Vulcan Hart VL2GSS User Manual

SERVICE MANUAL  
VL BOILER BASE SERIES  
CONVECTION STEAMERS  
(GAS, ELECTRIC, DIRECT AND REGENERATED)  
VL2GPS  
ML-52391  
VL2DPS  
VL2DMS  
VL2DAS  
VL2DSS  
VL3DPS  
VL3DMS  
VL3DAS  
VL3DSS  
VL2RPS  
VL2RMS  
VL2RAS  
VL2RSS  
VL3RPS  
VL3RMS  
VL3RAS  
VL3RSS  
ML-52749  
ML-52750  
ML-52751  
ML-52752  
ML-52753  
ML-52754  
ML-52755  
ML-52756  
ML-52757  
ML-52758  
ML-52759  
ML-52760  
ML-52761  
ML-52762  
ML-52763  
ML-52764  
VL2GMS ML-52388  
VL2GAS  
VL2GSS  
VL3GPS  
ML-52390  
ML-52389  
ML-52395  
VL3GMS ML-52392  
VL3GAS  
VL3GSS  
VL2EPS  
VL2EMS  
VL2EAS  
VL2ESS  
VL3EPS  
VL3EMS  
VL3EAS  
VL3ESS  
ML-52394  
ML-52393  
ML-52741  
ML-52742  
ML-52743  
ML-52744  
ML-52745  
ML-52746  
ML-52747  
ML-52748  
VL2GPS SHOWN  
- NOTICE -  
This Manual is prepared for the use of trained Vulcan Service  
Technicians and should not be used by those not properly  
qualified. If you have attended a Vulcan Service School for this  
product, you may be qualified to perform all the procedures  
described in this manual.  
This manual is not intended to be all encompassing. If you have  
not attended a Vulcan Service School for this product, you should  
read, in its entirety, the repair procedure you wish to perform to  
determine if you have the necessary tools, instruments and skills  
required to perform the procedure. Procedures for which you do  
not have the necessary tools, instruments and skills should be  
performed by a trained Vulcan Service Technician.  
Reproduction or other use of this Manual, without the express  
written consent of Vulcan, is prohibited.  
A product of VULCAN-HART  
Form 24650 (May 1999)  
LOUISVILLE, KY 40201-0696  
VL SERIES STEAMERS  
Direct Steam Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
Regenerated Steam (Older Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
Heater Contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
Heating Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
Thermal Switch - Prevent and Automatic Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
Water Level Gauge Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
Steam Gate Valve(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
ELECTRICAL OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38  
Water Level Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38  
Solid State - Low Level Cut-off & Differential Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38  
Electro Mechanical - Low Level Cut-off & Differential Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40  
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42  
Gas Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42  
Electric Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
Schematics, Gas Steamers, Boiler Controls  
VL2G AND VL3G - Prevent, Automatic, Standard and Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49  
Manual Ignition, Standard Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49  
Electronic Ignition, Standard Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50  
Manual Ignition, Csd-1 Code Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51  
Electronic Ignition, Csd-1 Code Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52  
Wiring Diagrams, Gas Steamers, Boiler Controls  
VL2G AND VL3G - Prevent, Automatic, Standard and Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54  
Manual Ignition, Standard Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54  
Electronic Ignition, Standard Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56  
Manual Ignition, Csd-1 Code Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58  
Electronic Ignition, Csd-1 Code Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60  
Schematics, Electric Steamers, Boiler Controls  
VL2E AND VL3E - Prevent, Automatic, Standard and Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62  
Auto Blowdown, Standard Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62  
Auto Blowdown, Cal-code Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63  
Wiring Diagrams, Electric Steamers, Boiler Controls  
VL2E AND VL3E - Prevent, Automatic, Standard and Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64  
Auto Blowdown, Standard Controls (Contactor - 1 Std.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64  
Auto Blowdown, Standard Controls (Contactors - 2 Std.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66  
Manual Blowdown, Cal-code Controls (Contactors - 1 Std. 1 Aux.) . . . . . . . . . . . . . . . . . . . . . . 68  
Auto Blowdown, Cal-code Controls ( Contactors - 1 Std. 1 Aux.) . . . . . . . . . . . . . . . . . . . . . . . . 70  
Auto Blowdown, Cal-code Controls (Contactors - 2 Std. 2 Aux.) . . . . . . . . . . . . . . . . . . . . . . . . 72  
Manual Blowdown, Cal-code Controls (Contactors - 2 Std. 2 Aux.) . . . . . . . . . . . . . . . . . . . . . . 74  
Wiring Diagrams, Electric Heater Circuits  
VL2E AND VL3E - Prevent, Automatic, Standard and Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76  
Schematic and Wiring Diagrams, Direct Steamers, Cabinet Base  
VL2D AND VL3D - Prevent, Automatic, Standard and Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77  
Wiring Diagrams, Regenerated Steamers, Boiler Controls  
VL2R AND VL3R - Prevent, Automatic, Standard and Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78  
Schematic and Wiring Diagrams - Compartment Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80  
Prevent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80  
Automatic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81  
Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82  
Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84  
© VULCAN 1999  
Page 3 of 88  
VL SERIES STEAMERS - GENERAL  
GENERAL  
Boiler Code Descriptions  
INTRODUCTION  
Vulcan-Hart incorporates redundant controls in  
compliance with California Code (Cal-Code) and  
CSD-1 as an option on steam equipment when  
required by state and/or local building code  
requirements. Descriptions of the codes are listed  
below.  
Steam Cooking  
Large capacity pressure steamers offer an efficient  
way to produce a wide variety of foods in small  
portions or larger batches. Steamers can be used to  
cook fresh foods, blanch foods for complete cooking  
later or will steam defrost and cook frozen foods.  
Cooking with steam assures the food will retain its  
maximum color, flavor and nutritional value with the  
least expenditure of energy and labor.  
Cal-Code Construction - Redundant controls in the  
electrical safety circuits that, if tripped, must  
manually be reset after the condition causing the trip  
subsides. These controls consist of one dual  
function water level cycling and low level cut off  
control and one single function low water level cut-  
off control (Aux - LLCO) and a high pressure relief  
switch in conjunction with a mechanical pressure  
relief valve.  
Compartment Pan Capacity  
PANS PER  
COMPARTMENT  
DEPTH  
(INCHES)  
SIZE  
CSD-1 Construction - Redundant controls in the  
electrical safety circuits that, if tripped, must  
manually be reset after the condition causing the trip  
subsides. These controls consist of one dual  
function water level cycling and low level cut off  
control and one single function low water level cut-  
off control (LLCO) and a high pressure relief switch  
in conjunction with a mechanical pressure relief  
valve. Additionally, both circuits have individual  
indicator lights that will illuminate for a visual  
verification of the shutdown mode.  
4
6
8
6
12" x 20"  
12" x 20"  
12" x 20"  
*18" x 20"  
6.0  
4.0  
2.5  
1.0  
* Remove center support for 18x20 inch pans  
Cal-Code and CSD-1 construction both require  
operator intervention in the event of a shutdown.  
CSD-1 is more informative by using indicator lights  
to show which safety system was shutdown.  
Model Designations  
V L X X XX  
Cooking Control Types:  
PS - Prevent Steam  
AS - Automatic Steam  
SS - Standard Steam  
MS - Manual Steam  
WATER CONDITIONING  
Furnishing the boiler with soft water to reduce scale  
formation is important. Scale formation will reduce  
steam output, cause premature component failure,  
and shorten equipment life. Most water supplies  
contain scale producing minerals such as Calcium  
and Magnesium. As steam is generated, the  
minerals remain and dissolve into the water. As the  
concentration of these minerals increases past a  
certain point, they precipitate from the water and  
coat the inside of the boiler, heating elements,  
thermostat bulbs and water level probes. Because of  
the high temperature of these surfaces, the  
precipitated minerals bake onto them and become  
very difficult to remove.  
Heating System:  
G - Gas  
E - Electric  
D - Direct  
R - Regenerated  
Number of Compartments  
Large Capacity Pressure  
Steamer  
Vulcan  
Page 4 of 88  
VL SERIES STEAMERS - GENERAL  
NOTE: Adaptors vary between manufacturers. An  
This causes several problems:  
example of one adaptor type is pictured below.  
1. Reduce the heat transfer efficiency of the  
heating system.  
2. Cause premature failure of Electric heaters.  
3. Water level probes will give false readings.  
4. Thermostat bulbs will sense temperature  
incorrectly.  
These problems are common to any manufacturer's  
steamer regardless of design, but they can all be  
prevented by furnishing the boiler with soft water.  
Vulcan recommends the water contain less than  
60ppm of “total dissolved solids” (TDS) and have a  
PH factor between 7 to 8. These water properties  
can be achieved by using a properly maintained  
water softener.  
SPECIFICATIONS  
Water Supply  
Other chemical properties in water supplies can also  
affect good steam generation and vary from within  
each state and locality.  
Supply pressure should be  
In line strainer for supply line  
Supply connection  
Total dissolved solids (TDS)*  
Total alkalinity  
20-80 psig  
(Not Supplied)  
cold  
The water level probes in the boiler use ions in the  
water to detect the water level. Do not use fully  
demineralized or de-ionized water since it is "non  
conductive" and the water level can not be detected.  
less than 60 ppm  
less than 20 ppm  
less than 13 ppm  
less than 30 ppm  
7 to 8  
Silica  
Chloride  
NOTE: The use of strainers, or filters will not  
remove minerals from the water.  
PH factor  
(*17.1 ppm = 1 grain of hardness)  
Vulcan recommends that a local water treatment  
specialist be consulted before the installation of any  
steam generating equipment.  
Steam Supply  
Steamers that operate over a long period of time  
without the benefit of a water softener, which have  
developed a heavy scale build up, should be  
cleaned before using a water softener.  
Dry steam must be provided to the steamer for  
suitable use. If the steam is heavy with condensate,  
a Ball Float Trap must be used in the line and  
plumbed in before the pressure reducing valve. To  
ensure rapid heat up of heavy cold loads, the steam  
supply line must be sized to maintain pressure as  
outlined below.  
TOOLS  
Standard  
Standard set of hand tools.  
Volt-Ohm-Meter (VOM) with AC current tester.  
DIRECT STEAM  
STEAMERS  
REGENERATED  
STEAMERS -  
(POTABLE)  
OLDER MODELS  
(*NON-POTABLE)  
(Any quality VOM with a sensitivity of at least  
20,000 ohms per volt can be used)  
Gas leak checking equipment.  
Gas pressure manometer  
Temperature meter and thermocouple.  
Special  
Supply  
Pressure Input  
15 psi (min.)  
15 psi (min.)  
Flow Rate  
50 lb. per hour per  
compartment  
125 lb. per hour  
Pressure  
Reducing Valve  
Output  
10 psi (furnished) set accordingly for good  
steam generation (10-  
CLR Treatment Kit - Used to remove  
Calcium/Lime/Rust from a boiler (Contact  
Vulcan Authorized Service Centers ).  
12psi)  
*Potable steam is not required for regenerated models but could  
be used.  
Adaptor to test thermocouple closed circuit  
voltages (DC) on gas models with manual  
ignition (purchase locally).  
Page 5 of 88  
VL SERIES STEAMERS - GENERAL  
Gas Steamers  
LINE PRESSURE  
MANIFOLD  
INPUT  
AMPS  
(MAX)  
(INCHES W.C.)  
PROPANE  
PRESSURE  
(BTU/HR)  
LOAD  
(INCHES W.C.)  
NATURAL  
(WATTS)  
MAX  
120V  
60HZ  
MODEL  
VL2GPS  
VL2GMS  
VL2GAS  
VL2GSS  
VL3GPS  
VL3GMS  
VL3GAS  
VL3GSS  
NAT.  
PROP. NAT.  
PROP.  
10.0  
10.0  
10.0  
10.0  
10.0  
10.0  
10.0  
10.0  
RECOMMEND  
MIN  
5.0  
5.0  
5.0  
5.0  
5.0  
5.0  
5.0  
5.0  
RECOMMEND  
11.0  
MIN  
200,000 200,000  
240,000 240,000  
200,000 200,000  
240,000 240,000  
200,000 200,000  
240,000 240,000  
200,000 200,000  
240,000 240,000  
200,000 200,000  
240,000 240,000  
200,000 200,000  
240,000 240,000  
200,000 200,000  
240,000 240,000  
200,000 200,000  
240,000 240,000  
4.0  
4.0  
4.0  
4.0  
4.0  
4.0  
4.0  
4.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
11.0 14.0  
11.0 14.0  
11.0 14.0  
11.0 14.0  
11.0 14.0  
11.0 14.0  
11.0 14.0  
11.0 14.0  
360  
360  
360  
360  
360  
360  
360  
360  
3.0  
3.0  
3.0  
3.0  
3.0  
3.0  
3.0  
3.0  
11.0  
11.0  
11.0  
11.0  
11.0  
11.0  
11.0  
Electric Steamers  
AMPERAGE  
1 PHASE  
3 PHASE  
3 PHASE - 4 WIRE  
TOTAL  
KW  
24*  
36  
MODEL  
208V 240V 208V 240V 480V 220/380V & 240/415V  
116 100  
116 100  
116 100  
116 100  
67  
58  
87  
29  
44  
34  
50  
100  
117  
VL2EPS  
42  
48  
116  
58  
58  
29  
44  
67  
34  
50  
24*  
36  
67  
100  
117  
87  
VL2EMS  
VL2ESS  
42  
48  
116  
58  
58  
29  
44  
67  
34  
50  
24*  
36  
67  
100  
117  
87  
42  
48  
116  
58  
58  
29  
44  
67  
34  
50  
24*  
36  
67  
100  
117  
87  
VL2EAS  
*std  
42  
48  
116  
58  
67  
Page 6 of 88  
VL SERIES STEAMERS - GENERAL  
Also, the ignition control module  
STEAMER OPERATION  
ON/OFF/RESET switch must be in the ON  
position to operate. This switch is located  
on the upper left side of the electrical  
control box for the ignition control module.  
A red light will illuminate when the switch  
is in the ON position. DO NOT ATTEMPT  
TO MANUALLY LIGHT THE PILOT IN AN  
AUTOMATIC TYPE IGNITION SYSTEM.  
Ensure that all utility connections to the steamer  
have been made and are turned on.  
On models that are CSD-1 equipped, amber colored  
lights for hi pressure and low water level will  
illuminate and stay on until the boiler is full and the  
manual reset switch pressed.  
After the main power switch is turned ON  
and the ignition control modules RESET  
switch is in the ON position, sparking will  
begin three seconds later to light the  
standing pilot. If the pilot lights, a signal is  
sent back through the ignition cable  
indicating the presence of pilot flame and  
sparking stops. If the water level in the  
boiler has reached the minimum level, the  
burners will ignite and begin to heat the  
water in the boiler. After approximately 15  
minutes, steam should be present for  
cooking product. Observe that the boiler  
pressure gauge indicates a steam  
pressure of 9-11 psi for models with a  
pressure regulating valve or 4-6 psi for  
models without the valve. If a pilot flame  
is not established immediately, sparking  
will continue for 90 seconds. After that  
duration, the ignition control module will  
lock out and needs to be reset to start the  
pilot and burner lighting cycle again.  
Gas Powered Steam Boiler  
5. Open the cabinet door and turn main power  
switch ON. The red light will illuminate, water  
will begin filling the boiler and the blowdown  
solenoid valve will close. The boiler should fill,  
in four to eleven minutes. Observe water level  
gauge glass to verify that water is in boiler and  
that the level in the gauge glass is about half  
full. Both valves on gauge glass assembly must  
be open to fill the gauge. Older models  
equipped with a manual “ball” type blowdown  
valve must be closed for the boiler to fill. The  
cycling pressure switch will maintain the proper  
steam pressure in the boiler by cycling the  
heating system on and off to generate steam  
pressure.  
A. On Models with Manual Ignition - The  
knob on the gas combination control valve  
has three positions (On-Pilot-Off) for  
control of main burners and pilot. Turn  
knob on gas combination valve to PILOT  
then depress and light pilot burner with a  
lit taper. Maintain knob in depressed  
position for about 30 seconds and release.  
Observe that pilot burner flame stays on. If  
the flame should go out, wait 5 minutes  
before relighting.  
Electrically Powered Steam Boiler  
Open the cabinet door and turn main power switch  
ON. The red light will illuminate, water will begin  
filling the boiler and the blowdown solenoid valve  
will close. The boiler should fill, in approximately 11  
minutes. Observe water level gauge glass to verify  
that water is in boiler and that the level in the gauge  
glass is about half full. Both valves on gauge glass  
assembly must be open to fill the gauge. Older  
models equipped with a manual “ball” type  
blowdown valve must be closed for the boiler to fill.  
If the water level in the boiler has reached the  
minimum level, the heater contactors will close, the  
heaters will energize and begin to heat the water in  
the boiler. After approximately 15 minutes, steam  
should be present for cooking product. Observe that  
the boiler pressure gauge indicates steam pressure  
of 9-11 psi for models with a pressure regulating  
valve or 4-6 psi for models without the valve.  
Turn knob on gas combination control  
valve to ON. If the water level in the boiler  
has reached the minimum level, burners  
will ignite and begin to heat the water in  
the boiler. After approximately 15 minutes,  
steam should be present for cooking  
product. Observe that the boiler pressure  
gauge indicates steam pressure of 9-11  
psi for models with a pressure regulating  
valve or 4-6 psi for models without the  
valve.  
B. On Models with Automatic Ignition -  
The knob on the gas combination control  
valve has two positions (On-Off) for  
Regenerated Steam Powered Boiler  
control of main burners and pilot. For the  
automatic ignition system to work, the  
knob must be set in the ON position or gas  
for the pilot and main burners will not flow.  
