343615-YTG-B-0308
®
DESCRIPTION
YORK Sunline Magnum™ units are convertible single pack-
age air conditioners with a common cabinet and a common
roof curb for the 3, 4 and 5 ton sizes. The units were
designed for light commercial and commercial applications.
They can easily be installed on a roof curb, slab, roof jack or
frame.
TECHNICAL GUIDE
SINGLE PACKAGE GAS/ELECTRIC UNITS
AND SINGLE PACKAGE
All units include:
•
Powder Paint finish that meets ASTM-B-117 750 hour salt
spray standards
AIR CONDITIONERS
•
•
Permanently lubricated motors
DY 036, 048 & 060
Bottom or side air discharge configuration capability
(field convertible)
3, 4 & 5 NOMINAL TONS
•
Manufactured under the quality standards of ISO9001
14.00 SEER
®
•
•
•
•
•
•
•
•
S implicity Control Board
Copper tube/aluminum fin coils
Easy access to all components
Rigging holes in base rails for lifting
Fork lift slots on three sides
Single point power connection
Complete factory package - tested, charged and wired
CSA agency listing on all units
WARRANTY
•
•
•
Factory Limited Parts Warranty
One-year parts warranty
A Five-year parts warranty on the compressor and
electric heat elements.
•
Ten-year parts warranty on the gas-fired heat
exchangers.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
343615-YTG-B-0308
PRODUCT NOMENCLATURE
3-5 Ton Sunline Magnum™ Model Number Nomenclature
D Y 048 N04 A 2 A AA 2 0 1 2 4 A
Product Category
Product Style
D = A/C, Single Pkg., R-22
A = Style A
Product Identifier
Y = 14.0 SEER
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
SS Drain Pan
CPC Controller, DFS, APS
Johnson Controller, DFS, APS
Nominal Cooling Capacity
Honeywell Controller, DFS, APS
036 = 3.0 Ton
048 = 4.0 Ton
060 = 5.0 Ton
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
2" Pleated filters
Heat Type and Nominal Heat Capacity
BAS Ready Economizer (2-10 V.D.C. Actuator without a Controller)
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
C00 = Cooling Only. Suitable for Field
Installed Electric Heat
Product Generation
2 = Second Generation
Gas Heat Options
N04 = 40 MBH Output Aluminized Steel, 1 Stage (036)
N06 = 60 MBH Output Aluminized Steel, 1 Stage (048)
N08 = 80 MBH Output Aluminized Steel, 1 Stage
(036, 060)
Additional Options
Hinged Filter Door & Toolless Access Cabinet
N10 = 100 MBH Output Aluminized Steel, 1 Stage
(048, 060)
Standard Cabinet
D06 = 60 MBH Output Aluminized Steel, 2 Stage
(036, 048, 060)
AA = None
BA = Hinged Filter Door & Toolless Access Panels
BB = Phase Monitor, Hinged Filter Door & Toolless
Access Panels
BC = Coil Guard, Hinged Filter Door & Toolless
Access Panels
BD = Dirty Filter Switch, Hinged Filter Door &
Toolless Access Panels
BE = Phase Monitor & Coil Guard, Hinged Filter
Door & Toolless Access Panels
BF = Phase Monitor & Dirty Filter Switch, Hinged
Filter Door & Toolless Access Panels
BG = Coil Guard & Dirty Filter Switch, Hinged Filter
Door & Toolless Access Panels
AB = Phase Monitor
D10 = 100 MBH Output Aluminized Steel, 2 Stage
(036*, 048, 060)
AC = Coil Guard
AD = Dirty Filter Switch
S04 = 40 MBH Output Stainless Steel, 1 Stage (036)
S06 = 60 MBH Output Stainless Steel, 1 Stage (048)
S08 = 80 MBH Output Stainless Steel, 1 Stage
(036, 060)
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
AS = Bottom Drain Connection
RC = Coil Guard & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator and Condenser Coil
S10 = 100 MBH Output Stainless Steel, 1 Stage
(048, 060)
T06 = 60 MBH Output Stainless Steel, 2 Stage
(036, 048, 060)
T10 = 100 MBH Output Stainless Steel, 2 Stage
(036*, 048, 060)
BH = Phase Monitor, Coil Guard & Dirty Filter Switch,
Hinged Filter Door & Toolless Access Panels
Electric Heat Options
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
E05 = 5 KW
E07 = 7 KW
E10 = 10 KW
E15 = 15 KW
E20 = 20 KW
E30 = 30 KW
Installation Options
A = No Options Installed
B = Option 1
*(D, T)10 = 92 MBH Output on 036 Models
Airflow
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
A = Direct Drive
B = Direct Drive/Single Input Economizer
D = Direct Drive/Motorized Damper
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
Voltage
1 = 208/230-1-60
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Johnson Controls Unitary Products
3
343615-YTG-B-0308
gas valve, if applicable, and the temperature limit
switch on gas heat units. The unit control board will
alarm on ignition failures, compressor lockouts and
repeated limit switch trips.
FEATURES
All models are available with a wide variety of factory-
mounted options such as stainless steel heat exchangers,
electric heaters, phase monitor, convenience outlet, dirty filter
switch, disconnect switch, smoke detectors, and coil guard to
make them suitable for almost every application.
•
•
Nuisance Trip Protection- To prevent nuisance
trouble calls, the control board uses a “three strikes,
you’re out” philosophy. The high and low-pressure
switches and the freezestats must trip three times
within two hours before the unit control board will
lock out the compressor.
All units are self-contained and assembled on full perimeter
base rails with forklift holes on three sides and holes for over-
head rigging. Every unit is completely piped, wired, charged
and tested at the factory to simplify the field installation and to
provide years of dependable operation.
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. For bottom
duct, remove the sheet metal panels from the supply and
return air openings through the base of the unit. For horizon-
tal duct, remove the supply and return air panels on the rear
of the unit.
All models are available with these “factory mounted” outdoor
air damper options:
All units have long lasting powder paint cabinets with 750 hour
salt spray test approval under ASTM-B117 procedures.
•
•
Single enthalpy economizer
Motorized outdoor air damper
All models are CSA listed.
•
Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.
Supply air blowers are equipped with a 5 speed direct drive
motor that can be adjusted to meet the exact requirements of
the job.
•
Gas Heat Operation - All single phase models with gas
heat have minimum annual fuel utilization efficiency
(AFUE) of 80%. All three phase models with gas heat
have minimum steady state efficiency of 80%. Each sec-
tion includes a durable heat exchanger with aluminized
steel or optional stainless steel tubes, a redundant gas
valve, spark ignition, power venting, an ignition module
for 100% shut-off and all of the safety controls required
to meet the latest ANSI standards.
All compressors are equipped with internal pressure relief.
Every refrigerant circuit includes a liquid line filter-drier, a high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch to protect all system compo-
nents.
®
®
•
S implicity Controls - S implicity control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
•
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
•
Electric Heat Operation - All electric heat models are
wired for a single power source and include a bank of
nickel chromium elements mounted at the discharge of
the supply air blower to provide a high velocity and uni-
form distribution of air across the heating elements.
Every element is fully protected against excessive tem-
perature by thermal limit switches.
•
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
The power supply wiring can be routed into the control
box through a threaded pipe connection (field supplied)
in the base pan of the unit or through a knockout in the
wiring panel on the side of the unit.
•
•
Fan Delays - Fan on and fan off delays are fully pro-
grammable and are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
•
BAS Controls - York’s Sunline™ series units offer factory
®
mounted BAS controls such as S implicity INTELLI-Com-
Safety Monitoring - The control board monitors the
fort™, Novar, Honeywell, Johnson, and CPC.
high and low-pressure switches, the freezestats, the
4
Johnson Controls Unitary Products
343615-YTG-B-0308
Gas/Electric
Electric heat
accessory location
20 Gauge aluminized
steel tubular heat exchanger
Power ventor motor with
post purge cycle
Direct drive
blower
High efficiency
compressor
HACR
breaker
Economizer
hood
Copper tube/
aluminum fin
condensing coil
Knockout
for side
power entry
Slide-in
economizer
Smoke
detector
Full perimeter baserails
with forklift slots and
lifting holes
Knockout for side
gas supply entry
3/4
"
PVC female
condensate drain
GFCI
convenience outlet
Simplicity® Lite™
control board
Knockout
for side
control entry
Electric/Electric and Heat Pump
Direct drive
blower
HACR
breaker
Knockout
for side
power entry
High efficiency
compressor
Economizer
hood
Copper tube/
aluminum fin
condensing coil
Slide-in
economizer
Smoke
detector
Full perimeter baserails
with forklift slots and
lifting holes
3/4
"
PVC female
Electric Heat
accessory location
condensate drain
GFCI
convenience outlet
Simplicity® Lite™
control board
Knockout
for side
control entry
FIGURE 1 - UNIT CUTAWAY
Johnson Controls Unitary Products
5
343615-YTG-B-0308
scheduling is built-in. Two different modes of demand
ventilation are achieved through the INTELLI-Comfort™
using CO2 sensors. It uses an inside CO2 sensor to per-
form Demand Ventilation. It can also use an Outside
CO2 sensor to perform Differential Demand Ventilation.
It uses a Patented Comfort Ventilation algorithm to pro-
vide comfortable ventilation air temperature. The pat-
ented economizer-loading algorithm will protect the
equipment when harsh operating conditions exist.
Humidity in the occupied space or return duct can be
monitored and controlled via humidity sensors and the
on-board connection for hot gas re-heat system. It uses
the INTELLI-Start™ algorithm to maximize energy sav-
ings by recovering the building from the Unoccupied Set-
points to the Occupied Setpoints just in time for the
FACTORY-INSTALLED OPTIONS
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is oper-
ating and will drive fully closed when the blower unit
shuts down.
®
Occupied Time Period to begin. The S implicity
INTELLI-Comfort™ balances space temperature, venti-
lation air temperature, CO2 and humidity for ultimate
comfort.
®
•
S implicity INTELLI-Comfort™ with MOD LINK CON-
The rain hood is painted to match the basic unit and
must be field assembled before installing.
®
TROL - The York® S implicity INTELLI-Comfort™ with
Mod Link control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an addi-
tional control to translate communications from MOD-
BUS to the BACnet MSTP protocol.
•
•
PHENOLIC COATED EVAPORATOR AND CON-
DENSER COILS - Special coating process that utilizes
TM
Technicoat 10-1 processes. Coating is applied by total
immersion of the complete coil for maximum protection.
•
•
Novar® BAS CONTROL - The Novar® ETC-3 building
automation system controller is factory installed.
Includes supply air sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
ELECTRIC HEATERS - Wired for single point power
supply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent
operation at excessive temperatures.
