FORM 100.50-EG1 (201)
Packaged Rooftop
Air Conditioning Units
00406VIP
R-407C OPTIMIZED
50 THROUGH 65 TONS
FORM 100.50-EG1
PAGE
FIGURES
1
2
3
4
5
6
7
8
Packaged Rooftop Air Conditioning Unit .................................................. 4
Single-Point Power Supply Wiring .......................................................... 31
Single-Point Power Supply Wiring with Non-Fused Disconnect ............. 32
Dual-Point Power Supply Wiring ............................................................ 33
Field Control Wiring ............................................................................... 34
General Arrangement Drawing – Bottom Return, Bottom Supply ........... 35
General Arrangement Drawing – Rear Return, Left or Right Supply ...... 36
Curb Layout Drawing.............................................................................. 37
NOMENCLATURE
BASIC MODEL NUMBER
1 2 3 4
BASE PRODUCT TYPE
5 6 7
NOMINAL CAPACITY
8 9
10
11 12
13 14
DUCT LOCATIONS
15 16
DESIGN SPECIAL
APPLICATION REFRIGERANT VOLTAGE
Y
0
0
0
0
5
5
6
6
0: 50-ton
5: 55-ton
0: 60-ton
5: 65-ton
B : R-407C
1
2
4
5
7
8
6
8
B
L
R
A
: 200 / 3 / 60
: 230 / 3 / 60
: 460 / 3 / 60
: 575 / 3 / 60
: Rev. Level A
: Std. Product
: Special
: YORK
: Packaged
Rooftop
: Air-Cooled
: Bottom Supply
: Left Supply
: Right Supply
: Bottom Return
: Front Return
: Side Return
P
S
X
A
B
F
S
L
: Scroll
: Cooling Only
C
: Constant Volume
: VAV, VFD
: VAV, VFD w/ Manual Bypass
C
V
B
YORK INTERNATIONAL
3
Introduction
00406VIP
FIG. 1 – PACKAGED ROOFTOP AIR CONDITIONING UNIT
FEATURES/BENEFITS
in two directions conforming to ASHRAE 62n, this
drain pan swiftly minimizes any condensate within
the unit. Best of all, the drain pan is accessible for
periodic cleaning required by IAQ standards.
Ecological and Economical Design
• First packaged RTU with 407C optimized design
• Smart ventilation – YORK maintains the leader-
ship role in IAQ products with adaptive ventilation
control. The OptiLogicTM controls provide continu-
ous monitoring of air quality and take action by open-
ing the outside air dampers, bringing in the right
amount of fresh air before air impurities reach un-
comfortable or even dangerous levels.
• Cooling and Heating – Superior operating perfor-
mance provides lower operating costs. Smaller
steps of cooling capacity provide tighter control of
building environment and occupant comfort while
optimizing energy efficiency.
• Indoor Air Quality (IAQ) – Outside air economiz-
ers provide energy savings in free cooling mode,
and can provide a healthier and more comfortable
building environment by introducing fresh outside air
into the building as needed. Indoor Air Quality (IAQ)
requirements for building ventilation and comfort are
controlled through the microprocessor control panel.
Optional air flow measurement provides an accu-
rate means of tracking air quality and alerting the
occupants or building owner to unhealthy situations.
• Air flow measurement – Precise measurement
of ventilation air flow is possible using an air flow
measurement station which can be installed in the
economizer section. Proper ventilation air flow is
required to ensure sufficient fresh air is in the build-
ing. A myriad of air flow measurement options are
available from minimum air flow to high-accuracy
full air flow capabilities. The complete system is
designed as an integrated component of the
OptiLogicTM control system to ensure optimum sys-
tem performance.
• High-Efficiency Motors – High-efficiency motors are
available for optimum energy efficiency. All motors
used on the eco2 packaged rooftop air conditioner
meet U.S. EPACT 1992 minimum requirements.
• Double-wall construction – Rigid double-wall
construction throughout provides ease of clean-
ing and protects against insulation fiber entrain-
ment in the breathable air. Double-wall construc-
tion also helps improve the acoustical character-
istics of the air handling unit.
Indoor Air Quality (IAQ)
• Double-sloped stainless steel drain pan – This
double-sloped inclined stainless steel drain pan fa-
cilitates removal of evaporator condensate. Sloped
YORK INTERNATIONAL
4
FORM 100.50-EG1
• Enhanced filtration – The Eco2 unit gives design-
ers the flexibility to meet various IAQ requirements
with a full range of rigid and throwaway filters at
various efficiency levels.
Serviceability
• OptiLogicTM – fully-integrated factory-packaged
controls are standard on every unit and include a
display unit with a 4x20 character LCD display.
OptiLogicTM continually monitors all control setpoints
and configurations. If a unit or control component,
or sensor fails, the controller notifies the user of a
problem. If desired, YORK service can provide re-
mote monitoring and automatically schedule a ser-
vice technician to make the repair and maintain your
comfort.
Reliable Scroll Compressor Technology
Reliable, efficient, trouble-free operation is the true mea-
sure of a packaged rooftop’s value. That’s why YORK
Eco2 Packaged Rooftop Air Conditioners use estab-
lished scroll-compressor technology to deliver depend-
able, economical performance in a wide range of appli-
cations. With the Eco2 Packaged Rooftop, you get the
latest generation of compressor enhancements added
to the scroll’s inherent strengths. The simplicity of a
hermetic scroll compressor allows the use of fewer
moving parts to minimize breakdown. YORK also em-
ploys the latest sealing technology to avoid metal-to-
metal contact. Axial sealing is accomplished with float-
ing tip seals, while radial sealing utilizes a microcushion
of oil. The result: a maintenance-free compressor pro-
viding minimum wear and maximum runtime.
• Access doors – full-sized access doors provide
easy access into the unit for routine maintenance
and inspection.
• Suction & discharge service valves – oversized
service valves to provide isolation and quick recla-
mation and charging of system refrigerant are avail-
able to minimize downtime and simplify the service
and repair task.
• VFD Fan Motor Control with Manual Bypass –
Optional manual VFD bypass reduces time required
for troubleshooting, commissioning and system
balancing.
A scroll compressor operates with two scroll members—
a fixed scroll and an identical orbiting scroll turned 180
degrees, like two hands curled and interlocked together.
As the orbiting scroll oscillates against the fixed scroll,
it traps and compresses suction gas inside involute
pockets. As the orbiting scroll moves, the gas is com-
pressed into the central area, where it is discharged as
compressed gas. High efficiency is achieved through a
precisely controlled orbit and the use of advanced scroll
geometry. There is no wasted motion. All rotating parts
are statically and dynamically balanced to ensure opti-
mal performance over the long haul.
• Convenience Outlet – for maintenance tasks re-
quiring power tools, an optional 110V GFCI power
supply can power lights, drills or any other power
hand tool needed.
• Filter Maintenance Alarm – An optional filter main-
tenance alarm indicates when a filter becomes dirty
and requires replacement or cleaning.
Install with Ease and Safety
Balanced components and precision machining also
ensure that smooth compression occurs in all involute
pockets simultaneously. When compression forces are
equally distributed over the entire scroll surface, equal
forces in opposing directions cancel one another, mini-
mizing any imbalance. Consequently, compression is
smooth, continuous, and quiet. Vibration isolators on
each compressor handle normal vibration. For extra
quiet operation, acoustic sound blankets for each com-
pressor are available as options.
• Factory run-tested – Each unit is subjected to a
series of quality assurance checks as well as an
automated quality control process before being run-
tested. Fans and drives are balanced at the factory
during testing. The factory run-test ensures safe,
proper operation when the unit is installed and re-
duces installation and commissioning time.
• Single-point power connection – Single-point
power connection reduces installation time by pro-
viding a single point for incoming power, including
YORK INTERNATIONAL
5
Introduction
the optional convenience outlet. All incoming power
is connected in one location, reducing the cost of
field-supplied and installed power wiring.
on all systems offering higher rooftop cooling ca-
pacity than competitive units.
• Hot Gas Bypass –Optional on constant volume units,
hot gas bypass reduces the cycling of compressors
which helps prolong the life of the equipment.
• Factory-mounted and wired controls – All con-
trol points within the unit are factory-installed, wired
and tested. The OptiLogicTM controls can commu-
nicate with BACNet IP.
• Supply Air Openings – Side supply connections
are available on select configurations, offering more
flexibility for duct layout and improving sound trans-
mission characteristics.
• Non-fused disconnect – A factory-installed non-
fused disconnect switch simplifies unit installation
and serviceability by reducing installed labor costs.
The disconnect switch is interlocked with the power
cabinet ensuring that all power to the unit has been
disconnected before servicing.
• Compressor Sound Blankets – For applications
in sound-sensitive areas, compressor sound blan-
kets are available to reduce sound emitted from
the rooftop unit.
• Fan Spring Isolators – One-inch spring isolation
is used to prevent vibration transmission from the
rooftop unit’s supply fan to the building. Two-inch
spring isolation is also available.
Design Flexibility
• Low Ambient Operation – Head-pressure control
is accomplished via a VFD motor controller rather
than an inefficient and noisy condenser fan damper.
By varying the speed of the condenser fan, better
control and quieter operation is obtained during the
colder months. Low ambient controls are available
• Harsh Environments – A variety of coil coating and
materials are available as well as hail guards to pro-
tect coils from weather damage. Seismic and hurri-
cane duty curbs and fan restraints are available.
YORK INTERNATIONAL
6
FORM 100.50-EG1
Physical Data
TABLE 1 – PHYSICAL DATA
MODEL SIZE
50
55
60
65
GENERAL DATA
Length (Inches)
Width (Inches)
336
92
336
92
336
92
336
92
Height (Inches)
82
82
82
82
Operating Weights (Lbs.) (base unit, no options)
Cooling Only (Rigging & Refrigerant)
Rigging Weights (Lbs.) (base unit, no options)
Cooling Only
8,080
8,010
8,290
8,210
8,530
8,440
8,740
8,640
Option Weights (Lbs.)
Power Exhaust (Blower, motor, fan skid & mod damper)
Power Exhaust (Blower, motor, fan skid, VFD & baro damper)
100% AMS (Measurement Station & Mounting)
25/75% AMS (Measurement Station & Mounting)
Min. AMS (Measurement Station & Mounting)
Barometric only
647
654
110
130
40
647
654
110
130
40
647
654
110
130
40
647
654
110
130
40
36
36
36
36
Condenser Hail Guard
32
32
32
32
Copper Condenser Coils
Copper Evaporator Coils
Roof Curb Weights (Lbs.)
14" Full Perimeter Roof Curb
14" Open Condenser Roof Curb
Compressor Data
617
262
617
320
793
400
793
500
787
555
787
555
787
555
787
555
Quantity / Size (Nominal Tons )
Type
4/13
Scroll
4/13
Scroll
4/15
Scroll
4/15
Scroll
Capacity Steps (%)
25, 50, 75, 100 25, 50, 75, 100 25, 50, 75, 100 25, 50, 75, 100
Supply Fan and Drive
Quantity
Type
1
FC
1
FC
1
FC
1
FC
Size
25-22
25-22
25-22
25-22
Motor Size Range (min. to max. HP)
Air Flow Range (min. to max. cfm)
Static Pressure Range (min. to max. ESP)
Exhaust Fan
7.5-40
10000-22500
0-4"
7.5-40
12000-24000
0-4"
7.5-40
14000-27000
0-4"
7.5-40
14000-27000
0-4"
Quantity
Type
2
FC
2
FC
2
FC
2
FC
Size
15-15
5-20
0-20000
0-1"
15-15
5-20
0-20000
0-1"
15-15
5-20
0-20000
0-1"
15-15
5-20
0-20000
0-1"
Motor Size Range (min. to max. HP)
Air Flow Range (min. to max. cfm)
Static Pressure Range (min. to max. ESP)
Evaporator Coil
Size (square feet)
48.8
3/8
48.8
4/8
48.8
4/12
48.8
5/10
Number of rows/fins per inch
Tube Diameter/Surface
Condenser Coil (Aluminum Fins)
Size (square feet)
1/2"/enhanced 1/2"/enhanced 1/2"/enhanced 1/2"/enhanced
121.3
3/14
3/8"
121.3
3/14
3/8"
121.3
3/18
3/8"
121.3
3/18
3/8"
Number of rows/fins per inch
Tube Diameter
Condenser Coil (Copper Fins – Opt)
Size (square feet)
121.3
3/14
3/8"
121.3
3/14
3/8"
121.3
3/18
3/8"
121.3
3/18
3/8"
Number of rows/fins per inch
Tube Diameter
YORK INTERNATIONAL
7
Physical Data (continued)
TABLE 1 – PHYSICAL DATA (Cont’d)
MODEL SIZE
50
55
60
65
GENERAL DATA
Condenser Fans
Quantity
4
4
4
4
Type
Diameter (inches)
Prop.
