INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national
wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading
it thoroughly.your set and retain it for future reference.
MODELS : ARUV Series
www.lg.com
P/NO : MFL46912316
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must
be followed.
n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
n Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
n Installation
Have all electric work done by a licensed
electrician according to "Electric Facility
Engineering Standard" and "Interior Wire
Regulations" and the instructions given in
this manual and always use a special circuit.
Ask the dealer or an authorized technician to
install the air conditioner.
• If the power source capacity is inadequate or
electric work is performed improperly, electric
shock or fire may result.
• Improper installation by the user may result in
water leakage, electric shock, or fire.
Always ground the product.
Always intstall a dedicated circuit and breaker.
• There is risk of fire or electric shock.
• Improper wiring or installation may cause fire or
electric shock.
For re-installation of the installed product,
always contact a dealer or an Authorized
Service Center.
Do not install, remove, or re-install the unit
by yourself (customer).
• There is risk of fire, electric shock, explosion, or
• There is risk of fire, electric shock, explosion, or
injury.
injury.
Do not store or use flammable gas or
combustibles near the air conditioner.
Use the correctly rated breaker or fuse.
• There is risk of fire or failure of product.
• There is risk of fire or electric shock.
Prepare for strong wind or earthquake and
install the unit at the specified place.
Do not install the product on a defective
installation stand.
• Improper installation may cause the unit to top-
• It may cause injury, accident, or damage to the
ple and result in injury.
product.
Installation Manual 3
Safety Precautions
When installing and moving the air condition-
er to another site, do not charge it with a
different refrigerant from the refrigerant
specified on the unit.
Do not reconstruct to change the settings of
the protection devices.
• If a different refrigerant or air is mixed with the
original refrigerant, the refrigerant cycle may
malfunction and the unit may be damaged.
• If the pressure switch, thermal switch, or other
protection device is shorted and operated
forcibly, or parts other than those specified by
LGE are used, fire or explosion may result.
Ventilate before operating air conditioner
when gas leaked out.
Securely install the cover of control box and
the panel.
• It may cause explosion, fire, and burn.
• If the cover and panel are not installed securely,
dust or water may enter the outdoor unit and fire
or electric shock may result.
If the air conditioner is installed in a small room, measures must be taken to prevent the
refrigerant concentration from exceeding the safety limit when the refrigerant leaks.
• Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceed-
ed. Should the refrigerant leak and cause the safety limit to be exceeded, harzards due to lack of oxy-
gen in the room could result.
Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or
Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
• There is the risk of death, injury, fire or explosion.
n Operation
Do not damage or use an unspecified power
cord.
Use a dedicated outlet for this appliance.
• There is risk of fire, electric shock, explosion, or
• There is risk of fire or electrical shock.
injury.
Be cautious that water could not enter the
product.
Do not touch the power switch with wet
hands.
• There is risk of fire, electric shock, or product
• There is risk of fire, electric shock, explosion, or
damage.
injury.
When the product is soaked (flooded or
submerged), contact an Authorized Service
Center.
Be cautious not to touch the sharp edges
when installing.
• There is risk of fire or electric shock.
• It may cause injury.
Take care to ensure that nobody could step
on or fall onto the outdoor unit.
Do not open the inlet grille of the product
during operation. (Do not touch the electro-
static filter, if the unit is so equipped.)
• This could result in personal injury and product
damage.
• There is risk of physical injury, electric shock, or
product failure.
4
Outdoor Unit
Safety Precautions
n Installation
Always check for gas (refrigerant) leakage
Do not install the product where the noise or
hot air from the outdoor unit could damage
the neighborhoods.
after installation or repair of product.
•
Low refrigerant levels may cause failure of product.
• It may cause a problem for your neighbors.
Keep level even when installing the product.
Do not install the unit where combustible gas
may leak.
• To avoid vibration or water leakage.
• If the gas leaks and accumulates around the
unit, an explosion may result.
Use power cables of sufficient current
carrying capacity and rating.
Do not use the product for special purposes,
such as preserving foods, works of art, etc. It
is a consumer air conditioner, not a precision
refrigeration system.
• Cables that are too small may leak, generate
heat, and cause a fire.
• There is risk of damage or loss of property.
Keep the unit away from children. The heat
exchanger is very sharp.
When installting the unit in a hospital, com-
munication station, or similar place, provide
sufficient protection against noise.
• It can cause the injury, such as cutting the finger.
Also the damaged fin may result in degradation
of capacity.
•
The inverter equipment, private power generator, high-fre-
quency medical equipment, or radio communication equip-
ment may cause the air conditioner to operate erroneous-
ly, or fail to operate. On the other hand, the air conditioner
may affect such equipment by creating noise that disturbs
medical treatment or image broadcasting.
Do not install the product where it is exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins,
could cause product malfunction or inefficient operation.
n Operation
Do not use the air conditioner in special
Do not block the inlet or outlet.
environments.
•
Oil, steam, sulfuric smoke, etc. can significantly reduce
the performance of the air conditioner or damage its parts.
• It may cause failure of appliance or accident.
Make the connections securely so that the
outside force of the cable may not be applied
to the terminals.
Be sure the installation area does not deteri-
orate with age.
• Inadequate connection and fastening may gen-
•
If the base collapses, the air conditioner could fall with it, caus-
ing property damage, product failure, or personal injury.
erate heat and cause a fire.
Install and insulate the drain hose to ensure that water is drained away properly based on the
installation manual.
• A bad connection may cause water leakage.
Installation Manual 5
Safety Precautions
Be very careful about product transportation.
• Only one person should not carry the product if it weighs more than 20 kg.
• Some products use PP bands for packaging. Do not use any PP bands for a means of transportation.
It is dangerous.
• Do not touch the heat exchanger fins. Doing so may cut your fingers.
• When transporting the outdoor unit, suspending it at the specified positions on the unit base. Also
support the outdoor unit at four points so that it cannot slip sideways.
Safely dispose of the packing materials.
Turn on the power at least 6 hours before
starting operation.
•
•
Packing materials, such as nails and other metal or
wooden parts, may cause stabs or other injuries.
Tear apart and throw away plastic packaging bags
so that children may not play with them. If children
play with a plastic bag which was not torn apart,
they face the risk of suffocation.
• Starting operation immediately after turning on
the main power switch can result in severe
damage to internal parts. Keep the power switch
turned on during the operational season.
Do not touch any of the refrigerant piping
during and after operation.
Do not operate the air conditioner with the
panels or guards removed.
• It can cause a burn or frostbite.
• Rotating, hot, or high-voltage parts can cause
injuries.
Do not directly turn off the main power
switch after stopping operation.
• Wait at least 5 minutes before turning off the
main power switch. Otherwise it may result in
water leakage or other problems.
Auto-addressing should be done in condition of
connecting the power of all indoor and outdoour
units. Auto-addressing should also be done in
case of changing the indoor unit PCB.
Use a firm stool or ladder when cleaning or
maintaining the air conditioner.
Do not insert hands or other objects through
the air inlet or outlet while the air conditioner
is plugged in.
• Be careful and avoid personal injury.
• There are sharp and moving parts that could
cause personal injury.
6
Outdoor Unit
Installation Process
Installation Process
Indicate clearly who is to be responsible for switch settings
Determination of division work
Make relationship between outdoor, indoor, remote controller, and option connections clear.
(Prepare control circuit diagram)
Preparation of contract drawings
Take account of gradient
of drain piping
The foundation must be level even
Sleeve and insert work
Outdoor unit foundation work
Installation of outdoor unit
Check model name to make
sure the fitting is made correctly
Avoid short circuits and ensure
sufficient space is allowed for service
Installation of indoor unit
Special attention to dryness,
cleanness and tightness
Refrigerant piping work
Drain pipe work
Duct work
Adjust to downward gradient
Make sure airflow is sufficient
Make sure no gaps are left where
the insulating materials are joined
Heat insulation work
Electrical work
(connection circuits and drive circuits)
Multiple core cable must not be used.
(suitable cable should be selected)
2
Airtight test
Vacuum drying
In the final check for 24hours at 3.8 MPa(38.7 kgf/cm ) there must be no drop in pressure.
The vacuum pump used must have a capacity of reaching at least 5 torr, more than 1 hour
Recharge correctly as calculated in this manual. and record the amount of added refrigerant
Additional charge of refrigerant
Fit facing panels
Make sure there are no gaps left between the facing materials used on the ceiling
Refer to automatic addressing flowchart
Automatic addressing of indoor unit
Preheat the crank case with the electrical heater for more than 6 hours.
Test run adjustment
Run each indoor unit in turn to make sure the pipe work has been fitted correctly
Transfer to customer with explanation
Explain the use of the system as clearly as possible to your customer and make sure all relevant
documentation is in order
• The above list indicates the order in which the individual work operations are normally carried out but this order may be
varied where local conditions warrants such change.
• The wall thickness of the piping should comply with the relevant local and national regulations for the designed pres-
sure 3.8MPa.
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.(If the refriger-
ant is charged in its gaseous state, its composition changes and the system will not work properly.)
Installation Manual 7
Outdoor units Information
Outdoor units Information
n Combination Ration(50~200%)
Outdoor Number
Single outdoor units
Double outdoor units
Triple outdoor units
Connection Capacity
200%
160%
130%
Notes:
* We can guarantee the operation only within 130% Combination.
If you want to connect more than 130% combination, please contact us and discuss the require-
ment like below.
1) If the operation of indoor unit is more than 130%, low airflow operation is recommended in all
the indoor units.
2) If the operation of indoor unit is more than 130%, additional refrigerant is needed according to
the headquarter guidance.
3)Over 130%, capacity is same as capacity of 130%, Same remark is valid for power input.
Caution : ARUV60LT3, ARUV80LT3 Models should be installed only a single unit.
Power Supply: Outdoor Unit (3Ø, 380 - 415V, 50Hz/3Ø, 380V, 60Hz)
n Cooling Only
Unit
1 Outdoor unit
System(HP)
Model
6
ARUV60LT3
ARUV60LT3
10
8
10
12
ARUV80LT3
ARUV80LT3
13
ARUV100LT3
ARUV11600LT3
ARUV120LT3
ARUV21020LT3
Max. Connectable No. of Indoor Units
Net Weight
kg
155 x 1
155 x 1
185 x 1
408 x 1
235 x 1
518 x 1
lbs
mm
341 x 1
341 x 1
Dimensions (WxHxD)
Connecting Pipes
(620 x 1,680 x 760) x 1
(24.4 x 66.1 x 29.9) x 1
9.52(3/8)
(620 x 1,680 x 760) x 1
(24.4 x 66.1 x 29.9) x 1
9.52(3/8)
(920 x 1,680 x 760) x 1
(36.2 x 66.1 x 29.9) x 1
9.52(3/8)
(920 x 1,680 x 760) x 1
(36.2 x 66.1 x 29.9) x 1
12.7(1/2)
inch
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
19.05(3/4)
19.05(3/4)
22.2(7/8)
28.58(1 1/8)
Unit
1 Outdoor Unit
System(HP)
Model
14
16
18
20
ARUV140LT3
ARUV21340LT3
ARUV160LT3
ARUV21660LT3
ARUV180LT3
ARUV21980LT3
ARUV200LT3
ARUV32200LT3
Max. Connectable No. of Indoor Units
Net Weight
kg
235 x 1
518 x 1
265 x 1
584 x 1
315 x 1
694 x 1
315 x 1
694 x 1
lbs
mm
Dimensions (WxHxD)
Connecting Pipes
(920 x 1,680 x 760) x 1 (1,240 x 1,680 x 760) x 1 (1,240 x 1,680 x 760) x 1 (1,240 x 1,680 x 760) x 1
inch
(36.2 x 66.1 x 29.9) x 1
12.7(1/2)
(48.8 x 66.1 x 29.9) x 1
12.7(1/2)
(48.8 x 66.1 x 29.9) x 1
15.88(5/8)
(48.8 x 66.1 x 29.9) x 1
15.88(5/8)
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
28.58(1 1/8)
28.58(1 1/8)
28.58(1 1/8)
28.58(1 1/8)
8
Outdoor Unit
Outdoor Units Information
Unit
2 Outdoor Unit
System(HP)
Model
22
24
26
28
ARUV220LT3
ARUV120LT3
ARUV31500LT3
ARUV240LT3
ARUV140LT3
ARUV31900LT3
ARUV260LT3
ARUV140LT3
ARUV41220LT3
ARUV280LT3
ARUV140LT3
ARUV41540LT3
Max. Connectable No. of Indoor Units
Net Weight
kg
185 x 1 + 235 x 1
408 x 1 + 518 x 1
(920 x 1,680 x 760) x 2
(36.2 x 66.1 x 29.9) x 2
15.88(5/8)
185 x 1 + 235 x 1
408 x 1 + 518 x 1
(920 x 1,680 x 760) x 2
(36.2 x 66.1 x 29.9) x 2
15.88(5/8)
235 x 2
518 x 2
235 x 2
518 x 2
lbs
mm
Dimensions (WxHxD)
Connecting Pipes
(920 x 1,680 x 760) x 2
(36.2 x 66.1 x 29.9) x 2
19.05(3/4)
(920 x 1,680 x 760) x 2
(36.2 x 66.1 x 29.9) x 2
19.05(3/4)
inch
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
28.58(1 1/8)
34.9(1 3/8)
34.9(1 3/8)
34.9(1 3/8)
Unit
2 Outdoor Unit
System(HP)
Model
30
32
34
36
ARUV300LT3
ARUV160LT3
ARUV41940LT3
ARUV320LT3
ARUV180LT3
ARUV51240LT3
ARUV340LT3
ARUV200LT3
ARUV51540LT3
ARUV360LT3
ARUV200LT3
ARUV51860LT3
Max. Connectable No. of Indoor Units
Net Weight
kg
lbs
235 x 1 + 265 x 1
518 x 1 + 584 x 1
235 x 1 + 315 x 1
518 x 1 + 694 x 1
235 x 1 + 315 x 1
518 x 1 + 694 x 1
265 x 1 + 315 x 1
584 x 1 + 694 x 1
Dimensions (WxHxD)
mm
(920 x 1,680 x 760) x 1
(920 x 1,680 x 760) x 1
(920 x 1,680 x 760) x 1 (1,240 x 1,680 x 760) x 2
(1,240 x 1,680 x 760) x 1 (1,240 x 1,680 x 760) x 1 (1,240 x 1,680 x 760) x 1
inch
(36.2 x 66.1 x 29.9) x 1
(48.8 x 66.1 x 29.9) x 1
19.05(3/4)
(36.2 x 66.1 x 29.9) x 1
(48.8 x 66.1 x 29.9) x 1
19.05(3/4)
(36.2 x 66.1 x 29.9) x 1
(48.8 x 66.1 x 29.9) x 1
19.05(3/4)
(48.8 x 66.1 x 29.9) x 2
Connecting Pipes
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
19.05(3/4)
41.3(1 5/8)
34.9(1 3/8)
34.9(1 3/8)
34.9(1 3/8)
Unit
2 Outdoor Unit
3 Outdoor Unit
System(HP)
Model
38
40
42
44
ARUV380LT3
ARUV200LT3
ARUV180LT3
ARUV400LT3
ARUV200LT3
ARUV200LT3
ARUV420LT3
ARUV140LT3
ARUV140LT3
ARUV61440LT3
ARUV440LT3
ARUV160LT3
ARUV140LT3
ARUV61440LT3
Max. Connectable No. of Indoor Units
61
64
Net Weight
kg
lbs
340 × 1 + 350 × 1
749 × 1 + 771 × 1
350 × 2
270 × 3
270 × 2 + 340 × 1
771 × 2
595 × 3
595 × 2 + 749 × 1
Dimensions (WxHxD)
mm
(1,240 × 1,680 × 760) × 2 (1,240 × 1,680 × 760) × 2 (1,240 × 1,680 × 760) × 3 (1,240 × 1,680 × 760) × 3
inch
(48.8 × 66.1 × 29.9) × 2
19.05(3/4)
(48.8 × 66.1 × 29.9) × 2
19.05(3/4)
(48.8 × 66.1 × 29.9) × 3 (48.8 × 66.1 × 29.9) × 3
Connecting Pipes
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
19.05(3/4)
41.3(1 5/8)
19.05(3/4)
41.3(1 5/8)
41.3(1 5/8)
41.3(1 5/8)
Unit
3 Outdoor Unit
System(HP)
Model
46
48
50
52
ARUV460LT3
ARUV180LT3
ARUV140LT3
ARUV61440LT3
ARUV480LT3
ARUV200LT3
ARUV140LT3
ARUV61440LT3
ARUV500LT3
ARUV200LT3
ARUV160LT3
ARUV61440LT3
ARUV520LT3
ARUV200LT3
ARUV180LT3
ARUV61440LT3
Max. Connectable No. of Indoor Units
Net Weight
kg
lbs
235 x 2 + 315 x 1
518 x 2 + 694 x 1
235 x 2 + 315 x 1
518 x 2 + 694 x 1
235 x 1 + 265 x 1 + 315 x 1
518 x 1 + 584 x 1 + 694 x 1
(920 x 1,680 x 760) x 1
235 x 1 + 315 x 2
518 x 1 + 694 x 2
Dimensions (WxHxD)
mm
(920 x 1,680 x 760) x 2
(920 x 1,680 x 760) x 2
(920 x 1,680 x 760) x 1
(1,240 x 1,680 x 760) x 1 (1,240 x 1,680 x 760) x 1 (1,240 x 1,680 x 760) x 2 (1,240 x 1,680 x 760) x 2
inch
(36.2 x 66.1 x 29.9) x 2
(48.8 x 66.1 x 29.9) x 1
19.05(3/4)
(36.2 x 66.1 x 29.9) x 2
(48.8 x 66.1 x 29.9) x 1
19.05(3/4)
(36.2 x 66.1 x 29.9) x 1
(48.8 x 66.1 x 29.9) x 2
19.05(3/4)
(36.2 x 66.1 x 29.9) x 1
(48.8 x 66.1 x 29.9) x 2
19.05(3/4)
Connecting Pipes
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
41.3(1 5/8)
41.3(1 5/8)
41.3(1 5/8)
41.3(1 5/8)
Installation Manual 9
Outdoor Units Information
Unit
3 Outdoor Unit
System(HP)
Model
54
56
58
60
ARUV540LT3
ARUV200LT3
ARUV200LT3
ARUV140LT3
64
ARUV560LT3
ARUV200LT3
ARUV200LT3
ARUV160LT3
64
ARUV580LT3
ARUV200LT3
ARUV200LT3
ARUV180LT3
64
ARUV600LT3
ARUV200LT3
ARUV200LT3
ARUV200LT3
64
Max. Connectable No. of Indoor Units
Net Weight
kg
lbs
235 x 1 + 315 x 2
518 x 1 + 694 x 2
265 x 1 + 315 x 2
584 x 1 + 694 x 2
315 x 3
315 x 3
694 x 3
694 x 3
Dimensions (WxHxD)
mm
(920 x 1,680 x 760) x 1 (1,240 x 1,680 x 760) x 3 (1,240 x 1,680 x 760) x 3 (1,240 x 1,680 x 760) x 3
(1,240 x 1,680 x 760) x 2
inch
(36.2 x 66.1 x 29.9) x 1
(48.8 x 66.1 x 29.9) x 2
19.05(3/4)
(48.8 x 66.1 x 29.9) x 3
(48.8 x 66.1 x 29.9) x 3
(48.8 x 66.1 x 29.9) x 3
Connecting Pipes
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
19.05(3/4)
41.3(1 5/8)
19.05(3/4)
41.3(1 5/8)
19.05(3/4)
41.3(1 5/8)
41.3(1 5/8)
Unit
4 Outdoor Unit
System(HP)
Model
62
64
66
68
ARUV620LT3
ARUV200LT3
ARUV140LT3
ARUV140LT3
ARUV61440LT3
ARUV640LT3
ARUV200LT3
ARUV160LT3
ARUV140LT3
ARUV61440LT3
ARUV660LT3
ARUV200LT3
ARUV180LT3
ARUV140LT3
ARUV61440LT3
ARUV680LT3
ARUV200LT3
ARUV200LT3
ARUV140LT3
ARUV61440LT3
Max. Connectable No. of Indoor Units
Net Weight
kg
lbs
235 x 3 + 315 x 1
518 x 3 + 694 x 1
235 x 2 + 265 x 1 + 315 x 1
518 x 2 + 584 x 1 + 694 x 1
(920 x 1,680 x 760) x 2
235 x 2 + 315 x 2
518 x 2 + 694 x 2
235 x 2 + 315 x 2
518 x 2 + 694 x 2
Dimensions (WxHxD)
mm
(920 x 1,680 x 760) x 3
(920 x 1,680 x 760) x 2
(920 x 1,680 x 760) x 2
(1,240 x 1,680 x 760) x 1 (1,240 x 1,680 x 760) x 2 (1,240 x 1,680 x 760) x 2 (1,240 x 1,680 x 760) x 2
inch
(36.2 x 66.1 x 29.9) x 3
(48.8 x 66.1 x 29.9) x 1
22.2(7/8)
(36.2 x 66.1 x 29.9) x 2
(48.8 x 66.1 x 29.9) x 2
22.2(7/8)
(36.2 x 66.1 x 29.9) x 2
(48.8 x 66.1 x 29.9) x 2
22.2(7/8)
(36.2 x 66.1 x 29.9) x 2
(48.8 x 66.1 x 29.9) x 2
22.2(7/8)
Connecting Pipes
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
44.5(1 3/4)
44.5(1 3/4)
53.98(2)
53.98(2)
Unit
4 Outdoor Unit
System(HP)
Model
70
72
74
76
ARUV700LT3
ARUV200LT3
ARUV200LT3
ARUV160LT3
ARUV61440LT3
ARUV720LT3
ARUV200LT3
ARUV200LT3
ARUV180LT3
ARUV61440LT3
ARUV740LT3
ARUV200LT3
ARUV200LT3
ARUV200LT3
ARUV61440LT3
ARUV760LT3
ARUV200LT3
ARUV200LT3
ARUV200LT3
ARUV61460LT3
Max. Connectable No. of Indoor Units
Net Weight
kg
lbs
235 x 1 + 265 x 1 + 315 x 2
518 x 1 + 584 x 1 + 694 x 2
(920 x 1,680 x 760) x 1
235 x 1 + 315 x 3
518 x 1 + 694 x 3
235 x 1 + 315 x 3
518 x 1 + 694 x 3
265 x 1 + 315 x 3
584 x 1 + 694 x 3
Dimensions (WxHxD)
mm
(920 x 1,680 x 760) x 1
(920 x 1,680 x 760) x 1 (1,240 x 1,680 x 760) x 4
(1,240 x 1,680 x 760) x 3 (1,240 x 1,680 x 760) x 3 (1,240 x 1,680 x 760) x 3
inch
(36.2 x 66.1 x 29.9) x 1
(48.8 x 66.1 x 29.9) x 3
22.2(7/8)
(36.2 x 66.1 x 29.9) x 1
(48.8 x 66.1 x 29.9) x 3
22.2(7/8)
(36.2 x 66.1 x 29.9) x 1
(48.8 x 66.1 x 29.9) x 3
22.2(7/8)
(48.8 x 66.1 x 29.9) x 4
Connecting Pipes
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
22.2(7/8)
53.98(2)
53.98(2)
53.98(2)
53.98(2)
Unit
4 Outdoor Unit
System(HP)
Model
78
80
ARUV780LT3
ARUV200LT3
ARUV200LT3
ARUV200LT3
ARUV61480LT3
ARUV800LT3
ARUV200LT3
ARUV200LT3
ARUV200LT3
ARUV62400LT3
Max. Connectable No. of Indoor Units
Net Weight
kg
315 x 4
694 x 4
315 x 4
694 x 4
lbs
mm
Dimensions (WxHxD)
Connecting Pipes
(1,240 x 1,680 x 760) x 4
(48.8 x 66.1 x 29.9) x 4
22.2(7/8)
(1,240 x 1,680 x 760) x 4
(48.8 x 66.1 x 29.9) x 4
22.2(7/8)
inch
Liquid Pipes[mm(inch)]
Gas Pipes[mm(inch)]
53.98(2)
53.98(2)
10
Outdoor Unit
Environment-friendly Alternative Refrigerant R410A
Environment-friendly Alternative Refrigerant R410A
• The refrigerant R410A has the property of higher operating pressure in comparison with R22.
Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this character-
istic should be also considered during the installation.
R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential (ODP) of R410A is
0. These days the developed countries have approved it as the environment-friendly refrigerant and encour-
aged to use it widely to prevent environment pollution.
CAUTION:
• The wall thickness of the piping should comply with the relevant local and national regulations for the designed
pressure 3.8MPa
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.
If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
• Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
• For high-pressure refrigerant, any unapproved pipe must not be used.
• Do not heat pipes more than necessary to prevent them from softening.
• Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.
Select the Best Location
Select space for installing outdoor unit, which will meet the following conditions:
• No direct thermal radiation from other heat sources
• No possibility of annoying neighbors by noise from unit
• No exposition to strong wind
• With strength which bears weight of unit
• Note that drain flows out of unit when heating
• With space for air passage and service work shown next
• Because of the possibility of fire, do not install unit to the space where generation, inflow, stagnation, and
leakage of combustible gas is expected.
• Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
• Do not use unit under any special environment where oil, steam and sulfuric gas exist.
• It is recommended to fence round the outdoor unit in order to prevent any person or animal from accessing the
outdoor unit.
• If installation site is area of heavy snowfall, then the following directions should be observed.
- Make the foundation as high as possible.
- Fit a snow protection hood.
• Select installation location considering following conditions to avoid bad condition when additionally performing
defrost operation.
1. Install the outdoor unit at a place well ventilated and having a lot of sunshine in case of installing the prod-
uct at a place with a high humidity in winter (neare beach, coast, lake, etc).
(Ex) Rooftop where sunshine always shines.
2. Performance of heating will be reduced and preheat time of the indoor unit may be lengthened in case of
installing the outdoor unit in winter at following location:
(1) Shade position with a narrow space
(2) Location with much moisture in neighboring floor.
(3) Location with much humidity around.
(4) Location where water gathers since the floor is not even.
Installation Manual 11
Installation Space
Installation Space
Individual Installation
n During the installation of the unit, consider service, inlet, and outlet and acquire the minimum space
as shown in the figures below.
Case 1
Case 429mm)
Category
Installation Space
(10mm≤Side Space≤49mm)
(Side Space
≥
B
A≥10
A≥50
B≥300
C≥10
D≥500
B≥100
C≥50
D≥500
A
C
Front
D
B
A≥10
B≥300
C≥10
D≥500
E≥20
A≥50
B≥100
C≥50
C
A
E
E
D≥500
E≥100
Front
D
B
A≥10
A≥50
4 sides are
walls
A
E
C
B≥300
C≥10
D≥500
E≥20
B≥100
C≥50
Front
Front
F
D≥500
E≥100
E≥500
F≥600
Front
Front
Front
D
B
A≥10
A≥50
A
E
C
B≥300
C≥10
D≥300
E≥20
B≥100
C≥50
Front
F
D≥100
E≥100
E≥500
F≥500
D
B
A≥10
B≥300
A
No limit to the height of the wall
Front
Only 2 sides
are walls
B
A≥200
B≥300
E≥400
E
E
A
No limit to the
height of the wall
Front
• The height of the wall on the front side must be 1500mm or less.
• The height of the wall on the inlet side must be 500mm or less.
• There is no limit to the wall on the side.
h2
Limitations on
the height of
the wall
• If the height of the walls on the front and the side are higher than the limit,
there must be additional space on the front and the side.
- Additional Space on the inlet side by 1/2 of h1.
- Additional Space on the front side by 1/2 of h2
- h1 = A(Actual height) - 1500
A
h1
B
(Refer to 4 side
walls)
- h2 = B(Actual height) - 500
12
Outdoor Unit
Installation Space
Seasonal wind and cautions in winter
• Sufficient measures are required in a snow area or severe cold area in winter so that product can be operated
well.
• Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
• Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes on the air suction
hole, the system may malfunction. If it is installed at snowy area, attach the hood to the system.
• Install the outdoor unit at the higher installation console by 50cm than the average snowfall (annual average
snowfall) if it is installed at the area with much snowfall.
• Where snow accumulated on the upper part of the Outdoor Unit by more than 10cm, always remove snow for
operation.
1. The height of H frame must be more than 2 times the snowfall and its width shall not exceed the width of the
product. (If width of the frame is wider than that of the product, snow may accumulate)
2. Don't install the suction hole and discharge hole of the Outdoor Unit facing the seasonal wind.
Installation Manual 13
Lifting Method
Lifting method
• When carrying the suspended, unit pass the ropes under the unit and use the two suspension points each at
the front and rear.
• Always lift the unit with ropes attached at four points so that impact is not applied to the unit.
• Attach the ropes to the unit at an angle of 40° or less.
Locking points for
transportation ropes
Forklift Carrying Hole
Weight per Capacitance
Chassis
Capacity(HP)
Weight(kg)
155
6
UX1
8
155
10
12
14
16
18
20
185
UX2
UX3
235
235
265
Forklift Carrying Guide
315
315
CAUTION
Be very careful while carrying the product.
• Do not have only one person carry product if it is more than 20 kg.
• PP bands are used to pack some products. Do not use them as a mean for transportation because they
are dangerous.
• Do not touch heat exchanger fins with your bare hands. Otherwise you may get a cut in your hands.
• Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging
bag may suffocate children to death.
• When carrying in Outdoor Unit, be sure to support it at four points. Carrying in and lifting with 3-point
support may make Outdoor Unit unstable, resulting in a fall.
• Use 2 belts of at least 8 m long.
• Place extra cloth or boards in the locations where the casing comes in contact with the sling to prevent
damage.
• Hoist the unit making sure it is being lifted at its center of gravity.
14
Outdoor Unit
Installation
Installation
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
• The outdoor unit supports at the bottom shall have width of at least 100mm under the unit°Øs legs before being fixed.
• The outdoor unit supports should have minimum height of 200mm.
• Anchor bolts must be inserted at least 75mm.
For outdoor units of 23kW or
above should not be supported
only by the corner supports.
Outdoor units of 14.5, 16kW
can be supported only by the
Needed for outdoor units of 23kW or above
corner supports.
Center of the Unit
Needed for outdoor units of 23kW or above
Center of the Unit
The location of the Anchor bolts
Unit : mm
Chassis
UX1
Capacity(HP)
6~8
A(mm)
620
B(mm)
497
UX2
10~14
920
792
UX3
16~20
1240
1102
Installation Manual 15
Installation
Foundation for Installation
• Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust.
• Use the H-beam support as a base support
• Noise and vibration may occur from the floor or wall since vibration is transferred through the installation
part depending on installation status. Thus, use anti-vibration materials (cushion pad) fully (The base pad
shall be more than 200mm).
At least 200mm
Unit : mm
- The corner part must be fixed firmly. Otherwise, the
support for the installation may be bent.
- Get and use M10 Anchor bolt.
- Put Cushion Pad between the outdoor unit and ground
support for the vibration protection in wide area.
- Space for pipes and wiring (Pipes and wirings for bot-
tom side)
- H-beam support
- Concrete support
WARNING
• Install where it can sufficiently support the weight of the outdoor unit.
If the support strength is not enough, the outdoor unit may drop and hurt people.
• Install where the outdoor unit may not fall in strong wind or earthquake.
If there is a fault in the supporting conditions, the outdoor unit may fall and hurt people.
• Please take extra cautions on the supporting strength of the ground, water outlet treatment(treat-
ment of the water flowing out of the outdoor unit in operation), and the passages of the pipe and
wiring, when making the ground support.
• Do not use tube or pipe for water outlet in the Base pan. Use drainage instead for water outlet. The
tube or pipe may freeze and the water may not be drained.
WARNING
• Be sure to remove the Pallet(Wood Support) of the bottom
side of the outdoor unit Base Pan before fixing the bolt. It
may cause the unstable state of the outdoor settlement,
and may cause freezing of the heat exchanger resulting in
abnormal operations.
• Be sure to remove the Pallet(Wood Support) of the bottom
side of the outdoor unit before welding. Not removing
Pallet(Wood Support) causes hazard of fire during welding.
Pallet(Wood Support)
- Remove before Installation
16
Outdoor Unit
Installation
Preparation of Piping
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
1) Cut the pipes and the cable.
n Use the accessory piping kit or the pipes purchased
Copper
tube
Slanted Uneven Rough
locally.
90°
n Measure the distance between the indoor and the out-
door unit.
n Cut the pipes a little longer than measured distance.
n Cut the cable 1.5m longer than the pipe length.
Pipe
2) Burrs removal
Reamer
n Completely remove all burrs from the cut cross section
of pipe/tube.
n Put the end of the copper tube/pipe to downward direc-
tion as you remove burrs in order to avoid to let burrs
drop in the tubing.
Point down
3) Flaring work
n Carry out flaring work using flaring tool as shown below.
Handle
Pipe
"ꢀA "
Indoor unit
[kW(Btu/h]
Bar
Bar
"A"
Gas
1/2"
5/8"
3/4"
Liquid
Gas
Liquid
0~0.5
Yoke
Cone
<5.6(19,100)
<16.0(54,600)
<22.4(76,400)
1/4"
3/8"
3/8"
0.5~0.8
0.8~1.0 0.5~0.8
1.0~1.3 0.5~0.8
Copper pipe
Firmly hold copper tube in a bar(or die) as indicated
Clamp handle
dimension in the table above.
Red arrow mark
4) Check
n Compare the flared work with figure below.
n If flare is noted to be defective, cut off the flared section
and do flaring work again.
Smooth all round
Inside is shining without scratches.
= Improper flaring =
Inclined Surface Cracked Uneven
damaged
thickness
Even length
all round
Installation Manual 17
Installation
FLARE SHAPE and FLARE NUT TIGHTENING TORQUE
Precautions when connecting pipes
• See the following table for flare part machining dimensions.
• When connecting the flare nuts, apply refrigerant oil to the inside and outside of the flares and turn them three
or four times at first. (Use ester oil or ether oil.)
• See the following table for tightening torque.(Applying too much torque may cause the flares to crack.)
• After all the piping has been connected, use nitrogen to perform a gas leak check.
pipe size
tightening torque(Ncm)
A(mm)
flare shape
2
90°
Ø9.5
3270-3990
12.8-13.2
A
Ø12.7
Ø15.9
4950-6030
6180-7540
16.2-16.6
19.3-19.7
R=0.4~0.8
CAUTION
• Always use a charge hose for service port connection.
• After tightening the cap, check that no refrigerant leaks are
present.
Union
• When loosening a flare nut, always use two wrenches in
combination, When connecting the piping, always use a spanner
and torque wrench in combination to tighten the flare nut.
• When connecting a flare nut, coat the flare(inner and outer faces)
with oil for R410A(PVE) and hand tighten the nut 3 to 4 turns as
the initial tightening.
Opening shutoff valve
1. Remove the cap and turn the valve counter clockwise with the hexagon wrench.
2. Turn it until the shaft stops.
Do not apply excessive force to the shutoff valve. Doing so may break the valve body, as the valve is not a
backseat type. Always use the special tool.
3. Make sure to tighten the cap securely.
Closing shutoff valve
1. Remove the cap and turn the valve clockwise with the hexagon wrench.
2. Securely tighten the valve until the shaft contacts the main body seal.
3. Make sure to tighten the cap securely.
* For the tightening torque, refer to the table on the below.
Tightening torque
Shutoff
Tightening torque N-m(Turn clockwise to close)
valve size
Shaft(valve body)
Cap(Valve lid) Service port
13.5-16.5
Flare nut
14-17
Gas line piping attached to unit
Ø6.4
5.4-6.6
Hexagonal
33-39
50-60
Ø9.5
Ø12.7
wrench 4mm
8.1-9.9
18-22
-
11.5-13.9
Hexagonal
13.5-16.5
23-27
62-75
Ø15.9
wrench 6mm
Ø22.2
Ø25.4
Hexagonal
27-33
36-44
-
22-28
wrench 10mm
18
Outdoor Unit
Installation
HEAT INSULATION
1. Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over
120°C).
Fastening band
(accessory)
2. Precautions in high humidity circumstance:
This air conditioner has been tested according to the
"ISO Conditions with Mist" and confirmed that there is
not any default. However, if it is operated for a long
Refrigerant piping
time in high humid atmosphere (dew point tempera-
ture: more than 23°C), water drops are liable to fall. In
this case, add heat insulation material according to the
following procedure:
Indoor unit
Thermal insulator
(accessory)
• Heat insulation material to be prepared... EPDM
(Ethylene Propylene Diene Methylene)-over 120°C
the heat-resistance temperature.
• Add the insulation over 10mm thickness at high humidity environment.
Installation Manual 19
Refrigerant piping installation
Refrigerant piping installation
Precautions on Pipe connection / Valve operation
Pipe connection is done by connecting from the end of the pipe to the
branching pipes, and the refrigerant pipe coming out of the outdoor
unit is divided at the end to connect to each indoor unit. Flare connec-
tion for the indoor unit, and welding connection for the outdoor pipe
and the branching parts.
Gas pipe
Liquid pipe
Common pipe
• Use hexagonal wrench to open/close the valve.
WARNING
• Always careful not to leak the refrigerant during welding.
• The refrigerant generates poisonous gas harmful to human body if combusted.
• Do not perform welding in a closed space.
• Be sure to close the cap of the service port to prevent gas leakage after the work.
CAUTION
Please block the pipe knock outs of the front and side panels after installing the pipes.
(Animals or foreign objects may be brought in to damage the cables.)
High Low Pressure Common Pipe Connections
1. For High Low Pressure Common Pipe, use provided elbows to
connect between the outdoor units using pipes.
2. During the cutting of the pipes, remove burr, foreign substances
before connecting. Otherwise, the unit may not operate because
of the sludge inside the pipe.
2
3. Apply Nitrogen Gas of pressure until 3.8MPa(38.7kgf/cm ) for work
Installing 2 units
Installing 3 units
area leakage test.
4. After the degree of a vacuum reaches 5 torr, continue the vacuum-
ing work for more than 1 hour.
5. Open the side pole with hexagonal wrench.
Installing 4 units
❈ When connecting to high low pressure com-
mon pipe, connect pipes using connecting
elbows.
Dig out
Knock Outs
according
the usages.
Dig out Knock Outs according
the usages.
Installing on the front side
Installing on the side(Limited to high
low pressure common pipe)
20
Outdoor Unit
Refrigerant piping installation
Connection of Outdoor units
2 outdoor units
[Unit : mm]
Outdoor units
Model
Gas pipe
Liquid pipe
416
408
331
314
I.D.15.88
I.D.15.88
I.D.28.58
I.D.28.58
I.D.22.2
C
I.D.12.7 I.D.9.52
I.D.19.05
C
111
83
ARCNN21
2 Unit
I.D.31.8 I.D.34.9
I.D.41.3 I.D.38.1 O.D.34.9
I.D.22.2 O.D.19.05
70
I.D.12.7
I.D.15.88
I.D.28.58
130
C
341
298
334
281
3 Unit
4 Unit
I.D.41.3
I.D.34.9
111
83
I.D.22.2 I.D.19.05
I.D.19.05
ARCNN31
ARCNN41
I.D.41.3
O.D.34.9
C
I.D.15.88 I.D.12.7
I.D.28.58
125
415
375
334
281
I.D.19.05
83
I.D.22.2 I.D.19.05
I.D.25.4 O.D.22.2
134
I.D.41.3
A
I.D.44.48 I.D.53.98
C
I.D.15.88 I.D.12.7
I.D.28.58
80
For more information, refer accessory installation manual.
Common pipes
I.D.19.05
O.D.19.05
I.D.19.05
O.D.19.05
Field Supply (Not provided by LG)
Facing
Facing
Y branch
A
downwards
upwards
Within +/- 10
B
Viewed from point A
in direction of arrow
To outdoor unit
To branch piping or indoor unit
A
B
Within 3°
Within 3°
Installation Manual 21
Refrigerant piping installation
Caution
1. Use the following materials for refrigerant piping.
• Material: Seamless phosphorous deoxidized copper pipe
• Wall thickness : Comply with the relevant local and national regulations for the designed pressure
3.8MPa. We recommend the following table as the minimum wall thickness.
Outer diameter
6.35 9.52 12.7 15.88 19.05 22.2 25.4 28.58 31.8 34.9 38.1 41.3 44.45 53.98
[mm]
Minimum
thickness [mm]
0.8
0.8
0.8
0.99
0.99 0.99 0.99 0.99
1.1 1.21 1.35 1.43 1.55 2.1
2. Commercially available piping often contains dust and other materials. Always blow it clean with a dry inert
gas.
3. Use care to prevent dust, water or other contaminants from entering the piping during installation.
4. Reduce the number of bending portions as much as possible, and make bending radius as big as possible.
5. Always use the branch piping set shown below, which are sold separately.
Header
Y branch
4 branch
ARBL054
ARBL104
7 branch
ARBL057
ARBL107
10 branch
ARBL1010
ARBL2010
ARBLN01621, ARBLN03321, ARBLN07121,
ARBLN14521, ARBLN23220
6. If the diameters of the branch piping of the designated refrigerant piping differs, use a pipe cutter to cut
the connecting section and then use an adapter for connecting different diameters to connect the piping.
7. Always observe the restrictions on the refrigerant piping (such as rated length, difference in height, and
piping diameter).
Failure to do so can result in equipment failure or a decline in heating/cooling performance.
8. A second branch cannot be made after a header. (These are shown by .)
A
A
B
To Outdoor Unit
Sealed Piping
A
B
9. The Multi V will stop due to an abnormality like excessive or insufficient refrigerant. At such a time, always
properly charge the unit. When servicing, always check the notes concerning both the piping length and
the amount of additional refrigerant.
