Crown Boiler 32 User Manual

D
E
S
I
G
N
E
D
T
O
L
E
A
D
Series 32  
Gas-Fired Natural Draft Steam or Water Boilers  
INSTALLATION AND OPERATING INSTRUCTIONS  
These instructions must be affixed on or adjacent to the boiler.  
WARNING: Improper installation,  
adjustment, alteration, service or  
maintenance can cause property  
damage, injury, or loss of life. For  
assistance or additional information,  
consult a qualified installer, service  
agency or the gas supplier. Read  
these instructions carefully before  
installing.  
Manufacturer of Hydronic Heating Products  
P.O. Box 14818 3633 I. Street  
Philadelphia, PA 19134  
Table of Contents  
I.  
Product Description  
1
2
7
7
II.  
Specifications  
III.  
IV.  
V.  
Before Installing  
Locating the Boiler  
Knockdown Boiler Assembly Instructions 10  
VI.  
VII.  
VIII.  
Air for Combustion & Ventilation  
Venting  
19  
23  
27  
27  
36  
37  
37  
42  
44  
45  
45  
46  
50  
56  
58  
Steam Boiler Piping & Trim Installation  
A. Heating System Piping  
B. Indirect Water Heater Piping  
Water Boiler Piping  
IX.  
A. Heating System Piping  
B. Tankless Heater Piping  
Gas Piping  
X.  
XI.  
Control System Wiring  
A. Standard Steam / Water  
B. CSD-1 Steam / Water  
Start-Up & Checkout  
XII.  
XIII.  
XIV.  
Service & Maintenance  
Parts & Cartons Contents  
I Product Description  
The Series 32 boilers are low pressure cast iron gas fired steam or hot water boilers designed for use in commercial heating  
applications. These boilers are Category I draft diverter equipped appliances, which must be vented by natural draft using a  
lined masonry or listed metal chimney system. An adequate supply of air for combustion, ventilation and dilution of flue gases  
must be available in the boiler room. This boiler is intended for use with natural gas only.  
The Series 32 may be used on low pressure steam heating systems or forced hot water heating systems and is intended for  
installation in “closed” systems only. Hot water Series 32 boilers are available with up to two optional tankless heaters for  
domestic hot water generation.  
1
II Specifications  
2
3
NATURAL GAS ONLY  
I=B=R NET RAT ING  
WATER WATER  
NUMBER  
OF  
BHP  
BASIC BOILER  
MODEL  
HEATING  
VOL. 1 VOL.  
INPUT  
Combustion  
Effy. %  
2
CAPACITY  
OUTPUT3  
St eam  
(Sq. ft)  
Water  
SECTIONS  
(MBH)  
475  
(MBH)  
380  
(MBH)  
285  
(MBH)  
330  
(Gal)  
(Gal)  
32-475W(S)N  
32-570W(S)N  
32-665W(S)N  
32-760W(S)N  
32-855W(S)N  
32-950W(S)N  
32-1045W(S)N  
32-1140W(S)N  
32-1235W(S)N  
32-1330W(S)N  
32-1425W(S)N  
32-1520W(S)N  
32-1615W(S)N  
32-1710W(S)N  
32-1805W(S)N  
32-1900W(S)N  
32-1995W(S)N  
32-2090W(S)N  
32-2185W(S)N  
32-2280W(S)N  
32-2375W(S)N  
32-2470W(S)N  
32-2565W(S)N  
32-2660W(S)N  
32-2755W(S)N  
32-2850W(S)N  
6
1188  
1425  
1663  
1900  
2138  
2376  
2613  
2851  
3088  
3326  
3563  
3801  
4050  
4312  
4575  
4839  
5102  
5366  
5628  
5890  
6143  
6392  
6638  
6884  
7130  
7376  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
80-1/2  
28.58  
39.80  
11.4  
13.6  
15.9  
18.2  
20.4  
22.7  
25.0  
27.2  
29.5  
31.8  
34.1  
36.3  
38.6  
40.9  
43.1  
45.4  
47.7  
49.9  
52.2  
54.5  
56.8  
59.0  
61.3  
63.6  
65.8  
68.1  
7
570  
665  
456  
532  
342  
399  
397  
463  
32.65  
36.72  
40.79  
44.86  
48.93  
53.00  
57.07  
61.14  
65.21  
69.28  
73.35  
77.42  
81.49  
85.56  
89.63  
93.70  
97.77  
45.47  
51.14  
8
9
760  
608  
456  
529  
56.81  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
855  
684  
513  
595  
62.48  
950  
760  
570  
661  
68.15  
1045  
1140  
1235  
1330  
1425  
1520  
1615  
1710  
1805  
1900  
1995  
2090  
2185  
2280  
2375  
2470  
2565  
2660  
2755  
2850  
836  
627  
727  
73.82  
912  
684  
793  
79.49  
988  
741  
859  
85.16  
1064  
1140  
1216  
1292  
1368  
1444  
1520  
1596  
1672  
1748  
1824  
1900  
1976  
2052  
2128  
2204  
2280  
798  
925  
90.83  
855  
991  
96.50  
912  
1057  
1123  
1190  
1256  
1322  
1388  
1454  
1520  
1586  
1652  
1718  
1784  
1850  
1917  
1983  
102.17  
107.84  
113.51  
119.18  
124.85  
130.52  
136.19  
972  
1035  
1098  
1161  
1225  
1288  
1351  
1414  
1474  
1534  
1593  
1652  
1711  
1770  
101.84 141.86  
105.91 147.53  
109.98 153.20  
114.05 158.87  
118.12 164.54  
122.19 170.21  
126.26 175.88  
130.33 181.55  
1. Water Volume Total To Normal Water Line (Steam Boiler).  
2. Water Volume Total (Water Boiler).  
3. Ratings Based on 33,475 Btuh Per Boiler Horsepower  
Table 1B: Specifications  
4
5
6
III Before Installing  
1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict  
accordance with this manual and the requirements of the authority having jurisdiction.  
In the absence of an authority having jurisdiction, installation must be in accordance with this manual and the latest  
edition of the National Fuel Gas Code, ANSI Z223.1.  
Where required by the authority having jurisdiction, this installation must conform to the latest edition of the  
Standard for Controls and Safety Devices for Automatically Fired Boilers (ANSI/ASME CSD-1)  
2) Make sure that a properly sized chimney is available and is in good condition. Consult the authority having  
jurisdiction, Part VII of this manual, and the National Fuel Gas Code for additional information on venting  
requirements.  
3) Make sure that the boiler is correctly sized.  
4) This boiler is designed and listed for use with natural gas only.  
5) Boilers installed at altitudes above 2000 ft. require different main burner orifice than those at sea level. Make sure that  
the boiler is configured for use at the correct altitude.  
6) If this boiler was received as a knockdown boiler, follow the instructions in Section V to assemble the boiler.  
WARNING  
This Product Must be Installed By A Licensed Plumber Or Gas Fitter when Installed Within  
The Commonwealth Of Massachusetts.  
If This Boiler is Equipped With a Tankless Heater, Tankless Heater Piping Must be Installed  
by a Licensed Plumber When Boiler is Installed Within the Commonwealth of Massachusetts.  
IV Locating the Boiler  
WARNING  
All Series 32 boilers must be installed in rooms that are large in comparison with the size of  
the equipment and must be installed with the clearances listed in Table 2. Such a room will  
have a volume equal to at least 16 times the total volume of the boiler.  
1) Minimum required boiler room volumes are shown in Table 2. To find the volume of the boiler room calculate:  
Boiler Room Volume (ft3) = Length (ft) x Width (ft) x Height (ft)  
If the height is greater than 8 ft for the room height, use 8 ft for the height in the above equation.  
2) Observe the minimum clearances as shown in Table 3. These clearances apply to all combustible construction, as well as  
noncombustible walls, ceilings and doors. Also see Figure 3.  
3) This boiler must be installed on a non-combustible floor. A concrete pad is not sufficient to protect combustible  
flooring.  
4) The boiler must be installed on a hard level surface.  
5) Do not install this boiler in a location where gasoline or other flammable vapors or liquids will be stored or used. Do  
not install this boiler in an area where large amounts of airborne dust will be present, such as a workshop.  
7
Over All  
Height  
Floor To  
Top Of  
Jacket  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
46 5/8  
Minimum  
Room  
Over All  
Length  
Jacket  
Over All  
Depth  
Boiler  
Volume  
(Ft3)  
Boiler  
Model  
Volume  
(Ft3)  
Jacket  
32-475  
32-570  
36 3/4  
42 1/4  
47 5/8  
53 1/8  
58 1/2  
64  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32 1/4  
32.0  
36.7  
511.7  
587.4  
32-665  
41.4  
663.1  
32-760  
32-855  
46.2  
50.9  
738.8  
814.5  
32-950  
55.6  
890.2  
32-1045  
32-1140  
32-1235  
32-1330  
32-1425  
32-1520  
32-1615  
32-1710  
32-1805  
32-1900  
32-1995  
32-2090  
32-2185  
32-2280  
32-2375  
32-2470  
32-2565  
32-2660  
32-2755  
32-2850  
69 3/8  
74 7/8  
80 1/4  
85 3/4  
91 1/8  
96 5/8  
102  
60.4  
65.1  
965.9  
1041.6  
1117.3  
1193.0  
1268.7  
1344.4  
1420.1  
1495.8  
1571.5  
1647.2  
1722.9  
1798.6  
1874.3  
1950.1  
2025.8  
2101.5  
2177.2  
2252.9  
2328.6  
2404.3  
69.8  
74.6  
79.3  
84.0  
88.8  
107 1/2  
112 7/8  
118 3/8  
123 3/4  
129 1/4  
134 5/8  
140 1/8  
145 1/2  
151  
93.5  
98.2  
103.0  
107.7  
112.4  
117.1  
121.9  
126.6  
131.3  
136.1  
140.8  
145.5  
150.3  
156 3/8  
161 7/8  
167 1/4  
172 3/4  
Table 2: Minimum Room Volumes Based On Sixteen Times Boiler Volume By Model Size  
Figure 3: Clearances To Combustible Construction  
8
MinimumClearance - Jacket  
To Combustible Or Non-  
Combustible Construction  
24"  
Clearances Required For Removal Of Tankless Heater  
Service Clearance To Non-  
Combustible Construction  
T-1  
27"  
T-2  
32"  
T-3  
42"  
Left Side  
Right Side  
Front  
18" (Controls)  
24"  
24"  
24"  
24"  
18" (Controls)  
27"  
32"  
42"  
36" (Cleaning-Burner Removal)  
36" (Cleaning)  
--------  
--------  
--------  
--------  
--------  
--------  
--------  
--------  
--------  
Rear  
Top  
---------------------  
Table 3: Minimum Clearances to Combustibles  
6) The boiler should be located as close to the chimney as possible.  
7) Do not install this boiler directly on a surface that may get wet. Raise the boiler on a pad.  
9
V Knockdown Boiler Assembly Instructions  
A. Prior To Assembly  
1) Thoroughly inspect the cast iron heat exchanger sections for any shipping damage, i.e. cracks in the castings, broken lugs  
or punctures due to mishandling.  
2) Do not use a damaged heat exchanger section. Replace it with an undamaged heat exchanger section.  
3) Keep the base in the shipping carton until it is time to perform the assembly. This keeps foreign material from contami-  
nating the burners or creating other hazards. Do not use the base assembly if there are any signs of visible damage.  
4) Review all of the installation requirements in this installation manual.  
5) Verify that all needed components are on hand. A complete list of all sections and cartons that should be on hand,  
along with their contents, can be found in the Parts Section. A summary of the cartons and their contents is shown  
below. All boilers except the 32-475 use multiple base modules and therefore require multiple Base Cartons and  
Intermediate Cartons. All boilers larger than the 32-855 require multiple Section Joiner Cartons. Some parts, such as  
jacket screws and jacket mounting brackets are packed in both the Base Carton and the Base Side Panel Carton.  
