SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
No. OB371
SERVICE MANUAL
Wireless type
Models
E1
(WH)
MSZ-FA25VA -
MSZ-FA35VA -
E1
(WH)
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················3
3. SPECIFICATION·················································5
4. NOISE CRITERIA CURVES·······························6
5. OUTLINES AND DIMENSIONS ·························7
6. WIRING DIAGRAM ············································8
7. REFRIGERANT SYSTEM DIAGRAM················8
8. SERVICE FUNCTIONS ······································9
9. TROUBLESHOOTING······································11
10. DISASSEMBLY INSTRUCTIONS·····················31
11. PARTS LIST······················································35
12. OPTIONAL PARTS···········································38
Indication of model name
E1
MSZ-FA25VA -
E1
MSZ-FA35VA -
NOTE:
This service manual describes technical data of the indoor units.
E1
E1
E1
•As for outdoor units MUZ-FA25VA- , MUZ-FA35VA- , MUZ-FA25VAH-
and
E1
MUZ-FA35VAH- , refer to service manual OB372.
•As for outdoor units MXZ-3A54VA- , MXZ-4A71VA-
E1
E1
E1
and MXZ-4A80VA-
,
refer to service manual OB377.
2
PART NAMES AND FUNCTIONS
INDOOR UNIT
E1
MSZ-FA25VA -
MSZ-FA35VA -
E1
Air inlet
PLASMA AIR PURIFYING filter
Front panel
Panel
PLASMA DEODORIZING filter
Fan guard
Heat exchanger
Anti-mold air filter
Air outlet
Vertical vane
Horizontal vane
Remote controller
Line flow fan
Auto front panel
Display section
Operation section
When the unit starts operating, the
front panel opens automatically to
draw in air. When the unit stops
operating, the front panel closes
automatically.
(When the front panel is opened)
POWER lamp
PLASMA/WASH lamp
Auto front panel
AREA lamp
Emergency operation
switch
i-see Sensor
Remote control
receiving section
WASH reset switch
<Open> <Closed>
i-see control operation
AREA lamp indicate AREA setting
In AREA setting, the horizontal air flow
direction changes automatically according
to the detection of i-see Sensor which detects
the floor/ wall temperature to air-condition
the room evenly.
i-see sensor constantly measure
floor/wall temperature to automatically
adjust to the set temperature by
estimating the temperature
actually perceived by a
person inside the room
("sensible temperature").
3
E1
E1
MSZ-FA25VA -
MSZ-FA35VA -
E1
E1
MSZ-FA25VA -
MSZ-FA35VA -
ACCESSORIES
Installation plate
1
2
3
4
5
6
7
1
5
1
2
2
1
1
Installation plate fixing screw 4 o 25 mm
Remote controller holder
Fixing screw for 33.5 o 1.6 mm (Black)
Battery (AAA) for remote controller
Wireless remote controller
Felt tape (Used for left or left-rear piping)
REMOTE CONTROLLER
Signal transmitting section
Operation display section
OPERATE/STOP
(ON/OFF) button
Temperature buttons
Indication of
remote controller
model is on back
Open the front lid.
WIDE VANE button
(Vertical vane button)
FAN SPEED CONTROL button
OFF-TIMER button
ON-TIMER button
OPERATION SELECT button
ECONO COOL button
TIME SET buttons
FORWARD button
BACKWARD button
PLASMA button
AREA button
CLOCK SET button
i-see button
VANE CONTROL button
(Horizontal vane button)
RESET button
4
3
SPECIFICATION
E1
E1
Indoor model
Function
MSZ-FA25VA -
Cooling
MSZ-FA35VA -
Cooling
Heating
Heating
Single phase
230V,50Hz
Single phase
230V,50Hz
Power supply
Air flow(Super High)
594
K/h
K/h
A
594
612
612
Capacity
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
Air flow(High /Med. /Low )
Power outlet
474 /354 /258
474 /354 /252
498 /384 /276
498 /384 /264
10
0.25
33
10
0.25
33
Running current ✽1
Power input ✽1
Auxiliary heater
Power factor ✽1
Fan motor current ✽1
Model
A
W
A(kW)
%
—
—
57
57
A
0.25
0.25
Fan motor
RC0J40-EB
RC0J40-EB
Dimensions WOHOD
Weight
mm
kg
780O298O198
780O298O198
10
4
10
4
Air direction
Sound level(Super High)
dB(A)
42
42
W
W
W
W
W
W
W
W
W
Sound level(High /Med. /Low ) dB(A)
36 /29 /21
36 /29 /22
Fan speed(Super High)
rpm
rpm
1,220
1,220
1,250
1,250
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
Fan speed(High /Med. /Low )
Fan speed regulator
1,010 /800 /630
1,010 /800 /610
1,050 /850 /660
1,050 /850 /640
4
4
Thermistor RT11(at25:)
Thermistor RT12(at25:)
Thermistor RT13(at25:)
Remote controller model
k"
k"
k"
10
10
10
10
10
10
KM05A
KM05A
When outdoor unit is MXZ type.
E1
E1
Indoor model
Function
MSZ-FA25VA -
MSZ-FA35VA -
Cooling
Cooling
546
Heating
540
Heating
642
Air flow(Super High)
K/h
K/h
dB(A)
dB(A)
rpm
Capacity
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
516 /390 /258
450 /348 /252
420 /372 /264
522 /402 /276
Air flow(High /Med. /Low )
42
42
W
Sound level(Super High)
W
W
W
W
W
W
W
36 /29 /21
36 /29 /22
Sound level(High /Med. /Low )
1,130
1,120
1,300
Fan speed(Super High)
W
W
W
W
W
W
W
W
W
W
W
W
W
W
1,080 /860 /630
960 /790 /610
910 /830 /640
1,090 /880 /660
Fan speed(High /Med. /Low )
rpm
NOTE : Test conditions are based on ISO 5151
Cooling : Indoor Dry-bulb temperature 27:Wet-bulb temperature 19:
Outdoor Dry-bulb temperature 35:Wet-bulb temperature 24:
Heating : Indoor Dry-bulb temperature 20:Wet-bulb temperature 15:
Outdoor Dry-bulb temperature 7: Wet-bulb temperature 6:
Refrigerant piping length (one way): 5m
w Reference value
✽1 Measured under rated operating frequency.
Specifications and rating conditions of main electric parts
INDOOR UNIT
Model
-
E1
-
E1
MSZ-FA25VA
MSZ-FA35VA
Item
Fuse
(F11)
(MP)
T3.15AL250V
Front panel driving motor
i-see Sensor motor
Horizontal vane motor
Vertical vane motor
Varistor
NSEJ001DA1 12V DC 100"(at 25˚C)
MP20Z 12V DC 300"(at 25˚C)
MSBPC20M16 12V DC 250"(at 25˚C)
MSBPC20M11 12V DC 300"(at 25˚C)
ERZV14D471
(MT)
(MV1)
(MV2)
(NR11)
(RR)
i-see Sensor
A2TPMI334F0V50HSOBA060P5L1J4S 5V DC
3P
Terminal block
(TB)
5
4
NOISE CRITERIA CURVES
E1
E1
MSZ-FA25VA -
MSZ-FA35VA -
FAN SPEED FUNCTION SPL(dB(A))
LINE
FAN SPEED FUNCTION SPL(dB(A))
LINE
COOLING
HEATING
42
42
42
42
COOLING
HEATING
Super High
Super High
Test conditions,
Test conditions,
Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
90
Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
90
80
70
60
50
40
30
20
10
80
70
60
50
40
30
20
10
NC-70
NC-70
NC-60
NC-50
NC-40
NC-30
NC-60
NC-50
NC-40
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
NC-20
63
125
250
500
1000 2000 4000 8000
63
125
250
500
1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
INDOORUNIT
1m
WALL
0.8m
MICROPHONE
6
5
OUTLINES AND DIMENSIONS
E1
Unit : mm
MSZ-FA25VA -
MSZ-FA35VA -
E1
INDOOR UNIT
11o26 Oblong hole
11o20 Oblong hole
225 225
55
55
Installation plate
780
155
155
320
55
335
Air in
70
Wall hole [65
Indoor unit
198
5
Installation plate
Liquid line [6.35 - 0.5m
Gas line [9.52 - 0.43m
Insulation [35 O.D
[19 I.D
{
Drain hose [16
(Connected part O.D)
90
Insulation [28
53.5
624.5
102
106
58
19
Air out
Required space (Indoor unit)
Wireless remote controller
75 or more
75 or more
7
6
WIRING DIAGRAM
E1
MSZ-FA25VA -
MSZ-FA35VA -
E1
MODELS WIRING DIAGRAM
INDOOR UNIT
INDOOR ELECTRONIC
CONTROL P.C. BOARD
4
3
2
1
RT13
RT12
TB
CN
TAB3
F11
S1
S2
S3
BLK
230V~
112
DB111
T111
TO OUTDOOR
BLU
RED
CN
UNIT
2
1
RT11
111
12-24V
NR11
CONNECTING
RED
1
2
3
4
5
6
CN201
LD
BLK
WHT
YLW
BLU
5
MF
LD104
CN
151
CN
1R1
LD
101(A)
CN
CN
CN
CN
105(T)
110
1T1
1T2
1U1
CN211
5
2
3
8
3
3
4
5
5
5
2
INTERLOCK
SWITCH(FAN)
SW P.C.