10. Never perform a pump down. This will not only damage the compressor but also deteriorate the
performance.
11. Never use refrigerant to perform an air purge. Always evacuate using a vacuum pump.
22
Outdoor Unit
Refrigerant piping installation
12. Always insulate the piping properly. Insufficient insulation will result in a decline in heating/cooling perfor-
mance, drip of condensate and other such problems.
13. When connecting the refrigerant piping, make sure the service valves of the Outdoor Unit is completely
closed (the factory setting) and do not operate it until the refrigerant piping for the Outdoor and Indoor
Units has been connected, a refrigerant leakage test has been performed and the evacuation process
has been completed.
14. Always use a non-oxidizing brazing material for brazing the parts and do not use flux. If not, oxidized film
can cause clogging or damage to the compressor unit and flux can harm the copper piping or refrigerant
oil.
WARNING
When installing and moving the air conditioner to another site, be sure to make recharge refrigerant
after perfect evacuation.
- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and
the unit may be damaged.
- After selecting diameter of the refrigerant pipe to suit total capacity of the indoor unit connected after
branching, use an appropriate branch pipe set according to the pipe diameter of the indoor unit and the
installation pipe drawing.
Installation Manual 23
Pipe connections between indoor and outdoor unit
Pipe connections between indoor and outdoor unit
• Pipe connections can be done on the front side or on the side according to the installation environments.
2
• Be sure to let 0.2kgf/cm Nitrogen flow in the pipe when welding.
• If Nitrogen was not flown during welding, many oxidized membranes may form inside the pipe and disturb the normal
operations of valves and condensers.
Regulator
Refrigerant Pipe
Right Side Pipe Draw Out
Nitrogen(
Direction
Taping
Valve
Left Side Pipe Draw Out
Nitrogen
Front Side Pipe Draw Out
Preparation Work
• Use Knock Outs of Base Pan of the outdoor unit for Left/Right or Bottom pipe drawing outs.
CAUTION
• Do not give damage to the pipe/base during the Knock Out
work.
• Proceed to pipe work after removing burr after Knock Out
work.
• Perform sleeve work to prevent damage to the wire when
connecting wires using knock Outs.
Removal Area for common
pipe bottom side connections.
Removal Area for Liquid/Gas pipe
bottom side connections.
CAUTION
• Remove the brackets on the inverter condenser legs that were fixed to protect the unit during the transportation.
(If bracket is not removed, abnormal noise or vibration may occur.)
Nut
Washer
1. Open the front panel.
2. Remove Brackets
3. Fix with only nut and washer as shown in the figure.
Brackets for Transportation
24
Outdoor Unit
Pipe connections between indoor and outdoor unit
Service Port
n Remove leakage prevention cap
• Remove the leakage prevention cap attached to the out-
door unit service valve before pipe work.
• Proceed the leakage prevention cap removal as follows:
1. Verify whether the liquid/gas/common pipes are locked.
2. Extract remaining refrigerant or air inside using the ser-
vice port.
Liquid pipe
Gas pipe
3. Remove the leakage prevention cap
Common pipe
n Method of pipe cap work during the instal-
lation of single outdoor unit
1. Remove rubber cap inserted in the common pipe.
2. Wrap the common pipe service valve with wet towel.
3. Insert the pipe cap provided into the common pipe.
4. Place high/low pressure flare nut cap under the pipe cap so
that the pipe cap does not move.
Leakage Prevention Cap
5. Weld the pipe cap.
h If not wrapped with a wet towel, there may be damages
inside the valve.
h If the unit is operated without pipe cap work, there may be
abnormality in the cycle caused by refrigerant leakage.
Pipe Cap
Flare Nut
Pipe Drawing Out during Single / Series connection
n Method of drawing out pipes on the front side
• Proceed with the pipe work as shown in the below figure for front side pipe drawing out.
Common pipe Liquid pipe Gas pipe
Pipe Knock Out for
Liquid/Gas pipes
Pipe Knock Out for
common pipes
Installation Manual 25
Pipe connections between indoor and outdoor unit
n Method of drawing out pipes on the bottom side
①
Drawing out common pipe through side panel
Common pipe
Liquid pipe Gas pipe
Remove only liquid/gas pipe Knock Out
Remove Base Pan
②
Drawing out common pipe through bottom pipe
Common pipe
Liquid pipe Gas pipe
Remove Base Pan
n Figure of Sides when drawing out through bottom pipe
Remove Pipe
Knock Out Hole
i) Single outdoor unit
ii) Series outdoor units
(Draw out common pipes
through bottom)
iii) Series outdoor units
(Draw out common pipes
through side panel)
26
Outdoor Unit
Pipe connections between indoor and outdoor unit
Refrigerant piping system
u Y branch method
1 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ : Outdoor Unit
Ⓑ : 1st branch (Y branch)
Ⓒ : Indoor Units
L150m (200 m : Conditional application)
l
40m (90 m : Conditional application)
Slave
2 Outdoor Units
Slave
Master
Slave
Master
Master
Example : 5 Indoor Units connected
Ⓐ : Outdoor Unit
10m or
less
Ⓑ : 1st branch (Y branch)
Ⓒ : Indoor Units
ODU Capacity
Master ≥ Slave
Ⓓ : Downward Indoor Unit
Ⓔ : Connection branch pipe
between Outdoor units:
ARCNN21
L150m (200 m : Conditional application)
40m (90 m : Conditional application)
l
Piping length from outdoor branch to outdoor unit ≤10m, equivalent length:max 13m
(for 22HP or more)
Additional Application
To satisfy below condition to make 40 m ~ 90 m of pipe length after first branch.
1) Diameter of pipes between first branch and the last branch should be increased by one step,
except pipe diameter B,C,D is same as Diameter A
Ø6.35 ’ Ø 9.52 ’ Ø 12.7 ’ Ø 15.88 ’ Ø 19.05 ’ Ø 22.2 ’ Ø 25.4*, Ø 28.58 ’ Ø 31.8*, Ø 34.9 ’ Ø
38.1*
* : It is not necessary to size up.
2) While calculating whole refrigerant pipe length, pipe B,C,D length should be calculated twice.
A+Bx2+Cx2+Dx2+a+b+c+d+e ≤ 1,000 m
3) Length of pipe from each indoor unit to the closest branch (a,b,c,d,e) ≤ 40 m
4) [Length of pipe from outdoor unit to the farthest indoor unit 5 (A+B+C+D+e)]
- [Length of pipe outdoor unit to the closest indoor unit 1 (A+a)] ≤ 40 m
Installation Manual 27
Pipe connections between indoor and outdoor unit
3 Outdoor Units
Slave2
Slave1
Example : 5 Indoor Units
connected
Master
10m or
less
Ⓐ : Outdoor Unit
ODU Capacity
Ⓑ : 1st branch (Y branch)
Master ≥ Slave1 ≥ Slave 2
Ⓒ : Indoor Units
Ⓓ : Downward Indoor Unit
Ⓔ : Connection branch pipe
between Outdoor units:
ARCNN31
L150m (200 m : Conditional application)
l
40m (90 m : Conditional application)
Ⓕ : Connection branch pipe
between Outdoor units:
ARCNN21
4 Outdoor Units
Slave3
Slave2
Slave1
Master
Example : 5 Indoor Units
connected
G
Ⓐ : Outdoor Unit
10m or
less
Ⓑ : 1st branch (Y branch)
ODU Capacity
Ⓒ : Indoor Units
Master ≥ Slave1 ≥ Slave 2 ≥ Slave 3
Ⓓ : Downward Indoor Unit
L150m (200 m : Conditional application)
Ⓔ : Connection branch pipe
between Outdoor units:
ARCNN41
l
40m (90 m : Conditional application)
Ⓕ : Connection branch pipe
between Outdoor units:
ARCNN31
Ⓖ : Connection branch pipe
between Outdoor units :
ARCNN21
Piping length form outdoor branch to outdoor unit ≤ 10 m, equivalent length : max. 13 m(for 22 HP or more)
Additional Application
To satisfy below condition to make 40 m ~ 90 m of pipe length after first branch.
1) Diameter of pipes between first branch and the last branch should be increased by one step,
except pipe diameter B,C,D is same as Diameter A
Ø6.35 ’ Ø 9.52 ’ Ø 12.7 ’ Ø 15.88 ’ Ø 19.05 ’ Ø 22.2 ’ Ø 25.4*, Ø 28.58 ’ Ø 31.8*, Ø 34.9 ’ Ø
38.1*
* : It is not necessary to size up.
2) While calculating whole refrigerant pipe length, pipe B,C,D length should be calculated twice.
A+Bx2+Cx2+Dx2+a+b+c+d+e ≤ 1,000 m
3) Length of pipe from each indoor unit to the closest branch (a,b,c,d,e) ≤ 40 m
4) [Length of pipe from outdoor unit to the farthest indoor unit 5 (A+B+C+D+e)]
- [Length of pipe outdoor unit to the closest indoor unit 1 (A+a)] ≤ 40 m
28
Outdoor Unit
Pipe connections between indoor and outdoor unit
Ú Refrigerant pipe diameter from branch to branch (B,C,D)
Liquid pipe
Gas pipe
Downward Indoor Unit total capacity
[kW(Btu/h)]
[mm(inch)]
[mm(inch)]
≤ 5.6(19,100)
< 16.0(54,600)
Ø6.35(1/4)
Ø9.52(3/8)
Ø9.52(3/8)
Ø9.52(3/8)
Ø12.7(1/2)
Ø15.88(5/8)
Ø15.88(5/8)
Ø19.05(3/4)
Ø19.05(3/4)
Ø22.2(7/8)
Ø22.2(7/8)
Ø12.7(1/2)
Ø15.88(5/8)
Ø19.05(3/4)
Ø22.2(7/8)
≤ 22.4(76,400)
< 33.6(114,700)
< 50.4(172,000)
< 67.2(229,400)
< 72.8(248.500)
< 100.8(344,000)
< 173.6(592,500)
< 184.8(630,700)
< 224.0(764,400)
Ø28.58(11/8 )
Ø28.58(11/8 )
3
Ø34.9(1 /8)
3
Ø34.9(1 /8)
5
Ø41.3(1 /8)
3
Ø44.5(1 /4)
Ø53.98(2)
Ú Total pipe length = A+B+C+D+a+b+c+d+e ≤ 1,000 m
Longest pipe length
Equivalent pipe length
A+B+C+D+e ≤ 175m(225 m**)
L
l
A+B+C+D+e ≤ 150m(200 m**)
*
Longest pipe length after 1st branch
B+C+D+e ≤ 40m(90 m**)
Difference in height(Outdoor Unit ÷ Indoor Unit)
H ≤ 110m
Difference in height (Indoor Unit ÷ Indoor Unit)
h ≤15m
H
h
Difference in height (Outdoor Unit ÷ Outdoor Unit)
h1 ≤ 5m
h1
• * : Assume equivalent piping length of Y branch to be 0.5m, that of header to be 1m, calculation purpose.
• ** : To apply Conditional Application
Ú Refrigerant pipe diameter from branch to branch(A,E,F,G)
Upward Outdoor Unit
Liquid pipe
Gas pipe
total capacity [kW(Btu/h)]
[mm(inch)]
[mm(inch)]
16.0~22.4(54,600~76,400)
28.0(95,900)
33.6(114,700)~44.8(152,900)
50.4(172,000)~61.6(210,600)
67.2(229,400)
72.8(248,500)~95.2(324,900)
100.8(344,000)~168.0(573,300)
173.6(592,500)~179.2(611,600)
184.8(630,700)~224.0(764,400)
Ø19.05(3/4)
Ø22.2(7/8)
Ø9.52(3/8)
Ø12.7(1/2)
Ø15.88(5/8)
Ø28.58(1 1/8 )
Ø34.9(1 3/8)
Ø19.05(3/4)
Ø22.2(7/8)
Ø41.3(1 5/8)
Ø44.5(1 3/4)
Ø53.98(2)
Installation Manual 29
Pipe connections between indoor and outdoor unit
u Header Method
1 Outdoor Unit
Example : 6 Indoor Units connected
Ⓐ : Outdoor Unit
Ⓑ : 1st branch
Ⓒ : Indoor Units
Ⓓ : Sealed piping
L 200m
40m
2 Outdoor Units
Slave
Slave
Slave
Master
Master
Master
Example : 6 Indoor Units connected
Ⓐ : Outdoor Unit
10m or
less
Ⓑ : Header branch
Ⓒ : Indoor Units
ODU Capacity
Master ≥ Slave
Ⓓ : Sealing
Ⓔ : Connection branch pipe
between Outdoor units:
ARCNN21
L 200m
40m
30
Outdoor Unit
Pipe connections between indoor and outdoor unit
3 Outdoor Units
Slave2
Slave1
Master
Example : 6 Indoor Units connected
Ⓐ : Outdoor Unit
Ⓑ : Header branch
Ⓒ : Indoor Units
Ⓓ : Sealing
Ⓔ : Connection branch pipe
between Outdoor units:
ARCNN31
ODU Capacity
Master ≥ Slave1 ≥ Slave2
10m or
less
L 200m
40m
Ⓕ : Connection branch pipe
between Outdoor units:
ARCNN21
Branch pipe can not be used after header
Slave3
Slave2
Slave1
Master
4 Outdoor Units
Example : 6 Indoor Units connected
ODU Capacity
Ⓐ : Outdoor Unit
Ⓑ : Header branch
Ⓒ : Indoor Units
Ⓓ : Sealing
G
F
Master ≥ Slave1 ≥ Slave2 ≥ Slave3
10m or
less
E
L 200m
Ⓔ : Connection branch pipe
between Outdoor units:
ARCNN41
40m
Ⓕ : Connection branch pipe
between Outdoor units:
ARCNN31
Ⓖ : Connection branch pipe
between Outdoor units :
ARCNN21
Branch pipe can not be used after header
Ú Total pipe length = A+a+b+c+d+e+f ≤ 1,000m
Longest pipe length
A+f ≤ 200m
* Equivalent pipe length
A+f ≤ 225m
L
WARNING
Longest pipe length after 1st branch
l
Pipe length after header branching
(a~f)
f ≤ 40m
Difference in height(Outdoor Unit ÷ Indoor Unit)
It is recommended that difference in
length of the pipes connected to the
Indoor Units is minimized.
Performance difference between
Indoor Units may occur.
H
h
H ≤ 110m
Difference in height (Indoor Unit ÷ Indoor Unit)
h ≤15m
Difference in height (Outdoor Unit
h1 ≤ 5m
÷
Outdoor Unit)
h1
• * : Assume equivalent piping length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
• Indoor Unit should be installed at lower position than the header.
• Piping length from outdoor branch to outdoor unit ≤ 10m, equivalent length : max 13m
(for 22HP or more)
Installation Manual 31
Pipe connections between indoor and outdoor unit
u Combination of Y branch/header method
1 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ : Outdoor Unit
Ⓑ : 1st branch (Y branch)
Ⓒ : Y branch
Ⓓ : Indoor Unit
Ⓔ : Header
Ⓕ : Sealed piping
L 150m(200m : Conditional application)
40m(90m : Conditional application)
Branch pipe can not be used after header
2 Outdoor Units
Slave
Slave
Slave
Example : 5 Indoor Units connected
Master
Master
Master
Ⓐ : Outdoor Unit
Ⓑ : 1st branch
ODU Capacity
Master ≥ Slave
10m or
less
Ⓒ : Y branch
Ⓓ : Indoor Unit
Ⓔ : Connection branch pipe
between Outdoor units:
ARCNN21
Ⓕ : Header
L 150m(200m : Conditional application)
40m(90m : Conditional application)
Ⓖ : Sealed piping
Branch pipe can not be used after header
32
Outdoor Unit
Pipe connections between indoor and outdoor unit
3 Outdoor Units
Slave2
Slave1
Master
Example : 5 Indoor Units connected
Ⓐ : Outdoor Unit
Ⓑ : 1st branch(Y branch)
Ⓒ : Y branch
ODU Capacity
Master ≥ Slave1 ≥ Slave2
10m or
less
F
E
Ⓓ : Indoor Unit
Ⓔ : Connection branch pipe
between Outdoor units:
ARCNN31
Ⓕ : Connection branch pipe
between Outdoor units:
ARCNN21
L 150m(200m : Conditional application)
40m(90m : Conditional application)
Ⓖ : Header
Ⓗ : Sealing
Branch pipe can not be used after header
4 Outdoor Units
Slave3
Slave2
Slave1
Example : 5 Indoor Units connected
Master
ODU Capacity
Ⓐ : Outdoor Unit
Master ≥ Slave1 ≥ Slave2 ≥ Slave3
Ⓑ : 1st branch(Y branch)
Ⓒ : Y branch
G
F
E
10m or
less
Ⓓ : Indoor Unit
Ⓔ : Connection branch pipe
between Outdoor units:
ARCNN41
Ⓕ : Connection branch pipe
between Outdoor units:
ARCNN31
L 150m(200m : Conditional application)
40m(90m : Conditional application)
Ⓖ : Connection branch pipe
between Outdoor units:
ARCNN21
Ⓗ : Header
Ⓘ : Sealing
Branch pipe can not be used after header
Installation Manual 33
Pipe connections between indoor and outdoor unit
Ú Refrigerant pipe diameter from branch to branch (B,C)
Liquid pipe
[mm(inch)]
Ø6.35(1/4)
Gas pipe
[mm(inch)]
Ø12.7(1/2)
Downward Indoor Unit total capacity
[kW(Btu/h)]
≤ 5.6(19,100)
< 16.0(54,600)
≤ 22.4(76,400)
Ø9.52(3/8)
Ø9.52(3/8)
Ø9.52(3/8)
Ø12.7(1/2)
Ø15.88(5/8)
Ø15.88(5/8)
Ø19.05(3/4)
Ø19.05(3/4)
Ø22.2(7/8)
Ø22.2(7/8)
Ø15.88(5/8)
Ø19.05(3/4)
Ø22.2(7/8)
Ø28.58(11/8 )
Ø28.58(11/8 )
Ø34.9(13/8)
Ø34.9(13/8)
Ø41.3(15/8)
Ø44.5(13/4)
Ø53.98(2)
< 33.6(114,700)
< 50.4(172,000)
< 67.2(229,400)
< 72.8(248,500)
< 100.8(344,000)
< 173.6(592,500)
< 184.8(630,700)
< 224.0(764,400)
Ú Total pipe length = A+B+C+a+b+c+d+e ≤ 1,000m
Longest pipe length
* Equivalent pipe length
A+B+b ≤ 175m(225m**)
L
l
A+B+b ≤ 150m(200m**)
Longest pipe length after 1st branch
B+b ≤ 40m(90m**)
Difference in height(Outdoor Unit ÷ Indoor Unit)
H ≤ 110m
H
h
Difference in height (Indoor Unit ÷ Indoor Unit)
h ≤ 15m
Difference in height (Outdoor Unit ÷ Outdoor Unit)
h1 ≤ 5m
h1
• *
:
Assume equivalent pipe length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
• Indoor Unit should be installed at lower position than the header.
WARNING
It is recommended that difference of piping length for pipes connected to the Indoor Unit is
minimized. Performance difference between Indoor Units may occur.
Ú Refrigerant pipe diameter from branch to branch(A,E,F,G)
Upward Outdoor Unit
Liquid pipe
Gas pipe
total capacity [kW(Btu/h)]
[mm(inch)]
[mm(inch)]
16.0~22.4(54,600~76,400)
28.0(95,900)
33.6(114,700)~44.8(152,900)
50.4(172,000)~61.6(210,600)
67.2(229,400)
72.8(248,500)~95.2(324,900)
100.8(344,000)~168.0(573,300)
173.6(592,500)~179.2(611,600)
184.8(630,700)~224.0(764,400)
Ø19.05(3/4)
Ø22.2(7/8)
Ø9.52(3/8)
Ø12.7(1/2)
Ø15.88(5/8)
Ø28.58(1 1/8 )
Ø34.9(1 3/8)
Ø19.05(3/4)
Ø22.2(7/8)
Ø41.3(1 5/8)
Ø44.5(1 3/4)
Ø53.98(2)
34
Outdoor Unit
Pipe connections between indoor and outdoor unit
u Outdoor unit Connection
WARNING
• In case of pipe diameter B connected after first branch is bigger than the main pipe diameter A, B should be of
the same size with A.
Ex) In case indoor unit combination ratio 120% is connected to 70kW outdoor unit.
1) Outdoor unit main pipe diameter A : Ø34.9(gas pipe), Ø15.88(liquid pipe)
2) Pipe diameter B after first branch according to 120% indoor unit combination(84kW) :Ø34.9(gas pipe),
Ø19.05(liquid pipe)
Therefore, pipe diameter B connected after first branch would be Ø34.9(gas pipe)/Ø15.88(liquid pipe)
which is same with main pipe diameter.
