EMERSON VILTER 20 20 User Manual

Vission 20/20 micro-controller  
Operation and service manual • Version 1.9  
Table of Contents  
Section Title  
Section Number  
How To Use This Manual......................................................................................................................... TOC-9  
Standard Vilter Warranty Statement ...................................................................................................... TOC-10  
Section 1 • Operational Flow Charts  
Requirements to Start Compressor ........................................................................................................ 1-1  
Critical Compressor Run Logic at Compressor Start................................................................................ 1-1  
Compressor Amperage Load Limiting .................................................................................................... 1-1  
Figure 1-1. Operational Flow Charts ....................................................................................................... 1-1  
High Discharge Pressure Load Limiting.................................................................................................. 1-1  
Suction Pressure Override Load Limit During Temperature Control ........................................................ 1-2  
Section 2 • Installation Recommendations  
Proper Wiring Sizing .............................................................................................................................. 2-1  
Voltage Source ...................................................................................................................................... 2-1  
Figure 2-1. Vission 20/20 with Individual Transformer ............................................................................ 2-1  
Figure 2-2. EMI and Vission 20/20 .......................................................................................................... 2-1  
Grounding ............................................................................................................................................. 2-2  
Mixing Voltages ..................................................................................................................................... 2-2  
DC signals.............................................................................................................................................. 2-2  
Figure 2-3. Ground Wiring ..................................................................................................................... 2-2  
Figure 2-4. Mixed Voltage Wiring........................................................................................................... 2-2  
Wiring Methods..................................................................................................................................... 2-3  
Figure 2-5. Correct Transformer Wiring Method .................................................................................... 2-3  
Figure 2-6. Incorrect Transformer Wiring Method .................................................................................. 2-3  
Best Practices......................................................................................................................................... 2-4  
Section 3 • Hardware Architecture  
Overview ............................................................................................................................................... 3-1  
Figure 3-1. Hardware Architecture Overview ......................................................................................... 3-1  
Digital Input/Output (I/O)...................................................................................................................... 3-2  
Table 3-1. Digital I/O .............................................................................................................................. 3-3  
Analog Inputs ........................................................................................................................................ 3-4  
Table 3-2. Analog Inputs......................................................................................................................... 3-5  
Analog Outputs ..................................................................................................................................... 3-6  
Digital & Analog I/O Boards Layout......................................................................................................... 3-7  
Table 3-3. Analog Outputs...................................................................................................................... 3-7  
Figure 3-2. Digital I/O Board Layout........................................................................................................ 3-7  
Digital Outpout Boards .......................................................................................................................... 3-8  
Figure 3-3. Digital Output Board Layout................................................................................................. 3-8  
Digital Input Boards ............................................................................................................................... 3-9  
Figure 3-4. Digital Input Board Layout .................................................................................................... 3-9  
Digital In-Out Boards ............................................................................................................................. 3-10  
Figure 3-5. Digital Input-Output Board Layout........................................................................................ 3-10  
Analog Input Boards .............................................................................................................................. 3-11  
Figure 3-6. Analog Input Board Layout ................................................................................................... 3-11  
Analog Input Jumper Tables ................................................................................................................... 3-12  
Table 3-4. Analog Input Jumper Tables................................................................................................... 3-12  
Analog Output Boards ........................................................................................................................... 3-14  
Figure 3-7. Analog Output Board Layout ................................................................................................ 3-14  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
TOC - 1  
Table of Contents  
Section Title  
Section Number  
Section 4 • Main Screen  
Overview ............................................................................................................................................... 4-1  
Figure 4-1. Main Screen.......................................................................................................................... 4-1  
Top Status Bar........................................................................................................................................ 4-2  
Figure 4-2. Top Status Bar ...................................................................................................................... 4-2  
Parameter Bar........................................................................................................................................ 4-3  
Figure 4-3. Parameter Bar ...................................................................................................................... 4-3  
Figure 4-4. Unit Start Pop-Up Window ................................................................................................... 4-4  
Bottom Status Bar.................................................................................................................................. 4-5  
Figure 4-5. Bottom Status Bar ................................................................................................................ 4-5  
Splash Screen......................................................................................................................................... 4-6  
Figure 4-6. Splash Screen ....................................................................................................................... 4-6  
Section 5 • Menu Screen  
Overview ............................................................................................................................................... 5-1  
Navigation Buttons ................................................................................................................................ 5-1  
Figure 5-1. Menu Screen ........................................................................................................................ 5-1  
Figure 5-2. Menu Screen with Remote Oil Cooler Enabled....................................................................... 5-2  
Section 6 • Compressor Control  
Overview ............................................................................................................................................... 6-1  
Suction Pressure Control and Process Temperature Control ................................................................... 6-1  
Figure 6-1. Compressor Control Screen - Suction Pressure Control ......................................................... 6-1  
Auto-Cycle ............................................................................................................................................. 6-2  
Figure 6-2. Compressor Control Screen - Process Temperature Control .................................................. 6-2  
Figure 6-3. Proportional Band & Setpoint ............................................................................................... 6-3  
Variable Frequency Drive (VFD).............................................................................................................. 6-4  
Figure 6-4. Compressor Control Screen - VFD Settings Control ............................................................... 6-4  
Figure 6-5. VFD One-Step Control Method ............................................................................................. 6-5  
Figure 6-6. VFD Two-Step Control Method ............................................................................................. 6-5  
Pumpdown Control................................................................................................................................ 6-6  
Figure 6-7. Compressor Control Screen - Pumpdown/Pulldown Control ................................................ 6-6  
Pulldown Control ................................................................................................................................... 6-7  
Control Mode......................................................................................................................................... 6-8  
Figure 6-8. Compressor Control Screen - Misc. 1 (Control Mode)............................................................ 6-8  
Stop load & Force unload ....................................................................................................................... 6-8  
Figure 6-9. Compressor Control Screen - Misc. 2 (Economizer & Hot Gas Bypass Control) ....................... 6-9  
Capacity Slide Triggered Outputs........................................................................................................... 6-9  
Volume Slide Position Offset .................................................................................................................. 6-10  
Soft Load ............................................................................................................................................... 6-10  
Load Anticipating................................................................................................................................... 6-10  
Oil Control ............................................................................................................................................. 6-11  
Figure 6-10. Compressor Control Screen - Oil Control & Liquid Injection Control .................................... 6-11  
Liquid Injection ...................................................................................................................................... 6-11  
Section 7 • Alarms and Trips  
Overview ............................................................................................................................................... 7-1  
Alarms and Trips Setpoints..................................................................................................................... 7-1  
Figure 7-1. Alarms and Trips Screen - Page 1........................................................................................... 7-1  
Figure 7-2. Alarms and Trips Screen - Page 1 as Level 2 User.................................................................... 7-2  
Figure 7-2. Alarms and Trips Screen - Page 2........................................................................................... 7-3  
Figure 7-2. Alarms and Trips Screen - Page 3 .......................................................................................... 7-4  
Compressor Inhibits............................................................................................................................... 7-5  
Safety Failure Messages ......................................................................................................................... 7-5  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
TOC - 2  
Table of Contents  
Section Title  
Section Number  
Compressor Warnings............................................................................................................................ 7-6  
Section 8 • Timers  
Overview ............................................................................................................................................... 8-1  
Timer Setpoints ..................................................................................................................................... 8-1  
Figure 8-1. Timers Screen - Page 1.......................................................................................................... 8-1  
Figure 8-2. Timers Screen - Page 2.......................................................................................................... 8-3  
Section 9 • Compressor Scheduling  
Overview ............................................................................................................................................... 9-1  
Scheduling Setpoint............................................................................................................................... 9-1  
Figure 9-1. Compressor Scheduling Screen ............................................................................................ 9-1  
Section 10 • Compressor Sequencing  
Overview ............................................................................................................................................... 10-1  
Pressure / Temperature Control Setpoints.............................................................................................. 10-1  
Figure 10-1. Compressor Sequencing Screen - Page 1 ............................................................................10-1  
Capacity Load/Unload Timers ................................................................................................................ 10-2  
Figure 10-2. Compressor Sequencing Screen - Page 2 ............................................................................10-2  
Compressor Sequencing Table ............................................................................................................... 10-3  
Figure 10-3. Compressor Sequencing Screen - Page 3 ............................................................................10-3  
Table 10-1. Status Symbols .................................................................................................................... 10-4  
Section 11 • Condenser Control  
Overview ............................................................................................................................................... 11-1  
Condenser Control Setpoint................................................................................................................... 11-1  
Figure 11-1. Condenser Control Screen - Page 1 ..................................................................................... 11-1  
Step Control........................................................................................................................................... 11-2  
VFD Settings .......................................................................................................................................... 11-3  
Figure 11-2. Condenser Control Screen - Page 2 ..................................................................................... 11-4  
Section 12 • Service Options  
Overview ............................................................................................................................................... 12-1  
Digital Outputs ...................................................................................................................................... 12-1  
Figure 12-1. Service Options Screen - Digital Outputs (Page 1)............................................................... 12-1  
Figure 12-2. Service Options Screen - Digital Outputs (Page 2)............................................................... 12-2  
Figure 12-3. Service Options Screen - Digital Outputs (Page 3)............................................................... 12-3  
Figure 12-4. Service Options Screen - Digital Outputs for Remote Oil Cooler (Page 3)............................. 12-4  
Analog Outputs ..................................................................................................................................... 12-5  
Figure 12-5. Service Options Screen - Analog Outputs (Page 4) .............................................................. 12-5  
Section 13 • Instruments Calibration  
Overview ............................................................................................................................................... 13-1  
Pressure and Temperature Inputs........................................................................................................... 13-1  
Figure 13-1. Instruments Calibration Screen - Analog Inputs (Page 1)..................................................... 13-1  
Motor Current........................................................................................................................................ 13-2  
Figure 13-2. Instruments Calibration Screen - Analog Inputs (Page 2) .................................................... 13-2  
Figure 13-3. Instruments Calibration Screen - Analog Inputs (Page 3)..................................................... 13-3  
Remote Capacity ................................................................................................................................... 13-4  
Figure 13-4. Instruments Calibration Screen - Analog Inputs (Page 4)..................................................... 13-4  
Analog Inputs ........................................................................................................................................ 13-4  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
TOC - 3  
Table of Contents  
Section Title  
Section Number  
Figure 13-5. Instruments Calibration Screen - Analog Inputs (Page 5)..................................................... 13-5  
Analog Outputs ..................................................................................................................................... 13-6  
Figure 13-6. Instruments Calibration Screen - Analog Outputs (Page 6).................................................. 13-6  
Section 14 • Slide Calibration  
Overview ............................................................................................................................................... 14-1  
Capacity Slide Valve Potentiometer........................................................................................................ 14-1  
Figure 14-1. Slide Calibration Screen...................................................................................................... 14-1  
Volume Slide Valve Potentiometer ......................................................................................................... 14-2  
Slide Valve Operation............................................................................................................................. 14-2  
Slide Valve Actuator Calibration for Optical Style Motors........................................................................ 14-2  
Figure 14-2. Photochopper .................................................................................................................... 14-3  
Command Shaft Rotation....................................................................................................................... 14-4  
Table 14-1. Command Shaft Rotation Required By Actuator................................................................... 14-4  
Slide Valve Troubleshooting Guide ......................................................................................................... 14-5  
Table 14-2. Slide Valve Troubleshooting Guide ....................................................................................... 14-5  
Slide Valve Actuator Troubleshooting Guide Blink Code .........................................................................14-7  
Table 14-3. LED Blink Codes and Troubleshooting Guide.........................................................................14-7  
Section 15 • Trend Chart  
Overview ............................................................................................................................................... 15-1  
Chart Operation..................................................................................................................................... 15-1  
Figure 15-1. Trend Chart Screen ............................................................................................................. 15-1  
Trend Data Storage ................................................................................................................................ 15-2  
Setup .................................................................................................................................................. 15-3  
Figure 15-2. Trend Setup Screen............................................................................................................. 15-3  
Section 16 • Event List  
Overview ............................................................................................................................................... 16-1  
Event list Columns.................................................................................................................................. 16-1  
Figure 16-1. Event List Screen................................................................................................................. 16-1  
Section 17 • Input / Output  
Overview ............................................................................................................................................... 17-1  
Figure 17-1. Input/Output Screen - Page 1 ............................................................................................. 17-1  
Figure 17-2. Input/Output Screen - Page 2 ............................................................................................. 17-2  
Figure 17-3. Input/Output Screen - Page 3 ............................................................................................. 17-2  
Figure 17-4. Input/Output Screen - Page 4 ............................................................................................. 17-3  
Figure 17-5. Input/Output Screen - Page 4 (Remote Oil Cooler Enabled)................................................. 17-3  
Figure 17-6. Input/Output Screen - Freeze Data Page ............................................................................. 17-4  
Section 18 • Auxiliary Input / Output  
Overview ............................................................................................................................................... 18-1  
Digital Inputs ......................................................................................................................................... 18-1  
Figure 18-1. Auxiliary I/O Screen - Digital Inputs (Page 1) ....................................................................... 18-1  
Digital Outputs ...................................................................................................................................... 18-2  
Analog Inputs ........................................................................................................................................ 18-2  
Figure 18-2. Auxiliary I/O Screen - Digital Outputs (Page 2) .................................................................... 18-3  
Figure 18-3. Auxiliary I/O Screen - Analog Inputs (Page 3) ...................................................................... 18-3  
Analog Outputs ..................................................................................................................................... 18-4  
Control .................................................................................................................................................. 18-4  
Figure 18-4. Auxiliary I/O Screen - Analog Inputs (Page 4) ...................................................................... 18-5  
Figure 18-5. Auxiliary I/O Screen - Analog Inputs (Page 5) ...................................................................... 18-5  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
TOC - 4  
Table of Contents  
Section Title  
Section Number  
Section 19 • Configuration  
Overview ............................................................................................................................................... 19-1  
Units .................................................................................................................................................. 19-1  
Figure 19-1. Confi guration Screen - Initial Setup (Page 1) ...................................................................... 19-1  
Time & Date........................................................................................................................................... 19-2  
Communications ................................................................................................................................... 19-2  
Touchscreen .......................................................................................................................................... 19-2  
Anti-Recycle........................................................................................................................................... 19-3  
Restart On Power Failure........................................................................................................................ 19-3  
Compressor Sequencing ........................................................................................................................ 19-4  
Language............................................................................................................................................... 19-4  
Model & Refrigerant............................................................................................................................... 19-4  
Figure 19-2. Confi guration Screen - Compressor Sequencing (Page 2)................................................... 19-4  
Figure 19-2. Configuration Screen - Page 2............................................................................................. 19-4  
Compressor Control............................................................................................................................... 19-5  
Optional Function Selection................................................................................................................... 19-5  
Condenser Control................................................................................................................................. 19-5  
Oil Pump................................................................................................................................................ 19-5  
Oil Cooling............................................................................................................................................. 19-6  
Motor Current Device ............................................................................................................................ 19-6  
Digital Inputs ......................................................................................................................................... 19-7  
Figure 19-3. Confi guration Screen - Digital Auxiliaries (Page 3) ............................................................. 19-7  
Analog Inputs ........................................................................................................................................ 19-8  
Figure 19-4. Confi guration Screen - Analog Auxiliaries (Page 4) ............................................................. 19-8  
Analog Outputs ..................................................................................................................................... 19-9  
Digital Outputs ...................................................................................................................................... 19-9  
Figure 19-5. Confi guration Screen - Analog and Digital Outputs (Page 5) .............................................. 19-9  
I/O Configuration................................................................................................................................... 19-10  
Figure 19-6. Confi guration Screen - I/O Confi guration (Page 6)............................................................. 19-10  
Section 20 • Data Backup  
Overview ............................................................................................................................................... 20-1  
Save / Load............................................................................................................................................. 20-1  
Figure 20-1. Data Backup Screen - Save/Load ......................................................................................... 20-1  
Migrate.................................................................................................................................................. 20-3  
Factory Reset ......................................................................................................................................... 20-3  
Figure 20-2. Data Backup Screen - Migrate and Factory Reset................................................................. 20-3  
Section 21 • Maintenance  
Overview ............................................................................................................................................... 21-1  
Checklist................................................................................................................................................ 21-1  
Figure 21-1. Maintenance Screen - Checklist .......................................................................................... 21-1  
Notes .................................................................................................................................................. 21-2  
Log  
.................................................................................................................................................. 21-2  
Chart .................................................................................................................................................. 21-2  
Figure 21-2. Maintenance Screen - Log................................................................................................... 21-2  
Figure 21-3. Maintenance Screen - Chart................................................................................................ 21-3  
Section 22 • User Access  
Overview ............................................................................................................................................... 22-1  
Apply .................................................................................................................................................. 22-1  
Figure 22-1. User Access Screen - Login .................................................................................................. 22-1  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
TOC - 5  
Table of Contents  
Section Title  
Section Number  
Login .................................................................................................................................................. 22-2  
Manage Accounts .................................................................................................................................. 22-2  
Figure 22-2. User Access Screen - Manage Accounts............................................................................... 22-2  
VNC Account ......................................................................................................................................... 22-3  
Figure 22-3. User Access Screen - VNC Accounts..................................................................................... 22-3  
Screen Security Levels............................................................................................................................ 22-4  
Table 22-1. Security Access Levels .......................................................................................................... 22-4  
Section 23 • Help Screen  
Overview ............................................................................................................................................... 23-1  
Screen Features ..................................................................................................................................... 23-1  
Figure 23-1. Help Screen - Manual.......................................................................................................... 23-1  
Figure 23-2. Help Screen - USB ............................................................................................................... 23-2  
Figure 23-2. Version Pop-Up Screen ....................................................................................................... 23-2  
Section 24 • Twin Screw Control  
Overview ............................................................................................................................................... 24-1  
Setup - Configuration Screen ................................................................................................................. 24-1  
Figure 24-1. Configuration Screen - Twin Screw Option.......................................................................... 24-1  
Operation .............................................................................................................................................. 24-2  
Slide Calibration - Capacity Slide Valve Potentiometer............................................................................ 24-2  
Figure 24-2. Slide Calibration - Twin Screw Control................................................................................. 24-2  
Figure 24-3. Slide Calibration - Twin Screw Bump Pop-Up Window......................................................... 24-3  
Section 25 • Cool Compression Control  
Overview ............................................................................................................................................... 25-1  
Setup .................................................................................................................................................. 25-1  
Figure 25-1. Cool Compression Control Screen....................................................................................... 25-1  
Control Functions .................................................................................................................................. 25-2  
Figure 25-2. Compressor Control Screen - Cool Compression Control (Page 4) ....................................... 25-2  
Operational Differences from Single Screw ............................................................................................ 25-3  
Section 26 • Remote Oil Cooler  
Overview ............................................................................................................................................... 26-1  
Remote Oil Cooler Setpoint.................................................................................................................... 26-1  
Figure 26-1. Remote Oil Cooler Screen (Page 1) ..................................................................................... 26-1  
Step Control........................................................................................................................................... 26-2  
VFD Settings .......................................................................................................................................... 26-2  
Figure 26-2. Remote Oil Cooler VFD Screen (Page 2) .............................................................................. 26-3  
Appendix A • Vission 20/20 Troubleshooting Guide  
Vission 20/20 Troubleshooting Guide..................................................................................................... A-1  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
TOC - 6  
List of Tables and Figures  
Table/Figure  
Page Number  
Table 3-1. Digital I/O .............................................................................................................................. 3-3  
Table 3-2. Analog Inputs......................................................................................................................... 3-5  
Table 3-3. Analog Outputs...................................................................................................................... 3-7  
Table 3-4. Analog Input Jumper Tables................................................................................................... 3-12  
Table 10-1. Status Symbols .................................................................................................................... 10-4  
Table 14-1. Command Shaft Rotation Required By Actuator................................................................... 14-4  
Table 14-2. Slide Valve Troubleshooting Guide ....................................................................................... 14-5  
Table 14-3. LED Blink Codes and Troubleshooting Guide.........................................................................14-7  
Table 22-1. Security Access Levels .......................................................................................................... 22-4  
Table A. Vission 20/20 Troubleshooting Guide........................................................................................ A-1  
Figure 1-1. Operational Flow Charts ....................................................................................................... 1-1  
Figure 2-1. Vission 20/20 with Individual Transformer ............................................................................ 2-1  
Figure 2-2. EMI and Vission 20/20 .......................................................................................................... 2-1  
Figure 2-3. Ground Wiring ..................................................................................................................... 2-2  
Figure 2-4. Mixed Voltage Wiring........................................................................................................... 2-2  
Figure 2-5. Correct Transformer Wiring Method .................................................................................... 2-3  
Figure 2-6. Incorrect Transformer Wiring Method .................................................................................. 2-3  
Figure 3-1. Hardware Architecture Overview ......................................................................................... 3-1  
Figure 3-2. Digital I/O Board Layout........................................................................................................ 3-7  
Figure 3-3. Digital Output Board Layout................................................................................................. 3-8  
Figure 3-4. Digital Input Board Layout .................................................................................................... 3-9  
Figure 3-5. Digital Input-Output Board Layout........................................................................................ 3-10  
Figure 3-6. Analog Input Board Layout ................................................................................................... 3-11  
Figure 3-7. Analog Output Board Layout ................................................................................................ 3-14  
Figure 4-1. Main Screen.......................................................................................................................... 4-1  
Figure 4-2. Top Status Bar ...................................................................................................................... 4-2  
Figure 4-3. Parameter Bar ...................................................................................................................... 4-3  
Figure 4-4. Unit Start Pop-Up Window ................................................................................................... 4-4  
Figure 4-5. Bottom Status Bar ................................................................................................................ 4-5  
Figure 4-6. Splash Screen ....................................................................................................................... 4-6  
Figure 5-1. Menu Screen ........................................................................................................................ 5-1  
Figure 5-2. Menu Screen with Remote Oil Cooler Enabled....................................................................... 5-2  
Figure 6-1. Compressor Control Screen - Suction Pressure Control ......................................................... 6-1  
Figure 6-2. Compressor Control Screen - Process Temperature Control .................................................. 6-2  
Figure 6-3. Proportional Band & Setpoint ............................................................................................... 6-3  
Figure 6-4. Compressor Control Screen - VFD Settings Control ............................................................... 6-4  
Figure 6-5. VFD One-Step Control Method ............................................................................................. 6-5  
Figure 6-6. VFD Two-Step Control Method ............................................................................................. 6-5  
Figure 6-7. Compressor Control Screen - Pumpdown/Pulldown Control ................................................ 6-6  
Figure 6-8. Compressor Control Screen - Misc. 1 (Control Mode)............................................................ 6-8  
Figure 6-9. Compressor Control Screen - Misc. 2 (Economizer & Hot Gas Bypass Control) ....................... 6-9  
Figure 6-10. Compressor Control Screen - Oil Control & Liquid Injection Control .................................... 6-11  
Figure 7-1. Alarms and Trips Screen - Page 1........................................................................................... 7-1  
Figure 7-2. Alarms and Trips Screen - Page 1 as Level 2 User.................................................................... 7-2  
Figure 7-2. Alarms and Trips Screen - Page 2........................................................................................... 7-3  
Figure 7-2. Alarms and Trips Screen - Page 3 .......................................................................................... 7-4  
Figure 8-1. Timers Screen - Page 1.......................................................................................................... 8-1  
Figure 8-2. Timers Screen - Page 2.......................................................................................................... 8-3  
Figure 9-1. Compressor Scheduling Screen ............................................................................................ 9-1  
Figure 10-1. Compressor Sequencing Screen - Page 1 ............................................................................10-1  
Figure 10-2. Compressor Sequencing Screen - Page 2 ............................................................................10-2  
Figure 10-3. Compressor Sequencing Screen - Page 3 ............................................................................10-3  
Figure 11-1. Condenser Control Screen - Page 1 ..................................................................................... 11-1  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
TOC - 7  
List of Tables and Figures  
Table/Figure  
Page Number  
Figure 11-2. Condenser Control Screen - Page 2 ..................................................................................... 11-4  
Figure 12-1. Service Options Screen - Digital Outputs (Page 1)............................................................... 12-1  
Figure 12-2. Service Options Screen - Digital Outputs (Page 2)............................................................... 12-2  
Figure 12-3. Service Options Screen - Digital Outputs (Page 3)............................................................... 12-3  
Figure 12-4. Service Options Screen - Digital Outputs for Remote Oil Cooler (Page 3)............................. 12-4  
Figure 12-5. Service Options Screen - Analog Outputs (Page 4) .............................................................. 12-5  
Figure 13-1. Instruments Calibration Screen - Analog Inputs (Page 1)..................................................... 13-1  
Figure 13-2. Instruments Calibration Screen - Analog Inputs (Page 2) .................................................... 13-2  
Figure 13-3. Instruments Calibration Screen - Analog Inputs (Page 3)..................................................... 13-3  
Figure 13-4. Instruments Calibration Screen - Analog Inputs (Page 4)..................................................... 13-4  
Figure 13-5. Instruments Calibration Screen - Analog Inputs (Page 5)..................................................... 13-5  
Figure 13-6. Instruments Calibration Screen - Analog Outputs (Page 6).................................................. 13-6  
Figure 14-1. Slide Calibration Screen...................................................................................................... 14-1  
Figure 14-2. Photochopper .................................................................................................................... 14-3  
Figure 15-1. Trend Chart Screen ............................................................................................................. 15-1  
Figure 15-2. Trend Setup Screen............................................................................................................. 15-3  
Figure 16-1. Event List Screen................................................................................................................. 16-1  
Figure 17-1. Input/Output Screen - Page 1 ............................................................................................. 17-1  
Figure 17-2. Input/Output Screen - Page 2 ............................................................................................. 17-2  
Figure 17-3. Input/Output Screen - Page 3 ............................................................................................. 17-2  
Figure 17-4. Input/Output Screen - Page 4 ............................................................................................. 17-3  
Figure 17-5. Input/Output Screen - Page 4 (Remote Oil Cooler Enabled)................................................. 17-3  
Figure 17-6. Input/Output Screen - Freeze Data Page ............................................................................. 17-4  
Figure 18-1. Auxiliary I/O Screen - Digital Inputs (Page 1) ....................................................................... 18-1  
Figure 18-2. Auxiliary I/O Screen - Digital Outputs (Page 2) .................................................................... 18-3  
Figure 18-3. Auxiliary I/O Screen - Analog Inputs (Page 3) ...................................................................... 18-3  
Figure 18-4. Auxiliary I/O Screen - Analog Inputs (Page 4) ...................................................................... 18-5  
Figure 18-5. Auxiliary I/O Screen - Analog Inputs (Page 5) ...................................................................... 18-5  
Figure 19-1. Confi guration Screen - Initial Setup (Page 1) ...................................................................... 19-1  
Figure 19-2. Confi guration Screen - Compressor Sequencing (Page 2)................................................... 19-4  
Figure 19-2. Configuration Screen - Page 2............................................................................................. 19-4  
Figure 19-3. Confi guration Screen - Digital Auxiliaries (Page 3) ............................................................. 19-7  
Figure 19-4. Confi guration Screen - Analog Auxiliaries (Page 4) ............................................................. 19-8  
Figure 19-5. Confi guration Screen - Analog and Digital Outputs (Page 5) .............................................. 19-9  
Figure 19-6. Confi guration Screen - I/O Confi guration (Page 6)............................................................. 19-10  
Figure 20-1. Data Backup Screen - Save/Load ......................................................................................... 20-1  
Figure 20-2. Data Backup Screen - Migrate and Factory Reset................................................................. 20-3  
Figure 21-1. Maintenance Screen - Checklist .......................................................................................... 21-1  
Figure 21-2. Maintenance Screen - Log................................................................................................... 21-2  
Figure 21-3. Maintenance Screen - Chart................................................................................................ 21-3  
Figure 22-1. User Access Screen - Login .................................................................................................. 22-1  
Figure 22-2. User Access Screen - Manage Accounts............................................................................... 22-2  
Figure 22-3. User Access Screen - VNC Accounts..................................................................................... 22-3  
Figure 23-1. Help Screen - Manual.......................................................................................................... 23-1  
Figure 23-2. Help Screen - USB ............................................................................................................... 23-2  
Figure 23-2. Version Pop-Up Screen ....................................................................................................... 23-2  
Figure 24-1. Configuration Screen - Twin Screw Option.......................................................................... 24-1  
Figure 24-2. Slide Calibration - Twin Screw Control................................................................................. 24-2  
Figure 24-3. Slide Calibration - Twin Screw Bump Pop-Up Window......................................................... 24-3  
Figure 25-1. Cool Compression Control Screen....................................................................................... 25-1  
Figure 25-2. Compressor Control Screen - Cool Compression Control (Page 4) ....................................... 25-2  
Figure 26-1. Remote Oil Cooler Screen (Page 1) ..................................................................................... 26-1  
Figure 26-2. Remote Oil Cooler VFD Screen (Page 2) .............................................................................. 26-3  
END OF TOC  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
TOC - 8  
How to Use This Manual  
This manual contains instructions for the Vission 20/20  
Operation & Service Manual. It has been divided into 27  
sections.  
WARNING - Warning statements are shown when there  
are hazardous situations, if not avoided, will result in se-  
rious injury or death.  
Section 1: Operational Flow Charts  
Section 2: Installation Recommendations  
Section 3: Hardware Architecture  
Section 4: Main Screen  
CAUTION - Caution statements are shown when there  
are potentially hazardous situations, if not avoided, will  
result in damage to equipment.  
NOTE - Notes are shown when there are addtional infor-  
mation pertaining to the instructions explained.  
Section 5: Menu Screen  
Section 6: Compressor Control  
Section 7: Alarms & Trips  
NOTICE - Notices are shown when there are important  
information that can help avoid system failure.  
Section 8: Timers  
Section 9: Compressor Scheduling  
Section 10: Compressor Sequencing  
Section 11: Condensor Control  
Section 12: Service Options  
Section 13: Instruments Calibration  
Section 14: Slide Calibration  
Section 15: Trend Chart  
For additional information pertaining to the Vission  
20/20, refer to www.Vission2020.net/documents.  
Information that can be found on the site are:  
• Manuals  
• Release Advisories  
• Application Notes  
• Videos  
Section 16: Event List  
Section 17: Input/Output  
Section 18: Auxiliary Input/Output  
Section 19: Conguration  
Section 20: Data Backup  
Section 21: Maintenance  
Section 22: User Access  
Section 23: Help Screen  
Section 24: Twin Screw Control  
Section 25: Cool Compression Control  
Section 26: Remote Oil Cooler  
Appendix A: Vission 20/20 Troubleshooting Guide  
It is highly recommended that the manual be reviewed  
prior to servicing the Vission 20/20 system parts.  
