INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
ALPINE™
CONDENSING HIGH EFFICIENCY
DIRECT VENT
GAS - FIRED HOT WATER BOILER
As an ENERGY STAR® Partner, Burnham Hydronics has determined that the Alpine™ Series meets the ENERGY
STAR® guidelines for energy efficiency established by the United States Environmental Protection Agency (EPA).
WaRning: Improper installation, adjustment, alteration, service or maintenance can cause property damage,
injury, or loss of life. For assistance or additional information, consult a qualified installer, service agency or the
gas supplier. This boiler requires a special venting system. Read these instructions carefully before installing.
Price - $5.00
101602-01R2-9/08
WaRning
This boiler requires regular maintenance and service to operate safely. Follow the instructions contained
in this manual.
improperinstallation,adjustment,alteration,serviceormaintenancecancausepropertydamage,personal
injury or loss of life. Read and understand the entire manual before attempting installation, start-up
operation, or service. installation and service must be performed only by an experienced, skilled, and
knowledgeable installer or service agency
This boiler must be properly vented.
This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate
combustion and ventilation air.
The interior of the venting system must be inspected and cleaned before the start of the heating season
and should be inspected periodically throughout the heating season for any obstructions. a clean and
unobstructed venting system is necessary to allow noxious fumes that could cause injury or loss of life
to vent safely and will contribute toward maintaining the boiler’s efficiency.
installation is not complete unless a pressure relief valve is installed into the tapping located on left side
of appliance. - See the Water Piping and Trim Section of this manual for details.
This boiler is supplied with safety devices which may cause the boiler to shut down and not re-start
without service. if damage due to frozen pipes is a possibility, the heating system should not be left
unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating
system to prevent damage if the boiler is inoperative.
This boiler contains very hot water under high pressure. Do not unscrew any pipe fittings nor attempt
to disconnect any components of this boiler without positively assuring the water is cool and has no
pressure. Always wear protective clothing and equipment when installing, starting up or servicing this
boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the
temperature and pressure of the boiler. This boiler contains components which become very hot when
the boiler is operating. Do not touch any components unless they are cool.
Boilermaterialsofconstruction,productsofcombustionandthefuelcontainalumina,silica,heavymetals,
carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause
death or serious injury and which are known to the state of California to cause cancer, birth defects and
other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing
or working nearby the appliance.
Failure to follow all instructions in the proper order can cause personal injury or death. Read all instruc-
tions, including all those contained in component manufacturers manuals which are provided with the
boiler before installing, starting up, operating, maintaining or servicing.
Keep boiler area clear and free from combustible materials, gasoline and other flammable vapors or
liquids.
all cover plates, enclosures and guards must be in place at all times.
nOTiCE
This boiler has a limited warranty, a copy of which is printed on the back of this manual. it is the responsibility
of the installing contractor to see that all controls are correctly installed and are operating properly when the
installation is complete.
ꢀ
Table of Contents
I. Product Description, Specifications
VIII. Electrical.......................................49
IX. Boiler Stacking .............................56
X. Modular Installation ....................58
XI. System Start-up ............................66
XII. Operation.....................................72
XIII. Service and Maintenance..............84
XIV. Troubleshooting ...........................88
XV. Repair Parts..................................91
and Dimensional Data....................4
II. Pre-Installation...............................8
III. Unpacking Boiler ...........................9
IV. Venting.........................................10
V. Condensate Disposal ....................29
VI. Water Piping and Trim .................31
VII. Gas Piping....................................46
I. Product Description, Specifications and Dimensional Data
Alpine™ Series boilers are condensing high efficiency
gas-fired direct vent hot water boilers designed for use
in forced hot water space or space heating with indirect
domestic hot water heating systems, where supply water
temperature does not exceed 210°F. These boilers have
special coil type stainless steel heat exchangers, constructed,
tested and stamped per Section IV ‘Heating Boilers’ of
ASME Boiler and Pressure Vessel Code, which provide a
maximum heat transfer and simultaneous protection against
flue gas product corrosion. These boilers are not designed
for use in gravity hot water space heating systems or
systems containing significant amount of dissolved oxygen
(swimming pool water heating, direct domestic hot water
heating, etc.).
Table 1: Dimensional Data (See Figures 1a & 1B)
Boiler Model
Dimension
ALP080
ALP105
ALP150
ALP210
ALP285
ALP399
28-7/8
(734)
A - Inch
12-9/16
14
19-11/16
23-15/16
21-13/16
(554)
(mm)
(320)
(356)
(500)
(608)
B - Inch
5-5/8
5-13/16
7-5/16
6-3/16
(mm)
(142)
(147)
(185)
(157)
C - Inch
7-5/16
14-1/8
13-1/16
(mm)
(186)
(358)
(332)
D - Inch
9-5/16
10-3/4
16-7/16
17-1/8
18
23-3/4
(mm)
(237)
(273)
(417)
(435)
(456)
(602)
E - Inch
5-15/16
12-1/4
15-13/16
(mm)
(151)
(312)
(402)
Gas Inlet F
(FPT)
1/2”
1”
3/4”
1”
Return G
(FPT)
1-1/4”
1-1/4”
1-1/2”
1-1/2”
Supply H
(FPT)
1”
* Factory Provided Socket End Compression Pipe Joining Clamp
Condensate Drain J *
for 3/4” Schedule 40 PVC Pipe
Boiler Two Pipe
CPVC/PVC Vent Connector
- Inch
3 x 3
3 x 4
4 x 4
Approx. Shipping Weight
(LBS)
137
155
182
206
256
304
ꢁ
5
6
Table 2a: Rating Data - Models aLP080 thru aLPꢀ99 (0 to 2000 Feet Elevation above Sea Level)
alpine Series gas-Fired Boilers
Input
(MBH)
Heat Transfer
Area
Net I=B=R
Ratings
Water (MBH)
Thermal
Efficiency
(%)
Boiler Water
Volume
* Model
Number
** Output
(MBH)
AFUE
%
Combustion
Efficiency (%)
(Gal.)
(Sq. Ft.)
Min. Max.
ALP080
ALP105
ALP150
ALP210
ALP285
ALP399
16
21
30
42
57
80
80
73
96
63
83
95
95
95
95
95
0.6
0.7
1.3
1.7
2.4
3.4
7.3
9.1
105
150
210
285
399
138
194
265
377
120
169
230
328
16.4
21.8
29.1
41.8
94.1
94.5
* Add Suffix “N” for Natural Gas or Suffix “P” for LP Gas Models.
notes: ** DOE Heating Capacity (ALP080 thru ALP285); Gross Output (ALP399)
Maximum Working Pressure, Water - 30 PSI Shipped from Factory (std.); 50 PSI - Optional (ALP080 thru ALP285)
Maximum Working Pressure, Water - 50 PSI Shipped from Factory (std.); (ALP399)
Maximum Allowable Temperature, Water - 210°F
Boilers are factory shipped as Natural Gas builds and have to be field adjusted for LP gas application. Refer to ‘System Start-
Up Section of this manual for detailed procedure.
Ratings shown are for installations at sea level and elevations up to 2000 Feet. For elevations above 2000 Feet, ratings should be
reduced at the rate of four percent (4%) for each 1000 Feet above sea level.
Table 2B: Rating Data - Models aLP080 thru aLPꢀ99 (2001 to ꢂ000 Feet Elevation above Sea Level)
alpine Series gas-Fired Boilers
Input
(MBH)
Net I=B=R
Ratings
Water (MBH)
Thermal
Efficiency
(%)
Boiler Water
Volume
Model
Number *
** Output
(MBH)
AFUE
%
Combustion
Efficiency (%)
Heat Transfer
Area (Sq. Ft.)
(Gal.)
Min. Max.
ALP080
ALP105
ALP150
ALP210
ALP285
ALP399
27
35
50
70
57
80
80
73
96
63
83
95
95
95
95
95
0.6
0.7
1.3
1.7
2.4
3.4
7.3
9.1
105
150
210
285
399
138
194
265
377
120
169
230
328
16.4
21.8
29.1
41.8
94.1
94.5
* Add Suffix “N” for Natural Gas or Suffix “P” for LP Gas Models.
notes: ** DOE Heating Capacity (ALP080 thru ALP285); Gross Output (ALP399)
Maximum Working Pressure, Water - 30 PSI Shipped from Factory (std.); 50 PSI - Optional
Maximum Allowable Temperature, Water - 210°F
Boilers are factory shipped as Natural Gas builds and have to be field adjusted for LP gas application. Refer to ‘System Start-
Up Section of this manual for detailed procedure.
For elevations above 2000 Feet, ratings should be reduced at the rate of four percent (4%) for each 1000 Feet above sea level.
ꢂ
ii. Pre-installation
WaRning
2. Access is provided to the condensate trap located
underneath the heat exchanger.
if you do not follow these instructions exactly,
a fire or explosion may result causing property
damage or personal injury.
D. Install on level floor. For basement installation provide
a solid base such as concrete, if floor is not level or if
water may be encountered on floor around boiler. Floor
must be able to support weight of boiler, water and all
additional system components.
DangER
E. Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during boiler operation
and service (circulator replacement, condensate trap,
control replacement, etc.).
Do not install boiler where gasoline or other
flammable vapors or liquids, or sources of
hydrocarbons (i.e. bleaches, cleaners, chemicals,
sprays, paint removers, fabric softeners, etc.) are
used or stored.
F. Provide combustion and ventilation air in accordance
with applicable provisions of local building codes,
or: USA - National Fuel Gas Code, NFPA 54/ANSI
Z223.1, Air for Combustion and Ventilation;
Canada - Natural Gas and Propane Installation Code,
CAN/CSA-B149.1, Venting Systems and Air Supply for
Appliances.
nOTiCE
Due to the low water content of the boiler, mis-
sizing of the boiler with regard to the heating
system load will result in excessive boiler cycling
and accelerated component failure. Burnham
DOES nOT warrant failures caused by mis-sized
boiler applications. DO nOT oversize the boiler to
the system. Modular boiler installations greatly
reduce the likelihood of boiler oversizing.
WaRning
Adequate combustion and ventilation air must
be provided to assure proper combustion.
G. The boiler should be located so as to minimize the
length of the vent system. The PVC combustion
air piping, or the optional concentric vent piping,
containing integral combustion air inlet piping, must
terminate where outdoor air is available for combustion
and away from areas that may contaminate combustion
air. In particular, avoid areas near chemical products
containing chlorines, chloro/fluorocarbons, paint
removers, cleaning solvents and detergents. Avoid
areas containing saw dust, loose insulation fibers, dry
wall dust etc.
A. Installation must conform to the requirements of the
authority having jurisdiction. In the absence of such
requirements, installation must conform to the National
Fuel Gas Code, NFPA 54/ANSI Z223.1, and/or CAN/
CSA B149.1 Installation Codes.
B. Appliance is design certified for installation on
combustible flooring. Do not install boiler on
carpeting.
C. Provide clearance between boiler jacket and
combustible material in accordance with local fire
ordinance. Refer to Figure 2 for minimum listed
clearances from combustible material. Recommended
service clearance is 24 inches from left side, front, top
and rear of the boiler. Recommended front clearance
may be reduced to the combustible material clearance
providing:
CaUTiOn
avoid operating this boiler in an environment
where saw dust, loose insulation fibers, dry wall
dust, etc. are present. if boiler is operated under
these conditions, the burner interior and ports
must be cleaned and inspected daily to insure
proper operation.
1. Access to boiler front is provided through a door or
removable front access panel.
8
Figure 2: Clearances To Combustible and non-combustible Material
iii. Unpacking Boiler
CaUTiOn
D. Remove boiler from cardboard positioning sleeve on
shipping skid.
Do not drop boiler.
WaRning
A. Move boiler to approximate installed position.
B. Remove all crate fasteners.
installation of this boiler should be undertaken
only by trained and skilled personnel from a
qualified service agency.
C. Lift and remove outside container.
E. Move boiler to its permanent location.
9
iV. Venting
WaRning
Failure to vent this boiler in accordance with these instructions could cause products of combustion to
enter the building resulting in severe property damage, personal injury or death.
Do not interchange vent systems or materials unless otherwise specified.
The use of thermal insulation covering pipe and fittings is prohibited.
Do not use a barometric damper, draft hood or vent damper with this boiler.
The use of CPVC is required when venting in chase ways and through interior wall penetrations.
Do not locate vent termination where exposed to prevailing winds. Moisture and ice may form on
surface around vent termination. To prevent deterioration, surface must be in good repair (sealed,
painted, etc.).
Do not locate vent termination where chlorines, chloro/fluorocarbons (CFC’s), petroleum distillates,
detergents, volatile vapors or other chemicals are present. Severe boiler corrosion and failure will
result.
The use of cellular core PVC (aSTM F891) is prohibited.
Do not locate vent termination under a deck.
Do not reduce size of vent/combustion air pipe diameter.
When installing vent pipe through chimney, no other appliance can be vented into the chimney.
Do not allow low spots in the vent where condensate may pool.
4. Place in operation the appliance being inspected.
Follow the Lighting (or Operating) Instructions.
Adjust thermostat so appliance will operate
continuously.
A. Vent Guidelines Due to Removal of an Existing
Boiler
For installations not involving the replacement of an
existing boiler, proceed to Step B.
5. Test for spillage at the draft hood relief opening
after five (5) minutes of main burner operation. Use
the flame of a match or candle, or smoke from a
cigarette, cigar or pipe.
When an existing boiler is removed from a common
venting system, the common venting system is likely
to be too large for proper venting of the remaining
appliances. At the time of removal of an existing
boiler, the following steps shall be followed with each
appliance remaining connected to the common venting
system placed in operation, while the other appliances
remaining connected to the common venting system are
not in operation:
6. After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers and
any other gas burning appliance to their previous
conditions of use.
1. Seal any unused openings in the common venting
system.
7. Any improper operation of the common venting
system should be corrected so the installation
conforms with the National Fuel Gas Code, NFPA
54/ANSI Z223.1. When resizing any portion of the
common venting system, the common venting
system should be resized to approach the minimum
size as determined using the appropriate tables in
Part II in the National Fuel Gas Code, NFPA 54/
ANSI Z223.1.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion, and other
deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and
windows and all doors between the space in which
the appliances remaining connected to the common
venting system are located and other spaces of the
building. Turn on clothes dryers and any appliance
not connected to the common venting system.
Turn on any exhaust fans, such as range-hoods and
bathroom exhausts, so they will operate at maximum
speed. Do not operate a summer exhaust fan. Close
fireplace dampers.
B. General Guidelines
1. Vent system installation must be in accordance
with National Fuel Gas Code, NFPA 54/ANSI
Z221.3 or applicable provisions of local building
codes. Contact local building or fire officials about
restrictions and installation inspection in your area.
10
2. The Alpine™ is designed to be installed as a Direct
Vent boiler. The air for combustion is supplied
directly to the burner enclosure from outdoors and
flue gases are vented directly outdoors (through wall
or roof).
See Table 6 for complete list of Burnham Vent
System Components. Use single wall thimble
[Burnham Part No. 102180-01 (3”), 102181-01 (4”)]
when penetrating a combustible wall for vent only.
1. Horizontal vent pipe must maintain a minimum ¼
inch per foot slope down towards boiler.
3. The following combustion air/vent system options
are approved for use with the Alpine™ boilers:
2. Use noncombustible ¾ inch pipe strap to support
horizontal runs and maintain vent location and slope
while preventing sags in pipe. Maximum support
spacing is four (4) feet. Avoid low spots where
condensate may pool. Do not penetrate any part of
the vent system with fasteners.
i. Two-Pipe CPVC/PVC Gas Vent/Combustion
Air System (factory standard) - separate
CPVC/PVC pipe serves to expel products of
combustion and separate PVC pipe delivers fresh
outdoor combustion air. Refer to Paragraph C
through F for specific details.
WaRning
ii. Combination Concentric Gas Vent/
Combustion Air Inlet (optional) - the assembly
consists of inner fire resistant polypropylene
vent pipe and outer steel pipe casing. The inner
pipe serves as conduit to expel products of
combustion, while outdoor fresh combustion air
is drawn through the space between the inner and
outer pipes. Refer to Paragraphs G through P for
specific details.
all condensate that forms in the vent must be
able to drain back to the boiler.
3. Vent length restrictions are based on equivalent
length of vent/combustion air pipe (total length
of straight pipe plus equivalent length of fittings).
Maximum vent/combustion air lengths are listed in
Table 7. Do not exceed maximum vent/combustion
air lengths. Table 6 lists equivalent lengths for
fittings. Do not include vent/combustion air
terminals in equivalent feet calculations. See
“Combustion Air/Vent, Equivalent Length Work
Sheet”.
4. Refer to Table 3 and the appropriate drawings to
determine the proper configuration of either factory
standard or optional venting/combustion air system
details.
C. The following information is applicable for Two-
Pipe CPVC/PVC Gas Vent/Combustion Air System
(factory standard).
4. Provide minimum service clearance between boiler
back and concentric vent exiting through outside
wall, for concentric vent installation/replacement
and/or flue temperature sensor service/replacement.
WaRning
5. Do not install venting system components on
the exterior of the building except as specifically
required by these instructions. The vent termination
location is restricted as follows (refer to Figures 6
and 9):
all CPVC vent components (supplied with boiler)
must be used for near-boiler vent piping before
transitioning to Schedule ꢁ0 PVC pipe (aSTM
2665) components for remainder of vent system.
CPVC vent components must be used prior to
exit of any closet or confined space.
a. Minimum twelve (12) inches above grade plus
normally expected snow accumulation level, or
seven (7) feet above grade, if located adjacent
Table ꢀ: Combustion air/Vent System Options
additional Components
installation
Option
Description
Vent Kit
included with Drawing and
Required
Boiler
Specification
Direct Vent (sealed combustion) with both the vent pipe and
combustion air pipe terminating horizontally (through a sidewall)
with individual penetrations for the vent and combustion air
piping and terminals.
TWO-PiPE
CPVC/PVC
HORizOnTaL
no
no
See Table ꢁ
See Figure 6
Direct Vent (sealed combustion) with both the vent pipe and
combustion air pipe terminating vertically (through the roof) with
individual penetrations for the vent and combustion air piping
and terminals.
TWO-PiPE
CPVC/PVC
VERTiCaL
See Figures
9 and 10
See Table ꢁ
COnCEnTRiC
HORizOnTaL
Direct Vent (sealed combustion) the concentric vent pipe
terminates horizontally (through a sidewall).
no
See Table 9
See Figure 1ꢀ
COnCEnTRiC
VERTiCaL
Direct Vent (sealed combustion) the concentric vent pipe
terminates vertically (through the roof).
Yes
See Table 9
See Figure 19
11
Table ꢁ: Vent System Components included with Boiler
Quantity
Part
Vent System Components
Number
ALP080 & ALP105 ALP150 & ALP210 ALP285 & ALP399
(P/N 102189-01)
(P/N 102189-02)
(P/N 102189-03)
3” Schedule 40 PVC Tee Combustion Air/Vent Terminal
4” Schedule 40 PVC Tee Combustion Air/Vent Terminal
3” Stainless Steel Rodent Screens
102190-01
102190-02
102191-01
102191-02
102193-01
102193-02
102192-01
102192-02
102195-01
102194-01
102188-01
102183-01
102183-02
102183-03
102185-01
102185-02
102153-01
2
---
2
1
1
---
2
1
---
2
4” Stainless Steel Rodent Screens
---
1
1
3” x 30” Schedule 40 CPVC Pipe
1
---
1
4” x 30” Schedule 40 CPVC Pipe
---
1
---
1
3” Schedule 80 CPVC 90° Elbow
---
1
4” Schedule 80 CPVC 90° Elbow
---
1
---
1
8 oz. Bottle of Transition Cement
1
8 oz. Bottle of Primer
1
1
1
Burnham Vent Supplement Manual
1
1
1
Two Pipe Vent System Connector for CPVC/PVC
Two Pipe Vent System Connector for CPVC/PVC
Two Pipe Vent System Connector for CPVC/PVC
Two Pipe Vent System Connector for CPVC/PVC Gasket
Two Pipe Vent System Connector for CPVC/PVC Gasket
Silicone Vent Sensor Cap
1
---
1
---
---
1
---
---
1
---
1
---
1
---
1
---
1
1
Table 5: Clearances from Vent Piping to Combustible Material
Minimum Clearance To
Combustible Material, Inches
Vent Pipe
Pipe Direction
Enclosure
CPVC/PVC Venting
Vertical or Horizontal
Enclosed at all Sides
1” Vent/0” Combustion Air
Table 6: Burnham Vent System and Combustion air System Components
Vent System Component
3” Schedule 40 CPVC Pipe x 30 Inches
4” Schedule 40 CPVC Pipe x 30 Inches
3” Schedule 80 CPVC 90° Elbow
Equivalent Length (Ft.)
Combustion Air
System Component
(Parts by Others)
Equivalent
Feet of Pipe*
2.5
2.5
5
3” or 4” ID Pipe x 1 Ft.
3” or 4” ID Pipe x 2 Ft.
3” or 4” ID Pipe x 4 Ft.
3” or 4” ID Pipe x 5 Ft.
3” or 4” 90° Elbow
1
2
4
5
5
5
4” Schedule 80 CPVC 90° Elbow
5
Maximum Number of 90’s and Straight Pipe
# of 90’s
1
2
3
4
5
6
7
8
9
10
10
Vent Pipe
3” or 4” 45° Elbow
Feet of Pipe 55
50
45
40
35
30
25
20
15
*Equivalent Feet of Pipe Based on
Standard 4” PVC Design
# of 90’s
1
2
3
4
5
6
7
8
9
10
10
Combustion
Air Pipe
Feet of Pipe 55
50
45
40
35
30
25
20
15
This distance may be reduced if equipment is
protected from damage due to condensation or
vapor by enclosure, overhangs, etc.
to public walkway. Do not install over public
walkway where local experience indicates
appliance flue gas vapor or condensate creates a
nuisance or hazard.
e. Minimum twelve (12) inches from overhang or
corner of building.
b. Minimum three (3) feet above any forced
combustion air located within ten (10) feet.
