Series 685 and 1085
Auxiliary Battery
Cabinets
Installation
Manual
164201408 Rev. P00
ATTENTION:
Une batterie peut prêsenter un risque de choc êlectrique, de brulure, ou d’incen-
die. Suivre les précautions qui s’imposent.
• Pour le remplacement, utiliser le même nombre et modéle des batteries.
• L’élimination des batteries est règlementée. Consulter les codes locaux à cet
effet.
General Notes About Installing Battery Cabinets
Each battery cabinet is packed and crated separately for shipping. You should
unpack and inspect each cabinet, roll it to its final position, and join it to the UPS
or other cabinets (refer to Chapter 3 or Chaper 4) before installing wiring.
These general installation notes apply to either the Series 685 Battery Cabinet
or the Series 1085 Battery Cabinet:
• Do not tilt battery cabinets more than 10˚ during installation.
• The recommended minimum clearance over each battery cabinet is
305 mm (12 in.).
• The conduit landing plates are removable to add conduit landing holes as
required. The conduit landing plates should be removed when holes are added
to keep metal particles from falling inside the battery cabinet. Plate material is
16 gauge steel (1.5 mm, 0.06 in. thick).
• Low voltage signal wiring must be installed in a separate conduit from the
power wiring.
• Each battery cabinet can be installed as a stand-alone unit or as part of a
redundant joined system.
• The instantaneous trip circuit breakers for the Series 685 and Series 1085
Battery Cabinets must remain set at minimum (full counterclockwise).
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
iii
UPS Systems Using Series 685 and Series 1085 Battery Cabinets
• Powerware 9350 (30 kVA---80 kVA)
• Powerware 9350 (100 kVA---160 kVA)
Conventions Used in This Manual
The text in this manual uses these conventions:
• Bold type highlights important concepts in discussions and key terms in
procedures.
• Italic type highlights notes and new terms where they are defined.
• Rectangular boxes containing bold type are warnings or cautions that pertain to
the battery system or its electrical connections.
In this manual, the term UPS refers only to the UPS cabinet and its internal
elements. The term UPS system refers to your entire power protection system—the
UPS cabinet plus battery cabinets that you have installed.
Read through each installation procedure before you begin it. Perform only those
procedures that apply to the battery system you are installing.
NOTE: The term “Separate” refers to battery cabinets that are not physically
attached to the UPS, are wired with external contractor supplied wiring, and
use a single overcurent protection and disconnect device located near the
batteries.
The term “Integral” refers to battery cabinets that are physically attached to
the UPS and the wiring between them is internal. The power wiring is
supplied with the system, and they use the UPS battery switch as the battery
isolation device.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
iv
Installation Manual 164201408 Rev. P00 053002
Table of Contents
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
Typical Battery Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Identification of Your Battery System . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
For More Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Getting Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
2
4
4
2 Unpacking Your Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . .
5
5
5
5
6
7
9
10
Preparing Your Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preparing for Wiring the Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . .
Inspecting and Unpacking Each Cabinet . . . . . . . . . . . . . . . . . . . . . . . . .
Unloading the Battery Cabinet from the Pallet . . . . . . . . . . . . . . . . . . . . .
Creating an Installation Plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
NOTES: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Connecting to Powerware 9350 30 thru 160 . . . . . . . . . . . . . . .
11
The Powerware 9350 UPS with Integral Battery Cabinets . . . . . . . . . . .
Powerware 9350 UPS with Separately Located Battery Cabinets . . . .
Separate Installation of Series 685 Battery Cabinets . . . . . . . . . . . . . . .
Separate Installation of Series 1085 Battery Cabinets . . . . . . . . . . . . . .
Completing the Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Checklist for Powerware 9350 30 through 160 . . . . . . . . . .
11
20
21
23
27
27
4 Connecting to Powerware 9350---80 and 160 . . . . . . . . . . . . . .
29
The Powerware 9350---80 or 160 with Separate Battery Cabinets . . . .
Completing the Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Checklist for Powerware 9350---80 or 160 . . . . . . . . . . . . . .
30
31
32
5 Installing a Remote Battery Disconnect . . . . . . . . . . . . . . . . . .
33
Appendix A — Customer Information . . . . . . . . . . . . . . . . . . . . . . .
A---1
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
v
dddddddddddddddddddddddddddddddddddddddddddddddddddddddddddddddddddddd
ddddddddddddddddddddddddddddddddddddddddddddddddddddddd
List of
Figures
Figure 1. Typical Battery Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 2. UPS with Lineup and Match Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3. UPS with Separate Battery Cabinets (Attached to Each Other) . . . . . . . .
Figure 4. Cabinet as Shipped, with Outer Packaging and Pallet . . . . . . . . . . . . . . . .
Figure 5. Removing Front and Rear Supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
2
3
6
8
Figure 6. UPS with Integral Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 7. Placement of Attaching Brackets, UPS to Battery Cabinet . . . . . . . . . . . . 13
Figure 8. Attaching UPS Base to Series 1085 Base . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 9. Attaching UPS Base to Series 685 Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 10. Series 685 Battery Cabinet Wiring Detail . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 11. Series 685 and 1085 Battery Cabinet Hanger Brackets . . . . . . . . . . . . . . 18
Figure 12. Series 1085 Battery Cabinet Wiring Detail . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 13. UPS with Separately Located Battery Cabinets . . . . . . . . . . . . . . . . . . . . . 20
Figure 14. Placement of Joining Brackets
(Two or More Series 685 Battery Cabinets) . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 15. Connecting Two Series 685 Bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 16. Placement of Joining Brackets
(Two or More Series 1085 Battery Cabinets) . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 17. Connecting Two Series 1085 Bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 18. Battery Connections for a Powerware 9350---80 . . . . . . . . . . . . . . . . . . . . 29
Figure 19. Battery Connections for a Powerware 9350---160 . . . . . . . . . . . . . . . . . . . 30
Figure 20. Remote Battery Disconnect Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 21. Knockout Pattern for Remote Battery Disconnect . . . . . . . . . . . . . . . . . . . 35
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
vi
Installation Manual 164201408 Rev. P00 053002
Introduction
This manual describes how to install the Powerware 9350 Series 685 or
Series 1085 Battery Cabinet (see Figure 1). It contains instructions for
unpacking and inspecting the battery cabinet, locating the battery cabinet with
respect to the UPS, and electrically connecting the battery cabinet to the UPS. The
information you will use depends on the type of UPS and series of battery cabinet
that you purchased.
Typical Battery Cabinets
Series 685 Battery Cabinet
Series 1085 Battery Cabinet
Figure 1. Typical Battery Cabinets
Two basic battery cabinet configurations are possible:
• The UPS and one or more battery cabinets in an integral configuration
(see Figure 2).
• The UPS and one or more battery cabinets separately installed (see Figure 3).
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
1
Identification of Your Battery System
Refer only to the parts of this manual that apply specifically to your system
configuration. See Figures 2 and 3 to determine where to find your system
installation instructions in this manual.
UPS
Battery Cabinet
Figure 2. UPS with Lineup and Match Battery Cabinet
For installation instructions, refer to “The Powerware 9350 UPS with Integral Battery
Cabinets” section of Chapter 3. Refer to Chapter 2, “Unpacking Your Battery Cabinet”
for unpacking instructions.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
2
Installation Manual 164201408 Rev. P00 053002
UPS
Battery Cabinets
Figure 3. UPS with Separate Battery Cabinets (Attached to Each Other)
For installation instructions, refer to “The Powerware 9350 UPS with Separate Battery
Cabinets” section of Chapter 3 or Chapter 4. Refer to Chapter 2, “Unpacking Your
Battery Cabinet” for unpacking instructions.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
3
For More Information
This manual describes how to install your battery cabinet. For more information
about the operation and communications capabilities of your UPS system, refer to
the following:
164201407
Powerwarer 9350 (100 kVA---160 kVA) UPS Installation
Describes the UPS installation procedure; discusses optional
accessories, environmental considerations, weight and point
loading, connection diagrams, and information on other optional
cabinets.