36
Prop.
36
Prop.
36
Prop.
36
Filters – 2" throwaway
Quantity
Size (length x width) (in.)
Total Filter Face Area (square feet)
Filters – 2" cleanable
Quantity
Size (length x width) (in.)
Total Filter Face Area (square feet)
Filters – 2" pleated (30% efficient)
Quantity
8
12
25x16 25x20 25x16 25x20 25x16 25x20 25x16 25x20
63.9 63.9 63.9 63.9
8
12
8
12
8
12
8
12
25x16 25x20 25x16 25x20 25x16 25x20 25x16 25x20
63.9 63.9 63.9 63.9
8
12
8
12
8
12
8
12
8
12
8
12
8
12
Size (length x width) (in.)
Total Filter Face Area (square feet)
Filters – 12" rigid 65%, 2" 30% prefilter
Quantity
25x16 25x20 25x16 25x20 25x16 25x20 25x16 25x20
63.9
4
63.9
4
63.9
4
63.9
4
1
9
1
9
1
9
1
9
Size (length x width) (in.)
Total Filter Face Area (square feet)
Filters – 12" rigid 95%, 2" 30% prefilter
Quantity
16x20 25x16 25x20 16x20 25x16 25x20 16x20 25x16 25x20 16x20 25x16 25x20
44.6
4
44.6
4
44.6
4
44.6
4
1
9
1
9
1
9
1
9
Size (length x width) (in.)
Total Filter Face Area (square feet)
Filters – 2" carbon (30% efficient)
Quantity
16x20 25x16 25x20 16x20 25x16 25x20 16x20 25x16 25x20 16x20 25x16 25x200
44.6
44.6
12
44.6
44.6
8
12
8
8
12
8
12
Size (length x width) (in.)
Total Filter Face Area (square feet)
Refrigerant
25x16 25x20 25x16 25x20 25x16 25x20 25x16 25x20
63.9
63.9
63.9
63.9
HFC-407C
HFC-407C
HFC-407C
HFC-407C
Minimum OA Temp. for Mech. Clg. (°F)
Low Ambient Option Min. OA Temp. (°F)
45
0
45
0
45
0
45
0
YORK INTERNATIONAL
8
FORM 100.50-EG1
Application Data
LOCATION
Spreader bars must be used to prevent damage to the
unit casing. All lifting lugs must be used when lifting the
rooftop unit.
Of the many factors that can affect the acoustical char-
acteristics of a rooftop installation, one of the most im-
portant is the unit location. Ideally, the rooftop unit should
be installed away from sound-sensitive areas, such as
conference rooms, auditoriums and executive offices.
Possible locations could be above storage areas, hall-
ways, mechanical or utility rooms, or bathrooms.
Care must be taken to keep the unit in the upright posi-
tion during rigging and to prevent damage to the water-
tight seams in the unit casing. Avoid unnecessary jar-
ring or rough handling.
Ground Level Locations
The eco2 air conditioning units are designed for out-
door installation. When selecting a site for installation,
be guided by the following conditions:
It is important that the units be installed on a substan-
tial base that will not settle, causing strain on the refrig-
erant lines and sheet metal and resulting in possible
leaks. A one-piece concrete slab with footers extended
below the frost line is highly recommended. Addition-
ally, the slab should not be tied to the main building
foundation as noises may be transmitted into the build-
ing structure.
• Unit must be installed on a level surface.
• For the outdoor location of the unit, select a place
having a minimum sun exposure and an adequate
supply of fresh air for the condenser.
For ground level installations, precautions should be
taken to protect the unit from tampering by, or injury to,
unauthorized persons. Erecting a fence around the unit
is another common practice.
• Also avoid locations beneath windows or between
structures.
• Optional condenser coil protection should be used
for seashore locations or other harsh environments.
• The unit should be installed on a roof that is struc-
turally strong enough to support the weight of the
unit with a minimum of deflection. Extreme caution
should be taken when the unit is mounted on a wood
structured roof. It is recommended that the unit(s)
be installed not more than 15 feet from a main sup-
port beam to provide proper structural support and
to minimize the transmission of sound and vibra-
tion. Ideally, the center of gravity should be located
over a structural support or building column.
ECONOMIZER
The economizer section is used for ventilation of the
conditioned space to maintain indoor air quality, and
also to reduce energy consumption by using outdoor
air cooling in lieu of mechanical cooling. If outdoor air
is appropriate for cooling, but not sufficient for the cool-
ing demand, mechanical cooling will stage on as nec-
essary until the cooling load is met.
Comparative enthalpy operation is the most accurate and
efficient means of economizer operation. The OptiLogicTM
control monitors the return and outside air energy con-
tent, and selects the lower of the two for operation.
• Location of unit(s) should also be away from build-
ing flue stacks or exhaust ventilators to prevent pos-
sible reintroduction of contaminated air through the
outside air intakes.
• Be sure the supporting structures will not obstruct
the duct, gas or wiring connections.
VAV SUPPLY AIR PRESSURE CONTROL
• Proper service clearance space of 6-feet around
the perimeter of the unit and 12-feet to any adja-
cent units is required to eliminate cross contami-
nation of exhaust and outdoor air, and for mainte-
nance tasks such as coil pull and cleaning. No ob-
structions should be above the condensing unit
section.
Traditional packaged rooftop systems use inlet guide
vanes (IGVs) for duct static pressure control. These con-
trol supply duct pressure by modulating dampers (intro-
ducing losses and inefficiencies) on the intlet of the fan,
open and closed. Variable frequency drives (VFDs) of-
fer superior fan speed control and quieter, energy effi-
cient operation.
RIGGING
IGV inefficiency can be compared to the operation of a
car. Modulating air flow with an IGV is like pressing on
the gas to drive the car, but modulating the speed of the
car by simultaneously pressing on the brake. VFD modu-
lation is speed modulation by using just the gas pedal.
Proper rigging and handling of the equipment is man-
datory during unloading and setting it into position to
retain warranty status.
YORK INTERNATIONAL
9
Application Data (continued)
For VAV applications, the YORK eco2 unit uses a VFD
to modulate fan speed and maintain a constant duct
static pressure. VFDs offer superior control over the
operation of the unit at part load, and offer the addi-
tional benefits of quieter and more efficient operation
when compared to IGV.
BUILDING EXHAUST SYSTEMS
Building exhaust systems are often necessary when
economizers are used to bring in outdoor air. Without
proper building exhaust, the building may become over-
pressurized. The exhaust system maintains the proper
building pressure by expelling the appropriate amount
of air from the building. Exhaust systems are typically
designed to exhaust approximately 10% less air than
what is entering the building. This provides a slight posi-
tive pressure on the building.
HARSH ENVIRONMENTS – CONDENSER AND
EVAPORATOR COIL PROTECTION
For harsh environmental conditions such as seashore
applications, YORK offers three types of coil protec-
tion: copper fin material, black fin and Technicoat coat-
ings. YORK recommends that for corrosive environ-
ments that copper fins be used to protect the evapora-
tor and/or condenser coils. In areas where chemicals
that can corrode copper are present, such as ammo-
nia, YORK recommends that the black fin or Technicoat
coating be used for maximum protection.
100% modulating exhaust with building static
pressure sensing and control
The 100% exhaust system can be configured with ei-
ther control actuated dampers or VFDs for modulating
control. The unit controller monitors the building pres-
sure using a differential pressure transducer and main-
tains the required building static pressure by modulat-
ing the exhaust control. If the building has other means
of exhaust or building pressure is not important, on/off
or barometric control may be used.
Copper Fin Condenser Coil
Copper fins can be used instead of aluminum for addi-
tional corrosion protection, however it is not suitable
for areas that are subject to acid rain or exposed to
ammonia.
100% modulating exhaust with fan on/off control
The 100% exhaust system can be configured for on/off
operation eliminating the expense of the damper ac-
tuators or VFDs. This exhaust system can be controlled
by either the outside air damper position, or a building
static pressure sensor.
Pre-Coated Condenser Fins
Black fin coating (yellow fin for evaporator fins) is pre-
coated application epoxy on aluminum fin stock to guard
from corrosive agents and insulate against galvanic po-
tential. It is used for mild seashore or industrial loca-
tions. This can provide corrosion resistance comparable
to copper fin coils in typical seashore locations.
Barometric exhaust
Barometric exhaust can be used when smaller amounts
of air at low static pressure variations within the build-
ing or other means of building exhaust are employed.
Barometric exhaust is commonly used where there are
only small fluctuations in building pressure or where
building static pressure control is not necessary.
Post-Coated Condenser Fins
Technicoat (a post-coated application of epoxy) can be
used for seashore and other corrosive applications with
the exception of strong alkalides, oxidizers, wet bro-
mide, chlorine and fluorine in concentrations greater
than 100 ppm.
ROOF CURB
Optional 14-inch full-perimeter or open condenser roof
curbs can be provided if necessary for mounting to
the building roof. These curbs come disassembled and
require installation in the field. For bottom supply and
return duct openings, the curbs have matching con-
nections to ease installation. A pipe chase that
matches the rooftop unit is also included in the curb
footprint for through-the-curb utility connections.
Any of the above suitable options should be selected
based on the particular project design parameters and
related environmental factors. The application should
be further reviewed and approved by the consulting en-
gineer or owner based on their knowledge of the job
site conditions.
YORK INTERNATIONAL
10
FORM 100.50-EG1
The curb should be located according to the location
recommendations above, and properly sealed to pre-
vent moisture and air leakage into and out of the duct
system. Flexible collars should be used when connect-
ing the duct work to prevent unit noise transmission
and vibration into the building.
and the unit requires a modulating economizer, 2-inch
pleated filters, bottom supply and bottom return air open-
ings and is constant volume.
Select Unit:
1. Determine the internal static pressure drop of the
cabinet by referencing Table 8.
Duct work should be supported independently of the
unit.
Wet evaporator coil
0.54
0.14
0.13
0.10
0.24
0.31
Bottom supply opening
Bottom return opening
2-inch pleated filters
Economizer openings
Modulating economizer dampers
ACOUSTICAL CONSIDERATIONS
The eco2 unit is designed for lower sound levels than
competitive units by using flexible fan connections, fan
spring isolators, double-wall construction, and lower
speed and horsepower fans. For VAV applications,
VFDs are used instead of inlet guide vanes. Additional
sound attenuation can be obtained using compressor
sound blankets and field-supplied sound attenuators
when necessary.
Total 1.46 IWG
2. Determine the total static pressure by adding the
internal to the external static pressure.
TSP = 1.46 IWG + 2.25 IWG
= 3.71 IWG total static pressure
Even with these equipment design features, the acous-
tical characteristics of the entire installation must never
be overlooked. Additional steps for the acoustical char-
acteristics of a rooftop installation should be addressed
during the design phase of a project to avoid costly al-
terations after the installation of the equipment. During
the design phase of a project, the designing engineer
should consider, at a minimum, the impact of the equip-
ment location, rooftop installation, building structure,
and duct work.
3. Determine the BHP of the supply fan from Table 6
using the supply air flow and total static pressure.
From the table, we interpolate to get 15.1 BHP. As-
suming a drive loss of 3% and a motor efficiency of
90%, we can calculate the heat rejection of the sup-
ply fan motor as:
(2545 x 15.1)/(0.90 x (1-0.03)) = 44.0 mbh
Required Cooling Capacities:
Total = 600 + 44.0 = 644 mbh
Sensible = 450 + 44.0 = 494 mbh
4. Required total and sensible capacities are 644 mbh
and 494 mbh, respectively. Using the Cooling Per-
formance Data starting with Tables 2, locate the
table with the correct ambient air temperature. Next,
trace the 83°F entering air dry bulb temperature to
match the 17,500 cfm and 67°F entering wet bulb
temperature condition. The resulting conditions are,
from the table, 645 mbh total cooling capacity and
497 mbh sensible cooling capacity. Thus, a 50-ton
unit is selected.
SELECTION PROCEDURE
Given:
Required total cooling capacity of 600 mbh and sen-
sible cooling capacity of 450 mbh with evaporator en-
tering air conditions of 83°F dry bulb and 67°F wet bulb.
