Burnham 8H User Manual

INSTALLATION, OPERATING AND  
SERVICE INSTRUCTIONS FOR  
SERIES 8H  
GAS - FIRED BOILER  
3050579  
For service or repairs to boiler, call your heating contractor. When seeking information on boiler,  
provide Boiler Model Number and Serial Number as shown on Rating Label.  
Boiler Model Number  
_8_ _ _ _ _ - _ _ _ _  
Heating Contractor  
Boiler Serial Number  
Installation Date  
6_ _ _ _ _ _ _  
Phone Number  
Address  
Commercial Boilers  
Price - $5.00  
8ꢀ4ꢀ602ꢀR3-6/ꢀ0  
WARNING  
This boiler requires regular maintenance and service to operate safely. Follow the instructions contained  
in this manual.  
Improperinstallation,adjustment,alteration,serviceormaintenancecancausepropertydamage,personal  
injury or loss of life. Read and understand the entire manual before attempting installation, start-up  
operation, or service. Installation and service must be performed only by an knowledgeable, experienced,  
and skilled installer or service agency.  
This boiler must be properly vented.  
This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate  
combustion and ventilation air.  
The interior of the venting system must be inspected and cleaned before the start of the heating season  
and should be inspected periodically throughout the heating season for any obstructions. A clean and  
unobstructed venting system is necessary to allow noxious fumes that could cause injury or loss of life  
to vent safely and will contribute toward maintaining the boiler’s efficiency.  
Installation is not complete unless a pressure relief valve is installed into the tapping located on the top  
of boiler - See the Water Trim and Piping Section of this manual for details.  
This boiler is supplied with safety devices which may cause the boiler to shut down and not re-start  
without service. If damage due to frozen pipes is a possibility, the heating system should not be left  
unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating  
system to prevent damage if the boiler is inoperative.  
This boiler contains very hot water under high pressure. Do not unscrew any pipe fittings nor attempt  
to disconnect any components of this boiler without positively assuring the water is cool and has no  
pressure. Always wear protective clothing and equipment when installing, starting up or servicing this  
boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the  
temperature and pressure of the boiler.  
This boiler contains components which become very hot when the boiler is operating. Do not touch any  
components unless they are cool.  
Boilermaterialsofconstruction,productsofcombustionandthefuelcontainalumina,silica,heavymetals,  
carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause  
death or serious injury and which are known to the state of California to cause cancer, birth defects and  
other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing  
or working nearby the appliance.  
Failuretofollowallinstructionsintheproperordercancausepersonalinjuryordeath. Readallinstructions,  
including all those contained in component manufacturers manuals which are provided with the boiler  
before installing, starting up, operating, maintaining or servicing.  
Keep boiler area clear and free from combustible materials, gasoline and other flammable vapors or  
liquids.  
Do not operate boiler with control which has been subject to water.  
All cover plates, enclosures and guards must be in place at all times.  
NOTICE  
This boiler has a limited warranty, a copy of which is printed on the back of this manual. It is the  
responsibility of the installing contractor to see that all controls are correctly installed and are operating  
properly when the installation is complete.  
USA boilers built for installation at altitudes greater than 2,000 feet above sea level have been specially  
orificed to reduce gas input rate 4 percent per 1,000 feet above sea level per the National Fuel Gas Code,  
NFPA 54/ANSI Z223.1, Section 8.1.2 and Appendix F. Canadian boilers’ orifice sizing is indicated on the  
rating label.  
3
Table of Contents  
I. Pre-Installation.............................................................6  
II. Boiler Assembly...........................................................8  
III. Gas Control System Assembly ..................................15  
(Knockdown Boilers)  
IV. Water Trim and Piping...............................................25  
V. Gas Piping..................................................................29  
VI. Venting.......................................................................31  
VII. Electrical....................................................................34  
VIII. System Start-up..........................................................52  
IX. Service .......................................................................61  
X. Repair Parts................................................................67  
4
Figure ꢀ: Dimensional Data  
Table ꢀ: Dimensional Data  
Dimensions (Inches)  
Recommended  
Chimney Size  
(Round)  
Water  
Content  
(Gallons)  
Approx.  
Shipping  
Weight (LB.)  
Boiler  
Model  
D
E
A
B
C
USA  
Canada  
USA  
Canada  
805H  
806H  
807H  
808H  
809H  
810H  
20  
10  
7
8
24-13/16  
27-13/16  
28-13/16  
30-13/16  
33-1/2  
24-13/16  
25-3/4  
16-1/8  
18  
16-1/8  
16  
7” dia. x 15 ft.  
8” dia. x 15 ft.  
8” dia. x 15 ft.  
8” dia. x 15 ft.  
10” dia. x 15 ft.  
10” dia. x 15 ft.  
11.9  
13.9  
15.9  
17.9  
19.9  
21.9  
705  
785  
23-3/4  
27-1/2  
31-1/4  
35  
11-7/8  
13-3/4  
15-5/8  
17-1/2  
19-3/8  
9
25-3/4  
18  
16  
890  
9
26-11/16  
26-7/16  
26-7/16  
20  
16  
1000  
1100  
1220  
10  
10  
22  
15  
38-3/4  
33-1/2  
22  
15  
5
I. Pre-Installation  
WARNING  
2. USA, 808H-810H: for installation in room which is  
large in comparison with size of boiler.  
a. Front: 18”  
Carefully read all instructions before installing  
boiler. Failure to follow all instructions in proper  
order can cause personal injury or death.  
b. Top: 51½”  
c. Draft hood, rear, sides, and flue connector: 6”  
3. Canada, 805H-810H:  
A. Inspect shipment carefully for any signs of damage.  
All equipment is carefully manufactured, inspected  
and packed. Our responsibility ceases upon delivery  
of boiler to carrier in good condition. Any claim  
for damage or shortage in shipment must be filed  
immediately against carrier by consignee. No claims  
for variances or shortages will be allowed by Boiler  
Manufacturer, unless presented within sixty (60) days  
after receipt of equipment.  
a. Top and front: 18” (45.7 cm)  
b. Flue, rear and sides: 6” (15.2 cm)  
D. Provide clearance for servicing and proper operation  
(following clearances are recommended and may be  
reduced to minimum clearances shown above):  
1. Single boiler, 805H-807H, Front/Top: 24” (61.0 cm)  
2. Single boiler, 808H-810H, Front/Top: 48”  
(122.0 cm)  
B. Installation must conform to the requirements of  
the authority having jurisdiction. In the absence of  
such requirements, installation must conform to the  
National Fuel Gas Code, NFPA 54/ANSI Z223.1 and/or  
CAN/CSA B149.1 Installation Codes. Where required  
by the authority having jurisdiction, the installation  
must conform to the Standard for Controls and Safety  
Devices for Automatically Fired Boilers, ANSI/ASME  
No CSD-1.  
3. Multiple/modular boiler, USA /Canada, Sides: 1”  
(2.5 cm)  
E. Install boiler on level floor as close to chimney as  
possible. For basement installation provide a solid base  
such as concrete or masonry construction if floor is not  
level or if water may be encountered on floor around  
boiler.  
F. Protect gas ignition system components from  
water (dripping, spraying, rain, etc.) during boiler  
operation and service (circulator replacement, control  
replacement, etc.).  
C. Provide clearance between combustible material and  
boiler jacket (following clearances are minimums):  
1. USA, 805H-807H: listed for Alcove installation  
a. Front: 18”  
G. Provide combustion and ventilation air in accordance  
with applicable provisions of local building codes,  
or the National Fuel Gas Code, NFPA 54/ANSI  
Z223.1, Air for Combustion and Ventilation; or CAN/  
CSA B149.1, Venting Systems and Air Supply for  
Appliances.  
b. Top: 36”  
c. Draft hood, rear, sides and flue connector: 6”  
WARNING  
Appliance is design certified for installation on  
noncombustible flooring only. For installation  
on combustible flooring only when installed on  
special base listed in Table 2. Boiler must not be  
installed on carpeting. When boiler is installed on  
concrete which is over a material that is subject  
to melting (PVC, PEX radiant tubing, etc.), the  
special base must be used. A concrete pad is not  
sufficient to protect combustible flooring.  
WARNING  
Adequate combustion and ventilation air must be  
provided to assure proper combustion.  
The following guideline is based on the National Fuel  
Gas Code, NFPA 54/ANSI Z223.1.  
1. Determine volume of space (boiler room). Rooms  
communicating directly with space (through  
permanent openings not furnished with doors) are  
considered part of space.  
Table 2: Special Base Required for Installation on  
Combustible Flooring  
Volume [ft3] = Length [ft] x Width [ft] x Height [ft]  
Boiler Model  
805H  
Special Base Part Number  
61816055  
2. Determine Total Input of all appliances in space.  
Round result to nearest 1,000 Btu per hour (Btuh).  
806H  
61816065  
3. Determine type of space. Divide Volume by Total  
Input.  
807H  
61816075  
808H  
61816085  
a. If result is greater than or equal to 50 ft3 per  
1,000 BtuH, space is considered an unconfined  
space.  
809H  
61816095  
810H  
61816105  
6
b. If result is less than 50 ft3 per 1,000 Btuh, space  
i. Minimum free area of 1 square inch per  
3,000 Btu per hour input of all equipment in  
space.  
is considered a confined space.  
4. Determine building type. A building of unusually  
ii. Free area shall not be less than the sum  
of the areas of all vent connectors in the  
confined space.  
tight construction has the following characteristics:  
a. Walls and ceiling exposed to outside atmosphere  
have a continuous water vapor retarder with a  
rating of 1 perm or less with openings gasketed  
and sealed, and  
Alternate method for boiler located within confined  
space. Use indoor air if two permanent openings  
communicate directly with additional space(s) of  
sufficient volume such that combined volume of all  
spaces meet criteria for unconfined space. Size each  
opening for minimum free area of 1 square inch per  
1,000 Btu per hour input of all equipment in spaces,  
but not less than 100 square inches.  
b. Weather-stripping has been added on openable  
windows and doors, and  
c. Caulking or sealants applied in joints around  
window and door frames, between sole  
plates and floors, between wall-ceiling joints,  
between wall panels, at plumbing and electrical  
penetrations, and at other openings.  
7. Ventilation Duct Louvers and Grilles. Equip outside  
openings with louvers to prevent entrance of rain  
and snow, and screens to prevent entrance of insects  
and rodents. Louvers and grilles must be fixed in  
open position or interlocked with equipment to open  
automatically before burner operation. Screens must  
not be smaller than ¼ inch mesh.  
5. For boiler located in an unconfined space in a  
building of other than unusually tight construction,  
adequate combustion and ventilation air is normally  
provided by fresh air infiltration through cracks  
around windows and doors.  
6. For boiler located in an unconfined space in a  
building of unusually tight construction or in  
a confined space, provide outdoor air through  
permanent opening(s) which communicate directly  
or by duct with the outdoors or spaces (crawl or  
attic) freely communicating with the outdoors.  
Minimum dimension of air opening(s) is 3” (7.6  
cm).  
Consider the blocking effect of louvers, grilles and  
screens when calculating the opening size to provide  
the required free area. If free area of louver or grille  
is not known, assume wood louvers have 20-25  
percent free area and metal louvers and grilles have  
60-75 percent free area.  
8. For Specially Engineered Installations. The above  
requirements shall be permitted to be waived  
where special engineering, consistent with good  
engineering practice and approved by the authority  
having jurisdiction, provides an adequate supply of  
air for combustion, ventilation, and dilution of flue  
gases.  
a. Two permanent openings: Locate one opening  
within 12 inches (30.5 cm) of top of space.  
Locate remaining opening within 12 inches  
(30.5 cm) of bottom of space. Size each opening  
per following:  
i. Direct communication with outdoors.  
Minimum free area of each opening must be  
1 square inch per 4,000 Btu per hour input  
of all equipment in space.  
ii. Vertical ducts. Minimum free area of each  
opening must be 1 square inch per 4,000  
Btu per hour input of all equipment in space.  
Duct cross-sectional area shall be same as  
opening free area.  
WARNING  
Do not install boiler where gasoline or other  
flammable vapors or liquids, or sources of  
hydrocarbons (i.e. bleaches, cleaners, chemicals,  
sprays, paint removers, fabric softeners, etc.) are  
used or stored.  
iii. Horizontal ducts. Minimum free area of each  
opening must be 1 square inch per 2,000  
Btu per hour input of all equipment in space.  
Duct cross-sectional area shall be same as  
opening free area.  
NOTICE  
Mis-sizing of the boiler with regard to the heating  
system load will result in excessive boiler cycling  
and accelerated component failure. Burnham  
DOES NOT warrant failures caused by mis-sized  
boiler applications. DO NOT oversize the boiler  
to the system. Modular/multiple boilers greatly  
reduce the likelihood of boiler oversizing.  
b. One permanent opening shall be permitted where  
the boiler has clearances of at least 1” (2.5 cm)  
from the sides and rear and 6” (15.2 cm) from  
the front. Locate the opening within 12 inches  
(30.5 cm) of top of space. Size opening per  
following:  
II. Boiler Assembly  
A. Remove Crate  
1. Remove all fasteners at crate skid.  
2. Lift outside container and remove with all other  
inside protective spacers and bracing.  
B. Remove boiler from skid. See Figure 2. Exercise care  
to avoid dropping boiler.  
1. Place boiler in approximate location. Refer to  
Section I: Pre-Installation. Remove base hold down  
bolts.  
2. Using pry bar under rear corner of Base End Panel,  
raise boiler and install 1½” wood blocks under rear  
corners. Install ¾” pipe roller between Base and  
skid.  
3. Remove 1½” wood blocks. Place 3” pipe roller on  
floor behind skid.  
4. Roll boiler off skid. Move skid out of way.  
5. Roll boiler until 3” roller is located as shown. Use  
pry bar to install wood blocks under front corners of  
base. Remove 3” roller.  
Figure 2: Skid Removal  
Figure 3: Tapping Locations  
Table 3: Purpose of Tappings  
Tapping  
Size  
2”  
Purpose  
Supply  
A
B
C
D
E
F
2”  
Return  
3/4”  
3/4”  
3/4”  
3/4”  
3/4”  
Relief Valve  
Limit  
Auxiliary Limit  
Washout  
Drain  
G
8
6. Lift boiler with pry bar. Remove wood blocks.  
Lower boiler.  
water pressure of at least 10 psi but less than 50 psi  
gauge pressure.  
6. Examine boiler for leaks or damage due to shipment  
or handling.  
C. For Packaged Boiler only, proceed to Paragraph E.  
D. Test Section Assembly for leaks before connecting to  
system and installing controls, trim and jacket. Refer to  
Figure 3 and Table 3.  
7. Remove plugs from Return Tapping B, Tapping C,  
and Tapping E (if second limit or operating control  
is used). Also remove fill valve and piping, purge  
valve and piping, and pressure gauge.  
