INSTALLATION INSTRUCTIONS
— Split System Air Conditioner —
CONTENTS
Model Combinations
IMPORTANT
Page
Combine indoor and outdoor units only as listed below.
Please Read Before Starting
Indoor units
XS1852 (PNR-XS2432)
Outdoor units
C1852, CL1852
1. GENERAL.............................................................3
1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied with Unit
1-3. Optional Copper Tubing Kit
Power Supply :
60Hz, single-phase, 208/230 V
1-4. Type of Copper Tube and Insulation Material
1-5. Additional Materials Required for Installation
1-6. Operating Range
Units should be installed by licensed contractor
according to local code requirements
1-7. Tubing Length
2. SELECTING THE INSTALLATION SITE ............ 5
Indoor Unit
7. HOW TO PROCESS TUBING ........................... 21
7-1. Use of the Flaring Method
Outdoor Unit
2-1. Baffle Plates for the Outdoor Unit
7-2. Flaring Procedure with a Flare Tool
7-3. Precaution before Connecting Tubes Tightly
7-4. Precautions during Brazing
7-5. Connecting Tubing between Indoor and
Outdoor Units
7-6. Insulating the Refrigerant Tubing
7-7. Taping the Tubes
7-8. Finishing the Installation
3. HOW TO INSTALL THE INDOOR UNIT.............. 7
3-1. Suspending the Indoor Unit
3-2. Preparation for Suspending
3-3. Placing the Unit Inside the Ceiling
3-4. Installing the Drain Piping
3-5. Checking the Drainage
8. AIR PURGING ....................................................24
■ Ceiling Panel......................................................11
3-6. Before Installing the Ceiling Panel
3-7. Installing the Ceiling Panel
3-8. When Removing the Ceiling Panel for
Servicing
■
Air Purging with a Vacuum Pump
(for Test Run)
9. TEST RUN ..........................................................26
9-1. Performing Test Run
3-9. Duct for Fresh Air
9-2. Performing Test Run with Optional Wired
Remote Control Unit
9-3. Basic Function of the Service Valves
9-4. Pump Down
4. HOW TO INSTALL THE REMOTE
CONTROL UNIT .................................................15
■ Wireless Remote Control Unit
4-1. Mounting on a Wall
■ Wired Remote Control Unit (Option)
4-2. Installing the Wired Remote Control Unit
5. ADDRESS SWITCHES .......................................17
5-1. Finding the Address Switches
5-2. Switch Positions for 2 Units or 2 Groups of
Units
6. ELECTRICAL WIRING .......................................18
6-1. General Precautions on Wiring
6-2. Recommended Wire Length and Wire
Diameter for Power Supply System
6-3. Wiring Instructions for the Outdoor Unit
6-4. Examples of Incorrect Wiring
6-5. How to Connect Wiring to the Terminal
SANYO FISHER COMPANY
A DIVISION OF SANYO NORTH
AMERICA CORPORATION
21605 Plummer Street
Chatsworth, CA91311
85464359128000
SANYO 2000
1
S4359128
1. General
Part Name
Wireless
remote control unit
Figure
Q’ty
This booklet briefly outlines where and how to install
the air conditioning system. Please read over the
entire set of instructions for the indoor and outdoor
units and make sure all accessory parts listed are with
the system before beginning.
1
AAA alkaline
battery
2
Special
screw
4 ✕ 16 mm
1
1
Tapping screw
Tapping screw
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
TOTA 4 ✕ 16
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the
indoor unit is available in kits which contain the narrow
and wide tubing, fittings and insulation. Consult your
nearest sales outlet or A/C workshop.
5. Level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
1-4. Type of Copper Tube and Insulation Material
10. Drill
11. Tube cutter
If you wish to purchase these materials separately
from a local source, you will need:
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
16. Service valve wrench
17. Wire cutter
1. Deoxidized annealed copper tube for refrigerant
tubing.
Cut each tube 12 in. to 16 in. longer than the
appropriate lengths to dampen vibration between
units.
2. Foamed polyethylene insulation for 5/8"
(15.88 mm) O.D. copper tubes as required to
precise length of tubing. Wall thickness of the
insulation should be not less than 0.3 inch
(8 mm).
1-2. Accessories Supplied with Unit
Table 1-1
Part Name
Full-scale
installation
diagram
Figure
Q’ty
Remarks
For determining
suspension bolt
pitch
1
Check local electrical codes
CAUTION
and regulations before
Flare
insulator
obtaining wire. Also, check
any specified instructions or
limitations.
1
1
1
For wide tubes
Installation
gauge
For adjusting the
unit position
Insulating
tape
For wide tube
flare nuts
1-5. Additional Materials Required for Installation
(White for insulating)
1. Insulated staples or clamps for connecting wire
(See your local codes.)
For securing drain
hose
2
1
1
1
1
Hose band
Packing
2. Putty
For drain joint
For drain joint
3. Refrigeration tubing lubricant
4. Clamps or saddles to secure refrigerant tubing
5. Scale for weighing
Drain
insulator
Drain hose
1-6. Operating Range
Drain hose
adapter
For drain outlet
Temperature Indoor Air Intake Outdoor Air Intake
Maximum
Minimum
95°F DB, 71°F WB
115°F DB
Owner’s
manual
Cooling
1
1
67°F DB, 57°F WB
67°F DB (0°F DB)*
*CL&&&& Models
To open and shut
the Narrow Tube
Service Valve
Hexagonal
Wrench*
*Packed in the outdoor unit
3
S4359128
1-7. Tubing Length
● Refrigerant tubing between the indoor and outdoor
Tubing length (L)
INDOOR
UNIT
units should be kept as short as possible.
● Select and decide the installation location so that
the length of the refrigerant tubing will be within the
limits given in Table 1-2.
Elevation difference (H)
OUTDOOR
UNIT
0711_M_I
Fig. 1-1
Table 1-2
Models
C1852
Tubing Data
CL1852
Narrow tube in. (mm)
1/4 (6.35): Thickness 0.0314" (0.8 mm)
5/8 (15.88): Thickness 0.0394" (1.0 mm)
65
Tubing size
outer dia.
