York Mv User Manual

255427-YTG-F-1006  
DESCRIPTION  
This unique modular system allows the flexibility to handle any  
application. These versatile coils and blowers may be used for  
upflow, downflow, or horizontal left or right applications. They  
may be combined to function as a cooling only unit or with a heat  
pump including electric heat for 1 and 3 phase applications. The  
blower and electric heater could be used as stand alone electric  
furnaces.  
FEATURES  
TECHNICAL GUIDE  
BLOWERS - Models to match any air flow or voltage require-  
ment. The compact size allows easy installation. Blowers are  
sized to deliver design air quantity both efficiently and quietly.  
The motors provide a selection of air quantities to match any  
application. All models include a one-minute blower off delay as  
standard to enhance system efficiency ratings. The durable, pre-  
painted steel protects the unit against rust and corrosion. All  
models have 1 inch foil face fiber glass insulation, providing a  
thermal insulation value of R-4.2.  
MODELS: MV  
MODULAR VARIABLE SPEED AIR HANDLERS  
FOR USE WITH SPLIT SYSTEM  
COOLING & HEAT PUMP  
1200 - 2000 CFM BLOWERS  
3 - 5 TON COILS  
COILS - Staggered rows of rifled copper tubes are mechanically  
expanded into enhanced surface aluminum fins to provide high  
heat transfer and long-lasting quality. The MC multi-position  
coils may be used for upflow, downflow, and horizontal left or  
right applications. Coil cabinets are insulated with 3/4" foil face  
insulation to prevent sweating.  
OPTIONAL 1 & 3φ ELECTRIC HEATERS  
ELECTRIC HEATERS - Both single and three phase electric  
heater models are available to match any requirement. All heat-  
ers include nickel-chromium elements with a 5-year limited war-  
ranty on 1 Ø heating elements and 1 year limited warranty on 3  
Ø heating elements. Sequential operation is provided to control  
heaters in all models. Circuit breakers are used in 208/230 volt,  
single-phase heaters of 15 KW and larger.  
Models equipped with circuit breakers may be altered in the field  
to use multi-source power supply. Over-temperature limit  
switches provide protection from airflow loss with fusible link  
backup protection.  
ACCESSORIES - A full line of matching accessories available  
for use with the blower and coils to allow any type application.  
LIMITATIONS - These units must be wired and installed in  
accordance with all national and local safety codes.  
Voltage limits are as follows:  
NORMAL OPERATING  
AIR HANDLER VOLTAGE  
VOLTAGE RANGE*  
208/230-1-60  
187 - 253  
* Rated in accordance with ARI Standard 110, utilization range “A”.  
Air flow must be within the minimum and maximum limits approved for electric  
heat, evaporator coils and outdoor units.  
ISO 9001  
Certified Quality  
Management System  
Due to continuous product improvement, specifications  
subject to change without notice.  