6. Enclose vent passing through occupied or
unoccupied spaces above the boiler with material
having a fire resistance rating of at least equal to the
rating of the adjoining floor or ceiling. Maintain
minimum clearances to combustible materials. See
Figure 2 and Table 5 for details.
c. Direct Vent - Minimum one (1) foot below, one
(1) foot horizontally from, or one (1) foot above
any door, window, or gravity air inlet.
d. Minimum four (4) feet horizontally from electric
meters, gas meters, regulators, and relief valves.
12
Table ꢂ: Vent/Combustion air Pipe Length
3” Combustion Air Pipe
(Equivalent Length)
4” Combustion Air Pipe
(Equivalent Length)
3” Vent Pipe
(Equivalent Length)
4” Vent Pipe
(Equivalent Length)
Boiler
Model
Min.
Max.
60 Ft.
60 Ft.
---
Min.
---
Max.
---
Min.
21-7/8 In.
21-7/8 In.
21-7/8 In.
21-7/8 In.
---
Max.
60 Ft.
60 Ft.
60 Ft.
60 Ft.
---
Min.
---
Max.
---
ALP080
ALP105
ALP150
ALP210
ALP285
ALP399
21-7/8 In.
21-7/8 In.
---
---
---
---
---
---
---
---
21-7/8 In.
21-7/8 In.
32 In.
32 In.
60 Ft.
60 Ft.
60 Ft.
60 Ft.
---
---
---
---
---
---
32 In.
32 In.
60 Ft.
60 Ft.
---
---
---
Combustion Air/Vent, Equivalent Length Work Sheet
This sheet is supplied to assist in vent/combustion air, equivalent length calculating
Combustion air
Vent
90° elbow(s) PVC
Supplied 30” straight CPVC
Length ft. = 2.5
Quantity =
x 5’ =
x 2.5’ =
x 1 =
equiv. ft. a.
equiv. ft. b.
equiv. ft. c.
x 1 =
2.5
5
equiv. ft. a.
equiv. ft. b.
equiv. ft. c.
equiv. ft. d.
45° elbow(s) PVC
Supplied 90° elbow CPVC
Quantity =
Quantity =
1
x 5’ =
x 5’ =
Straight pipe PVC
90° elbow(s) PVC
Length ft. =
Quantity =
45° elbow(s) PVC
Quantity =
x 2.5’ =
x 1 =
Straight pipe PVC
Length ft. =
equiv. ft. e.
equiv. ft.
Total*
a.+b.+c. =
equiv. ft.
Total*
a.+b.+c.+d.+e.=
* Total cannot exceed 60 equiv. ft. length.
Vent and combustion air terminals do not count towards total equiv. ft.
Note: For one or two family dwellings, fire
resistance rating requirement may not need to be
met, but is recommended.
vent connector mounting hardware - six (6) #8 x ½”
black oxide round head Phillips sheet metal screws - are
shipped inside Miscellaneous Part Carton.
7. Plan venting system to avoid possible contact with
plumbing or electrical wires. Start at vent connector
at rear of boiler and work towards vent termination.
1. Remove the vent connector and gasket from the vent
carton.
2. Locate six mounting screws.
8. Design the Vent System to allow a 3/8” of thermal
expansion per 10 feet of CPVC/PVC pipe. Runs of
20 ft. or longer that are restrained at both ends must
use an offset or expansion loop. Refer to Figure 3.
3. Position the vent connector and gasket onto jacket
combination rear/bottom panel and insert vent
connector inner stainless steel vent pipe into the heat
exchanger vent outlet.
9. Follow all manufacturer instructions and warnings
when preparing pipe ends for joining and using the
primer and the cement.
4. Align vent connector plate and gasket clearance
holes with rear/bottom panel engagement holes; then
secure the collar and gasket to rear/bottom panel
with six mounting screws. See Figure 4.
D. Installation of Two-Pipe CPVC/PVC Gas Vent/
5. Flue temperature sensor, factory attached to the
boiler wiring harness, is secured to the boiler rear/
bottom panel with tape.
Combustion Air System Connector
The boiler two pipe vent system connector for CPVC/
PVC and gasket are shipped inside the vent carton. The
1ꢀ
Figure ꢀ: Expansion Loop and Offset
6. Remove the Silicone flue sensor cap from the vent
b. Clean all vent and combustion air pipe joints
with primer and secure with transition cement,
(8 oz. bottle of primer and 8 oz. bottle of
transition cement supplied with boiler). Follow
the instructions provided on the primer and
cement.
carton and press onto the two pipe vent system
connector for CPVC/PVC sensor port. Remove
the tape holding the flue sensor and insert the flue
temperature sensor into the flue sensor plug until it
is firmly engaged. See Figure 4.
7. Near-Boiler Vent Piping (see Figure 5):
E. CPVC/PVC Horizontal Venting System
See Figures 3 thru 8.
WaRning
Vent Piping - Horizontal
all CPVC vent components (supplied with boiler)
must be used for near-boiler vent piping before
transitioning to Schedule ꢁ0 PVC pipe (aSTM
2665) components for remainder of vent system.
1. See Paragraph D for instructions on attaching the
vent system connector to the boiler.
2. Do not exceed maximum vent length. Refer to
Table 7 for pipe diameters and allowable lengths.
3. Horizontal vent pipe must maintain a minimum ¼
inch per foot slope down towards boiler.
a. All CPVC vent components (supplied with
boiler), 30” straight and 90° elbow, must be
used for near-boiler piping before transitioning
to Schedule 40 PVC (ASTM 2665) pipe
components for remainder of vent system.
The CPVC 30” straight section may be cut to
accommodate desired vent configuration for
near-boiler piping, provided both pieces are used
in conjunction with the CPVC 90° elbow, before
any PVC components are used. Ensure that the
CPVC elbow is the first elbow used in the vent
system as it exits the boiler.
4. Use appropriately designed thimbles when passing
through combustible walls (thimble use is optional
for noncombustible walls). Insert thimble through
wall from outside. Secure outside flange to wall
with nails or screws, and seal ID, OD and vent holes
with sealant material. Install inside flange to inside
wall, secure with nails or screws, and seal with
sealant material.
5. For noncombustible wall application when thimble
is not used, size opening such that a minimal
clearance is obtained.
1ꢁ
Figure ꢁ: Field installation of Two Pipe Vent System Connector for CPVC/PVC
Figure 5: near-Boiler Vent/Combustion air Piping
6. Install Rodent Screen and Vent Terminal (supplied
3. Horizontal combustion air pipe must maintain a
minimum ¼ inch per foot slope down towards
terminal, when possible. If not, slope toward boiler.
with boiler), see Figure 8 for appropriate
configuration.
7. Apply sealant between vent pipe and opening/
thimble to provide weather-tight seal. Sealant
should not restrain the expansion of the vent pipe.
4. It is strongly recommended to locate the combustion
air terminal on the same wall as the vent termination
to prevent nuisance boiler shutdowns. Combustion
air terminal can be installed closer to wall than vent.
Combustion Air Piping - Horizontal
1. See Paragraph D for instructions on attaching the
5. Start at vent connector (rear boiler jacket) and work
towards the combustion air terminal.
vent system connector to the boiler.
2. Do not exceed maximum combustion air length.
Refer to Table 7 for pipe diameters and allowable
lengths.
6. Size combustion air wall penetration to allow easy
insertion of combustion air piping.
15
7. Install Rodent Screen and Combustion Air Terminal
(supplied with boiler), see Figure 8 for appropriate
configuration.
8. Apply sealant between vent pipe and opening to
provide weather-tight seal
F. CPVC/PVC Vertical Venting System
Refer to Figures 3, 4, 5, 8, 9 & 10.
nOTiCE
Roof penetrations require the use of roof flashing
and storm collar that are not supplied with boiler.
Vent Piping - Vertical
1. See Paragraph D for instructions on attaching the
vent system connector to the boiler.
2. Do not exceed maximum vent length. Refer to
Table 7 for pipe diameters and allowable lengths.
3. Horizontal vent pipe must maintain a minimum ¼
inch per foot slope down towards boiler.
4. Install fire stops where vent passes through floors,
ceilings or framed walls. The fire stop must close
the opening between the vent pipe and the structure.
5. Whenever possible, install vent straight through the
roof. Refer to Figures 9 and 10.
Figure 6 : Direct Vent - Side Wall Terminations
Figure ꢂ: Location of Vent Terminal Relative to Windows, Doors, grades,
Overhangs, Meters and Forced air inlets (Combustion air Terminal not shown)
16
Figure 8: Rodent Screen installation
a. Size roof opening to maintain minimum
clearance of 1 inch from combustible materials.
b. Extend vent pipe to maintain minimum vertical
and horizontal distance of twelve (12) inches
from roof surface. Allow additional vertical
distance for expected snow accumulation.
Provide brace as required.
CaUTiOn
Vertical venting requires the use of roof flashing
and a storm collar to prevent moisture from
entering the structure.
c. Install storm collar on vent pipe immediately
above flashing. Apply Dow Corning Silastic 732
RTV Sealant between vent pipe and storm collar
to provide weather-tight seal.
6. Install Rodent Screen and Vent Terminal (supplied
with boiler), see Figure 8 for appropriate
configuration.
Figure 9: Direct Vent - Vertical Terminations
Figure 10: Direct Vent - Vertical Terminations with Sloped Roof
Extend vent/combustion air piping to maintain minimum vertical (‘X’) and minimum horizontal (‘Y’) distance of
twelve (12) inches (18 inches Canada) from roof surface. allow additional vertical (‘X’) distance for expected
snow accumulation.
1ꢂ
7. Brace exterior piping if required.
Vent Piping - Snorkel
1. See Paragraph D for instructions on attaching the
Combustion Air Piping - Vertical
1. See Paragraph D for instructions on attaching the
vent system connector to the boiler.
vent system connector to the boiler.
2. Do not exceed maximum vent length. Refer to
Table 7 for pipe diameters and allowable lengths.
2. Do not exceed maximum combustion air length.
Refer to Table 7 for pipe diameters and allowable
lengths.
3. Horizontal vent pipe must maintain a minimum ¼
inch per foot slope down towards boiler
3. Horizontal combustion air pipe must maintain a
minimum ¼ inch per foot slope down towards
boiler.
4. After penetrating wall/thimble, install a Schedule
40 PVC 90° elbow so that the elbow leg is in the up
direction.
4. Locate combustion air termination on the same roof
location as the vent termination to prevent nuisance
boiler shutdowns. Combustion air terminal can be
installed closer to roof than vent.
5. Install maximum vertical run of seven (7) feet of
Schedule 40 PVC vent pipe. See Figure 11.
5. Start at vent connector on burner enclosure (rear
boiler jacket) and work towards the combustion air
terminal.
6. Size roof opening to allow easy insertion of
combustion air piping and allow proper installation
of flashing and storm collar to prevent moisture
from entering the structure.
a. Use appropriately designed vent flashing
when passing through roofs. Follow flashing
manufacturers’ instructions for installation
procedures.
b. Extend combustion air pipe to maintain
minimum vertical and horizontal distance of
twelve (12) inches from roof surface. Allow
additional vertical distance for expected snow
accumulation. Provide brace as required.
c. Install storm collar on combustion air pipe
immediately above flashing. Apply Dow
Corning Silastic 732 RTV Sealant between
combustion air pipe and storm collar to provide
weather-tight seal.
Figure 11: Direct Vent - Optional Side Wall
Snorkel Terminations
6. At top of vent pipe length install another PVC 90°
elbow so that elbow leg is opposite the building’s
exterior surface.
7. Install Rodent Screen and Combustion Air Terminal
(supplied with boiler), see Figure 8 for appropriate
configuration.
8. Brace exterior piping if required.
7. Install Rodent Screen and Vent Terminal (supplied
with boiler), see Figure 8 for appropriate
configuration.
G. Optional Snorkel CPVC/PVC Horizontal Vent
System
8. Brace exterior piping if required.
Refer to Figures 3, 4, 5, 7, 8 and 11.
This installation will allow a maximum of seven (7) feet
vertical exterior run of the vent/combustion air piping
to be installed on the CPVC/PVC horizontal venting
application (Section E).
Combustion Air Piping - Snorkel
1. See Paragraph D for instructions on attaching the
vent system connector to the boiler.
2. Do not exceed maximum combustion air length.
Refer to Table 7 for pipe diameters and allowable
lengths.
nOTiCE
Exterior run to be included in equivalent vent/
combustion air lengths.
3. Horizontal combustion air pipe must maintain a
minimum ¼ inch per foot slope down towards
terminal, when possible. If not, slope toward boiler.
4. After penetrating wall, install a Schedule 40 PVC
90o elbow so that elbow leg is in the up direction.
18
2. Remove the collar from the bag and set aside.
3. Locate and remove six mounting screws.
5. Install maximum vertical run of seven (7) feet of
Schedule 40 PVC vent pipe. See Figure 11.
6. At top of vent pipe length install another PVC 90°
elbow so that elbow leg is opposite the building’s
exterior surface.
4. Position the Collar onto jacket combination rear/
bottom panel and insert collar inner stainless steel
vent pipe into the heat exchanger vent outlet.
7. Install Rodent Screen and Combustion Air Terminal
(supplied with boiler), see Figure 8 for appropriate
configuration.
5. Align collar plate clearance holes with rear/bottom
panel engagement holes; then secure the collar to
rear/bottom panel with six mounting screws. See
Figure 12.
8. Brace exterior piping if required.
6. Flue temperature sensor, factory attached to the
boiler wiring harness, is secured to the boiler rear/
bottom panel with tape.
H. The following information is applicable for
Combination Concentric Gas Vent/Combustion air
System (optional).
7. Remove the tape and push the sensor rubber plug
into Concentric Vent Collar sensor port until the
plug is securely engaged. See Figure 12.
I. Field Installation of Boiler Concentric Vent Collar
The Boiler Concentric Vent Collar is shipped inside the
boiler in plastic bag. The Collar mounting hardware
- six (6) #8 x ½” black oxide round head Phillips sheet
metal screws - are shipped inside Miscellaneous Part
Carton.
The installation of the Concentric Vent Collar is now
completed.
J. General Guidelines - Concentric Venting
1. Release four side draw latches and remove boiler
lower front door assembly to gain access to the Vent
Collar.
1. Vent system installation must be in accordance
with National Fuel Gas Code, NFPA 54/ANSI
Z221.3 or applicable provisions of local building
Table 8: Concentric Vent Components
Component
Part Number
Component Description
90° Elbow – Long Radius
Size
Equivalent Vent
Length, Ft
5.5
Comments
101493-01
101491-01
101163-01
101162-01
101485-01
101808-01
101495-01
101496-01
101497-01
101492-01
101498-01
101548-01
101549-01
101550-01
101551-01
101553-01
101809-01
101557-01
101558-01
101559-01
101560-01
101561-01
notes:
80/125 mm
80/125 mm
80/125 mm
80/125 mm
80/125 mm
80/125 mm
80/125 mm
80/125 mm
80/125 mm
80/125 mm
80/125 mm
100/150 mm
100/150 mm
100/150 mm
100/150 mm
100/150 mm
100/150 mm
100/150 mm
100/150 mm
100/150 mm
100/150 mm
100/150 mm
45° Elbow - Long Radius
3.0
Cut -To-Length Extension, 500 mm (19-1/2”)
Cut -To-Length Extension, 1000 mm (39”)
Fixed Extension, 2000 mm (78”)
Horizontal (Wall) Terminal
1.63
3.25
3.25
*NA
*NA
**Can be cut
**Can be cut
***Must not be cut
Supplied with boiler
See Note 1
Vertical Roof Terminal
Flat Roof Flashing
Sloped Roof Flashing
See Note 2
See Note 3
Support Elbow with Chimney Chase Bracket
Hanger Wall Bracket
8.5
90° Elbow – Long Radius
8.0
3.0
45° Elbow - Long Radius
1 Cut -To-Length Extension, 500 mm (19-1/2”)
Cut -To-Length Extension, 1000 mm (39”)
Fixed Extension, 2000 mm (78”)
Horizontal (Wall) Terminal
1.63
3.25
6.5
** Can be cut
** Can be cut
*** Must not be cut
Supplied with boiler
See Note 1
* NA
* NA
Vertical (Roof) Terminal
Flat Roof Flashing
Sloped Roof Flashing
See Note 2
See Note 3
Support Elbow with Chimney Chase Bracket
Hanger Wall Bracket
10.0
* NA – do not include vent terminal into total vent length calculations.
** These sections have plain male end and beaded female end. See Figure 11 for details.
*** These sections have beaded male end and beaded female end. See Figure 12 for details.
1. Vertical terminal can be used with either of the roof flashings listed beneath it.
2. Sloped roof flashing suitable for roof angles between 25° and 45°.
3. Used at base of vertical run inside unused masonry chimney.
19
Figure 12: Field installation of Boiler Concentric Vent Collar
codes. Contact local building or fire officials about
restrictions and installation inspection in your area.
5. Provide and maintain vent pipe minimum clearances
to combustible material. See Figure 2 and Table 10
for details.
2. Horizontal vent pipe must maintain a minimum ¼
inch per foot slope towards the boiler.
6. Provide minimum service clearance between boiler
back and concentric vent exiting through outside
wall, for concentric vent installation/replacement
and/or flue temperature sensor service/replacement,
as follows:
3. Use noncombustible ¾ inch pipe strap to support
horizontal runs and maintain vent location and
slope while preventing sags in pipe. Do not restrict
thermal expansion or movement of vent system.
Maximum support spacing is five (5) feet. Do not
penetrate any part of the vent system with fasteners.
a. For horizontal venting where supplied
Concentric Vent Terminal is attached directly to
installed Boiler Concentric Vent Collar - 6 inches
4. Vent length restrictions are based on equivalent
length of vent pipe i.e. total length of straight pipe
plus equivalent length of fittings. See Table 11
for specified vent length details. Do not exceed
maximum vent length. Table 8 lists available
concentric vent components and includes equivalent
vent length for fittings. Do not include vent terminal
into total vent length calculations.
b. For vertical venting where optional Concentric
Vent 90° long radius elbow is attached to
installed Boiler Concentric Vent Collar - 18
inches
7. Do not install venting system components on the
exterior wall of the building except as specifically
required by these instructions. Refer to Figure 7.
Table 9: Vent System Components included with Boiler
Vent System Components
Part Number
101808-01
80/125mm Horizontal (Wall) Terminal (ALP080 thru ALP210)
100/150mm Horizontal (Wall) Terminal (ALP285 thru ALP399)
101809-01
Table 10: Clearances from Vent Piping to Combustible Material
Minimum Clearance To
Enclosure
Vent Pipe
Pipe Direction
Combustible Material, Inches
CPVC/PVC Venting
Vertical Or Horizontal
Enclosed at All Sides
1” Vent/0” Combustion Air
20
Table 11: Concentric Vent Length
Vent Length
Inner/Outer Pipe
Boiler Model
Concentric Vent
Wall Opening Diameter
Dia., mm
Minimum
* Maximum
ALP080
ALP105
ALP150
ALP210
ALP285
ALP399
Factory Supplied
Horizontal (Wall) Terminal
80/125 mm
21-7/8 in
32 in
5-1/2 in
6-1/2 in
Total of 60
Equivalent ft.
Factory Supplied
Horizontal (Wall) Terminal
100/150 mm
note: * With optional concentric vent components. See Table 10 for details.
2. Concentric Vent components supplied with the boiler
are packed inside boiler carton and include the
following:
The direct vent termination location is restricted as
follows:
a. Minimum twelve (12) inches above grade plus
normally expected snow accumulation level, or
minimum seven (7) feet above grade, if direct
vent terminal is located adjacent to public
walkway. Do not install the terminal over public
walkway where local experience indicates that
appliance flue gas vapor or condensate creates a
nuisance or hazard.
a. 80/125 mm Horizontal (Wall) Terminal, Part
Number 101808-01
•
Horizontal (Wall) Terminal consists of
Straight section having plain male end with
locking band clamp installed; Terminal
Assembly with offset vent termination,
and Outside Wall Plate, both riveted
on the opposite end; overall length is
approximately 28-1/8”.
b. Minimum three (3) feet above any forced air
inlet located within ten (10) feet.
•
•
Separate Inside Wall Plate
c. Minimum four (4) feet horizontally from electric
meters, gas meters, regulators and relief valves.
This distance may be reduced if equipment is
protected from damage due to flue gas vapor or
condensation by enclosure, overhang, etc.
Two Hardware Bags (each bag contains
four screws and four anchors) to attach vent
terminal Outside Wall Plate to exterior wall
and Inside Wall Plate to interior wall.
d. Minimum twelve (12) inches below, above or
horizontally from any air opening into a building
(window, door or gravity air inlet).
b. 100/150 mm Horizontal (Wall) Terminal, Part
Number 101809-01
•
Horizontal Concentric Vent Terminal, which
consists of Straight section having plain
male end with locking band clamp installed;
Terminal Assembly with offset vent
termination, and Outside Wall Plate, both
riveted on the opposite end); overall length
is approximately 31-1/8”.
e. Minimum twelve (36) inches horizontally from a
building corner.
f. Minimum twelve (12) inches vertically from any
roof overhang twelve (12) inches or less wide.
If a roof overhang width exceeds twelve (12)
inches the terminal vertical clearance must be
increased to avoid flue vapor condensation.
•
•
Separate Inside Wall Plate.
8. Enclose vent passing through occupied or
unoccupied spaces above the boiler with material
having a fire resistance rating of at least equal to the
rating of the adjoining floor or ceiling. Maintain
minimum clearances to combustible materials. See
Figure 2.
Two Hardware Bags (each bag contains
four screws and four anchors) to attach vent
terminal Outside Wall Plate to exterior wall
and Inside Wall Plate to interior wall.
14. Installation of the Boiler Concentric Vent Collar is
covered in Section I above. See Figure 12.
Note: For one or two family dwellings, fire
resistance rating requirement may not need to be
met, but is recommended.
15. For horizontal (side wall) installation, the Horizontal
(Wall) Terminal will extend past outer wall surface
either by 4-1/4” (80/125 mm), or, 5-1/2” (100/150
mm). See Figure 13 “Horizontal (Wall) Terminal
Installation”.
9. Plan venting system to avoid possible contact with
plumbing or electrical wires. Start at vent connector
on top of boiler and work towards vent terminal.
