FB-I-O Rev H
Installation & Operation Manual
Models: 1.5 - 2.0 - 2.5 - 3.0 - 3.5
This manual must only be used by
ƽ WARNING
a qualified heating installer / service
technician. Read all instructions,
including this manual and the Crest
Service Manual, before installing.
Perform steps in the order given.
Failure to comply could result in
severe personal injury, death, or
substantial property damage.
Save this manual for future reference.
Installation & Operation Manual
Please read before proceeding
Installer – Read all instructions, including
When servicing boiler –
ƽ WARNING
this manual and the Crest Service Manual,
before installing. Perform steps in the
order given.
• To avoid electric shock, disconnect electrical supply
before performing maintenance.
User – This manual is for use only
• To avoid severe burns, allow boiler to cool before
performing maintenance.
by
a
qualified heating installer/
service technician. Refer to the User’s
Information Manual for your reference.
Boiler operation –
Have this boiler serviced/inspected by
a qualified service technician, at least
annually.
• Do not block flow of combustion or ventilation air to
the boiler.
• Should overheating occur or gas supply fail to shut off,
do not turn off or disconnect electrical supply to
circulator. Instead, shut off the gas supply at a location
external to the appliance.
Failure to comply with the above could
result in severe personal injury, death or
substantial property damage.
When calling or writing about the boiler
– Please have the boiler model and serial
number from the boiler rating plate.
NOTICE
• Do not use this boiler if any part has been under water.
The possible damage to a flooded appliance can be
extensive and present numerous safety hazards. Any
appliance that has been under water must be replaced.
Consider piping and installation when
determining boiler location.
Boiler water –
Any claims for damage or shortage in
shipment must be filed immediately
against the transportation company by
the consignee.
• Thoroughly flush the system (without boiler
connected) to remove sediment. The high-efficiency
heat exchanger can be damaged by build-up or
corrosion due to sediment.
Factory warranty (shipped with unit) does
not apply to units improperly installed or
improperly operated.
• Do not use petroleum-based cleaning or sealing
compounds in the boiler system. Gaskets and seals in
the system may be damaged. This can result in
substantial property damage.
Failure to adhere to the guidelines on this
page can result in severe personal injury,
death, or substantial property damage.
ƽ WARNING
• Do not use “homemade cures” or “boiler patent
medicines”. Serious damage to the boiler, personnel,
and/or property may result.
If the information in this manual is not
followed exactly, a fire or explosion may
result causing property damage, personal
injury or loss of life.
ƽ WARNING
• Continual fresh make-up water will reduce boiler life.
Mineral buildup in the heat exchanger reduces heat
transfer, overheats the stainless steel heat exchanger,
and causes failure. Addition of oxygen carried in by
makeup water can cause internal corrosion in system
components. Leaks in boiler or piping must be repaired
at once to prevent the need for makeup water.
This appliance MUST NOT be installed in
any location where gasoline or flammable
vapors are likely to be present.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a near by phone. Follow the
gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the fire department.
• Installation and service must be
performed by a qualified installer,
service agency, or the gas supplier.
Freeze protection fluids –
• NEVER use automotive antifreeze. Use only inhibited
propylene glycol solutions, which are specifically
formulated for hydronic systems. Ethylene glycol is
toxic and can attack gaskets and seals used in hydronic
systems.
3
Installation & Operation Manual
The Crest - How it works...
19. High limit devices (primary and backup)
1. Front access panels
The high limit devices are used to monitor the outlet water
temperature - if either device senses the water temperature
exceeding the predetermined setting, the boiler will shut down.
Provides access to the controls compartment.
2. Top access panel
Provides access to the burner compartment.
20. Ignition electrode
3. Air pressure switch
An electrical spark across the electrodes will ignite the first
burner.
The air pressure switch detects blocked flue/vent conditions.
4. Blowers
21. Line voltage junction box
The blowers pull in air and gas through the venturis (item
34). Air and gas mix inside the blowers and are pushed into the
burner, where they burn inside the combustion chamber.
The line voltage junction box contains the connection points for
the line voltage power to the boiler (and pumps if used).
22. Line voltage wiring connections (knockouts)
5. Boiler drain connection
Conduit connection points for the high voltage junction box.
Location from which the heat exchanger can be drained.
23. Low gas pressure switch
6. Boiler inlet temperature sensor
Monitors gas supply pressure to the boiler and shuts the boiler
down in the event a low gas pressure condition occurs.
The boiler inlet temperature sensor monitors system return
water temperature. If selected as the controlling sensor,
the control module will adjust the boiler firing rate so the inlet
temperature matches the set point.
24. High gas pressure switch (not shown)
Monitors gas supply pressure to the burner and shuts the boiler
down in the event a high gas pressure condition occurs.
7. Boiler outlet temperature sensor
25. Low voltage connection board(s)
The boiler outlet temperature sensor monitors boiler outlet
water temperature. If selected as the controlling sensor,
the control module will adjust the boiler firing rate so the outlet
temperature matches the set point.
Connection boards used to connect external low voltage devices.
26. Low voltage wiring connections (knockouts)
Conduit connection points for the low voltage connection boards.
8. Burner (not shown)
27. Low water cutoff probe (LWCO)
Integral dual chamber design with a stress free metal fiber
outer mesh and durable stainless steel structure. Provides two
(2) independent firing rates up to 25:1 turndown.
Ensures adequate water is supplied to the boiler. In the event of
inadequate water levels, the boiler will shut down.
28. Power switch
9. Condensate drain connection
The On/Off power switch provides the ability to turn line voltage
The condensate drain connection provides a connection
point to install a condensate drain line using flexible hose
provided.
power to the boiler on and off.
29. Relief valve
The safety relief valve protects the heat exchanger from an over
pressure condition. The boiler comes with a 50 PSI relief valve as
standard equipment. Optional settings are available.
10. Control module (on control panel assembly)
The control module responds to internal and external signals
and controls the blowers, gas valves, and pump(s), depending on
the application, to meet the heating demand.
30. Reset switch
11. Electronic display
Reset switch for the low water cutoff. Hold the switch for 10
seconds to reset.
Digital controls with SMART TOUCH screen technology, full
color display, and an 8" user interface screen.
31. Test switch
12. Flame inspection windows
The test switch permits manual triggering of the LWCO
safety circuit to test the contacts and evaluate the integrity of the
circuit. Hold the switch for 10 seconds to test.
Two large high temperature quartz observation windows
provide views of each independent burner surface during
firing.
32. Firetube heat exchanger
High grade stainless steel WAVETM firetube design that extracts
heat from flue gases and transfers it directly into boiler water.
13. Dual flame sensors
The dual flame sensors are used by the control module to detect
the presence of a burner flame at both independent burner
surfaces.
33. Temperature and pressure gauge
Monitors the outlet temperature of the boiler as well as the system
water pressure.
14. Flue temperature sensor
The flue sensor monitors flue gas temperature. The control
module will modulate or shut the boiler down if the flue gas
temperature gets too high.
34. Venturis
Separate venturis control air and gas flow into two (2) independent
burner sections.
15. Gas connection pipe
35. Water inlet
The gas connection pipe is a threaded black iron pipe
connection (see Gas Connections Section for specific model
pipe size requirements). This pipe should be connected to the
incoming gas supply to deliver gas to the boiler.
A 4" ANSI flange connects the return water from the system to the
heat exchanger.
36. Water outlet
A 4" ANSI flange connects the hot water supply from the boiler to
the system.
16. Gas shutoff valve (inside unit)
The manual gas shutoff valve is used to isolate the boiler gas
train from the gas supply.
37. Ignition transformer
The transformer provides voltage to the ignition electrode (item
20).
17. Gas valves
The gas valves sense the negative pressure created by the
blowers, allowing gas to flow only if the gas valves are powered
and combustion air is flowing.
38. Air arm temperature sensors (not shown)
Monitors fuel-air delivery temperature to the burner.
39. Air inlet cover (shipped loose)
Used with room air for combustion and to prevent debris from
entering the boiler.
18. Blower proving switches
Prove adequate airflow during prepurge.
4
Installation & Operation Manual
The Crest - How it works...
(continued)
Models 1.5 - 2.0 - 2.5 - 3.0 - 3.5
2
39
29
11
7
19
10
36
1
6
5
35
9
Front View
Rear View
18
15
16
34
23
19
3
37
25
26
29
21
22
33
12
13
34
28
30
31
20
12
27
17
4
14
Right Side (inside unit)
32
5
Left Side (inside unit)
Installation & Operation Manual
Ratings
Crest
AHRI Rating
Other Specifications
Net
AHRI
Ratings
Water,
MBH
Vent Weight
Size w/Water
Model Number
Gross
Output
MBH
Input
MBH
Appliance
Water
Content
Gallons
Pipe Pipe
Size Size
Outlet Inlet
Air
Size
(lbs.)
Gas Inlet
Size
Note: Change “N” to
“L” for L.P. gas models.
(Note 4)
(Note 3)
(Note 1)
(Note 2)
Min
60
Max
96
4"
4"
4"
4"
4"
4"
4"
4"
4"
4"
1 1/2"
1 1/2"
2"
7"
8"
7"
8"
2500
3055
3650
4125
4750
FB(N,L)1500
FB(N,L)2000
FB(N,L)2500
FB(N,L)3000
FB(N,L)3500
1500
1380
1840
2300
2760
3220
1200
1600
2000
2400
2800
132
161
181
215
80
2000
2500
3000
3500
8"
9"
125
150
200*
2”
10"
10"
10"
10"
2”
*For LP models the minimum input is 420 MBH.
Maximum allowed working pressure is located on the rating plate.
NOTICE
Notes:
1. The ratings are based on standard test procedures
prescribed by the United States Department of Energy.
UNIT EQUIPPED FOR
2. Net AHRI ratings are based on net installed radiation of
sufficient quantity for the requirements of the building
and nothing need be added for normal piping and pickup.
Ratings are based on a piping and pickup allowance of
1.15.
HIGH ALTITUDE
3,000 FT. TO 12,000 FT.
3. Crest boilers require special gas venting. Use only
the vent materials and methods specified in the Crest
Installation and Operation Manual.
4. Standard Crest boilers are equipped to operate from sea
level to 4,500 feet only with no adjustments.
5. High altitude Crest boilers are equipped to operate
from 3,000 to 12,000 feet. High altitude models are
manufactured with different control parameters for high
altitude operation, but the sequence of operation given
in this manual remains the same as the standard boilers.
A high altitude label (as shown in FIG A.) is also affixed
to the unit.
6. The boiler will de-rate by 4% for each 1,000 feet above
sea level up to 4,500 feet and 4.5% for each 1,000 feet
above 4,500 feet.
Figure A High Altitude Label Location
7. Ratings have been confirmed by the Hydronics Section
of AHRI.
6
Installation & Operation Manual
1 Determine boiler location
This appliance is certified as an indoor appliance.
Do not install the appliance outdoors or locate
where the appliance will be exposed to freezing
temperatures or to temperatures that exceed 100°F
(37.8°C).