Additional rating information can be found at  
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE  
255427-YTG-F-1006  
COOLING CAPACITY - COIL ONLY  
MBH @ Evaporator Temperature and  
Corresponding Pressure °F / PSIG  
Blower  
Model  
Coil  
Model  
Rated  
CFM  
Entering Air °F  
(Dry / Wet Bulb)  
35 / 61.5  
40 / 68.5  
45 / 76.0  
50 / 84.0  
Multi-Position - Upflow / Downflow / Horizontal  
85 / 72  
80 / 67  
75 / 62  
70 / 57  
85 / 72  
80 / 67  
75 / 62  
70 / 57  
85 / 72  
80 / 67  
75 / 62  
70 / 57  
85 / 72  
80 / 67  
75 / 62  
70 / 57  
85 / 72  
80 / 67  
75 / 62  
70 / 57  
85 / 72  
80 / 67  
75 / 62  
70 / 57  
85 / 72  
80 / 67  
75 / 62  
70 / 57  
85 / 72  
80 / 67  
75 / 62  
70 / 57  
85 / 72  
80 / 67  
75 / 62  
70 / 57  
85 / 72  
80 / 67  
75 / 62  
70 / 57  
41.5  
36.2  
29.1  
24.1  
52.0  
41.7  
32.5  
27.9  
46.8  
37.4  
28.9  
25.1  
53.7  
43.0  
33.1  
28.8  
91.7  
73.4  
57.3  
49.2  
88.4  
70.8  
55.2  
47.4  
100.5  
80.4  
62.7  
53.9  
119.9  
96.0  
74.0  
64.3  
124.8  
99.9  
77  
37.8  
32.4  
25.3  
21.5  
47.3  
36.8  
27.3  
25.8  
42.4  
33.3  
24.6  
23.3  
48.4  
38.0  
28.1  
26.5  
78.4  
61.5  
45.6  
43.0  
76.0  
59.4  
43.9  
41.5  
86.4  
67.5  
49.9  
47.2  
101.0  
79.2  
58.6  
55.4  
105.2  
82.5  
61.1  
57.7  
110.5  
86.6  
64.2  
60.6  
33.7  
28.6  
24.0  
18.7  
42.3  
32.3  
29.8  
23.8  
37.6  
29.4  
21.7  
21.7  
43.5  
33.3  
24.5  
24.5  
68.1  
52.0  
38.4  
38.4  
63.3  
48.4  
35.8  
35.8  
72.0  
55.0  
40.7  
40.7  
80.0  
62.6  
46.2  
46.2  
85.3  
65.2  
48.1  
48.1  
89.6  
68.5  
50.5  
50.5  
29.5  
24.5  
19.2  
15.8  
37.3  
27.4  
22.2  
22.2  
33.0  
24.3  
19.6  
19.6  
37.5  
27.7  
22.4  
22.4  
52.3  
38.6  
31.2  
31.2  
50.0  
37.0  
29.9  
29.9  
56.8  
42.1  
34.0  
34.0  
62.2  
45.8  
37.0  
37  
MC30B**H  
MC36B**H  
MC48D**H  
MC60D**H  
MC61D**H  
MC42C**H  
MC48C**H  
MC48D**H  
MC60D**H  
MC61D**H  
1025  
1250  
1125  
1275  
1450  
1400  
1650  
1725  
2000  
2200  
MV12B  
MV12D  
MV16C  
MV20D  
64.7  
47.7  
38.6  
38.6  
67.9  
50.1  
40.5  
40.5  
66.9  
131.0  
104.9  
81.8  
70.2  
Unitary Products Group  
3
255427-YTG-F-1006  
PHYSICAL & ELECTRICAL DATA  
Model  
MV12B  
10 x 7  
1/2  
MV12D  
10 x 10  
1/2  
MV16C  
10 x 10  
3/4  
MV20D  
10 x 10  
1
Blower - Diameter x Width  
HP  
Motor  
Nominal RPM  
1200  
1200  
1200  
1200  
Voltage  
208/230  
Amps  
Full Load (230)  
Type  
4.3  
4.3  
5.0  
7.0  
DISPOSABLE OR PERMANENT  
Filter  
Size  
16 x 20 x 1  
1PF0601BK  
1FR0717  
68 / 62  
22 x 20 x 1  
1PF0603BK  
1FR0724  
88 / 82  
20 x 20 x 1  
1PF0602BK  
1FR0721  
75 / 69  
22 x 20 x 1  
1PF0603BK  
1FR0724  
93 / 87  
Permanent Type Kit  
Filter Rack  
Shipping / Operating Weight (lbs.)  
COILS  
Refrig.  
Application Conn.  
Types  
Face  
Fin  
Per  
In.  
Operating  
Weight  
(Lbs.)  
Rows  
Deep  
Tube  
Geometry  
Tube  
Dia.  
Fin  
Type  
Model  
Area  
Coil Size  
TXV  
(Sq. Ft.)  
