Baxi Potterton BBU 15 HE User Manual

Installation & Servicing Instructions  
Baxi Bermuda BBU 15 HE  
Condensing Back Boiler Unit  
These Instructions must be read in conjunction with those for  
the separate Valor Dimension electric firefront.  
They include the Benchmark Commissioning Checklist  
and should be left with the user for safe keeping.  
© Baxi Heating UK Ltd 2009  
Installer Notification Guidelines  
Choose Building  
Regulations Notification  
Route  
Competent Person's  
Building Control  
Self Certification Scheme  
Install and Commission this  
appliance to manufacturer's  
instructions  
Contact your relevant Local  
Authority Building Control  
(LABC) who will arrange  
an inspection or contact  
a government approved  
inspector  
Complete the  
Benchmark Checklist  
If you notify via the ‘Gas Safe  
Register’, the register will issue  
the Building Regulations  
Install and Commission this  
appliance to manufacturer's  
instructions  
certificate on members’ behalf  
Scheme Members only  
Call ‘Gas Safe Register’ on:  
0800 408 5577  
Complete the  
Benchmark Checklist  
or log onto:  
within 10 days  
You must ensure that the  
certificate number issued by  
the ‘Gas Safe Register’ is written  
onto the Benchmark Checklist  
‘Gas Safe Register’ will issue a  
Building Regulations Compliance  
Certificate to the property owner  
and inform the relevant LABC  
LABC will record the data  
and will issue a  
certificate of compliance  
3
© Baxi Heating UK Ltd 2009  
Legislation  
IMPORTANT - Installation, Commissioning, Service & Repair  
This company declare that no substances harmful to health  
are contained in the appliance or used during appliance  
manufacture.  
This appliance must be installed in accordance with the manufacturer’s instructions and  
the regulations in force. Read the instructions fully before installing or using the  
appliance.  
The appliance is suitable only for installation in GB and IE and  
should be installed in accordance with the rules in force, and  
only used in a suitably ventilated location.  
In GB, this must be carried out by a competent person as stated in the Gas Safety  
(Installation & Use) Regulations.  
In GB, the installation must be carried out by a Gas Safe  
Registered Installer. It must be carried out in accordance with  
the relevant requirements of the:  
Definition of competence: A person who works for a Gas Safe registered company  
and holding current certificates in the relevant ACS modules, is deemed competent.  
• Gas Safety (Installation & Use) Regulations.  
• The appropriate Building Regulations either The Building  
Regulations, The Building Regulations (Scotland), Building  
Regulations (Northern Ireland).  
• The Water Fittings Regulations or Water Byelaws in  
Scotland.  
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domestic  
Gas Installations”.  
The addition of anything that may interfere with the normal operation of the appliance  
without express written permission from the manufacturer or his agent could invalidate  
the appliance warranty. In GB this could also infringe the Gas Safety (Installation and  
Use) Regulations.  
• The Current I.E.E. Wiring Regulations.  
Where no specific instructions are given, reference should be  
made to the relevant British Standard Code of Practice.  
In IE, the installation must be carried out by a competent  
Person and installed in accordance with the current edition of  
I.S. 813 ‘Domestic Gas Installations’, the current Building  
Regulations and reference should be made to the current ETCI  
rules for electrical installation.  
Warning - Check the information on the data plate is compatible with local supply  
conditions.  
All systems must be thoroughly flushed and treated with  
inhibitor (see section 6.2).  
All Gas Safe registered engineers carry an ID card with their licence number and a  
photograph. You can check your engineer is registered by telephoning  
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency)  
Codes of Practice, most recent version should be used  
o
Regulations 1993 N 3083” and is deemed to meet the requirements of Directive  
92/42/EEC on the energy efficiency requirements for new hot water boilers fired with  
liquid or gaseous fuels:-  
In GB the following Codes of Practice apply:  
Standard  
BS 6891  
BS 5546  
Scope  
Gas Installation.  
Installation of hot water supplies for  
domestic purposes.  
Type test for purpose of Regulation 5 certified by:  
Notified Body 0087.  
BS 5449  
BS 6798  
BS 5440 Part 1  
BS 5440 Part 2  
BS 7074  
Forced circulation hot water systems.  
Installation of gas fired hot water boilers.  
Chimneys.  
Product/Production certified by:  
Notified Bodies 0086.  
Ventilation.  
Expansion vessels and ancillary equipment for  
sealed water systems.  
BS 7593  
Treatment of water in domestic hot water central  
heating systems.  
For GB/IE only.  
Also the following standard includes relevant information about  
builders openings:  
BS 5871 Part 1  
Installation of gas fires, convector heaters,  
fire/back boilers and heating stoves.  
In IE the following Codes of Practice apply:  
Standard  
I.S. 813  
Scope  
Domestic Gas Installations.  
The following BS standards give valuable additional information;  
BS 5546  
BS 5449  
Installation of hot water supplies for  
domestic purposes.  
Forced circulation hot water systems.  
4
© Baxi Heating UK Ltd 2009  
Safe Manual Handling  
General  
The following advice should be adhered to, from when first handling the boiler to the final stages of installation, and also during maintenance.  
Most injuries as a result of inappropriate handling and lifting are to the back, but all other parts of the body are vulnerable, particularly shoulders, arms and hands.  
Health & Safety is the responsibility of EVERYONE.  
There is no ‘safe’ limit for one man - each person has different capabilities. The boiler should be handled and lifted by TWO PEOPLE.  
Do not handle or lift unless you feel physically able.  
Wear appropriate Personal Protection Equipment e.g. protective gloves, safety footwear etc.  
Preparation  
Co-ordinate movements - know where, and when, you are both going.  
Minimise the number of times needed to move the boiler - plan ahead.  
Always ensure when handling or lifting the route is clear and unobstructed. If possible avoid steps, wet or slippery surfaces, unlit areas etc. and take special care  
on ladders/into lofts.  
Technique  
When handling or lifting always use safe techniques - keep your back straight, bend your knees. Don’t twist - move your feet, avoid bending forwards and  
sideways and keep the load as close to your body as possible.  
Where possible transport the boiler using a sack truck or other suitable trolley.  
Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary. See the  
‘Installation’ section of these instructions for recommended lift points.  
Remember  
The circumstances of each installation are different. Always asses the risks associated with handling and lifting according to the individual conditions.  
If at any time when installing the boiler you feel that you may have injured yourself STOP !!  
DO NOT ‘work through’ the pain - you may cause further injury.  
IF IN ANY DOUBT DO NOT HANDLE OR LIFT THE BOILER - OBTAIN ADVICE OR ASSISTANCE BEFORE PROCEEDING !!  
Working at Height  
In order to reduce the number of fatalities and major accidents attributable to working at height, the Health and Safety Executive has introduced comprehensive  
regulations and guidance that should be followed by all businesses working at height.  
The following paragraphs consider some of the main features of the regulations and guidance. This is, however, only a limited summary and it is recommended  
that all businesses planning on undertaking air source heat pump heating installations obtain a copy of the regulations and guidance issued by the Health and  
Safety Executive and carefully consider the contents.  
The regulations and guidance state that you are required to carry out a risk assessment for all work conducted at height and to put in place arrangements for:  
Eliminating or minimising risks from work at height.  
Safe systems of work for organising and performing work at height.  
Safe systems for selecting suitable work equipment.  
Safe systems for protecting people from the consequences of work at height.  
The regulations and guidance highlight a hierarchy for safe work at height:  
Avoid the risk by not working at height if practicable.  
Prevent falls. Where it is not reasonably practicable to avoid work at height, you are required to take suitable and sufficient steps to prevent the risk of a fall  
including selecting the most suitable work equipment (in accordance with the regulations).  
Mitigate the consequences of a fall; where the risk of a person or object falling still remains, take suitable and sufficient measures to minimise  
the distance and consequences of any fall.  
Collective protection measures, such as guard rails on scaffold, should be given priority over personal protection measures, such as safety harnesses.  
Within the regulations’ framework, you are required to:  
1) Assess the risk to help you decide how to work safely.  
2) Follow the hierarchy for safe work at height (i.e. avoid, prevent and mitigate).  
3) Plan and organise your work properly, taking account of weather conditions and the possibility of emergencies.  
4) Make sure those working at height are competent.  
5) Make use of appropriate work equipment.  
6) Manage the risks from working on or around fragile surfaces and from falling objects.  
7) Inspect and maintain the work equipment to be used and inspect the place where the work will be carried out for both access and egress.  
5
© Baxi Heating UK Ltd 2009  
Contents  
Section  
Page  
1.0  
2.0  
3.0  
4.0  
5.0  
6.0  
7.0  
8.0  
Introduction  
7
General Layout  
8
Technical Data  
10  
11  
15  
20  
21  
25  
System Details  
Site Requirements  
Boiler Internal Wiring  
Installation  
Completion & Commissioning  
9.0  
Annual Servicing  
27  
29  
33  
34  
38  
39  
42  
10.0 Changing Components  
11.0 Setting the Gas Valve  
12.0 Fault Finding  
13.0 Short Parts List  
14.0 Notes  
Benchmark Checklist  
6
© Baxi Heating UK Ltd 2009  
1.0 Introduction  
1.1  
Description  
1. The Baxi Bermuda BBU 15 HE is a central heating  
boiler designed for installation within a builders opening  
in the living space of a dwelling.  
2. The boiler is a fully automatic gas fired condensing  
boiler. It is room sealed and fan assisted.  
3. The boiler output will automatically modulate  
between:  
Max  
Min  
15kW  
4.6kW  
15.7kW (condensing) 4.83kW (condensing)  
According to system load  
4. It must be fitted in conjunction with one of the  
available electric firefront units as listed on page 2.  
The separate electric firefront is intended for hearth  
mounting. All instructions, fixings etc. needed to fit the  
firefront are included in the firefront pack.  
5. These instructions relate to the central heating boiler  
section of the appliance (Fig. 1).  
6. The appliance is designed for use on NATURAL  
GAS (G20) only.  
Fig. 1  
7. It can be used on sealed or open vented systems.  
It must NOT be fitted on any type of gravity system.  
The boiler is suitable for fully pumped systems ONLY.  
8. The boiler is fitted with an integral pump unit for the  
removal of condensate.  
9. The boiler data badge gives details of the model,  
serial number and Gas Council number and is situated  
on the front case panel.  
