CatalogNo.:2100.50W
Effective: 10-01-04
Replaces: 04-01-04
INSTALLATION
ANDOPERATING
INSTRUCTIONS
RaythermTM
Type H
RESIDENTIALBOILERS
Models
0042B, 0066B,0090B
0135B, 0180B
FOR YOUR SAFETY
Donotstoreorusegasolineorotherflammablevaporsandliquidsorothercombustiblematerials
in the vicinity of this or any other appliance. To do so may result in an explosion or fire.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause
propertydamage, personalinjuryorlossoflife. Refertotheuser'sinformationmanualprovided
withthisboiler. Installationandservicemustbeperformedbyaqualifiedinstaller,serviceagency
or the gas supplier.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
*Do not try to light any appliance.
*Do not touch any electrical switch; do not use any phone in your building.
*Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's
instructions.
*If you cannot reach your gas supplier, call the fire department.
THIS MANUAL SHOULD BE MAINTAINED IN LEGIBLE CONDI-
TION AND KEPT ADJACENT TO THE BOILER OR IN A SAFE
PLACE FOR FUTURE REFERENCE.
P/N 240488
RECEIVING EQUIPMENT
Followtheinstallationinstructionsfurnishedwiththevent
damper package. The plug-in connector can also be
usedwithpowerventers. Refertothespecificinstallation
instructions supplied by the power vent manufacturer.
On receipt of your equipment, visually check for
externaldamagetothecarton. Ifthecartonisdamaged,
it is suggested that a note be made on the Bill of Lading
whensigningfortheequipment. Removetheboiler from
the carton, and if it is damaged, report the damage to
the carrier immediately. Be sure that you receive the
number of packages indicated on the Bill of Lading.
Claims for shortages and damages must be filed
with carrier by consignee.
SPECIFICATIONSANDDIMENSIONS
Purchased parts are subject to replacement only
underthemanufacturer'swarranty. Debitsfordefective
replacement parts will not be accepted and defective
parts will be replaced in kind only per our standard
warranties.
When ordering parts, you must specify Model and
Serial Number of boiler. When ordering under warranty
conditions, you must also specify date of installation.
Raypak recommends that this manual be re-
viewed thoroughly before installing the boiler. If
thereareanyquestionswhichthismanualdoesnot
answer, please contact your local Raypak repre-
sentative.
GENERAL SPECIFICATIONS
Raytherm hydronic boilers are design certified and
testedundertherequirementsofthelatesteditionofthe
AmericanNationalStandard,ANSIZ21.13. Eachboiler
hasbeenconstructedandpressuretestedinaccordance
with the requirements of Section IV of the American
SocietyofMechanicalEngineersCode, andfactory fire
tested.
Theboilersaredesignedforindoorinstallationwitha
built-indrafthood,andabuilt-insub-baseforcombustible
flooring. Models are available with standing pilot,
orwithintermittentignitiondevice(I.I.D.). Theboilersare
equipped with the following components: water circula-
tion pump, pressure relief valve, temperature/pressure
gauge, adjustable high limit switch, drain valve, fast
responsetemperaturesensor,40VAtransformer,pump
relay, vent thermal switch, flame roll-out switch, and
redundantcombinationgasvalve. Two-stagegasvalve
(50% firing on first stage) is standard on models
H-0090,H-0135andH-0180.
The automatic ignition models and some standing
pilotmodels areprovidedwithaplug-inconnectorthatis
compatiblewiththeHoneywellD80Dventdamper.Simi-
lartypeventdampersmadebyothermanufacturers,and
design certified by a nationally-recognized testing
agency, undertheANSIZ21.66standards, mayalsobe
used.
Fig.#8978.1
3
3. INSTALLATION PROCEDURES
CLEARANCEREQUIREMENTS
1) Minimum Clearances From Combustible Materials
CODE REQUIREMENTS
Installationmustbeinaccordancewithlocalcodes
intheabsenceoflocalcodes, withthe latesteditionsof
the National Fuel Gas Code, ANSI Z223.1, and the
NationalElectrical Code,ANSI/NFPA70. InCanada,
installations must conform with the current CAN/CGA
B149.1 or .2 and the Canadian Electrical Code Part
1 CSA C22.2 No.1. Where required by the authority
having jurisdiction, the installation must conform to
AmericanSocietyofMechanicalEngineersSafetyCode
forControlsandSafetyDevicesforAutomaticallyFired
Boilers,CSD-1.
Model Floor Front Back Right Left Top Flue
No.
Vent
16" 6"
0042 Comb. 4"
6"
6"
6"
6"
6"
0066
0090
0135 Comb. Alcove 6"
0180
16" 6"
2) A front clearance of at least 24" is recommended for
adequate service of burner-tray and controls.
MOUNTING BASE
3) Except for carpeted flooring, boilers are certified for
installation on combustible floors.
Boiler should be mounted on a level surface. Each
boiler is designed with a built-in sub-base approved for
mounting the boiler on combustible flooring. Boiler
must NOT be installed on carpet flooring.
4) For un-insulated hot water pipes, maintain a 2"
clearance, or consult local authority having jurisdic-
tion.
COMBUSTION/VENTILATIONAIR
WARNING: Air supply to the boiler room must not be
affected by mechanical exhaust vents located in other
parts of the house, such as kitchen or bathroom fans,
or atticblowers. Mechanicalexhaustventsmaycreate
a negative pressure condition in the boiler room that
canbecomeahazardofasphyxiation, explosionorfire.
CAUTION: Combustion air must not be contaminated
by corrosive chemical fumes which can damage the
boiler. Measures must be taken to prevent the entry of
corrosive chemical fumes to the combustion and ven-
tilation air supply. Such chemicals include, but are not
limited to, chlorinated and/or fluorinated hydrocarbons
such as found in refrigerants, aerosol propellants, dry-
cleaningfluids, degreasers, andpaintremovers. Other
harmful elements may come from bleaches, air fresh-
eners, or mastics. Vapors from these types of products
can form corrosive acid compounds when burned in a
gas flame. The resulting acid condensate can damage
or substantially reduce the life of the heater. It may be
necessary to provide outside air directly to the heater in
order to avoid this problem.
Fig.#8196
NOTE: The boiler should be located in an area where
water leakage will not result in damage to the area
adjacent to the appliance or to the structure. When
such locations cannot be avoided, it is recommended
that a suitable drain pan, adequately drained, be in-
stalled under the appliance. The pan must not restrict
air flow.
1) The boiler must be provided with adequate supply of
air for proper combustion and ventilation in accor-
dance with Sec. 5.3, of the latest edition of the
National Fuel Gas Code, ANSI Z223.1, or appli-
cable provisions of the local building codes.
In addition, the boiler shall be installed such that
thegasignitionsystemcomponentsareprotectedfrom
water (dripping, spraying, rain, etc.) during appliance
operation and service (circulator replacement, control
replacement, etc.)
4
Location of the openings is the same as in the
previouscase-thatis,within12"ofthetop,andwithin12"
of the bottom of the enclosure. If horizontal ducts are
used, the area must be doubled and the duct area shall
not be less than the area of the openings they connect,
andinnocaseshallthesmallestdimensionbelessthan
3".
2) Models 0042 and 0066 only-
When the boiler is installed in a confined space
such as a utility room or closet where all air is
suppliedfrominside the building, the boiler room
must be provided with two openings, each one
havingaminimumnetfreearea,insquareinchesas
follows:
Model
0042, 0066
Sq. In. of Free Area
70
VENTING CONNECTIONS
These boilers have built-in drafthoods. Vent piping
the same size or larger than the drafthood outlet is
recommended; however, when the total vent height
(drafthood outlet to vent terminal) is at least ten (10)
feet, the vent pipe size may be reduced by one size only
as specified in Chapter 10 of the latest edition of the
National Fuel Gas Code, ANSI Z 223.1. As much as
possible, avoid long horizontal runs of vent pipe and too
manyelbows. Ifinstallationrequireshorizontalruns,the
vent pipe must have a minimum of 1/4 inch per foot rise
and should be supported at not less than five foot
intervals. Maximum vent connector horizontal length
shallbe1-1/2feet(18inches)foreachinchofconnector
diameter as follows.