Open the cabinet door and turn main power switch  
ON. The pilot light will illuminate, water will begin  
filling the boiler and the blowdown solenoid valve  
will close. Models equipped with a manual “ball  
type” blowdown valve need to be closed for the  
boiler to fill. The boiler should fill, in approximately  
15 minutes.  
Page 7 of 88  
VL SERIES STEAMERS - GENERAL  
Observe water level gauge glass to verify that water  
Cooking Compartment Controls  
is in boiler and that the level in the gauge glass is  
about half full.  
Close the compartment door and turn the screw  
handle clockwise until the gasket touches the  
compartment surface then ½ turn further to  
adequately seal the compartment. If steam leaks  
occur after compartment heat up and pressurization,  
turn handle clockwise again to increase the sealing  
force until the leak stops.  
Both valves on the gauge glass assembly must be  
open to fill the gauge. When the water reaches the  
minimum level, the steam solenoid valve will open,  
allowing steam to enter the steam coil in the heat  
exchanger tank and begin heating the water. After  
approximately 20 minutes, a sufficient amount of  
pressurized steam should be present for cooking  
product.  
Proceed to the cooking compartment control  
instructions that apply to the steamer in use.  
Direct Steam Powered Cooker  
1. Manual  
1. Open the cabinet door and turn main power  
switch ON.  
A. Set the manual timer to the desired  
cooking time. If preheating is desired,  
allow five to ten minutes (recommended)  
of additional time at the beginning of the  
cook cycle. The length of time will vary  
with the type, size, temperature and  
condition (frozen or thawed) of the product  
and must be determined from experience.  
Pull the steam control arm handle forward  
and lock it by pulling the handle down.  
This closes the steam exhaust gate valve  
and opens the steam inlet gate valve,  
allowing steam to enter the compartment.  
During preheat, cooler air and condensate  
are exhausted from the compartment  
through the steam trap (condenser) until  
the temperature reaches 180°F, closing  
the internal bellows. Throughout the  
cooking cycle, the compartment pressure  
should be 6 psi if equipped with a  
A. The red light on the switch will illuminate.  
B. If steam pressure is above the minimum  
setting on the cooking compartment  
pressure switch then the switch will close,  
ready light will come ON and power to the  
other controls will be supplied.  
C. Observe that the steam pressure gauge in  
the cabinet base, indicates 10-12 psi.  
2. Steamer is ready to cook product.  
Boiler Blowdown and Steamer Shut off  
Turn the steamer off at least once daily and blow  
down the boiler to remove sediments, scalants and  
lime build-up in the boiler. Always blowdown the  
boiler when it is under maximum pressure and no  
steam is being used.  
3. Automatic blowdown.  
compartment pressure regulating valve.  
On models without the compartment  
pressure regulating valve, the  
compartment pressure cycles with the  
boiler pressure between 4 and 6 psi.  
A. Newer Models - Open the cabinet door  
and turn main power switch OFF. The  
switches’ red light will go out, the  
blowdown/drain solenoid valve will be de-  
energized and the boiler will begin to  
drain. The cold water condenser solenoid  
will continue to operate, as needed, to  
condense steam and to cool the water  
going into the drain.  
B. When the timer bell rings to signal the end  
of a cook cycle, turn it OFF. Lift the steam  
control arm handle to unlatch team control  
arm. An internal spring will automatically  
pull the arm to the rear. This closes the  
steam inlet gate valve and opens the  
B. Older Models - Turn power switch OFF  
and depress blowdown timer button.  
Blowdown timer will operate for 4 minutes.  
At the end of blowdown, turn fill switch ON  
and allow boiler to fill.  
steam exhaust gate valve, allowing steam  
and pressure to exit the compartment.  
C. Wait approximately 30 seconds for the  
steam to exhaust from the compartment  
and to depressurize. Turn the screw  
handle on the compartment door  
counterclockwise until the gasket no  
longer seals against the compartment  
surface. After the remaining steam  
escapes, move the latch paddle to the left  
and open the door.  
4. Manual blowdown.  
A. All Models - Turn power switch OFF. Open  
blowdown valve located on the bottom  
front of the cabinet base. After the boiler  
has completely drained, close blowdown  
valve and turn fill switch to ON and allow  
boiler to fill.  
Page 8 of 88  
VL SERIES STEAMERS - GENERAL  
2. Standard  
A. Set the timer to the desired cooking time.  
3. Automatic  
A. Set the timer to the desired cooking time.  
The timer must be set past five minutes to  
change the state of the timer control  
micro switch contacts.  
The timer must be set past five minutes to  
change the state of the timer control micro  
switch contacts. If preheating is desired,  
allow five to ten minutes (recommended)  
of additional time at the beginning of the  
cook cycle. The length of time will vary  
with the type, size, temperature and  
B. Pull the steam control arm handle forward  
and lock it by pulling the handle down.  
This closes the steam exhaust gate valve  
and opens the steam inlet gate valve,  
allowing steam to enter the compartment.  
condition (frozen or thawed) of the product  
and must be determined from experience.  
C. Press the compartment power switch to  
supply power to the compartment controls.  
The automatic compartment controls,  
feature load compensated cooking time by  
utilizing a thermal switch. With this  
B. Pull the steam control arm handle forward  
and lock it by pulling the handle down.  
This closes the steam exhaust gate valve  
and opens the steam inlet gate valve,  
allowing steam to enter the compartment.  
feature, when the compartment  
C. Press the compartment power switch to  
energize the timer and red light. The  
balance of the cooking sequence is  
automatic. During preheat, cooler air and  
condensate are exhausted from the  
compartment through the steam trap  
(condenser) until the temperature reaches  
180°F, closing the internal bellows.  
temperature reaches 180°F (the  
temperature at which preheating or  
defrosting is complete) the red light will  
then come on and the timer will start. For  
a small food load, the delay time before  
the timer starts might be a minute or less.  
For a large food load, the delay time could  
be four to five minutes. During preheat,  
cooler air and condensate are exhausted  
from the compartment through the steam  
trap (condenser) until the temperature  
reaches 180°F, closing the internal  
bellows. Throughout the cooking cycle, the  
compartment pressure should be 6 psi if  
equipped with a compartment pressure  
regulating valve. On models without the  
compartment pressure regulating valve,  
the compartment pressure cycles with the  
boiler pressure between 4 to 6 psi.  
Throughout the cooking cycle, the  
compartment pressure should be 6 psi if  
equipped with a compartment pressure  
regulating valve. On models without the  
compartment pressure regulating valve,  
the compartment pressure cycles with the  
boiler pressure between 4 and 6 psi.  
D. Approximately one minute before timer  
reaches zero the steam control solenoid is  
energized to unlatch the steam control  
arm. An internal spring will automatically  
pull the arm to the rear. This closes the  
steam inlet gate valve and opens the  
steam exhaust gate valve, allowing steam  
and pressure to exit the compartment.  
When the timer reaches "0" the red light  
shuts off and a buzzer sounds indicating  
the end of the cook cycle. Turn the  
D. Approximately one minute before timer  
reaches zero the steam control solenoid is  
energized to unlatch the steam control  
arm. An internal spring will automatically  
pull the arm to the rear. This closes the  
steam inlet gate valve and opens the  
steam exhaust gate valve, allowing steam  
and pressure to exit the compartment.  
When the timer reaches "0" the red light  
shuts off and a buzzer sounds indicating  
the end of the cook cycle. Turn the  
compartment power switch OFF to silence  
the buzzer and remove power from the  
compartment controls.  
E. Turn the screw handle on the  
compartment door counterclockwise until  
the gasket no longer seals against the  
compartment surface. After the remaining  
steam escapes, move the latch paddle to  
the left and open the door.  
compartment power switch OFF to silence  
the buzzer and remove power from the  
compartment controls.  
E. Turn the screw handle on the  
compartment door counterclockwise until  
the gasket no longer seals against the  
compartment surface. After the remaining  
steam escapes, move the latch paddle to  
the left and open the door.  
Page 9 of 88  
VL SERIES STEAMERS - GENERAL  
D. Approximately one minute before timer  
4. Prevent  
A. Set the timer to the desired cooking time.  
reaches zero the steam control solenoid is  
energized to unlatch the steam control  
arm. An internal spring will automatically  
pull the arm to the rear. This closes the  
steam inlet gate valve and opens the  
steam exhaust gate valve, allowing steam  
and pressure to exit the compartment.  
When the timer reaches "0" the red light  
shuts off and a buzzer sounds indicating  
the end of the cook cycle. Turn the  
compartment power switch OFF to silence  
the buzzer and remove power from the  
compartment controls.  
The timer must be set past five minutes to  
change the state of the timer control  
micro switch contacts.  
B. Pull the steam control arm handle forward  
and lock it by pulling the handle down.  
This opens the steam inlet gate valve,  
allowing steam to enter the compartment.  
C. Press the compartment power switch to  
supply power to the compartment controls.  
The prevent compartment controls feature  
load compensated cook times by utilizing  
a thermal switch. With this feature, when  
the compartment temperature reaches  
180°F (the temperature at which  
E. Turn the screw handle on the  
compartment door counterclockwise until  
the gasket no longer seals against the  
compartment surface. After the remaining  
steam escapes, move the latch paddle to  
the left and open the door.  
preheating or defrosting is complete) the  
red light will come on and the timer will  
start. For a small food load, the delay time  
before the timer starts might be a minute  
or less. For a large food load, the delay  
time could be four and five minutes.  
During preheat, the steam exhaust  
solenoid valve (N.O.) is open to allow the  
full free venting of cooler air and  
condensate from the compartment. When  
the temperature reaches 180°F, the  
exhaust solenoid valve is energized and  
closes. The compartment should then  
pressurize to 6 psi.  
Page 10 of 88  
VL SERIES STEAMERS - GENERAL  
COMPONENT FUNCTION  
CABINET BASE BOILER CONTROLS  
Water Level  
Gauge Assembly . . . . . . . . . . . . . . . Permits a visual confirmation the water level is being maintained in  
boiler during operation. The correct water level is a point one-half of the  
height of the glass. The manual valves at the top and bottom of this  
assembly must be fully open and only closed if the glass tube is  
damaged.  
Water Level Control and  
Level Sensing Probes . . . . . . . . . . . These controls allow water to enter the boiler to fill and maintain the  
proper water level. They will also shut off the heat source to the boiler if  
the water level drops too low. The water level control works by using  
three different probe lengths to monitor the water level. The probes  
consist of a high level (HL), low level (LL) and low water cut-off (LLCO).  
Boiler Fill Solenoid Valve . . . . . . . . Admits water to the boiler when demanded by the water level control to  
maintain the correct water level in the boiler.  
Cold Water Condenser  
Solenoid Valve . . . . . . . . . . . . . . . . . Allows cold water flow into the boiler blowdown drain box to condense  
steam and cool the hot water before its discharge into the drain.  
Cycling Pressure Switch . . . . . . . . . Controls boiler pressure between prescribed limits by turning the heat  
source on and off.  
High Limit Pressure Switch . . . . . . A switch of identical design to the cycling pressure switch but used as a  
high limit. The pressure settings are at higher and lower limits than the  
cycling pressure switch in order to turn off the heat source before the  
boiler pressure reaches its limit and automatically resets after the  
pressure drops below the lower limit set point.  
Blowdown/Drain  
Solenoid Valve . . . . . . . . . . . . . . . . . This valve is plumbed into the drain line of the boiler. Newer steamer  
models will automatically blowdown when power is turned off by using a  
normally open solenoid valve. Older models can have a solenoid valve  
that is activated by depressing a separate blowdown timer button or  
have a manual “ball” type valve.  
Inlet Water Strainer . . . . . . . . . . . . . A strainer is used in the water inlet line to prevent foreign matter from  
becoming lodged in the fill or cold water condenser solenoid valves and  
to keep unwanted particles out of the system. A "Y" strainer should be  
inserted upstream of the fill solenoid valve. On models using a direct  
steam supply, a strainer is also used in the pressure regulating valve.  
Power Switch . . . . . . . . . . . . . . . . . . When turned ON, power is supplied to the controls and the steam  
generating process is started in the boiler. The power switch is located  
on the front of the boiler control box.  
Water Inlet Valve . . . . . . . . . . . . . . . The water inlet valve is used to stop water flow to the steamer when the  
steamer is being serviced. Newer models will have a small Petcock type  
valve while older models will be a “ball” type valve. This valve should  
remain open during normal operation.  
High Limit Thermostat . . . . . . . . . . A protective device that shuts off the heat source if the boiler  
temperature exceeds a specified limit. All standard models are equipped  
with a surface high limit.  
Descaler . . . . . . . . . . . . . . . . . . . . . . Hangs submerged in water inside the boiler and is used to help control  
boiler surface scaling. Two descalers are used in each boiler.  
Page 11 of 88  
VL SERIES STEAMERS - GENERAL  
Handhole Cover Assembly . . . . . . . When unbolted and removed, allows internal examination and cleaning  
of boiler shell and its components if required.  
Boiler Pressure Gauge . . . . . . . . . . Indicates the amount of steam pressure in the boiler.  
Check Valve . . . . . . . . . . . . . . . . . . . On models with the delime piping assembly option, prevents the ejection  
of hot water and steam out of the delime funnel if the manual delime fill  
valve were to be opened.  
Delime Port Assembly . . . . . . . . . . . On models with the delime piping assembly option, allows the boiler and  
other internal components to be delimed, easily removing calcium, lime  
and rust build up.  
Gas Pilot . . . . . . . . . . . . . . . . . . . . . Should always remain lit to light the main burners upon a call for heat  
unless the steamer will not be in use for an extended period. If the pilot  
flame goes out, wait 5 minutes before relighting.  
Gas Burners . . . . . . . . . . . . . . . . . . . Heats the water in the boiler to generate steam.  
Gas Combination Control Valve . . . A gas solenoid valve that opens to allow gas flow when a call for heat is  
made. Also regulates the manifold gas pressure and supplies the gas  
pilot.  
Transformer . . . . . . . . . . . . . . . . . . . Provides 24VAC power to ignition control module. (gas models with  
electronic ignition)  
Ignition Control Module . . . . . . . . . Controls and monitors gas heating. Energizes pilot valve coil to supply  
gas to pilot, generates spark to ignite gas at the pilot, monitors the  
presence of flame and energizes main valve coil upon a call for heat to  
supply gas to the main burners. The pilot and main solenoids are part of  
the gas combination control valve. (gas models with electronic ignition)  
Ignition Control Module  
Reset (ON/OFF) Switch . . . . . . . . . . Controls power to the ignition control module and allows a reset of the  
module if the gas ignition exceeds trial time. (gas models with electronic  
ignition)  
Heater Contactor  
(Electric Boilers) . . . . . . . . . . . . . . . When coil is energized, supplies power to the electric heating elements.  
Heating Elements  
(Electric Boilers) . . . . . . . . . . . . . . . Heats the water in the boiler to generate steam.  
Steam Header Assembly . . . . . . . . . Main steam supply line from the boiler to the steam header inlet in the  
cooking control compartment.  
Pressure Relief Valve . . . . . . . . . . . A mechanical device that opens to relieve steam pressure in the boiler if  
the pressure exceeds 15 psi.  
Compartment Pressure  
Regulating Valve . . . . . . . . . . . . . . . Reduces steam pressure form the boiler or building steam (direct and  
regenerated models) to supply the compartments a steam pressure of 6  
psi. Standard on PS, option on MS, SS and AS compartment controls.  
Page 12 of 88  
VL SERIES STEAMERS - GENERAL  
COOKING COMPARTMENT CONTROLS  
The top half of the steamer consists of two to three separate cooking compartments depending on the model.  
Each compartment functions independently with its own set of controls. Power is supplied to the controls through  
the compartment power switch and the cooking timer control micro switch contacts. Prevent and Automatic  
models have a load compensating thermal switch that prevents the controls from receiving power until the  
compartment reaches 180°F to close the switch.  
Compartment Power Switch . . . . . . Supplies power to the cooking compartment controls.  
Cooking Light (Red) . . . . . . . . . . . . When lit, indicates steamer is in a cooking cycle. (All models except  
manual)  
Cooking Timer . . . . . . . . . . . . . . . . . Use to set desired cooking cycle time between 0-60 minutes. Energizes  
the buzzer when time expires (All models except manual). On Prevent  
models, also de-energizes the steam exhaust solenoid valve one minute  
before the end of a cook cycle to allow compartment venting.  
Buzzer . . . . . . . . . . . . . . . . . . . . . . . Signals end of a cook cycle, must be turned off manually. (All models  
except manual)  
Steam Exhaust Solenoid Valve . . . A normally open valve that allows full compartment venting of air and  
condensate up to 180°F during compartment heat up and “limited free  
venting” after energized by the closing of the thermal switch. The valve  
remains closed to allow compartment pressurization to 6 psi until one  
minute before the end of a cook cycle at which point the timer control  
micro switch contacts (SW2) change state and de-energize the valve to  
vent the compartment of pressure and steam. (prevent models)  
Steam Header Inlet (manifold) . . . . Main steam supply line from the boiler for each cooking compartment.  
Supplies steam to the manual steam gate valves.  
Compartment Pressure Gauge . . . . Indicates the amount of steam pressure in cooking compartments.  
Steam Control Arm Solenoid . . . . . When energized, engages the lift arm (plunger) to raise the steam  
control arm off of the catch, allowing it to return to its rear position. This  
closes the steam inlet gate valve and opens the steam exhaust gate  
valve. (prevent, automatic and standard models)  
Thermal Switch  
(Load Compensator) . . . . . . . . . . . . Controls power to the preheat cycle components. Turns the cooking light  
on, energizes the steam exhaust solenoid valve and energizes the  
cooking timer motor to start timing, after the compartment reaches  
180 F. (prevent and automatic models)  
Steam Gate Valves . . . . . . . . . . . . . Manual valves actuated by the steam control arm. Allows steam to flow  
into the cooking compartment through the inlet steam gate valve when  
the arm is in a forward position and exhaust the steam through the  
exhaust steam gate valve when the arm is at the rear. Prevent models  
use a steam exhaust solenoid valve to exhaust the steam and a single  
steam gate valve as the steam inlet. The automatic, standard and  
manual models use one steam gate valve to exhaust the steam and  
one additional steam gate valve as the steam inlet.  