10. The boiler is intended to be installed in a residential  
environment on a governed meter supply only.  
11. The boiler must be installed with one of the  
MULTIIFIT vertical concentric Flexi Flue kits available:-  
10m kit 720101701 or 12.5m kit 720102001.  
12. All systems must be thoroughly flushed and  
treated with inhibitor (see section 4.2).  
1.2  
Contents  
1. The boiler pack contains:  
• Boiler Unit  
• Plumbing Kit  
• Condensate Pipe & Elbow  
Fig. 2  
• Fixings Kit  
• Literature Pack  
2. The flue pack contains:  
• Terminal Cap  
• Flue Duct Adaptor (inc. seal)  
• Air Cowl  
• Air Duct Collar (inc. 4 screws)  
• Air Duct Clamp  
• Closure Plate  
• Boiler Concentric  
Adaptor (inc. 2 seals)  
• 10m or 12.5m of Concentric  
Flexible Duct  
• 2 x 60mm grey Seals  
• 1 x 100mm red Seal  
7
© Baxi Heating UK Ltd 2009  
2.0 General Layout  
2.1  
Layout (Fig. 3)  
1.  
Automatic Air Vent  
Flue Connection  
1
2.  
2
3.  
Spark Generator  
4.  
Spark & Sensing Electrodes  
Heat Exchanger  
5.  
3
17  
16  
6.  
Boiler Control Connector  
Control Wiring Connector  
Condensate Sump  
Gas Cock  
7.  
4
5
8.  
9.  
10.  
11.  
12.  
13.  
14.  
15.  
16.  
17.  
18.  
19.  
Condensate Pump  
Fan  
15  
14  
Drain  
Return Connection  
Air Sampling Point  
Flue Sampling Point  
Flow Connection  
6
13  
12  
7
Condensate Outlet  
PCB Control Box (shown removed for clarity)  
Boiler Control (cover open)  
8
The Boiler Control operates the boiler remotely. This is  
supplied with the firefront and is fitted, in operation, to the  
firefront spacer frame.  
IMPORTANT: To commission the boiler it is is necessary  
to remove the Boiler Control from the firefront  
packaging and connect it to the boiler at the upper right  
hand side (item 6).  
9
11  
10  
PCB Control Box  
removed for clarity  
Fig. 3  
18  
PCB Control Box  
19  
Calibration Controls  
8
© Baxi Heating UK Ltd 2009  
2.0 General Layout  
1
2
2.2  
Flue Kit (10m & 12.5m) (Fig. 3a)  
Terminal Cap  
8
1.  
2.  
Flue Duct Adaptor  
Air Cowl  
3.  
4.  
Air Duct Collar  
5.  
Air Duct Clamp  
Closure Plate  
6.  
7.  
Boiler Adaptor  
3
8.  
60mm Ø Seal  
9.  
Collar Securing Screws x 4  
100mm Ø Seal  
10.  
11.  
12.  
13.  
9
60mm Ø Flue Duct  
100mm Ø Air Duct  
‘C’ Clip  
4
5
6
8
11  
10  
12  
7
13  
Fig. 3a  
9
© Baxi Heating UK Ltd 2009  
3.0 Technical Data  
3.1  
Bermuda HE CBBU 15 HE  
Appliance Type  
Appliance Category  
C33  
Sedbuk Declaration For Bermuda  
BBU 15 HE  
CAT I  
2H  
The seasonal efficiency (SEDBUK) is 90.1%  
Inlet Pressure (Natural Gas - G20)  
mbar 20  
This value is used in the UK Government’s  
Standard Assessment Procedure (SAP) for energy  
rating of dwellings. The test data from which it has  
been calculated has been certified by 0087.  
Injector (Natural Gas - G20)  
420 (4.2 mm)  
NO Class  
x
5 (31mg/kWh)  
Heat Input (Net)  
Max  
15.4  
Min  
5.0  
kW  
Heat Input (Gross)  
Max  
17.1  
Min  
5.7  
kW  
Heat Output (Non-Condensing)  
Max  
Min  
kW  
15.0  
4.88  
Heat Output (Condensing)  
Max  
15.7  
Min  
5.25  
kW  
Boiler Set Temperature  
°C  
Max  
75  
Min  
25  
Gas Rate  
(Natural Gas - G20)  
(After 10 mins)  
Max  
1.63  
Min  
0.54  
3
m /h  
Electrical Supply  
230V~ 50H  
z
(Appliance must be connected to an  
earthed supply)  
Boiler Power Consumption  
112W  
Boiler Electrical Protection  
IPX0  
Boiler External Fuse Rating 3A  
Connections  
Gas Supply  
Flow  
Return  
-
-
-
15mm compression  
22mm male copper  
22mm male copper  
Weights  
Packaged Boiler Carton  
Installation Lift Weight  
28 kg  
27 kg  
Flue Length  
Max  
12.5  
Min  
3.0  
Metres  
Dimensions  
Casing Height  
Casing Width  
Casing Depth  
- 538mm  
- 383mm  
- 306mm  
Firefront  
See the instructions supplied with the firefront for  
all Technical Data  
10  
© Baxi Heating UK Ltd 2009  
4.0 System Details  
4.1  
Water Circulating Systems  
1. The appliance is suitable for use on fully pumped  
systems ONLY which may be sealed or open vented.  
2. The following conditions should be observed at all  
times:  
The static head must not exceed 30m  
of water.  
The static head must not be less than  
1m of water.  
The boiler must not be used with a  
direct cylinder.  
Drain cocks should be fitted to all  
system low points.  
All gas and water pipes and electrical  
wiring must be installed in such a way  
that they do not restrict the servicing of  
the boiler.  
Position isolating valves as close as  
possible to the circulating pump.  
There is a drain cock supplied in the  
plumbing kit.  
4.2  
Treatment of Water Circulating  
Systems  
All recirculatory water systems will be subject to  
corrosion unless they are flushed and an appropriate  
water treatment is applied. To prevent this, follow the  
guidelines given in BS 7593 “Treatment of Water in  
Domestic Hot Water Central Heating Systems” and  
the treatment manufacturers instructions.  
Treatment must involve the use of a proprietary  
cleanser, such as Sentinel X300 or X400, or Fernox F3  
and an inhibitor such as Sentinel X100 or Fernox MB-1.  
Full instructions are supplied with the products, for  
further information contact Sentinel (0800 389 4670)  
or Fernox (0870 870 0362).  
Failure to flush and add inhibitor to the system will  
invalidate the appliance warranty.  
It is important to check the inhibitor concentration after  
installation, system modification and at every service in  
accordance with the inhibitor manufacturer’s  
instructions. (Test kits are available from inhibitor  
stockists.)  
For information or advice regarding any of the above  
contact Technical Enquiries 0844 871 1555.  
11  
© Baxi Heating UK Ltd 2009  
4.0 System Details  
Copper  
0.5m  
4.3  
Pipework  
Copper  
0.5m  
Flow  
1. The sizes of the flow and return pipes from the  
boiler should be determined by normal methods  
according to the requirements of the system.  
Boiler  
Return  
Copper  
1m  
2. It is recommended that the system is designed for a  
drop in temperature across the system of between  
11& 20°C.  
Fig. 4  
3. In systems using non-metallic pipework it is  
necessary to use copper pipe for the boiler Flow and  
Return. The copper must extend at least 1 metre from  
the boiler and include any branches. The copper pipe  
must not be insulated (Fig. 4).  
22mm  
Open Vent  
Air Vent  
4.4  
System Controls  
Indirect  
Cylinder  
15mm  
Cold  
Feed  
1. The system in which the appliance is installed should  
include a control system.  
2. Such a system would comprise a timer control and a  
separate room and/or cylinder thermostat as  
appropriate.  
Pump  
Radiator  
Circuit  
3. The boiler should be controlled so that it operates  
on demand only.  
Flow  
Return  
Boiler  
4.5  
Fully Pumped Open Vent System (Fig. 5)  
Fully Pumped System  
1. The sizes of the system pipes should be determined  
by normal methods.  
Fig. 5  
2. The open vent pipe should be a minimum of 22mm  
and must rise continuously to a point above the feed  
and expansion tank.  
3. The flow pipe from the boiler form part of the vent  
pipe. No part of the open vent may contain a valve.  
4. Inverted pipe runs must be avoided.  
5. On low capacity systems with a maximum available  
flow rate of less than 8.3l/min (temperature differential  
›25°C) an external bypass must be fitted .  
6. The bypass must be of the automatic pressure  
operated type.  
4.6  
Storage Systems  
1. For information regarding the use of a Bermuda  
BBU 15 HE boiler with a storage system, contact the  
appropriate storage system manufacturer.  
12  
© Baxi Heating UK Ltd 2009  
4.0 System Details  
4.7  
Sealed Systems (Figs. 6, 7 & 8)  
1. Installation. The installation must comply with the  
requirements of BS 6798 and BS EN 12828. The British  
Gas publication “British Gas Specification for Domestic  
Wet Central Heating Systems” should also be  
consulted.  
Pressure  
Gauge  
Air Vent  
2. Pressure Relief Valve. A non-adjustable spring loaded  
Safety  
Valve  
pressure relief valve, preset to operate at 3 bar  
Indirect  
Cylinder  
2
(45 lbf/in ) shall be used. It must comply with BS 6759:1  
and include a manual testing device. It shall be  
positioned in the flow pipe either horizontally or  
vertically upwards and close to the boiler. No shut off  
valves are to be placed between the boiler and the  
safety valve. The valve should be installed with a  
discharge pipe which permits the safe discharge of  
steam and hot water such that no hazard to persons or  
damage to electrical components is caused.  
Pump  
Expansion  
Vessel  
Radiator  
Circuit  
Flow  
Return  
Boiler  
3. Pressure Gauge. A pressure gauge incorporating a fill  
Filling  
Point  
pressure indicator, covering the range 0-4 bar (60  
2
lbf/in ) shall be fitted to the system. It should be  
connected to the system, preferably at the same point  
as the expansion vessel. Its location should be visible  
from the filling point.  
Fully Pumped Sealed System  
Fig. 6  
13  
© Baxi Heating UK Ltd 2009  
4.0 System Details  
4.7  
Sealed Systems (cont)  
4. Expansion Vessel. A diaphragm type expansion vessel to  
BS 4814:1 shall be fitted close to the inlet side of the pump.  
