ABB ACS550 PD User Manual

User’s Manual  
ACS550-PD Stock 3R Irrigation Packaged Drive  
Supplement to ACS550-U1 User’s Manual  
ACS550-PD 3R Irrigation Packaged Drive  
3
Table of Contents  
Table of Contents  
Safety  
Use of Warnings and Notes..............................................4  
Installation  
Application .......................................................................5  
Input Disconnect Features and Functions ........................6  
Installation Flow Chart......................................................7  
Lifting ...............................................................................8  
Installing the Drive ...........................................................10  
Installing the Wiring..........................................................12  
Maintenance  
Maintenance Intervals......................................................15  
Drive Module Fan Replacement.......................................15  
Technical Data  
Typical Control Schematic................................................16  
Ratings.............................................................................17  
Input Power Connections .................................................18  
Power Connection Terminals ...........................................18  
Dimensions and Weights .................................................21  
Applicable Standards .......................................................22  
4
ACS550-PD 3R Irrigation Packaged Drive  
Safety  
WARNING! The ACS550 adjustable speed AC drive with Input Disconnect  
should ONLY be installed by a qualified electrician.  
WARNING! Even when the motor is stopped, dangerous voltage is present at  
the Power Circuit terminals U1, V1, W1 and U2, V2, W2 and, depending on the  
frame size, UDC+ and UDC-, or BRK+ and BRK-.  
WARNING! Dangerous voltage is present when input power is connected. After  
disconnecting the supply, wait at least 5 minutes (to let the intermediate circuit  
capacitors discharge) before removing the cover.  
WARNING! Even when power is removed from the input terminals of the  
ACS550, there may be dangerous voltage (from external sources) on the  
terminals of the relay outputs.  
WARNING! When the control terminals of two or more drive units are  
connected in parallel, the auxiliary voltage for these control connections must  
be taken from a single source which can either be one of the units or an  
external supply.  
WARNING! The ACS550 will start up automatically after an input voltage  
interruption if the external run command is on.  
WARNING! When the ACS550 with Input Disconnect is connected to the line  
power, the Motor Terminals T1, T2, and T3 are live even if the motor is not  
running. Do not make any connections when the ACS550 with Input Disconnect  
is connected to the line. Disconnect and lock out power to the drive before  
servicing the drive. Failure to disconnect power may cause serious injury or  
death.  
Note! For more technical information, contact the factory or your local ABB sales  
representative.  
Use of Warnings and Notes  
There are two types of safety instructions throughout this manual:  
• Notes draw attention to a particular condition or fact, or give information on a  
subject.  
• Warnings caution you about conditions which can result in serious injury or death  
and/or damage to the equipment. They also tell you how to avoid the danger. The  
warning symbols are used as follows:  
Dangerous voltage warning warns of high voltage which can cause physical injury  
and/or damage to the equipment.  
General warning warns about conditions, other than those caused by electricity,  
which can result in physical injury and/or damage to the equipment.  
Safety  
ACS550-PD 3R Irrigation Packaged Drive  
5
Installation  
Study these installation instructions carefully before proceeding. Failure to observe the  
warnings and instructions may cause a malfunction or personal hazard.  
WARNING! Before you begin read “Safety” on page 1.  
WARNING! When the ACS550 with Input Disconnect is connected to the line  
power, the Motor Terminals T1, T2, and T3 are live even if the motor is not  
running. Do not make any connections when the ACS550 with Input Disconnect  
is connected to the line. Disconnect and lock out power to the drive before  
servicing the drive. Failure to disconnect power may cause serious injury or  
death.  
Application  
This manual contains supplemental information that is unique to ACS550 input  
disconnect configurations (PD). Refer to the base manual, AC550-U1 User’s Manual, for  
all other information.  
Input Disconnect Features and Functions  
The ACS550 with Input Disconnect is an ACS550 AC adjustable frequency drive  
packaged with an input disconnect switch and with a door mounted, external operating  
handle. The operating handle can be padlocked in the OFF position (padlock not  
supplied). Enclosure are UL Type 3R (NEMA 3R).  
The following is a typical power diagram.  
