ACS880-307LC diode supply units  
Hardware manual  
3AXD50000579662 Rev A  
EN  
EFFECTIVE: 2020-06-30  
Table of contents 5  
Table of contents  
 
6 Table of contents  
Table of contents 7  
8 Table of contents  
Introduction to the manual 9  
1
Introduction to the manual  
Contents of this chapter  
This chapter contains general information on the manual.  
Applicability  
The manual is applicable to the cabinet-installed ACS880-307LC…+A018 diode supply  
units that form a part of an ACS880 multidrive system.  
Safety instructions  
Obey all safety instructions delivered with the drive.  
Read the complete safety instructions before you install, commission, use or service  
the drive. The complete safety instructions are given in ACS880 liquid-cooled multidrive  
cabinets and modules safety instructions (3AXD50000048633 [English]).  
Read the software-function-specific warnings and notes before changing the default  
settings of a function. For each function, the warnings and notes are given in the section  
describing the related user-adjustable parameters.  
Read the task-specific safety instructions before starting the task. See the section  
describing the task.  
Target audience  
This manual is intended for people who plan the installation, install, start up and do  
maintenance work on the drive, or create instructions for the end user of the drive concerning  
the installation and maintenance of the drive.  
Read the manual before working on the drive. You are expected to know the fundamentals  
of electricity, wiring, electrical components and electrical schematic symbols.  
         
10 Introduction to the manual  
Categorization by frame size and option code  
The frame size identifies information which concerns only a certain frame size of the drive.  
The frame size is shown on the type designation label. All frame sizes are listed in the  
technical data.  
The option code (for example, option +E200) identifies information which concerns only a  
certain optional selection. The options included in the drive are listed on the type designation  
label.  
Use of component designations  
Some device names in the manual include the item designation in brackets, for example  
[Q20], to make it possible to identify the components in the circuit diagrams of the drive.  
Terms and abbreviations  
Term  
Description  
ACU  
Auxiliary control unit. Contains control electronics, auxiliary voltage circuitry, etc.  
Type of control unit  
BCU  
CIO  
I/O module for controlling cooling fans  
Control board  
Control unit  
Cubicle  
Circuit board in which the control program runs  
Control board built in a housing (often rail-mountable)  
One section of a cabinet-installed drive. A cubicle is typically behind a door of its own.  
Frame size designation of the diode supply module  
DC circuit between rectifier and inverter  
D8T  
DC link  
DI  
Digital input  
Diode supply module  
Diode rectifier and related components enclosed in a metal frame or enclosure. Inten-  
ded for cabinet installation.  
Diode supply unit  
Drive  
Diode supply modules under control of one control board, and related components.  
Frequency converter for controlling AC motors  
Diode supply unit  
DSU  
Frame, frame size  
ICU  
Physical size of the drive or power module  
Incoming unit  
Intermediate circuit  
INU  
DC circuit between rectifier and inverter  
Inverter unit  
Inverter module  
Inverter bridge, related components and drive DC link capacitors enclosed in a metal  
frame or enclosure. Intended for cabinet installation.  
Inverter unit  
Multidrive  
Inverter module(s) under control of one control unit, and related components. One  
inverter unit typically controls one motor.  
Drive for controlling several motors which are typically coupled to the same machinery.  
Includes one supply unit, and one or several inverter units.  
Parameter  
In the drive control program, user-adjustable operation instruction to the drive, or  
signal measured or calculated by the drive.  
In some (for example fieldbus) contexts, a value that can be accessed as an object,  
eg, variable, constant, or signal.  
Rectifier  
Converts alternating current and voltage to direct current and voltage  
Drive for controlling one motor  
Single drive  
     
Introduction to the manual 11  
Related documents  
Manual  
Code  
General manuals  
ACS880 liquid-cooled multidrive cabinets and modules safety instructions  
3AXD50000048633  
ACS880 liquid-cooled multidrive cabinets and modules electrical planning instructions 3AXD50000048634  
ACS880 liquid-cooled multidrive cabinets mechanical installation instructions  
CIO-01 I/O module for distributed I/O bus control user's manual  
Supply unit manuals  
3AXD50000048635  
3AXD50000126880  
ACS880-207LC IGBT supply units hardware manual  
ACS880 IGBT supply control program firmware manual  
ACS880-307LC…+A018 diode supply units hardware manual  
ACS880 diode supply control program firmware manual  
Inverter unit manuals  
3AXD50000174782  
3AUA0000131562  
3AXD50000579662  
3AUA0000103295  
ACS880-107LC inverter units hardware manual  
3AXD50000196111  
3AUA0000085967  
3AUA0000098062  
ACS880 primary control program firmware manual  
ACS880 primary control program quick start-up guide  
Manuals for application programs (Crane, Winder, etc.)  
Brake unit and DC/DC converter unit manuals  
ACS880-607LC 1-phase brake units hardware manual  
ACS880 (3-phase) brake control program firmware manual  
ACS880-1607LC DC/DC converter units hardware manual  
ACS880 DC/DC converter control program firmware manual  
Option manuals  
3AXD50000481491  
3AXD50000020967  
3AXD50000431342  
3AXD50000024671  
ACS880-1007LC liquid cooling unit user's manual  
ACS880 +C132 marine type-approved cabinet-built drives supplement  
ACS-AP-x assistant control panels user’s manual  
Drive composer start-up and maintenance PC tool user’s manual  
Converter module lifting device for drive cabinets hardware manual  
Manuals for I/O extension modules, fieldbus adapters, safety options etc.  
3AXD50000129607  
3AXD50000039629  
3AUA0000085685  
3AUA0000094606  
3AXD50000210268  
You can find manuals on the Internet. See www.abb.com/drives/documents. For manuals  
not available in the document library, contact your local ABB representative.  
 
12  
Operation principle and hardware description 13  
2
Operation principle and hardware  
description  
Contents of this chapter  
This chapter contains a description of the diode supply unit. The information is valid for the  
ACS880-307LC…+A018 diode supply units.  
Operation principle  
The core of the diode supply unit is a diode-thyristor bridge. It rectifies three-phase AC  
current to direct current for the intermediate DC link of the drive. The intermediate DC link  
supplies the inverters that run the motors. There can be one inverter unit only (single drives)  
or several inverter units (multidrives) connected to the intermediate circuit. The DSU modules  
have inbuilt AC chokes. The AC chokes smoothen the current waveform in the power supply  
network and voltage in the DC link of the drive.  
The main difference between the ordinary diode-diode bridge and the controlled  
diode-thyristor bridge is the controllability. You cannot control the operation of the diodes  
but you can control the thyristors. By controlling the thyristors, you can limit the AC current  
of the drive at the power up without additional charging circuit in the supply unit or in inverter  
units.  
There are two control modes for the upper leg thyristor firing: the charging mode and the  
normal mode:  
The charging mode is in operation a short period after the power switch on: the supply  
control program controls the thyristor firing angle gradually towards zero while the  
intermediate circuit capacitors located in the inverter module(s) get charged.  
In the normal mode, the thyristor firing angle is 0 degrees: The thyristors operate as  
diodes.  
     
14 Operation principle and hardware description  
Overview diagram of the rectifier bridge  
2
3
U
1
1
2
3
Diodes. The diodes connect the AC terminals in cyclic sequence to the lower DC busbar (-).  
Thyristors. The thyristors connect the AC line terminals in cyclic sequence to the upper DC busbar (+).  
AC chokes  
6- and 12-pulse supply connections  
The figure below illustrates the difference between 6-pulse and 12-pulse AC supply  
connections. The 6-pulse connection is standard. If the drive has an even number of supply  
modules, you can order it as a 12-pulse version (option +A004).  
The 12-pulse supply connection eliminates the fifth and seventh harmonics, which  
substantially reduces the harmonic distortion of the line current and the conducted emissions.  
The 12-pulse connection requires a three-winding transformer, or two separate transformers.  
There must be phase shift of 30-degrees between the two 6-pulse supply lines, which are  
connected to different supply modules through electrically separate switching equipment.  
   
Operation principle and hardware description 15  
A
B
A
B
1
2
3
6-pulse connection  
12-pulse connection  
Supply transformer  
Switching equipment  
Diode supply modules  
16 Operation principle and hardware description  
Overview diagram of the drive system  
The following figure shows an example drive with a diode supply unit and three inverter  
units.  
5
4
5
5
8
1
2
6
6
6
9
3
M
3~  
M
3~  
M
3~  
7
1
2
3
4
5
6
7
8
9
Main circuit breaker [Q1]  
AC fuses  
Supply module [T01] (including choke and rectifier)  
Supply module DC fuses  
Inverter module DC fuses (with or without DC switches)  
Inverter module [T11]  
Motor  
Auxiliary voltage switch [Q21] (option +G344 or +G451)  
Auxiliary voltage transformer [T21] (option +G344)  
 
Operation principle and hardware description 17  
Layout drawings  
Overview layout drawing of the supply unit  
This drawing shows an example of a diode supply unit.  
2
1
3
5
4
8
9
10  
7
11  
6
1
2
3
Auxiliary control cubicle  
Incoming cubicle  
Supply module cubicle  
4…11 Control devices. See section Supply unit control devices.  
   
18 Operation principle and hardware description  
Auxiliary control cubicle layout  
1
3
2
4
5
8
6
7
1
2
3
4
5
Control panel [A59] (option +J400, or +J425)  
Operating switch [S21], emergency stop button [S61], etc.  
CIO-01 I/O module for cooling fan monitoring [A115.99]  
BCU control unit [A51]  
Auxiliary voltage transformers behind the assembly plates ([T21] option +G344, [T115] option +G451,  
in some deliveries also [T125])  
6
7
8
Cooling fan and heat exchanger [G115.99]  
Inlet manifold with stop and drain valves  
Outlet manifold with stop and drain valves  
 
Operation principle and hardware description 19  
Incoming cubicle layout - bottom cable entry  
1
2
6
7
3
4
8
5
9
10  
11  
12  
14  
13  
1…4  
5, 9 Main supply breaker [Q1.x] (option +F255)  
1, 6 Auxiliary voltage supply breaker (switch fuse) [Q21]  
4, 7 Grounding switch [Q9.x] (option +F259)  
8
Not in use.  
10 CIO-01 I/O module for cooling fan control [A115.x]  
11 Cooling fan and heat exchanger [G115.x]  
12 Input power cable terminals L1, L2, L3  
13 Inlet manifold with stop and drain valves  
14 Outlet manifold with stop and drain valves  
 
20 Operation principle and hardware description  
Supply module cubicle layout – frame 1×D8T  
Supply module cubicle layout – frame 1×D8T, electrical components  
1
2
3
4
M
5
6
7
8
9
M
1
DC voltage measuring/testing points  
1)  
Cabinet light ([H310.10 ], option +G301)  
2
3
4
5
6
Cabinet fan miniature circuit breaker [F115.10  
]
CIO-01 I/O module for distributed I/O bus control [A115.10  
]
Cabinet light switch ([S130.10 ], option +G301)  
Module 1 AC fuses [F3.11…  
]
]
Module 1 DC fuses [F2.11…  
Supply module [T01.1]  
7
8
Cabinet heater ([E95.10 ], option +G300)  
9
Cabinet fan [G115.10  
]
1)  
Latter number is for the first supply module cubicle. The number increases in other cubicles (if any).  
Supply module cubicle layout – frame 1×D8T, cooling circuit  
       
Operation principle and hardware description 21  
Supply module cubicle layout – frame 2×D8T  
Supply module cubicle layout – frame 2×D8T, electrical components  
1
2
4
3
M
5
6
7
M
8
9
10  
11  
12  
M
1
DC voltage measuring/testing points  
1)  
Cabinet light ([H310.10 ], option +G301)  
2
3
4
5
6
Cabinet fan miniature circuit breaker [F115.10  
]
CIO-01 I/O module for distributed I/O bus control [A115.10  
]
Cabinet light switch ([S130.10 ], option +G301)  
Module 1 AC fuses [F3.1…  
]
Module 1 DC fuses [F2.11…  
]
7
8
Supply module 1 [T01.1]  
Module 2 AC fuses [F3.4 or F3.7…  
]
9
Module 2 DC fuses [F2.21…  
]
10 Supply module [T01.2]  
11  
Cabinet heater ([E95.10 ], option +G300)  
   
22 Operation principle and hardware description  
12  
Cabinet fan [G115.10  
]
1)  
Latter number is for the first supply module cubicle. The number increases in other module cubicles (if any).  
Supply module cubicle layout – frame 2×D8T, cooling circuit  
6
4
5
6
4
2
1
5
4
7
3
7
5
1
2
3
4
5
6
7
Heat exchanger  
Inlet manifold with stop and drain valves  
Outlet manifold with stop and drain valves  
Inlet pipes (cold coolant) from main pipe to modules and heat exchanger  
Output pipes (warm coolant) to main pipe from modules and heat exchanger  
Supply modules [T01.x]  
Draining pipes (inlet draining pipe, and outlet draining pipe)  
   
Operation principle and hardware description 23  
Supply module layout - frame D8T  
1
3
1
6
5
3
2
4
4
1
AC input busbars  
DC output busbars  
Lifting eyes  
2
3
4
5
6
Coolant in and out connectors  
Fiber optic connectors  
230/115 V supply connection  
 
24 Operation principle and hardware description  
Overview of the control connections of the BCU control  
unit  
The diagram shows the control connections and interfaces of the BCU control unit.  
4
7
9
1
8
2
3
6
5
10  
1
2
3
Analog and digital I/O extension modules and  
fieldbus communication modules can be inserted  
into slots 1, 2 and 3.  
7
Control panel.  
4
Memory unit  
8
9
Fiber optic links to power modules (inverter,  
supply, brake or converter)  
5
6
Slot 4 for RDCO-0x  
Terminal blocks.  
Ethernet port. Not in use.  
10 Safety option interface. Only in use for the invert-  
er units.  
 
Operation principle and hardware description 25  
Supply unit control devices  
Overview of door switches and lights  
This figure shows and example of the door control devices. The devices and their exact  
locations varies depending on the options selected. The purpose of the devices is explained  
in the following sections.  
9
1
2
8
3
10  
11  
12  
14  
4
6
5
7
13  
15  
1…3 Not in use in multidrives  
4
Operating switch [S21]. OFF: Opens main breaker (Q1.x), disables supply unit. ON (ENABLE/RUN):  
Enables supply unit, closes main breaker (Q1.x).  
5
6
7
8
9
Emergency stop reset button and indication lamp [S62] (option +G331)  
Ground (earth) fault indicator light and reset button [S90] (option +Q954)  
Reserved for application-engineered equipment  
Emergency stop button [S61] (option +G331)  
Control panel [A59] (option +J400, or +J412)  
10 Auxiliary voltage supply breaker (switch fuse) [Q21]  
11 Voltage meter [P5.x] (option +G334)  
12 Selector switch for phase voltage meter [S5.x] (option +G334)  
13 Phase current meter(s) [P2.x] (option +G335)  
14 Grounding switch [Q9.x] (option +F259)  
15 Main supply breaker [Q1.x] (option +F255)  
Main disconnecting device [Q1.x]  
The supply unit is equipped with a main breaker ([Q1], option +F255) as standard. With this  
device, you can isolate the main circuit of the drive from the power line. The main breaker  
is withdrawable: to disconnect the drive, crank the breaker out with a separate loose handle  
(included in the delivery). For the 12-pulse supply unit and power ratings higher than 3000 A  
there are two main disconnecting devices ([Q1.1] and [Q1.2]).  
     