Steam Trap (Condenser) . . . . . . . . . Exhausts air and condensate from compartment during preheat until the  
compartment temperature reaches approximately 180 F. The bellows  
then close, stopping the exhaust. (all models except prevent)  
Page 13 of 88  
VL SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
REMOVAL AND REPLACEMENT OF PARTS  
COMPONENT LOCATIONS  
Page 14 of 88  
VL SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
Page 15 of 88  
VL SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
COOKING COMPARTMENT CONTROLS - COMPONENT CONFIGURATIONS  
1. Prevent  
thermal switch, inlet steam gate valve, steam exhaust solenoid  
(shown above) valve, steam control arm solenoid, timer, buzzer and power switch  
with light. Does not use a steam trap.  
2. Automatic  
same as prevent except does not include steam exhaust solenoid  
valve but does include an exhaust steam gate valve and two steam  
traps.  
3. Standard  
4. Manual  
same as automatic except does not include thermal switch.  
manual and exhaust steam gate valves and a manual timer.  
Includes two steam traps.  
Page 16 of 88  
VL SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
4. Slide the glass tube upwards until the bottom of  
WATER LEVEL CONTROLS -  
LOW LEVEL CUT OFF AND  
DIFFERENTIAL  
the tube is clear of the fitting and lift it out.  
5. When reinstalling the tube use new sealing  
washers. Do not over tighten the packing nuts;  
it could break the gauge glass.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
6. Open the top and bottom valves and check for  
proper operation.  
CYCLING AND HIGH LIMIT  
PRESSURE SWITCHES  
Solid State  
1. Open the cabinet base doors.  
(GAS AND ELECTRIC MODELS)  
2. Remove the two screws at the top of the boiler  
control box and allow cover to drop down.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
3. Water level control is mounted on the back  
side of cover.  
4. Disconnect lead wires from the board and  
remove the water level control.  
1. Open the cabinet base doors and remove the  
left side panel.  
5. Reverse procedure to install and check for  
proper operation.  
2. Remove the two screws at the top of the boiler  
control box and allow cover to drop down.  
Electro Mechanical  
3. The pressure switches are located at the rear of  
the box. The pressure switch on the right is the  
cycling or primary control; the one on the left is  
the high limit control. They are identical  
1. Open the cabinet base doors.  
2. Remove the two screws from the left and right  
side of the water level control box and lift cover  
off.  
switches, differing only in their settings.  
4. Remove the cover from the pressure switch  
being replaced and disconnect the lead wires.  
3. Disconnect lead wires from the control being  
replaced and remove.  
5. Disconnect the pressure fittings at the bottom  
of the switch.  
4. Reverse procedure to install and check for  
proper operation.  
6. Remove the mounting screws on the back side  
of the control box and lift out the pressure  
switch.  
WATER LEVEL GAUGE  
ASSEMBLY  
7. Preset the new pressure switch to the  
approximate cut-out (off) and cut-in (on) set  
points before installing. See the boiler pressure  
chart under “CYCLING AND HIGH LIMIT  
PRESSURE SWITCHES (GAS AND  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
ELECTRIC MODELS)” in “SERVICE  
PROCEDURES AND ADJUSTMENTS”.  
8. Reverse procedure to install.  
9. Adjust the pressure switch(s) final set points as  
outlined under “CYCLING AND HIGH LIMIT  
PRESSURE SWITCHES (GAS AND  
ELECTRIC MODELS)” in “SERVICE  
PROCEDURES AND ADJUSTMENTS” and  
check for proper operation.  
1. Open the cabinet base doors and remove the  
right side panel.  
2. Close the valve at the top and at the bottom of  
the gauge assembly.  
3. Unscrew the packing nuts at the top and bottom  
of the glass tube.  
Page 17 of 88  
VL SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
BOILER ASSEMBLY  
HIGH LIMIT THERMOSTAT  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
WARNING: SHUT OFF THE GAS BEFORE  
1. Open the cabinet base doors.  
SERVICING THE UNIT.  
2. Electric models only - for gas models proceed  
to step 3.  
WARNING: ALL GAS JOINTS DISTURBED  
DURING SERVICING MUST BE CHECKED FOR  
LEAKS. CHECK WITH A SOAP AND WATER  
SOLUTION (BUBBLES). DO NOT USE AN OPEN  
FLAME.  
A. Newer Models - are not equipped with a hi  
limit thermostat but rely on the Hi limit  
pressure switch instead.  
B. Older Models - the high limit thermostat is  
located behind the contactor box cover.  
On electric boilers with two heating  
elements, the thermostat is connected to  
one of the heating element lugs. On  
electric boilers with four heating elements,  
the thermostat is located on an aluminum  
plate between the center pair of elements  
at the top of the elements. Remove the  
thermostat lead wires and mounting nuts,  
replace thermostat and check for proper  
operation.  
1. Blow down the boiler and allow to cool, if  
necessary.  
2. Ensure that all utilities to the steamer are off  
and disconnected. Drain any excess water from  
the boiler.  
3. Disconnect the steam supply line, power leads  
and drain lines from the cooking compartment  
top to the boiler base.  
4. Disconnect all plumbing connections and power  
leads from the components inside the control  
boxes that would obstruct the removal of the  
boiler through the front of the base, then  
remove those control boxes.  
3. Gas Models only.  
A. Remove the thermostat cover which is  
located on the front of the boiler.  
5. Disconnect the remaining plumbing and  
electrical connections from the boiler to the  
controls.  
Disconnect the thermostat lead wires and  
remove the nuts securing the high limit  
thermostat to the boiler surface.  
6. Remove the screws holding the flue and flue  
collector to the base.  
4. Reverse procedure to install and check for  
proper operation.  
7. Remove the anchor screws holding the boiler to  
the frame. Slide the boiler forward. The burner  
box, anchored only by the boiler, must be  
prevented from sliding forward with the boiler.  
8. Reverse procedure to install a new boiler and  
check for leaks and proper operation.  
Page 18 of 88  
VL SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
BOILER FILL AND COLD WATER  
GAS COMBINATION CONTROL  
CONDENSER SOLENOID VALVES  
VALVE  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
1. Turn off the water supply to the steamer.  
WARNING: SHUT OFF THE GAS SUPPLY  
2. Open the cabinet base doors and remove the  
two screws at the top of the boiler control box  
and allow cover to drop down. Both solenoid  
valves are located side by side near the front of  
the boiler control box with the boiler fill on the  
right and the cold water condenser to the left.  
BEFORE SERVICING THE UNIT.  
WARNING: ALL GAS JOINTS DISTURBED  
DURING SERVICING MUST BE CHECKED FOR  
LEAKS. CHECK WITH A SOAP AND WATER  
SOLUTION (BUBBLES). DO NOT USE AN OPEN  
FLAME.  
3. Disconnect the power lead wires from the  
solenoid valve being serviced.  
NOTE: Gas combination control valves are not  
serviceable and should not be disassembled. Once  
the problem has been isolated to this control,  
replace it. Do not attempt to repair the assembly.  
4. Disconnect the water lines for the valve being  
serviced and remove the valve.  
5. Reverse procedure to install.  
1. Open the cabinet base doors and remove the  
two screws at the top of the boiler control box  
and allow cover to drop down.  
PILOT AND THERMOCOUPLE  
ASSEMBLY (GAS MODELS)  
2. Disconnect electrical supply wires and conduit  
running to the combination control valve.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
3. Disconnect the thermocouple lead (if  
applicable), pilot gas supply tube from control  
and pipe connections on each side of the  
control.  
4. Reverse procedure to install.  
WARNING: SHUT OFF THE GAS BEFORE  
SERVICING THE UNIT.  
5. Set manifold pressure as outlined under “GAS  
MANIFOLD PRESSURE ADJUSTMENT” in  
“SERVICE PROCEDURES AND  
WARNING: ALL GAS JOINTS DISTURBED  
DURING SERVICING MUST BE CHECKED FOR  
LEAKS. CHECK WITH A SOAP AND WATER  
SOLUTION (BUBBLES). DO NOT USE AN OPEN  
FLAME.  
ADJUSTMENTS”.  
6. Check for proper operation.  
1. Open the cabinet doors to access the pilot and  
thermocouple assembly. The assembly is  
located to the right of the center burner and  
half way back from the front.  
2. Disconnect thermocouple and pilot gas supply  
tubing from the combination control valve.  
3. Remove the two screws holding the pilot to its  
bracket.  
4. Replace the thermocouple or pilot assembly  
and check for proper operation.  
Page 19 of 88  
VL SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
4. Turn screw handle fully counterclockwise and  
COMPARTMENT GASKET AND  
remove from door.  
DOOR SCREW NUT, DOOR AND  
BUSHINGS  
5. Remove screws mounting the pressure bar to  
the backside of the compartment door.  
NOTE: A compression spring is mounted behind  
each screw. Set aside for reuse.  
Gasket  
6. Remove screws mounting the door screw nut  
(bronze) to the backside of the compartment  
door.  
1. Open the compartment door to be replaced.  
2. Remove screws securing the gasket retaining  
plate to the gasket.  
7. Reverse procedure to install and check for  
proper operation.  
Door and Bushing  
1. Open the compartment door to be replaced.  
2. Remove the right side pan support inside the  
compartment.  
3. Remove the four bolts inside the compartment  
that secure the block hinges to the exterior side  
of the compartment.  
3. Lift the gasket off the inner door plate.  
CAUTION: Door is extremely heavy and will drop  
when bolts are removed.  
4. Position the new gasket on the inner door plate  
and reverse procedure to install.  
NOTE: Damage to the gasket sealing surface, such  
as nicks or cuts, will cause steam leakage.  
Door Screw Nut  
1. Open compartment door to be serviced.  
2. Turn screw handle fully clockwise to extend  
inner door plate assembly.  
3. Lift the inner door plate assembly up, until the  
mounting pins are out of the holes in the  
pressure bar and set the assembly aside.  
4. At this time, the bushings can be replaced if  
necessary, by removing the bushings from the  
pin on each block hinge.  
5. Reverse procedure to install and check for  
proper operation.  
Page 20 of 88  
VL SERIES STEAMERS - REMOVAL AND REPLACEMENT OF PARTS  
HEATER CONTACTORS  
REGENERATED STEAM MODELS  
(STEAM COIL)  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
1. Open the cabinet base doors, remove the two  
screws from the contactor box cover and lift  
cover off.  
WARNING: SHUT OFF THE STEAM SUPPLY  
BEFORE SERVICING THE UNIT.  
2. Disconnect the electrical lead wires to the coil  
and the power supply wires from the contactor  
being replaced.  
1. Disconnect pipe unions in the steam supply line  
to the coils and in the condensate discharge  
line from the coils.  
3. Remove the screws form the base of the  
contactor and lift out.  
2. Remove header that supplies steam to the coils  
by disconnecting union at each coil.  
4. Reverse procedure to install and check for  
proper operation.  
3. Remove coil condensate collection header.  
4. Remove bolts securing the coil being replaced  
and pull coil forward.  
HEATING ELEMENTS  
5. Clean the mating surfaces of the steam coil  
flange and the boiler.  
6. Reverse procedure to install a new steam coil  
and gasket.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
7. Check steamer for proper operation.  
1. Open the cabinet base doors, remove the two  
screws from the contactor box cover and lift  
cover off.  
2. Disconnect the electrical lead wires to the  
element being replaced.  
3. Remove the bolts securing the heating element  
flange to the boiler and lift the element out.  
4. Clean the mating surface of the boiler and  
install a new flange gasket and heating  
element.  
5. Check for leaks and proper operation.  
Page 21 of 88  
VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
SERVICE PROCEDURES AND ADJUSTMENTS  
WARNING: CERTAIN PROCEDURES IN THIS SECTION REQUIRES ELECTRICAL TEST OR  
MEASUREMENTS WHILE POWER IS APPLIED TO THE MACHINE. EXERCISE EXTREME CAUTION AT ALL  
TIMES. IF TEST POINTS ARE NOT EASILY ACCESSIBLE, DISCONNECT POWER, ATTACH TEST  
EQUIPMENT AND REAPPLY POWER TO TEST.  
NOTE: Boiler water capacities vary between seven  
BOILER  
to nine gallons for both gas and electric models  
depending on the boiler size and BTU/KW rating.  
Inspection  
NOTE: If deliming solution accidently comes in  
contact with steamer components, lightly rinse off  
with clean water.  
It is recommended the boiler be inspected for  
excessive scale and lime build up on a quarterly  
basis. In hard water areas or for steamers heavily  
used, a more frequent interval should be used. This  
inspection consists of an internal examination and  
cleaning of the boiler, an examination of the two  
hanging descalers, and for lime build up on the  
water level probes. Also, a check of all boiler  
controls, including the pressure switches.  
A. Models with Blowdown Timer - Pour  
deliming solution into boiler shell. Proceed  
to step 9.  
B. Models without Blowdown Timer - Turn off  
the incoming water supply. Turn the power  
switch ON to close the drain valve. Pour  
deliming solution into boiler shell. Proceed  
to step 9.  
Periodic service must be performed as outlined in  
these procedures. See “WATER CONDITIONING”  
under “GENERAL”.  
C. Models with Deliming Port Assembly -  
Before pouring deliming solution into  
boiler, clean the seating surfaces for the  
hand hole gasket and then install a new  
gasket. Position the hand hole plate and  
tighten down. Turn off the incoming water  
supply. Turn the power switch ON to close  
the drain valve. Open the deliming  
WARNING: READ AND FOLLOW THE  
INSTRUCTIONS ON THE CLR BOTTLE. USE  
PLASTIC OR RUBBER GLOVES TO AVOID SKIN  
CONTACT. IF CLR LIQUID COMES IN CONTACT  
WITH THE SKIN, RINSE WITH CLEAN WATER.  
Clean-Out (All Boiler Models)  
assembly valve and pour the deliming  
solution into the port. Close the deliming  
assembly valve and proceed to step 10.  
1. Turn steamer OFF and drain boiler.  
2. Remove hand hole plate and gasket (top front)  
from the boiler by removing the nut and clamp,  
then tapping the cover lightly to free it while  
holding the cover stud. This prevents the cover  
from dropping into boiler.  
3. Remove old descaler retaining springs if  
present.  
4. With a wire brush, or equivalent, dislodge and  
remove all loose scale from boiler shell. The  
loose material must be either scooped from the  
boiler or flushed through the drain.  
5. Check probe canister and float valve assembly  
(regenerated models) for a scale build up and  
clean as necessary.  
6. Check drain hole for obstructions.  
7. Inspect the condition of the descalers as  
outlined in this section and replace if  
necessary.  
9. Clean the seating surfaces for the hand hole  
gasket and then Install a new gasket. Position  
and tighten the hand hole plate.  
8. Mix the deliming solution according to the  
instructions for the chemical being used.  
Page 22 of 88  
VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
10. Cooking compartment timers are to be in the  
OFF position. Turn the boiler switch ON and  
open water valve if necessary.  
B. Models without Blowdown Timer - Turn  
off the incoming water supply. Turn the  
power switch ON to close the drain valve.  
Open the deliming assembly valve and  
pour the deliming solution into the port.  
Close the deliming assembly valve and  
proceed to step 3.  
11. Boiler is to operate under pressure for 90  
minutes or per the instructions for the chemical  
in use.  
12. Drain boiler by normal methods.  
13. Refill boiler and allow to heat until fully  
pressurized.  
14. Repeat step 13 three times.  
15. The steamer is now ready for normal operation.  
Deliming Only (Models with Deliming Port  
Assembly)  
Boiler deliming should be performed on a weekly,  
bi-weekly or monthly basis, depending on the quality  
of the local water supply. See “WATER  
CONDITIONING” under “GENERAL”.  
On steamers using a water purification system,  
follow the instructions for that system to delime the  
boiler. Only use the type of chemical recommended  
or described in the instructions for deliming with this  
type of system.  
3. Top compartments are to be in the OFF  
position. Turn the boiler switch ON and open  
water valve if necessary.  
4. Boiler is to operate under pressure for 90  
minutes or per the instructions for the chemical  
in use.  
1. Turn steamer OFF and drain boiler.  
2. Mix the deliming solution according to the  
instructions for the chemical being used.  
5. Drain boiler by normal methods.  
NOTE: Boiler water capacities vary between seven  
to nine gallons for both gas and electric models  
depending on the boiler size and BTU/KW rating.  
6. Refill boiler and allow to heat until fully  
pressurized.  
7. Repeat step 6 three times.  
8. Steamer is now ready for normal operation.  
Descaler  
NOTE: If deliming solution accidently comes in  
contact with steamer components, lightly rinse off  
with clean water.  
The descaler is accessible through the hand hole  
opening. It is a coiled wire wound around a solid  
cylindrical core, and hangs by an open loop from the  
shell's horizontal stay rod, about 4 inches from the  
front of the shell. If the wire is eaten through, or if  
the core of the descaler is eaten away to half its  
original size, a new descaler should be installed.  
A. Models with Blowdown Timer - Open  
the deliming assembly valve and pour the  
deliming solution into the port. Close the  
deliming assembly valve and proceed to  
step 3.  
To install a new descaler, stretch its wire coil so the  
descaler hangs with its core completely below the  
minimum water level in the boiler, but hanging free.  