Figures and tables are included to illustrate key concepts.  
Safety precautions are shown throughout the manual.  
They are dened as the following:  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
TOC - 9  
Standard Vilter Warranty Statement  
Seller warrants the products it manufactures to be free from defects in material and workmanship for a period of eigh-  
teen (18) months from the date of shipment from Seller’s manufacturing plant or twelve (12) months from date of  
installation at the initial end users location, whichever occurs rst. In addition, Seller provides the following extended  
warranties: (a) three (3) years from the date of shipment on single screw compressor internal rotating parts, (b) two  
(2) years from the date of shipment on reciprocating compressors and single screw and reciprocating compressor  
parts, and (c) two (2) years on all other parts on a single screw compressor unit. Such warranties do not apply to  
ordinary wear and tear. Seller does not warrant that the product complies with any particular law or regulation not ex-  
plicitly set forth in the specications, and Buyer is responsible for ensuring that the product contains all features nec-  
essary to safely perform in Buyer’s and its customer’s plants and operations. Buyer must notify Seller of any warranty  
claim within ten (10) days after such claim arises, otherwise Buyer waives all rights to such claim. Products supplied  
by Seller, which are manufactured by others, are not warranted by Seller, but rather Seller merely passes through the  
manufacturer’s warranty to Buyer.  
SELLER EXPRESSLY DISCLAIMS ALL OTHER WARRANTIES, WHETHER EXPRESS OR IMPLIED, INCLUDING THE IMPLIED  
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.  
Unless otherwise agreed in writing, Buyer’s sole remedy for breach of warranty is, at Seller’s option, the re-pair of the  
defect, the correction of the service, or the providing a replacement part FOB Seller’s ofce. Seller will not be respon-  
sible for costs of dismantling, lost refrigerant, reassembling, or transporting the product. Further, Seller will not be  
liable for any other direct, indirect, consequential, incidental, or special damages arising out of a breach of warranty.  
THESE WARRANTY REMEDIES ARE EXCLUSIVE AND ALL OTHER WARRANTY REMEDIES ARE EXCLUDED. Products or  
parts for which a warranty claim is made are to be returned transportation prepaid to Seller’s factory. Any improper  
use, corrosion, neglect, accident, operation beyond rated capacity, substitution of parts not approved by Seller, or  
any alteration or repair by others which, in Seller’s judgement, adversely affects the Product, shall void all warranties  
and warranty obligations. Further, Seller shall not be liable under the above warranties should Buyer be in default of its  
payment obligations to Seller under this Agreement or any credit agreement.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
TOC - 10  
Section 1 • Operational Flow Charts  
Requirements to Start Compressor  
Volume and  
Capacity slides are  
less than 5%  
Oil Separator Temp  
>Oil Sep Start Trip  
Setpt  
Filter Diff Press <  
Start Filter Diff Trip  
Setpt  
Oil Pump On: Prelub Oil Press is > Prelub Oil  
Press Reset Setpt for “Min Compressor Prelub Timer”  
setting (typically 5 seconds)  
Start Compressor  
Critical Compressor Run Logic at Compressor Start  
Start  
Compressor  
Is  
Is  
“Oil Press  
Run Oil Press>  
Run Oil Press  
Reset setpt?  
(Default 40 PSI)  
Run Oil Press>  
Bypass at Comp  
Prelub Oil Press  
Reset setpt?  
Yes  
Yes  
Starttimer  
expires (60 sec  
after start)  
(Default 5 PSI)  
No  
No  
Run Oil Press Failure  
Run Oil Press Failure  
Yes  
Is  
Is Filter Diff >  
Hi Filter Diff Press Run  
Trip Setpt  
Oil Separator Temp  
“Filter Diff Press Safety  
Changeovertimer expires  
(60 sec after start)  
Oil Sep Temp > Lo  
Oil Sep Run Reset  
setpt?  
Safety Changeover  
Timer expires (5 min  
after start)  
Yes  
Yes  
Run  
No  
for 5 seconds  
No  
Yes  
Lo Run Oil Sep Temp Failure  
Run Filter Diff Press Failure  
Compressor Amperage Load Limiting  
High Discharge Pressure Load Limiting  
Is  
Is  
Capacity Increase  
Motor Amps >  
Capacity Increase  
Disabled  
Dsch Press >  
Cutin (ON)  
Setpt?  
Yes  
Yes  
Disabled  
FLA (ON)  
Setpt?  
No  
No  
Is  
Is  
Capacity Decrease until  
Dsch Press < ON Setpt x  
1.0625  
Capacity Decrease  
Motor Amps >  
Dsch Press >  
Cutout (OFF)  
Setpt?  
Yes  
Yes  
until Amps < FLA x  
1.0625  
FLA (OFF)  
Setpt?  
Normal Loading and  
Unloading  
Normal Loading and  
Unloading  
No  
No  
Figure 1-1. Operational Flow Charts (1 of 2)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
1 – 1  
Section 1 Operational Flow Charts  
Suction Pressure Override Load Limit During Temperature Control  
Is  
Suction Press <  
Suct Press Cap  
Dec OFF  
Capacity Increase  
Disabled  
Yes  
Setpt?  
No  
Is  
Suction Press <  
Suct Press Cap  
Dec ON  
Decrease compressor capacity until Suction  
Press > Suction Press Cap Decrease ON setpoint.  
Yes  
No  
Setpt?  
Normal Loading and  
Unloading  
Figure 1-1. Operational Flow Charts (2 of 2)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
1 – 2  
Section 2 Installation Recommendations  
Electro-Magnetic Interference (EMI). The Vilter  
Vission 20/20 should be isolated with its own con-  
trol transformer for the most reliable operation, see  
Figure 2-1. Vission 20/20 with Individual Transformer.  
Proper Wiring Sizing  
• Always size wire gauges as specied by the National  
Electrical Code (NEC) for electronic control devices.  
• For improved noise immunity, install one size larger  
wire gauge than the NEC requirement to assure am-  
ple current-carrying capability.  
• Connecting the Vilter Vission 20/20 to breaker panels  
and central control transformers exposes the Vission  
20/20 to large amounts of EMI emitted from the  
other devices connected to the secondary terminals  
of the transformer. This practice should be avoided if  
possible, see Figure 2-2. EMI and Vission 20/20.  
• Never under size wire gauges.  
Voltage Source  
• Transformers block  
a
large percentage of  
Figure 2-1. Vission 20/20 with Individual Transformer  
Figure 2-2. EMI and Vission 20/20  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
2 – 1  
Section 2 Installation Recommendations  
• Each voltage level must be run in separate conduit:  
Grounding  
• Continuous grounds must be run from the util-  
ity ground to the Vission 20/20, see Figure 2-3.  
Grounding.  
• 460 VAC  
• 230 VAC  
• 120 VAC  
• 24 VAC  
• DC Signals  
• If your installation site has wire-ways or conduit trays,  
dividers must be installed between the different  
voltages.  
• Grounds must be copper or aluminum wire.  
• Never use conduit grounds.  
Mixing Voltages  
DC signals  
• Separate different voltages from each other and  
separate AC from DC, see Figure 2-4. Mixed Voltage  
Wiring.  
• If your installation site has wire-ways or conduit trays,  
dividers must be installed between the different  
voltages.  
Figure 2-3. Ground Wiring  
Figure 2-4. Mixed Voltage Wiring  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
2 – 2  
Section 2 Installation Recommendations  
Wiring Methods  
• Each Vission 20/20 panel should have its own indi-  
vidual control transformer, see Figure 2-5. Correct  
Transformer Wiring Method and Figure 2-6. Incorrect  
Transformer Wiring Method.  
Figure 2-5. Correct Transformer Wiring Method  
Figure 2-6. Incorrect Transformer Wiring Method  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
2 – 3  
Section 2 Installation Recommendations  
Best Practices  
• Do:  
• Keep AC wires away from circuit boards.  
• Always run conduit into the bottom or sides  
of an enclosure.  
• If the conduit must be placed in the top of an  
enclosure, use a water-tight conduit tting to  
keep water from entering the enclosure.  
• The Vission 20/20 is supplied with pre-  
punched conduit holes. Use them!  
• Don’t:  
• Don’t run wires through the Vission 20/20  
enclosure that are not related to the compres-  
sor control.  
• Don’t add relays, timers, transformers, etc. in  
the Vission 20/20 enclosure without rst check-  
ing with Vilter.  
• Don’t run conduit into the top of an enclosure.  
• Don’t run refrigerant tubing inside the  
enclosure.  
• Don’t drill metal enclosures without taking  
proper precautions to protect circuit boards  
from damage.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
2 – 4  
Section 3 Hardware Architecture  
Overview  
The Vission 20/20 control panel utilizes X-86 PC tech-  
nology with a Linux operating system. For hardware  
architecture, see Figure 3-1. Hardware Architecture  
Overview.  
The Vission 20/20 has the following attributes:  
• Low power, Industrial rated X-86 CPU.  
• 15” XGA, high resolution LCD display. (Outdoor view-  
able LCD optional).  
• 8-wire touch screen operator interface.  
• Flexible and expandable I/O.  
• NEMA-4 enclosure (NEMA-4X optional).  
• Industrial temperature range design.  
Figure 3-1. Hardware Architecture Overview  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
3 – 1  
Section 3 • Hardware Architecture  
Trip Output:  
Digital Input/Output (I/O)  
Refer to Table 3-1. Digital I/O.  
• This output is energized when the system has no  
Trips. If a trip is issued, the output de-energizes and  
stays de-energized until the trip condition is cleared.  
Compressor Start Output:  
Slide Valve Setpoint #1 Output (Economizer Port #1):  
• When the Vission 20/20 signals the compressor to  
start, this output is energized. When the Vission  
20/20 signals the compressor to stop, this output is  
de-energized.  
• Normally used for an economizer solenoid, but could  
be used for other devices. When the compressor slide  
valve percentage is equal to or greater than “slide  
valve set-point #1”, the output is energized. When  
the compressor slide valve percentage is less than  
“slide valve set-point #1”, the output is de-energized.  
Oil Pump Start Output:  
• When the Vission 20/20 signals the oil pump to start,  
this output is energized. When the Vission 20/20 sig-  
nals the oil pump to stop, this output is de-energized.  
Slide Valve Setpoint #2 Output (Hot Gas Bypass):  
• Normally used for a hot gas solenoid, but could be  
used for other devices. When the compressor slide  
valve percentage is equal to or greater than “slide  
valve set-point #2”, the output is energized. When  
the compressor slide valve percentage is less than  
“slide valve set-point #2”, the output is de-energized.  
Capacity Increase Output:  
• This output is only active when the compressor is  
running. When the Vission 20/20 determines that  
the compressor should increase capacity by moving  
the slide valve to a higher percentage, this output is  
energized. Once the slide valve reaches 100%, this  
output will not energize.  
Alarm Output:  
• This output is energized when the system has no  
alarms. If an alarm is issued, the output de-energizes  
and stays de-energized until the alarm condition is  
cleared.  
Capacity Decrease Output:  
• This output is only active when the compressor is  
running. When the Vission 20/20 determines that  
the compressor should decrease capacity by moving  
the slide valve to a lower percentage, this output is  
energized. Once the slide valve reaches 0%, this out-  
put will not energize.  
Economizer Port #2 Output:  
• This output is energized when the compressor slide  
valve percentage is equal to or greater than slide  
valve set-point for economizer port 2. It is de-ener-  
gized when the compressor slide valve percentage is  
less than slide valve set-point for economizer port 2.  
Volume Increase Output:  
• This output is only active when the compressor is  
running. When the Vission 20/20 determines that  
the compressor should increase Volume Index (VI) by  
moving the volume slide to a higher percentage, this  
output is energized. Once the volume slide reaches  
100%, this output will not energize.  
Liquid Injection #1 Output:  
• The function of this output will differ depending on  
what type liquid injection is selected. If the liquid in-  
jection solenoid only is chosen, then the output will  
energize when discharge temperature is above liquid  
injection setpoint #1 and the oil separator tempera-  
ture is above the oil separator temperature override  
set-point. The output is de-energized when any one  
of the above condition is not met.  
Volume Decrease Output:  
• This output is only active when the compressor is run-  
ning. When the Vission 20/20 determines that the  
compressor should decrease Volume Index (VI) by  
moving the volume slide to a lower percentage, this  
output is energized. Once the volume slide reaches  
0%, this output will not energize.  
• If the compressor has liquid injection with motor-  
ized value oil cooling, then this output is energized  
when the compressor is running and the discharge  
temperature is above the oil separator temperature  
override set-point and the oil separator temperature  
is above the override setpoint. The output is de-en-  
ergized when the discharge temperature falls below  
the “on” setpoint minus the solenoid differential or  
when oil separator temperature is below the oil sepa-  
rator temperature override set-point.  
Oil Sump Heater Output:  
• This output is active and energized when the oil  
separator temperature is lower than the oil separator  
temperature setpoint. It is de-energized when the oil  
separator temperature is higher than the oil separa-  
tor temperature setpoint.  
Liquid Injection #2 Output:  
• Not Dened  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
3 – 2  
Section 3 • Hardware Architecture  
Table 3-1. Digital I/O (1 of 2)  
Description  
Board  
I/O #  
1
Type  
OUTPUT  
OUTPUT  
OUTPUT  
OUTPUT  
OUTPUT  
OUTPUT  
OUTPUT  
OUTPUT  
OUTPUT  
OUTPUT  
OUTPUT  
OUTPUT  
OUTPUT  
OUTPUT  
OUTPUT  
OUTPUT  
INPUT  
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4
Compressor Start  
2
Oil Pump Start  
3
Capacity Increase  
4
Capacity Decrease  
5
Volume Increase  
6
Volume Decrease  
7
Oil Separator Heater  
8
Trip indicator (ON=Normal)  
Slide Valve Set point #1 (Economizer Port #1)  
Slide Valve Set point #2 (Hot Gas Bypass)  
Alarm (ON=Normal)  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
Economizer Port #2  
Liquid Injection #1  
Liquid Injection #2  
Remote Enabled  
Shunt Trip  
Comp Motor Starter Auxiliary Contact  
High Level Shutdown  
INPUT  
Oil Level Float Switch #1  
Oil Level Float Switch #2  
Remote Setpoint #1/#2 Selection  
Remote Start/Stop  
INPUT  
INPUT  
INPUT  
INPUT  
Remote Capacity Increase  
Remote Capacity Decrease  
Condenser / Remote Oil Cooler Step #1  
Condenser / Remote Oil Cooler Step #2  
Condenser / Remote Oil Cooler Step #3  
Condenser / Remote Oil Cooler Step #4  
Auxiliary Input #1  
INPUT  
INPUT  
OUTPUT  
OUTPUT  
OUTPUT  
OUTPUT  
INPUT  
Auxiliary Input #2  
INPUT  
Auxiliary Input #3  
INPUT  
Auxiliary Input #4  
INPUT  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
3 – 3  
Section 3 • Hardware Architecture  
• The slide valve will continuously increase as long as  
this input is energized. The slide valve will not in-  
crease when this input is de-energized.  
Remote Enabled Output:  
• This output is energized when the Vission 20/20  
panel is enabled for remote control. If the compres-  
sor parameter does not satisfy start conditions or is  
placed into the manual stop position, this output is  
de-energized.  
Remote Capacity Decrease Input:  
• Operational only when the compressor is running.  
This input is enabled if the compressor is enabled  
for remote I/O control. Energizing this input will de-  
crease the slide valve position. The slide valve will  
continuously decrease as long as this input is ener-  
gized. The slide valve will not decrease when this in-  
put is de-energized.  
Shunt Trip:  
• This output is designed to be connected to a master  
power breaker with a shunt trip input. If the Vission  
20/20 detects the compressor motor is running when  
it’s not suppose to be, then this output can be ener-  
gized to trip the breaker supplying power to a starter.  
Condenser / Remote Oil Cooler Step #1 Output:  
• This output is enabled when condenser control or  
Remote Oil Cooler option is selected. A condenser /  
Remote Oil Cooler fan or pump will be turned on or  
off by this output.  
Comp Motor Starter Auxiliary Contact:  
• This input looks for a feedback signal from the com-  
pressor starter, conrming that the compressor  
starter is energized.  
Condenser / Remote Oil Cooler Step #2 Output:  
High Level Shutdown Input:  
• This output is enabled when condenser control or  
Remote Oil Cooler option is selected. A condenser /  
Remote Oil Cooler fan or pump will be turned on or  
off by this output.  
• This input must be energized in order for the com-  
pressor to operate. If de-energized, the compressor  
will shut down and issue a high level trip.  
Oil Level Float Switch #1 Input:  
Condenser / Remote Oil Cooler Step #3 Output:  
• This input must be energized in order for the com-  
pressor to operate. If de-energized, the compressor  
will shut down and issue a oil level #1 trip.  
• This output is enabled when condenser or Remote  
Oil Cooler control option is selected. A condenser /  
Remote Oil Cooler fan or pump will be turned on or  
off by this output.  
Oil Level Float Switch #2 Input:  
• This input must be energized in order for the com-  
pressor to operate. If de-energized, the compressor  
will shut down and issue a oil level #2 trip.  
Condenser / Remote Oil Cooler Step #4 Output:  
• This output is enabled when condenser or Remote  
Oil Cooler control option is selected. A condenser /  
Remote Oil Cooler fan or pump will be turned on or  
off by this output.  
Remote Select #1/#2 Input:  
• This input enables or disables remote I/O control.  
Energizing this input enables the Remote Capacity  
Increase and Remote Capacity Decrease inputs.  
Auxiliary Inputs #1 - #8:  
• Optional inputs that can be congured as an alarm  
or trip. Typically connected to external switched  
devices.  
Remote Start/Stop Input:  
• If the compressor is enabled for remote I/O control,  
this input is enabled. Energizing this input will issue  
a start for the compressor as long as it is available to  
run. De-energizing this input stops the compressor.  
Auxiliary Outputs #1 - #4:  
• Optional inputs that can be congured as an alarm  
or trip. Typically connected to external switched  
devices.  
Remote Capacity Increase Input:  
NOTE  
The scan interval on the remote increase and  
decrease inputs is approximately ONE SECOND.  
Please take that into account when developing  
a control scheme using the remote increase and  
remote decrease inputs for compressor control.  
Analog Inputs  
Refer to Table 3-2. Analog Inputs.  
Motor Current:  
• Default is a 0-5 Amp current transformer (CT). Current  
transformer ratio is set in the calibration screen.  
• If the compressor is enabled for remote I/O control,  
this input is enabled. Operational only when the com-  
pressor is running. Energizing this input will increase  
the slide valve position.  
Suction Pressure:  
• Default signal is 4-20mA. Suction pressure transducer  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
3 – 4  
Section 3 • Hardware Architecture  
Table 3-1. Digital I/O (2 of 2)  
Description  
Board  
I/O #  
33  
Type  
OUTPUT  
OUTPUT  
OUTPUT  
OUTPUT  
INPUT  
5
5
5
5
5
5
5
5
Auxiliary Output #1  
34  
Auxiliary Output #2  
Auxiliary Output #3  
Auxiliary Output #4  
Auxiliary Input #5  
Auxiliary Input #6  
Auxiliary Input #7  
Auxiliary Input #8  
35  
36  
37  
38  
INPUT  
39  
INPUT  
40  
INPUT  
Table 3-2. Analog Inputs (1 of 2)  
Description  
Board  
I/O #  
1
Type  
4-20 mA, 0-5A  
6
6
6
6
6
6
6
6
7
7
7
7
7
7
7
7
8
8
8
8
8
8
8
8
9
9
9
Motor Current  
2
Suction Pressure  
Discharge Pressure  
Oil Filter Inlet Pressure  
Oil Manifold Pressure  
Economizer Pressure  
% Slide Valve Position  
% Volume Position  
Suction Temperature  
Discharge Temperature  
Oil Separator Temperature  
Oil Manifold Temperature  
Process Temperature  
Chiller Inlet Temperature  
Condenser Pressure  
Remote Caphold Setpoint  
Auxiliary #1  
0-5V, 1-5 V, 0-10V, 4-20 mA  
3
0-5V, 1-5 V, 0-10V, 4-20 mA  
4
0-5V, 1-5 V, 0-10V, 4-20 mA  
5
0-5V, 1-5 V, 0-10V, 4-20 mA  
6
0-5V, 1-5 V, 0-10V, 4-20 mA  
7
0-5V, 4-20 mA, Potentiometer  
0-5V, 4-20 mA, Potentiometer  
4-20 mA, RTD, ICTD  
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
4-20 mA, RTD, ICTD  
4-20 mA, RTD, ICTD  
4-20 mA, RTD, ICTD  
4-20 mA, RTD, ICTD  
4-20 mA, RTD, ICTD  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
0-5V, 4-20 mA, RTD, ICTD  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
Auxiliary #2  
Auxiliary #3  
Auxiliary #4  
Auxiliary #5  
Auxiliary #6  
Auxiliary #7  
Auxiliary #8  
Auxiliary #9  
Auxiliary #10  
Auxiliary #11  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
3 – 5  
Section 3 • Hardware Architecture  
range and calibration is set in the calibration screen.  
Discharge Pressure  
screen.  
Remote Caphold:  
• Default signal is 4-20mA. Discharge pressure trans-  
ducer range and calibration is set in the calibration  
screen.  
• Default signal is 4-20mA. Active in “Direct I/O” mode.  
Adjusts the capacity of the compressor from 0-100%,  
proportional to the 4-20mA signal.  
Oil Filter Inlet Pressure:  
Auxiliary #1 - #16:  
• Default signal is 4-20mA. Oil lter pressure trans-  
ducer range and calibration is set in the calibration  
screen.  
• Flexible analog inputs that can be congured to con-  
trol, alarm or trip.  
Oil Manifold Pressure:  
Analog Outputs:  
Refer to Table 3-3. Analog Outputs.  
• Default signal is 4-20mA. Oil manifold pressure trans-  
ducer range and calibration is set in the calibration  
screen.  
Compressor VFD:  
Economizer Pressure:  
• 4-20mA output to control compressor motor speed  
with a Variable Frequency Drive (VFD).  
• Default signal is 4-20mA. Economizer pressure trans-  
ducer range and calibration is set in the calibration  
screen.  
Condenser / Remote Oil Cooler VFD:  
• 4-20mA output to control one condenser / remote oil  
cooler fan which is interleaved between the remain-  
ing condenser / remote oil cooler steps for smoother  
control.  
Slide Valve Position:  
• Reads the 0-5 volt signal back from the slide posi-  
tion motor actuator to indicate current slide valve  
position.  
% Slide Valve Position:  
Volume Position:  
• 4-20mA signal that transmits the slide valve position  
for remote monitoring.  
• Reads the 0-5 volt signal back from the slide volume  
motor actuator to indicate current volume position.  
Motorized Valve (V+):  
Suction Temperature:  
• For a cool compression compressor, this 4-20mA  
signal controls a motorized valve to regulate the liq-  
uid refrigerant level in the oil separator. For a liquid  
injection application on a standard single screw, this  
4-20mA signal controls a motorized valve to regulate  
the liquid refrigerant injected into the compressor for  
oil cooling purposes.  
• Default signal is RTD. Suction temperature calibra-  
tion is set in the calibration screen.  
Discharge Temperature:  
• Default signal is RTD. Discharge temperature calibra-  
tion is set in the calibration screen.  
Oil Separator Temperature:  
Auxiliary Outputs #1 - #4:  
• Default signal is RTD. Oil separator temperature cali-  
bration is set in the calibration screen.  
• Optional outputs that can be congured in user de-  
ned manner.  
Oil Manifold Temperature:  
• When Oil Flow Control option is selected from cong-  
uration screen, Auxiliary Output #1 which is 4-20mA  
signal is used to control the opening percentage of  
Danfoss valve.  
• Default signal is RTD. Oil manifold temperature cali-  
bration is set in the calibration screen.  
Process Temperature:  
• Default signal is 4-20mA. Process temperature cali-  
bration and range are set in the calibration screen.  
Chiller Inlet Temperature:  
• Default signal is 4-20mA. Measures separator level.  
Chiller Inlet Temperature calibration and range are  
set in the calibration screen.  
Condenser Pressure:  
• Default signal is 4-20mA. Condenser pressure trans-  
ducer range and calibration is set in the calibration  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
3 – 6  
Section 3 • Hardware Architecture  
Table 3-2. Analog Inputs (2 of 2)  
Description  
Board  
I/O #  
28  
Type  
9
9
9
9
9
Auxiliary #12  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
0-5V, 1-5 V, 0-10V, 4-20 mA, RTD, ICTD  
29  
Auxiliary #13  
Auxiliary #14  
Auxiliary #15  
Auxiliary #16  
30  
31  
32  
Table 3-3. Analog Outputs  
Description  
Board  
10  
I/O #  
Type  
1
2
3
Compressor VFD  
4-20 mA  
4-20 mA  
4-20 mA  
10  
Condenser / Remote Oil Cooler VFD  
% Slide Valve Position  
10  
Motorized Valve (Cool Compression or Liquid  
Injection), V+  
10  
4
4-20 mA  
10  
10  
10  
10  
5
6
7
8
Auxiliary Output #1  
Auxiliary Output #2  
Auxiliary Output #3  
Auxiliary Output #4  
4-20 mA  
4-20 mA  
4-20 mA  
4-20 mA  
Digital & Analog I/O Boards Layout  
It is important to install the boards in the proper layout.  
For the correct digital and analog input/output (I/O)  
board layout, see Figure 3-2. Digital I/O Board Layout.  
Dipswitches  
• Each board has a dipswitch which sets its communi-  
cations address so that it can communicate with the  
CPU board. The dipswitch settings must be correct  
or the I/O will not function.  
Jumpers  
• Jumpers are required on the analog boards to con-  
gure them for the type of sensors used. The jumper  
table for the analog board shows the optional jump-  
er congurations for sensors other than the default  
Vilter standard. If a different sensor is to be used, the  
jumpers on the analog board need to be changed. In  
addition, the conguration for this sensor must be  
changed in the Instrument Calibration screen. The  
following illustrations show the Vilter default con-  
gurations for the Vission 20/20.  
Figure 3-2. Digital I/O Board Layout  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
3 – 7  
Section 3 • Hardware Architecture  
Voltage LEDs:  
Digital Output Boards  
• Marked in the diagram below in Orange. These LEDs  
indicate the correct voltage of both the 5Vdc and  
24Vdc power sources.  
The digital output board convert signals generated by  
the Vission 20/20 program into 120Vac signals that can  
be energize or signal other devices. All the signals are  
digital in that the only two states available or either on  
or off. See board layout, Figure 3-3. Digital Output Board  
Layout.  
Communication LEDs:  
• Marked in the diagram below in Green. These LEDs  
show the active communications between the digital  
output board and the Vission 20/20 CPU board.  
Address Dipswitches:  
Signal LEDs:  
• Marked in the diagram below in Red. These dipswitch-  
es are used to assign each board its address position.  
The addresses are binary and therefore the address  
of a digital output board will either be address as 1  
(0001) or 2 (0010).  
• Marked in the diagram below in Blue. These LEDs in-  
dicated when a 120Vac output is being produced.  
Figure 3-3. Digital Output Board Layout  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
3 – 8  
Section 3 • Hardware Architecture  
Voltage LEDs:  
Digital Input Boards  
• Marked in the diagram below in Orange. These LEDs  
indicate the correct voltage of both the 5Vdc and  
24Vdc power sources.  
The digital input board convert 120Vdc signals from ex-  
ternal devices to signals for the Vission 20/20 program.  
All the signals are digital in that the only two states avail-  
able or either on or off. See board layout, Figure 3-4.  
Digital Input Board Layout.  
Communication LEDs:  
• Marked in the diagram below in Green. These LEDs  
show the active communications between the digital  
output board and the Vission 20/20 CPU board.  
Signal LEDs:  
Address Dipswitches:  
• Marked in the diagram below in light Blue. These  
LEDs indicate when a 120Vac input is detected.  
• Marked in the diagram below in Red. These dip-  
switches are used to assign each board its address  
position. The addresses are binary and therefore the  
address of a digital input board can only be addressed  
as 3 (0011).  
Figure 3-4. Digital Input Board Layout  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
3 – 9  
Section 3 • Hardware Architecture  
Voltage LEDs:  
Digital In-Out Boards  
• Marked in the diagram below in Orange. These LEDs  
indicate the correct voltage of both the 5Vdc and  
24Vdc power sources.  
The digital input - output board convert signals gener-  
ated by the Vission 20/20 program into 120Vac signals  
as well as detect external 120Vac inputs to signal the  
Vission 20/20 program.  
Communication LEDs:  
• Marked in the diagram below in Green. These LEDs  
show the active communications between the digital  
output board and the Vission 20/20 CPU board.  
All the signals are digital in that the only two states avail-  
able or either on or off. See board layout, Figure 3-5.  
Digital Input-Output Board Layout.  
Address Dipswitches:  
• Marked in the diagram below in Red. These dipswitch-  
es are used to assign each board its address position.  
The addresses are binary and therefore the address  
of a digital output board will either be address as 4  
(0100) or 5 (0101).  
Signal LEDs:  
• Marked in the diagram below in Blue or outputs and  
light blue for inputs. These LEDs indicate when a  
120Vac output is being produced or a 120Vac signal  
is detected.  
Figure 3-5. Digital Input-Output Board Layout  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
3 – 10  
Section 3 • Hardware Architecture  
Voltage LEDs:  
Analog Input Boards  
• Marked in the diagram below in Orange. These LEDs  
indicate the correct voltage of both the 5Vdc and  
24Vdc power sources.  
The analog input board convert varying DC signals into  
a signal that can interpreted by the Vission 20/20 pro-  
gram. The signals are considered analog because the  
input DC signal can vary from the minimum value to the  
maximum value. See board layout, Figure 3-6. Analog  
Input Board Layout.  
Communication LEDs:  
• Marked in the diagram below in Green. These LEDs  
show the active communications between the digital  
output board and the Vission 20/20 CPU board.  
Address Dipswitches:  
Conguration Jumpers:  
• Marked in the diagram below in Red. These dip-  
switches are used to assign each board its address  
position. The addresses are binary and therefore the  
address of a digital output board will be address as 6  
(0110), 7 (0111), 8 (1000) or 9 (1001).  