MC18A3XH1  
MC18A2AH1  
MC18B3XH1  
MC18B2AH1  
MC24A3XH1  
MC24A2AH1  
MC24B3XH1  
MC24B2AH1  
MC30A3XH1  
MC30A2AH1  
MC30B3XH1  
MC30B2AH1  
MC35B3XH1  
MC35C3XH1  
MC36A3XH1  
MC36A2AH1  
MC36B3XH1  
MC36B2AH1  
MC36C3XH1  
MC36C2AH1  
MC42B3XH1  
MC42B2CH1  
MC42C3XH1  
MC42C2CH1  
MC48C3XH1  
MC48C2CH1  
MC48D3XH1  
MC48D2CH1  
MC60D3XH1  
MC60D2CH1  
MC61D3XH1  
MC61D2CH1  
None  
2A  
3.40  
3.40  
4.38  
4.38  
4.38  
4.38  
3.90  
4.86  
4.86  
4.86  
5.83  
5.83  
5.35  
5.35  
5.83  
6.80  
2
14  
14  
14  
14  
14  
14  
12  
14  
14  
14  
14  
14  
12  
12  
12  
12  
(2) 14 x 17.5  
(2) 14 x 17.5  
(2) 18 x 17.5  
(2) 18 x 17.5  
(2) 18 x 17.5  
(2) 18 x 17.5  
(2) 16 x 17.5  
(2) 20 x 17.5  
(2) 20 x 17.5  
(2) 20 x 17.5  
(2) 24 x 17.5  
(2) 24 x 17.5  
(2) 22 x 17.5  
(2) 22 x 17.5  
(2) 24 x 17.5  
(2) 28 x 17.5  
53  
53  
56  
56  
56  
56  
65  
64  
65  
65  
72  
72  
82  
82  
86  
98  
None  
2A  
2
2
2
2
2
3
2
2
2
2
2
3
3
3
3
None  
2A  
None  
2A  
None  
2A  
None  
2A  
None  
None  
None  
2A  
Cooling /  
Sweat  
1 x 0.866  
3/8  
Enhanced  
Heat Pump  
None  
2A  
None  
2A  
None  
2C  
None  
2C  
None  
2C  
None  
2C  
None  
2C  
None  
2C  
4
Unitary Products Group  
255427-YTG-F-1006  
ELECTRICAL DATA - 208/230-1-60  
Max.  
Total Heat1  
MBH  
208V 240V 208V 240V  
KW Staging  
W2 Only  
Min.  
Speed  
Tap  
Model  
Heater Model*  
KW  
W1 Only  
208V  
W1 + W2  
208V 240V  
Static  
240V  
4.8  
3.75  
4.8  
4.8  
4.8  
3.75  
4.8  
4.8  
4.4  
4.8  
4.8  
3.75  
4.8  
4.8  
4.4  
4.8  
4.8  
4.8  
4.4  
4.8  
4.8  
208V  
3.6  
5.6  
7.2  
7.2  
3.6  
5.6  
7.2  
7.2  
6.6  
7.2  
3.6  
5.6  
7.2  
7.2  
6.6  
7.2  
7.2  
7.2  
6.6  
7.2  
10.8  
240V  
4HK*6500506  
4HK*6500806  
4HK*6501006  
4HK165N1506  
4HK*6500506  
4HK*6500806  
4HK*6501006  
4HK16501506  
4HK16501806  
4HK16502006  
4HK*6500506  
4HK*6500806  
4HK*6501006  
4HK16501506  
4HK16501806  
4HK16502006  
4HK*6501006  
4HK16501506  
4HK16501806  
4HK16502006  
4HK16502506  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
Heat-D  
3.6  
5.6  
7.2  
4.8  
7.5  
9.6  
12.3  
19.2  
24.6  
16.4  
25.6  
32.8  
49.1  
16.4  
25.6  
32.8  
49.1  
60.1  
65.5  
16.4  
25.6  
32.8  
49.1  
60.1  
65.5  
32.8  
49.1  
60.1  
65.5  
81.9  
3.6  
2.8  
3.6  
3.6  
3.6  
2.8  
3.6  
3.6  
3.3  
3.6  
3.6  
2.8  
3.6  
3.6  
3.3  
3.6  
3.6  
3.6  
3.3  
3.6  
3.6  
4.8  
7.5  
9.6  
9.6  
4.8  
7.5  
9.6  
9.6  
8.8  
9.6  
4.8  
7.5  
9.6  
9.6  
8.8  
9.6  
9.6  
9.6  
8.8  
9.6  
14.4  
3.6  
5.6  
4.8  
7.5  
MV12B  
7.2  
9.6  
10.8 14.4 36.9  
10.8  
3.6  
14.4  
4.8  
3.6  
5.6  
7.2  
4.8  
7.5  
9.6  
12.3  
19.2  
24.6  
5.6  
7.5  
7.2  
9.6  
MV12D  
10.8 14.4 36.9  
13.2 17.6 45.1  
14.4 19.2 49.2  
10.8  
13.2  
14.4  
3.6  
14.4  
17.6  
19.2  
4.8  
3.6  
5.6  
7.2  
4.8  
7.5  
9.6  
12.3  
19.2  
24.6  
5.6  
7.5  
7.2  
9.6  
MV16C  
MV20D  
10.8 14.4 36.9  
13.2 17.6 45.1  
14.4 19.2 49.2  
10.8  
13.2  
14.4  
7.2  
14.4  
17.6  
19.2  
9.6  
7.2  
9.6  
24.6  
10.8 14.4 36.9  
13.2 17.6 45.1  
14.4 19.2 49.2  
18.0 24.0 61.5  
10.8  
13.2  
14.4  
18.0  
14.4  
17.6  
19.2  
24  
1. See conversion table on Page 7.  
May be 0 (no breaker) or 1 (with breaker).  
