246653-YTG-E-0108
TOMORROW’S UNIT TODAY
GENERAL
®
Introducing the YORK Millennium 25, 30, & 40 ton rooftop
line - units designed to provide peak performance and value
both today and for years to come. Millennium units are manu-
factured at an ISO 9001 registered facility, and each rooftop
is completely computer-run tested prior to shipment.
TECHNICAL GUIDE
The Millennium is designed to be flexible enough to meet
your needs today and in the future. The true value of YORK’s
Millennium is that it can be designed to fit any need, from
cooling only, constant volume applications to variable air vol-
ume systems with variable frequency drive.
®
MILLENNIUM
SINGLE PACKAGE ROOFTOP UNITS
Y32, Y33 & Y34
FEATURING:
25, 30, & 40 TON
•
•
Cooling Only Units
Cooling/Gas Heating Units (Natural) Standard or
Modulating Gas Heat available
Cooling/Electric Heating Units
Cooling/Hot Water Heating Units
Cooling/Steam Heating Units
Industry Leading Efficiency
25 TON (10 EER)
30 & 40 TON (9.5 EER)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Double Wall Construction
Stainless Steel or Powder Coated Drain Pan
Multiple Scroll Compressors
Multiple Refrigeration Circuits
Upgradable Motor Efficiency
Enhanced Filtration
Vibration Isolated Supply Fan and Motor
Technicoated Evaporator and Condenser Coils
High Capacity Evaporator Coils
Single Power Point Connection
Easy Access Hinged Doors
Variable Air Volume
Constant Air Volume
30 TON UNIT SHOWN
Factory Installed Economizers/Disconnect/Convenience
Outlet/Control Options
•
Low Profile
®
MILLENNIUM SIMPLICITY ELITE™ FEATURES:
•
•
Single Button Programming and LED Display
Designed to operate on both constant and variable air
volume units
•
365-Day real time clock with automatic Daylight Savings
time adjustment
•
•
Occupancy Schedule allowing two schedules per day
20 Holiday schedules with programmable schedules that
can start at any time, day or night
•
•
Patented Comfort Ventilation operation for economical
and comfortable economizer operation
Demand Ventilation option to assure proper IAQ condi-
ISO 9001
Certified Quality
Management System
tions based on available space or return air CO levels
2
•
•
•
•
Temperature/Humidity programming algorithm allows
programmable limits to help control humidity in the space
Smoke Purge automatically ventilates the space when
smoke is detected
Monitors dirty filters and proves airflow before starting
heating or cooling
Intelligent recovery to bring the space temperature up to
occupied setting quicker and more economically
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
246653-YTG-E-0108
LIST OF FIGURES
Fig.#
Pg.#
Fig.#
Pg.#
2
18 STEAM PIPING CROSS SECTION . . . . . . . . . . . . . . 25
HOT WATER COIL - 25 & 30 TON, 1 ROW,
3
4
5
6
7
8
9
HOT WATER COIL - 25 & 30 TON, 1 ROW,
21 ALTITUDE/TEMPERATURE CONVERSION
HOT WATER COIL - 25 & 30 TON, 1 ROW,
HOT WATER COIL - 25 & 30 TON, 1 ROW,
25 POWER EXHAUST - ONE FORWARD CURVE
HOT WATER COIL - 40 TON, 1 ROW,
26 POWER EXHAUST - TWO FORWARD CURVED
HOT WATER COIL - 40 TON, 1 ROW,
HOT WATER COIL - 40 TON, 1 ROW,
HOT WATER COIL - 40 TON, 1 ROW,
10 HOT WATER COIL - 25 & 30 TON, 2 ROW,
11 HOT WATER COIL - 25 & 30 TON, 2 ROW,
12 HOT WATER COIL - 25 & 30 TON, 2 ROW,
13 HOT WATER COIL - 25 & 30 TON, 2 ROW,
36 CLEARANCES - HOOD/ECONOMIZER & MOTOR
37 CLEARANCES - HOOD/ECONOMIZER & MOTOR
Johnson Controls Unitary Products
3
246653-YTG-E-0108
LIST OF TABLES
Tbl.#
Pg.#
Tbl.#
Pg.#
6
9
34 COOLING PERFORMANCE 40 TON STANDARD
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
MODULATING GAS HEATING CAPACITIES . . . . . . 12
35 COOLING PERFORMANCE 40 TON HIGH
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
WATER PRESSURE DROP (1 ROW,
10 STATIC RESISTANCE HOT WATER COIL
43 POWER EXHAUST - ONE FORWARD CURVED
44 POWER EXHAUST - TWO FORWARD CURVED
12 STATIC RESISTANCE HOT WATER COIL
14 WATER PRESSURE DROP (2 ROW,
15 STATIC RESISTANCE HOT WATER COIL
48 ELECTRICAL DATA 25 TON WITH ELECTRIC
HEAT R22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
49 ELECTRICAL DATA 30 TON WITH ELECTRIC
HEAT R22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
50 ELECTRICAL DATA 40 TON WITH ELECTRIC
HEAT R22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
18 STATIC RESISTANCE HOT WATER COIL
51 ELECTRICAL DATA 25 TON WITH POWER
52 ELECTRICAL DATA 30 TON WITH POWER
21 STATIC RESISTANCE STEAM COIL
53 ELECTRICAL DATA 40 TON WITH POWER
23 STATIC RESISTANCE STEAM COIL
54 ELECTRICAL DATA 25 TON WITH ELECTRIC HEAT
AND POWER EXHAUST R22 . . . . . . . . . . . . . . . . . . 69
25 SUPPLY FAN MOTOR AND DRIVE DATA . . . . . . . . 27
55 ELECTRICAL DATA 30 TON WITH ELECTRIC HEAT
AND POWER EXHAUST R22 . . . . . . . . . . . . . . . . . . 72
56 ELECTRICAL DATA 40 TON WITH ELECTRIC HEAT
AND POWER EXHAUST R22 . . . . . . . . . . . . . . . . . . 75
29 DRIVE ADJUSTMENT FOR POWER EXHAUST
30 DRIVE ADJUSTMENT FOR POWER EXHAUST
31 COOLING PERFORMANCE 25 TON . . . . . . . . . . . . . 31
32 COOLING PERFORMANCE 30 TON STANDARD
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
33 COOLING PERFORMANCE 30 TON HIGH
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4
Johnson Controls Unitary Products
246653-YTG-E-0108
®
YORK Millennium
Efficient, Durable Scroll Compressors - The Millennium
design uses industrial grade hermetic scroll compressors for
peak efficiency and low noise operation. The compressor
design is so durable that it can actually hold more liquid
charge without slugging than is present in each refrigerant
circuit at shipment, dramatically reducing the chances of ever
slugging a compressor with liquid charge.
OVERVIEW
Introducing the YORK Millennium 25, 30, & 40 ton rooftop
line - units designed to provide peak performance and value
both today and for years to come. When we asked our cus-
tomers what they wanted in a new rooftop line, we were care-
ful to listen to both the needs of today and tomorrow. So,
you'll find that Millennium units not only help you solve
today's problems, but can handle tomorrow's difficulties as
well:
Multiple Refrigeration Circuits for Greater Turndown - The
YORK Millennium unit has intertwined 10 ton circuits (12.5
ton circuits on the 25 ton) - giving the best unloading capabil-
ity in the industry. With more and more designs requiring
higher outside air quantities, the lower capacity capability is
an outstanding way to neutralize outside air without over-con-
ditioning the space on off-peak days. And, Millennium's high
quality balance-port thermal expansion valves are more
effective at metering refrigerant flow in part-load conditions,
making Millennium a peak-performer across a wide capacity
range.
Industry Leading Efficiency - The Millennium's 9.5 EER (10
EER 25 ton) rating makes it the most frugal energy consumer
in its class. When it comes to lower operating costs, Millen-
nium simply outperforms the competition.
Double Wall Construction - Millennium units come double
walled as standard. The galvanized sheet metal liner pro-
vides the best protection against microbial growth, helping
both the unit and the indoor air stay fresh and clean. And, the
rigid sheet metal inner liner keeps the insulation completely
out of the air stream, eliminating concerns about fiberglass
particles.
FEATURES AND BENEFITS
When it comes to flexibility, Millennium really shines. Our cus-
tomers were clear about one thing - not all installations are
the same. Some have very simple needs, others are more
involved. The YORK Millennium serves both markets - and all
of those in between - extremely well. YORK engineers crafted
a design which is both uniquely flexible and competitive, giv-
ing you the best of both worlds. In addition to a competitive
base product, Millennium offers unparalleled flexibility.
Optional features include:
Drain Pan Whisks Away Condensate - Condensate is fre-
quently the source of microbial contamination. Competitive
drain pans often are insufficiently sloped to properly drain all
of the condensate, causing drain pan corrosion and bacterial
growth to begin almost immediately. The YORK design is
sloped at the 1/4” per foot recommended by the ASHRAE
62.1-2004 ventilation draft standard, with an extra large drain
connection capable of removing up to three gallons of con-
densate per minute. It is available in either powder coat
painted steel or stainless steel for long life.
Variable Air Volume - YORK gives you the ability to vary air
volume by inlet guide vanes or variable frequency drive - the
choice is yours. All Millennium VAV units come standard with
hot gas bypass to give extended operation range.
Johnson Controls Unitary Products
5
246653-YTG-E-0108
Optional Head Pressure Control - For those applications
where mechanical cooling is required below 40°F, optional
low ambient operation allows compressor operation down to
0°F.
ers. Comparative enthalpy, single enthalpy and dry bulb con-
trol are available.
Optional Factory Installed Disconnect - A conveniently
located actuator handle in the front of the unit can disconnect
line power to the entire unit, eliminating the need for a field
provided disconnect. The handle may also be locked in either
position through the use of a standard padlock. Millennium's
single point power connection makes this option particularly
appealing. If desired, the disconnect may be ordered with a
115 volt, GFCI protected convenience outlet, including a fac-
tory wired transformer to power the outlet from the single
point power connection; the convenience outlet remains
operational when the disconnect is open.
Easily Upgrade Motor Efficiency to Meet Tighter Codes -
Optional high efficiency motors help you make simple
upgrades to meet more demanding building and energy
codes.
Enhanced Filtration Options - Millennium gives designers the
flexibility to meet various IAQ requirements with a full range
of rigid and throwaway filters at different efficiency levels.
Vibration Isolation - The Millennium's neoprene mounts are
typically sufficient for most applications but when sound and
vibration transmission are a major concern, YORK offers 1"
and 2" isolation springs for even greater protection from sup-
ply air fan noise and vibration.
Heating Done Your Way - Millennium offers the choice of nat-
ural gas standard or modulating gas heat, electric resistance
heat, hot water heat, steam, or no heat at all. Very simply, the
choice is yours.
Corrosion Resistant Coils- Many industrial and seacoast
applications require enhanced protection from corrosive envi-
ronments.
INSTALLATION FEATURES
With YORK Millennium, high performance doesn't mean high
complexity. YORK listened carefully to make sure that Millen-
nium was as simple as possible, and service convenience
comes standard with each unit. From a single curb size to the
easy service access, you'll find that Millennium was designed
to be easy from start to finish.
Optional TechniCoated Coated Condenser and Evapo-
rator Coils - Many industrial and seacoast applications
require enhanced protection from corrosive environ-
ments. The special dipped phenolic coating process
provides a high level of protection for the exposed con-
denser coil.
Full Range of Air Flows and Static Pressures - The Millen-
nium design gives a complete offering of supply air flows and
static pressure combinations to meet most every application
requirement.
Optional Copper-Copper Condenser and Evaporator
Coils - For corrosion resistance.
High Capacity Evaporator Coils - For those applications
which require slightly more capacity than offered by the stan-
dard Millennium product, YORK offers the option of higher
capacity evaporator coils, boosting cooling output without
increasing unit size. (30 & 40 Ton R-22 only)
Single Power Point Connection - Millennium units have a sin-
gle gas and electric connection, minimizing time at the job
site. For further installation flexibility, power and gas connec-
tions may be brought up from the curb or through the side of
the unit.
Variety of Exhaust Air Options - YORK Millennium offers a
wide variety of exhaust air options, including barometric
relief, non-modulating power exhaust, and modulating power
exhaust. And, because Millennium units use forward-curved
blowers for power exhaust fans, they can exhaust up to 100%
of the nominal supply air at much greater static pressure
loads than competitive units. Not available on end return.
Simple Controls - Millennium's controls system is easy to
understand and apply, and it doesn't lock you into proprietary
devices. A choice for YORK Millennium today does not limit
your choices tomorrow.
Rain Hoods Rotate Into Place - No bulky, field--installed rain
hoods here. Millennium rain hoods ship rotated inside the
unit. Once on the job, installer merely rotates the hood
upward and puts in a few screws - an easy one-person job.
NOTE: In most applications, the supply fan will keep the
return at negative pressure. A barometric relief will
function better when ducted to building space, not
the return.
Excellent Access for Service - Service access on Millennium
is a snap. Hinged and latched door options give access on
both sides of the unit to all major components. Some doors
have positive action slide latches for even greater ease of
access. All service fittings are conveniently located to mini-
mize time and effort.
Optional Factory Installed Economizers - Millennium units
offer economizers with Standard or Optional low leak damp-
6
Johnson Controls Unitary Products
246653-YTG-E-0108
PITCHED ROOF
ANGLED CONDENSER
COILS
SOLID, CLASS II FAN CONSTRUCTION
INTERTWINED COIL
DOUBLE WALL CONSTRUCTION
HINGED, LATCHED
ACCESS DOORS
LOW LEAK DAMPERS
Low Profile - Millennium units stand only 64” above their
curb, minimizing potential aesthetic conflicts.
CONSTRUCTION FEATURES
YORK's Millennium rooftop line is built for the long haul, with
high end features and construction offered at a competitive
price. Millennium units are manufactured at an ISO 9001 reg-
istered facility, and each rooftop is completely computer-run
tested prior to shipment. Some of the valuable construction
features of the Millennium which are not found on competitive
units include:
Extended flue connection - Each gas unit ships with a field
mounted external flue. The flue lifts all products of furnace
combustion far above the unit - eliminating the possibility of
corrosion in the furnace heat exchanger from recirculating
flue gases.
Protective Covering - Special polyurethane sleeves which
cover the distributor tubing keep distributor tubes from con-
tacting each other and wearing out.
Double Wall Construction - Each unit has both an exterior
and an interior wall, which make for a more rigid design with
panels and doors that are solid, not flimsy. The unit features a
fully framed construction for even greater stability.
Built-in Hail Guard - Condenser coils angled at 30 degrees
from the vertical are inherently protected from damage due to
shipment, hail, etc.
Powder Paint - Industry leading 1000 salt spray hour paint
keeps the unit in great condition for years to come.
Induced Draft Furnace - This design provides a positive
exhaust of all combustion products.
Johnson Controls Unitary Products
7
246653-YTG-E-0108
LIST OF FEATURES AND BENEFITS
Field Installed Accessories
Standard Features
•
•
•
9.5 EER (10 EER on 25 ton)
Double wall construction
Major components have hinged and latched access
doors
Industrial duty scroll compressors
Sturdy framed construction
Sloped stainless steel or powder coated drain pan
Separate 10 ton circuits (30 and 40 ton units) or 12.5 ton
(25 ton unit)
Intertwined evaporator coil
Angled condenser coils for superior protection
Single power point connection
Through-the-curb or through-the-base utility connections
Retractable outside air hoods
Powder paint tested to 1000 salt spray hours
Mechanical cooling from 40° F to 125° F
1-1/2” insulation
•
•
•
7-Day Programmable Wall Thermostat-Can be used with
or without remote sensors. Can be used on CV and VAV
units when wall thermostat is required for scheduling and
temperature control.
Energy Recovery Ventilators- 8,000 and 13,000 CFM
models available. Great for applications involving 30% or
more of required outdoor air where energy use and com-
fort must be optimized.
Wall Sensors- Remote space sensors used with CV or
VAV unit for unit control via the Simplicity® Elite™ con-
trol. Standard sensor, sensor with override and sensor
with override and + 5 degree adjustment.
Simplicity® Transporter- Device allows internet control
and monitoring of HVAC units equipped with Simplicity®
Elite™ controls.
Phase Monitor Kit- Includes control and wiring to monitor
and protect the unit from phase reversal, phase loss and
low voltage.
Burglar Bars- Prevent any type of building entry through
the RTU unit with bars that block the return and supply
openings on downflow applications.
Partial perimeter roofcurb- Designed for application on
all 25-40 ton Millennium rooftop units. 14" height.
Barometric Relief Kit- Provides barometric relief hood
and dampers for duct mounting on units requiring end
return.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Sloped unit roof with drip lip
High and low refrigerant pressure protection
Polyurethane sleeves to protect small diameter tubing
Steel framing around blowers with deflection springs or
rubber isolators for low vibration
Fully factory packaged and run-tested
10 year gas heat exchanger warranty
One year compressor warranty
•
•
•
•
•
•
One year warranty on all parts
•
•
Natural Gas to Propane Conversion Kits- Contains ori-
fices and gas valves parts to convert from Natural Gas to
Propane. (Not available on modulating heat.)
High Altitude Kit- Natural gas kit designed for natural gas
heating applications between 2,000 and 6,000 feet
above sea level.
Factory Installed Options
•
•
Economizer with standard or low leak dampers
Natural gas standard or modulating gas heat with reli-
able induced draft design
•
•
Electric heat in three sizes
Variable air volume using either inlet guide vanes, wired
for VFD (variable frequency drive), or factory installed
VFD.
•
•
•
•
•
•
•
1, 2” blower isolator springs or rubber isolators
A variety of blower horsepower offerings
High efficiency motors
High efficiency filtration
Barometric relief
Power exhaust of 100% of nominal air flow
Technicoat corrosive resistant coating on condenser and
evaporator coils
•
Copper-Copper corrosive resistant condenser and evap-
orator coils
•
•
•
•
•
•
•
•
•
•
0°F low ambient operation of mechanical cooling
Hot gas bypass (standard on all VAV units)
High capacity evaporator coils
Single unit disconnect
Convenience outlet and transformer factory wired
Hot water heating coil with one or two rows
One row steam heating coil
®
Simplicity Elite™ controls
ModLINC translator
York Commercial Comfort System (YCCS)
8
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 1: GENERAL PHYSICAL DATA
UNIT SIZE
25 TON
30 TON
40 TON
UNIT EER / IPLV
(STANDARD CAPACITY EVAPORATOR)
10.0 / 10.92
9.5 / 10.97
9.5 / 9.73
COMPRESSOR DATA
NUMBER/SIZE
TYPE
2 x 12.5 Ton
3 x 10 Ton
Scroll
4 x 10 Ton
Scroll
Scroll
UNIT CAPACITY STEPS
50%, 100%
33%, 67%, 100%
25%, 50%, 75%, 100%
INDOOR FAN AND DRIVE
NUMBER / TYPE
DIAMETER X WIDTH (INCHES)
HP RANGE
1 / FC
1 / FC
22 x 20
1 / FC
25 x 22
22 x20
7.5 - 20
10 - 25
10 - 25
CFM RANGE (FULL LOAD)
ESP RANGE
6,000 - 12,500
6,000 - 15,000
0.2" - 4.0”
8,000 - 18,000
0.2" - 4.0"
0.2” - 4.0”
EXHAUST FAN
NUMBER/SIZE/TYPE
HP RANGE (SINGLE MOTOR)
CFM
1/FC
2/FC
7.5 - 15
2/FC
7.5 - 15
5 - 10
3,000 - 9,000
4,000 - 18,000
4,000 - 18,000
STANDARD EVAPORATOR COIL
SIZE (SQ. FT.)
ROWS/FPI
26.0
26.0
30.4
3 / 13
3 / 16
4 / 13
HIGH CAPACITY EVAPORATOR COIL
SIZE (SQ. FT.)
ROWS/FPI
26.0
26.0
30.4
2/16
4 / 16
4 / 16
CONDENSER COIL
SIZE (SQ. FT.)
ROWS/FPI
52.0
48.8
65.0
2/16
2 /16
2 /16
CONDENSER FANS
QUANTITY / DIAMETER (INCHES)
NOMINAL CFM
4 / 24
3 / 24
6,800
1.0
4 / 24
6,800
1.0
4,600
MOTOR HP
3 / 4
ELECTRIC HEAT
KW RANGE
40 KW
40 - 108
40 - 108
1
40 - 108
1
1
80 AND 108 KW / CAPACITY STEPS (CV/VAV)
2 / 1
2 / 1
2 / 1
NATURAL GAS HEAT
UNIT SIZE
25 TON
30 TON
1 / 1
2 / 1
-
40 TON
1 / 1
267 MBH CAPACITY STEPS (CV/VAV)
1 / 1
533 MBH CAPACITY STEPS (CV/VAV)
2 / 1
2 / 1
800 MBH CAPACITY STEPS (CV/VAV)
-
6 / 1
3 / 1*
6 / 1
267 MBH “MODULATING” CAPACITY STEPS (CV ONLY)
533 MBH “MODULATING” CAPACITY STEPS (CV ONLY)
800 MBH “MODULATING” CAPACITY STEPS (CV ONLY)
6 / 1
12 / 2
-
12 / 2
12 / 2
17 / 3
-
HOT WATER COIL
22.5” x 65”
25 Ton
SIZE (INCHES)
CAPACITY
22.5" X 65”
30 Ton
22.5" X 65”
40 Ton
STEAM COIL
SIZE (INCHES)
TYPE
21" X 65"
Steam Coil
FILTERS 2" TA
4 / 16 x 25 & 6 / 20 x 25
30.4
NUMBER / SIZE
4 / 16 x 25 & 6 / 20 x 25
30.4
4 / 16 x 25 & 6 / 20 x 25
30.4
FACE AREA (SQ. FT.)
FILTERS 2" PLEATED, 30%
4 / 16 x 25 & 6 / 20 x 25
30.4
NUMBER / SIZE
4 / 16 x 25 & 6 / 20 x 25
30.4
4 / 16 x 25 & 6 / 20 x 25
30.4
FACE AREA (SQ. FT.)
FILTERS 65% RIGID W/ 2” TA PREFILTERS
4 / 16 x 25 & 6 / 20 x 25
30.4
NUMBER / SIZE
4 /16 x 25 & 6 / 20 x 25
30.4
4 / 16 x 25 & 6 / 20 x 25
30.4
FACE AREA (SQ. FT.)
FILTERS 95% RIGID W/ 2” TA PREFILTERS
4 ea. 16 x 25 / 6 ea. 20 x 25
30.4
NUMBER / SIZE
4 ea. 16 x 25 / 6 ea. 20 x 25
30.4
4 ea. 16 x 25 / 6 ea. 20 x 25
30.4
FACE AREA (SQ. FT.)
* Unit Control Board with 3 heating outputs only, all other Unit Control Boards 2/1.
10
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 2: REFRIGERANT CHARGE
CHARGE
FACTORY/ FIELD
CHARGED
UNIT (TONS)
MODEL
TYPE
SYS #1
SYS #2
26lb / 0oz
SYS #3
SYS #4
25
25
30
30
30
30
40
40
wo/HGBP
w/HGBP
wo/HGBP
R22
R22
R22
R22
R22
R22
R22
R22
Factory
Factory
Factory
Factory
Factory
Factory
Factory
Factory
25 lb. / 8 oz.
26 lb. / 0 oz.
13 lb. / 4 oz.
14 lb. / 6 oz.
14 lb. / 0 oz.
15 lb. / 2 oz.
15 lb. / 5 oz.
15 lb. / 13 oz.
-
-
-
-
26 lb. / 0oz
13 lb. / 8 oz.
13 lb. / 8 oz.
14 lb. / 10 oz.
13 lb. / 8 oz.
14 lb. / 10 oz.
15 lb. / 5 oz.
15 lb. / 5 oz.
-
1
14 lb. / 10 oz.
13 lb. / 8 oz.
14 lb. / 10 oz.
15 lb. / 4 oz.
15 lb. / 4 oz.
-
wo/HGBP
w/HGBP
-
w/HGBP
-
wo/HGBP
w/HGBP
15 lb. / 15 oz.
15 lb. / 15 oz.
1.
With high capacity evaporator coil.
c. Ensure that it is offered in the Y34 unit. Read option
model as N5.
SELECTION PROCEDURE
GIVEN:
From the basic nomenclature, the model now becomes
Y34AN5. Add voltage code of “4” for 460-3-60. Nomen-
clature becomes Y34AN54.
Required Cooling Capacity
Required Sensible Cooling
Required Heating (Gas)
460,000 Btuh
390,000 Btuh
320,000 Btuh
SELECT FAN SPEED AND HORSEPOWER
REQUIREMENTS OF SUPPLY AIR FAN
Entering Air on Evaporator
Outside Design Temperature
Supply Fan CFM
83° F DB/ 67° F WB
95° F
1. Find Supply Air Performance Tables for the 40 ton unit.
13,000 CFM
1.25 IWG
a. Check footnotes and make necessary additions or
deductions to static resistance of ductwork:
External Static Pressure
Electrical Supply Voltage
Economizer Required
2” Throw Away Filters
Constant Volume
460-3-60
Ductwork static resistance
1.25 IWG
Economizer static resistance addition
(interpolate) =.25 IWG + Gas Heat (High) =
0.5 IWG
2.0 IWG
Total Static Resistance
b. Enter Fan Performance Table at 13,000 CFM and
2.0 IWG static pressure:
SELECT UNIT:
1. Determine nominal tons:
460,000 / 12,000 = 38.33 Tons
RPM = 690
BHP = 10.7
Thus, a nominal 40 ton unit is selected.
NOTE: Either a Class I or Class II blower could be used.
2. Reference Cooling Capacity Table for a 40 ton unit with
standard evaporator coil.
c. Enter the Fan Motor Drive Tables. Selecting a 15 hp
motor allows (service factor of 1.5) for a maximum
operating BHP greater than the 10.7 BHP require-
ment.
a. Locate the table for a standard evaporator coil with
95° F air on the condenser.
b. Enter table at 13,000 CFM and 67°F WB air on
evaporator
SIZE OVERCURRENT PROTECTION DEVICE AND
DETERMINE CIRCUIT AMPACITY
c. Trace to 83° F Entering Dry Bulb column.
1. Find electrical tables for the basic 40 ton unit.
a. Enter table for 460-3-60 voltage.
d. Read 493 MBH total capacity and 403 MBH sensi-
ble capacity.
The 40 ton unit will meet the cooling requirements. From
the nomenclature, the unit will be a Y34. Choose the
appropriate configuration for the next digit. Assuming
bottom return and supply, the fourth digit would be an
“A,” making the model Y34A.
b. Find 15 hp in the Supply Air Fan column.
c. Trace to Minimum Circuit Ampacity column - read
104.
d. Trace to Max. Fuse/Breaker Size column - read 110.
e. Size wire and overprotection device accordingly.
f. Check all footnotes.
3. Find Gas Heating Capacity Table.
a. Trace down Output column.
b. Find output which exceeds 320,000 Btuh require-
ment. The N5 option gives 426 MBH output.
Johnson Controls Unitary Products
11
246653-YTG-E-0108
TABLE 3: STANDARD GAS HEATING CAPACITIES
1
3
INPUT CAPACITY (MBH)
OUTPUT
GAS RATE, CU. FT./HR.
GAS HEAT
OPTION
AVAILABLE ON
MODELS
CAPACITY
(MBH)
1ST STAGE
TOTAL
1ST STAGE
TOTAL
2
N3
N5
N8
Y32/Y33/Y34
Y32/Y33/Y34
Y34 ONLY
267
267
267
533
800
213
426
638
247
247
247
247
495
742
4
267
1.
Heating capacity is only staged on CV models. VAV models use only one stage at full capacity.
Blower motor heat not included.
2.
3.
3
Based on a heat content of 1075 Btu/Ft.
4.
Unit Control Board with 3 heating outputs only. For all other Unit Control Boards the 1st Stage is 533 MBH.
TABLE 4: TEMPERATURE RISE
TABLE 5: MINIMUM HEATING CFM
MODULES
MODULES
TON
TON
1
2
3
1
2
3
25
30
40
5-35
5-35
5-30
25-55
20-50
10-45
-
-
25
30
40
5,644
5,644
6,584
7,183
7,901
8,779
-
-
25-55
13,169
TABLE 6: MODULATING GAS HEATING CAPACITIES
INPUT CAPACITY (MBH)
MINIMUM MAXIMUM
OUTPUT CAPACITY
GAS RATE, CU. FT./HR.
AVAILABLE ON
MODELS
GAS HEAT OPTION
STEPS
1
(MBH)
MINIMUM
MAXIMUM
2
D3
Y32/Y33/Y34
Y32/Y33/Y34
Y34 ONLY
69
267
6
213
426
638
64
247
2
D5
69
69
533
800
12
17
64
64
495
744
2
D8
1.
Output Capacity at Full Fire.
Modulating Gas Heat available on CV models only.
2.
12
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 7: MODULATING HEAT
STAGES OF GAS CONTROL (% OF FULL HEAT OUTPUT)
GAS HEAT OPTION
AVAILABLE ON MODELS
STEP
1
INPUT
OUTPUT
55,466
% OF TOTAL OUTPUT
26%
69,333
2
106,666
165,332
202,665
229,332
266,666
69,333
85,333
40%
D3
3
132,266
162,132
183,466
213,333
55,466
62%
(Turn down ration
3.8 to 1)
Y32, Y33, Y34
4
76%
5
86%
6
100%
13%
1
2
106,666
165,332
202,665
229,332
266,666
325,331
362,664
389,331
426,664
495,997
533,330
69,333
85,333
20%
3
132,266
162,132
183,466
213,333
260,265
290,132
311,465
341,331
396,798
426,664
55,466
31%
4
38%
5
43%
D5
6
50%
(Turn down ration
7.7 to 1)
Y32, Y33, Y34
7
61%
8
68%
9
73%
10
11
12
1
80%
93%
100%
9%
2
106,666
165,332
202,665
229,332
266,666
325,331
362,664
389,331
426,664
495,997
533,330
586,663
655,996
693,329
762,662
799,995
85,333
13%
3
132,266
162,132
183,466
213,333
260,265
290,132
311,465
341,331
396,798
426,664
469,330
524,797
554,663
610,130
639,996
21%
4
25%
5
29%
6
33%
7
41%
8
45%
D8
(Turn down ration
11.5 to 1)
Y34 Only
9
49%
10
11
12
13
14
15
16
17
53%
62%
67%
73%
82%
87%
95%
100%
TABLE 8: ELECTRIC HEATING CAPACITIES
2
MBH AND KW PER STAGE
ELECTRIC
NOMINAL
KW
NOMINAL
MBH
AVAILABLE ON MODELS
HEAT OPTION
RATED VOLTAGE
STAGE 1
STAGE 2
1
KW
MBH
137
137
246
KW
MBH
0
3
4
E4
E8
E1
Y32, Y33, Y34
Y32, Y33, Y34
240 /480 /575
40
80
137
273
369
40
40
72
0
2
3
240 /480 /575
40
36
136
123
3
Y32, Y33, Y34 (460 & 575 volt only)
480 /575
108
1.