17. For horizontal venting, to install the Horizontal
(Wall) Terminal:
Concentric Venting - Horizontal Venting
a. Cut a 5-1/2” diameter hole through the exterior
wall opening (for 80/125 mm concentric vent) or
6-1/2” diameter hole (for 100/150 mm concentric
vent) at the planned location of the horizontal
1. Permitted terminals for horizontal venting:
Horizontal (Wall) Terminal, either 80/125 mm (P/N
101808-01) or 100/150 mm (P/N 101809-01) - see
Table 8.
terminal.
21
several marks around the outer pipe to establish a
cut line. See Figure 15 ‘ Cutting Outer Pipe’.
d. Carefully cut the outer pipe at the marked line
using aviation shears, a hacksaw etc. Ensure the
pipe is cut square and cut end is deburred.
Figure 15: Cutting Outer Pipe
e. Mark the end of the Horizontal (Wall) Terminal
inner polypropylene vent pipe to extend ¾” past
the cut end of the outer pipe. To achieve a square
cut of the inner pipe, place several marks around
the inner pipe to establish a cut line.
f. Cut off the marked end of inner polypropylene
vent pipe with a fine tooth blade hacksaw etc.
and deburr. See Figure 16 “Cutting Inner Pipe.
Figure 1ꢀ: Horizontal (Wall) Terminal installation
g. Place a mark around the outer pipe, 1” from cut
edge, towards the attached Outside Wall Plate, to
establish visual insertion line as shown in Figure
16 “Cutting Inner Pipe”.
b. Measure dimension “L” from exterior wall outer
surface to the end of the last fitting (or end of
installed Boiler Concentric Vent Collar). See
Figure 14 ‘Dimension “L”’.
h. Pass the shortened Horizontal Concentric Vent
from outside, thru earlier cut exterior wall
opening and push in until the attached Outside
Wall Plate is tight against exterior wall surface.
Insure the proper position of the Horizontal
Concentric Vent before securing the Outside Wall
Plate to the wall with provided fasteners. Seal
plate edges with exterior grade sealant to prevent
moisture penetration.
Figure 1ꢁ: Dimension “L”
c. When factory supplied Horizontal (Wall)
Terminal needs to be shortened, measure
dimension “L” plus 1-¼” from inside of the
attached Outside Wall Plate and mark the
Horizontal (Wall) Terminal outer pipe. To
achieve a square cut of the outer pipe, place
Figure 16: Cutting inner Pipe
22
Concentric Venting - Vertical Venting
WaRning
For vertical (through the roof) venting, extend
Vertical (Roof) Terminal to maintain minimum 12
inches vertical and horizontal distance from building
roof surface. Allow additional vertical distance
for expected snow accumulation. Provide brace as
required. See Figure 19 ‘Vertical Concentric Vent
Installation’.
The terminal vent portion is offset towards the top
inside the outer pipe of the Horizontal Concentric
Vent Terminal to provide vent pipe pitch towards
the boiler for condensate removal.
See Figure 1ꢂ ‘Horizontal (Wall) Terminal Detail’.
it is imperative to properly mount the vent
terminal.
The terminal orientation label is located on the
inside of the terminal Outside Wall Plate. insure
the vent terminal is positioned as shown in
Figure 18 before securing the Outside Wall Plate
to exterior wall.
1. For vertical venting, where optional Concentric Vent
90° degree long radius elbow is attached to installed
Boiler Concentric Vent Collar, to install elbow:
a. Remove locking band clamp off the terminal and
set aside.
b. Lubricate the brown gasket inside boiler
concentric vent collar with small amount of
water.
CaUTiOn
c. Ensure that male end of the elbow inner plastic
pipe is evenly engaged into the gasket all around,
then, push the elbow male end inside boiler
concentric vent collar until the bead on male end
of elbow outer pipe bottoms out inside boiler
vent collar.
Exterior wall surface must be reasonably flat to
attach the Outside Wall Plate. When exterior wall
surface is not flat (covered with vinyl or wood
shingle siding etc.) the siding must be removed,
and a flat surface build up flash or above siding
exterior surface to secure/seal the terminal
Outside Wall Plate.
Figure 1ꢂ: Horizontal (Wall) Terminal Detail
i. Install the supplied Inside Wall Plate onto the
shortened Horizontal (Wall) Terminal interior
end and move the plate to cover interior wall
cut opening. Secure the plate with provided
fasteners, then, apply the sealant around plate
sides to seal it to interior wall.
Figure 18: Completing Horizontal (Wall)
Terminal installation
d. Re-install locking band clamp onto the joint to
secure the elbow to the collar.
j. Lubricate the brown gasket inside boiler
concentric vent collar or the last section of the
vent pipe with small amount of water.
e. Continue installing additional concentric vent
cuttable or non-cuttable piping as required.
k. Ensure that inner pipe of the terminal is evenly
engaged into the gasket all around, then push the
termination male end inside boiler concentric
vent collar or the last section of the vent pipe,
until the mark (see Step g) is no longer visible.
2. Additionally, secure elbow to boiler vent collar with
three evenly spaced #8 x ½” sheet metal screws.
Use collar rivets as reference attachment points.
Mark (center punch) each screw location off each
rivet centerline 5/8” towards collar-beaded end. See
Figure 18 ‘Completing Horizontal (Wall) Terminal
Installation’ for details. Drill 1/8” hole thru both
l. Re-install locking band clamp onto the joint
to secure the terminal to the collar or the last
section of the vent pipe.
2ꢀ
Figure 19: Vertical Concentric Vent installation
outer pipes to start the screw. Use a drill stop or
other means to ensure that the drill bit does not
penetrate more than 3/8” into the outer pipe. Do
not use sheet metal screws longer than ½”.
When Additional Concentric Vent Piping is
needed
1. If additional concentric vent piping is needed:
Figure 21: Fixed Extension (non-Cuttable)
a. Concentric Vent Cut-To-Length Extension pipes,
identified in Tables 8 and 10 CAN BE CUT
to required length when used as an extension.
These pipes have plain male end and beaded
female end. Always cut the pipe from plain
male end. See Figure 20 ‘Cut-To-Length
Extension (Cuttable)”.
b. Remove the plastic inner pipe by pulling it out
from the female end.
c. Cut the OUTER PIPE ONLY at the point
marked in Step (a) using aviation shears, a
hacksaw, or an abrasive wheel cutter. Be careful
to cut the pipe square. Deburr the cut end with a
file or emery cloth.
d. Make an insertion mark 1” from the male end of
the outer pipe.
e. Cut the plastic inner pipe so that it will protrude
3/8” beyond the male end of the outer pipe when
reinstalled in the outer pipe. Use a fine tooth
hacksaw or a PvC saw to cut the plastic pipe and
be careful to cut the pipe square. Deburr the cut
edge of the plastic pipe with a file, razor blade or
fine sandpaper.
Figure 20: Cut-To-Length Extension (Cuttable)
b. The remaining Concentric Vent Fixed Extensions
shown in Table 8 CANNOT BE CUT. These
pipes have beaded male and beaded female ends.
See Figure 21 ‘Fixed Extension (Non-Cuttable)’.
f. Reinstall the inner pipe.
2. To cut the Concentric Vent Straight pipe to required
length refer to Figure 22 “Cutting Straight Pipe” and
follow the procedure below:
3. To join Concentric Vent Pipe refer to Figure 23
“Joining Cuttable Pipe” and Figure 24 “Joining
Non-Cuttable Pipe” and follow the procedure below:
a. Determine the required length of the outer pipe.
When doing this allow an additional 1” of length
for insertion into the female end of the adjoining
pipe. Mark the cut line on the outer pipe.
a. Start assembly of the vent system at the boiler.
Lubricate the brown gasket in the boiler vent
collar with a few drops of water.
2ꢁ
Figure 22: Cutting Straight Pipe
b. Push the male end of the first fitting into the
boiler collar until it bottoms out. The male end
of cuttable sections should go 1” into the collar
until the insertion mark (made in Step 2d above)
is covered. On other fittings, the bead on the
male pipe will be bottom out on the collar (see
Figure 24).
c. The male end of cuttable fittings must be held to
the collar with three (3) #10 x 1/2” sheet metal
screws. Drill a 1/8 hole through both outer pipes
to start this screw. Use a drill stop or other
means to ensure that the drill bit does not
penetrate more than 3/8” into the outer pipe.
Do not use a sheet metal screw longer than
1/2” (see Figure 23).
Figure 2ꢀ: Joining Cuttable Pipe
d. Use locking bands (provided with all fittings) to
secure non-cuttable pipe, as well as fittings, to
the boiler collar (see Figure 24).
e. Use the same method to join all remaining vent
components except for the terminal.
Vertical (Roof Terminal Installation
1. Vertical (Roof) Terminal Installation. Refer to
Figures 26, 27 and 28.
In addition to the vertical terminal, either a Flat
Roof Flashing or Sloped Roof Flashing is required
for this installation. Refer to Table 8 ‘Concentric
Vent Components’ for details.
Figure 2ꢁ: Joining non-Cuttable Pipe
25
abrasive wheel cutter. Be careful to cut the pipe
square. De-burr the cut end with a file or emery
cloth.
a. Determine the centerline of the terminal location
on the roof. For flat roof, cut either 5-1/2”
diameter hole (80/125 mm concentric vent size)
or 6-1/2” diameter hole (100/150 mm concentric
vent size) for the terminal. For sloped roof, cut a
hole in the roof large enough for the terminal to
pass through the roof while remaining plumb.
g. Place a mark on the plastic inner pipe 3/8”
beyond the end of the outer pipe (Figure 26).
Use a fine tooth hacksaw to cut the plastic pipe
and be careful to cut the pipe square. De-burr the
cut edge of the plastic pipe with a file or emery
cloth.
CaUTiOn
h. Make a mark on the terminal section 1” from the
cut end of the outer pipe as shown in Figure 26.
if the boiler is located directly under the hole,
cover it while cutting the hole to prevent debris
from falling onto boiler.
i. Slip the terminal section through the roof from
the outside. Push into the last section of vent
pipe until the mark made in Step (h) is not
longer visible. Secure the terminal to the last
piece of pipe with three #10 x 1/2” sheet metal
screws. Drill a 1/8” hole through both outer
pipes to start these screws. Use a drill stop or
other means to ensure that the drill bit does
not penetrate more than 3/8” into the outer
pipe. Do not use a sheet metal screw longer
than 1/2”.
b. Install the roof flashing using standard practice
on the roofing system of the structure.
c. If not already done, assemble the venting system
inside the building. The last section of pipe needs
to be on the same center line as the terminal
and within 19-1/4” of the top edge of the roof
flashing.
d. Measure distance “H” from the top edge of the
storm collar to the end of the last fitting as shown
in Figure 25.
j. Secure the terminal section to the inside of
the roof structure using the mounting bracket
provided with the terminal (Figure 27).
e. Add 1” to distance “H”. Carefully mark this
length on the pipe as shown in Figure 26.
f. Cut the outer pipe only at the point marked in
Step (e) using aviation shears, a hacksaw, or an
Figure 25: Dimension "H"
Figure 26: Cutting Vertical Terminal
26
Vent Components’ for details. Slip the elbow
over the M10 x 35 screw in the support bracket.
Determine the desired vertical location of the
support elbow in the chimney and mark the
location of the pin, positioned on the back of
the support bracket, onto the chimney rear wall.
Drill a 7/16” diameter x 3-1/2” deep hole in the
marked location, then, insert the back bracket pin
into the hole. The front of the elbow mounting
bracket should be supported either by bottom of
the opening into chimney or installer supplied
spacer.
Table 10: Cut-To-Length Extensions (Cuttable)
Part No.
Component Description
Size
Cut-To-Length Extension,
101163-01
500 mm (19-1/2”)
80/125 mm
Cut-To-Length Extension,
101162-01
101550-01
101551-01
1000 mm (39”)
Cut-To-Length Extension,
500 mm (19-1/2”)
100/150 mm
Cut-To-Length Extension,
1000 mm (39”)
Chimney Chase Installation.
b. Construct a weather-tight flat roof to cover
the top of the old chimney. Install the vertical
terminal through this roof using the flat roof
flashing.
A vertical concentric vent system, either 80/125 mm
or 100/150 mm can be installed in an UNUSED
masonry chimney. Refer to Figure 28.
a. The Chimney chase Support Elbow with
attached Mounting Bracket is used at the base
of the chimney. Refer to Table 8 ‘Concentric
Figure 2ꢂ: Completing Vertical Terminal installation
2ꢂ
Figure 28: Chimney Chase installation
28
V. Condensate Disposal
6. If any additional condensate drain line is needed,
construct the extension from PVC or CPVC
Schedule 40 pipe. The factory supplied ¾” x 5-5/8”
long PVC coupling, located in the Part Carton, must
be used to connect drain line to the condensate trap
stub. Do not over tighten coupling compression nuts
when connecting drain line and condensate trap
stub.
A. Condensate Trap and Drain Line.
1. All condensate, which forms in the boiler or vent
system, collects in the sump under heat exchanger
and leaves the boiler through factory installed
condensate trap.
2. The trap allows condensate to drain from sump
while retaining flue gases in the boiler. The trap
has factory installed overflow switch, which shuts
down the boiler in the event the drain line becomes
obstructed, preventing proper condensate removal.
Refer to Section XIII “Service and Maintenance”
for condensate trap and condensate overflow switch
removal and replacement procedure, if required.
WaRning
Failure to install the condensate trap and
condensate drain in accordance with the above
instructions could cause flue gas to enter the
building, resulting in personal injury or death.
3. Note the following when disposing of the
condensate:
CaUTiOn
a. Condensate is slightly acidic, typical pH around
3.5 - 4.5. Do not use metallic pipe or fittings in
the condensate drain line. Do not route the drain
line through areas that could be damaged by
leaking condensate.
Boiler condensate is corrosive. Route
condensate drain line in a manner such
that any condensate leakage will not cause
property damage.
b. Do not route or terminate the condensate drain
Some jurisdictions may require that
condensate be neutralized prior to disposal.
line in arrears subject to freezing temperatures.
c. If the point of condensate disposal is above the
trap, a condensate pump is required to move
the condensate to the drain. Select a condensate
pump approved for use with condensing
furnaces. If overflow from the pump would
result in property damage, select a pump with an
overflow switch. Wire this switch in series with
installer provided external high limit, to shut off
the boiler, and, if desired, in series with installer-
supplied alarm, to trigger an alarm in the event
of overflow.
nOTiCE
Use materials approved by the authority having
jurisdiction.
B. Condensate Neutralizer Installation
1. Some jurisdictions may require that the condensate
be neutralized before being disposed of. Follow
local codes pertaining to condensate disposal.
d. Do not attempt to substitute another trap for one
2. A Condensate Neutralizer Kit (P/N 101867-01)
is available as optional equipment. Follow local
codes and instructions enclosed with the kit for
Condensate Neutralizer installation.
provided with the boiler.
e. In order for boiler to work properly, the boiler
must be leveled during installation.
4. The condensate trap stub is located at boiler left
side, below inlet and outlet water pipe connections.
Refer to Figures 1A and 1B.
3. Limestone chips will get coated by neutral salts
(product of chemical reaction between limestone
and acidic condensate) and lose neutralizing
effectiveness over time. Therefore, periodic
condensate neutralizer maintenance and limestone
chip replacement must be performed. A pH test or
acid test kits are available from HVAC/plumbing
distributors and should be used to measure
5. Condensate trap must be filled up with water,
prior to boiler start-up and before connecting any
condensate line to the boiler, to insure combustion
products cannot escape from operating boiler. To fill
the trap, inject water in the amount of 1 cup (8 fluid
ounces) through condensate trap stub opening. Do
not overfill the trap.
condensate acidity before/after neutralizer thus
indicating a need for service and chip replacement.
29
ꢀ0
Vi. Water Piping and Trim
WaRning
Failure to properly pipe boiler may result in improper operation and damage to boiler or structure.
install boiler so that the gas ignition system components are protected from water (dripping, spraying,
rain, etc.) during appliance operation and service (circulator replacement, etc.).
A. Installation of Factory Supplied Piping and Trim
nOTiCE
Components
Oxygen contamination of boiler water will cause
corrosion of iron and steel boiler components,
and can lead to boiler failure. Burnham’s Standard
Warranty does not cover problems caused by
oxygen contamination of boiler water or scale
(lime) build-up caused by frequent addition of
water.
Alpine (ALP) boilers have factory supplied
Miscellaneous Part Carton (P/N 101777-01 – ALP080
thru ALP210; 101777-02 – ALP285; 101777-03
– ALP399), which includes supply piping components,
gas piping components, Temperature & Pressure Gauge,
Pressure Relief Valve and Drain Valve. See Figure 30
“ Factory Supplied Piping and Trim Installation”. Install
these components prior to connecting boiler to system
piping as follows:
Do not fill boiler with softened water to prevent
chloride contamination.
Figure ꢀ0: Factory Supplied Piping and Trim installation
ꢀ1
1. ALP080 thru ALP285 Boiler Models
a. Locate and remove ¾” NPT x close black nipple,
¾” NPT black tee, ¾” MPT x ¾” FPT Pressure
Relief Valve, ¾” NPT Drain Valve.
b. Mount the nipple into 1” boiler supply tapping
(see Figure 1A), then, install the tee onto the
nipple, making sure 1” branch outlet is in
horizontal plane and facing the boiler front.
c. Install 1” x ¼” NPT black reducing bushing
into the tee branch, then, put in Temperature &
Pressure Gauge.
b. Install close nipple into tee branch, then, screw
the assembly into boiler left side front ¾”
tapping making sure tee run outlets are in vertical
plane and parallel to boiler side.
4. ALP285 Boiler Model
c. Mount ¾” MPT x ¾” FPT Pressure Relief Valve
into the tee top outlet.
a. Locate and remove 1¼” NPT x 2” long black
nipple, 1¼” x 1¼” x ¾” NPT black tee, ¾” x ¼”
NPT black reducing bushing and Temperature &
Pressure Gauge.
d. Install Drain Valve into the tee bottom outlet.
2. ALP399 Boiler Model
b. Mount the nipple into 1¼” boiler supply tapping
(see Figure 1B), then, install the tee onto the
nipple, making sure ¾” branch outlet is in
horizontal plane and facing the boiler front.
a. Locate and remove (2) ¾” NPT x close black
nipples, ¾” NPT black tee, ¾” FPT x ¾” FPT
Pressure Relief Valve, ¾” NPT Drain Valve.
b. Install close nipple into tee branch, then, screw
the assembly into boiler left side front ¾”
tapping making sure tee run outlets are in vertical
plane and parallel to boiler side.
c. Install ¾” x ¼” NPT black reducing bushing
into the tee branch, then, put in Temperature &
Pressure Gauge.
5. ALP399 Boiler Model
c. Install the second close nipple into tee run top
outlet.
a. Locate and remove 1½” NPT x 2” long black
nipple, 1½” x 1½” x ¾” NPT black tee, ¾” x ¼”
NPT black reducing bushing and Temperature &
Pressure Gauge.
d. Mount ¾” FPT x ¾” FPT Pressure Relief Valve
into the tee top outlet.
e. Install Drain Valve into the tee bottom outlet.
b. Mount the nipple into 1½” boiler supply tapping
(see Figure 1B), then, install the tee onto the
nipple, making sure ¾” branch outlet is in
horizontal plane and facing the boiler front.
3. ALP080 thru ALP210 Boiler Models
a. Locate and remove 1” NPT x 4” long black
nipple, 1” x 1” x 1” NPT black tee, 1” x ¼”
NPT black reducing bushing and Temperature &
Pressure Gauge.
c. Install ¾” x ¼” NPT black reducing bushing
into the tee branch, then, put in Temperature &
Pressure Gauge.
ꢀ2
B. Piping System To Be Employed.
nOTiCE
Alpine (ALP) boilers are designed to operate in a closed
loop pressurized system. Minimum pressure in the
boiler must be 12 PSI. Proper operation of the Alpine
(ALP) boiler requires that the water flow through the
boiler remain within the limits shown in Table 11, any
time the boiler is firing.
Failure to maintain the flow through boiler within
specified limits could result in erratic operation or
premature boiler failure.
1. Near boiler piping must isolate ALP boiler from
system piping via closely spaced tees to insure
specified flow range through boiler any time the
boiler is firing:
Table 11: Flow Range Requirement Through Boiler
Required
Boiler
Supply
Boiler
Return
Minimum
Required Flow Head Loss,
(GPM)
@ 35°F DT
Boiler
Required
Flow,
(GPM)
Boiler
Head Loss,
Ft.
Boiler
Head Loss,
Maximum
Required
Boiler
Head Loss,
Ft. @ 25°F Flow (GPM) Ft.
Flow,
(GPM)
@ 25°F
DT
Boiler
Model Connection, Connection,
Ft.
Inch, FPT
Inch, FPT
@ 35°F DT @ 30°F DT @ 30°F DT
DT
@ 20°F DT @ 20°F DT
ALP080
ALP105
ALP150
ALP210
ALP285
ALP399
1
1
1
1
4.2
5.5
4.8
7.0
5.2
5.4
5.9
6.1
4.9
6.4
6.4
9.3
6.6
7.1
7.8
7.9
5.8
7.7
8.9
12.8
8.9
7.3
9.6
13.4
19.1
12.7
14.4
16.0
15.9
1
1
7.9
9.2
11.0
15.5
21.2
30.2
13.8
19.4
26.5
37.7
1
1
11.1
15.1
21.5
12.9
17.7
25.1
9.8
1¼
1½
1¼
1½
10.7
10.8
Notes: Required Flow (GPM) = ** Output (MBH) * 1000/500 * DT
** Output (MBH) - Select Value for specific Boiler Model from Tables 2A or 2B
Using boiler antifreeze will result in higher fluid density and may require larger circulators.
Alpine Boiler Head Loss vs. Flow
20
18
16
14
12
10
8
105
285
399
210
80
150
6
4
2
0
0
5
10
15
20
25
30
35
40
Flow Rate (GPM)
ꢀꢀ
a. The flow rate through the isolated near-boiler
loop is maintained by factory recommended and
installer supplied boiler circulator.
compare the specified flow range through an
Alpine model boiler to an indirect water heater
(Alliance SL™) model coil flow rate required to
achieve water heater rating. Refer to Table 12B.
b. The flow rate through the isolated near-boiler
loop is completely independent of the flow rate
through the heating system loop(s).
f. When Alliance SL™ model coil flow rate,
required to achieve water heater rating, falls
within the specified flow range for Alpine
boiler model, the Alliance SL™ model can be
piped as part of Alpine near-boiler piping.
