You can rely on
Installation & Service Instructions
Gold HE A
Range
Condensing
Combination Boiler
These instructions include the Benchmark Commissioning
Checklist and should be left with the user for safe keeping.
© Baxi Heating UK Ltd 2008
Installer Notification Guidelines
Choose Building
Regulations Notification
Route
Competent Person's
Building Control
Self Certification Scheme
Contact your relevant Local
Authority Building Control
(LABC) who will arrange
an inspection or contact
a government approved
inspector
Install and Commission this
appliance to manufacturer's
instructions
Complete the
Benchmark Checklist
If you notify via CORGI Scheme,
CORGI will then notify the
relevant Local Authority
Building Control Scheme
on member's behalf
Install and Commission this
appliance to manufacturer's
instructions
Scheme Members only
Complete the
Benchmark Checklist
Call CORGI on: 0800 408 1007
or log onto:
within 10 days
You must ensure that the
notification number issued by
CORGI is written onto the
Benchmark Checklist
CORGI will record the data and
will send a certificate of
LABC will record the data
and will issue a
compliance to the property
certificate of compliance
3
© Baxi Heating UK Ltd 2008
Legislation
IMPORTANT - Installation, Commissioning, Service & Repair
This company declare that no substances harmful to health
are contained in the appliance or used during appliance
manufacture.
This appliance must be installed in accordance with the manufacturer’s instructions and
the regulations in force. Read the instructions fully before installing or using the
appliance.
The appliance is suitable only for installation in GB and IE and
should be installed in accordance with the rules in force, and
only used in a suitably ventilated location.
In GB, this must be carried out by a competent person as stated in the Gas Safety
(Installation & Use) Regulations.
In GB, the installation must be carried out by a CORGI
Registered Installer. It must be carried out in accordance with
the relevant requirements of the:
Definition of competence: A person who works for a CORGI registered company and
holding current certificates in the relevant ACS modules, is deemed competent.
• Gas Safety (Installation & Use) Regulations.
• The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building
Regulations (Northern Ireland).
• The Water Fittings Regulations or Water Byelaws in
Scotland.
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domestic
Gas Installations”.
The addition of anything that may interfere with the normal operation of the appliance
without express written permission from the manufacturer or his agent could invalidate
the appliance warranty. In GB this could also infringe the Gas Safety (Installation and
Use) Regulations.
• The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be
made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a competent
Person and installed in accordance with the current edition of
I.S. 813 ‘Domestic Gas Installations’, the current Building
Regulations and reference should be made to the current ETCI
rules for electrical installation.
Warning - Check the information on the data plate is compatible with local supply
conditions.
All CORGI registered installers carry a CORGI identification card and have a
All systems must be thoroughly flushed and treated with
inhibitor (see section 6.2).
registration number. You can check your installer is registered by telephoning
0800 915 0485 or writing to:-
1 Elmwood,
Chineham Park,
Crockford Lane,
Basingstoke. RG24 8WG
Codes of Practice - refer to the most recent version
In GB the following Codes of Practice apply:
Standard
BS 6891
BS 5546
Scope
Gas Installation.
Installation of hot water supplies for domestic
purposes.
Forced circulation hot water systems.
Installation of gas fired hot water boilers.
Flues.
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency)
o
BS 5449
BS 6798
BS 5440 Part 1
BS 5440 Part 2
BS 7074
Regulations 1993 N 3083” and is deemed to meet the requirements of Directive
92/42/EEC on the energy efficiency requirements for new hot water boilers fired with
liquid or gaseous fuels:-
Ventilation.
Expansion vessels and ancillary equipment for
sealed water systems.
BS 7593
Treatment of water in domestic hot water
central heating systems.
Type test for purpose of Regulation 5 certified by:
Notified Body 0085.
In IE the following Codes of Practice apply:
Standard
I.S. 813
Scope
Product/Production certified by:
Notified Body 0085 & 0086.
Domestic Gas Installations.
The following standards give valuable additional information;
BS 5546
Installation of hot water supplies for domestic
purposes.
BS 5449
BS 7074
Forced circulation hot water systems.
Expansion vessels and ancillary equipment for
sealed water systems.
For GB/IE only.
BS 7593
Treatment of water in domestic hot water
central heating systems.
4
© Baxi Heating UK Ltd 2008
Safe Manual Handling
General
The following advice should be adhered to, from when first handling the boiler to the final stages of installation, and also during maintenance.
Most injuries as a result of inappropriate handling and lifting are to the back, but all other parts of the body are vulnerable, particularly shoulders, arms and hands.
Health & Safety is the responsibility of EVERYONE.
There is no ‘safe’ limit for one man - each person has different capabilities. The boiler should be handled and lifted by TWO PEOPLE.
Do not handle or lift unless you feel physically able.
Wear appropriate Personal Protection Equipment e.g. protective gloves, safety footwear etc.
Preparation
Co-ordinate movements - know where, and when, you are both going.
Minimise the number of times needed to move the boiler - plan ahead.
Always ensure when handling or lifting the route is clear and unobstructed. If possible avoid steps, wet or slippery surfaces, unlit areas etc. and take special care
on ladders/into lofts.
Technique
When handling or lifting always use safe techniques - keep your back straight, bend your knees. Don’t twist - move your feet, avoid bending forwards and
sideways and keep the load as close to your body as possible.
Where possible transport the boiler using a sack truck or other suitable trolley.
Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary. See the
‘Installation’ section of these instructions for recommended lift points.
Remember
The circumstances of each installation are different. Always asses the risks associated with handling and lifting according to the individual conditions.
If at any time when installing the boiler you feel that you may have injured yourself STOP !!
DO NOT ‘work through’ the pain - you may cause further injury.
IF IN ANY DOUBT DO NOT HANDLE OR LIFT THE BOILER - OBTAIN ADVICE OR ASSISTANCE BEFORE PROCEEDING !!
5
© Baxi Heating UK Ltd 2008
CONTENTS
Section
1.0
Page
Introduction
7
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
General Layout
8
9
Appliance Operation
Technical Data
10
11
12
15
19
24
28
34
37
38
40
49
50
51
52
58
Dimensions and Fixings
System Details
Site Requirements
Flue Options
Plume Displacement
10.0 Installation
11.0 Commissioning
12.0 Completion
13.0 Servicing
14.0 Changing Components
15.0 Combustion Check
16.0 Electrical
17.0 Short Parts List
18.0 Fault Finding
Benchmark Checklist
6
© Baxi Heating UK Ltd 2008
1.0 Introduction
1.1
Description
1. The Potterton Gold Combi HE A is a fully automatic gas
fired wall mounted condensing combination boiler. It is room
sealed and fan assisted, and will serve central heating and
mains fed domestic hot water.
Case Front Panel
2. The boiler is set to give a maximum output of :-
24 models - 24 kW DHW
21 kW CH (Condensing)
28 models - 28 kW DHW
25.9 kW CH (Condensing)
33 models - 33 kW DHW
30.3 kW CH (Condensing)
3. It is designed for use on Natural Gas (G20).
4. The boiler is suitable for use only on fully pumped sealed
heating systems. Priority is given to domestic hot water.
5. The boiler is supplied with a filling loop and integral timer.
6. The boiler data badge gives details of the model, serial
number and Gas Council number and is situated on the inner
door panel. It is visible when the case front panel is removed
(Fig. 1).
Lower Door
Panel
7. The boiler model name and serial number are also shown
on the information label on the rear or the lower door panel.
This is for user reference.
8. The boiler is intended to be installed in residential /
commercial / light industrial E.M.C. environments on a
governed meter supply only.
Data Badge
Fig. 1
Information Label
9. The boiler must be installed with one of the purpose
designed flues such as the standard horizontal flue kit, part no.
5118489.
9. All systems must be thoroughly flushed and treated with
inhibitor (see section 6.2).
1.2
Contents of Pack
1. Boiler Unit
2. Wall Plate (inc. taps)
3. Set of Pipe (inc. nuts)
4. Template
5. Quick Fit Guide
6. Literature Pack
7. Filling Loop
7
© Baxi Heating UK Ltd 2008
2.0 General Layout
2.1
Layout
23
1
1.
Expansion Vessel
15
2.
Automatic Air Vent
DHW Plate Heat Exchanger
Circulation Pump
3.
22
4.
5.
Drain Off Point
14
6.
Pressure Relief Valve
Optional Integral Timer Position
Central Heating System Pressure Gauge
PCB
7.
13
8.
21
9.
16
20
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
Control Box
3-Way Valve Assembly
Condensate Trap
Flame Sensing Electrode
Spark Electrode
Primary Heat Exchanger
Fan Assembly
On/Off/Reset Selector Switch
Central Heating Temperature Control
Hot Water Temperature Control
Venturi
10
Air/Gas Collector
9
8
Combustion Box Cover & Burner
Igniter
7
Burner On Light
Central Heating Mode Light
Domestic Hot Water Mode Light
Display
12
Integral Timer
2
11
3
5
4
6
25
26
2
Reset
3
0
4
0
bar
24
18
19
28
17
8
27
8
© Baxi Heating UK Ltd 2008
3.0 Appliance Operation
1
Central Heating Circuit
3.1
Central Heating Mode (Fig. 2)
27
1. With a demand for heating, the pump circulates water
through the primary circuit.
2
2. Once main burner ignites the fan speed controls the gas
rate to maintain the heating temperature measured by the
temperature sensor.
3
5
4
7
26
20
6
3. When the flow temperature exceeds the setting
temperature, a 3 minute delay occurs before the burner
relights automatically (anti-cycling). The pump continues to
run during this period.
25
8
4. When the demand is satisfied the burner is extinguished
and the pump continues to run for a period of 3 minutes
(Pump Overrun).
24
18
22
9
11
23
3.2
Domestic Hot Water Mode (Fig. 3)
21
10
1. Priority is given to the domestic hot water supply. A
demand at a tap or shower will override any central heating
requirement.
17
16
15
14
13
12
19
2. The flow of water will operate the Hall Effect Sensor
which requests the 3 way valve to change position. This will
allow the pump to circulate the primary water through the
DHW plate heat exchanger.
Fig. 2
Key
1
2
3
4
5
6
7
8
9
Primary Heat Exchanger
Burner
Ignition Electrodes
Flame Sensing Electrode
Gas Valve
Pump
Automatic Air Vent
Plate Heat Exchanger
15 Domestic Hot Water Outlet
16 Heating Flow
17 Pressure Gauge
18 Water Pressure Sensor
19 Automatic By-Pass
20 Fan
21 Diverter Valve Assembly
22 Diverter Valve Motor
23 Domestic Hot Water Flow Temperature Sensor
24 Safety Thermostat
25 Central Heating Temperature Sensor
26 Expansion Vessel
3. The burner will light automatically and the temperature of
the domestic hot water is controlled by the temperature
sensor.
4. When the domestic hot water demand ceases the burner
will extinguish and the diverter valve will remain in the
domestic hot water mode, unless there is a demand for
central heating.
Flow Sensor with Filter & Regulator
10 Pressure Relief Valve
11 Boiler Drain Point
12 Heating Return
13 Cold Water Inlet On/Off Valve and Filter
14 Gas Inlet
27 Heat Exchanger Air Vent
IMPORTANT: When the selector switch is in the ‘0’
(Off) position the electrical supply to the boiler is isolated.
The boiler will not operate and the integral timer will
require resetting once the selector switch is set to either
Position (i) or Position (ii).
1
2
Domestic Hot Water Circuit
27
3.3
Frost Protection Mode
1. The frost protection mode is integral to the appliance and
functions only with the selector switch (see Section 2.1) in
the domestic hot water and central heating position. If the
system temperature falls below 5° C then the boiler will fire
on its minimum setting until a flow temperature of 30° C is
reached.
3
5
4
7
26
20
6
3.4
Pump Protection
25
24
8
1. With the selector switch (see Section 2.1) in either the
central heating or central heating and domestic hot water
position, the pump will automatically operate for 1 minute in
every 24 hours to prevent sticking.