[Example]
Do not choose the main pipe diameter by downward indoor unit total capacity but its outdoor unit model name.
Do not let the connection pipe from branch to branch exceed the main pipe diameter chosen by outdoor unit
model name.
EX) Where connecting the indoor units to the 22 HP (61.5 kW) outdoor unit to 120% of its system capacity (73.8
kW) and branching 7k (2.1kW) indoor unit at the 1st branch
Main pipe diameter(22 HP outdoor unit): Ø28.58(Gas pipe) Ø15.88(Liquid pipe)
Pipe diameter between 1st and 2nd branch (71.7kW indoor units):
Ø34.9(Gas pipe) Ø19.05(Liquid pipe) in conformity with downward indoor units.
Since the main pipe diameter of 22HP outdoor unit is Ø28.58(Gas pipe) and Ø15.88(Liquid pipe), Ø28.58 (Gas
pipe) and Ø15.88 (Liquid pipe) is used as the main pipe and the connection pipe between 1st and 2nd branch.
* High/Low Pressure Common Pipe: Ø19.05(22HP or more)
u Indoor Unit Connection
Ú Indoor Unit connecting pipe from branch (a,b,c,d,e,f)
Liquid pipe
[mm(inch)]
Ø6.35(1/4)
Ø9.52(3/8)
Ø9.52(3/8)
Gas pipe
Indoor Unit capacity [kW(Btu/h)]
[mm(inch)]
≤ 5.6(19,100)
< 16.0(54,600)
< 22.4(76,400)
Ø12.7(1/2)
Ø15.88(5/8)
Ø19.05(3/4)
Installation Manual 35
Pipe connections between indoor and outdoor unit
u Pipe Connection Method/Precautions for Series connections between Outdoor units
- Separate Y branch joints are needed for series connections between outdoor units.
- Please refer to the below connection examples to install pipe connections between outdoor units.
n Pipe connection between outdoor units
(General Case)
The maximum pipe length
after the first branching
between the outdoor units is
10m or less
n Pipes between outdoor units are
2m or less
2m or less
n Pipes between outdoor units are
2m or longer
Oil Trap
0.2m or more
2m or less
2m or longer
Oil Trap
Oil Trap
2m or less
2m or longer
2m or less
2m or longer
• If the distance between the outdoor units becomes more than 2m, apply Oil Traps between the gas pipes.
• If the outdoor unit is located lower than the main pipe, apply Oil Trap.
n Examples of Wrong Pipe Connections
If the main pipe is higher
than the outdoor units, oil
is accumulated in the
Oil Trap
outdoor unit.
If there are differences in the height
between the outdoor units, oil is
accumulated in the lower outdoor unit.
36
Outdoor Unit
Pipe connections between indoor and outdoor unit
• The pipes between the outdoor units must maintain horizontal levelness or give an inclination to prevent a back flow toward
the slave outdoor unit. Otherwise, the unit may not operate properly.
(Example 1)
Toward indoor unit
Toward indoor unit
(Example 2)
Toward indoor unit
Pipe inclination (2° or more)
Toward indoor unit
(Example 3)
Toward indoor unit
Toward indoor unit
• Apply Oil Trap as shown below when the length of the pipe between the outdoor units is more than 2m.
Otherwise, the unit may not operate properly.
(Example 1)
≤ 2m
Toward indoor unit
(Example 2)
Oil Trap
≤ 2m
Toward indoor unit
≥ 2m
Installation Manual 37
Pipe connections between indoor and outdoor unit
• When connecting the pipes between the outdoor units, the accumulation of oil in the slave outdoor unit should be avoided.
Otherwise, the unit may not operate properly.
(Example 1)
Toward indoor unit
Toward indoor unit
(Example 2)
h
Toward indoor unit
(Example 3)
Oil Trap
h
h
Toward indoor unit
Toward indoor unit
• h : Height of between outdoor units
38
Outdoor Unit
Pipe connections between indoor and outdoor unit
u
The amount of Refrigerant
The calculation of the additional charge should take into account the length of pipe and CF(correction
Factor) value of indoor unit.
Amount refrigerant of Indoor units
Total liquid pipe
:Ø25.4 mm
=
Additional charge(kg)
Example) 4Way Ceiling Cassette 14.5kW -1ea
Ceiling concealed Duct 7.3kW-2ea
Wall Mounted 2.3kW-4ea
Total liquid pipe
:Ø22.2 mm
+
+
CF = 0.64 × 1 + 0.26 × 2 + 0.24 × 4 = 2.12 kg
Total liquid pipe
:Ø19.05 mm
Total liquid pipe
:Ø15.88 mm
+
+
Total liquid pipe
:Ø12.7 mm
Total liquid pipe
:Ø9.52 mm
+
Total liquid pipe
:Ø6.35 mm
+
+
CF value of indoor unit
CF value of indoor unit
(unit : kg)
Capacity(Btu/h(kW)) 5k
7k
9k
12k 15k 18k 24k 28k 36k 42k 48k 76k 96k
Type
(1.6) (2.2) (2.8) (3.6) (4.5) (5.6) (7.1) (8.2) (10.6) (12.3) (14.1) (22.4) (28.0)
Ceiling Concealed Duct (Low Static)
Ceiling Concealed Duct (High Static)
Wall Mounted
-
-
-
-
-
0.17 0.17 0.17 0.17 0.37 0.37
-
-
-
-
-
-
0.26 0.26 0.26 0.26 0.26 0.26 0.44 0.44 0.44 0.62 1.00 1.00
0.24 0.24 0.24 0.24 0.28 0.28
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1Way Ceiling Cassette
2Way Ceiling Cassette
4Way Ceiling Cassette
ARTCOOL Gallery
Floor Standing
0.20 0.20 0.20
-
-
0.29 0.29
0.16 0.16
-
-
-
0.18 0.18 0.25 0.25 0.32 0.32 0.48 0.48 0.64 0.64 0.64
-
-
-
-
-
-
-
0.10 0.10 0.10
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.17 0.17 0.17 0.17 0.37 0.37
-
-
Ceiling & Floor
-
-
0.10 0.10
-
-
-
-
-
-
-
0.75
-
Ceiling Suspended
Console
-
0.35 0.35
0.54
0.17 0.17 0.17 0.17
-
-
-
-
-
-
-
Fresh Air Intake Unit
Heat recovery ventilator(DX)
-
-
-
-
-
-
-
0.62 1.00 1.00
0.20
0.20 0.20
-
-
-
CAUTION
Use only 2-series of indoor unit. Ex) ARNU***2
Installation Manual 39
Pipe connections between indoor and outdoor unit
WARNING
▶ Regulation for refrigerant leakage
: the amount of refrigerant leakage should satisfy the following equation for human safety.
Total amount of refrigerant in the system
3
≤ 0.44 ( kg / m )
Volume of the room at which Indoor Unit of the least capacity is installed
p If the above equation can not be satisfied, then follow the following steps.
- Selection of air conditioning system: select one of the next
1. Installation of effective opening part
2. Reconfirmation of Outdoor Unit capacity and piping length
3. Reduction of the amount of refrigerant
4. Installation of 2 or more security device (alarm for gas leakage)
- Change Indoor Unit type
: installation position should be over 2m from the floor (Wall mounted type ’ Cassette type)
- Adoption of ventilation system
: choose ordinary ventilation system or building ventilation system
- Limitation in piping work
: Prepare for earthquake and thermal stress
Refrigerant Bottling
Liquid pipe
Gas pipe
Ⓐ Manifold Gauge
Ⓑ Low pressure side Handle
Common pipe
Ⓒ High pressure side Handle
- Add exact amount of refrigerant calculated by the installation pipe diameter length and the indoor combination.
- If the refrigerant amount is not exact, it may not operate properly.
- If additionally bottled refrigerant amount is over 10%, condenser burning or insufficient indoor unit performance may be
caused.
WARNING
- Pipe to be vacuumed : gas pipe, water pipe, common pipe
- If the refrigerant amount is not exact, it may not operate properly.
- If additionally bottled refrigerant amount is over 10%, condenser burning or insufficient indoor unit per-
formance may be caused.
40
Outdoor Unit
Pipe connections between indoor and outdoor unit
Distribution Method
1. Line Distribution
Slave
Master
2nd
Slave
3rd main pipe distribution
Master
1st
Slave
Master
2nd
2nd
1st
3rd
1st
3rd
1st
Main pipe
Distribution
2nd
Main pipe
Distribution
2. Vertical Distribution
Ensure that the branch pipes are attached vertically.
Slave
Master
Slave
Master
3. The others
Slave
Master
Slave
Master
Header
Installation Manual 41
Pipe connections between indoor and outdoor unit
Branch pipe Fitting
Y branch
To Outdoor Unit
A
B
B
To Branch Piping or Indoor Unit
A
• Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)
Horizontal
plane
Facing
downwards
Facing
upwards
Within +/- 10°
A
Viewed from point A
in direction of arrow
Within 3°
Within 3°
• There is no limitation on the joint mounting configuration.
• If the diameter of the refrigerant piping selected by the procedures described is different from the size
of the joint, the connecting section should be cut with a pipe cutter.
• Branch pipe should be insulated with the insulator in each kit.
Tape
(field supply)
Liquid and gas
pipe joints
Insulator for
field piping
Insulator
(included with kit)
A
A To outdoor unit
Header
B
To indoor unit
• The indoor unit having larger capacity must be
installed closer to Ⓐ than smaller one.
• If the diameter of the refrigerant piping selected
by the procedures described is different from
the size of the joint, the connecting section
should be cut with a pipe cutter.
B
C
ⓒ Pipe cutter
• When the number of pipes to be connected is
smaller than the number of header branches,
install a cap to the unconnected branches.
42
Outdoor Unit
Pipe connections between indoor and outdoor unit
• When the number of indoor units to be connected to the branch pipes is less than the number of branch
pipes available for connection then cap pipes should be fitted to the surplus branches.
B
Pinched pipe
• Fit branch pipe lie in a horizontal plane.
Horizontal plane
View from point B in the direction of the arrow
• Header should be insulated with the insulator in each kit.
Insulate the header using
the insulation
material attached to the
branch pipe kit
as shown in the figure.
• Joints between branch and pipe should be sealed with the tape included in each kit.
Tape
Insulator
Insulator of field pipe
• Any cap pipe should be insulated using the insulator provided with each kit and then taped as described
above.
Insulator for cap pipe
Cap pipe
Tape
Installation Manual 43
Pipe connections between indoor and outdoor unit
u Y branch pipe
[unit:mm]
Models
Gas pipe
Liquid pipe
I.D.6.35 I.D9.52
I.D12.7
I.D15.88
I.D12.7
I.D6.35
I.D15.88
I.D9.52
1
74
I.D.6.35
I.D15.88
I.D12.7
74
I.D.9.52
ARBLN01621
281
292
281
292
1
O.D9.52
I.D19.05
O.D15.88
I.D12.7
70
70
I.D22.2
I.D19.05
I.D15.88
I.D19.05 I.D12.7
2
I.D12.7
1
I.D9.52
I.D9.52
I.D6.35
I.D19.05
I.D12.7
83
I.D25.4
I.D15.88
I.D12.7
I.D6.35
390
413
74
I.D12.7
3
I.D9.52
ARBLN03321
ARBLN07121
I.D22.2
I.D28.58
I.D22.2
O.D19.05
2
321
332
O.D19.05
70
O.D25.4
I.D25.4
3
1
1
80
110
I.D19.05
I.D19.05
I.D12.7
I.D15.88
I.D15.88
I.D12.7
2
I.D28.58
I.D31.8
I.D22.2
I.D15.88
2
I.D12.7
83
I.D15.88
I.D15.88 I.D19.05
I.D19.05
96
I.D19.05
I.D12.7
3
376
404
371
3
394
I.D28.58 I.D31.8
120
I.D34.9
O.D31.8
I.D22.2
O.D19.05
O.D12.7
I.D9.52 I.D6.35
O.D12.7 I.D9.52
2
I.D28.58
2
1
3
3
O.D22.2
90
120
110
70
I.D34.9
I.D38.1
I.D28.58
2
I.D19.05
I.D41.3
I.D38.1
I.D15.88 I.D19.05
I.D22.2
I.D15.88
2
I.D34.9
1
I.D28.58
I.D15.88
I.D19.05
125
I.D22.2
I.D12.7
I.D34.9
I.D22.2
3
96
471
517
416
444
3
ARBLN14521
ARBLN23220
I.D15.88
I.D41.3
I.D38.1
I.D19.05
O.D38.1
O.D34.9
3
3
2
I.D41.3
I.D12.7
O.D19.05
I.D9.52
110
O.D22.2
O.D15.88
2
I.D9.52
I.D22.2
O.D12.7
I.D6.35
120
130
I.D22.2
90
I.D12.7
O.D28.58
3
3
3
I.D19.05
2
O.D15.88
110
80
I.D.44.48
I.D41.3
I.D.25.4
I.D.53.98
I.D38.1
2
I.D25.4
I.D22.2
I.D.22.2
I.D.19.05
2
1
I.D.44.48
I.D38.1
I.D.44.48
134
I.D41.3
I.D.25.4
I.D.22.2
96
I.D.19.05
3
420
490
3
346
379
I.D.34.9 I.D31.8
I.D.28.58
I.D.53.98
X2
I.D.25.4
O.D.44.48
I.D.22.2
O.D.38.1
O.D.28.58
3
2
3
X2
2
3
I.D.15.88
110
I.D9.52
110
O.D.19.05
I.D.12.7
X2
O.D12.7
I.D6.35
175
115
I.D.15.88
100
I.D12.7
70
I.D.19.05
2
3
3
3
3
O.D15.88
O.D.22.2
120
44
Outdoor Unit
Pipe connections between indoor and outdoor unit
u Header
[unit:mm]
Models
Gas pipe
Liquid pipe
360
360
120
120
ID12.7
ID6.35
ID6.35
ID12.7
4 branch
ARBL054
ID9.52
150
ID15.88
150
ID9.52
120
120
ID15.88
ID12.7
ID9.52
ID15.88
ID19.05
540
540
120
120
ID12.7
ID6.35
ID12.7
7 branch
ARBL057
ID9.52
ID15.88
150
150
120
ID15.88
120
ID9.52
ID15.88
ID12.7
ID19.05
400
360
ID6.35
160
120
ID15.88
ID6.35
ID9.52
ID12.7
4 branch
ARBL104
ID9.52
ID19.05
150
150
120
120
ID15.88
ID22.2
ID9.52
ID12.7
ID28.58 ID25.4
700
580
160
120
ID15.88
ID6.35
ID6.35
ID9.52
ID12.7
7 branch
ARBL107
150
150
ID9.52
ID19.05
120
120
ID15.88
ID12.7
ID9.52
ID28.58 ID25.4
ID22.2
760
720
160
120
ID15.88
ID6.35
10 branch
ARBL1010
ID12.7
ID6.35
ID9.52
150
150
ID19.05
120
ID15.88
120
ID9.52
ID12.7
107
ID9.52
ID28.58
ID25.4
ID22.2
700
60*9=540
775
182
ID15.88
ID6.35
ID12.7
ID15.88
10 branch
ARBL2010
ID6.35
ID9.52
150
ID19.05
150
120
120
ID15.88
ID19.05
ID9.52
ID31.8 ID34.9
ID28.58
Installation Manual 45
Pipe connections between indoor and outdoor unit
Leak Test and Vacuum drying
(1) Leak test
2
Leak test should be made by pressurizing nitrogen gas to 3.8 MPa(38.7kgf/cm ). If the pressure does not drop for
24 hours, the system passes the test. If the pressure drops, check where the nitrogen leaks. For the test method,
refer to the following figure. (Make a test with the service valves closed. Be also sure to pressurize liquid pipe, gas
pipe and high/low pressure common pipe)
The test result can be judged good if the pressure has not be reduced after leaving for about one day after com-
pletion of nitrogen gas pressurization.
Slave 1 outdoor unit
Master outdoor unit
Close
Close
Nitrogen gas
cylinder
Close
Close
Close
Close
Liquid side
Gas side
Nitrogen gas
cylinder
Indoor unit
Note:
If the ambient temperature differs between the time when pressure is applied and when the pressure drop is
checked, apply the following correction factor
There is a pressure change of approximately 0.1 kg/cm (0.01 MPa) for each 1°C of temperature difference.
2
Correction= (Temp. at the time of pressurization – Temp. at the time of check) X 0.1
For example: Temperature at the time of pressurization (3.8 MPa) is 27 °C
24 hour later: 3.73 MPa, 20°C
In this case the pressure drop of 0.07 is because of temperature drop
And hence there is no leakage in pipe occurred.
Caution:
To prevent the nitrogen from entering the refrigeration system in the liquid state, the top of the cylinder must be
at higher position than the bottom when you pressurize the system.
Usually the cylinder is used in a vertical standing position.
46
Outdoor Unit
Pipe connections between indoor and outdoor unit
(2) Vacuum
Vacuum drying should be made from the service port provided on the outdoor unitʼs service valve to the vac-
uum pump commonly used for liquid pipe, gas pipe and high/low pressure common pipe. (Make Vacuum
from liquid pipe, gas pipe and high/low pressure common pipe with the service valve closed.)
* Never perform air purging using refrigerant.
• Vacuum drying: Use a vacuum pump that can evacuate to -100.7kPa (5 Torr, -755mmHg).
1. Evacuate the system from the liquid and gas pipes with a vacuum pump for over 2 hrs and bring the sys-
tem to -100.7kPa.
After maintaining system under that condition for over 1 hr, confirm the vacuum gauge rises. The system
may contain moisture or leak.
2. Following should be executed if there is a possibility of moisture remaining inside the pipe.
(Rainwater may enter the pipe during work in the rainy season or over a long period of time)
After evacuating the system for 2 hrs, give pressure to the system to 0.05MPa(vacuum break) with nitro-
gen gas and then evacuate it again with the vacuum pump for 1hr to -100.7kPa(vacuum drying). If the
system cannot be evacuated to -100.7kPa within 2 hrs, repeat the steps of vacuum break and its drying.
Finally, check if the vacuum gauge does not rise or not, after maintaining the system in vacuum for 1 hr.
Slave 1 outdoor unit
Master outdoor unit
Vacuum
pump
Close
Close
Close
Close
Close
Close
Vacuum
pump
Liquid side
Gas side
Indoor unit
Scale
Use a graviometer. (One that can measure
down to 0.1kg). If you are unable to prepare
such a high-precision gravimeter you may
use a charge cylinder.
Note : Always add an appropriate amount of refrigerant. (For the refrigerant additional charge)
Too much or too little refrigerant will cause trouble.
To use the Vacuum Mode
(If the Vacuum mode is set, all valves of Indoor units and Outdoor units will be opened.)
WARNING
When installing and moving the air conditioner to another site, recharge after perfect evacuation.
- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and
the unit may be damaged.
Installation Manual 47
Pipe connections between indoor and outdoor unit
Vacuum Mode
This function is used for creating vacuum in the system after compressor replacement, ODU parts replace-
ment or IDU addition/replacement.
Vacuum mode setting method
ODU power reset
Vacuum mode cancellation method
Main PCB
SW01S
Master main PCB DIP switch OFF( No.11,14)
Main PCB
SW02B
Power reset
Master main PCB DIP switch ON ( No.11,14)
Press the black button Main PCB (5 sec.)
Vacuum mode cancellation
Main PCB
SW01V
Vacuum mode setting
ODU V/V OPEN
Main EEV, SC EEV OPEN
IDU EEV OPEN
Caution
ODU operation stops during vacuum mode. Compressor can't operate.
48
Outdoor Unit
Pipe connections between indoor and outdoor unit
Thermal insulation of refrigerant piping
Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe separately with
enough thickness heat-resistant polyethylene, so that no gap is observed in the joint between indoor unit
and insulating material, and insulating materials themselves. When insulation work is insufficient, there is a
possibility of condensation drip, etc. Pay special attention to insulation work to ceiling plenum.
B
A
C
Heat
Adhesive + Heat - resistant polyethylene foam +
Adhesive tape
insulation
material
Indoor
Floor exposed Water-proof hemp cloth + Bronze asphalt
Outdoor Water-proof hemp cloth + Zinc plate + Oily paint
Vinyl tape
Outer
covering
A
B
C
Heat insulation material
Pipe
Note:
When using polyethylene cover as covering material, asphalt roof-
ing shall not be required.
Outer covering
(Wind the connection part and cutting part of
heat insulation material with a finishing tape.)
• Do not insulate gas or low pressure pipe and liquid or high
pressure pipe together.
• Be sure to fully insulate connecting portion.
A
B
F
Liquid pipe
A
B
C
D
E
F
A
Gas pipe
Bad example
Power lines
C
Finishing tape
Insulating material
Transmission lines
D
D
E
A
These parts are not insulated.
