Burnham PVG User Manual

INSTALLATION, OPERATING AND  
SERVICE INSTRUCTIONS FOR  
PVG™  
GAS - FIRED BOILER  
As an ENERGY STAR® Partner, Burnham Hydronics has determined that the PVG Series meets the ENERGY  
STAR® guidelines for energy efficiency established by the United States Environmental Protection Agency (EPA).  
For service or repairs to boiler, call your heating contractor. When seeking information on  
boiler, provide Boiler Model Number and Serial Number as shown on Rating Label.  
Boiler Model Number  
Boiler Serial Number  
Installation Date  
PVG  
Heating Contractor  
Phone Number  
Address  
8140708R8-8/08  
Price - $5.00  
WARNING  
This boiler requires regular maintenance and service to operate safely. Follow the instructions contained  
in this manual.  
Improperinstallation,adjustment,alteration,serviceormaintenancecancausepropertydamage,personal  
injury or loss of life. Read and understand the entire manual before attempting installation, start-up  
operation, or service. Installation and service must be performed only by an experienced, skilled, and  
knowledgeable installer or service agency.  
This boiler must be properly vented.  
This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate  
combustion and ventilation air.  
The interior of the venting system must be inspected and cleaned before the start of the heating season  
and should be inspected periodically throughout the heating season for any obstructions. A clean and  
unobstructed venting system is necessary to allow noxious fumes that could cause injury or loss of life  
to vent safely and will contribute toward maintaining the boiler’s efficiency.  
Installation is not complete unless a pressure relief valve is installed into the tapping located on top of  
appliance. - See the Water Piping and Trim Section of this manual for details.  
This boiler is supplied with safety devices which may cause the boiler to shut down and not re-start  
without service. If damage due to frozen pipes is a possibility, the heating system should not be left  
unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating  
system to prevent damage if the boiler is inoperative.  
This boiler contains very hot water under high pressure. Do not unscrew any pipe fittings nor attempt  
to disconnect any components of this boiler without positively assuring the water is cool and has no  
pressure. Always wear protective clothing and equipment when installing, starting up or servicing this  
boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the  
temperature and pressure of the boiler. This boiler contains components which become very hot when  
the boiler is operating. Do not touch any components unless they are cool.  
Boilermaterialsofconstruction,productsofcombustionandthefuelcontainalumina,silica,heavymetals,  
carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause  
death or serious injury and which are known to the state of California to cause cancer, birth defects and  
other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing  
or working nearby the appliance.  
Failure to follow all instructions in the proper order can cause personal injury or death. Read all instruc-  
tions, including all those contained in component manufacturers manuals which are provided with the  
boiler before installing, starting up, operating, maintaining or servicing.  
Keep boiler area clear and free from combustible materials, gasoline and other flammable vapors or  
liquids.  
All cover plates, enclosures and guards must be in place at all times.  
NOTICE  
This boiler has a limited warranty, a copy of which is printed on the back of this manual. It is the responsibility  
of the installing contractor to see that all controls are correctly installed and are operating properly when the  
installation is complete.  
Table of Contents  
I. Pre-Installation...............................6  
VI. Electrical.......................................28  
VII. Modular Installation ....................37  
VIII. System Start-up ............................39  
IX. Service ..........................................46  
X. Repair Parts..................................52  
II. Unpack Boiler ................................7  
III. Venting...........................................8  
IV. Water Piping and Trim .................20  
V. Gas Piping....................................25  
Figure 1: Minimum Clearances to Combustibles  
4
5
I. Pre-Installation  
WARNING  
F. Provide combustion and ventilation air in accordance  
with applicable provisions of local building codes,  
or: USA - National Fuel Gas Code, NFPA 54/ANSI  
Z223.1, Air for Combustion and Ventilation;  
Canada - Natural Gas or Propane Installation Code,  
CAN/CSA-B149.1.  
If you do not follow these instructions exactly,  
a fire or explosion may result causing property  
damage or personal injury.  
DANGER  
WARNING  
Do not install boiler where gasoline or other  
flammable vapors or liquids, or sources of  
hydrocarbons (i.e. bleaches, cleaners, chemicals,  
sprays, paint removers, fabric softeners, etc.) are  
used or stored.  
Adequate combustion and ventilation air must  
be provided to assure proper combustion.  
The following guideline is based on the National Fuel Gas  
Code, NFPA 54/ANSI Z223.1.  
1. Determine volume of space (boiler room). Rooms  
communicating directly with space (through  
openings not furnished with doors) are considered  
part of space.  
NOTICE  
Due to the low water content of the boiler, mis-  
sizing of the boiler with regard to the heating  
system load will result in excessive boiler cycling  
and accelerated component failure. Burnham  
DOES NOT warrant failures caused by mis-sized  
boiler applications. DO NOT oversize the boiler to  
the system. Modular boiler installations greatly  
reduce the likelihood of boiler oversizing.  
Volume [ft³] = Length [ft] x Width [ft] x Height [ft]  
2. Determine Total Input of all appliances in space.  
Round result to nearest 1,000 Btu per hour (Btuh).  
3. Determine type of space. Divide Volume by Total  
Input.  
a. If result is greater than or equal to 50 ft³ per  
1,000 Btuh, space is considered an unconfined  
space.  
A. Installation must conform to the requirements of the  
authority having jurisdiction. In the absence of such  
requirements, installation must conform to the National  
Fuel Gas Code, NFPA 54/ANSI Z223.1, and/or CAN/  
CSA B149.1 Installation Codes.  
b. If result is less than 50 ft³ per 1,000 Btuh, space  
is considered a confined space.  
4. Determine building type. A building of unusually  
tight construction has the following characteristics:  
B. Appliance is design certified for installation on  
combustible flooring. Do not install boiler on  
carpeting.  
a. Walls and ceiling exposed to outside atmosphere  
have a continuous water vapor retarder with a  
rating of 1 perm or less with openings gasketed  
and sealed, and;  
C. Provide clearance between boiler jacket and  
combustible material in accordance with local fire  
ordinance. Refer to Figure 1 for minimum listed  
clearance from combustible material. Recommended  
service clearance is 24 inches from left side, right  
side and front. Service clearances may be reduced to  
minimum clearances to combustible materials.  
b. Weather-stripping has been added on openable  
windows and doors, and;  
c. Caulking or sealants applied in joints around  
window and door frames, between sill plates and  
floors, between wall-ceiling joints, between wall  
panels, at plumbing and electrical penetrations,  
and at other openings.  
D. Install on level floor. For basement installation provide  
solid base such as concrete, if floor is not level or if  
water may be encountered on floor around boiler. Floor  
must be able to support weight of boiler, water and all  
additional system components.  
5. For boiler located in an unconfined space in a  
building of other than unusually tight construction,  
adequate combustion and ventilation air is normally  
provided by fresh air infiltration through cracks  
around windows and doors.  
E. Protect gas ignition system components from water  
(dripping, spraying, rain, etc.) during boiler operation  
and service (circulator replacement, condensate trap,  
control replacement, etc.).  
6. For boiler located within unconfined space in  
building of unusually tight construction or within  
confined space, provide outdoor air through two  
permanent openings which communicate directly or  
by duct with the outdoors or spaces (crawl or attic)  
freely communicating with the outdoors. Locate one  
opening within twelve (12) inches of top of space.  
Locate remaining opening within twelve (12) inches  
of bottom of space. Minimum dimension of air  
opening is three (3) inches. Size each opening per  
following:  
space(s) of sufficient volume such that combined  
volume of all spaces meet criteria for unconfined  
space. Size each opening for minimum free area  
of one (1) square inch per 1,000 Btu per hour  
input of all equipment in spaces, but not less than  
100 square inches.  
7. Combustion Air/Ventilation Duct Louvers and  
Grilles. Equip outside openings with louvers to  
prevent entrance of rain and snow, and screens to  
prevent entrance of insects and rodents. Louvers and  
grilles must be fixed in open position or interlocked  
with equipment to open automatically before burner  
operation. Screens must not be smaller than ¼ inch  
mesh.  
a. Direct communication with outdoors. Minimum  
free area of one (1) square inch per 4,000 Btu per  
hour input of all equipment in space.  
b. Vertical ducts. Minimum free area of one (1)  
square inch per 4,000 Btu per hour input of all  
equipment in space. Duct cross-sectional area  
shall be same as opening free area.  
Consider the blocking effect of louvers, grilles and  
screens when calculating the opening size to provide  
the required free area. If free area of louver or grille  
is not known, assume wood louvers have 20-25  
percent free area and metal louvers and grilles have  
60-75 percent free area.  
c. Horizontal ducts. Minimum free area of one (1)  
square inch per 2,000 Btu per hour input of all  
equipment in space. Duct cross-sectional area  
shall be same as opening free area.  
Alternate method for boiler located within  
confined space. Use indoor air if two permanent  
openings communicate directly with additional  
CAUTION  
Avoid operating this boiler in an environment where saw dust, loose insulation fibers, dry wall dust, etc.  
are present. If boiler is operated under these conditions, the burner interior and ports must be cleaned and  
inspected daily to insure proper operation.  
II. Unpack Boiler  
WARNING  
CAUTION  
Installation of this boiler should be undertaken  
only by trained and skilled personnel from a  
qualified service agency.  
Do not drop boiler. Do not bump boiler jacket  
against floor.  
A. Move boiler to approximate installed position.  
E. Tilt the boiler to its front side or back side and slide a  
B. Remove all crate fasteners.  
wooden slat under the three raised feet.  
C. Lift and remove outside container. Save two of the  
wooden slats from the container sleeve for use in Steps  
E and F.  
F. Tilt the boiler in the opposite direction and slide  
another wooden slat under the three raised feet.  
G. Slide the boiler left or right off the skid using the two  
D. Remove all boiler hold-down fasteners.  
wooden slats as runners.  
H. Move boiler to its permanent location.  
7
III. Venting  
WARNING  
Do not use this boiler with galvanized, Type ꢁ04 or Type ꢁ1ꢂ stainless steel, non metallic or any other  
non ALꢀ9-4C® based vent systems.  
Do not use a barometric damper or drafthood with this appliance.  
Do not use vent dampers with this boiler.  
Moisture and ice may form on surfaces around termination. To prevent deterioration, surfaces should  
be in good repair (sealed, painted, etc.).  
This appliance needs fresh air for safe operation and must be installed so there are provisions for  
adequate combustion and ventilation air.  
Read, understand and follow combustion air instruction restrictions contained in the Pre-Installation  
instructions of this manual.  
Do not operate appliance where gasoline or other flammable vapors or liquids, or sources of hydro-  
carbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) are used,  
stored and/or present in the air.  
When installing vent pipe through chimney, no other appliance can be vented into the chimney.  
Do not exceed maximum vent lengths. Refer to Table 4.  