SUM MARY OF CONTENTS  
PACKAGE  
BASE CARTON  
BASE MODULE  
BRACKETS AND HARDWARE FOR ATTACHING JACKET AND FLUE COLLECTOR  
FRONT, TOP, REAR JACKET PANELS  
FLUE COLLECTOR  
PUSHNIPPLES  
TIE ROD HARDWARE  
INTERMEDIATE CARTON  
SECTION JOINER CARTON  
PUSHNIPPLE LUBRICANT  
SECTION SEALING COMPOUND  
BASE SIDE PANELS  
BASE SIDE PANEL CARTON  
JACKET SIDE PANEL CARTON  
BRACKETS AND HARDWARE FOR ATTACHING JACKET AND FLUE COLLECTOR TO SIDES OF BOILER  
LEFT AND RIGHT SIDE JACKET PANELS  
LIMIT CONTROLS  
GAUGE  
WATER TRIM CARTON  
STEAM TRIM CARTON  
LOW WATER CUT-OFF (CSD-1 BOILERS ONLY)  
TANKLESS COIL OPENING COVER PLATES AND HARDWARE  
ASSORTED FITTINGS  
LIMIT CONTROLS  
GAUGE  
LOW WATER CUT-OFFS  
TANKLESS COIL OPENING COVER PLATES AND HARDWARE  
ASSORTED FITTINGS  
INSTALLATION M ANUAL  
USER'S M ANUAL  
WA RRA NTY  
PUSHNIPPLE GAUGE  
RATING PLATE  
BOILER CARTON  
SEALANT FOR SEALING HEAT EXCHANGER TO BASE  
POP SAFETY OR RELIEF VALVE  
FITTINGS FOR MOUNTING POP SAFETY OR RELIEF VALVE  
TANKLESS HEATER (IF USED)  
TANKLESS HEATER CARTON  
B. Base Assembly  
1) Each base module is tested and shipped assembled.  
a. All boilers are assembled using base modules with inputs of 285, 380 and 475 MBH  
b. The model 475 boiler requires only a single base module. All other boiler combinations require multiple  
base module subassemblies. See Figure 2 for the proper order of assembly.  
c. Join Base Sub-assemblies together. Use (4) 3/8”-16 x 3/4” screws, nuts and washers to attach subassemblies. (See  
Figure 4)  
d. Assemble the base in the location where the boiler is to be installed. Refer to Sections III and IV in this  
manual for additional information on placement.  
e. Once the base modules are assembled, install the base end panels. These base end panels must be installed  
prior to assembling the sections.  
f. The base must be level in both directions and supported under all feet. Shim and grout under base if  
necessary.  
g. Verify that the front and sides of the base are square.  
h. Place cardboard covering over the top of the burners to protect them during the assembly of the boiler  
sections.  
10  
11  
C. Section Assembly  
1) Clean the boiler sections inside and out to remove dirt due to shipping and handling.  
2) Clean all nipples and nipple ports with kerosene immediately prior to section assembly.  
3) Set the left end section on the base so that the locating lugs on the bottom of the section go inside the front and  
rear base panels. Left end sections are identified by “LEH” cast on the section. Right end sections are identified  
by “REH” cast on the section.  
4) Apply the Loctite 592 lubricant/sealant furnished to two nipples and the nipple ports in the left section.  
5) Start each nipple by hand in the nipple port and bump carefully with a wooden block to set. As this is done, check  
the nipple frequently with the nipple gauge to verify that the nipple is square in the port and not cocked (see  
Figure 5). Continue to bump the nipple until the nipple gauge just touches the ground surface as measured in two  
directions 90 degrees apart.  
CAUTION  
Seating the nipples in accordance with the above instructions will make drawing the sections  
together easier and assure water tight joints.  
6) Apply the “joint sealer” to all ground surfaces on the left end section.  
7) Carefully join the first intermediate section with the left end section. Bump lightly to secure.  
8) Install 5/8" nuts and washers on one end of each of three 9 ¾” tie rods. Install one of these tie rods in each of the  
three bosses in the left and intermediate section. Lubricate the other end of each of these tie rods with heavy oil or  
grease. Install 5/8" nuts and washers on the lubricated ends. Finger tighten.  
9) Draw the two sections together slowly and evenly, tightening each tie rod a little at a time so that the sections are  
evenly spaced. KEEP THE NIPPLES ALIGNED WITH THE NIPPLE PORTS – DO NOT DRAW UP THE  
SECTIONS IF THE NIPPLES ARE COCKED. Continue drawing up the sections in this manner until the  
ground surfaces on each section are touching.  
10) Repeat Steps (4-9) to assemble the remaining sections. After approximately five sections have been drawn  
together, use a pinch bar to insert the wood wedges supplied under the last intermediate section to raise it above  
the base. This will make it easier to assemble subsequent sections, particularly the right end section. As each  
section is drawn up, move the wedges under that section.  
CAUTION  
Some boilers use intermediate sections with supply tappings. When these sections are used, it is  
critical that they are located in the correct position. When assembling the sections refer to  
Figure 2 to verify that they are assembled in the correct order.  
11) After all sections have been drawn up, verify that the bottom lugs on the left end section are still against the left  
end base panel. Using a pinch bar, remove the wood wedges and carefully lower the right end of the assembled  
block onto the base.  
12) Install four block anchors using 3/8 x 2" cap screws, nuts and washers (Figure 6).  
13) Loosen all tie rod nuts so that they are finger tight.  
12  
Figure 5: Use Of Nipple Gauge  
Figure 6: Assembly Of Sections  
13  
14) Install the tankless coil/s and/or cover plates using the gaskets and 3/8 x 7/8 bolts and washers provided (see  
Figure 7).  
15) Test assembled block for leaks. Unless local codes have other requirements, use the following procedure:  
a) Run a hose from the water service to one of the lower tappings. Install a ball or gate valve in one of the  
tappings on the top of the block and connect the other end of this valve to a drain. Install a gauge in any  
other convenient tapping. Plug all remaining unused tappings (See Figure 8).  
b) Fill the boiler until a steady stream of water is observed going down the drain.  
c) Slowly close the valve until the pressure in the boiler reads between 10 and 50 psi. DO NOT EXCEED.  
d) Carefully examine all parts of the boiler block assembly for leaks.  
e) Drain the boiler and remove all plugs from tappings that will be used for connections and trim (see  
Piping Sections in this manual).  
16) Use the supplied Resbond sealant to seal the joint between the assembled block and the base.  
17) Inspect the joints between the sections for any areas that are not flue gas tight. Seal any areas found with the  
remaining Resbond sealant.  
Figure 8: Testing Boiler Assembly For Leaks  
D. Draft Hood Installation  
Figure 7: Tankless Heater Installation  
1) The model 32-475 requires only one draft hood. All other boilers require multiple draft hoods. WHEN MUL-  
TIPLE HOODS ARE USED THEY MUST BE ARRANGED SO THAT EACH HOOD IS OVER A COR-  
RESPONDING SIZED BASE MODULE.  
2) Use the 1" x ½” Cerablanket strips provided to seal the draft hoods to the block assembly. To do this, lay the strips  
along the top of the block in the locations that will be under the edges of the draft hood (see Figure 9). Overlap  
the Cerablanket strips at the corners.  
3) Install the rear panel support brackets using #10 x ½ sheet metal screws (Figure 3).  
4) On the left end section, insert a 5/8 x 4 threaded stud through the available hole in the top rear tie rod lug. Use a 5/  
8 nut and washer on each side of the lug to attach this stud, making sure that the stud is approximately centered on  
the lug (See Figure 10). In the same manner, install 5/8 x 4" studs on the right end section and on all intermediate  
sections that span the joint between base modules.  
5) Place the left-most draft hood on the boiler. Insert two 5/16 x 3 carriage bolts through the holes in the lip on the  
front of the hood with the head of the bolts on the underside of this lip. Thread a 5/16 washer and brass wing nuts  
on each of these bolts. Slip the bolt heads into the pockets on the top of the intermediate sections (Figure 11).  
Tighten just sufficiently enough to hold the hood in place.  
14  
NOTE  
Installation of the draft hoods will be easier if one person supports the rear of the hood while  
another installs the carriage bolts, nuts and washers.  
6) Hang a rear tie rod channel bracket on the 4" stud installed in the left end section (Figure 12a).  
7) Facing the rear of the boiler, find the square mounting holes underneath the draft hood. Drop a 5/16 x 5" carriage  
bolt through this hole and through the hole in the rear tie rod channel bracket. Loosely secure with a wing nut and  
washer (Figure 12b). Install a second rear tie rod channel bracket on the other side of the draft hood.  
8) Using a plumb bob, adjust the rear tie rod channel brackets so the jacket mounting holes in the rear tie rod channel  
brackets line up with the holes in the jacket rear panel support brackets on the base modules.  
9) Tighten the 5/16 wing nuts on the front and back of the draft hood.  
CAUTION  
Before tightening the draft hood hold-down nuts, make sure the gasketing is properly located  
under the draft hood. Recheck the positioning of the gaskets after tightening the nuts and make  
adjustments as necessary.  
10) Repeat Steps 5-9 to install the remaining draft hoods.  
Figure 9: Draft Hood Gasket Installation  
Figure 10: Hardware Arrangement for Rear Tie  
Rod Mounting Bracket Installation  
15  
Figure 11: Front Attachment Of Draft Hood  
Figure 12a: Mounting Rear Tie Rod Channel  
Bracket  
Figure 12b: Rear Attachment Of Draft Hood  
16  
D. Jacket Assembly Instructions  
NOTE  
Before installing the jacket, make sure to plug any tappings which are not going to be used. Also make sure that no  
tappings are plugged which will be needed later for piping the boiler. See Sections VIII and IX for piping and trim  
installation.  
1) On the left and right side base panels attach the jacket side panel zee bracket and the jacket top support  
bracket end angle with #10 x 1/2” sheet metal screws as shown in Figure 13.  
2) Jacket top support brackets are required at the joints between base modules and at each end of the base  
assembly. Attach the jacket top support brackets to the base front panel(s) with #10 x 1/2” sheet metel  
screws as shown in Figure 13. Also fasten the jacket top support brackets located on each end of the  
assembly to the jacket top support bracket end angles using #10 x 1/2” sheet metal screws.  
3) Remove the appropriate knockouts from the side jacket panels.  
4) Hang the left hand jacket side panel assembly in the slot of the jacket top support bracket and over the rear  
brackets of the boiler assembly. Fasten the jacket side panel to the jacket side panel zee bracket, the jacket  
rear panel support bracket, the rear tie rod channel bracket and the jacket top support bracket using  
#10 x 1/2” sheet metal screws.  
5) Repeat the instructions in step 3 to install the right side panel.  
6) Attach the jacket rear panel assembly(s) to the jacket rear panel support brackets and the tie rod channel  
brackets using #10 x 1/2” sheet metal screws.  
7) Before installing the jacket top panel(s) locate the position of any intermediate supply risers and remove the  
appropriate knockouts.  
8) Install the jacket top panel(s) by placing the left and right flanges of the jacket top panel(s) in the slots of the  
jacket top support brackets and attach using #10 x 1/2” sheet metal screws.  
9) Attach the door knobs to the removable jacket front panel(s) with 8-32 x 1/2” machine screws.  
10) Hang the jacket front panel(s) over the front flange of the jacket top panel while making sure the bottom of  
the door drops into the slots in the gas manifold bracket.  
Figure 13: Jacket Mounting Bracket Arrangement  
17  
18  
VI Air For Combustion and Ventilation  
Sufficient fresh air must be supplied for combustion, ventilation and flue gas dilution. Provisions for combustion,  
ventilation and flue gas dilution air for gas utilization equipment vented by natural draft must be made in accordance with  
local building codes or, in absence of such codes, in accordance with the National Fuel Gas Code, NFPA 54/ANSI Z223.1.  
Warning  
An adequate supply of combustion and ventilation air must be provided  
to assure proper combustion.  
1) Start by determining whether the boiler is to be installed in a building of conventional construction or of unusually  
tight construction. A good definition of a building of unusually tight construction is one which has all of the  
following features:  
Walls and ceilings exposed to outside atmosphere have a continuous water vapor retarder with a rating of  
1 perm or less with openings gasketed and sealed.  
Weather stripping has been added on openable windows and doors.  
Caulking and sealants are applied to areas such as joints around window and door frames, between sole plates  
and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas  
lines, and at other openings.  
2) Determine the volume of the boiler room space. Rooms communicating directly with the boiler room space, in  
which the fuel burning appliances are installed, through openings not furnished with doors, are considered a part of  
the boiler room space.  
Volume (ft³) = Length (ft) x Width (ft) x Height (ft)  
In calculating the volume of the boiler room, consider the volume of adjoining spaces only if no doors are  
installed between them. If doors are installed between the boiler room and an adjoining space, do not consider  
the volume of the adjoining space, even if the door is normally left open.  
3) Determine total input of all fuel burning appliances in the boiler room space. Add inputs of all fuel burning appliances  
in the boiler room space and round the result to the next highest 1000 Btu per hour.  
4) Determine type of boiler room space to be used. Divide Volume by Total Input (in MBH) of all fuel burning appliances  
in the boiler room space. If the result is greater than or equal to 50 ft³/MBH, then it is considered an unconfined space.  
If the result is less than 50 ft³/MBH, then the boiler room space is considered a confined space.  
A. For Buildings Not Of Unusually Tight Construction  
1) Unconfined space - Fresh air infiltration through cracks and around windows and doors normally provides  
adequate air for combustion and ventilation without additional louvers or openings into the boiler room.  
2) Confined space - Provide two openings into the boiler room, one near the floor and one near the ceiling. The top  
edge of the upper opening must be within 12” of the ceiling and the bottom edge of the lower opening must be  
within 12” of the floor. See Figure 15.  
Each opening must have a free area of 1 square inch per 1000 BTU/hr input of all gas burning appliances in the  
boiler room. The minimum opening dimension is 3 inches. Minimum opening free area is 100 square inches  
per opening.  
If the total volume of both the boiler room and the room to which the openings connect is less than 50 cubic  
feet per 1000 BTU/hr of total appliance input, install a pair of identical openings into a third room. Connect  
additional rooms with openings until the total volume of all rooms is at least 50 cubic feet per 1000 BTU/hr  
of input.  
