User’s Manual
ACS550-PD Stock 3R Irrigation Packaged Drive
Supplement to ACS550-U1 User’s Manual
ACS550-PD 3R Irrigation Packaged Drive
3
Table of Contents
Table of Contents
Safety
Use of Warnings and Notes..............................................4
Installation
Application .......................................................................5
Input Disconnect Features and Functions ........................6
Installation Flow Chart......................................................7
Lifting ...............................................................................8
Installing the Drive ...........................................................10
Installing the Wiring..........................................................12
Maintenance
Maintenance Intervals......................................................15
Drive Module Fan Replacement.......................................15
Technical Data
Typical Control Schematic................................................16
Ratings.............................................................................17
Input Power Connections .................................................18
Power Connection Terminals ...........................................18
Dimensions and Weights .................................................21
Applicable Standards .......................................................22
4
ACS550-PD 3R Irrigation Packaged Drive
Safety
WARNING! The ACS550 adjustable speed AC drive with Input Disconnect
should ONLY be installed by a qualified electrician.
WARNING! Even when the motor is stopped, dangerous voltage is present at
the Power Circuit terminals U1, V1, W1 and U2, V2, W2 and, depending on the
frame size, UDC+ and UDC-, or BRK+ and BRK-.
WARNING! Dangerous voltage is present when input power is connected. After
disconnecting the supply, wait at least 5 minutes (to let the intermediate circuit
capacitors discharge) before removing the cover.
WARNING! Even when power is removed from the input terminals of the
ACS550, there may be dangerous voltage (from external sources) on the
terminals of the relay outputs.
WARNING! When the control terminals of two or more drive units are
connected in parallel, the auxiliary voltage for these control connections must
be taken from a single source which can either be one of the units or an
external supply.
WARNING! The ACS550 will start up automatically after an input voltage
interruption if the external run command is on.
WARNING! When the ACS550 with Input Disconnect is connected to the line
power, the Motor Terminals T1, T2, and T3 are live even if the motor is not
running. Do not make any connections when the ACS550 with Input Disconnect
is connected to the line. Disconnect and lock out power to the drive before
servicing the drive. Failure to disconnect power may cause serious injury or
death.
Note! For more technical information, contact the factory or your local ABB sales
representative.
Use of Warnings and Notes
There are two types of safety instructions throughout this manual:
• Notes draw attention to a particular condition or fact, or give information on a
subject.
• Warnings caution you about conditions which can result in serious injury or death
and/or damage to the equipment. They also tell you how to avoid the danger. The
warning symbols are used as follows:
Dangerous voltage warning warns of high voltage which can cause physical injury
and/or damage to the equipment.
General warning warns about conditions, other than those caused by electricity,
which can result in physical injury and/or damage to the equipment.
Safety
ACS550-PD 3R Irrigation Packaged Drive
5
Installation
Study these installation instructions carefully before proceeding. Failure to observe the
warnings and instructions may cause a malfunction or personal hazard.
WARNING! Before you begin read “Safety” on page 1.
WARNING! When the ACS550 with Input Disconnect is connected to the line
power, the Motor Terminals T1, T2, and T3 are live even if the motor is not
running. Do not make any connections when the ACS550 with Input Disconnect
is connected to the line. Disconnect and lock out power to the drive before
servicing the drive. Failure to disconnect power may cause serious injury or
death.
Application
This manual contains supplemental information that is unique to ACS550 input
disconnect configurations (PD). Refer to the base manual, AC550-U1 User’s Manual, for
all other information.
Input Disconnect Features and Functions
The ACS550 with Input Disconnect is an ACS550 AC adjustable frequency drive
packaged with an input disconnect switch and with a door mounted, external operating
handle. The operating handle can be padlocked in the OFF position (padlock not
supplied). Enclosure are UL Type 3R (NEMA 3R).
The following is a typical power diagram.
Drive with Input Disconnect
Disconnect Switch
or Circuit Breaker
ACS550
Drive
3 Phase
Input Power
Motor
3
3
6
ACS550-PD 3R Irrigation Packaged Drive
The following figures show the front view of the ACS550 Drive with Input Disconnect
standard configurations, and identify the major components.
UL Type / NEMA 3R Enclosures
Operating
Handle for
Disconnect
Switch
Note! UL Type 3R enclosures are designed to be mounted on a wall. See section
“Prepare the UL Type 3R ACS550 for UNISTRUT® mounting” for more details.
ACS550-PD 3R Irrigation Packaged Drive
7
Installation Flow Chart
The installation of Input Disconnect configurations for ACS550 drives follows the outline
below. The steps must be carried out in the order shown. At the right of each step are
references to the detailed information needed for the correct installation of the unit.