The connecting pipework should not be less than 15mm.  
Pipework connecting the expansion vessel should not  
incorporate valves of any sort.  
Temporary  
Hose  
Mains Water  
Supply  
(Service Pipe)  
Hose  
Union  
Stop  
Valve  
Methods of supporting the vessel are supplied by the vessel  
manufacturer.  
The nitrogen or air charge pressure of the expansion vessel  
shall not be less than the hydrostatic head, (height of the  
top point of the system above the expansion vessel). To  
size the expansion vessel it is first necessary to calculate the  
volume of water in the system in litres. The following  
volumes may be used as a conservative guide to calculating  
the system volume.  
Double  
Check  
Valve  
Heating  
System  
Boiler Heat Exchanger:  
Small Bore Pipework:  
Micro Bore Pipework:  
Steel Panel Radiators:  
Low Water Capacity Radiators:  
Hot Water Cylinder:  
1.55 litres  
1 litre per kW of system output  
7 litre  
8 litre per kW of system output  
1 litre per kW of system output  
1 litre per kW of system output  
Filling a Sealed Water System (Method 1)  
Mains Topping Up Method  
NOTE: This method of filling a sealed system  
may only be used if acceptable to Local Water  
Undertaking  
Fig. 7  
If the system is extended, the expansion vessel volume may  
have to be increased unless provision has been made for  
extension. Where a vessel of the calculated size is not  
available, the next available larger size should be used.  
The boiler flow temperature is controlled at approx. 75°C.  
The vessel size can now be determined from the  
information in table 1 where V = System volume in litres.  
5. Cylinder. The hot water cylinder must be an indirect  
coiler type.  
Mains Water  
Supply  
6. Method of Make Up. Provision shall be made for  
replacing water loss from the system either:-  
Cistern  
Pressure Pump  
Reducing Valve  
(if required)  
a) From a make up vessel or tank mounted in a position  
higher than the top point of the system and connected  
through a non-return valve to the system on the return side  
of the hot water cylinder or the return side of all heat  
emitters.  
or  
b) Where access to a make up vessel would be difficult by  
using the mains top up method or a remote automatic  
pressurisation and make up unit.  
Stop  
Valve  
7. Mains Connection. There shall be no connection to the  
mains water supply or to the water storage tank which  
supplies domestic hot water even through a non-return  
valve, without the approval of the Local Water Authority.  
Heating  
System  
Filling a Sealed Water System (Method 2)  
8. Filling Point. A filling point connection on the central  
heating return pipework must be provided to facilitate initial  
filling and pressurising and also any subsequent water loss  
replacement/refilling.  
Cistern Filling Method  
Fig. 8  
NOTE: Cistern to be supplied through a  
temporary connection from a service pipe or  
cold water distributing pipe  
The sealed primary circuits may be filled or replenished by  
means of a temporary connection between the circuit and a  
supply pipe, provided a ‘Listed’ double check valve or some  
other no less effective backflow prevention device is  
permanently connected at the inlet to the circuit and the  
temporary connection is removed after use.  
The filling method adopted must be in accordance with all  
relevant water supply regulations and use approved  
equipment.  
Vessel Charge Pressure (bar)  
Initial System Pressure (bar)  
Expansion Vessel Volume (litres)  
0.5  
1.0  
1.5  
1.0  
V x 0.11  
V x 0.087  
Your attention is drawn to: for GB: Guidance G24.2 and  
recommendation R24.2 of the Water Regulations Guide. for  
IE: the current edition of IS 813 “Domestic Gas  
Installations”.  
Table 1  
14  
© Baxi Heating UK Ltd 2009  
5.0 Site Requirements  
5.1  
Builders Opening (Fig. 9)  
Builders  
Opening  
1. The boiler unit is designed to fit within a standard  
builders opening, the minimum dimensions of which are  
as shown.  
Fireplace  
Opening  
Height  
Width  
Depth  
570mm  
584mm  
305mm  
390mm min  
490mm max  
2. The opening should be soundly constructed of brick,  
pre-cast concrete or be a proprietary builders opening.  
584mm min  
3. The base of the opening should be sound and non-  
combustible and must be flat and level.  
4. The base of the builders opening should be at the  
same height as the finished level of the hearth.  
SURROUND OR FINISHED  
WALL FACE  
IMPORTANT: If a false chimney breast is intended  
to house the boiler, a simulated builders opening,  
within the breast, must be provided.  
5. The builders opening must not communicate with  
voids, pipe ducts or spaces other than the room in  
which the appliance is situated.  
Solid, non combustible hearth  
to support the boiler,  
as specified in BS 5871.  
5.2  
Location  
HEARTH  
LEVEL  
1. The appliance must be installed in the living space of a  
dwelling. It is recommended that it is a ground floor  
location.  
305mm minimum  
Fig. 9  
2. Restrictions to the siting of the appliance are covered  
by BS 5546. The appliance may not be installed in  
bathrooms or shower rooms. bedrooms or bed sitting  
rooms.  
5.3  
Fireplace Opening & Surround  
1. If a fireplace surround is to be used, it must be  
centrally placed and have opening sizes as shown in  
Fig. 9.  
5.4  
Firefont Frame Extension Kit  
1. To accommodate the firefront there must be at least  
95mm from the surround or finished face to the front of  
the boiler.  
2. If necessary this can be increased by the use of Frame  
Extension Kits. Each extension increases the effective  
depth of the opening by 50mm.  
3. See the instructions supplied with the firefront for full  
details.  
15  
© Baxi Heating UK Ltd 2009  
5.0 Site Requirements  
5.5  
Flue  
1. The following guidelines indicate the general  
requirements for installation of flues.  
For GB recommendations are given in BS 5440 Part 1.  
For IE recommendations are given in the current edition  
of I.S. 813 “Domestic Gas Installations”.  
A
B
2. Only one of the two available MULTIIFIT vertical  
concentric Flexi Flue kits approved for use with the  
boiler can be used (10m kit 720101701 or 12.5m kit  
720102001). Any proprietary flue systems, terminals,  
adaptors etc. MUST NOT BE USED.  
C
3. The available flue kits are intended for installation  
within an existing chimney. This should be clean and  
sound, and any other previously installed flue  
components (liners, dampers etc.) removed.  
4. The flue must have a minimum vertical height of 3m  
and have no bends greater than 45°.  
NO HORIZONTAL RUNS ARE PERMITTED !  
5. The terminal must be sited so that free passage of air  
across it can occur at all times.  
Fig. 10  
6. It must also be a MINIMUM of 150mm from any  
other terminals or obstructions (A). When adjacent to  
windows or openings on pitched or flat roofs it must be  
at least 600mm away (B). A minimum dimension of  
2000mm must be maintained when below windows or  
openings in pitched roofs (C) (Fig. 10).  
16  
© Baxi Heating UK Ltd 2009  
5.0 Site Requirements  
5.6  
Ventilation  
1. No ventilation is required for the boiler in the room of  
installation.  
5.7  
Gas Supply (Fig. 11)  
1. The gas installation should be in accordance with  
relevant standards. In GB this is BS 6891. In IE this is I.S.  
813 “Domestic Gas Installations”. The connection at the  
appliance is 15mm copper tail located at the rear of the  
gas tap.  
2. Ensure the pipework from the meter to the appliance is  
of adequate size. It is necessary to route the gas supply  
pipe to the right hand side of the builders opening. It must  
be routed so as not to restrict the installation and  
servicing of the appliance.  
5.8  
Electrical Supply (Fig. 11)  
1. External wiring must be correctly earthed, polarised and  
in accordance with relevant regulations/rules. In GB this is  
the current I.E.E. Wiring Regulations. In IE reference  
should be made to the current edition of the ETCI rules.  
The mains supply is 230V ~ 50Hz fused at 3A.  
NOTE: The method of connection to the electrical supply  
must facilitate complete electrical isolation of the  
appliance. Connection may be made via a fused double  
pole isolator with a contact separation of at least 3mm on  
all poles and serve the boiler and system controls only.  
The boiler MUST NOT be connected to the same supply  
as the firefront as their fuse ratings are different and  
subsequent damage may occur.  
Fig. 11  
Electrical Connection  
2. The boiler supply cable within the builders opening  
2
should be 0.75mm to IEC 53 code 227 (heat resistant).  
3. It is preferable to route the electrical supply cable to  
the right hand side of the builders opening. If however it  
must come from the left hand side it must be routed so  
as not to restrict the servicing of the appliance.  
Gas Connection  
4. The cable must be routed to avoid contact with any  
part of the boiler.  
17  
© Baxi Heating UK Ltd 2009  
5.0 Site Requirements  
5.9  
Condensate Drain - General  
Failure to install the condensate discharge pipework  
correctly will affect the reliable operation of the boiler.  
1. Ensure the discharge of condensate complies with any  
national or local regulations in force.  
BS 6798 & Part H1 of the Building Regulations give further  
guidance.  
2. If any further drain pipe is required (additional to that supplied  
with the boiler), it should be run in a proprietary material  
e.g. PVC, PVC-U, ABS, PVC-C or PP. John Guest ‘Speedfit’  
components are recommended.  
3. Metal pipework is NOT suitable for use in condensate  
discharge systems.  
4. Any pipe fitted externally must be kept as short as possible to  
minimise the potential of freezing and must be insulated using  
waterproof material.  
Min. radius 100mm  
Point ‘A’  
Gravity Drain  
min. fall 3°  
5. When discharging condensate into a soil stack or waste pipe  
the effects of existing plumbing must be considered.  
Max. Head  
3.5 metres  
Note: The point of discharge from the  
pumped length of condensate pipe  
(point ‘A’) must be 150mm above the  
base level of the boiler, whether  
discharging direct into a drain or into  
an additional gravity drain.  
5.10  
Condensate Disposal (Fig. 12)  
1. This boiler incorporates an automatic pumped condensate  
system. The pump is submerged in a sump assembly and is  
activated by the discharge float switch. A second (safety) float  
switch is fitted.  
Boiler  
2. The pump has an effective head of 3.5 metres. The  
condensate outlet is positioned at the top right front of the  
boiler. It is 10mm diameter plastic.  
3. 3.5 metres of flexible 10mm condensate discharge pipe and a  
10mm push fit elbow are supplied with the boiler.  