18
22
9
11
23
21
10
17
16
15
14
13
12
19
Fig. 3
9
© Baxi Heating UK Ltd 2008
4.0 Technical Data
4.1
Gold Combi 24, 28 & 33 HE A
NO Class
Appliance Type
C13
C33
C53
5
Inlet Pressure (Natural Gas - G20)
mbar 20
x
Appliance Category
Heat Input CH (Net)
CAT I
Central Heating Primary Circuit
Pressures
2H
Injector (Natural Gas - G20)
Max
20.5
24.7
28.9
Min
7
bar
3
7.5mm (24&28 model) 12mm(33 model)
24 model
28 model
33 model
kW
kW
kW
Safety Discharge
Electrical Supply
230V~ 50H
z
Max Operating
Min Operating
Recommended Operating Range
2.5
0.5
1-2
9
(Appliance must be connected to an
earthed supply)
9.7
Heat Input CH (Gross)
Max
22.7
27.4
32.1
Min
7.8
DHW Circuit
Pressures
Max Operating
Min Operating
bar
Power Consumption
24 model
28 model
33 model
kW
kW
kW
155W (24 & 28 model) 160W (33 model)
8
0.15
10
Electrical Protection
IPX0D
10.8
Flow Rates
(24)
l/min
(28)
l/min
(33)
l/min
Heat Output CH (Non-Condensing)
External Fuse Rating
3A
Max
Min
6.8
8.7
9.4
DHW Flow Rate
o
Internal Fuse Rating
Condensate Drain
To accept 21.5mm ( /4 in) plastic waste pipe
F2L
@ 30 CRise
11.43
9.8
2
13.3
11.5
2
15.7
13.5
2
24 model
28 model
33 model
kW
kW
kW
20
24
28
DHW Flow Rate
3
o
@ 35 CRise
Min Working
DHW Flow Rate
Flue Terminal
Dimensions
Diameter
Projection
100mm
125mm
Heat Output CH (Condensing)
Max
Min
7.4
Pump
Available Head
Connections
Gas Supply
Central Heating Flow
Central Heating Return
Cold Water Mains Inlet
DHW Flow
copper tails
22mm
24 model
28 model
33 model
kW
kW
kW
21
See graph below
- (For Central Heating
-
25.9
30.3
9.5
-
-
-
-
-
22mm
22mm
15mm
15mm
Expansion Vessel
only. Integral with appliance)
10.2
bar
0.5
Heat Input DHW (Net)
Max
24.7
28.9
34
Min Pre-charge Pressure
24 model
28 model
33 model
kW
kW
kW
Pressure Relief Discharge
15mm
(24,28) (33)
litre
125
Max Capacity of
CH System
litre
155
Outercase Dimensions
Casing Height
Overall Height Inc Flue Elbow
Casing Width
- 780mm
- 965mm
- 450mm
- 345mm
Heat Input DHW (Gross) Max
Primary Water Content
of Boiler (unpressurised)
24 model
28 model
33 model
kW
kW
kW
27.4
32.1
37.7
2.5
2.8
Casing Depth
Clearances
Temperatures
C.H. Flow Temp (adjustable)
Above Casing
Below Casing
Front
Front
L.H. Side
R.H. Side
200 mm Min
200 mm Min
450 mm Min (For Servicing)
5 mm Min (In Operation)
5 mm Min
25°C to 80°C max ( 5°C)
Heat Output DHW
Max
24
24 model
28 model
33 model
kW
D.H.W. Flow Temp (adjustable)
kW
kW
28
35°C to 60°C max ( 5°C)
dependent upon flow rate
5 mm Min (In Operation)
33
Weights (kg)
Max Gas Rate (Natural Gas - G20)
(24) (28) (33)
Packaged Boiler Carton 48.6 49.2 51
Installation Lift Weight 43.6 44.2 46
(After 10 mins)
3
24 model
28 model
33 model
m /h
2.61
3.1
3
m /h
3
m /h
3.6
Pump - Available Head
5.5
5
4.5
SEDBUK Declaration
4
The efficiency is 91.1% (all models)
This value is used in the UK Government’s Standard
Assessment Procedure (SAP) for energy rating of
dwellings. The test data from which it has been
calculated has been certified by 0087.
3.5
3
2.5
2
1.5
1
0.5
0
0
200
400
600
800
1000
1200
Flow Rate (l/h)
10
© Baxi Heating UK Ltd 2008
5.0 Dimensions and Fixings
Dimensions
A 780mm
E
At least 1.5°
G
A
B 345mm
C 450mm
D 116mm Ø Min.
E 185mm
(207mm for 80/125mm
flue systems)
F 145mm
G 131mm
B
H 180mm
360° Orientation
J
270mm
H
J
D
C
Flue Ø 100mm
F
Tap Rail
32.5 mm
Condensate
Drain
65 mm
65 mm
65 mm
Cold Water
65 mm
65 mm
Heating
Return
(22mm)
Pressure Relief
Heating
Flow
(22mm)
Domestic Hot
Water Outlet
(15mm)
Gas
Inlet
(22mm)
Valve
(15mm)
Inlet
(15mm)
11
© Baxi Heating UK Ltd 2008
6.0 System Details
6.1
Information
1. The Potterton Gold Combi HE A Condensing Combination
Boiler is a ‘Water Byelaws Scheme - Approved Product’.
To comply with the Water Byelaws your attention is drawn to
the following installation requirements and notes (IRN).
a) IRN 001 -
See text of entry for installation
requirements and notes.
Byelaw 14.
b) IRN 302 -
2. Reference to the WRc publications, ‘Water fittings and
materials directory’ and ‘Water supply byelaws guide’ give full
details of byelaws and the IRNs.
6.2
Central Heating Circuit
1. The appliance is suitable for fully pumped SEALED SYSTEMS
ONLY.
Treatment of Water Circulating Systems
• All recirculatory water systems will be subject to
corrosion unless an appropriate water treatment is
applied. This means that the efficiency of the system will
deteriorate as corrosion sludge accumulates within the system,
risking damage to pump and valves, boiler noise and circulation
problems.
• When fitting new systems flux will be evident within the system,
which can lead to damage of system components.
• All systems must be thoroughly drained and flushed out. Using,
for example Betz-Dearborn Sentinel X300 or X400 or Fernox
Superfloc Universal Cleanser. They should be used following the
flushing agent manufacturer’s instructions.
• System additives - corrosion inhibitors and flushing
agents/descalers should comply to BS7593 requirements, e.g.
Betz-Dearborn Sentinel X100 and Fernox-Copal which should be
used following the inhibitor manufacturer’s instructions.
Failure to flush and add inhibitor to the system will
invalidate the appliance warranty.
• It is important to check the inhibitor concentration after
installation, system modification and at every service in
accordance with the manufacturer’s instructions. (Test kits are
available from inhibitor stockists.)
• For information or advice regarding any of the above contact
Technical Enquiries.
6.3
Bypass
1. The boiler is fitted with an automatic integral bypass.
6.4
System Control
1. A 24 hour electro - mechanical timer is supplied fitted to
the boiler.
2. Further external controls (e.g. room thermostat) should be
fitted to optimise the economical operation of the boiler.
12
© Baxi Heating UK Ltd 2008
6.0 System Details
6.5
System Filling and Pressurising (Fig. 4)
1. A filling point connection on the central heating return
pipework must be provided to facilitate initial filling and
pressurising and also any subsequent water loss
replacement/refilling.
Double
Check
Valve
Stop
Valve
Stop
Valve
A filling loop & instructions are provided with the boiler
2. The filling method adopted must be in accordance with all
relevant water supply regulations and use approved
equipment.
Temporary
Hose
DHW
Mains
Inlet
CH
Return
Fig. 4
3. Your attention is drawn to:
for GB: Guidance G24.2 and recommendation R24.2 of the
Water Regulations Guide.
for IE: the current edition of I.S. 813 “Domestic Gas
Installations”.
4. The sealed primary circuits may be filled or replenished by
means of a temporary connection between the circuit and a
supply pipe, provided a ‘Listed’ double check valve or some
other no less effective backflow prevention device is
permanently connected at the inlet to the circuit and the
temporary connection is removed after use.
6.6
Expansion Vessel (Central Heating only)
Filling Loop
1. The appliance expansion vessel is pre-charged to 0.5 bar.
Therefore, the minimum cold fill pressure is 0.5 bar. The
vessel is suitable for correct operation for system capacities up
to 125 litres (24, 28 models) 155 litres (33 models). For
greater system capacities an additional expansion vessel must
be fitted. For GB refer to BS 7074 Pt 1. For IE, the current
edition of I.S. 813 “Domestic Gas Installations”.
Fig. 5
6.7
Pressure Relief Valve (Fig. 6)
1. The pressure relief valve is set at 3 bar, therefore all
pipework, fittings, etc. should be suitable for pressures in
excess of 3 bar and temperature in excess of 100°C.
2. The pressure relief discharge pipe should be not less than
15mm dia, run continuously downward, and discharge outside
the building, preferably over a drain. It should be routed in
such a manner that no hazard occurs to occupants or causes
damage to wiring or electrical components. The end of the
pipe should terminate facing down and towards the wall.
3. The discharge must not be above a window, entrance or
other public access. Consideration must be given to the
possibility that boiling water/steam could discharge from the
pipe.
4. A remote relief valve kit is available to enable the boiler to
be installed in cellars or similar locations below outside
ground level (kit no. 5121379).
Fig. 6
Pressure Relief Valve
Discharge Pipe
13
© Baxi Heating UK Ltd 2008
6.0 System Details
6.8
Domestic Hot Water Circuit (Fig. 7)
1. All DHW circuits, connections, fittings, etc. should be fully
in accordance with relevant standards and water supply
regulations.
Other Tap
Outlets
2. Your attention is drawn to:
for GB: Guidance G17 to G24 and recommendation R17 to
R24 of the Water Regulations Guide.
for IE: the current edition of I.S. 813 “Domestic Gas
Installations”.
Boiler
Expansion
Vessel
3. A single check valve must be fitted as shown in Fig. 7 to
prevent backflow to the supply pipe and to ensure the
efficient operation of the expansion vessel which is required
to accommodate the thermal expansion of the water.
Check
Valve
Pressure Reducer
Valve
4. When the domestic water system includes any device
which prevents water expanding back towards the supply
(check valve, loose jumpered stopcock, water meter, water
treatment device) then an expansion vessel must be fitted
To Hot
Taps
Stop Tap
1
(eg. Zilmet 160ml, R /2 15bar).
5. If the hot water expansion is not provided for, then high
pressures can develop which may result in damage to fittings
and devices on the system.
Fig. 7
6. The boiler’s maximum working mains pressure is 8 bar,
therefore all pipework, connections, fittings, etc. should be
suitable for pressures in excess of 8 bar. A pressure reducing
valve must be fitted for pressures in excess of 8 bar. The
manufacturer of any outlet fittings, such as a shower valve,
may require a lower maximum pressure. The pressure
reduction must take account of all fittings connected to the
DHW system.
6.9
Showers
1. If a shower control is supplied from the appliance it
should be of the thermostatic or pressure balanced type.
Thermostatic type shower valves provide the best comfort
and guard against water at too high a temperature. Existing
controls may not be suitable - refer to the shower valve
manufacturer.
6.10
Hard Water Areas
1. If the area of the installation is recognised as a HARD
WATER AREA then a suitable device should be fitted to
treat the mains water supply to the boiler. Contact your
Water Distribution Company for advice on suitable devices.
14
© Baxi Heating UK Ltd 2008
7.0 Site Requirements
450mm
5mm Min
5mm Min
7.1
Location
1. The boiler may be fitted to any suitable wall with the flue
passing through an outside wall or roof and discharging to
atmosphere in a position permitting satisfactory removal of
combustion products and providing an adequate air supply.
The boiler should be fitted within the building unless
otherwise protected by a suitable enclosure i.e. garage or
outhouse. (The boiler may be fitted inside a cupboard-see
Section 7.3).
200mm Min
(300mm Min if
using 80/125mm
flueing system)
2. If the boiler is sited in an unheated enclosure then it is
recommended to leave the ON/OFF Selector Switch in the
domestic hot water and central heating position to give frost
protection.
780mm
3. If the boiler is fitted in a room containing a bath or shower
reference must be made to the relevant requirements.
In GB this is the current I.E.E. Wiring Regulations and Building
Regulations.
In IE reference should be made to the current edition of I.S.
813 “Domestic Gas Installations” and the current ETCI rules.
4. If the boiler is to be fitted into a building of timber frame
construction then reference must be made to the current
edition of Institute of Gas Engineers Publication IGE/UP/7
(Gas Installations in Timber Framed Housing).
200mm Min
Fig. 8
7.2
Clearances (Figs. 8 & 9)
1. A flat vertical area is required for the installation of the
boiler.
At least 1.5°
2. These dimensions include the necessary clearances around
the boiler for case removal, spanner access and air
movement. Additional clearances may be required for the
passage of pipes around local obstructions such as joists
running parallel to the front face of the boiler.
450mm Min
For Servicing
Purposes
5mm Min
In Operation
Fig. 9
15
© Baxi Heating UK Ltd 2008
7.0 Site Requirement
Gas Service Cock
7.3
Ventilation of Compartments
1. Where the appliance is installed in a cupboard or
compartment, no air vents are required.
2. BS 5440: Part 2 refers to room sealed appliances
installed in compartments. The appliance will run sufficiently
cool without ventilation.
7.4
Gas Supply
1. The gas installation should be in accordance with the
relevant standards. In GB this is BS 6891. In IE this is the
current edition of I.S. 813 “Domestic Gas Installations”.
Fig. 10
2. The connection to the appliance is a 22mm copper tail
located at the rear of the gas service cock (Fig. 10).
3. Ensure that the pipework from the meter to the
appliance is of adequate size. Do not use pipes of a smaller
diameter than the boiler gas connection (22mm).
Zone 2
Window
Recess
Zone 1
Zone 0
7.5
Electrical Supply
Zone 2
1. External wiring must be correctly earthed, polarised and
in accordance with relevant regulations/rules. In GB this is
the current I.E.E. Wiring Regulations. In IE reference should
be made to the current edition of ETCI rules.
Zone 3
0.6 m
2.4 m
Window
Recess
2. The mains supply is 230V ~ 50H fused at 3A.
z
Zone 2
NOTE: The method of connection to the electricity
supply must facilitate complete electrical isolation of the
appliance.
Zone 3
Connection may be via a fused double-pole isolator
with a contact separation of at least 3mm in all poles
and servicing the boiler and system controls only.