The descaler must not contact the bottom of the  
boiler shell, electric heating elements or  
regenerating steam coils.  
Page 23 of 88  
VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
5. Once the water level reaches the high level  
WATER LEVEL CONTROL(S)  
TEST  
(HL) probe, the inverse latching relay of the  
board (solid state) should energize and lock  
through the low level probe (LL) and ILR-1  
contacts. With ILR-2 contacts open, the HL  
relay is de-energized and HL LED goes out.  
With the HL-3 contacts open, the boiler fill  
solenoid should de-energize and stop the boiler  
fill.  
Loose electrical connections may prevent the heat  
from coming on or may cause the boiler to overfill.  
An accumulation of lime scale on or near the water  
level sensing probes may cause them to retain  
water (moist) on the probe surface and give a false  
reading. Also, a cracked or damaged insulator may  
give a false reading. These conditions may prevent  
the boiler from filling or cause dry firing. Dry firing  
will result in damage to the heating elements on  
electric models or to the boiler on gas or electric  
models.  
6. If water is in the boiler but is not being detected  
by the water level probes, the probes may need  
cleaned and/or boiler delimed. See “Water  
Level Probes” as outlined below for inspecting  
and cleaning of probes and “BOILER” for a  
procedure on boiler inspection, clean-out and  
deliming.  
WARNING: THE FOLLOWING STEPS REQUIRE  
POWER TO BE APPLIED TO THE UNIT DURING  
THE TEST. USE EXTREME CAUTION AT ALL  
TIMES.  
7. Turn the power switch OFF and disconnect the  
lead wire from each probe. Check the probes  
as outlined below.  
A. With an ohmmeter, check between the  
probe terminal and boiler shell. An open  
circuit should be present when the boiler is  
empty. If resistance is present, remove  
and inspect the probes as outlined below  
under “Water Level Probes”. When the  
boiler is full of water, a resistance reading  
should be measurable between the probes  
and boiler.  
Solid State - Low level Cut-Off & Differential  
Control  
1. Turn the power switch ON.  
2. Ensure that water is filling the boiler.  
A. Confirm that water supply valve(s) are  
turned on.  
B. Observe boiler water level in the water  
level gauge. If empty, boiler should fill in  
approximately 11 minutes.  
NOTE: The actual resistance reading will depend on  
water quality and probe condition.  
3. Check the voltage across terminals L1 & L2 on  
the board. Meter should read 120VAC.  
8. After performing steps 1-5A and verifying the  
water level control boards operation, if the  
control is not functioning as described, then  
replace it and check for proper operation.  
A. If voltage is correct then the high level  
(HL) relay should energize, closing HL-3  
contacts and the HL LED should light up.  
The boiler fill solenoid should then  
Electro Mechanical - Low level Cut-Off &  
Differential Control  
energize and start filling the boiler. Verify  
boiler fill solenoid valve is receiving  
120VAC and water is flowing through it.  
WARNING: THE FOLLOWING STEPS REQUIRE  
POWER TO BE APPLIED TO THE UNIT DURING  
THE TEST. USE EXTREME CAUTION AT ALL  
TIMES.  
B. If boiler fill solenoid is receiving power but  
no water is flowing, inspect fill solenoid for  
malfunction or valve for clogged ports. If  
solenoid is bad or ports can not be  
1. Ensure that water is filling the boiler.  
A. Confirm that water supply valve(s) are  
turned on.  
cleaned, then replace boiler fill solenoid  
and check for proper operation.  
B. Observe boiler water level in the water  
level gauge.  
C. If boiler fill solenoid is not receiving power  
and the electrical connections have been  
checked, then the HL relay is not being  
energized or the HL-3 contacts are not  
closing. Replace water level control board  
and check for proper operation.  
C. Verify boiler fill solenoid valve is receiving  
120VAC and water is flowing through it.  
2. Check for correct voltage being applied to the  
low level and differential water level controls.  
4. If boiler is filling properly, when the water level  
reaches the low level cut-off (LLCO) probe,  
LLCO relay should energize closing LLCO-2  
contacts, heat source should come on  
(standard models only) and LLCO LED will  
light.  
A. Turn the water supply valve off then turn  
the power switch ON. Check the input  
voltage across terminals 1 & 2. Meter  
should read 120VAC. If voltage is correct  
proceed to step 2B. If voltage is incorrect,  
find the source of the problem and repeat  
this step.  
Page 24 of 88  
VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
B. With the boiler empty, check the voltage  
2. If lime scale build up is evident on the probe,  
thoroughly clean it removing all deposits from  
the probe and insulator. Do not use any thing  
abrasive on the insulator; use a soft cloth.  
across terminals 9 & 10. Meter should  
read 300 to 350VAC. If voltage is correct  
proceed to step 3. If voltage reading is  
approximately 30VAC then the internal  
contactor is energized but the probes are  
scaled over and moist and/or have a  
damaged insulator giving a false reading.  
See “Water Level Probes“ listed below for  
inspecting and cleaning and “BOILER” for  
procedures on boiler inspection, clean-out  
and deliming. If you do not read any  
voltage, then contactor coil on the water  
level control is bad and the control should  
be replaced. Check for proper operation  
after replacement.  
3. Inspect the probes for a cracked or damaged  
insulator. If a probe appears to be damaged,  
replace it with a new one and proceed to step  
5. If a probe does not appear to be damaged  
then proceed to step 4.  
4. Check through the probe socket opening in the  
top of the canister assembly for the presence of  
water. Water must drain from the probe  
canister and if in doubt, pour water into the  
canister and observe that it drains quickly. If  
water fails to drain from the canister, remove  
the cover or canister assembly and clean.  
3. If water is in the boiler but is not being detected  
by the water level probes, the probes may need  
cleaned and/or boiler delimed. See “Water  
Level Probes“ listed below for inspecting and  
cleaning and “BOILER” for procedures on  
boiler inspection, clean-out and deliming.  
5. Reverse procedure to install and check for  
proper operation.  
CYCLING AND HIGH LIMIT  
PRESSURE SWITCHES  
(GAS AND ELECTRIC MODELS)  
4. Turn the power switch OFF and disconnect the  
lead wire from each probe. Note the location of  
the probes and the number of the wire  
connected to it.  
A. Check the resistance between the probe  
terminal and boiler shell. An open circuit  
should be present when the boiler is  
empty. If resistance is present, remove  
and inspect the probes as outlined below  
under “Water Level Probes”. A resistance  
reading should only be measurable  
WARNING: THE FOLLOWING STEPS REQUIRE  
POWER TO BE APPLIED TO THE UNIT DURING  
THE TEST. USE EXTREME CAUTION AT ALL  
TIMES.  
Remove the boiler control box cover as outlined  
under “CYCLING AND HIGH LIMIT PRESSURE  
SWITCHES (GAS AND ELECTRIC MODELS)” to  
access the two controls. The pressure switch on the  
right is the cycling or primary control; the one on the  
left is the high limit control. They are identical  
switches, differing only in their settings.  
between the probes and boiler shell  
(ground) when the boiler is full of water.  
NOTE: The actual resistance reading will depend on  
water quality and probe condition.  
5. If after performing steps 1-4 and the control is  
not functioning properly, verify the water level  
controls operation as outlined in “WATER  
LEVEL CONTROLS” under “ELECTRICAL  
OPERATION”.  
Turn the power ON and let the boiler come up to  
pressure. Close and seal one of the compartment  
doors, set a time past 5 minutes on the cooking  
timer, pull the steam control arm handle forward and  
turn the compartment power switch ON to exhaust  
pressure from the boiler. Observe boiler pressure  
gauge readings for several cycles and compare  
them with the pressure settings in the chart.  
6. After checking the above items, if the low level  
cut off or differential water level control does  
not appear to be functioning as described, then  
replace the control and check for proper  
operation.  
If the readings differ, adjust the pressure settings as  
described below.  
Water Level Probes  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
1. Remove the cover over the water level probes  
and disconnect the lead wire from each probe.  
Note the location of each probe and the  
number of the wire connected to it. Remove  
each water level probe for examination.  
Page 25 of 88  
VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
Two slotted and square headed adjustment screws  
1. Remove the coil assembly from the valve stem  
by lifting up on the retaining cap at the top of  
the solenoid valve and sliding the metal cover  
plate off.  
extend through the top of the switch case. A  
pressure scale and indicating pointers are visible  
through the sight glass window to indicate the  
approximate pressure setting. The adjustment screw  
directly above the right side pointer changes the  
cut-out (off) set point and the adjustment screw  
directly above the left side pointer changes cut-in  
(on) set point. Adjust the screw to obtain the proper  
cut-out (off) setting first, then adjust the other screw  
to obtain the proper cut-in (on) setting. Turn the  
screw clockwise to increase the pressure setting and  
counterclockwise to decrease the pressure setting.  
The pressure settings for each switch are listed  
below.  
2. Clamp the body of the valve in a vise.  
3. Mark a scribe line on the stem nut to the valve  
body for proper retightening.  
4. Remove the stem locking nut to remove the  
stem from the valve body.  
5. All parts are now accessible for inspection and  
cleaning.  
NOTE: If internal solenoid parts appear to be  
damaged or worn, then replace the solenoid valve.  
Do not reuse damaged or worn parts. No internal  
solenoid parts are available as a service  
replacement.  
BOILER PRESSURE SETTINGS (PSI)  
CYCLING  
HIGH  
LIMIT  
CONTROL  
TYPE  
VL  
MODELS  
A. Check rubber seal on bottom of plunger.  
B. Check plunger spring.  
ON  
OFF ON OFF  
PS  
AS  
SS  
MS  
AS  
SS  
MS  
C. Check O-ring in valve body.  
D. Check ports in valve body.  
With  
Compartment  
Pressure  
9
11  
6
2
15  
15  
Regulating Valve  
With-Out  
Compartment  
Pressure  
4
6
Regulating Valve  
FILL AND COLD WATER  
SOLENOID VALVES  
6. Reverse procedure to install.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
COMPARTMENT PRESSURE  
ADJUSTMENT  
Check to assure the solenoid valve is receiving  
power. If the solenoid valve is receiving power but  
the valve is not opening, the coil may be  
malfunctioning. Replace the solenoid valve and  
check for proper operation. If the solenoid valve is  
receiving power and the valve appears to be  
opening but little or no water is flowing through it,  
then the valve ports may be clogged with debris or a  
valve component malfunctioning. To check solenoid  
valve further, follow the procedure outlined below.  
Remove the left side panel from the boiler base to  
access the compartment pressure regulating valve.  
If the steamer is equipped with the compartment  
pressure regulating valve and the steamer is  
operating, set the pressure regulating valve to read  
6 psi on the compartment gauge. Turn the hex head  
screw at the top clockwise to increase the pressure  
and counterclockwise to decrease. If the steamer is  
not equipped with the compartment pressure  
regulating valve, then the compartment will cycle at  
the same pressures of the boiler. A mechanical  
pressure relief valve serves as a safety backup  
control and is pre-set for a maximum of 8 psi.  
Disassembly  
NOTE: It is recommended that the valve be  
removed for cleaning as outlined in this procedure.  
This will prevent damage to the lines and fittings  
when the stem is removed from the body.  
Page 26 of 88  
VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
If water fails to drain from the canister, remove the  
HIGH LIMIT THERMOSTAT  
cover or canister assembly and clean. These  
conditions indicate extremely poor water quality  
being supplied to the boiler and/or boiler clean out  
and deliming has not been performed.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
The water condition must be cleared up immediately  
with a proper water conditioner to avoid further  
problems with the steamer. Re-install the water level  
probes and canister assembly (if applicable).  
Perform a boiler inspection, clean-out and deliming  
procedure as outlined under “BOILER”. Check for  
proper operation.  
Remove thermostat (bi-metallic disk type) as  
outlined under “HIGH LIMIT THERMOSTAT” in  
“REMOVAL AND REPLACEMENT OF PARTS”.  
Inspect the temperature sensing side of thermostat  
for corrosion or rust. Clean mounting and thermostat  
surfaces before remounting or replacing. A good  
metal-to-metal contact is essential for proper  
functioning of the thermostat. This service must be  
performed at least once a year. If thermostat mating  
surface can not be throughly cleaned or is severely  
pitted and rusted, then replace and check for proper  
operation.  
Water may be draining through an open boiler  
blowdown solenoid valve as quickly as it’s fed to the  
boiler. Loose wiring, a burned out coil or particles of  
scale trapped in the valve seat may prevent the  
valve from closing.  
Newer steamer models use a plunger type rod that  
raises and lowers to permit steam/water flow out of  
boiler. If debris has accumulated around the water  
orifice, the plunger may not seat properly to close  
off the opening. If this symptom is suspect, remove  
the solenoid as outlined in “FILL AND COLD  
WATER SOLENOID VALVES”. Remove any debris  
found on sealing surfaces, reassemble and install. If  
the solenoid valve still does not function properly,  
replace it with a new valve and check for proper  
operation.  
BOILER NOT FILLING WITH  
WATER  
Ensure that water to the steamer is turned on, then  
turn power switch ON. After approximately 10  
minutes, if no water is observed in the water level  
gauge sight glass, then check for a problem with the  
boiler fill solenoid valve, water level control(s) or the  
water level probes. See “WATER LEVEL  
CONTROL TEST”. Also, ”water hammering” in the  
supply line, in conjunction with a check valve can  
cause a high water pressure pocket in the water line  
to the fill solenoid valve. The fill solenoid valve will  
not be able to overcome this pressure and operate  
to supply the boiler with water. Shut off the water  
supply and relieve the pressure in the line. Turn the  
water supply back on and check for proper  
operation.  
Older steamer models have a movable blade and  
when closed, the blade reacts as a guillotine that  
should be free to move fully down into the valve  
pocket (projection at bottom of valve) so that the  
pierced hole in the blade aligns perfectly with the  
body opening. If debris has accumulated in the  
bottom of the valve pocket, then the blade will not  
move into the pocket completely. If this symptom is  
suspect, remove the solenoid as outlined in “FILL  
AND COLD WATER SOLENOID VALVES”.  
NOTE: On this valve body, remove the two  
assembly bolts holding the brass body together and  
remove the loose internal parts. Remove any debris  
found on sealing surfaces, reassemble and install. If  
the solenoid valve still does not function properly,  
replace it with a new valve and check for proper  
operation.  
NOTE: To eliminate this problem, the customer  
must install a “water hammer suppression device” in  
the supply line to the boiler.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
BOILER BLOWDOWN DRAIN  
SOLENOID VALVE  
Scalants may be covering the water level control  
probe giving a false indication of a sufficient water  
level in the boiler. Remove and thoroughly clean the  
water level probes to remove scalants and lime  
build up. Also, Check through the probe socket  
opening in the top of the canister assembly for the  
presence of water.  
The water contained in the boiler, being under  
pressure, should be blown through this valve and be  
noticeably visible exhausting out the steamer drain.  
Daily boiler blowdown is essential to proper  
operation and component life by removing sediment  
and scalants that may be lodged in the chamber of  
the boiler.  
Water must drain from the probe canister and if in  
doubt, pour water into the canister and observe that  
it drains quickly.  
Page 27 of 88  
VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
If the blowdown operation appears to function  
NORMAL OPERATING STEAMER PRESSURES (PSI)  
sluggishly or not at all, considerable scalants may  
be lodged in the drain pipe and/or the valve.  
Disconnect the valve from the drain line and inspect  
both the valve and the drain pipe fixed to the boiler.  
If considerable scalants or lime build up is apparent,  
then not only the valve, but also the boiler and water  
level probes must be thoroughly cleaned. See “FILL  
AND COLD WATER SOLENOID VALVES” for an  
inspection and cleaning procedure of a solenoid  
valve and "BOILER” for a procedure on boiler  
inspection, clean out and deliming.  
CYCLING  
HIGH LIMIT  
CONTROL  
TYPE  
VL  
MODELS  
ON  
OFF ON OFF  
PS  
AS  
SS  
MS  
With  
Compartment  
Pressure  
9
11  
6
15  
Regulating Valve  
AS  
SS  
MS  
With-Out  
Compartment  
Pressure  
4
6
2
15  
1. If your steamer has an automatic blowdown  
drain valve.  
Regulating Valve  
A. Newer Models  
1. All Models (With Boiler)  
1) Are equipped with normally open  
solenoid valves that close when  
energized by the main power switch.  
When the main power switch is  
turned off, the solenoid valve is de-  
energized and the boiler blowdown  
valve re-opens.  
A. Check for low water pressure input, line  
strainer clogged or fill solenoid valve  
malfunction. See “FILL AND COLD  
WATER SOLENOID VALVES”.  
B. Boiler blowdown solenoid valve may be  
clogged and not fully closing. Check for a  
slow leak out of steamer drain. If not able  
to verify, then proceed to step 1C. If  
blowdown solenoid valve appears to be  
functioning properly, then proceed to step  
1D.  
B. Older Models  
1) Turn the power switch(s) OFF and  
press the blowdown timer button. This  
activates the boiler blowdown timer  
and energizes (opens) the solenoid  
valve. Timer operates approximately  
four minutes then shuts off.  
C. Turn power switch OFF, disconnect lead  
wires from blowdown solenoid and remove  
it for inspection.  
D. A heavy build-up of scalants has possibly  
coated the interior of the boiler. The  
2. If your steamer has a manual blowdown drain  
valve.  
insulating effect of the scalants hampers  
heat transfer. Unbolt and remove the hand  
hole cover plate and gasket assembly.  
Examine interior of boiler and if scalants  
and/or lime build up is apparent, perform a  
boiler inspection, clean-out and deliming  
procedure. See “BOILER”. If considerable  
scalants are evident, then both the boiler  
blowdown solenoid valve and the water  
level probes must also be examined.  
