York Sunline Magnum Dy 060 User Manual

343615-YTG-B-0308  
®
DESCRIPTION  
YORK Sunline Magnumunits are convertible single pack-  
age air conditioners with a common cabinet and a common  
roof curb for the 3, 4 and 5 ton sizes. The units were  
designed for light commercial and commercial applications.  
They can easily be installed on a roof curb, slab, roof jack or  
frame.  
TECHNICAL GUIDE  
SINGLE PACKAGE GAS/ELECTRIC UNITS  
AND SINGLE PACKAGE  
All units include:  
Powder Paint finish that meets ASTM-B-117 750 hour salt  
spray standards  
AIR CONDITIONERS  
Permanently lubricated motors  
DY 036, 048 & 060  
Bottom or side air discharge configuration capability  
(field convertible)  
3, 4 & 5 NOMINAL TONS  
Manufactured under the quality standards of ISO9001  
14.00 SEER  
®
S implicity Control Board  
Copper tube/aluminum fin coils  
Easy access to all components  
Rigging holes in base rails for lifting  
Fork lift slots on three sides  
Single point power connection  
Complete factory package - tested, charged and wired  
CSA agency listing on all units  
WARRANTY  
Factory Limited Parts Warranty  
One-year parts warranty  
A Five-year parts warranty on the compressor and  
electric heat elements.  
Ten-year parts warranty on the gas-fired heat  
exchangers.  
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE  
 
343615-YTG-B-0308  
PRODUCT NOMENCLATURE  
3-5 Ton Sunline Magnum™ Model Number Nomenclature  
D Y 048 N04 A 2 A AA 2 0 1 2 4 A  
Product Category  
Product Style  
D = A/C, Single Pkg., R-22  
A = Style A  
Product Identifier  
Y = 14.0 SEER  
Configuration Options (not required for all units)  
These four digits will not be assigned until a quote is requested, or an order placed.  
SS Drain Pan  
CPC Controller, DFS, APS  
Johnson Controller, DFS, APS  
Nominal Cooling Capacity  
Honeywell Controller, DFS, APS  
036 = 3.0 Ton  
048 = 4.0 Ton  
060 = 5.0 Ton  
Novar Controller, DFS, APS  
Simplicity IntelliComfort Controller  
Simplicity IntelliComfort Controller w/ModLinc  
2" Pleated filters  
Heat Type and Nominal Heat Capacity  
BAS Ready Economizer (2-10 V.D.C. Actuator without a Controller)  
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned  
C00 = Cooling Only. Suitable for Field  
Installed Electric Heat  
Product Generation  
2 = Second Generation  
Gas Heat Options  
N04 = 40 MBH Output Aluminized Steel, 1 Stage (036)  
N06 = 60 MBH Output Aluminized Steel, 1 Stage (048)  
N08 = 80 MBH Output Aluminized Steel, 1 Stage  
(036, 060)  
Additional Options  
Hinged Filter Door & Toolless Access Cabinet  
N10 = 100 MBH Output Aluminized Steel, 1 Stage  
(048, 060)  
Standard Cabinet  
D06 = 60 MBH Output Aluminized Steel, 2 Stage  
(036, 048, 060)  
AA = None  
BA = Hinged Filter Door & Toolless Access Panels  
BB = Phase Monitor, Hinged Filter Door & Toolless  
Access Panels  
BC = Coil Guard, Hinged Filter Door & Toolless  
Access Panels  
BD = Dirty Filter Switch, Hinged Filter Door &  
Toolless Access Panels  
BE = Phase Monitor & Coil Guard, Hinged Filter  
Door & Toolless Access Panels  
BF = Phase Monitor & Dirty Filter Switch, Hinged  
Filter Door & Toolless Access Panels  
BG = Coil Guard & Dirty Filter Switch, Hinged Filter  
Door & Toolless Access Panels  
AB = Phase Monitor  
D10 = 100 MBH Output Aluminized Steel, 2 Stage  
(036*, 048, 060)  
AC = Coil Guard  
AD = Dirty Filter Switch  
S04 = 40 MBH Output Stainless Steel, 1 Stage (036)  
S06 = 60 MBH Output Stainless Steel, 1 Stage (048)  
S08 = 80 MBH Output Stainless Steel, 1 Stage  
(036, 060)  
AE = Phase Monitor & Coil Guard  
AF = Phase Monitor & Dirty Filter Switch  
AG = Coil Guard & Dirty Filter Switch  
AH = Phase Monitor, Coil Guard & Dirty Filter Switch  
AS = Bottom Drain Connection  
RC = Coil Guard & American Flag  
TA = Technicoat Condenser Coil  
TJ = Technicoat Evaporator Coil  
TS = Technicoat Evaporator and Condenser Coil  
S10 = 100 MBH Output Stainless Steel, 1 Stage  
(048, 060)  
T06 = 60 MBH Output Stainless Steel, 2 Stage  
(036, 048, 060)  
T10 = 100 MBH Output Stainless Steel, 2 Stage  
(036*, 048, 060)  
BH = Phase Monitor, Coil Guard & Dirty Filter Switch,  
Hinged Filter Door & Toolless Access Panels  
Electric Heat Options  
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be  
located in digits 15-18.  
E05 = 5 KW  
E07 = 7 KW  
E10 = 10 KW  
E15 = 15 KW  
E20 = 20 KW  
E30 = 30 KW  
Installation Options  
A = No Options Installed  
B = Option 1  
*(D, T)10 = 92 MBH Output on 036 Models  
Airflow  
C = Option 2  
D = Options 1 & 2  
E = Option 3  
F = Option 4  
A = Direct Drive  
B = Direct Drive/Single Input Economizer  
D = Direct Drive/Motorized Damper  
G = Options 1 & 3  
H = Options 1 & 4  
J = Options 1, 2 & 3  
K = Options 1, 2, & 4  
L = Options 1,3 & 4  
M = Options 1, 2, 3, & 4  
N = Options 2 & 3  
P = Options 2 & 4  
Q = Options 2, 3, & 4  
R = Options 3 & 4  
S = Option 5  
Voltage  
1 = 208/230-1-60  
2 = 208/230-3-60  
4 = 460-3-60  
5 = 575-3-60  
T = Options 1 & 5  
U = Options 1, 3, & 5  
V = Options 1, 4, & 5  
W = Options 1, 3, 4, & 5  
X = Options 3 & 5  
Y = Options 4 & 5  
Z = Options 3, 4 & 5  
Options  
1 = Disconnect  
2 = Non-Pwr'd Conv. Outlet  
3 = Smoke Detector S.A.  
4 = Smoke Detector R.A.  
5 = Pwr'd Conv. Outlet  
Johnson Controls Unitary Products  
3
 
343615-YTG-B-0308  
gas valve, if applicable, and the temperature limit  
switch on gas heat units. The unit control board will  
alarm on ignition failures, compressor lockouts and  
repeated limit switch trips.  
FEATURES  
All models are available with a wide variety of factory-  
mounted options such as stainless steel heat exchangers,  
electric heaters, phase monitor, convenience outlet, dirty filter  
switch, disconnect switch, smoke detectors, and coil guard to  
make them suitable for almost every application.  
Nuisance Trip Protection- To prevent nuisance  
trouble calls, the control board uses a “three strikes,  
you’re out” philosophy. The high and low-pressure  
switches and the freezestats must trip three times  
within two hours before the unit control board will  
lock out the compressor.  
All units are self-contained and assembled on full perimeter  
base rails with forklift holes on three sides and holes for over-  
head rigging. Every unit is completely piped, wired, charged  
and tested at the factory to simplify the field installation and to  
provide years of dependable operation.  
On Board Diagnostics - Each alarm will energize a  
trouble light on the thermostat, if so equipped, and  
flash an alarm code on the control board LED. Each  
high and low-pressure switch alarm as well as each  
freezestat alarm has its own flash code. The control  
board saves the five most recent alarms in memory,  
and these alarms can be reviewed at any time.  
Alarms and programmed values are retained  
through the loss of power.  
All models (including those with an economizer) are suitable  
for either bottom or horizontal duct connections. For bottom  
duct, remove the sheet metal panels from the supply and  
return air openings through the base of the unit. For horizon-  
tal duct, remove the supply and return air panels on the rear  
of the unit.  
All models are available with these “factory mounted” outdoor  
air damper options:  
All units have long lasting powder paint cabinets with 750 hour  
salt spray test approval under ASTM-B117 procedures.  
Single enthalpy economizer  
Motorized outdoor air damper  
All models are CSA listed.  
Warranty - All models include a one-year limited parts  
warranty on the complete unit. Compressors and electric  
heater elements carry a five-year warranty. Gas heat  
exchangers carry a 10-year parts warranty.  
Supply air blowers are equipped with a 5 speed direct drive  
motor that can be adjusted to meet the exact requirements of  
the job.  
Gas Heat Operation - All single phase models with gas  
heat have minimum annual fuel utilization efficiency  
(AFUE) of 80%. All three phase models with gas heat  
have minimum steady state efficiency of 80%. Each sec-  
tion includes a durable heat exchanger with aluminized  
steel or optional stainless steel tubes, a redundant gas  
valve, spark ignition, power venting, an ignition module  
for 100% shut-off and all of the safety controls required  
to meet the latest ANSI standards.  
All compressors are equipped with internal pressure relief.  
Every refrigerant circuit includes a liquid line filter-drier, a high  
pressure switch and a suction line with a freezestat and low  
pressure/loss of charge switch to protect all system compo-  
nents.  
®
®
S implicity Controls - S implicity control boards have  
standardized a number of features previously available  
only as options or by utilizing additional controls.  
Low Ambient - An integrated low-ambient control  
allows all units to operate in the cooling mode down  
to 0ºF outdoor ambient without additional assis-  
tance. Optionally, the control board can be pro-  
grammed to lockout the compressors when the  
outdoor air temperature is low or when free cooling  
is available.  
The gas supply piping can be routed into the heating  
compartment through a hole in the base pan of the unit  
or through a knockout in the piping panel on the front of  
the unit.  
Electric Heat Operation - All electric heat models are  
wired for a single power source and include a bank of  
nickel chromium elements mounted at the discharge of  
the supply air blower to provide a high velocity and uni-  
form distribution of air across the heating elements.  
Every element is fully protected against excessive tem-  
perature by thermal limit switches.  
Anti-Short Cycle Protection - To aid compressor  
life, an anti-short cycle delay is incorporated into the  
standard controls. Compressor reliability is further  
ensured by programmable minimum run times. For  
testing, the anti short cycle delay can be temporarily  
overridden with the push of a button.  
The power supply wiring can be routed into the control  
box through a threaded pipe connection (field supplied)  
in the base pan of the unit or through a knockout in the  
wiring panel on the side of the unit.  
Fan Delays - Fan on and fan off delays are fully pro-  
grammable and are independent of one another. All  
units are programmed with default values based  
upon their configuration of cooling and heat.  
BAS Controls - York’s Sunline™ series units offer factory  
®
mounted BAS controls such as S implicity INTELLI-Com-  
Safety Monitoring - The control board monitors the  
fort™, Novar, Honeywell, Johnson, and CPC.  
high and low-pressure switches, the freezestats, the  
4
Johnson Controls Unitary Products  
 
343615-YTG-B-0308  
Gas/Electric  
Electric heat  
accessory location  
20 Gauge aluminized  
steel tubular heat exchanger  
Power ventor motor with  
post purge cycle  
Direct drive  
blower  
High efficiency  
compressor  
HACR  
breaker  
Economizer  
hood  
Copper tube/  
aluminum fin  
condensing coil  
Knockout  
for side  
power entry  
Slide-in  
economizer  
Smoke  
detector  
Full perimeter baserails  
with forklift slots and  
lifting holes  
Knockout for side  
gas supply entry  
3/4  
"
PVC female  
condensate drain  
GFCI  
convenience outlet  
Simplicity® Lite™  
control board  
Knockout  
for side  
control entry  
Electric/Electric and Heat Pump  
Direct drive  
blower  
HACR  
breaker  
Knockout  
for side  
power entry  
High efficiency  
compressor  
Economizer  
hood  
Copper tube/  
aluminum fin  
condensing coil  
Slide-in  
economizer  
Smoke  
detector  
Full perimeter baserails  
with forklift slots and  
lifting holes  
3/4  
"
PVC female  
Electric Heat  
accessory location  
condensate drain  
GFCI  
convenience outlet  
Simplicity® Lite™  
control board  
Knockout  
for side  
control entry  
FIGURE 1 - UNIT CUTAWAY  
Johnson Controls Unitary Products  
5
 
343615-YTG-B-0308  
scheduling is built-in. Two different modes of demand  
ventilation are achieved through the INTELLI-Comfort™  
using CO2 sensors. It uses an inside CO2 sensor to per-  
form Demand Ventilation. It can also use an Outside  
CO2 sensor to perform Differential Demand Ventilation.  
It uses a Patented Comfort Ventilation algorithm to pro-  
vide comfortable ventilation air temperature. The pat-  
ented economizer-loading algorithm will protect the  
equipment when harsh operating conditions exist.  
Humidity in the occupied space or return duct can be  
monitored and controlled via humidity sensors and the  
on-board connection for hot gas re-heat system. It uses  
the INTELLI-Start™ algorithm to maximize energy sav-  
ings by recovering the building from the Unoccupied Set-  
points to the Occupied Setpoints just in time for the  
FACTORY-INSTALLED OPTIONS  
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-  
MIZERS - Includes a slide-in / plug-in damper assembly  
with fully modulating spring-return motor actuator capa-  
ble of introducing up to 100% outdoor air with nominal  
1% leakage type dampers.  
The enthalpy system contains one sensor that monitors  
the outdoor air and determines when the air is cool  
enough and dry enough to provide free cooling.  
The rainhood is painted to match the basic unit and must  
be field-assembled before installing.  
MOTORIZED OUTDOOR AIR INTAKE DAMPER -  
Includes a slide-in / plug-in damper assembly with a 2-  
position, spring return motor actuator which opens to a  
pre-set position whenever the supply air blower is oper-  
ating and will drive fully closed when the blower unit  
shuts down.  
®
Occupied Time Period to begin. The S implicity  
INTELLI-Comfort™ balances space temperature, venti-  
lation air temperature, CO2 and humidity for ultimate  
comfort.  
®
S implicity INTELLI-Comfort™ with MOD LINK CON-  
The rain hood is painted to match the basic unit and  
must be field assembled before installing.  
®
TROL - The York® S implicity INTELLI-Comfort™ with  
Mod Link control is factory installed. It includes all the  
features of the INTELLI-Comfort™ control with an addi-  
tional control to translate communications from MOD-  
BUS to the BACnet MSTP protocol.  
PHENOLIC COATED EVAPORATOR AND CON-  
DENSER COILS - Special coating process that utilizes  
TM  
Technicoat 10-1 processes. Coating is applied by total  
immersion of the complete coil for maximum protection.  
Novar® BAS CONTROL - The Novar® ETC-3 building  
automation system controller is factory installed.  
Includes supply air sensor, return air sensor, dirty filter  
indicator switch, and air proving switch.  
ELECTRIC HEATERS - Wired for single point power  
supply. These nickel chromium heater elements are pro-  
vided with limit and automatic reset capability to prevent  
operation at excessive temperatures.  
JOHNSON CONTROLS BAS CONTROL - The Johnson  
Control YK-UNT-1126 building automation system con-  
troller is factory installed. Includes supply air sensor,  
return air sensor, dirty filter indicator switch, and air prov-  
ing switch.  
FILTER OPTIONS - Standard units are shipped with 1”  
throw-away filters installed. 2” pleated filters are offered  
as a factory installed option.  
CONVENIENCE OUTLET - This 110 volt outlet can be  
“powered” by the unit with a stepdown transformer or the  
unit may be ordered with a “non-powered” convenience  
outlet that can be wired in the field.  
CPC BAS CONTROL - The Computer Process Controls  
Model 810-3060 ARTC Advanced Rooftop building auto-  
mation system controller is factory installed. Includes  
supply air sensor, return air sensor, dirty filter indicator  
switch and air proving switch.  
DISCONNECT SWITCH - For gas heat units and cooling  
units with electric heat, a HACR breaker sized to the unit  
is provided. For cooling only units, a switch sized to the  
largest electric heat available for the particular unit is  
provided. Factory installed option only.  
HONEYWELL BAS CONTROL - The Honeywell  
W7750C building automation system controller is factory  
installed. Includes air supply sensor, return air sensor,  
dirty filter indicator switch, and air proving switch.  
BAS - Building Automation System Controls  
®
SMOKE DETECTORS - (supply air & return air) The  
smoke detectors stop operation of the unit by interrupting  
power to the control board if smoke is detected within the  
air compartment.  
S implicity INTELLI-Comfort™ CONTROL - The York®  
®
S implicity INTELLI-Comfort™ control is factory  
installed. It includes a supply air sensor, a return air sen-  
sor, and an outside air sensor. There are provisions for a  
field installed dirty filter indicator switch, an air-proving  
switch, an Outside Air Humidity sensor, a Return Air  
Humidity sensor, an Inside IAQ sensor, and an Outside  
Air IAQ sensor. Construction mode operation, 365-day  
real time clock with 7 day programming plus holiday  
COIL GUARD - Customers can purchase a coil guard kit  
to protect the condenser coil from damage. This is not a  
hail guard kit.  
6
Johnson Controls Unitary Products  
 