Fig. 11
In GB Only
7.6
Bath & Shower Rooms
Ceiling
Outside Zones
1. As the boiler is fitted with an integral timer when
installed in a room containing a bath or shower it cannot
be fitted in zones 1 or 2. (Figs. 11 & 12 shows zone
dimensions for a bathtub. For other examples refer to
Section 601 of the Current I.E.E. Wiring Regulations).
Reference must be made to the relevant requirements.
In GB this is the current I.E.E. Wiring Regulations and
Building Regulations.
Zone 3
Zone 2
Window
Recess
Zone 2
Outside
Zones
3.0 m
Zone 3
2.25 m
Zone 1
Zone 0
Zone 2
In IE reference should be made to the current edition of I.S.
813 “Domestic Gas Installations” and the current ETCI
rules.
0.6 m
2.4 m
Fig. 12
In GB Only
16
© Baxi Heating UK Ltd 2008
7.0 Site Requirements
7.7
Condensate Drain
Termination to an internal soil and
vent pipe
Boiler
FAILURE TO INSTALL THE CONDENSATE DISCHARGE
PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE
OPERATION OF THE BOILER
The condensate discharge pipe MUST NOT RISE at any point
along its length. There MUST be a fall of AT LEAST 2.5°
(50mm per metre) along the entire run.
3
1. The condensate outlet will accept 21.5mm ( /4in) plastic
overflow pipe which should generally discharge internally into
the household drainage system. If this is not possible, discharge
into an outside drain is acceptable.
450mm min
Fig. 13
2. Ensure the discharge of condensate complies with any
national or local regulations in force.
External termination via internal discharge
branch
BS 6798:2000 & Part H1 of the Building Regulations give
further guidance.
Boiler
e.g sink waste - downstream
3. The discharge pipe should be run in a proprietary drain pipe
material e.g. PVC, PVC-U, ABS, PVC-C or PP.
Pipe must terminate
above water level but
below surrounding
surface
4. Metal pipework is NOT suitable for use in condensate
discharge systems.
Sink
5. The pipe should be a minimum of 21.5mm diameter and
must be supported using suitably spaced clips to prevent
sagging.
6. It is advisable to keep the condensate pipe internal.
Fig. 14
7. External runs greater than 3 metres or runs in cold areas
should use 32mm waste pipe.
8. If the boiler is fitted in an unheated location the entire
condensate discharge pipe should be treated as an external
run.
Termination to a drain or gully
Boiler
Pipe must terminate above
water level but below
surrounding surface
9. In all cases discharge pipe must be installed to aid disposal
of the condensate. To reduce the risk of condensate being
trapped, as few bends and fittings as possible should be used.
10. When discharging condensate into a soil stack or waste
pipe the effects of existing plumbing must be considered. If soil
pipes or waste pipes are subjected to internal pressure
fluctuations when WC's are flushed or sinks emptied then
back-pressure may force water out of the boiler trap and
cause appliance lockout.
Fig. 15
Termination to a purpose made soak-
away
Examples are shown of the following methods of termination:-
i) to an internal soil & vent pipe - Fig. 13
Boiler
ii) via an internal discharge branch (e.g. sink waste) - Fig. 14
iii) to a drain or gully - Fig. 15
500mm min
iv) to a purpose made soakaway - Fig. 16
Holes in the soak-away must
face away from the building
Fig. 16
17
© Baxi Heating UK Ltd 2008
Terminal Position with Minimum Distance (Fig. 18)
(mm)
7.0 Site Requirements
a
a
A
Directly below an opening, air brick, opening
windows, etc.
Above an opening, air brick, opening window etc.
Horizontally to an opening, air brick, opening window etc.
Below gutters, soil pipes or drain pipes.
Below eaves.
Below balconies or car port roof.
From a vertical drain pipe or soil pipe.
From an internal or external corner.
300
300
300
25
25
25
25
25
300
600
1200
600
a
B
7.8
Flue
C
D
E
F
G
H
I
NOTE: Due to the nature of the boiler a plume of water
vapour will be discharged from the flue. This should be
taken into account when siting the flue terminal.
Above ground, roof or balcony level.
1. The following guidelines indicate the general requirements
for siting balanced flue terminals. For GB recommendations
are given in BS 5440 Pt 1. For IE recommendations are given
in the current edition of I.S. 813 “Domestic Gas
Installations”.
J
K
From a surface or boundary line facing a terminal.
From a terminal facing a terminal (Horizontal flue).
From a terminal facing a terminal (Vertical flue).
From an opening in carport (e.g. door, window)
into the dwelling.
Vertically from a terminal on the same wall.
Horizontally from a terminal on the same wall.
From adjacent wall to flue (vertical only).
From an adjacent opening window (vertical only).
Adjacent to windows or openings on pitched and flat roofs
Below windows or openings on pitched roofs
L
1200
1500
300
300
1000
600
M
N
R
2. If the terminal discharges onto a pathway or passageway,
check that combustion products will not cause a nuisance
and that the terminal will not obstruct the passageway.
S
T
U
2000
3. If a terminal is less than 2 metres above a balcony, above
ground or above a flat roof to which people have access,
then a suitable terminal guard must be provided.
a
In addition, the terminal should be no nearer than 150 mm to an
opening in the building fabric formed for the purpose of accommodating
a built-in element such as a window frame. See BS 5440 Pt. 1.
IMPORTANT:
NOTE: The distance from a fanned draught appliance terminal
installed parallel to a boundary may not be less than 300mm in
accordance with the diagram below
• Only ONE 25mm clearance is allowed per installation.
• Under car ports we recommend the use of the plume
displacement kit.
• The terminal position must ensure the safe and
nuisance - free dispersal of combustion products.
300 min
Terminal
Assembly
*
Plume
Displacement Kit
IMPORTANT: If fitting a Plume
Displacement Flue Kit, the air inlet
must be a minimum of 100mm from
any opening windows or doors (see
Section 9.0).
TopView Rear Flue
Fig. 17
Property Boundary Line
Air Inlet
T
J,K
U
Opening Window
or Door
100mm
MIN.
Fig. 18a
N
R
I
D
E
A
M
I
C
I
I
S
F
B
J,K
F
L
A
A
I
G
H
H
Likely flue positions requiring
a flue terminal guard
Fig. 18
18
© Baxi Heating UK Ltd 2008
8.0 Flue Options
8.1
Horizontal Flue Systems
1. The standard flue is suitable only for horizontal termination
applications.
2. All fittings should be fully engaged. The approximate
engagement is 40mm. Apply soap solution to the seal on
each fitting to aid assembly.
Y
X
3. Maximum permissible equivalent flue lengths are:-
(60/100)
(80/125)
Horizontal Concentric 10 metres
20 metres
4. Any additional “in line” bends in the flue system must be
taken into consideration.
Their equivalent lengths are:-
Concentric Pipes:
135° bend
93° bend
0.5 metres
1.0 metres
Horizontal
Flues
Twin Flue Pipe
135° bend
91.5° bend
0.25 metres
0.50 metres
4. The elbow connected to the boiler adaptor is not included
in any equivalent length calculations.
Plume Displacement Kit 60 /100 Ø
5. The illustrations opposite show examples of permissible
flue systems.
1M Extensions, 45° & 93° bends are
also available - see Section 9.0
NOTE: Flue length is measured from point X to Y as
shown.
NOTE: Horizontal flue pipes should always be installed with a fall of at least 1.5°
from the terminal to allow condensate to run back to the boiler.
This bend is equivalent to
1 metre
C
A
Y
B
This bend is equivalent to
1 metre
X
Total equivalent length =
A+B+C+2x90°Bends
19
© Baxi Heating UK Ltd 2008
8.0 Flue Options
Vertical
Flues
8.2
Twin & Vertical Flue Systems
(Twin Pipe)
1. Maximum permissible equivalent flue lengths are:-
(60/100)
(80/125)
Vertical Concentric
Vertical Twin Pipe
10 metres
15 metres
20 metres
Y
2. Any additional “in line” bends in the flue system must be
taken into consideration.
X
Their equivalent lengths are:-
Concentric Pipes:
135° bend
93° bend
0.5 metres
1.0 metres
Twin Flue Pipe
135° bend
91.5° bend
0.25 metres
0.50 metres
Vertical
Flues
The elbow supplied with the standard horizontal telescopic
flue kit is not included in any equivalent length calculations
NOTE: Flue length is measured from point X to Y as
shown.
Y
X
Total Equivalent Length =
A+B+C+1x90°Bend
Roof
Terminal
All vertical and angled runs must be included,
measured from the boiler adaptor (point X) to the
joint with the flue terminal (point Y). One 91.5°
bend or two 135° bends can be included without
reduction of the flue length.
If further elbows are required the flue length must
be reduced by the following amounts:-
The total equivalent length for this example is
= 6.5 metres.
Y
1 metre for each 91.5° bend
0.5 metre for each 135° bend
AIR DUCT
N of
fittings/pipes
C
o
Equivalent
Sub total
Length Value
B
1m extension
135°bend
5
2
2
5.0m
0.5m
1.0m
1m
0.25m
0.5m
91.5°bend
This bend is equivalent to
1 metre
Equivalent Length Air Duct = 6.5m
FLUE DUCT
N of
fittings/pipes
A
X
o
Equivalent
Sub total
Length Value
1m
1m extension
135°bend
5
2
2
5.0m
0.5m
1.0m
0.25m
0.5m
91.5°bend
Equivalent Length Flue Duct = 6.5m
20
© Baxi Heating UK Ltd 2008
8.0 Flue Options
8.3
Flue Accessories
A4
Key Accessory
FLUE GROUP A
Concentric Flue System 100mm diameter
A3 Telescopic Internal Flue Kit 315-500mm5119654
A2 Telescopic Flue (inc. elbow) 315-500mm5118069
Size
Code No
A2
A
A
B
Horizontal Flue Terminal (inc. elbow)
5118489
Flue Extension
1000mm 5111074
C
D
D
U
R
P
Flue Bend
Flue Bend
Flue Bend (pair)
Pipe Support (painted)
Vertical Flue Adaptor
Wall Liner
93°
135°
135°
5111075
5111076
5111085
100Ømm 5111080
5111070
5111067
S
Flue Terminal Deflector
5111068
B
A3
E
FLUE GROUP N
P
Twin Flue System 80mm diameter
E
F
Flue Extension (pair)
Flue Bend (pair)
Flue Bend (2 pair)
Vertical Flue Boiler Adaptor Kit
Vertical Flue Adaptor
Pipe Support (pair)
Flue Termination Kit
(horizontal termination)
1000mm 5111087
K,K1
90°
135°
5111072
5111086
5111079
5111084
5111081
G
J
H
W
Y
80mm
80mm
5120172
R
D
FLUE GROUP G
C
Concentric Flue System 80/125mm diameter
A4 Horizontal Flue Kit
5118580
B
Straight Extension Kit
Bend Kit (pair)
Bend
1000mm 5118584
D
C
U
135°
5118597
5118588
5118610
91.5°
Pipe support
125mm
FLUE GROUP A, N, G
Vertical Flue Kits
G
F
K
K1
L
M
N
Vertical Flue Terminal (use with 5111070)
Vertical Flue Terminal
5111078
5118576
5122151
246143
M
H
Pitched Roof Flashing
Roof cover plate
Flat roof flashing
25°/50°
246144
U,W
Y
L
N
S
J
21
© Baxi Heating UK Ltd 2008
8.0 Flue Options
For Twin Flue Systems fit the adaptors as follows:-
8.4
Flue Duct Adaptor
Flue Duct Adaptor
1. Engage the flue duct adaptor on the boiler adaptor,
making sure that it is pushed down as far as possible.
Blanking Plate
Boiler Adaptor
8.5
Air duct adaptor
1. Undo the screws securing the blanking plate to the boiler
top panel. Discard the plate.
2. There are three restrictor plates supplied in the kit. One
marked ‘23’ and one marked ‘27’, these can be discarded
The third restrictor MUST be positioned as shown in the
diagrams below.
3. Take one of the gaskets supplied in the kit and place on
the boiler top panel.
4. Align the appropriate restrictor as shown. Position the
second gasket over the restrictor.
5. Using the screws previously removed secure the inlet
adaptor to the top panel.
6. Continue to fit the twin flue system.
Air Duct Adaptor
Position of Restrictor
Gasket
Restrictor
Gasket
24 kW models
28/33 kW models
22
© Baxi Heating UK Ltd 2008
8.0 Flue Options
8.6
For Roof Terminals
1. In the case of a pitched roof 25 - 50 degrees, position the lead
tile to replace/flash over existing roof tiling. Make an aperture in
the roof suitable for the lower tube of the roof terminal and
ensure the integrity of the roof cover is maintained. The
Approx
1425mm
adjustable plastic collar can either be positioned on the lead tile
or the lower tube of the roof terminal prior to the final
positioning of the vertical flue through the tile. Check the collar is
correctly located to suit required roof pitch (either 25° to 38° or
37° to 50°). From inside the roof adjust the flue to a vertical
position and secure to the roof structure with the clamp supplied.
2. For flat roof installations the aluminium flashing must be
incorporated into the roof covering and the appropriate aperture
made in the roof decking. The vertical flue is lowered onto the
flashing making sure the collar of the flue locates securely with the
flashing. (A mastic seal may be necessary). From inside the roof,
adjust the flue to a vertical position and secure to the roof
structure with the clamp supplied.