A. Turn the power switch(s) OFF then open  
the valve to blowdown the boiler. Close  
the valve at the end of the blowdown  
sequence so boiler will be ready to fill.  
BOILER SLOW TO PRESSURIZE  
2. Gas Models  
A. Low incoming gas pressure causes  
reduced BTU output. Check incoming line  
and manifold gas pressures as outlined in  
“GAS MANIFOLD PRESSURE  
If the boiler requires more than 15 minutes (20  
minutes for regenerated models) to achieve normal  
operating pressure as listed in below, then check the  
following conditions.  
ADJUSTMENT.”  
B. Gas combination control valve  
malfunction. Check incoming and manifold  
gas pressures as outlined in “GAS  
MANIFOLD PRESSURE ADJUSTMENT.”  
If pressure adjustments are made and  
manifold pressure remains low, replace  
the combination valve and check for  
proper operation.  
Page 28 of 88  
VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
C. Gas burner ports clogged or obstruction  
INLET WATER STRAINER  
around air shutter. After a period of time,  
gas burners can accumulate carbon in  
their ports or become clogged by food and  
grease debris from kitchen cleaning,  
restricting performance. To clean burners,  
remove them from burner box and boil in  
water for 10 -15 minutes to dislodge clog.  
Clean-out any remaining debris from the  
gas ports using a wire brush, scribe or pic  
type metal instrument. Remove any other  
foreign objects that appear to be  
The in-line Y strainer should be located upstream of  
the fill valve solenoid. Shut off the water supply.  
Unscrew the cap from the body on the leg of the Y  
that should be pointing downwards toward the floor.  
Remove the screen and any foreign particles  
trapped in the opening. Rinse the screen thoroughly  
to remove accumulated debris and replace the  
screen in the valve body. If screen can not be  
thoroughly cleaned, replace it with a new one.  
Reinstall the cap and ensure that the Y strainer is  
positioned with the cap pointing downward to catch  
debris.  
obstructing the gas ports or air shutters.  
D. Gas orifice clogged or obstructed around  
air shutter. It is possible for debris to  
become lodged in the small gas orifice  
opening over time. Clean-out the gas  
orifice using a round metal instrument of  
the same hole diameter or slightly smaller.  
Clean as needed. If clogging reappears,  
the orifice should be removed, cleaned  
and reinstalled. Remove any other foreign  
objects that appear to be obstructing the  
gas orifice or air shutters.  
The pressure regulating valve strainer will become  
clogged if dirty steam lines are connected to direct  
steam models. Remove the hex nut on the bottom  
of the pressure regulating valve to clean the strainer  
and valve seat.  
PILOT AND THERMOCOUPLE  
ASSEMBLY (GAS MODELS)  
3. Electric Models  
A. One or more electric heating elements  
malfunctioning. See “HEATING  
ELEMENTS”  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
B. One or more heater contactors not pulling  
in to power heating elements.  
C. If steamer operates under three phase  
power, then check line for all phases.  
WARNING: SHUT OFF THE GAS BEFORE  
SERVICING THE UNIT.  
D. Heavy scale build up on heating element  
causes reduced heating.  
The pilot thermocouple when heated, supplies a DC  
millivolt signal to an internal solenoid valve on the  
gas combination control valve. This solenoid valve  
is designed to shut off the gas flow to the pilot and  
main burners in case of a malfunction in the system.  
When energized by the thermocouple voltage, the  
valve is held in the open position to permit gas flow.  
The pilot burner flame is controlled by an adjustable  
needle valve located under a small cap screw on  
the combination control valve.  
4. Direct Steam Models  
A. Building steam supply pressure low.  
B. Cooking compartment steam solenoid  
valve malfunction.  
C. Steam pressure regulator adjusted too  
low.  
D. Clogging in the steam line reduces steam  
supply.  
When experiencing pilot outages, visually check  
pilot flame for the proper contact on thermocouple  
and the flame color. Also, check to see that  
excessive air drafts are not interfering with proper  
heating of the thermocouple by the pilot flame.  
5. Regenerated (Steam Coil) Steamers  
A. Heavy scale build up inside copper steam  
coil.  
B. Building steam supply pressure low  
The pilot flame should be a steady blue flame that  
envelopes the thermocouple tip. The flame should  
be about one inch long with half its length extending  
beyond the outer edges of the pilot shield. If the pilot  
flame does not appear to be this length and color,  
then adjust as necessary. See the diagram below for  
an example of unsatisfactory pilot flames. Turn  
clockwise to decrease pilot flame and  
C. Cooking compartment steam solenoid  
valve malfunction.  
counterclockwise to increase.  
Page 29 of 88  
VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
Check the thermocouple output voltage as follows:  
NOTE: If adjustments in gas or pilot pressure  
settings are made, always replace the adjustment  
cover screw to assure proper gas control operation.  
1. Turn the power switch OFF and disconnect the  
thermocouple from the gas combination control  
valve.  
2. Check the thermocouple DC millivolt output  
with a VOM. If a meter is not available, replace  
the thermocouple with a new one and check  
operation again.  
A. Install a thermocouple adaptor into the  
connection on the gas combination control  
valve. Screw the thermocouple in to the  
adaptor then connect the meter leads to it.  
See “TOOLS” under “GENERAL” for  
information on thermocouple adaptor. If a  
thermocouple adaptor is not available then  
turn the power switch OFF, disconnect the  
thermocouple from the gas combination  
control valve and proceed to step 2D.  
B. Turn the power switch ON and light the  
pilot. Allow the pilot to heat the  
thermocouple for one to two minutes and  
take a closed circuit reading. Compare the  
readings with the chart below.  
1) If the reading is less than the  
minimum or thermocouple is not  
operating as described, replace the  
thermocouple as outlined under  
“PILOT AND THERMOCOUPLE  
ASSEMBLY (GAS MODELS)” in  
“REMOVAL AND REPLACEMENT  
OF PARTS” then check for proper  
operation.  
If the adjustment does not result in a pilot flame of  
proper size, then gas might not be flowing properly  
to the pilot. Check for a plugged pilot orifice, a  
kinked or plugged pilot gas supply tube and for low  
gas supply pressure. The pilot operates unregulated  
at gas supply pressures while the pressure regulator  
in the combination control valve regulates pressure  
to the main burners only. Visually check the  
thermocouple tip (hot end) and tube lead for kinks or  
pinches that might be causing a short between the  
tube and the wire inside. Also, check the threaded  
connector tip for corrosion, tarnish or dirt which can  
cause a poor connection. If the thermocouple shows  
either of these signs, it should be replaced with a  
new one.  
2) If the reading is within the range listed  
in the chart below then thermocouple  
is operating properly. Reconnect the  
thermocouple to the gas combination  
control valve.  
3) If after replacing thermocouple, the  
pilot or main burners are still not  
functioning properly, then a problem  
in the gas combination control valve  
exists as well. Replace the  
combination control valve as outlined  
under “GAS COMBINATION  
CONTROL VALVE” in “REMOVAL  
AND REPLACEMENT OF PARTS”  
then check for proper operation.  
NOTE: The connection of the tubing from the  
thermocouple tip to the control valve is an electrical  
connection and must be clean. Do not use any  
sealing compound on the threads or over tighten the  
threaded connection. Finger tighten the nut plus 1/4  
turn with a wrench. Over tightening the nut could  
crush the insulator, shorting the thermocouple.  
C. Turn the power switch OFF and  
disconnect the thermocouple adaptor from  
the gas combination control valve and  
thermocouple.  
If the pilot flame is correct and there are no drafts,  
then the problem is in the thermocouple output  
voltage or the gas solenoid valve in the combination  
control.  
Page 30 of 88  
VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
D. With the thermocouple disconnected, 3. Loosen the set screw on the burner being  
connect the meter leads to the tube and  
threaded end. Turn the power switch ON  
and light the pilot. Hold down the  
adjusted. Closing the air shutter will decrease  
primary air to the burner and opening the  
shutter will increase primary air the burner.  
OFF/PILOT/ON knob and allow the pilot to  
heat the thermocouple for one to two  
minutes. Take an open circuit reading and  
compare with the chart below.  
4. Monitor the burner flame and set the air shutter  
opening as follows:  
A. Open up the air shutter until the inner  
portion (blue) of the flame lifts off the  
burner port and then turn the air shutter  
back until the flame touches the burner  
port again. A slight tinge of orange and  
yellow in the flame is acceptable. An  
extremely yellow flame indicates too little  
primary air (oxygen), producing poor  
burning characteristics and the heating  
efficiency drops off. A by product of this  
would be soot (carbon).  
1) If the reading is less than the  
minimum or thermocouple is not  
operating as described, replace the  
thermocouple as outlined under  
“PILOT AND THERMOCOUPLE  
ASSEMBLY (GAS MODELS)” in  
“REMOVAL AND REPLACEMENT  
OF PARTS” then check for proper  
operation.  
3. If after checking and/or replacing  
Factory air shutter settings are: natural  
gas - open approximately ½ inch;  
propane gas - fully open.  
thermocouple, the pilot or main burners are still  
not functioning properly, then a problem in the  
gas combination control valve exists as well.  
Replace the combination control valve as  
outlined under “GAS COMBINATION  
CONTROL VALVE” in “REMOVAL AND  
REPLACEMENT OF PARTS” then check for  
proper operation.  
5. After the air shutter adjustment is made, tighten  
the set screw.  
Inspection  
Remove gas burners by lifting burner up and sliding  
it to the rear just enough to clear the gas orifice  
hood. Lower the front end of burner and bring it  
forward under the gas manifold pipe. Inspect burner  
for clogged or damaged ports. Clean or replace as  
necessary. When reinstalling burners, assure that  
locating pin is in the hole for proper positioning and  
to prevent burner from rolling over.  
NOTE: Gas combination control valves are not  
serviceable and should not be disassembled. Once  
you have isolated the problem to this control,  
replace it. Do not attempt to repair the assembly.  
THERMOCOUPLE  
DC MILLIVOLT  
READINGS  
CLOSED CIRCUIT  
(CONNECTED)  
OPEN CIRCUIT  
(DISCONNECTED)  
AUTOMATIC IGNITION SYSTEMS  
(GAS MODELS)  
Typical  
Range  
15  
10 - 20  
20 - 35  
When the main power switch is turned ON and the  
ignition control modules reset switch is in the ON  
position, the ignition control module is energized  
with 24VAC between terminals five and six.  
GAS BURNERS  
High voltage is sent from terminal nine to the spark  
electrode and an output of 24 volts is sent from  
terminals two and three to the pilot coil in the  
combination valve, allowing gas to flow to the pilot.  
The sparking will continue for 90 seconds or until  
the flame sensor has confirmed that an adequate  
pilot flame is present.  
The main gas burners are located under the boiler  
for heating and number five to seven depending on  
the steamer model. They are made of aluminized  
steel with lanced type ports and have adjustable air  
shutters in the front. Fixed orifice type hoods extend  
from the manifold to establish gas flow to each  
burner.  
Air Shutter Adjustment  
1. Ignite the burners and allow to heat up for at  
least five minutes.  
2. Verify the manifold pressure as outlined under  
“GAS MANIFOLD PRESSURE  
ADJUSTMENT”.  
Page 31 of 88  
VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
Once the pilot flame is confirmed, a 24 volt output  
A. Check to ensure that all electrical terminal  
connections on the ignition control module  
and the ignitor are clean and tight. If loose  
connections are found, make the  
from terminal one will be sent, allowing the main  
valve (cycling) coil of the combination valve to  
operate at the request of the cycling pressure  
switch.  
necessary adjustments.  
B. Verify that the ignition control module and  
the ignitor have good ground wire  
connections. The ignitor mounting bracket  
should have good metal to metal contact  
to its mounting surface.  
C. Remove the pilot ignitor and check the  
following:  
1) The gap between the spark probe and  
the ground clip should be  
approximately 1/8 inch. If the gap  
appears to be excessive or poor  
sparking is occurring then adjust.  
Terminals:  
1. Main Valve - 24VAC will be present on terminal  
#1 with the pilot sensing electrode sensing an  
adequate pilot fame. This output will remain  
present as long as the pilot flame remains  
adequate.  
2) Inspect the ceramic flame rod  
insulator for cracks or evidence of  
exposure to extreme heat, which can  
permit leakage to ground. If either of  
these conditions exist, then replace  
the pilot ignitor and re-test.  
2. Common (MV/PV).  
3. Pilot Valve - 24VAC will be present on terminal  
#3 at the instant an input voltage is supplied to  
the module. This voltage will remain present on  
terminal #3 providing an adequate pilot flame is  
established within 90 seconds. In the event that  
an adequate pilot flame is not established  
within 90 seconds this output voltage will drop  
out.  
3) Check the ignition cable for tightness  
or damaged insulation. If the ignition  
cable appears to be damaged, then  
replace it and re-test.  
4. Ground (burner).  
5. 24VAC Neutral (ground).  
6. 24VAC Input.  
2. Install the pilot ignitor and attach ignition cable.  
A. Turn the main power switch ON and verify  
the ignition control modules re-set switch  
is ON. Observe spark condition from  
ignitor.  
7. High Voltage to spark electrode (The pilot  
flame current is sensed by the Ignitor Module  
via the spark electrode high voltage wire and  
terminal #9).  
1) If a spark from ignitor is present and  
ignites the gas from the pilot and  
burner then the system is working  
properly.  
Spark Ignition Control Test  
1. If the ignition control module does not appear  
to be sparking to ignite gas, perform the  
following:  
Page 32 of 88  
VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
2) If a spark from ignitor is present but  
does not ignite gas before the ignition  
control module locks out, (90 sec.)  
there may not be enough gas in the  
line for ignition. Verify the gas supply  
and gas combination control valve  
are both on. Turn the ignition control  
modules re-set switch OFF then ON  
to reset the module. Sparking should  
then resume to ignite gas. The  
4. After the burner lights, compare the manometer  
pressure reading to the pressure chart near the  
end of this procedure.  
A. If other appliances are connected to the  
same gas line, turn them all ON and check  
manometer pressure reading again. If the  
pressure drops ½ inch water column or  
more, then the incoming pressure should  
be checked. then the gas supply needs to  
be checked by the gas line installer or the  
local gas company for adequate sizing.  
module may need reset several times  
before ignition takes place.  
B. If no other gas appliances are connected  
to the gas line or the pressure does not  
drop as described above but the manifold  
pressure still requires adjustment, proceed  
to step 5.  
3) If ignitor is still not sparking proceed  
to step 3.  
3. Check the ignition control module and  
transformer.  
A. Turn the ignition control modules re-set  
switch OFF then ON to eliminate a lockout  
condition.  
5. Remove the adjustment screw cap to access  
the pressure adjustment screw.  
B. Check for 24VAC output on the ignition  
control module transformer.  
1) If 24VAC is present between  
terminals 5 & 6 on the ignition control  
module but ignitor is not sparking,  
then replace ignition control module  
and re-test.  
2) If 24VAC is not present then ensure  
that transformer is receiving 120VAC  
input. If ignition control module  
transformer is receiving proper  
voltage, then replace ignition control  
module transformer and re-test.  
4. After making the necessary component  
adjustments or replacements, check for proper  
operation.  
6. After the burner lights, set the pressure as  
outlined below.  
GAS MANIFOLD PRESSURE  
ADJUSTMENT  
A. To increase pressure, turn the screw  
clockwise.  
B. To decrease pressure, turn the screw  
counterclockwise.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
NOTE: Accurate gas pressure adjustments can only  
be made with the gas ON and the burner lit.  
PRESSURE READINGS  
(INCHES W.C.)  
WARNING: SHUT OFF THE GAS SUPPLY  
BEFORE SERVICING THE UNIT.  
LINE  
GAS TYPE MANIFOLD  
1. Open the front cabinet doors and turn the gas  
combination control valve off.  
RECOMMENDED  
MIN  
MAX  
Natural  
4.0  
7.0  
5.0  
2. To measure the manifold pressure, remove the  
1/8 inch NPT plug (pressure tap) on the outlet  
side of the valve and attach a manometer.  
14  
Propane  
10.0  
11.0  
11.0  
3. Turn the gas combination control valve and the  
main power switch to ON.  
NOTE: If the incoming line pressure is less than the  
minimum stated, then the manifold pressure can not  
be set correctly.  
Page 33 of 88  
VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
7. Once the correct pressure has been set, turn  
HEATER CONTACTORS  
the power switch OFF, replace the adjustment  
screw cap and 1/8 inch NPT plug (pressure tap)  
on the outlet side of the valve.  
WARNING: DISCONNECT THE ELECTRICAL  
POWER TO THE MACHINE AT THE MAIN  
CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT  
BOX INDICATING THE CIRCUIT IS BEING  
SERVICED.  
8. Check for proper operation.  
DIRECT STEAM MODELS  
The contactor can be serviced by removing the  
cover of the contactor box.  
These models consist of a pressure regulator and  
gauge that run off a buildings potable steam supply.  
The regulator used will be of the adjustable type and  
should be set for a discharge pressure of 10 psi. The  
maximum input pressure to the regulator should be  
15 psi. Incoming power (120VAC) for the  
A noisy contactor (hum or chatter) is generally due  
to excessive dust or dirt on the armature pole faces  
or around the armature core preventing the magnet  
coil from pulling the armature into a completely  
sealed position. This can usually be corrected by  
blowing or wiping the pole faces clean. To inspect  
electrical contacts, remove cover at top of contactor  
by removing two screws which hold it in place.  
Replace contactor if the electrical contacts appear  
to be severely pitted or burned.  
compartment controls is supplied from a junction  
box in the base.  