343615-YTG-B-0308  
MOTORIZED OUTDOOR AIR INTAKE DAMPER -  
Includes a slide-in / plug-in damper assembly with a 2-  
position, spring return motor actuator which opens to  
some pre-set position whenever the supply air blower is  
operating and will drive fully closed when the blower unit  
shuts down.  
Factory installed Smoke Detectors in the Return  
Air, may be subjected to freezing temperatures  
during "off" times due to Out Side Air infiltration.  
These Smoke Detectors have an operational limit  
of 32°F to 131°F. Smoke Detectors installed in  
areas that could be out side those limitations will  
have to be moved to prevent having false alarms.  
The rain hood is painted to match the basic unit and  
must be field assembled before installing.  
ELECTRIC HEATERS wired for single point power sup-  
ply. These nickel chromium heater elements are pro-  
vided with limit and automatic reset capability to prevent  
operation at excessive temperatures.  
STAINLESS STEEL HEAT EXCHANGER - For applica-  
tions in corrosive environments, this option provides a  
full stainless steel heat exchanger assembly.  
ROOF CURBS - Eight and fourteen-inch high roof curbs  
provide a water-tight seal between the unit and the finished  
roof. These full perimeter curbs meet the requirements of  
the National Roofing Contractors Association (NRCA) and  
are shipped knocked-down for field assembly.  
STAINLESS STEEL DRAIN PAN - An optional rust-  
proof stainless steel drain pan is available to provide  
years of trouble-free operation in corrosive environ-  
ments.  
Roof curbs are designed to fit inside the base rails of the  
unit and include both a wood nailing strip and duct  
hanger supports.  
BOTTOM DRAIN CONNECTION - An optional bottom  
drain connection is available for inside the curb connec-  
tions for applications in cold environments to reduce  
freezing drain lines.  
HIGH ALTITUDE NATURAL GAS - Burner orifices and  
pilot orifices are provided for proper furnace operation at  
altitudes up to 6,000 feet.  
PHASE MONITORS - Designed to prevent unit damage.  
The phase monitor will shut the unit down in an out-of-  
phase condition.  
PROPANE - Burner orifices, pilot orifices and gas valve  
parts are provided to convert a natural gas furnace to  
propane.  
DIRTY FILTER SWITCH - This kit includes a differential  
pressure switch that energizes the fault light on the unit  
thermostat, indicating that there is an abnormally high  
pressure drop across the filters. Factory installed option  
or field installed accessory.  
HIGH ALTITUDE PROPANE - Burner orifices and pilot  
orifices are provided for proper furnace operation at alti-  
tudes up to 6,000 feet. This accessory supplements the  
basic propane conversion kit.  
HINGED FILTER DOOR/“TOOLLESS” BLOWER AND  
ACCESS PANELS (not hinged) - This option allows for  
easy access and maintenance.  
LOW NOX KIT - Required to reduce the emission of  
nitrogen oxides below 40 nano grams per joule.  
NOTE:Knobs are shipped inside the unit to prevent ship-  
ping damage. These must be field installed for  
tool-less operation.  
POWER EXHAUST - Our single input economizer  
options are available with power exhaust. Whenever the  
outdoor air intake dampers are opened for free cooling,  
the exhaust fan will be energized to prevent the condi-  
tioned space from being over-pressurized during econo-  
mizer operation.  
FIELD-INSTALLED ACCESSORIES  
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-  
MIZERS - Includes a slide-in / plug-in damper assembly  
with fully modulating spring-return motor actuator capa-  
ble of introducing up to 100% outdoor air with nominal  
1% leakage type dampers.  
The power exhaust option can only be used on bot-  
tom duct configurations.  
BAROMETRIC RELIEF DAMPER - This damper acces-  
sory can be used to relieve internal building air pressure  
on units with an economizer without power exhaust. This  
accessory includes a rain hood, a bird screen and a fully  
assembled damper. With bottom duct connections, the  
damper should be mounted over the opening in the  
return air panel. With horizontal ductwork, the accessory  
should be mounted on the return air duct.  
The enthalpy system contains one sensor that monitors  
the outdoor air and determines when the air is cool  
enough and dry enough to provide free cooling.  
The rainhood is painted to match the basic unit and must  
be field-assembled before installing.  
Johnson Controls Unitary Products  
7
 
343615-YTG-B-0308  
ENTHALPY ACCESSORY CONTROL KIT - This kit  
contains the required components to convert a single  
enthalpy economizer to dual enthalpy.  
CO SENSOR - Senses CO levels and automatically  
overrides the economizer when levels rise above the  
present limits.  
2
2
BURGLAR BARS - Mount in the supply and return  
openings to prevent entry into the duct work.  
COIL GUARD - Customers can purchase a coil guard kit  
to protect the condenser coil from damage. This is not a  
hail guard kit.  
FLUE EXHAUST EXTENSION KIT - In locations with  
wind or weather conditions which may interfere with  
proper exhausting of furnace combustion products, this  
kit can be installed to prevent the flue exhaust from  
entering nearby fresh air intakes.  
HAIL GUARD - Hail Guard kit is available to prevent unit  
from hail damage. This is a sloped hood that fits above  
the coil.  
GAS PIPING KIT - This kit supplies all necessary fittings  
and shut off valve.  
1
1
TABLE 1: CAPACITY RATINGS - (ARI 210/240)  
TABLE 2: GAS HEAT RATINGS  
SOUND  
RATING  
(Db)4  
84  
MBH  
INPUT  
MBH  
OUTPUT  
AFUE  
(%)  
TEMP  
RISE ºF  
MODEL  
EER2  
SEER3  
MODEL  
MBH  
CFM  
DY036N04  
DY036N08  
DY048N06  
DY048N10  
DY060N08  
DY060N10  
50  
100  
40  
80  
80.9  
80.5  
15 - 45  
45 - 75  
DY036  
DY048  
DY060  
35.6  
46.0  
59.0  
12  
12  
14  
14  
14  
1200  
1600  
1750  
83  
75  
125  
60  
100  
80.9  
80.3  
25 - 70  
45 - 75  
11.6  
81  
100  
125  
80  
100  
80.5  
80.3  
25 - 55  
30 - 75  
1. 80/67°F Indoor and 95°F outdoor.  
2. EER = Energy Efficiency Ratio at full load - the cooling  
capacity in Btu’s per hour (Btuh) divided by the power  
input in watts, expressed in Btuh per watt (Btuh/watt).  
3. SEER = Seasonal Energy Efficiency Ratio.  
1. All units are single-stage heating.  
4. Rated in accordance with ARI 270 Standard.  
TABLE 3: 2 STAGE GAS HEAT RATINGS  
MBH INPUT  
MBH OUTPUT  
STEADY STATE EFFICIENCY  
RISE  
MINIMUM HEATING  
AIRFLOW (CFM)  
MODEL1  
1
ST STAGE 2ND STAGE 1ST STAGE 2ND STAGE 1ST STAGE  
2ND STAGE  
MIN. MAX.  
45  
69  
45  
75  
45  
75  
75  
115  
75  
35.8  
55.2  
35.7  
60.4  
35.8  
60.4  
60.8  
92  
79.4  
80.0  
79.4  
80.5  
79.4  
80.5  
81.1  
35  
55  
25  
45  
20  
35  
70  
90  
70  
75  
55  
75  
790  
950  
DY036D06  
DY036D10  
DY048D06  
DY048D10  
DY060D06  
DY060D10  
80.2  
60.8  
100.6  
60.8  
100.6  
81.1  
790  
125  
75  
80.5  
1230  
1010  
1230  
81.1  
125  
80.5  
1. Models are 3Ø only.  
8
Johnson Controls Unitary Products  
     
343615-YTG-B-0308  
TABLE 4: DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)  
UNIT DESCRIPTION / MODEL  
CONFIGURATION  
DY036 / 3 Ton  
Horizontal Ducted Inlet  
Indoor Blower Speed (RPM)  
Blower Static Pressure (IWG)  
Airflow (CFM)  
630  
0.2  
1116  
0.41  
631  
879  
0.2  
885  
0.7  
1020  
0.53  
0.3  
928  
0.37  
1979  
0.76  
Blower Motor BHP  
Cooling  
Cooling  
Cooling  
Cooling  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Octave Center Freq.  
63  
80  
76  
56  
50  
40  
41  
41  
45  
82  
77  
59  
50  
43  
42  
41  
45  
80  
76  
56  
49  
39  
40  
41  
45  
82  
77  
60  
50  
42  
42  
41  
45  
78  
82  
60  
54  
49  
49  
49  
47  
83  
83  
61  
54  
50  
49  
49  
47  
81  
81  
58  
51  
44  
43  
41  
45  
85  
82  
60  
52  
45  
44  
41  
45  
125  
250  
500  
1000  
2000  
4000  
8000  
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.  
2. Cooling Operation – ID blower, compressor and outdoor fan operating.  
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).  
4. Test duct termination is flush with reverberation room wall.  
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.  
TABLE 5: DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)  
UNIT DESCRIPTION / MODEL  
CONFIGURATION  
DY036 / 3 Ton  
Horizontal Ducted Discharge  
Indoor Blower Speed (RPM)  
Blower Static Pressure (IWG)  
Airflow (CFM)  
630  
0.2  
1116  
0.41  
631  
0.3  
879  
0.2  
885  
0.7  
928  
0.37  
1979  
0.76  
1020  
0.53  
Blower Motor BHP  
Cooling  
Cooling  
Cooling  
Cooling  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Octave Center Freq.  
63  
80  
74  
58  
48  
41  
39  
41  
45  
84  
77  
61  
51  
45  
41  
41  
45  
80  
74  
58  
47  
39  
37  
38  
44  
83  
76  
61  
50  
43  
39  
38  
44  
85  
80  
68  
58  
55  
53  
55  
52  
87  
82  
68  
58  
55  
53  
55  
53  
84  
80  
63  
53  
49  
46  
49  
47  
87  
83  
65  
54  
50  
47  
49  
47  
125  
250  
500  
1000  
2000  
4000  
8000  
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.  
2. Cooling Operation – ID blower, compressor and outdoor fan operating.  
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).  
4. Test duct termination is flush with reverberation room wall.  
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.  
Johnson Controls Unitary Products  
9
   
343615-YTG-B-0308  
TABLE 6: DY036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)  
UNIT DESCRIPTION / MODEL  
CONFIGURATION  
DY036 / 3 Ton  
Vertical Ducted Inlet  
Indoor Blower Speed (RPM)  
Blower Static Pressure (IWG)  
Airflow (CFM)  
632  
0.2  
1069  
0.36  
632  
881  
0.2  
883  
0.7  
917  
0.49  
0.3  
870  
0.33  
1903  
0.71  
Blower Motor BHP  
Cooling  
Cooling  
Cooling  
Cooling  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
Octave Center Freq.  
(dB)  
63  
78  
70  
55  
47  
40  
37  
36  
44  
82  
75  
60  
50  
43  
40  
37  
44  
78  
70  
55  
47  
39  
37  
36  
44  
82  
74  
60  
50  
43  
39  
37  
44  
80  
71  
59  
52  
50  
45  
45  
45  
85  
80  
61  
53  
51  
46  
46  
47  
80  
71  
58  
49  
45  
41  
40  
44  
84  
79  
62  
52  
46  
43  
40  
44  
125  
250  
500  
1000  
2000  
4000  
8000  
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.  
2. Cooling Operation – ID blower, compressor and outdoor fan operating.  
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).  
4. Test duct termination is flush with reverberation room wall.  
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.  
TABLE 7: DY036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)  
UNIT DESCRIPTION / MODEL  
CONFIGURATION  
DY036 / 3 Ton  
Vertical Ducted Discharge  
Indoor Blower Speed (RPM)  
Blower Static Pressure (IWG)  
Airflow (CFM)  
632  
0.2  
1069  
0.36  
632  
0.3  
881  
0.2  
883  
0.7  
917  
0.49  
870  
0.33  
1903  
0.71  
Blower Motor BHP  
Cooling  
Cooling  
Cooling  
Cooling  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Octave Center Freq.  
63  
80  
78  
55  
48  
41  
37  
38  
44  
83  
79  
60  
51  
44  
40  
39  
45  
80  
77  
54  
46  
39  
35  
36  
44  
83  
78  
59  
50  
43  
38  
37  
44  
83  
80  
63  
58  
54  
50  
52  
49  
86  
83  
63  
59  
55  
50  
53  
50  
82  
79  
58  
52  
48  
42  
44  
45  
85  
82  
62  
53  
49  
44  
44  
45  
125  
250  
500  
1000  
2000  
4000  
8000  
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.  
2. Cooling Operation – ID blower, compressor and outdoor fan operating.  
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).  
4. Test duct termination is flush with reverberation room wall.  
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.  
10  
Johnson Controls Unitary Products  
   