*
ELECTRICAL DATA - 208/230-3-60  
Total Heat1  
MBH  
KW Staging  
W2 Only  
Min.  
Speed  
Tap  
Heat Kit -  
Models  
Max.  
Static  
KW  
W1 Only  
W1 + W2  
Three Phase  
208V 240V 208V 240V 208V 240V 208V 240V 208V 240V  
MV12BN21  
MV12DN21  
4HK06501025  
4HK06501025  
4HK06501525  
4HK06501825  
4HK06501025  
4HK06501525  
4HK06501825  
4HK06501025  
4HK06501525  
4HK16502525  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
Heat-D  
Heat-D  
7.2  
7.2  
9.6  
9.6  
24.6  
24.6  
36.9  
44.7  
24.6  
36.9  
44.7  
24.6  
36.9  
61.4  
32.8  
32.8  
49.1  
58.7  
32.8  
49.1  
58.7  
32.8  
49.1  
81.4  
7.2  
7.2  
9.6  
9.6  
7.2  
7.2  
9.6  
9.6  
7.2  
7.2  
9.6  
9.6  
Heat-D 10.8  
Heat-D 12.9  
14.4  
17.2  
9.6  
10.8  
12.9  
7.2  
14.4  
17.2  
9.6  
10.8  
12.9  
7.2  
14.4  
17.2  
9.6  
10.8  
12.9  
7.2  
14.4  
17.2  
9.6  
Heat-D  
7.2  
MV16CN21  
MV20DN21  
Heat-D 10.8  
Heat-D 12.9  
14.4  
17.2  
9.6  
10.8  
12.9  
7.2  
14.4  
17.2  
9.6  
10.8  
12.9  
7.2  
14.4  
17.2  
9.6  
10.8  
12.9  
7.2  
14.4  
17.2  
9.6  
Heat-D  
7.2  
Heat-D 10.8  
Heat-D 18.0  
14.4  
24.0  
10.8  
9.0  
14.4  
12.0  
10.8  
18.0  
14.4  
24.0  
10.8  
18.0  
14.4  
24.0  
1. See conversion table on Page 7.  
Unitary Products Group  
5
255427-YTG-F-1006  
ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60  
Field Wiring  
Heater Model1,*  
Max. O.C.P.2 Amps/Type  
Model  
Heater Amps  
240V  
20.0  
Ampacity Min. Circuit  
Wire Size - AWG 75°C  
208V  
27.54  
39.73  
49.21  
70.88  
27.54  
39.73  
49.21  
70.88  
85.32  
92.54  
29.29  
41.48  
50.96  
72.63  
87.07  
94.29  
53.08  
74.75  
89.19  
96.42  
118.08  
240V  
30.38  
44.50  
55.38  
80.38  
30.38  
44.50  
55.38  
80.38  
97.00  
105.38  
31.88  
46.00  
56.88  
81.88  
98.50  
106.88  
58.75  
83.75  
100.38  
108.75  
133.75  
208V  
30  
240V  
35  
208V  
10  
8
240V  
8
4HK*6500506  
4HK*6500806  
4HK*6501006  
4HK165N1506  
4HK*6500506  
4HK*6500806  
4HK*6501006  
4HK16501506  
4HK16501806  
4HK16502006  
4HK*6500506  
4HK*6500806  
4HK*6501006  
4HK16501506  
4HK16501806  
4HK16502006  
4HK*6501006  
4HK16501506  
4HK16501806  
4HK16502006  
4HK16502506  
31.3  
40  
45  
8
MV12B  
40.0  
50  
60  
8
6
60.0  
90  
90  
4
3
20.0  
30  
35  
10  
8
8
31.3  
40  
45  
8
40.0  
50  
60  
8
6
MV12D  
60.0  
90  
90  
4
3
73.3  
90  
100  
125  
35  
4
3
80.0  
100  
30  
3
1
20.0  
10  
8
8
31.3  
45  
50  
8
40.0  
60  
60  
6
6
MV16C  
MV20D  
60.0  
90  
90  
3
3
73.3  
90  
100  
125  
60  
3
2
80.0  
100  
60  
3
1
40.0  
6
6
60.0  
90  
90  
3
3
73.3  
90  
110  
125  
150  
3
2
80.0  
100  
125  
3
1
100.0  
1
1/0  
1. 30 KW 3 phase not approved for single source power supply.  
2. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.  
* May be 0 (no breaker) or 1 (with breaker).  
ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60  
Field Wiring  
Heater  
Amps  
240V  
Heat Kit -  
Three Phase  
Max. O.C.P.1 Amps/Type  
Models  
Min. Circuit Ampacity  
75°C Wire Size - AWG  
208V  
30.9  
30.9  
43.4  
50.6  
32.6  
45.1  
52.4  
34.8  
47.3  
240V  
34.3  
34.3  
48.8  
57.1  
35.1  
49.6  
58.0  
37.6  
52.1  
208V  
35  
240V  
35  
208V  
240V  
12B  
12D  
4HK06501025  
4HK06501025  
4HK06501525  
4HK06501825  
4HK06501025  
4HK06501525  
4HK06501825  
4HK06501025  
4HK06501525  
23.1  
23.1  
34.7  
41.4  
23.1  
34.7  
41.4  
23.1  
34.7  
8
8
8
8
8
8
6
8
8
8
8
8
6
8
8
6
8
6
35  
35  
45  
50  
50  
60  
35  
35  
16C  
20D  
45  
50  
60  
60  
35  
40  
50  
60  
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.  
TABLE 1: Electrical Data - (For Multi-Source Power Supply) - Copper Wire - 208/230-3-60  
Max. O.C.P.1 Amps/Type  
Minimum Circuit Ampacity  
75°C Wire Size - AWG  
Heater  
Model  
Circuit  
2nd  
208/240 208/240 208/240 208/240 208/240 208/240 208/240  
- / - 45 / 45 35 / 40 - / - 8 / 8 8 / 8 - / -  
Models  
1st  
2nd  
3rd  
1st  
3rd  
1st  
2nd  
3rd  
208/240  
41.0 / 44.9  
208/240  
31.3 / 36.1  
20D  
4HK16502525  
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.  
6
Unitary Products Group  
255427-YTG-F-1006  
ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60  
1
Min. Circuit Ampacity  
75°C Wire Size - AWG  
Max. O.C.P. Amps/Type  
Circuit  
Circuit  
Circuit  
Heater  
Model  
Model  
1st  
208/240  
2nd  
3rd  
1st  
2nd  
3rd  
1st  
2nd  
3rd  
208/240  
208/240  
208/240  
50 / 60  
50 / 60  
50 / 60  
50 / 60  
50 / 60  
50 / 60  
50 / 60  
60 / 60  
50 / 60  
60 / 60  
50 / 60  
208/240  
25 / 25  
25 / 25  
40 / 50  
45 / 50  
25 / 25  
40 / 50  
45 / 50  
25 / 25  
40 / 50  
45 / 50  
45 / 50  
208/240  
208/240  
8 / 6  
8 / 6  
8 / 6  
8 / 6  
8 / 6  
8 / 6  
8 / 6  
6 / 6  
8 / 6  
6 / 6  
8 / 6  
208/240  
10 / 10  
10 / 10  
8 / 8  
208/240  
MV12B  
MV12D  
4HK165N1506 49.2 / 55.4 21.7 / 25.0  
4HK16501506 49.2 / 55.4 21.7 / 25.0  
4HK16501806 45.6 / 51.2 39.7 / 45.8  
4HK16502006 49.2 / 55.4 43.3 / 50.0  
4HK16501506 51.0 / 56.9 21.7 / 25.0  
4HK16501806 17.3 / 52.7 39.7 / 45.8  
4HK16502006 51.0 / 56.9 43.3 / 50.0  
4HK16501506 53.1 / 58.8 21.7 / 25.0  
4HK16501806 49.5 / 54.6 39.7 / 45.8  
4HK16502006 53.1 / 58.8 43.3 / 50.0  
8 / 8  
10 / 10  
8 / 8  
MV16C  
MV20D  
8 / 8  
10 / 10  
8 / 8  
8 / 8  
4HK16502506 49.3 / 56.5 43.3 / 50.0 21.7 / 25.0  
25 / 25  
8 / 8  
10 / 10  
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.  