Fig. 12  
4. The 10mm pipe can be routed to a maximum of 3.5 metres  
vertically and then discharge via gravity or be routed  
horizontally. A combination of vertical and horizontal runs is  
permissible.  
5. The pipe must be adequately supported, either using suitably  
spaced clips or run within larger diameter pipe. When using clips  
take care not to deform the pipe.  
6. When routing the pipe through a wall it must be suitably  
sleeved. Also the pipe must not be exposed to sources of heat,  
and should be protected in locations where it may be damaged.  
7. The pipe should be routed so that any sharp bends, dips and  
loops are avoided. A minimum radius of 100mm is  
recommended for any bends. No slope is necessary and air  
breaks are not required on the pumped part of the condensate  
run.  
8. Any part of the condensate drain system that is outside the  
dwelling, or in an unheated part of it must be at least 21.5mm  
diameter.  
18  
© Baxi Heating UK Ltd 2009  
5.0 Site Requirements  
5.10  
Condensate Disposal (cont.)  
Termination via internal discharge branch e.g  
sink waste - downstream  
9. Ensure that the condensate can discharge freely (without  
blockage or restriction of the pipe) into the drain.  
Pipe must terminate  
above water level but  
below surrounding surface  
Direct Connect Fitting  
10. Examples are shown of condensate pipe methods of  
termination:-  
Sink  
i) via an internal discharge branch  
(e.g. sink waste) - Fig. 13.  
ii) to an internal or external soil and vent pipe -  
Fig. 14.  
From Boiler  
iii) to a drain or gully - Fig. 15. Ensure that the  
condensate can discharge freely (without  
blockage or restriction of the pipe) into the  
drain.  
Fig. 13  
Termination to an internal soil and vent pipe  
iv) to a soakaway - Fig. 16.  
Direct Connect Fitting  
5.11  
Condensate Pump Operation  
1. The pump operates for 2 seconds when mains voltage is  
applied to the boiler, e.g. when the power has been  
interrupted and then reinstated.  
From Boiler  
Min. 450mm  
Fig. 14  
2. If the boiler reset rocker switch has been operated the  
pump will run also for 2 seconds.  
Termination to a drain or gully  
Pipe must terminate above  
water level but below  
surrounding surface  
3. When the level of condensate in the sump is sufficient to  
activate the discharge float switch the pump will run for 7  
seconds, during which time about 0.6 litres of condensate will  
be discharged.  
From Boiler  
Fig. 15  
4. In the event of condensate not being discharged the safety  
float switch will operate when the volume of condensate in  
the sump reaches 1.05 litres. Once the safety float switch has  
been activated the boiler will lockout.  
500mm Min.  
5. The total volume of the sump is 1.5 litres.  
Termination to a purpose made  
soak-away  
From Boiler  
Fig. 16  
Holes in the soak-away must  
face away from the building  
19  
© Baxi Heating UK Ltd 2009  
6.0 Boiler Internal Wiring  
6.1  
Boiler Internal Illustrated Wiring Diagram  
Central Heating  
NTC Flow Sensor  
gr  
gr  
OverheatThermostat  
Discharge Float  
Switch  
Safety Float  
Switch  
bk  
b
1
4
2
bk  
r
5
br  
b
gr  
gr  
g
Fan  
3
bk  
bk  
1
bk  
2
b
g/y  
br  
bk  
bk  
X400  
X401  
X900  
5
4
3
2
1
5
4
3
2
1
9
8 7  
6
10  
9
8 7  
6
X300  
Control PCB  
r
X501  
X500  
Condensate Pump  
5
6
7
8
9
y
1
2
1
2
3
4
5
1
2
3
4
X1  
X2  
X3  
b
b
br  
bk  
bk  
bk  
br  
bk  
br  
bk  
b
br  
b
ON/OFF  
Reset  
b
br  
b
b
b
br  
1
br  
3
b
Spark  
Generator  
a
N
2
GasValve  
r
r
bk  
b
Ignition  
Electrode  
y
3
N
2
1
Mains Input  
(Permanent Live to 3,  
Switched Live to 1)  
b
y
g
- green  
g/y - green / yellow  
- red  
gr - grey  
br - brown  
bk - black  
r
b
w
y
- blue  
- white  
- yellow  
20  
© Baxi Heating UK Ltd 2009  
7.0 Installation  
INSTALLATION SEQUENCE  
There are 4 main elements to the installation of the  
Baxi Bermuda BBU 15 HE:-  
• Preparation of pipework & opening  
• Inserting the flue into the chimney  
• Siting & fixing the boiler  
• Fitting the terminal assembly  
The sequence in which these are performed may  
depend upon various factors beyond the scope of  
these instructions. The above list is intended as a  
guide based on a typical installation.  
It is not necessary to open the firefront pack until  
the boiler and flue are installed, and the boiler is  
ready to be commissioned. The firefront pack  
includes full instructions.  
7.1  
Initial Preparation  
1. Remove the outer carton from the boiler pack.  
Discard the packing pieces and remove the fitting kit.  
Fig. 17  
2. Ensure that the base of the builders opening is clean  
and level.  
3. Complete any pipework installation and routing of  
electrical cables within the builders opening that may be  
difficult once the boiler is in place.  
7.2  
Flue System  
1. The actual length of flue (as opposed to the vertical  
distance from the boiler top to the chimney outlet)  
MUST be established before commencing.  
Fig. 18  
2. The flue must have a minimum vertical height of 3m  
and have no bends greater than 45°.  
NO HORIZONTAL RUNS ARE PERMITTED !  
3. Depending on the actual flue length it may be  
beneficial to shorten the flue at this point to enable  
easier handling.  
4. Take one of the 60mm lip seals supplied and fit to  
the first groove in the flue duct. Also fit the 100mm lip  
seal to the air duct. (Figs. 17 & 18).  
Fig. 19  
NOTE: Talcum powder may be used to ease fitting  
of the adaptors over the seals. DO NOT use oil,  
grease or soap.  
5. Unfasten the clips on the boiler adaptor and insert  
the end of the flue duct with the seal into the 60mm  
socket. Ensure the seal is positioned past the clips, then  
engage the clips over the larger diameter ‘rib’ on the  
duct (Fig. 19).  
6. Repeat the process for the 100mm air duct (Fig. 20)  
Fig. 20  
21  
© Baxi Heating UK Ltd 2009  
7.0 Installation  
7.2  
Flue System (cont.)  
8. It is recommended that the Pull Cone Flue Adaptor  
(part no. 720111801) is used as shown to ease the  
fitting of the flue into the chimney and prevent damage  
to the adaptor.  
Fig. 22  
Fig. 21  
9. The cone has two internal lugs that engage on the  
boiler adaptor in a bayonet action (Figs. 21 & 22).  
10. A suitable weight should then be tied to the guide  
rope fixed to the cone. The weight can then be passed  
into the chimney and will draw the guide rope down  
(Fig. 23).  
Remove plug  
from here  
11. Once the Pull Cone is visible in the builders opening  
it can be removed. It can be re-used indefinitely on  
other installations.  
Note: It is recommended that the boiler is installed  
at this point. See Sections 8.3 to 8.7  
NOTE: These seals  
factory lubricated  
Fig. 23  
12. Remove the plastic plug from the boiler flue outlet.  
Grasp the adaptor and locate it into the boiler, ensuring  
the two large barbs lock into position under the boiler  
top panel (Fig. 24) Fit the ‘C’ clip to the adaptor to  
secure the flue. It must fit into the barbs and clip  
securely into place (Fig. 24a).  
Fig. 24  
Barb  
13. There will now be an excess of flue and air duct  
protruding from the chimney.  
14. Cut the excess concentric ducts to leave  
approximately 300 to 500mm protrudung from the  
chimney and pass the square closure plate over the air  
duct (Figs. 25 & 26).  
‘C’ Clip  
15. Cut the 100mm air duct ONLY that 5 ‘ribs’ are  
above the level of the chimney, taking care not to  
damage the 60mm flue duct.  
Fig. 24a  
16. In a similar way to fitting the boiler adaptor fit the  
air duct clamp to the air duct. This will prevent the duct  
falling back into the chimney (Fig. 27).  
Cut to leave  
5 ribs visible  
Fig. 25  
Fig. 27  
Fig. 26  
22  
© Baxi Heating UK Ltd 2009  
7.0 Installation  
7.2  
Flue System (cont.)  
Air Cowl  
16. Pass the air duct collar and air cowl over the 60mm  
flue duct (Fig. 28) and secure the collar to the closure  
plate with the screws supplied (Fig. 29). The air cowl  
will fit snugly over the collar.  
Fig. 29  
17. Cut the protruding 60mm flue duct down so that 5  
ribs are visible and fit the remaining 60mm lip seal into  
the first groove (Fig. 30). The flue duct adaptor can  
now be fitted in the same manner as the boiler adaptor  
(Fig. 31).  
Air Duct  
Collar  
5 ribs  
18. Fit the terminal cap over the flue duct adaptor and  
air cowl. Once the cap is clipped into position it cannot  
be removed easily without damage (Fig. 33).  
Fig. 28  
19. Cement over the closure plate and air duct collar to  
a depth of approximately 100mm. Consideration should  
be given to the potential accumulation of snow in this  
area, and the possibility of it blocking the air inlet  
(Fig. 34).  
Fig. 30  
Fig. 31  
Fig. 32  
Terminal  
Cap  
Cement around  
Air Duct Collar  
& Cowl  
Fig. 33  
Fig. 34  
23  
© Baxi Heating UK Ltd 2009  
7.0 Installation  
7.3  
Siting the Boiler  
IMPORTANT - This product should be lifted and  
handled by two people. Stooping should be avoided and  
protective equipment worn where necessary. Carrying  
& lifting equipment should be used as required, e.g.  
when installing on another floor.  
Fixing Slot  
1. Lift the boiler from the packing base and place into the  
opening.  
2. Align the boiler centrally as far back in the opening as  
possible, and ensure the distance between each side and  
the opening is equal. Check that the boiler is level.  
3. Mark the hearth through two of the slots in the base  
(Fig. 35). Remove the boiler and drill the hearth. Insert  
suitable plugs. Replace the boiler & check the alignment  
within the opening. Secure the boiler with suitable screws.  
