Lochinvar 1 User Manual

SYNC-SER Rev H  
Service Manual  
Models: 1.0, 1.3, and 1.5  
This manual must only be  
used by a qualified heating  
installer / service technician.  
ƽ WARNING  
Read  
all  
instructions,  
including this manual and  
the SYNC Installation and  
Operation Manual, before  
installing. Perform steps in  
the order given. Failure to  
comply could result in severe  
personal injury, death, or  
substantial property damage.  
Save this manual for future reference.  
Service Manual  
Handling ceramic fiber materials  
REMOVAL OF COMBUSTION CHAMBER LINING  
The combustion chamber insulation in this appliance contains ceramic fiber material. Ceramic fibers can  
be converted to cristobalite in very high temperature applications. The International Agency for Research  
on Cancer (IARC) has concluded, “Crystalline silica in the form of quartz or cristobalite from occupational  
sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this appliance are below  
the level to convert ceramic fibers to cristobalite. Abnormal operating conditions would have to be created  
to convert the ceramic fibers in this appliance to cristobalite.  
ƽ WARNING  
The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic  
materials it is advisable that the installer follow these safety guidelines.  
Avoid breathing dust and contact with skin and eyes.  
• Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA  
requirements for cristobalite at the time this document was written. Other types of respirators may  
be needed depending on the job site conditions. Current NIOSH recommendations can be found on  
manufacturers, and phone numbers are also listed on this website.  
• Wear long-sleeved, loose fitting clothing, gloves, and eye protection.  
Apply enough water to the combustion chamber lining to prevent airborne dust.  
Remove the combustion chamber lining from the appliance and place it in a plastic bag for disposal.  
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer  
thoroughly.  
NIOSH stated First Aid.  
Eye: Irrigate immediately.  
Breathing: Fresh air.  
Boiler water –  
When servicing boiler –  
• Thoroughly flush the system (without boiler  
connected) to remove sediment. The high-efficiency  
heat exchanger can be damaged by build-up or  
corrosion due to sediment.  
• To avoid electric shock, disconnect electrical supply  
before performing maintenance.  
• To avoid severe burns, allow boiler to cool before  
performing maintenance.  
• Do not use petroleum-based cleaning or sealing  
compounds in the boiler system. Gaskets and seals in  
the system may be damaged. This can result in  
substantial property damage.  
Boiler operation –  
• Do not block flow of combustion or ventilation air to  
the boiler.  
• Do not use “homemade cures” or “boiler patent  
medicines”. Serious damage to the boiler, personnel,  
and/or property may result.  
• Should overheating occur or gas supply fail to shut  
off, do not turn off or disconnect electrical supply to  
circulator. Instead, shut off the gas supply at a  
location external to the appliance.  
• Continual fresh make-up water will reduce boiler  
life. Mineral buildup in the heat exchanger reduces  
heat transfer, overheats the stainless steel heat  
exchanger, and causes failure. Addition of oxygen  
carried in by makeup water can cause internal  
corrosion. Leaks in boiler piping must be repaired at  
once to prevent the introduction of makeup water.  
• Do not use this boiler if any part has been under  
water. The possible damage to a flooded appliance  
can be extensive and present numerous safety  
hazards. Any appliance that has been under water  
must be replaced.  
Freeze protection fluids –  
• NEVER use automotive antifreeze.  
Use only  
inhibited propylene glycol solutions which are  
specifically formulated for hydronic systems.  
Ethylene glycol is toxic and can attack gaskets and  
seals used in hydronic systems.  
3
Service Manual  
What is in this manual?  
Service  
Maintenance  
• Service and maintenance schedules  
• Address reported problems  
• Inspect boiler area and boiler interior  
• Clean condensate trap  
• Check all piping for leaks  
• Check air openings  
Near boiler piping  
• Typical system components  
The SMART TOUCH display  
• Touch screen readout, buttons and their functions  
• Flue vent system and air piping  
• Check water system  
• Check expansion tank  
Control module inputs  
• Control module inputs and options  
• Check boiler relief valve  
• Inspect ignition electrode  
• Check ignition ground wiring  
• Check all boiler wiring  
• Check control settings  
• Perform start-up and checks  
• Check burner flame  
• Check flame signal  
• Check flue gas temperature  
• General maintenance  
Control module outputs  
• Control module outputs and options  
General  
• How the boiler operates  
• How the control module operates  
• Access modes -- user and installer  
• Sequence of operation -- Hot Water Generation  
(HW)/space heating  
• Review with owner  
Control panel menu access  
• Cleaning boiler heat exchanger  
• Oiled bearing circulators  
A c c e s s i n g  
p r o g r a m m i n g  
mode and locating menus  
(See separate guides covering the PC interface.)  
Troubleshooting  
Control panel parameter access  
• Troubleshooting table - No display  
• Checking temperature sensors  
• Sensor tables  
• Accessing and changing parameters from the touch screen  
Quick start information -- parameter  
table  
• Troubleshooting table - Fault messages displayed on  
boiler interface  
• Combustion analysis procedure  
• Gas valve adjustment procedure  
• An index of available adjustments and readouts, where to  
access them and where to find detailed information.  
SYNC operation  
• Service / Setup  
• Set Points  
• Outdoor Reset  
• Night Setback  
• Cascade  
• Pumps  
• BMS  
4
Service Manual  
1 Service  
Near boiler piping  
This piping reference is included to specify the Near Boiler Piping specific to the SYNC. This piping scheme is important for  
proper operation of the SMART TOUCH control module. See the SYNC Installation and Operation Manual for more detailed  
piping diagrams.  
DRAIN (TYPICAL)  
SYSTEM SUPPLY SENSOR  
(NOTICE: A SYSTEM SUPPLY  
SENSOR MUST BE INSTALLED FOR  
PROPER BOILER OPERATION.)  
SYSTEM PUMP  
ISOLATION VALVE  
(TYPICAL)  
Y-STRAINER  
(RECOMMENDED)  
(TYPICAL)  
TEMPERATURE GAUGE  
HEAT EXCHANGER 1  
BOILER PUMP  
RELIEF VALVE  
HEAT EXCHANGER 2  
BOILER PUMP  
TO FLOOR DRAIN  
CHECK VALVE  
(TYPICAL)  
5
Service Manual  
1 Service  
The SYNC display  
6
Service Manual  
1 Service  
(continued)  
Control inputs  
SECONDARY  
SMART CONTROL  
MODULE  
LOW VOLTAGE  
CONNECTION  
BOARD  
PRIMARY  
SMART CONTROL  
MODULE  
SEQUENCER / BUILDING  
MANAGMENT SYSTEM  
O-TEMP  
OUTDOOR SENSOR  
HEAT EXCHANGER SWITCH  
HW TANK SENSOR  
SYSTEM SENSOR  
PRIMARY/SECONDARY INLET  
TEMPERATURE SENSOR  
O-TEMP  
HEAT EXCHANGER SWITCH  
PRIMARY/SECONDARY OUTLET  
TEMPERATURE SENSOR  
FLOW SWITCH  
BLOCKED DRAIN SWITCH  
HW THERMOSTAT  
PRIMARY/SECONDARY  
FLUE GAS SENSOR  
ROOM THERMOSTAT /  
ZONE CONTROL  
LOW WATER CUTOFF  
TOUCH PANEL  
PRIMARY/SECONDARY  
GAS PRESSURE SWITCH  
INTERFACE  
TOUCH DISPLAY  
PRIMARY/SECONDARY  
HIGH LIMIT SENSOR  
PRIMARY/SECONDARY  
FLAME SENSOR  
MODBUS COMMUNICATION  
BOARD  
PC INTERFACE  
IMG00004  
7
Service Manual  
1 Service  
Control outputs  
SECONDARY  
SMART TOUCH  
LOW VOLTAGE  
CONNECTION  
BOARD  
CONTROL MODULE  
PRIMARY  
SMART TOUCH  
CONTROL MODULE  
ALARM BELL  
RUN TIME CONTACTS  
HEAT EXCHANGER 1 /  
HEAT EXCHANGER 2  
BOILER PUMP  
SEQUENCER / BUILDING  
MANAGEMENT SYSTEM  
SYSTEM PUMP  
TOUCH PANEL  
HW PUMP  
IGNITOR  
TOUCH DISPLAY  
INTERFACE  
PC INTERFACE  
BLOWER  
GAS VALVE  
8
Service Manual  
1 Service  
(continued)  
General Operation  
How the boiler operates  
Access modes  
The SYNC uses two (2) advanced stainless steel heat User  
exchangers and two (2) electronic control modules that allow  
fully condensing operation. The blowers pull in gas and air The user can view all of the settings on the LCD screen. By  
and push flue products out of the boiler through the heat entering the user password (0704), the user can adjust the  
exchangers and flue piping. The control modules regulate User Set Point, Outdoor Shutdown, Night Setback, Boost,  
blower speeds to control total boiler firing rate. The gas HW Boiler Output Set Point, Backlight Time, and Backlight  
valves sense the amount of air flowing into the boiler and Brightness settings.  
allow only the right amount of gas to flow.  
Installer  
How the control module operates  
Most parameters are available only to the installer, accessible  
only by entering the installer access code (5309).  
The SYNC control modules receive input from boiler sensors.  
The control modules activate and control the blower and  
gas valves to regulate heat input and switches boiler, Hot  
Water Generation (HW) and system pumps on and off as  
needed. The user/installer programs the control module to  
meet system needs by adjusting control parameters. These  
parameters set operating temperatures and boiler operating  
modes.  
Sequence of operation  
Table 1A shows control module normal sequences of  
operation for space heating and HW operation for each  
individual control module. Additionally, the control  
modules are programmed to synchronize their combined  
modulation rates in order to maximize total boiler efficiency.  
The combined operation sequence is for a typical application,  
programmed to provide HW priority.  
9
Service Manual  
1 Service  
Sequence of operation  
Table 1A Sequence of operation - space heating and HW  
Note: This unit is equipped with two (2) independent, but synchronized combustion systems. Heat Exchanger 1 (top)  
combustion system will fire first. If the demand cannot be met by one (1) combustion system the same sequence of operation  
will be followed to bring the Heat Exchanger 2 combustion system online.  
Upon a call for heat, the control turns on the appropriate pumps (system and boiler pumps for a space heating call,  
HW pump relay output for a HW call).  
1.  
The control confirms that the low water cutoff and flow switch (optional) contacts are closed.  
2.  
The control starts the blower and closes the louver contacts to begin the Pre-Purge cycle.  
3.  
The control confirms that the blower comes up to the desired speed, the flap valve opens, and the air pressure switch,  
gas pressure switches, louver proving switch (field installed), and blocked drain switch contacts close.  
4.  
Once the Pre-Purge cycle is complete, the control lowers the blower speed, initiates sparking of the ignition electrode,  
and opens the gas valve.  
5.  
After a short wait, the control stops sparking and checks for the presence of flame current through the spark and  
flame sense electrodes.  
6.  
If the control does not detect flame current, the control will lockout, until the RESET button on the touch screen  
LCD is pressed.  
7.  
If the control detects flame current, the control will hold the blower speed constant for a few seconds to allow the  
flame to stabilize, then begin modulating the firing rate in order to maintain the controlling sensor to the desired set  
point temperature.  
8.  
If the current call for heat is for space heating and a HW call for heat becomes active, the control will turn on the HW  
pump relay output, then turn off the boiler pumps. It will then modulate the blower speed in order to maintain the  
outlet temperature to the desired HW outlet set point temperature.  
9.  
If the first heat exchanger in the boiler is unable to maintain the desired set point temperature, the second heat  
exchanger in the boiler will be started, using much of the same sequences as described above. Once both heat  
exchangers are firing, the controls will work in synchronization to maintain the desired set point temperature. If  
the heat load should decrease sufficiently, the second heat exchanger will be shut down, much like the sequences  
described below.  
10.  
Once both the space heating and HW calls for heat are satisfied, the control will turn off the gas valve and begin the  
Post-Purge cycle. Any pumps that are running will begin their respective Pump Delay cycles.  
11.  
At the end of the Post-Purge cycle, the louver contacts will open.  
12.  
The control verifies that the blower stops running and the flap valve closes.  
13.  
At the end of the Pump Delay cycle(s), the pumps will be turned off.  
14.  
10  
Service Manual  
1 Service  
(continued)  
Parameter table  
Table 1B This table lists the parameters and where to access them  
USER ACCESS  
INSTALLER ACCESS  
SEE  
MENU  
DESCRIPTION  
PAGE  
DISPLAY  
MODIFY  
Yes  
DISPLAY  
MODIFY  
Yes  
Service/Setup  
18  
18  
18  
18  
18  
18  
18  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Night Setback  
Set points  
Cascade  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Outdoor Reset  
Pumps  
Yes  
Yes  
Yes  
Yes  
BMS  
Yes  
Yes  
Demand Conf  
Serv Not Time  
Serv Not Run H  
Serv Not Cycl  
Ramp Delay  
Max Serv T  
19  
19  
19  
19  
19  
20  
20  
20  
20  
20  
Yes  
No  
No  
No  
No  
Yes  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
Yes  
Yes  
Yes  
Yes  
No  
Temp Unit  
Yes  
Yes  
Yes  
Yes  
User Passwd  
LCD Backlight  
LCD Bright  
User setp  
SH off df  
21  
21  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
SH off/on df  
Tank setp  
21  
21  
21  
21  
21  
21  
21  
21  
21  
21  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Tank off/on df  
Indirect HW setp  
SH/HW sw tim  
NSB setp  
Min User setp  
Max User setp  
Drop in Inlet  
Anti-C t  
11  
Service Manual  
1 Service  
Table 1B (continued from previous page) This table lists the parameters and where to access them  
USER ACCESS  
DISPLAY MODIFY  
INSTALLER ACCESS  
SEE  
MENU  
DESCRIPTION  
PAGE  
DISPLAY  
Yes  
MODIFY  
No  
Reset T Lo Out  
22  
22  
22  
22  
22  
22  
22  
23  
Yes  
No  
Reset T Hi Out  
Out T Hi Reset  
Out T Lo Reset  
Out SD setp  
Out SD df  
Yes  
No  
No  
No  
No  
No  
No  
Yes  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Boost tim  
Yes  
Yes  
Boost incr  
Yes  
Yes  
Date and time  
24  
24  
Yes  
No  
Yes  
No  
Yes  
Yes  
Yes  
Yes  
On Timer and Off Timer  
Casc Address  
Casc off df  
25  
25  
25  
25  
Yes  
No  
No  
No  
Yes  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Casc off/on df  
Max Outl temp  
Boiler Pump D  
HW Pump D  
26  
26  
26  
26  
Yes  
No  
No  
No  
Yes  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Sys Pump D  
Sys Pump mode  
BMS Type  
27  
27  
27  
27  
27  
27  
27  
28  
28  
28  
28  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
BMS Setp min V  
BMS Setp max V  
BMS V min Setp  
BMS V max Setp  
BMS V Heat  
Dropin BMS End  
BMS mod@minV  
BMS mod@maxV  
BMS V @min mod  
BMS V @max mod  
12  
Service Manual  
1 Service  
(continued)  
Viewable and changeable control parameters  
Status Screen:  
When the ON/OFF switch is turned to the ON position,  
the first screen visible on the LCD display will be the Status  
Screen. This screen displays the current status of the SYNC  
boiler. The following items can be viewed or interacted with  
on the Status Screen:  
• SH BMS - The boiler has received a call for heat from  
a 0-10 VDC BMS control.  