• Marked in the diagram below in Purple. The jumpers  
allow the operator to congure the signal type and  
range for incoming analog signals. For the correct  
jumper setting for a giving application, see Table 3-4.  
Analog Input Jumper Tables.  
Figure 3-6. Analog Input Board Layout  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
3 – 11  
Section 3 • Hardware Architecture  
Analog Input Jumper Tables  
The following tables are used to congure each channel of the analog input board signal type and range desired by the  
operator, see Table 3-4. Analog Input Jumper Tables.  
Table 3-4. Analog Input Jumper Tables  
CHANNEL 1  
SIGNAL  
0-5 AMP  
0-5 VOLT  
1-5 VOLT  
0-10 VOLT  
4-20 mA  
ICTD  
JP-1  
OUT  
OUT  
OUT  
OUT  
IN  
JP-2  
OUT  
OUT  
OUT  
OUT  
OUT  
IN  
JP-3  
OUT  
OUT  
OUT  
IN  
JP-27 JP-35  
Analog Input 1-A*  
Analog input 1-B**  
OUT  
OUT  
OUT  
OUT  
OUT  
OUT  
IN  
IN  
OUT  
OUT  
OUT  
OUT  
OUT  
OUT  
OUT  
OUT  
OUT  
OUT  
OUT  
RTD  
OUT  
*Use Analog Input 1-A when 0-5 AMP secondary current transformers are installed in the motor starter.  
**Use Analog Input 1-B when current transformers are installed in the motor starter.  
CHANNEL 2  
SIGNAL  
0-5 VOLT  
1-5 VOLT  
0-10 VOLT  
4-20 mA  
ICTD  
JP-4  
OUT  
OUT  
OUT  
IN  
JP-5  
OUT  
OUT  
OUT  
OUT  
IN  
JP-6  
OUT  
OUT  
IN  
JP-28  
OUT  
OUT  
OUT  
OUT  
OUT  
IN  
Analog Input 2  
OUT  
OUT  
OUT  
OUT  
OUT  
RTD  
OUT  
CHANNEL 3  
SIGNAL  
0-5 VOLT  
1-5 VOLT  
0-10 VOLT  
4-20 mA  
ICTD  
JP-7  
OUT  
OUT  
OUT  
IN  
JP-8  
OUT  
OUT  
OUT  
OUT  
IN  
JP-9  
OUT  
OUT  
IN  
JP-29  
OUT  
OUT  
OUT  
OUT  
OUT  
IN  
Analog Input 3  
OUT  
OUT  
OUT  
OUT  
OUT  
RTD  
OUT  
CHANNEL 4  
SIGNAL  
0-5 VOLT  
1-5 VOLT  
0-10 VOLT  
4-20 mA  
ICTD  
JP-10  
OUT  
OUT  
OUT  
IN  
JP-11  
OUT  
OUT  
OUT  
OUT  
IN  
JP-12  
OUT  
OUT  
IN  
JP-30  
OUT  
OUT  
OUT  
OUT  
OUT  
IN  
Analog Input 4  
OUT  
OUT  
OUT  
OUT  
OUT  
RTD  
OUT  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
3 – 12  
Section 3 • Hardware Architecture  
Table 3-4. Analog Input Jumper Tables (Continued)  
CHANNEL 5  
SIGNAL  
0-5 VOLT  
1-5 VOLT  
0-10 VOLT  
4-20 mA  
ICTD  
JP-13  
OUT  
OUT  
OUT  
IN  
JP-14  
OUT  
OUT  
OUT  
OUT  
IN  
JP-15  
OUT  
OUT  
IN  
JP-31  
OUT  
OUT  
OUT  
OUT  
OUT  
IN  
Analog Input 5  
OUT  
OUT  
OUT  
OUT  
OUT  
RTD  
OUT  
CHANNEL 6  
SIGNAL  
0-5 VOLT  
1-5 VOLT  
0-10 VOLT  
4-20 mA  
ICTD  
JP-16  
OUT  
OUT  
OUT  
IN  
JP-17  
OUT  
OUT  
OUT  
OUT  
IN  
JP-18  
OUT  
OUT  
IN  
JP-32  
OUT  
OUT  
OUT  
OUT  
OUT  
IN  
Analog Input 6  
OUT  
OUT  
OUT  
OUT  
OUT  
RTD  
OUT  
CHANNEL 7  
SIGNAL  
JP-19  
JP-20  
JP-21  
JP-33 JP-25  
Analog Input 7  
0-5 VOLT  
1-5 VOLT  
0-10 VOLT  
4-20 mA  
OUT  
OUT  
OUT  
IN  
OUT  
OUT  
OUT  
OUT  
IN  
OUT  
OUT  
IN  
OUT  
OUT  
OUT  
OUT  
OUT  
IN  
2
2
2
2
2
2
1
3
OUT  
OUT  
OUT  
OUT  
OUT  
ICTD  
OUT  
OUT  
OUT  
OUT  
RTD  
OUT  
OUT  
OUT  
ACTUATOR  
POTENTIOMETER  
OUT  
OUT  
CHANNEL 8  
SIGNAL  
0-5 VOLT  
1-5 VOLT  
0-10 VOLT  
4-20 mA  
JP-22  
OUT  
OUT  
OUT  
IN  
JP-23  
OUT  
OUT  
OUT  
OUT  
IN  
JP-24  
OUT  
OUT  
IN  
JP-34 JP-26  
Analog Input 8  
OUT  
OUT  
OUT  
OUT  
OUT  
IN  
2
2
2
2
2
2
1
3
OUT  
OUT  
OUT  
OUT  
OUT  
ICTD  
OUT  
OUT  
OUT  
OUT  
RTD  
OUT  
OUT  
OUT  
ACTUATOR  
POTENTIOMETER  
OUT  
OUT  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
3 – 13  
Section 3 • Hardware Architecture  
Communication LEDs:  
Analog Output Boards  
• Marked in the diagram below in Green. These LEDs  
show the active communications between the digital  
output board and the Vission 20/20 CPU board.  
The Analog Output board convert signals from the  
Vission 20/20 program into a current ranging from 4mA  
to 20mA, see Figure 3-7. Analog Output Board Layout.  
Address Dipswitches:  
• Marked in the diagram below in Red. These dipswitch-  
es are used to assign each board its address position.  
The addresses are binary and therefore the address  
of a digital output board will only be addressed as 10  
(1010).  
Voltage LEDs:  
• Marked in the diagram below in Orange. These LEDs  
indicate the correct voltage of both the 5Vdc and  
24Vdc power sources.  
Figure 3-7. Analog Output Board Layout  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
3 – 14  
Section 4 Main Screen  
Overview  
The Main Screen is the rst screen encountered when  
powering up the Vission 20/20 Panel, see Figure 4-1.  
Main Screen. This screen is designed as the starting  
point for all succeeding screens and provides as much in-  
formation as possible at a glance. The Main Screen is di-  
vided into four sections. Three of the sections are static;  
Top Status Bar, Bottom Status Bar and Parameters Bar.  
These three sections of the main screen will remain vis-  
ible while navigating through other screens and provide  
a constant view of critical information. The splash screen  
is the only dynamic section. All navigation to any other  
screens will be performed through the Main Screen.  
Figure 4-1. Main Screen  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
4 – 1  
Section 4 Main Screen  
Information Bars will ash their information over the top  
of the status bar. The operator will see the status bar  
and then one or more information bars in a repetitive  
sequence.  
Top Status Bar  
The standard view of the status bar shows three pieces  
of information. From left to right , the bar shows the con-  
trol method, the current run mode, and the difference  
between the desired control setpoint and the actual  
value of the processes control value, see Figure 4-2. Top  
Status Bar.  
Information Bar – blue:  
• Shows various operational modes that are different  
than normal running condition. An example of this  
would be a load limit condition. The compressor is  
not able to completely load due to some parameter  
like high motor current and therefore the operator is  
notied via this type of information bar.  
The status bar also has an alternate function where it dis-  
plays to the user any information that requires user at-  
tention or intervention. It accomplishes this by changing  
the status bar’s color and/or ashing a additional infor-  
mation bars over the standard status bar view.  
Information bar – yellow  
• This typically indicates an Alarm condition. Alarm  
conditions do not stop the compressor but it is meant  
to alert the operator of conditions that if corrective  
action is not taken, then a compressor trip can result.  
Standard Bar – blue:  
• Indicates a condition where the compressor motor is  
not running.  
Information bar – red  
Standard Bar – green:  
• Informs the operator that the compressor motor  
was stopped due the condition listed in the informa-  
tion bar. Compressor trips are designed to protect  
the equipment and any personnel operating the  
equipment.  
• Informs the operator that the compressor motor is  
currently running.  
Figure 4-2. Top Status Bar  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
4 – 2  
Section 4 Main Screen  
Stop Button:  
Parameter Bar  
• When pressed, stops the compressor in all cases.  
Remote Lock Out Button:  
The main purpose of the Parameter Bar is to display  
the common operational parameters that the operator  
would be most concerned with. It also gives the operator  
access to critical buttons such as the stop and start but-  
tons, see Figure 4-3. Parameter Bar.  
• When pressed, activates the remote lock out option.  
This is a safety feature that prevents any external de-  
vices from assuming control and starting the com-  
pressor. To release the remote lock out, the operator  
must press the unit start button and then the remote  
button when the start dialog box appears.  
Capacity Slide Indicator:  
• Shows the position of the capacity slide from 0% to  
100% via a horizontal blue bar. The buttons below the  
indicator are used in manual capacity control. The “-”  
button will decrease the capacity position and the  
“+” button will increase the position.  
Alarm Reset Button:  
• When pressed, clears any current alarms, trips or  
status messages that may be displayed on the infor-  
mation bar. Note, if the condition that created the  
alarm, trip or status message still exits, the message  
will reappear.  
Volume Slide Indicator:  
• Shows the position of the volume slide from 0% to  
100% via a horizontal blue bar. In some cases, in-  
crease and decrease buttons will appear below the  
volume indicator. The buttons only appear if the op-  
erator who is logged on has sufcient privileges. If  
available, the buttons work to increase and decrease  
the volume slide position in the same manner as the  
capacity slide.  
Figure 4-3. Parameter Bar  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
4 – 3  
Section 4 Main Screen  
• The suction box shows the current suction  
pressure and suction temperature.  
Parameter Bar (Continued)  
Unit Start Button:  
• The discharge box shows the current dis-  
charge pressure and discharge temperature .  
• When pressed, a start dialog box will appear that  
will give the operator a number of run options; Auto,  
Manual, Remote, or Auto Sequencing, see Figure 4-4.  
Unit Start Pop-Up Window.  
• The oil box shows the pressure differential  
which is calculated as oil lter out pressure mi-  
nus suction pressure. Filter differential is calcu-  
lated as oil lter in pressure minus oil lter out  
pressure. “Inj Temp” is the temperature of the  
oil at the oil injection port and “Sep Temp” is the  
temperature of the oil in the separator.  
Control Parameter Boxes:  
• The parameter boxes provide updated data on sev-  
eral key control parameters.  
• The top box indicates the desired control  
setpoint that is set in the Compressor Control  
Screen. In the case that the Run mode is in re-  
mote capacity control, this box will show the  
desired capacity position.  
• The motor box shows the motor current.  
Figure 4-4. Unit Start Pop-Up Window  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
4 – 4  
Section 4 Main Screen  
screen to create additional users.  
Log off Button:  
Bottom Status Bar  
The bottom status bar gives the operator easy access  
to some basic functions and information. The functions  
are available via the four button, see Figure 4-5. Bottom  
Status Bar.  
• Pressing the log off button logs off the correct user if  
any are logged in.  
Help Button:  
• Pressing the help button takes the operator to the  
help screen where the operator can access an opera-  
tion and service manual and also get access to pro-  
gram information.  
Maintenance Button:  
• Pressing the maintenance button will give the op-  
erator access to the maintenance charts and sign off  
tables.  
Status Bars  
• The information available is provide by two status  
bars, one for maintenance activities and the other for  
any alarms or trips that might be active. To the right  
of the status bars are positions for displaying the cur-  
rent user (if any are logged in), the date and time, and  
the total run hours of the compressor.  
User Access Button:  
• This button takes the operator to another login  
Figure 4-5. Bottom Status Bar  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
4 – 5  
Section 4 Main Screen  
Process:  
Splash Screen  
• When the Process control is selected as the control  
mode, this box will appear and displays the process  
temperature.  
The splash screen is the dynamic portion of the screen  
that will change as the operator navigates through  
the Vission 20/20 panel screen, see Figure 4-6. Splash  
Screen. The main screen shows a graphic of a Vilter com-  
pressor with a number of data boxes spread across the  
screen. Also on the top left are several indicators.  
% Vol:  
• Displays the position of the volume slide from 0% to  
100% .  
Anti-Recycle:  
Discharge:  
• Displays the anti-recycle time, if applicable.  
Oil Pump:  
• Displays the discharge pressure and temperature.  
Oil Filter:  
• The oil pump on a Vilter compressor often cycles on  
and off depending on differential pressure. This in-  
dicator informs the operator when the oil pump is  
running.  
• Displays the oil lter inlet pressure, oil lter outlet  
pressure, and oil differential pressure across the oil  
lter.  
Suction:  
Oil Heater:  
• Displays the suction pressure and temperature.  
Motor:  
• The oil heater often cycles on and off depending on  
the separator oil temperature. This indicator informs  
the operator when the oil heater is on.  
• Displays the motor current. When the motor VFD is  
enabled, this box will also display the motor RPM.  
Remote Lock Out:  
Separator:  
• Displays the current status of the remote lock out.  
While on, no system controller can remotely as-  
sume control of the Vission 20/20 panel and start the  
compressor.  
• Displays the temperature of the oil in the separator.  
% Cap:  
• Displays the position of the capacity slide from 0% to  
100%.  
Menu Button:  
• When pressed, navigates the operator to the menu  
screen.  
Figure 4-6. Splash Screen  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
4 – 6  
Section 5 Menu Screen  
Compressor Scheduling:  
Overview  
• Navigates to the compressor scheduling screen  
where the operator can set the scheduler to change  
the control method at settable dates and times.  
The menu screen is the launching point to every other  
section of the Vission 20/20 panel software. Every  
screen navigated to from this screen will return to the  
menu screen upon exiting, see Figure 5-1. Menu Screen.  
Compressor Sequencing:  
• Navigates to the compressor sequencing screen  
where the operator can set-up compressor to se-  
quence up to four other compressors. This is also  
sometimes known as lead-lag control.  
Navigation Buttons  
Condenser Control:  
Compressor Control:  
• Navigates to the condenser control screen where  
the operator can set up local condenser control  
parameter.  
• Navigates to the compressor control screen where  
the operator can set the various compressor control  
parameters.  
Vilter VFD:  
Alarms and Trips:  
• Not currently available.  
Service Options:  
• Navigates to the alarms and trips screen where the op-  
erator can set the various alarm and trip parameters.  
Timers:  
• Navigates to the service options screen where the  
operator can manually turn on/off digital and analog  
outputs for maintenance and diagnostics purposes.  
• Navigates to the timer screen where the operator can  
set the various time related parameters.  
Figure 5-1. Menu Screen  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
5 – 1  
Section 5 Menu Screen  
Auxiliary I/O  
Instrument Calibration:  
• Navigates to the auxiliary I/O screen where an op-  
erator can congure any auxiliary instruments or  
devices.  
• Navigates to the instrument calibration screen where  
the operator can calibrate all of the system sensors.  
Slide Calibration:  
Conguration:  
• Navigates to the slide calibration screen where the  
operator can calibrate the capacity and volume slide  
actuators.  
• Navigates to conguration screens where the initial  
system parameters are congured.  
Data Backup:  
Trend Chart:  
• Allows the operator to backup setpoints, congura-  
tion parameters, and calibration settings to a USB  
memory device. In addition, this allows the restora-  
tion of previously saved database les.  
• Navigates to the trend chart screen where the opera-  
tor can select up to four parameters for graphical his-  
torical data trending.  
Event List:  
Main:  
• Navigates to the event list screen where the operator  
can view the systems events such as trips or alarms in  
descending chronological order.  
• Navigates back to the main screen.  
Remote Oil Cooler:  
• Navigates to the Remote Oil Cooler screen where the  
operator can set up local Remote Oil Cooler control  
parameter. Menu screen will show this option in place  
of condenser control option when enabled, see Figure  
5-2. Menu Screen with Remote Oil Cooler Enabled.  
Input/Output States:  
• Allows viewing of the live data of all analog and digi-  
tal input and outputs. Also allows viewing of a “snap  
shot” of all analog and digital input and outputs at  
the time of the last compressor fault event.  
Figure 5-2. Menu Screen with Remote Oil Cooler Enabled  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
5 – 2  
Section 6 Compressor Control  
Overview  
Suction Pressure Control and Process  
Temperature Control  
The compressor control screen is where an operator  
can set the majority of the compressor settings. These  
setting dene how the compressor will operate and re-  
spond to changing loads. The compressor control screen  
consists of several screens but in order not to overwhelm  
the operator with options, many of the screens may not  
be visible.  
The Vission 20/20 uses a pulse proportional control  
method to control the compressor capacity slide valve  
in order to maintain the control setpoint. The control  
setpoint can either be process temperature control set-  
point or suction pressure control setpoint depending  
on what the operator has selected as the control mode.  
For screens, see Figure 6-1. Compressor Control Screen  
- Suction Pressure Control and Figure 6-2. Compressor  
Control Screen - Process Temperature Control.  
NOTE  
How the compressor is congured in the  
conguration screen (Section 19) will determine  
what compressor control pages are displayed.  
The proportion control uses the Interval Time Setpoint  
to dene the time the algorithm waits to read the cur-  
rent setpoint and calculates the error from the process  
control setpoint. Based on the error from setpoint, the  
algorithm calculates a pulse time in which the capacity  
slide is moved in the direction of the error. The further  
away the process variable is from the control setpoint,  
the larger the corrective pulse will be. The duration of  
the pulse is limited by the Pulse Time Setpoint. By default  
It is important to note that there isn’t one correct way to  
set these parameters. Every application is different and  
requires the operator to tune these settings to achieve  
the best operation.  
Figure 6-1. Compressor Control Screen - Suction Pressure Control  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
6 – 1  
Section 6 Compressor Control  
the maximum pulse time is the same as the interval  
time. This means that the pulse time can be 100% of the  
interval time given a near continuous movement of the  
capacity slide. Adjusting these setpoints can be useful  
in slowing down the reaction time of the compressor if  
large thermal time contents are present in the refrigera-  
tion cycle.As mentioned in the above paragraph, the dis-  
tance of the process variable from the control setpoint  
determines the size of the pulse used to move the capac-  
ity slide. This is called the proportional band and is set by  
the Proportional Setpoint. When the process variable is  
outside the proportional band, the slide will move in the  
direction of the error continuously. Increasing the size  
of the proportional band can help slow the compres-  
sors reaction by varying loads if desired, see Figure 6-3.  
Proportional Band & Setpoint.  
dead band +/- 0.4 Psig of the control setpoint. Once the  
process variable is within the dead band, the algorithm  
considers the compressor to be on setpoint. If the op-  
erator wishes the compressor to operate closer, the set-  
point can be set to a smaller percentage. However this  
will result in the capacity slide excessively moving to  
maintain the setpoint and could over heat the actuator  
or shorten the actuators operational life.  
Auto-Cycle  
The auto-cycle setpoints dene the control points in  
which the compressor will automatically cycle on and off  
when the compressor has been placed into “Auto” run  
mode. These setpoints can be “enabled” or “disabled”  
using the check box. A delay can be entered to momen-  
tarily delay the start or stop from immediately occurring  
when the setpoint is met. If a compressor shutdown is  
desired on a suction pressure drop and a manual reset  
is required, set the OFF value below the Low Suction  
The Dead Band Setpoint denes area around the control  
setpoint where the algorithm stops adjusting the capac-  
ity slide. This area is a percentage of the proportional  
band. By default the proportional band is set to 4 Psig  
and the dead band is set to 10% of 4 Psig. Making the  
Figure 6-2. Compressor Control Screen - Process Temperature Control  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
6 – 2  
Section 6 Compressor Control  
Pressure safety trip value. This will shut down the com-  
pressor and a Reset will be required to restart it.  
• Enables the Auto-cycle control. Uncheck the box to  
disable the Auto-cycle set-points.  
The auto-cycle function will operate only in local “Auto”  
mode and Direct I/O “Remote Auto” mode. If the au-  
to-cycle feature is enabled while running in any other  
remote mode, the function will simply be ignored.  
However, the Minimum slide position will continue to  
be respected in Remote “Auto” mode. If the compres-  
sor changes from a remote mode back to Local “Auto”  
mode, the auto-cycle feature will operate normally.  
Start Pressure:  
• When the suction pressure meets or exceeds this set-  
point, the compressor will start.  
Start Delay:  
• Delays the compressor from starting when the suc-  
tion pressure meets or exceeds this setpoint.  
Stop Pressure:  
NOTE  
• When the suction pressure meets or falls below this  
setpoint, the compressor will stop.  
When the Pump-down Feature is enabled, the Auto-  
cycle setpoints are automatically disabled. Pump-  
down mode will cause the compressor to cycle off  
via the Pump-down Stop Pressure setpoint, and will  
not allow the compressor to start again.  
Stop Delay:  
• Delays the compressor from stopping when the suc-  
tion pressure meets or exceeds this setpoint.  
Minimum Slide Position:  
Enable:  
• The minimum capacity slide position that the com-  
pressor is allowed to run at.  
Figure 6-3. Proportional Band & Setpoint  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
6 – 3  
Section 6 Compressor Control  
see Figure 6-6. VFD Two-Step Control Method. While  
loading; the compressor will rst move the capacity  
slide to the maximum set for step one then speed up the  
motor to its maximum speed for the same step. Once  
step one has completed, the control algorithm will again  
move the capacity slide to the maximum position and  
the maximum speed of step two. At this point the com-  
pressor would be fully loaded. Unloading occurs in the  
reverse direction. The two-step control method is not  
typical for most installations and is normally used when  
a Vilter engineer recommends it.NOTE  
Variable Frequency Drive (VFD) Settings  
Control  
The VFD page is where the operator can tune the motor  
VFD for desired operation, see Figure 6-4. Compressor  
Control Screen - VFD Settings Control. A Vilter compres-  
sor uses the variable speed of a VFD controlled motor to  
vary the amount of work or capacity of the compressor.  
The basic one step VFD control will use the capacity slide  
to control the rst half of the total available capacity and  
the motor speed to control the second half of the total  
available capacity, see Figure 6-5. VFD One-Step Control  
Method. For example, if the compressor needs to load  
to 100% of its capacity. The control algorithm will rst  
move the capacity slide to its maximum position, then  
the motor speed will ramp up to its maximum speed.  
In the unloading direction, the motor speed will ramp  
down to its minimum speed, then the capacity slide will  
move to its minimum position.  
VFD installation is not covered in this manual. A VFD  
that is not properly installed and congured has the  
potential of causing intermittent and dangerous  
problems. Please consult your VFD manual.  
1 Step VFD Control:  
• Enables the rst step in the VFD control algorithm.  
This check box is not deselectable by the operator.  
The two-step control method works much like the one-  
step method but divides the control into four sections,  
Capacity Slide Position:  
Figure 6-4. Compressor Control Screen - VFD Settings Control  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
6 – 4  
Section 6 Compressor Control  
• Denes the minimum and maximum positions for  
the capacity slide. While in 1 step control these values  
should be 0% for minimum and 100% for maximum.  
setpoint and the process variable (SP - PV error).  
This is a unit-less quantity and is used for coarse ad-  
justment. This setpoint should be set to the lowest  
value that gives adequate control system response.  
Increasing the proportional setting increases the  
control system’s sensitivity to small process uctua-  
tions and the tendency to hunt.  
VFD Speed:  
• Denes the minimum and maximum speed for the  
motor speed. While in 1 step control these values  
should reect the full range of the VFD.  
2 Step VFD Control:  
I = Integral (reset) setpoint:  
• Enables the second step in the VFD control algorithm.  
Capacity Slide Position:  
• Used to adjust the capacity control action, integrating  
the error over time, to account for a small error that  
has persisted for a long time. This quantity is used for  
ne adjustment. This setpoint is used to smooth out  
process variations. This setpoint should be set high  
enough to prevent hunting but low enough to pre-  
vent control system overshoot.  
• Denes the minimum and maximum position of the  
capacity slide in the 2 step VFD control.  
VFD Speed:  
• Denes the minimum and maximum speed for the  
motor in the 2 step VFD control.  
D = Derivative (rate) setpoint:  
P = Proportional (gain) setpoint:  
• Used to adjust the capacity control action, account-  
ing for how fast the error is changing, positively or  
negatively. A standard PID loop variable, it is not used  
for our applications.  
• Used to adjust the motor speed action in direct  
proportion to the difference between the control  
Figure 6-5. VFD One-Step Control Method  
Figure 6-6. VFD Two-Step Control Method  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
6 – 5  
Section 6 Compressor Control  
prevented from shutting down prematurely via the  
Auto-cycle Stop setpoint by automatically ignoring  
the Auto-cycle feature.  
Pumpdown Control  
NOTE  
• The compressor will be placed into “Stop” mode af-  
ter the suction pressure is equal to, or goes below the  
Pumpdown Stop Pressure.  
For use of compressor control screen - page 4, see  
Cool Compression Control in Section 25.  
The Pumpdown Control denes a method of “pump-  
ing” down a chiller, which is to draw off refrigerant  
from the chiller. This feature can be enabled or disabled  
from this page, see Figure 6-7. Compressor Control  
Screen - Pumpdown/Pulldown Control. If Pumpdown is  
enabled, this feature will only function when the com-  
pressor is running in local Auto Mode and Control Mode  
Congured is Suction Pressure.  
Pumpdown:  
• This checkbox enables the Pumpdown feature. If  
this box is unchecked, Pumpdown setpoints are ig-  
nored and the user is not allowed to edit Pumpdown  
setpoints.  
Stop Pressure:  
• This setpoint denes the suction pressure value at  
which the compressor will cycle off. Normally, this  
setpoint is set below the Suction Pressure Auto-cycle  
Stop Pressure setpoint.  
If Pumpdown Feature is enabled, then;  
• The Auto-cycle functionality is ignored. Pumpdown  
mode will cause the compressor to cycle off via the  
Pumpdown Stop Pressure setpoint. Normally, the  
Pumpdown Stop Pressure setpoint will be set lower  
than the Auto-cycle Stop setpoint. Therefore, as the  
suction pressure is pulled down, the compressor is  
Stop Delay:  
• This setpoint delays the compressor from stopping  
when the suction pressure is equal to or less than the  
Figure 6-7. Compressor Control Screen - Pumpdown/Pulldown Control  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
6 – 6  
Section 6 Compressor Control  
Stop Pressure.  
• Number of steps = delta 60 psig change * 1 step/5  
psig = 12 steps.  
Min Slide Position:  
• Delay per Step = 48 hours / 12 steps = 4 hours/step.  
• The minimum capacity slide is the setpoint that  
the compressor is allowed to run at. By forcing the  
compressor capacity to operate at a value above  
minimum, we insure that the suction pressure will be  
pulled down to the Stop Pressure setpoint.  
• So for the rst 4 hours, the compressor runs at 80  
psig.  
• Next 4 hours @ 75 psig  
• Next 4 hours @ 70 psig  
• And so forth.  
Pumpdown Operation (Run/Stop):  
• This button starts/stops the Pumpdown opera-  
tion. This button is active only when compressor is  
in local Auto mode and Control Mode Congured is  
Suction Pressure. This button will display “Run” when  
Pumpdown operation has not started or stopped,  
while button will display “Stop” when Pumpdown op-  
eration is running.  
After the 12th step (running at 25 psig), 48 hours will  
have elapsed, and the new setpoint becomes 20 psig,  
achieving the 20 psig setpoint after 48 hours. After the  
pulldown setpoint is equal to or is less than the control  
setpoint, the pulldown feature will disable itself.  
When Pumpdown feature is enabled, Pulldown check-  
box is automatically grayed out. Similarly when Pulldown  
feature is enabled, Pumpdown checkbox is automatically  
grayed out and hence, the user will not be able to oper-  
ate Pumpdown feature. This is done to keep Pumpdown  
and Pulldown features mutually exclusive.  
Pulldown:  
• This checkbox enables the Pulldown feature. If this  
box is unchecked, Pulldown setpoints are ignored  
and the operator is not allowed to edit Pulldown  
setpoints.  
Initiate Pulldown at Next Start:  
Pulldown Control  
• This checkbox when enabled, turns on the Pulldown  
process at the next start cycle, Pulldown operation  
will work in the following manners:  
The Pulldown Control denes a method of slowly pull-  
ing the suction pressure down from a high value. This is  
sometimes required on systems that have liquid recircu-  
lation systems or on new building to prevent structural  
damage by limiting the rate at which to build is cooled.  
• Pulldown only works when Control mode is  
Suction Pressure 1.  
• If not started in Suction Pressure 1 then  
Pulldown process will not run until stopped and  
restarted in Suction Pressure 1.  
This feature can be enabled or disabled from this page,  
see Figure 6-7. Compressor Control Screen - Pumpdown/  
Pulldown Control. If Pulldown is enabled, this feature will  
only function when the compressor is running in local  
Auto, Auto Sequencing mode and the Control mode is  
Suction Pressure 1.  
• If started in Suction Pressure 1 and changed  
after start, then Pulldown process will be sus-  
pended and restart once Control mode is  
changed back to Suction Pressure 1.  
The Pulldown feature provides a method to slowly pull  
the suction pressure down to operating conditions. The  
pulldown method used is to step the suction pressure  
down over a dened time interval.  
Step Pressure:  
• This setpoint denes the step decrements at which  
the suction pressure value will be controlled at.  
Delay Per Step:  
• This setpoint denes the time increment at which the  
Example:  
compressor will be controlled at each step.  
Assume the suction pressure is at 85 psig and the set-  
point we want to get to is 20 psig. The operator wants to  
allow 48 hours of pulldown time. Pick a reasonable step  
pressure of 5 psig for every step. This denes a change of  
(80 – 20 = 60) psig.  
Stop Pressure:  
• This setpoint denes the suction pressure value at  
which Pulldown operation will get completed. When  
suction pressure value is equal to or goes below  
this setpoint, Pulldown feature disables itself. Also  
“Pulldown” and “Initiate Pulldown at Next Start”  
checkboxes will be automatically deselected as nor-  
mally this is one time use feature.  