Also describes the UPS Cabinet Control Panel and Monitor
Panel, and explains the functions of the UPS; discusses the
standard features of the UPS and optional accessories;
provides procedures for starting and stopping the UPS, and
information about maintenance and responding to system
events.
Contact your local Powerware Corporation Field Service office for information
about how to obtain copies of these manuals.
Getting Help
If you have a question about any of the information in this manual, or if you have
a question this manual does not answer, please call the Powerware Corporation
Field Service office:
United States
Canada
1-800-843-9433
1-800-461-9166
Outside the U.S.
Call your local representative
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
4
Installation Manual 164201408 Rev. P00 053002
Unpacking Your Battery Cabinet
Each Powerware 9350 Series 685 or Series 1085 Battery Cabinet is shipped
on a separate pallet. Use a forklift or pallet jack to move the packaged cabinets
to the installation site, or as close as possible to the site, before you unload them
from the pallets.
Battery cabinets must be installed in accordance with all applicable codes and
regulations, including the National Electrical Code (NEC), Article 480.
NOTE: Startup and operational checks should be performed only by authorized
service personnel. This service is offered as part of the sales contract for
your battery system.
Preparing Your Site
The basic environmental requirements for the battery system are:
Ambient Temperature Range: 10 --- 40˚C (50 --- 104˚F)
Recommended Operating Range: 20 --- 25˚C (68 --- 77˚F)
Maximum Relative Humidity: 95% noncondensing
The Series 685 or Series 1085 Battery Cabinets use convection cooling to regulate
internal component temperature. Air inlets are in the bottom and top of the
cabinets. You must allow a minimum clearance of 305 mm (12 in.) above each
cabinet for proper air circulation. Additionally, a clearance of 915 mm (36 in.) must
be provided in front of the cabinet for component removal and maintenance .
Maintaining this clearance provides adequate airflow to the front of the cabinet.
Environmental Considerations
The life of the battery system is adversely affected if the installation does not meet
these guidelines:
• The battery cabinet must be installed on a sealed concrete pad
or a sealed concrete floor, or on a raised computer room floor.
• The battery cabinet must be installed in a dust-free, nonconductive
environment.
• The battery cabinet must be installed in a humidity-controlled environment.
Preparing for Wiring the Battery Cabinet
For external wiring requirements, including the minimum AWG size of external
wiring, refer to Appendix A, Table C.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
5
Inspecting and Unpacking Each Cabinet
The first task in preparing for installation is inspecting and unpacking each cabinet.
Cabinets arrive covered with protective packaging material, as shown in Figure 4.
OUTER
PACKAGING
PLY --- FOAM CU SHI ONS
Figure 4. Cabinet as Shipped, with Outer Packaging and Pallet
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
6
Installation Manual 164201408 Rev. P00 053002
1. Carefully inspect the outer packaging for evidence of damage during transit.
CAUTION:
DO NOT INSTALL A DAMAGED CABINET. REPORT ANY DAMAGE TO THE
CARRIER. CONTACT YOUR LOCAL SALES OR SERVICE OFFICE IMMEDIATELY.
2. Use appropriate material handling equipment to move the cabinet to a
convenient unpacking area. Space is provided between the pallets to insert
pallet jack blades on the bottom of the unit.
DANGER:
RISK OF INSTABILITY. DO NOT TILT CABINETS MORE THAN 10 DEGREES
FROM VERTICAL OR THE CABINET MAY TIP OVER.
3. Set each pallet on a firm, level surface, allowing a minimum clearance of 4.6m
(15 ft) on each side for removing the cabinets from the pallets.
4. Cut and remove the steel bands around each cabinet.
5. Remove the protective cardboard covering from the cabinets by vertically cutting
one corner, using a knife blade no longer than 25 mm (1 in.).
6. Remove the corrugated corner protectors, box, plastic bag, and discard or
recycle them in a responsible manner.
CAUTION:
IF YOU CAN SEE DAMAGE IN OR ON A CABINET, DO NOT INSTALL IT.
REPORT ANY DAMAGE TO THE CARRIER. CONTACT YOUR LOCAL SALES OR
SERVICE OFFICE IMMEDIATELY.
Unloading the Battery Cabinet from the Pallet
The battery cabinet is bolted to a pallet consisting of four angle metal supports
secured to laminated plywood/foam cushions. The foam cushions act as shock
absorbers for the cabinet during shipment.
1. Remove the doors. Remove the retaining screw located inside each door at the
bottom hinge pivot point, then lift the door off. Save the retaining screws for
reinstallation of the doors.
2. Locate the field kit (packed inside of the cabinet). Locate the four 1/2 in. jacking
bolts and install them in the threaded holes in the front and rear supports.
Place a floor protector underneath each jacking bolt, and screw the bolts down
against them. The floor protectors protect the floor from being marred by the
jacking bolts.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
7
LEFT HAND
DOOR
(Step 1)
FOAM
SIDE
SUPPORT
CUSHION
FRONT
SUPPORT
2
1
FLOOR
PROTECTOR
(Step 2)
2
2
2
1
JACKING
BOLT
(Step 2)
1
2
(Step 3)
(Step 8)
Figure 5. Removing Front and Rear Supports
3. Loosen, but do not remove, the hardware holding the foam cushions to the front
and rear supports (labeled “1” in Figure 5).
WARNING: SERIOUS INJURY MAY OCCUR!
BATTERY CABINETS ARE EXTREMELY HEAVY. IF UNLOADING INSTRUCTIONS
ARE NOT CLOSELY FOLLOWED, CABINET MAY TIP.
4. Turn each jacking bolt consecutively, two full turns, until the foam cushions clear
the floor by approximately 3 mm (1/8 in.).
DANGER: RISK OF INSTABILITY!
TURNING THE JACKING BOLTS UNEVENLY MAY CAUSE THE CABINET TO
BECOME UNBALANCED. TO PREVENT TIPPING THE CABINET, RAISE AND
LOWER THE JACKING BOLTS EVENLY.
DANGER: CABINET MAY TIP!
THE BATTERY CABINET SHOULD ONLY BE RAISED APPROXIMATELY 3 mm
(1/8 in.) ABOVE THE FLOOR (JUST ENOUGH TO ALLOW REMOVAL OF THE
FOAM CUSHIONS).
5. After the foam cushions clear the floor, remove the hardware loosened in Step 3.
Pull the foam cushions out from under the battery cabinet. Please discard or
recycle them in a responsible manner.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
8
Installation Manual 164201408 Rev. P00 053002
DANGER: CABINET MAY FALL!
DO NOT LOOSEN THE HARDWARE ATTACHING THE SIDE OR FRONT
SUPPORTS TO THE CABINET BASE, OR THE FRONT AND SIDE SUPPORTS
TO EACH OTHER, AT THIS TIME.
THE CABINET MUST BE LOWERED BY THE JACKING BOLTS BEFORE THE
SUPPORTS CAN BE REMOVED.
6. Carefully and evenly lower the cabinet by turning each jacking bolt consecutively
two full turns (maximum) until the supports contact the floor, and the cabinet is
no longer supported by the jacking bolts.
7. After the battery cabinet is resting on the floor, remove the jacking bolts and
discard or recycle them in a responsible manner.
8. Remove the hardware, labeled “2” in Figure 5, holding the front, rear and side
supports to the cabinet base. Discard or recycle the hardware and support
brackets in a responsible manner.
9. Replace the doors that were removed in Step 1. The battery cabinet is now
ready to be rolled to its final location.