Wide tube
in. (mm)
(ft.)
Limit of tubing length
Outdoor unit is higher
Limit of elevation
23
23
than indoor unit
(ft.)
difference between
Outdoor unit is lower
(ft.)
the 2 units
than indoor unit
Max. allowable tubing length at shipment (ft.)
Required additional refrigerant *1
(oz./ft.)
33
0.27
No additional charge of compressor oil is necessary.
1
*
If total tubing length becomes 33 to 65 ft., charge additional refrigerant (R22) by 0.27 oz./ft..
4
S4359128
2. Selecting the Installation Site
Indoor Unit
AVOID:
● areas where leakage of flammable gas may be
expected.
● places where large amount of oil mist exist.
● direct sunlight.
● locations near heat sources which may affect
performance of the unit.
● locations where external air may enter the room
directly. This may cause “sweating” on the air
discharge ports, causing them to spray or drip.
● locations where the remote control unit will be
splashed with water or affected by dampness or
humidity.
● installing the remote control unit behind curtains or
furniture.
● locations where the receiver in the indoor unit is
exposed to the inverter lamp light. Faulty operation
of the unit occurs.
DO:
3 ft.
3 ft.
● select an appropriate position from which every
corner of the room can be uniformly cooled.
● select a location where the ceiling is strong enough
3 ft.
to support the weight of the unit.
3 ft.
3 ft.
● select a location where tubing and drain pipe have
the shortest run to the outdoor unit.
1330_X_S
● allow room for operation and maintenance as well
Fig. 2-1
as unrestricted air flow around the unit. (Fig. 2-1)
● install the unit within the maximum elevation
difference above or below the outdoor unit and
within a total tubing length from the outdoor unit as
detailed in Table 1-2.
● allow room for mounting the remote control unit
about 3 ft. off the floor, in an area that is not in
direct sunlight nor in the flow of cool air from the
indoor unit.
NOTE
Air delivery will be degraded if the distance from the
floor to the ceiling is greater than 10 ft..
5
S4359128
Outdoor Unit
AVOID:
Exhaust fan
NO
Hot air
Heat source
● heat sources, exhaust fans, etc. (Fig. 2-2)
Out-
door
unit
● damp, humid or uneven locations.
DO:
1817_C_I
● choose a place as cool as possible.
Fig. 2-2
● choose a place that is well ventilated.
Obstacle above
● allow enough room around the unit for air intake/
Min.
exhaust and possible maintenance. (Fig. 2-3)
Min.
7 ft.
(2 m)
7 ft.
Air intake
Min. 6" (15 cm)
(2 m)
Valve side
Min. 10"
(25 cm)
● Install the outdoor unit above
snowfall line.
CAUTION
● Do not place objects on or sit
ontheoutdoorunit.Also,never
block the air intake/outlet or
exhaust. Distortion of the
outdoor unit or incomplete
combustion may result.
Min. 6"
(15 cm)
Air discharge
Min. 12"
(30 cm)
1818_M_I
Ground
Min. 6 in.
(15 cm)
● Donotintroduceforeignmatter
into the air intake/outlet or
exhaust.Donotpokethemwith
such objects as a stick.
Air intake
1819_M_I
Fig. 2-3
Anchor bolts
(4 pcs)
● provide a solid base (level concrete pad, concrete
block, 4 in. × 16 in. (10 × 40 cm) beams or equal), a
minimum of 4 in. (10 cm) above ground level to
reduce humidity and protect the unit against possible
water damage and decreased service life (Fig. 2-4).
Min. 4"
(10 cm)
Air intake
Concrete
or equal
● use lug bolts or equal to bolt down unit, reducing
vibration and noise.
2-1. Baffle Plates for the Outdoor Unit
1820_M_I
(CL×× models only)
Fig. 2-4
6" min
NOTE
Baffle
plate
Baffle
plate
It is recommended to use baffle plates for model
CL1852. The baffle plates are not normally required for
the other models.
When the outdoor unit is installed in a position exposed
to strong wind (like seasonal winds with low air
temperature in winter), baffle plates must be installed on
the outdoor unit. (Fig. 2-5)
Air discharge
This unit is designed so that the fan of the outdoor unit
runs at low speed when the air conditioner is operated at
low outdoor air temperatures. When the outdoor unit is
exposed to strong wind, the system pressure drops
because of the freeze protector.
1821_M_I
Fig. 2-5
6
S4359128
3. How to Install the Indoor Unit
3-1. Suspending the Indoor Unit
This unit uses a drain pump. Use a carpenter’s level to
check that the unit is level.
3-2. Preparation for Suspending
Hole-in-anchor
Hole-in-plug
Concrete
Insert
(1) Fix the suspension bolts securely in the ceiling
using the method shown in the diagrams (Figs.
3-1 and 3-2), by attaching them to the ceiling
support structure, or by any other method that
ensures that the unit will be securely and safely
suspended.
Suspension bolt (M10 or 3/8")
(field supply)
(2) Follow Fig. 3-2 and Table 3-1 to make the holes
in the ceiling.
0038_T_I
Fig. 3-1
A (ceiling opening dimension)
B (suspension bolt pitch)
Table 3-1
Unit : inch (mm)
Length
A
B
Type
1/2"
1/2"
XS1852 (PNR-XS2432) 32-9/32 (820) 28-3/4 (730)
Refrigerant
tubing side
Drain hose
side
(3) Determine the pitch of the suspension bolts using
the supplied full-scale installation diagram. The
diagram and table (Fig. 3-3 and Table 3-2) show
the relationship between the positions of the
suspension fitting, the unit, and the panel.