26 Operation principle and hardware description  
WARNING!  
The main disconnecting device does not isolate the input power terminals, AC  
voltage meters ([P5.x], option +G334) or the auxiliary circuit from the power line.  
To isolate auxiliary voltage, use the auxiliary voltage switch [Q21]. To isolate the  
input power terminals and AC voltage meters, open the main breaker of the supply  
transformer and lock it to the open position.  
If the drive is equipped with a main breaker and has a charging circuit: The main  
circuit breaker does not isolate the charging circuit. Use the charging switch [Q3].  
Auxiliary voltage switch [Q21]  
The supply unit is equipped with an auxiliary voltage switch [Q21] as standard. Using the  
switch, you can disconnect the auxiliary circuit from the power line. The switch has an  
operating handle on the cabinet door.  
Grounding switch [Q9.x]  
The supply unit can be equipped with an optional grounding switch ([Q9.x], option +F259).  
Using the switch, you can temporarily ground the main AC busbars of the supply unit during  
the maintenance work. The switch has an operating handle on the cabinet door.  
WARNING!  
The grounding switch does not ground the input power terminals of the drive or  
the auxiliary (control) voltage circuits.  
Operating switch [S21]  
The operating switch [S21] is a standard device.  
By default, the operating switch controls the unit as follows:  
The ENABLE/RUN position energizes digital input DI2 of the control unit: Control program  
receives Run/Enable command and controls the supply unit power up via the control  
unit I/O interface. The supply unit first charges the drive DC link and then starts normal  
operation. The main breaker [Q1] closes.  
The OFF position de-energizes digital input DI2 of the control unit: Control program  
does not receive Run/Enable command and it opens the main breaker [Q1]. Supply  
module stops rectifying.  
Position ENABLE/RUN (1)  
Position OFF (0)  
ENABLE / RUN  
0-1  
ENABLE / RUN  
0-1  
     
Operation principle and hardware description 27  
Emergency stop button [S61]  
The emergency stop button [S61] is an optional device (option +G331). Pressing the button  
activates an emergency stop function of the supply unit. The button locks to open position  
automatically. You must release the button before you can return to the normal operation.  
Before the restart, you also need to reset the emergency stop circuit with a separate reset  
button [S62].  
E-stop reset button [S62] and indication lamp [P62]  
The emergency stop reset button [S62] is automatically installed on the door when the  
supply unit is equipped with an emergency stop function (for example, options +Q951,  
+Q952, etc). The button is illuminated, ie it includes an indication lamp [P62]. You can reset  
the emergency stop circuit with the button.  
Note: The emergency stop options are described in separate option manuals.  
Other optional door controls  
A voltage meter is an optional device ([P5.x], option +G334). There is a meter on the  
door and a switch [S5.x] with which you can select which phase voltage value to display.  
An AC phase current meter is an optional device ([P2.x], option +G335). It is also possible  
to have three meters on the door - one for each phase currents (option +3G335).  
Tripping button for the supply breaker ([S22], option +Q959) is a push button on the  
cabinet door for the user-defined use, for example, for tripping the breaker of the supply  
transformer of the drive. The button is wired to a terminal block at the factory. The user  
connects the external circuit to be controlled on site.  
An electrical on/off push button ([S23], option +G332) on the cabinet door for tripping  
the supply unit. The button is connected in series with the operating switch. The button  
trips the Run enable signal and further the main contactor/breaker of the drive.  
Control panel  
The control panel is the user interface of the unit. For the cabinet-installed drives, the panel  
is optional (option +J400 or +J425). With the control panel, you can:  
start and stop the unit  
view and reset the fault and warning messages, and view the fault history  
view actual signals  
change parameter settings  
change between local and external control.  
To be able to start and stop the unit by the control panel, you must have the Run enable  
signal and Start enable signal on (1) on the control board. Normally this means, that you  
must have the operating switch on the cabinet door in ENABLE/RUN position. The control  
panel must also be in local control mode. You can select the mode with the Loc/Rem key  
on the panel.  
For the instructions on the use of the panel, see ACX-AP-x Assistant control panels user's  
manual (3AUA0000085685 [English]).  
PC connection  
There is a USB connector on the front of the control panel that can be used to connect a  
PC to the drive. When a PC is connected to the control panel, the control panel keypad is  
disabled.  
         
28 Operation principle and hardware description  
Fieldbus control  
You can control the unit through a fieldbus interface if the unit is equipped with an optional  
fieldbus adapter (for example, option +K454), and when you have configured the control  
program for the fieldbus control with the parameters. For information on the parameters,  
see the firmware manual.  
Note: To be able to switch the main breaker [Q1] and the supply unit on and off (Run enable  
signal) through the fieldbus, the Run enable command at digital input DI2 must be on (1).  
That is the case when the operating switch [S21] is switched to the ENABLE/RUN position.  
Type designation labels  
Each diode supply module and unit has a type designation label. The type designation  
stated on the label contains information on the specifications and configuration of the unit.  
Supply unit  
1
7
6
2
3
4
8
5
1
2
3
4
5
6
7
8
Type designation  
Frame size  
Cooling method  
Degree of protection  
UL/CSA data  
Ratings  
Valid markings  
Serial number. The first digit of the serial number refers to the manufacturing plant. The next four digits  
refer to the unit’s manufacturing year and week, respectively. The remaining digits complete the serial  
number so that there are no two units with the same number.  
   
Operation principle and hardware description 29  
Supply module  
1
7
6
2
3
4
5
8
1
2
3
4
5
6
7
8
Type designation  
Frame size  
Cooling method  
Degree of protection  
UL/CSA data  
Ratings  
Valid markings  
Serial number. The first digit of the serial number refers to the manufacturing plant. The next four digits  
refer to the unit’s manufacturing year and week, respectively. The remaining digits complete the serial  
number so that there are no two units with the same number.  
30 Operation principle and hardware description  
Type designation keys  
Type designation key of the supply unit  
The type designation describes the composition of the unit in short. The type designation  
is visible on the label (sticker) which is attached to the cabinet. The complete designation  
code is divided in subcodes:  
The first 1…18 digits form the basic code. It describes the basic construction of the unit.  
The fields in the basic code are separated by hyphens.  
The option codes follow the basic code. Each option code starts with an identifying letter  
(common for the whole product series), followed by descriptive digits. The option codes  
are separated by plus signs.  
Basic code  
Code  
Description  
ACS880 Product series  
307LC  
Default configuration: liquid-cooled cabinet-installed diode supply unit, IP42 (UL Type 1), supply  
frequency 50 Hz, control (auxiliary) voltage 230 V AC, half-controlled diode thyristor bridge, IEC  
industrial cabinet construction, main switch type: air circuit breaker, degree of protection IP42 (UL  
type 1), EMC filter (category 3, 2nd Environment), EN/IEC approved components, speed-controlled  
module cooling fans, DC busbar material copper, cable supply conductors, standard wiring material,  
power and control cabling through the bottom of the cabinet, ACS-AP-W assistant control panel,  
ACS880 diode supply control program, coated circuit boards, lead-through-type cable entries,  
multilingual door device label sticker, complete documentation in English in a USB memory stick.  
Size  
xxxxx  
Refer to the rating table in the technical data.  
Voltage range  
525…690 V. This is indicated in the type designation label as typical input voltage levels  
7
3~525/600/690 V AC.  
Option codes  
Code  
A004  
A012  
A013  
A018  
B054  
B055  
C121  
C129  
Description  
12-pulse supply connection  
50 Hz supply frequency  
60 Hz supply frequency  
Half-controlled diode-thyristor bridge  
IP42 (UL Type 1)  
IP54 (UL Type 12)  
Marine construction  
UL Listed (evaluated to both U.S. and Canadian safety requirements)  
Marine type approval. Refer to ACS880 +C132 marine type-approved cabinet-built drives supplement  
(3AXD50000039629 [English]).  
C132  
C164  
C176  
C179  
C205  
C206  
C207  
Plinth height 100 mm  
Door hinges on left  
Plinth height 200 mm  
Marine product certification issued by DNV GL  
Marine product certification issued by the American Bureau of Shipping (ABS)  
Marine product certification issued by Lloyd's Register (LR)  
       
Operation principle and hardware description 31  
Code  
C209  
C228  
C229  
E210  
F255  
F259  
F274  
G300  
G301  
G304  
G307  
G315  
G316  
G317  
G320  
G330  
G331  
G332  
G333  
G334  
G335  
G336  
G337  
G338  
G339  
G340  
G341  
G342  
G343  
G344  
G426  
H350  
H351  
H358  
H364  
H365  
H367  
H368  
J410  
Description  
Marine product certification issued by Bureau Veritas  
Marine product certification issued by China Classification Society (CCS)  
Marine product certification issued by Russian Maritime Register of Shipping (RS)  
EMC/RFI filter for 2nd environment TN (grounded) or IT (ungrounded) system, category C3  
Main circuit breaker  
Grounding (earthing) switch  
100 kA short-circuit rating  
Cabinet and module heating elements (external supply)  
Cabinet lighting  
Control (auxiliary) voltage 115 V AC  
Terminals for connecting external control voltage (230 V AC or 115 V AC, eg. UPS)  
Tin-plated copper DC busbars  
Cable supply conductors  
Supply connection by busbars  
Control (auxiliary) voltage 230 V AC  
Halogen-free wiring and materials  
Emergency stop push button on the door (red)  
Electrical disconnect push button on the door (black, opens main contactor / ACB)  
kW-meter on door  
V-meter with selector switch  
A-meter in one phase  
Arc monitoring  
Arc monitoring with current monitoring unit  
Additional wire markings  
Corrosion indicator  
Auxiliary voltage transformer  
Arc monitoring extension unit  
Bottom power cable entry  
Top power cable entry  
Cable gland plates (3 mm steel, undrilled)  
Cable gland plates (3 mm aluminum, undrilled)  
Cable gland plates (6 mm brass, undrilled)  
Control cable entry through floor of cabinet  
Control cabling through roof of cabinet  
Control panel mounting platform  
K450  
K451  
K454  
Panel bus (control of several units from one control panel)  
FDNA-01 DeviceNet™ adapter module  
FPBA-01 PROFIBUS DP adapter module  
32 Operation principle and hardware description  
Code  
K457  
K458  
K462  
K469  
K470  
Description  
FCAN-01 CANopen adapter module  
FSCA-01 RS-485 (Modbus/RTU) adapter module  
FCNA-01 ControlNet™ adapter module  
FECA-01 EtherCat adapter module  
FEPL-02 EtherPOWERLINK adapter module  
FENA-21 Ethernet adapter module for EtherNet/IP™, Modbus TCP and PROFINET IO protocols,  
2-port  
K475  
K480  
K483  
K490  
K491  
K492  
L500  
L501  
L503  
L508  
L509  
L525  
L526  
N8010  
P913  
P966  
Q951  
Q952  
Q954  
Q959  
Q963  
Q964  
Ethernet switch for PC tool or control network (for max. 6 inverter units)  
Ethernet switch with optical link for PC tool or control network (for max. 6 inverter units)  
FEIP-21 Ethernet adapter module for EtherNet/IP™  
FMBT-21 Ethernet adapter module for Modbus TCP  
FPNO-21 Ethernet adapter module for PROFINET IO  
FIO-11 analog I/O extension module  
FIO-01 digital I/O extension module  
FDCO-01 optical DDCS communication adapter module  
FDCO-02 optical DDCS communication adapter module  
RDCO-04 optical DDCS communication for BCU-xx (4xTransmitter/Receiver)  
FAIO-01 analog I/O extension module  
FDIO-01 digital I/O extension module  
IEC 61131-3 application programmability  
Special color (RAL Classic)  
Special color (other than RAL Classic)  
Emergency stop (category 0) with safety relays, by opening the main breaker/contactor  
Emergency stop (category 1) with safety relays, by opening the main breaker/contactor  
Earth fault monitoring for IT (ungrounded) systems  
Supply transformer breaker disconnect push button (red, wired to terminals) on the door  
Emergency stop (category 0) with safety relays, by activating the Safe torque off function  
Emergency stop (category 1) with safety relays, by activating the Safe torque off function  
Emergency stop (configurable for category 0 or 1) with FSO-xx safety functions module, by activating  
the Safe torque off function  
Q979  
Q984  
R700  
Emergency stop button monitoring  
Documentation/manuals in English  
Type designation key of the diode supply module  
The type designation describes the composition of the module in short. The complete  
designation code is divided in subcodes:  
The first 1…18 digits form the basic code. It describes the basic construction of the unit.  
The fields in the basic code are separated by hyphens.  
The option codes follow the basic code. Each option code starts with an identifying letter  
(common for the whole product series), followed by descriptive digits. The option codes  
are separated by plus signs.  
Code  
Description  
Basic codes  
 
Operation principle and hardware description 33  
Code  
Description  
ACS880 Product series  
304LC  
Construction: Liquid cooled diode supply module, IP00 (UL Open Type), AC-choke, circuit boards  
with coating, CE approval  
Size  
0780A  
Refer to the technical data.  
Voltage range  
7
525…690 V. This is indicated in the type designation label as typical input voltage levels  
3~525/600/690 V AC.  
Plus codes  
A018  
C132  
C209  
P904  
P909  
P911  
Half-controlled diode-thyristor bridge (as standard)  
Marine type approval  
Marine product certification (only with +C132)  
Extended warranty 24/30  
Extended warranty 36/42  
Extended warranty 60/66  
34  
Electrical installation 35  
3
Electrical installation  
Contents of this chapter  
This chapter instructs how to check the insulation of the assembly and how to install the  
input power cables and control cables. The information is valid for ACS880-307LC…+A018  
diode supply units.  
For more information on cable selection, protections, etc., see ACS880 multidrive cabinets  
and modules electrical planning instructions (3AUA0000102324 [English]).  
WARNING!  
Obey the safety instructions given in ACS880 liquid-cooled multidrive  
cabinets and modules safety instructions (3AXD50000048633 [English]).  
If you ignore the safety instructions, injury or death, or damage to the  
equipment can occur.  
If you are not a qualified electrical professional, do not do installation or  
maintenance work.  
   
36 Electrical installation  
Electrical safety precautions  
These electrical safety precautions are for all personnel who do work on the drive, motor  
cable or motor.  
WARNING!  
Obey these instructions. If you ignore them, injury or death, or damage to the  
equipment can occur.  
If you are not a qualified electrical professional, do not do installation or  
maintenance work.  
Go through these steps before you begin any installation or maintenance work.  
1. Clearly identify the work location and equipment.  
2. Disconnect all possible voltage sources. Make sure that re-connection is not possible.  
Lock out and tag out.  
Open the main disconnecting device of the drive.  
Open the charging switch if present.  
Open the disconnector of the supply transformer. (The main disconnecting device  
in the drive cabinet does not disconnect the voltage from the AC input power busbars  
of the drive cabinet.)  
Close the grounding switch or switches ([Q9], option +F259) if present. Do not use  
excessive force as the switch has electromagnetic interlocking.  
If the drive is equipped with a DC/DC converter unit (optional): Open the DC  
switch-disconnector ([Q11], option +F286) of the DC/DC converter. Open the  
disconnecting device of the energy storage connected to the DC/DC converter unit  
(outside the drive cabinet).  
Open the auxiliary voltage switch-disconnector (if present), and all other possible  
disconnecting devices that isolate the drive from dangerous voltage sources.  
In the liquid cooling unit (if present), open the switch-disconnector of the cooling  
pumps.  
If you have a permanent magnet motor connected to the drive, disconnect the motor  
from the drive with a safety switch or by other means.  
Disconnect all dangerous external voltages from the control circuits.  
After you disconnect power from the drive, always wait 5 minutes to let the  
intermediate circuit capacitors discharge before you continue.  
3. Protect any other energized parts in the work location against contact.  
4. Take special precautions when close to bare conductors.  
 
Electrical installation 37  
5. Measure that the installation is de-energized. If the measurement requires removal or  
disassembly of shrouding or other cabinet structures, obey the local laws and regulations  
applicable to live working (including – but not limited to – electric shock and arc  
protection).  
Before and after measuring the installation, verify the operation of the voltage tester  
on a known voltage source.  
Make sure that the voltage between the drive input power terminals (L1, L2, L3)  
and the grounding (PE) busbar is zero.  
Make sure that the voltage between the drive output terminals (T1/U, T2/V, T3/W)  
and the grounding (PE) busbar is zero.  
Make sure that the voltage between the drive DC busbars (+ and -) and the  
grounding (PE) busbar is zero.  
WARNING!  
The busbars inside the cabinet of liquid-cooled drives are partially coated.  
Measurements made through the coating are potentially unreliable, so only  
measure at uncoated portions. Note that the coating does not constitute a safe  
or touch-proof insulation.  
6. If the drive is not equipped with a grounding switch, install temporary grounding as  
required by the local regulations.  
7. Ask the person in control of the electrical installation work for a permit to work.  
General notes  
Static electricity  
WARNING!  
Use a grounding wristband when you handle printed circuit boards. Do not touch  
the boards unnecessarily. The boards contain components sensitive to electrostatic  
discharge.  
Optical components  
WARNING!  
Obey these instructions. If you ignore them, damage to the equipment can occur.  
Handle the fiber optic cables with care.  
When you unplug the fiber optic cables, always hold the connector, not the cable itself.  
Do not touch the ends of the fibers with bare hands as the ends are extremely sensitive  
to dirt.  
Do not bend the fiber optic cables too tightly. The minimum allowed bend radius is  
35 mm (1.4 in).  
     