Cut the same
amount off the
Air Duct &
Air Duct
Flue Duct
Flue Duct
IMPORTANT: If the boiler is not fitted immediately after the flue
system, temporary precautions must be taken to prevent rain
entry into the room of installation. Any precautionary measures
must be removed prior to commissioning the boiler.
Push Fit Adaptor
8.7
Flue Dimensions
The standard horizontal telescopic flue kit allows for lengths
between 100mm and 685mm from elbow to terminal (Fig. 19).
The maximum permissible equivalent flue length is:
10 metres (60/100 system)
20 metres (80/125 system)
Flue Deflector
8.8
Flue Trim
Fig. 19
1. The rubber flue trim supplied may be fitted to either the
outside wall or on the inner wall of installation.
8.9
Terminal Guard (Fig. 21)
Fig. 20
1. When codes of practice dictate the use of terminal guards, they
can be obtained from most Plumbers’ and Builders’ Merchants.
2. There must be a clearance of at least 50mm between any part
of the terminal and the guard.
3. When ordering a terminal guard, quote the appliance name
and model number.
4. The flue terminal guard should be positioned centrally over the
terminal and fixed as illustrated.
8.10
Flue Deflector (Fig. 20)
Fig. 21
1. If required, push the flue deflector over the terminal end and
rotate to the optimum angle for deflecting plume. Secure the
deflector to the terminal with screws provided.
23
© Baxi Heating UK Ltd 2008
93° Elbow/Plume
Outlet Assembly
9.0 Plume Displacement
60Ø Support
Bracket
9.1
Plume Displacement Kit (Fig. 23)
O Ring
Kit No 5118638
Content of kit
0.9 metres
1
1
1
2
1
1
3
1
1
0.9m 60/100 Concentric Flue
1m 60 Dia Exhaust Flue Pipe
Adaptor
60Ø Exhaust
Flue Pipe
60 Dia Support Brackets
93° Elbow/Plume Outlet Assembly
Flexible Flue Trim
60Ø Support
Bracket
“O” Rings
‘Jubilee Clip
O Ring
Adaptor
O Ring
Fig. 22
Boiler Elbow
Flexible Flue
Trim
1. This kit is recommended for installations where the
condensate plume emitted from the flue may cause a nuisance
or affect the surroundings.
‘Jubilee’ Clip
2. The terminal must be positioned outside the building with
the air inlet facing downward and outlet connection upwards.
3. The plume outlet must always be at least 45° to the wall,
with the ‘peak’ uppermost to prevent rain entry (Figs. 24 &
25), and be at least 2 metres above ground level. It must be
secured as shown in Fig. 19. The plume outlet must also be at
least 500mm from the air inlet in any direction (Fig. 25).
60/100Ø
Concentric Flue
Fig. 23
Outlet must be at
least 45° from
wall face
NOTE: The outlet must be positioned so that any
condensate plume is directed away from adjacent surfaces.
There must be a constant fall along the entire length of the
flue system from the outlet back to the boiler.
45°
‘Peak’ Uppermost
45°
4. It is possible to reduce or increase (with the addition of
extensions) the length of either or both the 60/100 concentric
and 60Ø exhaust.
5. Standard concentric flue extension kits may be added
between the boiler elbow and the terminal assembly.
6. The minimum length of the concentric flue is 100mm when
measured from the edge of the flue elbow.
500mm Min.
IMPORTANT: The maximum equivalent length of
concentric flue is:- 8 metres
Additional bends may be fitted in the concentric flue, but
the equivalent length must be reduced by 1 metre (93°
bend) or 0.5 metres (45° bend).
Fig. 24
Air Inlet at Bottom
7. 60Ø 1 metre extensions (including support bracket), and
additional 93° & 45° elbows are available. Any additional 93°
& 45° elbows must be accounted for when calculating flue
lengths.
Fig. 25
NOTE: Permitted positions of the plume outlet relative to
doors, windows etc. are the same as for conventional
concentric flues as detailed in the main Installation &
Servicing Instructions and BS5440 Pt. 1. It is NOT
necessary to fit a terminal guard over the air inlet or the
plume outlet.
24
© Baxi Heating UK Ltd 2008
9.0 Plume Displacement
16
14
12
10
16
14
12
10
9.2
Determining Permissible Lengths
In the graph the solid line diagonal represents the
relationship between the concentric flue assembly (and any
extensions) and the 60Ø exhaust (and any extensions or
additional bends).
8
6
4
2
0
8
6
4
2
0
Example 1 - Not Permissible
If, for instance, a concentric length of 5 metres was required
and the 60Ø exhaust needed to be 6 metres the graph
shows that this combination would NOT be permissible as
the intersection point would be above the solid diagonal line.
0
2
3
4
5
6
7
8
9
0
2
3
4
5
6
7
8
9
1
1
Concentric 60/100 Flue (metres)Y
Concentric 60/100 Flue (metres)Y
Example 1
Example 2
Flue Lengths - Not Permissible
Flue Lengths - OK
Example 2 - Flue Lengths OK
16
14
12
10
Where both lengths have been determined they can be
applied to the graph to check that the installation is
permissible. For example, if it was known that 2 metres of
concentric flue and 4 metres of 60Ø exhaust were required,
the values could be applied to the graph as shown in
Example 2.. As the point of intersection of the dotted lines is
below the solid diagonal line, the combination of lengths is
shown to be acceptable.
8
6
4
2
0
Example 3 - Flue Lengths OK
In the example shown in Fig. 4 assume that the concentric
part of the flue needs to be 2.3 metres long. Find the
position of ‘2.3’ on the horizontal axis of the graph and then
project upwards to the solid diagonal line. This is represented
by the vertical thick dotted line. Where this dotted line
intersects with the solid diagonal line on the graph, project
across to the vertical axis. As can be seen this corresponds
with 6 metres. Therefore, the total equivalent length of the
60Ø exhaust can be up to 6 metres. Any bend equivalencies
must be accounted for i.e. 93° bends are equal to 1 metre,
each 45° bend to 0.5 metres.
0
2
3
4
5
6
7
8
9
1
Concentric 60/100 Flue (metres)Y
Example 3
Flue Lengths - OK
Support
Bracket
60Ø Exhaust
X
45° Elbow
Y
Flue Length - Worked Example
Potterton Gold Combi 33HE A
93° Elbow
In Fig. 27 opposite an additional 93° bend and pair of 45°
elbows have been included in the 60Ø exhaust.
Also 3 straight extension pieces have been used.
1 metre Extension
Concentric 60/100 Flue
To calculate total length:-
1 metre supplied in kit
Length of 60Ø supplied in kit =
3 x 1 metre Extensions =
1 x 93° Elbow =
1 metre
Fig. 26
3 metres
1 metre
2 x 45° Elbow =
1 metre (0.5 metres each)
Concentric Flue
Total 60Ø =
6 metres
After consulting the table in Example 3 it can be determined
that the concentric flue could be up to approximately 2.3
metres long.
Additional Accessories
A - 93° Elbow
B - 45° Elbow (Pair)
5121369
5121370
Fig. 27
C - 1 metre 60Ø Extension 5121368
25
© Baxi Heating UK Ltd 2008
9.0 Plume Displacement
9.3
General Fitting Notes
1. Cut a hole in the external wall which the concentric flue
assembly will pass through. The hole should allow the flue
to fall back to the boiler at an angle of at least 1.5°.
2. When completed the terminal must be at least 2 metres
above ground level (Fig. 19).
3. Measure and cut to size the concentric assembly and any
extensions that are being used.
Min. 2 metres
4. Insert the concentric assembly through the hole from
outside the building.
5. If required, the flexible flue trim should be fitted prior to
this as it cannot be fitted after. Use the large ‘Jubilee’ clip to
secure the trim to the flue (See Fig. 20, trim shown
dotted), with the screw part of the clip at the bottom.
6. Connect any extensions or elbows that are being used
to the concentric assembly. Engage the extension, elbow
or concentric assembly in the boiler flue elbow. Fit the
boiler flue elbow to the boiler adaptor.
Fig. 28
Flue Trim
7. Ensure that the concentric assembly and any extensions
fall back to the boiler at an angle of at least 1.5° and that
the external air inlet is to the bottom.
8. Use suitable brackets to support the concentric
assembly and any extensions, and make good inside and
outside.
Spigot
9. The 60Ø exhaust can now be fitted. Slide the adaptor
over the plain end of the 60Ø exhaust (Fig. 22) and engage
the exhaust in the terminal. Slide the adaptor down over
the spigot. Mark and drill the adaptor, using a 2mm bit, as
shown in Fig. 21. Secure the adaptor to the spigot using
one of the screws supplied.
Position of ‘Jubilee’ Clip
screw
Fig. 29
50mm
10. If it is necessary to shorten the 60Ø exhaust or any of
the extensions, the excess material must be cut from the
plain end of the pipe.
Adaptor
11. Determine the position of the 60Ø exhaust and mark
on the wall a suitable position for the support bracket. If
extensions are being used, a support bracket is supplied in
each kit.
Fig. 31
12. Drill the wall, and fit the bracket(s) using the plug and
screw provided.
30mm
Fig. 30
13. Mark and drill the 60Ø exhaust, using a 2mm bit, as
shown in Fig. 23. Complete the installation of the 60Ø
exhaust, securing in the brackets.
30mm
14. Fit the 93° elbow/plume outlet and secure with the
two remaining screws supplied. Ensure the plume outlet is
at least 45° to the wall and that the ‘peak’ is uppermost
(Fig. 24).
Fig. 32
26
© Baxi Heating UK Ltd 2008
Fig. 33
9.0 Plume Displacement
Plume Outlet
Elbow
9.3
General Fitting Notes (cont.)
15. For aesthetic purposes it is permissible to route the
60Ø exhaust in an enclosed box, but the air inlet and
plume outlet MUST remain in free air.
16. It is also possible to separate the plume outlet from the
93° elbow to allow the flue to be installed as shown in
Fig. 34.
17. To do this, first slacken the two screws retaining the
plume outlet to the elbow, and remove the outlet (Fig. 35).
The elbow can now be used to connect the vertical to
horizontal 60Ø exhaust (Fig. 34). Retighten the screws in
the elbow.
Fig. 34
18. The outlet can now be fitted into the female end of an
60Ø extension piece. It must be secured using two of the
screws supplied in the bag with the ‘Jubilee’ clip.
19. Mark the female end of the extension at 30mm as
shown in two positions, directly opposite each other
(Fig. 36).
Fig. 35
30mm
20. Using a suitable bit (e.g. 2mm), drill through the
extension and outlet. Secure using two of the screws
supplied.
21. The remaining screw must be used to secure the
adaptor to the concentric terminal.
Fig. 36
22. When the plume outlet is positioned under a balcony
or other projection (Fig. 37) it must protrude at least
200mm (it is not necessary to extend it further than this).
200mm Min.
23. When under balconies or projections it is permissible to
rotate the concentric flue length up to 70°, clockwise or
anti-clockwise (Fig. 38), if there is insufficient space to
connect vertically.
24.This will allow the connection of the exhaust to the
outlet spigot.
25. All other minimum & maximum dimensions must be
adhered to, and the air inlet positioned such that it will not
be subject to rain entry.
Fig. 37
70°
Concentric Flue Length
(shown end-on)
Outlet Spigot
Fig. 38
27
© Baxi Heating UK Ltd 2008
10.0 Installation
10.1
Unpacking & Initial Preparation
The gas supply, gas type and pressure must be checked for
suitability before connection (see Section 7.4).
NOTE: a small amount of water may drain from the
boiler in the upright position.
1. Remove staples, open flaps and remove the cardboard
sheet. Remove the polystyrene side pieces and literature.
Two people can then lift out the boiler (Figs. 39 & 40).
Fig. 39
2. After considering the site requirements
(see Section 7.0) position the fixing template on the wall
ensuring it is level both horizontally and vertically.
3. Mark the position of the two most suitable fixing slots for
the wall plate and boiler lower fixing holes. It is preferable to
use the vertical fixing slots.
Fig. 40
4. Mark the position of the centre of the flue hole (rear
exit). For side flue exit, mark as shown (Fig. 41).
5. If required, mark the position of the gas and water pipes.
Remove the template.
145mm
6. Cut the hole for the flue (minimum diameter 116mm).
7. Drill the wall as previously marked to accept the wall
plugs supplied. Secure the wall plate using the fixing screws.
8. Using a spirit level ensure that the plate is level before
finally tightening the screws.
For Side Flue Exit
Fig. 41
9. Connect the gas and water pipes to the valves on the
wall plate using the copper tails supplied. Ensure that the
sealing washers are fitted between the connections.
Flushing Tube
10. Fit the filling loop as described in the instructions
supplied with it.
Wall Plate
10.2
Flushing
1. Connect a tube to the central heating flow or return pipe
(Fig. 42 & 43).
Central Heating Return
2. Flush thoroughly (see System Details, Section 6.2).
Fig. 42
Fig. 43
28
© Baxi Heating UK Ltd 2008
10.0 Installation
10.3
Fitting the Filling Loop
1. The filling loop supplied with the boiler can be
connected to the taps on the wall plate at this point.
2. The filling loop is to be connected between the mains
cold water inlet and central heating return isolation taps.
Cold Inlet
3. The loop and valves must be connected as shown in
the diagram (Fig. 44a).
4. Note the orientation of the flow direction arrows on
the stop valve and double check/stop valves.