Unit: inch
0962_S_I
Fig. 3-2
Refrigerant tubing joint (narrow tube side)
Refrigerant tubing joint (wide tube side)
Drain inspection port
Suspension lug
15/32"
15/32"
Power supply inlet
1019_X_I
Fig. 3-3
Table 3-2
Unit : inch
Length
A
B
C
D
E
Type
XS1852 (PNR-XS2432) 5-29/32 7-7/8 10-1/32 11-23/32 4-29/32
7
S4359128
3-3. Placing the Unit Inside the Ceiling
(1) When placing the unit inside the ceiling, deter-
mine the pitch of the suspension bolts using the
supplied full-scale installation diagram. (Fig. 3-4)
The size of the opening for the indoor unit can be
confirmed by attaching the full-scale installation
diagram beneath the unit. (Fig. 3-4)
Full-scale installation diagram
(printed on a cardboard packing)
Tubing and wiring must be laid inside the ceiling
when suspending the unit. If the ceiling is already
constructed, lay the tubing and wiring into posi-
tion for connection to the unit before placing the
unit inside the ceiling.
Full-scale installation
diagram
0963_X_I
Fig. 3-4
(2) The length of suspension bolt must be appropri-
ate for a distance between the bottom of the bolt
and the bottom of the ceiling of more than
2-3/8 in. as shown in Fig. 3-4.
Suspension bolt
Suspension lug
Nuts and washers
(2 sets)
(3) Thread the 2 hexagonal nuts and washers (field
supply) onto the 4 suspension bolts as shown in
Fig. 3-5.
Upper
Lower
Use 2 sets of nuts and washers (upper and
lower), so that the unit will not fall off the suspen-
sion lugs.
(4) Remove the protective cardboard used to protect
the fan parts during transport.
0041_X_I
Fig. 3-5
(5) Adjust the distance between the unit and surface
of the ceiling (1-7/8 in.) using the supplied instal-
lation gauge. (Fig. 3-4)
8
S4359128
3-4. Installing the Drain Piping
Transparent part for
checking drainage
Hard PVC pipe
(not supplied)
Hose band
(supplied)
(1) Prepare standard hard PVC pipe (O.D. 1-3/64 in.)
for the drain and use the supplied drain hose and
hose band to prevent water leaks.
The PVC pipe must be purchased separately.
The transparent part allows you to check drain-
age. (Fig. 3-6)
Drain hose
Packing
(supplied)
Drain hose
(supplied)
adapter
(supplied)
0964_X_I
Tighten the hose clamps
Fig. 3-6
CAUTION
so their locking nuts face
upward. (Fig. 3-6)
Drain insulator (supplied)
(2) After checking the drainage, wrap the supplied
packing and drain pipe insulator around the pipe.
(Fig. 3-7)
NOTE
Ensure the drain pipe has a downward gradient
(1/100 or more) and that there are no water traps.
0197_X_I
Fig. 3-7
● Do not install an air
Air bleeder
CAUTION
bleeder tubes, as this
may cause water to spray
from the drain tube outlet.
(Fig. 3-8)
0047_X_I
● If it is necessary to increase the height
of the drain pipe, the section directly
after the connection port can be raised
a maximum of 10 in. Do not raise it any
higher than 10 in., as this could result
in water leaks.
Fig. 3-8
5 in. or less (as short as possible)
10 in. or less
(Fig. 3-9)
● Do not install the pipe with an upward
gradient from the connection port. It
will cause the drain water to flow
backwards and leak when the unit is
stopped. (Fig. 3-10)
0965_X_I
Fig. 3-9
Upward gradient
● Do not apply force to the piping on the
unit side when connecting the drain
pipe. The pipe should not be allowed
to hang unsupported from its connec-
tion to the unit. Fasten the pipe to a
wall, frame, or other support as close
to the unit as possible. (Fig. 3-11)
0049_X_I
Fig. 3-10
● Provide insulation for any drain pipes
that are installed indoors.
Support
pieces
0050_X_I
Fig. 3-11
9
S4359128
3-5. Checking the Drainage
After wiring and piping are completed, use the follow-
ing procedure to check that the water will drain
smoothly. For this, prepare a bucket and wiping cloth
ready to catch and wipe up spilled water.
Do not supply power to the
unit until the tubing and
wiring to the outdoor unit
are completed.
(1) Take off the tube cover and through the opening,
slowly pour about 43 oz. of water into the drain
pan to check drainage.
(2) Do Test Run to check the drainage after complet-
ing installation. When performing Test Run, be
sure to observe the Test Run procedure.
Refer to page 37.
Be careful since the fan will
CAUTION
start turning when checking
the drainage.
5/16"(4 × 8 mm)
tapping screw
(3) After drain checking is finished, return the
Operation Selector switch to the RUN position
(ON position ) and remount the tube cover.
To mount the tube cover,
CAUTION
use 5/16" (4 × 8 mm) tapping
Tube cover
screws. Do not use long
screws as they may punc-
ture the drain pan and cause
water leakage.
Siphon
0966_X_I
Fig. 3-12
10
S4359128
■
Ceiling Panel
Never touch or attempt to
move the air direction louver
by hand or you may damage
the unit. Instead, use the
remote control unit if you
want to change the direction
or air flow.
CAUTION
3-6. Before Installing the Ceiling Panel
(1) Remove the air-intake grille and air filter from the
ceiling panel. (Figs. 3-13 and 3-14)
(a) Remove the 2 screws on the latch of the air-
intake grille. (Fig. 3-13)
Screw
(b) Press on the 2 latches of the air-intake grille
with your thumb in the direction of the arrow
to open the grille. (Fig. 3-13)
Latch
(c) With the air-intake grille open about 45˚,
remove the safety string (hook on the grille
side). (Fig. 3-14)
Air intake grille
(d) Pull the air-intake grille towards you to
remove it from the ceiling panel.
(2) Pull down the two panel catches on the body of
the indoor unit body. (Fig. 3-15)
Ceiling panel
0149_X_I
Fig. 3-13
Air filter
45°
Safety string
Fig. 3-14
0150_X_I
11
S4359128
3-7. Installing the Ceiling Panel
(1) Lift the ceiling panel and position it to align the
panel hook with the panel catch of the indoor unit.
(5) Install the air filter and air-intake grille by perform-
ing the steps in section 3-6 in reverse.
