You can rely on
Installation & Service Instructions
Gold
FSB 30 HE
Floor Standing
Condensing Boiler
These instructions include the Benchmark Commissioning Checklist
and should be left with the user for safe keeping.
© Baxi Heating UK Ltd 2011
Installer Notification Guidelines
Choose Building
Regulations Notification
Route
Competent Person's
Building Control
Self Certification Scheme
Install and Commission this
appliance to manufacturer's
instructions
Contact your relevant Local
Authority Building Control
(LABC) who will arrange
an inspection or contact
a government approved
inspector
Complete the
Benchmark Checklist
If you notify via the ‘Gas Safe
Register’, the register will issue
the Building Regulations
Install and Commission this
appliance to manufacturer's
instructions
certificate on members’ behalf
Scheme Members only
Call ‘Gas Safe Register’ on:
0800 408 5577
Complete the
Benchmark Checklist
or log onto:
within 10 days
You must ensure that the
certificate number issued by
the ‘Gas Safe Register’ is written
onto the Benchmark Checklist
‘Gas Safe Register’ will issue a
Building Regulations Compliance
Certificate to the property owner
and inform the relevant LABC
LABC will record the data
and will issue a
certificate of compliance
3
© Baxi Heating UK Ltd 2011
Legislation
This company declare that no substances harmful to
health are contained in the appliance or used during
appliance manufacture.
IMPORTANT - Installation, Commissioning, Service & Repair
This appliance must be installed in accordance with the manufacturer’s instructions and
the regulations in force. Read the instructions fully before installing or using the
appliance.
The appliance is suitable only for installation in GB and IE
and should be installed in accordance with the rules in
force, and only used in a suitably ventilated location.
In GB, this must be carried out by a competent person as stated in the Gas Safety
(Installation & Use) Regulations.
In GB, the installation must be carried out by a Gas Safe
Registered Installer. It must be carried out in accordance
with the relevant requirements of the:
Gas Safety (Installation & Use) Regulations.
The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building
Regulations (Northern Ireland).
The Water Fittings Regulations or Water Byelaws in
Scotland.
The Current I.E.E. Wiring Regulations.
Definition of competence: A person who works for a Gas Safe registered company
•
•
and holding current certificates in the relevant ACS modules, is deemed competent.
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domestic
Gas Installations”.
•
•
The addition of anything that may interfere with the normal operation of the appliance
without express written permission from the manufacturer or his agent could invalidate
the appliance warranty. In GB this could also infringe the Gas Safety (Installation and
Use) Regulations.
Where no specific instructions are given, reference should
be made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a competent
Person and installed in accordance with the current edition
of I.S. 813 ‘Domestic Gas Installations’, the current Building
Regulations and reference should be made to the current
ETCI rules for electrical installation.
Warning - Check the information on the data plate is compatible with local supply
conditions.
All systems must be thoroughly flushed and treated
with inhibitor (see section 6.2).
All Gas Safe registered engineers carry an ID card with their licence number and a
photograph. You can check your engineer is registered by telephoning
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency)
Regulations 1993 No 3083” and is deemed to meet the requirements of Directive
92/42/EEC on the energy efficiency requirements for new hot water boilers fired with
liquid or gaseous fuels:-
Codes of Practice, most recent version should be used
In GB the following Codes of Practice apply:
Standard
Scope
BS 6891
Gas Installation.
BS 5482 Part 1
BS 5546
Butane & Propane Gas Installation
Installation of hot water supplies for domestic
purposes.
Type test for purpose of Regulation 5 certified by:
Notified Body 0087.
BS EN 12828
BS EN 12831
BS EN 14336
Heating systems in buildings.
Heating systems in buildings - Calculation of load.
Installation & commissioning of water based
heating systems.
Product/Production certified by:
Notified Body 0086.
BS 6798
Installation of gas fired hot water boilers.
Flues.
Ventilation.
Expansion vessels and ancillary equipment for
sealed water systems.
BS 5440 Part 1
BS 5440 Part 2
BS 7074
For GB/IE only.
BS 7593
Treatment of water in domestic hot water
central heating systems.
In IE the following Codes of Practice apply:
Standard
Scope
I.S. 813
Domestic Gas Installations.
The following standards give valuable additional information;
BS 5546
Installation of hot water supplies for domestic
purposes.
BS EN 12828
BS EN 12831
BS EN 14336
Heating systems in buildings.
Heating systems in buildings - Calculation of load.
Installation & commissioning of water based
heating systems.
BS 7074
BS 7593
Expansion vessels and ancillary equipment for
sealed water systems.
Treatment of water in domestic hot water
central heating systems.
4
© Baxi Heating UK Ltd 2011
Contents
Section
1.0
Page
Introduction
6
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
General Layout
7
8
Boiler Operation
Technical Data
9
Dimensions and Fixings
System Details
10
11
15
20
25
29
34
36
38
39
42
49
50
58
Site Requirements
Flue Options
Plume Displacement
10.0 Installation
11.0 Electrical
12.0 Commissioning the Boiler
13.0 Completion
14.0 Servicing the Boiler
15.0 Changing Components
16.0 Short Parts List
17.0 Fault Finding
Benchmark Checklist
5
© Baxi Heating UK Ltd 2011
Facia Securing Screws
1.0 Introduction
1.1
Description
Optional Integral Timer
Position of Label
1. The Potterton Gold FSB 30 HE is a gas fired room
sealed fan assisted condensing central heating boiler.
2. The maximum output of the boiler is 30.18 kW (Non -
Condensing) 32.61 kW (Condensing).
3. The boiler is designed for use on Natural Gas (G20)
only.
4. The boiler is suitable for fully pumped open vented and
sealed systems, providing heating and hot water.
5. A label giving details of the model, serial number and
Gas Council number is situated on the rear of the drop
down facia panel (Fig. 1).
6. The boiler data badge is positioned on the air box door
(Fig. 2).
Fig. 1
7. The boiler is intended to be installed in residential /
commercial / light industrial E.M.C. environments on a
governed meter supply only.
8. The boiler must be installed with one of the purpose
designed flues such as the standard horizontal flue kit, part
no 236921.
Case Securing Screws
1.2
Important Information
Man-made mineral fibre
• Some component parts of this boiler (insulation pads,
gaskets and rope seals) are manufactured from man-made
mineral fibre.
• Prolonged or excessive exposure to this material may
result in some irritation to the eyes, skin or respiratory
tract.
• It is advisable to wear gloves when handling these items.
• Irritant dust will only be released from the items if they
are broken up or subjected to severe abrasion. In these
instances a suitable dust mask and goggles should be
worn.
• Always thoroughly wash hands after installation,
servicing or changing components.
Air Box Door
• When disposing of any items manufactured from man-
made mineral fibre care must be exercised.
• If any irritation of the eyes or severe irritation of the skin
is experienced seek medical attention.
Fig. 2
Data Badge
6
© Baxi Heating UK Ltd 2011
2.0 General Layout
2.1
Layout (Figs. 3, 4, 5 & 6)
16
1.
Condensate Pump
2.
Flue Elbow (supplied in std. flue kit)
Heat Exchanger
3.
4.
Burner
5.
Air Box
6.
Fan Protection Thermostat - Black
Fan Assembly
7.
Fig. 5
2
8.
Condensate Trap
15
14
9.
PCB Housing Assembly
Gas Tap
17
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
18
Gas / Air Ratio Valve
Flow Pipe Connection
Return Pipe Connection
Flow Temperature Safety Thermostat - Black
Flow Temperature Thermistor - Red
Flow Switch (dry fire protection)
Position of Optional Integral Timer Wiring
Pipe Access Panel
13
12
3
9
19
Manual Air Vent
4
6
2.2
KIT
110Ø Concentric Flues & Optional Extras
PART No
5
Standard Flue Kit 850mm (inc. elbow)
Extended Flue Kit - 1.75M ( inc. elbow)
Flue Plume Deflector Kit
236921
5111457
248167
248484
Terminal Guard (suitable for use with above)
FLUE EXTENSION KITS (110/70)
Flue Extension 250mm
241692
241694
241695
Flue Extension 500mm
Flue Extension 1000mm (Use two kits for 2M etc.)
Flue Bend x 2 - 45° (Reduce overall length of flue
by 0.5m when fitting this bend)
241689
241687
Fig. 3
Flue Bend - 93° (Reduce overall length of flue
by 1m when fitting each bend)
7
VERTICAL FLUE
Vertical Flue Terminal
242802
1
Vertical Flue Adaptor
5106888
See Section 7.12 for more flue option details
Integral Twin Channel Timer
5117696
8
11
Fig. 6
Fig. 4
10
7
© Baxi Heating UK Ltd 2011
3.0 Boiler Operation
3.1
Boiler Operation
Mains On.
Condensate Pump will
operate as necessary (3.1.9)
1. Switched Live On: When switched live is supplied to
the boiler and the flow temperature is less than the set
point the sequence below commences.
Flow
temperature less
than set point ?
2. Flow Switch: After 10 seconds if the flow switch has
made then fan pre-purge occurs. After 10 seconds if
the flow switch has not made then anti-cycle occurs.
3. Fan Pre-Purge: The flow switch is made and the fan
is on while the spark generator and gas valve are off.
After 5 seconds ignition occurs.
YES
System Pump
Running and Flow
switch made ?
NO
4. Ignition: The flow switch is made, fan, spark
generator and gas valve are on. If a flame is detected
then burner on occurs. If a flame is not detected within
5 seconds and less than 5 ignition attempts have been
made then fan purge occurs. If a flame is not detected
within 5 seconds and 5 ignition attempts have been
made then ignition lockout occurs.
YES
Ignition done
and less than 5
attempts made ?
YES
5 second
Fan Pre-Purge.
5. Burner On: The flow switch is made, fan and gas
valve are on while the spark generator is off. Flow
temperature is controlled by varying the fan speed (and
thereby the gas rate) to achieve optimum operation. If
the flow temperature is greater than the set point or
the TRVs all shut down then fan post purge occurs.
5 second
Ignition Period.
6. Fan Post Purge: The fan is on while the spark
generator and gas valve are off. After 5 seconds if the
TRVs are shut down then anti-cycle occurs.
Flame Detected ?
Ignition done and
5 attempts made ?
7. Anti-cycle: The fan, spark generator and gas valve
YES
are off.
Burner On.
YES
8. Ignition Lockout: The fan, spark generator and gas
valve are off. The boiler can only be reset by manually
using the reset button.
All TRVs
shut or Flow temperature
greater than set point ?
Ignition
Lockout.
9. Condensate Pump: Condensate accumulates in a
reservoir within the pump assembly. The pump may
run at any time, independent of boiler operation, to
discharge the condensate to drain.
YES
5 second
Fan Post Purge.
YES
All TRVs
shut down ?
3 minute
Anti-cycle.
8
© Baxi Heating UK Ltd 2011
4.0 Technical Data
Appliance Type
C13
C33
Horizontal
Electrical Supply
230V~ 50Hz
Flue Terminal
Dimensions
Diameter - 110mm
Projection - 150mm
The boiler must be connected to an earthed
supply. A permanent and switched live are
required. The boiler has a 4 wire connection.
Appliance Category
CAT I
2H
Heat Input (Q)(Gross)
Max
33.76
Min
Connections
Gas Supply
Central Heating Flow
Central Heating Return
Condensate Drain (Pump)
Power Consumption
80W
-
-
-
-
15mm
28mm
28mm
10mm o.d.
kW
10.3
External Fuse Rating
3A
Heat Output (P)
(Non Condensing 70° C Mean Water Temp)
Internal Fuse Rating (BS 4265)
Max
Min
Outercase Dimensions
Casing Height
Casing Width
Fuse
3.15 AT (PCB)
IPXX
kW
30.18
9.2
-
-
-
850mm
390mm
520mm
Electrical Protection
Heat Output (P)
Casing Depth
(Condensing 40° C Mean Water Temp)
Max
Water Content
Min
Minimum Clearances
litres
2.6
(For unventilated compartments see Section 7.2)
kW
32.61
10.0
Both Sides
Above Casing
Above Casing
Under fixed worktop -
(It is recommended that any
worktop is removable)
Front (For Servicing)
Front (In Operation)
-
-
5mm
15mm
Static Head
max
Max Gas Rate (2H - G20 - 20mbar)
(After 10 Mins)
30 metres
1 metre
min
kW Input
m3/hr
33.76
3.4
Low Head
0.2m min
-
-
-
25mm
500mm
5mm
Inlet Pressure at Gas Valve (Natural Gas)
System Detail
Fully pumped open vented & sealed systems.
No bypass required.