343615-YTG-B-0308  
TABLE 8: DY048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)  
UNIT DESCRIPTION / MODEL  
CONFIGURATION  
DY048 / 4 Ton  
Horizontal Ducted Inlet  
Indoor Blower Speed (RPM)  
Blower Static Pressure (IWG)  
Airflow (CFM)  
766  
0.2  
1484  
0.67  
769  
1077  
0.4  
1087  
1.0  
1406  
0.90  
0.5  
993  
0.54  
2270  
1.24  
Blower Motor BHP  
Cooling  
Cooling  
Cooling  
Cooling  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Octave Center Freq.  
63  
74  
70  
53  
49  
42  
40  
38  
42  
97  
86  
58  
55  
42  
44  
44  
43  
74  
69  
52  
47  
38  
38  
36  
42  
95  
86  
57  
54  
39  
43  
41  
44  
77  
73  
60  
54  
50  
48  
48  
45  
90  
78  
61  
56  
55  
51  
52  
48  
77  
72  
58  
51  
45  
45  
43  
44  
90  
77  
61  
53  
45  
46  
45  
45  
125  
250  
500  
1000  
2000  
4000  
8000  
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.  
2. Cooling Operation – ID blower, compressor and outdoor fan operating.  
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).  
4. Test duct termination is flush with reverberation room wall.  
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.  
TABLE 9: DY048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)  
UNIT DESCRIPTION / MODEL  
CONFIGURATION  
DY048 / 4 Ton  
Horizontal Ducted Discharge  
Indoor Blower Speed (RPM)  
Blower Static Pressure (IWG)  
Airflow (CFM)  
766  
0.2  
1484  
0.67  
769  
0.5  
1077  
0.4  
1087  
1.0  
993  
0.54  
2270  
1.24  
1406  
0.90  
Blower Motor BHP  
Cooling  
Cooling  
Cooling  
Cooling  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Octave Center Freq.  
63  
77  
72  
60  
53  
47  
45  
46  
47  
97  
86  
62  
56  
47  
46  
47  
47  
75  
69  
57  
49  
42  
40  
40  
45  
95  
85  
59  
54  
43  
43  
42  
45  
84  
81  
71  
60  
58  
54  
57  
54  
91  
83  
71  
61  
59  
55  
58  
54  
82  
78  
66  
55  
52  
50  
52  
48  
91  
80  
67  
56  
52  
50  
52  
49  
125  
250  
500  
1000  
2000  
4000  
8000  
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.  
2. Cooling Operation – ID blower, compressor and outdoor fan operating.  
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).  
4. Test duct termination is flush with reverberation room wall.  
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.  
Johnson Controls Unitary Products  
11  
   
343615-YTG-B-0308  
TABLE 10: DY048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)  
UNIT DESCRIPTION / MODEL  
CONFIGURATION  
DY048 / 4 Ton  
Vertical Ducted Inlet  
Indoor Blower Speed (RPM)  
Blower Static Pressure (IWG)  
Airflow (CFM)  
791  
0.2  
1408  
0.54  
794  
1084  
0.2  
1095  
1.0  
1275  
0.73  
0.5  
1000  
0.42  
2336  
1.12  
Blower Motor BHP  
Cooling  
Cooling  
Cooling  
Cooling  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
Octave Center Freq.  
(dB)  
63  
76  
68  
54  
48  
43  
40  
38  
43  
95  
84  
57  
53  
44  
43  
43  
43  
77  
67  
52  
46  
40  
38  
36  
43  
93  
82  
56  
53  
41  
42  
40  
43  
80  
76  
63  
54  
52  
49  
49  
45  
91  
84  
61  
57  
52  
51  
54  
47  
79  
73  
57  
50  
47  
44  
43  
44  
91  
80  
59  
53  
47  
46  
45  
44  
125  
250  
500  
1000  
2000  
4000  
8000  
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.  
2. Cooling Operation – ID blower, compressor and outdoor fan operating.  
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).  
4. Test duct termination is flush with reverberation room wall.  
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.  
TABLE 11: DY048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)  
UNIT DESCRIPTION / MODEL  
CONFIGURATION  
DY048 / 4 Ton  
Vertical Ducted Discharge  
Indoor Blower Speed (RPM)  
Blower Static Pressure (IWG)  
Airflow (CFM)  
791  
0.2  
1408  
0.54  
794  
0.5  
1084  
0.2  
1095  
1.0  
1275  
0.73  
1000  
0.42  
2336  
1.12  
Blower Motor BHP  
Cooling  
Cooling  
Cooling  
Cooling  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Octave Center Freq.  
63  
78  
73  
56  
51  
46  
42  
43  
44  
95  
84  
58  
54  
46  
44  
45  
44  
77  
72  
53  
48  
43  
38  
39  
43  
93  
82  
56  
53  
44  
42  
41  
43  
85  
84  
68  
61  
57  
53  
55  
52  
92  
87  
68  
62  
57  
54  
57  
52  
82  
78  
60  
54  
50  
46  
49  
46  
91  
82  
61  
55  
50  
48  
50  
47  
125  
250  
500  
1000  
2000  
4000  
8000  
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.  
2. Cooling Operation – ID blower, compressor and outdoor fan operating.  
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).  
4. Test duct termination is flush with reverberation room wall.  
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.  
12  
Johnson Controls Unitary Products  
   
343615-YTG-B-0308  
TABLE 12: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)  
UNIT DESCRIPTION / MODEL  
CONFIGURATION  
DY060 / 5 Ton  
Horizontal Ducted Inlet  
Indoor Blower Speed (RPM)  
Blower Static Pressure (IWG)  
Airflow (CFM)  
840  
0.2  
1695  
0.67  
845  
1166  
0.3  
1188  
1.3  
1323  
0.80  
0.6  
1100  
0.50  
2618  
1.51  
Blower Motor BHP  
Cooling  
Cooling  
Cooling  
Cooling  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Octave Center Freq.  
63  
77  
71  
57  
53  
50  
49  
49  
49  
84  
71  
58  
53  
50  
49  
49  
49  
77  
72  
55  
51  
45  
43  
42  
48  
84  
73  
56  
51  
46  
44  
43  
48  
81  
74  
66  
60  
60  
58  
59  
54  
85  
75  
66  
60  
60  
58  
59  
54  
79  
71  
60  
55  
53  
50  
47  
47  
84  
72  
61  
55  
53  
50  
47  
47  
125  
250  
500  
1000  
2000  
4000  
8000  
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.  
2. Cooling Operation – ID blower, compressor and outdoor fan operating.  
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).  
4. Test duct termination is flush with reverberation room wall.  
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.  
TABLE 13: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)  
UNIT DESCRIPTION / MODEL  
CONFIGURATION  
DY060 / 5 Ton  
Horizontal Ducted Discharge  
Indoor Blower Speed (RPM)  
Blower Static Pressure (IWG)  
Airflow (CFM)  
840  
0.2  
1695  
0.67  
845  
0.6  
1166  
0.3  
1188  
1.3  
1100  
0.50  
2618  
1.51  
1323  
0.80  
Blower Motor BHP  
Cooling  
Cooling  
Cooling  
Cooling  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Octave Center Freq.  
63  
82  
75  
69  
64  
59  
55  
58  
55  
87  
76  
69  
64  
60  
55  
58  
55  
79  
72  
66  
60  
55  
50  
52  
49  
88  
74  
66  
60  
56  
50  
52  
49  
88  
82  
79  
72  
68  
65  
68  
66  
89  
83  
79  
72  
68  
65  
68  
67  
82  
78  
73  
66  
61  
57  
60  
56  
87  
78  
73  
66  
61  
57  
60  
56  
125  
250  
500  
1000  
2000  
4000  
8000  
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.  
2. Cooling Operation – ID blower, compressor and outdoor fan operating.  
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).  
4. Test duct termination is flush with reverberation room wall.  
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.  
Johnson Controls Unitary Products  
13  
   
343615-YTG-B-0308  
TABLE 14: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)  
UNIT DESCRIPTION / MODEL  
CONFIGURATION  
DY060 / 5 Ton  
Vertical Ducted Inlet  
Indoor Blower Speed (RPM)  
Blower Static Pressure (IWG)  
Airflow (CFM)  
834  
0.2  
1525  
0.61  
840  
1171  
0.2  
1194  
1.3  
1256  
0.83  
0.6  
1019  
0.44  
2624  
1.43  
Blower Motor BHP  
Cooling  
Cooling  
Cooling  
Cooling  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
Octave Center Freq.  
(dB)  
63  
77  
69  
56  
50  
48  
43  
47  
46  
86  
70  
63  
52  
51  
47  
49  
47  
79  
70  
56  
48  
44  
39  
40  
44  
88  
72  
58  
49  
45  
41  
41  
45  
81  
71  
64  
57  
57  
54  
55  
51  
86  
73  
72  
59  
58  
57  
61  
57  
83  
72  
63  
53  
49  
47  
47  
47  
87  
72  
69  
56  
52  
50  
52  
49  
125  
250  
500  
1000  
2000  
4000  
8000  
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.  
2. Cooling Operation – ID blower, compressor and outdoor fan operating.  
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).  
4. Test duct termination is flush with reverberation room wall.  
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.  
TABLE 15: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)  
UNIT DESCRIPTION / MODEL  
CONFIGURATION  
DY060 / 5 Ton  
Vertical Ducted Discharge  
Indoor Blower Speed (RPM)  
Blower Static Pressure (IWG)  
Airflow (CFM)  
834  
0.2  
1525  
0.61  
840  
0.6  
1171  
0.2  
1194  
1.3  
1256  
0.83  
1019  
0.44  
2624  
1.43  
Blower Motor BHP  
Cooling  
Cooling  
Cooling  
Cooling  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
ID Blower  
Only (dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Operation2  
(dB)  
Octave Center Freq.  
63  
83  
78  
66  
59  
57  
51  
54  
52  
88  
78  
67  
60  
58  
52  
54  
52  
82  
75  
62  
54  
51  
45  
47  
46  
88  
76  
62  
54  
51  
45  
47  
47  
91  
85  
77  
70  
68  
62  
65  
65  
91  
85  
78  
70  
68  
63  
66  
66  
85  
79  
70  
61  
57  
52  
55  
52  
88  
79  
72  
61  
58  
53  
56  
53  
125  
250  
500  
1000  
2000  
4000  
8000  
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.  
2. Cooling Operation – ID blower, compressor and outdoor fan operating.  
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).  
4. Test duct termination is flush with reverberation room wall.  
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.  
14  
Johnson Controls Unitary Products  
   