MP
PLASMA_A
PLASMA_D
BOARD
POWER MONITOR
RECEIVER P.C. BOARD
SAFETY DEVICE
(PLASMA UNIT)
MT
RR
MV1
MV2
NAME
DB111 DIODE STACK
SYMBOL
MV2
NR11
NAME
NAME
SYMBOL
SYMBOL
RT12
RT13
T111
VANE MOTOR (VERTICAL)
VARISTOR
INDOOR COIL THERMISTOR (MAIN)
INDOOR COIL THERMISTOR (SUB)
TRANSFORMER
F11
MF
MP
FUSE (T3.15AL250V)
INDOOR FAN MOTOR
FRONT PANEL DRIVING MOTOR
i-see Sensor MOTOR
PLASMA_A PLASMA AIR PURIFYING FILTER UNIT
PLASMA_D PLASMA DEODORIZING FILTER UNIT
TB
TERMINAL BLOCK
RR
i-see Sensor
MT
RT11
ROOM TEMPERATURE THERMISTOR
MV1
VANE MOTOR (HORIZONTAL)
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block,
: Connector
7
REFRIGERANT SYSTEM DIAGRAM
E1
E1
Unit : mm
MSZ-FA25VA -
MSZ-FA35VA -
INDOOR UNIT
INDOOR UNIT
Refrigerant pipe [9.52
(with heat insulator)
Refrigerant pipe [9.52
(with heat insulator)
Indoor coil
thermistor
RT12(main)
Indoor coil
thermistor
RT12(main)
Indoor
Indoor
heat
heat
exchanger
exchanger
Flared connection
Flared connection
Indoor coil
Indoor coil
thermistor
RT13(sub)
thermistor
RT13(sub)
Room temperature
thermistor
Room temperature
thermistor
RT11
RT11
Flared connection
Flared connection
Refrigerant pipe [6.35
(with heat insulator)
Refrigerant pipe [6.35
(with heat insulator)
Refrigerant flow in cooling
Refrigerant flow in heating
8
8
SERVICE FUNCTIONS
E1
MSZ-FA25VA -
MSZ-FA35VA -
E1
8-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board.
The time will be shortened as follows. (Refer to 9-7.)
Set time : 1-minute ➔ 1-second
Set time : 3-minute ➔ 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below :
Remote controller model : KM05A
NOTE : For remodelling, take out
the batteries and press the
OPERATE/STOP(ON/OFF)
button twice or 3 times at
first.
After finish remodelling,
put back the batteries then
press the RESET button.
J1
J2
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1.
After modification, press the RESET button.
Table 1
4 units operation
Same as at left
1 unit operation
2 units operation
3 units operation
Same as at left
Same as at left
Solder J2
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
No modification
Same as at left
Same as at left
–
–
–
Solder J1
Same as at left
–
–
Solder both J1 and J2
–
How to set the remote controller exclusively for particular indoor unit.
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote
controller for the indoor unit.
The indoor unit will only accepts the signal from the remote controller that has been assigned to the indoor unit once they are
set.
The setting will be cancelled if the breaker has turned off, or the power supply has shut down.
Please conduct the above setting once again after the power has restored.
8-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed
are memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment
power has restored after power failure. Then, the unit will restart automatically.
Operation
1 If the main power has been cut, the operation settings remain.
2 After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
9
How to release “AUTO RESTART FUNCTION”
1Turn off the main power for the unit.
2Solder the Jumper wire to JR07 on the indoor electronic control P.C. board. (Refer to 9-7.)
JR07
NOTE:
• The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
• If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
• If the unit has been off with the remote controller before power failure, the auto restart function does not works as the
power button of the remote controller is off.
• To prevent breaker off due to the rush of starting current, systematize other home appliance not to turn on at the same
time.
• When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart.
Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current
by adding to the system that allows the units to start one by one.
8-4. Remote controller
Be sure to set the slide switch inside the remote controller to an appropriate position in accordance with the
installed position of the indoor unit. If the switch is not set correctly, the air conditioner may not function properly.
Side swich
Area
Left
Center
Right
Position of
the slide
switch
Display on
the remote
controller
Where is the indoor unit installed in your room?
Installed at left , if the
distance is not more
than 50 cm.
Installed at right , if the
distance is not more
than 50 cm.
(Left)
(Center)
(Right)
Is the indoor unit in-
stalled at right, left or
center?
NOTE:If the indoor unit is installed more than 50 cm away from the side walls, cabinets or other nearby objects, set the slide
switch to the “center” position.
10
9
TROUBLESHOOTING
E1
MSZ-FA25VA -
MSZ-FA35VA -
E1
9-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to turn off the unit first with the remote controller, and then after
confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the
electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
Housing point
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) When troubleshooting, refer to 9-2., 9-3. and 9-4.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction.
In this case, replace the batteries to operate the remote controller normally.
1 Remove the front lid and insert batteries.
2 Press RESET button with tip end of ball point pen
Then reattach the front lid.
or the like, and then use the remote controller.
Insert the negative pole of the
batteries first. Check if the polarity
of the batteries are correct.
RESET button
NOTE : 1. If RESET button is not pressed, the remote controller may not operate correctly.
2. This remote controller has a circuit to automatically reset the microcomputer when batteries are replaced.
This function is equipped to prevent the microcomputer from malfunctioning due to the voltage drop caused by
the battery replacement.
5. How to install the horizontal vane
If horizontal vane is not installed correctly, All of the operation indicator lamps will blink.
In this case, install the horizontal vane correctly by following the procedures 1 to 2.
NOTE: Before installation of the horizontal vane, turn OFF the power supply.
Stopper
1
2
In procedure 2 lock the
stoppers until they click
into place.
Left
Lock.
Insert this end first.
11
6. How to remove and install PLASMA DEODORIZING / AIR PURIFYING filter units
If PLASMA/WASH lamp on the indoor unit blinks, clean the filters as soon as possible. The lamp will start blinking when
accumulated operating time exceeds 330 hours.
Figure 1.
<Remove>
(1) Switch the indoor unit OFF with the remote controller and
disconnect the power supply plug and/ or turn OFF the
breaker.
NOTE: Otherwise, you may get injured since PLASMA
DEODORIZING/AIR PURIFYING filter units are
charged with high voltage.
(2) Hold the knobs on both sides of the front panel and lift the
panel up until its level.
(3) Remove the anti-mold air filter.(See Figure 1.)
(4) Remove PLASMA DEODORIZING/AIR PURIFYING filter
units. (See Figure 2.)
Figure 2.
<Install>
Install PLASMA DEODORIZING/AIR PURIFYING filter units by following the removal procedure in reverse.
(1) Insert the top of PLASMA DEODORIZING/AIR PURIFYING filter
Figure 3.
units into the aperture in the plasma element holder.
(See Figure 3.)
(2) Push in PLASMA DEODORIZING/AIR PURIFYING filter units
until they click into place.
•The front panel does not close if PLASMA DEODORIZING/AIR
PURIFYING filter units are not installed properly.
(3) Install the anti-mold air filter.
(4) Connect the power supply plug and/ or turn ON the breaker.
Plasma
element
holder
(5) Press WASH reset switch. A short “beep” is heard and the blinks
of PLASMA/WASH lamp will be cancelled. Make sure PLASMA/
WASH lamp is not blinking at the start of operation next time.
(See Figure 4.)
(6) Hold both sides of the front panel and close the front panel.
(7) Press the 3 positions on the front panel as indicated by the
arrows.(See Figure 5.)
Figure 4.
E.O.
SW
NOTE:
WASH
reset
Install PLASMA DEODORIZING/AIR PURIFYING filter units only
when they are completely dry. If the filter unit remains wet,
PLASMA/WASH lamp may blink and the plasma function may be
disabled.(When PLASMA DEODORIZING/AIR PURIFYING filter
units are cleaned.)
Figure 5.
12
INFORMATION FOR MULTI SYSTEM AIR CONDITIONER
OUTDOOR UNIT : MXZ series
Multi system air conditioner can connect two or more indoor units with one outdoor unit.
•Unit won’t operate in case the total capacity of indoor units exceeds the capacity of outdoor units. Do not
connect indoor units beyond the outdoor unit capacity.
Operation indicator lamp flashes as shown in the figure below.
•When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and
the other for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor
units which start the operation later cannot operate, indicating as shown in the figure below. In this case,
please set all the indoor units to the same operation mode.
Lighted
Blinking
Not lighted
•When indoor units start the operation while the defrosting of outdoor unit is being done, it takes a few minutes
(max. 10 minutes) to blow out the warm air.
•In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant
flowing may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
13
9-2. Failure mode recall function
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table disappears, the memorized failure details can be
recalled.
This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
1. Flow chart of the indoor/outdoor unit failure mode recall function
Operational procedure
1While pressing both OPERATION SELECT
button and TOO COOL button on the
remote controller at the same time,
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
press RESET button.
Turn ON the power supply.
2First, release RESET button.
1While pressing both OPERATION SELECT
button and TOO COOL button on the remote controller at the same
time, press RESET button.
And release the other two buttons since all LCD
in operation display section of the remote controller
is displayed after 3 seconds.
2First, release RESET button.