1. Plug Tappings C & E (¾ NPT) and Return Tapping  
B (2 NPT).  
E. Install special base if installation is on combustible  
flooring. See Figure 4. Floor shield adds 4¾” to boiler  
height.  
2. Insert ¾” NPT x ¼” NPT bushing in Tapping D.  
Install pressure gauge capable of indicating 50 psi.  
3. Insert 2” NPT x ¾” NPT bushing in Supply Tapping  
A. Install purge valve with a hose that runs to a  
drain.  
1. Place special base on combustible floor with surface  
marked “FRONT” in upward position.  
2. Locate special base with spacing to combustible  
materials as shown in Figure 4.  
4. Connect fill valve and piping to Drain Tapping G.  
3. Place boiler on special base. Boiler must rest inside  
locating brackets. Boiler jacket panels will overhang  
special base.  
WARNING  
Do not use air to leak test boiler.  
4. Do not enclose boiler (including special base) on all  
four sides. Models 805H - 807H may be enclosed  
on three sides (alcove) while maintaining clearances  
shown in Figure 4.  
5. Fill boiler completely with water by venting air  
through purge valve. Close purge valve and apply  
Figure 4: Installation of Special Base for Combustible Flooring  
Figure 5: General Assembly (Knockdown Boilers)  
F. Move boiler to permanent location by sliding or  
1. Attach Base Front Panel to Section Assembly using  
¼” - 20 x 1¼” carriage bolts, washers and nuts.  
walking. Do not drop.  
For Packaged Boiler, proceed to Paragraph L.  
2. Seal between top of Base Front Panel and Section  
Assembly with furnace cement (shipped in  
G. Confirm that one (1) Flue Baffle is properly  
positioned in each Boiler Flueway. Tabs at the top  
of each Flue Baffle should be resting on top row of Flue  
Pins on each adjoining section.  
Combination Boiler Parts and Control Carton).  
3. Seal between top of Base Rear Panel and Section  
Assembly with furnace cement.  
K. Install Pilot/Main Burner Assembly. See Figure 7.  
Assembly is located in Combination Boiler Parts and  
Control Carton. Verify assembly is properly located  
on support bracket in Base Rear Panel, seated on Main  
Burner Orifice, and secured with hitch pin clip.  
H. Install Canopy on section assembly. See Figure 5.  
Canopy and hardware are located in Combination  
Boiler Parts and Control Carton.  
1. Position Canopy on top of Section Assembly. Locate  
between end sections and sealing ledge on front and  
back of each section.  
L. Adjust Burner Air Shutters on all Burners. See  
Figure 7. (On Packaged Boilers, Front Door and  
Burner Access Panel(s) must be removed to make  
adjustments.) Distance between front edge of Burner  
Air Shutter and burner mounting ring should be  
approximately 11/16”. To adjust this distance, loosen  
screw at top of air shutter and slide into correct  
position. Then tighten screw. (Replace Burner Access  
Panel(s) and Front Door on Packaged Boilers.)  
2. Fasten each end with ¼” - 20 x 1” carriage bolts,  
washers and nuts.  
3. Seal between Canopy and Section Assembly with  
furnace cement.  
I. Inspect joints between sections. They were factory  
sealed. If any openings resulted during shipment or  
handling, reseal with furnace cement. Confirm tie rods  
are only hand tight to allow for thermal expansion.  
For Packaged Boiler, proceed to Section IV: Water Trim  
and Piping.  
J. Install Base Front Panel. See Figure 5. Panel and  
hardware located in Combination Boiler Parts and  
Control Carton.  
ꢀ0  
Figure 6: Flame Roll-out Switch Installation  
Figure ꢁ: Burner/Burner Access Panel Installation  
ꢀꢀ  
Combustible Clearance Label from Combination  
Boiler Parts and Controls Carton. Attach to  
Vestibule Panel in locations shown.  
M. Attach Flame Roll-out Switch to Burner Access Panel.  
See Figure 6. Flame Roll-out Switch and hardware  
are located in Combination Boiler Parts and Control  
Carton. Flame Roll-out Switch is a single use device  
- do not test with heat - switch cannot be reset.  
6. Attach Vestibule Panel to Left Side and Right Side  
Panels.  
1. Cut insulation from semicircular notch at right  
end of the burner access panel. Models 808H  
- 810H have two (2) burner access panels. Remove  
insulation from notch of right side burner access  
panel only.  
7. Attach Lower Front Tie Bar to Left Side and Right  
Side Panels.  
8. Engage Upper Front Panel in slots on Left Side  
and Right Side Panels. Place Top Panel in position.  
Attach Top Panel to Left Side, Right Side and Upper  
Rear Panels.  
2. Attach Flame Roll-out Switch Mounting Bracket to  
burner access panel with (1) #8 x ½” lg. sheet metal  
screw.  
9. Tighten all jacket screws.  
10. Affix Lighting/Operating Instructions Label and  
Wiring Diagram Label to inside of Front  
3. Attach Flame Roll-out Switch to mounting bracket  
with (1) #8 x ¾” lg. sheet metal screw.  
Removable Door. Labels are located in  
N. Install Burner Access Panel(s). Locate Burner Access  
Panel(s) in Combination Boiler Parts and Control  
Carton. Engage Burner Access Panel holes with  
projections on Base Front Panel. See Figure 5.  
Combination Boiler Parts and Control Carton.  
Q. Install Junction Box. See Figure 8. Attach junction  
box to inside of Left Side Panel with ¼” - 20 x ¼” lg.  
machine screw (located in Combination Boiler Parts  
and Control Carton).  
O. Install Immersion Well(s).  
1. Remove Immersion Well(s) from Combination  
Boiler Parts and Control Carton..  
R. Install Limit Control. Locate limit in Combination  
Boiler Parts and Control Carton. Insert limit probe  
into left immersion well as far as possible. Tighten set  
screw.  
2. Insert Immersion Well in Tapping D. See Figure 3.  
3. If second limit or operating control is used, insert  
immersion well in Tapping E. If vertical gas  
piping is to be installed inside of boiler jacket, it  
is recommended that second limit be installed in  
system piping.  
S. Install Auxiliary Limit or operating control (if used).  
Insert control probe into right immersion well as far as  
possible. Tighten set screw.  
T. Install Gas Control Assembly. Refer to Section III,  
P. Install Jacket. See Figure 8.  
Gas Control System Assembly (Knockdown Boilers).  
1. Locate four (4) Jacket Attachment Brackets in  
Combination Boiler Parts and Control Carton.  
Attach to Front Base Panel and Rear Base Panels  
with #8 sheet metal screws. See Figure 5.  
U. EP and OP System: See Figure 9.  
1. Install pre-wired EP/OP Control Cabinet Assembly  
to right front corner of jacket top panel.  
2. Install Honeywell RM7890 Control (located in  
RM7890 Control Carton).  
2. Hang Left Side Panel and Right Side Panel onto  
Jacket Attachment Brackets.  
3. Remove RM7890’s Dust Cover. With a pair of side  
cutters, carefully snip both wire leads to the brown  
resistor labelled “JR2” and discard it. Replace Dust  
Cover.  
3. Attach Lower Rear Panel to Left and Right Side  
Panels. Do not tighten sheet metal screws.  
4. Attach Upper Rear Panel to Lower Rear Panel. Do  
not install three (3) upper screws.  
4. Install Honeywell R7847 Flame Amplifier.  
5. Remove Rating Label from envelope marked  
“RATING LABEL ENCLOSED”. Remove  
5. Install heat shield.  
ꢀ2  
ꢀ3  
Figure ꢂ: EP/OP Control Installation  
ꢀ4  
III. Gas Control System Assembly (Knockdown Boilers)  
1. Install Gas Control Assembly on Manifold. See  
A. 24V Standing Pilot Control System  
Figure 14. Use thread (joint) compound (pipe dope)  
resistant to action of liquefied petroleum gas.  
Install Gas Control System. All components are  
located in Combination Boiler Parts and Control  
Carton.  
2. Install pilot burner piping and controls. See Figure  
14.  
1. Install Gas Control Assembly on Manifold. See  
Figure 10. Use thread (joint) compound (pipe dope)  
resistant to action of liquefied petroleum gas.  
3. Connect Thermocouple Lead to Gas Valve.  
4. Mount Transformer (continuous circulation) or  
Control Center (intermittent circulation) to Junction  
Box.  
2. Install pilot burner piping and controls. See Figure  
10.  
a. Canada only - loop 4” nylon cable tie between  
junction box and transformer/control center.  
3. Connect Thermocouple Lead to Gas Valve.  
4. Mount Transformer (continuous circulation) or  
Control Center (intermittent circulation) to Junction  
Box.  
b. Attach transformer/control center to junction  
box.  
D. OP-CSD-1 Control System  
a. Canada only - loop 4” nylon cable tie between  
junction box and transformer/control center.  
Install Gas Control System. All components are  
located in Combination Boiler Parts and Control  
Carton.  
b. Attach transformer/control center to junction  
box.  
1. Install Gas Control Assembly on Manifold. See  
Figure 15. Use thread (joint) compound (pipe dope)  
resistant to action of liquefied petroleum gas.  
B. EI (Intermittent Ignition)  
Install Gas Control System. All components are  
located in Combination Boiler Parts and Control  
Carton.  
2. Mount pilot switch.  
3. Install pilot burner piping and controls. See Figure  
15.  
1. Install Gas Control Assembly on Manifold. See  
Figure 11. Use thread (joint) compound (pipe dope)  
resistant to action of liquefied petroleum gas.  
4. Connect Thermocouple lead to pilot switch.  
5. Mount Transformer (continuous circulation) or  
Control Center (intermittent circulation) to Junction  
Box.  
2. Install pilot burner piping and controls.  
a. Honeywell EI  
i. USA - See Figure 12.  
ii. Canada - See Figure 13.  
6. Attach transformer/control center to junction box.  
E. EP Control System  
3. Install Ignition Module.  
Install Gas Control System. All components are  
located in Combination Boiler Parts and Control  
Carton.  
a. Attach Ignition Control Mounting Bracket to  
Jacket Vestibule Panel using two (2) #8 x ½”  
sheet metal screws.  
1. Install Gas Control Assembly on Manifold. See  
Figure 16.  
b. Attach Honeywell Ignition Module to Mounting  
Bracket using two (2) #8 x ½” sheet metal  
screws.  
2. Install pilot burner piping and controls. See Figure  
16.  
c. Connect pilot ground wire and ignitor/sensor  
lead(s) to ignition module. Refer to “Section VII:  
Electrical” for connection details.  
3. Install Ignition Transformer.  
a. Attach Ignition Transformer to Jacket Vestibule  
Panel using four (4) #8 x ½” lg. sheet metal  
screws.  
4. Mount Transformer (continuous circulation) or  
Control Center (intermittent circulation) to Junction  
Box. See Figure 8.  
b. Connect Ignition Lead from Pilot to Ignition  
Transformer.  
a. Canada only - loop 4” nylon cable tie between  
junction box and transformer/control center.  
4. Mount Transformer (continuous circulation) or  
Control Center (intermittent circulation) to Junction  
Box.  
b. Attach transformer/control center to junction  
box.  
C. OP Control System  
a. Canada only - loop 4” nylon cable tie between  
junction box and transformer/control center.  
Install Gas Control System. All components are  
located in Combination Boiler Parts and Control  
Carton.  
b. Attach transformer/control center to junction  
box.  
ꢀ5  
b. Connect Ignition Lead from Pilot to Ignition  
Transformer.  
F. EP-CSD-1 Control System  
Install Gas Control System. All components are  
located in Combination Boiler Parts and Control  
Carton.  
4. Mount Transformer (continuous circulation) or  
Control Center (intermittent circulation) to Junction  
Box.  
1. Install Gas Control Assembly on Manifold. See  
Figure 17.  
a. Canada only - loop 4” nylon cable tie between  
junction box and transformer/control center.  
2. Install pilot burner piping and controls. See Figure  
17.  
b. Attach transformer/control center to junction  
box.  
3. Install Ignition Transformer.  
a. Attach Ignition Transformer to Jacket Vestibule  
Panel using four (4) #8 x ½” lg. sheet metal  
screws.  
ꢀ6  
ꢀꢁ  
ꢀ8  
ꢀꢂ  
20  
2ꢀ  
22  
23  
24  
IV. Water Trim and Piping  
WARNING  
Failure to properly pipe boiler may result in improper operation and damage to boiler or structure.  
Oxygen contamination of boiler water will cause corrosion of iron and steel boiler components, and can  
lead to boiler failure. Burnham’s Warranty does not cover problems caused by oxygen contamination of  
boiler water or scale (lime) build-up caused by frequent addition of water.  
Table 4: Flow Rate, Temperature Rise, and  
Pressure Drop  
A. Design and install boiler and system piping to  
prevent oxygen contamination of boiler water and  
frequent water additions.  
Boiler  
Pressure  
Drop  
Boiler Flow Rate Temp. Rise Min. Boiler  
1. There are many possible causes of oxygen  
contamination such as:  
Model  
(GPM)  
Thru Boiler Piping NPT  
a. Addition of excessive make-up water as a result  
of system leaks.  
21  
14  
10  
20° F  
30° F  
40° F  
1½”  
1¼”  
1¼”  
3’  
2’  
1’  
805H  
b. Absorption through open tanks and fittings.  
26  
17  
13  
20° F  
30° F  
40° F  
1½”  
1½”  
1¼”  
3’  
2’  
1’  
c. Oxygen permeable materials in the distribution  
system.  
806H  
807H  
808H  
809H  
810H  
2. In order to insure long product life, oxygen sources  
must be eliminated. This can be accomplished by  
taking the following measures:  
31  
20  
15  
20° F  
30° F  
40° F  
2”  
1½”  
1¼”  
3’  
2’  
1’  
36  
24  
18  
20° F  
30° F  
40° F  
2”  
1½”  
1½”  
3’  
2’  
1’  
a. Repairing system leaks to eliminate the need for  
addition of make-up water.  
b. Eliminating open tanks from the system.  
40  
27  
20  
20° F  
30° F  
40° F  
2”  
2”  
1½”  
3’  
2’  
1’  
c. Eliminating and/or repairing fittings which allow  
oxygen absorption.  
45  
30  
22  
20° F  
30° F  
40° F  
2”  
2”  
1½”  
3’  
2’  
1’  
d. Use of non-permeable materials in the  
distribution system.  
e. Isolating the boiler from the system water by  
installing a heat exchanger.  
f. Use properly designed and operating air  
elimination devices in water piping.  
B. Design boiler piping and flow rate to obtain proper  
temperature rise though the boiler. (See Table 4)  
WARNING  
Pressure relief valve discharge piping must be  
piped such that the potential of severe burns  
is eliminated. DO NOT pipe in any area where  
freezing could occur. DO NOT install any shut off  
valves, plugs or caps. Consult Local Codes for  
proper discharge piping arrangement.  