Design ambient temperature is 95°F dry bulb. Supply
air requirements are 17500 cfm of air at 2.25 IWG ex-
ternal static pressure. Power supply is 460V/3ph/60Hz
YORK INTERNATIONAL
11
Cooling Performance Data – 50 Ton Model
TABLE 2 – COOLING PERFORMANCE DATA – 50 TON MODEL
85° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
ENTERING
90
86
83
80
77
74
CFM
WB (°F)
72
CAP
700
653
640
711
665
654
729
684
680
749
705
710
758
715
715
SHC
477
548
640
500
581
654
536
634
680
576
695
710
595
715
715
CAP
700
646
608
708
656
625
721
672
652
736
689
682
742
697
696
SHC
431
500
608
445
523
625
467
558
652
492
597
682
504
616
610
CAP
695
635
590
705
647
606
719
666
632
736
686
661
743
696
674
SHC
387
454
583
399
474
606
418
505
625
439
540
661
449
557
549
CAP
692
637
582
701
647
594
715
663
612
732
680
633
739
689
643
SHC
353
416
562
360
431
547
370
454
550
382
479
582
388
492
486
CAP
691
632
569
699
643
583
712
660
606
726
679
631
732
688
643
SHC
311
377
514
316
388
498
324
406
497
333
425
523
338
435
429
CAP
—
SHC
—
10000
67
626
574
—
343
455
—
62
72
14000
17500
20000
22500
67
637
585
—
349
439
—
62
72
67
653
603
—
359
438
—
62
72
67
672
622
—
370
467
—
62
72
67
680
631
376
370
62
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
95° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
83 80
ENTERING
90
86
77
74
CFM
WB (°F)
72
CAP
673
628
618
684
642
635
701
665
661
720
691
691
729
703
704
SHC
468
536
618
491
569
635
526
625
661
565
691
691
584
703
704
CAP
673
630
590
682
638
607
696
651
634
712
665
663
720
672
675
SHC
416
494
590
432
515
607
458
547
634
486
582
663
500
599
658
CAP
669
615
569
678
627
586
693
645
612
709
665
641
717
674
655
SHC
375
445
513
388
465
541
407
497
587
429
532
641
439
549
629
CAP
667
616
571
676
625
580
690
640
594
705
656
609
712
664
617
SHC
340
404
481
348
419
500
360
443
531
373
470
565
380
483
556
CAP
664
609
562
673
619
572
686
635
588
701
653
606
708
661
614
SHC
301
383
435
306
382
453
315
382
481
325
382
511
329
382
488
CAP
—
SHC
—
10000
67
605
562
—
331
390
—
62
72
14000
17500
20000
22500
67
615
571
—
338
407
—
62
72
67
630
586
—
348
433
—
62
72
67
647
602
—
360
462
—
62
72
67
655
610
366
447
62
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
YORK INTERNATIONAL
12
FORM 100.50-EG1
TABLE 2 – COOLING PERFORMANCE DATA – 50 TON MODEL (CONT’D)
105° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
83 80 77
ENTERING
90
86
74
CFM
WB (°F)
72
CAP
649
590
597
658
609
614
673
638
641
689
670
670
696
686
684
SHC
464
513
597
483
550
614
512
607
641
545
670
670
560
695
684
CAP
650
596
573
658
608
589
670
625
614
684
645
642
690
654
655
SHC
409
478
573
424
501
589
447
537
614
472
577
642
485
596
655
CAP
645
589
536
653
600
556
667
618
587
682
638
621
690
647
637
SHC
365
434
498
378
454
527
397
485
571
419
520
621
430
537
644
CAP
644
591
549
651
600
557
663
615
570
677
631
584
683
639
591
SHC
330
390
460
338
406
483
350
432
520
364
461
561
371
475
580
CAP
644
593
544
650
601
553
661
613
567
672
626
582
678
632
590
SHC
290
354
429
295
366
446
303
384
472
311
404
500
315
414
514
CAP
—
SHC
—
10000
67
589
542
—
318
384
—
62
72
14000
17500
20000
22500
67
597
550
—
326
397
—
62
72
67
609
563
—
337
419
—
62
72
67
623
576
—
350
443
—
62
72
67
629
583
356
455
62
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
115° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
83 80 77
ENTERING
90
86
74
CFM
WB (°F)
72
CAP
563
494
498
592
548
550
608
577
578
625
609
609
633
624
624
SHC
368
424
498
432
509
550
465
555
578
503
609
609
520
624
624
CAP
562
524
501
588
545
533
603
557
550
618
570
568
626
576
577
SHC
318
387
501
370
449
533
397
481
550
427
517
568
441
534
577
CAP
567
514
442
589
541
498
600
555
527
613
571
560
619
579
575
SHC
286
349
424
325
406
488
346
435
522
368
468
560
379
484
578
CAP
558
515
458
585
539
494
600
552
513
616
566
534
623
572
544
SHC
258
313
349
286
359
434
300
383
478
316
410
528
324
423
548
CAP
563
514
467
583
536
491
594
548
504
606
562
518
611
568
525
SHC
233
281
343
246
317
395
253
336
422
261
357
452
265
367
467
CAP
—
SHC
—
10000
67
518
467
—
254
306
—
62
72
14000
17500
20000
22500
67
537
489
—
276
349
—
62
72
67
547
500
—
288
371
—
62
72
67
558
513
—
301
396
—
62
72
67
563
520
307
408
62
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
YORK INTERNATIONAL
13
Cooling Performance Data – 55 Ton Model
TABLE 3 – COOLING PERFORMANCE DATA – 55 TON MODEL
85° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
ENTERING
90
86
83
80
77
74
CFM
WB (°F)
72
CAP
732
677
660
743
693
680
767
728
725
781
750
750
786
758
760
SHC
488
564
648
512
598
661
564
677
701
592
713
713
604
720
720
CAP
704
651
616
712
661
634
731
684
673
741
695
694
746
701
701
SHC
437
511
616
452
535
634
485
586
673
502
613
613
510
625
602
CAP
700
641
598
709
653
615
731
680
652
742
694
672
747
701
681
SHC
393
463
598
405
484
587
433
530
652
448
554
554
454
565
534
CAP
696
642
588
706
652
600
727
675
627
738
688
642
743
693
648
SHC
356
423
564
363
438
531
378
472
572
387
490
490
390
497
473
CAP
695
637
576
703
649
591
722
673
624
731
687
641
736
692
649
SHC
313
382
515
319
394
481
331
419
515
337
433
433
340
439
416
CAP
—
SHC
—
12000
67
631
579
—
346
456
—
62
72
16000
19250
22000
24000
67
642
591
—
353
421
—
62
72
67
666
616
—
367
458
—
62
72
67
679
630
—
375
375
—
62
72
67
685
636
378
357
62
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
95° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
83 80
ENTERING
90
86
77
74
CFM
WB (°F)
72
CAP
706
651
641
716
668
661
738
707
705
751
728
730
756
737
740
SHC
479
554
626
502
585
644
554
671
682
581
701
703
593
709
709
CAP
678
634
598
687
643
616
708
661
654
719
671
675
723
675
675
SHC
424
504
598
441
525
616
478
572
654
497
597
675
506
607
607
CAP
673
621
577
683
633
594
704
659
633
715
673
653
720
678
662
SHC
381
454
527
394
476
554
422
521
625
438
546
653
444
556
556
CAP
671
621
575
680
630
585
700
651
605
711
663
616
715
667
620
SHC
344
411
490
352
427
511
369
462
555
379
481
578
383
489
489
CAP
668
613
567
677
624
577
696
647
600
707
660
613
711
665
618
SHC
303
382
444
309
382
462
322
382
502
328
382
524
331
382
382
CAP
—
SHC
—
12000
67
610
566
—
334
398
—
62
72
16000
19250
22000
24000
67
620
576
—
341
415
—
62
72
67
642
598
—
357
453
—
62
72
67
654
609
—
365
473
—
62
72
67
659
614
369
369
62
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
YORK INTERNATIONAL
14
FORM 100.50-EG1
TABLE 3 – COOLING PERFORMANCE DATA – 55 TON MODEL (CONT’D)
105° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
ENTERING
90
86
83
80
77
74
CFM
WB (°F)
72
CAP
642
593
592
661
619
618
701
679
679
723
711
711
733
724
725
SHC
473
531
605
493
569
623
535
651
661
558
696
682
567
693
691
CAP
654
602
581
662
613
598
679
639
634
689
653
653
693
659
661
SHC
416
489
581
432
513
598
465
565
634
483
593
653
490
605
661
CAP
649
594
546
658
606
566
678
632
611
689
645
635
693
651
645
SHC
371
443
512
384
464
542
413
510
606
428
534
641
435
545
656
CAP
647
595
553
655
605
561
673
626
580
682
637
590
686
642
594
SHC
334
397
471
342
415
496
360
452
549
370
473
577
374
481
590
CAP
647
597
549
654
605
558
669
622
578
677
631
588
681
635
593
SHC
292
359
437
297
372
454
308
398
492
314
412
512
317
418
521
CAP
—
SHC
—
12000
67
593
546
—
322
390
—
62
72
16000
19250
22000
24000
67
601
554
—
330
405
—
62
72
67
619
572
—
346
436
—
62
72
67
628
582
—
355
453
—
62
72
67
632
586
359
460
62
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
115° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
83 80 77
ENTERING
90
86
74
CFM
WB (°F)
72
CAP
657
606
598
665
623
617
682
660
659
692
680
682
696
689
692
SHC
460
535
581
482
562
600
529
632
639
554
660
660
565
668
669
CAP
624
579
557
633
588
572
653
606
602
663
617
616
668
621
622
SHC
400
477
567
417
498
578
455
544
602
476
568
614
484
578
620
CAP
618
571
528
627
582
547
647
605
589
658
617
611
663
622
621
SHC
357
435
517
371
454
539
399
496
587
414
518
613
421
527
624
CAP
613
566
519
623
577
534
645
599
565
657
611
582
662
617
589
SHC
321
390
458
330
406
487
350
440
551
360
458
585
365
466
589
CAP
610
563
517
619
573
528
640
595
552
651
607
565
656
613
570
SHC
284
350
425
288
362
443
297
388
481
302
402
501
304
408
510
CAP
—
SHC
—
12000
67
559
512
—
312
381
—
62
72
16000
19250
22000
24000
67
570
523
—
319
395
—
62
72
67
592
547
—
335
426
—
62
72
67
603
559
—
343
443
—
62
72
67
608
565
347
450
62
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
YORK INTERNATIONAL
15
Cooling Performance Data – 60 Ton Model
TABLE 4 – COOLING PERFORMANCE DATA – 60 TON MODEL
85° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
ENTERING
90
86
83
80
77
74
CFM
WB (°F)
72
CAP
804
736
689
846
795
771
867
824
813
888
854
854
897
867
873
SHC
495
586
689
609
720
771
666
787
813
722
854
854
748
867
873
CAP
804
728
663
840
773
740
858
795
779
876
818
817
884
828
835
SHC
461
522
663
538
632
740
576
687
779
614
742
817
632
767
835
CAP
801
729
658
837
771
725
855
792
759
872
814
792
880
823
808
SHC
277
339
442
410
504
617
477
587
705
544
670
792
574
708
817
CAP
798
727
656
833
769
704
851
790
728
868
810
752
876
820
763
SHC
383
440
543
426
519
630
448
558
673
470
598
716
480
616
736
CAP
792
725
647
827
767
700
845
787
726
862
808
752
870
818
764
SHC
344
408
493
372
468
572
386
498
611
401
528
651
407
541
669
CAP
—
SHC
—
14000
67
723
654
—
377
424
—
62
72
18000
21000
24000
27000
67
761
699
—
415
502
—
62
72
67
780
722
—
434
541
—
62
72
67
799
744
—
453
580
—
62
72
67
808
755
461
598
62
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
95° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
83 80
ENTERING
90
86
77
74
CFM
WB (°F)
72
CAP
773
723
671
814
775
750
834
802
789
854
828
828
864
840
846
SHC
491
527
671
599
678
750
652
753
789
706
828
828
730
863
846
CAP
771
692
645
808
752
719
827
783
756
846
813
793
854
827
810
SHC
442
464
645
524
570
719
565
623
756
607
675
793
626
699
810
CAP
769
703
631
804
745
699
822
766
732
840
788
766
848
797
782
SHC
336
397
474
434
529
620
482
594
693
531
660
766
553
691
788
CAP
769
703
642
802
742
684
819
761
706
835
780
727
843
789
737
SHC
368
432
505
414
508
604
438
546
653
461
584
703
471
601
726
CAP
763
699
655
797
736
682
814
755
696
831
774
709
838
782
716
SHC
331
437
416
361
455
550
376
463
616
391
472
683
397
476
714
CAP
—
SHC
—
14000
67
696
673
—
363
318
—
62
72
18000
21000
24000
27000
67
732
681
—
402
494
—
62
72
67
751
685
—
421
582
—
62
72
67
769
689
—
441
670
—
62
72
67
778
690
450
710
62
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
YORK INTERNATIONAL
16
FORM 100.50-EG1
TABLE 4 – COOLING PERFORMANCE DATA – 60 TON MODEL (CONT’D)
105° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
83 80 77
ENTERING
90
86
74
CFM
WB (°F)
72
CAP
753
690
652
782
745
726
797
773
763
811
801
800
818
814
817
SHC
500
469
652
588
635
726
633
718
763
677
801
800
697
839
817
CAP
744
676
627
778
718
697
794
739
732
811
761
767
818
771
783
SHC
438
304
627
514
508
697
551
610
732
589
712
767
606
759
783
CAP
741
672
587
774
713
664
790
734
702
806
754
741
814
764
758
SHC
392
458
554
457
550
648
490
597
694
522
643