JOHNSON CONTROLS BAS CONTROL - The Johnson
Control YK-UNT-1126 building automation system con-
troller is factory installed. Includes supply air sensor,
return air sensor, dirty filter indicator switch, and air prov-
ing switch.
•
•
FILTER OPTIONS - Standard units are shipped with 1”
throw-away filters installed. 2” pleated filters are offered
as a factory installed option.
CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the
unit may be ordered with a “non-powered” convenience
outlet that can be wired in the field.
•
CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building auto-
mation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
•
•
DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
•
•
•
HONEYWELL BAS CONTROL - The Honeywell
W7750C building automation system controller is factory
installed. Includes air supply sensor, return air sensor,
dirty filter indicator switch, and air proving switch.
BAS - Building Automation System Controls
®
SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
S implicity INTELLI-Comfort™ CONTROL - The York®
®
S implicity INTELLI-Comfort™ control is factory
installed. It includes a supply air sensor, a return air sen-
sor, and an outside air sensor. There are provisions for a
field installed dirty filter indicator switch, an air-proving
switch, an Outside Air Humidity sensor, a Return Air
Humidity sensor, an Inside IAQ sensor, and an Outside
Air IAQ sensor. Construction mode operation, 365-day
real time clock with 7 day programming plus holiday
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
6
Johnson Controls Unitary Products
343615-YTG-B-0308
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
Factory installed Smoke Detectors in the Return
Air, may be subjected to freezing temperatures
during "off" times due to Out Side Air infiltration.
These Smoke Detectors have an operational limit
of 32°F to 131°F. Smoke Detectors installed in
areas that could be out side those limitations will
have to be moved to prevent having false alarms.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
•
ELECTRIC HEATERS wired for single point power sup-
ply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent
operation at excessive temperatures.
•
•
STAINLESS STEEL HEAT EXCHANGER - For applica-
tions in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.
ROOF CURBS - Eight and fourteen-inch high roof curbs
provide a water-tight seal between the unit and the finished
roof. These full perimeter curbs meet the requirements of
the National Roofing Contractors Association (NRCA) and
are shipped knocked-down for field assembly.
STAINLESS STEEL DRAIN PAN - An optional rust-
proof stainless steel drain pan is available to provide
years of trouble-free operation in corrosive environ-
ments.
Roof curbs are designed to fit inside the base rails of the
unit and include both a wood nailing strip and duct
hanger supports.
•
BOTTOM DRAIN CONNECTION - An optional bottom
drain connection is available for inside the curb connec-
tions for applications in cold environments to reduce
freezing drain lines.
•
•
•
HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
•
•
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of-
phase condition.
PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at alti-
tudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
•
HINGED FILTER DOOR/“TOOLLESS” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
•
•
LOW NOX KIT - Required to reduce the emission of
nitrogen oxides below 40 nano grams per joule.
NOTE:Knobs are shipped inside the unit to prevent ship-
ping damage. These must be field installed for
tool-less operation.
POWER EXHAUST - Our single input economizer
options are available with power exhaust. Whenever the
outdoor air intake dampers are opened for free cooling,
the exhaust fan will be energized to prevent the condi-
tioned space from being over-pressurized during econo-
mizer operation.
FIELD-INSTALLED ACCESSORIES
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The power exhaust option can only be used on bot-
tom duct configurations.
•
BAROMETRIC RELIEF DAMPER - This damper acces-
sory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
Johnson Controls Unitary Products
7
343615-YTG-B-0308
•
ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
•
•
•
•
CO SENSOR - Senses CO levels and automatically
overrides the economizer when levels rise above the
present limits.
2
2
•
•
BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.
HAIL GUARD - Hail Guard kit is available to prevent unit
from hail damage. This is a sloped hood that fits above
the coil.
GAS PIPING KIT - This kit supplies all necessary fittings
and shut off valve.
1
1
TABLE 1: CAPACITY RATINGS - (ARI 210/240)
TABLE 2: GAS HEAT RATINGS
SOUND
RATING
(Db)4
84
MBH
INPUT
MBH
OUTPUT
AFUE
(%)
TEMP
RISE ºF
MODEL
EER2
SEER3
MODEL
MBH
CFM
DY036N04
DY036N08
DY048N06
DY048N10
DY060N08
DY060N10
50
100
40
80
80.9
80.5
15 - 45
45 - 75
DY036
DY048
DY060
35.6
46.0
59.0
12
12
14
14
14
1200
1600
1750
83
75
125
60
100
80.9
80.3
25 - 70
45 - 75
11.6
81
100
125
80
100
80.5
80.3
25 - 55
30 - 75
1. 80/67°F Indoor and 95°F outdoor.
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
3. SEER = Seasonal Energy Efficiency Ratio.
1. All units are single-stage heating.
4. Rated in accordance with ARI 270 Standard.
TABLE 3: 2 STAGE GAS HEAT RATINGS
MBH INPUT
MBH OUTPUT
STEADY STATE EFFICIENCY
RISE
MINIMUM HEATING
AIRFLOW (CFM)
MODEL1
1
ST STAGE 2ND STAGE 1ST STAGE 2ND STAGE 1ST STAGE
2ND STAGE
MIN. MAX.
45
69
45
75
45
75
75
115
75
35.8
55.2
35.7
60.4
35.8
60.4
60.8
92
79.4
80.0
79.4
80.5
79.4
80.5
81.1
35
55
25
45
20
35
70
90
70
75
55
75
790
950
DY036D06
DY036D10
DY048D06
DY048D10
DY060D06
DY060D10
80.2
60.8
100.6
60.8
100.6
81.1
790
125
75
80.5
1230
1010
1230
81.1
125
80.5
1. Models are 3Ø only.
8
Johnson Controls Unitary Products
343615-YTG-B-0308
TABLE 4: DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
DY036 / 3 Ton
Horizontal Ducted Inlet
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
630
0.2
1116
0.41
631
879
0.2
885
0.7
1020
0.53
0.3
928
0.37
1979
0.76
Blower Motor BHP
Cooling
Cooling
Cooling
Cooling
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Octave Center Freq.
63
80
76
56
50
40
41
41
45
82
77
59
50
43
42
41
45
80
76
56
49
39
40
41
45
82
77
60
50
42
42
41
45
78
82
60
54
49
49
49
47
83
83
61
54
50
49
49
47
81
81
58
51
44
43
41
45
85
82
60
52
45
44
41
45
125
250
500
1000
2000
4000
8000
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 5: DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
DY036 / 3 Ton
Horizontal Ducted Discharge
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
630
0.2
1116
0.41
631
0.3
879
0.2
885
0.7
928
0.37
1979
0.76
1020
0.53
Blower Motor BHP
Cooling
Cooling
Cooling
Cooling
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Octave Center Freq.
63
80
74
58
48
41
39
41
45
84
77
61
51
45
41
41
45
80
74
58
47
39
37
38
44
83
76
61
50
43
39
38
44
85
80
68
58
55
53
55
52
87
82
68
58
55
53
55
53
84
80
63
53
49
46
49
47
87
83
65
54
50
47
49
47
125
250
500
1000
2000
4000
8000
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Johnson Controls Unitary Products
9
343615-YTG-B-0308
TABLE 6: DY036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
DY036 / 3 Ton
Vertical Ducted Inlet
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
632
0.2
1069
0.36
632
881
0.2
883
0.7
917
0.49
0.3
870
0.33
1903
0.71
Blower Motor BHP
Cooling
Cooling
Cooling
Cooling
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Operation2
Octave Center Freq.
(dB)
63
78
70
55
47
40
37
36
44
82
75
60
50
43
40
37
44
78
70
55
47
39
37
36
44
82
74
60
50
43
39
37
44
80
71
59
52
50
45
45
45
85
80
61
53
51
46
46
47
80
71
58
49
45
41
40
44
84
79
62
52
46
43
40
44
125
250
500
1000
2000
4000
8000
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 7: DY036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
DY036 / 3 Ton
Vertical Ducted Discharge
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
632
0.2
1069
0.36
632
0.3
881
0.2
883
0.7
917
0.49
870
0.33
1903
0.71
Blower Motor BHP
Cooling
Cooling
Cooling
Cooling
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Octave Center Freq.
63
80
78
55
48
41
37
38
44
83
79
60
51
44
40
39
45
80
77
54
46
39
35
36
44
83
78
59
50
43
38
37
44
83
80
63
58
54
50
52
49
86
83
63
59
55
50
53
50
82
79
58
52
48
42
44
45
85
82
62
53
49
44
44
45
125
250
500
1000
2000
4000
8000
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
10
Johnson Controls Unitary Products
343615-YTG-B-0308
TABLE 8: DY048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
DY048 / 4 Ton
Horizontal Ducted Inlet
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
766
0.2
1484
0.67
769
1077
0.4
1087
1.0
1406
0.90
0.5
993
0.54
2270
1.24
Blower Motor BHP
Cooling
Cooling
Cooling
Cooling
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Octave Center Freq.
63
74
70
53
49
42
40
38
42
97
86
58
55
42
44
44
43
74
69
52
47
38
38
36
42
95
86
57
54
39
43
41
44
77
73
60
54
50
48
48
45
90
78
61
56
55
51
52
48
77
72
58
51
45
45
43
44
90
77
61
53
45
46
45
45
125
250
500
1000
2000
4000
8000
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 9: DY048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
DY048 / 4 Ton
Horizontal Ducted Discharge
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
766
0.2
1484
0.67
769
0.5
1077
0.4
1087
1.0
993
0.54
2270
1.24
1406
0.90
Blower Motor BHP
Cooling
Cooling
Cooling
Cooling
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Octave Center Freq.
63
77
72
60
53
47
45
46
47
97
86
62
56
47
46
47
47
75
69
57
49
42
40
40
45
95
85
59
54
43
43
42
45
84
81
71
60
58
54
57
54
91
83
71
61
59
55
58
54
82
78
66
55
52
50
52
48
91
80
67
56
52
50
52
49
125
250
500
1000
2000
4000
8000
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Johnson Controls Unitary Products
11
343615-YTG-B-0308
TABLE 10: DY048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
DY048 / 4 Ton
Vertical Ducted Inlet
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
791
0.2
1408
0.54
794
1084
0.2
1095
1.0
1275
0.73
0.5
1000
0.42
2336
1.12
Blower Motor BHP
Cooling
Cooling
Cooling
Cooling
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Operation2
Octave Center Freq.
(dB)
63
76
68
54
48
43
40
38
43
95
84
57
53
44
43
43
43
77
67
52
46
40
38
36
43
93
82
56
53
41
42
40
43
80
76
63
54
52
49
49
45
91
84
61
57
52
51
54
47
79
73
57
50
47
44
43
44
91
80
59
53
47
46
45
44
125
250
500
1000
2000
4000
8000
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 11: DY048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
DY048 / 4 Ton
Vertical Ducted Discharge
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
791
0.2
1408
0.54
794
0.5
1084
0.2
1095
1.0
1275
0.73
1000
0.42
2336
1.12
Blower Motor BHP
Cooling
Cooling
Cooling
Cooling
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Octave Center Freq.