Table 1: Vent System Options  
Installation  
Additional  
Drawing and  
Specification  
(See Section)  
Option  
Description  
Vent Kit  
Required  
Power Vent (air from within building) the vent pipe terminates  
horizontally (through a sidewall).  
1. Horizontal  
2. Vertical  
No  
No  
F.  
Power Vent (air from within building) the vent pipe terminates  
vertically (through the roof).  
G.  
Table ꢀ: Vent System Components Included with Boiler  
Vent System Components  
Part Number  
Gasketed Vent Terminal 3” -Horizontal PVG-3 thru PVG-7)  
Gasketed Vent Terminal 4” -Horizontal (PVG-8 & PVG 9)  
8110701  
8110702  
8
Table ꢁ: Burnham Vent System Components  
Equivalent  
Vent System Component Part Number  
Feet of Pipe  
3” Dia. Pipe x 1 Ft  
4” Dia. Pipe x 1 Ft  
3” Dia. Pipe x 3 Ft  
4” Dia. Pipe x 3 Ft  
3” Dia. Pipe x 5 Ft  
4” Dia. Pipe x 5 Ft  
3” Dia. Pipe x Adjustable  
8116296U  
100176-01  
8116298U  
100177-01  
8116300U  
100178-01  
8116319U  
1
3
5
Equal to  
Installed Length  
(1.06 TO 1.64)  
4” Dia. Pipe x Adjustable  
100179-01  
3” Dia. 90° Elbow  
8116294U  
100180-01  
8116292U  
100181-01  
8116302U  
100182-01  
8116304U  
100183-01  
8116116  
5
5
4” Dia. 90° Elbow  
3” Dia. 45° Elbow  
4” Dia. 45° Elbow  
3” Dia. Horizontal Drain Tee  
4” Dia. Horizontal Drain Tee  
3” Dia. Vertical Drain Tee  
4” Dia. Vertical Drain Tee  
3” Single Wall Thimble  
4” Single Wall Thimble  
3” Double Wall Thimble  
4” Double Wall Thimble  
2
7½  
---  
---  
100184-01  
8116115  
100185-01  
Table 4: Vent Length  
3” Vent Pipe  
(Equiv. Ft.)  
Min. Max.  
4” Vent Pipe  
(Equiv. Ft.)  
Model  
Min.  
---  
Max.  
---  
PVG-3 & PVG-4  
PVG-5 & PVG-6  
PVG-7  
8
50  
8
8
50  
50  
---  
---  
---  
---  
---  
PVG-8 & PVG-9  
---  
8
40  
9
A. Vent Guidelines Due to Removal of an Existing  
Boiler  
B. General Guidelines  
1. Vent system installation must be in accordance  
with National Fuel Gas Code, NFPA 54/ANSI  
Z221.3 or applicable provisions of local building  
codes. Contact local building or fire officials about  
restrictions and installation inspection in your area.  
For installations not involving the replacement of an  
existing boiler, proceed to Step B.  
When an existing boiler is removed from a common  
venting system, the common venting system is likely  
to be too large for proper venting of the remaining  
appliances. At the time of removal of an existing  
boiler, the following steps shall be followed with each  
appliance remaining connected to the common venting  
system placed in operation, while the other appliances  
remaining connected to the common venting system are  
not in operation:  
2. Refer to the appropriate drawings in this section of  
this manual to determine the proper configuration of  
venting system. See Table 1.  
3. This appliance requires a Special Gas Vent. The  
productisdesignedtouseBurnhamsuppliedAL29-4C®  
StainlessSteelventsystemcomponents.Thefollowing  
manufacturers offer similar AL 29-4C® components  
and are approved for use with this product. Heat-Fab  
Inc.-Saf-T-Vent(800-772-0739);Flex-LInternational  
Inc. - Star-34 (800-561-1980); Z-Flex U. S., Inc.  
- Z-Vent (800-654-5600); and Protech Systems, Inc.-  
FasNSeal™ (800-766-3473) or equivalent. The use  
of these alternate manufacturer’s venting systems will  
require adapters to connect to the Burnham supplied  
vent connector and vent terminal. These adapters are  
notsuppliedwiththisunitandshouldbeobtainedfrom  
the supplier of the alternate manufacturer’s venting  
system. See Table 3 for complete list of Burnham  
Vent System Components.  
1. Seal any unused openings in the common venting  
system.  
2. Visually inspect the venting system for proper  
size and horizontal pitch and determine there is no  
blockage or restriction, leakage, corrosion, and other  
deficiencies which could cause an unsafe condition.  
3. Insofar as is practical, close all building doors and  
windows and all doors between the space in which  
the appliances remaining connected to the common  
venting system are located and other spaces of the  
building. Turn on clothes dryers and any appliance  
not connected to the common venting system.  
Turn on any exhaust fans, such as range-hoods and  
bathroom exhausts, so they will operate at maximum  
speed. Do not operate a summer exhaust fan. Close  
fireplace dampers.  
4. Horizontal vent pipe must maintain a minimum ¼  
inch per foot slope away from boiler.  
5. Use noncombustible ¾ inch pipe strap to support  
horizontal runs and maintain vent location and  
slope while preventing sags in pipe. Do not restrict  
thermal expansion or movement of vent system.  
Maximum support spacing is five (5) feet. Do not  
penetrate any part of the vent system with fasteners.  
4. Place in operation the appliance being inspected.  
Follow the Lighting (or Operating) Instructions.  
Adjust thermostat so appliance will operate  
continuously.  
6. Vent length restrictions are based on equivalent  
length of vent pipe (total length of straight pipe  
plus equivalent length of fittings). Maximum  
vent lengths are listed in Table 4. Do not exceed  
maximum vent lengths. Table 3 lists equivalent  
lengths for fittings. Do not include vent terminals in  
equivalent feet calculations.  
5. Test for spillage at the draft hood relief opening  
after five (5) minutes of main burner operation. Use  
the flame of a match or candle, or smoke from a  
cigarette, cigar or pipe.  
6. After it has been determined that each appliance  
remaining connected to the common venting system  
properly vents when tested as outlined above, return  
doors, windows, exhaust fans, fireplace dampers and  
any other gas burning appliance to their previous  
conditions of use.  
7. Provide and maintain vent pipe minimum clearances  
to combustible materials. Vent pipe minimum  
clearance to combustible material is four (4) inches  
when vent is installed in a fully enclosed (chase)  
application or three (3) inches when vent is installed  
with at least one side open, similar to a joist bay  
application. Use double wall thimble [Burnham  
Part No. 8116115 (3”), 100185-01 (4”)] when  
penetrating a combustible wall.  
7. Any improper operation of the common venting  
system should be corrected so the installation  
conforms with the National Fuel Gas Code, NFPA  
54/ANSI Z223.1. When resizing any portion of the  
common venting system, the common venting  
system should be resized to approach the minimum  
size as determined using the appropriate tables in  
Part II in the National Fuel Gas Code, NFPA 54/  
ANSI Z223.1.  
8. Do not install venting system components on  
the exterior of the building except as specifically  
required by these instructions. The vent termination  
location is restricted as follows:  
10  
a. Minimum twelve (12) inches above grade plus  
normally expected snow accumulation level, or  
seven (7) feet above grade if located adjacent  
to public walkway. Do not install over public  
walkway where local experience indicates  
appliance flue gas vapor or condensate creates a  
nuisance or hazard.  
requires a minimum installed length of 12¾ inch  
and can adjust across a 7 inch gap up to a maximum  
of 19¾ inch long. (Note for the adjustable pipe  
the installed length should be measured from the  
centerline of the bead on the male end of the first  
pipe to the end of the female pipe excluding the  
locking band of the second pipe with a single  
gasket.) Only in the event the adjustable length pipe  
is not sufficient a standard length pipe may be cut  
using the procedure outlined below for the Gasket-  
Less Vent System.  
b. Minimum three (3) feet above any forced air  
inlet located within ten (10) feet.  
c. Minimum four (4) feet below, four (4) feet  
horizontally from, or four (4) feet above any  
door, window, or gravity air inlet.  
WARNING  
d. Minimum four (4) feet horizontally from electric  
meters, gas meters, regulators, and relief valves.  
This distance may be reduced if equipment is  
protected from damage due to condensation or  
vapor by enclosure, overhangs, etc.  
Never exceed maximum installed length of 19¾  
inches for adjustable length pipe.  
Risk of flue gas leakage is possible.  
e. Minimum twelve (12) inches from overhang or  
corner of building.  
NOTICE  
9. Enclose vent passing through occupied or  
unoccupied spaces above the boiler with material  
having a fire resistance rating of at least equal to the  
rating of the adjoining floor or ceiling. Maintain  
minimum clearances to combustible materials. See  
Figure 1.  
Cut must be square with pipe and filed or  
sanded smooth before joining. Carefully ensure  
roundness of cut pipe by hand with gloves before  
installing. Seal joint with RTV specified in this  
manual.  
Note: For one or two family dwellings, fire  
resistance rating requirement may not need to be  
met, but is recommended.  
C. Install Vent Pipe, Burnham Gasketed Vent System.  
1. Procedure for Joining Burnham Gasketed Vent Pipe  
and Fittings. See Figure 3.  
10. Plan venting system to avoid possible contact with  
plumbing or electrical wires. Start at vent connector  
on top of boiler and work towards vent terminal.  
a. Wipe the male end of each joint using an alcohol  
pad to remove any dirt and grease.  
b. Align weld seams in pipes and use a slight  
twisting motion to FULLY insert male end into  
female end of joint. Ensure bead in male end  
of pipe is below locking band and rest against  
the end of the female pipe. Verify the factory-  
installed gasket is not dislodged or cut.  
11. Once a vent pipe manufacturer and system is chosen  
never mix and match vent systems.  
12. If a non-standard length pipe is required:  
Gasketed Vent System: The use of the adjustable  
length pipe (P/N 8116319U) is recommended to  
complete a non-standard pipe length. This pipe  
Figure ꢁ: Burnham Gasketed Vent Joint Detail  
11  
c. Tighten locking band by HAND with a 5/16”  
nut driver until snug plus ¼ turn. DO NOT  
SECURE JOINTS WITH SHEET METAL  
SCREWS OR POP RIVETS. DO NOT  
PUNCTURE THE VENT SYSTEM!  
4. Use appropriate designed thimbles when passing  
through combustible walls (thimble use optional for  
noncombustible walls). Insert thimble through wall  
from outside. Secure outside flange to wall with  
nails or screws, and seal ID, OD and vent holes with  
sealant material. Install inside flange to inside wall,  
secure with nails or screws, and seal with sealant  
material.  
d. Once the installation is complete, operate  
appliance and inspect all joints to ensure that flue  
gases and/or liquid condensate will not escape.  
5. For noncombustible wall application when thimble  
is not used, size opening such that bell with locking  
band attached cannot pass through.  