And release the other two buttons since all LCD in operation display
section of the remote controller is displayed after 3 seconds.
W1. Regardless of normal or abnormal, a short
W1
beep is emitted once as the signal is received.
Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature
is displayed).
With the remote controller headed towards the indoor unit, press TOO COOL or TOO
WARM button to adjust the set temperature to 24:.
No
(OFF)
Does POWER lamp on the indoor
Indoor unit is normal.
unit blink at the interval of 0.5 seconds?
Blinks: Either indoor or outdoor unit is abnormal.
Beep sounds are emitted at the same timing
of the blinking of POWER lamp. W2
There is a possibility that the plasma or outdoor unit is abnormal.
Confirm the presence of abnormality according to the flow chart of the
the prasma unit or detailed outdoor unit failure mode recall function.
Yes
(Blinks)
Judgment of indoor/outdoor abnormality
Before blinking, does POWER
lamp stay ON for 3 seconds?
Yes
Stays ON for 3 seconds (without beep):
The outdoor unit is abnormal.
No
The indoor unit is abnormal.
The outdoor unit is abnormal.
Check the blinking pattern, and refer to confirm the
abnormal point(9-2.4.).
Check the blinking pattern, and refer to confirm the abnormal point.
Make sure to check at least two consecutive blinking cycles. W3
Make sure to check at least two consecutive blinking cycles. W2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
1With the remote controller headed towards the indoor unit, press any button
that is not used in this failure mode recall function (e.g. TIMER button) .
OR
1Turn OFF the power supply and turn ON it again.
2Press RESET button of the remote controller.
•As for outdoor unit MUZ type, refer to service manual OB372.
As for outdoor unit MXZ type, refer to service manual OB377.
Repair the defective parts.
Deleting the abnormal condition
1After repairing the unit, recall the failure mode again according to
"Setting up the failure mode recall function" mentioned above.
2Press EMERGENCY OPERATION switch so that the memorized
abnormal condition is deleted.
3Release the failure mode recall function according to "Releasing the
failure mode recall function" mentioned above.
Note1.Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2.If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2. Blinking pattern when the indoor unit is abnormal:
Blinking at 0.5-
second interval
Blinking at 0.5-
second interval
2.5-second OFF
2.5-second OFF
ON
OFF
Beeps
Beeps
Beeps
Repeated cycle
Repeated cycle
Repeated cycle
W3.Blinking pattern when the outdoor unit is abnormal:
Blinking at 0.5-
Blinking at 0.5-
second interval
2.5-second OFF
3-second ON
second interval
2.5-second OFF
3-second ON
ON
OFF
No beep
Beeps
No beep
Beeps
Repeated cycle
Repeated cycle
Repeated cycle
14
2. Flow chart of PLASMA DEODORIZING/PLASMA AIR PURIFYING power failure mode recall function
Operational procedure
There is a possibility that the plasma unit is abnormal.
Confirm the presence of abnormality according to the following procedures.
Confirm that the remote controller is in the failure mode recall
function.
W1. Regardless of normal or abnormal, a short
beep is emitted as the signal is received.
W1
With the remote controller headed towards the indoor unit, press TOO COOL or TOO
WARM button to adjust the set temperature to 23:.
Confirmation of abnormality presence
Does POWER lamp on the indoor
No
unit blink at the interval of 0.5 seconds? W2
Blinks: The plasma unit is abnormal.
Beep sounds are emitted at the same timing
of the blinking of POWER lamp.
(OFF)
Yes
(Blinks)
The plasma unit is abnormal.
Check the blinking pattern, and refer to confirm the
abnormal point(9-2.5.).
The plasma unit is normal.
Make sure to check at least two consecutive blinking cycles. W2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
1With the remote controller headed towards the indoor unit, press any button
that is not used in this failure mode recall function (e.g. TIMER button) .
OR
Release the failure mode recall function according to the left
mentioned procedure.
1Turn OFF the power supply and turn ON it again.
2Press RESET button of the remote controller.
Repair the defective parts.
Deleting the abnormal condition
1After repairing the unit, recall the failure mode again according to
"Setting up the failure mode recall function" mentioned above.
2Press EMERGENCY OPERATION switch so that the memorized
abnormal condition is deleted.
3Release the failure mode recall function according to "Releasing the
failure mode recall function" mentioned above.
Note1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2.Blinking pattern when outdoor unit is abnormal:
Blinking at 0.5-
second interval
Blinking at 0.5-
second interval
2.5-second OFF
2.5-second OFF
ON
OFF
Beeps
Beeps
Beeps
Repeated cycle
Repeated cycle
Repeated cycle
3. PLASMA DEODORIZING/PLASMA AIR PURIFYING power operation check
PLASMA DEODORIZING/PLASMA AIR PURIFYING power goes ON when PLASMA button on the remote controller is pressed
once while the indoor error indication is being checked or after one short beep sound (signal reception beep) is emitted.
PLASMA button is pressed, the power of plasma is changed in sequence:
PLASMA DEODORIZING power goes ON
➔ PLASMA AIR PURIFYING power goes ON
➔ Cancel
Check the operation display section of the remote controller to confirm that PLASMA DEODORIZING power or PLASMA AIR
PURIFYING power is activated.
While PLASMA/WASH lamp stays OFF, and it means normal.
Flashing PLASMA/WASH lamp means abnormal, and the plasma power is not being conducted.
PLASMA/WASH lamp
Continuously flashes
Action
Follow "Check of PLASMA DEODORIZING power" or "Check of PLASMA AIR PURIFYING power"
to identify the error.(Refer to 9-6.For G.)
PLASMA DEODORIZING power or PLASMA AIR PURIFYING power control circuit on the indoor
electronic control P.C. board is out of order.(Refer to 9-6.For G.)
2-time flash
NOTE: Perform the above mentioned check with the front panel closed. Panel open is detected by the SAFETY DEVICE
(PLASMA UNIT).
15
4. Indoor unit failure mode table
NOTE: Blinking patterns of this mode differs from the ones of Troubleshooting check table(9-4.).
Abnormal point
(Failure mode)
POWER lamp
Not lighted
Detection method
–
Check point
–
Normal
When the room temperature thermistor short
or open circuit is detected every 8
seconds during operation.
Room temperature
thermistor
Refer to the characteristics of the room
temperature thermistor (9-7.).
1-time flash
every 0.5-second
When the indoor coil thermistor short or open Refer to the characteristic of the main
2-time flash
2.5-second OFF
circuit is detected every 8 seconds during
operation.
indoor coil thermistor, the sub indoor coil
thermistor (9-7.).
Indoor coil thermistor
Serial signal error
Indoor fan motor
3-time flash
2.5-second OFF
When the serial signal from outdoor unit is
not received for a maximum of 6 minutes.
Refer to 9-6.D"How to check miswiring
and serial signal error".
When the rotational frequency feedback
signal is not emit during 12-second the
indoor fan operation.
Refer to 9-6.A"Check of indoor fan
motor".
11-time flash
2.5-second OFF
When it cannot properly read data in the
nonvolatile memory of the indoor electronic
control P.C. board.
Replace the indoor electronic control
P.C. board.
12-time flash
2.5-second OFF
Indoor control system
5. PLASMA DEODORIZING/PLASMA AIR PURIFYING power failure mode table
Abnormal point
(Failure mode)
POWER lamp
1-time flash
Detection method
Check point
When PLASMA DEODORIZING/PLASMA
AIR PURIFYING power cannot be turned
OFF.
PLASMA DEODORIZING/
PLASMA AIR PURIFYING
power control
Replace the indoor electronic control P.C.
board.
When the voltage between CN1 1(+)
and 2(GND) on the PLASMA POWER P.C.
board (PLASMA DEODORIZING or PLASMA
AIR PURIFYING) falls below 1.6V(spark
discharge judgment voltage).
Refer to 9-6.F"Check of PLASMA
DEODORIZING power" or 9-6.G"Check
of PLASMA AIR PURIFYING power".
2-time flash
3-time flash
4-time flash
5-time flash
Spark discharge
When the voltage between CN1 1(+)
and 2(GND) on the PLASMA POWER P.C.
board (PLASMA DEODORIZING or PLASMA
AIR PURIFYING) falls 0.9V below the normal
range voltage.
Refer to 9-6.F"Check of PLASMA
DEODORIZING power" or 9-6.G"Check
of PLASMA AIR PURIFYING power".
Abnormal electric
discharge error 1
When the voltage between CN1 1(+)
and 2(GND) on the PLASMA POWER P.C.
board (PLASMA DEODORIZING or PLASMA
AIR PURIFYING) falls significantly.
(0.4V / 0.5ms)
Refer to 9-6.F"Check of PLASMA
DEODORIZING power" or 9-6.G"Check
of PLASMA AIR PURIFYING power".
Abnormal electric
discharge error 2
When the voltage between CN1 1(+)
and 2(GND) on the PLASMA POWER P.C.
board (PLASMA DEODORIZING or PLASMA
AIR PURIFYING) rises above the normal
voltage value (3V).
Refer to 9-6.F"Check of PLASMA
DEODORIZING power" or 9-6.G"Check
of PLASMA AIR PURIFYING power".
PLASMA DEODORIZING/
PLASMA AIR PURIFYING
power
w As soon as an error is detected, PLASMA DEODORIZING power or PLASMA AIR PURIFYING power goes OFF,
therefore measuring instrument which records the voltage wave is required in order to perform the above men-
tioned voltage measurement.
