Raypak RAYTHERM 962 1826 User Manual

Raytherm® - Type H  
Job:  
Engineer:  
Contractor:  
Prepared By:  
Model:  
Hydronic Heating Boilers  
Commercial  
Date:  
Models 962-1826 (Indoor)  
EFFICIENT  
82% efficiency – highest of any atmospheric  
boiler available today  
THERMAL SHOCK PROOF  
Twenty-year warranty against thermal shock damage  
up to 150°F differential  
Maximum operating temperature: 230°F  
LIGHTWEIGHT  
A floor load of 70 lbs./sq. ft. or less  
HIGH RECOVERY  
Cuts fuel costs substantially because the standby and  
radiation losses normal to other boilers are eliminated  
LOW WATER OPERATING TEMPERATURE  
Operates with inlet water temperature as low as 105°F  
without condensing  
INDOOR  
Heat Exchanger  
Controls (cont.)  
Temperature Controllers  
ƒ
ASME Inspected and Stamped  
160 PSIG  
ƒ
ƒ
Flow Switch  
Economaster Pump Time Delay  
Note: H1 and H5 do not require a  
controller  
ƒ
ƒ
National Board Listed  
Headers  
Glass-lined Cast Iron – Standard  
Bronze – Option A-1  
Finned Tubing  
B-6 Two-stage  
Gas Train  
B-36 TempTracker Mod+ Hybrid  
B-40 Motorized Modulation  
B-41 Motorized Modulation,  
Outdoor Reset  
ƒ
ƒ
ƒ
ƒ
ƒ
Manual Main Gas Shut-off Cock  
Main Gas Pressure Regulator  
Redundant Safety Shut-off Valve  
Control Valve  
ƒ
Copper – Standard  
B-  
Four-stage Digital  
Firing Mode  
Cupro Nickel – Option A-3  
ASME Steel Tube Sheet  
Silicone O-Rings  
60 PSIG ASME Pressure Relief Valve  
Temperature and Pressure Gauge  
Water Connections  
Left Hand – Standard  
Right Hand – Option A-6  
Flow Configuration  
Two-pass – Standard  
Single-pass – Cast Iron Only  
Pump - Rear-mounted, 1/2 HP,  
120 VAC, 1, 60 Hz – Optional  
4.25” Impeller  
Y-241 Electronic Sequencer,  
1-4 Stages  
Y-281 Electronic Sequencer,  
1-8 Stages  
On/off (H4)  
ƒ
ƒ
ƒ
ƒ
ƒ
Two-stage Firing (H3)  
Four-stage Firing (H9)  
Mechanical Modulation,  
110-170°F (H5)  
Mechanical Modulation,  
150-210°F (H1)  
Remote Controller  
By others:  
Additional Safety Controls  
Motorized Modulation (H2)  
Fuel  
Natural Gas  
Propane Gas  
Design Certified ANSI Z21.13/CSA 4.9  
ƒ
ƒ
F-9 Low Water Cut-off Probe  
ƒ
ƒ
I-1  
High Limit Control, Auto  
Reset, 240°F  
S-1 Low Gas Pressure Switch,  
Manual  
S-2 High Gas Pressure Switch,  
Manual  
Construction  
4.7” Impeller  
ƒ
ƒ
ƒ
ƒ
ƒ
AB 1953 & VLA 193 Compliant  
Front Controls  
Stainless Steel Burners  
Polytuf Powder Coat Finish  
Vent Selection  
Controls  
ƒ
ƒ
ƒ
ƒ
120V, 60Hz, 1 Ph Power Supply  
120/24V Transformer  
100% Pilot Shut-off/Lockout  
Electronic, Intermittent Ignition (IID)  
Pilot  
High Limit Control, Manual Reset,  
240°F  
Regulatory Agency Requirements  
Draft Diverter – Option D-10  
Power Vent, Loose – Option D-2  
Base (Optional)  
ƒ
ƒ
ƒ
Combustible Floor Shield –  
Option J-1  
On/Off Switch  
Catalog No.: 2000.24O  
Effective: 04-15-10  
Replaces: 12-01-07  

Plantronics Bluetooth Headset WO200 User Manual
Plantronics Bluetooth Headset 370 User Manual
NEC MultiSync LCD1860NX User Manual
Metra Electronics 95 7318 User Manual
Magic Chef EWWC2SI User Manual
Lochinvar Knight XL KB 399 thru 800 User Manual
Kompernass KH498 08 V1 User Manual
Kodak IMAGE SENSOR KAI 02150 User Manual
Kenwood KDC BT51U User Manual
Kenwood KDC 6060R User Manual