Min
18.1 mbar
Max
22.5 mbar
Weights
kg
(see Section 10.1)
Packaged Boiler Carton
Packaged Flue Kit
Installation Lift Weight
Installed Weight (dry)
-
-
-
-
49.5
3.6
37.5
44.5
Controls
Injector (Natural Gas)
boiler thermostat, safety thermostat,
flow switch, electronic flame sensing,
temperature protection thermostat &
condensate blockage and level sensors
Diameter
6.5mm
0.004
CO/CO2 Ratio
Recommended System
Temperature Drop
Condensing
NO Class
x
5
Boiler Flow Temperature (adjustable)
20°C
55° C to 78° C (± 5° C)
Condensate Pump
Head
3 metres
Flow Rate
Connection
1.8 l/min
10mm o.d. (pipe supplied)
Boiler Hydraulic Resistance Chart
SEDBUK Declaration
91
83
75
66
58
50
42
33
25
17
8
220
200
180
160
140
120
100
80
SAP 2005 Seasonal Efficiency
model is 90.9%
This value is used in the UK Government’s Standard
Assessment Procedure (SAP) for energy rating of
dwellings. The test data from which it has been
calculated has been certified by 0087.
60
40
20
0
10
20
30
40
Water Flow Rate (litres/min)
9
© Baxi Heating UK Ltd 2011
5.0 Dimensions and Fixings
DIMENSIONS
A 850mm
At least
1.5°
B 520mm
C 390mm
A
D 125mm Ø Min.
E 175mm
F 150mm
B
C
D
The 1.5° fall provided by the elbow
is to allow condensate to run back to
the boiler, for discharge through the
condensate disposal system.
Flue Ø 110mm
Fig. 7
F
E
SIDE FLUE (left and right)
For every 1m of horizontal flue
length, the clearance above the top
of the flue elbow should be 27.5mm
to incorporate the 1.5° fall in the flue
from the terminal to the elbow. It is
especially important to consider
this when fitting the boiler under a
work top !
Y
X
At least
1.5°
Flue length (Y)
up to 1m
1m - 2m
Clearance (X)
27.5mm
55mm
2m - 3m
82.5mm
3m - 4m
110mm
Fig. 8
10
© Baxi Heating UK Ltd 2011
6.0 System Details
6.1
Water Circulating Systems
1. The boiler is suitable for use with open vent fully
pumped systems and sealed systems .
The following conditions should be observed on all
systems:
• The static head must not exceed 30m of water.
• The boiler must not be used with a direct cylinder.
• Drain cocks should be fitted to all system low points.
• All gas and water pipes and electrical wiring must be
installed in a way which would not restrict the servicing
of the boiler.
• Position isolating valves as close to circulating pump as
possible.
6.2
Treatment of Water Circulating
Systems
1. All recirculatory water systems will be subject to
corrosion unless they are flushed and an appropriate
water treatment is applied. To prevent this, follow the
guidelines given in BS 7593 “Treatment of Water in
Domestic Hot Water Central Heating Systems” and the
treatment manufacturers instructions.
2. Treatment must involve the use of a proprietary
cleanser, such as Sentinel X300 or X400, or Fernox F3
and an inhibitor such as Sentinel X100 or Fernox MB-1.
3. Full instructions are supplied with the products, for
further information contact Sentinel (0800 389 4670) or
Fernox (0870 870 0362).
Failure to flush and add inhibitor to the system will
invalidate the appliance warranty.
4. It is important to check the inhibitor concentration after
installation, system modification and at every service in
accordance with the inhibitor manufacturer’s instructions.
(Test kits are available from inhibitor stockists.)
5. For information or advice regarding any of the above
contact Technical Enquiries 0844 871 1555.
11
© Baxi Heating UK Ltd 2011
Boiler Air
Vent
Copper
0.5m
6.0 System Details
Copper
0.5m
Flow
6.3
Pipework
Boiler
Return
Copper
1m
1. The sizes of flow and return pipes from the boiler
should be determined by normal methods, according to
the requirements of the system.
Fig. 9
2. The connection tails for the boiler are 28mm diameter.
The 28mm section of the tails can be cut back to 22mm if
required.
22mm
Open Vent
45°
3. The flow & return tails are push - fit ‘O’ ring
and clip connections within the boiler case.
1000mm
Min
15mm
Cold
Feed
400mm
Min Head
Boiler Air
Vent
4. A 20 °C drop in temperature across the system is
recommended for condensing boilers. Existing radiators
may be oversized and so allow this, but where radiator
sizing is marginal it may be advisable to retain a system
temperature drop of 11°C.
150mm
Max
Boiler
Pump
5. In systems using non-metallic pipework it is necessary
to use copper pipe for the boiler Flow and Return. The
copper must extend at least 1 metre from the boiler and
include any branches (Fig. 9).
Flow
Return
Typical Low Head Installation
Fig. 10
6. This boiler does not require a bypass.
6.4
Low Head Installation
22mm
Open Vent
45°
1. Using a close couple arrangement the minimum head is
as shown in the diagrams (Figs. 10 & 11) subject to the
following conditions:
Boiler Air
Vent
15mm
Cold
Feed
400mm
Min Head
1000mm
Min
a) The pump being adjusted to give a 20°C drop across
the boiler.
b) The pump must be fitted on the flow.
c) The pump must be fitted in accordance with the
pump manufacturer's instructions.
Boiler
150mm
Max
d) The open vent pipe must be taken up from a tee in a
horizontal section of the flow pipe.
Pump
Flow
Return
2. For heads below 400mm then an alternative utilising a
combined vent and feed pipe may be connected (Fig. 12).
This must be a minimum of 22mm diameter. It is
recommended that an air separator is fitted when using a
combined feed and vent pipe.
If Conditions Require,
This System Possible
Fig. 11
6.5
Air Vents
22mm
Feed & Vent
Pipe
For correct operation of the flow switch the boiler
and system MUST be completely vented.
200mm
Min
Boiler Air
Vent
1. A manual air vent is fitted on the flow pipe, to enable
complete venting of the boiler. The pipe access panel
must be removed to do this.
Air
Separator
2. Additional vents should be fitted at suitable points on
the system as required.
Boiler
Pump
Flow
Return
Fig. 12
Alternative Low Head Installation
12
© Baxi Heating UK Ltd 2011
Key to colours
b
-
-
-
-
-
-
Blue
6.0 System Details
br
w
o
Brown
White
Orange
Grey
6.6
System Controls & Wiring
gr
g/y
Green/Yellow
This boiler requires a permanent live for
operation of the condensate pump and frost
protection.
230V
50Hz
1. To comply with Part L1 of the Building Regulations the
heating system into which the boiler is installed should
include the following:
L
N
E
b
Y Plan
Diverter
Valve
g/y
w
Cylinder
Stat
gr
a) zone controls
1
o
Room
Stat
b) timing controls
C
2
c) boiler control interlocks
2. Such a system needs to be fully pumped and must
provide independent temperature and time control to
both the heating and hot water circuits and have a boiler
and system pump interlock.
S/L
E
N
P/L
System Control
Wiring Centre
Boiler Connection
(4 Core Wire)
Timer
3. The boiler should be controlled so that it operates on
demand only. Where it is proposed to effect control by
thermostatic radiator valves a room thermostat should
also be provided to switch off the boiler when there is
no demand for heating.
L
N
CH on
HW on
HW off
N E
L
Pump
Y Plan, Room Thermostat System, CH Interlocked By Room Thermostat,
DHW Interlocked By Cylinder Thermostat
At least the Radiator(s) near the Room Thermostat not TRV’d
Pump run from Switched Live
gr
230V
b
gr
50Hz
L
N
E
Motor
Motor
b
br
o
S Plan
Valve
S Plan
Valve
br
g/y
g/y
Cylinder
Stat
o
Room
Stat
S/L
E
N
P/L
System Control
Wiring Centre
Boiler Connection
(4 Core Wire)
Timer
L
N
CH on
HW on
N E
L
Pump
S Plan, Room Thermostat System, CH Interlocked By Room Thermostat,
DHW Interlocked By Cylinder Thermostat
At least the Radiator(s) near the Room Thermostat not TRV’d
Pump run from Switched Live
13
© Baxi Heating UK Ltd 2011
6.0 System Details
3 Litre
Top Up Bottle
(if required)
Air
Vent
6.7
Sealed Systems (Fig. 13)
1. SAFETY VALVE - A safety valve complying with the
requirements of BS 6750 Part 1 must be fitted close to
the boiler on the flow pipe by means of a horizontal or
vertically upward connection with no intervening valve
or restrictions and should be positioned to facilitate
testing. The valve should be pre-set and non-adjustable
to operate at a pressure of 3 bar (45 Ibf/in2). It must be
arranged to discharge any water or steam through a pipe
to a safe outlet position.
Filling
Point
Pressure
Gauge
Safety
Valve
Pump
Radiator
Circuit
Expansion
Vessel
2. PRESSURE GAUGE - A pressure gauge of minimum
range 0-4 bar (0-60 Ibf/in2) with a fill pressure indicator
must be fitted to the system, preferably at the same
point as the expansion vessel in an easily visible position.
Boiler
System Drains at
Low Point
Max Boiler Flow
Temp = 82° C
3. EXPANSION VESSEL - An expansion vessel
complying with the requirements of BS 4814 must be
fitted to the system by means of a connection close to
the inlet side of the circulating pump in accordance with
the manufacturers instructions, the connecting pipe being
unrestricted and not less than 15mm (1/2 in) nominal size.
The volume of the vessel should be suitable for the
system water content and the nitrogen or air charge
pressure should not be less than the system static head
(See Table. 1).
Fig. 13
Method of determining minimum expansion
vessel volume for sealed systems.
Multiply Total
Vessel Charge
Pressure (Bar)
Initial System
Pressure (Bar)
Water Content Of
System By (Litres)
Further details of sealed system design can be obtained
from BS 5449 and the British Gas publication entitled
'Specifications for Domestic Wet Central Heating
Systems'.
0.5
1.0
1.5
2.0
0.067
0.112
0.207
0.441
0.5
1.0
1.5
4. FILLING POINT - A filling point connection on the
central heating return pipework must be provided to
facilitate initial filling and pressurising and also any
subsequent water loss replacement / refilling. The sealed
primary circuits may be filled or replenished by means of
a temporary connection between the primary circuit and
a supply pipe provided a ‘Listed’ double check valve or
some other no less effective backflow prevention device
is permanently connected at the inlet to the circuit and
the temporary connection is removed after use. The
filling method adopted must be in accordance with all
relevant water supply regulations and use approved
equipment.
1.0
1.5
2.0
0.087
0.152
0.330
1.5
2.0
0.125
0.265
Example :- System Volume = 75 litres
Vessel Charge Pressure = 1.0 bar
Initial System Pressure = 1.5 bar
Then :- 75 x 0.152 = 11.4 litres
Expansion Vessel Volume
Table. 1
Your attention is drawn to, for GB: Guidance G24.2 and
recommendation R24.2 of the Water Regulations Guide.
for IE: the current edition of I.S. 813 “Domestic Gas
Installations”.
NOTE
Where a vessel of the calculated size is not obtainable then
the next available larger size should be used.
5. MAKE UP SYSTEM - A method of replacing water
lost from the system should be provided either by
means of a make up vessel of not more than 3 litres (5
pints) capacity, mounted above the highest point of the
system, or by re-pressurisation of the system.
6. VENTING - A method of venting the system during
filling and commissioning must be provided by fitting
automatic air vents or by venting manually.
Double
Check
Valve
7. HOT WATER STORAGE - The hot water storage
vessel must be of the indirect coil type.
Stop
Valve
Stop
Valve
8. COMPONENTS - All components used in the system
must be suitable for operation at 110°C (230°F) and at
the pressure allowed by the safety valve.
Mains
Inlet
Temporary
Hose
CH
Return
Fig. 14
14
© Baxi Heating UK Ltd 2011
7.0 Site Requirements
7.1
Location
NOTE: Due to the high efficiency of the boiler a
plume of water vapour will be discharged from the
flue. This should be taken into account when siting
the flue terminal.
1. The boiler must be fitted on a suitable flat and level
surface capable of supporting the weight. Any wall behind
the boiler must be at 90° to the floor to allow case top
cover to fit correctly.
Zone 2
Window
2. The flue must pass through an outside wall or roof and
discharge to atmosphere in a position permitting
satisfactory removal of combustion products and
providing an adequate air supply.
Recess
Zone 1
Zone 0
Zone 2
3. The boiler should be fitted within the building unless
otherwise protected by a suitable enclosure i.e. garage or
outhouse.
0.6 m
Window
Recess
4. The boiler incorporates a frost protection device. This
will only protect the boiler. To ensure protection of the
system pipework and components it is recommended to
incorporate an appropriate device within the system
controls.