D. Horizontal Venting System. See Figures 4, 4A and 5.  
Vent Piping –  
1. This boiler is supplied with components as standard  
equipment for installation of the separate horizontal  
venting system.  
6. Join vent terminal to vent pipe. See Figure 5.  
7. Insert vent pipe through thimble/opening from  
outside and join to vent system. Apply sealant  
between vent pipe and opening/thimble to provide  
weathertight seal.  
2. Do not exceed maximum vent lengths. Refer to  
Table 4.  
3. Recommended horizontal installation consists of  
vent being sloped down ¼ inch per foot away from  
boiler. See Figures 4 and 4A.  
1ꢀ  
1ꢁ  
14  
15  
E. Vertical Venting System - See Figures 6, 7 and 8.  
NOTICE  
Roof penetrations require the use of roof flashing  
and storm collar - not supplied with boiler.  
Maintain minimum clearance to combustible  
materials.  
Vent Piping –  
1. Do not exceed maximum vent lengths. Refer to  
Table 4.  
6. Install Vent Terminal.  
a. Size roof opening to maintain minimum  
clearance from combustible materials.  
2. Installation of a vertical vent tee 8116304U is  
required on all vertical vent applications. See  
Figures 6 and 7. Attach vertical vent drain tee  
directly to elbow or horizontal pipe from an elbow  
immediately after vent connector.  
b. Extend vent pipe to maintain minimum vertical  
and horizontal distance of twelve (12) inches  
from roof surface. Allow additional vertical  
distance for expected snow accumulation.  
Provide brace as required. Refer to Figure 8.  
3. Slope horizontal runs minimum ¼ inch per foot.  
Slope towards vertical vent drain tee. Position weld  
seams in vent pipes, in all horizontal runs, at the top  
to avoid condensate from lying on the seams.  
c. Install storm collar on vent pipe immediately  
above flashing. Apply Dow Corning Silastic 732  
RTV Sealant between vent pipe and storm collar  
to provide weathertight seal.  
4. Install fire stops where vent passes through floors,  
ceilings or framed walls. The fire stop must close  
the opening between the vent pipe and the structure.  
d. Attach vent terminal.  
5. Whenever possible, install vent straight through  
the roof. Refer to Figure 7 if offset is necessary.  
1ꢂ  
17  
18  
F. Optional Exterior Separate Horizontal Vent Terminal Mounting – See Figure 9.  
b. After penetrating wall/thimble, install an  
1. Do not exceed maximum vent lengths. Refer to  
Table 4.  
AL 29-4C® 90° elbow so that elbow leg is in the  
up direction.  
2. This installation will allow a maximum of seven  
(7) feet vertical exterior run of the vent piping to be  
installed .  
c. Install maximum of five (5) feet of AL 29-4C®  
vent pipe. Refer to Sections C through E for  
proper procedures for joining vent pipe and  
fittings.  
d. Install AL 29-4C® 45° elbow to upper AL 29-4C®  
90° elbow so that leg of 45° is in down direction  
(see Figure 9).  
NOTICE  
Exterior run to be included in equivalent vent  
lengths.  
f. Install vent terminal.  
3. Install vent piping.  
g. Brace piping if required.  
a. Install vent piping for desired venting system.  
Refer to specific section for details for vent pipe  
installation.  
Figure 9: Horizontal Vent Terminal Installation (3” Vent [left view] or 4” Vent [right view])  
19  
IV. Water Piping and Trim  
WARNING  
Failure to properly pipe boiler may result in improper operation and damage to boiler or structure.  
Oxygen contamination of boiler water will cause corrosion of iron and steel boiler components, and  
can lead to boiler failure. Burnham’s Standard Warranty does not cover problems caused by oxygen  
contamination of boiler water or scale (lime) build-up caused by frequent addition of water.  
A. Design and install boiler and system piping to  
prevent oxygen contamination of boiler water and  
frequent water additions.  
Where  
The universal location for a LWCO on both gas and oil  
hot water boilers is above the boiler, in either the supply  
or return piping. The minimum safe water level of a  
water boiler is at the uppermost top of the boiler; that is,  
it must be full of water to operate safely.  
1. There are many possible causes of oxygen  
contamination such as:  
a. Addition of excessive make-up water as a result  
of system leaks.  
What Kind  
b. Absorption through open tanks and fittings.  
c. Oxygen permeable materials in the distribution  
system.  
The PVG boiler is designed to accept the wiring of the  
Safgard Model 1100-H4 LWCO (P/N 100592-01). This  
is a probe type LWCO. The factory wiring is designed  
to allow simple “Plug-in” installation of the wiring.  
2. In order to insure long product life, oxygen sources  
must be eliminated. This can be accomplished by  
taking the following measures:  
How to Pipe  
A “tee” is commonly used to connect the probe LWCO  
to the supply or return piping, as shown below.  
a. Repairing system leaks to eliminate the need for  
addition of make-up water.  
b. Eliminating open tanks from the system.  
c. Eliminating and/or repairing fittings which allow  
oxygen absorption.  
d. Use of non-permeable materials in the  
distribution system.  
e. Isolating the boiler from the system water by  
installing a heat exchanger.  
f. Use properly designed and operating air  
elimination devices in water piping.  
B. Low Water Cut Off (LWCO) on Hot Water Boilers  
(Optional)  
WARNING  
DO NOT ATTEMPT to cut factory wires to  
install an aftermarket Low Water Cut Off  
(LWCO). Only use connections specifically  
identified for Low Water Cut Off.  
LWCO Location  
Select the appropriate size tee using the LWCO  
manufacturer’s instructions. Often, the branch  
connection must have a minimum diameter to prevent  
bridging between the probe and the tee. Also, the run  
of the tee must have a minimum diameter to prevent  
the end of the probe from touching or being located too  
close to the inside wall of the run of the tee.  
In all cases, follow the Low Water Cut Off  
(LWCO) manufacturer’s instructions.  
When  
A low water cutoff is required to protect a hot water  
boiler when any connected heat distributor (radiation)  
is installed below the top of the hot water boiler (i.e.  
baseboard on the same floor level as the boiler). In  
addition, some jurisdictions require the use of a LWCO  
with a hot water boiler.  
Ideally, manual shutoff valves should be located  
above the LWCO and the boiler to allow for servicing.  
This will allow probe removal for inspection without  
draining the heating system. Many probe LWCO  
manufacturers recommend an annual inspection of the  
probe.  
ꢀ0  
How to Wire  
Ensure power is turned off to boiler.  
Locate the LWCO jumper wire in the factory wiring  
harness. Remove the jumper wire and install  
the LWCO wiring from LWCO Model 1100-H4  
(P/N 100592-01) into the plug of the PVG factory  
wiring.  
WARNING  
Pressure relief valve discharge piping must be  
piped such that the potential of severe burns  
is eliminated. DO NOT pipe in any area where  
freezing could occur. DO NOT install any shut-off  
valves, plugs or caps. Consult Local Codes for  
proper discharge piping arrangement.  
How to Test  
Shut off fuel supply. Lower water level until water  
level is BELOW the LWCO. Generate a boiler demand  
by turning up thermostat. Boiler should not attempt to  
operate. Increase the water level by filling the system.  
The boiler should attempt to operate once the water  
level is above the LWCO.  
F. Space heating and domestic water heating with  
Alliance™ water heater. Install Alliance water heater as  
a separate heating zone. Refer to Alliance Installation,  
Operating and Service Instructions for additional  
information.  
G. If boiler is used in connection with refrigeration  
systems, boiler must be installed with chilled medium  
piped in parallel with the heating boiler using  
appropriate valves to prevent chilled medium from  
entering boiler, see Figure 10.  
NOTICE  
Ensure the location of the LWCO in the piping will  
allow for connection of the LWCO wiring harness  
to the factory wiring of the PVG.  
H. If boiler is connected to heating coils located in  
air handling units where they may be exposed to  
refrigerated air, boiler piping must be equipped with  
flow control valves to prevent gravity circulation of  
boiler water during operation of cooling system.  
C. Connect system supply and return piping to  
boiler. See Figures 11 and 12. Maintain minimum ½  
inch clearance from hot water piping to combustible  
materials.  
NOTICE  
Burnham recommends sizing the system  
circulator to supply sufficient flow (GPM) to allow a  
ꢀ0°F temperature differential in the system. When  
sizing the system circulator, the pressure drop of  
all radiators, baseboard and radiant tubing and all  
connecting piping must be considered.  
D. Install circulator with flanges, gaskets and bolts  
provided. Circulator harness allows circulator to be  
mounted on supply or return. Connect harness to  
circulator and secure any excess conduit.  
E. Install supply manifold, pressure/temperature gauge  
and pressure relief valve.  
Figure 10: Recommended Piping for Combination  
Heating & Cooling (Refrigeration) System  
See Figure 10A. Pressure Relief Valve must be installed  
with spindle in vertical position. Installation of the  
relief valve must comply with the ASME Boiler and  
Pressure Vessel Code, Section IV.  
I. Use a boiler bypass if the boiler is to be operated  
in a system which has a large volume or excessive  
radiation where low boiler water temperatures may be  
encountered (i.e. converted gravity circulation system,  
etc.).  
ꢀ1  
Figure 10A: Supply Water Manifold Piping  
Install pipe tee between circulator and boiler return  
J. After the boiler and system have been cleaned and  
flushed, and before refilling the entire system add  
appropriate water treatment chemicals, if necessary, to  
bring the pH between 7 and 11.  
along with second tee in supply piping as shown in  
Figure 11 or 12. Bypass should be same size as the  
supply and return lines with valves located in bypass  
and supply outlet as illustrated in Figure 11 or 12 in  
order to regulate water flow to maintain higher boiler  
water temperatures.  
After the boiler is operational (reference Section VIII.  
System Start-Up) set by-pass and boiler supply valves  
to half throttle position to start. Operate boiler until  
system water temperature reaches normal operating  
range.  
K. If it is required to perform a long term pressure  
test of the hydronic system, the boiler should first be  
isolated to avoid a pressure loss due to the escape of air  
trapped in the boiler.  
To perform a long term pressure test including the  
boiler, ALL trapped air must first be removed from the  
boiler.  
Adjust valves to provide 180° to 200°F supply water  
temperature. Opening the boiler supply valve will raise  
system temperature, while opening the by-pass valve  
will lower system supply temperature.  
A loss of pressure during such a test, with no visible  
water leakage, is an indication that the boiler contained  
trapped air.  
ꢀꢀ  
ꢀꢁ  
ꢀ4  
V. Gas Piping  
WARNING  
Table 7 for maximum capacity of Schedule 40 pipe.  
Table 8 lists equivalent pipe length for standard  
fittings.  
Failure to properly pipe gas supply to boiler may  
result in improper operation and damage to the  
boiler or structure. Always assure gas piping is  
absolutely leak free and of the proper size and  
type for the connected load.  
4. Corrections for the specific gravity of natural gas  
can be found in Table 6.  