38 Electrical installation  
Measuring the insulation  
Measuring the insulation of the drive  
WARNING!  
Do not do any voltage withstand or insulation resistance tests on any part of the  
drive as testing can damage the drive. Every drive has been tested for insulation  
between the main circuit and the chassis at the factory. Also, there are  
voltage-limiting circuits inside the drive which cut down the testing voltage  
automatically.  
Measuring the insulation of the input power cable  
Before you connect the input power cable to the drive, measure its insulation according to  
local regulations.  
Connecting the input power cables  
Connection diagram – 6-pulse supply unit  
This is a connection diagram for the 6-pulse supply unit. See also the delivery specific circuit  
diagrams.  
1
L1  
L2  
L3  
PE  
2
1
2
Fuses or other protection means for the short-circuit protection of the cable.  
Grounding of the cable shield at the cable entry (360 degrees grounding).  
Additional information:  
• See the technical data for the dimensions of the cable entries, and the dimensions and tightening torques  
of the terminals.  
• Use a separate PE conductor in addition if the conductivity of the shields does not meet the requirement for  
the PE conductor.  
• See ACS880 multidrive cabinets and modules electrical planning instructions [3AUA0000102324 (English)]  
for the cable selection instructions.  
Connection diagram – 12-pulse supply unit (option +A004)  
This is a connection diagram for the 12-pulse supply unit (option +A004). See also the  
delivery specific circuit diagrams.  
           
Electrical installation 39  
1
1L1  
1L2  
1L3  
PE  
2L1  
2L2  
2L3  
PE  
2
1
2
Fuses or other protection means for the short-circuit protection of the cable.  
Grounding of the cable shield at the cable entry (360 degrees grounding).  
Additional information:  
• See the technical data for the dimensions of the cable entries, and the dimensions and tightening torques  
of the terminals.  
• If the conductivity of the shields does not meet the requirement for the PE conductor, use a separate PE  
conductor in addition.  
• See ACS880 multidrive cabinets and modules electrical planning instructions (3AUA0000102324 [English])  
for the cable selection instructions.  
Connection procedure – bottom cable entry  
See the technical data for the dimensions of the cable entries, and the dimensions and  
tightening torques of the terminals.  
WARNING!  
Apply grease to stripped aluminum conductors before attaching them to non-coated  
aluminum cable lugs. Obey the grease manufacturer’s instructions.  
Aluminum-aluminum contact can cause oxidation in the contact surfaces.  
1. Disconnect the drive from the AC power line and make sure it is safe to start the work.  
2. Open the door of the incoming cubicle.  
3. Remove the shrouding covering the input terminals.  
4. Peel off 3 to 5 cm of the outer insulation of the cables above the lead-through plate for  
360° high-frequency grounding.  
5. Prepare the ends of the cables.  
6. Remove the rubber grommet from the cable entry plate for the cable to be connected.  
Cut adequate hole into the rubber grommet. Slide the grommet onto the cable. Slide  
the cable through the cable entry and attach the grommets to the holes.  
7. Fasten the conductive sleeve of the cable entry to the cable shield with cable ties.  
8. Tie up the unused conductive sleeves with cable ties.  
9. Connect the twisted shield of the cable to the PE busbar of the cabinet. Tighten the  
screw to the torque given in the technical data.  
10. Connect the phase conductors of the input cable to the L1, L2 and L3 terminals. Tighten  
the screws to the torque given in the technical data.  
 
40 Electrical installation  
11. Reinstall the shrouding removed earlier.  
12. Close the door.  
3
PE  
PE  
Electrical installation 41  
8
7
6
10  
9
42 Electrical installation  
Connecting the external power supply cable for the auxiliary  
circuit (option +G307)  
WARNING!  
Obey the safety instructions of the drive. If you ignore them, injury or death, or  
damage to the equipment can occur.  
If you are not a qualified electrical professional, do not do installation or  
maintenance work.  
For the connection diagram, see the delivery-specific circuit diagrams. For the auxiliary  
circuit current consumption, see the delivery-specific technical documentation.  
Wiring the functional safety options  
The wiring instructions for the functional safety options such as +Q951, +Q952, etc are in  
separate option manuals.  
Connecting the control cables  
See the chapter on control units for the default I/O connections. Note that the default I/O  
connections can be affected by some options. See the circuit diagrams delivered with the  
drive for the actual wiring.  
Control cable connection procedure  
WARNING!  
Obey the safety instructions given in ACS880 liquid-cooled multidrive  
cabinets and modules safety instructions (3AXD50000048633 [English]).  
If you ignore the safety instructions, injury or death, or damage to the  
equipment can occur.  
If you are not a qualified electrical professional, do not do installation or  
maintenance work.  
1. Stop the drive (if running) and do the steps in section Electrical safety  
precautions (page 36) before you start the work.  
2. Run the control cables into the cabinet as described in section Grounding the outer  
3. Route the control cables as described in section Routing the control cables inside the  
4. Connect the control cables as described in section Connecting control cabling.  
Grounding the outer shields of the control cables at the cabinet entry  
Ground the outer shields of all control cables 360 degrees at the EMI conductive cushions  
as follows (example constructions are shown below, the actual hardware may vary):  
1. Loosen the tightening screws of the EMI conductive cushions and pull the cushions  
apart.  
2. Cut adequate holes to the rubber grommets in the entry plate and put the cables through  
the grommets and the cushions.  
         
Electrical installation 43  
3. Strip off the cable plastic sheath above the entry plate just enough to ensure proper  
connection of the bare shield and the EMI conductive cushions.  
4. Tighten the two tightening screws so that the EMI conductive cushions press tightly  
round the bare shield.  
4
3
1
2
Note 1: Keep the shields continuous as close to the connection terminals as possible.  
Secure the cables mechanically at the entry strain relief.  
Note 2: If the outer surface of the shield is non-conductive:  
Cut the shield at the midpoint of the bare part. Be careful not to cut the conductors or  
the grounding wire (if present).  
Turn the shield inside out to expose its conductive surface.  
Cover the turned shield and the stripped cable with copper foil to keep the shielding  
continuous.  
A
B
C
A
B
C
1
2
3
4
Stripped cable  
Conductive surface of the shield exposed  
Stripped part covered with copper foil  
Cable shield  
2
2
1
3
4
Copper foil  
Shielded twisted pair  
Grounding wire  
5
Note for top entry of cables: When each cable has its own rubber grommet, sufficient IP  
and EMC protection can be achieved. However, if there is more than one cable per grommet,  
plan the installation beforehand as follows:  
1. Make a list of the cables coming to the cabinet.  
2. Sort the cables going to the left into one group and the cables going to the right into  
another group to avoid unnecessary crossing of cables inside the cabinet.  
3. Sort the cables in each group according to size.  
44 Electrical installation  
4. Group the cables for each grommet as follows ensuring that each cable has a proper  
contact to the cushions on both sides.  
Cable diameter in mm  
Max. number of cables per grommet  
≤ 13  
≤ 17  
< 25  
≥ 25  
4
3
2
1
5. Arrange the bunches according to size from thickest to the thinnest between the EMI  
conductive cushions.  
6. If more than one cable go through a grommet, seal the grommet by applying Loctite  
5221 inside the grommet.  
Routing the control cables inside the cabinet  
Use the existing trunking in the cabinet wherever possible. Use sleeving if cables are laid  
against sharp edges. When running cables to or from a swing-out frame, leave enough  
slack at the hinge to allow the frame to open fully.  
Connecting control cabling  
Connect the conductors to the appropriate terminals. Refer to the wiring diagrams delivered  
with the drive.  
Connect the inner twisted pair shields and all separate grounding wires to the grounding  
clamps closest to the terminals.  
The drawing below represents the grounding of the control cabling when connecting to a  
terminal block inside the cabinet. The grounding is done in the same way when connecting  
directly to a component such as the control unit.  
Notes:  
   
Electrical installation 45  
Do not ground the outer shield of the cable here since it is grounded at the cable entry.  
Keep any signal wire pairs twisted as close to the terminals as possible. Twisting the  
wire with its return wire reduces disturbances caused by inductive coupling.  
At the other end of the cable, leave the shields unconnected or ground them indirectly via  
a high-frequency capacitor with a few nanofarads, eg. 3.3 nF / 630 V. The shield can also  
be grounded directly at both ends if they are in the same ground line with no significant  
voltage drop between the end points.  
46 Electrical installation  
Connecting a PC  
WARNING!  
Do not connect the PC directly to the control panel connector of the control unit  
as this can cause damage.  
A PC (with eg, the Drive composer PC tool) can be connected as follows:  
1. Connect an ACx-AP-x control panel to the unit either  
by inserting the control panel into the panel holder or platform, or  
by using an Ethernet (eg, Cat 5e) networking cable.  
2. Remove the USB connector cover on the front of the control panel.  
3. Connect an USB cable (Type A to Type Mini-B) between the USB connector on the  
control panel (3a) and a free USB port on the PC (3b).  
4. The panel will display an indication whenever the connection is active.  
5. See the documentation of the PC tool for setup instructions.  
USB connected  
4
2
?
Stop  
Start  
Loc/Rem  
?
Stop  
Start  
Loc/Rem  
2
3b  
3a  
 
The control unit 47  
4
The control unit  
Contents of this chapter  
This chapter  
describes the connections of the control unit  
contains the specifications of the inputs and outputs of the control unit.  
   
48 The control unit  
BCU-x2 layout  
Description  
I/O  
I/O terminals (see following diagram)  
SLOT 1  
I/O extension, encoder interface or fieldbus  
adapter module connection. (This is the  
sole location for an FDPI-02 diagnostics  
and panel interface.)  
SLOT 2  
SLOT 3  
I/O extension, encoder interface or fieldbus  
adapter module connection  
I/O extension, encoder interface, fieldbus  
adapter or FSO-xx safety functions module  
connection  
SLOT 4  
RDCO-0x DDCS communication option  
module connection  
X205  
Memory unit connection  
BATTERY  
Holder for real-time clock battery (BR2032)  
AI1  
Mode selector for analog input AI1 (I =  
current, U = voltage)  
AI2  
Mode selector for analog input AI2 (I =  
current, U = voltage)  
D2D TERM  
Termination switch for drive-to-drive link  
(D2D)  
DICOM=  
DIOGND  
Ground selection. Determines whether  
DICOM is separated from DIOGND (ie. the  
common reference for the digital inputs  
floats). See the ground isolation diagram.  
7-segment display  
Multicharacter indications are displayed as repeated se-  
quences of characters  
(“U” is indicated briefly before “o”.)  
Control program running  
Control program startup in progress  
(Flashing) Firmware cannot be started.  
Memory unit missing or corrupted  
Firmware download from PC to control unit  
in progress  
At power-up, the display may show short  
indications of eg. “1”, “2”, “b” or “U”. These  
are normal indications immediately after  
power-up. If the display ends up showing  
any other value than those described, it in-  
dicates a hardware failure.  
 
The control unit 49  
Description  
XAI  
Analog inputs  
Analog outputs  
XAO  
XDI  
Digital inputs, Digital input interlock (DIIL)  
Digital input/outputs  
XRO3  
XRO2  
XRO1  
XD24  
XDIO  
XPOW  
XAO  
XDIO  
XD2D  
XD24  
XETH  
XPOW  
XRO1  
XRO2  
XRO3  
XSTO  
Drive-to-drive link  
+24 V output (for digital inputs)  
Ethernet port – Not in use  
External power input  
Relay output RO1  
XDI  
XAI  
Relay output RO2  
X485  
Relay output RO3  
Safe torque off connection (input signals)  
XSTO OUT Safe torque off connection (to inverter mod-  
ules)  
XSTO  
OUT  
XD2D  
XSTO  
X12  
(On the opposite side) Connection for FSO-  
xx safety functions module (optional)  
X13  
Control panel / PC connection  
Not in use  
X485  
V1T/V1R,  
V2T/V2R  
Fiber optic connection to modules 1 and 2  
(VxT = transmitter, VxR = receiver)  
V3T/V3R  
Fiber optic connection to modules 3…7 (BCU-  
12/22 only)  
V7T/V7R  
(VxT = transmitter, VxR = receiver)  
V8T/V8R  
Fiber optic connection to modules 8…12  
(BCU-22 only)  
V12T/V12R (VxT = transmitter, VxR = receiver)  
SD CARD Data logger memory card for inverter module  
communication  
BATT OK  
Real-time clock battery voltage is higher than  
2.8 V. If the LED is off when the control unit  
is powered, replace the battery.  
FAULT  
The control program has generated a fault.  
See the firmware manual of the supply/invert-  
er unit.  
PWR OK  
WRITE  
Internal voltage supply is OK  
Writing to memory card in progress. Do not  
remove the memory card.  
50 The control unit  
Default I/O diagram of the supply control unit  
The diagram below shows the default I/O connections on the supply control unit (A51), and  
describes the use of the connections in the supply unit. Under normal circumstances, the  
factory-made wiring should not be changed.  
The wire size accepted by all screw terminals (for both stranded and solid wire) is 0.5 …  
2.5 mm2 (24…12 AWG). The torque is 0.5 N·m (5 lbf·in).  
Terminal  
Description  
XD2D  
Drive-to-drive link  
1
B
1
2
3
4
2
3
4
A
Not in use by default  
BGND  
Shield  
1)  
D2D.TERM  
Drive-to-drive link termination switch  
RS485 connection  
X485  
5
6
7
8
B
5
6
7
8
A
Cooling fan monitoring (CIO module)  
BGND  
Shield  
XRO1, XRO2, XRO3  
Relay outputs  
Norm. closed  
Common  
11  
12  
13  
21  
22  
NC  
2)  
XRO1: Running (Energized = running)  
COM  
NO  
250 V AC / 30 V DC, 2 A  
Norm. open  
Norm. closed  
Common  
11  
12  
13  
21  
22  
23  
31  
32  
33  
NC  
XRO2: Fault (-1) (Energized = no fault)  
250 V AC / 30 V DC, 2 A  
COM  
Note: If drive is equipped with a liquid cool-  
ing unit, the relay output controls the cooling  
unit start signal. Then the selection Fault(-  
1) may also be changed to Started by bit  
12 of parameter 195.12. See ACS880 diode  
supply control program firmware manual  
(3AUA0000103295 [English]).  
23  
NO  
Norm. open  
31  
32  
33  
NC  
Norm. closed  
Common  
3)  
XRO3: MCB ctrl (Energized = closes  
COM  
NO  
main contactor/breaker) 250 V AC /  
30 V DC, 2 A  
Norm. open  
4)  
XSTO, XSTO OUT  
Safe torque off  
1
2
3
4
5
6
7
8
OUT  
1
2
3
4
5
6
7
8
SGND  
IN1  
XSTO: Factory connection. Both circuits must be closed for the drive to start  
(IN1 and IN2 must be connected to OUT).  
IN2  
IN1  
SGND  
IN2  
XSTO OUT: Not in use.  
Digital inputs  
SGND  
XDI  
 