Zone 2
5. If the boiler is fitted in a room containing a bath or
shower, it can only be fitted in Zone 3, (Figs. A & B
shows zone dimensions for a bathtub. For other
examples refer to the Current I.E.E. Wiring Regulations).
Reference must be made to the relevant requirements:-
In GB this is the current I.E.E. Wiring Regulations and
Building Regulations.
Fig. A
In GB Only
Ceiling
Window Recess
Zone 2
Outside Zones
In IE reference should be made to the current edition of
I.S. 813 “Domestic Gas Installations” and the current
ETCI rules.
6. If the boiler is to be fitted into a building of timber
frame construction then reference must be made to the
current edition of Institute of Gas Engineers Publication
IGE/UP/7 (Gas Installations in Timber Framed Housing).
2.25 m
Zone 1
Zone 0
Zone 2
0.6 m
7.2
Compartment
1. Where the boiler is installed in a cupboard or
compartment, no air vents are required for cooling
purposes providing that the minimum dimensions below
are maintained.
Fig. B
In GB Only
Width
Height
Depth
400mm
875mm
525mm
2. Any compartment should be large enough to house
the boiler only.
15
© Baxi Heating UK Ltd 2011
7.0 Site Requirements
5mm Min
5mm Min
390mm
7.3
Clearances (Figs. 15 &16)
15mm Min
1. These dimensions include the necessary clearances
around the boiler for case removal, spanner access and air
movement. Additional clearances may be required for the
passage of pipes around local obstructions such as joists
running parallel to the front face of the boiler. For side flue
installations also See Section 8.1, Figs. 20 & 21.
(25mm if under
non removable
worktop)
2. It is recommended that any worktop is removable for
servicing access.
7.4
Gas Supply
850mm
1. Check that the information concerning the state of
adjustment given on the data plate is compatible with local
supply conditions.
2. The gas installation should be in accordance with the
relevant standards. In GB this is BS 6891. In IE this is the
current edition of I.S. 813 “Domestic Gas Installations”.
3. The connection to the boiler is a 15mm tail on the gas
service cock. The tail protrudes through the boiler rear
panel and is protected by a transit bracket which may be
removed to aid connection.
Fig. 15
4. Ensure that the pipework from the meter to the boiler
is of adequate size. (If the boiler is further than 3 metres
from the Gas Meter 22mm pipe should be used). Do not
use pipes of a smaller diameter than the boiler gas
connection.
7.5
Electrical Supply
1. External wiring must be correctly earthed, polarised and
in accordance with relevant regulations/rules. In GB this is
the current I.E.E. Wiring Regulations. In IE reference
should be made to the current edition of ETCI rules.
2. The mains supply is 230V ~ 50Hz fused at 3A.
500mm Min
NOTE: “The method of connection to the electricity
supply must facilitate complete electrical isolation of the
appliance and system”.
For Servicing
Purposes
Connection may be via a fused double-pole isolator with a
contact separation of at least 3mm in all poles, which must
be in an accessible position to the user and serve the
boiler and system controls only.
There is no method of isolating the boiler at the user
interface.
3. Four core cable is required to supply the boiler as a
permanent live is necessary for the operation of the
condensate pump and frost protection.
520mm
5mm Min
Fig. 16
In Operation
16
© Baxi Heating UK Ltd 2011
7.0 Site Requirements
Condensate Pump Flow Graph
7.6
Condensate Drain - General
Failure to install the condensate discharge pipework
correctly will affect the reliable operation of the boiler.
4
3
2
1
1. Ensure the discharge of condensate complies with any
national or local regulations in force.
BS 6798 & Part H1 of the Building Regulations give further
guidance.
2. If any further drain pipe is required (additional to that supplied
with the boiler), it should be run in a proprietary material
e.g. PVC, PVC-U, ABS, PVC-C or PP.
0
3.5
2.5
Flow (l/min)
4
1.5
3
2
3. Metal pipework is NOT suitable for use in condensate
discharge systems.
4. Any pipe fitted externally must be kept as short as possible to
minimise the potential of freezing and must be insulated using
waterproof material.
Min. radius 100mm
Point ‘A’
5. When discharging condensate into a soil stack or waste pipe
the effects of existing plumbing must be considered.
Gravity Drain min. fall 3°
7.7
Condensate Disposal
Note: The point of discharge from
1. This boiler incorporates an automatic pumped condensate
system. See the graph opposite for available pump flow rates.
the pumped length of condensate
pipe (point ‘A’) must not be below
the level of the pump, whether
discharging direct into a drain or
into an additional gravity drain.
Max. Head
3 metres
2. 3.5 metres of flexible 10mm PVC pipe are supplied with the
boiler. 0.5 metres of this length remains coiled within the boiler
to allow removal of the pump assembly. This must not be
uncoiled to provide extra length.
Boiler
3. A fitting and securing clip (Fig. B) to accept the 10mm PVC
pipe and connect to 21.5mm overflow pipe is also supplied.
Alternative Horizontal
Discharge
4. The 10mm pipe can be routed to a maximum of 3 metres
vertically and then discharge via gravity or be routed horizontally
(Fig. A). A combination of vertical and horizontal runs is
permissible.
Fig. A
5. The pipe must be supported, either using suitably spaced clips
or run within larger diameter pipe. When using clips take care
not to deform the pipe.
10mm PVC Pipe
(8.5mm I.D.)
6. When routing the pipe through a wall it must be suitably
sleeved. Also the pipe must not be exposed to sources of heat,
and should be protected in locations where it may be damaged.
Securing Clip
8.5mm Ø O.D.
7. The pipe should be routed so that any sharp bends, dips and
loops are avoided. A minimum radius of 100mm is
recommended for any bends. No slope is necessary and air
breaks are not required on the pumped part of the condensate
run.
8. If the boiler is fitted in an unheated location the entire length
of condensate pipe should be treated as external, and run within
insulated larger diameter pipe.
21.5mm Ø O.D. to fit
Overflow Pipe
Condensate Pipe
Direct Connect
Fitting
Fig. B
17
© Baxi Heating UK Ltd 2011
7.0 Site Requirement
Termination via internal discharge branch e.g
sink waste - downstream
7.7
Condensate Disposal (cont.)
Pipe must terminate
Direct Connect Fitting
above water level but
below surrounding surface
9. Ensure that the condensate can discharge freely (without
blockage or restriction of the pipe) into the drain.
Sink
10. Examples are shown of condensate pipe methods of
termination:-
Branch of Tee to be
± 10° from vertical
i) via an internal discharge branch
(e.g. sink waste) - Fig. C.
10°
10°
ii) to an internal or external soil and vent pipe -
Fig. D.
From Boiler
Fig. C
iii) to a drain or gully - Fig. E. Ensure that the
condensate can discharge freely (without
blockage or restriction of the pipe) into the
drain.
iv) to a soakaway - Fig. F.
Termination to an internal soil and vent pipe
Direct Connect Fitting
From Boiler
Min. 450mm
Fig. D
Termination to a drain or gully
Pipe must terminate above
water level but below
surrounding surface
From Boiler
Fig. E
Termination to a purpose made
soak-away
500mm Min
Holes in the soak-away must
face away from the building
From Boiler
Fig. F
18
© Baxi Heating UK Ltd 2011
7.0 Site Requirements
Terminal Position with Minimum Distance (Fig. 17)
(mm)
a
A
Directly below an opening, air brick, opening
windows, etc.
Above an opening, air brick, opening window etc.
Horizontally to an opening, air brick, opening window etc.
Below gutters, soil pipes or drain pipes.
Below eaves.
300
300
300
25
7.8
Flue
a
a
B
C
NOTE: Due to the high efficiency of the boiler a plume of
water vapour will be discharged from the flue. This should
be taken into account when siting the flue terminal.
D
E
F
G
H
I
25
Below balconies or car port roof.
From a vertical drain pipe or soil pipe.
25
1. The following guidelines indicate the general requirements
for siting balanced flue terminals.
For GB recommendations are given in BS 5440 Pt.1.
For IE recommendations are given in the current edition of I.S.
813 “Domestic Gas Installations”.
25
115
300
600
1200
600
(i)
(ii)
(i)
(ii)
25
From an internal or external
corner.
Above ground, roof or balcony level.
J
K
From a surface or boundary line facing a terminal.
From a terminal facing a terminal (Horizontal flue).
From a terminal facing a terminal (Vertical flue).
From an opening in carport (e.g. door, window)
into the dwelling.
L
2. If the terminal discharges onto a pathway or passageway,
check that combustion products will not cause a nuisance and
that the terminal will not obstruct the passageway.
1200
1500
300
M
N
Vertically from a terminal on the same wall.
Horizontally from a terminal on the same wall.
3. When siting the flue take into consideration the effect the
plume of water vapour may have on neighbours .
R
S
T
U
From adjacent wall to flue (vertical only).
From an adjacent opening window (vertical only).
Adjacent to windows or openings on pitched and flat roofs
Below windows or openings on pitched roofs
300
1000
600
4. Adjacent surfaces close to the flue terminal may need
protection from the effects of condensation. Alternatively a flue
deflector kit (part no. 248167) is available.
2000
Table. 2
a
5. For installation of the flue into an internal corner at the
25mm dimension the flue plume deflector kit (part no. 248167)
must be fitted.
In addition, the terminal should be no nearer than 150 mm to an
opening in the building fabric formed for the purpose of accommodating
a built-in element such as a window frame. See BS 5440 Pt. 1.
6. * Reduction to the boundary is possible down to 25mm but
the flue plume deflector kit (part no. 248167) must be fitted.
NOTE: The distance from a fanned draught boiler terminal
installed parallel to a boundary may not be less than 300mm
in accordance with the diagram below, unless the flue deflector
kit is used (see 7.8.6 opposite)
*
7. If a terminal is less than 2 metres above a balcony, above
ground or above a flat roof to which people have access, then
a suitable terminal guard must be provided.
300 min
Terminal
Assembly
*
8. If required a suitable terminal guard (part no. 248484) is
available from Potterton for use with the flue deflector. See
also Section 8.8.
9. For fitting under low soffits and eaves the Plume
Displacement Kit or Flue Deflector Kit is recommended.
TopView Rear Flue
IMPORTANT:
• Only ONE 25mm clearance is allowed per installation.
• Under car ports we recommend the use of the plume
displacement kit.
Fig. 16a
Property Boundary Line
• The terminal position must ensure the safe and
nuisance - free dispersal of combustion products.
IMPORTANT: If fitting a Plume
Displacement Flue Kit, the air inlet
must be a minimum of 150mm from
any opening windows or doors.
T
J,K
U
Plume
Displacement Kit
N
R
D
E
A
M
I
C
I
I
I
S
F
F
B
J,K
L
A
A
I
Air Inlet
G
H
H
Likely flue positions requiring
a flue terminal guard
Fig. 17
Opening Window
or Door
150mm
MIN.
Fig. 17a
19
© Baxi Heating UK Ltd 2011
8.0 Flue Options
8.1
Horizontal Flue Systems
Only a flue approved with the Potterton Gold FSB HE 30
can be used.
(ii)
(i)
Concentric
The maximum equivalent lengths are 4m (horizontal) or
(vertical). Their lengths exclude the standard elbow and
flue/terminal assembly (horizontal) and terminal assembly
(vertical).
Horizontal
Flue System Examples
Any additional “in line” bends in the flue system must be
taken into consideration. Their equivalent lengths are:
Concentric Pipes:
45° bend
93° bend
0.5 m
1.0 m
(ii)
(i)
NOTE: Flue length is measured from point (i) to (ii) as
shown.
Plume Displacement 70/110 dia Kit
1M Extensions, 45° & 93° bends
are also available - see Section 9.0
IMPORTANT: All flue systems must be securely
supported at least once every metre. Suitable pipe
supports are available as accessories.
NOTE: Horizontal flue pipes should always be installed with a 1.5° fall from the
terminal to allow condensate to run back to the boiler.
This bend is equivalent to
0.5 metre
B
A
(ii)
This bend is equivalent to
0.5 metre
(i)
Total equivalent length =
A+B+2x45°Bends
20
© Baxi Heating UK Ltd 2011
Vertical Flue System
Examples (Twin Pipe)
8.0 Flue Options
8.2
Twin & Vertical Flue Systems
Concentric
The maximum equivalent lengths are 4m (vertical). Their
lengths exclude the standard elbow and terminal assembly
(vertical).
(ii)
(i)
Twin Flue
The total maximum equivalent flue length is 150m.
NOTE: Each 1m of flue duct should be calculated as 2m.