Installation must comply with:
ƽ WARNING
•
•
•
Local, state, provincial, and national codes, laws,
regulations, and ordinances.
National Fuel Gas Code, NFPA 54 / ANSI Z223.1 –
latest edition.
Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1 -
latest edition, when required.
Do not install the appliance where the relative
humidity may exceed 93%. Do not install the
appliance where condensation may form on
the inside or outside of the appliance, or where
condensation may fall onto the appliance.
•
•
National Electrical Code, NFPA 70 - latest edition.
For Canada only: CSA B149.1 Installation Code,
CSA C22.1 Canadian Electrical Code Part 1 and any
local codes.
Failure to install the appliance indoors could result
in severe personal injury, death, or substantial
property damage.
The Crest gas manifold and
NOTICE
This appliance requires a special venting system.
Use only the vent materials specified in this
manual. Failure to follow all instructions can
result in flue gas spillage and carbon monoxide
emissions, causing severe personal injury or death.
controls met safe lighting and other
ƽ WARNING
performance criteria when the boiler
underwent tests specified in ANSI
Z21.13/CSA 4.9 – latest edition.
Before locating the boiler, check:
Provide clearances:
1. Check for nearby connection to:
• System water piping
• Venting connections
• Gas supply piping
If you do not provide the recommended service
clearances shown, it may not be possible to service
the boiler without removing it from the space.
NOTICE
• Electrical power
Clearances from combustible materials
2. Locate the appliance so that if water connections
should leak, water damage will not occur. When
such locations cannot be avoided, it is
recommended that a suitable drain pan, adequately
drained, be installed under the appliance. The
panmustnotrestrictcombustionairflow. Underno
circumstances is the manufacturer to be held
responsible for water damage in connection with
this appliance, or any of its components.
- Hot water pipes........................................................ 1/4"
- Sides.......................................................................... 0"
- Rear........................................................................... 0"
- Front......................................................................... 0"
- Top ........................................................................... 0"
- Floor ....................................................... Combustible
- Vent pipe - Follow special vent system manufacturer’s instructions
Recommended clearances for service access
- Sides.......................................................................... 24"
- Rear........................................................................... 24"
- Front......................................................................... 30"
- Top ........................................................................... 24"
3. Check area around the boiler. Remove any
combustible materials, gasoline and other
flammable liquids.
Figure 1-1 Recommended Service Clearances
1/4" (6 MM) MINIMUM CLEARANCE
AROUND HOT WATER PIPES
Failure to keep boiler area clear
ƽ WARNING
and free of combustible materials,
24"
TOP
gasoline, and other flammable
liquids and vapors can result in
severe personal injury, death, or
substantial property damage.
VENTILATING*
AIR OPENING
4. The Crest must be installed so that gas control
system components are protected from dripping or
spraying water or rain during operation or service.
CLOSED DOOR
5. If a new boiler will replace an existing boiler, check
for and correct system problems, such as:
• System leaks causing oxygen corrosion or heat
exchanger cracks from hard water deposits.
• Incorrectly-sized expansion tank.
24"
LEFT
24"
REAR
• Lack of freeze protection in boiler water causing
system and boiler to freeze and leak.
24"
RIGHT
6. The appliance must be installed on a level floor,
both front to back and side to side, for proper
condensate drainage.
VENTILATING*
AIR OPENING
30"
FRONT
7
Installation & Operation Manual
1 Determine boiler location
Provide air openings to room:
The Crest alone in boiler room
Vent and air piping
The Crest requires a special gas vent system, designed for
pressurized venting.
1. No air ventilation openings into the boiler room are
needed when clearances around the Crest are at least
equal to the SERVICE clearances shown in FIG. 1-1.
For spaces that do NOT supply this clearance, provide
two openings as shown in FIG. 1-1. Each opening must
provide one square inch free area per 1,000 Btu/hr of
boiler input.
The boiler is to be used for either direct vent installation or
for installation using indoor combustion air. When room air
is considered, see page 23 of this manual. Note prevention of
combustion air contamination below when considering vent/
air termination.
Vent and air must terminate near one another and may be
vented vertically through the roof or out a side wall, unless
otherwise specified. You may use any of the vent/air piping
methods covered in this manual. Do not attempt to install
2. Combustion air openings are required when using the
Room Air Option on page 23 of this manual.
The Crest in same space with other gas or oil-fired the Crest using any other means.
appliances
Be sure to locate the boiler such that the vent and air piping
1. Follow the National Fuel Gas Code (U.S.) or CSA B149.1 can be routed through the building and properly terminated.
(Canada) to size/verify size of the combustion/ventilation The vent/air piping lengths, routing and termination method
air openings into the space.
must all comply with the methods and limits given in this
manual.
The space must be provided with
ƽ WARNING
combustion/ventilation air openings
correctly sized for all other appliances
located in the same space as the Crest.
Prevent combustion air contamination
Install air inlet piping for the Crest as described in this
manual. Do not terminate vent/air in locations that can
allow contamination of combustion air. Refer to Table 1A,
page 9 for products and areas which may cause contaminated
combustion air.
Failure to comply with the above warnings
could result in severe personal injury,
death, or substantial property damage.
2. Size openings only on the basis of the other appliances in
the space. No additional air opening free area is needed
for the Crest when it takes its combustion air from
outside (direct vent installation).
Ensure that the combustion air will not
ƽ WARNING
contain any of the contaminants in Table
1A, page 9. Contaminated combustion
air will damage the boiler, resulting in
possible severe personal injury, death
or substantial property damage. Do not
pipe combustion air near a swimming
pool, for example. Also, avoid areas
subject to exhaust fumes from laundry
facilities. These areas will always contain
contaminants.
Flooring and foundation
Flooring
The Crest is approved for installation on combustible flooring,
but must never be installed on carpeting.
Do not install the boiler on carpeting even
ƽ WARNING
if foundation is used. Fire can result,
causing severe personal injury, death, or
substantial property damage.
If flooding is possible, elevate the boiler sufficiently to prevent
water from reaching the boiler.
Assure that the floor and structure is
ƽ WARNING
sufficient to support the installed weight
of the boiler, including the water content
in the heat exchanger. If not, structural
building failure will result, causing severe
personal injury, death, or substantial
property damage.
8
Installation & Operation Manual
1 Determine boiler location
(continued)
When using an existing vent system to
install a new boiler:
Table 1A Corrosive Contaminants and Sources
Products to avoid:
Failure to follow all instructions can result
ƽ WARNING
in flue gas spillage and carbon monoxide
Spray cans containing chloro/fluorocarbons
Permanent wave solutions
emissions, causing severe personal injury
or death.
Chlorinated waxes/cleaners
Check the following venting components before installing:
Chlorine-based swimming pool chemicals
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
• Material - For materials listed for use with this appliance,
see Section 2 - General Venting, Table 2A. For stainless
steel venting, an adapter of the same manufacturer
(Table 2B) may be used at the flue collar connection.
• Size - To ensure proper pipe size is in place, see Table 2C.
Check to see that this size is used throughout the vent
system.
Paint or varnish removers
Hydrochloric acid/muriatic acid
Cements and glues
• Manufacturer - Only use the listed manufacturers and
their type product listed in Table 2A for CAT IV positive
pressure venting with flue producing condensate.
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and cleaning solvents
found in household laundry rooms
• Supports - Non-combustible supports must be in place
allowing a minimum 1/4" rise per foot. The supports
should adequately prevent sagging and vertical slippage,
by distributing the vent system weight. For additional
information, consult the vent manufacturer’s
instructions for installation.
Adhesives used to fasten building products and other similar
products
Areas likely to have contaminants
Dry cleaning/laundry areas and establishments
Swimming pools
• Terminations - Carefully review Sections 2 through 4 to
ensure requirements for the location of the vent and air
terminations are met and orientation of these fit the
appropriate image from the Sidewall or Vertical
options listed in the General Venting Section.
Metal fabrication plants
Beauty shops
Refrigeration repair shops
• Seal - With prior requirements met, the system should be
tested to the procedure listed in parts (c) through (f) of
the Removal of an Existing Boiler Section on page 10.
Photo processing plants
Auto body shops
With stainless steel vent, seal and connect all pipe and
components as specified by the vent manufacturer used.
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
If any of these conditions are not met,
the existing system must be updated or
ƽ WARNING
replaced for that concern. Failure to
follow all instructions can result in flue gas
spillage and carbon monoxide emissions,
causing severe personal injury or death.
Garages with workshops
9
Installation & Operation Manual
1 Determine boiler location
When removing a boiler from existing
common vent system:
Do not install the Crest into a common
ƽ DANGER
d. Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat so
appliance will operate continuously.
vent with any other appliance except
as noted in Section 2 on page 18.
This will cause flue gas spillage or
appliance malfunction, resulting in
possible severe personal injury, death,
or substantial property damage.
e. Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the flame of
a match or candle, or smoke from a cigarette, cigar, or
pipe.
Failure to follow all instructions can
ƽ WARNING
f. After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined herein, return
doors, windows, exhaust fans, fireplace dampers, and
any other gas-burning appliance to their previous
conditions of use.
result in flue gas spillage and carbon
monoxide emissions, causing severe
personal injury or death.
At the time of removal of an existing boiler, the following
steps shall be followed with each appliance remaining
connected to the common venting system placed in
operation, while the other appliances remaining connected
to the common venting system are not in operation.
g. Any improper operation of the common venting
system should be corrected so the installation conforms
with the National Fuel Gas Code, ANSI Z223.1/NFPA
54 and/or CAN/CSA B149.1, Natural Gas and Propane
Installation Code. When re-sizing any portion of the
common venting system, the common venting system
should be resized to approach the minimum size as
determined using the appropriate tables in Part 11 of
the National Fuel Gas Code, ANSI Z223.1/NFPA 54
and/or CAN/CSA B149.1, Natural Gas and Propane
Installation Code.
a. Seal any unused openings in the common venting
system.
b. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion, or other deficiencies,
which could cause an unsafe condition.
c. Test vent system – Insofar as is practical, close all
building doors and windows and all doors between
the space in which the appliances remaining connected
to the common venting system are located and other
spaces of the building. Turn on clothes dryers and
any appliance not connected to the common venting
system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, so they will operate at
maximum speed. Do not operate a summer exhaust
fan. Close fireplace dampers.
10
Installation & Operation Manual
1 Determine boiler location
(continued)
Remove boiler from wood pallet
Figure 1-3 Boiler Removed from Shipping Pallet
1. After removing the outer shipping crate and plastic
from the boiler, remove the parts package (packaged parts
inside the controls compartment of the boiler inside the
lower front access panel).
2. To remove the boiler from the pallet:
REMOVE MIDDLE
TOP COVER
a. Remove the three (3) shipping bolts located inside
the controls compartment securing the boiler to the
front of the pallet (see FIG. 1-2).
LIFTING
LUGS
b. Remove the three (3) shipping bolts that fasten the
tie-down brackets securing the legs to the rear of the
pallet (FIG. 1-2).
LIFTING
LUGS
c. The boiler can now be removed from the pallet
using a lift truck lifting from the front or rear of
the boiler. If lifting from the front, the lift truck
forks must extend at least half way under the boiler
heat exchanger to assure proper lifting technique
with no damage to the boiler.