• Service Set Point Met - While in Service Mode, the  
water temperature at either the outlet sensor or the  
system sensor has exceeded 185°F.  
• HW Outlet Set Point Met  
temperature has exceeded the HW Generator Set Point  
parameter.  
-
The outlet water  
On/Off button - Pressing this button allows the boiler to be  
placed in either Manual Shutdown Mode or Standby Mode.  
• OA Shutdown - The outside air temperature has  
exceeded the Outdoor Shutdown Set Point parameter.  
• SH Set Point Met - The water temperature as measured  
by the system supply sensor has exceeded the User Set  
Point parameter or if the optional Outdoor Air Sensor  
was used, the calculated set point based on the  
Outdoor Reset parameters.  
Boiler Status - This line shows the current operating status of  
the SYNC boiler. Displayed items are as follows:  
• Manual Shutdown  
-
The boiler will not  
respond to either a system call or a hot water  
generation call.  
• Standby - The boiler has not received a system call  
or hot water generation call.  
• Anti-Cycle Delay - The boiler has satisfied a system  
heat call, but has received another system heat call  
before the anti-cycling time parameter has elapsed.  
• Cascade ComError - A communication error has occurred  
between the Control Module 1 and Control Module 2 or  
between the Leader and Member boilers.  
• SH Call for Heat - The boiler has received a system heat  
call.  
• SH Pump Delay - The boiler has satisfied a system heat  
call and the boiler pumps are running for a fixed  
time to remove any residual heat.  
• HW Storage - The boiler has received a hot water  
generation call.  
• HW Pump Delay - The boiler has satisfied a hot water  
generation call and the hot water generator pumps  
are running for a fixed time to remove any residual  
heat.  
13  
Service Manual  
1 Service  
Hot Water Tank Temperature - This is the temperature as  
Boiler Configuration - This line shows the current  
measured by the tank sensor in the hot water storage tank.  
configuration of the two control modules inside the unit.  
Time - The time is displayed in the upper right-hand corner of  
the display. It is displayed in 24 hour format. Reference the  
Night Setback parameters on page 24 for information regarding  
adjusting the date and time.  
Outlet Water Temperature - This is a calculated temperature  
based on the readings of the outlet temperatures of the two  
(2) heat exchangers.  
System Water Temperature - This is the water temperature  
as measured by the system supply sensor located in the  
downstream piping.  
Details button - Pressing this button brings up the Details  
Screen. This screen shows the status of the various safeties,  
inputs, and outputs to each control module. Reference the  
Details Screen section on page 15 for more information  
regarding this screen.  
Inlet Water Temperature - This is a calculated temperature  
based on the inlet temperature readings from the two (2) heat  
exchangers.  
Main button - Pressing this button brings up the Main Screen.  
From this screen navigation to eight (8) other screens is  
possible. Reference the Main Screen section on page 17 of this  
manual for more information regarding this screen.  
14  
Service Manual  
1 Service  
(continued)  
Details Screen:  
• Alarm - Is ON when a fault has been detected and the  
alarm contacts are closed. Is OFF when the alarm  
contacts are open.  
• Louver Proving Switch - Is ON when a remote proving  
safety switch is closed. Is OFF when a remote proving  
safety switch is open.  
The Details Screen is accessed by pressing the DETAIL button  
on the Status Screen. This screen shows the status of the  
various safeties, inputs and outputs to each control module.  
Selection of the control module to be viewed is accomplished  
by pressing the SELECT button. The control module being  
displayed is shown in the module box.  
• Blocked Drain Switch - Is ON when the blocked drain  
switch on the condensate trap is closed. Is OFF when the  
blocked drain switch on the condensate trap is open.  
• Blower Power - Is ON when the combustion air blower is  
energized. Is OFF when the combustion air blower is de-  
energized.  
• System Pump - Is ON when a system heat call has been  
received and the system pump has been energized. Is  
OFF when the system pump is de-energized.  
• Auto Reset High Limit - An auto reset high limit is not used  
in the standard configuration of the SYNC boiler. If OFF is  
shown then a wiring problem exists.  
• Run Time Contacts - Is ON when the burner is energized.  
Is OFF when the burner is de-energized.  
• HW Pump - Is ON when a Hot Water Generation call has  
been received from a tank thermostat or a tank sensor and  
the hot water generation pump is energized. Is OFF when  
the hot water generation pump is de-energized.  
• 0-10Vdc - Shows the voltage signal being delivered from a  
remote Building Management System (BMS).  
Displayed items are as follows:  
• SH Enable - Is ON when a system heat call has been  
received from a remote end switch or enabling device. Is  
OFF when a system heat call is not present.  
• Manual Reset High Limit - Is ON when the manual reset  
high limit is closed. Is OFF when the manual reset high  
limit is open.  
• SH Pump - Is ON when a system heat call has been  
received and the boiler pump is energized. Is OFF  
when the boiler pump is de-energized.  
• HW Thermostat - Is ON when a Hot Water Generation  
call has been received from a tank thermostat. Is OFF  
when a Hot Water Generation call has not been received  
from a tank thermostat.  
• Air Pressure Switch - Is ON when the combustion air  
blower is energized and the flap valve switch is closed.  
Is OFF when the flap valve switch is open.  
• Gas Valve - Is ON when the gas valve is energized. Is OFF  
when the gas valve is de-energized.  
• Gas Pressure Switches - Is ON when the high and low gas  
pressure switches are closed. If OFF when either the high  
or low gas pressure switches are open.  
• Flow Switch / Low Water Cutoff - Is ON when the low  
water cutoff contacts are closed or if an optional flow  
switch is used and it is closed as well. Is OFF when the  
low water cutoff contacts are open or if an optional flow  
switch is open.  
15  
Service Manual  
1 Service  
Time - The time is displayed in the upper right-hand corner of  
the display. It is displayed in 24 hour format. Reference the  
night setback parameters on page 24 for information regarding  
adjusting the date and time.  
A blank message box is located on the Details Screen. This  
box will display various messages detailing the status of the  
control module. If a message is present in this box, the  
DETAILS button on the Status Screen will contain a yellow  
triangle with an exclamation mark (!) inside.  
Status button - Pressing this button displays the Status Screen.  
This screen shows the current status of the SYNC boiler.  
Reference pages 13 - 14 for more information regarding this  
screen.  
Displayed items are as follows:  
• Delta T Shutdown - The temperature rise between the  
inlet and outlet temperatures has exceeded 55°F.  
Reference page 53 for more information regarding this  
shutdown.  
• Outlet Temp Shutdown - The outlet temperature has  
exceeded 195°F. Reference page 53 for more information  
regarding this shutdown.  
Main button - Pressing this button displays the Main Screen.  
From this screen, navigation to eight (8) additional screens is  
possible. Refer to Main Screen on page 17 for more information  
regarding this screen.  
• Flue Temp Shutdown - The flue temperature has  
exceeded 240°F. Reference page 53 for more information  
regarding this shutdown.  
• Voltage too Low - The 120 VAC input to the control has  
dropped below 80 VAC. Reference page 52 for more  
information regarding this fault message.  
• Connect System Sensor - System sensor is not detected by  
Control Module 1. For proper operation of the SYNC  
boiler the system sensor must be connected.  
• Manual Shutdown - The boiler has been shutdown with  
the ON/OFF button on the Status Screen.  
16  
Service Manual  
1 Service  
(continued)  
Main Screen:  
The Main Screen allows navigation to eight (8) additional Navigation to the Main Screen can be accomplished by pressing  
screens which are used to set temperatures, operating the MAIN button at the bottom of the page.  
conditions, and monitor boiler operation. These screens are  
Reference pages 18 - 35 of this manual for more information  
as follows:  
regarding the eight (8) accessible screens.  
• Setup - Allows access to seven (7) other screens for the  
adjustment of the control parameters.  
Time - The time is displayed in the upper right-hand corner of  
the display. It is displayed in 24 hour format. Reference the  
• Cascade - Shows the status of multiple boilers connected  
night setback parameters on page 24 for information regarding  
together in a cascade arrangement.  
adjusting the date and time.  
• Temps - Shows the temperatures measured by the  
individual sensors connected to the boiler.  
• Burners - Shows the status of the two (2) independent  
burner systems used in the boiler.  
• Building - Shows the information from a Building  
Integration System using Modbus Protocols.  
• Graphs - Allows the selection of items to be graphed on a  
chart.  
Status button - Pressing this button displays the Status Screen.  
This screen shows the current status of the SYNC boiler.  
Reference pages 13 - 14 for more information regarding this  
screen.  
• History - Shows the operating and fault history of the  
two (2) control modules.  
• Service Mode - Allows the installer to control the fan  
speed of the individual control modules for the purposes  
of combustion analysis. Service Mode will override all  
other heat demands, however, all safeties will remain  
intact.  
17  
Service Manual  
1 Service  
Before changing parameters, note the settings so that the unit can be returned to its original operating  
parameters.  
CAUTION  
Setup Screen:  
The Setup Screen allows access to seven (7) other screens for If the password has been entered correctly, the Parameter  
adjusting control parameters.  
Change Screen will appear. The Parameter Change Screen will  
display the parameter being changed, the previous setting of the  
parameter, and adjustment buttons.  
These screens are as follows:  
• Service / Setup - Allows access to change service  
notification parameters, LCD backlight parameters, and  
temperature units.  
• Night Setback - Allows access to change the date and time  
and ON/OFF times for night setback.  
• Setpoints - Allows access to change the system heat  
set point, hot water generation set point, and ON/OFF  
differentials.  
• Cascade - Allows access to change the cascade parameters.  
• Outdoor Reset - Allows access to change the reset curve  
parameters.  
To adjust the parameter, press the + or - buttons to change the  
value being displayed. Once the parameter has been adjusted  
to the desired setting, press the APPLY button to change the  
parameter and return to the Parameter List Screen. If no further  
changes are necessary, press the BACK button to return to the  
Parameter List Screen. Once all the necessary adjustments  
have been made, press the BACK button to return to the Setup  
Screen. Repeat this procedure to adjust the parameters in other  
screens.  
Press the SAVE button to program all changes made to the  
control parameters and return to the Status Screen. Leaving the  
Setup Screen without pressing the SAVE button will erase the  
changes made to the control parameters and revert them back  
to their previous settings.  
• Pumps - Allows access to change pump delay timing.  
• BMS - Allows access to change the 0 - 10Vdc BMS  
parameters.  
To change a parameter, press one of the seven screen buttons.  
A list of parameters and their corresponding location are  
located on pages 11 and 12, Table 1B. Once a Screen button  
is pressed a list of adjustable parameters will appear.  
Time - The time is displayed in the upper right-hand corner of  
the display. It is displayed in 24 hour format. Reference the  
night setback parameters on page 24 for information regarding  
adjusting the date and time.  
Select the parameter to be adjusted by pressing the SELECT Main button - Pressing this button brings up the Main Screen.  
button next to the parameter. The first time the parameters From this screen navigation to eight (8) other screens is  
are accessed, you will be required to enter the service possible. Reference the Main Screen section on page 17 of this  
password. The service password is 5309. Using the keypad, manual for more information regarding this screen.  
enter the password and then press the OK button. If the  
Save button - Pressing this button will save all changes made to  
password is not entered correctly, the screen will revert to the  
the control parameters.  
Parameter List Screen and you will not be able to adjust the  
Status button - Pressing this button displays the Status Screen.  
This screen shows the current status of the SYNC boiler.  
Reference pages 13 - 14 for more information regarding this  
screen.  
parameters. If a digit has been entered incorrectly, press the  
left arrow key on the keypad to back the digit up.  
18  
Service Manual  
1 Service  
(continued)  
Service/Setup Parameters Screen:  
The Service / Setup Screen allows access to 10 parameters. If either BMS configuration is selected, additional parameters  
Those parameters are as follows:  
for BMS operation will have to be adjusted. Reference  
the BMS parameters on pages 27 and 28 for information  
regarding adjusting these parameters. There are three (3) other  
configuration selections that are possible, however, they must  
NOT be used on the SYNC boiler.  
This parameter can only be changed by the installer. The default  
configuration is Cascade Set Point Thermostat based.  
• Service Notification Time - When the boiler determines  
that a scheduled service is due based on days of  
installation, the Service Needed screen will appear. This  
parameter can only be changed by the installer. The  
adjustment range for this parameter is 0 months to 36  
months. The default time is 12 months.  
• Service Notification Running Hours - When the boiler  
determines that a scheduled service is due based on the  
hours of actual operation. This parameter can only be  
changed by the installer. The adjustment range for this  
parameter is 0 hours to 100,000 hours. The default time is  
10,000 hours.  
• Demand Configuration - Sets the configuration of the  
control modules inside the boiler. The configuration  
selections are:  
Demand Configuration 1: Cascade Set Point Thermostat  
based - the control modulates the boiler based on the user  
set point and the temperature of the controlling sensor. An  
enable signal from a remote end switch or enabling device  
must be present to initiate a system heat call.  