Any additional “in line” bends in the flue system must be
taken into consideration. Their equivalent lengths are:
Concentric Pipes:
135° bend
93° bend
0.5 m
1.0 m
Twin Flue Pipe:
135° bend (air duct)
135° bend (flue duct)
90° bend (air duct)
90° bend (flue duct)
1.3 m
2.6 m
4.8 m
9.6 m
(ii)
(i)
IMPORTANT: All flue systems must be securely
supported at least once every metre. Suitable pipe
supports are available as accessories.
Vertical Flue
System Examples
Total Equivalent Length =
A+B+C+1x90°Bend
Roof
Terminal
All vertical and angled runs must be included,
measured from the boiler adaptor (point X) to the
joint with the flue terminal (point Y). One 91.5°
bend or two 135° bends can be included without
reduction of the flue length.
The total equivalent length
for this example is
17.2 + 34.4 = 51.6 metres.
If further elbows are required the flue length must
be reduced by the following amounts:-
(ii)
1 metre for each 91.5° bend
0.5 metre for each 135° bend
AIR DUCT
No of
C
Equivalent
Sub total
Length Value
fittings/pipes
B
1m extension
135°bend
5
2
2
5.0m
2.6m
9.6m
1m
1.3m
4.8m
91.5°bend
This bend is equivalent to
1 metre
Equivalent Length Air Duct = 17.2m
FLUE DUCT
A
No of
Sub total
Equivalent
Length Value
fittings/pipes
(i)
1m extension
135°bend
5
2
2
10.0m
5.2m
2m
2.6m
91.5°bend
19.2m
9.6m
Equivalent Length Flue Duct = 34.4m
21
© Baxi Heating UK Ltd 2011
8.0 Flue Options
8.3
Flue Accessories
Key Accessory
FLUE GROUP B
Concentric Flue System 110mm diameter
Size
Code No
B
A1
A
Horizontal Flue Terminal
Horizontal Flue Terminal (incl elbow)
850mm
243013BAX
236921
A1
A
B
Flue Extension
1000mm 241695
500mm
250mm
93°
135°
110mm
241694
241692
241687
241689
243014BAX
5106888
248167
C
D
U
T
S
Flue Bend
Flue Bend (pair)
Pipe Support
Vertical Flue Boiler Adaptor
Flue Terminal Deflector
E
T
K
FLUE GROUP P
Twin Flue System 80mm diameter
E
Flue Extension (pair)
1000mm 246137
500mm
250mm
90°
246136
246135
5121560
5121561
242757
5111081
F
G
J
Flue Bend (pair)
Flue Bend (2 pair)
Vertical Flue Boiler Adaptor Kit
Pipe Support (pair)
135°
S
W
80mm
D
C
FLUE GROUP B,P
Vertical Flue Kits
K
L
M
N
Vertical Flue Terminal
242802
243015
243131
243016BAX
Pitched Roof Flashing
Roof Cover Plate
Flat Roof Flashing
25°/50°
G
F
U,W
M
L
N
J
22
© Baxi Heating UK Ltd 2011
8.0 Flue Options
For Vertical Flues
8.4
For Vertical Flue Systems
Vertical Flue
Adaptor
1. Undo the screws securing the blanking plate to the
boiler top panel. Discard the plate.
Gasket
2. Fix the vertical adaptor and gasket to the top panel with
the previously removed screws.
Blank Plate
8.5
For Twin Flue Systems
1. Undo the screws securing the blanking plate to the
boiler top panel. Discard the plate.
2. Fix both the air and flue adaptors with their gaskets
onto the boiler top panel. Secure with screws.
For Twin Flues
Air Duct
Adaptor
Flue Duct
Adaptor
Gasket
Gasket
23
© Baxi Heating UK Ltd 2011
8.0 Flue Options
8.6
For Roof Terminals
1. In the case of a pitched roof 25 - 50 degrees, position
the lead tile to replace/flash over existing roof tiling. Make
an aperture in the roof suitable for the lower tube of the
roof terminal and ensure the integrity of the roof cover is
maintained. The adjustable plastic collar can either be
positioned on the lead tile or the lower tube of the roof
terminal prior to the final positioning of the vertical flue
through the tile. Check the collar is correctly located to suit
required roof pitch (either 25° to 38° or 37° to 50°). From
inside the roof adjust the flue to a vertical position and
secure to the roof structure with the clamp supplied.
Approx
1425mm
2. For flat roof installations the aluminium flashing must be
incorporated into the roof covering and the appropriate
aperture made in the roof decking. The vertical flue is
lowered onto the flashing making sure the collar of the flue
locates securely with the flashing. (A mastic seal may be
necessary). From inside the roof, adjust the flue to a vertical
position and secure to the roof structure with the clamp
supplied.
Cut the same
amount off the
Air Duct &
Flue Duct
Air Duct
Flue Duct
Push Fit Adaptor
IMPORTANT: If the boiler is not fitted immediately
after the flue system, temporary precautions must be
taken to prevent rain entry into the room of installation.
Any precautionary measures must be removed prior to
commissioning the boiler.
8.7
Flue Dimensions
The standard horizontal flue kit allows for flue lengths
between 270mm (105/8”) and 800mm (32”) from elbow to
terminal (Fig. 18).
The maximum permissible equivalent flue length is: 4
Flue Deflector
metres.
NOTE: Each additional 45° of flue bend will account
for an equivalent flue length of 0.5m.
Fig. 18
eg. 45° = 0.5m,
90° = 2 x 45° = 1m etc.
8.8
Terminal Guard (Fig. 19)
Fig. 18a
1. When codes of practice dictate the use of terminal
guards, they can be obtained from most Plumbers’ and
Builders’ Merchants.
2. When ordering a terminal guard, quote the appliance
model number.
3. The flue terminal guard should be positioned centrally
over the terminal and fixed as illustrated.
8.9
Flue Deflector (Fig. 18a)
1. If required, push the flue deflector over the terminal end
and rotate to the optimum angle for deflecting plume.
Secure the deflector to the terminal with screws provided.
Fig. 19
24
© Baxi Heating UK Ltd 2011
9.0 Plume Displacement
Plume Outlet (‘Peak’
MUST be Uppermost)
9.1
Plume Displacement Kit (P.D.K.)
Kit No 5121371
Content of kit
1
1
2
1
1
2
1
70/110 Concentric Flue
1m 70 Dia Exhaust Flue Pipe
Support Brackets
0.94 metre
93° Elbow/Plume Outlet Assembly
Flue Trim
“O” Rings
Elbow with Gasket
1. This kit is recommended for installations where the
condensate plume emitted from the flue may cause a nuisance
or affect the surroundings.
2. The terminal must be positioned outside the building with
the outlet connection upwards.
3. The 70Ø pipe connects to the outlet of the concentric
terminal assembly. The elbow/plume outlet must be fitted to
the end of the 70Ø pipe.
NOTE: The plume outlet must always be at least 45° to
the wall, with the ‘peak’ uppermost to prevent rain entry
(Figs. A & B), and be at least 2 metres above ground level.
It must be secured as shown in Fig. C.
The outlet must be positioned so that any condensate
plume is directed away from adjacent surfaces.
Fig. C
4. It is possible to reduce or increase (with the addition of
extensions) the length of either or both the 70/110 concentric
and 70Ø exhaust.
5. Standard concentric flue extension kits may be added
between the boiler elbow and the terminal assembly.
Outlet must be
at least 45° from
wall face
‘Peak’ MUST be
Uppermost
45°
45°
6. The minimum length of the concentric flue is 100mm when
measured from the edge of the boiler flue elbow. There is a
further 45mm engagement into the elbow.
IMPORTANT: The maximum equivalent length of
concentric flue is:- 4 metres
Additional elbows may be fitted in the concentric flue, but
the equivalent length must be reduced by 1 metre (93°
elbow) or 0.5 metres (45° elbow).
7. 70Ø 1 metre extensions (including support bracket), and
additional 93° & 45° elbows are available. Any additional 93°
& 45° elbows must be accounted for when calculating flue
lengths. 70Ø 93° elbows are equivalent to 3.5 metres of
straight length and 45° elbows to 1 metre.
500mm Min.
NOTE: Permitted positions of the plume outlet relative to
doors, windows etc. are the same as for conventional
concentric flues as detailed in the main Installation &
Servicing Instructions and BS5440 Pt. 1. It is NOT
necessary to fit a terminal guard over the air inlet or the
plume outlet.
Fig. A
Outlet Connection
upwards
Fig. B
25
© Baxi Heating UK Ltd 2011
30
28
26
24
22
20
30
28
26
24
22
20
9.0 Plume Displacement
9.2
Determining Permissible Lengths - P.D.K.
18
16
14
12
10
18
16
14
12
10
In the graph the solid line diagonal represents the
relationship between the concentric flue assembly (and any
extensions) and the 70Ø exhaust (and any extensions or
additional bends).
8
6
4
2
0
8
6
4
2
0
Example 1 - Not Permissible
If, for instance, a concentric length of 3.25 metres was
required and the 70Ø exhaust needed to be 10 metres the
graph shows that this combination would NOT be
permissible as the intersection point would be above the
solid diagonal line.
0
1
2
3
4
0
1
2
3
4
Concentric 70/110 Flue (metres)
Concentric 70/110 Flue (metres)
Example 1
Example 2
Flue Lengths - Not Permissible
Flue Lengths - OK
30
28
26
24
22
20
Example 2 - Flue Lengths OK
Where both lengths have been determined they can be
applied to the graph to check that the installation is
permissible. For example, if it was known that 2 metres of
concentric flue and 4 metres of 70Ø exhaust were required,
the values could be applied to the graph as shown in
Example 2.. As the point of intersection of the dotted lines is
below the solid diagonal line, the combination of lengths is
shown to be acceptable.
18
16
14
12
10
Example 3 - Flue Lengths OK
8
6
4
2
In the example shown, assume that the concentric part of
the flue needs to be 2 metres long. Find the position of ‘2’ on
the horizontal axis of the graph and then project upwards to
the solid diagonal line. This is represented by the vertical
thick dotted line. Where this dotted line intersects with the
solid diagonal line on the graph, project across to the vertical
axis. As can be seen this corresponds with 14 metres.
Therefore, the total equivalent length of the 70Ø exhaust
can be up to 14 metres. Any elbow equivalencies must be
accounted for i.e. 93° elbows are equal to 1 metre, each 45°
elbow to 0.5 metres.
0
0
1
2
3
4
Concentric 70/110 Flue (metres)
Example 3
Flue Lengths - OK
Support
Bracket
70Ø Exhaust
45° Elbow
Flue Length - Worked Example
X
In Fig. D opposite an additional 93° elbow and pair of 45°
elbows have been included in the 70Ø exhaust.
Also 3 straight extension pieces have been used.
93° Elbow
Y
1 metre Extension
To calculate total length:-
1 metre supplied in kit
Length of 70Ø supplied in kit =
3 x 1 metre Extensions =
1 x 93° Elbow =
1 metre
3 metres
1 metre
Concentric 70/110 Flue
(MUST be installed
horizontally)
2 x 45° Elbow =
1 metre (0.5 metres each)
Concentric Flue
Total 70Ø =
6 metres
After consulting the table in Example 3 it can be determined
that the concentric flue could be up to approximately 3.25
metres long.
Additional Accessories
A - 93° Elbow
B - 45° Elbow (Pair)
5117381
5117382
C - 1 metre 60Ø Extension 5117380
Fig. D
26
© Baxi Heating UK Ltd 2011
9.0 Plume Displacement
9.3
General Fitting Notes - P.D.K.
1. Cut a hole in the external wall which the horizontal
concentric flue assembly will pass through.
This section of the
flue MUST be
horizontal
2. When completed the terminal must be at least 2 metres
above ground level (Fig. E).
Min. 2 metres
3. Measure and cut to size the concentric assembly and any
extensions that are being used.
4. Insert the concentric assembly through the hole from
outside the building and mark the position of the flue trim
securing holes.
Min. 0.3 metres
5. Drill and plug the wall to accept the flue trim securing
screws, and re-insert the concentric assembly through the
wall.
6. Connect any extensions that are being used to the
concentric assembly. Engage the extension or concentric
assembly in the boiler flue elbow.
7. Fit the boiler flue elbow to the boiler top panel, ensuring
the gasket is in place (Fig. F).
Fig. E
Ensure that the concentric assembly is horizontal and that
the external air inlet is to the bottom. Any extensions
should fall back to the boiler.
8. Use suitable brackets to support the concentric assembly
and any extensions, and make good inside and outside.
Secure the flue trim to the wall.
9. The 70Ø exhaust can now be fitted to the spigot at the
terminal end.