Drive with Input Disconnect  
Disconnect Switch  
or Circuit Breaker  
ACS550  
Drive  
3 Phase  
Input Power  
Motor  
3
3
6
ACS550-PD 3R Irrigation Packaged Drive  
The following figures show the front view of the ACS550 Drive with Input Disconnect  
standard configurations, and identify the major components.  
UL Type / NEMA 3R Enclosures  
Operating  
Handle for  
Disconnect  
Switch  
Note! UL Type 3R enclosures are designed to be mounted on a wall. See section  
“Prepare the UL Type 3R ACS550 for UNISTRUT® mounting” for more details.  
ACS550-PD 3R Irrigation Packaged Drive  
7
Installation Flow Chart  
The installation of Input Disconnect configurations for ACS550 drives follows the outline  
below. The steps must be carried out in the order shown. At the right of each step are  
references to the detailed information needed for the correct installation of the unit.  
Note! References in the middle column below are to the ACS550-U1 User’s Manual.  
References in the third column below are to this manual.  
Refer to the  
ACS550-U1 User’s  
Manual “Installation”  
section  
Additional Reference in  
this Manual  
Task  
PREPARE for  
installation  
“Preparing for Installation”  
“Drive Identification” on page #.  
“Suitable Mounting Location” on  
page #.  
“Prepare the Mounting Location”  
“Dimensions and Weights  
(Supplement to ACS550-U1  
User’s Manual)” on page #.  
PREPARE the  
Mounting Location  
MOUNT the drive  
“Mount the Drive”  
--  
INSTALL wiring  
“Wiring Overview” and  
“Install the Wiring”  
“Installing the Wiring (Supplement  
to ACS550-U1 User’s Manual)”  
starting on page #.  
CHECK installation  
APPLY power  
START-UP  
“Check Installation”  
“Apply Power”  
“Start-Up”  
--  
--  
--  
8
ACS550-PD 3R Irrigation Packaged Drive  
Preparing for Installation (Supplement to ACS550-U1 User’s Manual)  
Lifting the Drive  
ACS550-PD 3R Irrigation Packaged Drive  
9
Preparing for Installation (Supplement to ACS550-U1 User’s Manual)  
Drive Identification  
To identify the type of device you are installing, refer to the type code number on the  
device identification label.  
• Wall mounting base drives – label attached on the side surface of the heat sink.  
• Packaged drive – label attached to outside surface on the left ide of the enclosure.  
• Enclosure with hinged cover/door – label on inside surface of the cover/door.  
Type Code Number  
Use the following to interpret the type code found on the identification label.  
ACS550-PD-015A-4 +C192  
AC Drive = 550 Product Series  
Construction  
PD = Drive with disconnect switch  
Output current rating (See ratings chart for details)  
Voltage rating  
2 = 230 VAC  
4 = 480 VAC  
Enclosure protection class  
+C192 = 3R Stock Irrigation Drive  
Ratings and Frame Size  
Charts in the “Ratings” sections of the ACS550-U1 User’s Manual and this manual list  
technical specifications, and identify the drive’s frame size.  
Note! Some instructions in this document vary, depending on the drive’s frame size.  
To read the Ratings table, you need the “Output current rating” entry from the type  
code (see above).  
10  
ACS550-PD 3R Irrigation Packaged Drive  
Suitable Mounting Location  
For selecting a suitable mounting location for configurations, refer to:  
• Preparing for installation in the ACS550-U1 User’s Manual, and  
• The Technical Data section of this manual for information on dimensions and  
weights.  
Installing the Drive (Supplement to ACS550-U1 User’s Manual)  
WARNING!  
Metal shavings or debris in the enclosure can damage electrical equipment and  
create a hazardous condition. Where parts, such as conduit plates require  
cutting or drilling, first remove the part. If that is not practical, cover nearby  
electrical components to protect them from all shavings or debris.  
Do not connect or disconnect input or output power wiring, or control wires,  
when power is applied.  
Never connect line voltage to drive output Terminals T1, T2, and T3.  
Do not make any voltage tolerance tests (Hi Pot or Megger) on any part of the  
unit. Disconnect motor wires before taking any measurements in the motor or  
motor wires.  
Make sure that power factor correction capacitors are not connected between  
the drive and the motor.  
Prepare the Mounting Location  
The ACS550 should only be mounted where all of the requirements defined in “Preparing  
for Installation” are met.  
