WINEMATE Split System
Installation, Operation & Care Manual
WM1500 SSW
WM2500 SSW
Vinotemp International Corp.
Important Safety Information
• DO NOT USE A GROUND FAULT INTERRUPTER (GFI).
• A DEDICATED 20 AMPCIRCUIT IS HIGHLY RECOMMENDED.
- 2 -
Feature Description
• WineMate split cooling system is designed and used to provide a stable
temperature between 52~62 °F for suitable space at a normal
environment.
• The refrigerated space will maintain humidity of 50~70% RH even when
the environment becomes dry and humid.
• These temperatures and humilities are optimized for long term storage of
wine, fur and tobacco.
• SSW units are designed for installation between two wall studs, making
them an ideal choice for small and medium wine rooms.
• The condensing unit is located away from the wine cellar or other
refrigerated enclosure as far as 50 feet, which will bring you extremely
quiet operation.
The dimension and capacity are specified as follows:
Model
Capacity
(Btu/h)
Unit
Cooler
Cond
Unit
Electrical
Unit Cooler/Cond
Unit
Refrigerant
Weight (lb)
Unit Cooler/
Cond Unit
55/90°F
WM1500
SSW
1500
WM15
SFCW
WM15
SCU
115V 60HZ 0.71A/
115V 60HZ 3.2A
R134a
R134a
26/30
WM2500
SSW
2500
WM25
SFCW
WM25
SCU
115V 60HZ 0.71A/
115V 60HZ 5.7A
28/40
- 3 -
Evaporator Unit
Condensing Unit
- 4 -
Installation Instruction
Federal law requires that WINEMATE split cooling systems be
installed by an EPA certified refrigeration technician.
1. Location
• Place the condensing unit in a properly ventilated location. If it is not, heat
exhausted by the condensing unit will build up and the cooling system will
not operate properly.
• Leave minimum 3 feet clearance between the exhaust side and the wall.
• Leave minimum 1 foot clearance for the fresh air supply side.
• Condensing unit should be elevated to avoid possible flooding and shaded
from direct sun. It should not be exposed to temperatures higher than 125
°F or lower than 20 °F.
• Air flow from the unit cooler should be unobstructed for at least 1 foot.
2. Refrigeration Installation
Model
Liquid Line Diameter
(inch), recommended
Suction Line Diameter
(inch), recommended
WM-1500SSW
WM-2500SSW
3/8
3/8
3/8
3/8
WINEMATE split system is shipped as components and is ready for use only
after a certified refrigeration technician has properly installed and tested the
system. Proper installation is critical. WINEMATE can only warrant the quality of
the components. The installation and proper operation of the system must be
warranted by the installer.
Installation of the system must be done in accordance with all state and local
building codes.
- 5 -
The condensing unit and unit cooler are connected by a liquid line and an
insulated suction line that are supplied by the installer. These lines must be
properly sized for the distance between the two units. After the units and the lines
are installed, the system must be pressure tested. If no leaks are found,
evacuate and charge system with R134A. Refrigerant amount will vary
depending on the length of line set.
3. Electrical Wiring
• We strongly recommend against the use of an extension cord. However, if
you still select to use an extension cord, it is absolutely necessary that it is
a UL LISTED 3-wire grounding type appliance extension cord. The
marked rating of the extension cord should be 115 V, 20 A. or equivalent
and not greater than 15ft in length.
1500& 2500SSW Electrical Wiring Diagram
- 6 -
Use & Temperature Control
1. Temperature Setting
• Set the temperature at 55 °F for the optimum aging of wine
• Set the temperature higher at very high ambient temperature.
• On initial start-up, the time required to reach the desired temperature
will vary, depending on the quantity of bottles, temperature setting
and surrounding temperature.
• Allow 24 hours to stabilize the temperature for each new temperature
setting operation
2. Use of the controller
1) Display
During normal operating conditions, the display shows the value measured by
the air regulation probe. In case of active alarm, the temperature flashes
alternately to the code alarm.