C. Install Safety Relief Valve. See Figure 18.  
Components are located in Water Trim Carton. Safety  
Relief Valve must be installed with spindle in vertical  
position.  
1. Install ¾” NPT x 3½” lg. nipple in tapping “C”. See  
Figure 3.  
2. Install safety relief valve on ¾” NPT nipple.  
Figure ꢀ8: Safety Relief Valve Installation  
25  
Figure ꢀꢂ: Drain Piping Installation  
D. Install Drain Valve in rear of Left End Section,  
Tapping “G”. See Figure 19. Components are located  
in Water Trim Carton.  
E. Install Temperature-Pressure Gauge. Components  
are located in Water Trim Carton.  
1. Standard Temperature - Pressure Gauge Piping. See  
Figure 20.  
Figure 2ꢀ: Alternate Temperature-Pressure Gauge  
Installation  
b. Install 2 NPT x ¾ NPT x 2 NPT Tee (provided)  
or 2 NPT x 2 NPT x ¾ NPT Tee (installer  
furnished). ¾ NPT leg should face forward.  
c. Install ¾ NPT x ¼ NPT Bushing.  
d. Insert Temperature-Pressure Gauge. Tighten  
by applying pressure to square shank on back  
of gauge. DO NOT APPLY PRESSURE ON  
GAUGE CASE since this may ruin gauge  
calibration.  
F. Connect system supply and return piping to boiler.  
See Figure 23. Also consult I=B=R Installation and  
Piping Guides. Maintain minimum ½ inch clearance  
from hot water piping to combustible materials.  
1. If boiler is used in connection with refrigeration  
systems, boiler must be installed with chilled  
medium piped in parallel with heating boiler using  
appropriate valves to prevent chilled medium from  
entering boiler. See Figure 22. Also consult I=B=R  
Installation and Piping Guides.  
Figure 20: Temperature-Pressure Gauge  
Installation  
a. Install 2” NPT x 10” lg. nipple with gauge  
tapping into Supply Tapping “A”. See Figure 3.  
Gauge tapping should face forward.  
b. Insert Temperature-Pressure Gauge. Tighten  
by applying pressure to square shank on back  
of gauge. DO NOT APPLY PRESSURE ON  
GAUGE CASE since this may ruin gauge  
calibration.  
2. Alternate Temperature-Pressure Gauge Piping. See  
Figure 21.  
a. Install 2 NPT x 10” Nipple into Supply Tapping  
“A”. See Figure 3.  
Figure 22: Recommended Piping for Combination  
Heating & Cooling (Refrigeration) System  
26  
2. If boiler is connected to heating coils located in  
air handling units where they may be exposed to  
refrigerated air, boiler piping must be equipped with  
flow control valves to prevent gravity circulation of  
boiler water during cooling system operation.  
at 40°F or less, and return water temperature at  
minimum of 135°F.  
Continued boiler operation for prolonged periods of  
time under conditions when temperature differential  
across the system exceeds 40°F and/or return water  
temperature stays below 135°F, may result in  
premature boiler failure due to flue gas condensation  
and/or thermal shock.  
3. The piping diagrams shown (Figure 23, Detail “A”  
and Detail “B”) are recommended for optimum  
operation and long term reliability.  
Pump flow rates and minimum boiler supply and  
return pipe sizes are shown in Table 4.  
Burnham Commercial recommends maintaining  
temperature differential (drop) across the system  
Figure 23: Recommended Boiler Piping for Circulator Zoned Heating Systems  
Detail “B”: Primary/Secondary Piping  
with By-Pass  
Detail “A”: Blend Pump Piping  
2ꢁ  
a. A boiler by-pass is recommended for any  
installation for improved system temperature  
balance, while serving to protect the boiler from  
sustained condensing operation. The by-pass  
also provides some measure of low return water  
temperature protection by reducing flow through  
the boiler. See Figure 23.  
continuously run below 135°F for extended  
periods (due to low temperature applications  
like snowmelt, heat pump systems or others),  
primary/secondary boiler piping with a three-  
way valve and return temperature sensor is  
recommended. Refer to Burnham RTC Return  
Temperature Control Manual and Tekmar Essay  
#021 “Mixing Methods and Sizing of Variable  
Speed Injection Pumps” for more information on  
mixing devices and boiler protection from low  
return water temperature.  
b. A blend pump is recommended to divert hot  
supply water into the return when system return  
temperatures can periodically dip below 135°F  
or when delta T’s rise beyond 40°F because of  
control schemes that shut off zone pumps for  
extended periods. See Figure 23, Detail “A”.  
4. A hot water boiler installed above radiation level  
must be provided with a low water cutoff device as  
part of installation.  
c. Primary/secondary piping with a by-pass is  
recommended to provide two points of mixing  
when dual temperature systems are used (i.e.  
baseboard and radiant heat, outdoor reset  
and domestic hot water production, systems  
incorporating night setback or multiple zone  
pumps on clock schedules). See Figure 23,  
Detail “B”.  
5. A start-up strainer is recommended for all  
installations (new and replacement alike) to prevent  
system debris and sediment from ending up in the  
boilers where it will inhibit heat transfer and may  
eventually cause a cast iron section to crack from  
overheating.  
G. Alliance SL™ Water Heater (if used). Refer to  
Alliance SL™ Installation, Operating and Service  
Instructions for additional information. Install in same  
manner as space heating zone.  
d. If system three-way valves are used for  
temperature modulation, or if the system will  
WARNING  
Burnham Commercial recommends maintaining temperature differential (drop) across the system at  
40°F or less and return water temperature at minimum of ꢀ35°F.  
Continued boiler operation for prolonged periods of time under conditions when temperature differential  
acrossthesystemexceeds4Fand/orreturnwatertemperaturestaysbelow35°F,mayresultinpremature  
boiler failure due to flue gas condensation and/or thermal shock.  
If the above conditions exist, to protect a boiler from sustained flue gas condensation and/or thermal  
shock,theabove-recommendedtemperaturesmaybemaintainedbyemployingcommonindustry-accepted  
mixing methods to provide boiler protection.  
Some common methods are boiler by-pass piping, blend pumps, primary secondary piping with a by-  
pass, mixing valves and/or variable speed injection pumps.  
28  
V. Gas Piping  
WARNING  
4. Specific gravity of gas. Gas piping systems for  
gas with a specific gravity of 0.70 or less can be  
sized directly from Table 6, unless authority having  
jurisdiction specifies a gravity factor be applied.  
For specific gravity greater than 0.70, apply gravity  
factor from Table 8. If exact specific gravity is not  
shown choose next higher value.  
Failure to properly pipe gas supply to boiler may  
result in improper operation and damage to the  
boiler or structure. Always assure gas piping is  
absolutely leak free and of the proper size and  
type for the connected load.  
For materials or conditions other than those listed  
above, refer to the National Fuel Gas Code,  
NFPA 54/ANSI Z223.1 and/or CAN/CSA B149.1  
Installation Codes, or size system using standard  
engineering methods acceptable to authority having  
jurisdiction.  
An additional gas pressure regulator may be  
needed. Consult gas supplier.  
A. Size gas Piping. Design system to provide adequate gas  
supply to boiler. Consider these factors:  
1. Allowable pressure drop from point of delivery to  
boiler. Maximum allowable system pressure is ½  
psig. Actual point of delivery pressure may be less;  
contact gas supplier for additional information.  
Minimum allowable gas valve inlet pressure is  
indicated on rating label.  
WARNING  
Failure to use proper thread compounds on all  
gas connectors may result in leaks of flammable  
gas.  
2. Maximum gas demand. Table 5 lists boiler input  
rate. Also consider existing and expected future gas  
utilization equipment (i.e. water heater, cooking  
equipment).  
WARNING  
Gas supply to boiler and system must be  
absolutely shut off prior to installing or servicing  
boiler gas piping.  
3. Length of piping and number of fittings. Refer to  
Table 6 for maximum capacity of Schedule 40 pipe.  
Table 7 lists equivalent length for standard fittings.  
B. Connect boiler gas valve to gas supply system.  
1. Use methods and materials in accordance with local  
plumbing codes and requirements of gas supplier. In  
absence of such requirements, follow the National  
Fuel Gas Code, NFPA 54/ANSI Z223.1 and/or  
CAN/CSA B149.1 Installation Codes.  
Table 5: Rated Input  
Rated Capacity  
Gas  
Boiler  
Model  
(cubic feet per hour)  
Connection  
Size  
2. Use thread (joint) compound (pipe dope) resistant to  
Natural  
252  
LP / Propane  
100.8  
action of liquefied petroleum gas.  
805H  
806H  
807H  
808H  
809H  
810H  
1
1
1
1
1
1
3. Install sediment trap, ground-joint union and manual  
shut-off valve upstream of boiler gas valve and  
outside jacket. See Figure 24.  
315  
126  
374  
149.6  
433  
173.2  
4. All above ground gas piping upstream from  
manual gas valve must be electrically continuous  
and bonded to a grounding electrode. Do not use  
gas piping as a grounding electrode. Refer to the  
National Electrical Code, ANSI/NFPA 70 and/or  
CSA C22.1 Electrical Code.  
491  
196.4  
550  
220  
NOTICE  
USA boilers built for installation at altitudes greater than 2,000 feet above sea level have been specially  
orificed to reduce gas input rate 4 percent per 1,000 feet above sea level per the National Fuel Gas Code,  
NFPA 54/ANSI Z223.1, Section 8.1.2 and Appendix F. Canadian boilers’ orifice sizing is indicated on the  
rating label. High altitude boiler models are identifiable by the model number’s tenth digit on the rating label.  
(4=2000’ - 4500’, 5= 2000’ - 5000’)  
2ꢂ  
Table 6: Maximum Capacity of Schedule 40 Pipe in CFH for Gas Pressures of 0.5 psig or Less  
Length  
(Feet)  
0.3 Inch w.c. Pressure Drop  
0.5 Inch w.c. Pressure Drop  
½
132  
92  
73  
63  
56  
50  
46  
43  
40  
38  
¾
278  
190  
152  
130  
115  
105  
96  
1
1¼  
1,050  
730  
590  
500  
440  
400  
370  
350  
320  
305  
½
175  
120  
97  
¾
1
1¼  
1,400  
950  
770  
660  
580  
530  
490  
460  
430  
400  
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
520  
350  
285  
245  
215  
195  
180  
170  
160  
150  
360  
250  
200  
170  
151  
138  
125  
118  
110  
103  
680  
465  
375  
320  
285  
260  
240  
220  
205  
195  
82  
73  
66  
61  
90  
57  
84  
53  
79  
50  
Table 7: Equivalent Lengths of Standard Pipe Fittings & Valves  
Valves (Fully Open)  
Threaded Fittings  
90° Tee, Flow  
Pipe  
Size  
I.D.  
(Inches)  
Swing  
Check  
90°  
Elbow  
45°  
Elbow  
90° Tee, Flow  
Gate  
Globe  
Angle  
Through Run Through Branch  
½”  
¾”  
0.622  
0.824  
1.049  
1.380  
0.35  
0.44  
0.56  
0.74  
18.6  
23.1  
29.4  
38.6  
9.3  
4.3  
5.3  
6.8  
8.9  
1.6  
0.78  
0.97  
1.23  
1.6  
1.0  
1.4  
1.8  
2.3  
3.1  
4.1  
5.3  
6.9  
11.5  
14.7  
19.3  
2.1  
1”  
2.6  
1¼”  
3.5  
Table 8: Specific Gravity Correction Factors  
WARNING  
Specific  
Gravity  
Correction  
Factor  
Specific  
Gravity  
Correction  
Factor  
Do not use matches, candles, open flames, or  
other ignition source.  
0.50  
0.55  
0.60  
0.65  
0.70  
0.75  
0.80  
1.10  
1.04  
1.00  
0.96  
0.93  
0.90  
0.87  
1.30  
1.40  
1.50  
1.60  
1.70  
---  
1.07  
1.04  
1.00  
0.97  
0.94  
---  
---  
---  
C. Pressure Test. The boiler and its gas connection must  
be leak tested before placing boiler in operation.  
1. Protect boiler gas valve. For all testing over ½ psig,  
boiler and its individual shut-off valve must be  
disconnected from gas supply piping. For testing at  
½ psig or less, isolate boiler from gas supply piping  
by closing boiler’s individual manual shut-off valve.  
2. Locate leaks using approved combustible gas  
detector, soap and water, or similar nonflammable  
solution.  
Figure 24: Recommended Gas Piping  
30  
VI. Venting  
1. Uncoil power cord.  
A. Install vent system in accordance with local building  
codes; or local authority having jurisdiction; or  
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Part  
7, Venting of Equipment and/or CAN/CSA B149.1,  
Venting Systems and Air Supply for Appliances. Install  
any of the following for this Series 8H Category I, draft  
hood equipped appliance:  
2. Position mounting bracket onto lower edge of Draft  
Hood skirt. Locate center tooth (with #10 sheet  
metal screw) on outside and other two teeth inside  
Draft Hood skirt. See Figure 25.  
3. Slide mounting bracket tight against lower edge of  
Draft Hood skirt. Position #10 sheet metal screw  
above skirt’s stiffening rib.  
1. Type B or Type L gas vent. Install in accordance  
with listing and manufacturer’s instructions.  
4. Secure bracket in position by tightening #10 sheet  
metal screw against outer surface of Draft Hood  
skirt.  
2. Masonry or metal chimney. Build and install in  
accordance with local building codes; or local  
authority having jurisdiction; or Standard for  
Chimneys, Fireplaces, Vents, and Solid Fuel  
Burning Appliances, ANSI/NFPA 211 and/or  
National Building Code of Canada.  
5. Insert excess power cord through Jacket Right Side  
Panel hole. Remove slack.  
6. Position strain relief bushing around power cord.  
Pinch bushing’s two halves together and snap back  
into hole in Jacket Right Side Panel.  
Masonry chimney must be lined with approved  
clay flue lining or listed chimney lining system  
except as provided in ANSI Z223.1/NFPA 54,  
Paragraph 7.5.4(a): Exception: Where permitted by  
the authority having jurisdiction, existing chimneys  
shall be permitted to have their use continued when  
an appliance is replaced by an appliance of similar  
type, input rating, and efficiency.  
7. Verify power cord, mounting bracket, and Blocked  
Vent Switch are secure and located as shown in  
Figure 25.  
WARNING  
Do not operate boiler without Blocked Vent Switch  
Properly installed.  
3. Single wall metal vent. Allowed by ANSI Z223.1/  
NFPA 54 under very restrictive conditions.  
B. Inspect chimney and remove any obstructions or  
restrictions. Clean chimney if previously used for solid  
or liquid fuel-burning appliances or fireplaces.  
DANGER  
Inspect existing chimney before installing boiler.  
Failure to clean or replace perforated pipe or tile  
lining will cause severe injury or death.  