10. Repeat Steps 1 through 9 for each cabinet you are preparing to install.
Creating an Installation Plan
Before beginning to install your battery cabinet, you should be sure that you
understand the portions of this manual that apply to your system. Use the
procedures and illustrations in the following sections to create a logical plan for
installing the battery cabinet you purchased. Refer to Chapter 3, “Connecting to
Powerware 9350 30---160” to help plan your installation.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
9
NOTES:
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
10
Installation Manual 164201408 Rev. P00 053002
Connecting to Powerware 9350 30---160
The method you use to install your battery cabinets depends on which
UPS you have. For the purpose of discussion, this chapter uses the term UPS
to refer to the UPS cabinet, and the term battery cabinet to refer to any battery
cabinet. There are two different sizes of battery cabinets, but the procedure for
connecting the cabinets to your UPS system is the same.
• Joining one or more battery cabinets to the UPS
• One or more battery cabinets separately located from the UPS.
The Powerware 9350 UPS with Integral Battery Cabinets
Use this procedure to attach a Powerware 9350 Series 685 or Series 1085 Battery
Cabinet to any Powerware 9350 UPS cabinet (see Figure 6).
Figure 6. UPS with Integral Battery Cabinet
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
11
1. Make sure that the UPS is properly installed and secured with its leveling feet.
2. Roll the battery cabinet to a spot near the right-hand side of the UPS, as
shown in Figure 7.
3. The field kit is attached with cable ties to the frame inside the door. Remove
and retain the field kit for later use.
4. If necessary, remove the cosmetic covers and hanger brackets from the
right-hand side of the UPS. Save covers, screws, and brackets for later reuse.
5. Push the battery cabinet toward the UPS cabinet until the doors are flush with
each other.
6. Three cabinet attachment brackets are provided for securing each cabinet at
the top and bottom. Two flat brackets join the tops of the cabinets, one at the
front and one at the back. A larger flat bracket joins the cabinets at the
bottom. Attach the flat brackets to the cabinet tops first.
7. For Series 685 Battery Cabinets, remove the right-hand screw from the top
right door hinge of the UPS cabinet. Align the hole in one flat bracket over this
screw hole, and the other hole over the hole in the top of the battery cabinet.
Replace the screw in the hinge, and attach the other end of the bracket to the
top of the battery cabinet using an M4×10 hex screw from the field kit (see
Figure 7).
8. For Series 1085 Battery Cabinets, remove the right-hand screw from the top
right door hinge of the UPS cabinet, and the right-hand screw from the top left
door hinge of the battery cabinet. Align the holes in the flat bracket over these
screw holes and then replace the screws in the hinges (see Figure 7).
9. Align the holes in the other small flat bracket with the two holes in the top rear
of the UPS and the battery cabinet. Attach each end to its mating hole using
an M4×10 hex screw from the field kit (see Figure 7).
NOTE: Perform Steps 10 through 13 for the Series 1085 Battery Cabinet.
Perform Steps 14 through 18 for the Series 685 Battery Cabinet.
10. Locate the large flat bracket from the field kit. Place one end of the bracket
over the stud on the bottom side of the UPS cabinet lower right-hand hinge,
and the other end over the stud on the bottom side of the lower right-hand
hinge on the Series 1085 Battery Cabinet (see Figure 8).
11. Attach the bracket to the hinges with two M8 self-locking nuts from the field kit.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
12
Installation Manual 164201408 Rev. P00 053002
Screw from kit
Two small brackets go here
(see detail at left)
Back
of UPS
Back of 685 and 1085
Battery Cabinet
Bracket from kit
Existing Screw
Bracket from kit
Screw from kit
Front of 685
Front of
UPS
Battery Cabinet
UPS
Battery
Cabinet
Existing Screw
Cabinet
Large bracket goes here
(see Figure 8 for Series 1085)
Existing Screw
Bracket from kit
(see Figure 9 for Series 685)
NOTE: When cabinets are properly aligned,
all cabinet doors will be flush with each other.
Front of 1085
Front of
UPS
Battery Cabinet
Figure 7. Placement of Attaching Brackets, UPS to Battery Cabinet
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
13
TOP VIEW
Ground Wire
Ground Stud
Bracket from kit
Nut from kit
Existing hinge
FRONT VIEW
Nut from kit
Front of 1085
Battery Cabinet
Front of
UPS
Figure 8. Attaching UPS Base to Series 1085 Base
12. Route the ground wire (from the field kit) from the customer ground stud in the
battery cabinet, under the lower right-hand battery tray, through the access
hole in the side panel of the UPS, and attach to customer ground stud in the
UPS cabinet. Hardware is provided on each ground stud.
13. Repeat Steps 2 through 12 to attach additional Series 1085 Battery Cabinets to
the other side of the first battery cabinet. Level the cabinets with the leveling
screws.
14. Locate the cabinet connecting bracket from the field kit. Attach the bracket to
the lower right-hand side of the Series 685 base using 2 M4 screws.
15. Locate the large flat bracket from the field kit. Place one end of the bracket
over the stud on the bottom side of the UPS cabinet lower right-hand hinge,
and the other end over the stud on the bottom side of the lower right-hand
hinge on the Series 685 Battery Cabinet (see Figure 9).
16. Attach the bracket to the hinges with two M8 self-locking nuts from the field kit.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
14
Installation Manual 164201408 Rev. P00 053002
TOP VIEW
Ground Wire
Ground Stud
Bracket from kit
Bracket from kit
FRONT VIEW
Nut from kit
Nut from kit
Screw from kit
Front of 685
Battery Cabinet
UPS
Front of
Figure 9. Attaching UPS Base to Series 685 Base
17. Locate the ground wire from the field kit. Route the ground wire from the
customer ground stud in the battery cabinet, under the lower right-hand battery
tray, through the access hole in the side panel of the UPS, and attach to
customer ground stud in the UPS cabinet. Hardware is provided on each
ground stud.
18. Repeat Steps 2 through 17 to attach additional Series 685 Battery Cabinets to
the other side of the first battery cabinet. Level the cabinets with the leveling
screws.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
15
To Electrically Connect Integral Battery Cabinets Together and to the UPS:
1. All battery cabinets will arrive at your site with each battery connection string
electrically disconnected. If you are installing more than one battery cabinet,
perform Steps 2 through 6 for each cabinet. The battery cabinet adjacent to
the UPS will be the only cabinet directly connected to the UPS.
WARNING:
LETHAL VOLTAGE WILL BE PRESENT WHEN PERFORMING THE REMAINING
STEPS IN THIS SECTION AND SUBSEQUENT SECTIONS.
2. After making sure that all battery breakers are in the OFF position, connect the
string of battery trays together by mating the loose red connector from each
tray to the fixed black connector mounted on the front edge of the tray above it
(see Figure 10 for Series 685 and Figure 13 for Series 1085).
3. Find the red (positive) and black (negative) cables supplied coiled inside the
cabinet. These cables are provided half-stripped to facilitate attaching to the
lugs in the cabinet. Use double pole compression lugs to secure the wires to
the unit terminal blocks.
4. Wire the UPS to the Battery cabinet by attaching the provided cable from
E4(+) to “DC+” and E5( --- ) to “DC --- ” power interconnection cables provided.
The provided red(+) and black(---) cables are already cut to length.
5. Remove the cable tie securing the battery breaker sensing cable.
6. Locate the battery breaker sensing cable in the right-hand Battery cabinet.
Route this connector into the cabinet to the immediate left and mate with the
matching connector in the bottom of that cabinet. Connect all battery cabinets
together this way.
7. Locate control harness with semi-stripped ends in Battery cabinet. Connect
this to the CUSTTB terminal strip in the UPS. Route the battery cable to the
immediate right and mate with the matching connector in the bottom of the
UPS cabinet.