Maintain minimum specified clearances for adequate operation.
All installations must allow sufficient space for servicing the
vent connections, water pipe connections, piping and other
auxiliary equipment, as well as the appliance. The clearance
labels on each appliance note the same service and combustible
clearance requirements as shown in this manual.
Failure to assure the truck forks are
ƽ WARNING
long enough to extend at least halfway
under the boiler heat exchanger will
result in the boiler tipping off the lift
truck, and potentially falling. This will
result in severe personal injury, death, or
substantial property damage.
Multiple boilers may be installed side by side with no clearance
between adjacent boilers because this boiler is approved for zero
clearance from combustible surfaces; however, service access
will be limited from the sides.
d. If lifting by crane is desired, remove the top access
panels to gain access to the lifting lugs located on the
boiler (see FIG. 1-3). It is also recommended that the
upper and lower front panels along with both front
side panels be removed (no tools required).
Consult the Venting section of this manual for specific
installation instructions for the appropriate type of venting
system that you will be using.
Do not drop the boiler or bump the jacket
on the floor or pallet. Damage to the
NOTICE
boiler can result.
Figure 1-2 Boiler Mounted on Shipping Pallet
BOLT, WASHERS
& LOCKNUT (3X)
FRONT
LAG BOLTS & TABS
(3X)
REAR
11
Installation & Operation Manual
1 Determine boiler location
Combustion
and
ventilation
air
requirements for appliances drawing air
from the equipment room
Provisions for combustion and ventilation air must be in
accordance with Air for Combustion and Ventilation, of the
latest edition of the National Fuel Gas Code, NFPA 54 / ANSI
Z223.1, in Canada, the latest edition of CGA Standard B149
Installation Code for Gas Burning Appliances and Equipment,
or applicable provisions of the local building codes.
The equipment room MUST be provided with properly sized
openings and/or be of sufficient volume to assure adequate
combustion air and proper ventilation for all gas fired appliances
in the equipment room to assure adequate combustion air and
proper ventilation.
Figure 1-5_Combustion Air Through Ducts
2. If combustion and ventilation air is taken from the
outdoors using a duct to deliver the air to the
equipment room, each of the two openings should be
sized based on a minimum free area of one square inch
per 2000 Btu/hr (11 cm2 per kW) of input (see FIG. 1-5).
The requirements shown are for the appliance only; additional
gas fired appliances in the equipment room will require an
increase in the net free area and/or volume to supply adequate
combustion air for all appliances.
No combustion air openings are needed when the appliance is
installed in a space with a volume NO LESS than 50 cubic feet
per 1,000 Btu/hr of all installed gas fired appliances and the
3
building MUST NOT be of “Tight Construction” .
A combination of indoor and outdoor combustion air may
be utilized by applying a ratio of available volume to required
volume times the required outdoor air opening(s) size(s). This
must be done in accordance with the National Fuel Gas Code,
NFPA 54 / ANSI Z223.1.
Figure 1-6_Combustion Air from Interior Space
3. If air is taken from another interior space combined with
the equipment room:
(a) Two spaces on same story: Each of the two openings
specified above should have a net free area of one square
2
inch for each 1000 Btu/hr (22 cm per kW) of input, but
2
not less than 100 square inches (645 cm ) (see FIG. 1-6).
(b) Two spaces on different stories: One or more openings
should have a net free area of two square inches per 1000
2
Btu/hr (44 cm per kW).
Figure 1-4_Combustion Air Direct from Outside
1. If air is taken directly from outside the building
with no duct, provide two permanent openings to
the equipment room each with a net free area of one square
2
inch per 4000 Btu/hr input (5.5 cm per kW) (see FIG. 1-4).
Figure 1-7_Combustion Air from Outside - Single Opening
12
Installation & Operation Manual
1 Determine boiler location
(continued)
Under no circumstances should the
equipment room ever be under negative
pressure. Particular care should be taken
where exhaust fans, attic fans, clothes dryers,
compressors, air handling units, etc., may
take away air from the unit.
4. If a single combustion air opening is provided to bring
combustion air in directly from the outdoors, the
opening must be sized based on a minimum free area
of one square inch per 3000 Btu/hr (7 cm2 per kW). This
opening must be located within 12” (30 cm) of the top of
the enclosure (see FIG. 1-7).
ƽ CAUTION
The combustion air supply must be completely free of any
flammable vapors that may ignite or chemical fumes which may
be corrosive to the appliance. Common corrosive chemical
fumes which must be avoided are fluorocarbons and other
halogenated compounds, most commonly present as refrigerants
or solvents, such as Freon, trichlorethylene, perchlorethylene,
chlorine, etc. These chemicals, when burned, form acids which
quickly attack the stainless steel heat exchanger, headers, flue
collectors, and the vent system.
Combustion air requirements are based on the latest edition
of the National Fuel Gas Code, NFPA 54 / ANSI Z223.1; in
Canada refer to the latest edition of CGA Standard CAN/CSA
B149.1. Check all local code requirements for combustion air.
All dimensions based on net free area in square inches. Metal
louvers or screens reduce the free area of a combustion air
opening a minimum of approximately 25%. Check with
louver manufacturers for exact net free area of louvers.
Where two openings are provided, one must be within 12"
(30 cm) of the ceiling and one must be within 12" (30 cm) of
the floor of the equipment room. Each opening must have a
The result is improper combustion and a non-warrantable,
premature appliance failure.
net free area as specified in Table 1B. Single openings shall EXHAUST FANS: Any fan or equipment which exhausts air
commence within 12" (30 cm) of the ceiling. The minimum from the equipment room may deplete the combustion air
dimension of air openings shall not be less than 3" (80 mm).
supply and/or cause a downdraft in the venting system. Spillage
of flue products from the venting system into an occupied
living space can cause a very hazardous condition that must be
corrected immediately.
TABLE - 1B
MINIMUM RECOMMENDED COMBUSTION
AIR SUPPLY TO EQUIPMENT ROOM
FIG. 1-4
FIG. 1-5
FIG. 1-6
FIG. 1-7
Inside Air from
*Outside Air from
2 Openings Directly from
Outdoors1
*Outside Air from
2 Ducts Delivered from
Outdoors1
2 Ducts Delivered from Interior Space2
*Outside Air from
1 Opening Directly
from Outdoors, in2
(cm2)1
Model
Number
Different
Stories
Same Story
Top
Opening, in2
(cm2)
Bottom
Opening, in2
(cm2)
Top
Opening, in2
(cm2)
Bottom
Opening, in2
(cm2)
Top
Opening, in2
(cm2)
Bottom
Total
Opening, in2 Opening, in2
(cm2)
(cm2)
375
(2420)
500
(3226)
625
(4033)
375
(2420)
500
(3226)
625
(4033)
750
(4839)
1000
(6452)
1250
(8065)
750
(4839)
1000
(6452)
1250
(8065)
1500
(9678)
2000
(12904)
2500
(16129)
1500
(9678)
2000
(12904)
2500
(16129)
3000
(19355)
4000
(25807)
5000
(32258)
500
(3226)
667
(4304)
833
(5381)
FB 1500
FB 2000
FB 2500
FB 3000
FB 3500
750
(4839)
875
750
(4839)
875
1500
(9678)
1750
1500
(9678)
1750
3000
(19355)
3500
3000
(19355)
3500
6000
(38710)
7000
1000
(6452)
1167
(5646)
(5646)
(11291)
(11291)
(22581)
(22581)
(45162)
(7530)
The above requirements are for the appliance only; additional gas fired appliances in the equipment room will require an increase
in the net free area and/or volume to supply adequate combustion air for all appliances.
No combustion air openings are needed when the appliance is installed in a space with a volume NO LESS than 50 cubic feet per
3
1,000 Btu/hr of all installed gas fired appliances. Buildings MUST NOT be of *“Tight Construction” .
1
Outside air openings shall directly communicate with the outdoors.
2
Combined interior space must be 50 cubic feet per 1,000 Btu/hr input. Buildings MUST NOT be of *“Tight Construction”.
3
”Tight Construction” is defined as a building with less than 0.40 ACH (air changes per hour). For buildings of “Tight
Construction”, provide air openings into the building from outside.
13
Installation & Operation Manual
2 General venting
Direct venting
Sidewall
Vertical Vent, Sidewall Air
Vertical
Optional room air
Vertical
Sidewall
14
Installation & Operation Manual
2 General venting
(continued)
Install vent and combustion air piping
The Crest must be vented and supplied
with combustion and ventilation air as
Sealing of Type “B” double-wall vent material or galvanized
vent pipe material used for air inlet piping on a sidewall or
vertical rooftop Combustion Air Supply System:
ƽ DANGER
described in this section. Ensure the vent
and air piping and the combustion air
supply comply with these instructions
regarding vent system, air system, and
combustion air quality. See also Section
1 of this manual.
a. Seal all joints and seams of the air inlet pipe using either
Aluminum Foil Duct Tape meeting UL Standard 723 or
181A-P or a high quality UL Listed silicone sealant such
as those manufactured by Dow Corning or General
Electric.
Inspect finished vent and air piping
thoroughly to ensure all are airtight and
comply with the instructions provided
and with all requirements of applicable
codes.
b. Do not install seams of vent pipe on the bottom of
horizontal runs.
c. Secure all joints with a minimum of three sheet metal
screws or pop rivets. Apply Aluminum Foil Duct Tape or
silicone sealant to all screws or rivets installed in the vent
pipe.
Failure to provide a properly installed
vent and air system will cause severe
personal injury or death.
d. Ensure that the air inlet pipes are properly supported.
The PVC, CPVC, or ABS air inlet pipe should be cleaned and
sealed with the pipe manufacturer’s recommended solvents
and standard commercial pipe cement for the material used.
The ABS, PVC, CPVC, Dryer Vent or Flex Duct air inlet pipe
should use a silicone sealant to ensure a proper seal at the
appliance connection and the air inlet cap connection. Dryer
vent or flex duct should use a screw type clamp to seal the
vent to the appliance air inlet and the air inlet cap. Proper
sealing of the air inlet pipe ensures that combustion air will be
free of contaminants and supplied in proper volume.
Air inlet pipe materials:
The air inlet pipe(s) must be sealed. Choose acceptable
combustion air inlet pipe materials from the following list:
ABS, PVC, or CPVC
Dryer Vent or Sealed Flexible Duct (not recommended
for rooftop air inlet)
Galvanized steel vent pipe with joints and seams sealed
as specified in this section.
Type “B” double-wall vent with joints and seams sealed
as specified in this section.
AL29-4C, stainless steel material to be sealed to
specification of its manufacturer.
*Plastic pipe may require an adapter (not provided) to
transition between the air inlet connection on the appliance
and the plastic air inlet pipe.
Using vent or air intake materials other
ƽ WARNING
than those specified, failure to properly
seal all seams and joints or failure to follow
vent pipe manufacturer’s instructions can
result in personal injury, death or property
damage. Mixing of venting materials will
void the warranty and certification of the
appliance.
