INSTALLATION AND OPERATING
INSTRUCTIONS
COLD WATER START & COLD WATER RUN
For Hi Delta & MVB
Heaters & Boilers
This manual should be maintained in legible condition and kept adjacent to the heater or in another safe place
for future reference.
Catalog No: 1000.57A
Effective: 02-28-07
Replaces: 02-24-06
P/N 241275 Rev. 2
GENERAL SAFETY
To meet commercial hot water use needs, the high
limit safety control on this water heater is adjustable up
to 210°F. However, water temperatures over 125°F
can cause instant severe burns or death from scalds.
When supplying general purpose hot water, the rec-
ommended initial setting for the temperature control is
125°F.
Safety and energy conservation are factors to be con-
sidered when setting the water temperature on the
thermostat. The most energy-efficient operation will
result when the temperature setting is the lowest that
satisfies the needs of the application.
Water temperature over 125°F can
causeinstantsevereburnsordeath
from scalds.
Children, disabled, and elderly are
at highest risk of being scalded.
Water temperature over 125°F can cause instant
severe burns or death from scalds. Children, disabled
and elderly are at highest risk of being scalded.
See instruction manual before set-
ting temperature at water heater.
Feel water before bathing or show-
ering.
•
•
Feel water before bathing or showering.
Temperature limiting valves are available.
Temperature limiting valves are
available, see manual.
NOTE: When this water heater is supplying general
purpose hot water for use by individuals, a thermo-
statically controlled mixing valve for reducing point of
use water temperature is recommended to reduce
the risk of scald injury. Contact a licensed plumber or
the local plumbing authority for further information.
Time/Temperature
Relationships in Scalds
The following chart details the relationship of water
temperature and time with regard to scald injury and
may be used as a guide in determining the safest
water temperature for your applications.
Maximum water temperatures occur just after the
heater’s burner has shut off. To determine the water
temperature being delivered, turn on a hot water
faucet and place a thermometer in the hot water
stream and read the thermometer.
Water
Temp.
Time to Produce
Serious Burn
120°F
125°F
130°F
135°F
140°F
145°F
150°F
155°F
More than 5 minutes
1-1/2 to 2 minutes
About 30 seconds
About 10 seconds
Less than 5 seconds
Less than 3 seconds
About 1-1/2 seconds
About 1 second
Table courtesy of The Shriners Burn Institute
Table A: Time to Produce Serious Burn
3
COLD WATER START
Before arriving at the job site to begin the installation,
it's important to first inspect the system and determine
what materials you will need. Some parts are includ-
ed with the controller while others you will need to
provide.
1 Control Box
1 Temperature Sensor
1 Valve assembly with actuator (Shipped separately)
Wiring and mounting hardware (Provided by installer)
INSTALLATION
Check the Power Source
Fig. 2: Multi-meter
CAUTION: Do not use for swimming pool applica-
tions
so as to provide maximum support by using the
mounting holes provided on the base of the controller
to the side center brace on the heater. You will need to
drill mounting holes and holes through the heater side
panel for the routing of wiring and the sensor. A tem-
plate is supplied for field-installed kits to locate the
control box properly.
WARNING: Using a multi-meter, check the follow-
ing voltages at the circuit breaker panel prior to con-
necting any equipment. Make sure proper polarity is
followed and house ground is proven.
Attaching the Temperature
Sensor
BLACK
CIRCUIT
BREAKER
WHITE
Avoid routing wiring on or near other electrical wires,
conduit, motors, spark igniters or other sources of
high, intermittent voltage or current. The sensor should
be placed in the dry well on the inlet header. Ensure it
is installed using thermopaste (field supplied) and it is
held firmly at the bottom of the well.
GREEN
GROUND
Connecting the Valve
Assembly
A
B
C
Fig. 1: Wiring Connections
Connect valve assembly “T CONNECTION “ into the
piping with the actuator input wiring facing the heater
side panel, as shown below. Route wiring to the con-
trol thru the bottom panel knockouts to TB2. Refer to
the wiring diagram provided on the inside of control
cover assembly.
Check the power source:
AC = 108 VAC Minimum, 132 VAC MAX
AB = 108 VAC Minimum, 132 VAC MAX
BC = <1 VAC Maximum
Mounting the Control Box
NOTE: Four knockouts are located on the bottom
of the control for ease of installation.