Fig. 35  
Condensate  
7.4  
Water Connections  
Discharge (remove  
plug before connection)  
1. The boiler has one return and one flow connection. The  
flow is the upper connection. It is essential the flow and  
return pipes are connected correctly (Fig. 36).  
7.5  
Gas Connection  
1. Connection to the gas supply is a 15mm compression  
fitting on the gas cock. The gas supply pipe must be routed  
from the right hand side.  
2. The positioning of the gas supply pipe must not restrict  
the servicing of the boiler or installation of the firefront.  
7.6  
Electrical Connection  
1. The boiler requires an electrical supply from the heating  
controls system.  
Return  
Flow  
WARNING: The appliance must be earthed.  
The input cable for the appliance should be 0.75mm2 to  
IEC Code 227 (heat resistant). The system external  
controls and the boiler must be supplied by the same  
isolator. The boiler MUST NOT be connected to the  
same supply as the firefront as their fuse ratings are  
different.  
Fig. 36  
7.7  
Making the Electrical Connection  
1. Take the 5 pin plug from the boiler fitting kit, remove  
the securing screws and hinge the cover open.  
3
2. Route the mains inlet cable under the cable clamp and  
connect Permanent Live, Neutral & Earth to 3, N &  
respectively. Ensure that the Earth lead is longest.  
N
3. Connect the switched output from the system external  
control system to terminal 1.  
Fig. 37  
1
2
4. Refit the cover, tighten the screws to secure the cable  
and connect the plug to the one on the boiler.  
24  
© Baxi Heating UK Ltd 2009  
Auto Air  
Vent  
8.0 Completion & Commissioning  
ON/OFF  
8.1  
Completion  
Service  
Reset  
1. Seal off any secondary openings within the builders  
opening after wrapping the gas and water pipes through the  
brickwork and within the opening itself. (B.S. 5871 Part 1).  
2. Take the Boiler Control from the firefront packaging and  
connect it to the boiler (Fig. 38).  
8.2  
Commissioning the Boiler  
1. Reference should be made to BS 5449 Section 5 when  
commissioning the boiler.  
Fig. 38  
2. At the time of commissioning, complete all relevant  
sections of the Benchmark Checklist at the rear of this  
publication.  
IMPORTANT: The heat exchanger air vent on top of the  
boiler (Fig. 38) MUST be opened before filling the  
primary system.  
3. Ensure all valves in the water system are turned on.  
4. The system must be flushed in accordance with BS 7593  
(see Section 5.2) and the flushing agent manufacturers  
instructions.  
Fig. 39  
5. Turn the gas supply on and purge according to in GB BS  
6891 and in IE I.S. 813 "Domestic Gas Installations".  
6. Test for gas soundness.  
7. Ensure all external controls e.g. room stat, timer etc. are  
calling for heat and turn on the mains electrical supply. Turn  
the rocker switch at the top right of the boiler to ON. The  
fan and condensate pump will run briefly.  
Countdown  
8. The display will count down from 7 to 0, then the current  
water temperature will be displayed.  
9. When there is a demand for heating the bar on the top  
left of the display will be shown and the boiler will  
commence the ignition sequence.  
Current Temp.  
& Demand  
10. When ignition is established the ‘flame’ symbol on the  
display is illuminated. The display will indicate the flow  
temperature. The appliance is fully preset, therefore no  
adjustment is required.  
Burner Lit  
11. If the boiler fails to ignite within the three ignition  
attempts the error code E133 will appear in the display, ‘E1’  
alternating with ‘33’.  
12. To reset the boiler press the reset button for at least 3  
seconds. The ignition sequence will then recommence. A  
maximum of four resets in a five hour period are allowed.  
Remaining  
Resets  
13. When the reset button is activated the number of  
available reset attempts will be displayed  
Fig. 40  
25  
© Baxi Heating UK Ltd 2009  
8.0 Completion & Commissioning  
8.2  
Commissioning the Boiler (cont.)  
IMPORTANT: The combustion for this appliance has  
been checked, adjusted and preset at the factory for  
operation on the gas type specified on the appliance data  
plate. No measurement of the combustion is necessary.  
Do not adjust the air/gas ratio valve.  
Having checked:  
That the boiler has been installed in accordance with  
these instructions.  
The integrity of the flue system and the flue seals, as  
described in Section 7.2.  
Proceed to put the boiler into operation as follows:  
Check the Operational Gas Inlet Pressure  
14. Set the boiler to operate at maximum rate as  
described in Section 11.1.2 to 11.1.6.  
15. With the boiler operating in the maximum rate  
condition check that the operational gas pressure at the  
inlet gas pressure test point is 20mb (Fig. 40a).  
16. Ensure that this inlet pressure can be obtained with  
all other gas appliances in the property working.  
Measure the Gas Rate  
17. With any other appliances & pilot lights turned OFF  
the gas rate can be measured. It should be between 1.55  
Inlet Gas Pressure  
Test Point  
Fig. 40a  
3
and 1.71m /h.  
18. Carefully read and complete all sections of the  
Benchmark Commissioning Checklist at the rear of this  
publication that are relevant to the boiler and installation.  
These details will be required in the event of any  
warranty work. The publication must be handed to the  
user for safe keeping and each subsequent regular service  
visit recorded.  
For IE, it is necessary to complete a “Declaration of  
Conformity” to indicate compliance with I.S. 813. An  
example of this is given in I.S. 813 “Domestic Gas  
Installations”. This is in addition to the Benchmark  
Commissioning Checklist.  
19. Disconnect the Boiler Control and fit the firefront in  
accordance with the instructions supplied with it.  
IMPORTANT: The loose boiler serial number label  
supplied in the boiler kit must be applied to an area of  
the spacer frame that is visible to the end user e.g.  
lower right hand side.  
26  
© Baxi Heating UK Ltd 2009  
9.0 Annual Servicing  
9.1  
Annual Servicing  
1. For reasons of safety and economy, it is recommended that  
the boiler is serviced annually. Servicing must be performed by  
a competent person in accordance with B.S. 7967-4.  
2. After servicing, complete the relevant Service Interval  
Record section of the Benchmark Commissioning Checklist at  
the rear of this publication.  
3. Disconnect the firefront electric supply. Remove the fascia  
from the firefront. Unhook its hanging brackets from the slots  
in the top of the firefront. On Classica and Innova models also  
disengage the retaining magnets at the lower part of the fascia.  
4. Slacken the firefront retaining wire and unthread it from the  
bracket on top of the boiler. The firefront can now be  
manoeuvred away from the boiler. Do not drag the firefront  
as it may damage the hearth. To completely remove the  
firefront disconnect the boiler control cable.  
Flue Sampling  
Plug  
IMPORTANT: During routine servicing, and after any  
maintenance or change of part of the combustion circuit, the  
following must be checked:-  
The integrity of the flue system and the flue seals, as  
described in Section 7.2.  
The integrity of the boiler combustion circuit and relevant  
seals as described in Section 9.2.  
The operational gas inlet pressure as described in Section  
8.2.14 to 8.2.16 and the gas rate as described in 8.2.17.  
The combustion performance as described in 9.1.5 to 9.1.6.  
Competence to carry out checking Combustion  
Performance  
B.S. 6798 ‘Specification for Installation & Maintenance of Gas  
Fired Boilers not exceeding 70kW’ advises that:-  
The person carrying out a combustion measurement  
should have been assessed as competent in the use of a  
flue gas analyser and the interpretation of the results.  
Fig. 41  
The flue gas analyser used should be one meeting the  
requirements of BS7927 or BS-EN50379-3 and be  
calibrated in accordance with the analyser manufacturers’  
requirements.  
Off Position  
Competence can be demonstrated by satisfactory  
completion of the CPA1 ACS assessment, which covers  
the use of electronic portable combustion gas analysers in  
accordance with BS 7967, Parts 1 to 4.  
Check the Combustion Performance  
5. Set the boiler to operate at maximum rate as described in  
Section 11.1.2 to 11.1.6.  
6. Remove the threaded plug from the sampling point, insert  
the analyser probe and obtain the CO/CO2 ratio. This must  
be less than 0.004.  
On Position  
7. If the combustion reading is greater than this, and the  
integrity of the flue system and combustion circuit seals has  
been verified, and the inlet gas pressure and gas rate are  
satisfactory either adjust the gas valve (Section 11.0), replace  
the gas valve (Section 10.8) or contact the ‘heateam’ Technical  
Helpline (0844 871 1555).  
Fig. 42  
27  
© Baxi Heating UK Ltd 2009  
9.0 Annual Servicing  
PCB Control Box  
Securing Screw  
9.2  
Annual Servicing - Inspection  
Reset Switch  
1. Ensure that the boiler is cool.  
PCB Control  
Box  
2. Ensure that the gas supply to the boiler is isolated.  
3. Operate the Reset switch (Fig. 41) to activate the  
condensate pump and then repeat. This will empty most of  
the condensate from the sump.9. Isolate the boiler from the  
electrical supply.  
4. Undo & remove the flue sampling plug and washer. Remove  
the screws retaining the boiler front panel, and lift the panel  
away (Fig. 43).  
Off Position  
Fig. 43  
5. Remove the screw securing the PCB control box and swing  
the box to the right (Fig. 43).  
Boiler Front  
Panel  
6. Disconnect the two plugs from the fan motor and remove  
the sensing pipe from between the gas valve and fan outlet.  
7. Remove the gas feed pipe and washers, and extract the  
injector from the gas/air inlet manifold.  
Spark  
Generator  
8. For ease of access disconnect the following:-  
a) 2 pin plug on NTC lead  
b) all wires from electrode assembly  
c) all wires from spark generator  
d) both wires from the overheat thermostat  
e) the red and black wires connected together  
Electrode  
Assembly  
9. Undo the two securing nuts and remove the spark  
generator and bracket.  
10. Undo the combustion panel securing nuts and remove the  
special spring washers. Remove the complete fan & panel  
assembly from the boiler.  
Injector  
Sensing Pipe  
Gas Valve  
11. Lay the assembly to one side. The outer insulation panel is  
fitted to the rear of the combustion box panel.  
Gas Feed  
Pipe  
12. Clean inside the heat exchanger and examine the  
condition of the fins.  
13. Examine the burner, electrodes, insulation and seal,  
replacing if necessary. Also check the condition of the three  
insulation pieces in the rear of the heat exchanger.  