The control unit 51  
Terminal  
Description  
1
DI1  
DI2  
DI3  
DI4  
DI5  
DI6  
DIIL  
Temp fault (0 = overtemperature)  
1
2
3
4
5
6
7
2
3
4
5
6
7
Run enable (1 = run enable)  
MCB feedback (0 = main contactor/breaker open)  
Auxiliary circuit breaker fault  
Not in use by default. Can be used for eg. earth fault monitoring.  
Reset (0 -> 1 = fault reset)  
Not in use by default. Can be used for eg. emergency stop.  
Digital input/outputs  
XDIO  
1
2
3
4
DIO1  
Not in use by default  
1
2
3
4
DIO2  
Not in use by default  
DIOGND  
DIOGND  
Digital input/output ground  
Digital input/output ground  
Auxiliary voltage output  
XD24  
5)  
1
2
3
4
+24VD  
DICOM  
+24VD  
DIOGND  
+24 V DC 200 mA  
5
6
7
8
Digital input ground  
+24 V DC 200 mA  
Digital input/output ground  
6)  
DICOM=DIOGND  
Ground selection switch  
XAI  
Analog inputs, reference voltage output  
10 V DC, RL 1…10 kohm  
-10 V DC, RL 1…10 kohm  
Ground  
1
2
3
4
5
6
7
+VREF  
-VREF  
AGND  
AI1+  
1
2
3
4
5
6
7
7)  
Not in use by default. 0(2)…10 V, Rin > 200 kohm  
AI1-  
AI2+  
8)  
Not in use by default. 0(4)…20 mA, Rin = 100 ohm  
AI2-  
AI1  
AI2  
AI1 current/voltage selection switch  
AI2 current/voltage selection switch  
Analog outputs  
XAO  
1
2
3
4
AO1  
1
2
3
4
Zero (no signal indicated) 0…20 mA, RL < 500 ohm  
AGND  
AO2  
Zero (not signal indicated) 0…20 mA, RL < 500 ohm  
AGND  
XPOW  
External power input  
1
2
3
4
+24VI  
GND  
+24VI  
GND  
1
2
3
4
24 V DC, 2.05 A  
X12  
X13  
Not in use in supply units  
Control panel connection  
52 The control unit  
Terminal  
Description  
X205  
Memory unit connection  
1)  
Must be set to ON when the supply unit is the first or last unit on the drive-to-drive (D2D) link. On intermediate units, set  
termination to OFF.  
Default use of the signal in the control program. The use can be changed by a parameter. See also the delivery-specific  
circuit diagrams.  
2)  
3)  
4)  
Use of the signal in the control program (fixed). See also the delivery-specific circuit diagrams.  
This input only acts as a true Safe torque off input in inverter units. In other applications (such as a supply or brake unit),  
de-energizing the IN1 and/or IN2 terminal will stop the unit but not constitute a true safety function.  
5)  
6)  
Total load capacity of these outputs is 4.8 W (200 mA at 24 V) minus the power taken by DIO1 and DIO2.  
Determines whether DICOM is separated from DIOGND (ie, common reference for digital inputs floats). ON: DICOM  
connected to DIOGND. OFF: DICOM and DIOGND separate.  
7)  
8)  
Current [0(4)…20 mA, Rin = 100 ohm] or voltage [0(2)…10 V, Rin > 200 kohm] input selected by switch AI1. Change of  
setting requires reboot of control unit.  
Current [0(4)…20 mA, Rin = 100 ohm] or voltage [0(2)…10 V, Rin > 200 kohm] input selected by switch AI2. Change of  
setting requires reboot of control unit.  
External power supply for the control unit (XPOW)  
The control unit is powered from a 24 V DC, 2 A supply through terminal block XPOW. With  
a type BCU control unit, a second supply can be connected to the same terminal block for  
redundancy.  
Using an external supply is recommended if  
the control unit needs to be kept operational during input power breaks, for example,  
because of continuous fieldbus communication  
immediate restart is needed after a power break (that is, no control unit power-up delay  
is allowed).  
The X485 connector  
The X485 provides a connection for optional CIO-01 I/O module. The following diagram  
shows the wiring for the CIO module.  
BCU  
CIO  
CIO  
X485  
B
X485  
B
X485  
B
A
A
A
GND  
SHIELD  
BGND  
SHIELD  
GND  
SHIELD  
         
The control unit 53  
Safe torque off (XSTO, XSTO OUT)  
Note: The XSTO input only acts as a true Safe torque off input on the inverter control unit.  
De-energizing the IN1 and/or IN2 terminals of other units (supply, DC/DC converter, or brake  
unit) will stop the unit but not constitute a true safety function.  
FSO-xx safety functions module connection (X12)  
See the user manual of the FSO-xx module. Note that the FSO-xx safety functions module  
is not in use in supply, DC/DC converter or brake units.  
SDHC memory card slot  
The BCU-x2 has an on-board data logger that collects real-time data from the power modules  
to help fault tracing and analysis. The data is stored onto the SDHC memory card inserted  
into the SD CARD slot and can be analyzed by ABB service personnel.  
     
54 The control unit  
Connector data  
Power supply (XPOW)  
Connector pitch 5 mm, wire size 2.5 mm2  
24 V (±10%) DC, 2 A  
External power input.  
Two supplies can be connected for redundancy.  
Relay outputs RO1…RO3  
(XRO1…XRO3)  
Connector pitch 5 mm, wire size 2.5 mm2  
250 V AC / 30 V DC, 2 A  
Protected by varistors  
+24 V output (XD24:2 and XD24:4)  
Connector pitch 5 mm, wire size 2.5 mm2  
Total load capacity of these outputs is 4.8 W (200 mA / 24 V) minus  
the power taken by DIO1 and DIO2.  
Digital inputs DI1…DI6 (XDI:1…XDI:6) Connector pitch 5 mm, wire size 2.5 mm2  
24 V logic levels: “0” < 5 V, 1” > 15 V  
Rin: 2.0 kohm  
Input type: NPN/PNP (DI1…DI5), NPN (DI6)  
Hardware filtering: 0.04 ms, digital filtering up to 8 ms  
DI6 (XDI:6) can alternatively be used as an input for a PTC sensor.  
“0” > 4 kohm, “1” < 1.5 kohm.  
Imax: 15 mA (DI1…DI5), 5 mA (DI6)  
Start interlock input DIIL (XDI:7)  
Connector pitch 5 mm, wire size 2.5 mm2  
24 V logic levels: “0” < 5 V, 1” > 15 V  
Rin: 2.0 kohm  
Input type: NPN/PNP  
Hardware filtering: 0.04 ms, digital filtering up to 8 ms  
Digital inputs/outputs DIO1 and DIO2  
(XDIO:1 and XDIO:2)  
Connector pitch 5 mm, wire size 2.5 mm2  
As inputs: 24 V logic levels: “0” < 5 V, 1” > 15 V. Rin: 2.0 kohm. Fil-  
Input/output mode selection by paramet- tering: 1 ms.  
ers.  
As outputs: Total output current from +24VD is limited to 200 mA  
DIO1 can be configured as a frequency  
input (0…16 kHz with hardware filtering  
of 4 microseconds) for 24 V level square  
wave signal (sinusoidal or other wave  
form cannot be used). DIO2 can be con-  
figured as a 24 V level square wave fre-  
quency output. See the firmware manual,  
parameter group 111/11.  
+24VD  
DIOx  
RL  
DIOGND  
Reference voltage for analog inputs  
+VREF and -VREF (XAI:1 and XAI:2)  
Connector pitch 5 mm, wire size 2.5 mm2  
10 V ±1% and –10 V ±1%, Rload 1…10 kohm  
Maximum output current: 10 mA  
Analog inputs AI1 and AI2  
(XAI:4 … XAI:7).  
Connector pitch 5 mm, wire size 2.5 mm2  
Current input: –20…20 mA, Rin = 100 ohm  
Voltage input: –10…10 V, Rin > 200 kohm  
Differential inputs, common mode range ±30 V  
Sampling interval per channel: 0.25 ms  
Hardware filtering: 0.25 ms, adjustable digital filtering up to 8 ms  
Resolution: 11 bit + sign bit  
Current/voltage input mode selection by  
switches  
Inaccuracy: 1% of full scale range  
 
The control unit 55  
Analog outputs AO1 and AO2 (XAO)  
Connector pitch 5 mm, wire size 2.5 mm2  
0…20 mA, Rload < 500 ohm  
Frequency range: 0…500 Hz  
Resolution: 11 bit + sign bit  
Inaccuracy: 2% of full scale range  
XD2D connector  
Connector pitch 5 mm, wire size 2.5 mm2  
Physical layer: RS-485  
Transmission rate: 8 Mbit/s  
Cable type: Shielded twisted-pair cable with a twisted pair for data  
and a wire or another pair for signal ground (nominal impedance  
100 … 165 ohm, for example Belden 9842)  
Maximum length of link: 50 m (164 ft)  
Termination by switch  
RS-485 connection (X485)  
Connector pitch 5 mm, wire size 2.5 mm2  
Physical layer: RS-485  
Safe torque off connection (XSTO)  
Connector pitch 5 mm, wire size 2.5 mm2  
Input voltage range: -3…30 V DC  
Logic levels: “0” < 5 V, 1” > 17 V.  
Note: For the unit to start, both connections must be “1”. This applies  
to all control units (including drive, inverter, supply, brake, DC/DC  
converter etc. control units), but true Safe torque off functionality is  
only achieved through the XSTO connector of the drive/inverter  
control unit.  
EMC (immunity) according to IEC 61326-3-1  
Safe torque off output (XSTO OUT)  
Control panel connection (X13)  
Ethernet connection (XETH)  
Connector pitch 5 mm, wire size 2.5 mm2  
To STO connector of inverter module.  
Connector: RJ-45  
Cable length < 3 m  
Connector: RJ-45  
This connection is not supported by the firmware.  
SDHC memory card slot (SD CARD)  
Memory card type: SDHC  
Maximum memory size: 4 GB  
The terminals of the control unit fulfill the Protective Extra Low Voltage (PELV) requirements. The PELV re-  
quirements of a relay output are not fulfilled if a voltage higher than 48 V is connected to the relay output.  
56 The control unit  
BCU-x2 ground isolation diagram  
XPOW  
+24VI  
GND  
+24VI  
GND  
1
2
3
4
XAI  
+VREF  
-VREF  
AGND  
AI1+  
AI1-  
AI2+  
1
2
3
4
5
6
7
**  
AI2-  
XAO  
AO1  
AGND  
AO2  
1
2
3
4
AGND  
XD2D  
B
A
1
2
3
4
BGND  
SHIELD  
XRO1, XRO2, XRO3  
NC  
COM  
NO  
NC  
COM  
NO  
NC  
COM  
NO  
11  
12  
13  
21  
22  
23  
31  
32  
33  
XD24  
+24VD  
DICOM  
+24VD  
5
6
7
8
DIOGND  
XDIO  
DIO1  
DIO2  
DIOGND  
DIOGND  
1
2
3
4
XDI  
*
DI1  
DI2  
DI3  
DI4  
DI5  
DI6  
DIIL  
1
2
3
4
5
6
7
XSTO  
OUT  
SGND  
IN1  
1
2
3
4
IN2  
XSTO OUT  
IN1  
SGND  
IN2  
5
6
7
8
SGND  
*Ground selector (DICOM=DIOGND) settings  
DICOM=DIOGND: ON  
All digital inputs share a common ground (DICOM connected to DIOGND). This is the default setting.  
DICOM=DIOGND: OFF  
Ground of digital inputs DI1…DI5 and DIIL (DICOM) is isolated from DIO signal ground (DIOGND). Isolation  
voltage 50 V.  
**Common mode voltage between each AI input and AGND is +30 V  
 
Installation checklist 57  
5
Installation checklist  
Contents of this chapter  
This chapter contains a checklist of the mechanical and electrical installation of the drive.  
Checklist  
Examine the mechanical and electrical installation of the drive before start-up. Go through  
the checklist together with another person.  
WARNING!  
Obey the safety instructions of the drive. If you ignore them, injury or death, or  
damage to the equipment can occur.  
If you are not a qualified electrical professional, do not do installation or  
maintenance work.  
WARNING!  
Stop the drive and do the steps in section Electrical safety precautions (page 36)  
before you start the work.  
Make sure that …  
The ambient operating conditions meet the drive ambient conditions specification, and enclosure rating  
(IP code or UL enclosure type).  
The supply voltage matches the nominal input voltage of the drive. See the type designation label.  
The insulation resistance of the input power cable, motor cable and motor is measured according to  
local regulations and the manuals of the drive.  
The drive cabinet is attached to the floor, and if necessary due to vibration etc, also by its top to the  
wall or roof.  
The drive module is fastened properly to the cabinet.  
     
58 Installation checklist  
Make sure that …  
If the drive is connected to a network other than a symmetrically grounded TN-S system: You have  
done all the required modifications (for example, you may need to disconnect the EMC filter or ground-  
to-phase varistor). See the electrical installation instructions in the supply unit manual.  
Appropriate DC fuses are installed.  
There is an adequately sized protective earth (ground) conductor(s) between the drive and the  
switchboard, the conductor is connected to correct terminal, and the terminal is tightened to the correct  
torque.  
Proper grounding has also been measured according to the regulations.  
If the drive is equipped with a DC/DC converter unit: There is an adequately sized protective earth  
(ground) conductor between the energy storage and the DC/DC converter, the conductor has been  
connected to appropriate terminal, and the terminal has been tightened to the proper torque. Proper  
grounding has also been measured according to the regulations.  
If the drive is equipped with a DC/DC converter unit: The energy storage cable has been connected to  
the correct terminals of the DC/DC converter and energy storage, and the terminals have been tightened  
to the proper torque.  
If the drive is equipped with a DC/DC converter unit: The energy storage has been equipped with fuses  
for protecting energy storage cable in a cable short-circuit situation.  
If the drive is equipped with a DC/DC converter unit: The energy storage has been equipped with a  
disconnecting device.  
The input power cable is connected to the correct terminals, the phase order is correct, and the terminals  
are tightened to the correct torque.  
There is an adequately sized protective earth (ground) conductor between the motor and the drive,  
and the conductor is connected to the correct terminal, and the terminal is tightened to the correct  
torque.  
Proper grounding has also been measured according to the regulations.  
The motor cable is connected to the correct terminals, the phase order is correct, and the terminals  
are tightened to the correct torque.  
The motor cable is routed away from other cables.  
No power factor compensation capacitors are connected to the motor cable.  
If an external brake resistor is connected to the drive: There is an adequately sized protective earth  
(ground) conductor between the brake resistor and the drive, and the conductor is connected to the  
correct terminal, and the terminals are tightened to the correct torque. Proper grounding has also been  
measured according to the regulations.  
If an external brake resistor is connected to the drive: The brake resistor is connected to the correct  
terminals, and the terminals are tightened to the correct torque.  
If an external brake resistor is connected to the drive: The brake resistor cable is routed away from  
other cables.  
The control cables are connected to the correct terminals, and the terminals are tightened to the correct  
torque.  
The voltage setting of the auxiliary voltage transformers (if any) is correct. See the electrical installation  
instructions.  
If a drive bypass connection will be used: The direct-on-line contactor of the motor and the drive output  
contactor are either mechanically and/or electrically interlocked, that is, they cannot be closed at the  
same time. A thermal overload device must be used for protection when bypassing the drive. Refer to  
local codes and regulations.  
There are no tools, foreign objects or dust from drilling inside the drive.  
Cover(s) of the motor connection box are in place. Cabinet shrouds are in place and doors are closed.  
The motor and the driven equipment are ready for power-up.  
The coolant connections between cubicles (if any) and to the cooling circuit are tight.  
If the drive is equipped with a cooling unit: Refer to the cooling unit documentation for specific tasks.  
Start-up 59  
6
Start-up  
Contents of this chapter  
This chapter contains start-up instructions of the diode supply unit.  
The underlined tasks are necessary only for certain cases. The symbols in brackets, for  
example [Q1], refer to the item designations used in the circuit diagrams. If a task is valid  
only for a certain option device or feature, the option code is given in brackets, for example,  
(option +F259).  
Note: The instructions do not cover all possible supply unit configurations. Always refer to  
the delivery-specific circuit diagrams when proceeding with the start-up. This default start-up  
procedure is valid for a supply unit equipped with a main breaker ([Q1], option +F255) and  
an external auxiliary voltage supply (option +G307).  
Note: For the functional safety options, the start-up instructions are given in separate option  
manuals. Reserve the necessary option manuals at hand before the supply unit start-up.  
Obey their start-up instructions.  
WARNING!  
Obey the safety instructions during the start-up procedure. See ACS880  
liquid-cooled multidrive cabinets and modules safety instructions  
(3AXD50000048633 [English]). If you ignore the safety instructions, injury  
or death, or damage to the equipment can occur.  
If you are not a qualified electrical professional, do not do installation or  
maintenance work.  
   
60 Start-up  
Start-up procedure  
Basic checks with no voltage connected  
Action  
Disconnect the drive from the AC power line and make sure it is safe to start the work. See section  
Set the current trip limits of the main breaker. The trip limits have been preset to generic values by the  
breaker manufacturer. The generic limits do not correspond the protection requirements of the applic-  
ation.  
General rule  
Make sure that the selectivity condition is fulfilled, that is the breaker trips at the lower current than the  
protection device of the supplying network, and that the limit is high enough to cause unnecessary  
trips during the intermediate DC circuit load peak at start.  
Long term current limit  
Rule of thumb: Set to the rated AC current of the drive.  
Peak current limit  
Rule of thumb: Set to a value 3…4 times the rated AC current of the drive.  
Make sure that the mechanical and electrical installation of the drive is completed. See Installation  
Check the settings of breakers/switches in the auxiliary circuits.  
Make sure that the voltage settings of the auxiliary voltage transformers (option +G344) are according  
to the actual power line voltage. See the delivery-specific circuit diagrams.  
Transformer [T21] is selected by option +G344; [T101] and [T111] are present if required by the options  
specified by the customer.  
Starting and checking the cooling system  
Action  
Fill up and bleed the internal cooling circuit. Start the cooling unit up. See Internal cooling cir-  
Check the cooling system for leaks.  
Make sure that cooling circuit joints at the shipping split joining cubicles are tight and that all drain  
valves have been closed.  
Make sure that the coolant can flow freely in all cubicles.  
Install all shrouds (if removed) and close the cabinet doors.  
Connecting voltage to input terminals and auxiliary  
Action  
Remove the temporary grounding system (if installed).  
Drive with voltage meters (option +G334): Close the circuit breaker for the voltage meters [F5].  
Close the circuit breakers supplying the auxiliary circuits [F20, F22.x].  
Drive with an external control voltage supply (option +G307): Close the circuit breaker of the external  
control voltage supply.  
       