16
9-3. Instruction of troubleshooting
w"Test Run operation"
means the operation
within 30 minutes after
EMERGNCY OPERATION with failure mode recall function.
switch is pressed.
If blinking of OPERATION
INDICATOR lamp cannot
be checked, it can be checked
Start
OPERATION
OPERATION
Indoor unit
Indoor unit
Indoor unit operates.
Outdoor unit doesn't
operate normally.
INDICATOR
INDICATOR
operates.
Outdoor unit
doesn't
doesn't receive
the signal from
remote controller.
lamp on the
indoor unit is
flashing on
and off.
lamp on the
indoor unit
stays off.
operate.
PLASMA/WASH lamp
2-time flash
cause:
Indoor unit
doesn't operate,
when
EMERGENCY
OPERATION
switch is pressed.
Indoor unit
Outdoor unit
doesn't
operate
even in
Test Run
operation. w
Unit doesn't
operate
normal
operation in
COOL or
HEAT mode.
Outdoor unit
operates in
only Test Run
operation. w
operates, when
EMERGENCY
OPERATION
switch is pressed.
Indoor unit
• Trouble of PLASMA
DEODORIZNG power
control or PLASMA AIR
PURIFYING power
control
1. Check indoor / outdoor
connecting wire.
(Check if the power
is supplied to the
indoor unit.)
2. Refer to 9-6.C
"Check of indoor
electronic control
P.C. board and indoor
fan motor".
Replace the indoor
electronic control P.C.
board.
Refer to
"How to check
inverter/
Check room
temperature
thermistor.
Refer to 9-7.
"Test point
diagram and
voltage".
Refer to
"Check of
R.V. coil".
Refer to 9-6.B
"Check of
remote controller
and receiver
P.C. board".
compressor".
As for outdoor unit MUZ type,
refer to service manual OB372.
As for outdoor unit MXZ type,
refer to service manual OB377.
POWER lamp
2-time flash
Cause:
Indoor unit
• Trouble of
room temp-
erature/
indoor coil
thermistor
POWER lamp
Flash on and off
at 0.5-second
intervals
Cause:
Indoor/
Outdoor unit
• Mis-wiring
or trouble
POWER lamp POWER lamp
POWER lamp
3-time flash
Cause:
Indoor unit
• Trouble of
indoor fan
motor
Left lamp
POWER lamp POWER lamp
All lamps
7-time flash
Cause:
14-time flash
Cause:
of AREA lamp
4-time flash
Cause:
Indoor unit
• Trouble of
indoor unit
control
5-time flash
Cause:
6-time flash
Cause:
Flash on and off
at 0.5-second
intervals
Outdoor unit Outdoor unit
Outdoor unit
• Outdoor
power
system
abnormality
Outdoor unit
• Trouble of
thermistor
in outdoor
unit
Cause:
• Trouble of
outdoor
control
• Other
abnormality
Indoor unit
• The horizontal
vane is not
installed
system
correctly.
system
of serial signal
Refer to
"How to check
inverter/
Refer to 9-6.
A"Check of
indoor fan
motor".
Check
Replace the
indoor
electronic
control
Refer to
"Check of
outdoor
thermistors". the outdoor
electronic
Replace the
inverter P.C.
board or
Check room
temperature
thermistor
and indoor
coil thermis-
tor.
Refer to 9-7.
"Test point
diagram and
voltage".
Refer to 9-6. Refer to 9-6.
E "Check of D "How to
installation of check of
the horizontal mis-wiring
"Flow chart of
the detailed
outdoor unit
failure mode
recall function."
compressor".
P.C. board.
vane".
and serial
signal error
(when
control P.C.
board.
outdoor unit
doesn't work)".
17
9-4. Troubleshooting check table
· Flashing of POWER lamp indicates abnormalities.
Lighted
Blinking
Not lighted
NOTE : Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
Self check table
Abnormal
point
No.
1
Operation indicator lamp
POWER lamp flashes.
Symptom
Detection method
Check point
0.5-second ON
• Refer to 9-6.D"How to check
mis-wiring and serial signal
error".
Mis-Wiring
or serial
signal
Outdoor unit
does not
operate.
When the serial signal form the outdoor unit is
not received for a maximum of 6 minutes.
0.5-second OFF
• Check the blinking pattern of
the LED on the inverter P.C.
board or the outdoor lectronic
control P.C. board.
When it cannot properly read data in the
nonvolatile memory of the inverter P.C. board
or the outdoor electronic control P.C. board.
Outdoor
control
system
Outdoor unit
does not
operate.
POWER lamp lights up
2
3
Indoor coil
thermistor
POWER lamp flashes.
2-time flash
Indoor unit
and outdoor
unit do not
operate.
• Refer to 9-7.the
When the indoor coil or the room temperature
thermistor is short or open circuit.
characteristics of indoor coil
thermistor, and the room
temperature thermistor.
Room
tempera-
ture
2.5-second OFF
thermistor
POWER lamp flashes.
3-time flash
Indoor unit
and outdoor
unit do not
operate.
When the rotational frequency feedback
signal is not emit during the indoor fan
operation.
• Refer to 9-7.A"Check of
indoor fan motor".
Indoor fan
motor
4
5
6
2.5-second OFF
POWER lamp flashes.
5-time flash
• Refer to "Check of inverter/
compressor".
Refer to service manual
OB372 or OB377.
Indoor unit
and outdoor
unit do not
operate.
When it consecutively occurs 3 times that the
compressor stops for overcurrent protection or
start-up failure protection witth in 1 minute
after start-up.
Outdoor
power
system
Check the stop valve.
2.5-second OFF
POWER lamp flashes.
6-time flash
Indoor unit
and outdoor
unit do not
operate.
• Refer to "Check of outdoor
thermistor".
Refer to service manual
OB372 or OB377.
When the outdoor thermistors short or open
circuit during the compressor operation.
Outdoor
thermistors
2.5-second OFF
2.5-second OFF
POWER lamp flashes.
7-time flash
• Replace the inverter P.C.
board or the outdoor
electronic control P.C. board.
Refer to service manual
OB372 or OB377.
Indoor unit
and outdoor
unit do not
operate.
Outdoor
control
system
When it cannot properly read data in the
nonvolatile memory of the inverter P.C. board
or the outdoor electronic control P.C. board.
7
8
POWER lamp flashes.
14-time flash
Indoor unit
and outdoor
unit do not
operate.
• Confirm the abnormarity in
detail using the failure mode
recall function.
An abnormality other than above mentioned is
deteced.
Other
abnonmality
2.5-second OFF
NOTE : When the indoor unit has started operation and the above detection method has detected an abnormality (the first
detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with
OPERATION INDICATOR lamp flashing.
18
· Flashing of AREA lamp(left-hand side lamp) indicates abnormality.
Lighted
Blinking
Not lighted
NOTE : Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
Self check table
Abnormal
point
No.
1
Operation indicator lamp
Symptom
Detection method
Check point
Left lamp of AREA lamp flashes.
4-time flash
Indoor unit
and outdoor
unit do not
operate.
Indoor
control
system
When it cannot properly read data in the
nonvolatile memory of the indoor electronic
control P.C. board.
• Replace the indoor electronic
control P.C. board.
2.5-second OFF
· Flashing of All lamps indicate abnormality.
Lighted
Blinking
Not lighted
Abnormal
point
No.
1
Operation indicator lamp
Symptom
Detection method
Check point
All lamps flash at the same time.
0.5-second ON
Attachment
of the
horizontal
vane
Indoor unit
and outdoor
unit do not
operate.
• Refer to 9-6.E"Check of
installation of the horizontal
vane".
When the electricity is not conducted to the
interlock switch (Fan) of the horizontal vane.
0.5-second OFF
· Flashing of AREA lamp(both lamps) indicates abnormality.
· POWER lamp is lighted.
Lighted
Blinking
Not lighted
Abnormal
point
No.
1
Operation indicator lamp
Symptom
Detection method
Check point
Both lamps flash
When the operation mode of the each indoor
unit is differently set to COOL(includes DRY)
and HEAT at the same time, the operation
mode of the indoor unit that has operated at
first has the priority.
Outdoor unit
operates but
indoor unit
does not
MXZ type
Operation
mode
• Unify the operation mode.
Refer to service manual
OB377.
2.5-second OFF
setting
operate.
· Flashing of PLASMA/WASH lamp indicates abnormality.
Lighted
Blinking
Not lighted
Abnormal
point
No.
1
Operation indicator lamp
Symptom
Detection method
Check point
PLASMA
DEODORIZING/
PLASMA
AIR
PURIFYING
power control
PLASMA/WASH lamp flashes.
2-time flash
Indoor unit
and outdoor
unit do not
operate.
When PLASMA DEODORIZING power or
PLASMA AIR PURIFYING power can not be
turned OFF.
• Replace the indoor electronic
control P.C. board.
2.5-second OFF
NOTE : When the indoor unit has started operation and the above detection method has detected an abnormality (the first
detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with
OPERATION INDICATOR lamp flashing.
