Crown Boiler BWC300 User Manual

Table 1.1: Summary of PPs Flex Venting Options  
VENT OPTION #  
9
10  
PPs FLEX  
(MASONRY)  
PPs FLEX  
(MASONRY)  
CLASSIFICATION USED IN THIS MANUAL  
ILLUSTRATED IN FIGURE  
1.0  
CHIMNEY CAP  
CHIMNEY CAP  
6” DIA  
1.0  
CHIMNEY CAP  
CHIMNEY CAP  
7” DIA  
VENT PIPE PENETRATION THROUGH STRUCTURE  
AIR INTAKE PENETRATION THROUGH STRUCTURE  
MIN CHASE ID (ROUND)  
6” x 6”  
80 mm  
7” x 7”  
MIN CHASE ID (RECTANGULAR)  
NOMINAL PPs FLEX LINER SIZE  
CONCENTRIC VENT/INTAKE CONNECTOR SIZE  
BWC070  
100mm  
80/125  
100/150  
51ft  
BWC090  
51ft  
BWC120  
51ft  
BWC151  
BWC150  
BWC225  
BWC300  
BWC070  
BWC090  
BWC120  
BWC151  
51ft  
47ft  
45ft  
68ft  
51ft  
51ft  
51ft  
51ft  
BWC150  
BWC225  
47ft  
45ft  
68ft  
32ft  
BWC300  
32ft  
MAX CHASE HEIGHT  
CROWN PPs FLEX LINER PART # (32ft COIL)  
CROWN PPs FLEX INSTALLATION KIT PART #  
230955  
230958  
230956  
230959  
3
WARNING  
Failure to ensure that the chimney is clean, leak tight, water tight, and structurally sound could result in severe  
corrosion damage to the boiler, damage to the vent system, restriction of combustion air supply, or the entry of ue  
products into the structure which in turn could cause unreliable operation, property damage, personal injury, or loss of  
life.  
4) Installation of this kit will require an opening at the base of the chimney (at the level of the horizontal vent connection) that is  
approximately 7” wide and 12” tall. A slightly smaller, or signicantly larger opening may be required depending on the chimney  
wall thickness. Before attempting to install this kit, make sure that such an opening either exists, or can be made, without  
compromising the structural integrity of the chimney (much of this opening will be re-closed later in the installation process).  
5) Maximum distance from center of chimney chase to outside surface of chimney base is 23” (Figure 1.2).  
6) Verify that there are no offsets in the chimney that will cause the PPs Flex Liner to bend more than 45 degrees.  
7) Verify that it will be possible to maintain a 5/8in per ft. pitch towards the boiler in all horizontal piping between the boiler and the  
elbow at the base of the chimney chase.  
8) PPs Flex Liner and the hardware needed for a single PPs Flex Liner installation are sold separately. All hardware is included in a  
“PPs Flex Installation kit”. Table 1.1 shows the Crown part numbers for these kits and the PPs Flex Liner itself.  
4
6) Remove the rope or pull tool from the end of the vent.  
7) Verify that the Male Adaptor is undamaged. Lubricate the brown gasket in the female end of the Elbow with a few drops of water  
and insert the Male Adaptor fully into the Elbow.  
8) Mount the bottom end of the PPs Flex Liner with the Elbow onto the Elbow Support Bracket installed in Step #2 using the Male  
Adapter Clamp as shown in Figure 1.9.  
9) The cap provided with this kit is designed for installation over chimney crowns with round openings up to 12” and square  
openings having inside dimensions up to 8-1/2”. If the opening in the crown is larger than this, the installer must provide a  
weather tight crown with an opening below these limits. The minimum diameter of the opening in this crown must be 6” for the  
80mm PPs Flex Liner and 7” for 100mm PPs Flex Liner. Make such modications to the crown in accordance with standard  
practice before proceeding further.  
10) Cut the top end of the PPs Flex Liner so that it protrudes between 1-3/4” and 2-1/4” above the top surface of the crown (Figure  
2.0). Cut the pipe in one of the grooves using a sharp utility knife.  
11) Install the Female Adaptor on the top end of the PPs Flex Liner using the same technique used to attach the Male Adaptor (Figure  
1.7). Allow the Female Adaptor to rest on Support Cross.  
12) Apply a bead of weather resistant caulk or mortar to the crown and set the Lower Vent Cap ange on the crown so that the joint  
between the Lower Vent Cap ange and the crown is completely air and water tight. Anchor the Lower Vent Cap Flange to the  
crown using an appropriate fastener through the knock-out in each corner.  
13) Moisten the brown gasket in top of the Female Adaptor with a small amount of water and fully insert the Stainless Termination  
Pipe.  
14) Slide the Upper Vent Cap over the Stainless Termination Pipe and snap in place on the Lower Cap.  