Demand Configuration 4: Cascade Set Point Modbus  
Thermostat based - the control modulates the boiler based  
on the user set point and the temperature of the controlling  
sensor. An enable signal is provided by writing to the  
holding registers on the Modbus communication board.  
Demand Configuration 2: Cascade BMS Thermostat  
based - a 0 - 10Vdc signal is provided to the boiler to  
control either the set point or the modulation of the boiler.  
An enable signal from a remote end switch or enabling  
device must be present to initiate a system heat call.  
• Service Notification Cycles - When the boiler determines  
that a scheduled service is due based on the number of  
boiler cycles, the Service Needed screen will appear. This  
parameter can only be changed by the installer. The range  
for this parameter is 0 cycles to 100,000 cycles. The default  
is 10,000 cycles.  
Demand Configuration 5:  
Cascade Modbus BMS  
Thermostat based - a 0 - 10V dc signal is provided to the  
boiler to control either the set point or the modulation of  
the boiler. An enable signal and an equivalent 0 - 10V signal  
is provided by writing to the holding registers on the  
Modbus communication board.  
• Ramp Delay - Sets the mode of operation of the ramp delay.  
The selections are:  
Demand Configuration 3: Cascade BMS Voltage based - a  
0 - 10Vdc signal is provided to the boiler to control either  
set point or modulation. A minimum voltage signal is  
required to initiate a system heat call.  
Demand Configuration 6: Cascade Modbus BMS Voltage  
based - a 0 - 10V dc signal is provided to the boiler to  
control either set point or modulation. An equivalent 0 -  
10V dc signal is provided by writing to the holding registers  
on the Modbus communication board.  
0. Off - Ramp delay disabled.  
1. Step Up - The total output of the boiler or cascade will  
be limited after the call for heat begins.  
2. Step Up / Down - The initial limitation will be  
determined by how long the boiler or cascade has been  
off. This parameter can only be changed by the  
installer. The default value is 0 - Off.  
19  
Service Manual  
1 Service  
Reference page 18 for information regarding changing  
parameters.  
• Maximum Service Time - Service Mode allows the  
installer to control the fan speed of the individual control  
modules for the purposes of combustion analysis.  
Time - The time is displayed in the upper right-hand corner of  
the display. It is displayed in 24 hour format. Reference the  
night setback parameters on page 24 for information regarding  
adjusting the date and time.  
Service Mode will override all other heat demands,  
however, all safeties will remain intact. Maximum service  
time sets the length of time the boiler will stay in Service  
Mode if no buttons are pressed before reverting back to  
its original state. This parameter can only be changed by  
the installer. The time range of this parameter is 0 to 40  
minutes. The default value is 20 minutes.  
Back button - Pressing this button will back the screen up to  
the previous screen.  
• Temperature Units - The control can be configured to  
display temperatures in either °C or °F. The default is °F.  
• User Password - Allows the user to access and change a  
limited number of control parameters. The access code  
can be changed by the user or the installer to a code of  
their choosing. The default code is 0704.  
• LCD Backlight - Sets the length of time the LCD Screen  
will stay on after a button has been pressed. This  
parameter can be changed by the user or the installer.  
The time range for this parameter is 30 seconds to ON.  
With a setting of ON, the LCD Screen will be on  
continuously. The default time is 15 minutes.  
• LCD Brightness - Controls the brightness of the screen.  
This parameter can be changed by the user or the  
installer. The range for this parameter is 10% to 100%.  
The default percentage is 50%.  
20  
Service Manual  
1 Service  
(continued)  
Set Point Parameters Screen:  
The Set Point Screen allows access to 12 parameters. Those  
parameters are as follows:  
The user or installer may not go below this  
value when programming the “User Set Point”.  
The  
temperature range of this parameter is 0° to 190°F. The  
default value is 60°F.  
• User Set Point - Sets the water temperature set point for  
fixed temperature operation or the maximum  
temperature set point when the outdoor air sensor is  
used. This parameter can be changed by the user or the  
installer. The temperature range of this parameter is 50°  
to 190°F. The default value is 125°F.  
• Maximum User Set Point - Sets the maximum water  
temperature set point that can be used for space heating.  
The user or installer may not go above this value when  
programming the “User Set Point”. The temperature  
range of this parameter is 0° to 190°F. The default value  
is 190°F.  
• Hot Water Tank Set Point - When a tank sensor is  
installed in a hot water storage tank, the hot water tank  
set point sets the target temperature of the water in the  
tank. This parameter can be changed by the user or the  
installer. The temperature range of this parameter is 60°  
to 185°F. The default value is 125°F.  
• Drop in Inlet Temperature for Ending Anti-cycling - The  
control will bypass the anti-cycling time if the inlet water  
temperature drops too quickly. The control will use the  
inlet water temperature at Heat Exchanger 1 when it shuts  
off as the starting point. If the temperature drops below the  
temperature parameter the control will abort anti-cycling  
and allow the boiler to fire. This parameter can only be  
changed by the installer. The temperature range of this  
parameter is 0° to 86°F. The default value is 10°F.  
• Anti-cycling Time - Once a system heat call has been  
satisfied, a set amount of time must elapse before the  
control will respond to a new system heat call. The  
control will block the new system heat call and Anti-  
cycling will be shown in the boiler status display until the  
time has elapsed or the inlet water temperature drops  
below the parameter drop in inlet temperature for ending  
anti-cycling. This parameter can only be changed by the  
installer. The time range for this parameter is 0 minutes  
to 40 minutes. The default value is 1 minute.  
• Hot Water Tank Differential - Sets how many degrees  
below the Hot Water Tank Set Point the hot water tank  
temperature must drop before the boiler will turn on.  
This parameter can only be changed by the installer. The  
temperature range for this parameter is 0° to 100°F. The  
default value is 5°F.  
• Indirect HW Set Point - When a Hot Water Generation  
call for heat becomes active, the control will use the  
Indirect HW set point to determine the firing rate of the  
boiler based on the actual boiler outlet water  
temperature. This parameter can be changed by the user  
or the installer. The temperature range of this parameter  
is 50° to 190°F. The default value is 180°F.  
• Night Setback Set Point - Once the internal clock has  
been set correctly, the night setback feature can be used to  
program a lower water temperature set point for space  
heating. This parameter can be changed by the user or  
the installer. The temperature range for this parameter is  
32° to 140°F. This feature is turned off with a setting of  
32°F. The default value is 32°F.  
Reference page 18 for information regarding changing  
parameters.  
Time - The time is displayed in the upper right-hand corner of  
the display. It is displayed in 24 hour format. Reference the  
night setback parameters on page 24 for information regarding  
adjusting the date and time.  
• Minimum User Set Point - Sets the minimum water  
temperature set point that can be used for space heating  
operation.  
Back button - Pressing this button will back the screen up to the  
previous screen.  
21  
Service Manual  
1 Service  
Outdoor Reset Parameters Screen:  
• Outdoor Temperature at Low Reset Temperature - When  
the outdoor air temperature rises to or above this point, the  
water temperature will be at its minimum setting. This  
parameter can only be changed by the installer. The  
temperature range of this parameter is 25° to 86°F. The  
default value is 70°F.  
When the outdoor air sensor is installed, the control will  
calculate the water temperature set point based on the  
outdoor air temperature. As the outdoor air temperature  
drops the water temperature set point increases. This feature  
allows the boiler to be more efficient in periods of mild  
weather.  
• Outdoor Shutdown Set Point - When the outdoor air  
temperature rises above this point, the control will block  
all system heat calls. The Hot Water Generation call will  
be unaffected. This parameter can be changed by the  
user or the installer. The temperature range of this  
parameter is 32° to 122°F. The default value is 70°F.  
The Outdoor Reset Screen allows access to eight (8)  
parameters. Those parameters are as follows:  
• Reset Temperature at Low Outdoor Temperature - When  
the outdoor air temperature drops to its minimum  
setting, the water temperature will be at this point, if the  
user set point parameter is set higher. This parameter can  
only be changed by the installer. The temperature range  
of this parameter is 0° to 190°F. The default value is  
180°F.  
• Outdoor Shutdown Differential - The number of degrees  
below the outdoor shutdown set point that the outdoor air  
temperature must go before the boiler will respond to a  
system heat call. This parameter can be changed by the user  
or the installer. The temperature range of this parameter is  
0° to 90°F. The default value is 10°F.  
• Reset Temperature at High Outdoor Temperature -  
When the outdoor air temperature rises to or above its  
maximum setting, the water temperature will be at this  
point. This parameter can only be changed by the  
installer. The temperature range of this parameter is 32°  
to 180°F. The default value is 100°F.  
• Boost Time - If the boost increment parameter is set to  
active, the boost time parameter will set the amount of time  
that must elapse with a system heat call before the water  
temperature set point will be increased. This parameter can  
be changed by the user or the installer. The time range for  
this parameter is 0 minutes to 250 minutes. The default  
value is 20 minutes.  
• Outdoor Temperature at High Reset Temperature -  
When the outdoor air temperature drops to this point,  
the water temperature will be at its maximum setting.  
However, if the user set point is set lower, the water  
temperature will be limited by the user set point. This  
parameter can only be changed by the installer. The  
temperature rane of this parameter is -22° to 70°F. The  
default value is 25°F.  
22  
Service Manual  
1 Service  
(continued)  
• Boost Increment - If a system heat call last longer than the  
programmed boost time setting and there have been no Hot  
Water Generation calls, the control will increase the water  
temperature set point by the amount in this parameter. If  
the system heat call continues through another time period,  
the set point will be increased again. This will continue  
until either the system heat call ends, a maximum of 20  
increases has occurred, or the maximum set point has been  
reached. Once the system heat call has been satisfied the set  
point will revert back to its calculated setting. This  
parameter can be changed by the user or the installer. The  
temperature range of this parameter is 0° to 45°F. The  
default value is 0°F. This feature will be active if this  
parameter is set to anything other than 0°F.  
Reference page 18 for information regarding changing  
parameters.  
Time - The time is displayed in the upper right-hand corner  
of the display. It is displayed in 24 hour format. Reference  
the night setback parameters on page 24 for information  
regarding adjusting the date and time.  
Back button - Pressing this button will back the screen up to  
the previous screen.  
23  
Service Manual  
1 Service  
Night Setback Parameters Screen:  
The Night Setback Screen allows access to 15 parameters. Example: Monday ON: 22:30, Tuesday OFF: 6:45. If you wish  
Those parameters are as follows:  
to skip a day and no night setback is necessary, program the on  
and off times the same and set them prior to 12:00 (noon). If  
you wish to keep night setback active throughout an entire day,  
program the on and off times the same and set them after 12:00  
(noon). The default times for each day will be on at 18:00 and  
off at 8:00.  
• Date and Time - The control uses an internal clock for the  
night setback feature and for logging of events. For these  
features to work correctly, the clock must be set when the  
boiler is first installed or any time the boiler has been  
powered off for more than 30 days.  
To adjust the on and off times, select the parameter to be  
adjusted by pressing the SELECT button next to the parameter.  
Using the keypad, adjust the time by working from left to right.  
If a digit has been entered incorrectly, press the left arrow key  
on the keypad to back the digit up. If no change is necessary,  
press the BACK button to return to the Parameter List Screen.  
Once the correct time has been entered press the OK button on  
the display to program the time into memory and return to the  
Parameter List Screen.  
To set the clock, press the SELECT button in the upper right-  
hand corner of the display. The date and time are displayed  
as “Day dd/mm/yy hh:mm”. Day = day of the week (1 =  
Monday, 2 = Tuesday, etc.), dd = date, mm = month, yy =  
year, hh = hour, mm = minutes (24 hours time; 2:30 PM =  
14:30). Using the keypad, adjust the date and time by working  
from left to right. If a digit has been entered incorrectly, press  
the left arrow key on the keypad to back the digit up. If a  
change is not necessary, press the BACK button to return to  
the Parameter List Screen. Once the correct date and time Reference page 21 for information regarding NSB Set Point  
have been entered press the OK button on the display to Temp programming.  
program the date and time into memory and return to the  
Apply button - If changes have been made to the date and time  
or to one of the on or off timers, the APPLY button must be  
Parameter List Screen.  
The internal clock does not adjust for Daylight Savings Time pressed to program the changes into the control module and  
and therefore, will require a manual adjustment.  
return to the Setup Screen.  
• On Timer and Off Timer - If the parameter night setback Back button - Pressing this button will back the screen up to the  
set point is set to anything other than 32°F, the night previous screen.  
setback feature becomes active. This will require on and  
off times to be programmed for the days that reduced  
temperatures are required. Each day of the week  
(Monday through Sunday) will have an on and off time.  
24  
Service Manual  
1 Service  
(continued)  
Cascade Parameters Screen:  
• Cascade Off/On Differential - Sets how many degrees  
below the turn off temperature (set point + Cascade Off  
Differential) the temperature has to go before the lead  
boiler will turn on. This parameter can only be changed  
by the installer. The temperature range of this parameter  
is 0° to 72°F. The default value is 20°F.  
Cascade Operation  
When multiple boilers are installed, they can be wired  
together in a cascade sequence. A maximum of eight (8)  
boilers can be controlled from a single control. In this  
application one boiler would be designated as the Leader and  
all others would be designated as Members. The designated  
Leader boiler determines the total output needed from the  
group based on the set point and the system sensor reading.  
Reference the Wiring of the Cascade section in the SYNC  
Installation and Operation Manual for more information  
regarding the cascade feature.  
• Maximum Outlet Temperature - Sets the set point that  
individual boilers will attempt to achieve in a cascade.  
When a boiler is commanded to fire by the Leader, it will  
attempt to achieve this temperature at its outlet. The Leader  
will control the modulation of the last boiler to fire in order  
to hold the temperature at the system supply sensor to the  
user set point. If any of the boiler outlet temperatures reach  
the Maximum Outlet Temperature setting, the boiler will  
then modulate down on its own in order to keep its outlet  
temperature within the Maximum Outlet Temperature  
setting. Therefore, this parameter can be used to limit the  
outlet temperatures of all the boilers in a cascade.  