• Note: First step is applied immediately. So rst step  
starts at (85 – 5 = 80) psig  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
6 – 7  
Section 6 Compressor Control  
Auto Cycle Differential:  
operator can also switch from setpoint 1 and setpoint 2  
for each control method. What is available in this drop-  
down box is dependent on the number and type of con-  
trol selected in the conguration screen, see Figure 6-8.  
Compress Control Screen - Misc 1 (Control Mode).  
• This setpoint denes the offset pressure values for  
Auto Cycle Start Pressure and Stop Pressure from the  
Suction Pressure setpoint. Auto Cycle Start Pressure  
setpoint will be Suction Pressure setpoint increment-  
ed by this setpoint pressure value, while Auto Cycle  
Stop Pressure value will be Suction Pressure setpoint  
decremented by this setpoint pressure value.  
Stop Load and Force Unload  
When Pulldown feature is enabled, Pumpdown checkbox  
is automatically grayed out. Similarly when Pumpdown  
feature is enabled, Pulldown checkbox is automatically  
grayed out and hence, the user will not be able to op-  
erate Pulldown feature. This is done to keep Pulldown &  
Pumpdown features mutually exclusive.  
The stop load and force unload feature’s primary pur-  
pose is to attempt to prevent the compressor from  
tripping off due to particular instrument reading. For  
example, if the suction pressure drops too low, the com-  
pressor will trip off for safety reasons. However, the stop  
load & force unload algorithm recognizes a potential trip  
and either stops the compressor from loading up or even  
unloads the compressor to prevent the trip.  
Control Mode  
This drop down box gives the operator the ability to  
change the type of control mode such as suction pres-  
sure control or process temperature control. The  
Stop load:  
• When this value is reached, the capacity slide will not  
Figure 6-8. Compressor Control Screen - Misc. 1 (Control Mode)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
6 – 8  
Section 6 Compressor Control  
advance in any condition.  
Force Unload:  
Capacity Slide Triggered Outputs  
The Vission 20/20 offers two digital outputs that can  
be triggered at a specied capacity slide position. By  
default, the outputs are preselected for economizer  
and hot gas bypass. However, these preselected out-  
puts are customizable by the operator, see Figure 6-9.  
Compressor Control Screen - Misc. 2 (Economizer & Hot  
Gas Bypass Control).  
• When this value is reached, the capacity slide posi-  
tion will decrease until the variable reading is below  
this value.  
High Motor Amps:  
• Motor current values for stop load and force unload.  
High Discharge Pressure:  
• Discharge pressure value for stop load and force  
unload.  
Slide Valve Setpoint:  
Low Suction Pressure:  
• Operator editable labels for the each output. Only  
Economizer Port 2 Label is non-editable.  
• Suction pressure values for stop load and force unload  
High Discharge Superheat:  
Slide %:  
• Indicates the capacity slide position where the digital  
output is triggered.  
• Discharge temperature superheat values for stop  
load and force unload. This is only used for Cool  
Compression.  
State Below Setpoint:  
• Denes the state of the digital output when the slide  
Figure 6-9. Compressor Control Screen - Misc. 2 (Economizer & Hot Gas Bypass Control)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
6 – 9  
Section 6 Compressor Control  
position is below the “Slide %” setpoint. The operator  
can choose between “N.O.” or “N.C.”. This setpoint  
is not available for Economizer Port 2, so Economizer  
Port 2 follows the setpoint of Economizer Port 1.  
setpoint. This advanced feature of the Vission 20/20  
closely monitors the rate of change of the process vari-  
able and compares it to the control setpoint. If the pro-  
cess variable is changing in the direction of the control  
setpoint at the specied rate or greater, then the normal  
command to move the capacity slide is interrupted. The  
rate is calculated between time intervals set in the pro-  
portional control section of this screen.  
Active:  
• Check box to enable the digital output. There is no  
check box for enabling Economizer Port 2 digital  
output. Economizer Port 2 digital output is enabled  
when Compressor type selected from conguration  
screen is “VSM7” and Economizer Port 1 digital out-  
put is enabled.  
Enable Load Anticipation Algorithm:  
• Allows the operator to choose if the load anticipation  
algorithm runs.  
Rate Dead Band:  
Volume Slide Position Offset  
• Denes the rate at which the capacity slide move-  
ment will be interrupted. This value is an absolute val-  
ue of the process variable. For example, the default  
value is 0.25. If the control mode is suction pressure,  
then this value is 0.25 Psig or if process temperature  
is the control mode then the value would be 0.25°F.  
These setpoints offer the ability to alter the Volume po-  
sition table to take advantage of potential energy sav-  
ings. Since the volume position is a function of the ca-  
pacity position, the offset to the volume is based on the  
position of the capacity slide. The volume offset can be  
applied to the entire capacity slide range or just a por-  
tion using the Capacity Range minimum and maximum  
setpoints.  
Volume Slide Adjustment %:  
• The value in percentage of the volume slide offset.  
Capacity Range:  
• Denes the range that the volume position slide off-  
set will be applied.  
Soft Load  
This setpoint is used to slow the loading of the compres-  
sor. In some refrigeration systems, a loading compres-  
sor can have dramatic effects on the system parameters.  
This setpoint allows an operator to reduce the continu-  
ous load pulse as dened in the proportional control sec-  
tion to a percent duty cycle.  
Soft load %:  
• Denes the duty cycle of the continuous load pulse.  
At 100%, the continuous pulse will truly be continu-  
ous. At 50%, the continuous pulse would be reduced  
to half time on and half time off in the time interval  
dened in the proportional control section.  
Load Anticipating  
The purpose of the load anticipating algorithm is to re-  
duce the amount of overshoot of the capacity slide posi-  
tion while the compressor attempts to meet the control  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
6 – 10  
Section 6 Compressor Control  
Oil Control  
Liquid Injection  
These setpoints determine how the Vission 20/20 will  
manage the oil of the compressor, see Figure 6-10.  
Compressor Control Screen - Oil Control & Liquid  
Injection Control.  
The setpoints is this section are to control the behavior  
of the liquid refrigerant injected into the compressor for  
oil cooling purposes. The liquid injection solenoid con-  
trol is based off of discharge temperature whether the  
compressor uses just an injection solenoid or a motor-  
ized valve in conjunction with the solenoid.  
Oil Pump Press Restart Ratio:  
Liquid Injection Solenoid Control ONLY  
• The on and off setpoints dene when the oil pump  
will cycle on and off if the oil pump is selected to cycle  
from the conguration screen.  
• When using only the liquid injection solenoid, the so-  
lenoid is activated once the value of discharge tem-  
perature meets or exceeds the value of “Liquid inj.  
Setpoint 1” and the value of oil separator tempera-  
ture meets or exceeds the value of “Oil Sep. Temp.  
Override”. The injection solenoid will deactivate if  
either of setpoints are not met. This will prevent situ-  
ations where the discharge temperature may rise  
quickly, but the oil temperature is still very cold. By  
preventing the liquid injection solenoid from turning  
on at this point, the oil separator will not be subjected  
to additional liquid refrigerant, that would cool the oil  
Oil Separator Heater Temp:  
• When the oil temperature falls below this setpoint  
the oil heater will turn on. Note, there is a 5°F differen-  
tial associated with this setpoint. For example, when  
set at 100°F, the heater will turn on at 95°F and off at  
105°F.  
Figure 6-10. Compressor Control Screen - Oil Control & Liquid Injection Control  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
6 – 11  
even further.  
Oil Sep. Temp. Override:  
Liquid Injection Control using a 4-20ma motorized valve.  
• Denes the temperature the oil must reach before the  
liquid injection solenoid is allowed to be activated.  
• When a motorized valve is used to control the amount  
of liquid being injected into the compressor the pre-  
viously mentioned setpoints have a slightly different  
function. The Oil Sep. Temp. Override is still used in  
controlling the injection solenoid, however the Liquid  
Inj. Setpoint 1 is now used as the target temperature  
for the PID Algorithm that controls the position of  
the motorized valve. The algorithm compares the  
actual discharge temperature against the Liquid Inj.  
Setpoint 1. The difference between these is the error.  
The PID algorithm tries to drive the error to “zero” by  
moving the positioning valve to allow more or less  
liquid refrigerant to be injected into the compressor.  
P = Proportional (Gain):  
• Used to adjust the positioning valve in direct propor-  
tion to the difference between the control setpoint  
and the discharge temperature (SetPt - DT = error).  
The proportional term is a unit-less quantity and is  
used for coarse adjustment. This setpoint should be  
set to the lowest value that gives adequate response  
to the control system. Increasing the proportional  
setting increases the control system’s sensitivity to  
small discharge temperature uctuations and the  
tendency to hunt.  
I = Integral (reset):  
• PID algorithm can be notoriously hard to tune. As  
a result the Vission 20/20 offers a couple of addi-  
tional features to help control wild uctuations in  
oil temperatures that could result in the compres-  
sor tripping off. The operator can choose to enable  
the minimum value position that automatically sets  
the liquid injection motorized value to the specied  
value whenever the discharge temperature has fallen  
below the Liquid inj. Setpoint 1. This feature nearly  
eliminates the overshoot of the PID in the downward  
direction and reduces the chance of the compressor  
tripping off due to low oil temperature. The operator  
can also choose to use an average of the discharge  
temperature and the oil manifold temperature as the  
control variable. The discharge temperature can vary  
quite drastically forcing the PID algorithm to drasti-  
cally adjust the motorized value. By averaging the  
more stable oil manifold temperature and discharge  
temperature, the control variable stabilizes and the  
PID is more easily tuned.  
• This parameter integrates the error over time, to ac-  
count for a small error that has persisted for a long  
time. This quantity is used for ne adjustment. This  
setpoint is used to smooth out discharge tempera-  
ture variations. This setpoint should be set high  
enough to prevent hunting but not too high or it will  
cause control system overshoot.  
D = Derivative (rate):  
• This parameter accounts for how fast the error is  
changing, positively or negatively.  
Minimum Valve Open %:  
• When enabled, this is the valve position used when-  
ever the control variable drops below Liquid inj.  
Setpoint 1. Use only if the compressor is tripping off  
for low oil temperature due to large overshoots and  
all other tuning methods have failed.  
Avg. with Oil Manifold Temperature:  
• When enabled, averages the Oil manifold tempera-  
ture and the discharge temperature. This creates  
a more stable control variable and should result in  
more stable control.  
• Please note that as stated above, PID algorithms can  
be difcult to tune and there is no one set of PID val-  
ues that will work. The work required for a compres-  
sor to meet the requirement of its installation vary  
greatly and therefore the amount of heat transfered  
to the oil varies just as greatly. We recommend the  
operator consult PID tuning guides available from  
many different source before attempting to tune this  
PID.  
Liquid Inj. Setpoint 1:  
• Setpoint at which the liquid solenoid will activate if in  
solenoid control or if the setting for the control vari-  
able for the PID is in liquid motorized value control.  
Liquid Inj. Setpoint 2:  
• Not yet available  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
6 – 12  
Section 7 • Alarms and Trips  
side tabs in the input/output screens and are very useful  
as a troubleshooting tool for the operator.  
Overview  
The Alarms and Trips screen allows the operator to view  
and adjust settings for compressor safety and alarm set-  
tings. For Alarms and Trips Screen Pages refer to Figures  
7-1, 7-2, 7-3 and 7-4.  
The Vission 20/20 uses Warnings as a way to notify the  
operator of parameters that may inhibit the compressor  
when started. Warnings are monitored only when com-  
pressor is not running. Warnings are always displayed  
as a orange banner on bottom status bar. Warnings  
uses the alarm setpoint for detection and message. All  
warnings messages present can be seen collectively in a  
pop-up window. This pop-up is displayed when warning  
condition is present and bottom status bar used for dis-  
playing warnings is pressed.  
Vission 20/20 uses Alarms as a way to notify the opera-  
tor of running parameters that if left unchecked could  
result in the compressor shutting down due to a trip.  
Trips are the conditions that exceed the safety limits of  
the compressor or refrigeration system and stops the  
compressor. Trips are always displayed as a red banner  
and alarms are yellow banners on the top and bottoms  
status bars.  
Alarms and Trips Setpoints  
Alarms and trip conditions are also logged to provide  
an operational history for the operator. Both alarms  
and trips will be logged in the event list accessible from  
the menu screen. Trips also trigger the input/output  
screen to take a snapshot of all input and output values  
as freeze screen. The freeze screens are available as left  
Use Figure 7-1. Alarms and Trips Screen - Page 1.  
Low Suction Pressure (Alarm & Trip):  
• This is the low suction pressure safety. This safety  
is active in both temperature and pressure control  
Figure 7-1. Alarms and Trips Screen - Page 1  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
7 – 1  
Section 7 • Alarms and Trips  
modes. An alarm or trip will be activated if the suc-  
tion pressure falls below the setpoint values.  
Use Figure 7-2. Alarms and Trips Screen - Page 2.  
Low Suction Temperature (Alarm & Trip):  
High Discharge Pressure (Alarm & Trip):  
• This is the low suction temperature safety. The alarm  
or trip will be activated if the suction temperature  
drops below the setpoint value.  
• This is the high discharge pressure safety. The alarm  
or trip will be activated if the discharge pressure rises  
above the setpoint value.  
High Discharge Temperature (Alarm & Trip):  
High Process Temperature (Alarm only)  
• This is the high discharge temperature safety. The  
alarm or trip will be activated if the discharge tem-  
perature rises above the setpoint value.  
• This alarm is active when the process temperature  
is at or above the setpoint value. There is no trip  
setpoint.  
Low Oil Separator Start Temperature (Alarm & Trip):  
Low Process Temperature (Alarm & Trip):  
• This is the starting low oil separator temperature  
safety. The compressor is prevented from starting  
or running if the oil in the separator is below the  
alarm value. After a time delay (setting of the Oil  
Separator Temperature Safety Changeover timer),  
this safety is deactivated and the Low Oil Separator  
Run Temperature alarm and safety setpoints become  
active.  
• This is the low control temperature safety. This safety  
is active when process temperature control has been  
selected in the Control Mode dropdown selection  
found in the Compressor Control screen. An alarm or  
trip will be activated on a drop in process tempera-  
ture below the setpoint value.  
Low Oil Separator Run Temperature (Alarm & Trip):  
• This is the running low oil separator temperature  
Figure 7-2. Alarms and Trips Screen - Page 1 as Level 2 User  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
7 – 2  
Section 7 • Alarms and Trips  
safety. After a time delay, (setting of the Oil Separator  
Temperature Safety Changeover timer), the Low Oil  
Separator Start Temperature is bypassed and Low  
Oil Separator Run Temperature alarm and safety set-  
points become active. The alarm or trip will be acti-  
vated if the oil temperature in the separator drops  
below the setpoint value.  
monitor is enabled in the conguration screen. The  
compressor is prevented from starting or running if  
the superheat is above the setpoint value. The warn-  
ing or trip will be activated if the superheat tem-  
perature rises above the setpoint value. There is no  
ALARM setpoint.  
High Superheat Run Temperature (Alarm & Trip):  
Low Oil Injection Temperature (Alarm & Trip):  
• This is the running high discharge superheat tem-  
perature safety. This safety is active when super-  
heat monitor is enabled in the conguration screen.  
After a time delay, (setting of the High Superheat  
Temperature Safety Changeover timer), the High  
Superheat Start Offset Temperature is bypassed and  
High Superheat Run Temperature alarm and safety  
setpoints become active. The alarm or trip will be ac-  
tivated if the superheat temperature rises above the  
setpoint value.  
• This is the low oil injection safety. The alarm and  
trip setpoints are bypassed at start for a time pe-  
riod (setting of the Oil Injection Temperature Safety  
Changeover timer). The alarm and trip will be acti-  
vated after the time delay has expired.  
High Oil Injection Temperature (Alarm & Trip):  
• This is the high oil injection temperature safety. The  
alarm or trip will be activated if the oil injection tem-  
perature rises above the setpoint value.  
High Superheat Start Offset Temperature (Trip Only):  
High Superheat Start Temperature (Trip Only):  
• This is the starting high discharge superheat tem-  
perature safety. This safety is active when super-  
heat monitor is enabled in the conguration screen.  
• This is the starting high discharge superheat tem-  
perature safety. This safety is active when superheat  
Figure 7-2. Alarms and Trips Screen - Page 2  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
7 – 3  
Section 7 • Alarms and Trips  
After a time delay, (setting of the High Superheat  
Temperature Safety Changeover timer), this safety is  
deactivatedandtheHighSuperheatRunTemperature  
alarm and safety setpoints become active. The trip  
will be activated if the superheat temperature from  
start rises above the superheat temperature plus the  
setpoint value. There is no ALARM setpoint.  
zeroed prelube oil pressure difference value is shown  
on main screen during start sequence. The prelube  
oil pressure is redened as manifold pressure minus  
suction pressure after the start sequence. This safety  
insures adequate lubrication of the compressor at  
startup.  
Low (Run) Oil Pressure (Alarm & Trip):  
• This is the running oil pressure safety. The normal  
alarm and trip setpoints of this safety are “messaged”  
as soon as the compressor starts. The “Pre lube Oil  
Pressure” Alarm and Trip setpoints are substituted  
into this safety setpoints for a time of the “Oil Pressure  
Bypass” timer (typically 60 seconds). After this timer  
expires, then the setpoints return back to the normal  
settings. The action of adjusting the setpoints for  
about a minute allows the (Run) Oil Pressure to build  
up to normal running pressures after the compressor  
starts. After the Oil Pressure Bypass Timer has ex-  
pired, the Oil Pressure must be above the normal set-  
points, or else an Alarm or Trip will occur. An alarm or  
trip will be active if the oil pressure drops below the  
Use Figure 7-3. Alarms and Trips Screen - Page 3.  
Prelube Oil Pressure (Alarm & Trip):  
• This is the prelube oil pump failure safety. If prelube  
oil pressure does not rise by prelube alarm setting  
congured with in prelube oil pressure trials of pre-  
lube oil pressure monitor time for a minimum time  
set at Minimum Comp. Prelube Time, then the start  
sequence will be aborted. The prelube oil pressure  
trials, prelube oil pressure monitor time, Minimum  
Comp. Prelube Time is set on the Timer screen. The  
prelube oil pressure is dened as manifold pressure  
minus discharge pressure during the start sequence,  
Figure 7-2. Alarms and Trips Screen - Page 3  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
7 – 4  
Section 7 • Alarms and Trips  
normal setpoint values after the Oil Pressure Bypass  
timer has expired. This time limit is set on the Timer  
menu screen. Run oil pressure is dened as manifold  
pressure minus suction pressure.  
Safety Failure Messages  
Low Suction Pressure Trip  
• This message will appear when the suction pressure  
falls below the safety setting of the Low Suction Pres-  
sure Trip Setpoint No.1 or No. 2.  
High Filter Differential Pressure Start (Alarm & Trip):  
• This safety allows a higher than normal lter differ-  
ential pressure to exist during the rst minute after  
a compressor starts. This allows time for cold oil that  
is present in the oil piping and lters to be passed  
and replaced with warmer oil. After a time delay (set-  
ting of the Filter Diff Pressure Safety Changeover  
timer), this safety is deactivated and the High Filter  
Differential Pressure-Run alarm and safety setpoints  
become active. An alarm or trip will be active if the  
lter differential (= Filter Inlet Pressure minus Filter  
Outlet Pressure) exceeds the setpoint value.  
High Discharge Pressure Trip  
• This message will appear when the discharge pres-  
sure exceeds the safety setting of the Hi Dsch Press  
Trip Setpoint No. 1 or No. 2.  
Low Suction Temp Trip  
• This message will appear when the suction tempera-  
ture falls below the safety setting of the Low Suction  
Temperature Trip setpoint.  
High Discharge Temp Trip  
High Filter Differential Pressure Run (Alarm & Trip):  
• This message will appear when the discharge tem-  
perature rises above the safety setting of the High  
Discharge Temperature Trip setpoint.  
• This safety setpoint is active when the compres-  
sor has started and the Filter Diff Pressure Safety  
Changeover timer has timed out. An alarm or trip will  
be active if the lter differential (= Filter Inlet Pressure  
minus Filter Outlet Pressure) exceeds by the setpoint  
value.  
Low Oil Separator Temp Trip  
• This message will appear when the Oil Separator  
Temp is below the Low Oil Separator Start Temp Trip  
setpoint. In addition this message will appear after  
the Oil Separator Temp Safety Changeover timer  
times out and the Oil Separator temperature fails to  
rise above the Low Oil Separator Start Temp Reset af-  
ter the compressor is started.  
High Motor Amps:  
• This safety setpoint is active after the Volume  
Decrease At Start Timer expires (this timer is not set-  
table by the operator). A trip will occur if the motor  
amperage exceeds the safety setpoint value. For a  
motor with a 1.15 Service Factor, the trip setpoint  
should be set at 125% of the motor full load amper-  
age value. The alarm setpoint should be set at 120%  
of the motor full load amperage value.  
Low Oil Separator Temp Trip  
• This message will appear when the Oil Separator  
Temp is below the Low Oil Separator Run Temp  
Reset setpoint after the Oil Separator Temp Safety  
Changeover timer times out.  
Low Run Pressure Ratio (Alarm & Trip):  
• This is the low run pressure ratio safety. This safety is  
active when Cool Compression is enabled in the con-  
guration screen. An alarm or trip will be active if the  
pressure ratio drops below the setpoint values after  
the Low Pressure Ratio Bypass timer has expired.  
Low Process Temp Trip  
• This message will appear when the Process Control  
Temperature falls below the safety setting of the Lo  
Control Temperature Trip Setpoint.  
Prelube Oil Pump Inhibit  
• This message will appear when the Prelube Oil  
Pressure (Manifold minus Discharge) has remained  
below the Prelube Oil Pressure Reset setpoint. The  
oil pump will try to generate “prelube pressure” for  
the time period of the Low Oil Pressure Safety Bypass  
timer setting.  
Compressor Inhibits  
The Vission 20/20 uses several start inhibits to prevent  
the compressor from starting to protect the compres-  
sor and the refrigeration system. While starting the  
compressor, the inhibits are checked rst before the oil  
pump is started or the motor is started. The failed starts  
due to an inhibit does not count toward any of the anti-  
recycle timers including hot starts. The Inhibits uses the  
alarm setpoint to trigger an aborted start and message.  
Low Oil Pressure Trip  
• This message will appear when the Running Oil  
Pressure (Manifold minus Suction) has remained be-  
low the low Oil Pressure Reset setpoint when the Oil  
Pressure Bypass Start timer times out. This message  
will also appear when the Running Oil Pressure falls  
below the Low Oil Pressure trip setpoint after the Low  
All inhibits will be logged in the event list.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
7 – 5  
Section 7 • Alarms and Trips  
Oil Pressure Safety Bypass timer times out.  
Low Oil Injection Temp Trip  
Compressor Warnings  
High Level Shutdown Warning  
• This message will appear when High Level Shutdown  
switch is Active Low.  
• This message will appear when the Oil Injection tem-  
peraturefallsbelowtheLowOilInjectionTemperature  
trip setpoint. This message will also appear when the  
Oil Injection temperature fails to rise above the Low  
Oil Injection Temperature reset setpoint after the  
Low Oil Injection Temp Bypass timer times out.  
Low Process Temp Warning  
• This message will appear when Process Control  
Temperature falls below the safety setting of the  
Low Process Temperature Alarm setpoint.  
High Oil Injection Temp Trip  
High Discharge Pressure Warning  
• This message will appear when the Oil Injection  
temperature rises above the High Oil Injection  
Temperature trip setpoint.  
• This message will appear when the Discharge  
Pressure exceeds the safety setting of the High  
Discharge Pressure Alarm setpoint.  
High Filter Differential Trip  
High Discharge Temp Warning  
• This message will appear if the Filter Differential  
Pressure rises above the High Fltr Diff Press – Start  
setpoint before the Filter Differential Pressure Safety  
Changeover timer times out.  
• This message will appear when the Discharge  
Temperature exceeds the safety setting of the High  
Discharge Temperature Alarm setpoint.  
Low Suction Pressure Warning  
High Filter Differential Trip  
• This message will appear when Suction Pressure falls  
below the safety setting of Low Suction Pressure  
Alarm setpoint.  
• This message will appear if the Filter Differential  
pressure rises above the High Fltr Diff Press Run  
setpoint after the Filter Differential Pressure Safety  
Changeover timer times out.  
Low Suction Temp Warning  
• This message will appear when Suction Temperature  
falls below the safety setting of Low Suction  
Temperature Alarm setpoint.  
High Motor Current Trip  
• This message will appear if the motor amperage rises  
above the Hi Motor Amps trip setpoint.  
Low Oil Separator Start Temp Warning  
Compressor Interlock Trip  
• This message will appear when the Oil Separator  
Temperature falls below the safety setting of the Low  
Oil Separator Start Temp Alarm setpoint.  
• This message will appear if the Motor Auxiliary con-  
tact fails to close before the Compressor Starter  
Auxiliary Contact Bypass timer times out. Refer to  
wiring diagram.  
High Oil Injection Temp Warning  
• This message will appear when the Oil Injection  
Temperature exceeds the safety setting of the High  
Oil Injection Temp Alarm setpoint.  
High Level Shutdown Trip  
• This message will appear when power is removed  
from the input module that is designated as “Auxiliary  
#1 Safety” Refer to wiring diagram.  
High Filter Differential Warning  
• This message will appear when the Filter Differential  
Pressure exceeds the safety setting of the High Filter  
Diff Start Pressure Alarm setpoint.  
False Start  
• This message appears when the compressor stops  
and the motor auxiliary contact fails to open. The  
message will also appear if the compressor shuts  
down and the amperage is 20% of the maximum amp  
setting, indicating that the starter is still energized.  
High Superheat Temp Warning  
• This message will appear when the Discharge  
Superheat Temperature exceeds the safety setting of  
the High Superheat Start Temp Trip setpoint.  
Low Oil Level Trip  
Analog Aux in 1-16 Warning  
• This message appears when power is removed from  
the designated input module, refer to wiring dia-  
gram. This safety will activate only after the oil level  
has been low for the time period dened by the “Low  
Oil Separator Safety Trip Delay” timer.  
• This message will appear when the Analog Aux in  
1-16 exceeds / falls below the safety setting of the  
High / Low Alarm setpoint.  
Digital Aux in 1-16 Warning  
• This message will appear when the Digital Aux in 1-8  
is Active High / Low.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
7 – 6  
Section 8 Timers  
amount of time.  
Timers:  
Overview  
The timers screen allows the operator to view and adjust  
timer settings associated with compressor operation.  
There are different types of timers that the operator  
should be aware of listed below. For Timer Screen Pages,  
see Figures 8-1 and 8-2.  
• A general timer requiring the time to expire before  
the listed event can occur.  
Timer Setpoints  
Use Figure 8-1. Timers Screen - Page 1.  
Capacity Increase Start Delay:  
Changeover:  
• At compressor startup, the capacity slide position is  
held at minimum position for this time period. This is  
to allow compressor and system conditions to stabi-  
lize. After the timer expires, the slide is free to move  
in accordance to the system demands.  
• The changeover timers will change from one type  
control to another once the compressor has started  
and then the timer has expired.  
Bypass:  
Minimum Compressor Pre-lube Time:  
The bypass timers prevent certain alarm and trip  
checks from occurring until the compressor has  
started and then the time has expired.  
• This is the length of time the oil pump will run, after  
establishing Pre-lube Oil Pressure, to prime the oil cir-  
cuit before starting the compressor.  
Delays:  
• Delays require the condition to occur for the specied  
Figure 8-1. Timers Screen - Page 1  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
8 – 1  
Section 8 Timers  
Low Oil Pressure Safety Bypass:  
Low Oil Separator Temperature Safety Changeover:  
• This is the length of time in which the normal Low  
(Run) Oil Pressure setpoints will be adjusted by the  
values of the Pre-lube Oil Pressure setpoints. After  
the timer has expired, the normal Low Oil Pressure  
setpoints become active.  
• This timer allows Low Oil Separator Start Temperature  
safety setpoint to protect the compressor against  
cold oil during starting. After the timer has expired,  
the Low Oil Separator Run Temperature is then active.  
Low Oil Injection Safety Bypass:  
Prelube Oil Pressure Monitor Time:  
• This timer bypasses the Low Oil Injection Temperature  
Safety setpoint during start-up, to allow any cold oil in  
the oil lines and lter to pass. After the timer expires,  
the Low Oil Injection Temperature safety is active.  
• The Prelube Oil Pressure Monitor time denes timer  
to monitor raise in prelube oil pressure against pre-  
lube oil pressure alarm settings. If prelube oil pres-  
sure is unable to raise by oil pressure alarm settings  
in Prelube oil pressure monitor time then it restarts  
oil pump.  
Use Figure 8-2. Timers Screen - Page 2.  
Max Restart After Power Failure:  
Prelube Oil Pressure Monitor Trials:  
• This timer forces the compressor to wait for the set  
time period after a power failure and the panels re-  
starts before it can be started automatically. By stag-  
gering the time settings of this timer between other  
compressor panels, the compressors can be allowed  
to start automatically, one at a time, after a power  
failure. This will prevent excessive load demand on  
the power system that could occur if all of the com-  
pressor equipment were to start at the same time.  
The Power-up Auto Re-Start [x]Enable option must  
be selected on the Conguration screen for this op-  
tion to be active.  
• The Prelube oil pressure monitor trials denes  
maximum number of retries to monitor prelube oil  
pressure.  
Prelube Oil Pressure Safety Changeover:  
• After compressor starts, drop in prelube oil pressure  
is monitored for prelube oil pressure safety change-  
over time. If prelube oil pressure drops with in pre-  
lube oil pressure safety changeover time then com-  
pressor trips on prelube oil pressure trip.  
High Filter Differential Pressure Safety Changeover:  
• This timer bypasses the High Filter Differential Run  
Pressure safety settings when the compressor starts.  
It denes how long the High Filter Differential Start  
Pressure setpoints will be active after the compres-  
sor starts. After the timer has expired, then the High  
Filter Differential Run Pressure safety setpoints will be  
active.  
Hot Starts per Hour:  
• This counter counts compressor starts. After every  
start, a one-hour timer is reset and starts timing. If  
the timer times out, the hot starts counter is reset.  
When the counter reaches its preset value, it will not  
allow another compressor start until the one-hour  
timer times out and resets the counter. The hot starts  
counter, therefore, will be reset when the time be-  
tween compressor starts total one hour. This coun-  
ter allows repetitive compressor starts, but once the  
counter has reached its set point, it requires a one-  
hour window between compressor starts in order for  
the counter to be reset.  