The “free area” of an opening takes into account the blocking effect of mesh, grills, and louvers. Where screens  
are used, they must be no finer than 1/4” (4 x 4) mesh.  
19  
Figure 15: Boiler Installed In Confined Space, All Air From Inside  
If providing openings into adjacent rooms is undesirable, combustion and ventilation air can be brought into  
the boiler room from outdoors. See the instructions under “For Buildings of Unusually Tight Construction”.  
B. For Buildings Of Unusually Tight Construction  
1) Provide outdoor air through two permanent openings which communicate directly or by duct with the outdoors or  
spaces (crawl or attic) freely exchanging air with the outdoors. The top edge of the upper opening must be within  
12” of the ceiling and the bottom edge of the lower opening must be within 12” of the floor. The minimum  
dimension of each air opening is 3 inches. Size each opening per the following instructions:  
a. Direct communication with outdoors (Figure 18) require a minimum free area of 1 square inch per 4,000 Btu per  
hour input based on all fuel burning appliances in the boiler room space but not less than 100 square inches. The  
minimum opening size is 3 inches.  
b. Vertical ducts or Openings (Figure 16 and Figure 17) require a minimum free area of 1 square inch per 4,000 Btu  
per hour input of all fuel burning appliances in the boiler room space but not less than 100 square inches. The cross-  
sectional area of the duct shall be the same as the required free area opening. The minimum opening size is 3 inches.  
c. Horizontal ducts to the outdoors (Figure 19) require a minimum free area of 1 square inch per 2,000 Btu per hour  
input of all fuel burning appliances in the boiler room space but not less than 100 square inches. The cross-sectional  
area of the duct shall be the same as the required free area opening. The minimum opening size is 3 inches.  
d. Louvers and Grilles of Ventilation Ducts - All outside openings should be screened or louvered. Louvers will  
prevent the entrance of rain and snow. Louvers and grilles must be fixed in the open position. If motorized louvers  
are used, they must be interlocked to prevent boiler operation in the event the louvers do not fully open.  
Important  
When determining the “free area” of an opening the blocking effects of mesh screens,  
grills, louvers and the like should be taken into account. Where screens are used, they  
must be no finer than 1/4” (4 x 4) mesh.  
20  
Figure 16: All Air From Outdoors, Ventilated Crawl Space & Attic  
Figure 17: All Air From Outdoors, Via Ventilated Attic  
Figure 18: All Air From Outdoors, Using Openings Into Boiler Room  
21  
Figure 19: All Air From Outdoors, Using Horizontal Ducts Into The Boiler Room  
22  
VII Venting  
Vent installation must be in accordance with local building codes, or the authority having jurisdiction, or the  
National Fuel Gas Code, NFPA 54/ANSI Z223.1.  
Typical vent installations are shown in Figures 20 and 21. The vent system shown in Figure 20 uses a common vent  
for all boiler modules. In Figure 21, each boiler module is equipped with its own vent. The vent system in Figure 21 is  
ideal on large boilers with many individually controlled base modules as the vent system will not be effectively  
oversized when only a single module is firing.  
1) Acceptable Chimneys - The following chimneys may be used to vent Series 32 boilers:  
Listed Type B or L gas vent - Install in accordance with the manufacturer’s instructions, the terms of its listing, and  
applicable codes.  
Masonry Chimney - The masonry chimney must be constructed in accordance with the Standard for Chimneys,  
Fireplaces, Vents, and Solid Fuel Burning Appliances (NFPA 211) and lined with a clay liner or other listed lining  
system. Do not vent a Series 32 boiler into an unlined chimney.  
2) Acceptable Vent Connectors - The following may be used for vent connectors:  
Listed type B or L Gas Vent  
Single Wall Galvanized Pipe - Use 0.018” (26 gauge or heavier). The size and location of the chimney may not  
permit the use of a single wall connector in some cases. See the National Fuel Gas Code. Do not use single wall  
pipe for vent connectors in attics.  
Other Vent Connectors Permitted by the National Fuel Gas Code.  
3) Chimney and Vent Connector sizing – If the entire vent system (chimney and vent connector) are constructed from  
Type “B” vent, size the vent system using the National Fuel Gas Code. Where possible, also use the National Fuel  
Gas Code to size vents employing single wall connectors and/or masonry chimneys. The minimum chimney size of  
the 32-475 is 12”, even if the National Fuel Gas Code permits a smaller size. For boilers with more than one module,  
use the Multiple Appliance vent section of the code and treat each base module as though it were a separate boiler.  
For boilers with more than one module, the vent connector is always the same size as the module’s flue collar.  
Many Series 32 boiler vent systems with single wall connectors and/or masonry chimneys are too large to be sized  
using the National Fuel Gas Code. In these cases Table 4 may be used to size the vent system. The vent sizes shown  
in Table 4 are based on the following assumptions:  
· Chimney Height (Dimension “H”) at least 20 ft high  
· Total length of lateral (“Lm”) less than or equal to that shown in Table 4  
· No more than one 90 elbow is permitted in lateral common venting  
· Vent connectors and common vent lateral constructed of single wall pipe or “B” vent  
· Chimney is constructed of B vent or is a lined masonry chimney in good condition  
· No other appliances are connected into the vent system  
· Listed Chimney Cap is used  
If any of these assumptions are not valid, and where the National Fuel Gas Code cannot be used, use other accepted  
chimney design methods such as those shown in Chapter 30 of the ASHRAE HVAC Systems and Equipment Hand-  
book.  
4) Do not connect the boiler into a chimney flue serving an open fireplace or other solid fuel appliance.  
5) Prior to boiler installation, inspect chimney for obstructions or other defects and correct as required. Clean chimney  
as necessary.  
23  
6) Lateral venting should slope upwards towards the chimney not less than one inch in four feet. No portion of vent pipe  
should run downward or have sags. Vent pipe must be securely supported.  
7) The connector rise coming off the boiler should be as tall as possible, while still maintaining the proper  
clearance from the horizontal vent connector to combustibles and the proper pitch called for in (6) above.  
8) Lateral vent pipe should be installed above the bottom of the chimney to prevent blockage.  
9) Lateral vent pipe must be inserted flush with inside face of the chimney liner and the space between vent pipe and  
chimney sealed tight.  
IMPORTANT: READ THE ENTIRE VENT SECTION  
AND REFER TO FIGURE 20 BEFORE  
ATTEMPTING TO USE THIS CHART  
MIN. CHIMNEY  
HEIGHT (H), ft  
MAX. LATERAL  
COMMON VENT (Lm), ft INSIDE DIA. (D), in  
MIN. COMMON VENT  
MODEL  
32-475*  
32-570  
20  
9 1/2  
12  
32-665  
32-760  
32-855  
32-950  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
9 1/2  
10  
10 1/2  
11  
11 1/2  
12  
12 1/2  
13  
13 1/2  
14  
14 1/2  
14 1/2  
15  
15 1/2  
16  
16 1/2  
17  
17 1/2  
18  
18 1/2  
19  
19 1/2  
19 1/2  
20  
12  
12  
12  
14  
14  
14  
14  
16  
16  
16  
16  
18  
18  
18  
18  
18  
20  
20  
20  
20  
20  
22  
22  
22  
32-1045  
32-1140  
32-1235  
32-1330  
32-1425  
32-1520  
32-1615  
32-1710  
32-1805  
32-1900  
32-1995  
32-2090  
32-2185  
32-2280  
32-2375  
32-2470  
32-2565  
32-2660  
32-2755  
32-2850  
* USE NATIONAL FUEL GAS CODE TO SIZE 32-475 VENTING  
Table 4: Sizing For Vent Systems Outside The Scope Of The National Fuel Gas Code Venting Tables  
24  
Figure 20: Typical Series 32 Venting (Common Module Venting)  
Figure 21: Series 32 Venting (Each Module Individually Vented)  
25  
Removing An Existing Boiler From A Common Chimney  
In some cases, when an existing boiler is removed from a common chimney, the common venting system may be too large  
for the remaining appliances. At the time of removal of an existing boiler, the following steps shall be followed with each  
appliance remaining connected to the common venting system placed in operation, while the other appliances remaining  
connected to the common venting system are not in operation.  
a) Seal any unused opening in the common venting system.  
b) Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or  
restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.  
c) Insofar as practical, close all building doors and windows and all doors between the space in which all the appliances  
remaining connected to the common venting system are located and other spaces of the building. Turn on clothes  
dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range  
hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close  
fireplace dampers.  
d) Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so the  
appliance will operate continuously.  
e) Test for spillage at the draft hood relief opening after five (5) minutes of main burner operation. Use the flame of a  
match or candle, or smoke from a cigarette, cigar, or pipe.  
f) After it has been determined that each appliance remaining connected to the common venting system properly vents  
when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning  
appliances to their previous condition of use.  
g) Any improper operation of the common venting system should be corrected so the installation conforms with the  
National Fuel Gas Code, ANSI Z223.1. When resizing any portion of the common venting system, the common  
venting system should be resized to approach the minimum size as determined using the appropriate tables in Part 11  
of the National Fuel Gas Code, ANSI Z223.1.  
26  
VIII Steam Boiler Piping & Trim Installation  
CAUTION  
INSTALL BOILER SO THAT THE GAS IGNITION SYSTEM COMPONENTS ARE PROTECTED  
FROM WATER (DRIPPING, SPRAYING, RAIN, ETC.) DURING APPLIANCE OPERATION  
AND SERVICE (CIRCULATOR REPLACEMENT, ETC.).  
OPERATION OF THIS BOILER IN A SYSTEM HAVING SIGNIFICANT AMOUNTS OF  
DISSOLVED OXYGEN CAN CAUSE SEVERE HEAT EXCHANGER CORROSION DAMAGE.  
A. Heating System Piping (Steam Boilers)  
1) Figures 27 shows the recommended near boiler piping for most common types of gravity return steam systems. Use  
Table 6 to determine the riser, header and equalizer piping sizes for the appropriate boiler model.  
2) One of the primary purposes of the near boiler piping is to separate tiny water droplets from the steam exiting the  
boiler so that “dry” steam is sent to the system. If the near boiler piping is not correct, wet steam will enter the  
system and the following problems may occur:  
Short cycling on low water  
Boiler or system Flooding  
Hammering  
Failure to heat one or more radiators  
3) Avoid the three common piping mistakes shown in Figure 25. This applies even if the existing boiler has one of  
the piping mistakes shown in Figure 25 and appears to be working. If two or more steam mains must be connected  
to the boiler, connect a separate take-off for each main into the header between the riser(s) and equalizer. Also  
note the following points:  
a. A size reduction must be made to connect the header to the equalizer. This reduction must be made in the  
equalizer line. Do not make this size reduction in the horizontal header.  
b. For installations with condensate or boiler feed pumps, follow the pump manufacturer’s piping instructions. Such  
systems generally do not require Hartford loops. Figure 26 shows typical near-boiler piping when a boiler feed  
pump is used.  
c. Do not use a check valve in place of, or in addition to, a Hartford loop on a gravity return system.  
d. Steam pipes shall have a clearance of at least 1/2” from all combustible construction.  
e. Pipe the fill connection from a clean source of cold water. When the water supply is from a well, make sure that  
a strainer is installed in the well system.  
4) Boiler trim may be installed on either the left or right side of the boiler. Table 4B shows the uses of all steam boiler  
tappings. The tapping letter designations referenced below are shown in Figure 22:  
a. Pressure Gauge – Install in tapping “D”using the 1/2” nipple, tee and bushing provided. See Figure 23. DO  
NOT TIGHTEN THE GAUGE BY ITS’ CASE.  
b. Low Water Cut-off – Depending upon local codes, and how the boiler is ordered, one or more of the following  
low water cut-offs may be used:  
McDonnell & Miller #67 – Install in tappings “E”. If redundant low water cut-offs are used, the #67 must  
be the back-up low water cut-off. The #67M (manual reset type) is standard on the CSD-1 control package  
and should also be used when other codes require a back-up low water cut-off with manual reset.  
27  
Hydrolevel CG450 – This is a probe type LWCO and is installed in tapping “G”. On the CSD-1 control  
package, and other boilers with redundant low water cut-offs, the CG450 is the operating low water cut-off  
and should be used to control a feeder (if used).  
The CG450 supplied with the Series 32 uses a special probe which does not have a mounting flange.  
Install this probe in tapping “G”. DO NOT INSTALL WITH TEFLON TAPE. With the jacket already  
installed, installation of the probe is most easily done using a 1-1/16" deep throated socket. After the probe  
is installed, mount the case of the CG450 to the jacket using two #10 x ½ sheet metal screws through the  
keyhole slots in the case (Figure 24). Connect the white probe wire to the wing nut on the probe. Note: A  
direct ground connection between the case and the body of the probe is not required.  