Start-up 61  
Action  
Make sure that it is safe to connect voltage:  
• nobody is working on the unit or circuits that are wired from outside into the cabinets  
• covers of the motor terminal boxes are on  
• cabinet doors are closed  
• the disconnecting device [Q1] is open.  
Drive with the earthing/grounding switch [Q9] (option +F259): Open the earthing/grounding switch.  
Close the auxiliary voltage switch [Q21].  
Setting the supply unit parameters  
Action  
If the supply unit includes one supply module:  
• Check the correct voltage ranges by parameter 195.01 Supply voltage.  
• Reboot the control unit by parameter 196.08 Control board boot.  
If the supply unit includes more than one supply module: Make sure that the value of parameter 195.31  
Parallel connection rating id corresponds to the actual number of parallel-connected diode supply  
modules:  
• Select the correct voltage range with parameter 195.30 Parallel type filter.  
• Select the correct supply unit type with parameter 195.31 Parallel connection rating id.  
• Reboot the control unit by parameter 196.08 Control board boot.  
• Check the correct voltage range, parameter 195.01 Supply voltage.  
• Reboot the control unit by parameter 196.08 Control board boot.  
If you need more information on the use of the control panel, see ACX-AP-x assistant control panels  
user's manual (3AUA0000085685 [English]).  
Powering up the drive  
Action  
Close the disconnecting device of the supply unit.  
Drive with main breaker [Q1] (option +F255): Unlock the withdrawn breaker, and crank it in.  
WARNING!  
Never use the start button of the air circuit breaker to close it. Start button bypasses normal  
start-up procedure and may damage the module.  
Make sure that the control panel [A59] is in the remote mode (Loc/Rem key of the panel).  
Switch the Run enable and Start signals at digital input DI2 on (1) to start the operation of the supply  
unit.  
Turn the operating switch [S21] on the cabinet door to ENABLE/RUN (1) position.  
Run enable starts the supply unit power up sequence. After the program has stepped through it (ap-  
proximately 3 seconds), the drive DC link is charged, the main breaker is closed and the supply unit  
is in operation and ready to the supply inverters.  
Turn the operating switch [S21] to on (1) position to activate the Run enable signal and to close the  
main breaker [Q1].  
   
62 Start-up  
Safety function validation  
Action  
Validate the operation of safety functions (for example, emergency stop).  
WARNING!  
The safety functions are not safe before they are validated according to the instructions.  
See the function-specific manual for the validation tasks.  
Safety functions are optional. See the function-specific manual for the validation tasks.  
On-load checks  
Action  
Make sure that the cooling operates properly (no overtemperature related warnings or faults).  
Switching the supply unit off  
1. Stop the motors connected to inverter units. See the inverter unit hardware and firmware  
manuals.  
2. Turn the operating switch [S21] to the OFF (0) position to deactivate the Run enable  
signal and to switch off the main disconnecting device (main breaker [Q1]).  
ENABLE / RUN  
0-1  
Disconnecting and temporary grounding the drive  
       
Maintenance 63  
7
Maintenance  
Contents of this chapter  
This chapter instructs how to maintain the diode supply unit and how to interpret its fault  
indications. The information is valid for ACS880-307LC…+A018 diode supply units.  
WARNING!  
Obey the safety instructions given in ACS880 liquid-cooled multidrive  
cabinets and modules safety instructions (3AXD50000048633 [English]).  
If you ignore the safety instructions, injury or death, or damage to the  
equipment can occur.  
If you are not a qualified electrical professional, do not do installation or  
maintenance work.  
Maintenance intervals  
The table below shows the maintenance tasks which can be done by the end user. The  
complete maintenance schedule is available on the Internet (www.abb.com/drivesservices).  
For more information, consult your local ABB Service representative  
     
64 Maintenance  
Years from start-up  
Component  
1
2
3
4
5
6
7
8
9
10 11 12  
Coolant  
Coolant draining and refill  
Checking coolant quantity  
R
P
P
R
P
P
P
P
P
P
P
P
P
P
Checking coolant antifreeze con-  
centration  
P
P
P
P
P
P
P
External circuit of main heat ex-  
changer (temperature, flow, pres-  
sure)  
I
I
I
I
I
I
Cabinet fans and fan control board  
Cooling fans 230 V AC 50/60 Hz  
R
R
CIO-module for fan control  
(230 V AC)  
Cooling fans 115 V AC 50/60 Hz  
R
R
R
R
I/R  
CIO-module for fan control  
1)  
(115 V AC)  
Batteries  
Control panel battery  
Control unit battery  
Control unit  
R
R
R
R
P
BCU Control unit  
Connections and environment  
Quality of supply voltage  
Inspections  
P
P
P
P
P
P
P
P
P
P
P
P
Tightness of terminals  
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Ambient conditions (dustiness,  
moisture, corrosion, temperature)  
Cooling liquid pipe connections  
Spare parts  
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Spare part stock  
Other  
ABB-SACE Air circuit breaker  
maintenance  
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
ABB Contactors maintenance  
1)  
Replace CIO-module or reset fan counters, see CIO-01 I/O module for distributed I/O bus control user's manual  
(3AXD50000126880 [English])  
Symbols  
I
Inspection (visual inspection and maintenance action if needed)  
Performance of on/off-site work (commissioning, tests, measurements or other work)  
Replacement  
P
R
Maintenance and component replacement intervals are based on the assumption that the  
equipment is operated within the specified ratings and ambient conditions. ABB recommends  
annual drive inspections to ensure the highest reliability and optimum performance.  
Maintenance 65  
Note: Long term operation near the specified maximum ratings or ambient conditions may  
require shorter maintenance intervals for certain components. Consult your local ABB Service  
representative for additional maintenance recommendations.  
Maintenance timers and counters  
The control program has maintenance timers and counters that can be configured to generate  
a warning when a pre-defined limit is reached. Each timer/counter can be set to monitor  
any parameter. This feature is especially useful as a service reminder. For more information,  
see the firmware manual.  
Internal liquid-cooling system  
For instructions on coolant replacement and checking the liquid-cooling system, see chapter  
Power connections  
Retightening the power connections  
WARNING!  
Obey the safety instructions given in ACS880 liquid-cooled multidrive  
cabinets and modules safety instructions (3AXD50000048633 [English]).  
If you ignore the safety instructions, injury or death, or damage to the  
equipment can occur.  
If you are not a qualified electrical professional, do not do installation or  
maintenance work.  
1. Stop the drive and do the steps in section Electrical safety precautions (page 36) before  
you start the work.  
2. Examine the tightness of the cable connections. Use the tightening torques given in the  
technical data.  
Fans  
The lifespan of the cooling fans of the drive depends on the running time, ambient  
temperature and dust concentration. See the firmware manual for the actual signal which  
indicates the running time of the cooling fan. Reset the running time signal after fan  
replacement.  
Replacement fans are available from ABB. Do not use other than ABB specified spare parts.  
Replacing the fan in the 600 mm wide incoming cubicle  
WARNING!  
Read the safety instructions given in Safety instructions for ACS880  
liquid-cooled multidrive cabinets and modules (3AXD50000048633  
[English]). If you ignore them, injury or death, or damage to the equipment  
can occur.  
           
66 Maintenance  
WARNING!  
Wear protective gloves and long sleeves. Some parts have sharp edges.  
1. Repeat the steps described in section Electrical safety precautions (page 36) before  
you start the work.  
2. Remove the shrouding in front of the fan (if any).  
3. Disconnect the fan wiring. Remove the CIO module.  
4. Remove the two screws and slide the fan unit out.  
5. Remove the four screws to detach the fan from the fan unit.  
6. Remove the eight screws surrounding the fan unit.  
7. Install a new fan in reverse order.  
5
4
6
Maintenance 67  
Replacing the cooling fan of a D8T supply module  
WARNING!  
Use the required personal protective equipment. Wear protective gloves and long  
sleeves. Some parts have sharp edges.  
1. Repeat the steps described in section Electrical safety precautions (page 36).  
2. Remove any shrouding in front of the cooling fan.  
3. Remove the support bracket of the fan.  
4. Disconnect the fan wiring.  
5. Undo the two retaining screws.  
6. Pull the fan outwards to separate it from the heat exchanger housing.  
7. Install new fan in reverse order. Align the guide pins at the rear of the fan cowling with  
the slots in the bottom guide, then reinstall the retaining screws.  
7
5
4
3
 
68 Maintenance  
Fuses  
Checking and replacing the AC fuses  
WARNING!  
Obey the safety instructions given in ACS880 liquid-cooled multidrive  
cabinets and modules safety instructions (3AXD50000048633 [English]).  
If you ignore the safety instructions, injury or death, or damage to the  
equipment can occur.  
If you are not a qualified electrical professional, do not do installation or  
maintenance work.  
WARNING!  
Use the required personal protective equipment. Wear protective gloves and long  
sleeves. Some parts have sharp edges.  
1. Stop the motors connected to the drive.  
2. Repeat the steps described in section Electrical safety precautions (page 36).  
3. Open the cubicle door.  
4. Remove any shrouding in front of the fuses.  
5. 2×D8T: For replacing lower module AC fuses, remove the DC fuse assemblies:  
Remove the screws, nuts and washers (8 pcs) from the top and bottom of the DC  
fuses. Write down the correct order of the washers.  
Remove the screws and nuts from the L-shaped busbars.  
Remove the DC fuses and the L-shaped busbars.  
6. Remove the screw, nut and washer in the middle.  
7. Remove the screws (3 pcs, 1 per each phase) from the L-shaped busbars above the  
fuses.  
8. Remove the screws that attach the L-shape busbars below the fuses to the module AC  
busbars. There is one screw and busbar for each AC phase (3 pcs). Pull out the fuse  
assemblies with the L-shaped busbars (above and below) attached.  
9. Remove the screws, nuts and washers that attach the old fuses to the busbars, remove  
the old fuses and attach the new fuses in reverse order. Make sure to keep the washers  
in the original order. See section Tightening torques (page 98).  
10. Install the fuse assemblies and busbars in reverse order. See section Tightening  
   
Maintenance 69  
6
7
9
8
5
4
Checking and replacing the DC fuses  
WARNING!  
Obey the safety instructions given in ACS880 liquid-cooled multidrive  
cabinets and modules safety instructions (3AXD50000048633 [English]).  
If you ignore the safety instructions, injury or death, or damage to the  
equipment can occur.  
If you are not a qualified electrical professional, do not do installation or  
maintenance work.  
WARNING!  
Use the required personal protective equipment. Wear protective gloves and long  
sleeves. Some parts have sharp edges.  
1. Stop the motors connected to the drive.  
2. Repeat the steps described in section Electrical safety precautions (page 36).  
3. Open the cubicle door.  
4. Remove any shrouding in front of the DC fuses.  
5. Remove the screws, nuts and washers from the old fuses. Write down the correct order  
of the washers. Pull the fuses out.  
6. Install the new fuses in reverse order. Make sure that the washers are in the correct  
order. If necessary, loosen the bolts of the L-shape busbars somewhat. Retighten, after  
the fuses are attached. See section Tightening torques (page 98).  
 
70 Maintenance  
5
4
Supply module  
Replacing the D8T supply module  
WARNING!  
Obey the safety instructions of the drive. If you ignore them, injury or death, or  
damage to the equipment can occur.  
If you are not a qualified electrical professional, do not do installation or  
maintenance work.  
   
Maintenance 71  
WARNING!  
Use the required personal protective equipment. Wear protective gloves and long  
sleeves. Some parts have sharp edges.  
Keep the module in its package until you install it. After unpacking, protect the  
module from dust, debris and moisture.  
Lift/lower a heavy module with a lifting device. Use the designated lifting points.  
See the dimension drawings. There is a lifting device available from ABB (order  
code 3AXD50000047447).  
Make sure that the drive cabinet is attached to the floor to prevent it from toppling  
over. The cabinet has a high center of gravity. When you pull out heavy components  
or power modules, there is a risk of overturning.  
1. Stop the motors connected to the drive.  
2. Repeat the steps described in section Electrical safety precautions (page 36).  
3. Open the cubicle door.  
4. Close the inlet and outlet valve.  
5. Lead the drain hoses into a suitable container. If necessary, extend the hoses. Open  
the inlet and outlet drain valves. This will drain all modules in the cubicle.  
6. After the cubicle has drained, disconnect the piping from the module.  
7. 2×D8T module: If lower module needs to be replaced, remove the cooling fan (see the  
fan replacement instructions).  
8. Remove any shrouding above the module.  
9. Remove the DC fuses above the module. See section Checking and replacing the DC  
10. Disconnect the plug connector and fiber optic connectors in front of the module.  
11. Remove the L-shaped busbars (3 pcs above the module).  
12. Remove the module fastening screws (4 pcs).  
13. Install the module lifting device to the cabinet. See Converter module lifting device for  
drive cabinets hardware manual (3AXD50000210268 [English]).  
14. Attach one lifting hook to the front lifting eye of the module and pull the module out 10  
centimeters. Keep the lifting chain tight.  
15. Attach the second lifting hook to the rear lifting eye, and pull the module completely out  
of the cabinet. Keep the weight constantly on the lifting device.  
72 Maintenance  
16. Lower the module on a pallet. Keep the lifting chain attached to the module and attach  
the module safely to the pallet.  
17. Remove the lifting chains from the old module and move the pallet out of the way.  
18. Install the new module:  
a. Attach the lifting hooks to the module, lift the module and place it on the module  
guide plate. Keep the weight on the lifting device.  
b. Push the module into cabinet.  
c. Fasten the module fastening screws.  
d. Remove the lifting chains.  
e. Reinstall the DC busbars and fuses above the module.  
f. Connect the plug connector and fiber optic connectors.  
g. Reconnect the coolant pipes to the module.  
h. Fill up the cooling system.  
i. Reinstall all shrouds removed earlier.  
j. Remove the lifting device.  
9
8
Maintenance 73  
11  
12  
10  
6
12  
74 Maintenance  
14  
15  
Control panel  
For detailed information on the control panel, see ACx-AP-x assistant control panels user’s  
manual (3AUA0000085685 [English]).  
Cleaning the control panel  
Use a soft damp cloth to clean the control panel. Avoid harsh cleaners which could scratch  
the display window.  
Replacing the control panel battery  
For instructions on how to replace the control panel battery, see ACx-AP-x assistant control  
panels user’s manual (3AUA0000085685 [English]).  
     
Maintenance 75  
Control unit  
Replacing the memory unit  
After replacing a control unit, you can keep the existing parameter settings by transferring  
the memory unit from the defective control unit to the new control unit.  
WARNING!  
Do not remove or insert the memory unit when the control unit is powered.  
1. Stop the drive and do the steps in section Electrical safety precautions (page 36) before  
you start the work.  
2. Make sure that the control unit is not powered.  
3. Remove the fastening screw and pull the memory unit out.  
4. Install a memory unit in reverse order.  
Replacing the BCU control unit battery  
Replace the real-time clock battery if the BATT OK LED is not illuminated when the control  
unit is powered.  
1. Stop the drive and do the steps in section Electrical safety precautions (page 36) before  
you start the work.  
2. Undo the fastening screw and remove the battery.  
3. Replace the battery with a new BR2032 battery.  
     