REGENERATED STEAM  
(OLDER MODELS)  
HEATING ELEMENTS  
The steam coils on a regenerated type steamer are  
intended for use at a steam supply pressure of 15  
psi maximum. A pressure regulating valve is  
WARNING: THE FOLLOWING STEPS REQUIRE  
POWER TO BE APPLIED TO THE UNIT DURING  
THE TEST. USE EXTREME CAUTION AT ALL  
TIMES.  
available as optional equipment for steamers where  
a buildings steam supply pressure exceeds 15 psi.  
The regulator used will be of the adjustable type and  
should be set for a discharge pressure high enough  
for good steam generation. This pressure can be  
monitored by the supplied pressure gauge. The  
regulator should be set, only when steam is flowing  
(steam solenoid valve is open). If steam is heavy  
with condensate, install a ball float trap in the steam  
line before the pressure regulating valve.  
1. Measure the voltage at the heating element  
terminals and verify it against the data plate  
voltage.  
A. If voltage is incorrect, find the source of  
the problem.  
B. If voltage is correct, check current draw  
(amps) through the heating element lead  
wires. See table below for proper  
values.  
WARNING: SHUT OFF THE STEAM SUPPLY  
BEFORE SERVICING THE UNIT.  
To remove a steam coil, disconnect union in steam  
supply line to the coils and in the condensate  
discharge line from the coils. Remove header that  
supplies steam to coils by disconnecting union at  
each coil. In same way, remove coil condensate  
collection header. Remove four bolts clamping each  
coil flange in place and pull coil forward. Use a new  
flange gasket when replacing coil. The faces that  
mate with gasket must be clean.  
C. If current draw is correct then heating  
element is ok.  
D. If current draw is not correct then replace  
the element and proceed to step 3.  
NOTE: When replacing an element, always use a  
new gasket and ensure that the flange and tube  
surfaces which contact the gasket are clean. If  
removed element shows a pronounced scale  
build-up on its heating tubes, the other elements  
should be removed and mechanically cleaned to  
remove the scale. This will prolong their life. DO  
NOT immerse elements in a chemical solution to  
descale.  
Turn steamer power switch ON, allowing steam  
generation and, consequently, pressure to rise to  
normal operating level and then turn power switch  
OFF for a final purging of boiler and steam supply  
lines. Steamer is now ready for use.  
2. Check for proper operation.  
Page 34 of 88  
VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
AMPERAGE  
PER LINE  
RESISTANCE  
PER  
ELEMENT  
(OHMS)  
NUMBER  
OF  
ELEMENTS ELEMENT  
KW  
PER  
TOTAL  
KW  
VOLTAGE  
1 PH 3 PH  
208  
240  
480  
18  
18  
18  
2
2
2
9
9
9
87  
75  
50  
44  
22  
14.42  
19.20  
76.80  
*220/380  
240/415  
18  
2
9
25  
19.20  
208  
240  
480  
24  
24  
24  
2
2
2
12  
12  
12  
116  
100  
68  
58  
29  
10.82  
14.40  
57.60  
*220/380  
240/415  
24  
2
12  
34  
14.40  
208  
240  
480  
36  
36  
36  
4
4
4
9
9
9
100  
87  
14.42  
19.20  
76.80  
44  
*220/380  
240/415  
36  
4
9
50  
19.20  
208  
240  
480  
42  
48  
48  
4
4
4
10.5  
12  
117  
116  
58  
12.36  
14.40  
57.60  
12  
*220/380  
240/415  
48  
4
12  
67  
14.40  
NOTES:  
1. Values in the table are nominal. Tolerance is +/-10 %.  
2. Asterisk (*) indicates 3 phase/4wire.  
3. Each heater has three internal elements.  
Page 35 of 88  
VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
D. If the cooking cycle is started normally, but  
THERMAL SWITCH - PREVENT  
AND AUTOMATIC MODELS  
the red light and timer do not come on or  
an abnormal amount of time elapses  
before they come on, then the load  
compensator is set too high. Also, if the  
timer stops, the red light goes out, and the  
buzzer does not sound after the  
compartment has exhausted the steam or  
if the time is set as usual for the product  
and the product is overcooked or if the  
time is set as usual for the product and the  
product is overcooked.  
The load compensator is a thermal switch in a  
stainless steel housing that screws into a 3/8 NPT  
fitting (newer models) on the left side wall of the  
compartment. The switch contacts should close  
when the compartment temperature reaches 180 F,  
supplying power to the steam exhaust solenoid  
valve, pilot light and cooking timer motor.  
1. Newer Models  
E. If there is too short a time between starting  
and the red light coming on, or if it comes  
on immediately, the load compensator is  
set too low. Also, if the time is set as usual  
for the product and the product is  
undercooked.  
A. This switch is NON-ADJUSTABLE. Check  
to see if the switch is operating properly as  
described below. If the switch is suspected  
to be malfunctioning, replace it and check  
for proper operation.  
2. Older Models  
A. The switch can be adjusted by turning the  
slotted screw. Turn the screw clockwise to  
lower the closing temperature and  
counterclockwise to raise the closing  
temperature. Check the operation of the  
switch as described below. These models  
are ½ NPT.  
WATER LEVEL GAUGE  
ASSEMBLY  
1. Close the valve at the top and at the bottom of  
the gauge assembly.  
2. Unscrew the packing nuts at the top and bottom  
of the glass tube.  
The correct adjustment or verification of the load  
compensator can best be made by using a digital  
thermometer and thermocouple to sense the  
compartment temperature.  
3. Slide the glass tube upwards, until the bottom  
of the tube is clear of the fitting and lift it out.  
1. Position the thermocouple near the exposed  
bulb of the load compensator inside the  
compartment.  
4. Reinstall the tube and use new sealing  
washers. Do not over tighten the packing nuts,  
it could break the gauge glass.  
2. Close and seal the compartment. Pull the  
steam control arm handle forward, set the timer  
and turn the compartment power switch ON.  
5. Open the top and bottom valves fully.  
6. Check for proper operation.  
3. Monitor the thermocouple temperature, and  
adjust or verify (as applicable) the load  
compensator temperature.  
A. The red light of the compartment switch  
should light when the thermocouple reads  
185 ±7 F.  
B. After the cooking cycle ends and the  
compartment temperature lowers, the  
thermal switch should then re-open at  
165 ±7 °F.  
C. If the load compensator can not be  
adjusted correctly or the temperature is  
out side the allowable limits, then replace  
thermal switch and check for proper  
operation.  
Page 36 of 88  
VL SERIES STEAMER - SERVICE PROCEDURES AND ADJUSTMENTS  
Replace the packing nut and control arm bracket.  
STEAM GATE VALVE(S)  
Tighten the packing nut finger tight plus ½ turn and  
check for proper operation. If steam continues to  
leak, tighten the packing nut in additional ½ turn  
increments until it stops and re-check operation of  
the steam control arm.  
On all models, each cooking compartment has its  
own mechanical steam gate valve that supplies  
steam to the cooking compartment when the steam  
control arm handle is pulled forward. The Prevent  
models use a solenoid valve to exhaust steam from  
the compartment whereas the Automatic, Standard  
and Manual models use an additional steam gate  
valve to exhaust steam when the steam control arm  
handle is returned to the rear. These gate valves are  
a standard type and can be disassembled for  
cleaning and gasket replacement.  
NOTE: Do not over tighten packing glands, the  
linkage system must be free enough for the spring  
to return the steam control arm to the fully closed  
position.  
For other service to these valves, remove the stem  
assembly and cap at the top of the valve. Check the  
valve linkage for loose or binding parts.  
The steam gate valve linkage for these controls are  
simple and there function easily seen. The inlet and  
exhaust steam gate valves must be positioned so  
the inlet valve is open and the exhaust valve closed  
when the steam control arm handle is pulled forward  
and reverses when the control arm is released.  
If steam leaks are noticed around the packing nut  
and stem during cooking, tighten the packing nut  
until the steam leak ceases. Release steam control  
arm to ensure its automatic return. If arm does not  
return freely or steam is still leaking, then further  
inspection or adjustments are necessary. Turn the  
timer and compartment power switch OFF and  
blowdown the boiler. Remove the control arm  
bracket and packing nut from the stem and clean  
out the old string packing. The valve stems may  
then be re-packed using a string packing suitable for  
steam service.  
NOTE: In the event of an electrical component or a  
power failure, the steam control arm can be  
operated manually on automatic models.  
Page 37 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
ELECTRICAL OPERATION  
When the water level drops below the low level (LL)  
WATER LEVEL CONTROLS  
probe, power is removed from the inverse latching  
relay, the HL relay energizes through ILR-2 and HL  
contacts change state. The fill solenoid is energized  
through HL-3 to refill the boiler and the HL LED is lit.  
The HL relay and LED will toggle ON and OFF  
during a cooking cycle as needed.  
Solid State - Low level Cut-Off & Differential  
Control  
The steamer is equipped with three water level  
sensing probes (high, low and low level cut-off) and  
a single water level control board. The water level  
control board performs two functions:  
1. Provide low level cut-off protection to shut off  
the heat source in case the water level drops  
below the low level cut-off (LLCO) probe.  
2. Performs as a differential level control to  
maintain the water level between the low and  
high water level probes.  
The water level control (WLC) has input voltage  
(120VAC) across terminals 11 and 12 which powers  
the transformer. On one side of the transformer  
secondary, power is provided to the control by a  
series path through chassis ground (terminal 10).  
The other side of the transformer secondary  
(12VAC) supplies power to one side of the internal  
relays LLCO, HL and ILR. As water enters the  
boiler, it becomes part of the water level control’s  
circuit. When the water level in the boiler reaches a  
probe, that circuit is completed.  
The inverse latching relay of the board is de-  
energized, leaving the ILR-1 (N.O.) and ILR-2 (N.C.)  
contacts in their shelf state.  
When the main power switch is turned ON, power is  
supplied to the WLC board which energizes the high  
level (HL) relay and illuminates the HL relay LED.  
With the HL-3 contacts closed, the boiler fill  
solenoid is energized and water begins filling the  
boiler.  
When the water level reaches the low level cut-off  
(LLCO) probe, the LLCO relay is energized and  
illuminates the LLCO LED. With the LLCO-2  
contacts closed the heat source is then energized.  
The LLCO relay will remain energized and its LED  
will stay lit until the water level in the boiler drops  
below the LLCO probe.  
When the water level reaches the low level (LL)  
probe, power to terminal 2 on the WLC board is  
present but no switching occurs.  
After the water level reaches the high level (HL)  
probe, the inverse latching relay of the board is  
energized and locked through the low level probe  
(LL) and ILR-1 contacts. With ILR-2 contacts open,  
this de-energizes the HL relay and the HL LED goes  
out. With the HL-3 contacts open, the boiler fill  
solenoid is de-energized, stopping the flow of water  
into the boiler.  
Page 38 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
When the boiler stops filling, press the manual reset  
Solid State - Auxiliary Low Level Cut-Off  
button on the boiler control box. On CSD-1 models,  
this energizes the low water relay, turns off the low  
water light and energizes the heat source auxiliary  
control. On Cal-Code models, this closes and locks  
the manual reset switch contacts to energize the  
heat source auxiliary control.  
This control serves as a safety backup to the main  
water level control (WLC) board to meet Cal-Code  
and CSD-1 code requirements. The auxiliary control  
provides auxiliary low level cut-off protection to shut  
off the heat source in case the water level drops  
below the low level cut-off (LLCO) probe. A single  
LLCO probe is connected to the auxiliary control.  
The auxiliary water level control (WLC) has input  
voltage (120VAC) across terminals L1 and L2 to  
power the transformer primary. On one side of the  
transformer secondary, power is provided to the  
control by a series path through chassis ground. The  
other side of the transformer secondary (12VAC)  
supplies power to one side of the internal relay  
LLCO. As water enters the boiler, it becomes part of  
the auxiliary water level control’s circuit. When the  
water level in the boiler reaches the LLCO probe,  
the circuit is completed.  
When the main power switch is turned ON, power is  
supplied to the auxiliary WLC board but no  
switching occurs. On CSD-1 models, the low water  
level indicator light (amber) on the boiler control box  
comes on.  
When the water level reaches the low level cut-off  
(LLCO) probe, the LLCO relay is energized and  
illuminates the LLCO LED. With the LLCO-2  
contacts closed the auxiliary heating control is then  
energized. The LLCO relay will remain energized  
and its LED will stay lit until the water level in the  
boiler drops below the LLCO probe.  
Page 39 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
When the water level reaches the low level cut-off  
Electro Mechanical - Low level Cut-Off &  
Differential Control  
(LLCO) probe, the internal contactor coil on the low  
water level control is energized. With the contacts  
on terminals 7 & 8 now closed, the heat source is  
then energized. The internal contactor coil will  
remain energized until the water level in the boiler  
drops below the LLCO probe.  
The steamer is equipped with three water level  
sensing probes (high, low and low level cut-off), a  
differential level control (1G1GO) and a low level  
cut-off control (1D1DO). The low-level cut-off is an  
additional control that is identical to the differential  
level control but serves as the safety backup to shut  
off the heat source in case the water level drops  
below the low level cut-off (LLCO) probe. The  
differential level control maintains the water level  
between the low and high water level probes.  
When the water level reaches the low level (LL)  
probe, power to terminal 7 on the differential level  
control will be present but no switching occurs.  
After the water level reaches the high level (HL)  
probe, the differential control contactor coil is  
energized and the normally closed contacts on  
terminals 3 & 4 open, which de-energizes the boiler  
fill solenoid and stops the flow of water into the  
boiler. The internal contactor coil will have a locking  
path through contacts 7 & 8 to the low level probe to  
keep the coil energized after the water level drops  
below the high level probe.  
Each control is powered by input voltage (120VAC)  
on terminals 1 and 2 which also connect to the  
primary side of the internal transformer. The  
transformer secondary (300VAC) will provide power  
to the internal contactor coil through a series path  
going from one side of the secondary winding,  
through the contactor coil, through the water level  
control probe, through the water in the boiler and to  
the boiler for ground. The other side of the  
When the water level drops below the low level (LL)  
probe, the internal contactor coil is de-energized,  
returning contacts 3 & 4 back to their normally  
closed state and energizing the boiler fill solenoid to  
refill the boiler. The water level must then fill to the  
high level probe again, to energize the internal  
contactor coil. The differential control will toggle ON  
and OFF during a cooking cycle as needed.  
transformer secondary is attached to ground.  
When the main power switch is turned ON, both  
water level controls are energized. The boiler fill  
solenoid is then energized through the normally  
closed contacts (terminals 3 & 4) on the differential  
level control and water begins filling the boiler.  
Page 40 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Electro Mechanical - Auxiliary Low Level Cut-Off  
This control serves as a safety backup to the main low level cut-off (LLCO) control to meet Cal-Code  
requirements. The operation of the auxiliary control is identical to the main low level cut-off control but performs  
a single function: 1) Provide auxiliary low level cut-off protection to shut off the heat source in case the water  
level drops below the low level cut-off (LLCO) probe. A single LLCO probe identical to the LLCO probe on the  
main low level cut-off control is connected to the auxiliary control.  
The auxiliary control is powered by input voltage (120VAC) on terminals 1 and 2 which also connect to the  
primary side of the internal transformer. The transformer secondary winding (300 VAC) will provide power to the  
internal contactor coil through a series path going from one side of the secondary winding, through the contactor  
coil, through the water level control probe, through the water in the boiler and to the boiler for ground. The other  
side of the transformer secondary is attached to ground.  
When the main power switch is turned ON, the auxiliary low level control is energized but no switching occurs.  
When the water level reaches the low level cut-off (LLCO) probe, the internal contactor coil on the low level  
control is energized, closing the contacts on terminals 7 & 8. The internal contactor coil will remain energized  
until the water level in the boiler drops below the LLCO probe.  
When the boiler stops filling, press the manual reset button on the boiler control box. This closes and locks the  
manual reset switch contacts to energize the heat source auxiliary control.  
Page 41 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
NOTE: The high pressure indicator light will remain  
SEQUENCE OF OPERATION  
on and the safety circuit de-energized until boiler  
steam pressure is within operational limits (high limit  
pressure switch closed) and the manual reset button  
is pressed. The low water indicator light will remain  
on and the safety circuit de-energized until the water  
level in the boiler reaches the low level cut-off  
probes (minimum level) for the water level control,  
the auxiliary low level cut-off control and the manual  
reset switch is pressed. The gas burners will not  
light until these conditions are satisfied.  
GAS MODELS  
This sequence of operation is written for steamers  
with electronic ignition, solid state water level  
controls, CSD-1 (code) boiler controls option and  
with Prevent cooking compartment controls. Refer  
to schematic diagram numbers 3928 and 3929 for a  
boiler control schematic and 3962 for a schematic  
and wiring diagram on Prevent cooking  
D. Water level control (WLC) is powered.  
compartment controls.  
Initial Fill and Preheat  
1) High level (HL) relay is energized,  
HL-3 (N.O.) contacts close and HL  
LED lights up.  
1. Conditions.  
A. Power switch OFF.  
2) The inverse latching relay of the  
board remains de-energized, leaving  
the ILR-1 (N.O.) and ILR-2 (N.C.)  
contacts in their shelf state.  
B. Ignition module reset switch ON  
C. Cooking timers off.  
D. Compartment power switches OFF.  
E. Unit connected to correct voltage .  
E. Auxiliary low water level cut-off control is  
powered, LLCO-2 (N.O.) contacts remain  
open.  
1) L1 (HOT) to one side of the cooking  
compartment controls; to one side of  
the cold water condenser thermostat;  
to one side of the power ON/OFF  
switch.  
F. With the HL-3 and ILR-2 contacts closed,  
the fill solenoid is energized and water  
boiler begins filling.  
G. Blowdown solenoid valve is energized and  
closes.  