Double Check Valve
& Stop Valve
Fig. 44a
5. Remove the end caps from the isolation taps and put
to one side. Connect the valves to the taps. Ensure that
the fibre washers supplied are used on these joints.
Temporary Filling
Loop
CH Return
Stop Valve
6. Connect the temporary loop, ensuring that the seals
are fitted.
To fill, test and flush if required (Fig. 44c)
7. Take the blanking plugs from the kit, and using washers
supplied with the boiler, connect them to the central
heating flow and return taps, and the cold inlet tap. The
system can now be filled by opening the cold inlet supply
and stop valves.
Fitting the Valves
to the Taps
8. If desired a suitable gauge can be connected to one of
the taps so that the system may be accurately
pressurised.
Temporary Loop and
Flanged Washers
9. All joints, fittings and system components can now be
examined for soundness at operating pressure.
10. The system can be flushed by turning off the central
heating tap and connecting a suitable fitting to the loose
nut. From the fitting a hose pipe can be run to the
nearest convenient drain. When the tap is reopened the
system will flush.
Fig. 44b
11. Remove the blanking plug(s), pressure gauge and
flushing equipment from the appliance if used.
12. Continue with the installation and commissioning.
13. The filling loop must be disconnected and completely
removed after the system is pressurised.
Pressure
Gauge
14. Hand tighten the two previously removed end caps
to the stop valve and double check valve.
Blanking
Plugs
Hose and
Fitting
Fig. 44c
29
© Baxi Heating UK Ltd 2008
10.0 Installation
Wall Plate
10.4
Fitting The Boiler
1. Lift the boiler using the Lifting Points as shown by the
shaded areas (Fig. 45). The boiler should be lifted by TWO
PEOPLE. Engage the slots at the top rear of the boiler on the
wall plate (Fig. 46) (see Safe Manual Handling page 5).
2. Ease the boiler forwards and remove the sealing caps from
the boiler connections.
NOTE: A small amount of water may drain from the boiler
once the caps are removed.
3. Insert the sealing washers between the valves and pipes on
the wall plate and the boiler connections. THE RUBBER
WASHERS MUST BE USED ON THE GAS CONNECTION.
Fig. 46
4. Tighten all the connections.
Fig. 45
Suggested Lifting Points
shown as shaded area
10.5
Fitting the Pressure Relief Discharge Pipe
(Fig. 47)
1. Remove the discharge pipe from the kit.
2. Determine the routing of the discharge pipe in the vicinity of
the boiler. Make up as much of the pipework as is practical,
including the discharge pipe supplied.
3. The pipework must be at least 15mm diameter and run
continuously downwards to a discharge point outside the
building. See section 6.7 for further details.
4. Utilising one of the sealing washers, connect the discharge
pipe to the adaptor and tighten the nut.
5. Complete the discharge pipework and route it to the
outside discharge point.
Pressure Relief Valve
IMPORTANT: Make all soldered joints before connecting
to the pressure relief valve.
10.6
Condensate Drain (see section 7.7)
Fig. 47
1. Connect the condensate drain to the trap outlet pipe.
Ensure the discharge of condensate complies with any
national or local regulations in force (see British Gas
“Guidance Notes for the Installation of Domestic Gas
Condensing Boilers”.
Discharge Pipe
3
2. The connection will accept 21.5mm ( /4in) plastic overflow
pipe which should generally discharge internally into the
household drainage system. If this is not possible, discharge into
an outside drain is acceptable.
30
© Baxi Heating UK Ltd 2008
10.0 Installation
10.7
Fitting The Flue
HORIZONTAL FLUE
1. The standard flue is suitable for lengths between 100mm
minimum and 685mm maximum, as measured from the
edge of the flue elbow outlet to the joint between the
terminal and air duct (Fig. 48).
Fig. 48
2. Locate the flue elbow on the adaptor at the top of the
boiler. Set the elbow to the required orientation (Fig. 50).
The elbow is fully engaged when there is a distance of
20mm from the adaptor to the indicator line (Fig. 49).
20mm
NOTE: The flue elbow is angled at 93 degrees to
ensure a fall back to the boiler.
Wall Thickness
Indicator line
3. Measure the distance from the outside wall face to the
elbow. This dimension will be known as ‘X’ (Fig. 51).
Fig. 49
Flue Elbow
4. To dimension ‘X’ add 50mm. This dimension to be
known as ‘Y’.
(X)
Apply Lubricant for
ease of assembly.
IMPORTANT: Check all dimensions before cutting.
Ensure Elbow is fully
engaged into Boiler
Adaptor
Adaptor
5. Mark dimension ‘Y’ on the flue as shown (Fig. 52).
Carefully cut the waste material from the flue, ensuring that
the ducts are square and free from burrs.
Fig. 50
Wall Thickness
(X)
Fig. 51
Waste
Y
Flue
Fig. 52
31
© Baxi Heating UK Ltd 2008
10.0 Installation
Inner Flue Support Bracket
10.7
Fitting the Flue (Cont)
6. The inner flue duct support bracket may be in the waste
portion of the flue. In this case retrieve the bracket before
discarding the waste.
7. Take the inner flue support bracket (if not already fitted)
and engage it over the flue duct. This will centralise the flue
and air ducts, and ease assembly (Fig. 53).
Fig. 53
8. Insert the flue through the hole in the wall. Fit the elbow
to the boiler adaptor, ensuring that it is pushed fully in.
Apply Lubricant for
ease of assembly.
Ensure Flue is fully
engaged into Flue
Elbow
9. Draw the flue back through the wall and engage it in the
elbow. It may be necessary to use soap solution or similar
to ease assembly of the elbow adaptor and flue (Fig. 54).
10. Ensure that the terminal is positioned with the slots to
the bottom (Fig. 55).
IMPORTANT: It is essential that the flue terminal is fitted
as shown to ensure correct boiler operation and prevent
water entering the flue.
11. Make good between the wall and air duct outside the
building.
12. Fit the flue trim if required, and if necessary fit a terminal
guard (see Section 8.8 & 8.9).
Slots at bottom
Fig. 55
CONCENTRIC VERTICAL FLUE
13. Once the length of the vertical concentric extension has
been determined mark and carefully cut off the excess
material. The cut end MUST be square and free of burrs to
ensure correct insertion into the boiler adaptor.
Fig. 54
25mm
14. Measure 25mm from the end of the flue extension and
apply a length of tape around the outer duct (Fig. 56).
15. Engage the extension into the adaptor up to this
position (Fig. 57). Once the installation of the flue is
complete and all support brackets are securely in place
remove the tape.
Extension
Fig. 56
Tape
Cut End
Adaptor
Apply Lubricant for
ease of assembly.
Ensure Extension is
fully engaged into
Boiler Adaptor
Fig. 57
32
© Baxi Heating UK Ltd 2008
10.0 Installation
10.8
Making The Electrical Connections
The boiler is fitted with a 1.3m length of 3 core cable. This
can be connected to the fused 3A 230V 50HZ supply.
NOTE: Both the Live and Neutral connections are fused.
To connect an external control proceed as follows:-
Terminal Block Cover
1. Slacken the facia panel securing screws and lift the
outercase panel so that its securing tabs are clear of the
facia. Remove the panel.
2. Completely undo the screws securing the facia panel and
hinge it down (Fig. 58).
3. Undo the terminal block cover securing screw and
remove the cover (Fig. 58).
Fig. 58
4. Slacken the unused cable clamp on the LH side of the
boiler chassis (Fig. 59). Insert the external control wiring
through the clamp and route it to the terminal block.
Fig. 59
Facia Panel
Cable Clamp
5. Refer to the instructions supplied with the control.
IMPORTANT: The room thermostat MUST be suitable
Fused Spur
for 230V switching.
L
N
Room ‘Stat
N
NOTE: An external frost thermostat cannot be used
with the optional integral timer.
6. Remove the link between terminals 1 & 2. The 230V
supply at terminal 2 must be connected to the thermostat.
The switched output from the thermostat must be
connected to terminal 1 (Figs. 60 & 61). If the room
thermostat being used incorporates an anticipator it MUST
be wired as shown in Figs. 60 & 61.
bk
bk
1
2
230V
g/y
b
N
L
7. Ensure that the external control input cable(s) have
sufficient slack to allow the control box to drop down.
Tighten the cable clamp on the boiler chassis.
br
Fig. 60
8. Replace the terminal block cover, routing the external
control input cable(s) through the second cut-out.
Frost Thermostat
Fused Spur
L
N
Room ‘Stat
10.9
Preliminary Electrical Checks
230V
N
1. Prior to commissioning the boiler preliminary electrical
system checks should be carried out.
bk
bk
1
2
230V
2. These should be performed using a suitable meter, and
include checks for Earth Continuity,
External Clock
g/y
Resistance to Earth, Short Circuit and Polarity.
b
N
L
br
Fig. 61
NOTE: The 230V switched signal for external controls
(Frost Stat - Room Stat - Timer) must always be taken
from terminal 2 at the boiler. Live, Neutral and Earth to
power these controls must be taken from the Fused Spur.
33
© Baxi Heating UK Ltd 2008
Heat Exchanger
Automatic Air Vent
11.0 Commissioning
Fig. 62
11.1
Commissioning the Boiler
1. Reference should be made to BS 5449 Section 5 when
commissioning the boiler.
2. Open the mains water supply to the boiler.
IMPORTANT: The heat exchanger air vent on top of the
boiler (Fig. 62) MUST be opened before filling the
primary system.
Screw
3. Open all hot water taps to purge the DHW system.
Pump
Automatic Air
Vent
4. Ensure that the filling loop is connected and open, then
open the heating flow and return valves on the boiler.
5. Open the screw on the automatic air vent on the pump
body (Fig. 63).
6. The system must be flushed in accordance with BS 7593
(see Section 6.2) and the flushing agent manufacturers
instructions.
7. Pressurise the system to 1.5 bar (Fig. 64) then close and
disconnect the filling loop.
2
Pump
Fig. 63
1
3
8. Turn the gas supply on and purge according to in GB BS
6891 and in IE I.S. 813 “Domestic Gas Installations”.
0
4
bar
Selector Switch
Display
Pressure Gauge
Fig. 64
9. Test for gas soundness.
10. Hinge the facia panel upwards and refit the case front
panel. Tighten the securing screws.
2
Reset
3
11. Turning either of the temperature control knobs will set
the relevant temperature. When the knob is turned the
display will alter and show the selected temperature. After a
few seconds the display reverts to show the current boiler
temperature (Fig. 65).
0
4
0
bar
Central Heating
Temperature Control
Domestic Hot Water
Temperature Control
Fig. 65
34
© Baxi Heating UK Ltd 2008
11.0 Commissioning
11.2
Checking
1. The gas valve is factory set and the burner pressure cannot
be measured as it is altered by suction of the fan and
modulates as demand on the boiler alters. The gas supply
pressure should be 20mb.
x 2
2. If necessary the gas rate may be checked after running the
boiler for 10 minutes with any other appliances and pilot
lights turned off.
3. Ensure that the integral timer and any external controls are
calling for heat, and the selector switch is in the central
Central Heating
Temperature Control
Domestic Hot Water
Temperature Control
heating and hot water position (
). The current boiler
Fig. 66
temperature is shown on the display.
4. To check the gas rate it is necessary to set the boiler to
‘Calibration Mode’.
Display
Selector Switch
5. Turn both temperature control knobs fully anticlockwise,
1
then quickly turn the DHW temperature knob /4 clockwise
twice and back fully anticlockwise (Fig. 66).
2
Reset
3
6. The display will now alternate between ‘SF’ and the
current boiler temperature and both green LEDs will flash
(Figs. 67 & 68).
0
4
0
bar
Central Heating
Temperature Control
Domestic Hot Water
Temperature Control
7. Turn CH temperature control knob fully clockwise. As the
knob is turned the display will change from ‘0’ to ‘00’ (Fig. 69)
indicating maximum rate, then revert to ‘P’ alternating with
the current boiler temperature (Figs 70 & 71).
8. A gas rate measurement may now be made. Approximate
values are:-
3
24 model
28 model
33 model
2.6m /h
3
3.1m /h
3
3.6 m /h
9. The ‘Calibration Function’ is active for 20 minutes unless
the maximum CH temperature is exceeded.
Fig. 67
Fig. 68
10. The function can be disabled at any time by turning the
DHW temperature knob.
Fig. 69
Fig. 71
Fig. 70
35
© Baxi Heating UK Ltd 2008
11.0 Commissioning
11.3
Setting the Timer
The Electro-Mechanical Timer allows the central heating
system to be set every 15 minutes.
Time Pointer
Using the three position switch the timer will allow either
constant operation, timed operation or central heating off.
Constant
Timed
Off
Move the switch button by sliding to the desired position.
Three position switch (Fig. 71a)
Constant (Top position): The heating will be on
constantly irrespective of the position of the tappets.The
heating will be controlled by the main thermostat on the
appliance and/or any external controls.
0
IN
Timed (Central position): The heating will operate
according to the position of the tappets and be controlled as
above.
Fig. 71a
Rotate to adjust time
0
Off (Bottom position): No central heating.
Domestic hot water will operate on demand.
To set the time of day
Turn the timer outer bezel clockwise, to align the pointer
with the correct time to the nearest 15 minutes
ensuring that A.M./P.M. is considered. Do not at any time
attempt to turn the bezel anti-clockwise.