19
9-5. Trouble criterion of main parts
E1
E1
MSZ-FA25VA -
MSZ-FA35VA -
Part name
Check method and criterion
Measure the resistance with a tester. (Part temperature 10˚C ~ 30˚C)
Figure
Room temperature
thermistor(RT11)
Normal
Abnormal
Indoor coil thermistor
(RT12(MAIN), RT13(SUB))
Open or short-circuit
8 k"~ 20 k"
Indoor fan motor(MF)
Check 9-6. A.
RED
Measure the resistance between the terminals with a tester.
ROTOR
(Part temperature 10°C ~ 30°C)
Horizontal vane
motor(MV1)
YLW
BRN
Abnormal
Color of the lead wire
BRN-other one
Normal
Open or short-circuit
235 "~ 255 "
GRN
ORN
ORN
ORN
RED
Measure the resistance between the terminals with a tester.
Vertical vane
motor(MV2)
i-see Sensor
motor(MT)
ROTOR
(Part temperature 10°C ~ 30°C)
YLW
BRN
Abnormal
Color of the lead wire
BRN-other one
Normal
Open or short-circuit
282 "~ 306 "
GRN
RED
Measure the resistance between the terminals with a tester.
ROTOR
Front panel
driving motor
(MP)
(Part temperature 10°C ~ 30°C)
YLW
BRN
Abnormal
Color of the lead wire
BRN-other one
Normal
Open or short-circuit
94 "~ 102 "
GRN
Turn the power ON(i-see Sensor is energized) with the aluminum block part
on the i-see Sensor P.C. board (upper part of i-see Sensor) covered with black
vinyl tape, then measure the voltage between connector terminals of i-see
Sensor using tester.
(Part temperature 10 ~ 40°C)
wThe aluminum block
part is covered with
black vinyl tape.
i-see Sensor
Aluminum block
i-see Sensor(RR)
Black
Connector i-see Sensor P.C. board
vinyl tape
i-see Sensor
connector terminals
Normal range
Abnormal
Below 1.874 or above 3.387V DC
Below 1.010 or above 1.420V DC
2(-)
1(+)
-
-
4(+)
2(-)
1.874 ~ 3.387V DC
1.010 ~ 1.420V DC
NOTE: Pay attention to static electricity.
PLASMA DEODORIZING/
PLASMA AIR PURIFYING
power
Check 9-6. For G.
20
9-6. Troubleshooting flow
When POWER lamp flashes 3-time.
Indoor fan does not operate.
A
Check of indoor fan motor
The indoor fan motor error has occurred, and the indoor fan doesn't operate.
Turn OFF the power supply.
Insert a stick such as a screw driver
into the air outlet, and check if there is
any catch in the rotation of the line
Pay careful attention to the high voltage on
the fan motor connector CN211.
flow fan.
w
Turn ON the power supply, wait 5 seconds or more, and then press
EMERGENCY OPERATION switch.
Measure the supply voltage as follows within 12 seconds
after EMERGENCY OPERATION switch is pressed.
If more than 12 seconds passes by, turn OFF the power supply and
turn ON it again, then measure the voltage.
Is there any foreign matter that
interferes the rotation of the
line flow fan?
No
1.Measure the voltage between CN211 1(+) and 3(-).
2.Measure the voltage between CN211 5(+) and 3(-).
Yes
wIf 12 seconds or more passes after EMERGENCY OPERATION switch
is pressed, the voltage mentioned above 2 goes 0V DC although the
indoor electric control P.C. board is normal.
Adjust the line flow fan and
remove the foreign matter.
Is there 311V DC between
CN211 1(+) and 3(-), and does
the voltage between CN211 5(+)
and 3(-) rise to the range of 3 to 6V
DC within 12 seconds after
EMERGENCY OPERATION switch
is pressed?
CN211
Indoor electronic
control P.C. board
Yes
Replace the indoor fan motor.
No
Replace the indoor electronic control P.C. board.
The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3 times, and then stops.
Measure the voltage between CN211
6(+) and 3(-) while the fan
motor is rotating.
Changed
Is it unchanged holding
0V DC or 15V DC?
Replace the indoor electronic control P.C. board.
Unchanged
Replace the indoor fan motor.
21
Indoor unit operates by pressing EMERGENCY OPERATION switch, but does not operate with the remote controller.
B Check of remote controller and receiver P.C. board
wCheck if the remote controller is exclusive for this air conditioner.
Switch on the remote controller.
No
Is LCD display on the the remote
Replace the batteries. (Refer to 9-1.4.)
controller visible?
(not clear)
Yes
Remove the batteries, then set them back
and press RESET button. (Refer to 9-1.4.)
Check if the unit operates with the remote
controller.
No
Turn on a radio to AM and press switch on
the remote controller.
Does the unit operate with the
remote controller?
Yes
OK
No
Replace the remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of
inverter or rapid-start type within
the range of 1m?
Yes
●Reinstall the unit away from lights.
●Attach a filter on receiving part.
Replace the indoor electronic
control P.C. board.
22
The unit does not operate with the remote controller.
Also, POWER lamp does not light up by pressing EMERGENCY OPERATION switch.
C Check of indoor electronic control P.C. board and indoor fan motor
Short circuit:
Turn OFF the power supply.
Measure the resistance of the front panel
driving motor coil.
Normal value is approx. 100'
Replace the front panel driving motor
and the indoor electronic control P.C.
board.
Remove indoor fan motor connector CN211, vane motor
connector CN151 front panel driving motor connector
connector CN1U1 and i-see Sensor motor connector
CN110 from the indoor electronic
control P.C. board and turn ON the power supply.
Short circuit:
Replace i-see Sensor motor and the
indoor electronic control P.C. board.
Measure the resistance of i-see Sensor
motor coil.
Normal value is approx. 300'
Yes
Does the unit operate with the remote controller?
Does POWER lamp light up by pressing EMERGENCY
OPERATION switch?
Measure the resistance between CN211 3
and 4of the indoor fan motor connector.
Normal value is approx. 30k'to 50k'.
Short circuit:
Replace the indoor fan motor.
No
Short circuit:
Measure the resistance of the horizontal vane
motor coil and the vertical vane motor coil.
Normal value is approx. 300'or 250'.
Replace the horizontal vane motor, the
vertical vane motor and the indoor
electronic control P.C. board.
Replace the varistor(NR11) and fuse(F11).
Yes
No
Are the varistor(NR11) burnt
and the fuse(F11) blown?
Turn OFF the power supply.
Check both “parts side” and “pattern
side” of the indoor electronic control P.C.
board visually.
Be sure to check both the fuse
and the varistor in any case.
No
Is the fuse(F11) blown only?
w1,2
Yes
Measure the resistance between
1(+) and 3(-) of the indoor fan
w1. The fan motor connector's 1lead wire is red, whereas 3is black.
motor connector (to CN211 on the
indoor electronic control P.C. board) .
w2. Connect "+" of the tester to fan motor connector's 1lead
wire, and "-" to 3lead wire, otherwise the resistance cannot be
measured properly.
w3
w3. Short circuit:
No
Is the resistance 1M'
or more?
Replace the fuse (F11) and the indoor fan motor.
The indoor fan motor is
abnormal.
Yes
Replace the fuse (F11).
No
Is the resistance
approx. 4'?
Measure the cement resistance R111 on
the indoor electronic control P.C. board.
Replace the indoor electronic control P.C. board
and the indoor fan motor.
Yes
Indoor electronic
control P.C.Board
Replace the indoor electronic control P.C. board.
CN211
Varistor(NR11)
CN201
Fuse(F11)
23
When POWER lamp flashes ON and OFF in every 0.5-second.
Outdoor unit does not operate.
D
How to check mis-wiring and serial signal error
Turn OFF the power supply.
Is there rated voltage of
230V AC in the power
supply?
No
No
Check the power
supply.
Yes
Turn ON the power supply.
Is there 230V AC between
outdoor terminal block S1 and
S2?
Check the wiring.
Yes
Press EMERGENCY OPERATION switch.
Does POWER lamp light up?
<Confirmation of the power to the indoor unit>
No
Yes
Is there any mis-wiring,
poor contact, or wire
disconnection of the
indoor/outdoor
No
Yes
Is the self-check of the indoor unit displayed 6
minutes after?
Make them sure.
connecting wire?
Yes
Serial signal error display
No
POWER lamp
blinks quickly.
A
Turn OFF the power supply.
Check once more if the indoor/outdoor
connecting wire is not mis-wiring.
B
Short-circuit outdoor terminal block S2 and
W1. Mis-wiring may damage indoor electronic control
P.C. board during the operation.
S3.
W1
Be sure to confirm the wiring is correct before the
operation starts.
Turn ON the power supply of the outdoor unit.
In 3 minutes after turning ON the
power supply of the outdoor unit, does
the LED on the inverter P.C. board
repeat quick blinking "3.6-second-OFF
and 0.8-second-ON"?
Be sure to check above in 3 minutes
after turning ON. After 3 minutes, LED
blinks 6 times. When the inverter P.C.
board is normal, LED also blinks 6
times after 3 minutes.
Inverter P.C.board
(Parts side)
Replace the inverter
P.C. board.
W2
No
(Lighting)
W2 Be careful to the residual
LED
voltage of smoothing capacitor.
Blinking
Yes
A
Remove the short-circuit between
outdoor terminal block S2 and S3.