343615-YTG-B-0308  
TABLE 16: DY036 COOLING CAPACITIES (3 TON)  
Temperature of Air on Condenser Coil  
Air on Evap-  
orator Coil  
75°F  
85°F  
1
1
2
2
Sensible Capacity (MBH)  
Return Dry Bulb (°F)  
Sensible Capacity (MBH)  
Return Dry Bulb (°F)  
Total Total  
Cap.  
Total Total  
Cap.  
WB  
CFM  
1
1
Input  
Input  
(°F)  
(MBH) (kW)  
(MBH) (kW)  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
44  
42  
40  
39  
44  
42  
40  
39  
44  
43  
40  
39  
45  
43  
41  
40  
46  
44  
42  
41  
2.3  
2.3  
2.3  
2.3  
2.2  
2.3  
2.3  
2.3  
2.2  
2.3  
2.3  
2.3  
2.2  
2.3  
2.3  
2.3  
2.3  
2.3  
2.3  
2.3  
24  
30  
40  
39  
26  
33  
40  
39  
28  
35  
40  
39  
30  
37  
41  
40  
32  
40  
42  
41  
21  
28  
35  
37  
23  
30  
38  
38  
25  
32  
40  
39  
26  
33  
41  
40  
27  
35  
42  
41  
19  
25  
33  
35  
20  
27  
35  
37  
21  
28  
37  
39  
22  
29  
39  
40  
23  
31  
42  
41  
95°F  
16  
22  
27  
27  
18  
24  
30  
30  
19  
26  
32  
32  
20  
27  
32  
33  
21  
29  
33  
33  
115°F  
13  
18  
21  
23  
15  
20  
23  
25  
16  
22  
25  
27  
17  
23  
25  
26  
18  
25  
25  
25  
16  
23  
30  
32  
17  
24  
32  
34  
18  
25  
33  
36  
18  
25  
35  
36  
18  
26  
37  
36  
14  
20  
28  
30  
14  
21  
29  
31  
14  
21  
30  
32  
14  
21  
31  
32  
14  
22  
33  
32  
-
-
41  
38  
35  
35  
42  
39  
35  
35  
43  
40  
36  
36  
43  
40  
37  
36  
44  
41  
37  
37  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
23  
29  
35  
35  
25  
31  
35  
35  
27  
34  
36  
36  
29  
36  
37  
36  
31  
39  
37  
37  
20  
26  
32  
34  
22  
28  
34  
35  
24  
31  
36  
36  
25  
32  
37  
36  
27  
34  
37  
37  
18  
24  
30  
31  
19  
25  
32  
33  
20  
27  
34  
36  
21  
28  
36  
36  
22  
30  
37  
37  
105°F  
15  
20  
24  
25  
16  
22  
26  
27  
18  
24  
29  
30  
19  
25  
29  
30  
20  
27  
29  
29  
125°F  
12  
17  
18  
20  
13  
18  
20  
22  
14  
20  
22  
22  
15  
21  
21  
22  
16  
23  
21  
22  
15  
21  
27  
28  
16  
22  
29  
30  
17  
24  
31  
32  
17  
24  
32  
32  
18  
25  
33  
32  
12  
18  
25  
26  
13  
19  
26  
27  
13  
20  
27  
29  
13  
20  
28  
28  
13  
21  
28  
28  
-
-
18  
25  
27  
-
18  
26  
28  
-
18  
26  
29  
-
18  
27  
28  
-
15  
23  
25  
-
15  
23  
25  
-
14  
23  
25  
-
14  
23  
24  
-
16  
22  
23  
-
16  
23  
24  
-
17  
24  
25  
-
16  
24  
24  
-
13  
20  
21  
-
13  
20  
21  
-
13  
20  
22  
-
12  
20  
20  
-
900  
67  
1050  
62  
57  
72  
67  
1200  
62  
57  
72  
67  
1350  
62  
57  
72  
67  
62  
57  
17  
28  
27  
13  
24  
23  
16  
24  
23  
12  
19  
19  
1500  
72  
67  
62  
57  
72  
38  
35  
30  
30  
39  
36  
31  
31  
41  
37  
32  
32  
41  
37  
32  
33  
42  
38  
33  
33  
2.7  
2.7  
2.7  
2.7  
2.7  
2.7  
2.7  
2.7  
2.7  
2.7  
2.7  
2.7  
2.7  
2.7  
2.7  
2.7  
2.7  
2.7  
2.7  
2.7  
21  
27  
30  
30  
24  
30  
31  
31  
26  
33  
32  
32  
28  
35  
32  
33  
30  
38  
33  
33  
19  
24  
29  
30  
21  
27  
31  
31  
23  
30  
32  
32  
24  
31  
32  
33  
26  
33  
33  
33  
14  
19  
24  
25  
15  
21  
26  
27  
16  
23  
29  
29  
16  
23  
28  
29  
17  
24  
28  
29  
11  
17  
22  
22  
12  
18  
23  
24  
12  
19  
25  
25  
12  
19  
24  
25  
12  
20  
24  
24  
-
-
35  
31  
27  
27  
36  
32  
28  
28  
37  
33  
29  
29  
37  
33  
29  
29  
37  
33  
29  
29  
3.0  
2.9  
3.0  
3.0  
3.0  
2.9  
2.9  
2.9  
2.9  
2.8  
2.9  
2.9  
3.0  
2.9  
2.9  
2.9  
3.1  
2.9  
3.0  
3.0  
20  
25  
27  
27  
22  
28  
28  
28  
25  
31  
29  
29  
27  
32  
29  
29  
28  
33  
29  
29  
17  
23  
26  
27  
19  
25  
28  
28  
21  
28  
29  
29  
23  
29  
29  
29  
24  
31  
29  
29  
12  
18  
21  
22  
13  
19  
23  
24  
14  
21  
25  
26  
15  
21  
25  
26  
15  
22  
24  
25  
10  
15  
19  
20  
10  
16  
20  
21  
11  
17  
22  
23  
11  
17  
21  
22  
11  
18  
20  
20  
-
-
14  
19  
19  
-
15  
20  
21  
-
16  
22  
22  
-
15  
20  
21  
-
12  
17  
17  
-
12  
17  
18  
-
12  
18  
18  
-
11  
16  
17  
-
12  
16  
17  
-
13  
17  
18  
-
14  
18  
19  
-
13  
17  
18  
-
10  
14  
15  
-
10  
14  
15  
-
10  
15  
16  
-
900  
67  
1050  
62  
57  
72  
67  
1200  
62  
57  
72  
67  
9
1350  
62  
57  
72  
67  
62  
57  
13  
14  
-
9
11  
11  
15  
19  
20  
11  
15  
15  
13  
15  
16  
1500  
72  
67  
62  
57  
72  
32  
27  
24  
25  
32  
28  
25  
25  
33  
29  
25  
26  
33  
29  
25  
26  
33  
28  
25  
25  
3.3  
3.1  
3.2  
3.2  
3.3  
3.0  
3.1  
3.1  
3.2  
3.0  
3.1  
3.1  
3.3  
3.1  
3.2  
3.2  
3.4  
3.2  
3.3  
3.3  
18  
23  
24  
25  
21  
26  
25  
25  
23  
29  
25  
26  
25  
29  
25  
26  
27  
28  
25  
25  
16  
21  
23  
25  
18  
23  
24  
25  
20  
26  
25  
26  
21  
27  
25  
26  
22  
28  
25  
25  
11  
16  
18  
20  
12  
17  
20  
22  
13  
19  
22  
24  
13  
19  
21  
22  
13  
20  
20  
21  
8
-
-
8
11  
12  
-
28  
24  
21  
22  
29  
24  
21  
22  
29  
25  
22  
22  
29  
24  
21  
22  
28  
24  
21  
22  
3.7  
3.3  
3.5  
3.5  
3.5  
3.2  
3.4  
3.4  
3.4  
3.1  
3.3  
3.3  
3.6  
3.2  
3.4  
3.4  
3.8  
3.4  
3.6  
3.6  
17  
22  
21  
22  
19  
24  
21  
22  
21  
25  
22  
22  
23  
24  
21  
22  
25  
24  
21  
22  
14  
19  
20  
22  
16  
22  
21  
22  
18  
24  
22  
22  
19  
24  
21  
22  
20  
24  
21  
22  
9
7
-
9
10  
13  
-
-
6
8
10  
-
6
8
10  
-
6
8
11  
-
6
5
7
-
13  
16  
17  
9
14  
17  
19  
9
15  
18  
20  
9
15  
17  
18  
9
11  
13  
15  
-
11  
14  
16  
-
12  
15  
17  
-
11  
13  
14  
-
14  
15  
18  
10  
15  
17  
19  
11  
17  
18  
21  
11  
17  
17  
19  
11  
18  
16  
17  
11  
13  
15  
7
12  
14  
16  
7
13  
15  
18  
7
13  
13  
15  
7
900  
67  
8
9
1050  
62  
57  
72  
11  
13  
-
11  
13  
-
10  
11  
14  
-
10  
9
11  
-
67  
8
1200  
62  
57  
72  
11  
13  
-
8
9
10  
-
7
7
8
67  
1350  
62  
57  
72  
67  
62  
57  
16  
16  
16  
11  
11  
12  
14  
12  
13  
9
7
8
5
3
4
1500  
1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-  
mance table for the kW of the supply air blower motor.  
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.  
Johnson Controls Unitary Products  
15  
 
343615-YTG-B-0308  
TABLE 17: DY048 COOLING CAPACITIES (4 TON)  
Temperature of Air on Condenser Coil  
Air on Evap-  
orator Coil  
75°F  
85°F  
1
1
2
2
Sensible Capacity (MBH)  
Return Dry Bulb (°F)  
Sensible Capacity (MBH)  
Return Dry Bulb (°F)  
Total Total  
Cap.  
Total Total  
Cap.  
WB  
CFM  
1
1
Input  
Input  
(°F)  
(MBH) (kW)  
(MBH) (kW)  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
58  
57  
53  
51  
58  
56  
53  
51  
57  
56  
53  
51  
57  
56  
53  
51  
57  
55  
52  
50  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
2.8  
32  
43  
53  
51  
34  
45  
53  
51  
36  
48  
53  
51  
39  
52  
53  
51  
41  
55  
52  
50  
28  
39  
47  
51  
30  
41  
50  
51  
32  
43  
53  
51  
33  
46  
53  
51  
35  
48  
52  
50  
25  
36  
44  
49  
26  
37  
46  
51  
27  
39  
47  
53  
28  
40  
50  
52  
29  
42  
52  
50  
95°F  
22  
30  
37  
37  
24  
33  
41  
40  
26  
35  
44  
43  
27  
38  
44  
43  
29  
40  
43  
42  
115°F  
18  
25  
28  
28  
20  
28  
31  
31  
22  
30  
34  
34  
24  
33  
34  
33  
25  
35  
33  
33  
22  
32  
40  
45  
22  
33  
41  
47  
22  
34  
43  
48  
23  
35  
45  
46  
23  
36  
46  
44  
18  
29  
37  
42  
18  
29  
37  
43  
18  
29  
38  
43  
17  
30  
39  
41  
17  
30  
40  
38  
-
-
54  
51  
47  
46  
55  
52  
48  
46  
55  
52  
48  
47  
55  
52  
48  
47  
55  
52  
48  
46  
3.1  
3.1  
3.0  
3.0  
3.1  
3.1  
3.0  
3.0  
3.1  
3.1  
3.1  
3.0  
3.1  
3.1  
3.1  
3.1  
3.1  
3.1  
3.1  
3.1  
30  
40  
47  
46  
33  
43  
48  
46  
36  
46  
48  
47  
38  
49  
48  
47  
41  
52  
48  
46  
27  
36  
44  
46  
29  
39  
46  
46  
31  
42  
48  
47  
33  
44  
48  
47  
35  
47  
48  
46  
23  
33  
41  
43  
25  
35  
43  
45  
26  
37  
46  
48  
28  
39  
47  
47  
29  
41  
48  
46  
105°F  
20  
27  
33  
32  
22  
30  
36  
35  
24  
33  
39  
39  
25  
35  
39  
38  
27  
37  
38  
38  
125°F  
16  
22  
23  
23  
18  
25  
26  
26  
20  
28  
29  
29  
22  
30  
29  
29  
23  
31  
28  
28  
20  
29  
37  
39  
21  
31  
39  
41  
22  
32  
41  
43  
22  
34  
41  
42  
23  
35  
42  
40  
17  
26  
34  
36  
17  
27  
35  
37  
17  
28  
36  
39  
17  
28  
36  
37  
17  
29  
36  
34  
-
-
26  
33  
38  
-
25  
33  
39  
-
25  
33  
39  
-
24  
34  
36  
-
22  
30  
35  
-
21  
29  
34  
-
20  
29  
34  
-
19  
29  
30  
-
23  
30  
32  
-
23  
31  
33  
-
23  
32  
34  
-
23  
31  
31  
-
19  
27  
29  
-
19  
27  
29  
-
18  
27  
29  
-
18  
25  
26  
-
1200  
67  
1400  
62  
57  
72  
67  
1600  
62  
57  
72  
67  
1800  
62  
57  
72  
67  
62  
57  
24  
34  
32  
18  
28  
26  
23  
30  
28  
17  
24  
23  
2000  
72  
67  
62  
57  
72  
50  
45  
41  
40  
52  
47  
42  
42  
54  
49  
44  
43  
53  
48  
44  
43  
53  
48  
43  
42  
3.3  
3.4  
3.3  
3.3  
3.4  
3.4  
3.3  
3.3  
3.4  
3.4  
3.3  
3.3  
3.4  
3.4  
3.3  
3.3  
3.4  
3.4  
3.3  
3.3  
29  
37  
41  
40  
32  
41  
42  
42  
35  
45  
44  
43  
38  
46  
44  
43  
41  
48  
43  
42  
25  
33  
41  
40  
28  
37  
42  
42  
30  
40  
44  
43  
33  
43  
44  
43  
35  
46  
43  
42  
18  
27  
34  
33  
20  
29  
37  
36  
21  
31  
39  
39  
22  
32  
38  
38  
23  
34  
37  
37  
15  
23  
31  
30  
16  
25  
33  
32  
16  
26  
35  
34  
17  
27  
33  
32  
17  
28  
31  
31  
-
-
45  
39  
36  
35  
47  
41  
37  
37  
49  
43  
39  
39  
49  
43  
39  
38  
48  
42  
38  
38  
3.7  
3.7  
3.6  
3.6  
3.7  
3.7  
3.6  
3.6  
3.7  
3.7  
3.6  
3.6  
3.7  
3.7  
3.6  
3.7  
3.7  
3.7  
3.7  
3.7  
27  
34  
36  
35  
30  
38  
37  
37  
33  
41  
39  
39  
36  
42  
39  
38  
39  
42  
38  
38  
23  
31  
36  
35  
26  
34  
37  
37  
28  
37  
39  
39  
31  
39  
39  
38  
33  
41  
38  
38  
16  
24  
29  
29  
18  
26  
32  
31  
19  
28  
34  
34  
20  
30  
33  
33  
21  
31  
32  
32  
13  
21  
26  
25  
14  
22  
28  
27  
14  
24  
30  
29  
15  
24  
28  
27  
15  
25  
26  
26  
-
-
20  
27  
26  
-
20  
29  
28  
-
21  
30  
29  
-
22  
28  
27  
-
16  
24  
23  
-
16  
24  
24  
-
17  
25  
25  
-
16  
22  
22  
-
17  
22  
22  
-
18  
24  
23  
-
19  
25  
25  
-
19  
23  
22  
-
14  
19  
19  
-
14  
20  
19  
-
14  
20  
20  
-
14  
17  
17  
-
1200  
67  
1400  
62  
57  
72  
67  
1600  
62  
57  
72  
67  
1800  
62  
57  
72  
67  
62  
57  
22  
25  
25  
16  
19  
19  
19  
20  
20  
14  
14  
14  
2000  
72  
67  
62  
57  
72  
40  
34  
31  
30  
42  
36  
32  
32  
45  
38  
34  
34  
44  
37  
34  
33  
43  
36  
33  
33  
4.0  
3.9  
3.9  
3.9  
4.0  
4.0  
3.9  
3.9  
4.0  
4.0  
3.9  
4.0  
4.0  
4.0  
4.0  
4.0  
4.1  
4.0  
4.0  
4.0  
25  
32  
31  
30  
28  
35  
32  
32  
31  
38  
34  
34  
34  
37  
34  
33  
37  
36  
33  
33  
21  
28  
31  
30  
24  
32  
32  
32  
27  
35  
34  
34  
29  
36  
34  
33  
31  
36  
33  
33  
14  
21  
25  
24  
16  
24  
27  
27  
17  
26  
30  
29  
18  
27  
28  
28  
19  
29  
27  
27  
11  
18  
21  
21  
12  
20  
23  
23  
13  
21  
25  
25  
13  
22  
23  
23  
13  
23  
21  
21  
-
-
35  
28  
26  
25  
38  
30  
28  
27  
40  
32  
29  
29  
39  
31  
29  
29  
39  
31  
28  
28  
4.3  
4.2  
4.2  
4.2  
4.3  
4.3  
4.2  
4.3  
4.3  
4.3  
4.2  
4.3  
4.4  
4.3  
4.3  
4.3  
4.4  
4.3  
4.3  
4.3  
23  
28  
26  
25  
26  
30  
28  
27  
29  
32  
29  
29  
32  
31  
29  
29  
35  
31  
28  
28  
19  
26  
26  
25  
22  
29  
28  
27  
25  
32  
29  
29  
27  
31  
29  
29  
29  
31  
28  
28  
13  
19  
20  
20  
14  
21  
22  
22  
15  
23  
25  
24  
16  
25  
23  
23  
17  
27  
22  
22  
9
-
-
9
10  
9
-
9
10  
10  
-
15  
18  
17  
-
16  
19  
19  
-
16  
20  
20  
-
17  
18  
17  
-
11  
14  
14  
-
11  
15  
15  
-
12  
16  
15  
-
11  
12  
12  
-
15  
16  
16  
10  
17  
18  
18  
11  
19  
20  
20  
11  
20  
18  
18  
11  
21  
16  
16  
12  
13  
13  
-
13  
14  
14  
-
14  
15  
15  
-
14  
13  
13  
-
1200  
67  
1400  
62  
57  
72  
67  
9
1600  
62  
57  
72  
11  
10  
-
9
8
7
-
9
4
67  
1800  
62  
57  
72  
67  
62  
57  
17  
15  
15  
11  
9
9
15  
10  
10  
2000  
4
1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower  
Performance table for the kW of the supply air blower motor.  
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.  
16  
Johnson Controls Unitary Products  
 