8. Repeat Steps 2 through 7 for each battery cabinet to be joined.
9. Mount the side panel to the side of the right-hand battery cabinet:
a. Mount the hanger brackets to the top side of the right-hand battery
cabinet using M4 screws (see Figure 11).
b. Hang the side panel on the hanger brackets and align with the front
and rear of the battery cabinet.
c. Secure the side panel at the bottom using M4 hex head screws.
10. Secure all battery cabinets by closing and latching the doors.
11. Secure the UPS by reinstalling safety shields and closing and latching the
doors.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
16
Installation Manual 164201408 Rev. P00 053002
BATTERY
BREAKER
FIXED RIGHT BATTERY
POWER CONNECTOR
(BLACK)
STRING
CONNECTORS
(RED)
CONNECTION FOR
REMOTE
MONITORING
CUSTOMER CONNECTION
CABINET GROUNDING
(REMOTE INSTALLATION)
CABINET TO CABINET
TERMINAL (+) (LEFT)
CABINET TO CABINET
TERMINAL (---) (RIGHT)
GROUNDING STUD
LOCATION (2X)
GROUNDING STUD
LOCATION (2X)
CABLE ACCESS LOCATION
LEVELING FEET
Figure 10. Series 685 Battery Cabinet Wiring Detail
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
17
HANGER BRACKET LOCATION
(SECURED WITH SCREWS)
Series 685 Cabinet
Series 1085 Cabinet
CABINET TO CABINET
CABLE ACCESS AREA
(EACH SIDE)
Figure 11. Series 685 and 1085 Battery Cabinet Hanger Brackets
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
18
Installation Manual 164201408 Rev. P00 053002
BATTERY
BREAKER
FIXED RIGHT BATTERY
POWER CONNECTOR
(BLACK)
STRING
CONNECTORS
(RED)
CONNECTION FOR
REMOTE
MONITORING
CUSTOMER CONNECTION
CABINET GROUNDING
(REMOTE INSTALLATION)
CABINET TO CABINET
TE R M I N A L ( --- )
NOTE: COMPRESSION LUGS
SHOWN ARE USED FOR
REMOTE INSTALLATION
ONLY
CABINET TO CABINET
TERMINAL (+)
GROUNDING STUD
LOCATION (2X)
CABLE ACCESS LOCATION
LEVELING FEET
Figure 12. Series 1085 Battery Cabinet Wiring Detail
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
19
Powerware 9350 UPS with Separately Located Battery Cabinets
Use this procedure to wire a separately located Series 685 or Series 1085 Battery
Cabinet to any Powerware 9350 UPS cabinet (see Figure 14).
In this situation, the Battery cabinets are remotely loacted
from the UPS and are lineup and match with each other.
Figure 13. UPS with Separately Located Battery Cabinets
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
20
Installation Manual 164201408 Rev. P00 053002
Two small brackets go here
(see detail at left)
Back of
Battery Cabinet #2
Back of
Battery Cabinet #1
Screw from kit
Screw from kit
Bracket from kit
Existing Screw
Screw from kit
Bracket from kit
BATTERY
BATTERY
Front of
Battery Cabinet #2
CABINET #1
CABINET #2
Front of
Battery Cabinet #1
Large bracket goes here
(see Figure 15)
NOTE: When cabinets are properly aligned, all cabinet doors
will be flush with each other.
Figure 14. Placement of Joining Brackets (Two or More Series 685 Battery Cabinets)
Separate Installation of Series 685 Battery Cabinets
1. Remove the right-hand screw from the top door hinge of battery cabinet #1.
Align the hole in one flat bracket over this screw hole, and the other hole over
the hole in the top of battery cabinet #2. Replace the screw in the hinge, and
attach the other end of the bracket by using an M4×10 hex screw from the
field kit (see Figure 14).
2. Align the holes in the other small flat bracket with the two holes in the top rear
of battery cabinets #1 and #2. Attach each end to its mating hole using an
M4×10 hex screw from the field kit (see Figure 14).
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
21
Grounding cable
Ground
Studs
Existing hinge
Nut from kit
Bracket from kit
Bracket from kit
Nut from kit
Screw from kit
Front of
Battery Cabinet #2
Front of
Battery Cabinet #1
Figure 15. Connecting Two Series 685 Bases
3. Locate the cabinet connecting bracket and two M4×10 hex head screws from
the field kit. Attach the bracket to the lower right-hand side of battery cabinet
#2 using the two screws (see Figure 15).
4. Locate the large flat bracket from the field kit. Place the bracket over the stud
on the bottom side of battery cabinet #1 lower hinge, and over the stud on the
bottom side of the cabinet connecting bracket on battery cabinet #2. Attach
the bracket with two M8 self-locking nuts from the field kit (see Figure 15).
5. Locate the ground wire from the field kit. Route the ground wire from the
customer ground stud in battery cabinet #1, under the lower right-hand battery
tray, into the cable access area in battery cabinet #2, and attach to customer
ground stud. Hardware is provided on each ground stud.
6. Repeat Steps 1 through 5 to join additional Series 685 Battery Cabinets
together.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
22
Installation Manual 164201408 Rev. P00 053002
Back of
Battery Cabinet #2
Back of
Battery Cabinet #1
Two small brackets go here
(see detail at left)
Screw from kit
Screw from kit
Bracket from kit
Existing Screw
Existing Screw
Bracket from kit
BATTERY
CABINET #1
BATTERY
CABINET #2
Large bracket goes here
Front of
Battery Cabinet #2
Front of
Battery Cabinet #1
(see Figure 17)
NOTE: When cabinets are properly aligned, all cabinet doors
will be flush with each other.
Figure 16. Placement of Joining Brackets (Two or More Series 1085 Battery Cabinets)
Separate Installation of Series 1085 Battery Cabinets
1. Remove the right-hand screw from the top door hinge of battery cabinet #1.
Align the hole in one flat bracket over this screw hole, and the other hole over
the hole in the top of battery cabinet #2. Replace the screw in the hinge, and
attach the other end of the bracket by using an M4×10 hex screw from the
field kit (see Figure 16).
2. Align the holes in the other small flat bracket with the two holes in the top rear
of battery cabinets #1 and #2. Attach each end to its mating hole using an
M4×10 hex screw from the field kit (see Figure 16).
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
23
Ground
Wire
Ground
Studs
Bracket from kit
Nut from kit
Existing
hinge
Nut from kit
Battery Cabinet #1
Front of
Front of
Battery Cabinet #2
Figure 17. Connecting Two Series 1085 Bases
3. Locate the large flat bracket from the field kit. Place the bracket over the stud
on the bottom side of battery cabinet #1 lower hinge, and over the stud on the
bottom side of battery cabinet #1 lower hinge. Attach the bracket with two M8
self-locking nuts from the field kit (see Figure 17).
4. Locate the ground wire from the field kit. Route the ground wire from the
customer ground stud in battery cabinet #1, under the lower right-hand battery
tray, into the cable access area in battery cabinet #2, and attach to customer
ground stud. Hardware is provided on each ground stud.
5. Repeat Steps 1 through 4 to join additional Series 1085 Battery Cabinets
together.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
24
Installation Manual 164201408 Rev. P00 053002
To Electrically Connect Separate Battery Cabinets to the UPS:
1. All battery cabinets will arrive at your site with each battery connection string
electrically disconnected. If you are installing more than one battery cabinet,
perform Steps 2 through 6 for each cabinet. Battery cabinet #1 (the left-hand
cabinet) will be the only cabinet directly connected to the UPS.
WARNING:
LETHAL VOLTAGE WILL BE PRESENT WHEN PERFORMING THE REMAINING
STEPS IN THIS SECTION AND SUBSEQUENT SECTIONS.
2. After making sure that all battery breakers are in the OFF position, connect the
string of battery trays together by mating the loose red connector from each
tray to the fixed black connector mounted on the front edge of the tray above it
(see Figure 10 for Series 685 and Figure 13 for Series 1085 for location of all
items discussed in this section).