One opening shall be within 12" of the top, and the
other opening within 12" of the floor. If additional gas
appliancesareinstalledinthesamespace,thetotalinput
of all gas appliances installed in the same space, must
beconsideredinthecalculation.RefertoSec.5.3.5ofthe
latesteditionoftheNationalFuelGasCodeforadditional
requirements.
Model
VentConnector
Diameter
MaxHorizontal
Length
42
66 & 90
135
4"
5"
6"
7"
6'
7.5'
9'
180
10.5'
Fig.#8198.0
Gasventssupportedonlybytheflashingandextend-
ingabovetheroofmorethanfivefeetshouldbesecurely
guyed or braced to withstand snow and wind loads. We
recommenduseofinsulatedventpipespacerthroughthe
roofs and walls.
Forprotectionagainstrainorblockagebysnow,the
vent pipe must terminate with a listed vent cap which
complies with the local codes or, in the absence of such
codes, to the latest edition of the National Fuel Gas
Code, ANSI Z 223.1.
The discharge opening must be a minimum of two
feet vertically from the roof surface and at least two (2)
feet higher than any part of the building within ten (10)
feet. Vent stack shall be at least five (5) feet in vertical
heightabovethedrafthoodoutlet. Theventcaplocation
shallhaveaminimumclearanceoffour(4)feethorizon-
tallyfrom,andinnocaseaboveorbelow,unlessa4-foot
horizontal distance is maintained, from electric meters,
gas meters regulators and relief equipment.
NOTE:If louvers, grills or screens are used on the
openings, obtain the net free area requirements from
their supplierormanufacturer. Ifthedesignfreeareaof
a louver is not known nor available, it shall be assumed
thatwoodlouverswillhave20-25 percentfreeareaand
metal louverswillhave60-75percentfreeareaasshown
in Sec. 5.3.5 National Fuel Gas Code.
3) If the boiler room is located against an outside wall
and air openings can communicate directly with the
outdoors,thetwoopeningsontheoutsidewallmust
each have a net free area as follows:
Model
0042
0066
0090
0135
0180
(Sq.In.)NetFreeArea
12
18
24
35
45
5
Theweightoftheventstackorchimneymustnotrest
on the boiler's drafthood. Support must be provided in
compliance with applicable codes. The boiler top and
drafthoodmustbereadilyremovableformaintenanceand
inspection. Ventpipeshouldbeadequatelysupportedto
maintainproperclearancesfromcombustibleconstruc-
tion.
Type "B" double-wall (or equivalent vent pipe is
recommended. Howeversingle-wallmetalventpipemay
be used as specified in the latest edition of the National
Flue Gas Code ANSI Z 223.1.
Lowest Discharge
Opening
Listed Cap
Listed Gas Vent
Fig.#8191
X
12
WARNING: These boilers must not be connected into
any portion of mechanical draft systems operating
under positive pressure. To do so may cause the flue
products to be discharged into the living space causing
serious health injury.
Roof Pitch is X/12
H - Minimum Height from
Roof to Lowest
For connections to gas vents or chimneys, vent
installationsshallbeinaccordancewithPart7, Venting
of Equipment, of the National Fuel Gas Code, ANSI
Z223.1, or applicable provisions of the local building
codes.
Discharge Opening
Roof Pitch
Flat to 6/12
H (Min. Ft.)
1.0
6/12 to 7/12
1.25
1.5
2.0
2.5
3.25
4.0
5.0
6.0
7.0
7.5
COMMON VENTS
Over 7/12 to 8/12
Over 8/12 to 9/12
Over 9/12 to 10/12
Over 10/12 to 11/12
Over 11/12 to 12/12
Over 12/12 to 14/12
Over 14/12 to 16/12
Over 16/12 to 18/12
Over 18/12 to 20/12
Over 20/12 to 21/12
Manifolds that connect more than one
boiler to a common chimney must be
sized to handle the combined load.
Consult available guides for proper
sizing of the manifold and the chimney.
At no time should the area be less than
the area of the largest outlet.
8.0
Fig. #9001
6
At the time of removal of an existing boiler, the
following steps shall be followed with each appliance
remaining connected to the common venting system
placedinoperation, whiletheotherappliancesremain-
ingconnectedtothecommonventingsystemarenotin
operation.
VENTDAMPERINSTALLATION
LOCATION
Theventdampersuppliedwitheachboilermustbe
locatedintheventsothatitservesonlytheappliancefor
which it is intended.
If improperly installed, a hazardous condition,
such as an explosion or carbon monoxide poison-
ing, could result. Makecertainthatitismountedinan
accessible location at least 6 in. (152.4 mm) from any
combustiblematerialortheheatexchangerandthatthe
position indicator is in a visible location.
The vent damper must be installed at the appli-
ance drafthood, and without modification of the
drafthood.
To connect the vent damper wiring to the boiler wiring,
remove the jumper from the circuit plug. (See wiring
diagram, pg. 8) Connect the damper circuit plug to the
boiler circuit plug.
(a) Seal any unused openings in the common venting
system.
(b) Visually inspect the venting system for proper size
and horizontal pitch and make sure there is no
blockage or restriction, leakage, corrosion and
other deficiencies which could cause an unsafe
condition.
(c) Insofar as is practical, close all building doors and
windows and all doors between the space in which
the appliances remaining connected to the com-
mon venting system are located and other spaces
of the building. Turn on clothes dryers and any
appliance not connected to the common venting
system. Turn on any exhaust fans, such as range
hoodsandbathroomexhausts,sotheywilloperate
at maximum speed. Do not operate a summer
exhaust fan. Close fireplace dampers.
(d) Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat
so appliance will operate continuously.
e) Test for spillage at the drafthood relief opening
after 5 minutes of main burner operation. Use the
flame of a match or candle, or smoke from a
cigarette, cigar or pipe to visually check spillage.
(f) After it has been determined that each appliance
remaining connected to the common venting sys-
tem properly vents when tested as outlined above,
return doors, windows, exhaust fans, fireplace
dampers and any other gas burning appliance to
their previous conditions of use.
(g) Anyimproperoperationofthecommonventing
system should be corrected so that the installation
conformswiththelatesteditionoftheNationalFuel
Gas Code, ANSI Z223.1. When resizing any
portion of the common venting system, the com-
monventing systemshouldberesizedtoapproach
the minimum size as determined using the
appropriate tables in Chapter 10 and in Appendix
Gof theNationalFuelGasCode,ANSIZ223.1and
CAN/CGA - B149.1 - B149.2.
Fig. #8642
WARNING: Read carefully and follow the installation
instructions furnished with the vent damper package.
Failure to follow these instructions can cause asphyxi-
ation, explosion or fire.
7
MOUNTING
On vertical vents, the vent damper may be mounted with the actuator in any position. On horizontal vents,
do not mount the actuator either directly above or directly below the vent pipe; mount the vent damper actuator
to the side of the vent.
The vent damper is set up for a continuous pilot system. If the vent damper is installed on a system with an
IntermittentPilotor HotSurfaceIgnition,theenergysavingsoftheventdampercanbeimprovedbypluggingthehole
in the vent damper blade using the knockout plug, Part No. 105612R, provided in the parts envelope.
Hole in Vent Damper Blade
Closed Position
Fig. #8994
DO NOT plug the hole if installing the vent damper on a continuous pilot system as this will create a
hazardous condition.