Mount the Drive  
1. Use a hoist to move the cabinet into position.  
Note! If the cabinet location does not provide access to the cabinet sides, be  
sure to re-mount side panels before positioning cabinet.  
2. Install and tighten mounting bolts.  
ACS550-PD 3R Irrigation Packaged Drive  
11  
Prepare the UL Type 3R ACS550 for UNISTRUT® mounting  
The ACS550 UL Type 3R cabinet frame sizes are designed to be mounted on a solid  
vertical surface or using UNISTRUT.  
12  
ACS550-PD 3R Irrigation Packaged Drive  
Installing the Wiring (Supplement to ACS550-U1 User’s Manual)  
Wiring Requirements  
Refer to the “Wiring Requirements” Section in the ACS550-U1 User’s Manual. The  
requirements apply to all ACS550 drives. In particular:  
• Use separate, metal conduit runs for the following different classes of wiring:  
– Input power wiring.  
– Motor wiring.  
– Control/communications wiring.  
• Properly and individually ground the drive, the motor and cable shields.  
Wiring Overview  
Power Connection – Standard Drive with Input Disconnect (Wall Mounted)  
The following figures show the Standard Drive with Input Disconnect (wall mounted)  
typical layout. (Refer to the ACS550-U1 User’s Manual and 3R Irrigation Control  
Schematic for control connections to the drive.)  
Install the Line Input Wiring  
Line Input Connections – Standard Drive with Input Disconnect Configurations  
Connect input power to the terminals of the disconnect switch. Connect the equipment  
grounding conductor to the ground lug. The figure below shows typical connection points  
for Standard ACS550 Drive with Input Disconnect configurations.  
WARNING! Check the motor and motor wiring insulation before connecting the  
ACS550 to line power. Follow the procedure in the ACS550-U1 User’s Manual.  
Before proceeding with the insulation resistance measurements, check that  
the ACS550 is disconnected from incoming line power. Failure to disconnect  
line power could result in death or serious injury.  
Note! For the remainder of the installation and start-up (motor and control wiring)  
refer to the ACS550-U1 User’s Manual.  
ACS550-PD 3R Irrigation Packaged Drive  
13  
Typical Power Connections for Single and Three Phase  
14  
ACS550-PD 3R Irrigation Packaged Drive  
ACS550-PD 15-200 hp  
*Typical ACS550 3R irrigation panel layout  
ACS550-PD 3R Irrigation Packaged Drive  
15  
Maintenance  
Maintenance Intervals  
If installed in an appropriate environment, the drive requires very little maintenance. This  
table lists the routine maintenance intervals recommended by ABB.  
Maintenance  
Configuration  
Interval  
Instruction  
Check/replace UL  
Type 3R/NEMA 3R enclosures  
enclosure air filters  
UL Type / NEMA 3R Check every 3  
months. Replace  
as needed.  
Check and clean  
heatsink.  
All  
Depends on the  
dustiness of the  
environment  
(every 6…12  
months)  
See “Maintenance” in ACS550-U1  
User’s Manual.  
Replace drive  
module fan.  
All  
Every six years  
See “Maintenance” in ACS550-U1  
User’s Manual.  
Replace enclosure NEMA 3R  
Every three years See “Enclosure Fan Replacement  
– UL Type / NEMA 3R. See  
fan(s).  
enclosures  
“Maintenance” in ACS550-U1  
User’s Manual.  
Change capacitor.  
Frame sizes R5 and Every ten years  
R6  
See “Maintenance” in ACS550-U1  
User’s Manual.  
Replace battery in  
the Assistant  
All  
Every ten years  
See “Maintenance” in ACS550-U1  
User’s Manual.  
control panel.  
Drive Module Fan Replacement  
The drive module fan cools the heatsink. Fan failure can be predicted by the increasing  
noise from fan bearings and the gradual rise in the heatsink temperature in spite of  
heatsink cleaning. If the drive is operated in a critical part of a process, fan replacement is  
recommended once these symptoms start appearing. Replacement fans are available  
from ABB. Do not use other than ABB specified spare parts.  
To monitor the running time of the cooling fan, see “Group 29: Maintenance Trig” in the  
ACS550-U1 Users’s Manual.  