Oil Separator Level #1 Safety Trip Delay:  
• This timer bypasses the low oil level switch for mo-  
mentary drops in the oil level. This timer activates  
when the low oil level switch opens, and deactivates  
when the switch closes. If the switch is still open af-  
ter the timer has timed out, the compressor will be  
shut down and a trip message will be displayed. This  
timer is available if the unit is equipped with a low oil  
separator oat switch (the oil level switch is standard  
on all liquid injection units and optional on all others).  
True Anti-Recycle Timer:  
• Once the compressor turns off, this timer will keep  
the compressor off for the setting of the True Anti-  
Recycle Timer. This timer is used to prevent short cy-  
cling of the compressor.  
Oil Separator Level #2 Safety Trip Delay:  
• This timer bypasses the low oil level switch for mo-  
mentary drops in the oil level. This timer activates  
when the low oil level switch opens, and deactivates  
when the switch closes. If the switch is still open af-  
ter the timer has timed out, the compressor will be  
shut down and a trip message will be displayed. This  
timer is available if the unit is equipped with a low oil  
separator oat switch (the oil level switch is standard  
on all liquid injection units and optional on all others).  
Accumulative Anti-Recycle Timer:  
• This timer forces a specied time between compres-  
sor starts. When the compressor starts, the timer  
resets and starts timing and accumulates running  
time. Once the compressor shuts down, it will not  
be allowed to restart for the remainder of time left  
on the Accumulative Anti-Recycle Timer. Unlike the  
True Anti-Recycle Timer, if the compressor has run  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
8 – 2  
Section 8 Timers  
for a time period that exceeds the setpoint of the  
Accumulative Anti-Recycle Timer, then when the  
compressor shuts down, it will be allowed to restart  
immediately.  
Emergency Stop Timer:  
• Denes the amount of time the compressor is in a  
False start condition before activating the Emergency  
stop. The emergency stop output can be connected  
to a shunt-trip in the case of a run away compressor  
to remove all power to the system.  
Compressor Interlock Bypass:  
• Once the Vission 20/20 has sent a command to the  
compressor starter to start, a return signal is expect-  
ed. This timer denes how much time to wait for that  
signal before setting a trip condition.  
Low Suction Pressure Safety Bypass:  
• Sets the time that the compressor is allowed to run  
at lower suction pressure then would usually be allow  
at start-up.  
High Motor Amps Safety Bypass:  
• Starting motors can typically pull much more than  
its rates full load amps for a short time. This timer ig-  
nores that sudden inrush of current for the specied  
time.  
High Superheat Temp Safety Changeover:  
• This timer activates at shutdown and changes the re-  
start parameters if the time has not been met.  
Figure 8-2. Timers Screen - Page 2  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
8 – 3  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
8 – 4 / Blank  
Section 9 Compressor Scheduling  
< Event 2 < Event 3 < Event 4 for all days. If events are  
not in order, invalid events are marked with caution  
symbol to indicate the operator to correct events and  
then enable feature.  
Overview  
This menu allows the operator to schedule control set-  
point switching during the day and week. This feature  
can be enabled and disabled from the Compressor  
Schedule screen. Up to four setpoint “switch” events  
can be scheduled per day, see Figure 9-1. Compressor  
Scheduling Screen.  
Control Mode:  
• These drop-down boxes allow selection of operat-  
ing modes which gets switched once schedule event  
time is achieved.  
• The list of allowable modes depends on the number  
of controllers selected in the conguration screen.  
For example, if the number of Suction Pressure  
Control Setpoints selected is “2” and the number  
of Process Temperature Control Setpoints selected  
is “1”, then Control Mode drop-down box will have  
“Unscheduled”, “Suction Pressure SP1”, “Suction  
Pressure SP2” and “Process Temperature SP1” as op-  
tions for selection.  
Scheduling Setpoint  
Schedule:  
• The options for selection are “Enable” & “Disable”.  
The operator is allowed to congure setpoints relat-  
ed to schedule events, but only when the schedule is  
disabled.  
• The operator can Enable Compressor Scheduling  
Feature, only if Time Intervals are in order of Event 1  
• If Control Mode is selected as “Unscheduled” and  
Time set in an event is achieved, then control mode  
will not get switched. Hence Control Mode can be set  
Figure 9-1. Compressor Scheduling Screen  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
9 – 1  
Section 9 Compressor Scheduling  
as “Unscheduled” if operator does not want to use all  
4 events per day.  
Time:  
• This setpoint allows selection of Hours, Minutes and  
AM/PM values for an event. When time set for an  
event is achieved, control mode will get changed as  
selected for that event.  
• The range of values allowed to set for Hours setpoint  
is 0 – 12 for 12 hour format and 0 – 23 for 24 hour for-  
mat. The range of values allowed to set for Minutes  
setpoint is 0 – 59. AM/PM selection is active for se-  
lection only when Time Format selected in congura-  
tion screen is 12 hour.  
When scheduling feature is enabled and No. of control-  
lers for Suction Pressure Control & Process Temperature  
Control are changed in conguration screen which  
makes control modes selected in compressor schedul-  
ing screen as invalid, then feature will get disabled auto-  
matically and indication will be sent to operator to cor-  
rect the setting.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
9 – 2  
Section 10 Compressor Sequencing  
and goes beyond Load Rate 2 setpoint offset then se-  
quencing decisions are made according to Load Rate  
2 timer.  
Overview  
Compressor sequencing screen is where more than one  
Vission 20/20 panels can be sequenced in network using  
Modbus TCP. These settings dene how the master com-  
pressor should control sequenced Vission 20/20 panels.  
This feature is enabled from the Conguration Screen,  
see Section 19 for Compressor Sequencing.  
Load Rate 1 offset (inner):  
• Denes the inner pressure/temp setpoint offset to  
monitor compressor load. If Suction pressure / pro-  
cess temperature goes beyond Load Rate 1 setpoint  
offset then sequencing decisions are made according  
to Load Rate 1 timer.  
Suction Pressure/Process Temperature Control Setpoint:  
Pressure / Temperature Control Setpoints  
• The target setpoints are read only values here.  
These setpoints can be changed by logging on to  
“Compressor Control” Screen.  
Compressor Sequencing screen denes settings  
those are used by master compressor for sequenc-  
ing. For Pressure Control Setpoints see Figure 10-1, for  
Temperature Control Setpoints see Figure 10-2.  
Unload Rate 1 Offset (inner):  
• Denes the inner pressure/temp setpoint to moni-  
tor compressor load. If Suction Pressure/Process  
Temperature Control drops below Unload Rate 1 set-  
point offset then sequencing decisions are made ac-  
cording to Unload Rate 1 timer.  
Load Rate 2 offset (outer):  
• Denes the outer pressure/temperature setpoint off-  
set to monitor compressor load. If Suction pressure  
/ process temperature surpasses Load Rate 1 offset  
Figure 10-1. Compressor Sequencing Screen - Page 1  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
10 – 1  
Section 10 Compressor Sequencing  
Unload Rate 2 Offset (outer):  
Load Rate 2 (Outer):  
• Denes the outer Pressure/Temp setpoint offset  
to monitor compressor load. If Suction Pressure/  
Process Temperature drops below Unload Rate 1  
offset and goes below Unload Rate 2 setpoint offset,  
then sequencing decisions are made according to  
Unload Rate 2 timer.  
• If Suction Pressure/Process Temperature surpasses  
Load Rate 1 offset and goes beyond Load Rate 2 set-  
point offset then Load Rate 2 timer is used to make  
periodic sequencing decisions.  
Unload Rate 1 (Inner):  
• If Suction Pressure/Process Temperature goes below  
Unload Rate 1 setpoint offset then Unload Rate 1  
timer is used to make periodic sequencing decisions.  
Capacity Load/Unload Timers  
Unload Rate 2 (Outer):  
One of the following Capacity Load/Unload rate tim-  
ers are used to make sequencing decisions periodically.  
Suction Pressure/Process Temperature setpoints are  
monitored to identify which one of the following timers  
to be used.  
• If Suction Pressure/Process Temperature surpasses  
Unload Rate 1 offset and goes below Unload Rate 2  
setpoint offset then Unload Rate 2 timer is used to  
make periodic sequencing decisions.  
Load Rate 1 (Inner):  
• If Suction Pressure/Process Temperature goes be-  
yond Load Rate 1 setpoint offset then Load Rate 1  
timer is used to make periodic sequencing decisions.  
Figure 10-2. Compressor Sequencing Screen - Page 2  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
10 – 2  
Section 10 Compressor Sequencing  
NOTE  
Compressor Sequencing Table  
Switching a compressor control to OFF when running  
in auto seq mode puts respective slave compressor  
into local auto mode. This feature is used to add or  
remove slave compressors to sequence table when  
running in auto sequence mode.  
Compressor sequencing table menu allows operator to  
view and adjust settings those are used for compressor  
sequencing, see Figure 10-3. Compressor Sequencing  
Screen - Page 3.  
CFM:  
• CFM column is read only. These values are updat-  
ed automatically when Equipment combo box is  
changed. This indicates Slave compressor capacity in  
CFM.  
Equipment:  
• Options of this combo box are updated automatical-  
ly. This contains names of all the compressors in the  
network communicating with Master compressor.  
Equipment name can be selected from drop-down  
list. Same Equipment name should not be congured  
more than once in Sequencing table.  
Priority:  
• This denes priorities of compressors on the network.  
This priority will decide the sequence in which com-  
pressors will be turned on and off during sequence  
cycle. Lower the priority number greater the priority  
of the compressor.  
Control:  
• Inclusion/exclusion of compressor partaking in the  
sequencing can be decided on basis of this toggle  
button. Compressors can be included/excluded by  
toggling ON/OFF.  
Figure 10-3. Compressor Sequencing Screen - Page 3  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
10 – 3  
Section 10 Compressor Sequencing  
Step:  
Machine Start Time:  
• This parameter would decide stepwise increment or  
decrement value in percentage of the compressor  
capacity. In the case when last step makes total ca-  
pacity greater than maximum capacity, total capac-  
ity will get reduced to maximum capacity. Same is  
applicable when last step makes total capacity lower  
than minimum capacity takes priority.  
• Machine start timer shows the time in seconds that  
the Master Compressor will hold before starting slave  
compressor once (Start) decision is taken.  
Machine Stop Time:  
• Machine Stop timer shows the time in sec that the  
Master Compressor will hold before stopping slave  
compressor once (Stop ) decision is taken.  
Min Cap:  
• Denes the lowest capacity in percentage with which  
a compressor is allowed to run. Minimum capacity  
value takes preference on rst step value.  
Refresh:  
NOTE  
Max Cap:  
Before Conguring Sequencing table on Master  
Compressor, log on to slave compressors one by  
one and enable sequencing in slave mode, put slave  
in remote mode. Then log on to Master Compressor  
and wait till all slaves show up their names under  
equipment List.  
• Denes the highest capacity in percentage with  
which a compressor is allowed to run. Maximum ca-  
pacity value takes preference over last step value.  
Status Symbols:  
• Status symbols shows status of Slave compressors on  
the sequencing table, see Table 10-1. Status Symbols.  
For further details, see Application Notes.  
• Compressor Sequencing table is automatically re-  
freshed every 1 minute. Pressing “Refresh” button  
refreshes the status of the Compressor Sequencing  
table on Master Compressor.  
Table 10-1. Status Symbols  
Symbol  
Description  
Slave Compressor is detected but is not congured  
in the sequencing table.  
Default, If slave Compressor is not present.  
Slave Compressor is congured in sequencing table  
but is not congured in “Remote” mode.  
Slave Compressor congured in sequencing table  
and is in ready to run state.  
Slave Compressor is running with Alarm condition.  
Slave Compressor stopped due to Error Condition.  
Slave Compressor running at maximum capacity  
without any error.  
Slave Compressor under active control of Master  
Compressor  
Slave Compressor running into its stop timer, will be  
stopped.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
10 – 4  
Section 11 Condenser Control  
Overview  
Condenser Control Setpoint:  
This screen allows the operator to view and adjust con-  
denser setpoint settings associated with condenser op-  
eration. This screen will only be active if the Condenser  
Control option has been enabled from the Conguration  
Screen, see Figure 11-1. Condenser Control Screen.  
Run Mode:  
• Run Mode allows the selection of different modes of  
operation for condenser control. The choices for se-  
lection are:  
Run Never  
The Condenser Control operation allows the cycling of  
fans and pumps in order to maintain a specic condens-  
ing pressure. The ve different steps in step control al-  
low selection of fans, pumps and VFD in one or more  
steps. When a VFD is employed, VFD is allowed to reach  
maximum speed, if additional capacity is needed, the  
next fan or pump is turned on. The VFD will modulate  
down and then once it is back up to 100% again, then  
the next fan or pump is turned on. This method allows  
the smoothest condenser control by spacing the VFD  
between the fan and pump steps, while maintaining a  
condenser pressure that matches the setpoint.  
• The mode of operation by default. Condenser Control  
operation will not be performed when this mode is  
active.  
Run With Comp  
• Automatic operation of condenser control selected  
when control of the condenser is required to only run  
when the compressor is running.  
Run Always  
• Automatic operation of condenser control selected  
when control of the condenser is required to run even  
when the compressor is off.  
Figure 11-1. Condenser Control Screen - Page 1  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
11 – 1  
Section 11 Condenser Control  
Manual:  
High to Low Speed Fan Delay:  
• Mode for controlling condenser control operation  
manually. Operator controls the operation by manual  
stepping using an on/off toggle button at each step.  
• This is a time delay for the fan spin down in case of  
2- speed motor/dual speed fan.  
Summer/Winter Auto Switch:  
Condenser Press:  
• This checkbox when enabled allows proles to switch  
automatically depending on ambient temperature  
setpoint when Run Mode is “Auto”. When ambient  
temperature falls below ambient temperature set-  
point, winter prole is used. Similarly when ambient  
temperature is above ambient temperature setpoint,  
summer prole is used.  
• This is the read only parameter and it displays the  
present value of condenser pressure.  
Condenser Setpoint:  
• This is the condenser pressure setpoint that needs to  
be maintained.  
Upper Deadband:  
Wetbulb Override:  
• This is the condenser pressure setpoint upper dead-  
band value. No additional condenser capacity is add-  
ed when the condenser is selected for automatic step  
control and the condenser pressure falls within this  
deadband.  
• This checkbox when enabled gives the operator a  
functionality to control energy wastage. When the  
condenser temperature reaches wetbulb tempera-  
ture plus the operator given offset, then the con-  
denser control operation does not add additional  
steps. This is done as it is not possible to lower the  
temperature anymore, and by adding more fans or  
pumps controls the operation by manually stepping  
using an on/off toggle button at each step.  
Lower Deadband:  
• This is the condenser pressure setpoint lower dead-  
band value. Condenser capacity is not reduced  
when the condenser is selected for automatic step  
control and the condenser pressure falls within this  
deadband.  
Step Control  
Ambient Temp:  
• This is the read only parameter and it displays the  
present value of ambient temperature. This is dis-  
played only when Ambient Sensor is enabled from  
Conguration Screen.  
The Step Control allows the operator to setup the man-  
ner in which Fans, Pumps & VFD will be turned on/off.  
Fans & Pumps are connected on digital outputs Out #1  
to Out #4. VFD Fan is connected on Analog Output. Each  
step can have maximum of ve outputs connected to it.  
Each step can be opted in or out depending on enabling  
of checkbox.  
Wetbulb Temp:  
• This is the read only parameter and it displays the  
present value of wetbulb temperature. This is dis-  
played only when Wetbulb Sensor is enabled from  
Conguration Screen.  
When Run Mode is Auto and condenser pressure rises  
above upper deadband, condenser step gets incremen-  
tal from Step 1 to Step 5 and hence switching on/off  
Pumps, Fans & VFD connected on outputs. This holds  
true for decremented of steps from Step 5 to Step 1  
when condenser pressure falls below lower deadband.  
Wetbulb Offset:  
• This is the offset value from wetbulb temperature as  
the override point.  
Switch Temp:  
Step Delay:  
• This is the ambient temperature setpoint used for au-  
tomatic switching of prole from summer to winter  
and vice-versa.  
• Allows operator to set time delays between condens-  
er steps. Condenser Pressure must be outside upper  
or lower deadband continuously for delay time in or-  
der to increase or decrease condenser steps. While  
in a VFD step, an additional step can only be added  
once VFD has reached its maximum speed setpoint  
and the delay timers are satised.  
Prole Selection:  
• Prole selection allows operator to have two different  
output proles for summer and winter. Operator can  
have different selection of fans, pumps & VFD in ve  
steps of step control table. Different proles allow  
inclusion/exclusion of water pumps in cold weather  
when summer/winter auto switch is enabled. This  
selection is inactive when Run mode is Auto and  
Summer/Winter Auto Switch is enabled.  
• Similarly in a VFD step, a step can only be removed  
once VFD has reached its minimum speed setpoint  
and the delay timers are satised. Step Delay acts  
as “ON” timer while loading and acts as “OFF” timer  
while unloading for the same step.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
11 – 2  
Section 11 Condenser Control  
Low Speed Fan:  
percentage for Condenser VFD Fan at which it should  
run for continuous step delay time to increase con-  
denser steps. E.g. let’s say setpoint is kept at 95%.  
Then condenser VFD fan will have to run at speed  
of 95% or more to advance to next step. Maximum  
Speed can be set as 100%, which is when analog out-  
put (at which condenser VFD fan is connected) reach-  
es to 20mA in its normal range of 4-20 mA  
• Allows steps to have option for time delay in case of  
fan spin down. Any of Out #1 to Out #4 can be se-  
lected as Low Speed Fan through combo box. E.g.:  
Let’s say Out #2 is selected as Low Speed Fan in Step  
2. When step 2 becomes active during condenser  
control operation which is after Step 2 time-out de-  
lay, Out #2 is left off for time as set by the operator in  
High to Low Speed Delay. After low speed fan ener-  
gizes, then timer for Step 3 starts timing.  
Minimum Speed:  
• This setpoint denes the minimum speed in percent-  
age for Condenser VFD Fan at which it should run for  
continuous step delay time to decrease condenser  
steps. E.g. let’s say setpoint is kept at 5%. Then con-  
denser VFD fan will have to run at speed 5% or less to  
advance to next step. Minimum Speed can be set as  
0%, which is when analog output (at which condens-  
er VFD fan is connected) reaches 4mA in its normal  
range of 4-20 mA.  
Control:  
• Toggle any of the steps On/Off during Manual opera-  
tion of Condenser Control. This button is active only  
when Run Mode selected is Manual. During Auto op-  
eration of Condenser Control, control button for ac-  
tive step will be “ON”.  
VFD Settings  
This page is active only when Condenser VFD is selected  
in the Conguration Screen, see Section 19. For VFD  
controls refer to Figure 11-2. Condenser Control Screen  
- Page 2. When a VFD Fan is used for condenser control  
operation, the speed of the VFD is controlled using PID  
algorithm.  
P = Proportional (gain):  
• Used to adjust the fan speed action in direct propor-  
tion to the difference between the control setpoint  
and the process variable (SP - PV = error). The pro-  
portional term is a unit less quantity and is used for  
coarse adjustment. This setpoint should be set to the  
lowest value that gives adequate control system re-  
sponse. Increasing the proportional setting increases  
the control system’s sensitivity to small process uc-  
tuations and the tendency to hunt.  
I = Integral (reset):  
• Used to adjust the capacity control action, integrat-  
ing the error over time, to account for a small er-  
ror that has persisted for a long time. This quantity  
is used for ne adjustment. This setpoint is used to  
smooth out process variations. This setpoint should  
be set high enough to prevent hunting but not too  
high or it will cause control system overshoot.  
D = Derivative (rate):  
• Used to adjust the capacity control action, account-  
ing for how fast the error is changing, positively or  
negatively.  
Maximum Speed:  
• This setpoint denes the maximum speed in  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
11 – 3  
Section 11 Condenser Control  
Figure 11-2. Condenser Control Screen - Page 2  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
11 – 4  
Section 12 Service Options  
Use Figure 12-1. Service Options Screen - Digital Outputs  
(Page 1)  
Overview  
The Service Option screen allows the operator the ability  
to force individual digital or analog outputs ON. This fea-  
ture is used for diagnostic purposes during initial setup  
and/or if the operator suspects an issue with the out-  
puts. The buttons in this screen are not available while  
the compressor is running .  
Compressor Start:  
• Activates the output assigned to the compressor mo-  
tor starter. The output is connected to terminal 11  
and is the 1st LED on card 1.  
Oil Pump Start:  
• Activates the output assigned to the oil pump. The  
output is connected to terminal 12 and is the 2nd  
LED down on card 1.  
Digital Outputs  
Capacity Increase Motor:  
The digital output buttons are momentary toggle but-  
tons. The output will be active while the operator has his  
nger on the button. The output will deactivate when  
the operators nger is removed. The operator can mea-  
sure the output at the terminal block or view the output  
by watching the LEDs located on the cards. For Digital  
Output screens, see Figures 12-1, 12-2, 12-3 and 12-4.  
• Activates the output assigned to the increase input  
of the capacity actuator. The output is connected to  
terminal 13 and is the 3rd LED down on card 1.  
Capacity Decrease Motor:  
• Activates the output assigned to the decrease input  
of the capacity actuator. The output is connected to  
terminal 14 and is the 4th LED down on card 1.  
Figure 12-1. Service Options Screen - Digital Outputs (Page 1)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
12 – 1  
Section 12 Service Options  
Use Figure 12-2. Service Options Screen - Digital Outputs  
(Page 2)  
Volume Increase Motor:  
• Activates the output assigned to the increase input  
of the volume actuator. The output is connected to  
terminal 15 and is the 5th LED down on card 1.  
Slide Valve Setpoint # 1 (Economizer):  
• Activates the output typically assigned to the econo-  
mizer solenoid, but can be changed by the operator.  
The output is connected to terminal 21 and is the 1st  
LED on card 2.  
Volume Decrease Motor:  
• Activates the output assigned to the decrease input  
of the volume actuator. The output is connected to  
terminal 16 and is the 6th LED down on card 1.  
Slide Valve Setpoint # 2 (Hot Gas Bypass):  
• Activates the output typically assigned to the hot gas  
bypass solenoid, but can be changed by the operator.  
The output is connected to terminal 22 and is the 2nd  
LED on card 2.  
Oil Separator Heater  
• Activates the output assigned to the oil separator  
heater. The output is connected to terminal 17 and is  
the 7th LED down on card 1.  
Alarm:  
Trip:  
• Activates the output during an alarm condition. This  
is a reverse acting output. The output is connected to  
terminal 23 and is the 3rd LED on card 2.  
• Deactivates the output during a trip or inhibit con-  
dition. This is a reverse acting output. The output is  
connected to terminal 18 and is the bottom LED on  
card 1.  
Economizer Port # 2 :  
• Activates the output typically assigned to the econo-  
mizer solenoid. The output is connected to terminal  
Figure 12-2. Service Options Screen - Digital Outputs (Page 2)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
12 – 2  
Section 12 Service Options  
on card 2.  
24 and is the 4th LED down on card 2.  
Liquid Injection # 1:  
Use Figure 12-3. Service Options Screen - Digital Outputs  
(Page 3) and Figure 12-4. Service Options Screen - Digital  
Outputs for Remote Oil Cooler (Page 3)  
• Activates the output assigned to the liquid injection  
solenoid. The output is connected on terminal 25  
and is the 5th LED on card 2.  
Condenser / Remote Oil Cooler Step # 1:  
• Activates the output assigned to the 1st step of the  
Condenser / Remote Oil Cooler. The output is con-  
nected to terminal 41 and is the 1st LED on card 4.  
Liquid Injection # 2:  
• Not currently used.  
Remote Enabled:  
Condenser / Remote Oil Cooler Step # 2:  
• Activates the output assigned to notify a central con-  
trol system of the Vission 20/20 run status. The out-  
put is connected to terminal 27 and is the 7th LED on  
card 2.  
• Activates the output assigned to the 2nd step of the  
Condenser / Remote Oil Cooler. The output is con-  
nected to terminal 42 and is the 2nd LED down on  
card 4.  
Shunt Trip:  
Condenser / Remote Oil Cooler Step # 3:  
• Activates the output during a false start condition  
and the emergency stop timer has expired. This out-  
put could be wired the a breaker with a shunt trip that  
feeds power to a starter to force a shutdown. The  
output is connected to terminal 28 and is the 8th LED  
• Activates the output assigned to the 3rd step of the  
Condenser / Remote Oil Cooler. The output is con-  
nected to terminal 43 and is the 3rd LED down on  
card 4.  
Figure 12-3. Service Options Screen - Digital Outputs (Page 3)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
12 – 3  
Section 12 Service Options  
Condenser / Remote Oil Cooler Step # 4:  
• Activates the output assigned to the 4th step of the  
Condenser / Remote Oil Cooler. The output is con-  
nected to terminal 44 and is the 4th LED down on  
card 4.  
Figure 12-4. Service Options Screen - Digital Outputs for Remote Oil Cooler (Page 3)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
12 – 4  
Section 12 Service Options  
% Slide Valve Position  
Analog Outputs  
• Sets the analog output assigned to the Slide Value  
position used to inform a central control system of  
the capacity position. The output is connected to AO  
#3 on card 10.  
The Analog Output (AO) selections allow the operator  
to enter a desired value of the output then turn on the  
output, see Figure 12-5. Service Options Screen - Analog  
Outputs (Page 4). The operator will have to measure  
the output using meter capable of measuring a 4-20mA  
signal.  
Liquid injection Motorized Valve:  
• Sets the analog output assigned to the liquid injec-  
tion motorized value position. The output is connect-  
ed to AO #4 on card 10.  
Compressor VFD:  
• Sets the analog output assigned to the compressor  
VFD. The output is connected to AO #1 on card 10.  
Condenser / Remote Oil Cooler VFD:  
• Sets the analog output assigned to the Condenser /  
Remote Oil Cooler VFD. The output is connected to  
AO #2 on card 10.  
Figure 12-5. Service Options Screen - Analog Outputs (Page 4)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
12 – 5  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
12 – 6 / Blank  
Section 13 Instruments Calibration  
calibrated through the Vission 20/20.  
Overview  
The Instrument Calibration screen allows the operator  
to dene how the Vission 20/20 will interpret the signal  
from any devices attached to the panel’s analog inputs.  
The instrument calibration screen is organized up to six  
pages. Each page is then divided into several left side  
selected tabs. Each tab will be headed with an informa-  
tion bar labeled “I/O” that give the basic information  
for that device. The “A/D bit Value” display box shows  
the unmodied value read by the Vission 20/20 analog  
to digital converters. This display box is not affected by  
any changes to the calibrations settings. As long as a de-  
vice is connected to the associated input, there will be  
a value in this display box. The “Calibrated Value” dis-  
play box shows the end result of the calibration process.  
Therefore, any changes to the calibration setpoint will  
effect what value is shown.  
Pressure and Temperature Inputs  
The most commonly used instruments are tempera-  
ture and pressure sensors. The rst two pages of the  
Instrument Calibration screen are dedicated to these  
instruments, see Figures 13-1 and 13-2.  
Each tab on these two pages are divided into two sec-  
tions, Device Calibration and Channel Calibration. The  
device calibration section is where the operation param-  
eters of the instrument is dened. The channel calibra-  
tion denes the type of signal sent by the instrument.  
Default Devices:  
• By selecting this option, the operator will have access  
via a drop-down box of several common devices. The  
devices are predened and if one is selected, then all  
the setpoints will be set for the operator.  
All instruments are calibrated using a two point linear  
calibration process. Any device that has a non-linear re-  
sponse to environmental stimuli will not be able to be  
Figure 13-1. Instruments Calibration Screen - Analog Inputs (Page 1)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
13 – 1  
Section 13 Instruments Calibration  
Custom Device:  
Motor Current  
• This option allows the operator to choose the mini-  
mum and maximum value of the instrument being  
used.  
The Vission 20/20 has two options for measuring motor  
current. A 4-20mA signal transmitted from an external  
device or a 0-5Amp AC current Transformer. The type  
of device being used is selected in the Conguration  
Screen, Motor Current Device in Section 19.  
Offset:  
• Once the two point calibration is completed, it is not  
uncommon for there to be a small error. By entering  
the value of the error from the calibrated value and  
the actual value into the adjustment entry box, that  
error will be added/subtracted from the total offset.  
The offset is applied to the calibrated value which  
should correct the error.  
The motor current tab has the ability to calibrate both  
measurement options through the 4-20mA scale and  
current transformer ratio sections, see Figure 13-3.  
Instruments Calibration Screen - Analog Inputs (Page 3).  
However, the device type that is selected in the congu-  
ration screen will be the only section that will be avail-  
able to the operator.  
Range:  
• This option is available when the custom device op-  
tion is chosen. Here the operator denes the signal  
type and range transmitted by the instrument. The  
operator can choose from several predened ranges  
in the drop-down box or enter a value.  
The calibration differs from all other calibration proce-  
dures in that the motor current must be calibrated while  
the compressor is running at close to full load amps as  
possible. In addition, the operator will need to enter a val-  
ue into the “Enter Desired Value” entry box that is equal  
to the measured value in amps by a calibrating measure-  
ment device. After entering the measured value, the  
Figure 13-2. Instruments Calibration Screen - Analog Inputs (Page 2)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
13 – 2  
Section 13 Instruments Calibration  
displayed motor current may still be off slightly. In this  
case reenter the desired value and the displayed value  
should get progressively closer.  
total error offset of entries from the “Enter  
Desired Value” setpoint.  
Current Transformer Ratio:  
• Primary  
• Denes the upper value of the current  
transformer.  
• Secondary:  
4-20mA Scale:  
• 4mA:  
• Not editable by the operator. Denes the  
minimum value in amps represented by a 4ma  
inputs.  
• Not editable by the operator. Denes the  
minimum value of the current transformer.  
• 20mA:  
• Enter Desired Value:  
• Denes the maximum value in amps repre-  
sented by a 20ma inputs.  
• The operator enters the value of the cor-  
rect current value. Each entry will recalculate  
the point-slope calculations of the current  
calibration.  
• Enter Desired Value:  
• The operator enters the correct current value.  
Each entry will recalculate the point-slope calcu-  
lations of the current calibration.  