Table 6: Specific Gravity Correction Factors for  
An additional gas pressure regulator may be  
needed. Consult gas supplier.  
Natural Gas  
Specific  
Gravity  
Correction  
Factor  
Specific  
Gravity  
Correction  
Factor  
A. Size gas piping. Design system to provide adequate gas  
supply to boiler. Consider these factors:  
---  
---  
0.85  
0.90  
1.00  
1.10  
1.20  
1.30  
1.40  
0.81  
0.82  
0.78  
0.74  
0.71  
0.68  
0.66  
1. Allowable pressure drop from point of delivery to  
boiler. Maximum allowable system pressure is ½  
psig. Actual point of delivery pressure may be less;  
contact gas supplier for additional information.  
Minimum gas valve inlet pressure is stamped on  
the rating label located in the boiler’s vestibule  
compartment.  
---  
---  
0.60  
0.65  
0.70  
0.75  
0.80  
1.00  
0.96  
0.93  
0.90  
0.87  
2. Maximum gas demand. Refer to the boiler’s input as  
printed on its rating label. Also consider existing and  
expected future gas utilization equipment (i.e. water  
heater, cooking equipment).  
For materials or conditions other than those listed  
above, refer to National Fuel Gas Code, NFPA54/ANSI  
Z223.1, or size system using standard engineering  
methods acceptable to authority having jurisdiction.  
3. Length of piping and number of fittings. Refer to  
Table 5: Gas Ratings  
Boiler  
Model  
Number Gas Pressure  
Natural/LP  
Maximum  
Minimum Natural  
Gas Pressure  
(in. w.c.)  
Minimum LP  
Gas Pressure  
(in. w.c.)  
Natural  
Manifold  
Pressure  
(in. w.c.)  
LP  
Manifold  
Pressure  
(in. w.c.)  
(in. w.c.)  
Inlet to Gas Valve Inlet to Gas Valve  
PVG-3  
PVG-4  
PVG-5  
PVG-6  
PVG-7  
PVG-8  
PVG-9  
14  
4.5  
11.5  
3.5  
10.5  
NOTICE  
PVG boilers built for altitudes greater than 4,999 feet above sea level need to be specially orificed to adjust for  
changes in atmospheric conditions. The PVG boiler “H” Model has been certified to operate in atmospheric  
conditions from 5,000 to 10,000 feet above sea level. Input is derated by 10% for applications at 5,000 feet  
above sea level, and ꢀ0% for applications at 10,000 feet above sea levels. Derate is based on ꢀ% reduction  
per 1000 feet.  
The PVG boiler is available in two (2) altitude Models: The “S” Model 0 to 4,999 feet above sea level, and the  
“H” Model 5,000 to 10,000 feet above sea level.  
For applications above 10,000 feet, consult the manufacturer.  
ꢀ5  
Table 7: Maximum Capacity of Schedule 40 Pipe in CFH* For Natural Gas Pressures of 0.5 psig or Less  
0.3 inch w.c. Pressure Drop  
0.5 inch w.c. Pressure Drop  
Length  
[Feet]  
½
132  
92  
73  
63  
56  
50  
46  
43  
40  
38  
¾
278  
190  
152  
130  
115  
105  
96  
1
1¼  
1,050  
730  
590  
500  
440  
400  
370  
350  
320  
305  
½
175  
120  
97  
¾
1
1¼  
1,400  
950  
770  
660  
580  
530  
490  
460  
430  
400  
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
520  
350  
285  
245  
215  
195  
180  
170  
160  
150  
360  
250  
200  
170  
151  
138  
125  
118  
110  
103  
680  
465  
375  
320  
285  
260  
240  
220  
205  
195  
82  
73  
66  
61  
90  
57  
84  
53  
79  
50  
* 1 CFH of Natural Gas is approximately equal to 1 MBH; 1 CFH of LP is approximately equal to 2.5 MBH; con-  
tact your gas supplier for the actual heating value of your gas.  
2. Use thread (joint) compounds (pipe dope) resistant  
B. Connect boiler gas valve to gas supply system.  
to action of liquefied petroleum gas.  
3. Install sediment trap, ground-joint union and manual  
shut-off valve upstream of boiler gas control valve  
and outside jacket. See Figure 13.  
WARNING  
Failure to use proper thread compounds on all  
gas connectors may result in leaks of flammable  
gas.  
WARNING  
Gas supply to boiler and system must be  
absolutely shut off prior to installing or servicing  
boiler gas piping.  
1. Use methods and materials in accordance with local  
plumbing codes and requirements of gas supplier. In  
absence of such requirements, follow National Fuel  
Gas Code, NFPA 54/ANSI Z223.1.  
Figure 1ꢁ: Recommended Gas Piping  
Table 8: Equivalent Lengths of Standard Pipe Fittings & Valves  
VALVES FULLY OPEN  
Pipe  
Size  
I.D.  
Inches  
Swing  
Check  
90°  
Elbow  
45°  
Elbow  
90° Tee, Flow  
Through Run Through Branch  
90° Tee, Flow  
Gate  
Globe  
Angle  
½”  
¾”  
0.622  
0.824  
1.049  
1.380  
0.35  
0.44  
0.56  
0.74  
18.6  
23.1  
29.4  
38.6  
9.3  
4.3  
5.3  
6.8  
8.9  
1.6  
2.1  
2.6  
3.5  
0.78  
0.97  
1.23  
1.60  
1.0  
1.4  
1.8  
2.3  
3.1  
4.1  
5.3  
6.9  
11.5  
14.7  
19.3  
1”  
1¼”  
ꢀꢂ  
4. All above ground gas piping upstream from manual  
shut-off valve must be electrically continuous and  
bonded to a grounding electrode. Do not use gas  
piping as grounding electrode. Refer to National  
Electrical Code, NFPA 70.  
at ½ psig or less, isolate boiler from gas supply  
piping by closing boiler’s individual manual shutoff  
valve.  
2. Locate leaks using approved combustible gas  
detector, soap and water, or similar nonflammable  
solution.  
C. Pressure test. The boiler and its gas connection must  
be leak tested before placing boiler in operation.  
DANGER  
1. Protect boiler gas control valve. For all testing over  
½ psig, boiler and its individual shutoff valve must  
be disconnected from gas supply piping. For testing  
Do not use matches, candles, open flames or  
other ignition source to check for leaks.  
ꢀ7  
VI. Electrical  
DANGER  
Positively assure all electrical connections are unpowered before attempting installation or service of  
electrical components or connections of the boiler or building. Lock out all electrical boxes with padlock  
once power is turned off.  
WARNING  
Failure to properly wire electrical connections to the boiler may result in serious physical harm.  
Electrical power may be from more than one source. Make sure all power is off before attempting any  
electrical work.  
Each boiler must be protected with a properly sized over-current device.  
Never jump out or make inoperative any safety or operating controls.  
The wiring diagrams contained in this manual are for reference purposes only. Each boiler is shipped with  
a wiring diagram attached to the front door. Refer to this diagram and the wiring diagram of any controls  
used with the boiler. Read, understand and follow all wiring instructions supplied with the controls.  
service switch such that the boiler can be shut-off  
without exposing personnel to danger in the event of  
an emergency. Connect the main power supply and  
ground to the three (3) boiler wires (black, white and  
green) located in the junction box at the inside top of  
the boiler jacket. If a low water cutoff is to be used,  
connect the low water cutoff so that all 120V power  
to boiler is interrupted if the low water cutoff’s switch  
opens.  
A. General. Install wiring and electrically ground boiler  
in accordance with authority having jurisdiction or, in  
the absence of such requirements, follow the National  
Electrical Code, NFPA 70, and/or CSA C22.1 Electrical  
Code.  
B. A separate electrical circuit must be run from  
the main electrical service with an over-current  
device/disconnect in the circuit. A service switch is  
recommended and may be required by some local  
jurisdictions. Install the service switch in the line  
voltage “Hot” leg of the power supply. Locate the  
C. Refer to Figures 14 and 15 for details on the internal  
boiler wiring.  
NOTICE  
This boiler is equipped with a high water temperature limit located inside the internal wiring of the boiler.  
This limit provides boiler shutdown in the event the boiler water temperature exceeds the set point of the  
limit control. Certain Local Codes require an additional water temperature limit. In addition, certain types  
of systems may operate at temperatures below the minimum set point of the limit contained in the boiler.  
If this occurs, install an additional water temperature limit (Honeywell L4006 Aquastat) located in the system  
piping as shown in the Water Piping and Trim Section of this manual. Wire as indicated in the Electrical  
Section of this manual.  
NOTICE  
All wire, wire nuts, controls etc. are installer supplied unless otherwise noted.  
ꢀ8  
ꢀ9  
NOTICE  
If an additional system limit is used, install in series with the auxiliary limit jumper shown in the drawing  
below.  
Figure 15: Internal Boiler Wiring Ladder Diagram  
ꢁ0  
D. System Controls and Wiring  
1. Refer to National Electric Code or Local Electric Codes for proper size and type of wire required. Follow Code.  
2. Use anti-short bushings on all wiring passing through boiler jacket, junction boxes and/or control boxes.  
3. Use armored cable (BX) over all exposed line voltage wiring.  
4. If an Alliance™ indirect water heater is used, use priority zoning except for Hydro-Air Systems.  
5. Single Zone Heating System – Refer to Figure 16 of this manual for the electrical diagram for this type of system.  
Set the thermostat heat anticipator to 0.60 amps.  
6. Single Zone Heating System with Alliance™ Water Heater - Refer to Figure 17 of this manual for the electrical diagram  
for this type of system.  
Set the thermostat heat anticipator to 0.60 amps.  
7. Conventional Circulator Zoned System – Refer to Figure 18 of this manual for the electrical diagram for this type of  
system.  
Read, understand and follow all of the instructions provided with the Honeywell R8888 control.  
Connect the thermostat of each zone and the circulator for that zone to R8888 panel. If an Alliance™ indirect water  
heater is used, connect the Alliance™ thermostat and circulator to the Zone 1 terminals of the R8888.  
Set the thermostat heat anticipator to 0.12 amps.  
NOTICE  
The Honeywell R8888 Control is available in a three (ꢁ) zone Model (R8888A) and a four (4) zone Model  
(R8888B). Up to four (4) R8888’s may be used together to provide control for up to twelve (1ꢀ) individual  
zones. Only one (1) zone, the first zone of the main control, will provide priority circulation. If more than  
four (4) zones are required, connect additional R8888’s by wiring the A, B, and C terminals of each control  
together. Each R8888 requires a 120 volt power supply. If more than one (1) R8888 is used, set the panel  
type switch to “main” on the first R8888 and set the panel type switch to “expansion” on the second, third  
or fourth R8888.  
8. Conventional Zone Valve Zoned System – Refer to Figure 19. Wiring to the most popular models of zone valves is given  
in Figure 20.  