15) Provide a thimble for the penetration into the bottom of the chimney chase. This can be a section of smoke pipe, duct or ceramic  
chimney tile. It must be installed so that the following requirements are met (Figure 2.1):  
The inside dimensions of this thimble must meet the minimum chase ID requirements shown in Table 1.1.  
The thimble must be located so that a 5/8” in per ft. pitch can be maintained in the Vent Stub between the Elbow and  
Concentric Adaptor.  
The thimble must be sealed to both the chimney ue and the exterior surface of the chimney using mortar or other suitable  
sealant having a service temperature rating of at least 210F.  
The thimble must not protrude into the original chimney ue.  
16) Lubricate the gasket in the female end of the Vent Stub with a few drops of water and push it onto the Elbow.  
17) Mount the Exterior Wall Plate so that the Vent Stub will pass through the center of the opening in this plate when properly  
pitched. Anchor the Exterior Wall Plate to the wall using four masonry anchors, or other appropriate fasteners, capable of  
supporting at least 40lbs each. Note: Exterior Wall plate must completely cover the thimble. Exterior Wall Plate can be cut down  
as long as this condition is met. If the ange on the Concentric Adaptor is large enough to cover the thimble, the exterior wall  
plate may be omitted completely. If the Exterior Wall Plate is too small to cover the thimble, a larger plate may be fabricated in  
the eld using 18GA (or heavier) galvanized steel. If the exterior wall plate is cut down or replaced, the Usage Warning Label on  
the plate must be saved and attached to the base of the chimney near the concentric adaptor.  
18) Seal the Exterior Wall Plate (if used) to the outer wall of the chimney using a suitable sealant having a service temperature rating  
of at least 210F.  
19) Mark the Vent stub at a point 1” beyond where it exits the Exterior Wall Plate (Figure 2.1). Cut the Vent Stub squarely at this point  
with a ne tooth hacksaw or PVC saw. De-burr the cut end with a le, razor blade, or ne sandpaper.  
10  
20) Lubricate the gasket in the female side of the Concentric Adaptor with a few drops of water. Apply a bead of sealant to the  
Concentric Adaptor ange and secure to the Exterior Wall Plate using the four #6 stainless steel sheet metal screws provided. If  
the Exterior Wall Plate is omitted as described in Step 17, secure the Concentric Adaptor directly to the exterior wall using four  
masonry anchors, or other appropriate fasteners, capable of supporting at least 40lbs each.  
21) If there is a cleanout at the base of the chimney, seal it.  
22) Assemble the concentric vent system between the boiler and the base of the chimney in accordance with the instructions in the  
appropriate BWC installation manual.  
C. PPs Flex Maintenance  
In addition to the maintenance steps described in the boiler installation manual, the use of the PPs Flex Liner system requires that  
the following steps be performed by a service technician as part of the annual maintenance procedure:  
1) Disconnect the concentric venting from the Concentric Vent Adaptor at the base of the chimney. Use a ashlight and mirror to  
inspect as much of the chase and PPs vent system as possible through the openings in this adaptor. Look for:  
Loose mortar or other debris in the chase (old chimney). If any is found, clean it out.  
Damage or deterioration to visible portions of the PPs Flex system itself.  
Obstructions inside the PPs Flex system itself  
2) Visually inspect all exposed portions of the chimney inside and outside of the building that can be accessed without the use of  
ladders. Look for:  
Deterioration of the masonry chimney including possible leaks at mortar joints.  
Damage, deterioration, or blockage of the Cap assembly  
Signs that water may be entering the chase  
3) If the above inspections suggest that further action is needed in order to assure that the chimney chase is still in compliance with  
Part B of this manual, perform additional inspections and repairs as necessary.  
4) Reassemble the concentric vent system between the base of the chimney and the boiler. Verify that it is properly supported.  
5) Inspect the Exterior Wall plate and Concentric Adaptor to be sure that they are rmly attached to the base of the chimney and are  
sealed.  
Warning  
Failure to maintain the vent system, and boiler in accordance with these maintenance instructions, and those in the  
boiler installation and operating manual could cause unreliable operation, severe property damage, personal injury,  
or loss of life.  
Important  
Failure to document the annual boiler and vent system maintenance described above may void the boiler warranty.  
12  
Manufacturer of Hydronic Heating Products  
P.O. Box 14818 3633 I. Street  
Philadelphia, PA 19134  
PN: 980079 Rev. 0  
07/10  

Black Decker BLC18750DB User Manual
Broan Car Amplifier SPA1900D User Manual
Bryant 39006DP4 A User Manual
Canon MV300 User Manual
Clarion APX4241 User Manual
Clarion Car Amplifier APX480M User Manual
GE General Electric Camcorder E148OW User Manual
Gitzo GT2531EX User Manual
JL Audio e1800D User Manual
JVC GR AXM300 User Manual