KW & MBH CONVERSIONS  
208-VOLT  
230-VOLT  
240-VOLT  
240-VOLT  
.751  
.918  
FOR  
OPERATION MULTIPLY  
TABULATED KW & MBH BY  
ELECTRICAL DATA - COOLING UNIT ONLY (60 Hz)  
Total Motor Amps  
60 Hertz  
Minimum Circuit Ampacity  
60 Hertz  
Minimum Wire Size  
AWG @ 75°C  
Max. O.C.P.1 Amps/Type  
MODEL  
208V  
4.7  
230V  
4.3  
208V  
5.9  
230V  
5.4  
MV12B  
MV12D  
MV16C  
MV20D  
15  
15  
15  
15  
14  
14  
14  
14  
4.7  
4.3  
5.9  
5.4  
6.1  
5.0  
7.6  
6.9  
7.8  
7.0  
9.7  
8.8  
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.  
POWER WIRING  
ELECTRIC HEAT  
WITHOUT CIRCUIT BREAKER  
3 PHASE (10 - 15 KW)  
1 PHASE ELECTRIC HEAT  
TYPICAL WIRING WITHOUT ELECTRIC HEAT  
GND.  
LUG  
WITH CIRCUIT BREAKER  
AS SHIPPED FROM FACTORY  
SINGLE SOURCE  
GND. LUG  
GND.  
LUG  
GND. LUG  
(2.5 - 25 KW) - 25 KW SHOWN  
POWER  
SUPPLY  
GND. LUG  
GND.  
LUG  
POWER  
SUPPLY  
1 PHASE ELECTRIC HEAT  
WITH CIRCUIT BREAKER  
& BREAKER BAR REMOVED  
TERMINAL  
BLOCK  
ELECTRIC HEAT  
WITHOUT CIRCUIT BREAKER  
SINGLE SOURCE (2.5 - 10 KW)  
MULTI-SOURCE (15 - 25 KW) - 25 KW SHOWN  
GND. LUG  
POWER  
SUPPLY  
GND.  
LUG  
GND.  
LUG  
GND. LUG  
(JUMPER BAR)  
POWER  
SUPPLY 1  
MAY BE 1, 2, OR 3  
CIRCUIT BREAKERS  
POWER  
SUPPLY 2  
POWER  
SUPPLY  
POWER  
SUPPLY 3  
POWER WIRING (208/230-1-60)  
TERMINAL  
BLOCK  
NOTE: USE ONLY COPPER CONDUCTORS  
MAY BE 1, 2, OR 3  
CIRCUIT BREAKERS  
CONNECT LEADS WITH WIRE NUTS  
(TYPICAL ALL HEAT KITS)  
Line Power  
Unitary Products Group  
7
255427-YTG-F-1006  
Filter Rack - One of the following external filter rack accesso-  
ries: 1FR07* or 1FR08* must be used when unit is installed  
for application outlined.  
ACCESSORIES  
Refer to Price Manual for specific model numbers.  
Electric Heaters - Models shown under Electrical Data  
include sequencers and temperature limit switches and fus-  
ible links for safe, efficient operation. Circuit breakers are pro-  
vided where shown.  
Combustible Floor Base - If an electric heat accessory  
which is rated for greater than zero clearance to combustible  
surfaces is installed in these air handlers in the downflow  
operating positions on a combustible floor, one of the follow-  
ing combustible floor base accessories is required: 1FB1817,  
1FB1821, or 1FB1824.  
Suspension Kit - Suspension Kit Model 1BH0601 is  
designed specifically for upflow application of the units con-  
tained in this technical guide. For suspension of these units in  
horizontal applications, it is recommended to use angle sup-  
port brackets with threaded rods at locations shown in air  
handler installation instructions.  
1/2”  
3/4”  
1/2”  
1-1/2”  
2” Max  
Thick  
Filter  
1”  
3-1/2”  
C
D
7/8”  
1/2”  
19-7/8”  
3-1/2”  
B
1/2”  
(All four sides)  
NOTE: May be used with up to a 2” filter.  
Required for downflow application.  
May also be used in upflow application.  
22”  
A
16-1/2”  
20”  
23-1/2”  
21”  
22”  
All dimensions are inches. They are subject to change  
without notice. Certified dimensions will be provided upon  
request.  