The control box should be mounted on the side of the
heater to which the system piping and valve assembly
are to be attached. The controller should be mounted
4
NOTE: If a “DIP” switch is provided on the control
PCB, verify that the switch settings are correct: 1 =
OFF, 2 = ON, 3 = OFF.
OPERATION
Verify the following upon a CALL FOR HEAT signal
from the heater:
1. CALL FOR HEAT LED on PCB illuminates GREEN.
2. START UP MODE LED on PCB illuminates YEL-
LOW. Before 7 minutes it should go out if boiler
inlet temperature is approaching the set point tem-
perature.
Models
X
CALL FOR HEAT
START UP MODE
302B-902B
7.0″
INLET TEMP ERROR
SENSOR OUT OF RANGE
992B-2342B 13.20″
LEFT SIDE
Fig. 3: Component Locations — Hi Delta
Connecting Power to the
Controller
Set
Point
Pot
Supply power from the 120 VAC power input from the
heater to the controller power inputs Terminal Block
(TB1). This is accomplished by connecting wiring from
the control box to the heater TB1 board 120 VAC
power input connections. Refer to wiring diagrams.
Fig. 5: Control PCB
3. The “ACTUATOR” should be in the fully open posi-
tion or move to the fully open position if not already
there. (Actuator at the fully CCW position)
4. Before 7 minutes time has elapsed if the control is
operating properly the “START UP MODE” LED
should go out. The inlet water temperature should
be stable at a temperature between 105° F and
120° F (Normally set to 110° F) cooresponding to
the Set Point Pot setting on the PCB. The actuator
should have stopped moving.
Reset Switch
Fig. 4: Location of TB1 in Control Box
5
16) Once the NO contacts of the DPST close, the
heater 24 VAC is sent back to the heater to com-
plete the Economaster circuit (pin 3 of terminal
block 3) and the interlock circuit (pin 1 of terminal
block 3) allowing the heater to fire.
NOTE: The minimum return water temperature to
the heater to prevent condensate is 105°F on stan-
dard heaters and 120°F on 87% Efficiency heaters.
Ensure that during operation the Set Point Pot is
adjusted properly.
17) Pin FR on the TVC board outputs 10VDC to the
modulating three way valve actuator to drive it fully
open for two-minutes waiting for the heater to
reach full fire.
Cold Start Sequence of
Operation
18) After the two-minute delay the 10VDC output sig-
nal from pin FR reduces to approximately 8VDC at
the inverter thus slowing the pump to approxi-
mately 50 Hz.
1) 120VAC to heater sends 120VAC to Cold Start
control on terminal block 1.
19) The output signal continues to vary depending on
the heater inlet temperature.
2) 120/24VAC transformer and 120VAC-12VDC con-
verter are powered.
3) 120/24VAC transformer outputs 24VAC to pin 2 of
terminal block 2
The heater will lockout and shut down if the set point
on the inlet temperature is not achieved within seven-
minutes from a call for heat.
4) 24VAC leaves pin 2 of terminal block 2 and goes
to the modulating three way valve on the 20-
30VAC lead, and to the NO contacts of the SPST
relay located in the cold start control panel.
The DIP switches on the 3-way valve actuator must be
set as indicated in the Fig. 6.
5) 120VAC-12VDC converter outputs 12VDC to pin 3
of terminal block 2.
6) The 12VDC signal leaves pin 2 of terminal block 2
and goes to the common terminal of the reset
switch, located on the bottom of the cold start con-
trol panel.
MODE SELECTION SWITCH
DIRECT ACTING, ON INCREASING SIGNAL
DIP SWITCH SETTINGS
FOR 3-WAY ACTUATOR
7) The 12VDC signal crosses over the reset switch
and goes to Pin FS on cold start circuit board.
VDC
0-10
DA
mA
2-10
RA
8) Cold start control remains on standby until a Call
for heat occurs at heater.
FIXED
~
AUTO
6-9
9) TRIG terminal of Economaster connection on
heater CPW board outputs 24VAC to terminal 4 of
terminal block 3 located in Cold Start controller.
SWITCH MUST BE IN THIS POSITION
TURN CLOCKWISE TO FURTHEST STOP
10) Terminal 4 of TB 3 sends 24VAC to the coil of the
SPST relay located in the cold start control panel.
Fig. 6: Set Dip Switch Settings — Delta Actuator
11) The SPST relay coil is energized and closes the
contacts allowing 24VAC to energize the CFH pin
on the cold start circuit board.
a) A two second delay occurs from the CFH signal
waiting to send power from terminal MC of the cold
start circuit board.