Note! References in the middle column below are to the ACS550-U1 User’s Manual.
References in the third column below are to this manual.
Refer to the
ACS550-U1 User’s
Manual “Installation”
section
Additional Reference in
this Manual
Task
PREPARE for
installation
“Preparing for Installation”
•
•
“Drive Identification” on page #.
“Suitable Mounting Location” on
page #.
“Prepare the Mounting Location”
•
“Dimensions and Weights
(Supplement to ACS550-U1
User’s Manual)” on page #.
PREPARE the
Mounting Location
MOUNT the drive
“Mount the Drive”
--
INSTALL wiring
“Wiring Overview” and
“Install the Wiring”
“Installing the Wiring (Supplement
to ACS550-U1 User’s Manual)”
starting on page #.
CHECK installation
APPLY power
START-UP
“Check Installation”
“Apply Power”
“Start-Up”
--
--
--
8
ACS550-PD 3R Irrigation Packaged Drive
Preparing for Installation (Supplement to ACS550-U1 User’s Manual)
Lifting the Drive
ACS550-PD 3R Irrigation Packaged Drive
9
Preparing for Installation (Supplement to ACS550-U1 User’s Manual)
Drive Identification
To identify the type of device you are installing, refer to the type code number on the
device identification label.
• Wall mounting base drives – label attached on the side surface of the heat sink.
• Packaged drive – label attached to outside surface on the left ide of the enclosure.
• Enclosure with hinged cover/door – label on inside surface of the cover/door.
Type Code Number
Use the following to interpret the type code found on the identification label.
ACS550-PD-015A-4 +C192
AC Drive = 550 Product Series
Construction
PD = Drive with disconnect switch
Output current rating (See ratings chart for details)
Voltage rating
2 = 230 VAC
4 = 480 VAC
Enclosure protection class
+C192 = 3R Stock Irrigation Drive
Ratings and Frame Size
Charts in the “Ratings” sections of the ACS550-U1 User’s Manual and this manual list
technical specifications, and identify the drive’s frame size.
Note! Some instructions in this document vary, depending on the drive’s frame size.
To read the Ratings table, you need the “Output current rating” entry from the type
code (see above).
10
ACS550-PD 3R Irrigation Packaged Drive
Suitable Mounting Location
For selecting a suitable mounting location for configurations, refer to:
• Preparing for installation in the ACS550-U1 User’s Manual, and
• The Technical Data section of this manual for information on dimensions and
weights.
Installing the Drive (Supplement to ACS550-U1 User’s Manual)
WARNING!
Metal shavings or debris in the enclosure can damage electrical equipment and
create a hazardous condition. Where parts, such as conduit plates require
cutting or drilling, first remove the part. If that is not practical, cover nearby
electrical components to protect them from all shavings or debris.
Do not connect or disconnect input or output power wiring, or control wires,
when power is applied.
Never connect line voltage to drive output Terminals T1, T2, and T3.
Do not make any voltage tolerance tests (Hi Pot or Megger) on any part of the
unit. Disconnect motor wires before taking any measurements in the motor or
motor wires.
Make sure that power factor correction capacitors are not connected between
the drive and the motor.
Prepare the Mounting Location
The ACS550 should only be mounted where all of the requirements defined in “Preparing
for Installation” are met.
Mount the Drive
1. Use a hoist to move the cabinet into position.
Note! If the cabinet location does not provide access to the cabinet sides, be
sure to re-mount side panels before positioning cabinet.
2. Install and tighten mounting bolts.
ACS550-PD 3R Irrigation Packaged Drive
11
Prepare the UL Type 3R ACS550 for UNISTRUT® mounting
The ACS550 UL Type 3R cabinet frame sizes are designed to be mounted on a solid
vertical surface or using UNISTRUT.
12
ACS550-PD 3R Irrigation Packaged Drive
Installing the Wiring (Supplement to ACS550-U1 User’s Manual)
Wiring Requirements
Refer to the “Wiring Requirements” Section in the ACS550-U1 User’s Manual. The
requirements apply to all ACS550 drives. In particular:
• Use separate, metal conduit runs for the following different classes of wiring:
– Input power wiring.
– Motor wiring.
– Control/communications wiring.
• Properly and individually ground the drive, the motor and cable shields.
Wiring Overview
Power Connection – Standard Drive with Input Disconnect (Wall Mounted)
The following figures show the Standard Drive with Input Disconnect (wall mounted)
typical layout. (Refer to the ACS550-U1 User’s Manual and 3R Irrigation Control
Schematic for control connections to the drive.)
Install the Line Input Wiring
Line Input Connections – Standard Drive with Input Disconnect Configurations
Connect input power to the terminals of the disconnect switch. Connect the equipment
grounding conductor to the ground lug. The figure below shows typical connection points
for Standard ACS550 Drive with Input Disconnect configurations.