To set the timed heating program
Decide which times of the day the central heating is required.
0
The heating will operate when the white tappets are set to
the outer edge of the bezel.
To ensure the heating stays OFF set the required tappets
inwards towards the centre of the bezel.
Each tappet represents 15 minutes.
For example: If the heating is not required between
10 A.M. and 11 A.M. the four tappets anticlockwise from the
10 A.M. will be set inwards (Fig. 71b).
On Position
Off Position
Time Pointer
Fig. 71b
36
© Baxi Heating UK Ltd 2008
12.0 Completion
12.1
Completion
Case Front Panel
1. Instruct the user in the operation of the boiler and
system explaining the operational sequence.
2. Set the central heating and hot water temperature
control knobs to the requirements of the user.
3. Carefully read and complete all sections of the
Benchmark Commissioning Checklist at the rear of this
publication that are relevant to the appliance and
installation. These details will be required in the event of
any warranty work. The publication must be handed to the
user for safe keeping and each subsequent regular service
visit recorded.
4. For IE, it is necessary to complete a “Declaration of
Conformity” to indicate compliance with I.S. 813. An
example of this is given in I.S. 813 “Domestic Gas
Installations”. This is in addition to the Benchmark
Commissioning Checklist.
5. Hand over the Users Operating, Installation and
Servicing Instructions giving advice on the necessity of
regular servicing.
Facia Panel
Fig. 72
37
© Baxi Heating UK Ltd 2008
13.0 Servicing
13 .1 Annual Servicing
Case Front Panel
1. For reasons of safety and economy, it is recommended that
the boiler is serviced annually. Servicing must be performed by
a competent person in accordance with B.S. 7967-4:2007.
If a suitably calibrated combustion analyser is available it
may not be necessary to perform a full strip down of the
appliance. Proceed as follows.
Check for/inspect:-
Evidence of leakage of products of combustion
Water leaks
Heat stress
Deterioration such as corrosion
Visible condition of seals and joints
Flue system and ventilation
Condensate drain system
Operation at designed maximum heat input
Fig. 73
If the above are satisfactory perform a combustion check
The CO/CO2 ratio must be less than 0.004 and the CO2
should be 8.7% 0.2 (max. rate) and 8.4% 0.2 (min.
rate). This can be adjusted - see Section 15.0 - if the
readings are incorrect. When correct combustion
readings cannot be achieved by adjustment a full strip
down must be performed - see below. Carefully check
items such as the burner, injector and heat exchanger
for blockage or damage, rectifying as necessary. Re-
check the combustion. Once satisfactory readings have
been achieved and any other defects corrected complete
the relevant Service Interval Record section of the
Benchmark Commissioning Checklist at the rear of this
publication.
Facia Panel Securing
Screws
Where no suitable analyser is available a strip down
service must be performed as described below.
2. After servicing, complete the relevant Service Interval
Record section of the Benchmark Commissioning Checklist at
the rear of this publication.
If a full strip-down is to be performed proceed as follows:-
3. Ensure that the boiler is cool.
4. Ensure that both the gas and electrical supplies to the
boiler are isolated.
Inner Door
Panel
Fig. 74
5. Slacken the screws securing the facia panel. Lift the
outercase panel so that its securing tabs are clear of the facia.
Remove the panel, allowing the facia to hinge down (Fig. 73).
6. Remove the screws securing the inner door panel. Lift the
panel slightly to disengage it from the studs on top of the case
(Fig. 74).
7. Unscrew the sump from the bottom of the condensate trap
assembly (Fig. 75).
Sump
8. Remove any deposits from the sump and trap. Clean as
necessary and replace the sump.
Fig. 75
38
© Baxi Heating UK Ltd 2008
13.0 Servicing
Burner
Viewing Window
13.1
Annual Servicing (Cont)
7.5
1
9. Undo the nut on the gas inlet pipe to the venturi (Fig. 77)
and pull the sensing pipe off the fan.
4
0.5
10. Disconnect the electrode leads, noting their position,
and the fan electrical plugs.
11. Undo the four nuts retaining the combustion box cover
to the heat exchanger.
12. Carefully draw the fan, collector and cover assembly
forward, being careful to retain the injector in the venturi
(Figs. 76 & 77).
10
1
Electrode Position
13. Clean any debris from the heat exchanger and check
that the gaps between the tubes are clear.
Fan, Collector and Cover
Assembly
14. Inspect the burner, electrodes and insulation, cleaning or
replacing if necessary. Clean any dirt or dust from the air
box.
15. Reassemble in reverse order.
NOTE: The sensing pipe must be reconnected to the
fan, not the venturi.
Electrode
Leads
DHW Filter (Fig. 79)
16. If the flow of domestic hot water is diminished, it may
be necessary to clean the filter.
Fig. 76
17. Initially check the cold water inlet tap filter.
Venturi
18. Turn the tap off and draw off from a hot tap. Undo the
blanking cap and remove the threaded bush (Fig. 78).
19. Extract the filter and rinse thoroughly in clean water.
Reassemble and check the flow. If required clean the
restricter filter as described below.
Injector
Fig. 78
Threaded
Bush
20. Pull off the Hall Effect sensor. Undo the restricter from
the inlet/return manifold (Fig. 79).
21. Rinse the filter thoroughly in clean water and reassemble
in reverse order.
Gas Inlet Pipe
Fig. 77
22. Turn the selector switch fully anticlockwise against the
spring pressure to the reset position and hold for 5 seconds
to reset the boiler.
Hall Effect
Sensor
Blanking
Cap
Cold Water
Inlet Tap
23. Complete the relevant Service Interval Record section of
the Benchmark Commissioning Checklist at the rear of this
publication and then hand it back to the user.
Restricter
Hydraulic Inlet
Assembly
Fig. 79
Filter
39
© Baxi Heating UK Ltd 2008
14.0 Changing Components
IMPORTANT: When changing components ensure that
both the gas and electrical supplies to the boiler are
isolated before any work is started. When the
component has been changed turn the selector switch
fully anticlockwise against the spring pressure to the
reset position and hold for 5 seconds to reset the boiler
before recommissioning.
Bracket
Igniter
Igniter Feed
Plug
See Section 13.1 “Annual Servicing” for removal of case
panel, door etc.
Electrode
Leads
14.1
Igniter (Fig. 80)
1. Disconnect the igniter feed plug and the electrode leads,
noting their positions.
Fig. 80
2. Undo the screw securing the bracket to the boiler.
3. Remove the igniter and transfer the bracket to the new
component.
4. Reassemble in reverse order.
14.2
Spark and Sensing Electrodes (Fig. 81)
1. Disconnect the electrode leads, noting their positions.
2. Remove the retaining screws securing each of the
electrodes to the combustion box cover and remove the
electrodes.
3. Check the condition of the sealing gasket and replace if
necessary. Reassemble in reverse order.
Spark
Electrode
Electrode
Leads
Sensing
Electrode
Fig. 81
40
© Baxi Heating UK Ltd 2008
14.0 Changing Components
14.3
Fan (Fig. 83)
1. Undo the nut on the gas inlet pipe to the venturi (Fig. 83)
and pull the sensing pipe off the fan.
2. Disconnect the electrode leads, noting their position and
disconnect the fan electrical plugs.
3. Undo the screws securing the collector to the cover (33
models) or extension piece (24 & 28 models).
4. Remove the collector and fan assembly, being careful to
retain the injector in the venturi.
5. Undo the screws securing the fan to the venturi and fit the
new fan, replacing the seal if necessary.
6. Examine the burner gasket and replace if necessary.
Venturi
Injector
7. Reassemble in reverse order, ensuring that the injector is
in place and the sensing pipe is connected to the fan.
14.4
Venturi (Fig. 82)
Cover
1. Remove the collector and fan assembly as described in
section 14.3.
2. Extract the injector from the venturi.
Gas Inlet Pipe
Fig. 83
3. Undo the screws securing the fan to the venturi and the
venturi to the collector.
Burner
Gasket
IMPORTANT: When fitting the new venturi, ensure the
arrows on it’s base point into the collector (Fig. 84).
4. Examine the seals and burner gasket, replace if necessary.
Gas Inlet
5. Reassemble in reverse order, ensuring that the injector is
in place.
Fan
14.5
Injector (Fig. 82)
Venturi
Injector
1. Remove the collector and fan assembly as described in
section 14.3.
Collector
Fig. 82
2. Extract and replace the injector and reassemble in reverse
order.
Fig. 84
When fitting the venturi
ensure that the arrow is
pointing forward
41
© Baxi Heating UK Ltd 2008
14.0 Changing Components
Cover
14.6
Burner (Fig. 85)
Burner
1. Undo the screws securing the collector to the cover and
venturi. (On 24 & 28 models there is an extension piece
fitted to the cover, remove this also).
Gasket
Extension Piece
(24 & 28 models)
2. Withdraw the burner from the cover and replace with
the new one.
3. Examine the gasket, replacing if necessary.
4. Reassemble in reverse order.
Venturi
14.7
Insulation (Fig. 86)
1. Remove the electrode leads, noting their positions. Also
remove the electrodes as described in section 14.2.
Collector
Fig. 85
2. Undo the screws securing the collector to the venturi and
the nuts holding the cover to the heat exchanger. Draw the
collector and cover assembly away.
3. Remove the cover insulation piece.
4. Fit the new insulation carefully over the burner and align
it with the slots for the electrodes.
5. The rear insulation is retained by a screw and large
washer, remove these and draw the insulation out of the
heat exchanger.
6. Examine the cover seal and replace if necessary.
Heat
Exchanger
Rear
Insulation
Spark
Electrode
Venturi
Cover
Insulation
Seal
Fig. 86
Collector
Electrode
Leads
Sensing
Electrode
42
© Baxi Heating UK Ltd 2008
14.0 Changing Components
Electrical
Plug
14.8
Flue/Heat Exchanger Thermostat Sensor
(Fig. 87)
Flue/Heat Exchanger
Thermostat Sensor
1. Ease the retaining tab on the sensor away and disconnect
the electrical plug.
°
2. Turn the sensor 90 anticlockwise to remove - it is a
bayonet connection.
3. Reassemble in reverse order.
Fig. 87
14.9
Water Pressure Sensor (Fig. 89)
1. Drain the primary circuit.
2. Disconnect the two wires from the sensor.
3. Undo the nut on the flow pipe securing and sealing the
sensor.
4. Remove the sensor, examine the sealing washer, replacing if
necessary.
5. Reassemble in reverse order. The component is not
polarised - either wire will fit each terminal.
14.10 Central Heating Temperature Sensor (NTC)
(Fig. 88)
Flow Pipe
Central Heating
Temperature Sensor
1. Ease the retaining tab on the sensor away and disconnect
the electrical plug.
2. Unscrew the sensor from it’s pocket and reassemble in
reverse order. The plug will only fit one way.
14.11 Safety Thermostat (Fig. 88)
1. Pull the plug off the thermostat.
Safety Thermostat
2. Remove the screws securing the thermostat to the
mounting plate on the flow pipe.
3. Reassemble in reverse order, ensuring that the plug is
pushed fully on.
Fig. 88
14.12 DHW Temperature Sensor (NTC) (Fig. 89)
1. Turn off the mains cold water supply tap and draw off the
residual domestic hot water.
Pressure Sensor
Plate Heat
Exchanger
2. Ease the retaining tab on the sensor away and disconnect
the electrical plug.
3. Unscrew the sensor from the plate heat exchanger
manifold. Examine the sealing washer,replacing if necessary.
4. Reassemble in reverse order. The plug will only fit one way.
Fig. 89
DHW Temperature
Sensor
43
© Baxi Heating UK Ltd 2008
14.0 Changing Components
Heat Exchanger
Air Vent
14.11 Heat Exchanger Automatic Air Vent (Fig. 90)
1. Drain the boiler primary circuit and unscrew the
automatic air vent from the pump body.
2. Examine the ‘O’ ring seal, replacing if necessary, and fit it
to the new automatic air vent.
Grommet
3. Reassemble in reverse order, transferring the grommet to
the new vent.
4. Ensure that the grommet is is sealed correctly to the
boiler top panel.
Fig. 90
14.12 Pump - Head Only (Fig. 91)
1. Drain the boiler primary circuit and remove the socket
head screws securing the pump head to the body and draw
the head away.
2. Undo the screw on the pump wiring cover and remove
the cover. Using a suitable flat bladed screw driver press the
cable securing levers downwards to release each wire after
noting their position.
Pump Wiring
Pump Body
Cover
3. A standard replacement Grundfos 15-60 head can now
be fitted. Connect the pump wiring to the new head. The
pump speed must be set to 3 (Fig. 92).
4. Reassemble in reverse order.
Socket Headed
Screw
14.13 Pump - Complete (Fig. 93)
1. Drain the boiler primary circuit.
Pump Head
2. Undo the two screws securing the body to the pipe and
manifold and draw the pump forwards.
Fig. 91
3. Undo the screw on the pump wiring cover and remove
the cover. Using a suitable flat bladed screw driver press the
cable securing levers downwards to release each wire after
noting their position.
Pump Setting
4. Unscrew the automatic air vent from the pump body.
Fig. 92
Automatic Air
Vent
5. Connect the wiring to the new pump. Examine the ‘O’
ring seals on the return pipe and manifold, replacing if
necessary.