Other Low Water Cut-offs – Other float type low water cut-offs, such as the McDonnell & Miller #150  
pump controller, are installed in an equalizing pipe connected between tappings “B” and “J”.  
c. Gauge Glass – Install gauge glass in tappings “E” or in the #67 LWCO Tees (if used).  
d. Pressure Limit Controls – All Series 32 steam boilers are supplied with a PA404A or L404A operating pressure  
limit control. In addition, a manual reset L404C is supplied on boilers with the CSD-1 control package.  
Install the PA404A using the straight pigtail siphon and bushing in the tee installed in Tapping “D”. See  
Figure 23.  
When an L404C is used, install it using the straight pigtail siphon in the 1/4” tapping on top of the #67 LWCO.  
e. Safety Valve – Before installing the safety valve, examine the tag on the valve and confirm that it has a capacity  
greater than or equal to the of the boiler’s gross output. Also confirm that its’ pressure setting is less than or  
equal to that marked on the boiler sections (15 psi for steam). The location of the safety valve depends upon its’  
size:  
· Safety Valves of 1-1/2" and smaller are installed in one of the “C” tappings using the 1-1/2” nipple, tee and  
bushing provided. See Figures 26 or 27. To do this, install a 1-1/2" nipple and 1-½” Tee in the “C” tapping  
with the run of the Tee horizontal and the “bull” (side outlet) of the Tee pointing up. Install the Safety Valve in  
the “bull” of the Tee and plug the remaining opening in the Tee. The use of a Tee to mount the relief valve  
will permit Tapping “C” to also be used for skimming the boiler.  
· Safety Valves greater than 1-1/2" must be installed in the steam riser with their spindle vertical (Figure 27c).  
No valves are permitted between the boiler and the steam header.  
Pipe the discharge of the safety valve to a location where hot water and steam will not create a hazard or cause  
property damage if the valve opens. The discharge pipe must be the same size as the outlet connection on the  
safety valve and must terminate in unthreaded pipe. The safety valve discharge piping must be in an area where it  
is not likely to become plugged by debris or subjected to freezing.  
DANGER  
CONFIRM SAFETY VALVE HAS THE CORRECT PRESSURE SETTING AND CAPACITY  
FOR THE BOILER.  
PIPE SAFETY VALVE DISCHARGE TO A SAFE LOCATION.  
PIPING BETWEEN SAFETY VALVE CONNECTION AND BOILER MUST BE AT LEAST  
AS LARGE AS SAFETY VALVE INLET CONNECTION.  
DO NOT INSTALL A VALVE IN THE SAFETY VALVE DISCHARGE LINE.  
DO NOT MOVE SAFETY VALVE FROM FACTORY LOCATION.  
DO NOT PLUG SAFETY VALVE DISCHARGE.  
DO NOT INSTALL A POP SAFETY VALVE WITH A SETTING GREATER THAN 15 PSI.  
28  
Figure 22: Steam Boiler Tapping Locations  
Tapping Uses Chart For Steam Boilers1  
Component Description  
Tapping  
Location  
A
Tapping  
Size (in)  
3
Standard  
Equipment  
N
CSD-1  
Package  
N
Supply Piping  
Return Piping  
B
3
N
N
Safety Relief Valves  
C2  
1-1/2  
Y
Y
(With Inlet Opening Up To & Including 1-1/2" NPT Inlet)  
Safety Relief Valves  
Riser  
(See Figure 27c)  
-
(With Inlets Larger Than 1-1/2" NPT Inlet)  
Pressure Gauge  
Y
Y
Y
Y
N
N
Y
Y
Y
N
Y
Y
D
1/2  
1/2  
1/2  
1/2  
3/4  
Water Gauge Glass Fittings  
E
M & M #67 Low Water Cut-Off  
E
E
M & M #67M Low Water Cut-Off with Manual Reset  
Hydrolevel CG450 Probe Low Water Cut-Off  
Steam Equalizer Installed On The End Not Equipped With Trim  
(With Optional M & M #150 Float Low Water Cut-Off / Pump Controller)  
Honeywell PA404AOr L404A Pressure Limit  
G
Between  
B & J  
3 & 1  
N
N
D
1/2  
-
Y
N
Y
Y
1/4" Tapping on  
Top of #67 LWCO  
Honeywell L404C Manual Reset Pressure Limit Control  
Boiler Drain Valve  
Bottom Blowoff Piping  
Cover Plate  
B
B
F
H
I
3
3
Y
N
Y
N
N
Y
N
Y
N
N
-
Indirect Water Heater Connection  
1-1/2  
3/4  
Indirect Water Heater Aquastat  
1. TrimMay Be Installed On Either End Section.  
2. Use The Tapping Located On The End Not Equipped With Trim For The Safety Relief Valve & The Surface Blow off .  
Table 5  
29  
f. Boiler Drain Valve - Install with a 3” x ¾” bushing into one of the two return tappings “B”. The drain valve  
may also be installed in the return piping, but it must be installed in the leg of a tee so that it is directly opposite  
and as close as possible to the return tapping. The leg of the tee must be at least 1½” pipe size.  
A bottom blowoff using a valve must also be connected to one of the return tappings (B). The ¾” Drain Valve  
maybe used for a bottom blowoff for the boiler model 32-570 or smaller boilers. Bottom blowoff piping and  
valves for the boiler models 32-665 through the 32-1520 must be at least 1”. Bottom blowoff piping and valves  
for the boiler models 32-1615 through the 32-2850 must be at least 1¼”.  
g. Install the “Lowest Permissible Water Level Plate” using the holes provided in the jacket panel near the  
LWCO.  
Figure 23: Pressuretrol / Gauge Installation  
Figure 24: CG450 Installation  
30  
Figure 25: Common Near-Boiler Piping Mistakes  
Steam  
Steam  
Return  
Header  
Condensate  
Return Pipe  
Equalizer  
Pipe  
Boiler  
Header  
Riser Pipe  
Model  
32-380  
32-475  
32-570  
32-665  
32-760  
32-855  
32-950  
32-1045  
32-1140  
32-1235  
32-1330  
32-1425  
32-1520  
32-1615  
32-1710  
32-1805  
32-1900  
32-1995  
32-2090  
32-2185  
32-2280  
32-2375  
32-2470  
32-2565  
32-2660  
32-2755  
32-2850  
Size (in) Quantity Size (in) Size (in) Quantity Size (in) Quantity Size (in)  
3
3
4
4
4
4
5
5
5
5
5
5
6
6
6
6
6
6
6
8
8
8
8
8
8
8
8
1
1
2
2
2
2
2
3
3
3
3
3
3
4
4
4
4
4
5
5
5
5
5
5
6
6
6
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1 1/2  
1 1/2  
1 1/2  
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 1/2  
1 1/2  
1 1/2  
2
2
2
2
2
2
2
2
2
2
2
2
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
3
3
3
3
3
3
3
3
4
2
2
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
2 1/2  
3
3
3
3
3
3
3
3
3
3
3
3
4
4
4
4
1. The pipe sizes listed above are nominal trade sizes for Schedule 40 pipe.  
Note:  
Table 6: Steam Boiler Riser & Header Pipe Sizes  
31  
32  
33  
34  
35  
B. Indirect Water Heating Piping (Steam Boilers)  
The steam version of the Series 32 boiler is equipped with tappings to permit the connection of a Crown Mega-Stor, or other  
indirect water heater. In this type of system, hot boiler water is drawn from below the water line and passed through the heat  
exchanger in the indirect water heater. This section describes boiler-side piping only. Refer to the indirect water heater  
instruction manual for domestic water piping. The components in this system and their functions are as follows:  
1) Circulator - Mount the circulator as shown in Figure 28. The circulator should be located as low and as close to the  
boiler as practical. Do not install valves, or other devices having a significant pressure drop, between the boiler and  
the circulator inlet. All piping between the boiler and the circulator inlet should be 1-1/2”, regardless of the size of the  
piping required in the rest of the system.  
2) “Y” Strainer - Install a “Y” strainer to prevent sediment from accumulating inside the indirect water heater.  
3) Check Valve - Prevents gravity circulation through the indirect water heater when the boiler is responding to a call for  
heat.  
4) Boiler Limit Control - Use a SPST break-on-rise temperature limit control such as the Honeywell L4006A. Do not  
set the limit above 180F as doing so may cause the boiler to steam when there is no call for heat.  
5) Valves and Unions - Install shut-off valves, drain valves, and unions in locations that will facilitate maintenance of the  
system. Do not install any valves between the boiler and circulator inlet.  
IMPORTANT  
Some indirect water heaters may not be suitable for use with a steam boiler. Consult the water heater  
manufacturer’s guidelines before installing it in this type of system.  
Boiler water temperatures and flow rates in this type of system may be considerably lower than those upon which the  
water heater manufacturer’s ratings are based. This may result in substantially longer water heater recovery times.  
Figure 28: Indirect Water Heater Boiler-Side Piping  
36  
IX Water Boiler Piping  
CAUTION  
INSTALL BOILER SO THAT THE GAS IGNITION SYSTEM COMPONENTS ARE PROTECTED FROM  
WATER (DRIPPING, SPRAYING, RAIN, ETC.) DURING APPLIANCE OPERATION AND SERVICE  
(CIRCULATOR REPLACEMENT, ETC.).  
OPERATION OF THIS BOILER WITH CONTINUOUS RETURN TEMPERATURES BELOW 120°F CAN  
CAUSE SEVERE HEAT EXCHANGER CORROSION DAMAGE.  
OPERATION OF THIS BOILER IN A SYSTEM HAVING SIGNIFICANT AMOUNTS OF DISSOLVED  
OXYGEN CAN CAUSE SEVERE HEAT EXCHANGER CORROSION DAMAGE.  
DO NOT USE TOXIC ADDITIVES, SUCH AS AUTOMOTIVE ANTIFREEZE, IN A HYDRONIC SYSTEM.  
A. Heating System Piping  
1) Figure 30 shows the recommended water boiler system piping. Use Table 8 to determine the supply riser, supply  
header, return header and boiler return piping connection sizes for the appropriate boiler model. On boilers  
requiring one supply riser, use the supply connection opposite the return connection. Install the trim on the same  
end as the supply connection. Additional information on hydronic system design may be found in the I=B=R  
Advanced Installation and Piping Guide (Pub. #250) published by the Hydronics Institute in Berkeley Heights,  
NJ or the ASHRAE Systems Handbook. Table 7 shows the use of all boiler tappings on water boilers. The  
tapping letter designations referenced are shown in Figure 29. The water trim components are as follows:  
a. Pressure Gauge – Install in tapping “D”. Tapping “D” must be reduced from ½” to ¼”. DO NOT TIGHTEN  
THE GAUGE BY ITS CASE.  
b. Low Water Cut-off – (Required in some situations) - A low water cutoff is required when the boiler is installed  
above radiation. In addition, some codes, such as ASME CSD-1, require low water cutoffs. Codes may also  
require that this low water cutoff have a manual reset function. When a probe low water cut-off is used, install it  
in the supply piping above the boiler with no intervening valves between it and the boiler.  
c. Limit Controls – All Series 32 water boilers are supplied with an L4006A operating temperature limit control.  
In addition, a L4006E manual reset control is supplied on boilers with the CSD-1 control package. Install the  
immersion well supplied with the L4006A in Tapping “C” with a bushing. Insert the bulb of the control in the  
well until it rests against the bottom of the well. Bend the tubing if necessary to provide enough force to hold  
the bulb against the bottom of the well. Avoid making a sharp bend in the tubing as this can cause the control to  
malfunction. Tighten the screw on the bottom of the control so that it is securely clamped onto the well. When  
an L4006E is used, install it in the supply riser on the same side of the boiler as the L4006A. Install it in a well  
in the same manner as the L4006A.  
d. Pressure Relief Valve (Required) - Before installing the relief valve, examine the tag on the valve and confirm  
that it has a capacity greater than or equal to the boiler’s gross output. Also confirm that its pressure setting is  
less than or equal to that marked on the boiler sections for water. Install Relief Valves in the “C” tapping on the  
opposite end of the boiler from the other trim. Install the relief valve using the elbow and nipples provided so  
that its’ spindle is vertically oriented (Figure 30).  
Pipe the discharge of the relief valve to a location where hot water and steam will not create a hazard or cause  
property damage if the valve opens. The discharge pipe must be the same size as the outlet connection on the  
safety valve and must terminate in unthreaded pipe. The relief valve discharge piping must be in an area where it  
is not likely to become plugged by debris or subjected to freezing.  
37  
DANGER  
CONFIRM RELIEF VALVE HAS THE CORRECT PRESSURE SETTING AND CAPACITY FOR THE  
BOILER.  
PIPE THE PRESSURE RELIEF VALVE DISCHARGE TO A SAFE LOCATION.  
DO NOT INSTALL A VALVE IN THE RELIEF VALVE DISCHARGE LINE.  
DO NOT PLUG RELIEF VALVE DISCHARGE.  