The Cascade Screen allows access to four (4) parameters.  
Those parameters are as follows:  
Cascade Address - The boiler designated as the Leader  
should be programmed with address 0-1. All Member  
boilers require addresses from 2-3 through 14-15. The  
address must be different for each member. The  
addresses can be in any order, regardless of the order in  
which the boilers are wired together. This parameter can  
only be changed by the installer. The default address is  
0-1.  
Note that this parameter does not apply when the boiler is  
in Hot Water Generation Mode. This parameter can be  
changed by the user or the installer. The temperature range  
of this parameter is 32° to 212°F. The default value is 185°F.  
Reference page 18 for information regarding changing  
parameters.  
Cascade Off Differential - Sets how many degrees above  
set point the temperature has to go before the lead boiler  
will shut off. This parameter can only be changed by the  
installer. The temperature range of this parameter is 0° to  
72°F. The default value is 10°F.  
Time - The time is displayed in the upper right-hand corner of  
the display. It is displayed in 24 hour format. Reference the  
night setback parameters on page 24 for information regarding  
adjusting the date and time.  
Back button - Pressing this button will back the screen up to the  
previous screen.  
25  
Service Manual  
1 Service  
Pumps Parameters Screen:  
Time - The time is displayed in the upper right-hand corner of  
the display. It is displayed in 24 hour format. Reference the  
night setback parameters on page 24 for information regarding  
adjusting the date and time.  
The Pumps Screen allows access to four (4) parameters.  
Those parameters are as follows:  
• Boiler Pump Delay - Sets the length of time the boiler  
pumps will run after a system heat call has been satisfied.  
This parameter can only be changed by the installer. The  
time range for this parameter is 0 minutes to 40 minutes.  
The default time is 30 seconds.  
Back button - Pressing this button will back the screen up to the  
previous screen.  
• HW Pump Delay - Sets the length of time the Hot Water  
Generation pumps (if connected) will run after a Hot  
Water Generation call has been satisfied. This parameter  
can only be changed by the installer. The time range for  
this parameter is 0 minutes to 40 minutes. The default  
time is 30 seconds.  
• System Pump Delay - Sets the length of time the system  
pump (if connected) will run after a system heat call has  
been satisfied. This parameter can only be changed by the  
installer. The time range for this parameter is 0 minutes  
to 40 minutes. the default time is 30 seconds.  
• System Pump Mode - Sets the configuration of the system  
pump. The configuration selections are:  
0. The system pump will be on continuously except  
during outdoor shutdown.  
1. The system pump will be off.  
2. The system pump will be on only during a system  
heat call.  
This parameter can only be changed by the installer. The  
default configuration is 2: On only during a system heat call.  
Reference page 18 for information regarding changing  
parameters.  
26  
Service Manual  
1 Service  
(continued)  
0 - 10Vdc BMS Parameters Screen:  
ModBus Timeout  
0-10Vdc Operation  
• BMS Voltage at Minimum Set Point - Determines the  
voltage at which the external signal begins to increase the  
set point. Below this voltage, the set point will be at the  
setting of the BMS Set Point Minimum Voltage  
parameter. This parameter is only active when the BMS  
Type is set to Set Point. This parameter can only be  
changed by the installer. The range of this parameter is 0  
to 10V. The default value is 2V.  
When the Demand Configuration parameter (see page 19)  
is set to either Cascade BMS Thermostat Based, Cascade  
BMS Voltage Based, Cascade Modbus BMS Thermostat  
Based, or Cascade Modbus BMS Voltage Based; a 0 - 10Vdc  
signal can be supplied to the terminal strip connection or  
through Modbus communications to control a single unit or  
a multiple unit cascade.  
The BMS Screen allows access to 11 parameters. Those  
parameters are:  
• BMS Voltage at Maximum Set Point - Determines the  
voltage at which the external signal forces the set point to  
the setting of the BMS Set Point Maximum Voltage  
parameter. This parameter is only active when the BMS  
Type is set to Set Point. This parameter can only be changed  
by the installer. The range of this parameter is 2V to 10V.  
The default value is 10V.  
• BMS Type - When the unit or cascade is controlled by the  
0-10Vdc BMS input, the voltage signal can control either  
the modulation rate or set point. This parameter can only  
be changed by the installer. The default method of  
control is modulation rate.  
• BMS Set Point at Minimum Voltage - Determines the set  
point used by the unit or cascade when the BMS voltage  
is at or below the setting of the BMS Voltage Minimum  
Set Point parameter. This parameter is only active when  
the BMS Type is set to Set Point. This parameter can only  
be changed by the installer. The temperature range of this  
parameter is 32° to 179°F. The default value is 70°F.  
• BMS Voltage at Start Call for Heat - When the Demand  
Configuration parameter (see page 19) is set to Cascade  
BMS Voltage Based, this parameter determines the BMS  
input voltage at which the unit or cascade is enabled. The  
unit or cascade will become enabled when the BMS input  
voltage rises up to or above this value. This parameter can  
only be changed by the installer. The range of this  
parameter is 0 to 10V. The default value is 2V.  
• BMS Set Point at Maximum Voltage - Determines the set  
point used by the unit or cascade when the BMS voltage  
is at or above the setting of the BMS Voltage Maximum  
Set Point parameter. This parameter is only active when  
the BMS Type is set to Set Point. This parameter can only  
be changed by the installer. The temperature range of this  
parameter is 70° to 190°F. The default value is 179°F.  
• Drop in BMS Voltage to End Call for Heat - When the  
Demand Configuration parameter (see page 19) is set to  
Cascade BMS Voltage Based, this parameter determines the  
BMS input voltage at which the unit or cascade is disabled.  
The unit or cascade will become disabled when the BMS  
input voltage drops down to or below the BMS voltage at  
start call for heat minus this value. This parameter can only  
be changed by the installer. The range of this parameter is  
0 to 10V. The default value is 1V.  
27  
Service Manual  
1 Service  
ModBus Timeout  
Reference page 18 for information regarding changing  
parameters.  
• BMS Modulation at Minimum Voltage - Determines the  
modulation rate of the unit or cascade when the BMS  
input voltage is at or below the setting of the BMS Voltage  
at Minimum Modulation parameter. This parameter is  
only active when the BMS Type is set to modulation rate.  
This parameter can only be changed by the installer. The  
range of this parameter is 0% to 100%. The default value  
is 14.5%.  
Time - The time is displayed in the upper right-hand corner of  
the display. It is displayed in 24 hour format. Reference the  
night setback parameters on page 24 for information regarding  
adjusting the date and time.  
Back button - Pressing this button will back the screen up to the  
previous screen.  
• BMS Modulation at Maximum Voltage - Determines the  
modulation rate of the unit or cascade when the BMS  
input voltage is at or above the setting of the BMS Voltage  
at Maximum Modulation parameter. This parameter is  
only active when the BMS Type is set to modulation rate.  
This parameter can only be changed by the installer. The  
range of this parameter is 14.5% to 100%. The default  
value is 100%.  
• BMS Voltage at Minimum Modulation - Determines the  
voltage at which the external signal begins to increase the  
modulation rate (power). Below this voltage, the  
modulation rate (power) will be at the setting of the BMS  
Modulation at Minimum Voltage parameter. This  
parameter is only active when the BMS Type is set to  
modulation rate (power). This parameter can only be  
changed by the installer. The range of this parameter is  
0V to 10V. The default value is 2V.  
• BMS Voltage at Maximum Modulation - Determines the  
voltage at which the external signal forces the modulation  
rate (power) to the setting of the BMS Modulation at  
Maximum Voltage parameter. This parameter is only  
active when the BMS Type is set to modulation rate  
(power). This parameter can only be changed by the  
installer. The range of this parameter is 2V to 10V. The  
default value is 10V.  
28  
Service Manual  
1 Service  
(continued)  
Cascade Screen:  
System Temperature - This is the water temperature as measured  
by the system sensor located in the system supply piping.  
The Cascade Screen provides the status of the cascade system.  
Items that can be viewed on the Cascade Screen are as follows:  
SH Set Point - This is the set point of the cascade system.  
The boiler designated as the Leader will use this set point  
to determine the power level required to bring the system  
temperature to this point. A default value of 50°F (10°C) is  
displayed when the SH Call for Heat is inactive.  
Boiler Power Level Indicators - For each boiler present in  
the cascade a power level indicator will be present above  
its corresponding number.  
The level will rise and  
fall indicating the approximate power level of the boiler.  
The display box underneath each number will  
display “HW” when that boiler is providing heat for a Hot  
Water Generation call.  
Time - The time is displayed in the upper right-hand corner of  
the display. It is displayed in 24 hour format. Reference the  
night setback parameters on page 24 for information regarding  
adjusting the date and time.  
On Timer and Off Timer - The ON and OFF timers are  
used to force each boiler in the cascade to have a  
minimum on and off time to prevent short cycling.  
Status button - Pressing this button displays the Status Screen.  
This screens shows the current status of the SYNC boiler.  
Reference the Status Screen on page 13 for more information  
regarding this screen.  
Block Switch On Timer  
-
Whenever  
a
boiler is  
commanded to start, the block switch on timer is started.  
This provides a delay between the first ignition system  
and the second ignition system inside the boiler. Once the  
second ignition system is started, the timer is reset and the  
next boiler is prevented from starting until the timer  
times out. This process is repeated for each boiler in the  
cascade.  
Main button - Pressing this button displays the Main Screen.  
From this screen, navigation to eight (8) other screens is  
possible. Reference the Main Screen on page 17 for more  
information regarding this screen.  
Demand - Shows the status of the cascade. Displayed  
items are:  
No Demand - the Cascade leader has not received a  
system heat call.  
SH Demand - the Cascade leader has received a  
system heat call.  
Set Point Met - the system temperature has met the  
User Set Point + the Off Differential.  
Pump Delay - the cascade has satisfied a system  
heat call and the system pump is running for a fixed  
time.  
29  
Service Manual  
1 Service  
1
On  
34  
80  
55  
The Building Screen displays information that is specific to the Building Automation System and is being transmitted through  
the Modbus communication link:  
Modbus Address - This is the address of a specific SYNC  
boiler. This address is set by dip switches on the Modbus  
communication board. The value displayed here should  
be the same as the value of the dip switches. The Building  
Automation System should use this address to communicate  
with the boiler.  
Boiler Command - This displays the value written to register  
40003 of the Modbus communication board by the Building  
Automation System. The value is displayed as the percent of  
firing rate, 80 = 80% firing rate.  
Effective Setpoint - This displays the value written to register  
40003 of the Modbus communication board by the Building  
Automation System. The value is displayed as the effective  
setpoint in degrees (°F or °C).  
Boiler Enable - This displays the enable status that has been  
transmitted to the boiler by the Building Automation System.  
Boiler State - This displays the state code of the boiler. Please  
reference the SYNC Modbus Instruction Manual for a full  
definition of each code.  
Note: The boiler can be configured to operate off the boiler  
command or the effective setpoint. The boiler configuration  
determines which value is meaningful.  
30  
Service Manual  
1 Service  
(continued)  
Temps Screen:  
The Temps Screen displays the various temperatures as  
measured by sensors connected to each control module.  
Items that can be viewed on the Temps Screen are as follows:  
Time - The time is displayed in the upper right-hand corner of  
the display. It is displayed in 24 hour format. Reference the  
night setback parameters on page 24 for information regarding  
adjusting the date and time.  
• Heat Exchanger 1/2 Inlet - This is the water temperature  
as measured by the sensor located in the inlet of each heat  
exchanger.  
Status button - Pressing this button displays the Status Screen.  
this screen shows the current status of the SYNC boiler.  
Reference page 13 for more information regarding this screen.  
• Heat Exchanger 1/2 Outlet - This is the water temperature  
as measured by the sensor located in the outlet of each  
heat exchanger.  
Main button - Pressing this button displays the Main Screen.  
From this screen, navigation to eight (8) other screens is  
possible. Reference the Main Screen on page 17 for more  
information regarding this screen.  
• Heat Exchanger 1/2 Flue - This is the temperature as  
measured by the sensor located in the flue connection on  
each heat exchanger.  
• Set Point - Two temperatures are shown in this display.  
the top temperature is the Cascade Maximum Outlet  
Temperature. The lower temperature is the tank set point  
for a Hot Water Generation call.  
• System Sensor - This is the water temperature as  
measured by the sensor located in the system supply  
piping. The system sensor must be installed for the  
proper operation of the boiler.  
• Outdoor Sensor - This is the temperature of the outside  
air as measured by the sensor located outside. The use of  
the outdoor sensor is optional. If the sensor is connected  
the control will calculate the set point based on the  
programmed outdoor parameters. See page 22 for  
information regarding adjusting the outdoor parameters.  
If the sensor is not present, none will be shown in the  
display.  
31  
Service Manual  
1 Service  
Burners Screen:  
This screen provides the status of the combustion air blowers  
and flame signals. Items that can be viewed on the Burners  
Screen are as follows:  
Time - The time is displayed in the upper right-hand corner of  
the display. It is displayed in 24 hour format. Reference the  
night setback parameters on page 24 for information regarding  
adjusting the date and time.  
• Blower Power Level Indicator - Two (2) blowers are  
depicted on the display. The top blower corresponds with  
Heat Exchanger 1 or Top heat exchanger. The lower  
blower corresponds with Heat Exchanger 2 or Bottom  
heat exchanger. Beside each blower is a power level  
indicator. The level will increase and decrease indicating  
the approximate power level of the blower. The display  
box underneath each indicator level will display the firing  
rate of each control module.  
Status button - Pressing this button displays the Status Screen.  
this screen shows the current status of the SYNC boiler.  
Reference page 13 for more information regarding this screen.  
Main button - Pressing this button displays the Main Screen.  
From this screen, navigation to eight (8) other screens is  
possible. Reference the Main Screen on page 17 for more  
information regarding this screen.  
• RPM’s - Each blower will display the rpm that the  
control module is requiring of the blower.  
• Flame Signal - The flame signal for each control module  
will be displayed in dc microamps.  