Fig. #8183.0
INSTALLING THE VENT DAMPER IN HORIZONTAL
&VERTICALVENTS
D80D GENERAL WIRING DIAGRAM
INSTALL THE VENT DAMPER TO SERVICE ONLY THE SINGLE APPLIANCE FOR WHICH IT IS INTENDED.
IF IMPROPERLY INSTALLED, A HAZARDOUS CONDITION, SUCH AS AN EXPLOSION OR CARBON
MONOXIDE POISONING, COULD RESULT.
8
VENTDAMPEROPERATION
Forsafe,efficientoperation,theventdamperandallflue-product-carryingareasoftheappliancemust
be checked annually, with particular attention given to deterioration from corrosion or other sources.
Check vent damper operation as follows:
1. When the boiler is off, check that the vent damper position indicator points to the closed position, below.
DAMPERPOSITION
INDICATOR
DAMPERPOSITION
INDICATOR
NOTE:Toplaceventdamperinthe
open position to allow burner
operation:
Turnthepoweroff.Turnthedamper
blade to fully open position (arrow
facingsamedirectionasventpipe).
Turnpoweron.
DAMPER OPEN
DAMPERCLOSED
Fig. # 8181.0
VENTDAMPERPOSITIONINDICATOR
2. Turn the thermostat or controller up to call for heat and check that the vent damper indicator points to the
openposition,above.
3. Turn the thermostat or controller down again and check that the vent damper position indicator returns to
the closed position.
THE VENT DAMPER MUST BE INSPECTED AT LEAST ONCE A YEAR BY A TRAINED, EXPERIENCED
SERVICE TECHNICIAN. THE NAME OF THE PERSON WHO ORIGINALLY INSTALLED YOUR VENT
DAMPER IS SHOWN ON THE INSTALLATION LABEL. DAMPER MUST BE IN OPEN POSITION WHEN
BOILER MAIN BURNERS ARE OPERATING.
FLAIR DAMPER
SYSTEM SCHEMATIC
LEGEND
M - Damper motor
R - Relay
LADDER DIAGRAM
ES - End switch
SS1 - N/C Safety switch
SS2 - N/O Safety switch
contacts
R
24
V
R
AC
R2
SS2
ES
TR - Transformer 120/24V
HL - High limit
TH
2
4
GV
GV - 24V gas valve
TH - Thermostat, heating,
low voltage
SC
SS1
HL
SS1
3
J
ES
R1
SS
R 2
JUMPER
3
J - Jumper
2
SC
M
Note: Circuit shown with
damper in closed
position, no call
R 1
M
1
2
4
for heat.
HL
GV
24 VAC
TH
TR
L 2
120 VAC
60Hz
Fig. #9002
Fig. #9003
L1
9
VENT DAMPER WIRING DIAGRAM
10
GASSUPPLYCONNECTIONS
The gas valve is provided with pressure taps to
measure gas pressure upstream of the gas valve and
downstream which is the same as the manifold pres-
sure.
The inlet gas connection of the boiler gas valve is
1/2". Provide an adequate gas piping supply line no
smaller than 1/2", according to the chart below:
Maximum Equivalent Pipe Length (Feet)
WATER CONNECTIONS & SYSTEM PIPING
The pipe size for water connections is shown on
page 3. Typical piping systems are shown on pages 12
to 14.
The boiler is supplied with a circulator and built-in
bypass as standard to ensure the required minimum
water flow in the boiler. The bypass on models H-0135
and H-0180 is provided with an adjustable valve that is
factory-setinthefullopenposition. Thehandleisshipped
loose. The full open position is appropriate for most
systems, and ensures adequate flow through the boiler.
If system flow is inadequate, (indicated by excessive
temperature drop through the system) the bypass valve
canbethrottledslightly. Caremustbetakenagainstover
-throttlingwhichmayleadtoinadequateflowthroughthe
boiler and boiler harmonics (a humming sound from the
heat exchanger). If adequate system flow cannot be
obtainedwithoutcausingharmonics,anadditionalpump
is required. The factory-mounted circulator will provide
adequate water flow for systems designed at a 20°F
temperaturedrop,andsystempressuredroporheadnot
exceeding that which is shown below.
Gas piping must have a sediment trap ahead of the
boiler gas controls, and a manual shut-off valve located
outside the jacket. All gas piping should be tested after
installation in accordance with local codes.
Manual
Valve
Union
Sediment Trap
Gas Valve
Fig. # 8192.0
CAUTION: The boiler and its manual shut-off valve must be
disconnected from the gas supply during any pressure
testing of that system at test pressures in excess of 1/2 psig
(3.45 KPA). Dissipate test pressure in the gas supply line
before reconnecting the boiler and its manual shut-off valve
to gas supply line. FAILURE TO FOLLOW THIS PROCE-
DURE MAY DAMAGE THE GAS VALVE. OVER PRES-
SURED GAS VALVES ARE NOT COVERED BY WAR-
RANTY. The boiler and its gas connections shall be leak
tested before placing the appliance in operation. Use soapy
water for leak test. DO NOT use open flame.
When the total system head exceeds the available
head pressures, a primary/secondary pumping system
is recommended.
The minimum boiler operating temperature
should be 105°F. When operating at low tempera-
NOTE: Do not use teflon tape on gas line pipe thread.
A flexible sealant suitable for use with Natural and
Propane gases is recommended.
ture applications,
20°F or less.
T (temperature rise) must be
These boilers are also certified to operate on propane
gas,whenequippedwiththecombinationgasvalveand
orifices (pilot and main burners) sized for propane gas.
Propylene glycol solution is commonly used in the
heatingsystemwhenfreezeprotectionisrequired. This
willaffectthesystemdesignandpumpperformance. As
a rule of thumb, 50% solution of propylene glycol will
require the system flow (GPM) to increase by 14%, and
thesystemhead(Ft/Wtr)by23%inordertomaintainthe
same heat transfer load.
GASPRESSURE
Inches
Min.
7.0
W.C.
Max.
14.0
14.0
Regulator
Setting
3.5
Natural
Propane
12.0
11.0
11
Systemswithmultiplezonesmayrequireanadditionalcirculator. Consultmanufacturer'sdataforvalvepressure
drops. When an indirect water heating system is used, it is recommended that a separate circulator be installed
to meet the required flow and pressure drop conditions of the indirect water heater.
Werecommendthatthemake-upwaterfromthecoldwaterlinehaveacheckvalve, gatevalve, andfeedwater
regulatorsetat12psig. Installunionsandgateorball valvesatinletandoutletconnections at theboilertofacilitate
servicing.
The pressure relief valve is mounted on the boiler and must be piped to a drain. We recommend that all high
points be vented and that purge valves be installed. A boiler installed above radiation level must be provided with
alowwatercut-offdevice. Seepage22forwiringhook-up. Theboiler,whenusedinconnectionwitharefrigeration
system, must be installed so that the chilled medium is piped in parallel with the boiler with appropriate valves to
prevent the chilled medium from entering the boiler.
The boiler piping system of a hot water heating boiler, that is connected to heating coils located in air handling
units where they may be exposed to refrigerated air circulation, must be equipped with flow control valves or other
automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
A diaphragm expansion tank should be installed in the return line. A typical 8"-diameter expansion tank can
be used on models H-0042, and H-0066, and an 11"-diameter expansion tank can be used on models
H-0090, H-0135 and H-0180. Consult tank manufacturer for correct sizing.
PIPINGDIAGRAMS
AIR
VENT
AIR
SCOOP
DIAPHRAGM
EXPANSION TANK
FEED
VALVE
PIPE PRESSURE
RELIEF VALVE
TO DRAIN
COLD
WATER
INLET
HEATING UNITS
SINGLE-ZONEPIPING
Fig.# 8997.1
12
AIR
VENT
AIR
SCOOP
DIAPHRAGM
EXPANSION
TANK
FEED
VALVE
PIPEPRESSURE
RELIEFVALVE
TODRAIN
ZONE
VALVES
COLD
WATER
INLET
HOTWATER
SUPPLY
HEATINGUNITS
CIRCULATOR
COLD
WATER
SUPPLY
Fig.# 8998.1
ZONEHEATING WITH INDIRECTDOMESTIC
HOT WATER SUPPLY
13
12"MAX.