3. Find the red (positive) and black (negative) cables supplied coiled inside the
cabinet. These cables are provided half-stripped to facilitate attaching to the
lugs in the cabinet. Use double pole compression lugs to secure the wires to
the unit terminal blocks.
4. Remove the cable tie securing the battery breaker sensing cable.
5. Locate the battery breaker sensing cable in the right-hand battery cabinet.
Route this connector into the cabinet to the immediate left and mate with the
matching connector in the bottom of that cabinet. Connect all battery cabinets
together this way.
6. Repeat Steps 2 through 5 for each battery cabinet to be joined.
7. Route cables from positive (+) and negative (---) terminals in the bottom of
battery cabinet #1 through conduit (top or bottom entry) to terminals E4 and
E5 of the UPS cabinet. See Figure 10 or Figure 12 for location of positive (+)
and negative (---) terminals.
a. Refer to Appendix A, Table C to size wire for connecting the battery
cabinets to the remotely located UPS cabinet.
b. See Drawing 164201408---1 in Appendix A for Series 685 Battery
Cabinet top or bottom conduit landing locations.
c. See Drawing 164201408---2 in Appendix A for Series 1085 Battery
Cabinet top or bottom conduit landing locations.
d. See Installation Manual 164200253 for Powerware 9350 30---80 kVA top
or bottom conduit landing locations.
e. See Installation Manual 164200292 for Powerware 9350 100---160 kVA
top or bottom conduit landing locations. The conduit landing plates are
removable to add conduit landing holes as required. The conduit
landing plates should be removed when holes are added to keep metal
particles from falling inside the battery cabinet.
f. Refer to Chapter 5, Table C for remote battery disconnect circuit
breaker information.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
25
8. Mount the side panels to the sides of the first and last battery cabinets:
a. Mount the hanger brackets to the top side of the battery cabinets using
M4 screws (see Figure 11).
b. Hang the side panel on the hanger brackets and align it with the front
and rear of the battery cabinet.
c. Secure the side panel at the bottom using M4 hex head screws.
9. Secure all battery cabinets by closing and latching the doors.
10. Secure the UPS by reinstalling safety shields and closing and latching the
doors.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
26
Installation Manual 164201408 Rev. P00 053002
Completing the Installation Checklist
The final step in installing your battery cabinet is to complete the Installation
Checklist. This checklist ensures that you have installed all hardware, cables,
and other equipment. Completing all items on the checklist will ensure a smooth
installation. Make a copy of the Installation Checklist before filling it out, and retain
the original.
After completing your installation, a service representative will be able to verify the
operation of your battery cabinet, and commission it to support your critical load.
The service representative cannot perform any installation tasks other than verifying
that the battery cabinet has been correctly installed. Service personnel may request
a copy of the completed Installation Checklist to be sure you have completed all
applicable equipment installation requirements.
NOTE:
The Installation Checklist MUST be completed prior to starting up the UPS system
for the first time.
Installation Checklist for Powerware 9350 30 through 160
-All packing materials and restraints have been removed from each cabinet.
-Each cabinet in the battery system is placed in its correct location.
-All cabinets are bolted together.
-A ground wire is installed between all cabinets that are bolted together.
-All conduits and cables are properly routed to the battery cabinets.
-A ground conductor is properly installed.
-Battery cables and harness are terminated on the K2 battery contactor E4 and E5 in
the UPS cabinet.
-Internal battery cabinet connections have been completed (bus bars, plugs, etc.)
-Air conditioning equipment is installed and operating correctly.
-The area around the installed battery system is clean and dust-free.
(It is recommended that the battery cabinet be installed on a sealed concrete pad or a
sealed concrete floor.)
-Adequate working area exists around the battery cabinet and other cabinets.
-Adequate lighting is provided around all battery cabinet equipment.
-A remote battery disconnect control is mounted in its installed location and its wiring is
terminated inside the battery cabinet (OPTIONAL).
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
27
This Page Intentionally Left Blank.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
28
Connecting to
Powerware 9350---80 and 160
This chapter will explain how to electrically connect your battery cabinets to
your Powerware 9350---80 or 160 UPS.
Figure 18 details the Battery cabinet DC connections and control wiring connection
point in a Powerware 9350---80 UPS. Figure 19 details the same connections in a
Powerware 9350---160 UPS.
NOTE: See Table C in Appendix A for sizing wire for separate battery configurations.
There are no battery cabinet-to-UPS mechanical attachment requirements for this
type of system. However, individual battery cabinets should be attached and
grounded to each other. Please refer to later sections of this chapter for
instructions on these procedures.
CUSTTB terminal block
for control wiring.
Mounted to inside top of
cabinet.
DC INPUT
from battery
to UPS
(E4, E5)
Figure 18. Battery Connections for a Powerware 9350---80
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
29
Powerware 9350---80 or 160 with Separate Battery Cabinets
1. Make sure that the UPS is properly installed and secured.
2. Roll the battery cabinets to their permanent location.
3. Attach and connect the battery cabinets to each other (refer to “The
Powerware 9350 UPS with Separate Battery Cabinets” section of Chapter 3).
4. If necessary, remove the cosmetic covers and doors from the UPS. Save
covers, screws, and brackets for later reuse.
5. Each battery cabinet in your system will have to be individually connected to
terminals E4 and E5.
6. Route cables from positive (+) and negative (---) terminals in the bottom of
each battery cabinet through conduit (top or bottom entry) to terminals E4
and E5 of the UPS cabinet. See Figure 18 or 19 for location of terminals E4
and E5. Refer to Chapter 3, Figure 11 or Figure 13 for location of battery
cabinet positive (+) and negative (---) terminals.
CUSTTB terminal block
for control wiring.
Mounted to inside top of
cabinet.
DC INPUT
from battery
to UPS
(E4, E5)
Figure 19. Battery Connections for a Powerware 9350---160
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
30
Installation Manual 164201408 Rev. P00 053002
7. Mount the side panels to the sides of the first and last battery cabinets:
a. Mount the hanger brackets to the top side of the battery cabinets using
M4 screws (refer to Chapter 3, Figure 11 for location).
b. Hang the side panel on the hanger brackets and align it with the front
and rear of the battery cabinet.
c. Secure the side panel at the bottom using M4 hex head screws.
8. Secure all battery cabinets by closing and latching the doors.
9. Secure the UPS by reinstalling safety shields and closing and latching the
doors.
WARNING:
Initial closing of the battery cabinet breakers or the external battery disconnect
should be performed only in the presence of authorized service personnel.
Completing the Installation Checklist
The final step in installing your battery cabinet is to complete the Installation
Checklist. This checklist ensures that you have installed all hardware, cables, and
other equipment. Completing all items on the checklist will ensure a smooth
installation. Make a copy of the Installation Checklist before filling it out, and retain
the original.
After completing your installation, a service representative will be able to verify the
operation of your battery cabinet, and commission it to support your critical load.
The service representative cannot perform any installation tasks other than verifying
that the battery cabinet has been correctly installed. Service personnel may
request a copy of the completed Installation Checklist to be sure you have
completed all applicable equipment installation requirements.
NOTE:
The Installation Checklist MUST be completed prior to starting up the UPS system
for the first time.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
31
Installation Checklist for Powerware 9350---160
-All packing materials and restraints have been removed from each cabinet.
-Each cabinet in the battery system is placed in its correct location.
-All battery cabinets are bolted together.
-A ground wire is installed between all cabinets that are bolted together.
-All conduits and cables are properly routed to the battery cabinets.
-A ground conductor is properly installed.
-Battery cables and harness are terminated on the battery terminals E4 and E5 in the
UPS cabinet.
-Internal battery cabinet connections have been completed (bus bars, plugs, etc.)