741
537
664
759
CAP
741
681
616
771
715
658
787
732
679
802
750
700
809
757
710
SHC
357
416
489
403
494
589
425
533
639
448
572
690
459
589
709
CAP
737
681
632
767
711
655
782
727
667
798
742
679
804
749
684
SHC
319
384
454
347
442
536
361
471
576
375
500
617
382
514
636
CAP
—
SHC
—
14000
67
678
624
—
350
412
—
62
72
18000
21000
24000
27000
67
708
655
—
389
480
—
62
72
67
723
670
—
409
515
—
62
72
67
738
686
—
428
549
—
62
72
67
744
693
437
565
62
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
115° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
83 80 77
ENTERING
90
86
74
CFM
WB (°F)
72
CAP
726
629
626
749
700
699
760
736
735
772
772
772
777
788
788
SHC
485
574
626
572
673
699
615
722
735
658
772
772
678
788
788
CAP
711
647
607
742
688
666
758
708
695
774
728
724
781
737
737
SHC
413
512
622
496
603
673
538
648
698
580
693
724
599
714
735
CAP
702
647
562
736
683
639
754
701
677
771
718
715
779
727
732
SHC
376
447
543
440
537
629
473
582
672
505
627
715
520
647
733
CAP
698
643
561
732
680
625
749
699
657
766
717
690
773
726
704
SHC
345
411
467
389
484
578
411
521
634
433
558
690
443
574
706
CAP
689
635
582
726
673
620
744
692
640
763
711
659
771
719
668
SHC
309
370
447
335
429
524
349
458
563
362
487
602
368
501
619
CAP
—
SHC
—
14000
67
633
574
—
338
404
—
62
72
18000
21000
24000
27000
67
669
617
—
376
472
—
62
72
67
687
638
—
395
505
—
62
72
67
706
659
—
414
539
—
62
72
67
714
669
423
555
62
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
YORK INTERNATIONAL
17
Cooling Performance Data – 65 Ton Model
TABLE 5 – COOLING PERFORMANCE DATA – 65 TON MODEL
85° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
ENTERING
90
86
83
80
77
74
CFM
WB (°F)
72
CAP
840
785
754
853
802
779
876
827
821
899
862
862
909
878
878
SHC
584
669
754
615
713
779
668
788
821
721
862
862
745
878
878
CAP
839
774
724
851
788
748
871
810
787
892
833
827
901
843
843
SHC
516
605
724
540
638
748
582
694
787
623
750
827
642
776
765
CAP
836
771
695
848
784
719
868
806
760
888
828
801
898
838
820
SHC
467
554
640
486
582
676
518
630
739
550
678
801
564
700
686
CAP
833
772
710
844
784
723
864
804
745
884
824
767
893
833
777
SHC
418
502
589
431
525
620
454
563
674
477
601
727
488
619
604
CAP
828
768
707
840
780
719
859
800
741
878
820
762
887
829
772
SHC
368
456
542
377
473
568
392
502
612
407
531
656
413
544
530
CAP
—
SHC
—
14000
67
764
706
—
406
492
—
62
72
18000
21000
24000
27000
67
776
717
—
418
513
—
62
72
67
796
737
—
439
548
—
62
72
67
815
757
—
460
584
—
62
72
67
824
766
469
455
62
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
95° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
83 80
ENTERING
90
86
77
74
CFM
WB (°F)
72
CAP
810
767
733
822
782
756
844
800
797
866
837
837
875
854
854
SHC
572
658
733
603
699
756
656
768
797
709
837
837
733
854
854
CAP
808
747
704
820
759
726
839
781
764
858
802
802
867
812
812
SHC
504
593
704
528
625
726
569
681
764
610
737
802
629
762
753
CAP
806
743
676
817
756
699
836
777
737
855
798
776
863
807
794
SHC
454
542
631
473
570
664
505
618
720
537
665
776
552
687
674
CAP
802
744
686
813
755
697
832
774
717
850
793
737
859
801
746
SHC
405
491
581
419
513
610
442
551
661
464
589
712
475
606
592
CAP
798
740
682
809
751
694
827
770
714
844
788
734
852
797
743
SHC
357
443
530
365
460
556
380
489
600
394
519
644
401
532
518
CAP
—
SHC
—
14000
67
737
680
—
393
477
—
62
72
18000
21000
24000
27000
67
748
691
—
406
500
—
62
72
67
766
710
—
426
538
—
62
72
67
784
729
—
447
577
—
62
72
67
792
738
456
441
62
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
YORK INTERNATIONAL
18
FORM 100.50-EG1
TABLE 5 – COOLING PERFORMANCE DATA – 65 TON MODEL (CONT’D)
105° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
83 80 77
ENTERING
90
86
74
CFM
WB (°F)
72
CAP
780
737
710
792
753
732
812
771
771
831
809
809
840
826
826
SHC
560
646
710
591
683
732
643
746
771
696
809
809
720
826
826
CAP
777
717
682
788
730
703
805
752
739
822
774
774
830
784
791
SHC
493
581
682
516
613
703
555
668
739
595
722
774
613
747
791
CAP
774
714
650
785
726
672
802
746
711
820
766
750
828
775
767
SHC
442
529
621
461
556
650
493
604
700
524
651
750
539
673
772
CAP
771
714
658
781
725
669
798
744
689
816
762
709
823
770
718
SHC
393
476
565
406
499
595
429
538
647
452
576
698
462
594
721
CAP
768
711
655
777
721
666
794
738
685
810
756
704
817
763
712
SHC
342
430
516
351
447
542
365
476
586
379
505
630
386
518
650
CAP
—
SHC
—
14000
67
708
653
—
381
466
—
62
72
18000
21000
24000
27000
67
718
663
—
393
486
—
62
72
67
734
681
—
413
522
—
62
72
67
751
699
—
433
558
—
62
72
67
759
707
442
574
62
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
115° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
83 80 77
ENTERING
90
86
74
CFM
WB (°F)
72
CAP
748
708
681
759
724
704
776
741
741
794
779
779
802
796
796
SHC
548
639
681
578
671
704
629
725
741
680
779
779
703
796
796
CAP
744
690
664
754
700
679
771
716
706
789
732
732
797
740
740
SHC
478
570
664
502
599
679
543
650
706
584
700
732
603
723
717
CAP
742
686
621
752
696
644
768
714
682
784
732
721
791
740
738
SHC
429
517
608
448
544
634
479
591
678
511
637
721
525
658
648
CAP
738
684
625
748
694
642
766
711
669
784
728
697
792
736
710
SHC
378
463
550
392
486
583
415
523
640
438
561
697
449
578
563
CAP
735
681
628
744
690
638
759
706
655
774
722
672
781
729
680
SHC
330
417
503
338
434
528
352
462
571
366
491
615
372
504
490
CAP
—
SHC
—
14000
67
678
625
—
368
452
—
62
72
18000
21000
24000
27000
67
687
635
—
380
473
—
62
72
67
703
651
—
400
508
—
62
72
67
718
668
—
419
543
—
62
72
67
725
676
428
414
62
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
YORK INTERNATIONAL
19
Fan Performance
TABLE 6 – 50 THROUGH 65 TON SUPPLY FAN DATA
TOTAL STATIC PRESSURE (inches of water column)
1.00 1.50 2.00 2.50
RPM RPM RPM RPM
CFM
STD. AIR
10000
12000
14000
16000
17500
18000
19250
20000
21000
22000
22500
24000
26000
27000
0.50
RPM
3.00
RPM
HP
1.7
HP
2.5
HP
3.3
HP
HP
––
HP
249
269
290
312
329
334
348
357
370
383
387
398
417
429
321
335
352
371
386
391
404
412
423
434
440
458
478
490
382
392
405
421
435
439
451
458
468
478
484
500
520
533
––
––
––
––
—
2.5
3.4
4.4
443
454
467
478
482
493
499
510
520
524
537
559
572
5.3
493
497
510
519
522
532
538
547
555
560
574
593
602
6.4
––
—
3.6
4.7
5.8
6.9
8.0
540
549
558
561
570
575
583
591
595
607
626
638
9.1
5.1
6.3
7.5
8.7
10.0
11.7
12.3
14.0
15.1
16.7
18.3
19.2
22.1
26.3
28.6
11.2
13.1
13.8
15.5
16.6
18.3
20.0
20.9
23.8
28.3
30.9
6.3
7.7
9.0
10.4
10.9
12.5
13.5
15.1
16.7
17.6
20.2
24.4
26.8
6.8
8.2
9.6
8.1
9.6
11.1
12.1
13.5
15.0
15.8
18.4
22.3
24.6
8.9
10.5
11.9
13.3
14.1
16.6
20.2
22.3
10.1
11.4
12.0
13.9
16.8
18.6
TABLE 6 – 50 THROUGH 65 TON SUPPLY FAN DATA (CONT’D)
TOTAL STATIC PRESSURE (inches of water column)
4.00 4.50 5.00 5.50
RPM RPM RPM RPM
CFM
STD. AIR
10000
12000
14000
16000
17500
18000
19250
20000
21000
22000
22500
24000
26000
27000
3.50
RPM
6.00
HP
––
HP
––
HP
––
HP
––
HP
––
RPM
––
HP
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
585
587
595
597
605
609
617
624
628
640
656
665
10.5
12.5
14.5
15.2
17.1
18.2
19.9
21.7
22.7
25.7
30.2
32.7
––
––
––
––
––
––
––
––
––
––
622
629
631
638
642
649
655
659
671
687
693
13.8
15.9
16.6
18.6
19.8
21.6
23.4
24.4
27.5
32.2
34.6
663
664
664
670
674
681
688
691
700
716
723
15.4
17.3
18.0
20.1
21.4
23.3
25.3
26.3
29.4
34.2
36.8
700
697
696
702
705
710
715
719
729
742
751
17.0
18.8
19.5
21.6
22.9
24.9
26.9
28.0
31.4
36.1
38.9
––
––
––
––
549
732
734
735
740
744
748
759
769
778
15.9
21.2
23.3
24.5
26.6
28.6
29.8
33.4
38.2
41.0
575
766
765
764
769
773
776
783
798
802
17.3
23.0
25.0
26.1
28.2
30.4
31.5
35.1
40.5
43.1
YORK INTERNATIONAL
20
FORM 100.50-EG1
TABLE 7 – 50 THROUGH 65 TON EXHAUST FAN DATA
TOTAL STATIC PRESSURE (inches of water column)
1.00 1.50 2.00 2.50
RPM RPM RPM RPM
––
CFM
STD. AIR
10000
12000
14000
16000
18000
20000
0.50
RPM
3.00
RPM
HP
HP
HP
–––
6.87
HP
––
––
HP
––
––
HP
––
––
––
674
713
762
819
3.30
4.84
6.84
9.36
801
823
858
4.18
––
––
––
––
––
––
––
5.82 929
7.98 952
9.12 1043 10.32 1132 11.62
904 10.73 988 12.04 1070 13.33 1150 14.69 1229 16.10
879 12.42 957 14.04 1032 15.56 1107 17.02 1179 18.48
943 16.18 1014 18.04 –– –– –– –– –– ––
––
––
––
––
YORK INTERNATIONAL
21
Fan Performance (continued)
TABLE 8 – COMPONENT STATIC PRESSURE DROPS (INCHES OF WATER COLUMN)
FILTERS
2" 2"
THROW- CLEAN- PLEAT-
EVAPORATOR
COILS
SUPPLY
RETURN AIR
OPENING
AIR FLOW
2"
SIZE
50
2"
OPENING
CFM STD. AIR
CARBON
WET
DRY
BOTTOM LEFT RIGHT BOTTOM REAR SIDES AWAY
ABLE
ED
10000
12000
14000
16000
17500
18000
20000
21000
22000
22500
12000
14000
16000
18000
19250
20000
22000
24000
14000
16000
18000
20000
21000
22000
24000
26000
27000
14000
16000
18000
20000
21000
22000
24000
26000
27000
0.22
0.30
0.38
0.47
0.54
0.57
0.67
0.72
0.78
0.80
0.30
0.38
0.47
0.57
0.63
0.67
0.78
0.89
0.38
0.47
0.57
0.67
0.72
0.78
0.89
1.01
1.07
0.38
0.47
0.57
0.67
0.72
0.78
0.89
1.01
1.07
0.15
0.21
0.27
0.35
0.41
0.44
0.53
0.58
0.63
0.66
0.21
0.27
0.35
0.44
0.49
0.53
0.63
0.74
0.27
0.35
0.44
0.53
0.58
0.63
0.74
0.86
0.92
0.27
0.35
0.44
0.53
0.58
0.63
0.74
0.86
0.92
0.04
0.06
0.09
0.11
0.14
0.14
0.18
0.20
0.21
0.22
0.06
0.09
0.11
0.14
0.16
0.18
0.21
0.25
0.09
0.11
0.14
0.18
0.20
0.21
0.25
0.30
0.32
0.09
0.11
0.14
0.18
0.20
0.21
0.25
0.30
0.32
0.08 0.08
0.11 0.11
0.15 0.15
0.20 0.20
0.24 0.24
0.25 0.25
0.31 0.31
0.35 0.35
0.38 0.38
0.40 0.40
0.11 0.11
0.15 0.15
0.20 0.20
0.25 0.25
0.29 0.29
0.31 0.31
0.38 0.38
0.45 0.45
0.15 0.15
0.20 0.20
0.25 0.25
0.31 0.31
0.35 0.35
0.38 0.38
0.45 0.45
0.53 0.53
0.57 0.57
0.15 0.15
0.20 0.20
0.25 0.25
0.31 0.31
0.35 0.35
0.38 0.38
0.45 0.45
0.53 0.53
0.57 0.57
0.04
0.06
0.08
0.11
0.13
0.13
0.17
0.18
0.20
0.21
0.06
0.08
0.11
0.13
0.15
0.17
0.20
0.24
0.08
0.11
0.13
0.17
0.18
0.20
0.24
0.28
0.30
0.08
0.11
0.13
0.17
0.18
0.20
0.24
0.28
0.30
0.06 0.04
0.09 0.06
0.12 0.09
0.15 0.11
0.18 0.14
0.19 0.14
0.24 0.18
0.26 0.20
0.29 0.21
0.30 0.22
0.09 0.06
0.12 0.09
0.15 0.11
0.19 0.14
0.22 0.16
0.24 0.18
0.29 0.21
0.34 0.25
0.12 0.09
0.15 0.11
0.19 0.14
0.24 0.18
0.26 0.20
0.29 0.21
0.34 0.25
0.40 0.30
0.43 0.32
0.12 0.09
0.15 0.11
0.19 0.14
0.24 0.18
0.26 0.20
0.29 0.21
0.34 0.25
0.40 0.30
0.43 0.32
0.05
0.07
0.09
0.11
0.12
0.13
0.15
0.16
0.17
0.17
0.07
0.09
0.11
0.13
0.14
0.15
0.17
0.19
0.09
0.11
0.13
0.15
0.16
0.17
0.19
0.21
0.23
0.09
0.11
0.13
0.15
0.16
0.17
0.19
0.21
0.23
0.01
0.02
0.03
0.04
0.05
0.05
0.06
0.07
0.08
0.08
0.02
0.03
0.04
0.05
0.06
0.06
0.08
0.09
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.11
0.12
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.11
0.12
0.04
0.06
0.07
0.09
0.10
0.10
0.12
0.13
0.14
0.15
0.06
0.07
0.09
0.10
0.12
0.12
0.14
0.16
0.07
0.09
0.10
0.12
0.13
0.14
0.16
0.19
0.20
0.07
0.09
0.10
0.12
0.13
0.14
0.16
0.19
0.20
0.08
0.11
0.14
0.16
0.19
0.19
0.22
0.24
0.26
0.26
0.11
0.14
0.16
0.19
0.21
0.22
0.26
0.29
0.14
0.16
0.19
0.22
0.24
0.26
0.29
0.32
0.34
0.14
0.16
0.19
0.22
0.24
0.26
0.29
0.32
0.34
55
60
65
For Aluminum Fins Only
*
YORK INTERNATIONAL
22
FORM 100.50-EG1
FILTERS
ECONOMIZER DAMPERS
ECONOMIZER
FRESH AIR
OPENINGS
RIGID FILTER
RACK NO.