1.1 LED Functions
- 7 -
1.2 Front Panel Commands
2) Alarm Signals
2.1 Code Description
2.2 Alarm Recovery
Probe alarms P1”, start a few seconds after the fault in the related probe; they
automatically stop a few seconds after the probe restarts normal operation.
Check connections before replacing the probe. Temperature alarms “HA”, “LA”
automatically stop as soon as the temperature returns to normal value. Alarm
“CA” (with i1F=PAL) recovers only by switching off and on the instrument.
3) Set-Point (desired temperature value)
3.1 How to see the set-point
1. Push and immediately release the SET key: the display will show the Set-point
value;
2. Push and immediately release the SET key or wait for 5 seconds to display the
probe value again.
3.2 How to change the set-point
- 8 -
1. Push the SET key for more than 3 seconds to change the Set point value;
2. The value of the set point will be displayed and the “°C” or “°F” LED starts
blinking;
3. To change the Set value, push the o or n arrows within 10s.
4. To memorize the new set point value, push the SET key again or wait 10s.
4) Manual Defrost
Push the DEF key for more than 2 seconds and a manual defrost will start.
- 9 -
Care Guide
In general, always unplug system or disconnect power while doing care.
1. Coil Cleaning
• Clean the condenser coil regularly. Coil may need to be cleaned at
least every 6 months.
• Unplug the system or disconnect power.
• Use a vacuum cleaner with an extended attachment to clean the coil
when it is dusty or dirty.
• Plug cooling system or reconnect power.
2. Moisture Removing
• Remove the extra condensate if it is accumulated in the wine cellar at
high ambient temperature and humidity.
- 10 -
Troubleshooting
This Troubleshooting Chart is not prepared to replace the training required for a
professional refrigeration service person, not is it comprehensive
Troubleshooting Chart
Complaint
Possible Causes
Response
1. Unit not running
a. Power cord unplugged
b. No power to unit
c. Temperature setting high
d. Low voltage.
e. Incorrect or loose wirings.
f. Defrost light blinking
g. Running light blinking
a. Check for power cord plug
b. Check power at receptacle & fuses
c. Lower temperature setting
d. Contact an authorized electrician
e. Check all wirings and connections
f. Under defrost
g. Call service for failed components
2. Compressor stopping and starting but short running time
a. Incorrect temperature setting
b. Incorrect voltage
c. Failed thermistor
a. Set 55 to 60 °F
b. Check for voltage
c. Check thermistor by placing it in ice
water and measuring resistance
d. Check compressor windings, start
relay and overload protector.
e. Check for condenser fan
f. Clean condenser
d. Failed components
e. Improper condenser airflow
f. Dirty condenser
g. Overcharge of refrigerant
h. Discharge or suction pressure too
high
g. Call service for removing refrigerant
h. Call service for OEM information
3. Fan motor running but compressor not running
a. Incorrect power supply
b. Incorrect or loose wirings
c. Failed components
a. Check for proper voltage
b. Check all wirings and connections
c. Check start relay, start capacitor,
overload protector, compressor.
d. Liquid refrigerant in the compressor
d. Call service for OEM information.
4. Compressor running but fan not running
a. Fan blade bond
a. Check for proper clearance
b. Check all wirings
c. Call service for checking open or
shorted windings
b. Incorrect or loose wirings
c. Failed motors
5. No cooling but compressor and fan running
a. Evaporator airflow restriction
a. Check for airflow through evaporator
b. Check for loss of refrigerant
b. Refrigerant leakage
c. Refrigeration system restriction
c. Call service for checking restrictions
6. Temperature too high or unit running too long
a. Improper evaporator or condenser a. Check for air restrictions
airflow
b. Dirty Condenser
c. Iced evaporator
d. Malfunctioning fans
e. Improper seals
f. Improper area to be cooled.