C
Power lines
Transmission lines
D
A
B
E
Good example
Liquid pipe
Gas pipe
A
Separation
B
C
D
E
Power lines
Insulating material
Transmission lines
Penetrations
Sleeve
Heat insulating material
Lagging
Outer wall
Outer wall (exposed)
Inner wall (concealed)
D
C
E
B
B
A
A
B
Caulking material
Band
I
Waterproofing layer
Sleeve with edge
Penetrating portion on fire
limit and boundary wall
Lagging material
Mortar or other incombustible caulking
Incombustible heat insulation material
Floor (fireproofing)
Roof pipe shaft
I
D
G
J
F
D
B
When filling a gap with mortar, cover the
penetration part with steel plate so that
the insulation material will not be caved in.
For this part, use incombustible materials
for both insulation and covering.(Vinyl
covering should not be used.)
H
G
B
A
1m
1m
49
Outdoor Unit
Installation Manual 49
Electrical Wiring
Electrical Wiring
Caution
1. Follow ordinance of your governmental organization for technical standard related to electrical equipment,
wiring regulations and guidance of each electric power company.
WARNING
Be sure to have authorized electrical engineers do the electric work using special circuits in
accordance with regulations and this installation manual. If power supply circuit has a lack of
capacity or electric work deficiency, it may cause an electric shock or fire.
2. Install the Outdoor Unit transmission line away from the power source wiring so that it is not affected by elec-
tric noise from the power source. (Do not run it through the same conduit.)
3. Be sure to provide designated grounding work to Outdoor Unit.
CAUTION
Be sure to correct the outdoor unit to earth. Do not connect earth line to any gas pipe, liquid pipe,
lightening rod or telephone earth line. If earth is incomplete, it may cause an electric shock.
4. Give some allowance to wiring for electrical part box of Indoor and Outdoor Units, because the box is some-
times removed at the time of service work.
5. Never connect the main power source to terminal block of transmission line. If connected, electrical parts will
be burnt out.
6. Use 2-core shield cable for transmission line.(O mark in the figure below) If transmission lines of different sys-
tems are wired with the same multiplecore cable, the resultant poor transmitting and receiving will cause erro-
neous operations. (
mark in the figure below)
7. Only the transmission line specified should be connected to the terminal block for Outdoor Unit transmission.
Outdoor Unit
Outdoor Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Remote
control
Remote
control
Remote
control
Remote
control
Outdoor Unit
Outdoor Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Remote
control
Remote
control
Remote
control
Remote
control
2-Core Shield Cable
Multi-Core Cable
50
Outdoor Unit
Electrical Wiring
Outdoor Unit
Outdoor Unit
Master Slave1
Slave2
Master Slave1 Slave2
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Remote
controller
Remote
Remote
controller
Remote
controller
controller
Outdoor Unit
Outdoor Unit
Master Slave1
Slave2
Master Slave1
Slave2
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Remote
controller
Remote
Remote
Remote
controller
controller
controller
2-Core Shield Cable
Multi-Core Cable
CAUTION
• Use the 2-core shield cables for transmission lines. Never use them together with power cables.
• The conductive shielding layer of cable should be grounded to the metal part of both units.
• Never use multi-core cable
• As this unit is equipped with an inverter, to install a phase leading capacitor not only will deteriorate
power factor improvement effect, but also may cause capacitor abnormal heating. Therefore, never
install a phase leading capacitor.
• Make sure that the power unbalance ratio is not greater than 2%. If it is greater the units lifespan will
be reduced.
u Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.
Power wire
Round pressure terminal
When none are available, follow the instructions below.
• Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power wiring
may cause abnormal heat.)
• When connecting wiring which is the same thickness, do as shown in the figure below.
• For wiring, use the designated power wire and connect firmly, then secure to prevent outside pressure
being exerted on the terminal block.
• Use an appropriate screwdriver for tightening the terinal screws. A screwdriver with a small head will
strip the head and make proper tighterning impossible.
• Over-tightening the terminal screws may break them.
CAUTION
When the 400 volt power supply is applied to “N” phase by mistake, replace inverter PCB and transformer in
control box.
Installation Manual 51
Electrical Wiring
Control box and connecting position of wiring
- Remove all of the screws at front panel and remove the panel by pulling it forward.
- Connect transmission line between main and sub outdoor unit through the
terminal block.
- Connect transmission lines between outdoor unit and indoor units through
the terminal block.
- When the central control system is connected to the outdoor unit, a dedicat-
ed PCB must be connected between them.
- When connecting transmission line between outdoor unit and indoor units
with shielded wire, connect the shield ground to the earth screw.
Front Panel
WARNING
The temperature sensor for outdoor air should not be exposed to direct sunlight.
- Provide an appropriate cover to intercept direct sunlight.
UX3
Main PCB
Inverter fan PCB
Noise filter
Reactor
Bridge diode
Magnet switch
Inverter PCB
Take care of the phase
sequence of 3-phase 4-wire
power system
UX2
UX1
Main PCB
Main PCB
Inverter fan PCB
Inverter fan PCB
Noise filter
Reactor
Noise filter
Reactor
Bridge diode
Bridge diode
Magnet switch
Inverter PCB
Inverter PCB
Take care of the phase
sequence of 3-phase 4-wire
power system
Take care of the phase
sequence of 3-phase 4-wire
power system
52
Outdoor Unit
Electrical Wiring
Transmission and Power Lines
1) Transmission cable
• Types : shielding wire
2
• Diameter : 10.~1.5mm
• Maximum allowable temperature: 60°C
• Maximum allowable line length: under 300m
2) Remote control cable
• Types : 3-core cable
3) Central control cable
Product type
Wire type
Diameter
2
2
2
ACP&AC Manager(256 IDU) 4-core cable(Shielding wire)
AC Smart II
Simple central controller
10.~1.5mm
10.~1.5mm
10.~1.5mm
4-core cable(Shielding wire)
4-core cable(Shielding wire)
4) Separation of transmission and power lines
• If transmission and power lines are run alongside each other then there is a strong likelihood of operational
faults developing due to interference in the signal wiring caused by electrostatic and electromagnetic cou-
pling.
The tables below indicates our recommendation as to appropriate spacing of transmission and power lines
where these are to be run side by side
Current capacity of power line
Spacing
300mm
500mm
1000mm
1500mm
10A
50A
100A
100V or more
Exceed 100A
Note:
1. The figures are based on assumed length of parallel cabling up to 100m. For length in excess of 100m
the figures will have to be recalculated in direct proportion to the additional length of line involved.
2. If the power supply waveform continues to exhibit some distortion the recommended spacing in the
table should be increased.
• If the lines are laid inside conduits then the following point must also be taken into account when grouping
various lines together for introduction into the conduits
• Power lines(including power supply to air conditioner) and signal lines must not be laid inside the same
• In the same way, when grouping the lines power and signal lines should not be bunched together.
CAUTION
n If apparatus is not properly earthed then there is always a risk of electric shocks, the earthing of the
apparatus must be carried out by a qualified person.
Installation Manual 53
Electrical Wiring
u Wiring of Main Power Supply and Equipment Capacity
1. Use a separate power supply for the Outdoor Unit and Indoor Unit.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceed-
ing with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank
thicker taking into account the line voltage drops. Make sure the power-supply voltage does not drop
more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use should not be lighter than polychloroprene
sheathed flexible cord.
6. Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from
the power supply.
WARNING
• Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring reg-
ulations and guidance of each electric power company.
• Make sure to use specified wires for connections so that no external force is imparted to terminal connections. If con-
nections are not fixed firmly, it may cause heating or fire.
• Make sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include
some amount of direct current.
CAUTION
•
Some installation site may require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may
cause an electric shock.
• Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large
capacity may cause a malfunction of unit or fire.
54
Outdoor Unit
Electrical Wiring
Field Wiring
1. 50Hz
u Example Connection of Communication Cable
n 1 Outdoor Unit-3Ø, 380-415V
3 Phase 4 Wires
Power supply
50Hz 380-415V
[Outdoor Unit]
(Main Switch)
R
S
T
N
Switch
Fuse
Power supply
1 Phase 50Hz
220-240V
N
L
Power Line
(4 Wires Cable)
Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Pull Box
Pull Box
Pull Box
Pull Box
(Installer option)
(Installer option)
(Installer option)
(Installer option)
Power Line
(2 Wires Cable)
Power Line
Power Line
Power Line
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the prod-
uct is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Between Indoor and Master Outdoor unit
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Master
Outdoor Unit
B
A
B
A
B
A
3
4
3
4
3
4
The GND terminal is a '–' terminal for Dry Contact not Ground Line
Installation Manual 55
Electrical Wiring
n 2 Outdoor Units-3Ø, 380-415V
■ When the power source is connected
In series between the units.
3 Phase 4 Wires
Power supply
50Hz 380-415V
(Main Switch)
[Master]
[Slave]
R
S
T
N
Switch
Fuse
Power supply
1 Phase 50Hz
220-240V
N
L
Power Line
(4 Wires Cable)
Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Pull Box
Pull Box
Pull Box
Pull Box
(Installer option)
(Installer option)
(Installer option)
(Installer option)
Power Line
Power Line
Power Line
Power Line
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
■ When the power source is supplied to
Each outdoor unit individually.
3 Phase 4 Wires
Power supply
50Hz 380-415V
(Main Switch)
[Master]
[Slave]
R
S
T
N
R
S
T
N
Switch
Switch
Fuse
Fuse
Power supply
1 Phase 50Hz
220-240V
N
L
Power Line
(4 Wires Cable)
Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Pull Box
Pull Box
Pull Box
Pull Box
(Installer option)
(Installer option)
(Installer option)
(Installer option)
Power Line
Power Line
Power Line
Power Line
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
56
Outdoor Unit
Electrical Wiring
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product
is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Between Indoor and Master Outdoor unit
SODU
IDU INTERNET DRY1 DRY2 GND 12V
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Master
Master
Outdoor unit
Outdoor unit
B
A
B
A
B
A
B
A
B
A
B
A
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Slave
Outdoor Unit
B
A
B
A
B
A
The GND terminal is a '–' terminal for the central controller, not Ground Line
• Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
Installation Manual 57
Electrical Wiring
n 3 Outdoor Units-3Ø, 380-415V
■ When the power source is connected
In series between the units.
3 Phase 4 Wires
Power supply
50Hz 380-415V
(Main Switch)
[Master]
[Slave1]
[Slave2]
R
S
T
N
Switch
Fuse
Power supply
1 Phase 50Hz
220-240V
N
L
Power Line
(4 Wires Cable)
Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Pull Box
Pull Box
Pull Box
Pull Box
(Installer option)
(Installer option)
(Installer option)
(Installer option)
Power Line
Power Line
Power Line
Power Line
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
■ When the power source is supplied to
Each outdoor unit individually.
3 Phase 4 Wires
Power supply
50Hz 380-415V
(Main Switch)
[Master]
[Slave1]
[Slave2]
R
S
T
N
R
S
T
N
R
S
T
N
Switch
Switch
Switch
Fuse
Fuse
Fuse
Power supply
1 Phase 50Hz
220-240V
N
L
Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Power Line
(4 Wires Cable)
Pull Box
Pull Box
Pull Box
Pull Box
(Installer option)
(Installer option)
(Installer option)
(Installer option)
Power Line
Power Line
Power Line
Power Line
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
58
Outdoor Unit
Electrical Wiring
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the prod-
uct is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Between Indoor and Master Outdoor unit
SODU
IDU INTERNET DRY1 DRY2 GND 12V
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Master
Master
Outdoor Unit
B
A
B
A
B
A
Outdoor Unit
B
A
B
A
B
A
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Slave1
Outdoor Unit
B
A
B
A
B
A
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Slave2
The GND terminal is a '–' terminal for the central controller, not Ground Line
• Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
Outdoor Unit
B
A
B
A
B
A
Installation Manual 59
Electrical Wiring
n 4 Outdoor Units - 3Ø, 380-415V
n When the power source is connected
In series between the units.
3 Phase 4 Wires
Power supply
50Hz 380-415V
(Main Switch)
[Master]
[Slave1]
[Slave2]
[Slave3]
R
S
T
N
Switch
Fuse
Power supply
1 Phase 50Hz
220-240V
N
L
Power Line
(4 Wires Cable)
Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Pull Box
Pull Box
Pull Box
Pull Box
(Installer option)
(Installer option)
(Installer option)
(Installer option)
Power Line
Power Line
Power Line
Power Line
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
n When the power source is supplied to
Each outdoor unit individually.
3 Phase 4 Wires
Power supply
50Hz 380-415V
(Main Switch)
[Master]
[Slave1]
[Slave2]
[Slave3]
R
S
T
N
R
S
T
N
R
S
T
N
R
S
T
N
Switch
Switch
Switch
Switch
Fuse
Fuse
Fuse
Fuse
Power supply
1 Phase 50Hz
220-240V
N
L
Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Power Line
(4 Wires Cable)
Pull Box
Pull Box
Pull Box
Pull Box
(Installer option)
(Installer option)
(Installer option)
(Installer option)
Power Line
Power Line
Power Line
Power Line
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
60
Outdoor Unit
Electrical Wiring
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product
is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Between Indoor and Master Outdoor unit
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Master
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Master
Outdoor unit
B
A
B
A
B
A
Outdoor unit
B
A
B
A
B
A
SODU
IDU INTERNET DRY1 DRY2 GND 12V Slave1
Outdoor unit
B
A
B
A
B
A
SODU
IDU INTERNET DRY1 DRY2 GND 12V Slave2
Outdoor unit
B
A
B
A
B
A
The GND terminal is a '–' terminal for the
central controller, not Ground Line
• Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
Installation Manual 61
Electrical Wiring
2. 60Hz
u Example Connection of Communication Cable
n 1 Outdoor Unit - 3Ø, 380V
3 Phase 4 Wires
Power supply
60Hz 380V
[Outdoor Unit]
(Main Switch)
R
S
T
N
Switch
Fuse
Power supply
1 Phase 60Hz
220V
N
L
Power Line
(4 Wires Cable)
Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Pull Box
Pull Box
Pull Box
Pull Box
(Installer option)
(Installer option)
(Installer option)
(Installer option)
Power Line
Power Line
Power Line
Power Line
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the prod-
uct is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Between Indoor and Master Outdoor unit
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Master
Outdoor Unit
B
A
B
A
B
A
3
4
3
4
3
4
The GND terminal is a '–' terminal for Dry Contact not Ground Line
62
Outdoor Unit
Electrical Wiring
n 2 Outdoor Units - 3Ø, 380V
n When the power source is connected
In series between the units.
3 Phase 4 Wires
Power supply
60Hz 380V
(Main Switch)
[Master]
[Slave]
R
S
T
N
Switch
Fuse
Power supply
1 Phase 60Hz
220V
N
L
Power Line
(4 Wires Cable)
Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Pull Box
Pull Box
Pull Box
Pull Box
(Installer option)
(Installer option)
(Installer option)
(Installer option)
Power Line
Power Line
Power Line
Power Line
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
n When the power source is supplied to
Each outdoor unit individually.
3 Phase 4 Wires
Power supply
60Hz 380V
(Main Switch)
[Master]
[Slave]
R
S
T
N
R
S
T
N
Switch
Switch
Fuse
Fuse
Power supply
1 Phase 60Hz
220V
N
L
Power Line
(4 Wires Cable)
Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Pull Box
Pull Box
Pull Box
Pull Box
(Installer option)
(Installer option)
(Installer option)
(Installer option)
Power Line
Power Line
Power Line
Power Line
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
Installation Manual 63
Electrical Wiring
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the prod-
uct is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Between Indoor and Master Outdoor unit
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Master
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Master
Outdoor Unit
B
A
B
A
B
A
Outdoor Unit
B
A
B
A
B
A
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Slave
Outdoor Unit
B
A
B
A
B
A
The GND terminal is a '–' terminal for the central controller, not Ground Line
• Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
64
Outdoor Unit
Electrical Wiring
n 3 Outdoor Units - 3Ø, 380V
n When the power source is connected
In series between the units.
3 Phase 4 Wires
Power supply
60Hz 380V
(Main Switch)
[Master]
[Slave1]
[Slave2]
R
S
T
N
Switch
Fuse
Power supply
1 Phase 60Hz
220V
N
L
Power Line
(4 Wires Cable)
Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Pull Box
Pull Box
Pull Box
Pull Box
(Installer option)
(Installer option)
(Installer option)
(Installer option)
Power Line
Power Line
Power Line
Power Line
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
n When the power source is supplied to
Each outdoor unit individually.
3 Phase 4 Wires
Power supply
60Hz 380V
(Main Switch)
[Master]
[Slave1]
[Slave2]
R
S
T
N
R
S
T
N
R
S
T
N
Switch
Switch
Switch
Fuse
Fuse
Fuse
Power supply
1 Phase 60Hz
220V
N
L
Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Power Line
(4 Wires Cable)
Pull Box
Pull Box
Pull Box
Pull Box
(Installer option)
(Installer option)
(Installer option)
(Installer option)
Power Line
Power Line
Power Line
Power Line
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
Installation Manual 65
Electrical Wiring
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the prod-
uct is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Between Indoor and Master Outdoor unit
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Master
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Master
Outdoor Unit
B
A
B
A
B
A
Outdoor Unit
B
A
B
A
B
A
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Slave1
Outdoor Unit
B
A
B
A
B
A
SODU
IDU INTERNET DRY1 DRY2 GND 12V
The GND terminal is a '–' terminal for the central controller, not Ground Line
• Make sure that terminal number of master and slave outdoor units are matched.
(A-A,B-B)
Slave2
Outdoor Unit
B
A
B
A
B
A
66
Outdoor Unit
Electrical Wiring
n 4 Outdoor Units - 3Ø, 380V
n When the power source is connected
In series between the units.
3 Phase 4 Wires
Power supply
60Hz 380V
(Main Switch)
[Master]
[Slave1]
[Slave2]
[Slave3]
R
S
T
N
Switch
Fuse
Power supply
1 Phase 60Hz
220V
N
L
Power Line
(4 Wires Cable)
Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Pull Box
Pull Box
Pull Box
Pull Box
(Installer option)
(Installer option)
(Installer option)
(Installer option)
Power Line
Power Line
Power Line
Power Line
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
n When the power source is supplied to
Each outdoor unit individually.
3 Phase 4 Wires
Power supply
60Hz 380V
(Main Switch)
[Master]
[Slave1]
[Slave2]
[Slave3]
R
S
T
N
R
S
T
N
R
S
T
N
R
S
T
N
Switch
Switch
Switch
Switch
Fuse
Fuse
Fuse
Fuse
Power supply
1 Phase 60Hz
220V
N
L
Power Line
(2 Wires Cable)
Communication Line
(2 Wires Cable)
Power Line
(4 Wires Cable)
Pull Box
Pull Box
Pull Box
Pull Box
(Installer option)
(Installer option)
(Installer option)
(Installer option)
Power Line
Power Line
Power Line
Power Line
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
Installation Manual 67
Electrical Wiring
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equip-
ment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the product is
operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Between Indoor and Master Outdoor unit
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Master
SODU
IDU INTERNET DRY1 DRY2 GND 12V
Master
Outdoor unit
B
A
B
A
B
A
Outdoor unit
B
A
B
A
B
A
SODU
IDU INTERNET DRY1 DRY2 GND 12V Slave1
Outdoor unit
B
A
B
A
B
A
SODU
IDU INTERNET DRY1 DRY2 GND 12V Slave2
Outdoor unit
B
A
B
A
B
A
The GND terminal is a '–' terminal for the
central controller, not Ground Line
• Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
u Example Connection of Communication Cable
[BUS type]
[STAR type]
• Connection of communication cable must be
installed like below figure between indoor unit to
outdoor unit.
• Abnormal operation can be caused by communi-
cation defect, when connection of communication
cable is installed like below figure(STAR type).