12) J9 terminal on the heater CPW board (interlock
connection) outputs a 24 VAC signal to terminal 2
of terminal block 3 located in the cold start con-
troller.
13) 24 VAC is sent from terminal 2 of terminal block 3
to the NO contacts of the DPST relay located in
the cold start control panel.
14) After the two second delay on the cold start circuit
board, pin MC outputs a 24 VAC signal to the coil
of the DPST relay located in the cold start control
panel.
15) The DPST relay coil energizes and closes the NO
contacts.
Fig. 7: Delta Actuator — Actuator Shown in Full System
Flow Position
6
TROUBLESHOOTING
Check your power source using a Volt-Ohm meter;
check the following voltages at TB1 terminal block:
TB1-1 to TB1-2 = 108 VAC Minimum, 132 VAC
Maximum
TB1-1 to TB1-3 = 108 VAC Minimum, 132 VAC
Maximum
TB1-2 to TB1-3 = Must be less than .6 VAC
IF CALL FOR HEAT LED does not illuminate when the
heater has a CFH signal, check for 24VAC at the
heater CPW Board (J17-TRIG) output. If voltage is
present, check wiring using the wiring diagram. If volt-
age is not present, the problem exists in the heater.
IF VALVE DOES NOT MOVE: Check for voltage out at
TB2-1: Should be a 1VDC to 10VDC output to the
actuator valve. If no voltage is present, check for volt-
age at TB2-3, there should be a 12VDC signal. If the
12VDC signal is not present, verify that the converter
is wired correctly using the wiring diagram.
Fig. 8: Elodrive Actuator — Rotation Knob Setting
IF SENSOR OUT OF RANGE LED is illuminated: The
set point temperature has not been reached within the
7 minute time period.
•
Push the Reset Switch (see Fig. 4) or remove
power and watch for proper operation.
•
Check pump sizing and valve/piping sizing and cor-
rect as necessary.
•
•
Replace sensor.
Check wiring using wiring diagram.
Fig. 9: Elodrive Actuator — Actuator Shown in Full
System Flow Position
NOTE: Elodrive actuator is Nema 4 rated.
7
Cold Water Start Troubleshooting Guide
8
Wiring Diagram
9
Installation Codes
COLD WATER RUN
Installations must be in accordance with local, state,
provincial, and national codes, laws, regulations and
ordinances. In the absence of local codes, installa-
tions must be in accordance with the latest editions of
the:
Purpose
The Cold Water Run system utilizes a variable-speed
pump to inject the proper amount of water from the
main system loop into the boiler to maintain the opti-
mum inlet temperature. This approach allows the full
capacity of the boiler to be utilized to meet the system
load, while at the same time continuously maintaining
the optimum inlet water temperature to prevent con-
densation.
•
•
•
National Fuel Gas Code, ANSI Z223.1/NFPA 54
National Electrical Code, ANSI/NFPA 70
For Canada only: CAN/CGA B149.1 installation
Code (B149.1) and CSA C22.1 C.E.C. Part 1 and
Part 2
Mounting the Control Box
Typical Cold Water Run
Applications
NOTE: The heater should not be located in an area
where possible water leakage will result in damage
to the area adjacent to the heater or to the structure.
When such locations cannot be avoided, it is rec-
ommended that a suitable drain pan, with adequate
drainage, be installed under the heater. The pan
must not restrict combustion air flow.
•
•
•
•
•
Swimming pools.
Snow melting.
Low temperature radiant panel.
Water source heat pumps.
The control box should be mounted on the side of the
heater to which the system piping and pump assem-
blies are to be attached. The controller should be
mounted so as to provide maximum support by using
the mounting holes provided on the base of the con-
troller to the side center brace on the heater. You will
need to drill mounting holes and holes through the
heater side panel for the routing of wiring and the sen-
sor. A template is supplied for field-installed kits to
locate the control box properly.
Any system with steady state return water temper-
ature below 105°F.
CWR vs. CWS
•
•
•
Cold water start is for transient cold water opera-
tion.
Cold water run is for continuous operation below
105°F system return temperature.
Cold water start maintains design flow rate at sys-
tem design temperature but reduces bolier flow
rate during heavy by-pass operation.
CAUTION: Remote mounted controller must be
installed within 25 feet of the heater.