• Total Error:  
• Not editable by the operator. Displays the to-  
tal error offset of entries from the “Enter Desired  
Value” setpoint  
• Total Error:  
• Not editable by the operator. Displays the  
Figure 13-3. Instruments Calibration Screen - Analog Inputs (Page 3)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
13 – 3  
Section 13 Instruments Calibration  
Remote Capacity  
Analog Inputs  
The remote capacity input allows a system controller  
such as the PLC to control the capacity position during  
direct I/O control.  
This section of the Calibration screen allows the opera-  
tor to dene the parameters of an installed auxiliary ana-  
log instrument. These instruments are usually not part  
of a typical compressor setup but Vission 20/20 provides  
a way for the operator to add additional capabilities. The  
layout of this screen is typical to the pressure and tem-  
perature calibration screens. For Analog Inputs screens,  
see Figures 13-4 and 13-5.  
Control Input:  
• This dropdown box is not used at this time.  
Scale:  
• Denes the minimum and maximum Capacity posi-  
Device Calibration:  
tion between 0% & 100% for the 4-20ma input.  
• These setpoints allow the operator to dene what the  
input from the auxiliary instrument means in terms  
of units and range. If a temperature measuring in-  
strument is connected, then the operator would se-  
lect temperature from the Unit drop-down box then  
set the maximum and minimum value for the scale.  
Offset:  
• Used to correct any error in the capacity position. By  
entering a value into the Adjustment entry box, that  
value will be added to the total offset displayed in the  
“total offset” entry box.  
Offset:  
• Once the two-point calibration is completed, it is not  
Figure 13-4. Instruments Calibration Screen - Analog Inputs (Page 4)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
13 – 4  
Section 13 Instruments Calibration  
uncommon for there to be a small error. By entering  
the value of the error from the calibrated value and  
the actual value into the adjustment entry box, that  
error will be added/subtracted from the total offset.  
The offset is applied to the calibrated value which  
should correct the error.  
Range:  
• Here the operator denes the signal type and range  
transmitted by the instrument. The operator can  
choose from several predened ranges in the drop-  
down box or enter a value.  
Figure 13-5. Instruments Calibration Screen - Analog Inputs (Page 5)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
13 – 5  
Section 13 Instruments Calibration  
the output will go to either 4ma or 20 ma. The opera-  
tor can then measure the output for accuracy.  
Analog Outputs  
Min (mA):  
The Analog output card of the Vission 20/20 generates  
a 4 – 20mA signal to any attached devices. However,  
it is not uncommon that small difference in the board  
components might result in small difference in the out-  
put. So this screen offers the operator the ability to ne  
tune the upper and lower output values, see Figure 13-6.  
Instruments Calibration Screen - Analog Outputs (Page  
6).  
• If the 4ma output has an unacceptable amount of  
error. The operator can use the “+” & “-” buttons to  
adjust the output.  
Max (mA):  
• If the 20ma output has an unacceptable amount of  
error. The operator can use the “+” & “-” buttons to  
adjust the output  
Test Limits:  
• By pressing either the Test Min or Test Max buttons,  
Figure 13-6. Instruments Calibration Screen - Analog Outputs (Page 6)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
13 – 6  
Section 14 Slide Calibration  
this section displays the value of the actuator signals in  
millivolts in the “input Value” display box.  
Overview  
The Slide Calibration screen is used in calibrating the  
slide actuators and to establish Vission 20/20 control  
parameters. It is important that the operator uses cau-  
tion while operating in this screen, see Figure 14-1. Slide  
Calibration Screen. The normal safety checks that pre-  
vent the slide from colliding with the mechanical stops  
are overridden. When the calibration process is complet-  
ed and the operator exits the screen, Both actuator will  
return the slides back to their minimum positions.  
“-” Button:  
• When the operator presses and holds this button,  
the output associated with capacity slide decrease  
is energized. If the actuator does not turn in the cor-  
rect direction when this button is pressed, then the  
operator will have to alter how the actuator is wired  
to the panel.  
“+” Button:  
• When the operator presses and holds this button,  
the output associated with capacity slide increase is  
energized. If the actuator does not turn in the cor-  
rect direction when this button is pressed, then the  
operator will have to alter how the actuator is wired  
to the panel.  
Capacity Slide Valve Potentiometer  
This section provides critical information and control pa-  
rameters related to the capacity slide actuator. The “%  
cap” display shows the actual value in percent of the ca-  
pacity slide with out any conditioning that might be ap-  
plied to the other capacity position displays. In addition,  
Software limit setpoint:  
• The Vission 20/20 uses the “Min Limit” and  
“Max Limit” setpoint to dene an area within the  
Figure 14-1. Slide Calibration Screen  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
14 – 1  
Section 14 Slide Calibration  
mechanical stops for normal slide travel. These soft-  
ware limits purpose is to prevent the slide from actu-  
ally hitting the mechanical stops which could result  
in a number of undesirable consequences. By default,  
the software limits are set to 150mV from either end  
point. The position percentage is calculated from the  
software limits. Therefore, it is possible to read a val-  
ue greater than 100% or less than 0% if inertial carries  
the slides after these limits are reached.  
directions from the main computer in the control panel.  
The position sensor tells the main computer the position  
of the slide valve. The main computer uses the position  
and process information to decide where to move the  
slide valve next.  
During calibration, the position sensor records the high  
and low count of motor turns. The operator tells the  
position sensor when the actuator is at the high or low  
position with the push button. Refer to the calibration  
instructions for the detailed calibration procedure.  
The position sensor can get “lost” if the motor is moved  
while the position sensor is not powered. To prevent  
this, the motor can only be moved electrically while  
the position sensor is powered. When the position sen-  
sor loses power, power is cut to the motor. A capaci-  
tor stores enough energy to keep the position sensor  
circuitry alive long enough for the motor to come to a  
complete stop and then save the motor position to non-  
volatile EEPROM memory. When power is restored, the  
saved motor position is read from EEPROM memory and  
the actuators resumes normal function This scheme is  
not foolproof. If the motor is moved manually while the  
power is off or the motor brake has failed, allowing the  
motor to free wheel for too long after the position sen-  
sor looses power, the actuator will loose its calibrated  
position.  
Volume Slide Valve Potentiometer  
This section provided critical information and control  
parameters related to the volume slide actuator. The “%  
Vol” display shows the actual value in percent of the vol-  
ume slide with out any conditioning that might be ap-  
plied to the other volume position displays. In addition,  
this section displays the value of the actuator signals in  
millivolts in the “input Value” display box.  
“-” Button:  
• When the operator presses and holds this button,  
the output associated with volume slide decreases  
is energized. If the actuator does not turn in the cor-  
rect direction when this button is pressed, then the  
operator will have to alter how the actuator is wired  
to the panel.  
A brake failure can sometimes be detected by the po-  
sition sensor. If the motor never stops turning after a  
power loss, the position sensor detects this, knows it will  
be lost, and goes immediately into calibrate mode when  
power is restored.  
“+” Button:  
• When the operator presses and holds this button,  
the output associated with volume slide increase is  
energized. If the actuator does not turn in the cor-  
rect direction when this button is pressed, then the  
operator will have to alter how the actuator is wired  
to the panel.  
Slide Valve Actuator Calibration for Optical  
Style Motors  
Software limit setpoint:  
Assuming that the actuator motors have not been cali-  
brated, the transmitter output of the actuator motor  
will uctuate wildly until they are calibrated. To prevent  
damage to actuator motors, do not connect the Power  
Cable (Yellow TURCK cable) or the Position Transmitter  
Cable (Gray TURCK cable) until instructed to do so in this  
procedure.  
• The Vission 20/20 uses the “Min Limit” and “Max  
Limit” setpoint to dene an area within the mechani-  
cal stops for normal slide travel. These software limits  
purpose is to prevent the slide from actually hitting  
the mechanical stops which could result in a number  
of undesirable consequences. By default, the soft-  
ware limits are set to 150mV from either end point.  
The position percentage is calculated from the soft-  
ware limits. Therefore It is possible to read a value  
greater than 100% or less than 0% if inertial carries  
the slides after these limits are reached.  
1. Open the plastic cover of the capacity motor by re-  
moving the four #10 Pan Head Phillips screws. Gently lift  
the cover and tilt it toward the TURCK connectors. Raise  
the cover enough to be able to press the blue calibrate  
button and to be able to see the red LED on the top of  
the assembly, see Figure 14-2. Photochopper.  
Slide Valve Operation  
2. Remove actuator motor cover(s).  
3. Log In on the Vission 20/20.  
The slide valve actuator is a gear-motor with a position  
sensor. The motor is powered in the forward and reverse  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
14 – 2  
Section 14 Slide Calibration  
4. From the main screen select the Menu button.  
9. Quickly press and release the BLUE CALIBRATION  
BUTTON on the ACTUATOR motor once. The RED LED  
will stop ashing. This now instructs the ACTUATOR mo-  
tor that this point is the maximum slide position. This  
point corresponds to 5 volts. The ACTUATOR calibration  
procedure is completed.  
5. On the menu screen select the Slide Calibration but-  
ton. When the “Slide Valve Calibration” screen appears,  
then you can safely connect the Power Cable (Yellow  
TURCK cable) and the Position Transmitter Cable (Gray  
TURCK cable) to the Capacity motor. Press “+” or “-” to  
move the slide valves to check the rotation. (See Table 1  
below for proper shaft rotation). If for any reason the “+”  
or “-” command on the panel does not correspond to the  
slide increase or decrease, swap the blue & brown wires  
of the Yellow TURCK cable in the control panel to reverse  
the rotation of the motor.  
Now the Capacity Channel is automatically calibrated  
based on the calibration settings made to the actuator.  
CAUTION  
DO NOT CONTINUE TO ENERGIZE THE ACTUATOR  
MOTOR AFTER THE SLIDE HAS REACHED THE  
MECHANICAL STOP. Doing so may cause mechanical  
damage to the motor or shear the motor shaft  
key. When the slide has reached the mechanical  
stop position, press the button in the center of the  
photochopper to release the brake, and thereby  
release the tension on the actuator motor.  
6. Quickly press and release the BLUE CALIBRATION  
BUTTON on the ACTUATOR motor once. This instructs  
the ACTUATOR motor to enter the calibration mode. The  
red LED on the actuator control board will begin ash-  
ing. Use the “-” button on the Vission 20/20 panel to  
drive the capacity slide to its minimum mechanical stop  
position.  
This will be apparent by a slowing of the motor rotation  
and a winding sound from the actuator motor. When  
you hear the motor wind-up, release the “-” button.  
Figure 14-2. Photochopper  
Then use the “+” button to pulse the motor so that the  
capacity slide is “just off” of its minimum position and  
there is no tension on the motor shaft.  
CAUTION  
7. Quickly press and release the BLUE CALIBRATION  
BUTTON on the ACTUATOR motor once. The red LED  
will now ash at a slower rate. This now instructs the  
ACTUATOR motor that this point is the minimum slide  
position. This point will correspond to 0 volts AFTER the  
ACTUATOR calibration procedure is completed.  
Do not over tigten screws. Failure to comply may  
result in damage to equipment.  
.
10. Gently lower the plastic cover to where it contacts  
the base and O-ring seal. After making sure that the  
cover is not binding, gently tighten the four # 10 Phillips  
screws.  
8. Use the “+” button on the Vission 20/20 to drive the  
capacity slide to its maximum mechanical stop position.  
This will be apparent by a slowing of the motor rotation  
and a winding sound from the actuator motor. When  
you hear the motor wind-up, release the “+” button.  
11. Repeat the same procedure for the Volume slide  
motor.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
14 – 3  
Section 14 Slide Calibration  
Command Shaft Rotation  
The following table describes the rotation direction required by the actuator. Every optical actuator has the ability to  
be wired to rotate in either direction. Energizing the blue actuator wire results in a CCW rotation and energizing the  
brown wire results in a CW rotation, see Table 14-1. Command Shaft Rotation Required By Actuator.  
Table 14-1. Command Shaft Rotation Required By Actuator  
Command Shaft Rotation  
Capacity Volume  
INC INC  
Number of Turns / Rotation Angle / Slide Travel  
Capacity Volume  
Turns Angle Travel Turns Angle  
Compressor  
Model  
DEC  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CW  
DEC  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CW  
Travel  
2.045”  
2.045”  
2.045”  
2.045”  
2.045”  
2.045”  
2.473”  
2.473”  
2.889”  
2.889”  
2.889”  
3.200”  
3.433”  
3.200”  
3.433”  
3.433”  
5.341”  
5.341”  
5.341”  
5.341”  
1.767”  
1.767”  
1.767”  
1.767”  
1.767”  
1.767”  
1.767”  
1.767”  
1.767”  
2.045”  
2.045”  
2.045”  
VSR 111  
VSR 151  
VSR 221  
VSR 301  
VSS 451  
VSS 601  
VSS 751  
VSS 901  
VSS 1051  
VSS 1201  
VSS 1301  
VSS 1501  
VSS 1551  
VSS 1801  
VSS 1851  
VSS 2101  
VSS 2401  
VSS 2601  
VSS 2801  
VSS 3001  
VSM 71  
CW  
CW  
CW  
CW  
0.91  
0.91  
0.91  
0.91  
0.91  
0.91  
1.09  
1.09  
1.22  
1.22  
1.22  
1.36  
1.48  
1.36  
1.48  
1.48  
1.80  
1.80  
1.80  
1.80  
0.80  
0.80  
0.80  
0.80  
0.80  
0.80  
0.80  
0.80  
0.80  
0.91  
0.91  
0.91  
328  
328  
328  
328  
328  
328  
392  
392  
439  
439  
439  
490  
533  
490  
533  
533  
648  
648  
648  
648  
288  
288  
288  
288  
288  
288  
288  
288  
288  
328  
328  
328  
3.568” 0.52  
3.568” 0.52  
3.568” 0.52  
3.568” 0.52  
3.568” 0.52  
3.568” 0.52  
4.283” 0.63  
4.283” 0.63  
4.777” 0.74  
4.777” 0.74  
4.777” 0.74  
5.325” 0.82  
5.823” 0.87  
5.325” 0.82  
5.823” 0.87  
5.823” 0.87  
7.072” 1.36  
7.072” 1.36  
7.072” 1.36  
7.072” 1.36  
3.141” 0.45  
3.141” 0.45  
3.141” 0.45  
3.141” 0.45  
3.141” 0.45  
3.141” 0.45  
3.141” 0.45  
3.141” 0.45  
3.141” 0.45  
3.568” 0.52  
3.568” 0.52  
3.568” 0.52  
187  
187  
187  
187  
187  
187  
227  
227  
266  
266  
266  
295  
313  
295  
313  
313  
490  
490  
490  
490  
162  
162  
162  
162  
162  
162  
162  
162  
162  
187  
187  
187  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CW  
VSM 91  
CW  
CW  
VSM 101  
VSM 151  
VSM 181  
VSM 201  
VSM 301  
VSM 361  
VSM 401  
VSM 501  
VSM 601  
VSM 701  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CW  
CCW  
CCW  
CCW  
CCW  
CCW  
CCW  
CW  
CW  
CW  
CW  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
14 – 4  
Section 14 Slide Calibration  
Slide Valve Troubleshooting Guide  
The Analog output card of the Vission 20/20 produces a 4–20mA signal to any attached devices. However, it is not  
uncommon that small differences in the board components might result in small differences in the output. So this  
screen offers the operator the ability to ne tune the upper and lower output values, see Table 14-2. Slide Valve  
Troubleshooting Guide.  
Table 14-2. Slide Valve Troubleshooting Guide (1 of 2)  
Problem  
Reason  
Solution  
Dirt or debris is blocking one or both Clean the optocoupler slots with a  
optocoupler slots.  
cotton swab and rubbing alcohol.  
Adjust the photochopper so that  
the fence extends further into the  
optocoupler slots. Make sure the  
motor brake operates freely and  
the photochopper will not contact  
the optocouplers when the shaft is  
pressed down.  
The photochopper fence extends  
less than about half way into the  
optocoupler slots.  
The actuator cannot be calibrated.  
Tape the end of the white wire in the  
panel and make sure that it cannot  
touch metal.  
The white calibrate wire in the grey  
Turck cable is grounded.  
Dirt and/or condensation on the  
position sensor boards are causing it  
to malfunction.  
Clean the boards with an electronics  
cleaner or compressed air.  
The calibrate button is stuck down.  
The position sensor has failed.  
Try to free the stuck button.  
Replace the actuator.  
Push button is being held down for  
more that ¾ second when going  
through the calibration procedure.  
Depress the button quickly and then  
let go. Each ¾ second the button is  
held down counts as another press.  
The white calibrate wire in the  
grey Turck cable is grounding  
intermittently.  
Tape the end of the white wire in the  
panel and make sure that it cannot  
touch metal.  
The actuator goes into calibration  
mode spontaneously.  
Increase the distance between the  
EMI source and the actuator.  
A very strong source of electromag-  
netic interference (EMI), such as a  
contactor, is in the vicinity of the  
actuator or grey cable.  
Install additional metal shielding ma-  
terial between the EMI source and  
the actuator or cable.  
The motor was manually moved  
while the position sensor was not  
powered.  
Recalibrate.  
The actuator does not transmit the  
correct position after a power loss.  
The motor brake is not working  
properly.  
Get the motor brake to where it op-  
erates freely and then recalibrate.  
The position sensor’s EEPROM  
memory has failed.  
Replace the actuator.  
The photochopper is misaligned  
with the slotted optocouplers.  
Try to realign or replace the actuator.  
There is a rapid clicking noise when  
the motor is operating.  
The motor brake is not working  
properly.  
Get the motor brake to where it op-  
erates freely and then recalibrate.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
14 – 5  
Section 14 Slide Calibration  
Table 14-2. Slide Valve Troubleshooting Guide (2 of 2)  
Problem  
Reason  
Solution  
There is a rapid clicking noise when  
the motor is operating. (Continued) memory has failed.  
The position sensor’s EEPROM  
Replace the actuator.  
The photochopper is misaligned  
with the slotted optocouplers.  
Try to realign or replace the actuator.  
There is a rapid clicking noise when  
the motor is operating.  
Adjust the photochopper so that  
the fence extends further into the  
optocoupler slots.  
The photochopper is positioned too  
low on the motor shaft.  
A motor bearing has failed.  
Replace the actuator.  
There is a loose connection in the  
screw terminal blocks.  
Tighten.  
There is a loose or dirty connection  
in the yellow Turck cable.  
Clean and tighten.  
The motor operates in one direction  
only.  
The position sensor has failed.  
Replace the actuator.  
Replace the actuator.  
There is a broken motor lead or  
winding.  
The motor will resume operation  
when it cools. This could be caused  
by a malfunctioning control panel.  
Consult the factory.  
The thermal switch has tripped be-  
cause the motor is overheated.  
Any of the reasons listed in “The mo-  
tor operates in one direction only”.  
The motor will not move in either  
direction.  
See above.  
The command shaft is jammed.  
Broken gears in the gear-motor.  
Free the command shaft.  
Replace the actuator.  
Check and replace blown relays and/  
or fuses.  
Blown relays or fuses.  
This could be caused by a malfunc-  
tioning control panel. Consult the  
factory.  
The motor runs intermittently, sev-  
eral minutes on, several minutes off. mal switch is tripping.  
Motor is overheating and the ther-  
Bad thermal switch.  
Replace the actuator.  
The motor runs sporadically.  
Any of the reasons listed in “The mo-  
tor will not move in either direction”.  
See above.  
Stripped gears inside the gear rotor,  
or the armature has come unpressed Replace the actuator.  
from the armature shaft.  
The motor runs but output shaft will  
not turn.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
14 – 6  
Section 14 Slide Calibration  
Slide Valve Actuator Troubleshooting Guide Blink Code  
Vilter actuators communicate problems discovered by the internal diagnostics to the technician by LED blink codes.  
Only one blink code is displayed, even though it is possible that more than one problem has been detected. The actua-  
tor motor will not operate until the error code is cleared by pressing the blue bottom, see Table 14-3. LED Blink Codes  
and Troubleshooting Guide.  
Table 14-3. LED Blink Codes and Troubleshooting Guide (1 of 2)  
Flash Pattern  
Meaning  
* = ON - = OFF  
Calibration step 1.  
Calibration step 2.  
*-*-*-*-*-*-*-*-*-*-*-*-  
*---*---*---*---*---*---  
This indicates a zero span. This error can only occur dur-  
ing calibration. The typical cause is forgetting to move  
the actuator when setting the upper limit of the span.  
If this is the case, press the blue button to restart the  
calibration procedure. This error can also occur if either  
or both of the slotted optocouplers are not working. If  
this is the case, the slide valve actuator will have to be  
replaced.  
The operation of the slotted optocouplers can be tested  
as follows:  
*--*--------------------  
1. Manually rotate the motor shaft until the aluminum  
photochopper fence is not blocking either of the opto-  
coupler slots.  
2. Using a digital multimeter, measure the DC voltage  
between terminal 3 of the small terminal block and TP1  
on the circuit board (see Note 1). The measurement  
should be between 0.1 and 0.2 Volts.  
3. Next, measure the DC voltage between terminal 3  
and TP2 on the circuit board. You should measure be-  
tween 0.1 and 0.2 Volts.  
A motor over-speed occurred. At some time during  
operation, the motor armature spun too fast for the  
encoder to measure. A nonfunctional motor brake is  
usually to blame. This error means that the slide valve  
actuator is no longer transmitting accurate position  
information. The actuator should be recalibrated as  
soon as possible, after the cause of the over-speed is  
identied and corrected. This error will not clear until  
the actuator is re-calibrated.  
*-----------------------  
Note 1: TP1 and TP2 are plated-thru holes located close to the slotted optocouplers on the board. They are clearly  
marked on the board silkscreen legend.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
14 – 7  
Section 14 Slide Calibration  
Table 14-3. LED Blink Codes and Troubleshooting Guide (2 of 2)  
Flash Pattern  
Meaning  
* = ON - = OFF  
The motor is overheated. The actuator motor will not  
run until it cools. Once the motor cools, the actuator will  
resume normal operation.  
Motor overheating is sometimes a problem in hot  
humid environments when process conditions demand  
that the slide valve actuators reposition often. Solutions  
are available; consult your Vilter authorized distributor  
for details.  
*--*--*-----------------  
Another possible cause for this error is a stuck motor  
thermal switch. The thermal switch can be tested by  
measuring the DC voltage with a digital multimeter be-  
tween the two TS1 wire pads (see Note 2). If the switch  
is closed (normal operation) you will measure 0 Volts.  
The 24V supply voltage is low. This will occur momen-  
tarily when the actuator is powered up and on power  
down.  
If the problem persists, measure the voltage using a  
digital multimeter between terminals 3 and 4 of the  
small terminal block. If the voltage is less than 24V, the  
problem is in the supply to the board.  
*********************  
If the voltage is >= 24V, replace the actuator..  
The EEPROM data is bad. This is usually caused by loss of  
24V power before the calibration procedure was com-  
pleted. The actuator will not move while this error code  
is being displayed. To clear the error, calibrate the actua-  
tor. If this error has occurred and the cause was not loss  
of 24V power during calibration, the EEPROM memory  
is bad and the actuator will need to be replaced.  
-********************  
*****----*--------------  
Microcontroller program failure. Please notify your  
Vilter authorized distributor.  
Note 2: The TS1 wire pads are where the motor thermal switch leads solder into the circuit board. They are clearly  
marked on the board silkscreen legend and are oriented at a 45° angle.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
14 – 8  
Section 15 Trend Chart  
Overview  
Chart Operation  
This screen allows the operator to view and adjust set-  
tings for the trend chart, see Figure 15-1. Trend Chart  
Screen. Trending feature can be started & stopped from  
this screen. Up to four variables can be selected for plot-  
ting on screen. Each variable is assigned one of four  
colors; the plotted trace and the vertical axis labels for  
a variable will be in its assigned color. The operator can  
select from viewing the plot to selecting which variables  
and time intervals to show as often as necessary. The  
vertical axis scaling and offset for each variable plotted  
is based on its range of values over the entire data plot-  
ted on screen. The data available for display is 120 hours  
maximum.  
Pen Selection:  
• Pen selection allows operator to select different pens  
for plotting of data on the screen. The operator can  
select “None” as an option for disabling plotting of  
data for particular pen. Options in pen selection  
drop-down box will depend on channels selected in  
Trend Setup screen.  
Start/Stop:  
• This button allows the operator to start/stop trend  
feature. When trend feature is not running, button  
will display “Start” and will be green in color. While  
trend feature is running, button will display “Stop”  
and will be red in color. When “Stop” button is  
pressed, trend data is saved to a le.  
Zoom In/Out:  
• These buttons allow the operator to adjust the num-  
ber of data points plotted on the screen. At maximum  
Figure 15-1. Trend Chart Screen  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
15 – 1  
Section 15 Trend Chart  
zoom level operator can view 3 minutes of trend data  
and Zoom In button will be inactive. At minimum  
zoom level operator can view full 120 hours of trend  
data and Zoom Out button will be inactive.  
Trend Data Storage  
The trend analysis screen shows recorded data for prob-  
lem analysis or tuning improvements. A logging buffer  
holds 5 minutes of data sampled at 10 second intervals.  
Back/Forward:  
• These buttons allow the operator to move the plot  
and view trend data at different time intervals.  
When the logging buffer lls with 5 minutes of data, it  
is automatically transferred to a temp csv le. A temp  
trend le will hold up to 1MB of accumulated data.  
When the temp le has accumulated 1MB of data, data  
from temp le is written to new trend le and temp le  
is overwritten with new data in logging buffer till next  
1MB of data. When a total of 15MB of trend data is accu-  
mulated, and the logging buffer has lled with another  
5 minutes of data to write, the le with the oldest trend  
data is deleted.  
• Forward button will be inactive when the operator  
is viewing the rst data point plotted on the screen  
(i.e. when time interval is displaying 0:00). Back but-  
ton will be inactive when the operator is viewing the  
last data point on the screen (i.e. when time interval  
is displaying 120:00). At minimum zoom level, Back  
& Forward buttons will be inactive.  
Trace:  
• This button allows the operator to move a white cur-  
sor line across all four trend lines and receive a read-  
out of all four variables at that point in time. When the  
Trace button is pressed, cursor position is displayed  
along with value of all four variables on the screen.  
Hold:  
• This button allows the operator to stop the data from  
advancing on the display without stopping the trend  
feature. When the Hold button in pressed, Hold Time  
is displayed on the screen.  
Trace Back( < ) / Forward ( > ):  
• These buttons allow the operator to move a white  
cursor line across trend lines and view trend data  
value at that point. These buttons will only be active  
when Trace button is pressed. When these buttons  
are pressed, cursor is moved and trace position is up-  
dated on the screen.  
Setup:  
• This button allows operator to open the Trend Setup  
screen. This button is inactive when the trend feature  
is running.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
15 – 2  
Section 15 Trend Chart  
Setup  
The operator can modify trending options through the  
Trend Setup screen, see Figure 15-2. Trend Setup Screen.  
Trend Setup screen can be accessed by pressing the  
Setup button when the trending feature is not run-  
ning. Trend Setup screen allows the operator to select  
a maximum of 10 analog I/O channels for trending. The  
operator can also set a path for trend data les from the  
drop-down box in the setup screen. The USB will appear  
as an option in drop-down box only when a USB drive is  
mounted on the panel.  
If there is no space available on the USB or when the USB  
is unmounted from the panel and USB is selected for sav-  
ing trend les, trend data les will be written to hard disk.  
If the operator changes Press/Temp units from the con-  
guration screen when running the trending feature,  
then the background trending will stop.  
Figure 15-2. Trend Setup Screen  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
15 – 3  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
15 – 4 / Blank  
Section 16 Event List  
Time:  
Overview  
• Displays the time of the event in HH:MM:SS format.  
Event Type:  
This screen is designed to display compressor events in  
chronological order. The information available on the  
screen is valuable for understanding the operation of the  
compressor and troubleshooting, see Figure 16-1. Event  
List Screen. This screen Is divided into four columns and  
can list up to 128 separate events. The operator can  
download the information on the event list through the  
Data Backup Screen.  
• Displays the type of message for a particular listing.  
Common type are “Start”, “Stop”, “Trip”, “Inhibit”,  
“Alarm”, and “System”. These help the operator to  
understand the meaning of the message in the next  
column.  
Message:  
• Displays the informational string that describes the  
event.  
Event list Columns  
Date:  
• Displays the date of the event in MM-DD-YYYY  
format.  
Figure 16-1. Event List Screen  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
16 – 1  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
16 – 2 / Blank  
Section 17 Input / Output  
Overview  
This screen displays “Live Data” of all the analog points  
and digital points being monitored. There are four  
pages of Input / Outputs (I/O) available for viewing, see  
Figures 17-1, 17-2, 17-3 , 17-4 and 17-5. This screen also  
takes a snapshot of all the I/O points if the compressor  
experiences a trip condition and saves this data as Freeze  
pages, for example, see Figure 17-6. Up to ve Freeze  
pages can be saved. The oldest Freeze page will be re-  
moved when more than ve Freeze events occur. These  
Freeze events can be downloaded to a USB drive though  
the Data Backup screen, see Section 20.  
Figure 17-1. Input/Output Screen - Page 1  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
17 – 1  
Section 17 Input / Output  
Figure 17-2. Input/Output Screen - Page 2  
Figure 17-3. Input/Output Screen - Page 3  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
17 – 2  
Section 17 Input / Output  
Figure 17-4. Input/Output Screen - Page 4  
Figure 17-5. Input/Output Screen - Page 4 (Remote Oil Cooler Enabled)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
17 – 3  
Section 17 Input / Output  
Figure 17-6. Input/Output Screen - Freeze Data Page  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
17 – 4  
Section 18 Auxiliary Input / Output  
alarm, a trip, and an inhibit on either a high or low in-  
put. A low input is 0vac and a high is 120vac on the en-  
abled input. Leaving all options in their default setting  
will mean no action will be taken on an enable input. The  
input will simply be available for viewing at the panel or  
by communications.  
Overview  
The Auxiliary Input/Output (I/O) section of the Vission  
20/20 gives the operator exibility to add peripheral  
instruments and/or devices such as motors, valves and  
solenoids. With these additions, customer congurable  
I/Os are useful in expanding the functions of the Vission  
20/20 where it was not explicitly designed to control.  