2.
3.
4.
Supply air fan motor heat not included.
Heating capacity is only staged on CV models. VAV models use only one stage at full capacity.
For 208 volts, multiply kW and MBH values by .751. For 230 volts, multiply kW and MBH values by .918
For 460 volts, multiply kW and MBH values by .918.
Johnson Controls Unitary Products
13
246653-YTG-E-0108
1
HOT WATER HEATING
The YORK Millennium Rooftop units (30 - 40 Ton sizes) can
be furnished with a YORK hot water coil as the source of heat
(Bottom Supply Only). A one or two row coil will be factory
installed in the heating section downstream of the supply air
fan and just above the supply air opening in the bottom of the
unit.
DO NOT use tin based solder. Brazing with tin
based solder could cause equipment damage or
possible injury to OCCUPANTS of the structure
that is being conditioned.
TABLE 11: HOT WATER COIL (1 ROW, 25 & 30
The hot water control valve will not be provided. The installer
will need to field supply a water valve. The installer must also
connect the hot water piping, and valve wiring at the job site
for the hot water heat section to be operational.
1
TON)
CAPACITY (MBH) AT ENTERING WATER
TEMPERATURE
GPM
10
CFM
140 °F
91.4
160 °F
180 °F
139.3
155.8
168.8
179.6
192.9
156
200 °F
163.6
182.9
198.4
211.2
226.9
182.7
207.7
228.2
245.6
267.8
190.1
217.5
240.2
259.7
284.8
194.1
222.8
246.8
267.5
294.1
For all hot water coils the entering water temperature should
not exceed 200°F.
6000
8000
115.3
128.8
139.5
148.4
159.2
129.4
147
102
10000
12000
15000
6000
110.4
117.3
125.9
103
PHYSICAL DATA HOT WATER COIL - 1 ROW
Coil Casing . . . . . . . . . . . . . . . . . . . . Galvanized Steel
Coil Construction. . . . . . . . . . . . . . . . Al Fin / Cu. Tube
Rows Deep . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Fin Thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . .006”
Tube Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .016”
Tubes / Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Fins Per Inch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Tubes High . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.50”
Tube Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65”
8000
116.8
128.2
137.8
150
177.2
194.7
209.5
228.2
162.5
185.8
205.1
221.8
243
20
30
10000
12000
15000
6000
161.3
173.6
189
107.6
122.8
135.5
146.4
160.3
110.1
126.1
139.6
151.2
166.1
135
8000
154.3
170.3
184
10000
12000
15000
6000
201.6
138
166
8000
158.2
175.2
189.8
208.6
190.5
210.9
228.5
251.3
40
10000
12000
15000
Face Area . . . . . . . . . . . . . . . . . . . . . . . . . . . .10.16ft.2
Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71lbs.
Operating Weight . . . . . . . . . . . . . . . . . . . . . . . .83lbs.
1.
Based on 60°F entering air temperature, 2.00” maximum pres-
sure drop across the hot water coil.
TABLE 9: WATER PRESSURE DROP (1 ROW, 25 &
30 TON)
PIPING CONNECTIONS
GPM
10
20
30
40
WATER PRESSURE DROP
0.9
3.0
6.0
10.0
The hot water piping must enter the unit through the floor of
the heat section compartment. The access doors to the com-
partment are gasketed so the compartment can be sealed.
However, as added protection for water leakage into the
space, the piping access holes should be sealed with a heat
resistant mastic (see the following illustration for approximate
location of the compartment and piping connections.
TABLE 10: STATIC RESISTANCE HOT WATER COIL
(25 & 30 TON)
CFM
6000
0.07
0.14
8000
0.11
0.23
10000
0.16
15000
0.32
AIR PRESSURE DROP 1 ROW
AIR PRESSURE DROP 2 ROW
0.33
0.65
NOTE: Water pressure drop numbers are based on 60°F
entering air temperature, 2.00” maximum air pres-
sure drop across the hot water coil(s). ARI certified
ratings at covering other conditions are available
upon request. Hot water coils are approved for use
with glycol (rates available upon request).
1. Hot water, steam or electric heat is not available for
front or rear supply.
14
Johnson Controls Unitary Products
246653-YTG-E-0108
1
TABLE 13: HOT WATER COIL (1 ROW 40 TON)
(1 OR 2 ROW)
CAPACITY (MBH) AT ENTERING WATER
TEMPERATURE
GPM
CFM
CONDENSING
SECTION
HOT WATER
COIL
140 °F
102
160 °F
128.8
144.1
155.9
165.4
173.3
147
180 °F
155.8
174.4
188.8
200.4
210.1
177.2
202.3
222.4
239
200 °F
182.9
205.1
222.1
235.8
247.3
207.7
237.2
260.8
280.5
297.3
217.5
250.3
276.9
299.3
318.6
222.8
257.5
285.8
309.7
330.6
8000
11000
14000
17000
20000
8000
26"
114
INLET (2")
OUTLET (2")
8.38"
10
123.2
130.6
136.8
116.8
133.2
146.2
157
OUTSIDE OF
BASE RAIL
15.8"
11.88"
2.25"
2.55"
88.75"
11000
14000
17000
20000
8000
167.7
184.2
197.9
209.6
154.3
177.4
196.1
211.8
225.3
158.2
182.7
202.6
219.5
234.2
HEAT SECTION
COMPARTMENT
C
L
20
30
166.2
122.8
141.2
155.9
168.3
179.1
126.1
145.6
161.4
174.7
186.3
253.2
185.8
213.8
236.4
255.4
271.8
190.5
220
FIGURE 1 - HOT WATER PIPING CROSS-SEC-
TION
11000
14000
17000
20000
8000
TABLE 12: STATIC RESISTANCE HOT WATER COIL
(1 ROW, 40 TON)
11000
14000
17000
20000
CFM
8000
0.11
0.23
11000
0.19
14000
0.29
20000
0.52
40
244.1
264.5
282.3
AIR PRESSURE DROP 1 ROW
AIR PRESSURE DROP 2 ROW
0.39
0.58
1.06
1.
Based on 60°F entering air temperature, 2.00” maximum pres-
sure drop across the hot water coil.
Johnson Controls Unitary Products
15
246653-YTG-E-0108
2 3 0 .0
2 2 0 .0
2 1 0 .0
2 0 0 .0
1 9 0 .0
1 8 0 .0
1 7 0 .0
1 6 0 .0
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 1 0 .0
1 0 0 .0
9 0 .0
1 4 0 °F
1 6 0 °F
1 8 0 °F
2 0 0 °F
8 0 .0
6 0 0 0
7 0 0 0
8 0 0 0
9 0 0 0
1 0 0 0 0
1 1 0 0 0
1 2 0 0 0
1 3 0 0 0
1 4 0 0 0
1 5 0 0 0
F L O W R A T E (C F M )
FIGURE 2 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 10 GPM
270.0
260.0
250.0
240.0
230.0
220.0
210.0
200.0
190.0
180.0
170.0
160.0
150.0
140.0
130.0
120.0
110.0
100.0
90.0
140 °F
160 °F
180 °F
200 °F
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
FLO W RATE (CFM )
FIGURE 3 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 20 GPM
16
Johnson Controls Unitary Products
246653-YTG-E-0108
2 9 0 .0
2 8 0 .0
2 7 0 .0
2 6 0 .0
2 5 0 .0
2 4 0 .0
2 3 0 .0
2 2 0 .0
2 1 0 .0
2 0 0 .0
1 9 0 .0
1 8 0 .0
1 7 0 .0
1 6 0 .0
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 1 0 .0
1 0 0 .0
1 4 0 °F
1 6 0 °F
1 8 0 °F
2 0 0 °F
6 0 0 0
7 0 0 0
8 0 0 0
9 0 0 0
1 0 0 0 0
1 1 0 0 0
1 2 0 0 0
1 3 0 0 0
1 4 0 0 0
1 5 0 0 0
F L O W R A T E (C F M )
FIGURE 4 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 30 GPM
300.0
290.0
280.0
270.0
260.0
250.0
240.0
230.0
220.0
210.0
200.0
190.0
180.0
170.0
160.0
150.0
140.0
130.0
120.0
110.0
100.0
140 °F
160 °F
180 °F
200 °F
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R AT E (C F M )
FIGURE 5 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 40 GPM
Johnson Controls Unitary Products
17
246653-YTG-E-0108
250.0
240.0
230.0
220.0
210.0
200.0
190.0
180.0
170.0
160.0
150.0
140.0
130.0
120.0
110.0
100.0
90.0
140 °F
160 °F
180 °F
200 °F
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
FLO W R AT E (C FM )
FIGURE 6 - HOT WATER COIL - 40 TON, 1 ROW, AT 10 GPM
300.0
290.0
280.0
270.0
260.0
250.0
240.0
230.0
220.0
210.0
200.0
190.0
180.0
170.0
160.0
150.0
140.0
130.0
120.0
110.0
100.0
140 °F
160 °F
180 °F
200 °F
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
FLO W RATE (CFM )
FIGURE 7 - HOT WATER COIL - 40 TON, 1 ROW, AT 20 GPM
18
Johnson Controls Unitary Products
246653-YTG-E-0108
320.0
310.0
300.0
290.0
280.0
270.0
260.0
250.0
240.0
230.0
220.0
210.0
200.0
190.0
180.0
170.0
160.0
150.0
140.0
130.0
120.0
110.0
140 °F
160 °F
180 °F
200 °F
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
FLOW RATE (CFM )
FIGURE 8 - HOT WATER COIL - 40 TON, 1 ROW, AT 30 GPM
3 4 0 .0
3 3 0 .0
3 2 0 .0
3 1 0 .0
3 0 0 .0
2 9 0 .0
2 8 0 .0
2 7 0 .0
2 6 0 .0
2 5 0 .0
2 4 0 .0
2 3 0 .0
2 2 0 .0
2 1 0 .0
2 0 0 .0
1 9 0 .0
1 8 0 .0
1 7 0 .0
1 6 0 .0
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 4 0 °F
1 6 0 °F
1 8 0 °F
2 0 0 °F
8 0 0 0
9 0 0 0
1 0 0 0 0
1 1 0 0 0
1 2 0 0 0
1 3 0 0 0
1 4 0 0 0
1 5 0 0 0
1 6 0 0 0
1 7 0 0 0
1 8 0 0 0
1 9 0 0 0
2 0 0 0 0
F L O W R A T E (C F M )
FIGURE 9 - HOT WATER COIL - 40 TON, 1 ROW, AT 40 GPM
Johnson Controls Unitary Products
19
246653-YTG-E-0108
PHYSICAL DATA HOT WATER COIL - 2 ROW
TABLE 16: HOT WATER COIL (2 ROW, 25 & 30
1
TON) (CONTINUED)
Coil Casing . . . . . . . . . . . . . . . . . . . . Galvanized Steel
Coil Construction. . . . . . . . . . . . . . . . Al Fin / Cu. Tube
Rows Deep . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Fin Thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . .006”
Tube Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .016”
Tubes / Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Fins Per Inch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Tubes High . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.50”
Tube Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65”
CAPACITY (MBH) AT ENTERING WATER TEMPERATURE
GPM
60
CFM
140 °F
206.1
243.6
275.3
302.9
338.4
210.5
249.8
283.3
312.7
351.0
160 °F
258.7
305.9
345.9
380.7
425.7
263.9
313.3
355.6
392.7
440.9
180 °F
311.4
368.4
416.8
458.9
513.4
317.4
377.1
428.2
473.0
531.3
200 °F
364.2
431.1
488.0
537.6
601.7
371.1
441.1
501.0
553.6
622.1
6000
8000
10000
12000
15000
6000
8000
80
10000
12000
15000
1.
Based on 60°F entering air temperature, 2.00” maximum pres-
sure drop across the hot water coil.
Face Area . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.16 ft.2
Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90 lbs
1
TABLE 17: HOT WATER COIL (2 ROWS, 40 TON)
Operating Weight . . . . . . . . . . . . . . . . . . . . . . .110 lbs
CAPACITY (MBH) AT ENTERING WATER
TEMPERATURE
GPM
CFM
140 °F
203.8
233.9
257.0
275.5
290.9
232.2
273.3
306.3
333.9
357.5
243.6
289.5
327.2
359.2
386.9
249.8
298.5
338.9
373.4
403.6
160 °F
180 °F
311.1
358.1
394.2
423.3
447.4
352.2
415.3
466.3
508.9
545.4
368.4
438.5
496.3
545.3
587.9
377.1
451.2
512.8
565.6
611.8
200 °F
365.5
421.0
463.8
498.3
526.9
412.7
487.0
547.1
597.3
640.5
431.1
513.6
581.5
639.2
689.4
441.1
528.1
600.5
662.5
716.8
TABLE 14: WATER PRESSURE DROP (2 ROW, 25 &
30 TON)
8000
11000
14000
17000
20000
8000
257.2
295.7
325.3
349.0
368.7
292.0
344.1
386.0
421.1
451.1
305.9
363.9
411.5
452.0
487.1
313.3
374.7
425.7
469.3
507.5
20
GPM
20
40
60
80
WATER
PRESSURE
DROP
0.9
3.0
6.0
10.0
11000
14000
17000
20000
8000
TABLE 15: STATIC RESISTANCE HOT WATER COIL
(25 & 30 TON)
40
60
CFM
6000
8000
10000
15000
AIR PRESSURE DROP
1 ROW
11000
14000
17000
20000
8000
0.07
0.11
0.16
0.32
AIR PRESSURE DROP
2 ROW
0.14
0.23
0.33
0.65
NOTE: Water pressure drop numbers are based on 60°F
entering air temperature, 2.00” maximum air pres-
sure drop across the hot water coil(s). ARI certified
ratings at covering other conditions are available
upon request. Hot water coils are approved for use
with glycol (rates available upon request.)
11000
14000
17000
20000
80
1.
Based on 60°F entering air temperature, 2.00” maximum air
pressure drop across the hot water coil.
ARI certified ratings at other conditions available upon request.
Hot water coils are approved for use with glycol (ratings avail-
able upon request).
TABLE 16: HOT WATER COIL (2 ROW, 25 & 30
1
TON)
TABLE 18: STATIC RESISTANCE HOT WATER
COIL (40 TON)
CAPACITY (MBH) AT ENTERING WATER TEMPERATURE
GPM
20
CFM
140 °F
177.5
203.8
224.8
242.2
263.6
198.1
232.2
260.7
285.0
316.0
160 °F
223.8
257.2
284.1
306.4
333.8
248.9
292.0
328.1
359.0
398.4
180 °F
270.4
311.1
343.9
371.1
404.6
300.0
352.2
395.9
433.4
481.3
200 °F
317.3
365.5
404.2
436.4
476.1
351.3
412.7
464.1
508.3
564.8
6000
8000
CFM
8000
0.11
0.23
11000
0.19
14000
0.29
20000
0.52
AIR PRESSURE DROP 1 ROW
AIR PRESSURE DROP 2 ROW
10000
12000
15000
6000
0.39
0.58
1.06
TABLE 19: WATER PRESSURE DROP (2 ROW, 40
TON)
8000
40
10000
12000
15000
GPM
20
40
60
80
WATER PRESSURE DROP
0.9
3.0
6.0
10.0
20
Johnson Controls Unitary Products
246653-YTG-E-0108
480.0
460.0
440.0
420.0
400.0
380.0
360.0
340.0
320.0
300.0
280.0
260.0
240.0
220.0
200.0
180.0
160.0
140 °F
160 °F
180 °F
200 °F
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F LO W R AT E (C F M )
FIGURE 10 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 20 GPM
580.0
560.0
540.0
520.0
500.0
480.0
460.0
440.0
420.0
400.0
380.0
360.0
340.0
320.0
300.0
280.0
260.0
240.0
220.0
200.0
180.0
140 °F
160 °F
180 °F
200 °F
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R AT E (C F M )
FIGURE 11 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 40 GPM
Johnson Controls Unitary Products
21
246653-YTG-E-0108
610.0
590.0
570.0
550.0
530.0
510.0
490.0
470.0
450.0
430.0
410.0
390.0
370.0
350.0
330.0
310.0
290.0
270.0
250.0
230.0
210.0
140 °F
160 °F
180 °F
200 °F
190.0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
FLO W RATE (CFM )
FIGURE 12 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 60 GPM
640.0
620.0
600.0
580.0
560.0
540.0
520.0
500.0
480.0
460.0
440.0
420.0
400.0
380.0
360.0
340.0
320.0
300.0
280.0
260.0
240.0
220.0
200.0
140 °F
160 °F
180 °F
200 °F
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
FLO W R AT E (C FM )
FIGURE 13 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 80 GPM
22
Johnson Controls Unitary Products
246653-YTG-E-0108
530.0
510.0
490.0
470.0
450.0
430.0
410.0
390.0
370.0
350.0
330.0
310.0
290.0
270.0
250.0
230.0
210.0
190.0
140 °F
160 °F
180 °F
200 °F
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
FLO W R ATE (C FM )
FIGURE 14 - HOT WATER COIL - 40 TON, 2 ROW, AT 20 GPM
650.0
630.0
610.0
590.0
570.0
550.0
530.0
510.0
490.0
470.0
450.0
430.0
410.0
390.0
370.0
350.0
330.0
310.0
290.0
270.0
250.0
230.0
210.0
140 °F
160 °F
180 °F
200 °F
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
FLO W R AT E (C F M )
FIGURE 15 - HOT WATER COIL - 40 TON, 2 ROW, AT 40 GPM
Johnson Controls Unitary Products
23
246653-YTG-E-0108
700.0
680.0
660.0
640.0
620.0
600.0
580.0
560.0
540.0
520.0
500.0
480.0
460.0
440.0
420.0
400.0
380.0
360.0
340.0
320.0
300.0
280.0
260.0
240.0
220.0
140 °F
160 °F
180 °F
200 °F
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
FLO W R AT E (C FM )
FIGURE 16 - HOT WATER COIL - 40 TON, 2 ROW, AT 60 GPM
730.0
710.0
690.0
670.0
650.0
630.0
610.0
590.0
570.0
550.0
530.0
510.0
490.0
470.0
450.0
430.0
410.0
390.0
370.0
350.0
330.0
310.0
290.0
270.0
250.0
230.0
140 °F
160 °F
180 °F
200 °F
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R AT E (C F M )
FIGURE 17 - HOT WATER COIL - 40 TON, 2 ROW, AT 80 GPM
24
Johnson Controls Unitary Products
246653-YTG-E-0108
STEAM HEATING
TABLE 22: STEAM COIL (1 ROW, 40 TON)
CAPACITY (MBH) AT STEAM PRESSURE (PSI)
The YORK Millennium units (25, 30, and 40 ton sizes) can be
manufactured with a steam heat coil (Bottom Supply only).
YORK's one row steam coil is installed in the heating section
just downstream of the supply air fan and just above the sup-
ply air opening in the bottom of the unit.
CFM
2
6
10
15
8000
11000
14000
17000
20000
221.1
252.9
278.2
299.4
317.6
236.9
271.0
298.0
320.7
340.2
250.4
286.4
315.0
339.0
359.6
265.0
303.1
333.4
358.8
380.6
The steam control valve will not be provided. The installer
will need to field supply a steam control valve. Connect the
steam piping and valve power wiring at the job site for the
steam heat section to be operational.
TABLE 23: STATIC RESISTANCE STEAM COIL
(1 ROW, 40 TON)
There are no provisions in the coil or control sequence to pre-
vent freezing of condensate. The control valve, piping and
field installed wiring connections are particularly vulnerable
because they are installed in the vestibule outside of the con-
ditioned air stream.
CFM
8000
11000
14000
17000
20000
AIR PRESSURE DROP
0.18
0.31
0.48
0.67
0.88
PIPING CONNECTIONS
The steam piping must enter the unit through the floor of the
heat section compartment. The access doors to the compart-
ment are gasketed to the compartment can be sealed. How-
ever, as added protection for condensate leakage into the
space, the piping access holes should be sealed with a heat
resistant mastic. The following figure illustrates the approxi-
mate location of the compartment and piping connections.
All piping, control valves, and wiring that is field installed must
conform to all local and national codes
Condensate can freeze on the control valve and piping if they
are not properly insulated.
PHYSICAL DATA STEAM COIL - 1 ROW
Coil Casing . . . . . . . . . . . . . . . . . . . . Galvanized Steel
Coil Construction . . . . . . . . . . . . . . . Al Fin / Cu. Tube
Rows Deep. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Fin Thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . ..010”
Tube Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..035”
Tubes / Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Fins Per Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Tubes High . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21”
Tube Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65”
T
O
P
V
I
E
W
C
O
N
D
E
N
S
I
N
G
S
T
E
O
A
M
S
E
C
T
I
O
N
C
I
L
2
6
"
O
U
T
L
E
T
(
1
1
/
2
"
)
O
U
T
S
I
D
E
O
F
1
5
.
8
"
I
N
L
E
T
(
2
"
)
B
A
S
E
R
A
I
L
8
"
8
.
3
8
"
Face Area. . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.48 ft.2
Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 lbs.
2
.
5
5
"
9
"
8
8
.
7
5
"
H
E
A
T
S
E
C
T
I
E
O
N
*Hot water, steam coil or electric heat not available for front or
rear supply.
C
O
M
P
A
R
T
M
N
T
C
L
1
FIGURE 18 - STEAM PIPING CROSS SECTION
TABLE 20: STEAM COIL (1 ROW, 25 & 30 TON)
CAPACITY (MBH) AT STEAM PRESSURE (PSI)
CFM
2
6
10
15
6000
8000
194.1
221.1
243.2
261.9
285.6
207.9
236.9
260.5
280.6
306.0
219.8
250.4
275.4
296.6
323.5
232.6
265.0
291.4
313.9
342.4
10000
12000
15000
DO NOT use tin based solder. Brazing with tin
based solder could cause equipment damage or
possible injury to OCCUPANTS of the structure that
is being conditioned.
1.
Based on 60°F entering air temperature, 2.00” maximum air
pressure drop across the coil.
TABLE 21: STATIC RESISTANCE STEAM COIL
(1 ROW, 25 & 30 TON)
CFM
6000
8000
10000
12000
15000
AIR PRESSURE DROP
0.11
0.18
0.26
0.36
0.54
Johnson Controls Unitary Products
25
246653-YTG-E-0108
350
340
330
320
310
300
290
280
270
260
250
240
230
220
210
200
190
180
2 psi
6 psi
10 psi
15 psi
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
FLO W R ATE (C FM )
FIGURE 19 - STEAM COIL - 25 & 30 TON, 1 ROW
390
380
370
360
350
340
330
320
310
300
290
280
270
260
250
240
230
220
210
2 psi
6 psi
10 psi
15 psi
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
FLOW RATE (CFM )
FIGURE 20 - STEAM COIL - 40 TON, 1 ROW
26
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 24: EXHAUST FAN DRIVE DATA
MOTOR
MOTOR PULLEY
BLOWER PULLEY
BELTS
BLOWER
RPM
RANGE
MOTOR EFF
(STD.
MOTOR)
MOTOR
EFF (HI
EFF OPT)
MODEL
FRAME
SIZE
PITCH DIA
BORE
PITCH DIA
BORE
HP
DESIGNATION
QTY
(INCHES)
(INCHES)
(INCHES)
(INCHES)
758
852
976
852
976
1069
852
976
1069
5
213T
215T
215T
213T
215T
254T
184T
215T
254T
87.5
88.5
89.5
84
89.5
91.7
91
4.9
5.5
6.3
5.5
6.3
6.9
5.5
6.3
6.9
1-3/8
1-3/8
1-5/8
1-3/8
1-3/8
1-3/8
1-3/8
1-3/8
1-3/8
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
2-3/16
2-3/16
BX63
BX63
BX63
B65
2
2
2
2
2
2
2
2
2
25 Ton
30 Ton
40 Ton
7.5
10
7.5
10
15
7.5
10
15
2-3/16
86.5
89.5
89.5
86.5
89.5
89.5
1-11/16
1-11/16
1-11/16
1-11/16
1-11/16
1-11/16
86.5
85.7
84
B65
B65
B65
86.5
85.7
B65
B65
1
TABLE 25: SUPPLY FAN MOTOR AND DRIVE DATA
MOTOR
MOTOR PULLEY
BLOWER PULLEY
BELTS
BLOWER
RPM
RANGE
MOTOR
MOTOR
EFFICIENCY
(STD. MOTOR)
MODEL
25 Ton
30 Ton
FRAME
SIZE
EFFICIENCY
(ULTRA HI
EFF OPT)
PITCH DIA
(INCHES)
BORE
(INCHES)
PITCH DIA
(INCHES)
BORE
(INCHES)
DESIGNA
TION
HP
QTY
567
692
793
894
617
743
856
907
617
652
728
780
7.5
10
15
20
10
15
20
25
10
15
20
25
213T
215T
254T
256T
215T
254T
256T
284T
215T
254T
256T
284T
88.5
89.5
91
91.7
91
4.5
5.5
6.3
7.1
4.9
5.9
6.7
7.1
4.9
5.1
5.7
6.1
1-3/8
1-3/8
1-5/8
1-5/8
1-3/8
1-5/8
1-5/8
1-7/8
1-3/8
1-5/8
1-5/8
1-7/8
13.9
13.9
13.9
13.9
13.9
13.9
13.7
13.7
13.9
13.7
13.7
13.7
2-3/16
2-3/16
2-3/16
2-3/16
2-3/16
2-3/16
2-3/16
2-3/16
2-7/16
2-7/16
2-7/16
2-7/16
BX56
BX56
2
2
2
2
2
2
2
2
2
2
2
2
91.7
93
BX56
91
BX56
89.5
91
91
BX56
91.7
93
BX56
91
5VX610
5VX610
BX67
91.7
89.5
91
93.6
91
91.7
93
5VX710
5VX710
5VX710
40 Ton
91
91.7
93.6
1.
kW = (BHP X 0.746) / Motor Eff.
MBH = kW X 3.414
MBH = (BHP X 2.546) / Motor Eff.
NOTES: 1) Class I Blowers are limited to 15 HP motors on 25 and 30 Ton units.
2) Class I Blowers are limited to 20 HP motors on the 40 Ton units.
3) Class II Blowers are not HP limited, can use 25 HP.
Johnson Controls Unitary Products
27
246653-YTG-E-0108
SUPPLY AIR DRIVE ADJUSTMENT
At unit start-up, the measured CFM may be higher or lower
achieve the specified CFM, the speed of the drive may have
to be decreased or increased by changing the pitch diameter
(PD) of the motor sheave as outlined below:
Even small changes in blower speed can result in
substantial changes in static pressure and bhp.
Bhp or amp draw of the blower motor will increase
(see table) by the cube ratio of the blower speed.
Static pressure will increase by the square ratio of
reference only. All blower speed changes must be
made by qualified personnel with strict adherence
to the fan laws.
Example:
Failure to properly adjust the total system air quan-
tity can result in extensive blower damage.
A 30-ton unit was selected to deliver 12,000 CFM with a 20
HP motor and a 856 RPM drive, but the unit is only delivering
Use the equation to determine the required PD for the new
motor sheave (12,000 CFM / 11,000 CFM) x 6.7” = 7.31”.
Before making any blower speed changes review
the installation for any installation errors, leaks or
undesirable systems effects that can result in loss
of air flow.
Use the 30-ton table to select a Browning 2B5V74 which will
increase the speed of the unit's drive and its supply air CFM
109%.
New drive speed = 1.091 x 856 = 933 RPM
New supply air = 1.091 x 11,000 = 12,000 CFM
Re-use the existing belts and blower sheave.
New motor BHP = (speed increase)3 x estimated motor
BHP at original start-up with 11,000 CFM and 856 RPM =
(1.091)3 x 11.0 BHP = 1.2986 x 11.0 BHP = 14.3 BHP
New motor amps = (speed increase)3 x measured motor
amps at original start-up with 11,000 CFM and 856 RPM.
28
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 26: 25 TON DRIVE ADJUSTMENT
7.5 HP MOTOR & 567 RPM DRIVE
10 HP MOTOR & 692 RPM DRIVE
15 HP MOTOR & 793 RPM DRIVE
20 HP MOTOR & 894 RPM DRIVE
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
-
-
-
-
82
86
89
93
96
4.5
4.7
4.9
5.1
5.3
42
44
46
48
50
84
87
90
94
97
5.3
5.5
5.7
5.9
6.1
50
52
54
56
58
86
89
91
94
97
6.1
6.3
6.5
6.7
6.9
58
60
62
64
66
-
-
100
104
109
(Std.)4.5
4.7
42
44
46
4.9
(Std.)
5.5
(Std)
6.3
(Std.)
7.1
113
5.1
48
100
52
100
60
100
68
118
5.3
5.5
5.7
-
50
52
54
-
104
107
111
115
118
122
5.7
5.9
6.1
6.3
6.5
6.7
54
56
58
60
62
64
103
106
110
113
116
122
6.5
6.7
6.9
7.1
7.3
7.7
62
64
66
68
70
74
103
108
117
125
-
7.3
7.7
8.3
8.9
-
70
74
80
86
-
122
126
-
-
-
-
-
-
-
-
-
-
TABLE 27: 30 TON DRIVE ADJUSTMENT
10 HP MOTOR & 617 RPM DRIVE
15 HP MOTOR & 743 RPM DRIVE
20 HP MOTOR & 856 RPM DRIVE
25 HP MOTOR & 907 RPM DRIVE
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
91.8
95.9
4.5
4.7
42
44
86.4
89.8
5.1
5.3
48
50
82.1
85.1
5.5
5.7
54
56
86.3
89.0
6.1
6.3
60
62
(Std.)
4.9
100.0
104.1
108.2
46
48
50
93.2
96.6
5.5
5.7
52
54
56
88.1
91.0
94.0
5.9
6.1
6.3
58
60
62
91.8
94.5
97.3
6.5
6.7
6.9
64
66
68
5.1
(Std.)
5.9
5.3
100.0
(Std.)
7.1
112.2
116.3
5.5
5.7
52
54
103.4
106.8
6.1
6.3
58
60
97.0
6.5
64
66
100.0
105.5
70
74
(Std.)