Refer to Table 12B, Figures 32A, 32B, 35 and 36
for recommended circulator models, piping and
wiring details.
c. The flow rate through the heating system loop(s)
is controlled by installer sized/provided system
loop circulator(s).
d. This piping arrangement can be used either for
space heating-only applications or space heating
with indirect water heater(s) applications.
i. Space heating only - refer to Table 12A and
Figures 31A or 31B “Near Boiler Piping
- Heating Only” as applicable.
g. When Alliance SL™ model coil flow rate,
required to achieve water heater rating,
exceeds the specified flow range for Alpine
boiler model, the Alliance SL™/Alpine boiler
combination may result in excessive noise and
boiler heat exchanger erosion, and therefore,
is not recommended. Refer to Table 12B for
details.
ii. Space heating plus indirect water
heater(s) - refer to Tables 12A, 12B and, as
applicable, to:
• Figures 32A or 32B “Near Boiler Piping -
Heating Plus Indirect Water Heater”
- when indirect water heater can be piped
as part of near-boiler piping.
• Figures 32C or 32D “Near Boiler Piping -
Heating Plus Indirect Water Heater”
- when indirect water heater must be
piped as a separate heating zone off the
system header.
h. When Alliance SL™ model coil flow rate,
required to achieve water heater rating, falls
below the specified flow range for Alpine boiler
model, the Alliance SL™ model must be piped
as a separate heating zone off the system
header. The circulator must be sized based on
the Alliance SL™ model coil flow and combined
coil pressure drop and the zone piping total
equivalent length. Refer to Table 12B, Figures
32C, 32D, 37A and 37B for piping and wiring
details.
e. For installations where indirect domestic hot
water heater is combined with space heating,
when sizing an indirect water heater circulator,
Table 12a: Recommended Circulator Models for alpine (aLP) Boilers Based on 25°F Temperature Differential
and Up to 75 ft. Equivalent Length Near-Boiler Piping - Space Heating Circulator
Near-Boiler Near-Boiler
Piping Piping
Supply Pipe Return Pipe
Combined
Boiler & Piping
Loop Head
Loss, Ft.
Boiler Supply Boiler Return
Flow, GPM
@ 25°F Temp.
Differential
* Recommended
Circulator
Make & Model
Boiler
Model
Connection,
Connection,
Inch, FPT
Inch, FPT
Size, Inch
Size, Inch
Taco 0010
Grundfos UPS
15-58 FRC
ALP080
ALP105
ALP150
ALP210
ALP285
1
1
1
1
1
1
5.8
7.7
10.3
15.1
13.1
12.7
13.0
12.0
Taco 0014
Grundfos UPS
26-99 FC (second speed)
1
1
1
1
Taco 0014
Grundfos UP
26-99 FC (first speed)
1
1
11.0
15.5
21.5
30.2
Taco 0014
Grundfos UP
26-99 FC (first speed)
1
1
1¼
1½
2
1¼
1½
2
Taco 0013
Grundfos UP
26-99 FC (third speed)
1¼
1½
1¼
1½
Taco 1400-20
Grundfos UPS
ALP399
32-80/2 F (second speed)
notes:
* Circulator Models shown are not equipped with internal flow check valve (IFC).
When selecting Circulators with IFC contact Circulator Manufacturer for sizing information.
Near-Boiler Piping Size shown is based on 2 to 5.5 Ft/Sec. velocity range to avoid potential noise and pipe erosion.
ꢀꢁ
35
36
Table 13: Fitting and Valve Equivalent Length (cont’d)
Table 13: Fitting and Valve Equivalent Length
Copper Fitting and Sweat Valve Equivalent Length (Ft)
Threaded Fitting and Valve Equivalent Length (Ft)
Copper Pipe or Valve Size
Black Threaded Pipe or Valve Size
Fitting or Valve
Fitting or Valve
Description
Description
1
1¼
3.0
1½
4.0
1
1¼
1½
90° Elbow
2.5
1.0
0.5
4.5
23.5
0.3
25.0
5.3
4.3
4.5
54.0
2.7
90° Elbow
2.6
3.5
4.0
45° Elbow
1.2
1.5
Long Radius
Elbow (45° or 90°)
1.4
1.8
2.2
Tee (thru flow)
0.6
0.8
Tee (thru flow)
1.8
5.3
2.3
6.9
2.7
8.1
Tee (Branch flow)
Diverter Tee (typical)
Gate Valve
5.5
7.0
Tee (Branch flow)
25.0
0.4
23.0
0.5
Close Return
Bend
4.4
5.8
6.7
Globe Valve
36.0
7.8
46.0
9.4
Gate Valve (full open)
Globe Valve (full open)
Angle Valve (full open)
0.7
0.9
1.1
Angle Valve
30.0
13.0
39.0
17.0
46.0
20.0
Ball Valve (standard port)
Swing Check Valve
Flow-Check Valve (typical)
Butterfly Valve
7.0
6.6
5.5
6.5
Swing Check Valve
(full open)
8.7
12.0
60.0
13.0
63.0
74.0
2.0
57.0
2.7
Flow-Check Valve
(typical)
42.0
NOTE: Table 13 is provided as reference to assist in piping design and specifies equivalent length of typical piping fittings and
valves.
nOTiCE
The alpine (aLP) boiler heat exchanger is made from stainless steel tubular coil having relatively narrow
waterways. Once filled with water, it will be subject to the effects of corrosion. Failure to take the following
precautions to minimize corrosion and heat exchanger waterways overheating could result in severe boiler
damage.
•
Before connecting the boiler, insure the system is free of impurities, grease, sediment, construction
dust, sand, copper dust, flux and any residual boiler water additives. Flush the system thoroughly and
repeatedly,ifneeded,withclearwatermixedwithconcentratedrinseagenttoremovethesecontaminants
completely.
•
iron oxide (red oxide sludge Fe2Oꢀ) is produced during oxygenation. To minimize any oxygen presence
in the system, the system must be air free and leak tight. Do not connect the boiler to radiant tubing
without an oxygen barrier. Using automatic water refill is not recommended, however, if such refill is
employed, a water meter must be added to evaluate the makeup water volume taken after initial fill and
eliminate any water leakage as early as possible.
•
•
Maintain the water pressure in the boiler at a minimum of 12 PSi.
The boiler water pH must be within 8.2 < pH < 9.5. if the system contains any aluminum components,
pH must be less than 8.5.
•
•
Black oxide sludge (magnetite FeꢀOꢁ) forms as the result of continuous electrolytic corrosion in any
system not protected by an inhibitor.
Scale deposit is made up of lime scale contained in most distributed water and settles over the warmest
surfaces of boiler heat exchanger causing subsequent overheating and eventual failure. Water hardness
must be maintained within ꢀ to 9 grain/gal range.
•
Refer to Section Xiii “Service and Maintenance” for recommended heating system water treatment
products (corrosion/scale inhibitors, cleaners etc) and their suppliers.
ꢀꢂ
ꢀ8
ꢀ9
ꢁ0
ꢁ1
ꢁ2
ꢁꢀ
nOTiCE
WaRning
Where it is not possible to install a separate
boiler loop, the system circulator must be
sized to ensure that the flow through boiler
stays within the defined parameters to prevent
overheating when the boiler is fired at it’s full
rated input. Install a flow meter to measure the
flow, or fire the boiler at full rate and ensure the
boiler DT does not exceed ꢀ5°F.
Pressure relief valve discharge piping must be
piped such that the potential of severe burns
is eliminated. DO nOT pipe in any area where
freezing could occur. DO nOT install any shut-off
valves, plugs or caps. Consult Local Codes for
proper discharge piping arrangement.
2. Circulator (Required) – Usually at least two
circulators will be required to properly install a
Alpine™ Series boiler. See Section B above for
information on sizing the circulators.
2. Direct connection of Alpine (ALP) boiler to
heating system, similar to a conventional boiler, is
NOT RECOMMENDED because:
3. Expansion Tank (Required) - If this boiler is
replacing an existing boiler with no other changes
in the system, the old expansion tank can generally
be reused. If the expansion tank must be replaced,
consult the expansion tank manufacturer’s literature
for proper sizing.
a. The flow rate through system must be the same
as through boiler and fall within limits specified
in Table 11.
b. Pressure drop through entire system must be
known, added to pressure drop through boiler,
and, a circulator selected to provide required
flow at total calculated pressure drop.
4. Fill Valve (Required) – Either manual
(recommended) or automatic fill valve may be used.
However, if automatic refill is employed, a water
meter must be added to evaluate the makeup water
volume taken after initial fill and eliminate any
water leakage as early as possible.
c. It is often very difficult to accurately calculate
the pressure drop through the system.
d. In replacement installations, it may be nearly
impossible to get an accurate measurement of
piping amount and number of fittings in the
system. If system is zoned, the system flow rate
may drop well below recommended minimum
5. Automatic Air Vent (Required) -At least one
automatic air vent is required. Manual vents will
usually be required in other parts of the system to
remove air during initial fill.
flow when only a single zone is calling for heat.
6. Manual Reset High Limit (Required by some
Codes) - This control is required by ASME CSD-1
and some other codes. Install the high limit in the
boiler supply piping just above the boiler with no
intervening valves. Set the manual reset high limit
to 200°F. Wire the limit per Figures 36, 37A and
37B in VIII Electrical Section.
C. Piping Standard Installation Requirements.
Observe the following guidelines when making the
actual installation of the boiler piping:
1. Pressure Relief Valve (Required) - The relief valve
is packaged loose with boiler and must be installed
in the location shown in Figure 30 “Factory
Supplied Piping and Trim Installation”. The relief
valve must be installed with spindle in vertical
position. Installation of the relief valve must comply
with ASME Boiler and Pressure Vessel Code,
Section IV. The standard factory shipped relief valve
is rated for 30 PSI maximum working pressure.
Optional 50 PSI maximum working pressure
rated relief valve is available. If the valve is to be
replaced, the replacement valve must have a relief
capacity equal or exceeding the boiler DOE Heating
Capacity (models ALP080 thru ALP285) or the
boiler I=B=R Gross Output rating (model ALP399).
Pipe the relief valve discharge to a location where
hot water or steam will not create hazard or property
damage if the valve opens. The end of the discharge
pipe must terminate in an unthreaded pipe. If the
relief valve is not piped to a drain, it must terminate
at least 6” above the floor. Do not run relief valve
discharge piping through an area prone to freezing.
The termination of discharge piping must be in an
area where it will not become plugged by debris.
7. Flow Control Valve (Strongly Recommended)
- The flow control valve prevents flow through the
system unless the circulator is operating. Flow
control valves are used to prevent gravity circulation
or “ghost flows” in circulator zone systems through
zones that are not calling for heat.
8. Isolation Valves (Strongly recommended) -
Isolation valves are useful when the boiler must be
drained, as they will eliminate having to drain and
refill the entire system.
9. Drain Valve (Required) – Drain valve is packaged
loose with boiler and must be installed in the
location shown in Figure 30 “Factory Supplied
Piping and Trim Installation”.
10. Low Water Cutoff (Required by some Codes)
– LWCO with harness and LWCO transformer are
available as optional components. Order Complete
Kit (Part No. 102097-01) when required.
ꢁꢁ
a heat exchanger as shown in Figure 33. Consult
the heat exchanger manufacturer for proper heat
exchanger sizing as well as flow and temperature
requirements. All components on the oxygenated
side of the heat exchanger, such as the pump
and expansion tank, must be designed for use in
oxygenated water.
D. Special Situation Piping Installation Requirements
Observe the following guidelines when making the
actual installation of the boiler piping for special
situations:
1. Systems containing high level of dissolved oxygen
– Many hydronic systems contain enough dissolved
oxygen to cause severe corrosion damage to Alpine
(ALP) boiler heat exchanger. Some examples
include but not limited to:
2. Piping with a Chiller - If the boiler is used in
conjunction with a chiller, pipe the boiler and chiller
in parallel. Use isolation valves to prevent chilled
water from entering the boiler.
•
Radiant systems employing tubing without
oxygen barrier
3. Boiler Piping with Air Handlers - Where the
boiler is connected to air handlers through which
refrigerated air passes, use flow control valves in the
boiler piping or other automatic means to prevent
gravity circulation during the cooling cycle.
•
•
Systems with routine additions of fresh water
Systems open to atmosphere
If the boiler is used in such a system, it must be
separated from oxygenated water being heated with
Figure ꢀꢀ: isolation of the Boiler From Oxygenated Water with a Plate Heat Exchanger
ꢁ5
Vii. gas Piping
WaRning
3. Length of piping and number of fittings. Refer
to Tables 14A (natural gas) or 14B (LP gas) for
maximum capacity of Schedule 40 pipe. Table 15
lists equivalent pipe length for standard fittings.
Failure to properly pipe gas supply to boiler may
result in improper operation and damage to the
boiler or structure. always assure gas piping is
absolutely leak free and of the proper size and
type for the connected load.
4. Specific gravity of gas. Gas piping systems for gas
with a specific gravity of 0.60 or less can be sized
directly from Tables 14A or 14B, unless authority
having jurisdiction specifies a gravity factor be
applied. For specific gravity greater than 0.60,
apply gravity factor from Table 16. If exact specific
gravity is not shown choose next higher value.
an additional gas pressure regulator may be
needed. Consult gas supplier.
A. Size gas piping. Design system to provide adequate gas
supply to boiler. Consider these factors:
For materials or conditions other than those listed
above, refer to National Fuel Gas Code, NFPA54/ANSI
Z223.1, or size system using standard engineering
methods acceptable to authority having jurisdiction.
1. Allowable pressure drop from point of delivery to
boiler. Maximum allowable system pressure is ½
psig. Actual point of delivery pressure may be less;
contact gas supplier for additional information.
Minimum gas valve inlet pressure is stamped on
the rating label located in the boiler’s vestibule
compartment.
B. Connect boiler gas valve to gas supply system.
WaRning
2. Maximum gas demand. Refer to the boiler’s input as
printed on its rating label. Also consider existing and
expected future gas utilization equipment (i.e. water
heater, cooking equipment).
Failure to use proper thread compounds on all
gas connectors may result in leaks of flammable
gas.
Table 1ꢁa: Maximum Capacity of Schedule ꢁ0 Black Pipe in CFH* (natural gas) For gas Pressures
of 0.5 psig or Less
inlet Pressure 0.5 PSi or less; 0.ꢀ inch W.C. Pressure Drop
Nominal Pipe
Inside
Length of Pipe, Ft.
Size, In.
Diameter, In.
10
20
90
30
72
40
62
50
55
60
50
70
46
80
42
90
40
100
38
½
¾
0.622
0.824
1.049
1.380
1.610
2.067
2.469
3.068
131
273
188
151
284
583
873
1681
2680
4738
129
243
499
747
1439
2294
4055
114
104
195
400
600
1156
1842
3256
95
89
83
79
1
514
353
215
442
662
1275
2033
3594
179
368
552
1063
1695
2996
167
343
514
989
1576
2787
157
322
482
928
1479
2615
148
304
455
877
1397
2470
1¼
1½
2
1056
1582
3046
4856
8584
726
1087
2094
3337
5900
2½
3
inlet Pressure 0.5 PSi or less; 0.5 inch W.C. Pressure Drop
Nominal Pipe
Inside
Length of Pipe, Ft.
Size, In.
Diameter, In.
10
172
20
30
95
40
81
50
72
60
65
70
60
80
56
90
52
100
50
½
¾
0.622
0.824
1.049
1.380
1.610
2.067
2.469
3.068
118
360
247
199
170
320
657
985
1897
3024
5345
151
284
583
873
1681
2680
4738
137
257
528
791
1523
2428
4293
126
237
486
728
1402
2234
3949
117
110
104
195
400
600
1156
1842
3256
1
678
466
374
220
452
677
1304
2078
3674
207
424
635
1223
1950
3447
1¼
1½
2
1392
2085
4016
6401
11316
957
768
1433
2760
4400
7778
1151
2217
3533
6246
2½
3
* 1 CFH of Natural Gas is approximately equal to 1 MBH; contact your gas supplier for the actual heating
value of your gas.
ꢁ6
Table 1ꢁB: Maximum Capacity of Schedule ꢁ0 Black Pipe in CFH* (LP gas) For gas Pressures
of 0.5 psig or Less
inlet Pressure 11.0 inch W.C.; 0.ꢀ inch W.C. Pressure Drop
Nominal Pipe
Inside
Length of Pipe, Ft.
Size, In.
Diameter, In.
10
88
20
60
30
48
40
41
50
37
60
33
70
31
80
29
90
27
100
25
½
¾
0.622
0.824
1.049
1.380
1.610
2.067
2.469
3.068
184
126
238
488
732
1409
2246
3970
101
191
392
588
1131
1803
3188
87
77
70
64
60
56
53
1
346
163
336
503
968
1543
2729
145
297
446
858
1368
2418
131
269
404
778
1239
2191
121
248
371
715
1140
2016
112
231
346
666
1061
1875
105
216
324
624
995
1760
100
204
306
590
940
1662
1¼
1½
2
710
1064
2050
3267
5776
2½
3
inlet Pressure 11.0 inch W.C.; 0.5 inch W.C. Pressure Drop
Nominal Pipe
Inside
Length of Pipe, Ft.
Size, In.
Diameter, In.
10
20
80
30
64
40
55
50
48
60
44
70
40
80
38
90
35
100
33
½
¾
0.622
0.824
1.049
1.380
1.610
2.067
2.469
3.068
116
242
166
314
644
964
1858
2961
5234
134
252
517
775
1492
2377
4203
114
101
191
392
588
1131
1803
3188
92
85
79
74
70
1
456
215
442
663
1277
2035
3597
173
355
532
1025
1634
2889
159
327
490
943
1503
2658
148
304
456
877
1399
2472
139
285
427
823
1312
2320
131
269
404
778
1239
2191
1¼
1½
2
937
1403
2703
4308
7615
2½
3
* 1 CFH of LP Gas is approximately equal to 2.5 MBH; contact your gas supplier for the actual heating value
of your gas.
Table 15: Equivalent Lengths of Standard Pipe Fittings & Valves
Valves (Screwed) - Fully Open
Screwed Fittings
Nominal
Pipe Size, Diameter,
Inside
180 Close
Return
Bend
90 Tee
Flow Thru
90 Tee,
Flow Thru
Branch
Swing
45°
90°
Gate Globe Angle
Inc.
In.
Check Elbow Elbow
Run
½
¾
0.622
0.824
1.049
1.38
0.4
0.5
0.6
0.8
0.9
1.2
1.4
1.8
17.3
22.9
29.1
38.3
44.7
57.4
68.5
85.2
8.7
4.3
5.7
0.7
1.0
1.2
1.6
1.9
2.4
2.9
3.6
1.6
2.1
2.6
3.5
4.0
5.2
6.2
7.7
3.5
4.6
1.6
2.1
2.6
3.5
4.0
5.2
6.2
7.7
3.1
4.1
11.4
14.6
19.1
22.4
28.7
34.3
42.6
1
7.3
5.8
5.2
1¼
1½
2
9.6
7.7
6.9
1.61
11.2
14.4
17.1
21.3
9.0
8.0
2.067
2.469
3.068
11.5
13.7
17.1
10.3
12.3
15.3
2½
3
ꢁꢂ
Table 16: Specific Gravity Correction Factors
C. Pressure test. See Table 17 for Alpine Min./Max.
Pressure Ratings. The boiler and its gas connection
must be leak tested before placing boiler in operation.
Specific
Gravity
Correction
Factor
Specific
Gravity
Correction
Factor
0.60
0.65
0.70
0.75
0.80
0.85
1.00
0.96
0.93
0.90
0.87
0.81
0.90
1.00
1.10
1.20
1.30
1.40
0.82
0.78
0.74
0.71
0.68
0.66
1. Protect boiler gas control valve. For all testing over
½ psig, boiler and its individual shutoff valve must
be disconnected from gas supply piping. For testing
at ½ psig or less, isolate boiler from gas supply
piping by closing boiler’s individual manual shutoff
valve.
2. Locate leaks using approved combustible gas non-
corrosive leak detector solution.
WaRning
DangER
gas supply to boiler and system must be
absolutely shut off prior to installing or servicing
boiler gas piping.
Do not use matches, candles, open flames or
other ignition source to check for leaks.
1. Use methods and materials in accordance with local
plumbing codes and requirements of gas supplier. In
absence of such requirements, follow National Fuel
Gas Code, NFPA 54/ANSI Z223.1.
Table 1ꢂ: Min./Max. Pressure Ratings
Natural/LP
Gas
Max.
Pressure
(in. w.c.)
LP Gas
Min. Pressure
Inlet to Gas
Valve
Natural Gas
Min. Pressure
Inlet to Gas Valve
(in. w.c.)
Boiler
Model
No.
2. Use thread (joint) compounds (pipe dope) resistant
to action of liquefied petroleum gas.
(in. w.c.)
3. Alpine (ALP) boilers have factory supplied
Miscellaneous Part Carton (P/N 101777-01
- ALP080 thru ALP210; 101777-02 - ALP285;
101777-03 - ALP399), which includes gas piping
components to connect boiler gas valve to gas
supply system. Install these components prior to
connecting boiler to gas supply system piping as
follows:
ALP080
ALP105
ALP150
ALP210
ALP285
ALP399
14
4.0
11.0
a. Locate and remove either ½” NPT x 6” long
black nipple and ½” NPT external gas shutoff
valve (ALP080 thru ALP210), or ¾” NPT x
6” long black nipple and ¾” NPT external gas
shutoff valve (ALP285 thru ALP399).
b. Feed the appropriate nipple through factory
installed jacket left side panel grommet (refer
to Figure 1A or 1B for gas supply connection
identification) and screw the nipple into boiler
gas valve inlet port.
c. Mount the appropriate external gas shutoff valve
onto the threaded nipple end outside of the jacket
left side panel.
d. Install sediment trap, ground-joint union and
manual shut-off valve upstream of boiler gas
control valve and outside jacket. See Figure 34.
4. All above ground gas piping upstream from manual
shut-off valve must be electrically continuous and
bonded to a grounding electrode. Do not use gas
piping as grounding electrode. Refer to National
Electrical Code, NFPA 70.
Figure ꢀꢁ: Recommended gas Piping
ꢁ8
Viii. Electrical
DangER
Positively assure all electrical connections are unpowered before attempting installation or service of
electrical components or connections of the boiler or building. Lock out all electrical boxes with padlock
once power is turned off.