Trip/Alarm Check:  
Setting up one or more of the auxiliary inputs or out-  
puts start with the conguration screen. In order to en-  
able the auxiliary I/O, the Vission 20/20 must rst be  
equipped with one of the available expandable I/O cards  
and the card must be selected on page 6 of the congu-  
ration screen. Once the appropriate card is available,  
then the operator will be permitted to enable and name  
the desired auxiliary I/O. The operator can then navigate  
to the Auxiliary I/O screen where the operator can dene  
• Selecting this checkbox enables the alarms and/or  
trip functions of the Vission 20/20 for the desired  
digital input. The accompanying drop-down box  
gives the operator the exibility to choose whether  
the alarm and/or tip occurs if the input is high or low.  
Inhibit Check:  
• Selecting this checkbox enables the inhibit function  
of the Vission 20/20 for the desired digital input. An  
inhibit check prevents the compressor from starting  
if the condition is true where a trip will shut down  
the compressor after it as started. The inhibit can be  
selected to inhibit on a high or low input and can be  
selected to work with or without the alarm and trip  
function  
how that I/O will operate.  
Digital Inputs:  
The Digital Inputs section of the auxiliary I/O allows an  
operator to congure the auxiliary digital inputs, see  
Figure 18-1. Auxiliary I/O Screen - Digital Inputs (Page  
1). The digital input can be congured to produce an  
Figure 18-1. Auxiliary I/O Screen - Digital Inputs (Page 1)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
18 – 1  
Section 18 Auxiliary Input / Output  
Digital Relay:  
Digital Outputs  
• The digital relay option is used to pass along the in-  
formation from a digital input to another control de-  
vice or to operate a peripheral device. This output can  
be congured to either reect the selected input or  
show the opposite value.  
The digital outputs section of the Auxiliary I/O screen  
allows an operator to congure the auxiliary digital  
outputs, see Figure 18-2. Auxiliary I/O Screen - Digital  
Outputs (Page 2). The digital output can be congured  
to activate (go High, 120vac) based on either a digital  
input or a specied level on an analog input. Every digital  
and analog input in the Vission 20/20 are made available  
for controlling a digital output.  
• Mirror:  
• Selecting this option will produce a high out-  
put when the selected input is High; and pro-  
duce a low output when the selected input is  
low.  
Analog Input:  
• Invert:  
• Selecting the Analog Input radio button lls the  
Active Input drop-down box with all available analog  
inputs. One of the analog inputs can then be selected  
to control the digital outputs.  
• Selecting this option will produce a low out-  
put when the selected input is high; and pro-  
duce a High output when the selected input is  
low.  
Digital Input:  
• Selecting the Digital Input radio button lls the  
Active Input drop-down box with all available digital  
inputs. One of the digital inputs can then be selected  
to control the digital outputs.  
Analog Inputs  
The Analog inputs section of the auxiliary I/O screen al-  
lows an operator to dene the function of an instrument  
connected to the Vission 20/20. For Auxiliary Analog  
Inputs Screens, see Figure 18-3, 18-4 and 18-5. The ana-  
log inputs can be congured to simply monitor an input  
for informational purposes or used as a control input for  
the auxiliary digital and analog outputs. The analog in-  
puts can also be congured to alarm, trip, and inhibit on  
specied values.  
Run Always:  
• Selecting this checkbox enables the function that  
controls the digital output to operate only when the  
compressor is running or runs all the time.  
Analog Trigger:  
• The analog trigger toggles the digital output based  
on a specied value plus the specied differential  
value.  
• Alarm / Trip:  
• Analog Trigger value:  
• This drop-down box allows the operator to  
select whether the analog input should gener-  
ate an alarm, trip, or both when the input value  
exceeds the limits entered into the alarm and  
trip entry boxes.  
• This denes the specied value in which the  
output will toggle. This is an absolute value  
and not based on units. For example, 100 could  
mean temperature or pressure depending on  
the type of input selected.  
• Inhibit:  
• N/O & N/C:  
• Selecting this checkbox will prevent a start if  
the input value exceeds the alarm limit values.  
• Choosing the Normally Open (N/O) or  
Normally Closed (N/C) radio buttons denes  
what the output will be above or below the trig-  
ger value. In the N/O setting, the output will be  
off (0vac) while the input value is below the trig-  
ger value.  
• Low Alarm:  
• This denes the lower limit of the input value  
that when exceeded will generate an alarm.  
• High Alarm:  
• Differential:  
• This denes the upper limit of the input value,  
that when exceeded will generate an alarm.  
• This is the differential around the trigger val-  
ue. For example, if a trigger value of 100 is en-  
tered with a differential of 1, then as the value  
increases to 101, the output will be triggered. If  
the value decreases to 99, then the output will  
be toggled in the opposite direction.  
• Low Trip:  
• Denes the lower limit of the input value that  
when exceeded will generate a trip.  
• High Trip:  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
18 – 2  
Section 18 Auxiliary Input / Output  
Figure 18-2. Auxiliary I/O Screen - Digital Outputs (Page 2)  
Figure 18-3. Auxiliary I/O Screen - Analog Inputs (Page 3)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
18 – 3  
Section 18 Auxiliary Input / Output  
• Denes the upper limit of the input value that  
I = Integral (reset):  
when exceeded will generate a trip.  
• Used to integrate the error over time, to account for  
a small error that has persisted for a long time. This  
quantity is used for ne adjustment. This setpoint is  
used to smooth out process variations. This setpoint  
should be set high enough to prevent hunting but  
not too high or it will cause control system overshoot.  
Analog Outputs  
This screen allows to map any standard analog input or  
auxiliary input to any of the four analog auxiliary out-  
puts. There are two pages of auxiliary output congura-  
tion, each consists of two analog auxiliary outputs. For  
Auxiliary Outputs Screens, see Figures 18-6 and 18-7.  
D = Derivative (rate):  
• Used to account for how fast the error is changing,  
positively or negatively.  
• Active Input:  
Scalable Control:  
• Active Input can be selected from avail-  
able standard analog inputs or auxiliary inputs.  
Selected Active Input gets mapped to auxiliary  
output.  
• Minimum Input / Maximum Input:  
• These setpoints denes minimum and maxi-  
mum Input range for congured active input .  
• Minimum Output / Maximum Output:  
• Run Always:  
• These setpoints denes minimum and maxi-  
mum output. The Auxiliary output produces a  
linear value based on these settings.  
• “Run Always” option can be selected to en-  
able mapped auxiliary output irrespective of the  
compressor’s run state. If “Run Always” is not  
selected then the mapped auxiliary output is  
enabled only when compressor is running.  
• Trigger:  
• Trigger conguration is used to enable / dis-  
able auxiliary output according to the cong-  
ured trigger input. Trigger input can be selected  
from available standard analog inputs , auxiliary  
analog inputs or digital inputs. Trigger value  
and differential in combination with trigger  
type (“enable if above / On” or “enable if below /  
Off”) enables or disables auxiliary output.  
Control  
Auxiliary outputs can be PID Controlled or Scalable  
Controlled.  
PID Control:  
P = Proportional (gain):  
• Used to adjust the auxiliary output in direct propor-  
tion to the difference between the control setpoint  
and the active input . The proportional term is a unit  
less quantity and is used for coarse adjustment. This  
setpoint should be set to the lowest value that gives  
adequate control system response. Increasing the  
proportional setting increases the control system’s  
sensitivity to small process uctuations and the ten-  
dency to hunt.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
18 – 4  
Section 18 Auxiliary Input / Output  
Figure 18-4. Auxiliary I/O Screen - Analog Inputs (Page 4)  
Figure 18-5. Auxiliary I/O Screen - Analog Inputs (Page 5)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
18 – 5  
Section 18 Auxiliary Input / Output  
Figure 18-6. Auxiliary I/O Screen - Analog Outputs (Page 6)  
Figure 18-7. Auxiliary I/O Screen - Analog Outputs (Page 7)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
18 – 6  
Section 19 Configuration  
Press Units:  
Overview  
• Drop-down Box to select the pressure units. Psig, Bar,  
and Kpa are the possible selections and the units will  
be displayed for every pressure value throughout the  
screens.  
The conguration screen is where most of the Vission  
20/20 features are enabled and congured. The initial  
setup of the Vission 20/20 will generally start here, see  
Figure 19-1. Conguration Screen - Initial Setup (Page  
1). Depending on what is selected, different portions of  
the Vission 20/20 will be available to the operator.  
Order Num:  
• Identies the Order number of the purchase of the  
compressor. This Number will be needed If the opera-  
tor requires help from Vilter.  
Run Hours:  
Units  
• Offers the ability to change the compressor run  
hours. This is typically used when replacing an older  
micro controller on and existing compressor with a  
new Vission 20/20.  
This section sets how values will be represented through  
out the program.  
Temp Units:  
• Drop-down box to select the temperature units from  
Fahrenheit and Celsius. Once selected, all screen  
temperatures will be displayed in the chosen units.  
Figure 19-1. Conguration Screen - Initial Setup (Page 1)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
19 – 1  
Section 19 Configuration  
selected, the remainder of the serial setpoints will be  
available for editing.  
Time & Date  
Panel ID:  
This section sets the time and date of the Vission 20/20.  
Accurate time and date are accentual for accurate log-  
ging and troubleshooting. Setting these parameter will  
set the hardware clock embedded in the Vission 20/20  
CPU. If the time is not retained after powering down the  
panel, the operator should check and/or replace the coin  
style battery on the panel SBC behind the touchscreen.  
• Panel Identier used by the controller when commu-  
nicating with multiple panels.  
Port:  
• The Vission 20/20 has two ways to communicate on  
serial bus. Either via the built in serial port, P12, or  
through one of the USB ports. This drop-down box  
allows the operator to chose which one will be used.  
Format:  
• Selection to choose between 12 hour or 24 hours  
clock.  
Baud Rate:  
• Sets the Baud Rate for the serial communication.  
Hour:  
Data Bits:  
• Entry box to set the clock hours. AM or PM drop-down  
box will available if the 12 hour format is selected.  
• Fixed at 8 Data bits.  
Minute:  
Stop Bits:  
• Entry Box to set the clock minutes.  
• Identies the end of character for re-synchronizing.  
Second:  
Parity:  
• Entry Box to set the clock seconds.  
• Identies the type of error detection.  
Year:  
Ethernet:  
• Entry Box to set the current year.  
Month:  
• Enables the Ethernet port. Once selected, the re-  
mainder of the Ethernet setpoints will be available for  
editing.  
• Entry Box to set the current month.  
Day:  
Panel ID:  
• Panel Identier used by the controller when commu-  
• Entry Box to set the current date.  
nicating with multiple panels.  
IP Address:  
Communications  
• Entry box to set the IP address.  
Subnet Mask:  
The communication section is the control center for all  
communications to the Vission 20/20 panel. It is possi-  
ble to have multiple modes of communications enabled  
and used. However, only one mode can be used to con-  
trol the Vission 20/20 which is selected in the “Active  
Remote Control” drop-down box. For a complete list  
of communication registers, please refer to the Vission  
20/20 communication table.  
• Entry box to set the Subnet Mask.  
Gateway:  
• Entry box to set the Gateway address.  
Protocol:  
• Drop-down box to select the type of protocol used to  
remotely control the Vission 20/20.  
Active Remote Control:  
Touchscreen  
• Selects the mode of remote control. The operator  
can select between Direct I/O, Serial, or Ethernet.  
The “Calibrate” button changes the screen into touch-  
screen calibration mode. Calibrating the touchscreen  
is only required if the operator nds that the pointer ar-  
row no longer follows his nger. The calibration mode  
requires the operator to touch the four corners of the  
touchscreen and then the accept button.  
Direct I/O:  
• Enables the Direct I/O inputs. Once selected a pop-up  
will be displayed and the operator will need to choose  
a one of the three Direct I/O options  
Serial (Modbus RTU):  
• Enables the Serial Modbus RTU protocol. Once  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
19 – 2  
Section 19 Configuration  
Anti-Recycle  
Anti-Recycle denes the method of motor protection  
due to repeated motor starts. The operator has 3 choices  
of protection. Hot starts allows only a certain number of  
starts per hour before setting an hour to the anti-recy-  
cle timer. The number of starts is set in the timer page.  
Accumulative immediately adds time to the anti-recycle  
timer once the compressor is started and the time can  
be set in the timers screen. True anti-recycle adds to the  
anti-recycle timer once the compressor is shutdown. The  
motor of the compressor can not be restarted as long as  
there is anti-recycle time left and the operator can view  
this time on the top left corner of the main screen.  
Restart On Power Failure  
This feature of the Vission 20/20 offers the ability to de-  
ne how the Vission 20/20 will handle a power failure.  
This can also be useful to allow system controller to re-  
gain control of the Vission panel without the need for  
operator intervention.  
Always:  
• When selected, initiates a start after the panel pow-  
ers back up after a power failure, but only if the com-  
pressor was running before the power failure and  
starts the compressor in Auto mode.  
Never:  
• When selected, prevents any automatic action once  
the panel powers back up after a power failure.  
Timed:  
• When selected, initiates a start after the panel pow-  
ers back up after a power failure and the operator set  
timer runs out. When there are multiple compressor  
in a larger system, it is recommended that the opera-  
tor gives each compressor a different start times. A  
restart will only occur if the compressor was running  
before the power failure and starts the compressor in  
Auto mode.  
Remote Lock Off:  
• When selected, turns the remote lock out off when  
the panel powers up. Select this option if the opera-  
tor wishes a system controller to regain control of the  
Vission 20/20 without human interference.  
Boot in Remote (Direct I/O)  
• When selected, places the panel into remote mode  
when the panel powers up. Select this option when  
under direct I/O control and the system controller is  
to gain control of the Vission 20/20 without human  
interference.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
19 – 3  
Section 19 Configuration  
Compressor Name:  
Compressor Sequencing  
• Unique identier that is broadcasted to all other  
Vission 20/20 units in the sequencing network.  
The compressor sequencing is a feature of the Vission  
20/20 that allows the operator to setup as many as ve  
compressor to automatically start, stop and maintain  
system loads. The compressor that is designated as the  
master will monitor systems parameter and make deci-  
sions on how many compressor are required to meet the  
load as efciently as possible.  
Language  
Allows the operator to select the language in which all  
screens will be displayed in.  
Compressor Sequencing:  
Model & Refrigerant  
• Enables the compressor sequencing algorithms and  
allows access to the compressor sequencing screen.  
The values in this section provide the Vission 20/20 algo-  
rithm critical information on how to efciently and safely  
control the compressor, see Figure 19-2. Conguration  
Screen - Compressor Sequencing (Page 2).  
Master:  
• Identies the panel as the master while in sequencing  
control.  
Slave:  
Compressor:  
• Identies the panel as a slave while in sequencing  
• Dropdown box to select the compressor type. This  
control.  
Figure 19-2. Conguration Screen - Compressor Sequencing (Page 2)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
19 – 4  
Section 19 Configuration  
selection is critical for proper volume slide control.  
Model:  
Condenser Control  
The values in this section enables the condenser con-  
trol feature of the Vission 20/20. Once selected the  
checkboxes will become available for selection and the  
condenser control screen will be available via the menu  
screen. Some of the options check boxes in this section  
may not be available for selection unless the proper  
I/O cards are installed and enabled, see Figure 19-2.  
Conguration Screen - Page 2.  
• Drop-down box to select the compressor size. This  
selection is critical for proper volume slide control.  
Refrigerant:  
• Drop-down box to select the type of refrigerant. This  
selection is critical for proper volume slide control.  
Other (K-Factor):  
• Optional setting to adjust volume slide control.  
Ambient Sensor:  
Compressor Control  
• Enables the ambient temperature option for the con-  
denser control algorithm.  
Vilter compressors typically run in one of two control  
modes, suction pressure or process temperature con-  
trol, see Figure 19-2. Conguration Screen - Page 2.  
Wetbulb Sensor:  
• Enables the wetbulb temperature override option for  
the condenser control algorithm.  
VFD Fan:  
Suction Pressure Control:  
• Enables the VFD output option for the condenser  
control algorithm.  
• This denes the suction pressure input as the pro-  
cess variable and all controls will be based on suction  
pressure. The operator has the option to select up to  
two controllers where each can have its own set of  
setpoints.  
Oil Pump  
Process Temp. Control:  
This section denes how the Vission 20/20 will control  
the oil pump, see Figure 19-2. Conguration Screen -  
Page 2.  
• This denes the process temperature input as the  
process variable and all controls will be based on the  
process temperature. The operator has the option to  
select up to two controllers where each can have its  
No Pump:  
• Disables all functions for oil pump control.  
Cycling:  
own set of setpoints.  
• Enables option for cycling oil pump. Oil pump is cy-  
cled on and off depending on compressor differential  
pressure.  
Optional Function Selection  
The following options are additional features of the  
Vission 20/20 that can be selected. Some of these op-  
tions will not be available for selection unless the proper  
I/O cards are installed and enabled, see Figure 19-2.  
Conguration Screen - Page 2.  
Full Time:  
• Enables option for full time oil pump. Oil pump will  
always be running while the compressor is running.  
# Pumps:  
• Not currently used  
Oil Flow Control:  
Compressor VFD:  
• Enables the compressor motor VFD option.  
% Slide Volume Position:  
• Unused.  
• Enables option for oil ow control. Oil ow control  
will vary analog output for controlling danfoss valve  
opening % depending on capacity slide position. Oil  
ow control output will be regulated only when com-  
pressor is running, start condition is over i.e. low oil  
pressure timer is elapsed, pumpdown control opera-  
tion is not running and oil injection temperature is  
above oil injection temperature override setpoint. If  
any of the above condition is not satised, then oil  
ow analog output will be 4 mA which corresponds  
Economizer Pressure:  
• Enables the economizer pressure input.  
Superheat Monitor:  
• Enables the superheat safety algorithms.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
19 – 5  
Section 19 Configuration  
to 100 % valve open.  
Oil Cooling  
The section denes how the Vission 20/20 will monitor  
and/or control the temperature of the compressor oil,  
see Figure 19-2. Conguration Screen - Page 2.  
Thermosyphon:  
• This denes the compressor oil cooling method as  
thermosyphon.  
H20 Oil Cooler:  
• This denes the compressor oil cooling method as  
water heat exchange.  
Liquid Injection:  
• This denes the compressor oil cooling method as  
liquid refrigerant injection.  
Solenoids:  
• Enables the solenoid for liquid injection control.  
Motorized Valve:  
• Enables the motorized value for liquid injection con-  
trolled by PID settings.  
Remote Oil Cooler:  
• Denes the compressor oil cooling method as  
Remote Oil Cooler. Remote Oil Cooler vfd fan can  
be enabled when Auxiliary Output board is installed  
and enabled. Rest of the Remote Oil Cooler setpoints  
can be dened by navigating to Remote Oil Cooler  
Screen. Remote Oil Cooler and Condenser Control  
feature are mutually exclusive.  
Motor Current Device  
The Vission 20/20 can read the motor current in a couple  
of different ways. The following selections denes the  
method, see Figure 19-2. Conguration Screen - Page 2.  
Current Transformer:  
• This denes the input used for motor current when a  
current transformer is used.  
4-20ma Transformer:  
• This denes the input used for motor current.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
19 – 6  
Section 19 Configuration  
Digital Inputs  
The Vission 20/20 has several digital inputs that the op-  
erator can choose how the input will be used. Once an  
input is enabled, the Auxiliary I/O screen will be avail-  
able from the menu screen where the operator can  
further dene the inputs operation, see Figure 19-3.  
Conguration Screen - Digital Auxiliaries (Page 3).  
Enable Input #:  
• Enables the selected digital input.  
Set Name:  
• Allows the operator to assign a name to the input.  
Figure 19-3. Conguration Screen - Digital Auxiliaries (Page 3)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
19 – 7  
Section 19 Configuration  
Analog Inputs  
The Vission 20/20 has several Analog inputs that the  
operator can choose how the input will be used. Once  
an input is enabled, the Auxiliary I/O screen will be avail-  
able from the menu screen where the operator can  
further dene the inputs operation, see Figure 19-4.  
Conguration Screen - Analog Auxiliaries (Page 4).  
Enable Input #:  
• Enables the selected analog input.  
Set Name:  
• Allows the operator to assign a name to the input.  
Figure 19-4. Conguration Screen - Analog Auxiliaries (Page 4)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
19 – 8  
Section 19 Configuration  
Analog Outputs  
Digital Outputs  
The Vission 20/20 has several Analog outputs that the  
operator can choose how the outputs will be used. Once  
an output is enabled, the Auxiliary I/O screen will be  
available from the menu screen where the operator can  
further dene the outputs operation, see Figure 19-5.  
Conguration Screen - Analog Outputs (Page 5).  
The Vission 20/20 has several Digital outputs that the  
operator can choose how the output will be used. Once  
an output is enabled, the Auxiliary I/O screen will be  
available from the menu screen where the operator can  
further dene the outputs operation, see Figure 19-5.  
Conguration Screen - Page 5.  
Enable Output #:  
Enable Output #:  
• Enables the selected analog output.  
Set Name:  
• Enables the selected digital output.  
Set Name:  
• Allows the operator to assign a name to the output.  
• Allows the operator to assign a name to the output  
Figure 19-5. Conguration Screen - Analog and Digital Outputs (Page 5)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
19 – 9  
Section 19 Configuration  
Digital Input/Output 1:  
I/O Conguration  
• Enables the optional digital input/output card 1  
Digital Input/Output 2:  
If any additional I/O card are added to Vission 20/20, this  
is where these cards are enabled for use by the Vission  
20/20 algorithms. Some feature of the Vission 20/20  
will not be available unless specic expansions cards are  
selected, see Figure 19-6. Conguration Screen - I/O  
Conguration (Page 6).  
• Enables the optional digital input/output card 2  
Analog Input 1:  
• Not editable by the operator. Identies that the  
Analog Input card 1 is enabled.  
Analog Input 2:  
Digital Output 1:  
• Not editable by the operator. Identies that the  
• Not editable by the operator. Identies that the  
Analog Input card 2 is enabled.  
Digital Output card 1 is enabled.  
Analog Input 3:  
Digital Output 2:  
• Enables the optional Analog input card 3.  
Analog Input 4:  
• Not editable by the operator. Identies that the  
Digital Output card 2 is enabled.  
• Enables the optional Analog input card 4.  
Analog Output:  
Digital Input 1:  
• Not editable by the operator. Identies that the  
• Enables the optional Analog Output card.  
Digital Input card 1 is enabled.  
Figure 19-6. Conguration Screen - I/O Conguration (Page 6)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
19 – 10  
Section 20 Data Backup  
Refresh:  
Overview  
• The Refresh button is used to initiate a scan of the  
USB ports and list any devices found in the “Available  
Devices” window.  
The database backup screen provides the operator a  
way to extract information out of the Vission 20/20 for  
backup purposes or diagnostics, see Figure 20-1 Data  
Backup Screen. Through this screen, the operator can  
download all the Setpoint Databases, Maintenance Logs,  
Event Lists, Freeze Data, Trend Data and Compressor Run  
Hours to a portable USB ash drive. That information can  
then be uploaded back to the Vission 20/20 in the case  
of data corruption or to update the Vission program.  
Built in migrate function examines the previous setpoint  
databases, compares it with newer program setpoint da-  
tabase, and moves the old information into the new pro-  
gram. In addition, this screen also allows the operator to  
reset all values to the factory defaults.  
Save / Load  
Save / Load section is where the operator can either save  
the Vission 20/20 setpoints and log information to a  
USB ash drive or load from a USB ash drive back to the  
Vission 20/20.  
Save:  
• Selecting save allows the operator to save the Vission  
20/20 data to a USB ash drive using the information  
provided further down the screen. The bottom but-  
ton will be labeled “Save” when this is selected.  
All of the information saved to the USB ash drive is  
open information. Meaning none of the information is  
encrypted and the operator is free to examine it. The log  
les are all saved as simple ASCII text and the databases  
can be examined with SQLite.  
Figure 20-1. Data Backup Screen - Save/Load  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
20 – 1  
Section 20 Data Backup  
Load:  
• Selecting load allows the operator to load data from  
a USB ash drive to the Vission 20/20 using the in-  
formation provided further down the screen. The  
bottom button will be labeled “Load” when this is  
selected.  
Available Devices:  
• This window displays any USB ash drive plugged  
into one of the Vission 20/20 USB ports. Once one  
of the available devices is selected, then the drives  
contents will be displayed in the “Select Folder / File”  
window. If the USB ash drive that is plugged in by  
the operator is not showing up, then the operator  
can try pressing the “Refresh” button at the bottom  
of the screen. Unfortunately, not all USB ash drives  
are compatible with the Vission 20/20 and will never  
show up as available device.  
Select Folder/File:  
• This window displays the folders and les contained in  
the USB ash drive selected in the “Available Devices”  
window. The information from the Vission 20/20 will  
be contained into a .zip le. So a zip le will have to  
be selected to load or overwritten when saved. Once  
a zip les is selected, the name will be shown in the  
lename window.  
Unmount:  
• By pressing the Unmount button, any USB drive se-  
lected in the “Available Devices” window will be dis-  
connected from the operating system and can be  
safely removed from the USB port.  
Back:  
• The back button returns the operator to the preced-  
ing window display of les and folders.  
Filename:  
• This window is where the operator can give a name  
to a saved backup le. This eld will automatically be  
populated if a le is selected in the “Select Folder/  
File” window.  
Settings:  
• Using this table, the operator can choose to save or  
load all or part of the information contained in the  
Vission 20/20.  
Data Items:  
• Using this table, the operator can choose to save or  
load all or part of the information contained in the  
Vission 20/20 according to checkbox selections.  
Save / Load Button:  
• This button initiates the save or load process.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
20 – 2  
Section 20 Data Backup  
Migrate  
Factory Reset  
Loading data from an older version of the Vission 20/20  
software to a newer one can be complicated due to dif-  
ferences in databases. This migrate function closely  
examines each eld in the database being loaded and  
determines whether it can be used in the new program.  
The Migrate function is executed automatically when a  
data is loaded from a USB ash drive. The only time an  
operator should have to use the following migrate but-  
ton is if a new Vission 20/20 program is loaded over an  
existing Flash card, see Figure 20-2. Data Backup Screen  
- Migrate and Factory Reset.  
The Factory reset button offers the operator the ability  
to reset all the Vission 20/20 setpoints back to the facto-  
ry default settings or a specic database. If the operator  
nds that a screen will not load when selected, it is likely  
that the database associated with that screen has been  
corrupted. Unfortunately, data corruption is always a  
possibility in any system. So this function was designed  
to help the operator to regain control, see Figure 20-2.  
Data Backup Screen - Migrate and Factory Reset.  
Reset:  
• This button initiates the process to revert the Vission  
20/20 back to the factory default settings.  
Migrate:  
• This button initiates the migrate function.  
Figure 20-2. Data Backup Screen - Migrate and Factory Reset  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
20 – 3  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
20 – 4 / Blank  
Section 21 Maintenance  
Overview  
Maintenance Name:  
The maintenance screen is a convenient place to keep  
track of the the maintenance performed and any up-  
coming maintenance recommended by Vilter. Based on  
this page, banners will be displayed on the lower status  
bar. Yellow banners are to warn the operator of any up-  
coming maintenance and red banners indicate mainte-  
nance that is overdue.  
• This column of tasks that should be performed at the  
run hours indicated in Maintenance interval column.  
Select the checkbox from the maintenance task name  
and press “update” button to perform the sign-off.  
Maintenance Interval (Hours):  
• This column indicates the Run hours at which the task  
in the rst column should be performed. When a task  
is selected, the maintenance interval will change to  
reect the next interval.  
Checklist  
Time Remaining (Hours):  
The check list is where the operator will perform the  
maintenance sign-off, see Figure 21-1. Maintenance  
Screen - Checklist. Once the operator has selected the  
item to sign off, pressing the “Update” button at the  
bottom of the page will perform the sign-off operation  
and list the maintenance performed in the maintenance  
log.  
• This column indicates the Run hours left before the  
maintenance task should be performed.  
Figure 21-1. Maintenance Screen - Checklist  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
21 – 1  
Section 21 Maintenance  
Time:  
Notes  
• Lists the time the maintenance task was performed.  
User:  
The notes tab allows the operator to make notes to any  
other personnel that might have access to the Vission  
20/20.  
• Lists the operator name who performed the mainte-  
nance task.  
Maintenance Performed:  
Log  
• Lists the maintenance task that was performed.  
Run Hours:  
The maintenance log tab lists all the maintenance  
tasks performed in descending order, see Figure 21-2.  
Maintenance Screen - Log.  
• Lists the run hours at which the maintenance task  
was performed.  
Date:  
Chart  
• Lists the date the maintenance task was performed.  
This chart is the original maintenance chart that is pro-  
vided with the compressor, see Figure 21-3. Maintenance  
Screen - Chart.  
Figure 21-2. Maintenance Screen - Log  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
21 – 2  
Section 21 Maintenance  
Figure 21-3. Maintenance Screen - Chart  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
21 – 3  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
21 – 4 / Blank  
Section 22 User Access  
calibrating instrument will be available to an opera-  
tor with this level of access.  
Overview  
• Level 3 – This is considered a contractor level of ac-  
cess. The setpoints available at this level have the  
most potential of causing damage to the compressor.  
Therefore, this access is restricted to those only with  
the highest level of competence.  
The user access screen is where all operators go to log  
in. In the Vission 20/20, each screen has a security level,  
whereby allowing operators, technicians and/or supervi-  
sors the ability to modify different sets of setpoints. The  
Vission 20/20 has four levels of security, see Figure 22-1.  
User Access Screen - Login.  
The user access screen is also where new operators are  
added, changed or removed. Any operator can add an  
additional operator but can only add an operator of less-  
er or equal security level.  
• Level 0 – This is the default level with no operator  
logged in. The function available to the operator are  
very limited and basically only allows someone to  
start and stop the compressor.  
Apply  
• Level 1 – This is a technician level of access. All the  
setpoints needed to operate and adjust the perfor-  
mance of the compressor will be available to an op-  
erator with this level of access.  
When selected, applies the user name and password  
for security evaluation. If the User name and password  
matches an existing user then the operators name will  
be applied to the lower status bar and the operator will  
be given access to screens of equal security level.  
• Level 2 – This is a supervisor level of access. Setpoints  
that require a higher level of knowledge such as  
Figure 22-1. User Access Screen - Login  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
22 – 1  
Section 22 User Access  
password can be entered by touching the password  
entry box and entering the password via the pop-up  
keyboard.  
Login  
The login tab is where an operator will enter the users  
name and password in order to gain access to Vission  
20/20 screens.  