32  
Service Manual  
1 Service  
(continued)  
Graph Select Screen:  
The Graphs Screen consists of two (2) different screens. The  
first screen is the Parameter Selection Screen. By pressing the  
box beside the desired item, a check will appear in the selected  
Time - The time is displayed in the upper right-hand corner of  
the display. It is displayed in 24 hour format. Reference the  
night setback parameters on page 24 for information regarding  
adjusting the date and time.  
box and the control will graph the status of that item.  
maximum of five (5) items can be graphed at one time.  
A
Status button - Pressing this button displays the Status Screen.  
this screen shows the current status of the SYNC boiler.  
Reference page 13 for more information regarding this screen.  
The second screen is accessed by pressing the NEXT button.  
Once the items to be graphed are selected, press the NEXT  
button to view the graph. Each item graphed will have a  
different color line to represent it. The items selected will  
be shown in a display bar with their Min and Max ranges  
listed below them. Press the BACK button to return to the  
Parameter Selection Screen.  
Main button - Pressing this button displays the Main Screen.  
From this screen, navigation to eight (8) other screens is  
possible. Reference the Main Screen on page 17 for more  
information regarding this screen.  
33  
Service Manual  
1 Service  
History Screen:  
The History Screen shows the status of various counters  
and faults for each control module. Selection of the control  
module to be viewed is accomplished by pressing the SELECT  
button. The control module being displayed is shown in the  
module box. Items that can be viewed on the History Screen  
are as follows:  
Time - The time is displayed in the upper right-hand corner of  
the display. It is displayed in 24 hour format. Reference the  
night setback parameters on page 24 for information regarding  
adjusting the date and time.  
Status button - Pressing this button displays the Status Screen.  
this screen shows the current status of the SYNC boiler.  
Reference page 13 for more information regarding this screen.  
• Power Hours - Shows the number of hours the control  
has been powered on.  
Main button - Pressing this button displays the Main Screen.  
From this screen, navigation to eight (8) other screens is  
possible. Reference the Main Screen on page 17 for more  
information regarding this screen.  
• Successful Ignitions - Shows the number of times the  
control has successfully ignited.  
• Hours SH < 50% - Shows the number of hours the  
control has operated at less than 50%.  
• Total Ignitions - Shows the total number of times the  
control has attempted to ignite.  
• Last 10 Faults - Shows the last 10 faults of the control  
module by date and time.  
34  
Service Manual  
1 Service  
(continued)  
Service Mode Screen:  
The Service Mode Screen allows the individual control  
modules to override all other heat demands and operate at  
a full fire condition for the purpose of combustion analysis.  
Selection of the control module to be placed into Service  
Mode is accomplished by pressing the SELECT button. The  
control module being placed into Service Mode is shown in  
the module box.  
Time - The time is displayed in the upper right-hand corner of  
the display. It is displayed in 24 hour format. Reference the  
night setback parameters on page 24 for information regarding  
adjusting the date and time.  
Status button - Pressing this button displays the Status Screen.  
this screen shows the current status of the SYNC boiler.  
Reference page 13 for more information regarding this screen.  
To place the unit into Service Mode, press the ON/OFF button  
until ON is displayed. The control module will override all  
other heat demands, however, all safeties will be active. If no  
buttons are pressed, the control module will automatically  
revert back to its original state after the Max Service Time  
delay has expired. The default setting for the Max Service  
Time is 20 minutes. To take the control module out of Service  
Mode, press the ON/OFF button until OFF is displayed.  
Main button - Pressing this button displays the Main Screen.  
From this screen, navigation to eight (8) other screens is  
possible. Reference the Main Screen on page 17 for more  
information regarding this screen.  
Items that can be viewed and interacted with on the Service  
Mode Screen are as follows:  
• Blower Power Level Indicator - A blower is depicted on  
the display with a power level indicator beside it. The  
level will increase and decrease indicating the  
approximate power level of the blower. The display box  
underneath the indicator level will display the firing rate  
of the control module.  
• RPM’s - The blower motor rpm that the control module  
is requiring of the blower.  
• Plus and Minus Buttons - By pressing the plus or minus  
button the rpm of the blower motor can be increased or  
decreased.  
• Flame Signal - The flame signal for the control module  
will be displayed in dc microamps.  
35  
Service Manual  
2 Maintenance  
Maintenance and annual startup  
Table 2A Service and Maintenance Schedules  
Owner maintenance  
Service technician  
(see the SYNC User’s Information Manual for  
instructions)  
(see the following pages for instructions)  
General:  
• Address reported problems  
• Check boiler area  
• Inspect interior; clean and vacuum if  
necessary;  
Daily  
Check pressure/temperature  
gauge  
• Clean condensate trap and fill with fresh  
water  
• Check for leaks (water, gas, flue,  
condensate)  
• Verify flue and air lines in good condition  
and sealed tight  
• Check vent piping  
• Check air piping  
• Check system water pressure/system  
piping/expansion tank  
• Check air and vent termination  
screens  
Monthly  
• Check control settings  
• Check ignition and flame sense  
electrodes (sand off any deposits; clean  
and reposition)  
• Check relief valve  
• Check condensate drain system  
• Check wiring and connections  
Check  
automatic  
air  
vents  
Perform start-up checkout and  
performance verification per Section 9  
in the SYNC Installation and  
Operation Manual.  
• Test low water cutoff  
• Reset button (low water cutoff)  
Every  
• Flame inspection (stable, uniform)  
6 months  
• Check boiler piping (gas and  
water) for leaks  
• Flame signal (at least 10 microamps at  
high fire)  
Clean the heat exchanger if flue  
temperature is more than 54°F (30°C)  
above return water temperature.  
• Operate relief valve  
• Test low water flow conditions.  
If combustion or performance  
indicate need:  
End  
of season  
months  
Shut boiler down (unless boiler  
used for hot water generation)  
• Clean heat exchanger  
• Remove and clean burner using  
compressed air only  
• Clean the blower wheel  
36  
Service Manual  
2 Maintenance  
(continued)  
Follow the service and maintenance procedures given throughout this manual and in component literature  
shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler  
or system. Failure to follow the directions in this manual and component literature could result in severe  
personal injury, death, or substantial property damage.  
ƽ WARNING  
The boiler should be inspected annually only by a qualified service technician. In addition, the maintenance  
and care of the boiler designated in Table 2A and explained on the following pages must be performed to  
assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could  
result in equipment failure.  
ƽ WARNING  
Electrical shock hazard – Turn off power to the boiler before any service operation on the boiler except as  
noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock,  
causing severe personal injury or death.  
ƽ WARNING  
Address reported problems  
Figure 2-1 Condensate Trap  
1. Inspect any problems reported by the owner and correct  
before proceeding.  
2” PVC CAP WITH  
BLOCKED DRAIN SWITCH  
Inspect boiler area  
RETAINING  
SCREW  
PVC TEE ASSEMBLY  
(FACTORY SUPPLIED)  
1. Verify that boiler area is free of any combustible materials,  
gasoline and other flammable vapors and liquids.  
CONDENSATE FROM  
HEAT EXCHANGER  
2. Verify that air intake area is free of any of the contaminants  
listed in Section 1 of the SYNC Installation and Operation  
Manual. If any of these are present in the boiler intake  
air vicinity, they must be removed. If they cannot be  
removed, reinstall the air and vent lines per this manual  
and the SYNC Installation and Operation Manual.  
TO FLOOR  
DRAIN  
Inspect boiler interior  
1. Remove the front access cover and inspect the interior of  
the boiler.  
The condensate trap must be filled with  
water during all times of boiler operation  
to avoid flue gas emission from the  
condensate drain line. Failure to fill the  
trap could result in severe personal injury  
or death.  
ƽ WARNING  
2. Vacuum any sediment from inside the boiler and  
components. Remove any obstructions.  
Clean condensate trap  
Check all piping for leaks  
1. Inspect the condensate drain line, condensate PVC  
fittings, and condensate trap.  
Eliminate all system or boiler leaks.  
ƽ WARNING  
Continual fresh makeup water will  
reduce boiler life. Minerals can build  
up in sections, reducing heat transfer,  
overheating heat exchanger, and causing  
heat exchanger failure. Leaking water may  
also cause severe property damage.  
2. Remove the PVC cap retaining screw from the PVC cap  
(FIG. 2-1).  
3. Remove the 2 inch PVC cap with the switch located at the  
top of the trap (FIG. 2-1).  
4. Remove any sediment in the trap.  
1. Inspect all water and gas piping and verify to be leak free.  
5. Fill with fresh water until the water begins to pour out of  
the drain.  
2. Look for signs of leaking lines and correct any problems  
found.  
6. Replace the cap. Press the cap onto the trap until the cap  
makes contact with the drain.  
3. Check gas line using the procedure found in Section 6 -  
Gas Connections of the SYNC Installation and Operation  
Manual.  
7. Replace the retaining screw.  
37  
Service Manual  
2 Maintenance  
Safety relief valves should be re-inspected  
AT LEAST ONCE EVERY THREE YEARS,  
by a licensed plumbing contractor or  
authorized inspection agency, to ensure  
that the product has not been affected by  
corrosive water conditions and to ensure  
that the valve and discharge line have not  
been altered or tampered with illegally.  
Certain naturally occurring conditions  
may corrode the valve or its components  
over time, rendering the valve inoperative.  
Such conditions are not detectable unless  
the valve and its components are physically  
removed and inspected. This inspection  
must only be conducted by a plumbing  
contractor or authorized inspection  
agency – not by the owner. Failure to  
re-inspect the boiler relief valve as directed  
could result in unsafe pressure buildup,  
which can result in severe personal injury,  
death, or substantial property damage.  
Flue vent system and air piping  
ƽ WARNING  
1. Visually inspect the entire flue gas venting system and air  
piping for blockage, deterioration or leakage. Repair any  
joints that show signs of leakage. Verify that air inlet pipe  
is connected and properly sealed.  
2. Verify that boiler vent discharge and air intake are clean  
and free of obstructions.  
Failure to inspect for the above conditions  
and have them repaired can result in  
severe personal injury or death.  
ƽ WARNING  
Check water system  
1. Verify all system components are correctly installed and  
operational.  
2. Check the cold fill pressure for the system. Verify it is  
correct (must be a minimum of 12 psi (82.7 kPa)).  
3. Watch the system pressure as the boiler heats up (during  
testing) to ensure pressure does not rise too high.  
Excessive pressure rise indicates expansion tank sizing or  
performance problem.  
Following installation, the valve lever  
must be operated AT LEAST ONCE  
A YEAR to ensure that waterways are  
ƽ WARNING  
clear.  
Certain naturally occurring  
4. Inspect automatic air vents and air separators. Remove  
air vent caps and briefly press push valve to flush vent.  
Replace caps. Make sure vents do not leak. Replace any  
leaking vents.  
mineral deposits may adhere to the valve,  
rendering it inoperative. When manually  
operating the lever, water will discharge  
and precautions must be taken to avoid  
contact with hot water and to avoid water  
damage. Before operating lever, check  
to see that a discharge line is connected  
to this valve directing the flow of hot  
water from the valve to a proper place of  
disposal. Otherwise severe personal injury  
may result. If no water flows, valve is  
inoperative. Shut down the boiler until a  
new relief valve has been installed.  
Check expansion tank  
1. Expansion tanks provide space for water to move in  
and out as the heating system water expands due to  
temperature increase or contracts as the water cools.  
Tanks may be open, closed or diaphragm or bladder type.  
See Section 6 - Hydronic Piping of the SYNC Installation  
and Operation Manual for suggested best location of  
expansion tanks and air eliminators.  
2. After following the above warning directions, if the relief  
valve weeps or will not seat properly, replace the relief  
valve. Ensure that the reason for relief valve weeping is  
the valve and not over-pressurization of the system due  
to expansion tank waterlogging or undersizing.  
Check boiler relief valve  
1. Inspect the relief valve and lift the lever to verify flow.  
Before operating any relief valve, ensure that it is piped  
with its discharge in a safe area to avoid severe scald  
potential. Read Section 6 - Hydronic Piping of the SYNC  
Installation and Operation Manual before proceeding  
further.  
38  
Service Manual  
2 Maintenance  
(continued)  
Inspect ignition and flame sense Check burner flame  
electrodes  
1. Inspect flame through observation window.  
1. Remove the ignition and flame sense electrodes from the  
boiler heat exchanger access cover.  
2. If the flame is unsatisfactory at either high fire or low fire,  
turn off boiler and allow boiler to cool down. Remove the  
burner and clean it thoroughly using a vacuum cleaner or  
compressed air. Do not use compressed air to clean burner  
if performed inside a building.  
2. Remove any deposits accumulated on the ignition/flame  
sense electrode using sandpaper. If the electrodes cannot  
be cleaned satisfactorily, replace with new ones.  
3. Remove the burner, reference FIG. 2-2.  
3. Replace ignition/flame sense electrode, making sure  
gasket is in good condition and correctly positioned.  
4. When replacing the burner, ensure gasket is in good  
condition and positioned correctly (FIG. 2-2).  
Check ignition ground wiring  
Figure 2-2 Burner Assembly  
1. Inspect boiler ground wire from the heat exchanger  
access cover to ground terminal strip.  
DOOR FIBER  
2. Verify all wiring is in good condition and securely  
attached.  
BURNER DOOR  
BURNER DOOR  
HEX NUT (6)  
BURNER  
3. Check ground continuity of wiring using continuity  
meter.  
AIR/GAS GASKET  
4. Replace ground wires if ground continuity is not  
satisfactory.  
IGNITER GASKET  
FLAPPER VALVE  
SCREW (5X)  
IGNITER  
FLAME SENSE  
GASKET  
IGNITER SCREW (2X)  
FLAPPER VALVE  
FLAME SENSE  
FLAME SENSE  
SCREW (2X)  
Check all boiler wiring  
1. Inspect all boiler wiring, making sure wires are in good  
condition and securely attached.  
Check control settings  
1. Go to the Setup Screen and check all settings. See Section  
1 of this manual. Adjust settings if necessary. See Section  
1 of this manual for adjustment procedures.  
2. Check settings of external limit controls (if any) and  
adjust if necessary.  