2) L2 (NEUTRAL) to one side of the  
cooking compartment controls; to one  
side of the cold water condenser  
(CWC) solenoid valve; to one side of  
the power ON/OFF switch.  
H. Ignition module begins sparking to light  
pilot after a 3 second delay.  
1) If pilot ignition is established (pilot lit)  
then a micro amp flame sense  
F. Unit properly grounded. (Boiler and water  
level control share a common ground)  
current is sent back to the ignition  
control module through the ignition  
cable. Sparking stops, pilot remains  
lit and is ready to ignite burners.  
G. Water supply valve on.  
H. Gas supply valve on.  
I.  
Gas combination control valve ON.  
2) If pilot ignition is not established after  
90 seconds, sparking stops and the  
ignition control module locks out  
power to the combination gas valve  
(pilot valve and main valve remain  
closed). The module remains locked  
out until the reset switch on the  
ignition control module box is  
J. Control (cycling) pressure switch closed.  
K. High limit pressure switch closed.  
L. Cold water condenser (CWC) thermostat  
open.  
M. Blowdown solenoid valve (drain) open and  
boiler empty.  
switched to OFF then ON to re-start  
the ignition trial cycle.  
N. Compartment doors open.  
2. Power switch turned ON. (located on boiler  
control box)  
NOTE: If the modules re-set switch is in the OFF  
position, no sparking will occur or if it’s turned OFF  
while idling or cooking, then pilot and burners will go  
out and not re-ignite upon call for heat by the cycling  
pressure switch.  
A. Power switch indicator light (red) comes  
on.  
B. Hi pressure indicator light (amber) comes  
on.  
C. Low water level indicator light (amber)  
comes on.  
Page 42 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
3. Water level reaches LLCO (low water level cut-  
C. Auxiliary gas solenoid valve is energized  
and opens to allow gas flow.  
D. As long as the ignition control module is  
sensing a pilot flame, the internal main  
valve (MV) contacts close (N.O.) on the  
ignition control module. The main gas  
valve is energized and gas begins flowing.  
off) probe for the water level control and to the  
auxiliary LLCO probe for the auxiliary low level  
cut-off control.  
A. Power to terminal 9 on the water level  
control.  
1) LLCO relay energizes, LLCO-2 (N.O.)  
contacts close and LED lights.  
E. Burners light and water in boiler begins to  
heat up.  
B. Power to terminal LLCO on the auxiliary  
low water level cut-off control.  
7. Boiler steam pressure reaches upper limit set  
point of 11 PSI. (Approximately 15 min.)  
1) LLCO relay energizes, LLCO-2 (N.O.)  
contacts close and LED lights.  
A. Cycling pressure switch opens, main gas  
solenoid valve de-energizes, gas flow  
shuts off and burners go out.  
NOTE: LLCO relays will remain energized  
and LLCO LED’S will remain lit until the  
water level drops below the LLCO probes  
or the power switch is turned OFF.  
B. As boiler heats up and builds pressure,  
some by-pass water/steam is produced  
which runs into the steam drain box. This  
causes the cold water condenser (CWC)  
solenoid to cycle, cooling the drain water.  
This solenoid is powered by the CWC  
thermostat.  
4. Water reaches LL (low level) probe.  
A. Power to terminal 2 on the water level  
control is present but no switching occurs.  
5. Water reaches HL (high level) probe.  
NOTE: Steam should not be seen entering a  
compartment until the manual steam control arm is  
pulled forward and locked.  
8. Boiler steam pressure drops below lower limit  
set point of 9 PSI and the cycling pressure  
switch closes.  
A. Power to terminal 6 on water level control.  
1) The inverse latching relay of the  
board is energized, changing the  
state of ILR-1 (N.O.) and ILR-2 (N.C.)  
contacts. The inverse latching relay  
will remain energized through the  
alternate latching path of ILR-1  
contacts until the water level recedes  
below the low level probe.  
A. Boiler steam pressure is maintained by the  
cycling of the pressure switch between the  
upper and lower set point limits. The  
cycling pressure switch continues to  
energize and de-energize the main gas  
solenoid valve starting and stopping the  
flow of gas, which in turn, cycles the  
burners on and off. This sequence  
2) With ILR-2 contacts open, HL relay is  
de-energized, HL-3 (N.O.) contacts  
open and HL LED goes out.  
3) Water fill solenoid is de-energized.  
(boiler fill time approx. 11 min.)  
continues until one of the following occurs:  
1) Boiler pressurizes to 15 PSI, causing  
the high limit pressure switch to open.  
At that time, the auxiliary gas valve  
de-energizes, shutting off the gas  
flow to the burners and the high limit  
failure light will come on. This light  
will stay lit until the pressure drops  
below the lower limit set point of 6  
PSI and the manual re-set switch is  
pressed.  
6. Manual re-set switch is pressed, energizing the  
coils on the high limit and low water relays.  
A. Contacts 1 & 9 on the high pressure relay  
change state and lock from N.C. to N.O.  
and turn off the high pressure indicator  
light. Concurrently, Contacts 1 & 9 on the  
low water relay change state and lock from  
N.C. to N.O. and turn off the low water  
indicator light.  
2) Boiler water level drops below the  
LLCO probes for the water level and  
the auxiliary low level cut-off controls  
which then de-energizes the LLCO  
relays, changing the contact state of  
LLCO-2 (N.O.) back to open. This de-  
energizes the main and auxiliary gas  
solenoid valves. The gas solenoid  
valves will remain off and the low  
water level light will come on and stay  
lit until the water level rises above the  
LLCO probes and the manual re-set  
switch is pressed.  
B. Contacts 5 & 9 on the high pressure relay  
change state and lock from N.O. to N.C.,  
supplying power (NEUTRAL) to one side  
of the auxiliary gas solenoid valve.  
Concurrently, Contacts 5 & 9 on the low  
water relay change state and lock from  
N.O. to N.C., supplying power (L1) to the  
other side of the auxiliary gas solenoid  
valve.  
NOTE: For both relays to energize, the high  
pressure switch must be closed and the water level  
in the boiler must be above the low level cut-off  
probes in order for LLCO-2 (N.O.) contacts to close.  
Page 43 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
A. Micro switch SW1 contacts change state  
Cook Cycle  
from N.O. back to N.C. (normal starting  
position)..  
1. A Cook cycle should not be started, until the  
initial fill and preheat is completed, in order for  
the boiler steam pressure to be within  
operational limits.  
4. Cooking timer is manually turned off.  
5. Compartment power switch is turned OFF,  
buzzer is de-energized and power is removed  
from the common side of micro switch SW1.  
A. Insert product into steamer.  
B. Compartment door is closed and screw  
handle tightened down.  
6. Steamer reverts to preheat cycle until:  
A. A cooking cycle is started. i.e.  
compartment door is closed and screw  
handle tightened down, time is dialed into  
timer (past 5 minutes) and the  
C. Compartment steam control arm is pulled  
forward and latches, allowing steam to  
enter compartment.  
NOTE: Cool air and condensate exit through the  
steam exhaust solenoid valve (N.O.) until  
compartment temperature reaches 180°F.  
compartment power switch is turned ON.  
B. Water level drops below low level cut-off  
probe.  
D. Time is dialed on timer (past 5 minutes).  
C. Power switch is turned OFF.  
1) Micro switch SW1 contacts change  
state from N.C. to N.O.  
NOTE: Burners will re-light after the boiler pressure  
drops below the low pressure set point limit (9 psi)  
and will stay on until the high pressure set point (11  
psi) is reached. As long as steam pressure is within  
limits, even while cooking, burners can go off. The  
boiler is able to re-pressurize to the upper set point  
limit even with all compartments in cook mode.  
2) Micro switch SW2 contacts also  
change state from N.C. to N.O.  
E. Compartment power switch is turned ON.  
1) L1 (HOT) to one side of the thermal  
switch.  
NOTE: The cold water condenser thermostat  
remains closed and cold water condenser solenoid  
stays energized while cooking. If main water is shut  
off after boiler fill, then no cold water is present to  
condense steam/hot water and steam vapors exit  
the floor drain.  
NOTE: L2 (NEUTRAL) is connected to the other  
side of the buzzer, steam exhaust solenoid valve,  
trip solenoid, pilot light and timer motor.  
F. Once compartment temperature reaches  
approximately 180°F thermal switch  
closes and supplies power L1 (HOT) to:  
Water Refill (After Initial Fill)  
1) Steam exhaust solenoid valve (N.O.)  
energized and closes.  
1. Water level drops below low level probe (LL).  
A. Power is removed from terminal 2 on the  
water level control .  
NOTE: Even though steam exhaust solenoid valve  
is closed, a small opening exists in the “guillotine”  
blade of the valve to allow “limited free venting” of  
condensate during a cook cycle.  
1) The inverse latching relay is de-  
energized, returning ILR-1 (N.O.) and  
ILR-2 (N.C.) contacts back to their  
original state.  
2) Pilot light (red) comes on indicating  
timed cooking at 180°F has started.  
B. HL relay is energized.  
1) Contacts HL-3 close.  
2) HL LED comes on.  
3) Timer motor energized  
2. Cooking Timer times down to approximately  
one minute before zero.  
3) Fill solenoid is energized and water  
flows into tank.  
A. Micro switch SW2 contacts change state  
from N.O. back to N.C. (normal starting  
position).  
2. Water reaches LL (low level) probe.  
1) Steam exhaust solenoid valve is de-  
energized and opens to exhaust  
steam and pressure from the  
compartment.  
A. Power to terminal 2 on the water level  
control is present but no switching occurs.  
3. Water reaches high level probe.  
A. The inverse latching relay of the water  
level control is energized, changing the  
state of ILR-1 (N.O.) and ILR-2 (N.C.)  
contacts.  
2) Steam trip solenoid is energized and  
unlatches steam control arm allowing  
it to return to the rear. Steam supply  
the compartment is shut off.  
B. HL relay is de-energized.  
3. Cooking timer reaches zero.  
Page 44 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
2) L2 to the common terminal on the  
1) HL-3 opens.  
blowdown timer relay; to pin 4 on the  
boiler ON/OFF switch; to one side of  
the manual reset switch; to one side  
of the auxiliary switch(s) mounted on  
the side of the auxiliary contactor(s);  
to the compartment controls.  
2) Fill solenoid de-energized and water  
stops flowing into tank.  
3) HL LED goes out.  
4. The water refill cycle will occur whenever the  
water level is below the low level probe and will  
not affect the operation of either the preheat or  
cook cycle.  
F. Unit properly grounded. (Boiler and water  
level control share a common ground)  
G. Water supply valve on.  
Boiler Blowdown/drain  
H. Control (cycling) pressure switch closed.  
1. Main power switch turned OFF.  
A. Boiler blowdown sequence starts.  
I.  
High limit pressure switch closed.  
J. Cold water condenser (CWC) thermostat  
open.  
B. The blowdown solenoid valve (N.O.) is de-  
energized and valve opens to drain the  
boiler.  
K. Blowdown solenoid valve (drain) closed  
and boiler empty.  
C. Power is removed from all components  
except cold water condenser (CWC)  
L. Compartment doors open.  
thermostat and solenoid valve. The CWC  
thermostat cycles as necessary to lower  
the discharge temperature of the water  
and condense steam going into the drain.  
2. Power switch turned ON. (located on boiler  
control box)  
A. Power to terminal 2 on the differential  
water level control then jumpers connect  
to terminal 2 on both the low level cut-off  
and auxiliary low level cut-off water level  
controls.  
ELECTRIC MODELS  
This sequence of operation is written for steamers  
with electro mechanical water level controls, Cal-  
Code boiler controls option and with Prevent  
cooking compartment controls. Refer to schematic  
diagram number 3941 for a boiler control schematic  
and 3962 for a schematic and wiring diagram on  
Prevent cooking compartment controls.  
B. Power switch indicator light (red) comes  
on.  
C. Boiler fill solenoid valve is energized and  
boiler begins to fill.  
INITIAL FILL AND PREHEAT  
1. Conditions.  
NOTE: The safety circuit remains de-energized  
until the water level in the boiler reaches the  
low level cut-off probe (minimum level) for the  
auxiliary low level cut-off control and the  
manual reset switch is pressed. Also, until the  
water level in the boiler reaches the low level  
cut-off probe (minimum level) for the low level  
cut-off control, the low level cut-off control  
remains de-energized. The heating elements  
will not come on until the manual rest switch is  
pressed these conditions are satisfied.  
A. Power switch OFF.  
B. Manual reset switch OFF.  
C. Cooking timers off.  
D. Compartment power switches OFF.  
E. Unit connected to correct voltage supply.  
1) L1 to one side of the boiler fill  
solenoid valve; to one side of the  
main and auxiliary contactor(s); to  
one side of the power on light (red);  
to one side of the heat on light  
(amber); to one side of the timer  
motor; to one side of the cold water  
condenser solenoid valve; to one side  
of the blowdown solenoid valve; to  
terminal 1 on the auxiliary low level  
control then jumpers connect L1 to  
terminal 1 on the differential and low  
level controls; to the compartment  
controls.  
3. Water level reaches LLCO (low water level cut-  
off) probe for the low level cut-off control and to  
the auxiliary LLCO probe for the auxiliary low  
level cut-off control.  
A. Power to terminal 10 on the low level cut-  
off and on the auxiliary low level cut-off  
control is present. The internal contactor  
coil on the water level controls are then  
energized.  
1) The normally open contacts on  
terminals 7 and 8 for both the main  
and auxiliary low level cut-off controls  
close.  
2) The main heater contactor(s) are then  
energized.  
Page 45 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
1) Boiler pressurizes to 15 PSI, causing  
NOTE: Power the internal contactors on  
the low level cut-off and auxiliary low level  
cut-off will remain, until the water level  
drops below the LLCO probes or the power  
switch is turned OFF.  
the high limit pressure switch to open.  
At that time, the auxiliary heating  
element contactor(s) are de-  
energized, shutting off power to the  
heating elements. The pressure  
switch will remain open until the  
pressure drops below the lower limit  
set point of 6 PSI. Boiler water level  
drops below the LLCO (low water  
level cut-off) probes for the low level  
cut-off and the auxiliary low level cut-  
off controls, de-energizing the internal  
contactor on both controls. This de-  
energizes the main and auxiliary  
heater contactors, shutting off power  
to the heating elements. The heating  
elements will remain off until the  
water level rises above the LLCO  
probes and the manual re-set switch  
is pressed.  
4. Manual reset switch is pressed (momentary).  
A. The auxiliary heater contactor is energized  
supplying power to the heating elements  
and the heat light (amber) comes on.  
1) Water in boiler heats up.  
B. Internal relay on manual reset switch is  
energized.  
1) Normally open contacts close and  
lock to provide power to the auxiliary  
heater contactor and the heat light  
after the reset switch is released.  
5. Water reaches LL (low level) probe.  
A. Power to terminal 7 on the differential  
level control is present but no switching  
occurs.  
COOK CYCLE  
1. A Cook cycle should not be started, until the  
initial fill and preheat is completed, in order for  
the boiler steam pressure to be within  
operational limits.  
6. Water reaches HL (high level) probe.  
A. Power to terminal 10 on the differential  
level control.  
A. Insert product into steamer.  
1) The internal contactor coil on the  
differential level controls is energized.  
B. Compartment door is closed and screw  
handle tightened down.  
a. The normally closed contacts on  
terminals 3 and 4 open, de-  
C. Compartment steam control arm is pulled  
forward and latches, allowing steam to  
enter compartment.  
energizing the boiler fill solenoid  
and the boiler stops filling.  
NOTE: The internal contactor coil has a  
locking path through contacts on terminals  
7 & 8 to the low level probe to keep the  
coil energized after the water level drops  
below the high level probe.  
NOTE: Cool air and condensate exit through  
the steam exhaust solenoid valve (N.O.) under  
“Full Free Venting” until the compartment  
temperature reaches 180°F. When the solenoid  
valve energizes and closes, condensate will  
continue to exhaust through a small opening  
the valve under “Limited Free Venting” until the  
solenoid valve de-energizes and re-opens, one  
minute before the end of a cook cycle.  
7. Boiler steam pressure reaches upper limit set  
point of 11 PSI. (Approximately 15 min.)  
A. Cycling pressure switch opens, heater  
contactor(s) de-energize and power to the  
heating elements is removed.  
D. Time is dialed on timer (past 5 minutes).  
1) Micro switch SW1 contacts change  
state from N.C. to N.O.  
NOTE: Steam should not be seen entering a  
compartment until the manual steam control  
arm is pulled forward and locked.  
2) Micro switch SW2 contacts also  
change state from N.C. to N.O.  
8. Boiler steam pressure drops below lower limit  
set point of 9 PSI and the cycling pressure  
switch closes.  
E. Compartment power switch is turned ON.  
1) L1 (HOT) to one side of the thermal  
switch.  
A. Boiler steam pressure is maintained by the  
cycling of the pressure switch between the  
upper and lower set point limits. The  
cycling pressure switch continues to  
energize and de-energize the heating  
element contactor(s), which in turn, cycles  
the heating elements on and off. This  
sequence continues until one of the  
following occurs:  
NOTE: L2 (NEUTRAL) is connected to the  
other side of the buzzer, steam exhaust  
solenoid valve, trip solenoid, pilot light and  
timer motor.  
Page 46 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
F. Once compartment temperature reaches  
WATER REFILL (AFTER INITIAL FILL)  
approximately 180°F thermal switch  
closes and supplies power L1 (HOT) to:  
1. Water level drops below low level probe (LL).  
A. Power is removed from terminal 7 on the  
differential water level control.  
1) Steam exhaust solenoid valve (N.O.)  
energized and closes.  