Connect the thermostat of each zone and the zone valve for that zone to the R8889 control. If an Alliance™ indirect water  
heater is used, connect the Alliance™ thermostat and zone valve to the “zone 1” terminals of the R8889.  
Set the thermostat heat anticipator to 0.12 amps.  
NOTICE  
The Honeywell R8889 Control is available in two three (ꢁ) zone models and two four (4) zone models.  
Burnham recommends using Model R8889A for three (ꢁ) zone systems and Model R8889B for four (4) zone  
systems. Models R8889C and R8889D have less load capacity and may not operate with certain types of  
zone valves. Up to four (4) R8889’s may be used together to provide up to sixteen (1ꢂ) individual zones.  
Only one (1) zone, the first zone of the main control will provide priority zoning for the Alliance indirect  
water heater. If more than four (4) zones are required, connect additional R8889’s by wiring the A, B and  
C terminals of each control together. Each R8889 requires a 120 volt power supply. If more than one (1)  
R8889 is used, set the panel type switch to “main” on the first R8889 and set the panel type switch to  
“expansion” on the second, third or fourth R8889.  
ꢁ1  
ꢁꢀ  
NOTICE  
If an additional system limit is used, install in series with the auxiliary limit jumper shown in the drawing  
below.  
ꢁꢁ  
ꢁ4  
ꢁ5  
Figure ꢀ0: Different Manufacturer’s Zone Valve Connections to Honeywell R8889  
ꢁꢂ  
VII. Modular Installation  
A. General Guidelines  
E. Gas Piping  
1. Refer to National Fuel Gas Code, Local Codes and  
1. Read and follow all venting, combustion air,  
water piping, gas piping and electrical instructions  
contained in this manual unless otherwise instructed  
in this section.  
Tables 7 and 8 for gas pipe sizing.  
Table 9: Modular Boiler Water Manifold Sizing  
2. Consult Local Building Codes or National Fuel Gas  
Code, NFPA 54/ANSI Z222.3 for restrictions and  
instructions on modular boiler installations.  
Recommended Minimum  
Combined Output  
Common Water Manifold  
(MBH)  
Size (NPT)  
< 166  
< 260  
< 550  
< 900  
< 2000  
1¼”  
1½”  
2”  
B. Module Sizing  
Burnham recommends sizing each boiler in a modular  
system to provide 20 % of the combined heating load  
where ever possible.  
2½”  
3”  
C. Venting  
1. Each boiler must have an individual vent pipe.  
Refer to Venting Section of this manual for venting  
guidelines and options.  
2. Each boiler must be piped as shown in Figure 13.  
WARNING  
WARNING  
Do not manifold vent pipes together.  
If gas pressure in the building is above ½ psig,  
an additional gas pressure regulator is required.  
Using one additional regulator for multiple  
boilers may result in unsafe boiler operation.  
The additional regulator must be able to properly  
regulate gas pressure at the input of the smallest  
boiler. If the regulator cannot do this, two or  
more additional regulators are required. Consult  
regulator manufacturer and/or local gas supplier  
for instructions and equipment ratings.  
2. The maximum vent length for each boiler is fifty  
(50) equivalent feet.  
3. The minimum horizontal distance between vent  
terminations is one (1) foot. Additional horizontal  
distance is desirable to avoid frost damage to the  
building. Vent terminations must be at least twelve  
(12) inches above the ground plus the expected  
snow accumulation.  
F. Electrical  
CAUTION  
1. Each boiler must be provided with a fused  
disconnect and service switch.  
Installing multiple vent terminations close  
together promotes frost buildup on buildings.  
To minimize this possibility, extend the distance  
from the building to the end of the vent  
termination and increase the horizontal distance  
between terminations.  
2. Install wiring in accordance with requirements of  
authority having jurisdiction. In the absence of such  
requirements, follow the National Electric Code,  
NFPA 70 and/or CSA C22.1 Electric Code.  
G. Modular Boiler Control Systems  
4. Multiple vertical vent pipes may be piped through  
a common conduit or chase so that one roof  
penetration may be made. Each vent termination  
must be one (1) foot from other terminations.  
Contact a controls manufacturer such as Honeywell or  
Tekmar to properly apply a modular control system.  
Common systems may use outdoor temperature, return  
water temperature or both to stage the boilers.  
D. Water Piping (See Table 9 and Figure 21)  
Installing a low water cutoff in the system piping of  
modular systems is strongly recommended and may be  
required by Local Codes.  
ꢁ7  
ꢁ8  
VIII. System Start-up  
4. Starting with one circuit at a time, open zone valve  
or shut-off valve in system supply and return piping.  
A. Safe operation and other performance criteria were  
met with gas manifold and control assembly provided  
on boiler when boiler underwent tests specified in  
American National Standard for Gas-Fired Low-  
Pressure Steam and Hot Water Boilers, ANSI Z21.13.  
5. Open hose bib.  
6. Open fill valve (Make-up water line should be  
located directly after full port ball valve in system  
supply piping between air scoop and expansion  
tank).  
B. Verify that the venting, water piping, gas piping and  
electrical system are installed properly. Refer to  
installation instructions contained in this manual.  
7. Allow water to overflow from bucket until discharge  
from hose is bubble free for 30 seconds.  
C. Confirm all electrical, water and gas supplies are  
turned off at the source and that vent is clear of  
obstructions.  
8. Close the opened zone valve or shut-off valve for  
the zone being purged of air, then open the zone  
valve or shut-off valve for the next zone to be  
purged. Repeat this step until all zones have been  
purged. At completion, open all zone valves or  
shut-off valves.  
D. Confirm that all manual shut-off gas valves between  
the boiler and gas source are closed.  
WARNING  
9. Close hose bib, continue filling the system until the  
pressure gauge reads 12 psi. Close fill valve.  
Completely read, understand and follow all  
instructions in this manual before attempting  
start up.  
(Note - If make-up water line is equipped with  
pressure reducing valve, system will automatically  
fill to 12 psi. Follow fill valve manufacturer’s  
instructions).  
E. Fill entire heating system with water and vent air  
from system. Use the following procedure on a Series  
Loop or multi-zoned system installed as per Figure 11  
or 12 to remove air from system when filling.  
10.Open isolation valve in boiler supply piping.  
11.Remove hose from hose bib.  
F. Confirm that the boiler and system have no water  
WARNING  
leaks.  
The maximum operating pressure of this boiler  
is ꢁ0 psig. Never exceed this pressure. Do not  
plug or change pressure relief valve.  
G. Prepare to check operation.  
1. Obtain gas heating value (in Btu per cubic foot)  
from gas supplier.  
2. Connect manometer to pressure tap on gas valve.  
Use 1/8 NPT tapping provided.  
NOTICE  
If it is required to perform a long term pressure  
test of the hydronic system, the boiler should  
first be isolated to avoid a pressure loss due to  
the escape of air trapped in the boiler.  
3. Temporarily turn off all other gas-fired appliances.  
4. Turn on gas supply to the boiler gas piping.  
5. Confirm that the supply pressure to the gas valve is  
14 in. w.c. or less. Refer to Table 5 for minimum  
supply pressure.  
To perform a long term pressure test including  
the boiler, ALL trapped air must first be removed  
from the boiler.  
6. Open the field installed manual gas shut-off valve  
located upstream of the gas valve on the boiler.  
A loss of pressure during such a test, with no  
visible water leakage, is an indication that the  
boiler contained trapped air.  
7. Using soap solution, or similar non-combustible  
solution, electronic leak detector or other approved  
method. Check that boiler gas piping valves, and  
all other components are leak free. Eliminate any  
leaks.  
1. Close full port ball valve in boiler supply piping.  
2. Isolate all zones by closing zone valves or shut-off  
valves in supply and return of each zone(s).  
DANGER  
3. Attach a hose to the vertical hose bib located prior to  
the full port ball valve in the system supply piping.  
(Note - Terminate hose in five gallon bucket at a  
suitable floor drain or outdoor area).  
Do not use matches, candles, open flames or  
other ignition source to check for leaks.  
8. Purge gas line of air.  
ꢁ9  
Figure ꢀꢀ: Operating Instructions  
40  
numbers in the wiring ladder diagrams. The yellow  
LED indicates the status of the flame, see Table 11.  
The green LED indicates the status of the system,  
see Table 12. See Figure 23 for LED locations. See  
Figure 24 for Troubleshooting Guide.  
H. Operating Instructions  
1. Follow Operating Instructions to place boiler in  
operation. See Figure 22.  
2. Electronic Ignition Modules with LED indicators.  
Table 10 cross-references the ignition module  
terminal designations to the ignition terminal  
Table 10: Ignition Module Terminal  
Cross-Reference  
Ignition Module  
Wiring Ladder Diagram  
Terminal Designation  
Terminal Number  
MV  
MV/PV  
PV  
1
2
3
GND  
4
24V (GND)  
5
24V  
6
SPARK  
9
Figure ꢀꢁ: LED Locations  
TABLE 11: Yellow LED Flame Codes  
Yellow LED  
Indicates  
Recommended Service Action  
Flash Codea  
Heartbeat  
Normal Flame Signal  
N/A  
Weak Flame Signal -  
System will operate reliably but flame signal is  
less than desired.  
Note: This indication may flash temporarily  
during or shortly after lightoff on some appli-  
cations.  
Perform routine maintenance to  
assure optimum flame signal.  
2
Marginal Flame Signal (less than 1.1 µA) -  
System may not operate reliably over time.  
Service call recommended.  
Note: This indication may flash temporarily  
during or shortly after lightoff on some appli-  
cations.  
Check gas supply, pilot burner, flame  
sense wiring, contamination of flame  
rod, burner ground connection.  
1
No Flame or Flame Signal -  
Below minimum threshold for system opera-  
tion.  
OFF  
N/A  
aFlash Code Descriptions  
- Heartbeat: Constant ½ second bright, ½ second dim cycles.  
- The flash code number signifies that the LED flashes X times at 2Hz, remains off for two  
seconds, and then repeats sequence.  
41  
Table 1ꢀ: Green LED Status Codes  
Green LED  
Flash Code  
Indicates  
Next System Action  
Recommended Service Action  
(X + Y)a  
OFF  
No “Call for Heat”  
N/A  
N/A  
N/A  
None  
None  
None  
Startup - Flame sense  
calibration  
Flash Fast  
Heartbeat  
Normal operation  
If system fails to light on next trial  
for ignition check gas supply, pilot  
burner, spark and flame sense wir-  
ing, flame rod contamination or out  
of position, burner ground connec-  
tion.  
5 minute Retry Delay-  
Pilot flame not detected  
during trial for ignition  
Initiate new trial for ignition after retry  
delay completed.  
2
If system fails to light on next trial  
for ignition check gas supply, pilot  
burner, flame sense wiring, flame  
rod contamination, burner ground  
connection.  
Initiate new trial for ignition. Flash  
code will remain through the ignition  
trial until flame is proved.  