NOTE
NOTE
The ceiling panel must be mounted in the correct
direction. Note that the 2 catches of the panel differ in
size.
Rehook the safety string before closing the air-intake
grille.
Confirm that the catches are correctly matched be-
tween the ceiling panel and the indoor unit body.
3-8. When Removing the Ceiling Panel for
Servicing
(2) Next, check to see that the ceiling panel is prop-
erly aligned with the seamline of the ceiling. If it is
not, remove the ceiling panel and slightly readjust
the indoor unit body to the proper suspension
point.
When removing the ceiling panel for servicing, remove
the air-intake grille and air filter, disconnect the wiring
connector inside the electrical component box, and
then remove the 4 mounting screws.
(3) When the ceiling panel has been properly
aligned, use the supplied 4 mounting screws (M5)
with washers to permanently fasten the ceiling
panel.
(4) Install the wiring connector from the ceiling panel
to the connector in the electrical component box
of the indoor unit. After installing the connector,
use the clamp on the body of the indoor unit to
secure the wiring.
Panel catch
(pull down)
Connector on unit
(inside electrical component box)
Electrical component box
Connector of ceiling panel
Ceiling panel
Unit body
Electrical
component box
Panel catch (pull down)
Clamp
Ceiling panel wiring
connector
Ceiling panel
Screws M5 with washer
Mark
Air filter
Air-intake grille
Fig. 3-15
0967_X_I
12
S4359128
3-9. Duct for Fresh Air
● Air-intake chamber (including Duct connection box and flange) are attached to the indoor unit when used to
take fresh outdoor air.
High-performance filter or Super long-life filter can be also installed in the air-intake chamber.
(1) SETUP PRIOR TO INSTALLATION
● When installing the high performance filter or super long-life filter, the parts and parts numbers of filters to be
assembled with the air-intake chamber are listed below. Please check that the correct part numbers are
present.
High performance
filter
Air-intake
chamber
Super long-life
filter
AFT-MSJ80T
AFT-HSJ80T
CMB-GSJ80T
(XS1852)
AFT-LSJ80T
(2) ACCESSORIES
● Check that the following parts are in the box when unpacking.
NAME
Cord with socket
(9P)
QT’Y
1
REMARKS
Connecting line. Connect only when
high-performance filter is used
Screw
(M5 × L125)
Air-intake filter
(for fastening)
4
Screw
(M4 × L12)
Duct connection flange/ box
(for fastening)
4+4
Duct connection box
1
1
(for fresh air)
)
(for connecting fresh air duct
Duct connection flange
(3) INSTALLATION
(a) Setup for the indoor unit
●
When assembling the high-performance filter, open the lid of the electrical component box, remove the socket
(9P) of the fan motor cable inside the electrical component box and connect the accessory cord with socket (9P).
Do not connect the “acces-
sory cord with socket” to
the electrical component box
when the unit is used to take
fresh air.
CAUTION
Cord with socket
(9P)
Do not connect the “acces-
sory cord with socket” when
assembling the super long-
life filter.
Always store the “accessory
cord with socket” inside the
electrical component box.
Installation steps (a) to (b) are the same for both
the CMB-GSJ80T and the GSJ140T. The drawing
illustrates installation of air-intake chamber to the
CMB-GSJ80T.
Electrical
component box
1114_X_S
Fig. 3-16
13
S4359128
(b) INSTALLING THE AIR-INTAKE CHAMBER
● Set the air-intake chamber to the indoor unit taking
care not to set to the incorrect direction. (Fig. 3-17)
● Fasten the air-intake camber with the accessory
screws. (M5 × L125, 4pcs) (Fig. 3-17)
Installation screws
Socket cover
(c) INSTALLING THE DUCT CONNECTION BOX
● Fasten the duct connection flange to the duct
connection box with the accessory screws (M4 ×
L12, 4 pcs.). (Fig. 3-18)
● Put the duct connction box into the rectangular hole
of the air-intake chamber and fasten it to the both
sides of the indoor unit and chamber with the
accessory screws (M4 × L12, 4 pcs.). (Fig. 3-18)
Air-intake chamber
(6P socket)
(d) INSTALLING THE INDOOR UNIT
3P socket
(from ceiling panel)
● Install the indoor unit to the ceiling.
3P plug
(electrical
(Install the indoor unit according to items 3-1 to 3-6.)
Operation
selector
component box)
(e) INSTALLING THE CEILING PANEL
● Attach the ceiling panel to the chamber.
● Remove the socket cover of the air-intake chamber
and pass the 3P and 6P sockets through it. (Fig. 3-17)
● Connect the 3P socket to the 3P plug of the indoor
unit electrical component box.
Indoor unit
6P plug
1115_X_S
Fig. 3-17
● Connect the 6P socket to the 6P plug from the
operation selector.
● Reattach the socket cover.
Installation screws Installation screws
(f) INSTALLING THE HIGH-PERFORMANCE FILTER
(M4 × 12)
(M4 × 12)
OR SUPER LONG-LIFE FILTER (Fig. 3-18)
● Turn the filter hooks of the air-intake chamber.
● Install high-performance or super long-life filter into
the chamber. (Install in the correct direction. Set the
filter so that the arrow on the side as shown in the
Duct
connection box
Air filter
Arrow
Duct
connection
flange
drawing on the right can be installed into
air-intake chamber.
the
Rectangular
hole
● Turn the filter hook (positioned so the filter frame is
Filter hook
aligned) and secure the air filter in place.
Ceiling panel
Take adequate precautions
CAUTION
when installing onto the
ceiling. The air-intake cham-
ber is especially prone to
rupture if struck on it’s side.
1113_X_S
Fig. 3-18
14
S4359128
4. How to Install the Remote Control Unit
■ Wireless Remote Control Unit
The remote control unit can be operated from either a
non-fixed position or a wall-mounted position.