6.7
100.0
7.5
120.4
5.9
56
58
-
110.2
113.6
116.9
120.3
123.7
6.5
6.7
6.9
7.1
7.3
62
64
66
68
70
103.0
106.0
112.0
120.9
129.9
6.9
7.1
7.5
8.1
8.7
68
70
74
80
86
113.7
8.1
80
86
-
124.5
6.1
121.9
8.7
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
TABLE 28: 40 TON DRIVE ADJUSTMENT
10 HP MOTOR & 617 RPM DRIVE
15 HP MOTOR & 652 RPM DRIVE
20 HP MOTOR & 728 RPM DRIVE
25 HP MOTOR & 780 RPM DRIVE
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
% RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
91.8
95.9
4.5
4.7
42
44
88.2
92.1
4.5
4.7
44
46
82.5
86.0
4.7
4.9
46
48
83.7
86.9
5.1
5.3
50
52
(Std.)
4.9
100.0
46
96.0
4.9
48
89.5
5.1
50
90.2
5.5
54
(Std.)
5.1
104.1
108.2
112.2
5.1
5.3
5.5
48
50
52
100.0
103.9
107.8
50
52
54
93.0
96.5
5.3
5.5
52
54
56
93.4
96.7
5.7
5.9
56
58
60
5.3
(Std.)
5.7
(Std.)
6.1
5.5
100.0
100.0
116.3
5.7
54
-
111.7
115.6
119.5
123.4
127.4
-
5.7
5.9
6.1
6.3
6.5
-
56
58
60
62
64
66
103.5
107.0
110.5
114.0
117.5
121.1
5.9
6.1
6.3
6.5
6.7
6.9
58
60
62
64
66
68
103.3
106.6
109.8
113.1
116.4
119.7
6.3
6.5
6.7
6.9
7.1
7.5
62
64
66
68
70
74
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1) Class I Blowers are limited to 15 HP motors on 25 and 30 Ton units.
2) Class I Blowers are limited to 20 HP motors on the 40 Ton units.
3) Class II Blowers are not HP limited, can use 25 HP.
Johnson Controls Unitary Products
29
246653-YTG-E-0108
TABLE 29: DRIVE ADJUSTMENT FOR POWER EXHAUST - 25 TON
5 HP MOTOR & 759 RPM DRIVE
7.5 HP MOTOR & 852 RPM DRIVE
10 HP MOTOR & 975 RPM DRIVE
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
BROWNING
2B5V_ _
REQ’D PD
100
(Std.) 4.9
5.1
46
92
5.1
5.3
48
93
5.9
6.1
56
104
48
96
50
97
58
109
5.3
50
100
104
108
112
(Std.) 5.5
5.7
52
100
103
107
110
(Std.) 6.3
6.5
60
113
5.5
52
54
62
117
5.7
54
5.9
56
6.7
64
122
5.9
56
6.1
58
6.9
66
TABLE 30: DRIVE ADJUSTMENT FOR POWER EXHAUST - 30 & 40 TON
7.5 HP MOTOR & 852 RPM DRIVE
10 HP MOTOR & 976 RPM DRIVE
15 HP MOTOR & 1069 RPM DRIVE
% RPM
& CFM
REQ’D
PD (IN)
BROWNING
2B5V_ _
% RPM
& CFM
REQ’D
PD (IN)
BROWNING
2B5V_ _
% RPM
& CFM
REQ’D
PD (IN)
BROWNING
2B5V_ _
96.4
5.3
(Std.) 5.5
5.7
52
93.7
5.9
6.1
58
94.2
6.5
6.7
64
100.0
103.6
107.3
110.9
114.5
54
96.8
60
97.1
66
56
100.0
103.2
106.3
109.5
(Std.) 6.3
6.5
62
100.0
102.9
108.7
117.4
(Std.) 6.9
7.1
68
5.9
58
64
70
6.1
60
6.7
66
7.5
74
6.3
62
6.9
68
8.1
80
30
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 31: COOLING PERFORMANCE 25 TON
TEMPERATURE OF AIR ON CONDENSER COIL
2
AIR ON EVAPORATOR COIL
75°F
85°F
2
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
TOTAL
CAP.
(MBH)
TOTAL
INPUT
(KW)
TOTAL
TOTAL
INPUT
(KW)
WB
(°F)
1
1
CFM
7500
CAP.
(MBH)
86 83 80 77 74 71 68
86 83 80 77 74 71 68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
337.7
310.2
271.9
243.9
344.1
316.1
277.1
248.7
350.5
321.9
282.3
253.4
355.5
326.5
286.3
257.1
360.5
331.1
290.4
260.8
23.0
21.6
21.5
20.8
23.7
22.2
22.1
21.4
24.3
22.8
22.7
21.9
26.5
24.9
24.7
23.9
28.7
26.9
26.8
25.9
179 165 152 138 124
-
-
326.9
296.8
269.6
253.3
331.9
301.4
273.7
257.2
336.8
305.9
277.9
261.0
341.2
309.8
281.4
264.4
345.5
313.8
285.0
267.7
24.5
23.9
23.5
23.1
25.2
24.5
24.1
23.7
25.8
25.1
24.7
24.3
27.7
27.0
26.6
26.1
29.7
28.9
28.4
28.0
175 161 147 133 119
-
-
223 209 195 181 168 154 140
254 240 226 212 198 184 170
243 247 246 233 219 205 191
217 203 189 175 161 147 134
257 243 229 215 201 187 174
253 253 246 232 218 204 190
194 177 159 141 124
-
-
186 170 154 138 122
-
-
240 222 205 187 170 152 134
268 255 237 220 202 184 167
248 250 259 241 223 206 188
230 214 198 182 165 149 133
267 256 240 223 207 191 175
257 257 257 241 224 208 192
8750
10000
11250
12500
209 188 166 145 124
-
-
198 179 161 142 124
-
-
257 236 214 193 172 150 129
282 270 248 227 206 184 163
253 253 271 249 228 207 185
244 225 206 188 169 151 132
277 269 250 232 213 194 176
261 261 268 249 231 212 194
218 197 177 156 136
-
-
209 190 171 152 133
-
-
269 249 228 208 187 167 146
286 280 267 247 226 206 185
257 257 265 245 224 204 183
258 239 220 201 182 163 144
281 277 266 247 228 210 191
264 264 268 249 230 211 192
227 207 187 168 148
-
-
221 201 182 162 143
-
-
281 261 242 222 202 183 163
290 290 286 267 247 227 208
260 260 260 241 221 201 182
95°F
272 253 233 214 195 175 156
285 285 283 263 244 225 205
267 267 267 248 228 209 190
105°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
316.1
283.5
267.4
262.7
319.6
286.7
270.4
265.7
323.2
289.8
273.4
268.6
326.8
293.1
276.5
271.7
330.5
296.4
279.6
274.7
26.1
26.2
25.5
25.4
26.6
26.8
26.1
26.0
27.2
27.4
26.7
26.6
29.0
29.1
28.4
28.3
30.7
30.9
30.1
30.0
171 157 143 129 115
-
-
297.4
268.6
251.6
242.6
301.6
272.4
255.1
246.0
305.7
276.1
258.6
249.4
309.0
279.0
261.4
252.0
312.2
282.0
264.1
254.7
29.4
29.0
28.5
28.3
29.9
29.5
28.9
28.8
30.3
30.0
29.4
29.2
32.2
31.8
31.2
31.0
34.0
33.6
32.9
32.8
162 149 135 121 107
-
-
211 197 183 169 155 141 127
260 246 232 219 205 191 177
262 259 245 231 217 203 189
204 190 176 163 149 135 121
248 239 226 212 198 184 170
242 240 232 218 204 190 176
7500
8750
179 164 149 134 119
-
-
170 155 141 126 111
-
-
221 206 191 176 161 146 131
267 257 242 227 212 198 183
265 263 255 240 225 210 196
214 199 184 170 155 140 125
253 248 236 221 206 191 177
246 245 242 227 212 198 183
187 171 155 139 124
-
-
178 162 147 131 115
-
-
230 214 199 183 167 151 136
273 268 252 236 220 205 189
268 268 265 250 234 218 202
223 208 192 177 161 145 130
258 256 246 230 214 199 183
249 249 252 237 221 205 190
10000
11250
12500
200 183 166 148 131
-
-
191 174 157 139 122
-
-
247 229 212 194 177 160 142
276 273 266 248 231 213 196
271 271 270 252 235 217 200
240 223 205 188 171 153 136
261 260 255 237 220 203 185
252 252 253 236 219 201 184
214 195 176 157 138
-
-
205 186 167 148 129
-
-
264 244 225 206 187 168 149
279 279 279 260 241 222 203
274 274 274 255 236 217 198
115°F
256 237 218 199 180 161 142
264 264 264 245 226 207 188
254 254 254 235 216 197 178
125°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
278.8
253.7
235.8
222.5
283.5
258.0
239.8
226.3
288.3
262.4
243.9
230.1
291.1
265.0
246.2
232.3
293.9
267.5
248.6
234.6
32.7
31.9
31.4
31.2
33.1
32.2
31.7
31.5
33.4
32.6
32.1
31.8
35.4
34.4
34.0
33.7
37.3
36.3
35.8
35.6
154 140 126 113 99.
-
-
260.1
238.8
220.0
202.4
265.5
243.7
224.5
206.6
270.8
248.6
229.1
210.8
273.3
250.9
231.1
212.7
275.7
253.1
233.1
214.5
36.1
34.7
34.4
34.0
36.3
34.9
34.6
34.3
36.5
35.1
34.8
34.5
38.6
37.1
36.7
36.4
40.6
39.1
38.7
38.3
145 132 118 104 91.
-
-
197 183 170 156 142 129 115
235 232 219 205 191 178 164
222 222 219 205 191 177 164
190 177 163 149 136 122 109
220 220 212 198 185 171 157
202 202 202 192 178 165 151
7500
8750
162 147 132 118 103
-
-
153 138 124 109 95.
-
-
207 192 178 163 149 134 119
239 238 229 214 200 185 171
226 226 229 214 200 185 170
200 186 171 157 142 128 113
224 224 223 208 194 179 165
206 206 206 201 187 172 158
169 154 138 123 107
-
-
161 145 130 115 99.
-
-
217 201 186 170 155 139 124
243 243 239 224 208 193 178
230 230 239 224 208 193 177
210 195 179 164 149 133 118
229 229 229 218 202 187 172
210 210 210 210 196 180 165
10000
11250
12500
182 165 148 131 113
-
-
173 156 139 122 105
-
-
233 216 199 181 164 147 130
246 246 244 227 209 192 175
232 232 237 220 202 185 168
226 209 192 175 158 141 124
231 231 231 216 199 182 165
212 212 212 203 186 169 152
195 176 157 138 119
-
-
185 167 148 129 110
-
-
249 230 211 192 173 155 136
248 248 248 229 210 191 173
234 234 234 215 196 177 159
242 223 204 185 167 148 129
233 233 233 214 195 176 158
214 214 214 195 177 158 139
1.
2.
The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat *MBh = 3.415 x kW). Refer to the
appropriate Blower Performance table for the kW of the supply air blower motor.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
31
246653-YTG-E-0108
TABLE 32: COOLING PERFORMANCE 30 TON STANDARD CAPACITY COIL
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON EVAPORATOR COIL
75°F
85°F
2
2
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
TOTAL
CAP.
(MBH)
TOTAL
INPUT
(KW)
TOTAL
CAP.
(MBH)
TOTAL
WB
(°F)
1
1
CFM
6000
INPUT
(KW)
86 83 80 77 74 71 68
86 83 80 77 74 71 68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
385
353
330
316
398
366
342
339
405
375
354
353
415
385
369
368
420
393
379
379
424
399
391
391
430
406
399
402
436
401
410
409
436
419
416
418
439
425
421
424
27.8
27.3
26.6
26.1
28.0
27.2
26.9
26.8
28.3
27.5
27.1
27.3
28.5
27.6
27.3
27.5
28.7
27.7
27.5
27.1
28.8
27.9
27.5
27.4
28.6
28.0
27.6
27.6
29.0
28.1
27.5
27.5
29.0
28.2
27.9
27.9
28.8
28.2
27.8
27.8
223 203 183 163 142
-
-
370
341
316
306
382
353
329
326
391
362
342
342
398
371
356
356
404
378
368
367
408
383
378
378
412
388
387
387
416
393
395
395
419
403
402
402
422
409
408
408
30.6
30.0
29.4
28.9
30.9
30.2
29.7
29.4
31.1
30.4
29.9
29.7
31.2
30.6
30.1
30.0
31.4
30.7
30.2
30.2
31.5
30.8
30.3
30.4
31.5
30.9
30.6
30.6
31.6
31.0
30.7
30.7
31.7
31.1
30.9
30.9
31.7
31.2
31.0
31.0
217 197 177 157 136
-
-
259 240 220 200 179 159 141
295 275 254 235 215 195 175
316 307 287 269 249 229 209
254 234 214 194 174 153 133
289 269 249 229 209 189 169
306 298 283 263 243 223 203
240 216 193 169 145
-
-
234 210 187 163 139
-
-
281 258 238 212 191 164 143
321 300 279 256 230 206 183
339 327 318 293 270 246 226
276 253 230 206 183 159 135
318 294 271 248 224 201 177
326 316 307 288 264 241 218
7000
8000
256 229 202 175 147
-
-
250 223 196 169 141
-
-
304 277 250 223 196 169 141
354 327 297 270 247 217 190
353 344 334 322 290 263 239
298 271 245 218 191 164 136
342 319 292 265 239 212 185
342 332 322 312 285 258 232
272 241 211 183 149
-
-
266 236 205 175 143
-
-
325 298 265 238 205 177 146
369 344 317 291 258 231 200
368 355 348 336 311 280 253
320 290 260 230 199 169 138
356 341 312 283 253 223 193
356 345 335 324 304 275 245
9000
284 254 220 186 152
-
-
281 248 214 180 146
-
-
341 313 283 246 213 179 147
379 369 334 307 275 241 208
379 371 358 348 326 297 265
339 308 275 241 207 173 139
368 357 331 300 267 234 200
367 357 346 335 321 290 258
10000
11000
12000
13000
14000
15000
303 266 229 192 154
-
-
297 260 223 186 148
-
-
363 329 294 261 224 183 145
391 381 346 321 286 251 215
391 377 366 356 348 312 276
358 324 289 253 216 178 140
378 367 348 315 280 244 207
378 366 355 344 333 304 269
317 277 238 197 156
-
-
311 273 232 192 150
-
-
388 344 308 267 229 191 146
399 388 377 338 298 260 221
402 388 376 365 351 329 286
377 339 302 263 223 183 141
387 375 364 329 291 253 214
387 375 363 352 340 317 280
329 287 245 203 161
-
-
324 283 241 197 153
-
-
398 361 324 277 236 192 147
410 398 383 350 306 268 227
409 397 386 374 360 328 299
392 354 314 272 231 187 142
395 383 371 342 302 261 220
395 383 371 359 347 329 291
338 297 252 209 160
-
-
337 293 249 203 155
-
-
419 372 333 289 242 200 148
416 404 389 366 323 276 235
418 403 391 380 368 354 308
403 368 326 281 237 192 143
402 390 377 355 314 269 226
402 389 377 365 353 341 300
356 306 259 213 163
-
-
350 302 256 209 157
-
-
425 398 344 295 248 201 153
421 412 397 370 333 283 240
424 409 399 385 373 361 317
409 383 337 290 243 196 145
408 396 383 366 324 277 231
408 395 383 370 358 346 310
32
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 32: COOLING PERFORMANCE 30 TON STANDARD CAPACITY COIL (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON EVAPORATOR COIL
95°F
105°F
2
2
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
TOTAL
CAP.
(MBH)
TOTAL
TOTAL
TOTAL
INPUT
(KW)
WB
1
1
CFM
(°F)
INPUT
(KW)
CAP.
(MBH)
86 83 80 77 74 71 68
86 83 80 77 74 71 68
72
67
62
57
72
355
328
303
296
366
339
316
314
375
348
330
330
381
356
343
343
387
362
355
354
391
367
364
364
394
372
373
372
397
381
380
380
401
387
387
386
404
393
393
392
34.0
33.3
32.7
32.2
34.3
33.6
33.0
32.6
34.5
33.8
33.2
32.9
34.6
34.0
33.4
33.2
34.8
34.1
33.5
33.6
34.9
34.2
33.7
33.8
35.0
34.3
34.0
34.0
35.0
34.4
34.2
34.2
35.1
34.5
34.3
34.3
35.2
34.6
34.5
34.5
211 191 171 151 130
-
-
340
314
291
286
350
324
303
303
357
333
318
317
364
340
330
329
369
345
340
340
373
351
349
349
376
358
357
357
379
365
365
364
382
371
371
370
385
377
376
376
38.0
37.2
36.5
36.0
38.2
37.4
36.8
36.4
38.5
37.7
37.0
36.9
38.7
37.8
37.2
37.1
38.9
37.9
37.4
37.3
39.0
38.1
37.7
37.6
39.1
38.2
37.8
37.8
39.2
38.3
38.0
38.0
39.2
38.4
38.1
38.1
39.3
38.4
38.3
38.3
205 185 165 145 124
-
-
248 228 208 188 168 147 126
283 263 243 223 203 183 163
296 288 277 257 237 217 197
241 222 202 182 161 141 120
277 257 236 217 197 177 157
286 277 269 251 231 211 191
6000
228 204 181 157 133
-
-
222 198 175 151 127
-
-
67
270 247 223 200 176 153 128
312 288 264 241 218 195 171
314 305 296 282 258 235 211
263 240 217 194 170 146 122
303 282 258 235 212 188 165
303 294 285 275 252 228 205
7000
62
57
72
244 217 190 163 135
-
-
238 211 184 157 129
-
-
67
292 265 239 212 185 158 130
330 312 286 259 232 206 179
330 320 310 301 279 252 225
286 259 232 205 178 151 123
318 306 279 252 226 199 172
317 308 298 289 272 245 218
8000
62
57
72
260 230 199 168 137
-
-
254 223 193 162 131
-
-
67
314 283 254 223 193 162 131
343 333 306 276 247 216 186
343 333 322 312 297 269 238
307 277 247 217 187 156 125
330 320 299 270 240 210 179
329 319 309 300 290 262 232
9000
62
57
72
276 242 208 174 140
-
-
269 236 202 168 134
-
-
67
334 302 268 235 201 167 132
355 344 325 293 260 227 193
354 343 333 322 312 283 251
326 295 262 228 195 161 126
340 330 316 286 254 220 187
340 329 319 309 299 276 244
10000
62
57
72
291 254 217 180 142
-
-
285 248 211 174 136
-
-
67
352 318 283 246 209 172 134
364 353 342 308 273 237 200
364 353 342 331 319 296 262
345 311 276 240 203 165 127
349 339 328 300 265 230 194
349 338 327 317 306 288 255
11000
62
57
72
305 267 226 186 144
-
-
299 259 220 179 138
-
-
67
367 333 295 257 217 176 135
373 361 350 321 284 246 207
372 361 349 338 327 308 273
358 326 287 249 211 170 128
357 346 335 314 277 239 200
357 346 334 323 312 302 265
12000
62
57
72
318 277 235 191 146
-
-
311 269 227 185 140
-
-
67
381 347 306 266 225 181 136
380 368 357 334 296 254 213
380 368 356 344 333 322 283
365 340 300 259 218 174 129
365 353 341 326 288 247 206
364 352 341 329 318 307 275
13000
62
57
72
332 287 243 197 149
-
-
323 279 234 191 142
-
-
67
387 361 319 274 231 185 137
387 375 363 345 306 262 218
386 374 362 350 338 327 292
371 351 312 268 224 179 130
371 359 347 336 299 255 211
370 358 346 335 323 312 284
14000
62
57
72
67
62
57
343 296 250 203 151
-
-
335 288 241 195 145
-
-
393 372 330 284 237 190 138
393 380 368 356 316 270 223
392 380 367 355 343 331 302
377 365 323 277 230 183 132
376 364 352 340 309 262 216
376 364 351 340 328 316 293
15000
Johnson Controls Unitary Products
33
246653-YTG-E-0108
TABLE 32: COOLING PERFORMANCE 30 TON STANDARD CAPACITY COIL (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON EVAPORATOR COIL
115°F
125°F
2
2
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
TOTAL
CAP.
(MBH)
TOTAL
TOTAL
CAP.
(MBH)
TOTAL
WB
(°F)
1
1
CFM
6000
INPUT
(KW)
INPUT
(KW)
86 83 80 77 74 71 68
86 83 80 77 74 71 68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
324
299
277
275
333
309
291
291
340
317
305
305
345
323
317
316
350
329
326
326
353
335
334
334
357
343
342
341
361
349
348
348
364
354
354
353
366
359
359
359
42.5
41.7
40.7
40.3
42.8
41.8
41.0
40.8
42.8
42.0
41.3
41.2
43.0
42.2
41.5
41.6
43.2
42.3
41.9
41.9
43.5
42.5
42.2
42.0
43.6
42.6
42.2
42.2
43.7
42.9
42.4
42.4
43.8
43.0
42.6
42.6
43.8
43.1
42.7
42.7
199 179 159 138 118
-
-
307
283
261
263
315
294
280
278
324
300
291
294
324
305
304
304
330
314
313
312
331
319
319
319
337
327
328
324
343
333
329
332
347
336
336
335
347
339
342
341
47.5
46.8
45.3
45.1
48.1
46.8
45.6
45.8
47.4
46.7
46.1
45.8
47.5
47.2
46.3
46.7
47.7
47.3
47.0
47.4
48.4
47.4
47.2
47.0
48.5
47.5
47.2
47.2
48.5
48.2
47.4
47.4
48.9
48.3
47.8
47.8
48.7
48.7
47.7
47.7
193 173 153 130 112
-
-
235 215 195 175 155 135 114
270 250 230 210 190 170 150
275 266 258 244 224 204 184
230 207 187 167 150 129 108
262 242 225 202 182 162 142
263 255 244 236 216 196 176
215 192 168 144 120
-
-
207 186 160 136 112
-
-
257 234 211 187 164 140 115
291 275 252 228 205 182 158
291 282 273 265 245 221 198
252 229 205 179 158 135 107
276 267 246 220 197 177 150
278 269 260 252 237 214 190
7000
8000
231 205 178 150 123
-
-
223 199 172 142 117
-
-
279 252 226 199 172 145 117
305 296 273 246 219 192 165
305 295 286 276 264 239 212
271 244 221 194 167 140 112
291 282 268 241 211 185 158
294 281 274 262 255 234 207
247 217 187 156 125
-
-
239 212 181 150 119
-
-
300 271 240 210 180 149 118
317 307 292 262 233 203 173
316 306 296 287 277 254 225
293 265 233 202 172 141 110
304 294 285 252 226 195 168
304 294 283 273 258 245 217
9000
263 230 196 162 127
-
-
258 224 190 156 119
-
-
320 289 255 222 188 154 119
326 316 306 277 245 213 180
326 315 305 295 285 267 235
316 284 247 217 180 146 111
313 302 295 266 233 206 172
312 301 291 280 270 256 224
10000
11000
12000
13000
14000
15000
278 242 205 168 130
-
-
270 236 199 162 124
-
-
335 304 269 233 196 159 120
334 324 314 291 257 223 186
334 323 313 303 292 282 247
322 297 262 225 188 154 113
319 308 300 281 249 216 176
319 308 300 289 277 278 238
292 252 214 173 132
-
-
284 246 208 168 126
-
-
343 318 281 241 204 163 122
342 331 320 304 268 231 191
341 330 319 309 298 288 256
322 309 277 233 196 155 117
328 316 305 291 257 222 180
324 313 304 296 285 266 246
305 264 221 179 134
-
-
300 262 217 173 128
-
-
349 332 291 250 210 168 122
348 337 326 315 278 239 197
348 336 325 314 304 293 267
333 323 279 239 201 163 115
329 320 312 301 266 230 186
332 320 308 299 291 280 259
317 274 228 184 136
-
-
314 272 225 176 131
-
-
354 343 302 261 215 172 123
354 342 331 320 288 247 203
353 342 330 319 308 297 276
336 337 289 253 204 164 116
336 324 315 297 273 238 194
335 326 314 302 293 282 268
329 283 234 188 139
-
-
325 281 229 182 133
-
-
359 348 313 268 221 176 124
359 347 335 324 300 255 208
359 347 335 323 312 301 283
339 321 300 257 210 169 114
342 329 317 308 289 249 199
341 329 319 304 295 286 272
1.
2.
The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat *MBh = 3.415 x kW). Refer to the
appropriate Blower Performance table for the kW of the supply air blower motor.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
34
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 33: COOLING PERFORMANCE 30 TON HIGH CAPACITY COIL
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON EVAPORATOR COIL
75°F
85°F
2
2
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
TOTAL
CAP.
(MBH)
TOTAL
TOTAL
CAP.
TOTAL
WB
1
1
CFM
(°F)
INPUT
(KW)
INPUT
(KW)
(MBH)
86 83 80 77 74 71 68
86 83 80 77 74 71 68
72
67
62
57
72
401
367
338
321
412
382
352
345
423
394
364
361
432
404
380
377
440
410
389
391
445
416
405
402
449
420
414
413
453
431
424
424
459
431
431
430
461
440
437
439
27.9
27.3
27.1
26.5
28.2
27.4
26.9
26.8
28.5
28.0
27.4
27.2
28.7
27.7
27.3
27.1
28.8
28.0
27.7
27.4
28.9
28.2
27.7
27.4
29.0
28.3
28.0
27.6
29.4
28.4
27.9
27.9
29.5
28.8
28.1
28.4
29.6
28.9
28.3
28.3
232 212 192 168 151
-
-
385
354
327
312
397
367
340
333
407
378
351
350
415
387
366
365
421
393
378
378
426
399
390
389
431
405
399
399
434
411
408
408
438
416
416
415
441
423
422
422
31.0
30.4
29.8
29.2
31.3
30.6
30.0
29.5
31.5
30.9
30.3
29.8
31.7
31.0
30.4
30.1
31.8
31.1
30.6
30.4
32.0
31.2
30.7
30.6
32.0
31.3
30.9
30.8
32.1
31.4
31.0
31.0
32.2
31.5
31.2
31.2
32.3
31.6
31.3
31.3
224 204 184 163 143
-
-
268 248 225 205 185 165 147
302 283 263 240 223 203 183
321 312 292 277 254 234 217
260 240 220 200 180 160 140
295 275 255 235 216 196 176
312 303 288 269 249 229 210
6000
245 225 198 177 153
-
-
240 217 193 170 146
-
-
67
287 267 244 220 194 173 149
327 304 285 261 238 215 189
345 333 324 298 278 252 229
282 259 236 213 189 166 142
323 300 277 254 231 208 184
333 323 314 293 271 247 224
7000
62
57
72
261 234 210 180 156
-
-
256 229 203 175 148
-
-
67
309 285 256 232 205 178 147
364 330 306 279 253 226 199
361 351 342 326 298 272 245
304 278 251 225 198 171 143
351 325 299 272 246 219 192
350 340 330 318 292 265 238
8000
62
57
72
280 250 220 186 155
-
-
272 242 212 181 150
-
-
67
334 301 271 241 213 183 152
380 355 327 297 267 237 206
377 367 356 347 319 289 258
327 296 266 236 206 176 145
366 350 320 290 260 230 200
365 354 344 333 312 282 252
9000
62
57
72
296 259 229 195 157
-
-
288 254 221 187 152
-
-
67
356 322 288 255 221 187 153
389 378 348 314 281 247 214
391 381 370 359 340 308 272
348 315 281 248 214 180 146
378 367 341 307 274 240 207
378 367 356 345 332 299 265
10000
62
57
72
312 275 238 197 162
-
-
304 267 230 192 155
-
-
67
378 340 303 266 229 192 153
405 390 364 331 295 258 221
402 390 379 365 357 323 285
370 333 296 259 222 185 147
390 378 362 325 288 251 214
389 377 366 354 343 315 278
11000
62
57
72
325 284 247 206 164
-
-
319 279 239 198 157
-
-
67
393 358 318 275 237 193 155
414 402 391 350 311 268 227
413 401 390 375 364 332 297
392 351 311 270 230 189 148
399 387 376 342 302 261 221
399 387 375 363 351 329 291
12000
62
57
72
340 296 256 211 166
-
-
335 291 248 204 159
-
-
67
425 372 333 289 245 201 158
424 412 397 368 322 281 234
424 409 397 385 370 350 314
409 369 326 282 238 194 149
408 396 383 357 315 272 228
408 395 383 371 358 343 304
13000
62
57
72
356 312 265 214 168
-
-
351 304 257 209 161
-
-
67
431 393 347 300 253 205 159
431 419 404 377 340 291 244
430 415 406 391 379 367 326
416 386 340 293 246 198 150
416 403 390 372 329 282 235
415 402 390 377 365 353 315
14000
62
57
72
67
62
57
372 321 273 223 171
-
-
367 316 266 215 163
-
-
440 404 360 312 260 209 155
437 424 415 403 348 302 248
439 424 412 396 387 372 339
423 400 354 304 254 203 150
422 409 397 385 340 292 241
422 409 396 383 371 358 326
15000
Johnson Controls Unitary Products
35
246653-YTG-E-0108
TABLE 33: COOLING PERFORMANCE 30 TON HIGH CAPACITY COIL (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON EVAPORATOR COIL
95°F
105°F
2
2
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
TOTAL
CAP.
(MBH)
TOTAL
INPUT
(KW)
TOTAL
CAP.