Recycle- Flame failed  
during run  
3
4
If situation self corrects within 10  
Check for pilot flame. Replace gas  
valve if pilot flame present. If no  
pilot flame, cycle “Call for Heat.” If  
error repeats, replace control.  
seconds, control returns to normal  
sequence. If flame out of sequence re-  
mains longer than 10 seconds, control  
goes to Flash code 6+4 (see below)  
Flame sensed out of  
sequence  
Check flame sense lead wire for  
damage or shorting. Check that  
the fault corrects, control resumes nor- flame rod is in proper position.  
mal operation after a one minute delay. Check flame rod ceramic for cracks,  
damage or tracking.  
Control remains in wait mode. When  
Flame sense leakage to  
ground  
7
Check transformer and AC line for  
Control remains in wait mode. When  
proper input voltage to the control.  
Low secondary voltage  
supply- (below 15.5 Vac)  
8
the fault corrects, control resumes nor-  
Check with full system load on the  
mal operation after one minute delay.  
transformer.  
Check gas supply, pilot burner, spark  
5 minute Retry Delay-  
On every third retry on  
same “Call for Heat”  
Initiate new trial for ignition after retry  
delay completed.  
and flame sense wiring, flame rod  
contamination or out of position,  
burner ground connection.  
6 + 2  
6 + 3  
6 + 4  
ON  
On every 6th flame  
failure during run on the  
same “Call for Heat”  
Check gas supply, pilot burner, flame  
sense wiring, contamination of flame  
rod, burner ground connection.  
5 minute retry delay, then initiate new  
trial for ignition.  
Control waits until flame is no longer  
sensed and then goes to soft lockout.  
Flash code continues. Control auto  
Check for pilot flame. Replace gas  
valve if pilot flame present. If no  
pilot flame, cycle “Call for Heat.” If  
Flame sensed out of  
sequence- longer than  
10 seconds  
resets from soft lockout after one hour. error repeats, replace control.  
Soft lockout due to error  
detected during self  
check sequences  
Control auto resets from soft lockout  
after one hour.  
Reset by cycling “Call for Heat.” If  
error repeats, replace the control  
aFlash Code Descriptions:  
-
-
-
Flash Fast: rapid blinking  
Heartbeat: Constant ½ second bright, ½ second dim cycles.  
A single flash code number signifies that the LED flashes X times at 2Hz, remains off for two seconds, and then  
repeats the sequence.  
-
X + Y flash codes signify that the LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2  
Hz, remains off for three seconds, and then repeats the sequence.  
4ꢀ  
Honeywell Electronic Ignition Troubleshooting Guide  
Figure ꢀ4: Troubleshooting Guide  
4ꢁ  
Figure 26: 1 Inch Main Burner flame  
Figure ꢀ7: Pilot Burner Flame  
L. Check thermostat operation. Raise and lower  
temperature setting to start and stop boiler operation.  
M. Check ignition control module shut-off. Disconnect  
pilot lead wires from gas valve. If burners do not  
shutdown, determine cause of malfunction. Replace  
necessary items and check operation.  
N. Check low water cutoff (if so equipped).  
1. Adjust thermostat to highest setting.  
2. With boiler operating, open drain valve and slowly  
drain boiler.  
Figure 25: Sequence of Operation  
3. Main burners and pilot burner will extinguish and  
blower will stop when water level drops below low  
water cutoff probe. Verify limit, thermostat or other  
controls have not shut off boiler.  
I. Sequence of Operation. See Figure 25. If boiler fails  
to operate properly, see Troubleshooting Tree in Section  
IX: Service.  
J. Check pilot burner flame. See Figure 27. Flame  
should be steady, medium hard blue enveloping 3/8 to  
½ inch of sensing probe.  
4. Adjust thermostat to lowest setting. Refill boiler.  
O. Check limit.  
1. Adjust thermostat to highest setting.  
K. Check main burner flame. See Figures 26. Flame  
should have clearly defined inner cone with no yellow  
tipping. Orange-yellow streaks should not be confused  
2. Observe temperature gauge. When temperature is  
indicated, adjust limit to setting below observed  
with true yellow tipping.  
44  
temperature. Main burners and pilot burner should  
extinguish, and blower should stop.  
ii. Remove gas orifices. Drill one (1) drill size  
larger (drill size is stamped on orifice, or see  
Section X: Repair Parts).  
iii. Reinstall gas orifices and main burners.  
Measure input rate.  
3. Adjust limit to setting above observed temperature.  
Ignition sequence should begin.  
4. Adjust thermostat to lowest setting. Adjust limit to  
desired setting.  
6. Recheck Main Burner Flame.  
7. Return other gas-fired appliances to previous  
P. Adjust gas input rate to boiler.  
conditions of use.  
1. Adjust thermostat to highest setting.  
Q. Review User’s Information Manual and system  
2. Check manifold gas pressure. See Table 5 or rating  
label located in the boiler’s vestibule compartment.  
Adjust gas valve pressure regulator as necessary  
(turn adjustment screw counterclockwise to  
decrease manifold pressure, or clockwise to increase  
manifold pressure). If pressure cannot be attained,  
check gas valve inlet pressure. If less than minimum  
indicated in Table 5 or boiler’s rating label, contact  
gas supplier for assistance.  
operation with owner or operator.  
Table 1ꢁ: Gas Flow Rate in Cubic Feet  
Per Hour  
Seconds  
for One  
Revolution  
Size of Gas Meter Dial  
One-Half  
One  
Two  
Cu. Ft.  
Cu. Ft.  
Cu. Ft.  
3. Clock gas meter for at least 30 seconds. Use Table  
13 to determine gas flow rate in Cubic Feet per  
Hour.  
30  
32  
34  
36  
38  
40  
42  
44  
46  
48  
50  
52  
54  
56  
58  
60  
60  
120  
113  
106  
100  
95  
240  
225  
212  
200  
189  
180  
172  
164  
157  
150  
144  
138  
133  
129  
124  
120  
56  
53  
WARNING  
50  
Failure to properly adjust gas input rate will result  
in over firing or under firing of the appliance.  
Improper and unsafe boiler operation may result.  
47  
45  
90  
43  
86  
41  
82  
4. Determine Input Rate. Multiply gas flow rate by gas  
heating value.  
39  
78  
5. Compare measured input rate to input rate stated on  
rating plate.  
37  
75  
36  
72  
a. Boiler must not be over fired. Reduce input rate  
by decreasing manifold pressure. Do not reduce  
more than 0.3 inch w.c. If boiler is still overfired,  
contact your Burnham distributor or Regional  
Office for replacement Gas Orifice.  
35  
69  
33  
67  
32  
64  
31  
62  
30  
60  
b. Increase input rate if less than 98% of rating  
plate input. Increase manifold gas pressure no  
more than 0.3 inch w.c. If measured input rate is  
still less than 98% of rated input:  
i. Remove Main Burners per procedure in  
Section IX: Service.  
45  
IX. Service  
DANGER  
This boiler uses flammable gas, high voltage electricity, moving parts, and very hot water under high  
pressure. Assure that all gas and electric power supplies are off and that the water temperature is cool  
before attempting any disassembly or service.  
Do not attempt any service work if gas is present in the air in the vicinity of the boiler. Never modify,  
remove or tamper with any control device.  
WARNING  
This boiler must only be serviced and repaired by skilled and experienced service technicians.  
If any controls are replaced, they must be replaced with identical models.  
Read, understand and follow all the instructions and warnings contained in all the sections of this  
manual.  
If any electrical wires are disconnected during service, clearly label the wires and assure that the wires  
are reconnected properly.  
Never jump out or bypass any safety or operating control or component of this boiler.  
Read, understand and follow all the instructions and warnings contained in ALL of the component  
instruction manuals.  
Assure that all safety and operating controls and components are operating properly before placing  
the boiler back in service.  
4. Pipe must be supported at minimum five (5) foot  
A. General. Inspection and service should be conducted  
annually. Turn off electrical power and gas supply while  
conducting service or maintenance. Follow instructions  
TO TURN OFF GAS TO APPLIANCE. See Figure 22.  
intervals and must not sag.  
5. All vent joints must be secure and watertight.  
6. All joints must be secure and airtight. Horizontal  
vent tee drain or vertical vent tee drain (if used)  
must have minimum 6 inch trap and allow  
condensate to flow freely. To Clean:  
B. Low water cutoff (if so equipped).  
Probe Type (Annual Service). Probe type LWCO  
should be removed once a year, examined and  
cleaned of any dirt accumulations to assure proper  
operations. Do not attempt to repair mechanisms in the  
field. Complete replacement mechanisms, including  
necessary gaskets and installation instructions, are  
available from the manufacturer.  
a. Disconnect drain tube from drain fitting.  
b. Flush drain tube with water. Fill trap with water.  
c. Securely fasten drain tube to drain fitting,  
providing gas-tight and watertight seal.  
7. If pipe must be disassembled for removal of  
obstructions or resealing of joint, see Section III,  
Paragraph C.  
C. Vent System. Inspect for obstructions, soot  
accumulation, proper support, and deterioration of pipe,  
fittings, and joints.  
D. Boiler Flue Passages. Inspect for blockage or soot  
accumulation.  
1. Clean terminal screens. Terminals must be free of  
obstruction, undamaged, with screens securely in  
place.  
1. Remove Main Burners. See Figure 30.  
a. Remove front door.  
2. Terminal and wall thimbles (if used) must be  
weathertight.  
b. Disconnect pilot tubing and pilot lead wires at  
the gas valve.  
3. Pipe must be full round shape, and show no damage  
from impact or excessive temperature.  
c. Remove wires to Flame Roll-out Switch.  
d. Remove Burner Access Panel.  
4ꢂ  
e. Mark location of Main Burner with Pilot Bracket  
on gas manifold.  
f. Hold Main Burner on throat. Lift front of  
burners to clear orifice. Burner which holds  
pilot can be removed by lifting the burner  
adjacent to its right first.  
2. Disconnect Vent Connector and Vent Pipe from  
Blower Outlet.  
3. Remove Jacket Top Panel.  
4. Disconnect the Black and Gray Silicone Tubing  
from the Canopy.  
5. Disconnect Wiring Harness from Blower Motor.  
6. Remove Canopy/Blower Assembly.  
Figure ꢀ9: Blower Vent Connector Assembly  
a. Loosen the (4) screws from Canopy.  
7. Remove Flue Gas Baffles. Inspect Flue Gas Baffles  
for deterioration.  
E. Main Burners and Firebox.  
8. Inspect flue passages. Clean with flue brush. See  
1. Vacuum firebox. Exercise care - do not damage base  
Figure 30.  
insulation.  
9. Inspect heating surface in combustion chamber.  
Clean with straight handle wire brush.  
2. Clean main burners. Brush top of burners with soft  
bristle brush. See Figure 30. Vacuum to remove any  
dirt and lint.  