76 Maintenance  
4. Dispose of the old battery according to local disposal rules or applicable laws.  
5. Set the real-time clock.  
LEDs and other status indicators  
This section instructs how to interpret the status indications of the diode supply unit.  
Warnings and faults reported by the control program are displayed on the control panel on  
the cabinet door. For further information, see the firmware manual.  
Control panel and panel platform/holder LEDs  
The ACS-AP-… control panel has a status LED. The control panel mounting platform or  
holder has two status LEDs. For their indications, see the following table.  
Location  
LED  
Indication  
Control panel  
Continuous green  
Flickering green  
The unit is functioning normally.  
Data is transferred between the PC and the unit through the USB  
connection of the control panel.  
Blinking green  
Continuous red  
Blinking red  
There is an active warning in the unit.  
There is an active fault in the unit.  
There is a fault that requires the stopping and restarting of the  
drive/converter/inverter.  
Blinking blue (ACS- The Bluetooth interface is enabled, in discoverable mode, and  
AP-W only)  
ready for pairing.  
Flickering blue  
(ACS-AP-W only)  
Data is being transferred through the Bluetooth interface of the  
control panel.  
Control panel  
mounting platform or  
holder (with the  
control panel  
Red  
There is an active fault in the unit.  
Green  
Power supply for the control unit is OK.  
removed)  
   
Maintenance 77  
Control unit LEDs  
LED  
Color  
Indication  
BATT OK  
Green  
Battery voltage of the real-time clock is OK (higher than 2.8 V).  
When the LED is not lit,  
• battery voltage is below 2.8 V,  
• the battery is missing, or  
• the control unit is not powered.  
PWR OK  
FAULT  
Green  
Red  
Internal voltage OK  
The control program indicates that the equipment is faulty. See  
the appropriate firmware manual.  
WRITE  
Yellow  
Writing to SD card in progress.  
 
78  
Internal cooling circuit 79  
8
Internal cooling circuit  
Contents of this chapter  
The cooling system of a liquid-cooled drive consists of two circuits: the internal cooling circuit  
and the external cooling circuit. The internal cooling circuit covers the heat-generating  
electrical components of the drive and transfers the heat to the cooling unit. In the cooling  
unit, the heat is transferred to the external cooling circuit which is usually part of a larger  
external cooling system. This chapter deals with the internal cooling circuit.  
Applicability  
The information in this chapter is applicable to cabinet-built ACS880 liquid-cooled drives.  
Except where otherwise indicated, the information is also applicable to drives built out of  
ACS880 liquid-cooled multidrive modules.  
Internal cooling system  
Each cubicle has an inlet and an outlet manifold, fitted with a stop valve and a drain valve.  
The stop valves can be closed to isolate all modules in the cubicle from the main cooling  
circuit.  
In cabinet line-ups built by ABB, valves are color-coded:  
Blue – Open during operation  
Red – Closed during operation  
The following diagram shows the coolant pipe connections in a drive system consisting of  
a supply unit and an inverter unit.  
       
80 Internal cooling circuit  
2
2
A/L  
A/L  
A/L  
1
HS  
HS  
HS  
A/L  
A/L  
d
HS  
a
c
a
c
b
d
b
3
1
Supply modules. The drawing shows the configuration of a diode supply unit, ie. there is a common  
air-to-liquid exchanger in the cubicle. With an IGBT supply unit, each module has a dedicated air-to-  
liquid exchanger as shown for item 2.  
2
3
Inverter modules  
To/From cooling unit  
Air-to-liquid heat exchanger  
Heat sink  
A/L  
HS  
a
Inlet valve  
b
Inlet-side drain valve  
Outlet valve  
c
d
Outlet-side drain valve  
The coolant used with ACS880 liquid-cooled drive systems is Antifrogen® L 25% or 50%  
Internal cooling circuit 81  
Connection to a cooling unit  
Connection to an ACS880-1007LC cooling unit  
Refer to ACS880-1007LC cooling unit user’s manual (3AXD50000129607 [English]).  
Connection to a custom cooling unit  
General requirements  
Equip the system with an expansion vessel to damp pressure rise due to volume changes  
when the temperature varies. Equip the system with a pump that provides a nominal flow  
and pressure. Keep the pressure within the limits specified in Technical data (page 84).  
Install a pressure regulator to make sure that the maximum permissible operating pressure  
is not exceeded.  
Install a bleed valve at the highest point of the cooling circuit, and a drain valve at the lowest  
point.  
The materials that can be used are listed in Cooling circuit materials (page 86).  
Coolant temperature control  
The temperature of the coolant in the internal cooling circuit must be kept within the limits  
specified in Technical data (page 84). Note that the minimum temperature is dependent on  
ambient temperature and relative humidity.  
         
82 Internal cooling circuit  
Filling up and bleeding the internal cooling circuit  
Both the drive and coolant must be at room temperature before filling up the cooling circuit.  
WARNING!  
Make sure that the maximum permissible operating pressure is not exceeded.  
When necessary regulate the pressure to appropriate level by draining excess  
coolant out of the system.  
WARNING!  
Bleeding of the cooling circuit is very important and has to be done with great care.  
Air bubbles in the cooling circuit may reduce or completely block coolant flow and  
lead to overheating. Let the air out of the cooling system while filling in coolant  
and, eg. after any power module replacements.  
Drive line-ups with an ACS880-1007LC cooling unit  
Follow the filling up and bleeding instructions in ACS880-1007LC cooling unit user's manual  
(3AXD50000129607 [English]).  
Drive line-ups with a custom cooling unit  
Note:  
In filling up the system, the drain valves in the line-up are used only to vent the air from  
the circuit so that it can be displaced by the coolant. The actual bleeding of the circuit  
must be done via an external bleed valve installed at the highest point of the cooling  
circuit. The most practical location for the valve is usually near or at the cooling unit.  
Observe the instructions given by the manufacturer of the cooling unit. Pay special  
attention to filling up and bleeding the pumps properly as they may be damaged if  
operated when dry.  
Draining coolant into the sewer system is not allowed.  
1. Open the bleed valve at the cooling unit.  
2. Open the inlet valve and the outlet-side drain valve of one cubicle. Keep the outlet valve  
and the inlet-side drain valve closed.  
3. Attach a hose to the outlet-side drain valve and lead it into a suitable container.  
4. Fill the circuit with coolant. For coolant specification, see Coolant specification (page 84).  
Note: To minimize foaming, do not exceed the filling flow rate of 5 l/min  
(1.3 US gallon/min).  
5. As the piping and modules in the cubicle fills up, coolant starts to flow from the hose.  
Let some coolant flow out, then close the drain valve.  
6. Close the inlet valve.  
7. Repeat steps 2 to 6 for all cubicles in the line-up.  
8. Open the inlet and outlet valves in all cubicles. Let any air remaining in the system out  
through the bleed valve at the cooling unit.  
9. Close the bleed valve at the cooling unit.  
10. Continue to fill in coolant until a base pressure of 100…150 kPa is achieved.  
11. Open the bleed valve of the pump to let out any air.  
12. Re-check the pressure and add coolant if necessary.  
     
Internal cooling circuit 83  
13. Start the coolant pump. Let any air remaining in the system out through the bleed valve  
at the cooling unit.  
14. After one to two minutes, stop the pump or block the coolant flow with a valve.  
15. Re-check the pressure and add coolant if necessary.  
16. Repeat steps 13 to 15 a few times until all air is let out of the cooling circuit. Listen for  
a humming sound and/or feel the piping for vibration to find out if there is still air left in  
the circuit.  
84 Internal cooling circuit  
Draining the internal cooling circuit  
The modules in each cubicle can be drained through the drain valves without draining the  
whole internal cooling circuit.  
WARNING!  
Hot, pressurized coolant can be present in the cooling circuit. Do not work on the  
cooling circuit before the pressure is released by stopping the pumps and draining  
coolant.  
1. Attach hoses to each drain valve in the cubicle to be drained. Lead the hoses into a  
suitable container. Make sure the ends of the hoses are not immersed in coolant at any  
point so that air can displace the coolant in the system.  
2. Open the drain valves. Wait until all coolant has drained.  
Note: Draining coolant into the sewer system is not allowed.  
3. If required, dry the piping with compressed oil-free air of less than 6 bar.  
4. If the drive is to be stored in temperatures below 0 °C (32 °F),  
dry the cooling circuit with air,  
fill the cooling circuit with coolant specified under Coolant specification (page 84).  
drain the cooling circuit again.  
Maintenance intervals  
As a general rule, the quality of the coolant should be checked at intervals of two years.  
This can be done by distributors of Antifrogen® L (see www.clariant.com) if a 250 milliliter  
sample is provided.  
Technical data  
Coolant specification  
Coolant type  
Antifrogen® L (by Clariant International Ltd, www.clariant.com) 25% or 50% mixture, available  
from Clariant distributors and ABB Service representatives.  
Note: Do not dilute the coolant. It is ready to use.  
Antifrogen® L 25% mixture is usable in storage temperatures down to -16 °C (3.2 °F).  
Antifrogen® L 50% mixture is usable in storage temperatures down to -40 °C (-40 °F).  
Note that operation below 0 °C (32 °F) is not allowed regardless of the freezing point of the  
coolant.  
WARNING!  
The warranty does not cover damage occurring from use of improper coolant.  
Temperature limits  
Ambient temperature: See the technical data of the drive/unit.  
Freeze protection: The freezing point of the coolant is determined by the concentration of  
heat transfer fluid in the mixture.  
           
Internal cooling circuit 85  
The higher the concentration of heat transfer fluid, the higher the viscosity of the coolant.  
This results in a higher pressure loss in the system. See Pressure limits (page 86).  
The nominal current ratings of drive system modules apply to an Antifrogen® L / water  
solution of 25/75% (volume). With the Antifrogen® L concentration between 25% and 50%,  
the drive output current must be derated by 1/3 percentage point per 1 p.p. increase in  
Antifrogen® L concentration. The drawing below shows the derating factor (k) in relation to  
Antifrogen® L concentration.  
k
1.00  
0.95  
0.90  
25%  
30%  
35%  
40%  
45%  
50%  
Antifrogen® L concentration  
Incoming coolant temperature:  
0…40 °C (32…104 °F): no drive output current derating required  
40…45 °C (104…113 °F): drive output current must be derated by 2 percentage points  
per 1 °C (1.8 °F) temperature increase, as shown by curve (a).  
45…50 °C (113…122 °F):  
If components with a maximum operating temperature of 55 °C (131 °F) are installed  
in the same space as the drive modules, drive output current must be derated by  
6 percentage points per 1 °C (1.8 °F) temperature increase, as shown by curve (c).  
If there are no components with a maximum operating temperature of 55 °C (131 °F)  
installed in the same space as the drive modules, drive output current must be  
derated by 2 percentage points per 1 °C (1.8 °F) temperature increase, as shown  
by curve (b).  
The drawing below shows the derating factor (k) in relation to coolant temperature.  
k
1.00  
(a)  
0.90  
(b)  
0.80  
(c)  
0.70  
0.60  
+40 °C  
+45 °C  
+50 °C  
T
+104 °F  
+113 °F  
+122 °F  
Condensation is not allowed. The minimum coolant temperature to avoid condensation (at  
an atmospheric pressure of 1 bar) is shown below as a function of relative humidity (RH)  
and ambient temperature (Tair).  
Tair  
Min. Tcoolant (°C)  
RH = 65%  
-0.9  
(°C)  
RH = 95%  
RH = 80%  
RH = 50%  
RH = 40%  
5
4.3  
1.9  
-4.5  
-7.4  
86 Internal cooling circuit  
Tair  
Min. Tcoolant (°C)  
(°C)  
RH = 95%  
RH = 80%  
6.7  
RH = 65%  
3.7  
RH = 50%  
-0.1  
RH = 40%  
-3.0  
10  
15  
20  
25  
30  
35  
40  
45  
50  
55  
9.2  
14.2  
19.2  
24.1  
29.1  
34.1  
39.0  
44.0  
49.0  
53.9  
11.5  
8.4  
4.6  
1.5  
16.5  
21.4  
26.2  
31.1  
35.9  
40.8  
45.6  
50.4  
13.2  
17.9  
22.7  
27.4  
32.2  
36.8  
41.6  
46.3  
9.4  
6.0  
13.8  
18.4  
23.0  
27.6  
32.1  
36.7  
42.2  
10.5  
15.0  
19.4  
23.8  
28.2  
32.8  
37.1  
= Not allowed as standard but the coolant temperature must be 0 °C (32 °F) or above.  
At an air temperature of 45 °C and relative humidity of 65% the coolant temperature may  
not be below +36.8 °C  
Example:  
Maximum temperature rise: Depends on heat losses and mass flow. Typically 10 °C (18  
°F) with nominal losses and flow.  
Pressure limits  
Base pressure: 250 kPa (recommended); 300 kPa (maximum). “Base pressure” denotes  
the pressure of the system compared with the atmospheric pressure when the cooling circuit  
is filled with coolant.  
Air counterpressure in expansion vessel (with ACS880-1007LC cooling unit): 80 kPa  
Design pressure (PS): 600 kPa  
Nominal pressure difference: 120 kPa with Antifrogen® L 25% coolant solution, 140 kPa  
with Antifrogen® L 50% coolant solution. This has to be taken into account when  
dimensioning the liquid cooling circuit.  
Maximum pressure difference: 160 kPa  
Coolant flow rate limits  
The maximum coolant flow rate for all drive equipment is 1.3 × nominal. See the technical  
data chapter for nominal values.  
Cooling circuit materials  
Materials used in the internal cooling circuit are listed below. These are also the only materials  
that can be used in the external cooling circuit.  
stainless steel AISI 316L (UNS 31603)  
heavy gauge aluminum  
plastic materials such as PA, PEX and PTFE  
Note: PVC hoses are not suitable for use with antifreeze.  
     
Internal cooling circuit 87  
rubber gasketing NBR (nitrile rubber).  
WARNING!  
If connecting external piping to the internal cooling circuit, use only materials  
that are specified above. Copper, brass or bronze must not be used under  
any circumstances. Even minor dissolution of copper can cause copper  
precipitation on aluminum and subsequent galvanic corrosion. The liquid  
cooling system must not contain any zinc (eg. galvanized pipes).  
If the plant incorporates normal iron pipes or cast iron accessories (eg. motor housings), a  
cooling unit with a heat exchanger (such as the ACS880-1007LC) must be used to separate  
the systems.  
88  
Technical data 89  
9
Technical data  
Contents of this chapter  
This chapter contains the technical data.  
The information is valid for ACS880-307LC…+A018 diode supply units.  
Ratings  
Supply unit  
type  
No overload use  
Light overload Heavy-duty use  
use  
ACS880-  
307LC-…  
I1  
I2  
Imax_1  
SN  
Imax_2  
PN  
ILd  
PLd  
IHd  
PHd  
A (AC) A (DC) A (DC)  
kVA  
A (AC)  
kW  
A (DC)  
kW  
A (DC)  
kW  
(DC)  
(DC)  
(DC)  
UN = 690 V  
6-pulse  
0490A-7+A018  
0780A-7+A018  
490  
780  
600  
955  
900  
1430  
1950  
2700  
3675  
5505  
7350  
9180  
11025  
585  
932  
735  
559  
890  
576  
917  
537  
854  
449  
714  
418  
666  
1170  
1590  
2205  
3000  
4500  
6000  
7500  
9000  
1060A-7+A018 1060  
1470A-7+A018 1470  
2000A-7+A018 2000  
3000A-7+A018 3000  
4000A-7+A018 4000  
5000A-7+A018 5000  
6000A-7+A018 6000  
12-pulse  
1300  
1800  
2450  
3670  
4900  
6120  
7350  
1267  
1757  
2390  
3585  
4780  
5979  
7171  
1211  
1677  
2283  
3420  
4566  
5703  
6849  
1248  
1728  
2352  
3523  
4704  
5875  
7056  
1163  
1610  
2192  
3283  
4383  
5475  
6575  
972  
906  
1346  
1833  
2745  
3665  
4578  
5498  
1255  
1708  
2558  
3415  
4266  
5123  
0920A-7  
920  
1130  
1695  
1100  
1380  
1053  
1085  
1011  
845  
788  
+A004+A018  
     