Maintenance  
16  
ACS550-PD Packaged Drive with Disconnect  
Typical Control Schematic  
ACS550-PD Packaged Drive with Disconnect  
17  
Technical Data  
Ratings (Supplement to ACS550-U1 User’s Manual)  
Note! The ratings listed below are exceptions to the ratings listed in the  
ACS550-U1 User’s Manual.  
Technical Data  
18  
ACS550-PD Packaged Drive with Disconnect  
Input Power Connections and Power Connection Terminals  
(Supplement to ACS550-U1 User’s Manual)  
1-Phase 240V  
Drive Input Fuse  
Incoming Power Connections  
Tightening  
Output Connections to Motor  
Ground  
Lugs  
Rating  
HP  
ABB Product Code  
UL Type  
3R/  
Tightening  
Minimum Maximum  
Torque  
Amps Bussman Minimum Maximum  
Torque  
(lb/ft)  
(600V)  
Type  
Wire Size Wire Size  
Wire Size Wire Size  
(lb/ft)  
NEMA 3R  
15 ACS550-PD-088A-2+C192 100 JJS-110  
20 ACS550-PD-114A-2+C192 150 JJS-150  
25 ACS550-PD-143A-2+C192 200 JJS-200  
30 ACS550-PD-178A-2+C192 250 JJS-250  
40 ACS550-PD-221A-2+C192 300 JJS-300  
50 ACS550-PD-248A-2+C192 350 JJS-350  
#8  
#4  
#4  
#4  
#4  
#2  
1/0  
55  
10  
10  
1/0  
4
#2  
50 in-lbs  
300MCM  
300MCM  
300MCM  
300MCM  
600MCM  
200  
200  
200  
200  
375  
1/0  
4
3/0  
3/0  
3/0  
3/0  
350MCM  
350MCM  
350MCM  
350MCM  
30  
30  
30  
30  
#2/0  
275 in-lbs  
350MCM  
100 in-lbs  
NOTE: For information regarding motor terminals. refer to “Drives Power Connection Terminals” in the ACS550-U1 User Manual .  
ACS550-PD Packaged Drive with Disconnect  
19  
Input Power Connections and Power Connection Terminals  
(Supplement to ACS550-U1 User’s Manual)  
3-Phase 240V  
Ground  
Drive Input Fuse  
Incoming Power Connections  
Tightening  
Output Connections to Motor  
Lugs  
Rating  
HP  
ABB Product Code  
UL Type  
3R/  
Tightening  
Minimum Maximum  
Torque  
Amps Bussman Minimum Maximum  
Torque  
(lb/ft)  
(600V)  
Type  
Wire Size Wire Size  
Wire Size Wire Size  
(lb/ft)  
NEMA 3R  
25 ACS550-PD-075A-2+C192 100 JJS-100  
30 ACS550-PD-088A-2+C192 110 JJS-110  
40 ACS550-PD-114A-2+C192 150 JJS-150  
50 ACS550-PD-143A-2+C192 200 JJS-200  
60 ACS550-PD-178A-2+C192 250 JJS-250  
75 ACS550-PD-221A-2+C192 300 JJS-300  
100 ACS550-PD-248A-2+C192 350 JJS-350  
#8  
#8  
#4  
#4  
#4  
#4  
#2  
1/0  
55  
10  
10  
1/0  
4
4
#2  
50 in-lbs  
1/0  
55  
1/0  
300MCM  
300MCM  
300MCM  
300MCM  
600MCM  
200  
200  
200  
200  
375  
10  
1/0  
4
3/0  
3/0  
3/0  
3/0  
350MCM  
350MCM  
350MCM  
350MCM  
30  
30  
30  
30  
#2/0  
275 in-lbs  
350MCM  
100 in-lbs  
NOTE: For information regarding motor terminals. refer to “Drives Power Connection Terminals” in the ACS550-U1 User Manual .  