The use of double-wall vent or insulated
NOTICE
material for the combustion air inlet
pipe is recommended in cold climates
to prevent the condensation of airborne
moisture in the incoming combustion air.
15
Installation & Operation Manual
2 General venting
When a sidewall or vertical rooftop combustion air supply Air intake/vent connections
system is disconnected for any reason, the air inlet pipe must
be resealed to ensure that combustion air will be free of
contaminants and supplied in proper volume.
1. Combustion Air Intake Connector (FIG. 2-1) - Used to
provide combustion air directly to the unit from outdoors.
A fitting is provided with the unit for final connection.
Combustion air piping must be supported per guidelines
listed in the National Mechanical Code, Section 305, Table
305.4 or as local codes dictate.
Failure to properly seal all joints and seams
ƽ DANGER
as required in the air inlet piping may
result in flue gas recirculation, spillage
of flue products and carbon monoxide
emissions causing severe personal injury
or death.
2. Vent Connector (FIG. 2-1) - Used to provide a
passageway for conveying combustion gases to the
outside. A transition fitting is provided on the unit for
final connection. Vent piping must be supported per the
National Building Code, Section 305, Table 305.4 or as
local codes dictate.
Vent and air piping
This product has been approved for use with stainless steel
vent systems.
Figure 2-1 Combustion Air Adapter
Use only the materials, vent systems, and
ƽ WARNING
terminations listed in Table 2A. DO
NOT mix vent systems of different types
or manufacturers, unless listed in this
manual. Failure to comply could result
in severe personal injury, death, or
substantial property damage.
AIR PIPE
(FIELD SUPPLIED)
ADAPTER
GASKET
SHIPPED LOOSE
WITH THE BOILER
Installations must comply with applicable
NOTICE
national, state, and local codes. Stainless
steel vent systems must be listed as a
UL-1738 approved system for the United
States and a ULC-S636 approved system
for Canada.
Installation of a stainless steel vent system
NOTICE
should adhere to the stainless steel vent
manufacturer’s installation instructions
supplied with the vent system.
VENT PIPE
(FIELD SUPPLIED)
The Crest is supplied with an integral
NOTICE
FasNSeal vent connector (FIG. 2-1). The
installer must use a specific vent starter
adapter supplied by the vent manufacturer
to adapt to different vent systems.
CONNECTOR
The Crest uses model specific combustion air intake and vent
piping sizes as detailed in Tables 2B and 2C on page 17.
Increasing or decreasing combustion air
NOTICE
or vent piping to sizes not specified in this
manual is not authorized.
Table 2A Approved Stainless Steel Vent Manufacturers
Approved Stainless Steel Vent Manufacturers
Make
Model
FasNSeal Vent
ProTech Systems (Simpson Dura-Vent Co.)
Z-Flex (Nova Flex Group)
Heat Fab (Selkirk Corporation)
Metal Fab
Z-Vent
Saf-T Vent
Corr/Guard
Secure Seal SS
eVent
Securities Chimneys International
Schebler Chimney Systems
16
Installation & Operation Manual
2 General venting
(continued)
Table 2B Direct Vent Minimum / Maximum Allowable Air / Vent Lengths
AIR INLET
VENT
Input
Model
De-Rate per
25 feet of Vent
Air Intake
Air Intake
Air Intake
Vent
Vent
Vent
Diameter Min. Length Max. Length Diameter
Min. Length Max. Length
FB 1500
FB 2000
FB 2500
FB 3000
FB 3500
7"
8"
12'
12'
12'
12'
12'
100'
100'
100'
100'
100'
7"
8"
12'
12'
12'
12'
12'
100'
100'
100'
100'
100'
2%
2%
2%
2%
2%
8"
9"
10"
10"
10"
10"
Table 2C Room Air Minimum / Maximum Allowable Air / Vent Lengths
Vent
Diameter
Vent
Min. Length
12'
Vent
Max. Length
Input De-Rate per
25 feet of Vent
Model
FB 1500
FB 2000
FB 2500
FB 3000
FB 3500
7"
8"
100'
100'
100'
100'
100'
1%
1%
12'
9"
12'
12'
12'
1%
1%
1%
10"
10"
When determining equivalent combustion air and vent
length, add 5 feet (1.5m) for each 90° elbow and 3 feet (.9 m)
for each 45° elbow.
Vent, air piping and termination:
The Crest vent and air piping can be installed through the roof
or through a sidewall. Follow the procedures in this manual for
the method chosen. Refer to the information in this manual to
determine acceptable vent and air piping length.
EXAMPLE: 20 feet (6 m) of pipe + (4) 90° elbows + (3) 45°
elbows = 49 equivalent feet (15 m) of piping.
Air contamination
Removing from existing vent
Pool and laundry products and common household and hobby
products often contain fluorine or chlorine compounds. When
these chemicals pass through the boiler, they can form strong
acids. The acid can eat through the boiler wall, causing serious
damage and presenting a possible threat of flue gas spillage or
boiler water leakage into the building.
Follow the instructions in Section 1, page 10 of this manual
when removing a boiler from an existing vent system.
Vent and air piping
Vent and air system:
Please read the information given in Table 1A, page 9,
listing contaminants and areas likely to contain them. If
contaminating chemicals will be present near the location of the
boiler combustion air inlet, have your installer pipe the boiler
combustion air and vent to another location, per this manual.
Installation must comply with local
requirements and with the National Fuel
Gas Code, NFPA 54 / ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.
NOTICE
If the boiler combustion air inlet is located
in a laundry room or pool facility, for
example, these areas will always contain
hazardous contaminants.
You must also install air piping from outside to the boiler
air intake adapter. The resultant installation is direct vent
(sealed combustion).
ƽ WARNING
You may use any of the vent/air piping methods covered in
this manual. Do not attempt to install the Crest using any
other means.
To prevent the potential of severe personal
injury or death, check for areas and products
listed in Table 1A, page 9 before installing
the boiler or air inlet piping.
ƽ WARNING
DO NOT mix components from different
ƽ WARNING
systems. The vent system could fail,
If contaminants are found, you MUST:
• Remove products permanently.
—OR—
causing leakage of flue products into the
living space. Use only approved stainless
steel pipe and fittings.
• Relocate air inlet and vent
terminations to other areas.
17
Installation & Operation Manual
2 General venting
Common venting
Table 2D Flue Damper Kits
Crest boilers may be common vented; however, the following
criteria MUST BE followed:
Flue Damper Kits
1. Only Crest boilers may be connected to the common
vent. DO NOT mix other manufacturer’s appliances or
other Lochinvar models.
Model
FB1500
FB2000
FB2500
FB3000
FB3500
Damper Size
Kit Number
7"
DRH30000
DRH30001
DRH30002
DRH30003
DRH30003
2. Crest boilers connected to the common vent must all be
of the same size.
8"
9"
3. Each Crest boiler must have a Lochinvar supplied flue
damper installed (see Table 2D).
10"
10"
4. Only vertical venting may be used when common venting
Crest boilers. Sidewall venting is not allowed.
5. Crest boilers in a common vent must be connected and
controlled with the integral Crest SMART TOUCH
Cascade.
a. The Leader may be controlled through the Crest
SMART TOUCH control through BMS (external
0 - 10V signal), ModBus or its own internally
calculated set point.
b. The Cascade (Members) must be controlled by the
Crest Leader boiler using the efficiency optimized
Cascade.
For approved common vent sizing, contact the factory.
When Crest boilers are common vented,
ƽ WARNING
the criteria above MUST BE followed.
Failure to follow all these requirements
will result in severe personal injury, death,
or substantial property damage.
18
Installation & Operation Manual
3 Vertical direct venting
Vent/air termination – vertical
Follow instructions below when determining
vent location to avoid possibility of severe
personal injury, death or substantial property
damage.
ƽ WARNING
Figure 3-2 Vertical Termination of Air and Vent w/Rain
Cap
Do not connect any other appliance to the
ƽ WARNING
vent pipe or multiple boilers to a common
BIRD SCREEN
[TYPICAL]
vent pipe except as noted in Section 2 on
page 18. Failure to comply could result in
severe personal injury, death, or substantial
property damage.
VENT OUTLET
36" [914 MM] MINIMUM
ABOVE AIR INLET
12" [305 MM] MINIMUM
ABOVE ROOF /
SNOW LINE
Installation must comply with local
NOTICE
requirements and with the National Fuel
Gas Code, NFPA 54 / ANSI Z223.1 - latest
edition for U.S. installations or CSA B149.1
Installation Code for Canadian installations.
Determine location
Locate the vent/air terminations using the following guidelines:
5. Locate terminations so they are not likely to be damaged
by foreign objects, such as stones or balls, or subject to
buildup of leaves or sediment.
1. The total length of piping for vent or air must not exceed
the limits given in the General Venting Section on page 17
of this manual.
2. The vent must terminate at least 3 feet above the highest
place in which the vent penetrates the roof and at least 2 feet
above any part of a building within 10 horizontal feet.
3. The air piping must terminate in a down-turned 180°
return pipe no further than 2 feet (.6 m) from the center of
the vent pipe. This placement avoids recirculation of flue
products into the combustion air stream.
4. The vent piping must terminate in an up-turned coupling
as shown in FIG. 3-1. The top of the coupling or the rain
cap must be at least 36" (914 mm) above the air intake. The
air inlet pipe and vent pipe can be located in any desired
position on the roof, but must always be no further than 2
feet (.6 m) apart and with the vent termination at least 36"
(914 mm) above the air intake.
Prepare roof penetrations
1. Air pipe penetration:
a. Cut a hole for the air pipe. Size the air pipe hole as
close as desired to the air pipe outside diameter.
2. Vent pipe penetration:
a. Cut a hole for the vent pipe. For either combustible
or noncombustible construction, size the vent pipe
hole per the vent manufacturer’s instructions.
b. Insert a galvanized metal thimble in the vent pipe
hole (when required by local codes).
3. Space the air and vent holes to provide the minimum
spacing shown in FIG. 3-1.
4. Follow all local codes for isolation of vent pipe when
passing through floors, ceilings, and roofs.
Rooftop vent and air inlet terminations
ƽ WARNING
5. Provide flashing and sealing boots sized for the vent pipe
and air pipe.
must terminate in the same pressure zone,
unless vertical vent sidewall air is set up as
shown in the General Venting - Vertical
Vent, Sidewall Air Section.
Termination and fittings
1. Prepare the vent termination coupling and the air
termination elbow (FIG. 3-1) by inserting bird screens.
Bird screens should be obtained locally.
Figure 3-1 Vertical Termination of Air and Vent
BIRD SCREEN
[TYPICAL]
2. The air piping must terminate in a down-turned 180°
return bend as shown in FIG. 3-1. Locate the air inlet
pipe no further than 2 feet (.6 m) from the center of the
vent pipe. This placement avoids recirculation of flue
products into the combustion air stream.