68
Outdoor Unit
Electrical Wiring
u UX1 Chassis Wire Connection
Left Side
Right Side
Main Powerr Terminal Block
Main Powerr Terminal Block
Power/Ground lines
Power/Ground lines
Ground Cable
Ground Cable
Over 50mm Gap
Over 50mm Gap
Communication line
Communication line
Front Side 2
Front Side 1
Main Powerr Terminal Block
Main Powerr Terminal Block
Ground Cable
Ground Cable
Power/Ground lines
Over
50mm Gap
Power/Ground lines
Communication line
Communication line
Over 50mm Gap
Main Power Connection
Main PCB Connection
Main Powerr Terminal Block
Insulation sleeves attachments
Ground Cable
ODU-ODU
Communication line
ODU-IDU
Communication
line
Fix firmly not
to be displaced
Installation Manual 69
Electrical Wiring
u UX2 Chassis Wire Connection
Left Side
Right Side
Main Power
Main Power
Terminal Block
Terminal Block
Power/Ground lines
Power/Ground lines
Ground Cable
Ground Cable
Over 50mm Gap
Over 50mm Gap
Communication line
Communication line
Front Side 1
Front Side 2
Main Power
Main Power
Terminal Block
Terminal Block
Ground Cable
Ground Cable
Power/Ground lines
Over
50mm Gap
Power/Ground lines
Communication line
Communication line
Over 50mm Gap
Main Power Connection
Main PCB Connection
Ma
a
ininPo
P
w
o
ew
r
er
Terminal Block
Terminal Block
Insulation sleeves attachments
Ground Cable
ODU-IDU
Communication line
ODU-ODU
Communicattion line
Fix firmly not to be displaced
70
Outdoor Unit
Electrical Wiring
u UX3 Chassis Wire Connection
Right Side
Left Side
Main Power
႖MaဴinꢀPఎowၴerఝ
Terminal Block
Terminal Block
Power/Ground lines
Power/Ground lines
Ground Cable
Ground Cable
Over 50mm Gap
Over 50mm Gap
Communication line
Communication line
Front Side 1
Front Side 2
Main Power
Main Power
Terminal Block
Terminal Block
Ground Cable
Ground Cable
Power/Ground lines
Over
50mm Gap
Power/Ground lines
Communication line
Communication line
Over 50mm Gap
Main Power Connection
Main PCB Connection
:
;
<
6
Main Power Terminal Block
Insulation sleeves attachments
Ground Cable
ODU-IDU
ODU-ODU
Communication
line
Communicaationn line
Fix firmly not
to be displaced
Installation Manual 71
Electrical Wiring
Location of setting Switch
Main PCB
SW01B
SW02B
7 - Segment
SW02V
(Auto Addressing)
72
Outdoor Unit
Electrical Wiring
DIP switch setting
n Checking according to dip switch setting
1. You can check the setting values of the Master outdoor unit from the 7 segment LED.
The dip switch setting should be changed when the power is OFF.
2. It checks whether the input is properly performed without the bad contact of the dip switch or not
n Checking the setting of the Master unit
The number is sequentially appeared at the 7 segment in 5 seconds after applying the power. This
number represents the setting condition. (For example, represents R410A 30HP)
Master model code ‘ Slave1 model code ‘ Slave2 model code ‘ total capacity ‘ 2 ‘ 25 ‘ 150
1 ~255 : Master model code
1 ~255 : Slave1 model code
Refer to table code
1 ~255 : Slave2 model code
}
6~80HP : HP number(sum of master capacity and slave capacity)
No display : cooling only
25 : normal
2 : heat pump
150 : Model Type
Example) 30Hp, R410A
16 ’ 15 ’ 30 ’ 2 ’ 25 ’ 150
CAUTION
Product may not properly operate if the relevant DIP switch is not properly setup.
Model Code
Model Code
Unit (HP)
Unit
Ref.
11
12
13
14
15
16
17
18
6
8
10
12
14
16
18
20
Master &
Slave
R410A
Installation Manual 73
Electrical Wiring
n Setting the DIP switch
• If you set the Dip switch when power is on, the changed setting will not be applied immediately.
The changed setting will be enabled only when Power is reset or by pressing Reset button.
Index
1
2
3
4
5
6
7
8
9
10 11 12 13 14
●
●
●
●
●
●
●
●
●
●
●
●
●
●
ⅹ
ⅹ
ⅹ
●
●
●
ⅹ
●
ⅹ
●
ⅹ
Auto charging
Refrigerant Checking Function
Indoor EEV malfunction (Cooling)
Indoor EEV malfunction (Heating)
Integrated test operation function (Cooling)
Inverter backup
●
●
Unit backup
ⅹ
ⅹ
ⅹ
ⅹ
●
ⅹ
●
ⅹ
●
●
ⅹ
ⅹ
ⅹ
Non-operation indoor unit EEV adjustment
Indoor unit target subcooling/overheating adjustment
Dry contact
Snow removal function
Static pressure mode
Night low noise operation (Cooling only)
Night low noise operation (Cooling/Heating)
Pump down
●
ⅹ
ⅹ
ⅹ
ⅹ
ⅹ
ⅹ
●
●
●
ⅹ
●
ⅹ
●
●
ⅹ
●
ⅹ
●
●
●
Pump out
●
Forced oil return operation
Vacuum mode
●
ⅹ
ⅹ
ⅹ
●
ⅹ
●
ⅹ
ⅹ
●
●
ⅹ
●
●
●
Master unit
Slave 1 unit
Slave 2 unit
Slave 3 unit
CAUTION
1. ʻXʼ mark within the table means that the dip switch must be pulled down. If not, the function may not work properly.
2. If the applicable dip switch is not set properly, the product may not work properly.
3. When executing the test operation, check the operating condition of the indoor unit and only execute the operation when
all indoor units are stopped.
4. Auto test operation function does not work for the product where only one indoor unit is connected for use.
74
Outdoor Unit
Electrical Wiring
Automatic Addressing
• The address of indoor units would be set by auto
addressing
SW01B
SW02B
7 - Segment
1) Wait for 3 minutes after applying power supply
(master and sub outdoor unit, indoor unit).
2) Press the switch of the outdoor unit (SW02V) for 5
seconds.
SW02V
(Auto Addressing)
3) A "88" is indicated on 7-segment LED of the out-
door unit PCB.
4) For completing addressing, 2~7 minutes are
required depending on numbers of indoor unit con-
nection set.
5) Numbers of indoor unit connection set whose
addressing is completed are indicated for 30sec-
onds on 7-segment LED of the outdoor unit PCB.
6) After completing addressing, address of each
indoor unit is indicated on the wired remote control
display window. (CH01, CH02, CH03, .............
CH06: Indicated as numbers of indoor unit connec-
tion set.)
CAUTION
- In replacement of the indoor unit PCB, always perform auto address setting again.
If power supply is not applied to the indoor unit, operation error occurs.
Auto addressing is only possible on the main PCB
Auto addressing has to be performed after 3 minutes to improve communication.
u The Procedure of Automatic Addressing
Power On
Waiting 3 minutes
Press SW02V for 5 sec.
Auto addressing start
7-segment LED
= 88
Don't Press SW02V
• Auto addressing setting end
Numbers of indoor unit connection set whose
addressing is completed are indicated for 30seconds
on 7-segment LED after completing setting
Waiting about 2~7 minutes
NO
Check the connections
of transmission line
7-segment LED
= 88
Indoor address number is displayed on wired remote control or
indoor unit display window. It is not an error message, will
disappeared when on/off button is pressed on remote control
ex) Display of 01, 02, ..., 15 means connection of 15 indoor
units and auto addressing is completed normally.
YES
OK
Installation Manual 75
Electrical Wiring
Group Number setting
Group Number setting for Indoor Units
① Confirm the power of whole system(Indoor Unit, Outdoor Unit) is OFF, otherwise turn off.
② The transmission lines connected to INTERNET terminal should be connected to central control of Outdoor
unti with care for their polarity( A ’ A, B ’ B )
③ Turn the whole system on.
④ Set the group and Indoor Unit number with a wired remote control.
⑤ To control several sets of Indoor Units into a group, set the group ID from 0 to F for this purpose.
Outdoor Units
Terminal block on the main PCB
SODU
IDU
INTERNET
DRY1
DRY2
GND
12V
A
A
A
B
B
B
B
A
B(D)
A(C)
Group recognizing the simple central controller
No.0 group (00~0F)
No.1 group (10~1F)
No.2 group (20~2F)
No.3 group (30~3F)
No.4 group (40~4F)
No.5 group (50~5F)
No.6 group (60~6F)
No.7 group (70~7F)
No.8 group (80~8F)
No.9 group (90~9F)
No. A group (A0~AF)
No. B group (B0~BF)
No. C group (C0~CF)
No. D group (D0~DF)
No. E group (E0~EF)
No. F group (F0~FF)
76
Outdoor Unit
Electrical Wiring
Outdoor unit Dry Contact installation and connection
• Connect wires as below figure at the hole of backside of Outdoor Unit Dry Contact.
• Insert the wire in the connection hole pushing the "Push" button.
• Setting Main PCB Dip SW of Master Outdoor Unit.
Mode Change
Fan
Outdoor Unit
Heating
Cooling
Push Button
Installation Manual 77
Test Run
Test Run
Checks Before Test Run
1
Check to see whether there is any refrigerant leakage, and slack of power or transmission cable.
2
Confirm that 500 V megger shows 2 MΩ or more between power supply terminal block and ground. Do
not operate in the case of 2 MΩ or less.
NOTE: Never carry out megaohm check over terminal control board. Otherwise the control board
would be broken.
Immediately after mounting the unit or after leaving it turned off for an extended length of time,
the resistance of the insulation between the power supply terminal board and the ground may
decrease to approx. 2 MΩ as a result of refrigerant accumulating in the internal compressor.
If the insulation resistance is less than 2 MΩ, turning on the main power supply and energizing
the crankcase heater for more than 6 hours will cause the refrigerant to evaporate, increasing
the insulation resistance.
3
4
Check if high/low pressure common pipe, liquid pipe and gas pipe valves are fully opened.
NOTE: Be sure to tighten caps.
Check if there are any problems in automatic addressing or not:
Check and confirm that there are no error messages in the display of indoor units or remote controls
and LED in outdoor units.
Functions of each Test run steps
Step 0. Verify the command signals
Select function to be executed during the test run
Step 1. Examine Sensor
Examine the normal operations of the sensors attached to the outdoor/indoor units
Step 2. Examine Indoor unit EEV and wrong wirings
Examine the normal operation of EEV attached to the indoor unit, and examine the wirings of the indoor unit.
Step 3. Refrigerant Automatic Recharge
If additional bottling of the refrigerant is needed, operate to perform this automatically.
Step 4. Automatic Refrigerant Decisions
Inspect if the bottled refrigerant in the system has adequate quantity.
Step 5. Integrated Test Run
Process to verify the normal operations of the parts attached to the system, and verify normal operation of the sys-
tem.
Step 6. Real-time sensor checking
Check the sensors while operating in real-time.
h Gas pipes and Liquid pipes connections inspection
: Inspect whether the gas pipes and Liquid pipes are connected to each other.
CAUTION
when cutting main power of the Multi V
• Always apply main power of the outdoor unit during use of product
(cooling season/heating season).
• Always apply power 6 hours in advance to heat the crank case heater where performing test run
after installation of product. It may result in burning out of the compressor if not preheating the
crank case with the electrical heater for more than 6 hours.(In case of the outdoor temperatue
below 10°C)
78
Outdoor Unit
Test Run
How to Cope with Test Run Abnormality
The phenomena from main component failure
Component
Phenomenon
Not operating
Cause
Check method and Trouble shooting
Motor insulation broken Check resistance between terminals and
chassis
Strainer clogged
Oil leakage
Change strainer
Check oil amount after opening oil port
Compressor
Stop during running Motor insulation failure Check resistance between terminals and
chassis
Abnormal noise
during running
R-S-T misconnection
Check compressor R-S-T connection
High pressure error Motor failure,
Check the outdoor fan operation after being
Outdoor
fan
at cooling
bad ventilation around turned the outdoor units off for some time.
outdoor heat exchanger Remove obstacles around the outdoor units
Heating failure, fre- Bad connector contact Check connector
quent defrosting
No operating sound Coil failure
Check resistance between terminals
at applying power
Outdoor
EEV
Heating failure,
frozen outdoor heat
exchanger part
Low pressure error
or discharge temper-
ature error
EEV clogged
EEV clogged
Service necessary
Service necessary
When system fault occurs, the error code is displayed at indoor unit display or remote control display,
the trouble shooting guide is in the service manual
Installation Manual 79
Test Run
Sensor Checking Function
Sensor checking function judges whether the current temperature of indoor and outdoor unit sensors iNsotreig1)ht
or not. -3 indoor temperature sensors, 9 outdoor temperature sensors, 2 outdoor pressure sensors.
It is used for judging sensor abnormality. Note 2)
DIP Switch Settings
Start
- Setting1
(Refrigerant Auto Recharge)
3 minutes
past after power
reset
NO
- Setting2
(Refrigerant Quantity Auto
Decide)
YES
DIP switch set
- Setting3
(Indoor EEV malfunction
check - cooling)
- Setting4
Setting 1
Setting 2
Setting 3
Setting 4
Setting 5
NO
(Indoor EEV malfunction
check - heating)
Note 3)
- Setting5
(Integrated Test Run -
cooling)
Warning : Please reset Main PCB before starting this function
Press black button
for 2 seconds
Press black button for
5 seconds
Sensor Normal
NO
YES
Setting 1
Setting 2
Setting 3
Setting 4
Setting 5
Display Error
Press black button for 2 seconds
End
Indoor EEV
All DIP switches OFF and press black
button for 2 seconds
Refrigerant
Refrigerant
Auto decide
Inspection
C: Cooing
E: Cooling
Auto Recharge
Data Reset and Wait
Start Inspection of each Function
Note 1. Sensor Check Function is used along with refrigerant quantity auto check function and refrigerant auto recharge
function.
Note 2. Please check the sensor that is found abnormal.
Note 3. Each step is displayed on the Main PCB LED.
Note 4. Please refer to the sensor error descriptions on the next page.
WARNING
1. Please confirm if auto addressing function was executed. (Check the number of installed indoor units)
2. Error may occur when the sensor is normal according to the installed location and the temperature
conditions. When error occurs, please check each sensor and decide faultiness.
80
Outdoor Unit
Test Run
Sensor Check Error Code Display
In case error occurs during sensor checking process, error display is as shown below.
Following contents are displayed one after the other on the main PCB of master outdoor unit.
Indoor sensor error :
319
Outdoor sensor error :
309
* 5 number of errors is displayed
Displaying error content
continuously and repeatedly.
Displaying error content
■ Indoor unit error display
1.1st and 2nd number represents indoor unit number.
2. Last number represents sensor.
ex) Indoor unit No. 2 Pipe inlet temperature sensor
error
1: Pipe inlet temperature sensor
2: Pipe outlet temperature sensor
3: Air temperature sensor
■ Displaying outdoor unit error
1.1st and 2nd number represents error content(code).
2.Last number represents outdoor unit number.
ex) Outdoor Master Unit Liquid pipe temperature
sensor error
1 : Master
2 : Slave 1
3 : Slave 2
4 : Slave 3
* Indoor unit number follows auto addressing number.
(To check the LGMV Data)
ex) IDU No.2 Pipe inlet temperature sensor error and Master
ODU suction temperature sensor, Slave 3 high pressure
sensor error
No.
1
Sensor type
Outdoor Air Temperature
2
Heat Exchanger Temperature
Partition Heat Exchanger Temperature(Upper)
Partition Heat Exchanger Temperature(Low)
Liquid Pipe Temperature
3
4
5
6
SC pipe out
Suction Temperature
.......
7
8
Inverter Comp. Discharge Temperature
Constant Comp.1 Discharge Temperature
Constant Comp.2 Discharge Temperature
High Pressure
9
10
11
12
13
Caution
Low Pressure
IPM temperature
1. Up to 5 number of errors is displayed continuously and
repeatedly. In case 5 error occurs, again perform sensor
checking after solving errors.
2. IDU in which error occurred operates air circulation mode.
Installation Manual 81
Test Run
Refrigerant Auto Charging (Setting 1)
This function charges appropriate amount of refrigerant automatically through cycle operation.
It can be used when refrigerant amount Isn't certain because of SVC and leakage.
Note
Start
1. After installing the refrigerant charging
device
as shown below in figure,
Main PCB
SW01S
open the valve.
Wait for 3 min. after power reset
2. In case air temperature is out of guaranteed
temperature, it may end without performing
auto charging.
Main PCB
SW01B
SW02B
Set the Dip S/W.
3. Refrigerant Charging Time may change
according to the charging amount.
(Refrigerant Charging Time : about 1.5 min/lb)
Refrigerant Auto Changing : 1,2,7 ON
Main PCB
SW01V
Press the black button on main PCB.
( Press until ‘508’ is displayed )
Main PCB
SW01V
Press the black button on main PCB.
IDU runs with cooling mode In designated order.
Is it necessary to
charge refrigerant?
Yes
*1)
No
Press the black button
Refrigerant Auto
Charging Process
IDU and ODU are turned off when Auto Charging
is completed. Close the valve.
*2)
Main PCB
SW01V
Press the black button
Press the black button for 2 sec. after turning off
all of dip S/W.
Completed.
82
Outdoor Unit
Test Run
Liquid Pipe
Gas Pipe
manifold
Capillary Assembly
Procedure
1. Arrange manifold,capillary assembly, refrigerant vessel and scale
2. Connect manifold to the gas pipe service valve of ODU as shown in the figure.
3. Connect manifold and Capillary tube.
Use designated capillary assembly only.
If designated capillary assembly isn't used, the system may get damaged.
4. Connect capillary and refrigerant vessel.
5. Purge hose and manifold.
6. After
Is displayed, open the valve and charge the refrigerant
n Error contents about auto refrigerant charging function
1.
2.
3.
: Temperature Range Error (In case that IDU or ODU is out of range)
: Low Pressure Descent Error (In case the system runs at low pressure limit for over 10 minutes)
: Judging rapid refrigerant inflow ( In case the liquid refrigerant flows in because of not using designat-
ed Capillary Assembly)
4.
: Instability Error( In case the high/low pressure target doesn't get satisfied for some time
after the starting operation)
CAUTION
1. Guaranteed temperature range (Error will occur if temperature is out of range)
IDU : 20°C(68°F) ~ 32°C(90°F)
ODU : 0°C(32°F) ~ 43°C (77°F)
2. For refrigerant charging, use designated device only. (Capillary Assem Set)
3. Set the IDU wired remote controller temperature sensing mode as IDU
4. Be careful that IDU should not be thermo off.
Installation Manual 83
Test Run
Refrigerant Checking Function (Setting 2)
1. This function charges appropriate amount of refrigerant automatically through cycle operation.
2. This function judges refrigerant leakage and overcharging.
3. It can be used with refrigerant auto charging function.
DIP Switch Settings
Inspection Start
Warning : Please reset Main PCB before start-
ing this function
Press black button for 2 seconds
Display Error
YES
NO
NO
Proper Temperature
Thermo off indoor unit
YES
Decide Refrigerant Quantity
Display Error
Based on Refrigerant Quantity
Press black button for 2 seconds
End
Refrigerant
Gas/Liquid
Too much
Not enough
Refrigerant
Cannot tell
Quantity
pipe direct
connection
Refrigerant
Quantity
Normal
Press black button for 2 seconds
Data Reset and Wait
Indoor Unit OFF
Note
1. In case air temperature is out of guaranteed temperature, refrigerant checking function may end without performing
refrigerant checking. Use guaranteed temperature range only.
2. During the process of judging refrigerant amount, if the cycle isn't stable, refrigerant checking function may end
without performing refrigerant checking.
84
Outdoor Unit
Test Run
CAUTION
1. Guaranteed Temperature range(Error occurs out of guaranteed temperature range)
IDU : 20 ~ 35 °C
ODU : 0 ~ 43 °C
2. Set IDU wired remote controller temperature sensor setting as 'IDU'.
3. Make certain that IDU doesn't run with thermo off mode during operation.
[ Error contents about auto refrigerant charging function ]
1.
2.
: Temperature Range Error (In case that IDU or ODU is out of range)
: System Unstable Error (In case, After 45 min operating the system, it does not be stable)
How to Cope with Result of Refrigerant checking
1. If the temperature is not in guaranteed Temperature range, the system will not execute Refrigerant check-
ing and the system will be OFF.
2. Excess of Refrigerant(619)
After remove the 20% of calculated total refrigerant, recharge the refrigerant by using Refrigerant Auto
Charging Function.
3. Scarcity of Refrigerant(629)
Charge the refrigerant by using Refrigerant Auto Charging Function.
4. Impossible to Judge(639)
IF the system is not in order, check the other problem except refrigerant.
Installation Manual 85
Test Run
IDU EEV Abnormal Checking Function (Setting 3,4)
1. Operate system.
2. Check refrigerant amount of incoming to IDU throughout the IDU EEV.
3. Judge IDU temperature sensor.
4. Judge IDU EEV and IDU to ODU wiring.
Dip Switch Setting
Cooling
Heating
C : Cooling Mode
D : Heating Mode
Start
Caution
Please start these functions after
main PCB reset.
Press the black button for 2 sec
No
No
Temp. Condition
Yes
Error Display
Check IDU EEV Operation
Normal
Note 1
Error Display
Yes
End
Press the black button for 2 sec
Press the black button for 2 sec.
after turning off all of Dip switch.
Completed
Note 1
No. of IDU
IDU Fan Operation
CAUTION
1. Guaranteed Temperature range(Error occurs out of guaranteed temperature range)
1) Cooling mode : Indoor : 18~32°C, Outdoor : 10~43°C
2) Heating mode : Indoor : 18~33°C, Outdoor : -5~24°C
86
Outdoor Unit
Test Run
Integrated Test Running Function_Cooling Mode (Setting 5)
This function is checking process for normal operation of parts and system On operating system.
•
•
All processes carry out included refrigerant amount judge logic and check normal condition of parts on cooling mode.
This function check only normal condition of parts on heating mode.
• Saved data can check using LGMV.