To ensure that the air conditioner operates correctly,
do not install the remote control unit in the following
places:
● In direct sunlight
● Behind a curtain or other place where it is covered
● More than 26 ft. away from the air conditioner
● In the path of the air conditioner’s airstream
● Where it may become extremely hot or cold
● Where it may be subject to electrical or magnetic
interference
Removable mounting
4-1. Mounting on a Wall
Wall
(1) Removable mounting
(a) Momentarily hold the remote control unit in
the desired mounting position.
(b) Confirm that the air conditioner responds
correctly when you press keys on the
remote control from that position.
Special
mounting
screw
(Packed in indoor unit)
(c) After confirming correct operation, use a
screwdriver to screw the supplied special
mounting screw into the wall. (Fig. 4-1)
0532_M_I
Fig. 4-1
(d) Hang the remote control unit from the
mounting screw.
(2) Non-removable mounting
(a) Momentarily hold the remote control unit in
the desired mounting position.
Non-removable mounting
(b) Confirm that the air conditioner responds
correctly when you press keys on the
remote control from that position.
Wall
(c) After confirming correct operation, use a
screwdriver to screw the mounting screw
into the wall. (Fig. 4-1)
(d) Remove the remote control cover by sliding
it downward.
Screw
(Packed in indoor unit)
(e) Remove the batteries of the remote control
unit.
0533_M_I
Fig. 4-2
(f) Hang the remote control unit from the
mounting screw, and use a screwdriver to
screw the remote control unit securing
screw into the wall through the hole in the
battery compartment. (Fig. 4-2)
(g) Replace the batteries.
(h) Again confirm that the remote control unit
operates correctly.
15
S4359128
■ Wired Remote Control Unit (Option)
Electrical
Cover plate
component box
(1) To access the printed circuit board, remove the
cover plate of the electrical component box.
(2) Attach the remote control connectors securely to
the mating connector pins on the printed circuit
board.
(3) Turn the R.C.U. switch from “WIRELESS” to
“WIRED”.
(4) Replace the cover plate.
Do not supply power to
the unit until the tubing and
wiring to the outdoor unit is
completed.
The mounting position for the remote control unit
should be located in an accessible place for control
and permit the average room temperature to be
detected. Never cover the unit or recess it into the wall.
Connector for the wired
remote control unit
WIRED
WIRELESS
R.C.U. Switch
1006_M_I
Fig. 4-3
4-2. Installing the Wired Remote Control Unit
(1) Use a ballpoint pen or similar pointed object to
remove the plastic bushing which is inserted in
the rear of the remote control unit. The bushing
can be discarded. (Fig. 4-4)
Flat-head
Groove
tapping screw
25/64"(3 × 10 mm)
(SATA)
Cord
Rear
Plastic
bushing
(2) Align the cord with the groove of the remote
control unit.
Cord clip
Ballpoint
pen
(3) Attach the mounting plate to the wall with the 2
supplied screws. Then align the rail on the rear of
the control unit with the slot of the mounting plate
and slide the unit down as far as it will go. (Fig. 4-4)
Fix the control unit cord to the wall.
Remote
control
unit
Remote
control
unit
Mounting
plate
(4) If local codes allow, the remote control unit cord
can be wired in the wall. (Fig. 4-5)
Truss-head
tapping screw
5/8"(4 × 16 mm)
(TOTA)
Wall
1020_M_I
0531_M_I
Fig. 4-4
Fig. 4-5
16
S4359128
5. Address Switches
If you are installing one indoor unit or one group of
indoor units in the same room, it is necessary for you
to assign each unit its own address so that each can
be operated by its own remote control unit. You assign
the addresses by matching the switch position of each
indoor unit with the switch position of its remote control
unit. The switch of the remote control unit is shown in
Fig. 5-1.
A
B
5-1. Finding the Address Switches
Address
Remote Control Unit
Remove the lid by sliding it off. You can see the
switches inside the battery compartment. (Fig. 5-1)
Indoor Unit
Address switch is in “A” position
at time of shipment.
1008_M_I
(1) Turn off the Power Switch.
(2) Remove the Grille.
(3) Remove the cover of the Electrical Component
Box.
Fig. 5-1
5-2. Switch Positions for 2 Units or 2 Groups of Units
Table 5-1 shows the positions you can use for up to 2
units or 2 groups of indoor units installed in the same
room. Two remote control units are necessary to allow
the respective units or group to be controlled indepen-
dently.
Table 5-1
Remote Control
Address switch
Indoor Unit
Unit No.
Address switch
1
2
1
2
A
B
OFF
ON
OFF
ON
The indoor unit address switch is set at 1-OFF & 2-OFF
position at shipment.
NOTE
An indoor unit cannot be controlled if its remote control
unit is too far away (more than 26 ft.). If the remote
control unit does not work correctly, bring it closer to
the unit being operated and try again. There should be
no obstacles between the remote control unit and the
indoor unit. For this reason, if the remote control unit is
to be used from a fixed position, check the operation
before mounting.
P.C.B
ON
1
2
WIRED
WIRELESS
R.C.U. Switch
Address Switch
(DSW1)
1321_M_I
Fig. 5-2
17
S4359128
6. Electrical Wiring
6-1. General Precautions on Wiring
(7) Regulations on wire diameters differ from locality
to locality. For field wiring rules, please refer to
your LOCAL ELECTRICAL CODES (ex. National
Electric Code: ANSI/NFPA70) before beginning.
You must ensure that installation complies with all
relevant rules and regulations.
(1) Before wiring, confirm the rated voltage of the unit
as shown on its nameplate, then carry out the
wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, and a power supply disconnect and
circuit breaker for overcurrent protection should
be provided in the exclusive line.
(8) To prevent malfunction of the air conditioner
caused by electrical noise, care must be taken
when wiring as follows:
(3) To prevent possible hazards from insulation
failure, the unit must be grounded.
● The inter-unit control wiring and the remote control
wiring (option) should be wired apart from the inter-
unit power wiring.
(4) Each wiring connection must be done in accor-
dance with the wiring system diagram. Wrong
wiring may cause the unit to misoperate or
become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can
be very dangerous. The manufacturer will accept
no responsibility for any damage or misoperation
that occurs as a result of such unauthorized
changes.