63
78
73
56
51
46
42
43
44
95
84
58
54
46
44
45
44
77
72
53
48
43
38
39
43
93
82
56
53
44
42
41
43
85
84
68
61
57
53
55
52
92
87
68
62
57
54
57
52
82
78
60
54
50
46
49
46
91
82
61
55
50
48
50
47
125
250
500
1000
2000
4000
8000
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
12
Johnson Controls Unitary Products
343615-YTG-B-0308
TABLE 12: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
DY060 / 5 Ton
Horizontal Ducted Inlet
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
840
0.2
1695
0.67
845
1166
0.3
1188
1.3
1323
0.80
0.6
1100
0.50
2618
1.51
Blower Motor BHP
Cooling
Cooling
Cooling
Cooling
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Octave Center Freq.
63
77
71
57
53
50
49
49
49
84
71
58
53
50
49
49
49
77
72
55
51
45
43
42
48
84
73
56
51
46
44
43
48
81
74
66
60
60
58
59
54
85
75
66
60
60
58
59
54
79
71
60
55
53
50
47
47
84
72
61
55
53
50
47
47
125
250
500
1000
2000
4000
8000
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 13: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
DY060 / 5 Ton
Horizontal Ducted Discharge
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
840
0.2
1695
0.67
845
0.6
1166
0.3
1188
1.3
1100
0.50
2618
1.51
1323
0.80
Blower Motor BHP
Cooling
Cooling
Cooling
Cooling
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Octave Center Freq.
63
82
75
69
64
59
55
58
55
87
76
69
64
60
55
58
55
79
72
66
60
55
50
52
49
88
74
66
60
56
50
52
49
88
82
79
72
68
65
68
66
89
83
79
72
68
65
68
67
82
78
73
66
61
57
60
56
87
78
73
66
61
57
60
56
125
250
500
1000
2000
4000
8000
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Johnson Controls Unitary Products
13
343615-YTG-B-0308
TABLE 14: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
DY060 / 5 Ton
Vertical Ducted Inlet
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
834
0.2
1525
0.61
840
1171
0.2
1194
1.3
1256
0.83
0.6
1019
0.44
2624
1.43
Blower Motor BHP
Cooling
Cooling
Cooling
Cooling
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Operation2
Octave Center Freq.
(dB)
63
77
69
56
50
48
43
47
46
86
70
63
52
51
47
49
47
79
70
56
48
44
39
40
44
88
72
58
49
45
41
41
45
81
71
64
57
57
54
55
51
86
73
72
59
58
57
61
57
83
72
63
53
49
47
47
47
87
72
69
56
52
50
52
49
125
250
500
1000
2000
4000
8000
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 15: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
DY060 / 5 Ton
Vertical Ducted Discharge
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
834
0.2
1525
0.61
840
0.6
1171
0.2
1194
1.3
1256
0.83
1019
0.44
2624
1.43
Blower Motor BHP
Cooling
Cooling
Cooling
Cooling
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
ID Blower
Only (dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Operation2
(dB)
Octave Center Freq.
63
83
78
66
59
57
51
54
52
88
78
67
60
58
52
54
52
82
75
62
54
51
45
47
46
88
76
62
54
51
45
47
47
91
85
77
70
68
62
65
65
91
85
78
70
68
63
66
66
85
79
70
61
57
52
55
52
88
79
72
61
58
53
56
53
125
250
500
1000
2000
4000
8000
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
14
Johnson Controls Unitary Products
343615-YTG-B-0308
TABLE 16: DY036 COOLING CAPACITIES (3 TON)
Temperature of Air on Condenser Coil
Air on Evap-
orator Coil
75°F
85°F
1
1
2
2
Sensible Capacity (MBH)
Return Dry Bulb (°F)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
Total Total
Cap.
Total Total
Cap.
WB
CFM
1
1
Input
Input
(°F)
(MBH) (kW)
(MBH) (kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
44
42
40
39
44
42
40
39
44
43
40
39
45
43
41
40
46
44
42
41
2.3
2.3
2.3
2.3
2.2
2.3
2.3
2.3
2.2
2.3
2.3
2.3
2.2
2.3
2.3
2.3
2.3
2.3
2.3
2.3
24
30
40
39
26
33
40
39
28
35
40
39
30
37
41
40
32
40
42
41
21
28
35
37
23
30
38
38
25
32
40
39
26
33
41
40
27
35
42
41
19
25
33
35
20
27
35
37
21
28
37
39
22
29
39
40
23
31
42
41
95°F
16
22
27
27
18
24
30
30
19
26
32
32
20
27
32
33
21
29
33
33
115°F
13
18
21
23
15
20
23
25
16
22
25
27
17
23
25
26
18
25
25
25
16
23
30
32
17
24
32
34
18
25
33
36
18
25
35
36
18
26
37
36
14
20
28
30
14
21
29
31
14
21
30
32
14
21
31
32
14
22
33
32
-
-
41
38
35
35
42
39
35
35
43
40
36
36
43
40
37
36
44
41
37
37
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
23
29
35
35
25
31
35
35
27
34
36
36
29
36
37
36
31
39
37
37
20
26
32
34
22
28
34
35
24
31
36
36
25
32
37
36
27
34
37
37
18
24
30
31
19
25
32
33
20
27
34
36
21
28
36
36
22
30
37
37
105°F
15
20
24
25
16
22
26
27
18
24
29
30
19
25
29
30
20
27
29
29
125°F
12
17
18
20
13
18
20
22
14
20
22
22
15
21
21
22
16
23
21
22
15
21
27
28
16
22
29
30
17
24
31
32
17
24
32
32
18
25
33
32
12
18
25
26
13
19
26
27
13
20
27
29
13
20
28
28
13
21
28
28
-
-
18
25
27
-
18
26
28
-
18
26
29
-
18
27
28
-
15
23
25
-
15
23
25
-
14
23
25
-
14
23
24
-
16
22
23
-
16
23
24
-
17
24
25
-
16
24
24
-
13
20
21
-
13
20
21
-
13
20
22
-
12
20
20
-
900
67
1050
62
57
72
67
1200
62
57
72
67
1350
62
57
72
67
62
57
17
28
27
13
24
23
16
24
23
12
19
19
1500
72
67
62
57
72
38
35
30
30
39
36
31
31
41
37
32
32
41
37
32
33
42
38
33
33
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
21
27
30
30
24
30
31
31
26
33
32
32
28
35
32
33
30
38
33
33
19
24
29
30
21
27
31
31
23
30
32
32
24
31
32
33
26
33
33
33
14
19
24
25
15
21
26
27
16
23
29
29
16
23
28
29
17
24
28
29
11
17
22
22
12
18
23
24
12
19
25
25
12
19
24
25
12
20
24
24
-
-
35
31
27
27
36
32
28
28
37
33
29
29
37
33
29
29
37
33
29
29
3.0
2.9
3.0
3.0
3.0
2.9
2.9
2.9
2.9
2.8
2.9
2.9
3.0
2.9
2.9
2.9
3.1
2.9
3.0
3.0
20
25
27
27
22
28
28
28
25
31
29
29
27
32
29
29
28
33
29
29
17
23
26
27
19
25
28
28
21
28
29
29
23
29
29
29
24
31
29
29
12
18
21
22
13
19
23
24
14
21
25
26
15
21
25
26
15
22
24
25
10
15
19
20
10
16
20
21
11
17
22
23
11
17
21
22
11
18
20
20
-
-
14
19
19
-
15
20
21
-
16
22
22
-
15
20
21
-
12
17
17
-
12
17
18
-
12
18
18
-
11
16
17
-
12
16
17
-
13
17
18
-
14
18
19
-
13
17
18
-
10
14
15
-
10
14
15
-
10
15
16
-
900
67
1050
62
57
72
67
1200
62
57
72
67
9
1350
62
57
72
67
62
57
13
14
-
9
11
11
15
19
20
11
15
15
13
15
16
1500
72
67
62
57
72
32
27
24
25
32
28
25
25
33
29
25
26
33
29
25
26
33
28
25
25
3.3
3.1
3.2
3.2
3.3
3.0
3.1
3.1
3.2
3.0
3.1
3.1
3.3
3.1
3.2
3.2
3.4
3.2
3.3
3.3
18
23
24
25
21
26
25
25
23
29
25
26
25
29
25
26
27
28
25
25
16
21
23
25
18
23
24
25
20
26
25
26
21
27
25
26
22
28
25
25
11
16
18
20
12
17
20
22
13
19
22
24
13
19
21
22
13
20
20
21
8
-
-
8
11
12
-
28
24
21
22
29
24
21
22
29
25
22
22
29
24
21
22
28
24
21
22
3.7
3.3
3.5
3.5
3.5
3.2
3.4
3.4
3.4
3.1
3.3
3.3
3.6
3.2
3.4
3.4
3.8
3.4
3.6
3.6
17
22
21
22
19
24
21
22
21
25
22
22
23
24
21
22
25
24
21
22
14
19
20
22
16
22
21
22
18
24
22
22
19
24
21
22
20
24
21
22
9
7
-
9
10
13
-
-
6
8
10
-
6
8
10
-
6
8
11
-
6
5
7
-
13
16
17
9
14
17
19
9
15
18
20
9
15
17
18
9
11
13
15
-
11
14
16
-
12
15
17
-
11
13
14
-
14
15
18
10
15
17
19
11
17
18
21
11
17
17
19
11
18
16
17
11
13
15
7
12
14
16
7
13
15
18
7
13
13
15
7
900
67
8
9
1050
62
57
72
11
13
-
11
13
-
10
11
14
-
10
9
11
-
67
8
1200
62
57
72
11
13
-
8
9
10
-
7
7
8
67
1350
62
57
72
67
62
57
16
16
16
11
11
12
14
12
13
9
7
8
5
3
4
1500
1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-
mance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
15
343615-YTG-B-0308
TABLE 17: DY048 COOLING CAPACITIES (4 TON)
Temperature of Air on Condenser Coil
Air on Evap-
orator Coil
75°F
85°F
1
1
2
2
Sensible Capacity (MBH)
Return Dry Bulb (°F)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
Total Total
Cap.
Total Total
Cap.