Discharge Pipe  
14. Disconnect the wires on the condensate pump motor and  
pull off the plastic discharge pipe. Cut and remove the transit  
cable tie. It is not necessary to replace this item.  
Locking Clip  
Fan  
15. Squeeze the two retaining clips and turn the pump  
anticlockwise to remove it. Draw it upwards from the sump.  
Condensate Pump  
16. Clean any debris from the sump and examine the  
condition of the pump seal, replacing if necessary.  
17. Reassemble in reverse order of dismantling, checking and  
replacing any components as necessary. Recommission the  
boiler and complete the relevant Service Interval Record  
section of the Benchmark Commissioning Checklist at the rear  
of this publication.  
Fig. 44  
28  
© Baxi Heating UK Ltd 2009  
10.0 Changing Components  
10.1  
Changing Components  
1. To change any components on the back boiler it is  
necessary to remove the firefront.  
2. Refer to the Installer Guide that accompanies the  
firefront for details of removal.  
3. Ensure that the boiler is cool and that the electrical  
and gas supplies are isolated.  
4. After changing any components carry out gas  
soundness checks.  
Fig. 45  
5. Undo & remove the flue sampling plug and washer.  
Remove the screws retaining the boiler front panel, and  
lift the panel away.  
Spark Generator  
6. Remove the screw securing the PCB control box and  
swing the box to the right.  
10.2  
Spark Generator (Fig. 46)  
Plug  
1. Note the position of the two leads on the spark  
generator and disconnect them. Also disconnect the  
earth wire and plug, and remove the screws securing the  
spark generator to the bracket.  
Fig. 46  
2. Remove the spark generator. Replace in reverse order  
of dismantling, using the screws previously removed.  
3. Ensure that the leads and plug are pushed fully on to  
their terminals.  
10.3  
Electrode Assembly (Fig. 47)  
PCB Control Box  
removed for clarity  
1. Note the position of the two leads on the electrode  
assembly and disconnect them. Disconnect the in-line  
connection on the black wire and the earth wire.  
2. Undo the securing screws and remove the electrode  
assembly and earth tag from the combustion box panel.  
Sealing Gasket  
3. Replace in reverse order of dismantling, using the  
screws previously removed. Examine the sealing gasket  
and replace if necessary.  
Electrode  
Fig. 47  
4. Ensure that the leads are pushed fully on to their  
terminals.  
Condensate Pump  
10.4  
Condensate Pump (Fig.48)  
1. Note the position of the two leads and earth wire on  
the pump motor and disconnect them.  
Locking Clip  
2. Cut and remove the transit cable tie. It is not  
necessary to replace this item.  
3. Squeeze in the two locking clips and turn the pump  
anti-clockwise. Pull the condensate discharge pipe off its  
connection and remove the pump.  
4. Replace in reverse order of dismantling. Examine the  
sealing ring and replace if necessary.  
5. Ensure that the leads are pushed fully on to their  
terminals.  
Fig. 48  
29  
© Baxi Heating UK Ltd 2009  
Spark Generator  
10.0 Changing Components  
10.5  
Fan (Fig. 49)  
1. Disconnect the two plugs from the fan motor and  
remove the sensing pipe from between the gas valve  
and fan outlet.  
Plug  
2. Remove the gas feed pipe and washers, and extract  
the injector from the gas/air inlet manifold.  
Injector  
3. For ease of access disconnect the following:-  
a) 2 pin plug on NTC lead  
Note position  
of Slot  
b) all wires from electrode assembly  
c) all wires from spark generator  
Electrode  
d) both wires from the overheat thermostat  
e) the red and black wires connected together  
4. Undo the two securing nuts and remove the spark  
generator and bracket.  
5. Undo the combustion panel securing nuts and remove  
the special spring washers. Remove the complete fan &  
panel assembly from the boiler. Check the condition of  
the insulation piece.  
Fig. 49  
6. Undo and remove the nuts and washers securing the  
fan to the gas/air inlet. NOTE THE POSITION OF THE  
RESTRICTOR PLATE !  
Fan  
7. Remove the securing screws and transfer the fan inlet  
to the new fan. Use a new sealing gasket if necessary.  
8. Replace in reverse order. ENSURE THAT THE  
RESTRICTOR PLATE IS CORRECTLY FITTED ! THE  
SLOT MUST BE TO THE REAR. Check the condition of  
the sealing gaskets between the fan and gas/air inlet and  
the combustion panel and heat exchanger and replace if  
necessary.  
10.6  
Burner (Fig. 50)  
1. Proceed as described in points 1. to 5. above.  
2. Undo the screws securing the burner to the  
combustion panel. Remove the burner.  
3. Replace in reverse order of dismantling, using the  
screws previously removed. Examine the sealing gasket  
and replace if necessary.  
PCB Control Box  
removed for clarity  
10.7  
Injector (Fig. 50)  
Burner  
1. Remove the gas feed pipe and washers, and extract  
the injector from the gas/air inlet manifold.  
2. Replace in reverse order of dismantling. Examine the  
sealing washers and replace if necessary.  
Spark Generator  
Plug  
Fig. 50  
Gas Feed  
Pipe  
Injector  
30  
© Baxi Heating UK Ltd 2009  
10.0 Changing Components  
10.8  
Gas Valve (Fig. 51)  
IMPORTANT: After replacing the valve the CO2 must be  
checked and adjusted as detailed in Section 11.0 Setting  
the Gas Valve. Only change the valve if a suitable  
calibrated combustion analyser is available, operated by a  
competent person - see Section 9.1  
1. Disconnect the plug and earth wire from the gas valve and  
remove the sensing pipe from between the valve and fan  
outlet.  
2. Remove the gas feed pipe and washers, and extract the  
injector from the gas/air inlet manifold.  
3. Undo the nut on the pipe from the gas cock to the valve  
inlet adaptor, and remove the screws securing the adaptor to  
the boiler side panel.  
PCB Control Box  
removed for clarity  
4. Remove the valve complete with the inlet and outlet  
adaptors, and the seal on the inner face of the side panel.  
Transfer the adaptors to the new valve, using new ‘O’ rings if  
necessary.  
5. Replace in reverse order of dismantling, using the screws  
previously removed. Examine all sealing gaskets and washers  
and replace if necessary.  
Injector  
NOTE: To assist the boiler to light prior to final setting,  
use a suitable hexagon key to wind out the Gas/Air  
adjustment screw until it is flush with the valve body, then  
turn the screw 4 full turns clockwise (Fig. 51). If the boiler  
will not light, or the correct CO2 cannot be achieved  
contact the ‘heateam’ technical helpline.  
Gas Valve  
Earth Wire  
Fig. 51  
31  
© Baxi Heating UK Ltd 2009  
10.0 Changing Components  
Safety Thermostat  
10.9  
PCB (Fig. 54)  
1. Pull off the two control knobs and disengage the  
securing tabs of the cover. Undo the screws securing the  
PCB.  
Flow Pipe  
2. Draw the PCB forwards and disconnect the wiring.  
Transfer the two potentiometer drive pins to the new  
PCB and replace in reverse order of dismantling.  
Fig. 52  
3. Ensure that the wiring connectors are pushed fully on  
to the PCB terminals.  
10.10 NTC (Fig. 53)  
1. Disconnect the 2 pin plug. Remove the clip retaining  
the NTC in the heat exchanger pocket. Pull the NTC  
out of the pocket.  
2. Apply suitable heat transfer paste to the new NTC.  
Replace in reverse order of dismantling, using the clip  
previously removed. Ensure that the plug is fully engaged.  
Clip  
10.11 Safety Thermostat (Fig. 52)  
1. Disconnect the two leads from the thermostat.  
Fig. 53  
NTC  
2. Remove the screws securing the thermostat to the  
mounting plate on the flow pipe.  
3. Replace in reverse order. The thermostat is not  
polarised - either wire can fit either terminal on the  
thermostat.  
10.12 Float Switches (Fig. 55)  
1. Remove the fan as described in Section 10.5,  
paragraphs 1 to 5.  
2. The two float switches are the same, but oriented  
differently. The discharge switch is at the left, the safety  
at the right.  
PCB  
3. To remove either switch disconnect the lead and pull  
off the alignment bracket.  
Fig. 54  
4. Undo the retaining nut. The sealing grommet will be  
released from the sump body and allow the switch to be  
removed.  
Control Knobs  
5. Note the orientation of the alignment rib on the  
switch. It is positioned uppermost on the safety float  
switch and to the bottom on the discharge switch.  
Discharge  
Float Switch  
6. Take the new switch assembly and insert it into the  
sump. Hand tighten the nut and slide the alignment  
bracket in place to ensure the switch is in position.  
Tighten the nut a further 2 turns.  
7. Reconnect the lead to the switch, ensuring it is fully  
engaged.  
Safety Float  
Switch  
Alignment  
Bracket  
Fig. 55  
32  
© Baxi Heating UK Ltd 2009  
11.0 Setting the Gas Valve  
11.1  
Setting the Gas Valve (CO2 check)  
IMPORTANT: The CO2 must be only be checked and  
adjusted to set the valve if a suitable calibrated  
combustion analyser is available, operated by a  
competent person - see Section 9.1  
Flue Sampling  
Point  
1. The combustion (CO2) may be checked after running the  
boiler for several minutes. To do this it is necessary to set  
the boiler to ‘Calibration Mode’.  
Display  
2. Ensure that all external controls are calling for heat. The  
actual current boiler temperature is shown on the display.  
3. Turn both control knobs fully anticlockwise, then quickly  
1
Fig. 56  
turn the right hand knob /4 clockwise twice and back fully  
Control  
Knobs  
anticlockwise (Fig. 56).  
4. The display will now alternate between ‘SF’ and the  
current boiler temperature and both green LEDs will flash  
(Figs. 57 & 58).  
5. Turn the left hand knob fully clockwise. As the knob is  
turned the display will change, indicating the fan speed.  
Fig. 57  
Fig. 58  
6. The display will show ‘00’, indicating maximum rate, then  
revert to ‘P ‘ alternating with the current boiler temperature  
(Figs. 59, 60 & 61 ).  
Fig. 59  
7. Remove the plug from the flue sampling test point. Insert  
the analyser probe and allow sufficient time for the reading  
to settle (Fig. 56).  