10. Install Flue Gas Baffles.  
11. Replace Canopy Assembly and seal.  
3. Vacuum tip of pilot burner.  
12. Connect Silicone Tubing between Pressure Fittings  
on Canopy Assembly and Pressure Switch. Route  
through bushings in Vestibule Panel . See Figure  
28.  
4. Check gas orifices for lint and dirt. Clean as  
necessary.  
5. Install main burners by reversing procedure to  
remove burners.  
13. Install Jacket Top Rear Panel.  
a. Pilot burner must be installed in original  
location. See Table 14.  
14. Connect vent system. See Figure 29.  
15. Connect Blower Motor Wiring Harness  
b. Main burners must be properly secured in burner  
tray slot at rear of firebox and over gas orifice.  
See Figure 30.  
c. Pilot gas supply and pilot lead wires must be  
reconnected.  
d. Burner access panel must be securely in place.  
e. Reconnect Flame Roll-out wires.  
F. Check operation. Follow steps G through P from  
Section VIII: System Start-up.  
G. Procedure for measuring differential pressure (See  
Figure 31).  
1. With boiler off, remove Gray and Black Hoses at  
differential pressure switch.  
2. With tees and ¼ inch aluminum stubs, connect water  
manometer as shown with additional tubing.  
Figure ꢀ8: Silicone Tubing Assembly  
47  
48  
Table 14: Pilot Burner Location  
Boiler Model  
PVG-3  
Main Burner with Pilot Bracket  
Pilot Burner Located Between Main Burners *  
2
3
4
5
6
7
8
2 & 3  
3 & 4  
4 & 5  
5 & 6  
6 & 7  
7 & 8  
8 & 9  
PVG-4  
PVG-5  
PVG-6  
PVG-7  
PVG-8  
PVG-9  
* Main burners numbered left to right as viewed from front of boiler.  
3. Start boiler and read Pressure on Manometer  
when boiler water temperature reaches operating  
temperature. Refer to Table 15 for minimum  
readings.  
NOTE: If switch drops-out before boiler reaches  
temperature or if pressure differential readings are  
below minimums shown in Table 15, check for  
cracks in hose or contact your nearest Burnham  
representative.  
4. Stop boiler, remove manometer and reconnect hoses  
to differential pressure switch. See Figures 28 and  
31.  
Figure ꢁ1: Differential Pressure Measurement  
Table 15: Differential Pressure Switch Settings  
Minimum Differential Pressure  
Boiler Model  
Sea Level to 4,999 Ft.  
1.32” w.c.  
5,000 - 10,000 Ft. Elevation  
PVG-3  
PVG-4  
PVG-5  
PVG-6  
PVG-7  
PVG-8  
PVG-9  
.80” w.c.  
.65” w.c.  
.65” w.c.  
.35” w.c.  
.30” w.c.  
.35” w.c.  
.35” w.c.  
1.17” w.c.  
1.17” w.c.  
.88” w.c.  
.80” w.c.  
.88” w.c.  
.88” w.c.  
49  
50  
51  
XI. Repair Parts  
All PVG Repair Parts may be obtained through your local Burnham Wholesale distributor. Should  
you require assistance in locating a Burnham distributor in your area, or have questions regarding  
the availability of Burnham products or repair parts, please contact Burnham Customer Service at  
(717) 481-8400 or Fax (717) 481-8408.  
5ꢀ  
[Quantity] Part Number  
Key  
No.  
Description  
PVG-3  
PVG-4  
PVG-5  
PVG-6  
PVG-7  
PVG-8  
PVG-9  
1. CASTING ASSEMBLY  
1
Section Assembly  
61707031  
61707041  
61707051  
61707061  
71707001  
61707071  
61707081  
61707091  
1A Left End Section  
1B Center Section  
1C Right End Section  
1D Slip Nipple, #3  
[1]  
[2]  
[3]  
[4]  
[5]  
[6]  
[7]  
71707003  
71707003  
71707003  
71707003  
71707003  
71707003  
71707003  
71707002  
[4]  
[6]  
[8]  
[10]  
[12]  
[14]  
[16]  
806600009 806600009 806600009 806600009 806600009 806600009 806600009  
[2]  
71107002  
[3]  
71107002  
[4]  
71107002  
[5]  
71107002  
[6]  
71107002  
[7]  
71107002  
[8]  
71107002  
1E Flue Gas Baffle  
[2]  
[2]  
[2]  
[2]  
[2]  
[2]  
[2]  
1F  
Tie Rod, ¼” -20  
100109-01  
100108-05  
100108-07  
100108-13  
100108-14  
100108-15  
100108-16  
1G Hex Nut, ¼” -20  
[4] 80860407  
5ꢁ  
54  
[Quantity] Part Number  
PVG-5 PVG-6 PVG-7  
Key  
No.  
Description  
PVG-3  
PVG-4  
PVG-8  
PVG-9  
2. BASE ASSEMBLY  
2A Base Wrapper  
71807031 71807041 71807051 71807061 71807071 71807081 71807091  
2B Base Tray  
71807032 71807042 71807052 71807062 71807072 71807082 71807092  
2C Burner Tray Assembly  
2D Base Front Panel  
61807031 61807041 61807051 61807061 61807071 61807081 61807091  
71807035 71807045 71807055 71807065 71807075 71807085 71807095  
2E Burner Access Panel  
2F Cerafelt Gasket 1/2” x 2”  
2G Cerafelt Gasket 1/2” x 2”  
2H Base Side Insulation  
2J Base Rear Insulation  
2K Base Front Insulation  
2L Base Leg Assembly  
71807036 71807046 71807056 71807066 71807076 71807086 71807096  
6206002  
6206002  
[2] 72007001  
72007031 72007041 72007051 72007061 72007071 72007081 72007091  
72007032 72007042 72007052 72007062 72007072 72007082 72007092  
[4] 6186001  
[18] 80860700  
80160044  
2M Self Tapping Screw, 1/4” -20 x 1/2”  
2N Flame Roll-out Switch  
2P Sheet Metal Screw, #8 x 3/4”  
2Q Self Tapping Screw, 10-32 x 3/8”  
80860030  
[5] 80860705  
[6] 80860705  
[4] 80860717  
[7] 80860705  
Self Tapping Screw Hex Cap,  
5/16 - 18 x 1-1/4”  
2R  
55  
[Quantity] Part Number  
PVG-5 PVG-6 PVG-7  
Key  
No.  
Description  
PVG-3  
PVG-4  
PVG-8  
PVG-9  
3. BASE ASSEMBLY  
3A Burner Cover (Natural Gas Only) 102033-03 102033-04 102033-05 102033-06 102033-07 102033-08 102033-09  
3B Manifold Support Bracket  
718070001  
[2] 80860000  
[6] 80860705  
3C Sheet Metal Screw, #8 x 1/2”  
3D Self Tapping Screw, 10-32 x 3/8”  
5ꢂ  
[Quantity] Part Number  
PVG-5 PVG-6 PVG-7  
Key  
No.  
Description  
PVG-3  
PVG-4  
PVG-8  
PVG-9  
4. FAN/CANOPY ASSEMBLY  
Canopy Assembly - Sea Level  
61107031 61107041 61107051 61107061 61107071 61107081 61107091  
4A  
Canopy Assembly - High Altitude 61107032 61107042 61107052 61107062 61107072 61107082 61107092  
4B Cerafelt  
9206005  
[4] 80861512  
[4] 808600141  
8206085  
4C U-Clip  
4D Sheet Metal Screw, #10 x 1”  
4E Fan Gasket  
4F Fan  
81161512  
4G Lock Washer, #10  
4H Machine Screw, #10-24 x 2-1/2”  
[4] 80860636  
[4] 808608982  
57  
58  
[Quantity] Part Number  
PVG-5 PVG-6 PVG-7  
Key  
No.  
Description  
PVG-3  
PVG-4  
PVG-8  
PVG-9  
5. BURNER ASSEMBLY  
Gas Valve (Natural Gas),  
Honeywell VR8204P1171  
81660282  
N/A  
Gas Valve (Natural Gas),  
Honeywell VR8304P4496  
N/A  
81660146  
N/A  
81660283  
N/A  
5A  
Gas Valve (LP Gas),  
Honeywell VR8204C3015  
Gas Valve (LP Gas),  
Honeywell VR8304P4280  
81660181  
Nipple, ½” NPT x Close  
5B  
806600040  
N/A  
N/A  
806600022  
N/A  
Nipple, ¾” NPT x Close  
Union, ½” NPT  
5C  
806604023  
N/A  
Union, ¾” NPT  
806604001  
---  
½” Gas Manifold  
5D  
82207031 82207041 82207051 82207061  
---  
---  
¾” Gas Manifold  
---  
---  
---  
---  
82207071 82207081 82207091  
[4]  
822710  
[6]  
822710  
[8]  
822710  
[10]  
822710  
[12]  
822710  
[14]  
822710  
[16]  
822710  
Burner Orifices - Natural Gas #47  
5E  
[4]  
822792  
[6]  
822792  
[8]  
822792  
[10]  
822792  
[12]  
822792  
[14]  
822792  
[16]  
822792  
Burner Orifices - LP Gas 1.20 mm  
Pilot Assembly - Natural Gas  
5F  
8236163  
8236164  
Pilot Assembly - LP Gas  
5G Pilot Burner  
100147-01  
[9]  
[3]  
[5]  
[7]  
[11]  
[13]  
[15]  
5H Main Burner  
100146-01 100146-01 100146-01 100146-01 100146-01 100146-01 100146-01  
5J Pilot Tubing  
8236122  
5K Self Tapping Screw, ¼ - 20 x ½”  
[6] 80860700  
59  
[Quantity] Part Number  
Key  
No.  
Description  
PVG-3  
PVG-4  
PVG-5  
PVG-6  
PVG-7  
PVG-8  
PVG-9  
6. CONTROL PANEL ASSEMBLY  
6A Limit, Honeywell L4080D  
100189-01  
80160155U  
Transformer/Relay, Honeywell  
6B  
R8285D  
Ignition Module, Honeywell  
S8670E3003  
6C  
100959-01  
Blower Relay, Honeywell  
R8222U1006  
6D  
80160096U  
Differential Pressure Switch  
Sea Level 0’ - 4999’  
80160762  
80160759  
80160761  
80160763  
80160760 80160759  
80160760  
80160764  
6E  
High Altitude - 5000’ - 10,000’  
80160764 80160765  
8136259  
6F Junction box  
ꢂ0  
[Quantity] Part Number  
Key  
No.  