C. Install Draft Hood on canopy outlet. Maintain height  
from Jacket Top Panel to Draft Hood skirt as shown  
in Figure 1. DO NOT ALTER, CUT, OR MODIFY  
DRAFT HOOD.  
WARNING  
Do not alter boiler draft hood or place any  
obstruction or non-approved damper in the  
breeching or vent system. Flue gas spillage can  
occur. Unsafe boiler operation will occur.  
D. Install Blocked Vent Switch. The Blocked Vent  
Switch Assembly consists of a strain relief bushing,  
power cord, and switch attached to mounting bracket.  
On Packaged boilers, the assembly is shipped attached  
to top of boiler. On Knocked Down boilers, the  
assembly is located in Combination Boiler Parts and  
Control Carton.  
Figure 25: Blocked Vent Switch Installation  
3ꢀ  
2. Where two or more appliances vent into a common  
vent, the area of the common vent should at least  
equal the area of the largest vent plus 50 % of the  
area of the additional vents. Do not connect the  
vent of this appliance into any portion of mechanical  
draft system operating under positive pressure.  
E. Boiler Equipped With Vent Damper. See Figure 26.  
1. Open Vent Damper Carton and remove Installation  
Instructions. Read Installation Instructions  
thoroughly before proceeding.  
CAUTION  
3. Vent connector should have the greatest possible  
initial rise above the draft hood consistent with the  
head room available and the required clearance from  
adjacent combustible building structure.  
Do not use one vent damper to control two or  
more heating appliances.  
2. Vent damper must be same size as draft hood  
outlet. See Figure 1. Unpack vent damper carefully.  
Forcing vent damper open or closed may damage  
gear train and void warranty. Vent damper assembly  
includes pre-wired connection harness with  
polarized plug.  
4. Install vent connector above bottom of chimney to  
prevent blockage - inspect chimney for obstructions  
or restrictions and remove - clean chimney if  
necessary.  
5. Vent connector should slope upward from draft hood  
to chimney not less than one inch in four feet. No  
portion of vent connector should run downward or  
have dips or sags. Vent connector must be securely  
supported.  
3. Mount vent damper assembly on draft hood without  
modification to either (Refer to instructions packed  
with vent damper for specific instructions). Vent  
damper position indicator to be visible to users.  
6. Use thimble where vent connector enters masonry  
chimney - keep vent connector flush with inside of  
flue liner.  
WARNING  
Provide adequate clearance for servicing -  
provide 6” minimum clearance between damper  
and combustible construction.  
7. Do not install Non-listed (AGA, CGA, CSA, ETL,  
or UL) vent damper or other obstruction in vent  
pipe.  
8. Locate Boiler as close to Chimney as possible  
consistent with necessary clearances. See Section I:  
Pre-Installation.  
F. Install Vent Connector from draft hood or vent  
damper to chimney. See Figure 27.  
1. Do not connect into same leg of chimney serving an  
open fireplace.  
Figure 26: Vent Damper Installation  
32  
9. Design vent system for sea level input.  
venting system are located and other spaces of the  
building. Turn on clothes dryers and any appliance  
not connected to the common venting system.  
Turn on any exhaust fans, such as range-hoods and  
bathroom exhausts, so they will operate at maximum  
speed. Do not operate a summer exhaust fan. Close  
fireplace dampers.  
10. Provide adequate ventilation of Boiler Room. See  
Section I: Pre-Installation.  
11. Never pass any portion of vent system through a  
circulating air duct or plenum.  
WARNING  
4. Place in operation the appliance being inspected.  
Follow the Lighting (or Operating) Instructions.  
Adjust thermostat so appliance will operate  
continuously.  
When an existing boiler is removed from a  
common venting system, the common venting  
system is likely to be too large for proper venting  
of the appliances remaining connected to it.  
5. Test for spillage at the draft hood relief opening after  
5 minutes of main burner operation. Use the flame  
of a match or candle, or smoke from a cigarette,  
cigar or pipe.  
G. If an Existing Boiler is Removed:  
At the time of removal of an existing boiler,  
the following steps shall be followed with each  
appliance remaining connected to the common  
venting system placed in operation, while the other  
appliances remaining connected to the common  
venting system are not in operation:  
6. After it has been determined that each appliance  
remaining connected to the common venting system  
properly vents when tested as outlined above, return  
doors, windows, exhaust fans, fireplace dampers and  
any other gas-burning appliance to their previous  
condition of use.  
1. Seal any unused openings in the common venting  
system.  
7. Any improper operation of the common venting  
system should be corrected so the installation  
conforms with the National Fuel Gas Code, NFPA  
54/ANSI Z223.1. When resizing any portion of  
the common venting system, the common venting  
system should be resized to approach the minimum  
size as determined using the appropriate tables in  
Part 7 and Part 11 in the National Fuel Gas Code,  
NFPA 54/ANSI Z223.1.  
2. Visually inspect the venting system for proper  
size and horizontal pitch and determine there is no  
blockage or restriction, leakage, corrosion, or other  
deficiencies which could cause an unsafe condition.  
3. Insofar as is practical, close all building doors and  
windows and all doors between the space in which  
the appliances remaining connected to the common  
Figure 2ꢁ: Typical Vent System  
33  
VII. Electrical  
DANGER  
Positively assure all electrical connections are unpowered before attempting installation or service of  
electrical components or connections of the boiler or building. Lock out all electrical boxes with padlock  
once power is turned off.  
WARNING  
Failure to properly wire electrical connections to the boiler may result in serious physical harm.  
Electrical power may be from more than one source. Make sure all power is off before attempting any  
electrical work.  
Each boiler must be protected with a properly sized fused disconnect.  
Never jump out or make inoperative any safety or operating controls.  
The wiring diagrams contained in this manual are for reference purposes only. Each boiler is shipped with  
a wiring diagram attached to the front door. Refer to this diagram and the wiring diagram of any controls  
used with the boiler. Read, understand and follow all wiring instructions supplied with the controls.  
2. Remove factory installed Jumper Plug from Vent  
Damper Receptacle on Vestibule Wiring Harness  
and discard.  
A. Install Boiler Wiring  
1. Knockdown boilers only. Locate wiring harnesses  
in Combination Boiler Parts and Control Carton.  
Refer to Table 10 and connect wiring as shown on  
the appropriate wiring diagram.  
3. Plug Vent Damper Harness Plug into Vent Damper  
Receptacle. See Figure 26.  
C. Install thermostat. Locate on inside wall  
approximately 4 feet above floor. Do not install on  
outside wall, near fireplace, or where influenced  
by drafts or restricted air flow, hot or cold pipes,  
lighting fixtures, television, or sunlight. Allow free air  
movement by avoiding placement of furniture near  
thermostat.  
2. Connect supply wiring and electrically ground boiler  
in accordance with requirements of authority having  
jurisdiction, or in absence of such requirements the  
National Electrical Code, ANSI/NFPA 70 and/or  
CSA C22.1 Electrical Code.  
B. Wire Vent Damper (if used; required on 805H,  
optional on 806H - 810H). See Figure 26.  
Set heat anticipator to match control system  
requirements. Refer to Table 9.  
1. Attach Vent Damper Harness to mounting hole in  
Jacket Left Side Panel. Install Cable Clamp around  
flexible conduit and attach to Jacket Top Panel.  
D. Wire thermostat. Provide Class II circuit between  
thermostat and boiler. Refer to appropriate wiring  
diagram for control system being used.  
Figure 28: Vent Damper Schematic Wiring Diagram  
34  
through Terminal 2 and the damper motor is de-  
energized.  
E. Alliance SL™ Water Heater (if used). May be used  
with Intermittent Circulation only.  
5. When the call for heat is satisfied, the damper  
relay coil is de-energized - closing contacts which  
energize the damper motor. This causes the damper  
to close. When the damper blade reaches the fully  
closed position, the damper motor is de-energized.  
Refer to Alliance SL™ Installation, Operating  
and Service Instructions for wiring, piping and  
additional information.  
F. Vent Damper Sequence of Operation. See Figure 28  
for schematic wiring diagram.  
POWER FAILURE - The damper blade will stop in the  
position it was in when power failed. (Combustion  
can never take place unless the damper blade is in  
the fully open position).  
1. The Vent Damper is continuously powered at  
Terminal 1.  
2. When there is a call for heat, the damper relay coil  
is energized through Terminal 5 if all limits ahead of  
the damper are satisfied.  
G. Sequence of Operation and Wiring. Refer to Table  
10 for the appropriate control system.  
3. The relay coil closes contacts which energize the  
damper motor, causing the damper to open.  
H. Optional Low-Water Cut-Off Wiring. See Figures 45  
through 48.  
4. When the damper blade reaches the fully open  
position, power is sent back to the ignition circuit  
Table ꢂ: Heat Anticipator Settings  
Heat Anticipator Setting *  
Control System  
24V Standing Pilot  
24V Electronic Ignition  
Continuous Circulation  
Intermittent Circulation  
0.3  
1.1  
USA: 0.9  
0.3  
Canada: 1.2  
* If room is heated above thermostat temperature setting, reduce heat anticipator setting by 0.1 or  
0.2 amps. If boiler short cycles without room reaching desired temperature, increase heat anticipator  
by 0.1 or 0.2 amps.  
35  
Table 10: Sequence of Operation and Wiring Diagrams  
Wiring Diagram Figure  
Sequence of  
Operation  
Ignition System  
Country  
Fuel  
Boiler Sizes  
6 & 7 Sect.  
Continuous  
Intermittent  
Natural Gas  
LP Gas  
USA &  
Canada  
Standing Pilot (24V)  
Figure 29  
Figure 30  
Page 36  
Natural Gas  
LP Gas  
Standing Pilot  
(OP - 120V)  
USA &  
Canada  
6 - 10 Sect.  
8 - 10 Sec.  
5 - 10 Sect.  
Figure 31  
Figure 31  
Figure 33  
Figure 32  
Figure 32  
Figure 34  
Page 39  
Page 39  
Standing Pilot  
(OP-CSD-1 - 120V  
USA  
USA  
LP Gas  
Natural Gas  
LP Gas  
Intermittent Ignition  
(Honeywell EI - 24V)  
Page 42  
Natural Gas  
LP Gas  
5 - 10 Sect.  
5 - 7 Sect.  
6 - 10 Sect.  
Canada  
Figure 35  
Figure 37  
Figure 36  
Figure 38  
Natural Gas  
LP Gas  
Page 47  
Page 47  
Intermittent Ignition  
(EP - 120V)  
USA &  
Canada  
Not Available  
Intermittent Ignition  
(EP-CSD-1 - 120V)  
USA  
Natural Gas  
8 - 10 Sect.  
Figure 37  
Figure 38  
1. Standing Pilot (24) Sequence of Operation  
a. Normal Operation  
Circulator continues to operate and Vent  
Damper (if used) remains open with call  
for heat. If blocked vent switch is activated  
do not attempt to place boiler in operation.  
Correct cause of spillage and reset blocked  
vent switch.  
i. Thermostat or operating control calls for  
heat. Vent Damper (if used) opens.  
ii. Gas valves are energized allowing main gas  
flow and ignition of main burners.  
iii. Flame Roll-out Switch: Automatically  
interrupts main burner operation when  
flames or excessive heat are present in  
vestibule. Circulator continues to operate  
and Vent Damper (if used) remains open  
with call for heat. Control is single use  
device. If flame roll-out switch is activated,  
do not attempt to place boiler in operation.  
Correct cause of spillage and replace flame  
roll-out switch.  
iii. Call or heat ends. Gas valves are de-  
energized, extinguishing main flame. Vent  
Damper (if used) closes.  
b. Safety Shutdown  
i. Limit: Automatically interrupts main burner  
operation when water temperature exceeds  
set point. Maximum allowable temperature  
is 250°F. Circulator continues to operate  
with call for heat, Vent Damper (if used)  
closes. Normal operation resumes when  
water temperature falls below set point.  
iv. Thermocouple: Senses pilot flame and  
causes gas valves to turn off main burner  
and pilot burner gas flow should pilot burner  
flame extinguish. Circulator continues to  
operate and Vent Damper (if used) remains  
open with call for heat.  
ii. Blocked Vent Switch: Automatically  
interrupts main burner operation when  
excessive flue gas spillage occurs.  
36  
Figure 2ꢂ: Wiring Diagram, Standing Pilot (24V), USA and Canada, Continuous Circulation  
3ꢁ  
Figure 30: Wiring Diagram, Standing Pilot (24V), USA and Canada, Intermittent Circulation  
38  
2. Electronically Supervised Standing Pilot (OP)  
Sequence of Operation  
3. ElectronicallySupervisedStandingPilot(OP-CSD-1)  
Sequence of Operation  
a. Normal Operation  
a. Normal Operation  
i. Thermostat or operating control calls for  
heat.  
i. Thermostat or operating control calls for  
heat.  
ii. Terminal #6 of RM7890C Burner Control  
is energized, initiating a microcomputer  
monitored circuit test.  
ii. Terminal #6 of RM7890C Burner Control  
is energized, initiating a microcomputer  
monitored circuit test.  
iii. Pilot Flame Establishing Period (PFEP)  
begins.  
iii. Pilot Flame Establishing Period (PFEP)  
begins.  
iv. After pilot flame is proven, terminal #9 of  
RM7890C is energized, allowing main gas  
flow and ignition of main burners. “Main”  
gas light will be illuminated.  
iv. After pilot flame is proven, terminal #9 of  
RM7890C is energized, allowing main gas  
flow and ignition of main burners. “Main”  
gas light will be illuminated.  
v. Call for heat ends. Terminal #6 of  
RM7890C is de-energized, in turn de-  
energizing gas valves and extinguishing  
main flame. “Main” gas light is de-  
energized.  
v. Call for heat ends. Terminal #6 of  
RM7890C is de-energized, in turn de-  
energizing gas valves and extinguishing  
main flame. “Main” gas light is de-  
energized.  
b. Safety Shutdown  
b. Safety Shutdown  
i. Limit: Automatically interrupts main burner  
operation when water temperature exceeds  
set point. Maximum allowable temperature  
is 250°F. Circulator continues to operate  
with call for heat. Normal operation  
resumes when water temperature falls below  
set point.  
i. Limit: Automatically interrupts main burner  
operation when water temperature exceeds  
set point. Maximum allowable temperature  
is 250°F. Circulator continues to operate  
with call for heat. Normal operation  
resumes when water temperature falls below  
set point.  
ii. Blocked Vent Switch: Automatically  
interrupts main burner operation when  
excessive flue gas spillage occurs.  
ii. Blocked Vent Switch: Automatically  
interrupts main burner operation when  
excessive flue gas spillage occurs.  
Circulator continues to operate with call for  
heat. If blocked vent switch is activated  
do not attempt to place boiler in operation.  
Correct cause of spillage and reset blocked  
vent switch.  
Circulator continues to operate with call for  
heat. If blocked vent switch is activated  
do not attempt to place boiler in operation.  