WARNING! Check the motor and motor wiring insulation before connecting the
ACS550 to line power. Follow the procedure in the ACS550-U1 User’s Manual.
Before proceeding with the insulation resistance measurements, check that
the ACS550 is disconnected from incoming line power. Failure to disconnect
line power could result in death or serious injury.
Note! For the remainder of the installation and start-up (motor and control wiring)
refer to the ACS550-U1 User’s Manual.
ACS550-PD 3R Irrigation Packaged Drive
13
Typical Power Connections for Single and Three Phase
14
ACS550-PD 3R Irrigation Packaged Drive
ACS550-PD 15-200 hp
*Typical ACS550 3R irrigation panel layout
ACS550-PD 3R Irrigation Packaged Drive
15
Maintenance
Maintenance Intervals
If installed in an appropriate environment, the drive requires very little maintenance. This
table lists the routine maintenance intervals recommended by ABB.
Maintenance
Configuration
Interval
Instruction
Check/replace UL
Type 3R/NEMA 3R enclosures
enclosure air filters
UL Type / NEMA 3R Check every 3
months. Replace
as needed.
Check and clean
heatsink.
All
Depends on the
dustiness of the
environment
(every 6…12
months)
See “Maintenance” in ACS550-U1
User’s Manual.
Replace drive
module fan.
All
Every six years
See “Maintenance” in ACS550-U1
User’s Manual.
Replace enclosure NEMA 3R
Every three years See “Enclosure Fan Replacement
– UL Type / NEMA 3R. See
fan(s).
enclosures
“Maintenance” in ACS550-U1
User’s Manual.
Change capacitor.
Frame sizes R5 and Every ten years
R6
See “Maintenance” in ACS550-U1
User’s Manual.
Replace battery in
the Assistant
All
Every ten years
See “Maintenance” in ACS550-U1
User’s Manual.
control panel.
Drive Module Fan Replacement
The drive module fan cools the heatsink. Fan failure can be predicted by the increasing
noise from fan bearings and the gradual rise in the heatsink temperature in spite of
heatsink cleaning. If the drive is operated in a critical part of a process, fan replacement is
recommended once these symptoms start appearing. Replacement fans are available
from ABB. Do not use other than ABB specified spare parts.
To monitor the running time of the cooling fan, see “Group 29: Maintenance Trig” in the
ACS550-U1 Users’s Manual.
Maintenance
16
ACS550-PD Packaged Drive with Disconnect
Typical Control Schematic
ACS550-PD Packaged Drive with Disconnect
17
Technical Data
Ratings (Supplement to ACS550-U1 User’s Manual)
Note! The ratings listed below are exceptions to the ratings listed in the
ACS550-U1 User’s Manual.
Technical Data
18
ACS550-PD Packaged Drive with Disconnect
Input Power Connections and Power Connection Terminals
(Supplement to ACS550-U1 User’s Manual)
1-Phase 240V
Drive Input Fuse
Incoming Power Connections
Tightening
Output Connections to Motor
Ground
Lugs
Rating
HP
ABB Product Code
UL Type
3R/
Tightening
Minimum Maximum
Torque
Amps Bussman Minimum Maximum
Torque
(lb/ft)
(600V)
Type
Wire Size Wire Size
Wire Size Wire Size
(lb/ft)
NEMA 3R
15 ACS550-PD-088A-2+C192 100 JJS-110
20 ACS550-PD-114A-2+C192 150 JJS-150
25 ACS550-PD-143A-2+C192 200 JJS-200
30 ACS550-PD-178A-2+C192 250 JJS-250
40 ACS550-PD-221A-2+C192 300 JJS-300
50 ACS550-PD-248A-2+C192 350 JJS-350
#8
#4
#4
#4
#4
#2
1/0
55
10
10
1/0
4
#2
50 in-lbs
300MCM
300MCM
300MCM
300MCM
600MCM
200
200
200
200
375
1/0
4
3/0
3/0
3/0
3/0
350MCM
350MCM
350MCM
350MCM
30
30
30
30
#2/0
275 in-lbs
350MCM
100 in-lbs
NOTE: For information regarding motor terminals. refer to “Drives Power Connection Terminals” in the ACS550-U1 User Manual .