343615-YTG-B-0308  
TABLE 18: DY060 COOLING CAPACITIES (5 TON)  
Temperature of Air on Condenser Coil  
Air on Evap-  
orator Coil  
75°F  
85°F  
1
1
2
2
Sensible Capacity (MBH)  
Return Dry Bulb (°F)  
Sensible Capacity (MBH)  
Return Dry Bulb (°F)  
Total Total  
Cap.  
Total Total  
Cap.  
WB  
CFM  
1
1
Input  
Input  
(°F)  
(MBH) (kW)  
(MBH) (kW)  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
73.9  
67.1  
60.7  
57.7  
76.2  
69.2  
62.7  
59.6  
78.6  
71.4  
64.6  
61.4  
79.1  
71.9  
65.0  
61.8  
79.6  
72.3  
65.5  
62.2  
3.7  
3.7  
3.6  
3.7  
3.7  
3.7  
3.7  
3.7  
3.7  
3.7  
3.7  
3.7  
3.7  
3.7  
3.7  
3.7  
3.8  
3.7  
3.7  
3.7  
39.9 35.6 31.3 27.0 22.8  
-
-
69.2  
4.3  
4.2  
4.1  
4.2  
4.3  
4.2  
4.1  
4.2  
4.3  
4.2  
4.2  
4.2  
4.3  
4.2  
4.2  
4.2  
4.3  
4.3  
4.2  
4.2  
38.6 34.3 30.1 25.8 21.5  
-
-
50.5 46.3 42.0 37.7 33.4 29.2 24.9 63.1  
60.7 55.2 50.9 46.7 42.4 38.1 33.8 57.6  
57.7 57.7 54.1 49.8 45.5 41.3 37.0 55.4  
48.9 44.6 40.4 36.1 31.8 27.5 23.2  
57.6 53.6 49.4 45.1 40.8 36.5 32.3  
55.4 55.4 51.6 47.4 43.1 38.8 34.5  
1500  
44.3 39.2 34.1 29.1 24.0  
-
-
71.3  
42.9 37.8 32.7 27.7 22.6  
-
-
67  
55.9 50.9 45.8 40.8 35.7 30.6 25.6 65.0  
62.7 59.9 55.6 50.5 45.4 40.4 35.3 59.4  
59.6 59.6 59.0 53.9 48.9 43.8 38.8 57.0  
54.1 49.0 44.0 38.9 33.9 28.8 23.8  
59.4 57.4 53.8 48.7 43.7 38.6 33.6  
57.0 57.0 56.3 51.2 46.2 41.1 36.1  
1750  
62  
57  
72  
48.7 42.8 37.0 31.2 25.3  
-
-
73.4  
47.1 41.3 35.4 29.6 23.8  
-
-
67  
61.3 55.5 49.6 43.8 38.0 32.1 26.3 66.9  
64.6 64.6 60.2 54.3 48.5 42.7 36.9 61.1  
61.4 61.4 63.9 58.1 52.2 46.4 40.6 58.7  
59.2 53.4 47.6 41.8 35.9 30.1 24.3  
61.1 61.1 58.2 52.4 46.6 40.7 34.9  
58.7 58.7 60.9 55.1 49.2 43.4 37.6  
2000  
62  
57  
72  
52.5 45.8 39.2 32.5 25.9  
-
-
73.8  
50.9 44.2 37.6 30.9 24.3  
-
-
67  
66.8 59.2 52.6 45.9 39.3 32.6 26.0 67.3  
65.0 65.0 62.8 56.2 49.5 42.9 36.3 61.4  
61.8 61.8 63.1 56.4 49.8 43.1 36.5 59.0  
63.5 57.1 50.5 43.8 37.2 30.5 23.9  
61.4 61.4 60.0 53.4 46.7 40.1 33.4  
59.0 59.0 60.1 53.5 46.8 40.2 33.6  
2250  
62  
57  
72  
67  
62  
57  
56.3 48.8 41.4 33.9 26.5  
-
-
74.2  
54.6 47.2 39.7 32.3 24.8  
-
-
72.3 62.9 55.5 48.0 40.6 33.1 25.7 67.7  
65.5 65.5 65.5 58.0 50.6 43.1 35.7 61.8  
62.2 62.2 62.2 54.8 47.3 39.9 32.4 59.3  
95°F  
67.7 60.8 53.3 45.9 38.4 31.0 23.5  
61.8 61.8 61.8 54.3 46.9 39.4 32.0  
59.3 59.3 59.3 51.9 44.4 37.0 29.5  
105°F  
2500  
72  
67  
62  
57  
72  
64.6  
59.2  
54.6  
53.0  
66.4  
60.8  
56.1  
54.5  
68.2  
62.5  
57.6  
55.9  
68.5  
62.8  
57.8  
56.2  
68.8  
63.0  
58.1  
56.4  
4.8  
4.7  
4.6  
4.7  
4.8  
4.7  
4.6  
4.7  
4.8  
4.7  
4.7  
4.7  
4.8  
4.8  
4.7  
4.7  
4.9  
4.8  
4.7  
4.8  
37.4 33.1 28.8 24.5 20.2  
-
-
61.3  
5.4  
5.3  
5.3  
5.3  
5.4  
5.3  
5.3  
5.3  
5.4  
5.3  
5.3  
5.3  
5.4  
5.4  
5.3  
5.3  
5.5  
5.4  
5.3  
5.4  
35.6 31.3 27.0 22.8 18.5  
-
-
47.3 43.0 38.7 34.4 30.2 25.9 21.6 55.7  
54.6 52.1 47.8 43.5 39.3 35.0 30.7 51.5  
53.0 53.0 49.2 44.9 40.7 36.4 32.1 50.4  
45.6 41.3 37.0 32.7 28.4 24.2 19.9  
51.5 50.0 45.8 41.5 37.2 32.9 28.6  
50.4 50.4 46.5 42.2 38.0 33.7 29.4  
1500  
41.5 36.4 31.3 26.3 21.2  
-
-
62.7  
39.5 34.4 29.4 24.3 19.3  
-
-
67  
52.2 47.2 42.1 37.1 32.0 27.0 21.9 57.0  
56.1 54.8 52.0 47.0 41.9 36.9 31.8 52.7  
54.5 54.5 53.6 48.5 43.4 38.4 33.3 51.6  
50.3 45.3 40.2 35.2 30.1 25.1 20.0  
52.7 52.0 49.7 44.7 39.6 34.6 29.5  
51.6 51.6 50.6 45.5 40.5 35.4 30.4  
1750  
62  
57  
72  
45.6 39.7 33.9 28.1 22.2  
-
-
64.1  
43.4 37.6 31.7 25.9 20.1  
-
-
67  
57.2 51.4 45.5 39.7 33.9 28.1 22.2 58.3  
57.6 57.6 56.3 50.4 44.6 38.8 32.9 53.9  
55.9 55.9 57.9 52.1 46.2 40.4 34.6 52.8  
55.1 49.3 43.4 37.6 31.8 25.9 20.1  
53.9 53.9 53.7 47.9 42.1 36.2 30.4  
52.8 52.8 54.6 48.8 43.0 37.1 31.3  
2000  
62  
57  
72  
49.3 42.6 36.0 29.3 22.7  
-
-
64.2  
47.1 40.5 33.9 27.2 20.6  
-
-
67  
60.1 55.0 48.4 41.7 35.1 28.4 21.8 58.4  
57.8 57.8 57.2 50.5 43.9 37.2 30.6 54.0  
56.2 56.2 57.2 50.5 43.9 37.2 30.6 52.8  
56.8 52.8 46.3 39.7 33.1 26.4 19.8  
54.0 54.0 53.9 47.3 40.6 34.0 27.3  
52.8 52.8 53.8 47.1 40.5 33.9 27.2  
2250  
62  
57  
72  
67  
62  
57  
53.0 45.5 38.1 30.6 23.2  
-
-
64.3  
50.9 43.4 36.0 28.5 21.1  
-
-
63.0 58.6 51.2 43.7 36.3 28.8 21.4 58.5  
58.1 58.1 58.1 50.6 43.2 35.7 28.3 54.1  
56.4 56.4 56.4 49.0 41.5 34.1 26.6 52.9  
115°F  
58.5 56.3 49.2 41.8 34.3 26.9 19.4  
54.1 54.1 54.1 46.6 39.2 31.7 24.3  
52.9 52.9 52.9 45.5 38.0 30.6 23.1  
125°F  
2500  
72  
67  
62  
57  
72  
57.9  
52.2  
48.5  
47.8  
59.0  
53.1  
49.3  
48.7  
60.0  
54.1  
50.2  
49.6  
59.9  
54.0  
50.2  
49.5  
59.9  
53.9  
50.1  
49.4  
6.0  
6.0  
5.9  
5.9  
6.0  
6.0  
5.9  
5.9  
6.0  
5.9  
5.9  
5.9  
6.1  
6.0  
5.9  
6.0  
6.1  
6.0  
6.0  
6.0  
33.8 29.5 25.3 21.0 16.7  
-
-
54.6  
6.7  
6.6  
6.6  
6.6  
6.7  
6.6  
6.5  
6.6  
6.6  
6.5  
6.5  
6.5  
6.7  
6.6  
6.6  
6.6  
6.7  
6.6  
6.6  
6.6  
32.0 27.8 23.5 19.2 14.9  
-
-
43.8 39.6 35.3 31.0 26.7 22.5 18.2 48.7  
48.5 48.0 43.7 39.4 35.1 30.9 26.6 45.4  
47.8 47.8 43.8 39.6 35.3 31.0 26.7 45.2  
42.1 37.8 33.6 29.3 25.0 20.7 16.5  
45.4 45.4 41.6 37.3 33.1 28.8 24.5  
45.2 45.2 41.1 36.9 32.6 28.3 24.0  
1500  
37.5 32.5 27.4 22.4 17.3  
-
-
55.3  
35.6 30.5 25.5 20.4 15.4  
-
-
67  
48.4 43.4 38.3 33.3 28.2 23.1 18.1 49.3  
49.3 49.1 47.4 42.4 37.3 32.3 27.2 46.0  
48.7 48.7 47.6 42.5 37.5 32.4 27.4 45.8  
46.5 41.5 36.4 31.3 26.3 21.2 16.2  
46.0 46.0 45.1 40.1 35.0 30.0 24.9  
45.8 45.8 44.6 39.6 34.5 29.4 24.4  
1750  
62  
57  
72  
41.3 35.4 29.6 23.8 17.9  
-
-
55.9  
39.1 33.3 27.4 21.6 15.8  
-
-
67  
53.0 47.2 41.3 35.5 29.7 23.8 18.0 49.9  
50.2 50.2 51.2 45.3 39.5 33.7 27.9 46.5  
49.6 49.6 51.4 45.5 39.7 33.9 28.0 46.4  
49.9 45.1 39.2 33.4 27.6 21.7 15.9  
46.5 46.5 46.5 42.8 37.0 31.1 25.3  
46.4 46.4 46.4 42.2 36.4 30.6 24.7  
2000  
62  
57  
72  
45.0 38.4 31.7 25.1 18.5  
-
-
55.7  
42.9 36.3 29.6 23.0 16.3  
-
-
67  
53.5 50.6 44.3 37.7 31.0 24.4 17.8 49.7  
50.2 50.2 50.6 44.0 37.3 30.7 24.1 46.3  
49.5 49.5 50.4 43.7 37.1 30.5 23.8 46.1  
49.7 48.3 42.3 35.7 29.0 22.4 15.7  
46.3 46.3 46.3 40.7 34.1 27.4 20.8  
46.1 46.1 46.1 40.4 33.7 27.1 20.4  
2250  
62  
57  
72  
67  
62  
57  
48.8 41.3 33.9 26.4 19.0  
-
-
55.4  
46.7 39.2 31.8 24.3 16.9  
-
-
53.9 53.9 47.3 39.9 32.4 25.0 17.5 49.4  
50.1 50.1 50.1 42.6 35.2 27.7 20.3 46.1  
49.4 49.4 49.4 42.0 34.5 27.1 19.6 45.9  
49.4 49.4 45.4 37.9 30.5 23.0 15.6  
46.1 46.1 46.1 38.6 31.2 23.7 16.3  
45.9 45.9 45.9 38.5 31.0 23.6 16.1  
2500  
1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-  
mance table for the kW of the supply air blower motor.  
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.  
Johnson Controls Unitary Products  
17  
 
343615-YTG-B-0308  
TABLE 19: SUPPLY AIR BLOWER PERFORMANCE (DY036, 048, & 060 DIRECT DRIVE) SIDE DUCT APPLICATION  
2
AVAILABLE EXTERNAL STATIC PRESSURE - IWG  
0.5 0.6 0.7  
0.2  
0.3  
0.4  
0.8  
0.9  
1.0  
1
UNIT  
MOTOR  
TONNAGE  
SPEED  
HI  
1582 320 1538 335 1496 349 1458 363 1418 376 1381 390 1338 403 1298 417 1255 430  
MED/HI 1488 263 1440 276 1396 290 1354 303 1309 316 1263 329 1214 343  
1158  
358 1085 374  
3
MED  
1339 208 1292 221 1247 234 1201 246  
1152  
195 1082 207 1026 220  
145 863 158  
258  
1102  
957  
-
272 1036 288  
967  
303  
924  
313  
3
MED/LOW 1233 171  
1184  
997  
183  
134  
1135  
935  
235  
-
895  
-
248  
-
-
-
-
-
-
-
-
-
LOW  
HI  
1081 130  
-
-
2056 636 2017 696 1978 714 1942 734 1906 749 1864 764 1815 769 1728 743 1582 685  
MED/HI 1866 539 1832 557 1795 571 1754 585 1722 602 1679 619 1636 638 1582 653 1508 639  
MED 1680 408 1641 426 1594 438 1558 455 1517 472 1469 490 1415 505 1370 521 1337 536  
MED/LOW 1582 362 1541 380 1495 391 1465 406 1426 423 1377 440 1326 455 1292 469 1247 485  
3
4
LOW  
HI  
1300 223 1258 237 1202 247  
2256 883 2258 931 2247 950 2223 964 2182 979 2125 971 2044 940 1958 898 1864 854  
2119 808 2089 826 2051 844 2014 859 1965 861 1896 843 1801 806  
2020 637 1999 656 1985 675 1947 696 1910 715 1876 730 1832 740 1793 756 1725 748  
-
-
-
-
-
-
-
-
-
-
-
-
MED/HI 2145 771 2127 784  
MED  
MED/LOW 1757 413 1713 432 1677 451 1639 468 1597 479 1559 497 1521 513 1472 523  
LOW 1570 327 1536 339 1499 356  
1. Factory set on medium speed tap.  
3
5
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values.  
3. Side Duct application (230 Volts)  
TABLE 20: SUPPLY AIR BLOWER PERFORMANCE (DY036, 048, & 060 DIRECT DRIVE) BOTTOM DUCT APPLICATION  
2
AVAILABLE EXTERNAL STATIC PRESSURE - IWG  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.0  
1
UNIT  
MOTOR  
TONNAGE  
SPEED  
HI  
1527 320 1485 335 1445 349 1408 363 1370 376 1334 390 1292 403 1254 417 1213 430  
MED/HI 1437 263 1391 276 1349 290 1308 303 1265 316 1221 329  
1174  
343  
1120  
358 1049 374  
3
MED  
1293 208 1248 221 1205 234  
1161  
183 1097 195 1046 207  
134 904 145  
246  
1114  
992  
-
258 1065 272 1002 288  
935  
303  
894  
313  
3
MED/LOW 1191  
171  
1045 130  
1144  
964  
220  
-
926  
-
235  
-
866  
-
248  
-
-
-
-
-
-
-
-
-
LOW  
HI  
-
-
1985 636 1947 696 1909 714 1875 734 1840 749 1800 764 1752 769 1668 743 1528 685  
MED/HI 1802 539 1768 557 1733 571 1694 585 1662 602 1621 619 1580 638 1528 653 1456 639  
MED 1622 408 1585 426 1539 438 1505 455 1465 472 1419 490 1367 505 1324 521 1291 536  
MED/LOW 1528 362 1489 380 1444 391 1415 406 1377 423 1330 440 1281 455 1248 469 1205 485  
3
4
LOW  
HI  
1256 223 1216 237  
1161  
247  
-
-
-
-
-
-
-
-
-
-
-
-
2177 883 2179 931 2169 950 2145 964 2106 979 2051 971 1973 940 1890 898 1800 854  
MED/HI 2071 771 2053 784 2045 808 2016 826 1980 844 1944 859 1897 861 1830 843 1739 806  
MED 1950 637 1929 656 1916 675 1880 696 1844 715 1811 730 1768 740 1731 756 1665 748  
MED/LOW 1697 413 1654 432 1619 451 1583 468 1542 479 1506 497 1469 513  
LOW 1516 327 1484 339 1448 356  
1. Factory set on medium speed tap.  
3
5
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values.  
3. Bottom Duct application (230 Volts)  
18  
Johnson Controls Unitary Products  
   