WB
CFM
1
1
Input
Input
(°F)
(MBH) (kW)
(MBH) (kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
58
57
53
51
58
56
53
51
57
56
53
51
57
56
53
51
57
55
52
50
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
32
43
53
51
34
45
53
51
36
48
53
51
39
52
53
51
41
55
52
50
28
39
47
51
30
41
50
51
32
43
53
51
33
46
53
51
35
48
52
50
25
36
44
49
26
37
46
51
27
39
47
53
28
40
50
52
29
42
52
50
95°F
22
30
37
37
24
33
41
40
26
35
44
43
27
38
44
43
29
40
43
42
115°F
18
25
28
28
20
28
31
31
22
30
34
34
24
33
34
33
25
35
33
33
22
32
40
45
22
33
41
47
22
34
43
48
23
35
45
46
23
36
46
44
18
29
37
42
18
29
37
43
18
29
38
43
17
30
39
41
17
30
40
38
-
-
54
51
47
46
55
52
48
46
55
52
48
47
55
52
48
47
55
52
48
46
3.1
3.1
3.0
3.0
3.1
3.1
3.0
3.0
3.1
3.1
3.1
3.0
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
30
40
47
46
33
43
48
46
36
46
48
47
38
49
48
47
41
52
48
46
27
36
44
46
29
39
46
46
31
42
48
47
33
44
48
47
35
47
48
46
23
33
41
43
25
35
43
45
26
37
46
48
28
39
47
47
29
41
48
46
105°F
20
27
33
32
22
30
36
35
24
33
39
39
25
35
39
38
27
37
38
38
125°F
16
22
23
23
18
25
26
26
20
28
29
29
22
30
29
29
23
31
28
28
20
29
37
39
21
31
39
41
22
32
41
43
22
34
41
42
23
35
42
40
17
26
34
36
17
27
35
37
17
28
36
39
17
28
36
37
17
29
36
34
-
-
26
33
38
-
25
33
39
-
25
33
39
-
24
34
36
-
22
30
35
-
21
29
34
-
20
29
34
-
19
29
30
-
23
30
32
-
23
31
33
-
23
32
34
-
23
31
31
-
19
27
29
-
19
27
29
-
18
27
29
-
18
25
26
-
1200
67
1400
62
57
72
67
1600
62
57
72
67
1800
62
57
72
67
62
57
24
34
32
18
28
26
23
30
28
17
24
23
2000
72
67
62
57
72
50
45
41
40
52
47
42
42
54
49
44
43
53
48
44
43
53
48
43
42
3.3
3.4
3.3
3.3
3.4
3.4
3.3
3.3
3.4
3.4
3.3
3.3
3.4
3.4
3.3
3.3
3.4
3.4
3.3
3.3
29
37
41
40
32
41
42
42
35
45
44
43
38
46
44
43
41
48
43
42
25
33
41
40
28
37
42
42
30
40
44
43
33
43
44
43
35
46
43
42
18
27
34
33
20
29
37
36
21
31
39
39
22
32
38
38
23
34
37
37
15
23
31
30
16
25
33
32
16
26
35
34
17
27
33
32
17
28
31
31
-
-
45
39
36
35
47
41
37
37
49
43
39
39
49
43
39
38
48
42
38
38
3.7
3.7
3.6
3.6
3.7
3.7
3.6
3.6
3.7
3.7
3.6
3.6
3.7
3.7
3.6
3.7
3.7
3.7
3.7
3.7
27
34
36
35
30
38
37
37
33
41
39
39
36
42
39
38
39
42
38
38
23
31
36
35
26
34
37
37
28
37
39
39
31
39
39
38
33
41
38
38
16
24
29
29
18
26
32
31
19
28
34
34
20
30
33
33
21
31
32
32
13
21
26
25
14
22
28
27
14
24
30
29
15
24
28
27
15
25
26
26
-
-
20
27
26
-
20
29
28
-
21
30
29
-
22
28
27
-
16
24
23
-
16
24
24
-
17
25
25
-
16
22
22
-
17
22
22
-
18
24
23
-
19
25
25
-
19
23
22
-
14
19
19
-
14
20
19
-
14
20
20
-
14
17
17
-
1200
67
1400
62
57
72
67
1600
62
57
72
67
1800
62
57
72
67
62
57
22
25
25
16
19
19
19
20
20
14
14
14
2000
72
67
62
57
72
40
34
31
30
42
36
32
32
45
38
34
34
44
37
34
33
43
36
33
33
4.0
3.9
3.9
3.9
4.0
4.0
3.9
3.9
4.0
4.0
3.9
4.0
4.0
4.0
4.0
4.0
4.1
4.0
4.0
4.0
25
32
31
30
28
35
32
32
31
38
34
34
34
37
34
33
37
36
33
33
21
28
31
30
24
32
32
32
27
35
34
34
29
36
34
33
31
36
33
33
14
21
25
24
16
24
27
27
17
26
30
29
18
27
28
28
19
29
27
27
11
18
21
21
12
20
23
23
13
21
25
25
13
22
23
23
13
23
21
21
-
-
35
28
26
25
38
30
28
27
40
32
29
29
39
31
29
29
39
31
28
28
4.3
4.2
4.2
4.2
4.3
4.3
4.2
4.3
4.3
4.3
4.2
4.3
4.4
4.3
4.3
4.3
4.4
4.3
4.3
4.3
23
28
26
25
26
30
28
27
29
32
29
29
32
31
29
29
35
31
28
28
19
26
26
25
22
29
28
27
25
32
29
29
27
31
29
29
29
31
28
28
13
19
20
20
14
21
22
22
15
23
25
24
16
25
23
23
17
27
22
22
9
-
-
9
10
9
-
9
10
10
-
15
18
17
-
16
19
19
-
16
20
20
-
17
18
17
-
11
14
14
-
11
15
15
-
12
16
15
-
11
12
12
-
15
16
16
10
17
18
18
11
19
20
20
11
20
18
18
11
21
16
16
12
13
13
-
13
14
14
-
14
15
15
-
14
13
13
-
1200
67
1400
62
57
72
67
9
1600
62
57
72
11
10
-
9
8
7
-
9
4
67
1800
62
57
72
67
62
57
17
15
15
11
9
9
15
10
10
2000
4
1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
16
Johnson Controls Unitary Products
343615-YTG-B-0308
TABLE 18: DY060 COOLING CAPACITIES (5 TON)
Temperature of Air on Condenser Coil
Air on Evap-
orator Coil
75°F
85°F
1
1
2
2
Sensible Capacity (MBH)
Return Dry Bulb (°F)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
Total Total
Cap.
Total Total
Cap.
WB
CFM
1
1
Input
Input
(°F)
(MBH) (kW)
(MBH) (kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
73.9
67.1
60.7
57.7
76.2
69.2
62.7
59.6
78.6
71.4
64.6
61.4
79.1
71.9
65.0
61.8
79.6
72.3
65.5
62.2
3.7
3.7
3.6
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.8
3.7
3.7
3.7
39.9 35.6 31.3 27.0 22.8
-
-
69.2
4.3
4.2
4.1
4.2
4.3
4.2
4.1
4.2
4.3
4.2
4.2
4.2
4.3
4.2
4.2
4.2
4.3
4.3
4.2
4.2
38.6 34.3 30.1 25.8 21.5
-
-
50.5 46.3 42.0 37.7 33.4 29.2 24.9 63.1
60.7 55.2 50.9 46.7 42.4 38.1 33.8 57.6
57.7 57.7 54.1 49.8 45.5 41.3 37.0 55.4
48.9 44.6 40.4 36.1 31.8 27.5 23.2
57.6 53.6 49.4 45.1 40.8 36.5 32.3
55.4 55.4 51.6 47.4 43.1 38.8 34.5
1500
44.3 39.2 34.1 29.1 24.0
-
-
71.3
42.9 37.8 32.7 27.7 22.6
-
-
67
55.9 50.9 45.8 40.8 35.7 30.6 25.6 65.0
62.7 59.9 55.6 50.5 45.4 40.4 35.3 59.4
59.6 59.6 59.0 53.9 48.9 43.8 38.8 57.0
54.1 49.0 44.0 38.9 33.9 28.8 23.8
59.4 57.4 53.8 48.7 43.7 38.6 33.6
57.0 57.0 56.3 51.2 46.2 41.1 36.1
1750
62
57
72
48.7 42.8 37.0 31.2 25.3
-
-
73.4
47.1 41.3 35.4 29.6 23.8
-
-
67
61.3 55.5 49.6 43.8 38.0 32.1 26.3 66.9
64.6 64.6 60.2 54.3 48.5 42.7 36.9 61.1
61.4 61.4 63.9 58.1 52.2 46.4 40.6 58.7
59.2 53.4 47.6 41.8 35.9 30.1 24.3
61.1 61.1 58.2 52.4 46.6 40.7 34.9
58.7 58.7 60.9 55.1 49.2 43.4 37.6
2000
62
57
72
52.5 45.8 39.2 32.5 25.9
-
-
73.8
50.9 44.2 37.6 30.9 24.3
-
-
67
66.8 59.2 52.6 45.9 39.3 32.6 26.0 67.3
65.0 65.0 62.8 56.2 49.5 42.9 36.3 61.4
61.8 61.8 63.1 56.4 49.8 43.1 36.5 59.0
63.5 57.1 50.5 43.8 37.2 30.5 23.9
61.4 61.4 60.0 53.4 46.7 40.1 33.4
59.0 59.0 60.1 53.5 46.8 40.2 33.6
2250
62
57
72
67
62
57
56.3 48.8 41.4 33.9 26.5
-
-
74.2
54.6 47.2 39.7 32.3 24.8
-
-
72.3 62.9 55.5 48.0 40.6 33.1 25.7 67.7
65.5 65.5 65.5 58.0 50.6 43.1 35.7 61.8
62.2 62.2 62.2 54.8 47.3 39.9 32.4 59.3
95°F
67.7 60.8 53.3 45.9 38.4 31.0 23.5
61.8 61.8 61.8 54.3 46.9 39.4 32.0
59.3 59.3 59.3 51.9 44.4 37.0 29.5
105°F
2500
72
67
62
57
72
64.6
59.2
54.6
53.0
66.4
60.8
56.1
54.5
68.2
62.5
57.6
55.9
68.5
62.8
57.8
56.2
68.8
63.0
58.1
56.4
4.8
4.7
4.6
4.7
4.8
4.7
4.6
4.7
4.8
4.7
4.7
4.7
4.8
4.8
4.7
4.7
4.9
4.8
4.7
4.8
37.4 33.1 28.8 24.5 20.2
-
-
61.3
5.4
5.3
5.3
5.3
5.4
5.3
5.3
5.3
5.4
5.3
5.3
5.3
5.4
5.4
5.3
5.3
5.5
5.4
5.3
5.4
35.6 31.3 27.0 22.8 18.5
-
-
47.3 43.0 38.7 34.4 30.2 25.9 21.6 55.7