(MBH)
TOTAL
WB
(°F)
1
1
CFM
6000
INPUT
(KW)
86 83 80 77 74 71 68
86 83 80 77 74 71 68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
369
340
314
302
381
352
326
321
390
362
338
338
397
370
352
352
402
376
365
364
407
382
375
375
412
388
384
384
415
393
392
392
418
400
400
399
421
406
406
405
34.5
33.8
33.0
32.4
34.8
34.1
33.4
32.8
35.0
34.3
33.6
33.1
35.2
34.5
33.8
33.5
35.3
34.6
34.0
33.8
35.5
34.7
34.1
34.1
35.5
34.8
34.3
34.3
35.6
34.9
34.5
34.5
35.7
34.9
34.7
34.6
35.8
35.0
34.8
34.8
217 197 177 157 136
-
-
353
325
299
291
364
337
310
309
372
346
325
325
378
353
338
338
383
359
350
349
388
365
360
360
392
369
369
368
396
377
376
376
399
383
383
382
401
389
389
388
38.4
37.5
36.7
36.1
38.7
37.9
37.1
36.7
39.0
38.2
37.3
37.1
39.2
38.2
37.5
37.3
39.3
38.5
37.9
37.6
39.4
38.7
37.9
37.9
39.5
38.8
38.2
38.1
39.9
38.9
38.4
38.4
40.0
39.0
38.6
38.6
40.1
39.1
38.8
38.8
211 191 171 150 130
-
-
253 233 214 194 174 154 133
288 268 248 229 209 189 169
302 293 282 262 243 223 203
247 227 207 187 167 147 126
281 262 242 222 202 182 162
291 282 274 256 236 216 196
234 210 187 163 139
-
-
227 204 180 156 132
-
-
276 252 229 206 183 159 135
317 294 270 247 224 201 178
321 312 303 287 264 241 218
269 246 223 199 176 152 128
309 286 264 240 217 194 171
309 300 291 280 257 234 211
7000
8000
250 223 196 169 141
-
-
243 216 189 162 135
-
-
298 271 245 218 191 164 137
338 319 292 265 239 212 185
338 328 318 308 285 258 231
291 264 238 211 184 157 129
325 312 285 258 232 205 178
325 315 306 296 277 251 224
265 235 205 175 144
-
-
259 229 199 168 137
-
-
320 290 260 230 199 169 138
352 341 313 283 253 223 193
352 341 331 320 305 275 245
313 283 253 223 192 162 131
338 328 306 276 246 216 185
338 328 317 308 298 268 237
9000
281 248 214 180 146
-
-
275 241 208 174 139
-
-
341 308 274 241 207 173 139
365 354 334 300 267 233 200
364 353 342 331 321 291 258
335 301 267 234 200 166 132
350 339 327 293 260 226 193
349 339 328 317 307 284 251
10000
11000
12000
13000
14000
15000
297 260 223 186 148
-
-
291 254 217 179 141
-
-
363 326 289 252 215 178 140
375 364 353 318 281 244 207
375 363 352 341 329 307 271
357 319 282 245 208 171 132
360 348 337 310 274 237 200
360 348 337 326 315 299 264
313 273 232 191 150
-
-
307 266 226 185 143
-
-
384 344 304 264 223 183 141
384 372 361 334 294 254 214
384 372 360 349 337 322 284
369 337 297 257 216 175 134
369 357 346 326 287 247 206
368 356 345 333 322 311 276
329 285 241 197 152
-
-
322 278 235 190 145
-
-
393 363 319 275 231 187 141
392 380 368 348 308 264 221
392 380 368 356 344 332 295
377 354 312 268 224 180 134
376 364 352 341 301 257 213
376 364 352 340 328 317 287
345 297 250 203 154
-
-
338 291 244 196 147
-
-
400 378 333 286 239 191 142
400 387 375 362 320 274 227
399 387 374 362 350 338 306
383 369 326 279 232 184 135
383 371 359 347 313 267 220
382 370 358 346 334 322 299
361 310 259 208 156
-
-
354 303 252 202 150
-
-
406 391 347 297 247 196 144
406 393 380 368 332 284 234
405 393 380 368 355 343 316
389 377 339 291 239 188 137
389 376 364 352 324 278 227
388 376 364 351 339 327 309
36
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 33: COOLING PERFORMANCE 30 TON HIGH CAPACITY COIL (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON EVAPORATOR COIL
115°F
125°F
2
2
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
TOTAL
CAP.
(MBH)
TOTAL
INPUT
(KW)
TOTAL
CAP.
(MBH)
TOTAL
WB
(°F)
1
1
CFM
6000
INPUT
(KW)
86 83 80 77 74 71 68
86 83 80 77 74 71 68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
336
310
286
280
346
321
297
297
354
329
312
312
359
335
324
324
364
341
335
334
369
345
344
344
372
353
352
352
375
360
359
359
378
366
366
365
381
371
371
371
42.9
41.9
41.2
40.3
43.3
42.4
41.5
41.0
43.5
42.6
41.8
41.4
43.7
42.8
42.0
41.8
43.9
43.0
42.4
42.2
44.0
43.1
42.5
42.3
44.1
43.3
42.5
42.5
44.2
43.4
42.8
42.7
44.3
43.5
43.1
43.1
44.3
43.4
43.3
43.3
204 184 164 144 123
-
-
318
295
275
269
327
304
287
285
336
311
299
299
340
316
310
310
345
322
320
319
350
322
327
327
352
340
333
336
352
342
341
341
355
349
349
348
361
352
352
354
48.0
47.0
46.5
45.0
48.6
47.6
46.6
45.7
48.5
47.5
47.1
46.0
48.7
48.3
47.3
47.0
49.1
48.1
47.5
47.6
49.3
47.9
47.9
47.3
49.3
48.3
47.2
47.5
48.5
48.4
47.7
47.4
48.6
48.4
48.2
48.1
48.4
47.9
48.3
48.3
196 176 156 139 115
-
-
240 220 200 180 160 140 119
274 255 235 215 195 175 155
280 271 263 248 229 209 189
232 212 193 173 153 133 112
267 247 227 208 188 168 148
269 260 249 238 222 202 182
220 197 173 150 126
-
-
213 189 166 145 121
-
-
262 239 216 192 169 145 121
297 280 257 233 210 187 163
297 288 279 270 250 227 203
255 231 208 185 162 138 114
281 276 249 226 203 180 154
285 276 267 257 243 220 194
7000
8000
236 210 183 155 128
-
-
229 205 178 148 120
-
-
284 258 231 204 177 150 122
312 303 277 251 224 198 171
312 302 293 283 270 244 217
277 253 224 197 170 143 116
299 292 268 244 215 191 164
299 289 279 269 264 237 210
252 222 192 161 130
-
-
244 214 184 154 123
-
-
306 276 246 216 185 155 123
324 314 299 269 238 208 178
324 314 304 294 284 260 230
299 269 239 209 178 148 114
310 299 292 262 229 199 172
310 299 292 278 263 251 224
9000
268 235 201 167 132
-
-
260 230 193 159 125
-
-
328 294 260 227 193 159 124
335 324 314 286 252 219 185
334 324 314 303 293 277 243
320 287 253 220 186 152 115
320 309 295 279 243 212 176
319 308 300 289 279 270 234
10000
11000
12000
13000
14000
15000
284 247 210 172 134
-
-
276 239 202 165 127
-
-
345 312 275 238 201 164 125
344 333 322 303 266 229 192
344 333 322 311 301 291 256
327 305 268 231 194 157 119
327 319 308 297 257 220 183
327 318 307 296 287 283 247
300 259 219 178 136
-
-
292 252 211 170 129
-
-
353 331 290 250 209 168 126
352 341 329 318 280 239 199
352 340 329 318 307 296 267
336 326 283 243 202 162 117
333 324 310 310 273 230 193
336 324 312 304 292 277 257
316 272 228 184 139
-
-
311 267 220 179 134
-
-
360 347 305 261 217 173 128
359 347 336 325 293 250 206
359 347 335 324 313 302 280
342 342 298 254 210 166 123
341 329 320 300 284 243 200
341 329 317 308 299 287 274
332 284 237 189 141
-
-
327 276 229 182 136
-
-
366 354 319 272 225 177 120
366 354 342 330 305 260 213
365 353 341 330 318 307 290
349 333 312 265 218 170 97
349 336 324 311 296 253 206
348 336 323 314 302 293 279
347 297 246 195 139
-
-
340 292 241 187 123
-
-
371 359 332 283 233 182 128
371 359 347 335 315 270 219
371 358 346 334 323 311 298
352 337 326 273 229 178 117
352 342 329 317 305 260 210
354 339 326 317 307 295 283
1.
2.
The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat *MBh = 3.415 x kW). Refer to the
appropriate Blower Performance table for the kW of the supply air blower motor.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
37
246653-YTG-E-0108
TABLE 34: COOLING PERFORMANCE 40 TON STANDARD CAPACITY COIL
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON EVAPORATOR COIL
75°F
85°F
2
2
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
TOTAL
CAP.
(MBH)
TOTAL
INPUT
(KW)
TOTAL
CAP.
(MBH)
TOTAL
WB
(°F)
1
1
CFM
8000
INPUT
(KW)
86 83 80 77 74 71 68
86 83 80 77 74 71 68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
530
488
454
430
544
505
466
452
556
515
471
468
566
526
488
490
572
535
506
503
580
544
518
517
585
544
528
530
589
552
540
539
593
555
551
550
599
559
559
558
602
569
568
565
608
575
575
574
608
581
583
580
39.3
37.7
37.5
36.6
39.0
37.7
37.8
37.1
39.3
38.3
38.1
37.1
39.5
39.1
38.3
38.1
39.7
39.5
38.6
38.3
39.6
39.4
39.0
38.3
40.0
39.5
38.1
38.3
40.1
39.6
38.5
38.5
40.2
39.8
38.7
38.5
40.0
39.9
38.7
38.7
40.1
39.7
38.9
39.2
40.2
39.8
39.1
39.1
40.6
40.1
39.5
39.4
303 280 253 226 195
-
-
509
469
435
416
522
484
447
437
533
494
455
453
542
504
471
472
548
512
487
485
555
520
499
498
560
522
509
510
564
529
520
519
568
533
530
529
573
538
538
537
576
547
546
544
581
553
553
552
582
559
560
558
43.3
42.2
41.4
40.6
43.5
42.5
41.7
41.1
43.7
42.8
42.0
41.4
43.9
43.0
42.2
41.8
44.1
43.2
42.4
42.1
44.2
43.3
42.6
42.4
44.4
43.4
42.6
42.6
44.5
43.5
42.8
42.8
44.6
43.7
43.0
43.0
44.6
43.7
43.2
43.2
44.7
43.8
43.4
43.4
44.8
43.9
43.5
43.5
44.9
44.0
43.7
43.7
296 270 243 216 188
-
-
352 325 302 272 245 218 194
397 375 345 319 295 266 239
430 416 389 364 337 311 287
344 318 292 265 238 211 184
391 365 338 312 286 259 232
416 404 383 357 330 304 278
323 293 259 232 198
-
-
313 283 252 222 191
-
-
377 344 317 287 254 226 195
427 397 367 340 310 280 250
452 437 424 394 361 331 302
367 337 308 278 247 217 186
419 390 360 331 301 271 241
437 424 412 382 352 322 293
9000
339 302 272 238 200
-
-
329 295 262 228 193
-
-
396 366 332 299 265 231 197
450 421 391 358 325 288 258
474 455 443 412 382 349 315
389 356 323 290 256 222 188
448 415 382 349 316 282 249
455 441 428 406 373 340 307
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
355 318 281 244 206
-
-
345 308 271 234 196
-
-
418 384 347 308 271 236 195
488 446 412 376 339 302 265
484 475 459 446 408 366 329
411 375 338 301 264 227 189
471 439 403 367 330 293 257
470 457 443 430 394 357 320
371 330 287 246 205
-
-
361 321 280 239 198
-
-
440 402 362 322 282 241 200
500 469 432 393 353 313 273
500 486 473 460 423 382 345
433 393 353 313 273 232 191
485 462 424 384 344 304 264
484 470 456 442 413 374 334
383 340 296 252 207
-
-
376 333 289 245 200
-
-
464 418 377 334 290 246 201
515 498 448 410 367 323 280
514 497 483 469 438 398 355
455 411 368 325 281 237 192
498 482 443 402 358 315 271
497 482 468 453 429 390 347
399 352 305 261 209
-
-
392 345 298 251 202
-
-
485 437 392 345 298 250 202
528 510 476 426 381 334 287
524 510 495 481 452 414 371
473 430 383 336 289 241 193
509 494 461 418 372 325 278
508 493 478 463 444 405 360
415 368 314 263 215
-
-
408 358 307 256 205
-
-
505 452 402 356 306 255 203
537 522 487 443 391 343 294
539 521 506 489 474 433 381
492 446 397 347 297 246 194
519 504 477 433 385 336 285
519 503 488 472 457 419 372
433 377 323 269 214
-
-
424 370 316 262 207
-
-
522 471 419 368 314 256 204
548 533 500 462 402 353 301
547 529 514 499 481 441 395
510 462 411 359 305 250 195
529 513 492 447 397 346 292
528 512 496 481 465 431 383
442 391 332 278 216
-
-
437 383 325 268 209
-
-
526 482 430 375 321 264 205
556 540 524 476 418 365 306
555 539 524 505 490 455 402
527 476 424 369 313 255 196
537 521 505 461 409 355 299
536 520 504 488 472 443 393
464 398 341 280 218
-
-
451 393 334 273 211
-
-
548 504 444 385 334 268 206
565 546 530 486 429 373 311
565 546 530 514 499 454 412
540 491 436 378 321 260 197
545 528 512 473 420 363 306
544 527 511 495 479 454 403
471 408 354 289 223
-
-
464 403 343 279 214
-
-
572 517 459 394 337 273 210
572 556 536 491 437 378 319
571 555 539 520 504 486 420
552 505 448 388 328 264 199
552 535 518 484 430 371 312
551 534 518 501 485 468 413
486 421 364 292 226
-
-
476 413 351 284 216
-
-
581 527 464 402 349 274 208
577 561 545 505 449 386 324
580 560 541 528 509 490 434
559 518 458 396 334 268 200
558 541 524 500 441 379 317
558 540 523 507 490 473 423
38
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 34: COOLING PERFORMANCE 40 TON STANDARD CAPACITY COIL (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON EVAPORATOR COIL
95°F
105°F
2
2
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
TOTAL
CAP.
(MBH)
TOTAL
TOTAL
TOTAL
INPUT
(KW)
WB
1
1
CFM
(°F)
INPUT
(KW)
CAP.
(MBH)
86 83 80 77 74 71 68
86 83 80 77 74 71 68
72
67
62
57
72
488
450
416
402
500
463
428
422
510
473
439
438
518
482
454
454
524
489
468
467
530
496
480
479
535
500
490
490
539
506
500
499
543
511
509
508
547
517
517
516
550
525
524
523
554
531
531
530
556
537
537
536
48.1
47.1
46.0
45.2
48.5
47.5
46.3
45.7
48.7
47.7
46.6
46.2
48.9
47.7
46.8
46.4
49.1
47.9
47.0
46.7
49.3
48.1
47.2
47.1
49.4
48.2
47.5
47.4
49.5
48.3
47.7
47.6
49.6
48.4
47.9
47.9
49.7
48.5
48.1
48.1
49.8
48.7
48.3
48.2
49.9
48.8
48.4
48.4
49.9
48.8
48.6
48.6
288 261 234 207 180
-
-
467
431
397
388
478
442
409
407
487
452
423
423
494
460
437
436
500
466
449
449
505
472
461
460
510
478
471
470
514
483
480
479
518
489
488
487
521
496
496
495
524
503
502
502
527
509
509
508
530
515
514
514
53.7
52.4
51.3
50.4
54.0
52.7
51.6
50.9
54.3
53.0
51.9
51.5
54.5
53.2
52.1
51.9
54.7
53.6
52.4
52.1
54.9
53.8
52.8
52.4
55.0
53.9
52.8
52.7
55.1
54.0
53.2
52.9
55.2
53.9
53.4
53.2
55.3
54.3
53.4
53.4
55.4
54.4
53.6
53.6
55.5
54.5
53.8
53.8
55.6
54.5
54.2
54.1
279 253 226 199 171
-
-
336 310 283 257 230 203 175
383 356 330 304 277 251 224
402 391 375 349 322 296 269
328 301 275 248 221 194 167
373 348 321 295 268 242 215
388 377 365 340 313 287 260
8000
304 274 244 213 183
-
-
296 266 235 205 174
-
-
67
358 329 299 269 239 208 177
411 382 352 322 292 262 232
422 410 398 372 343 313 284
350 320 290 260 230 199 168
403 373 343 313 283 253 223
407 395 382 364 334 304 275
9000
62
57
72
320 287 253 219 185
-
-
312 278 245 211 176
-
-
67
381 347 314 281 247 213 179
439 407 373 340 307 274 240
438 426 413 397 364 331 298
372 339 305 272 238 204 170
423 397 364 331 298 264 231
423 410 398 385 355 322 288
10000
62
57
72
336 299 262 225 187
-
-
328 291 254 217 179
-
-
67
403 366 329 293 256 218 181
454 431 394 358 321 284 248
454 440 427 414 383 348 311
394 357 320 284 247 209 171
437 422 385 349 312 275 238
436 424 411 398 375 339 302
11000
62
57
72
352 312 272 231 190
-
-
344 303 263 222 181
-
-
67
425 384 344 304 264 223 182
468 451 415 375 335 295 255
467 453 439 425 403 365 324
416 375 335 295 255 214 173
449 436 405 366 326 286 246
449 435 422 409 393 355 315
12000
62
57
72
368 325 281 237 192
-
-
359 316 272 228 183
-
-
67
446 403 359 316 272 228 183
480 465 434 393 349 306 262
479 465 451 436 418 381 338
437 394 350 307 263 219 174
461 447 421 383 340 296 253
460 446 432 418 405 371 328
13000
62
57
72
384 337 290 242 194
-
-
375 328 281 234 185
-
-
67
463 421 374 327 280 232 184
490 476 449 409 363 316 269
490 475 460 445 431 395 350
455 410 365 318 271 223 175
471 456 440 399 354 307 260
470 456 441 427 413 384 341
14000
62
57
72
400 349 299 248 196
-
-
391 341 290 239 188
-
-
67
481 437 389 338 288 237 185
500 485 465 423 376 327 276
499 484 469 454 439 407 362
472 425 378 329 279 228 176
480 465 451 413 364 316 267
479 464 449 435 420 397 351
15000
62
57
72
415 362 308 254 199
-
-
406 353 299 245 190
-
-
67
499 452 402 350 296 242 186
509 493 478 435 388 337 283
508 493 477 462 447 420 372
489 441 392 341 287 232 177
488 473 458 426 375 326 274
487 472 457 442 427 408 362
16000
62
57
72
429 374 317 259 201
-
-
418 364 308 251 192
-
-
67
517 467 415 360 304 246 187
517 501 485 448 399 345 290
516 500 484 469 453 431 383
496 455 403 348 294 237 178
496 480 464 437 388 335 279
495 479 464 448 433 419 372
17000
62
57
72
440 385 326 265 203
-
-
431 374 317 256 194
-
-
67
525 479 426 369 310 251 188
524 508 492 461 410 353 297
523 507 491 475 459 444 393
503 468 414 358 301 241 179
502 486 470 450 399 343 284
502 486 470 454 439 424 382
18000
62
57
72
455 395 333 270 205
-
-
444 384 324 262 196
-
-
67
531 494 437 379 318 255 189
531 514 498 474 421 362 302
530 513 497 481 465 449 403
509 484 426 367 307 246 180
509 493 476 461 410 351 289
508 492 476 460 444 429 390
19000
62
57
72
67
62
57
466 404 340 276 207
-
-
456 394 331 268 199
-
-
537 507 449 387 322 260 191
537 520 503 487 431 370 307
536 519 503 486 470 454 411
515 494 437 375 313 250 181
514 498 482 466 419 359 294
514 497 481 465 449 433 398
20000
Johnson Controls Unitary Products
39
246653-YTG-E-0108
TABLE 34: COOLING PERFORMANCE 40 TON STANDARD CAPACITY COIL (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON EVAPORATOR COIL
115°F
125°F
2
2
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
TOTAL
CAP.
(MBH)
TOTAL
TOTAL
CAP.
(MBH)
TOTAL
WB
(°F)
1
1
CFM
8000
INPUT
(KW)
INPUT
(KW)
86 83 80 77 74 71 68
86 83 80 77 74 71 68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
446
411
379
373
456
421
391
391
464
430
406
406
470
437
419
419
475
443
431
431
481
449
441
441
485
455
450
450
489
460
459
458
492
467
466
466
495
475
473
473
498
481
480
479
501
486
485
485
503
491
491
490
60.0
58.5
57.5
56.5
60.3
59.1
57.7
57.1
60.3
59.4
57.9
57.6
60.6
59.3
58.4
58.1
61.1
59.5
58.4
58.5
61.2
60.0
58.6
58.8
61.4
59.9
59.2
59.1
61.5
60.3
59.4
59.1
61.6
60.4
59.7
59.4
61.7
60.3
59.6
59.6
61.8
60.7
59.9
59.8
61.9
60.8
60.1
60.0
62.0
60.6
60.2
60.2
271 244 217 190 163
-
-
425
392
360
359
434
400
372
376
441
409
390
391
446
415
402
401
451
420
412
413
456
425
422
422
460
433
431
430
464
437
439
438
467
445
445
445
469
454
452
452
472
459
458
458
474
464
463
463
477
469
468
468
65.6
63.8
62.8
61.7
65.8
64.3
63.0
62.3
65.9
64.7
63.2
62.9
66.2
64.8
63.7
63.6
66.7
65.2
63.8
63.9
66.8
65.7
64.2
64.1
67.0
65.6
64.5
64.4
67.1
66.0
64.9
64.4
67.2
65.9
65.2
64.7
67.3
66.1
64.9
64.9
67.4
66.4
65.2
65.2
67.5
66.5
65.5
65.4
67.7
66.3
65.8
65.7
262 236 209 182 154
-
-
319 292 266 239 212 185 158
365 339 312 286 259 233 206
373 362 351 330 304 278 251
311 283 258 230 203 176 150
355 331 303 277 250 224 197
359 348 341 321 295 269 242
287 257 227 196 165
-
-
279 249 218 188 156
-
-
341 311 281 251 221 190 159
391 363 334 304 274 244 214
391 379 367 355 325 295 265
333 302 272 242 212 181 150
383 354 325 295 265 235 205
376 364 351 347 316 286 256
9000
303 270 236 202 168
-
-
295 261 228 194 159
-
-
363 330 296 263 229 195 161
406 388 355 321 288 255 222
406 393 381 369 345 312 279
354 322 287 254 220 186 152
390 378 346 312 279 245 213
391 377 366 357 336 303 269
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
319 282 245 208 170
-
-
311 274 237 200 162
-
-
385 348 311 275 238 200 162
419 407 376 339 303 266 229
419 406 393 381 365 329 292
376 339 302 266 229 191 152
402 398 367 330 294 257 219
401 390 377 365 357 320 283
335 295 254 214 172
-
-
327 286 245 205 163
-
-
406 366 326 286 246 205 163
431 418 395 357 316 276 236
431 417 404 391 378 344 305
397 357 317 277 237 196 154
412 403 385 348 307 267 227
413 399 387 375 368 334 296
351 307 263 219 174
-
-
342 298 254 210 165
-
-
427 385 341 297 254 209 165
441 427 414 372 330 287 243
441 427 414 400 387 358 318
418 376 332 288 245 200 156
422 409 401 362 321 277 234
422 408 395 382 374 348 308
367 320 272 225 177
-
-
358 311 263 217 168
-
-
445 402 356 309 262 214 166
450 436 423 386 344 297 250
450 436 422 408 395 372 330
437 391 347 300 253 205 157
431 416 414 376 335 288 241
430 417 403 390 377 361 321
383 332 282 231 179
-
-
374 324 273 222 171
-
-
460 416 369 320 270 219 167
459 444 431 400 356 308 257
458 444 429 416 402 384 341
451 404 358 311 261 210 158
439 424 417 390 344 297 248
438 424 409 397 383 374 330
397 345 291 236 181
-
-
388 336 282 227 172
-
-
467 432 381 330 278 223 167
466 452 437 414 367 316 264
466 451 436 422 408 394 351
457 421 371 321 269 213 158
445 432 417 405 354 305 255
445 430 416 402 388 382 341
410 355 300 242 183
-
-
399 345 291 234 174
-
-
475 444 394 339 285 228 168
473 458 443 429 378 323 271
473 458 443 428 414 399 361
454 432 382 327 275 219 159
452 437 422 418 367 313 260
452 437 423 407 394 387 350
422 367 307 248 186
-
-
413 356 298 239 177
-
-
481 460 404 348 291 232 169
480 464 449 434 389 331 276
479 464 448 433 419 404 371
459 449 392 337 282 222 160
458 442 427 423 378 321 263
458 443 427 412 399 384 360
434 375 314 253 188
-
-
423 364 305 245 179
-
-
486 471 416 357 297 237 169
485 470 454 439 398 339 281
485 469 454 438 423 408 378
464 461 405 345 286 228 160
463 449 432 426 387 328 268
463 448 433 417 402 388 365
447 385 321 259 190
-
-
437 375 312 251 182
-
-
491 475 429 366 303 241 171
491 475 459 444 407 347 286
490 474 458 443 427 412 386
469 462 417 354 294 231 161
468 453 438 423 395 336 273
468 452 436 422 406 391 373
1.
2.
The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat *MBh = 3.415 x kW). Refer to the
appropriate Blower Performance table for the kW of the supply air blower motor.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
40
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 35: COOLING PERFORMANCE 40 TON HIGH CAPACITY COIL
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON EVAPORATOR COIL
75°F
85°F
2
2
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
TOTAL
CAP.
(MBH)
TOTAL
TOTAL
CAP.
TOTAL
WB
1
1
CFM
(°F)
INPUT
(KW)
INPUT
(KW)
(MBH)
86 83 80 77 74 71 68
86 83 80 77 74 71 68
72
67
62
57
72
535
492
459
432
553
510
475
457
564
520
483
480
572
528
493
492
578
539
511
508
590
543
523
526
592
559
537
536
599
561
549
546
600
571
558
557
607
570
569
569
611
577
576
576
614
587
583
585
617
593
592
594
39.0
38.2
37.7
36.7
39.1
38.9
38.1
37.2
40.2
38.8
38.4
37.3
40.2
39.4
38.3
38.4
40.7
39.3
38.6
38.6
40.8
39.5
38.9
38.3
41.0
39.6
39.0
38.6
40.8
39.8
39.1
38.9
40.9
39.6
38.7
38.8
41.0
40.0
39.1
39.0
41.1
40.3
39.3
39.2
41.2
40.4
39.4
39.1
41.3
40.8
39.9
39.8
310 280 253 226 199
-
-
517
476
440
421
531
490
454
443
542
501
465
462
551
511
478
478
558
520
494
493
565
527
507
507
570
534
519
519
575
539
530
529
579
545
540
539
584
550
549
548
588
557
557
556
591
565
564
564
594
572
571
571
43.4
42.4
41.6
40.8
43.7
42.8
41.9
41.2
44.0
43.0
42.2
41.6
44.2
43.3
42.4
42.0
44.4
43.4
42.6
42.3
44.6
43.6
42.7
42.6
44.7
43.7
42.9
42.9
44.8
43.8
43.0
43.1
44.9
43.9
43.2
43.3
45.0
44.1
43.5
43.5
45.1
44.2
43.7
43.7
45.1
44.3
43.9
43.8
45.2
44.4
44.0
44.0
300 273 246 219 192
-
-
357 331 302 278 251 224 197
404 378 351 325 298 272 245
432 421 393 370 343 317 290
348 322 295 269 242 215 188
395 368 342 316 289 263 236
421 409 386 360 334 308 281
8000
323 293 263 235 204
-
-
316 286 256 226 195
-
-
67
380 350 317 288 260 230 199
435 403 373 343 313 284 253
457 442 427 400 362 335 305
371 341 311 281 251 221 190
424 394 364 334 305 275 245
443 430 416 386 355 326 296
9000
62
57
72
342 306 275 241 204
-
-
333 299 266 232 197
-
-
67
402 369 336 302 269 235 201
453 427 395 361 331 295 261
480 464 449 415 385 352 319
393 360 327 294 260 226 192
452 419 386 353 320 286 253
462 448 435 409 377 343 310
10000
62
57
72
358 321 284 247 209
-
-
349 312 275 238 200
-
-
67
421 384 351 314 280 240 202
493 452 416 382 342 309 272
492 481 469 444 408 369 332
415 378 342 305 269 231 193
478 443 407 371 334 298 261
478 464 451 434 398 361 324
11000
62
57
72
374 334 294 250 211
-
-
365 325 284 243 202
-
-
67
446 406 366 326 285 245 206
511 468 436 397 356 317 276
508 494 483 464 426 389 349
437 397 357 317 277 236 195
494 468 428 388 348 308 268
493 479 465 450 417 378 338
12000
62
57
72
387 346 300 258 211
-
-
380 337 293 249 204
-
-
67
467 421 381 337 294 249 204
523 509 456 414 370 327 283
526 508 494 480 440 405 362
459 415 372 329 285 241 196
507 492 449 406 362 319 275
507 492 477 462 437 395 351
13000
62
57
72
406 356 309 264 216
-
-
396 349 302 255 207
-
-
67
493 443 395 349 301 257 206
537 522 479 432 384 341 293
536 521 507 489 466 418 375
481 434 387 340 293 246 197
519 504 470 423 376 330 283
519 503 488 473 455 411 364
14000
62
57
72
422 371 318 267 218
-
-
412 362 311 260 209
-
-
67
516 461 413 360 309 259 207
549 531 490 451 398 348 300
546 534 516 498 486 438 385
502 452 402 351 301 250 198
530 514 488 441 390 340 290
529 514 498 482 467 427 377
15000
62
57
72
437 381 327 275 220
-
-
428 374 320 266 211
-
-
67
529 477 425 371 317 266 208
558 542 519 464 412 358 307
557 542 526 508 493 450 400
521 470 416 363 309 255 199
540 524 505 457 404 350 297
539 523 507 491 475 441 390
16000
62
57
72
453 396 336 281 219
-
-
444 387 329 272 213
-
-
67
543 492 440 382 325 268 209
569 550 534 492 428 371 314
569 552 534 518 500 464 414
541 487 431 374 317 259 200
549 532 516 472 418 361 304
548 532 515 499 482 454 403
17000
62
57
72
467 408 345 284 224
-
-
459 399 338 277 215
-
-
67
577 513 454 394 333 275 210
576 560 541 504 436 382 321
576 559 543 524 508 472 420
557 503 446 385 325 264 201
557 540 523 485 430 371 311
556 539 523 506 489 466 413
18000
62
57
72
482 418 354 292 224
-
-
475 411 347 283 217
-
-
67
587 532 467 406 341 276 211
583 566 550 510 447 391 325
585 566 549 530 517 498 441
565 517 458 397 333 268 203
564 547 530 499 441 381 317
564 546 529 512 496 479 423
19000
62
57
72
67
62
57
492 432 363 295 229
-
-
488 424 356 288 220
-
-
593 534 475 413 351 284 215
592 575 556 521 468 396 332
594 575 558 539 519 503 438
572 532 470 408 341 273 204
571 554 536 513 452 389 324
571 553 536 518 501 484 433
20000
Johnson Controls Unitary Products
41
246653-YTG-E-0108
TABLE 35: COOLING PERFORMANCE 40 TON HIGH CAPACITY COIL (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON EVAPORATOR COIL
95°F
105°F
2
2
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
TOTAL
CAP.
(MBH)
TOTAL
INPUT
(KW)
TOTAL
CAP.