343615-YTG-B-0308  
TABLE 21: STATIC RESISTANCES  
RESISTANCE, IWG  
CFM  
DESCRIPTION  
1000  
1200  
0.08  
0.05  
0.07  
0.10  
1400  
0.09  
0.06  
0.08  
0.12  
1600  
0.11  
0.07  
0.09  
0.14  
1800  
2000  
0.15  
0.10  
0.13  
0.18  
2200  
2400  
0.20  
0.14  
0.17  
0.23  
2600  
0.23  
0.16  
0.20  
0.26  
2800  
0.26  
0.19  
0.23  
0.29  
3000  
0.30  
0.22  
0.26  
0.32  
1,3  
ECONOMIZER  
ELECTRIC  
0.07  
0.04  
0.06  
0.08  
0.13  
0.08  
0.11  
0.16  
0.17  
0.12  
0.15  
0.20  
7-15KW  
1
HEATERS  
20-30KW  
2
COOLING ONLY  
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.  
2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.  
3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than  
0.25 IWG, the unit will deliver less CFM during full economizer operation.  
TABLE 22: ELECTRIC HEAT CFM LIMITATIONS  
Minimum Supply Air (CFM)  
Heater kW  
Size  
(Tons)  
Voltage  
5
7
10  
15  
20  
30  
208/230-1-60  
208/230-3-60  
460-3-60  
900  
900  
900  
900  
-
900  
900  
900  
900  
-
900  
900  
900  
-
3
-
900  
900  
900  
-
600-3-60  
-
900  
900  
900  
-
208/230-1-60  
208/230-3-60  
460-3-60  
1200  
1200  
1200  
1200  
-
1200  
1200  
1200  
1200  
1500  
1500  
1500  
1500  
1200  
1200  
1200  
1200  
1500  
1500  
1500  
1500  
1200  
1200  
1200  
1200  
1500  
1500  
1500  
1500  
-
-
1200  
4
5
-
-
600-3-60  
-
-
208/230-1-60  
208/230-3-60  
460-3-60  
1500  
1500  
1500  
1500  
-
1500  
1500  
1500  
1500  
1500  
-
-
600-3-60  
Johnson Controls Unitary Products  
19  
   
343615-YTG-B-0308  
TABLE 23: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET  
OD Fan Supply  
Pwr  
Conv  
Outlet  
Max  
Fuse /  
Breaker  
Size  
(Amps)  
30  
Compressors  
(each)  
2
Motors  
(each)  
Blower  
Motor  
Electric Heat Option  
1
Size  
(Tons)  
MCA  
3
Volt  
(Amps)  
RLA LRA MCC  
FLA  
FLA  
FLA  
Model  
kW  
Stages  
Amps  
None  
E05  
E07  
E10  
E15  
E20  
None  
E05  
E07  
E10  
E15  
E20  
None  
E05  
E07  
E10  
E15  
E20  
None  
E05  
E07  
E10  
E15  
E20  
None  
E07  
E10  
E15  
E20  
None  
E10  
E15  
E20  
None  
E05  
E07  
E10  
E15  
E20  
None  
E05  
E07  
E10  
E15  
E20  
None  
E05  
E07  
E10  
E15  
E20  
None  
E05  
E07  
E10  
E15  
E20  
None  
E07  
E10  
E15  
E20  
None  
E10  
E15  
E20  
-
-
-
22.4  
31.5  
41.2  
55.6  
79.0  
103.1  
22.4  
35.1  
46.6  
62.7  
90.3  
117.9  
18.7  
21.4  
26.9  
35.3  
48.8  
62.7  
18.7  
23.4  
30.1  
39.4  
55.3  
71.2  
10.7  
14.0  
18.9  
24.2  
33.1  
7.4  
15.7  
22.1  
28.5  
29.1  
33.5  
43.2  
57.6  
81.0  
105.1  
29.1  
37.1  
48.6  
64.7  
92.3  
119.9  
24.3  
24.3  
28.9  
37.3  
50.8  
64.7  
24.3  
25.4  
32.1  
41.4  
57.3  
73.2  
12.4  
15.0  
19.9  
25.2  
34.1  
10.5  
16.5  
22.9  
29.3  
4.0  
5.6  
8.0  
11.9  
15.9  
-
5.3  
7.5  
10.6  
15.9  
21.2  
-
4.0  
5.6  
8.0  
11.9  
15.9  
-
5.3  
7.5  
10.6  
15.9  
21.2  
-
6.8  
10.1  
13.6  
19.5  
-
10.6  
15.9  
21.2  
-
4.0  
5.6  
8.0  
11.9  
15.9  
-
5.3  
7.5  
10.6  
15.9  
21.2  
-
4.0  
5.6  
8.0  
11.9  
15.9  
-
5.3  
7.5  
10.6  
15.9  
21.2  
-
6.8  
10.1  
13.6  
19.5  
-
10.6  
15.9  
21.2  
1
1
1
2
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
2
2
-
1
1
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
2
2
-
1
1
2
19.2  
26.9  
38.5  
57.2  
76.4  
-
23.0  
32.6  
46.1  
69.1  
92.2  
-
11.1  
15.5  
22.2  
33.0  
44.1  
-
13.3  
18.8  
26.6  
39.9  
53.2  
-
35  
45  
60  
80  
110  
30  
40  
50  
70  
100  
125  
25  
25  
30  
40  
50  
70  
25  
25  
35  
40  
60  
80  
15  
15  
20  
25  
35  
15  
15  
25  
30  
35  
40  
208-1-60 11.3 68.0 17.5  
230-1-60 11.3 68.0 17.5  
208-3-60 8.3 68.0 13.0  
230-3-60 8.3 68.0 13.0  
2.3  
6.0  
0.0  
2.3  
2.3  
2.3  
6.0  
6.0  
6.0  
0.0  
0.0  
0.0  
036  
(3.0)  
8.5  
460-3-60 5.1 34.0  
575-3-60 3.2 26.0  
8.0  
5.0  
1.3  
1.3  
6.0  
6.0  
0.0  
0.0  
12.7  
17.1  
24.5  
-
10.6  
16.0  
21.3  
-
19.2  
26.9  
38.5  
57.2  
76.4  
-
23.0  
32.6  
46.1  
69.1  
92.2  
-
11.1  
15.5  
22.2  
33.0  
44.1  
-
13.3  
18.8  
26.6  
39.9  
53.2  
-
45  
60  
90  
110  
35  
208-1-60 15.4 86.0 24.0  
230-1-60 15.4 86.0 24.0  
208-3-60 11.5 84.0 18.0  
230-3-60 11.5 84.0 18.0  
2.3  
2.3  
2.3  
2.3  
7.6  
7.6  
7.6  
7.6  
0.0  
0.0  
0.0  
0.0  
40  
50  
70  
100  
125  
30  
30  
35  
40  
60  
70  
30  
35  
35  
45  
60  
80  
15  
15  
20  
25  
35  
15  
20  
25  
30  
048  
(4.0)  
8.5  
460-3-60 5.8 42.0  
575-3-60 5.1 34.0  
9.0  
8.0  
1.3  
1.3  
7.6  
7.6  
0.0  
0.0  
12.7  
17.1  
24.5  
-
10.6  
16.0  
21.3  
20  
Johnson Controls Unitary Products  
 
343615-YTG-B-0308  
TABLE 23: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET (CONT)  
OD Fan Supply  
Pwr  
Conv  
Outlet  
Max  
Compressors  
(each)  
2
Motors  
(each)  
Blower  
Motor  
Electric Heat Option  
Fuse /  
Breaker  
Size  
1
Size  
(Tons)  
MCA  
3
Volt  
(Amps)  
RLA LRA MCC  
FLA  
FLA  
FLA  
Model  
kW  
Stages  
Amps  
(Amps)  
None  
E05  
E07  
E10  
E15  
E20  
E30  
None  
E05  
E07  
E10  
E15  
E20  
E30  
None  
E05  
E07  
E10  
E15  
E20  
E30  
None  
E05  
E07  
E10  
E15  
E20  
E30  
None  
E07  
E10  
E15  
E20  
E30  
None  
E10  
E15  
E20  
E30  
-
-
-
45.9  
45.9  
45.9  
57.6  
81.0  
105.1  
142.9  
45.9  
45.9  
48.6  
64.7  
92.3  
119.9  
163.7  
31.5  
31.5  
31.5  
37.3  
50.8  
64.7  
86.5  
31.5  
31.5  
32.1  
41.4  
57.3  
73.2  
98.5  
17.1  
17.1  
19.9  
25.2  
34.1  
48.1  
13.3  
16.5  
22.9  
29.3  
40.4  
50  
50  
50  
60  
4.0  
5.6  
8.0  
11.9  
15.9  
22.2  
-
5.3  
7.5  
10.6  
15.9  
21.2  
29.6  
-
4.0  
5.6  
8.0  
11.9  
15.9  
22.2  
-
5.3  
7.5  
10.6  
15.9  
21.2  
29.6  
-
1
1
1
2
2
2
-
1
1
1
2
2
2
-
1
1
1
2
2
2
-
1
1
1
2
2
2
-
19.2  
26.9  
38.5  
57.2  
76.4  
106.7  
-
23.0  
32.6  
46.1  
69.1  
92.2  
128.7  
-
11.1  
15.5  
22.2  
33.0  
44.1  
61.6  
-
13.3  
18.8  
26.6  
39.9  
53.2  
74.3  
-
208-1-60 28.8 145.0 45.0  
230-1-60 28.8 145.0 45.0  
208-3-60 17.3 123.0 27.0  
230-3-60 17.3 123.0 27.0  
2.3  
7.6  
0.0  
90  
110  
150  
50  
50  
50  
2.3  
2.3  
2.3  
7.6  
7.6  
7.6  
0.0  
0.0  
0.0  
70  
100  
125  
175  
35  
35  
35  
40  
60  
70  
90  
35  
35  
35  
45  
60  
80  
100  
20  
20  
20  
25  
35  
50  
15  
20  
25  
30  
060  
(5.0)  
6.8  
1
1
2
2
2
-
1
1
2
2
8.5  
10.1  
13.6  
19.5  
28.8  
-
10.6  
15.9  
21.2  
30.4  
12.7  
17.1  
24.5  
36.1  
-
10.6  
16.0  
21.3  
30.5  
460-3-60 9.6 70.0 15.0  
1.3  
1.3  
7.6  
7.6  
0.0  
0.0  
575-3-60 7.4 53.0 11.5  
40  
1. Minimum Circuit Ampacity.  
2. Dual Element, Time Delay Type.  
3. HACR type per NEC.  
Johnson Controls Unitary Products  
21  
343615-YTG-B-0308  
TABLE 24: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/ POWERED CONVENIENCE OUTLET  
OD Fan Supply  
Pwr  
Conv  
Outlet  
Max  
Fuse /  
Breaker  
Size  
(Amps)  
40  
Compressors  
(each)  
2
Motors  
(each)  
Blower  
Motor  
Electric Heat Option  
1
Size  
(Tons)  
MCA  
3
Volt  
(Amps)  
RLA LRA MCC  
FLA  
FLA  
FLA  
Model  
kW  
Stages  
Amps  
None  
E05  
E07  
E10  
E15  
E20  
None  
E05  
E07  
E10  
E15  
E20  
None  
E05  
E07  
E10  
E15  
E20  
None  
E05  
E07  
E10  
E15  
E20  
None  
E07  
E10  
E15  
E20  
None  
E10  
E15  
E20  
None  
E05  
E07  
E10  
E15  
E20  
None  
E05  
E07  
E10  
E15  
E20  
None  
E05  
E07  
E10  
E15  
E20  
None  
E05  
E07  
E10  
E15  
E20  
None  
E07  
E10  
E15  
E20  
None  
E10  
E15  
E20  
-
-
-
32.4  
44.0  
53.7  
68.1  
91.5  
115.6  
32.4  
47.6  
59.1  
75.2  
102.8  
130.4  
29.1  
33.9  
39.4  
47.8  
61.3  
75.2  
29.1  
35.9  
42.6  
51.9  
67.8  
83.7  
15.7  
20.2  
25.2  
30.4  
39.3  
11.6  
20.7  
27.1  
33.5  
39.1  
46.0  
55.7  
70.1  
93.5  
117.6  
39.1  
49.6  
61.1  
77.2  
104.8  
132.4  
34.3  
35.9  
41.4  
49.8  
63.3  
77.2  
34.3  
37.9  
44.6  
53.9  
69.8  
85.7  
17.4  
21.2  
26.2  
31.4  
40.3  
14.5  
21.5  
27.9  
34.3  
4.0  
5.6  
8.0  
11.9  
15.9  
-
5.3  
7.5  
10.6  
15.9  
21.2  
-
4.0  
5.6  
8.0  
11.9  
15.9  
-
5.3  
7.5  
10.6  
15.9  
21.2  
-
6.8  
10.1  
13.6  
19.5  
-
10.6  
15.9  
21.2  
-
4.0  
5.6  
8.0  
11.9  
15.9  
-
5.3  
7.5  
10.6  
15.9  
21.2  
-
4.0  
5.6  
8.0  
11.9  
15.9  
-
5.3  
7.5  
10.6  
15.9  
21.2  
-
6.8  
10.1  
13.6  
19.5  
-
10.6  
15.9  
21.2  
1
1
1
2
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
2
2
-
1
1
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
1
2
2
-
1
1
2
2
-
1
1
2
19.2  
26.9  
38.5  
57.2  
76.4  
-
23.0  
32.6  
46.1  
69.1  
92.2  
-
11.1  
15.5  
22.2  
33.0  
44.1  
-
13.3  
18.8  
26.6  
39.9  
53.2  
-
45  
60  
70  
100  
125  
40  
50  
60  
208-1-60 11.3 68.0 17.5  
230-1-60 11.3 68.0 17.5  
208-3-60 8.3 68.0 13.0  
230-3-60 8.3 68.0 13.0  
2.3  
6.0  
10.0  
2.3  
2.3  
2.3  
6.0  
6.0  
6.0  
10.0  
10.0  
10.0  
80  
110  
150  
35  
35  
40  
50  
70  
80  
35  
40  
45  
60  
70  
90  
20  
20  
25  
30  
40  
15  
20  
30  
35  
50  
50  
60  
80  
100  
125  
50  
036  
(3.0)  
8.5  
460-3-60 5.1 34.0  
575-3-60 3.2 26.0  
8.0  
5.0  
1.3  
1.3  
6.0  
6.0  
5.0  
4.0  
12.7  
17.1  
24.5  
-
10.6  
16.0  
21.3  
-
19.2  
26.9  
38.5  
57.2  
76.4  
-
23.0  
32.6  
46.1  
69.1  
92.2  
-
11.1  
15.5  
22.2  
33.0  
44.1  
-
13.3  
18.8  
26.6  
39.9  
53.2  
-
208-1-60 15.4 86.0 24.0  
230-1-60 15.4 86.0 24.0  
208-3-60 11.5 84.0 18.0  
230-3-60 11.5 84.0 18.0  
2.3  
2.3  
2.3  
2.3  
7.6  
7.6  
7.6  
7.6  
10.0  
10.0  
10.0  
10.0  
50  
70  
80  
110  
150  
45  
45  
45  
50  
70  
80  
45  
45  
45  
60  
70  
90  
20  
20  
25  
30  
40  
15  
20  
30  
35  
048  
(4.0)  
8.5  
460-3-60 5.8 42.0  
575-3-60 5.1 34.0  
9.0  
8.0  
1.3  
1.3  
7.6  
7.6  
5.0  
4.0  
12.7  
17.1  
24.5  
-
10.6  
16.0  
21.3  
22  
Johnson Controls Unitary Products  
 