MEDIA
POWERED
EXHAUST
12" RIGID
65%*
12" RIGID
95%*
MANUAL OR
0 - 100%
2-POSITION MODULATION
0.05
0.07
0.09
0.11
0.12
0.13
0.15
0.16
0.17
0.17
0.07
0.09
0.11
0.13
0.14
0.15
0.17
0.19
0.09
0.11
0.13
0.15
0.16
0.17
0.19
0.21
0.23
0.09
0.11
0.13
0.15
0.16
0.17
0.19
0.21
0.23
0.21
0.28
0.34
0.42
0.47
0.49
0.58
0.62
0.66
0.68
0.28
0.34
0.42
0.49
0.54
0.58
0.66
0.75
0.34
0.42
0.49
0.58
0.62
0.66
0.75
0.84
0.89
0.34
0.42
0.49
0.58
0.62
0.66
0.75
0.84
0.89
0.30
0.38
0.46
0.55
0.62
0.65
0.74
0.79
0.84
0.87
0.38
0.46
0.55
0.65
0.71
0.74
0.84
0.95
0.46
0.55
0.65
0.74
0.79
0.84
0.95
1.06
1.11
0.46
0.55
0.65
0.74
0.79
0.84
0.95
1.06
1.11
0.07
0.11
0.15
0.20
0.24
0.25
0.31
0.35
0.38
0.40
0.11
0.15
0.20
0.25
0.29
0.31
0.38
0.46
0.15
0.20
0.25
0.31
0.35
0.38
0.46
0.55
0.59
0.15
0.20
0.25
0.31
0.35
0.38
0.46
0.55
0.59
0.05
0.08
0.11
0.14
0.17
0.18
0.22
0.24
0.27
0.28
0.08
0.11
0.14
0.18
0.20
0.22
0.27
0.32
0.11
0.14
0.18
0.22
0.24
0.27
0.32
0.37
0.40
0.11
0.14
0.18
0.22
0.24
0.27
0.32
0.37
0.40
0.11
0.16
0.21
0.26
0.31
0.32
0.39
0.42
0.46
0.48
0.16
0.21
0.26
0.32
0.36
0.39
0.46
0.54
0.21
0.26
0.32
0.39
0.42
0.46
0.54
0.62
0.67
0.21
0.26
0.32
0.39
0.42
0.46
0.54
0.62
0.67
0.08
0.11
0.15
0.20
0.24
0.25
0.31
0.34
0.37
0.39
0.11
0.15
0.20
0.25
0.29
0.31
0.37
0.45
0.15
0.20
0.25
0.31
0.34
0.37
0.45
0.52
0.56
0.15
0.20
0.25
0.31
0.34
0.37
0.45
0.52
0.56
YORK INTERNATIONAL
23
Electrical Data
ELECTRICAL SERVICE SIZING
In order to use the electrical service required for the
cooling only Eco2 rooftop, use the appropriate calcula-
tions listed below from U.L. 1995. Based on the operat-
ing mode and configuration of the rooftop, the calcula-
tions will yield different MCA (minimum circuit ampac-
ity), and MOP (maximum overcurrent protection).
• LOAD3 is the current of the electric heaters – zero
for cooling only units.
• LOAD4 is the sum of any remaining currents
greater than or equal to 1.0 amp
Use the following calculations to determine MCA
and MOP for units supplied with a single-point power
connection:
Using the following load definitions and calculations,
determine the correct electrical sizing for your unit. All
concurrent load conditions must be considered in the
calculations, and you must use the highest value for
any combination of loads.
MCA = (1.25 x LOAD1) + LOAD2 + LOAD4
MOP = (2.25 x LOAD1) + LOAD2 + LOAD4
Load Definitions:
If the MOP does not equal a standard current rating of
an overcurrent protective device, then the marked maxi-
mum rating is to be the next lower standard rating. How-
ever, if the device selected for MOP is less than the
MCA, then select the lowest standard maximum fuse
size greater than or equal to the MCA.
• LOAD1 is the current of the largest motor – com-
pressor or fan motor.
• LOAD2 is the sum of the remaining motor currents
that may run concurrently with LOAD1 (i.e., exhaust
fan motor).
TABLE 9 – COMPRESSORS
COMPRESSOR
NOMINAL VOLTAGE
QUANTITY
208V
230V
RLA*
460V
575V
LRA*
PER
MODEL
MODEL
UNIT
RLA*
54.0
54.0
62.3
62.3
LRA*
265.0
265.0
380.0
380.0
LRA*
265.0
265.0
380.0
380.0
RLA*
24.2
24.2
27.9
27.9
LRA*
135.0
135.0
175.0
175.0
RLA*
19.4
19.4
22.3
22.3
50
55
60
65
4
4
4
4
SZ160
SZ160
SZ185
SZ185
48.8
48.8
56.3
56.3
120.0
120.0
140.0
140.0
* Values shown are per compressor
YORK INTERNATIONAL
24
FORM 100.50-EG1
TABLE 10 – SUPPLY AND EXHAUST FAN MOTOR (ODP OR TEFC)
High Efficiency Premium Efficiency
NOMINAL VOLTAGE
NOMINAL VOLTAGE
MOTOR
HP
208V
230V
FLA
13.4
21.6
28.4
39.0
50.0
60.0
76.0
95.6
460V
FLA
6.7
575V
FLA
5.3
MOTOR
HP
208V
FLA
14.9
22.5
29.2
41.5
55.0
71.0
85.5
109.0
230V
FLA
13.6
20.0
25.8
36.0
48.0
61.0
74.0
96.0
460V
FLA
6.8
575V
FLA
5.5
FLA
14.0
22.2
28.5
44.8
61.0
74.0
87.0
113.0
5.0
5.0
7.5
10.8
14.2
19.5
25.0
30.0
38.0
47.8
8.2
7.5
10.0
12.9
18.0
24.0
30.5
37.0
48.0
7.9
10.0
15.0
20.0
25.0
30.0
40.0
11.4
16.0
20.0
24.2
30.3
38.0
10.0
15.0
20.0
25.0
30.0
40.0
10.3
14.5
19.3
24.5
30.0
38.0
TABLE 11 – CONDENSER FAN MOTORS / EACH
TABLE 12 – CONTROLS AND CONVENIENCE
OUTLET
NOMINAL VOLTAGE
NOMINAL VOLTAGE
NOMINAL
208V
FLA
7.5
230V
FLA
6.8
460V
FLA
3.4
575V
FLA
2.7
208V 230V 460V 575V
DESCRIPTION
TONS
50
AMPS AMPS AMPS AMPS
Control Transformer
Convenience Outlet
3.6
9.6
3.3
8.7
1.6
4.3
3.3
3.5
55
7.5
6.8
3.4
2.7
60
7.5
6.8
3.4
2.7
65
7.5
6.8
3.4
2.7
YORK INTERNATIONAL
25
Controls
CONTROL SEQUENCES FOR ALL UNITS
GENERAL
ECONOMIZER OPERATION
The control system for the YORK eco2 Packaged Roof-
top Unit is fully self-contained and based around an
OptiLogic™ rooftop unit controller. To aid in unit setup,
maintenance, and operation, the OptiLogic™ rooftop
unit controller is equipped with a user interface that is
based around a 4 line x 20 character backlit LCD dis-
play. The LCD displays plain language text in a menu-
driven format to facilitate use. In addition to the display,
the OptiLogic™ user interface is also equipped with an
LED indicator light, which will warn of any abnormal
operation of the equipment or communication failures.
The unit can be equipped with one of three types of
optional economizers, dry bulb, single enthalpy, or com-
parative enthalpy. When the unit controller determines
that Outside Air is suitable for economizing, the unit
controller will control the outside air damper(s) open to
provide economizer cooling. If economizer cooling alone
is insufficient for the cooling load, the unit controller
shall stage up compressors, one at a time, to meet
demand.
The control logic for the three types of economizers is
as follows:
For the maximum in system flexibility, the YORK ECO2
Packaged Rooftop Unit can be operated by either a
typical 7-wire thermostat (2 cool / 2 heat), a space tem-
perature sensor, or stand-alone (VAV only). Note, a field
wiring terminal block is provided to facilitate unit setup
and installation.
Dry Bulb Economizer
The dry bulb economizer is the default economizer con-
trol scheme. With the dry bulb economizer, the unit con-
troller monitors the Outside Air temperature only and
compares it to a reference temperature setting. Outside
Air is deemed suitable for economizing when the Out-
side Air temperature is determined to be less than the
reference temperature setting. This method of econo-
mizing is effective, but is prone to some changeover in-
efficiencies due to the fact that this method is based on
sensible temperatures only and does not take Outside
Air moisture content into consideration.
In lieu of the hard-wired control options, the OptiLogic™
rooftop unit controller can be connected to and oper-
ated by a Building Automation System (BAS). If re-
quired, the OptiLogic™ rooftop unit controller can be
equipped with an optional BACNet IP communication
card, which allows communication, via Ethernet, to a
BACNet IP based BAS.
Single Enthalpy Economizer
UNOCCUPIED / OCCUPIED SWITCHING
With the optional single enthalpy economizer, the unit
controller monitors the Outside Air enthalpy in addition
to the Outside Air temperature and compares it to a
reference enthalpy setting and a reference tempera-
ture setting. Outside Air is deemed suitable for econo-
mizing when the Outside Air enthalpy is determined to
be less than the reference enthalpy setting and the Out-
side Air temperature is less than the reference tem-
perature setting. This method of economizing allows
the reference temperature setting to be set higher than
the DB Economizer and is consequently a more effi-
cient packaged rooftop economizer.