AIR
VENT
AIR
SCOOP
DIAPHRAGM
EXPANSION
TANK
FEED
VALVE
PIPE PRESSURE
RELIEF VALVE
TO DRAIN
CIRCULATORS
COLD
WATER
INLET
HEATING UNITS
Fig.#8999.1
MULTIPLEZONESWITHCIRCULATORS
AIR
VENT
AIR
SCOOP
DIAPHRAGM
EXPANSION
TANK
FEED
VALVE
PIPE PRESSURE
RELIEF VALVE
TO DRAIN
COLD
ZONE
VALVES
WATER
INLET
HEATING UNITS
Fig.#9000.1
MULTIPLEZONESWITHZONEVALVES
14
ELECTRICAL WIRING
The electrical power supply requirement for these
boilers is 115 volts, 60 Hz. Field wiring connections and
electrical grounding must comply with the local codes,
or in the absence of local codes, with the National
Electrical Code, ANSI/NFPA 70-1987. Provide a sepa-
rate fused circuit from the main electrical panel to the
boiler, and a disconnecting means within sight of the
boiler.
The room thermostat should be installed in accordance
withthemanufacturer'sinstructions.Thethermostatheat
anticipator should be set at 1.0 ampere (automatic
ignition)and0.60ampere(standingpilot)forsingle-zone
installations.Formulti-zoneapplications,theheatantici-
pator setting should be based on the ampere load in the
thermostat circuit.
Remove the control box cover and make the power
supply connections in the field wiring compartment.
(See general location of controls drawing on page 23).
The pump is supplied and factory-wired to operate with
the boiler. The "TH" wire leads are for the room thermo-
stat or zone valve connections.
NOTE: If it is necessary to replace any of the original
wiring, it must be replaced with 105°C wire or its
equivalent,except 150°Cblack wire must be replaced
with150°Cwireoritsequivalent. SeeWiringDiagramKey
for150°Cwireindication.
WIRING DIAGRAM KEY
Fig.# 8096.2
15
WIRINGDIAGRAMS
16
17
18
WIRING DIAGRAM: Single-Zone Taco Valve
Fig. # 2228e
WIRING DIAGRAM: Dual-Zone Taco Valve
Fig. # 2229e
NOTE: Maximum three (3) zone valves per one (1) 40 VA transformer.
WIRING DIAGRAM: Dual-Zone Honeywell Valve
Fig. # 2230e
NOTE: Maximum five (5) zone valves per one (1) 40 VA Transformer.
19
WIRING DIAGRAM: System with (3) Zone Pumps
Fig. #2232e
NOTE: Check VA rating of each relay coil. Total load must not exceed VA rating of transformer.
WIRING DIAGRAM: Power Vent System w/ Zone Valve
Fig. #2233e
Fig. #2234e
20
WIRING DIAGRAM: Primary/Secondary Pumping System
Honeywell Zone Valve
Fig. #2223.2e
21
WIRING DIAGRAM: Standing Pilot With Low Water Cut-off Device
Fig. # 2223.1e
Note: Low water cut-off (LWCO) and system switch supplied by others.
WIRING DIAGRAM: IID Units With Low Water Cut-off Device
Fig. # 2357E
Note: Low water cut-off (LWCO) and system switch supplied by others.
22
SERVICING PROCEDURES
CIRCULATOR
GENERAL LOCATION OF CONTROLS
VENT SENSOR
BYPASS VALVE
CONTROL BOX COMPONENT
LOCATIONS MODELS 135 & 180
(MODELS 135 & 180 ONLY)
BYPASS LINE
2-Stage Controller
TEMPERATURE
AND PRESSURE GAUGE
2-STAGECONTROLLER
(MODEL 90 ONLY)
Relay
PRESSURE
RELIEF VALVE
RELAY
ADJUSTABLE
HIGH LIMIT
FIELD WIRING
COMPARTMENT
FAST RESPONSE
TEMPERATURE SENSOR
Fast-
Ignition Module
(Auto Ignition Only)
Response
Temperature
Sensor
IGNITION MODULE
(AUTO IGNITION ONLY)
TRANSFORMER
ROLL-OUT SENSOR
GAS VALVE
Fig.#8195.1
Fig.#8195.4
SEQUENCE OF OPERATION
INTERMITTENT IGNITION DEVICE (IID)
Boilers equipped with the IID system will automatically light the pilot burner first and then the main burner, each
time there is a call for heat from the room thermostat. Whenever the room thermostat is calling for heat, the
circulator supplied with the boiler, will be energized and should be running. The ignition control module will also
be energized to initiate the pilot ignition by opening the first main valve (pilot). At the same time, the electronic
sparkgeneratorinthemoduleproducesahigh-voltagesparkpulseoutputthatlightsthepilotburner. Ifthepilotburner
does not light, the module will not energize the second main valve and the burners will not light. Ignition spark
continues only until the timed trial for ignition period ends. Then, the module goes into safety shutdown or lockout.
Lockoutde-energizesthefirstmainvalveoperatorandclosesthefirstmain(pilot)valveinthegascontrol,stopping
pilot gas flow. The ignition control system must be reset by setting the thermostat below room temperature for one
minuteorbyturningoffpowertothemoduleforoneminute. Whenthepilotflameisestablished, flamerectification
circuitiscompletedbetweenthesensorandburnerground. Theflamesensingcircuitinthemoduledetectstheflame
current,shutsoffthesparkgeneratorandenergizesthesecondmainvalveoperatorwhichopensthesecondmain
valve. This allows gas to flow to the burners where it is ignited by the pilot burner flame. When the thermostat is
satisfied, the valve operators are de-energized shutting off the pilot and main burners, and also the circulator.
23
START-UPPROCEDURES
Filling the System
Flushsystembeforeputtingintooperationtoensure
that foreign material does not damage pump seals.
Fillsystemwithwater. Purgeallairfromthesystem
Lighting the Boiler
Safe-lightingandotherperformancecriteriaweremet
withthegasmanifoldandcontrolassemblyprovidedon using purge valve sequence. After system is purged of
theboilerwhentheboilerunderwenttestsspecifiedinthe air, lower system pressure. Open valves for normal
latest edition of the ANSI-Z21.13 Standard.
system operation, fill system through feed pressure
regulator to minimum12PSI. Manuallyopenairventon
CAUTION: Propane gas is heavier than air and sinks to the compression tank until water appears, then close
the ground. Exercise extreme care in lighting boiler in vent.
confinedareas.
On multiple-zone systems, purge each zone sepa-
rately. Isolate the other zones while one zone is being
purgedofair.
For Standing Pilot Models
WARNING: If you do not follow these instructions
exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
Checking the Circulator
Before lighting the boiler and after system is filled,
make sure that circulator is operating properly. Manual
gas valve should be off. By adjusting the wall thermo-
A. This boiler has a pilot which must be lighted by
hand. When lighting the pilot, follow these instructions stat to the maximum setting, circulator should run
exactly.
immediately and allow water to flow through the boiler
and the entire system.
B. BEFORE LIGHTING Smell all around the boiler
area for gas. Be sure to smell next to the floor because NOTE: Circulator motor supplied with the boiler does
some gas is heavier than air and will settle on the floor. not require lubrication.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch;
• Do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
CAUTION: In case of a prolonged power failure during
freezing weather conditions, boiler and piping system
must be drained completely to avoid possible damage
to the heating system.