A
ACCESSORY FOOTPRINT  
FILTER RACK ACCESSORY  
Filter Rack Model  
Rack Dimensions Inches  
Filter Dimensions Inches  
Used With  
Multi-Position Horizontal Only  
A
B
C
D
Width  
17-1/2  
21  
Length  
22  
Thickness  
1FR0817  
1FR0821  
1FR0824  
1FR0717  
1FR0721  
1FR0724  
MV12B  
MV16C  
17-1/2  
21  
16-3/8  
19-7/8  
23-3/8  
15-1/2  
19  
21  
21  
21  
1
1
1
22  
MV12D, MV20D  
24-1/2  
22-1/2  
24-1/2  
22  
8
Unitary Products Group  
255427-YTG-F-1006  
AIR HANDLER  
DEPTH  
FRONT  
DOWNFLOW  
AIR HANDLER  
FLOOR  
APPROX. 1/2”  
CLEARANCE  
ALL AROUND  
10-47/64  
PLENUM  
WARM AIR PLENUM  
WITH 1” FLANGES  
1
12-1/2  
FLOOR OPENING  
B
A
FIBERGLASS  
INSULATION  
FIBERGLASS TAPE  
UNDER FLANGE  
A
AIR HANDLER  
WIDTH  
B
A
COMBUSTIBLE  
FLOOR BASE  
FLOOR  
COMBUSTIBLE FLOOR  
BASE ACCESSORY  
B
PLENUM  
APPROX. 1/2”  
CLEARANCE  
ALL AROUND  
1
1
C
FLOOR OPENING  
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.  
COMBUSTIBLE FLOOR BASE ACCESSORY  
Dimensions  
Floor Base Model  
Used with  
A
B
C
D
1FB1817  
1FB1821  
1FB1824  
MV12B  
MV16C  
19.9  
23.4  
26.9  
18.0  
21.5  
25.0  
14.9  
18.4  
21.9  
16.9  
20.4  
23.9  
MV12D, MV20D  
Unitary Products Group  
9
255427-YTG-F-1006  
COOLING AIRFLOW DATA - MV MODELS  
HIGH / LOW SPEED COOLING AND HEAT PUMP CFM  
12D Air Handler  
12B Air Handler  
JUMPER SETTINGS  
m3/min  
m3/min  
CFM  
CFM  
High  
1307  
1080  
1270  
943  
Low  
882  
756  
862  
689  
786  
726  
632  
594  
668  
565  
624  
567  
High  
Low  
25.0  
21.4  
24.4  
19.5  
22.3  
20.6  
17.9  
16.8  
18.9  
16.0  
17.7  
16.1  
High  
1366  
1097  
1312  
957  
Low  
869  
717  
856  
646  
761  
703  
580  
520  
629  
495  
567  
488  
High  
38.7  
31.1  
37.2  
27.1  
33.0  
29.8  
24.4  
20.9  
26.2  
18.6  
23.5  
16.8  
Low  
24.6  
20.3  
24.2  
18.3  
21.5  
19.9  
16.4  
14.7  
17.8  
14.0  
16.1  
13.8  
COOL Tap  
ADJ Tap*  
37.0  
30.6  
36.0  
26.7  
32.5  
29.7  
24.6  
21.8  
26.4  
19.6  
24.1  
18.5  
A
B
A
B
A
C
B
D
C
D
C
D
B
B
A
A
C
B
C
B
A
A
C
C
1146  
1050  
870  
1167  
1051  
863  
771  
739  
931  
927  
693  
658  
851  
830  
655  
594  
16C Air Handler  
20D Air Handler  
JUMPER SETTINGS  
m3/min  
m3/min  
CFM  
CFM  
High  
1920  
1699  
1884  
1558  
1714  
1451  
1403  
1288  
1336  
1214  
1239  
1098  
Low  
1321  
1189  
1296  
1094  
1193  
1037  
1009  
947  
High  
Low  
37.4  
33.7  
36.7  
31.0  
33.8  
29.4  
28.6  
26.8  
27.7  
25.1  
25.9  
23.8  
High  
2209  
2022  
2178  
1798  
1965  
1843  
1596  
1700  
1608  
1493  
1430  
1334  
Low  
1394  
1394  
1381  
1378  
1226  
1143  
1226  
1066  
1023  
967  
High  
62.6  
57.3  
61.7  
50.9  
55.6  
52.2  
45.2  
48.1  
45.5  
42.3  
40.5  
37.8  
Low  
39.5  
39.5  
39.1  
39.0  
34.7  
32.4  
34.7  
30.2  
29.0  
27.4  
25.8  
24.8  
COOL Tap  
ADJ Tap*  
54.4  
48.1  
53.3  
44.1  
48.5  
41.1  
39.7  
36.5  
37.8  
34.4  
35.1  
31.1  
A
B
A
B
A
C
B
D
C
D
C
D
B
B
A
A
C
B
C
B
A
A
C
C
978  
888  
915  
911  
839  
877  
All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to  
0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c.  
external static pressure is not recommended.  