3) In addition to the boiler trim, the following system components are required:  
a. Circulator - The best circulator location is usually on the supply piping just downstream of the expansion  
tank as shown in Figure 30.  
b. Expansion Tank - Consult the expansion tank manufacturer’s literature for proper sizing.  
c. Fill Valve - Either a manual or automatic fill valve may be used. The fill connection should be located at the  
expansion tank. On large systems with an automatic fill valve, it is recommended that a small water meter be  
installed in the make-up water line to monitor the amount of water added to the system.  
d. Air Elimination Device - At least one automatic air elimination device is required and should be located at the  
expansion tank. Manual vents will usually be required in other parts of the system to facilitate the removal of air  
during initial fill.  
4) Certain systems will require additional considerations:  
a. Low System Return Temperatures - The bypass piping shown in Figure 30 will minimize the amount of time that  
the boiler operates with return temperatures below 120°F on these systems. A bypass is installed as shown to  
divert some supply water directly into the return water. The bypass pipe should be the same size as the supply.  
The two throttling valves shown are adjusted so that the return temperature rises above 120°F during the first few  
minutes of operation. A three-way valve can be substituted for the two throttling valves shown.  
b. Systems containing oxygen - Many hydronic systems contain enough dissolved oxygen to cause severe corrosion  
damage to a cast iron boiler such as the Series 32. Some examples include:  
• Radiant systems that employ tubing without an oxygen barrier.  
• Systems with routine additions of fresh water.  
• Systems which are open to the atmosphere.  
If the boiler is to be used in such a system, it must be separated from the oxygenated water being heated with a  
heat exchanger. Consult the heat exchanger manufacturer for proper heat exchanger sizing as well as flow and  
temperature requirements. All components on the oxygenated side of the heat exchanger, such as the pump and  
expansion tank, must be designed for use in oxygenated water.  
c. Piping with a Chiller - If the boiler is used in conjunction with a chiller, pipe the boiler and chiller in parallel.  
Use isolation valves to prevent chilled water from entering the boiler. See Figure 31.  
d. Air Handlers - Where the boiler is connected to air handlers through which refrigerated air passes, use flow  
control valves in the boiler piping or other automatic means to prevent gravity circulation during the cooling  
cycle.  
38  
Figure 29: Water Boiler Tapping Locations  
Tapping Uses Chart For Water Boilers1  
Component Description  
Tapping  
Location  
A
Tapping Standard  
CSD-1  
Size (in) Equipment Package  
SupplyPiping  
Return Piping  
3
3
N
N
Y
Y
N
Y
N
N
Y
Y
Y
Y
B
PressureReliefValves  
C
2
1-1/2  
1/2  
-
Combination Pressure / Temperature / Altitude Gauge  
Hydrolevel #750 Probe Low Water Cut-Off  
Honeywell L4006APressure Limit Control  
Honeywell L4006EManual Reset Pressure Limit Control  
(To Be Installed On The Same Side As L4006A)  
Boiler Drain Valve  
E
SupplyRiser  
D
1/2  
SupplyRiser  
-
N
Y
B
F
F
3
-
Y
Y
N
Y
Y
N
Cover Plate  
Optional Tankless Heater  
-
1. TrimMayBe Installed On Either End Section.  
2. Use The Tapping Located On The End Not Equipped With TrimFor The Pressure Relief Valve.  
Table 7  
39  
40  
Supply  
Header  
Supply Water  
Riser Connections Header  
Return  
Return Water  
Connections  
Boiler  
Model  
Size (in) Quantity Size (in) Size (in) Quantity Size (in)  
32-475  
32-570  
32-665  
32-760  
32-855  
32-950  
2
2
2 1/2  
2 1/2  
2 1/2  
3
3
3
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4
4
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2 1/2  
2 1/2  
2 1/2  
3
3
3
3
3
3
2 1/2  
2 1/2  
2 1/2  
2 1/2  
3
3
3
3
3
3
3
3
3
3
3
2
2
2 1/2  
2 1/2  
2 1/2  
3
3
3
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4
4
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2 1/2  
2 1/2  
2 1/2  
3
3
3
3
3
3
2 1/2  
2 1/2  
2 1/2  
2 1/2  
3
3
3
3
3
3
3
3
3
3
3
32-1045  
32-1140  
32-1235  
32-1330  
32-1425  
32-1520  
32-1615  
32-1710  
32-1805  
32-1900  
32-1995  
32-2090  
32-2185  
32-2280  
32-2375  
32-2470  
32-2565  
32-2660  
32-2755  
32-2850  
4
4
Note: 1.The pipe sizes listed above are nominal trade sizes for Schedule 40  
Table 8: Water Boiler Supply & Return Pipe Sizes  
Figure 31: Recommended Boiler Piping For  
Combination Heating & Cooling Systems  
41  
B. TANKLESS HEATER PIPING  
If the Series 32 water boiler is installed with an optional tankless heater, pipe the heater as shown in Figure 32. The  
components in this system and their functions are as follows:  
1) Mixing Valve (Required) - During the heating season, the water exiting the tankless heater may be 180 degrees or  
more. The mixing valve blends hot water leaving the tankless heater with cold water so as to maintain the hot water  
supplied to the fixtures at a fixed temperature. This saves energy, increases the amount of usable hot water available  
to the homeowner, and reduces the risk of scalding.  
Install a mixing valve with a setting range of approximately 110 to 130F. Follow the manufacturer’s instructions for  
installing this valve. Usually a “heat trap” will be required between the coil and the “hot” connection on the mixing  
valve.  
WARNING  
A mixing valve does not eliminate the risk of scalding.  
Set the mixing valve and boiler low limit adjustments as low as possible.  
Feel water before showering or bathing  
If anti-scald or anti-chill protection is required, use devices specifically designed for such service. Install and  
maintain these devices in accordance with the manufacturer’s instructions. Do not use the mixing valve as a  
substitute for pressure balancing valves or other devices required by plumbing codes to protect against  
scalding.  
2) Flow Restrictor (Recommended) - If water is drawn from the tankless coil at a rate in excess of the rating in Table 9,  
the temperature of the hot water may be too low to be of use. The use of a flow restrictor will prevent this problem by  
limiting the rate at which water can pass through the tankless heater. If a restrictor is used, select one having a rating  
inGPM approximately equal to the rating shown in Table 9. If possible, locate this restrictor at least 3 feet from the  
tankless heater inlet so that it is not subjected to excessive temperatures when no water is flowing through the coil.  
3) Pressure Relief Valve (Required) - Limits the pressure in the tankless heater and piping. Use an ASME constructed  
valve designed for domestic water service, such as the Watts #3L. Note that this is a pressure relief valve, not a T&P  
valve. Select a valve with a pressure setting less than or equal to the working pressure marked on the tankless coil.  
Pipe the discharge to a safe location using piping the same size as the discharge connection on the valve.  
4) Hose Bib Valves (Recommended) - These valves permit the coil to be periodically “backflushed” to remove sediment.  
5) Globe or Ball Valve (Recommended) - Used to adjust the flow through the entire tankless heater system if needed.  
6) Unions (Required) - Tankless heaters may require periodic gasket replacement or other maintenance which requires  
removal of the heater from the boiler. Install unions anywhere in the tankless heater piping that will facilitate removal  
of the heater.  
7) Backflow Preventer (Required in Massachusetts) - If required by local codes, install a backflow preventer in the cold  
water connection to the tankless coil just upstream of the piping shown in Figure 32. Install in accordance with local  
codes and the backflow preventer’s installation instructions. Also install a potable water expansion tank on the outlet  
side of the backflow preventer (between the backflow preventer and the piping shown in Figure 32).  
42  
8) Multiple Tankless Heaters - If two tankless heaters are installed in the boiler, it is recommended that each heater be  
installed in parallel with its own mixing valve, relief valve, flow restrictor, etc.. This will permit either heater to be  
removed from service for maintenance while still providing some domestic water to the building.  
Figure 32: Tankless Heater Piping  
Continuous Draw  
Heater Ratings  
40° - 140° Rise  
Minimum  
Num ber of  
Sections  
Clearance  
Requirement  
For Heater  
Rem oval  
Pressure Drop  
Through Heater  
(psi)  
Tankless Heater  
Model Number  
For Use In  
Boilers  
with 200°F Boiler  
Temperature  
Required Per  
Heater  
All Sizes  
All Sizes  
4.5 GPM  
5.0 GPM  
6.0 GPM  
8.8  
18.0  
1.2  
5
6
8
27"  
32"  
42"  
T-1  
T-2  
T-3  
32-665 & Larger  
All Series 32 boilers are furnished w ith left and right heater end sections. It is possible to install a heater in both ends  
provided the number of sections in the boiler in not less than the sum of the number of sections required for each  
heater as indicated in the table. Example: T2 + T3 = 6 + 8 = 14 section or larger boiler.  
Table 9: Tankless Heater Specifications  
43  
X Gas Piping  
1) Gas piping to the boiler must be sized to deliver an adequate supply of gas for the boiler to fire at the nameplate  
input with the inlet pressure at the gas valves between the minimum and maximum valves shown on the rating  
plate. For more information on gas line sizing, consult the Utility or the National Fuel Gas Code.  
2) Figure 33 shows the typical gas piping connection(s) to the Series 32 boiler. A sediment trap must be installed  
upstream of all gas controls. Install a manual shut-off valve and ground joint union as shown.  
3) The boiler and its gas connection must be leak tested before placing the boiler in operation. When doing this, the  
boiler and its individual shut-off must be disconnected from the rest of the system during any pressure testing of  
that system at pressures in excess of 1/2 psi. When pressure testing the gas system at pressures of 1/2 psi or  
less, isolate the boiler from the gas supply system by closing its individual manual shut-off valve.  
Figure 33: Gas Main Piping And Branch Connections To Boiler  
44  
XI Control System Wiring  
WARNING  
All wiring and grounding must be done in accordance with the authority having jurisdiction or, in the absence of such  
requirements, with the National Electrical Code (ANSI/NFPA 70).  
1) Provide the boiler with a dedicated branch circuit with a fused disconnect. The minimum rating of this circuit  
must be 15A.  
2) Wire the boiler following the appropriate wiring diagram in Figures 35 or 36. Use 14 gauge wire for all 120 volt  
boiler wiring. Use wire with a temperature rating of 105°C for wiring routed along gas manifolds. Install the  
junction box provided on one of the end panels. This junction box is to become the hub for all limit and low water  
cut-off wiring. All 120 volt boiler wiring must be enclosed in conduit. Route wiring to base modules in flexible  
conduit along the gas manifolds. See Figure 34 for typical wire routing.  
3) Make sure that all single pole switches and safety controls are in the “hot” (ungrounded) side of the circuit.  
4) The “operating control” shown in Figures 35 and 36 is not supplied. It is the control that turns on the boiler in  
response to a call for heat. If a 24 volt thermostat is to be used as the operating control a 24 volt relay center,  
such as the Honeywell R845, may be used to cycle the boiler in response to a call for heat. An R845A may also be  
used to start a system circulator if necessary as long as it’s contact rating is not exceeded.  
On water boilers with multiple base modules, the bases may be “staged” by using a set of operating control  
contacts to break the 24 volt “hot” (ungrounded) lead connecting the base transformer to the ignition module. Do  
not stage steam boilers with multiple bases.  
WARNING  
OPERATING CONTROL CONTACTS MUST BE “DRY” (ELECTRICALLY ISOLATED FROM ALL OTHER  
CIRCUITS IN THE OPERATING CONTROL). IF OPERATING CONTROL CONTACTS ARE NOT DRY, THE  
BOILER SAFETY DEVICES COULD BE DEFEATED RESULTING IN PROPERTY DAMAGE, INJURY OR  
LOSS OF LIFE.  
Sequence of Operation – Standard Boiler Wiring  
1) All low water cut-offs, limit controls, and the operating contacts are wired in series so that the boiler will not  
operate if any of these controls are open. Under normal circumstances, only the operating control contacts will be  
open.  
2) Upon a call for heat, the operating control will make and 120 volts will be applied to all base module transformers,  
which are wired in parallel.  
3) 24 volts will then appear across the “24V” and “24V (GND)” terminals on the ignition modules.  
4) Upon application of voltage across the “24V” and “24V (GND)” terminals, the ignition module will start an ignition  
spark at the pilot and apply 24 volts across the pilot valve.  
5) Once the pilot is established, the pilot flame will act as a diode, converting the AC current at the electrode to a half  
wave DC current at the pilot’s ground strap. This DC current flows through the boiler to the “GND (BURNER)”  
connection on the ignition module.  
45  
6) Once the ignition module detects the presence of a pilot flame, voltage is applied across the main valve, opening  
the valve and establishing main flame.  
7) The way in which the ignition module handles failure to establish pilot or the loss of an already established pilot  
depends upon the exact ignition module supplied with the boiler. For more information on module operation,  
consult the ignition module instructions supplied with the boiler or the local Crown representative.  
Sequence of Operation – CSD-1 Boiler Wiring  
1) All low water cut-offs, limit controls, and the operating contacts are wired in series so that the boiler will not  
operate if any of these controls are open. Under normal circumstances, only the operating control contacts will be  
open.  
2) Upon a call for heat, the operating control will make and 120 volts will be applied to all base module transformers,  
which are wired in parallel.  
3) 24 volts will then appear across the “24V” and “24V (GND)” terminals on the ignition modules and on the  
“24VAC” and “COM” terminals on the 1145-2 Daughter Board.  