• If you cannot reach your gas supplier, call the
fire department.
C. Use only your hand to push in, move or turn the gas
control knob or lever. Never use tools. If the knob or
lever will not push in, move or turn by hand, don't try to
repair it. Call a qualified service technician. Force or
attempted repair may result in a fire or explosion.
D. Donotusethisboilerifanyparthasbeenunderwater.
Immediatelycallaqualifiedservicetechniciantoinspect
the boiler and to replace any part of the control system
and any gas control which has been under water.
24
10. Turn on all electrical power to the boiler.
11. Set the thermostat to the desired setting.
FOR STANDING PILOT MODELS WITH ROBERT-
SHAWGASVALVE,2-STAGEOPERATION
(Models 90, 135 & 180)
TO TURN OFF GAS TO THE BOILER:
(Models 90, 135 & 180)
1. STOP! Read the safety information.
2. Set the thermostat to the lowest setting.
3. Turn off all electrical power to the boiler.
4. Push in and move gas control lever counter-
1. Set the thermostat to the lowest setting.
2. Turn off all electrical power to the boiler
3. Push in and move gas control lever counter-
clockwise
to "OFF" position.
clockwise
to "OFF" position. Do not force.
GAS CONTROL
LEVER SHOWN
IN "OFF" POSITION
FOR AUTOMATIC IGNITION MODELS.
Please read carefully and understand the following
safety information before operating the boiler.
GAS INLET
WARNING: If you do not follow these instructions
exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
Fig. #8934.0
NOTE: Lever cannot be moved from "ON" to
"OFF" unless lever is pushed in slightly. Do not
force.
A. This boiler is equipped with an ignition device which
automatically lights the pilot. Do not try to light the pilot
by hand; or this boiler may not have a pilot and is
equipped with a hot surface ignition device which auto-
matically lights the burners. Do not try to light the
burners by hand.
5. Wait five (5) minutes to clear out any gas. Then
smell for gas, including near the floor. If you smell
gas, STOP! Follow "B" in the safety information on
thelabelaffixedtotheunit. Ifyoudon'tsmellgas,go
to the next step.
B. BEFORE OPERATING smell all around the boiler
area for gas. Be sure to smell next to the floor because
some gases are heavier than air and will settle on the
floor.
6. Locate pilot mounted on the right side of the
burner tray, and right of first burner.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
Fig.# 8083.2
Fig.# 8041.2
• If you cannot reach your gas supplier, call the
fire department.
HONEYWELL PILOT
ROBERTSHAW PILOT
to "SET"
C. Use only your hand to push in, move or turn the gas
control knob or lever. Never use tools. If the knob or
lever will not push in, move or turn by hand don't try to
repair it, call a qualified service technician. Force or
attempted repair may result in a fire or explosion.
7. Movecontrolleverclockwise
position and immediately light pilot with a match.
8. Hold lever in "SET" position for 1/2 minute after
pilot is lit. Release lever, and it will spring back
to "PILOT" position. Pilot should remain lit. If it
goes out, repeat steps 4 through 8.
D. Donotusethisboilerifanyparthasbeenunderwater.
Immediatelycallaqualifiedservicetechniciantoinspect
the boiler and to replace any part of the control system
and any gas control which has been under water.
*If lever does not spring back to "PILOT" position
when released, stop and immediately call your
service technician or gas supplier.
*If the pilot does not stay lit after several tries,
move the gas control lever to "OFF" and call your
service technician or gas supplier.
9. Stand to the side of the boiler and move the gas
control lever counter-clockwise
to "ON".
25
TO TURN OFF GAS TO BOILER
FOR INTERMITTENT IGNITION (IID) WITH HONEY-
WELL OR ROBERTSHAW GAS VALVE (All Models)
1. Set the thermostat at the lowest setting.
2. Turn off all electrical power to the boiler if service
is to be performed.
1. STOP!Readtheprevioussafetyinformation.
2. Set the thermostat to the lowest setting.
3. Turn off all electrical power to the appliance.
4. Thisboilerisequippedwithanignitiondevicewhich
automatically lights the pilot. Do not try to light the
pilot by hand.
3. For Honeywell valve:
Turn gas control knob clockwise
"Off". Make sure knob rest against stop.
For Robertshaw valve:
to
Push in and move gas control lever to "Off"
position.
GASCONTROL
KNOBSHOWN
IN"ON"
POSITION
GASINLET
Fig.#8201.0
HONEYWELL
(Models 30 - 90)
5. For Honeywell valve: Turn gas control knob
HONEYWELL PILOT
clockwise
to "Off".
For Robertshaw valve: Push in and move gas
control lever to "Off" position.
6. Wait 5 minutes to clear out any gas. Then smell for
gas, including near the floor. If you smell gas,
STOP! Follow "B" in the safety information on the
labelaffixedtothefrontoftheunit. Ifyoudon'tsmell
gas, go to the next step.
SHUT-DOWNPROCEDURE
7. For Honeywell valve: turn gas control counter-
To prevent freeze damage to the heating system, it
is recommended that the following system shut-down
procedurebeperformed.
1. Set the room thermostat to "OFF" or the lowest
setting.
2. Turn off all electrical switches to the boiler.
3. Turn off all gas valves supplying gas to the boiler.
Refer to operating instruction label on the boiler.
4. Shut-offthewatersupplytotheboilerpipingsystem
loop.
clockwise
to "On".
For Robertshaw valve: Move gas control lever
to "On" position.
GAS CONTROL
KNOB SHOWN
IN "OFF"
POSITION
GAS INLET
5. Opendrainvalveontheboilertoremovewaterfrom
the boiler and the piping circuits.
Note: Itmaybenecessarytoopenthepurgevalvesand/
or manual air vents to facilitate complete drainage of
water from the heating system.
Fig. #8199.0
ROBERTSHAW
(All Models)
8. Turn on all electrical power to the boiler.
9. Set thermostat to desired setting.
10. If the boiler will not operate, follow the instructions
"To Turn Off Gas To Boiler" and call your service
technician or gas supplier.
26
CAUTION:Shouldoverheatingoccuror thegassupply
fails to shut-off, DO NOT turn off or disconnect the
electrical supply to the pump. Instead, shut-off the gas
supply at a location external to the boiler. Failure to
observe this precaution may aggravate the overheated
condition resulting in possible damage to the boiler and
injury to the user.
FORAUTOMATICIGNITIONSYSTEMS
IntermittentIgnition(IID)
1. Turn on power to the ignition systems and turn gas
supply off at the gas valve.
2. Check ignition module as follows:
a. Set the thermostat or controller above room
temperature to call for heat.
SECTION 4. Testing the Ignition Safety Shut-off.
The ignition system safety shut-off must be tested
by conducting the following tests:
b. Watch for continuous spark at the pilot burner.
c. Time the spark operation. Time must be within
the lockout timing period (15 or 90 seconds).
d. Turn thermostat down to end call for heat and
wait 60 seconds on lockout models before
beginning step 3.
For Standing Pilot Systems
a. With the main burners on, remove the pilot
adjustmentcoverscrew.
3. Turn on gas supply.
* NOTE: There is no pilot adjustment cover on
Robertshaw 7200 gas valve.
4. Setthermostatorcontrolleraboveroomtempera-
ture to call for heat.
b. Insert a small slot screw driver and turn the
5. Systems should start as follows:
a. Spark will turn on and pilot gas valve will open
at once. Pilot burner should ignite after gas
reaches the pilot burner.
adjustment screw clockwise
until pilot
flamegoesout. Noteandcountnumberofturns
made.
c. Gasvalvewillshut-offmainburnersafterabout
three(3)minutes.Ifthegasvalvewillnotshut-off,
followtheinstructions"ToTurnOffGasToBoiler"
and call service technician or your gas supplier.
d. Return pilot adjustment screw counter-clock-
b. Sparkignitionshouldcut-offwhenpilotflameis
established.
c. Maingasvalveshouldopenandmainburner
shouldigniteaftergasreachestheburnerport.
wise
, using the same number of turns as
in step (b).