(MBH)
TOTAL
WB
(°F)
1
1
CFM
8000
INPUT
(KW)
86 83 80 77 74 71 68
86 83 80 77 74 71 68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
497
458
422
408
509
470
434
428
519
481
447
445
528
491
462
462
535
499
476
476
540
506
489
488
546
510
500
500
550
516
510
510
555
521
520
519
559
529
528
527
563
536
536
535
566
543
543
542
569
550
549
548
48.4
47.2
46.2
45.4
48.7
47.5
46.5
45.9
48.8
47.8
46.8
46.4
49.1
48.0
47.1
46.6
49.2
48.2
47.3
46.9
49.4
48.4
47.4
47.4
49.5
48.5
47.6
47.7
49.7
48.6
47.8
47.9
49.8
48.8
48.2
48.2
49.9
48.9
48.4
48.4
50.0
49.0
48.6
48.6
50.0
49.1
48.8
48.8
50.1
49.2
48.9
48.9
291 265 238 211 184
-
-
475
438
405
393
487
450
415
412
495
460
429
429
503
468
445
444
509
476
457
457
515
480
469
469
520
487
480
479
524
492
489
489
528
499
498
497
532
507
506
506
536
514
513
513
539
521
520
519
542
527
526
525
54.0
52.6
51.5
50.5
54.1
53.0
51.9
51.3
54.6
53.2
52.2
51.7
54.9
53.5
52.4
52.2
55.1
53.7
52.7
52.4
55.2
53.9
53.0
52.7
55.4
54.0
53.1
53.0
55.5
54.2
53.5
53.3
55.6
54.3
53.7
53.5
55.7
54.4
53.8
53.7
55.8
54.7
54.0
53.9
55.9
54.8
54.1
54.1
56.0
55.2
54.6
54.5
283 256 229 202 175
-
-
339 313 287 260 233 206 179
386 359 333 307 280 254 227
408 396 378 351 325 299 272
330 304 278 251 224 197 170
377 351 324 298 271 245 218
393 382 369 343 316 290 263
308 278 248 217 186
-
-
299 269 239 208 177
-
-
362 332 303 273 242 212 181
414 385 355 325 296 266 236
428 416 403 375 347 317 287
353 323 293 264 233 203 172
405 376 346 316 286 257 226
412 400 388 367 338 308 278
9000
324 291 257 223 189
-
-
315 282 248 214 180
-
-
384 351 318 285 251 217 183
444 410 377 344 310 277 244
445 432 420 401 368 334 301
375 342 309 275 242 208 174
429 400 368 334 301 268 234
429 416 404 391 358 325 292
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
340 303 266 229 191
-
-
331 294 257 220 182
-
-
407 370 333 296 259 222 184
462 434 398 361 325 288 251
462 447 434 421 388 352 315
397 360 324 287 250 213 175
445 425 389 352 315 279 242
444 430 418 405 378 342 305
356 316 275 235 193
-
-
347 307 267 226 184
-
-
428 388 348 308 268 227 185
476 460 419 379 339 299 259
476 462 447 434 408 368 328
419 379 339 299 258 218 176
457 444 409 370 329 290 249
457 443 429 416 399 359 319
372 328 285 240 196
-
-
363 319 276 231 187
-
-
450 407 363 320 276 232 187
489 474 440 397 353 310 266
488 474 459 444 428 385 341
440 397 354 310 267 222 177
469 455 429 387 343 300 256
469 454 440 426 413 375 332
387 341 294 246 198
-
-
379 332 285 237 189
-
-
471 425 378 331 284 236 188
500 485 460 414 367 320 273
500 484 469 455 440 402 354
463 416 368 322 274 227 179
480 465 449 405 357 311 263
479 464 450 435 421 391 345
403 353 303 252 200
-
-
395 344 294 243 191
-
-
491 443 392 342 292 241 189
510 495 478 431 381 331 280
510 494 479 464 448 416 368
483 434 383 333 282 232 180
489 474 460 421 371 321 270
489 474 459 444 429 405 358
419 366 312 257 202
-
-
410 357 303 248 193
-
-
511 461 407 354 300 245 190
520 504 488 447 395 341 287
519 503 487 472 456 430 380
499 450 398 344 290 236 181
498 482 468 434 385 331 277
497 482 466 451 436 417 370
435 378 321 263 205
-
-
426 369 312 254 195
-
-
529 478 422 365 308 250 191
528 512 496 458 408 351 294
527 511 495 479 463 442 392
507 465 413 355 298 241 182
506 490 474 450 398 341 284
506 489 474 458 443 428 381
451 390 330 269 206
-
-
443 381 321 260 197
-
-
536 492 436 376 316 254 192
536 519 503 472 421 361 301
535 518 502 486 469 453 403
514 480 424 367 306 245 183
513 497 481 465 409 352 291
513 496 480 464 448 433 390
467 403 339 274 209
-
-
458 394 330 265 200
-
-
543 505 448 387 324 259 194
543 526 509 486 432 371 308
542 525 508 492 475 459 409
521 496 437 376 314 249 184
520 503 487 471 420 361 298
519 503 486 470 454 438 399
481 415 348 280 211
-
-
471 405 339 271 202
-
-
550 524 461 399 331 263 194
549 532 515 498 439 380 315
548 531 514 497 481 464 423
527 510 448 386 321 254 185
526 509 493 476 429 369 305
525 509 492 476 459 443 408
42
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 35: COOLING PERFORMANCE 40 TON HIGH CAPACITY COIL (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON EVAPORATOR COIL
115°F
125°F
2
2
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
SENSIBLE CAPACITY (MBH)
RETURN DRY BULB (°F)
TOTAL
CAP.
(MBH)
TOTAL
INPUT
(KW)
TOTAL
CAP.
(MBH)
TOTAL
WB
(°F)
1
1
CFM
8000
INPUT
(KW)
86 83 80 77 74 71 68
86 83 80 77 74 71 68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
453
417
384
378
464
428
396
396
472
438
412
412
478
446
427
426
484
451
438
438
490
457
449
449
494
464
459
459
499
469
468
468
502
477
476
476
505
485
483
483
508
491
490
489
511
497
496
496
513
502
502
501
60.3
59.0
57.7
56.7
60.7
59.4
57.9
57.3
60.7
59.4
58.2
57.9
61.0
59.7
58.9
58.3
61.5
59.9
59.0
58.8
61.6
60.1
59.2
59.1
61.8
60.5
59.5
59.5
61.9
60.4
59.8
59.5
62.1
60.8
60.1
59.8
62.2
60.7
60.0
60.0
62.3
61.1
60.2
60.2
62.3
61.1
60.5
60.4
62.4
61.0
60.6
60.6
274 247 220 193 166
-
-
431
397
367
363
442
408
377
380
448
417
394
396
453
423
410
408
458
428
419
419
465
431
429
430
468
441
439
438
473
445
447
447
475
455
454
454
478
463
461
462
481
469
467
467
484
475
473
473
486
479
479
478
65.9
64.4
63.0
61.8
66.1
64.9
63.3
62.7
66.5
64.8
63.6
63.2
66.8
65.2
64.2
63.9
67.4
65.4
64.4
64.3
67.4
65.6
64.8
64.4
67.7
66.0
65.0
64.8
67.7
66.0
65.5
64.9
67.9
66.3
65.6
65.1
68.0
66.2
65.4
65.3
68.1
66.8
65.6
65.5
68.2
66.8
65.8
65.7
68.3
67.0
66.3
66.2
266 238 211 184 157
-
-
321 295 269 242 215 188 161
367 342 315 288 262 236 209
378 367 356 333 307 281 254
312 286 260 233 206 179 152
358 334 306 279 253 227 200
363 353 347 325 298 272 245
290 260 230 199 168
-
-
281 251 221 190 159
-
-
344 314 284 254 224 194 163
396 367 337 307 277 247 217
396 384 373 358 328 298 268
335 305 274 245 215 185 154
387 358 328 298 267 238 207
380 368 358 350 319 289 259
9000
306 273 239 205 171
-
-
297 264 230 196 162
-
-
366 333 300 266 233 199 164
412 391 358 325 292 258 225
412 400 387 375 348 316 282
357 324 291 256 224 190 155
397 381 349 315 283 249 215
396 384 371 365 338 307 273
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
322 285 248 211 173
-
-
313 276 239 202 164
-
-
388 351 315 278 241 203 166
427 413 379 342 306 269 232
426 413 400 387 369 332 296
378 341 306 269 232 194 157
410 404 370 333 296 260 223
408 396 384 371 359 322 286
338 298 258 217 175
-
-
329 289 250 208 166
-
-
409 370 329 289 249 208 167
438 425 400 360 320 280 239
438 425 411 398 385 349 309
400 361 320 280 239 199 158
419 409 390 351 310 271 229
419 406 393 380 376 340 300
354 310 267 222 178
-
-
345 301 258 213 169
-
-
431 388 344 301 257 213 168
449 436 420 377 334 290 247
449 435 421 408 394 365 322
421 378 335 291 248 203 158
429 417 409 367 324 280 237
430 415 402 390 379 355 313
370 323 276 228 180
-
-
362 314 267 219 171
-
-
453 406 359 312 265 217 169
459 445 431 394 348 301 254
459 444 431 416 402 380 335
445 397 349 303 255 208 160
439 425 420 385 338 292 244
438 424 412 396 383 369 326
386 335 285 234 182
-
-
378 326 276 225 173
-
-
469 424 374 324 273 222 169
468 453 439 408 361 311 260
468 453 438 424 410 395 348
461 415 365 315 263 213 160
447 432 421 398 351 301 250
447 433 418 404 391 384 338
402 348 294 239 184
-
-
393 339 285 230 175
-
-
477 442 389 335 281 227 170
476 461 446 425 373 321 267
476 460 445 430 416 402 359
465 431 380 325 271 218 161
454 439 426 412 363 311 257
454 439 424 409 396 389 349
418 360 303 245 186
-
-
409 351 294 236 176
-
-
485 455 404 346 289 231 171
483 468 453 438 385 330 274
483 467 452 437 422 407 368
463 442 395 336 279 222 162
461 446 431 430 375 320 264
462 445 431 416 402 393 357
432 372 312 251 189
-
-
424 363 303 242 180
-
-
491 472 414 357 297 235 172
490 474 458 444 398 339 281
489 474 458 442 427 412 380
469 460 402 348 287 226 163
467 452 436 437 386 330 271
467 452 436 420 406 392 367
446 385 321 256 190
-
-
437 376 312 247 181
-
-
497 481 428 367 305 240 174
496 480 464 449 408 348 288
496 479 464 448 432 417 389
475 472 417 356 295 230 164
473 457 442 434 396 338 278
473 457 442 426 411 396 379
460 396 330 262 193
-
-
450 386 321 253 184
-
-
502 486 441 376 311 244 175
502 485 469 453 420 356 294
501 485 469 453 437 421 399
479 472 428 363 301 235 166
479 462 447 431 410 345 284
478 463 447 432 415 400 384
1.
2.
The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat *MBh = 3.415 x kW). Refer to the
appropriate Blower Performance table for the kW of the supply air blower motor.
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
43
246653-YTG-E-0108
order to use the indoor blower tables for high altitude applica-
tions, certain corrections are necessary.
CFM, STATIC PRESSURE, AND POWER - ALTI-
TUDE AND TEMPERATURE CORRECTIONS
A centrifugal fan is a "constant volume" device. This means
that, if the rpm remains constant, the CFM delivered is the
same regardless of the density of the air. However, since the
air at high altitude is less dense, less static pressure will be
generated and less power will be required than a similar
application at sea level. Air density correction factors are
The information below should be used to assist in application
of product when being applied at altitudes at or exceeding
1000 feet above sea level.
The air flow rates listed in the standard blower performance
tables are based on standard air at sea level. As the altitude
or temperature increases, the density of air decreases. In
TABLE 36: ALTITUDE CORRECTION FACTORS
ALTITUDE (FEET)
AIR TEMP
0
1000
1.022
1.002
0.982
0.964
0.947
0.929
0.912
2000
0.986
0.966
0.948
0.930
0.913
0.897
0.880
3000
0.950
0.931
0.913
0.896
0.880
0.864
0.848
4000
0.916
0.898
0.880
0.864
0.848
0.833
0.817
5000
0.882
0.864
0.848
0.832
0.817
0.802
0.787
6000
0.849
0.832
0.816
0.801
0.787
0.772
0.758
7000
0.818
0.802
0.787
0.772
0.758
0.744
0.730
8000
0.788
0.772
0.757
0.743
0.730
0.716
0.703
9000
0.758
0.743
0.729
0.715
0.702
0.689
0.676
10000
0.729
0.715
0.701
0.688
0.676
0.663
0.651
40
50
1.060
1.039
1.019
1.000
0.982
0.964
0.946
60
70
80
90
100
The examples below will assist in determining the airflow per-
formance of the product at altitude.
blower tables to select the blower speed and the BHP
requirement.
Example 1: What are the corrected CFM, static pressure,
and BHP at an elevation of 5,000 ft. if the blower performance
data is 6,000 CFM, 1.5 IWC and 4.0 BHP?
Solution: As in the example above, no temperature informa-
tion is given so 70°F is assumed.
The 1.5" static pressure given is at an elevation of 5,000 ft.
The first step is to convert this static pressure to equivalent
sea level conditions.
Solution: At an elevation of 5,000 ft the indoor blower will still
deliver 6,000 CFM if the rpm is unchanged. However, Table
Since no temperature data is given, we will assume an air
be 0.832.
Sea level static pressure = 1.5 / .832 = 1.80"
Enter the blower table at 6000 sCFM and static pressure of
1.8". The rpm listed will be the same rpm needed at 5,000 ft.
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC
Corrected BHP = 4.0 x 0.832 = 3.328
Suppose that the corresponding BHP listed in the table is 3.2.
This value must be corrected for elevation.
Example 2: A system, located at 5,000 feet of elevation, is to
BHP at 5,000 ft = 3.2 x .832 = 2.66
deliver 6,000 CFM at a static pressure of 1.5". Use the unit
44
Johnson Controls Unitary Products
246653-YTG-E-0108
1, 2
TABLE 37: FAN PERFORMANCE - 25 TON
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
0.6 0.8
0.2
1.2
2.2
3.2
0.4
1.4
2.4
3.4
1.0
2.0
3.0
4.0
AIRFLOW CFM
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
-
BHP
BHP
0.9
1.1
1.5
2.0
2.6
3.4
4.3
5.4
6.7
8.1
BHP
1.1
1.4
1.8
2.3
2.9
3.8
4.7
5.8
7.1
8.6
BHP
1.4
1.7
2.1
2.7
3.3
4.2
5.1
6.3
7.5
9.1
4000
5000
-
342
362
387
415
446
480
514
550
585
622
0.6
0.9
1.2
1.7
2.3
3.0
3.9
5.0
6.3
7.7
404
415
433
456
484
514
545
579
612
647
456
465
478
497
520
547
576
608
638
671
506
512
521
535
555
579
606
635
664
696
306
337
370
408
444
481
520
557
596
0.7
1.0
1.4
2.0
2.7
3.6
4.6
5.8
7.2
6000
7000
8000
9000
10000
11000
12000
13000
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
1.6 1.8
AIRFLOW CFM
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
1.7
2.1
2.5
3.0
3.7
4.6
5.5
6.7
8.0
9.6
BHP
2.0
2.4
2.9
3.4
4.1
5.0
6.0
7.2
8.5
BHP
2.3
2.8
3.3
3.9
4.6
5.4
6.4
7.6
9.0
BHP
2.7
3.2
3.7
4.3
5.0
5.9
6.9
8.1
9.5
BHP
3.0
3.5
4.1
4.7
5.4
6.4
7.4
8.6
4000
5000
549
555
562
573
591
611
634
662
690
720
591
597
602
610
624
642
663
689
714
743
628
634
638
645
657
673
692
715
739
766
663
670
674
679
689
703
719
741
763
789
698
705
709
713
720
732
747
766
787
811
6000
7000
8000
9000
10000
11000
12000
13000
10.0
11.8
10.1
10.6
11.2
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
2.6 2.8
AIRFLOW CFM
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
3.3
3.9
4.5
5.2
6.0
6.9
7.9
9.2
BHP
3.7
BHP
4.1
4.7
5.4
6.1
7.0
7.9
9.0
BHP
4.4
BHP
4.8
4000
5000
728
736
740
744
751
760
774
792
811
833
757
767
772
775
781
789
801
817
834
855
787
798
803
805
810
817
826
841
857
877
814
825
830
833
837
843
852
865
880
899
839
851
858
861
865
870
878
890
903
921
4.3
5.1
5.5
6000
5.0
5.9
6.3
7000
5.6
6.6
7.1
8000
6.5
7.5
8.0
9000
7.4
8.4
9.0
10000
11000
12000
13000
8.4
9.5
10.1
11.4
13.0
14.7
9.7
10.2
11.8
13.5
10.8
12.4
14.1
10.6
12.3
11.2
12.9
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
3.6 3.8
AIRFLOW CFM
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
5.1
BHP
5.5
BHP
5.9
6.8
7.7
8.7
9.6
BHP
6.3
BHP
6.7
4000
5000
864
878
885
889
892
897
903
913
926
942
890
904
911
914
918
921
927
936
948
963
913
927
935
939
942
946
951
959
970
984
935
950
959
964
967
970
975
983
992
1005
957
973
6.0
6.4
7.3
7.7
6000
6.8
7.3
8.2
983
8.7
7000
7.6
8.1
9.2
988
9.7
8000
8.5
9.1
10.2
11.3
12.6
14.0
15.4
17.3
992
10.8
11.9
13.2
14.6
16.1
18.0
9000
9.5
10.1
11.3
12.7
14.2
15.9
10.7
11.9
13.3
14.8
16.6
995
10000
11000
12000
13000
10.7
12.1
13.6
15.3
999
1005
1013
1025
1.
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.
BHP includes drive losses.
2.
3.
4. Shaded RPMs require Class II blower.
46
Johnson Controls Unitary Products
246653-YTG-E-0108
25 Ton Forward Curve
8.0
7.5
7.0
6.5
6.0
5.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
5
00
A
0
1
2
3
4
5
6
7
8
9
10
11
12
13
CFM (x1000)
A - Standard Unit
Note: Standard Unit includes wet evaporator coil, clean 2" throwaway filters, system
and cabinet effects at standard air density and 0' elevation.
FIGURE 22 - FAN PERFORMANCE - 25 TON
Johnson Controls Unitary Products
47
246653-YTG-E-0108
1, 2
0.4
TABLE 38: FAN PERFORMANCE - 30 TON
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
0.6
0.2
1.2
2.2
3.2
0.8
1.8
2.8
3.8
1.0
2.0
3.0
4.0
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
0.9
1.4
1.9
2.6
3.4
4.4
5.7
7.1
8.8
BHP
1.2
1.7
2.2
2.9
3.9
4.9
6.2
7.7
9.3
BHP
1.6
2.0
2.6
3.4
4.3
5.4
6.7
8.2
BHP
1.9
2.3
3.0
3.8
4.7
5.9
7.2
8.8
BHP
2.2
2.7
3.5
4.2
5.3
6.4
7.8
9.3
6000
7000
321
357
398
436
477
519
560
603
645
688
373
404
437
473
511
549
589
629
669
711
422
447
477
509
543
579
617
654
694
733
469
490
515
543
575
609
643
680
718
755.6
513
529
551
577
606
637
670
705
741
778
8000
9000
10000
11000
12000
13000
14000
15000
10.0
12.1
10.5
12.7
11.2
13.3
10.7
11.3
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
1.6
1.4
2.4
3.4
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
2.5
BHP
2.9
3.6
4.3
5.1
6.3
7.5
8.9
BHP
3.4
4.0
4.7
5.7
6.8
8.0
9.6
BHP
3.7
BHP
4.1
6000
7000
554
568
587
610
636
665
697
729
764
800
596
607
622
642
666
693
722
753
787
821
632
642
655
673
695
720
747
777
809
842
668
676
689
704
723
746
772
801
831
863
703
710
720
734
751
773
797
824
853
884
3.2
4.4
4.8
8000
3.9
5.3
5.7
9000
4.7
6.2
6.7
10000
11000
12000
13000
14000
15000
5.8
7.4
7.9
6.9
8.6
9.2
8.3
10.1
11.9
13.9
16.0
10.7
12.5
14.5
16.7
10.0
11.9
14.0
10.5
12.5
14.6
11.2
13.2
15.3
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
2.6
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
4.5
BHP
4.9
5.8
6.7
7.8
9.0
BHP
5.4
6.3
7.2
8.3
9.6
BHP
5.8
BHP
6.3
6000
7000
734
741
750
763
779
799
821
847
874
904
765
772
781
792
807
824
845
869
896
924
796
803
810
820
833
849
869
892
917
944
824
830
837
847
859
874
893
914
938
964
850
858
865
873
885
899
916
936
959
984
5.3
6.7
7.2
8000
6.2
7.8
8.3
9000
7.2
8.9
9.5
10000
11000
12000
13000
14000
15000
8.4
10.2
11.7
13.3
15.2
17.3
19.7
10.8
12.3
14.1
15.9
18.1
20.5
9.8
10.4
12.1
13.9
15.9
18.3
11.0
12.7
14.6
16.6
19.0
11.3
13.2
15.2
17.4
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
3.6
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
6.7
BHP
7.1
BHP
7.7
BHP
8.1
BHP
8.6
6000
7000
877
885
892
900
910
923
939
958
980
1004
904
911
928
935
951
959
975
984
7.7
8.2
8.7
9.2
9.7
8000
8.8
917
925
934
946
961
980
1001
1023
9.3
942
9.9
966
10.4
11.8
13.3
14.9
16.8
18.8
21.1
23.6
991
10.9
12.4
14.0
15.5
17.5
19.5
21.8
24.5
9000
10.0
11.4
13.0
14.7
16.6
18.8
21.2
10.6
12.1
13.7
15.3
17.3
19.6
22.1
949
11.1
12.7
14.3
16.1
18.1
20.4
22.9
974
998
10000
11000
12000
13000
14000
15000
958
982
1006
1015
1028
1043
1060
1081
970
993
984
1006
1022
1040
1062
1001
1021
1043
1.
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.
BHP includes drive losses.
2.
3.
4. Shaded RPMs require Class II blower.
48
Johnson Controls Unitary Products
246653-YTG-E-0108
30 Ton Forward Curve
8.0
7.5
7.0
6.5
6.0
5.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
A
0
2
4
6
8
10
12
14
16
18
20
CFM (x1000)
A - Standard Unit
Note: Standard Unit includes wet evaporator coil, clean 2" throwaway filters, system
and cabinet effects at standard air density and 0' elevation.
FIGURE 23 - FAN PERFORMANCE - 30 TON
Johnson Controls Unitary Products
49
246653-YTG-E-0108
1,2
TABLE 39: FAN PERFORMANCE - 40 TON
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
0.6
0.2
1.2
2.2
3.2
0.4
0.8
1.8
2.8
3.8
1.0
2.0
3.0
4.0
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
1.4
1.9
2.4
3.0
3.9
4.8
6.0
7.2
8.7
BHP
1.8
2.3
2.8
3.6
4.5
5.5
6.6
8.0
9.5
BHP
2.2
2.7
3.4
4.1
5.0
6.1
7.2
8.6
BHP
2.6
3.2
3.9
4.7
5.7
6.7
8.0
9.3
BHP
3.0
3.7
4.4
5.3
6.2
7.4
8.6
8000
9000
304
329
356
385
414
442
472
503
532
562
593
348
371
396
421
446
473
502
529
557
587
616
393
411
432
454
479
504
529
555
583
611
638
431
448
467
488
510
532
556
581
607
633
660
469
484
502
519
539
560
583
607
631
656
682
10000
11000
12000
13000
14000
15000
16000
17000
18000
10.1
11.8
13.5
15.4
10.2
12.0
13.9
10.9
12.7
14.7
10.4
12.3
11.1
13.1
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
1.6
1.4
2.4
3.4
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
3.5
4.2
4.9
5.8
6.8
8.0
9.3
BHP
4.0
4.6
5.5
6.4
7.5
8.6
BHP
4.4
5.1
6.1
7.0
8.1
9.3
BHP
4.9
5.8
6.6
7.6
BHP
5.5
8000
9000
506
518
532
549
568
588
609
631
654
678
703
537
549
563
579
596
614
634
655
677
701
724
569
581
594
608
623
640
658
679
700
722
744
601
610
621
634
649
665
683
702
722
742
764
627
637
648
661
675
690
707
724
743
763
785
6.3
7.1
8.2
9.5
10.7
12.2
13.9
15.6
17.6
19.8
10000
11000
12000
13000
14000
15000
16000
17000
18000
8.7
10.0
11.4
13.1
14.8
16.8
19.0
10.0
11.6
13.2
15.1
17.2
10.7
12.3
14.1
16.0
18.1
10.8
12.5
14.3
16.4
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
2.6
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
6.0
6.8
7.8
8.8
BHP
6.5
7.4
8.4
9.5
BHP
7.0
8.0
BHP
7.6
8.5
BHP
8.1
8000
9000
654
664
675
687
700
714
729
746
764
784
805
681
691
701
712
723
737
752
768
786
805
824
706
715
725
735
747
760
774
790
807
824
843
729
738
748
758
770
782
796
811
826
843
862
752
761
771
781
793
805
817
831
846
863
881
9.1
10000
11000
12000
13000
14000
15000
16000
17000
18000
9.0
9.6
10.2
11.4
12.9
14.4
16.0
17.9
19.8
22.1
24.5
10.2
11.4
12.9
14.5
16.2
18.2
20.3
22.6
10.8
12.2
13.7
15.2
17.0
19.0
21.1
23.5
10.1
11.4
13.0
14.6
16.5
18.5
20.7
10.7
12.2
13.8
15.4
17.3
19.4
21.6
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
3.6
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
8.7
9.8
BHP
BHP
BHP
10.4
11.6
12.9
14.3
15.8
17.4
19.2
21.2
23.3
25.7
-
BHP
11.0
12.2
13.5
14.9
16.5
18.2
20.1
22.1
24.3
-
8000
9000
774
784
794
804
814
825
837
851
866
882
900
797
806
815
824
835
846
858
871
886
901
-
9.2
817
826
836
845
855
866
878
891
905
919
-
9.9
837
846
856
865
876
886
898
910
923
937
-
857
866
876
886
896
906
917
928
941
-
10.3
11.6
12.8
14.3
15.9
17.6
19.5
21.5
23.8
-
10.9
12.2
13.5
15.0
16.6
18.4
20.4
22.5
24.8
-
10000
11000
12000
13000
14000
15000
16000
17000
18000
10.8
12.2
13.5
15.1
16.8
18.7
20.7
23.0
25.4
-
-
1.
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.
BHP includes drive losses.
2.
3.
4. Shaded RPMs require Class II blower.
50
Johnson Controls Unitary Products
246653-YTG-E-0108
40 Ton Forward Curve
7.0
6.5
6.0
5.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
A
300
0
2
4
6
8
10
12
14
16
18
20
CFM (x1000)
A - Standard Unit
Note: Standard Unit includes wet evaporator coil, clean 2" throwaway filters, system
and cabinet effects at standard air density and 0' elevation.
FIGURE 24 - FAN PERFORMANCE - 40 TON
Johnson Controls Unitary Products
51
246653-YTG-E-0108
1,2
TABLE 40: FAN PERFORMANCE - 25 & 30 TON AIRFOIL
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
0.6
0.2
1.2
2.2
3.2
0.4
1.4
2.4
3.4
0.8
1.8
2.8
3.8
1.0
2.0
3.0
4.0
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
0.3
0.6
0.9
1.3
1.9
2.7
3.6
4.7
6.0
7.6
9.4
BHP
0.5
0.7
1.1
1.6
2.2
2.9
3.9
5.0
6.4
7.9
9.8
BHP
0.6
0.9
1.3
1.8
2.4
3.2
4.2
5.3
6.7
8.3
BHP
0.8
1.1
1.5
2.0
2.7
3.5
4.5
5.7
7.1
8.7
BHP
1.0
1.3
1.7
2.3
2.9
3.8
4.8
6.1
7.5
9.1
4000
5000
595
709
667
769
735
827
800
882
862
935
6000
827
879
929
977
1024
1122
1227
1336
1449
1565
1682
1802
1922
2043
7000
948
995
1038
1151
1268
1387
1508
1629
1752
1875
2000
1081
1190
1303
1418
1536
1656
1777
1899
2022
8000
1072
1197
1322
1447
1574
1701
1828
1955
1113
1233
1354
1478
1602
1726
1852
1978
9000
10000
11000
12000
13000
14000
15000
10.2
12.4
10.6
12.8
11.1
13.2
11.5
11.9
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
1.6
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
1.1
1.5
1.9
2.5
3.2
4.1
5.1
6.4
7.8
9.6
11.5
13.7
BHP
1.3
1.7
2.2
2.8
3.5
4.4
5.5
6.8
8.2
BHP
1.5
1.9
2.4
3.0
3.8
4.7
5.8
7.1
8.6
BHP
1.7
BHP
1.9
4000
5000
921
978
1032
1087
1158
1241
1335
1434
1539
1648
1760
1874
1990
2107
1085
1134
1201
1280
1369
1466
1569
1675
1785
1898
2012
2128
1135
1180
1242
1318
1404
1498
1598
1702
1810
1921
2034
2149
988
1037
1114
1203
1300
1403
1510
1621
1734
1850
1967
2086
2.1
2.4
6000
1070
1163
1263
1370
1480
1593
1709
1826
1944
2065
2.7
2.9
7000
3.3
3.6
8000
4.1
4.4
9000
5.0
5.4
10000
11000
12000
13000
14000
15000
6.2
6.5
7.5
7.8
9.0
9.4
10.0
11.9
14.2
10.4
12.4
14.7
10.8
12.8
15.1
11.2
13.3
15.6
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
2.6
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
2.2
BHP
2.4
2.9
3.4
4.1
5.0
6.0
7.2
8.6
BHP
2.6
3.1
3.7
4.4
5.3
6.4
7.6
9.0
BHP
2.8
BHP
3.1
4000
5000
1184
1225
1283
1355
1438
1529
1626
1728
1835
1944
2055
2169
1231
1269
1323
1392
1471
1559
1654
1755
1859
1967
2077
2190
1277
1312
1362
1427
1504
1590
1683
1781
1884
1990
2099
2210
1321
1353
1402
1463
1537
1620
1710
1807
1908
2012
2120
2230
1364
1395
1439
1498
1569
1649
1738
1832
1932
2035
2141
2250
2.6
3.4
3.6
6000
3.2
4.0
4.3
7000
3.9
4.7
5.0
8000
4.7
5.7
6.0
9000
5.7
6.7
7.1
10000
11000
12000
13000
14000
15000
6.9
7.9
8.3
8.2
9.4
9.8
9.8
10.2
12.1
14.2
16.6
10.6
12.5
14.7
17.1
11.1
13.0
15.1
17.6
11.5
13.4
15.6
18.1
11.7
13.7
16.1
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
3.6
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
3.3
BHP
3.6
4.2
4.9
5.7
6.7
7.8
9.1
BHP
3.8
4.4
5.1
6.0
7.0
8.1
9.5
BHP
4.1
BHP
4.4
4000
5000
1407
1434
1476
1532
1601
1679
1765
1858
1955
2057
2162
2270
1447
1473
1513
1566
1632
1708
1792
1883
1979
2079
2183
2290
1487
1512
1549
1600
1663
1737
1819
1908
2003
2102
2204
2310
1525
1549
1584
1633
1694
1765
1846
1933
2026
2123
2225
2329
1563
1586
1619
1666
1724
1794
1872
1957
2049
2145
2245
2348
3.9
4.7
5.0
6000
4.6
5.5
5.8
7000
5.4
6.3
6.7
8000
6.3
7.3
7.7
9000
7.4
8.5
8.9
10000
11000
12000
13000
14000
15000
8.7
9.9
10.3
11.9
13.7
15.7
18.1
20.6
10.2
11.9
13.9
16.1
18.6
10.6
12.4
14.3
16.6
19.1
11.0
12.8
14.8
17.1
19.6
11.4
13.2
15.2
17.6
20.1
52
Johnson Controls Unitary Products
246653-YTG-E-0108
1,2
TABLE 40: FAN PERFORMANCE - 25 & 30 TON AIRFOIL (CONTINUED)
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
4.2
4.4
4.6
4.8
5.0
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
4.6
5.3
6.1
7.0
8.0
9.3
BHP
4.9
5.6
6.4
7.3
8.4
9.7
BHP
5.2
5.9
6.7
7.7
8.8
BHP
5.5
6.2
7.0
8.0
9.1
BHP
5.8
4000
5000
1601
1621
1653
1698
1754
1822
1898
1982
2072
2167
2265
2368
1636
1656
1687
1730
1784
1850
1924
2006
2095
2188
2286
2387
1672
1691
1720
1761
1814
1877
1950
2030
2117
2210
2306
2406
1707
1725
1753
1792
1843
1905
1976
2054
2140
2231
2326
2425
1740
1758
1785
1822
1872
1932
2001
2078
2162
2252
2346
2444
6.5
6000
7.4
7000
8.4
8000
9.5
9000
10.0
11.5
13.1
15.0
17.2
19.6
22.2
10.4
11.9
13.6
15.5
17.7
20.1
22.8
10.8
12.3
14.0
15.9
18.2
20.6
23.3
10000
11000
12000
13000
14000
15000
10.7
12.3
14.1
16.2
18.6
21.1
11.1
12.7
14.6
16.7
19.1
21.7
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
5.6
5.2
5.4
5.8
6.0
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
6.1
BHP
6.4
BHP
6.7
BHP
7.0
BHP
7.3
4000
5000
1774
1791
1817
1853
1901
1958
2026
2102
2185
2273
2366
2463
1807
1823
1847
1883
1928
1985
2051
2126
2207
2294
2386
2482
1838
1855
1878
1912
1956
2012
2076
2149
2229
2315
2406
2501
1870
1886
1909
1941
1984
2038
2101
2172
2251
2336
2425
1902
1917
1938
1970
2012
2064
2125
2196
2273
2356
2445
6.8
7.1
7.5
7.8
8.1
6000
7.7
8.0
8.4
8.7
9.1
7000
8.7
9.1
9.4
9.8
10.2
11.4
12.8
14.4
16.3
18.3
20.6
23.2
8000
9.9
10.2
11.6
13.1
14.9
16.9
19.1
21.6
24.4
10.6
12.0
13.6
15.3
17.4
19.6
22.1
24.9
11.0
12.4
14.0
15.8
17.9
20.1
22.6
9000
11.2
12.7
14.5
16.4
18.6
21.1
23.8
10000
11000
12000
13000
14000
15000
1.