Correct cause of spillage and reset blocked  
vent switch.  
iii. Flame Roll-out Switch: Automatically  
interrupts main burner operation when  
flames or excessive heat are present in  
vestibule. Circulator continues to operate  
with call for heat. Control is single use  
device. If flame roll-out switch is activated,  
do not attempt to place boiler in operation.  
Correct cause of spillage and replace flame  
roll-out switch.  
iii. Flame Roll-out Switch: Automatically  
interrupts main burner operation when  
flames or excessive heat are present in  
vestibule. Circulator continues to operate  
with call for heat. Control is single use  
device. If flame roll-out switch is activated,  
do not attempt to place boiler in operation.  
Correct cause of spillage and replace flame  
roll-out switch.  
iv. RM7890C Burner Control: Automatically  
interrupts main burner operation if a pilot  
flame is not detected during the four or ten  
second pilot flame establishing period. The  
RM7890C will lockout or recycle based  
on jumper settings. “Alarm” light will be  
illuminated. Refer to instructions supplied  
with RM7890C for additional control  
information.  
iv. RM7890C Burner Control: Automatically  
interrupts main burner operation if a pilot  
flame is not detected during the four or ten  
second pilot flame establishing period. The  
RM7890C will lockout or recycle based  
on jumper settings. “Alarm” light will be  
illuminated. Refer to instructions supplied  
with RM7890C for additional control  
information.  
v. Pilot Safety Switch: Automatically de-  
energizes main gas valve and interrupts pilot  
gas supply if pilot flame is not detected at  
any time.  
3ꢂ  
Figure 3ꢀ: Wiring Diagram, OP/OP-CSD-ꢀ Ignition System, Continuous Circulation  
40  
Figure 32: Wiring Diagram, OP/OP-CSD-ꢀ Ignition System, Intermittent Circulation  
4ꢀ  
4. Honeywell EI Sequence of Operation  
a. Normal Operation  
Circulator continues to operate and Vent  
Damper (if used) remains open with call  
for heat. If blocked vent switch is activated  
do not attempt to place boiler in operation.  
Correct cause of spillage and reset blocked  
vent switch.  
i. Thermostat or operating control calls for  
heat. Vent Damper (if used) opens.  
ii. Ignition Module Terminals PV, MV/PV  
and the Ignition Terminal are energized.  
Terminals PV and MV/PV power the Pilot  
Valve in the Gas Valve supplying gas to  
the Pilot. The Ignition Terminal supplies  
voltage to the Ignition Electrode creating an  
electric spark to ignite the Pilot.  
iii. The sensing Circuit between the Q348  
Pilot Burner and the IGNITION MODULE  
proves the presence of the Pilot Flame  
Electronically and the Ignition Terminal is  
de-energized.  
iii. Flame Roll-out switch: Automatically  
interrupts main burner operation when  
flames or excessive heat are present in  
vestibule. Circulator continues to operate,  
Vent Damper (if used) remains open with  
call for heat. Control is single use device.  
If flame roll-out switch is activated, do not  
attempt to place boiler in operation. Correct  
cause of spillage and replace flame roll-out  
switch.  
iv. Pilot  
iv. Terminals MV and MV/PV of the  
IGNITION MODULE are energized and  
supply power to the Main Gas Valve. The  
Gas Valve is energized allowing main gas  
flow, and ignition of Main Burners.  
v. Call for heat ends. Ignition module is de-  
energized, de-energizing gas valve, and  
extinguishing pilot and main flame. Vent  
Damper (if used) closes.  
Pilot failure can occur during the start-up or  
the operating cycle of the boiler. Any pilot  
failure of the Q348 Electronic Pilot, after  
ignition of pilot flame will close the main  
gas valve in 0.8 seconds.  
For approximately 90 seconds after failure  
of the Q348 pilot, the module through the  
ignition terminal will try to reestablish  
pilot flame. If no pilot flame can be sensed  
by the flame rod circuit, terminals PV and  
MV/PV are de-energized and the module  
will lock out on safety. Five to six minutes  
after shutdown, the IGNITION MODULE  
restarts the ignition sequence. The ignition  
trial, shutdown, and wait sequence continues  
until either the pilot lights or the Thermostat  
is set below room temperature (to end the  
call for heat). The ignition sequence can be  
reset by setting down the Thermostat for one  
minute.  
b. Safety Shutdown  
i. Limit: Automatically interrupts power  
to the Ignition Module and Gas Valve(s),  
extinguishing pilot and main flame, when  
water temperature exceeds set point.  
Maximum allowable temperature is 250°F.  
Circulator continues to operate with call for  
heat, Vent Damper (if used) closes. Normal  
operation resumes when water temperature  
falls below set point.  
ii. Blocked Vent Switch: Automatically  
interrupts main burner operation when  
excessive flue gas spillage occurs.  
c. Trouble Shooting Guide. See Page 66.  
42  
Figure 33: Wiring Diagram, Honeywell EI, USA, Continuous Circulation  
43  
Figure 34: Wiring Diagram, Honeywell EI, USA, Intermittent Circulation  
44  
Figure 35: Wiring Diagram, Honeywell EI, Canada, Continuous Circulation  
45  
Figure 36: Wiring Diagram, Honeywell EI, Canada, Intermittent Circulation  
46  
ii. Blocked Vent Switch: Automatically  
interrupts main burner operation when  
excessive flue gas spillage occurs.  
6. Electronically Supervised Intermittent Ignition  
(EP/EP-CSD-1) Sequence of Operation  
a. Normal Operation  
Circulator continues to operate with call for  
heat. If blocked vent switch is activated,  
do not attempt to place boiler in operation.  
Correct cause of spillage and reset blocked  
vent switch.  
i. Thermostat or operating control calls for  
heat.  
ii. Terminal #6 of RM7890A Burner Control  
is energized, initiating a microcomputer  
monitored circuit test.  
iii. Flame Roll-out Switch: Automatically  
interrupts main burner operation when  
flames or excessive heat are present in  
vestibule. Circulator continues to operate  
with call for heat. Control is single use  
device. If flame roll-out switch is activated,  
do not attempt to place boiler in operation.  
Correct cause of spillage and replace flame  
roll-out switch.  
iv. RM7890A Burner Control: Automatically  
interrupts main burner operation if a pilot  
flame is not detected during the four or ten  
second pilot flame establishing period. The  
RM7890A will lockout or recycle based  
on jumper settings. “Alarm” light will be  
illuminated. Refer to instructions supplied  
with RM7890A for additional control  
information.  
iii. The pilot valve (terminal 8) and ignition  
transformer (terminal 10) are energized.  
The pilot valve opens and the ignition  
electrode sparks, igniting the pilot.  
iv. After the pilot flame is proven, the ignition  
terminal (10) is de-energized and the main  
valve terminal (9) is energized, allowing  
main gas flow and ignition of main burners.  
“Main” gas light will be illuminated.  
v. When the call for heat ends, terminal #6  
is de-energized, extinguishing the pilot  
and main flames. “Main” gas light is de-  
energized.  
b. Safety Shutdown  
i. Limit: Automatically interrupts main burner  
operation when water temperature exceeds  
set point. Maximum allowable temperature  
is 250°F. Circulator continues to operate  
with call for heat. Normal operation  
resumes when water temperature falls below  
set point.  
4ꢁ  
Figure 3ꢁ: Wiring Diagram, EP/EP-CSD-ꢀ Ignition System, USA, Continuous Circulation  
48  
Figure 38: Wiring Diagram, EP/EP-CSD-ꢀ Ignition System, USA, Intermittent Circulation  
4ꢂ  
Figure 3ꢂ: McDonnell & Miller ꢁ50P-MT (ꢀ20V) L.W.C.O. Wiring for Boilers with 24V Limit Circuits  
Figure 40: McDonnell & Miller ꢁ50P-MT (ꢀ20V) L.W.C.O. Wiring for Boilers with ꢀ20V Limit Circuits (OP & EP)  
50  
Figure 4ꢀ: Hydrolevel OEM - ꢀꢁ0/550/650/ꢁ50 (ꢀ20V) L.W.C.O. Wiring for Boilers with 24V Limit Circuits  
Figure 42: Hydrolevel OEM - ꢀꢁ0/550/650/ꢁ50 (ꢀ20V) L.W.C.O. Wiring for Boilers with ꢀ20V Limit Circuits  
5ꢀ  
VIII. System Start-Up  
WARNING  
9. Close purge valve, continue filling the system  
until the pressure gauge reads the desired cold fill  
pressure. Close fill valve.  
Completely read, understand and follow all  
instructions in this manual before attempting  
start-up.  
(Note - If make-up water line is equipped with  
pressure reducing valve, adjust pressure reducing  
valve to desired cold fill pressure. Follow fill valve  
manufacturer’s instructions).  
A. Safe operation and other performance criteria were met  
with the gas manifold and control assembly provided  
on boiler when boiler underwent tests specified in  
American National Standard for Gas-Fired Low-  
Pressure Steam and Hot Water Boilers, ANSI Z21.13.  
10. Open isolation valve in boiler supply piping.  
11. Remove hose from purge valve.  
F. Confirm that the boiler and system have no water  
leaks.  
B. Check Main Burners. Main burners must be properly  
located on support bracket in Base Rear Panel, seated  
on Main Burner Orifices, and secured with hitch pin  
clips.  
G. Prepare to check operation.  
1. Obtain gas heating value (in Btu per cubic foot)  
from gas supplier.  
C. Verify that the venting, water piping, gas piping  
and electrical system are installed properly. Refer to  
installation instructions contained in this manual.  
2. Connect manometer to pressure tap on gas valve.  
Use 1/8 NPT tapping provided.  
3. Temporarily turn off all other gas-fired appliances.  
D. Confirm all electrical, water and gas supplies  
are turned off at the source and that vent is clear of  
obstructions.  
4. Turn on gas supply to the boiler gas piping.  
5. Confirm that the supply pressure to the gas valve is  
14 in. w.c. or less.  
E. FILL ENTIRE HEATING SYSTEM WITH WATER  
and vent air from system. Use following procedure on  
a Series Loop or multi-zoned system installed as per  
Figure 23 to remove air from system when filling.  
6. Open the field installed manual gas shut-off valve  
located upstream of the gas valve on the boiler.  
7. Using soap solution, or similar non-combustible  
solution, electronic leak detector or other approved  
method. Check that boiler gas piping, valves, and  
all other components are leak free. Eliminate any  
leaks.  
WARNING  
The maximum operating pressure of this boiler is  
50 psig. Never exceed this pressure. Do not plug  
or modify pressure relief valve.  
8. Purge gas line of air.  
H. Follow Lighting or Operating Instructions to place  
boiler in operation. Refer to label on inside of Front  
Removable Panel or appropriate Figure as listed in  
Table 11.  
1. Close full port ball valve in boiler supply piping.  
2. Isolate all zones by closing zone valves or shut-off  
valves in supply and return of each zone(s).  
3. Attach a hose to the vertical purge valve located  
prior to the full port ball valve in the system supply  
piping. (Note - Terminate hose in five gallon bucket  
at a suitable floor drain or outdoor area).  
DANGER  
Do not use matches, candles, open flames or  
other ignition source to check for leaks.  
4. Starting with one circuit at a time, open zone valve  
or shut-off valve in system supply and return piping.  
Table ꢀꢀ: Lighting and Operating Instructions  
5. Open purge valve.  
Lighting or  
Pilot Flame  
6. Open fill valve (Make-up water line should be  
located directly after full port ball valve in system  
supply piping between air scoop and expansion  
tank).  
Ignition System  
Operating  
Instructions  
Figure 43  
Illustration  
Standing Pilot (24)  
Honeywell EI  
OP  
Figure 48  
Figure 49  
Figure 50  
Figure 51  
Figure 50  
Figure 51  
Figure 44  
Figure 45  
Figure 46  
7. Allow water to overflow from bucket until discharge  
from hose is bubble free for 30 seconds.  
EP  
8. Close the open zone valve or shut-off valve for the  
zone being purged of air, then open the zone valve  
or shut-off valve for the next zone to be purged.  
Repeat this step until all zones have been purged. At  
OP-CSD-1  
EP-CSD-1  
Figure 47  
completion, open all zone valves or shut-off valves.  
52  
Figure 43: Lighting Instructions (24V Standing Pilot)  
53  
Figure 44: Operating Instructions (EI)  
54  
Figure 45: Lighting Instructions (OP)  
55  
Figure 46: Operating Instructions (EP)  
56  
BOILER OPERATING INSTRUCTIONS  
TO SHUT DOWN:  
1. Close manual main shut-off valve(s) and pilot  
valve(s).  
2. Turn off main electric switch.  
TO START UP:  
1. Make sure that both the main manual and the pilot  
valve(s) have been off for at least five minutes.  
2. Turn room thermostat and all operating controls to  
lowest setting.  
3. Remove burner access panel(s).  
4. Open manual pilot valve(s).  
NOTE:  
Item (5) applies only to boilers with standing pilot  
safety switch(es).  
5. Depress button on standing pilot safety switch and  
hold lighted match to pilot, holding button in for at  
least one minute or until pilot remains lighted after  
button is released. Repeat for remaining standing  
pilots.  
6. Turn on main electric switch.  
7. Reset safety switch on flame safeguard relay.  
8. Immediately light constant burning rectification pilot(s)  
Q179D with a lighted match. If pilot is not lighted  
in 15 seconds, Step (7) must be repeated. Electric  
pilot valve(s) are automatic, opening after Step (7).  
(“OP” System).  
8a. Intermittent electric ignition rectification pilot(s)  
Q179C light up automatically when thermostat or  
operating control calls for heat. (“EP” System).  
9. Replace burner access panel(s).  
10. Open manual main shut-off valve(s).  
11. Adjust room thermostat and operating controls to  
desired setting.  
Figure 4ꢁ: Lighting / Operating Instructions (OP/EP-CSD-ꢀ)  
5ꢁ  
Figure 48: Honeywell Q3ꢀ4 Pilot Flame  
(24V Standing Pilot)  
Figure 50: Honeywell QꢀꢁꢂD Pilot Flame (OP)  
Figure 5ꢀ: Honeywell QꢀꢁꢂC Pilot Flame (EP)  
Figure 4ꢂ: Honeywell Q348 Pilot Flame  
(24V Electronic Ignition)  
I. Check pilot burner flame and main burner flames  
through observation port.  
1. Check pilot flame. Refer to Table 11 for appropriate  
pilot detail.  
2. Adjust thermostat to highest setting.  
3. Check main burner flames. See Figure 52. Flame  
should have clearly defined inner cones with no  
yellow tipping. Orange-yellow streaks caused  
by dust should not be confused with true yellow  
tipping.  
Yellow-tipping indicates lack of primary air.  