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air  
cleaners. Consult the instructions for the electronic air cleaner for further details.  
* The ADJ “D” tap should not be used.  
HEATING AIRFLOW DATA - MV MODELS  
HIGH / LOW SPEED COOLING AND HEAT PUMP CFM  
12B Air Handler  
12D Air Handler  
JUMPER SETTINGS  
m3/min  
m3/min  
CFM  
CFM  
CFM  
CFM  
High  
1270  
943  
Low  
791  
714  
643  
567  
High  
Low  
22.4  
20.2  
18.2  
16.1  
High  
1312  
957  
Low  
762  
668  
591  
488  
High  
37.2  
27.1  
26.2  
18.6  
Low  
21.6  
18.9  
16.7  
13.8  
COOL Tap  
ADJ Tap*  
36.0  
26.7  
26.4  
19.6  
A
B
C
D
A
A
A
A
931  
927  
693  
658  
16C Air Handler  
20D Air Handler  
JUMPER SETTINGS  
m3/min  
m3/min  
High  
1884  
1558  
1336  
1214  
Low  
1217  
1065  
823  
High  
Low  
34.5  
30.2  
23.3  
20.6  
High  
2178  
1798  
1608  
1493  
Low  
1217  
1036  
748  
High  
61.7  
50.9  
45.5  
42.3  
Low  
34.5  
29.3  
21.2  
15.6  
COOL Tap  
ADJ Tap*  
53.3  
44.1  
37.8  
34.4  
A
B
C
D
A
A
A
A
727  
551  
All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to  
0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c.  
external static pressure is not recommended.  
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air  
cleaners. Consult the instructions for the electronic air cleaner for further details.  
* The ADJ “D” tap should not be used.  
10  
Unitary Products Group  
255427-YTG-F-1006  
APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM  
% OF RATED AIR FLOW  
CAPACITY FACTOR  
80%  
0.96  
90%  
0.98  
RATED CFM  
1.00  
110%  
1.02  
120%  
1.03  
Horizontal Right  
Horizontal Left  
Up Flow  
Down Flow  
Typical Applications with MC Multi-Position Coils  
MA SERIES - Air Handler Control Wiring  
Typical A/C - Cooling only Applications  
MA SERIES - Air Handler Control Wiring  
Typical A/C with Electric Heat Applications  
AIR HANDLER  
BOARD  
AIR HANDLER  
THERMOSTAT  
1 - STAGE  
BOARD  
THERMOSTAT  
1 - STAGE  
AIR CONDITIONING  
AIR CONDITIONING  
R
G
R
G
R
G
Y
R
G
Y
Y / Y2  
Y
Y / Y2  
Y
W1  
W2  
C
Y1  
Y1  
W2  
W2  
W2  
*
*
W1  
O
W1  
O
HUMIDISTAT  
HUMIDISTAT  
W1  
C
HUM  
X / L  
COM  
HUM  
X / L  
COM  
C
C
COOLING MODELS WITH ELECTRIC HEAT  
CONTROL WIRING - MA Series - Air Handler & New UPG HP Systems  
Two Stage H/P with York Guard VI Board & Copeland “Ultra Tech”  
Conventional Application - Not Hot Heat Pump  
2 - STAGE SCROLL  
HEAT PUMP  
AIR HANDLER  
BOARD  
THERMOSTAT  
R
G
R
G
R
Y2  
Y2  
Y / Y2  
Y1  
Y2 OUT  
Y1  
Y1  
W2 OUT  
W2  
W1  
E
W1 OUT  
W
O
W
O
O
*
HUMIDISTAT  
HUM  
X / L  
BS  
X / L  
C
X / L  
C
COM  
CONTROL WIRING - MV SERIES  
Unitary Products Group  
11  
NOTES  
Subject to change without notice. Printed in U.S.A.  
255427-YTG-F-1006  
Copyright © by York International/JCI. 2006. All rights reserved.  
Supersedes: 255427-YTG-E-0906  
Unitary  
Products  
Group  
5005  
York  
Drive  
Norman  
OK  
73069  

Sharp Mx Amx1 User Manual
Samsung Scx 5530fn User Manual
Samsung As24hpbx User Manual
Lindy 38022 User Manual
LG LRE30453S User Manual
HP CP6015N User Manual
DENON DP 300F User Manual
CRAFTSMAN 315.216360 User Manual
BROTHER HL 2400CE 02 User Manual
ACER ASPIRE 5 A515 53G User Manual