WaRning
Failure to properly wire electrical connections to the boiler may result in serious physical harm.
Electrical power may be from more than one source. Make sure all power is off before attempting any
electrical work.
Each boiler must be protected with a properly sized over-current device.
never jump out or make inoperative any safety or operating controls.
The wiring diagrams contained in this manual are for reference purposes only. Each boiler is shipped with
a wiring diagram attached to the front door. Refer to this diagram and the wiring diagram of any controls
used with the boiler. Read, understand and follow all wiring instructions supplied with the controls.
service switch such that the boiler can be shut-off
without exposing personnel to danger in the event of
an emergency. Connect the main power supply and
ground to the three (3) boiler wires (black, white and
green) located in the junction box at the inside top of
the boiler jacket.
A. General. Install wiring and electrically ground boiler
in accordance with authority having jurisdiction or, in
the absence of such requirements, follow the National
Electrical Code, NFPA 70, and/or CSA C22.1 Electrical
Code.
B. A separate electrical circuit must be run from
the main electrical service with an over-current
device/disconnect in the circuit. A service switch is
recommended and may be required by some local
jurisdictions. Install the service switch in the line
voltage “Hot” leg of the power supply. Locate the
C. Refer to Figures 35 and 36 or details on the internal
boiler wiring.
1. Line Voltage (120 VAC) Connections (Figure 35)
– The line voltage connections are located in the
junction box on the left side of the vestibule:
nOTiCE
This boiler is equipped with a high water temperature limit located inside the internal wiring of the boiler.
This limit provides boiler shutdown in the event the boiler water temperature exceeds the set point of the
limit control. Certain Local Codes require an additional water temperature limit. In addition, certain types
of systems may operate at temperatures below the minimum set point of the limit contained in the boiler.
If this occurs, install an additional water temperature limit (Honeywell L4006 Aquastat) located in the system
piping as shown in the Water Piping and Trim Section of this manual. Wire as indicated in the Electrical
Section of this manual.
nOTiCE
all wire, wire nuts, controls etc. are installer supplied unless otherwise noted.
ꢁ9
•
•
•
•
•
Black – Line voltage “hot”
WaRning
White – “Neutral” for boiler and circulators
Red – “Heating” circulator “hot”
Blue – “Indirect Water Heater “ circulator “hot”
Green – Ground connection
When making low voltage connections, make
sure that no external power source is present
in the thermostat or limit circuits. if such a
power source is present, it could destroy the
boiler’s Microprocessor Control (MCBa). One
example of an external power source that could
be inadvertently connected to the low voltage
connections is a transformer in old thermostat
wiring.
2. Maximum circulator continuous current draw is 2A.
With primary/secondary piping, it may be desirable
to use the boiler to directly control the primary
circulator in addition to the secondary circulator. If
this is done, control both heating circulators using
a relay with a 120VAC coil, such as a Honeywell
R4222, as shown in Figures 37A and 37B. Select a
relay with a contact rating in excess of the combined
draw of the two circulators.
4. If the outdoor sensor is connected to terminals 3
and 4, the boiler will adjust the target space heating
set point supply water temperature downwards
as the outdoor air temperature increases. If used,
this sensor should be located on the outside of the
structure in an area where it will sense the average
air temperature around the house. Avoid placing this
sensor in areas where it may be covered with ice or
snow. In general, locations where the sensor will
pick up direct radiation from the sun should also
be avoided. Avoid placing the sensor near potential
sources of electrical noise such as transformers,
power lines, and fluorescent lighting. Wire the
sensor to the boiler using 22 gauge or larger wire.
As with the sensor, the sensor wiring should be
routed away from sources of electrical noise. Where
it is impossible to avoid such noise sources, wire
the sensor using a 2 conductor, UL Type CM, AWM
Style 2092, 300Volt 60°C shielded cable. Connect
one end of the shielding on this cable to ground.
3. Low Voltage Connections (Figure 35) – These
connections are screw terminals located on the
terminal strip next to the junction box on the left:
•
•
•
•
Terminals 1 and 8 – “Heating” thermostat
connections
Terminals 5 and 6 – “External Limit Control”
connections
Terminals 3 and 4 – “Outdoor Reset Sensor”
connections
Terminals 2 and 4 – “Domestic Indirect Water
Heater” thermostat connections
Terminal 7 – “Flame Signal Reading”
Heat anticipator setting for the thermostat
connection is 0.1 A when thermostat is connected
directly to terminals 1 and 8.
•
•
50
Figure ꢀ5: Wiring Connections Diagram
51
Figure ꢀ6: Ladder Diagram
52
Figure 37A: Modified Wiring For DHW Priority When Using Low Flow Circulator Piped Off System Header -
Heating (with Central Heating Circulators) Plus alternately Piped indirect Water Heater
5ꢀ
Figure 37B: Modified Wiring For DHW Priority When Using Low Flow Circulator Piped Off System Header -
Heating (with Central Heating zone Valves) Plus alternately Piped indirect Water Heater
5ꢁ
Figure ꢀ8: Wiring for MCBa Modulating Boiler Control Time Delay Relay Box
5. If the boiler installation site may be subject to low
f. Connect additional field wiring (not included
in the kit) from MCBA Time Delay Relay Box
to 120 volt power wiring as per wiring diagram
(Figure 38).
supply voltage conditions or “brownouts”, that
would affect MCBA Modulating Boiler Control
operation, a separate optional Time Delay Relay
Box (P/N 101693-01) installation is strongly
recommended. See Figure 38 “Wiring for MCBA
Modulating Boiler Control Time Delay Relay Box”
and follow the following installation steps:
g. Install cover on MCBA Time Delay Relay Box
and restore power to boiler.
h. Measure time from when power is restored until
the boiler actually powers up (LED numbers
will reappear on MCBA display panel). This
MCBA Time Delay Relay Box has a delay on
make timer that delays powering of the boiler for
3 minutes whenever power is lost to the boiler.
Timing should be approximately 3 minutes, but
no longer than 4 minutes.
a. Turn off power to boiler.
b. Remove 120 volt power wiring, L1, L2 and
ground.
c. Remove cover to MCBA Time Delay Relay Box.
d. Mount MCBA Time Delay Relay Box on secure
surface near boiler.
i. Cycle boiler per installation manual.
e. Connect wiring to MCBA Time Delay Relay Box
as per wiring diagram (Figure 38).
55
iX. Boiler Stacking
For installations with unusually high space heating
and/or domestic hot water heating loads, where employing
two (2) Alpine (ALP) boilers will offer the benefits of
greater operational efficiency, floor space savings and boiler
redundancy, the Alpine (ALP) boilers may be installed
stacked one on the top of the other. Refer to Table 18
“Alpine (ALP) Boiler Model Stacking Combinations” for
details.
bottom positioning dimples are evenly spaced
from boiler front and back, while side panel top
positioning dimples follow specific pattern to
compensate for Alpine (ALP) boiler model variable
depth.
4. Position the upper boiler on the top of the bottom
boiler and align boiler front doors and sides flush
with each other.
Table 18: alpine (aLP) Boiler Model
•
Place first Stacking Boiler Attachment Bracket
onto the upper boiler left side panel, at the panel
lower left corner and align bracket two upper
holes with corresponding side panel lower
dimples.
The remaining lower bracket hole must align
with a matching bottom boiler left side panel top
positioning dimple.
Once bracket holes and side panel dimple
alignment is verified, attach the bracket to top
and bottom boiler left side panels with the
mounting screws.
Stacking Combinations
Bottom Boiler Model
ALP080
Top Boiler Model
ALP080
ALP080
ALP105
ALP080
ALP105
ALP150
ALP080
ALP105
ALP150
ALP210
ALP080
ALP105
ALP150
ALP285
ALP080
ALP105
ALP150
ALP210
ALP285
ALP399
ALP105
•
•
ALP150
ALP210
ALP285
5. Repeat above procedure to install second Stacking
Boiler Attachment Bracket and secure the stacked
boiler right side panels together at the front right
corner.
6. Install the third Stacking Boiler Attachment Bracket
to secure top and bottom boiler left side panels at
the rear left corner. Align the bracket holes with
corresponding positioning dimples in the top boiler
and bottom boiler left side panels, then secure
bracket with the screws.
ALP399
7. Repeat above procedure to install the forth Stacking
Boiler Attachment Bracket to secure stacked boiler
right side panels at the rear right corner.
B. When installing stackable boiler combinations
A. To field assemble individual Alpine (ALP) boilers
observe the following guidelines:
into a stackable configuration, use the steps below:
1. Venting - Top and bottom boilers must have their
individual concentric vent piping and vent terminals.
1. Position the bottom boiler first. Refer to Sections II
“Pre-Installation” and III “Unpacking Boiler” of the
manual for details. Always position higher input
boiler model as bottom boiler.
WaRning
no common manifolded venting is permitted.
2. Each Alpine (ALP) boiler is factory packaged with
two (2) Stacking Boiler Attachment Brackets (P/N
101679-01) and the bracket mounting hardware [six
(6) self-drilling hex washer head plated #8 x ½”
long screws, P/N 80860743]. Locate and remove
the brackets and the hardware. The Stacking Boiler
Attachments Bracket has three 7/32” diameter holes
punched in a triangular pattern. See Figure 39
“Stacking Boiler Attachment Bracket Placement”.
For side-wall venting individual model vent
terminals must terminate not closer than 12
inches horizontally and three (3) feet vertically
from each other in order to prevent combustion
air contamination. For vertical through the roof
venting, individual vertical vent terminals, if level
with each other, must be spaced no closer than 12
inches horizontally. If vertical terminals cannot end
in one plane, they must be spaced no closer than
three (3) feet horizontally.
3. Alpine (ALP) boiler left and right side panels have
a series of dimples at panel top and bottom. These
dimples are positioning dimples for Stacking Boiler
Attachment Bracket mounting screws. Side panel
Chimney chase concentric venting is permitted for
modules, when stackable, providing concentric
56
vertical (roof) vent terminals, if level with
each other, are spaced no closer then 12 inches
horizontally.
of an individual boiler. When common gas piping
is sized, insure it will have adequate capacity for
combined input (GPH gas flow) of the selected
stackable boiler combination.
If vertical vent terminals cannot end in one plane,
they must be spaced no closer then three (3) feet
horizontally.
3. Water Piping and Trim - Follow instructions in
Section VI “Water Piping and Trim” of the manual
for system piping and boiler secondary piping
selection/sizing based on combined heating
capacity and/or gross output of the selected
stackable boiler combination. Follow instructions
of Section VI for each individual boiler trim
installation.
Follow instructions in Section IV “Venting” of
the manual for specifics of individual boiler vent
termination. Follow instructions in Section V for
each individual boiler flue gas condensate line
construction and condensate disposal. Terminating
individual boiler condensate lines into common
pipe prior to drain disposal is permissible, providing
common pipe has sufficient flow capacity to
handle combined condensate volume of stackable
combination.
4. Electrical - Follow instructions in Section VIII
“Electrical” of the manual to wire individual boilers.
Stackable boilers require a separate, installer
provided, staging control (Tekmar Model 265 or
equivalent) to operate the boilers. Follow control
manufacturer instructions to wire it to the boilers.
2. Gas Piping - Follow instructions in Section VII “Gas
Piping” of the manual for sizing and installation
Figure ꢀ9: Stacking Boiler attachment Bracket Placement
5ꢂ
X. Modular installation
Using PVC Pipe for Individual Module Combustion
Air Intake Piping – (See Figure 40)
A. General Guidelines
1. Read and follow all venting, combustion air,
water piping, gas piping and electrical instructions
contained in the Installation, Operating and Service
Instructions unless otherwise instructed in this
section.
1. Each individual module (boiler) must have own
combustion air intake pipe and combustion air
intake terminal. Refer to Section IV “Venting” of
these Instructions for individual module (boiler)
combustion air intake guidelines and options.
2. Consult Local Building Codes or National Fuel Gas
Code, NFPA 54/ANSI Z222.3 for restrictions and
instructions on modular boiler installations.
2. The individual module (boiler) maximum
combustion air intake pipe length is sixty (60)
equivalent feet.
B. Modular Boiler Venting System Arrangements
3. If possible, locate each individual module (boiler)
both combustion air intake termination and vent
termination on the same side wall, to prevent
nuisance boiler shutdowns.
Using CPVC/PVC pipe for Individual Module Vent
Piping – (See Figure 40)
1. Each individual module (boiler) must have own
vent pipe and vent terminal. Refer to Section IV
“Venting” of these Instructions for individual
module (boiler) venting guidelines and options.
However, if same side wall placement is
problematic, an individual module (boiler) may
be installed using vertical venting and side wall
combustion air intake termination (or, vice versa)
WaRning
Using Concentric Combination Venting/Combustion
Air Intake Piping - Inner Polypropylene Vent
Pipe/Outer Combustion Air Intake Steel Pipe Casing
– (See Figure 40)
no common manifolded venting (vent piping and
vent terminals) is permitted.
2. The individual module (boiler) maximum vent
length is sixty (60) equivalent feet.
1. Each individual module (boiler) must have own
concentric vent pipe and vent termination. Follow
Section IV “Venting” of these Instructions for
individual module (boiler) concentric venting
guidelines.
3. For side wall venting the minimum horizontal
distance between any adjacent individual module
(boiler) vent terminations is twelve (12) inches.
Additional horizontal spacing between any adjacent
individual module (boiler) vent terminations as well
as extending the distance from building surfaces
to vent termination end are recommended to avoid
frost damage to building surfaces where vent
terminations are placed.
WaRning
no common manifolded concentric venting is
permitted.
2. The individual module (boiler) maximum concentric
vent length is sixty (60) equivalent feet.
CaUTiOn
3. For sidewall venting any adjacent individual module
(boiler) concentric vent terminals must be spaced no
closer than 12 inches horizontally and three (3) feet
vertically from each other to prevent combustion air
contamination.
installing multiple individual module (boiler) vent
terminations too close together may result in
combustion product water vapor condensation
on building surfaces, where vent termination are
placed, and subsequent frost damage. To avoid/
minimize frost damage, extend the distance from
building surfaces to vent termination end and
increase the horizontal distance between adjacent
vent terminations.
Additional horizontal spacing between any
adjacent individual module (boiler) concentric vent
terminations and increased distance from building
surfaces to concentric vent termination end are
recommended to avoid frost damage to building
surfaces where vent terminations are placed.
4. Individual module (boiler) sidewall vent terminals
must be placed at least twelve (12) inches above the
ground plus the expected snow accumulation.
4. Individual module (boiler) sidewall concentric
vent terminals must be placed at least twelve (12)
inches above the ground plus the expected snow
accumulation.
5. Multiple individual module vertical vent pipes may
be piped through a common conduit or chase so that
one roof penetration may be made.
5. For vertical through the roof venting any adjacent
individual module (boiler) vertical vent terminals, if
level with each other, must be spaced no closer than
12 inches horizontally.
The minimum horizontal distance between any
adjacent individual module (boiler) roof vent
terminations is one (1) foot.
58
59
60
If vertical vent terminals cannot end in one plane,
they must be spaced no closer than three (3) feet
horizontally.
D. Modular Boiler Gas Piping
1. Individual module (boiler) gas pipe sizing specific
details
6. Chimney chase concentric venting is permitted for
modules, when stackable, providing concentric
vertical (roof) vent terminals, if level with
each other, are spaced no closer then 12 inches
horizontally.
2. Individual module (boiler) recommended gas piping.
See Figure 34.
3. Requirement to install additional gas pressure
regulators to properly regulate gas pressure at the
input of the smallest individual module (boiler).
If vertical vent terminals cannot end in one plane,
they must be spaced no closer then three (3) feet
horizontally.
WaRning
7. When individual modules (boilers) are installed in
the same horizontal plane, chimney chase vertical
concentric venting is permitted provided:
if gas pressure in the building is above ½ psig,
an additional gas pressure regulator is required.
Using one additional regulator for multiple
boilers may result in unsafe boiler operation.
The additional regulator must be able to properly
regulate gas pressure at the input of the smallest
boiler. if the regulator cannot do this, two or
more additional regulators are required. Consult
regulator manufacturer and/or local gas supplier
for instructions and equipment ratings.
a. Sufficient inside space available at the base of
the chimney to install multiple chimney chase
brackets and support elbows.
b. Spacing between adjacent vertical vent terminals
is in accordance with paragraph 6 above.
CaUTiOn
E. Modular Boiler Electrical
installing multiple individual module (boiler)
concentric vent terminations too close together
may result in combustion product water vapor
condensation on building surfaces, where
termination are placed, and subsequent frost
damage. To avoid/minimize frost damage extend
the distance from building surfaces to concentric
vent termination end as well as increase the
horizontal distance between adjacent concentric
vent terminations.
Refer to Section VIII “Electrical” of these Instructions
for:
1. Individual module (boiler) wiring specific details
2. Individual module (boiler) internal wiring details,
high and low voltage connections
Each individual module (boiler) must be provided with own
fused disconnect and own service switch.
Installmodularboilerwiringinaccordancewithrequirementsof
authorityhavingjurisdiction. Inabsenceofsuchrequirements,
followtheNationalElectricCode, NFPA70and/orCSAC22.1
Electric Code.
C. Modular Boiler Water Piping – (See Table 19 and
Figure 42)
Refer to Section VI “Water Piping and Trim” of these
Instructions for:
F. Modular Boiler Control Systems – (See Figures 44
and 45)
1. Installation of Factory Supplied Piping and Trim
Components for an individual module (boiler).
1. Follow modular boiler control system manufacturer
(Honeywell, Tekmar etc.) instructions to properly
apply a modular control system.
2. Regarding an individual module (boiler) piping
system specific details.
2. Tekmar model 264 and model 265 based control
wiring diagrams (Figures 44 and 45) are provided as
examples of typical modular boiler control system.
3. Selection criteria for individual module (boiler)
space heating and/or DHW circulators.
3. Additionally, common modular boiler control
systems may use outdoor temperature sensing,
return water temperature sensing or both to stage
modular boilers.
Table 19: Modular Boiler Water Manifold Sizing
number of Units
Boiler Model
2
ꢀ
ꢁ
5
6
ꢂ
8
Recommended Minimum Common Water Manifold Size (nPT)
aLP080
aLP105
aLP150
aLP210
aLP285
aLPꢀ99
1¼”
1½”
2”
1½”
2”
2”
2½”
2½”
2½”
ꢀ”
2½”
2½”
2½”
ꢀ½”
ꢀ½”
ꢁ”
2½”
2½”
ꢀ”
2½”
ꢀ”
2”
2”
2½”
ꢀ”
ꢀ½”
ꢁ”
2”
2½”
2½”
ꢀ”
ꢁ”
2½”
2½”
ꢀ”
ꢀ½”
ꢁ”
ꢁ”
5”
ꢀ”
5”
5”
61
62
6ꢀ
6ꢁ
65
Xi. System Start-up
A. Verify that the venting, water piping, gas piping and
electrical system are installed properly. Refer to
installation instructions contained in this manual.
nOTiCE
If it is required to perform a long term pressure
test of the hydronic system, the boiler should
first be isolated to avoid a pressure loss due to
the escape of air trapped in the boiler.
B. Confirm all electrical, water and gas supplies are
turned off at the source and that vent is clear of
obstructions.
To perform a long term pressure test including
the boiler, ALL trapped air must first be removed
from the boiler.
C. Confirm that all manual shut-off gas valves between
the boiler and gas source are closed.
a loss of pressure during such a test, with no
visible water leakage, is an indication that the
boiler contained trapped air.
WaRning
Completely read, understand and follow all
instructions in this manual before attempting
start up.
3. Temporarily turn off all other gas-fired appliances.
4. Turn on gas supply to the boiler gas piping.
D. If not already done, flush the system to remove
sediment, flux and traces of boiler additives. This must
be done with the boiler isolated from the system. Fill
entire heating system with water meeting the following
requirements:
5. Open the field installed manual gas shut-off valve
located upstream of the gas valve on the boiler.
6. Confirm that the supply pressure to the gas valve is
14 in. w.c. or less. Refer to Table 21 for minimum
supply pressure.
nOTiCE
7. Using soap solution, or similar non-combustible
solution, electronic leak detector or other approved
method. Check that boiler gas piping valves, and
all other components are leak free. Eliminate any
leaks.
pH between 8.2 and 9.5.
if system contains aluminum components, pH
must be less than 8.5
Total Dissolved Solids - less than 2500 PPM
Hardness - ꢀ to 9 grains/gallon.
DangER
Pressurize the system to at least 12 PSI. Purge air from
the system.
Do not use matches, candles, open flames or
other ignition source to check for leaks.
WaRning
8. Purge gas line of air.
G. Operating Instructions
The maximum operating pressure of this boiler
is ꢀ0 psig. never exceed this pressure. Do not
plug or change pressure relief valve.
Start the boiler using the lighting instructions, see
Figure 46. After the boiler is powered up, it should go
through the following sequence.
E. Confirm that the boiler and system have no water
Sequence
1
Display
Meaning
leaks.
U.125
or Blank
Checking internal software
(power-up only)
F. Prepare to check operation.
1. Obtain gas heating value (in Btu per cubic foot)
from gas supplier.
2
0.SWT
Boiler in standby. SWT = Supply
Water Temp. No call for heat.
(After call for heat from heating
thermostat)
2. Alpine gas valves have inlet and outlet pressure
taps with built-in shut off screw. Turn each
screw from fully closed position three to four
turns counterclockwise to open taps. Connect
manometers to pressure taps on gas valve.
3
4
A.SWT
5.SWT
Self-Check on Start-up
Blower and circulator on. Check-
ing for adequate air flow.
5
6
7
1.SWT
2.SWT
3.SWT
Prepurge
Trial for ignition
Flame established. Boiler re-
sponding to a call for heat.
66
Alpine™ Series Lighting and Operating Instructions
Figure ꢁ6: Lighting instructions
6ꢂ
Figure ꢁꢂ: Burner Flame
H. Purge Air From Gas Train
K. Perform Combustion Test
Upon initial start-up, the gas train will be filled with air.
Even if the gas line has been completely purged of air,
it may take several tries for ignition before a flame is
established. If more than 5 tries for ignition are needed,
it will be necessary to press the reset button to restart
the boiler. Once a flame has been established for the
first time, subsequent calls for burner operation should
result in a flame on the first try.