•
Cold water run maintains constant design flow rate
in the boiler.
Indoor and Outdoor
Installations
INSTALLATION
The cold water run control panel is rated for indoor use
only. Do not mount or install the control panel in areas
where dripping, flooding, rain, snow or spraying water
may come in contact with the enclosure. If the injection
pump is located outdoors, the optional outdoor cover
must be installed according to the instructions in the
following section. For outdoor installations mount the
control panel indoors and route the wiring to the appro-
priate connection points. Wire length is not to exceed
25 feet in any one direction. Contact your local sales
representative for further information.
Before arriving at the job site to begin the installation,
it's important to first inspect the system and determine
what materials you will need. Some parts are includ-
ed with the controller while others you will need to
provide.
10
Injection & Heater Pump Comparison — Hi Delta
Heater Pump
Injection Pump
Flow Temp. Rise
13 40
Heater
Model
Injection
Pump
Flow
Temp. Rise Press. Drop
Heater Pump
302
402
502
652
752
902
992
32
34
42
55
63
76
83
16
20
20
20
20
20
20
2
1911-1⁄4 hp
1911-1⁄4 hp
1911-1⁄4 hp
1911-1⁄4 hp
1911-1⁄4 hp
1911-1⁄4 hp
1911-1⁄4 hp
112
2
17
22
28
32
38
42
40
40
40
40
40
40
112
2.3
4.1
5.7
8.4
5.2
1630 4.0
1630 4.0
1630 4.2
1630 4.2
1630 4.7
1262
1532
1802
107
120
120
20
22
25
9.6
12.4
13
54
62
68
40
42
45
1911-1⁄3hp
1911-1⁄3hp
1911-1⁄3hp
1630 4.7
1632 5.6
1632 5.6
2002
2072
2342
132
132
132
26
27
30
19
19
74
75
80
46
47
50
1935-3⁄4hp
1935-3⁄4hp
1935-3⁄4hp
1634 6.1
1634 6.1
1634 6.1
21.4
Table B: Injection and heater pump specifications
Check the power source:
Check the Power Source
AC = 108 VAC Minimum, 132 VAC MAX
AB = 198 VAC Minimum, 250 VAC MAX
BC = 108-132 VAC Maximum
WARNING: Using a multi-meter, check the follow-
ing voltages at the circuit breaker panel prior to con-
necting any equipment. Make sure proper polarity is
followed and house ground is proven.
BLACK
CIRCUIT
BREAKER
WHITE
GREEN
GROUND
A
B
C
Fig. 11: Multi-meter
Fig. 10: Wiring Connections
11
Injection Pump Cover
Installation
Before Starting
1) Turn off power to the unit at the circuit breaker.
2) Turn off gas supply.
3) Shut off the water supply to the heater and, if nec-
essary, drain water from the system.
4) Allow heater to cool down before attempting work.
In order to install the pump cover, you will need to
rotate the pump body so that the electrical box is point-
ing downward, as outlined in the following steps:
1. Loosen and remove the eight (8) 9/16” wrench
bolts holding the pump body in place. See Fig. 12.
Fig. 13: Remove the pump body
Fig. 12: Remove the eight bolts holding the pump body
in place
2. Remove the pump body then rotate it so that the
electrical box is pointing downward, ensuring not
to damage the seal. See Fig. 13, 14 and 15.
Fig. 14: Be sure not to damage the seal when removing
or replacing the pump body
12
Fig 17: Pump cover - angle view
Fig 15: Reposition the pump body so that the electrical
box points downward
3. Insert and tighten all eight (8) wrench bolts, secur-
ing the pump body in place.
4. You will now be able to install the pump cover. See
Fig. 18 and 19.
Fig. 16: Place the cover on the pump
13
Typical Boiler Piping (Hi Delta shown)
14
the cold run control panel.
START-UP PROCEDURE
8) After the two second delay on the cold run circuit
board, pin MC outputs a 24 VAC signal to terminal
AL0 of the Hitachi inverter.
9) The AL0 relay closes and outputs a 24 VAC signal
to the coil of the DPST relay located in the cold run
control panel.
•
•
Run full system flow for two minutes.
Initiate PID pump control to achieve target inlet
temperature by slowing injector pump.
•
•
Boiler ΔT will not increase during bypass operation.
10) The DPST relay coil energizes and closes the NO
contacts.