VENT
VENT OUTLET
36" MINIMUM
12" [305 MM] MINIMUM
ABOVE AIR INLET
ABOVE ROOF /
SNOW LINE
COMBUSTION AIR
19
Installation & Operation Manual
3 Vertical direct venting
3. The vent piping must terminate in an up-turned coupling
as shown in FIG. 3-1. The top of the coupling or the
rain cap must be at least 36" (914 mm) above the air
intake. The air inlet pipe and vent pipe can be located
in any desired position on the roof, but must always be
no further than 2 feet (.6 m) apart and with the vent
termination at least 36" (914 mm) above the air intake.
Figure 3-4 Alternate Vertical Terminations with Multiple
Boilers
4. Maintain the required dimensions of the finished
termination piping as shown in FIG. 3-1.
5. Do not extend exposed vent pipe outside of building
more than shown in this document. Condensate could
freeze and block vent pipe.
36” (914 MM)
12”
(305 MM)
Multiple vent/air terminations
36” (914 MM)
1. When terminating multiple Crest boilers, terminate
each vent/air connection as described in this manual
(FIG. 3-3).
12”
(305 MM)
Terminate all vent pipes at the same height
ƽ WARNING
and all air pipes at the same height to
avoid recirculation of flue products and
the possibility of severe personal injury,
death, or substantial property damage.
2. Place roof penetrations to obtain minimum clearance of
12 inches (305 mm) between edge of air intake elbow and
adjacent vent pipe of another boiler for U.S. installations
(see FIG. 3-3). For Canadian installations, provide
clearances required by CSA B149.1 Installation Code.
3. The air inlet of a Crest boiler is part of a direct vent
connection. It is not classified as a forced air intake with
regard to spacing from adjacent boiler vents.
Figure 3-3 Vertical Terminations with Multiple Boilers
36” (914 MM)
12”
(305 MM)
12”
(305 MM)
12”
(305 MM)
36” (914 MM)
12”
(305 MM)
12”
(305 MM)
12”
(305 MM)
20
Installation & Operation Manual
4 Sidewall direct venting
Vent/air termination – sidewall
Follow instructions below when
determining vent location to avoid
possibility of severe personal injury, death,
or substantial property damage.
Sidewall vent and air inlet terminations
must terminate in the same pressure
zone.
ƽ WARNING
ƽ WARNING
f. Do not terminate above any door or above or
below any window. Condensate can freeze, causing
ice formations.
A gas vent extending through an exterior
ƽ WARNING
wall shall not terminate adjacent to a wall
g. Locate or guard vent to prevent condensate
damage to exterior finishes.
or below building extensions such as eaves,
parapets, balconies, or decks. Failure to
comply could result in severe personal
injury, death, or substantial property
damage.
Figure 4-1 Sidewall Termination of Air and Vent
PVC/CPVC or ABS is acceptable air inlet pipe material.
NOTICE
Do not connect any other appliance to the
ƽ WARNING
vent pipe or multiple boilers to a common
vent pipe except as noted in Section 2
on page 18. Failure to comply could
result in severe personal injury, death, or
substantial property damage.
FROM BOILER VENT
PIPE CONNECTION
Sidewall venting commercial products will
ƽ CAUTION
36" MIN
48" MAX
result in large exhaust plumes in cold
climates. Consideration should be taken
when locating in proximity to windows,
doors, walkways, etc.
TO BOILER INTAKE
AIR CONNECTION
12" MIN
Installation must comply with local
NOTICE
requirements and with the National Fuel
Gas Code, NFPA 54 / ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.
GRADE OR
SNOW LINE
3. Maintain clearances as shown in FIG.’s 4-1 thru 4-3,
pages 21 and 22. The vent termination should not be
located in traffic areas such as walkways, adjacent
buildings, operable windows, or doors. Also maintain
the following:
Determine location
Locate the vent/air terminations using the following
guidelines:
a. Vent must terminate:
1. The total length of piping for vent or air must not exceed
the limits given in the General Venting Section on page
17 of this manual.
• At least 6 feet (1.8 m) from adjacent walls.
• Not less than 7 feet (2.1 m) above grade where located
adjacent to public walkways.
2. You must consider the surroundings when terminating
the vent and air:
• No closer than 12 inches (305 mm) below roof
overhang.
a. Position the vent termination where vapors will
not damage nearby shrubs, plants or air
conditioning equipment or be objectionable.
b. The flue products will form a noticeable plume as
they condense in cold air. Avoid areas where the
plume could obstruct window views.
c. Prevailing winds could cause freezing of condensate
and water/ice buildup where flue products impinge
on building surfaces or plants.
• At least 3 feet (.9 m) above any forced air intake
within 10 feet (3 m).
• No closer than 4 feet (1.2 m) horizontally
from any door or window or any other gravity air
inlet.
b. Air inlet must terminate at least 12 inches (305 m)
above grade or snow line; at least 36 inches
(914 mm) below the vent termination.
c. Do not terminate closer than 4 feet (1.2 m)
horizontally from any electric meter, gas meter,
regulator, relief valve, or other equipment. Never
terminate above or below any of these within 4 feet
(1.2 m) horizontally.
d. Avoid possibility of accidental contact of flue
products with people or pets.
e. Do not locate the terminations where wind eddies
could affect performance or cause recirculation,
such as inside building corners, near adjacent
buildings or surfaces, window wells, stairwells,
alcoves, courtyards, or other recessed areas.
4. Locate terminations so they are not likely to be damaged
by foreign objects, such as stones or balls, or subject to
buildup of leaves or sediment.
21
Installation & Operation Manual
4 Sidewall direct venting
Vent/air termination – sidewall
Prepare wall penetrations
Figure 4-2 Clearance to Doors and Windows
1. Air pipe penetration:
a. Cut a hole for the air pipe. Size the air pipe hole as
close as desired to the air pipe outside
diameter.
Vent pipe penetration:
a. Cutaholefortheventpipe. Foreithercombustible
or noncombustible construction, size the vent pipe
hole per the vent manufacturer’s instructions.
2. Install the vent and air intake piping. Seal all gaps
between the pipes and wall with RTV silicone sealant.
3. Seal all wall cavities.
Termination and fittings
1. The air termination must be oriented at least 12 inches
4'
above grade or snow line as shown in FIG. 4-1, page
21.
4'
2. Maintain the required dimensions of the finished
termination piping as shown in FIG. 4-1, page 21.
3. Do not extend exposed vent pipe outside of the
building more than what is shown in this document.
Condensate could freeze and block vent pipe.
Figure 4-3 Clearance to Forced Air Inlets
4. Stainless steel terminations are designed to penetrate
walls with a thickness up to 9.25 inches of standard
construction.
IF LESS THAN 10’
VENT TERMINATION
36” MIN.
Multiple vent/air terminations
1. When terminating multiple Crest boilers terminate
each vent/air connection as described in this manual
(FIG. 4-4).
All vent pipes and air inlets must
ƽ WARNING
terminate at the same height to avoid
possibility of severe personal injury,
death, or substantial property damage.
FORCED AIR
INLET
AIR TERMINATION
Sidewall venting commercial products will
result in large exhaust plumes in cold
climates. Consideration should be taken
when locating in proximity to windows,
doors, walkways, etc.
ƽ CAUTION
22
Installation & Operation Manual
4 Sidewall direct venting
(continued)
2. Place wall penetrations to obtain minimum clearance
of 12 inches (305 mm) between vent pipe and adjacent
air inlet, as shown in FIG. 4-4 for U.S. installations. For
Canadian installations, provide clearances required by
CSA B149.1 Installation Code.
Figure 4-6 Room Air (Direct Exhaust Terminations)
ROOM AIR (DIRECT EXHAUST TERMINATIONS)
Vent Termination
3. The air inlet of a Crest is part of a direct vent
connection. It is not classified as a forced air intake
with regard to spacing from adjacent boiler vents.
23° Elbow
45° Elbow
Figure 4-4 Multiple Vent Terminations (must also
comply with Figure 4-1)
VENT
90° Elbow
Room air
AIR
The Crest boiler may be installed with a single pipe carrying the
flue products to the outside while using combustion air from
the equipment room.
Follow the requirements in the General Venting, Sidewall Direct
Venting, and Vertical Direct Venting sections for vent material
specifications, vent length requirements, and vent termination
requirements.
12"
36" MIN
48" MAX
36"
Install the air inlet cover (shipped loose with the boiler) per
FIG. 4-7. Combustion and ventilation air must be supplied to
the equipment room per the requirements on pages 12 and 13
of this manual for proper operation of the Crest boiler when
utilizing the single pipe method.
12"
12" MIN
Figure 4-5 Direct Vent Terminations
Figure 4-7 Room Air Installation
DIRECT VENT TERMINATIONS
AIR INLET COVER
Air Inlet
Vent Termination
Dryer Inlet
Straight
Mitered
90° Elbow
23° Elbow
23
Installation & Operation Manual
5 Hydronic piping
System water piping methods
General piping information
The Crest is designed to function in a closed loop pressurized Basic steps are listed below along with illustrations on the
system not less than 12 psi (83 kPa). A temperature and following pages, which will guide you through the installation
pressure gauge is included to monitor system pressure and of the Crest (5-2 thru 5-5).
outlet temperature and should be located on the boiler outlet.
1. Connect the system return to the 4" flanged connection
marked “Inlet”, make sure to install with a suitable gasket
It is important to note that the boiler has a pressure drop
between flanges.
which must be figured in when sizing the circulators. Each
boiler installation must have an air elimination device, which
will remove air from the system.
2. Connect the system supply to the 4" flanged connection
marked “Outlet”, make sure to install with a suitable gasket
between flanges.
Install the boiler so the gas ignition system components
3. Install purge and balance valve or shutoff valve and drain
on system return to purge air out of each zone.
are protected from water (dripping, spraying, etc.) during
appliance operation or basic service of circulator replacement,
valves, and others.
4. Install a backflow preventer on the cold feed make-up water
line.
Observe a minimum of 1/4 inch (6 mm) clearance around all
uninsulated hot water pipes when openings around the pipes
are not protected by non-combustible materials.
5. Install a pressure reducing valve on the cold feed make-up
water line, (15 psi (103 kPa) nominal). Check temperature
and pressure gauge, which should read a minimum pressure
of 12 psi (83 kPa).
Low water cutoff device
6. Install the circulators as shown on the piping diagrams in
this section. Make sure the circulators are properly sized
for the system and friction loss. Install check valves with
each boiler circulator.
An electronic low water cutoff is provided as standard
equipment on all models. The low water cutoff should be
inspected every 6 months.
Chilled water system
7. Install an expansion tank on the system supply. Consult the
tank manufacturer’s instruction for specific information
relating to tank installation. Size the expansion tank for the
required system volume and capacity.
If the boiler supplies hot water to heating coils in air handler
units, flow control valves or other devices must be installed to
prevent gravity circulation of heater water in the coils during
the cooling cycle. A chilled water medium must be piped in
parallel with the heater.
8. Install an air elimination device on the system supply.
9. This appliance is supplied with a relief valve sized in
accordance with ASME Boiler and Pressure Vessel Code,
Section IV (“Heating Boilers”). The safety relief valve
is installed at the factory and is located on the rear of
the boiler. Pipe the discharge of the safety relief valve to
prevent injury in the event of pressure relief. Pipe the
discharge to a drain. Provide piping that is the same size as
the safety relief valve outlet. Never block the outlet of the
safety relief valve.