10. If it is necessary to shorten the 70Ø exhaust or any of
the extensions, the excess material must be cut from the
plain end of the pipe.
Fig. F
11. Determine the position of the 70Ø exhaust and mark
on the wall a suitable position for the support bracket. Drill
and plug the wall. If extensions are being used, a support
bracket is supplied in each kit.
12. Engage the M6 threaded part of the mounting bolt in
the boss on the support bracket. Using the bracket for
leverage, screw the mounting bolt into the plugged hole
until the bracket is secure and level (Fig. G).
13. Slacken the two screws securing the retaining strap to
the bracket, and pivot the strap aside to allow fitting the
70Ø exhaust.
14. Complete the installation of the 70Ø exhaust, securing
in the brackets. Fit the 93° elbow and plume outlet. Ensure
the plume outlet is at least 45° to the wall and that the
‘peak’ is uppermost.
Fig. G
15. Continue with installation and commissioning of the
boiler.
27
© Baxi Heating UK Ltd 2011
9.0 Plume Displacement
Plume Outlet
9.3
General Fitting Notes - P.D.K. (cont.)
Elbow
16. For aesthetic purposes it is permissible to route the
70Ø exhaust in an enclosed box, but the air inlet and
plume outlet MUST remain in free air.
17. It is also possible to separate the plume outlet from
the 93° elbow to allow the flue to be installed as shown
in Fig. H.
18. When the plume outlet is positioned under a balcony
or other projection (Figs. I & J) it must protrude at least
200mm (it is not necessary to extend it further than this).
Fig. H
200mm Min.
Fig. I
200mm Min.
Fig. J
28
© Baxi Heating UK Ltd 2011
10.0 Installation
Example
2m
Edge of Boiler
125mm
Check Site Requirements before commencing.
EXAMPLE: If the boiler is 2 metres
away from corner of wall the flue
duct hole will be 55mm higher than
the horizontal side flue centre line.
This will maintain an approx. 1.5°
backfall to the boiler. It is especially
important to consider this when
fitting the boiler under a work top !
10.1
Initial Preparation & Installation
Example
V = 55mm
1. Remove the outer carton.
2. For the boiler to operate correctly it must be level
in both planes. Place the fixing template in the
proposed boiler position ensuring that it is level.
Horizontal
Side Flue
Centre Line
3. Mark the centre of the flue hole (rear exit).
For side exit: project the horizontal side flue centre
line into the corner of the room and along the wall to
where the flue hole will be drilled. (Fig. 20).
Centre
Hole
Wall Thickness
up to 227mm
Flue Hole ø
125mm core drill
150mm core drill
175mm core drill
The diagram (Fig. 21) shows the dimensions required
to ensure any horizontal flue is installed with the
correct fall to the boiler. Mark the offset (V) dimension
and if required, mark the position of the gas, water and
condensate pipes. Remove the template.
up to 750mm
up to 1200mm
Template
Fig. 20
4. Cut the hole for the flue (minimum diameter
125mm, see table (Fig. 20) for wall thicknesses and flue
hole diameters).
Backfall to the boiler, ie. 2m flue offset (V) position 55mm
Flue Duct Hole
OffsetV (mm)
13.5
27.5
55
82.5
110 (mm)
5. Complete any pipework and wiring that will be
inaccessible once the boiler is in position.
1.5°
V
6. Undo the securing screws and remove the facia,
front door panel and top panel (see Figs. 1 & 2 on
page 6). Remove the securing screw and disengage the
pipe access panel.
0.5
1.0
2.0
3.0
10.2
Making the Water Connections
4.0
(metres)
1. If desired the flow and return tails supplied with the
boiler can be fitted at this stage and secured with the
spring clips. The flow and return connections are
identified on the boiler rear panel. The flow pipe
incorporates a manual air vent.
Fig. 21
2. Note that the seal is made by use of an ‘O’ ring,
therefore some pipe movement will be evident even
though a water tight seal has been achieved. Excessive
force could result in damage to the connection.
3. Make all soldered joints before connecting the tails
to the boiler to avoid damaging the ‘O’ rings.
4. Refit the pipe access panel.
10.3
Making the Gas Connection
1. The connection to the boiler is a 15mm tail on the
gas service cock. The tail protrudes through the boiler
rear panel and is protected by a transit bracket which
may be removed to aid connection (see Fig. 22).
Flow
Tail
Hole for
Electrical
Cable
Return
Tail
2. If solder joints are being used for the gas connection,
remove the gas tap from the valve as excessive heat
may damage the ‘O’ ring seal.
Hole for
Transit
Bracket
Condensate
Drain Outlet
10.4
Priming the Condensate Trap
1. Using a funnel and tube, carefully pour
Gas
approximately 1 cupful (250ml) of tap water into the
flue products exhaust at the terminal or flue elbow
sampling point to ensure a seal is made in the trap.
Connection
Fig. 22
29
© Baxi Heating UK Ltd 2011
10.0 Installation
Wall Thickness
10.5
Fitting the Standard Flue
IMPORTANT: The flue should always be installed
with at least 1.5° fall from terminal to elbow, to
allow condensate to run back to the boiler.
At least
1.5°
1. The standard flue is suitable for lengths 270mm
minimum to 800mm maximum (measured from the
edge of the flue elbow outlet).
Rear Flue: maximum wall thickness - 575mm
Side Flue: maximum wall thickness - 535mm
2. For rear exit - measure the wall thickness
(Fig. 26) and to this dimension add 270mm. This
dimension to be known as (X).
i.e. (X) = wall thickness + 270
3. Take the flue and mark off (X) from the terminal end
as indicated in the diagram (Fig. 27).
4. For side exit - measure the distance from the edge
of the boiler case to the inner face of the wall (Fig. 26)
and to this dimension add the wall thickness + 280mm.
This dimension to be known as (Z).
i.e. (Z) = case to wall + wall thickness + 280
5. Take the flue and mark off (Z) from the terminal end
as indicated (Fig. 27).
Edge of Boiler Case to Wall
Wall Thickness
Before cutting check your dimensions !
6. The flue tubes are fixed together. Cut through both
tubes whilst resting the flue on the semi-circular packing
pieces. Deburr both tube ends.
Fig. 26
NOTE: When cutting ensure the cut does not
interfere with the inner flue support bracket
(Fig. 27a).
(Z) = Side Exit
(X) = Rear Exit
Waste
Flue
Fig. 27
Inner Flue Support Bracket
Fig. 27a
30
© Baxi Heating UK Ltd 2011
10.0 Installation
10.5
Fitting the Standard Flue (Cont)
Inner Flue Support Bracket
7. Ensure the inner flue support bracket is positioned
in the flue (Fig. 28).
8. Engage the flue into the flue elbow using soap
solution to ease the engagement, ensuring the flue
terminal is positioned as shown (Fig. 29).
Fig. 28
9. Place the gasket over the flue exit on the boiler.
10. Slide the flue assembly through the hole in the wall.
Flue
11. Engage the elbow on to the flue connection on top
of the boiler. Secure with the four screws supplied in
the kit.
12. Make good between the wall and air duct outside
the building ensuring the 3° drop between the terminal
and elbow.
Flue Elbow
13. The flue trim should be fitted once the installation
is complete and the flue secure (Fig. 30). Apply a
suitable mastic to the inside of the trim and press
against the wall finish, making sure the brickwork is
dust free and dry.
Fig. 29
14. If necessary fit a flue plume deflector kit and/or
terminal guard (see Sections 7.6 & 8.8).
Gasket
Fig. 30
Flue Trim
Shaded Areas indicate
Recommended Handling
Points
31
© Baxi Heating UK Ltd 2011
Min. radius 100mm
Point ‘A’
10.0 Installation
Gravity Drain min. fall 3°
Note: The point of discharge from
10.6
Making the Condensate Drain
Connection
the pumped length of condensate
pipe (point ‘A’) must not be below
the level of the pump, whether
discharging direct into a drain or
into an additional gravity drain.
Max. Head
3 metres
Boiler
1. 3.5 metres of flexible 10mm PVC pipe are supplied
with the boiler, ready connected to the pump. 0.5
metres of this length remains coiled within the boiler
to allow removal of the pump assembly. This must not
be uncoiled to provide extra length.
Alternative Horizontal
Discharge
2. A fitting and securing clip (Fig. B) to accept the
10mm PVC pipe and connect to 21.5mm overflow
pipe is also supplied. When using this fitting to connect
to a 21.5mm overflow tee piece the branch must be
vertical ± 10° (Fig. C).
Fig. A
10mm PVC Pipe
(8.5mm I.D.)
Condensate Pipe
Direct Connect
Fitting
3. Feed the pipe through the grommet in the rear
panel and connect to the drain system.
Securing Clip
4. The 10mm pipe can be routed to a maximum of 3
metres vertically and then discharge via gravity or be
routed horizontally (Fig. A). A combination of vertical
and horizontal runs is permissible.
8.5mm Ø O.D.
21.5mm Ø O.D. to fit
Overflow Pipe
Fig. B
5. The pipe must be supported, either using suitably
spaced clips or run within larger diameter pipe. When
using clips take care not to deform the pipe.
Termination via internal discharge branch e.g
sink waste - downstream
Pipe must terminate
Direct Connect Fitting
Branch of Tee to be
± 10° from vertical
above water level but
below surrounding surface
10°
10°
6. When routing the pipe through a wall it must be
suitably sleeved. Also the pipe must not be exposed to
sources of heat, and should be protected in locations
where it may be damaged.
Sink
7. The pipe should be routed so that any sharp bends,
dips and loops are avoided. A minimum radius of
100mm is recommended for any bends. No slope is
necessary and air breaks are not required on the
pumped part of the condensate run.
From Boiler
Fig. C
Termination to an internal soil and vent pipe
8. If the boiler is fitted in an unheated location the
entire length of condensate pipe should be treated as
external, and run within insulated larger diameter pipe.
Direct Connect Fitting
9. Ensure that the condensate can discharge freely
(without blockage or restriction of the pipe) into the
drain.
From Boiler
Min. 450mm
Fig. D
10. Examples are shown of condensate pipe methods
of termination:-
Termination to a drain or gully
i) via an internal discharge branch
(e.g. sink waste) - Fig. B.
Pipe must terminate above
water level but below
surrounding surface
ii) to an internal or external soil and vent
pipe - Fig. C.
Termination to a purpose made
soak-away
iii) to a drain or gully - Fig. D. Ensure that
the condensate can discharge freely
(without blockage or restriction of the
pipe) into the drain.
From Boiler
500mm Min
Fig. E
iv) to a soakaway - Fig. E.
From Boiler
Holes in the soak-
away must face away
from the building
Fig. F
32
© Baxi Heating UK Ltd 2011
10.0 Installation
10.7
Making The Electrical Connections
W ARN IN G: T his boile r m ust be e ar t he d
IMPORTANT: Four core cable is required to supply the
boiler as a permanent live is necessary for the operation
of the condensate pump and frost protection.
1. The electrical connections are on the right hand side of the
boiler. Depending upon the nature of the installation it may
be preferable to wire up to the boiler first before
manoeuvering into position.
2. Undo the two screws securing the cable clamp and place
to one side (Fig. 31).
3. Route the incoming electrical cable(s) from the system
control wiring centre through the grommet in rear of the
boiler and the grommet in the support bracket. This will
prevent damage to the cable(s).
4. Lay the cable through the cable clamp to gauge the length
of wire required when it is connected to the 4-way terminal
block.
5. Connect the (S/L), ( ), (N) and (P/L) wires to the
4-way terminal block (Fig. 33) and refit the cable clamp
(Fig. 31).
Fig. 31
Cable Clamp
INTEGRAL PROGRAMMER
If the optional integral programmer is being fitted it can be
done at this stage. Consult the instructions supplied in the
programmer kit.
Check the electrical installation for;
earth continuity, short circuits, resistance to earth, correct
polarity and fuse rating.