6-2. Recommended Wire Length and Wire Diameter for Power Supply System
Power Supply Terminal Base
(Outdoor Unit)
(B)*1 Inter-unit
Wiring
Time Delay
Fuse or
Circuit
(A)*1 Power Supply
Models
Max. Wire
Diameter
Capacity
Capacity
AWG #12
75 ft.
AWG #12
65 ft.
C1852, CL1852
15 A
20 A
AWG #12
*1 Refer to the Wiring System Diagrams (See Fig. 6-3) for the meaning of “A”, “B”.
Terminal
block
AWG = American Wire Gauge
Lock nut
Access panel
6-3. Wiring Instructions for the Outdoor Unit
(1) To take off the access panel, remove the 4
screws. (See Fig. 6-1)
(2) Dismount plugs on the conduit plate.
(3) Temporarily mount the conduits on the conduit
Conduit
plate
plate.
(4) Properly connect both the power supply and inter-
unit lines to the corresponding terminals on the
terminal block.
Refer to the wiring diagram in Fig. 6-2 (which also
appears on the access panel).
Plug
Power supply
Inter-unit line
1822_M_I
Fig. 6-1
18
S4359128
INDOOR
INDOOR UNIT
NOTE
OUTDOOR UNIT
● Conduit's trade size for this unit is 1/2". The
(Inter-unit)
Power lines
conduit can be purchased at a hardware store.
B
230/208 V
230/208 V
230/208 V
1
2
3
1
Fuse
● The fuse located in the outdoor unit provides
power supply protection and may blow when
power is applied if the system has been
incorrectly wired.
2
3
4
A
Disconnect
switch
(Field supply)
L1
5
L2
6
(5) Ground the unit in accordance with local codes.
G
G
(6) Be sure to size each wire allowing several inches
longer than the required length for wiring.
Grounding
line
1823_M_I
Fig. 6-2
(7) Use lock nuts to secure the conduit tubes.
● Be sure to comply with
local codes while running
the wire from the indoor
unit to the outdoor unit
(size of wire and wiring
method, etc.).
● Every wire must be
connected firmly.
● No wire should be
allowed to touch
● To avoid the risk of
electric shock, each air
conditioner unit must be
grounded.
● Be sure to connect the
power supply line to the
outdoor unit as shown in
the wiring diagram. The
indoor unit draws its
power from the outdoor
unit.
CAUTION
refrigerant tubing, the
compressor or any
moving part.
6-4. Examples of Incorrect Wiring
The following are examples of improper wiring that result in system misoperation. You should confirm that you
have wired the units correctly before beginning the test run.
Problem 1
Problem 2
● Short circuit will occur after approx.
3 minutes and the power circuit
fuse blows.
● Air conditioner will not operate.
Disconnect
switch
Disconnect
(B)
Disconnect
switch
(A)
(C)
switch
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
G
G
G
G
G
G
Grounding line
Grounding line
Grounding line
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
1301_C_I
1302_C_I
1303_C_I
Problem 3
● Compressor will not start; only indoor unit will operate.
Disconnect
switch
Disconnect
switch
(D)
(E)
1
2
3
1
2
3
1
2
3
1
2
3
G
G
G
G
Grounding line
Grounding line
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
1304_C_I
1305_C_I
19
S4359128
Loose wiring may cause the
terminal to overheat or result
in unit malfunction. A fire
hazard may also exist.
Therefore, ensure that all
wiring is tightly connected.
When connecting each power wire to the correspond-
ing terminal, follow the instructions on “How to connect
wiring to the terminal” and fasten the wire securely with
the fixing screw of the terminal plate.
6-5. How to Connect Wiring to the Terminal
Solid wire
Insulation
Loop
■ For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter or wire-cutting
pliers, then strip the insulation to expose the solid
wire about 1 in.. (Fig. 6-3)
1004_M_I
(2) Using a screwdriver, remove the terminal
screw(s) on the terminal plate.
Fig. 6-3
(3) Using the pliers, bend the solid wire to form a
loop suitable for the terminal screw.
Stranded wire
(4) Shape the wire loop properly, position it on the
terminal plate and fix it securely with the terminal
screw using a screwdriver.
Ring
pressure
terminal
■ For stranded wiring
(1) Cut the wire end with a wire cutter or wire-cutting
pliers, then strip the insulation to expose the
stranded wiring about 3/8 in.. (Fig. 6-4)
1106_M_I
Fig. 6-4
(2) Using a Pillips head screwdriver, remove the
terminal screw(s) on the terminal plate.
Special
washer
Screw
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring pressure
terminal. (Fig. 6-4)
Ring pressure
terminal
Screw and
Special washer
Terminal plate
Wire
(4) Place the ring pressure terminal, and replace and
tighten the removed terminal screw using a
screwdriver. (Fig. 6-5)
Ring
connector
Wire
1308_M_I
Fig. 6-5
20
S4359128
7. How to Process Tubing
Deburring
The narrow tubing side is connected by flare nut, and
the wide tubing side is connected by brazing.
Before
After
7-1. Use of the Flaring Method
Many of the conventional split system air conditioners
employ the flaring method to connect refrigerant tubes
which run between indoor and outdoor units. In this
method, the copper tubes are flared at each end and
connected with flare nuts.
7-2. Flaring Procedure with a Flare Tool
(1) Cut the copper tube to the required length with a
tube cutter. It is recommended to cut about
0126_M_I
Fig. 7-1
12 – 20 in. longer than the estimated tubing length.
(2) Remove burrs at the end of the copper tube with
a tube reamer or file. This process is important
and should be done carefully to make a good
flare. (Fig. 7-1)
Copper
tubing
NOTE
Reamer
When reaming, hold the tube end downward and be
sure that no copper scraps fall into the tube. (Fig. 7-2)
(3) Remove the flare nut from the unit and mount it
on the copper tube.
0127_M_I
Fig. 7-2
(4) Make a flare at the end of copper tube with a flare
tool.* (Fig. 7-3)
®
*Use “RIGID ” or equivalent.