Freeze protection
Freeze protection for new or existing systems must use glycol
that is specially formulated for this purpose. This includes
inhibitors, which prevent the glycol from attacking the
metallic system components. Make certain to check that
the system fluid is correct for the glycol concentration and
inhibitor level. The system should be tested at least once
a year and as recommended by the producer of the glycol
solution. Allowance should be made for the expansion of the
glycol solution in the system piping.
10. On any pre-existing system, it is good practice to install
a field supplied strainer to prevent damage to the heat
exchanger.
Use only inhibited propylene glycol
ƽ WARNING
solutions, which are specifically formulated
See the piping illustrations included in this section, FIG.’s 5-2
thru 5-5 for suggested guidelines in piping the Crest.
for hydronic systems. Ethylene glycol is
toxic and can attack gaskets and seals used
in hydronic systems.
Please note that these illustrations are meant
NOTICE
to show system piping concept only, the
installer is responsible for all equipment and
detailing required by local codes.
24
Installation & Operation Manual
5 Hydronic piping
(continued)
Circulator sizing
The Crest heat exchanger does have a pressure drop, which must be considered in your system design. Refer to the graph in
FIG. 5-1 for pressure drop through the Crest heat exchanger.
Figure 5-1 Pressure Drop vs. Flow
CREST Pressure Drop Curve
Flow Rate (GPM)
Table 5A Sizing Information for Temperature Rise Applications_20°F, 40°F and 60°F
TEMPERATURE RISE APPLICATIONS
20°F
40°F
FT/HD
60°F
BOILER
CONNECTION SIZE
Model
GPM
138
FT/HD
3.4
GPM
69
GPM
FT/HD
1.0
FB 1500
FB 2000
FB 2500
FB 3000
FB 3500
4"
4"
4"
4"
4"
1.5
1.6
1.3
1.2
1.2
46
61
184
4.1
92
1.0
230
4.6
115
138
161
77
0.7
277
5.6
92
0.7
323
7.5
108
0.7
[Based on 92% AHRI Efficiency]
The pressure drop reflected in FIG. 5-1 is
for the boiler only. Additional allowances
must be made for piping, especially if
sizing pumps for Primary/Secondary
applications.
It is required that boiler piping systems
utilize Primary/Secondary or Fixed or
Variable Flow Primary configurations as
shown in FIG.’s 5-2 thru 5-5. The use of
other boiler piping configurations could
result in improper building and system flow
rates leading to inadvertent boiler high limit
shutdowns and poor system performance.
NOTICE
NOTICE
25
Installation & Operation Manual
5 Hydronic piping
Near boiler piping components
A system supply sensor (factory supplied)
MUST BE installed with Primary/Secondary
systems for proper boiler operation.
1. Boiler piping:
NOTICE
Boiler system piping should be sized per the pipe
requirements listed in Tables 5A and 5C.
2. Boiler circulating pump:
10. Y-Strainer:
Field supplied. When using Primary/Secondary piping the
boiler circulating pump should be sized per Table 5A.
Field supplied. A Y-strainer or equivalent multipurpose
strainer is recommended at the inlet of the heat
exchanger to remove system particles from older
hydronic systems and protect newer systems.
3. Hot Water Generator circulating pump:
Field supplied. When installed in a Primary/Secondary
arrangement, the Crest requires an additional pump for
the Hot Water Generator Loop. The pump should
be sized per Table 5A. Consult the indirect water
heater operating guide to determine flow characteristics
for the selected product used. The pump’s total flow and
heat requirements are the sum of the boiler and the indirect
water heater.
The maximum allowable water flow rate
through a single Crest boiler is 350 GPM.
Exceeding this flow rate will result in damage
to the heat exchanger and/or piping.
ƽ CAUTION
Reference Table 5B1 for the minimum
NOTICE
recommended flow rate through a single
Crest boiler at full fire to maintain a 80°F
temperature rise. Reference Table 5B2 for
the absolute minimum flow rate through a
single Crest boiler.
4. Boiler isolation valves:
Field supplied. Full port valves are required. Failure
to use full port valves could result in a restricted flow
rate through the boiler.
Table 5B1 Minimum Flow Rate with the Boiler at Full Fire
5. Check valves:
TEMPERATURE RISE APPLICATIONS
Field supplied. Check valves are required for
installation as shown in FIG.’s 5-2 and 5-3. Failure to
install check valves could result in a reverse flow
condition during pump(s) off cycle.
MODEL
FLOW RATE (GPM)
FB(N,L)1500
FB(N,L)2000
FB(N,L)2500
FB(N,L)3000
FB(N,L)3500
35
46
58
70
81
6. Domestic indirect hot water isolation valves:
Field supplied. Full port valves are required. Failure to use
full port valves could result in a restricted flow rate through
the boiler.
7. Anti-scald mixing valve:
[Based on 80°F Temperature Rise]
Field supplied.
An anti-scald mixing valve is
recommended when storing domestic hot water above
115°F (46°C).
Table 5B2 Absolute Minimum Flow Rate
8. Pressure relief valve:
ABSOLUTE MINIMUM FLOW RATE
Factory supplied. The pressure relief valve is sized to
ASME specifications.
MODEL
FLOW RATE (GPM)
9. System temperature sensor:
FB(N,L)1500
FB(N,L)2000
FB(N,L)2500
FB(N,L)3000
FB(N,L)3500
25
25
25
25
45
Lochinvar supplies
a
system temperature sensor.
The sensor is to be installed in the heating loop
downstream from the boiler hot water piping and
heating loop junction.
The sensor should be
located far enough downstream to sense system diluted
water temperature.
26
Installation & Operation Manual
5 Hydronic piping
(continued)
Figure 5-2 Single Boiler - Recommended - Primary / Secondary Piping with a Hot Water Generator
FROM SYSTEM
SYSTEM RETURN
SENSOR
12"
MAX
BALL VALVE
RELIEF
VALVE
HOT WATER
GENERATOR
(TYPICAL)
AIR SEPERATOR
DRAIN PORT
(TYPICAL)
SYSTEM SUPPLY
SENSOR
SYSTEM
CIRCULATOR
TO SYSTEM
BOILER
DRAIN
PRESSURE
REDUCING VALVE
MAKE UP
WATER
BACK FLOW
PREVENTER
WATER
PRESSURE
GAUGE
EXPANSION
TANK
GENERATOR
CIRCULATOR
Y-STRAINER
(RECOMMENDED)
FLOW CHECK
VALVE (TYPICAL)
BOILER PUMP
System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in
operation to prevent short cycling and high limit issues.
NOTICE
NOTICE
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.
27
Installation & Operation Manual
5 Hydronic piping
Table 5C Multiple Boilers - Common Header - Primary / Secondary Flow
Number of Units
2
3
4
5
6
7
8
Model
Recommended Common Header Pipe Sizes in Inches
FB 1500
FB 2000
FB 2500
FB 3000
FB 3500
4
4
5
5
5
4
5
5
6
6
5
5
6
7
7
5
6
7
7
8
6
7
7
8
6
7
8
10
10
7
8
10
10
10
10
[Based on a boiler ΔT of 30°F.]
A system supply sensor (factory supplied) MUST BE installed for proper boiler operation.
NOTICE
Figure 5-3 Multiple Boilers - Common Header - Recommended - Primary / Secondary Flow
FROM SYSTEM
SYSTEM RETURN
SENSOR
BALL VALVE
(TYPICAL)
AIR SEPARATOR
RELIEF
VALVE
DRAIN PORT
(TYPICAL)
HOT WATER
GENERATOR
SYSTEM SUPPLY
SENSOR
SYSTEM
CIRCULATOR
TO SYSTEM
MAKE UP
WATER
BACK FLOW
PREVENTER
WATER
PRESSURE
GENERATOR
CIRCULATOR
REDUCING VALVE
BOILER DRAIN
(TYPICAL)
PRESSURE
GAUGE
EXPANSION
TANK
Y-STRAINER
(RECOMMENDED)
BOILER PUMP
(TYPICAL)
FLOW CHECK
VALVE (TYPICAL)
System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in
operation to prevent short cycling and high limit issues.
NOTICE
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.
NOTICE
28
Installation & Operation Manual
5 Hydronic piping
(continued)
Figure 5-4 Single Boiler - Alternate - Fixed or Variable Flow Primary System Piping
RELIEF
VALVE
BALL VALVE
(TYPICAL)
FROM SYSTEM
AIR SEPERATOR
BOILER DRAIN
DRAIN PORT
(TYPICAL)
SYSTEM
CIRCULATOR
Y-STRAINER
(RECOMMENDED)
EXPANSION
TANK
TO SYSTEM
PRESSURE
PRESSURE
GAUGE
REDUCING VALVE
BACK FLOW
PREVENTER
MAKE UP
WATER
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.
NOTICE
29
Installation & Operation Manual
5 Hydronic piping
Figure 5-5 Multiple Boilers - Alternate - Common Header - Fixed or Variable Flow Primary
RELIEF
VALVE
(TYPICAL)
BALL VALVE
(TYPICAL)
FROM SYSTEM
BOILER DRAIN
(TYPICAL)
SYSTEM RETURN
AIR SEPERATOR
SENSOR
DRAIN PORT
(TYPICAL)
SYSTEM SUPPLY
SENSOR
SYSTEM
CIRCULATOR
Y-STRAINER
(RECOMMENDED)
(TYPICAL)
TO SYSTEM
EXPANSION
TANK
PRESSURE
GAUGE
MAKE UP
WATER
BACK FLOW
PREVENTER
PRESSURE
REDUCING VALVE
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.
NOTICE
NOTICE
When installing multiple Crest boilers in fixed or variable flow primary applications, utilize a reverse-return
or other piping method to ensure balanced flow through each boiler.
30
Installation & Operation Manual
6 Gas connections
Connecting gas supply piping
3. Purge all air from the gas supply piping.
For dual fuel models, reference the Crest
NOTICE
Dual Fuel Supplemental Manual.
4. Before placing the boiler in operation, check the boiler
and its gas connection for leaks.
1. Refer to FIG. 6-1 to pipe gas to the boiler.
a. Install ground joint union for servicing, when
required.
a. The appliance must be disconnected from the gas
supply piping system during any pressure testing of
that system at a test pressure in excess of 1/2 PSIG
(3.5 kPa).
b. In Canada – When using manual main shutoff
valves, it must be identified by the installer.
b. The appliance must be isolated from the gas supply
piping system by closing a manual shutoff valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 PSIG
(3.5 kPa).
Figure 6-1 Gas Supply Piping
GAS SUPPLY
c. The appliance and its gas connection must be leak
tested before placing it in operation.
Do not check for gas leaks with an open
ƽ WARNING
flame – use the bubble test. Failure to
use the bubble test or check for gas leaks
can cause severe personal injury, death, or
substantial property damage.
UNION
(FACTORY SUPPLIED)
MANUAL SHUTOFF
VALVE
(FACTORY SUPPLIED)
5. Use pipe sealing compound compatible with propane
gases. Apply sparingly only to male threads of the pipe
joints so that pipe dope does not block gas flow.