90 Technical data  
Supply unit  
type  
No overload use  
Light overload Heavy-duty use  
use  
ACS880-  
307LC-…  
I1  
I2  
Imax_1  
SN  
Imax_2  
PN  
ILd  
PLd  
IHd  
PHd  
A (AC) A (DC) A (DC)  
kVA  
A (AC)  
kW  
A (DC)  
kW  
A (DC)  
kW  
(DC)  
(DC)  
(DC)  
1470A-7  
+A004+A018  
1470  
2000  
2940  
4000  
6000  
1800  
2450  
3600  
4900  
7350  
2700  
3675  
5400  
7350  
11025  
1757  
2390  
3514  
4780  
7171  
2205  
3000  
4410  
6000  
9000  
1677  
2283  
3355  
4566  
6849  
1728  
2352  
3456  
4704  
7056  
1610  
2192  
3220  
4383  
6575  
1346  
1833  
2693  
3665  
5498  
1255  
1708  
2509  
3415  
5123  
2000A-7  
+A004+A018  
2940A-7  
+A004+A018  
4000A-7  
+A004+A018  
6000A-7  
+A004+A018  
Definitions  
Nominal ratings  
UN  
Nominal input voltage. For U1, see Electrical power network  
specification (page 101). For U2, see DC connection data.  
I1  
Continuous rms input (AC) current. No overload capability at the coolant  
temperature of 40 °C (104 °F) and air temperature of 45 °C (113 °F).  
I2  
Continuous rms output (DC) current. No overload capability at the coolant  
temperature of 40 °C (104 °F) and air temperature of 45 °C (113 °F).  
Imax_1  
Maximum output (DC) current. Available for 10 s at start, otherwise as long as  
allowed by module temperature.  
SN  
Nominal apparent (AC) power  
Maximum input (AC) current  
Nominal output (DC) power  
Imax_2  
PN  
Light-overload use (50% overload capability) ratings  
ILd  
Continuous current. 50% overload is allowed for one minute every 5 minutes.  
Output power in light-overload use  
PLd  
Heavy-duty use (50% overload capability) ratings  
IHd  
Continuous current. 50% overload is allowed for one minute every 5 minutes.  
Output power in heavy-duty use  
PHd  
Derating  
Surrounding air temperature derating  
In the temperature range +45…55 °C (+113…131 °F), the rated output current is derated  
by 0.5 percentage points for every added 1 °C (1.8 °F). The output current can be calculated  
by multiplying the current given in the rating table by the derating factor (k):  
   
Technical data 91  
k
1.00  
0.95  
0.90  
T
+45 °C  
+55 °C  
+113 °F  
+131 °F  
Coolant temperature derating  
Antifreeze content derating  
Altitude derating  
At altitudes 1000 … 2000 m (3281 … 6562 ft) above sea level, the output current derating  
is 1 percentage point for every added 100 m (328 ft). For example, the derating factor for  
1500 m (4921 ft) is 0.95. For altitudes above 2000 m (6562 ft), contact ABB.  
For a more accurate derating, use the DriveSize PC tool.  
Type equivalence table  
Supply unit type  
Basic module type  
Frame  
UN = 690 V  
6-pulse  
ACS880-307LC-0490A-7+A018  
ACS880-307LC-0780A-7+A018  
ACS880-307LC-1060A-7+A018  
ACS880-307LC-1470A-7+A018  
ACS880-307LC-2000A-7+A018  
ACS880-307LC-3000A-7+A018  
ACS880-307LC-4000A-7+A018  
ACS880-307LC-5000A-7+A018  
ACS880-307LC-6000A-7+A018  
12-pulse  
ACS880-304LC-0490A-7+A018  
ACS880-304LC-0780A-7+A018  
ACS880-304LC-1060A-7+A018  
ACS880-304LC-0780A-7+A018  
ACS880-304LC-1060A-7+A018  
ACS880-304LC-1060A-7+A018  
ACS880-304LC-1060A-7+A018  
ACS880-304LC-1060A-7+A018  
ACS880-304LC-1060A-7+A018  
D8T  
D8T  
D8T  
2×D8T  
2×D8T  
3×D8T  
4×D8T  
5×D8T  
6×D8T  
ACS880-307LC-0920A-7+A004+A018  
ACS880-307LC-1470A-7+A004+A018  
ACS880-307LC-2000A-7+A004+A018  
ACS880-307LC-2940A-7+A004+A018  
ACS880-307LC-4000A-7+A004+A018  
ACS880-307LC-6000A-7+A004+A018  
ACS880-304LC-0490A-7+A018  
ACS880-304LC-0780A-7+A018  
ACS880-304LC-1060A-7+A018  
ACS880-304LC-0780A-7+A018  
ACS880-304LC-1060A-7+A018  
ACS880-304LC-1060A-7+A018  
2×D8T  
2×D8T  
2×D8T  
4×D8T  
4×D8T  
6×D8T  
       
92 Technical data  
Fuses  
Main circuit AC fuses  
IEC  
IN  
Supply unit type  
ACS880-307LC-…  
Type  
Pcs.  
Size  
A
UN = 690 V  
6-pulse  
0490A-7+A018  
0780A-7+A018  
1060A-7+A018  
1470A-7+A018  
2000A-7+A018  
3000A-7+A018  
4000A-7+A018  
5000A-7+A018  
6000A-7+A018  
12-pulse  
170M6413  
170M6416  
170M6413  
170M6416  
170M6413  
170M6413  
170M6413  
170M6413  
170M6413  
3
3
900  
size 3  
1250  
size 3  
6
2 × 900  
1250  
2 × size 3  
size 3  
6
12  
18  
24  
30  
36  
2 × 900  
2 × 900  
2 × 900  
2 × 900  
2 × 900  
2 × size 3  
2 × size 3  
2 × size 3  
2 × size 3  
2 × size 3  
0920A-7+A004+A018  
1470A-7+A004+A018  
2000A-7+A004+A018  
2940A-7+A004+A018  
4000A-7+A004+A018  
6000A-7+A004+A018  
170M6413  
170M6416  
170M6413  
170M6416  
170M6413  
170M6413  
6
900  
size 3  
size 3  
6
1250  
12  
12  
24  
36  
2 × 900  
1250  
2 × size 3  
size 3  
2 × 900  
2 × 900  
2 × size 3  
2 × size 3  
UL/CSA  
IN  
Supply unit type  
ACS880-307LC-…  
Type  
Pcs.  
Size  
A
UN = 690 V  
6-pulse  
0490A-7+A018  
0780A-7+A018  
1060A-7+A018  
1470A-7+A018  
2000A-7+A018  
3000A-7+A018  
4000A-7+A018  
5000A-7+A018  
6000A-7+A018  
12-pulse  
170M6413  
170M6416  
170M6904  
170M6416  
170M6904  
170M6904  
170M6904  
170M6904  
170M6904  
3
3
900  
size 3  
size 3  
1250  
1800  
1250  
1800  
1800  
1800  
1800  
1800  
3
size 23  
size 3  
6
6
size 23  
size 23  
size 23  
size 23  
size 23  
9
12  
15  
18  
0920A-7+A004+A018  
1470A-7+A004+A018  
170M6413  
170M6416  
6
6
900  
size 3  
size 3  
1250  
   
Technical data 93  
UL/CSA  
IN  
Supply unit type  
ACS880-307LC-…  
Type  
Pcs.  
Size  
A
2000A-7+A004+A018  
2940A-7+A004+A018  
4000A-7+A004+A018  
6000A-7+A004+A018  
170M6904  
170M6416  
170M6904  
170M6904  
6
1800  
1250  
1800  
1800  
size 23  
size 3  
12  
12  
18  
size 23  
size 23  
Main circuit DC fuses  
IEC  
IN  
Supply unit type  
ACS880-307LC-…  
Type  
Pcs.  
Size  
A
UN = 690 V  
6-pulse  
0490A-7+A018  
0780A-7+A018  
1060A-7+A018  
1470A-7+A018  
2000A-7+A018  
3000A-7+A018  
4000A-7+A018  
5000A-7+A018  
6000A-7+A018  
12-pulse  
170M6549  
170M6546  
170M6549  
170M6546  
170M6549  
170M6549  
170M6549  
170M6549  
170M6549  
2
4
1100  
size 3  
2 × 800  
2 × 1100  
2 × 800  
2 × 1100  
2 × 1100  
2 × 1100  
2 × 1100  
2 × 1100  
2 × size 3  
2 × size 3  
2 × size 3  
2 × size 3  
2 × size 3  
2 × size 3  
2 × size 3  
2 × size 3  
4
8
8
12  
16  
20  
24  
0920A-7+A004+A018  
1470A-7+A004+A018  
2000A-7+A004+A018  
2940A-7+A004+A018  
4000A-7+A004+A018  
6000A-7+A004+A018  
170M6549  
170M6546  
170M6549  
170M6546  
170M6549  
170M6549  
4
8
1100  
size 3  
2 × 800  
2 × 1100  
2 × 800  
2 × 1100  
2 × 1100  
2 × size 3  
2 × size 3  
2 × size 3  
2 × size 3  
2 × size 3  
8
16  
16  
24  
UL/CSA  
IN  
Supply unit type  
ACS880-307LC-…  
Type  
Pcs.  
Size  
A
UN = 690 V  
6-pulse  
0490A-7+A018  
0780A-7+A018  
1060A-7+A018  
1470A-7+A018  
2000A-7+A018  
3000A-7+A018  
170M6549  
170M6792  
170M6827  
170M6792  
170M6827  
170M6827  
2
2
2
4
4
6
1100  
1600  
2100  
1600  
2100  
2100  
size 3  
size 23  
size 23  
size 23  
size 23  
size 23  
 
94 Technical data  
UL/CSA  
IN  
Supply unit type  
ACS880-307LC-…  
Type  
Pcs.  
Size  
A
4000A-7+A018  
170M6827  
170M6827  
170M6827  
8
2100  
2100  
2100  
size 23  
size 23  
size 23  
5000A-7+A018  
10  
12  
6000A-7+A018  
12-pulse  
0920A-7+A004+A018  
1470A-7+A004+A018  
2000A-7+A004+A018  
2940A-7+A004+A018  
4000A-7+A004+A018  
6000A-7+A004+A018  
170M6789  
170M6792  
170M6827  
170M6792  
170M6827  
170M6827  
4
4
1100  
1600  
2100  
1600  
2100  
2100  
size 3  
size 23  
size 23  
size 23  
size 23  
size 23  
4
8
8
12  
Dimensions, weights and free space requirements  
Note: The following dimensions and weights are applicable to diode supply module cubicle  
only. Incoming and auxiliary control cubicles not included.  
Height Width  
Depth Weight  
Supply unit type  
ACS880-307LC-…  
Basic module type  
ACS880-304LC-…  
Frame  
mm  
mm  
mm  
kg  
6-pulse  
0490A-7+A018  
0780A-7+A018  
1060A-7+A018  
1470A-7+A018  
2000A-7+A018  
3000A-7+A018  
4000A-7+A018  
5000A-7+A018  
6000A-7+A018  
12-pulse  
0490A-7+A018  
0780A-7+A018  
1060A-7+A018  
0780A-7+A018  
1060A-7+A018  
1060A-7+A018  
1060A-7+A018  
1060A-7+A018  
1060A-7+A018  
D8T  
D8T  
2002  
2002  
2002  
2002  
2002  
2002  
2002  
2002  
2002  
400  
400  
400  
400  
400  
800  
800  
1200  
1200  
644  
644  
644  
644  
644  
644  
644  
644  
644  
300  
300  
300  
450  
450  
750  
900  
1200  
1350  
D8T  
2xD8T  
2xD8T  
3xD8T  
4xD8T  
5xD8T  
6xD8T  
0920A-7+A004+A018  
1470A-7+A004+A018  
2000A-7+A004+A018  
2940A-7+A004+A018  
4000A-7+A004+A018  
6000A-7+A004+A018  
0490A-7+A018  
0780A-7+A018  
1060A-7+A018  
0780A-7+A018  
1060A-7+A018  
1060A-7+A018  
2xD8T  
2xD8T  
2xD8T  
4xD8T  
4xD8T  
6xD8T  
2002  
2002  
2002  
2002  
2002  
2002  
400  
400  
400  
800  
800  
1200  
644  
644  
644  
644  
644  
644  
450  
450  
450  
900  
900  
1350  
3AXD00000601909  
 
Technical data 95  
Cooling data and noise  
Coolant volume  
Coolant flow rate  
Noise level  
Pressure  
Supply unit type  
ACS880-307LC-…  
Modules Modules + Modules Modules +  
Average  
loss  
cabinet  
cabinet  
l
l
l/min  
l/min  
kPa  
dB (A)  
UN = 690 V  
6-pulse  
0490A-7+A018  
0780A-7+A018  
1060A-7+A018  
1470A-7+A018  
2000A-7+A018  
3000A-7+A018  
4000A-7+A018  
5000A-7+A018  
6000A-7+A018  
12-pulse  
0.6  
0.6  
0.6  
1.2  
1.2  
1.8  
2.4  
3.0  
3.6  
3.5  
3.5  
14  
14  
14  
28  
28  
42  
56  
70  
84  
20  
20  
20  
34  
34  
54  
68  
88  
102  
120  
120  
120  
120  
120  
120  
120  
120  
120  
65  
65  
65  
65  
65  
67  
67  
68  
68  
3.5  
4.2  
4.2  
7.7  
8.4  
11.9  
12.6  
0920A-7+A004+A018  
1470A-7+A004+A018  
2000A-7+A004+A018  
2940A-7+A004+A018  
4000A-7+A004+A018  
6000A-7+A004+A018  
1.2  
1.2  
1.2  
2.4  
2.4  
3.6  
4.2  
4.2  
28  
28  
28  
56  
56  
84  
34  
34  
120  
120  
120  
120  
120  
120  
67  
67  
67  
68  
68  
68  
4.2  
34  
8.4  
68  
8.4  
68  
12.6  
102  
Terminal and cable entry data for the input power cable  
These drawings (from front, side and above) show the terminal and cable entry dimensions  
for incoming cubicles. The dimensions are given in millimeters. Tightening torque for the  
cable lug connection depends on the bolt size and type. See section Tightening  
   
96 Technical data  
400 mm wide input cubicle  
 
Technical data 97  
600 mm wide incoming cubicle or input cubicle  
 
98 Technical data  
Tightening torques  
Unless a tightening torque is specified in the text, the following torques can be used.  
Electrical connections  
Size  
M3  
Torque  
Note  
0.5 N·m (4.4 lbf·in)  
1 N·m (9 lbf·in)  
Strength class 4.6...8.8  
Strength class 4.6...8.8  
Strength class 8.8  
Strength class 8.8  
Strength class 8.8  
Strength class 8.8  
Strength class 8.8  
Strength class 8.8  
M4  
M5  
4 N·m (35 lbf·in)  
9 N·m (6.6 lbf·ft)  
22 N·m (16 lbf·ft)  
42 N·m (31 lbf·ft)  
70 N·m (52 lbf·ft)  
120 N·m (90 lbf·ft)  
M6  
M8  
M10  
M12  
M16  
Mechanical connections  
Size  
M5  
Max. torque  
6 N·m (53 lbf·in)  
10 N·m (7.4 lbf·ft)  
24 N·m (17.7 lbf·ft)  
Note  
Strength class 8.8  
Strength class 8.8  
Strength class 8.8  
M6  
M8  
Insulation supports  
Size  
M6  
Max. torque  
Note  
5 N·m (44 lbf·in)  
9 N·m (6.6 lbf·ft)  
18 N·m (13.3 lbf·ft)  
31 N·m (23 lbf·ft)  
Strength class 8.8  
Strength class 8.8  
Strength class 8.8  
Strength class 8.8  
M8  
M10  
M12  
Cable lugs  
Size  
M8  
Max. torque  
15 N·m (11 lbf·ft)  
32 N·m (23.5 lbf·ft)  
50 N·m (37 lbf·ft)  
Note  
Strength class 8.8  
Strength class 8.8  
Strength class 8.8  
M10  
M12  
         