Technical Data  
20  
ACS550-PD Packaged Drive with Disconnect  
Input Power Connections and Power Connection Terminals  
(Supplement to ACS550-U1 User’s Manual)  
3-Phase 480V  
Ground  
Drive Input Fuse  
Incoming Power Connections  
Tightening  
Output Connections to Motor  
Lugs  
Rating  
HP  
ABB Product Code  
UL Type  
3R/  
Tightening  
Torque  
(lb/ft)  
Amps Bussman Minimum Maximum  
Minimum Maximum  
Wire Size Wire Size  
Torque  
(lb/ft)  
(600V)  
Type  
Wire Size Wire Size  
NEMA 3R  
40 ACS550-PD-059A-4+C192  
50 ACS550-PD-072A-4+C192  
80  
JJS-80  
#8  
#8  
#8  
#4  
#4  
#4  
#2  
1/0  
55  
55  
10  
10  
1/0  
1/0  
4
4
90  
JJS-90  
1/0  
#2  
50 in-lbs  
60 ACS550-PD-078A-4+C192 100 JJS-100  
75 ACS550-PD-097A-4+C192 125 JJS-125  
100 ACS550-PD-125A-4+C192 175 JJS-175  
125 ACS550-PD-157A-4+C192 200 JJS-200  
150 ACS550-PD-180A-4+C192 250 JJS-250  
1/0  
55  
10  
1/0  
4
300MCM  
300MCM  
300MCM  
600MCM  
200  
200  
200  
375  
10  
1/0  
4
3/0  
3/0  
3/0  
350MCM  
350MCM  
350MCM  
30  
30  
30  
#2/0  
375 in-lbs  
350MCM  
100 in-lbs  
200 ACS550-PD-246A-4+C192 350 JJS-350  
#2  
600MCM  
375  
3/0  
350MCM  
30  
NOTE: For information regarding motor terminals. refer to “Drives Power Connection Terminals” in the ACS550-U1 User Manual .  
Technical Data  
ACS550-PD Packaged Drive with Disconnect  
21  
Dimensions and Weights (Supplement to ACS550-U1 User’s Manual)  
Dimensions: ACS550-PD UL Type / NEMA 3R  
1-Phase 240V  
Weight*  
(lbs)  
Height  
(in)  
Width  
(in)  
Depth  
(in)  
HP  
15  
20  
25  
30  
40  
50  
310  
320  
330  
340  
345  
350  
49.00  
32.36  
22.88  
3-Phase 240V  
3-Phase 480V  
Weight*  
(lbs)  
Height  
(in)  
Width  
(in)  
Depth  
(in)  
Weight*  
(lbs)  
Height  
(in)  
Width  
(in)  
Depth  
(in)  
HP  
HP  
25  
30  
40  
50  
305  
310  
320  
330  
340  
345  
350  
300  
305  
310  
320  
330  
340  
345  
350  
40  
60  
50  
75  
49.00  
32.36  
22.88  
49.00  
32.36  
22.88  
60  
100  
125  
150  
200  
75  
100  
* Shipping crate adds approximately 170 lbs.  
Technical Data  
22  
ACS550-PD Packaged Drive with Disconnect  
Applicable Standards  
Drive compliance with the following standards is identified by the standards “marks” on  
the type code label.  
Mark  
Applicable Standards  
UL 508C and  
C22.2 No. 14  
UL Standard for Safety, Power Conversion Equipment, second  
edition and CSA Standard for Industrial Control Equipment  
UL 508A  
UL Standard for Safety, Industrial Control Panels  
CSA Standard for Industrial Control Equipment  
C22.2 No. 14  
Compliance is valid with the following provisions:  
• The motor and control cables are chosen as specified in this manual.  
• The installation rules of this manual are followed.  
Technical Data  
ACS550-PD 3R Irrigation Packaged Drive  
23  
ABB Inc.  
Low Voltage Drives  
16250 West Glendale Drive  
New Berlin, WI 53151  
USA  
Telephone +1 262 785-3200  
+1 800 HELP-365  
Telefax  
Internet  
+1 262 780-5135  

Mr Coffee MPX23 User Manual
Melissa 145 009 User Manual
LG Electronics 5450 User Manual
LaCie LaCinema Rugged HD User Manual
HP Hewlett Packard TM 11 6625 2779 14&P User Manual
GPX C389B User Manual
Gemini CD 4700 E User Manual
Fujitsu MAB3091 User Manual
Curtis KCR2613P User Manual
Aiwa XR M35 User Manual