-Air conditioning equipment is installed and operating correctly.
-The area around the installed battery system is clean and dust-free.
(It is recommended that the battery cabinet be installed on a sealed concrete pad or a
sealed concrete floor.)
-Adequate working area exists around the battery cabinet and other cabinets.
-Adequate lighting is provided around all battery cabinet equipment.
-A remote battery disconnect control is mounted in its installed location and its wiring is
terminated inside the battery cabinet (OPTIONAL).
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
32
Installation Manual 164201408 Rev. P00 053002
Installing a Remote Battery Disconnect
The remote battery disconnect is crated separately for shipping. It is enclosed
in a box and is designed to be wall mounted on a surface that can support the
weight and bolt pattern described in this chapter. You can install a remote battery
disconnect anywhere between the remote DC supply and the UPS, according to
national and local codes. Figure 20 shows the remote battery disconnect
enclosure.
SIDE
FRONT
ON
OFF
Figure 20. Remote Battery Disconnect Enclosure
The breaker switch on the remote battery disconnect should be set to ON for
normal UPS operation when DC power is available at the UPS. When service
personnel are performing maintenance on the UPS or battery cabinet, the switch
should be OFF.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
33
You should read and understand these general notes before beginning installation:
• The material and labor for external wiring requirements is to be supplied by
others.
• Power cables and control wiring must be installed in separate conduit.
• The ground conductor is to be sized per NEC Article 250 and local electrical
code requirements.
• The maximum current listed is at the minimum DC operating voltage.
• Nominal voltages listed in this chapter are for a lead-acid battery plant rated per
NEC at 2.00 VDC per cell.
• Battery cabinets must be installed in accordance with all applicable codes and
regulations, including the National Electrical Code (NEC), Article 480.
• The UPS to battery cable should be sized for a total maximum voltage drop of
1% nominal DC link voltage at maximum current.
• The external wiring specifications are outlined in Table C of Appendix A. Tables
A and B in this chapter detail the power cable terminations.
• The remote battery disconnect weighs approximately 11.4 kg (25 lb) and has an
ampere interrupting capacity of 10,000 at 500 VDC.
• Tightening Torque:
28.7 --- 31.1 N-M (255---275 lb-in.)
5/16 in.
Internal Drive Hex Size:
• The knockout pattern for conduit is shown in Figure 21. If a larger size conduit
is required, the contractor may enlarge knockouts at your site during
installation.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
34
Installation Manual 164201408 Rev. P00 053002
E
E
T
T
A
T
A
T
A
A
A
E
E
T
T
T
T
A
E
E
Figure 21. Knockout Pattern for Remote Battery Disconnect
Table A. Remote Battery Disconnect Power Terminations
Terminal
E4 (+)
Size of Pressure Termination
1 --- #8 --- 3/ 0
Terminal Function
UPS Battery Contactor K2 (+)
UPS Battery Contactor K2 (---)
Battery Disconnect (+)
1 --- #8 --- 3/ 0
E5 ( --- )
1 --- #4 --- 300 k cmil
1 --- #4 --- 300 k cmil
1 --- #4 --- 300 k cmil
See Table C (Appendix A)
See Table C (Appendix A)
Breaker (+)
Breaker ( --- )
Battery Disconnect (---)
Breaker (jumper)
Battery Cabinet (+)
Battery Cabinet (---)
Battery Disconnect (jumper)
Stand---alone battery cabinet (+)
Stand --- alone battery cabinet ( --- )
Table B. Battery Cabinet Terminations
Battery Cabinet
Size of Pressure Termination
(1) #2 --- 1/0 kcmil [Breaker (+) & ( --- )]
(1) 3/0 --- 250 kcmil [Breaker (+) & ( --- )]
Series 685
Series 1085
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
35
Table C. Remote Battery Disconnect Circuit Breaker Ratings
UPS Model
9350---40
Circuit Breaker Rating
DC Voltage
420
125
125
175
200
350
350
350
350
600
600
800
800
900
1200
1000
1200
9350---50
480
9350---65
420
9350---80
480
9350---125
9350---130
9350---150
9350---160
9350---200
9350---225
9350---250
9350---300
9350---300
9350---400
9350---400
9350---500
420
420
480
480
420
480
420
480
420
420
480
480
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
36
Installation Manual 164201408 Rev. P00 053002
Appendix A --- Customer Information
The information in the appendix will help you plan for and install your battery
system. The appendix contains these drawings:
164201408---1
164201408---2
164201408---3
164201408---4
Series 685 Battery Cabinet
Series 1085 Battery Cabinet
Remote Interface Connections
Series 685 / 1085 Configurations
NOTE: Outline diagrams and oneline diagrams for the various UPS models are
available in their respective manuals. See this manual for more information.
164201407
Powerwarer 9350 (100 kVA---160 kVA) UPS Installation
and Operation Manual
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
A --- 1
1. The output of the UPS is a separately derived source. Output neutral is bonded
to equipment ground through the main bonding jumper. Refer to NEC Article
250 and local codes for proper grounding practices.
2. Your battery cabinet operating environment must meet the size and weight
requirements shown in Table A:
Table A. Equipment Weight and Point Loading (on casters)
(4 leveling feet are provided)
Weight
Kg (lb)
Point Loading
Kg (lb)
Component
Series 685-J14
Series 685-J17
Series 1085-J27
Series 1085-J31
Series 1085-J37
Series 1085-J47
869 (1915)
1111 (2450)
1429 (3150)
1588 (3500)
1708 (3765)
2178 (4800)
4 at 217 (479)
4 at 278 (613)
8 at 179 (394)
8 at 199 (438)
8 at 214 (471)
8 at 272 (600)
3. The basic environmental requirements for operation of the battery system are:
Ambient Temperature Range: 10 --- 40˚C (50 --- 104˚F)
Recommended Operating Range: 20 --- 25˚C (68 --- 77˚F)
Maximum Relative Humidity: 95% noncondensing
4. Use Class 1 wiring methods (as defined by the NEC) for control wiring. Install
the control wiring in separate conduit from the power wiring. The wire should
be rated at 24 volts, 1 amp minimum.
5. Battery voltage is computed at 2 volts per cell as defined by Article 480 of the
NEC. Rated battery current is computed at 1.8 volts per cell.
6. The battery wiring used between the battery and the UPS should not allow a
voltage drop of more than 1% of nominal DC voltage at rated battery current.
7. A battery disconnect switch is recommended, and may be required by NEC or
local codes when batteries are separately located. The battery disconnect
switch may be supplied as an accessory, and should be installed between the
battery and the UPS.
8. If the conductors used for DC input from the battery cabinet(s) to the UPS are
those provided by the UPS manufacturer, and the UPS and battery cabinet are
manufactured by the same supplier, then it is acceptable if they do not meet the
noted minimum conductor sizes.