Improper burner alignment on Main Burner Orifice  
will also affect primary air injection. Adjust primary  
air as follows:  
Figure 52: Main Burner Flame  
58  
3. Clock gas meter for at least 30 seconds. Use Table  
12 to determine gas flow rate in Cubic Feet per  
Hour.  
CAUTION  
Avoid operating this boiler in an environment  
where saw dust, loose insulation fibers, dry wall  
dust, etc. are present. If boiler is operated under  
these conditions, the burner interior and ports  
must be cleaned and inspected daily to insure  
proper operation.  
Table ꢀ2: Input Rate  
Size of Gas Meter Dial  
Seconds  
for One  
Revolution  
One-Half  
Cu. Ft.  
One  
Cu. Ft.  
Two  
Cu. Ft.  
Five  
Cu. Ft.  
30  
32  
34  
36  
40  
38  
40  
42  
44  
46  
48  
50  
52  
54  
56  
58  
60  
62  
64  
66  
68  
70  
72  
74  
76  
78  
80  
60  
56  
53  
50  
45  
47  
45  
43  
41  
39  
37  
36  
35  
33  
32  
31  
30  
29  
29  
29  
28  
26  
25  
24  
24  
23  
22  
120  
113  
106  
100  
90  
95  
90  
86  
82  
78  
75  
72  
69  
67  
64  
62  
60  
58  
56  
54  
53  
51  
50  
48  
47  
46  
45  
240  
225  
212  
200  
180  
189  
180  
172  
164  
157  
150  
144  
138  
133  
129  
124  
120  
116  
112  
109  
106  
103  
100  
97  
600  
563  
529  
500  
450  
474  
450  
430  
410  
391  
375  
360  
346  
333  
321  
310  
300  
290  
281  
273  
265  
257  
250  
243  
237  
231  
225  
a. Loosen lock screw.  
b. Close air adjustment until yellow tips appear on  
flames.  
c. Slowly open air adjustment until clearly defined  
inner cones are visible.  
d. Tighten lock screw.  
4. Adjust thermostat to normal setting.  
J. Check thermostat or operating control operation.  
Raise and lower temperature setting to start and stop  
boiler operation.  
K. Check ignition system shut-off.  
1. Standing Pilot (24V): Disconnect thermocouple  
lead at Gas Valve. Gas Valve must close and pilot  
and main burners extinguish. If not, replace the gas  
valve.  
2. Honeywell EI: Disconnect ignitor/sensor cable from  
ignition module. Gas valve must close and pilot and  
main burners extinguish. If not, measure voltage  
across gas valve terminals “TH” and “TR”.  
a. If voltage is not present, replace gas valve.  
b. If voltage is present, replace ignition module.  
3. EP and OP: Refer to instructions supplied with the  
Honeywell RM7890 Burner Control.  
L. Check Limit(s).  
1. Adjust thermostat to highest setting.  
95  
2. Observe temperature gauge. When temperature  
exceeds limit set point main burners should  
extinguish.  
92  
90  
3. Adjust limit to setting above observed reading. Main  
burners should reignite.  
4. Determine Input Rate. Multiply gas flow rate by gas  
heating value.  
4. Adjust thermostat to lowest setting. Adjust limit to  
desired setting.  
Warning  
M. Adjust gas input rate to boiler. Natural Gas.  
Failure to properly adjust gas input rate will result  
in over firing or under firing of the appliance.  
Improper and unsafe boiler operation may result.  
1. Adjust thermostat to highest setting.  
2. Check manifold gas pressure. Manifold pressure  
is listed on rating label. Adjust gas valve pressure  
regulator as necessary (turn adjustment screw  
counterclockwise to decrease manifold pressure, or  
clockwise to increase manifold pressure). If pressure  
can not be attained, check gas valve inlet pressure.  
If less than minimum gas supply pressure listed on  
rating label, contact gas supplier for assistance.  
5. Compare measured input rate to input rate stated on  
rating label.  
a. Boiler must not be overfired. Reduce input rate  
by decreasing manifold pressure. Do not reduce  
more than 0.3 inch w.c. If boiler is still overfired,  
contact your Burnham distributor or Regional  
Office for replacement Gas Orifices.  
5ꢂ  
b. Increase input rate if less than 98% of rating  
plate input. Increase manifold gas pressure no  
more than 0.3 inch w.c. If measured input rate is  
still less than 98% of rated input:  
reworked system should be boiled out, and then  
thoroughly flushed. A qualified water treatment  
chemical specialist should be consulted for  
recommendations regarding appropriate chemical  
compounds and concentrations which are compatible  
with local environmental regulations.  
i. Remove Main Burners per procedure in  
Section IX: Service.  
ii. Remove gas orifices. Drill one (1) drill size  
larger (drill size is stamped on orifice, or see  
Key No. 4E).  
iii. Reinstall gas orifices and main burners.  
Measure input rate.  
P. Check Damper Operation - If boiler is equipped with  
vent damper, vent damper must be in open position  
when boiler main burners are operating. Start boiler,  
refer to instructions on damper to determine if damper  
is in full open position.  
6. Recheck Main Burner Flame.  
Q. Install Front Removable Panel.  
7. Return other gas-fired appliances to previous  
1. Engage top flange (longer of 2 flanges) behind  
conditions of use.  
Upper Front Panel.  
N. Adjust gas input rate to boiler. LP/Propane.  
2. Swing lower portion of door toward boiler.  
1. Set thermostat to highest setting.  
3. Lower door to engage bottom flange behind Lower  
2. Adjust tank regulator for gas valve inlet pressure of  
13.5 inches w.c. or less.  
Front Tie Bar.  
R. Combustion Chamber Burn-Off  
3. Gas valve has step opening regulator which initially  
opens to 1.4 or 2.5 inch w.c. and steps to full  
1. The mineral wool combustion chamber panels  
contain a cornstarch based binder that must be  
burned out at installation to prevent odors during  
subsequent boiler operation.  
pressure after approximately 30 seconds. Check  
manifold pressure after step has occurred. Adjust gas  
valve pressure regulator as necessary for 10.0 inches  
w.c. (turn adjustment screw counterclockwise to  
decrease manifold pressure, or clockwise to increase  
manifold pressure). If 10.0 inches w.c. can not be  
attained, check gas valve inlet pressure. If less than  
11.0 inches w.c., contact gas supplier for assistance.  
2. Ventilate the boiler room, set the high limit to its  
maximum setting, set the thermostat to call for heat.  
3. Allow the boiler to fire for at least an hour or until  
the odor from the cornstarch has dissipated.  
4. Return the high limit and thermostat to their desired  
settings.  
O. Clean Heating System  
Oil, grease, and other foreign materials which  
accumulate in new hot water boilers and a new or  
S. Review User’s Information Manual and system  
operation with owner or operator.  
60  
IX. Service  
WARNING  
Service on this boiler should be undertaken only by trained and skilled personnel from a qualified service  
agency. Inspections should be performed at intervals specified in this manual. Maintain manual in a  
legible condition.  
Keep boiler area clear and free of combustible materials, gasoline and other flammable vapors and  
liquids.  
Do not place any obstructions in boiler room that will hinder flow of combustion and ventilation air.  
The service instructions contained in this manual are in addition to the instructions provided by the  
manufacturer of the boiler components. Follow component manufacturer’s instructions. Component  
manufacturer’s instructions were provided with the boiler. Contact component manufacturer for replace-  
ment if instructions are missing. Do not install, start up, operate, maintain or service this boiler without  
reading and understanding all of the component instructions. Do not allow the boiler to operate with  
altered, disconnected or jumpered components. Only use replacement components identical to those  
originally supplied by Burnham Commercial.  
A. General. Inspection and service must be conducted  
annually. Turn off electrical power and gas supply while  
conducting service or maintenance. Follow instructions  
TO TURN OFF GAS TO APPLIANCE. See Lighting/  
Operating Instructions on inside of Front Removable  
Door.  
4. Remove burner access panel(s).  
5. Mark location of Main Burner with Pilot Bracket on  
manifold.  
6. Remove hitch pin clips from Main Burner Orifices.  
7. Hold Main Burner on throat. Lift slightly to raise  
rear of burner. Push to rear of boiler until burner  
clears Main Burner Orifice. Lift burners out.  
WARNING  
8. Check burners to be sure they do not contain foreign  
matter or restrictions. Clean burners with a soft  
bristle brush, blow any dirt out with compressed air  
or use a vacuum cleaner. See Figure 53.  
Label all wires prior to disconnection when  
servicing controls. Wiring errors can cause  
improper and dangerous operation. Verify proper  
operation after servicing.  
E. Clean Boiler Flueways. See Figure 53.  
B. Maintenance of Low Water Cut-off (if used). Follow  
1. Shut down gas boiler in accordance with Lighting/  
Operating Instructions on inside of Front Removable  
Door. Close Manual Shut-off Valve.  
instructions provided with low water cut-off.  
C. Vent System. Check for:  
1. obstructions  
2. Disconnect vent system. Remove Draft Hood.  
3. Remove Jacket Top Panel.  
2. accumulations of soot  
3. deterioration of vent pipe or vent accessories due to  
condensation or other reasons  
4. Remove Canopy from top of boiler.  
5. Lift Flue Baffles out of flueways. Remove any  
4. proper support—no sags, particularly in horizontal  
runs  
accumulated scale or soot.  
6. Thoroughly clean flueways with flue brush,  
5. tightness of joints. Remove all accumulations of  
soot with wire brush and vacuum  
removing all scale and soot. See Figure 53.  
7. Clean boiler heating surface accessible from  
combustion chamber with straight handle wire  
brush.  
Remove all obstructions. Replace all deteriorated parts  
and support properly. Seal all joints.  
8. Reinsert Blue Baffles into flueways. See Figure 53  
for correct baffle orientation. Tabs at top of each  
baffle should rest o top of Flue Pins.  
D. Remove Main Burners for cleaning, changing orifice  
plugs, or repairs.  
1. Shut down gas boiler in accordance with Lighting/  
Operating Instructions on inside of Front Removable  
Door. Close Manual Shut-off Valve.  
9. Install Canopy. See Section II: Boiler Assembly,  
Paragraph G.  
10. Install Jacket Top Panel, Draft Hood, Vent Damper  
(if used) and Vent System.  
2. Remove Front Removable Door. Raise Lower Front  
Tie Bar.  
3. Disconnect ignition system.  
6ꢀ  
Important Product Safety Information  
Refractory Ceramic Fiber Product  
Warning:  
The Repair Parts list designates parts that contain refractory ceramic fibers  
(RCF). RCF has been classified as a possible human carcinogen. When  
exposed to temperatures about 1805°F, such as during direct flame contact,  
RCF changes into crystalline silica, a known carcinogen. When disturbed as a  
result of servicing or repair, these substances become airborne and, if inhaled,  
may be hazardous to your health.  
AVOID Breathing Fiber Particulates and Dust  
Precautionary Measures:  
Do not remove or replace RCF parts or attempt any service or repair work  
involving RCF without wearing the following protective gear:  
1. A National Institute for Occupational Safety and Health (NIOSH)  
approved respirator  
2. Long sleeved, loose fitting clothing  
3. Gloves  
4. Eye Protection  
• Take steps to assure adequate ventilation.  
• Wash all exposed body areas gently with soap and water after contact.  
• Wash work clothes separately from other laundry and rinse washing  
machine after use to avoid contaminating other clothes.  
• Discard used RCF components by sealing in an airtight plastic bag. RCF  
and crystalline silica are not classified as hazardous wastes in the United  
States and Canada.  
First Aid Procedures:  
• If contact with eyes: Flush with water for at least 15 minutes. Seek  
immediate medical attention if irritation persists.  
• If contact with skin: Wash affected area gently with soap and water.  
Seek immediate medical attention if irritation persists.  
• If breathing difficulty develops: Leave the area and move to a location  
with clean fresh air. Seek immediate medical attention if breathing  
difficulties persist.  
• Ingestion: Do not induce vomiting. Drink plenty of water. Seek  
immediate medical attention.  
62  
Figure 53: Boiler Flueway Cleaning  
F. Clean Combustion Chamber by vacuuming. Exercise  
care to avoid damaging Base Insulation.  
G. Install Burners by reversing procedures used to  
remove burners. Verify Main Burners are properly  
located on support bracket in Base Rear Panel, seated  
on Main Burner Orifices, and secured with hitch pin  
clips. Verify Main Burner with Pilot Bracket is in  
proper location. See Table 13.  
Table ꢀ3: Pilot Burner Location  
Boiler Model  
805H  
Pilot Located Between Burners*  
4 & 5  
5 & 6  
6 & 7  
6 & 7  
7 & 8  
8 & 9  
806H  
807H  
H. Lubrication. Manufacturers Instruction should be  
followed on all parts installed on boiler requiring  
lubrication. This includes type of lubricant to be used,  
frequency of lubrication, and points to lubricate.  
808H  
809H  
810H  
* Burners numbered left to right as viewed from front of boiler.  
I. Check operation. Refer to Section VIII: System Start-  
up.  
63  
Honeywell EI Ignition Module Yellow LED Flame Codes  
Yellow LED  
Indicates  
Recommended Service Action  
N/A  
Flash Codea  
Heartbeat  
Normal Flame Signal  
Weak Flame Signal -  
System will operate reliably but flame signal is less than  
desired.  
Note: This indication may flash temporarily during or  
shortly after lightoff on some applications.  
Perform routine maintenance to  
assure optimum flame signal.  
2
Marginal Flame Signal (less than 1.1 µA) -  
System may not operate reliably over time. Service call  
recommended.  
Note: This indication may flash temporarily during or  
shortly after lightoff on some applications.  
Check gas supply, pilot burner, flame  
sense wiring, contamination of flame rod,  
burner ground connection.  
1
No Flame or Flame Signal -  
below minimum threshold for system operation.  
OFF  
N/A  
aFlash Code Descriptions  
- Heartbeat: Constant ½ second bright, ½ second dim cycles.  
- The flash code number signifies that the LED flashes X times at 2Hz, remains off for two seconds, and then repeats  
sequence.  
64  
Honeywell EI Ignition Module Green LED Status Codes  
Green LED  
Flash Code  
Indicates  
Next System Action  
Recommended Service Action  
(X + Y)a  
OFF  
No “Call for Heat”  
N/A  
N/A  
N/A  
None  
None  
None  
Startup - Flame sense  
calibration  
Flash Fast  
Heartbeat Normal operation  
If system fails to light on next trial for  
ignition check gas supply, pilot burner,  
spark and flame sense wiring, flame rod  
contamination or out of position, burner  
ground connection.  
5 minute Retry Delay-  
Pilot flame not detected  
during trial for ignition  
Initiate new trial for ignition after  
retry delay completed.  
2
3
If system fails to light on next trial  
for ignition check gas supply, pilot  
burner, flame sense wiring, flame rod  
contamination, burner ground connection.  
Initiate new trial for ignition. Flash  
code will remain through the ignition  
trial until flame is proved.  