b. Clean condenser
c. Defrost and reset temperature
d. Check for both fans
e. Check for gasket and door opening
f. Check for excessive load incorrect
installation
- 11 -
g. Low voltage
g. Check power supply
h. Operating 60 Hz unit at 50Hz
i. Sealed system problem
h. Use proper 60 Hz
i. Call service for checking loss of
refrigerant or restrictions
j. Undercharge or overcharge
j. Call service to add or remove
refrigerant
7. House circuit tripping
a. Incorrect fuse or breaker
b. Incorrect wirings
c. Failed components
a. Check for proper fuse or breaker
b. Check for wirings and connections
c. Call service
8. Noisy operation
a. Mounting area not firm
b. Loose parts
a. Add support to improve installation
b. Check fan blades, bearings, cabinet
washers, tubing contact and loose
screws.
c. Compressor overloaded due to high c. Check for airflow blockage
ambient temperatures or airflow
restriction
d. Malfunctioning components
d. Call service for checking Internal
loose, inadequate lubrication and
incorrect wirings
- 12 -
Customer Support
If you still have problems, please contact us at:
Vinotemp International
17631 South Susana Road
Rancho Dominguez, CA 90221
Tel: (310) 886-3332
Fax: (310) 886-3310
Email: [email protected]
- 13 -
Warranty
Thank you for choosing a Vinotemp wine cellar.
Please enter the complete model and serial numbers in the space provided:
Model_________________________________________________________
Serial No.______________________________________________________
Attach your purchase receipt to this owner’s manual.
1. Limited Warranty
VINOTEMP warrants its products, parts only, to be free from defects due to
workmanship or materials under normal use and service for twelve months after
the initial sale. If the product is defective due to workmanship or materials, is
removed within twelve months of the initial sale and is returned to VINOTEMP, in
the original shipping carton, shipping prepaid, VINOTEMP will at its option, repair
or replace the product free of charge.
This warranty constitutes the entire warranty of the VINOTEMP with respect to its
products and is in lieu of all other warranties, express or implied, including any of
fitness for a particular purpose. In no event shall VINOTEMP be responsible for
any consequential damages what is so ever. Any modification of VINOTEMP
products shall void this warranty.
Service under Warranty
This service is provided to customers within the continental UNITED STATES
only. VINOTEMP cooling units are warranted to produce the stated number of
BTU/H. While every effort has been made to provide accurate guidelines,
VINOTEMP can not warranty its units to cool a particular enclosure.
In case of failure, VINOTEMP cooling units must be repaired by the factory or its
authorized agent. Repairs or modifications made by anyone else will void the
warranty.
Should a VINOTEMP cooling unit fail, contact the dealer for instructions. Do not
return the unit to the factory without authorization from VINOTEMP. If the unit
requires repair, re-pack it in the original shipping carton and return it to the
factory, shipping prepaid. VINOTEMP will not accept COD shipments. If the unit
is determined to be faulty and is within the twelve month warranty period
- 14 -
VINOTEMP will, at its discretion, repair or replace the unit and return it free of
charge to the original retail customer. If the unit is found to be in good working
order, or beyond the initial twelve month period, it will be returned freight collect.
2. Limitation of Implied Warranty
VINOTEMP’S SOLE LIABILITY FOR ANY DEFECTIVE PRODUCT IS LIMITED
TO, AT OUR OPTION, REPAIRING OR REPLACING OF UNIT.
VINOTEMP SHALL NOT BE LIABLE FOR:
DAMAGE TO OTHER PROPERTY CAUSED BY ANY DEFECTS IN THE UNIT,
DAMAGES BASED UPON INCONVENIENCE, LOSS OF USE OF THE UNIT,
LOSS OF TIME OR COMMERCIAL LOSS, ANY OUTER DAMAGES,
WHETHER INCIDENTAL, CONSEQUENTIAL OR OTHERWISE.
THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER
WARRANTIES, EXPRESSED OR INPLIED, INCLUDING BUT NOT LIMITED
TO, IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE.
While great effort has been made to provide accurate guidelines VINOTEMP
cannot warrant its units to properly cool a particular enclosure. Customers are
cautioned that enclosure construction, unit location and many other factors can
affect the operation and performance of the unit. There for suitability of the unit
for a specific enclosure or application must be determined by the customer and
cannot be warranted by VINOTEMP.