4) The ignition module will start an ignition spark at the pilot and apply 24 volts across the pilot valve.  
5) Once a pilot is established, the pilot flame will act as a diode, converting AC current at the pilot electrode to a half  
wave DC current at the pilot’s ground strap. This DC current flows through the boiler to the “GND” terminal on  
the ignition module.  
6) Once the ignition module detects the presence of a pilot flame, voltage is applied across the main valve, opening  
the valve and establishing main flame.  
7) If the pilot flame is not established during the trial for ignition period, or if the pilot signal is lost after the main  
flame is established, the module will de-energize the open pilot valve and main valve (if open) and wait 5 minutes.  
It will then repeat steps 4-6. If the pilot is still not established, the Alarm contacts on the ignition module will  
make. This will cause the 1145-2 Daughter Board to break power to the ignition module and illuminate the red  
LED on the Daughter Board. The ignition module will remain de-energized until the reset button on the daughter  
board is pressed.  
Figure 34: Typical Wire Routing  
46  
Figure 35: Series 32 Standard Boiler Wiring  
47  
Figure 36: Series 32 - CSD-1 Boiler Wiring  
48  
Safety Control Operation  
Temperature Limit Control (Water Boilers) – The temperature limit control interrupts burner operation when the supply  
water temperature exceeds the set point. Maximum allowable water temperature in a water boiler is 250F. The L4006A  
will reset itself when the water temperature drops below the set point less the differential (typically 15F). Manual reset  
water limit controls, such as the Honeywell L4006E, must be manually reset. For this reason, they should be set well  
above the operating limit control to avoid nuisance boiler shut-downs.  
Pressure Limit Control (Steam Boilers) – The pressure limit control interrupts burner operation when the steam pressure  
exceeds the set point. Maximum allowable steam pressure is 15psi, however the pressure limits should be set below this  
to prevent the safety valve from opening unnecessarily. Manual reset pressure limit controls, such as the Honeywell  
L404C, must be manually reset. For this reason, they should be set well above the operating pressure limit control to  
avoid nuisance boiler shut-downs.  
Low Water Cut-off (Steam and Water Boilers) – Low water cut-offs interrupt burner operation if the water level in the  
boiler drops below a safe level. Steam boilers may be equipped with two low water cutoffs so that there is a back up low  
water cut-off if the first one fails to shut down the boiler in a low water condition. In this case, the back up low water  
cutoff must be installed below the “operating” low water cut-off and is usually a manual reset type.  
49  
XII Start-up and Checkout  
NOTE  
SAFE LIGHTING AND OTHER PERFORMANCE CRITERIA WERE MET WITH THE GAS MANIFOLD AND  
CONTROL ASSEMBLY PROVIDED ON THE BOILER WHEN THE BOILER UNDERWENT THE TESTS  
SPECIFIED IN Z21.13.  
Use the following procedure for initial start-up of the boiler:  
1) Make sure that the boiler is filled with water.  
2) Check all new gas piping for leaks and purge piping sections that are filled with air. See the National Fuel Gas  
Code for additional information on testing and purging gas lines.  
3) Verify that vent system is complete and free of obstructions before attempting to fire boiler.  
4) Inspect all wiring for loose or uninsulated connections.  
5) Make sure the main burners are seated properly in the rear of burner tray and on orifices.  
6) Adjust thermostat to the highest setting.  
7) Start the boiler using the appropriate lighting instructions for the gas valve on the boiler on pages 54 and 55.  
8) Upon initial start-up, the gas train will be filled with air. Even if the gas line has been completely purged of air, it  
may take several tries for ignition before a flame is established. Once a flame has been established for the first time,  
subsequent calls for burner operation should result in a flame on the first try.  
9) Observe pilot burner flame. See Figure 37. The pilot flame should be a steady medium blue flame covering around  
3/8” to ½” of the spark electrode/flame rod.  
10) Inspect the main burner flames visible through the observation port in burner access panel. The flame should be  
stable and mostly blue (See Figure 38). No yellow tipping should be present; however, intermittent flecks of yellow  
and orange in the flame are normal.  
11) Check entire gas train for leaks using soap and water or other approved leak detection method while boiler is  
firing. Fix any leaks found immediately.  
WARNING  
NEVER USE A FLAME TO CHECK FOR GAS LEAKS.  
MAKE SURE THAT THE AREA AROUND THE BOILER IS CLEAR AND FREE FROM  
COMBUSTIBLE MATERIALS, GASOLINE, AND OTHER FLAMMABLE VAPORS AND  
LIQUIDS.  
12) Run the gas valve safety shutdown test with the main burners firing. Disconnect ignition cable from the ignition  
module on the first base module. Both the pilot burner and main burners on the base module should stop firing.  
Repeat this procedure for each base module.  
50  
WARNING  
FAILURE TO FOLLOW THE FOLLOWING PROCEDURE EXACTLY COULD RESULT  
IN OVER-FIRING OF THE BOILER AND A CARBON MONOXIDE HAZARD.  
13) Check the manifold pressure and adjust if necessary. To do this, use the following procedure:  
a. Connect a manometer to the inlet pressure tap on the gas valve (see Figures 39 - 41).  
b. Check the inlet pressure with all gas appliances on and off. The inlet pressure at the inlet of each gas valve  
must be within the following limits regardless of what combination of appliances is firing:  
Inlet Press (inches w.c.)  
Natural Gas  
5.0  
Min.  
Max.  
14.0  
If the inlet pressure falls outside of these limits, find and correct the cause of the problem before proceeding  
further.  
c. Connect a manometer to the manifold (outlet) pressure tap on the gas valve on the first base module. See  
Figures 39 - 41.  
d. Read the manifold pressure. It should be set at 3.5 inches w.c..  
e. If a manifold pressure adjustment is needed, make the adjustment by turning the pressure regulator (see Figures  
39 - 41) screw clockwise to raise the pressure and counter clockwise to reduce the pressure. If a manifold  
pressure adjustment is made, recheck the line pressure at each base module to be certain that it is still within  
acceptable limits. Replace the cover screw on the regulator.  
f. Repeat steps a - e for the remaining base modules.  
14) Test thermostat operation while the boiler is running. Turn the thermostat to the lowest setting. Both pilot  
burner and main burners should stop firing. Raise the thermostat back to the highest setting. The pilot burner and  
main burners should relight.  
15) (Water Boilers) - Verify high limit operation. Allow the boiler water temperature to increase to high limit setting.  
The burners should shut down and the circulator continue running. Allow the boiler water temperature to drop  
below high limit setting. The pilot burner and main burners should relight.  
Figure 37: Pilot Burner Flame  
Figure 38: Main Burner Flame  
51  
16) (Steam Boilers) - Verify low water cutoff operation while the boiler is running. Slowly open drain valve and drain  
boiler until the water level drops below low water cutoff line. Water still should be visible in the gauge glass  
when the low water cutoff shuts down the main burners. The pilot burner and main burners should stop firing.  
Make sure pressure limit, thermostat or other controls have not shut off the boiler. Upon test completion refill  
the boiler to the normal water level.  
17) (Steam Boilers) - Check pressure limit control operation. When steam pressure is registered on pressure gauge,  
lower pressure limit setting below gauge reading. The pilot burner and main burners should stop firing. Raise  
pressure limit setting above gauge reading. The pilot burner and main burners should relight.  
18) (Steam Boilers) - Replacement of a steam boiler tends to break loose accumulated scale from the system. During  
the first week of operation, blow down any float type water cut-offs at least three times following the blow down  
instructions provided by the low water cut-off manufacturer.  
19) (Steam Boilers) - After the new boiler has been installed and put into continuous operation for several days, clean  
the boiler of oil, grease, sludge, and other contaminants that may have been present in existing piping. This will  
prevent unsteady water line and water carry over into supply main. The boiler boil-out should be done as follows:  
a. Turn off gas supply to boiler per the appropriate Lighting and Operating instructions on pages 54 and 55.  
b. Drain water from boiler until about one inch of water is visible in gauge glass.  
c. Run a hose or temporary piping from the boiler drain valve to a location where hot water can be safely  
discharged. Drain approximately five gallons of water from the boiler and mix-in an appropriate amount of an  
approved boil-out compound. Refill the boiler with prepared solution through funnel inserted into the surface  
skimmer tapping. Run a temporary drain line made of hose or piping from the surface skimmer tapping to a  
location where hot water can be safely discharged.  
d. Light off the boiler per the appropriate instructions on pages 54 and 55. Run boiler for several hours, boiling  
the water, without generating steam pressure. Open the water feed valve sufficiently to allow a slight overflow  
of water through the temporary drain line attached to the surface skimmer tapping. Continue boiling until  
water coming out is clear.  
e. Turn off gas supply to boiler per the appropriate Lighting and Operating instructions on pages 54 and 55.  
Drain hot water from boiler through boiler drain valve to a location where hot water can be safely discharged.  
Refill the boiler to normal water line level. If water in the gauge glass does not look clear, repeat above boil-  
out procedure again until water is clears.  
f. Close the surface skimmer tapping.  
g. Conduct pH and Alkalinity test of water in the system. The pH reading should be in 7 to 11 range.  
NOTE  
When substantial amount of make-up water is used due to lost condensate, or when make-up water is hard or corrosive,  
water treatment is required. Contact qualified water treatment company for recommended water treatment compounds  
and procedures.  
20) (All Boilers) - Inspect the vent system for flue gas leaks. Repair any leaks found before leaving the boiler in  
operation.  
21) (All Boilers) - After the boiler has operated for approximately 30 minutes, check the boiler and heating  
system piping for leaks. Repair any leaks found at once.  
52  
Figure 39: Gas Valve Detail - Honeywell VR8304  
Figure 40: Gas Valve Detail - Robertshaw 7000DERHC  
Figure 41: CSD-1 Gas Train  
53  
LIGHTING INSTRUCTIONS FOR BASE MODULES EQUIPPED WITH  
HONEYWELL VR8304 SERIES GAS VALVES  
FOR YOUR SAFETY READ BEFORE LIGHTING  
WARNING: If you do not follow these instructions exactly, a fire or explosion  
may result causing property damage, personal injury or loss of life.  
A. This appliance is equipped with an ignition  
device which automatically lights the pilot.  
Do not try to light the pilot by hand.  
If you cannot reach your gas supplier, call  
the fire department.  
C. Use only your hand to push in or turn the gas  
control knob. Never use tools. If the knob will  
not push in or turn by hand, don’t try to repair it,  
call a qualified service technician. Force or  
attempted repair may result in a fire or explosion.  
B. BEFORE LIGHTING smell all around the  
appliance area for gas. Be sure to smell next  
to the floor because some gas is heavier than  
air and will settle on the floor.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
Do not touch any electric switch; do not  
use any phone in your building.  
Immediately call your gas supplier from  
a neighbor’s phone. Follow the gas  
supplier’s instructions.  
D. Do not use this appliance if any part has been  
under water. Immediately call a qualified service  
technician to inspect the appliance and to  
replace any part of the control system and any  
gas control which has been under water.  
OPERATING INSTRUCTIONS  
1. STOP! Read the safety information above on  
this label.  
5. Remove front access panel.  
6. Rotate the gas control knob clockwise  
to OFF.  
2. Set the thermostat to lowest setting.  
7. Wait five (5) minutes to clear out any gas. Then  
smell for gas, including near the floor. If you then  
smell gas, STOP! Follow “B” in the safety inform-  
ation above on this label. If you don’t smell gas  
go to the next step.  
3. Turn off all electric power to the appliance.  
4. This appliance is equipped with an ignition  
device which automatically lights the pilot.  
Do not try to light the pilot by hand.  
8. Rotate the gas control knob counter clockwise  
to “ON”.  
GAS CONTROL KNOB  
(SHOWN IN “ON” POSITION)  
9. Replace front access panel.  
10. Turn on all electric power to the appliance.  
11. Set thermostat to desired setting.  
GAS INLET  
GAS OUTLET  
12. If the appliance will not operate, follow the  
instructions “To Turn Off Gas To Appliance” and  
call your service technician or gas supplier.  
GAS VALVE - TOP VIEW  
TO TURN OFF GAS TO APPLIANCE  
1. Set the thermostat to lowest setting.  
3. Push in gas control knob slightly and turn  
clockwise to “OFF”. Do not Force.  
2. Turn off all electric power to the appliance if  
service is to be performed.  
54  
LIGHTING INSTRUCTIONS FOR BASE MODULES EQUIPPED WITH  
ROBERTSHAW 7000DERHC SERIES GAS VALVES  
FOR YOUR SAFETY READ BEFORE LIGHTING  
WARNING: If you do not follow these instructions exactly, a fire or explosion  
may result causing property damage, personal injury or loss of life.  
A. This appliance is equipped with an ignition  
device which automatically lights the pilot.  
Do not try to light the pilot by hand.  
If you cannot reach your gas supplier, call  
the fire department.  
C. Use only your hand to push in or turn the gas  
control knob. Never use tools. If the knob will  
not push in or turn by hand, don’t try to repair it,  
call a qualified service technician. Force or  
attempted repair may result in a fire or explosion.  