Fig. 32
4-way Terminal Block
Fig. 33
S/L
N
P/L
Wiring from System
Controls
S/L Switched Live
Earth
Neutral
N
Permanent Live
P/L
33
© Baxi Heating UK Ltd 2011
11.0 Electrical
11.1
Schematic Wiring Diagram
Condensate Removal System
Condensate Pump
Condensate
Level Switch
Condensate
Over-Level Switch
Fan
Overheat
Thermostat
Condensate
Trap
N
L
g/y
CH
Flow
Switch
bk
325Vdc
DC Fan
bk
Spark
Electrode Detection
Electrode
Flame
Flow
gy
Gas
Valve
Thermistor
w
Flow
Overheat
Thermostat
w
gy
gy
gy
bk
r
g/y
r
b
r
bk
br
r
w
b
g
br
w
g/y
op
PCB
b
br
Optional InternalTimer
g/y
o
Electrical
Filter
Earths not shown to aid
clarity of diagram
o
y
v
b
br
Boiler Connection
(4 Core Cable)
P/L
S/L
N
Key To Wiring Colours
b - Blue
r
- Red
bk - Black
w - White
br - Brown
gy - Grey
o - Orange
g - Green
g/y- Green/Yellow
op - Opaque
y - Yellow
v - Violet
34
© Baxi Heating UK Ltd 2011
11.0 Electrical
11.2
Illustrated Wiring Diagram
P/L
br
N
S/L
Flow
Thermistor
b
g/y
r
g/y
r
CH
Flow Switch
Electrical
Filter
g/y
br
Spark
Electrode
b
gy
Flame
Detection
Electrode
gy
o
Main
PCB
g/y
w
Layout of PCB Pins
op
CondensateTrap
w
br
g
r
bk
GasValve
w
r
bk
gy
g/y
b
gy
br
bk
Fan Overheat
Thermostat
b
w
bk
Fan
Flow Overheat
Thermostat
g/y
Wiring Key
b
- Blue
bk - Black
br - Brown
r
- Red
w
- White
g/y - Green/Yellow
- Green
g
gy - Grey
op - Opaque
y
- Yellow
35
© Baxi Heating UK Ltd 2011
12.0 Commissioning the Boiler
12.1
Commissioning the Boiler
W ARN IN G: T he PCB Cont r ol and Fan Asse m bly
ar e 325 Vdc. Isolat e at supply be for e acce ss.
1. Reference should be made to BS:EN 12828 & 14336 when
commissioning the boiler.
Flue Sampling Point
2. At the time of commissioning, complete all relevant sections
of the Benchmark Checklist at the rear of this publications.
Manual Air Vent
3. Flush the whole system using a suitable flushing agent (see
Section 6.2) and vent the radiators. Check for water leaks.
Gas Service
Cock
4. Refill the system with inhibitor following the inhibitor
manufacturer’s instructions and BS 7593 Code of Practice for
Treatment of Water in Domestic Hot Water Central Heating
Systems (see Section 6.2).
5. Complete the label supplied with the inhibitor and attach to
the inside of the boiler case. Detail of system treatment should
be added for future reference.
Fig. 35
Open
Fig. 34
6. Turn the gas supply on and purge according to in GB BS 6891
and in IE I.S. 813 “Domestic Gas Installations”.
7. Turn the gas service cock anticlockwise to the ON position
and check for gas tightness up to the gas valve (Fig. 34). Turn the
power to the boiler ON.
DO NOT check gas pressure here
IMPORTANT: The combustion for this appliance has been
checked, adjusted and preset at the factory for operation on
the gas type specified on the appliance data plate. No
measurement of the combustion is necessary. Do not adjust
the air/gas ratio valve.
Fig. 36
8. Having checked:
• That the boiler has been installed in accordance with
these instructions.
Inlet Gas Pressure Test Point
•The integrity of the flue system and the flue seals.
•The integrity of the boiler combustion circuit and the
relevant seals.
Turn the Central Heating Control Knob clockwise
to increase or anticlockwise to decrease the
boiler flow temperature.
Central Heating
Control Knob
(No OFF Position)
Low
Proceed to put the boiler into operation as follows:
High
The Reset Button should extinguish the
Flame Failure Light and restore normal
operation.
Reset Button
12.2
Priming the Condensate Pump
Reset
1. Using a funnel and tube, carefully pour approximately 1litre of
tap water into the flue products exhaust at the terminal or flue
elbow sampling point to fill the trap and allow the condensate
pump reservoir to fill.
This indicates that there is electricity to the Boiler.
Mains On
(Green Light)
This indicates that the Burner has fired up
and is heating your system.
Burner On
(Green Light)
If Flame Failure Light is ON. Press the Reset
Button. If Flame Failure occurs persistently
consult your Installer or Service Engineer.
Flame Failure
(Red Light)
2. Continue filling with water until the condensate pump
operates.
This indicates that the Condensate Pump is running.
The pump ONLY runs when the condensate reservoir is full.
Condensate Pump
(Green Light)
3. Check that the condensate drain pipework is not leaking and
that it is discharging correctly to drain.
4. See Fig. 36a for operation of LEDs on boiler facia.
Fig. 36a
36
© Baxi Heating UK Ltd 2011
12.0 Commissioning the Boiler
12.3
Check the Operational (Working) Gas
Inlet Pressure
1. Ensure that all controls are calling for heat and
maximum load is applied to the system.
2. With the boiler operating in the maximum rate
condition check that the operational (working) gas
pressure at the inlet gas pressure test point is in
accordance with B.S. 6798 & B.S. 6891.
3. Ensure that this inlet pressure can be obtained with
all other gas appliances in the property working.
Measure the Gas Rate
4. With any other appliances & pilot lights turned OFF
the gas rate can be measured. It should be as shown in
Section 4.0 Technical Data.
DO NOT check gas pressure here
5. Carefully read and complete all sections of the
Benchmark Commissioning Checklist at the rear of this
publication that are relevant to the boiler and
installation. These details will be required in the event of
any warranty work. The publication must be handed to
the user for safe keeping and each subsequent regular
service visit recorded.
Fig. 36b
6. For IE, it is necessary to complete a “Declaration of
Conformity” to indicate compliance with I.S. 813. An
example of this is given in I.S. 813 “Domestic Gas
Installations”. This is in addition to the Benchmark
Commissioning Checklist.
Inlet Gas Pressure Test Point
37
© Baxi Heating UK Ltd 2011
13.0 Completion
13.1
Fitting The Case Panels & Facia
1. Refit the case top panel and front door, securing with
the screws previously removed (Fig.37).
2. Locate the facia panel and secure with the screws
previously removed (Fig. 38).
3. The “Important Ventilation Information” label can be
removed unless the boiler is installed in an unventilated
compartment.
13.2
‘Benchmark’ Checklist
1. Carefully read and complete all sections of the
Benchmark Commissioning Checklist at the rear of this
publication that are relevant to the boiler and
installation. These details will be required in the event
of any warranty work. The publication must be handed
to the user for safe keeping and each subsequent
regular service visit recorded.
Outercase Securing
Screws
2. For IE, it is necessary to complete a “Declaration of
Conformity” to indicate compliance to I.S. 813. An
example of this is given in I.S. 813 “Domestic Gas
Installations”. This is in addition to the Benchmark
Commissioning Checklist.
Fig. 37
13.3
Handover
1. Instruct the user in the operation of the boiler and
system controls. Hand over the User’s Operating,
Installation and Servicing Instructions, giving advice on
the necessity of regular servicing.
2. Demonstrate to the user the action required if a gas
leak occurs or is suspected. Show them how to turn off
the gas supply at the meter control, and advise them
not to operate electric light or power switches, and to
ventilate the property.
3. Show the user the location of the system control
isolation switch, and demonstrate its operation.
4. Advise the user that they may observe a plume of
vapour from the flue terminal, and that it is part of the
normal efficient operation of the boiler.
Facia Securing Screws
Fig. 38
38
© Baxi Heating UK Ltd 2011
14.0 Servicing the Boiler
14.1
Annual Servicing
W ARN IN G: T he PCB Cont r ol and Fan
Asse m bly ar e 325 Vdc. Isolat e syst e m cont r ols
be for e acce ss.
IMPORTANT: When servicing ensure that both the gas and
electrical supplies, including Switched and Permanent Live to the
boiler are isolated before any work is started.
The four LEDs on the facia will all be OFF.
It is important to isolate the electrical supply at the system
isolation switch as it is not possible to do this on the boiler itself.
Hazardous materials are not used in the construction of this
product, however reasonable care during service is
recommended - see Section 1.2.
When replacing the combustion box door after servicing it is
essential that the retaining screws are tightened fully.
1. For reasons of safety and economy, it is recommended that
the boiler is serviced annually. Servicing must be performed by a
competent person in accordance with B.S. 7967-4.
2. After servicing, complete the relevant Service Interval Record
section of the Benchmark Commissioning Checklist at the rear of
this publication.
IMPORTANT: During routine servicing, and after any
maintenance or change of part of the combustion circuit, the
following must be checked:-
• The integrity of the complete flue system and the flue seals.
• The integrity of the boiler combustion circuit and relevant
seals as described in Section 14.2.
• The operational gas inlet pressure as described in Section
12.2.1 to 12.2.3 and the gas rate as described in 12.2.4.
• The combustion performance as described in ‘Check the
Combustion Performance’ (14.1.4 to 14.1.6 below).
3. Competence to carry out Checking Combustion
Performance
B.S. 6798 ‘Specification for Installation & Maintenance of Gas
Fired Boilers not exceeding 70kW’ advises that:-
• The person carrying out a combustion measurement should
have been assessed as competent in the use of a flue gas
analyser and the interpretation of the results.
• The flue gas analyser used should be one meeting the
requirements of BS7927 or BS-EN50379-3 and be calibrated
in accordance with the analyser manufacturers’ requirements.
• Competence can be demonstrated by satisfactory
completion of the CPA1 ACS assessment, which covers the
use of electronic portable combustion gas analysers in
accordance with BS 7967, Parts 1 to 4.
Check the Combustion Performance (CO/CO ratio)
2
4. Set the boiler to operate at maximum rate as described in
Section 12.2.
5. Remove the cap from the flue sampling point, insert the
analyser probe and obtain the CO/CO ratio. This must be
2
less than 0.004.
6. If the combustion reading (CO/CO ratio) is greater than
2
this, and the integrity of the complete flue system and
combustion circuit seals has been verified, and the inlet gas
pressure and gas rate are satisfactory either:
• Perform the ‘Annual Servicing - Inspection’ (Section 14.2) &
re-check.
• Replace the gas valve (Section 15.8) & re-check.
39
© Baxi Heating UK Ltd 2011
14.0 Servicing the Boiler
14.2
Annual Servicing - Inspection
W ARN IN G: T he PCB Cont r ol and Fan
Asse m bly ar e 325 Vdc. Isolat e syst e m
cont r ols be for e acce ss
1. Ensure that the boiler is cool.
2. Remove the facia and front door panel.
3. Release the four 1/4 turn screws securing the air box door
panel and remove the panel (Fig. 39).
4. Disconnect the three leads from the terminals (Fig. 40).
5. Undo the four screws securing the combustion box door
and remove the door (Fig. 41).
6. Visually check for debris/damage and clean or replace if
necessary the following:
a) Burner.
Air Box Door Panel
b) Heat exchanger fins.
Fig. 39
c) Fan compartment (Check also for condensate leaks).
d) Insulation.
e) Door seals-Important: Pay particular attention to
the condition of the combustion box door seals.
f) Electrodes.
g) The condensate trap.
h) The condensate pump
i) Top of heat exchanger.
Spark
Sleeve
Sensing
Lead Terminals
Fig. 40
Earth
Combustion Box
Door Panel
Fig. 41
40
© Baxi Heating UK Ltd 2011
14.0 Servicing the Boiler
14.2
Annual Servicing - Inspection (Cont)
Flue Sampling Point
7. To clean the heat exchanger and burner proceed as
follows:
a) Disconnect the electrical leads to the fan component
protection sensor (Fig. 42).
Fig. 41a
b) Loosen the screw retaining the gas injector pipe at
the venturi (Fig. 42).
c) Undo the two wing nuts to disconnect the fan
(Fig. 42).
d) Remove the fan and disconnect the electrical supply
to it (Fig. 42).
e) Remove the gas injector pipe from the gas valve
(push-fit) (Fig. 42).
Injector Pipe
f) Remove the condensate trap drain plug and place a
vessel underneath to catch the condensate (care should
be taken as this could be hot). The condensate drain
pipe may be removed to increase access.
Injector Pipe Retaining
Screw
g) Undo the condensate trap securing nut, lock nut and
the condensate drain pipe. Remove the condensate trap
and disconnect the sensor leads (Fig. 43). Clean the trap
and refit the drain plug.
Securing Nut
Fan
h) Remove the two screws securing the burner and
remove the burner. Visually inspect the internal burner
baffle for obstruction, check seal around baffle for
cracks/damage. Clean with a soft brush.
Sensor
Leads
Protection
Sensor Leads
Electrical Supply
i) Loosen the two screws retaining the heat exchanger
support bracket and slide to the left to remove
(Fig. 44).
Condensate
Trap
Fig. 42
Wing Nuts
Lock Nut
Service Drain
Plug
j) Remove the four screws securing the heat
exchanger/combustion box base and withdraw the
base.