1) The internal contactor coil is de-  
energized returning contacts 3 and 4  
back to there original state and  
energizing the boiler fill solenoid to  
refill the boiler.  
NOTE: Even though steam exhaust  
solenoid valve is closed, a small opening  
exists in the “guillotine” blade of the valve  
to allow “limited free venting” of  
condensate during a cook cycle.  
2. Water reaches LL (low level) probe.  
2) Pilot light (red) comes on indicating  
timed cooking at 180°F has started.  
A. Power to terminal 2 on the water level  
control is present but no switching occurs.  
3) Timer motor energized  
3. Water reaches HL (high level) probe.  
2. Cooking Timer times down to approximately  
one minute before zero.  
A. Power to terminal 10 on the differential  
level control.  
A. Micro switch SW2 contacts change state  
from N.O. back to N.C. (normal starting  
position).  
1) The internal contactor coil on the  
differential level controls is energized.  
1) Steam exhaust solenoid valve is de-  
energized and opens to exhaust  
steam and pressure from the  
compartment.  
a. The normally closed contacts on  
terminals 3 and 4 open, de-  
energizing the boiler fill solenoid  
and the boiler stops filling.  
2) Steam control solenoid (trip) is  
energized and unlatches steam  
control arm allowing it to return to the  
rear. Steam supply the compartment  
is shut off.  
NOTE: The internal contactor coil has a  
locking path through contacts on terminals  
7 & 8 to the low level probe to keep the  
coil energized after the water level drops  
below the high level probe.  
3. Cooking timer reaches zero.  
4. The water refill cycle will occur whenever the  
water level is below the low level probe and will  
not affect the operation of either the preheat or  
cook cycle.  
A. Micro switch SW1 contacts change state  
from N.O. back to N.C. (normal starting  
position).  
BOILER BLOWDOWN/DRAIN  
B. Buzzer is energized.  
1. Main power switch turned OFF.  
4. Cooking timer is manually turned off.  
A. Power switch indicator light (red) goes out  
and power is removed form all boiler  
controls except the blowdown timer.  
5. Compartment power switch is turned OFF,  
buzzer is de-energized and power is removed  
from the common side of micro switch SW1.  
2. Blowdown timer switch is pressed.  
6. Steamer reverts to preheat cycle until:  
A. The normally open timer contacts close,  
energizing the blowdown solenoid valve  
and the cold water condenser valve.  
A. A cooking cycle is started. i.e.  
compartment door is closed and screw  
handle tightened down, time is dialed into  
timer (past 5 minutes) and the  
B. Boiler begins blowing down and draining  
until timer “times out” after approximately  
4 minutes.  
compartment power switch is turned ON.  
B. Water level drops below low level cut-off  
probes.  
C. Timer contacts re-open and power is then  
removed from the blowdown solenoid  
C. Power switch is turned OFF.  
valve and the cold water condenser valve.  
NOTE: Heating elements will come back on, after  
the boiler pressure drops below the low pressure set  
point limit (9 psi) and will stay on until the high  
pressure set point (11 psi) is reached. As long as  
steam pressure is within limits, even while cooking,  
heating elements can go off. The boiler is able to re-  
pressurize to the upper set point limit even with all  
compartments in cook mode.  
Page 47 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
PAGE PURPOSELY LEFT BLANK  
Page 48 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
SCHEMATICS, GAS STEAMERS, BOILER CONTROLS  
VL2G AND VL3G - PREVENT, AUTOMATIC, STANDARD AND MANUAL  
Manual Ignition, Standard Controls  
Page 49 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Electronic Ignition, Standard Controls  
Page 50 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Manual Ignition, CSD-1 Code Controls  
Page 51 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Electronic Ignition, CSD-1 Code Controls  
Page 52 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Page 53 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
WIRING DIAGRAMS, GAS STEAMERS, BOILER CONTROLS  
VL2G AND VL3G - PREVENT, AUTOMATIC, STANDARD AND MANUAL  
Manual Ignition, Standard Controls  
Page 54 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Page 55 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Electronic Ignition, Standard Controls  
Page 56 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Page 57 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Manual Ignition, CSD-1 Code Controls  
Page 58 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Page 59 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Electronic Ignition, CSD-1 Code Controls  
Page 60 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Page 61 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
SCHEMATICS, ELECTRIC STEAMERS, BOILER CONTROLS  
VL2E AND VL3E - PREVENT, AUTOMATIC, STANDARD AND MANUAL  
Auto Blowdown, Standard Controls  
Page 62 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Auto Blowdown, Cal-Code Controls  
Page 63 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
WIRING DIAGRAMS, ELECTRIC STEAMERS, BOILER CONTROLS  
VL2E AND VL3E - PREVENT, AUTOMATIC, STANDARD AND MANUAL  
Auto Blowdown, Standard Controls (contactor - 1 std.)  
Page 64 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Page 65 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Auto Blowdown, Standard Controls (contactors - 2 std.)  
Page 66 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Page 67 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Manual Blowdown, Cal-Code Controls (contactors - 1 std. 1 aux.)  
Page 68 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Page 69 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Auto Blowdown, Cal-Code Controls ( contactors - 1 std. 1 aux.)  
Page 70 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Page 71 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Auto Blowdown, Cal-Code Controls (contactors - 2 std. 2 aux.)  
Page 72 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Page 73 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Manual Blowdown, Cal-Code Controls (contactors - 2 std. 2 aux.)  
Page 74 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Page 75 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
WIRING DIAGRAMS, ELECTRIC HEATER CIRCUITS  
VL2E AND VL3E - PREVENT, AUTOMATIC, STANDARD AND MANUAL  
Standard and Cal-Code/CSD-1 Controls  
Page 76 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
SCHEMATIC AND WIRING DIAGRAMS, DIRECT STEAMERS, CABINET BASE  
VL2D AND VL3D - PREVENT, AUTOMATIC, STANDARD AND MANUAL  
See “SCHEMATIC AND WIRING DIAGRAMS - COMPARTMENT CONTROLS”  
Page 77 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
WIRING DIAGRAMS, REGENERATED STEAMERS, BOILER CONTROLS  
VL2R AND VL3R - PREVENT, AUTOMATIC, STANDARD AND MANUAL  
Manual Blowdown (Older Models)  
Page 78 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Auto Blowdown (Older Models)  
Page 79 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
SCHEMATIC AND WIRING DIAGRAMS - COMPARTMENT CONTROLS  
Prevent  
Page 80 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Automatic  
Page 81 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Standard  
Page 82 of 88  
VL SERIES STEAMER - ELECTRICAL OPERATION  
Manual  
NO ELECTRICAL COMPONENTS ARE USED WITH THE MANUAL COMPARTMENT CONTROLS OPTION.  
THE CONTROLS CONSIST OF A MANUAL COOKING TIMER AND MANUAL STEAM CONTROL ARM TO  
CLOSE AND OPEN THE STEAM GATE VALVES.  
Page 83 of 88  
VL SERIES STEAMER - TROUBLESHOOTING  
TROUBLESHOOTING  
ALL MODELS  
WARNING: CERTAIN PROCEDURES IN THIS SECTION REQUIRE ELECTRICAL TESTS OR  
MEASUREMENTS WHILE POWER IS APPLIED TO THE MACHINE. EXERCISE EXTREME CAUTION AT ALL  
TIMES. IF TEST POINTS ARE NOT EASILY ACCESSIBLE, DISCONNECT POWER, ATTACH TEST  
EQUIPMENT AND REAPPLY POWER TO TEST.  
SYMPTOM  
POSSIBLE CAUSES  
Compartment leaks water around door.  
1. Drain screen clogged.  
2. Drain line obstructed or not to an open gap drain.  
3. Steamer not level.  
4. Excessive cooking compartment pressures.  
A. On models equipped with the compartment pressure  
regulating valve, verify the compartment pressure is 6  
psi during cooking. If pressure is higher then adjust the  
pressure regulating valve and re-check. See  
COMPARTMENT PRESSURE ADJUSTMENT” in  
“SERVICE PROCEDURES AND ADJUSTMENTS”.  
B. On models with out the compartment pressure  
regulating valve, verify the compartment pressure is 6  
psi during cooking. If pressure is higher then adjust the  
cycling pressure switch and re-check. See “CYCLING  
AND HIGH LIMIT PRESSURE SWITCHES (GAS AND  
ELECTRIC MODELS)” in “SERVICE PROCEDURES  
AND ADJUSTMENTS”.  
Cold water condenser not operating  
properly.  
1. Water supply not on.  
2. Plugged spray nozzle.  
3. Cold water condenser solenoid inoperative or plugged.  
4. Cold water condenser thermostat malfunction or needs  
adjustment.  
5. No power to cold water condenser solenoid.  
1. Compartment door not properly sealed.  
2. Worn or damaged gasket.  
Steam leaks around door.  
3. Drain line obstructed or not to an open drain.  
Steam generated inside compartment  
when timer or compartment power switch  
is OFF.  
1. Steam gate valve not fully closing (clogged, dirty or  
malfunctioning). See “STEAM GATE VALVE” in “SERVICE  
PROCEDURES”.  
Heat coming on without water in boiler  
(Dry firing).  
1. Lime scale (moist) on LLCO water level probe or probe  
damaged (shorted to ground).  
2. Retention of water in probe canister assembly.  
3. Water level control malfunction.  
Pressure relief valve opening or leaking.  
1. Pressure relief valve malfunction.  
2. Cycling pressure switch set to high. See “CYCLING AND HI  
LIMIT PRESSURE SWITCHES (GAS AND ELECTRIC  
MODELS)” in “SERVICE PROCEDURES”.  
Page 84 of 88  
VL SERIES STEAMER - TROUBLESHOOTING  
SYMPTOM  
POSSIBLE CAUSES  
Boiler base will not heat or build  
pressure.  
1. Check incoming voltage.  
2. Boiler not filled - check fill solenoid for power, clogging or  
malfunction.  
3. Water Level Control malfunction. HL-3 relay not energizing  
or contacts not closing to power boiler fill solenoid.  
4. Water too “pure” for probes to properly conduct electricity.  
5. Contactor malfunction (electric only).  
6. Heating element inoperative (electric only).  
7. Cycling pressure switch open or set too high. Steamer is  
cycling on high limit.  
8. High limit thermostat open.  
9. Problem with auto blowdown timer (older models).  
10. Power switch malfunction.  
11. Pressure reducing valve malfunction or needs cleaned  
(direct or regenerated models only).  
12. Low or no steam supply to steamer (direct or regenerated  
models only).  
Steam output low or slow cooking.  
1. Steam gate valve not fully opening or blocked.  
2. Cycling pressure switch malfunction or needs adjustment.  
3. Steam header line (supply) blockage.  
4. Heavy amount of condensate in the pressure controls steam  
supply line.  
5. Pressure relief valve leaking.  
6. Steam supply lines leaking.  
Boiler leaks water.  
1. Loose water, steam or drain line connections (top or base).  
2. Boiler hand hole gasket not sealing.  
3. Leak at gauge glass.  
Boiler fill solenoid cycling to frequently.  
Boiler water level too high.  
1. LL probe lime scaled over (dry) or damaged and not sensing  
water.  
2. Water level control malfunction.  
1. Fill solenoid does not shut off.  
2. High level probe lime scaled over (dry) or damaged and is  
not sensing water (open circuit).  
3. Water level control malfunction. HL-3 relay not de-energizing  
or contacts not opening.  
Boiler does not fill or slow to fill.  
1. Water supply not on or pressure too low.  
2. Line strainer clogged.  
3. Fill solenoid not malfunctioning or plugged.  
4. A High pressure pocket in the supply line to the boiler causes  
the fill solenoid valve not to open. See ”BOILER NOT  
FILLING WITH WATER” in “SERVICE PROCEDURES AND  
ADJUSTMENTS”.  
5. Water level control malfunction. HL-3 relay not energizing or  
contacts not closing to power boiler fill solenoid.  
Page 85 of 88  
VL SERIES STEAMER - TROUBLESHOOTING  
SYMPTOM  
POSSIBLE CAUSES  
Cooking timer motor does not run.  
1. Timer not getting power.  
2. Timer motor inoperative.  
1. Cooking timer malfunction.  
2. Buzzer malfunction.  
Buzzer not operating.  
Compartment red light and timer do not  
come on; excessive time elapses before  
they come on; timer stops, the red light  
goes out, and the buzzer does not sound  
after compartment exhausts steam; time  
is set as usual for the product and the  
product is overcooked.  
1. Thermal switch (load compensator) is set too high.  
Short a time between starting and the red 1. Thermal switch (load compensator) is set too low.  
light coming on; red light comes on  
immediately; time is set as usual for the  
product and the product is undercooked.  
Cooking Compartment Controls  
inoperative  
1. Ensure that voltage is reaching control circuit through  
compartment power switch when turned ON.  
2. On electric heat models with a transformer, check step down  
transformer (located in the contactor box) for proper  
operation.  
3. Check cooking timer function and contact position. See  
“SCHEMATIC AND WIRING DIAGRAMS -  
COMPARTMENT CONTROLS” under “ELECTRICAL  
OPERATION”.  
4. Check that timer motor operates when connected to power. If  
a problem is found in timer, replace it, do not take timer  
apart.  
5. On prevent and automatic models check the load  
compensator for malfunction.  
6. Check wiring for damaged insulation. (no short circuit)  
7. Check that all connections and terminals are securely  
fastened. (no open circuits)  
8. Check that all connections are made according to  
compartment control wiring diagram.  
Cooking Compartment not venting at end 1. Steam control arm not returning after unlatching (automatic,  
of cook cycle (Prevent models) or when  
manual steam control arm is released.  
standard and manual models).  
A. Broken or missing return spring.  
B. Packing nut on steam gate valve to tight.  
C. Steam control (trip) solenoid malfunction (prevent and  
automatic models).  
2. Steam exhaust solenoid valve malfunctioning (prevent  
models).  
Page 86 of 88  
VL SERIES STEAMER - TROUBLESHOOTING  
GAS MODELS ONLY  
SYMPTOM  
Burner won’t light.  
POSSIBLE CAUSES  
1. Gas not on.  
2. Ignition control module reset switch in the OFF position or  
malfunctioning.  
3. Ignition module not receiving power. Check ignition module  
transformer for 24VAC output to module on automatic  
ignition systems.  
4. Steamer not properly grounded and/or polarity of incoming  
power is incorrect on automatic ignition systems.  
5. Low incoming gas pressure. See “GAS MANIFOLD  
PRESSURE ADJUSTMENT” in “SERVICE  
PROCEDURES”.  
6. Ignition module malfunction.  
7. Gas combination control valve malfunction.  
8. Boiler not filling. Check fill solenoid for power, clogging or  
malfunction.  
9. Water level control malfunction. HL-3 relay not energizing  
or contacts not closing to power boiler fill solenoid.  
10. Water too ”pure” for probes to properly conduct electricity.  
11. High limit thermostat open (if equipped).  
12. High limit pressure switch open.  
13. Cycling pressure switch open or set too high. Steamer is  
cycling on high limit. See “CYCLING AND HI LIMIT  
PRESSURE SWITCHES (GAS AND ELECTRIC MODELS)  
in SERVICE PROCEDURES”.  
Burner won’t stay lit.  
1. Gas pressure low. See “GAS MANIFOLD PRESSURE  
ADJUSTMENT” in “SERVICE PROCEDURES”.  
2. Check gas orifice for obstruction.  
3. Ignition module malfunction.  
Page 87 of 88  
VL SERIES STEAMER - TROUBLESHOOTING  
POSSIBLE CAUSES  
SYMPTOM  
Pilot not lit or goes out.  
1. Gas not on.  
2. Pilot going out due to drafts, excess steam from drain or  
steamer not level. Improper venting can direct the pilot  
flame away from thermopile or flame sensor.  
3. Low incoming gas pressure. See “GAS MANIFOLD  
PRESSURE ADJUSTMENT” in “SERVICE  
PROCEDURES”.  
4. Pilot not adjusted correctly. See “PILOT AND  
THERMOCOUPLE ASSEMBLY (GAS MODELS)” in  
“SERVICE PROCEDURES AND ADJUSTMENTS”.  
5. Check thermopile millivolts. See “PILOT AND  
THERMOCOUPLE ASSEMBLY (GAS MODELS)” in  
“SERVICE PROCEDURES AND ADJUSTMENTS”.  
6. Burners ignite too violently. Check gas pressure to the  
steamer. See “GAS MANIFOLD PRESSURE  
ADJUSTMENT” in “SERVICE PROCEDURES”.  
7. If auto ignition and no sparking - ignition module  
malfunction.  
8. Wrong pilot assembly used.  
Spark Ignitor not sparking.  
1. Poor ground between pilot bracket and burner.  
2. Loose, broken or damaged lead wires (including ground)  
from ignition module to ignitor.  
3. Ignitor boot on ignition cable loose, damaged or missing  
causing excessive ignition voltage leakage.  
4. Ceramic flame rod insulator on ignitor cracked or damaged  
from extreme heat.  
5. Incorrect spark gap setting. See “AUTOMATIC IGNITION  
SYSTEMS (GAS MODELS)” in “SERVICE  
PROCEDURES”.  
6. Ignition module not receiving power. Check to ensure the  
ignition control module reset switch is ON.  
7. Ignition module malfunction.  
Form 24650 (May 1999)  
Printed in U.S.A.  

Toshiba TEC EO 11024 User Manual
Sub Zero WS 30 User Manual
Sony TC WR681 User Manual
Sony MSA512A PINK User Manual
Sony DCR DVD404E User Manual
Sony Camcorder DSR PD170 User Manual
Shure Car Amplifier RK100PKW User Manual
Sharp Viewcam VL NZ10S User Manual
Sanyo PID 42AE1 User Manual
Rockford Fosgate RFX9210 User Manual