If target temperature is not achieved after seven
minutes from “call for heat”, the system will shut
down.
11) Once the NO contacts of the DPST close, the
heater 24 VAC is sent back to the heater to com-
plete the Economaster circuit (pin 3 of terminal
block 3) and the interlock circuit (pin 1 of terminal
block 3) allowing the heater to fire.
12) Pin SC of the cold run circuit board sends 24VAC
to Pin 1 (Forward) on Hitachi Inverter.
13) PCS terminal on Inverter outputs 12VDC signal to
the common terminal of the reset switch located
on the bottom of the cold run control panel.
14) The 12VDC signal crosses over the reset switch
and goes to Pin FS on cold run circuit board.
15) 12VDC on pin FS is jumpered to pin S1 on the
cold run circuit board.
16) Pin FR on the TVC board outputs 10VDC to the
Inverter to drive injector pump at full speed two-
minutes waiting for the heater to reach full fire.
17) After the two-minute delay the 10VDC output sig-
nal from pin FR reduces to approximately 8VDC at
the inverter thus slowing the pump to approxi-
mately 50 Hz.
18) The output signal continues to vary depending on
the heater inlet temperature.
Fig. 18: Control Board
Sequence of Operation
The heater will lockout and shut down if the set point
on the inlet temperature is not achieved within seven-
minutes from a call for heat.
1) Supply separate 220VAC, 1 Ø, 60 Hz power to
Cold Run control.
The DIP switches on the Hitachi Inverter must be set
as indicated on Fig. 19 below.
2) Call for heat occurs at heater.
3) TRIG terminal of Economaster connection on
heater CPW board outputs 24VAC to terminal 4 of
terminal block 3 located in Cold Run controller.
4) Terminal 4 of TB 3 sends 24VAC to the coil of the
SPST relay located in the cold run control panel.
5) The SPST relay coil is energized and closes the
contacts allowing 24VAC from the Cold Run con-
trol transformer to be sent to the CFH terminal of
the Cold Run circuit board.
a) A two second delay occurs from the CFH signal
waiting to send power from terminal MC of the cold
run circuit board.
6) J9 terminal on the heater CPW board (interlock
connection) outputs a 24 VAC signal to terminal 2
of terminal block 3 located in the cold run con-
troller.
Fig. 19: DIP Switch Settings
7) 24 VAC is sent from terminal 2 of terminal block 3
to the NO contacts of the DPST relay located in
15
Wiring Diagram
16
Cold Water Run Troubleshooting Guide
Does TB1 of cold run
controller have 120
VAC?
Verify 120VAC from
TB1 on the heater
and correct
NO
Step 1
Is there a Call For
Heat at the heater?
YES
YES
Heater is in standby mode
NO
Is the 220VAC inverter in the
cold run controller powered?
Correct Wiring
Step 2
Step 3
Step 4
Step 5
NO
YES
Does the cold run inverter output
12VDC from PCS to pin FS?
Replace inverter or install jumper
and correct switch settings
NO
YES
Is 24VAC present at Poolstat
connection on cold run circuit
board?
Check 24VAC output at J17 of
heater circuit board and correct
NO
YES
Does cold run relay K-6
coil receive 24VAC from
MC on circuit board?
Replace circuit board
NO
Call our Technical Service Department
1-800-927-2975 Outside California
1-800-627-2975 Inside California
YES
Are the Economaster and
Interlock leads connected to
N.O. contacts of relay K-6?
YES
Step 6
Step 7
NO
Correct wiring
Is sensor resistance correct?
NO
YES
Replace sensor
Correct wiring
Correct 3Ø pump wiring
Are the Economaster
and Interlock leads
connected correctly to
heater CPW board?
NO
NO
Verify pump is rotating in proper
direction
YES
YES
Is the injector pump
modulating after 2-1/2
Is the heater tripping the high
limit?
Pump must decrease
RPM’s on decreasing 0-
YES
Step 8
Step 9
YES
10VDC signal
NO
NO
The unit is okay
Is 0-10VDC present at
connection FR of cold run circuit
board?
NO
Replace cold run circuit board
NO
Step 10
Does cold run circuit board lock-out on
“Sensor out of Range”?