Trap to Condensate
Pump Inlet Pipe
Central Insulation Panel
k) Lower the central insulation panel and check
condition (Fig. 44). Replace the lower insulation pad if
necessary.
Fig. 43
l) Ensure the heat exchanger fins are clear of any
obstruction.
Burner
m) Check condition of all seals. Important: Pay
particular attention to the condition of the
combustion box door seals.
Combustion
Box Base
Heat Exchanger
Support Bracket
n) Reassemble in reverse order and check for leaks.
8. Check the operation of the condensate pump and
drain pipework (see Section 10.1)
9. Check CO/CO
See section 4.0.
2
ratio at flue sampling point (Fig.41a).
Combustion Box Base
Securing Screws
Burner Securing
Screws
10. Complete the relevant Service Interval Record
section of the Benchmark Commissioning Checklist at
the rear of this publication and then hand it back to the
user.
Fig. 44
41
© Baxi Heating UK Ltd 2011
15.0 Changing Components
15.1
Changing Components & Preparation
W ARN IN G: T he PCB Cont r ol and Fan
Asse m bly ar e 325 Vdc. Isolat e syst e m
cont r ols be for e acce ss.
IMPORTANT: Ensure that both the gas and electrical
supplies, including Switched and Permanent Live to the
boiler are isolated before any work is started.
The four facia LEDs will be all OFF.
It is important to isolate the electrical supply at the
system isolation switch as it is not possible to do this
on the boiler itself.
Hazardous materials are not used in the construction of
this product, however reasonable care is recommended
- see Section 1.2.
When replacing the combustion box door it is essential
that the retaining screws are tightened fully.
Remove the facia and front door panel.
For the replacement of some components it will be
necessary to drain the boiler. Proceed as follows:-
Fig. 45
Heat Exchanger
Manifold
1. Isolate the water circuit and drain the system as
necessary. A drain point is located on the heat
exchanger manifold at the right hand side of the boiler
(Fig. 45) to enable the heat exchanger to be drained.
2. Place a tube on the drain point to drain water away
from the electrics. Turn anticlockwise to open (Fig. 45).
Drain Point
Tube
3. After changing a component recommission the boiler
where appropriate and check the inhibitor
concentration (see Section 6.2 and 10.1).
Electrical Connections
Pipe Access
Panel
The thermistor, safety thermostat, interface PCB and
the flow switch can be accessed after removal of the
pipe access panel (Fig. 46).
Flow Temperature Thermistor (Red)
15.2
Flow Temperature Thermistor and
Safety Thermostat (Fig. 46)
1. The procedure is the same for both the thermistor
and the safety thermostat.
Safety
Thermostat
(Black)
2. Remove the pipe access panel and disconnect the
electrical connections from the sensor.
Fig. 46
3. Remove the sensor from the pipe.
4. Fit the new thermistor or safety thermostat and
reassemble in reverse order.
42
© Baxi Heating UK Ltd 2011
15.0 Changing Components
Pipe Access
Panel
15.3
Flowswitch (Fig. 47)
1. Drain the boiler (see Section 13.1 paragraph 2 & 3).
2. Remove the pipe access panel and remove the securing
clip from the ‘O’ ring joint between the flow pipe and the
system. Undo screws on support bracket.
Support Bracket
3. Remove the securing clip from the ‘O’ ring joint
between the flow pipe and the flowswitch.
4. Remove the two screws securing the flow switch to the
boiler.
5. Disconnect the inline electrical connection and remove
the flowswitch.
Flow Switch
6. Fit the new flowswitch and reassemble in reverse order.
7. Recommission the boiler and check the inhibitor
concentration (see Section 6.2 and 10.1).
Flow Pipe
15.4
Condensate Pump - Complete (Fig. 47a)
Fig. 47
1. Remove the pipe from the trap to the pump inlet and
disconnect the electrical plug.
2. Lift the pump off the support studs and ease it
forwards. Release the snap fit clip and disconnect the
condensate outlet pipe.
Clip
Over Level Switch
3. Connect the condensate outlet pipe to the new pump
using the new clip provided.
4. With the new pump in place on the studs, refit the trap
discharge pipe, ensuring the ‘O’ ring is in place. Reconnect
the electrical plug.
5. Neatly coil the excess condensate outlet pipe adjacent
to the pump, ensuring that it is not kinked or restricted.
6. Check operation of the pump - See Section 10.2.
15.5
Condensate Pump - Level Switches
(Fig. 47a)
1. Remove the complete Condensate Pump as described
in Section 13.4, and remove the cover.
Condensate Pump
(Cover Removed)
Fig. 47a
2. Disconnect the wires from the switch(es) and remove
the retaining screws. On the Level Switch remove the
circlip and washers connecting the plunger to the
actuating arm.
3. Fit the new switch(es). Align the actuating arm of the
Level Switch with the plunger, ensuring that there is a
washer at each side of the arm.
Level Switch
4. Reconnect the wires. On the Over Level Switch there
is no connection to the lower spade terminal.
5. Check operation of the pump - See Section 10.2.
43
© Baxi Heating UK Ltd 2011
15.0 Changing Components
15.6
PCB (Figs. 48 & 49)
Control
Knob
W ARN IN G: T he PCB Cont r ol and Fan
Asse m bly ar e 325 Vdc. Isolat e syst e m
cont r ols be for e acce ss.
1. Pull the control knob off the spindle and remove the
plastic button cover. Refit them onto the new PCB
(Fig. 48).
2. Remove the top right hand securing screw and swing
out the PCB housing. Remove the PCB cover and
disconnect the electrical plugs noting their positions
3. Remove the screw securing the PCB to the housing.
The PCB can be removed from the housing.
4. Ensure that the two jumpers are fitted to the new
PCB as shown (Fig. 49).
Fig. 48
PCB Housing Securing
Screw
5. Reconnect the plugs, fit the new PCB to the housing
and reassemble in reverse order.
Plastic Button
Cover
Hinge open
PCB Housing
Blue (CN11) Jumper
Red (CN12) Jumper
Fig. 49
44
© Baxi Heating UK Ltd 2011
15.0 Changing Components
The fan and venturi, gas valve, injector pipe,
condensate trap, fan protection sensor, spark and
sensing electrodes can be accessed and changed on
the removal of the airbox door panel.
1. Remove the airbox door panel by loosening the four
1
/
4
turn screws (Fig. 50).
15.7
Spark and Sensing Electrodes
(Fig. 51)
1. Disconnect all three leads from tabs.
Spark
Earth
-
-
-
Opaque cable
Green/Yellow cable
White cable
Sensing
2. Remove the two screws securing each of the
electrodes to the combustion box door and remove the
electrodes.
3. Fit the new electrodes (and new gasket, as required)
and reassemble in reverse order.
Air Box Door Panel
Fig. 50
15.8
Fan (Fig. 52)
W ARN IN G: T he PCB Cont r ol and Fan
Asse m bly ar e 325 Vdc. Isolat e syst e m
cont r ols be for e acce ss.
1. Loosen the screw holding the injector pipe into the
venturi.
2. Remove the electrical connections to the fan and
protection sensor on the fan.
Sensing
Combustion
Box Door
Earth
Spark
3. Remove the wing nuts securing the fan to the base of
the combustion box.
Fig. 51
4. Lower the fan and remove.
5. If changing the fan, remove the screws securing the
venturi and fan protection sensor bracket, noting the
positions of the injector opening and sensor bracket, fix
them to the new fan.
Injector Pipe
Injector
Opening
Screw
6. Fit the new fan and reassemble in reverse order.
Gasket
Fan
The injector pipe, condensate trap and gas valve can
be changed after the removal of
the fan.
Protection
Sensor
Venturi
Electrical Connections
Fig. 52
Electrical Connection
Wing Nuts
45
© Baxi Heating UK Ltd 2011
15.0 Changing Components
The removal of the fan is necessary to enable the changing of
the injector pipe, condensate trap and gas valve (see section
13.6).
15.9
Injector Pipe (Fig. 53)
1. Remove the injector pipe by pulling out from the ‘O’ ring
joint in the gas valve.
2. Fit the new injector pipe and reassemble in reverse order.
Injector Pipe
15.10 Gas Valve (Fig. 53)
IMPORTANT: After replacing the valve the CO must be
2
checked as detailed in Section 14.1.4 to 14.1.6. Only
change the valve if a suitable calibrated combustion
analyser is available, operated by a competent person -
see Section 14.1.3.
Gas Valve
Securing Screws
Case Pressure Pipe
Gasket
1. Isolate gas supply and disconnect the gas tap by removing
the four screws.
2. If required remove the condensate pump to increase access
(see Section 13.4) and undo the case pressure pipe from the
valve.
Boiler Side
3. Disconnect the electrical plug from the gas valve.
4. Remove the fan (see Section 13.6) and injector pipe.
Aluminium
Spacer
‘O ring’
Gas Valve
Gas Tap
5. Remove the two gas valve securing screws from inside the
air box holding the gas valve, and remove the valve.
6. Remove the aluminium spacer and its gasket from the gas
valve.
Fig. 53
Electrical Plug
7. Fit the aluminium spacer and its gasket to the new valve.
8. Fit the new gas valve and reassemble in reverse order.
NOTE: Check for gas tightness after replacing gas valve.
9. Check the CO2 level. If the level is greater than that quoted,
telephone the Technical Enquiries for further advice.
Securing
Nut
15.11 Condensate Trap (Fig. 54)
Sensor
Leads
1. Disconnect the condensate trap from the base of the heat
exchanger.
2. Disconnect the condensate drain ‘O’ ring connection from
the condensate trap and condensate pump. For ease of access
also remove the pump.
Condensate
Trap
3. Undo the condensate trap lock nut.
4. Remove the condensate trap from the boiler.
5. Disconnect the sensor leads.
Lock Nut
Service Drain
Plug
6. Fit the new condensate trap and reassemble in reverse
order. When refitting the pipe from the trap to the pump
ensure that all seals and connections are made.
Trap to Condensate
Pump Inlet Pipe
Fig. 54
7. Prime the condensate trap (fill first chamber), check for leaks
(see Section 8.5).
46
© Baxi Heating UK Ltd 2011
15.0 Changing Components
Combustion Box
Door Panel
The burner and heat exchanger can be changed after
removal of the combustion box door. To change the
heat exchanger, the fan and burner must be removed
first (see section 13.6 and 13.10).
1. Remove the combustion box door by removing the
four securing screws (Fig. 55).
IMPORTANT: On refitting the combustion box
door check the condition of the combustion box
door seals.
15.12 Burner (Fig. 56)
Fig. 55
1. Remove the two screws securing the burner to the
base of the combustion box.
Burner
Support
Bracket
2. Remove the burner carefully from the combustion
box base.
Return
Connection
3. Check the burner seal on the heat exchanger base,
replace if necessary. Fit the new burner and reassemble
in reverse order.
Fig. 57
15.13 Heat Exchanger
Fig. 56
1. Drain the boiler (see section 13.1 paragraph 2 & 3).
2. Remove all components in the base of the airbox.
Flow
Switch
Securing Screws
3. Undo the screws on the support bracket. Remove
the screws securing the flow switch and return
connections and remove the connections (Fig. 57).
4. Remove the screws securing the heat exchanger
manifold and remove the manifold (Fig. 58).
5. Ease the combustion box left hand side panel to clear
the stud, lift the heat exchanger assembly (Fig. 59) and
rotate the bottom upwards whilst pulling it forwards
out of the airbox.
6. Ensure that the heat exchanger is disengaged from
the flue elbow and clear of the stud in the left hand side
of the combustion box.
Fig. 58
7. Fit the new heat exchanger and reassemble in reverse
order.
Heat Exchanger
Manifold
8. Recommission the boiler and check the inhibitor
concentration (see Section 6.2 and 10.1).
Heat Exchanger
Assembly
Fig. 59
47
© Baxi Heating UK Ltd 2011
15.0 Changing Components
15.14 Heat Exchanger Lower Insulation Pad
(Fig. 60)
1. Remove all components in the base of the airbox.
2. Remove the burner (see section 13.10).
3. Remove the four bolts securing the combustion box
base.
4. Remove the combustion box base.
5. Pull the central insulation panel down from the
centre of the heat exchanger and remove the lower
insulation pad.
Central Insulation Panel
Upper Insulation
6. Fit the new insulation pad and reassemble in reverse
order.
Pad
Lower Insulation
Pad
15.15 Heat Exchanger Upper Insulation Pad
(Fig. 60)
Fig. 60
Burner
1. Remove all components in the base of the airbox.
2. Remove the burner (see section 13.10).
Combustion
Box Base
3. Remove the heat exchanger (see section 13.11).
4. Remove the four bolts securing the combustion box
base.