B. BEFORE LIGHTING smell all around the  
appliance area for gas. Be sure to smell next  
to the floor because some gas is heavier than  
air and will settle on the floor.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
Do not touch any electric switch; do not  
use any phone in your building.  
Immediately call your gas supplier from  
a neighbor’s phone. Follow the gas  
supplier’s instructions.  
D. Do not use this appliance if any part has been  
under water. Immediately call a qualified service  
technician to inspect the appliance and to  
replace any part of the control system and any  
gas control which has been under water.  
OPERATING INSTRUCTIONS  
1. STOP! Read the safety information above on  
this label.  
5. Remove front access panel.  
6. Rotate the gas control knob clockwise  
to OFF.  
2. Set the thermostat to lowest setting.  
7. Wait five (5) minutes to clear out any gas. Then  
smell for gas, including near the floor. If you then  
smell gas, STOP! Follow “B” in the safety inform-  
ation above on this label. If you don’t smell gas  
go to the next step.  
3. Turn off all electric power to the appliance.  
4. This appliance is equipped with an ignition  
device which automatically lights the pilot.  
Do not try to light the pilot by hand.  
8. Rotate the gas control knob counter clockwise  
to “ON”.  
POSITION  
INDICATOR  
9. Replace front access panel.  
10. Turn on all electric power to the appliance.  
11. Set thermostat to desired setting.  
F
O F  
O N  
GAS  
INLET  
12. If the appliance will not operate, follow the  
instructions “To Turn Off Gas To Appliance” and  
call your service technician or gas supplier.  
GAS CONTROL KNOB  
SHOWNIN"OFF" POSITION  
TO TURN OFF GAS TO APPLIANCE  
1. Set the thermostat to lowest setting.  
3. Push in gas control knob slightly and turn  
clockwise to “OFF”. Do not Force.  
2. Turn off all electric power to the appliance if  
service is to be performed.  
55  
XIII Service and Maintenance  
The following routine maintenance should be performed:  
On a continuous basis:  
1) Keep the area around the boiler free and clear from combustible materials, gasoline, and other flammable vapors  
and liquids.  
2) Keep the area around the boiler and boiler room ventilation openings clear of objects which might obstruct the  
flow of combustion and ventilation air.  
On at least a weekly basis:  
For boilers equipped with a float type low water cut-off, blow down the low water cut-off by following the low water  
cut-off manufacturer’s instructions. During this blow down, the low water cutoff should shut down the burners. If it does  
not, the low water cut-off should be replaced immediately.  
On an annual basis:  
1) Turn off electrical power and gas supply to the boiler  
2) Inspect the flue passages for signs of blockage. If there is any carbon in the combustion chamber or the flue  
passages, clean the heat exchanger before proceeding further. See the cleaning procedure below.  
3) Remove any debris found in the combustion chamber, being careful not to disturb combustion chamber insulation  
4) Remove all burners, noting the location of the pilot main burner. If burners show signs of deterioration, they  
should be replaced (some discoloration around the burner ports is normal). Clean the burners by first brushing  
the ports with a soft bristle brush and then vacuuming out any debris through the venturi opening.  
5) Inspect the pilot assembly. Clean any deposits found on the electrode and grounding strap. The ideal gap between  
the electrode and the ground strap is 1/8”. Inspect the porcelain for cracks or other deterioration. Replace pilot  
assembly if deterioration is found.  
6) Inspect the combustion chamber insulation for deterioration.  
7) Inspect the ignition cable insulation for cracks or other deterioration. If deterioration is found, replace cable.  
CAUTION  
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN  
CAUSE IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER SERVICING  
8) Reinstall burners, being careful to put the pilot main burner in its original location.  
9) Inspect all boiler wiring for loose connections or deterioration.  
10) Inspect the vent system:  
Make sure that both the vent system is free of obstructions.  
Make sure that all vent system supports are intact.  
Inspect joints for signs of condensate or flue gas leakage.  
Inspect venting components for corrosion or other deterioration. Replace any defective vent components.  
11) Inspect the boiler system for leaks.  
CAUTION  
WATER LEAKS CAN CAUSE SEVERE CORROSION DAMAGE TO THE BOILER OR OTHER SYSTEM COMPO-  
NENTS. REPAIR ANY LEAKS FOUND IMMEDIATELY  
56  
12) Place the boiler back in operation using the procedure outlined in “Start-up”. Check the pilot line and any other  
gas piping disturbed during the inspection process for leaks.  
Heat Exchanger Cleaning Procedure  
1) Turn off electrical power and gas supply to the boiler  
2) Disconnect the vent connectors from the boiler.  
3) Remove the front, top and rear jacket panels.  
4) Remove the burners.  
5) Remove the nuts and washers holding the flue collector onto the heat exchanger.  
6) Carefully remove the flue collector gasket strips and set them aside.  
7) Remove the flue collector from the heat exchanger.  
8) Clean the flue passageways using a stiff bristle brush. Be certain that all foreign material is removed from the  
gaps between the pins.  
9) Clean the bottom surfaces of the heat exchanger.  
10) Put a light in the combustion chamber and look through the flue passages from the top to verify that they have  
been thoroughly cleaned.  
11) Replace the flue collector gasket strips.  
12) Replace the nuts and washers that hold down the flue collector.  
13) Reattach all the jacket components.  
14) Reinstall burners, being careful to put the pilot main burner in its’ original location.  
15) Reconnect the vent system.  
WARNING  
SOOT DEPOSITS IN THE FLUE PASSAGES ARE A SIGN THAT THE BOILER MAY BE OPERATING AT HIGH  
CARBON MONOXIDE (CO) LEVELS. AFTER CLEANING THE BOILER OF SOOT DEPOSITS, CHECK THE CO  
LEVEL IN THE FLUE GAS TO INSURE THAT THE BOILER IS OPERATING PROPERLY.  
If it is necessary to check CO, use a combustion analyzer, or other instrument which is designed to measure CO in flue gas.  
A CO “sniffer” designed for testing CO levels in ambient air cannot be used to check boiler combustion. Take a flue gas  
sample by inserting a sample probe through the draft diverter opening and into the flue collector so that the sample is taken  
in the area directly over the heat exchanger. Do not take a sample until the boiler has been firing for at least five minutes.  
A normal CO reading for a Series 32 boiler is less than 50ppm (0.005%). A reading of more than 100ppm (0.01%) is  
indicative of a combustion problem.  
Some causes of excessive CO include:  
Incorrectly sized main burner orifice for the altitude at which boiler is installed  
Crooked or out-of-round orifice holes (never attempt to drill orifice for this boiler in the field)  
Partially plugged flue passages  
Improper manifold pressure  
Foreign material in burner venturis or burner ports  
Inadequate supply of combustion air  
57  
XIV PARTS  
The following parts may be obtained from any Crown distributor. To find the closest Crown distributor, consult the area Crown  
representative or the factory at:  
Crown Boiler Co.  
Customer Service  
P.O. Box 14818  
Philadelphia PA. 19134  
(215) 535-8900  
For boilers installed at elevations above 2000 ft, consult the local Crown representative or the factory for the correct main burner  
orifice.  
58  
)
E A M S D T T S ( N O  
W D A T T S ( N O  
E L R I C A R B T O  
R E )  
R E C L A R T B O I  
N O  
O N  
C M A I R R T T E A M S T  
C M A I R R T E R T W A T  
D E S P I A N E C L A K E T J  
N O  
C A R T  
N O  
C A R T  
D E P A N E L B A S E S I  
E L R I S ) B O E T A S M (  
A T E D I R E M T N  
E
A T P P E D I  
E L R I S ) B O E T A S M (  
E T I A D E M R E T I N  
E L R I S )  
E R A B T W O (  
E T I A D E M R E T I N  
E L R I S ) B L O L A (  
D N E T F L E  
E L R I S ) B L O L A (  
D N E T G I H R  
59  
TANKLESS COILS PARTS  
PA RT #  
310020  
310021  
310022  
MODEL  
T-1  
T-2  
T-3  
BASE CARTON  
QUANTITY  
380  
DESCRIPTION  
PA RT #  
285  
1
475  
1
285 BASEASSEMBLY (STD)  
380 BASEASSEMBLY (STD)  
475 BASEASSEMBLY (STD)  
310114  
310115  
310116  
3101145  
3101155  
3101165  
310311  
900309  
900312  
900311  
310310  
310320  
90-212  
900145  
900315  
900313  
900104  
900102  
90-210  
90-211  
90-035  
90-036  
90-221  
1
1
285 BASEASSEMBLY (CSD-1)  
380 BASEASSEMBLY (CSD-1)  
475 BASEASSEMBLY (CSD-1)  
REAR TIE ROD CHANNEL BRACKET  
5/8 X 4 STUD  
1
1
1
1
1
1
1
1
5/8 USS WASHER  
2
2
2
5/8 NUT  
2
2
2
JACKET REAR PANEL SUPPORT BRACKET  
JA CKET TOP SUPPORT BRA CKET  
#10 X 1/2 HEX HD SHEET METAL SCREW  
GASKET ROPE  
1
1
1
1
1
1
12  
5 ft  
2
12  
6 ft  
2
12  
7 ft  
2
5/16-18 X 5 CARRIAGE BOLT  
5/16-18 X 3 CARRIAGE BOLT  
5/16-18 WING NUT  
2
2
2
2
2
2
5/16 USS FLAT WASHER  
JACKET KNOBS  
4
4
4
2
2
2
8-32 X 1/4 SCREW  
2
2
2
3/8-16 X 3/4 CAPSCREW  
3/8 USS FLAT WASHER  
3/8-16 HEX NUT  
4
4
4
4
4
4
4
4
4
INTERMEDIATE CARTON  
PA RT #  
QUANTITY  
380  
DESCRIPTION  
285 FRONT PANEL  
285  
1
475  
1
310314  
310315  
310316  
310324  
310325  
310326  
310304  
310305  
310306  
310124  
310125  
310126  
380 FRONT PANEL  
475 FRONT PANEL  
285 TOPPANEL  
1
1
1
1
1
1
1
380 TOPPANEL  
475 TOPPANEL  
1
285 REAR PANEL *  
380 REAR PANEL *  
475 REAR PANEL *  
285 FLUECOLLECTOR  
380 FLUECOLLECTOR  
475 FLUECOLLECTOR  
1
1
* INCLUDES HEAT SHIELD  
60  
SECTION JOINER CARTON  
QUANTITY  
DESCRIPTION  
7" PUSHNIPPLE  
PA RT #  
"A"  
"B"  
6
"C"  
7
"D"  
8
"E"  
9
310005  
310006  
900310  
900311  
900312  
900350  
900355  
900360  
970030  
5
5
3" PUSHNIPPLE  
6
7
8
9
5/8 X 9 3/4 TIE ROD  
5/8 HEX NUT  
15  
30  
30  
2
18  
36  
36  
3
21  
42  
42  
3
24  
48  
48  
27  
54  
54  
5/8 FLAT WASHER  
LOCTITE # 592, 50 ml TUBE  
LOCTITE # 592, 250 ml TUBE  
"SECTION SEAL", 1 QUART CAN  
WOOD WEDGE  
1
2
2
1
2
2
2
2
2
2
2
2
BASE SIDE CARTON  
DESCRIPTION  
PA RT #  
QTY .  
RH BASE SIDE PANEL ASSY.  
LH BASE SIDE PANEL ASSY.  
JA CKET SIDE PA NEL ZEE BRA CKET  
JA CKET TOP SUPPORT BRA CKET  
JA CKET TOP SUPPORT END A NGLE  
JACKET REAR PANEL SUPPORT BRACKET  
REAR TIE ROD CHANNEL BRACKET  
5/8 X 4 STUD  
310662  
310663  
310302  
310320  
310321  
310310  
310311  
900309  
900312  
900311  
90-035  
90-036  
90-221  
310010  
900455  
90-212  
1
1
2
1
2
1
1
1
2
2
4
4
8
4
4
20  
5/8 USS WASHER  
5/8 NUT  
3/8-16 X 3/4 CAPSCREW  
3/8 USS FLAT WASHER  
3/8-16 HEX NUT  
BLOCK ANCHOR  
3/8-16 X 2 CAPSCREW  
#10 X 1/2 HEX HD SHEET METAL SCREW  
JACKET SIDE PANEL CARTON  
DESCRIPTION  
PA RT #  
QTY.  
RH JACKET SIDE PANEL ASSY.  
LH JACKET SIDEPANEL ASSY.  