Is there amplitude of 10 to 20V DC
between outdoor terminal block S2
and S3? <Confirmation of serial
signal>
Is there any error of the
· Turn OFF inverter-controlled lighting
equipment.
· Turn OFF the power supply and then
turn ON again.
· Press EMERGENCY OPERATION
switch.
Replace the
indoor/outdoor
connecting.
indoor/outdoor connecting wire,
such as the damage of the wire,
intermediate connection, poor
contact to the terminal block?
Yes
Yes
No
No
No
Yes
· Reinstall
either the
unit or the
light each
other away.
· Attach a filter
on receiving
section of
the indoor
unit.
Is there any error of the
Is there 230V AC between outdoor
terminal block S1 and S2?
<Confirmation of power voltage>
indoor/outdoor connecting wire,
such as the damage of the wire,
intermediate connection, poor
contact to the terminal block?
Replace the
indoor/outdoor
connecting.
Is serial signal
error indicated
6 minutes later?
No
Yes
Replace the indoor electronic control P.C. board.
Be sure to release the failure-mode
recall function after checking.
Yes
B
As for outdoor unit MUZ type,refer to service manual OB372.
As for outdoor unit MXZ type,refer to service manual OB377.
24
When All lamps flash ON and OFF every 0.5-second.
Indoor unit and outdoor unit do not operate.
Check of installation of the horizontal vane
E
Start
Turn OFF the
power supply.
No
Relock the stopper of the
horizontal vane to the indoor unit.
Refer to 9-1.5.
Is the stopper of the horizontal vane
locked to the indoor unit correctly?
Yes
Turn ON the
power supply.
No
Are all lamp flashing?
Yes
OK
To check the continuity of the interlock switch
Turn OFF the
power supply.
(Fan), measure the resistance of connector 1- 2
connected to CN1R1 on the indoor
electronic control P.C. board.
No(∞)
Replace the
interlock switch(Fan).
Is there resistance 0 "?
Yes
Replace the
indoor electronic
control P.C. board.
25
When PLASMA/WASH lamp flashes 2-time.
wThe power failure mode for PLASMA DEODORIZING power is memorized when the failure mode is called.
F
Check of PLASMA DEODORIZING power
After performing the check, make sure to release the failure mode recall function.
High voltage (approx. -3.9kV) is generated during PLASMA
DEODORIZING power operation.
Turn ON the power supply.
Pay careful attention and never touch PLASMA/WASH unit
and the high-voltage lead part (red wire).
While the operation is being
stopped, does
PLASMA/WASH lamp flash
twice?
Yes
Replace the indoor electronic control P.C. board is out of order.
1During pressing both OPERATION SELECT
button and TOO COOL button on the remote
controller at the same time, press RESET button.
2First, release RESET button.
And release the other two buttons since
all LCD in operation display section of the
remote controller is displayed after 3 seconds.
(Failure mode recall function is set.)
3Press OPERATE/STOP (ON/OFF) button.
4After a short beep sound is emitted, press
once PLASMA button.
No
Make sure that the front panel is firmly closed.
1During pressing both OPERATION SELECT button and
TOO COOL button on the remote controller at the same time,
press RESET button.
2First, release RESET button.
And release the other two buttons since
all LCD in operation display section of the
remote controller is displayed after 3 seconds.
(Failure mode recall function is set.)
3Press OPERATE/STOP (ON/OFF) button.
4After a short beep sound is emitted, press
once PLASMA button.
PLASMA DEODORIZING operation is
selected.
wThe plasma power operation check mode is set.(Refer to 9-2.5.)
PLASMA DEODORIZING operation is
selected.
PLASMA
DEODORIZING
operation
PLASMA DEODORIZING power supply is normal.
The front panel is not firmly closed, therefore the
protection by the interlock switch is active.
Stays OFF
Does PLASMA/WASH lamp stay OFF, or
continuously flash?
w1 Turn PLASMA DEODORIZING power OFF and ON again.
(For turning off PLASMA DEODORIZING power, refer to 9-2.3.)
(If it goes normal without turning OFF and ON, PLASMA/WASH lamp
doesn't go OFF.
Continuously flashes.
If the plasma unit is dirty, clean the unit.
After cleaning, make sure to attach the unit when it is
completely dry.
If the air conditioner goes ON with the plasma unit
being wet, protection gets active and PLASMA/WASH
lamp continuously flashes.
Remove the plasma unit, firmly close the
front panel, and then perform PLASMA
DEODORIZING power operation check (w1).
Does PLASMA/WASH lamp stay OFF, or
continuously flash?
Stays OFF
Continuously flashes.
Turn OFF the power supply, and check the
SAFETY DEVICE(PLASMA UNIT).
Is it firmly fixed?
No
Firmly fix the SAFETY DEVICE.
Yes
Turn ON and OFF the SAFETY DEVICE
(PLASMA UNIT) using something like a screw
driver, and measure the resistance value between
CN1T2 1and 3 on the indoor electronic control
P.C. board. Does the switch work?
No
No
Replace the SAFETY DEVICE(PLASMA UNIT).
Yes
Keep the SAFETY DEVICE(PLASMA UNIT)
ON using something like a screw driver.
Turn ON the power supply.
9.5V DC is generated.
While the operation is being stopped, is the
voltage between CN1 1(+) and 2(GND)
on the PLASMA POWER P.C. board
(PLASMA DEODORIZING) 0V?
Replace the indoor electronic control P.C. board.
Yes
Set the plasma power failure mode recall function.
When PLASMA button is pressed, is
there voltage of 12.5V DC between CN1
1(+) and 2(GND)?
Replace the indoor electronic control P.C. board.
Check the wiring of CN1T1 on the indoor electronic control
P.C. board.
No
Yes
Replace the PLASMA POWER P.C. board
(PLASMA DEODORIZING).
26
When PLASMA/WASH lamp flashes 2-time.
wThe power failure mode for PLASMA AIR PURIFYING power is memorized when the failure mode is called.
G
Check of PLASMA AIR PURIFYING power
After performing the check, make sure to release the failure mode recall function.
High voltage (approx. -3.9kV) is generated during
Turn ON the power supply.
PLASMA AIR PURIFYING power operation.
Pay careful attention and never touch PLASMA/WASH unit
and the high-voltage lead part (red wire).
While the operation is being
stopped, does
PLASMA/WASH lamp flash
twice?
Yes
Replace the indoor electronic control P.C. board is out of order.
1During pressing both OPERATION SELECT
button and TOO COOL button on the remote
controller at the same time, press RESET button.
2First, release RESET button.
No
Make sure that the front panel is firmly closed.
1During pressing both OPERATION SELECT button and
TOO COOL button on the remote controller at the same time,
press RESET button.
And release the other two buttons since
all LCD in operation display section of the
remote controller is displayed after 3 seconds.
(Failure mode recall function is set.)
3Press OPERATE/STOP (ON/OFF) button.
4After a short beep sound is emitted, press
twice PLASMA button.
2First, release RESET button.
And release the other two buttons since
all LCD in operation display section of the
remote controller is displayed after 3 seconds.
(Failure mode recall function is set.)
3Press OPERATE/STOP (ON/OFF) button.
4After a short beep sound is emitted, press
twice PLASMA button.
PLASMA AIR PURIFYING operation is
selected.
wThe plasma power operation check mode is set.(Refer to 9-2.5.)
PLASMA AIR PURIFYING operation is
selected.
PLASMA AIR
PURIFYING
operation
PLASMA AIR PURIFYING power supply is normal.
The front panel is not firmly closed, therefore the
protection by the interlock switch is active.
Stays OFF
Does PLASMA/WASH lamp stay OFF, or
continuously flash?
w1 Turn PLASMA AIR PURIFYING power OFF and ON again.
(For turning off PLASMA AIR PURIFYING power, refer to 9-2.3.)
(If it goes normal without turning OFF and ON, PLASMA/WASH lamp
doesn't go OFF.
Continuously flashes.
If the plasma unit is dirty, clean the unit.
After cleaning, make sure to attach the unit when it is
completely dry.
If the air conditioner goes ON with the plasma unit
being wet, protection gets active and PLASMA/WASH
lamp continuously flashes.
Remove the plasma unit, firmly close the
front panel, and then perform PLASMA AIR
PURIFYING power operation check (w1).
Does PLASMA/WASH lamp stay OFF, or
continuously flash?
Stays OFF
Continuously flashes.
Turn OFF the power supply, and check the
SAFETY DEVICE(PLASMA UNIT).
Is it firmly fixed?
No
Firmly fix the SAFETY DEVICE.
Yes
Turn ON and OFF the SAFETY DEVICE
(PLASMA UNIT) using something like a screw
driver, and measure the resistance value between
CN1T2 1and 3 on the indoor electronic control
P.C. board. Does the switch work?
No
No
Replace the SAFETY DEVICE(PLASMA UNIT).
Yes
Keep the SAFETY DEVICE(PLASMA UNIT)
ON using something like a screw driver.
Turn ON the power supply.
While the operation is being stopped, is the
voltage between CN1 1(+) and 2(GND) on
the PLASMA POWER P.C. board (PLASMA
AIR PURIFYING) 0V?
9.5V DC is generated.
Replace the indoor electronic control P.C. board.
Yes
Set the plasma power failure mode recall function.
When PLASMA button is pressed, is
there voltage of 12.5V DC between CN1
1(+) and 2(GND)?