Perform a combustion test. Boilers equipped with a
concentric vent system have a flue gas sample tap
located in the boiler vent collar (under the screw cap).
Insert the analyzer probe in the flue gas sample tap.
Check CO2 (or O2) and CO at both high and low fire.
The boiler may be temporarily locked into high or low
fire for 15 minutes as follows:
1. To lock the boiler in high fire, simultaneously press
and hold the “Mode” button and “+“ button until the
display flashes “H”, indicating that the boiler has
been driven to high fire. After this happens, allow
the boiler to operate for approximately 5 minutes
before taking combustion readings.
I. Check Burner Flame
Inspect the flame visible through the window. On high
fire the flame should be stable and mostly blue (Figure
47). No yellow tipping should be present; however,
intermittent flecks of yellow and orange in the flame are
normal.
2. To lock the boiler in low fire, simultaneously press
and hold the “Mode” button and “-“ button until the
display flashes “L”, indicating that the boiler has
been driven to low fire. After this happens, allow the
boiler to operate for approximately 5 minutes before
taking combustion readings.
J. Check Gas Inlet Pressure
Check the inlet pressure and adjust if necessary. Verify
that the inlet pressure is between the upper and lower
limits shown on the rating plate with all gas appliances
on and off.
3. Normal modulation of the boiler should return 15
minutes after the boiler is locked in high or low fire.
WaRning
Typical CO2 readings are shown in Table 20.
The outlet pressure for the gas valve has been
factory set and requires no field adjustment. This
setting is satisfactory for both natural gas and
propane. attempting to adjust the outlet pressure
may result in damage to the gas valve and cause
property damage, personal injury or loss of life.
WaRning
Each alpine Series boiler is tested at the factory
and adjustments to the air fuel mixture are
normally not necessary. Consult a U.S. Boiler
representative before attempting to make any
such adjustments. improper gas valve or mixture
adjustments could result in property damage,
personal injury, or loss of life.
Table 20: Recommended Combustion Settings,
natural gas
Altitude Range
Boiler
Model
0 - 7000 Ft.
L. Test External Limits
% CO2
% O2 Range
CO, PPM
Test any external limits or other controls in accordance
with the manufacturer’s instructions.
ALP080
ALP105
ALP150
ALP210
ALP285
ALP399
M. Check Thermostat Operation
Less than 75
PPM
8.2 - 8.8
5.5 - 6.5
Verify that the boiler starts and stops in response to
calls for heat from the heating thermostat and indirect
water heater thermostat. Make sure that the appropriate
circulators also start and stop in response to the
thermostats.
68
Table 21: Permitted Conversions
N. Adjust Supply Water Temperature
As shipped, the heating and indirect water heater set
point supply temperatures are both set to 180°F. If
necessary, adjust these to the appropriate settings for
the type of system to which this boiler is connected. See
Section XII “Operation” of this manual for information
on how to do this.
Gas
Valve
Planned
Installation
Altitude
Fuel Converted
Boiler
Model
(Dungs)
Size Gas Valve Model
(NPT)
From
To
Range
GB-WND 055 D01
ALP080
S00 253082
ALP105
ALP150
GB-WND 055 D01
1/2”
O. Adjust Thermostats
S00 253083
Natural
Gas
Adjust the heating and indirect water heater thermostats
to their final set points.
GB-WND 055 D01
LP
0 - 7,000 Ft.
ALP210
ALP285
ALP399
S00 253084
GB-WND 057 D01
P. Field Conversion From Natural Gas to LP Gas
S00 253085
3/4”
GB-WND 057 D01
Alpine Series boilers are factory shipped as Natural Gas
builds. Follow steps below for field conversion from
Natural Gas to LP Gas.
S00 253086
3. If conversion is being made on a new installation,
install the boiler in accordance with the installation
instructions supplied with the boiler. If an installed
boiler is being converted, connect the new gas
supply to the boiler, check for gas leaks, and purge
the gas line up to the boiler in accordance with
the National Fuel Gas Code (ANSI Z223.1) or the
requirements of the authority having jurisdiction.
WaRning
This conversion should be performed by a
qualified service agency in accordance with the
manufacturer’s instructions and all applicable
codes and requirements of the authority having
jurisdiction. iftheinformationintheseinstructions
is not followed exactly, a fire, an explosion or
production of carbon monoxide may result
causing property damage, personal injury, or loss
of life. The qualified service agency is responsible
for proper conversion of these boilers. The
conversion is not proper and complete until the
operation of the converted appliance is checked
as specified in the Alpine™ Installation, Operating
and Service instructions.
4. Before attempting to start the boiler, make the
number of turns to the throttle screw called for in
Table 22.
Table 22: number of Clockwise Throttle Screw
Turns
Throttle Screw Turns at
Altitude Range
Boiler Model
Gas Valve
0 - 7000 Ft.
ALP080
ALP105
ALP150
ALP210
2¾
4
Dungs
GB-055
(½” NPT)
WaRning
3¼
4
These instructions include a procedure for
adjusting the air-fuel mixture on this boiler.
This procedure requires a combustion analyzer
to measure the CO2 (or Oxygen) and Carbon
Monoxide (CO) levels in flue gas. Adjusting the
air-fuel mixture without a proper combustion
analyzercouldresultin unreliableboileroperation,
personal injury, or death due to carbon monoxide
poisoning.
Dungs
GB-057
(¾” NPT)
ALP285
ALP399
4½
1¾
Dungs
GB-057 HO
(¾” NPT)
5. Attempt to start the boiler using the lighting
instructions located inside the lower front cover of
the boiler. If the boiler does not light on the first
try for ignition, allow to boiler to make at least
four more attempts to light. If boiler still does not
light, turn the throttle counter clockwise in 1/4 turn
increments, allowing the boiler to make at least
three tries for ignition at each setting, until the boiler
lights.
1. Make sure that the planned fuel conversion is listed
in Table 21. If the planned conversion is not shown
in Table 21, it is not permitted. Refer to Figure
34 to identify the valve used on the model being
converted.
2. Conversion of Alpine Series boilers from one fuel
to another is accomplished using the throttle screw
on the gas valve. Figure 48 shows the location of
the throttle screw on the Dungs valve. Locate the
throttle on the boiler being converted.
69
7. Perform a combustion test. Boilers equipped with a
concentric vent system have a flue gas sample tap
located in the boiler vent collar (under the screw
cap).
8. While the burner is at high fire adjust the throttle as
needed to obtain the CO2 (or O2) settings shown in
the Table 23:
•
To reduce the CO2 (increase the O2) turn the
throttle clockwise
•
To increase the CO2 (reduce the O2) turn the
throttle counter-clockwise
Make adjustments in increments of 1/8 to 1/4 turn
and allow the boiler at least a minute to respond to
each adjustment before making another. In general,
the CO level will be at its lowest somewhere in the
CO2 range shown in this table.
Table 2ꢀ: Recommended Combustion Settings,
LP gas
Altitude Range
Boiler
Model
0 - 7000 Ft.
% CO2
% O2 Range
CO, PPM
ALP080
ALP105
ALP150
ALP210
ALP285
ALP399
Less than
75 PPM
9.5 - 10.1
5.5 - 6.5
9. Verify that the gas inlet pressure is between the
upper and lower limits shown in Table 24 with all
gas appliances (including the converted boiler) both
on and off:
Figure ꢁ8: Dungs gas Valve Detail
6. After the burner lights, force the burner to high fire
by simultaneously pressing and holding the “Mode”
button and “+“ button. After a few seconds, the
display should flash “H”, indicating that the boiler
has been driven to high fire. Allow the boiler to
operate for approximately 5 minutes before taking
combustion readings. Note: after 15 minutes, the
boiler is automatically released from high fire hold.
Be sure to restore high fire hold if additional time is
needed to obtain high fire combustion readings.
10. A label sheet is provided with the boiler for
conversions from natural to LP gas. Once conversion
is completed, apply labels as follows:
•
Apply the “Rating Plate Label” adjacent to the
rating plate.
•
Apply the “Gas Valve Label” to a conspicuous
area on the gas valve.
WaRning
The pressure regulator has been factory set using precision instruments and must never be adjusted in
the field. The gas valve outlet pressure is the same for both natural gas and propane. Make sure that
all adjustments are made with the throttle, not the pressure regulator. attempting to adjust the pressure
regulator will result in damage to the gas valve and may cause property damage, personal injury or loss of
life.
ꢂ0
WaRning
The throttle adjustments shown in Table 22 are approximate. The final throttle setting must be found using
a combustion analyzer. Leaving the boiler in operation with a CO level in excess of the value shown in
Table 2ꢀ could result in injury or death from carbon monoxide poisoning.
nOTiCE
if the throttle is very far out of adjustment on the “rich” (counter-clockwise) side, the boiler burner may be
running at 0% Excess Air or even with air deficiency.
at 0% Excess air the CO2 readings will be either 11.9% CO2 for natural gas or 1ꢀ.8% CO2 for LP gas (O2 will
be 0%) and CO level will be extremely high (well over 1000 PPM).
If the burner operates with air deficiency, the following phenomena may be observed:
% CO2 will actually drop (% O2 will increase) as the throttle is turned counterclockwise
% CO2 will actually increase (% O2 will drop) as the throttle is turned clockwise
If the boiler appears to operate with air deficiency, turn the throttle clockwise to increase the amount of
Excess air to the burner.
as the throttle is turned clockwise, the CO2 level will rise, eventually peaking @ 11.8% or 1ꢀ.8%, depending
of the type of gas being used, before falling (conversely, O2 level will drop to 0% before rising). after this
happens, continue turning the throttle clockwise, until CO2 level drops (or O2 level increases) to the values
shown in Table 20 or Table 2ꢀ.
Table 2ꢁ: inlet Pressure Limits
•
Apply the “Boiler Conversion Label” to a
conspicuous surface on, or adjacent to, the outer
boiler jacket. Fill in the date of the conversion
and the name and address of the company
making the conversion with a permanent marker.
Inlet Pressure (Inches w.c.)
Fuel
Min.
4.0
Max.
14.0
14.0
Natural Gas
LP
11.0
11. Refer to Section XI “System Start-up” of this manual
and perform any checks not already completed.
ꢂ1
Xii. Operation
c. “Stby” for Standby Mode. Upon entering
standby mode, “Stby” will briefly appear on
the display and then the display will show the
boiler’s status along with the supply temperature
(Figure 49).
I. Factory Preset Boiler Operating Parameters
(See Table 25 for Parameter Descriptions)
A. The Alpine (ALP) boiler uses a microprocessor based
Honeywell control, known as a “MCBA”, to manage
all boiler functions including flame supervision and
modulation. Two set point or “target” boiler supply
temperatures are stored in the MCBA’s memory;
one for space heating and one for domestic water
production. If an outdoor temperature sensor is
connected to the boiler, the space heating supply set
point will automatically adjust downwards as the
outdoor temperature increases. For more information
on this feature see the discussion on boiler water reset
below.
The control will return to standby mode from any
other mode if no key is pressed for 20 minutes.
The MCBA modulates the boiler input by varying the
fan speed. As the fan speed increases, so does the
amount of gas drawn into the blower. As a result, a
fairly constant air-fuel ratio is maintained across all
inputs.
Figure ꢁ9: normal Display in Standby Mode
C. In standby mode, it is possible to view both the
heating supply set point temperature and the “domestic
hot water reference set point”. The “domestic hot
water reference set point” plus 45°F equals the boiler
supply set point when it is responding to a call from
the indirect water zone. It is not the actual domestic
hot water set point. The Alpine (ALP) is designed
for use with a storage type indirect water heater such
as the Alliance SL™. The domestic water set point
is controlled by the thermostat on the indirect water
heater. The “default domestic water reference set point”
is 135°F and target boiler supply temperature when
responding to a call from the indirect water heater is
therefore 180°F (135°F +45°F). The default heating
supply set point (parameter 4) is 180°F.
The MCBA determines the input needed by looking
at both current and recent differences between the
supply temperature and the set point temperature.
As the supply temperature approaches the set point
temperature, the fan will slow down and the input drop.
Depending on the model boiler, the minimum input
is between 1/3 (high altitude) and 1/5 (sea level) of
maximum input.
The MCBA also monitors boiler return and flue
temperatures. In addition, all other safety controls,
including the low water cut-off and safety limit, are
connected into the MCBA. The MCBA uses input from
all of these controls to either shut down the boiler when
an unsafe condition exists or, in some cases, to correct
the problem.
In standby mode it is also possible to turn on or off
either the heating or domestic water zone. There is
normally no reason to turn off either of these zones and
doing so is not recommended.
B. The display panel has three primary modes of
operation. These are:
WaRning
1. Standby Mode – Displays boiler’s current status.
This is the default operating mode.
Pushing and holding the “+” while in Standby
Mode will prevent the boiler from responding to
a call for heat. Pushing and holding the “-” while
in Standby Mode will prevent the boiler from
responding to a call for domestic water. if this
happens, “cOFF” or “dOFF” will appear on the
display. To turn back on the heating function,
press and hold “+” until “c” and the set point
temperature appears on the display. To turn back
on the domestic water function, press and hold “-”
until “d” and the set point temperature appears on
the display. after pressing any keys, and before
leaving the installation, verify that the boiler fires
in response to a call for heat and domestic water.
2. Parameter Mode – Used to change control settings
3. Information Mode – Displays boiler operating
temperatures
Under normal conditions, the boiler is in standby mode
and the display looks like that shown in Figure 49. The
three digits to the right of the decimal point are the
boiler’s supply temperature. The digit to the left of the
decimal point is the boiler’s status code. A list of status
codes, and their meanings, is shown in Table 26.
Figure 50 is a map of the menu structure for the control
panel. Push the mode key to move from one mode
to the next. As you change modes, the mode you are
entering is shown on the display:
a. “PArA” for Parameter Mode
b. “Info” for Information Mode
ꢂ2
Table 25: Parameter Descriptions
Factory Setting
Access Parameter
Description
Code
No.
ALP080 ALP105 ALP150 ALP210
ALP285 ALP399
1
2
T3set DHW
DHW system
CH system
140
1 (On)
1 (On)
190
130
0
no
access
Code
3
needed
4
T1top CH Mode
5
T1foot CH Mode
6
T4 minimum
7
T4 maximum
60
8
T4 frost protection *
-22
0
9
T4 correction
10
Tblocking
32
11
Booster time
0
12
Tparallel shift
0
13/14
15/16
17/18
19
Maximum fanspeed CH
Maximum fanspeed DHW
Minimum fanspeed
4450
4450
1125
4850
4850
1250
5500
5500
1300
3000
6200
6200
1375
6300
6300
1450
5867
5867
1267
2300
Ignition fanspeed
20
CH postpump time
0
10.2
10
2
21
DHW postpump time
CH modulation hysteresis on
CH modulation hysteresis off
DHW modulation hysteresis on
DHW modulation hysteresis off
DHW detection hysteresis on
DHW detection hysteresis off
CH blocking time
22
23
24
10
2
25
26
-8
10
0
27
28
29
DHW blocking time
0
30
DHW-> CH blocking time
Modulate back difference T1-T2
RMCI Address
0
31
54
-1
50
32
33
Tplus: Setvalue addition for DHW
2nd CH-Circuit (1st digit)
CH Type (2nd digit)
34-1
34-2
35-1
35-2
36
0 (2nd Heating Circuit Off)
0 (Room Thermostat)
DHW 3=way valve or pump (1st digit)
DHW-type (2nd digit)
Manual fanspeed
1 (Hot Water Pump)
3 (Storage Tank without NTC3)
-1
37-1
37-2
38
PWM-pump level (1st digit)
PWM-pump level (2nd digit)
Tset hold boiler warm
Ttop for 2nd CH circuit
Tfoot for 2nd CH circuit
Thysteresis for 2nd CH circuit
Pump settings for CH and DHW
Minimum Off Cycle (2nd digit)
4
1
36
39
190
130
40
41
10
42-1
42-2
0 (CH Normal Pump)
0 (Not Active)
* Circulator will start when boiler supply sensor will detect temperature 44.6° F or less
ꢂꢀ
ꢂꢁ
D. Two basic types of errors codes are shown on the
G. An external limit control can be installed between
terminals 5 and 6 on the terminal strip. Be sure to
remove the jumper between terminals 5 and 6 when
adding an external limit control to the system. If the
external limit opens, the boiler will shut down and error
code “b 26” will be displayed. If the limit installed is
a manual reset type, it will need to be reset before the
boiler will operate.
display:
1. Soft Lockout Codes – When a soft lockout occurs,
the boiler will shut down and the display will
alternate between the number “9” and the letter
“b” followed by a two digit service code. A list of
these codes, and their meanings, is shown in Table
29 in Section XIV Troubleshooting. The boiler will
automatically restart once the condition that caused
the lockout is corrected.
H. The sequence of operation for a Alpine Series boiler
on a call for heat from a thermostat is as described
below:
2. Hard Lockout Codes – When a hard lockout occurs,
the boiler will shut down and the display will flash
the letter “E” followed by a two digit service code.
A list of these codes, and their meanings, is shown
in Table 30 in Section XIV Troubleshooting. Once
the condition that caused the lockout is corrected,
the boiler will need to be manually reset using the
RESET button on the display.
1. When power is first turned on, 120V is provided
to the MCBA, the combustion fan and the LWCO
transformer. A separate 50VA transformer,
connected directly to the MCBA, powers all other
low voltage circuits.
2. For the first few seconds after power-up the control
module goes through a self check.
Table 2ꢀ: Boiler Status
3. When there is a call for heat, the control module
checks to make sure the air pressure switch is
open. If it is, the combustion fan will be energized
and will ramp up to ignition speed. When the air
pressure switch closes, a 10 second prepurge is
activated.
First
Boiler Status
Digit
0
1
2
3
4
5
6
7
8
Burner off - No call for heat or DHW
Pre-purge or post-purge
Ignition
4. After the prepurge, the control module energizes
the gas control valve and the spark for 4.5 seconds.
If a flame is established and proved, the control
allows the flame to stabilize for 5 seconds at the
combustion fan ignition speed setting. If the flame
fails to prove, the control module will attempt to
light the burner 4 more times. If a flame is still not
established, the control will lockout.
Burner responding to call for heat
Burner responding to call for DHW
Checking air pressure switch
Burner off - Set point temperature has been reached
Call for heat ended. 10s heating post pump period
Call for DHW ended. 10s DHW post pump period
9 and b Burner off - on soft lockout. See Troubleshooting Section to
Flashing determine meaning of error code.
5. Once the flame stabilization period has ended,
the MCBA allows the burner to modulate. The
actual firing rate is dependent upon the measured
current and recent differences between the set point
temperature and the supply temperature. If an
outdoor sensor is connected to the control module
and the boiler is responding to a call for heat, the set
point temperature will be determined by the outdoor
reset curve shown in Figure 51.
A
H
L
Boiler responding to call from heating zone
Burner on - Held in high fire
Burner on - Held in low fire
E. If an outdoor sensor is installed, the boiler will
automatically adjust the heating zone set point
temperature based on the outdoor reset curve in Figure
51. The maximum set point is defined by parameter
4 (factory set to 180°F) when the outdoor temperature
is 0°F or below. The minimum set point temperature
shown is 100°F when the outdoor temperature is 60°F
or above. As the outdoor temperature falls the supply
water target temperature increases. For example,
if the outdoor air temperature is 30°F, the set point
temperature for the supply water is 140°F.
6. Once the set point temperature is reached, the
MCBA will turn the burner off and allow the
combustion fan to operate in postpurge for 30
seconds before it turns off.
7. The central heating pump will continue to operate
until the room thermostat has been satisfied.
8. A demand for domestic hot water (DHW) is given
priority on Alpine Series boilers. If a call for DHW
is received while the boiler is responding to a call
for heat, the heating circulator is de-energized until
the call for DHW is satisfied.
F. An indirect water heater thermostat can be connected
between terminals 2 and 4 on the terminal strip. When
this thermostat closes, the central heating circulator will
be turned off and the DHW circulator will be turned on.
ꢂ5
Additionally, either the keypad or the personal computer can
be used to obtain information about the boiler current status
and operating history.
A. Adjusting Parameters via Boiler Keypad
Entering the Access Code
1. With boiler running, toggle the Mode key until you
reach the (STBY) Standby mode.
2. Depress and hold the Step key and then quickly
depress and hold the Mode key for 2 - 6 seconds
until the display reads (CODE). Release the Mode
key, then the Step key. The display should show a
‘C’ followed by a random two digit number.
3. Use the + or - keys to scroll to the number 05.
4. Press the Store key momentarily and watch for the
display to blink twice. If the access code has been
successfully entered, the menu tree will be expanded
to include the items shown inside the dashed lines
in Figure 52. Access to parameters 5 - 42 will be
possible by following the instructions in Section
C. After 15 minutes have passed without any keys
being pressed, access to the expanded menu will
end and the access code will need to be reentered to
regain access to parameters 5 - 42.
Figure 51: Outdoor Reset Curve
II. Field Adjustable Boiler Operating
Parameters
MCBA control factory programmed operating parameters
will result in satisfactory operation under most conditions.
However, because all systems are different, there may exist
situations where boiler operation may be enhanced by
adjusting a few of these parameters in the field. A total of
46 field adjustable parameters are stored in the memory
of the MCBA control. By adjusting these parameters an
installer can fine-tune MCBA operation under different
fields conditions. Refer to Table 25 for the list of adjustable
parameters and their factory settings.
NOTE: Access Code is not required for Parameters 1
thru 4.
Changing Parameters
1. Toggle the Mode key until you reach (PARA)
Parameter mode.
2. Press the Step key to scroll through the parameters
until you reach the desired parameter number.
3. Use the + or - key to scroll to the desired parameter
setting.
Parameters are numbered from “1” to “42-2”. Parameters
“1” thru “4” are accessible by anyone. Parameters “5” thru
“42-2” require an access code to be viewed and adjusted.
4. Press the Store key momentarily and watch for the
display to blink once. The parameter setting has
now stored it new value.
Parameters may be changed by:
•
Using the keypad on the boiler as input device to
make adjustments.