Dip Switch Setting
Start
Press the black button for 2 sec
Caution
Please start these functions after
main PCB reset.
All IDU operation on
Cooling mode
Temp. Condition
Yes
Error Display
Thermo off
IDU judge
No
Yes
Error Display
Refrigerant amount judge
during all IDU operation
data on Test Runing(15min)
Press the black button for 2 sec
1 IDU operation
Note 1
End
1 IDU operation data
(10min)
Press the black button for 2 sec.
after turning off all of Dip switch.
Completed
Note
1. Judge the normal condition refer to report of Test Running.
Installation Manual 87
Test Run
Night Low Noise Function
In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at
night which has low cooling load.
Max. RPM setting method
Master ODU
Dip S/W No.12+14 ON
SW01B
Master ODU
Main PCB Power Reset
SW01S
Note 1)
SW01V
Setting the Fan Max. RPM
SW02V
Setting Complete
Example of Max. RPM Setting
Fan Max. RPM : Step 1
- Night silent operation start
fi 8 hours after max. ODU temp. sensing, the fan max. RPM is operated setting RPM.
- Night silent operation end
fi 9 hours after Night silent operation is started, the function should be stopped automatically.
CAUTION
1. Request installer to set the function during installation.
2. In case the function is not used, set the dip S/W OFF and reset the power.
3. If ODU RPM changes, cooling capacity may go down.
[Note]
1. Select appropriate RPM referencing noise table.
RPM / Time Settings
Noise
Capacity
29~41kW
Noise(dB)
58
Capacity
Judgment Operation
46~58kW
16~23kW
Cooling Only
Step
Cooling Only 16~23kW 29~41kW
46~58kW Time(Hr) Time(Hr)
Fan Maximum RPM
Step
Standard
56
53
50
47
62
59
56
53
1
8
6.5
5
9
55
2
3
4
5
6
7
8
9
10.5
12
730
620
510
790
680
620
900
800
780
52
49
8
9
6.5
5
10.5
12
8
9
6.5
5
10.5
12
88
Outdoor Unit
Test Run
Vacuum Mode
This function is used for creating vacuum in the system after compressor replacement, ODU parts replace-
ment or IDU addition/replacement.
Vacuum mode setting method
ODU power reset
Vacuum mode cancellation method
Main PCB
SW01S
Master main PCB DIP switch OFF( No.11,14)
Main PCB
SW02B
Power reset
Master main PCB DIP switch ON ( No.11,14)
Press the black button Main PCB (5 sec.)
Vacuum mode cancellation
Main PCB
SW01V
Vacuum mode setting
ODU V/V OPEN
Main EEV, SC EEV OPEN
IDU EEV OPEN
Caution
ODU operation stops during vacuum mode. Compressor can't operate.
Static pressure compensation mode
This function secures the air flow rate of ODU, in case static pressure has been applied like using duct at fan
discharge of ODU.
n Static pressure compensation dip S/W setting method
High static pressure mode : Master ODU Main PCB SW02B NO.13 Dip S/W
Static pressure compensation mode setting
method
Static pressure compensation mode cancellation
method
DIP switch setting
DIP switch OFF
Power Reset
High static pressure:No. 13
Power Reset
Static pressure compensation mode is cancelled
Static pressure compensation mode is set
Installation Manual 89
Test Run
Self-Diagnosis Function
Error Indicator
• This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
• Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LEDꢀof
outdoor unit control board as shown in the table.
•ꢁ If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
1st,2nd LED of 7-segment indicates error number, 3rd LED indicates unit number.
Ex) 211 : No.21 error of master unit
213 : No.21 error of slave2
011 ’ 051 : No.105 error of master unit
h Refer to the DX-Venitilation manual for DX-Venitilation error code
Display
Title
Cause of Error
0
0
0
0
0
0
0
1
1
1
2
3
4
5
6
9
0
7
-
-
Air temperature sensor of indoor unit
Air temperature sensor of indoor unit is open or short
Inlet pipe temperature sensor of indoor unit Inlet pipe temperature sensor of indoor unit is open or short
Communication error : wired remote con-
Failing to receive wired remote controller signal in indoor
unit PCB
-
troller ÷ indoor unit
-
Drain pump
Malfunction of drain pump
Communication error : outdoor unit ÷
-
Failing to receive outdoor unit signal in indoor unit PCB
indoor unit
Outlet pipe temperature sensor of indoor
unit
Outlet pipe temperature sensor of indoor unit is open or
short
-
In case when the serial number marked on EEPROM of
Indoor unit is 0 or FFFFFF
-
Indoor EEPROM Error
Disconnecting the fan motor connector/Failure of indoor
fan motor lock
-
Poor fan motor operation
-
Inlet Air temperature sensor of FAU
Air temperature sensor of indoor unit is open or short
Master Outdoor Unit Inverter Compressor Drive IPM Fault
Slave1 Outdoor Unit Inverter Compressor Drive IPM Fault
Slave2 Outdoor Unit Inverter Compressor Drive IPM Fault
Slave3 Outdoor Unit Inverter Compressor Drive IPM Fault
Master Outdoor Unit Inverter Compressor
IPM Fault
1
2
3
4
1
2
3
4
Slave1 Outdoor Unit Inverter Compressor
IPM Fault
2
2
1
2
Slave2 Outdoor Unit Inverter Compressor
IPM Fault
Slave3 Outdoor Unit Inverter Compressor
IPM Fault
Inverter Board Input Over Current(RMS) of Master Outdoor Unit Inverter Board Input Current excess
Master Outdoor Unit
Inverter Board Input Over Current(RMS) of Slave1 Outdoor Unit Inverter Board Input Current excess
Slave1 Outdoor Unit (RMS)
Inverter Board Input Over Current(RMS) of Slave2 Outdoor Unit Inverter Board Input Current excess
Slave2 Outdoor Unit (RMS)
Inverter Board Input Over Current(RMS) of Slave3 Outdoor Unit Inverter Board Input Current excess
Slave3 Outdoor Unit (RMS)
(RMS)
90
Outdoor Unit
Test Run
Display
Title
Cause of Error
DC charging is not performed at Master Outdoor Unit
Master Outdoor Unit Inverter
1
after starting relay turn on.
Compressor DC link Low Voltage
DC charging is not performed at Slave1 Outdoor Unit
after starting relay turn on.
Slave1 Outdoor Unit Inverter
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
Compressor DC link Low Voltage
2
3
DC charging is not performed at Slave2 Outdoor Unit
Slave2 Outdoor Unit Inverter
after starting relay turn on.
Compressor DC link Low Voltage
DC charging is not performed at Slave3 Outdoor Unit
after starting relay turn on.
Slave3 Outdoor Unit Inverter
Compressor DC link Low Voltage
Master Outdoor Unit High
System is turned off by Master Outdoor Unit high pres-
Pressure Switch
sure switch.
Slave1 Outdoor Unit High
Pressure Switch
System is turned off by slave1 Outdoor Unit high pres-
sure switch.
2
2
2
4
5
6
Slave2 Outdoor Unit High
System is turned off by slave2 Outdoor Unit high pres-
Pressure Switch
sure switch.
Slave3 Outdoor Unit High
Pressure Switch
System is turned off by slave3 Outdoor Unit high pres-
sure switch.
Master Outdoor Unit Input Voltage
Master Outdoor Unit input voltage is over 487V or
High/ Low Voltage
below 270V
Slave1 Outdoor Unit Input Voltage
High/ Low Voltage
Slave1 Outdoor Unit input voltage is over 487V or
below 270V
Slave2 Outdoor Unit Input Voltage
Slave2 Outdoor Unit input voltage is over 487V or
High/ Low Voltage
below 270V
Slave3 Outdoor Unit Input Voltage
High/ Low Voltage
Slave3 Outdoor Unit input voltage is over 487V or
below 270V
Master Outdoor Unit Inverter
The First Start Failure by Master Outdoor Unit Inverter
Compressor Start Failure
Compressor Abnormality
Slave1 Outdoor Unit Inverter
Compressor Start Failure
The First Start Failure by Slave1 Outdoor Unit Inverter
Compressor Abnormality
Slave2 Outdoor Unit Inverter
The First Start Failure by Slave2 Outdoor Unit Inverter
Compressor Start Failure
Compressor Abnormality
Slave3 Outdoor Unit Inverter
Compressor Start Failure
The First Start Failure by Slave3 Outdoor Unit Inverter
Compressor Abnormality
Master Outdoor Unit Inverter DC
link High Voltage
System is turned off by Master Outdoor Unit DC
Voltage Over Charging
1
2
3
4
1
2
3
4
Slave1 Outdoor Unit Inverter DC
System is turned off by Slave1 Outdoor Unit DC
link High Voltage
Voltage Over Charging
2
2
8
9
Slave2 Outdoor Unit Inverter DC
link High Voltage
System is turned off by Slave2 Outdoor Unit DC
Voltage Over Charging
Slave3 Outdoor Unit Inverter DC
System is turned off by Slave3 Outdoor Unit DC
link High Voltage
Voltage Over Charging
Master Outdoor Unit Inverter Compressor Fault OR
Drive Fault
Master Outdoor Unit Inverter
Compressor Over Current
Slave1 Outdoor Unit Inverter Compressor Fault OR
Slave1 Outdoor Unit Inverter
Drive Fault
Compressor Over Current
Slave2 Outdoor Unit Inverter Compressor Fault OR
Drive Fault
Slave2 Outdoor Unit Inverter
Compressor Over Current
Slave3 Outdoor Unit Inverter Compressor Fault OR
Slave3 Outdoor Unit Inverter
Drive Fault
Compressor Over Current
Installation Manual 91
Test Run
Display
Title
Cause of Error
Master Outdoor Unit Constant Speed
System is turned off by Master Outdoor Uunit Constant Speed
1
Compressor2 High Discharge Temperature
Compressor2 High Discharge Temperature
Slave1 Outdoor Unit Constant Speed
System is turned off by Slave1 Outdoor Unit Constant Speed
Compressor2 High Discharge Temperature
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
Compressor2 High Discharge Temperature
3
0
2
3
Slave2 Outdoor Unit Constant Speed
System is turned off by Slave2 Outdoor Unit Constant Speed
Compressor2 High Discharge Temperature
Compressor2 High Discharge Temperature
Slave3 Outdoor Unit Constant Speed
System is turned off by Slave3 Outdoor Unit Constant Speed
Compressor2 High Discharge Temperature
Compressor2 High Discharge Temperature
Master Outdoor Unit Inverter Compressor
System is turned off by Master Outdoor Unit Inverter Compressor
High Discharge Temperature
High Discharge Temperature
Slave1 Outdoor Unit Inverter Compressor
High Discharge Temperature
System is turned off by Slave1 Outdoor Unit Inverter Compressor
High Discharge Temperature
3
3
Slave2 Outdoor Unit Inverter Compressor
System is turned off by Slave2 Outdoor Unit Inverter Compressor
Discharge High Temperature
High Discharge Temperature
Slave3 Outdoor Unit Inverter Compressor
High Discharge Temperature
System is turned off by Slave3 Outdoor Unit Inverter Compressor
High Discharge Temperature
Master Outdoor Unit Constant Speed
System is turned off by Master Outdoor Uunit Constant Speed
Compressor1 High Discharge Temperature
Compressor1 High Discharge Temperature
Slave1 Outdoor Unit Constant Speed
System is turned off by Slave1 Outdoor Unit Constant Speed
Compressor1 High Discharge Temperature
Compressor1 High Discharge Temperature
Slave2 Outdoor Unit Constant Speed
System is turned off by Slave2 Outdoor Unit Constant Speed
Compressor1 High Discharge Temperature
Compressor1 High Discharge Temperature
Slave3 Outdoor Unit Constant Speed
System is turned off by Slave3 Outdoor Unit Constant Speed
Compressor1 High Discharge Temperature
Compressor1 High Discharge Temperature
High Pressure of Master Outdoor Unit
High Pressure of Slave1 Outdoor Unit
High Pressure of Slave2 Outdoor Unit
High Pressure of Slave3 Outdoor Unit
Low Pressure of Master Outdoor Unit
Low Pressure of Slave1 Outdoor Unit
Low Pressure of Slave2 Outdoor Unit
Low Pressure of Slave3 Outdoor Unit
System is turned off by excessive increase of high pressure of
Master Outdoor Unit
System is turned off by excessive increase of high pressure of
Slave1 Outdoor Unit
3
3
4
5
System is turned off by excessive increase of high pressure of
Slave2 Outdoor Unit
System is turned off by excessive increase of high pressure of
Slave3 Outdoor Unit
System is turned off by excessive decrease of low pressure of
Master Outdoor Unit
System is turned off by excessive decrease of low pressure of
Slave1 Outdoor Unit
System is turned off by excessive decrease of low pressure of
Slave2 Outdoor Unit
System is turned off by excessive decrease of low pressure of
Slave3 Outdoor Unit
Master Outdoor Unit Low Condensing
Ratio Limited
Master Outdoor Unit stayed under low condensing limit for 3 minutes
Slave1 Outdoor Unit stayed under low condensing limit for 3 minutes
Slave2 Outdoor Unit stayed under low condensing limit for 3 minutes
Slave3 Outdoor Unit stayed under low condensing limit for 3 minutes
1
2
3
4
Slave1 Outdoor Unit Low Condensing
Ratio Limited
3
6
Slave2 Outdoor Unit Low Condensing
Ratio Limited
Slave3 Outdoor Unit Low Condensing
Ratio Limited
92
Outdoor Unit
Test Run
Display
Title
Cause of Error
Master Outdoor Unit Inverter Compressor CT Sensor
Master Outdoor Unit Inverter
1
Compressor CT Sensor Fault
open or short
Slave1 Outdoor Unit Inverter
Compressor CT Sensor Fault
Slave1 Outdoor Unit Inverter Compressor CT Sensor
open or short
2
3
Slave2 Outdoor Unit Inverter
Slave2 Outdoor Unit Inverter Compressor CT Sensor
4
4
0
1
Compressor CT Sensor Fault
open or short
Slave3 Outdoor Unit Inverter
Compressor CT Sensor Fault
Slave3 Outdoor Unit Inverter Compressor CT Sensor
open or short
4
1
Master Outdoor Unit Inverter
Compressor Discharge
Master Outdoor Unit Inverter Compressor Discharge
Temperature Sensor open or short
Temperature Sensor Fault
Slave1 Outdoor Unit Inverter
Slave1 Outdoor Unit Inverter Compressor Discharge
Temperature Sensor open or short
2
3
4
Compressor Discharge
Temperature Sensor Fault
Slave2 Outdoor Unit Inverter
Slave2 Outdoor Unit Inverter Compressor Discharge
Temperature Sensor open or short
Compressor Discharge
Temperature Sensor Fault
Slave3 Outdoor Unit Inverter
Slave3 Outdoor Unit Inverter Compressor Discharge
Temperature Sensor open or short
Compressor Discharge
Temperature Sensor Fault
Master Outdoor Unit Low Pressure
Master Outdoor Unit Low Pressure Sensor open or
short
1
2
3
4
1
2
3
4
1
2
3
4
Sensor Fault
Slave1 Outdoor Unit Low Pressure
Sensor Fault
Slave1 Outdoor Unit Low Pressure Sensor open or
short
4
2
Slave2 Outdoor Unit Low Pressure
Slave2 Outdoor Unit Low Pressure Sensor open or
short
Sensor Fault
Slave3 Outdoor Unit Low Pressure
Sensor Fault
Slave3 Outdoor Unit Low Pressure Sensor open or
short
Master Outdoor Unit High
Master Outdoor Unit High Pressure Sensor open or
short
Pressure Sensor Fault
Slave1 Outdoor Unit High
Pressure Sensor Fault
Slave1 Outdoor Unit High Pressure Sensor open or
short
4
4
3
4
Slave2 Outdoor Unit High
Slave2 Outdoor Unit High Pressure Sensor open or
short
Pressure Sensor Fault
Slave3 Outdoor Unit High
Pressure Sensor Fault
Slave3 Outdoor Unit High Pressure Sensor open or
short
Master Outdoor Unit Air
Master Outdoor Unit Air Temperature Sensor open or
short
Temperature Sensor Fault
Slave1 Outdoor Unit Air
Slave1 Outdoor Unit Air Temperature Sensor open or
Temperature Sensor Fault
short
Slave2 Outdoor Unit Air
Slave2 Outdoor Unit Air Temperature Sensor open or
short
Temperature Sensor Fault
Slave3 Outdoor Unit Air
Slave3 Outdoor Unit Air Temperature Sensor open or
Temperature Sensor Fault
short
Installation Manual 93
Test Run
Display
Title
Cause of Error
Master Outdoor Unit Heat Exchanger Temperature
Master Outdoor Unit Heat
Exchanger Temperature Sensor
(Front side) Fault
1
Sensor(Front side) open or short
Slave1 Outdoor Unit Heat Exchanger Temperature
Sensor (Front side) open or short
Slave1 Outdoor Unit Heat
Exchanger Temperature Sensor
(Front side) Fault
Slave2 Outdoor Unit Heat
Exchanger Temperature Sensor
(Front side) Fault
Slave3 Outdoor Unit Heat
Exchanger Temperature Sensor
(Front side) Fault
2
3
4
4
5
6
Slave2 Outdoor Unit Heat Exchanger Temperature
Sensor(Front side) open or short
Slave3 Outdoor Unit Heat Exchanger Temperature
Sensor(Front side) open or short
Master Outdoor Unit Suction Temperature Sensor
open or short
Master Outdoor Unit Suction
1
2
3
4
Temperature Sensor Fault
Slave1 Outdoor Unit Suction Temperature Sensor
Slave1 Outdoor Unit Suction
Temperature Sensor Fault
open or short
4
4
Slave2 Outdoor Unit Suction Temperature Sensor
open or short
Slave2 Outdoor Unit Suction
Temperature Sensor Fault
Slave3 Outdoor Unit Suction Temperature Sensor
Slave3 Outdoor Unit Suction
Temperature Sensor Fault
open or short
Master Outdoor Unit Constant Speed Compressor1
Discharge Temperature Sensor open or short
Master Outdoor Unit Constant
Speed Compressor1 Discharge
Temperature Sensor Fault
Slave1 Outdoor Unit Constant
Speed Compressor1 Discharge
Temperature Sensor Fault
Slave2 Outdoor Unit Constant
Speed Compressor1 Discharge
Temperature Sensor Fault
Slave3 Outdoor Unit Constant
Speed Compressor1 Discharge
Temperature Sensor Fault
1
2
3
4
1
2
3
4
Slave1 Outdoor Unit Constant Speed Compressor1
Discharge Temperature Sensor open or short
7
Slave2 Outdoor Unit Constant Speed Compressor1
Discharge Temperature Sensor open or short
Slave3 Outdoor Unit Constant Speed Compressor1
Discharge Temperature Sensor open or short
Master Outdoor Unit Constant
Speed Compressor2 Discharge
Temperature Sensor Fault
Slave1 Outdoor Unit Constant
Speed Compressor2 Discharge
Temperature Sensor Fault
Slave2 Outdoor Unit Constant
Speed Compressor2 Discharge
Temperature Sensor Fault
Slave3 Outdoor Unit Constant
Speed Compressor2 Discharge
Temperature Sensor Fault
Master Outdoor Unit Constant Speed Compressor 2
Discharge Temperature Sensor open or short
Slave1 Outdoor Unit Constant Speed Compressor 2
Discharge Temperature Sensor open or short
4
8
Slave2 Outdoor Unit Constant Speed Compressor 2
Discharge Temperature Sensor open or short
Slave3 Outdoor Unit Constant Speed Compressor 2
Discharge Temperature Sensor open or short
94
Outdoor Unit
Test Run
Display
Title
Cause of Error
Master Outdoor Unit IPM Temperature Sensor
Master Outdoor Unit Faulty IPM
1
short/open
Temperature Sensor
Slave1 Outdoor Unit IPM Temperature Sensor
short/open
Slave1 Outdoor Unit Faulty IPM
Temperature Sensor
2
3
4
1
2
3
4
1
4
9
Slave2 Outdoor Unit IPM Temperature Sensor
Slave2 Outdoor Unit Faulty IPM
short/open
Temperature Sensor
Slave3 Outdoor Unit IPM Temperature Sensor
short/open
Slave3 Outdoor Unit Faulty IPM
Temperature Sensor
Omitting connection of Master outdoor unit
Omitting connection of Slave1 Outdoor Unit
Omitting connection of Slave2 Outdoor Unit
Omitting connection of Slave3 Outdoor Unit
Omitting connection of R, S, T
power of Master Outdoor Unit
Omitting connection of R, S, T
power of Slave1 Outdoor Unit
5
5
0
1
Omitting connection of R, S, T
power of Slave2 Outdoor Unit
Omitting connection of R, S, T
power of Slave3 Outdoor Unit
Excessive capacity of indoor units
Excessive connection of indoor units compared to
capacity of Outdoor Unit
Failing to receive inverter signal at main PCB of Master
Transmission error : inverter PCB
1
2
Outdoor Unit
’ Main PCB
Failing to receive inverter signal at main PCB of Slave1
Outdoor Unit
Transmission error : inverter PCB
’ Main PCB
5
5
2
3
Failing to receive inverter signal at main PCB of Slave2
Transmission error : inverter PCB
3
4
1
Outdoor Unit
’ Main PCB
Failing to receive inverter signal at main PCB of Slave3
Outdoor Unit
Transmission error : inverter PCB
’ Main PCB
Failing to receive indoor unit signal at main PCB of
Transmission error : indoor unit ’
Outdoor Unit .