The CO2 should be 9.3% 0.2  
8. It is possible to alter the CO2 by adjustment of the gas  
valve. Remove the plastic cover from the ‘Max Rate’  
adjustment screw. At maximum rate the ‘Max. Rate’  
adjustment screw should be turned, using a suitable hexagon  
key, until the correct reading is obtained (Fig. 62).  
Fig. 60  
Fig. 61  
Turning clockwise will reduce the CO2. Anticlockwise will  
increase the CO2  
.
Max Rate  
Adjustment Screw  
(cover removed)  
Min Rate  
Adjustment Screw  
(cap fitted)  
9. The CO2 must then be checked at minimum rate. Turn  
the left hand knob fully anti-clockwise. As the knob is turned  
the display will change, indicating the fan speed. When the  
display reads ‘ 0’ the boiler runs at minimum rate.  
The CO2 should be 8.2% 0.2  
Reduce CO2 Increase CO2  
Reduce CO2 Increase CO2  
at min. rate  
at min. rate  
at max. rate  
at max. rate  
10. With the boiler on minimum, the ‘Min. Rate’ adjustment  
screw must be altered, using a suitable hexagon key, after  
removing the cap (Fig. 62). Turning anti-clockwise will reduce  
the CO2. Clockwise will increase the CO2  
.
11. The ‘Calibration Function’ is maintained for 20 minutes  
unless the maximum CH temperature is exceeded. The  
function can be disabled at any time by turning the right  
hand knob.  
Fig. 62  
If the CO2 is reset at minimum rate it must  
be rechecked at maximum rate again and  
adjusted if required. If the CO2 is reset at  
12. Check the CO/CO2 ratio. This must be less than 0.004.  
maximum rate it must be rechecked at  
minimum rate and adjusted if required.  
33  
© Baxi Heating UK Ltd 2009  
12.0 Fault Finding  
12.1  
Initial Fault Finding Checks  
1. Check that gas, water and electrical supplies are available  
at the boiler.  
NOTE: When instructed to  
operate the reset button, press  
and hold for 5 seconds to reset  
the boiler.  
2. Electrical supply = 230V ~ 50 Hz. Check the CH & DHW  
system. The preferred minimum gas pressure is 20 mbar.  
3. Carry out electrical system checks, i.e. Earth Continuity,  
Resistance to Earth, Short Circuit and Polarity with a suitable  
meter.  
NOTE: These checks must be repeated after any  
servicing or fault finding.  
4. Ensure all external controls are calling for heat and check  
all external and internal fuses. Before any servicing or  
replacement of parts, ensure the gas and electrical supplies  
are isolated.  
Table Of Error Codes  
12.2  
Error Codes  
E20  
Central Heating NTC Fault  
Incorrect PCB Fitted  
1. If a fault occurs on the boiler an error code may be shown  
on the boiler display and the Boiler Control.  
E28  
E50  
Hot Water NTC Fault  
E110  
E125  
E131  
E133  
E155  
E158  
E160  
Safety Thermostat or Condensate Safety Float Switch Operated  
Circulation Fault (Primary Circuit)  
Interruption Of Power Supply while in fault mode  
Interruption Of Gas Supply or Flame Failure  
Lock Out of Boiler Control  
2. The codes are either two or three digit, preceded by the  
letter 'E'. For example, code E133 will be displayed by 'E1'  
alternating with '33'. E20 is shown as 'E' then '20'  
E20 & E28 indicate faulty or incorrect components.  
Condensate Discharge System Fault  
Fan or Fan Wiring Fault  
E110 shows overheat of the primary water or excess  
condensate in the sump.  
E125 is displayed if within 2 hours of the burner lighting the  
boiler temperature twice exceeds the selected temperature  
by 25°.  
In these instances poor primary circulation or no water in the  
system is indicated.  
Service Reset  
To perform a Service Reset it is necessary to have access to the boiler.  
By pressing the Reset rocker switch on the right of the boiler case for a  
minimum of 5 seconds when error codes are displayed it is possible to  
reset the boiler once the fault has been rectified.  
E133 indicates that the gas supply has been interrupted,  
ignition has failed or the flame has not been detected.  
E155 indicates a Boiler Control reset when Service & Boiler  
Control reset counters are out of step. Boiler Control default  
not restored correctly.  
Restoring Boiler Control Default  
Following a Service Reset it is necessary to restore the Boiler Control to  
default condition:-  
E158 indicates a condensate discharge system fault.  
Disconnect the main power supply  
On reinstating the power supply the Boiler Control display will count  
down from 7.  
3. By pressing the 'Reset' button on the Boiler Control for a  
minimum of 5 seconds when E110 & E133 are displayed it is  
possible to relight the boiler.  
Before the count reaches 3 press both the ‘On/Off’ and ‘Reset’ buttons  
simultaneously and hold until the count reaches 0.  
The Boiler Control display will show ‘SEt’ to confirm default restoration.  
4. If this does not have any effect, or the codes are displayed  
regularly further investigation is required. It is possible to  
reset the boiler up to 4 times in any 5 hour period. Further  
resets via the Boiler Control are then blocked for 5 hours  
unless a Service Reset is performed.  
34  
© Baxi Heating UK Ltd 2009  
12.0 Fault Finding  
Refer to Section 16.0 “Illustrated Wiring Diagram” for position of terminals and components  
Central Heating - Follow operational sequence  
NOTE: Sections ‘A’ to ‘L’  
Turn on Power Supply  
Display Illuminates  
NO  
referred to in the chart  
opposite are on the  
following pages  
Go to section ‘A’  
YES  
Error 110 flashing  
Error 131 flashing  
If the error 110 is still flashing.  
Press the Service Reset  
switch for 5 seconds  
YES  
YES  
Go to section ‘I’  
NO  
YES  
YES  
Error 20 or 28 flashing  
NO  
Go to section ‘E’  
Error 158 flashing  
Go to section ‘C’  
NO  
Ensure controls are set to  
demand and verify the  
contacts are closed  
NO  
Turn Central Heating  
thermostat to Maximum.  
Pump runs  
Ensure all external controls  
are calling for heat  
NO  
YES  
YES  
Go to section ‘B’  
YES  
Go to section ‘J’  
Error 155 flashing  
NO  
Ensure that the system is full,  
primary circulation is OK &  
that there is no blockage  
YES  
NO  
NO  
Error 125 flashing  
NO  
Go to section ‘J’  
Error 160 flashing  
Go to section ‘D’  
Fan runs  
YES  
Error 160 flashing  
Go to section ‘K’  
Fan runs at correct speed  
YES  
Go to section ‘G’  
Turn the selector switch to  
reset  
Spark at ignition electrodes for  
up to 5 seconds and for 3  
attempts  
YES  
YES  
NO  
YES  
Error 133 flashing  
Go to section ‘F’  
YES  
NO  
Burner does not stay alights  
after 5 seconds  
Error 133 flashing  
Go to section ‘H’  
Burner lights  
YES  
NO  
YES  
Check the Central Heating  
NTC sensor  
Burner output modulates to  
maintain the temperature set  
Go to section ‘E’  
YES  
Burner relights after at least 3  
minutes, when the display is  
less than the set temperature  
(room thermostat open)  
YES  
YES  
Operation sequence  
successful  
Burner goes out  
Fan stops after 10 seconds  
35  
© Baxi Heating UK Ltd 2009  
Fault Finding Solutions Sections  
12.0 Fault Finding  
Is there 230V at:  
A
NO  
NO  
NO  
1.  
2.  
3.  
Main terminals L and N  
Main terminal fuse  
Check electrical supply  
Replace fuse  
NO  
Display  
illuminated  
Replace PCB  
Check wiring  
PCB - X1 connector  
terminals 1,2  
Check all system wiring and pump  
B
Service Reset  
C
Condensate Pump does not run  
On Reset is there 230V at:  
PCB - X3 connector terminals 5 &  
6 for at least 2 seconds  
NO  
NO  
1.  
2.  
Replace PCB  
Condensate Pump terminals for at  
least 2 seconds  
Replace wiring  
YES  
Replace Cond. Pump  
YES  
YES  
Condensate Pump runs  
Condensate drain system blocked  
NO  
Clean condensate drain system  
Replace Float Switch  
D
E
Fan connections correct at fan. PCB -  
X2 connector, is 230V AC across  
terminals 5 & 7  
YES  
YES  
Fan jammed or faulty winding  
Replace PCB  
Replace fan  
NO  
E20 - Temperature sensor faulty.  
Cold resistance approximately  
10kΩ @ 25° C  
NO  
Replace sensor or PCB (E28)  
(resistance reduces with increase in temp.)  
E28 - Incorrect PCB fitted  
F
1.  
Check and correct the connection of the  
tube between the venturi and gas valve  
NO  
2.  
Gas at burner  
Ensure gas is on and purged  
Replace PCB  
NO  
YES  
PCB - X3 connector is 230V AC across  
terminals 1 & 2  
Replace gas valve  
G
voltage at PCB - X2 connector is  
110V AC across terminals 2 & 5  
(Note: from multimeter connect  
‘common’ to 2 & ‘volts’ to 5)  
Check wiring  
NO  
Check and correct if necessary  
1. Ignition electrode and lead  
2. Electrode connection  
Replace PCB  
Replace igniter  
YES  
YES  
3. Spark gap and position  
36  
© Baxi Heating UK Ltd 2009  
1.  
2.  
Check the gas supply pressure:  
For Natural Gas greater than  
10 - 11 mbar  
H
12.0 Fault Finding  
Check and correct if necessary  
1. The mechanical set of the gas valve  
(CO2 values - see instruction)  
2. Flame sensing electrode and lead connections  
3. Flame sensing electrode position  
YES  
NO  
Replace PCB  
Replace flame sensing electrode  
Flame current should be more than 0.5 μA  
Overheat Thermostat or  
Condensate Safety Float Switch  
operated or faulty  
Allow to cool. Continuity  
across thermostat terminals  
more than 1.5 ohm  
I
YES  
Replace Safety Thermostat  
Replace PCB  
NO  
Continuity across plug  
terminals at 3 & 4 of connector  
X401 more than1.5 ohm  
NO  
YES  
YES  
Check condensate system  
and Pump  
Condensate drain system fault  
NO  
Replace Safety Float Switch  
or wiring  
Press the Service Reset switch  
for 5 seconds  
J
Restore Boiler Control defaults  
YES  
Fan connections correct at fan.  