ACS550-PD Packaged Drive with Disconnect
19
Input Power Connections and Power Connection Terminals
(Supplement to ACS550-U1 User’s Manual)
3-Phase 240V
Ground
Drive Input Fuse
Incoming Power Connections
Tightening
Output Connections to Motor
Lugs
Rating
HP
ABB Product Code
UL Type
3R/
Tightening
Minimum Maximum
Torque
Amps Bussman Minimum Maximum
Torque
(lb/ft)
(600V)
Type
Wire Size Wire Size
Wire Size Wire Size
(lb/ft)
NEMA 3R
25 ACS550-PD-075A-2+C192 100 JJS-100
30 ACS550-PD-088A-2+C192 110 JJS-110
40 ACS550-PD-114A-2+C192 150 JJS-150
50 ACS550-PD-143A-2+C192 200 JJS-200
60 ACS550-PD-178A-2+C192 250 JJS-250
75 ACS550-PD-221A-2+C192 300 JJS-300
100 ACS550-PD-248A-2+C192 350 JJS-350
#8
#8
#4
#4
#4
#4
#2
1/0
55
10
10
1/0
4
4
#2
50 in-lbs
1/0
55
1/0
300MCM
300MCM
300MCM
300MCM
600MCM
200
200
200
200
375
10
1/0
4
3/0
3/0
3/0
3/0
350MCM
350MCM
350MCM
350MCM
30
30
30
30
#2/0
275 in-lbs
350MCM
100 in-lbs
NOTE: For information regarding motor terminals. refer to “Drives Power Connection Terminals” in the ACS550-U1 User Manual .
Technical Data
20
ACS550-PD Packaged Drive with Disconnect
Input Power Connections and Power Connection Terminals
(Supplement to ACS550-U1 User’s Manual)
3-Phase 480V
Ground
Drive Input Fuse
Incoming Power Connections
Tightening
Output Connections to Motor
Lugs
Rating
HP
ABB Product Code
UL Type
3R/
Tightening
Torque
(lb/ft)
Amps Bussman Minimum Maximum
Minimum Maximum
Wire Size Wire Size
Torque
(lb/ft)
(600V)
Type
Wire Size Wire Size
NEMA 3R
40 ACS550-PD-059A-4+C192
50 ACS550-PD-072A-4+C192
80
JJS-80
#8
#8
#8
#4
#4
#4
#2
1/0
55
55
10
10
1/0
1/0
4
4
90
JJS-90
1/0
#2
50 in-lbs
60 ACS550-PD-078A-4+C192 100 JJS-100
75 ACS550-PD-097A-4+C192 125 JJS-125
100 ACS550-PD-125A-4+C192 175 JJS-175
125 ACS550-PD-157A-4+C192 200 JJS-200
150 ACS550-PD-180A-4+C192 250 JJS-250
1/0
55
10
1/0
4
300MCM
300MCM
300MCM
600MCM
200
200
200
375
10
1/0
4
3/0
3/0
3/0
350MCM
350MCM
350MCM
30
30
30
#2/0
375 in-lbs
350MCM
100 in-lbs
200 ACS550-PD-246A-4+C192 350 JJS-350
#2
600MCM
375
3/0
350MCM
30
NOTE: For information regarding motor terminals. refer to “Drives Power Connection Terminals” in the ACS550-U1 User Manual .
Technical Data
ACS550-PD Packaged Drive with Disconnect
21
Dimensions and Weights (Supplement to ACS550-U1 User’s Manual)
Dimensions: ACS550-PD UL Type / NEMA 3R
1-Phase 240V
Weight*
(lbs)
Height
(in)
Width
(in)
Depth
(in)
HP
15
20
25
30
40
50
310
320
330
340
345
350
49.00
32.36
22.88
3-Phase 240V
3-Phase 480V
Weight*
(lbs)
Height
(in)
Width
(in)
Depth
(in)
Weight*
(lbs)
Height
(in)
Width
(in)
Depth
(in)
HP
HP
25
30
40
50
305
310
320
330
340
345
350
300
305
310
320
330
340
345
350
40
60
50
75
49.00
32.36
22.88
49.00
32.36
22.88
60
100
125
150
200
75
100
* Shipping crate adds approximately 170 lbs.
Technical Data
22
ACS550-PD Packaged Drive with Disconnect
Applicable Standards
Drive compliance with the following standards is identified by the standards “marks” on
the type code label.
Mark
Applicable Standards
UL 508C and
C22.2 No. 14
UL Standard for Safety, Power Conversion Equipment, second
edition and CSA Standard for Industrial Control Equipment
UL 508A
UL Standard for Safety, Industrial Control Panels
CSA Standard for Industrial Control Equipment
C22.2 No. 14
Compliance is valid with the following provisions:
• The motor and control cables are chosen as specified in this manual.
• The installation rules of this manual are followed.
Technical Data
ACS550-PD 3R Irrigation Packaged Drive
23
ABB Inc.
Low Voltage Drives
16250 West Glendale Drive
New Berlin, WI 53151
USA
Telephone +1 262 785-3200
+1 800 HELP-365
Telefax