Pilot Adjustment
Fig.# 8935.0
ROBERTSHAW7200 GASVALVE
(Models 90, 135 & 180)
e. Replace pilot adjustment cover screw, then
follow the lighting instructions to get boiler
ready for operation.
27
SAFESHUT-DOWNTESTS
LIMIT ACTION
With the burner operating, lower the high limit
setting to simulate an overheated boiler. Normal shut-
down should occur. Restore the normal limit setting,
and the burner should restart.
FLAME FAILURE
Withburneroperating, closethemanualfuelvalves
to simulate a flame failure. System should lock out after
safety switch timing (15 seconds). After the safety
switch has cooled, open the manual valves (relight
standing pilots) and reset the safety switch; the burner
should restart.
Fig.#8964
PILOTBURNERFLAME(STANDINGPILOTUNITS)
INSPECTIONSCHEDULE
Tobeperformedthefirstandthirdmonthafterinitial
start up and then on an annual basis. If problems are
found,refertoTroubleshootingGuideforadditionaldirec-
tions.
INSPECTION PROCEDURES
BURNERS
1. Remove top of boiler and inspect heat exchanger
for soot and examine venting system.
2. Remove rear header and inspect for scale depos-
its.
*3. Inspect pilot and main burner flame and firing rate.
*4. Inspect and operate all controls and gas valve.
*5. Visually inspect system for water leaks.
*6. Inspect oil pump motor and bearing assembly, if oil
cupsareprovided.
Clean main burners and air louvers of dust, lint and
debris.Keepboilerareaclearandfreefromcombustibles
and flammable liquids. Do not obstruct the flow of
combustion and ventilation air. Make visual check of
burnerandpilotflame.Yellowflameindicatescloggingof
air openings. Lifting or blowing flame indicates high gas
pressure. Low flame indicates low gas pressure.
7. Check flow switch paddle.
8. Cleanroomairintakeopeningstoensureadequate
flow of combustion and ventilation air.
9. Keep boiler area clear and free from combustible
materials, gasoline, and other flammable vapors
and liquids.
*Should be checked monthly. (Takes approximately 15
minutes).
Fig. #8144
MAIN BURNER FLAME
NOTE: Modulating burner flame varies in height from
approximately 1/4" at low fire to approximately 4" in
high fire.
28
LOWWATERCUT-OFF (WHENINSTALLED)
BURNERTRAYREMOVAL
The low water cut-off automatically shuts down 1. Shut-off power and gas supply to the boiler. Dis-
burner whenever water level drops below probe. 90
second time delay prevents premature lockout due to
connect union(s) and pilot tubing when present;
thenloosenand removeburnerhold-downscrews.
temporary conditions such as power failure or air pock- 2. Disconnect wires at gas valve and slide burner
ets. Flushfloattypedevicesatbeginningofeachheating
season.
tray out.
MAINBURNERANDORIFICEREMOVAL
1. Removescrewsandburnerhold-downbracket.
PROCEDUREFORCLEANINGFLUEGAS
PASSAGEWAYS
Sootwillclogareasbehindfinsandeventuallycause NOTE: If theheatexchangerissootedbadly,theburner
tubefailure. Anysignofsootatbaseofburnersoraround hold-down bracket and spacer can become distorted
outer jacket indicates a need for cleaning.
fromdirectflameimpingementandthisusuallynecessi-
tates replacement of these parts.
1. Liftoffdrafthoodandfluecollectorbyremoving
bolts and screws.
2. Lift burners from slotted spacer and slide from
orifices. Clean with a wire brush.
2. Remove"V"bafflesfromheatexchanger.
3. Removeburnertray,seeBurnerTrayRemoval.
4. Take garden hose and wash heat exchanger, mak-
ing sure soot is removed from between fins.
(Avoidexcessivewateragainstrefractory).
5. Reassemble; when boiler is fired, some steam will
form from wet refractory. This is normal.
NOTE: Inextremecasesitmaybenecessarytoremove
the heat exchanger completely for cleaning. The sim-
plest method is steam cleaning at a local car wash. DO
NOT WIRE BRUSH!
3. Orifices usually do not need to be replaced. To
clean, run either copper wire or wood through
orifice. Do not enlarge hole. To remove orifice, use
a socket wrench and remove the manifold. DO
NOTovertightenwhenreinstalling.
CAUTION:
Soot is combustible, so exercise extreme care.
RAYPAKTUBECLEANINGKIT
Extension Pieces (5)
Auger with Carbide Tip
Wire Brush
Fig.#8154
5/8" - PN 052871F
7/8" - PN 052870F
REPAIRPROCEDURES
Another method is to remove the heat exchanger,
reamtubesandimmerseheatexchangerinnon-inhibited
de-scalesolvent.
TUBECLEANINGPROCEDURE(TYPICAL)
Establish a regular inspection schedule, the fre-
quencyofwhichdependsonthelocalwaterconditionand
severity of service. Do not let the tubes clog up solidly.
Clean out deposits over 1/16" in thickness.
Theboilermaybecleanedfromthesideoppositethe
water connections as shown, without breaking pipe
connections. It is preferable, however, to remove both
headers for better visibility through the tubes and to be
sure the residue does not get into the system.
Note that you do not typically remove the top pan or
the heat exchanger.
HEATEXCHANGERREMOVAL
1. Shut water, gas and electricity off, close valves,
relievepressureandremovereliefvalve. Removeside
inspectionpanels.
2. Removetopholdingscrews.
3. Removedraftdiverter,liftandremovetopandflue
collectoronstacktypemodels. Removeinspection
panels.
4. Loosen bolts and disconnect flange nuts on inlet-
outletheader,loosenunion(s)atgaspipe,andslide
boiler away from piping until studs clear the heater.
5. Removeheatexchangercornerbrackets.
After reaming with the auger, mount the wire brush
and clean out the debris remaining in the tubes.
29
6. Remove combustion chamber clips at the four
corners of the heat exchanger.
7. Lift heat exchanger straight up using caution not to
damage refractory.
boiler and piping system for leaks at full line pres-
sure. Run system circulating pump for a minimum
of 1/2 hour with boiler shut off.
8. Shutdownentiresystemandventallradiationunits
and high points in system piping. Check all strain-
ers for debris. Expansion tank water level should
be at the 1/4 mark and the balance of the tank filled
with air (when using Air-X-Tank).
9. Install flue collector, jacket top and inspection pan-
els. Install top holding screws. Install draft diverter
and vent piping if so equipped.
10. If gas piping was disconnected, reconnect gas
piping system and check for leakage using a soap
solution.
11. Check for correct water pressure and water level in
the system. Make sure that system pump operates
immediately on the call for heat. The system is
readyforoperation.
12. Within two (2) days of start-up, recheck all air vents
and expansion tank levels.
Fig#9337
HEAT EXCHANGER RE-ASSEMBLY
COMBUSTION CHAMBER REMOVAL
1. Heat exchanger water header O-rings should be
replaced with new ones.
2. Install in/out and return water headers and
install header retainer nuts and torque nuts evenly.
3. Replace "V" baffles.
To remove combustion chamber you must first
have removed the heat exchanger. Unbolt metal com-
bustion chamber retainer from top and remove com-
bustion chamber panels individually.
4. Install thermostat sensing bulbs in header wells
and replace bulb retaining clips.
5. Install inlet and return pipes in water headers using
pipe thread sealant.
6. Install water pressure relief valve, flow switch, and
low water cut-off devices if so equipped.