Failure to apply pipe sealing compound as
ƽ WARNING
SEDIMENT TRAP /
DRIP LEG CLEAN OUT
(FACTORY SUPPLIED)
detailed in this manual can result in severe
personal injury, death, or substantial
property damage.
Table 6A Gas Inlet Size
Model
FB1500
FB2000
FB2500
FB3000
FB3500
Gas Inlet Size
1 1/2"
1 1/2"
2"
2. Support piping with hangers, not by the boiler or its
accessories.
The gas valve and blower will not support
the weight of the piping. Do not attempt
ƽ WARNING
to support the weight of the piping with
the boiler or its accessories. Failure to
comply could result in severe personal
injury, death, or substantial property
damage.
2"
2"
31
Installation & Operation Manual
6 Gas connections
Natural gas supply pressure requirements
Use two wrenches when tightening gas
ƽ WARNING
piping at boiler (FIG. 6-2), using one
wrench to prevent the boiler gas line
connection from turning. Failure to
support the boiler gas connection pipe
to prevent it from turning could damage
gas line components.
1. Pressure required at the gas valve inlet pressure port:
• Maximum 14 inches w.c. (3.5 kPa) with no flow
(lockup) or with boiler on.
• Minimum 4 inches w.c. (.99 kPa) with gas flowing (verify
during boiler startup).
2. Install 100% lockup gas pressure regulator in supply line
if inlet pressure can exceed 14 inches w.c. (3.5 kPa) at any
time. Adjust lockup regulator for 14 inches w.c. (3.5 kPa)
maximum.
Figure 6-2 Inlet Pipe with Backup Wrench
Ensure that the high gas pressure regulator
is at least 10 feet (3 m) upstream of the
appliance.
ƽ WARNING
Propane Gas:
Check boiler rating plate to determine which
fuel the boiler is set for. Crest boilers CAN
ƽ WARNING
NOT be field converted. Failure to comply
could result in severe personal injury, death,
or substantial property damage.
Pipe sizing for propane gas
1. Contact gas supplier to size pipes, tanks, and 100% lockup
gas pressure regulator.
Propane Supply Pressure Requirements
USE BACK UP WRENCH TO PREVENT
PIPE FROM ROTATING
1. Adjust propane supply regulator provided by the gas
supplier for 14 inches w.c. (3.5 kPa) maximum pressure.
Maximum inlet gas pressure must not
NOTICE
2. Pressure required at gas valve inlet pressure port:
• Maximum 14 inches w.c. (3.5 kPa)with no flow (lockup)
or with boiler on.
exceed the value specified. Minimum
value listed is for the purposes of input
adjustment.
• Minimum 4 inches w.c. (.99 kPa) with gas flowing (verify
during boiler startup).
Natural gas:
Check boiler rating plate to determine
Ensure that the high gas pressure regulator
is at least 10 feet (3 m) upstream of the
appliance (FIG. 6-3).
ƽ WARNING
ƽ WARNING
which fuel the boiler is set for. Crest
boilers CANNOT be field converted.
Failure to comply could result in severe
personal injury, death, or substantial
property damage.
Figure 6-3 Gas Supply Piping to Regulator
10'
* GAS PRESSURE
MINIMUM
REGULATOR
(FIELD SUPPLIED)
Pipe sizing for natural gas
* MANUAL SHUT
OFF VALVE
1. Refer to Table 6B for pipe length and diameter. Based on
rated boiler input (divide by 1,000 to obtain cubic feet per
hour).
(FIELD SUPPLIED)
a. Table 6B is only for natural gas with specific gravity
0.60 inches, with a pressure drop through the gas
piping of 0.5 inches w.c.
b. For additional gas pipe sizing information, refer to
the National Fuel Gas Code, NFPA 54 / ANSI Z223.1
- latest edition, or in Canada CSA B149.1 Installation
Code.
* REQUIRED FOR INSTALLATION
IN THE COMMONWEALTH OF
MASSACHUSETTS
32
Installation & Operation Manual
6 Gas connections
(continued)
Table 6B Natural Gas Pipe Size Chart
TABLE - 6B
GAS PIPING SIZE CHART
Maximum
Capacity of Pipe
in Thousands
of Btu/hr for
gas pressures of
14 Inches Water
Column (0.5
PSIG) or less and
a pressure drop
of 0.5 Inch Water
Column (Based
on NAT GAS,
Nominal
Iron Pipe
Size
Length of Pipe in Straight Feet
Inches
10
20
30
40
50
60
70
80
90
100 125 150 175 200
1½
2
2,150 1,500 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
4,100 2,820 2,260 1,950 1,720 1,560 N/A N/A N/A N/A N/A N/A N/A
6,460 4,460 3,610 3,100 2,720 2,460 2,310 2,100 2,000 1,900 1,700 1,540 N/A
N/A
N/A
N/A
2½
3
1025 Btu/hr per
Cubic Foot of
Gas and 0.60
11,200 7,900 6,400 5,400 4,870 4,410 4,000 3,800 3,540 3,300 3,000 2,720 2,500 2,340
23,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690 7,380 6,870 6,150 5,640 5,130 4,720
Specific Gravity)
4
Check inlet gas supply
4. Slowly turn on the gas supply at the factory installed
manual gas valve.
DO NOT adjust or attempt to measure gas
ƽ WARNING
valve outlet pressure. Attempting to alter
or measure the gas valve outlet pressure
could result in damage to the valve, causing
potential severe personal injury, death, or
substantial property damage.
5. Turn the power switch to the “ON” position.
6. Adjust the temperature set point on the control panel of
the SMART TOUCH control module to call for heat or
utilize Service Mode, see page 44 of this manual.
The gas piping must be sized for the proper flow and length of
pipe, to avoid excessive pressure drop. Both the gas meter and
the gas regulator must be properly sized for the total gas load.
7. Observe the gas supply pressure as the burner fires at
100% of rated input. Percent of burner input will be
displayed on the Modulation Screen.
8. Ensure inlet pressure is within specified range.
Minimum and maximum gas supply pressures are
specified in this section of the manual.
If you experience a pressure drop greater than 1 inch w.c.
(249 Pa), the meter, regulator, or gas line is undersized or in
need of service. Perform the steps below when checking inlet
gas supply:
9. If gas supply pressure is within normal range and no
adjustments are needed, proceed on to Step 11.
1. Turn the main power switch to the “OFF” position.
10. If the gas pressure is out of range, contact the gas utility,
gas supplier, qualified installer or service agency to
determine the necessary steps to provide proper gas
pressure to the control.
2. Shut off gas supply at the manual gas valve in the gas
piping to the appliance.
3. Remove the 1/8" pipe plug on the flange to the factory
supplied gas shutoff valve and install a suitable 1/8"
fitting (field supplied) for the manometer tubing. Place the
tubing of the manometer over the tap once the 1/8"
fitting is installed as shown in FIG. 6-4.
11. Turn the power switch to the “OFF” position.
12. Shut off the gas supply at the manual gas valve in the gas
piping to the appliance.
13. Remove the manometer from the pressure tap on top of
the gas valve. Remove the 1/8" (3 mm) field supplied
fitting and reinstall the pipe plug removed in Step 3.
33
Installation & Operation Manual
6 Gas connections
Do not check for gas leaks with an open
Gas Pressure
ƽ WARNING
flame -- use the bubble test. Failure to
use the bubble test or check for gas leaks
can cause severe personal injury, death, or
substantial property damage.
The gas pressure must remain between 4 inches w.c.
(.99 kPa) minimum and 14 inches w.c. (3.5 kPa)
maximum for Natural gas and between 4 inches w.c.
(.99 kPa) minimum and 14 inches w.c. (3.5 kPa)
maximum for LP gas during standby (static) mode
and while in operating (dynamic) mode. If an in-line
regulator is used, it must be a minimum of 10 feet
(3 m) from the Crest boiler. It is very important that
the gas line is properly purged by the gas supplier or
utility company. Failure to properly purge the lines or
improper line sizing, will result in ignition failure.
14. Turn on the gas supply at the manual gas valve.
15. Turn the power switch to the “ON” position.
16. Adjust the temperature set point on the control panel of
the SMART TOUCH control module to the desired
water temperature so the appliance will call for heat.
17. Check burner performance by cycling the system while
you observe burner response. The burner should ignite
promptly. Flame pattern should be stable. Turn system
off and allow burner to cool, then cycle burner again to
ensure proper ignition and flame characteristics.
Ignition problems are especially noticeable in NEW LP
installations and also in empty tank situations. This can
also occur when a utility company shuts off service to an
area to provide maintenance to their lines.
Figure 6-4 Inlet Gas Supply Check
Gas valve replacement
The gas valve MUST NOT be replaced with a
conventional gas valve under any circumstances. As
an additional safety feature, the gas valves have flanged
connections to the venturis and blowers.
Failure to follow all precautions
ƽ WARNING
could result in fire, explosion, or
death!
DO NOT adjust or attempt to
ƽ WARNING
measure gas valve outlet pressure.
Attempting to alter or measure the
gas valve outlet pressure could result
in damage to the valve, causing
potential severe personal injury,
death, or substantial property
damage.
34
Installation & Operation Manual
7 Field wiring
ELECTRICAL SHOCK HAZARD – For
Installation must comply with:
ƽ WARNING
your safety, turn off electrical power supply
before making any electrical connections
to avoid possible electric shock hazard.
Failure to do so can cause severe personal
injury or death.
1. National Electrical Code and any other national, state,
provincial, or local codes, or regulations.
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1, and
any local codes.
Wiring must be N.E.C. Class 1.
NOTICE
Line voltage connections
1. Connect 120 VAC power wiring to the line voltage terminal
If original wiring as supplied with boiler
must be replaced, use only type 105°C
wire or equivalent.
strip in the junction box, as shown in FIG. 7-1.
2. Provide and install a fused disconnect or service switch
sized per the boiler amp draw (shown on the boiler rating
plate) as required by the code (see FIG. 7-1).
Boiler must be electrically grounded as
required by National Electrical Code
ANSI/NFPA 70 – latest edition.
3. When connecting the boiler, system and hot water generator
pumps connect the wiring to the line voltage terminal strip
as shown in FIG. 7-1. Maximum current is 1.5 amps.
Install a field supplied contactor between the pump(s) and
the boiler connections.
Label all wires prior to disconnection when
servicing controls. Wiring errors can
cause improper and dangerous operation.
ƽ CAUTION
4. For alternate voltages, consult factory.
Figure 7-1 Boiler Line Voltage Field Wiring Connections
NEUTRAL W
GROUND G
LINE BK
SERVICE SWITCH
SYSTEM PUMP
DRY CONTACT
BOILER PUMP
DRY CONTACT
HWG PUMP
DRY CONTACT
CONTACTOR
(FIELD SUPPLIED)
35
Installation & Operation Manual
7 Field wiring
Low voltage connections
ModBus
The RS-485 ModBus cable is connected to the ModBus
terminals. Use shielded, 2-wire twisted pair cable. If desired,
the shield can be connected to ground by installing a jumper
wire between terminals 1 and 3 on connector X5 on the
ModBus interface module.