NOTE
Flare nut
A good flare should have the following characteristics:
Copper
tubing
● inside surface is glossy and smooth.
● edge is smooth.
● tapered sides are of uniform length.
Flare tool
0128_M_I
7-3. Precaution before Connecting Tubes Tightly
Fig. 7-3
(1) Apply a sealing cap or water-proof tape to pre-
vent dust or water from entering the tubes before
they are used.
(2) Apply refrigerant lubricant to the matching sur-
faces of the flare and union before connecting
them together. This helps to reduce gas leaks.
(Fig. 7-4)
Apply refrigerant
lubricant here and here
0129_M_I
Fig. 7-4
(3) For proper connection, align the union tube and
flare tube with each other, then screw in the flare
nut lightly at first to obtain a smooth match.
(Fig. 7-5)
● Adjust the shape of the narrow and wide tubes
using a tube bender at the installation site and
connect them to the each tubing side valve using
a flare nut.
Union
Flare nut
0130_M_I
Fig. 7-5
21
S4359128
7-4. Precautions during Brazing
Torque wrench
● Replace air inside the tube with nitrogen gas to
prevent copper oxide film from forming during the
brazing process.
Spanner
Indoor unit
● Do not allow the tubing to get too hot during the
brazing process.
Outdoor unit
The nitrogen gas inside the tubing may overheat,
causing refrigerant system valves to become
damaged. Therefore allow the tubing to cool be-
tween brazings.
0131_C_I
Fig. 7-6
7-5. Connecting Tubing between Indoor and
Outdoor Units
Refrigerant tubing
Seal (supplied)
Insulation tape (white)
(supplied)
(1) Tightly connect the indoor side refrigerant tubing
with the outdoor side tubing. (Fig. 7-6)
Flare insulator (supplied)
Tube insulator
(not supplied)
(2) To fasten the flare nuts, apply specified torque as:
Unit side
insulator
Table 7-1
Tube Dia.
Tightening Torque
Flare nut
Vinyl clamps (supplied)
Approx. 140 — 180 kg-cm
(120 — 160 Ibs-in.)
1015_X_I
1/4" (6.35 mm)
Fig. 7-7
Approx. 680 — 820 kg-cm
(590 — 710 lbs-in.)
5/8" (15.88 mm)
7-6. Insulating the Refrigerant Tubing
Always insulate tubes after
Refrigerant tubing and insulator
(not supplied)
Drain insulator
and clamp.
Large
Drain pipe and insulator
(not supplied)
CAUTION
completing leak tests on all
connection points.
(supplied)
Important
Packing
clamp.
Small
hose band
(supplied)
To avoid condensation and water leaks, the wide and
narrow tubes must be insulated with the supplied
insulation materials.
Insulation
tape
Vinyl
clamp
insulator
Flare
Taping the flare nuts
Seal
Wind white insulation tape around the flare nuts at the
wide and narrow tube connections. Place the seal
(supplied) on the unit. Then cover up the tubing
connections with the flare nut insulator, and cover the
gap at the union with the supplied black insulation
tape. Finally, fix the insulator at both ends with vinyl
clamps. (Fig. 7-7)
0558_X_I
Never grasp the drain or refrigerant connecting
outlets when moving the unit.
Insulation material
Fig. 7-8
The material used for insulation must have good
insuIation characteristics, be easy to use, be age
resistant, and must not easily absorb moisture.
After a tube has been insu-
CAUTION
lated, never try to bend it
because it can cause the
tube to break or crack.
22
S4359128
Important
Insulation
Because capillary tubing is installed in the outdoor unit,
both the wide and narrow tubes of this air conditioner
become cold. Therefore, to prevent heat loss and wet
floors due to dripping of condensation water, both
tubes must be well insulated with proper insulation
material. The thickness of the insulation material
should be a min. 8 mm (5/16").
Thickness:
Min. 5/16 in.
Thickness:
Min. 5/16 in.
Narrow tube
Wide tube
0999_C_I
7-7. Taping the Tubes
(1) At this time, the refrigerant tubes (and electrical
wiring if local codes permit) should be taped with
armoring tape in 1 bundle. To prevent the con-
densation from overflowing the drain pan, keep
the drain hose separate from the refrigerant
tubing.
(2) Wrap the armoring tape from the bottom of the
outdoor unit to the top of the tubing where it
enters the wall. As you wrap the tubing, overlap
half of each previous tape turn. (Fig. 7-9)
Clamp
Drain hose
Insulated tubes
(3) Clamp the tubing bundle to the wall, using 1
clamp about every 3 feet.
NOTE
Do not wind the armoring tape too tightly since this will
decrease the heat insulation effect. Also ensure that
the condensation drain hose splits away from the
bundle and drips clear of the unit and the tubing.
0136_M_I
Fig. 7-9
7-8. Finishing the Installation
Apply putty here
After finishing insulating and taping over the tubing,
use sealing putty to seal off the hole in the wall to
prevent rain and draft from entering. (Fig. 7-10)
Tubing
0137_C_I
Fig. 7-10
23
S4359128
8. Air Purging
Indoor unit
Air and moisture remaining in the refrigerant system have
undesirable effects as indicated below. Therefore, they
must be purged completely.
● pressure in the system rises
● operating current rises
Outdoor unit
● cooling (or heating) efficiency drops
● moisture in the air may freeze and block capillary tubing
● water may lead to corrosion of parts in the refrigerant
system
■ Air Purging with a Vacuum Pump (for Test Run)
(1) Check that each tube (both narrow and wide tubes)
between the indoor and outdoor units have been
properly connected and all wiring for the test run has
been completed.Note that both narrow and wide tube
service valves on the outdoor unit are kept closed at
this stage.
Manifold valve
(2) Using an adjustable wrench or box wrench, remove
the valve caps from the service valve on both narrow
and wide tubes.
Pressure
gauge
Lo
Hi
(3) Connect a vacuum pump and a manifold valve (with
pressure gauges) to the service port on the wide tube
service valve. (Fig. 8-1)
Be sure to use a manifold valve
for air purging. If it is not
available, use a stop valve for
this purpose. The “Hi” knob of
the manifold valve must always
be kept closed.