main PCB of Outdoor Unit
Reverse connection or omitting connection of R, S, T
power of Master Outdoor Unit
Reverse connection of R, S, T
1
2
3
4
power of Master Outdoor Unit
Reverse connection or omitting connection of R, S, T
Reverse connection of R, S, T
power of Slave1 Outdoor Unit
power of Slave1 Outdoor Unit
5
4
Reverse connection or omitting connection of R, S, T
power of Slave2 Outdoor Unit
Reverse connection of R, S, T
power of Slave2 Outdoor Unit
Reverse connection or omitting connection of R, S, T
Reverse connection of R, S, T
power of Slave3 Outdoor Unit
power of Slave3 Outdoor Unit
Master Outdoor Unit Controller part cannot receive
inverter control signals (usually happens after on-
boarding)
Slave1 Outdoor Unit Controller part cannot receive
inverter control signals (usually happens after on-
boarding)
Slave2 Outdoor Unit Controller part cannot receive
inverter control signals (usually happens after on-
boarding)
Master Outdoor Unit
Communication Error with Inverter
Controller
Slave1 Outdoor Unit
Communication Error with Inverter
Controller
Slave2 Outdoor Unit
Communication Error with Inverter
Controller
1
2
3
5
5
7
9
Slave3 Outdoor Unit Controller part cannot receive
inverter control signals (usually happens after on-
boarding)
Slave3 Outdoor Unit
Communication Error with Inverter
Controller
4
1
Mixing Installation of Old Sub Outdoor Unit and New
Mixing Installation of Sub Outdoor
Slave Outdoor Unit
Unit
Installation Manual 95
Test Run
Display
Title
Cause of Error
Access Error of Inverter PCB of Master Outdoor Unit
Inverter PCB EEPROM Error of
1
Master Outdoor Unit
Inverter PCB EEPROM Error of
Slave1 Unit
Access Error of Inverter PCB of Slave1 Outdoor Unit
Access Error of Inverter PCB of Slave2 Outdoor Unit
Access Error of Inverter PCB of Slave3 Outdoor Unit
2
3
4
6
0
7
Inverter PCB EEPROM Error of
Slave2 Unit
Inverter PCB EEPROM Error of
Slave3 Unit
Master Outdoor Unit Fan Lock
Slave1 Outdoor Unit Fan Lock
Slave2 Outdoor Unit Fan Lock
Slave3 Outdoor Unit Fan Lock
1
2
3
4
Restriction of Master Outdoor Unit
Restriction of Slave1 Outdoor Unit
Restriction of Slave2 Outdoor Unit
Restriction of Slave3 Outdoor Unit
6
6
Constant1 CT Sensor open or short of Master Outdoor
Constant1 CT Sensor Error of
1
2
3
4
1
2
3
Unit
Master Outdoor Unit
Constant1 CT Sensor open or short of Slave1 Outdoor
Unit
Constant1 CT Sensor Error of
Slave1 Outdoor Unit
9
Constant1 CT Sensor open or short of Slave2 Outdoor
Constant1 CT Sensor Error of
Unit
Slave2 Outdoor Unit
Constant1 CT Sensor open or short of Slave3 Outdoor
Unit
Constant1 CT Sensor Error of
Slave3 Outdoor Unit
Constant2 CT Sensor open or short of Master Outdoor
Constant2 CT Sensor Error of
Unit
Master Outdoor Unit
Constant2 CT Sensor open or short of Slave1 Outdoor
Unit
Constant2 CT Sensor Error of
Slave1 Outdoor Unit
7
7
0
3
Constant2 CT Sensor open or short of Slave2 Outdoor
Constant2 CT Sensor Error of
Unit
Slave2 Outdoor Unit
Constant2 CT Sensor open or short of Slave3 Outdoor
Unit
Constant2 CT Sensor Error of
Slave3 Outdoor Unit
4
1
Instant Over Current(Peak) of
Instant Over Current(Peak) of Master Outdoor Unit
Master Outdoor Unit PFC
PFC
Instant Over Current(Peak) of
Slave1 Outdoor Unit PFC
Instant Over Current(Peak) of Slave1 Outdoor Unit
PFC
2
3
4
Instant Over Current(Peak) of
Instant Over Current(Peak) of Slave2 Outdoor Unit
Slave2 Outdoor Unit PFC
PFC
Instant Over Current(Peak) of
Slave3 Outdoor Unit PFC
Instant Over Current(Peak) of Slave3 Outdoor Unit
PFC
Master Outdoor Unit Fan CT
Master Outdoor Unit Fan CT Sensor open or short
Slave1 Outdoor Unit Fan CT Sensor open or short
Slave2 Outdoor Unit Fan CT Sensor open or short
Slave3 Outdoor Unit Fan CT Sensor open or short
1
2
3
4
Sensor Error
Slave1 Outdoor Unit Fan CT
Sensor Error
7
5
Slave2 Outdoor Unit Fan CT
Sensor Error
Slave3 Outdoor Unit Fan CT
Sensor Error
96
Outdoor Unit
Test Run
Display
Title
Cause of Error
Master Outdoor Unit Fan DC Link Master Outdoor Unit Fan DC Link High Voltage Error
1
High Voltage Error
Slave1 Outdoor Unit Fan DC Link Slave1 Outdoor Unit Fan DC Link High Voltage Error
High Voltage Error
2
3
7
7
6
7
Slave2 Outdoor Unit Fan DC Link Slave2 Outdoor Unit Fan DC Link High Voltage Error
High Voltage Error
Slave3 Outdoor Unit Fan DC Link Slave3 Outdoor Unit Fan DC Link High Voltage Error
High Voltage Error
4
1
Master Outdoor Unit Fan Current is over 5A
Slave1 Outdoor Unit Fan is over 5A
Slave2 Outdoor Unit Fan is over 5A
Slave3 Outdoor Unit Fan is over 5A
Master Outdoor Unit Fan Over
Current Error
Slave1 Outdoor Unit Fan Over
Current Error
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
Slave2 Outdoor Unit Fan Over
Current Error
Slave3 Outdoor Unit Fan Over
Current Error
Master Outdoor Unit Fan Start
Master Outdoor Unit Fan First Position Sensing Failure
Slave1 Outdoor Unit Fan First Position Sensing Failure
Slave2 Outdoor Unit Fan First Position Sensing Failure
Slave3 Outdoor Unit Fan First Position Sensing Failure
Failure Error
Slave1 Outdoor Unit Fan Start
Failure Error
7
8
9
6
Slave2 Outdoor Unit Fan Start
Failure Error
Slave3 Outdoor Unit Fan Start
Failure Error
Master Outdoor Unit Main PCB
Communication Fail Between Master Outdoor Unit
Main MICOM and EEPROM or omitting EEPROM
EEPROM Error
Slave1 Outdoor Unit Main PCB
EEPROM Error
Communication Fail Between Slave1 Outdoor Unit
Main MICOM and EEPROM or omitting EEPROM
Slave2 Outdoor Unit Main PCB
Communication Fail Between Slave2 Outdoor Unit
Main MICOM and EEPROM or omitting EEPROM
EEPROM Error
Slave3 Outdoor Unit Main PCB
EEPROM Error
Communication Fail Between Slave3 Outdoor Unit
Main MICOM and EEPROM or omitting EEPROM
Master Outdoor Unit Fan PCB
Communication Fail Between Master Outdoor Unit Fan
MICOM and EEPROM or omitting EEPROM
EEPROM Error
Slave1 Outdoor Unit Fan PCB
EEPROM Error
Communication Fail Between Slave1 Outdoor Unit Fan
MICOM and EEPROM or omitting EEPROM
8
7
Slave2 Outdoor Unit Fan PCB
Communication Fail Between Slave2 Outdoor Unit Fan
MICOM and EEPROM or omitting EEPROM
EEPROM Error
Slave3 Outdoor Unit Fan PCB
EEPROM Error
Communication Fail Between Slave3 Outdoor Unit Fan
MICOM and EEPROM or omitting EEPROM
Installation Manual 97
Test Run
Display
Title
Cause of Error
Failing to receive Slave Unit signal at main PCB of
Communication Error Between
Master Outdoor Unit and Other
Outdoor Unit
Communication Error Between
Slave1 Outdoor Unit and Other
Outdoor Unit
Communication Error Between
Slave2 Outdoor Unit and Other
Outdoor Unit
Communication Error Between
Slave3 Outdoor Unit and Other
Outdoor Unit
1
2
3
4
Master Outdoor Unit
Failing to receive master and other Slave Unit signal at
main PCB of Slave1 Outdoor Unit
1
0
4
Failing to receive master and other Slave Unit signal at
main PCB of Slave2 Outdoor Unit
Failing to receive master and other Slave Unit signal at
main PCB of Slave3 Outdoor Unit
Failing to receive fan signal at main PCB of master
unit.
Master Outdoor Unit Fan PCB
1
Communication Error
Failing to receive fan signal at main PCB of Slave1
Slave1 Outdoor Unit Fan PCB
Communication Error
2
3
4
1
2
unit.
1
0
5
Failing to receive fan signal at main PCB of Slave2
unit.
Slave2 Outdoor Unit Fan PCB
Communication Error
Failing to receive fan signal at main PCB of Slave3
Slave3 Outdoor Unit Fan PCB
Communication Error
unit.
Instant Over Current at Master Outdoor Unit Fan IPM
Instant Over Current at Slave1 Outdoor Unit Fan IPM
Instant Over Current at Slave2 Outdoor Unit Fan IPM
Instant Over Current at Slave3 Outdoor Unit Fan IPM
Master Outdoor Unit FAN IPM
Fault Error
Slave1 Outdoor Unit FAN IPM
Fault Error
1
0
6
Slave2 Outdoor Unit FAN IPM
3
4
1
2
3
4
1
2
3
4
Fault Error
Slave3 Outdoor Unit FAN IPM
Fault Error
Master Outdoor Unit Fan DC Link Input Voltage is
under 380V
Master Outdoor Unit Fan DC Link
Low Voltage Error
Slave1 Outdoor Unit Fan DC Link Input Voltage is
Slave1 Outdoor Unit Fan DC Link
Low Voltage Error
under 380V
1
1
0
1
7
3
Slave2 Outdoor Unit Fan DC Link Input Voltage is
under 380V
Slave2 Outdoor Unit Fan DC Link
Low Voltage Error
Slave3 Outdoor Uni Fan DC Link Input Voltage is
Slave3 Outdoor Unit Fan DC Link
Low Voltage Error
under 380V
Liquid pipe temperature sensor of Master Outdoor Unit
is open or short
Master Outdoor Unit Liquid pipe
Temperature Sensor Error
Liquid pipe temperature sensor of slave1 Outdoor Unit
Slave1 Outdoor Unit Liquid pipe
Temperature Sensor Error
is open or short
Liquid pipe temperature sensor of slave2 Outdoor Unit
is open or short
Slave2 Outdoor Unit Liquid pipe
Temperature Sensor Error
Liquid pipe temperature sensor of slave3 Outdoor Unit
Slave3 Outdoor Unit Liquid pipe
Temperature Sensor Error
is open or short
98
Outdoor Unit
Test Run
Display
Title
Cause of Error
Master Outdoor Unit Subcooling Outlet Temperature
Master Outdoor Unit Subcooling
1
2
3
4
1
2
3
4
1
2
3
4
Outlet Temperature Sensor Error
Slave1 Outdoor Unit Subcooling
Outlet Temperature Sensor Error
Sensor open or short
Slave1 Outdoor Unit Subcooling Outlet Temperature
Sensor open or short
Slave2 Outdoor Unit Subcooling Outlet Temperature
1
1
1
1
5
5
5
3
4
Slave2 Outdoor Unit Subcooling
Outlet Temperature Sensor Error
Sensor open or short
Slave3 Outdoor Unit Subcooling
Outlet Temperature Sensor Error
Slave3 Outdoor Unit Subcooling Outlet Temperature
Sensor open or short
Master Outdoor Unit upper part temperature sensor
Master upper part heat exchanger
temperature sensor error
open/short
Slave1 upper part heat exchanger
temperature sensor error
Slave1 Outdoor Unit upper part temperature sensor
open/short
Slave2 Outdoor Unit upper part temperature sensor
Slave2 upper part heat exchanger
temperature sensor error
open/short
Slave3 upper part heat exchanger
temperature sensor error
Slave3 Outdoor Unit upper part temperature sensor
open/short
Master Outdoor Unit lower part temperature sensor
Master lower part heat exchanger
temperature sensor error
open/short
Slave1 lower part heat exchanger
temperature sensor error
Slave1 Outdoor Unit lower part temperature sensor
open/short
Slave2 Outdoor Unit lower part temperature sensor
Slave2 lower part heat exchanger
temperature sensor error
open/short
Slave3 lower part heat exchanger
temperature sensor error
Slave3 Outdoor Unit lower part temperature sensor
open/short
Master Outdoor Unit Constant
Speed Compressor Fault
Comp locking, Check Valve leakage, comp dielectric
break down at Master Outdoor Unit
1
2
3
4
Slave1 Outdoor Unit Constant
Comp locking, Check Valve leakage, comp dielectric at
Speed Compressor Fault
Slave1 Outdoor Unit
1
1
1
7
7
8
3
4
2
Slave2 Outdoor Unit Constant
Speed Compressor Fault
Comp locking, Check Valve leakage, comp dielectric at
Slave2 Outdoor Unit
Slave3 Outdoor Unit Constant
Comp locking, Check Valve leakage, comp dielectric at
Speed Compressor Fault
Slave3 Outdoor Unit
Master outdoor unit rated speed 2
condenser over-current
Master Outdoor Unit rated speed 2 condenser burned /
locked or fault by over-current
1
2
3
4
1
2
3
4
Slave1 outdoor unit rated speed 2
Slave1 Outdoor Unit rated speed 2 condenser burned /
condenser over-current
locked or fault by over-current
Slave2 outdoor unit rated speed 2
condenser over-current
Slave2 Outdoor Unit rated speed 2 condenser burned /
locked or fault by over-current
Slave3 outdoor unit rated speed 2
Slave3 Outdoor Unit rated speed 2 condenser burned /
condenser over-current
locked or fault by over-current
Master outdoor unit Main Board Main-
Sub Micom communication error
Master Outdoor Unit Main Board Main-Sub Micom
communication failed
Slave1 outdoor unit Main Board Main-
Slave1 Outdoor Unit Main Board Main-Sub Micom
Sub Micom communication error
communication failed
Slave2 outdoor unit Main Board Main-
Sub Micom communication error
Slave2 Outdoor Unit Main Board Main-Sub Micom
communication failed
Slave3 outdoor unit Main Board Main-
Slave3 Outdoor Unit Main Board Main-Sub Micom
Sub Micom communication error
communication failed
Installation Manual 99
Test Run
Display
Title
Cause of Error
Excessive increase of Master
Outdoor Unit Fan PCB Heat Sink
Temperature
Excessive increase of Slave1
Outdoor Unit Fan PCB Heat Sink
Temperature
Excessive increase of Slave2
Outdoor Unit Fan PCB Heat Sink
Temperature
Excessive increase of Slave3
Outdoor Unit Fan PCB Heat Sink
Temperature
Master Outdoor Unit Fan Inverter PCB Temperature is
Over 95°C
1
2
3
4
1
Slave1 Outdoor Unit Fan Inverter PCB Temperature is
Over 95°C
1
9 3
Slave2 Outdoor Unit Fan Inverter PCB Temperature is
Over 95°C
Slave3 Outdoor Unit Fan Inverter PCB Temperature is
Over 95°C
Master Outdoor Unit Fan PCB
Heat Sink Temperature Sensor
Error
Master Outdoor Unit Fan PCB Heat Sink Temperature
Sensor open or short
Slave1 Outdoor Unit Fan PCB
Heat Sink Temperature Sensor
Error
Slave2 Outdoor Unit Fan PCB
Heat Sink Temperature Sensor
Error
Slave3 Outdoor Unit Fan PCB
Heat Sink Temperature Sensor
Error
Slave1 Outdoor Unit Fan PCB Heat Sink Temperature
Sensor open or short
2
3
4
1
9 4
Slave2 Outdoor Unit Fan PCB Heat Sink Temperature
Sensor open or short
Slave3 Outdoor Unit Fan PCB Heat Sink Temperature
Sensor open or short
100
Outdoor Unit
Caution For Refrigerant Leak
Caution For Refrigerant Leak
The installer and system specialist shall secure safety against leakage according to local regulations or standards.
The following standards may be applicable if local regulations are not available.
Introduction
Though the R410A refrigerant is harmless and incombustible itself , the room to equip the air conditioner should be large to
such an extent that the refrigerant gas will not exceed the limiting concentration even if the refrigerant gas leaks in the room.
n Limiting concentration
Limiting concentration is the limit of Freon gas concentration where immediate measures can be taken with-
out hurting human body when refrigerant leaks in the air. The limiting concentration shall be described in the
3
unit of kg/m (Freon gas weight per unit air volume) for facilitating calculation.
3
Limiting concentration: 0.44kg/m (R410A)
Outdoor unit
Flow of
refrigerant
(No.1 system)
Indoor unit
Room where refrigerant leaks
(Refrigerant of the whole No.1
system flows out.)
Checking procedure of limiting concentration
Check limiting concentration along following steps and take appropriate measure depending on the situation.
n Calculate amount of all the replenished refrigerant (kg) per each refrigerant
system.
Amount of replenished
refrigerant per one outdoor
unit system
Amount of additional
replenished refrigerant
Total amount of replenished
refrigerant in refrigerant
facility (kg)
=
+
Note : In case one refrigerant facility is
Amount of replenished
refrigerant at factory shipment
Amount of additionally
replenished refrigerant
depending on piping
length or piping
divided into 2 or more refrigerant
systems and each system is
independent, amount of replenished
refrigerant of each system shall be
adopted.
diameter at customer
n Calculate minimum room capacity
Calculate room capacity by regarding a portion as one room or the smaller room.
(1) Without partition
(2) With partition and with opening which serve as
passage of air to adjoining room
Outdoor unit
Outdoor unit
In the case of opening
without door , or 0.15
% or more openings
Indoor unit
Indoor unit
Opening
(to floor space) both
above and below door)
Partition
Installation Manual 101
Caution For Refrigerant Leak
(3) With partition and without opening which serve as passage of air to adjoining room
Outdoor unit
Indoor unit
Smallest
room
n Calculate refrigerant concentration
Total amount of replenished
refrigerant in refrigerant facility (kg)
In case the result of calculation exceeds
=
Refrigerant concentration
(kg/m3)
the limiting concentration, perform the
same calculations by shifting to the
second smallest, and the third smallest
rooms until at last the result is below the
limiting concentration.
Capacity of smallest room where
indoor unit is installed (m3)
(R410A)
n In case the concentration exceeds the limit
When the concentration exceeds the limit, change original plan or take one of the countermeasures
shown below:
• Countermeasure 1
Provide opening for ventilation.
Provide 0.15% or more opening to floor space both above and below door, or provide opening without
door.
• Countermeasure 2
Provide gas leak alarm linked with mechanical ventilator.
Reducing the outdoor refrigerant qty.
Gas leak alarm
Countermeasure 2
Mechanical ventilator
Indoor unit
Countermeasure 1
Opening effective to ventilation
Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant is
heavier than air.
102
Outdoor Unit
Installation guide at the seaside
Installation guide at the seaside
CAUTION
1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion
on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunc-
tion or inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it
needs additional anticorrosion treatment on the heat exchanger.
Selecting the location(Outdoor Unit)
1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.
Install the outdoor unit on the opposite side of the sea wind direction.
Sea wind
Sea wind
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
• It should be strong enough like concrete to prevent
Windbreak
the sea wind from the sea.
• The height and width should be more than 150% of
the outdoor unit.
Sea wind
• It should be keep more than 70 cm of space
between outdoor unit and the windbreak for easy
air flow.
3) Select a well-drained place.
1. If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment.
2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
Installation Manual 103
|
York 69 1659 Uv100a User Manual
Whirlpool Air Conditioner User Manual
Toshiba Lf470 User Manual
Sharp All In One Printer Mx 3500n User Manual
HP APOLLO 9000 425S User Manual
CRAFTSMAN 580.753000 User Manual
BROTHER HL 5350DN 02 User Manual
BLACK DECKER PI100AB User Manual
ACER EXTENSA 5220 User Manual
ACER B286HK User Manual