PCB - X401 connector terminals 5,6,7 & 8  
K
L
Replace fan  
1.  
2.  
Temperature sensors faulty.  
Cold resistance approximately  
10kΩ @ 25° C (CH sensor)  
NO  
Replace sensor  
(resistance reduces with increase in temp.)  
YES  
Replace heat exchanger  
If pump is running the heat exchanger could be  
obstructed  
IMPORTANT:There is no limit to the number of repeated ‘Service Reset’  
operations but the Boiler Control must be refreshed by ‘Restoring Boiler  
Control Default’ as described on p.34 following the final ‘Service Reset’ and  
before the Boiler Control reset is re-used.  
37  
© Baxi Heating UK Ltd 2009  
13.0  
Short Parts List  
Short Parts List  
Key  
No.  
Description  
Manufacturers  
Part No.  
A
J
A
B
C
D
E
F
Burner Assy  
Injector  
720125701  
720126301  
720127501  
720127001  
720125801  
5121447  
Ignition Lead  
Gas Valve  
P.C.B  
B
I
Fan  
C
G
H
I
NTC Sensor  
Float Switch (Safety or Discharge)  
Safety Thermostat  
Spark Generator  
Condensate Pump  
720126101  
720126201  
720126401  
5114766  
J
G
H
K
720125901  
E
F
K
D
38  
© Baxi Heating UK Ltd 2009  
14.0 Notes  
39  
© Baxi Heating UK Ltd 2009  
14.0 Notes  
40  
© Baxi Heating UK Ltd 2009  
14.0 Notes  
41  
© Baxi Heating UK Ltd 2009  
GAS BOILER SYSTEM COMMISSIONING CHECKLIST  
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating  
compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.  
Failure to install and commission this equipment to the manufacturer’s instructions may invalidate the warranty but does not affect statutory rights.  
Customer Name  
Address  
Telephone Number  
Boiler Make and Model  
Boiler Serial Number  
Commissioned by (print name)  
Company Name  
Gas Safe Register licence No.  
Telephone Number  
Company Address  
Commissioning Date  
To be completed by the customer on receipt of a Building Regulations Compliance Certificate :  
*
Building Regulations Notification Number (if applicable)  
CONTROLS Tick the appropriate boxes  
Time and Temperature Control to Heating  
Room Thermostat and  
Programmer/Timer  
Programmable  
Room Thermostat  
Load/Weather  
Compensation  
Optimum Start  
Control  
Time and Temperature Control to Hot Water  
Heating Zone Valves  
Cylinder Thermostat and Programmer/Timer  
Combination Boiler  
Not Required  
Not Required  
Not Required  
Not Required  
Provided  
Fitted  
Fitted  
Fitted  
Fitted  
Hot Water Zone Valves  
Thermostatic Radiator Valves  
Automatic Bypass to System  
Boiler Interlock  
ALL SYSTEMS  
The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer’s instructions  
Yes  
What system cleaner was used?  
What inhibitor was used?  
Quantity  
litres  
ft3/hr  
CENTRAL HEATING MODE Measure and Record:  
m3/hr  
mbar  
OR  
OR  
Gas Rate  
Burner Operating Pressure (if applicable)  
Central Heating Flow Temperature  
Central Heating Return Temperature  
Gas Inlet Pressure  
mbar  
°C  
°C  
COMBINATION BOILERS ONLY  
Is the installation in a hard water area (above 200ppm)?  
If yes, has a water scale reducer been fitted?  
What type of scale reducer has been fitted?  
DOMESTIC HOT WATER MODE Measure and Record:  
Gas Rate  
Yes  
Yes  
No  
No  
ft3/hr  
m3/hr OR  
mbar OR  
Burner Operating Pressure (at maximum rate)  
Cold Water Inlet Temperature  
Gas Inlet Pressure (at maximum rate)  
mbar  
°C  
Hot water has been checked at all outlets  
Water Flow Rate  
Yes  
Temperature  
°C  
l/min  
CONDENSING BOILERS ONLY  
The condensate drain has been installed in accordance with the manufacturer’s instructions and/or BS5546/BS6798  
Yes  
ALL INSTALLATIONS  
If required by the manufacturer, record the following  
CO2  
%
OR CO  
ppm OR CO/CO2 Ratio  
The heating and hot water system complies with the appropriate Building Regulations  
Yes  
Yes  
Yes  
Yes  
The boiler and associated products have been installed and commissioned in accordance with the manufacturer’s instructions  
The operation of the boiler and system controls have been demonstrated to and understood by the customer  
The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained and left with the customer  
Commissioning Engineer’s Signature  
Customer’s Signature  
(To confirm satisfactory demonstration and receipt of manufacturer’s literature)  
All installations in England and Wales must be notified to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme.  
A Building Regulations Compliance Certificate will then be issued to the customer.  
*
42  
©Heating and Hotwater Industry Council (HHIC)  
SERVICE RECORD  
It is recommended that your heating system is serviced regularly and that the appropriate Service Record is completed.  
Service Provider  
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s  
instructions.  
Always use the manufacturer’s specified spare part when replacing controls.  
SERVICE 1 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
SERVICE 2 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
No  
No  
Company Name  
Company Name  
Telephone Number  
Telephone Number  
Gas Safe Register licence No.  
Comments  
Gas Safe Register licence No.  
Comments  
Signature  
Signature  
SERVICE 3 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
SERVICE 4 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
Company Name  
Company Name  
Telephone Number  
Telephone Number  
Gas Safe Register licence No.  
Comments  
Gas Safe Register licence No.  
Comments  
Signature  
Signature  
SERVICE 5 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
SERVICE 6 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
Company Name  
Company Name  
Telephone Number  
Telephone Number  
Gas Safe Register licence No.  
Comments  
Gas Safe Register licence No.  
Comments  
Signature  
Signature  
SERVICE 7 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
SERVICE 8 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
Company Name  
Company Name  
Telephone Number  
Telephone Number  
Gas Safe Register licence No.  
Comments  
Gas Safe Register licence No.  
Comments  
Signature  
Signature  
SERVICE 9 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
SERVICE 10 Date  
Energy Efficiency Checklist completed?  
Engineer Name  
Company Name  
Company Name  
Telephone Number  
Telephone Number  
Gas Safe Register licence No.  
Comments  
Gas Safe Register licence No.  
Comments  
Signature  
Signature  
43  
Please complete the boxes below  
9.0 Warranty & Service  
Serial Number  
Standard Warranty Terms & Conditions  
To activate your second year free warranty you must register your boiler with  
heateam the service division of Baxi Heating UK Ltd either by completing and  
returning the registration card or calling our telephone registration line on  
0800 013 7989.  
It is also a requirement of the warranty that the boiler has an annual service  
(every 12 months) in accordance with the installation and servicing  
instructions, performed by a Gas Safe registered engineer.  
Date of Installation  
If you would like heateam to carry this out please call on 0844 871 1525.  
Our promise to you  
If you experience a fault with your new boiler, we aim to provide a safe and  
high quality repair service supported by our dedicated national network of  
highly skilled engineers. If your installer can’t resolve the problem for you, we  
will do everything we can to get an engineer out to you as quickly as possible.  
Nothing in this warranty will affect your statutory consumer rights.  
D
D
M M  
Y
Y
Installer Details (name, address and contact number(s))  
What you need to do if you experience a problem with your heating system  
or the operation of the boiler  
You should always contact your installer first, because the cause of the fault  
may not be related to the boiler. If your installer confirms that the fault is with  
the boiler and he/she can’t repair it, our friendly customer service team is on  
hand to help. Simply call our service division heateam on 0844 871 1525 to  
book an engineer visit or for any general advice that you may need. Our  
contact centre is open Monday to Friday 8am - 6pm, weekends and Bank  
Holidays 8.30am - 2pm, excluding Christmas Day and New Years Day.  
When calling heateam it would be helpful if you could have the following  
information to hand:-  
1
2
3
4
Boiler serial number (see opposite).  
Boiler make and model number.  
Your installer name and address details.  
Proof of purchase (if you do not have the boiler serial number).  
What this warranty covers  
Free of charge repair or replacement of components found to be of faulty  
manufacture.  
Free of charge replacement of the complete unit provided always that the  
failure is related to a manufacturing fault that cannot be repaired or is  
uneconomic to repair.  
What this warranty does not cover  
Repairs to boilers which haven’t been installed and commissioned properly,  
and as set out in the installation instructions (this includes the need to flush the  
system effectively and add a suitable corrosion inhibitor).  
Any damage caused by hard water scale deposits and/or aggressive water  
resulting from corrosion.  
Any other defects or failures, either in the connected heating system or  
outside of the boiler itself.  
Faults caused by inadequate supply of electricity, gas or water to the property.  
Installations within commercial settings for which this boiler was not designed.  
All descriptions and illustrations provided in this leaflet have been carefully  
prepared but we reserve the right to make changes and improvements in  
our products which may affect the accuracy of the information contained in  
this leaflet. All goods are sold subject to our standard Conditions of Sale  
which are available on request.  
Reimbursement of any third party repair or replacement costs that we haven’t  
been told about or agreed with you in advance.  
Compensation for consequential losses (e.g. loss of earnings, business losses,  
stress and inconvenience) arising from a production breakdown, including  
repair delays caused by factors outside our reasonable control.  
BAXI  
A Trading Division of Baxi Heating UK Ltd (3879156)  
A Division of Baxi Group  
After Sales Service 0844 871 1525  
Brooks House, Coventry Road, Warwick. CV34 4LL  
After Sales Service 0844 871 1525 Technical Enquiries 0844 871 1555  
e&oe  
o
Comp N 710161501 (7/09)  
© Baxi Heating UK Ltd 2009  

Aiwa CDC Z117 User Manual
Behringer Car Speaker MS40 User Manual
Bose Bluetooth CINEMATE1SR User Manual
Bushnell Binoculars 110833 User Manual
Canon MV530i User Manual
Casio FX 82SX PLUS User Manual
Citizen Systems Calculator sdc 620II User Manual
GE PROFILETM PNRQ21L User Manual
Hanns G Car Video System HSG 1083 User Manual
Hitachi DZMV200A User Manual