Depending on application, the unit can be indexed be-
tween unoccupied and occupied modes of operation
by one of three methods, hard-wired input, internal time
clock, or BAS. A contact-closure input is provided for
hard-wiring to an external indexing device such as a
central time clock, thermostat with built in scheduling,
or a manual switch. The unit controller is also equipped
with a built in 7-day time clock which can be used, in
lieu of the contact closure input, to switch the unit be-
tween Unoccupied and Occupied modes of operation.
The internal time clock is fully configurable via the user
interface and includes Holiday scheduling. In addition
to the hard-wired input or the internal time clock, the
unit can also be indexed between unoccupied and oc-
cupied modes of operation via a BAS command.
Comparative Enthalpy Economizer
With the optional comparative enthalpy economizer, the
unit controller monitors and compares the Outside Air
and Return Air enthalpies in addition to comparing the
Outside Air temperature to the reference temperature
setting. Outside Air is deemed suitable for economiz-
ing when the Outside Air enthalpy is determined to be
Note a unit operated from a space sensor can be
equipped to temporarily override an unoccupied mode
of operation. This Unoccupied Override feature is fully
configurable via the OptiLogic™ user interface.
YORK INTERNATIONAL
26
FORM 100.50-EG1
less than the Return Air enthalpy and the Outside Air
temperature is less than the reference temperature set-
ting. This method of economizing is the most accurate
and provides the highest degree of energy efficiency
for a packaged rooftop economizer.
Demand Ventilation
If an optional CO2 sensor is connected to the unit, the
unit controller can reset the minimum OA damper
position(s) or minimum flow rate based on demand.
The unit controller shall monitor the CO2 level within the
building. If the CO2 level rises above the CO2 setpoint,
the controller will temporarily increase the Minimum OA
Damper Position or Minimum OA flow rate to increase
ventilation. If the CO2 level drops below the CO2 set-
point, the controller will decrease the Minimum OA
Damper Position or Minimum OA flow rate to decrease
ventilation.
VENTILATION CONTROL SEQUENCES
Minimum OA Damper Position (CV Units)
When the unit goes into the Occupied mode of opera-
tion, the unit controller shall open the Outside Air
Damper to a fixed minimum position. The damper shall
remain at this position as long as the unit is in the occu-
pied mode. The minimum position may be overridden
more open by the unit controller when Outside Air con-
ditions are suitable for economizing.
Demand Ventilation shall remain active as long as the
unit is in the Occupied mode of operation.
Minimum OA Damper Position (VAV Units)
EXHAUST CONTROL SEQUENCES
Barometric
With Variable Air Volume units, there are two Minimum
OA Damper Positions, one when the unit is at full speed
and the second when the unit is at approximately half
speed. These two points allow the control to linearly
reset the position of the OA damper in response to fan
speed.
The optional barometric exhaust system consists of a
lightweight barometric relief damper installed on the end
of the unit in the Return Air section. As more outside air
is introduced into the controlled zone due to Econo-
mizer and Ventilation control sequences, the pressure
inside the building rises. This increase in building pres-
sure forces the barometric relief damper open to allow
exhaust air to escape. Because this type of exhaust
system is not powered, it is limited to small amounts of
exhaust.
When the unit goes into the Occupied mode of opera-
tion, the unit controller shall monitor the speed of the
supply fan and open the Outside Air damper to a calcu-
lated minimum position based on the fan speed. This
minimum position shall vary as the speed of the fan
changes. The damper shall remain at this calculated
position as long as the unit is in the occupied mode.
The minimum position may be overridden more open
by the unit controller when Outside Air conditions are
suitable for economizing.
Powered Fixed Volume Exhaust Based on
Outside Air Damper Position
This optional fixed volume powered exhaust system
consists of a fixed speed fan that is controlled ON and
OFF based on the position of the Outside Air Damper.
During operation, when the Outside Air Damper opens
to a selected turn-on point, the Exhaust Fan is cycled
ON. The fan remains on as long as the Outside Air
damper is above a selected turn-off point. If the Out-
side Air Damper closes to the selected turn-off point,
the Exhaust Fan is cycled OFF. The turn-on and turn-
off points are user selectable from the OptiLogic™ User
Interface panel.
Air Measurement Stations
When the unit is equipped with an air measurement
station, the unit controller shall control the Outside Air
damper to a measured flow rate through the Air Mea-
surement Station.
When the unit goes into the Occupied mode of opera-
tion, the unit controller shall control the Outside Air
damper to maintain the Minimum AirFlow Setpoint
through the Air Measurement Station. The unit control-
ler shall control the Outside Air damper to this flow rate
as long as the unit is in the Occupied mode. The Out-
side Air damper may be overridden more open by the
unit controller when Outside Air conditions are suitable
for economizing.
Powered Fixed Volume Exhaust Based on
Building Pressure
This optional fixed volume powered exhaust system
consists of a fixed speed fan that is controlled ON and
OFF based on the pressure inside the building. During
YORK INTERNATIONAL
27
Controls (continued)
operation, the pressure within the building in monitored
by the OptiLogic™ controller. If the pressure rises to or
above a selected turn-on pressure, the Exhaust Fan is
cycled ON. The fan shall remain on as long as the pres-
sure within the building remains above a selected turn-
off pressure. If the building pressure falls to or below
the selected turn-off pressure, the Exhaust Fan is cycled
OFF. The turn-on and turn-off pressure setpoints are
user selectable from the OptiLogic™ User Interface.
For these applications, the unit can be equipped with
optional Low Ambient controls. For optional Low Ambi-
ent operation, the OptiLogic™ controller monitors the
refrigeration system discharge pressure and controls
the speed of the condenser fans. If the discharge pres-
sure falls, the speeds of the condenser fans are re-
duced to maintain acceptable condensing pressures in
the refrigeration system. With the optional Low Ambi-
ent controls, mechanical cooling is allowed down to
Outside Air temperatures of 0°F.
Powered Variable Volume Exhaust-Discharge
Damper Controlled
SMOKE PURGE SEQUENCES
General
This optional variable volume powered exhaust system
consists of a fixed speed fan configured with a propor-
tionally controlled discharge damper. The OptiLogic™
controller monitors the pressure inside the building and
controls the Exhaust Damper and the Exhaust Fan. If
the Building Pressure rises, the Exhaust Damper is pro-
portionally controlled open and the Exhaust Fan is con-
trolled ON. If the Building Pressure falls, the Exhaust
Damper is proportionally controlled closed and the Ex-
haust Fan is controlled OFF. The position of the Ex-
haust Damper in which the Exhaust Fan is controlled
ON and OFF as well as the Building Pressure setpoint
is user selectable from the OptiLogic™ User Interface.
As a convenience, for when buildings catch fire or the
building is inundated with smoke or fumes from manu-
facturing processes, etc., the OptiLogic™ control sys-
tem provides one of five ventilation override control se-
quences for building purge. The five selectable purge
sequences are, Shutdown, Pressurization, Exhaust,
Purge and Purge with duct pressure control. Note, when
any of the purge sequences are activated, cooling and
heating modes are disabled. A contact closure is pro-
vided which indexes the OptiLogic™ controller into the
selected purge sequence.
Powered Variable Volume Exhaust-VFD
Controlled
Shutdown
When this purge sequence is selected and activated,
the supply and exhaust fans are controlled OFF and
the Outside Air damper is overridden closed. This idle
state is maintained until the purge input is deactivated
and the unit returns to normal operation.
This optional variable volume powered exhaust system
consist of an Exhaust Fan driven by a Variable Fre-
quency Drive (VFD), which is controlled by the
OptiLogic™ controller. The OptiLogic™ controller moni-
tors the pressure within the building. As the pressure
rises, the VFD is controlled to increase Exhaust Fan
speed. As the pressure falls, the VFD is controlled to
decrease Exhaust Fan speed. The Building Pressure
Setpoint is user selectable from the OptiLogic™ User
Interface.
Pressurization
When this purge sequence is selected and activated,
the exhaust fan is controlled OFF and the Supply Fan
is controlled ON. The Outside Air damper is opened
full and the Return Air Damper is closed full. If the unit
is a VAV unit, the VAV boxes are also driven full open to
prevent duct over-pressurization. This mode is main-
tained until the smoke purge input is deactivated and
the unit returns to normal operation.
LOW AMBIENT OPERATION
The OptiLogic™ controller continuously monitors the
outside air temperature to determine if mechanical cool-
ing should be allowed. As a safety, if the Outside Air
temperature falls to or below the Low Ambient Lockout
temperature, mechanical cooling is prevented from op-
erating. For units with economizers, the Low Ambient
Lockout temperature is typically low enough that me-
chanical cooling will rarely be required. However, for
some applications mechanical cooling is required when
the Outside Air temperature is lower than the Low Am-
bient Lockout temperature.
Exhaust
When this purge sequence is selected and activated,
the Supply Fan is controlled OFF and the Exhaust Fan
is controlled ON (Exhaust Damper driven full open).
This mode is maintained until the smoke purge input is
deactivated and the unit returns to normal operation.
YORK INTERNATIONAL
28
FORM 100.50-EG1
Purge
When a Cooling Stage 1 call (“Y1”) is received, and the
unit is equipped with an economizer, the OptiLogic™
controller will check the Outside Air conditions to de-
termine if conditions are suitable for economizing and
modulate the outside air damper and or stage up com-
pressors as required to maintain the VAV High Supply
Air Temperature Setpoint. This setpoint is user select-
able at the OptiLogic™ User Interface. The OptiLogic™
controller will control to this setpoint as long as Cooling
Stage 1 (“Y1”) remains active.
When this purge sequence is selected and activated,
the Supply Fan is controlled ON and the Exhaust Fan
is controlled ON. The Outside Air damper is opened
full and the Return Air damper is closed full. If the unit
is a VAV unit, the VAV boxes are also driven full open to
prevent duct over-pressurization. This mode is main-
tained until the smoke purge input is deactivated and
the unit returns to normal operation.
Purge With Duct Pressure Control (VAV Only)
When a Cooling Stage 2 call (“Y2”) is received, and the
unit is equipped with an economizer, the OptiLogic™
controller will check the Outside Air conditions to de-
termine if conditions are suitable for economizing and
modulate the outside air damper and or stage up com-
pressors as required to maintain the VAV Low Supply
Air Temperature Setpoint. This setpoint is user select-
able at the OptiLogic™ User Interface. The OptiLogic™
controller will control to this setpoint as long as Cooling
Stage 2 (“Y2”) remains active.
When this purge sequence is selected and activated,
the Supply Fan is cycled ON and controlled to maintain
the duct static pressure setpoint. The Exhaust Fan is
also controlled ON (Exhaust Damper driven full open)
and the Outside Air Damper is driven full open. This
mode is maintained until the smoke purge input is de-
activated and the unit returns to normal operation.
VAV SPECIFIC SEQUENCES
Supply fan operation
The VAV High SAT Setpoint is always greater than the
VAV Low SAT Setpoint and because of this essentially
makes this control sequence a Supply Air Tempera-
ture Reset algorithm based on Zone Temperature.
For VAV units, the supply fan is controlled ON and OFF
based on the occupancy state or the G input from a
Thermostat (Unit must be configured for Thermostat
operation to respond to the G input). When the unit
goes into the Occupied mode of operation (or “G” is
called) the Supply Fan will be controlled ON. The
OptiLogic™ controller will monitor the static pressure
within the supply duct system and control the speed of
the supply fan to maintain a specified Duct Static Pres-
sure setpoint. A Variable Frequency Drive (VFD) is used
on all VAV units to vary the speed of the supply fan.
Note, the use of a VFD in lieu of inlet guide vanes pro-
vides for higher energy efficiency for the unit by elimi-
nating the losses (air pressure drop) typical of inlet guide
vane systems.
Zone Sensor Control
When a VAV unit is configured for Zone Sensor opera-
tion, the OptiLogic™ controller will monitor a reference
Zone Temperature and command the Supply Fan to
start when the unit goes into the Occupied mode.
If the zone temperature is above the VAV Setpoint for
SAT Reset, the OptiLogic™ controller will modulate the
outside air damper (Economizer available and condi-
tions suitable) and/or stage compressors up and down,
as required, to maintain the VAV High Supply Air Tem-
perature Setpoint.
If the zone temperature is below or falls below the VAV
Setpoint for SAT Reset, the OptiLogic™ controller will
modulate the Outside Air Damper (Economizer avail-
able and conditions suitable) and/or stage compres-
sors up and down, as required, to maintain the VAV
Low Supply Air Temperature Setpoint.