1. Route all low voltage wires through the knockouts in the
rear of the boiler, as shown in FIG. 7-2.
2. Connect low voltage wiring to low voltage connection
board as shown in FIG. 7-3 on page 38 of this manual and
the boiler wiring diagram.
Hot Water Generator (HWG)
thermostat
1. Connect the HWG tank thermostat to the Tank
Thermostat terminals on the connection board
(FIG. 7-3).
Figure 7-2 Routing Field Wiring
Hot Water Generator (HWG) tank
sensor
LOW VOLTAGE
WIRING KNOCKOUTS
LINE VOLTAGE
WIRING KNOCKOUTS
1. By installing a HWG tank sensor, the SMART TOUCH
control can perform the tank thermostat function. The
SMART TOUCH control automatically detects the
presence of this sensor, and generates a HWG call for heat
when the tank temperature drops 6°F (3°C) below the
tank set point, and finishes the call for heat when the tank
temperature reaches the tank set point.
LOW VOLTAGE
J-BOX
LINE VOLTAGE
J-BOX
Enable
1. Connect the room thermostat or boiler enable contacts
(isolated contact only) to terminals 7 and 8, as shown in
FIG. 7-3.
2. A TST20015 sensor MUST be used with any indirect tank.
Failure to use the correct sensor will result in the tank
temperature being either above or below the set point.
Connect the correct sensor to the Tank Sensor terminals
(see FIG. 7-3).
2. If a thermostat is used, install the thermostat on the inside
wall away from influences of drafts, hot or cold water
pipes, lighting fixtures, television, sunlight, or fireplaces.
Louver relay
If louvers need to operate before the boiler fires, they can be
controlled by this output. Connect these terminals to a 24V
relay coil, which is wired to operate the louvers (FIG. 7-3).
3. Thermostat anticipator (if applicable):
a. If connected directly to boiler, set for 0.1 amps.
b. If connected to relays or other devices, set to match
total electrical power requirements of connected
devices. See device manufacturers’ specifications
and thermostat instructions for details.
Louver proving switch
Louvers are used to provide combustion air for the room air
option. A louver proving switch should be connected to the
appropriate terminals and are verified prior to operation (see
FIG. 7-3).
Outdoor temperature sensor
1. Connect the outdoor temperature sensor (FIG. 7-3) to
the Outdoor Sensor terminals on the connection board to
enable outdoor reset operation of the Crest.
Boiler pump speed output
This 0 - 10V output is available to control the speed of a
variable speed boiler pump. The SMART TOUCH control will
vary the speed of this pump in order to maintain a minimum
T (set by the installer, see the Crest Service Manual) across
the heat exchanger, as well as prevent high limit lockouts when
the flow in the primary loop is extremely low. Connect this
output to the 0 - 10V input on the boiler pump speed control.
2. Mount the sensor on an exterior wall, shielded from direct
sunlight or flow of heat or cooling from other sources.
3. Route sensor wires through a knockout at the rear of the
boiler (see FIG. 7-2).
Variable speed system pump
A system supply sensor must be installed
for this feature to work.
If a variable speed pump is used in the primary loop, and
a 0-10V signal is available from the pump speed control,
this signal can be used by the SMART TOUCH control to
anticipate changes in the building heat load. By connecting
this 0 - 10V signal to the 0 - 10V SYS PUMP IN terminals, the
boiler (or cascade) can modulate up and down as the primary
flow increases and decreases.
NOTICE
Rate output
This output provides a 0 - 10V signal that is proportional to
the firing rate of the boiler. This may be used by a BMS system
to monitor the actual rate of the boiler.
36
Installation & Operation Manual
7 Field wiring
(continued)
Auxiliary switch 1 & 2
Wiring of the cascade
Additional field supplied limit controls may be connected to
the auxiliary switch inputs. If additional limit controls fail or
open, it will result in a manual reset lockout.
When wiring the boilers for Cascade operation, select one boiler
as the Leader boiler. The remaining boilers will be designated
as Members. See page 45 “Configuration of the Cascade” for a
detailed explanation of this procedure.
System supply sensor
1. By installing the system supply sensor into the supply
of the primary loop, the temperature of the system
supply can be controlled. The SMART TOUCH control
automatically detects the presence of this sensor, and
controls the boiler firing rate to maintain the system
supply temperature to the set point.
Connect the system supply sensor, system return sensor and
outdoor air sensor (if used) to the Leader boiler.
Unless a firing rate is being provided by a
NOTICE
BMS system, a system supply sensor (factory
supplied) MUST BE installed with Primary/
Secondary piping systems for proper boiler
operation.
DO NOT INSTALL THE SYSTEM
SUPPLY SENSOR INTO THE SYSTEM
RETURN.
NOTICE
The location of the system supply sensor should be downstream
of the boiler connections in the main system loop (FIG.’s 5-5
and 5-6). The system supply sensor should be wired to the Low
Voltage Connection Board at the terminals marked for the
system supply sensor (see FIG. 7-3). The Leader control will use
the water temperature at the system supply sensor to control the
operation of the Cascade.
2. For system supply sensor wiring information reference
(FIG. 7-3).
Unless a firing rate is being provided by
a BMS system, a system supply sensor
NOTICE
(factory supplied) MUST BE installed
with Primary/Secondary piping systems
for proper boiler operation.
If outdoor air reset is desired, the outdoor air sensor should be
wired to the Low Voltage Connection Board at the terminals
marked for the outdoor air sensor on the Leader boiler
(FIG. 7-3). If the outdoor air sensor is connected, the Leader
control will calculate the water temperature set point based
on the programmed reset curve parameters. If the outdoor air
sensor is not connected, the Leader control will maintain the
fixed water temperature set point that is programmed into the
control.
Boiler management system
1. An external control may be connected to control either
the firing rate or the set point of the boiler. Connect the
0 - 10 VDC terminals to the 0 - 10 VDC output of the
external control. The SMART TOUCH control can be
enabled using the Enable output (see page 38) or using
the voltage applied to the 0 - 10 VDC input. Reference
the Crest Service Manual for more details.
If a Thermostat enable output is available, it should be wired
to the Low Voltage Connection Board on the Leader boiler at
the terminals marked Enable (FIG. 7-3). If the boilers are to
run continuously, connect a jumper wire between the 7 and 8
terminals at the Enable input. This will initiate a call for heat on
the Cascade. If the SMART TOUCH control is being controlled
by a Boiler Management System (BMS), a call for heat may be
initiated by the voltage applied to the BMS 0 - 10 VDC input
instead.
2. Make sure terminal #34 on the Low Voltage Connection
Board is connected to the (-) or COM output terminal
of the external control, and 0 - 10 VDC terminal #33 is
connected to the 0 - 10 VDC terminal of the external
control.
Runtime contacts
The SMART TOUCH control closes a set of dry contacts
whenever the burner is running. This is typically used by
Building Management Systems to verify that the boiler is
responding to a call for heat.
Communication between the Leader boiler and the Member
boilers is accomplished by using shielded, 2-wire twisted pair
communication cable. Connect one of the twisted pair wires
to Cascade terminal A on each of the Low Voltage Connection
boards, and the other wire of the twisted pair to Cascade
terminal B on each of the Low Voltage Connection Boards.
Connect the shield wires to one of the Cascade shield ground
terminals on the Low Voltage Connection Boards (FIG. 7-3).
If more than two boilers are on the Cascade, daisy chain the
wiring from the Cascade terminals on the second boiler to the
Cascade terminals on the third boiler, then from the third to the
forth, and so on. The connections between boilers can be made
in any order, regardless of the addresses of the boilers. Try to
keep each cable as short as possible.
Alarm contacts
The SMART TOUCH control closes another set of contacts
whenever the boiler is locked out or the power is turned off.
This can be used to turn on an alarm, or signal a Building
Management System that the boiler is down.
System return sensor
1. Install the system return sensor into the return of the
primary loop.
2. Connect the terminals to the system return sensor as
shown in FIG. 7-3.
37
Installation & Operation Manual
7 Field wiring
Figure 7-3 Low Voltage Field Wiring Connections
38
Installation & Operation Manual
8 Condensate disposal
Condensate drain
9. Do not expose condensate line to freezing temperatures.
1. The Crest is a high efficiency appliance that produces
Use materials approved by the authority
condensate.
NOTICE
having jurisdiction. In the absence of
other authority, PVC and CPVC pipe
must comply with ASTM D1785 or D2845.
Cement and primer must comply with
ASME D2564 or F493. For Canada use
CSA or ULC certified PVC or CPVC pipe,
fittings, and cement.
2. The rear of the boiler has a 1 inch (25.4 mm) stainless steel
drain fitting and a 3/8 inch (9.8 mm) stainless steel vent line
for connection to the condensate trap.
3. Connect the 1 inch (25.4 mm) fitting to the 1 inch (25.4
mm) fitting on the condensate trap with the factory
supplied silicone hose. Secure the hose to the condensate
trap and the boiler using the factory supplied hose clamps.
To allow for proper drainage on large
NOTICE
4. Connect the 3/8 inch (9.8 mm) fitting to the 3/8 inch (9.8
mm) fitting on the condensate trap (shipped loose) with
the factory supplied silicone hose. Secure the hose to the
condensate trap and the boiler using the factory supplied
hose clamps.
horizontal runs, a second line vent may
be required and tubing size may need to
increase to 1 inch (25 mm).
The condensate line must remain
unobstructed, allowing free flow of
condensate. If condensate is allowed to
freeze in the line or if the line is obstructed
in any other manner, condensate can exit
from the boiler tee, resulting in potential
water damage to property.
5. The condensate trap must be installed at the same level or
below the boiler base.
6. The condensate trap is sized for a 1" PVC outlet connection
pipe.
7. Plug the wiring connection from the condensate trap into
the connector located on the back of the unit.
10. A condensate removal pump is required if boiler is below
the drain. When installing a condensate pump, select one
approved for use with condensing boilers and furnaces.
The pump should have an overflow switch to prevent
property damage from condensate spillage. The switch
should be wired to the auxiliary device proving switch
terminals on the low voltage connection board.
8. Slope condensate tubing down and away from the boiler
into a drain or condensate neutralizing filter. Condensate
from the Crest will be slightly acidic (typically with a pH
from 3 to 5). Install a neutralizing filter if required by local
codes.
A neutralizer kit (FIG. 8-1) is available from the factory
(KIT30097). The neutralizer kit must be placed on a surface
that is a minimum of 3 inches lower than the condensate
trap with field supplied piping (vacuum break) installed
between the condensate trap and the neutralizer kit.
Figure 8-1 Condensate Disposal
M
VACUU
BREAK
DETAIL
DRAIN
FLOOR
OR DRAIN PAN
IMG00174
NSATE TRAP
CONDE
SAME LEVEL OR BELOW
BOILER BASE
T
ZER KI
NEUTRALI
(OPTIONAL)
39
3” MINIMUM BELOW
CONDENSATE TRAP
|