Perform start-up and checks  
1. Start boiler and perform checks and tests specified  
in Section 9 - Start-up of the SYNC Installation and  
Operation Manual.  
2. Verify cold fill pressure is correct and that operating  
pressure does not go too high.  
39  
Service Manual  
2 Maintenance  
(continued)  
5. Remove the condensate hose from the heat exchanger end.  
Connect a field supplied 3/4” diameter hose to a drain pan.  
Using field supplied means, cover the refractory in the back  
of the combustion chamber of the heat exchanger.  
Check flame signal  
1. At high fire the flame signal shown on the display should  
be at least 10 microamps.  
6. Use a vacuum cleaner to remove any accumulation on the  
boiler heating surfaces. Do not use any solvent.  
2. A lower flame signal may indicate a fouled or damaged  
flame sense electrode. If cleaning the flame sense  
electrode does not improve, ground wiring is in good  
condition, and ground continuity is satisfactory, replace  
the flame sense electrode.  
7. Brush the heat exchanger while dry using a nylon bristle  
brush. Caution: DO NOT use a metal brush. Re-vacuum  
the heat exchanger.  
8. Finish cleaning using a clean cloth dampened with warm  
water. Rinse out debris with a low pressure water supply.  
3. See Section 3 - Troubleshooting in this manual for other  
procedures to deal with low flame signal.  
9. Allow the heat exchanger to thoroughly dry.  
10. Remove the field supplied rear refractory cover from the  
back of the combustion chamber of the heat exchanger and  
reassemble.  
Review with owner  
1. Review the SYNC User’s Information Manual with the  
owner.  
11. Close isolation valves on piping to isolate boiler from  
system. Attach a hose to the boiler drain and flush boiler  
thoroughly with clean water by using purging valves to  
allow water to flow through the water make-up line to the  
boiler.  
2. Emphasize the need to perform the maintenance schedule  
specified in the SYNC User’s Information Manual (and in  
this manual as well).  
12. Perform start-up and check-out procedures in the Check  
Flame and Combustion Section of the SYNC Installation  
and Operation Manual.  
3. Remind the owner of the need to call a licensed contractor  
should the boiler or system exhibit any unusual behavior.  
13. Replace the access cover and restore boiler to operation.  
4. Remind the owner to follow the proper shutdown  
procedure and to schedule an annual start-up at the  
beginning of the next heating season.  
Table 2B Heat Exchanger Cleaning Kits  
Model  
Kit  
Part  
Component  
Description  
Cleaning boiler heat exchanger  
Number Number Number  
For recommended materials; including brush, appropriate  
extension(s), refractory cover, and detailed instructions see  
Table 2B - Heat Exchanger Cleaning Kits.  
MSC20083* Nylon 4” Wheel Brush*  
SB 1.0 - 1.5 KIT30064 MSC20085 1/4” x 12” Drill Extension  
MSC20086 1/4” x 24” Drill Extension  
1. Shut down boiler:  
• Follow the “To Turn Off Gas to Appliance” instructions  
for the boiler in the SYNC Installation and Operation  
Manual.  
• Do not drain the boiler unless it will be exposed to  
freezing temperatures. If using freeze prevention fluid  
in system, do not drain.  
* Do NOT use a metal brush. Only use  
ƽ CAUTION  
the kit provided brush or an equivalent  
replacement nylon brush.  
2. Allow time for the boiler to cool to room temperature if  
it has been firing.  
3. Remove the nuts securing the heat exchanger access  
cover to the heat exchanger and set aside.  
4. Remove the heat exchanger access cover, burner, and  
gas/air arm assembly.  
The boiler contains ceramic fiber  
ƽ WARNING  
materials. Use care when handling these  
materials per instructions on page 3 of  
this manual. Failure to comply could  
result in severe personal injury.  
40  
Service Manual  
2 Maintenance  
Test low water flow conditions  
10. Restrict the isolation valve until both control modules have  
shut down. If both control modules have been shut down,  
the test was successful.  
This test is to be carried out once the  
NOTICE  
SYNC boiler is completely piped in  
11. Disconnect the jumper wire from the low voltage terminal  
strip connected in step 3.  
with adequate gas and water flow.  
Once the test is completed, ensure  
that the isolation valve is opened up to  
allow full water flow.  
12. If necessary, reset the demand configuration in the Service/  
Setup Menu to the required operational mode.  
NOTE: See Section 1 of this manual for complete details of  
the SmartTouch controls.  
Test procedure  
13. Completely open the isolation valve on the outlet piping of  
the boiler.  
1. Set the SYNC to operate with the demand configuration  
parameter set to 1 (Cascade Set Point Thermostat-  
Based).  
14. Resume operation.  
NOTE: This lockout is a soft lockout. Once the T has  
decreased to an acceptable level and there is a call for heat,  
the unit will fire again to meet the demand.  
NOTE: This can be accomplished by selecting the  
demand configuration parameter in the Service/Setup  
Menu. See Section 1 of this manual for complete details  
of the SmartTouch controls.  
Figure 2-3 Low voltage terminal strip & enable contacts  
2. Set the system setpoint to the max user setpoint. Max  
user setpoint will allow the boiler to operate without  
reaching this setpoint. The boiler will require a load  
large enough to dissipate a large portion of the heat it is  
generating.  
LOW VOLTAGE CONNECTION BOARD  
1
2
3
4
5
6
7
8
9
ALARM  
CONTACTS  
RUN TIME  
CONTACTS  
LOUVER  
PROVING  
MODULE 2  
FLOW SWITCH  
MODULE 1  
3. Simulate a call for heat by placing a jumper wire across  
the enable contacts on the low voltage terminal strip  
located at the rear of the unit (FIG. 2-3).  
10 FLOW SWITCH  
11 TANK  
12 THERMOSTAT  
ENABLE  
CONTACTS  
13 R  
14 W  
ENABLE  
LBL20052 REV  
B
15 SHIELD GND  
16 A  
17 B  
4. Allow the unit to progress through its normal diagnostics  
and pre-purge programming.  
18 SHIELD GND  
19 (+)  
10V INPUT  
0
-
20 (-)  
21 SYSTEM  
22 SENSOR  
23 OUT DOOR  
24 SENSOR  
25 TANK  
5. Allow the unit to fire and operate until the temperatures  
stabilize. This occurs when the inlet and outlet  
temperatures are rising together and the Delta T (T)  
is maintained.  
26 SENSOR  
27 SHIELD GND  
28 B  
29 A  
30 SHIELD GND  
6. When the unit stabilizes, begin to slowly shut off the  
isolation valve on the outlet piping of the boiler (see  
FIG. 2-4). This will begin to restrict the flow and  
simulate a low flow condition.  
Figure 2-4 Adjust outlet isolation valve  
7. While slowly shutting off the isolation valve, refer to  
the Burner Screen to watch the behavior of the boiler.  
On this screen, you will witness each individual control  
module modulating its’ respective burner’s firing rate  
while reacting to the rising T.  
ADJUST OUTLET  
ISOLATION VALVE  
ONLY  
8. When the T reaches 50˚F for an individual heat  
exchanger, the control for the heat exchanger will  
attempt to modulate the firing rate down to protect it  
from low flow conditions.  
9. When the T reaches 60˚F for an individual heat  
exchanger, the control module for the heat exchanger  
will turn off the respective burner.  
NOTE: The Temperature Menu will show the inlet and  
outlet temperatures for each individual heat exchanger.  
41  
Service Manual  
3 Troubleshooting  
Alarm Screen:  
Reset button - The RESET button must be pressed to reset an  
alarm. Once the button is pressed, the Reset Confirmation  
Screen appears. You are asked if you wish to reset the control  
module. If so, press the YES button. If you do not wish to reset  
the control module press the NO button. If neither button is  
pressed within 20 seconds, the screen will return to the Alarm  
Screen.  
If a fault occurs which requires a Manual Reset, the unit  
will go into a lockout condition and the Alarm Screen will  
be activated. The screen will switch between a black or red  
background every 5 seconds with the text “Alarm Unit Needs  
Servicing” shown on the display.  
A message box shows the alarm status of the two (2) control  
modules. Mod1 is for Control Module 1 and Mod2 is for  
Control Module 2. A description of the alarm will be beside  
the control module with the fault. If a control module does  
not have a fault, “No Alarm Present” will be in the text.  
Once the condition has been corrected and the alarm is reset,  
the Status Screen will be displayed.  
It is possible for one control module to be in alarm while the  
other continues to function. However, it will not be possible  
to view any other screens until the control module is reset.  
42  
Service Manual  
3 Troubleshooting  
(continued)  
Label all wires prior to disconnection  
when servicing controls. Wiring errors can  
cause improper and dangerous operation.  
Always disconnect power to the boiler  
before servicing. Failure to comply could  
result in severe personal injury, death, or  
substantial property damage.  
Figure 3-1 Control Module Fuses  
ƽ WARNING  
F3 - 1.25 AMP FUSE  
MAIN BOARD  
F4 - 3.15 AMP FUSE  
BLOWER  
Never jumper (bypass) any device except  
for momentary testing as outlined in the  
Troubleshooting chart. Severe personal  
injury, death, or substantial property  
damage can result.  
F5 - 5 AMP FUSE  
PUMPS  
F2 - 3.15 AMP FUSE  
24V SUPPLY  
ƽ WARNING  
Before troubleshooting:  
1. Have the following items:  
a. Voltmeter that can check 120 VAC, 24 VAC, and  
12 VDC.  
4. Remove the two (2) nuts on the control module cover.  
5. Inspect fuses F2, F3, F4, and F5, see FIG 3-1.  
b. Continuity checker.  
c. Contact thermometer.  
2. Check for 120 VAC (minimum 102 VAC to maximum  
132 VAC) to boiler.  
6. The boiler is shipped with six (6) spare fuses in a plastic  
bag located under the low water cutoff on the control  
module.  
3. Make sure thermostat is calling for heat and contacts  
(including appropriate zone controls) are closed. Check  
for 24 VAC between thermostat wire nuts and ground.  
7. If necessary, replace open fuse (F3 is 1.25 amps, F2 and F4  
are 3.15 amps, and F5 is 5 amps).  
4. Make sure all external limit controls are installed and  
operating.  
Note: Fuses F2 - F5 are all slow blow fuses.  
Do not jumper fuse or replace with any  
ƽ WARNING  
Check the following:  
1. Wire connectors to control module are securely plugged  
in at the control module and originating control.  
fuse except as specified. Failure to comply  
could result in severe personal injury,  
death, or substantial property damage.  
2. Gas pressures:  
8. Re-install the control module cover using the nuts  
removed in Step 4.  
• Maximum: 14 inches w.c. (3.5 kPa) natural,  
14 inches w.c. (3.2 kPa) LP with no flow (lockup)  
or with boiler on  
Note: If the spark wire was unplugged, reattach it to the  
control.  
• Minimum: 4 inches (5 inches on 1.0 models only) w.c.  
(1.0 kPa) natural, 8 inches w.c. (2.0 kPa) LP with gas  
flowing (verify during boiler startup)  
9. Re-install the control panel using the two (2) screws  
removed in Step 3. Re-install the front access cover after  
fuse inspection.  
10. Restore power to the boiler at the external line switch  
and verify boiler operation (Section 9 - Start-up in the  
SYNC Boiler Installation and Operation Manual) after  
completing boiler service.  
Check control module fuses  
ALWAYS check control module fuses  
NOTICE  
before replacing control module or any  
major components (blower, etc.). If one  
of these fuses is blown, it can prevent the  
control module or other components from  
operating.  
1. Turn OFF the power to the boiler at the external line  
switch.  
2. Remove the front access cover.  
3. Remove the two (2) screws securing the control panel to  
the unit to gain access to the control module.  
43  
Service Manual  
3 Troubleshooting  
Table 3A Troubleshooting Chart - No Display  
FAULT  
CAUSE  
CORRECTIVE ACTION  
- No 120 VAC supplied to unit.  
• Check external line switch, fuse, or breaker.  
• Check position of ON/OFF switch. Turn switch to the  
ON position.  
• Check 120 VAC through the ON/OFF switch.  
• Check wiring harness connection between display  
board and main control board. Connect  
harness at both points.  
No Display  
- No voltage through the switch.  
- Bad display board.  
• Replace switch.  
• Replace board.  
- Bad main control board.  
- Blown fuse.  
• Replace the main control board.  
• Replace fuse F3 on the main control board, see  
page 43 of this manual.  
- Main control board temperature set point • Review temperature setting.  
satisfied.  
- Remote thermostat satisfied.  
• Review remote thermostat setting.  
No Burner  
Operation  
- Outside air temperature above Warm • Check location of outside air sensor.  
Check  
Weather Shutdown (WWSD) set point for  
main control board.  
resistance of outdoor air sensor and compare to Table  
3D on page 45 of this manual.  
- Unit locked out on fault.  
- Ramp delay active.  
• Consult display for specific fault. Refer to fault  
descriptions on page 47 of this manual for corrective  
actions.  
• Check ramp delay parameter settings. Optional PC  
software required.  
• Turn ramp delay feature off. See page 19 of this  
manual for instructions on how to turn this feature off.  
Unit Does  
Not Modulate  
Above 50%  
• Check BMS parameter settings.  
software required.  
Optional PC  
- Boiler controlled by BMS.  
- Flue sensor open.  
• Verify that the flue sensor is located in the flue outlet.  
• Check wiring connections at the flue sensor.  
• Check the resistance of the flue sensor and compare  
to Table 3C on page 45 of this manual.  
44  
Service Manual  
3 Troubleshooting  
(continued)  
Checking temperature sensors  
The boiler temperature sensors (inlet water, outlet water, system water, flue, and outdoor air) are all resistance type devices. The  
following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the  
sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor.  