5. When using the keypad, all parameters show up on
the boiler display as two-digit numbers. This creates
the following special situations:
•
Using personal computer, hooked up to MCBA
control via the GPI PC Interface Kit (P/N 101152-
01), available from US Boiler, as input device to
make adjustments.
a. Two parameters are required to define some
of the fan speeds. For example, the maximum
CH fan speed is defined by Parameters 13 and
WaRning
improper setting of parameters can cause unreliable or unsafe operation, resulting in property damage,
personal injury, or loss of life:
•
Changing parameters should only be attempted by a professional heating service technician.
•
•
Do not change any parameters not described in this manual without first consulting the
manufacturer.
After changing any parameters, carefully confirm proper boiler operation before leaving the installation
site.
ꢂ6
Figure 52: Expanded Menu Tree (Cont’d on next page)
ꢂꢂ
Figure 52: Expanded Menu Tree (cont’d.)
Figure 5ꢀ: adjusting Boiler Water Reset Curve
ꢂ8
14; Parameter 13 defines the “thousands” and
hundreds” places and Parameter 14 defines the
“tens” and “ones” places. The ignition fan speed
is only adjustable in increments of hundreds, so
only one parameter (19) is required to define it.
the target supply temperature is always defined
by Parameter 4 when the boiler is responding to
a call for central heat, regardless of the outdoor
temperature. In this case, the settings of Parameters
5, 6, and 7 are meaningless.
IMPORTANT: Field adjustment of fan speeds is
not recommended.
3. Allowing an external control to directly manage
modulation of the boiler. The MCBA control
permits the Alpine to be modulated solely using 0 -
10 VDC signal supplied by an external control,
like multiple - modulating boiler control. When this
function is used, the boiler no longer responds to a
heating thermostat, or an outdoor sensor connected
to a boiler MCBA itself. The boiler will respond
normally to the call from the domestic hot water
thermostat.
b. In some cases one two-digit number defines two
separate parameters. For example, if Parameter
34 is viewed on the boiler display, the “tens
place” is Parameter 34-1 (default value is 0) and
the “ones place” is Parameter 34-2 (default value
is also 0). As viewed on the boiler display, the
factory set Parameter 34 will therefore appear as
“00”. If Parameters 34-2 is changed to accept a
0-10 VDC reading from an AM-4 (see Section
D), Parameter 34 will then read “04” as viewed
on the boiler display.
In order for the boiler MCBA control to
recognize 0 - 10 VDC signal, Parameter 34-2
(“Room Thermostat” - see Table 25) must be
re-programmed. The factory programmed
default value for Parameter 34 is “0”. It must
be re-programmed to value “4” for MCBA to
recognize 0 - 10 VDC signal. Once this parameter
is changed, the boiler will ignore any call from a
thermostat connected across boiler terminals 1 and 2
(see Figures 35 and 36). It will continue to respond
to a call from the indirect water heater thermostat.
Common Field Adjustments
Please note that although it is physically possible to
adjust all parameters listed in Table 25 the parameters
shaded gray need not be adjusted in the field. In case
these parameters are accidentally changed, they should
be restored to default factory settings shown in Table 25
“Parameter Descriptions”.
Parameters permitted to be field adjusted are non-
shaded ones in Table 25. In order to change these
parameters, three subsequent tasks must be performed:
Also, Parameters 2 and 3 (see Table 25) should
be left at factory settings they could be changed
inadvertently (for example, pushing and holding
“+” or “-” key while boiler is in Standby Mode
will change them). If the boiler does not respond
to a call from one or both thermostats, verify that
Parameters 2 and 3 are both “ON”.
1. Adjusting the target boiler supply temperature when
responding to call from an indirect water heater -
The default IWH target supply temperature is 180°F.
Since most indirect water heaters have ratings based
on 180°F boiler supply temperature, it should rarely
be necessary to adjust this parameter.
4. Communication, Fan Speed and Error Modes
In addition to providing access to all field adjustable
parameters, entering the access code also provides
access to three additional mode menus using the
boiler keypad. These are shown in Figure 52:
2. Changing the boiler water reset curve - When an
outdoor temperature sensor is connected to a Alpine
boiler, the MCBA will adjust the target boiler supply
temperature based on outdoor temperature when
the boiler is responding to a call for central heat.
Figure 53 is a graph showing the target boiler supply
temperature as a function of outdoor temperature.
The curve shown in Figure 53 is that obtained with
the factory set parameters. The shape of this curve
may be changed by changing Parameters 4, 5, 6, and
7 as shown in Figure 53. Refer to Part I Section C
for the procedure to change parameters.
a. Communication Mode - This mode does not
currently have any function.
b. Fan Speed Mode - Allows the user to view the
blower fan speed (firing rate is determined by fan
speed).
c. Error Mode - Pressing STEP while in Error mode
allows the user to see the six most recent error
codes.
If the outdoor sensor is not connected to the boiler,
ꢂ9
e. Open Gascom by selecting the “Gascom
1.0” icon on the desk top. Before using the
program for the first time it must be configured
properly to work with the Alpine boiler and
your computer. Go to the menu bar and select
“Gascom” and then “Configuration”. Refer to
the menu tree shown in Figure 55.
B. Adjusting Parameters via Personal Computer with
GCI Interface
1. Operating System Requirements
The GCI Interface requires a PC computer running a
Windows 98/NT/2000 or XP operating system. In
addition, the PC must have an open serial port.
2. Connecting Personal Computer to MCBA Control
a. Connect the serial cable from the GCI to the
computer.
i. From the drop down box labeled
“MCBA1400” select the “Standard
HR7A60Hz” option.
b. Plug in the GCI.
ii. From the drop down box labeled “Interface
c. Open the lower front jacket panel. Loosen the
screws holding the control cover and swing down
the control cover so that the control compartment
is open.
device” select the “CGI232” option.
iii. The “Communication port” setting is the
serial port on the PC to which the GCI
interface is connected. Most often this serial
port will be “COM1”.
d Connect the ribbon cable from the GCI into the
open receptacle on the MCBA next to the ribbon
cable from the boiler display/keypad (Figure 54).
iv. The “Gascom Directory” field will contain
the correct field and will not need to be
changed as long as you accepted all of the
default file locations during installation.
Otherwise, you will need to locate the
Gascom directory on your hard drive and
enter the correct path name in this field.
3. Installing GCI Interface Gascom Software
a. Gascom is the name of the software, which
must be installed on personal computer in order
to communicate with MCBA control via GCI
Interface.
v. If you wish to access Parameters 5 to 42
enter “05” in the “Access Code” field (the
access code will need to be entered every
time the Gascom program is reopened).
b. Insert the Gascom CD in your computer’s
CDROM drive and wait a few seconds for the
software to prompt you to continue setup. Select
“NEXT” to continue the installation. Follow
the prompts to install the software. U.S. Boiler
highly recommends accepting the default
directories recommended.
Changing Parameters
Open the Gascom Program
1. If not already done connect GCI PC Interface, and
install the Gascom software as described in Part II
of this manual and open the Gascom software.
c. The last screen allows the user to select whether
or not to restart the computer. The computer
must be restarted prior to using the Gascom
program.
2. Click on the “Parameters” menu on the top of the
screen.
d. U.S. Boiler recommends the user register the
software on the date of installation however
registration is not required. Registration gives
the user access to our technical support personnel
online as well as information about software
updates. To register the software click on the
“Gascom Online” icon on the desk top and
select “Registration”. You will be asked to fill
out a short form including your e-mail address.
Once the form is submitted a return e-mail will
be sent to you confirming the information you
entered along with your registration number.
3. Click on “Read from MCBA”. After a few seconds,
a list of parameters and their settings will appear
on the screen. Parameters which are not accessible
are grayed out. If the access code has not been
entered in the configuration screen, this will include
Parameters 5-42. Parameters 43 and above are
always grayed out because they are inaccessible in
the field.
Figure 5ꢁ: MCBa Control
80
Figure 55: gascom Menu Tree
4. Double-click on the desired parameter. A window
Using Gascom To Monitor The MCBA
will open with either a field or a pull down list of
options will appear. Enter or select the desired
value for the parameter.
From the Monitor Menu select “Monitor MCBA”.
This will bring up a window which plots the following
information:
5. Click OK.
1. Temperatures:
6. Repeat Steps (3) - (5) to change any other desired
parameters.
Flow - Actual boiler supply temperature
Return - Actual Boiler return temperature
7. After all parameters have been changed, click on the
“Parameters” menu at the top of the screen and then
click on “Write to MCBA”. After a few seconds,
the display on the boiler will blink. This indicates
that the parameters are written to the control and are
in effect.
Outdoor - Temperature being read by outdoor sensor
if it is connected. If it is not, temperature reading is
“-22”.
Fluegas - Flue gas temperature
Set - Target boiler supply temperature
2. Status:
Field Adjustable Parameters
Refer to Field Adjustable Parameters under A.
Adjusting Parameters via Boiler Keypad on pages 76
and 79 of this manual.
Room - Room thermostat (“1” = Calling, “0” = Not
Calling)
81
Hotwater - Indirect water heater thermostat (“1” =
Calling, “0” = Not Calling)
2. If the signal is lower then 6 VDC, check the
continuity of the ground wire between the ignitor
and the junction box. If the ground wire is suspect
replace the ground wire.
Pump - Heating circulator (“1” = On, “0” = Off)
Air-switch - Status of air pressure switch (“1” =
Closed, “0” = Open)
3. If the ground wire is in good condition, remove
the ignitor and flame sensor to inspect the ceramic
insulator for cracks. If none are found, sand off
any oxide deposits which formed on the electrodes.
If the insulator is cracked or the electrode cannot
be properly cleaned, replace the ignitor and flame
sensor. When replacing the ignitor and flame sensor,
be sure to replace the ignitor and flame sensor
gasket as well.
Gaspressure - This is actually the status of the high
limit (“1” = Closed, “0” = Open)
GasValve - Status of gas valve (“1” = Open , “0” =
Closed)
Flame - Shows whether the MCBA detects the
presence of the burner flame (“1” = Flame, “0” = No
Flame)
4. Other problems that can cause a low flame signal
DHW Pump - Indirect water heater circulator (“1” =
On, “0” = Off)
include:
•
An improperly adjusted throttle (confirm that the
CO2 is within the limits shown in the installation
manual).
3. RPM:
Fan - Actual speed of fan
Set - Target speed of fan.
•
•
•
Fouling of the burner (remove the burner and
clean with compressed air).
Reading the MCBA Error Log
Low inlet gas pressure (verify that gas pressure
is within the limits shown on the rating plate).
1. The MCBA keeps a log of the last six error codes.
To view these error codes select “Read from
MCBA” from the Error Menu.
Grounded 24 VAC or sensor wiring (this problem
will result in no flame voltage reading, but will
normally not result in an E02 error because there
is still adequate flame current).
2. This data can be saved as a file to disk by selecting
“Save to file” from the Error Menu or printed by
selecting “Print” from the same menu.
3. Error codes can also be removed from the memory
of the MCBA by selecting “Clear in MCBA” from
the Error Menu.
B. NTC Temperature Sensors
1. The supply, return, flue, and outdoor reset sensors
used on the Alpine are of the resistance type.
III. Component Test Procedures
A. Flame Signal Check
2. The Table 27 shows the range of resistance values
for these sensors at various temperatures.
1. The flame signal can be checked between terminal
number 7 on the low voltage terminal strip and
ground. A good signal reading should be 6 VDC or
greater.
82
Table 2ꢂ: nTC Sensor Resistance Values
8ꢀ
Xiii. Service and Maintenance
DangER
This boiler uses flammable gas, high voltage electricity, moving parts, and very hot water under high
pressure. assure that all gas and electric power supplies are off and that the water temperature is cool
before attempting any disassembly or service.
Do not attempt any service work if gas is present in the air in the vicinity of the boiler. never modify,
remove or tamper with any control device.
WaRning
This boiler must only be serviced and repaired by skilled and experienced service technicians.
if any controls are replaced, they must be replaced with identical models.
Read, understand and follow all the instructions and warnings contained in all the sections of this
manual.
if any electrical wires are disconnected during service, clearly label the wires and assure that the wires
are reconnected properly.
never jump out or bypass any safety or operating control or component of this boiler.
Read, understand and follow all the instructions and warnings contained in aLL of the component
instruction manuals.
assure that all safety and operating controls and components are operating properly before placing
the boiler back in service.
3. Inspect the water and gas lines to verify they are
free from leaks. Call the service technician to make
repairs if required.
nOTiCE
Warranty does not cover boiler damage or
malfunction if the following steps are not
performed at the intervals specified.
CaUTiOn
Water leaks can cause severe corrosion damage
to the boiler or other system components.
A. Continuously:
1. Keep the area around the boiler free from
combustible materials, gasoline and other flammable
vapors and liquids.
immediately repair any leaks found.
C. Annual Inspections and Service: In addition to
the inspections listed above the following should be
performed by a service technician once every year.
2. Keep the area around the combustion air inlet
terminal free from contaminates .
1. If equipped, test the low water cutoff by pressing
the “Test” button located at its end. The yellow
light should come on and “E12” should flash on
the display. Push the reset button on the display to
restore normal operation. If the yellow light does
not come on, determine why the low water cutoff is
not working properly.
3. Keep the boiler room ventilation openings open and
unobstructed.
B. Monthly Inspections:
1. Inspect the vent piping and outside air intake piping
to verify they are open, unobstructed and free from
leakage or deterioration. Call the service technician
to make repairs if needed.
2. Follow the procedure for turning the boiler off
found in the Alpine™ Series Lighting and Operating
Instructions.
2. Inspect the condensate drain system to verify it is
leak tight, open and unobstructed. Call the service
technician if the condensate drain system requires
maintenance.
8ꢁ
10. Reinstall the burner, burner hood and fan/gas valve
assembly.
3. Inspect the wiring to verify the conductors are in
good condition and attached securely.
11. Reconnect any wiring which has been disconnected.
CaUTiOn
12. Inspect the heating system and correct any other
deficiencies prior to restarting the boiler.
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation. Verify
proper operation after servicing.
13. Follow Section XI System Start-up before leaving
installation.
14. Perform the combustion test outlined in Section XI
System Start-up.
4. Remove the ignition electrode and inspect it for
oxides. Clean the oxides from the electrode with
steel wool. Do not use sandpaper for the cleaning.
Inspect the ceramic insulator for cracks and replace
the ignitor assembly if necessary. Check the ignitor
electrode spacing gap. Refer to Figure 56 “Ignitor
Electrode Gap” for details.
15. Verify that the system PH is between 8.2 and 9.5/.
16. Check for vent terminal obstructions and clean as
necessary.
D. Recommended Heating System Water Treatment
Products:
1. System Cleaning and Conditioning:
a. The following heating system water treatment
products are recommended for an initial existing
heating system sludge removal, initial boiler
cleaning from copper dust, flux residue and any
boiler debris and for preventive treatment as
corrosion/scale inhibitors:
i. Fernox™ Restorer (universal cleaner, sludge
remover, scale remover, flux residue/debris
remover, corrosion inhibitor)
Figure 56: ignitor Electrode gap
5. Remove the fan/gas valve assembly from the burner
hood. Inspect for lint and dust. If significant lint
and dust are found, disassemble the fan/gas valve
assembly to expose the swirlplate and fan inlet (see
the exploded diagram in the parts list at the back of
this manual). Vacuum these parts as required, being
careful not to damage the vanes on the swirlplate.
ii. Fernox™ Protector (Alphi 11, CH#, Copal)
(sludge remover, corrosion inhibitor)
Follow manufacturer application procedure
for proper heating system/boiler cleaning
and preventive treatment.
Above referenced products are available
from Cookson Electronics Company, 4100
Sixth Avenue, Altoona, PA 16602, Tel:
(814) 946-1611 and/or selected HVAC
distributors. Contact US Boiler for specific
details.
6. Remove the burner hood to access the burner and
the combustion chamber.
7. Remove the burner and vacuum any dust or lint
from the burner. If the burner shows signs of
deterioration or corrosion, replace it immediately.
Inspect the burner gasket and replace, if necessary.
iii. Equivalent system water treatment products
may be used in lieu of products referenced
above.
8. Inspect the heat exchanger, clean and vacuum any
debris found on the surfaces. A soft nylon brush
must be used for cleaning. Remove insulation disc
and clean the surfaces by flushing with clean water.
Drain and flush the inside of the heat exchanger
and condensate collector. Do not use any cleaning
agents or solvents. Re-install insulation disc.
2. System Freeze Protection:
a. The following heating system freeze protection
products are recommended for Alpine boilers:
i. Fernox™ Protector Alphi 11 (combined
antifreeze and inhibitor).
Follow manufacturer application procedure
to insure proper antifreeze concentration and
inhibitor level.
Above referenced product is available from
Cookson Electronics Company, 4100 Sixth
Avenue, Altoona, PA 16602, Tel: (814) 946-
1611 and/or selected HVAC distributors.
Contact US Boiler for specific details.
9. Inspect the condensate trap to verify it is open and
free from debris. Inspect condensate line integrity
between boiler and condensate neutralizer (if used)
and condensate neutralizer and the drain. Clean/
repair if needed.
If the condensate neutralizer is used, check pH
before and after the neutralizer to determine
neutralizing effectiveness. Replace limestone chips
and clean out the neutralizer if needed.
85
f. Reconnect the switch wire pigtails to the boiler
wiring and secure with wire nuts.
b. Equivalent system freeze protection products
may be used in lieu of product referenced
above. In general, freeze protection for new or
existing systems must use specially formulated
glycol, which contains inhibitors, preventing
the glycol from attacking the metallic system
components. Insure that system fluid contains
proper glycol concentration and inhibitor level.
The system should be tested at least once a year
and as recommended by the manufacturer of the
glycol solution. Allowance should be made for
expansion of the glycol solution.
g. Restore power supply to boiler. Fill up the trap
(see Section V “Condensate Disposal”) and
verify the switch operation.
2. Condensate Trap Removal and Reinstallation:
a. Disconnect power supply to boiler.
b. Remove two (2) wire nuts and disconnect
overflow switch wire pigtails from boiler wiring.
c. Disconnect pressure switch hose from
condensate trap.
d. Disconnect outside condensate compression
fitting from condensate trap stab.
CaUTiOn
e. Using pliers, release spring clip securing the
overflow switch to condensate trap body and
remove the switch. Note that the switch has
factory applied silicon adhesive seal, which may
have to be carefully cut all around to facilitate
the switch removal.
Use only inhibited propylene glycol solutions
specifically formulated for hydronic systems.
Do not use ethylene glycol, which is toxic and
can attack gaskets and seals used in hydronic
systems.
f. Using pliers, release spring clip securing
condensate trap body to the heat exchanger
bottom drain stab.
E. Condensate Overflow Switch and Condensate Trap
Removal and Replacement:
For removal or replacement of the condensate overflow
switch and/or condensate trap follow the steps below.
For parts identification, refer to Section XV “Repair
Parts”.
g. Firstly, pull the trap downwards to release from
the heat exchanger bottom drain stab; secondly,
pull the trap end from left side jacket panel
sealing grommet and remove the trap from
boiler.
1. Condensate Overflow Switch Removal and
Replacement:
h. To reinstall the trap, reverse above steps.
a. Disconnect power supply to boiler.
i. If the original condensate overflow switch is
to be re-used, follow the appropriate switch
removal steps from Condensate Overflow Switch
Removal and Replacement procedure above.
b. Remove two (2) wire nuts and disconnect
overflow switch wire pigtails from boiler wiring.
c. Using pliers, release spring clip securing the
overflow switch to condensate trap body and
remove the switch. Note that the switch has
factory applied silicon adhesive seal, which may
have to be carefully cut all around to facilitate
the switch removal.
j. Insure that fresh silicon sealant is applied to
the overflow switch threads, and the switch is
properly oriented relative to the trap body -
the arrow molded into the switch hex side end
must face down for proper switch operation.
See Figure 57 “Condensate Overflow Switch
Orientation” for details. Insure that pressure
switch hose is reconnected to the trap.
d. Insure the trap overflow switch port is not
obstructed with silicon seal debris, clean as
needed.
k. Restore power supply to boiler. Fill up the trap
(see Section V “Condensate Disposal”) and
verify the switch operation.
e. Apply silicon seal to the replacement switch
threads and install the switch into the trap
body making sure it is properly oriented - the
arrow molded into the switch hex end side
must face down for proper switch operation.
See Figure 57 “Condensate Overflow Switch
Orientation” for details.
86
8ꢂ
XiV: Troubleshooting
WaRning
Turn off power to boiler before replacing fuses or working on wiring.
A. Troubleshooting problems where no error code is displayed. Refer to Table 28 for problems and possible causes.
Table 28: no Error Code Displayed
CONDITION
POSSIBLE CAUSES
Display Blank, Fan off, LWCO lights off
• No 120VAC Power at boiler. Check breaker and wiring between breaker panel and boiler
• Loose 120VAC connection wiring between boiler J-Box and MCBA
• Blown “F1” fuse in MCBA (see Figure 58 for location). Replace with 5A fuse provided
Display Panel Blank, Fan running
• Defective AT250 transformer
Display reads “U.125” continuously, Fan running
• Blown “F3” fuse in MCBA (see Figure 58 for location). Replace with 4A slow-blow fuse
provided
Boiler not responding to call for heat,
Status code on display =”0” (see Figure 50)
• Boiler is not seeing call for heat. Check thermostat or zone wiring for loose connection,
miswiring, or defective thermostat/zone control.
• Loose ribbon cable
Boiler fires, but display panel is blank
• Defective display
Figure 58: MBCa Fuse Location
88
B. Trouble shooting problems where a soft lockout code is displayed. When a soft lockout occurs, the boiler will shut down
and the display will alternate between the number “9” and the letter “b” followed by a two digit service code. The boiler will
automatically restart once the condition that caused the lockout is corrected.
Table 29: Soft Lockout Codes Displayed
CODE CONDITION
POSSIBLE CAUSES
• Blockage in intake or vent system.
• Vent and/or intake system not constructed in accordance with Part VI.
• Blocked or leaking pressure switch tubing
• Heat exchanger or burner blockage
b 08
Pressure switch circuit open
• Terminals exposed to high winds
• Blockage in condensate trap above vent.
• Heating load at time of error was far below the minimum firing rate of the
boiler
MCBA supply sensor detected temperatures in excess
of 200°F
b 18
b 19
• Defective primary pump or no flow in primary loop (Piping Method 1)
• Control system miswired so that boiler operation is permitted when no zones
are calling
• See possible causes for “b18”
• Flow through boiler reversed
• Sensor wiring reversed
MCBA return sensor detected temperatures in excess
of 200°F
• Flow through boiler reversed. Verify correct piping and pump orientation.