Support Bracket
5. Remove the combustion box base.
Combustion Box Base
Securing Screws
6. Pull the central insulation panel down from the
centre of the heat exchanger.
Burner Securing
Screws
7. Fit the new insulation pad and reassemble in reverse
order.
48
© Baxi Heating UK Ltd 2011
16.0 Short Parts List
Short Parts List
A
B
C
Key
No.
G.C.
No.
Description
Manufacturers
Part No.
A
E06 058
Flow Temperature
Thermistor (Red)
240670
242459
B
C
E06 059
E06 060
Flow Switch
Safety Thermostat
(Black)
242235
D
E
F
PCB
5129147
5109925
241900
Fan
E
Gas Valve
G
H
I
E06 085
Viewing Window
Condensate Trap
Electrodes Kit
Burner Assy
242484
D
5111714
5132366
5107430
242497
J
G
K
L
M
N
O
E06 097
Heat Exchanger Assy
Control Knob
Condensate Pump
Level Switch
Over Level Switch
5109996
5117661
5117591
5117592
F
I
H
M
K
J
N
O
L
49
© Baxi Heating UK Ltd 2011
17.0 Fault Finding
NOTE: The fan is supplied with 325 Vdc.
Fan Fault Finding should only be carried out after the
boiler has been electrically isolated.
Mains On
LED Light LED Light LED Light
(Green)
(Green) (Red)
Boiler On
Lockout
General Fault Finding should only be carried out by
someone who is appropriately qualified.
denotes LED flashing
*
Lights
Off Off Off
Lights
Go to Electrical Supply
section of the fault finding
instructions.
Go to Thermistor section
YES
YES
YES
YES
YES
YES
On
On
YES
YES
*
of the fault finding
instructions.
Low Electrical Supply
Incoming Voltage less than
180V. Check System
Lights
Lights
Off On
Off onn
Live & Neutral Reversed
Incoming Live and Neutral
reversed.
*
*
*
Controls & System Wiring.
Otherwise contact Electricity
Provider.
LV Wiring Harness
Ensure the small 8 way
connector is securely plugged
into the PCB. If the fault
Lights
On On On
YES
YES
YES
Lights
Go to Dry-Fire
section of the fault finding
instructions.
On
* *
persists replace wiring harness.
Lights
On
PCB Fault
Replace PCB.
*
*
*
Lights
On Off On
Go to Ignition Lockout section
of the fault finding instructions.
Lights
On On
PCB Fault
Replace PCB.
Lights
On Off
Go to Overheat Lockout
section of the fault finding
instructions.
*
Lights
On On
YES
YES
PCB Fault
Replace PCB.
*
Lights
Go to Fan Lockout
section of the fault finding
instructions.
On
*
*
Lights
Go to Condensate Pump
section of the fault finding
instructions.
On
* *
50
© Baxi Heating UK Ltd 2011
Lights
Off Off Off
17.0 Fault Finding
ELECTRICAL SUPPLY
No Permanent Live to
boiler. Check Mains Fuse
and
NO
240V at A ?
A
System Wiring.
B
YES
No Switched Live to
boiler. Check System
Controls and System
Wiring.
NO
NO
240V at B ?
N
P/L
S/L
YES
Check P/L wiring from
terminal block to PCB.
240V at C ?
YES
NO
NO
Check S/L wiring from
terminal block to PCB.
240V at D ?
YES
Check for short circuit on
condensate pump, fan &
gas valve. Replace if
PCB fuse OK ?
shorted & replace fuse.
YES
Replace PCB.
C
D
Fuse
51
© Baxi Heating UK Ltd 2011
Lights
* * On
17.0 Fault Finding
DRY-FIRE
NO
Is the
Fill system with water and
system full of water ?
bleed out all air.
YES
NO
Is the
Pump or Pump Wiring
fault.
pump running ?
YES
Unplug
5-way PCB
connector. Is
there continuity
between H
YES
Replace PCB.
H
Viewed from
Wire Entry end
NO
Disconnect
Flow Switch Inline
connector. With pump running is
there continuity across flow
switch ?
YES
NO
Wires from inline
connector to PCB faulty.
NO
Remove
Is there a
NO
flow switch from boiler.
Is there a physical blockage to
the paddle within the
flow switch ?
Replace Flow Switch.
blockage in the system ?
YES
YES
Remove Blockage.
Remove Blockage.
52
© Baxi Heating UK Ltd 2011
Lights
On Off On
17.0 Fault Finding
IGNITION LOCKOUT
I
Gas Valve 5-way
Connector Plug
Is there
NO
Check isolation valve and
gas supply.
gas at gas valve inlet ?
J
YES
Remove
5-way connector
YES
Reset Lockout.
Is there gas flow
(check at meter) ?
NO
from gas valve. Is there 240
Vdc between I & J
Replace Gas Valve.
during ignition ?
NO
YES
Is
Remove
the larger of the
two 6-way PCB connectors.
Is there continuity from I to L
& from J to K ?
Remove Gas Valve & check
inlet filter for blockage.
Otherwise incorrect gas supply
to boiler.
NO
there at least
NO
Lead from PCB to Gas
Valve faulty.
18mbar dynamic at gas valve
inlet ?
YES
YES
Replace PCB.
Is
YES
Condensate Trap
blocked or water on
terminals ?
Clear blockage and dry
sensors.
K
L
NO
Is
YES
YES
Check and if necessary
change over level switch
(see Section 13.5)
Condensate Pump
reservoir full ?
6-way Connector
NO
Is
Replace spark or flame
detection probe and
gaskets.
spark or flame detection
probe damaged ?
NO
NO
Is
Set spark gap to 3.5mm.
spark gap between 3 and
4mm ?
YES
Is
Is the
YES
wiring from PCB
NO
to spark probe & flame
detection probe OK ?
burner blocked or
damaged ?
Replace PCB.
YES
NO
Clean burner or replace as
necessary.
Rectify wiring.
53
© Baxi Heating UK Ltd 2011
Lights
On Off onn
17.0 Fault Finding
*
OVERHEAT LOCKOUT
Disconnect
NO
black stat on flow pipe.
When flow < 60° C is there
continuity across stat ?
Replace Stat.
YES
Reconnect stat.
Disconnect fan stat.
When fan temp < 60° C
is there continuity
across stat ?
NO
NO
NO
Replace Stat.
YES
Reconnect stat.
Disconnect the larger of
the 6-way PCB connectors.
Is there continuity
M
Wiring from PCB to
thermostats faulty.
across M ?
YES
6-way Connector
Disconnect
thermistor
(red sensor on flow pipe).
Is resistance between
0.5kë & 20kë ?
Replace thermistor.
YES
Is
YES
Replace combustion
chamber door seal & trim
seal.
combustion chamber
door seal damaged or not in
place ?
NO
Replace PCB.
54
© Baxi Heating UK Ltd 2011
Lights
17.0 Fault Finding
On
*
*
FAN LOCKOUT
NOTE: The fan is supplied with 325 Vdc.
Fan Fault Finding should only be carried out after the
boiler has been electrically isolated.
Fan
PCB
Connection
Connection
Unplug
NO
3-way PCB connector
& unplug fan. Is there
continuity from N to O &
from P to Q ?
O
Q
N
P
Rectify wiring.
YES
Fan
PCB
Connection
Connection
Unplug
the smaller of the
6-way PCB connector. Is there
continuity from R to S & from T
to U & from
NO
Rectify wiring.
R
T
V
S
U
W
V to W ?
YES
Viewed from
Wire Entry end
Replace fan.
55
© Baxi Heating UK Ltd 2011
17.0 Fault Finding
Lights
On
On
THERMISTOR
*
Unplug
thermistor,
Is thermistor resistance between
NO
Replace thermistor.
0.5kë & 20kë ?
D
YES
Plug in
thermistor, leave
NO
Wiring from PCB to
thermistor faulty.
8-way connector unplugged.
Is resistance at D between
0.5kë & 20kë ?
Viewed from
Wire Entry end
YES
Replace PCB.
56
© Baxi Heating UK Ltd 2011
17.0 Fault Finding
CONDENSATE PUMP
Lights
Lights
On Off On
* * On
Reset boiler
and add approx. 1 litre
tap water to the condensate
system via the flue or
sample point
Condensate pump level switch
activated for longer than 3
minutes - boiler locks out.
Boiler will try to relight 4 times
in 5 minutes.
Condensate pump over level
switch activated - pump
reservoir level too high
resulting in ignition lockout.
5Vdc at A ?
No - replace PCB
Does the
pump motor run as
the condensate level
rises ?
Mechanical fault
NO
NO
on float, linkage or switch.
Mechanical fault on pump
or impellor.
5Vdc at B ? No - check wiring.
240V across C & D ?
No - replace level
switch
YES
YES
Go to diagram for
connections to check
Is motor
resistance across C & D
approx. 40 ohms ?
No - replace pump
assembly
If fault cannot be rectified
replace level switch or
pump assembly.
NO
NO
Condensate pipe
blocked or kinked, or outlet
blocked or frozen
at drain.
Condensate pump
outlet back check valve
blocked or seized shut.
As the pump motor runs
does the condensate flow to
drain ?
YES
YES
Rectify fault, replacing pipe
if necessary.
If fault cannot be rectified
replace pump assembly.
YES
Is
Condensate pipe
has high resistance - too long
or restricted, head greater than
3 metres.
NO
NO
condensate flow
rate at least 1.8 l/min and run
time less than 3
Pump motor or
impellor worn - replace
pump assembly
minutes ?
YES
YES
Rectify fault, replacing or
re - routing pipe
if necessary.
Condensate Pump Assembly
Condensate
Level Switch
Condensate Pump
Condensate
Motor
Over-Level Switch
N
L
Does
NO
Mechanical fault on
float, linkage or level switch.
After 3 mins boiler
pump motor stop
as level in reservoir
falls ?
gy
‘C’ ‘D’
‘B’
will lock out.
gy
YES
YES
If fault cannot be rectified
replace level switch or
pump assembly.
PCB
Operation correct
‘A’
57
© Baxi Heating UK Ltd 2011
Failure to install and commission according to the manufacturer’s instructions and complete this Benchmark Commissioning Checklist will invalidate the warranty. This
does not affect the customer’s statutory rights.
If yes, and if required by the manufacturer, has a water scale reducer been fitted?
CONDENSING BOILERS ONLY
The condensate drain has been installed in accordance with the manufacturer’s instructions and/or BS5546/BS6798
If the condensate pipe terminates externally has the pipe diameter been increased and weatherproof insulation fitted?
Yes
Yes
58
Service Record
It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the
manufacturer’s instructions.
Always use the manufacturer’s specified spare part when replacing controls.
Service 1
Service 2
Date:
Date:
Engineer Name:
Engineer Name:
Company Name:
Telephone No.
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Gas Safe Register No.
Comments:
Signature:
Signature:
Service 3
Service 4
Date:
Date:
Engineer Name:
Engineer Name:
Company Name:
Telephone No.
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Gas Safe Register No.
Comments:
Signature:
Signature:
Service 5
Service 6
Date:
Date:
Engineer Name:
Engineer Name:
Company Name:
Telephone No.
Company Name:
Telephone No.
Operative ID No.
Comments:
Gas Safe Register No.
Comments:
Signature:
Signature:
Service 7
Service 8
Date:
Date:
Engineer Name:
Engineer Name:
Company Name:
Telephone No.
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Gas Safe Register No.
Comments:
Signature:
Signature:
Service 9
Service 10
Date:
Date:
Engineer Name:
Engineer Name:
Company Name:
Telephone No.
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Gas Safe Register No.
Comments:
Signature:
Signature:
59
All descriptions and illustrations provided in this leaflet have been carefully
prepared but we reserve the right to make changes and improvements in
our products which may affect the accuracy of the information contained in
this leaflet. All goods are sold subject to our standard Conditions of Sale
which are available on request.
PO TTERTO N
A Tr ading Divisio n o f Baxi Heat ing UK Lt d (3879156)
Brooks House, Coventry Road, Warwick. CV34 4LL
After Sales Service 0844 871 1560 Technical Enquiries 0844 871 1555
e&oe
© Baxi Heating UK Ltd 2011
Comp No. 720896601 (6/11)
|
Aiwa CDC X135 User Manual
A O Smith GWT 2500 User Manual
ARRI ULTRA 16 User Manual
Black Box Cable Box Zone 4 Seismic Cabinets, 45U User Manual
Bushnell Binoculars 20 1925 User Manual
Bushnell Binoculars 202310 User Manual
Chromalox PQ404 6 User Manual
Infiniti Car Speaker 6 1 User Manual
JVC Camcorder GR SXM530 User Manual
JVC Car Stereo System KD R205 User Manual