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.
Refer to Tables 10, 12, 15, 18, 21, 23 and 42 for component additions and deductions to fan performance tables.
BHP includes drive losses.
2.
3.
4. Shaded RPMs require Class II blower.
Johnson Controls Unitary Products
53
246653-YTG-E-0108
1,2
TABLE 41: FAN PERFORMANCE - 40 TON AIRFOIL
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
0.6
0.2
1.2
2.2
0.4
1.4
2.4
0.8
1.8
2.8
1.0
2.0
3.0
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
1.4
1.8
2.5
3.2
4.1
5.1
6.3
7.7
9.2
BHP
1.6
2.1
2.8
3.5
4.5
5.5
6.8
8.2
9.8
BHP
1.9
2.4
3.1
3.9
4.8
5.9
7.2
8.6
BHP
2.2
2.7
3.4
4.3
5.2
6.4
7.7
9.1
BHP
2.4
3.1
3.8
4.6
5.6
6.8
8.1
9.6
8000
9000
769
855
814
896
856
898
937
933
971
1008
1081
1157
1236
1316
1397
1479
1563
1647
1732
1817
1903
1989
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
21000
22000
941
978
1013
1095
1177
1261
1346
1431
1518
1604
1691
1778
1866
1953
2042
1047
1126
1207
1289
1372
1455
1540
1625
1712
1798
1884
1971
1029
1117
1205
1294
1382
1471
1560
1649
1739
1828
1918
2008
1062
1147
1233
1320
1407
1495
1582
1670
1758
1847
1936
2025
10.3
12.1
14.2
16.4
19.0
21.7
24.8
10.8
12.6
14.7
17.1
19.6
22.4
11.3
13.2
15.3
17.7
20.3
23.1
11.0
13.0
15.2
17.7
20.4
23.4
11.6
13.6
15.8
18.3
21.1
24.1
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
1.6
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
2.7
BHP
3.0
3.7
4.5
5.4
6.5
7.7
9.1
BHP
3.3
4.0
4.8
5.8
6.9
8.1
9.5
BHP
3.6
BHP
4.0
8000
9000
975
1013
1077
1146
1218
1292
1368
1446
1526
1607
1689
1771
1855
1939
2024
1049
1111
1177
1247
1320
1395
1471
1549
1629
1710
1791
1874
1957
1085
1144
1208
1276
1346
1420
1495
1572
1650
1730
1811
1893
1975
1120
1177
1238
1305
1373
1445
1519
1595
1672
1750
1830
1911
1993
1043
1114
1188
1264
1342
1422
1503
1585
1668
1751
1836
1921
2007
3.4
4.4
4.7
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
21000
22000
4.1
5.2
5.6
5.0
6.2
6.6
6.1
7.3
7.7
7.2
8.6
9.0
8.6
10.0
11.6
13.4
15.4
17.7
20.1
22.9
10.5
12.1
14.0
16.0
18.3
20.8
23.5
10.1
11.8
13.8
15.9
18.3
20.9
23.8
10.6
12.4
14.3
16.5
18.9
21.5
24.5
11.1
12.9
14.9
17.1
19.5
22.2
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
2.6
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
4.3
BHP
4.6
5.4
6.3
7.4
8.6
9.9
BHP
4.9
5.8
6.7
7.8
9.0
BHP
5.3
BHP
5.6
8000
9000
1154
1209
1268
1332
1400
1470
1542
1617
1693
1770
1849
1929
2010
1188
1240
1298
1359
1425
1494
1565
1638
1714
1791
1868
1947
2027
1220
1270
1326
1387
1451
1518
1588
1660
1734
1810
1887
1965
1252
1301
1355
1414
1476
1542
1611
1682
1755
1830
1906
1984
1284
1330
1383
1440
1502
1566
1633
1704
1775
1849
1925
2002
5.0
6.1
6.5
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
6.0
7.1
7.5
7.0
8.2
8.6
8.1
9.4
9.9
9.5
10.4
11.9
13.7
15.6
17.7
20.1
22.7
10.8
12.4
14.2
16.1
18.3
20.7
23.3
11.3
12.9
14.7
16.7
18.9
21.3
24.0
10.9
12.6
14.5
16.6
18.9
21.4
24.2
11.4
13.1
15.0
17.2
19.5
22.0
24.8
54
Johnson Controls Unitary Products
246653-YTG-E-0108
1,2
TABLE 41: FAN PERFORMANCE - 40 TON AIRFOIL (CONTINUED)
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
3.2
3.4
3.6
3.8
4.0
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
6.0
BHP
6.4
BHP
6.7
BHP
7.1
BHP
7.4
8000
9000
1315
1360
1411
1466
1526
1590
1656
1725
1796
1868
1943
2019
1345
1389
1438
1492
1550
1613
1678
1745
1816
1888
1961
1375
1417
1464
1517
1575
1635
1700
1766
1835
1907
1980
1405
1445
1491
1542
1599
1658
1721
1787
1855
1926
1998
1433
1472
1517
1567
1622
1681
1743
1808
1875
1944
2016
6.9
7.3
7.6
8.0
8.4
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
7.9
8.3
8.7
9.1
9.5
9.0
9.5
9.9
10.3
11.7
13.2
14.9
16.9
19.0
21.2
23.8
10.8
12.2
13.7
15.5
17.4
19.5
21.8
24.4
10.3
11.8
13.4
15.2
17.3
19.5
21.9
24.6
10.8
12.3
13.9
15.8
17.8
20.1
22.5
11.2
12.7
14.4
16.3
18.4
20.6
23.2
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
4.6
4.2
4.4
4.8
5.0
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
7.8
BHP
8.2
BHP
8.6
BHP
9.0
BHP
9.4
8000
9000
1462
1500
1543
1592
1645
1703
1764
1828
1895
1963
2033
1490
1526
1569
1617
1669
1725
1785
1848
1914
1981
1518
1553
1594
1640
1692
1747
1806
1868
1933
2000
1545
1579
1619
1664
1715
1769
1827
1888
1952
2018
1572
1605
1644
1688
1737
1791
1847
1908
1971
2036
8.8
9.2
9.6
10.0
11.2
12.6
14.1
15.7
17.6
19.6
21.8
24.3
10.4
11.7
13.0
14.6
16.2
18.1
20.2
22.4
24.9
10000
11000
12000
13000
14000
15000
16000
17000
18000
9.9
10.4
11.7
13.1
14.7
16.5
18.5
20.7
23.1
10.8
12.1
13.6
15.2
17.1
19.1
21.2
23.7
11.2
12.6
14.2
16.0
18.0
20.1
22.5
25.0
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
5.6
5.2
5.4
5.8
6.0
AIRFLOW (CFM)
3
3
3
3
3
RPM
RPM
RPM
RPM
RPM
BHP
9.8
BHP
BHP
BHP
11.0
12.2
13.5
14.9
16.6
18.4
20.3
22.5
24.8
BHP
11.4
12.6
13.9
15.4
17.1
18.9
20.8
23.0
8000
9000
1599
1630
1668
1712
1759
1812
1868
1927
1990
1624
1655
1692
1734
1782
1833
1888
1947
2008
10.2
11.3
12.6
14.0
15.5
17.3
19.2
21.3
23.6
1650
1680
1716
1757
1804
1854
1908
1966
2027
10.6
11.7
13.0
14.5
16.0
17.8
19.8
21.9
24.2
1675
1705
1740
1780
1825
1875
1928
1985
2045
1701
1729
1763
1803
1847
1896
1948
2004
10.9
12.1
13.5
15.0
16.8
18.7
20.7
23.0
10000
11000
12000
13000
14000
15000
16000
17000
18000
1.
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.
Refer to Tables 10, 12, 15, 18, 21, 23 and 42 for component additions and deductions to fan performance tables.
BHP includes drive losses.
2.
3.
4. Shaded RPMs require Class II blower.
Johnson Controls Unitary Products
55
246653-YTG-E-0108
1, 2
TABLE 42: COMPONENT STATIC RESISTANCE
CFM
12,000
-0.13
COMPONENT COIL
LOSSES
6,000
-0.06
8,000
-0.08
10,000
14,000
-
16,000
-
18,000
-
STD. 25 TON, DRY
STD. 25 TON, WET
STD. 30 TON, DRY
STD. 30 TON, WET
HI CAP 30 TON, DRY
HI CAP 30 TON, WET
STD. 40 TON, DRY
STD. 40 TON, WET
HI CAP 40 TON, DRY
HI CAP 40 TON, WET
FILTER LOSSES
2” TA OR HI EFF.
RIGID 6”, 65%
-0.10
Baseline
-0.112
Baseline
-0.045
Baseline
-0.019
0.042
Baseline
-0.075
Baseline
-0.035
0.069
Baseline
-0.157
Baseline
-0.073
0.142
Baseline
-0.207
Baseline
-0.098
0.186
Baseline
-0.264
Baseline
-0.124
0.236
Baseline
-0.326
Baseline
-0.155
0.290
Baseline
-0.052
0.103
-0.030
Baseline
-0.020
0.023
-0.051
Baseline
-0.033
0.038
-0.076
Baseline
-0.050
0.057
-0.106
Baseline
-0.069
0.079
-0.140
Baseline
-0.092
0.105
-0.177
Baseline
-0.116
0.133
-0.219
Baseline
-0.144
0.164
Baseline
0.048
Baseline
0.080
Baseline
0.119
Baseline
0.165
Baseline
0.217
Baseline
0.274
Baseline
0.338
RIGID 6”, 95%
0.189
0.308
0.448
0.609
0.790
0.988
1.205
IGV LOSSES
25 & 30 TON
0.048
0.027
0.085
0.049
0.132
0.076
0.190
0.110
0.259
0.149
0.338
0.195
0.428
0.246
40 TON
GAS HEAT
267 MBH HEAT
533 MBH HEAT
800 MBH HEAT
ELECTRIC HEAT
ECONOMIZER
0.106
0.212
0.318
0.050
0.063
0.046
0.141
0.283
0.423
0.100
0.104
0.081
0.177
0.353
0.531
0.150
0.153
0.127
0.212
0.424
0.636
0.310
0.210
0.182
0.247
0.495
0.741
0.430
0.276
0.248
0.283
0.566
0.849
0.530
0.349
0.324
0.318
0.636
0.954
0.680
0.429
0.410
POWER EXHAUST
1.
Baseline losses based on system/cabinet effects, wet standard coil and 2” throwaway filters at 70°F, 0 feet elevation with standard air.
2.
56
Johnson Controls Unitary Products
246653-YTG-E-0108
1
TABLE 43: POWER EXHAUST - ONE FORWARD CURVED FAN 25 TON
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
0.2
0.4 0.6 0.8
1.0
AIRFLOW CFM
2
2
2
2
2
RPM
RPM
RPM
RPM
RPM
BHP
BHP
BHP
BHP
BHP
4000
5000
6000
7000
8000
9000
10000
442
524
612
703
791
877
967
0.66
1.21
1.93
3.00
3.81
5.81
8.42
496
566
646
731
821
911
0.78
1.35
2.18
3.32
4.29
6.17
8.76
562
609
679
759
844
932
1022
0.91
1.50
2.36
3.54
4.77
6.53
9.09
626
663
717
787
868
953
1041
1.05
1.66
2.55
3.75
5.24
6.90
9.43
687
717
762
820
892
974
1059
1.22
1.83
2.73
3.97
5.49
7.27
9.77
1004
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
1.4 1.6 1.8
1.2
2.0
AIRFLOW CFM
2
2
2
2
2
RPM
RPM
RPM
RPM
RPM
BHP
1.39
2.00
2.92
4.18
5.74
7.63
10.10
BHP
BHP
BHP
1.93
2.60
3.57
4.83
6.50
8.54
-
BHP
2.14
2.81
3.80
5.04
6.75
8.81
-
4000
5000
6000
7000
8000
9000
10000
743
768
806
857
921
995
1077
799
818
1.54
2.18
3.10
4.40
6.00
7.97
10.44
850
865
895
933
985
1048
-
1.74
2.39
3.33
4.61
6.25
8.25
-
900
911
937
972
1018
1075
-
948
955
978
1010
1052
1103
-
850
895
953
1020
1096
1.
Fan performance is based on system/cabinet effects and back draft damper effects at standard air density and 0 feet elevation.
BHP includes 5% drive losses.
2.
Johnson Controls Unitary Products
57
246653-YTG-E-0108
Power Exhaust 25 Ton
8.0
7.5
7.0
6.5
6.0
5.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
1600
1500
10 BHP
7.5 BHP
1400
1300
5 BHP
1200
1100
1000
900
800
700
600
500
400
300
0.0
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
CFM (x1000)
FIGURE 25 - POWER EXHAUST - ONE FORWARD CURVE FAN - 25 TONS
58
Johnson Controls Unitary Products
246653-YTG-E-0108
1
TABLE 44: POWER EXHAUST - TWO FORWARD CURVED FANS - 30 & 40 TON
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
0.2
0.4
.06
0.8
1.0
AIRFLOW CFM
2 3
2 3
BHP
2 3
2 3
BHP
2 3
RPM
RPM
RPM
RPM
RPM
BHP
BHP
0.32
BHP
0.74
4000
5000
363
402
445
494
544
597
651
705
761
817
874
932
989
468
494
527
565
609
654
703
753
805
858
912
967
1022
0.53
560
576
602
633
670
711
641
652
670
697
729
765
805
847
893
939
988
1037
1088
0.95
716
722
735
757
784
817
853
893
934
979
1025
1072
-
1.16
1.47
2.00
2.52
3.15
3.89
4.83
5.99
7.25
8.82
10.50
12.60
-
0.53
0.84
1.26
1.79
2.42
3.26
4.31
5.46
6.93
8.51
10.40
12.60
0.74
1.05
1.58
2.10
2.84
3.68
4.73
5.88
7.35
9.03
10.92
13.23
1.05
1.37
1.79
2.42
3.15
3.99
5.15
6.30
7.77
9.56
11.55
13.76
1.26
1.68
2.10
2.73
3.47
4.41
5.57
6.83
8.30
9.98
12.08
14.28
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
16000
754
801
849
899
950
1002
1055
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
1.6
1.2
1.4
1.8
2
AIRFLOW CFM
2 3
2 3
BHP
2 3
2 3
BHP
2 3
RPM
RPM
RPM
RPM
RPM
BHP
1.47
BHP
1.89
BHP
2.42
4000
5000
783
788
798
814
837
866
900
936
976
1018
1061
1107
844
848
1.68
903
906
956
959
2.21
1008
1011
1014
1021
1033
1050
1073
1101
1131
1165
1202
1240
1.79
2.21
2.84
3.47
4.31
5.25
6.41
7.77
9.35
11.13
13.23
2.10
2.63
3.15
3.89
4.73
5.67
6.93
8.30
9.87
11.66
13.76
2.42
2.94
3.47
4.20
5.15
6.20
7.35
8.72
10.40
12.29
14.39
2.63
3.26
3.89
4.62
5.57
6.62
7.88
9.24
10.92
12.92
14.91
2.94
3.57
4.20
5.04
5.99
7.14
8.30
9.77
11.55
13.44
15.54
6000
855
911
963
7000
869
922
972
8000
889
938
987
9000
915
961
1007
1032
1061
1094
1129
1167
1208
10000
11000
12000
13000
14000
15000
945
989
979
1020
1055
1093
1133
1175
1016
1055
1098
1141
1.
2.
3.
Fan performance is based on system/cabinet effects and back draft damper effects at standard air density and 0 feet elevation.
BHP includes the sum of both exhaust fan motors.
BHP does includes 5% drive losses.
Johnson Controls Unitary Products
59
246653-YTG-E-0108
TABLE 45: ELECTRICAL DATA 25 TON BASIC UNIT R22
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
SUPPLY BLOWER
1
2
MCA
/
VOLTAGE
3
(AMPS)
QTY.
RLA
LRA
MCC
QTY
FLA
HP
FLA
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
24.2
30.8
46.2
59.4
22.0
28.0
42.0
54.0
11.0
14.0
21.0
27.0
9.0
137
144
160
177
134
140
154
169
59
175
175
200
225
150
175
175
200
70
208-3-60
2
42.3
245
66.0
4
4
4
4
3.8
230-3-60
460-3-60
2
2
2
42.3
17.6
14.2
245
125
100
66.0
27.5
22.2
3.8
1.9
1.5
62
70
70
90
78
100
60
48
11.0
17.0
22.0
50
60
575-3-60
56
70
63
80
1.
Minimum Circuit Ampacity.
Dual Element, Time Delay Type.
HACR type per NEC
2.
3.
TABLE 46: ELECTRICAL DATA 30 TON BASIC UNIT R22
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
2
SUPPLY BLOWER
1
MCA
FUSE
/
VOLTAGE
3
(AMPS)
BREAKER
SIZE
QTY.
RLA
LRA
MCC
QTY
FLA
HP
FLA
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
30.8
46.2
59.4
74.8
28.0
42.0
54.0
68.0
14.0
21.0
27.0
34.0
11.0
17.0
22.0
27.0
165
183
199
219
162
177
192
210
76
200
225
250
250
175
200
225
250
90
208-3-60
3
37.2
239
58.0
3
3
3
3
4.5
230-3-60
460-3-60
3
3
3
37.2
17.2
12.4
239
125
80
58.0
27.0
19.3
4.5
2.2
1.7
84
100
110
125
60
92
101
56
64
80
575-3-60
70
90
76
100
1.
Minimum Circuit Ampacity.
Dual Element, Time Delay Type.
HACR type per NEC
2.
3.
Johnson Controls Unitary Products
61
246653-YTG-E-0108
TABLE 47: ELECTRICAL DATA 40 TON BASIC UNIT R22
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
SUPPLY BLOWER
1
2
MCA
/
VOLTAGE
3
(AMPS)
QTY.
RLA
LRA
MCC
QTY
FLA
HP
FLA
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
30.8
46.2
59.4
74.8
28.0
42.0
54.0
68.0
14.0
21.0
27.0
34.0
11.0
17.0
22.0
27.0
207
225
241
260
203
219
234
251
96
225
250
250
300
225
250
250
300
110
110
125
150
80
208-3-60
4
37.2
239
58.0
4
4
4
4
4.5
230-3-60
460-3-60
4
4
4
37.2
17.2
12.4
239
125
80
58.0
27.0
19.3
4.5
2.2
1.7
104
111
120
71
78
90
575-3-60
84
100
110
90
1.
Minimum Circuit Ampacity.
Dual Element, Time Delay Type.
HACR type per NEC
2.
3.
62
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 48: ELECTRICAL DATA 25 TON WITH ELECTRIC HEAT R22
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
SUPPLY BLOWER
ELECTRIC HEAT
1
2
MCA
/
VOLTAGE
3
(AMPS)
APPLIED
QTY. RLA LRA MCC
QTY
FLA
HP
FLA
OPTION
KW
KW
STAGES
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
24.2
30.8
46.2
59.4
24.2
30.8
46.2
59.4
22.0
28.0
42.0
54.0
22.0
28.0
42.0
54.0
11.0
14.0
21.0
27.0
11.0
14.0
21.0
27.0
11.0
14.0
21.0
27.0
9.0
E4
E4
E4
E4
E8
E8
E8
E8
E4
E4
E4
E4
E8
E8
E8
E8
E4
E4
E4
E4
E8
E8
E8
E8
E1
E1
E1
E1
E4
E4
E4
E4
E8
E8
E8
E8
E1
E1
E1
E1
40
40
30
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
2
2
2
2
1
1
1
1
2
2
2
2
2
2
2
2
137
144
162
178
197
205
225
241
148
155
173
188
220
227
245
260
74
175
175
200
225
225
225
250
300
175
175
175
200
250
250
250
300
80
30
40
30
40
30
208-3-60
2
42.3
245
66.0
4
3.8
80
60
80
60
80
60
80
60
40
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
99.4
99.4
99.4
99.4
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
99.4
99.4
99.4
99.4
40
40
40
230-3-60
2
42.3
245
66.0
4
3.8
80
80
80
80
40
40
78
80
40
86
90
40
94
110
125
125
125
150
175
175
175
175
60
80
110
114
122
130
144
147
156
164
59
80
460-3-60
2
17.6
125
27.5
4
1.9
80
80
108
108
108
108
40
11.0
17.0
22.0
9.0
40
62
70
40
69
70
40
76
80
80
88
100
100
110
125
125
150
150
150
11.0
17.0
22.0
9.0
80
91
575-3-60
2
14.2
100
22.2
4
1.5
80
98
80
104
115
118
125
131
108
108
108
108
11.0
17.0
22.0
1.
Minimum Circuit Ampacity.
2.
3.
Dual Element, Time Delay Type.
HACR type per NEC
Johnson Controls Unitary Products
63
246653-YTG-E-0108
TABLE 49: ELECTRICAL DATA 30 TON WITH ELECTRIC HEAT R22
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
SUPPLY BLOWER
ELECTRIC HEAT
1
2
MCA
/
VOLTAGE
208-3-60
3
(AMPS)
APPLIED
QTY. RLA LRA MCC
QTY
FLA
HP
FLA
OPTION
KW
KW
STAGES
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
30.8
46.2
59.4
74.8
30.8
46.2
59.4
74.8
28.0
42.0
54.0
68.0
28.0
42.0
54.0
68.0
14.0
21.0
27.0
34.0
14.0
21.0
27.0
34.0
14.0
21.0
27.0
34.0
11.0
17.0
22.0
27.0
11.0
17.0
22.0
27.0
11.0
17.0
22.0
27.0
E4
E4
E4
E4
E8
E8
E8
E8
E4
E4
E4
E4
E8
E8
E8
E8
E4
E4
E4
E4
E8
E8
E8
E8
E1
E1
E1
E1
E4
E4
E4
E4
E8
E8
E8
E8
E1
E1
E1
E1
40
40
30
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
2
2
2
2
1
1
1
1
2
2
2
2
2
2
2
2
165
183
199
219
205
225
241
260
162
177
192
210
227
245
260
277
78
200
225
250
250
225
250
300
300
175
200
225
250
250
250
300
300
90
30
40
30
40
30
3
37.2
239
58.0
3
4.5
80
60
80
60
80
60
80
60
40
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
99.4
99.4
99.4
99.4
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
99.4
99.4
99.4
99.4
40
40
40
230-3-60
3
37.2
239
58.0
3
4.5
80
80
80
80
40
40
86
100
110
125
125
125
150
150
175
175
175
200
70
40
94
40
103
114
122
130
139
147
156
164
172
62
80
80
460-3-60
3
17.2
125
27.0
3
2.2
80
80
108
108
108
108
40
40
69
80
40
76
90
40
82
100
100
110
125
125
150
150
150
150
80
91
80
98
575-3-60
3
12.4
80
19.3
3
1.7
80
104
111
118
125
131
138
80
108
108
108
108
1.
Minimum Circuit Ampacity.
2.
3.
Dual Element, Time Delay Type.
HACR type per NEC
64
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 50: ELECTRICAL DATA 40 TON WITH ELECTRIC HEAT R22
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
SUPPLY BLOWER
ELECTRIC HEAT
1
2
MCA
/
VOLTAGE
3
(AMPS)
APPLIED
QTY. RLA LRA MCC
QTY
FLA
HP
FLA
OPTION
KW
KW
STAGES
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
30.8
46.2
59.4
74.8
30.8
46.2
59.4
74.8
28.0
42.0
54.0
68.0
28.0
42.0
54.0
68.0
14.0
21.0
27.0
34.0
14.0
21.0
27.0
34.0
14.0
21.0
27.0
34.0
11.0
17.0
22.0
27.0
11.0
17.0
22.0
27.0
11.0
17.0
22.0
27.0
E4
E4
E4
E4
E8
E8
E8
E8
E4
E4
E4
E4
E8
E8
E8
E8
E4
E4
E4
E4
E8
E8
E8
E8
E1
E1
E1
E1
E4
E4
E4
E4
E8
E8
E8
E8
E1
E1
E1
E1
40
40
30.0
30.0
30.0
30.0
60.1
60.1
60.1
60.1
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
99.4
99.4
99.4
99.4
36.8
36.8
36.8
36.8
73.6
73.6
73.6
73.6
99.4
99.4
99.4
99.4
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
1
1
1
1
2
2
2
2
2
2
2
2
1
1
1
1
2
2
2
2
2
2
2
2
207
225
241
260
207
225
241
260
203
219
234
251
227
245
260
277
96
225
250
300
300
225
250
300
300
225
250
250
300
250
250
300
300
110
110
125
150
125
125
150
150
175
175
175
200
80
40
40
208-3-60
4
37.2
239
58.0
4
4.5
80
80
80
80
40
40
40
40
230-3-60
4
37.2
239
58.0
4
4.5
80
80
80
80
40
40
104
111
120
114
122
130
139
147
156
164
172
71
40
40
80
80
460-3-60
4
17.2
125
27.0
4
2.2
80
80
108
108
108
108
40
40
78
90
40
84
100
110
100
110
125
125
150
150
150
150
40
90
80
91
80
98
575-3-60
4
12.4
80
19.3
4
1.7
80
104
111
118
125
131
138
80
108
108
108
108
1.
Minimum Circuit Ampacity.
2.
3.
Dual Element, Time Delay Type.
HACR type per NEC
Johnson Controls Unitary Products
65
246653-YTG-E-0108
TABLE 51: ELECTRICAL DATA 25 TON WITH POWER EXHAUST R22
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
SUPPLY BLOWER
PWR EXH MOTOR
1
2
MCA
/
VOLTAGE
3
(AMPS)
QTY.
RLA
LRA
MCC
QTY
FLA
HP
FLA
HP
FLA
5
7.5
10
5
16.7
24.2
30.8
16.7
24.2
30.8
16.7
24.2
30.8
16.7
24.2
30.8
15.2
22.0
28.0
15.2
22.0
28.0
15.2
22.0
28.0
15.2
22.0
28.0
7.6
154
161
168
160
168
175
177
184
191
193
201
207
149
156
162
155
162
168
169
176
182
184
191
197
67
175
200
200
200
200
200
200
225
225
250
250
250
175
175
200
175
200
200
200
200
200
225
225
250
80
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
24.2
30.8
46.2
59.4
22.0
28.0
42.0
54.0
11.0
14.0
21.0
27.0
9.0
7.5
10
5
208-3-60
2
42.3
245
66.0
4
3.8
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
230-3-60
2
2
2
42.3
17.6
14.2
245
125
100
66.0
27.5
22.2
4
4
4
3.8
1.9
1.5
7.5
10
5
7.5
10
5
7.5
10
5
11.0
14.0
7.6
70
80
73
90
70
80
7.5
10
5
11.0
14.0
7.6
73
90
76
90
460-3-60
78
90
7.5
10
5
11.0
14.0
7.6
81
100
100
110
110
110
60
84
85
7.5
10
5
11.0
14.0
6.1
89
92
54
7.5
10
5
9.0
57
70
11.0
6.1
59
70
56
70
11.0
17.0
22.0
7.5
10
5
9.0
59
70
11.0
6.1
61
70
575-3-60
63
70
7.5
10
5
9.0
65
80
11.0
6.1
67
80
69
90
7.5
10
9.0
72
90
11.0
74
90
1.
Minimum Circuit Ampacity.
Dual Element, Time Delay Type.
HACR type per NEC
2.
3.