COOLING OPERATION
Thermostat Control
When a VAV unit is configured for thermostat opera-
tion, the OptiLogic™ controller will command the Sup-
ply Fan to start when the unit goes into the Occupied
mode or a thermostat “G” signal is received by the con-
trol. With no thermostat calls for cooling, the unit shall
remain idle with the Supply Fan operating as required.
As with thermostat operation, this sequence is also a
Supply Air Temperature Reset algorithm based on Zone
Temperature.
YORK INTERNATIONAL
29
Controls (continued)
Stand Alone Control
SAT setpoint. If conditions are not suitable for econo-
mizing or not equipped with an economizer, the control
will stage up 50% of the compressors. This shall be
maintained until Stage 1 is deactivated or Stage 2 is
called.
If the unit is not configured for Thermostat or Zone Sen-
sor operation, the unit will operate in Stand Alone Mode.
In Stand Alone Mode, the OptiLogic™ Controller will
monitor only the Occupied/Unoccupied state. When the
unit is commanded into the Occupied Mode of opera-
tion, the OptiLogic™ Controller will start the Supply Fan.
If the unit is equipped with an Economizer, the Control-
ler will check to see if Outside Air conditions are suit-
able for Economizing. The controller will then use Out-
side Air (when available and suitable) and/or stage com-
pressors up and down, as required, to maintain the VAV
Low SAT Setpoint.
Stage 2 (“Y2”) Call
If Y2 is called and the unit is equipped with an econo-
mizer, the control will check to see if the Outside Air is
suitable for economizing. If conditions are suitable for
economizing, the control will control the economizer and
stage up compressors, as required, to maintain a LOW
SAT setpoint. If conditions are not suitable for econo-
mizing or not equipped with an economizer, the control
will stage up 100% of the compressors. This shall be
maintained until Stage 2 is deactivated.
CV SPECIFIC SEQUENCES
Zone Sensor Control
Cooling Operation
Thermostat Control
If a zone sensor controls the unit, the OptiLogic™ con-
troller shall maintain all zone temperature setpoints.
These setpoints are user selectable at the OptiLogic™
User Interface.
If a 7-wire thermostat (2 Cool/2Heat) controls the unit,
all zone temperature setpoint control is maintained at
the thermostat. With this operation, the unit remains
idle until it receives a stage call from the Thermostat. If
“G” is called from the thermostat, the Supply Fan will
start and all occupied functions (if equipped), i.e. venti-
lation, economizer, etc. will be allowed to operate.
When a zone sensor is used for control, the OptiLogic™
unit controller will monitor the temperature within the
space and control the unit accordingly. A closed-loop
staging algorithm is used to stage compressors up and
down as required to maintain the desired zone tempera-
ture setpoint. If the unit is equipped with an economizer,
Outside Air conditions are continuously monitored by the
control to determine if conditions are suitable for econo-
mizing. If conditions are suitable for economizing, the
OptiLogic™ controller will modulate the Outside Air
damper in addition to staging compressors up and down
to maintain the zone temperature setpoint.
Stage 1 (“Y1”) Call
If Y1 is called and the unit is equipped with an econo-
mizer, the control will check to see if the Outside Air is
suitable for economizing. If conditions are suitable for
economizing, the control will control the economizer and
stage up compressors, as required, to maintain a high
YORK INTERNATIONAL
30
FORM 100.50-EG1
Power Wiring
SINGLE-POINT POWER SUPPLY WIRING
TB1
Wiring Terminal
Block
LD06414
Line 1
Line 2
Line 3
Field Power
Supply
Earth
Ground
NOTES:
1. All field wiring must be provided through a field-supplied fused disconnect switch to the unit terminals (or optional molded
disconnect switch).
2. All electrical wiring must be made in accordance with all N.E.C. and/or local code requirements.
3. Minimum Circuit Ampacity (MCA) is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440.34).
4. Maximum Dual Element Fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440.22)
5. Use copper conductors only.
6. On units with an optional disconnect switch, the supplied disconnect switch is a “Disconnecting Means” as defined in the N.E.C. Section
100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect
switch is not intended to be a Load Break Device.
FIG. 2 – SINGLE-POINT POWER SUPPLY WIRING
YORK INTERNATIONAL
31
Power Wiring (continued)
SINGLE-POINT POWER SUPPLY WIRING
WITH NON-FUSED DISCONNECT
Electrical / Controls Box
Molded
Case
Disconnect
Switch
Wiring Terminal
Block
LD06415
Line 1
Line 2
Line 3
Field Power
Supply
Earth
Ground
NOTES:
1. All field wiring must be provided through a field-supplied fused disconnect switch to the unit terminals (or optional molded
disconnect switch).
2. All electrical wiring must be made in accordance with all N.E.C. and/or local code requirements.
3. Minimum Circuit Ampacity (MCA) is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440.34).
4. Maximum Dual Element Fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440.22)
5. Use copper conductors only.
6. On units with an optional disconnect switch, the supplied disconnect switch is a “Disconnecting Means” as defined in the N.E.C. Section
100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect
switch is not intended to be a Load Break Device.
FIG. 3 – SINGLE-POINT POWER SUPPLY WIRING WITH NON-FUSED DISCONNECT
YORK INTERNATIONAL
32
FORM 100.50-EG1
DUAL-POINT POWER SUPPLY WIRING
Wiring Terminal
Block
LD06416
Line 1
Line 2
Line 3
Field Power
Supply #2
Earth
Ground
Line 1
Line 2
Line 3
Field Power
Supply #1
Earth
Ground
NOTES:
1. All field wiring must be provided through a field-supplied fused disconnect switch to the unit terminals (or optional molded
disconnect switch).
2. All electrical wiring must be made in accordance with all N.E.C. and/or local code requirements.
3. Minimum Circuit Ampacity (MCA) is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440.34).
4. Maximum Dual Element Fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440.22)
5. Use copper conductors only.
6. On units with an optional disconnect switch, the supplied disconnect switch is a “Disconnecting Means” as defined in the N.E.C. Section
100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect
switch is not intended to be a Load Break Device.
FIG. 4 – DUAL-POINT POWER SUPPLY WIRING
YORK INTERNATIONAL
33
Field Control Wiring
Wiring Notes:
1. Wiring shown indicates typical wiring.
2. All wiring is Class 2, low voltage.
3. Maximum power available from the 24 VAC
terminal is 40 VA.
4. Use shielded wire where shown.
1
2
3
4
5
6
7
8
9 10 11 12
14 15 16 17 18 19 20 21
13
7 Wire Thermostat
COMMON
R (24VAC)
Y1 (Cool Stage 1)
Y2 (Cool Stage 2)
G (Fan)
Space Sensor
* Use Shielded Wire
* Use Shielded Wire
1K Nickel
Signal
Common
RTD Sensor
Signal
1.5K Adjust
Common
Potentiometer
CO2 Sensor
* Use Shielded Wire
Signal
0-5V Output
Common
Note, 24VAC switch voltage must be
sourced from the unit. Use of another
power source external of the unit may
cause equipment damage.
Closed = Occupied
Open = Unoccupied
Occupied /
Unoccupied Input
Closed = Shutdown
Open = Normal
Shutdown Input
Closed = Smoke Purge
Open = Normal
Smoke Purge Input
24 VAC Signal
VAV Heat
Relay Output
Common
Note: VAV Heat Relay
output shall be used to
command the VAV boxes
to open full.
LD06158
FIG. 5 – FIELD CONTROL WIRING
YORK INTERNATIONAL
34
GeneralArrangementDrawing
TOP VIEW
SUPPLY OPENING
RETURN OPENING
53"
106-7/16"
40"
5-3/4"
SECTION DESCRIPTIONS
31-7/8"
36-7/8"
35-3/4"
EE = Economizer
FE = Fan Exhaust
MB = Mixing Box
CONTROL PANEL DETAIL
_F = Filter Segment
CC = Cooling Coils
FS = Supply Fan
DP = Discharge Plenum
CO = Condenser Section
CP = Control Panel
I R
A
F
L
OW
10'
CP
72"
FRONT
72"
SIDE
72"
REAR
72"
SIDE
1-1/2" FPT
FRONT VIEW
16-1/16"
REAR VIEW
COUPLING
DRAIN CONN.
179"
SIDE VIEW
(LEFT SIDE)
(LEFT SIDE)
7-3/16"
24-5/16"
236-1/16"
95-1/4"
(SEE NOTE 6)
344"
92-3/16"
1-9/16"
140-3/4"
379-9/16"
NOTES:
1. 10' CLEARANCE MINIMAL OVER THE TOP OF THE CONDENSING UNIT.
2. ONLY ONE ADJACENT WALL CAN EXCEED UNIT HEIGHT.
3. 12' CLEARANCE REQUIRED TO ADJACENT UNITS.
4. 8' SERVICE ACCESS RECOMMENDED ON ONE SIDE.
5. ECONOMIZER AND EXHAUST HOODS, WHERE APPLICABLE, ARE FOLDED
INSIDE UNIT FOR SHIPMENT.
6. DIM. IS TO OUTSIDE OF LIFTING LUGS
FIG. 6 – GENERAL ARRANGEMENT DRAWING
LD06417
GeneralArrangementDrawing
NOTES:
1. 10' CLEARANCE MINIMAL OVER THE TOP OF THE CONDENSING UNIT.
2. ONLY ONE ADJACENT WALL CAN EXCEED UNIT HEIGHT.
3. 12' CLEARANCE REQUIRED TO ADJACENT UNITS.
4. 8' SERVICE ACCESS RECOMMENDED ON ONE SIDE.
5. ECONOMIZER AND EXHAUST HOODS, WHERE APPLICABLE, ARE FOLDED
INSIDE UNIT FOR SHIPMENT.
TOP VIEW
53"
31-7/8"
36-7/8"
CONTROL PANEL DETAIL
SECTION DESCRIPTIONS
EE = Economizer
FE = Fan Exhaust
MB = Mixing Box
_F = Filter Segment
CC = Cooling Coils
FS = Supply Fan
DP = Discharge Plenum
CO = Condenser Section
CP = Control Panel
SUPPLY
OPENING
I
A
RETURN
OPENING
C
(continued)
FRONT VIEW
EE
FE
16-1/16"
24-5/16"
95-1/4"
(SEE NOTE 6)
117-7/16"
28-1/2"
140-3/4"
REAR VIEW
79-1/8"
SIDE VIEW
(LEFT SIDE)
6-1/2"
LD06418
FIG. 7 – GENERAL ARRANGEMENT DRAWING
CurbLayoutDrawing
87"
RETURN
237"
339"
35-3/4"
71-3/5"
52"
Y
SUPPL
53-3/4"
40"
NOTES:
1. CURB, NAILER & GASKET ONLY, FURNISHED BY YORK. ALL
OTHER PARTS ARE FURNISHED AND INSTALLED "BY OTHERS".
2. ROOF CURB SHIPPED IN PIECES FOR FIELD ASSEMBLY.
3. ROOF CURB MUST BE INSTALLED SQUARE AND LEVEL.
4. CURB MATERIAL IS 14 GAUGE GALVANIZED, NOT PAINTED.
5. CURB INSULATED WITH 1.5"-3# INSULATION.
LD06419
FIG. 8 – CURB LAYOUT DRAWING
Guide Specifications
GENERAL
doors shall be a minimum of 18 gauge on the exterior
surfaces, and 20 gauge on the interior. Interior floor
panels shall be 18 gauge.
Units shall be designed for outdoor rooftop installation
on a roof curb. Units shall be rated according to ARI
360. Units shall be shipped in a single package, fully
charged with HFC-407C refrigerant. The manufactur-
ing facility shall be registered under ISO 9001 Quality
Standards for Manufacturing. All units shall be com-
pletely factory assembled and run tested.
All serviceable sections shall have hinged access doors
with latches on both sides of the unit. All access doors
shall be constructed of 20-gauge steel on the outside,
with 24 gauge on the inside. Each door shall seal against
PVC gaskets to prevent air and water leakage.
Units shall be ETL listed and be tested according to UL
1995. Tags and decals to aid in the service or indicate
caution areas shall be provided. Installation, operation
and maintenance manuals shall be supplied with each
unit.
The roof shall be double wall, with 18 gauge on the
external surface and 24 gauge on the interior. The roof
shall be formed with a 45 degree “drip lip” overhanging
the side walls to prevent precipitation drainage from
streaming down the side of the unit. Roof sections shall
be connected together via integral channels fastened
with screws and sealed with gasketing. Each fastened
seam shall be further protected by a sheet metal chan-
nel covering the full length of the gasket surface, mak-
ing a completely water tight seal.
Units shall be capable of providing mechanical cooling
down to 45° F (0°F with a low ambient kit). Unit shall be
capable of starting and running at 120° F. Unit electric
and gas connections shall be either through the curb or
the side of the unit.