54.6 52.1 47.8 43.5 39.3 35.0 30.7 51.5
53.0 53.0 49.2 44.9 40.7 36.4 32.1 50.4
45.6 41.3 37.0 32.7 28.4 24.2 19.9
51.5 50.0 45.8 41.5 37.2 32.9 28.6
50.4 50.4 46.5 42.2 38.0 33.7 29.4
1500
41.5 36.4 31.3 26.3 21.2
-
-
62.7
39.5 34.4 29.4 24.3 19.3
-
-
67
52.2 47.2 42.1 37.1 32.0 27.0 21.9 57.0
56.1 54.8 52.0 47.0 41.9 36.9 31.8 52.7
54.5 54.5 53.6 48.5 43.4 38.4 33.3 51.6
50.3 45.3 40.2 35.2 30.1 25.1 20.0
52.7 52.0 49.7 44.7 39.6 34.6 29.5
51.6 51.6 50.6 45.5 40.5 35.4 30.4
1750
62
57
72
45.6 39.7 33.9 28.1 22.2
-
-
64.1
43.4 37.6 31.7 25.9 20.1
-
-
67
57.2 51.4 45.5 39.7 33.9 28.1 22.2 58.3
57.6 57.6 56.3 50.4 44.6 38.8 32.9 53.9
55.9 55.9 57.9 52.1 46.2 40.4 34.6 52.8
55.1 49.3 43.4 37.6 31.8 25.9 20.1
53.9 53.9 53.7 47.9 42.1 36.2 30.4
52.8 52.8 54.6 48.8 43.0 37.1 31.3
2000
62
57
72
49.3 42.6 36.0 29.3 22.7
-
-
64.2
47.1 40.5 33.9 27.2 20.6
-
-
67
60.1 55.0 48.4 41.7 35.1 28.4 21.8 58.4
57.8 57.8 57.2 50.5 43.9 37.2 30.6 54.0
56.2 56.2 57.2 50.5 43.9 37.2 30.6 52.8
56.8 52.8 46.3 39.7 33.1 26.4 19.8
54.0 54.0 53.9 47.3 40.6 34.0 27.3
52.8 52.8 53.8 47.1 40.5 33.9 27.2
2250
62
57
72
67
62
57
53.0 45.5 38.1 30.6 23.2
-
-
64.3
50.9 43.4 36.0 28.5 21.1
-
-
63.0 58.6 51.2 43.7 36.3 28.8 21.4 58.5
58.1 58.1 58.1 50.6 43.2 35.7 28.3 54.1
56.4 56.4 56.4 49.0 41.5 34.1 26.6 52.9
115°F
58.5 56.3 49.2 41.8 34.3 26.9 19.4
54.1 54.1 54.1 46.6 39.2 31.7 24.3
52.9 52.9 52.9 45.5 38.0 30.6 23.1
125°F
2500
72
67
62
57
72
57.9
52.2
48.5
47.8
59.0
53.1
49.3
48.7
60.0
54.1
50.2
49.6
59.9
54.0
50.2
49.5
59.9
53.9
50.1
49.4
6.0
6.0
5.9
5.9
6.0
6.0
5.9
5.9
6.0
5.9
5.9
5.9
6.1
6.0
5.9
6.0
6.1
6.0
6.0
6.0
33.8 29.5 25.3 21.0 16.7
-
-
54.6
6.7
6.6
6.6
6.6
6.7
6.6
6.5
6.6
6.6
6.5
6.5
6.5
6.7
6.6
6.6
6.6
6.7
6.6
6.6
6.6
32.0 27.8 23.5 19.2 14.9
-
-
43.8 39.6 35.3 31.0 26.7 22.5 18.2 48.7
48.5 48.0 43.7 39.4 35.1 30.9 26.6 45.4
47.8 47.8 43.8 39.6 35.3 31.0 26.7 45.2
42.1 37.8 33.6 29.3 25.0 20.7 16.5
45.4 45.4 41.6 37.3 33.1 28.8 24.5
45.2 45.2 41.1 36.9 32.6 28.3 24.0
1500
37.5 32.5 27.4 22.4 17.3
-
-
55.3
35.6 30.5 25.5 20.4 15.4
-
-
67
48.4 43.4 38.3 33.3 28.2 23.1 18.1 49.3
49.3 49.1 47.4 42.4 37.3 32.3 27.2 46.0
48.7 48.7 47.6 42.5 37.5 32.4 27.4 45.8
46.5 41.5 36.4 31.3 26.3 21.2 16.2
46.0 46.0 45.1 40.1 35.0 30.0 24.9
45.8 45.8 44.6 39.6 34.5 29.4 24.4
1750
62
57
72
41.3 35.4 29.6 23.8 17.9
-
-
55.9
39.1 33.3 27.4 21.6 15.8
-
-
67
53.0 47.2 41.3 35.5 29.7 23.8 18.0 49.9
50.2 50.2 51.2 45.3 39.5 33.7 27.9 46.5
49.6 49.6 51.4 45.5 39.7 33.9 28.0 46.4
49.9 45.1 39.2 33.4 27.6 21.7 15.9
46.5 46.5 46.5 42.8 37.0 31.1 25.3
46.4 46.4 46.4 42.2 36.4 30.6 24.7
2000
62
57
72
45.0 38.4 31.7 25.1 18.5
-
-
55.7
42.9 36.3 29.6 23.0 16.3
-
-
67
53.5 50.6 44.3 37.7 31.0 24.4 17.8 49.7
50.2 50.2 50.6 44.0 37.3 30.7 24.1 46.3
49.5 49.5 50.4 43.7 37.1 30.5 23.8 46.1
49.7 48.3 42.3 35.7 29.0 22.4 15.7
46.3 46.3 46.3 40.7 34.1 27.4 20.8
46.1 46.1 46.1 40.4 33.7 27.1 20.4
2250
62
57
72
67
62
57
48.8 41.3 33.9 26.4 19.0
-
-
55.4
46.7 39.2 31.8 24.3 16.9
-
-
53.9 53.9 47.3 39.9 32.4 25.0 17.5 49.4
50.1 50.1 50.1 42.6 35.2 27.7 20.3 46.1
49.4 49.4 49.4 42.0 34.5 27.1 19.6 45.9
49.4 49.4 45.4 37.9 30.5 23.0 15.6
46.1 46.1 46.1 38.6 31.2 23.7 16.3
45.9 45.9 45.9 38.5 31.0 23.6 16.1
2500
1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-
mance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
17
343615-YTG-B-0308
TABLE 19: SUPPLY AIR BLOWER PERFORMANCE (DY036, 048, & 060 DIRECT DRIVE) SIDE DUCT APPLICATION
2
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
0.5 0.6 0.7
0.2
0.3
0.4
0.8
0.9
1.0
1
UNIT
MOTOR
TONNAGE
SPEED
HI
1582 320 1538 335 1496 349 1458 363 1418 376 1381 390 1338 403 1298 417 1255 430
MED/HI 1488 263 1440 276 1396 290 1354 303 1309 316 1263 329 1214 343
1158
358 1085 374
3
MED
1339 208 1292 221 1247 234 1201 246
1152
195 1082 207 1026 220
145 863 158
258
1102
957
-
272 1036 288
967
303
924
313
3
MED/LOW 1233 171
1184
997
183
134
1135
935
235
-
895
-
248
-
-
-
-
-
-
-
-
-
LOW
HI
1081 130
-
-
2056 636 2017 696 1978 714 1942 734 1906 749 1864 764 1815 769 1728 743 1582 685
MED/HI 1866 539 1832 557 1795 571 1754 585 1722 602 1679 619 1636 638 1582 653 1508 639
MED 1680 408 1641 426 1594 438 1558 455 1517 472 1469 490 1415 505 1370 521 1337 536
MED/LOW 1582 362 1541 380 1495 391 1465 406 1426 423 1377 440 1326 455 1292 469 1247 485
3
4
LOW
HI
1300 223 1258 237 1202 247
2256 883 2258 931 2247 950 2223 964 2182 979 2125 971 2044 940 1958 898 1864 854
2119 808 2089 826 2051 844 2014 859 1965 861 1896 843 1801 806
2020 637 1999 656 1985 675 1947 696 1910 715 1876 730 1832 740 1793 756 1725 748
-
-
-
-
-
-
-
-
-
-
-
-
MED/HI 2145 771 2127 784
MED
MED/LOW 1757 413 1713 432 1677 451 1639 468 1597 479 1559 497 1521 513 1472 523
LOW 1570 327 1536 339 1499 356
1. Factory set on medium speed tap.
3
5
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values.
3. Side Duct application (230 Volts)
TABLE 20: SUPPLY AIR BLOWER PERFORMANCE (DY036, 048, & 060 DIRECT DRIVE) BOTTOM DUCT APPLICATION
2
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1
UNIT
MOTOR
TONNAGE
SPEED
HI
1527 320 1485 335 1445 349 1408 363 1370 376 1334 390 1292 403 1254 417 1213 430
MED/HI 1437 263 1391 276 1349 290 1308 303 1265 316 1221 329
1174
343
1120
358 1049 374
3
MED
1293 208 1248 221 1205 234
1161
183 1097 195 1046 207
134 904 145
246
1114
992
-
258 1065 272 1002 288
935
303
894
313
3
MED/LOW 1191
171
1045 130
1144
964
220
-
926
-
235
-
866
-
248
-
-
-
-
-
-
-
-
-
LOW
HI
-
-
1985 636 1947 696 1909 714 1875 734 1840 749 1800 764 1752 769 1668 743 1528 685
MED/HI 1802 539 1768 557 1733 571 1694 585 1662 602 1621 619 1580 638 1528 653 1456 639
MED 1622 408 1585 426 1539 438 1505 455 1465 472 1419 490 1367 505 1324 521 1291 536
MED/LOW 1528 362 1489 380 1444 391 1415 406 1377 423 1330 440 1281 455 1248 469 1205 485
3
4
LOW
HI
1256 223 1216 237
1161
247
-
-
-
-
-
-
-
-
-
-
-
-
2177 883 2179 931 2169 950 2145 964 2106 979 2051 971 1973 940 1890 898 1800 854
MED/HI 2071 771 2053 784 2045 808 2016 826 1980 844 1944 859 1897 861 1830 843 1739 806
MED 1950 637 1929 656 1916 675 1880 696 1844 715 1811 730 1768 740 1731 756 1665 748
MED/LOW 1697 413 1654 432 1619 451 1583 468 1542 479 1506 497 1469 513
LOW 1516 327 1484 339 1448 356
1. Factory set on medium speed tap.
3
5
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values.