Replace the indoor electronic control P.C. board.
Check the wiring of CN1T1 on the indoor electronic control
P.C. board.
No
Yes
Replace the PLASMA POWER P.C. board
(PLASMA AIR PURIFYING).
27
Indoor unit and outdoor unit do not operate.
Check of auto front panel
H
Turn the remote controller ON.
No
Does the front panel automatically
open? (Does it start to move?)
Yes
No
Is the connector of the front panel
driving motor unit or the indoor
electric control P.C. board unplugged?
Yes
No
Is the resistance value between
terminals of the front panel driving
motor unit normal?
Plug in the connector and
check from the start again.
Yes
Replace the front panel
driving motor unit.
Replace the indoor electric
control P.C. board.
No
Is the front panel held 10mm or
more upper than the level line of
the nozzle top?
Yes
Replace the front panel
driving motor unit.
Front panel is normal.
10 mm or
more
Z-Z side view
28
Electromagnetic noise enters into TV sets or radios
I
No
Is the unit earthed?
Earth the unit.
Yes
Is the distance between the
antennas and the indoor
unit within 3m, or is the
distance between the
antennas and the outdoor
unit within 3m?
Extend the distance between
the antennas and the indoor
unit, or the antennas and the
outdoor unit.
Yes
No
Is the distance between the
TV sets or radios and the
Extend the distance between
the TV sets or radios and the
indoor unit, or the TV sets or
radios and the outdoor unit.
Yes
indoor unit within 1m, or is
the distance between the TV
sets or radios and the
outdoor unit within 3m?
No
Is there any antennas damage
by rust or something , coaxial
cable damage, or poor
Yes
Replace the antennas.
Replace the coaxial cable.
contact such as loosing of
the connectors or wire
disconnection of wiring of the
antennas?
No
Yes
Is the indoor/outdoor
Extend the distance between
the indoor/outdoor connecting
wire of the air conditioner and
the wiring of the antennas.
connecting wire of the air
conditioner and the wiring of
the antennas in close?
No
Even if all of the above conditions is fulfilled, the electromagnetic noise may enter, depending on
the electric field strength or the installation condition (combination of specific conditions such as
antennas or wiring).
Check the followings before asking for service.
1.Devices affected by the electromagnetic noise
TV sets, radios (FM/AM broadcast, shortwave)
2.Channel, frequency, broadcast station affected by the electromagnetic noise
3.Channel, frequency, broadcast station unaffected by the electromagnetic noise
4.Layout of ;
indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring
from antennas, receiver
5.Electric field intensity of the broadcast station affected by the electromagnetic noise
6.Presence or absence of amplifier such as booster
7.Operation condition of air conditioner when the electromagnetic noise enters in.
1)Turn OFF the power supply once, and then turn ON the power supply. In this situation check for
the electromagnetic noise.
2)Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button
on the remote controller for power-on, and check for the electromagnetic noise.
3)After a short time (3 minutes later after turning ON), the outdoor unit starts running. During
operation, check for the electromagnetic noise.
4)Press OPERATE/STOP (ON/OFF) button on the remote controller for power off, when the
outdoor unit stops but the indoor/outdoor communication still runs on. In this situation check for
the electromagnetic noise.
After checking the above, consult the service representative.
29
9-7. Test point diagram and voltage
E1
E1
MSZ-FA25VA -
MSZ-FA35VA -
Indoor electronic control P.C. board
Cement resistance
(R111)
5V DC
12V DC
Indoor fan motor
(CN211)
1311V DC
3(-) Fiducial terminal of
cathode side on measur-
ing high-voltage DC
415V DC
5(+)3-6V DC
6(+)0V DC or 15V DC
Interlock switch(Fan)
(CN1R1)
Room temperature
thermistor (CN111)
Power supply input
230V AC
{
SW P.C. Board
Varistor
(NR11)
WASH reset
switch(SW2)
CN2011
(Used for check of con-
ducting of thermal fuse)
Indoor coil thermistor
RT12(MAIN)12
RT13(SUB)34
(CN112)
Emergency
operation
switch(SW1)
Plasma deodorizing/air
purifying filter units
(CN1T1)
Safety device(Plasma unit)
(CN1T2)
Horizontal and
Vertical vane
motor(CN151)
Timer short mode
point JPG, JPS
(Refer to 8-1.)
}
Power monitor
receiver P.C.
board.
Front panel
driving motor
(CN1U1)
i-see Sensor
(CN110)
Fuse
(F11)
Release of Auto restart
function
Solder the Jumper wire
to JR07.
(Refer to 8-3.)
Indoor coil thermistor [RT12 (MAIN), RT13 (SUB)]
Room temperature thermistor (RT11)
Plasma power P.C. board
1DC 2.5V during PLASMA
AIR PURIFYING/PLASMA
DEODORIZING operation
CN1
High-voltage lead wire
(Red)
2GND
3DC 12.5V during PLASMA
AIR PURIFYING/PLASMA
DEODORIZING operation
Standard lead wire
(Green)
Temperature (:)
30
10
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below.
There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.
(2) The terminal with this connector has the
locking mechanism.
Sleeve
1Slide the sleeve.
1Hold the sleeve, and
2Pull the terminal while
pushing the locking
pull out the terminal
slowly.
Locking lever
lever.
Connector
E1
E1
MSZ-FA25VA -
INDOOR UNIT
MSZ-FA35VA -
OPERATING PROCEDURE
PHOTOS
1. Removing the panel
Photo 1
(1) Press and unlock the knobs on both sides of the front
panel and lift the front panel until it is level, and then pull
the hinges forward to remove the front panel.
(2) Remove the horizontal vane.
Front panel
(3) Remove the screw caps of the panel.
Remove the screws. (See Photo 1.)
(4) Remove the screw of the front panel driving motor.
(See Photo 2.)
(5) Hold the lower part of both ends on the panel and pull it
slightly toward you, and then remove the panel by pushing
it upward.
Screws of the panel
Horizontal vane
Photo 2
Screw of the front panel
driving motor
31
OPERATING PROCEDURE
PHOTOS
2. Removing the electronic control P.C. board, the
power monitor receiver P.C. board, i-see Sensor,
SW P.C. board and the terminal block
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
Photo 3
(2) Remove the screw of the V.A. clamp, and then the
indoor/outdoor connecting wire.(See Photo 3.)
(3) Remove the switch holder from the electrical cover.
(See Photo 4.)
Screws of
(4) Remove the screw of the electrical cover, and then the
electrical cover. (See Photo 4.)
the terminal
block cover
(5) Remove the ground wire connected to the indoor electronic
control P.C. board from the electrical box. (See Photo 5.)
(6) Unhook the power monitor receiver P.C. board holder from
the catch. (See Photo 5.)
(7) Open the rear cover of the power monitor receiver P.C.
board holder and pull out the power monitor receiver P.C.
board.
Screw of the V.A. clamp
Drain hose
(8) Remove the screws of the i-see Sensor cover and the i-see
Sensor motor, and then the i-see Sensor motor.
(9) Open the i-see Sensor holder and pull out the i-see Sensor.
(10) Open the switch holder and pull out SW P.C. board.
(11) Pull the electronic control P.C. board slightly toward you
from the electrical box, and disconnect TAB3 and all the
connectors on the electronic control P.C. board.
(LD101 and LD105 are direct-mounted to the electronic
control P.C. board.)
Photo 4
Switch holder
(12) Pull out the electronic control P.C. board from the electrical
box.
(13) Remove the ground wire connected to the heat exchanger
from the electrical box. (See Photo 5.)
(14) Unhook the catches of the electrical box, and pull out the
electrical box.
Screw of the
electrical cover.
(15) Remove the screws of the terminal block cover, and then
the terminal block cover and the terminal block holder.
(See Photo 3.)
(16) Remove the terminal block by sliding it.
Photo 5
Ground wires Fan motor
connector (CN211)
Connector of the
interlock switch(Fan)
(CN1R1)
3. Removing the electrical box
(1) Remove the horizontal vane, the panel (Refer to 1.) and the
corner box.
(2) Remove the screw of the V.A. clamp, and then the indoor/
outdoor connecting wire.(See Photo 3.)
(3) Remove the switch holder and the electrical cover.
(See Photo 4.)
(4) Remove the ground wire connected to the heat exchanger
from the electrical box.(See Photo 5.)
Indoor coil thermistor
connector (CN112)
Connector of the
plasma power
P.C.board(CN1T1)
(5) Disconnect the following connectors on the electronic
control P.C. board; the fan motor connector <CN211>, the
indoor coil thermistor connector <CN112>, the vane motor
connector <CN151>, the connector of the interlock switch
(Fan) of the horizontal vane <CN1R1>, the connector of
the safety device (plasma unit) <CN1T2>, the connector of
the plasma power P.C. board <CN1T1>, the connector of
the front panel driving motor <CN1U1>.
Connector of the
safety device(Plasma
unit) (CN1T2)
Vane motor
connector (CN151)
Connector of the
front panel driving
motor (CN1U1)
(6) Unhook the catches of the electrical box, and pull out the
electrical box. (See Photo3.)
Power monitor
receiver P.C.
board holder
i-see Sensor
i-see Sensor
cover
32
OPERATING PROCEDURE
PHOTOS
Photo 6
4. Removing the horizontal vane motor unit
(1) Remove the horizontal vane and the panel. (Refer to 1.)