343615-YTG-B-0308  
TABLE 24: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/ POWERED CONVENIENCE OUTLET (CONT)  
OD Fan Supply  
Pwr  
Conv  
Outlet  
Max  
Compressors  
(each)  
2
Motors  
(each)  
Blower  
Motor  
Electric Heat Option  
Fuse /  
Breaker  
Size  
1
Size  
(Tons)  
MCA  
3
Volt  
(Amps)  
RLA LRA MCC  
FLA  
FLA  
FLA  
Model  
kW  
Stages  
Amps  
(Amps)  
None  
E05  
E07  
E10  
E15  
E20  
E30  
None  
E05  
E07  
E10  
E15  
E20  
E30  
None  
E05  
E07  
E10  
E15  
E20  
E30  
None  
E05  
E07  
E10  
E15  
E20  
E30  
None  
E07  
E10  
E15  
E20  
E30  
None  
E10  
E15  
E20  
E30  
-
-
-
55.9  
55.9  
55.9  
70.1  
93.5  
117.6  
155.4  
55.9  
55.9  
61.1  
77.2  
104.8  
132.4  
176.2  
41.5  
41.5  
41.5  
49.8  
63.3  
77.2  
99.0  
41.5  
41.5  
44.6  
53.9  
69.8  
85.7  
111.0  
22.1  
22.1  
26.2  
31.4  
40.3  
54.3  
17.3  
21.5  
27.9  
34.3  
45.4  
60  
60  
60  
80  
100  
125  
175  
60  
60  
70  
4.0  
5.6  
8.0  
11.9  
15.9  
22.2  
-
5.3  
7.5  
10.6  
15.9  
21.2  
29.6  
-
4.0  
5.6  
8.0  
11.9  
15.9  
22.2  
-
5.3  
7.5  
10.6  
15.9  
21.2  
29.6  
-
1
1
1
2
2
2
-
1
1
1
2
2
2
-
1
1
1
2
2
2
-
1
1
1
2
2
2
-
19.2  
26.9  
38.5  
57.2  
76.4  
106.7  
-
23.0  
32.6  
46.1  
69.1  
92.2  
128.7  
-
11.1  
15.5  
22.2  
33.0  
44.1  
61.6  
-
13.3  
18.8  
26.6  
39.9  
53.2  
74.3  
-
208-1-60 28.8 145.0 45.0  
230-1-60 28.8 145.0 45.0  
208-3-60 17.3 123.0 27.0  
230-3-60 17.3 123.0 27.0  
2.3  
7.6  
10.0  
2.3  
2.3  
2.3  
7.6  
7.6  
7.6  
10.0  
10.0  
10.0  
80  
110  
150  
200  
45  
45  
45  
50  
70  
80  
100  
45  
45  
45  
60  
70  
90  
125  
25  
25  
25  
060  
(5.0)  
6.8  
1
1
2
2
2
-
1
1
2
2
8.5  
10.1  
13.6  
19.5  
28.8  
-
10.6  
15.9  
21.2  
30.4  
12.7  
17.1  
24.5  
36.1  
-
10.6  
16.0  
21.3  
30.5  
460-3-60 9.6 70.0 15.0  
1.3  
1.3  
7.6  
7.6  
5.0  
4.0  
30  
40  
60  
20  
20  
30  
35  
45  
575-3-60 7.4 53.0 11.5  
1. Minimum Circuit Ampacity.  
2. Dual Element, Time Delay Type.  
3. HACR type per NEC.  
Johnson Controls Unitary Products  
23  
343615-YTG-B-0308  
TABLE 25: DY PHYSICAL DATA  
DY  
MODELS  
036  
12 X 10  
3/4  
3
048  
12 X 10  
1
060  
12 X 10  
1
Centrifugal Blower (Dia. x Wd. in.)  
Fan Motor HP (Direct Drive)  
Rows Deep  
EVAPORATOR  
BLOWER  
4
4
EVAPORATOR  
COIL  
Fins Per Inch  
13  
13  
13  
2
Face Area (Ft. )  
5.1  
24  
5.1  
24  
5.1  
24  
Propeller Dia. (in.)  
Fan Motor HP  
Nom. CFM  
CONDENSER  
FANS  
1/2  
4200  
2
1/2  
4200  
2
1/2  
4200  
2
Rows Deep  
CONDENSER  
COILS  
Fins Per Inch  
18  
18  
18  
2
Face Area (Ft. )  
17.1  
1
17.1  
1
17.1  
1
Quantity  
COMPRESSOR  
Type  
Recip.  
2
Recip.  
2
Scroll  
2
Quantity Per Unit (15” X 20” X 1” or 2“)  
Quantity Per Unit (14” X 25” X 1” or 2“)  
AIR  
FILTERS  
1
1
1
2
Total Face Area (Ft. )  
6.3  
9/4  
6.3  
9/8  
6.3  
11/8  
CHARGE  
Refrigerant 22 (lbs./oz.)  
1
TABLE 26: ELECTRIC HEAT CORRECTION FACTORS  
kW CAP. MULTI-  
TABLE 27: VOLTAGE LIMITATIONS  
VOLTAGE  
NOMINAL VOLTAGE  
VOLTAGE  
POWER SUPPLY  
PLIER  
MIN.  
MAX.  
208  
230  
460  
575  
1.00  
0.92  
0.92  
0.92  
208  
240  
480  
600  
208/230-1-60  
208/230-3-60  
187  
252  
252  
187  
460-3-60  
575-3-60  
432  
540  
504  
630  
1. Utilization Range “A” in accordance with ARI Standard  
110.  
24  
Johnson Controls Unitary Products  
     
343615-YTG-B-0308  
TYPICAL POWER WIRING  
REFER TO THE ELECTRICAL DATA  
TABLES TO SIZE THE DISCONNECT  
SWITCH, OVERCURRENT PROTEC-  
TION AND WIRING.  
TYPICAL CONTROL WIRING  
COOLING ONLY (24 VOLT THERMOSTAT)  
COOLING / HEATING (24 VOLT THERMOSTAT)  
THERMOSTAT1 UNIT TERMINAL  
THERMOSTAT1  
TERMINALS  
TERMINALS  
STRIP TB1  
UNIT TERMINAL  
RV  
R
RH  
STRIP TB1  
ADD  
JUMPER  
24 VOLT  
YC  
GF  
Y1  
Y2  
G
RC  
Y
R
Y1  
Y2  
W1  
W2  
G
TRANSFORMER  
24 VOLT  
TRANSFORMER  
W
G
C
124 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER  
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.  
C
COOLING / HEATING (ELECTRONIC THERMOSTAT)  
MULTI STAGE  
1
24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND  
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF  
HEAT, USE THERMOSTAT 2TH0471024.  
1
THERMOSTAT  
TERMINALS  
UNIT TERMINAL  
STRIP TB1  
RC  
RH  
Y1  
24 VOLT  
TRANSFORMER  
ADD  
JUMPER  
R
Y1  
Y2  
W1  
W2  
G
COOLING / HEATING (ELECTRONIC THERMOSTAT)  
SINGLE STAGE  
2
3
Y2  
W1  
THERMOSTAT1  
4
W2  
UNIT TERMINAL  
STRIP TB1  
TERMINALS  
G
B
RH  
RC  
Y
C
R
Y1  
W1  
G
LED 1  
X
ADD  
JUMPER  
NOT  
USED  
LED 2  
COM  
A1  
OCC  
W
4
G
ADD  
JUMPER  
C
A2  
24 VOLT  
TRANSFORMER  
T
TO REMOTE SENSOR  
2TH040702224 IF USED  
T
1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).  
2 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.  
1ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).  
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT  
2TH04700224.  
3 SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE  
ELECTRIC HEATER OR 2 STAGE GAS HEAT.  
4
REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR  
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY  
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE  
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.  
FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING  
Johnson Controls Unitary Products  
25  
 
343615-YTG-B-0308  
FIGURE 3 - UNIT DIMENSIONS (3 - 5 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW  
FIGURE 4 - UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEAT) FRONT VIEW  
26  
Johnson Controls Unitary Products  
   
343615-YTG-B-0308  
DETAIL “A”  
FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD  
DETAIL “B”  
FIGURE 6 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD  
Johnson Controls Unitary Products  
27  
   
343615-YTG-B-0308  
FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)  
TABLE 29: MINIMUM CLEARANCES  
LOCATION  
Filter Access  
CLEARANCE  
Blower Motor Access  
Dot Plugs  
24” (Cooling/Electric Heat)  
32” (Gas Heat)  
Front  
Rear  
12” (Less Economizer)  
36” (With Economizer or Fixed  
Air/Motorized Damper)  
Field-Supplied Disconnect  
Switch Location  
24” (Less Economizer)  
36” (With Economizer)  
Mounting Bracket for  
Disconnect Switch  
Left Side (Filter Access)  
A,B  
(Field Supplied)  
Wiring Entry  
(See Detail “B”)  
Control Box Access  
Right Side (Cond. Coil)  
Below Unit1  
24”  
0”  
Disconnect Switch Location  
and Motor Access Panel for  
Unit with “Belt-Drive” Option  
72” (For  
Condenser Air Discharge)  
Above Unit2  
FIGURE 8 - DISCONNECT/BLOWER ACCESS LOCATION  
TABLE 28: UTILITIES ENTRY  
1. Units may be installed on combustible floors made  
from wood or class A, B, or C roof covering material.  
2. Units must be installed outdoors. Overhanging struc-  
tures or shrubs should not obstruct condenser air dis-  
charge outlet.  
HOLE  
A
OPENING SIZE (DIA.)  
USED FOR  
Side  
Bottom  
Side  
1
2
7/8” KO  
Control Wiring  
B
Power Wiring  
2” KO  
Bottom  
C
D
1-5/8” KO  
1-1/2” KO  
Gas Piping (Front)  
Gas Piping (Bottom)  
1. Opening in the bottom to the unit can be located by the  
side in the insulation.  
2. Do not remove the 2” knockout ring.  
28  
Johnson Controls Unitary Products  
         
343615-YTG-B-0308  
FIGURE 9 - TYPICAL APPLICATIONS  
Johnson Controls Unitary Products  
29  
 
343615-YTG-B-0308  
BACK OF UNIT  
BACK OF UNIT  
A
A
7
7
44 /8  
44 /8  
1
1
82 /4  
82 /4  
B
D
F
X
X
B
C
E
APPROXIMATE  
APPROXIMATE  
CENTER OF GRAVITY  
CENTER OF GRAVITY  
CONDENSER COIL  
END OF UNIT  
CONDENSER COIL  
END OF UNIT  
C
D
FRONT OF UNIT  
FRONT OF UNIT  
Y
Y
FIGURE 10 -FOUR AND SIX POINT LOADING  
TABLE 30: DY 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION  
4-Point Loading (lb)  
6-Point Loading (lb)  
UNIT  
TOTAL  
A
B
C
D
A
B
C
D
E
F
132  
141  
143  
145  
148  
134  
145  
150  
135  
147  
149  
151  
125  
133  
135  
138  
140  
127  
138  
142  
128  
139  
141  
143  
155  
166  
168  
171  
174  
158  
171  
177  
159  
173  
175  
178  
164  
175  
178  
181  
184  
167  
181  
187  
168  
182  
185  
188  
89  
95  
85  
91  
93  
94  
96  
87  
94  
97  
88  
95  
97  
98  
82  
88  
89  
91  
92  
84  
91  
94  
84  
92  
93  
95  
102  
110  
111  
113  
115  
104  
113  
117  
105  
114  
116  
118  
106  
114  
115  
117  
119  
108  
117  
121  
109  
118  
120  
122  
110  
118  
120  
122  
124  
112  
122  
125  
113  
123  
125  
126  
DY036 Cooling/ Electric  
DY036N04  
575  
615  
625  
635  
645  
585  
635  
655  
590  
640  
650  
660  
96  
DY036D06  
98  
DY036N08  
99  
DY036D10  
90  
DY048 Cooling/ Electric  
DY048(D,N)06  
DY048(D,N)10  
DY060 Cooling/ Electric  
DY060D06  
98  
101  
91  
99  
100  
102  
DY060N08  
DY060(D,N)10  
TABLE 31: CENTER OF GRAVITY  
DIMENSION  
3 - 5 TON  
40”  
X
Y
20”  
30  
Johnson Controls Unitary Products  
     
343615-YTG-B-0308  
TABLE 32: OPERATING WEIGHTS (LBS.)  
MODEL SIZE  
DY (Cooling Only)  
3 TON  
575  
615  
-
4 TON  
585  
-
5 TON  
590  
-
N04  
N06  
N08  
N10  
D06  
D10  
635  
-
-
BASIC  
UNIT  
635  
-
650  
660  
640  
660  
DY  
(Gas/Electric)  
655  
635  
655  
50  
625  
645  
Economizer  
Motorized Damper  
26  
OPTIONS  
ACCY.  
5 - 7 kW  
10 - 15 kW  
20 - 30 kW  
18  
Electric Heater  
23  
28  
Roof Curb  
Barometric Relief / Fixed Air Damper  
92  
10  
FIGURE 11 -ROOF CURB DIMENSIONS  
Johnson Controls Unitary Products  
31  
   