Table B. External Ground Wire Requirements for Battery Cabinets
Integral
Tool Size
Battery
Cabinet
Torque
N-M
(lb-in)
UPS
Model
Battery
Series
Battery
Type
# of
Cabinets
or
Wire Size
Battery
Separate
Battery
all
685 or 1085
all
all
all
1/0
7/16I slot
5.6 (50)
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
A --- 2
Installation Manual 164201408 Rev. P00 053002
Table C. External Wiring Requirements (UPS-to-Battery or Remote Disconnect-to-Battery)
NOTE: All specified wire sizes are 90_C rated copper minimum
Battery Cabinet
UPS Cabinet
Wire
UPS
Series/
Model
Battery
Cabinet
Series
Integral
or
Separate
Torque
Torque
Battery
Type*
# of
Cabinets
Size
Tool Size
N-M
Tool Size
N-M
UPS to
Battery
(lb-in)
(lb-in)
B14, B17,
H20
B14, B17,
H20
42.4
22.6
50/30
50/30
50/30
50/30
685
685
1 or 2
1 or 2
Integral Supplied 3/8I hex
Separate 2/0 3/8I hex
Integral Supplied 3/8I hex
Separate 3/0 3/8I hex
1/4I hex
1/4I hex
3/8I hex
3/8I hex
(375)
(200)
42.4
(375)
42.4
(375)
42.4
(375)
22.6
(200)
42.4
(375)
42.4
(375)
1, 2, 3,
or 4
1, 2, 3,
or 4
1085R
1085R
B10
B10
B27, B31,
B37, B47,
H30, H40,
H50
B27, B31,
B37, B47,
H30, H40,
H50
1, 2, 3,
or 4
42.4
22.6
50/30
50/30
1085
1085
Integral Supplied 3/8I hex
1/4I hex
(375)
(200)
1, 2, 3,
or 4
42.4
(375)
22.6
(200)
Separate
2/0
3/8I hex
1/4I hex
B14, B17,
H20
B14, B17,
H20
42.4
22.6
50/40
50/40
50/40
50/40
685
685
1 or 2
1 or 2
Integral Supplied 3/8I hex
Separate 2/0 3/8I hex
Integral Supplied 3/8I hex
Separate 3/0 3/8I hex
1/4I hex
1/4I hex
3/8I hex
3/8I hex
(375)
(200)
42.4
(375)
42.4
(375)
42.4
(375)
22.6
(200)
42.4
(375)
42.4
(375)
1, 2, 3,
or 4
1, 2, 3,
or 4
1085R
1085R
B10
B10
B27, B31,
B37, B47,
H30, H40,
H50
B27, B31,
B37, B47,
H30, H40,
H50
1, 2, 3,
or 4
42.4
22.6
50/40
50/40
1085
1085
Integral Supplied 3/8I hex
1/4I hex
(375)
(200)
1, 2, 3,
or 4
42.4
(375)
22.6
(200)
Separate
2/0
3/8I hex
1/4I hex
B14, B17,
H20
B14, B17,
H20
42.4
22.6
50/50
50/50
50/50
50/50
685
685
1 or 2
1 or 2
Integral Supplied 3/8I hex
Separate 2/0 3/8I hex
Integral Supplied 3/8I hex
Separate 3/0 3/8I hex
1/4I hex
1/4I hex
3/8I hex
3/8I hex
(375)
(200)
42.4
(375)
42.4
(375)
42.4
(375)
22.6
(200)
42.4
(375)
42.4
(375)
1, 2, 3,
or 4
1, 2, 3,
or 4
1085R
1085R
B10
B10
B27, B31,
B37, B47,
H30, H40,
H50
B27, B31,
B37, B47,
H30, H40,
H50
1, 2, 3,
or 4
42.4
22.6
50/50
50/50
1085
1085
Integral Supplied 3/8I hex
1/4I hex
(375)
(200)
1, 2, 3,
or 4
42.4
(375)
22.6
(200)
Separate
2/0
3/8I hex
1/4I hex
B14, B17,
H20
B14, B17,
H20
42.4
22.6
80/50
80/50
80/50
685
685
1 or 2
1 or 2
Integral Supplied 3/8I hex
Separate 2/0 3/8I hex
Integral Supplied 3/8I hex
1/4I hex
1/4I hex
3/8I hex
(375)
(200)
42.4
(375)
42.4
(375)
22.6
(200)
42.4
(375)
1, 2, 3,
or 4
1085R
B10
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
A --- 3
Table C. External Wiring Requirements (UPS-to-Battery or Remote Disconnect-to-Battery)
NOTE: All specified wire sizes are 90_C rated copper minimum
Battery Cabinet
UPS Cabinet
Wire
UPS
Battery
Cabinet
Series
Integral
or
Torque
Torque
Size
Battery
# of
Series/
Model
N-M
N-M
Tool Size
Tool Size
3/8I hex
1/4I hex
UPS to
Battery
Type*
Cabinets
Separate
(lb-in)
(lb-in)
1, 2, 3,
or 4
42.4
(375)
42.4
(375)
80/50
80/50
1085R
1085
B10
Separate
3/0
3/8I hex
B27, B31,
B37, B47,
H30, H40,
H50
1, 2, 3,
or 4
42.4
(375)
22.6
(200)
Integral Supplied 3/8I hex
B27, B31,
B37, B47,
H30, H40,
H50
1, 2, 3,
or 4
42.4
(375)
22.6
(200)
80/50
1085
Separate
2/0
3/8I hex
1/4I hex
H20
B14, B17
H20
1
2
1
2
42.4
22.6
80/60
80/60
685
685
Integral Supplied 3/8I hex
Separate 2/0 3/8I hex
Integral Supplied 3/8I hex
Separate 3/0 3/8I hex
1/4I hex
(375)
(200)
42.4
(375)
22.6
(2)
1/4I hex
B14, B17
42.4
(375)
42.4
(375)
42.4
(375)
42.4
(375)
80/60
80/60
1085R
1085R
B10
B10
1
1
3/8I hex
3/8I hex
B27, B31,
B37, B47,
H30, H40,
H50
B27, B31,
B37, B47,
H30, H40,
H50
1, 2, 3,
or 4
42.4
22.6
80/60
80/60
1085
1085
Integral Supplied 3/8I hex
1/4I hex
(375)
(200)
1, 2, 3,
or 4
42.4
(375)
22.6
(200)
Separate
2/0
3/8I hex
1/4I hex
H20
1
2
1
2
42.4
22.6
80/80
80/80
685
685
Integral Supplied 3/8I hex
1/4I hex
B14, B17,
H20
(375)
(200)
H20
42.4
(375)
22.6
(200)
Separate
2/0
3/8I hex
1/4I hex
B14, B17,
H20
B27, B31,
B37, B47,
H30, H40,
H50
B27, B31,
B37, B47,
H30. H40,
H50
1, 2, 3,
or 4
42.4
22.6
80/80
80/80
1085
1085
Integral Supplied 3/8I hex
1/4I hex
(375)
(200)
1, 2, 3,
or 4
42.4
(375)
22.6
(200)
Separate
2/0
3/8I hex
1/4I hex
B14, B17,
H20
B14, B17,
H20
42.4
42.4
160/100
160/100
685
685
2
2
Integral Supplied 3/8I hex
Separate 3/0 3/8I hex
3/8I hex
(375)
(375)
42.4
(375)
42.4
(375)
3/8I hex
B27, B31,
B37, B47,
H30, H40,
H50
B27, B31,
B37, B47,
H30, H40,
H50
1, 2, 3,
or 4
42.4
42.4
160/100
160/100
1085
1085
Integral Supplied 3/8I hex
3/8I hex
(375)
(375)
1, 2, 3,
or 4
42.4
(375)
42.4
(375)
Separate
3/0
3/8I hex
3/8I hex
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
A --- 4
Installation Manual 164201408 Rev. P00 053002
Table C. External Wiring Requirements (UPS-to-Battery or Remote Disconnect-to-Battery)
NOTE: All specified wire sizes are 90_C rated copper minimum
Battery Cabinet
UPS Cabinet
Wire
UPS
Series/
Model
Battery
Cabinet
Series
Integral
or
Separate
Torque
Torque
Size
Battery
Type*
# of
Cabinets
N-M
N-M
Tool Size
Tool Size
UPS to
Battery
(lb-in)
(lb-in)
42.4
42.4
160/125
160/125
685
685
H20
H20
2
2
Integral Supplied 3/8I hex
3/8I hex
(375)
(375)
300
42.4
(375)
42.4
(375)
Separate
3/8I hex
3/8I hex
kcmil
B27, B31,
B37, B47,
H30, H40,
H50
B27, B31,
B37, B47,
H30, H40,
H50
42.4
42.4
160/125
160/125
1085
1085
2, 3, or 4 Integral Supplied 3/8I hex
3/8I hex
(375)
(375)
300
42.4
(375)
42.4
(375)
2, 3, or 4 Separate
3/8I hex
3/8I hex
kcmil
42.4
42.4
160/150
160/150
685
685
H20
H20
2
2
Integral Supplied 3/8I hex
3/8I hex
(375)
(375)
300
42.4
(375)
42.4
(375)
Separate
3/8I hex
3/8I hex
kcmil
B27, B31,
B37, B47,
H30, H40,
H50
B27, B31,
B37, B47,
H30, H40,
H50
42.4
42.4
160/150
160/150
1085
1085
2, 3, or 4 Integral Supplied 3/8I hex
3/8I hex
(375)
(375)
300
42.4
(375)
42.4
(375)
2, 3, or 4 Separate
3/8I hex
3/8I hex
kcmil
42.4
42.4
160/160
160/160
685
685
H20
H20
2
2
Integral Supplied 3/8I hex
3/8I hex
(375)
(375)
300
42.4
(375)
42.4
(375)
Separate
3/8I hex
3/8I hex
kcmil
B27, B31,
B37, B47,
H30, H40,
H50
B27, B31,
B37, B47,
H30, H40,
H50
1, 2, 3,
or 4
42.4
42.4
160/160
160/160
1085
1085
Integral Supplied 3/8I hex
3/8I hex
(375)
(375)
1, 2, 3,
or 4
350
42.4
(375)
42.4
(375)
Separate
3/8I hex
3/8I hex
kcmil
* BATTERY TYPE DESIGNATIONS: B = C&D, H = HAWKER
NOTE: The term “Separate” refers to battery cabinets that are not physically attached to the
UPS, are wired with external contractor supplied wiring, and use a single overcurent
protection and disconnect device located near the batteries.