66
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 52: ELECTRICAL DATA 30 TON WITH POWER EXHAUST R22
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
SUPPLY BLOWER
PWR EXH MOTOR
1
2
MCA
/
VOLTAGE
3
(AMPS)
QTY.
RLA
LRA
MCC
QTY
FLA
HP
FLA
HP
FLA
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
9.0
189
196
214
207
214
229
224
230
246
243
249
265
184
190
205
199
205
219
214
220
234
232
238
252
87
225
225
250
250
250
250
250
250
300
300
300
300
200
225
225
225
225
250
250
250
250
250
300
300
100
100
110
110
110
125
125
125
125
125
125
150
70
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
30.8
46.2
59.4
74.8
28.0
42.0
54.0
68.0
14.0
21.0
27.0
34.0
11.0
17.0
22.0
27.0
208-3-60
3
37.2
239
58.0
3
4.5
230-3-60
3
3
3
37.2
17.2
12.4
239
125
80
58.0
27.0
19.3
3
3
3
4.5
2.2
1.7
90
98
95
98
105
103
106
113
112
115
122
65
460-3-60
11.0
17.0
9.0
67
70
75
90
73
80
11.0
17.0
9.0
75
90
81
90
575-3-60
79
100
100
100
110
110
110
11.0
17.0
9.0
81
87
85
11.0
17.0
87
93
1.
Minimum Circuit Ampacity.
Dual Element, Time Delay Type.
HACR type per NEC
2.
3.
Johnson Controls Unitary Products
67
246653-YTG-E-0108
TABLE 53: ELECTRICAL DATA 40 TON WITH POWER EXHAUST R22
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
SUPPLY BLOWER
PWR EXH MOTOR
1
2
MCA
/
VOLTAGE
3
(AMPS)
QTY.
RLA
LRA
MCC
QTY
FLA
HP
FLA
HP
FLA
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
9.0
231
238
255
249
255
271
265
272
287
285
291
307
225
231
247
241
247
261
256
262
276
273
279
293
107
110
118
115
118
125
122
125
132
131
134
141
80
250
250
300
250
300
300
300
300
300
350
350
350
250
250
250
250
250
300
300
300
300
300
300
350
110
125
125
125
125
125
125
150
150
150
150
150
90
10
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
30.8
46.2
59.4
74.8
28.0
42.0
54.0
68.0
14.0
21.0
27.0
34.0
11.0
17.0
22.0
27.0
208-3-60
4
37.2
239
58.0
4
4.5
230-3-60
4
4
4
37.2
17.2
12.4
239
125
80
58.0
27.0
19.3
4
4
4
4.5
2.2
1.7
460-3-60
11.0
17.0
9.0
82
90
89
100
100
100
110
110
110
110
125
125
125
87
11.0
17.0
9.0
89
95
575-3-60
93
11.0
17.0
9.0
95
101
99
11.0
17.0
101
107
1.
Minimum Circuit Ampacity.
Dual Element, Time Delay Type.
HACR type per NEC
2.
3.
68
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 54: ELECTRICAL DATA 25 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
ELECTRIC HEAT
SUPPLY BLOWER
PWR EXH MOTOR
1
2
MCA
/
VOLTAGE
3
(AMPS)
OPTION KW STAGES QTY. RLA LRA MCC
QTY
FLA
HP
FLA
HP
FLA
5
7.5
10
5
16.7
24.2
30.8
16.7
24.2
30.8
16.7
24.2
30.8
16.7
24.2
30.8
16.7
24.2
30.8
16.7
24.2
30.8
16.7
24.2
30.8
16.7
24.2
30.8
15.2
22.0
28.0
15.2
22.0
28.0
15.2
22.0
28.0
15.2
22.0
28.0
15.2
22.0
28.0
15.2
22.0
28.0
15.2
22.0
28.0
15.2
22.0
28.0
154
161
168
160
168
175
179
186
193
195
203
209
214
221
229
222
229
236
241
249
255
258
265
272
163
170
177
170
177
183
188
195
201
203
210
216
235
242
249
243
249
255
260
267
273
275
282
288
175
200
200
200
200
200
200
225
225
250
250
250
225
225
250
250
250
250
250
250
300
300
300
300
175
175
200
175
200
200
200
200
225
225
225
250
250
250
250
250
250
300
300
300
300
300
300
300
7.5
24.2
10
15
20
7.5
10
15
20
7.5
10
15
20
7.5
10
15
20
30.8
46.2
59.4
24.2
30.8
46.2
59.4
22.0
28.0
42.0
54.0
22.0
28.0
42.0
54.0
7.5
10
5
E4
E8
E4
E8
40
80
40
80
1
2
1
2
2
2
2
2
42.3 245 66.0
42.3 245 66.0
42.3 245 66.0
42.3 245 66.0
4
3.8
7.5
10
5
7.5
10
5
208-3-60
7.5
10
5
7.5
10
5
4
4
4
3.8
3.8
3.8
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
5
230-3-60
7.5
10
5
7.5
10
5
7.5
10
5
7.5
10
Johnson Controls Unitary Products
69
246653-YTG-E-0108
TABLE 54: ELECTRICAL DATA 25 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22 (CONTINUED)
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
ELECTRIC HEAT
SUPPLY BLOWER
PWR EXH MOTOR
1
2
MCA
/
VOLTAGE
3
(AMPS)
OPTION KW STAGES QTY. RLA LRA MCC
QTY
FLA
HP
FLA
HP
FLA
5
7.5
10
5
7.6
11.0
14.0
7.6
81
90
7.5
11.0
85
90
89
90
85
90
10
15
20
7.5
10
15
20
7.5
10
15
20
14.0
21.0
27.0
11.0
14.0
21.0
27.0
11.0
14.0
21.0
27.0
7.5
10
5
11.0
14.0
7.6
89
90
92
100
100
100
110
110
110
110
125
125
125
125
125
150
150
150
150
150
150
150
175
175
175
175
175
175
175
175
175
175
200
200
E4
E8
E1
40
1
2
2
2
2
2
17.6 125 27.5
17.6 125 27.5
17.6 125 27.5
4
1.9
94
7.5
10
5
11.0
14.0
7.6
97
100
101
105
108
118
121
125
121
125
128
130
133
136
138
141
144
151
155
158
155
158
161
164
167
170
171
175
178
7.5
10
5
11.0
14.0
7.6
7.5
10
5
11.0
14.0
7.6
7.5
10
5
11.0
14.0
7.6
460-3-60
80
4
1.9
7.5
10
5
11.0
14.0
7.6
7.5
10
5
11.0
14.0
7.6
7.5
10
5
11.0
14.0
7.6
7.5
10
5
11.0
14.0
7.6
108
4
1.9
7.5
10
5
11.0
14.0
7.6
7.5
10
11.0
14.0
70
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 54: ELECTRICAL DATA 25 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22 (CONTINUED)
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
ELECTRIC HEAT
SUPPLY BLOWER
PWR EXH MOTOR
1
2
MCA
/
VOLTAGE
3
(AMPS)
OPTION KW STAGES QTY. RLA LRA MCC
QTY
FLA
HP
FLA
HP
FLA
5
7.5
10
5
6.1
9.0
65
68
70
70
7.5
9.0
11.0
6.1
71
80
68
70
10
15
20
7.5
10
15
20
7.5
10
15
20
11.0
17.0
22.0
9.0
7.5
10
5
9.0
71
80
11.0
6.1
73
80
E4
E8
E1
40
1
2
2
2
2
2
14.2 100 22.2
14.2 100 22.2
14.2 100 22.2
4
1.5
75
80
7.5
10
5
9.0
78
80
11.0
6.1
80
90
82
90
7.5
10
5
9.0
85
90
11.0
6.1
87
90
94
100
100
110
100
110
110
110
110
125
125
125
125
150
150
150
150
150
150
150
150
150
150
150
150
7.5
10
5
9.0
97
11.0
6.1
100
97
11.0
17.0
22.0
9.0
7.5
10
5
9.0
100
102
104
107
109
111
113
115
121
124
127
124
127
129
131
134
136
138
140
142
11.0
6.1
575-3-60
80
4
1.5
7.5
10
5
9.0
11.0
6.1
7.5
10
5
9.0
11.0
6.1
7.5
10
5
9.0
11.0
6.1
11.0
17.0
22.0
7.5
10
5
9.0
11.0
6.1
108
4
1.5
7.5
10
5
9.0
11.0
6.1
7.5
10
9.0
11.0
1.
Minimum Circuit Ampacity.
2.
3.
Dual Element, Time Delay Type.
HACR type per NEC
Johnson Controls Unitary Products
71
246653-YTG-E-0108
TABLE 55: ELECTRICAL DATA 30 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
ELECTRIC HEAT
SUPPLY BLOWER
PWR EXH MOTOR
1
2
MCA
/
VOLTAGE
3
(AMPS)
OPTION KW STAGES QTY. RLA LRA MCC
QTY
FLA
HP
FLA
HP
FLA
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
189
196
214
207
214
229
224
230
246
243
249
265
229
236
255
249
255
271
265
272
287
284
291
306
184
190
205
199
205
219
214
220
234
232
238
252
249
255
273
267
273
287
282
288
302
299
305
319
225
225
250
250
250
250
250
250
300
300
300
300
250
250
300
250
300
300
300
300
300
350
350
350
200
225
225
225
225
250
250
250
250
250
300
300
250
300
300
300
300
300
300
300
350
350
350
350
10
30.8
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
46.2
59.4
74.8
30.8
46.2
59.4
74.8
28.0
42.0
54.0
68.0
28.0
42.0
54.0
68.0
E4
E8
E4
E8
40
80
40
80
1
2
1
2
3
3
3
3
37.2 239 58.0
37.2 239 58.0
37.2 239 58.0
37.2 239 58.0
3
5.8
208-3-60
3
3
3
5.8
5.8
5.8
230-3-60
72
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 55: ELECTRICAL DATA 30 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22 (CONTINUED)
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
ELECTRIC HEAT
SUPPLY BLOWER
PWR EXH MOTOR
1
2
MCA
/
VOLTAGE
3
(AMPS)
OPTION KW STAGES QTY. RLA LRA MCC
QTY
FLA
HP
FLA
HP
FLA
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
89
100
100
110
110
110
125
125
125
125
125
125
150
125
150
150
150
150
150
150
150
175
175
175
175
175
175
175
175
175
200
200
200
200
200
200
225
10
14.0
92
100
97
15
20
25
10
15
20
25
10
15
20
25
21.0
27.0
34.0
14.0
21.0
27.0
34.0
14.0
21.0
27.0
34.0
100
107
105
108
115
114
117
124
125
128
136
133
136
143
141
144
151
150
153
160
158
161
170
167
170
177
175
178
185
183
186
193
E4
E8
E1
40
1
2
2
3
3
3
17.2 125 27.0
17.2 125 27.0
17.2 125 27.0
3
2.2
460-3-60
80
3
2.2
108
3
2.2
Johnson Controls Unitary Products
73
246653-YTG-E-0108
TABLE 55: ELECTRICAL DATA 30 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22 (CONTINUED)
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
ELECTRIC HEAT
SUPPLY BLOWER
PWR EXH MOTOR
1
2
MCA
/
VOLTAGE
3
(AMPS)
OPTION KW STAGES QTY. RLA LRA MCC
QTY
FLA
HP
FLA
HP
FLA
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
9.0
11.0
17.0
9.0
71
73
80
10
11.0
80
80
90
78
80
15
20
25
10
15
20
25
10
15
20
25
17.0
22.0
27.0
11.0
17.0
22.0
27.0
11.0
17.0
22.0
27.0
11.0
17.0
9.0
80
90
86
90
E4
E8
E1
40
1
2
2
3
3
3
12.4
12.4
12.4
80
80
80
19.3
19.3
19.3
3
1.7
85
100
100
100
110
110
110
110
110
125
110
125
125
125
125
125
125
125
150
150
150
150
150
150
150
150
150
150
150
175
175
11.0
17.0
9.0
87
93
91
11.0
17.0
9.0
93
99
100
102
109
107
109
115
113
115
121
120
122
128
127
129
136
134
136
142
140
142
148
147
149
155
11.0
17.0
9.0
11.0
17.0
9.0
575-3-60
80
3
1.7
11.0
17.0
9.0
11.0
17.0
9.0
11.0
17.0
9.0
11.0
17.0
9.0
108
3
1.7
11.0
17.0
9.0
11.0
17.0
1.
Minimum Circuit Ampacity.
2.
3.
Dual Element, Time Delay Type.
HACR type per NEC
74
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 56: ELECTRICAL DATA 40 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
ELECTRIC HEAT
SUPPLY BLOWER
PWR EXH MOTOR
1
2
MCA
/
VOLTAGE
3
(AMPS)
OPTION KW STAGES QTY. RLA LRA MCC
QTY
FLA
HP
FLA
HP
FLA
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
24.2
30.8
46.2
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
22.0
28.0
42.0
231
238
255
249
255
271
265
272
287
285
291
307
231
238
255
249
255
271
265
272
287
285
291
307
225
231
247
241
247
261
256
262
276
273
279
293
249
255
273
267
273
287
282
288
302
299
305
319
250
250
300
250
300
300
300
300
300
350
350
350
250
250
300
250
300
300
300
300
300
350
350
350
250
250
250
250
250
300
300
300
300
300
300
350
250
300
300
300
300
300
300
300
350
350
350
350
10
30.8
15
20
25
10
15
20
25
10
15
20
25
10
15
20
25
46.2
59.4
74.8
30.8
46.2
59.4
74.8
28.0
42.0
54.0
68.0
28.0
42.0
54.0
68.0
E4
E8
E4
E8
40
80
40
80
1
2
1
2
4
4
4
4
37.2 239 58.0
37.2 239 58.0
37.2 239 58.0
37.2 239 58.0
4
4.5
208-3-60
4
4
4
4.5
4.5
4.5
230-3-60
Johnson Controls Unitary Products
75
246653-YTG-E-0108
TABLE 56: ELECTRICAL DATA 40 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22 (CONTINUED)
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
ELECTRIC HEAT
SUPPLY BLOWER
PWR EXH MOTOR
1
2
MCA
/
VOLTAGE
3
(AMPS)
OPTION KW STAGES QTY. RLA LRA MCC
QTY
FLA
HP
FLA
HP
FLA
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
11.0
14.0
21.0
107
110
118
115
118
125
122
125
132
131
134
141
125
128
136
133
136
143
141
144
151
150
153
160
158
161
170
167
170
177
175
178
185
183
186
193
110
125
125
125
125
125
125
150
150
150
150
150
125
150
150
150
150
150
150
150
175
175
175
175
175
175
175
175
175
200
200
200
200
200
200
225
10
14.0
15
20
25
10
15
20
25
10
15
20
25
21.0
27.0
34.0
14.0
21.0
27.0
34.0
14.0
21.0
27.0
34.0
E4
E8
E1
40
1
2
2
4
4
4
17.2 125 27.0
17.2 125 27.0
17.2 125 27.0
4
2.2
460-3-60
80
4
2.2
108
4
2.2
76
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 56: ELECTRICAL DATA 40 TON WITH ELECTRIC HEAT AND POWER EXHAUST R22 (CONTINUED)
COMPRESSORS
(EACH)
OD FAN MOTORS
(EACH)
MAX
FUSE
BREAKER
SIZE
ELECTRIC HEAT
SUPPLY BLOWER
PWR EXH MOTOR
1
2
MCA
/
VOLTAGE
3
(AMPS)
OPTION KW STAGES QTY. RLA LRA MCC
QTY
FLA
HP
FLA
HP
FLA
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
9.0
11.0
17.0
9.0
80
90
10
11.0
82
90
89
100
100
100
110
110
110
110
125
125
125
110
110
125
110
125
125
125
125
125
125
125
150
150
150
150
150
150
150
150
150
150
150
175
175
87
15
20
25
10
15
20
25
10
15
20
25
17.0
22.0
27.0
11.0
17.0
22.0
27.0
11.0
17.0
22.0
27.0
11.0
17.0
9.0
89
95
E4
E8
E1
40
1
2
2
4
4
4
12.4
12.4
12.4
80
80
80
19.3
19.3
19.3
4
1.7
93
11.0
17.0
9.0
95
101
99
11.0
17.0
9.0
101
107
100
102
109
107
109
115
113
115
121
120
122
128
127
129
136
134
136
142
140
142
148
147
149
155
11.0
17.0
9.0
11.0
17.0
9.0
575-3-60
80
4
1.7
11.0
17.0
9.0
11.0
17.0
9.0
11.0
17.0
9.0
11.0
17.0
9.0
108
4
1.7
11.0
17.0
9.0
11.0
17.0
1.
Minimum Circuit Ampacity.
2.
3.
Dual Element, Time Delay Type.
HACR type per NEC
Johnson Controls Unitary Products
77
246653-YTG-E-0108
TABLE 57: UNIT WEIGHTS
TABLE 58: SUPPLY FAN MOTOR VFD WEIGHTS
Supply Fan Motor VFD
230V
460V
575V
COMPONENT
Basic Unit
25 TON
30 TON
40 TON
4410
Gas Heat
4565
4845
W/O Bypass
7.5hp
60
60
25
25
50
50
50
30
30
60
60
60
267 MBH
533 MBH
800 MBH
180
320
-
180
320
-
180
320
450
10hp
15hp
75
Electric Heat
20hp
75
40KW
80KW
108KW
40
105
110
40
105
110
40
105
110
25hp
115
W/Bypass
7.5hp
Hot Water Heat
155
155
185
185
255
90
90
120
120
155
155
155
1 Row Coil
2 Row Coil
70
85
70
85
70
85
10hp
Steam Heat
85
Blower
15hp
140
140
140
1 Row Coil
85
85
20hp
Forward Curve Fan (Std Fan)
FC IGV
0
0
0
25hp
155
135
155
155
135
155
175
155
180
Air Foil Fan
AF IGV
TABLE 59: EXHAUST FAN MOTOR VFD WEIGHTS
Exhaust Fan Motor
W/O Bypass
230V
460V
575V
Motor - Supply Fan
7.5hp
10hp
15hp
20hp
25hp
110
145
200
240
-
-
-
145
200
240
300
145
200
240
300
5hp
7.5hp
10hp
15hp
15
50
50
65
10
15
15
40
20
20
20
50
Supply Fan Motor VFD
Refrigeration
Hi Cap. Evap. Coil
T-Coat Evap.
T-Coat cond.
-
50
30
30
10
15
40
40
10
NOTE: If the Millennium is VAV with ERV, add the weight of an
exhaust VFD - it will be in the unit.
32
32
10
Hot Gas Bypass
CENTER OF
Low Ambient Head Pressure Control
C
GRAVITY
208-230/380/460
575
5
25
5
25
5
25
BACK
CONDENSER
COIL END
B
Filters
D
6" Rigid
70
70
70
Exhaust1
X
Exhaust Type
92
"
Barometric
Modulated
Exhaust Motor
45
140
65
275
65
275
Y
A
FRONT
240"
5hp
7.5hp
10hp
80
80
110
145
80
110
145
200
110
145
200
FIGURE 27 - CENTER OF GRAVITY
TABLE 60: UNIT CENTER OF GRAVITY
15hp
200
Exhaust Motor VFD
Economizer
25 TON
30 TON
40 TON
X
Std. Econ.
Econ. w/ERV
235
235
50
235
50
MODEL
X
Y
X
Y
Y
50
Control
15
BASIC UNIT
99”
48”
100”
47”
96”
46"
BASIC UNIT /W
ECON.
Disconnect
110V outlet
Optilogic
15
55
20
15
55
20
110”
48”
48”
110”
47”
46”
100”
46"
55
20
BASIC UNIT /W
ECON. & GAS OR
ELECT. HEAT,
STEAM OR HOT
WATER HEAT
104”
118”
104”
114”
99”
45"
45"
Roof Curb
415
Partial Curb
415
415
1.
BASIC UNIT /W
ECON. & GAS OR
ELECT. HEAT, &
POWER EXHAUST
If ERV and Supply Fan VAV are selected, add the weight of an
47”
46”
111”
78
Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 61: UNIT CORNERWEIGHT
25 TON
30 TON
40 TON
UNIT
DESCRIPTION
A
B
C
D
A
B
C
D
A
B
C
D
BASIC UNIT
870
949
1352
1239
930
972
1360
1328
1303
969
969
1454
1454
BASIC UNIT WITH
ECONOMIZER
1018
1111
1313
1203
1076
1124
1272
1058
1058
1482
1482
BASIC UNIT WITH
ECONOMIZER AND
GAS OR ELECTRIC
HEAT
994
1084
1418
1300
1073
1073
1403
1410
1403
1102
1055
1503
1570
BASIC UNIT WITH
ECONOMIZER AND
GAS OR ELECTRIC
HEAT AND POWER
EXHAUST
1220
1275
1318
1262
1275
1275
1410
1335
1278
1485
1551
NOTES:Basic Unit = cooling only, 10hp FC fan.
+ Econ = +235lb
+ Heat = single stage gas, 180 lb
+ Power Exhaust = modulating 7.5hp
TABLE 62: INDOOR SOUND POWER RATING
SOUND POWER (DB 10-12 WATTS)
OCTAVE BAND CENTERLINE FREQUENCY (HZ)
ESP
BLOWER
MODEL NUMBER
CFM
DBA
IWG
1.5
RPM
BHP
63
125
88
250
85
500
85
1000
80
2000
78
4000
74
8000
Y32
Y33
Y34
10,000
12750
17500
750
840
800
7.5
12.8
20
90
93
95
68
71
72
87
90
91
1.5
91
88
88
83
81
77
1.3
92
89
89
84
83
78
Sound Power Ratings for Supply Air Blowers in our Millen-
nium Units with High Gas Heat, Economizer, 2: T/A Filters
and Wet DX Sound power calculations complements of Lau’s
revised “Whirlwind” application selection software for air mov-
ing components.
The sound ratings above occur at the blower wheel. To deter-
mine the sound rating at a unit’s supply and return air duct
connection, subtract the attenuation factors listed below.
TABLE 63: ATTENUATION FACTORS
OCTAVE BAND CENTERLINE FREQUENCY (HZ)
63
125
250
500
1000
12
2000
4000
8000
LOCATION
SOUND ATTENUATION (DB WATTS)
SUPPLY AIR
RETURN AIR
11
13
13
15
18
22
10
23
21
25
21
25
23
29
23
29
TABLE 64: OUTDOOR SOUND POWER RATING
OCTAVE BAND CENTERLINE FREQUENCY (HERTZ)
MODEL
65
125
250
500
1000
2000
4000
8000
db(A)
SOUND POWER LEVEL, DB (10)-12 WATTS
Y32
Y33
Y34
88
87
88
91
90
91
89
88
89
86
86
86
82
82
82
79
80
80
76
77
77
72
73
73
88
88
88
NOTE: These values have been accessed using a model of
sound propagation from a point source into the
hemispheric free field (AMCA 303-79). The dBA val-
ues provided are to be used for reference only. Cal-
culation of dBA values cover matters of system
design, and the fan manufacturer has no way of
knowing the details of each system. This constitutes
an exception to any specification or guarantee
requiring a dBA value or sound data in any other
form than sound power level ratings.
Johnson Controls Unitary Products
79
246653-YTG-E-0108
EVAPORATOR COIL
AND DRAINPAN ACCESS
POWER & CONTROL WIRING
FILTER ACCESS
COMPRESSOR ACCESS
REAR
RIGHT
SIDE
HEAT SECTION
FRONT
LEFT SIDE
POWER EXHAUST ACCESS
HEAT SECTION
EVAPORATOR COIL
AND DRAINPAN ACCESS
FILTER DRIERS
FILTER ACCESS
REAR
SUPPLY BLOWER & MOTOR
FIGURE 28 - COMPONENT LOCATION
80
Johnson Controls Unitary Products
246653-YTG-E-0108
NOTE:
RETURN AIR
SUPPLY AIR
FACTORY INSTALLED POWER
EXHAUST CANNOT BE ORDERED
WITH END RETURN.
REAR
RIGHT SIDE
SEE
DETAIL
C
SEE
DETAIL
B
7-7/8"
64"
75.6"
24.9"
6.25"
100.10"
128.50"
8.15"
76-3/8
92"
LEFT SIDE
FRONT
RIGHT
SIDE
4.5"
REAR
OPEN
3.625"
80.93"
26"
SEE
DETAIL
A
71.61"
12"
MIN
6.46"
15.89"
C
L
88.7"
FRONT
LEFT SIDE
240"
TO GAS VALVE
MANIFOLD
2-1/2”
DIA. HOLES
3-5/8"
4-5/8”
7”
28”
BASE RAIL
6.46"
3-1/16"
11”
BASE RAIL
2-1/2"
1-1/2" FPT
1-1/4” NPT
DETAIL B
(ELECTRICAL CONNECTION)
DETAIL A
DETAIL C
(GAS CONNECTION
THROUGH CURB)
(DRAIN CONNECTION)
FOR COOLING ONLY AND ALL HEATING APPLICATIONS
FIGURE 29 - END RETURN, BOTTOM SUPPLY
Johnson Controls Unitary Products
81
246653-YTG-E-0108
RETURN AIR
SUPPLY AIR
REAR
RIGHT
SIDE
SEE
DETAIL
C
SEE
DETAIL
B
64"
100.10"
128.50"
FRONT
92"
LEFT
SIDE
RIGHT
SIDE
REAR
4.5"
OPEN
3.625"
80.93"
4.5"
SEE
DETAIL
A
26"
71.61"
6.46"
12"
MIN
15.89"
88.7"
38.59"
127.5"
83"
FRONT
LEFT
SIDE
C
240"
L
C
L
4.5"
TO GAS VALVE
MANIFOLD
2-1/2”
DIA. HOLES
3-5/8"
4-5/8”
7”
BASE RAIL
28”
6.46"
3-1/16"
BASE RAIL
11”
1-1/4" FPT
1-1/2" FPT
1-1/4” NPT
DETAIL B
(ELECTRICAL CONNECTION)
DETAIL A
(DRAIN CONNECTION)
DETAIL C
(GAS CONNECTION
THROUGH CURB)
FOR COOLING ONLY AND ALL HEATING APPLICATIONS
FIGURE 30 - BOTTOM SUPPLY AND RETURN
82
Johnson Controls Unitary Products
246653-YTG-E-0108
FRONT SUPPLY: FOR COOLING ONLY APPLICATIONS
REAR SUPPLY: FOR COOLING ONLY OR GAS HEAT APPLICATIONS
FRONT
REAR
RETURN AIR
SUPPLY AIR
REAR
RIGHT SIDE
26"
55"
64"
75.6"
100.10"
8.15"
SEE
128.50"
DETAIL
92"
B
SEE
DETAIL
C
FRONT
LEFT SIDE
RIGHT
SIDE
REAR
OPEN
3.625"
80.93"
4.5"
SEE
DETAIL
A
12"
MIN
6.46"
TO GAS VALVE
MANIFOLD
38.59"
83"
FRONT
2-1/2”
DIA. HOLES
240"
LEFT SIDE
4.5"
3-5/8"
4-5/8”
7”
28”
BASE RAIL
6.46"
3-1/16"
11”
BASE RAIL
2-1/2"
1-1/2" FPT
1-1/4” NPT
DETAIL C
(GAS CONNECTION
THROUGH CURB)
DETAIL B
(ELECTRICAL CONNECTION)
DETAIL A
(DRAIN CONNECTION)
FIGURE 31 - BOTTOM RETURN, FRONT & REAR SUPPLY
Johnson Controls Unitary Products
83
246653-YTG-E-0108
FRONT SUPPLY: FOR COOLING ONLY APPLICATIONS
REAR SUPPLY: FOR COOLING ONLY OR GAS HEAT APPLICATIONS
26"
55"
REAR
RETURN AIR
SUPPLY AIR
REAR
RIGHT
SIDE
26"
55"
7-7/8"
64"
75.6"
100.10"
24.9"
6.25"
8.15"
76-3/8
92"
128.50"
SEE
DETAIL
B
SEE
LEFT
SIDE
FRONT
DETAIL
C
RIGHT
SIDE
REAR
OPEN
3.625"
80.93"
SEE
DETAIL
A
12"
MIN
6.46"
FRONT
TO GAS VALVE
MANIFOLD
LEFT
SIDE
240"
2-1/2”
DIA. HOLES
3-5/8"
7”
4-5/8”
28”
BASE RAIL
11”
6.46"
3-1/16"
1-1/4” NPT
1-1/2" FPT
2-1/2"
BASE RAIL
DETAIL C
(GAS CONNECTION
THROUGH CURB)
DETAIL A
(DRAIN CONNECTION)
DETAIL B
(ELECTRICAL CONNECTION)
FIGURE 32 - END RETURN, FRONT & REAR SUPPLY
84
Johnson Controls Unitary Products
246653-YTG-E-0108
Hinged,
Tool-Free
Door
Optional
Hinged,
Tool-Free
Door
Hinged,
Tool-Free
Door
Hinged, Tool-Free
w/PE Option
1
2
3
4
BACK VIEW
Hinged,
Tool-Free
Door
Optional
Hinged,
Tool-Free
Door
Hinged,
Tool-Free
Door
Hinged,
Tool-Free
w/Gas
or Other
Heat Source
Hinged, Tool-Free
w/PE Option
5
6
7
8
9
FRONT VIEW
1. STD Cabinet Option includes Hinged, Tool-Free
Doors # 1, 3, 6, 8.
4. Doors 1, 2, 3, 6, 7, 8 & 9 are 56.31 inches high by
27.33 inches wide.
2. Premium Cabinet Option includes Hinged, Tool-Free
Doors # 1, 2, 3, 6, 7, 8.
5. Doors 4 & 5 are 26.5 inches high by 33.63 inches
wide.
3. Doors # 4, 5, 9 are dependent upon unit Heating
and Power Exhaust Options.
FIGURE 35 - MILLENNIUM CABINET DOOR CONFIGURATION
86
Johnson Controls Unitary Products
246653-YTG-E-0108
2
3
5
.
0
0
9
5
.
0
9
3
8
.
5
9
2
6
.
0
0
7
1
.
6
1
R
E
T
U
R
N
S
U
P
P
L
Y
8
3
.
0
0
A
I
R
A
I
R
O
P
E
N
I
N
G
O
P
E
N
I
N
G
8
7
.
0
0
1
1
.
3
9
4
.
0
0
2
.
0
0
1
4
.