CAUTION
Vacuum pump
1824_M_I
(4) With the “Lo” knob of the manifold valve open, run the
vacuum pump. The operation time for the vacuum
pump varies with tubing length and the capacity of the
pump. The following table shows the amount of time
for evacuation:
Fig. 8-1
Required time for evacuation when capacity
of 100 liter/h vacuum pump is used
If tubing length is
If tubing length is
less than 33 ft. (10 m)
more than 33 ft. (10 m)
10 min. or more
15 min. or more
NOTE
The required time in the above table is calculated based on
the assumption that the ideal (or target) vacuum condition
is around 10 mmHg abs.
24
S4359128
(5) With the vacuum pump still running, close the “Lo”
knob of the manifold valve. Then stop the vacuum
pump.
90° (1/4 turn)
Narrow tube
(6) With the accessory hex wrench, turn the valve stem
on the narrow tube service valve counter-clockwise by
90 degress (1/4 turn) for 10 seconds, and then turn
the stem clockwise to close it again. (Fig. 8-2)
Hex wrench
Wide tube
Be sure to completely insert
the hex wrench before
CAUTION
attempting to turn the valve.
Valve cap
Vacuum hose to manifold valve
(7) Leak test all joints at the tubing (both indoor and
outdoors) with liquid soap. Bubbles indicate a leak. Be
sure to wipe off the soap with a clean cloth.
1825_M_I
Fig. 8-2
(8) With the hex wrench, turn the wide tube service valve
stem counter-clockwise to fully open the valve.
(9) Turn the narrow tube service valve stem counter-
clockwise to fully open the valve.
(10) Loosen the vacuum hose connected to the wide tube
service port slightly to release the pressure. Then,
remove the hose.
(11) Replace the bonnet and flare nut on the wide tube
service port and fasten the flare nut securely with an
adjustable wrench or box wrench or box wrench.
Next, mount the valve cap and tighten it with a torque
wrench (the cap needs to be tightened with the torque
of 170 ibs.·in. (200 kg·cm)). This process is very
important to prevent gas from leaking from the
system.
(12) Test run the air conditioner. (See next page.)
(13) While the air conditioner is running, apply liquid soap
to check for any gas leaks around the service valves
or caps.
(14) If there is no leakage, stop the air conditioner.
(15) Wipe off the soap on the tubing.
This completes air purging with a vacuum pump and the air
conditioner is ready for actual operation.
25
S4359128
9. Test Run
9-1. Performing Test Run
TEST OFF ON
Operation
selector
Be careful since the fan will
CAUTION
start when performing Test
Run.
(1) The Operation Selector is located on the electrical
component box inside the indoor unit. To access the
Operation Selector, press the two latches of the air
intake grille in the direction of the arrow to open the
grille. Open the air intake grille downward.
(Fig. 9-1)
Air filter
Air intake grille
(2) Set the Operation Selector to the “Test” position.
The air conditioner will start running.
1323_M_I
Fig. 9-1
(3) Let the unit run for about 30 minutes and check that
the unit operates normally.
(4) After the Test Run, be sure to reset the Operation
Selector to the “ON” position for normal operation.
The air conditioner continues to run .
(5) Referring to the Operating Instructions, select the
Cooling mode and press the ON / OFF operation
button on the remote control unit, to confirm remote
control unit operation.
Important
Set the Operation Selector at the “ON” position. Other-
wise the unit will stop or will not run correctly.
9-2. Performing Test Run with Optional Wired
Remote Control Unit
Service TEST RUN
switch
(1) Service TEST RUN switch is located on the rear
side of the remote control unit. Set the switch to the
TEST RUN position. (Fig. 9-2)
RUN
TEST
RUN
(2) Referring to the Operating Instructions, select the
cooling mode and press the ON / OFF operation
button on the remote control unit.
(3) The air conditioner will start running 3 minutes after
the ON / OFF operation button is pressed.
(Bottom)
Remote control unit
viewed from rear
(4) Let the unit run for about 30 minutes and check that
it operates normally.
0543_M_I
Fig. 9-2
(5) Press the ON / OFF operation button again to stop
the unit.
Important
Set the Service Test RUN switch at “RUN” position,
otherwise the unit will not run correctly.
26
S4359128
9-3. Basic Function of the Service Valves
The basic function of the service valves are given in Table 7 below.
Narrow Tube Service
Valve (2-Way)
Wide Tube Service
Valve (3-Way)
Action
O-ring
Valve cap
Stem
Shipping
1827_M_I
1826_M_I
Operating and
test running the
air conditioner
1829_M_I
1828_M_I
Measuring
∗
pressure
and gas charging
1831_M_I
1830_M_I
∗
Air purging with a
vacuum pump
1833_M_I
1832_M_I
∗ The service port on the wide tube service
valve uses a Schrader core valve to access
the refrigerant system. Therefore, be sure to
use a hose connector which has a push-pin
inside. (Fig. 9-3)
Service valve
Hose with push-pin
PUSH
1834_M_I
Fig. 9-3
9-4. Pump Down
Pump down means collecting all refrigerant gas in the
system back into the outdoor unit without losing any of
the gas. Pump down is used when the unit is to be
moved or before servicing the refrigerant circuit
valve clockwise all the way to close the service
valve. (Be sure to confirm that the wide tube
service valve is fully open.)
(3) Press the operation button and start cooling
operation.
Pump Down Procedure
Be sure to carry out pump down with the unit in
cooling mode.
(4) When the low pressure gauge reading falls to 1 to
0.5 kg/cm2 (14.2 to 7.1 PSI), fully close the wide
tube valve stem with a standard screwdriver. Then
quickly stop the unit.
(1) Connect the Lo side charging hose of the manifold
valve to the service port on the wide tube service
valve.
(5) Disconnect all gauges and hose, and replace the
bonnets and the valve caps as they were before.
(2) Using a hex wrench, turn the narrow tube service
27