7. Open water supply and return shut-off valves. Fill
boiler and water piping system with water. Check
30
TROUBLESHOOTING GUIDE
IMPORTANTNOTICE
These instructions are primarily intended for the use of qualified personnel specifically trained and experienced
in the installation of this type of heating equipment and related system components. Installation and service
personnel may be required by some states to be licensed. Persons not qualified shall not attempt to install this
equipment nor attempt repairs according to these instructions.
SOLUTIONS
PROBLEM
CAUSES
1)Check circuit breakers, disconnect
switch. Make sure power is on.
1)When room thermostat is turned on,
boiler does not operate.
1)No power to the boiler.
2)Check continuity on thermostat and
wiring circuit. Replace thermostat, or
repair wiring connections.
2)Defective room thermostat or discon-
nected wire in thermostat circuit.
3) Check secondary voltage. If no 24V,
replace transformer.
4) Check relay coil or contacts. Replace
as required.
3)Defective transformer.
4)Defective pump relay.
5)Defective pump.
5) Replace pump.
1)Light pilot burner. (Follow lighting
instructions on rating plate.)
2)Check thermocouple MV generation.
If less than 25MV (open circuit), re-
place thermocouple. If between 25-
35 MV, replace gas valve.
2)When room thermostat is calling for
heat, pump is on, but burners will not
turn on.
1)For standing pilot models, pilot
burner not lighted.
2)If pilot burner will not stay lighted,
thermocouple or gas valve may be
defective.
3)Turn knob to "ON" position.
3)Gas knob in "Pilot" position.
4)For automatic ignition models,
gas valve knob is in "off" position.
4)Turn gas knob to "ON". If ignition
module locks out, reset by interrupt-
ing power to boiler.
5) Check for blockage of venting system
or disconnected vent piping. After
problem is corrected push button to
reset, or replace single-use type vent
switch.
5)Vent switch is open.
6)Check for blockage of flue or sooted
heat exchanger. After problem is
corrected push button to reset or re-
place single use type roll-out switch.
7)Setting may be too low. Check water
flow and adjust setting to obtain 20-
30°F temperature rise.
6)Roll-out switch is open.
7)High limit is open.
8)Red LED on circuit board will be ON
to indicate a loose sensor connection
or a shorted sensor. Check terminal
connectors or replace sensor as re-
quired.
8) Fast Response Temperature
Sensor probe is defective.
NOTE: Red LED will also be ON if
sensor temperature exceeds 300°F or
drops below - 20°F. It will turn OFF
when sensor temperature returns to
the proper range. Yellow LED will be
ONiftemperatureexceeds240°F. Itwill
turn off when sensor temperature falls
below 180°F. When either Red or Yel-
low LED is ON, boiler will be shut down.
9)Check voltage across output and
common terminals. If no 24V is pres-
ent, replace board.
9) Fast Response Temperature
sensor board is defective.
31
10) Defective ignition module or
defective gas valve.
10)Beforemodulegoesintoalock-out,
check voltage across MV and MV/
PV. If no 24V is present, replace
module. If 24V is present, replace
gas valve.
3)Pilot Outage.
(Standing pilot models)
1) Too low or too high gas pressures.
1) Adjust inlet gas pressure as shown
on rating plate.
2) Restricted pilot.
2) Clean pilot orifice.
3) Weak thermocouple.
3) Replace thermocouple.
4)Yellow lazy flame.
1) Too low gas pressure.
2) Restricted burner intake ports.
3) Restricted gas line.
1) Adjust manifold pressure as shown
on rating plate.
2) Clean burners free of debris or in-
sects.
3) Clean gas line or increase gas line
piping.
5)Sooting
1) Refer to installation instructions re-
garding combustion air require-
ments.
1) Insufficient combustion air.
2) Improper venting.
3) Severe yellow burner flames.
2) Refer to installations instructions.
3) See yellow flame section above.
32
ADJUSTMENT/REPLACEMENTOF
COMPONENTS
3. Flame Roll-out Switch Replacement
a) Shut-off electrical power to the boiler.
b) Remove wiring connections to switch.
c) Remove screws (2) holding the switch.
d) Reverse above procedure to re-install.
DANGER - SHOCK HAZARD
Make sure electrical power to the boiler is disconnect-
ed to avoid potential serious injury or damage to com-
ponents.
4. Vent Thermal Switch Replacement
a) Shut-off electrical power to the boiler.
b) Remove wiring connections to switch.
c) Remove the screws (2).
1. Gas Valve Replacement
a) Shut-off electrical power and gas supply to the
boiler.
d) Reverse above procedure to re-install.
b) Remove gas piping to gas valve inlet.
c) Disconnect wiring connections, pilot tubing
(when present).
d) Remove screws (2) holding the burner tray.
e) Slide burner tray out.
5. Ignition Module Replacement
a) Shut-off electrical power to the boiler.
b) Remove control cover screws and open control
compartment.
f) Remove gas valve bracket screws and bracket.
g) Unscrew gas valve from gas pipe.
h) Reverse above procedure to re-install.
c) Disconnect wiring connections to module.
d) Remove screws (2) holding module.
e) Reverse above procedure to re-install.
2. Pilot Burner Cleaning or Replacement (Standing
Pilot)
6. Transformer Replacement
a) Shut-off electrical power to the boiler.
b) Remove control cover screws and open control
compartment.
a) Shut-off electrical power and gas supply to the
boiler.
b) Disconnect gas piping to gas valve.
c) Disconnect wiring connections to gas valve.
d) Remove screws (2) holding the burner tray.
e) Slide burner tray out.
c) Disconnect wiring connections from trans-
former leads.
d) Remove screws (2) holding transformer.
e) Reverse above procedure to re-install.
f) Remove screw holding pilot lighter tube.
g) Remove screws (2) holding pilot bracket on the
burner tray.
h) Disconnect thermocouple and pilot tubing from
the gas valve.
7. Pump Relay Replacement
a) Shut-off electrical power to the boiler.
b) Remove control cover screws and open control
compartment.
i) Remove pilot burner from pilot bracket.
j) Remove pilot orifice and blow away lint or dirt.
Clean with wire or small brush.
c) Disconnect wiring to the relay.
d) Remove screws (2) holding relay.
e) Reverse above procedure to re-install.
NOTE: Make sure pilot orifice is clear, but do not
enlarge the hole.
8. High Limit Control
a) Shut-off electrical power to the boiler.
b) Remove control cover screws and open
control compartment.
k) Reverse above procedure to re-install.
HONEYWELL PILOT
PILOT
ROBERTSHAW PILOT
c) The control is factory set at 180°F. To adjust
setting, use a small screw driver and turn dial
clockwise
counter-clockwise
to lower the temperature or
to raise the setting.
d) To replacethelimitcontrol,disconnectthewir-
ing connections.
PILOT
AIR
e) Remove screws (2) holding the limit control.
f) Remove upper access panel.
g) Remove the wedge or retaining clip holding
the sensing bulb in the control well in the in/out
header.
OPENING
ORIFICE
h) Pull out the sensing bulb carefully from the
control well.
ORIFICE
i) Remove the limit control with capillary from
unit.
j) Reverseaboveproceduretore-install.