Description  
PVG-3  
PVG-4  
PVG-5  
PVG-6  
PVG-7  
PVG-8  
PVG-9  
7. JACKET PARTS  
7A Left Side Panel  
7B Right Side Panel  
7C Rear Panel  
7D Vestibule Panel  
7E Top Panel  
60407002  
60407001  
60407033 60407043 60407053 60407063 60407073 60407083 60407093  
60407034 60407044 60407054 60407064 60407074 60407084 60407094  
60407032 60407042 60407052 60407062 60407072 60407082 60407092  
7F Front Door  
101354-03 101354-04 101354-05 101354-06 101354-07 101354-08 101354-09  
7G Jacket Cover Plate  
7H Handle  
80407001  
8056184  
7J Door Clip  
[2] 7041921  
8136048  
7K Bushing  
7L Burnham Logo  
81460099  
ꢂ1  
[Quantity] Part Number  
Key  
No.  
Description  
PVG-3  
PVG-4  
PVG-5  
PVG-6  
PVG-7  
PVG-8  
PVG-9  
8. MISCELLANEOUS PARTS CARTON  
8A Water Manifold  
80607001  
8056169  
8B Temperature/Pressure Gauge  
8C Circulator Wiring Harness  
8D Safety Relief Valve  
8E Boiler Drain Valve  
8F Vent Terminal  
6130701  
81660363  
806603061  
8110701  
8110703  
8110702  
8110704  
8G Vent Connector  
ꢂꢀ  
Important Product Safety Information  
Refractory Ceramic Fiber Product  
Warning:  
The Repair Parts list designates parts that contain refractory ceramic fibers  
(RCF). RCF has been classified as a possible human carcinogen. When  
exposed to temperatures about 1805°F, such as during direct flame contact,  
RCF changes into crystalline silica, a known carcinogen. When disturbed as a  
result of servicing or repair, these substances become airborne and, if inhaled,  
may be hazardous to your health.  
AVOID Breathing Fiber Particulates and Dust  
Precautionary Measures:  
Do not remove or replace RCF parts or attempt any service or repair work  
involving RCF without wearing the following protective gear:  
1. A National Institute for Occupational Safety and Health (NIOSH)  
approved respirator  
2. Long sleeved, loose fitting clothing  
3. Gloves  
4. Eye Protection  
• Take steps to assure adequate ventilation.  
• Wash all exposed body areas gently with soap and water after contact.  
• Wash work clothes separately from other laundry and rinse washing  
machine after use to avoid contaminating other clothes.  
• Discard used RCF components by sealing in an airtight plastic bag. RCF  
and crystalline silica are not classified as hazardous wastes in the United  
States and Canada.  
First Aid Procedures:  
• If contact with eyes: Flush with water for at least 15 minutes. Seek  
immediate medical attention if irritation persists.  
• If contact with skin: Wash affected area gently with soap and water.  
Seek immediate medical attention if irritation persists.  
• If breathing difficulty develops: Leave the area and move to a location  
with clean fresh air. Seek immediate medical attention if breathing  
difficulties persist.  
• Ingestion: Do not induce vomiting. Drink plenty of water. Seek  
immediate medical attention.  
ꢂꢁ  
Limited Warranty  
FOR RESIDENTIAL CAST IRON WATER BOILERS  
for its intended purposes and its maintenance accordance with U. S.  
Subject to the terms and conditions set forth below, U.S. Boiler™  
Co., Inc. Lancaster, pennsylvania hereby extends the following limited  
warranties to the original owner of a residential grade water boiler  
manufactured and shipped on or after July 1,1991:  
Boiler Co., Inc. recommendations and hydronics industry standards.  
These warranties will be inapplicable if the residential grade water boiler  
is used or operated over its rated capacity, is subjected to unauthorized  
modification, or is damaged as a result of being otherwise improperly  
operated or serviced including, but not limited to, damage from any of the  
following: operation with insufficient water, allowing the boiler to freeze,  
subjecting the boiler to flood conditions, and operation with unapproved  
water or fuel additives which cause deposits or corrosion.  
ONEYEAR LIMITED WARRANTY  
ON RESIDENTIAL GRADE WATER BOILERS  
U.S. Boiler Co., Inc. warrants to the original owner that its residential  
grade water boilers comply at the time of manufacture with recognized  
hydronic industry standards and requirements then in effect and will be  
free of defects in material and workmanship under normal usage for a  
period of one year from the date of original installation. If any part of a  
water boiler is found to be defective in material or workmanship during  
this one year period, U.S. Boiler Co., Inc. will, at its option, repair or  
replace the defective part.  
5. Removal and Installation: These warranties do not cover expenses  
of removal or reinstallation. The owner is responsible for the cost of  
removing and reinstalling any defective part and its replacements and all  
labor and material connected therewith.  
6. Exclusive Remedy: U.S. Boiler Co., Inc. obligation for any breach  
of these warranties is limited to the repair or replacement of its parts in  
accordance with the terms and conditions of these warranties.  
LIFETIME LIMITED WARRANTY ON HEAT EXCHANGER  
U.S. Boiler Co., Inc. warrants to the original owner that the heat  
exchanger of its residential grade water boilers will remain free from  
defects in material and workmanship under normal usage for the  
lifetime of the original owner at the original place of installation. If a  
claim is made under this warranty during the first ten years from the  
date of original installation, U.S. Boiler Co., Inc. will, at its option, repair  
or replace the heat exchanger. If a claim is made under this warranty  
after the expiration of ten years from the date of original installation,  
U.S. Boiler Co., Inc. will, at its option and upon payment of the pro-rated  
service charge set forth below, repair or replace the heat exchanger.  
The service charge applicable to a heat exchanger warranty claim is  
based upon the number of years the heat exchanger has been in service  
and will be determined as a percentage of the retail price of the heat  
exchanger model involved at the time the warranty claim is made as  
follows:  
7. Limitation of Damages: Under no circumstances shall U.S. Boiler Co.,  
Inc. be liable for incidental, indirect, special or consequential damages  
of any kind whatsoever under these warranties, including, but not limited  
to, injury or damage to persons or property and damages for loss of use,  
inconvenience or loss of time. U.S. Boiler Co., Inc. liability under these  
warranties shall under no circumstances exceed the purchase price paid  
by the owner for the residential grade water boiler involved. Some states  
do not allow the exclusion or limitation of incidental or consequential  
damages, so the above limitation or exclusion may not apply to you.  
8. Limitation of Warranties: These warranties set forth the entire  
obligation of U.S. Boiler Co., Inc. with respect to any defect in a  
residential grade water boiler and U.S. Boiler Co., Inc. shall have no  
express obligations, responsibilities or liabilities of any kind whatsoever  
other than those set forth herein. These warranties are given in lieu of all  
other express warranties.  
Years  
In Service  
ALL AppLICABLE ImpLIED WARRAnTIES, If Any, InCLUDIng  
Any WARRAnTy of mERChAnTABILITy oR fITnESS foR A  
pARTICULAR pURpoSE ARE ExpRESSLy LImITED In DURATIon  
To A pERIoD of onE yEAR ExCEpT ThAT ImpLIED WARRAnTIES,  
If Any, AppLICABLE To ThE hEAT ExChAngER In A RESIDEnTIAL  
gRADE WATER BoILER ShALL ExTEnD To ThE oRIgInAL  
oWnER foR ThE LIfETImE of ThE oRIgInAL oWnER AT ThE  
oRIgInAL pLACE of InSTALLATIon. SomE STATES Do no ALLoW  
LImITATIon on hoW Long An ImpLIED WARRAnTy LASTS, So  
ThE ABovE LImITATIon mAy noT AppLy To yoU.  
1-10  
11  
5
12  
10  
13  
15  
14  
20  
15  
25  
16  
30  
17  
35  
Service Charge  
as % of  
Retail Price  
No  
Charge  
Years  
In Service  
25 and  
above  
18  
40  
19  
45  
20  
50  
21  
55  
22  
60  
23  
65  
24  
70  
Service Charge  
as % of  
Retail Price  
75  
PROCEDURE FOR OBTAINING WARRANTY SERVICE  
In order to assure prompt warranty service, the owner is requested to  
complete and mail the attached Warranty Card within ten days after the  
installation of the boiler, although failure to comply with this request will  
not void the owner’s rights under these warranties.  
noTE: If the heat exchanger model involved is no longer available  
due to product obsolescence or redesign, the value used to establish  
the retail price will be the published price as shown in the Burnham  
hydronics Repair parts price Sheet where the heat exchanger last  
appeared or the current retail price of the then nearest equivalent heat  
exchanger.  
Upon discovery of a condition believed to be related to a defect in  
material or workmanship covered by these warranties, the owner should  
notify the installer, who will in turn notify the distributor. If this action is  
not possible or does not produce a prompt response, the owner should  
write to U.S. Boiler Co., Inc., Burnham hydronics, at p.o. Box 3079,  
Lancaster, pA 17604, giving full particulars in support of the claim.  
ADDITIONAL TERMS AND CONDITIONS  
1. Applicability: The limited warranties set forth above are extended  
only to the original owner at the original place of installation within the  
United States and Canada. These warranties are applicable only to  
water boilers designated as residential grade by U.S. Boiler Co., Inc. and  
installed in a single or two-family residence and do not apply to steam  
boilers of any kind or to commercial grade boilers.  
The owner is required to make available for inspection by U.S. Boiler  
Co., Inc. or its representative the parts claimed to be defective and, if  
requested by U.S. Boiler Co., Inc. to ship these parts prepaid to U.S.  
Boiler Co., Inc. at the above address for inspection or repair. In addition,  
the owner agrees to make all reasonable efforts to settle any disagree-  
ment arising in connection with a claim before resorting to legal remedies  
in the courts.  
2. Components manufactured by others: Upon expiration of the  
one year limited warranty on residential grade water boilers, all boiler  
components manufactured by others but furnished by U.S. Boiler Co.,  
Inc. (such as oil burner, circulator and controls) will be subject only to the  
manufacturer’s warranty, if any.  
ThIS WARRAnTy gIvES yoU SpECIfIC LEgAL RIghTS AnD  
yoU mAy ALSo hAvE oThER RIghTS WhICh vARy fRom STATE  
To STATE.  
3. proper Installation: The warranties extended by U.S. Boiler Co., Inc.  
are conditioned upon the installation of the residential grade water boiler  
in strict compliance with U.S. Boiler Co., Inc. installation instructions.  
U. S. Boiler Co., Inc. specifically disclaims liability of any kind caused by  
or relating to improper installation.  
4. proper Use and maintenance:The warranties extended by U.S. Boiler  
Co., Inc. conditioned upon the use of the residential grade water boiler  
03/03  

Black Decker BLC12650H User Manual
Bogen Communications Car Speaker FMH15T User Manual
Dice electronic Dice Electronics Carrying Case DCR 300 User Manual
Elmo Cable Box CBL CELIO2 5 User Manual
Epson Camera Accessories 800 User Manual
EverFocus 520TVL, 380TVL User Manual
JBL GTO6538 User Manual
JVC CAMESCOPE GR DVL100 User Manual
JVC DV 3 CCD GY DV5000U User Manual
JVC GR AX760 User Manual