SUPPLY AIR SYSTEM
Supply Air Fan
CONSTRUCTION
Base
Fans shall be centrifugal type, statically and dynami-
cally balanced in the factory. Fan wheels shall be de-
signed for continuous operation at the maximum rate
of fan speed and motor HP. Fans shall be double-width,
double-inlet with forward curved blades.
The base rail shall be constructed of 12 gauge galva-
nized steel, extending the full perimeter of the unit. All
components shall be supported from the base, and the
base shall include integral lifting lugs. The unit base
rail shall overhang the roof curb for water runoff and
shall have a fabricated recess with a continuous flat
surface to seat on the roof curb gasket, providing a
positive, weather tight seal between the unit and the
curb.
The fan and motor assembly shall be mounted on a
common base to allow consistent belt tension with no
relative motion between the fan and motor shafts. The
entire assembly shall be isolated from the unit base
with 1" deflection springs. The fan discharge shall be
connected to the cabinet through a reinforced neoprene
flexible connection to eliminate vibration transmission
from the fan to the unit casing.
Casing
The unit cabinet shall be double wall construction to
provide both maximum resistance to bacterial growth
in the air stream and superior structural integrity. All
sheet metal shall be G90 mill galvanized sheet metal,
formed and reinforced to provide a rigid assembly. Cabi-
net shall be coated with baked on powder paint which,
when subject to ASTM B117, 500 hour, 5% salt spray
test, yields minimum ASTM 1654 rating of “6”. The unit
shall be insulated with 1-1/2,” 1 pound fiberglass insu-
lation between the two sheet metal skins. Insulation shall
meet NFPA-90A regulations for smoke and flame
spread ratings. Single-wall units, or foil-faced insula-
tion in the air stream shall be not acceptable.
BEARINGS AND DRIVES
Bearings shall be self-aligning pillow-block re-greasable
ball bearings with an average life expectancy L10 of
40,000 hours. Grease fittings shall be accessible
through access doors.
Fan motors shall be NEMA designed, Standard effi-
ciency ball bearing type with electrical characteristics
and horsepower as specified. Motors shall be 1750
RPM, open drip proof type. The motor shall be located
within the unit on an adjustable, heavy steel base.
The cabinet corner post and the intermediate side sup-
ports shall be a minimum of 16-gauge steel. All access
YORK INTERNATIONAL
38
FORM 100.50-EG1
densate drain opening shall be flush with the bottom of
the drain pan to allow complete drainage. Coils in ex-
cess of 48” high shall have an intermediate drain pan,
extending the entire width of the coil to provide better
water drainage.
All fan motor drives shall be selected for a minimum
service factor of 1.2 and have fixed pitched sheaves.
AIR FILTERING SYSTEM
All filter holding frames shall be of heavy-duty construc-
tion designed for industrial applications. All filters shall
be either side accessible via access doors on both sides
of the filter section.
Compressors
Compressors shall be hermetic, scroll-type, including
tip seals to provide efficient axial sealing while prevent-
ing scroll tip to base contact, controlled orbit design for
radial sealing to incorporate minimum flank-to-flank con-
tact for long service life, refrigerant cooled motors, large
suction side free volume and oil sump to provide liquid
handling capability, annular discharge check valve and
reverse vent assembly to provide low pressure drop,
silent shutdown and reverse rotation protection, initial
oil charge, oil level sight glass, vibration isolator mounts
for compressors, and brazed-type connections for fully
hermetic refrigerant circuits.
All filter media shall be Class II listed under UL Stan-
dard 900. Filter efficiencies shall be rated in accordance
with ASHRAE Standard 52-76
Two-inch throwaway filters in an angled filter rack shall
be standard. On units with rigid filters, two-inch prefilters
shall be installed upstream of the rigid filters.
AIR INLET SYSTEM
General
Condenser Coils
Condenser coils shall have 3/8” seamless copper tubes,
arranged in staggered rows, mechanically expanded into
aluminum fins. Coils shall be protected from hail dam-
age with a “V” configuration, with individual flat coils ro-
tated from the vertical plane for each condensing circuit.
A factory installed outside air rain hood permanently
attached to the cabinet to prevent windblown precipita-
tion from entering the unit shall cover inlet openings.
The rain hoods on the sides of the unit shall be rotated
into the cabinet and secured for shipment so that upon
installation they need only be rotated upwards and
screwed into place. The outside air hood shall contain
a removable and cleanable filter.
Condenser Fans and Motors
Condenser fans shall be direct drive, propeller type,
discharging vertically. Condenser fan motors shall be
3-phase, totally enclosed air over (TEAO). Thermal
overload protection shall be provided for each con-
denser fan motor.
All damper assemblies shall be of low leak design.
Damper blades shall be fabricated from a minimum of
16 gauge galvanized steel.
Refrigerant Piping
REFRIGERATION SYSTEM
All interconnecting piping between refrigeration com-
ponents shall be copper tubing with brazed joints.
Units shall have four compressors for maximum load-
matching capability. Each refrigerant circuit shall be
controlled with a thermal expansion valve for maximum
control at low load conditions.
Each refrigerant circuit shall be equipped with liquid line
filter drier, and moisture indicating sight glass. Each
circuit shall also have both high and low pressure
switches installed on either side of the compressor and
include access fittings for replacement of the pressure
switches without removing charge.
Evaporator Coils
Evaporator coils shall be direct expansion. Coil tubes
shall be 3/8” OD copper, with internally enhanced tubes.
Fins shall be enhanced aluminum mechanically ex-
panded to bond with the copper tubes. Coil casing shall
be fabricated from heavy gauge galvanized steel.
Polyurethane sleeves shall protect all small diameter
distributor tubing to the evaporator coil to prevent the
tubes from copper-to-copper contact during shipment
or operation.
A stainless steel double-sloped drain pan shall be pro-
vided under the entire width of the evaporator coil, in-
cluding all return bends. The main drain pan shall be
sloped a total of 1/4” per foot towards the drainage point
according to ASHRAE 62 guidelines. Main drain pan
shall be accessible and cleanable in the field. The con-
POWER SUPPLY
Unit power supply shall be 460V 3-phase 60Hz (208,
230 and 575V optional) single-point power connections
with terminal block connections.
YORK INTERNATIONAL
39
Guide Specifications (continued)
CONTROLS
ACCESSORIES AND OPTIONS
A factory-mounted unit controller with a 4x20 character
alphanumeric display and user keypad shall be included
as standard. The controller and keypad shall be housed
inside the low-voltage compartment of the control/power
panel. On units with supply or exhaust VFDs, the VFD
keypads shall be located inside the same panel as the
unit controller and interface keypad. Control operating
data, setpoints, unit setup, configuration, service and
history shall all be accessible via a single key. A sys-
tem alarm LED shall indicate failures to the operator
with more detail provide in the menu screens. The user
interface shall function with a simple menu-driven dis-
play for easy access to unit data with integral time clock
for weekly and holiday scheduling. The unit keypad
shall include password protection to prevent unautho-
rized access and tampering with unit setpoints and con-
figuration.
Full perimeter and partial perimeter roof curbs - 14”
high roof curb with wood nailer. Roof curb covers the
entire perimeter of the unit (full curb) or that portion of
the unit that has airflow (partial curb).
Supply Fan VFD Manual Bypass – provides full air-
flow in the event of a VFD failure.
Power Supply Connections – single-point power with
manual disconnect, and dual-point power wiring options
are available for various applications.
Supply air setpoint reset by outside air or space air
temperature - Allows VAV supply air setpoint to float
upward (saving energy) if the outdoor air temperature
or the space temperature is sufficiently low.
A single terminal strip shall be provided for all thermo-
stat and customer hard-wired field connections.
Supply Fan Isolation – the entire supply fan assem-
bly shall be isolated from the unit base with 2" deflec-
tion springs.
Unit controls shall be completely factory packaged and
compatible with a room thermostat. Constant volume
units shall operate with a two (2) cool/two (2) heat ther-
mostat. Staging decisions shall be based upon the de-
viation of space temperature from set point and the rate
of change of the space temperature.
Supply and Exhaust Fan Motors – high efficiency
ODP, and standard and high efficiency TEFC motors
are available all meeting the Energy Policy Act of 1992
(EPACT).
VAV units shall operate with a sensor in the supply air
stream for cooling operation. Staging decisions shall
be based upon the deviation of supply air temperature
from set point and the rate of change of the supply air
temperature.
Low Ambient Operation – a low ambient kit is avail-
able to control compressor head pressure via VFD con-
denser fan speed control. Head pressure control is
accomplished by monitoring head pressure with suc-
tion and discharge line pressure transducers rather than
less accurate temperature control.
Controllers shall have the following safeties (both VAV
and CV):
ECONOMIZERS
• High and low pressure cut-outs (one each refriger-
ant circuit)
• Minimum on time for compressors
Manual Damper Economizer – economizer is avail-
able with a manual damper adjustable between 0-25
percent.
• Delay between compressor stages
• Anti-short cycle delays (minimum off time) for com-
pressors and supply fan
Two-Position Damper Economizer – economizer is
available with a two-position damper with the open po-
sition adjustable between 0-25 percent. The operation
of the two-position economizer shall be based on oc-
cupancy; occupied is open, unoccupied is closed.
• Cooling lockout at 40° F; 0° F if equipped for low
ambient operation
• Air flow proving switch requiring proper air flow for
cooling operation
YORK INTERNATIONAL
40
FORM 100.50-EG1
Modulating Damper Economizer – economizer is
available with a modulating damper arrangements.
Modulating damper economizers shall have outdoor air
and return air dampers that are interlocked and posi-
tioned by fully modulating, solid state damper actua-
tors. The actuators shall be spring loaded so that the
outside air damper will close when power to the unit is
interrupted. The operation of the modulating economizer
shall be fully integrated into the cooling control system.
The modulating economizer control shall be via a dry
bulb sensor, single or dual enthalpy sensors.
EVAPORATOR COIL PROTECTION
Copper Fins – provided in lieu of aluminum fins.
Pre-Coated Fins – an epoxy-coated aluminum fin stock
to guard from corrosive agents and insulate against gal-
vanic potential. Used for mild seashore or industrial
locations.
CONDENSER COIL PROTECTION
Copper Fins – provided in lieu of aluminum fins.
Airflow Measurement – airflow measurement is avail-
able for the Modulating Damper Economizer option
listed above. Three options exist for airflow measure-
ment; minimum airflow and 100% air flow. Minimum
airflow measures airflow between 0 and the minimum
ventilation airflow up to 25% outside air. 100% airflow
measurement measures air flow from 0-100% of the
outside airflow.
Pre-Coated Fins – an epoxy-coated aluminum fin stock
to guard from corrosive agents and insulate against gal-
vanic potential. Used for mild seashore or industrial
locations.
Post-Coated Fins – Technicoat coil-coating process
used on condenser coils for seashore and other corro-
sive applications (with the exception of strong alkalis,
oxidizers, wet bromide, chlorine and fluorine in concen-
trations greater than 100ppm).
RELIEF SYSTEM
Barometric Relief - building air exhaust shall be ac-
complished through barometric relief dampers installed
in the return air plenum. The dampers will open relative
to the building pressure.
Hot Gas Bypass (Optional on Constant Volume;
Standard on VAV) – permits continuous, stable opera-
tion at capacities below the minimum step of unloading
by introducing an artificial load on the evaporator.
Exhaust Air Fans - two (2) forward curved centrifugal
fans shall be installed in the return air plenum for posi-
tive power exhaust. Fan impellers shall be on a com-
mon shaft, driven by a single motor. The fans, motors
and drives shall be of the same quality and design as
specified for the supply air fan, except the fans shall be
Class I. Exhaust control options are on/off, modulating
discharge damper, or VFD fan speed control. On units
with non-modulating exhaust a barometric relief damper
is included to prevent outside air from entering in the
off cycle. Fans shall cycle on and off with building pres-
sure. On units with modulating exhaust and two posi-
tion control based on building pressure, a field-installed
static pressure sensor mounted in the conditioned
space or return air duct is required for damper and VFD
modulation.
BACNet Communications Card – for BAS commu-
nications, a BACNet card is available with Ethernet
connection.
Compressor Sound Blankets – compressor acoustic
sound blankets for sound sensitive applications.
CO2 Sensors – carbon dioxide sensors for occupied
space that operate demand ventilation control opening
outside air dampers to ventilate building.
Suction and Discharge Pressure Transducers –moni-
tor and readout of suction and discharge pressures.
YORK INTERNATIONAL
41
NOTES
YORK INTERNATIONAL
42
FORM 100.50-EG1
NOTES
YORK INTERNATIONAL
43
Proud Sponsor
of the 2002
U.S. Olympic Team
36USC380
Tele. 800-861-1001
P.O. Box 1592, York, Pennsylvania USA 17405-1592
Copyright © by York International Corporation 2001
Subject to change without notice. Printed in USA
ALL RIGHTS RESERVED
Form 100.50-EG1 (201)
New Release
|