Table 3B - Inlet/Outlet System Sensor Resistance vs. Temperature  
Temperature  
Resistance  
Temperature  
Resistance  
50  
68  
18,780  
12,263  
8,194  
5,592  
3,893  
2,760  
158  
176  
194  
212  
--  
1,990  
1,458  
1,084  
817  
--  
86  
104  
122  
140  
--  
--  
Table 3C - Flue Temperature Sensor Resistance vs. Temperature  
Temperature  
Resistance  
Temperature  
Resistance  
68  
14,773  
9,804  
6,652  
4,607  
3,252  
2,337  
176  
194  
212  
230  
248  
--  
1,707  
1,266  
952  
726  
560  
--  
86  
104  
122  
140  
158  
Table 3D - Outdoor Air Sensor Resistance vs. Temperature  
Temperature  
Resistance  
Temperature  
Resistance  
-50  
-40  
-30  
-20  
10  
490,813  
336,606  
234,196  
165,180  
118,018  
85,362  
20  
30  
40  
50  
60  
70  
80  
46,218  
34,558  
26,099  
19,900  
15,311  
11,883  
9,299  
0
10  
62,465  
45  
Service Manual  
3 Troubleshooting  
Table 3E Troubleshooting Chart - Noisy System  
FAULT  
CAUSE  
CORRECTIVE ACTION  
- Supply gas problem. Natural gas pressures  
should be between 4 inches w.c. (1.0 kPa)  
and 14 inches w.c. (3.5 kPa). LP gas  
pressures should be between 8 inches w.c.  
(2.0 kPa) and 14 inches w.c. (3.2 kPa).  
• Refer to Section 6 - Gas Connections of the SYNC  
Installation and Operation Manual for detailed  
information concerning the gas supply.  
• Refer to the Gas Valve Adjustment Procedure on  
page 55 of this manual for the proper gas valve setting.  
Verify that the vent/air intake lengths do not exceed the  
maximum listed in the General Venting section of the  
SYNC Installation and Operation Manual.  
- Gas/air mixture problem.  
- Dirty/damaged burner.  
Noisy  
Operation  
• Refer to page 39 in this manual for the burner removal  
and inspection procedure. Clean or replace the burner  
as necessary.  
• Refer to Section  
6
-
Hydronic Piping of the  
SYNC Installation and Operation Manual for  
- Low water flow through the heat exchanger. minimum flow rates. Verify that the boiler is piped in a  
primary/secondary fashion and that the boiler and  
system pump are running on a call for heat.  
- Air in the piping system.  
• Properly purge all air from the piping system.  
• Verify system pressure is a minimum of 12 psi  
(82.7 kPa).  
- Low system water pressure.  
• Replace fuse F5 on the control board, see page 43 of  
this manual.  
- Blown fuse.  
No Pump  
Operation -  
Boiler Pump  
System Pump  
or  
- Faulty pump.  
• Replace pump.  
- Internal fault on control board.  
- Faulty pump relay.  
• Replace main control board.  
• Replace relay.  
HW Pump  
• Lower the system pressure below the 50 psi  
(344.7 kPa) rating of the supplied relief valve or replace  
Relief Valve  
Opening  
- System pressure exceeds relief valve the standard relief valve with a higher rated valve up to  
setting.  
the maximum pressure of the heat exchanger.  
• Improperly sized expansion tank.  
• Reset the pressure switches.  
• Measure the supply gas pressure to determine cause  
of failure. Natural gas pressures should be between  
4 - 14 inches w.c. (1.0 - 3.5 kPa) and LP gas  
pressures should be between 8 - 14 inches w.c.  
(2.0 - 3.2 kPa).  
Gas Pressure  
Switch  
(will require a  
Either the manual reset low gas pressure  
switch or the manual reset high gas pressure  
switch tripped.  
manual reset once  
the condition has  
been corrected.  
Press the RESET  
button on the  
• Refer to Section 6 - Gas Connections of the SYNC  
Installation and Operation Manual for detailed  
information concerning the gas supply.  
display to reset.)  
• Correct the supply gas pressure if necessary.  
• Check for a loose or misplaced jumper if pressure  
switches are not installed.  
46  
Service Manual  
3 Troubleshooting  
(continued)  
Table 3F Troubleshooting Chart - Fault Messages Displayed on Boiler Interface  
FAULT  
DESCRIPTION  
CORRECTIVE ACTION  
• Check boiler pump operation on a call for heat.  
• Check for closed valves or obstructions in the boiler  
piping.  
Flow Switch/  
LWCO  
Either the low water cutoff or the optional  
flow switch is not making.  
• Verify system is full of water and all air has been  
purged from the system.  
(will require a manual  
reset once condition has  
been corrected. Press  
the RESET button on  
the display to reset.)  
• Check for loose or misplaced jumpers if flow switch is  
not installed.  
• Replace fuse F2 on the control board, see page 43 of  
this manual.  
Blown fuse.  
• Check condensate tube from unit to floor drain for  
proper installation and obstructions.  
Condensate  
Drain Blocked  
• Inspect condensate trap for blockage. Clean if  
necessary.  
(will require a manual The blocked drain switch has detected  
excessive condensate build up inside the  
unit.  
reset once condition has  
been corrected. Press  
the RESET button on  
the display to reset.)  
• Check for loose wiring connection at wire harness  
plug.  
• Bad blocked drain switch. Replace switch.  
Flame out of  
Sequence  
• Check supply voltage for proper polarity.  
• Check external wiring for voltage feedback.  
• Check the flame rod and make sure it is clean.  
• Check the internal wiring for bad connections.  
• Replace main control board.  
(will require a manual  
reset once the condition  
has been corrected.  
The flame detector circuit is seeing a flame  
signal while no flame is present.  
Press the RESET button  
on the display to reset.)  
Gas Valve /  
Connection  
• Check wiring harness connection at the gas valve and  
at the main control board.  
(will require a manual  
reset once the condition  
has been corrected.  
The main control board did not detect the  
gas valve.  
• Replace the gas valve wire harness.  
• Replace the gas valve.  
Press the RESET button  
on the display to reset.)  
• Replace the main control board.  
• Inspect spark electrode and associated wiring for  
damage and connection. Reference page 39 of this  
manual for removal and cleaning procedures.  
Replace if necessary.  
• Check for proper electrical grounding of the unit.  
• Check incoming supply gas pressure. Natural gas  
pressures should be between 4 - 14 inches w.c.  
(1.0 - 3.5 kPa) and LP gas pressures should be  
between 8 - 14 inches w.c. (2.0 - 3.2 kPa). Refer  
to Section 6 - Gas Connections of the SYNC  
Installation and Operation Manual for detailed  
information concerning the gas supply.  
Burner Did Not  
Light  
The unit has failed to prove main burner  
ignition after one attempt. It will require a  
manual reset before attempting to fire again.  
(will require a manual  
reset once the condition  
has been corrected.  
Press the RESET button  
on the display to reset.)  
• Verify that the plastic hose from the gas valve to the  
air inlet is connected and is not damaged.  
• Verify that the vent/air intake pipes are correctly  
installed and that there are no obstructions.  
• Check for 24 VAC to the gas valve at the 2-pin  
connection on the side of the main control board  
during the ignition attempt. If no voltage is present,  
replace the main control board.  
47  
Service Manual  
3 Troubleshooting  
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface  
FAULT  
DESCRIPTION  
CORRECTIVE ACTION  
• If 24 VAC is present at the main control board, check  
the wiring between the main control board and the gas  
valve. Replace the wiring if necessary. Do not  
disconnect the wiring from the gas valve and attempt  
to measure voltage at that point. The main control  
board can detect if the gas valve is not connected and  
will display the Gas Valve / Connection fault.  
• If 24 VAC is present, check the outlet of the valve to  
ensure the valve is flowing gas. With a manometer  
connected to the outlet tap of the gas valve, when the  
unit is in the prepurge period, there should be a  
negative pressure present. When the valve is  
energized a change in pressure should occur. If the  
pressure change does not occur, the gas valve is not  
opening. Replace the gas valve.  
Burner Did Not  
Light (cont’d)  
The unit has failed to prove main burner  
ignition after one attempt. It will require a  
manual reset before attempting to fire again.  
(will require a manual  
reset once the condition  
has been corrected.  
Press the RESET button  
on the display to reset.)  
• Inspect flame sensor and associated wiring.  
Reference page 39 of this manual for removal and  
cleaning procedures. Replace if necessary.  
• Inspect the burner. Reference page 39 of this manual  
for removal and cleaning procedures. Replace if  
necessary.  
• Replace the main control board.  
• Inspect spark electrode and associated wiring for  
damage and connection. Reference page 39 of this  
manual for removal and cleaning procedures.  
Replace if necessary.  
• Check for proper electrical grounding of unit.  
• Check incoming supply gas pressure. Natural gas  
pressures should be between 4 - 14 inches w.c.  
(1.0 - 3.5 kPa) and LP gas pressures should be  
between 8 - 14 inches w.c. (2.0 - 3.2 kPa).  
Refer to Section 6 - Gas Connections of the SYNC  
Installation and Operation Manual for detailed  
information concerning the gas supply.  
Flame Lost  
While Running  
(will require a manual  
reset once the condition  
has been corrected.  
The unit was running and lost the flame  
signal. This condition occurred twice .  
Press the RESET button  
on the display to reset.)  
• Verify that the plastic hose from the gas valve to the air  
inlet is connected and is not damaged.  
• Verify that the vent/air intake pipes are installed  
correctly and there are no obstructions.  
• Check for 24 VAC to the gas valve at the 2-pin  
connection on the side of the main control board  
during the ignition attempt. If no voltage is present,  
replace the main control board.  
48  
Service Manual  
3 Troubleshooting  
(continued)  
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface  
FAULT  
DESCRIPTION  
CORRECTIVE ACTION  
• If 24 VAC is present at the main control board, check  
the wiring between the main control board and the gas  
valve. Replace the wiring if necessary. Do not  
disconnect the wiring from the gas valve and attempt  
to measure voltage at that point. The main control  
board can detect if the gas valve is not connected and  
will display the Gas Valve / Connection fault.  
Flame Lost  
While Running  
(cont’d)  
• If 24 VAC is present, check the outlet of the valve to  
ensure the valve is flowing gas. With a manometer  
connected to the outlet tap of the gas valve, when the  
unit is in the prepurge period, there should be a  
negative pressure present. When the valve is  
energized a change in pressure should occur. If the  
pressure change does not occur, the gas valve is not  
opening. Replace the gas valve.  
The unit was running and lost the flame  
signal. This condition occurred twice .  
(will require a  
manual reset once the  
condition has been  
corrected. Press the  
RESET button on the  
display to reset.)  
• Inspect flame sensor and associated wiring.  
Reference page 39 of this manual for removal and  
cleaning procedures. Replace if necessary.  
• Inspect the burner. Reference page 39 of this manual  
for removal and cleaning procedures. Replace if  
necessary.  
• Replace the main control board.  
• Verify that the system is full of water and that all air  
has been properly purged from the system.  
• Verify that the boiler is piped properly into the heating  
system. Refer to Section 6 - Hydronic Piping of the  
SYNC  
Installation  
and  
Operation  
Manual  
for the proper piping methods for the SYNC.  
• Check voltage to boiler pump motor on a call for  
heat. If voltage is not present, check wiring back to  
the pump relay.  
Manual Reset  
High Limit  
• Replace the pump relay if necessary.  
(will require a  
• If 120 VAC is present on a call for heat and the boiler  
pump is not operating, replace the pump.  
manual reset once the  
condition has been  
corrected. Press the  
RESET button on the  
display to reset.)  
The outlet water temperature has exceeded  
the setting of the high limit.  
• If the system pump is a variable speed pump, ensure  
that the system flow is not less than the boiler flow.  
• If operating on either an inlet or system supply  
sensor, check temperature setting of the main control  
board.  
• If the high limit has tripped, check setting of the  
device.  
• Check resistance of water sensors and compare to  
Table 3B on page 45 of this manual. Replace sensor  
if necessary.  
• Replace high limit.  
49  
Service Manual  
3 Troubleshooting  
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface  
FAULT  
DESCRIPTION  
CORRECTIVE ACTION  
Automatic Reset High Limit:  
• Verify that the system is full of water and that all air  
has been properly purged from the system.  
• Verify that the boiler is piped properly into the heating  
system. Refer to Section 6 - Hydronic Piping of the  
SYNC Installation and Operation Manual  
for the proper piping methods for the SYNC.  
• Check voltage to boiler pump motor on a call for  
heat. If voltage is not present, check wiring back to  
the pump relay.  
• Replace the pump relay if necessary.  
• If 120 VAC is present on a call for heat and the boiler  
pump is not operating, replace the pump.  
Automatic Reset  
High Limit / HEX-  
Temp SW  
• If the system pump is a variable speed pump, ensure  
that the system flow is not less than the boiler flow.  
• If operating on either an inlet or system supply  
sensor, check temperature setting of the main control  
board.  
Either the auto-reset high limit (optional),  
or the O-temp heat exchanger switch as  
opened.  
(will require a manual  
reset once the condition  
has been corrected. Press  
the RESET button on the  
display to reset.)  
• If the high limit has tripped, check setting of the  
device.  
• Check resistance of water sensors and compare to  
Table 3B on page 45 of this manual. Replace sensor  
if necessary.  
• Replace high limit.  
HEX Temp SW:  
• Check continuity across two contacts. Wires should  
be connected at both poles of normally closed switch.  
• Inspect the rear of the inner combustion chamber  
at the burner level, for refractory breakdown/missing.  
Replace the refractory if no damage to the heat  
exchanger as a result of the burner, otherwise,  
replace the heat exchanger.  
• Faulty O-temp heat exchanger switch. Replace  
switch.  
• Vent/air intake lengths exceed the maximum allowed  
lengths. Refer to Section 2 - General Venting of the  
SYNC Installation and Operation Manual for  
proper lengths.  
The actual fan rpm is 30% lower than what  
is being called for. Reference the Burners  
Screen information on page 32 of this  
manual.  
Blower RPM’s  
Too Low  
• Check for obstruction or blockage in the vent/air  
intake pipes or at terminations.  
(will require a manual  
reset once the condition  
has been corrected. Press  
the RESET button on the  
display to reset.)  
• Check the wiring connections at the fan and at the  
main control board.  
• Replace the fan.  
• Replace the main control board.  
• Replace fuse F4 on the control board, see page 43 of  
this manual.  
Blown fuse.  