0
0
I
n
s
u
l
a
t
i
o
n
E
d
g
e
P
r
o
t
e
c
t
o
r
(
S
h
e
e
t
M
e
t
a
l
N
o
s
e
P
i
e
c
e
)
A
A
F
I
E
L
D
S
U
P
P
L
I
E
D
T
y
p
i
c
a
l
I
n
s
u
l
a
t
i
o
n
D
U
C
T
A
B
A
B
-
-
I
I
F
F
U
U
N
N
I
I
T
T
I
I
S
S
N
A
O
T
I
N
S
T
A
L
L
E
D
S
E
E
S
E
C
T
I
O
N
"
A
-
A
"
L
R
E
A
D
Y
I
N
S
T
A
L
L
E
D
N
O
T
E
:
P
r
o
t
e
c
t
i
n
s
u
l
a
t
i
o
l
n
w
i
t
h
a
s
h
e
e
t
m
e
t
a
l
n
d
o
u
s
c
e
t
p
i
e
c
k
e
.
w
h
e
n
i
n
s
t
a
l
i
n
g
a
i
n
t
e
r
n
a
l
l
y
i
n
s
u
l
a
t
e
d
w
o
r
T
Y
P
I
C
A
L
D
U
C
T
I
N
S
T
A
L
L
A
T
I
O
N
S
B
A
S
E
R
A
I
L
B
A
S
E
R
A
I
L
C
R
O
S
S
-
S
E
C
T
I
O
N
(
Y
O
R
K
U
N
I
T
)
1
.
2
5
"
C
U
R
B
G
A
S
K
E
T
1
.
7
5
"
4
.
6
3
"
2
.
5
0
"
1
.
5
0
"
2
"
X
4
"
N
A
I
L
E
R
(
1
4
.
0
0
)
2
.
0
0
"
1
4
G
A
.
G
A
L
V
S
T
E
E
L
R
O
O
F
C
U
R
B
S
E
C
T
I
O
N
"
A
-
A
"
FIGURE 38 - PARTIAL ROOF CURB MODEL 1RC0455P
88
Johnson Controls Unitary Products
246653-YTG-E-0108
meet NFPA-90A regulations for smoke and flame spread rat-
ings. The cabinet corner post and the intermediate side sup-
ports shall be 16 gauge steel. All access doors shall be 18
gauge on the exterior surfaces, and 20 gauge on the interior.
Floor shall be 18 gauge, and 24 gauge. All serviceable sec-
tions shall have hinged access doors with latches on both
sides of the unit. All access doors shall be constructed of 20
gauge steel on the outside, with 24 gauge on the inside. Each
door shall seal against a rubber gasket to prevent air and
water leakage. The roof shall be double wall, with 18 gauge
on the external surface and 24 gauge on the interior. The roof
shall be formed with a 45 degree drip lip overhanging the
sidewalls to prevent precipitation drainage from streaming
down the side of the unit. Roof sections shall be connected
together via integral channels fastened with screws and
sealed with rubber gasketing. Each fastened seam shall be
further protected by a sheet metal channel covering the full
length of the gasket surface, making a completely water tight
seal.
GUIDE SPECIFICATIONS - YORK
MILLENNIUM 25, 30, & 40 TON UNITS
GENERAL
Units shall be manufactured by Johnson Controls Unitary
Products in an ISO 9001 certified facility. Introducing the
YORK Millennium 25, 30, & 40 ton rooftop line - units
designed to provide peak performance and value both today
and for years to come. Millennium units are manufactured at
an ISO 9001 registered facility, and each rooftop is com-
pletely computer-run tested prior to shipment. The Millennium
is designed to be flexible enough to meet your needs today
and in the future. The true value of York's Millennium is that it
can be designed to fit any need, from cooling only, constant
volume applications to variable air volume systems with vari-
able frequency drive.
DESCRIPTION
SUPPLY AIR SYSTEM
SUPPLY AIR FAN
Supply York Millennium packaged rooftop system in accor-
dance with the capacities in the plans. Units shall be rated by
the manufacturer at a minimum (30/40 Ton units: 9.5 EER /
25 Ton units: 10 EER) according to ARI 360. Units shall be
shipped in a single package, fully charged with R-22 refriger-
ant. The manufacturing facility shall be registered under ISO
9001 Quality Standards for Manufacturing. Units shall carry
both ETL and CSA safety approval ratings. Tags and decals
to aid in the service or indicate caution areas shall be pro-
vided. Installation and maintenance manuals shall be sup-
plied with each unit. Units shall be capable of providing
mechanical cooling down to 40°F (0°F with low ambient kit).
Unit shall be capable of starting and running at 125°F. Unit
electric and gas connections shall be either through the curb
or the side of the unit.
Fans shall be centrifugal type - Class I or Class II, statically
and dynamically balanced in the factory. Fan wheels shall be
designed for continuous operation at the maximum rate of fan
speed and motor HP. The fan and motor assembly shall be
mounted on a common base to allow consistent belt tension
with no relative motion between the fan and motor shafts.
The entire assembly shall be isolated from the unit base with
(optional 1”, 2" deflection springs or rubber isolators). The fan
discharge shall be connected to the cabinet through a rein-
forced neoprene flexible connection to eliminate vibration
transmission from the fan to the unit casing. Fans shall be
double-width, double-inlet with forward curved blades.
OPTIONAL
CONSTRUCTION
Base
On variable air volume units without variable frequency
drives, fans shall be provided with heavy gauge, corrosion
resistant blades, with zinc-plated steel inter-locking operating
mechanism. Both inlet vanes must operate from a single
shaft and be synchronized for precise control.
The base rail shall be constructed of 12 gauge galvanized
steel, extending the full perimeter of the unit. All components
shall be supported from the base, and the base shall include
integral lifting lugs. The unit base rail shall overhang the roof
curb for water runoff and shall have a fabricated recess with a
continuous flat surface to seat on the roof curb gasket, pro-
viding a positive, weather tight seal between the unit and the
curb.
Units equipped with variable frequency drive on supply fan
must be controlled by a duct static transducer providing a 2-
10 VDC signal to the drive. Supply fan variable frequency
drives shall have factory option of being equipped with a
manual drive bypass.
Casing
BEARINGS AND DRIVES
The unit cabinet shall be double wall construction to provide
both maximum resistance to bacterial growth in the air stream
and superior structural integrity. All sheet metal shall be G90
mill galvanized sheet metal, formed and reinforced to provide
a rigid assembly. Sheet metal shall be cleaned in an alkaline
and zinc phosphate bath, and the exterior surfaces shall be
coated with a 1.5 mil powder paint, capable of withstanding
1000 salt spray hours in accordance with ASTM B-117. The
unit shall be insulated with 1-1/2", 1 pound density fiberglass
insulation between the two sheet metal skins. Insulation shall
Bearings shall be self-aligning pillow-block re-greasable ball
bearings with an average life expectancy of 200,000 hours.
Grease fittings shall be accessible through access doors. Fan
motors shall be NEMA designed, Standard efficiency (option,
Hi-efficiency) ball bearing type with electrical characteristics
and horsepower as specified. Motors shall be 1750 RPM,
open drip proof type. The motor shall be located within the
unit on an adjustable, heavy steel base. All fan motor drives
Johnson Controls Unitary Products
89
246653-YTG-E-0108
shall be selected for a minimum service factor of 1.2 and
have fixed pitched sheaves.
Barometric Relief (Optional)
Building air exhaust shall be accomplished through baromet-
ric relief dampers installed in the return air plenum. The
dampers will open relative to the building pressure. The
opening pressure shall be adjustable.
AIR FILTERING SYSTEM
All filter holding frames shall be of heavy duty construction
designed for industrial applications. All filters shall be either
side accessible or front loading with access doors provided
on both sides of the filter section. All filter media shall be
Class II listed under UL Standard 900. Filter efficiencies shall
be rated in accordance with ASHRAE Standard 52-76 2"
Throwaway Filters with fiberglass media multiple shall be
standard
Exhaust Air Fans (Optional)
General - forward curved centrifugal fan(s) shall be installed
in the return air plenum for positive power exhaust. Fans shall
be on a common shaft, driven by a single motor. The fans,
motors and drives shall be of the same quality and design as
specified for the Supply Air Fan, except the fans shall be
Class I. Fans shall be capable of exhausting up to 100% of
the nominal CFM of the unit. Non-modulating Exhaust - Units
with non-modulating power exhaust shall have a barometric
relief damper to prevent outside air from entering in the off
cycle. The fans shall cycle on and off with building pressure.
Modulating Operation - The fans shall be capable of modulat-
ing the amount of air from 0% to 100% of nominal CFM. Mod-
ulation shall be through discharge dampers or variable
frequency motor speed modulation. Dampers or VFD shall be
controlled by static pressure in the conditioned space or
return air duct.
OPTIONAL
Two inch pleated, throwaway filters with 30% efficiency. Rigid
filters shall be high performance, expanded area, disposable
type filters. Rigid filter sections shall be preceded by a 2
throwaway prefilter assembly. Filter efficiency shall be 95%
(Option: 65%) based on ASHRAE Standard 52-76.
AIR INLET SYSTEM
General
ENERGY RECOVERY VENTILATION (FIELD
INSTALLED OPTION)
Outside Air inlet openings shall be covered by a factory
installed rain hood permanently attached to the cabinet to
prevent windblown precipitation from entering the unit. The
rain hoods on the front and back of the unit shall be rotated
into the cabinet and secured for shipment so that upon instal-
lation they need only be rotated upwards and screwed into
place. The outside air hood shall contain a removable and
cleanable filter with an efficiency rating of 50% based on
ASHRAE 52- 76. All damper assemblies shall be of low leak
design. Damper blades shall be fabricated from a minimum of
16 gauge galvanized steel. Blade ends and edges shall be
covered with vinyl seals. Damper shafts shall be fabricated
from solid steel and mounted in the frame with bronze bear-
ings. On all units not equipped with an economizer, an option
shall be available for a manually adjustable outside air
damper shall be capable of admitting 0-25% outside air.
General
The packaged rooftop unit shall have attached at the jobsite a
powered exhaust combined with an air intake through a rotat-
ing energy recovery wheel, which captures sensible and
latent heat from the exhaust air stream and returns it to the
incoming air stream. The energy recovery module will be con-
tained in a separate enclosure designed to attach to the end
of the Millennium packaged rooftop unit equipped with Sim-
plicity® Elite™ control.
The Energy Recovery Ventilation module will be capable of
exhausting up to 8,000 (13,000) CFM.
Control parameters for the ERV will be preset in the unit con-
trol.
Economizer (Optional)
An economizer shall have outdoor air and return air dampers
(optional standard or low leak type) that are interlocked and
positioned by fully modulating, solid state damper actuators.
The actuators shall be spring loaded so that the outside air
damper will close when power to the unit is interrupted. The
operation of the economizer shall be fully integrated into the
cooling control system. The economizer shall be available for
control via a dry bulb sensor (Optional: single or dual
enthalpy sensors).
HEATING SYSTEM (OPTIONAL)
Gas-fired Heating Section
One or more gas-fired heating modules shall be installed to
provide the heating requirements per the schedule shown on
the plans. The heat exchanger shall be of tubular design.
Tubes shall be 2-1/4" OD and constructed of minimum 20
gauge, G160 aluminized steel (1.6 mil aluminum silicone
alloy) for corrosion resistance (Optional: 409 Stainless Steel).
Flue baffles shall be made of 430 stainless steel. Each gas-
fired heat module shall have an induced draft combustion fan
with energy efficient intermittent pilot spark ignition and
redundant main gas valves with pressure regulator. Units with
standing pilot ignition shall not be acceptable. An induced
draft fan shall be provided to maintain a positive flow of air
RELIEF SYSTEM (Optional)
All units with relief must have an economizer.
90
Johnson Controls Unitary Products
246653-YTG-E-0108
through each tube, to expel the flue gas and to maintain a
negative pressure within the heat exchanger relative to the
conditioned space. Induced draft fans shall be direct-drive.
One (1) high limit controller per heating module, with auto-
matic reset to prevent the heat exchanger from operating at
an excessive temperature will be installed. A pressure switch
on the combustion section must be provided to prevent igni-
tion until sufficient air flow is established through the heat
exchanger. Secondary airflow safety shall be provided by roll-
out switch protection. The rollout switch shall discontinue fur-
nace operation if the flue becomes restricted. Units shall ship
with an external flue to be shipped in the unit and mounted on
the job site. The flue shall discharge products of combustion
above the unit, preventing recycling of corrosive combustion
gases back through the heat exchanger. Gas heating sec-
tions shall be both ETL and CSA approved to both US and
Canadian safety standards.
fully drawn collars to accurately space fins, and to form a pro-
tective sheath for the primary surface. A structural galvanized
steel casing shall protect the coil. Tube sheets on each end
shall have drawn collars to support tubes. An intermediate
coil support shall be provided. The coil shall be circuited to
provide free draining and venting, through one vent and
drain. Completed coil, including headers, connections and
return bends shall be tested with 325 pounds compressed air
under water. Coils shall be designed for operation at 250 psig
design working pressure.
Steam Heating Coil
The manufacturer shall furnish and factory install a steam
heating coil in the rooftop units, as described in the following
specifications. Steam coil capacities and pressure drops shall
be certified in accordance with ARI standard 410. The steam
coil shall be constructed in the non-freeze style. The steam
coil shall have six fins per inch, and 2" inlet, and 1 1/2" outlet
connection. Tubes shall be 1" OD seamless copper tubing
with a minimum wall thickness of 0.035" and expanded into
the fin collars for maximum fin-tube bond. Inner distributing
tubes shall be 5/8" OD seamless copper tubing with a mini-
mum wall thickness of 1/4". The copper to copper joints shall
be joined with high temperature, silver solder. Corrugated fins
with integral spacing collars shall cover the entire tube sur-
face. Headers shall be constructed of seamless copper. The
header tube holes shall be extruded providing better tube to
header contact for a stronger braze connection. All header
connections shall be of red brass or steel, with male pipe
threads and silver braze to headers. Casing shall be 16
gauge galvanized steel. Chafing shall be prevented by
extruding and flaring the holes in the tube sheet and interme-
diate tube sheet. The core shall be pitched in the direction of
the condensate connection for proper drainage. The com-
pleted coil (including headers and connections) shall be
tested underwater with 325 lbs. compressed air to ensure a
leak free coil.
Optional Modulating Furnace control or Single Stage control
available.
Electric Heating Section
An electric slip-in heater shall be installed within the rooftop
unit to provide the heating requirements per the schedule
shown on the plans. The electric heater shall be wired in such
a manner as to provide two equal steps of capacity (80 and
108 kW) or a single step of capacity (40 kW). The furnace
shall be an industrial grade design using an open coil(s)
made of the highest grade resistance wire containing 80%
nickel and 20% chromium. The resistance coil(s) shall be
adequately supported in the air stream using ceramic bush-
ings in the supporting framework. Terminals of the coil(s)
shall be stainless steel with high temperature ceramic bush-
ings. The primary high temperature protection shall be an
automatic reset type thermal cut out. Secondary protection
shall be an automatic reset type thermal cut out. Secondary
protection shall be a replaceable thermal link. The operation
of the electric heater shall be an integral part of the roof top
control system. Power connection to the strip heater shall be
through the single power point connection for the entire unit.
Electric heat shall be ETL certified to both US and Canadian
safety standards.
REFRIGERATION SYSTEM
Units shall have two (25 ton), three (30 ton) or four (40 ton)
independent refrigerant circuits for maximum load-matching
capability. Each refrigerant circuit shall be controlled with a
balance-port thermal expansion valve for maximum control at
low load conditions.
Hot Water Heating Coil
The manufacturer shall furnish and factory install a hot water
coil in the rooftop units, as described in the following specifi-
cations. Water coil capacities and pressure drops shall be
certified in accordance with ARI Standard 410. The hot water
coil shall have eight fins per inch, 2 tubes per circuit, and 2"
inlet and outlet connection. Primary surface shall be 1/2" OD
copper tube, staggered in direction of airflow. Tubes shall be
mandrel expanded to form fin bond and provide burnished,
work-hardened interior surface. Return bends shall be die
formed and silver-brazed to tubes. Headers shall be of heavy
seamless copper tubing, silver-brazed to tubes. Connections
shall be of red brass, with male pipe threads, silver brazed to
headers. Connections also have 1/4" FPT drain plug on each
connection. Extended surface shall consist of die-formed,
continuous, aluminum fins with formed channels, and surface
treatment to minimize moisture carry-over. Fins shall have
Evaporator Coils
Evaporator coils shall be direct expansion type with inter-
twined circuiting to assure complete coil face activity during
part load operation. Coil fins shall be enhanced aluminum
type. Coil types shall be 3/8” OD copper, internally enhanced
and mechanically expanded to bond with the fins. Coil casing
shall be fabricated from heavy gauge galvanized steel. All
coils shall be pressure tested at a minimum of 450 PSIG. A
galvanized powder painted steel drain pan shall be provided
under the entire length and width of the evaporator coil,
including all return bends. The main drain pan shall be sloped
a total of 1/4” per foot towards the drainage point. Main drain
pan shall be easily cleanable in the field. The condensate
drain opening shall be flush with the bottom of the drain pan
Johnson Controls Unitary Products
91
246653-YTG-E-0108
to allow complete drainage. Coils in excess of 48 inches high
shall have an intermediate drain pan, also fabricated of galva-
nized powder painted steel extending the entire finned length
of the coil to provide better water drainage. Drainage from the
intermediate drain pan shall be to the primary drain pan.
OPTIONAL: Drain pans shall be constructed of stainless
steel. OPTIONAL: Evaporator coils shall be protected by the
Technicoat 10-1 four coat process. Coils shall be dipped in a
phenolic coating, which provides substantial resistance to
corrosion of aluminum and copper. OPTIONAL: Copper-tube/
Copper-finned evaporator coil assemblies.
CONTROLS
GENERAL DESCRIPTION
Equipment with Simplicity® as standard shall be factory run-
tested through the control, after the test is complete; there will
be no wires to re-connect. All control wiring points shall be
tested and verified through communication.
The control shall be UL or CSA recognized. The control shall
be manufactured in a manufacturing facility that is certified to
ISO 9001.
Compressors
COMPRESSOR CONTROL
Units shall have two (25 ton), three (30 ton) or four (40 ton)
industrial duty hermetic scroll compressors, independently
piped and charged. Compressor frame shall be cast iron, with
cast iron fixed and orbiting scrolls. Compressors shall be
internally protected with thermal pressure relief. Each com-
pressor shall include a discharge line check valve.Compres-
sors shall be vibration isolated from the unit, and installed in
an easily accessible area of the unit.
The control shall have a five-minute Anti-Short Cycle Delay to
prevent excessive compressor cycling. The control shall
have a three-minute minimum run time to insure that oil gets
returned to the compressor each time it starts. The minimum
runtime shall be programmable up to 10 minutes.
The control shall monitor the High and Low Pressure
switches separately for each refrigeration circuit. The control
shall have a 30 second Low Pressure Switch bypass when it
starts any compressor.
Condenser Coils
Condenser coils shall have 3/8” seamless copper tubes,
arranged in staggered rows, mechanically expanded into alu-
minum fins. Coils shall be protected from hail damage with a
V configuration, with individual flat coils rotated 30 from the
vertical plane for each condensing circuit. Condensing coils
shall have an integral subcooler for more efficient, stable
operation. OPTIONAL: Condenser coils shall be protected by
the TechniCoat 10-1 four coat process. Coils shall be dipped
in a phenolic coating, which provides substantial resistance
to corrosion of aluminum and copper. OPTIONAL: Copper-
tube/Copper-finned condenser coil assemblies.
A hard compressor lockout shall occur if the control detects
the same switch trip three times in a two-hour window, which
starts when the first trip occurs. On the first and second trips,
the control will turn the compressor off and wait five-minutes
after the switch re-closes, before restarting the compressor.
The control shall be capable of operating both compressors
and the economizer when there is a call for both stages of
cooling.
The control shall have a means of locking out mechanical
compression below a programmable low ambient trip point.
This must be done without adding extra components to the
unit.
Condenser Fans and Motors
Condenser fans shall be direct drive, propeller type, discharg-
ing vertically. Condenser fan motors shall be 3 phase, totally
enclosed air over (TEAO) type, with built in thermal overload
protection.
The control shall have a means of locking out the mechanical
compression when the economizer is operating in free cool-
ing mode without additional components
Refrigerant Piping
All interconnecting piping between refrigeration components
shall be copper tubing with brazed joints. Each refrigerant cir-
cuit shall be equipped with liquid line filter drier, and moisture
indicating sight glass. Each circuit shall also have both high
and low pressure switches installed on either side of the com-
pressor and include shrader depressors for replacement of
the pressure switches without removing charge. All small
diameter distributor tubing to the evaporator coil shall be pro-
tected by polyurethane sleeves over the length of the tubing
to prevent the tubes from copper-to-copper contact during
shipment or operation.
The control shall have a means of starting the compressor
before the indoor Fan comes on w1hen operating with a
Thermostat in the AUTO FAN mode.
FAN CONTROL
The control shall have fully adjustable Fan ON and Fan OFF
delays for both Heating and Cooling settable at the control or
via communication.
The control's default Fan OFF delay for Cooling shall be 30
seconds to take advantage of the remaining capacity in the
coil after the compressor has been turned off.
Hot Gas Bypass (Optional on CV; standard on VAV)
Unit shall have hot gas bypass factory installed on the lead
compressor.
92
Johnson Controls Unitary Products
246653-YTG-E-0108
The control shall lock on the Fan if the high temperature limit
trips three times in one hour of operation.
The control will have low voltage protection for the contactors
and will not energize a contactor if the voltage is below 19.2
VAC, to insure contactor pull-in. If the control has a compres-
sor contactor energized when the voltage drops, it shall not
de-energize the contactor until the voltage drops below 16
VAC, which is the drop out voltage for most contactors.
The control will have a software programmable Fan Mode
Switch for Auto operation or Continuous operation.
When the Fan is in the Continuous mode, it will run continu-
ously during the occupied schedule and in the Auto mode
when in an unoccupied schedule.
The control shall have a means of low ambient control with-
out adding any additional components. The control shall
have a means of cycling the compressor on for 10 minutes
and off for 5 minutes to defrost the indoor coil when the out
side ambient is below a low ambient switch point without add-
ing additional components.
The control shall be capable of operating the fan without a G
or fan signal from the thermostat.
EQUIPMENT CONTROL FEATURES
The control shall have a means of storing compressor run
time. This data shall be available through communication.
The control shall have the ability to clear this data when a
compressor is replaced.
The control shall be capable of communicating on the Stan-
dard Open protocol, Modbus RTU.
®
®
The register data for the Modbus must be publicly available
and open.
The control shall have the ability to store a name of at least
26 characters in length. The control will leave the factory with
the serial number of the equipment it is in, stored in non-vola-
tile memory in the Name location.
Monitoring Software shall be provided at no cost. The moni-
toring software shall have a flashing icon when any unit wired
to the computer has an alarm. Clicking the flashing icon shall
display the fault code and the details of the fault.
The control shall have the ability to store the model number
of the equipment of at least 26 characters in length. The con-
trol will leave the factory with the model number of the equip-
ment it is in, stored in non-volatile memory.
The networking setup shall be completed by connecting a
three-wire daisy chain cable to each unit, then powering all
the units up and pushing a button on each control. There
shall not be any dipswitches to configure the network
address.
The control shall have the ability to store the serial number of
the equipment of at least 26 characters in length. The control
will leave the factory with the serial number of the equipment
it is in, stored in non-volatile memory.
The control shall use a communication driver that is capable
of having 64 nodes on the bus before a repeater is needed.
The control shall not power the contactors through the ther-
mostat wiring. Dropping voltage over the thermostat wiring
causes chattering contactors when the contactors are pow-
ered in this manner.
The control shall use non-volatile memory to store the last
five alarms. There shall be a single button to push to recall
these last five alarms. The alarms shall be stored first in last
out. The first flash code shall be the last alarm that occurred.
There shall be a button press sequence to clear the alarms in
non-volatile memory.
The control will operate and monitor up to 3 stages of heat
independently.
The control shall have a button to reset compressor lockouts
without powering the unit down.
The control shall monitor the Gas Heat operation in the heat-
ing mode. It shall monitor the gas valve when there is a call
for heating. The control shall alarm when there is a call for
heat and no gas valve voltage after 5 minutes.
The control shall have a button to clear compressor Anti-
Short Cycle Delays. When this button is pressed it will only
clear the Anti-Short Cycle Delays for one cycle only and not
permanently.
There will only be one control board for this series of units, for
both CV and VAV operation.
The control will be compatible with any BAS (Building Auto-
mation System). Any BAS shall be able to control the equip-
ment when wired to the control's Thermostat Terminal Strip.
COMFORT CONTROL FEATURES
The control will be installed and tested at the factory where
the equipment is assembled.
The control shall have loading of at least 25 milliamps on all
thermostat inputs for controllers and thermostats that use out-
put TRIACs.
The control will use a Wall Senor that has a means of overrid-
ing the unoccupied mode for a programmable amount of
time.
The control shall have a Smoke Detector Shutdown input on
the board. The control shall be powered through this input,
so when the Smoke Detector trips, the control will shut down
the unit immediately.
The Unoccupied Override time will be programmed in min-
utes up to 4 hours.
Johnson Controls Unitary Products
93
246653-YTG-E-0108
The control will use a Wall Sensor that has a warmer/cooler
dial so the occupants can offset the programmed setpoint by
a programmed amount between 1 and 5 degrees.
The control will have a Space Temperature Alarm.
The control will have a Supply Air Temperature Alarm for
Heating and Cooling. The Alarm temperature will be pro-
grammable
The control will have a Supply Air Sensor as standard.
The control will have a Return Air Sensor as standard.
The control will have an Outside Air Sensor as standard.
The Control will be able to do a Pre-Occupancy Purge at a
Programmable Time.
The control will have a hardware Smoke-Purge input.
The control will have the ability to read a dirty filter switch
The control will use the Return Air Sensor in place of the
Space Sensor if the Space Sensor fails for any reason, the
control will have a 365 day Real Time Clock.
The control will have the capability of reading a Fan proving
switch.
The Real Time Clock will be able to do automatic Daylight
Savings Time adjustment.
The control will have an intelligent recovery function that will
bring the space to the Occupied Setpoint just before or at the
beginning of the first Occupied schedule each day. The con-
trol will learn and apply the minimum run time required to heat
or cool the space to setpoint for the first Occupied period of a
day.
The control will have an Occupancy Schedule that allows two
different Occupied schedules per day for each of the seven
days of the week individually.
The control will have 20 Holiday Schedules, each capable of
99 days.
The control will have Software controllable Mode Switches
(Heat, Cool, and Fan).
The control's Holiday Schedules will have a start time associ-
ated with each schedule.
The control will meter and track Unoccupied Override Time
for billing purposes.
The control will control the Economizer directly.
The control will be capable of operating the Economizer using
Dry Bulb, Outside Enthalpy, or Differential Enthalpy.
OPTIONAL COMMUNICATION TRANSLATOR
Overview
When the control is using Enthalpy to control the Economizer,
it will also have an Outside Air Temperature enable Setpoint.
®
The ModLINC translator operates as a Modbus Client pro-
®
viding an interface between a BACnet control system and
®
devices that communicate using the Modbus RTU protocol.
The control will use two setpoints for Supply Air Temperature
for the Economizer operation. One will be for a small space
cooling demand and one for a large space cooling demand.
The ModLINC is preconfigured to provide an interface to
YORK UP products equipped with an Intelli-Comfort or Sim-
plicity-Elite controller and allows monitoring and control by a
®
third-party BACnet Building Automation System (BAS).
The control will have the ability to do Demand Ventilation
using one CO sensor.
2
The ModLINC mounts inside the control panel of the UP unit
and utilizes 24 VAC power from the unit's control transformer.
One port is connected to the UP controller. The other port
The control will have a programmable maximum Outside Air
Damper Position for IAQ operation.
®
must be connected to the BACnet network.
The control will have the ability to temper the ventilation air
during times when heating or cooling is not required.
The ModLINC translator is preconfigured to obtain opera-
tional data points from the controller and expose them on a
BACnet network.
®
The control will have the ability to offset the operating set-
point based on high Humidity in the Space.
"The ModLINC device is primary a control offered and config-
ured by York's ESG (Engineering Systems Group). The
The control will have programmable limits when offsetting the
Operating Setpoint to control Humidity.
®
device can be used with other BACnet MS/TP systems, but
a qualified controls contractor must be involved. UP cannot
support the ModLINC device beyond its hardware functional-
ity and cannot guarantee functionality with the ISN or other
third party BAS devices."
The control must be able to lockout Cooling below a program-
mable Outside Air Temperature Setpoint.
The control will be able to lockout Heating above a program-
mable Outside Air Temperature Setpoint.
Please refer to the ModLINC Installation/Application manual
Part Number 126367.
94
Johnson Controls Unitary Products
246653-YTG-E-0108
Remote Wall Mounted Temperature Sensors
OPTIONAL CONTROL
Attractive wall mounted temperature sensors are available to
precisely control multiple or individual zone temperature.
Sensors are available without adjustment, with override and
override with programmable setpoint adjustment.
York Commercial Comfort System (YCCS)
Provides rooftop system integration for YCCS single zone,
change-over bypass and VAV systems.
Dirty Filter Switch
AVAILABLE ACCESSORIES
The following accessories shall be available:
Partial perimeter roof curbs
A Dirty Filter pressure switch kit is available for field installa-
tion. Switches will monitor pressure drop across the units air
filters and provide an alarm when filters become dirty.
Propane Conversion Kits
14" high roof curb with wood nailer. The partial perimeter roof
curb surrounds the portion of the unit which has airflow, and
includes a support at the compressor end of the unit.
Contains the necessary orifices and gas valve parts to con-
vert from natural gas to propane. Propane cannot be used on
modulating gas heat units.
Burglar Bars
High Altitude Conversion Kits
This accessory mounts in the supply and return opening of
the partial perimeter curb to prevent entry into the building
through the ductwork.
These kits are required for natural gas applications between
2,000 and 6,000 feet.
Field Installed Barometric Relief
Energy Recovery Ventilators
This accessory is a set of barometric relief dampers and hood
used for the millennium barometric relief option that is fully
assembled for mounting to return ductwork. This accessory is
intended for use on horizontal return applications.
8,000 and 13,000 CFM models available. Great applications
involving 30% or more of required outdoor air where energy
use and comfort must be optimized.
Programmable thermostat, with or without remote sen-
sor (required for constant volume units)
Provides 2 Heat/4 Cool control and 7 day programming.
Johnson Controls Unitary Products
95
Subject to change without notice. Printed in U.S.A.
246653-YTG-E-0108
Copyright © 2008 by Johnson Controls, Inc. All rights reserved.
Supersedes: 246653/036-21091-004-D-0206
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
|
Sharp Ar C160 User Manual
Savin 9700 User Manual
NEC NP510W User Manual
NEC MULTISYNC PA271Q BK User Manual
Monarch Act 1b 10 User Manual
Microsoft Spc210sf User Manual
D LINK COVR X1864 User Manual
CRAFTSMAN 151.30383 User Manual
ASUS VP229DA User Manual
ACER AT310 F1 User Manual