310300  
310301  
1
1
61  
BASE PARTS  
QTY PER BASE MODULE  
KEY  
DESCRIPTION  
BASEFRONT PANEL (285)  
PA RT #  
285  
1
380  
475  
1
1
310604  
310605  
310606  
310110  
310111  
312614  
312615  
312616  
310664  
310665  
310666  
310660  
310661  
312600  
312604  
312605  
312606  
900203  
900200  
900440  
90-221  
90-036  
310650  
310651  
310624  
310625  
310626  
90-212  
900305  
BASEFRONT PANEL (380)  
BASEFRONT PANEL (475)  
BASE FRONT LEG (RH)  
1
1
1
1
1
2a  
2b  
3
1
1
1
1
1
BASE FRONT LEG (LH)  
INSULATION BASE FRONT (285)  
INSULATION BASE FRONT (380)  
INSULATION BASE FRONT (475)  
BASEREAR PANEL (285)  
BASEREAR PANEL (380)  
BASEREAR PANEL (475)  
RIGHT SIDE PANEL  
3
1
1
3
1
1
4
1
4
4
1 PER BOILER  
1 PER BOILER  
2 PER BOILER  
5
6
LEFT SIDEPANEL  
7
BASE SIDEINSULATION  
INSULATION BASE REAR (285)  
INSULATION BASE REAR (380)  
INSULATION BASE REAR (475)  
#10 x 1-1/4 CUPHEAD PIN  
#10 SPEED NUT  
8
1
8
1
8
1
9
8 PER MODULE, 6 PER SIDE  
PA NEL  
10  
11  
12  
13  
15  
16  
17  
17  
17  
18  
19  
3/8-16 X 3/4 CARRIAGEBOLT  
3/8-16 HEX NUT  
4
4
4
1
1
1
4
4
4
1
1
4
4
4
1
1
3/8-16 USS FLAT WASHER  
BASE SIDE CHANNEL (RH)  
BASE SIDE CHANNEL (LH)  
BURNER ACCESS PANEL (285)  
BURNER ACCESS PANEL (380)  
BURNER ACCESS PANEL (475)  
1
1
2
6
#10 X 1/2 HEX HD SHEET METAL SCREW  
2
6
2
6
1/4-20 X 3/4 GRADE5 HEX WASH HD SCREW  
62  
63  
BASE PARTS (CONTD.)  
QUANTITY  
380  
KEY  
DESCRIPTION  
PA RT #  
285  
1
475  
20  
20  
20  
21  
22  
23  
24  
24a  
24b  
25  
*
MANIFOLD ASSY, COMPLETE(285)  
MANIFOLD ASSY, COMPLETE(380)  
MANIFOLD ASSY, COMPLETE(475)  
1/4-20 X 1/2 SELF TAPPING SCREW  
MAIN BURNER LESS PILOT BRKT  
MAIN BURNER WITH PILOT BRKT.  
PILOT ASSY, Q362A1037  
310154  
310155  
1
310156  
1
4
900100  
4
7
4
10  
1
150321  
13  
1
150320  
1
3504060  
3501550  
3501150  
146-95-301  
9601101  
3501136  
900040  
1
1
1
BCR-18 PILOT ORIFICE  
1
1
1
1/4" COMPRESSION FERRULE  
10-32 X 3/16 MACHINESCREW  
GROUND WIRE  
2
2
2
2
2
2
1
1
1
*
36" IGNITION CABLE  
1
1
1
*
1/4" O.D. PILOT TUBING (ft)  
1.5  
8
1.5  
11  
11  
1.5  
14  
14  
26  
27  
28  
29  
30  
31  
*
2.75mm MAIN BURNER ORIFICE(SEA LEVEL)  
ORIFICEHITCH PIN  
950380  
950370  
8
3/4" 45 DEGREESTREET EL  
950044  
1
1" 45 DEGREE STREET EL  
950045  
1
1
GAS VALVE, VR8304P4306  
GAS VALVE, ROBERTSHAW 7000DERHC  
PILOT VALVE(CSD-1 ONLY)  
RV12L PILOT REGULATOR (CSD-1 ONLY)  
JUNCTION BOX  
3507250  
3507310  
3503107  
3503115  
96-055  
1 (**)  
(**)  
1
1
1
1
1
1
1
2
2
1
2
1
1
1
1
1
1
2
2
1
2
*
1
32  
33  
34  
35  
36  
37  
*
1
JUNCTION BOX COVER  
96-054  
1
TRANSFORMER, AT140C1030  
8-32 X 1/2" SCREW  
35-2000  
90-052  
1
2
8-32 HEX NUT  
90-053  
2
IGNITION MODULE, S8610M 1011(STD ONLY)  
TRANSFORMER HARNESS (STD ONLY)  
IGNITION HARNESS (STD ONLY)  
IGNITION HARNESS (STD ONLY)  
IGNITION MODULE, UT 1003-612A (CSD-1 ONLY)  
DAUGHTER BOARD, UT 1145-2 (CSD-1 ONLY)  
3505015  
9605110  
9601100  
9605100  
3503100  
3503105  
1
2
*
1
*
1
1
1
1
1
1
38  
*
1
1
DAUGHTER BOARD MOUNTING BRACKET  
(CSD-1 ONLY)  
*
310200  
1
1
1
*
*
*
*
*
*
DAUGHTER BOARD COVER (CSD-1 ONLY)  
VALVE HARNESS (CSD-1 ONLY)  
310205  
9605900  
9605902  
9605907  
9605905  
9605910  
1
1
2
1
1
1
1
1
2
1
1
1
1
1
2
1
1
1
ALARM HARNESS (CSD-1 ONLY)  
"R-STAT" JUMPER HARNESS (CSD-1 ONLY)  
"IGNITION MODULE HARNESS" (CSD-1 ONLY)  
"HOT" TRANSFORMER HARNESS (CSD-1 ONLY)  
"COMMON" TRANSFORMER HARNESS  
(CSD-1 ONLY)  
*
9605912  
900460  
1
1
1
1
1
1
"PILOT COMPRESSION" x NPT THREAD ADAPTER  
(CSD-1 ONLY)  
*
* NOT PICTURED  
** ROBERTSHAW 7000 DERHC USED ON CSD-1 285 BASES  
NOTE: SOME STANDARD FITTINGS USED ON CSD-1 BASES NOT LISTED - PROCURE THESE LOCALLY  
64  
65  
WATER TRIM CARTON  
DESCRIPTION  
PART #  
QTY  
L4006A2015  
35-3510  
35-3100  
35-1006  
450550  
950021  
95-038  
95-053  
270003  
270001  
90-036  
900450  
95-143  
950100  
95-048  
95-052  
950035  
95-041  
1
1
L4006E1109 MAN. RESET (CSD-1 ONLY)  
1/2 LONG WELL  
1
HYDROLEVEL 550 LWCO (CSD-1 ONLY)  
1-1/2 X 1/2 BLK BUSHING  
TRIDICATOR GAUGE  
1
1
1
1/2 X 1/4 BLK BUSHING  
BLANK COIL PLATE  
1
2
COIL GASKET  
2
3/8 USS FLAT WASHER  
3/8-16 X 7/8 HEX HD CAP SCREW  
1-1/2" NPT BLK PLUG  
1" NPT BLK PLUG  
12  
12  
2
2
3/4" NPT BLK PLUG  
4
1/2" NPT BLK PLUG  
7
3 X 3/4 BLK BUSHING  
BOILER DRAIN  
1
1
STEAM TRIM CARTON  
DESCRIPTION  
PART #  
QTY  
LWCO, #67 CR-3 (STANDARD)  
LWCO, CG450 (CSD-1 ONLY)  
GLASS SET (20-104-10, 8" CTR TO CTR)  
PA404A1009  
400680  
45-460P  
950080  
35-5020  
35-3020  
95-060  
950004  
951441  
95-091  
95-070  
95-146  
95-116  
95-150  
95-147  
270003  
270001  
90-036  
900450  
95-143  
950100  
95-048  
95-052  
950035  
95-041  
1
1
1
1
L404C1147 (CSD-1 ONLY)  
STRAIGHT BRASS PIGTAIL  
1/2 X 4 BRASS NIPPLE  
1/2 BRASS TEE  
1
1*  
1
1
1/2 BRASS PLUG  
1
PRESSURE GAUGE  
1
1/2 X 1/4 BRASS BUSHING  
1/2 X 3 BR NIPPLES  
2
2
1/2" BR. UNION  
2
1/2 X CL BRASS NIPPLES  
BLANK COIL PLATE  
2
2
COIL GASKET  
2
3/8 USS FLAT WASHER  
3/8-16 X 7/8 HEX HD CAP SCREW  
1-1/2" NPT BLK PLUG  
1" NPT BLK PLUG  
12  
12  
3
2
3/4" NPT BLK PLUG  
4
1/2" NPT BLK PLUG  
5
3 X 3/4 BLK BUSHING  
BOILER DRAIN  
1
1
* 2 REQD. ON CSD-1 BOILERS  
66  
E
P P L K N I B L X 4 / C 1 - L  
W O B L  
1
9 5 - 0 3 1  
1 - 1 / 4 E 9 5 - 0 5 8  
E
P P L K N I B L X 4 / 4 1 -  
1
9 5 - 0 3 3  
G I N H S U B K L  
1 - 1 / 4 B 1 - 1 / 2 X 9 5 - 0 4 7  
E
P P L K N I B L X C 1 L  
9 5 0 1 1 0  
W B O E L 1  
9 5 0 1 9 0  
9 5 0 1 1 4  
9 5 0 1 8 5  
9 5 - 1 0 5  
E
P P L K N I B L X 4 1  
N G  
K B U B S L H X I 2 / 1 1 -  
1
E
P P L K N I B L X 4 / C L 3  
W O B L  
3 / 4 E 9 5 - 0 5 7  
E
P P L K N I B L X 4 / 3  
K B U B 4 S / L H I X 2 / 3 1 -  
3
9 5 - 0 2 7  
9 5 - 0 9 6  
9 5 0 5 0 0  
9 5 - 1 3 4  
9 5 - 0 8 1  
9 5 - 0 4 0  
N G  
1
1 O 0 - C 6 A 1 6 R - B 0 N 5 O C , E V L A V F L I E E R I S  
1 O 0 - C 6 A 1 5 R - B 0 N 5 O C , E V L A V F L I E E R I S  
1 O 0 - C 6 A 1 4 R - B 0 N 5 O C , E V L A V F L I E E R I S  
1 O 0 - C 4 A 0 8 R - B 0 N 5 O C , E V L A V F L I E E R I S  
3 0 P  
3 0 P  
3 0 P  
3 0 P  
E B U  
, 1 1 C 6 o P - z T  
R E S B O N 9 D 0 0 9 3 0 6 7 5 G F  
N I P P 0 L E 9 2 9 8 0  
U G G E A  
N A U A L S M  
U S E R ' 9 8 0 4 2 5  
L
N U A I O T N M L A L A A T  
I N S  
9 8 0 8 8 8  
9 8 - 1 1 1  
E
A T P G L N I  
R L A T E T  
67  
G I N H S U B K L  
1 - 1 / 4 B 1 - 1 / 2 X 9 5 - 0 4 7  
N G  
K B U B S L H X I 2 / 1 1 -  
1
9 5 0 1 8 5  
G N I H S U B K L  
3 / 4 B  
1 - 1 / 2 X 9 5 - 0 9 6  
U G K P L B 2 / L 1 -  
1
9 5 0 1 7 0  
G
L I P N U O C K L  
1 - 1 / 2 B 9 5 0 1 7 5  
1 - 1 / 2 B 9 5 0 1 8 0  
1 - 1 / 2 X 9 5 0 1 2 4  
E E T K L  
L E P P I N K L  
4 B  
5 0 2 - 2 1  
4 1 2 - 3 1  
3 1 2 - 3 1  
2 0 2 - 3 1  
1 1 2 - 3 1  
N B R C A C O V O E , V Y A T L E  
N B R C A C O V O E , V Y A T L E  
N B R C A C O V O E , V Y A T L E  
N B R C A C O V O E , V Y A T L E  
N B R C A C O V O E , V Y A T L E  
1 , 1 o 6 z - C T F P  
S A F P 5 S I 1  
S A F P 5 S I 1  
S A F P 5 S I 1  
S A F P 5 S I 1  
S A F P 5 S I 1  
9 5 0 5 3 0  
9 5 0 5 2 5  
9 5 0 5 2 0  
9 5 0 5 1 5  
9 5 0 5 1 0  
E B U  
R E S B O N 9 D 0 0 9 3 0 6 7 5 G  
E G U G A L E P P I N 0 9 2 9 8 0  
N A U A L S M  
U S E R ' 9 8 0 4 2 5  
L
N U A I O T N M L A L A A T  
I N S  
9 8 0 8 8 8  
9 8 - 1 1 1  
E
A T P G L N I  
R L A T E T  
68  
Manufacturer of Hydronic Heating Products  
P.O. Box 14818 3633 I. Street  
Philadelphia, PA 19134  
PN 980888  
Rev.2 10/08  

Brother BRUGSANVISNING FAX T106 User Manual
Bryan Boilers DSH 20 User Manual
Bushnell Boating Equipment 70 0101 User Manual
Bushnell Night Vision 26 26 4366 User Manual
Canon zr830 User Manual
FujiFilm Camera Lens YV3 3X15SA 2 User Manual
Grizzly G0562Z User Manual
Havis Shields S UMM DLX TX2 User Manual
Infinity Systems Inc Car Speaker 40 2CS User Manual
Jensen MP6512i User Manual