Technical data 99  
Typical power cable sizes  
The tables below give current carrying capacity (ILmax) for aluminum and copper PVC/XLPE  
insulated cables. A correction factor K = 0.70 is used. Time const is the temperature time  
constant of the cable.  
The cable sizing is based on max. 9 cables laid on the cable trays side by side, three ladder  
type trays one on top of the other, ambient temperature 30 °C (EN 60204-1 and  
IEC 60364-5-52).  
Aluminum cable  
PVC insulation  
XLPE insulation  
Conductor temperature 70 °C Conductor temperature 90 °C  
Size  
[mm]  
ILmax [A]  
Time const. [s] ILmax [A]  
Time const. [s]  
3 × 35 + 10 Cu  
3 × 50 + 15 Cu  
3 × 70 + 21 Cu  
3 × 95 + 29 Cu  
3 × 120 + 41 Cu  
3 × 150 + 41 Cu  
3 × 185 + 57 Cu  
3 × 240 + 72 Cu  
3 × 300 + 88 Cu  
26  
29  
32  
38  
41  
44  
49  
54  
58  
67  
736  
84  
669  
82  
959  
102  
131  
159  
184  
213  
243  
286  
330  
874  
105  
128  
148  
171  
196  
231  
267  
1182  
1492  
1776  
2042  
2422  
2967  
3478  
1079  
1376  
1637  
1881  
2237  
2740  
3229  
2 × (3 × 70 + 21 Cu)  
2 × (3 × 95 + 29 Cu)  
2 × (3 × 120 + 41 Cu)  
2 × (3 × 150 + 41 Cu)  
2 × (3 × 185 + 57 Cu)  
2 × (3 × 240 + 72 Cu)  
2 × (3 × 300 + 88 Cu)  
2 × 32  
2 × 38  
2 × 41  
2 × 44  
2 × 49  
2 × 54  
2 × 58  
210  
256  
297  
343  
392  
462  
533  
1182  
1492  
1776  
2042  
2422  
2967  
3478  
262  
318  
368  
425  
486  
572  
659  
1079  
1376  
1637  
1881  
2237  
2740  
3229  
3 × (3 × 150 + 41 Cu)  
3 × (3 × 185 + 57 Cu)  
3 × (3 × 240 + 72 Cu)  
3 × (3 × 300 + 88 Cu)  
3 × 44  
3 × 49  
3 × 54  
3 × 58  
514  
588  
693  
800  
2042  
2422  
2967  
3478  
638  
728  
859  
989  
1881  
2237  
2740  
3229  
4 × (3 × 185 + 57 Cu)  
4 × (3 × 240 + 72 Cu)  
4 × (3 × 300 + 88 Cu)  
4 × 49  
4 × 54  
4 × 58  
784  
2422  
2967  
3478  
971  
2237  
2740  
3229  
924  
1145  
1319  
1067  
5 × (3 × 185 + 57 Cu)  
5 × (3 × 240 + 72 Cu)  
5 × (3 × 300 + 88 Cu)  
5 × 49  
5 × 54  
5 × 58  
980  
2422  
2967  
3478  
1214  
1431  
1648  
2237  
2740  
3229  
1155  
1333  
6 × (3 × 240 + 72 Cu)  
6 × (3 × 300 + 88 Cu)  
6 × 54  
6 × 58  
1386  
1600  
2967  
3478  
1718  
1978  
2740  
3229  
7 × (3 × 240 + 72 Cu)  
7 × (3 × 300 + 88 Cu)  
7 × 54  
7 × 58  
1617  
1867  
2967  
3478  
2004  
2308  
2740  
3229  
8 × (3 × 240 + 72 Cu)  
8 × (3 × 300 + 88 Cu)  
8 × 54  
8 × 58  
1848  
2133  
2967  
3478  
2290  
2637  
2740  
3229  
9 × (3 × 240 + 72 Cu)  
9 × (3 × 300 + 88 Cu)  
9 × 54  
9 × 58  
2079  
2400  
2967  
3478  
2577  
2967  
2740  
3229  
10 × (3 × 240 + 72 Cu)  
10 × (3 × 300 + 88 Cu)  
10 × 54  
10 × 58  
2310  
2667  
2967  
3478  
2867  
3297  
2740  
3229  
 
100 Technical data  
Copper cable  
Size  
PVC insulation  
XLPE insulation  
Conductor temperature 70 °C Conductor temperature 90 °C  
[mm]  
ILmax [A]  
Time const. [s] ILmax [A]  
Time const. [s]  
3 × 1.5 + 1.5  
3 × 2.5 + 2.5  
(3 × 4 + 4)  
13  
14  
16  
18  
21  
23  
24  
26  
29  
32  
38  
41  
44  
50  
55  
58  
13  
85  
16  
67  
18  
121  
23  
88  
24  
175  
30  
133  
3 × 6 + 6  
30  
251  
38  
186  
3 × 10 + 10  
3 × 16 + 16  
3 × 25 + 16  
3 × 35 + 16  
3 × 50 + 25  
3 × 70 + 35  
3 × 95 + 50  
3 × 120 + 70  
3 × 150 + 70  
3 × 185 + 95  
3 × 240 + 120  
3 × 300 + 150  
42  
359  
53  
268  
56  
514  
70  
391  
71  
791  
89  
598  
88  
1000  
1308  
1613  
2046  
2441  
2820  
3329  
4073  
4779  
110  
134  
171  
209  
241  
279  
319  
376  
435  
760  
107  
137  
167  
193  
223  
255  
301  
348  
990  
1230  
1551  
1859  
2139  
2525  
3099  
3636  
2 × (3 × 70 + 35)  
2 × (3 × 95 + 50)  
2 × (3 × 120 + 70)  
2 × (3 × 150 + 70)  
2 × (3 × 185 + 95)  
2 × (3 × 240 + 120)  
2 × (3 × 300 + 150)  
2 × 32  
2 × 38  
2 × 41  
2 × 44  
2 × 50  
2 × 55  
2 × 58  
274  
334  
386  
446  
510  
602  
696  
1613  
2046  
2441  
2820  
3329  
4073  
4779  
342  
418  
482  
558  
638  
752  
869  
1230  
1551  
1859  
2139  
2525  
3099  
3636  
3 × (3 × 120 + 70)  
3 × (3 × 150 + 70)  
3 × (3 × 185 + 95)  
3 × (3 × 240 + 120)  
3 × (3 × 300 + 150)  
3 × 41  
3 × 44  
3 × 50  
3 × 55  
3 × 58  
579  
669  
765  
903  
1044  
2441  
2820  
3329  
4073  
4779  
723  
1859  
2139  
2525  
3099  
3636  
837  
957  
1128  
1304  
4 × (3 × 150 + 70)  
4 × (3 × 185 + 95)  
4 × (3 × 240 + 120)  
4 × (3 × 300 + 150)  
4 × 44  
4 × 50  
4 × 55  
4 × 58  
892  
2820  
3329  
4073  
4779  
1116  
1276  
1504  
1304  
2139  
2525  
3099  
3636  
1020  
1204  
1391  
5 × (3 × 185 + 95)  
5 × (3 × 240 + 120)  
5 × (3 × 300 + 150)  
5 × 50  
5 × 55  
5 × 58  
1275  
1505  
1739  
3329  
4073  
4779  
1595  
1880  
2173  
2525  
3099  
3636  
6 × (3 × 185 + 95)  
6 × (3 × 240 + 120)  
6 × (3 × 300 + 150)  
6 × 50  
6 × 55  
6 × 58  
1530  
1806  
2087  
3329  
4073  
4779  
1914  
2256  
2608  
2525  
3099  
3636  
7 × (3 × 240 + 120)  
7 × (3 × 300 + 150)  
7 × 55  
7 × 58  
2107  
2435  
4073  
4779  
2632  
3043  
3099  
3636  
8 × (3 × 240 + 120)  
8 × (3 × 300 + 150)  
8 × 55  
8 × 58  
2408  
2783  
4073  
4779  
3008  
3477  
3099  
3636  
Technical data 101  
Electrical power network specification  
Voltage (U1)  
690 V units: 525…690 V AC 3-phase ± 10% (525…600 V AC ± 10% in UL/CSA  
installations, or corner-grounded TN systems). This is indicated in the type desig-  
nation label as typical input voltage levels (3~ 525/600/690 V AC).  
Network type  
Frequency  
TN (grounded) and IT (ungrounded) systems  
50/60 Hz, variation ± 5% of nominal frequency  
Imbalance  
Max. ± 3% of nominal phase-to-phase input voltage  
Supply units with main circuit breaker (option +F255) and without grounding/earthing  
Short-circuit withstand  
strength (IEC/EN 61439-1) switch (without option +F259):  
Rated peak withstand current (Ipk): 143 kA  
Rated short-time withstand current (Icw): 65 kA/1 s  
All other configurations:  
Rated peak withstand current (Ipk): 105 kA  
Rated short-time withstand current (Icw): 50 kA/1 s  
Short-circuit current protec- The drive is suitable for use on a circuit capable of delivering not more than  
tion (UL 508A, CSA C22.2 100,000 rms symmetrical amperes at 600 V maximum when the input cable is  
No. 14-13)  
protected with class T fuses.  
Transformer specification Connection: Dy 11 d0 or Dyn 11 d0  
for 12-pulse supply  
Phase shift between secondaries: 30° electrical  
(IEC 60076-1:2011)  
Voltage difference between secondaries: < 0.5%  
Short-circuit impedance of secondaries: > 5%  
Short-circuit impedance difference between secondaries: ≤ 10% of the percentage  
impedance  
To avoid a potentially destructive DC voltage level in an earth fault situation,  
grounding of the secondaries is not allowed. Static shielding is recommended.  
Control unit (board) connection data  
Auxiliary circuit current consumption  
Auxiliary circuit current consumption varies depending on the actual drive configuration and  
options. Contact ABB for the delivery-specific value.  
Efficiency  
Efficiency  
98.2…98.8% at nominal power level depending on drive type  
Protection classes  
Degrees of protection  
(IEC/EN 60529)  
IP42 (standard), IP54 (option +B055)  
Enclosure types (UL50) UL Type 1 (standard), UL Type 12 (option +B055). For indoor use only.  
Overvoltage category  
(IEC/EN 60664-1)  
III, except for auxiliary power connections (fan, control, heating, lighting, cooling  
unit pump etc) which are category II.  
Protective class  
I
(IEC/EN 61800-5-1)  
         
102 Technical data  
Ambient conditions  
Environmental limits for the drive are given below. The drive is to be used in a heated,  
indoor, controlled environment.  
Operation  
Storage  
Transportation  
installed for stationary in the protective package in the protective package  
use  
Installation site altitude  
0…2000 m (0…6562 ft)  
above sea level. For alti-  
tudes over 2000 m, contact  
ABB.  
-
-
Output derated above 1000  
m (3281 ft).  
Air temperature  
0 … +45 °C  
(+32 … +113 °F), no con-  
densation allowed. Output  
derated in the range  
+45 … +55 °C  
-40 to +70 °C (-  
40 to +158 °F)  
-40 to +70 °C (-  
40 to +158 °F)  
(+113 … +131 °F).  
Relative humidity  
Contamination  
Max. 95%  
Max. 95%  
Max. 95%  
No condensation allowed. Maximum allowed relative humidity is 60% in the presence  
of corrosive gases.  
IEC/EN 60721-3-3:2002:  
Classification of environ-  
mental conditions - Part 3-  
3: Classification of groups  
of environmental paramet-  
ers and their severities -  
Stationary use of weather  
protected locations  
IEC 60721-3-1:1997  
IEC 60721-3-2:1997  
Chemical gases: Class  
1C2  
Chemical gases: Class  
2C2  
Solid particles: Class 1S3 Solid particles: Class 2S2  
(packing must support this,  
otherwise 1S2)  
Chemical gases: Class  
3C2  
Solid particles: Class 3S2.  
No conductive dust al-  
lowed.  
Pollution degree  
2
Vibration  
IEC/EN 60721-3-3:2002 IEC/EN 60721-3-1:1997 IEC/EN 60721-3-2:1997  
10…57 Hz: max. 0.075 mm 10…57 Hz: max. 0.075 mm 2…9 Hz: max. 3.5 mm  
IEC/EN 61800-5-1  
amplitude  
amplitude  
amplitude  
9…200 Hz: 10 m/s2  
(32.8 ft/s2)  
IEC 60068-2-6:2007,  
EN 60068-2-6:2008 Envir-  
onmental testing Part 2:  
Tests –Test Fc: Vibration  
(sinusoidal)  
57…150 Hz: 1 g  
57…150 Hz: 1 g  
Units with marine construc-  
tion (option +C121): Max.  
1 mm (0.04 in)  
(5 … 13.2 Hz), max. 0.7 g  
(13.2 … 100 Hz) sinusoidal  
Shock  
Not allowed  
With packing max.  
With packing max.  
100 m/s2 (328 ft/s2) 11 ms 100 m/s2 (328 ft/s2) 11 ms  
IEC 60068-2-27:2008, EN  
60068-2-27:2009  
Environmental testing -  
Part 2-27: Tests - Test Ea  
and guidance: Shock  
 
Technical data 103  
Materials  
See ACS880 cabinet-installed drives Recycling instructions and environmental information  
(3AXD50000153909 [English]).  
Color  
RAL 7035 and RAL 9017.  
Package  
Vertical package  
Cabinets are attached to the pallet with screws and braced at the top to the package walls  
against swaying inside the package. Package elements are attached to each other with  
screws.  
Standard package  
Timber, polyethylene sheet (thickness 0.15 mm), stretch film (thickness 0.023 mm),  
PP tape, PET strap, sheet metal (steel).  
For land and air transport when planned storage time is less than 2 months, or,  
when storage can be arranged in clean and dry conditions, less than 6 months.  
Can be used when product will not be exposed to corrosive atmosphere during  
transport or storage.  
Seaworthy package  
(option +P912)  
Timber, plywood, VCI sheet film (PE, thickness 0.10 mm), VCI stretch film (PE,  
thickness 0.04 mm), VCI emitter bags, PP tape, PET strap, sheet metal (steel).  
For sea transport with or without containerization.  
For long storage periods in environments where roofed and humidity-controlled  
storage cannot be arranged.  
Container package  
(option +P929)  
Timber, VCI sheet film (PE, thickness 0.10 mm), VCI stretch film (PE, thickness  
0.04 mm), VCI emitter bags, PP tape, PET strap, sheet metal (steel).  
For sea transport in containers.  
Recommended for land and air transport when storage time prior to installation  
exceeds 6 months or storage is arranged in partially weather-protected conditions.  
Disposal  
The main parts of the drive can be recycled to preserve natural resources and energy.  
Product parts and materials should be dismantled and separated.  
Generally all metals, such as steel, aluminum, copper and its alloys, and precious metals  
can be recycled as material. Plastics, rubber, cardboard and other packaging material can  
be used in energy recovery. Printed circuit boards and large electrolytic capacitors need  
selective treatment according to IEC 62635 guidelines. To aid recycling, plastic parts are  
marked with an appropriate identification code.  
Contact your local ABB distributor for further information on environmental aspects and  
recycling instructions for professional recyclers. End of life treatment must follow international  
and local regulations. See ACS880 cabinet-installed drives recycling instructions and  
environmental information (3AXD50000153909 [English]).  
Applicable standards  
See ACS880 liquid-cooled multidrive cabinets and modules Electrical planning  
(3AXD50000048634 [English]).  
           
104 Technical data  
Markings  
See ACS880 liquid-cooled multidrive cabinets and modules Electrical planning  
(3AXD50000048634 [English]).  
Disclaimers  
Generic disclaimer  
The manufacturer shall have no obligation with respect to any product which (i) has been  
improperly repaired or altered; (ii) has been subjected to misuse, negligence or accident;  
(iii) has been used in a manner contrary to the manufacturer’s instructions; or (iv) has failed  
as a result of ordinary wear and tear.  
Cybersecurity disclaimer  
This product is designed to be connected to and to communicate information and data via  
a network interface. It is Customer's sole responsibility to provide and continuously ensure  
a secure connection between the product and Customer network or any other network (as  
the case may be). Customer shall establish and maintain any appropriate measures (such  
as but not limited to the installation of firewalls, application of authentication measures,  
encryption of data, installation of anti-virus programs, etc) to protect the product, the network,  
its system and the interface against any kind of security breaches, unauthorized access,  
interference, intrusion, leakage and/or theft of data or information. ABB and its affiliates are  
not liable for damages and/or losses related to such security breaches, any unauthorized  
access, interference, intrusion, leakage and/or theft of data or information.  
       
Further information  
Product and service inquiries  
Address any inquiries about the product to your local ABB representative, quoting the type  
designation and serial number of the unit in question. A listing of ABB sales, support and service  
contacts can be found by navigating to www.abb.com/searchchannels.  
Product training  
For information on ABB product training, navigate to new.abb.com/service/training.  
Providing feedback on ABB manuals  
Your comments on our manuals are welcome. Navigate to  
Document library on the Internet  
You can find manuals and other product documents in PDF format on the Internet at  
a1 (frozen)  
PDF-A4  
Created 2020-06-30, 09:37:26  
 
www.abb.com/drives  
3AXD50000579662A  
© Copyright 2020 ABB. All rights reserved.  
Specifications subject to change without notice.  

Mr Coffee PRX29 User Manual
Motorola MOTO W409G User Manual
Hitachi Deskstar HTS723225A7A364 User Manual
Hitachi Deskstar HDS721032CLA362 User Manual
Dymo Clock DATEMARK User Manual
COBY electronic CD SH 287 User Manual
Bodum MOCCA 1176 USA User Manual
Belkin OMNIVIEW P72114 User Manual
American DJ PRO DJ1 User Manual
ABB SM1000 User Manual