The term “Integral” refers to battery cabinets that are physically attached to the UPS
and the wiring between them is internal. The power wiring is supplied with the
system, and they use the UPS battery switch as the battery isolation device.
The wire size rating for products up to and including the 160/160 are for the total
battery supply. Since these UPS units can only land one wire per DC connection
point, a common DC collector including an isolation device and overcurrent
protection should be used. Refer to applicable national or local code requirements
for your installation.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
A --- 5
Installation Manual 164201408 Rev. P00 053002
735.8
(28.97)
685
(26.97)
(without decorative panels)
1870.3
(73.6)
Series 685 Battery Cabinet
DESCRIPTION:
Series 685 Battery Cabinet (elevation)
DRAWING NO:
SHEET:
Dimensions are in millimeters (inches)
164201408--1
1 of 2
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
A --- 6
Installation Manual 164201408 Rev. P00 053002
WALL --- NO BACK ACCESS REQUIRED
TOP CABLE ENTRY LOCATION
(COVER SECURED WITH SCREWS)
201.1
(7.92)
Series 685 Battery Cabinet
335
TOP VIEW
(13.19)
120
(4.72)
80
(3.15)
175
280.4
(6.89)
(11.04)
282
226.9
(8.93)
914.4 (36.00)
(11.1)
MINIMUM CLEARANCE
FOR SUBASSEMBLY
REMOVAL
735.8
(28.97)
61.4
613
(2.42)
(24.14)
135
300.4
(11.83)
75
(5.32)
(2.95)
141.4
(5.57)
453
(17.83)
71
(2.80)
151
(5.95)
148
(5.83)
690
(27.17)
Series 685 Battery Cabinet
530
BOTTOM VIEW
(20.87)
802.7
(31.6)
BOTTOM CABLE ENTRY LOCATION
(COVER SECURED WITH SCREWS)
DESCRIPTION:
DRAWING NO:
Series 685 Battery Cabinet (plan)
SHEET:
Dimensions are in millimeters (inches)
2 of 2
164201408--1
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
A --- 7
1135.8
(44.72)
1085
(42.72)
(without decorative panels)
1870.3
(73.6)
Series 1085 Battery Cabinet
DESCRIPTION:
Series 1085 Battery Cabinet (elevation)
Dimensions are in millimeters (inches)
DRAWING NO:
SHEET:
1 of 2
164201408--2
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
A --- 8
Installation Manual 164201408 Rev. P00 053002
Series 1085 Battery Cabinet
(TOP VIEW)
TOP CABLE ENTRY LOCATION
(COVER SECURED WITH SCREWS)
WALL --- NO BACK ACCESS REQUIRED
201.1
(7.92)
335
(13.19)
120
(4.72)
80
(3.15)
480.4
175
(18.91)
(6.89)
282
426.9
914.4 (36.00)
MINIMUM CLEARANCE
FOR SUBASSEMBLY
REMOVAL
(11.1)
(16.81)
1135.8
(44.72)
426.5
426.5
141.4
(5.57)
(16.79)
(16.79)
1013
(39.88)
61.4
(2.42)
442.9
(17.44)
250
(9.84)
71
88.9
(3.5)
(2.80)
151
151
(5.95)
(5.95)
102
(4.02)
229.1
(9.02)
265
(10.43)
265
(10.43)
802.7
(31.6)
690
(27.27)
265
265
(10.43)
(10.43)
BOTTOM CABLE ENTRY LOCATION
(COVER SECURED WITH SCREWS)
Series 1085 Battery Cabinet
(BOTTOM VIEW)
DESCRIPTION:
DRAWING NO:
Series 1085 Battery Cabinet (plan)
SHEET:
Dimensions are in millimeters (inches)
164201408--2
2 of 2
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
A --- 9
1 2 3 4 5 6 7 8 9 10 11 12
TB1
Note 1
Note 1
Note 2,3,4
Note 2,3,4
Notes:
1. Shunt trip requires 24V (150 VA instantaneous) to activate (supplied by user).
2. Auxiliary switches are rated as follows:
240 VAC @ 15A
125 VDC @ 0.3A
250 VDC @ 0.15A
3. Wiring shall be suitable for Class 1, 600V wiring methods.
All wiring shall be #10-22 AWG, 75 deg. C minimum.
4. Torque screw terminals to 20 in.-lb.
DESCRIPTION:
Remote Interface Connections
DRAWING NO:
SHEET:
164201408--3
1 of 1
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
A --- 10
Installation Manual 164201408 Rev. P00 053002
4 Cabinets Maximum
(E4)
(E5)
UPS
CABINET
BATTERY
CABINET
BATTERY
CABINET
Powerware 9350 30 through 160
Battery Cabinets integral to UPS
and connected using Manufacturer supplied wiring
CONTRACTOR
WIRING (1)
CONTRACTOR
WIRING (2)
4 Cabinets Maximum
BATTERY
DISCONNECT
(E4)
(E5)
UPS
CABINET
BATTERY
CABINET
BATTERY
CABINET
Powerware 9350 30 through 160
Battery Cabinets located separately
from the UPS
NOTE: The term “Separate” refers to battery cabinets that are not physically attached
to the UPS, are wired with external contractor supplied wiring, and use a single
overcurent protection and disconnect device located near the batteries.
The term “Integral” refers to battery cabinets that are physically attached to the
UPS and the wiring between them is internal. The power wiring is supplied
with the system, and they use the UPS battery switch as the battery isolation
device.
The wire size rating for products up to and including the 160/160 are for the
total battery supply. Since these UPS units can only land one wire per DC
connection point, a common DC collector including an isolation device and
overcurrent protection should be used. Refer to applicable national or local
code requirements for your installation.
Contractor Wiring (1): Refer to UPS manual to size wiring
Contractor Wiring (2): See
Table C of Appendix A to size
Contractor Supplied wiring
DESCRIPTION:
Series 685 / 1085 Configurations
DRAWING NO:
SHEET:
164201408--4
1 of 1
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
A---11
This Page Intentionally Left Blank.
Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
A --- 12
|