Fig.# 8045.2
Fig.# 8102.1
33
9.Fast-ResponseTemperatureSensorModule
Replacement
12. 2-Stage Controller (Models 90, 135 & 180)
a) Shut-off electrical power to the boiler.
b) Remove control cover screws and open con-
trol compartment.
a) Shut-off electrical power to the boiler.
b) Remove control cover screws and open
control compartment.
c) The control is factory set at 160°F. To adjust
c) Disconnect wiring to the board.
d) Carefully pull out the control board from the
nylon pin supports.
to another setting, use a small screw driver
and turn dial clockwise
to lower the
to
temperature or counter-clockwise
raise the setting.
e) Reverse above procedure to re-install.
d) To replace the stage controller, disconnect
10.Fast-ResponseTemperatureSensorProbe
Replacement
the wiring connections.
e) Remove screws (2) holding the staged
controller.
f) Remove upper access panel.
g) Remove the wedge or retaining clip holding
the sensing bulb in the control well in the in/
out header.
a) Shut-off electrical power to the boiler.
b) Shut-off water supply to the boiler and open
drain valve to remove water to the sensor
probe level.
c) Remove control cover screws and open
control compartment.
h) Pull out the sensing bulb carefully from the
d) Disconnect wire leads from control board.
e) Remove upper access panel.
f) Remove sensor probe from in/out header.
g) Reverse above procedure to re-install.
control well.
i) Remove the stage control with capillary from
unit.
j) Reverseaboveproceduretore-install.
11. Circulator Replacement
a) Shut-off electrical power to the boiler.
b) Shut-offwatersupplyandopendrainvalve
to remove water in the piping at the pump
level.
REPLACEMENT PARTS LIST
NOTE:Tosupplythecorrectpartitisimportantthatyou
supplythemodelnumber,serialnumberandtypeofgas
when applicable.
CAUTION: To avoid damage to electrical components
keep water from getting into the control compartments
and gas valve.
Any part returned for replacement under standard
company warranties must be properly tagged with
Raypak return parts tag, completely filled in with the
heaterserialnumber, model numberetc., andshipped
toRaypakfreightprepaid.
c) Disconnect wiring and conduit connections to
the pump.
d) Disconnect the bypass tube connections to
If determined defective by Raypak and within war-
ranty, thepartwillbereturnedinkindorequal substitu-
tion, freight collect. Credit will not be issued.
the inlet flange.
e) Remove the nuts and bolts at the inlet and
outlet flanges. Remove old gaskets.
f) Remove the pump.
g) Reverse the above procedure to re-install.
Use new gaskets and make sure they are
seated properly when tightening the nuts
and bolts.
RAYPAK,INC.
2151 Eastman Avenue
Oxnard, CA 93030
34
35
36
37
Catalog No.: 1910.10H
Effective: 01-01-04
Replaces: 05-15-03
LIMITED PARTS WARRANTY
RESIDENTIALHEATING BOILERS
MODELS 42 TO 180
SCOPE:
Raypak, Inc. (“Raypak”) warrants to the original owner that all parts of this boiler which are actually manufactured by Raypak will be free
from failure under normal use and service for the specified warranty periods and subject to the conditions set forth in this Warranty. Labor
charges and other costs for parts removal or reinstallation, shipping and transportation are not covered by this Warranty but are the
owner’s responsibility.
ANY PART MANUFACTURED BY RAYPAK:
One (1) year warranty from date of boiler installation, or eighteen (18) months from date of factory shipment based on Raypak’s records,
whichever comes first.
SATISFACTORY PROOF OF INSTALLATION DATE, SUCHAS INSTALLER INVOICE, IS REQUIRED. THIS WARRANTY WILLBE VOID IF THE
BOILER RATING PLATE ISALTERED OR REMOVED.
HEAT EXCHANGER WARRANTY:
Second through tenth years from date of installation, Raypak warrants that the copper and cast iron waterway are free from defects in
material and workmanship. If any of these parts are found defective Raypak will replace or repair free of charge subject to conditions
listed under “Scope” above.
Eleventh through twentieth years from date of installation, Raypak warrants that the copper and cast iron waterways are free from
defects in material and workmanship. If any of these parts are found defective Raypak will replace the original parts and payment of a
proportionate charge equal to 1/120th of the list price of such parts, at the time the warranty claim is made, for each month, or portion there
of, beyond the tenth year.
ADDITIONAL WARRANTY EXCLUSIONS:
This warranty does not cover failures or malfunctions resulting from:
1. Failure to properly install, operate or maintain the boiler in accordance with our printed instructions provided;
2. Abuse, alteration, accident, fire, flood and the like;
3. Sediment or lime buildup, freezing, or other conditions causing inadequate water circulation;
4. High velocity flow exceeding boiler design rates;
5. Failure of connected systems devices, such as pump or controller;
6. Use of non-factory authorized accessories or other components in conjunction with the boiler system;
7. Failure to eliminate air from, or replenish water in, the connected water system;
8. Chemical contamination of combustion air or use of chemical additives to water;
9. Boilers installed in buildings other that one- or two-family dwellings.
PARTS REPLACEMENT:
Under this Warranty, Raypak will furnish a replacement for any failed part. The failed part must first be returned to Raypak if requested,
with transportation charges prepaid, and all applicable warranty conditions satisfied. The replacement part will be warranted for only the
unexpired portion of the original warranty. Raypak makes no warranty whatsoever on parts manufactured by others, but Raypak will
apply any such warranty as may be provided by the parts manufacturers.
TO MAKE WARRANTY CLAIM:
Promptly notify the original installer, supplying the model and serial numbers of the unit, date of installation and description of the problem.
The installer must then notify a Raypak distributor for instructions regarding the claim. If neither the installer nor the distributor is available,
contact Service Manager, Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 or call (805) 278-5300. In all cases proper authoriza-
tion must first be received from Raypak before replacement of any part.
EXCLUSIVE WARRANTY - LIMITATION OF LIABILITY:
This is the only warranty given by Raypak. No one is authorized to make any other warranties on Raypak’s behalf. THIS WARRANTY IS
IN LIEU OFALLOTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUTNOTLIMITEDTO IMPLIED WARRANTIES OF MERCHANTABIL-
ITYAND FITNESS FORAPARTICULAR PURPOSE. RAYPAK’S SOLE LIABILITYANDTHE SOLE REMEDYAGAINST RAYPAK WITH RESPECT
TO DEFECTIVE PARTS SHALLBEAS PROVIDED IN THIS WARRANTY. ITISAGREED THAT RAYPAK SHALLHAVE NO LIABILITY, WHETHER
UNDERTHIS WARRANTY, OR IN CONTRACT, TORT, NEGLIGENCE OR OTHERWISE, FORANYSPECIAL, CONSEQUENTIAL, OR INCIDENTAL,
DAMAGE, INCLUDING DAMAGE FROM WATER LEAKAGE. Some states do not allow limitations on how long an implied warranty lasts, or
for the exclusion of incidental or consequential damages. So the above limitation or exclusion may not apply to you.
This Limited Warranty gives you specific legal rights. You may also have other rights which may vary from state to state. We suggest that
you complete the information below and retain this certificate in the event warranty service is needed. Reasonable proof of the effective
date of the warranty (date of installation) must be presented, otherwise, the effective date will be based on the date of manufacture plus
thirty (30) days.
_____________________________________________________
Name of Owner
______________________________________________
Name of Installer
_____________________________________________________
Address
______________________________________________
Address
_____________________________________________________
______________________________________________
_____________________________________________________
ModelNo.
______________________________________________
Serial No.
Date of Installation_____________________________________
Date of Initial Operation___________________________
RAYPAK, INC. • 2151 Eastman Avenue • Oxnard, CA 93030 • (805) 278-5300 • Fax (800) 872-9725 • www.raypak.com
P/N:240419
Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 FAX (800) 872-9725
Raypak Canada LTD, 2805 Slough Street, Mississauga, Ontario, Canada L4T 1G2 (905) 677-7999 FAX (905) 677-8036
Litho in U.S.A.
|
Panasonic AK HC1800G User Manual
Panasonic AK HC910 User Manual
Nokia 2118 User Manual
Newcon Optik LASER RANGE FINDER LRB 7X50 SPD User Manual
MB QUART PVL216 User Manual
Lanzar Car Audio HERITAGE HTG 2600D User Manual
Kodak PLAYFULL Ze2 User Manual
Kenwood KRC 108S User Manual
JVC LYT0191 001B User Manual
JVC LYT0110 001A User Manual