3. Bottom Duct application (230 Volts)
18
Johnson Controls Unitary Products
343615-YTG-B-0308
TABLE 21: STATIC RESISTANCES
RESISTANCE, IWG
CFM
DESCRIPTION
1000
1200
0.08
0.05
0.07
0.10
1400
0.09
0.06
0.08
0.12
1600
0.11
0.07
0.09
0.14
1800
2000
0.15
0.10
0.13
0.18
2200
2400
0.20
0.14
0.17
0.23
2600
0.23
0.16
0.20
0.26
2800
0.26
0.19
0.23
0.29
3000
0.30
0.22
0.26
0.32
1,3
ECONOMIZER
ELECTRIC
0.07
0.04
0.06
0.08
0.13
0.08
0.11
0.16
0.17
0.12
0.15
0.20
7-15KW
1
HEATERS
20-30KW
2
COOLING ONLY
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.
3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than
0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 22: ELECTRIC HEAT CFM LIMITATIONS
Minimum Supply Air (CFM)
Heater kW
Size
(Tons)
Voltage
5
7
10
15
20
30
208/230-1-60
208/230-3-60
460-3-60
900
900
900
900
-
900
900
900
900
-
900
900
900
-
3
-
900
900
900
-
600-3-60
-
900
900
900
-
208/230-1-60
208/230-3-60
460-3-60
1200
1200
1200
1200
-
1200
1200
1200
1200
1500
1500
1500
1500
1200
1200
1200
1200
1500
1500
1500
1500
1200
1200
1200
1200
1500
1500
1500
1500
-
-
1200
4
5
-
-
600-3-60
-
-
208/230-1-60
208/230-3-60
460-3-60
1500
1500
1500
1500
-
1500
1500
1500
1500
1500
-
-
600-3-60
Johnson Controls Unitary Products
19
343615-YTG-B-0308
TABLE 23: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET
OD Fan Supply
Pwr
Conv
Outlet
Max
Fuse /
Breaker
Size
(Amps)
30
Compressors
(each)
2
Motors
(each)
Blower
Motor
Electric Heat Option
1
Size
(Tons)
MCA
3
Volt
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages
Amps
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E07
E10
E15
E20
None
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E07
E10
E15
E20
None
E10
E15
E20
-
-
-
22.4
31.5
41.2
55.6
79.0
103.1
22.4
35.1
46.6
62.7
90.3
117.9
18.7
21.4
26.9
35.3
48.8
62.7
18.7
23.4
30.1
39.4
55.3
71.2
10.7
14.0
18.9
24.2
33.1
7.4
15.7
22.1
28.5
29.1
33.5
43.2
57.6
81.0
105.1
29.1
37.1
48.6
64.7
92.3
119.9
24.3
24.3
28.9
37.3
50.8
64.7
24.3
25.4
32.1
41.4
57.3
73.2
12.4
15.0
19.9
25.2
34.1
10.5
16.5
22.9
29.3
4.0
5.6
8.0
11.9
15.9
-
5.3
7.5
10.6
15.9
21.2
-
4.0
5.6
8.0
11.9
15.9
-
5.3
7.5
10.6
15.9
21.2
-
6.8
10.1
13.6
19.5
-
10.6
15.9
21.2
-
4.0
5.6
8.0
11.9
15.9
-
5.3
7.5
10.6
15.9
21.2
-
4.0
5.6
8.0
11.9
15.9
-
5.3
7.5
10.6
15.9
21.2
-
6.8
10.1
13.6
19.5
-
10.6
15.9
21.2
1
1
1
2
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
2
2
-
1
1
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
2
2
-
1
1
2
19.2
26.9
38.5
57.2
76.4
-
23.0
32.6
46.1
69.1
92.2
-
11.1
15.5
22.2
33.0
44.1
-
13.3
18.8
26.6
39.9
53.2
-
35
45
60
80
110
30
40
50
70
100
125
25
25
30
40
50
70
25
25
35
40
60
80
15
15
20
25
35
15
15
25
30
35
40
208-1-60 11.3 68.0 17.5
230-1-60 11.3 68.0 17.5
208-3-60 8.3 68.0 13.0
230-3-60 8.3 68.0 13.0
2.3
6.0
0.0
2.3
2.3
2.3
6.0
6.0
6.0
0.0
0.0
0.0
036
(3.0)
8.5
460-3-60 5.1 34.0
575-3-60 3.2 26.0
8.0
5.0
1.3
1.3
6.0
6.0
0.0
0.0
12.7
17.1
24.5
-
10.6
16.0
21.3
-
19.2
26.9
38.5
57.2
76.4
-
23.0
32.6
46.1
69.1
92.2
-
11.1
15.5
22.2
33.0
44.1
-
13.3
18.8
26.6
39.9
53.2
-
45
60
90
110
35
208-1-60 15.4 86.0 24.0
230-1-60 15.4 86.0 24.0
208-3-60 11.5 84.0 18.0
230-3-60 11.5 84.0 18.0
2.3
2.3
2.3
2.3
7.6
7.6
7.6
7.6
0.0
0.0
0.0
0.0
40
50
70
100
125
30
30
35
40
60
70
30
35
35
45
60
80
15
15
20
25
35
15
20
25
30
048
(4.0)
8.5
460-3-60 5.8 42.0
575-3-60 5.1 34.0
9.0
8.0
1.3
1.3
7.6
7.6
0.0
0.0
12.7
17.1
24.5
-
10.6
16.0
21.3
20
Johnson Controls Unitary Products
343615-YTG-B-0308
TABLE 23: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET (CONT)
OD Fan Supply
Pwr
Conv
Outlet
Max
Compressors
(each)
2
Motors
(each)
Blower
Motor
Electric Heat Option
Fuse /
Breaker
Size
1
Size
(Tons)
MCA
3
Volt
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages
Amps
(Amps)
None
E05
E07
E10
E15
E20
E30
None
E05
E07
E10
E15
E20
E30
None
E05
E07
E10
E15
E20
E30
None
E05
E07
E10
E15
E20
E30
None
E07
E10
E15
E20
E30
None
E10
E15
E20
E30
-
-
-
45.9
45.9
45.9
57.6
81.0
105.1
142.9
45.9
45.9
48.6
64.7
92.3
119.9
163.7
31.5
31.5
31.5
37.3
50.8
64.7
86.5
31.5
31.5
32.1
41.4
57.3
73.2
98.5
17.1
17.1
19.9
25.2
34.1
48.1
13.3
16.5
22.9
29.3
40.4
50
50
50
60
4.0
5.6
8.0
11.9
15.9
22.2
-
5.3
7.5
10.6
15.9
21.2
29.6
-
4.0
5.6
8.0
11.9
15.9
22.2
-
5.3
7.5
10.6
15.9
21.2
29.6
-
1
1
1
2
2
2
-
1
1
1
2
2
2
-
1
1
1
2
2
2
-
1
1
1
2
2
2
-
19.2
26.9
38.5
57.2
76.4
106.7
-
23.0
32.6
46.1
69.1
92.2
128.7
-
11.1
15.5
22.2
33.0
44.1
61.6
-
13.3
18.8
26.6
39.9
53.2
74.3
-
208-1-60 28.8 145.0 45.0
230-1-60 28.8 145.0 45.0
208-3-60 17.3 123.0 27.0
230-3-60 17.3 123.0 27.0
2.3
7.6
0.0
90
110
150
50
50
50
2.3
2.3
2.3
7.6
7.6
7.6
0.0
0.0
0.0
70
100
125
175
35
35
35
40
60
70
90
35
35
35
45
60
80
100
20
20
20
25
35
50
15
20
25
30
060
(5.0)
6.8
1
1
2
2
2
-
1
1
2
2
8.5
10.1
13.6
19.5
28.8
-
10.6
15.9
21.2
30.4
12.7
17.1
24.5
36.1
-
10.6
16.0
21.3
30.5
460-3-60 9.6 70.0 15.0
1.3
1.3
7.6
7.6
0.0
0.0
575-3-60 7.4 53.0 11.5
40
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
21
343615-YTG-B-0308
TABLE 24: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/ POWERED CONVENIENCE OUTLET
OD Fan Supply
Pwr
Conv
Outlet
Max
Fuse /
Breaker
Size
(Amps)
40
Compressors
(each)
2
Motors
(each)
Blower
Motor
Electric Heat Option
1
Size
(Tons)
MCA
3
Volt
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages
Amps
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E07
E10
E15
E20
None
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E05
E07
E10
E15
E20
None
E07
E10
E15
E20
None
E10
E15
E20
-
-
-
32.4
44.0
53.7
68.1
91.5
115.6
32.4
47.6
59.1
75.2
102.8
130.4
29.1
33.9
39.4
47.8
61.3
75.2
29.1
35.9
42.6
51.9
67.8
83.7
15.7
20.2
25.2
30.4
39.3
11.6
20.7
27.1
33.5
39.1
46.0
55.7
70.1
93.5
117.6
39.1
49.6
61.1
77.2
104.8
132.4
34.3
35.9
41.4
49.8
63.3
77.2
34.3
37.9
44.6
53.9
69.8
85.7
17.4
21.2
26.2
31.4
40.3
14.5
21.5
27.9
34.3
4.0
5.6
8.0
11.9
15.9
-
5.3
7.5
10.6
15.9
21.2
-
4.0
5.6
8.0
11.9
15.9
-
5.3
7.5
10.6
15.9
21.2
-
6.8
10.1
13.6
19.5
-
10.6
15.9
21.2
-
4.0
5.6
8.0
11.9
15.9
-
5.3
7.5
10.6
15.9
21.2
-
4.0
5.6
8.0
11.9
15.9
-
5.3
7.5
10.6
15.9
21.2
-
6.8
10.1
13.6
19.5
-
10.6
15.9
21.2
1
1
1
2
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
2
2
-
1
1
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
2
2
-
1
1
2
19.2
26.9
38.5
57.2
76.4
-
23.0
32.6
46.1
69.1
92.2
-
11.1
15.5
22.2
33.0
44.1
-
13.3
18.8
26.6
39.9
53.2
-
45
60
70
100
125
40
50
60
208-1-60 11.3 68.0 17.5
230-1-60 11.3 68.0 17.5
208-3-60 8.3 68.0 13.0
230-3-60 8.3 68.0 13.0
2.3
6.0
10.0
2.3
2.3
2.3
6.0
6.0
6.0
10.0
10.0
10.0
80
110
150
35
35
40
50
70
80
35
40
45
60
70
90
20
20
25
30
40
15
20
30
35
50
50
60
80
100
125
50
036
(3.0)
8.5
460-3-60 5.1 34.0
575-3-60 3.2 26.0
8.0
5.0
1.3
1.3
6.0
6.0
5.0
4.0
12.7
17.1
24.5
-
10.6
16.0
21.3
-
19.2
26.9
38.5
57.2
76.4
-
23.0
32.6
46.1
69.1
92.2
-
11.1
15.5
22.2
33.0
44.1
-
13.3
18.8
26.6
39.9
53.2
-
208-1-60 15.4 86.0 24.0
230-1-60 15.4 86.0 24.0
208-3-60 11.5 84.0 18.0
230-3-60 11.5 84.0 18.0
2.3
2.3
2.3
2.3
7.6
7.6
7.6
7.6
10.0
10.0
10.0
10.0
50
70
80
110
150
45
45
45
50
70
80
45
45
45
60
70
90
20
20
25
30
40
15
20
30
35
048
(4.0)
8.5
460-3-60 5.8 42.0