YES
YES
17
ILLUSTRATED PARTS LISTS
Cold Water Start
18
2-M
1-M
3-M
4-M
CALL OUT
1-C
DESCRIPTION
HI DELTA
011717F
011718F
011719F
011720F
009039F
007155F
010787F
005641F
007226F
007232F
N/A
MVB
PC BOARD ASSY-CONTROL
TRANSFORMER
011717F
011718F
011719F
011720F
009039F
007155F
010787F
005641F
007226F
007232F
007347F
007353F
007348F
007354F
007348F
007354F
007937F
007938F
011939F
011721F
011722F
011723F
011724F
011834F
000919
2-C
3-C
4-C
5-C
6-C
7-C
8-C
1-M
POWER SUPPLY 120VAC/12VDC
RELAY-DPDT 24V
RELAY-SPDT 24V
GROUND LUG
TEMP SENSOR 10K (NOT SHOWN)
RESET SWITCH
PUMP-WATER BR 2" FLANGE, 1/4 HP
PUMP-WATER CI 2" FLANGE, 1/4 HP
PUMP-WATER BR 2" FLANGE, 1/2 HP
PUMP-WATER CI 2" FLANGE, 1/2 HP
PUMP-WATER BR 2-1/2" FLANGE, 3/4 HP
PUMP-WATER CI 2-1/2" FLANGE, 3/4 HP
PUMP-WATER BR 2-1/2" FLANGE, 1 HP
PUMP-WATER CI 2-1/2" FLANGE, 1 HP
PUMP-WATER BR 2-1/2" FLANGE, 1.5 HP
PUMP-WATER CI 2-1/2" FLANGE, 1.5 HP
3-WAY VALVE 2 NPT 24 Cv
N/A
007348F
007354F
007348F
007354F
N/A
N/A
2-M
011939F
011721F
011722F
011723F
011724F
011834F
000919
011716F
N/A
3-WAY VALVE 2 NPT 38 Cv
3-WAY VALVE 2 NPT 57 Cv
3-WAY VALVE 2-1/2 NPT 74 Cv
3-WAY VALVE 2-1/2 NPT 100 Cv
ACTUATOR
3-M
4-M
1-S
2-S
THERMOMETER-VERTICAL
CONTROL BOX SHEET METAL
CONTROL BOX COVER
011716F
011978F
NOTE: Sizing is specific to this application.
19
Cold Water Run
20
CALL
OUT
DESCRIPTION
PC BOARD ASSY-CONTROL
HI DELTA
MVB
1-C
2-C
3-C
4-C
011717F
011720F
009039F
011835F
011836F
011718F
010787F
005641F
007226F
007232F
007348F
007354F
007351F
007357F
000919
951414
951415
951394
951413
951411
011717F
011720F
009039F
011835F
011836F
011718F
010787F
005641F
007226F
007232F
007348F
007354F
007351F
007357F
000919
N/A
RELAY-DPDT 24VAC
RELAY-SPDT 24VAC
INVERTER-1/2 HP
INVERTER-1 HP
5-C
6-C
7-C
1-M
TRANSFORMER-115/230 VAC
TEMPERATURE SENSOR 10K (NOT SHOWN)
ALARM RESET SWITCH
PUMP-WATER BR 2" FLANGE, 1/4 HP
PUMP-WATER CI 2" FLANGE, 1/4 HP
PUMP-WATER BR 2-1/2" FLANGE, 3/4 HP
PUMP-WATER CI 2-1/2" FLANGE, 3/4 HP
PUMP-WATER BR 2-1/2" FLANGE, 1 HP
PUMP-WATER CI 2-1/2" FLANGE, 1 HP
THERMOMETER-VERTICAL
2-M
3-M
INJECTOR PUMP, BR 302B-902B (NOT SHOWN)
INJECTOR PUMP, CI 302B-902B (NOT SHOWN)
INJECTOR PUMP, BR 992B-1802B (NOT SHOWN)
INJECTOR PUMP, CI 992B-1802B (NOT SHOWN)
INJECTOR PUMP, BR 2002B-2342B (NOT SHOWN)
INJECTOR PUMP, CI 2002B-2342B (NOT SHOWN)
CONTROL BOX SHEET METAL
N/A
N/A
N/A
N/A
951416
011716F
N/A
N/A
1-S
2-S
011716F
011978F
CONTROL BOX COVER
NOTE: Sizing is specific to this application.
21
Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468
Raypak Canada Limited, 2805 Slough St., Mississauga, Ontario, Canada L4T 1G2 (905) 677-7999 Fax (905) 677-8036
Litho in U.S.A.
|