Manage Accounts  
Operators:  
This tab allows the addition, removal, and modication  
of authorized users, see Figure 22-2. User Access Screen  
- Manage Accounts.  
• All operators that have been added to the Vission  
20/20 user tables will be displayed in this window. If  
a name of an operator is selected from this window,  
the name is added to the “Operator Name” entry box.  
Operators:  
Operator Name:  
• This window contains the list of authorized users al-  
ready added to the Vission 20/20. Selecting a name  
from this list will add that name to the “Operator  
Name” entry box.  
• This entry box is for the operator’s username. The  
operator can either select the username from the op-  
erators window or enter the username manually by  
touching the entry box and entering the name via the  
pop-up keyboard.  
Operator Name:  
• This entry box is for the operator’s username who is  
Operator Password:  
to be added, removed or modied. The operator can  
• This entry box is for the operator’s password. The  
Figure 22-2. User Access Screen - Manage Accounts  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
22 – 2  
Section 22 User Access  
either select the username from the operators win-  
dow or enter the username manually by touching  
the entry box and entering the name via the pop-up  
keyboard.  
Add / Update:  
• Pressing this button will initiate the creation or modi-  
cation of the specied account.  
Delete:  
Operator Password:  
• Pressing this button will delete the specied account.  
• This entry box is for the operator’s password. The  
password can be entered by touching the password  
entry box and entering the password via the pop-up  
keyboard.  
VNC Account  
Verify Password:  
Vission 20/20 panels can be accessed remotely by us-  
ing a VNC client over TCP/IP network. This tab allows  
the operator to change default VNC Password and VNC  
Port number, see Figure 22-3. User Access Screen - VNC  
Accounts.  
• This entry box is to verify the operator’s password.  
Verifying the password can be entered by touching  
the “Verify Password” entry box and entering the  
password via the pop-up keyboard.  
Security Level:  
Change VNC Password  
New Password:  
• Select a security level for the account being added or  
modied. Only levels that are equal to or less than the  
operator’s own security level will be shown.  
• The operator will add the password by touching the  
entry box and typing the password via the pop-up  
keyboard.  
Figure 22-3. User Access Screen - VNC Accounts  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
22 – 3  
Section 22 User Access  
Verify New Password:  
Update:  
• The operator will re-enter the password by touching  
the entry box and typing the password via the pop-  
up keyboard.  
• Pressing this button will initiate the modication of  
the specied VNC account Port number.  
Update:  
Screen Security Levels  
• Pressing this button will initiate the modication of  
the VNC account.  
The following table lists all screen and their base securi-  
ty levels, see Table 22-1. Security Access Levels. The ma-  
jority of the screens have more than one security level.  
The base security level gives the user access to the set-  
points that can change to performance of the compres-  
sor. The secondary security level is typically level 3 and is  
reserved for those setpoints that require great care and  
knowledge of the system in order to change safely.  
Change VNC Port Number  
Port Number:  
• The operator will change the port number for VNC  
server by touching the entry box and typing via the  
pop-up keyboard. Default port number is 5900.  
Operator can assign port number ranging between  
5900 to 6000.  
Table 22-1. Security Access Levels  
Security Access Levels  
User Level  
Level 0  
Page  
*Note  
Event List  
-
Input/Output States  
Trend Chart  
Level 0  
-
Level 0  
-
Help  
Level 0  
-
Alarms & Trips  
Level 1*  
Level 1  
Level 3 required for constraints  
Compressor Scheduling  
Compressor Sequencing  
Condenser Control  
Compressor Control  
Maintenance  
-
Level 1  
-
Level 1*  
Level 1*  
Level 1  
Level 3 required for constraints  
Level 3 required for constraints  
-
Data Backup  
Level 1*  
Level 2  
Level 3 required to upload data  
Instrument Calibration  
Service Option  
Conguration  
-
Level 2  
-
Level 2*  
Level 2  
Level 3 required for pages 3 - 6  
-
Slide Calibration  
Timers  
Level 2*  
Level 3  
Level 3 required for constraints  
VNC Account  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
22 – 4  
Section 23 Help Screen  
connected USB drive, the names will be listed in this  
section. The operator will have to navigate through  
the le structure of the USB drive to nd the docu-  
ments. The top box in the USB drive will display any  
USB drives mounted to the Vission 20/20 OS.  
Overview  
Use this screen to receive help on other setpoint screens  
contained within the software. These help les can be ac-  
cessed from any screen. The help les describe the func-  
tionality of that screen as well as compressor operation.  
• Touching one of the listed USB devices will select that  
device and list any les or PDF documents contained  
on the USB drive. Selecting a folder will open that  
folder and display any sub-folders of PDF documents.  
Screen Features:  
Unmount:  
Manual Tab:  
• Pressing the unmount button will disconnect the USB  
drive from the Vission 20/20 operating system. Once  
the device has been remove from the device list, the  
USB drive can be safely removed  
• Contains the list of available manual sections to be  
displayed in the display window, see Figure 23-1.  
Help Screen - Manual.  
Refresh:  
USB tab:  
• Pressing this button will reread the USB ports and dis-  
play any new USB drives.  
• The operator as the option to view other manuals,  
typically Vilter compressor manuals on the Vission  
20/20 from a USB drive, see Figure 23-2. Help Screen  
- USB. If there are any PDF type documents on a  
Figure 23-1. Help Screen - Manual  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
23 – 1  
Section 23 Help Screen  
Back:  
Previous:  
• Pressing the back button will rewrite the le/folder  
• Changes the page in the display window one page  
less then what was showing.  
list with the previous folder level.  
Display Window:  
Next:  
• This window displays the context of the manual.  
Fullscreen:  
• Changes the page in the display window one page  
more then what was showing.  
Version:  
• Pressing this button expand the display window to t  
the entire screen.  
• Pressing the Version button displays a pop-up screen  
that gives the operator information of the version of  
software running on the Vission 20/20, see Figure  
23-3. Version Pop-Up Screen.  
Page:  
• Enter the page number the operator wishes to be dis-  
played in the display window.  
Figure 23-2. Help Screen - USB  
Figure 23-3. Version Pop-Up Screen  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
23 – 2  
Section 24 Twin Screw Control  
• Standard - Selects the oil pump operation as  
“Full Time”.  
Overview  
• Stal - Selects the oil pump control as “No  
pump”.  
The Vission 20/20 is capable of operating a twin screw  
compressor from a number of different manufacturers.  
The Vission 20/20 currently operates as a twin screw  
controller in the full time oil pump and the no oil pump  
conguration.  
Menu Changes:  
• When selecting the twin screw option there will be  
other changes that occur in other menu pages.  
Setup - Conguration Screen  
• Volume position indicator will disappear from  
the main screen and right data panel.  
Conguration Screen:  
• Prelube oil pump alarms and trip values will  
be changed to default values for the twin screw  
• To setup the Vission 20/20 panel for twin screw, navi-  
gate to the Conguration Screen, page 2, and select  
“VRS” from the dropdown box label “Compressor”,  
see Figure 24-1. Twin Screw Control Screen. Once  
selected, another dropdown box labeled “Operation  
Type” will appear directly below the “Compressor”  
drop-down box. You should also notice that the oil  
pump control becomes grayed out because the oil  
pump operation is now determined by the type of  
compressor that is select from the “Type” drop-down  
box.  
• Run oil pump alarm and trip values will be  
changed to default values for the twin screw.  
Figure 24-1. Conguration Screen - Twin Screw Option  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
24 – 1  
Section 24 Twin Screw Control  
24-2. Slide Valve Calibration - Twin Screw Control.  
“-” Button:  
Operation  
Once the twin screw is congured, its operation is  
very similar as the single screw and all options that  
are available for single screw conguration are also  
available for twin screw. The only operational differ-  
ence is the manual mode of operation. Twin screw  
compressors can experience leaky slide seals that can  
cause the capacity slide to drift after it has been po-  
sitioned by the controller. To counteract the capacity  
slide drift problem, the twin screw manual mode op-  
eration has an added anti-drift feature that automati-  
cally maintains the position of the hydraulic actuator.  
• When the operator presses and holds this button,  
the output associated with capacity slide decrease  
is energized. If the actuator does not turn in the cor-  
rect direction when this button is pressed, then the  
operator will have to alter how the actuator is wired  
to the panel.  
“+” Button:  
• When the operator presses and holds this button,  
the output associated with capacity slide increase is  
energized. If the actuator does not turn in the cor-  
rect direction when this button is pressed, then the  
operator will have to alter how the actuator is wired  
to the panel.  
Slide Calibration - Capacity Slide Valve  
Potentiometer  
Software limit setpoint:  
• The Vission 20/20 uses the “Min Limit” and “Max  
Limit” setpoint to dene an area within the mechani-  
cal stops for normal slide travel. These software limits  
purpose is to prevent the slide from actually hitting  
the mechanical stops which could result in a number  
of undesirable consequences. By default, the soft-  
ware limits are set to 150mV from either end point.  
This section provides critical information and control pa-  
rameters related to the capacity slide actuator. The “%  
cap” display shows the actual value in percent of the ca-  
pacity slide with out any conditioning that might be ap-  
plied to the other capacity position displays. In addition,  
this section displays the value of the actuator signals  
in millivolts in the “input Value” display box, see Figure  
Figure 24-2. Slide Calibration - Twin Screw Control  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
24 – 2  
Section 24 Twin Screw Control  
The position percentage is calculated from the soft-  
ware limits. Therefore, it is possible to read a value  
greater than 100% or less than 0% if inertial carries  
the slides after these limits are reached.  
Compressor Bump Pop-Up Window  
• This window allows the operator to bump the com-  
pressor to ush out any oil in the compressor after  
a slide valve calibration, see Figure 24-3. Slide Valve  
Calibration - Twin Screw Bump Pop-Up Window.  
Position Signal Type:  
• Position signals can be 0-5 VDC or 4-20mA to indi-  
cate current slide valve position.  
Figure 24-3. Slide Calibration - Twin Screw Bump Pop-Up Window  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
24 – 3  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
24 – 4 / Blank  
Section 25 Cool Compression Control  
injection line into the suction chamber of the compres-  
sor. This oil and liquid provides lubrication and cooling  
until full pressure differential lubrication is attained. As  
the differential pressure increases, the oil and liquid am-  
monia is now injected into the screw during the com-  
pression process and the oil injection valve is allowed to  
close.  
Overview  
The cool compression compressor operation is similar  
to the standard single screw compressor units, except  
there is no external oil cooler to the unit. A blanket of  
liquid ammonia lies on top of the oil in the oil separa-  
tor. The liquid ammonia level is regulated by sensing  
the liquid ammonia level with a level probe, and using  
a positioning valve to vary the amount of liquid ammo-  
nia being added to the separator. The cooling occurs  
through the entire compression and separation process.  
The Cool Compression compressor does not have an oil  
pump. When the Cool Compression compressor unit is  
commanded to start, the control panel rst insures that  
the slide valves are at their minimum positions. The suc-  
tion oil injection solenoid (SOI) is energized – allowing a  
path for oil to ow into the compressor. The compressor  
now starts. There is an initial pressure drop in the suc-  
tion chamber of the compressor and a corresponding  
increase in pressure on the discharge of the compres-  
sor. This creates a pressure differential that forces the  
oil and liquid ammonia mixture through the suction oil  
Setup  
Conguration Screen:  
• TosetuptheVission20/20panelforCoolCompression,  
rst ensure that an analog output card is installed in  
the panel, and it is selected from page 6 of the con-  
guration screen, see Section 19. Navigate to cong-  
uration page 2, and select “R717-Cool Comp” from  
the drop-down box that is labeled “Refrigerant”,  
see Figure 25-1. Cool Compression Control Screen.  
Once selected “Cool Compression” option will ap-  
pear in Oil Pump and Oil Cooling sections and “Cool  
Compression” gets selected automatically. It will also  
Figure 25-1. Cool Compression Control Screen  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
25 – 1  
Section 25 Cool Compression Control  
enable Superheat Monitoring on the screen.  
• As previously described, Cool Compression  
compressor does not have an oil pump. Instead  
it has a suction oil injection solenoid to pro-  
vide oil and liquid ammonia for lubrication and  
cooling.  
Auto Load  
• Auto load operation will force the compressor to  
load to a minimum value once the compressor has  
started. By loading the compressor to a minimum  
value, and maintaining this capacity, a pressure ratio  
is created across the compressor, to ensure adequate  
lubrication of the compressor, and also that the com-  
pressor does not experience high discharge super-  
heat conditions. Since compressor lubrication is of  
great importance, all load limiting is disabled when  
auto load is engaged.  
• Cool Compression liquid injection 1 and liq-  
uid injection 2 outputs will operate as high / low  
pressure ratio solenoid outputs.  
Control Functions  
• Auto Load at Start  
In the Compressor Control Menu, special cool compres-  
sion control functions are now available, see Figure 25-2.  
Compressor Control Screen - Cool Compression Control  
(Page 4). These new functions are:  
• Denes the value at which Compressor (ca-  
pacity slide) should be loaded (and maintained)  
at start if Auto Load is enabled.  
• Auto Load Timer  
• Auto Load  
• This timer denes the maximum time that  
the Auto Load operation will be engaged. After  
the timer expires, Auto Load will be disengaged.  
• Suction Oil Injection Settings  
• Danfoss Positioning Valve Settings  
Figure 25-2. Compressor Control Screen - Cool Compression Control (Page 4)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
25 – 2  
Section 25 Cool Compression Control  
• Auto load will be disengaged when one of the follow-  
ing conditions occur;  
Using a Positioning Valve for Liquid Ammonia Level  
Control  
• Pressure ratio reaches a value of 2.0 or  
greater.  
• A level probe inserted in the oil separator detects  
liquid ammonia level. Based on the level of the am-  
monia (0-100%), the level probe sends a directly pro-  
portional 4-20 mA signal to the Vission 20/20 panel.  
The positioning valve is then positioned based on the  
Positioning Valve settings graph shown in Figure 25-  
2. Cool Compression Control Functions Screen.  
• Compressor has been running for 10 minutes  
(dened by Auto Load Timer).  
• Suction pressure setpoint has been reached.  
• Looking at the graph, when the compressor starts,  
the positioning valve placement (Vertical Axis) is de-  
termined based on the liquid ammonia level that is  
sensed in the oil separator (Horizontal Axis). It can  
be seen that as the liquid ammonia level increases  
(corresponding to a larger mA value), the positioning  
valve moves towards a closed position.  
Suction Oil Injection Setting  
• In order to maintain adequate lubrication during low  
pressure ratio conditions, the Suction Oil Injection  
(SOI) solenoid is turned ON and the capacity of the  
compressor is reduced.  
• The SOI solenoid will cycle ON and OFF based on the  
pressure ratio across the compressor.  
• The Positioning Valve position (0-100% limits) is de-  
• SOI Solenoid ON  
ned at three distinct levels;  
• Denes the Pressure ratio value at which  
SOI is turned ON (default 2.00) (Digital Output  
Board #1:2).  
• Start Level (lowest liquid ammonia level - po-  
sitioning valve at maximum open position).  
• Leakage (normal operating position and am-  
monia level).  
• SOI Solenoid OFF  
• Denes the Pressure ratio value at which SOI  
is turned OFF (default 2.04) (Digital Output  
Board #1:2).  
• Overll Leakage (highest liquid ammo-  
nia level–positioning valve at minimum open  
position).  
• SOI Load Limit  
• Denes the capacity slide position at which  
the compressor capacity slide will unload to if  
pressure ratio falls below “SOI Solenoid ON” set-  
point. This setpoint is not active until Auto Load  
disengages.  
• Liquid ammonia levels are dened at four distinct lev-  
els (4-20ma limits);  
• Start SP (minimum liquid ammonia level in  
separator – the positioning valve is maximum  
open).  
• The SOI solenoid will also cycle on if the discharge  
temperature superheat reaches a value of 5°F (this  
value is not settable). Generally, anytime the SOI  
solenoid cycles on, the capacity is limited to the SOI  
Load Limit setpoint. However, this is not true if the  
SOI solenoid cycles on based on the discharge tem-  
perature superheat 5°F rule. If discharge temperature  
superheat continues to climb and reaches a value of  
6°F, the compressor will be inhibited from loading. If  
discharge temperature superheat still continues to  
climb and reaches a value of 8°F or more, then the  
compressor will be unloaded until the superheat  
drops below 8°F or the capacity has reached the SOI  
Load Limit setting.  
• Linear SP (minimum level of liquid ammonia  
for normal operating position).  
• Upper SP (maximum level of liquid ammonia  
for normal operating position).  
• Max SP (maximum liquid ammonia level – po-  
sitioning valve is minimum open position, main-  
taining some leakage).  
• On Alarms and Trips screen, Low Oil Separator Start  
Temperature, High Filter Diff Start Pressure settings  
are disabled.  
• On Timers screen Oil Level #1 Safety Trip Delay, Oil  
Level #2 Safety Trip Delay settings are disabled.  
Operational Differences from Single Screw  
Once the Cool Compression is congured, most setup  
options available for a single screw are also available  
for Cool Compression. However, there are signicant  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
25 – 3  
Section 25 Cool Compression Control  
operational differences that are mostly associated with  
the compressor safeties:  
5.0, the solenoid is turned on. When the pressure ra-  
tio falls back to below 4.8, the solenoid is turned off.  
1. The Cool Compression program ignores,  
• Low Oil Separator Alarm / Trip at start  
• High Filter Differential at start  
Level Switches  
• There are two level switches in the oil separator, a  
“high” and a “low”. During normal running opera-  
tion, the oil level is above both switches. When the oil  
level starts to drop and opens the high level switch,  
a 10 minute timer starts. When the timer elapses a  
ashing “add oil to middle of sight glass” message ap-  
pears on the main screen. When the operator adds  
enough oil to close the high level switch, the mes-  
sage disappears.  
• Prelube Oil Pressure Alarm and Trip  
• Run Oil Pressure Alarm and Trip (Pressure  
Ratios are monitored instead).  
• High Discharge Temp Alarm and Trip  
(Discharge Temp Superheat is monitored)  
• Low Suction Temp Alarm and Trip  
• Low Oil Injection Temp Alarm and Trip  
• High Oil Injection Temp Alarm and Trip  
NOTICE  
2. SOI solenoid is forced on for rst 60 seconds of run-  
ning and 10 minutes after compressor is stopped.  
If oil is not added and the oil level continues to drop  
thereby opening the “low” oil level switch, a 10 minute  
timer starts again. When the timer elapses, the com-  
pressor shutdowns immediately and displays “Low Oil  
Level” failure. If enough oil is added to close the low  
level switch, then this will allow the opeator to press the  
reset button and clear the “Low Oil Level” failure and  
“Add Oil” message.  
3. Auto Load Enabled: When Auto Load is engaged at  
start, it then maintains the position of capacity slide to  
the Auto Load limit (approx : 30 %, but less than 50 %).  
It displays status message “Cool Compression Capacity  
Hold” when it is running. Unless Auto load is disengaged  
compressor will run at auto load limit position. Auto load  
disengages if enough Pressure Ratio is built (typically  
more than 2.04) or setpoints are achieved.  
Oil Level Messaging After Compressor Stops  
4. SOI Solenoid: During normal operation if pressure ra-  
tio drops to a lower value (typically below 2.00) then it  
energizes SOI solenoid and maintains the position of ca-  
pacity slide to the SOI Load limit (approx : 30 %, less than  
50 %). It also displays status message “Cool Compression  
Capacity Hold”. If enough Pressure Ratio is built across  
the compressor (typically more than 2.04), it again re-  
sumes the run mode and control normally.  
• The low level switch is monitored after the compres-  
sor stops. If the switch opens after the compressor  
stops, a two minute timer starts. If the switch stays  
open, and the timer expires, a failure is generated  
called “Lo Oil Level Fail after Stop” and the compres-  
sor is disabled from restarting until oil is added to  
close the low level switch. Note that this failure is  
generated ONLY when the low level switch opens af-  
ter the compressor stops.  
5. It performs Cool Compression specic checks periodi-  
cally like:  
• Controlling the liquid level positioning valve  
as liquid ammonia level changes .  
• Low / high Pressure Oil Injection ports control  
as Pressure Ratio and Superheat temperature  
changes.  
Supplemental Oil Cooling Solenoids  
• Some cool compression units will have supplemental  
oil cooling solenoids. One is called the suction liquid  
injection solenoid and is controlled via discharge su-  
perheat. When the discharge superheat reaches 5°F,  
the solenoid is turned on. When it falls back to below  
4°F, the solenoid is turned off. An additional solenoid  
(referenced as SV4 – as called the High Press Ratio  
solenoid) provides supplemental oil cooling based on  
pressure ratio. When the pressure ratio rises above  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
25 – 4  
Section 26 Remote Oil Cooler  
Overview  
Remote Oil Cooler Setpoint  
This screen allows the operator to view and adjust  
Remote Oil Cooler setpoint settings associated with  
Remote Oil Cooler operation, see Figure 26-1. Remote  
Oil Cooler Screen (Page 1). This screen will only be ac-  
tive if the Remote Oil Cooler Control option has been  
enabled from the Conguration Screen, see Section 19.  
Run Mode:  
• Run Mode allows the selection of different modes of  
operation for Remote Oil Cooler. The choices for se-  
lection are;  
Run Never  
• The mode of operation by default. Remote Oil Cooler  
operation will not be performed when this mode is  
active.  
The Remote Oil Cooler Control operation allows the cy-  
cling of fans and pumps in order to maintain a specic  
Remote Oil Cooler Temperature. The ve different steps  
in step control allow selection of fans, pumps and VFD  
in one or more steps. When a VFD is employed, VFD is  
allowed to reach maximum speed, then if additional ca-  
pacity is needed, the next fan or pump is brought on.  
The VFD will modulate down and then back up to 100%  
again, then the next fan or pump is brought on. This  
method allows the smoothest Remote Oil Cooler control  
by spacing the VFD between the fan and pump steps,  
while maintaining a Remote Oil Cooler Temperature  
pressure that matches the setpoint.  
Run With Comp  
• Automatic operation of Remote Oil Cooler selected  
when cooling control is required to only run when the  
compressor is running.  
Run Always  
• Automatic operation of Remote Oil Cooler selected  
when cooling control is required to run even when  
the compressor is off.  
Figure 26-1. Remote Oil Cooler Screen (Page 1)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
26 – 1  
Section 26 Remote Oil Cooler  
Manual  
setpoint and the delay timers are satised. Step Delay  
acts as “ON” timer while loading and acts as “OFF”  
timer while unloading for the same step.  
• Mode for controlling Remote Oil Cooler operation  
manually. Operator controls the operation by manual  
stepping using an on/off toggle button at each step.  
Low Speed Fan:  
Remote Oil Cooler Temperature:  
• Allows steps to have option for time delay in case of  
fan spin down. Any of Out #1 to Out #4 can be se-  
lected as Low Speed Fan through combobox. E.g.:  
Let’s say Out #2 is selected as Low Speed Fan in Step  
2. When step 2 becomes active during Remote Oil  
Cooler operation which is after Step 2 timeout de-  
lay, Out #2 is left off for time as set by the operator  
in High to Low Speed Delay. After low speed fan ener-  
gizes, then timer for Step 3 starts timing.  
• This is the read only parameter and it displays the  
present value of Remote Oil Cooler Temperature.  
Remote Oil Cooler Temperature is mapped on Analog  
Auxiliary Input #5.  
Remote Oil Cooler Temperature Setpoint:  
• This is the Remote Oil Cooler Temperature setpoint  
that needs to be maintained.  
Control:  
Upper Deadband:  
• Toggle any of the steps On/Off during Manual opera-  
tion of Remote Oil Cooler. This button is active only  
when Run Mode selected is Manual. During Auto op-  
eration of Remote Oil Cooler Control, control button  
• This is the Remote Oil Cooler Temperature setpoint  
upper deadband value.  
Lower Deadband:  
• This is the Remote Oil Cooler Temperature setpoint  
lower deadband value.  
for active step will be “ON”.  
High to Low Speed Fan Delay:  
VFD Settings  
• This is time delay for fan spin down in case of 2 speed  
motor/dual speed fan.  
This page is active only when Remote Oil Cooler VFD is  
selected in Conguration Screen, see Section 19. For  
Remote Oil Cooler VFD Screen, see Figure 26-2. When a  
VFD fan is used for the remote oil cooler oil cooling, the  
speed of the VFD is controlled using PID algorithm.  
Step Control  
The Step Control allows the operator to setup the man-  
ner in which Fans, Pumps & VFD will be turned on/off.  
Fans & Pumps are connected on digital outputs Out #1  
to Out #4. VFD Fan is connected on Analog Output. Each  
step can have maximum of ve outputs connected to it.  
Each step can be opted in or out depending on enabling  
of checkbox.  
P = Proportional (gain):  
• Used to adjust the fan speed action in direct propor-  
tion to the difference between the control setpoint  
and the process variable (SP - PV = error). The pro-  
portional term is a unit less quantity and is used for  
coarse adjustment. This setpoint should be set to the  
lowest value that gives adequate control system re-  
sponse. Increasing the proportional setting increases  
the control system’s sensitivity to small process uc-  
tuations and the tendency to hunt.  
When Run Mode is Auto and Remote Oil Cooler  
Temperature rises above upper deadband, Remote Oil  
Cooler step gets incremented from Step 1 to Step 5 and  
hence switching on/off Pumps, Fans & VFD connected on  
outputs. This holds true for decrementing of steps from  
Step 5 to Step 1 when Remote Oil Cooler Temperature  
falls below lower deadband.  
I = Integral (reset):  
• Used to adjust the capacity control action, integrat-  
ing the error over time, to account for a small error  
that has persisted for a long time. This quantity is  
used for ne adjustment. This setpoint is used to  
smooth out process variations. This setpoint should  
be set high enough to prevent hunting but not too  
high or it will cause control system overshoot.  
Step Delay:  
• Allows operator to set time delays between Remote  
Oil Cooler steps. Remote Oil Cooler Temperature  
must be outside upper or lower deadband continu-  
ously for delay time in order to increase or decrease  
Remote Oil Cooler steps. While in a VFD step, an ad-  
ditional step can only be added once VFD has reached  
its maximum speed setpoint and the delay timers are  
satised. Similarly in a VFD step, a step can only be  
removed once VFD has reached its minimum speed  
D = Derivative (rate):  
• Used to adjust the capacity control action, account-  
ing for how fast the error is changing, positively or  
negatively.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
26 – 2  
Section 26 Remote Oil Cooler  
Maximum Speed:  
Minimum Speed:  
• This setpoint denes the maximum speed in per-  
centage for Remote Oil Cooler VFD Fan at which it  
should run for continuous step delay time to increase  
Remote Oil Cooler steps. E.g. let’s say setpoint is kept  
at 95%. Then Remote Oil Cooler VFD fan will have to  
run at speed of 95% or more to advance to next step.  
Maximum Speed can be set as 100%, which is when  
analog output (at which Remote Oil Cooler VFD fan  
is connected) reaches to 20mA in its normal range of  
4-20 mA  
• This setpoint denes the minimum speed in percent-  
age for Remote Oil Cooler VFD Fan at which it should  
run for continuous step delay time to decrease  
Remote Oil Cooler steps. E.g. let’s say setpoint is kept  
at 5%. Then Remote Oil Cooler VFD fan will have to run  
at speed 5% or less to advance to next step. Minimum  
Speed can be set as 0%, which is when analog output  
(at which Remote Oil Cooler VFD fan is connected)  
reaches 4mA in its normal range of 4-20 mA  
Figure 26-2. Remote Oil Cooler VFD Screen (Page 2)  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
26 – 3  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
26 – 4 / Blank  
Appendix A Vission 20/20 Troubleshooting Guide  
Vission 20/20 Troubleshooting Guide  
In the event of a problem with the Vilter Vission 20/20, the help screen, along with your electrical drawings will help  
determine the cause.  
NOTICE  
Before applying power to the Vission 20/20 control  
panel, all wiring to the panel should be per the  
National Electrical Code (NEC). Specically check for  
proper voltage and that the neutral is grounded at  
the source. An equipment ground should also be run  
to the panel.  
Table A. Vission 20/20 Troubleshooting Guide  
Problem  
Solution  
Vission 20/20 does not boot up, no Check that 120VAC is run to circuit breaker CB1 located on the terminal  
lights light on any boards.  
strip. The neutral should be brought to any “N” terminal on the terminal  
strip.  
Check that circuit breaker CB1’s switch is in the ON position.  
Use a voltmeter to insure 120VAC is being applied to the power supply,  
located on the door. Check that 120 volts is present at the F1 fuse on the  
power supply, located on the front of the door. If all of the above are OK,  
the power supply may be bad. To test the power supply, check DC voltages  
at the power supply output. If proper voltages are not found at these test  
points, the power supply may be faulty.  
Vission 20/20 appears to be boot- Remove power COMPLETELY from the Vission 20/20 and restart the  
ed, lights are lit on the boards, but controller.  
no touchscreen display is evident:  
WARNING  
The inverter board creates a high rms voltage to drive  
the backlight - it can exceed 1500VAC. Use extreme  
caution and insure that voltage has been removed  
from the board before physical inspection. Visually  
check cable connections located on the LCD inverter  
board. This board is located inside the door on the  
LCD touch screen back plane next to the single board  
computer. Physically inspect board to insure that  
all cable connectors are connected tightly to the  
board connectors. If these are inserted correctly,  
the problem could be a bad LCD inverter board or a  
component failure.  
Vission 20/20 boots up but all data Check analog board jumpers to insure proper node addresses are set up  
temperatures and pressures are ze- on all boards. Physically inspect power and communication jumper ca-  
roed and do not update.  
bles to insure they are inserted properly and completely. Two LEDs on all  
boards show the status of the communications for the board. LED1 is on  
when a command is received at the board from the single board computer  
(SBC), and LED2 is on when a response is sent from the board to the SBC.  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
A - 1  
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9  
A - 2 / Blank  
35391SC 1.9 (1/13) Emerson and Vilter are trademarks of Emerson Electric Co. or one of its afliated companies. © 2012 Emerson Climate Technologies, Inc. All rights reserved. Printed in the USA.  

Savin 9450 User Manual
Samsung Tad 798 User Manual
Samsung Split Type Room Air Conditioner User Manual
Samsung Scx 6220 User Manual
Precisionaire Series 425t Cube User Manual
Philips Sbcsc363 User Manual
Omega Ftb500 User Manual
JVC CS FX502 User Manual
BLACK DECKER GT220 User Manual
ACER CZ340CK User Manual