Pump Wiring
Cover
6. Fit the air vent to the pump body and reassemble in
reverse order.
14.14 Automatic Air Vent (Fig. 93)
1. Drain the boiler primary circuit and unscrew the
automatic air vent from the pump body.
2. Examine the ‘O’ ring seal, replacing if necessary, and fit it
to the new automatic air vent.
Fig. 93
3. Reassemble in reverse order.
44
© Baxi Heating UK Ltd 2008
14.0 Changing Components
14.15 Pressure Gauge (Figs. 94 & 95)
Gauge Retaining
Bracket
1. Drain the boiler primary circuit and undo the nut on the
pressure gauge capillary.
2. Undo the screws securing the gauge retaining bracket.
3. Remove the bracket and gauge assembly. Depress the
barbs on the side of the gauge and remove the retaining
bracket.
Pressure Gauge
Fig. 94
4. Examine the sealing washer, replace if necessary.
5. Reassemble in reverse order.
14.16 Hall Effect Sensor (Fig. 96)
1. Ease the sensor upwards off the hydraulic inlet manifold
assembly.
2. Disconnect the electrical plug from the sensor.
3. Connect the plug to the new sensor. Carefully fit the new
sensor to the hydraulic assembly, ensuring it is fully down.
Fig. 95
Pressure Gauge
Capillary
Hall Effect
Sensor
14.17 Pressure Relief Valve (Fig. 97)
1. Drain the boiler primary circuit.
2. Disconnect the discharge pipe from the valve. Using a
suitable hexagon key undo the grub screw sufficiently to
release the valve.
3. Note the orientation of the valve, rotate it and withdraw
it from the manifold.
Hydraulic Inlet
Assembly
4. Fit the new valve and ‘O’ ring seal and set to the
previously noted orientation. Reassemble in reverse order.
Fig. 96
‘O’ ring seal
Grub Screw
Pressure Relief Valve
Fig. 97
Discharge Pipe
45
© Baxi Heating UK Ltd 2008
14.0 Changing Components
14.18 Plate Heat Exchanger (Fig. 98)
1. Drain the boiler primary circuit and remove the gas valve
as described in section 13.22.
Plate Heat Exchanger
2. While supporting the heat exchanger undo the screws
securing it to the brass manifolds.
3. Withdraw the heat exchanger upwards, taking care not to
damage any wires or controls.
Seals
4. There are four rubber seals between the manifolds and
heat exchanger which may need replacement.
LH Location Stud
Fig. 98
5. Ease the seals out of the manifold. Replace carefully,
ensuring that when the seal is inserted into the manifold it is
parallel and pushed fully in.
Rubber Seal
6. When fitting the new heat exchanger note that the left
hand location stud is offset towards the centre more than the
right hand one.
7. Reassemble in reverse order.
14.19 Diverter Valve - Motor Unit & Assembly
(Figs. 99 & 100)
1. To replace the motor unit, disconnect the multi-pin plug.
2. Pull off the retaining clip and remove the motor unit.
Motor Unit
3. The motor unit can now be replaced, or the valve
assembly removed.
Multi-pin Plug
4. Drain the primary circuit and draw off any hot water once
the isolating taps are closed.
Retaining Clip
5. Remove the spring clip retaining the bypass pipe to the
rear of the assembly and under the flow pipe nut at the left
hand side.
Valve
Assembly
6. Undo the nuts on the tap rail under the boiler. Remove
the screws securing the valve assembly to the boiler bottom
panel and plate heat exchanger.
Fig. 99
7. Remove the valve assembly. Examine any seals or washers,
replacing if necessary. Transfer the DHW NTC to the new
valve and reassemble in reverse order.
Pressure Sensor
Bypass Pipe
Spring Clip
Fig. 100
Securing Screw
46
© Baxi Heating UK Ltd 2008
14.0 Changing Components
14.20
P.C.B. (Fig. 102)
1. Note the settings of the temperature control knobs,
rotate them fully anticlockwise and carefully pull them off
the drive pins.
2. Completely undo the screws securing the control box
cover and release the cover retaining barbs from their slots.
Disengage the rear of the cover from the control box hinge
pin (Fig. 101).
3. Note the position of all plugs and wires on the P.C.B. and
disconnect them.
4. Undo the securing screws and remove the P.C.B. Transfer
the control knob drive pins to the new P.C.B. and turn them
fully anticlockwise.
Control Box Cover
P.C.B.
Fig. 101
5. Reassemble in reverse order, ensuring that the
temperature controllers are reset to their previous positions.
14.21 Selector Switch (Fig. 102)
Selector
Switch
1. Note the setting of the selector switch knob and carefully
pull it off the facia.
Drive Pins
2. Completely undo the screws securing the control box
cover and release the cover retaining barbs from their slots.
Disengage the rear of the cover from the control box hinge
pin (Fig. 101).
3. Note the position of the electrical connections and the
orientation of the switch. Remove the electrical connections.
4. Remove the screws securing the switch to the facia panel.
Facia
5. Fit the new switch, ensuring that it is correctly positioned
and reassemble in reverse order.
Selector Switch Knob
Temperature Control Knobs
Fig. 102
47
© Baxi Heating UK Ltd 2008
Venturi Inlet
Pipe
14.0 Changing Components
Outlet Adaptor
14.23 Gas Valve (Fig. 103)
IMPORTANT: After replacing the valve the CO2 must be
checked and adjusted as detailed in Section 15.0
Combustion Check. Only change the valve if a suitable
calibrated combustion analyser is available.
Gas Valve
Sensing Pipe
Ignition Lead
1. Turn the gas cock off and undo the nut on the gas feed
elbow under the boiler.
2. Remove the screws securing the inlet pipe flange to the
boiler bottom panel.
3. Pull off the earth lead and sensing pipe.
4. Undo the nut on the venturi inlet pipe and slacken the nut
on the venturi. Ease the pipe aside and remove the gas valve.
Valve
Inlet Pipe
5. Remove the outlet adaptor and inlet pipe and transfer them
to the new valve. Examine the ‘O’ ring seals, replace if
necessary.
Gas Feed
Elbow
Fig. 103
6. Reassemble in reverse order.
NOTE: To assist the boiler to light prior to final setting,
use a suitable hexagon key to wind out the Gas/Air
adjustment screw until it is flush with the valve body, then
turn the screw 4 full turns clockwise (Fig. 103a). If the
boiler will not light, or the correct CO2 cannot be achieved
contact the ‘heateam’ technical helpline.
Gas/Air
Adjustment Screw
14.24 Expansion Vessel (Fig. 104)
1. Drain the primary circuit and undo the nut on the vessel
connection pipe.
Fig. 103a
2. Undo and remove the locknut securing the vessel spigot to
the boiler air box.
Retaining Bracket
3. Remove the bracket and vessel from the boiler.
Expansion Vessel
4. Locate the retaining bracket on the upper flange of the
vessel and fit to the boiler.
5. Reassemble in reverse order.
Lock Nut
Boiler Chassis
Fig. 104
48
© Baxi Heating UK Ltd 2008
15.0 Combustion Check
15.1
Checking the CO2
x 2
IMPORTANT: The CO2 must only be checked and
adjusted if a suitable calibrated combustion analyser is
available.
1. The combustion (CO2) may be checked using a suitably
calibrated analyser after running the boiler for several
minutes.
Central Heating
Temperature Control
2. To do this it is necessary to set the boiler to ‘Calibration
Mode’.
Domestic Hot Water
Temperature Control
Fig. 105
Display
Selector Switch
3. Ensure that all external controls are calling for heat. The
actual current boiler temperature is shown on the display.
4. Turn both temperature control knobs fully anticlockwise,
1
2
then quickly turn the DHW temperature knob /4 clockwise
Reset
3
twice and back fully anticlockwise (Fig. 105).
0
4
0
bar
5. The display will now alternate between ‘SF’ and the
current boiler temperature and both green LEDs will flash
(Figs. 106 & 107).
Central Heating
Temperature Control
Domestic Hot Water
Temperature Control
6. Turn the CH temperature knob fully clockwise. As the
knob is turned the display will change, indicating the fan
speed.
7. The display will show ‘00’, indicating maximum rate, then
revert to ‘P ‘ alternating with the current boiler temperature
(Figs 108, 109 & 110).
Fig. 107
Fig. 106
8. Remove the plug from the flue adaptor test point. Insert
the analyser probe and allow time for the reading to settle
(Fig. 111).
The CO2 should be 8.7% 0.2
9. It is possible to alter the CO2 by adjustment of the gas
valve. Remove the plastic cover from the ‘Max Rate’
adjustment screw. At maximum rate the ‘Max. Rate’
adjustment screw should be turned, using a suitable
hexagon key, until the correct reading is obtained (Fig. 112).
Turning clockwise will reduce the CO2. Anticlockwise will
increase the CO2.
Fig. 109
Fig. 110
Fig. 108
Flue Adaptor Test
Point
Plug
10. The CO2 must then be checked at minimum rate. Turn
the CH temperature knob fully anticlockwise. As the knob is
turned the display will change, indicating the fan speed.
When the display reads ‘ 0’ the boiler runs at minimum rate.
The CO2 should be 8.4% 0.2.
Analyser Probe
Fig. 111
Max Rate
Adjustment Screw
(cover removed)
Min Rate
Adjustment Screw
(cap fitted)
11. With the boiler on minimum, the ‘Min. Rate’ adjustment
screw must be altered, using a suitable hexagon key, after
removing the cap (Fig. 112). If the CO2 is reset at either
boiler rate it must be rechecked at the other rate and also
adjusted if required.
12. The ‘Calibration Function’ is maintained for 20 minutes
unless the maximum CH temperature is exceeded. The
function can be disabled at any time by turning the DHW
knob.
Gas Valve
Fig. 112
49
© Baxi Heating UK Ltd 2008
16.0 Electrical
16.1
Illustrated Wiring Diagram
Central Heating
NTC Sensor
b
DHW
NTC Sensor
b
Overheat Stat
Hall Effect
Sensor
b
r
b
Water Pressure
Switch
r
Flue Sensor
1
4
2
g
5
br
r
b
w
b
g
Fan
3
bk
g
1
2
b
g/y
b
b
br
4
3
2
X400
X401
1
5
4
3
2
1
5
4
3
2
1
9
8 7
6
10
9
8 7
6
Timer
bk
br
Control PCB
bk
b
X501
5
6
7
8
r
9
1
2
1
2
3
4
5
1
2
3
4
X1
X2
X3
b
bk
br
Flame
Sensing
Electrode
br
Pump
w
b
bk
br
b
br
br
r
b
b
br
b
w
r
Spark
Generator
L
N
bk
b
b
a
DiverterValve
br
bk
g
w
br
GasValve
b
Link
Ignition
Electrode
g/y
b
bk
r
br
Mains Input Cable
g
- green
br - brown
bk - black
g/y - green / yellow
- red
r
b
- blue
w
- white
50
© Baxi Heating UK Ltd 2008
17.0 Short Parts List
Short Parts List
Key
No.
G.C.
No.
Description
Manufacturers
Part No.
426
306
326
426
315
316
422
404
313
Fan
5121447
248733
Motor 3way Valve
Igniter Electrode
Sensing Electrode
Gas Valve
5114702
5114703
5119647
5114767
315
316
311
Hall Effect Sensor
Burner 24
Burner 28
Burner 33
5122149
5114697
5114698
419
400
Water Pressure Switch
Plate Heat Exchanger 24
5114748
248048
419
624
422
Plate Heat Exchanger 28/33 5114708
415
421
420
504
503
Pump
248042
5114725
5114729
248090
NTC Sensor
Overheat Thermostat
Pressure Gauge
400
PCB 24
PCB 28
PCB 33
5121862
5120218
5120219
415
421
420
302
503
504
51
© Baxi Heating UK Ltd 2008
18.0 Fault Finding
18.1
Initial Fault Finding Checks
NOTE: When instructed to turn the
selector to the reset position turn the
selector switch fully anticlockwise against
the spring pressure to the reset position
and hold for 5 seconds to reset the
boiler.
1. Check that gas, water and electrical supplies are available
at the boiler.
2. Electrical supply = 230V ~ 50 Hz.
3. CH water system pressurised to 0.5 bar minimum when
the boiler is cold.
4. The preferred minimum gas pressure is 20 mbar.
5. Carry out electrical system checks, i.e. Earth Continuity,
Resistance to Earth, Short Circuit and Polarity with a suitable
meter.
NOTE: These checks must be repeated after any
servicing or fault finding.
6. Ensure all external controls are calling for heat and check
all external and internal fuses. Before any servicing or
replacement of parts, ensure the gas and electrical supplies
are isolated.
18.2
Error Codes
1. If a fault occurs on the boiler an error code may be shown
by the facia display.
2. The codes are either two or three digit, preceded by the
letter 'E'. For example, code E133 will be displayed by 'E1'
alternating with '33'. E50 is shown as 'E' then '50'
Table Of Error Codes
E20
Central Heating NTC Fault
Flue NTC Fault
E28
E20, E28 & E50 indicate faulty or incorrect components.
E50
Hot Water NTC Fault
E110 shows overheat of the primary water and E130
overheat of the flue system.
E110
E119
E125
E130
E133
E160
E193
Safety Thermostat Operated
Water Pressure Switch Not Operated
Circulation Fault (Primary Circuit)
Flue NTC Operated
E119 is displayed when the primary water pressure is less
than 0.5 bar.