575-3-60 5.1 34.0
9.0
8.0
1.3
1.3
7.6
7.6
5.0
4.0
12.7
17.1
24.5
-
10.6
16.0
21.3
22
Johnson Controls Unitary Products
343615-YTG-B-0308
TABLE 24: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/ POWERED CONVENIENCE OUTLET (CONT)
OD Fan Supply
Pwr
Conv
Outlet
Max
Compressors
(each)
2
Motors
(each)
Blower
Motor
Electric Heat Option
Fuse /
Breaker
Size
1
Size
(Tons)
MCA
3
Volt
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages
Amps
(Amps)
None
E05
E07
E10
E15
E20
E30
None
E05
E07
E10
E15
E20
E30
None
E05
E07
E10
E15
E20
E30
None
E05
E07
E10
E15
E20
E30
None
E07
E10
E15
E20
E30
None
E10
E15
E20
E30
-
-
-
55.9
55.9
55.9
70.1
93.5
117.6
155.4
55.9
55.9
61.1
77.2
104.8
132.4
176.2
41.5
41.5
41.5
49.8
63.3
77.2
99.0
41.5
41.5
44.6
53.9
69.8
85.7
111.0
22.1
22.1
26.2
31.4
40.3
54.3
17.3
21.5
27.9
34.3
45.4
60
60
60
80
100
125
175
60
60
70
4.0
5.6
8.0
11.9
15.9
22.2
-
5.3
7.5
10.6
15.9
21.2
29.6
-
4.0
5.6
8.0
11.9
15.9
22.2
-
5.3
7.5
10.6
15.9
21.2
29.6
-
1
1
1
2
2
2
-
1
1
1
2
2
2
-
1
1
1
2
2
2
-
1
1
1
2
2
2
-
19.2
26.9
38.5
57.2
76.4
106.7
-
23.0
32.6
46.1
69.1
92.2
128.7
-
11.1
15.5
22.2
33.0
44.1
61.6
-
13.3
18.8
26.6
39.9
53.2
74.3
-
208-1-60 28.8 145.0 45.0
230-1-60 28.8 145.0 45.0
208-3-60 17.3 123.0 27.0
230-3-60 17.3 123.0 27.0
2.3
7.6
10.0
2.3
2.3
2.3
7.6
7.6
7.6
10.0
10.0
10.0
80
110
150
200
45
45
45
50
70
80
100
45
45
45
60
70
90
125
25
25
25
060
(5.0)
6.8
1
1
2
2
2
-
1
1
2
2
8.5
10.1
13.6
19.5
28.8
-
10.6
15.9
21.2
30.4
12.7
17.1
24.5
36.1
-
10.6
16.0
21.3
30.5
460-3-60 9.6 70.0 15.0
1.3
1.3
7.6
7.6
5.0
4.0
30
40
60
20
20
30
35
45
575-3-60 7.4 53.0 11.5
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
23
343615-YTG-B-0308
TABLE 25: DY PHYSICAL DATA
DY
MODELS
036
12 X 10
3/4
3
048
12 X 10
1
060
12 X 10
1
Centrifugal Blower (Dia. x Wd. in.)
Fan Motor HP (Direct Drive)
Rows Deep
EVAPORATOR
BLOWER
4
4
EVAPORATOR
COIL
Fins Per Inch
13
13
13
2
Face Area (Ft. )
5.1
24
5.1
24
5.1
24
Propeller Dia. (in.)
Fan Motor HP
Nom. CFM
CONDENSER
FANS
1/2
4200
2
1/2
4200
2
1/2
4200
2
Rows Deep
CONDENSER
COILS
Fins Per Inch
18
18
18
2
Face Area (Ft. )
17.1
1
17.1
1
17.1
1
Quantity
COMPRESSOR
Type
Recip.
2
Recip.
2
Scroll
2
Quantity Per Unit (15” X 20” X 1” or 2“)
Quantity Per Unit (14” X 25” X 1” or 2“)
AIR
FILTERS
1
1
1
2
Total Face Area (Ft. )
6.3
9/4
6.3
9/8
6.3
11/8
CHARGE
Refrigerant 22 (lbs./oz.)
1
TABLE 26: ELECTRIC HEAT CORRECTION FACTORS
kW CAP. MULTI-
TABLE 27: VOLTAGE LIMITATIONS
VOLTAGE
NOMINAL VOLTAGE
VOLTAGE
POWER SUPPLY
PLIER
MIN.
MAX.
208
230
460
575
1.00
0.92
0.92
0.92
208
240
480
600
208/230-1-60
208/230-3-60
187
252
252
187
460-3-60
575-3-60
432
540
504
630
1. Utilization Range “A” in accordance with ARI Standard
110.
24
Johnson Controls Unitary Products
343615-YTG-B-0308
TYPICAL POWER WIRING
REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTEC-
TION AND WIRING.
TYPICAL CONTROL WIRING
COOLING ONLY (24 VOLT THERMOSTAT)
COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT1 UNIT TERMINAL
THERMOSTAT1
TERMINALS
TERMINALS
STRIP TB1
UNIT TERMINAL
RV
R
RH
STRIP TB1
ADD
JUMPER
24 VOLT
YC
GF
Y1
Y2
G
RC
Y
R
Y1
Y2
W1
W2
G
TRANSFORMER
24 VOLT
TRANSFORMER
W
G
C
124 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.
C
COOLING / HEATING (ELECTRONIC THERMOSTAT)
MULTI STAGE
1
24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF
HEAT, USE THERMOSTAT 2TH0471024.
1
THERMOSTAT
TERMINALS
UNIT TERMINAL
STRIP TB1
RC
RH
Y1
24 VOLT
TRANSFORMER
ADD
JUMPER
R
Y1
Y2
W1
W2
G
COOLING / HEATING (ELECTRONIC THERMOSTAT)
SINGLE STAGE
2
3
Y2
W1
THERMOSTAT1
4
W2
UNIT TERMINAL
STRIP TB1
TERMINALS
G
B
RH
RC
Y
C
R
Y1
W1
G
LED 1
X
ADD
JUMPER
NOT
USED
LED 2
COM
A1
OCC
W
4
G
ADD
JUMPER
C
A2
24 VOLT
TRANSFORMER
T
TO REMOTE SENSOR
2TH040702224 IF USED
T
1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).
2 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.
1ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT
2TH04700224.
3 SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE
ELECTRIC HEATER OR 2 STAGE GAS HEAT.
4
REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.
FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING
Johnson Controls Unitary Products
25
343615-YTG-B-0308
FIGURE 3 - UNIT DIMENSIONS (3 - 5 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW
FIGURE 4 - UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEAT) FRONT VIEW
26
Johnson Controls Unitary Products
343615-YTG-B-0308
DETAIL “A”
FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD
DETAIL “B”
FIGURE 6 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD
Johnson Controls Unitary Products
27
343615-YTG-B-0308
FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)
TABLE 29: MINIMUM CLEARANCES
LOCATION
Filter Access
CLEARANCE
Blower Motor Access
Dot Plugs
24” (Cooling/Electric Heat)
32” (Gas Heat)
Front
Rear
12” (Less Economizer)
36” (With Economizer or Fixed
Air/Motorized Damper)
Field-Supplied Disconnect
Switch Location
24” (Less Economizer)
36” (With Economizer)
Mounting Bracket for
Disconnect Switch
Left Side (Filter Access)
A,B
(Field Supplied)
Wiring Entry
(See Detail “B”)
Control Box Access
Right Side (Cond. Coil)
Below Unit1
24”
0”
Disconnect Switch Location
and Motor Access Panel for
Unit with “Belt-Drive” Option
72” (For
Condenser Air Discharge)
Above Unit2
FIGURE 8 - DISCONNECT/BLOWER ACCESS LOCATION
TABLE 28: UTILITIES ENTRY
1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.
HOLE
A
OPENING SIZE (DIA.)
USED FOR
Side
Bottom
Side
1
2
7/8” KO
Control Wiring
B
Power Wiring
2” KO
Bottom
C
D
1-5/8” KO
1-1/2” KO
Gas Piping (Front)
Gas Piping (Bottom)
1. Opening in the bottom to the unit can be located by the
side in the insulation.
2. Do not remove the 2” knockout ring.
28
Johnson Controls Unitary Products
343615-YTG-B-0308
FIGURE 9 - TYPICAL APPLICATIONS
Johnson Controls Unitary Products
29
343615-YTG-B-0308
BACK OF UNIT
BACK OF UNIT
A
A
7
7
44 /8
44 /8
1
1
82 /4
82 /4
B
D
F
X
X
B
C
E
APPROXIMATE
APPROXIMATE
CENTER OF GRAVITY
CENTER OF GRAVITY
CONDENSER COIL
END OF UNIT
CONDENSER COIL
END OF UNIT
C
D
FRONT OF UNIT
FRONT OF UNIT
Y
Y
FIGURE 10 -FOUR AND SIX POINT LOADING
TABLE 30: DY 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION
4-Point Loading (lb)
6-Point Loading (lb)
UNIT
TOTAL
A
B
C
D
A
B
C
D
E
F
132
141
143
145
148
134
145
150
135
147
149
151
125
133
135
138
140
127
138
142
128
139
141
143
155
166
168
171
174
158
171
177
159
173
175
178
164
175
178
181
184
167
181
187
168
182
185
188
89
95
85
91
93
94
96
87
94
97
88
95
97
98
82
88
89
91
92
84
91
94
84
92
93
95
102
110
111
113
115
104
113
117
105
114
116
118
106
114
115
117
119
108
117
121
109
118
120
122
110
118
120
122
124
112
122
125
113
123
125
126
DY036 Cooling/ Electric
DY036N04
575
615
625
635
645
585
635
655
590
640
650
660
96
DY036D06
98
DY036N08
99
DY036D10
90
DY048 Cooling/ Electric
DY048(D,N)06
DY048(D,N)10
DY060 Cooling/ Electric
DY060D06
98
101
91
99
100
102
DY060N08
DY060(D,N)10
TABLE 31: CENTER OF GRAVITY
DIMENSION
3 - 5 TON
40”
X
Y
20”
30
Johnson Controls Unitary Products
343615-YTG-B-0308
TABLE 32: OPERATING WEIGHTS (LBS.)