343615-YTG-B-0308  
UNIT CABINET  
GUIDE SPECIFICATIONS  
Unit cabinet shall be constructed of a combination of G60 and  
G90 galvanized steel, with exterior surfaces coated with a  
non-chalking, powdered paint finish, certified at 750 hours  
salt spray test per ASTMB117 standards. Indoor blower sec-  
tion shall be insulated with a minimum 1/2” thick insulation,  
coated on the airside. Aluminum foil faced insulation shall be  
used in the furnace compartment and be fastened with ridged  
fasteners to prevent insulation from entering the air stream.  
Cabinet panels shall be “large” size, easily removable for ser-  
vicing and maintenance. Full perimeter base rails shall be  
provided to assure reliable transit of equipment, overhead rig-  
ging and proper sealing on roof curb applications. Disposable  
1" filters shall be furnished and be accessible through a  
removable access door, sealed airtight. Units filter track shall  
be designed to accommodate either 1" or 2" filters. Fan per-  
formance measuring ports shall be provided on the outside of  
the cabinet to allow accurate air measurements of evaporator  
fan performance without removing panels or creating air by-  
pass of the coils. Condensate pan shall be internally sloped  
and conform to ASHRAE 62-89 self-draining standards. Con-  
densate connection shall be a minimum of 3/4” I.D. female  
and be a ridged mount connection.  
GENERAL  
Units shall be manufactured by York International Unitary  
Products Group in an ISO 9001 certified facility.  
York's Sunline Magnumunits are convertible single pack-  
age units. Although the units are primarily designed for curb  
mounting on a roof, they can also be slab-mounted at ground  
level or set on steel beams above a finished roof. Cooling  
only, cooling with gas heat and cooling with electric heat  
models are available with a wide variety of factory-mounted  
options and field-installed accessories to make them suitable  
for almost every application. All units are self-contained and  
assembled on full perimeter base rails with holes in the four  
corners for overhead rigging. Every unit is completely piped,  
wired, charged and tested at the factory to simplify the field  
installation and to provide years of dependable operation. All  
models (including those with an economizer) are suitable for  
either bottom or horizontal duct connections. Models with  
power exhaust are suitable for bottom duct connections only.  
For bottom duct, remove the sheet metal panels from the  
supply and return air openings through the base of the unit.  
For horizontal duct, remove the supply and return air panels  
on the rear of the unit.  
INDOOR (EVAPORATOR) FAN ASSEMBLY  
The indoor fan shall be a factory installed direct drive. Job  
site selected (B.H.P.) brake horsepower shall not exceed the  
motors nameplate horsepower rating, plus the service factor.  
Units shall be designed not to operate above service factor.  
Fan wheel shall be double-inlet type with forward-curved  
blades, dynamically balanced to operate smoothly throughout  
the entire range of operation. Airflow design shall be constant  
air volume. Bearings shall be sealed and permanently lubri-  
cated for longer life and no maintenance.  
All non-Scroll compressors include crankcase heaters and all  
compressors have internal pressure relief. Every refrigerant  
circuit includes a liquid line filter-drier, a discharge line high  
pressure switch and a suction line with a freezestat and low  
pressure/loss of charge switch.The unit control circuit  
includes a 75 VA transformer, a 24-volt circuit breaker and a  
relay board with a compressor lockout circuit, a terminal strip  
for thermostat wiring, plus an additional set of pin connectors  
to simplify the interface of additional field controls. All models  
are CSA listed. All models include a 1-year limited warranty  
on the complete unit. Compressors and electric heater ele-  
ments carry a 5-year warranty. Aluminized steel and Stainless  
steel tubular heat exchangers carry a 10-year warranty.  
OUTDOOR (CONDENSER) FAN ASSEMBLY  
The outdoor fan shall be of the direct-driven propeller type,  
discharge air vertically, have aluminum blades riveted to a  
corrosion resistant steel spider bracket and shall be dynami-  
cally balanced for smooth operation. The outdoor fan motor  
shall be totally enclosed with permanently lubricated bear-  
ings, internally protected against overload conditions and  
staged independently.  
DESCRIPTION  
Units shall be factory-assembled, single packaged, Electric  
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat  
and designed for outdoor mounted installation.  
REFRIGERANT COMPONENTS  
The 3 ton, 4 ton and 5 ton units shall have minimum SEER  
rating of 14. They shall have built-in field convertible duct  
connections for down discharge supply/return or horizontal  
discharge supply/return, and be available with factory  
installed options or field installed accessories. The units shall  
be factory wired, piped, charged with R-22 refrigerant and  
factory tested prior to shipment. All unit wiring shall be both  
numbered and color coded. All units the cooling performance  
shall be rated in accordance with DOE and ARI test proce-  
dures. Units shall be CSA listed, classified to ANSI Z21.47,  
UL 1995/CSA No. 236 standards.  
Compressor:  
a. Shall be internally protected with internal high-pres-  
sure relief and over temperature protection.  
b. Shall have internal spring isolation and sound muf-  
fling to minimize vibration and noise, and be exter-  
nally isolated on a dedicated, independent mounting.  
32  
Johnson Controls Unitary Products  
 
343615-YTG-B-0308  
Coils:  
dant main gas valve. Venter wheel shall be constructed of  
stainless steel for corrosion resistance. The heat exchanger  
shall be of the tubular type, constructed of T1-40 aluminized  
steel for corrosion resistance and allowing minimum mixed  
air entering temperature of 25°F. Burners shall be of the  
inshot type, constructed of aluminum coated steel and con-  
tain air mixture adjustments. All gas piping shall enter the unit  
cabinet at a single location through either the side or curb  
without any field modifications. Integrated control boards  
shall provide timed control of evaporator fan functioning and  
burner ignition. Heating section shall be provided with the fol-  
lowing minimum protection:  
a. Evaporator and condenser coils shall have alumi-  
num plate fins mechanically bonded to seamless  
internally enhanced copper tubes with all joints  
brazed. Special Phenolic coating shall be available  
as a factory option.  
b. Evaporator and Condenser coils shall be of the  
direct expansion, draw-thru, design.  
Refrigerant Circuit and Refrigerant Safety Components shall  
include:  
a. Independent fixed-orifice or thermally operated  
expansion devices.  
a. Primary and auxiliary high-temperature limit switches.  
b. Induced draft motor speed sensor.  
c. Flame roll out switch.  
b. Filter drier/strainer to eliminate any moisture or for-  
eign matter.  
c. Accessible service gage connections on both suc-  
tion and liquid lines to charge, evacuate, and mea-  
sure refrigerant pressure during any necessary  
servicing or troubleshooting, without losing charge.  
d. Flame proving controls.  
e. If any of the above safety devices trip, a LED (light-  
emitting diode) indicator shall flash a diagnostic  
code that indicates which safety switch has tripped.  
d. The refrigeration system shall provide at least 15°F  
of sub-cooling at design conditions.  
ELECTRIC HEATING SECTION  
UNIT CONTROLS  
An electric heating section, with nickel chromium elements,  
shall be provided in a range of 5 thru 30 KW, offering two  
stages of capacity - 16 KW and above on 208/230 volt heaters  
and 20 KW and above on 460 and 575 volt heaters. The heat-  
ing section shall have a primary limit control(s) and automatic  
reset to prevent the heating element system from operating at  
an excessive temperature. The heating section assembly  
shall slide out of the unit for easy maintenance and service.  
Units with Electric Heating shall be wired for a single point  
power supply with branch circuit fusing (where required).  
a. Unit shall be complete with self-contained low-volt-  
age control circuit protected by a resetable circuit  
breaker on the 24-volt transformer side.  
b. Unit shall incorporate a lockout circuit which pro-  
vides reset capability at the space thermostat or  
base unit, should any of the following standard  
safety devices trip and shut off compressor.  
c. Loss-of-charge/Low-pressure switch.  
d. High-pressure switch.  
UNIT OPERATING CHARACTERISTICS  
e. Freeze-protection thermostat, evaporator coil.  
a. Unit shall be capable of starting and running at 125°F  
outdoor temperature, exceeding maximum load crite-  
ria of ARI Standard 210/240. The compressor, with  
standard controls, shall be capable of operation  
down to 0°F outdoor temperature. Unit shall be pro-  
vided with fan time delay to prevent cold air delivery  
before heat exchanger warms up (Gas heat only).  
f. Unit shall incorporate “AUTO RESET” compressor  
over temperature, over current protection.  
g. Unit shall operate with conventional thermostat  
designs and have a low voltage terminal strip for  
easy hook-up.  
h. Unit control board shall have on-board diagnostics  
and fault code display.  
ELECTRICAL REQUIREMENTS  
All unit power wiring shall enter unit cabinet at a single factory  
provided location and be capable of side or bottom entry, to  
minimize roof penetrations and avoid unit field modifications.  
Separate side and bottom openings shall be provided for the  
control wiring.  
i.  
Standard controls shall include anti-short cycle and  
low voltage protection, and permit cooling operation  
down to 0°F.  
j.  
Control board shall monitor each refrigerant safety  
switch independently.  
STANDARD LIMITED WARRANTIES  
k. Control board shall retain last 5 fault codes in non  
volatile memory which will not be lost in the event of  
a power loss.  
Compressor 5 Years  
Heat Exchanger 10 Years  
Electric Heat Element 5 Years  
Other Parts 1 Year  
GAS HEATING SECTION (SINGLE OR 2 STAGE)  
Shall be designed with induced draft combustion with post  
purge logic, energy saving direct spark ignition, and redun-  
Johnson Controls Unitary Products  
33  
343615-YTG-B-0308  
OPTIONAL OUTDOOR AIR (Shall be made available by  
either/or):  
HIGH ALTITUDE - PROPANE GAS - Contains orifices  
required for applications between 2000 and 6000 feet  
altitude. Must be used with propane conversion kit.  
ELECTRONIC ENTHALPY AUTOMATIC ECONO-  
MIZER- Outdoor and return air dampers that are inter-  
locked and positioned by a fully-modulating, spring  
return damper actuator. The maximum leakage rate for  
the outdoor air intake dampers shall not exceed 2%  
when dampers are fully closed and operating against a  
pressure differential of 0.5 IWG. A unit-mounted potenti-  
ometer shall be provided to adjust the outdoor and return  
air damper assembly to take in CFM of outdoor air to  
meet the minimum ventilation requirement of the condi-  
tioned space during normal operation. During econo-  
mizer operation, a mixed-air temperature control shall  
modulate the outdoor and return air damper assembly to  
prevent the supply air temperature from dropping below  
55°F. Changeover from compressor to economizer oper-  
ation shall be provided by an integral electronic enthalpy  
control that feeds input into the basic module. The out-  
door intake opening shall be covered with a rain hood  
that matches the exterior of the unit. Water eliminator/fil-  
ters shall be provided. Simultaneous economizer/com-  
pressor operation is also possible. Dampers shall fully  
close on power loss.  
LOW NOX - Required to reduce the emission of nitrogen  
oxides below 40 nanograms per joule.  
GAS PIPING - Contains 1/2” pipe nipples, fittings and  
gas cock (including panel assess gaskets) required for  
bottom gas supply connection with external shut off.  
POWER EXHAUST OPTION - To work in conjunction  
with economizers.  
ELECTRIC HEATERS  
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD -  
Contains all hood panels and the hardware for assem-  
bling.  
MANUAL OUTDOOR AIR DAMPER  
COIL GUARD KIT - Guard for cooling coil.  
HAIL GUARD  
FLUE EXHAUST EXTENSION  
OTHER FACTORY INSTALLED OPTIONS  
POWER EXHAUST OPTION - To work in conjunction  
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air  
dampers are positioned by a 2-position, spring-return  
damper actuator. The maximum leakage rate for the out-  
door air intake dampers shall not exceed 2% when  
dampers are fully closed and operating against a pres-  
sure differential of 0.5 IWG. A unit-mounted potentiome-  
ter shall be provided to adjust the outdoor damper  
assembly to take in the design CFM of outdoor air to  
meet the ventilation requirements of the conditioned  
space during normal operation. Whenever the indoor fan  
motor is energized, the dampers open up to one of two  
pre-selected positions - regardless of the outdoor air  
enthalpy. Dampers return to the fully closed position  
when the indoor fan motor is de-energized. Dampers  
shall fully close on power loss.  
with economizers.  
STAINLESS STEEL HEAT EXCHANGER  
STAINLESS STEEL DRAIN PAN  
BOTTOM DRAIN CONNECTION  
TECHNICOAT PHENOLIC COATED CONDENSER  
AND EVAPORATOR COIL  
ELECTRONIC SINGLE ENTHALPY ECONOMIZER  
DIRTY FILTER SWITCH  
PHASE MONITOR  
COIL GUARD  
POWERED GFI CONVENIENCE OUTLET  
NON-POWERED GFI CONVENIENCE OUTLET  
®
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE  
BAS CONTROLS (S implicity INTELLI-Comfort™,  
CPC, JOHNSON, HONEYWELL, NOVAR)  
ROOF CURB - 14"and 8” high, full perimeter curb with  
wood nailer (shipped knocked-down).  
BAS READY ECONOMIZER (2-10 V.D.C. ACTUATOR  
WITHOUT A CONTROLLER)  
BAROMETRIC RELIEF DAMPER - Contains a rain  
hood, air inlet screen, exhaust damper and mounting  
hardware. Used to relieve internal air pressure through  
the unit.  
HINGED FILTER DOOR ACCESS AND TOOLESS  
ACCESS PANELS  
2" PLEATED FILTERS  
PROPANE CONVERSION KIT - Contains new orifices  
and gas valve parts to convert from natural to L.P. gas.  
One per unit required.  
DISCONNECT SWITCH  
SUPPLY AIR SMOKE DETECTOR  
RETURN AIR SMOKE DETECTOR  
HIGH ALTITUDE - NATURAL GAS - Contains orifices  
required for applications between 2000 and 6000 feet  
altitude.  
34  
Johnson Controls Unitary Products  
343615-YTG-B-0308  
Johnson Controls Unitary Products  
35  
Subject to change without notice. Printed in U.S.A.  
343615-YTG-B-0308  
Copyright © 2008 by Johnson Controls, Inc. All rights reserved.  
Supersedes: 343615-YTG-A-0807  
Johnson Controls Unitary Products  
5005 York Drive  
Norman, OK 73069  

Sanyo Spw Umr124exh56 User Manual
Samsung Tipo Ventana Aw1090a User Manual
Samsung Avmkh026ea User Manual
Panasonic Cs Ce7gkew User Manual
LG 43LX340H UA User Manual
HP DESKJET D4363 User Manual
HP 2520G User Manual
HITACHI CP WX8265 02 User Manual
DENON HEOS LINK User Manual
CRAFTSMAN 316.711201 User Manual