Interruption Of Gas Supply or Flame Failure
Fan or Fan Wiring Fault
E133 indicates that the gas supply has been interrupted,
ignition has failed or the flame has not been detected.
Pre-Circulation Fault
E125 is displayed in either of two situations:-
i) If within 15 seconds of the burner lighting the boiler
temperature has not changed by 1°.
ii) If within 10 minutes of the burner lighting the boiler
temperature twice exceeds the selected temperature by 30°.
In these instances poor primary circulation is indicated.
3. By turning the selector switch to the 'Reset' position for a
minimum of 5 seconds when E110, E130 & E133 are
displayed it is possible to relight the boiler.
4. If this does not have any effect, or the codes are displayed
regularly further investigation is required.
52
© Baxi Heating UK Ltd 2008
18.0 Fault Finding
Refer to Section 16.0 “Illustrated Wiring Diagram” for position of terminals and components
Central Heating - Follow operational sequence (do
Turn selector switch to
The display illuminates
NO
Go to section ‘A’
YES
Error 110 flashing
Error 130 flashing
Error 133 flashing
If the error 110 is still flashing.
Go to section ‘J’
Turn the selector switch to
reset position for 5 seconds
YES
YES
NO
YES
YES
Error 20, 28 or 50 flashing
NO
Go to section ‘E’
Error 119 flashing
Go to section ‘C’
NO
Ensure controls are set to
demand and verify the
contacts are closed
NO
Turn Central Heating
thermostat to Maximum.
Pump runs
Ensure all controls (and
integral clock if fitted) are
calling for heat
NO
YES
Go to section ‘B’
YES
Ensure that primary
circulation is OK & that
there is no blockage
YES
NO
Error 125 or 193 flashing
NO
3-way valve is open to Central
Heating circuit
Go to section ‘K’
YES
NO
NO
Error 160 flashing
Go to section ‘D’
Fan runs
YES
Error 160 flashing
Go to section ‘L’
Fan runs at correct speed
YES
Go to section ‘H’
Turn the selector switch to
reset
Spark at ignition electrodes for
up to 5 seconds and for 3
attempts
YES
YES
NO
YES
Error 133 flashing
Go to section ‘F’
YES
NO
Burner does not stay alights
after 5 seconds
Error 133 flashing
Go to section ‘I’
Burner lights
Check the Central Heating
NTC sensor
YES
NO
Go to section ‘E’
Burner output modulates to
maintain the temperature set
Error 130 flashing
Go to section ‘M’
YES
Pump continues to run for 3
YES
YES
YES
Operation sequence
successful
Burner goes out
Fan stops after 10 seconds
minutes
(room thermostat open)
53
© Baxi Heating UK Ltd 2008
18.0 Fault Finding
Domestic Hot Water - Follow operational sequence
Turn selector switch to
The display illuminates
NO
Go to section ‘A’
YES
YES
Error 110 flashing
Error 133 flashing
If the error 110 is still flashing.
Go to section ‘J’
Turn the selector switch to
reset position for 5 seconds
YES
NO
YES
YES
Error 20, 28 or 50 flashing
NO
Go to section ‘E’
Go to section ‘C’
Error 119 flashing
Go to section ‘B’
YES
NO
Turn Domestic Hot Water
thermostat to Maximum.
Open DHW tap fully.
DHW Hall Effect sensor
operated (red neon on the
sensor illuminated
Is mains water filter and
assembly clean?
Is the magnetic detector free
to move in the Hall Effect
sensor
NO
NO
YES
DHW flow rate more than 2
l/min
YES
3-way valve is open to
Domestic Hot Water circuit
Go to section ‘K’
YES
Error 125 flashing
Go to section ‘B’
NO
NO
Pump runs
YES
Error 160 flashing
Go to section ‘D’
Fan runs
YES
NO
NO
Error 160 flashing
Go to section ‘L’
Fan runs at correct speed
YES
Go to section ‘H’
Turn the selector switch to the
reset position for 5 seconds
Spark at ignition electrodes for
up to 5 seconds and for 3
attempts
YES
Error 133 flashing
Go to section ‘F’
YES
NO
YES
NO
YES
NO
Burner does not stay alights
after 5 seconds
Error 133 flashing
Go to section ‘I’
Burner lights
YES
Clean DHW NTC sensor
and DHW heat exchanger
Reduce DHW flow rate
Burner modulates
Burner output modulates to
maintain the temperature set
NO
Error 130 flashing
Go to section ‘M’
YES
Close DHW tap
YES
YES
DHW flow sensor senses no
flow. Burner goes out
YES
YES
Operation sequence
successful
Fan stops after 10 seconds
Pump runs for 30 seconds
54
© Baxi Heating UK Ltd 2008
18.0 Fault Finding
Fault Finding Solutions Sections
Is there 230V at:
A
NO
NO
NO
1.
2.
3.
Main terminals L and N
Main terminal fuse
Check electrical supply
Replace fuse
NO
Display
illuminated
Replace PCB
Check wiring
PCB - X1 connector
terminals 1,2
Is there 230V at:
YES
B
NO
NO
1.
2.
Pump
If pump jammed, release
Replace pump
Replace PCB
PCB - X3 connector terminals 3 & 4
YES
Change pump supply cable
YES
1.
CH system pressure less than 0.5 bar
NO
Re-pressurise system
C
Check connection water pressure
switch terminal
YES
Replace water
pressure switch
COM - NO and PCB connector
X400 terminals 3,4
2.
1.
NO
Check the tap of the automatic air
vent is opened
Open the automatic air vent
D
Fan connections correct at fan. PCB -
X2 connector, is 230V AC across
terminals 5 & 7
YES
YES
Fan jammed or faulty winding
Replace PCB
Replace fan
NO
55
© Baxi Heating UK Ltd 2008
18.0 Fault Finding
E
F
E20 or E50 - Temperature sensors faulty.
Cold resistance approximately
10kΩ @ 25° C (DHW and CH sensors)
20kΩ @ 25° C (Flue sensor)
NO
Replace sensor or PCB (E28)
(resistance reduces with increase in temp.)
E28 - Incorrect PCB fitted
1.
Check and correct the connection of the
tube between the venturi and gas valve
NO
2.
Gas at burner
Ensure gas is on and purged
YES
PCB - X3 connector is 230V AC across
terminals 1 & 2
Replace gas valve
NO
Replace PCB
G
H
1.
Ensure that the Hall Effect Sensor is in position.
Check the connection between the PCB - X400
connector terminals 3,6,7 and the electronic sensor
YES
Check the voltage between red wire and blue
wire is more than 5V DC
YES
NO
Replace PCB
Replace Hall
Effect Sensor
Voltage at PCB - X2 connector is at
least 100V DC across terminals 2 & 5
(Note: from multimeter connect
‘common’ to 2 & ‘volts’ to 5).
Check wiring
NO
YES
Check and correct if necessary
Replace PCB
YES
1. Ignition electrode and lead
2. Electrode connection
3. Spark gap and position
Replace igniter
Burner
Viewing Window
7.5
1
4
0.5
10
1
Electrode Position
56
© Baxi Heating UK Ltd 2008
18.0 Fault Finding
1.
2.
Check the gas supply pressure:
For Natural Gas greater than
10 - 11 mbar
I
Check and correct if necessary
1. The mechanical set of the gas valve
(CO2 values - see instruction)
2. Flame sensing electrode and lead connections
3. Flame sensing electrode position
YES
NO
Replace PCB
Replace flame sensing electrode
Flame current should be more than 0.5 μA
1.
Overheat thermostat operated or
NO
Allow to cool. Continuity
across thermostat terminals
more than 1.5 ohm
J
YES
Replace safety thermostat
faulty, i.e. continuity across
thermostat terminals
YES
Replace PCB
Is there 230V at:
K
YES
1.
Motor 3-way valve
Replace motor 3-way valve
NO
2. PCB - X3 connector terminals
5 & 6 central heating mode
Replace PCB
5 & 7 domestic hot water mode
YES
Change pump supply cable
1.
L
YES
Fan connections correct at fan.
PCB - X401 connector terminals 5,6,7 & 8
Replace fan
M
1.
2.
Temperature sensors faulty.
Cold resistance approximately
10kΩ @ 25° C (CH sensor)
20kΩ @ 25° C (Flue sensor)
(resistance reduces with increase in temp.)
NO
Replace sensor
If pump is running the heat exchanger could be
obstructed
YES
Replace heat exchanger
57
© Baxi Heating UK Ltd 2008
5 1 1 6 2 8 2
BENCHMARK No.
GAS BOILER COMMISSIONING CHECKLIST
C O L L E C T I V E M A R K
BOILER SERIAL No.
NOTIFICATION No.
CONTROLS To comply with the Building Regulations, each section must have a tick in one or other of the boxes
TIME & TEMPERATURE CONTROL TO HEATING ROOM T/STAT & PROGRAMMER/TIMER
TIME & TEMPERATURE CONTROL TO HOT WATER CYLINDER T/STAT & PROGRAMMER/TIMER
PROGRAMMABLE ROOMSTAT
COMBI BOILER
HEATING ZONE VALVES
FITTED
FITTED
FITTED
FITTED
NOT REQUIRED
HOT WATER ZONE VALVES
NOT REQUIRED
THERMOSTATIC RADIATOR VALVES
AUTOMATIC BYPASS TO SYSTEM
NOT REQUIRED
FOR ALL BOILERS CONFIRM THE FOLLOWING
THE SYSTEM HAS BEEN FLUSHED IN ACCORDANCE WITH THE BOILER MANUFACTURER’S INSTRUCTIONS?
THE SYSTEM CLEANER USED
THE INHIBITOR USED
FOR THE CENTRAL HEATING MODE, MEASURE & RECORD
GAS RATE
m3/hr
N/A
ft3/hr
mbar
°C
BURNER OPERATING PRESSURE (IF APPLICABLE)
CENTRAL HEATING FLOW TEMPERATURE
CENTRAL HEATING RETURN TEMPERATURE
°C
FOR COMBINATION BOILERS ONLY
HAS A WATER SCALE REDUCER BEEN FITTED?
YES
NO
WHAT TYPE OF SCALE REDUCER HAS BEEN FITTED?
FOR THE DOMESTIC HOT WATER MODE, MEASURE & RECORD
m3/hr
N/A
GAS RATE
ft3/hr
mbar
°C
MAXIMUM BURNER OPERATING PRESSURE (IF APPLICABLE)
COLD WATER INLET TEMPERATURE
HOT WATER OUTLET TEMPERATURE
WATER FLOW RATE
°C
lts/min
FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING
THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH
THE MANUFACTURER’S INSTRUCTIONS?
YES
FOR ALL INSTALLATIONS CONFIRM THE FOLLOWING
THE HEATING AND HOT WATER SYSTEM COMPLIES
WITH CURRENT BUILDING REGULATIONS
THE APPLIANCE AND ASSOCIATED EQUIPMENT HAS BEEN INSTALLED AND COMMISSIONED
IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS
IF REQUIRED BY THE MANUFACTURER, HAVE YOU RECORDED A CO/CO2 RATIO READING? N/A
YES
CO/CO2 RATIO
THE OPERATION OF THE APPLIANCE AND SYSTEM
CONTROLS HAVE BEEN DEMONSTRATED TO THE CUSTOMER
THE MANUFACTURER’S LITERATURE HAS BEEN LEFT WITH THE CUSTOMER
COMMISSIONING ENG’S NAME PRINT
CORGI ID No.
DATE
SIGN
58
SERVICE INTERVAL RECORD
It is recommended that your heating system is serviced regularly
and that you complete the appropriate Service Interval Record Below.
Service Provider. Before completing the appropriate Service Interval Record below, please ensure you have carried out the service
as described in the boiler manufacturer’s instructions. Always use the manufacturer’s specified spare part when replacing all controls
SERVICE 1 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
SERVICE 2 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SIGNATURE
SERVICE 3 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
SERVICE 4 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SIGNATURE
SERVICE 5 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
SERVICE 6 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SIGNATURE
SERVICE 7 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
SERVICE 8 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SIGNATURE
SERVICE 9 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
SERVICE 10 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SIGNATURE
59
All descriptions and illustrations provided in this leaflet have been carefully
prepared but we reserve the right to make changes and improvements in
our products which may affect the accuracy of the information contained in
this leaflet. All goods are sold subject to our standard Conditions of Sale
which are available on request.
POTTERTON
A Trading Division of Baxi Heating UK Ltd (3879156)
A Division of Baxi Group
Brooks House, Coventry Road, Warwick. CV34 4LL
After Sales Service 08706 017 017 Technical Enquiries 08706 049 049
e&oe
IT Comp No 925.659.2
o
UK Comp N 5116282 - Iss 7 - 4/08
|
Audiovox 50 0244x 001 SERIES User Manual
Blaupunkt MIAMI 7 641 803 310 User Manual
Canon Camcorder HF R10 A User Manual
Casio Cash Register Med Metal TK1550 User Manual
Cuisinart ICE 40 User Manual
Datexx DS 700 30Xa User Manual
Frigidaire FFWC38F6LS User Manual
JVC AA V33U User Manual
JVC Blu ray Player SR HD2500US User Manual
JVC GET0287 003A User Manual