• No boiler water flow. Verify that system is purged of air and that appropriate
valves are open.
MCBA is reading a return sensor temperature higher
than the supply sensor temperature. Condition must be
present for at least 75s for this error code to appear.
b 24
b 25
• Sensor wiring reversed.
• Supply or return sensor defective.
• See possible causes for “b18”
Supply water temperature has risen too quickly
• Inadequate boiler water flow. Verify that pump is operating and that pump
and piping are sized per Part VIII of this manual
• See possible causes for “b18”
Boiler safety limit, or external limit wired across
terminals 3&4, is open.
b 26
b 30
• Defective supply sensor.
Temperature rise between supply and return is too
high.
• Inadequate boiler water flow. Verify that pump is operating and that pump
and piping are sized per Part VIII of this manual
• Blockage in pressure switch hose
• Pressure switch wires shorted together
• Defective pressure switch
b 61
b 65
Pressure switch circuit closed with fan off
Fan is not achieving set point speed
• Loose or miswired fan speed harness (if “b61” error code is observed while
fan is running)
• Loose or incorrect fan speed control connection
• Defective fan
89
the condition that caused the lockout is corrected, the
boiler will need to be manually reset using the RESET
button on the display.
C. Trouble shooting problems where a hard lockout
code is displayed. When a hard lockout occurs, the
boiler will shut down and the display will flash the
letter “E” followed by a two digit service code. Once
Table ꢀ0: Hard Lockout Codes Displayed
CODE
CONDITION
POSSIBLE CAUSES
A flame signal was present when there should
be no flame.
• Defective gas valve - make sure inlet pressure is below maximum on rating plate
before replacing valve.
E 00
• No gas pressure
• Gas pressure under minimum value shown on rating plate
• Gas line not completely purged of air
• Defective Electrode
E 02
Flame failure after 5 tries to restart
• Loose burner ground connection
• Defective Ignition Cable
• Defective gas valve (check for 24 VDC at harness during trial for ignition before
replacing valve)
• Air-fuel mixture out of adjustment - consult factory
• Loose or defective gas valve harness. Check electrical connections.
• Defective gas valve (check for 24 VDC at harness during trial for ignition before
replacing valve)
E 03
E 04
Gas valve error
• Some other error on this list occurred and power to the boiler was then
interrupted. Reset control and see if hard lockout reoccurs.
Power failure occurred after lockout
E 05
E 06
E 07
E 11
Internal control failure
• Reset the control. If problem reoccurs, replace the MCBA.
• If yellow light on LWCO is on, system is low on water
• If neither yellow nor green light is on, check LWCO harness and check for
24VAC across AT140 transformer
E 12
Low water cut-off circuit open
E 13
E 14
E 15
E 16
E 17
Internal control failure
• Reset the control. If problem reoccurs, replace the MCBA.
MCBA supply sensor detected temperatures in
excess of 200°F for an extended period of time
E 18
E 19
• See possible causes for “b18” error. Also, check safety limit for proper operation.
• See possible causes for “b19” error.
MCBA return sensor detected temperatures in
excess of 200°F for an extended period of time
• Loose connection in 120 VAC fan wiring
• Loose or miswired fan speed harness
• Defective fan
Blower is not running when it should or fan speed
signal not being detected by MCBA
E 28
• Miswired fan speed harness
• Defective fan
E 29
E 31
E 32
E 35
E 36
E 37
Blower fan speed has not returned to zero rpm
Shorted supply temperature sensor
• Shorted or miswired supply sensor wiring
• Defective supply sensor
• Shorted or miswired return sensor wiring
• Defective return sensor
Shorted return temperature sensor
• Shorted or miswired flue temp sensor wiring
• Defective flue temp sensor
Flue gas temperature sensor short circuit
Supply water temperature sensor circuit open
Return water temperature sensor circuit open
• Loose or miswired supply sensor wiring
• Defective supply sensor
• Loose or miswired return sensor wiring
• Defective return sensor
• Loose or miswired flue temp sensor wiring
• Defective flue temp sensor
E 40
E 44
Flue gas temperature sensor circuit open
Internal control failure
• Reset the control. If problem reoccurs, replace the MCBA.
• Heat exchanger needs to be cleaned
• Boiler over-fired
E 52
Flue gas temperature over 230°F
• Air-fuel mixture out of adjustment - consult factory
E 60
Internal control failure
• Reset the control. If problem reoccurs, replace the MCBA.
90
XV. Repair Parts
All Alpine™ Series Repair Parts may be obtained through your local Burnham Wholesale distributor.
Should you require assistance in locating a Burnham distributor in your area, or have questions regarding
the availability of Burnham products or repair parts, please contact Burnham Customer Service at
(717) 481-8400 or Fax (717) 481-8408.
91
(Quantity) Part Number
ALP150 ALP210
Key
No.
Description
ALP080
ALP105
ALP285
ALP399
1
2
3
4
5
6
7
Heat Exchanger, Burner, Etc. (Key No’s 2 thru 23)
Heat Exchanger Assembly
101520-01 101521-01 101522-01 101523-01 101524-01 101525-01
101710-01 101711-01 101712-01 101713-01 101714-01 101715-01
101717-01 101718-01 101719-01 101720-01 101721-01 101722-01
(6) 101724-01
Burner Assembly
M6x1 Hex Flange Nut (Not Shown)
Gas/Air Intake Duct Assembly (Not Shown)
Gas/Air Intake Duct Weldment (Not Shown)
Burner Plate (Not Shown)
101725-01
101725-02
N/A
101727-01
Burner Plate Insulation
(Warning: Contains RCF, Not Shown)
8
101728-01
9
Burner Plate Inner Seal (Not Shown)
Burner Plate Outer Seal (Not Shown)
Burner Head (Not Shown)
Burner Head Seal (Not Shown)
Ignitor
101729-01
101730-01
10
11
12
13
14
15
16
17
101731-01 101731-02 101731-03 101731-04 101731-05 101731-06
101732-01
101733-01
101734-01
101735-01
101736-01
101737-01
Flame Sensor
Observation Glass Retaining Plate
Observation Glass
Observation Glass Gasket
M3x6 mm Socket Hd Thread Forming Screw,
T10 Drive (Not Shown)
18
(2) 101738-01
19
20
Ignitor Gasket (Not Shown)
101740-01
101741-01
Flame Sensor Gasket (Not Shown)
M4x8 mm Socket Hd Cap Thread Forming Screw,
X20 Drive (Not Shown)
21
22
(4) 101739-01
M5x14 mm Pan Hd Thread Forming Screw, T25 Drive
(Not Shown)
101742-01
23
31
32
33
42
Insulation Disc (Warning: Contains RCF, Not Shown)
Air Vent Valve
101996-01
101586-01
(2) 101685-01
101653-01
101454-01
Water Temp Sensor
High Limit
Wire Harness (Not Shown)
92
(Quantity) Part Number
ALP150 ALP210
Key
No.
Description
ALP080
ALP105
ALP285
ALP399
Gas Train Assembly
(Key No’s 24 thru 29)
23
101585-01 101585-02 101585-03 101585-04 101585-05 101585-06
24
25
26
27
28
29
Blower
101527-01
101704-01
101528-01 101529-01
101704-02 101704-03
101345-01
N/A
101703-04 101703-05 101703-06
Included with Gas Valve (Key 28)
101530-01
Blower Inlet Shroud Assembly
Blower Outlet Gasket
Blower Mounting Plate
Gas Valve
101704-04
101703-01
101703-03
Gas Valve Harness with Plug
9ꢀ
(Quantity) Part Number
ALP150 ALP210
Key
No.
Description
ALP080
ALP105
ALP285
ALP399
35
36
37
38
39
40
41
Air Pressure Switch
80160762
7016039
101862-01
7016046
Air Pressure Switch Hose
Rubber Grommet, Condensate Trap
Condensate Trap, Blow Molded
Spring Clip, Condensate Trap
Blocked Condensate Drain Switch
Condensate Comp. Fitting
101595-01
101239-01
(2) 101632-01
101587-01
101546-01
9ꢁ
(Quantity) Part Number
ALP150 ALP210
Key
No.
Description
ALP080
ALP105
ALP285
ALP399
42
43
44
Wiring Harness (Not Shown)
101454-01
MCBA Slide Out Assembly
(Includes all parts shown)
101230-01
101219-01
Control Panel, MCBA
10186
6-05
45A MCBA (programmed - 0-2000’ or 0-7000’) 101866-01 101866-02 101866-03 101866-04
101866-06
45B MCBA (programmed - 2001 - 7000’)
101866-08 101866-09 101866-10 101866-11
N/A
46
47
48
49
50
MCBA Transformer
100474-01
100450-01
101331-01
101609-01
(4) 101636-01
MCBA Display Board
MCBA Display Board Cable
Label, MCBA Display
MCBA Display Spacer
95
(Quantity) Part Number
ALP150 ALP210
Key
No.
Description
ALP080
ALP105
ALP285
ALP399
30
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
Rubber Grommet, Gas Line
Jacket, Rear/Bottom Panel
Lower Front Door Assembly
Draw Latch
820SOL0001
101217-02 101217-03 101217-04 101764-01 101764-02
101227-01 101227-02
101638-01
101217-01
101037-01
Jacket, Left Side Panel
Jacket, Right Side Panel
Partition Shelf Assembly
Jacket Support Bracket
Jacket, Top Panel
101215-01
101216-01
101536-01
101215-02 101215-03 101215-04 101765-01 101765-02
101216-02 101216-03 101216-04 101766-01 101766-02
101536-02 101536-03 101536-04 101536-05 101536-06
101593-01
101218-01
101232-01
101224-01
101218-02 101218-03 101218-04 101218-05 101218-06
101232-02 101232-03 101232-04 101232-05 101232-06
101224-02 101224-03 101224-04 101224-05 101224-06
101326-01
Bracket Assembly, Right Side
Side Bracket
Junction Box Cover
Bracket, Rear HX Support
Bracket, Left Clip
101381-01
101507-01
101507-02
Bracket, Right Clip
101508-01
101245-01
101509-01
Rubber Pad, Right Clip
Jacket, Upper Front Panel
Gasket, Header (All Three)
Gasket, Header, 1” NPT
Gasket, Header, 1” & 3/4” NPT
Gasket, Header, Duo Size
Gasket, Header, Duo Size
101240-01
N/A
N/A
101243-01
101252-01
N/A
N/A
N/A
N/A
N/A
101372-02 101372-03
101372-01
96
(Quantity) Part Number
ALP150 ALP210
Key
No.
Description
ALP080
ALP105
ALP285
ALP399
34
42
72
76
Flue Temp Sensor
101687-01
101454-01
Wire Harness (Not Shown)
Concentric Vent Collar with Viton Cap
Vent Terminal Kit
101598-01
101808-01
101599-01
101809-01
9ꢂ
(Quantity) Part Number
ALP150 ALP210
Key No. Description
ALP080
ALP105
ALP285
ALP399
101777-01
101777-02
101777-03
MiSCELLanEOUS PaRTS CaRTOn
73
74
75
77
78
79
80
Temperature/Pressure Gauge
External Gas Shut Off Valve
Relief Valve
8056169
806SOL0005
81660363
101615-01
81660302
Boiler Drain Valve
806603061
(4) 101679-01
(12) 80860743
(1) 101639-01
Boiler Stacking Brackets
Boiler Stacking Bracket Screws
Outdoor Temperature Sensor
98
important Product Safety information
Refractory Ceramic Fiber Product
Warning:
The Repair Parts list designates parts that contain refractory ceramic fibers
(RCF). RCF has been classified as a possible human carcinogen. When
exposed to temperatures about 1805°F, such as during direct flame contact,
RCF changes into crystalline silica, a known carcinogen. When disturbed as a
result of servicing or repair, these substances become airborne and, if inhaled,
may be hazardous to your health.
AVOID Breathing Fiber Particulates and Dust
Precautionary Measures:
Do not remove or replace RCF parts or attempt any service or repair work
involving RCF without wearing the following protective gear:
1. A National Institute for Occupational Safety and Health (NIOSH)
approved respirator
2. Long sleeved, loose fitting clothing
3. Gloves
4. Eye Protection
• Take steps to assure adequate ventilation.
• Wash all exposed body areas gently with soap and water after contact.
• Wash work clothes separately from other laundry and rinse washing
machine after use to avoid contaminating other clothes.
• Discard used RCF components by sealing in an airtight plastic bag. RCF
and crystalline silica are not classified as hazardous wastes in the United
States and Canada.
First aid Procedures:
• If contact with eyes: Flush with water for at least 15 minutes. Seek
immediate medical attention if irritation persists.
• If contact with skin: Wash affected area gently with soap and water.
Seek immediate medical attention if irritation persists.
• If breathing difficulty develops: Leave the area and move to a location
with clean fresh air. Seek immediate medical attention if breathing
difficulties persist.
• Ingestion: Do not induce vomiting. Drink plenty of water. Seek
immediate medical attention.
99
Limited Warranty
FOR RESIDENTIAL GRADE STAINLESS STEEL WATER BOILERS
Subject to the terms and conditions set forth below, U.S. Boiler Company, Inc.
e. Boilers installed outside the 48 contiguous United States, the State of Alaska,
and Canada.
Lancaster, Pennsylvania hereby extends the following limited warranties to the
original owner of a residential grade stainless steel water boiler manufactured and
shipped on or after november 1, 2007:
f. Damage to the boiler and /or property due to installation or operation of the
boiler that is not in accordance with the boiler installation and operating instruction
manual.
ONEYEAR LIMITED WARRANTY ON RESIDENTIAL
STAINLESS STEEL GRADE WATER BOILERS
g. Any damage of failure of the boiler resulting from hard water or scale buildup in the
heat exchanger.
U.S. Boiler Company, Inc. warrants to the original owner that its residential grade
stainless steel water boilers comply at the time of manufacture with recognized
hydronic industry standards and requirements then in effect and will be free of
defects in material and workmanship under normal usage for a period of one year
from the date of original installation. If any part of a stainless steel water boiler is
found to be defective in material or workmanship during this one year period, U.S.
Boiler Company, Inc. will, at its option, repair or replace the defective part.
h. Any damage caused by improper fuels, fuel additives or contaminated combustion
air that may cause fireside corrosion and/or clogging of the burner or heat
exchanger.
i. Any damage resulting from combustion air contaminated with particulate which
cause clogging of the burner or combustion chamber including but not limited to
sheetrock or plasterboard particles, dirt, and dust particulate. (See Air Ventilation
section of the Installation and Operating Manual furnished with the unit)
TWELVEYEAR LIMITED WARRANTY ON HEAT EXCHANGER
The second through 7th year warranty covers only the heat exchanger. All other
component parts furnished by U.S. Boiler Company, Inc., but purchased from other
manufacturers, shall be limited to their warranties, if any.
j. Any damage, defects or malfunctions resulting from improper operation,
maintenance, misuse, abuse, accident, negligence including but not limited to
operation with insufficient water flow, improper water level, improper water
chemistry, or damage from freezing. (See System Piping, Start up and Checkout,
Operation and Service and Maintenance sections of the Installation and
Operating Manual furnished with the unit)
U.S. Boiler Company, Inc. warrants to the original owner and at its original place
of installation that the heat exchanger of its residential grade stainless steel water
boilers will remain free from defects in material and workmanship under normal
usage for seven years. If a claim is made under this warranty during the first seven
years from the date of original installation, U.S. Boiler Company, Inc. will, at its
option, repair or replace the heat exchanger. If a claim is made under this warranty
after the expiration of seven years and up to twelve years from the date of original
installation, U.S. Boiler Company, Inc. will, at its option and upon payment of the
pro-rated service charge set forth below, repair or replace the stainless steel heat
exchanger. The service charge applicable to a stainless steel heat exchanger
warranty claim is based upon the number of years the heat exchanger has been
in service and will be determined as a percentage of the retail price of the heat
exchanger model involved at the time the warranty claim is made as follows:
k. Any damage caused by water side clogging due to dirty systems or corrosion
products from the system. (See System Piping section of the Installation and
Operating Manual furnished with the unit)
l. Any damage resulting from natural disaster.
m. Damage or malfunction due to the lack of required maintenance outlined in the
Service and Maintenance section of the Installation and Operating Manual
furnished with the unit.
6. Exclusive Remedy: U.S. Boiler Company, Inc. obligation for any breach of these
warranties is limited to the repair or replacement of its parts in accordance with the
terms and conditions of these warranties.
years in Service
1-7
8
9
10
50
11
60
12
70
13 +
100
7. Limitation of Damages: Under no circumstances shall U.S. Boiler Company,
Inc. be liable for incidental, indirect, special or consequential damages of any kind
whatsoever under these warranties, including, but not limited to, injury or damage to
persons or property and damages for loss of use, inconvenience or loss of time. U.S.
Boiler Company, Inc. liability under these warranties shall under no circumstances
exceed the purchase price paid by the owner for the residential grade water boiler
involved. Some states do not allow the exclusion or limitation of incidental or
consequential damages, so the above limitation or exclusion may not apply to you.
Service Charge
as % of
Retail Price
no
Charge
30
40
nOTE: If the heat exchanger model involved is no longer available due to product
obsolescence or redesign, the value used to establish the retail price will be the
published price as shown in the Burnham hydronics Repair Parts Price Sheet
where the heat exchanger last appeared or the current retail price of the then
nearest equivalent heat exchanger.
8. Limitation of Warranties: These warranties set forth the entire obligation of U.S.
Boiler Company, Inc. with respect to any defect in a residential grade stainless
steel water boiler and U.S. Boiler Company, Inc. shall have no express obligations,
responsibilities or liabilities of any kind whatsoever other than those set forth herein.
These warranties are given in lieu of all other express warranties.
ADDITIONAL TERMS AND CONDITIONS
1. Applicability: The limited warranties set forth above are extended only to the
original owner at the original place of installation within the United States and
Canada. These warranties are applicable only to stainless steel water boilers
designated as residential grade by U.S. Boiler Company, Inc. and installed in a
single or two-family residence and do not apply to steam boilers of any kind, any
application other than for space heating or to commercial grade boilers.
ALL APPLICABLE IMPLIED WARRAnTIES, If Any, InCLUDIng Any WARRAnTy
Of MERChAnTABILITy OR fITnESS fOR A PARTICULAR PURPOSE ARE
ExPRESSLy LIMITED In DURATIOn TO A PERIOD Of OnE yEAR ExCEPT ThAT
IMPLIED WARRAnTIES, If Any, APPLICABLE TO ThE hEAT ExChAngER In A
RESIDEnTIAL STAInLESS STEEL gRADE WATER BOILER ShALL ExTEnD TO
ThE ORIgInAL OWnER fOR A MAxIMUM Of TWELVE yEARS AT ThE ORIgInAL
PLACE Of InSTALLATIOn. SOME STATES DO nO ALLOW LIMITATIOn On hOW
LOng An IMPLIED WARRAnTy LASTS, SO ThE ABOVE LIMITATIOn MAy nOT
APPLy TO yOU.
2. Components Manufactured by Others: Upon expiration of the one year limited
warranty on residential grade stainless steel water boilers, all boiler components
manufactured by others but furnished by U.S. Boiler Company, Inc. (such as
burners, gas valves and controls) will be subject only to the manufacturer’s
warranty, if any.
PROCEDURE FOR OBTAINING WARRANTY SERVICE
3. Proper Installation: The warranties extended by U.S. Boiler Company, Inc. are
conditioned upon the installation of the residential grade stainless steel water boiler
in strict compliance with U.S. Boiler Company, Inc. installation instructions. U. S.
Boiler Company, Inc. specifically disclaims liability of any kind caused by or relating
to improper installation.
In order to assure prompt warranty service, the owner is requested to complete and
mail the attached Warranty Card within ten days after the installation of the boiler,
although failure to comply with this request will not void the owner’s rights under these
warranties.
Upon discovery of a condition believed to be related to a defect in material or
workmanship covered by these warranties, the owner should notify the installer, who
will in turn notify the distributor. If this action is not possible or does not produce a
prompt response, the owner should write to U.S. Boiler Company, Inc., Burnham
hydronics, at P.O. Box 3079, Lancaster, PA 17604, giving full particulars in support
of the claim.
4. Proper Use and Maintenance: The warranties extended by U.S. Boiler Company,
Inc. conditioned upon the use of the residential grade stainless steel water boiler for
its intended purposes and its maintenance in accordance with U.S. Boiler Company,
Inc. requirements and hydronics industry standards.
5. This warranty does not cover the following:
a. Expenses for removal or re-installation. The homeowner will be responsible for
the cost of removing and reinstalling the alleged defective part or its replacement
and all labor and material connected therewith, and transportation to and from
U.S. Boiler Company, Inc.
The owner is required to make available for inspection by U.S. Boiler Company, Inc.
or its representative the parts claimed to be defective and, if requested by U.S. Boiler
Company, Inc. to ship these parts prepaid to U.S. Boiler Company, Inc. at the above
address for inspection or repair. In addition, the owner agrees to make all reasonable
efforts to settle any disagreement arising in connection with a claim before resorting
to legal remedies in the courts.
b. Components that are part of the heating system but were not furnished by
U.S. Boiler Company, Inc., as part of the residential boiler.
c. Improper burner adjustment, control settings, care or maintenance.
ThIS WARRAnTy gIVES yOU SPECIfIC LEgAL RIghTS AnD yOU MAy ALSO
hAVE OThER RIghTS WhICh VARy fROM STATE TO STATE.
d. This warranty cannot be considered as a guarantee of workmanship of an
installer connected with the installation of the U.S. Boiler Company, Inc. boiler,
or as imposing on U.S. Boiler Company, Inc. liability of any nature for
unsatisfactory performance as a result of faulty workmanship in the installation,
which liability is expressly disclaimed.
10/07
|
Alpine Electronics Car Stereo System XMDALP100 User Manual
Asus Car Video System VH238H User Manual
Audiovox ACD 13 User Manual
Blaupunkt IVMR 1042 User Manual
Bryan Boilers Broile System User Manual
Burnham Independence IN11(3) User Manual
Canon VIXIA HV30 User Manual
FujiFilm 16125864 User Manual
Hoist Fitness Bicycle Accessories CD2400 User Manual
JVC GR FX16 User Manual