Recycle- Flame failed  
during run  
If situation self corrects within 10  
seconds, control returns to normal  
Check for pilot flame. Replace gas valve  
Flame sensed out of  
sequence  
sequence. If flame out of sequence if pilot flame present. If no pilot flame,  
remains longer than 10 seconds, cycle “Call for Heat.” If error repeats,  
4
control goes to Flash code 6+4 (see replace control.  
below)  
Control remains in wait mode.  
Flame sense leakage to When the fault corrects, control  
Check flame sense lead wire for damage  
or shorting. Check that flame rod is in  
proper position. Check flame rod ceramic  
for cracks, damage or tracking.  
7
8
ground  
resumes normal operation after a  
one minute delay.  
Control remains in wait mode.  
When the fault corrects, control  
Check transformer and AC line for proper  
input voltage to the control. Check with  
full system load on the transformer.  
Low secondary voltage  
supply- (below 15.5 Vac) resumes normal operation after one  
minute delay.  
Check gas supply, pilot burner, spark  
and flame sense wiring, flame rod  
contamination or out of position, burner  
ground connection.  
5 minute Retry Delay-  
Initiate new trial for ignition after  
On every third retry on  
retry delay completed.  
same “Call for Heat”  
6 + 2  
6 + 3  
On every 6th flame  
Check gas supply, pilot burner, flame  
sense wiring, contamination of flame rod,  
burner ground connection.  
5 minute retry delay, then initiate  
failure during run on the  
new trial for ignition.  
same “Call for Heat”  
Control waits until flame is no  
Check for pilot flame. Replace gas valve  
if pilot flame present. If no pilot flame,  
cycle “Call for Heat.” If error repeats,  
replace control.  
Flame sensed out of  
sequence- longer than  
10 seconds  
longer sensed and then goes to  
soft lockout. Flash code continues.  
Control auto resets from soft  
lockout after one hour.  
6 + 4  
Soft lockout due to error  
detected during self  
check sequences  
Control auto resets from soft  
lockout after one hour.  
Reset by cycling “Call for Heat.” If error  
repeats, replace the control  
ON  
aFlash Code Descriptions:  
-
-
-
Flash Fast: rapid blinking  
Heartbeat: Constant ½ second bright, ½ second dim cycles.  
A single flash code number signifies that the LED flashes X times at 2Hz, remains off for two seconds, and then  
repeats the sequence.  
-
X + Y flash codes signify that the LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at  
2 Hz, remains off for three seconds, and then repeats the sequence.  
65  
Honeywell EI Trouble Shooting Guide  
66  
X. Repair Parts  
All Series 8H Repair Parts may be obtained through your local Burnham Wholesale distributor. Should  
you require assistance in locating a Burnham Distributor in your area, or have questions regarding the  
availability of Burnham products or repair parts, please contact Burnham Customer Service at:  
(717) 481-8400 or Fax (717) 481-8408.  
6ꢁ  
Quantity  
Item No.  
Description  
Part No.  
805H  
806H  
807H  
808H  
809H  
810H  
ꢀ. Heat Exchanger Assembly  
6171605  
6171606  
6171607  
6171608  
6171609  
6171610  
7171601  
7171603  
7171602  
80861032  
80861033  
80861013  
80861034  
80861035  
80861036  
80860600  
80860400  
7066002  
7111622  
1
---  
---  
---  
---  
---  
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
1
1
Complete (Less Flue Baffles)  
---  
---  
---  
1
---  
---  
1
---  
1
1A  
1B  
1C  
Left End Section  
1
Intermediate Section  
Right End Section  
3
4
5
6
7
8
1
1
1
1
1
1
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
4
---  
---  
---  
---  
4
1D  
Tie Rod  
---  
---  
---  
4
---  
---  
4
---  
4
1E  
1F  
1G  
1H  
Washer  
4
Nut  
4
4
4
4
4
4
Slip Nipple, 3”  
Flue Baffle  
8
10  
5
12  
6
14  
7
16  
8
18  
9
4
68  
Quantity  
Item No.  
Description  
Part No.  
805H  
806H  
807H  
808H  
809H  
810H  
2. Canopy  
6111605  
6111606  
6111607  
6111608  
6111609  
6111610  
80860115  
80860603  
80860407  
1
---  
---  
---  
---  
---  
2
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
2
2A  
Canopy  
---  
---  
---  
2
---  
---  
2
---  
2
2B  
2C  
2D  
Bolt, Carriage, ¼ - 20 x 1”  
Washer, ¼” Flat  
2
2
2
2
2
2
2
Nut, ¼” - 20  
2
2
2
2
2
2
6ꢂ  
Quantity  
Item  
No.  
Description  
Part No.  
805H  
806H  
807H  
808H  
809H  
810H  
3. Base Assembly  
3A  
Base End Panel  
7181601  
61816052  
61816062  
61816072  
61816082  
61816092  
61816102  
61816051  
61816061  
61816071  
61816081  
61816091  
61816101  
61816053  
61816063  
61816073  
61816083  
61816093  
61816103  
61816054  
61816064  
61816074  
61816084  
61816094  
61816104  
7041601  
2
2
2
---  
2
2
---  
---  
2
2
---  
---  
---  
2
2
---  
---  
---  
---  
2
2
---  
---  
---  
---  
---  
2
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
3B  
Base Channel Assembly  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
3C  
3D  
3E  
Base Rear Panel Assembly  
Base Front Panel Assembly  
Burner Access Panel Assembly  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
2
---  
---  
---  
---  
---  
2
---  
---  
---  
---  
---  
2
---  
---  
---  
---  
---  
4
---  
---  
---  
---  
4
---  
---  
---  
4
---  
---  
4
---  
4
3F  
3G  
3H  
3J  
Jacket Attachment Bracket  
Bolt, Carriage, ¼ - 20 x 1¼”  
Washer, ¼” Flat  
4
80860106  
80860603  
80860407  
80860700  
80861302  
80861311  
80860000  
80860600  
80860403  
80860702  
4
4
4
4
4
4
4
4
4
4
4
4
Nut, ¼ - 20  
4
4
4
4
4
4
3K  
3L  
Screw, Self Tapping, ¼ - 20 x ½”  
Screw, Cap, Hex Head, 5/16” - 18 x ¾”  
Screw, Cap, Hex Head, 5/16 - 18 x 1¼”  
Screw, Sheet Metal, #8 x ½”  
Washer, 3/8” Flat  
3
4
4
5
5
6
2
2
2
2
2
2
3M  
3N  
3P  
3Q  
3R  
6
6
6
6
6
6
8
8
8
8
8
8
6
6
6
6
6
6
Nut, 5/16”  
6
6
6
6
6
6
Screw, Self Tapping, ¼ - 20 x ¾”  
10  
10  
10  
10  
10  
10  
ꢁ0  
Quantity  
Item  
No.  
Description  
Part No.  
805H  
806H  
807H  
808H  
809H  
810H  
4. Manifold and Main Burners  
4A  
Main Burner  
8231602  
8231601  
8231604  
8
---  
1
10  
1
12  
1
15  
1
17  
1
19  
1
Main Burner with Pilot Bracket, Standing Pilot (24V)  
Main burner with Pilot Bracket, Honeywell EI  
Main Burner with Pilot Bracket, OP  
Main burner with Pilot Bracket, EP  
1
1
1
1
1
4B  
8231603  
---  
1
1
1
1
1
82216051  
82216061  
82216071  
82216081  
82216091  
82216101  
---  
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
1
4C  
Manifold  
---  
---  
---  
1
---  
---  
1
---  
1
4D  
4E  
4F  
Pipe Plug, 1/8 NPT (Included with 4C)  
Main Burner Orifice, #39 (Natural Gas Only *  
Main Burner Orifice, #53 (LP/Propane Only) *  
Hitch Pin Clip  
1
822603  
9
11  
13  
13  
16  
16  
18  
18  
20  
20  
8226002  
822604  
9
11  
* Main burner orifice sizes shown for normal altitude (0-2000 feet). For High Altitude consult factory.  
ꢁꢀ  
Item  
No.  
Description  
Part No.  
Size  
Quantity  
5-ꢀ Gas Train -- Standing Pilot (24V, OP)  
24V: USA & Canada, 6 & ꢁ Section, Natural & LP Gas  
OP: USA & Canada, 6 - ꢀ0 Section, Natural & LP Gas  
Gas Valve, Robertshaw 7000ERHC-S7C, Natural Gas, 1” NPT  
Gas Valve, Robertshaw 7000ERHC-LP-S7C, LP Gas, 1” NPT  
Solenoid Gas Valve, Honeywell V8295A1024, ¾” NPT  
Solenoid Gas Valve, Honeywell V8295A1032, 1” NPT  
81660156  
A
B
806H - 810H  
1
81660157  
81660235  
81660236  
806H-807H  
808H-810H  
1
1
808H-810H  
Canada Only  
C
D
Lubricated Manual Shut-Off Valve, Newman-Milliken 200M, 1” NPT  
822619  
1
Hex Bushing, 1” NPT x ¾” NPT  
Nipple, ¾” NPT x 2” Lg.  
806600501  
806600003  
806600004  
806601512  
806601513  
806H & 807H  
806H & 807H  
808H-810H  
1
USA: 1  
Canada: 2  
E
F
Nipple, 1” NPT x 2” Lg.  
Street Elbow, 1” NPT x ¾” NPT  
Street Elbow, 1¼” NPT x 1” NPT  
806H - 807H  
808H - 810H  
1
ꢁ2  
Item  
No.  
Description  
Part No.  
Quantity  
5-2 Gas Train -- Standing Pilot (OP-CSD-ꢀ)  
OP-CSD-ꢀ: USA Only, 8-ꢀ0 Section, LP Gas Only  
A
B
C
D
E
F
Gas Valve, Robertshaw 7000GVERHC-S7C, LP Gas, 1” NPT  
81660271  
81660236  
822615  
1
1
1
2
2
1
2
1
1
1
1
1
Solenoid Gas Valve, Honeywell V8295A1032, 1” NPT  
Lubricated Manual Shut-Off Valve, Conbraco #50-403-02, 1” NPT  
Leak Test/Shut-off Valve, Conbraco #56-221-01, 1/8” x 1/8”  
Pipe Plug, 1/8”  
822679  
806603594  
806600520  
806600004  
806601514  
806600033  
806602502  
6136230  
Hex Bushing, 1/4” x 1/8”  
G
H
J
Nipple, 1” x 2” Long  
Street Elbow, 90° x 1”  
Close Nipple, 1”  
K
L
Malleable Coupling, 1-1/4” x 1”  
Wiring Harness, Gas Valve to Solenoid Valve  
Pilot Outlet Plug, Honeywell #394424  
M
8226051  
ꢁ3  
Item  
No.  
Description  
Part No.  
Size  
Quantity  
5-3 Gas Train -- Intermittent Ignition (EI)  
USA: 5 - ꢀ0 Section, Natural and LP Gas  
Canada: 5 - ꢀ0 Section, Natural Gas  
5 - ꢁ Section, LP Gas  
Gas Valve, Robertshaw 7000DERHC, Natural Gas, 1” NPT  
81660151  
81660158  
805H-810H  
A
1
USA: 805H-810H  
Canada: 805H-807H  
Gas Valve, Robertshaw 7000DERHC-LP, LP Gas, 1” NPT  
B
C
Lubricated Manual Shut-Off Valve, Newman-Milliken 200M, 1” NPT  
Nipple, 1’ NPT x 2” Lg.  
822619  
808H-810H  
Canada Only  
1
1
806600004  
806601514  
806601513  
Street Elbow, 1” NPT  
805H-807H  
808H-810H  
D
Street Elbow, 1¼” NPT x 1” NPT  
ꢁ4  
Item  
No.  
Description  
Part No.  
Size  
Quantity  
5-4 Gas Train -- Intermittent Ignition (EP)  
USA & Canada: 6 - ꢀ0 Section, Natural Gas Only  
A
Gas Valve, Robertshaw 7000GVERHC-S7C, Natural Gas, 1” NPT  
81660168  
81660235  
81660236  
806H-810H  
806H-807H  
808H-810H  
1
1
Solenoid Gas Valve, Honeywell V8295A1024, ¾” NPT  
Solenoid Gas Valve, Honeywell V8295A1032, 1” NPT  
B
808H-810H  
Canada Only  
C
D
Lubricated Manual Shut-Off Valve, Newman-Milliken 200M, 1” NPT  
822619  
1
Hex Bushing, 1” NPT x ¾” NPT  
Nipple, ¾” NPT x 2” Lg.  
806600501  
806600003  
806H & 807H  
806H & 807H  
1
1
E
F
USA: 1  
Canada: 2  
Nipple, 1” NPT x 2” Lg.  
806600004  
808H-810H  
Street Elbow, 1” NPT x ¾” NPT  
Street Elbow, 1¼” NPT x 1” NPT  
806601512  
806601513  
806H & 807H  
808H-810H  
1
ꢁ5  
Item  
No.  
Description  
Part No.  
Quantity  
5-5 Gas Train -- Intermittent Ignition (EP-CSD-ꢀ)  
USA Only: 8 - ꢀ0 Section, Natural Gas Only  
A
B
C
D
E
F
Gas Valve, Robertshaw 7000GVERHC-S7C, Natural Gas, 1” NPT  
81660168  
81660236  
822615  
1
1
1
2
2
1
2
1
1
1
1
1
Solenoid Gas Valve, Honeywell V8295A1032, 1” NPT  
Lubricated Manual Shut-Off Valve, Conbraco #50-403-02, 1” NPT  
Leak Test/Shut-Off Valve, Conbraco #56-221-01, 1/8” x 1/8”  
Pipe Plug, 1/8”  
822679  
806603594  
806600520  
806600004  
806601514  
806600033  
806602502  
6136230  
Hex Bushing, 1/4” x 1/8”  
G
H
J
Nipple, 1” x 2” Long  
Street Elbow, 90° x 1”  
Close Nipple, 1”  
K
L
Malleable Coupling, 1-1/4” x 1”  
Wiring Harness, Gas Valve to Solenoid Valve  
Pilot Outlet Plug, Honeywell #394424  
M
8226051  
ꢁ6  
Item  
No.  
Description  
Part No.  
Size  
Quantity  
5-6 Pilot Assembly and Piping -- Standing Pilot (24V)  
USA & Canada: 6 & ꢁ Section, Natural and LP Gas  
Pilot Burner, Honeywell Q314A3687, Natural Gas  
8236033  
8236034  
8236004  
8236008  
A
Pilot Burner, Honeywell Q314A3828, LP Gas  
Thermocouple, Honeywell Q309A1996 w/36” Lg. Lead  
Brass Compression Union, 1/4” OD Tube  
All  
1
B
C
806H & 807H  
1
1
Canada: 806H & 807H  
Natural Gas Only  
D
E
Regulator, Maxitrol RV12LT, Natural Gas  
8226005  
822630  
Canada: 806H & 807H  
Natural Gas Only  
Brass Compression Adapter, 1/4” OD Tube x 1/8” NPT  
2
ꢁꢁ  
Item  
No.  