(2) Remove the screws of the horizontal vane motor unit,
and pull out the horizontal vane motor unit. (See Photo 6.)
(3) Disconnect the connector from the horizontal vane motor
unit.
Screw of the horizontal
vane motor unit
Photo 7
5. Removing the vertical vane motor unit
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
(2) Pull out the drain hose from the nozzle assembly, and
remove the nozzle assembly. (See Photo 5.)
(3) Remove the crank of the vertical vane motor unit from the
arm of the vertical vane.(See Photo 7.)
(4) Remove the screws of the vertical vane motor unit, and pull
the vertical vane motor unit. (See Photo 7.)
Arm
Crank of the vertical
vane motor unit
Screws of the vertical
vane motor unit
6. Removing the indoor fan motor and the line flow
fan
Photo 8
Motor band
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
(2) Remove the switch holder and the electrical box. (Refer to 3.)
(3) Pull out the drain hose from the nozzle assembly, and
remove the nozzle assembly.
(4) Remove the screws fixing the motor bed. (See Photo 8.)
(5) Loosen the screw fixing the line flow fan. (See Photo 9.)
(6) Remove the motor bed together with fan motor and motor
band.
(7) Release the hooks of the motor band, and remove the
motor band then pull out the indoor fan motor.
(8) Remove the screws fixing the left side of the heat
exchanger. (See Photo 10.)
(9) Lift the heat exchanger, and pull out the line flow fan to the
lower-left.
Screws of
the motor
bed
Photo 10
Photo 9
Screws of the
left side of the
heat exchanger
Screw of
the line
flow fan
33
OPERATING PROCEDURE
PHOTOS
7. Removing the plasma power P.C. board
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
Photo 11
Photo 12
Photo 13
(2) Remove the switch holder and the electrical cover.
(Refer to 3.)
Screw of the plasma
element holder
Front panel
driving motor
(3) Disconnect the connector of the front panel driving motor
<CN1U1> from the electronic control P.C. board.
(4) Remove the front panel driving motor.
(5) Remove the screw of the plasma element holder, and remove
the plasma element holder from the heat exchanger.
(See Photo 11.)
(6) Unhook all the catches of plasma unit cover and remove
the plasma unit cover. (See Photo 12.)
(7) Remove the terminals with locking mechanism connected
to the plasma power P.C. board and the safety device
(Plasma unit). (See Photo 13.)
(8) Remove the plasma electrical box from the plasma element
holder.
(9) Remove the screw fixing the plasma electrical box, and
open the plasma electrical box then pull out the plasma
power P.C. board from the plasma electrical box.
(See Photo 13.)
Plasma unit cover
Terminal
Screw of
the plasma
electrical box
Terminal
Safety device
(Plasma unit)
Terminal
Terminal
Plasma
power
P.C. board
34
11 PARTS LIST
E1
MSZ-FA25VA - (WH)
E1
MSZ-FA35VA - (WH)
11-2. ACCESSORY AND REMOTE
CONTROLLER
11-1. INDOOR UNIT STRUCTURAL PARTS
10
9
1
8
7
2
3
4
5
6
11-1. INDOOR UNIT STRUCTURAL PARTS
Q'ty/unit
Symbol
Remarks
No.
Part No.
in Wiring
Diagram
Part name
E1
MSZ-FA25VA -
E1
MSZ-FA35VA -
(WH)
(WH)
1
2
3
4
5
6
7
8
E02 897 234
E02 913 000
E02 913 067
E02 913 010
E02 914 100
E02 913 100
E02 913 975
E02 913 970
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
BOX
PANEL ASSEMBLY (WH)
SCREW CAP
Including No.3,4
2PCS/SET
FRONT PANEL (WH)
AIR FILTER (LEFT)
AIR FILTER (RIGHT)
CORNER BOX (RIGHT)
INSTALLATION PLATE
11-2. ACCESSORY AND REMOTE CONTROLLER
E02 913 426
1
1
1
1
9
REMOTE CONTROLLER
KM05A
E02 527 083
10
REMOTE CONTROLLER HOLDER
35
E1
MSZ-FA25VA - (WH)
E1
MSZ-FA35VA - (WH)
11-3. INDOOR UNIT ELECTRICAL PARTS
AND FUNCTIONAL PARTS
SAFETY
DEVICE
(PLASMA UNIT)
PLASMA
POWER
P.C.BOARD
29
25 24
27 26
20
30
1
28
31
2
SLEEVE
BEARING
22
3
4
32
5
INTERLOCK
SWITCH
(FAN)
6
7
21
23
8
SW P.C. BOARD
18
17
16
POWER MONITOR
RECEIVER P.C. BOARD
18
15
14
13
i-see Sensor
MOTOR
POWER MONITOR
RECEIVER P.C.
11
BOARD HOLDER
12
i-see Sensor
9
10
18
19
FUSE VARISTOR
NR11
ROOM
TEMPERATURE
THERMISTOR
11-4. INDOOR UNIT HEAT EXCHANGER
33
34
35
36
11-3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS
Q'ty/unit
Symbol
in Wiring
Diagram
No.
Part No.
Part name
Remarks
E1
E1
MSZ-FA25VA-
(WH)
MSZ-FA35VA-
(WH)
1
2
3
4
5
6
7
8
9
E02 751 509 BEARING MOUNT
E02 001 504 SLEEVE BEARING
E02 897 702 DRAIN HOSE
E02 913 235 NOZZLE ASSEMBLY
E02 897 303 VANE MOTOR UNIT (HORIZONTAL)
E02 897 316 INTERLOCK SWITCH(FAN)
E02 913 303 VANE MOTOR UNIT (VERTICAL)
E02 913 040 HORIZONTAL VANE
E02 127 382 FUSE
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
UP & DOWN
MV1
MV2
RIGHT & LEFT
3.15A
F11
NR11
10 E02 661 385 VARISTOR
11 E02 913 095 POWER MONITOR RECEIVER P.C. BOARD HOLDER
12 E02 913 391 i-see Sensor
13 E02 914 303 i-see Sensor MOTOR
14 E02 897 784 VA CLAMP
15 E02 897 780 TERMINAL BLOCK COVER
16 E02 897 779 TERMINAL BLOCK HOLDER
17 E02 913 375 TERMINAL BLOCK
RR
MT
TB
AUTO RESTART
AUTO RESTART
E02 913 452 ELECTRONIC CONTROL P.C. BOARD W1
E02 914 452 ELECTRONIC CONTROL P.C. BOARD W1
18
1
1
RT11
RT12, RT13
RT12, RT13
19 E02 897 308 ROOM TEMPERATURE THERMISTOR
1
1
E02 913 307 INDOOR COIL THERMISTOR
E02 914 307 INDOOR COIL THERMISTOR
20
1
1
1
1
1
1
1
1
1
2
1
1
1
21 E02 913 782 SWITCH HOLDER
22 E02 897 300 INDOOR FAN MOTOR W2
23 E02 897 333 MOTOR BAND
24 E02 898 303 FRONT PANEL DRIVING MOTOR
25 E02 897 302 LINE FLOW FAN
26 E02 913 775 PLASMA ELEMENT HOLDER
27 E02 913 776 PLASMA UNIT COVER
28 E02 913 777 PLASMA ELECTRICAL BOX
29 E02 897 440 PLASMA POWER P.C. BOARD
30 E02 898 316 SAFETY DEVICE (PLASMA UNIT)
31 E02 913 774 PLASMA AIR PURIFYING FILTER UNIT
32 E02 914 774 PLASMA DEODORIZING FILTER UNIT
1
1
1
1
1
1
1
1
2
1
1
1
MF
MP
RC0J40-
PLASMA_A
PLASMA_D
W1 Including SW P.C. BOARD and POWER MONITOR RECEIVER P.C. BOARD
W2 Including FAN MOTOR RUBBER MOUNT (2 PCS/SET)
11-4. INDOOR UNIT HEAT EXCHANGER
INDOOR HEAT EXCHANGER
INDOOR HEAT EXCHANGER
UNION (GAS)
1
E02 913 620
E02 914 620
34 E02 815 666
35 E02 151 667
33
1
1
1
{9.52
{6.35
1
1
UNION (LIQUID)
37
12 OPTIONAL PARTS
DEODORIZING CERAMIC FILTER
Replacement of the deodorizing ceramic filter(about once every 6 years)
Deodorizing ceramic filter is installed inside PLASMA DEODORIZING filter unit. The filter is fragile. Handle it with care.
NOTE: PLASMA DEODORIZING filter unit may not operate properly if the deodorizing ceramic filter is not installed.
Be sure to install the deodorizing ceramic filter.
(1) Release the two knobs to open the filter unit.
(2) Pull the side knobs to outward and then
forward to remove, as illustrated below.
(3) Pull out the deodorizing ceramic filter from the side of
the filter unit.
Deodorizing ceramic filter
(1)
(2)
(4) Install the deodorizing ceramic filter by following the
removal procedure in reverse.
Model
Part No.
MAC-305FT-E
E1
MSZ-FA25VA -
MSZ-FA35VA -
E1
38
39
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
C Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD
New publication, effective Jan. 2005
Specifications subject to change without notice.
Distributed in Jan. 2005. No. OB371 6
Made in Japan
|