MODEL SIZE
DY (Cooling Only)
3 TON
575
615
-
4 TON
585
-
5 TON
590
-
N04
N06
N08
N10
D06
D10
635
-
-
BASIC
UNIT
635
-
650
660
640
660
DY
(Gas/Electric)
655
635
655
50
625
645
Economizer
Motorized Damper
26
OPTIONS
ACCY.
5 - 7 kW
10 - 15 kW
20 - 30 kW
18
Electric Heater
23
28
Roof Curb
Barometric Relief / Fixed Air Damper
92
10
FIGURE 11 -ROOF CURB DIMENSIONS
Johnson Controls Unitary Products
31
343615-YTG-B-0308
UNIT CABINET
GUIDE SPECIFICATIONS
Unit cabinet shall be constructed of a combination of G60 and
G90 galvanized steel, with exterior surfaces coated with a
non-chalking, powdered paint finish, certified at 750 hours
salt spray test per ASTMB117 standards. Indoor blower sec-
tion shall be insulated with a minimum 1/2” thick insulation,
coated on the airside. Aluminum foil faced insulation shall be
used in the furnace compartment and be fastened with ridged
fasteners to prevent insulation from entering the air stream.
Cabinet panels shall be “large” size, easily removable for ser-
vicing and maintenance. Full perimeter base rails shall be
provided to assure reliable transit of equipment, overhead rig-
ging and proper sealing on roof curb applications. Disposable
1" filters shall be furnished and be accessible through a
removable access door, sealed airtight. Units filter track shall
be designed to accommodate either 1" or 2" filters. Fan per-
formance measuring ports shall be provided on the outside of
the cabinet to allow accurate air measurements of evaporator
fan performance without removing panels or creating air by-
pass of the coils. Condensate pan shall be internally sloped
and conform to ASHRAE 62-89 self-draining standards. Con-
densate connection shall be a minimum of 3/4” I.D. female
and be a ridged mount connection.
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
York's Sunline Magnum™ units are convertible single pack-
age units. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at ground
level or set on steel beams above a finished roof. Cooling
only, cooling with gas heat and cooling with electric heat
models are available with a wide variety of factory-mounted
options and field-installed accessories to make them suitable
for almost every application. All units are self-contained and
assembled on full perimeter base rails with holes in the four
corners for overhead rigging. Every unit is completely piped,
wired, charged and tested at the factory to simplify the field
installation and to provide years of dependable operation. All
models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. Models with
power exhaust are suitable for bottom duct connections only.
For bottom duct, remove the sheet metal panels from the
supply and return air openings through the base of the unit.
For horizontal duct, remove the supply and return air panels
on the rear of the unit.
INDOOR (EVAPORATOR) FAN ASSEMBLY
The indoor fan shall be a factory installed direct drive. Job
site selected (B.H.P.) brake horsepower shall not exceed the
motors nameplate horsepower rating, plus the service factor.
Units shall be designed not to operate above service factor.
Fan wheel shall be double-inlet type with forward-curved
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
air volume. Bearings shall be sealed and permanently lubri-
cated for longer life and no maintenance.
All non-Scroll compressors include crankcase heaters and all
compressors have internal pressure relief. Every refrigerant
circuit includes a liquid line filter-drier, a discharge line high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch.The unit control circuit
includes a 75 VA transformer, a 24-volt circuit breaker and a
relay board with a compressor lockout circuit, a terminal strip
for thermostat wiring, plus an additional set of pin connectors
to simplify the interface of additional field controls. All models
are CSA listed. All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater ele-
ments carry a 5-year warranty. Aluminized steel and Stainless
steel tubular heat exchangers carry a 10-year warranty.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to a
corrosion resistant steel spider bracket and shall be dynami-
cally balanced for smooth operation. The outdoor fan motor
shall be totally enclosed with permanently lubricated bear-
ings, internally protected against overload conditions and
staged independently.
DESCRIPTION
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat
and designed for outdoor mounted installation.
REFRIGERANT COMPONENTS
The 3 ton, 4 ton and 5 ton units shall have minimum SEER
rating of 14. They shall have built-in field convertible duct
connections for down discharge supply/return or horizontal
discharge supply/return, and be available with factory
installed options or field installed accessories. The units shall
be factory wired, piped, charged with R-22 refrigerant and
factory tested prior to shipment. All unit wiring shall be both
numbered and color coded. All units the cooling performance
shall be rated in accordance with DOE and ARI test proce-
dures. Units shall be CSA listed, classified to ANSI Z21.47,
UL 1995/CSA No. 236 standards.
Compressor:
a. Shall be internally protected with internal high-pres-
sure relief and over temperature protection.
b. Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on a dedicated, independent mounting.
32
Johnson Controls Unitary Products
343615-YTG-B-0308
Coils:
dant main gas valve. Venter wheel shall be constructed of
stainless steel for corrosion resistance. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 25°F. Burners shall be of the
inshot type, constructed of aluminum coated steel and con-
tain air mixture adjustments. All gas piping shall enter the unit
cabinet at a single location through either the side or curb
without any field modifications. Integrated control boards
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the fol-
lowing minimum protection:
a. Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
b. Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent fixed-orifice or thermally operated
expansion devices.
a. Primary and auxiliary high-temperature limit switches.
b. Induced draft motor speed sensor.
c. Flame roll out switch.
b. Filter drier/strainer to eliminate any moisture or for-
eign matter.
c. Accessible service gage connections on both suc-
tion and liquid lines to charge, evacuate, and mea-
sure refrigerant pressure during any necessary
servicing or troubleshooting, without losing charge.
d. Flame proving controls.
e. If any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic
code that indicates which safety switch has tripped.
d. The refrigeration system shall provide at least 15°F
of sub-cooling at design conditions.
ELECTRIC HEATING SECTION
UNIT CONTROLS
An electric heating section, with nickel chromium elements,
shall be provided in a range of 5 thru 30 KW, offering two
stages of capacity - 16 KW and above on 208/230 volt heaters
and 20 KW and above on 460 and 575 volt heaters. The heat-
ing section shall have a primary limit control(s) and automatic
reset to prevent the heating element system from operating at
an excessive temperature. The heating section assembly
shall slide out of the unit for easy maintenance and service.
Units with Electric Heating shall be wired for a single point
power supply with branch circuit fusing (where required).
a. Unit shall be complete with self-contained low-volt-
age control circuit protected by a resetable circuit
breaker on the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which pro-
vides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.
c. Loss-of-charge/Low-pressure switch.
d. High-pressure switch.
UNIT OPERATING CHARACTERISTICS
e. Freeze-protection thermostat, evaporator coil.
a. Unit shall be capable of starting and running at 125°F
outdoor temperature, exceeding maximum load crite-
ria of ARI Standard 210/240. The compressor, with
standard controls, shall be capable of operation
down to 0°F outdoor temperature. Unit shall be pro-
vided with fan time delay to prevent cold air delivery
before heat exchanger warms up (Gas heat only).
f. Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.
g. Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.
h. Unit control board shall have on-board diagnostics
and fault code display.
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
i.
Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0°F.
j.
Control board shall monitor each refrigerant safety
switch independently.
STANDARD LIMITED WARRANTIES
k. Control board shall retain last 5 fault codes in non
volatile memory which will not be lost in the event of
a power loss.
•
•
•
•
Compressor 5 Years
Heat Exchanger 10 Years
Electric Heat Element 5 Years
Other Parts 1 Year
GAS HEATING SECTION (SINGLE OR 2 STAGE)
Shall be designed with induced draft combustion with post
purge logic, energy saving direct spark ignition, and redun-
Johnson Controls Unitary Products
33
343615-YTG-B-0308
OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
•
HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude. Must be used with propane conversion kit.
•
ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER- Outdoor and return air dampers that are inter-
locked and positioned by a fully-modulating, spring
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/fil-
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully
close on power loss.
•
•
LOW NOX - Required to reduce the emission of nitrogen
oxides below 40 nanograms per joule.
GAS PIPING - Contains 1/2” pipe nipples, fittings and
gas cock (including panel assess gaskets) required for
bottom gas supply connection with external shut off.
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
•
ELECTRIC HEATERS
•
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD -
Contains all hood panels and the hardware for assem-
bling.
•
•
•
•
MANUAL OUTDOOR AIR DAMPER
COIL GUARD KIT - Guard for cooling coil.
HAIL GUARD
FLUE EXHAUST EXTENSION
OTHER FACTORY INSTALLED OPTIONS
•
POWER EXHAUST OPTION - To work in conjunction
•
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air
dampers are positioned by a 2-position, spring-return
damper actuator. The maximum leakage rate for the out-
door air intake dampers shall not exceed 2% when
dampers are fully closed and operating against a pres-
sure differential of 0.5 IWG. A unit-mounted potentiome-
ter shall be provided to adjust the outdoor damper
assembly to take in the design CFM of outdoor air to
meet the ventilation requirements of the conditioned
space during normal operation. Whenever the indoor fan
motor is energized, the dampers open up to one of two
pre-selected positions - regardless of the outdoor air
enthalpy. Dampers return to the fully closed position
when the indoor fan motor is de-energized. Dampers
shall fully close on power loss.
with economizers.
•
•
•
•
STAINLESS STEEL HEAT EXCHANGER
STAINLESS STEEL DRAIN PAN
BOTTOM DRAIN CONNECTION
TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL
•
•
•
•
•
•
•
ELECTRONIC SINGLE ENTHALPY ECONOMIZER
DIRTY FILTER SWITCH
PHASE MONITOR
COIL GUARD
POWERED GFI CONVENIENCE OUTLET
NON-POWERED GFI CONVENIENCE OUTLET
®
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
BAS CONTROLS (S implicity INTELLI-Comfort™,
CPC, JOHNSON, HONEYWELL, NOVAR)
•
ROOF CURB - 14"and 8” high, full perimeter curb with
wood nailer (shipped knocked-down).
•
•
BAS READY ECONOMIZER (2-10 V.D.C. ACTUATOR
WITHOUT A CONTROLLER)
•
BAROMETRIC RELIEF DAMPER - Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit.
HINGED FILTER DOOR ACCESS AND TOOLESS
ACCESS PANELS
•
•
•
•
2" PLEATED FILTERS
•
•
PROPANE CONVERSION KIT - Contains new orifices
and gas valve parts to convert from natural to L.P. gas.
One per unit required.
DISCONNECT SWITCH
SUPPLY AIR SMOKE DETECTOR
RETURN AIR SMOKE DETECTOR
HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude.
34
Johnson Controls Unitary Products
343615-YTG-B-0308
Johnson Controls Unitary Products
35
Subject to change without notice. Printed in U.S.A.
343615-YTG-B-0308
Copyright © 2008 by Johnson Controls, Inc. All rights reserved.
Supersedes: 343615-YTG-A-0807
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
|