Description  
Part No.  
Size  
Quantity  
5-ꢁ Pilot Assembly and Piping -- Intermittent Ignition (Honeywell EI) USA  
5 - ꢀ0 Section, Natural and LP Gas  
Pilot Burner, Honeywell Q348A1002, Natural Gas  
Pilot Burner, Honeywell Q348A1010, LP Gas  
Igniter/Sensor Cable, 36” Lg., Honeywell 394803-2  
Ground Wire Assembly  
8236072U  
8236081  
8236121  
6136054  
8236008  
A
1
B
C
D
805H-810H  
1
1
Brass Compression Union, 1/4” OD Tube  
ꢁ8  
Item  
No.  
Description  
Part No.  
Size  
Quantity  
5-8 Pilot Assembly and Piping -- Intermittent Ignition (Honeywell EI) Canada  
5 - ꢀ0 Section, Natural Gas  
5 - ꢁ Section, LP Gas  
Pilot Burner, Honeywell Q348A1002, Natural Gas  
Pilot Burner, Honeywell Q348A1010, LP Gas  
Igniter/Sensor Cable, 36” Lg., Honeywell 394800-36  
Ground Wire Assembly  
8236072U  
8236081  
8236084  
6136054  
8236008  
822645  
805H-810H  
805H-807H  
A
1
B
C
D
E
F
All  
1
1
Brass Compression Union, 1/4” OD Tube  
Shut-Off Valve, Essex P2L  
805H-807H  
Pipe Tee, 1/8” NPT, Malleable  
806601005  
806603508  
808H-810H  
1
G
Pipe Plug, 1/8” NPT, Sq. Head  
805H-807H Natural Gas  
808H-810H Natural Gas  
805H-807H LP Gas  
2
3
1
H
Brass Compression Adapter, 1/4” OD Tube x 1/8” NPT  
822630  
J
K
L
Solenoid Gas Valve, Johnson H91WG-6  
Junction Box, 4” Sq. x 1-1/2” Deep  
Rigid Conduit Nipple, 1/2” NPT x 1-1/2” Lg.  
Conduit Locknut, 1/2”  
822666  
8136259  
8136019  
8136220  
8136034  
1
All  
M
N
2
1
Plastic Insulating Bushing, 1/2”  
805H-810H  
Natural Gas Only  
P
Regulator, Maxitrol RV12LT, Natural Gas  
8226005  
1
ꢁꢂ  
Item  
No.  
Description  
Part No.  
Size  
Quantity  
5-ꢂ Pilot Assembly and Piping -- Standing Pilot (OP)  
USA & Canada: 6 - ꢀ0 Section, Natural and LP Gas  
Pilot Burner, Honeywell Q179D1008, Natural Gas  
8236025  
6236039  
8236004  
71362561  
8236021  
6136259  
A
Pilot Burner, Honeywell Q179D1008 w/388146KD Orifice, LP Gas  
Thermocouple, Honeywell Q309A1996 w/36” Lg. Lead  
Flame Rod Lead, Honeywell R1298020, 4 Ft. Lg.  
Rajah Connector, Honeywell 37356  
B
C
D
E
806H-810H  
1
Ground Wire Assembly  
USA: 806H-810H  
Canada: 806H & 807H  
F
Brass Compression Union, 1/4” OD Tube  
Regulator, Maxitrol RV12LT, Natural Gas  
8236008  
8226005  
1
1
Canada: 806H-810H  
Natural Gas Only  
G
H
J
Pipe Tee, 1/8” NPT, Malleable  
Pipe Plug, 1/8” NPT, Sq. Head  
Shut-Off Valve, Essex P2L  
806601005  
806603508  
822645  
808H-810H  
Canada Only  
1
K
806H & 807H  
Natural Gas  
2
L
Brass Compression Adapter, 1/4” OD Tube x 1/8” NPT  
822630  
808H-810H Natural Gas  
806H-810H LP Gas  
3
1
80  
Item  
No.  
Description  
Part No.  
Size  
Quantity  
5-ꢀ0 Pilot Assembly and Piping -- Standing Pilot (OP-CSD-ꢀ)  
USA Only: 8 - ꢀ0 Section, LP Gas Only  
A
B
C
D
E
Pilot Burner, Honeywell Q179D1008 w/388146KD Orifice, LP Gas  
6236039  
8236004  
71362561  
8236021  
6136259  
1
1
1
1
1
Thermocouple, Honeywell Q309A1996 w/36” Lg. Lead  
Flame Rod Lead, Honeywell R1298020, 4 Ft. Lg.  
Rajah Connector, Honeywell 37356  
Ground Wire Assembly  
808H-810H  
F
Brass Compression Union, 1/4” OD Tube  
8236008  
1
G
H
J
Regulator, Maxitrol RV12LT, Natural / LPGas  
Pilot Switch, Johnson L62-GB-3C  
8226005  
80160138  
822679  
1
1
1
2
Conbraco Leak Test / Shut-Off Valve, 1/8” x 1/8”  
Brass Compression Adapter, 1/4” OD Tube x 1/8” NPT  
K
822630  
8ꢀ  
Item  
No.  
Description  
Part No.  
Size  
Quantity  
5-ꢀꢀ Pilot Assembly and Piping -- Intermittent Ignition (EP)  
USA & Canada: 6 - ꢀ0 Section, Natural Gas Only  
A
B
C
D
E
Pilot Burner, Honeywell Q179C1009, Natural Gas  
8236017  
71362561  
8236021  
7136247  
6136259  
1
1
2
1
1
Flame Rod Lead, Honeywell R1298020, 4 Ft. Lg.  
Rajah Connector, Honeywell 37356  
Ignition Lead, Honeywell R1061012, 3 Ft. Lg.  
Ground Wire Assembly  
806H-810H  
806H & 807H  
USA & Canada  
808H-810H  
F
Brass Compression Coupling, 1/4” OD Tube  
8236008  
1
1
USA Only  
G
H
J
Shut-Off Valve, Essex P2L  
Pipe Tee, 1/8” NPT, Malleable  
Pipe Plug, 1/8” NPT, Sq. Head  
822645  
808H-810H  
Canada Only  
806601005  
806603508  
806H & 807H  
Canada Only  
2
3
K
Brass Compression Adapter, 1/4” OD Tube x 1/8” NPT  
822630  
808H-810H  
Canada Only  
L
M
N
P
Solenoid Gas Valve, Johnson H91WA-4  
Junction Box, 4” Sq. x 1-1/2” Deep  
Rigid Conduit Nipple, 1/2” NPT x 1-1/2” Lg.  
Conduit Locknut, 1/2”  
822662  
8136259  
8136019  
8136220  
8136034  
1
1
1
2
1
806H-810H  
Q
Plastic Insulating Bushing, 1/2”  
806H-810H  
Canada Only  
R
Regulator, Maxitrol RV12LT, Natural / LP Gas  
8226005  
1
82  
Item  
No.  
Description  
Part No.  
Size  
Quantity  
5-ꢀ2 Pilot Assembly and Piping -- Intermittent Ignition (EP-CSD-ꢀ)  
USA Only: ꢀ0 Section, Natural Gas Only  
A
B
C
D
E
F
Pilot Burner, Honeywell Q179C1009, Natural Gas  
Flame Rod Lead, Honeywell R1298020, 4 Ft. Lg.  
Rajah Connector, Honeywell 37356  
8236017  
71362561  
8236021  
7136247  
6136259  
8236008  
822679  
1
1
2
1
1
1
1
2
1
1
1
2
1
Ignition Lead, Honeywell R1061012, 3 Ft. Lg.  
Ground Wire Assembly  
Brass Compression Coupling, 1/4” OD Tube  
Conbraco Leak Test / Shut-Off Cock, 1/8” x 1/8”  
Brass Compression Adapter, 1/4” OD Tube x 1/8” NPT  
Solenoid Gas Valve, Johnson H91WA-4  
Junction Box, 4” Sq. x 1-1/2” Deep  
G
H
J
808H-810H  
822630  
822662  
K
L
8136259  
8136019  
8136220  
8136034  
Rigid Conduit Nipple, 1/2” NPT x 1-1/2” Lg.  
Conduit Locknut, 1/2”  
M
N
Plastic Insulating Bushing, 1/2”  
P
Regulator, Maxitrol RV12LT, Natural / LP Gas  
8226005  
1
83  
84  
Quantity  
Item  
No.  
Description  
Part No.  
805H  
806H  
807H  
808H  
809H  
810H  
6. Jacket  
60416111  
60416121  
60416131  
60416141  
60416151  
60416161  
70416053  
70416063  
70416073  
70416083  
70416093  
70416103  
72016058  
72016068  
72016078  
72016088  
72016098  
72016108  
70416056  
70416066  
70416076  
70416086  
70416096  
70416106  
72016059  
72016069  
72016079  
72016089  
72016099  
72016109  
60416056  
60416066  
60416076  
60416086  
60416096  
60416106  
70416051  
70416061  
70416071  
70416081  
70416091  
70416101  
1
---  
----  
---  
---  
---  
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
6
Complete  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
6A  
6B  
6C  
6D  
6E  
6F  
Jacket Top Panel  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
Jacket Top Panel Insulation  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
Jacket Upper Rear Panel  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
Jacket Upper Rear Panel Insulation  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
Jacket Lower Rear Panel  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
Jacket Upper Front Panel  
---  
---  
---  
---  
---  
---  
85  
Quantity  
Item  
No.  
Description  
Part No.  
805H  
806H  
807H  
808H  
809H  
810H  
6. Jacket (Continued)  
7041605  
7041606  
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
7041607  
---  
---  
---  
---  
1
6G  
Jacket Front Removable Panel  
7041608  
---  
---  
---  
1
7041609  
---  
---  
1
7041610  
---  
1
6H  
6J  
Jacket Left Side Panel  
6041601  
1
Jacket Left Side Panel Main Insulation Piece  
Jacket Left Side Panel Upper Corner Insulation Piece  
Jacket Left Side Panel Lower Corner Insulation Piece  
Jacket Right Side Panel  
72016021  
72016023  
72016022  
6041602  
1
1
1
1
1
1
6K  
6L  
1
1
1
1
1
1
1
1
1
1
1
1
6M  
6N  
6P  
1
1
1
1
1
1
Jacket Right Side Panel Main Insulation Piece  
Jacket Right Side Panel Lower Corner Insulation Piece  
72016011  
72016012  
70416055  
70416065  
70416075  
70416085  
70416095  
70416105  
72016057  
72016067  
72016077  
72016087  
72016097  
72016107  
72016056  
72016066  
72016076  
72016086  
72016096  
72016106  
70416052  
70416062  
70416072  
70416082  
70416092  
70416102  
1
1
1
1
1
1
1
1
1
1
1
1
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
6Q  
6R  
6S  
6T  
Jacket Vestibule Panel  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
Jacket Vestibule Panel Upper Insulation Piece  
Jacket Vestibule Panel Lower Insulation Piece  
Jacket Lower Front Tie Bar  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
86  
Quantity  
805H 806H 807H 808H 809H 810H  
Item  
No.  
Description  
Part No.  
ꢁ. Trim and Miscellaneous Controls  
Limit, 140-220°F, Honeywell  
L4080D1218 (EI & Standing Pilot);  
L4080B1212 (EP * OP)  
80160251  
80160474  
1
1
1
1
1
1
A
Immersion Well, ¾” NPT x 1½” Insul. Depth  
80160426  
80160703  
80160452  
100282-01  
8061601  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
B
B1  
C
Limit, Manual Reset, Honeywell L4006E1133  
Immersion Well, ¾” NPT x 3” Insul. Depth  
Temperature - Pressure Gauge  
Nipple, 2 NPT x 10” w/Gauge Tapping  
Safety Relief Valve, ¾ NPT, 50 psi  
Nipple, ¾ NPT x 3½”  
C1  
D
81660302  
806600038  
806603061  
806600038  
806602561  
6016058  
D1  
E
Drain Valve, ¾ NPT, Conbraco 35-302-03  
Nipple, ¾ NPT x 3½”  
E1  
E2  
F
Coupling, ¾ NPT  
Blocked Vent Switch Replacement Assembly  
Flame Roll-out Switch  
G
80160044  
7181612  
G1  
H
Flame Roll-out Switch Mounting Bracket  
Junction Box  
8136010  
Control Center, Honeywell R8285D500  
(Intermittent Circulation builds)  
J
80160155U  
1
1
1
1
1
1
K
L
Transformer, 50VA (Continuous Circulation builds)  
Ignition Module, Honeywell S8610M3009  
80160249  
100958-01  
81316010  
81316011  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
---  
1
---  
1
---  
1
Vestibule Wiring Harness, Complete with Vent Damper Bypass  
Plug (EI and Standing Pilot) (Not Depicted)  
M
---  
---  
---  
8ꢁ  
Quantity  
Item  
No.  
Description  
Part No.  
805H  
806H  
807H  
808H  
809H  
810H  
8. Draft Hood and Automatic Vent Damper  
8111605  
8111604  
8111607  
8111603  
8111608  
8111602  
8111608  
8111601  
8111609  
1
---  
1*  
---  
---  
---  
1*  
---  
---  
---  
---  
---  
1*  
---  
---  
---  
---  
---  
---  
---  
1*  
---  
---  
---  
---  
---  
---  
---  
1*  
---  
---  
---  
---  
---  
---  
---  
---  
1**  
---  
---  
---  
---  
---  
---  
8A  
Draft Hood  
1**  
---  
---  
---  
---  
1**  
---  
---  
1**  
1**  
Automatic Vent Damper, 7”  
Effikal RVGP-7  
8116324  
8116325  
8116326  
8116327  
1
---  
1
---  
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
1
Automatic Vent Damper, 8”  
Effikal RVGP-8  
---  
---  
---  
8B  
Automatic Vent Damper, 9”  
Effikal RVGP-9  
---  
---  
Automatic Vent Damper, 10”  
Effikal RVGP-10  
---  
---  
All components for use in both USA and Canada, unless marked with * for USA Only or ** for Canada Only.  
88  
SERVICE RECORD  
DATE  
SERVICE PERFORMED  
8ꢂ  
SERVICE RECORD  
DATE  
SERVICE PERFORMED  
ꢂ0  
SERVICE RECORD  
DATE  
SERVICE PERFORMED  
ꢂꢀ  

Advent ADV10 User Manual
Attwood 69397 User Manual
Black Decker BL3900 User Manual
Black Decker BLC12650HBC User Manual
Burnham V8 Series User Manual
Casio Desk Calculator With Check Correct Function DJ120D User Manual
Clarion DB265MP User Manual
Crown Boiler BSI103 User Manual
HP (Hewlett Packard) Hewlett Packard Car Amplifier 463A User Manual
JBL GTO6528S User Manual