50  
Service Manual  
3 Troubleshooting  
(continued)  
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface  
FAULT  
DESCRIPTION  
CORRECTIVE ACTION  
• Vent/air intake lengths exceed the maximum allowed  
lengths. Refer to Section 2 - General Venting of the  
SYNC Installation and Operation Manual for  
proper lengths.  
Blower RPM’s  
Too High  
• Check for obstruction or blockage in the vent/air  
intake pipes or at terminations.  
(will require a manual  
reset once the condition  
has been corrected. Press  
the RESET button on the  
display to reset.)  
The actual fan rpm is 30% higher than what  
is being called for.  
• Check the wiring connections at the fan and at the  
main control board.  
• Replace the fan.  
• Replace the main control board.  
• Check the sensors and their associated wiring.  
Repair or replace the sensor or wiring if damaged.  
Either the inlet water or outlet water • Measure the resistance of the sensors and compare  
Sensor Open  
(will require a manual  
reset once the condition  
has been corrected. Press  
the RESET button on the  
display to reset.)  
temperature sensor has been disconnected.  
the resistance to the tables on page 45 of this  
manual.  
• Replace the sensor if necessary.  
• Check the sensors and their associated wiring.  
Repair or replace the sensor or wiring if damaged.  
Sensor Shorted  
(will require a manual  
reset once the condition  
has been corrected. Press  
the RESET button on the  
display to reset.)  
Either the inlet water or outlet water • Measure the resistance of the sensors and compare  
temperature sensor has been shorted.  
the resistance to the tables on page 45 of this  
manual.  
• Replace the sensor if necessary.  
• Check the sensor and its associated wiring. Repair  
or replace the sensor or wiring if damaged.  
Flue Sensor  
Open / Removed  
(will require a manual  
reset once the condition  
has been corrected. Press  
the RESET button on the  
display to reset.)  
• Measure the resistance of the sensors and compare  
the resistance to the tables on page 45 of this  
manual.  
The flue sensor has been disconnected or  
removed from the flue.  
• Replace the sensor in flue.  
• Replace the sensor if necessary.  
• Check the sensor and its associated wiring. Repair  
or replace the sensor or wiring if damaged.  
Flue Sensor  
Shorted  
(will require a manual  
reset once the condition  
has been corrected. Press  
the RESET button on the  
display to reset.)  
• Measure the resistance of the sensors and compare  
the resistance to the tables on page 45 of this  
manual.  
The flue sensor has been shorted.  
• Replace the sensor if necessary.  
Louver Proving  
Switch  
• Check function of remote devices.  
(will require a manual  
reset once the condition  
has been corrected. Press  
the RESET button on the  
display to reset.)  
An optional remote proving switch is not  
making.  
• Check for loose or misplaced jumper if proving switch  
is not installed.  
Sensors equipped with an internal limit (such  
as the Lochinvar Squire Indirect Tank), the  
limit has opened due to temperature (195°F)  
or the sensor has become disconnected.  
• Check the tank temperature.  
®
• Repair or replace the sensor wiring if damaged.  
• Replace the sensor if necessary.  
Tank Open  
51  
Service Manual  
3 Troubleshooting  
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface  
FAULT  
DESCRIPTION  
CORRECTIVE ACTION  
Air pressure switch contacts are open.  
• Check the wiring connections to switch. Wires should  
be connected to the common and normally closed  
terminals.  
• Vent/air intake lengths exceed the maximum allowed  
lengths. Refer to Section 2 - General Venting of the  
SYNC Installation and Operation Manual for  
proper lengths.  
• Check for obstruction or blockage in the vent/air  
intake pipes or at terminations.  
• Check reference hoses connected to the air pressure  
switch for blockage or obstruction.  
Air Flow Too  
Low  
• Inspect the burner. Reference page 39 of this manual  
for removal and cleaning procedures. Replace if  
necessary.  
(will require a manual  
reset once the condition  
has been corrected.  
Press the RESET button  
on the display to reset.)  
• Inspect the heat exchanger. Reference page 40 of  
this manual for removal and cleaning procedures.  
Replace if necessary.  
• Faulty air pressure switch. Replace switch.  
• Check the wiring connections to the flap valve switch.  
Replace or repair wiring if necessary.  
• Check for obstruction in the vent / air intake pipes or  
at terminations.  
Flap valve contacts are in an open position.  
• Verify combustion air blower is operating. Replace if  
necessary.  
• Replace flap valve switch.  
• Check wiring connections to the flap valve switch.  
Replace or repair wiring if necessary.  
Flap Valve  
Stuck Open  
Flap valve contacts are in a closed position.  
• Check flap valve for obstruction or blockage.  
• Replace flap valve switch.  
• Wait 15 minutes and try again.  
Too Many  
Resets - Try Later  
Too many manual resets have occurred  
during a 15 minute period.  
• Turn power off to unit, wait 30 seconds and then turn  
power back on.  
• Check 120 VAC supply to the transformer.  
• Check wiring connections at the low voltage terminal  
strip.  
Voltage Too  
Low  
120 VAC input to the main control board has  
dropped below 80 VAC.  
• Check the wire size/length to remote devices.  
• Replace the main control board.  
52  
Service Manual  
3 Troubleshooting  
(continued)  
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface  
FAULT  
DESCRIPTION  
CORRECTIVE ACTION  
The main control board has detected an  
internal fault.  
• Replace the main control board.  
Internal Fault  
Writing to  
Memos  
The main control board has detected an  
internal fault.  
• Replace the main control board.  
• Replace the main control board.  
The main control board has detected an  
internal fault.  
CRC Parameters  
No Error Stored  
The main control board has detected an • Press the RESET button on the SMART  
internal fault.  
TOUCH display panel.  
• Inspect the heat exchanger. Reference page 40 of  
this manual for the procedure on how to clean the  
flue side of the heat exchanger.  
• Inspect the flue sensor and associated wiring.  
Measure the resistance of the flue sensor and  
compare to Table 3C on page 45 of this manual.  
Replace the sensor if necessary.  
Flue Temp  
Shutdown  
The stack temperature has exceeded the  
set parameters for the boiler.  
• Verify that the vent/air intake pipes are properly  
installed and that there are no obstructions.  
• Replace the main control board.  
• Verify that the system is full of water and that all air  
has been properly purged from the system.  
• Verify that the boiler is piped properly into the heating  
system. Refer to Section 6 - Hydronic Piping of the  
SYNC Installation and Operation Manual  
for the proper piping methods for the SYNC boiler.  
• Check for voltage to the boiler pump motor on a call  
for heat. If voltage is not present, check the wiring  
back to the pump relay. Replace the pump relay if  
necessary.  
Delta T  
Shutdown  
The temperature rise across the heat  
exchanger has exceeded the set parameters  
for the boiler.  
• If 120 VAC is present on a call for heat and the boiler  
pump is not operating, replace the pump.  
• Verify that the boiler pump is set to the proper speed  
or that the pump is the proper size. Reference  
Section  
6
-
Hydronic Piping of the SYNC  
Boiler Installation and Operation Manual for boiler  
pump specifications.  
• Verify that the system is full of water and that all air  
has been properly purged from the system.  
• Verify that the boiler is piped properly into the heating  
system. Refer to Section 6 - Hydronic Piping of the  
SYNC Installation and Operation Manual  
for the proper piping methods for the SYNC boiler.  
Outlet Temp  
Shutdown  
Outlet water temperature has exceeded the  
maximum outlet water temperature.  
• Check for voltage to the boiler pump motor on a call  
for heat. If voltage is not present, check wiring back  
to the pump relay. Replace the pump relay if  
necessary.  
• If 120 VAC is present on a call for heat and the boiler  
pump is not operating, replace the pump.  
53  
Service Manual  
3 Troubleshooting  
Combustion Analysis Procedure  
Table 3H Flue Products  
1. Turn the main power off to the boiler by placing the  
“On/Off” switch in the OFF position.  
Natural Gas  
Propane  
CO2 O2  
2. Remove the flue temperature sensors from the flue pipe  
connections. Note: Combustion measurements will be  
made at this point.  
CO2  
O2  
8.0% - 10% 3.0% - 6.5% 9.0% - 11% 4.1% - 6.9%  
3. Turn the main power on to the boiler by placing the  
“On/Off” switch in the ON position.  
8. Once the Heat Exchanger 1 analysis is complete, test the  
safety shutoff device by turning the manual shutoff valve  
to the OFF position and ensuring that Heat Exchanger  
1 shuts down and registers an alarm. Open the manual  
shutoff valve, reset the control, and return to Service  
Mode.  
4. Navigate to the Service Mode Screen from the Status  
Screen by pressing the MAIN button and then the  
SERVICE MODE button.  
5. On the Service Screen place Heat Exchanger 1 into  
operation by selecting Heat Exchanger 1 with the SELECT  
button and turning the heat exchanger on by pressing the  
ON/OFF button (OFF indicates that the heat exchanger  
is off and ON indicates that the heat exchanger should be  
firing).  
9. Repeat the same procedure for Heat Exchanger 2  
by selecting Heat Exchanger 2 while on the Service  
Mode Screen. Be certain to insert the probe from the  
combustion analyzer into the Heat Exchanger 2 flue  
temperature sensor location.  
6. Insert the probe from a combustion analyzer into the  
hole left by the removal of the flue temperature sensor.  
10. Turn the main power off to the boiler and replace the  
flue temperature sensor into the flue pipe connection.  
Note: Heat Exchanger 1 is the top heat exchanger; please  
11. Place the boiler back into normal operation.  
ensure the probe is in the top flue sensor location.  
You must replace the flue gas temperature  
ƽ WARNING  
7. Once the heat exchanger has modulated up to full fire  
measure the combustion. The values should be in the  
range listed in Table 3H above. CO levels should be  
less than 200 ppm for a properly installed unit. If the  
combustion is not within range reference the chart below  
for possible causes and corrective actions.  
sensor to prevent flue gas spillage into  
the room. Failure to comply could  
result in severe personal injury, death, or  
substantial property damage.  
Table 3G Troubleshooting Chart - Combustion Levels  
POSSIBLE CAUSE  
CORRECTIVE ACTION  
• Refer to Section 2 - General Venting of the SYNC Installation and Operation Manual  
for the proper venting and air intake methods for the SYNC boiler.  
Vent/Air Intake Length  
or Obstruction  
• Check for obstructions at the vent/air intake terminals.  
• Refer to Section 6 - Gas Connections of the SYNC Installation and Operation  
Manual for the proper gas supply for the SYNC boiler.  
Gas Supply Pressure  
• Refer to page 39 of this manual for burner removal and cleaning procedures.  
• Replace burner if necessary.  
Dirty/Damaged Burner  
Gas Valve Adjustment  
54  
• Refer to page 55 of this manual for the gas valve adjustment procedure.  
Service Manual  
3 Troubleshooting  
(continued)  
Models 1.3 - 1.5  
Gas valve adjustment procedure  
If adjustment of the gas valve is deemed necessary, use the  
following procedures: (Note: The procedures below are  
model specific.)  
Locate the throttle adjustment screw on top of the gas valve,  
see FIG. 3-3. Using an Allen wrench, turn the screw a 1/4  
turn counterclockwise to increase CO2 levels or a 1/4 turn  
clockwise to decrease CO2 levels. After one adjustment on  
the valve, follow the Combustion Analysis Procedure on page  
54 of this manual to measure the combustion.  
Under normal operating conditions this  
CAUTION  
valve should not need adjusting.  
Model 1.0  
If combustion is still not within the specified range, repeat  
the procedure. This procedure SHOULD NOT be performed  
more than four (4) times. If after four (4) adjustments and  
the combustion is still not within the specified range, revisit  
the possible causes in Table 3G on page 54 or replace the gas  
valve.  
Locate the throttle adjustment screw on top of the gas valve,  
see FIG. 3-2. Using a screwdriver, turn the screw a 1/4 turn  
counterclockwise to increase CO2 levels or a 1/4 turn  
clockwise to decrease CO2 levels. After one adjustment on  
the valve, follow the Combustion Analysis Procedure on  
page 54 of this manual to measure the combustion.  
Figure 3-3 Gas Valve Adjustment: Models 1.3 - 1.5  
If combustion is still not within the specified range,  
repeat the procedure. This procedure SHOULD NOT  
be performed more than four (4) times. If after four (4)  
adjustments and the combustion is still not within the  
specified range, revisit the possible causes in Table 3G on  
page 54 or replace the gas valve.  
THROTTLE ADJUSTMENT  
SCREW (REMOVE BLUE COVER)  
Figure 3-2 Gas Valve Adjustment: Model 1.0  
THROTTLE ADJUSTMENT SCREW  
55  
Revision Notes: Revision A (ECO #C02428) initial release.  
Revision B (ECO #C03046) reflects changes made to the History,  
Details, and Graphs screen shots (pgs. 15, 33 and 34).  
Revision C (ECO #CO2918) reflects the addition of Tank Sensor Open  
on page 50.  
Revision D (ECO #C04062) reflects changes to the terminology in all  
SYNC manuals and labels from module to heat exchanger (exception:  
control module), edits made to the ceramic fiber material warning,  
removal of the stabilitor from FIG. 2-2 (C04057) along with the addition  
of the Low Water Flow Test Procedure (R02559).  
Revision E (ECO #C04560) reflects the addition of Modbus to the  
manual and a new heat exchanger cleaning procedure.  
Revision F (ECO #C06388) reflects the correction of “Manual Reset  
High Limit” instructions on page 15.  
Revision G (ECO C07981) reflects the addition of the O-temp switch  
(Table 3F) and edits made to the Inputs diagram on page 7.  
Revision H (ECO C09659) reflects the update of information within  
Section 3 “Troubleshooting” on page 43.  
SYNC-SER Rev H  
01/12  

Rockford Fosgate FRC3204 User Manual
Raypak XTHERM 1505 User Manual
Philips Stereo System MCM1120 User Manual
Philips AQ5150 User Manual
Panasonic Palmcorder PV DV950 User Manual
Orion Car Audio HCCA COMPETITION HCCA102 User Manual
Olympus FL 20 User Manual
NAD Blu ray Disc Player T557 User Manual
Motorola H17 Bluetooth Earset 89334N User Manual
KitchenAid 4KFPW760WH1 User Manual